Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2024-07-03 12:20:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2721.34 | 546.22 | 546.22 |
Net Site Energy | 2721.34 | 546.22 | 546.22 |
Total Source Energy | 8618.50 | 1729.86 | 1729.86 |
Net Source Energy | 8618.50 | 1729.86 | 1729.86 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 13.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 847.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 236.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 262.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2721.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 13.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 847.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 236.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 262.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 38.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 13.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 847.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 236.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 262.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 38.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 233.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 546.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 233.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 546.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2721.345 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2721.345 | 100.00 |
Total On-Site and Utility Electric Sources | 2721.345 | 100.00 |
Total Electricity End Uses | 2721.345 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 385.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1448.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| CORE_BOTTOM PIU FAN | PERIMETER_BOT_ZN_1 PIU FAN | PERIMETER_BOT_ZN_2 PIU FAN | PERIMETER_BOT_ZN_3 PIU FAN | PERIMETER_BOT_ZN_4 PIU FAN | CORE_MID PIU FAN | PERIMETER_MID_ZN_1 PIU FAN | PERIMETER_MID_ZN_2 PIU FAN | PERIMETER_MID_ZN_3 PIU FAN | PERIMETER_MID_ZN_4 PIU FAN | CORE_TOP PIU FAN | PERIMETER_TOP_ZN_1 PIU FAN | PERIMETER_TOP_ZN_2 PIU FAN | PERIMETER_TOP_ZN_3 PIU FAN | PERIMETER_TOP_ZN_4 PIU FAN | PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-JUN-15:09 | - | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 131079.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32054.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2561.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 258492.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 131079.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 32054.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 2561.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 43.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2683.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 747.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 830.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 122.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8618.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 8.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 538.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 166.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1729.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 8.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 538.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 166.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1729.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
AirTerminal:SingleDuct:ParallelPIU:ReheatDesign Size Maximum Primary Air Flow Rate [m3/s] | Design Size Maximum Secondary Air Flow Rate [m3/s] | Design Size Minimum Primary Air Flow Fraction | User-Specified Minimum Primary Air Flow Fraction | |
CORE_BOTTOM VAV BOX COMPONENT | 3.44 | 3.44 | 0.123301 | 0.300000 |
CORE_MID VAV BOX COMPONENT | 2.87 | 2.87 | 0.147864 | 0.300000 |
CORE_TOP VAV BOX COMPONENT | 3.50 | 3.50 | 0.121197 | 0.300000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.32 | 1.32 | 0.067937 | 0.300000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.991144 | 0.991144 | 0.057185 | 0.300000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.33 | 1.33 | 0.067239 | 0.300000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.11 | 1.11 | 0.050886 | 0.300000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.08 | 1.08 | 0.083044 | 0.300000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.887114 | 0.887114 | 0.063891 | 0.300000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.10 | 1.10 | 0.081757 | 0.300000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.937340 | 0.937340 | 0.060464 | 0.300000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 1.11 | 1.11 | 0.080694 | 0.300000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.923238 | 0.923238 | 0.061392 | 0.300000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.13 | 1.13 | 0.079377 | 0.300000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.983215 | 0.983215 | 0.057643 | 0.300000 |
Design Size Maximum Flow Rate [m3/s] | |
CORE_BOTTOM PIU FAN | 3.44 |
CORE_MID PIU FAN | 2.87 |
CORE_TOP PIU FAN | 3.50 |
PERIMETER_TOP_ZN_3 PIU FAN | 1.32 |
PERIMETER_TOP_ZN_2 PIU FAN | 0.991144 |
PERIMETER_TOP_ZN_1 PIU FAN | 1.33 |
PERIMETER_TOP_ZN_4 PIU FAN | 1.11 |
PERIMETER_BOT_ZN_3 PIU FAN | 1.08 |
PERIMETER_BOT_ZN_2 PIU FAN | 0.887114 |
PERIMETER_BOT_ZN_1 PIU FAN | 1.10 |
PERIMETER_BOT_ZN_4 PIU FAN | 0.937340 |
PERIMETER_MID_ZN_3 PIU FAN | 1.11 |
PERIMETER_MID_ZN_2 PIU FAN | 0.923238 |
PERIMETER_MID_ZN_1 PIU FAN | 1.13 |
PERIMETER_MID_ZN_4 PIU FAN | 0.983215 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 73239.47 |
CORE_MID VAV BOX REHEAT COIL | 60934.30 |
CORE_TOP VAV BOX REHEAT COIL | 74185.75 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 27849.42 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20946.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 28138.85 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23537.73 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 22829.98 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 18746.70 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 23189.36 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 19808.10 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 23446.14 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 19510.38 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 23835.05 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 20777.87 |
PACU_VAV_BOT HEATING COIL | 0.000000 |
PACU_VAV_MID HEATING COIL | 0.000000 |
PACU_VAV_TOP HEATING COIL | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.23 | 2.23 | 7.44 | 2.36 | 6.98 | 6.98 | 0.300000 | 0.338410 | 6.98 |
PACU_VAV_MID | 2.10 | 2.10 | 7.02 | 3.14 | 6.51 | 6.51 | 0.300000 | 0.481872 | 6.51 |
PACU_VAV_TOP | 2.48 | 2.48 | 8.26 | 4.80 | 8.11 | 8.11 | 0.300000 | 0.592063 | 8.11 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.98 |
PACU_VAV_MID_OA_CONTROLLER | 6.51 |
PACU_VAV_TOP_OA_CONTROLLER | 8.11 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.98 | 143526.67 | 0.764910 | 2.33 | 47837.44 | 0.764910 |
PACU_VAV_MID COOLING COIL | 6.51 | 135513.86 | 0.760189 | 2.17 | 45166.77 | 0.760189 |
PACU_VAV_TOP COOLING COIL | 8.11 | 162727.41 | 0.775206 | 2.70 | 54237.05 | 0.775206 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.98 |
PACU_VAV_MID FAN | 6.51 |
PACU_VAV_TOP FAN | 8.11 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
43 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
44 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
45 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
46 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
47 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
48 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
49 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_1.22_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
2 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
3 | WINDOW_U_1.22_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
4 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40196.00528 | 46225.40608 | 2.99508 | 3.44435 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 2897.94303 | 3622.42878 | 0.21398 | 0.42469 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 33542.38630 | 38573.74425 | 2.49755 | 2.87218 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 10473.92171 | 13092.40213 | 0.76588 | 0.95735 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 40556.04097 | 46639.44711 | 3.04708 | 3.50414 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 21061.73017 | 26327.16272 | 1.55903 | 1.94878 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 15252.15071 | 17539.97332 | 1.14592 | 1.31781 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9275.40039 | 11594.25049 | 0.69050 | 0.86313 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11471.37731 | 13192.08391 | 0.86186 | 0.99114 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6024.86796 | 7531.08494 | 0.44857 | 0.56072 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15410.65933 | 17722.25823 | 1.15783 | 1.33151 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9270.26435 | 11587.83044 | 0.69012 | 0.86264 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12890.78680 | 14824.40482 | 0.96850 | 1.11378 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 41.28867 | 9.15671E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6066.89281 | 7583.61601 | 0.45172 | 0.56465 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 12477.64556 | 14349.29240 | 0.93747 | 1.07809 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6282.62529 | 7853.28162 | 0.46667 | 0.58334 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 10267.35181 | 11807.45458 | 0.77140 | 0.88711 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 39.04150 | 9.15295E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4123.89839 | 5154.87299 | 0.30639 | 0.38299 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12674.06007 | 14575.16908 | 0.95223 | 1.09506 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6282.61217 | 7853.26522 | 0.46667 | 0.58334 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10848.66963 | 12475.97007 | 0.81508 | 0.93734 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 41.28867 | 9.15671E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4169.08720 | 5211.35899 | 0.30978 | 0.38722 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 12840.98715 | 14767.13522 | 0.96477 | 1.10948 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7065.99551 | 8832.49438 | 0.52520 | 0.65650 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10685.44690 | 12288.26393 | 0.80282 | 0.92324 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 39.04150 | 9.15295E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4632.24947 | 5790.31184 | 0.34439 | 0.43048 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 13053.98486 | 15012.08259 | 0.98077 | 1.12789 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7059.34861 | 8824.18576 | 0.52470 | 0.65588 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11379.62025 | 13086.56329 | 0.85497 | 0.98322 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 41.28867 | 9.15671E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4679.10730 | 5848.88412 | 0.34789 | 0.43487 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 111696.37 | 6.97848 | 6.97848 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 7198.91 | 2.36159 | 2.36159 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 105436.84 | 6.50603 | 6.50603 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 7181.67 | 3.13508 | 3.13508 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 126385.67 | 8.10712 | 8.10712 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 6742.31 | 4.79992 | 4.79992 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 3.44435 |
2 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 3.44435 |
3 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.12330 |
4 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
5 | Fan:ConstantVolume | CORE_BOTTOM PIU FAN | Design Size Maximum Flow Rate [m3/s] | 3.44435 |
6 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 73239.46935 |
7 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 2.87218 |
8 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 2.87218 |
9 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.14786 |
10 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
11 | Fan:ConstantVolume | CORE_MID PIU FAN | Design Size Maximum Flow Rate [m3/s] | 2.87218 |
12 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 60934.30154 |
13 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 3.50414 |
14 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 3.50414 |
15 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.12120 |
16 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
17 | Fan:ConstantVolume | CORE_TOP PIU FAN | Design Size Maximum Flow Rate [m3/s] | 3.50414 |
18 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 74185.74687 |
19 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.31781 |
20 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.31781 |
21 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.79374E-002 |
22 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
23 | Fan:ConstantVolume | PERIMETER_TOP_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.31781 |
24 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27849.41981 |
25 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.99114 |
26 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.99114 |
27 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.71855E-002 |
28 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
29 | Fan:ConstantVolume | PERIMETER_TOP_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.99114 |
30 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20946.00266 |
31 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.33151 |
32 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.33151 |
33 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.72386E-002 |
34 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
35 | Fan:ConstantVolume | PERIMETER_TOP_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.33151 |
36 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 28138.84742 |
37 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.11378 |
38 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.11378 |
39 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.08855E-002 |
40 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
41 | Fan:ConstantVolume | PERIMETER_TOP_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.11378 |
42 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23537.73149 |
43 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.07809 |
44 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.07809 |
45 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 8.30438E-002 |
46 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
47 | Fan:ConstantVolume | PERIMETER_BOT_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.07809 |
48 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22829.98329 |
49 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.88711 |
50 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.88711 |
51 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.38915E-002 |
52 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
53 | Fan:ConstantVolume | PERIMETER_BOT_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.88711 |
54 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18746.69683 |
55 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.09506 |
56 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.09506 |
57 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 8.17568E-002 |
58 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
59 | Fan:ConstantVolume | PERIMETER_BOT_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.09506 |
60 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23189.36047 |
61 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.93734 |
62 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.93734 |
63 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.04640E-002 |
64 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
65 | Fan:ConstantVolume | PERIMETER_BOT_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.93734 |
66 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19808.10362 |
67 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.10948 |
68 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.10948 |
69 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 8.06940E-002 |
70 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
71 | Fan:ConstantVolume | PERIMETER_MID_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.10948 |
72 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23446.14213 |
73 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.92324 |
74 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.92324 |
75 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.13915E-002 |
76 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
77 | Fan:ConstantVolume | PERIMETER_MID_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.92324 |
78 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19510.38184 |
79 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.12789 |
80 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.12789 |
81 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 7.93773E-002 |
82 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
83 | Fan:ConstantVolume | PERIMETER_MID_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.12789 |
84 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23835.04800 |
85 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.98322 |
86 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.98322 |
87 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.76428E-002 |
88 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
89 | Fan:ConstantVolume | PERIMETER_MID_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.98322 |
90 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20777.86797 |
91 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.23258 |
92 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.23258 |
93 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.44195 |
94 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.36159 |
95 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.97848 |
96 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.97848 |
97 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
98 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.33841 |
99 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.10480 |
100 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.10480 |
101 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.01600 |
102 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 3.13508 |
103 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.50603 |
104 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 6.50603 |
105 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
106 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.48187 |
107 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.47752 |
108 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.47752 |
109 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.25838 |
110 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 4.79992 |
111 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.10712 |
112 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 8.10712 |
113 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
114 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.59206 |
115 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.97848 |
116 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 6.50603 |
117 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 8.10712 |
118 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.97848 |
119 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.97848 |
120 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 143526.67165 |
121 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76491 |
122 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.32593 |
123 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 47837.43966 |
124 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76491 |
125 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
126 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.97848 |
127 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.50603 |
128 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.50603 |
129 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 135513.85782 |
130 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76019 |
131 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.16846 |
132 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 45166.76881 |
133 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76019 |
134 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
135 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 6.50603 |
136 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.10712 |
137 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 8.10712 |
138 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 162727.41013 |
139 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77521 |
140 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.70210 |
141 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 54237.04580 |
142 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77521 |
143 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
144 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 8.10712 |
145 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
146 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
147 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
148 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
149 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 142365.33 | 485770.69 | 11.60 | 2.97 | 3.32 | 3.50 | 3.67 | 10.15 | 11.34 | 11.93 | 12.53 | 7.8677 | 6.2787 | 4.2275 | 1.7147 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 134481.42 | 458869.67 | 11.63 | 2.98 | 3.33 | 3.51 | 3.68 | 10.17 | 11.36 | 11.97 | 12.55 | 7.3351 | 5.8515 | 3.9398 | 1.6046 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 161259.86 | 550241.49 | 11.55 | 2.96 | 3.31 | 3.48 | 3.66 | 10.11 | 11.28 | 11.87 | 12.50 | 9.1402 | 7.3073 | 4.9226 | 1.9738 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.0812698427E-003 | 4.6991612909E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1191386293 | 8.4010473726E-002 | Pass | Pass | 2.0140637605E-002 | 0.1450057296 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3001628424E-002 | 5.9726465371E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0634679429E-002 | 4.8437419536E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.3425167896E-003 | 5.3000999847E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.4393849422E-002 | 2.0183229243E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.6685874414E-002 | 3.4256452504E-002 | Pass | Pass | 1.1111729156E-002 | 9.3332568289E-002 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.2675721620E-002 | 4.7643386965E-002 | Pass | Pass | 3.1904499988E-002 | 0.2401879497 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.6659091282E-002 | 6.8226290832E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.9668473631E-002 | 6.0789523167E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.4338381011E-002 | 2.3258390498E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.0805969080E-002 | 4.4592671580E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.5456576406E-002 | 5.2534311560E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.0609498547E-002 | 4.7477343882E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.8995322886E-002 | 2.3640538044E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.7361745227E-002 | 4.9524398541E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.8690600989E-002 | 5.9539452676E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.0553426118E-002 | 5.1422035242E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3631.09 | -60.2 | 0.00 | -737.0 | 4014.74 | 6848.64 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_1.22_SHGC_EAST_0.25 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_1.22_SHGC_EAST_0.25 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_1.22_SHGC_WEST_0.25 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_1.22_SHGC_WEST_0.25 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
North Total or Average | 183.92 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
Non-North Total or Average | 429.15 | 6.926 | 0.251 | 0.277 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.75 | 83.75 | 236.03 | |
Exterior Lighting Total | 15013.15 | 236.03 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 143526.67 | 109785.02 | 33741.65 | 0.76 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 135513.86 | 103016.19 | 32497.67 | 0.76 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 162727.41 | 126147.25 | 36580.16 | 0.78 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 142365.3 | 2.97 | 10.15 | N/A | N/A | 11.60 | |
PACU_VAV_MID COOLING COIL | 134481.4 | 2.98 | 10.17 | N/A | N/A | 11.63 | |
PACU_VAV_TOP COOLING COIL | 161259.9 | 2.96 | 10.11 | N/A | N/A | 11.55 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 73239.47 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 60934.30 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 74185.75 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 27849.42 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20946.00 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 28138.85 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23537.73 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22829.98 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18746.70 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23189.36 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19808.10 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23446.14 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19510.38 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23835.05 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20777.87 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CORE_BOTTOM PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 3.44 | 2553.14 | 741.25 | 1.00 | 1.23 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
CORE_MID PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 2.87 | 2129.01 | 741.25 | 1.00 | 1.25 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
CORE_TOP PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 3.50 | 2597.46 | 741.25 | 1.00 | 1.22 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 |
PERIMETER_TOP_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.32 | 976.83 | 741.25 | 1.00 | 1.38 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 |
PERIMETER_TOP_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.99 | 734.69 | 741.25 | 1.00 | 1.45 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 |
PERIMETER_TOP_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.33 | 986.98 | 741.25 | 1.00 | 1.37 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 |
PERIMETER_TOP_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.11 | 825.59 | 741.25 | 1.00 | 1.42 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 |
PERIMETER_BOT_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.08 | 799.14 | 741.25 | 1.00 | 1.42 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 |
PERIMETER_BOT_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.89 | 657.58 | 741.25 | 1.00 | 1.48 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 |
PERIMETER_BOT_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.10 | 811.72 | 741.25 | 1.00 | 1.42 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 |
PERIMETER_BOT_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.94 | 694.81 | 741.25 | 1.00 | 1.46 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 |
PERIMETER_MID_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.11 | 822.41 | 741.25 | 1.00 | 1.42 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 |
PERIMETER_MID_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.92 | 684.35 | 741.25 | 1.00 | 1.47 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 |
PERIMETER_MID_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.13 | 836.05 | 741.25 | 1.00 | 1.41 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 |
PERIMETER_MID_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.98 | 728.81 | 741.25 | 1.00 | 1.45 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.98 | 15337.17 | 2197.78 | 1.00 | 1.13 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1337.13 | 6.51 | 14391.08 | 2211.96 | 1.00 | 1.13 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 8.11 | 17817.67 | 2197.78 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 142365.33 | 2.97 | 10.15 | 11.60 | 7.8677 | 3.32 | 11.34 | 6.2787 | 3.50 | 11.93 | 4.2275 | 3.67 | 12.53 | 1.7147 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 134481.42 | 2.98 | 10.17 | 11.63 | 7.3351 | 3.33 | 11.36 | 5.8515 | 3.51 | 11.97 | 3.9398 | 3.68 | 12.55 | 1.6046 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 161259.86 | 2.96 | 10.11 | 11.55 | 9.1402 | 3.31 | 11.28 | 7.3073 | 3.48 | 11.87 | 4.9226 | 3.66 | 12.50 | 1.9738 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40196.01 | 46225.41 | 47.00 | 2.995 | 3.444 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 34.82 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 33542.39 | 38573.74 | 39.22 | 2.498 | 2.872 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 34.82 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 40556.04 | 46639.45 | 47.42 | 3.047 | 3.504 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 24.00 | 24.00 | 0.00879 | 42.00 | 0.00916 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15252.15 | 17539.97 | 84.60 | 1.146 | 1.318 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 24.00 | 0.00867 | 41.90 | 0.00916 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11471.38 | 13192.08 | 100.50 | 0.862 | 0.991 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 24.00 | 24.00 | 0.00865 | 39.53 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15410.66 | 17722.26 | 85.48 | 1.158 | 1.332 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00867 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12890.79 | 14824.40 | 112.94 | 0.969 | 1.114 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 24.00 | 24.00 | 0.00863 | 41.29 | 0.00916 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12477.65 | 14349.29 | 69.21 | 0.937 | 1.078 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 24.00 | 0.00871 | 41.90 | 0.00916 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 10267.35 | 11807.45 | 89.95 | 0.771 | 0.887 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 24.00 | 24.00 | 0.00866 | 39.04 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12674.06 | 14575.17 | 70.30 | 0.952 | 1.095 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 24.00 | 24.00 | 0.00870 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10848.67 | 12475.97 | 95.05 | 0.815 | 0.937 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 24.00 | 24.00 | 0.00865 | 41.29 | 0.00916 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12840.99 | 14767.14 | 71.22 | 0.965 | 1.109 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 24.00 | 0.00870 | 41.90 | 0.00916 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10685.45 | 12288.26 | 93.62 | 0.803 | 0.923 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 24.00 | 24.00 | 0.00866 | 39.04 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13053.98 | 15012.08 | 72.40 | 0.981 | 1.128 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 24.00 | 24.00 | 0.00870 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11379.62 | 13086.56 | 99.70 | 0.855 | 0.983 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | 24.00 | 24.00 | 0.00865 | 41.29 | 0.00916 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 2897.94 | 3622.43 | 3.68 | 0.214 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
CORE_MID | 10473.92 | 13092.40 | 13.31 | 0.766 | 0.957 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
CORE_TOP | 21061.73 | 26327.16 | 26.77 | 1.559 | 1.949 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9275.40 | 11594.25 | 55.92 | 0.691 | 0.863 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6024.87 | 7531.08 | 57.37 | 0.449 | 0.561 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9270.26 | 11587.83 | 55.89 | 0.690 | 0.863 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6066.89 | 7583.62 | 57.78 | 0.452 | 0.565 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6282.63 | 7853.28 | 37.88 | 0.467 | 0.583 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4123.90 | 5154.87 | 39.27 | 0.306 | 0.383 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6282.61 | 7853.27 | 37.88 | 0.467 | 0.583 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4169.09 | 5211.36 | 39.70 | 0.310 | 0.387 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7066.00 | 8832.49 | 42.60 | 0.525 | 0.657 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4632.25 | 5790.31 | 44.11 | 0.344 | 0.430 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7059.35 | 8824.19 | 42.56 | 0.525 | 0.656 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4679.11 | 5848.88 | 44.56 | 0.348 | 0.435 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.98 | 6.98 | 2.36 | 2.36 | 6.9785 | 2.3616 | 6.9785 | 0.3384 | 0.3000 |
PACU_VAV_MID | 6.51 | 6.51 | 3.14 | 3.14 | 6.5060 | 3.1351 | 6.5060 | 0.4819 | 0.3000 |
PACU_VAV_TOP | 8.11 | 8.11 | 4.80 | 4.80 | 8.1071 | 4.7999 | 8.1071 | 0.5921 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 73239.469 | 73239.469 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 73239.47 | 6946.53 | 0.424691 | 18.45 | 4.87 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00799998 | 50.4124 | 3622.43 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 60934.302 | 60934.302 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60934.30 | 15623.41 | 0.957345 | 18.48 | 4.89 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 13092.40 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 74185.747 | 74185.747 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 74185.75 | 31736.48 | 1.948784 | 18.51 | 4.90 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 26327.16 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 27849.420 | 27849.420 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27849.42 | 14031.17 | 0.863125 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798787 | 50.3372 | 11594.25 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 20946.003 | 20946.003 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20946.00 | 9115.17 | 0.560717 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798773 | 50.3364 | 7531.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 28138.847 | 28138.847 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28138.85 | 14023.35 | 0.862645 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798786 | 50.3371 | 11587.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 23537.731 | 23537.731 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23537.73 | 9179.12 | 0.564650 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798787 | 50.3372 | 7583.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 22829.983 | 22829.983 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22829.98 | 9502.34 | 0.583342 | 18.50 | 4.90 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798470 | 50.3175 | 7853.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 18746.697 | 18746.697 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18746.70 | 6225.76 | 0.382993 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798507 | 50.3198 | 5154.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 23189.360 | 23189.360 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23189.36 | 9502.32 | 0.583340 | 18.50 | 4.90 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798470 | 50.3175 | 7853.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 19808.104 | 19808.104 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19808.10 | 6294.51 | 0.387221 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798541 | 50.3220 | 5211.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 23446.142 | 23446.142 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23446.14 | 10671.95 | 0.656503 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798218 | 50.3019 | 8832.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 19510.382 | 19510.382 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19510.38 | 6997.82 | 0.430481 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798251 | 50.3039 | 5790.31 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 23835.048 | 23835.048 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23835.05 | 10661.84 | 0.655881 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798215 | 50.3017 | 8824.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 20777.868 | 20777.868 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20777.87 | 7069.10 | 0.434866 | 18.53 | 4.92 | -999.0 | 32.11 | 18.45 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798285 | 50.3061 | 5848.88 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 143526.672 | 109785.021 | 6.978477 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 131047.22 | 124763.88 | 6.978477 | 26.47 | 17.24 | 0.00880746 | 11.06 | 11.06 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 13.7007 | 24.00 | 0.00875179 | 45.9079 | 80723.29 | 0.00 | 147995.26 | 110083.74 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 2.093543 | 14.00 | 10.94 | 0.00708755 | 12.89 | 11.41 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 45.6690 | 19.99 | 0.00794943 | 53.3134 | 7293.15 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 135513.858 | 103016.192 | 6.506031 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 123964.88 | 117698.20 | 6.506031 | 26.65 | 17.32 | 0.00882887 | 11.04 | 11.04 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 14.6956 | 24.00 | 0.00877210 | 46.0129 | 75194.73 | 0.00 | 139732.98 | 103323.38 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.951809 | 13.80 | 10.81 | 0.00704682 | 12.89 | 11.41 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 48.9853 | 18.49 | 0.00797631 | 58.7552 | 7250.65 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 162727.410 | 126147.248 | 8.107116 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 148219.49 | 141777.47 | 8.107116 | 26.11 | 17.09 | 0.00877100 | 11.06 | 11.06 | 0.00850000 | 41.90 | 0.00915774 | 22.24 | 11.7933 | 24.00 | 0.00871928 | 45.7396 | 93793.85 | 0.00 | 167793.80 | 126408.92 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 2.432135 | 13.25 | 10.74 | 0.00720166 | 12.89 | 11.41 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 39.3111 | 19.48 | 0.00793104 | 54.9253 | 15214.40 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 73239.469 | 73239.469 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 73239.47 | 6946.53 | 1.0000 | 0.49849623 | 0.424691 | 18.45 | 4.87 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73239.47 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.83 | 0.00799998 | 21.00 | 0.00799998 | 50.4124 | 3622.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 60934.302 | 60934.302 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 60934.30 | 15623.41 | 1.0000 | 1.12371800 | 0.957345 | 18.48 | 4.89 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60934.30 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 13092.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 74185.747 | 74185.747 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 74185.75 | 31736.48 | 1.0000 | 2.28745378 | 1.948784 | 18.51 | 4.90 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 74185.75 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 26327.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 27849.420 | 27849.420 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27849.42 | 14031.17 | 1.0000 | 1.01312371 | 0.863125 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27849.42 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798787 | 21.00 | 0.00798787 | 50.3372 | 11594.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 20946.003 | 20946.003 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20946.00 | 9115.17 | 1.0000 | 0.65816154 | 0.560717 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20946.00 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798773 | 21.00 | 0.00798773 | 50.3364 | 7531.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 28138.847 | 28138.847 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28138.85 | 14023.35 | 1.0000 | 1.01255974 | 0.862645 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28138.85 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798786 | 21.00 | 0.00798786 | 50.3371 | 11587.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 23537.731 | 23537.731 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23537.73 | 9179.12 | 1.0000 | 0.66277800 | 0.564650 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23537.73 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798787 | 21.00 | 0.00798787 | 50.3372 | 7583.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 22829.983 | 22829.983 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22829.98 | 9502.34 | 1.0000 | 0.68471801 | 0.583342 | 18.50 | 4.90 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22829.98 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00798470 | 21.00 | 0.00798470 | 50.3175 | 7853.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 18746.697 | 18746.697 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18746.70 | 6225.76 | 1.0000 | 0.44955123 | 0.382993 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18746.70 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798507 | 21.00 | 0.00798507 | 50.3198 | 5154.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 23189.360 | 23189.360 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23189.36 | 9502.32 | 1.0000 | 0.68471657 | 0.583340 | 18.50 | 4.90 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23189.36 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00798470 | 21.00 | 0.00798470 | 50.3175 | 7853.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 19808.104 | 19808.104 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19808.10 | 6294.51 | 1.0000 | 0.45451464 | 0.387221 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19808.10 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798541 | 21.00 | 0.00798541 | 50.3220 | 5211.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 23446.142 | 23446.142 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23446.14 | 10671.95 | 1.0000 | 0.77059333 | 0.656503 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23446.14 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798218 | 21.00 | 0.00798218 | 50.3019 | 8832.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 19510.382 | 19510.382 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19510.38 | 6997.82 | 1.0000 | 0.50529271 | 0.430481 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19510.38 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798251 | 21.00 | 0.00798251 | 50.3039 | 5790.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 23835.048 | 23835.048 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23835.05 | 10661.84 | 1.0000 | 0.76986352 | 0.655881 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23835.05 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798215 | 21.00 | 0.00798215 | 50.3017 | 8824.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 20777.868 | 20777.868 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20777.87 | 7069.10 | 1.0000 | 0.51043926 | 0.434866 | 18.53 | 4.92 | -999.0 | -999.0 | 32.11 | 18.45 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20777.87 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798285 | 21.00 | 0.00798285 | 50.3061 | 5848.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 143526.672 | 109785.021 | 6.978477 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2126 | 1004.8586 | 1.1738 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.978477 | 8.19123505 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | Sensible | 131047.22 | 124763.88 | 0.9131 | 8.19123505 | 6.978477 | 26.47 | 17.24 | 0.00880746 | 49054.8 | 11.06 | 11.06 | 0.00850000 | 32541.6 | -999.0 | -999.00 | -999.00 | -999.00 | 15337.165 | 115710.06 | 42.00 | 0.00915790 | 22.26 | 0.95610000 | 13.7007 | 24.00 | 0.00875179 | 24.00 | 0.00875179 | 45.9079 | 80723.29 | 0.00 | 147995.26 | 110083.74 | 7.86774319 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.98 | 12.96 | 0.00929540 | 36512.0 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.978477 | 8.19123505 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.45737052 | 2.093543 | 14.00 | 10.94 | 0.00708755 | 31976.9 | 12.89 | 11.41 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 6.30 | 0.00607234 | 6.30 | 0.95610000 | 45.6690 | 20.47 | 0.00794090 | 19.99 | 0.00794943 | 53.3134 | 7293.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 135513.858 | 103016.192 | 6.506031 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2524 | 1004.8586 | 1.1738 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.506031 | 7.63668501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | Sensible | 123964.88 | 117698.20 | 0.9148 | 7.63668501 | 6.506031 | 26.65 | 17.32 | 0.00882887 | 49294.7 | 11.04 | 11.04 | 0.00850000 | 32529.6 | -999.0 | -999.00 | -999.00 | -999.00 | 14391.083 | 109573.79 | 42.00 | 0.00915790 | 22.26 | 0.95610000 | 14.6956 | 24.00 | 0.00877210 | 24.00 | 0.00877210 | 46.0129 | 75194.73 | 0.00 | 139732.98 | 103323.38 | 7.33509368 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.88 | 12.86 | 0.00923848 | 36272.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.506031 | 7.63668501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.29100550 | 1.951809 | 13.80 | 10.81 | 0.00704682 | 31670.4 | 12.89 | 11.41 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 6.30 | 0.00607234 | 6.30 | 0.95610000 | 48.9853 | 21.00 | 0.00798253 | 18.49 | 0.00797631 | 58.7552 | 7250.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 162727.410 | 126147.248 | 8.107116 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1449 | 1004.8586 | 1.1738 | PACU_VAV_TOP FAN | Fan:VariableVolume | 8.107116 | 9.51601533 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | Sensible | 148219.49 | 141777.47 | 0.9108 | 9.51601533 | 8.107116 | 26.11 | 17.09 | 0.00877100 | 48599.0 | 11.06 | 11.06 | 0.00850000 | 32541.5 | -999.0 | -999.00 | -999.00 | -999.00 | 17817.667 | 130401.82 | 41.90 | 0.00915774 | 22.24 | 0.95610000 | 11.7933 | 24.00 | 0.00871928 | 24.00 | 0.00871928 | 45.7396 | 93793.85 | 0.00 | 167793.80 | 126408.92 | 9.14020466 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.14 | 13.13 | 0.00940942 | 36964.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_TOP FAN | Fan:VariableVolume | 8.107116 | 9.51601533 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.85480460 | 2.432135 | 13.25 | 10.74 | 0.00720166 | 31504.7 | 12.89 | 11.41 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 6.30 | 0.00607234 | 6.30 | 0.95610000 | 39.3111 | 17.76 | 0.00793318 | 19.48 | 0.00793104 | 54.9253 | 15214.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 4867.50 | 175.50 | 12.17 |
