Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2024-07-03 12:20:10
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3327.22 | 667.82 | 667.82 |
Net Site Energy | 3327.22 | 667.82 | 667.82 |
Total Source Energy | 7693.41 | 1544.18 | 1544.18 |
Net Source Energy | 7693.41 | 1544.18 | 1544.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1365.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 139.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 235.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 63.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1961.93 | 1365.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1365.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 139.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 235.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 193.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 63.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1365.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 139.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 235.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 193.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 6.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 63.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 81.00 | 274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 393.79 | 274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 81.00 | 274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 393.79 | 274.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1961.931 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1961.931 | 100.00 |
Total On-Site and Utility Electric Sources | 1961.931 | 100.00 |
Total Electricity End Uses | 1961.931 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 634.33 |
Time Setpoint Not Met During Occupied Cooling | 33.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3392.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-JUL-10:39 | 09-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 434518.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85456.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32080.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5390.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 215724.10 | 434518.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 434518.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 85456.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 32080.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 5390.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1479.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 442.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 745.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 612.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 200.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6213.44 | 1479.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 123.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 40.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1247.13 | 297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 123.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 40.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1247.13 | 297.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.51 | 0.213439 | 0.300000 | 1.05 | 0.569170 | 0.500000 | 0.001785 | 0.000188 | 1.05 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.88 | 0.259835 | 0.300000 | 0.865304 | 0.692894 | 0.500000 | 0.001466 | 0.000355 | 1.77 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 3.83 | 0.195497 | 0.300000 | 1.15 | 0.521325 | 0.500000 | 0.001949 | 0.000763 | 3.83 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.77 | 0.089454 | 0.300000 | 0.529856 | 0.300000 | 0.500000 | 0.004259 | 0.000351 | 1.77 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.15 | 0.086616 | 0.300000 | 0.346431 | 0.300000 | 0.500000 | 0.004399 | 0.000229 | 1.15 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.79 | 0.088312 | 0.300000 | 0.536704 | 0.300000 | 0.500000 | 0.004314 | 0.000355 | 1.79 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.24 | 0.080851 | 0.300000 | 0.371107 | 0.300000 | 0.500000 | 0.004712 | 0.000233 | 1.17 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.37 | 0.114973 | 0.300000 | 0.412249 | 0.306595 | 0.500000 | 0.003314 | 0.000273 | 1.37 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.904106 | 0.110631 | 0.300000 | 0.271232 | 0.300000 | 0.500000 | 0.003444 | 0.000180 | 0.904106 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.40 | 0.113123 | 0.300000 | 0.418993 | 0.301660 | 0.500000 | 0.003368 | 0.000278 | 1.40 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.940856 | 0.106302 | 0.300000 | 0.282257 | 0.300000 | 0.500000 | 0.003584 | 0.000183 | 0.918815 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 1.34 | 0.118010 | 0.300000 | 0.401641 | 0.314693 | 0.500000 | 0.003229 | 0.000266 | 1.34 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 1.10 | 0.300000 | 0.500000 | 0.004192 | 0.000176 | 0.883363 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.36 | 0.116162 | 0.300000 | 0.408030 | 0.309765 | 0.500000 | 0.003280 | 0.000270 | 1.36 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.14 | 0.087650 | 0.300000 | 0.342321 | 0.300000 | 0.500000 | 0.004347 | 0.000179 | 0.898437 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21456.87 | 0.000188 | 487.23 |
CORE_MID VAV BOX REHEAT COIL | 40522.39 | 0.000355 | 947.75 |
CORE_TOP VAV BOX REHEAT COIL | 87229.69 | 0.000763 | 2038.02 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 40114.52 | 0.000351 | 936.76 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 26226.57 | 0.000229 | 612.44 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 40632.35 | 0.000355 | 948.84 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 26585.50 | 0.000233 | 620.81 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 31221.53 | 0.000273 | 729.16 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 20540.31 | 0.000180 | 479.70 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 31731.39 | 0.000278 | 741.06 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 20873.92 | 0.000183 | 487.48 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 30419.81 | 0.000266 | 710.44 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 20069.97 | 0.000176 | 468.72 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 30902.88 | 0.000270 | 721.72 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 20411.86 | 0.000179 | 476.70 |
PACU_VAV_BOT HEATING COIL | 45158.44 | 0.000395 | 724.71 |
PACU_VAV_MID HEATING COIL | 45070.34 | 0.000394 | 723.87 |
PACU_VAV_TOP HEATING COIL | 39217.25 | 0.000343 | 663.77 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 4.06 | 2.44 | 8.13 | 5.44 | 6.22 | 6.22 | 0.300000 | 0.874491 | 6.22 |
PACU_VAV_MID | 3.91 | 2.35 | 7.82 | 6.25 | 6.02 | 6.25 | 0.300000 | 1.00 | 6.25 |
PACU_VAV_TOP | 4.89 | 2.93 | 9.78 | 9.71 | 7.24 | 9.71 | 0.300000 | 1.00 | 9.71 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.22 |
PACU_VAV_MID_OA_CONTROLLER | 6.25 |
PACU_VAV_TOP_OA_CONTROLLER | 9.71 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.22 | 114716.20 | 0.800094 | 2.07 | 38234.91 | 0.800094 |
PACU_VAV_MID COOLING COIL | 6.25 | 116301.56 | 0.800315 | 2.08 | 38763.31 | 0.800315 |
PACU_VAV_TOP COOLING COIL | 9.71 | 175387.58 | 0.800084 | 3.24 | 58456.68 | 0.800084 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.22 |
PACU_VAV_MID FAN | 6.25 |
PACU_VAV_TOP FAN | 9.71 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000395 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000394 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000343 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.005410 | 0.649189 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.005410 | 1629.23 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 618385.58 | 618385.58 | 0.005410 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
43 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
44 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
45 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
46 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
47 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
48 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
49 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
50 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
51 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
52 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
53 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
54 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
55 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
56 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