CORE_MID | 3939.00 | 1155.50 | 2.83 |
CORE_TOP | 3665.17 | 1757.33 | 52.00 |
PERIMETER_TOP_ZN_3 | 3593.50 | 2507.00 | 484.17 |
PERIMETER_TOP_ZN_2 | 3767.00 | 2310.50 | 482.00 |
PERIMETER_TOP_ZN_1 | 4195.17 | 1863.33 | 483.33 |
PERIMETER_TOP_ZN_4 | 3588.17 | 2489.50 | 521.33 |
PERIMETER_BOT_ZN_3 | 3643.33 | 2140.33 | 193.00 |
PERIMETER_BOT_ZN_2 | 3946.67 | 1922.00 | 275.67 |
PERIMETER_BOT_ZN_1 | 4478.17 | 2085.00 | 989.50 |
PERIMETER_BOT_ZN_4 | 3814.33 | 2005.00 | 262.50 |
PERIMETER_MID_ZN_3 | 3663.67 | 2230.33 | 290.50 |
PERIMETER_MID_ZN_2 | 3147.67 | 1922.33 | 332.67 |
PERIMETER_MID_ZN_1 | 4383.67 | 1539.50 | 370.00 |
PERIMETER_MID_ZN_4 | 3688.67 | 2185.50 | 323.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5301.00 | 3543.00 | 1448.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 1.00 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 35.83 | 0.00 | 27.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 55.17 | 0.00 | 48.17 |
PERIMETER_TOP_ZN_1 | 0.00 | 64.33 | 0.00 | 55.50 |
PERIMETER_TOP_ZN_4 | 0.00 | 51.50 | 0.00 | 35.50 |
PERIMETER_BOT_ZN_3 | 0.00 | 21.50 | 0.00 | 16.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 46.00 | 0.00 | 41.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 288.83 | 0.00 | 282.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 44.83 | 0.00 | 30.17 |
PERIMETER_MID_ZN_3 | 0.00 | 24.00 | 0.00 | 18.33 |
PERIMETER_MID_ZN_2 | 0.00 | 43.17 | 0.00 | 40.00 |
PERIMETER_MID_ZN_1 | 0.00 | 58.83 | 0.00 | 53.50 |
PERIMETER_MID_ZN_4 | 0.00 | 43.83 | 0.00 | 30.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 415.67 | 0.00 | 385.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 0.435 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 0.384 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 0.384 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 0.668 | 0.032 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.823 | 0.034 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 0.784 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.877 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 0.538 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.699 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 0.731 | 1.244 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.716 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 0.670 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.854 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 0.816 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.908 | 0.028 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.60 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.81 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 7256700.39 | 0.00 | 7256700.39 | 0.00 | 7256700.39 | 13393058.27 | 7966.80 | 141.23 | 651.97 | 390.65 |
CORE_MID | 6309141.58 | 0.00 | 6309141.58 | 0.00 | 6309141.58 | 13393058.27 | 8738.74 | 7.50 | 13.76 | 286.36 |
CORE_TOP | 6318071.89 | 0.00 | 6318071.89 | 0.00 | 6318071.89 | 13393058.27 | 8756.96 | 0.28 | 2.76 | 288.91 |
PERIMETER_TOP_ZN_3 | 2323358.97 | 0.00 | 2323358.97 | 173897.85 | 2497256.82 | 2823374.22 | 3618.30 | 42.63 | 5099.07 | 288.91 |
PERIMETER_TOP_ZN_2 | 1807781.11 | 0.00 | 1807781.11 | 115931.20 | 1923712.31 | 1787429.43 | 3468.16 | 0.67 | 5291.16 | 288.91 |
PERIMETER_TOP_ZN_1 | 2703077.41 | 0.00 | 2703077.41 | 173897.85 | 2876975.25 | 2823374.22 | 3472.27 | 3.21 | 5284.52 | 288.91 |
PERIMETER_TOP_ZN_4 | 1936377.54 | 0.00 | 1936377.54 | 115931.20 | 2052308.74 | 1787312.18 | 3465.06 | 0.92 | 5294.02 | 288.91 |
PERIMETER_BOT_ZN_3 | 1919205.98 | 0.00 | 1919205.98 | 92461.45 | 2011667.43 | 2823374.22 | 5088.16 | 137.16 | 3534.69 | 390.65 |
PERIMETER_BOT_ZN_2 | 1577377.94 | 0.00 | 1577377.94 | 61640.59 | 1639018.54 | 1787429.43 | 3571.98 | 68.16 | 5119.86 | 390.65 |
PERIMETER_BOT_ZN_1 | 2549526.39 | 0.00 | 2549526.39 | 4106049.28 | 6655575.67 | 2823374.22 | 3842.78 | 58.28 | 4858.94 | 390.65 |
PERIMETER_BOT_ZN_4 | 1622136.66 | 0.00 | 1622136.66 | 61640.59 | 1683777.25 | 1787312.18 | 3602.85 | 62.01 | 5095.14 | 390.65 |
PERIMETER_MID_ZN_3 | 2331190.25 | 0.00 | 2331190.25 | 144757.29 | 2475947.54 | 2823374.22 | 3836.90 | 52.68 | 4870.41 | 286.36 |
PERIMETER_MID_ZN_2 | 1885830.33 | 0.00 | 1885830.33 | 96504.28 | 1982334.61 | 1601953.02 | 3463.67 | 1.34 | 5294.99 | 1195.36 |
PERIMETER_MID_ZN_1 | 2811008.42 | 0.00 | 2811008.42 | 144757.29 | 2955765.72 | 2823374.22 | 3513.38 | 10.42 | 5236.20 | 286.36 |
PERIMETER_MID_ZN_4 | 2006423.44 | 0.00 | 2006423.44 | 96504.28 | 2102927.73 | 1787312.18 | 3473.39 | 10.01 | 5276.60 | 286.36 |
Total Facility | 45357208.31 | 0.00 | 45357208.31 | 5383973.17 | 50741181.48 | 67658168.57 | 8760.00 | 530.46 | 5659.43 | 1416.86 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3155 | 0.0000 | 0.3155 | 0.0000 | 0.3155 | 0.4247 | 5157.74 | 141.01 | 644.25 |
CORE_MID | 0.2786 | 0.0000 | 0.2786 | 0.0000 | 0.2786 | 0.4247 | 5922.92 | 7.35 | 12.73 |
CORE_TOP | 0.2789 | 0.0000 | 0.2789 | 0.0000 | 0.2789 | 0.4247 | 5940.88 | 0.25 | 1.87 |
PERIMETER_TOP_ZN_3 | 0.1024 | 0.0000 | 0.1024 | 0.0050 | 0.1073 | 0.0895 | 1086.01 | 42.42 | 4814.58 |
PERIMETER_TOP_ZN_2 | 0.0799 | 0.0000 | 0.0799 | 0.0033 | 0.0832 | 0.0567 | 936.76 | 0.46 | 5005.78 |
PERIMETER_TOP_ZN_1 | 0.1201 | 0.0000 | 0.1201 | 0.0050 | 0.1250 | 0.0895 | 940.16 | 2.99 | 4999.85 |
PERIMETER_TOP_ZN_4 | 0.0852 | 0.0000 | 0.0852 | 0.0033 | 0.0885 | 0.0567 | 934.77 | 0.82 | 5007.42 |
PERIMETER_BOT_ZN_3 | 0.0824 | 0.0000 | 0.0824 | 0.0026 | 0.0850 | 0.0895 | 2644.93 | 135.16 | 3162.91 |
PERIMETER_BOT_ZN_2 | 0.0677 | 0.0000 | 0.0677 | 0.0018 | 0.0695 | 0.0567 | 1139.34 | 67.12 | 4736.53 |
PERIMETER_BOT_ZN_1 | 0.1117 | 0.0000 | 0.1117 | 0.1902 | 0.3019 | 0.0895 | 1401.87 | 57.13 | 4484.00 |
PERIMETER_BOT_ZN_4 | 0.0694 | 0.0000 | 0.0694 | 0.0018 | 0.0711 | 0.0567 | 1172.44 | 61.38 | 4709.18 |
PERIMETER_MID_ZN_3 | 0.1026 | 0.0000 | 0.1026 | 0.0041 | 0.1067 | 0.0895 | 1301.06 | 52.52 | 4589.41 |
PERIMETER_MID_ZN_2 | 0.0828 | 0.0000 | 0.0828 | 0.0028 | 0.0857 | 0.0567 | 929.89 | 1.14 | 4102.97 |
PERIMETER_MID_ZN_1 | 0.1249 | 0.0000 | 0.1249 | 0.0041 | 0.1291 | 0.0895 | 977.80 | 10.26 | 4954.94 |
PERIMETER_MID_ZN_4 | 0.0881 | 0.0000 | 0.0881 | 0.0028 | 0.0909 | 0.0567 | 940.47 | 9.67 | 4992.86 |
Total Facility | 1.9901 | 0.0000 | 1.9901 | 0.2268 | 2.2169 | 2.1513 | 5943.00 | 524.54 | 5152.43 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 20563191.38 | 0.00 | 20563191.38 | 22614548.33 | 3346.44 | 1.62 | 5411.95 | 390.65 |
PACU_VAV_MID | 21139991.17 | 0.00 | 21139991.17 | 22429071.92 | 3462.98 | 1.13 | 5295.89 | 286.36 |
PACU_VAV_TOP | 20788755.56 | 0.00 | 20788755.56 | 22614548.33 | 3467.14 | 0.44 | 5292.42 | 288.91 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.8909 | 0.0000 | 0.8909 | 0.7171 | 916.66 | 1.10 | 5025.24 |
PACU_VAV_MID | 0.9330 | 0.0000 | 0.9330 | 0.7084 | 928.89 | 1.06 | 5013.04 |
PACU_VAV_TOP | 0.9182 | 0.0000 | 0.9182 | 0.7171 | 936.18 | 0.38 | 5006.43 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 71.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5359.11 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 84.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5222.43 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 36.20 | 0.00 | 0.00 | 0.00 | 0.00 | 5263.09 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.8766 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0526 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.0543 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1055 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.9545 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0900 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 842 |
Defaulted Fields | 530 |
Fields with Defaults | 2032 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2721.34 | 15934.24 | 20-FEB-18:10 | 258492.76 | 12-JUN-15:10 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 1150.89 | 383.73 | 01-JAN-00:10 | 165160.39 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 05-JAN-17:10 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 05-JAN-17:10 |
ElectricityPurchased:Facility | 2721.34 | 15934.24 | 26-FEB-18:10 | 258492.76 | 12-JUN-15:10 |
ElectricityPurchased:Plant | 2721.34 | 15934.24 | 26-FEB-18:10 | 258492.76 | 12-JUN-15:10 |
Cogeneration:ElectricityPurchased | 2721.34 | 15934.24 | 26-FEB-18:10 | 258492.76 | 12-JUN-15:10 |
General:Cogeneration:ElectricityPurchased | 2721.34 | 15934.24 | 26-FEB-18:10 | 258492.76 | 12-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2721.34 | 15934.24 | 26-FEB-18:10 | 258492.76 | 12-JUN-15:10 |
ElectricityNet:Plant | 2721.34 | 15934.24 | 26-FEB-18:10 | 258492.76 | 12-JUN-15:10 |
Cogeneration:ElectricityNet | 2721.34 | 15934.24 | 26-FEB-18:10 | 258492.76 | 12-JUN-15:10 |
General:Cogeneration:ElectricityNet | 2721.34 | 15934.24 | 26-FEB-18:10 | 258492.76 | 12-JUN-15:10 |
Fans:Electricity | 262.21 | 0.00 | 01-JAN-00:10 | 35339.24 | 05-JUN-14:20 |
General:Fans:Electricity | 262.21 | 0.00 | 01-JAN-00:10 | 35339.24 | 05-JUN-14:20 |
Heating:Electricity | 13.69 | 0.00 | 01-JAN-00:10 | 141096.90 | 02-JAN-07:10 |
General:Heating:Electricity | 13.69 | 0.00 | 01-JAN-00:10 | 141096.90 | 02-JAN-07:10 |
ExteriorLights:Electricity | 236.03 | 0.00 | 01-JAN-07:20 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 236.03 | 0.00 | 01-JAN-07:20 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 847.49 | 0.00 | 01-JAN-00:10 | 131417.58 | 12-JUN-15:30 |
General:Cooling:Electricity | 847.49 | 0.00 | 01-JAN-00:10 | 131417.58 | 12-JUN-15:30 |
Electricity:Plant | 38.90 | 0.00 | 01-JAN-00:10 | 5349.21 | 19-JAN-12:50 |
WaterSystems:Electricity | 38.75 | 0.00 | 01-JAN-00:10 | 5342.36 | 19-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 38.75 | 0.00 | 01-JAN-00:10 | 5342.36 | 19-JAN-12:50 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-APR-15:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-APR-15:20 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5668.54 | 0.00 | 01-JAN-00:10 | 705764.49 | 02-JAN-07:20 |
EnergyTransfer:Building | 2451.58 | 0.00 | 01-JAN-00:10 | 572794.90 | 02-JAN-07:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 345.72 | 0.00 | 01-JAN-00:10 | 27410.68 | 05-SEP-08:00 |
Heating:EnergyTransfer | 324.55 | 0.00 | 01-JAN-00:10 | 562035.07 | 02-JAN-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 324.55 | 0.00 | 01-JAN-00:10 | 562035.07 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 2127.04 | 0.00 | 01-JAN-00:10 | 241298.67 | 12-JUN-15:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 345.72 | 0.00 | 01-JAN-00:10 | 27410.68 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 2127.04 | 0.00 | 01-JAN-00:10 | 241298.67 | 12-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 345.72 | 0.00 | 01-JAN-00:10 | 27410.68 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 324.68 | 0.00 | 01-JAN-00:10 | 211591.54 | 02-JAN-07:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 202.01 | 0.00 | 01-JAN-00:10 | 211591.54 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 202.01 | 0.00 | 01-JAN-00:10 | 211591.54 | 02-JAN-07:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 122.68 | 0.00 | 01-JAN-00:10 | 24817.22 | 08-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 122.68 | 0.00 | 01-JAN-00:10 | 24817.22 | 08-JUN-14:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 122.53 | 0.00 | 01-JAN-00:10 | 178480.23 | 02-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 70.20 | 0.00 | 01-JAN-00:10 | 178480.23 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 70.20 | 0.00 | 01-JAN-00:10 | 178480.23 | 02-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.33 | 0.00 | 01-JAN-00:10 | 7578.58 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.33 | 0.00 | 01-JAN-00:10 | 7578.58 | 12-JUN-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 106.82 | 0.00 | 01-JAN-00:10 | 103177.53 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 45.74 | 0.00 | 01-JAN-00:10 | 103177.53 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 45.74 | 0.00 | 01-JAN-00:10 | 103177.53 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 61.08 | 0.00 | 01-JAN-00:10 | 7211.45 | 30-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 61.08 | 0.00 | 01-JAN-00:10 | 7211.45 | 30-MAY-16:00 |
EnergyTransfer:Zone:CORE_MID | 241.12 | 0.00 | 01-JAN-00:10 | 21870.57 | 30-MAY-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 8095.67 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.01 | 0.00 | 01-JAN-00:10 | 8095.67 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 241.11 | 0.00 | 01-JAN-00:10 | 21870.57 | 30-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 241.11 | 0.00 | 01-JAN-00:10 | 21870.57 | 30-MAY-16:00 |
EnergyTransfer:Zone:CORE_TOP | 263.70 | 0.00 | 01-JAN-00:10 | 27491.72 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.19 | 0.00 | 01-JAN-00:10 | 21892.19 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.19 | 0.00 | 01-JAN-00:10 | 21892.19 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 263.51 | 0.00 | 01-JAN-00:10 | 27491.72 | 12-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 263.51 | 0.00 | 01-JAN-00:10 | 27491.72 | 12-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 91.50 | 0.00 | 01-JAN-00:10 | 12309.59 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.97 | 0.00 | 01-JAN-00:10 | 10498.81 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.97 | 0.00 | 01-JAN-00:10 | 10498.81 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 90.53 | 0.00 | 01-JAN-00:10 | 12309.59 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 90.53 | 0.00 | 01-JAN-00:10 | 12309.59 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 72.69 | 0.00 | 01-JAN-00:10 | 11515.74 | 03-MAY-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.42 | 0.00 | 01-JAN-00:10 | 6686.37 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.42 | 0.00 | 01-JAN-00:10 | 6686.37 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 72.26 | 0.00 | 01-JAN-00:10 | 11515.74 | 03-MAY-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 72.26 | 0.00 | 01-JAN-00:10 | 11515.74 | 03-MAY-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 114.12 | 0.00 | 01-JAN-00:10 | 16667.24 | 02-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.57 | 0.00 | 01-JAN-00:10 | 10262.11 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.57 | 0.00 | 01-JAN-00:10 | 10262.11 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 113.55 | 0.00 | 01-JAN-00:10 | 16667.24 | 02-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 113.55 | 0.00 | 01-JAN-00:10 | 16667.24 | 02-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 74.52 | 0.00 | 01-JAN-00:10 | 13229.51 | 08-JUN-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.61 | 0.00 | 01-JAN-00:10 | 6703.13 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.61 | 0.00 | 01-JAN-00:10 | 6703.13 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 73.91 | 0.00 | 01-JAN-00:10 | 13229.51 | 08-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 73.91 | 0.00 | 01-JAN-00:10 | 13229.51 | 08-JUN-15:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.90 | 0.00 | 01-JAN-00:10 | 11082.07 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.21 | 0.00 | 01-JAN-00:10 | 3795.40 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.21 | 0.00 | 01-JAN-00:10 | 3795.40 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.70 | 0.00 | 01-JAN-00:10 | 11082.07 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.70 | 0.00 | 01-JAN-00:10 | 11082.07 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.81 | 0.00 | 01-JAN-00:10 | 10595.59 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 2593.04 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 2593.04 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.71 | 0.00 | 01-JAN-00:10 | 10595.59 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.71 | 0.00 | 01-JAN-00:10 | 10595.59 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 130.95 | 0.00 | 01-JAN-00:10 | 21961.96 | 03-JAN-07:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.67 | 0.00 | 01-JAN-00:10 | 21961.96 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.67 | 0.00 | 01-JAN-00:10 | 21961.96 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 128.28 | 0.00 | 01-JAN-00:10 | 20189.60 | 07-JUN-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 128.28 | 0.00 | 01-JAN-00:10 | 20189.60 | 07-JUN-16:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 72.15 | 0.00 | 01-JAN-00:10 | 11682.52 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.14 | 0.00 | 01-JAN-00:10 | 2519.96 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.14 | 0.00 | 01-JAN-00:10 | 2519.96 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 72.01 | 0.00 | 01-JAN-00:10 | 11682.52 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 72.01 | 0.00 | 01-JAN-00:10 | 11682.52 | 08-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 84.82 | 0.00 | 01-JAN-00:10 | 11094.93 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.26 | 0.00 | 01-JAN-00:10 | 6533.20 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.26 | 0.00 | 01-JAN-00:10 | 6533.20 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 84.57 | 0.00 | 01-JAN-00:10 | 11094.93 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 84.57 | 0.00 | 01-JAN-00:10 | 11094.93 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 68.27 | 0.00 | 01-JAN-00:10 | 11110.39 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.14 | 0.00 | 01-JAN-00:10 | 4276.28 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.14 | 0.00 | 01-JAN-00:10 | 4276.28 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 68.13 | 0.00 | 01-JAN-00:10 | 11110.39 | 03-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 68.13 | 0.00 | 01-JAN-00:10 | 11110.39 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 108.64 | 0.00 | 01-JAN-00:10 | 15410.85 | 02-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.12 | 0.00 | 01-JAN-00:10 | 5569.79 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.12 | 0.00 | 01-JAN-00:10 | 5569.79 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 108.51 | 0.00 | 01-JAN-00:10 | 15410.85 | 02-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 108.51 | 0.00 | 01-JAN-00:10 | 15410.85 | 02-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 70.63 | 0.00 | 01-JAN-00:10 | 12344.99 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.19 | 0.00 | 01-JAN-00:10 | 4217.03 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.19 | 0.00 | 01-JAN-00:10 | 4217.03 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 70.44 | 0.00 | 01-JAN-00:10 | 12344.99 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 70.44 | 0.00 | 01-JAN-00:10 | 12344.99 | 08-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
PlantLoopHeatingDemand:Plant | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
EnergyTransfer:HVAC | 3180.95 | 0.00 | 01-JAN-00:10 | 382013.71 | 22-JUN-15:40 |
HeatingCoils:EnergyTransfer | 13.69 | 0.00 | 01-JAN-00:10 | 141096.90 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 3167.26 | 0.00 | 01-JAN-00:10 | 382013.71 | 22-JUN-15:40 |
EnergyTransfer:Plant | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
WaterSystems:EnergyTransfer | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -345.719 | 0.000 | 0.000 | 32.677 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -58.744 |
CORE_MID | 0.000 | 0.000 | 0.006 | -241.114 | 0.000 | 0.000 | 32.926 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -19.029 |
CORE_TOP | 0.000 | 0.000 | 0.191 | -263.511 | 0.000 | 0.000 | 33.403 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 2.705 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.968 | -90.530 | 0.000 | 0.000 | 7.220 | 23.566 | 24.333 | 42.358 | 0.000 | 0.806 | 11.362 | 0.000 | -19.766 | 0.000 | -0.316 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.424 | -72.265 | 0.000 | 0.000 | 4.520 | 14.919 | 15.404 | 46.511 | 0.000 | 0.529 | 2.454 | 0.000 | -12.271 | 0.000 | -0.224 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.572 | -113.551 | 0.000 | 0.000 | 7.056 | 23.566 | 24.332 | 82.369 | 0.000 | 0.778 | 0.003 | 0.000 | -19.532 | 0.000 | -0.381 | -5.208 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.612 | -73.911 | 0.000 | 0.000 | 4.585 | 14.918 | 15.403 | 47.535 | 0.000 | 0.538 | 3.775 | 0.000 | -13.233 | 0.000 | -0.221 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.205 | -86.698 | 0.000 | 0.000 | 7.128 | 23.566 | 24.333 | 42.233 | 0.000 | 0.431 | 11.187 | 0.000 | -22.191 | 0.000 | -0.193 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.100 | -71.707 | 0.000 | 0.000 | 4.471 | 14.919 | 15.404 | 46.424 | 0.000 | 0.283 | 4.196 | 0.000 | -13.951 | 0.000 | -0.137 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.666 | -128.284 | 0.000 | 0.000 | 6.971 | 23.566 | 24.332 | 82.202 | 0.000 | 21.523 | 0.000 | 0.000 | -22.785 | 0.000 | -8.851 | -1.339 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.138 | -72.009 | 0.000 | 0.000 | 4.516 | 14.918 | 15.403 | 47.592 | 0.000 | 0.283 | 4.413 | 0.000 | -15.118 | 0.000 | -0.136 | -0.001 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.256 | -84.565 | 0.000 | 0.000 | 7.134 | 23.566 | 24.333 | 42.330 | 0.000 | 0.666 | 8.344 | 0.000 | -21.767 | 0.000 | -0.297 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.141 | -68.129 | 0.000 | 0.000 | 3.316 | 14.919 | 15.404 | 46.370 | 0.000 | 0.439 | 1.096 | 0.000 | -13.349 | 0.000 | -0.207 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.123 | -108.512 | 0.000 | 0.000 | 6.991 | 23.566 | 24.332 | 82.383 | 0.000 | 0.644 | 0.000 | 0.000 | -21.386 | 0.000 | -0.351 | -7.790 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.195 | -70.436 | 0.000 | 0.000 | 4.537 | 14.918 | 15.403 | 47.603 | 0.000 | 0.443 | 2.055 | 0.000 | -14.514 | 0.000 | -0.205 | -0.001 |
TOPFLOOR_PLENUM | 6.303 | -124.086 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.019 | 117.294 | 0.000 | 0.000 | 0.000 | -0.530 | -0.001 |
MIDFLOOR_PLENUM | 1.041 | -55.028 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.029 | 53.528 | 0.000 | 0.000 | 0.000 | -0.570 | -0.000 |
FIRSTFLOOR_PLENUM | 0.502 | -64.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.791 | 63.308 | 0.000 | 0.000 | 0.000 | -0.488 | -0.001 |
Total Facility | 7.846 | -243.226 | 6.596 | -1890.941 | 0.000 | 0.000 | 167.451 | 566.263 | 729.266 | 655.910 | 0.000 | 30.200 | 285.722 | 0.000 | -209.864 | 0.000 | -13.109 | -92.117 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 25-MAY-04:01 | 0.00 | 0.00 | 0.00 | -54381.18 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 47330.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-04:03 | 0.00 | 0.00 | 0.00 | -46263.60 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 42737.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-APR-04:01 | 0.00 | 0.00 | 0.00 | -53363.02 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 49836.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 29-MAY-16:12 | 0.00 | 0.00 | 0.00 | -23248.30 | 0.00 | 0.00 | 22.08 | 114.31 | 478.42 | 5159.02 | 0.00 | 244.40 | 17230.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 16-APR-08:31 | 0.00 | 0.00 | 0.00 | -18645.59 | 0.00 | 0.00 | 12.87 | 72.37 | 302.86 | 9862.50 | 0.00 | 2.52 | 8392.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 08-OCT-12:41 | 0.00 | 0.00 | 0.00 | -25253.02 | 0.00 | 0.00 | 20.59 | 114.31 | 478.41 | 12200.74 | 0.00 | 21.79 | 12417.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:12 | 0.00 | 0.00 | 0.00 | -21818.40 | 0.00 | 0.00 | 8.35 | 72.36 | 302.86 | 10091.97 | 0.00 | 143.50 | 11199.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 02-JUL-16:41 | 0.00 | 0.00 | 0.00 | -18702.12 | 0.00 | 0.00 | 24.69 | 114.31 | 478.42 | 5673.52 | 0.00 | 113.34 | 12297.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-09:21 | 0.00 | 0.00 | 0.00 | -16148.91 | 0.00 | 0.00 | 13.78 | 72.37 | 302.86 | 7610.19 | 0.00 | 84.02 | 8065.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-12:01 | 0.00 | 0.00 | 0.00 | -21417.67 | 0.00 | 0.00 | 20.01 | 114.31 | 478.41 | 13709.05 | 0.00 | 32.63 | 7063.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-16:01 | 0.00 | 0.00 | 0.00 | -18237.17 | 0.00 | 0.00 | 11.18 | 72.36 | 302.86 | 9900.89 | 0.00 | 65.26 | 7884.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 29-MAY-15:21 | 0.00 | 0.00 | 0.00 | -20017.44 | 0.00 | 0.00 | 24.15 | 114.31 | 478.42 | 5401.50 | 0.00 | 275.18 | 13723.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 16-APR-09:41 | 0.00 | 0.00 | 0.00 | -18226.28 | 0.00 | 0.00 | 11.67 | 72.37 | 302.86 | 9346.55 | 0.00 | 10.91 | 8481.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-12:01 | 0.00 | 0.00 | 0.00 | -22066.61 | 0.00 | 0.00 | 19.86 | 114.31 | 478.41 | 13638.30 | 0.00 | 50.65 | 7765.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 29-MAY-16:01 | 0.00 | 0.00 | 0.00 | -20364.12 | 0.00 | 0.00 | 9.55 | 72.36 | 302.86 | 10382.66 | 0.00 | 115.54 | 9481.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 29-MAY-15:31 | 0.00 | -35709.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.84 | 35355.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 20-DEC-06:12 | 0.00 | -13309.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13357.69 | 0.00 | -0.00 | 0.00 | -48.05 | 0.00 |
FIRSTFLOOR_PLENUM | 06-JAN-06:12 | 0.00 | -14280.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14280.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-MAY-04:01 | 0.00 | 16828.76 | 0.00 | -306895.03 | 0.00 | 0.00 | 0.00 | 5493.69 | 15894.33 | 877.70 | 0.00 | 995.94 | 266804.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:03 | 0.00 | 0.00 | 24289.53 | 0.00 | 0.00 | 0.00 | 916.05 | 3253.54 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31485.03 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 57646.90 | 0.00 | 0.00 | 0.00 | 507.92 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -62265.24 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 24661.89 | 0.00 | 0.00 | 0.00 | 113.18 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2527.24 | 0.00 | 0.00 | -23114.34 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 18263.41 | 0.00 | 0.00 | 0.00 | 71.65 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1685.39 | 0.00 | 0.00 | -17198.22 |
PERIMETER_TOP_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 24755.66 | 0.00 | 0.00 | 0.00 | 113.17 | 228.62 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2581.39 | 0.00 | 0.00 | -23153.96 |
PERIMETER_TOP_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 20286.28 | 0.00 | 0.00 | 0.00 | 71.65 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1692.35 | 0.00 | 0.00 | -19214.11 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 24040.71 | 0.00 | 0.00 | 0.00 | 103.71 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3249.30 | 0.00 | 0.00 | -21761.64 |
PERIMETER_BOT_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 18741.32 | 0.00 | 0.00 | 0.00 | 65.64 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2188.54 | 0.00 | 0.00 | -17166.98 |
PERIMETER_BOT_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 23979.28 | 0.00 | 0.00 | 0.00 | 104.14 | 228.62 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3401.99 | 0.00 | -2496.78 | -19051.16 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 18164.86 | 0.00 | 0.00 | 0.00 | 65.59 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2196.48 | 0.00 | 0.00 | -16582.51 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 23504.62 | 0.00 | 0.00 | 0.00 | 107.60 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2997.10 | 0.00 | 0.00 | -21481.63 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 19310.13 | 0.00 | 0.00 | 0.00 | 68.51 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1985.10 | 0.00 | 0.00 | -17942.09 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 23389.89 | 0.00 | 0.00 | 0.00 | 106.62 | 228.62 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3076.16 | 0.00 | 0.00 | -21286.85 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 20388.08 | 0.00 | 0.00 | 0.00 | 68.47 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1993.44 | 0.00 | 0.00 | -19011.64 |
TOPFLOOR_PLENUM | 02-JAN-06:15 | 39264.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39264.68 |
MIDFLOOR_PLENUM | 02-JAN-07:15 | 8954.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8954.96 |
FIRSTFLOOR_PLENUM | 18-AUG-04:01 | 6617.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6649.05 |
Total Facility | 02-JAN-06:11 | -16633.47 | 15207.96 | 317133.01 | -15207.96 | 0.00 | 0.00 | 2420.75 | 5493.69 | 20036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29574.47 | 0.00 | -2496.78 | -296379.08 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 7.4419 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.9785 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 7.0160 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.5060 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 8.2584 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.1071 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.2326 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2326 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.1048 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.1048 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.4775 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.4775 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 3.4443 | 3.4443 | 1.0333 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.8722 | 2.8722 | 0.8617 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 3.5041 | 3.5041 | 1.0512 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.3178 | 1.3178 | 0.3953 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9911 | 0.9911 | 0.2973 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.3315 | 1.3315 | 0.3995 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.1138 | 1.1138 | 0.3341 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0781 | 1.0781 | 0.3234 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.8871 | 0.8871 | 0.2661 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0951 | 1.0951 | 0.3285 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9373 | 0.9373 | 0.2812 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.1095 | 1.1095 | 0.3328 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9232 | 0.9232 | 0.2770 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.1279 | 1.1279 | 0.3384 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9832 | 0.9832 | 0.2950 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 7.4419 | 6.9785 | 7.4419 | 2.2326 | 0.0000 | 1.0000 |
PACU_VAV_MID | 7.0160 | 6.5060 | 7.0160 | 2.1048 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 8.2584 | 8.1071 | 8.2584 | 2.4775 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0333 | 4.4777 | 1.0333 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.8617 | 3.7338 | 0.8617 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0512 | 4.5554 | 1.0512 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3953 | 1.7132 | 0.3953 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2973 | 1.2885 | 0.2973 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3995 | 1.7310 | 0.3995 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3341 | 1.4479 | 0.3341 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3234 | 1.4015 | 0.3234 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2661 | 1.1532 | 0.2661 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3285 | 1.4236 | 0.3285 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2812 | 1.2185 | 0.2812 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3328 | 1.4423 | 0.3328 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2770 | 1.2002 | 0.2770 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3384 | 1.4663 | 0.3384 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2950 | 1.2782 | 0.2950 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.2326 | 2.2326 | 9.6745 | 2.2326 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.1048 | 2.1048 | 9.1208 | 2.1048 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.4775 | 2.4775 | 10.7359 | 2.4775 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 385.67 |
Number of hours not met | 385.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 13.69 | 141096.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 847.49 | 131417.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 236.03 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 262.21 | 35339.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 38.75 | 5342.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 2721.34 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2721.34 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 2.75 |
Space Cooling | 170.10 |
Fans (All) | 52.63 |
Service Water Heating | 7.78 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 546.22 |
Subtotal | 546.22 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.81 |
Space Heating | 0.50 |
Space Cooling | 31.14 |
Fans (All) | 9.64 |
Service Water Heating | 1.42 |
Receptacle Equipment | 26.80 |
Miscellaneous | 9.69 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7796.17 | 963.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8702.67 | 57.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8682.17 | 77.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8225.50 | 534.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8177.83 | 582.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8132.67 | 627.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8108.17 | 651.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8282.17 | 477.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8180.17 | 579.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8044.83 | 715.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8056.50 | 703.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8202.00 | 558.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8161.67 | 598.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8080.50 | 679.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8044.17 | 715.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8041.83 | 718.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8698.17 | 61.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
Min | 7796.17 | 21.33 | 0.00 | 0.00 | 0.00 |
Max | 8738.67 | 963.83 | 0.00 | 0.00 | 0.00 |
Average | 8241.99 | 518.01 | 0.00 | 0.00 | 0.00 |
Sum | 148355.83 | 9324.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 127972.00 | 332.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128292.00 | 12.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128287.33 | 16.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24819.67 | 89.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128292.00 | 332.00 | 0.00 | 0.00 | 0.00 |
Average | 34118.33 | 25.00 | 0.00 | 0.00 | 0.00 |
Sum | 614130.00 | 450.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7211.33 | 1548.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7526.00 | 1234.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7574.33 | 1185.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7287.33 | 1472.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7299.17 | 1460.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7222.67 | 1537.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7319.50 | 1440.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7256.83 | 1503.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7281.33 | 1478.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6492.17 | 2267.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7262.50 | 1497.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7182.83 | 1577.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7235.00 | 1525.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7105.50 | 1654.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7218.50 | 1541.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 5527.67 | 3232.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 6976.50 | 1783.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6823.83 | 1936.17 | 0.00 | 0.00 | 0.00 |
Min | 5527.67 | 1185.67 | 0.00 | 0.00 | 0.00 |
Max | 7574.33 | 3232.33 | 0.00 | 0.00 | 0.00 |
Average | 7100.17 | 1659.83 | 0.00 | 0.00 | 0.00 |
Sum | 127803.00 | 29877.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127524.33 | 779.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127732.50 | 571.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127699.67 | 604.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24900.50 | 8.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24900.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24903.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 21658.33 | 3250.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24895.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24896.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127732.50 | 3250.67 | 0.00 | 0.00 | 0.00 |
Average | 33851.38 | 291.95 | 0.00 | 0.00 | 0.00 |
Sum | 609324.83 | 5255.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187538E+11 | 21035.78 | 13-JAN-17:00 | 20.30 | 14.67 | 0.198338E+10 | 2606.69 | 23-JAN-14:09 | 17.67 | 10.95 |
February | 0.202683E+11 | 31971.86 | 27-FEB-07:03 | 11.00 | 10.65 | 0.180701E+10 | 2606.69 | 01-FEB-14:09 | 11.00 | 10.65 |
March | 0.286450E+11 | 49041.26 | 13-MAR-05:12 | 20.73 | 15.50 | 0.216091E+10 | 2606.69 | 01-MAR-10:00 | 20.73 | 15.50 |
April | 0.305160E+11 | 54093.02 | 26-APR-04:02 | 24.73 | 20.70 | 0.191936E+10 | 2606.69 | 04-APR-09:50 | 24.73 | 20.70 |
May | 0.347550E+11 | 54393.33 | 25-MAY-04:01 | 26.00 | 23.62 | 0.207744E+10 | 2606.69 | 02-MAY-13:00 | 26.00 | 23.62 |
June | 0.343955E+11 | 53763.99 | 28-JUN-04:02 | 26.40 | 25.32 | 0.207054E+10 | 2606.69 | 20-JUN-13:30 | 26.40 | 25.32 |
July | 0.338086E+11 | 53644.61 | 19-JUL-04:02 | 24.72 | 24.59 | 0.192451E+10 | 2606.69 | 03-JUL-13:20 | 24.72 | 24.59 |
August | 0.350573E+11 | 53375.71 | 24-AUG-04:02 | 25.48 | 24.97 | 0.216095E+10 | 2606.69 | 02-AUG-13:09 | 25.48 | 24.97 |
September | 0.317465E+11 | 53882.74 | 07-SEP-04:02 | 24.78 | 23.91 | 0.192020E+10 | 2606.69 | 01-SEP-09:30 | 24.78 | 23.91 |
October | 0.309561E+11 | 49196.93 | 07-OCT-05:12 | 21.73 | 20.00 | 0.199695E+10 | 2606.69 | 03-OCT-13:39 | 21.73 | 20.00 |
November | 0.260196E+11 | 48886.78 | 13-NOV-06:12 | 15.27 | 12.05 | 0.197517E+10 | 2606.69 | 27-NOV-14:09 | 26.35 | 13.94 |
December | 0.207961E+11 | 24068.95 | 01-DEC-07:03 | 12.92 | 9.54 | 0.192076E+10 | 2606.69 | 15-DEC-10:09 | 14.62 | 12.17 |
Annual Sum or Average | 0.345718E+12 | 0.239172E+11 | ||||||||
Minimum of Months | 0.187538E+11 | 21035.78 | 11.00 | 9.54 | 0.180701E+10 | 2606.69 | 11.00 | 10.65 | ||
Maximum of Months | 0.350573E+11 | 54393.33 | 26.40 | 25.32 | 0.216095E+10 | 2606.69 | 26.40 | 25.32 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250791E+10 | 7125.66 | 31-JAN-14:10 | 21.07 | 11.19 | 0.00 | 0.00 | 01-JAN-00:10 | 21.07 | 11.19 |
February | 0.427596E+10 | 11707.87 | 22-FEB-14:10 | 27.02 | 16.30 | 0.00 | 0.00 | 01-FEB-00:10 | 27.02 | 16.30 |
March | 0.914039E+10 | 18458.47 | 28-MAR-14:50 | 35.50 | 18.44 | 0.00 | 0.00 | 01-MAR-00:10 | 35.50 | 18.44 |
April | 0.143950E+11 | 21695.03 | 26-APR-14:05 | 38.88 | 22.02 | 0.00 | 0.00 | 01-APR-00:10 | 38.88 | 22.02 |
May | 0.179359E+11 | 35706.67 | 29-MAY-15:31 | 41.30 | 21.69 | 0.00 | 0.00 | 01-MAY-00:10 | 41.30 | 21.69 |
June | 0.175959E+11 | 24817.22 | 08-JUN-14:20 | 43.90 | 22.25 | 0.00 | 0.00 | 01-JUN-00:10 | 43.90 | 22.25 |
July | 0.140919E+11 | 21790.69 | 10-JUL-13:30 | 39.20 | 26.69 | 0.00 | 0.00 | 01-JUL-00:10 | 39.20 | 26.69 |
August | 0.129923E+11 | 19579.04 | 07-AUG-14:00 | 37.20 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 37.20 | 26.26 |
September | 0.107049E+11 | 18342.61 | 26-SEP-13:50 | 35.57 | 22.93 | 0.00 | 0.00 | 01-SEP-00:10 | 35.57 | 22.93 |
October | 0.999451E+10 | 18349.15 | 02-OCT-14:05 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.615828E+10 | 13085.09 | 09-NOV-14:00 | 29.40 | 17.86 | 0.00 | 0.00 | 01-NOV-00:10 | 29.40 | 17.86 |
December | 0.288478E+10 | 7961.28 | 01-DEC-14:10 | 23.48 | 13.12 | 0.00 | 0.00 | 01-DEC-00:10 | 23.48 | 13.12 |
Annual Sum or Average | 0.122678E+12 | 0.00 | ||||||||
Minimum of Months | 0.250791E+10 | 7125.66 | 21.07 | 11.19 | 0.00 | 0.00 | 21.07 | 11.19 | ||
Maximum of Months | 0.179359E+11 | 35706.67 | 43.90 | 26.69 | 0.00 | 0.00 | 43.90 | 26.69 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438567E+09 | 2721.50 | 27-JAN-06:43 | 10.93 | 9.84 | 0.00 | 0.00 | 01-JAN-00:10 | 10.93 | 9.84 |
February | 0.131635E+10 | 3109.53 | 18-FEB-06:25 | 11.55 | 9.21 | 0.00 | 0.00 | 01-FEB-00:10 | 11.55 | 9.21 |
March | 0.365618E+10 | 5192.02 | 13-MAR-15:10 | 32.83 | 18.67 | 0.00 | 0.00 | 01-MAR-00:10 | 32.83 | 18.67 |
April | 0.580877E+10 | 6757.87 | 17-APR-14:20 | 34.40 | 21.79 | 0.00 | 0.00 | 01-APR-00:10 | 34.40 | 21.79 |
May | 0.753140E+10 | 7354.18 | 30-MAY-14:20 | 40.23 | 24.40 | 0.00 | 0.00 | 01-MAY-00:10 | 40.23 | 24.40 |
June | 0.730837E+10 | 7773.55 | 12-JUN-12:02 | 42.55 | 22.27 | 0.00 | 0.00 | 01-JUN-00:10 | 42.55 | 22.27 |
July | 0.661554E+10 | 7469.09 | 05-JUL-12:04 | 37.65 | 25.58 | 0.00 | 0.00 | 01-JUL-00:10 | 37.65 | 25.58 |
August | 0.647551E+10 | 6719.52 | 07-AUG-15:30 | 37.20 | 26.62 | 0.00 | 0.00 | 01-AUG-00:10 | 37.20 | 26.62 |
September | 0.546393E+10 | 6533.07 | 25-SEP-15:00 | 35.10 | 23.91 | 0.00 | 0.00 | 01-SEP-00:10 | 35.10 | 23.91 |
October | 0.453515E+10 | 6572.79 | 02-OCT-16:00 | 35.90 | 21.25 | 0.00 | 0.00 | 01-OCT-00:10 | 35.90 | 21.25 |
November | 0.248503E+10 | 3424.66 | 09-NOV-15:20 | 28.93 | 17.66 | 0.00 | 0.00 | 01-NOV-00:10 | 28.93 | 17.66 |
December | 0.692226E+09 | 2800.56 | 01-DEC-06:42 | 12.28 | 9.30 | 0.00 | 0.00 | 01-DEC-00:10 | 12.28 | 9.30 |
Annual Sum or Average | 0.523270E+11 | 0.00 | ||||||||
Minimum of Months | 0.438567E+09 | 2721.50 | 10.93 | 9.21 | 0.00 | 0.00 | 10.93 | 9.21 | ||
Maximum of Months | 0.753140E+10 | 7773.55 | 42.55 | 26.62 | 0.00 | 0.00 | 42.55 | 26.62 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104046E+10 | 2699.74 | 26-JAN-18:03 | 17.23 | 12.41 | 0.00 | 0.00 | 01-JAN-00:10 | 17.23 | 12.41 |
February | 0.204294E+10 | 3669.71 | 27-FEB-06:20 | 10.83 | 10.37 | 0.00 | 0.00 | 01-FEB-00:10 | 10.83 | 10.37 |
March | 0.440668E+10 | 5701.68 | 13-MAR-16:00 | 32.50 | 18.65 | 0.00 | 0.00 | 01-MAR-00:10 | 32.50 | 18.65 |
April | 0.621765E+10 | 7550.36 | 28-APR-12:07 | 36.60 | 19.98 | 0.00 | 0.00 | 01-APR-00:10 | 36.60 | 19.98 |
May | 0.773518E+10 | 9004.67 | 05-MAY-12:07 | 41.65 | 20.98 | 0.00 | 0.00 | 01-MAY-00:10 | 41.65 | 20.98 |
June | 0.765514E+10 | 9511.05 | 12-JUN-12:07 | 42.55 | 22.27 | 0.00 | 0.00 | 01-JUN-00:10 | 42.55 | 22.27 |
July | 0.724141E+10 | 9165.45 | 05-JUL-12:07 | 37.65 | 25.58 | 0.00 | 0.00 | 01-JUL-00:10 | 37.65 | 25.58 |
August | 0.736961E+10 | 7928.18 | 07-AUG-12:07 | 35.75 | 26.36 | 0.00 | 0.00 | 01-AUG-00:10 | 35.75 | 26.36 |
September | 0.639660E+10 | 7159.52 | 18-SEP-12:07 | 31.20 | 23.84 | 0.00 | 0.00 | 01-SEP-00:10 | 31.20 | 23.84 |
October | 0.562005E+10 | 7068.38 | 02-OCT-17:06 | 34.42 | 21.24 | 0.00 | 0.00 | 01-OCT-00:10 | 34.42 | 21.24 |
November | 0.356472E+10 | 4643.87 | 13-NOV-15:50 | 27.70 | 16.51 | 0.00 | 0.00 | 01-NOV-00:10 | 27.70 | 16.51 |
December | 0.179409E+10 | 2955.87 | 01-DEC-06:20 | 11.33 | 8.92 | 0.00 | 0.00 | 01-DEC-00:10 | 11.33 | 8.92 |
Annual Sum or Average | 0.610845E+11 | 0.00 | ||||||||
Minimum of Months | 0.104046E+10 | 2699.74 | 10.83 | 8.92 | 0.00 | 0.00 | 10.83 | 8.92 | ||
Maximum of Months | 0.773518E+10 | 9511.05 | 42.55 | 26.36 | 0.00 | 0.00 | 42.55 | 26.36 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111783E+11 | 13237.64 | 26-JAN-17:00 | 18.60 | 12.70 | 0.188122E+10 | 2606.69 | 26-JAN-14:00 | 18.60 | 12.70 |
February | 0.126274E+11 | 16466.76 | 23-FEB-17:00 | 23.60 | 14.87 | 0.177051E+10 | 2606.69 | 27-FEB-14:00 | 22.20 | 13.82 |
March | 0.195251E+11 | 31046.21 | 13-MAR-05:12 | 20.73 | 15.50 | 0.214887E+10 | 2606.69 | 02-MAR-14:09 | 20.73 | 15.50 |
April | 0.225341E+11 | 44049.54 | 17-APR-04:01 | 24.68 | 19.16 | 0.191532E+10 | 2606.69 | 04-APR-13:00 | 24.68 | 19.16 |
May | 0.266403E+11 | 43930.27 | 15-MAY-04:02 | 24.27 | 18.74 | 0.207482E+10 | 2606.69 | 01-MAY-09:20 | 24.27 | 18.74 |
June | 0.260883E+11 | 42676.68 | 28-JUN-04:02 | 26.40 | 25.32 | 0.206781E+10 | 2606.69 | 09-JUN-13:39 | 26.40 | 25.32 |
July | 0.251119E+11 | 41618.12 | 13-JUL-04:02 | 27.87 | 26.38 | 0.192201E+10 | 2606.69 | 03-JUL-09:39 | 27.87 | 26.38 |
August | 0.254204E+11 | 42982.01 | 16-AUG-04:02 | 24.40 | 23.90 | 0.215834E+10 | 2606.69 | 02-AUG-13:20 | 24.40 | 23.90 |
September | 0.222905E+11 | 46275.68 | 05-SEP-04:03 | 26.28 | 25.12 | 0.191697E+10 | 2606.69 | 19-SEP-13:00 | 32.90 | 24.72 |
October | 0.210494E+11 | 43102.07 | 04-OCT-04:02 | 25.08 | 21.56 | 0.199039E+10 | 2606.69 | 03-OCT-13:09 | 25.08 | 21.56 |
November | 0.164255E+11 | 17792.98 | 13-NOV-16:50 | 26.60 | 16.65 | 0.195722E+10 | 2606.69 | 22-NOV-14:09 | 26.22 | 15.35 |
December | 0.122227E+11 | 14811.15 | 01-DEC-17:00 | 21.20 | 14.26 | 0.186479E+10 | 2606.69 | 07-DEC-14:09 | 19.85 | 12.21 |
Annual Sum or Average | 0.241114E+12 | 0.236683E+11 | ||||||||
Minimum of Months | 0.111783E+11 | 13237.64 | 18.60 | 12.70 | 0.177051E+10 | 2606.69 | 18.60 | 12.21 | ||
Maximum of Months | 0.266403E+11 | 46275.68 | 27.87 | 26.38 | 0.215834E+10 | 2606.69 | 32.90 | 26.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112657E+11 | 13087.85 | 26-JAN-16:20 | 19.67 | 13.02 | 0.173980E+10 | 2606.69 | 26-JAN-14:00 | 19.67 | 13.02 |
February | 0.130024E+11 | 17998.23 | 23-FEB-15:00 | 25.80 | 14.10 | 0.168679E+10 | 2606.69 | 16-FEB-14:50 | 25.80 | 14.10 |
March | 0.206911E+11 | 23204.54 | 13-MAR-15:00 | 32.90 | 18.68 | 0.211713E+10 | 2606.69 | 02-MAR-14:20 | 32.90 | 18.68 |
April | 0.254350E+11 | 53365.74 | 17-APR-04:01 | 24.68 | 19.16 | 0.191003E+10 | 2606.69 | 20-APR-13:50 | 36.50 | 19.72 |
May | 0.309753E+11 | 52534.42 | 15-MAY-04:02 | 24.27 | 18.74 | 0.207435E+10 | 2606.69 | 01-MAY-13:00 | 24.27 | 18.74 |
June | 0.306084E+11 | 51449.59 | 20-JUN-04:01 | 28.05 | 23.71 | 0.206717E+10 | 2606.69 | 02-JUN-09:50 | 28.05 | 23.71 |
July | 0.287733E+11 | 49750.15 | 19-JUL-05:02 | 26.00 | 25.06 | 0.192163E+10 | 2606.69 | 13-JUL-13:00 | 26.00 | 25.06 |
August | 0.283270E+11 | 53060.84 | 21-AUG-04:01 | 25.67 | 25.19 | 0.215689E+10 | 2606.69 | 07-AUG-13:50 | 25.67 | 25.19 |
September | 0.240938E+11 | 52551.95 | 25-SEP-04:01 | 26.32 | 23.72 | 0.191255E+10 | 2606.69 | 05-SEP-09:30 | 26.32 | 23.72 |
October | 0.218940E+11 | 49943.97 | 04-OCT-05:02 | 25.07 | 21.35 | 0.197219E+10 | 2606.69 | 06-OCT-09:39 | 26.50 | 22.65 |
November | 0.163251E+11 | 19407.16 | 09-NOV-15:00 | 29.20 | 17.71 | 0.189765E+10 | 2606.69 | 06-NOV-14:39 | 29.20 | 17.71 |
December | 0.121189E+11 | 14515.32 | 01-DEC-16:00 | 22.30 | 13.72 | 0.173453E+10 | 2606.69 | 01-DEC-14:00 | 22.30 | 13.72 |
Annual Sum or Average | 0.263510E+12 | 0.231907E+11 | ||||||||
Minimum of Months | 0.112657E+11 | 13087.85 | 19.67 | 13.02 | 0.168679E+10 | 2606.69 | 19.67 | 13.02 | ||
Maximum of Months | 0.309753E+11 | 53365.74 | 32.90 | 25.19 | 0.215689E+10 | 2606.69 | 36.50 | 25.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237999E+10 | 3691.63 | 26-JAN-14:50 | 21.75 | 13.69 | 0.329522E+09 | 519.41 | 26-JAN-14:00 | 21.60 | 13.66 |
February | 0.345176E+10 | 5232.99 | 23-FEB-14:30 | 26.10 | 14.00 | 0.323888E+09 | 549.51 | 23-FEB-14:00 | 25.80 | 14.10 |
March | 0.635653E+10 | 8137.95 | 29-MAR-14:50 | 33.05 | 19.10 | 0.425041E+09 | 549.51 | 06-MAR-14:00 | 33.05 | 19.10 |
April | 0.909896E+10 | 21971.05 | 16-APR-15:11 | 39.57 | 22.43 | 0.398455E+09 | 549.51 | 17-APR-13:09 | 34.63 | 22.33 |
May | 0.122455E+11 | 23251.00 | 29-MAY-16:12 | 41.17 | 21.49 | 0.437312E+09 | 549.51 | 05-MAY-09:09 | 41.17 | 21.49 |
June | 0.124306E+11 | 22307.83 | 04-JUN-16:31 | 41.97 | 22.48 | 0.435853E+09 | 549.51 | 14-JUN-13:09 | 35.30 | 24.25 |
July | 0.112787E+11 | 21126.58 | 04-JUL-17:02 | 39.95 | 24.24 | 0.405415E+09 | 549.51 | 03-JUL-09:09 | 39.95 | 24.24 |
August | 0.105024E+11 | 16986.06 | 14-AUG-04:01 | 28.85 | 26.06 | 0.453866E+09 | 549.51 | 02-AUG-13:09 | 28.85 | 26.06 |
September | 0.838711E+10 | 16670.98 | 05-SEP-04:01 | 26.28 | 25.12 | 0.400476E+09 | 549.51 | 08-SEP-13:30 | 28.50 | 25.88 |
October | 0.702048E+10 | 9098.92 | 02-OCT-14:30 | 36.40 | 21.05 | 0.403316E+09 | 549.51 | 03-OCT-13:09 | 35.38 | 22.15 |
November | 0.462296E+10 | 5755.57 | 09-NOV-14:10 | 29.37 | 17.83 | 0.372732E+09 | 549.51 | 06-NOV-14:00 | 29.37 | 17.83 |
December | 0.275595E+10 | 3752.45 | 03-DEC-13:02 | 24.08 | 14.17 | 0.325022E+09 | 518.97 | 01-DEC-14:00 | 24.08 | 14.17 |
Annual Sum or Average | 0.905308E+11 | 0.471090E+10 | ||||||||
Minimum of Months | 0.237999E+10 | 3691.63 | 21.75 | 13.69 | 0.323888E+09 | 518.97 | 21.60 | 13.66 | ||
Maximum of Months | 0.124306E+11 | 23251.00 | 41.97 | 26.06 | 0.453866E+09 | 549.51 | 41.17 | 26.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214667E+10 | 2784.43 | 26-JAN-14:10 | 22.35 | 13.84 | 0.214854E+09 | 329.70 | 26-JAN-14:20 | 22.20 | 13.80 |
February | 0.291068E+10 | 4697.74 | 23-FEB-10:40 | 22.80 | 14.32 | 0.215932E+09 | 347.89 | 21-FEB-14:30 | 22.80 | 14.32 |
March | 0.544157E+10 | 7945.29 | 28-MAR-10:20 | 29.33 | 18.17 | 0.278442E+09 | 347.89 | 02-MAR-14:50 | 29.33 | 18.17 |
April | 0.793396E+10 | 18651.35 | 16-APR-08:31 | 31.90 | 20.92 | 0.254319E+09 | 348.26 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.999264E+10 | 18206.47 | 29-MAY-09:31 | 35.10 | 21.77 | 0.277005E+09 | 348.11 | 03-MAY-09:00 | 35.10 | 21.77 |
June | 0.944840E+10 | 17377.37 | 11-JUN-10:12 | 37.37 | 25.15 | 0.275597E+09 | 348.00 | 07-JUN-09:00 | 37.37 | 25.15 |
July | 0.825432E+10 | 17214.38 | 04-JUL-10:22 | 35.80 | 25.02 | 0.256244E+09 | 347.97 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.764446E+10 | 12771.39 | 06-AUG-10:42 | 33.30 | 25.72 | 0.286722E+09 | 347.89 | 02-AUG-13:09 | 33.30 | 25.72 |
September | 0.649915E+10 | 10385.68 | 05-SEP-04:01 | 26.28 | 25.12 | 0.253453E+09 | 347.89 | 19-SEP-13:09 | 32.48 | 24.54 |
October | 0.582305E+10 | 13540.42 | 15-OCT-11:02 | 31.10 | 17.89 | 0.259133E+09 | 347.89 | 06-OCT-13:00 | 31.10 | 17.89 |
November | 0.380949E+10 | 4911.44 | 09-NOV-10:30 | 25.75 | 18.10 | 0.247545E+09 | 347.89 | 06-NOV-14:50 | 25.75 | 18.10 |
December | 0.236055E+10 | 3176.20 | 03-DEC-13:02 | 24.08 | 14.17 | 0.213444E+09 | 339.66 | 01-DEC-10:50 | 24.08 | 14.17 |
Annual Sum or Average | 0.722649E+11 | 0.303269E+10 | ||||||||
Minimum of Months | 0.214667E+10 | 2784.43 | 22.35 | 13.84 | 0.213444E+09 | 329.70 | 22.20 | 13.80 | ||
Maximum of Months | 0.999264E+10 | 18651.35 | 37.37 | 25.72 | 0.286722E+09 | 348.26 | 37.37 | 25.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469489E+10 | 9503.52 | 12-JAN-14:00 | 23.30 | 13.98 | 0.375762E+09 | 549.51 | 03-JAN-14:09 | 23.30 | 13.98 |
February | 0.572863E+10 | 23572.46 | 20-FEB-13:32 | 26.23 | 13.43 | 0.349920E+09 | 549.51 | 15-FEB-14:39 | 26.23 | 13.43 |
March | 0.927476E+10 | 22750.78 | 05-MAR-14:32 | 29.00 | 17.51 | 0.435978E+09 | 549.67 | 13-MAR-13:50 | 32.32 | 18.86 |
April | 0.110654E+11 | 23377.02 | 16-APR-14:31 | 39.63 | 22.15 | 0.399297E+09 | 549.65 | 27-APR-13:00 | 39.60 | 19.54 |
May | 0.126854E+11 | 23461.52 | 29-MAY-16:12 | 41.17 | 21.49 | 0.437144E+09 | 549.51 | 01-MAY-09:20 | 41.17 | 21.49 |
June | 0.123542E+11 | 22391.71 | 04-JUN-15:51 | 42.30 | 22.20 | 0.435720E+09 | 549.51 | 02-JUN-13:30 | 42.30 | 22.20 |
July | 0.113568E+11 | 20763.04 | 04-JUL-16:22 | 39.80 | 24.49 | 0.405349E+09 | 549.51 | 03-JUL-09:09 | 39.80 | 24.49 |
August | 0.110439E+11 | 20884.77 | 06-AUG-15:22 | 36.30 | 26.24 | 0.453875E+09 | 549.51 | 24-AUG-13:09 | 34.37 | 27.89 |
September | 0.101156E+11 | 22486.99 | 24-SEP-13:52 | 35.10 | 24.61 | 0.401138E+09 | 549.65 | 29-SEP-13:00 | 35.10 | 22.47 |
October | 0.110504E+11 | 25253.33 | 08-OCT-12:41 | 31.85 | 19.14 | 0.410516E+09 | 549.73 | 04-OCT-13:00 | 31.85 | 19.14 |
November | 0.886420E+10 | 23803.09 | 23-NOV-13:02 | 25.77 | 14.30 | 0.398338E+09 | 549.76 | 09-NOV-14:09 | 25.77 | 14.30 |
December | 0.531770E+10 | 20218.10 | 03-DEC-13:02 | 24.08 | 14.17 | 0.371238E+09 | 549.51 | 21-DEC-14:09 | 14.77 | 8.46 |
Annual Sum or Average | 0.113552E+12 | 0.487427E+10 | ||||||||
Minimum of Months | 0.469489E+10 | 9503.52 | 23.30 | 13.43 | 0.349920E+09 | 549.51 | 14.77 | 8.46 | ||
Maximum of Months | 0.126854E+11 | 25253.33 | 42.30 | 26.24 | 0.453875E+09 | 549.76 | 42.30 | 27.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211480E+10 | 4059.27 | 31-JAN-16:00 | 21.10 | 11.23 | 0.214602E+09 | 346.71 | 12-JAN-14:00 | 21.10 | 11.23 |
February | 0.299260E+10 | 9515.48 | 20-FEB-16:12 | 25.27 | 14.30 | 0.204702E+09 | 347.86 | 23-FEB-14:00 | 25.80 | 14.10 |
March | 0.567372E+10 | 16252.50 | 05-MAR-15:52 | 28.80 | 17.84 | 0.263787E+09 | 347.86 | 13-MAR-13:20 | 32.07 | 18.93 |
April | 0.801527E+10 | 20100.55 | 16-APR-15:11 | 39.57 | 22.43 | 0.249610E+09 | 347.86 | 03-APR-13:50 | 39.57 | 22.43 |
May | 0.995613E+10 | 21821.34 | 29-MAY-16:12 | 41.17 | 21.49 | 0.275469E+09 | 347.86 | 18-MAY-13:30 | 41.17 | 21.49 |
June | 0.980886E+10 | 20535.21 | 04-JUN-15:51 | 42.30 | 22.20 | 0.274619E+09 | 347.86 | 06-JUN-13:30 | 43.30 | 22.42 |
July | 0.834585E+10 | 18944.79 | 09-JUL-15:52 | 36.40 | 27.43 | 0.254851E+09 | 347.86 | 07-JUL-13:50 | 36.40 | 27.43 |
August | 0.775455E+10 | 18996.30 | 06-AUG-16:02 | 36.25 | 26.27 | 0.285008E+09 | 347.86 | 02-AUG-13:09 | 36.25 | 26.27 |
September | 0.667849E+10 | 18927.89 | 24-SEP-15:52 | 34.80 | 25.26 | 0.250414E+09 | 347.86 | 19-SEP-13:20 | 34.80 | 25.26 |
October | 0.600365E+10 | 19308.47 | 08-OCT-16:02 | 31.85 | 19.36 | 0.250823E+09 | 347.86 | 10-OCT-13:39 | 31.70 | 20.72 |
November | 0.416901E+10 | 7100.30 | 08-NOV-15:20 | 29.67 | 18.20 | 0.233550E+09 | 347.86 | 09-NOV-14:00 | 29.20 | 17.71 |
December | 0.239949E+10 | 4571.97 | 01-DEC-15:30 | 22.85 | 13.56 | 0.210337E+09 | 347.86 | 01-DEC-14:00 | 22.85 | 13.56 |
Annual Sum or Average | 0.739124E+11 | 0.296777E+10 | ||||||||
Minimum of Months | 0.211480E+10 | 4059.27 | 21.10 | 11.23 | 0.204702E+09 | 346.71 | 21.10 | 11.23 | ||
Maximum of Months | 0.995613E+10 | 21821.34 | 42.30 | 27.43 | 0.285008E+09 | 347.86 | 43.30 | 27.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268281E+10 | 3037.48 | 26-JAN-14:20 | 22.20 | 13.80 | 0.341081E+09 | 521.03 | 26-JAN-14:30 | 22.05 | 13.77 |
February | 0.322560E+10 | 4047.04 | 24-FEB-15:10 | 26.38 | 17.40 | 0.331960E+09 | 549.51 | 24-FEB-14:00 | 26.38 | 17.40 |
March | 0.518538E+10 | 6343.04 | 29-MAR-15:20 | 33.03 | 18.92 | 0.432551E+09 | 549.51 | 28-MAR-13:20 | 33.03 | 18.92 |
April | 0.741284E+10 | 8627.18 | 27-APR-04:01 | 29.08 | 19.93 | 0.400913E+09 | 549.51 | 05-APR-13:20 | 29.08 | 19.93 |
May | 0.106046E+11 | 17817.46 | 28-MAY-16:21 | 42.00 | 19.52 | 0.437740E+09 | 549.51 | 09-MAY-09:50 | 42.00 | 19.52 |
June | 0.113896E+11 | 17958.00 | 11-JUN-16:51 | 43.10 | 23.03 | 0.436593E+09 | 549.51 | 14-JUN-13:09 | 35.30 | 24.25 |
July | 0.111411E+11 | 18711.53 | 02-JUL-16:41 | 40.32 | 26.53 | 0.406364E+09 | 549.51 | 03-JUL-09:20 | 32.33 | 25.34 |
August | 0.109815E+11 | 16642.60 | 06-AUG-15:11 | 36.30 | 26.24 | 0.455660E+09 | 549.51 | 02-AUG-13:09 | 36.30 | 26.24 |
September | 0.895351E+10 | 17628.49 | 24-SEP-15:41 | 34.85 | 25.19 | 0.404245E+09 | 549.51 | 25-SEP-13:50 | 35.12 | 24.01 |
October | 0.716780E+10 | 12885.72 | 01-OCT-16:01 | 35.32 | 20.17 | 0.416581E+09 | 549.51 | 06-OCT-13:20 | 30.87 | 22.40 |
November | 0.464978E+10 | 5315.67 | 09-NOV-14:10 | 29.37 | 17.83 | 0.394875E+09 | 549.51 | 09-NOV-14:09 | 29.37 | 17.83 |
December | 0.330449E+10 | 3872.12 | 03-DEC-14:02 | 24.35 | 14.18 | 0.344135E+09 | 534.24 | 01-DEC-14:00 | 24.35 | 14.18 |
Annual Sum or Average | 0.866990E+11 | 0.480270E+10 | ||||||||
Minimum of Months | 0.268281E+10 | 3037.48 | 22.20 | 13.80 | 0.331960E+09 | 521.03 | 22.05 | 13.77 | ||
Maximum of Months | 0.113896E+11 | 18711.53 | 43.10 | 26.53 | 0.455660E+09 | 549.51 | 42.00 | 26.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245814E+10 | 2582.81 | 26-JAN-10:40 | 18.90 | 13.09 | 0.224288E+09 | 338.62 | 26-JAN-10:50 | 19.30 | 13.14 |
February | 0.290575E+10 | 4430.89 | 23-FEB-10:30 | 22.35 | 14.32 | 0.220501E+09 | 347.89 | 23-FEB-14:50 | 25.90 | 14.07 |
March | 0.483661E+10 | 10550.76 | 12-MAR-09:32 | 25.13 | 16.98 | 0.281205E+09 | 347.89 | 10-MAR-14:20 | 25.13 | 16.98 |
April | 0.698447E+10 | 15161.61 | 16-APR-10:02 | 35.32 | 21.70 | 0.254905E+09 | 347.97 | 28-APR-09:39 | 33.23 | 18.26 |
May | 0.909189E+10 | 15628.41 | 29-MAY-09:42 | 35.45 | 21.98 | 0.277231E+09 | 348.05 | 26-MAY-09:00 | 35.45 | 21.98 |
June | 0.888130E+10 | 15324.21 | 11-JUN-10:12 | 37.37 | 25.15 | 0.276146E+09 | 347.96 | 12-JUN-09:00 | 40.00 | 22.14 |
July | 0.825601E+10 | 16159.64 | 02-JUL-09:21 | 34.90 | 25.85 | 0.257090E+09 | 347.91 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.802835E+10 | 15616.41 | 06-AUG-09:52 | 32.30 | 25.19 | 0.288234E+09 | 347.89 | 02-AUG-13:09 | 32.30 | 25.19 |
September | 0.701197E+10 | 15178.78 | 24-SEP-09:42 | 30.85 | 25.27 | 0.255563E+09 | 347.89 | 18-SEP-09:50 | 30.85 | 25.27 |
October | 0.622292E+10 | 15734.08 | 01-OCT-10:02 | 30.08 | 19.42 | 0.264159E+09 | 347.89 | 25-OCT-13:30 | 30.65 | 18.10 |
November | 0.414316E+10 | 5173.44 | 01-NOV-10:00 | 23.40 | 14.90 | 0.255900E+09 | 347.89 | 01-NOV-13:09 | 28.17 | 15.90 |
December | 0.288665E+10 | 3410.74 | 03-DEC-14:02 | 24.35 | 14.18 | 0.226515E+09 | 347.89 | 01-DEC-10:00 | 24.35 | 14.18 |
Annual Sum or Average | 0.717072E+11 | 0.308174E+10 | ||||||||
Minimum of Months | 0.245814E+10 | 2582.81 | 18.90 | 13.09 | 0.220501E+09 | 338.62 | 19.30 | 13.14 | ||
Maximum of Months | 0.909189E+10 | 16159.64 | 37.37 | 25.85 | 0.288234E+09 | 348.05 | 40.00 | 25.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419721E+10 | 9475.90 | 08-JAN-14:43 | 22.80 | 13.74 | 0.378566E+09 | 549.51 | 12-JAN-14:20 | 23.40 | 14.05 |
February | 0.513604E+10 | 14599.59 | 20-FEB-13:43 | 26.32 | 13.45 | 0.354999E+09 | 549.51 | 23-FEB-14:09 | 26.30 | 13.93 |
March | 0.882828E+10 | 19657.02 | 12-MAR-12:52 | 30.70 | 19.02 | 0.442218E+09 | 610.91 | 28-MAR-12:09 | 33.22 | 18.26 |
April | 0.117589E+11 | 18557.76 | 16-APR-13:22 | 39.30 | 21.89 | 0.406039E+09 | 682.99 | 27-APR-12:09 | 38.00 | 21.24 |
May | 0.147055E+11 | 19871.38 | 03-MAY-16:20 | 43.93 | 21.05 | 0.445698E+09 | 733.85 | 01-MAY-12:09 | 43.93 | 21.05 |
June | 0.149971E+11 | 20189.60 | 07-JUN-16:50 | 44.18 | 21.64 | 0.443975E+09 | 746.09 | 12-JUN-12:09 | 42.55 | 22.27 |
July | 0.138192E+11 | 18866.13 | 02-JUL-16:01 | 40.38 | 26.40 | 0.409874E+09 | 684.08 | 07-JUL-12:09 | 39.13 | 24.79 |
August | 0.141614E+11 | 18384.70 | 06-AUG-14:31 | 36.17 | 26.28 | 0.458956E+09 | 643.86 | 07-AUG-12:09 | 35.75 | 26.36 |
September | 0.128014E+11 | 19717.37 | 17-SEP-13:32 | 34.27 | 26.14 | 0.408093E+09 | 669.86 | 29-SEP-12:09 | 35.52 | 22.70 |
October | 0.130690E+11 | 21417.92 | 01-OCT-12:01 | 34.03 | 19.84 | 0.423476E+09 | 697.35 | 02-OCT-12:09 | 35.70 | 21.30 |
November | 0.960990E+10 | 20774.30 | 12-NOV-12:51 | 27.70 | 16.23 | 0.408639E+09 | 586.23 | 09-NOV-13:09 | 27.70 | 16.23 |
December | 0.520081E+10 | 18430.29 | 03-DEC-14:02 | 24.35 | 14.18 | 0.379372E+09 | 549.51 | 05-DEC-14:50 | 21.72 | 14.57 |
Annual Sum or Average | 0.128285E+12 | 0.495990E+10 | ||||||||
Minimum of Months | 0.419721E+10 | 9475.90 | 22.80 | 13.45 | 0.354999E+09 | 549.51 | 21.72 | 13.93 | ||
Maximum of Months | 0.149971E+11 | 21417.92 | 44.18 | 26.40 | 0.458956E+09 | 746.09 | 43.93 | 26.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240715E+10 | 3361.94 | 31-JAN-16:00 | 21.10 | 11.23 | 0.220971E+09 | 347.57 | 25-JAN-14:00 | 21.10 | 11.23 |
February | 0.291161E+10 | 5064.29 | 21-FEB-16:00 | 26.10 | 15.66 | 0.210352E+09 | 347.86 | 23-FEB-14:00 | 25.80 | 14.10 |
March | 0.492834E+10 | 15906.46 | 12-MAR-16:12 | 31.07 | 19.87 | 0.270048E+09 | 347.86 | 14-MAR-13:50 | 28.78 | 17.30 |
April | 0.693484E+10 | 16585.99 | 30-APR-16:01 | 37.68 | 18.13 | 0.252883E+09 | 347.86 | 19-APR-13:30 | 37.68 | 18.13 |
May | 0.892246E+10 | 17057.53 | 28-MAY-16:21 | 42.00 | 19.52 | 0.276699E+09 | 347.86 | 02-MAY-13:39 | 42.00 | 19.52 |
June | 0.914991E+10 | 16933.39 | 11-JUN-16:11 | 43.30 | 23.15 | 0.276039E+09 | 347.86 | 14-JUN-13:09 | 35.30 | 24.25 |
July | 0.820824E+10 | 18250.16 | 02-JUL-16:01 | 40.38 | 26.40 | 0.256832E+09 | 347.86 | 10-JUL-09:00 | 34.40 | 26.59 |
August | 0.801575E+10 | 16418.27 | 06-AUG-15:51 | 36.30 | 26.24 | 0.288031E+09 | 347.86 | 02-AUG-13:09 | 36.30 | 26.24 |
September | 0.706739E+10 | 17463.60 | 24-SEP-15:41 | 34.85 | 25.19 | 0.255284E+09 | 347.86 | 01-SEP-13:30 | 34.85 | 25.19 |
October | 0.618577E+10 | 17582.14 | 01-OCT-16:01 | 35.32 | 20.17 | 0.262131E+09 | 347.86 | 03-OCT-13:09 | 35.38 | 22.15 |
November | 0.436419E+10 | 11614.94 | 05-NOV-15:02 | 28.82 | 17.45 | 0.246801E+09 | 347.86 | 09-NOV-14:00 | 29.20 | 17.71 |
December | 0.291409E+10 | 4135.34 | 01-DEC-15:30 | 22.85 | 13.56 | 0.220325E+09 | 347.86 | 01-DEC-14:00 | 22.85 | 13.56 |
Annual Sum or Average | 0.720097E+11 | 0.303640E+10 | ||||||||
Minimum of Months | 0.240715E+10 | 3361.94 | 21.10 | 11.23 | 0.210352E+09 | 347.57 | 21.10 | 11.23 | ||
Maximum of Months | 0.914991E+10 | 18250.16 | 43.30 | 26.40 | 0.288031E+09 | 347.86 | 42.00 | 26.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261007E+10 | 3220.34 | 26-JAN-14:40 | 21.90 | 13.73 | 0.340459E+09 | 533.23 | 26-JAN-14:50 | 21.75 | 13.69 |
February | 0.339589E+10 | 4851.69 | 23-FEB-14:30 | 26.10 | 14.00 | 0.336945E+09 | 549.51 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.587451E+10 | 7342.77 | 29-MAR-14:50 | 33.05 | 19.10 | 0.437396E+09 | 549.51 | 22-MAR-13:30 | 33.05 | 19.10 |
April | 0.828606E+10 | 18437.23 | 30-APR-15:51 | 37.80 | 18.20 | 0.401992E+09 | 549.51 | 03-APR-13:39 | 37.80 | 18.20 |
May | 0.111383E+11 | 20018.22 | 29-MAY-15:21 | 41.30 | 21.75 | 0.438022E+09 | 549.51 | 04-MAY-09:39 | 41.30 | 21.75 |
June | 0.112862E+11 | 18512.22 | 04-JUN-16:31 | 41.97 | 22.48 | 0.436498E+09 | 549.51 | 05-JUN-13:20 | 42.30 | 22.45 |
July | 0.103040E+11 | 18269.92 | 02-JUL-16:41 | 40.32 | 26.53 | 0.406105E+09 | 549.51 | 20-JUL-13:30 | 34.05 | 26.39 |
August | 0.971680E+10 | 13530.75 | 21-AUG-04:01 | 25.67 | 25.19 | 0.455090E+09 | 549.51 | 02-AUG-13:00 | 25.67 | 25.19 |
September | 0.783337E+10 | 17663.41 | 24-SEP-15:41 | 34.85 | 25.19 | 0.403021E+09 | 549.51 | 05-SEP-09:39 | 34.85 | 25.19 |
October | 0.657827E+10 | 11403.86 | 01-OCT-16:01 | 35.32 | 20.17 | 0.412480E+09 | 549.51 | 02-OCT-13:50 | 36.37 | 21.07 |
November | 0.449599E+10 | 5344.95 | 09-NOV-14:10 | 29.37 | 17.83 | 0.388680E+09 | 549.51 | 08-NOV-14:30 | 29.37 | 17.83 |
December | 0.304629E+10 | 3825.55 | 03-DEC-13:12 | 24.17 | 14.17 | 0.339841E+09 | 533.82 | 01-DEC-14:00 | 24.17 | 14.17 |
Annual Sum or Average | 0.845658E+11 | 0.479653E+10 | ||||||||
Minimum of Months | 0.261007E+10 | 3220.34 | 21.90 | 13.73 | 0.336945E+09 | 533.23 | 21.75 | 13.69 | ||
Maximum of Months | 0.112862E+11 | 20018.22 | 41.97 | 26.53 | 0.455090E+09 | 549.51 | 42.30 | 26.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234389E+10 | 2694.72 | 26-JAN-11:20 | 20.27 | 13.36 | 0.161948E+09 | 330.73 | 26-JAN-11:30 | 20.55 | 13.44 |
February | 0.297764E+10 | 5862.71 | 22-FEB-11:05 | 23.90 | 14.68 | 0.161497E+09 | 356.46 | 22-FEB-11:09 | 23.90 | 14.68 |
March | 0.516867E+10 | 14004.83 | 12-MAR-09:32 | 25.13 | 16.98 | 0.206844E+09 | 356.46 | 24-MAR-12:09 | 25.92 | 14.87 |
April | 0.733687E+10 | 18232.75 | 16-APR-09:41 | 34.62 | 21.58 | 0.189087E+09 | 356.46 | 27-APR-12:09 | 38.00 | 21.24 |
May | 0.916434E+10 | 18176.55 | 07-MAY-09:11 | 34.60 | 20.48 | 0.205692E+09 | 356.47 | 03-MAY-10:09 | 34.60 | 20.48 |
June | 0.858002E+10 | 16112.80 | 11-JUN-10:12 | 37.37 | 25.15 | 0.204451E+09 | 356.46 | 12-JUN-10:09 | 40.23 | 22.18 |
July | 0.751905E+10 | 16935.50 | 02-JUL-09:21 | 34.90 | 25.85 | 0.190697E+09 | 356.46 | 07-JUL-12:09 | 39.13 | 24.79 |
August | 0.699097E+10 | 12023.86 | 06-AUG-10:42 | 33.30 | 25.72 | 0.212700E+09 | 356.46 | 25-AUG-12:09 | 34.08 | 28.91 |
September | 0.604997E+10 | 15728.07 | 24-SEP-09:42 | 30.85 | 25.27 | 0.188512E+09 | 356.46 | 29-SEP-12:09 | 35.52 | 22.70 |
October | 0.552689E+10 | 16365.16 | 01-OCT-10:02 | 30.08 | 19.42 | 0.193340E+09 | 356.46 | 02-OCT-12:09 | 35.70 | 21.30 |
November | 0.386225E+10 | 6283.24 | 01-NOV-10:05 | 23.77 | 15.01 | 0.184703E+09 | 356.46 | 09-NOV-11:09 | 27.23 | 18.25 |
December | 0.260853E+10 | 3578.33 | 03-DEC-11:52 | 22.70 | 14.22 | 0.161672E+09 | 338.72 | 01-DEC-09:00 | 22.70 | 14.22 |
Annual Sum or Average | 0.681291E+11 | 0.226115E+10 | ||||||||
Minimum of Months | 0.234389E+10 | 2694.72 | 20.27 | 13.36 | 0.161497E+09 | 330.73 | 20.55 | 13.44 | ||
Maximum of Months | 0.916434E+10 | 18232.75 | 37.37 | 25.85 | 0.212700E+09 | 356.47 | 40.23 | 28.91 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500317E+10 | 12109.62 | 08-JAN-14:12 | 22.50 | 13.35 | 0.387756E+09 | 549.51 | 11-JAN-10:00 | 16.90 | 10.80 |
February | 0.580421E+10 | 20267.34 | 20-FEB-13:32 | 26.23 | 13.43 | 0.359731E+09 | 549.51 | 03-FEB-10:00 | 26.23 | 13.43 |
March | 0.891201E+10 | 20499.68 | 12-MAR-12:52 | 30.70 | 19.02 | 0.444827E+09 | 549.78 | 29-MAR-13:20 | 32.27 | 19.61 |
April | 0.102694E+11 | 20257.01 | 16-APR-11:01 | 37.12 | 21.93 | 0.402579E+09 | 549.91 | 20-APR-13:20 | 35.90 | 19.63 |
May | 0.115719E+11 | 20481.72 | 29-MAY-15:21 | 41.30 | 21.75 | 0.437992E+09 | 549.88 | 05-MAY-13:20 | 41.30 | 21.75 |
June | 0.112089E+11 | 18640.21 | 04-JUN-15:51 | 42.30 | 22.20 | 0.436418E+09 | 549.51 | 01-JUN-13:30 | 42.30 | 22.20 |
July | 0.103837E+11 | 18435.84 | 02-JUL-16:01 | 40.38 | 26.40 | 0.406063E+09 | 549.51 | 05-JUL-09:09 | 35.53 | 25.08 |
August | 0.102542E+11 | 17158.79 | 06-AUG-15:22 | 36.30 | 26.24 | 0.455155E+09 | 549.51 | 02-AUG-13:09 | 36.30 | 26.24 |
September | 0.959122E+10 | 20229.41 | 17-SEP-12:22 | 33.60 | 26.01 | 0.403413E+09 | 549.90 | 20-SEP-13:20 | 32.73 | 24.12 |
October | 0.107434E+11 | 22067.14 | 01-OCT-12:01 | 34.03 | 19.84 | 0.416659E+09 | 560.09 | 02-OCT-13:20 | 36.27 | 21.14 |
November | 0.900509E+10 | 21360.32 | 11-NOV-13:01 | 28.53 | 16.97 | 0.406436E+09 | 549.80 | 08-NOV-14:00 | 28.53 | 16.97 |
December | 0.576572E+10 | 19544.85 | 03-DEC-13:12 | 24.17 | 14.17 | 0.382480E+09 | 549.51 | 04-DEC-10:50 | 15.73 | 10.97 |
Annual Sum or Average | 0.108513E+12 | 0.493951E+10 | ||||||||
Minimum of Months | 0.500317E+10 | 12109.62 | 22.50 | 13.35 | 0.359731E+09 | 549.51 | 15.73 | 10.80 | ||
Maximum of Months | 0.115719E+11 | 22067.14 | 42.30 | 26.40 | 0.455155E+09 | 560.09 | 42.30 | 26.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232302E+10 | 3963.33 | 31-JAN-16:00 | 21.10 | 11.23 | 0.219414E+09 | 347.84 | 25-JAN-14:00 | 21.10 | 11.23 |
February | 0.307288E+10 | 8937.61 | 20-FEB-16:12 | 25.27 | 14.30 | 0.210014E+09 | 347.86 | 22-FEB-14:00 | 27.10 | 16.20 |
March | 0.543154E+10 | 17162.10 | 12-MAR-16:12 | 31.07 | 19.87 | 0.270800E+09 | 347.86 | 07-MAR-14:20 | 31.07 | 19.87 |
April | 0.748847E+10 | 19604.98 | 30-APR-15:51 | 37.80 | 18.20 | 0.252694E+09 | 347.86 | 06-APR-13:50 | 37.80 | 18.20 |
May | 0.923558E+10 | 20365.41 | 29-MAY-16:01 | 41.23 | 21.53 | 0.276500E+09 | 347.86 | 03-MAY-13:09 | 41.23 | 21.53 |
June | 0.905180E+10 | 17905.22 | 04-JUN-15:51 | 42.30 | 22.20 | 0.275610E+09 | 347.86 | 01-JUN-13:50 | 42.30 | 22.20 |
July | 0.768747E+10 | 18444.02 | 02-JUL-16:01 | 40.38 | 26.40 | 0.256074E+09 | 347.86 | 06-JUL-13:20 | 39.70 | 25.48 |
August | 0.721276E+10 | 16804.12 | 06-AUG-16:02 | 36.25 | 26.27 | 0.286677E+09 | 347.86 | 04-AUG-13:50 | 36.25 | 26.27 |
September | 0.630317E+10 | 18072.09 | 24-SEP-15:41 | 34.85 | 25.19 | 0.253260E+09 | 347.86 | 19-SEP-13:39 | 34.85 | 25.19 |
October | 0.573846E+10 | 18533.44 | 01-OCT-16:01 | 35.32 | 20.17 | 0.257065E+09 | 347.86 | 05-OCT-13:39 | 33.03 | 20.80 |
November | 0.423391E+10 | 8115.59 | 12-NOV-15:02 | 28.08 | 15.73 | 0.240758E+09 | 347.86 | 09-NOV-14:00 | 28.08 | 15.73 |
December | 0.265759E+10 | 4520.43 | 01-DEC-15:30 | 22.85 | 13.56 | 0.216820E+09 | 347.86 | 01-DEC-14:00 | 22.85 | 13.56 |
Annual Sum or Average | 0.704366E+11 | 0.301569E+10 | ||||||||
Minimum of Months | 0.232302E+10 | 3963.33 | 21.10 | 11.23 | 0.210014E+09 | 347.84 | 21.10 | 11.23 | ||
Maximum of Months | 0.923558E+10 | 20365.41 | 42.30 | 26.40 | 0.286677E+09 | 347.86 | 42.30 | 26.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.789794E+11 | 211922.44 | 02-JAN-07:10 | 6.78 |
February | 0.344158E+11 | 210266.50 | 11-FEB-07:10 | 9.97 |
March | 0.601254E+10 | 122135.92 | 01-MAR-07:08 | 14.10 |
April | 54527255.69 | 9154.78 | 17-APR-04:01 | 24.68 |
May | 39347372.54 | 8101.99 | 22-MAY-04:01 | 27.75 |
June | 28910266.05 | 7750.59 | 19-JUN-04:01 | 27.82 |
July | 22513796.80 | 5994.61 | 19-JUL-05:02 | 26.00 |
August | 20734458.75 | 7060.18 | 21-AUG-04:01 | 25.67 |
September | 23189447.78 | 8386.34 | 18-SEP-04:01 | 27.28 |
October | 0.163053E+10 | 121628.68 | 31-OCT-06:35 | 16.30 |
November | 0.168205E+11 | 209185.84 | 27-NOV-07:15 | 10.23 |
December | 0.639590E+11 | 211199.22 | 23-DEC-07:10 | 6.25 |
Annual Sum or Average | 0.202007E+12 | |||
Minimum of Months | 20734458.75 | 5994.61 | 6.25 | |
Maximum of Months | 0.789794E+11 | 211922.44 | 27.82 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356522E+11 | 178708.65 | 02-JAN-07:15 | 6.87 |
February | 0.108006E+11 | 105229.92 | 09-FEB-21:35 | 14.63 |
March | 0.132394E+09 | 72032.34 | 01-MAR-07:03 | 14.10 |
April | 23980757.17 | 5668.79 | 16-APR-15:01 | 39.63 |
May | 36011318.06 | 5920.25 | 07-MAY-14:31 | 42.13 |
June | 38219809.56 | 6294.29 | 11-JUN-15:31 | 43.33 |
July | 41103188.98 | 5927.36 | 02-JUL-15:21 | 40.20 |
August | 25234737.59 | 4472.97 | 25-AUG-04:01 | 29.07 |
September | 21306249.08 | 4050.08 | 24-SEP-14:21 | 35.10 |
October | 32125700.78 | 5109.37 | 01-OCT-14:41 | 35.98 |
November | 0.142327E+10 | 104334.10 | 25-NOV-07:40 | 11.83 |
December | 0.219773E+11 | 104822.85 | 11-DEC-07:08 | 9.18 |
Annual Sum or Average | 0.702037E+11 | |||
Minimum of Months | 21306249.08 | 4050.08 | 6.87 | |
Maximum of Months | 0.356522E+11 | 178708.65 | 43.33 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249008E+11 | 103177.53 | 02-JAN-09:10 | 8.57 |
February | 0.914354E+10 | 102970.52 | 10-FEB-08:00 | 12.70 |
March | 0.105747E+10 | 50130.63 | 02-MAR-07:03 | 15.07 |
April | 25434168.88 | 4451.92 | 27-APR-04:01 | 29.08 |
May | 45159991.50 | 5465.02 | 18-MAY-04:01 | 30.20 |
June | 55863918.07 | 6271.45 | 11-JUN-15:31 | 43.33 |
July | 72102375.59 | 6577.34 | 20-JUL-04:01 | 28.45 |
August | 53554736.09 | 6617.62 | 18-AUG-04:01 | 28.00 |
September | 44682005.10 | 5946.09 | 02-SEP-04:01 | 27.62 |
October | 87497317.65 | 25637.53 | 31-OCT-07:00 | 16.60 |
November | 0.136847E+10 | 98877.89 | 27-NOV-07:03 | 10.02 |
December | 0.888472E+10 | 102453.14 | 11-DEC-08:00 | 8.60 |
Annual Sum or Average | 0.457393E+11 | |||
Minimum of Months | 25434168.88 | 4451.92 | 8.57 | |
Maximum of Months | 0.249008E+11 | 103177.53 | 43.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6308375.62 | 24287.00 | 02-JAN-07:03 | 6.78 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 6308375.62 | |||
Minimum of Months | 0.00 | 0.00 | 6.78 | |
Maximum of Months | 6308375.62 | 24287.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154370E+09 | 57654.42 | 02-JAN-06:11 | 6.50 |
February | 8130921.26 | 10559.41 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 28373284.52 | 25092.22 | 11-DEC-07:03 | 9.18 |
Annual Sum or Average | 0.190874E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 0.154370E+09 | 57654.42 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538676E+09 | 24660.67 | 02-JAN-06:11 | 6.50 |
February | 0.128430E+09 | 14690.06 | 02-FEB-06:12 | 6.93 |
March | 3220136.04 | 5563.36 | 03-MAR-07:03 | 14.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 57665.32 | 480.54 | 31-OCT-06:02 | 15.85 |
November | 25656662.73 | 7823.80 | 27-NOV-07:03 | 10.02 |
December | 0.271650E+09 | 22850.36 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.967691E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 0.538676E+09 | 24660.67 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238595E+09 | 18262.34 | 02-JAN-06:11 | 6.50 |
February | 51067448.28 | 9847.50 | 02-FEB-06:12 | 6.93 |
March | 1691424.98 | 2550.54 | 01-MAR-07:03 | 14.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 169348.03 | 1411.23 | 31-OCT-06:02 | 15.85 |
November | 10692493.07 | 4658.78 | 27-NOV-07:03 | 10.02 |
December | 0.121622E+09 | 16944.94 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.423838E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 0.238595E+09 | 18262.34 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329543E+09 | 24756.98 | 02-JAN-06:11 | 6.50 |
February | 79958334.07 | 13677.79 | 02-FEB-06:12 | 6.93 |
March | 2401493.27 | 5038.39 | 02-MAR-07:03 | 15.07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 13205152.95 | 7274.92 | 27-NOV-07:03 | 10.02 |
December | 0.146628E+09 | 22614.02 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.571735E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 0.329543E+09 | 24756.98 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335784E+09 | 20285.88 | 02-JAN-06:11 | 6.50 |
February | 85305894.59 | 10177.08 | 02-FEB-06:12 | 6.93 |
March | 2025668.64 | 3309.49 | 01-MAR-07:03 | 14.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 239982.74 | 1999.86 | 31-OCT-06:02 | 15.85 |
November | 16418551.89 | 4682.41 | 27-NOV-07:03 | 10.02 |
December | 0.171947E+09 | 18785.25 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.611721E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 0.335784E+09 | 20285.88 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134064E+09 | 24047.55 | 02-JAN-06:11 | 6.50 |
February | 35790919.60 | 5343.64 | 07-FEB-07:03 | 9.75 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 470607.07 | 1468.03 | 27-NOV-07:03 | 10.02 |
December | 34812332.67 | 5127.91 | 26-DEC-07:03 | 10.65 |
Annual Sum or Average | 0.205138E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 0.134064E+09 | 24047.55 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59558430.48 | 18750.43 | 02-JAN-06:11 | 6.50 |
February | 19391651.69 | 2763.21 | 07-FEB-07:03 | 9.75 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 150290.88 | 1001.94 | 27-NOV-07:03 | 10.02 |
December | 20462867.86 | 2541.12 | 11-DEC-07:03 | 9.18 |
Annual Sum or Average | 99563240.91 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 59558430.48 | 18750.43 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113389E+10 | 23987.13 | 02-JAN-06:11 | 6.50 |
February | 0.592556E+09 | 20692.30 | 02-FEB-07:03 | 7.12 |
March | 0.104278E+09 | 5098.00 | 03-MAR-07:05 | 14.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 3486805.34 | 2827.72 | 31-OCT-06:06 | 15.85 |
November | 0.150431E+09 | 9814.50 | 27-NOV-07:05 | 10.02 |
December | 0.681158E+09 | 23061.05 | 21-DEC-07:03 | 5.68 |
Annual Sum or Average | 0.266580E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.68 | |
Maximum of Months | 0.113389E+10 | 23987.13 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76048193.51 | 18173.91 | 02-JAN-06:11 | 6.50 |
February | 30472213.57 | 3185.71 | 14-FEB-07:03 | 10.50 |
March | 958632.39 | 1316.59 | 03-MAR-07:03 | 14.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 1146098.38 | 1246.20 | 25-NOV-07:03 | 11.28 |
December | 29666485.47 | 3015.63 | 26-DEC-07:03 | 10.65 |
Annual Sum or Average | 0.138292E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 76048193.51 | 18173.91 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167609E+09 | 23509.67 | 02-JAN-06:11 | 6.50 |
February | 29232628.26 | 5830.37 | 04-FEB-07:03 | 8.40 |
March | 196977.33 | 832.54 | 01-MAR-07:03 | 14.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 2540619.73 | 5876.23 | 27-NOV-07:03 | 10.02 |
December | 56351648.20 | 8430.94 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.255931E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 0.167609E+09 | 23509.67 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79717819.94 | 19317.06 | 02-JAN-06:11 | 6.50 |
February | 18287487.17 | 3092.93 | 02-FEB-06:12 | 6.93 |
March | 360177.32 | 844.82 | 01-MAR-07:03 | 14.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 2931691.46 | 2778.47 | 25-NOV-07:03 | 11.28 |
December | 39836511.02 | 6418.89 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.141134E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 79717819.94 | 19317.06 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81863402.29 | 23395.81 | 02-JAN-06:11 | 6.50 |
February | 15224005.76 | 4963.30 | 14-FEB-07:03 | 10.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 813617.55 | 2683.68 | 27-NOV-07:03 | 10.02 |
December | 25559414.18 | 6003.19 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.123460E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 81863402.29 | 23395.81 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113042E+09 | 20395.63 | 02-JAN-06:11 | 6.50 |
February | 26486658.35 | 3401.88 | 02-FEB-06:12 | 6.93 |
March | 1626944.54 | 1104.12 | 01-MAR-07:03 | 14.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 5751984.12 | 2560.74 | 25-NOV-07:03 | 11.28 |
December | 47999344.98 | 6561.22 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.194907E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 0.113042E+09 | 20395.63 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186000.88 | 77247434.77 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4853255.62 | 82988501.82 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27441035.15 | 54362326.67 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95228951.42 | 4501734.71 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192838E+09 | 1872663.69 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130677E+09 | 860440.80 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163086E+09 | 420726.12 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92169446.20 | 889865.70 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56143916.12 | 1293955.59 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32329905.23 | 4202682.29 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9667349.62 | 16815131.32 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1387212.76 | 70475709.12 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806007E+09 | 0.315931E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186000.88 | 420726.12 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192838E+09 | 82988501.82 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72823.46 | 53563017.84 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2431200.58 | 59585493.85 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16801460.75 | 38469102.88 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60861703.10 | 3334752.55 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127026E+09 | 1276962.92 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87329347.07 | 571173.86 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109120E+09 | 269482.71 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61280408.31 | 585571.94 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37325531.38 | 811085.24 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20122293.33 | 3115858.83 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5504640.96 | 12626895.76 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 640000.96 | 50139684.07 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528516E+09 | 0.224349E+09 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72823.46 | 269482.71 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127026E+09 | 59585493.85 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93985777.20 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1082769.86 | 0.100826E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20991868.25 | 60753395.65 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91251306.15 | 4816263.21 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192825E+09 | 1913474.64 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130904E+09 | 832995.55 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163173E+09 | 417339.39 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91460422.05 | 899913.54 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54473142.82 | 1347928.77 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26813051.66 | 4859830.09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4859209.74 | 21796140.90 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19192.56 | 88670417.18 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777853E+09 | 0.381120E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417339.39 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192825E+09 | 0.100826E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21689.04 | 54486122.67 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2115977.24 | 58142266.50 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16451595.77 | 38197921.14 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62579293.76 | 3220596.47 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129645E+09 | 1355450.67 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87792286.98 | 613095.66 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111290E+09 | 259308.74 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62712697.36 | 577860.94 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37855494.97 | 783370.47 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20893935.03 | 2750323.52 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5781969.47 | 11503757.15 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 551125.50 | 49296236.87 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537691E+09 | 0.221186E+09 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21689.04 | 259308.74 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129645E+09 | 58142266.50 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74661.95 | 47985541.01 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2684475.47 | 49443720.38 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15170076.70 | 30687823.00 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52080651.86 | 2454643.89 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104645E+09 | 778836.58 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69977324.56 | 485161.71 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86690917.38 | 312297.27 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48762078.35 | 578621.11 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29273706.28 | 1033236.49 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16545228.12 | 3134320.80 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4531323.62 | 11245345.75 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 578383.01 | 44762752.80 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431014E+09 | 0.192902E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74661.95 | 312297.27 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104645E+09 | 49443720.38 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28826.70 | 33444740.27 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1345680.48 | 35606392.38 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9194618.66 | 22281936.05 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33071184.02 | 1934809.21 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68356160.66 | 582726.92 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46799877.30 | 339073.77 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58222424.66 | 209937.49 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32590247.01 | 390303.72 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19675022.46 | 638991.47 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10524599.88 | 2248013.42 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2692834.36 | 8182265.64 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 280342.14 | 31604238.15 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282782E+09 | 0.137463E+09 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28826.70 | 209937.49 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68356160.66 | 35606392.38 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289442E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64218479.03 | 0.160271E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939751E+09 | 0.678358E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254480E+10 | 69000972.30 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410838E+10 | 847271.86 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415789E+10 | 556289.31 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286404E+10 | 321199.14 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280004E+10 | 607762.44 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208507E+10 | 2536973.54 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149092E+10 | 0.270381E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466934E+09 | 0.965960E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662339.17 | 0.236482E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215227E+11 | 0.885052E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321199.14 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415789E+10 | 0.289442E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3461.99 | 33803889.08 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1079283.81 | 34801633.50 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8824342.74 | 22327279.23 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33235346.78 | 1925166.55 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68993826.16 | 629240.80 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46452542.83 | 391169.30 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58503904.93 | 210260.82 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32776376.70 | 388600.19 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19569686.95 | 655141.24 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10560882.83 | 2107170.78 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2665234.61 | 7694228.75 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 212011.38 | 31162754.17 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282877E+09 | 0.136097E+09 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3461.99 | 210260.82 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68993826.16 | 34801633.50 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111666.15 | 72262693.36 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3764885.48 | 77466699.31 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22690018.72 | 51069092.73 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78799035.97 | 4557678.51 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160277E+09 | 1659775.62 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108447E+09 | 705278.59 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135166E+09 | 386549.00 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76115582.55 | 737546.55 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45905294.43 | 1334945.59 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26512562.11 | 4290237.74 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7334601.53 | 16400339.44 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 980898.09 | 66193368.27 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666105E+09 | 0.297064E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111666.15 | 386549.00 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160277E+09 | 77466699.31 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58762.65 | 49465836.66 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2066729.24 | 54398634.92 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14116153.63 | 35389959.65 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50666856.77 | 3277370.22 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105817E+09 | 1111252.27 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72562521.48 | 466626.75 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90737813.68 | 248038.95 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50549715.89 | 484053.53 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30513361.76 | 819864.63 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16559769.85 | 3039772.70 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4393384.66 | 11859650.32 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497591.63 | 46355272.93 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438539E+09 | 0.206916E+09 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58762.65 | 248038.95 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105817E+09 | 54398634.92 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86091156.25 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 912337.41 | 92292907.13 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17407385.51 | 56339816.27 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75305985.64 | 4832370.82 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160239E+09 | 1689110.45 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108704E+09 | 681726.01 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135277E+09 | 384821.58 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75473837.90 | 745549.84 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44481111.94 | 1381308.26 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22075814.50 | 4842465.68 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4025318.76 | 20470204.92 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17201.71 | 81148787.51 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643920E+09 | 0.350900E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384821.58 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160239E+09 | 92292907.13 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10358.14 | 50332988.27 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1608721.10 | 53425043.39 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13573297.37 | 35527333.41 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51566530.50 | 3219478.55 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107664E+09 | 1193809.17 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72712822.75 | 507415.45 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92014707.60 | 243407.74 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51589706.96 | 482360.96 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30826968.09 | 818617.84 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16972975.64 | 2745233.17 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4407521.69 | 10988818.61 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 407817.24 | 45784145.11 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443355E+09 | 0.205269E+09 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10358.14 | 243407.74 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107664E+09 | 53425043.39 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119349E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1389964.35 | 0.127674E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21524334.81 | 82310647.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90651278.90 | 7182072.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197600E+09 | 2191627.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133656E+09 | 1197770.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168107E+09 | 535789.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92259631.65 | 864299.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52843210.35 | 1498351.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27598636.18 | 7327997.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5368174.30 | 28060988.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199671.75 | 0.110175E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791198E+09 | 0.488367E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535789.17 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197600E+09 | 0.127674E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41109.79 | 0.135963E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2996137.84 | 0.149960E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29482157.93 | 0.100139E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117389E+09 | 8737630.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253371E+09 | 2933229.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172720E+09 | 1525251.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217028E+09 | 603206.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119706E+09 | 1036896.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69626687.61 | 1546035.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37451830.64 | 8498055.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8433725.49 | 32554398.