57 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
58 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
59 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
60 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
61 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
62 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
63 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
64 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
65 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.49 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.49 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40284.13684 | 46326.75737 | 3.05333 | 3.51133 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9122.48927 | 11403.11158 | 0.67789 | 0.84736 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 33116.01174 | 38083.41350 | 2.50813 | 2.88435 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18871.52998 | 23589.41248 | 1.41935 | 1.77418 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 36779.58541 | 42296.52322 | 2.81092 | 3.23255 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 40513.26169 | 50641.57711 | 3.06687 | 3.83359 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10725.87609 | 12334.75750 | 0.81978 | 0.94275 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 18610.81614 | 23263.52017 | 1.41295 | 1.76619 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 12502.14808 | 14377.47029 | 0.95553 | 1.09886 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 12167.30571 | 15209.13214 | 0.92382 | 1.15477 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 17016.47854 | 19568.95032 | 1.30056 | 1.49564 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 18850.79613 | 23563.49516 | 1.43121 | 1.78901 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 14074.11214 | 16185.22896 | 1.07567 | 1.23702 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 12333.64675 | 15417.05844 | 0.93647 | 1.17059 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7585.98935 | 8723.88776 | 0.57978 | 0.66675 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 14487.37021 | 18109.21277 | 1.09933 | 1.37416 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9849.24478 | 11326.63150 | 0.75275 | 0.86566 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.33400 | 1.27158E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 9530.65628 | 11913.32035 | 0.72329 | 0.90411 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12842.61188 | 14769.00367 | 0.98153 | 1.12876 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 14723.62803 | 18404.53504 | 1.11731 | 1.39664 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10704.76344 | 12310.47795 | 0.81814 | 0.94086 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 26.50400 | 1.27196E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 9685.24852 | 12106.56065 | 0.73505 | 0.91882 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8955.20311 | 10298.48358 | 0.68444 | 0.78711 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 14117.21619 | 17646.52024 | 1.07104 | 1.33880 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 12520.20328 | 14398.23377 | 0.95690 | 1.10044 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 22.88733 | 1.27133E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 9313.59841 | 11641.99802 | 0.70669 | 0.88336 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 15362.59903 | 17666.98889 | 1.17414 | 1.35027 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.68667 | 1.27251E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 14341.06428 | 17926.33035 | 1.08808 | 1.36010 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 12982.51319 | 14929.89016 | 0.99223 | 1.14107 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 9472.03335 | 11840.04169 | 0.71875 | 0.89844 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 86912.45 | 6.22200 | 6.22200 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 50341.25 | 5.44109 | 5.44109 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 84339.48 | 6.02482 | 6.02482 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 50372.22 | 6.25489 | 6.25489 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 99933.02 | 7.24099 | 7.24099 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 48374.41 | 9.71415 | 9.71415 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.51133 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21344 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.05340 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56917 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78505E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.87714E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.05340 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21456.87245 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87714E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 487.22765 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.88435 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25984 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.86530 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69289 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46631E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.54508E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.77418 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40522.38956 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.54508E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 947.75477 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.83359 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19550 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15008 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52133 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94888E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.63123E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.83359 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 87229.68902 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.63123E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2038.02339 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.76619 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.94536E-002 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.52986 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.25919E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.50939E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.76619 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40114.52393 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.50939E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 936.75549 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15477 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.66163E-002 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34643 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.39871E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.29441E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15477 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26226.57211 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.29441E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 612.43628 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.78901 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.83122E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.53670 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.31424E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55470E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78901 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40632.34846 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55470E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 948.84349 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23702 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.08515E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37111 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.71234E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.32582E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17059 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26585.49635 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32582E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 620.81497 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37416 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11497 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41225 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30659 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31382E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.73140E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.37416 