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902075.56 | 0.126986E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102915E+10 | 0.570483E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41109.79 | 603206.29 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253371E+09 | 0.149960E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135743E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121465.57 | 0.146677E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19525772.99 | 82908701.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110046E+09 | 4755832.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262783E+09 | 1692721.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179000E+09 | 1267180.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222310E+09 | 389795.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121547E+09 | 1243992.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68519468.96 | 865113.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30989553.24 | 5591275.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3743542.99 | 28207162.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6719.89 | 0.121013E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101859E+10 | 0.530355E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389795.61 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262783E+09 | 0.146677E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 08-JAN-14:40 | 206.16 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 129.20 | 19-FEB-15:00 | 298.62 | 09-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 312.00 | 26-MAR-15:00 | 586.06 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.52 | 15-APR-17:02 | 73.23 | 22-APR-18:50 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 786.84 | 28-MAY-14:25 | 59.14 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 402.35 | 17-JUN-20:30 | 47.99 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.50 | 02-JUL-11:40 | 43.28 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.39 | 06-AUG-08:50 | 58.89 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.98 | 24-SEP-14:40 | 16.75 | 08-SEP-22:20 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.94 | 15-OCT-12:10 | 87.30 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.37 | 12-NOV-14:00 | 137.01 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.45 | 24-DEC-14:00 | 319.52 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 16.75 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 786.84 | 586.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 | 08-JAN-14:40 | 134.72 | 15-JAN-17:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.53 | 19-FEB-14:40 | 198.37 | 09-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.89 | 26-MAR-15:20 | 393.30 | 24-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.11 | 15-APR-17:02 | 59.51 | 02-APR-08:40 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 532.11 | 28-MAY-14:25 | 41.04 | 15-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.91 | 17-JUN-20:30 | 31.12 | 18-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.46 | 02-JUL-11:36 | 28.09 | 19-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.23 | 06-AUG-14:08 | 39.15 | 15-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.07 | 24-SEP-14:40 | 10.04 | 08-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.86 | 15-OCT-12:30 | 57.16 | 12-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.88 | 12-NOV-14:00 | 91.40 | 28-NOV-05:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.47 | 24-DEC-14:00 | 211.67 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 | 10.04 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 532.11 | 393.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 299.14 | 22-JAN-14:13 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 21-FEB-15:00 | 298.77 | 09-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.35 | 26-MAR-15:18 | 625.21 | 24-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.36 | 15-APR-17:10 | 78.60 | 22-APR-18:50 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 775.95 | 28-MAY-14:25 | 61.04 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.97 | 17-JUN-20:30 | 47.41 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.12 | 02-JUL-11:38 | 43.13 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.79 | 06-AUG-08:50 | 59.04 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.80 | 24-SEP-14:36 | 16.91 | 08-SEP-22:20 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.00 | 15-OCT-12:24 | 88.62 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.72 | 12-NOV-14:36 | 145.48 | 29-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 28-DEC-14:00 | 491.29 | 31-DEC-14:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 775.95 | 625.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 08-JAN-13:53 | 137.29 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 | 19-FEB-13:33 | 198.39 | 09-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 194.96 | 26-MAR-12:52 | 409.75 | 24-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.58 | 15-APR-17:08 | 47.15 | 22-APR-18:50 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 521.89 | 29-MAY-09:00 | 43.54 | 15-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.95 | 17-JUN-21:10 | 33.02 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.33 | 02-JUL-11:00 | 27.60 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.78 | 06-AUG-08:50 | 38.94 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.96 | 24-SEP-13:56 | 9.40 | 19-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.29 | 15-OCT-11:50 | 57.18 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.14 | 12-NOV-12:40 | 92.33 | 28-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.92 | 24-DEC-13:40 | 230.43 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 9.40 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 521.89 | 409.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 08-JAN-15:00 | 129.54 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.78 | 19-FEB-15:00 | 169.70 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.47 | 26-MAR-14:30 | 343.52 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.29 | 15-APR-17:02 | 46.40 | 22-APR-18:20 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.22 | 28-MAY-15:04 | 27.22 | 13-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.25 | 17-JUN-20:40 | 27.73 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.01 | 02-JUL-11:30 | 29.28 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.41 | 06-AUG-09:20 | 34.88 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.97 | 24-SEP-14:30 | 19.08 | 08-SEP-22:10 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.02 | 15-OCT-12:00 | 58.64 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.37 | 12-NOV-14:20 | 90.41 | 28-NOV-05:30 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.36 | 24-DEC-14:10 | 203.04 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 19.08 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 422.22 | 343.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | 08-JAN-14:50 | 86.02 | 15-JAN-17:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.82 | 19-FEB-15:00 | 115.35 | 18-FEB-06:00 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.86 | 26-MAR-15:10 | 240.57 | 24-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.87 | 15-APR-17:02 | 35.19 | 22-APR-18:10 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.68 | 28-MAY-15:04 | 19.88 | 15-MAY-03:40 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.49 | 17-JUN-20:20 | 18.69 | 18-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.79 | 02-JUL-12:05 | 19.14 | 19-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.43 | 06-AUG-14:00 | 23.64 | 15-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.23 | 24-SEP-14:30 | 11.91 | 08-SEP-22:20 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.64 | 15-OCT-12:40 | 38.98 | 12-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.23 | 12-NOV-14:20 | 62.31 | 28-NOV-05:20 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 | 24-DEC-14:10 | 135.16 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | 11.91 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 284.68 | 240.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 21004.11 | 05-JAN-07:10 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3133.42 | 22-FEB-13:00 | 17952.58 | 02-FEB-07:10 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12533.31 | 28-MAR-16:03 | 8696.35 | 01-MAR-07:10 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17220.67 | 27-APR-16:01 | 4021.90 | 11-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21789.61 | 03-MAY-16:01 | 116.52 | 15-MAY-05:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22182.21 | 07-JUN-16:01 | 99.74 | 27-JUN-11:10 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17372.86 | 07-JUL-16:01 | 29.37 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14275.79 | 07-AUG-16:02 | 35.72 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12852.30 | 26-SEP-16:02 | 495.59 | 27-SEP-05:02 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12621.78 | 02-OCT-16:02 | 7657.94 | 30-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5128.83 | 09-NOV-13:00 | 14036.65 | 27-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 107.01 | 28-DEC-14:00 | 19945.80 | 21-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.37 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 22182.21 | 21004.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 08-JAN-14:12 | 87.41 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 19-FEB-13:53 | 114.82 | 18-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | 26-MAR-13:10 | 250.51 | 24-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.87 | 15-APR-17:10 | 31.13 | 22-APR-18:20 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.46 | 28-MAY-13:45 | 22.33 | 15-MAY-03:10 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.07 | 17-JUN-20:20 | 20.66 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.77 | 02-JUL-11:30 | 19.18 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.69 | 06-AUG-09:20 | 23.70 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 24-SEP-14:24 | 11.78 | 08-SEP-22:20 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.50 | 15-OCT-12:00 | 38.97 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.36 | 12-NOV-12:22 | 62.36 | 28-NOV-05:30 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 | 24-DEC-13:43 | 134.55 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 11.78 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 273.46 | 250.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 | 08-JAN-15:00 | 191.69 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.11 | 19-FEB-15:00 | 260.73 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 260.45 | 26-MAR-15:10 | 553.00 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.14 | 15-APR-17:02 | 73.23 | 22-APR-18:20 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 655.89 | 28-MAY-14:25 | 51.25 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.58 | 17-JUN-20:40 | 40.58 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.83 | 02-JUL-11:30 | 40.22 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.64 | 06-AUG-08:50 | 48.96 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.79 | 24-SEP-14:30 | 20.32 | 08-SEP-22:20 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.79 | 15-OCT-12:10 | 81.05 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 | 12-NOV-13:50 | 132.61 | 28-NOV-05:20 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.81 | 24-DEC-13:55 | 295.74 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 | 20.32 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 655.89 | 553.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 | 08-JAN-15:00 | 125.26 | 15-JAN-17:00 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.02 | 19-FEB-15:00 | 172.58 | 18-FEB-06:00 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.03 | 26-MAR-15:00 | 368.39 | 24-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.67 | 15-APR-17:02 | 54.96 | 02-APR-08:30 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.27 | 28-MAY-15:04 | 34.98 | 15-MAY-03:00 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.07 | 17-JUN-20:40 | 26.33 | 18-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.41 | 02-JUL-12:05 | 25.95 | 19-JUL-03:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.73 | 06-AUG-14:10 | 32.68 | 15-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.92 | 24-SEP-14:30 | 12.02 | 08-SEP-22:20 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.28 | 15-OCT-12:50 | 52.93 | 12-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.34 | 12-NOV-13:50 | 87.87 | 28-NOV-05:00 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.13 | 24-DEC-13:53 | 195.24 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 | 12.02 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 443.27 | 368.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 255.97 | 22-JAN-14:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | 21-FEB-15:00 | 265.97 | 18-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.25 | 26-MAR-17:00 | 583.95 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 371.67 | 15-APR-17:02 | 78.81 | 22-APR-18:20 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 646.32 | 28-MAY-14:25 | 52.92 | 15-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.01 | 17-JUN-20:40 | 40.03 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.70 | 02-JUL-11:26 | 40.07 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.18 | 06-AUG-08:50 | 49.10 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.86 | 24-SEP-14:24 | 20.39 | 08-SEP-22:20 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.31 | 15-OCT-13:00 | 82.17 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.46 | 12-NOV-13:44 | 139.73 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 28-DEC-14:00 | 422.65 | 31-DEC-14:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 646.32 | 583.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 08-JAN-13:53 | 127.44 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 19-FEB-13:00 | 172.28 | 18-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.99 | 26-MAR-13:02 | 384.02 | 24-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.37 | 15-APR-17:08 | 47.21 | 22-APR-18:20 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 425.41 | 28-MAY-15:04 | 38.01 | 15-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.12 | 17-JUN-20:40 | 28.07 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.55 | 02-JUL-11:30 | 25.83 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.48 | 06-AUG-08:50 | 32.54 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.98 | 24-SEP-14:24 | 11.49 | 08-SEP-22:20 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.92 | 15-OCT-12:10 | 53.12 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.64 | 12-NOV-12:30 | 88.85 | 28-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.57 | 24-DEC-13:53 | 203.65 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 11.49 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 425.41 | 384.02 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 296.87 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.85 | 19-FEB-15:10 | 420.98 | 09-FEB-22:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.15 | 26-MAR-14:52 | 911.23 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.96 | 15-APR-17:02 | 123.37 | 22-APR-18:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819.14 | 28-MAY-14:51 | 68.54 | 15-MAY-03:43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.66 | 17-JUN-20:40 | 68.19 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.78 | 02-JUL-11:50 | 56.08 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.37 | 06-AUG-14:00 | 58.98 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.63 | 24-SEP-14:10 | 26.61 | 08-SEP-22:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.83 | 15-OCT-12:20 | 120.53 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.73 | 12-NOV-14:00 | 213.90 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 | 24-DEC-13:53 | 478.37 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819.14 | 911.23 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 08-JAN-14:52 | 339.51 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.19 | 19-FEB-15:10 | 512.22 | 09-FEB-22:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.82 | 26-MAR-15:10 | 1119.81 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.60 | 15-APR-17:02 | 143.87 | 22-APR-18:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1045.69 | 28-MAY-14:51 | 91.66 | 15-MAY-04:02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.26 | 17-JUN-20:40 | 86.76 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.96 | 02-JUL-11:50 | 66.39 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.59 | 06-AUG-13:51 | 73.14 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.64 | 24-SEP-14:10 | 33.53 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.66 | 15-OCT-12:30 | 142.64 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.81 | 12-NOV-14:10 | 251.15 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.24 | 24-DEC-14:00 | 569.44 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 | 33.53 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1045.69 | 1119.81 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 400.17 | 22-JAN-14:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.32 | 19-FEB-23:00 | 482.22 | 09-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.98 | 26-MAR-15:00 | 796.82 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.66 | 15-APR-17:02 | 91.12 | 22-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.35 | 28-MAY-15:10 | 64.30 | 13-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.07 | 17-JUN-20:30 | 73.58 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.67 | 02-JUL-11:00 | 49.75 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.19 | 06-AUG-09:02 | 79.47 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.42 | 24-SEP-14:00 | 17.15 | 03-SEP-19:52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.94 | 15-OCT-12:10 | 124.79 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.77 | 12-NOV-14:00 | 191.10 | 28-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 | 24-DEC-15:00 | 639.62 | 31-DEC-14:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.35 | 796.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21035.78 | 13-JAN-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31971.86 | 27-FEB-07:03 | 5082.11 | 13014.15 | 41900.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49041.26 | 13-MAR-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54093.02 | 26-APR-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54393.33 | 25-MAY-04:01 | 0.00 | 7591.59 | 41762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 53763.99 | 28-JUN-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 53644.61 | 19-JUL-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 53375.71 | 24-AUG-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53882.74 | 07-SEP-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49196.93 | 07-OCT-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48886.78 | 13-NOV-06:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24068.95 | 01-DEC-07:03 | 5082.11 | 13014.15 | 41900.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21035.78 | 0.00 | 4338.05 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54393.33 | 6035.01 | 13014.15 | 41900.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7125.66 | 31-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 |
February | 11707.87 | 22-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 0.00 |
March | 18458.47 | 28-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 | 0.00 |
April | 21695.03 | 26-APR-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.82 | 0.00 |
May | 35706.67 | 29-MAY-15:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.84 | 0.00 |
June | 24817.22 | 08-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 0.00 |
July | 21790.69 | 10-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 0.00 |
August | 19579.04 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.24 | 0.00 |
September | 18342.61 | 26-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.15 | 0.00 |
October | 18349.15 | 02-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.90 | 0.00 |
November | 13085.09 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 0.00 |
December | 7961.28 | 01-DEC-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7125.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35706.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.84 | 40.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2721.50 | 27-JAN-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 |
February | 3109.53 | 18-FEB-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.08 |
March | 5192.02 | 13-MAR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 | 0.00 |
April | 6757.87 | 17-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.36 | 0.00 |
May | 7354.18 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.20 | 0.00 |
June | 7773.55 | 12-JUN-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.96 | 0.00 |
July | 7469.09 | 05-JUL-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.61 | 0.00 |
August | 6719.52 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | 0.00 |
September | 6533.07 | 25-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.85 | 0.00 |
October | 6572.79 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | 0.00 |
November | 3424.66 | 09-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 0.00 |
December | 2800.56 | 01-DEC-06:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2721.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7773.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.96 | 136.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2699.74 | 26-JAN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 |
February | 3669.71 | 27-FEB-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 |
March | 5701.68 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.59 | 0.00 |
April | 7550.36 | 28-APR-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.11 | 0.00 |
May | 9004.67 | 05-MAY-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.28 | 0.00 |
June | 9511.05 | 12-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.23 | 0.00 |
July | 9165.45 | 05-JUL-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.83 | 0.00 |
August | 7928.18 | 07-AUG-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.41 | 0.00 |
September | 7159.52 | 18-SEP-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.68 | 0.00 |
October | 7068.38 | 02-OCT-17:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 0.00 |
November | 4643.87 | 13-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.32 | 0.00 |
December | 2955.87 | 01-DEC-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2699.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9511.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.28 | 30.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13237.64 | 26-JAN-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16466.76 | 23-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31046.21 | 13-MAR-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44049.54 | 17-APR-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43930.27 | 15-MAY-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42676.68 | 28-JUN-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41618.12 | 13-JUL-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42982.01 | 16-AUG-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46275.68 | 05-SEP-04:03 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43102.07 | 04-OCT-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17792.98 | 13-NOV-16:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14811.15 | 01-DEC-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13237.64 | 0.00 | 4338.05 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46275.68 | 6035.01 | 9760.61 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13087.85 | 26-JAN-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17998.23 | 23-FEB-15:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23204.54 | 13-MAR-15:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53365.74 | 17-APR-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52534.42 | 15-MAY-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51449.59 | 20-JUN-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 49750.15 | 19-JUL-05:02 | 3811.58 | 6507.07 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 53060.84 | 21-AUG-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 52551.95 | 25-SEP-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49943.97 | 04-OCT-05:02 | 3811.58 | 6507.07 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19407.16 | 09-NOV-15:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14515.32 | 01-DEC-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13087.85 | 0.00 | 6507.07 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53365.74 | 6198.29 | 9760.61 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3691.63 | 26-JAN-14:50 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 |
February | 5232.99 | 23-FEB-14:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 0.00 |
March | 8137.95 | 29-MAR-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 79.95 | 0.00 |
April | 21971.05 | 16-APR-15:11 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 73.14 | 0.00 |
May | 23251.00 | 29-MAY-16:12 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 244.40 | 0.00 |
June | 22307.83 | 04-JUN-16:31 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 275.44 | 0.00 |
July | 21126.58 | 04-JUL-17:02 | 0.00 | 685.87 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 161.92 | 0.00 |
August | 16986.06 | 14-AUG-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16670.98 | 05-SEP-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
October | 9098.92 | 02-OCT-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 47.48 | 0.00 |
November | 5755.57 | 09-NOV-14:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
December | 3752.45 | 03-DEC-13:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3691.63 | 0.00 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23251.00 | 1306.65 | 2057.62 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 275.44 | 10.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2784.43 | 26-JAN-14:10 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
February | 4697.74 | 23-FEB-10:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
March | 7945.29 | 28-MAR-10:20 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 | 0.00 |
April | 18651.35 | 16-APR-08:31 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 0.00 |
May | 18206.47 | 29-MAY-09:31 | 339.13 | 578.95 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 335.75 | 0.00 |
June | 17377.37 | 11-JUN-10:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 73.92 | 0.00 |
July | 17214.38 | 04-JUL-10:22 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 104.82 | 0.00 |
August | 12771.39 | 06-AUG-10:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 131.16 | 0.00 |
September | 10385.68 | 05-SEP-04:01 | 0.00 | 1013.17 | 2281.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 0.00 |
October | 13540.42 | 15-OCT-11:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 104.45 | 0.00 |
November | 4911.44 | 09-NOV-10:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 0.00 |
December | 3176.20 | 03-DEC-13:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2784.43 | 0.00 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18651.35 | 827.22 | 1302.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 335.75 | 5.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9503.52 | 12-JAN-14:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 |
February | 23572.46 | 20-FEB-13:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 |
March | 22750.78 | 05-MAR-14:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 0.00 |
April | 23377.02 | 16-APR-14:31 | 535.68 | 914.50 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 85.66 | 0.00 |
May | 23461.52 | 29-MAY-16:12 | 669.60 | 1143.12 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 244.75 | 0.00 |
June | 22391.71 | 04-JUN-15:51 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 299.96 | 0.00 |
July | 20763.04 | 04-JUL-16:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 160.15 | 0.00 |
August | 20884.77 | 06-AUG-15:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 218.42 | 0.00 |
September | 22486.99 | 24-SEP-13:52 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 192.85 | 0.00 |
October | 25253.33 | 08-OCT-12:41 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 | 0.00 |
November | 23803.09 | 23-NOV-13:02 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 |
December | 20218.10 | 03-DEC-13:02 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9503.52 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25253.33 | 1272.23 | 2057.62 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 299.96 | 11.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4059.27 | 31-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 |
February | 9515.48 | 20-FEB-16:12 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 |
March | 16252.50 | 05-MAR-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 0.00 |
April | 20100.55 | 16-APR-15:11 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 44.28 | 0.00 |
May | 21821.34 | 29-MAY-16:12 | 423.88 | 723.64 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 143.50 | 0.00 |
June | 20535.21 | 04-JUN-15:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 | 0.00 |
July | 18944.79 | 09-JUL-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 123.00 | 0.00 |
August | 18996.30 | 06-AUG-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 128.13 | 0.00 |
September | 18927.89 | 24-SEP-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 99.27 | 0.00 |
October | 19308.47 | 08-OCT-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 | 0.00 |
November | 7100.30 | 08-NOV-15:20 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 | 0.00 |
December | 4571.97 | 01-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4059.27 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21821.34 | 805.38 | 1302.56 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 | 10.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3037.48 | 26-JAN-14:20 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 |
February | 4047.04 | 24-FEB-15:10 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 0.00 |
March | 6343.04 | 29-MAR-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.70 | 0.00 |
April | 8627.18 | 27-APR-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 14.08 | 0.00 |
May | 17817.46 | 28-MAY-16:21 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 362.69 | 0.00 |
June | 17958.00 | 11-JUN-16:51 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 70.29 | 0.00 |
July | 18711.53 | 02-JUL-16:41 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 113.34 | 0.00 |
August | 16642.60 | 06-AUG-15:11 | 602.64 | 1028.81 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 120.52 | 0.00 |
September | 17628.49 | 24-SEP-15:41 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 86.69 | 0.00 |
October | 12885.72 | 01-OCT-16:01 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 37.20 | 0.00 |
November | 5315.67 | 09-NOV-14:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 0.00 |
December | 3872.12 | 03-DEC-14:02 | 267.84 | 457.25 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3037.48 | 0.00 | 457.25 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18711.53 | 1306.65 | 2057.62 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 362.69 | 4.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2582.81 | 26-JAN-10:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 |
February | 4430.89 | 23-FEB-10:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 |
March | 10550.76 | 12-MAR-09:32 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
April | 15161.61 | 16-APR-10:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 | 0.00 |
May | 15628.41 | 29-MAY-09:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 197.63 | 0.00 |
June | 15324.21 | 11-JUN-10:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 40.34 | 0.00 |
July | 16159.64 | 02-JUL-09:21 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.02 | 0.00 |
August | 15616.41 | 06-AUG-09:52 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 62.05 | 0.00 |
September | 15178.78 | 24-SEP-09:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 0.00 |
October | 15734.08 | 01-OCT-10:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | 0.00 |
November | 5173.44 | 01-NOV-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 3410.74 | 03-DEC-14:02 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2582.81 | 169.56 | 289.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16159.64 | 827.22 | 1302.65 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.63 | 10.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9475.90 | 08-JAN-14:43 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 |
February | 14599.59 | 20-FEB-13:43 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
March | 19657.02 | 12-MAR-12:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 0.00 |
April | 18557.76 | 16-APR-13:22 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 54.98 | 0.00 |
May | 19871.38 | 03-MAY-16:20 | 2008.79 | 5715.62 | 3986.77 | 0.00 | 0.00 | 0.00 | 0.00 | 17983.35 | 0.00 |
June | 20189.60 | 07-JUN-16:50 | 401.76 | 1143.12 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 17930.25 | 0.00 |
July | 18866.13 | 02-JUL-16:01 | 669.60 | 1143.12 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 115.12 | 0.00 |
August | 18384.70 | 06-AUG-14:31 | 535.68 | 914.50 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 121.03 | 0.00 |
September | 19717.37 | 17-SEP-13:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 77.10 | 0.00 |
October | 21417.92 | 01-OCT-12:01 | 535.68 | 914.50 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 32.63 | 0.00 |
November | 20774.30 | 12-NOV-12:51 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 |
December | 18430.29 | 03-DEC-14:02 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9475.90 | 267.84 | 457.25 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21417.92 | 2008.79 | 5715.62 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17983.35 | 24.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3361.94 | 31-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
February | 5064.29 | 21-FEB-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
March | 15906.46 | 12-MAR-16:12 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 0.00 |
April | 16585.99 | 30-APR-16:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 113.42 | 0.00 |
May | 17057.53 | 28-MAY-16:21 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 219.16 | 0.00 |
June | 16933.39 | 11-JUN-16:11 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 | 0.00 |
July | 18250.16 | 02-JUL-16:01 | 423.88 | 723.64 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 65.26 | 0.00 |
August | 16418.27 | 06-AUG-15:51 | 381.49 | 651.28 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 66.56 | 0.00 |
September | 17463.60 | 24-SEP-15:41 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 44.09 | 0.00 |
October | 17582.14 | 01-OCT-16:01 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 0.00 |
November | 11614.94 | 05-NOV-15:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 0.00 |
December | 4135.34 | 01-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3361.94 | 254.33 | 434.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18250.16 | 805.38 | 1302.56 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 219.16 | 5.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3220.34 | 26-JAN-14:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 |
February | 4851.69 | 23-FEB-14:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 |
March | 7342.77 | 29-MAR-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 66.75 | 0.00 |
April | 18437.23 | 30-APR-15:51 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 282.41 | 0.00 |
May | 20018.22 | 29-MAY-15:21 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 275.18 | 0.00 |
June | 18512.22 | 04-JUN-16:31 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 232.82 | 0.00 |
July | 18269.92 | 02-JUL-16:41 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 175.22 | 0.00 |
August | 13530.75 | 21-AUG-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17663.41 | 24-SEP-15:41 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 136.79 | 0.00 |
October | 11403.86 | 01-OCT-16:01 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 0.00 |
November | 5344.95 | 09-NOV-14:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 | 0.00 |
December | 3825.55 | 03-DEC-13:12 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3220.34 | 0.00 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20018.22 | 1306.65 | 2057.62 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 282.41 | 9.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2694.72 | 26-JAN-11:20 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
February | 5862.71 | 22-FEB-11:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
March | 14004.83 | 12-MAR-09:32 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 |
April | 18232.75 | 16-APR-09:41 | 381.52 | 651.32 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 | 0.00 |
May | 18176.55 | 07-MAY-09:11 | 381.52 | 651.32 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 86.78 | 0.00 |
June | 16112.80 | 11-JUN-10:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 62.07 | 0.00 |
July | 16935.50 | 02-JUL-09:21 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.22 | 0.00 |
August | 12023.86 | 06-AUG-10:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 110.21 | 0.00 |
September | 15728.07 | 24-SEP-09:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 0.00 |
October | 16365.16 | 01-OCT-10:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 0.00 |
November | 6283.24 | 01-NOV-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 3578.33 | 03-DEC-11:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2694.72 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18232.75 | 1610.86 | 2605.29 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 129.22 | 13.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12109.62 | 08-JAN-14:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.45 |
February | 20267.34 | 20-FEB-13:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.36 |
March | 20499.68 | 12-MAR-12:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 | 0.00 |
April | 20257.01 | 16-APR-11:01 | 535.68 | 914.50 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 52.82 | 0.00 |
May | 20481.72 | 29-MAY-15:21 | 669.60 | 1143.12 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 273.13 | 0.00 |
June | 18640.21 | 04-JUN-15:51 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 253.95 | 0.00 |
July | 18435.84 | 02-JUL-16:01 | 669.60 | 1143.12 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 178.03 | 0.00 |
August | 17158.79 | 06-AUG-15:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 183.56 | 0.00 |
September | 20229.41 | 17-SEP-12:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 | 0.00 |
October | 22067.14 | 01-OCT-12:01 | 535.68 | 914.50 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 50.65 | 0.00 |
November | 21360.32 | 11-NOV-13:01 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
December | 19544.85 | 03-DEC-13:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12109.62 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22067.14 | 669.60 | 1143.12 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 273.13 | 43.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3963.33 | 31-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
February | 8937.61 | 20-FEB-16:12 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 |
March | 17162.10 | 12-MAR-16:12 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 34.54 | 0.00 |
April | 19604.98 | 30-APR-15:51 | 423.88 | 723.64 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 138.66 | 0.00 |
May | 20365.41 | 29-MAY-16:01 | 423.88 | 723.64 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 115.54 | 0.00 |
June | 17905.22 | 04-JUN-15:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 153.81 | 0.00 |
July | 18444.02 | 02-JUL-16:01 | 423.88 | 723.64 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 99.31 | 0.00 |
August | 16804.12 | 06-AUG-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 107.56 | 0.00 |
September | 18072.09 | 24-SEP-15:41 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 68.02 | 0.00 |
October | 18533.44 | 01-OCT-16:01 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 28.91 | 0.00 |
November | 8115.59 | 12-NOV-15:02 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 | 0.00 |
December | 4520.43 | 01-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3963.33 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20365.41 | 805.38 | 1302.56 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 153.81 | 8.81 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.179767E+12 | 221088.83 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 0.165288E+12 | 154673.22 | 22-FEB-15:09 | 0.00 | 0.00 |
March | 0.208113E+12 | 201656.87 | 28-MAR-15:50 | 0.00 | 0.00 |
April | 0.229831E+12 | 230359.66 | 27-APR-14:00 | 0.00 | 0.00 |
May | 0.279471E+12 | 257069.12 | 01-MAY-14:00 | 0.00 | 0.00 |
June | 0.284855E+12 | 258492.76 | 12-JUN-15:09 | 0.00 | 0.00 |
July | 0.272157E+12 | 245125.57 | 03-JUL-15:00 | 0.00 | 0.00 |
August | 0.276364E+12 | 236490.98 | 07-AUG-15:09 | 0.00 | 0.00 |
September | 0.240216E+12 | 219360.53 | 14-SEP-15:20 | 0.00 | 0.00 |
October | 0.219372E+12 | 211301.42 | 02-OCT-15:39 | 0.00 | 0.00 |
November | 0.189163E+12 | 166985.74 | 08-NOV-15:09 | 0.00 | 0.00 |
December | 0.176748E+12 | 147041.46 | 21-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.272134E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.165288E+12 | 147041.46 | 0.00 | 0.00 | |
Maximum of Months | 0.284855E+12 | 258492.76 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.226819E+11 | 0.613996E+11 | 0.230900E+10 | 0.147438E+11 | 12379742.02 | 0.715936E+10 | 0.202870E+11 | 0.00 | 0.00 | 0.00 | 0.392627E+10 | 0.00 |
February | 0.428574E+11 | 0.196282E+11 | 0.556056E+11 | 0.209511E+10 | 0.131565E+11 | 11196021.66 | 0.211679E+10 | 0.263210E+11 | 0.00 | 0.00 | 0.00 | 0.349660E+10 | 0.00 |
March | 0.509265E+11 | 0.203398E+11 | 0.635880E+11 | 0.240664E+10 | 0.187483E+11 | 12675672.10 | 90702702.61 | 0.481338E+11 | 0.00 | 0.00 | 0.00 | 0.386676E+10 | 0.00 |
April | 0.454877E+11 | 0.183220E+11 | 0.594055E+11 | 0.224272E+10 | 0.248325E+11 | 11960507.72 | 0.00 | 0.763599E+11 | 0.00 | 0.00 | 0.00 | 0.316914E+10 | 0.00 |
May | 0.490872E+11 | 0.177365E+11 | 0.624938E+11 | 0.235782E+10 | 0.307590E+11 | 12527707.06 | 0.00 | 0.113987E+12 | 0.00 | 0.00 | 0.00 | 0.303652E+10 | 0.00 |
June | 0.488499E+11 | 0.165205E+11 | 0.612808E+11 | 0.231841E+10 | 0.306957E+11 | 12231776.97 | 0.00 | 0.122445E+12 | 0.00 | 0.00 | 0.00 | 0.273219E+10 | 0.00 |
July | 0.457251E+11 | 0.174213E+11 | 0.606074E+11 | 0.228147E+10 | 0.272166E+11 | 12256437.81 | 0.00 | 0.116403E+12 | 0.00 | 0.00 | 0.00 | 0.248941E+10 | 0.00 |
August | 0.509265E+11 | 0.183851E+11 | 0.635880E+11 | 0.240664E+10 | 0.274346E+11 | 12675672.10 | 0.00 | 0.110797E+12 | 0.00 | 0.00 | 0.00 | 0.281349E+10 | 0.00 |
September | 0.454877E+11 | 0.190967E+11 | 0.593832E+11 | 0.224140E+10 | 0.232558E+11 | 11960507.72 | 0.00 | 0.879526E+11 | 0.00 | 0.00 | 0.00 | 0.278647E+10 | 0.00 |
October | 0.472479E+11 | 0.211505E+11 | 0.614108E+11 | 0.230966E+10 | 0.209186E+11 | 12379742.02 | 1182720.20 | 0.631058E+11 | 0.00 | 0.00 | 0.00 | 0.321487E+10 | 0.00 |
November | 0.466941E+11 | 0.216460E+11 | 0.599069E+11 | 0.224962E+10 | 0.162301E+11 | 12059151.09 | 0.484711E+09 | 0.384435E+11 | 0.00 | 0.00 | 0.00 | 0.349601E+10 | 0.00 |
December | 0.457251E+11 | 0.231052E+11 | 0.605962E+11 | 0.228081E+10 | 0.142169E+11 | 12256437.81 | 0.383879E+10 | 0.232505E+11 | 0.00 | 0.00 | 0.00 | 0.372261E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.236034E+12 | 0.729266E+12 | 0.274993E+11 | 0.262208E+12 | 0.146559E+09 | 0.136915E+11 | 0.847486E+12 | 0.00 | 0.00 | 0.00 | 0.387504E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.165205E+11 | 0.556056E+11 | 0.209511E+10 | 0.131565E+11 | 11196021.66 | 0.00 | 0.202870E+11 | 0.00 | 0.00 | 0.00 | 0.248941E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.231052E+11 | 0.635880E+11 | 0.240664E+10 | 0.307590E+11 | 12675672.10 | 0.715936E+10 | 0.122445E+12 | 0.00 | 0.00 | 0.00 | 0.392627E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 05-JAN-17:10 | 20909.67 | 02-JAN-06:49 | 6.85 | 01-JAN-06:10 | 141096.90 | 02-JAN-07:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 01-FEB-08:39 | 18825.50 | 03-FEB-07:49 | 6.85 | 01-FEB-06:10 | 61681.79 | 02-FEB-07:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 06-MAR-08:20 | 28500.20 | 28-MAR-15:00 | 6.85 | 01-MAR-06:10 | 13611.01 | 01-MAR-07:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 14-APR-12:09 | 32646.56 | 17-APR-15:00 | 6.85 | 02-APR-15:20 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 04-MAY-11:09 | 34695.80 | 01-MAY-14:20 | 6.85 | 04-MAY-11:09 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 02-JUN-16:10 | 35339.24 | 05-JUN-14:20 | 6.85 | 04-JUN-13:50 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 05-JUL-11:09 | 33658.70 | 03-JUL-15:09 | 6.85 | 02-JUL-10:09 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 07-AUG-12:09 | 32323.10 | 07-AUG-15:30 | 6.85 | 02-AUG-22:30 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 01-SEP-16:10 | 30136.94 | 25-SEP-15:20 | 6.85 | 17-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 02-OCT-11:09 | 29059.17 | 02-OCT-15:00 | 6.85 | 01-OCT-11:30 | 1333.47 | 31-OCT-06:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 01-NOV-07:19 | 21739.55 | 01-NOV-15:30 | 6.85 | 01-NOV-05:10 | 31848.86 | 27-NOV-07:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 21-DEC-12:09 | 18970.71 | 04-DEC-07:30 | 6.85 | 01-DEC-06:10 | 71273.67 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 18825.50 | 6.85 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 35339.24 | 6.85 | 141096.90 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 26853.01 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 5342.36 | 19-JAN-12:50 | 0.00 |
February | 40240.38 | 22-FEB-15:09 | 0.00 | 0.00 | 0.00 | 5247.05 | 03-FEB-12:00 | 0.00 |
March | 77318.15 | 28-MAR-15:30 | 0.00 | 0.00 | 0.00 | 4978.27 | 01-MAR-12:20 | 0.00 |
April | 102626.29 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 4583.12 | 03-APR-11:20 | 0.00 |