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31221.53266 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73140E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 729.15630 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90411 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11063 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27123 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44389E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.79696E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90411 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20540.30558 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79696E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 479.69516 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39664 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11312 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41899 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30166 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36803E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.77600E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.39664 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31731.38736 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.77600E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 741.05786 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94086 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10630 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28226 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.58411E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82614E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.91882 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20873.91980 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82614E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 487.48275 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33880 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11801 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40164 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31469 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22855E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.66126E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.33880 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30419.81078 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66126E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 710.44359 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10044 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.19174E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.75581E-004 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.88336 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20069.96549 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.75581E-004 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 468.71695 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36010 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11616 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40803 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30976 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27991E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70352E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.36010 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30902.87727 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70352E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 721.71978 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14107 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.76504E-002 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34232 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.34681E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.78572E-004 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.89844 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20411.86389 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78572E-004 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 476.69791 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.06355 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.43813 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.12710 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.44109 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.22200 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.22200 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.87449 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.91238 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.34743 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.82475 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 6.25489 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.02482 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 6.25489 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.89029 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.93417 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.78058 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 9.71415 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.24099 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 9.71415 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.22200 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 6.25489 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 9.71415 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.22200 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.22200 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 114716.20180 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80009 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.07379 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38234.91006 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80009 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 45158.43733 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.95066E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 724.70811 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.22200 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.95066E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.25489 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.25489 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 116301.56139 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80031 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.08475 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38763.31041 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80031 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 45070.33543 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.94295E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 723.87434 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 6.25489 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.94295E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.71415 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 9.71415 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 175387.58213 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80008 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 3.23773 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 58456.68113 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80008 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 39217.24849 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.43090E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 663.77285 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 9.71415 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.43090E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.40991E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.64919 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.40991E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1629.22635 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 618385.57595 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 618385.58000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.40991E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20360.49 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 38444.47 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 82757.07 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 38057.77 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24881.88 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 38549.05 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 25222.41 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 29620.73 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 19487.16 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 30104.44 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 19803.67 