May | 129538.45 | 01-MAY-14:00 | 0.00 | 0.00 | 0.00 | 4200.45 | 01-MAY-11:20 | 0.00 |
June | 131417.58 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 3540.34 | 01-JUN-11:30 | 0.00 |
July | 116743.87 | 03-JUL-15:00 | 0.00 | 0.00 | 0.00 | 3504.19 | 03-JUL-11:30 | 0.00 |
August | 109286.85 | 07-AUG-14:50 | 0.00 | 0.00 | 0.00 | 3533.00 | 31-AUG-11:00 | 0.00 |
September | 95405.95 | 14-SEP-14:39 | 0.00 | 0.00 | 0.00 | 3885.82 | 29-SEP-11:20 | 0.00 |
October | 90784.63 | 02-OCT-14:09 | 0.00 | 0.00 | 0.00 | 4575.39 | 31-OCT-11:30 | 0.00 |
November | 50898.43 | 09-NOV-13:39 | 0.00 | 0.00 | 0.00 | 4965.11 | 30-NOV-12:20 | 0.00 |
December | 30187.14 | 01-DEC-14:39 | 0.00 | 0.00 | 0.00 | 5157.90 | 28-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 26853.01 | 0.00 | 0.00 | 0.00 | 3504.19 | 0.00 | ||
Maximum of Months | 131417.58 | 0.00 | 0.00 | 0.00 | 5342.36 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 221088.83 | 02-JAN-07:10 | 16481.06 | 22777.10 | 15013.15 | 1008.91 | 19490.33 | 6.85 | 141096.90 | 3564.25 | 0.00 |
February | 154673.22 | 22-FEB-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 18754.82 | 6.85 | 0.00 | 40240.38 | 0.00 |
March | 201656.87 | 28-MAR-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 28280.73 | 6.85 | 0.00 | 77042.19 | 0.00 |
April | 230359.66 | 27-APR-14:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 32394.54 | 6.85 | 0.00 | 102626.29 | 0.00 |
May | 257069.12 | 01-MAY-14:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 32477.39 | 6.85 | 0.00 | 129538.45 | 0.00 |
June | 258492.76 | 12-JUN-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 32054.40 | 6.85 | 0.00 | 131079.06 | 0.00 |
July | 245125.57 | 03-JUL-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 33027.18 | 6.85 | 0.00 | 116743.87 | 0.00 |
August | 236490.98 | 07-AUG-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 32195.88 | 6.85 | 0.00 | 108945.25 | 0.00 |
September | 219360.53 | 14-SEP-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 28694.94 | 6.85 | 0.00 | 94995.03 | 0.00 |
October | 211301.42 | 02-OCT-15:39 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 28977.15 | 6.85 | 0.00 | 86341.96 | 0.00 |
November | 166985.74 | 08-NOV-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 21109.44 | 6.85 | 0.00 | 50511.08 | 0.00 |
December | 147041.46 | 21-DEC-07:10 | 16481.06 | 22777.10 | 15013.15 | 1008.91 | 17098.02 | 6.85 | 71273.67 | 1733.97 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 147041.46 | 16481.06 | 22777.10 | 0.00 | 1008.91 | 17098.02 | 6.85 | 0.00 | 1733.97 | 0.00 | |
Maximum of Months | 258492.76 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 33027.18 | 6.85 | 141096.90 | 131079.06 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.27 | 0.17 | 27.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 27.27 | 0.17 | 27.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.27 | 0.17 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.86 | 2.33 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.03 | 7.67 | 28.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.00 | 4.50 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.88 | 7.33 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.76 | 3.83 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.42 | 1.33 | 27.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 35.83 | 27.91 | 27.00 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.03 | 7.67 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.59 | 0.33 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.35 | 5.83 | 28.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 28.48 | 11.67 | 28.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.23 | 6.50 | 28.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.09 | 10.50 | 28.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.00 | 6.00 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.73 | 4.00 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.63 | 3.33 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 55.17 | 28.17 | 48.17 | 28.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 28.48 | 11.67 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.84 | 1.83 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.02 | 3.83 | 28.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.27 | 5.33 | 28.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.14 | 8.33 | 28.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.01 | 4.33 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.92 | 7.83 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.07 | 4.50 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.38 | 3.17 | 28.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.55 | 9.83 | 28.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.13 | 6.17 | 28.13 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.33 | 27.38 |
Annual Sum or Average | 0.00 | 0.00 | 64.33 | 28.15 | 55.50 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.55 | 9.83 | 28.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.93 | 1.67 | 27.96 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.66 | 4.50 | 28.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.66 | 8.33 | 28.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.62 | 5.17 | 28.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.48 | 6.00 | 28.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.44 | 3.50 | 28.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.42 | 2.17 | 28.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.40 | 4.17 | 28.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 51.50 | 28.54 | 35.50 | 28.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.66 | 8.33 | 28.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.64 | 4.00 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.73 | 2.50 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.51 | 5.83 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.49 | 3.67 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.50 | 27.58 | 16.00 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.73 | 5.83 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.97 | 4.83 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.28 | 8.50 | 28.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.01 | 4.83 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.79 | 9.33 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.72 | 6.50 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.64 | 3.67 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.65 | 3.83 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 46.00 | 27.90 | 41.50 | 27.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.28 | 9.33 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.84 | 2.00 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.83 | 9.00 | 25.83 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 25.82 | 32.00 | 25.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 26.38 | 43.67 | 26.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 26.07 | 45.50 | 26.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 25.94 | 34.33 | 25.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 25.59 | 34.17 | 25.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 25.56 | 29.50 | 25.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 26.09 | 38.17 | 26.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.14 | 11.83 | 27.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.64 | 1.50 | 27.64 |
Annual Sum or Average | 0.00 | 0.00 | 288.83 | 26.02 | 282.00 | 26.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.56 | 0.33 | 25.54 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 27.84 | 45.50 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.30 | 3.83 | 28.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.51 | 5.83 | 28.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.32 | 4.17 | 28.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.09 | 5.33 | 28.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.00 | 4.00 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.43 | 2.00 | 28.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.21 | 4.17 | 28.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 44.83 | 28.25 | 30.17 | 28.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.51 | 5.83 | 28.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.47 | 1.67 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.87 | 5.17 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.85 | 2.83 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.58 | 5.50 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.44 | 3.17 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.00 | 27.68 | 18.33 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.87 | 5.50 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.07 | 6.50 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.43 | 9.33 | 28.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.18 | 4.83 | 28.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.96 | 7.83 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.70 | 5.67 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.67 | 2.33 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.80 | 2.67 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 43.17 | 28.05 | 40.00 | 28.06 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.43 | 9.33 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.83 | 2.33 | 27.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.91 | 3.83 | 27.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.09 | 4.83 | 28.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.92 | 6.67 | 27.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.86 | 3.00 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.62 | 7.17 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.83 | 4.50 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.16 | 3.50 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.47 | 9.83 | 28.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.20 | 7.00 | 28.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.77 | 0.83 | 27.77 |
Annual Sum or Average | 0.00 | 0.00 | 58.83 | 28.01 | 53.50 | 28.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.47 | 9.83 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.91 | 1.33 | 27.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.52 | 4.00 | 28.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.54 | 7.00 | 28.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.49 | 4.00 | 28.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.41 | 4.67 | 28.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.24 | 3.17 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.33 | 2.17 | 28.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.25 | 4.00 | 28.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 43.83 | 28.42 | 30.33 | 28.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.54 | 7.00 | 28.61 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 119.17 | 23.68 | 119.33 | 24.26 | 12.17 | 24.24 |
February | 19.67 | 23.77 | 247.67 | 24.55 | 0.00 | 24.55 |
March | 0.00 | 0.00 | 441.83 | 24.44 | 0.00 | 24.44 |
April | 0.00 | 0.00 | 456.00 | 24.46 | 0.00 | 24.46 |
May | 0.00 | 0.00 | 507.33 | 24.40 | 0.00 | 24.40 |
June | 0.00 | 0.00 | 496.00 | 24.36 | 0.00 | 24.36 |
July | 0.00 | 0.00 | 497.00 | 24.42 | 0.00 | 24.42 |
August | 0.00 | 0.00 | 514.00 | 24.40 | 0.00 | 24.40 |
September | 0.00 | 0.00 | 485.00 | 24.49 | 0.00 | 24.49 |
October | 0.00 | 0.00 | 502.00 | 24.50 | 0.00 | 24.50 |
November | 0.00 | 0.00 | 429.50 | 24.48 | 0.00 | 24.48 |
December | 36.67 | 23.79 | 171.83 | 24.55 | 0.00 | 24.55 |
Annual Sum or Average | 175.50 | 23.72 | 4867.50 | 24.44 | 12.17 | 24.44 |
Minimum of Months | 0.00 | 0.00 | 119.33 | 24.26 | 0.00 | 24.24 |
Maximum of Months | 119.17 | 23.79 | 514.00 | 24.55 | 12.17 | 24.55 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.83 | 22.94 | 1.83 | 22.95 | 0.00 | 22.95 |
February | 221.33 | 23.18 | 73.67 | 23.45 | 0.00 | 23.45 |
March | 73.17 | 23.47 | 301.83 | 24.11 | 0.00 | 24.11 |
April | 0.00 | 0.00 | 415.83 | 24.33 | 0.00 | 24.33 |
May | 0.00 | 0.00 | 499.33 | 24.31 | 0.00 | 24.31 |
June | 0.00 | 0.00 | 496.00 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 497.00 | 24.32 | 0.00 | 24.32 |
August | 0.00 | 0.00 | 514.00 | 24.31 | 0.00 | 24.31 |
September | 2.83 | 27.13 | 483.00 | 24.38 | 2.83 | 24.40 |
October | 0.00 | 0.00 | 450.83 | 24.32 | 0.00 | 24.32 |
November | 103.17 | 23.37 | 201.83 | 23.98 | 0.00 | 23.98 |
December | 338.17 | 23.12 | 3.83 | 23.13 | 0.00 | 23.13 |
Annual Sum or Average | 1155.50 | 23.12 | 3939.00 | 24.04 | 2.83 | 24.04 |
Minimum of Months | 0.00 | 0.00 | 1.83 | 22.95 | 0.00 | 22.95 |
Maximum of Months | 416.83 | 27.13 | 514.00 | 24.38 | 2.83 | 24.40 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 470.33 | 22.03 | 31.17 | 21.90 | 31.17 | 21.77 |
February | 330.00 | 22.60 | 51.33 | 22.81 | 0.00 | 22.81 |
March | 161.33 | 23.11 | 235.33 | 23.73 | 0.00 | 23.73 |
April | 18.67 | 23.32 | 387.50 | 24.27 | 0.00 | 24.27 |
May | 1.67 | 26.47 | 502.83 | 24.33 | 1.67 | 24.34 |
June | 1.67 | 26.49 | 491.83 | 24.29 | 1.67 | 24.29 |
July | 0.50 | 26.47 | 497.00 | 24.34 | 0.50 | 24.35 |
August | 0.00 | 0.00 | 514.00 | 24.30 | 0.00 | 24.30 |
September | 8.33 | 24.25 | 467.67 | 24.33 | 2.67 | 24.35 |
October | 58.83 | 23.14 | 352.00 | 24.09 | 0.00 | 24.09 |
November | 269.50 | 22.90 | 118.00 | 23.24 | 0.00 | 23.24 |
December | 436.50 | 22.25 | 16.50 | 22.19 | 14.33 | 22.14 |
Annual Sum or Average | 1757.33 | 22.50 | 3665.17 | 23.67 | 52.00 | 23.64 |
Minimum of Months | 0.00 | 0.00 | 16.50 | 21.90 | 0.00 | 21.77 |
Maximum of Months | 470.33 | 26.49 | 514.00 | 24.34 | 31.17 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.33 | 21.08 | 111.50 | 20.84 | 111.50 | 20.67 |
February | 393.50 | 21.66 | 65.83 | 21.71 | 33.50 | 21.60 |
March | 262.67 | 22.36 | 186.50 | 23.07 | 0.00 | 23.07 |
April | 68.67 | 23.27 | 376.00 | 24.22 | 9.17 | 24.27 |
May | 38.50 | 26.53 | 492.67 | 24.60 | 36.33 | 24.74 |
June | 43.00 | 26.16 | 486.50 | 24.54 | 41.00 | 24.67 |
July | 70.83 | 26.34 | 495.33 | 24.72 | 70.83 | 24.90 |
August | 48.33 | 26.15 | 504.50 | 24.51 | 48.33 | 24.64 |
September | 65.67 | 24.72 | 430.33 | 24.41 | 40.33 | 24.53 |
October | 156.00 | 22.54 | 278.83 | 23.60 | 1.00 | 23.60 |
November | 363.33 | 21.99 | 82.17 | 22.27 | 8.83 | 22.22 |
December | 495.17 | 21.30 | 83.33 | 21.09 | 83.33 | 20.93 |
Annual Sum or Average | 2507.00 | 22.14 | 3593.50 | 23.27 | 484.17 | 23.26 |
Minimum of Months | 38.50 | 21.08 | 65.83 | 20.84 | 0.00 | 20.67 |
Maximum of Months | 501.33 | 26.53 | 504.50 | 24.72 | 111.50 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.50 | 21.31 | 80.00 | 21.09 | 80.00 | 20.92 |
February | 335.83 | 21.79 | 89.83 | 22.07 | 22.33 | 21.96 |
March | 189.83 | 22.31 | 266.17 | 23.42 | 1.17 | 23.43 |
April | 70.00 | 24.20 | 408.67 | 24.44 | 26.00 | 24.57 |
May | 53.33 | 26.77 | 491.33 | 24.72 | 51.33 | 24.92 |
June | 51.83 | 26.16 | 480.33 | 24.57 | 47.33 | 24.73 |
July | 78.67 | 26.46 | 490.50 | 24.76 | 78.33 | 24.97 |
August | 56.17 | 26.18 | 493.33 | 24.53 | 53.33 | 24.69 |
September | 76.83 | 24.73 | 426.33 | 24.43 | 46.83 | 24.58 |
October | 136.67 | 22.78 | 333.17 | 23.88 | 12.83 | 23.95 |
November | 275.00 | 21.97 | 151.83 | 22.66 | 7.00 | 22.62 |
December | 486.83 | 21.60 | 55.50 | 21.42 | 55.50 | 21.26 |
Annual Sum or Average | 2310.50 | 22.42 | 3767.00 | 23.51 | 482.00 | 23.57 |
Minimum of Months | 51.83 | 21.31 | 55.50 | 21.09 | 1.17 | 20.92 |
Maximum of Months | 499.50 | 26.77 | 493.33 | 24.76 | 80.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.17 | 21.34 | 160.33 | 21.73 | 61.67 | 21.51 |
February | 266.67 | 21.85 | 177.33 | 22.69 | 26.00 | 22.60 |
March | 197.83 | 22.66 | 276.83 | 23.62 | 12.83 | 23.71 |
April | 77.50 | 23.96 | 387.50 | 24.40 | 22.50 | 24.51 |
May | 40.17 | 26.60 | 489.50 | 24.62 | 37.83 | 24.77 |
June | 43.50 | 26.12 | 485.50 | 24.53 | 41.50 | 24.66 |
July | 70.33 | 26.37 | 494.83 | 24.72 | 70.33 | 24.91 |
August | 50.50 | 26.28 | 504.33 | 24.54 | 50.50 | 24.68 |
September | 70.17 | 25.05 | 434.33 | 24.52 | 46.17 | 24.66 |
October | 140.50 | 23.74 | 349.83 | 24.29 | 38.33 | 24.50 |
November | 238.67 | 22.54 | 247.67 | 23.49 | 27.17 | 23.60 |
December | 312.33 | 21.51 | 187.17 | 22.18 | 48.50 | 21.98 |
Annual Sum or Average | 1863.33 | 22.71 | 4195.17 | 23.80 | 483.33 | 23.87 |
Minimum of Months | 40.17 | 21.34 | 160.33 | 21.73 | 12.83 | 21.51 |
Maximum of Months | 355.17 | 26.60 | 504.33 | 24.72 | 70.33 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.67 | 21.09 | 107.67 | 20.90 | 99.33 | 20.73 |
February | 355.17 | 21.52 | 103.83 | 21.85 | 32.00 | 21.73 |
March | 263.17 | 22.21 | 203.67 | 23.07 | 5.67 | 23.11 |
April | 100.83 | 23.50 | 363.33 | 24.26 | 24.17 | 24.38 |
May | 64.50 | 25.74 | 468.17 | 24.60 | 54.33 | 24.76 |
June | 65.67 | 25.63 | 478.00 | 24.50 | 57.17 | 24.65 |
July | 67.33 | 26.23 | 481.67 | 24.61 | 64.00 | 24.80 |
August | 56.83 | 25.55 | 477.83 | 24.41 | 45.33 | 24.56 |
September | 87.83 | 23.99 | 400.50 | 24.29 | 38.00 | 24.42 |
October | 190.83 | 22.68 | 271.33 | 23.63 | 16.83 | 23.74 |
November | 333.83 | 21.79 | 133.67 | 22.38 | 8.67 | 22.34 |
December | 443.83 | 21.26 | 98.50 | 21.17 | 75.83 | 21.00 |
Annual Sum or Average | 2489.50 | 22.20 | 3588.17 | 23.30 | 521.33 | 23.33 |
Minimum of Months | 56.83 | 21.09 | 98.50 | 20.90 | 5.67 | 20.73 |
Maximum of Months | 459.67 | 26.23 | 481.67 | 24.61 | 99.33 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.61 | 29.67 | 21.53 | 29.67 | 21.45 |
February | 406.33 | 22.11 | 21.50 | 22.17 | 5.33 | 22.15 |
March | 259.83 | 22.74 | 167.00 | 23.26 | 0.00 | 23.26 |
April | 36.50 | 23.10 | 379.00 | 24.22 | 1.00 | 24.23 |
May | 15.67 | 26.68 | 506.00 | 24.50 | 15.67 | 24.56 |
June | 24.00 | 26.38 | 496.00 | 24.51 | 24.00 | 24.59 |
July | 55.67 | 26.49 | 497.00 | 24.76 | 55.67 | 24.92 |
August | 30.50 | 26.47 | 514.00 | 24.56 | 30.50 | 24.66 |
September | 22.67 | 26.42 | 485.00 | 24.53 | 22.67 | 24.61 |
October | 27.00 | 22.98 | 423.50 | 24.20 | 0.00 | 24.20 |
November | 268.50 | 22.74 | 116.17 | 23.11 | 0.00 | 23.11 |
December | 491.67 | 21.97 | 8.50 | 21.94 | 8.50 | 21.91 |
Annual Sum or Average | 2140.33 | 22.45 | 3643.33 | 23.64 | 193.00 | 23.69 |
Minimum of Months | 15.67 | 21.61 | 8.50 | 21.53 | 0.00 | 21.45 |
Maximum of Months | 502.00 | 26.68 | 514.00 | 24.76 | 55.67 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.67 | 21.90 | 28.83 | 21.83 | 28.83 | 21.76 |
February | 328.50 | 22.23 | 71.00 | 22.59 | 0.50 | 22.58 |
March | 167.50 | 22.62 | 273.33 | 23.60 | 0.33 | 23.60 |
April | 41.50 | 24.43 | 418.50 | 24.45 | 16.00 | 24.53 |
May | 39.83 | 26.93 | 505.83 | 24.66 | 39.83 | 24.82 |
June | 34.00 | 26.61 | 495.17 | 24.54 | 34.00 | 24.67 |
July | 65.67 | 26.60 | 497.00 | 24.79 | 65.67 | 24.98 |
August | 40.50 | 26.63 | 514.00 | 24.58 | 40.50 | 24.72 |
September | 32.83 | 26.42 | 483.83 | 24.54 | 32.83 | 24.65 |
October | 37.50 | 24.09 | 432.00 | 24.37 | 12.00 | 24.43 |
November | 182.17 | 22.61 | 217.67 | 23.45 | 0.00 | 23.45 |
December | 456.33 | 22.19 | 9.50 | 22.20 | 5.17 | 22.18 |
Annual Sum or Average | 1922.00 | 22.78 | 3946.67 | 23.85 | 275.67 | 23.94 |
Minimum of Months | 32.83 | 21.90 | 9.50 | 21.83 | 0.00 | 21.76 |
Maximum of Months | 495.67 | 26.93 | 514.00 | 24.79 | 65.67 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 345.50 | 21.99 | 109.33 | 22.51 | 15.33 | 22.49 |
February | 233.67 | 22.29 | 167.83 | 23.23 | 2.67 | 23.26 |
March | 141.33 | 22.81 | 306.00 | 23.87 | 6.67 | 23.92 |
April | 42.50 | 24.42 | 423.83 | 24.55 | 19.67 | 24.62 |
May | 77.33 | 25.64 | 506.67 | 24.78 | 77.33 | 24.88 |
June | 127.00 | 25.04 | 496.00 | 24.70 | 127.00 | 24.75 |
July | 227.00 | 24.87 | 497.00 | 24.72 | 227.00 | 24.76 |
August | 243.17 | 24.62 | 514.00 | 24.57 | 243.17 | 24.58 |
September | 170.17 | 24.77 | 485.00 | 24.64 | 170.17 | 24.67 |
October | 87.00 | 25.43 | 474.67 | 24.77 | 72.67 | 24.92 |
November | 117.00 | 23.51 | 331.83 | 24.30 | 26.83 | 24.46 |
December | 273.33 | 22.22 | 166.00 | 23.14 | 1.00 | 23.15 |
Annual Sum or Average | 2085.00 | 23.56 | 4478.17 | 24.25 | 989.50 | 24.36 |
Minimum of Months | 42.50 | 21.99 | 109.33 | 22.51 | 1.00 | 22.49 |
Maximum of Months | 345.50 | 25.64 | 514.00 | 24.78 | 243.17 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.67 | 21.68 | 37.33 | 21.64 | 30.83 | 21.57 |
February | 354.17 | 22.01 | 65.83 | 22.37 | 0.83 | 22.36 |
March | 227.83 | 22.55 | 209.67 | 23.33 | 1.83 | 23.35 |
April | 52.00 | 24.03 | 392.67 | 24.39 | 15.33 | 24.47 |
May | 35.67 | 26.99 | 504.83 | 24.60 | 35.67 | 24.75 |
June | 41.17 | 26.71 | 494.00 | 24.58 | 41.17 | 24.73 |
July | 49.83 | 26.71 | 497.00 | 24.71 | 49.83 | 24.87 |
August | 34.50 | 26.80 | 514.00 | 24.55 | 34.50 | 24.68 |
September | 30.17 | 26.54 | 481.83 | 24.53 | 30.17 | 24.64 |
October | 50.50 | 24.10 | 412.67 | 24.33 | 16.00 | 24.42 |
November | 240.33 | 22.53 | 163.17 | 23.18 | 0.00 | 23.18 |
December | 429.17 | 21.90 | 41.33 | 22.05 | 6.33 | 22.02 |
Annual Sum or Average | 2005.00 | 22.59 | 3814.33 | 23.75 | 262.50 | 23.84 |
Minimum of Months | 30.17 | 21.68 | 37.33 | 21.64 | 0.00 | 21.57 |
Maximum of Months | 459.67 | 26.99 | 514.00 | 24.71 | 49.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.33 | 21.47 | 46.17 | 21.34 | 46.17 | 21.22 |
February | 382.00 | 22.09 | 47.00 | 22.23 | 8.50 | 22.19 |
March | 213.67 | 22.74 | 215.00 | 23.42 | 0.00 | 23.42 |
April | 33.50 | 23.61 | 411.67 | 24.33 | 5.50 | 24.36 |
May | 30.17 | 26.71 | 506.33 | 24.60 | 30.17 | 24.71 |
June | 31.50 | 26.31 | 495.00 | 24.53 | 31.50 | 24.63 |
July | 66.00 | 26.33 | 497.00 | 24.75 | 66.00 | 24.92 |
August | 45.00 | 26.19 | 514.00 | 24.54 | 45.00 | 24.66 |
September | 36.67 | 26.02 | 467.17 | 24.51 | 35.83 | 24.61 |
October | 79.50 | 22.80 | 343.50 | 23.96 | 0.17 | 23.96 |
November | 322.17 | 22.50 | 99.17 | 22.85 | 0.00 | 22.85 |
December | 490.83 | 21.75 | 21.67 | 21.68 | 21.67 | 21.61 |
Annual Sum or Average | 2230.33 | 22.44 | 3663.67 | 23.59 | 290.50 | 23.64 |
Minimum of Months | 30.17 | 21.47 | 21.67 | 21.34 | 0.00 | 21.22 |
Maximum of Months | 499.33 | 26.71 | 514.00 | 24.75 | 66.00 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 423.50 | 21.59 | 30.17 | 21.47 | 30.17 | 21.36 |
February | 290.67 | 22.05 | 63.67 | 22.38 | 7.33 | 22.33 |
March | 161.83 | 22.58 | 212.50 | 23.54 | 1.50 | 23.56 |
April | 46.33 | 24.62 | 347.33 | 24.58 | 20.50 | 24.70 |
May | 47.17 | 26.85 | 425.33 | 24.80 | 46.00 | 24.99 |
June | 38.00 | 26.56 | 413.67 | 24.64 | 37.83 | 24.79 |
July | 71.00 | 26.47 | 420.00 | 24.86 | 71.00 | 25.06 |
August | 50.33 | 26.35 | 427.50 | 24.61 | 50.33 | 24.78 |
September | 54.17 | 25.47 | 379.00 | 24.57 | 42.67 | 24.72 |
October | 94.67 | 23.08 | 292.83 | 24.10 | 12.00 | 24.18 |
November | 238.00 | 22.31 | 120.83 | 22.97 | 0.00 | 22.97 |
December | 406.67 | 21.86 | 14.83 | 21.82 | 13.33 | 21.76 |
Annual Sum or Average | 1922.33 | 22.68 | 3147.67 | 23.75 | 332.67 | 23.86 |
Minimum of Months | 38.00 | 21.59 | 14.83 | 21.47 | 0.00 | 21.36 |
Maximum of Months | 423.50 | 26.85 | 427.50 | 24.86 | 71.00 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.17 | 21.77 | 142.33 | 22.30 | 27.83 | 22.16 |
February | 238.83 | 22.29 | 180.00 | 23.19 | 10.33 | 23.19 |
March | 147.17 | 23.07 | 312.33 | 23.92 | 12.00 | 24.00 |
April | 44.67 | 24.73 | 421.67 | 24.50 | 19.00 | 24.60 |
May | 35.33 | 26.76 | 505.83 | 24.62 | 35.33 | 24.75 |
June | 30.17 | 26.32 | 494.83 | 24.52 | 30.17 | 24.62 |
July | 65.83 | 26.37 | 497.00 | 24.75 | 65.83 | 24.92 |
August | 49.17 | 26.33 | 514.00 | 24.58 | 49.17 | 24.72 |
September | 46.67 | 26.34 | 468.17 | 24.62 | 45.83 | 24.77 |
October | 90.17 | 24.73 | 409.50 | 24.57 | 40.33 | 24.76 |
November | 193.67 | 23.15 | 270.17 | 23.96 | 24.17 | 24.12 |
December | 276.67 | 21.96 | 167.83 | 22.86 | 10.00 | 22.81 |
Annual Sum or Average | 1539.50 | 23.13 | 4383.67 | 24.09 | 370.00 | 24.19 |
Minimum of Months | 30.17 | 21.77 | 142.33 | 22.30 | 10.00 | 22.16 |
Maximum of Months | 321.17 | 26.76 | 514.00 | 24.75 | 65.83 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 453.00 | 21.44 | 57.00 | 21.37 | 44.67 | 21.25 |
February | 347.00 | 21.88 | 85.17 | 22.29 | 8.33 | 22.25 |
March | 222.83 | 22.51 | 226.00 | 23.36 | 4.00 | 23.40 |
April | 59.50 | 24.07 | 392.00 | 24.41 | 19.00 | 24.52 |
May | 40.83 | 26.80 | 494.00 | 24.62 | 39.17 | 24.78 |
June | 43.83 | 26.46 | 488.17 | 24.55 | 41.83 | 24.70 |
July | 54.83 | 26.52 | 492.00 | 24.64 | 54.83 | 24.81 |
August | 40.33 | 26.43 | 500.50 | 24.46 | 40.33 | 24.60 |
September | 57.00 | 24.93 | 438.33 | 24.43 | 36.17 | 24.56 |
October | 126.50 | 23.05 | 325.67 | 23.96 | 15.67 | 24.06 |
November | 307.33 | 22.24 | 134.67 | 22.84 | 0.00 | 22.84 |
December | 432.50 | 21.64 | 55.17 | 21.76 | 19.00 | 21.70 |
Annual Sum or Average | 2185.50 | 22.45 | 3688.67 | 23.60 | 323.00 | 23.68 |
Minimum of Months | 40.33 | 21.44 | 55.17 | 21.37 | 0.00 | 21.25 |
Maximum of Months | 453.00 | 26.80 | 500.50 | 24.64 | 54.83 | 24.81 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.20343 | 37.25631 | 0.37075 | 8.13228 |
February | 454.00000 | 24.34645 | 39.43324 | 0.44957 | 9.50270 |
March | 514.00000 | 24.38384 | 43.75185 | 0.52722 | 11.08366 |
April | 485.00000 | 24.43007 | 44.67048 | 0.56702 | 12.02713 |
May | 508.00000 | 24.39551 | 50.44184 | -0.2258 | 6.54789 |
June | 496.00000 | 24.35899 | 52.68477 | -0.2217 | 6.48308 |
July | 497.00000 | 24.41839 | 53.65965 | -0.2031 | 6.37500 |
August | 514.00000 | 24.39684 | 53.74018 | -0.2039 | 6.41226 |
September | 485.00000 | 24.48699 | 53.13019 | -0.1875 | 6.47130 |
October | 502.00000 | 24.49865 | 48.45904 | 0.60530 | 13.01432 |
November | 489.00000 | 24.42765 | 42.51247 | 0.52215 | 10.97381 |
December | 497.00000 | 24.30655 | 36.68467 | 0.41075 | 8.71998 |
Annual Sum or Average | 5943.00000 | 24.38771 | 46.42804 | 0.19826 | 8.80108 |
Minimum of Months | 454.00000 | 24.20343 | 36.68467 | -0.2258 | 6.37500 |
Maximum of Months | 514.00000 | 24.49865 | 53.74018 | 0.60530 | 13.01432 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.12519 | 39.77513 | 0.10296 | 5.92615 |
February | 454.00000 | 23.66274 | 40.74401 | 0.26727 | 7.06763 |
March | 514.00000 | 24.08737 | 44.29268 | 0.43358 | 9.20991 |
April | 485.00000 | 24.28377 | 46.04731 | 0.52132 | 10.89676 |
May | 508.00000 | 24.30049 | 52.12824 | -0.2689 | 6.82524 |
June | 496.00000 | 24.25930 | 54.62495 | -0.2653 | 6.73138 |
July | 497.00000 | 24.32286 | 55.38000 | -0.2477 | 6.63291 |
August | 514.00000 | 24.30555 | 55.56026 | -0.2517 | 6.69650 |
September | 485.00000 | 24.36380 | 55.14619 | -0.2476 | 6.81395 |
October | 502.00000 | 24.27766 | 49.60062 | 0.53230 | 11.13803 |
November | 489.00000 | 23.99346 | 43.15504 | 0.38729 | 8.44950 |
December | 497.00000 | 23.41387 | 38.36893 | 0.17743 | 6.24167 |
Annual Sum or Average | 5943.00000 | 24.03540 | 47.96211 | 0.09302 | 7.71950 |
Minimum of Months | 454.00000 | 23.12519 | 38.36893 | -0.2689 | 5.92615 |
Maximum of Months | 514.00000 | 24.36380 | 55.56026 | 0.53230 | 11.13803 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15334 | 40.96133 | -0.1252 | 6.84008 |
February | 454.00000 | 22.98830 | 41.25647 | 0.11083 | 6.56676 |
March | 514.00000 | 23.78520 | 43.70641 | 0.36556 | 8.44996 |
April | 485.00000 | 24.21927 | 45.45232 | 0.52372 | 11.08312 |
May | 508.00000 | 24.31765 | 51.77357 | -0.2246 | 6.54928 |
June | 496.00000 | 24.27196 | 54.51213 | -0.2194 | 6.42454 |
July | 497.00000 | 24.34262 | 55.54760 | -0.2068 | 6.39009 |
August | 514.00000 | 24.29569 | 55.74156 | -0.2269 | 6.51688 |
September | 485.00000 | 24.29512 | 55.16439 | -0.2512 | 6.96807 |
October | 502.00000 | 24.02800 | 49.29576 | 0.47646 | 10.16690 |
November | 489.00000 | 23.38871 | 43.29891 | 0.24214 | 7.13833 |
December | 497.00000 | 22.45355 | 39.47982 | -0.0487 | 6.46729 |
Annual Sum or Average | 5943.00000 | 23.71695 | 48.07263 | 0.03343 | 7.46441 |
Minimum of Months | 454.00000 | 22.15334 | 39.47982 | -0.2512 | 6.39009 |
Maximum of Months | 514.00000 | 24.34262 | 55.74156 | 0.52372 | 11.08312 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.07841 | 43.62261 | -0.3841 | 9.84411 |
February | 454.00000 | 21.95538 | 44.09720 | -0.1150 | 7.42921 |
March | 514.00000 | 23.14254 | 45.32354 | 0.24633 | 8.12678 |
April | 485.00000 | 24.10670 | 45.62066 | 0.54876 | 12.35410 |
May | 508.00000 | 24.41653 | 51.61243 | -0.0868 | 6.63450 |
June | 496.00000 | 24.37220 | 54.60767 | -0.0689 | 6.36408 |
July | 497.00000 | 24.48908 | 56.29704 | -0.0528 | 6.66346 |
August | 514.00000 | 24.32427 | 56.52967 | -0.1260 | 6.59800 |
September | 485.00000 | 24.20635 | 56.69467 | -0.2046 | 7.46476 |
October | 502.00000 | 23.58850 | 50.37770 | 0.40778 | 9.86469 |
November | 489.00000 | 22.45387 | 45.54214 | 0.04395 | 7.05739 |
December | 497.00000 | 21.31079 | 42.06613 | -0.3161 | 8.77763 |
Annual Sum or Average | 5943.00000 | 23.29716 | 49.41021 | -0.0087 | 8.09348 |
Minimum of Months | 454.00000 | 21.07841 | 42.06613 | -0.3841 | 6.36408 |
Maximum of Months | 514.00000 | 24.48908 | 56.69467 | 0.54876 | 12.35410 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.31658 | 43.19653 | -0.3002 | 8.63488 |
February | 454.00000 | 22.35509 | 43.21458 | 0.00419 | 7.52169 |
March | 514.00000 | 23.43147 | 44.56487 | 0.35286 | 9.69832 |
April | 485.00000 | 24.24900 | 45.19608 | 0.64132 | 15.00220 |
May | 508.00000 | 24.45681 | 51.45412 | 0.00505 | 7.21002 |
June | 496.00000 | 24.35387 | 54.62691 | -0.0213 | 6.76890 |
July | 497.00000 | 24.46746 | 56.32880 | -0.0231 | 7.16305 |
August | 514.00000 | 24.28280 | 56.64169 | -0.1057 | 6.94513 |
September | 485.00000 | 24.18301 | 56.71239 | -0.1659 | 7.63750 |
October | 502.00000 | 23.77803 | 49.83791 | 0.49008 | 11.83755 |
November | 489.00000 | 22.83853 | 44.61075 | 0.16008 | 7.90095 |
December | 497.00000 | 21.64218 | 41.41005 | -0.2161 | 7.77383 |
Annual Sum or Average | 5943.00000 | 23.45439 | 49.03130 | 0.06835 | 8.67142 |
Minimum of Months | 454.00000 | 21.31658 | 41.41005 | -0.3002 | 6.76890 |
Maximum of Months | 514.00000 | 24.46746 | 56.71239 | 0.64132 | 15.00220 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.18480 | 41.13641 | -0.0776 | 9.33634 |
February | 454.00000 | 22.86272 | 41.73212 | 0.14051 | 9.40141 |
March | 514.00000 | 23.54606 | 44.08165 | 0.39025 | 10.79624 |
April | 485.00000 | 24.20725 | 45.24956 | 0.60727 | 14.15786 |
May | 508.00000 | 24.41289 | 51.59433 | -0.0772 | 6.80939 |
June | 496.00000 | 24.36164 | 54.64114 | -0.0743 | 6.40716 |
July | 497.00000 | 24.48418 | 56.30201 | -0.0524 | 6.73531 |
August | 514.00000 | 24.33837 | 56.43123 | -0.1082 | 6.72478 |
September | 485.00000 | 24.27593 | 56.31625 | -0.1371 | 7.52178 |
October | 502.00000 | 24.02320 | 48.96963 | 0.57819 | 14.48507 |
November | 489.00000 | 23.39313 | 42.85428 | 0.33687 | 11.28247 |
December | 497.00000 | 22.58156 | 39.00325 | 0.02675 | 9.34107 |
Annual Sum or Average | 5943.00000 | 23.72860 | 48.24786 | 0.12854 | 9.40455 |
Minimum of Months | 454.00000 | 22.18480 | 39.00325 | -0.1371 | 6.40716 |
Maximum of Months | 514.00000 | 24.48418 | 56.43123 | 0.60727 | 14.48507 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.32368 | 43.43084 | -0.3058 | 9.60864 |
February | 454.00000 | 22.08361 | 43.72904 | -0.0590 | 8.11703 |
March | 514.00000 | 23.07189 | 45.35988 | 0.27608 | 9.30389 |
April | 485.00000 | 24.04686 | 45.73054 | 0.59455 | 14.33586 |
May | 508.00000 | 24.32983 | 51.84935 | -0.0441 | 7.79341 |
June | 496.00000 | 24.28821 | 54.85679 | -0.0333 | 7.28428 |
July | 497.00000 | 24.33879 | 56.73025 | -0.0651 | 7.39179 |
August | 514.00000 | 24.16997 | 57.00272 | -0.1396 | 7.34690 |
September | 485.00000 | 24.05437 | 57.11497 | -0.2015 | 8.41149 |
October | 502.00000 | 23.49763 | 50.57939 | 0.43060 | 11.21728 |
November | 489.00000 | 22.49045 | 45.32468 | 0.09003 | 8.04358 |
December | 497.00000 | 21.54202 | 41.53178 | -0.2421 | 8.84220 |
Annual Sum or Average | 5943.00000 | 23.27861 | 49.48494 | 0.02508 | 8.96927 |
Minimum of Months | 454.00000 | 21.32368 | 41.53178 | -0.3058 | 7.28428 |
Maximum of Months | 514.00000 | 24.33879 | 57.11497 | 0.59455 | 14.33586 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.61318 | 43.93738 | -0.2278 | 6.93161 |
February | 454.00000 | 22.29868 | 45.16075 | -0.0268 | 6.26566 |
March | 514.00000 | 23.33619 | 46.96367 | 0.27489 | 7.53264 |
April | 485.00000 | 24.14797 | 45.56399 | 0.51696 | 11.07126 |
May | 508.00000 | 24.42876 | 50.54244 | -0.1412 | 6.23018 |
June | 496.00000 | 24.41861 | 52.83221 | -0.0998 | 5.97126 |
July | 497.00000 | 24.56720 | 53.89480 | -0.0516 | 6.20673 |
August | 514.00000 | 24.44921 | 54.07464 | -0.0944 | 6.05835 |
September | 485.00000 | 24.44581 | 53.96951 | -0.1348 | 6.25506 |
October | 502.00000 | 24.13403 | 49.65308 | 0.53562 | 11.40158 |
November | 489.00000 | 23.24752 | 45.88514 | 0.24418 | 7.09904 |
December | 497.00000 | 21.98620 | 42.33055 | -0.1234 | 6.20935 |
Annual Sum or Average | 5943.00000 | 23.59834 | 48.76914 | 0.05580 | 7.27003 |
Minimum of Months | 454.00000 | 21.61318 | 42.33055 | -0.2278 | 5.97126 |
Maximum of Months | 514.00000 | 24.56720 | 54.07464 | 0.53562 | 11.40158 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.92443 | 43.36855 | -0.1266 | 6.25744 |
February | 454.00000 | 22.72007 | 44.04658 | 0.10122 | 6.78050 |
March | 514.00000 | 23.60808 | 46.02696 | 0.38338 | 9.27299 |
April | 485.00000 | 24.28931 | 44.99447 | 0.61482 | 13.75923 |
May | 508.00000 | 24.47767 | 50.27966 | -0.0407 | 6.48599 |
June | 496.00000 | 24.39821 | 52.82307 | -0.0503 | 6.13897 |
July | 497.00000 | 24.54736 | 53.91291 | -0.0207 | 6.47120 |
August | 514.00000 | 24.42375 | 54.13424 | -0.0691 | 6.17298 |
September | 485.00000 | 24.40820 | 53.98772 | -0.0976 | 6.33171 |
October | 502.00000 | 24.21992 | 49.25044 | 0.60211 | 13.33607 |
November | 489.00000 | 23.50536 | 45.04785 | 0.34078 | 8.49220 |
December | 497.00000 | 22.32885 | 41.49108 | -0.0187 | 6.15577 |
Annual Sum or Average | 5943.00000 | 23.74454 | 48.32031 | 0.13437 | 7.97000 |
Minimum of Months | 454.00000 | 21.92443 | 41.49108 | -0.1266 | 6.13897 |
Maximum of Months | 514.00000 | 24.54736 | 54.13424 | 0.61482 | 13.75923 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.68857 | 40.62847 | 0.08452 | 7.35719 |
February | 454.00000 | 23.28059 | 42.14169 | 0.25629 | 8.79004 |
March | 514.00000 | 23.81837 | 44.88321 | 0.44260 | 10.54431 |
April | 485.00000 | 24.40893 | 44.65243 | 0.61189 | 13.70497 |
May | 508.00000 | 24.64122 | 51.85012 | -0.0587 | 6.31107 |
June | 496.00000 | 24.60845 | 55.99178 | -0.0266 | 6.05469 |
July | 497.00000 | 24.65773 | 59.31761 | 0.01473 | 6.16631 |
August | 514.00000 | 24.54869 | 60.55948 | -0.0039 | 6.01038 |
September | 485.00000 | 24.59711 | 58.49294 | -0.0035 | 6.22573 |
October | 502.00000 | 24.55366 | 49.47330 | 0.72401 | 17.20112 |
November | 489.00000 | 24.07337 | 43.00291 | 0.53051 | 12.69322 |
December | 497.00000 | 23.21434 | 38.68869 | 0.22267 | 8.39723 |
Annual Sum or Average | 5943.00000 | 24.09581 | 49.20676 | 0.23172 | 9.11134 |
Minimum of Months | 454.00000 | 22.68857 | 38.68869 | -0.0587 | 6.01038 |
Maximum of Months | 514.00000 | 24.65773 | 60.55948 | 0.72401 | 17.20112 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.87542 | 43.39081 | -0.1432 | 6.77568 |
February | 454.00000 | 22.47007 | 44.58642 | 0.04170 | 6.82291 |
March | 514.00000 | 23.35501 | 46.65862 | 0.32667 | 8.67498 |
April | 485.00000 | 24.19855 | 45.33793 | 0.59008 | 13.29207 |
May | 508.00000 | 24.42258 | 50.52661 | -0.0696 | 6.71454 |
June | 496.00000 | 24.40015 | 52.86926 | -0.0426 | 6.37780 |
July | 497.00000 | 24.50677 | 54.07750 | -0.0390 | 6.47834 |
August | 514.00000 | 24.39883 | 54.25968 | -0.0794 | 6.24603 |
September | 485.00000 | 24.39287 | 54.11104 | -0.1024 | 6.50693 |
October | 502.00000 | 24.13734 | 49.56524 | 0.58031 | 12.92783 |
November | 489.00000 | 23.26646 | 45.57259 | 0.29139 | 8.04831 |
December | 497.00000 | 22.18190 | 41.72969 | -0.0529 | 6.48106 |
Annual Sum or Average | 5943.00000 | 23.64174 | 48.59545 | 0.10808 | 7.94405 |
Minimum of Months | 454.00000 | 21.87542 | 41.72969 | -0.1432 | 6.24603 |
Maximum of Months | 514.00000 | 24.50677 | 54.25968 | 0.59008 | 13.29207 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.48627 | 43.58954 | -0.2645 | 7.60178 |
February | 454.00000 | 22.37991 | 43.99976 | -0.0082 | 6.57900 |
March | 514.00000 | 23.47962 | 45.74581 | 0.32014 | 8.22472 |
April | 485.00000 | 24.24526 | 45.92425 | 0.56325 | 12.22769 |
May | 508.00000 | 24.46834 | 51.66064 | -0.1048 | 6.26748 |
June | 496.00000 | 24.41660 | 54.40410 | -0.0909 | 6.06692 |
July | 497.00000 | 24.53947 | 55.77286 | -0.0685 | 6.38647 |
August | 514.00000 | 24.39682 | 56.04598 | -0.1290 | 6.32226 |
September | 485.00000 | 24.34659 | 56.34383 | -0.1799 | 6.78925 |
October | 502.00000 | 23.90359 | 50.47839 | 0.47526 | 10.37810 |
November | 489.00000 | 22.97106 | 45.56360 | 0.16917 | 6.85592 |
December | 497.00000 | 21.77242 | 41.86939 | -0.1872 | 6.90407 |
Annual Sum or Average | 5943.00000 | 23.54234 | 49.32792 | 0.04099 | 7.54907 |
Minimum of Months | 454.00000 | 21.48627 | 41.86939 | -0.2645 | 6.06692 |
Maximum of Months | 514.00000 | 24.53947 | 56.34383 | 0.56325 | 12.22769 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.60278 | 43.39010 | -0.2195 | 7.13802 |
February | 385.00000 | 22.55639 | 43.13769 | 0.05315 | 6.98960 |
March | 433.00000 | 23.54870 | 44.74773 | 0.36684 | 9.35440 |
April | 410.00000 | 24.36877 | 44.85238 | 0.63213 | 14.53306 |
May | 430.00000 | 24.56108 | 51.13646 | -0.0203 | 7.04069 |
June | 418.00000 | 24.45239 | 54.26540 | -0.0477 | 6.52740 |
July | 422.00000 | 24.57535 | 55.77784 | -0.0364 | 7.02552 |
August | 433.00000 | 24.38666 | 56.19818 | -0.1150 | 6.87599 |
September | 410.00000 | 24.32187 | 56.53268 | -0.1574 | 7.30742 |
October | 427.00000 | 23.95296 | 49.80233 | 0.51396 | 11.84160 |
November | 417.00000 | 23.05840 | 44.60868 | 0.21183 | 7.63821 |
December | 422.00000 | 21.94622 | 41.23170 | -0.1333 | 6.68738 |
Annual Sum or Average | 5034.00000 | 23.61651 | 48.84587 | 0.08700 | 8.24505 |
Minimum of Months | 385.00000 | 21.60278 | 41.23170 | -0.2195 | 6.52740 |
Maximum of Months | 433.00000 | 24.57535 | 56.53268 | 0.63213 | 14.53306 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.64977 | 40.59597 | 0.05039 | 8.09390 |
February | 454.00000 | 23.25624 | 41.58286 | 0.24153 | 9.06029 |
March | 514.00000 | 23.83746 | 44.50336 | 0.45576 | 10.96974 |
April | 485.00000 | 24.34344 | 45.51757 | 0.62185 | 14.00314 |
May | 508.00000 | 24.46851 | 51.62466 | -0.0942 | 6.36380 |
June | 496.00000 | 24.40643 | 54.43550 | -0.0964 | 6.09715 |
July | 497.00000 | 24.53512 | 55.77219 | -0.0681 | 6.43995 |
August | 514.00000 | 24.41258 | 55.93455 | -0.1108 | 6.42032 |
September | 485.00000 | 24.40760 | 55.95477 | -0.1144 | 6.83074 |
October | 502.00000 | 24.28128 | 49.11386 | 0.63521 | 15.00258 |
November | 489.00000 | 23.79456 | 43.01647 | 0.44073 | 11.64440 |
December | 497.00000 | 23.03815 | 38.66922 | 0.15373 | 8.65292 |
Annual Sum or Average | 5943.00000 | 23.95718 | 48.11541 | 0.17494 | 9.12048 |
Minimum of Months | 454.00000 | 22.64977 | 38.66922 | -0.1144 | 6.09715 |
Maximum of Months | 514.00000 | 24.53512 | 55.95477 | 0.63521 | 15.00258 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.69171 | 43.14318 | -0.1955 | 7.64094 |
February | 454.00000 | 22.41237 | 43.75232 | 0.02985 | 7.28125 |
March | 514.00000 | 23.36508 | 45.83434 | 0.34216 | 9.28674 |
April | 485.00000 | 24.20120 | 45.98113 | 0.61301 | 14.15696 |
May | 508.00000 | 24.39934 | 51.84452 | -0.0559 | 7.06699 |
June | 496.00000 | 24.35285 | 54.58176 | -0.0488 | 6.69877 |
July | 497.00000 | 24.41587 | 56.09827 | -0.0730 | 6.88067 |
August | 514.00000 | 24.26961 | 56.42172 | -0.1349 | 6.84486 |
September | 485.00000 | 24.21743 | 56.67952 | -0.1703 | 7.44826 |
October | 502.00000 | 23.80160 | 50.68749 | 0.49622 | 11.59844 |
November | 489.00000 | 22.90056 | 45.50864 | 0.19511 | 7.76204 |
December | 497.00000 | 21.94283 | 41.36529 | -0.1253 | 7.17874 |
Annual Sum or Average | 5943.00000 | 23.50541 | 49.37225 | 0.07236 | 8.31732 |
Minimum of Months | 454.00000 | 21.69171 | 41.36529 | -0.1955 | 6.69877 |
Maximum of Months | 514.00000 | 24.41587 | 56.67952 | 0.61301 | 14.15696 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.303518E+11 | 0.760224E+10 | 389.62 | 0.272199E+11 | 0.313189E+10 | 0.00 | 0.89 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 | 42547.48 | 12-JAN-15:20 | 42547.48 | 12-JAN-15:20 | 8074.56 | 17-JAN-17:30 | 9746.31 | 12-JAN-15:20 | 0.00 |
February | 0.392509E+11 | 0.951517E+10 | 366.29 | 0.359407E+11 | 0.331018E+10 | 0.00 | 1.00 | 21-FEB-13:30 | 0.00 | 01-FEB-00:10 | 56880.56 | 22-FEB-15:10 | 56880.56 | 22-FEB-15:10 | 9068.30 | 25-FEB-17:10 | 13644.53 | 22-FEB-15:10 | 0.00 |
March | 0.670322E+11 | 0.166341E+11 | 440.24 | 0.635901E+11 | 0.344205E+10 | 0.00 | 1.00 | 01-MAR-15:00 | 0.00 | 01-MAR-00:10 | 86867.50 | 29-MAR-11:10 | 81033.38 | 28-MAR-15:50 | 23094.35 | 29-MAR-11:10 | 24675.51 | 28-MAR-15:50 | 0.00 |
April | 0.917225E+11 | 0.257369E+11 | 446.39 | 0.872173E+11 | 0.450522E+10 | 0.00 | 1.00 | 01-APR-05:13 | 0.00 | 01-APR-00:10 | 138696.80 | 27-APR-04:01 | 105414.18 | 27-APR-04:01 | 33282.62 | 27-APR-04:01 | 34557.77 | 27-APR-04:01 | 0.00 |
May | 0.130182E+12 | 0.388439E+11 | 516.79 | 0.112199E+12 | 0.179823E+11 | 0.00 | 1.00 | 01-MAY-03:36 | 0.00 | 01-MAY-00:05 | 160077.45 | 24-MAY-04:01 | 124024.58 | 06-MAY-04:01 | 65240.89 | 24-MAY-04:01 | 41240.43 | 03-MAY-15:40 | 0.00 |
June | 0.145996E+12 | 0.426054E+11 | 515.58 | 0.113732E+12 | 0.322640E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 159122.81 | 27-JUN-04:01 | 121825.20 | 13-JUN-04:01 | 64049.68 | 26-JUN-04:01 | 48845.83 | 11-JUN-14:51 | 0.00 |
July | 0.156590E+12 | 0.415839E+11 | 523.27 | 0.105071E+12 | 0.515185E+11 | 0.00 | 1.00 | 01-JUL-00:02 | 0.00 | 01-JUL-00:33 | 164664.11 | 20-JUL-04:03 | 112161.32 | 07-JUL-04:01 | 83226.55 | 20-JUL-04:03 | 47537.81 | 02-JUL-16:01 | 0.00 |
August | 0.158930E+12 | 0.407329E+11 | 514.47 | 0.103829E+12 | 0.551016E+11 | 0.00 | 1.00 | 01-AUG-02:62 | 0.00 | 01-AUG-00:10 | 160399.72 | 11-AUG-04:02 | 111000.01 | 03-AUG-04:01 | 64583.36 | 11-AUG-04:02 | 43076.05 | 06-AUG-15:11 | 0.00 |
September | 0.128831E+12 | 0.326923E+11 | 465.79 | 0.900283E+11 | 0.388023E+11 | 0.00 | 1.00 | 01-SEP-02:42 | 0.00 | 01-SEP-00:10 | 158996.20 | 06-SEP-04:02 | 111195.96 | 02-SEP-04:01 | 66145.10 | 08-SEP-04:02 | 40721.61 | 24-SEP-15:41 | 0.00 |
October | 0.914698E+11 | 0.232032E+11 | 449.82 | 0.804060E+11 | 0.110638E+11 | 0.00 | 1.00 | 01-OCT-08:42 | 0.00 | 01-OCT-00:10 | 109275.60 | 12-OCT-05:12 | 93404.38 | 01-OCT-16:01 | 37626.12 | 12-OCT-05:12 | 30633.13 | 02-OCT-15:00 | 0.00 |
November | 0.591191E+11 | 0.142474E+11 | 407.65 | 0.558271E+11 | 0.329202E+10 | 0.00 | 1.00 | 01-NOV-05:12 | 0.00 | 01-NOV-00:10 | 72477.58 | 09-NOV-12:00 | 68161.64 | 08-NOV-15:10 | 13276.12 | 17-NOV-12:20 | 17943.03 | 09-NOV-12:00 | 0.00 |
December | 0.359581E+11 | 0.885921E+10 | 394.97 | 0.331645E+11 | 0.279355E+10 | 0.00 | 0.99 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 49015.32 | 01-DEC-15:10 | 49015.32 | 01-DEC-15:10 | 8089.79 | 29-DEC-18:25 | 10890.64 | 01-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.113543E+13 | 0.302257E+12 | 5430.88 | 0.908226E+12 | 0.227208E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.303518E+11 | 0.760224E+10 | 366.29 | 0.272199E+11 | 0.279355E+10 | 0.00 | 0.89 | 0.00 | 42547.48 | 42547.48 | 8074.56 | 9746.31 | 0.00 | ||||||
Maximum of Months | 0.158930E+12 | 0.426054E+11 | 523.27 | 0.113732E+12 | 0.551016E+11 | 0.00 | 1.00 | 0.00 | 164664.11 | 124024.58 | 83226.55 | 48845.83 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.224261E+11 | 0.574652E+10 | 381.01 | 0.190734E+11 | 0.335273E+10 | 0.00 | 0.77 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 33361.24 | 12-JAN-15:00 | 33361.24 | 12-JAN-15:00 | 7644.81 | 17-JAN-15:10 | 7915.41 | 12-JAN-15:00 | 0.00 |
February | 0.316413E+11 | 0.782377E+10 | 366.78 | 0.277304E+11 | 0.391095E+10 | 0.00 | 1.00 | 22-FEB-13:05 | 0.00 | 01-FEB-00:10 | 50223.53 | 22-FEB-15:10 | 50223.53 | 22-FEB-15:10 | 9045.41 | 25-FEB-17:40 | 12049.58 | 22-FEB-15:10 | 0.00 |
March | 0.583384E+11 | 0.146374E+11 | 444.02 | 0.543034E+11 | 0.403500E+10 | 0.00 | 1.00 | 03-MAR-14:40 | 0.00 | 01-MAR-00:10 | 77631.02 | 28-MAR-15:50 | 77631.02 | 28-MAR-15:50 | 11682.66 | 10-MAR-20:50 | 23523.93 | 28-MAR-15:50 | 0.00 |
April | 0.828694E+11 | 0.233000E+11 | 445.84 | 0.791277E+11 | 0.374170E+10 | 0.00 | 1.00 | 01-APR-14:00 | 0.00 | 01-APR-00:10 | 141832.12 | 27-APR-04:01 | 111958.21 | 28-APR-04:01 | 33306.06 | 27-APR-04:01 | 40787.98 | 16-APR-15:41 | 0.00 |
May | 0.117014E+12 | 0.348152E+11 | 512.22 | 0.101503E+12 | 0.155110E+11 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:05 | 152167.45 | 24-MAY-04:01 | 119482.39 | 30-MAY-04:01 | 68338.86 | 24-MAY-05:02 | 44194.31 | 29-MAY-14:01 | 0.00 |
June | 0.128154E+12 | 0.372062E+11 | 503.46 | 0.999586E+11 | 0.281958E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 153331.07 | 26-JUN-04:01 | 111590.87 | 05-JUN-04:02 | 63476.27 | 26-JUN-04:01 | 47499.33 | 11-JUN-15:31 | 0.00 |
July | 0.134601E+12 | 0.355343E+11 | 501.95 | 0.886054E+11 | 0.459952E+11 | 0.00 | 1.00 | 01-JUL-00:02 | 0.00 | 01-JUL-00:33 | 157076.74 | 20-JUL-04:01 | 105693.50 | 10-JUL-04:02 | 75481.77 | 20-JUL-04:01 | 44896.38 | 02-JUL-16:01 | 0.00 |
August | 0.131399E+12 | 0.334988E+11 | 484.70 | 0.840674E+11 | 0.473320E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 152945.78 | 19-AUG-04:01 | 100963.68 | 04-AUG-04:01 | 71096.48 | 11-AUG-04:02 | 37742.42 | 06-AUG-15:22 | 0.00 |
September | 0.104678E+12 | 0.264774E+11 | 433.21 | 0.719729E+11 | 0.327051E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 153436.91 | 11-SEP-04:02 | 104138.08 | 18-SEP-04:01 | 72660.00 | 11-SEP-04:02 | 40218.85 | 24-SEP-15:41 | 0.00 |
October | 0.738107E+11 | 0.188848E+11 | 431.04 | 0.642970E+11 | 0.951365E+10 | 0.00 | 1.00 | 01-OCT-08:42 | 0.00 | 01-OCT-00:10 | 97760.14 | 04-OCT-04:02 | 87788.32 | 01-OCT-16:01 | 29111.47 | 04-OCT-04:02 | 28548.65 | 02-OCT-14:05 | 0.00 |
November | 0.467035E+11 | 0.114852E+11 | 403.81 | 0.427329E+11 | 0.397064E+10 | 0.00 | 1.00 | 01-NOV-10:50 | 0.00 | 01-NOV-00:10 | 61750.83 | 09-NOV-13:03 | 59889.81 | 09-NOV-15:05 | 9486.53 | 08-NOV-18:50 | 15660.86 | 09-NOV-13:03 | 0.00 |
December | 0.266394E+11 | 0.673570E+10 | 390.57 | 0.231847E+11 | 0.345464E+10 | 0.00 | 0.88 | 03-DEC-13:12 | 0.00 | 01-DEC-00:10 | 39648.72 | 03-DEC-13:12 | 39648.72 | 03-DEC-13:12 | 7302.86 | 29-DEC-19:57 | 9185.08 | 03-DEC-13:12 | 0.00 |
Annual Sum or Average | 0.958275E+12 | 0.256145E+12 | 5298.61 | 0.756557E+12 | 0.201718E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.224261E+11 | 0.574652E+10 | 366.78 | 0.190734E+11 | 0.335273E+10 | 0.00 | 0.77 | 0.00 | 33361.24 | 33361.24 | 7302.86 | 7915.41 | 0.00 | ||||||
Maximum of Months | 0.134601E+12 | 0.372062E+11 | 512.22 | 0.101503E+12 | 0.473320E+11 | 0.00 | 1.00 | 0.00 | 157076.74 | 119482.39 | 75481.77 | 47499.33 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.270765E+11 | 0.693822E+10 | 376.98 | 0.231206E+11 | 0.395584E+10 | 0.00 | 0.74 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 38626.64 | 12-JAN-15:00 | 38626.64 | 12-JAN-15:00 | 8402.34 | 17-JAN-15:00 | 9222.55 | 12-JAN-15:00 | 0.00 |