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 28860.11 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 19040.93 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 29318.41 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 19365.30 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 32941.51 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 32932.50 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 31885.63 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 113289.72 | 386560.57 | 11.40 | 2.92 | 3.26 | 3.43 | 3.62 | 9.97 | 11.13 | 11.71 | 12.37 | 6.8962 | 5.4930 | 3.6934 | 1.4766 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 114896.43 | 392042.90 | 11.41 | 2.93 | 3.27 | 3.44 | 3.63 | 9.99 | 11.14 | 11.72 | 12.39 | 6.9326 | 5.5304 | 3.7208 | 1.4791 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 173050.89 | 590474.14 | 11.35 | 2.91 | 3.25 | 3.42 | 3.61 | 9.94 | 11.08 | 11.66 | 12.30 | 10.7667 | 8.5550 | 5.7461 | 2.3231 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.49 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.49 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.49 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.49 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.49 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.49 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.49 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.49 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.49 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.49 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.1261260316E-002 | 4.1483088908E-002 | Pass | Pass | 0.4869495407 | 0.4963600985 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.5046882422 | 0.4203273800 | Pass | Pass | 0.4897434340 | 0.4960742857 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1569336455 | 9.8866379767E-002 | Pass | Pass | 0.4850128289 | 0.4874275043 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1274959797 | 8.0875294336E-002 | Pass | Pass | 0.4788201383 | 0.4855503537 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.2667436410E-002 | 2.6255676399E-002 | Pass | Pass | 0.6834156246 | 1.1692021843 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2569398144 | 0.2762991807 | Pass | Pass | 0.6015093422 | 0.6149602113 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.1617977075 | 1.0898576768 | Pass | Pass | 0.5852052676 | 0.5494225396 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.0751599936 | 1.0504994967 | Pass | Pass | 0.5943614710 | 0.5528332897 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7960091188 | 0.9420019433 | Pass | Pass | 0.6014382577 | 0.5795003237 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.1160512663 | 1.0964983215 | Pass | Pass | 0.5929575059 | 0.5513575777 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.9275451973 | 0.8667049600 | Pass | Pass | 0.6003660413 | 0.5591734192 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8108554171 | 0.8019225172 | Pass | Pass | 0.6222239165 | 0.5660228309 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5069947859 | 0.6024205277 | Pass | Pass | 0.6466491546 | 0.6275151710 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8531759575 | 0.8426171654 | Pass | Pass | 0.6167097295 | 0.5635819519 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.9163718455 | 0.8494891457 | Pass | Pass | 0.6209563897 | 0.5452038982 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8270622447 | 0.8322962816 | Pass | Pass | 0.6324287037 | 0.5594972908 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6113488617 | 0.6929250982 | Pass | Pass | 0.7251719715 | 1.0552209931 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8682861920 | 0.8690457938 | Pass | Pass | 0.6285692279 | 0.5559517185 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3495.84 | 195.25 | 0.00 | 2544.47 | 1179.60 | 7415.17 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.49 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.491 | 0.541 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.49 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.491 | 0.541 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.491 | 0.541 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.49 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.491 | 0.541 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.49 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.49 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.49 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.49 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.49 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.491 | 0.541 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.49 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.491 | 0.541 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.49 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.491 | 0.541 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.49 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.491 | 0.541 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.49 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.491 | 0.541 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 3.241 | 0.491 | 0.541 | |||||||||||||||||
North Total or Average | 183.92 | 3.241 | 0.491 | 0.541 | |||||||||||||||||
Non-North Total or Average | 429.15 | 3.241 | 0.491 | 0.541 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.52 | 83.52 | 235.37 | |
Exterior Lighting Total | 15013.15 | 235.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 618385.58 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 114716.20 | 91783.73 | 22932.47 | 0.80 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 116301.56 | 93077.87 | 23223.69 | 0.80 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 175387.58 | 140324.75 | 35062.83 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 113289.7 | 2.92 | 9.97 | N/A | N/A | 11.40 | |
PACU_VAV_MID COOLING COIL | 114896.4 | 2.93 | 9.99 | N/A | N/A | 11.41 | |
PACU_VAV_TOP COOLING COIL | 173050.9 | 2.91 | 9.94 | N/A | N/A | 11.35 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 21456.87 | 20360.49 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 40522.39 | 38444.47 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 87229.69 | 82757.07 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 40114.52 | 38057.77 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 26226.57 | 24881.88 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40632.35 | 38549.05 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 26585.50 | 25222.41 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 31221.53 | 29620.73 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 20540.31 | 19487.16 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31731.39 | 30104.44 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 20873.92 | 19803.67 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 30419.81 | 28860.11 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 20069.97 | 19040.93 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30902.88 | 29318.41 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 20411.86 | 19365.30 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 45158.44 | 32941.51 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 45070.34 | 32932.50 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 39217.25 | 31885.63 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1337.13 | 6.22 | 13762.83 | 2211.96 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1337.13 | 6.25 | 13835.56 | 2211.96 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 9.71 | 21349.57 | 2197.78 | 1.00 | 1.12 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.005410 | 1629.23 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 113289.72 | 2.92 | 9.97 | 11.40 | 6.8962 | 3.26 | 11.13 | 5.4930 | 3.43 | 11.71 | 3.6934 | 3.62 | 12.37 | 1.4766 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 114896.43 | 2.93 | 9.99 | 11.41 | 6.9326 | 3.27 | 11.14 | 5.5304 | 3.44 | 11.72 | 3.7208 | 3.63 | 12.39 | 1.4791 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 173050.89 | 2.91 | 9.94 | 11.35 | 10.7667 | 3.25 | 11.08 | 8.5550 | 3.42 | 11.66 | 5.7461 | 3.61 | 12.30 | 2.3231 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40284.14 | 46326.76 | 47.10 | 3.053 | 3.511 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 20.92 | 0.01271 | 0.425 | 0.00 |
CORE_MID | 33116.01 | 38083.41 | 38.72 | 2.508 | 2.884 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 20.92 | 0.01271 | 0.425 | 0.00 |
CORE_TOP | 36779.59 | 42296.52 | 43.00 | 2.811 | 3.233 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00882 | 29.98 | 0.01273 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10725.88 | 12334.76 | 59.49 | 0.820 | 0.943 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00889 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 12502.15 | 14377.47 | 109.53 | 0.956 | 1.099 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00872 | 23.63 | 0.01271 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17016.48 | 19568.95 | 94.38 | 1.301 | 1.496 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00875 | 29.79 | 0.01273 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 14074.11 | 16185.23 | 123.31 | 1.076 | 1.237 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00870 | 28.16 | 0.01272 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7585.99 | 8723.89 | 42.08 | 0.580 | 0.667 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00895 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9849.24 | 11326.63 | 86.29 | 0.753 | 0.866 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00873 | 24.33 | 0.01272 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12842.61 | 14769.00 | 71.23 | 0.982 | 1.129 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00877 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10704.76 | 12310.48 | 93.79 | 0.818 | 0.941 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00871 | 26.50 | 0.01272 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8955.20 | 10298.48 | 49.67 | 0.684 | 0.787 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00894 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 12520.20 | 14398.23 | 109.69 | 0.957 | 1.100 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00871 | 22.89 | 0.01271 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 15362.60 | 17666.99 | 85.21 | 1.174 | 1.350 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00876 | 29.69 | 0.01273 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 12982.51 | 14929.89 | 113.75 | 0.992 | 1.141 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00870 | 27.95 | 0.01272 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9122.49 | 11403.11 | 11.59 | 0.678 | 0.847 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
CORE_MID | 18871.53 | 23589.41 | 23.98 | 1.419 | 1.774 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
CORE_TOP | 40513.26 | 50641.58 | 51.49 | 3.067 | 3.834 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 18610.82 | 23263.52 | 112.20 | 1.413 | 1.766 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 12167.31 | 15209.13 | 115.87 | 0.924 | 1.155 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 18850.80 | 23563.50 | 113.65 | 1.431 | 1.789 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12333.65 | 15417.06 | 117.46 | 0.936 | 1.171 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 14487.37 | 18109.21 | 87.34 | 1.099 | 1.374 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9530.66 | 11913.32 | 90.76 | 0.723 | 0.904 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 14723.63 | 18404.54 | 88.77 | 1.117 | 1.397 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9685.25 | 12106.56 | 92.24 | 0.735 | 0.919 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 14117.22 | 17646.52 | 85.11 | 1.071 | 1.339 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9313.60 | 11642.00 | 88.69 | 0.707 | 0.883 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14341.06 | 17926.33 | 86.46 | 1.088 | 1.360 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9472.03 | 11840.04 | 90.21 | 0.719 | 0.898 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -32.70 | 0.00018 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.22 | 6.22 | 5.44 | 5.44 | 6.2220 | 5.4411 | 6.2220 | 0.8745 | 0.3000 |
PACU_VAV_MID | 6.02 | 6.02 | 6.25 | 6.25 | 6.0248 | 6.2549 | 6.2549 | 1.0000 | 0.3000 |
PACU_VAV_TOP | 7.24 | 7.24 | 9.71 | 9.71 | 7.2410 | 9.7141 | 9.7141 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21456.872 | 21456.872 | 1.053400 | 0.00018771 | 487.228 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21456.87 | 21456.87 | 1.053400 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 11403.11 | 0.00 | 21557.75 | 21557.75 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 40522.390 | 40522.390 | 1.774184 | 0.00035451 | 947.755 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40522.39 | 40522.39 | 1.774184 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 23589.41 | 0.00 | 40708.08 | 40708.08 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 87229.689 | 87229.689 | 3.833587 | 0.00076312 | 2038.023 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87229.69 | 86708.83 | 3.833587 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 50641.58 | 0.00 | 87629.58 | 87629.58 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 40114.524 | 40114.524 | 1.766186 | 0.00035094 | 936.755 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40114.52 | 39947.93 | 1.766186 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00787543 | 48.8001 | 23263.52 | 0.00 | 40298.46 | 40298.46 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 26226.572 | 26226.572 | 1.154769 | 0.00022944 | 612.436 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26226.57 | 26118.79 | 1.154769 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00787296 | 48.7851 | 15209.13 | 0.00 | 26346.83 | 26346.83 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 40632.348 | 40632.348 | 1.789014 | 0.00035547 | 948.843 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40632.35 | 40464.26 | 1.789014 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00787700 | 48.8097 | 23563.50 | 0.00 | 40818.66 | 40818.66 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 26585.496 | 26585.496 | 1.170592 | 0.00023258 | 620.815 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26585.50 | 26585.50 | 1.170592 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00787465 | 48.7954 | 15417.06 | 0.00 | 26707.40 | 26707.40 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 31221.533 | 31221.533 | 1.374163 | 0.00027314 | 729.156 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31221.53 | 31081.08 | 1.374163 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00791533 | 49.0431 | 18109.21 | 0.00 | 31364.69 | 31364.69 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 20540.306 | 20540.306 | 0.904106 | 0.00017970 | 479.695 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20540.31 | 20449.26 | 0.904106 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00791416 | 49.0360 | 11913.32 | 0.00 | 20634.48 | 20634.48 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 31731.387 | 31731.387 | 1.396642 | 0.00027760 | 741.058 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31731.39 | 31589.52 | 1.396642 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00791667 | 49.0513 | 18404.54 | 0.00 | 31876.88 | 31876.88 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 20873.920 | 20873.920 | 0.918815 | 0.00018261 | 487.483 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20873.92 | 20873.92 | 0.918815 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00791551 | 49.0442 | 12106.56 | 0.00 | 20969.63 | 20969.63 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 30419.811 | 30419.811 | 1.338802 | 0.00026613 | 710.444 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30419.81 | 30281.28 | 1.338802 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786418 | 48.7309 | 17646.52 | 0.00 | 30559.29 | 30559.29 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 20069.965 | 20069.965 | 0.883363 | 0.00017558 | 468.717 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20069.97 | 20069.97 | 0.883363 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786270 | 48.7219 | 11642.00 | 0.00 | 20161.99 | 20161.99 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 30902.877 | 30902.877 | 1.360100 | 0.00027035 | 721.720 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30902.88 | 30763.02 | 1.360100 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786626 | 48.7437 | 17926.33 | 0.00 | 31044.57 | 31044.57 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 20411.864 | 20411.864 | 0.898437 | 0.00017857 | 476.698 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20411.86 | 20411.86 | 0.898437 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786495 | 48.7357 | 11840.04 | 0.00 | 20505.45 | 20505.45 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 114716.202 | 91783.730 | 6.222004 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 115696.52 | 99282.40 | 6.222004 | 24.94 | 17.05 | 0.00942610 | 11.01 | 10.98 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 15.3664 | 24.00 | 0.00882695 | 45.5138 | 70788.79 | 0.00 | 118287.80 | 91048.49 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 45158.437 | 45158.437 | 