February | 0.361768E+11 | 0.898205E+10 | 364.40 | 0.316795E+11 | 0.449739E+10 | 0.00 | 1.00 | 20-FEB-13:32 | 0.00 | 01-FEB-00:10 | 61142.53 | 22-FEB-14:50 | 61142.53 | 22-FEB-14:50 | 9861.08 | 15-FEB-17:20 | 14704.54 | 22-FEB-15:00 | 0.00 |
March | 0.667052E+11 | 0.168623E+11 | 442.54 | 0.617428E+11 | 0.496244E+10 | 0.00 | 1.00 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 | 97505.57 | 28-MAR-15:20 | 97505.57 | 28-MAR-15:20 | 13008.70 | 30-MAR-17:10 | 29392.74 | 28-MAR-15:10 | 0.00 |
April | 0.964509E+11 | 0.273230E+11 | 444.97 | 0.922479E+11 | 0.420297E+10 | 0.00 | 1.00 | 01-APR-13:00 | 0.00 | 01-APR-00:10 | 163416.72 | 16-APR-15:11 | 147120.07 | 16-APR-14:31 | 19887.39 | 17-APR-04:01 | 52447.75 | 16-APR-15:11 | 0.00 |
May | 0.134614E+12 | 0.403280E+11 | 511.06 | 0.118762E+12 | 0.158521E+11 | 0.00 | 1.00 | 01-MAY-07:10 | 0.00 | 01-MAY-00:05 | 182586.46 | 24-MAY-04:01 | 163473.47 | 29-MAY-15:31 | 79701.09 | 24-MAY-04:01 | 55724.00 | 28-MAY-15:01 | 0.00 |
June | 0.145881E+12 | 0.426337E+11 | 505.26 | 0.117521E+12 | 0.283594E+11 | 0.00 | 1.00 | 01-JUN-08:40 | 0.00 | 01-JUN-00:10 | 183845.55 | 27-JUN-04:01 | 151910.53 | 04-JUN-15:11 | 79834.80 | 29-JUN-05:02 | 57779.97 | 11-JUN-15:31 | 0.00 |
July | 0.148176E+12 | 0.392849E+11 | 505.91 | 0.102023E+12 | 0.461531E+11 | 0.00 | 1.00 | 01-JUL-00:02 | 0.00 | 01-JUL-00:33 | 188721.57 | 20-JUL-04:01 | 136983.99 | 04-JUL-15:02 | 91043.22 | 20-JUL-04:01 | 53901.81 | 02-JUL-16:11 | 0.00 |
August | 0.142900E+12 | 0.365650E+11 | 486.64 | 0.952715E+11 | 0.476289E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 182539.88 | 31-AUG-04:01 | 127072.97 | 14-AUG-04:01 | 82189.03 | 19-AUG-04:01 | 49763.53 | 06-AUG-15:22 | 0.00 |
September | 0.112999E+12 | 0.287830E+11 | 431.88 | 0.801449E+11 | 0.328543E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 181409.97 | 01-SEP-04:01 | 119968.12 | 18-SEP-04:01 | 76370.73 | 01-SEP-04:01 | 42001.47 | 01-SEP-04:01 | 0.00 |
October | 0.813322E+11 | 0.210178E+11 | 429.75 | 0.712711E+11 | 0.100611E+11 | 0.00 | 1.00 | 01-OCT-10:12 | 0.00 | 01-OCT-00:10 | 108183.96 | 03-OCT-13:30 | 102736.34 | 02-OCT-14:40 | 24786.39 | 04-OCT-05:02 | 32674.20 | 02-OCT-13:30 | 0.00 |
November | 0.511033E+11 | 0.127110E+11 | 401.38 | 0.463167E+11 | 0.478666E+10 | 0.00 | 1.00 | 01-NOV-12:10 | 0.00 | 01-NOV-00:10 | 71956.27 | 09-NOV-14:10 | 71956.27 | 09-NOV-14:10 | 10921.60 | 06-NOV-17:30 | 18342.05 | 08-NOV-14:30 | 0.00 |
December | 0.301334E+11 | 0.765556E+10 | 385.32 | 0.260626E+11 | 0.407071E+10 | 0.00 | 0.88 | 03-DEC-13:02 | 0.00 | 01-DEC-00:10 | 47777.18 | 03-DEC-13:02 | 47777.18 | 03-DEC-13:02 | 7587.10 | 29-DEC-19:53 | 11039.83 | 03-DEC-13:02 | 0.00 |
Annual Sum or Average | 0.107355E+13 | 0.289085E+12 | 5286.08 | 0.866164E+12 | 0.207385E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.270765E+11 | 0.693822E+10 | 364.40 | 0.231206E+11 | 0.395584E+10 | 0.00 | 0.74 | 0.00 | 38626.64 | 38626.64 | 7587.10 | 9222.55 | 0.00 | ||||||
Maximum of Months | 0.148176E+12 | 0.426337E+11 | 511.06 | 0.118762E+12 | 0.476289E+11 | 0.00 | 1.00 | 0.00 | 188721.57 | 163473.47 | 91043.22 | 57779.97 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.50 | 0.00 | 232.50 | 193.79 | 1673.42 | 19.67 | 0.00 | 0.00 |
February | 275.70 | 0.00 | 275.70 | 423.64 | 1300.93 | 0.00 | 0.00 | 0.00 |
March | 332.22 | 0.00 | 332.22 | 885.62 | 763.34 | 0.00 | 0.00 | 0.00 |
April | 361.34 | 2.07 | 359.27 | 1725.22 | 274.52 | 0.00 | 0.00 | 0.00 |
May | 404.51 | 16.32 | 388.19 | 2489.09 | 50.95 | 0.00 | 0.00 | 0.00 |
June | 419.80 | 21.68 | 398.12 | 2713.15 | 47.94 | 0.00 | 0.00 | 0.00 |
July | 410.25 | 8.96 | 401.29 | 2357.50 | 8.32 | 0.00 | 0.00 | 0.00 |
August | 374.93 | 1.78 | 373.15 | 1946.63 | 26.65 | 0.00 | 0.00 | 0.00 |
September | 333.55 | 0.05 | 333.51 | 1453.96 | 107.99 | 0.00 | 0.00 | 0.00 |
October | 288.95 | 0.00 | 288.95 | 1069.19 | 572.56 | 0.00 | 0.00 | 0.00 |
November | 244.74 | 0.00 | 244.74 | 557.19 | 1111.70 | 0.00 | 0.00 | 0.00 |
December | 226.81 | 0.00 | 226.81 | 248.79 | 1617.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 325.69 | 4.25 | 321.44 | 1343.17 | 626.77 | 19.67 | 0.00 | 0.00 |
Minimum of Months | 226.81 | 0.00 | 226.81 | 193.79 | 8.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 419.80 | 21.68 | 401.29 | 2713.15 | 1673.42 | 19.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 333.34 | 134.58 | 198.76 | 510.60 | 1000.55 | 19.83 | 0.00 | 0.00 |
February | 403.95 | 167.10 | 236.84 | 814.90 | 800.36 | 0.00 | 0.00 | 0.00 |
March | 491.51 | 202.54 | 288.97 | 1336.80 | 482.84 | 0.00 | 0.00 | 0.00 |
April | 584.19 | 271.71 | 312.48 | 2167.22 | 183.79 | 0.00 | 0.00 | 0.00 |
May | 576.27 | 255.50 | 320.77 | 2571.86 | 33.30 | 0.00 | 0.00 | 0.00 |
June | 471.16 | 157.78 | 313.38 | 2396.11 | 31.54 | 0.00 | 0.00 | 0.00 |
July | 394.40 | 83.47 | 310.93 | 1945.73 | 4.84 | 0.00 | 0.00 | 0.00 |
August | 354.97 | 61.61 | 293.35 | 1623.03 | 17.51 | 0.00 | 0.00 | 0.00 |
September | 379.14 | 105.51 | 273.63 | 1438.23 | 71.01 | 0.00 | 0.00 | 0.00 |
October | 416.81 | 169.40 | 247.41 | 1370.76 | 372.33 | 0.00 | 0.00 | 0.00 |
November | 371.37 | 161.31 | 210.05 | 921.97 | 698.80 | 0.00 | 0.00 | 0.00 |
December | 323.27 | 129.51 | 193.76 | 570.21 | 993.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 424.91 | 158.09 | 266.82 | 1474.85 | 389.12 | 19.83 | 0.00 | 0.00 |
Minimum of Months | 323.27 | 61.61 | 193.76 | 510.60 | 4.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 584.19 | 271.71 | 320.77 | 2571.86 | 1000.55 | 19.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1042.23 | 627.34 | 414.89 | 2218.46 | 1563.86 | 21.17 | 0.00 | 0.00 |
February | 1005.27 | 558.30 | 446.98 | 2379.97 | 1285.03 | 0.00 | 0.00 | 0.00 |
March | 889.08 | 409.13 | 479.95 | 2573.77 | 782.55 | 0.00 | 0.00 | 0.00 |
April | 649.30 | 215.89 | 433.41 | 2704.89 | 290.21 | 0.00 | 0.00 | 0.00 |
May | 452.96 | 50.87 | 402.09 | 2655.64 | 49.28 | 0.00 | 0.00 | 0.00 |
June | 402.91 | 12.48 | 390.43 | 2656.82 | 47.52 | 0.00 | 0.00 | 0.00 |
July | 418.14 | 9.51 | 408.63 | 2390.94 | 7.44 | 0.00 | 0.00 | 0.00 |
August | 447.55 | 31.51 | 416.04 | 2195.43 | 27.41 | 0.00 | 0.00 | 0.00 |
September | 607.63 | 171.35 | 436.27 | 2322.70 | 115.89 | 0.00 | 0.00 | 0.00 |
October | 1024.28 | 576.64 | 447.64 | 3322.58 | 608.40 | 0.00 | 0.00 | 0.00 |
November | 1248.16 | 818.92 | 429.24 | 3403.24 | 1139.27 | 0.00 | 0.00 | 0.00 |
December | 1109.38 | 687.48 | 421.90 | 2516.62 | 1551.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 773.37 | 346.19 | 427.18 | 2611.91 | 619.37 | 21.17 | 0.00 | 0.00 |
Minimum of Months | 402.91 | 9.51 | 390.43 | 2195.43 | 7.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1248.16 | 818.92 | 479.95 | 3403.24 | 1563.86 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 326.50 | 128.08 | 198.43 | 577.68 | 1103.81 | 24.83 | 0.00 | 0.00 |
February | 372.57 | 138.00 | 234.57 | 808.90 | 872.47 | 0.00 | 0.00 | 0.00 |
March | 481.11 | 191.97 | 289.14 | 1347.96 | 518.36 | 0.00 | 0.00 | 0.00 |
April | 584.22 | 273.30 | 310.92 | 2183.34 | 192.81 | 0.00 | 0.00 | 0.00 |
May | 554.91 | 235.67 | 319.24 | 2534.83 | 36.23 | 0.00 | 0.00 | 0.00 |
June | 522.20 | 203.73 | 318.47 | 2563.95 | 32.65 | 0.00 | 0.00 | 0.00 |
July | 386.79 | 75.53 | 311.26 | 1928.63 | 5.41 | 0.00 | 0.00 | 0.00 |
August | 354.72 | 62.91 | 291.81 | 1633.71 | 17.53 | 0.00 | 0.00 | 0.00 |
September | 389.61 | 114.02 | 275.58 | 1488.16 | 74.23 | 0.00 | 0.00 | 0.00 |
October | 408.03 | 163.67 | 244.36 | 1383.16 | 390.81 | 0.00 | 0.00 | 0.00 |
November | 370.64 | 159.86 | 210.78 | 1001.63 | 751.35 | 0.00 | 0.00 | 0.00 |
December | 316.53 | 122.06 | 194.47 | 607.45 | 1063.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.24 | 155.53 | 266.71 | 1507.34 | 419.62 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 316.53 | 62.91 | 194.47 | 577.68 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 584.22 | 273.30 | 319.24 | 2563.95 | 1103.81 | 24.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.50 | 0.00 | 77.50 | 61.40 | 628.22 | 23.67 | 0.00 | 0.00 |
February | 91.90 | 0.00 | 91.90 | 145.29 | 470.12 | 0.00 | 0.00 | 0.00 |
March | 110.74 | 0.00 | 110.74 | 307.18 | 265.14 | 0.00 | 0.00 | 0.00 |
April | 120.44 | 0.69 | 119.75 | 589.41 | 89.43 | 0.00 | 0.00 | 0.00 |
May | 134.83 | 5.44 | 129.39 | 839.36 | 15.04 | 0.00 | 0.00 | 0.00 |
June | 139.93 | 7.23 | 132.70 | 906.77 | 16.07 | 0.00 | 0.00 | 0.00 |
July | 136.75 | 2.99 | 133.76 | 780.34 | 3.98 | 0.00 | 0.00 | 0.00 |
August | 124.97 | 0.59 | 124.38 | 641.00 | 12.79 | 0.00 | 0.00 | 0.00 |
September | 111.18 | 0.02 | 111.17 | 473.69 | 48.07 | 0.00 | 0.00 | 0.00 |
October | 96.31 | 0.00 | 96.31 | 347.54 | 225.66 | 0.00 | 0.00 | 0.00 |
November | 81.58 | 0.00 | 81.58 | 174.17 | 434.83 | 0.00 | 0.00 | 0.00 |
December | 75.60 | 0.00 | 75.60 | 72.90 | 616.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.56 | 1.42 | 107.14 | 446.39 | 234.55 | 23.67 | 0.00 | 0.00 |
Minimum of Months | 75.60 | 0.00 | 75.60 | 61.40 | 3.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.93 | 7.23 | 133.76 | 906.77 | 628.22 | 23.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.50 | 0.00 | 77.50 | 61.40 | 628.26 | 23.67 | 0.00 | 0.00 |
February | 91.90 | 0.00 | 91.90 | 145.30 | 470.15 | 0.00 | 0.00 | 0.00 |
March | 110.74 | 0.00 | 110.74 | 307.20 | 265.16 | 0.00 | 0.00 | 0.00 |
April | 120.45 | 0.69 | 119.76 | 589.45 | 89.43 | 0.00 | 0.00 | 0.00 |
May | 134.84 | 5.44 | 129.40 | 839.42 | 15.04 | 0.00 | 0.00 | 0.00 |
June | 139.94 | 7.23 | 132.71 | 906.83 | 16.07 | 0.00 | 0.00 | 0.00 |
July | 136.75 | 2.99 | 133.76 | 780.38 | 3.98 | 0.00 | 0.00 | 0.00 |
August | 124.98 | 0.59 | 124.39 | 641.04 | 12.79 | 0.00 | 0.00 | 0.00 |
September | 111.19 | 0.02 | 111.17 | 473.71 | 48.07 | 0.00 | 0.00 | 0.00 |
October | 96.32 | 0.00 | 96.32 | 347.56 | 225.67 | 0.00 | 0.00 | 0.00 |
November | 81.58 | 0.00 | 81.58 | 174.18 | 434.86 | 0.00 | 0.00 | 0.00 |
December | 75.60 | 0.00 | 75.60 | 72.90 | 616.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.57 | 1.42 | 107.15 | 446.41 | 234.56 | 23.67 | 0.00 | 0.00 |
Minimum of Months | 75.60 | 0.00 | 75.60 | 61.40 | 3.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.94 | 7.23 | 133.76 | 906.83 | 628.26 | 23.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.50 | 0.00 | 77.50 | 61.40 | 628.26 | 23.67 | 0.00 | 0.00 |
February | 91.90 | 0.00 | 91.90 | 145.30 | 470.15 | 0.00 | 0.00 | 0.00 |
March | 110.74 | 0.00 | 110.74 | 307.20 | 265.16 | 0.00 | 0.00 | 0.00 |
April | 120.45 | 0.69 | 119.76 | 589.45 | 89.43 | 0.00 | 0.00 | 0.00 |
May | 134.84 | 5.44 | 129.40 | 839.42 | 15.04 | 0.00 | 0.00 | 0.00 |
June | 139.94 | 7.23 | 132.71 | 906.83 | 16.07 | 0.00 | 0.00 | 0.00 |
July | 136.75 | 2.99 | 133.76 | 780.38 | 3.98 | 0.00 | 0.00 | 0.00 |
August | 124.98 | 0.59 | 124.39 | 641.04 | 12.79 | 0.00 | 0.00 | 0.00 |
September | 111.19 | 0.02 | 111.17 | 473.71 | 48.07 | 0.00 | 0.00 | 0.00 |
October | 96.32 | 0.00 | 96.32 | 347.56 | 225.67 | 0.00 | 0.00 | 0.00 |
November | 81.58 | 0.00 | 81.58 | 174.18 | 434.86 | 0.00 | 0.00 | 0.00 |
December | 75.60 | 0.00 | 75.60 | 72.90 | 616.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.57 | 1.42 | 107.15 | 446.41 | 234.56 | 23.67 | 0.00 | 0.00 |
Minimum of Months | 75.60 | 0.00 | 75.60 | 61.40 | 3.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.94 | 7.23 | 133.76 | 906.83 | 628.26 | 23.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 320.67 | 129.46 | 191.21 | 466.58 | 1097.10 | 22.33 | 0.00 | 0.00 |
February | 388.59 | 160.75 | 227.84 | 786.75 | 847.74 | 0.00 | 0.00 | 0.00 |
March | 472.83 | 194.85 | 277.98 | 1311.98 | 494.37 | 0.00 | 0.00 | 0.00 |
April | 561.99 | 261.39 | 300.60 | 2120.21 | 180.67 | 0.00 | 0.00 | 0.00 |
May | 554.37 | 245.79 | 308.57 | 2501.27 | 31.12 | 0.00 | 0.00 | 0.00 |
June | 453.25 | 151.79 | 301.46 | 2317.56 | 31.65 | 0.00 | 0.00 | 0.00 |
July | 379.41 | 80.30 | 299.11 | 1865.36 | 7.00 | 0.00 | 0.00 | 0.00 |
August | 341.48 | 59.27 | 282.21 | 1548.81 | 24.54 | 0.00 | 0.00 | 0.00 |
September | 364.73 | 101.50 | 263.23 | 1367.38 | 91.87 | 0.00 | 0.00 | 0.00 |
October | 400.97 | 162.97 | 238.01 | 1306.24 | 426.73 | 0.00 | 0.00 | 0.00 |
November | 357.25 | 155.18 | 202.07 | 861.13 | 793.67 | 0.00 | 0.00 | 0.00 |
December | 310.98 | 124.59 | 186.39 | 511.27 | 1101.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 408.77 | 152.08 | 256.68 | 1416.09 | 425.56 | 22.33 | 0.00 | 0.00 |
Minimum of Months | 310.98 | 59.27 | 186.39 | 466.58 | 7.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 561.99 | 261.39 | 308.57 | 2501.27 | 1101.66 | 22.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.68 | 5.12 | 7.56 | 18.45 | 43.38 | 22.33 | 0.00 | 0.00 |
February | 15.36 | 6.36 | 9.01 | 31.11 | 33.52 | 0.00 | 0.00 | 0.00 |
March | 18.70 | 7.70 | 10.99 | 51.87 | 19.55 | 0.00 | 0.00 | 0.00 |
April | 22.22 | 10.34 | 11.89 | 83.83 | 7.14 | 0.00 | 0.00 | 0.00 |
May | 21.92 | 9.72 | 12.20 | 98.90 | 1.23 | 0.00 | 0.00 | 0.00 |
June | 17.92 | 6.00 | 11.92 | 91.63 | 1.25 | 0.00 | 0.00 | 0.00 |
July | 15.00 | 3.17 | 11.83 | 73.75 | 0.28 | 0.00 | 0.00 | 0.00 |
August | 13.50 | 2.34 | 11.16 | 61.24 | 0.97 | 0.00 | 0.00 | 0.00 |
September | 14.42 | 4.01 | 10.41 | 54.07 | 3.63 | 0.00 | 0.00 | 0.00 |
October | 15.85 | 6.44 | 9.41 | 51.65 | 16.87 | 0.00 | 0.00 | 0.00 |
November | 14.13 | 6.14 | 7.99 | 34.05 | 31.38 | 0.00 | 0.00 | 0.00 |
December | 12.30 | 4.93 | 7.37 | 20.21 | 43.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.16 | 6.01 | 10.15 | 55.99 | 16.83 | 22.33 | 0.00 | 0.00 |
Minimum of Months | 12.30 | 2.34 | 7.37 | 18.45 | 0.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.22 | 10.34 | 12.20 | 98.90 | 43.56 | 22.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 347.42 | 209.12 | 138.30 | 740.47 | 609.00 | 21.67 | 0.00 | 0.00 |
February | 335.10 | 186.10 | 149.00 | 802.78 | 484.59 | 0.00 | 0.00 | 0.00 |
March | 296.37 | 136.38 | 159.99 | 873.43 | 284.86 | 0.00 | 0.00 | 0.00 |
April | 216.44 | 71.97 | 144.47 | 913.15 | 100.00 | 0.00 | 0.00 | 0.00 |
May | 150.99 | 16.96 | 134.03 | 884.51 | 15.61 | 0.00 | 0.00 | 0.00 |
June | 134.31 | 4.16 | 130.15 | 877.92 | 16.23 | 0.00 | 0.00 | 0.00 |
July | 139.38 | 3.17 | 136.21 | 786.00 | 3.75 | 0.00 | 0.00 | 0.00 |
August | 149.19 | 10.50 | 138.68 | 719.73 | 13.55 | 0.00 | 0.00 | 0.00 |
September | 202.55 | 57.12 | 145.43 | 763.71 | 54.64 | 0.00 | 0.00 | 0.00 |
October | 341.44 | 192.22 | 149.22 | 1103.06 | 248.24 | 0.00 | 0.00 | 0.00 |
November | 416.06 | 272.98 | 143.08 | 1131.80 | 461.50 | 0.00 | 0.00 | 0.00 |
December | 369.80 | 229.17 | 140.64 | 830.43 | 611.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.80 | 115.40 | 142.40 | 868.88 | 240.84 | 21.67 | 0.00 | 0.00 |
Minimum of Months | 134.31 | 3.17 | 130.15 | 719.73 | 3.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.06 | 272.98 | 159.99 | 1131.80 | 611.01 | 21.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 347.42 | 209.12 | 138.30 | 740.47 | 609.00 | 21.67 | 0.00 | 0.00 |
February | 335.10 | 186.10 | 149.00 | 802.78 | 484.59 | 0.00 | 0.00 | 0.00 |
March | 296.37 | 136.38 | 159.99 | 873.43 | 284.86 | 0.00 | 0.00 | 0.00 |
April | 216.44 | 71.97 | 144.47 | 913.15 | 100.00 | 0.00 | 0.00 | 0.00 |
May | 150.99 | 16.96 | 134.03 | 884.51 | 15.61 | 0.00 | 0.00 | 0.00 |
June | 134.31 | 4.16 | 130.15 | 877.92 | 16.23 | 0.00 | 0.00 | 0.00 |
July | 139.38 | 3.17 | 136.21 | 786.00 | 3.75 | 0.00 | 0.00 | 0.00 |
August | 149.19 | 10.50 | 138.68 | 719.73 | 13.55 | 0.00 | 0.00 | 0.00 |
September | 202.55 | 57.12 | 145.43 | 763.71 | 54.64 | 0.00 | 0.00 | 0.00 |
October | 341.44 | 192.22 | 149.22 | 1103.06 | 248.24 | 0.00 | 0.00 | 0.00 |
November | 416.06 | 272.98 | 143.08 | 1131.80 | 461.50 | 0.00 | 0.00 | 0.00 |
December | 369.80 | 229.17 | 140.64 | 830.43 | 611.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.80 | 115.40 | 142.40 | 868.88 | 240.84 | 21.67 | 0.00 | 0.00 |
Minimum of Months | 134.31 | 3.17 | 130.15 | 719.73 | 3.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.06 | 272.98 | 159.99 | 1131.80 | 611.01 | 21.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 347.40 | 209.11 | 138.29 | 740.43 | 608.96 | 21.67 | 0.00 | 0.00 |
February | 335.08 | 186.09 | 148.99 | 802.73 | 484.55 | 0.00 | 0.00 | 0.00 |
March | 296.35 | 136.37 | 159.98 | 873.38 | 284.84 | 0.00 | 0.00 | 0.00 |
April | 216.43 | 71.96 | 144.46 | 913.09 | 99.99 | 0.00 | 0.00 | 0.00 |
May | 150.98 | 16.96 | 134.02 | 884.46 | 15.61 | 0.00 | 0.00 | 0.00 |
June | 134.30 | 4.16 | 130.14 | 877.86 | 16.23 | 0.00 | 0.00 | 0.00 |
July | 139.37 | 3.17 | 136.20 | 785.95 | 3.75 | 0.00 | 0.00 | 0.00 |
August | 149.18 | 10.50 | 138.67 | 719.68 | 13.55 | 0.00 | 0.00 | 0.00 |
September | 202.53 | 57.12 | 145.42 | 763.66 | 54.64 | 0.00 | 0.00 | 0.00 |
October | 341.41 | 192.21 | 149.21 | 1102.99 | 248.22 | 0.00 | 0.00 | 0.00 |
November | 416.04 | 272.96 | 143.07 | 1131.73 | 461.47 | 0.00 | 0.00 | 0.00 |
December | 369.78 | 229.15 | 140.63 | 830.38 | 610.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.78 | 115.39 | 142.39 | 868.83 | 240.82 | 21.67 | 0.00 | 0.00 |
Minimum of Months | 134.30 | 3.17 | 130.14 | 719.68 | 3.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 416.04 | 272.96 | 159.98 | 1131.73 | 610.97 | 21.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 314.10 | 123.21 | 190.88 | 559.80 | 1212.82 | 24.33 | 0.00 | 0.00 |
February | 358.41 | 132.75 | 225.65 | 797.59 | 924.98 | 0.00 | 0.00 | 0.00 |
March | 462.83 | 184.67 | 278.15 | 1331.87 | 534.08 | 0.00 | 0.00 | 0.00 |
April | 562.02 | 262.92 | 299.10 | 2136.78 | 193.01 | 0.00 | 0.00 | 0.00 |
May | 533.82 | 226.71 | 307.11 | 2454.56 | 35.22 | 0.00 | 0.00 | 0.00 |
June | 502.35 | 195.99 | 306.37 | 2469.15 | 33.79 | 0.00 | 0.00 | 0.00 |
July | 372.09 | 72.66 | 299.43 | 1840.79 | 7.82 | 0.00 | 0.00 | 0.00 |
August | 341.24 | 60.52 | 280.72 | 1552.37 | 25.01 | 0.00 | 0.00 | 0.00 |
September | 374.80 | 109.69 | 265.11 | 1410.99 | 97.69 | 0.00 | 0.00 | 0.00 |
October | 392.52 | 157.45 | 235.07 | 1319.24 | 454.22 | 0.00 | 0.00 | 0.00 |
November | 356.55 | 153.79 | 202.77 | 950.54 | 857.21 | 0.00 | 0.00 | 0.00 |
December | 304.50 | 117.42 | 187.08 | 571.08 | 1181.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 406.19 | 149.62 | 256.58 | 1451.72 | 461.17 | 24.33 | 0.00 | 0.00 |
Minimum of Months | 304.50 | 60.52 | 187.08 | 559.80 | 7.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 562.02 | 262.92 | 307.11 | 2469.15 | 1212.82 | 24.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.42 | 4.87 | 7.55 | 22.13 | 47.95 | 24.33 | 0.00 | 0.00 |
February | 14.17 | 5.25 | 8.92 | 31.54 | 36.57 | 0.00 | 0.00 | 0.00 |
March | 18.30 | 7.30 | 11.00 | 52.66 | 21.12 | 0.00 | 0.00 | 0.00 |
April | 22.22 | 10.40 | 11.83 | 84.49 | 7.63 | 0.00 | 0.00 | 0.00 |
May | 21.11 | 8.96 | 12.14 | 97.05 | 1.39 | 0.00 | 0.00 | 0.00 |
June | 19.86 | 7.75 | 12.11 | 97.63 | 1.34 | 0.00 | 0.00 | 0.00 |
July | 14.71 | 2.87 | 11.84 | 72.78 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 13.49 | 2.39 | 11.10 | 61.38 | 0.99 | 0.00 | 0.00 | 0.00 |
September | 14.82 | 4.34 | 10.48 | 55.79 | 3.86 | 0.00 | 0.00 | 0.00 |
October | 15.52 | 6.23 | 9.29 | 52.16 | 17.96 | 0.00 | 0.00 | 0.00 |
November | 14.10 | 6.08 | 8.02 | 37.58 | 33.89 | 0.00 | 0.00 | 0.00 |
December | 12.04 | 4.64 | 7.40 | 22.58 | 46.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.06 | 5.92 | 10.14 | 57.40 | 18.23 | 24.33 | 0.00 | 0.00 |
Minimum of Months | 12.04 | 2.39 | 7.40 | 22.13 | 0.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.22 | 10.40 | 12.14 | 97.63 | 47.95 | 24.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.50 | 0.00 | 232.50 | 177.62 | 1841.30 | 22.33 | 0.00 | 0.00 |
February | 275.70 | 0.00 | 275.70 | 409.05 | 1427.08 | 0.00 | 0.00 | 0.00 |
March | 332.22 | 0.00 | 332.22 | 881.47 | 835.80 | 0.00 | 0.00 | 0.00 |
April | 361.34 | 2.07 | 359.27 | 1738.28 | 297.17 | 0.00 | 0.00 | 0.00 |
May | 404.51 | 16.32 | 388.19 | 2507.07 | 52.91 | 0.00 | 0.00 | 0.00 |
June | 419.80 | 21.68 | 398.12 | 2732.23 | 48.67 | 0.00 | 0.00 | 0.00 |
July | 410.25 | 8.96 | 401.29 | 2373.45 | 9.21 | 0.00 | 0.00 | 0.00 |
August | 374.93 | 1.78 | 373.15 | 1958.24 | 29.31 | 0.00 | 0.00 | 0.00 |
September | 333.55 | 0.05 | 333.51 | 1454.39 | 122.76 | 0.00 | 0.00 | 0.00 |
October | 288.95 | 0.00 | 288.95 | 1062.92 | 633.79 | 0.00 | 0.00 | 0.00 |
November | 244.74 | 0.00 | 244.74 | 533.83 | 1239.13 | 0.00 | 0.00 | 0.00 |
December | 226.81 | 0.00 | 226.81 | 223.67 | 1782.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 325.69 | 4.25 | 321.44 | 1342.28 | 690.22 | 22.33 | 0.00 | 0.00 |
Minimum of Months | 226.81 | 0.00 | 226.81 | 177.62 | 9.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 419.80 | 21.68 | 401.29 | 2732.23 | 1841.30 | 22.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 333.34 | 134.58 | 198.76 | 485.14 | 1094.03 | 21.50 | 0.00 | 0.00 |
February | 403.95 | 167.10 | 236.84 | 798.73 | 866.77 | 0.00 | 0.00 | 0.00 |
March | 491.51 | 202.54 | 288.97 | 1331.89 | 519.20 | 0.00 | 0.00 | 0.00 |
April | 584.19 | 271.71 | 312.48 | 2175.65 | 196.11 | 0.00 | 0.00 | 0.00 |
May | 576.27 | 255.50 | 320.77 | 2585.00 | 34.24 | 0.00 | 0.00 | 0.00 |
June | 471.16 | 157.78 | 313.38 | 2408.17 | 31.86 | 0.00 | 0.00 | 0.00 |
July | 394.40 | 83.47 | 310.93 | 1955.91 | 5.32 | 0.00 | 0.00 | 0.00 |
August | 354.97 | 61.61 | 293.35 | 1627.57 | 18.88 | 0.00 | 0.00 | 0.00 |
September | 379.14 | 105.51 | 273.63 | 1437.11 | 78.87 | 0.00 | 0.00 | 0.00 |
October | 416.81 | 169.40 | 247.41 | 1364.02 | 405.47 | 0.00 | 0.00 | 0.00 |
November | 371.37 | 161.31 | 210.05 | 903.08 | 765.99 | 0.00 | 0.00 | 0.00 |
December | 323.27 | 129.51 | 193.76 | 540.97 | 1085.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 424.91 | 158.09 | 266.82 | 1470.38 | 423.30 | 21.50 | 0.00 | 0.00 |
Minimum of Months | 323.27 | 61.61 | 193.76 | 485.14 | 5.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 584.19 | 271.71 | 320.77 | 2585.00 | 1094.03 | 21.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1042.23 | 627.34 | 414.89 | 2187.84 | 1720.44 | 20.83 | 0.00 | 0.00 |
February | 1005.27 | 558.30 | 446.98 | 2366.37 | 1401.58 | 0.00 | 0.00 | 0.00 |
March | 889.08 | 409.13 | 479.95 | 2577.68 | 849.94 | 0.00 | 0.00 | 0.00 |
April | 649.30 | 215.89 | 433.41 | 2724.23 | 313.25 | 0.00 | 0.00 | 0.00 |
May | 452.96 | 50.87 | 402.09 | 2674.21 | 51.48 | 0.00 | 0.00 | 0.00 |
June | 402.91 | 12.48 | 390.43 | 2676.05 | 48.15 | 0.00 | 0.00 | 0.00 |
July | 418.14 | 9.51 | 408.63 | 2407.27 | 8.29 | 0.00 | 0.00 | 0.00 |
August | 447.55 | 31.51 | 416.04 | 2207.67 | 29.90 | 0.00 | 0.00 | 0.00 |
September | 607.63 | 171.35 | 436.27 | 2328.79 | 130.45 | 0.00 | 0.00 | 0.00 |
October | 1024.28 | 576.64 | 447.64 | 3326.48 | 666.18 | 0.00 | 0.00 | 0.00 |
November | 1248.16 | 818.92 | 429.24 | 3389.63 | 1255.11 | 0.00 | 0.00 | 0.00 |
December | 1109.38 | 687.48 | 421.90 | 2479.89 | 1702.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 773.37 | 346.19 | 427.18 | 2612.36 | 678.16 | 20.83 | 0.00 | 0.00 |
Minimum of Months | 402.91 | 9.51 | 390.43 | 2187.84 | 8.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1248.16 | 818.92 | 479.95 | 3389.63 | 1720.44 | 20.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 326.50 | 128.08 | 198.43 | 570.41 | 1213.10 | 23.67 | 0.00 | 0.00 |
February | 372.57 | 138.00 | 234.57 | 805.96 | 951.57 | 0.00 | 0.00 | 0.00 |
March | 481.11 | 191.97 | 289.14 | 1351.29 | 564.13 | 0.00 | 0.00 | 0.00 |
April | 584.22 | 273.30 | 310.92 | 2196.87 | 208.34 | 0.00 | 0.00 | 0.00 |
May | 554.91 | 235.67 | 319.24 | 2549.10 | 37.98 | 0.00 | 0.00 | 0.00 |
June | 522.20 | 203.73 | 318.47 | 2577.60 | 33.52 | 0.00 | 0.00 | 0.00 |
July | 386.79 | 75.53 | 311.26 | 1937.95 | 5.97 | 0.00 | 0.00 | 0.00 |
August | 354.72 | 62.91 | 291.81 | 1639.90 | 19.08 | 0.00 | 0.00 | 0.00 |
September | 389.61 | 114.02 | 275.58 | 1488.19 | 83.27 | 0.00 | 0.00 | 0.00 |
October | 408.03 | 163.67 | 244.36 | 1381.80 | 430.62 | 0.00 | 0.00 | 0.00 |
November | 370.64 | 159.86 | 210.78 | 992.57 | 830.73 | 0.00 | 0.00 | 0.00 |
December | 316.53 | 122.06 | 194.47 | 593.38 | 1169.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.24 | 155.53 | 266.71 | 1509.49 | 460.23 | 23.67 | 0.00 | 0.00 |
Minimum of Months | 316.53 | 62.91 | 194.47 | 570.41 | 5.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 584.22 | 273.30 | 319.24 | 2577.60 | 1213.10 | 23.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.622722E+09 | 0.00 | 0.622722E+09 | 0.519044E+09 | 0.448209E+10 |
February | 0.666980E+09 | 0.00 | 0.666980E+09 | 0.102487E+10 | 0.314722E+10 |
March | 0.889827E+09 | 0.00 | 0.889827E+09 | 0.237203E+10 | 0.204453E+10 |
April | 0.936597E+09 | 5377957.18 | 0.931219E+09 | 0.447177E+10 | 0.711546E+09 |
May | 0.108344E+10 | 43714162.19 | 0.103972E+10 | 0.666677E+10 | 0.136469E+09 |
June | 0.108813E+10 | 56191051.23 | 0.103194E+10 | 0.703249E+10 | 0.124270E+09 |
July | 0.109881E+10 | 24006596.20 | 0.107481E+10 | 0.631433E+10 | 22294563.59 |
August | 0.100422E+10 | 4760961.04 | 0.999456E+09 | 0.521386E+10 | 71384822.97 |
September | 0.864572E+09 | 121533.02 | 0.864451E+09 | 0.376867E+10 | 0.279901E+09 |
October | 0.773912E+09 | 0.00 | 0.773912E+09 | 0.286371E+10 | 0.153355E+10 |
November | 0.634366E+09 | 0.00 | 0.634366E+09 | 0.144424E+10 | 0.288152E+10 |
December | 0.607476E+09 | 0.00 | 0.607476E+09 | 0.666363E+09 | 0.433112E+10 |
Annual Sum or Average | 0.102711E+11 | 0.134172E+09 | 0.101369E+11 | 0.423581E+11 | 0.197659E+11 |
Minimum of Months | 0.607476E+09 | 0.00 | 0.607476E+09 | 0.519044E+09 | 22294563.59 |
Maximum of Months | 0.109881E+10 | 56191051.23 | 0.107481E+10 | 0.703249E+10 | 0.448209E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.892808E+09 | 0.360451E+09 | 0.532357E+09 | 0.136759E+10 | 0.267988E+10 |
February | 0.977224E+09 | 0.404250E+09 | 0.572974E+09 | 0.197141E+10 | 0.193623E+10 |
March | 0.131645E+10 | 0.542486E+09 | 0.773965E+09 | 0.358047E+10 | 0.129323E+10 |
April | 0.151423E+10 | 0.704278E+09 | 0.809952E+09 | 0.561742E+10 | 0.476393E+09 |
May | 0.154348E+10 | 0.684337E+09 | 0.859142E+09 | 0.688848E+10 | 89193642.57 |
June | 0.122124E+10 | 0.408972E+09 | 0.812269E+09 | 0.621073E+10 | 81750477.52 |
July | 0.105636E+10 | 0.223561E+09 | 0.832794E+09 | 0.521144E+10 | 12974509.85 |
August | 0.950751E+09 | 0.165030E+09 | 0.785721E+09 | 0.434711E+10 | 46887096.09 |
September | 0.982723E+09 | 0.273473E+09 | 0.709250E+09 | 0.372790E+10 | 0.184064E+09 |
October | 0.111640E+10 | 0.453729E+09 | 0.662667E+09 | 0.367144E+10 | 0.997253E+09 |
November | 0.962579E+09 | 0.418127E+09 | 0.544452E+09 | 0.238974E+10 | 0.181129E+10 |
December | 0.865841E+09 | 0.346880E+09 | 0.518961E+09 | 0.152726E+10 | 0.266229E+10 |
Annual Sum or Average | 0.134001E+11 | 0.498557E+10 | 0.841451E+10 | 0.465110E+11 | 0.122714E+11 |
Minimum of Months | 0.865841E+09 | 0.165030E+09 | 0.518961E+09 | 0.136759E+10 | 12974509.85 |
Maximum of Months | 0.154348E+10 | 0.704278E+09 | 0.859142E+09 | 0.688848E+10 | 0.267988E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279150E+10 | 0.168026E+10 | 0.111123E+10 | 0.594192E+10 | 0.418864E+10 |
February | 0.243196E+10 | 0.135063E+10 | 0.108133E+10 | 0.575762E+10 | 0.310875E+10 |
March | 0.238130E+10 | 0.109580E+10 | 0.128550E+10 | 0.689360E+10 | 0.209598E+10 |
April | 0.168299E+10 | 0.559598E+09 | 0.112339E+10 | 0.701107E+10 | 0.752233E+09 |
May | 0.121320E+10 | 0.136247E+09 | 0.107695E+10 | 0.711287E+10 | 0.131987E+09 |
June | 0.104434E+10 | 32339881.00 | 0.101200E+10 | 0.688648E+10 | 0.123180E+09 |
July | 0.111995E+10 | 25481342.32 | 0.109447E+10 | 0.640390E+10 | 19919372.76 |
August | 0.119870E+10 | 84388870.00 | 0.111432E+10 | 0.588024E+10 | 73401581.44 |
September | 0.157497E+10 | 0.444149E+09 | 0.113082E+10 | 0.602043E+10 | 0.300375E+09 |
October | 0.274343E+10 | 0.154448E+10 | 0.119895E+10 | 0.889919E+10 | 0.162955E+10 |
November | 0.323523E+10 | 0.212264E+10 | 0.111259E+10 | 0.882121E+10 | 0.295299E+10 |
December | 0.297136E+10 | 0.184134E+10 | 0.113002E+10 | 0.674052E+10 | 0.415534E+10 |
Annual Sum or Average | 0.243889E+11 | 0.109174E+11 | 0.134716E+11 | 0.823691E+11 | 0.195324E+11 |
Minimum of Months | 0.104434E+10 | 25481342.32 | 0.101200E+10 | 0.575762E+10 | 19919372.76 |
Maximum of Months | 0.323523E+10 | 0.212264E+10 | 0.128550E+10 | 0.889919E+10 | 0.418864E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.874508E+09 | 0.343046E+09 | 0.531463E+09 | 0.154726E+10 | 0.295645E+10 |
February | 0.901317E+09 | 0.333846E+09 | 0.567471E+09 | 0.195689E+10 | 0.211067E+10 |
March | 0.128860E+10 | 0.514159E+09 | 0.774445E+09 | 0.361036E+10 | 0.138837E+10 |
April | 0.151430E+10 | 0.708395E+09 | 0.805908E+09 | 0.565923E+10 | 0.499769E+09 |
May | 0.148627E+10 | 0.631213E+09 | 0.855055E+09 | 0.678928E+10 | 97048224.23 |
June | 0.135354E+10 | 0.528064E+09 | 0.825475E+09 | 0.664577E+10 | 84637546.21 |
July | 0.103598E+10 | 0.202307E+09 | 0.833669E+09 | 0.516565E+10 | 14487212.63 |
August | 0.950072E+09 | 0.168495E+09 | 0.781577E+09 | 0.437572E+10 | 46940293.24 |
September | 0.100986E+10 | 0.295548E+09 | 0.714311E+09 | 0.385731E+10 | 0.192416E+09 |
October | 0.109287E+10 | 0.438379E+09 | 0.654486E+09 | 0.370466E+10 | 0.104674E+10 |
November | 0.960693E+09 | 0.414357E+09 | 0.546336E+09 | 0.259623E+10 | 0.194749E+10 |
December | 0.847791E+09 | 0.326929E+09 | 0.520862E+09 | 0.162699E+10 | 0.284804E+10 |
Annual Sum or Average | 0.133158E+11 | 0.490474E+10 | 0.841106E+10 | 0.475353E+11 | 0.132331E+11 |
Minimum of Months | 0.847791E+09 | 0.168495E+09 | 0.520862E+09 | 0.154726E+10 | 14487212.63 |
Maximum of Months | 0.151430E+10 | 0.708395E+09 | 0.855055E+09 | 0.678928E+10 | 0.295645E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207566E+09 | 0.00 | 0.207566E+09 | 0.164460E+09 | 0.168262E+10 |
February | 0.222318E+09 | 0.00 | 0.222318E+09 | 0.351486E+09 | 0.113731E+10 |
March | 0.296598E+09 | 0.00 | 0.296598E+09 | 0.822754E+09 | 0.710153E+09 |
April | 0.312187E+09 | 1792595.88 | 0.310394E+09 | 0.152776E+10 | 0.231790E+09 |
May | 0.361132E+09 | 14570928.00 | 0.346561E+09 | 0.224815E+10 | 40288025.32 |
June | 0.362696E+09 | 18729759.89 | 0.343966E+09 | 0.235036E+10 | 41642594.13 |
July | 0.366258E+09 | 8001946.45 | 0.358256E+09 | 0.209005E+10 | 10662910.68 |
August | 0.334727E+09 | 1586936.98 | 0.333140E+09 | 0.171686E+10 | 34252190.04 |
September | 0.288180E+09 | 40509.73 | 0.288140E+09 | 0.122780E+10 | 0.124587E+09 |
October | 0.257961E+09 | 0.00 | 0.257961E+09 | 0.930853E+09 | 0.604409E+09 |
November | 0.211447E+09 | 0.00 | 0.211447E+09 | 0.451439E+09 | 0.112708E+10 |
December | 0.202485E+09 | 0.00 | 0.202485E+09 | 0.195259E+09 | 0.165190E+10 |
Annual Sum or Average | 0.342356E+10 | 44722676.92 | 0.337883E+10 | 0.140772E+11 | 0.739670E+10 |
Minimum of Months | 0.202485E+09 | 0.00 | 0.202485E+09 | 0.164460E+09 | 10662910.68 |
Maximum of Months | 0.366258E+09 | 18729759.89 | 0.358256E+09 | 0.235036E+10 | 0.168262E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207576E+09 | 0.00 | 0.207576E+09 | 0.164466E+09 | 0.168273E+10 |
February | 0.222329E+09 | 0.00 | 0.222329E+09 | 0.351503E+09 | 0.113738E+10 |
March | 0.296612E+09 | 0.00 | 0.296612E+09 | 0.822799E+09 | 0.710192E+09 |
April | 0.312202E+09 | 1792665.09 | 0.310410E+09 | 0.152786E+10 | 0.231801E+09 |
May | 0.361150E+09 | 14571490.63 | 0.346578E+09 | 0.224829E+10 | 40289090.06 |
June | 0.362714E+09 | 18730483.11 | 0.343983E+09 | 0.235050E+10 | 41644679.78 |
July | 0.366275E+09 | 8002255.43 | 0.358273E+09 | 0.209017E+10 | 10663130.54 |
August | 0.334742E+09 | 1586998.26 | 0.333155E+09 | 0.171695E+10 | 34253325.73 |
September | 0.288194E+09 | 40511.29 | 0.288153E+09 | 0.122786E+10 | 0.124591E+09 |
October | 0.257974E+09 | 0.00 | 0.257974E+09 | 0.930906E+09 | 0.604441E+09 |
November | 0.211458E+09 | 0.00 | 0.211458E+09 | 0.451464E+09 | 0.112715E+10 |
December | 0.202494E+09 | 0.00 | 0.202494E+09 | 0.195268E+09 | 0.165199E+10 |
Annual Sum or Average | 0.342372E+10 | 44724403.81 | 0.337899E+10 | 0.140780E+11 | 0.739712E+10 |
Minimum of Months | 0.202494E+09 | 0.00 | 0.202494E+09 | 0.164466E+09 | 10663130.54 |
Maximum of Months | 0.366275E+09 | 18730483.11 | 0.358273E+09 | 0.235050E+10 | 0.168273E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.207576E+09 | 0.00 | 0.207576E+09 | 0.164466E+09 | 0.168273E+10 |
February | 0.222329E+09 | 0.00 | 0.222329E+09 | 0.351503E+09 | 0.113738E+10 |
March | 0.296612E+09 | 0.00 | 0.296612E+09 | 0.822799E+09 | 0.710192E+09 |
April | 0.312202E+09 | 1792665.09 | 0.310410E+09 | 0.152786E+10 | 0.231801E+09 |
May | 0.361150E+09 | 14571490.63 | 0.346578E+09 | 0.224829E+10 | 40289090.06 |
June | 0.362714E+09 | 18730483.11 | 0.343983E+09 | 0.235050E+10 | 41644679.78 |
July | 0.366275E+09 | 8002255.43 | 0.358273E+09 | 0.209017E+10 | 10663130.54 |
August | 0.334742E+09 | 1586998.26 | 0.333155E+09 | 0.171695E+10 | 34253325.73 |
September | 0.288194E+09 | 40511.29 | 0.288153E+09 | 0.122786E+10 | 0.124591E+09 |
October | 0.257974E+09 | 0.00 | 0.257974E+09 | 0.930906E+09 | 0.604441E+09 |
November | 0.211458E+09 | 0.00 | 0.211458E+09 | 0.451464E+09 | 0.112715E+10 |
December | 0.202494E+09 | 0.00 | 0.202494E+09 | 0.195268E+09 | 0.165199E+10 |
Annual Sum or Average | 0.342372E+10 | 44724403.81 | 0.337899E+10 | 0.140780E+11 | 0.739712E+10 |
Minimum of Months | 0.202494E+09 | 0.00 | 0.202494E+09 | 0.164466E+09 | 10663130.54 |
Maximum of Months | 0.366275E+09 | 18730483.11 | 0.358273E+09 | 0.235050E+10 | 0.168273E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.858880E+09 | 0.346756E+09 | 0.512124E+09 | 0.124969E+10 | 0.293847E+10 |
February | 0.940088E+09 | 0.388890E+09 | 0.551198E+09 | 0.190329E+10 | 0.205084E+10 |
March | 0.126642E+10 | 0.521874E+09 | 0.744550E+09 | 0.351402E+10 | 0.132412E+10 |
April | 0.145668E+10 | 0.677518E+09 | 0.779167E+09 | 0.549558E+10 | 0.468300E+09 |
May | 0.148482E+10 | 0.658335E+09 | 0.826487E+09 | 0.669941E+10 | 83345148.91 |
June | 0.117483E+10 | 0.393433E+09 | 0.781396E+09 | 0.600710E+10 | 82042327.90 |
July | 0.101621E+10 | 0.215066E+09 | 0.801144E+09 | 0.499619E+10 | 18747222.78 |
August | 0.914619E+09 | 0.158759E+09 | 0.755860E+09 | 0.414832E+10 | 65732286.35 |
September | 0.945377E+09 | 0.263082E+09 | 0.682295E+09 | 0.354425E+10 | 0.238116E+09 |
October | 0.107397E+10 | 0.436489E+09 | 0.637481E+09 | 0.349864E+10 | 0.114295E+10 |
November | 0.925998E+09 | 0.402239E+09 | 0.523759E+09 | 0.223206E+10 | 0.205719E+10 |
December | 0.832937E+09 | 0.333699E+09 | 0.499237E+09 | 0.136937E+10 | 0.295069E+10 |
Annual Sum or Average | 0.128908E+11 | 0.479614E+10 | 0.809470E+10 | 0.446579E+11 | 0.134205E+11 |
Minimum of Months | 0.832937E+09 | 0.158759E+09 | 0.499237E+09 | 0.124969E+10 | 18747222.78 |
Maximum of Months | 0.148482E+10 | 0.677518E+09 | 0.826487E+09 | 0.669941E+10 | 0.295069E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33959342.73 | 13710404.37 | 20248938.36 | 49411550.52 | 0.116184E+09 |
February | 37170217.21 | 15376355.68 | 21793861.53 | 75254565.31 | 81088500.30 |
March | 50073233.46 | 20634411.77 | 29438821.69 | 0.138941E+09 | 52354448.31 |
April | 57596009.93 | 26788437.06 | 30807572.87 | 0.217290E+09 | 18516152.24 |
May | 58708506.07 | 26029954.27 | 32678551.80 | 0.264889E+09 | 3295392.15 |
June | 46451666.37 | 15555971.31 | 30895695.07 | 0.237516E+09 | 3243879.78 |
July | 40180038.30 | 8503521.77 | 31676516.52 | 0.197545E+09 | 741248.31 |
August | 36163228.95 | 6277189.41 | 29886039.55 | 0.164021E+09 | 2598995.42 |
September | 37379355.27 | 10402025.88 | 26977329.40 | 0.140137E+09 | 9414882.24 |
October | 42463789.63 | 17258381.63 | 25205408.00 | 0.138333E+09 | 45191147.25 |
November | 36613139.57 | 15904178.74 | 20708960.83 | 88253617.84 | 81339441.05 |
December | 32933575.55 | 13194176.67 | 19739398.87 | 54143820.70 | 0.116668E+09 |
Annual Sum or Average | 0.509692E+09 | 0.189635E+09 | 0.320057E+09 | 0.176573E+10 | 0.530636E+09 |
Minimum of Months | 32933575.55 | 6277189.41 | 19739398.87 | 49411550.52 | 741248.31 |
Maximum of Months | 58708506.07 | 26788437.06 | 32678551.80 | 0.264889E+09 | 0.116668E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.930524E+09 | 0.560103E+09 | 0.370421E+09 | 0.198328E+10 | 0.163115E+10 |
February | 0.810674E+09 | 0.450222E+09 | 0.360452E+09 | 0.194209E+10 | 0.117231E+10 |
March | 0.793788E+09 | 0.365277E+09 | 0.428511E+09 | 0.233940E+10 | 0.762974E+09 |
April | 0.561010E+09 | 0.186538E+09 | 0.374473E+09 | 0.236688E+10 | 0.259201E+09 |
May | 0.404408E+09 | 45417059.96 | 0.358991E+09 | 0.236908E+10 | 41819642.32 |
June | 0.348120E+09 | 10780252.70 | 0.337340E+09 | 0.227557E+10 | 42080558.04 |
July | 0.373325E+09 | 8494011.13 | 0.364831E+09 | 0.210521E+10 | 10049007.12 |
August | 0.399578E+09 | 28130386.24 | 0.371448E+09 | 0.192772E+10 | 36283585.31 |
September | 0.525002E+09 | 0.148054E+09 | 0.376948E+09 | 0.197953E+10 | 0.141623E+09 |
October | 0.914501E+09 | 0.514842E+09 | 0.399659E+09 | 0.295445E+10 | 0.664885E+09 |
November | 0.107844E+10 | 0.707566E+09 | 0.370871E+09 | 0.293363E+10 | 0.119620E+10 |
December | 0.990479E+09 | 0.613798E+09 | 0.376681E+09 | 0.222423E+10 | 0.163652E+10 |
Annual Sum or Average | 0.812985E+10 | 0.363922E+10 | 0.449063E+10 | 0.274011E+11 | 0.759510E+10 |
Minimum of Months | 0.348120E+09 | 8494011.13 | 0.337340E+09 | 0.192772E+10 | 10049007.12 |
Maximum of Months | 0.107844E+10 | 0.707566E+09 | 0.428511E+09 | 0.295445E+10 | 0.163652E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.930524E+09 | 0.560103E+09 | 0.370421E+09 | 0.198328E+10 | 0.163115E+10 |
February | 0.810674E+09 | 0.450222E+09 | 0.360452E+09 | 0.194209E+10 | 0.117231E+10 |
March | 0.793788E+09 | 0.365277E+09 | 0.428511E+09 | 0.233940E+10 | 0.762974E+09 |
April | 0.561010E+09 | 0.186538E+09 | 0.374473E+09 | 0.236688E+10 | 0.259201E+09 |
May | 0.404408E+09 | 45417059.96 | 0.358991E+09 | 0.236908E+10 | 41819642.32 |
June | 0.348120E+09 | 10780252.70 | 0.337340E+09 | 0.227557E+10 | 42080558.04 |
July | 0.373325E+09 | 8494011.13 | 0.364831E+09 | 0.210521E+10 | 10049007.12 |
August | 0.399578E+09 | 28130386.24 | 0.371448E+09 | 0.192772E+10 | 36283585.31 |
September | 0.525002E+09 | 0.148054E+09 | 0.376948E+09 | 0.197953E+10 | 0.141623E+09 |
October | 0.914501E+09 | 0.514842E+09 | 0.399659E+09 | 0.295445E+10 | 0.664885E+09 |
November | 0.107844E+10 | 0.707566E+09 | 0.370871E+09 | 0.293363E+10 | 0.119620E+10 |
December | 0.990479E+09 | 0.613798E+09 | 0.376681E+09 | 0.222423E+10 | 0.163652E+10 |
Annual Sum or Average | 0.812985E+10 | 0.363922E+10 | 0.449063E+10 | 0.274011E+11 | 0.759510E+10 |
Minimum of Months | 0.348120E+09 | 8494011.13 | 0.337340E+09 | 0.192772E+10 | 10049007.12 |
Maximum of Months | 0.107844E+10 | 0.707566E+09 | 0.428511E+09 | 0.295445E+10 | 0.163652E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.930465E+09 | 0.560067E+09 | 0.370397E+09 | 0.198316E+10 | 0.163105E+10 |
February | 0.810623E+09 | 0.450194E+09 | 0.360429E+09 | 0.194197E+10 | 0.117223E+10 |
March | 0.793738E+09 | 0.365254E+09 | 0.428484E+09 | 0.233925E+10 | 0.762926E+09 |
April | 0.560975E+09 | 0.186526E+09 | 0.374449E+09 | 0.236673E+10 | 0.259184E+09 |
May | 0.404382E+09 | 45414189.86 | 0.358968E+09 | 0.236893E+10 | 41816999.55 |
June | 0.348098E+09 | 10779571.45 | 0.337319E+09 | 0.227542E+10 | 42077898.78 |
July | 0.373301E+09 | 8493474.36 | 0.364808E+09 | 0.210508E+10 | 10048372.08 |
August | 0.399553E+09 | 28128608.56 | 0.371424E+09 | 0.192760E+10 | 36281292.39 |
September | 0.524968E+09 | 0.148044E+09 | 0.376924E+09 | 0.197940E+10 | 0.141614E+09 |
October | 0.914443E+09 | 0.514809E+09 | 0.399633E+09 | 0.295426E+10 | 0.664843E+09 |
November | 0.107837E+10 | 0.707521E+09 | 0.370848E+09 | 0.293345E+10 | 0.119612E+10 |
December | 0.990417E+09 | 0.613759E+09 | 0.376658E+09 | 0.222409E+10 | 0.163642E+10 |
Annual Sum or Average | 0.812933E+10 | 0.363899E+10 | 0.449034E+10 | 0.273993E+11 | 0.759462E+10 |
Minimum of Months | 0.348098E+09 | 8493474.36 | 0.337319E+09 | 0.192760E+10 | 10048372.08 |
Maximum of Months | 0.107837E+10 | 0.707521E+09 | 0.428484E+09 | 0.295426E+10 | 0.163642E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.841273E+09 | 0.330010E+09 | 0.511263E+09 | 0.149936E+10 | 0.324843E+10 |
February | 0.867063E+09 | 0.321160E+09 | 0.545903E+09 | 0.192953E+10 | 0.223771E+10 |
March | 0.123963E+10 | 0.494622E+09 | 0.745010E+09 | 0.356729E+10 | 0.143049E+10 |
April | 0.145675E+10 | 0.681477E+09 | 0.775275E+09 | 0.553854E+10 | 0.500279E+09 |
May | 0.142978E+10 | 0.607228E+09 | 0.822554E+09 | 0.657429E+10 | 94342135.41 |
June | 0.130210E+10 | 0.507998E+09 | 0.794098E+09 | 0.640003E+10 | 87572946.28 |
July | 0.996604E+09 | 0.194619E+09 | 0.801984E+09 | 0.493037E+10 | 20943160.31 |
August | 0.913964E+09 | 0.162092E+09 | 0.751872E+09 | 0.415787E+10 | 66991357.06 |
September | 0.971480E+09 | 0.284318E+09 | 0.687162E+09 | 0.365730E+10 | 0.253208E+09 |
October | 0.105133E+10 | 0.421721E+09 | 0.629609E+09 | 0.353346E+10 | 0.121660E+10 |
November | 0.924181E+09 | 0.398612E+09 | 0.525570E+09 | 0.246379E+10 | 0.222188E+10 |
December | 0.815571E+09 | 0.314506E+09 | 0.501066E+09 | 0.152958E+10 | 0.316495E+10 |
Annual Sum or Average | 0.128097E+11 | 0.471836E+10 | 0.809137E+10 | 0.457814E+11 | 0.145434E+11 |
Minimum of Months | 0.815571E+09 | 0.162092E+09 | 0.501066E+09 | 0.149936E+10 | 20943160.31 |
Maximum of Months | 0.145675E+10 | 0.681477E+09 | 0.822554E+09 | 0.657429E+10 | 0.324843E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33263180.64 | 13048305.40 | 20214875.24 | 59283366.73 | 0.128440E+09 |
February | 34282882.91 | 12698373.44 | 21584509.47 | 76291756.99 | 88477074.90 |
March | 49013909.72 | 19556897.25 | 29457012.48 | 0.141047E+09 | 56560145.16 |
April | 57598652.55 | 26944983.53 | 30653669.02 | 0.218989E+09 | 19780585.13 |
May | 56532285.70 | 24009236.18 | 32523049.52 | 0.259941E+09 | 3730203.09 |
June | 51483740.13 | 20085801.40 | 31397938.73 | 0.253051E+09 | 3462555.45 |
July | 39404805.25 | 7695078.50 | 31709726.75 | 0.194942E+09 | 828073.70 |
August | 36137322.54 | 6408966.96 | 29728355.58 | 0.164398E+09 | 2648777.94 |
September | 38411433.87 | 11241670.67 | 27169763.20 | 0.144606E+09 | 10011631.08 |
October | 41568659.99 | 16674475.53 | 24894184.46 | 0.139710E+09 | 48103097.65 |
November | 36541303.43 | 15760748.54 | 20780554.88 | 97416018.18 | 87851141.81 |
December | 32246961.03 | 12435277.46 | 19811683.57 | 60478086.75 | 0.125139E+09 |
Annual Sum or Average | 0.506485E+09 | 0.186560E+09 | 0.319925E+09 | 0.181015E+10 | 0.575033E+09 |
Minimum of Months | 32246961.03 | 6408966.96 | 19811683.57 | 59283366.73 | 828073.70 |
Maximum of Months | 57598652.55 | 26944983.53 | 32523049.52 | 0.259941E+09 | 0.128440E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.622722E+09 | 0.00 | 0.622722E+09 | 0.475748E+09 | 0.493173E+10 |
February | 0.666980E+09 | 0.00 | 0.666980E+09 | 0.989585E+09 | 0.345238E+10 |
March | 0.889827E+09 | 0.00 | 0.889827E+09 | 0.236093E+10 | 0.223861E+10 |
April | 0.936597E+09 | 5377957.18 | 0.931219E+09 | 0.450563E+10 | 0.770269E+09 |
May | 0.108344E+10 | 43714162.19 | 0.103972E+10 | 0.671495E+10 | 0.141712E+09 |
June | 0.108813E+10 | 56191051.23 | 0.103194E+10 | 0.708194E+10 | 0.126150E+09 |
July | 0.109881E+10 | 24006596.20 | 0.107481E+10 | 0.635705E+10 | 24679557.50 |
August | 0.100422E+10 | 4760961.04 | 0.999456E+09 | 0.524495E+10 | 78496022.81 |
September | 0.864572E+09 | 121533.02 | 0.864451E+09 | 0.376978E+10 | 0.318193E+09 |
October | 0.773912E+09 | 0.00 | 0.773912E+09 | 0.284692E+10 | 0.169753E+10 |
November | 0.634366E+09 | 0.00 | 0.634366E+09 | 0.138369E+10 | 0.321184E+10 |
December | 0.607476E+09 | 0.00 | 0.607476E+09 | 0.599076E+09 | 0.477511E+10 |
Annual Sum or Average | 0.102711E+11 | 0.134172E+09 | 0.101369E+11 | 0.423303E+11 | 0.217667E+11 |
Minimum of Months | 0.607476E+09 | 0.00 | 0.607476E+09 | 0.475748E+09 | 24679557.50 |
Maximum of Months | 0.109881E+10 | 56191051.23 | 0.107481E+10 | 0.708194E+10 | 0.493173E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.892808E+09 | 0.360451E+09 | 0.532357E+09 | 0.129939E+10 | 0.293026E+10 |
February | 0.977224E+09 | 0.404250E+09 | 0.572974E+09 | 0.193229E+10 | 0.209689E+10 |
March | 0.131645E+10 | 0.542486E+09 | 0.773965E+09 | 0.356734E+10 | 0.139062E+10 |
April | 0.151423E+10 | 0.704278E+09 | 0.809952E+09 | 0.563929E+10 | 0.508323E+09 |
May | 0.154348E+10 | 0.684337E+09 | 0.859142E+09 | 0.692367E+10 | 91720466.27 |
June | 0.122124E+10 | 0.408972E+09 | 0.812269E+09 | 0.624198E+10 | 82593334.15 |
July | 0.105636E+10 | 0.223561E+09 | 0.832794E+09 | 0.523870E+10 | 14251744.33 |
August | 0.950751E+09 | 0.165030E+09 | 0.785721E+09 | 0.435929E+10 | 50579088.39 |
September | 0.982723E+09 | 0.273473E+09 | 0.709250E+09 | 0.372499E+10 | 0.204436E+09 |
October | 0.111640E+10 | 0.453729E+09 | 0.662667E+09 | 0.365339E+10 | 0.108601E+10 |
November | 0.962579E+09 | 0.418127E+09 | 0.544452E+09 | 0.234079E+10 | 0.198545E+10 |
December | 0.865841E+09 | 0.346880E+09 | 0.518961E+09 | 0.144893E+10 | 0.290796E+10 |
Annual Sum or Average | 0.134001E+11 | 0.498557E+10 | 0.841451E+10 | 0.463700E+11 | 0.133491E+11 |
Minimum of Months | 0.865841E+09 | 0.165030E+09 | 0.518961E+09 | 0.129939E+10 | 14251744.33 |
Maximum of Months | 0.154348E+10 | 0.704278E+09 | 0.859142E+09 | 0.692367E+10 | 0.293026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279150E+10 | 0.168026E+10 | 0.111123E+10 | 0.585992E+10 | 0.460803E+10 |
February | 0.243196E+10 | 0.135063E+10 | 0.108133E+10 | 0.572473E+10 | 0.339070E+10 |
March | 0.238130E+10 | 0.109580E+10 | 0.128550E+10 | 0.690405E+10 | 0.227648E+10 |
April | 0.168299E+10 | 0.559598E+09 | 0.112339E+10 | 0.706119E+10 | 0.811954E+09 |
May | 0.121320E+10 | 0.136247E+09 | 0.107695E+10 | 0.716260E+10 | 0.137879E+09 |
June | 0.104434E+10 | 32339881.00 | 0.101200E+10 | 0.693633E+10 | 0.124792E+09 |
July | 0.111995E+10 | 25481342.32 | 0.109447E+10 | 0.644764E+10 | 22194542.97 |
August | 0.119870E+10 | 84388870.00 | 0.111432E+10 | 0.591302E+10 | 80072261.61 |
September | 0.157497E+10 | 0.444149E+09 | 0.113082E+10 | 0.603622E+10 | 0.338122E+09 |
October | 0.274343E+10 | 0.154448E+10 | 0.119895E+10 | 0.890965E+10 | 0.178429E+10 |
November | 0.323523E+10 | 0.212264E+10 | 0.111259E+10 | 0.878592E+10 | 0.325325E+10 |
December | 0.297136E+10 | 0.184134E+10 | 0.113002E+10 | 0.664214E+10 | 0.455866E+10 |
Annual Sum or Average | 0.243889E+11 | 0.109174E+11 | 0.134716E+11 | 0.823834E+11 | 0.213864E+11 |
Minimum of Months | 0.104434E+10 | 25481342.32 | 0.101200E+10 | 0.572473E+10 | 22194542.97 |
Maximum of Months | 0.323523E+10 | 0.212264E+10 | 0.128550E+10 | 0.890965E+10 | 0.460803E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.874508E+09 | 0.343046E+09 | 0.531463E+09 | 0.152777E+10 | 0.324917E+10 |
February | 0.901317E+09 | 0.333846E+09 | 0.567471E+09 | 0.194979E+10 | 0.230203E+10 |
March | 0.128860E+10 | 0.514159E+09 | 0.774445E+09 | 0.361931E+10 | 0.151098E+10 |
April | 0.151430E+10 | 0.708395E+09 | 0.805908E+09 | 0.569430E+10 | 0.540015E+09 |
May | 0.148627E+10 | 0.631213E+09 | 0.855055E+09 | 0.682751E+10 | 0.101718E+09 |
June | 0.135354E+10 | 0.528064E+09 | 0.825475E+09 | 0.668113E+10 | 86878255.02 |