1.866601 | 0.00039507 | 724.708 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 45158.44 | 45158.44 | 1.866601 | -7.98 | -7.98 | 0.00390662 | 12.89 | 11.26 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 51.2214 | 18.66 | 0.00790557 | 56.6397 | 8777.28 | 0.00 | 39856.45 | 39856.45 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 116301.561 | 93077.875 | 6.254886 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 117402.49 | 100011.68 | 6.254886 | 24.97 | 17.10 | 0.00947619 | 11.01 | 10.98 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 15.2857 | 24.00 | 0.00886287 | 45.6968 | 68516.15 | 0.00 | 119922.52 | 92348.33 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 45070.335 | 45070.335 | 1.876466 | 0.00039429 | 723.874 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 45070.34 | 45070.34 | 1.876466 | -7.83 | -7.83 | 0.00387726 | 12.89 | 11.26 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 50.9522 | 18.00 | 0.00786767 | 58.7554 | 8695.04 | 0.00 | 39845.39 | 39845.39 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 175387.582 | 140324.749 | 9.714147 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 176509.54 | 153511.86 | 9.714147 | 24.81 | 16.93 | 0.00933138 | 11.03 | 10.99 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 9.8423 | 24.00 | 0.00881430 | 45.4500 | 82288.70 | 0.00 | 180848.14 | 139206.07 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 39217.248 | 39217.248 | 2.914244 | 0.00034309 | 663.773 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39217.25 | 39217.25 | 2.914244 | 1.28 | 1.28 | 0.00524003 | 12.89 | 11.26 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 32.8078 | 16.34 | 0.00788388 | 65.3858 | 14077.59 | 0.00 | 38597.50 | 38597.50 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 21456.872 | 21456.872 | 1.053400 | 0.00018771 | 487.228 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 3.4014 | 3.469821 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21456.87 | 21456.87 | 1.0000 | 1.21554456 | 1.053400 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.18769493 | 60.00 | 32.22 | 27.78 | 0.000 | 21456.87 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.85 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 11403.11 | 0.00 | 21557.75 | 21557.75 | 1.21554456 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.19 | 18.10 | 0.00800000 | 50794.9 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 40522.390 | 40522.390 | 1.774184 | 0.00035451 | 947.755 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 6.4237 | 6.552933 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40522.39 | 40522.39 | 1.0000 | 2.04727510 | 1.774184 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.35447138 | 60.00 | 32.22 | 27.78 | 0.000 | 40522.39 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 23589.41 | 0.00 | 40708.08 | 40708.08 | 2.04727510 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.30 | 18.79 | 0.00800000 | 52943.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 87229.689 | 87229.689 | 3.833587 | 0.00076312 | 2038.023 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 13.8277 | 14.106036 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 87229.69 | 86708.83 | 1.0000 | 4.42367165 | 3.833587 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.76304553 | 60.00 | 32.22 | 27.78 | 0.000 | 87229.69 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 50641.58 | 0.00 | 87629.58 | 87629.58 | 4.42367165 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52869.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40114.524 | 40114.524 | 1.766186 | 0.00035094 | 936.755 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 6.3590 | 6.486976 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40114.52 | 39947.93 | 1.0000 | 2.03804542 | 1.766186 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.35090356 | 60.00 | 32.22 | 27.78 | 0.000 | 40114.52 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00787543 | 21.00 | 0.00787543 | 48.8001 | 23263.52 | 0.00 | 40298.46 | 40298.46 | 2.03804542 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52832.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26226.572 | 26226.572 | 1.154769 | 0.00022944 | 612.436 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 4.1575 | 4.241136 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26226.57 | 26118.79 | 1.0000 | 1.33251651 | 1.154769 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.22941809 | 60.00 | 32.22 | 27.78 | 0.000 | 26226.57 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00787296 | 21.00 | 0.00787296 | 48.7851 | 15209.13 | 0.00 | 26346.83 | 26346.83 | 1.33251651 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52832.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40632.348 | 40632.348 | 1.789014 | 0.00035547 | 948.843 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 6.4411 | 6.570714 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40632.35 | 40464.26 | 1.0000 | 2.06438721 | 1.789014 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.35543325 | 60.00 | 32.22 | 27.78 | 0.000 | 40632.35 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00787700 | 21.00 | 0.00787700 | 48.8097 | 23563.50 | 0.00 | 40818.66 | 40818.66 | 2.06438721 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52832.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26585.496 | 26585.496 | 1.170592 | 0.00023258 | 620.815 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 4.2144 | 4.299178 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26585.50 | 26585.50 | 1.0000 | 1.35077486 | 1.170592 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.23255779 | 60.00 | 32.22 | 27.78 | 0.000 | 26585.50 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00787465 | 21.00 | 0.00787465 | 48.7954 | 15417.06 | 0.00 | 26707.40 | 26707.40 | 1.35077486 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52831.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31221.533 | 31221.533 | 1.374163 | 0.00027314 | 729.156 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 4.9493 | 5.048878 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31221.53 | 31081.08 | 1.0000 | 1.58568029 | 1.374163 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.27311172 | 60.00 | 32.22 | 27.78 | 0.000 | 31221.53 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00791533 | 21.00 | 0.00791533 | 49.0431 | 18109.21 | 0.00 | 31364.69 | 31364.69 | 1.58568029 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52839.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20540.306 | 20540.306 | 0.904106 | 0.00017970 | 479.695 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 3.2561 | 3.321602 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20540.31 | 20449.26 | 1.0000 | 1.04327082 | 0.904106 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.17967722 | 60.00 | 32.22 | 27.78 | 0.000 | 20540.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00791416 | 21.00 | 0.00791416 | 49.0360 | 11913.32 | 0.00 | 20634.48 | 20634.48 | 1.04327082 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31731.387 | 31731.387 | 1.396642 | 0.00027760 | 741.058 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 5.0301 | 5.131327 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31731.39 | 31589.52 | 1.0000 | 1.61161973 | 1.396642 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.27757170 | 60.00 | 32.22 | 27.78 | 0.000 | 31731.39 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00791667 | 21.00 | 0.00791667 | 49.0513 | 18404.54 | 0.00 | 31876.88 | 31876.88 | 1.61161973 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52839.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20873.920 | 20873.920 | 0.918815 | 0.00018261 | 487.483 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 3.3090 | 3.375551 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20873.92 | 20873.92 | 1.0000 | 1.06024369 | 0.918815 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.18259553 | 60.00 | 32.22 | 27.78 | 0.000 | 20873.92 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00791551 | 21.00 | 0.00791551 | 49.0442 | 12106.56 | 0.00 | 20969.63 | 20969.63 | 1.06024369 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30419.811 | 30419.811 | 1.338802 | 0.00026613 | 710.444 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 4.8222 | 4.919230 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30419.81 | 30281.28 | 1.0000 | 1.54487674 | 1.338802 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.26609863 | 60.00 | 32.22 | 27.78 | 0.000 | 30419.81 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00786418 | 21.00 | 0.00786418 | 48.7309 | 17646.52 | 0.00 | 30559.29 | 30559.29 | 1.54487674 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52840.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20069.965 | 20069.965 | 0.883363 | 0.00017558 | 468.717 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 3.1815 | 3.245542 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20069.97 | 20069.97 | 1.0000 | 1.01933427 | 0.883363 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.17556290 | 60.00 | 32.22 | 27.78 | 0.000 | 20069.97 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00786270 | 21.00 | 0.00786270 | 48.7219 | 11642.00 | 0.00 | 20161.99 | 20161.99 | 1.01933427 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52839.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30902.877 | 30902.877 | 1.360100 | 0.00027035 | 721.720 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 4.8988 | 4.997348 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30902.88 | 30763.02 | 1.0000 | 1.56945367 | 1.360100 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.27032427 | 60.00 | 32.22 | 27.78 | 0.000 | 30902.88 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00786626 | 21.00 | 0.00786626 | 48.7437 | 17926.33 | 0.00 | 31044.57 | 31044.57 | 1.56945367 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52840.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20411.864 | 20411.864 | 0.898437 | 0.00017857 | 476.698 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 3.2357 | 3.300831 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20411.86 | 20411.86 | 1.0000 | 1.03672866 | 0.898437 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.17855367 | 60.00 | 32.22 | 27.78 | 0.000 | 20411.86 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.94 | 0.00786495 | 21.00 | 0.00786495 | 48.7357 | 11840.04 | 0.00 | 20505.45 | 20505.45 | 1.03672866 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.8 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 114716.202 | 91783.730 | 6.222004 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3626 | 1004.8586 | 1.1539 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.222004 | 7.17972492 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 115696.52 | 99282.40 | 1.0085 | 7.17972492 | 6.222004 | 24.94 | 17.05 | 0.00942610 | 49068.0 | 11.01 | 10.98 | 0.00850000 | 32499.3 | -999.0 | -999.00 | -999.00 | -999.00 | 13762.826 | 101933.69 | 30.10 | 0.01272586 | 21.13 | 0.95610000 | 15.3664 | 24.00 | 0.00882695 | 24.00 | 0.00882695 | 45.5138 | 70788.79 | 0.00 | 118287.80 | 91048.49 | 6.89618006 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.76 | 13.59 | 0.00963599 | 38169.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 45158.437 | 45158.437 | 1.866601 | 0.00039507 | 724.708 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.222004 | 7.17972492 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 7.1586 | 7.302634 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 45158.44 | 45158.44 | 1.0000 | 2.15391748 | 1.866601 | -7.98 | -7.98 | 0.00390662 | 1698.3 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 0.39502541 | 60.00 | 32.22 | 27.78 | 0.000 | 45158.44 | -32.70 | 0.00018338 | -32.70 | 0.95610000 | 51.2214 | 17.99 | 0.00781633 | 18.66 | 0.00790557 | 56.6397 | 8777.28 | 0.00 | 39856.45 | 39856.45 | 2.15391748 | 2.80 | 1.82 | 0.00390662 | 12604.1 | 21.08 | 10.86 | 0.00390662 | 31108.3 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 116301.561 | 93077.875 | 6.254886 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.4558 | 1004.8586 | 1.1539 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.254886 | 7.21766844 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 117402.49 | 100011.68 | 1.0095 | 7.21766844 | 6.254886 | 24.97 | 17.10 | 0.00947619 | 49227.2 | 11.01 | 10.98 | 0.00850000 | 32499.4 | -999.0 | -999.00 | -999.00 | -999.00 | 13835.560 | 103566.93 | 30.10 | 0.01272586 | 21.13 | 0.95610000 | 15.2857 | 24.00 | 0.00886287 | 24.00 | 0.00886287 | 45.6968 | 68516.15 | 0.00 | 119922.52 | 92348.33 | 6.93262510 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.64 | 13.54 | 0.00962519 | 38024.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 45070.335 | 45070.335 | 1.876466 | 0.00039429 | 723.874 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.254886 | 7.21766844 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 7.1446 | 7.288387 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 45070.34 | 45070.34 | 1.0000 | 2.16530053 | 1.876466 | -7.83 | -7.83 | 0.00387726 | 1777.2 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 0.39425473 | 60.00 | 32.22 | 27.78 | 0.000 | 45070.34 | -32.70 | 0.00018338 | -32.70 | 0.95610000 | 50.9522 | 18.02 | 0.00771457 | 18.00 | 0.00786767 | 58.7554 | 8695.04 | 0.00 | 39845.39 | 39845.39 | 2.16530053 | 2.80 | 1.77 | 0.00387726 | 12530.5 | 20.98 | 10.79 | 0.00387726 | 30932.3 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 175387.582 | 140324.749 | 9.714147 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1866 | 1004.8586 | 1.1539 | PACU_VAV_TOP FAN | Fan:VariableVolume | 9.714147 | 11.20939565 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 176509.54 | 153511.86 | 1.0064 | 11.20939565 | 9.714147 | 24.81 | 16.93 | 0.00933138 | 48692.6 | 11.03 | 10.99 | 0.00850000 | 32511.2 | -999.0 | -999.00 | -999.00 | -999.00 | 21349.568 | 155159.97 | 30.10 | 0.01272586 | 21.13 | 0.95610000 | 9.8423 | 24.00 | 0.00881430 | 24.00 | 0.00881430 | 45.4500 | 82288.70 | 0.00 | 180848.14 | 139206.07 | 10.76670925 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.03 | 13.73 | 0.00966823 | 38525.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 39217.248 | 39217.248 | 2.914244 | 0.00034309 | 663.773 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_TOP FAN | Fan:VariableVolume | 9.714147 | 11.20939565 | 4197.9300 | 999.8980 | 5.40935492 | 54.44 | 82.22 | 27.78 | 630830.83 | 6.2168 | 6.341876 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39217.25 | 39217.25 | 1.0000 | 3.36281869 | 2.914244 | 1.28 | 1.28 | 0.00524003 | 14407.0 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 0.34305460 | 60.00 | 32.22 | 27.78 | 0.000 | 39217.25 | -32.70 | 0.00018338 | -32.70 | 0.95610000 | 32.8078 | 17.88 | 0.00770904 | 16.34 | 0.00788388 | 65.3858 | 14077.59 | 0.00 | 38597.50 | 38597.50 | 3.36281869 | 2.80 | 2.80 | 0.00524003 | 15945.8 | 14.11 | 9.23 | 0.00524003 | 27423.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.22 | - | |||
PACU_VAV_MID_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.25 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | FixedDryBulb | 0.00 | 9.71 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2238.83 | 3257.50 | 442.67 |
CORE_MID | 2684.83 | 4009.17 | 1394.67 |
CORE_TOP | 3215.33 | 4616.17 | 2334.33 |
PERIMETER_TOP_ZN_3 | 3589.50 | 5107.83 | 3010.50 |
PERIMETER_TOP_ZN_2 | 3790.00 | 4622.33 | 2781.00 |
PERIMETER_TOP_ZN_1 | 3460.67 | 4576.33 | 2463.50 |
PERIMETER_TOP_ZN_4 | 3710.50 | 4807.33 | 2856.17 |
PERIMETER_BOT_ZN_3 | 3410.83 | 5295.83 | 3042.50 |
PERIMETER_BOT_ZN_2 | 3764.83 | 4550.33 | 2705.83 |
PERIMETER_BOT_ZN_1 | 3458.83 | 4721.33 | 2537.83 |
PERIMETER_BOT_ZN_4 | 3675.17 | 4692.67 | 2759.50 |
PERIMETER_MID_ZN_3 | 3580.67 | 4726.33 | 2682.67 |
PERIMETER_MID_ZN_2 | 3106.17 | 3814.00 | 2180.17 |
PERIMETER_MID_ZN_1 | 3367.00 | 4180.83 | 2086.17 |
PERIMETER_MID_ZN_4 | 3545.50 | 4611.83 | 2528.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5355.83 | 5442.00 | 3392.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.33 | 0.00 | 2.33 | 0.00 |
CORE_MID | 10.00 | 0.00 | 9.00 | 0.00 |
CORE_TOP | 29.33 | 0.00 | 15.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 278.33 | 0.00 | 88.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 278.00 | 4.67 | 82.67 | 4.67 |
PERIMETER_TOP_ZN_1 | 227.67 | 5.17 | 60.33 | 5.17 |
PERIMETER_TOP_ZN_4 | 269.17 | 10.67 | 81.33 | 6.33 |
PERIMETER_BOT_ZN_3 | 146.17 | 0.00 | 58.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 132.50 | 0.50 | 44.00 | 0.50 |
PERIMETER_BOT_ZN_1 | 610.50 | 2.00 | 545.17 | 2.00 |
PERIMETER_BOT_ZN_4 | 132.17 | 4.50 | 48.17 | 2.00 |
PERIMETER_MID_ZN_3 | 150.33 | 0.00 | 53.00 | 0.00 |
PERIMETER_MID_ZN_2 | 141.00 | 7.67 | 38.33 | 7.67 |
PERIMETER_MID_ZN_1 | 109.50 | 9.33 | 31.33 | 9.33 |