July | 0.103598E+10 | 0.202307E+09 | 0.833669E+09 | 0.519059E+10 | 15977285.55 |
August | 0.950072E+09 | 0.168495E+09 | 0.781577E+09 | 0.439232E+10 | 51113364.18 |
September | 0.100986E+10 | 0.295548E+09 | 0.714311E+09 | 0.385739E+10 | 0.215842E+09 |
October | 0.109287E+10 | 0.438379E+09 | 0.654486E+09 | 0.370102E+10 | 0.115337E+10 |
November | 0.960693E+09 | 0.414357E+09 | 0.546336E+09 | 0.257274E+10 | 0.215325E+10 |
December | 0.847791E+09 | 0.326929E+09 | 0.520862E+09 | 0.158930E+10 | 0.313355E+10 |
Annual Sum or Average | 0.133158E+11 | 0.490474E+10 | 0.841106E+10 | 0.476032E+11 | 0.145139E+11 |
Minimum of Months | 0.847791E+09 | 0.168495E+09 | 0.520862E+09 | 0.152777E+10 | 15977285.55 |
Maximum of Months | 0.151430E+10 | 0.708395E+09 | 0.855055E+09 | 0.682751E+10 | 0.324917E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 193.79 | 1673.42 | 232.50 | 0.00 | 232.50 | 0.00 | 0.00 |
February | 423.64 | 1300.93 | 275.70 | 0.00 | 275.70 | 0.00 | 0.00 |
March | 885.62 | 763.34 | 332.22 | 0.00 | 332.22 | 0.00 | 0.00 |
April | 1725.22 | 274.52 | 361.34 | 2.07 | 359.27 | 0.00 | 0.00 |
May | 2489.09 | 50.95 | 404.51 | 16.32 | 388.19 | 0.00 | 0.00 |
June | 2713.15 | 47.94 | 419.80 | 21.68 | 398.12 | 0.00 | 0.00 |
July | 2357.50 | 8.32 | 410.25 | 8.96 | 401.29 | 0.00 | 0.00 |
August | 1946.63 | 26.65 | 374.93 | 1.78 | 373.15 | 0.00 | 0.00 |
September | 1453.96 | 107.99 | 333.55 | 0.05 | 333.51 | 0.00 | 0.00 |
October | 1069.19 | 572.56 | 288.95 | 0.00 | 288.95 | 0.00 | 0.00 |
November | 557.19 | 1111.70 | 244.74 | 0.00 | 244.74 | 0.00 | 0.00 |
December | 248.79 | 1617.06 | 226.81 | 0.00 | 226.81 | 0.00 | 0.00 |
Annual Sum or Average | 1343.17 | 626.77 | 325.69 | 4.25 | 321.44 | 0.00 | 0.00 |
Minimum of Months | 193.79 | 8.32 | 226.81 | 0.00 | 226.81 | 0.00 | 0.00 |
Maximum of Months | 2713.15 | 1673.42 | 419.80 | 21.68 | 401.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 510.60 | 1000.55 | 333.34 | 134.58 | 198.76 | 0.00 | 0.00 |
February | 814.90 | 800.36 | 403.95 | 167.10 | 236.84 | 0.00 | 0.00 |
March | 1336.80 | 482.84 | 491.51 | 202.54 | 288.97 | 0.00 | 0.00 |
April | 2167.22 | 183.79 | 584.19 | 271.71 | 312.48 | 0.00 | 0.00 |
May | 2571.86 | 33.30 | 576.27 | 255.50 | 320.77 | 0.00 | 0.00 |
June | 2396.11 | 31.54 | 471.16 | 157.78 | 313.38 | 0.00 | 0.00 |
July | 1945.73 | 4.84 | 394.40 | 83.47 | 310.93 | 0.00 | 0.00 |
August | 1623.03 | 17.51 | 354.97 | 61.61 | 293.35 | 0.00 | 0.00 |
September | 1438.23 | 71.01 | 379.14 | 105.51 | 273.63 | 0.00 | 0.00 |
October | 1370.76 | 372.33 | 416.81 | 169.40 | 247.41 | 0.00 | 0.00 |
November | 921.97 | 698.80 | 371.37 | 161.31 | 210.05 | 0.00 | 0.00 |
December | 570.21 | 993.99 | 323.27 | 129.51 | 193.76 | 0.00 | 0.00 |
Annual Sum or Average | 1474.85 | 389.12 | 424.91 | 158.09 | 266.82 | 0.00 | 0.00 |
Minimum of Months | 510.60 | 4.84 | 323.27 | 61.61 | 193.76 | 0.00 | 0.00 |
Maximum of Months | 2571.86 | 1000.55 | 584.19 | 271.71 | 320.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2218.46 | 1563.86 | 1042.23 | 627.34 | 414.89 | 0.00 | 0.00 |
February | 2379.97 | 1285.03 | 1005.27 | 558.30 | 446.98 | 0.00 | 0.00 |
March | 2573.77 | 782.55 | 889.08 | 409.13 | 479.95 | 0.00 | 0.00 |
April | 2704.89 | 290.21 | 649.30 | 215.89 | 433.41 | 0.00 | 0.00 |
May | 2655.64 | 49.28 | 452.96 | 50.87 | 402.09 | 0.00 | 0.00 |
June | 2656.82 | 47.52 | 402.91 | 12.48 | 390.43 | 0.00 | 0.00 |
July | 2390.94 | 7.44 | 418.14 | 9.51 | 408.63 | 0.00 | 0.00 |
August | 2195.43 | 27.41 | 447.55 | 31.51 | 416.04 | 0.00 | 0.00 |
September | 2322.70 | 115.89 | 607.63 | 171.35 | 436.27 | 0.00 | 0.00 |
October | 3322.58 | 608.40 | 1024.28 | 576.64 | 447.64 | 0.00 | 0.00 |
November | 3403.24 | 1139.27 | 1248.16 | 818.92 | 429.24 | 0.00 | 0.00 |
December | 2516.62 | 1551.43 | 1109.38 | 687.48 | 421.90 | 0.00 | 0.00 |
Annual Sum or Average | 2611.91 | 619.37 | 773.37 | 346.19 | 427.18 | 0.00 | 0.00 |
Minimum of Months | 2195.43 | 7.44 | 402.91 | 9.51 | 390.43 | 0.00 | 0.00 |
Maximum of Months | 3403.24 | 1563.86 | 1248.16 | 818.92 | 479.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 577.68 | 1103.81 | 326.50 | 128.08 | 198.43 | 0.00 | 0.00 |
February | 808.90 | 872.47 | 372.57 | 138.00 | 234.57 | 0.00 | 0.00 |
March | 1347.96 | 518.36 | 481.11 | 191.97 | 289.14 | 0.00 | 0.00 |
April | 2183.34 | 192.81 | 584.22 | 273.30 | 310.92 | 0.00 | 0.00 |
May | 2534.83 | 36.23 | 554.91 | 235.67 | 319.24 | 0.00 | 0.00 |
June | 2563.95 | 32.65 | 522.20 | 203.73 | 318.47 | 0.00 | 0.00 |
July | 1928.63 | 5.41 | 386.79 | 75.53 | 311.26 | 0.00 | 0.00 |
August | 1633.71 | 17.53 | 354.72 | 62.91 | 291.81 | 0.00 | 0.00 |
September | 1488.16 | 74.23 | 389.61 | 114.02 | 275.58 | 0.00 | 0.00 |
October | 1383.16 | 390.81 | 408.03 | 163.67 | 244.36 | 0.00 | 0.00 |
November | 1001.63 | 751.35 | 370.64 | 159.86 | 210.78 | 0.00 | 0.00 |
December | 607.45 | 1063.33 | 316.53 | 122.06 | 194.47 | 0.00 | 0.00 |
Annual Sum or Average | 1507.34 | 419.62 | 422.24 | 155.53 | 266.71 | 0.00 | 0.00 |
Minimum of Months | 577.68 | 5.41 | 316.53 | 62.91 | 194.47 | 0.00 | 0.00 |
Maximum of Months | 2563.95 | 1103.81 | 584.22 | 273.30 | 319.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 184.21 | 1884.74 | 232.50 | 0.00 | 232.50 | 0.00 | 0.00 |
February | 435.88 | 1410.41 | 275.70 | 0.00 | 275.70 | 0.00 | 0.00 |
March | 921.58 | 795.45 | 332.22 | 0.00 | 332.22 | 0.00 | 0.00 |
April | 1768.32 | 268.28 | 361.34 | 2.07 | 359.26 | 0.00 | 0.00 |
May | 2518.20 | 45.13 | 404.51 | 16.32 | 388.19 | 0.00 | 0.00 |
June | 2720.43 | 48.20 | 419.80 | 21.68 | 398.12 | 0.00 | 0.00 |
July | 2341.10 | 11.94 | 410.25 | 8.96 | 401.28 | 0.00 | 0.00 |
August | 1923.08 | 38.37 | 374.93 | 1.78 | 373.15 | 0.00 | 0.00 |
September | 1421.11 | 144.20 | 333.55 | 0.05 | 333.51 | 0.00 | 0.00 |
October | 1042.66 | 677.00 | 288.94 | 0.00 | 288.94 | 0.00 | 0.00 |
November | 522.52 | 1304.54 | 244.74 | 0.00 | 244.74 | 0.00 | 0.00 |
December | 218.71 | 1850.32 | 226.80 | 0.00 | 226.80 | 0.00 | 0.00 |
Annual Sum or Average | 1339.21 | 703.67 | 325.69 | 4.25 | 321.44 | 0.00 | 0.00 |
Minimum of Months | 184.21 | 11.94 | 226.80 | 0.00 | 226.80 | 0.00 | 0.00 |
Maximum of Months | 2720.43 | 1884.74 | 419.80 | 21.68 | 401.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 485.03 | 1140.48 | 333.35 | 134.58 | 198.77 | 0.00 | 0.00 |
February | 817.85 | 881.25 | 403.96 | 167.11 | 236.85 | 0.00 | 0.00 |
March | 1363.86 | 513.92 | 491.52 | 202.55 | 288.97 | 0.00 | 0.00 |
April | 2204.04 | 187.81 | 584.21 | 271.72 | 312.49 | 0.00 | 0.00 |
May | 2600.17 | 32.35 | 576.29 | 255.51 | 320.78 | 0.00 | 0.00 |
June | 2409.19 | 32.90 | 471.17 | 157.79 | 313.38 | 0.00 | 0.00 |
July | 1939.12 | 7.28 | 394.41 | 83.47 | 310.94 | 0.00 | 0.00 |
August | 1610.04 | 25.51 | 354.98 | 61.62 | 293.36 | 0.00 | 0.00 |
September | 1421.45 | 95.50 | 379.15 | 105.51 | 273.64 | 0.00 | 0.00 |
October | 1357.89 | 443.60 | 416.83 | 169.41 | 247.42 | 0.00 | 0.00 |
November | 895.18 | 825.05 | 371.38 | 161.32 | 210.06 | 0.00 | 0.00 |
December | 531.48 | 1145.22 | 323.28 | 129.52 | 193.76 | 0.00 | 0.00 |
Annual Sum or Average | 1472.08 | 442.39 | 424.93 | 158.10 | 266.83 | 0.00 | 0.00 |
Minimum of Months | 485.03 | 7.28 | 323.28 | 61.62 | 193.76 | 0.00 | 0.00 |
Maximum of Months | 2600.17 | 1145.22 | 584.21 | 271.72 | 320.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2221.37 | 1826.97 | 1042.23 | 627.34 | 414.89 | 0.00 | 0.00 |
February | 2408.30 | 1453.72 | 1005.28 | 558.30 | 446.98 | 0.00 | 0.00 |
March | 2620.24 | 854.57 | 889.08 | 409.13 | 479.95 | 0.00 | 0.00 |
April | 2739.39 | 299.99 | 649.30 | 215.90 | 433.41 | 0.00 | 0.00 |
May | 2653.49 | 46.84 | 452.96 | 50.87 | 402.09 | 0.00 | 0.00 |
June | 2633.70 | 48.70 | 402.91 | 12.48 | 390.43 | 0.00 | 0.00 |
July | 2357.94 | 11.26 | 418.14 | 9.51 | 408.63 | 0.00 | 0.00 |
August | 2159.14 | 40.64 | 447.55 | 31.51 | 416.04 | 0.00 | 0.00 |
September | 2291.07 | 163.91 | 607.63 | 171.35 | 436.27 | 0.00 | 0.00 |
October | 3309.12 | 744.70 | 1024.28 | 576.65 | 447.64 | 0.00 | 0.00 |
November | 3395.34 | 1384.46 | 1248.16 | 818.92 | 429.24 | 0.00 | 0.00 |
December | 2491.24 | 1832.99 | 1109.38 | 687.48 | 421.90 | 0.00 | 0.00 |
Annual Sum or Average | 2606.59 | 722.50 | 773.37 | 346.19 | 427.18 | 0.00 | 0.00 |
Minimum of Months | 2159.14 | 11.26 | 402.91 | 9.51 | 390.43 | 0.00 | 0.00 |
Maximum of Months | 3395.34 | 1832.99 | 1248.16 | 818.92 | 479.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 581.93 | 1260.78 | 326.51 | 128.08 | 198.43 | 0.00 | 0.00 |
February | 829.12 | 961.55 | 372.58 | 138.00 | 234.58 | 0.00 | 0.00 |
March | 1384.53 | 555.20 | 481.13 | 191.97 | 289.15 | 0.00 | 0.00 |
April | 2221.27 | 200.64 | 584.24 | 273.31 | 310.93 | 0.00 | 0.00 |
May | 2551.61 | 36.62 | 554.93 | 235.68 | 319.25 | 0.00 | 0.00 |
June | 2566.77 | 35.12 | 522.21 | 203.74 | 318.48 | 0.00 | 0.00 |
July | 1913.57 | 8.13 | 386.80 | 75.54 | 311.27 | 0.00 | 0.00 |
August | 1613.75 | 26.00 | 354.73 | 62.91 | 291.82 | 0.00 | 0.00 |
September | 1466.78 | 101.55 | 389.62 | 114.03 | 275.59 | 0.00 | 0.00 |
October | 1371.40 | 472.18 | 408.04 | 163.68 | 244.36 | 0.00 | 0.00 |
November | 988.12 | 891.10 | 370.65 | 159.87 | 210.78 | 0.00 | 0.00 |
December | 593.66 | 1228.38 | 316.54 | 122.07 | 194.47 | 0.00 | 0.00 |
Annual Sum or Average | 1509.12 | 479.40 | 422.25 | 155.53 | 266.72 | 0.00 | 0.00 |
Minimum of Months | 581.93 | 8.13 | 316.54 | 62.91 | 194.47 | 0.00 | 0.00 |
Maximum of Months | 2566.77 | 1260.78 | 584.24 | 273.31 | 319.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.62 | 1841.30 | 232.50 | 0.00 | 232.50 | 0.00 | 0.00 |
February | 409.05 | 1427.08 | 275.70 | 0.00 | 275.70 | 0.00 | 0.00 |
March | 881.47 | 835.80 | 332.22 | 0.00 | 332.22 | 0.00 | 0.00 |
April | 1738.28 | 297.17 | 361.34 | 2.07 | 359.27 | 0.00 | 0.00 |
May | 2507.07 | 52.91 | 404.51 | 16.32 | 388.19 | 0.00 | 0.00 |
June | 2732.23 | 48.67 | 419.80 | 21.68 | 398.12 | 0.00 | 0.00 |
July | 2373.45 | 9.21 | 410.25 | 8.96 | 401.29 | 0.00 | 0.00 |
August | 1958.24 | 29.31 | 374.93 | 1.78 | 373.15 | 0.00 | 0.00 |
September | 1454.39 | 122.76 | 333.55 | 0.05 | 333.51 | 0.00 | 0.00 |
October | 1062.92 | 633.79 | 288.95 | 0.00 | 288.95 | 0.00 | 0.00 |
November | 533.83 | 1239.13 | 244.74 | 0.00 | 244.74 | 0.00 | 0.00 |
December | 223.67 | 1782.82 | 226.81 | 0.00 | 226.81 | 0.00 | 0.00 |
Annual Sum or Average | 1342.28 | 690.22 | 325.69 | 4.25 | 321.44 | 0.00 | 0.00 |
Minimum of Months | 177.62 | 9.21 | 226.81 | 0.00 | 226.81 | 0.00 | 0.00 |
Maximum of Months | 2732.23 | 1841.30 | 419.80 | 21.68 | 401.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 485.14 | 1094.03 | 333.34 | 134.58 | 198.76 | 0.00 | 0.00 |
February | 798.73 | 866.77 | 403.95 | 167.10 | 236.84 | 0.00 | 0.00 |
March | 1331.89 | 519.20 | 491.51 | 202.54 | 288.97 | 0.00 | 0.00 |
April | 2175.65 | 196.11 | 584.19 | 271.71 | 312.48 | 0.00 | 0.00 |
May | 2585.00 | 34.24 | 576.27 | 255.50 | 320.77 | 0.00 | 0.00 |
June | 2408.17 | 31.86 | 471.16 | 157.78 | 313.38 | 0.00 | 0.00 |
July | 1955.91 | 5.32 | 394.40 | 83.47 | 310.93 | 0.00 | 0.00 |
August | 1627.57 | 18.88 | 354.97 | 61.61 | 293.35 | 0.00 | 0.00 |
September | 1437.11 | 78.87 | 379.14 | 105.51 | 273.63 | 0.00 | 0.00 |
October | 1364.02 | 405.47 | 416.81 | 169.40 | 247.41 | 0.00 | 0.00 |
November | 903.08 | 765.99 | 371.37 | 161.31 | 210.05 | 0.00 | 0.00 |
December | 540.97 | 1085.71 | 323.27 | 129.51 | 193.76 | 0.00 | 0.00 |
Annual Sum or Average | 1470.38 | 423.30 | 424.91 | 158.09 | 266.82 | 0.00 | 0.00 |
Minimum of Months | 485.14 | 5.32 | 323.27 | 61.61 | 193.76 | 0.00 | 0.00 |
Maximum of Months | 2585.00 | 1094.03 | 584.19 | 271.71 | 320.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2187.84 | 1720.44 | 1042.23 | 627.34 | 414.89 | 0.00 | 0.00 |
February | 2366.37 | 1401.58 | 1005.27 | 558.30 | 446.98 | 0.00 | 0.00 |
March | 2577.68 | 849.94 | 889.08 | 409.13 | 479.95 | 0.00 | 0.00 |
April | 2724.23 | 313.25 | 649.30 | 215.89 | 433.41 | 0.00 | 0.00 |
May | 2674.21 | 51.48 | 452.96 | 50.87 | 402.09 | 0.00 | 0.00 |
June | 2676.05 | 48.15 | 402.91 | 12.48 | 390.43 | 0.00 | 0.00 |
July | 2407.27 | 8.29 | 418.14 | 9.51 | 408.63 | 0.00 | 0.00 |
August | 2207.67 | 29.90 | 447.55 | 31.51 | 416.04 | 0.00 | 0.00 |
September | 2328.79 | 130.45 | 607.63 | 171.35 | 436.27 | 0.00 | 0.00 |
October | 3326.48 | 666.18 | 1024.28 | 576.64 | 447.64 | 0.00 | 0.00 |
November | 3389.63 | 1255.11 | 1248.16 | 818.92 | 429.24 | 0.00 | 0.00 |
December | 2479.89 | 1702.01 | 1109.38 | 687.48 | 421.90 | 0.00 | 0.00 |
Annual Sum or Average | 2612.36 | 678.16 | 773.37 | 346.19 | 427.18 | 0.00 | 0.00 |
Minimum of Months | 2187.84 | 8.29 | 402.91 | 9.51 | 390.43 | 0.00 | 0.00 |
Maximum of Months | 3389.63 | 1720.44 | 1248.16 | 818.92 | 479.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 570.41 | 1213.10 | 326.50 | 128.08 | 198.43 | 0.00 | 0.00 |
February | 805.96 | 951.57 | 372.57 | 138.00 | 234.57 | 0.00 | 0.00 |
March | 1351.29 | 564.13 | 481.11 | 191.97 | 289.14 | 0.00 | 0.00 |
April | 2196.87 | 208.34 | 584.22 | 273.30 | 310.92 | 0.00 | 0.00 |
May | 2549.10 | 37.98 | 554.91 | 235.67 | 319.24 | 0.00 | 0.00 |
June | 2577.60 | 33.52 | 522.20 | 203.73 | 318.47 | 0.00 | 0.00 |
July | 1937.95 | 5.97 | 386.79 | 75.53 | 311.26 | 0.00 | 0.00 |
August | 1639.90 | 19.08 | 354.72 | 62.91 | 291.81 | 0.00 | 0.00 |
September | 1488.19 | 83.27 | 389.61 | 114.02 | 275.58 | 0.00 | 0.00 |
October | 1381.80 | 430.62 | 408.03 | 163.67 | 244.36 | 0.00 | 0.00 |
November | 992.57 | 830.73 | 370.64 | 159.86 | 210.78 | 0.00 | 0.00 |
December | 593.38 | 1169.93 | 316.53 | 122.06 | 194.47 | 0.00 | 0.00 |
Annual Sum or Average | 1509.49 | 460.23 | 422.24 | 155.53 | 266.71 | 0.00 | 0.00 |
Minimum of Months | 570.41 | 5.97 | 316.53 | 62.91 | 194.47 | 0.00 | 0.00 |
Maximum of Months | 2577.60 | 1213.10 | 584.22 | 273.30 | 319.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.519044E+09 | 0.448209E+10 | 0.622722E+09 | 0.00 | 0.622722E+09 | 0.00 | 0.00 |
February | 0.102487E+10 | 0.314722E+10 | 0.666980E+09 | 0.00 | 0.666980E+09 | 0.00 | 0.00 |
March | 0.237203E+10 | 0.204453E+10 | 0.889827E+09 | 0.00 | 0.889827E+09 | 0.00 | 0.00 |
April | 0.447177E+10 | 0.711546E+09 | 0.936597E+09 | 5377957.18 | 0.931219E+09 | 0.00 | 0.00 |
May | 0.666677E+10 | 0.136469E+09 | 0.108344E+10 | 43714162.19 | 0.103972E+10 | 0.00 | 0.00 |
June | 0.703249E+10 | 0.124270E+09 | 0.108813E+10 | 56191051.23 | 0.103194E+10 | 0.00 | 0.00 |
July | 0.631433E+10 | 22294563.59 | 0.109881E+10 | 24006596.20 | 0.107481E+10 | 0.00 | 0.00 |
August | 0.521386E+10 | 71384822.97 | 0.100422E+10 | 4760961.04 | 0.999456E+09 | 0.00 | 0.00 |
September | 0.376867E+10 | 0.279901E+09 | 0.864572E+09 | 121533.02 | 0.864451E+09 | 0.00 | 0.00 |
October | 0.286371E+10 | 0.153355E+10 | 0.773912E+09 | 0.00 | 0.773912E+09 | 0.00 | 0.00 |
November | 0.144424E+10 | 0.288152E+10 | 0.634366E+09 | 0.00 | 0.634366E+09 | 0.00 | 0.00 |
December | 0.666363E+09 | 0.433112E+10 | 0.607476E+09 | 0.00 | 0.607476E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.423581E+11 | 0.197659E+11 | 0.102711E+11 | 0.134172E+09 | 0.101369E+11 | 0.00 | 0.00 |
Minimum of Months | 0.519044E+09 | 22294563.59 | 0.607476E+09 | 0.00 | 0.607476E+09 | 0.00 | 0.00 |
Maximum of Months | 0.703249E+10 | 0.448209E+10 | 0.109881E+10 | 56191051.23 | 0.107481E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136759E+10 | 0.267988E+10 | 0.892808E+09 | 0.360451E+09 | 0.532357E+09 | 0.00 | 0.00 |
February | 0.197141E+10 | 0.193623E+10 | 0.977224E+09 | 0.404250E+09 | 0.572974E+09 | 0.00 | 0.00 |
March | 0.358047E+10 | 0.129323E+10 | 0.131645E+10 | 0.542486E+09 | 0.773965E+09 | 0.00 | 0.00 |
April | 0.561742E+10 | 0.476393E+09 | 0.151423E+10 | 0.704278E+09 | 0.809952E+09 | 0.00 | 0.00 |
May | 0.688848E+10 | 89193642.57 | 0.154348E+10 | 0.684337E+09 | 0.859142E+09 | 0.00 | 0.00 |
June | 0.621073E+10 | 81750477.52 | 0.122124E+10 | 0.408972E+09 | 0.812269E+09 | 0.00 | 0.00 |
July | 0.521144E+10 | 12974509.85 | 0.105636E+10 | 0.223561E+09 | 0.832794E+09 | 0.00 | 0.00 |
August | 0.434711E+10 | 46887096.09 | 0.950751E+09 | 0.165030E+09 | 0.785721E+09 | 0.00 | 0.00 |
September | 0.372790E+10 | 0.184064E+09 | 0.982723E+09 | 0.273473E+09 | 0.709250E+09 | 0.00 | 0.00 |
October | 0.367144E+10 | 0.997253E+09 | 0.111640E+10 | 0.453729E+09 | 0.662667E+09 | 0.00 | 0.00 |
November | 0.238974E+10 | 0.181129E+10 | 0.962579E+09 | 0.418127E+09 | 0.544452E+09 | 0.00 | 0.00 |
December | 0.152726E+10 | 0.266229E+10 | 0.865841E+09 | 0.346880E+09 | 0.518961E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.465110E+11 | 0.122714E+11 | 0.134001E+11 | 0.498557E+10 | 0.841451E+10 | 0.00 | 0.00 |
Minimum of Months | 0.136759E+10 | 12974509.85 | 0.865841E+09 | 0.165030E+09 | 0.518961E+09 | 0.00 | 0.00 |
Maximum of Months | 0.688848E+10 | 0.267988E+10 | 0.154348E+10 | 0.704278E+09 | 0.859142E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.594192E+10 | 0.418864E+10 | 0.279150E+10 | 0.168026E+10 | 0.111123E+10 | 0.00 | 0.00 |
February | 0.575762E+10 | 0.310875E+10 | 0.243196E+10 | 0.135063E+10 | 0.108133E+10 | 0.00 | 0.00 |
March | 0.689360E+10 | 0.209598E+10 | 0.238130E+10 | 0.109580E+10 | 0.128550E+10 | 0.00 | 0.00 |
April | 0.701107E+10 | 0.752233E+09 | 0.168299E+10 | 0.559598E+09 | 0.112339E+10 | 0.00 | 0.00 |
May | 0.711287E+10 | 0.131987E+09 | 0.121320E+10 | 0.136247E+09 | 0.107695E+10 | 0.00 | 0.00 |
June | 0.688648E+10 | 0.123180E+09 | 0.104434E+10 | 32339881.00 | 0.101200E+10 | 0.00 | 0.00 |
July | 0.640390E+10 | 19919372.76 | 0.111995E+10 | 25481342.32 | 0.109447E+10 | 0.00 | 0.00 |
August | 0.588024E+10 | 73401581.44 | 0.119870E+10 | 84388870.00 | 0.111432E+10 | 0.00 | 0.00 |
September | 0.602043E+10 | 0.300375E+09 | 0.157497E+10 | 0.444149E+09 | 0.113082E+10 | 0.00 | 0.00 |
October | 0.889919E+10 | 0.162955E+10 | 0.274343E+10 | 0.154448E+10 | 0.119895E+10 | 0.00 | 0.00 |
November | 0.882121E+10 | 0.295299E+10 | 0.323523E+10 | 0.212264E+10 | 0.111259E+10 | 0.00 | 0.00 |
December | 0.674052E+10 | 0.415534E+10 | 0.297136E+10 | 0.184134E+10 | 0.113002E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.823691E+11 | 0.195324E+11 | 0.243889E+11 | 0.109174E+11 | 0.134716E+11 | 0.00 | 0.00 |
Minimum of Months | 0.575762E+10 | 19919372.76 | 0.104434E+10 | 25481342.32 | 0.101200E+10 | 0.00 | 0.00 |
Maximum of Months | 0.889919E+10 | 0.418864E+10 | 0.323523E+10 | 0.212264E+10 | 0.128550E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154726E+10 | 0.295645E+10 | 0.874508E+09 | 0.343046E+09 | 0.531463E+09 | 0.00 | 0.00 |
February | 0.195689E+10 | 0.211067E+10 | 0.901317E+09 | 0.333846E+09 | 0.567471E+09 | 0.00 | 0.00 |
March | 0.361036E+10 | 0.138837E+10 | 0.128860E+10 | 0.514159E+09 | 0.774445E+09 | 0.00 | 0.00 |
April | 0.565923E+10 | 0.499769E+09 | 0.151430E+10 | 0.708395E+09 | 0.805908E+09 | 0.00 | 0.00 |
May | 0.678928E+10 | 97048224.23 | 0.148627E+10 | 0.631213E+09 | 0.855055E+09 | 0.00 | 0.00 |
June | 0.664577E+10 | 84637546.21 | 0.135354E+10 | 0.528064E+09 | 0.825475E+09 | 0.00 | 0.00 |
July | 0.516565E+10 | 14487212.63 | 0.103598E+10 | 0.202307E+09 | 0.833669E+09 | 0.00 | 0.00 |
August | 0.437572E+10 | 46940293.24 | 0.950072E+09 | 0.168495E+09 | 0.781577E+09 | 0.00 | 0.00 |
September | 0.385731E+10 | 0.192416E+09 | 0.100986E+10 | 0.295548E+09 | 0.714311E+09 | 0.00 | 0.00 |
October | 0.370466E+10 | 0.104674E+10 | 0.109287E+10 | 0.438379E+09 | 0.654486E+09 | 0.00 | 0.00 |
November | 0.259623E+10 | 0.194749E+10 | 0.960693E+09 | 0.414357E+09 | 0.546336E+09 | 0.00 | 0.00 |
December | 0.162699E+10 | 0.284804E+10 | 0.847791E+09 | 0.326929E+09 | 0.520862E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.475353E+11 | 0.132331E+11 | 0.133158E+11 | 0.490474E+10 | 0.841106E+10 | 0.00 | 0.00 |
Minimum of Months | 0.154726E+10 | 14487212.63 | 0.847791E+09 | 0.168495E+09 | 0.520862E+09 | 0.00 | 0.00 |
Maximum of Months | 0.678928E+10 | 0.295645E+10 | 0.151430E+10 | 0.708395E+09 | 0.855055E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.493392E+09 | 0.504808E+10 | 0.622718E+09 | 0.00 | 0.622718E+09 | 0.00 | 0.00 |
February | 0.105449E+10 | 0.341207E+10 | 0.666976E+09 | 0.00 | 0.666976E+09 | 0.00 | 0.00 |
March | 0.246835E+10 | 0.213054E+10 | 0.889822E+09 | 0.00 | 0.889822E+09 | 0.00 | 0.00 |
April | 0.458347E+10 | 0.695391E+09 | 0.936591E+09 | 5377926.06 | 0.931213E+09 | 0.00 | 0.00 |
May | 0.674473E+10 | 0.120866E+09 | 0.108343E+10 | 43713909.26 | 0.103972E+10 | 0.00 | 0.00 |
June | 0.705135E+10 | 0.124932E+09 | 0.108812E+10 | 56190726.11 | 0.103193E+10 | 0.00 | 0.00 |
July | 0.627040E+10 | 31989171.77 | 0.109881E+10 | 24006457.30 | 0.107480E+10 | 0.00 | 0.00 |
August | 0.515077E+10 | 0.102759E+09 | 0.100421E+10 | 4760933.49 | 0.999451E+09 | 0.00 | 0.00 |
September | 0.368353E+10 | 0.373770E+09 | 0.864567E+09 | 121532.31 | 0.864446E+09 | 0.00 | 0.00 |
October | 0.279267E+10 | 0.181329E+10 | 0.773908E+09 | 0.00 | 0.773908E+09 | 0.00 | 0.00 |
November | 0.135437E+10 | 0.338138E+10 | 0.634362E+09 | 0.00 | 0.634362E+09 | 0.00 | 0.00 |
December | 0.585794E+09 | 0.495589E+10 | 0.607473E+09 | 0.00 | 0.607473E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.422333E+11 | 0.221909E+11 | 0.102710E+11 | 0.134171E+09 | 0.101368E+11 | 0.00 | 0.00 |
Minimum of Months | 0.493392E+09 | 31989171.77 | 0.607473E+09 | 0.00 | 0.607473E+09 | 0.00 | 0.00 |
Maximum of Months | 0.705135E+10 | 0.504808E+10 | 0.109881E+10 | 56190726.11 | 0.107480E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129910E+10 | 0.305465E+10 | 0.892839E+09 | 0.360466E+09 | 0.532373E+09 | 0.00 | 0.00 |
February | 0.197855E+10 | 0.213193E+10 | 0.977258E+09 | 0.404266E+09 | 0.572992E+09 | 0.00 | 0.00 |
March | 0.365296E+10 | 0.137647E+10 | 0.131650E+10 | 0.542508E+09 | 0.773988E+09 | 0.00 | 0.00 |
April | 0.571287E+10 | 0.486816E+09 | 0.151428E+10 | 0.704306E+09 | 0.809975E+09 | 0.00 | 0.00 |
May | 0.696430E+10 | 86640541.06 | 0.154353E+10 | 0.684364E+09 | 0.859166E+09 | 0.00 | 0.00 |
June | 0.624462E+10 | 85286207.68 | 0.122128E+10 | 0.408989E+09 | 0.812292E+09 | 0.00 | 0.00 |
July | 0.519374E+10 | 19488471.09 | 0.105639E+10 | 0.223570E+09 | 0.832821E+09 | 0.00 | 0.00 |
August | 0.431234E+10 | 68331281.77 | 0.950783E+09 | 0.165036E+09 | 0.785746E+09 | 0.00 | 0.00 |
September | 0.368439E+10 | 0.247531E+09 | 0.982756E+09 | 0.273484E+09 | 0.709272E+09 | 0.00 | 0.00 |
October | 0.363697E+10 | 0.118814E+10 | 0.111643E+10 | 0.453747E+09 | 0.662686E+09 | 0.00 | 0.00 |
November | 0.232031E+10 | 0.213853E+10 | 0.962611E+09 | 0.418143E+09 | 0.544468E+09 | 0.00 | 0.00 |
December | 0.142352E+10 | 0.306736E+10 | 0.865870E+09 | 0.346894E+09 | 0.518977E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.464237E+11 | 0.139512E+11 | 0.134005E+11 | 0.498577E+10 | 0.841476E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129910E+10 | 19488471.09 | 0.865870E+09 | 0.165036E+09 | 0.518977E+09 | 0.00 | 0.00 |
Maximum of Months | 0.696430E+10 | 0.306736E+10 | 0.154353E+10 | 0.704306E+09 | 0.859166E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.594972E+10 | 0.489336E+10 | 0.279151E+10 | 0.168027E+10 | 0.111124E+10 | 0.00 | 0.00 |
February | 0.582616E+10 | 0.351685E+10 | 0.243197E+10 | 0.135064E+10 | 0.108133E+10 | 0.00 | 0.00 |
March | 0.701806E+10 | 0.228887E+10 | 0.238131E+10 | 0.109581E+10 | 0.128551E+10 | 0.00 | 0.00 |
April | 0.710049E+10 | 0.777585E+09 | 0.168300E+10 | 0.559601E+09 | 0.112339E+10 | 0.00 | 0.00 |
May | 0.710710E+10 | 0.125456E+09 | 0.121320E+10 | 0.136248E+09 | 0.107695E+10 | 0.00 | 0.00 |
June | 0.682656E+10 | 0.126239E+09 | 0.104434E+10 | 32340076.84 | 0.101200E+10 | 0.00 | 0.00 |
July | 0.631550E+10 | 30146386.33 | 0.111995E+10 | 25481496.62 | 0.109447E+10 | 0.00 | 0.00 |
August | 0.578305E+10 | 0.108848E+09 | 0.119871E+10 | 84389381.03 | 0.111432E+10 | 0.00 | 0.00 |
September | 0.593846E+10 | 0.424860E+09 | 0.157497E+10 | 0.444151E+09 | 0.113082E+10 | 0.00 | 0.00 |
October | 0.886315E+10 | 0.199461E+10 | 0.274344E+10 | 0.154449E+10 | 0.119895E+10 | 0.00 | 0.00 |
November | 0.880071E+10 | 0.358852E+10 | 0.323524E+10 | 0.212265E+10 | 0.111259E+10 | 0.00 | 0.00 |
December | 0.667255E+10 | 0.490947E+10 | 0.297138E+10 | 0.184135E+10 | 0.113002E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.822015E+11 | 0.227848E+11 | 0.243890E+11 | 0.109174E+11 | 0.134716E+11 | 0.00 | 0.00 |
Minimum of Months | 0.578305E+10 | 30146386.33 | 0.104434E+10 | 25481496.62 | 0.101200E+10 | 0.00 | 0.00 |
Maximum of Months | 0.886315E+10 | 0.490947E+10 | 0.323524E+10 | 0.212265E+10 | 0.128551E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155864E+10 | 0.337687E+10 | 0.874536E+09 | 0.343058E+09 | 0.531478E+09 | 0.00 | 0.00 |
February | 0.200582E+10 | 0.232619E+10 | 0.901346E+09 | 0.333858E+09 | 0.567487E+09 | 0.00 | 0.00 |
March | 0.370833E+10 | 0.148705E+10 | 0.128865E+10 | 0.514179E+09 | 0.774467E+09 | 0.00 | 0.00 |
April | 0.575752E+10 | 0.520060E+09 | 0.151435E+10 | 0.708422E+09 | 0.805929E+09 | 0.00 | 0.00 |
May | 0.683423E+10 | 98072338.50 | 0.148631E+10 | 0.631237E+09 | 0.855077E+09 | 0.00 | 0.00 |
June | 0.665308E+10 | 91035501.73 | 0.135358E+10 | 0.528084E+09 | 0.825496E+09 | 0.00 | 0.00 |
July | 0.512531E+10 | 21771234.01 | 0.103601E+10 | 0.202315E+09 | 0.833694E+09 | 0.00 | 0.00 |
August | 0.432227E+10 | 69640135.00 | 0.950102E+09 | 0.168501E+09 | 0.781601E+09 | 0.00 | 0.00 |
September | 0.380190E+10 | 0.263220E+09 | 0.100989E+10 | 0.295559E+09 | 0.714332E+09 | 0.00 | 0.00 |
October | 0.367317E+10 | 0.126470E+10 | 0.109290E+10 | 0.438396E+09 | 0.654503E+09 | 0.00 | 0.00 |
November | 0.256121E+10 | 0.230973E+10 | 0.960723E+09 | 0.414372E+09 | 0.546350E+09 | 0.00 | 0.00 |
December | 0.159005E+10 | 0.329009E+10 | 0.847818E+09 | 0.326941E+09 | 0.520877E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.475915E+11 | 0.151184E+11 | 0.133162E+11 | 0.490492E+10 | 0.841129E+10 | 0.00 | 0.00 |
Minimum of Months | 0.155864E+10 | 21771234.01 | 0.847818E+09 | 0.168501E+09 | 0.520877E+09 | 0.00 | 0.00 |
Maximum of Months | 0.683423E+10 | 0.337687E+10 | 0.151435E+10 | 0.708422E+09 | 0.855077E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.475748E+09 | 0.493173E+10 | 0.622722E+09 | 0.00 | 0.622722E+09 | 0.00 | 0.00 |
February | 0.989585E+09 | 0.345238E+10 | 0.666980E+09 | 0.00 | 0.666980E+09 | 0.00 | 0.00 |
March | 0.236093E+10 | 0.223861E+10 | 0.889827E+09 | 0.00 | 0.889827E+09 | 0.00 | 0.00 |
April | 0.450563E+10 | 0.770269E+09 | 0.936597E+09 | 5377957.18 | 0.931219E+09 | 0.00 | 0.00 |
May | 0.671495E+10 | 0.141712E+09 | 0.108344E+10 | 43714162.19 | 0.103972E+10 | 0.00 | 0.00 |
June | 0.708194E+10 | 0.126150E+09 | 0.108813E+10 | 56191051.23 | 0.103194E+10 | 0.00 | 0.00 |
July | 0.635705E+10 | 24679557.50 | 0.109881E+10 | 24006596.20 | 0.107481E+10 | 0.00 | 0.00 |
August | 0.524495E+10 | 78496022.81 | 0.100422E+10 | 4760961.04 | 0.999456E+09 | 0.00 | 0.00 |
September | 0.376978E+10 | 0.318193E+09 | 0.864572E+09 | 121533.02 | 0.864451E+09 | 0.00 | 0.00 |
October | 0.284692E+10 | 0.169753E+10 | 0.773912E+09 | 0.00 | 0.773912E+09 | 0.00 | 0.00 |
November | 0.138369E+10 | 0.321184E+10 | 0.634366E+09 | 0.00 | 0.634366E+09 | 0.00 | 0.00 |
December | 0.599076E+09 | 0.477511E+10 | 0.607476E+09 | 0.00 | 0.607476E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.423303E+11 | 0.217667E+11 | 0.102711E+11 | 0.134172E+09 | 0.101369E+11 | 0.00 | 0.00 |
Minimum of Months | 0.475748E+09 | 24679557.50 | 0.607476E+09 | 0.00 | 0.607476E+09 | 0.00 | 0.00 |
Maximum of Months | 0.708194E+10 | 0.493173E+10 | 0.109881E+10 | 56191051.23 | 0.107481E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129939E+10 | 0.293026E+10 | 0.892808E+09 | 0.360451E+09 | 0.532357E+09 | 0.00 | 0.00 |
February | 0.193229E+10 | 0.209689E+10 | 0.977224E+09 | 0.404250E+09 | 0.572974E+09 | 0.00 | 0.00 |
March | 0.356734E+10 | 0.139062E+10 | 0.131645E+10 | 0.542486E+09 | 0.773965E+09 | 0.00 | 0.00 |
April | 0.563929E+10 | 0.508323E+09 | 0.151423E+10 | 0.704278E+09 | 0.809952E+09 | 0.00 | 0.00 |
May | 0.692367E+10 | 91720466.27 | 0.154348E+10 | 0.684337E+09 | 0.859142E+09 | 0.00 | 0.00 |
June | 0.624198E+10 | 82593334.15 | 0.122124E+10 | 0.408972E+09 | 0.812269E+09 | 0.00 | 0.00 |
July | 0.523870E+10 | 14251744.33 | 0.105636E+10 | 0.223561E+09 | 0.832794E+09 | 0.00 | 0.00 |
August | 0.435929E+10 | 50579088.39 | 0.950751E+09 | 0.165030E+09 | 0.785721E+09 | 0.00 | 0.00 |
September | 0.372499E+10 | 0.204436E+09 | 0.982723E+09 | 0.273473E+09 | 0.709250E+09 | 0.00 | 0.00 |
October | 0.365339E+10 | 0.108601E+10 | 0.111640E+10 | 0.453729E+09 | 0.662667E+09 | 0.00 | 0.00 |
November | 0.234079E+10 | 0.198545E+10 | 0.962579E+09 | 0.418127E+09 | 0.544452E+09 | 0.00 | 0.00 |
December | 0.144893E+10 | 0.290796E+10 | 0.865841E+09 | 0.346880E+09 | 0.518961E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.463700E+11 | 0.133491E+11 | 0.134001E+11 | 0.498557E+10 | 0.841451E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129939E+10 | 14251744.33 | 0.865841E+09 | 0.165030E+09 | 0.518961E+09 | 0.00 | 0.00 |
Maximum of Months | 0.692367E+10 | 0.293026E+10 | 0.154348E+10 | 0.704278E+09 | 0.859142E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.585992E+10 | 0.460803E+10 | 0.279150E+10 | 0.168026E+10 | 0.111123E+10 | 0.00 | 0.00 |
February | 0.572473E+10 | 0.339070E+10 | 0.243196E+10 | 0.135063E+10 | 0.108133E+10 | 0.00 | 0.00 |
March | 0.690405E+10 | 0.227648E+10 | 0.238130E+10 | 0.109580E+10 | 0.128550E+10 | 0.00 | 0.00 |
April | 0.706119E+10 | 0.811954E+09 | 0.168299E+10 | 0.559598E+09 | 0.112339E+10 | 0.00 | 0.00 |
May | 0.716260E+10 | 0.137879E+09 | 0.121320E+10 | 0.136247E+09 | 0.107695E+10 | 0.00 | 0.00 |
June | 0.693633E+10 | 0.124792E+09 | 0.104434E+10 | 32339881.00 | 0.101200E+10 | 0.00 | 0.00 |
July | 0.644764E+10 | 22194542.97 | 0.111995E+10 | 25481342.32 | 0.109447E+10 | 0.00 | 0.00 |
August | 0.591302E+10 | 80072261.61 | 0.119870E+10 | 84388870.00 | 0.111432E+10 | 0.00 | 0.00 |
September | 0.603622E+10 | 0.338122E+09 | 0.157497E+10 | 0.444149E+09 | 0.113082E+10 | 0.00 | 0.00 |
October | 0.890965E+10 | 0.178429E+10 | 0.274343E+10 | 0.154448E+10 | 0.119895E+10 | 0.00 | 0.00 |
November | 0.878592E+10 | 0.325325E+10 | 0.323523E+10 | 0.212264E+10 | 0.111259E+10 | 0.00 | 0.00 |
December | 0.664214E+10 | 0.455866E+10 | 0.297136E+10 | 0.184134E+10 | 0.113002E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.823834E+11 | 0.213864E+11 | 0.243889E+11 | 0.109174E+11 | 0.134716E+11 | 0.00 | 0.00 |
Minimum of Months | 0.572473E+10 | 22194542.97 | 0.104434E+10 | 25481342.32 | 0.101200E+10 | 0.00 | 0.00 |
Maximum of Months | 0.890965E+10 | 0.460803E+10 | 0.323523E+10 | 0.212264E+10 | 0.128550E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.152777E+10 | 0.324917E+10 | 0.874508E+09 | 0.343046E+09 | 0.531463E+09 | 0.00 | 0.00 |
February | 0.194979E+10 | 0.230203E+10 | 0.901317E+09 | 0.333846E+09 | 0.567471E+09 | 0.00 | 0.00 |
March | 0.361931E+10 | 0.151098E+10 | 0.128860E+10 | 0.514159E+09 | 0.774445E+09 | 0.00 | 0.00 |
April | 0.569430E+10 | 0.540015E+09 | 0.151430E+10 | 0.708395E+09 | 0.805908E+09 | 0.00 | 0.00 |
May | 0.682751E+10 | 0.101718E+09 | 0.148627E+10 | 0.631213E+09 | 0.855055E+09 | 0.00 | 0.00 |
June | 0.668113E+10 | 86878255.02 | 0.135354E+10 | 0.528064E+09 | 0.825475E+09 | 0.00 | 0.00 |
July | 0.519059E+10 | 15977285.55 | 0.103598E+10 | 0.202307E+09 | 0.833669E+09 | 0.00 | 0.00 |
August | 0.439232E+10 | 51113364.18 | 0.950072E+09 | 0.168495E+09 | 0.781577E+09 | 0.00 | 0.00 |
September | 0.385739E+10 | 0.215842E+09 | 0.100986E+10 | 0.295548E+09 | 0.714311E+09 | 0.00 | 0.00 |
October | 0.370102E+10 | 0.115337E+10 | 0.109287E+10 | 0.438379E+09 | 0.654486E+09 | 0.00 | 0.00 |
November | 0.257274E+10 | 0.215325E+10 | 0.960693E+09 | 0.414357E+09 | 0.546336E+09 | 0.00 | 0.00 |
December | 0.158930E+10 | 0.313355E+10 | 0.847791E+09 | 0.326929E+09 | 0.520862E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.476032E+11 | 0.145139E+11 | 0.133158E+11 | 0.490474E+10 | 0.841106E+10 | 0.00 | 0.00 |
Minimum of Months | 0.152777E+10 | 15977285.55 | 0.847791E+09 | 0.168495E+09 | 0.520862E+09 | 0.00 | 0.00 |
Maximum of Months | 0.682751E+10 | 0.324917E+10 | 0.151430E+10 | 0.708395E+09 | 0.855055E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.392637E+10 | -0.369108E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235292164.9 | 60.05 | 0.00 | 0.00 |
February | 0.349657E+10 | -0.328574E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -210823585.7 | 60.05 | 0.00 | 0.00 |
March | 0.386674E+10 | -0.363450E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232237705.0 | 60.05 | 0.00 | 0.00 |
April | 0.316914E+10 | -0.294508E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224051735.9 | 60.05 | 0.00 | 0.00 |
May | 0.303646E+10 | -0.280387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232594675.6 | 60.05 | 0.00 | 0.00 |
June | 0.273232E+10 | -0.250665E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225672204.4 | 60.05 | 0.00 | 0.00 |
July | 0.248938E+10 | -0.225654E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232832179.7 | 60.05 | 0.00 | 0.00 |
August | 0.281349E+10 | -0.258092E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232565008.4 | 60.05 | 0.00 | 0.00 |
September | 0.278647E+10 | -0.256232E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224153206.9 | 60.05 | 0.00 | 0.00 |
October | 0.321485E+10 | -0.298370E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231142480.0 | 60.05 | 0.00 | 0.00 |
November | 0.349601E+10 | -0.327156E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224450337.7 | 60.05 | 0.00 | 0.00 |
December | 0.372259E+10 | -0.348864E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233951337.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.387504E+11 | -0.360106E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273977E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.248938E+10 | -0.369108E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -235292164.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.392637E+10 | -0.225654E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -210823585.7 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 319.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 364.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 386.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 379.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 372.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 317.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 315.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108678E+10 | 23189.36 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.497894E+09 | 20562.45 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36201799.86 | 3381.28 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67404667.04 | 8531.57 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608798E+09 | 22727.54 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108678E+10 | 23189.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 33506833.71 | 18170.09 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2320043.22 | 1804.94 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2636979.43 | 1998.87 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38463856.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33506833.71 | 18170.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100927E+09 | 22829.98 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8331810.78 | 3984.02 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8708700.46 | 4255.42 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100927E+09 | 22829.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 56228613.57 | 17567.15 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4052322.65 | 2002.19 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4775018.81 | 2190.08 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65055955.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56228613.57 | 17567.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22781634.99 | 31476.97 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22781634.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22781634.99 | 31476.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162172E+09 | 23835.05 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18708614.13 | 5603.77 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 545606.62 | 2604.86 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 37273022.97 | 7316.02 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218699E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162172E+09 | 23835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136114E+09 | 19510.38 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11780329.11 | 3309.14 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 904821.57 | 2112.45 | 25-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27420105.94 | 5086.59 | 23-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136114E+09 | 19510.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.296033E+09 | 23446.14 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38055872.78 | 6239.64 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1739424.23 | 5709.73 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 74014452.12 | 7741.84 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.296033E+09 | 23446.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230966E+09 | 20777.87 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31497205.45 | 3587.27 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1101303.93 | 2125.13 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 58482300.65 | 5124.03 | 23-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230966E+09 | 20777.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.695940E+09 | 74185.75 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77173044.42 | 21145.96 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1587414.39 | 5474.85 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192433E+09 | 36091.30 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.967134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.695940E+09 | 74185.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.986530E+09 | 28138.85 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339906E+09 | 17922.25 | 02-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10758960.84 | 7471.70 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78997036.87 | 10749.00 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.615113E+09 | 28138.85 | 21-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.986530E+09 | 28138.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.787982E+09 | 20946.00 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238698E+09 | 12867.91 | 02-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6043999.33 | 4441.94 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 302799.59 | 2195.53 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68137290.47 | 7204.46 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.525276E+09 | 20946.00 | 23-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.787982E+09 | 20946.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145111E+10 | 27849.42 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.461631E+09 | 18848.23 | 02-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18334336.47 | 7559.33 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 193277.67 | 1610.65 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136161E+09 | 11260.65 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.931353E+09 | 27849.42 | 21-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145111E+10 | 27849.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111229E+10 | 23537.73 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.386743E+09 | 13484.80 | 02-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19363606.12 | 5391.05 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 686642.94 | 2825.04 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128133E+09 | 7509.84 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.752509E+09 | 23537.73 | 23-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111229E+10 | 23537.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.303518E+11 | 0.272199E+11 | 42547.48 | 12-JAN-15:20 | 42547.48 | 0.00 |
February | 0.00 | 0.00 | 0.392509E+11 | 0.359407E+11 | 56880.56 | 22-FEB-15:10 | 56880.56 | 0.00 |
March | 0.00 | 0.00 | 0.670322E+11 | 0.635901E+11 | 86867.50 | 29-MAR-11:10 | 63773.14 | 0.00 |
April | 0.00 | 0.00 | 0.917225E+11 | 0.872173E+11 | 138696.80 | 27-APR-04:01 | 105414.18 | 0.00 |
May | 0.00 | 0.00 | 0.130182E+12 | 0.112199E+12 | 160077.45 | 24-MAY-04:01 | 94836.56 | 0.00 |
June | 0.00 | 0.00 | 0.145996E+12 | 0.113732E+12 | 159122.81 | 27-JUN-04:01 | 100910.78 | 0.00 |
July | 0.00 | 0.00 | 0.156590E+12 | 0.105071E+12 | 164664.11 | 20-JUL-04:03 | 81437.57 | 0.00 |
August | 0.00 | 0.00 | 0.158930E+12 | 0.103829E+12 | 160399.72 | 11-AUG-04:02 | 95816.36 | 0.00 |
September | 0.00 | 0.00 | 0.128831E+12 | 0.900283E+11 | 158996.20 | 06-SEP-04:02 | 94914.84 | 0.00 |
October | 0.00 | 0.00 | 0.914698E+11 | 0.804060E+11 | 109275.60 | 12-OCT-05:12 | 71649.48 | 0.00 |
November | 0.00 | 0.00 | 0.591191E+11 | 0.558271E+11 | 72477.58 | 09-NOV-12:00 | 62919.81 | 0.00 |
December | 0.00 | 0.00 | 0.359581E+11 | 0.331645E+11 | 49015.32 | 01-DEC-15:10 | 49015.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113543E+13 | 0.908226E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.303518E+11 | 0.272199E+11 | 42547.48 | 42547.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.158930E+12 | 0.113732E+12 | 164664.11 | 105414.18 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.224261E+11 | 0.190734E+11 | 33361.24 | 12-JAN-15:00 | 33361.24 | 0.00 |
February | 0.00 | 0.00 | 0.316413E+11 | 0.277304E+11 | 50223.53 | 22-FEB-15:10 | 50223.53 | 0.00 |
March | 0.00 | 0.00 | 0.583384E+11 | 0.543034E+11 | 77631.02 | 28-MAR-15:50 | 77631.02 | 0.00 |
April | 0.00 | 0.00 | 0.828694E+11 | 0.791277E+11 | 141832.12 | 27-APR-04:01 | 108526.06 | 0.00 |
May | 0.00 | 0.00 | 0.117014E+12 | 0.101503E+12 | 152167.45 | 24-MAY-04:01 | 91199.42 | 0.00 |
June | 0.00 | 0.00 | 0.128154E+12 | 0.999586E+11 | 153331.07 | 26-JUN-04:01 | 89854.80 | 0.00 |
July | 0.00 | 0.00 | 0.134601E+12 | 0.886054E+11 | 157076.74 | 20-JUL-04:01 | 81594.97 | 0.00 |
August | 0.00 | 0.00 | 0.131399E+12 | 0.840674E+11 | 152945.78 | 19-AUG-04:01 | 89093.13 | 0.00 |
September | 0.00 | 0.00 | 0.104678E+12 | 0.719729E+11 | 153436.91 | 11-SEP-04:02 | 80776.90 | 0.00 |
October | 0.00 | 0.00 | 0.738107E+11 | 0.642970E+11 | 97760.14 | 04-OCT-04:02 | 68648.67 | 0.00 |
November | 0.00 | 0.00 | 0.467035E+11 | 0.427329E+11 | 61750.83 | 09-NOV-13:03 | 57332.21 | 0.00 |
December | 0.00 | 0.00 | 0.266394E+11 | 0.231847E+11 | 39648.72 | 03-DEC-13:12 | 39648.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.958275E+12 | 0.756557E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.224261E+11 | 0.190734E+11 | 33361.24 | 33361.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134601E+12 | 0.101503E+12 | 157076.74 | 108526.06 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.270765E+11 | 0.231206E+11 | 38626.64 | 12-JAN-15:00 | 38626.64 | 0.00 |
February | 0.00 | 0.00 | 0.361768E+11 | 0.316795E+11 | 61142.53 | 22-FEB-14:50 | 61142.53 | 0.00 |
March | 0.00 | 0.00 | 0.667052E+11 | 0.617428E+11 | 97505.57 | 28-MAR-15:20 | 97505.57 | 0.00 |
April | 0.00 | 0.00 | 0.964509E+11 | 0.922479E+11 | 163416.72 | 16-APR-15:11 | 146344.73 | 0.00 |
May | 0.00 | 0.00 | 0.134614E+12 | 0.118762E+12 | 182586.46 | 24-MAY-04:01 | 102885.37 | 0.00 |
June | 0.00 | 0.00 | 0.145881E+12 | 0.117521E+12 | 183845.55 | 27-JUN-04:01 | 109500.83 | 0.00 |
July | 0.00 | 0.00 | 0.148176E+12 | 0.102023E+12 | 188721.57 | 20-JUL-04:01 | 97678.35 | 0.00 |
August | 0.00 | 0.00 | 0.142900E+12 | 0.952715E+11 | 182539.88 | 31-AUG-04:01 | 112962.87 | 0.00 |
September | 0.00 | 0.00 | 0.112999E+12 | 0.801449E+11 | 181409.97 | 01-SEP-04:01 | 105039.24 | 0.00 |
October | 0.00 | 0.00 | 0.813322E+11 | 0.712711E+11 | 108183.96 | 03-OCT-13:30 | 95620.03 | 0.00 |
November | 0.00 | 0.00 | 0.511033E+11 | 0.463167E+11 | 71956.27 | 09-NOV-14:10 | 71956.27 | 0.00 |
December | 0.00 | 0.00 | 0.301334E+11 | 0.260626E+11 | 47777.18 | 03-DEC-13:02 | 47777.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107355E+13 | 0.866164E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.270765E+11 | 0.231206E+11 | 38626.64 | 38626.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.148176E+12 | 0.118762E+12 | 188721.57 | 146344.73 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1369.18 | 4991.59 | 17-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1349.30 | 4961.58 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1347.92 | 4749.25 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1127.65 | 4301.50 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 1038.30 | 3854.02 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 958.58 | 3415.11 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 834.39 | 3149.66 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 955.10 | 3361.94 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 980.18 | 3750.11 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1105.43 | 4259.50 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1253.37 | 4684.49 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1293.77 | 4939.69 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1133.26 | ||||
Minimum of Months | 0.00 | 0.00 | 834.39 | 3149.66 | ||
Maximum of Months | 0.00 | 0.00 | 1369.18 | 4991.59 |
Report: FanReportMonthly
For: CORE_BOTTOM PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147541E+09 | 0.04 | 811.72 | 02-JAN-06:11 | 0.62 |
February | 88883039.55 | 0.03 | 811.72 | 01-FEB-06:12 | 0.62 |
March | 31900488.17 | 0.01 | 811.72 | 01-MAR-07:03 | 0.62 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 1412388.03 | 0.00 | 811.72 | 31-OCT-06:06 | 0.62 |
November | 39619919.27 | 0.01 | 811.72 | 01-NOV-06:08 | 0.62 |
December | 75396937.14 | 0.02 | 811.72 | 01-DEC-07:03 | 0.62 |
Annual Sum or Average | 0.384754E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147541E+09 | 0.04 | 811.72 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139741E+09 | 0.05 | 657.58 | 02-JAN-06:11 | 0.62 |
February | 40572470.06 | 0.02 | 657.58 | 01-FEB-06:12 | 0.62 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 98636.48 | 0.00 | 657.58 | 27-NOV-07:03 | 0.62 |
December | 39250741.29 | 0.01 | 657.58 | 02-DEC-07:03 | 0.62 |
Annual Sum or Average | 0.219662E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139741E+09 | 0.05 | 657.58 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229184E+09 | 0.07 | 799.14 | 02-JAN-06:11 | 0.62 |
February | 66208555.46 | 0.02 | 799.14 | 01-FEB-06:12 | 0.62 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 599353.25 | 0.00 | 799.14 | 27-NOV-07:03 | 0.62 |
December | 70380054.06 | 0.02 | 799.14 | 02-DEC-07:03 | 0.62 |
Annual Sum or Average | 0.366372E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229184E+09 | 0.07 | 799.14 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.214250E+09 | 0.07 | 694.81 | 02-JAN-06:11 | 0.62 |
February | 74795945.95 | 0.03 | 694.81 | 01-FEB-06:12 | 0.62 |
March | 868508.43 | 0.00 | 694.81 | 01-MAR-07:03 | 0.62 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 1320132.81 | 0.00 | 694.81 | 25-NOV-07:03 | 0.62 |
December | 77304198.29 | 0.03 | 694.81 | 01-DEC-07:03 | 0.62 |
Annual Sum or Average | 0.368538E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214250E+09 | 0.07 | 694.81 | 0.62 |
Report: FanReportMonthly
For: CORE_MID PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 13881165.29 | 0.00 | 2129.01 | 02-JAN-06:30 | 0.62 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 13881165.29 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13881165.29 | 0.00 | 2129.01 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158723E+09 | 0.04 | 836.05 | 02-JAN-06:11 | 0.62 |
February | 55513749.10 | 0.02 | 836.05 | 01-FEB-06:12 | 0.62 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 2758966.45 | 0.00 | 836.05 | 22-NOV-07:03 | 0.62 |
December | 81615243.79 | 0.02 | 836.05 | 01-DEC-07:03 | 0.62 |
Annual Sum or Average | 0.298611E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158723E+09 | 0.04 | 836.05 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.222161E+09 | 0.08 | 684.35 | 02-JAN-06:11 | 0.62 |
February | 63850228.92 | 0.02 | 684.35 | 01-FEB-06:12 | 0.62 |
March | 444830.11 | 0.00 | 684.35 | 01-MAR-07:03 | 0.62 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 7219934.78 | 0.00 | 684.35 | 04-NOV-06:07 | 0.62 |
December | 0.155800E+09 | 0.05 | 684.35 | 01-DEC-07:03 | 0.62 |
Annual Sum or Average | 0.449476E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.222161E+09 | 0.08 | 684.35 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321783E+09 | 0.09 | 822.41 | 02-JAN-06:11 | 0.62 |
February | 89848172.88 | 0.03 | 822.41 | 01-FEB-06:12 | 0.62 |
March | 287843.12 | 0.00 | 822.41 | 01-MAR-07:03 | 0.62 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 9827786.42 | 0.00 | 822.41 | 20-NOV-07:03 | 0.62 |
December | 0.186991E+09 | 0.05 | 822.41 | 01-DEC-07:03 | 0.62 |
Annual Sum or Average | 0.608738E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.321783E+09 | 0.09 | 822.41 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.329728E+09 | 0.10 | 728.81 | 02-JAN-06:11 | 0.62 |
February | 0.110269E+09 | 0.04 | 728.81 | 01-FEB-06:12 | 0.62 |
March | 2915248.62 | 0.00 | 728.81 | 01-MAR-07:03 | 0.62 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 21791483.43 | 0.01 | 728.81 | 04-NOV-06:03 | 0.62 |
December | 0.224700E+09 | 0.07 | 728.81 | 01-DEC-06:47 | 0.62 |
Annual Sum or Average | 0.689404E+09 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.329728E+09 | 0.10 | 728.81 | 0.62 |
Report: FanReportMonthly
For: CORE_TOP PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.318237E+09 | 0.03 | 2597.46 | 02-JAN-06:11 | 0.62 |
February | 64676767.99 | 0.01 | 2597.46 | 01-FEB-07:03 | 0.62 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 1948095.42 | 0.00 | 2597.46 | 27-NOV-07:03 | 0.62 |
December | 0.149614E+09 | 0.01 | 2597.46 | 02-DEC-07:30 | 0.62 |
Annual Sum or Average | 0.534476E+09 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318237E+09 | 0.03 | 2597.46 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.393708E+09 | 0.09 | 986.98 | 02-JAN-06:05 | 0.62 |
February | 0.194683E+09 | 0.05 | 986.98 | 01-FEB-06:12 | 0.62 |
March | 32323713.31 | 0.01 | 986.98 | 01-MAR-06:40 | 0.62 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 3493921.99 | 0.00 | 986.98 | 28-OCT-06:05 | 0.62 |
November | 80498383.43 | 0.02 | 986.98 | 01-NOV-06:03 | 0.62 |
December | 0.323721E+09 | 0.08 | 986.98 | 01-DEC-06:13 | 0.62 |
Annual Sum or Average | 0.102843E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.393708E+09 | 0.09 | 986.98 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.394425E+09 | 0.12 | 734.69 | 01-JAN-05:50 | 0.62 |
February | 0.166444E+09 | 0.06 | 734.69 | 01-FEB-06:12 | 0.62 |
March | 25824319.80 | 0.01 | 734.69 | 01-MAR-06:17 | 0.62 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 8279945.49 | 0.00 | 734.69 | 21-OCT-06:03 | 0.62 |
November | 91872864.61 | 0.03 | 734.69 | 01-NOV-06:03 | 0.62 |
December | 0.346244E+09 | 0.11 | 734.69 | 01-DEC-06:13 | 0.62 |
Annual Sum or Average | 0.103309E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.394425E+09 | 0.12 | 734.69 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.653221E+09 | 0.15 | 976.83 | 01-JAN-05:50 | 0.62 |
February | 0.287872E+09 | 0.08 | 976.83 | 01-FEB-06:12 | 0.62 |
March | 43810903.58 | 0.01 | 976.83 | 01-MAR-06:20 | 0.62 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 10579087.75 | 0.00 | 976.83 | 27-OCT-06:03 | 0.62 |
November | 0.142051E+09 | 0.03 | 976.83 | 01-NOV-06:03 | 0.62 |
December | 0.562049E+09 | 0.13 | 976.83 | 01-DEC-06:13 | 0.62 |
Annual Sum or Average | 0.169958E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.653221E+09 | 0.15 | 976.83 | 0.62 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.567258E+09 | 0.16 | 825.59 | 02-JAN-06:03 | 0.62 |
February | 0.294820E+09 | 0.09 | 825.59 | 01-FEB-06:12 | 0.62 |
March | 68028966.74 | 0.02 | 825.59 | 01-MAR-06:17 | 0.62 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 20961838.17 | 0.01 | 825.59 | 21-OCT-06:03 | 0.62 |
November | 0.168892E+09 | 0.05 | 825.59 | 01-NOV-06:03 | 0.62 |
December | 0.496757E+09 | 0.14 | 825.59 | 01-DEC-06:13 | 0.62 |
Annual Sum or Average | 0.161672E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.567258E+09 | 0.16 | 825.59 | 0.62 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.398406E+10 | 0.47 | 5100.85 | 12-JAN-15:10 | 1.15 |
February | 0.444379E+10 | 0.52 | 7088.07 | 27-FEB-07:03 | 1.32 |
March | 0.685232E+10 | 0.62 | 9905.18 | 13-MAR-16:00 | 1.52 |
April | 0.854626E+10 | 0.71 | 11676.03 | 27-APR-04:01 | 1.63 |
May | 0.105900E+11 | 0.81 | 15323.36 | 04-MAY-04:02 | 1.83 |
June | 0.108640E+11 | 0.84 | 15323.36 | 03-JUN-04:01 | 1.83 |
July | 0.101854E+11 | 0.80 | 15323.36 | 07-JUL-04:01 | 1.83 |
August | 0.106308E+11 | 0.81 | 15323.36 | 02-AUG-04:01 | 1.83 |
September | 0.898108E+10 | 0.74 | 15323.36 | 01-SEP-04:01 | 1.83 |
October | 0.796429E+10 | 0.67 | 10216.30 | 06-OCT-15:40 | 1.54 |
November | 0.622765E+10 | 0.59 | 8658.23 | 13-NOV-15:50 | 1.44 |
December | 0.446819E+10 | 0.50 | 6226.38 | 01-DEC-15:10 | 1.25 |
Annual Sum or Average | 0.937378E+11 | 0.67 | |||
Minimum of Months | 0.398406E+10 | 0.47 | 5100.85 | 1.15 | |
Maximum of Months | 0.108640E+11 | 0.84 | 15323.36 | 1.83 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.322352E+10 | 0.45 | 3788.06 | 12-JAN-15:00 | 1.05 |
February | 0.352721E+10 | 0.49 | 5998.32 | 22-FEB-15:10 | 1.27 |
March | 0.584298E+10 | 0.60 | 9742.23 | 28-MAR-16:00 | 1.56 |
April | 0.800352E+10 | 0.70 | 14243.46 | 28-APR-04:01 | 1.84 |
May | 0.983684E+10 | 0.80 | 14378.13 | 02-MAY-04:01 | 1.84 |
June | 0.965524E+10 | 0.81 | 14378.13 | 03-JUN-04:01 | 1.84 |
July | 0.843038E+10 | 0.74 | 14378.13 | 10-JUL-04:02 | 1.84 |
August | 0.841703E+10 | 0.73 | 14378.13 | 02-AUG-04:01 | 1.84 |
September | 0.718691E+10 | 0.66 | 14378.13 | 01-SEP-04:01 | 1.84 |
October | 0.646507E+10 | 0.62 | 10082.96 | 02-OCT-16:00 | 1.58 |
November | 0.478118E+10 | 0.55 | 7397.80 | 09-NOV-15:05 | 1.39 |
December | 0.343891E+10 | 0.46 | 4750.59 | 01-DEC-14:30 | 1.16 |
Annual Sum or Average | 0.788088E+11 | 0.64 | |||
Minimum of Months | 0.322352E+10 | 0.45 | 3788.06 | 1.05 | |
Maximum of Months | 0.983684E+10 | 0.81 | 14378.13 | 1.84 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.343242E+10 | 0.42 | 3447.59 | 12-JAN-15:30 | 0.92 |
February | 0.358711E+10 | 0.46 | 5845.55 | 22-FEB-15:00 | 1.14 |
March | 0.584660E+10 | 0.55 | 10484.26 | 28-MAR-15:20 | 1.46 |
April | 0.828268E+10 | 0.65 | 14132.54 | 28-APR-04:01 | 1.67 |
May | 0.103321E+11 | 0.74 | 17801.63 | 18-MAY-04:01 | 1.83 |
June | 0.101765E+11 | 0.76 | 17801.63 | 16-JUN-04:01 | 1.83 |
July | 0.860081E+10 | 0.69 | 17801.63 | 12-JUL-04:01 | 1.82 |
August | 0.838680E+10 | 0.66 | 17801.63 | 02-AUG-04:01 | 1.83 |
September | 0.708778E+10 | 0.60 | 16592.71 | 05-SEP-04:01 | 1.77 |
October | 0.644452E+10 | 0.56 | 11341.36 | 02-OCT-15:40 | 1.51 |
November | 0.465274E+10 | 0.49 | 7216.44 | 09-NOV-14:10 | 1.24 |
December | 0.352003E+10 | 0.43 | 4265.45 | 01-DEC-14:50 | 1.01 |
Annual Sum or Average | 0.803501E+11 | 0.58 | |||
Minimum of Months | 0.343242E+10 | 0.42 | 3447.59 | 0.92 | |
Maximum of Months | 0.103321E+11 | 0.76 | 17801.63 | 1.83 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.50 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.61 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.72 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:02 | 2.06 | 2.06 | 57.98 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 58.29 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:02 | 2.06 | 2.06 | 58.40 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 58.45 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.47 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 58.47 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.78 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:02 | 2.06 | 2.06 | 58.01 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.75 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.61 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.78 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.50 | 58.50 | 1369.18 | 4991.59 | 17-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.11 | 58.11 | 1349.30 | 4961.58 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.19 | 58.19 | 1347.92 | 4749.25 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.35 | 58.35 | 1127.65 | 4301.50 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.85 | 58.85 | 1038.30 | 3854.02 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.71 | 58.71 | 958.58 | 3415.11 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 58.80 | 58.80 | 834.39 | 3149.66 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.82 | 58.82 | 955.10 | 3361.94 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.74 | 58.74 | 980.18 | 3750.11 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.99 | 57.99 | 1105.43 | 4259.50 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.39 | 58.39 | 1253.37 | 4684.49 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.22 | 58.22 | 1293.77 | 4939.69 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1133.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.99 | 57.99 | 834.39 | 3149.66 | ||
Maximum of Months | 0.00 | 0.00 | 58.85 | 58.85 | 1369.18 | 4991.59 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.135945E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.147420E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.235554E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.342832E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.494340E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.534694E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.517693E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.513637E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.416733E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.311689E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.205841E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142147E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.399852E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135945E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.534694E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.108644E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.117705E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.204840E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.313035E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.446521E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.468614E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.439647E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.419158E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.336643E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.253498E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163123E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110209E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.338164E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.108644E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.468614E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177313E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150818E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.229334E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.356057E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.506601E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.528102E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.478857E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.449518E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.358708E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.275068E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.182620E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.160707E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.385370E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150818E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.528102E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.471478E+10 | 0.303518E+11 | 0.127744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.471425E+10 | 0.392509E+11 | 0.512598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.688509E+10 | 0.670322E+11 | 36201799.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.854626E+10 | 0.917225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105900E+11 | 0.130182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108640E+11 | 0.145996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101854E+11 | 0.156590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106308E+11 | 0.158930E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.898108E+10 | 0.128831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.796570E+10 | 0.914698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.626928E+10 | 0.591191E+11 | 67404667.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473052E+10 | 0.359581E+11 | 0.624918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.950771E+11 | 0.113543E+13 | 0.251857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.471425E+10 | 0.303518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108640E+11 | 0.158930E+12 | 0.127744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.426979E+10 | 0.224261E+11 | 0.848067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384669E+10 | 0.316413E+11 | 0.100042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.584663E+10 | 0.583384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.800352E+10 | 0.828694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.983684E+10 | 0.117014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.965524E+10 | 0.128154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.843038E+10 | 0.134601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.841703E+10 | 0.131399E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.718691E+10 | 0.104678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.646507E+10 | 0.738107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.482278E+10 | 0.467035E+11 | 4291156.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408801E+10 | 0.266394E+11 | 0.197190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.808689E+11 | 0.958275E+12 | 0.114959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.384669E+10 | 0.224261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.983684E+10 | 0.134601E+12 | 0.848067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.575926E+10 | 0.270765E+11 | 0.503385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.459560E+10 | 0.361768E+11 | 0.150415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601659E+10 | 0.667052E+11 | 54500902.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.828268E+10 | 0.964509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103321E+11 | 0.134614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101765E+11 | 0.145881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.860081E+10 | 0.148176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.838680E+10 | 0.142900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.708778E+10 | 0.112999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.648783E+10 | 0.813322E+11 | 1182720.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.513800E+10 | 0.511033E+11 | 0.413015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.539841E+10 | 0.301334E+11 | 0.301668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.862624E+11 | 0.107355E+13 | 0.100234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.459560E+10 | 0.270765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103321E+11 | 0.148176E+12 | 0.503385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.471478E+10 | 0.00 | 0.00 | 0.00 | 0.760224E+10 | 0.127744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.471425E+10 | 0.00 | 0.00 | 0.00 | 0.951517E+10 | 0.512598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.688509E+10 | 0.00 | 0.00 | 0.00 | 0.166341E+11 | 36201799.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.854626E+10 | 0.00 | 0.00 | 0.00 | 0.257369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105900E+11 | 0.00 | 0.00 | 0.00 | 0.388439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108640E+11 | 0.00 | 0.00 | 0.00 | 0.426054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101854E+11 | 0.00 | 0.00 | 0.00 | 0.415839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106308E+11 | 0.00 | 0.00 | 0.00 | 0.407329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.898108E+10 | 0.00 | 0.00 | 0.00 | 0.326923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.796570E+10 | 0.00 | 0.00 | 0.00 | 0.232032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.626928E+10 | 0.00 | 0.00 | 0.00 | 0.142474E+11 | 67404667.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473052E+10 | 0.00 | 0.00 | 0.00 | 0.885921E+10 | 0.624918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.950771E+11 | 0.00 | 0.00 | 0.00 | 0.302257E+12 | 0.251857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.471425E+10 | 0.00 | 0.00 | 0.00 | 0.760224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108640E+11 | 0.00 | 0.00 | 0.00 | 0.426054E+11 | 0.127744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.426979E+10 | 0.00 | 0.00 | 0.00 | 0.574652E+10 | 0.848067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384669E+10 | 0.00 | 0.00 | 0.00 | 0.782377E+10 | 0.100042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.584663E+10 | 0.00 | 0.00 | 0.00 | 0.146374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.800352E+10 | 0.00 | 0.00 | 0.00 | 0.233000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.983684E+10 | 0.00 | 0.00 | 0.00 | 0.348152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.965524E+10 | 0.00 | 0.00 | 0.00 | 0.372062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.843038E+10 | 0.00 | 0.00 | 0.00 | 0.355343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.841703E+10 | 0.00 | 0.00 | 0.00 | 0.334988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.718691E+10 | 0.00 | 0.00 | 0.00 | 0.264774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.646507E+10 | 0.00 | 0.00 | 0.00 | 0.188848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.482278E+10 | 0.00 | 0.00 | 0.00 | 0.114852E+11 | 4291156.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408801E+10 | 0.00 | 0.00 | 0.00 | 0.673570E+10 | 0.197190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.808689E+11 | 0.00 | 0.00 | 0.00 | 0.256145E+12 | 0.114959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.384669E+10 | 0.00 | 0.00 | 0.00 | 0.574652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.983684E+10 | 0.00 | 0.00 | 0.00 | 0.372062E+11 | 0.848067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.575926E+10 | 0.00 | 0.00 | 0.00 | 0.693822E+10 | 0.503385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.459560E+10 | 0.00 | 0.00 | 0.00 | 0.898205E+10 | 0.150415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601659E+10 | 0.00 | 0.00 | 0.00 | 0.168623E+11 | 54500902.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.828268E+10 | 0.00 | 0.00 | 0.00 | 0.273230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103321E+11 | 0.00 | 0.00 | 0.00 | 0.403280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101765E+11 | 0.00 | 0.00 | 0.00 | 0.426337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.860081E+10 | 0.00 | 0.00 | 0.00 | 0.392849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.838680E+10 | 0.00 | 0.00 | 0.00 | 0.365650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.708778E+10 | 0.00 | 0.00 | 0.00 | 0.287830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.648783E+10 | 0.00 | 0.00 | 0.00 | 0.210178E+11 | 1182720.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.513800E+10 | 0.00 | 0.00 | 0.00 | 0.127110E+11 | 0.413015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.539841E+10 | 0.00 | 0.00 | 0.00 | 0.765556E+10 | 0.301668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.862624E+11 | 0.00 | 0.00 | 0.00 | 0.289085E+12 | 0.100234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.459560E+10 | 0.00 | 0.00 | 0.00 | 0.693822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103321E+11 | 0.00 | 0.00 | 0.00 | 0.426337E+11 | 0.503385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.937738E+09 | 3796856.82 | 0.00 | 37089696.29 | 530137.19 | 0.00 | 0.458145E+10 | 0.00 | 0.28 |
February | 0.318624E+09 | 42212412.37 | 0.00 | 37006608.51 | 12249748.83 | 0.00 | 0.292626E+10 | 0.00 | 0.30 |
March | 88510702.38 | 0.859944E+09 | 0.00 | 32867785.57 | 0.157316E+09 | 0.00 | 0.169835E+10 | 0.00 | 0.33 |
April | 29812192.17 | 0.341547E+10 | 0.00 | 6339702.57 | 0.818918E+09 | 0.00 | 96075080.14 | 0.00 | 0.31 |
May | 358504.18 | 0.973970E+10 | 0.00 | 103552.54 | 0.222281E+10 | 0.00 | 863787.27 | 0.00 | 0.33 |
June | 0.00 | 0.139556E+11 | 0.00 | 0.00 | 0.357879E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.171835E+11 | 0.00 | 0.00 | 0.636718E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.192589E+11 | 0.00 | 0.00 | 0.447409E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.138741E+11 | 0.00 | 0.00 | 0.309911E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 36109092.37 | 0.370744E+10 | 0.00 | 10361950.14 | 0.635930E+09 | 0.00 | 0.233326E+09 | 0.00 | 0.31 |
November | 0.154222E+09 | 0.163038E+09 | 0.00 | 41391716.46 | 83610105.40 | 0.00 | 0.204671E+10 | 0.00 | 0.31 |
December | 0.577888E+09 | 4131997.94 | 0.00 | 43344589.59 | 5288374.35 | 0.00 | 0.460563E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.214326E+10 | 0.822079E+11 | 0.00 | 0.208506E+09 | 0.214558E+11 | 0.00 | 0.161887E+11 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 3796856.82 | 0.00 | 0.00 | 530137.19 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.937738E+09 | 0.192589E+11 | 0.00 | 43344589.59 | 0.636718E+10 | 0.00 | 0.460563E+10 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.317518E+10 | 0.00 | 0.00 | 6594084.52 | 10982126.10 | 6802192.33 | 0.116897E+10 | 0.00 | 0.24 |
February | 0.116559E+10 | 15469897.66 | 0.00 | 13530034.85 | 60895112.31 | 0.00 | 0.120032E+10 | 0.00 | 0.25 |
March | 0.255233E+09 | 0.658958E+09 | 0.00 | 17539884.84 | 0.263504E+09 | 0.00 | 0.101802E+10 | 0.00 | 0.28 |
April | 31948292.45 | 0.271058E+10 | 0.00 | 4881449.07 | 0.813249E+09 | 0.00 | 83967012.12 | 0.00 | 0.28 |
May | 715698.86 | 0.842031E+10 | 0.00 | 54382.09 | 0.212957E+10 | 0.00 | 1494778.44 | 0.00 | 0.30 |
June | 0.00 | 0.123967E+11 | 0.00 | 0.00 | 0.324350E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.156590E+11 | 0.00 | 0.00 | 0.544780E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.177473E+11 | 0.00 | 0.00 | 0.337365E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.123228E+11 | 0.00 | 0.00 | 0.224858E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 56225680.11 | 0.324266E+10 | 0.00 | 3764780.08 | 0.537772E+09 | 0.00 | 84999778.75 | 0.00 | 0.27 |
November | 0.550445E+09 | 0.136974E+09 | 0.00 | 18114754.44 | 0.154846E+09 | 0.00 | 0.931850E+09 | 0.00 | 0.26 |
December | 0.224710E+10 | 0.00 | 0.00 | 11290663.56 | 29591290.40 | 0.00 | 0.155340E+10 | 0.00 | 0.24 |
Annual Sum or Average | 0.748243E+10 | 0.733108E+11 | 0.00 | 75770033.45 | 0.183139E+11 | 6802192.33 | 0.604303E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10982126.10 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.317518E+10 | 0.177473E+11 | 0.00 | 18114754.44 | 0.544780E+10 | 6802192.33 | 0.155340E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311865E+10 | 0.00 | 0.00 | 2687999.66 | 9553840.36 | 99057340.87 | 0.644683E+09 | 0.00 | 0.23 |
February | 0.127382E+10 | 5074445.13 | 0.00 | 8655360.96 | 0.106392E+09 | 4188701.34 | 0.800646E+09 | 0.00 | 0.25 |
March | 0.253500E+09 | 0.625625E+09 | 0.00 | 14530631.57 | 0.324432E+09 | 0.00 | 0.830362E+09 | 0.00 | 0.27 |
April | 20844964.25 | 0.252112E+10 | 0.00 | 6772504.17 | 0.838059E+09 | 0.00 | 0.115706E+09 | 0.00 | 0.28 |
May | 82286.97 | 0.808590E+10 | 0.00 | 19519.40 | 0.220713E+10 | 0.00 | 79783.71 | 0.00 | 0.31 |
June | 0.00 | 0.119041E+11 | 0.00 | 0.00 | 0.359619E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.151866E+11 | 0.00 | 0.00 | 0.580394E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.172460E+11 | 0.00 | 0.00 | 0.376387E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.116750E+11 | 0.00 | 0.00 | 0.274247E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 29711960.08 | 0.293821E+10 | 0.00 | 2455919.11 | 0.853334E+09 | 0.00 | 30909426.16 | 0.00 | 0.26 |
November | 0.544144E+09 | 0.125271E+09 | 0.00 | 12732104.98 | 0.261891E+09 | 0.00 | 0.593594E+09 | 0.00 | 0.25 |
December | 0.251835E+10 | 0.00 | 0.00 | 4472274.32 | 28229985.96 | 10316125.26 | 0.742056E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.775911E+10 | 0.703129E+11 | 0.00 | 52326314.16 | 0.205355E+11 | 0.113562E+09 | 0.375804E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9553840.36 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.311865E+10 | 0.172460E+11 | 0.00 | 14530631.57 | 0.580394E+10 | 99057340.87 | 0.830362E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100984E+10 | 0.00 | 0.00 | 30207.26 | 3592930.20 | 0.419082E+09 | 19996452.12 | 0.00 | 0.41 |
February | 0.512733E+09 | 0.00 | 29132.07 | 1107122.01 | 41889695.96 | 0.111455E+09 | 0.121500E+09 | 416.11 | 0.42 |
March | 0.156053E+09 | 0.164654E+09 | 0.00 | 3231293.68 | 0.174611E+09 | 1201096.56 | 0.193497E+09 | 0.00 | 0.44 |
April | 7935420.22 | 0.887188E+09 | 0.00 | 2239049.99 | 0.359016E+09 | 0.00 | 37478172.46 | 0.00 | 0.48 |
May | 41335.55 | 0.329187E+10 | 0.00 | 6822.00 | 0.707250E+09 | 0.00 | 20264.18 | 0.00 | 0.57 |
June | 0.00 | 0.505766E+10 | 0.00 | 0.00 | 0.109710E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.636173E+10 | 0.00 | 0.00 | 0.178212E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.655898E+10 | 0.00 | 0.00 | 0.128781E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.380120E+10 | 0.00 | 0.00 | 0.132402E+10 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 11394274.44 | 0.778840E+09 | 0.00 | 723951.02 | 0.527924E+09 | 4766.30 | 9340477.20 | 0.00 | 0.43 |
November | 0.254192E+09 | 17112157.62 | 0.00 | 2207046.96 | 0.125048E+09 | 19465791.31 | 0.115776E+09 | 0.00 | 0.41 |
December | 0.943294E+09 | 0.00 | 0.00 | 55381.80 | 10616502.42 | 0.258581E+09 | 20144978.94 | 0.00 | 0.42 |
Annual Sum or Average | 0.289548E+10 | 0.269192E+11 | 29132.07 | 9600874.70 | 0.744100E+10 | 0.809790E+09 | 0.517754E+09 | 416.11 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3592930.20 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.100984E+10 | 0.655898E+10 | 29132.07 | 3231293.68 | 0.178212E+10 | 0.419082E+09 | 0.193497E+09 | 416.11 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.845071E+09 | 0.00 | 0.00 | 68160.16 | 2702293.89 | 0.213533E+09 | 31102406.92 | 0.00 | 0.49 |
February | 0.335722E+09 | 0.00 | 22036.30 | 1709382.98 | 31505835.93 | 56268817.42 | 0.173620E+09 | 187.31 | 0.51 |
March | 83986472.37 | 0.165721E+09 | 0.00 | 3400967.31 | 0.115052E+09 | 647158.11 | 0.189623E+09 | 0.00 | 0.57 |
April | 3917832.54 | 0.874791E+09 | 0.00 | 1972289.67 | 0.207109E+09 | 0.00 | 33533002.82 | 0.00 | 0.65 |
May | 40908.51 | 0.268685E+10 | 0.00 | 2937.20 | 0.512507E+09 | 0.00 | 7330.35 | 0.00 | 0.73 |
June | 0.00 | 0.376222E+10 | 0.00 | 0.00 | 0.880540E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.462238E+10 | 0.00 | 0.00 | 0.137219E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.472458E+10 | 0.00 | 0.00 | 0.995258E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.297584E+10 | 0.00 | 0.00 | 0.951583E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 8355912.03 | 0.706802E+09 | 0.00 | 545078.17 | 0.347002E+09 | 3584.80 | 7047793.94 | 0.00 | 0.55 |
November | 0.155950E+09 | 36388654.55 | 0.00 | 2480838.50 | 74505118.85 | 9050430.52 | 0.130192E+09 | 0.00 | 0.50 |
December | 0.725066E+09 | 1930.00 | 0.00 | 138734.14 | 7982892.41 | 0.138400E+09 | 55535175.07 | 0.00 | 0.50 |
Annual Sum or Average | 0.215811E+10 | 0.205556E+11 | 22036.30 | 10318388.13 | 0.549794E+10 | 0.417903E+09 | 0.620660E+09 | 187.31 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2702293.89 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.845071E+09 | 0.472458E+10 | 22036.30 | 3400967.31 | 0.137219E+10 | 0.213533E+09 | 0.189623E+09 | 187.31 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.725689E+09 | 2385607.47 | 0.00 | 5826340.94 | 1244662.80 | 0.249370E+09 | 0.703035E+09 | 0.00 | 0.49 |
February | 0.367208E+09 | 11597799.26 | 0.00 | 6957981.77 | 30757096.96 | 76041682.26 | 0.504930E+09 | 0.00 | 0.53 |
March | 0.115028E+09 | 0.285749E+09 | 0.00 | 6934969.72 | 0.113913E+09 | 730229.85 | 0.363572E+09 | 0.00 | 0.57 |
April | 7808465.43 | 0.111300E+10 | 0.00 | 3053855.47 | 0.317601E+09 | 0.00 | 51048947.12 | 0.00 | 0.56 |
May | 41765.14 | 0.340130E+10 | 0.00 | 6775.70 | 0.704735E+09 | 0.00 | 20580.85 | 0.00 | 0.58 |
June | 0.00 | 0.499519E+10 | 0.00 | 0.00 | 0.112904E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.638281E+10 | 0.00 | 0.00 | 0.181414E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.692854E+10 | 0.00 | 0.00 | 0.124544E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.459432E+10 | 0.00 | 0.00 | 0.123386E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 11516865.77 | 0.135595E+10 | 0.00 | 1425922.28 | 0.370538E+09 | 0.00 | 16074566.48 | 0.00 | 0.60 |
November | 0.176202E+09 | 0.114057E+09 | 0.00 | 9980506.09 | 73026835.39 | 6662032.09 | 0.404299E+09 | 0.00 | 0.61 |
December | 0.613769E+09 | 5529411.62 | 0.00 | 6222372.75 | 5835480.97 | 0.164871E+09 | 0.675244E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.201726E+10 | 0.291904E+11 | 0.00 | 40408724.74 | 0.704013E+10 | 0.497675E+09 | 0.271822E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 2385607.47 | 0.00 | 0.00 | 1244662.80 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.725689E+09 | 0.692854E+10 | 0.00 | 9980506.09 | 0.181414E+10 | 0.249370E+09 | 0.703035E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.734415E+09 | 0.00 | 0.00 | 643912.59 | 3036656.59 | 0.324203E+09 | 0.167359E+09 | 0.00 | 0.55 |
February | 0.388872E+09 | 4521382.46 | 116864.28 | 1698230.15 | 30789544.55 | 96809961.40 | 0.163689E+09 | 1326.89 | 0.58 |
March | 0.130382E+09 | 0.147522E+09 | 102970.17 | 3290136.02 | 0.145478E+09 | 1616235.66 | 0.196021E+09 | 618.79 | 0.62 |
April | 6864676.65 | 0.791881E+09 | 0.00 | 2148407.60 | 0.283653E+09 | 0.00 | 34117897.14 | 0.00 | 0.66 |
May | 45970.24 | 0.261479E+10 | 0.00 | 3463.61 | 0.654088E+09 | 0.00 | 8074.37 | 0.00 | 0.74 |
June | 0.00 | 0.379502E+10 | 0.00 | 0.00 | 0.107344E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 0.00 | 0.455785E+10 | 0.00 | 0.00 | 0.167040E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.469654E+10 | 0.00 | 0.00 | 0.131052E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.293828E+10 | 0.00 | 0.00 | 0.123212E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 9620419.68 | 0.628147E+09 | 81778.80 | 778727.19 | 0.479090E+09 | 13233.93 | 10143933.37 | 610.23 | 0.58 |
November | 0.210426E+09 | 20207341.64 | 45442.48 | 2647162.92 | 0.102233E+09 | 17711292.57 | 0.120188E+09 | 479.90 | 0.58 |
December | 0.687570E+09 | 0.00 | 0.00 | 780223.25 | 8972807.76 | 0.208764E+09 | 0.138602E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.216820E+10 | 0.201948E+11 | 347055.74 | 11990263.34 | 0.699382E+10 | 0.649118E+09 | 0.830128E+09 | 3035.81 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3036656.59 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.734415E+09 | 0.469654E+10 | 116864.28 | 3290136.02 | 0.167040E+10 | 0.324203E+09 | 0.196021E+09 | 1326.89 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125552E+10 | 0.00 | 0.00 | 18200.50 | 1331556.96 | 0.162597E+09 | 8952039.58 | 0.00 | 0.33 |
February | 0.658576E+09 | 0.00 | 0.00 | 708778.74 | 15259199.59 | 18768331.33 | 65999337.63 | 0.00 | 0.32 |
March | 0.226148E+09 | 0.144426E+09 | 0.00 | 1899245.41 | 94812762.81 | 0.00 | 0.123873E+09 | 0.00 | 0.32 |
April | 20336182.38 | 0.837513E+09 | 0.00 | 550040.01 | 0.307474E+09 | 0.00 | 8047501.56 | 0.00 | 0.37 |
May | 181583.19 | 0.293199E+10 | 0.00 | 6415.69 | 0.715940E+09 | 0.00 | 210772.19 | 0.00 | 0.48 |
June | 0.00 | 0.466078E+10 | 0.00 | 0.00 | 0.103902E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.592701E+10 | 0.00 | 0.00 | 0.173290E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.618894E+10 | 0.00 | 0.00 | 0.126151E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.373748E+10 | 0.00 | 0.00 | 0.111492E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 43259498.14 | 0.869714E+09 | 0.00 | 726336.48 | 0.232370E+09 | 0.00 | 14221302.07 | 0.00 | 0.35 |
November | 0.353223E+09 | 27399518.79 | 0.00 | 2265114.63 | 33645096.08 | 0.00 | 0.108986E+09 | 0.00 | 0.30 |
December | 0.118737E+10 | 0.00 | 0.00 | 102677.67 | 2886147.01 | 21458731.37 | 26490216.83 | 0.00 | 0.32 |
Annual Sum or Average | 0.374462E+10 | 0.253253E+11 | 0.00 | 6276809.13 | 0.655206E+10 | 0.202824E+09 | 0.356780E+09 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1331556.96 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.125552E+10 | 0.618894E+10 | 0.00 | 2265114.63 | 0.173290E+10 | 0.162597E+09 | 0.123873E+09 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106206E+10 | 0.00 | 0.00 | 112541.58 | 1095681.76 | 57027346.33 | 55093632.22 | 0.00 | 0.43 |
February | 0.461304E+09 | 0.00 | 0.00 | 1620961.90 | 12556148.35 | 2988080.20 | 0.155158E+09 | 0.00 | 0.42 |
March | 0.133507E+09 | 0.134514E+09 | 0.00 | 3144557.72 | 70830352.80 | 0.00 | 0.170249E+09 | 0.00 | 0.45 |
April | 12827974.19 | 0.807278E+09 | 0.00 | 932659.47 | 0.215419E+09 | 0.00 | 15498865.37 | 0.00 | 0.54 |
May | 184972.51 | 0.249807E+10 | 0.00 | 3809.37 | 0.540662E+09 | 0.00 | 139349.93 | 0.00 | 0.65 |
June | 0.00 | 0.354547E+10 | 0.00 | 0.00 | 0.879212E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.434366E+10 | 0.00 | 0.00 | 0.142236E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.444922E+10 | 0.00 | 0.00 | 0.103896E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.285266E+10 | 0.00 | 0.00 | 0.921382E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 32842189.19 | 0.727840E+09 | 0.00 | 1104275.46 | 0.180118E+09 | 0.00 | 19749974.97 | 0.00 | 0.48 |
November | 0.244490E+09 | 25255760.10 | 0.00 | 3318616.41 | 25057682.63 | 0.00 | 0.151962E+09 | 0.00 | 0.41 |
December | 0.867755E+09 | 0.00 | 0.00 | 489112.56 | 2374888.00 | 6140895.83 | 0.142894E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.281497E+10 | 0.193840E+11 | 0.00 | 10726534.46 | 0.531002E+10 | 66156322.36 | 0.710746E+09 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1095681.76 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.106206E+10 | 0.444922E+10 | 0.00 | 3318616.41 | 0.142236E+10 | 57027346.33 | 0.170249E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.936530E+09 | 1231236.61 | 0.00 | 4352952.21 | 157318.40 | 0.201786E+09 | 0.446108E+09 | 0.00 | 0.38 |
February | 0.456091E+09 | 9672131.10 | 0.00 | 6013497.91 | 6156555.55 | 82051715.03 | 0.358182E+09 | 0.00 | 0.41 |
March | 0.151403E+09 | 0.346133E+09 | 0.00 | 5766367.04 | 36857616.83 | 22645327.08 | 0.283834E+09 | 0.00 | 0.47 |
April | 20591903.80 | 0.143276E+10 | 0.00 | 966220.29 | 0.237090E+09 | 0.00 | 12821910.43 | 0.00 | 0.53 |
May | 113979.07 | 0.411101E+10 | 0.00 | 21665.58 | 0.660379E+09 | 0.00 | 273447.27 | 0.00 | 0.61 |
June | 0.00 | 0.597539E+10 | 0.00 | 0.00 | 0.105387E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.728300E+10 | 0.00 | 0.00 | 0.172419E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.796283E+10 | 0.00 | 0.00 | 0.116225E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.548774E+10 | 0.00 | 0.00 | 0.947817E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 41059961.44 | 0.168998E+10 | 0.00 | 1618482.73 | 0.148316E+09 | 0.00 | 25351146.77 | 0.00 | 0.57 |
November | 0.215847E+09 | 0.106274E+09 | 0.00 | 11090646.25 | 10852498.62 | 30715898.92 | 0.414415E+09 | 0.00 | 0.52 |
December | 0.788957E+09 | 2210026.82 | 0.00 | 5940821.69 | 1310786.45 | 0.115690E+09 | 0.526574E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.261059E+10 | 0.344082E+11 | 0.00 | 35770653.71 | 0.598925E+10 | 0.452888E+09 | 0.206756E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 1231236.61 | 0.00 | 0.00 | 157318.40 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.936530E+09 | 0.796283E+10 | 0.00 | 11090646.25 | 0.172419E+10 | 0.201786E+09 | 0.526574E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100248E+10 | 0.00 | 0.00 | 609751.12 | 1157716.37 | 0.122914E+09 | 0.116013E+09 | 0.00 | 0.45 |
February | 0.541245E+09 | 4464313.30 | 0.00 | 1353962.17 | 8802730.99 | 13376756.97 | 0.101180E+09 | 0.00 | 0.45 |
March | 0.193277E+09 | 0.158970E+09 | 0.00 | 2044460.25 | 67177507.85 | 0.00 | 0.128668E+09 | 0.00 | 0.47 |
April | 17731531.03 | 0.863329E+09 | 0.00 | 413045.37 | 0.203038E+09 | 0.00 | 6459025.17 | 0.00 | 0.54 |
May | 157876.71 | 0.256544E+10 | 0.00 | 4364.41 | 0.541737E+09 | 0.00 | 184976.85 | 0.00 | 0.65 |
June | 0.00 | 0.376435E+10 | 0.00 | 0.00 | 0.850593E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 0.00 | 0.435118E+10 | 0.00 | 0.00 | 0.147895E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.447599E+10 | 0.00 | 0.00 | 0.112532E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.297350E+10 | 0.00 | 0.00 | 0.925656E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 38329758.61 | 0.764800E+09 | 0.00 | 436797.04 | 0.184312E+09 | 0.00 | 11010679.48 | 0.00 | 0.48 |
November | 0.303521E+09 | 30161024.89 | 0.00 | 2241164.17 | 28425924.58 | 0.00 | 0.108867E+09 | 0.00 | 0.44 |
December | 0.945663E+09 | 422552.33 | 0.00 | 874908.99 | 2086795.56 | 15112873.54 | 0.115839E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.304240E+10 | 0.199526E+11 | 0.00 | 7978453.52 | 0.541726E+10 | 0.151404E+09 | 0.588222E+09 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1157716.37 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.100248E+10 | 0.447599E+10 | 0.00 | 2241164.17 | 0.147895E+10 | 0.122914E+09 | 0.128668E+09 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134283E+10 | 0.00 | 0.00 | 73733.93 | 4242246.50 | 0.279522E+09 | 26029370.87 | 0.00 | 0.42 |
February | 0.685666E+09 | 4599.65 | 0.00 | 1256494.85 | 29494168.96 | 42561127.23 | 0.109496E+09 | 0.00 | 0.42 |
March | 0.221928E+09 | 0.216025E+09 | 0.00 | 2951437.19 | 0.116043E+09 | 0.00 | 0.182109E+09 | 0.00 | 0.43 |
April | 21167244.74 | 0.103867E+10 | 0.00 | 1161253.72 | 0.345900E+09 | 0.00 | 17018765.29 | 0.00 | 0.48 |
May | 348837.38 | 0.366476E+10 | 0.00 | 11763.20 | 0.698551E+09 | 0.00 | 506069.90 | 0.00 | 0.59 |
June | 0.00 | 0.557764E+10 | 0.00 | 0.00 | 0.104140E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.683607E+10 | 0.00 | 0.00 | 0.175477E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.695205E+10 | 0.00 | 0.00 | 0.119311E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.418478E+10 | 0.00 | 0.00 | 0.104942E+10 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 42891156.13 | 0.942634E+09 | 0.00 | 336218.03 | 0.333540E+09 | 0.00 | 5858293.76 | 0.00 | 0.41 |
November | 0.390088E+09 | 27299487.70 | 0.00 | 2218340.39 | 76734150.52 | 1353194.83 | 0.102463E+09 | 0.00 | 0.40 |
December | 0.128715E+10 | 0.00 | 0.00 | 122085.98 | 11430714.52 | 79006776.01 | 35600649.10 | 0.00 | 0.41 |
Annual Sum or Average | 0.399208E+10 | 0.294399E+11 | 0.00 | 8131327.30 | 0.665464E+10 | 0.402443E+09 | 0.479081E+09 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4242246.50 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.134283E+10 | 0.695205E+10 | 0.00 | 2951437.19 | 0.175477E+10 | 0.279522E+09 | 0.182109E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118947E+10 | 0.00 | 0.00 | 76849.27 | 3530115.47 | 0.137931E+09 | 44264482.27 | 0.00 | 0.56 |
February | 0.523813E+09 | 0.00 | 0.00 | 1588121.37 | 24546913.82 | 10480011.17 | 0.168765E+09 | 0.00 | 0.55 |
March | 0.149568E+09 | 0.175198E+09 | 0.00 | 3241697.87 | 0.103438E+09 | 195270.44 | 0.190228E+09 | 0.00 | 0.59 |
April | 13212169.39 | 0.942272E+09 | 0.00 | 1397209.73 | 0.245644E+09 | 0.00 | 22063323.58 | 0.00 | 0.67 |
May | 551991.12 | 0.289405E+10 | 0.00 | 4136.80 | 0.590486E+09 | 0.00 | 155047.30 | 0.00 | 0.76 |
June | 0.00 | 0.399758E+10 | 0.00 | 0.00 | 0.989590E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 0.00 | 0.481702E+10 | 0.00 | 0.00 | 0.154865E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.486321E+10 | 0.00 | 0.00 | 0.104565E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 0.00 | 0.304130E+10 | 0.00 | 0.00 | 0.990134E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 33422823.31 | 0.745981E+09 | 0.00 | 489795.01 | 0.291134E+09 | 0.00 | 7946808.25 | 0.00 | 0.55 |
November | 0.290598E+09 | 33199943.59 | 0.00 | 2397754.71 | 54677396.77 | 1616420.18 | 0.123174E+09 | 0.00 | 0.53 |
December | 0.106894E+10 | 7327.50 | 0.00 | 210478.38 | 9504553.08 | 25720259.55 | 71944746.84 | 0.00 | 0.55 |
Annual Sum or Average | 0.326957E+10 | 0.215098E+11 | 0.00 | 9406043.14 | 0.589699E+10 | 0.175943E+09 | 0.628541E+09 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3530115.47 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.118947E+10 | 0.486321E+10 | 0.00 | 3241697.87 | 0.154865E+10 | 0.137931E+09 | 0.190228E+09 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102882E+10 | 3382225.88 | 0.00 | 7123404.35 | 930903.77 | 0.138729E+09 | 0.811108E+09 | 0.00 | 0.54 |
February | 0.555589E+09 | 17706797.80 | 0.00 | 7227378.26 | 13057055.93 | 15594996.14 | 0.480199E+09 | 0.00 | 0.56 |
March | 0.180259E+09 | 0.373393E+09 | 0.00 | 6430734.82 | 61881652.49 | 0.00 | 0.349628E+09 | 0.00 | 0.58 |
April | 21518351.92 | 0.139044E+10 | 0.00 | 1599745.99 | 0.270764E+09 | 0.00 | 22958439.58 | 0.00 | 0.58 |
May | 354623.65 | 0.381052E+10 | 0.00 | 10849.43 | 0.701652E+09 | 0.00 | 514842.42 | 0.00 | 0.61 |
June | 0.00 | 0.548989E+10 | 0.00 | 0.00 | 0.110057E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.688741E+10 | 0.00 | 0.00 | 0.177842E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.740608E+10 | 0.00 | 0.00 | 0.112854E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.518144E+10 | 0.00 | 0.00 | 0.935000E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 42127711.90 | 0.168628E+10 | 0.00 | 717116.24 | 0.194272E+09 | 0.00 | 10055571.24 | 0.00 | 0.61 |
November | 0.301135E+09 | 0.151171E+09 | 0.00 | 9590680.41 | 25269556.38 | 501234.63 | 0.391962E+09 | 0.00 | 0.63 |
December | 0.911372E+09 | 9681707.05 | 0.00 | 7435487.93 | 4623653.90 | 27441539.20 | 0.791338E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.304118E+10 | 0.324074E+11 | 0.00 | 40135397.43 | 0.621498E+10 | 0.182267E+09 | 0.285776E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 3382225.88 | 0.00 | 0.00 | 930903.77 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.102882E+10 | 0.740608E+10 | 0.00 | 9590680.41 | 0.177842E+10 | 0.138729E+09 | 0.811108E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105474E+10 | 0.00 | 0.00 | 789108.24 | 3759444.72 | 0.251885E+09 | 0.158485E+09 | 0.00 | 0.60 |
February | 0.585426E+09 | 7050199.88 | 0.00 | 1686354.82 | 19138022.86 | 40666971.33 | 0.134761E+09 | 0.00 | 0.60 |
March | 0.200670E+09 | 0.207555E+09 | 0.00 | 2741272.34 | 98244420.58 | 545587.04 | 0.181133E+09 | 0.00 | 0.63 |
April | 19001497.20 | 0.100981E+10 | 0.00 | 996045.08 | 0.247320E+09 | 0.00 | 13702426.78 | 0.00 | 0.70 |
May | 634460.30 | 0.307924E+10 | 0.00 | 4570.89 | 0.613165E+09 | 0.00 | 119108.57 | 0.00 | 0.79 |
June | 0.00 | 0.436208E+10 | 0.00 | 0.00 | 0.100992E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
July | 0.00 | 0.498953E+10 | 0.00 | 0.00 | 0.166759E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.511609E+10 | 0.00 | 0.00 | 0.117431E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.327547E+10 | 0.00 | 0.00 | 0.106211E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 38858469.37 | 0.802972E+09 | 0.00 | 274170.74 | 0.321856E+09 | 0.00 | 5176370.76 | 0.00 | 0.58 |
November | 0.350230E+09 | 35683746.95 | 0.00 | 2300586.92 | 61534040.87 | 1721892.49 | 0.100975E+09 | 0.00 | 0.58 |
December | 0.104125E+10 | 886364.57 | 0.00 | 938728.75 | 9243442.67 | 74319578.69 | 0.132106E+09 | 0.00 | 0.59 |
Annual Sum or Average | 0.329081E+10 | 0.228864E+11 | 0.00 | 9730837.78 | 0.628819E+10 | 0.369139E+09 | 0.726458E+09 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3759444.72 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.105474E+10 | 0.511609E+10 | 0.00 | 2741272.34 | 0.166759E+10 | 0.251885E+09 | 0.181133E+09 | 0.00 | 0.80 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.240891E+12 | 0.418950E+10 | 0.00 | 0.625538E+11 | 0.100141E+12 |
February | 0.265518E+12 | 0.263504E+10 | 0.00 | 0.337574E+11 | 0.133390E+12 |
March | 0.353160E+12 | 0.342088E+09 | 0.00 | 0.618900E+10 | 0.240210E+12 |
April | 0.385926E+12 | -0.350496E+10 | 0.00 | -0.379070E+11 | 0.347403E+12 |
May | 0.406688E+12 | -0.998405E+10 | 0.00 | -0.102833E+12 | 0.495797E+12 |
June | 0.370151E+12 | -0.122121E+11 | 0.00 | -0.155156E+12 | 0.542476E+12 |
July | 0.302015E+12 | -0.173451E+11 | 0.00 | -0.210388E+12 | 0.555770E+12 |
August | 0.258187E+12 | -0.159474E+11 | 0.00 | -0.212368E+12 | 0.544027E+12 |
September | 0.285286E+12 | -0.102410E+11 | 0.00 | -0.158569E+12 | 0.434460E+12 |
October | 0.286934E+12 | -0.270654E+10 | 0.00 | -0.377602E+11 | 0.309718E+12 |
November | 0.255104E+12 | 0.934358E+09 | 0.00 | 0.195908E+11 | 0.195370E+12 |
December | 0.221231E+12 | 0.366642E+10 | 0.00 | 0.558363E+11 | 0.115981E+12 |
Annual Sum or Average | 0.363109E+13 | -0.601738E+11 | 0.00 | -0.737053E+12 | 0.401474E+13 |
Minimum of Months | 0.221231E+12 | -0.173451E+11 | 0.00 | -0.212368E+12 | 0.100141E+12 |
Maximum of Months | 0.406688E+12 | 0.418950E+10 | 0.00 | 0.625538E+11 | 0.555770E+12 |