PERIMETER_MID_ZN_4 | 139.83 | 11.67 | 40.33 | 7.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 959.67 | 40.67 | 634.33 | 33.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.895 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.647 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.687 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 1.416 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.622 | 0.090 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 1.583 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.691 | 0.090 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 1.184 | 0.046 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 1.352 | 0.048 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 1.336 | 0.875 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 1.359 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 1.219 | 0.072 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 1.647 | 0.080 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 1.463 | 0.072 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.746 | 0.075 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.86 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14286355.08 | 0.00 | 14286355.08 | 0.00 | 14286355.08 | 13393058.27 | 6257.93 | 36.08 | 2466.00 | 435.67 |
CORE_MID | 10337747.65 | 0.00 | 10337747.65 | 0.00 | 10337747.65 | 13393058.27 | 6727.13 | 27.31 | 2005.57 | 426.41 |
CORE_TOP | 10920634.99 | 0.00 | 10920634.99 | 0.00 | 10920634.99 | 13393058.27 | 6525.13 | 23.52 | 2211.35 | 56.35 |
PERIMETER_TOP_ZN_3 | 4763842.37 | 0.00 | 4763842.37 | 554487.21 | 5318329.58 | 2823374.22 | 4168.32 | 5.65 | 4586.02 | 56.35 |
PERIMETER_TOP_ZN_2 | 3443246.90 | 0.00 | 3443246.90 | 369655.91 | 3812902.81 | 1787429.43 | 4154.20 | 1.14 | 4604.66 | 56.35 |
PERIMETER_TOP_ZN_1 | 5309764.05 | 0.00 | 5309764.05 | 554487.21 | 5864251.26 | 2823374.22 | 4155.04 | 1.51 | 4603.45 | 56.35 |
PERIMETER_TOP_ZN_4 | 3595709.49 | 0.00 | 3595709.49 | 369655.91 | 3965365.41 | 1787312.18 | 4150.60 | 1.37 | 4608.03 | 56.35 |
PERIMETER_BOT_ZN_3 | 4046393.44 | 0.00 | 4046393.44 | 294816.05 | 4341209.49 | 2823374.22 | 4343.81 | 9.43 | 4406.76 | 435.67 |
PERIMETER_BOT_ZN_2 | 2911354.39 | 0.00 | 2911354.39 | 196542.85 | 3107897.25 | 1787429.43 | 4136.09 | 12.93 | 4610.98 | 435.67 |
PERIMETER_BOT_ZN_1 | 4553209.40 | 0.00 | 4553209.40 | 3086506.81 | 7639716.22 | 2823374.22 | 4088.87 | 6.27 | 4664.86 | 435.67 |
PERIMETER_BOT_ZN_4 | 2930343.97 | 0.00 | 2930343.97 | 196542.85 | 3126886.82 | 1787312.18 | 4147.39 | 11.33 | 4601.28 | 435.67 |
PERIMETER_MID_ZN_3 | 4136475.75 | 0.00 | 4136475.75 | 461566.56 | 4598042.32 | 2823374.22 | 4105.83 | 10.01 | 4644.15 | 426.41 |
PERIMETER_MID_ZN_2 | 3333072.52 | 0.00 | 3333072.52 | 307709.19 | 3640781.72 | 1601953.02 | 4062.95 | 3.19 | 4693.86 | 1335.39 |
PERIMETER_MID_ZN_1 | 4936366.02 | 0.00 | 4936366.02 | 461566.56 | 5397932.58 | 2823374.22 | 4088.85 | 3.18 | 4667.97 | 426.41 |
PERIMETER_MID_ZN_4 | 3745233.41 | 0.00 | 3745233.41 | 307709.19 | 4052942.61 | 1787312.18 | 4058.14 | 3.92 | 4697.93 | 426.39 |
Total Facility | 83249749.45 | 0.00 | 83249749.45 | 7161246.32 | 90410995.77 | 67658168.57 | 6813.59 | 147.93 | 4782.06 | 1490.26 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6561 | 0.0000 | 0.6561 | 0.0000 | 0.6561 | 0.4247 | 3462.85 | 36.08 | 2444.07 |
CORE_MID | 0.4755 | 0.0000 | 0.4755 | 0.0000 | 0.4755 | 0.4247 | 3934.44 | 27.31 | 1981.25 |
CORE_TOP | 0.5057 | 0.0000 | 0.5057 | 0.0000 | 0.5057 | 0.4247 | 3731.11 | 23.52 | 2188.36 |
PERIMETER_TOP_ZN_3 | 0.2205 | 0.0000 | 0.2205 | 0.0135 | 0.2340 | 0.0895 | 1374.98 | 5.65 | 4562.37 |
PERIMETER_TOP_ZN_2 | 0.1595 | 0.0000 | 0.1595 | 0.0090 | 0.1685 | 0.0567 | 1360.86 | 1.14 | 4581.00 |
PERIMETER_TOP_ZN_1 | 0.2460 | 0.0000 | 0.2460 | 0.0135 | 0.2594 | 0.0895 | 1361.70 | 1.51 | 4579.79 |
PERIMETER_TOP_ZN_4 | 0.1665 | 0.0000 | 0.1665 | 0.0090 | 0.1755 | 0.0567 | 1357.25 | 1.37 | 4584.37 |
PERIMETER_BOT_ZN_3 | 0.1845 | 0.0000 | 0.1845 | 0.0072 | 0.1917 | 0.0895 | 1568.57 | 7.02 | 4367.41 |
PERIMETER_BOT_ZN_2 | 0.1330 | 0.0000 | 0.1330 | 0.0048 | 0.1378 | 0.0567 | 1362.78 | 11.87 | 4568.35 |
PERIMETER_BOT_ZN_1 | 0.2081 | 0.0000 | 0.2081 | 0.1376 | 0.3458 | 0.0895 | 1313.67 | 5.17 | 4624.16 |
PERIMETER_BOT_ZN_4 | 0.1338 | 0.0000 | 0.1338 | 0.0048 | 0.1386 | 0.0567 | 1377.54 | 10.01 | 4555.44 |
PERIMETER_MID_ZN_3 | 0.1897 | 0.0000 | 0.1897 | 0.0112 | 0.2009 | 0.0895 | 1314.66 | 9.85 | 4618.49 |
PERIMETER_MID_ZN_2 | 0.1621 | 0.0000 | 0.1621 | 0.0079 | 0.1700 | 0.0567 | 1278.42 | 2.29 | 3753.29 |
PERIMETER_MID_ZN_1 | 0.2271 | 0.0000 | 0.2271 | 0.0112 | 0.2383 | 0.0895 | 1297.70 | 2.94 | 4642.36 |
PERIMETER_MID_ZN_4 | 0.1719 | 0.0000 | 0.1719 | 0.0075 | 0.1794 | 0.0567 | 1275.93 | 1.83 | 4665.24 |
Total Facility | 3.8401 | 0.0000 | 3.8401 | 0.2370 | 4.0770 | 2.1513 | 4008.85 | 139.32 | 4720.88 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 38252097.42 | 0.00 | 38252097.42 | 22614548.33 | 4099.97 | 3.69 | 4656.34 | 435.67 |
PACU_VAV_MID | 35271091.92 | 0.00 | 35271091.92 | 22429071.92 | 4093.75 | 1.58 | 4664.67 | 426.37 |
PACU_VAV_TOP | 37327396.37 | 0.00 | 37327396.37 | 22614548.33 | 4160.05 | 0.86 | 4599.08 | 56.26 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.7517 | 0.0000 | 1.7517 | 0.7171 | 1322.16 | 2.11 | 4618.73 |
PACU_VAV_MID | 1.6205 | 0.0000 | 1.6205 | 0.7084 | 1301.94 | 1.50 | 4639.57 |
PACU_VAV_TOP | 1.7286 | 0.0000 | 1.7286 | 0.7171 | 1366.71 | 0.86 | 4575.43 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 20.55 | 3383.71 | 0.00 | 0.00 | 0.00 | 1854.75 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 62.24 | 3071.97 | 0.00 | 0.00 | 0.00 | 2151.24 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 26.30 | 2787.05 | 0.00 | 0.00 | 0.00 | 1974.58 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2100 | 2.8453 | 0.0000 | 0.0000 | 0.0000 | 1.0777 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2019 | 2.6840 | 0.0000 | 0.0000 | 0.0000 | 1.1417 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1913 | 2.9669 | 0.0000 | 0.0000 | 0.0000 | 1.0846 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1961.93 | 15934.24 | 12-MAR-17:10 | 215724.10 | 05-JUL-10:40 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 360.71 | 385.65 | 01-JAN-18:40 | 118946.87 | 05-JUL-10:40 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:20 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:20 |
ElectricityPurchased:Facility | 1961.93 | 15934.24 | 12-MAR-17:10 | 215724.10 | 05-JUL-10:40 |
ElectricityPurchased:Plant | 1961.93 | 15934.24 | 12-MAR-17:10 | 215724.10 | 05-JUL-10:40 |
Cogeneration:ElectricityPurchased | 1961.93 | 15934.24 | 12-MAR-17:10 | 215724.10 | 05-JUL-10:40 |
General:Cogeneration:ElectricityPurchased | 1961.93 | 15934.24 | 12-MAR-17:10 | 215724.10 | 05-JUL-10:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1961.93 | 15934.24 | 12-MAR-17:10 | 215724.10 | 05-JUL-10:40 |
ElectricityNet:Plant | 1961.93 | 15934.24 | 12-MAR-17:10 | 215724.10 | 05-JUL-10:40 |
Cogeneration:ElectricityNet | 1961.93 | 15934.24 | 12-MAR-17:10 | 215724.10 | 05-JUL-10:40 |
General:Cogeneration:ElectricityNet | 1961.93 | 15934.24 | 12-MAR-17:10 | 215724.10 | 05-JUL-10:40 |
Fans:Electricity | 193.55 | 0.00 | 01-JAN-00:40 | 32080.24 | 05-JUL-10:40 |
General:Fans:Electricity | 193.55 | 0.00 | 01-JAN-00:40 | 32080.24 | 05-JUL-10:40 |
ExteriorLights:Electricity | 235.37 | 0.00 | 01-JAN-08:20 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 235.37 | 0.00 | 01-JAN-08:20 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 139.67 | 0.00 | 01-JAN-00:10 | 87514.39 | 29-JUN-16:00 |
General:Cooling:Electricity | 139.67 | 0.00 | 01-JAN-00:10 | 87514.39 | 29-JUN-16:00 |
Electricity:Plant | 70.32 | 0.00 | 01-JAN-00:40 | 8907.54 | 23-JAN-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 63.34 | 0.00 | 01-JAN-00:10 | 7751.33 | 21-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 63.34 | 0.00 | 01-JAN-00:10 | 7751.33 | 21-FEB-12:50 |
Pumps:Electricity | 6.99 | 0.00 | 01-JAN-00:40 | 1673.64 | 09-JAN-07:20 |
General:Pumps:Electricity | 6.99 | 0.00 | 01-JAN-00:40 | 1673.64 | 09-JAN-07:20 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1365.29 | 0.00 | 01-JAN-00:40 | 434518.68 | 09-JAN-07:20 |
NaturalGas:Plant | 1365.29 | 0.00 | 01-JAN-00:40 | 434518.68 | 09-JAN-07:20 |
Heating:NaturalGas | 1365.29 | 0.00 | 01-JAN-00:40 | 434518.68 | 09-JAN-07:20 |
Boiler:Heating:NaturalGas | 1365.29 | 0.00 | 01-JAN-00:40 | 434518.68 | 09-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3977.83 | 0.00 | 01-JAN-00:40 | 849484.75 | 09-JAN-07:20 |
EnergyTransfer:Building | 1512.92 | 0.00 | 01-JAN-00:40 | 230433.91 | 26-DEC-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 229.28 | 0.00 | 01-JAN-00:40 | 29072.72 | 05-JUL-10:50 |
Heating:EnergyTransfer | 498.35 | 0.00 | 01-JAN-00:40 | 230433.91 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.34 | 0.00 | 01-JAN-00:10 | 10705.75 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 498.35 | 0.00 | 01-JAN-00:40 | 230433.91 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.34 | 0.00 | 01-JAN-00:10 | 10705.75 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 1014.57 | 0.00 | 01-JAN-00:40 | 195631.92 | 30-JUN-14:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 228.94 | 0.00 | 01-JAN-00:40 | 29072.72 | 05-JUL-10:50 |
General:Cooling:EnergyTransfer | 1014.57 | 0.00 | 01-JAN-00:40 | 195631.92 | 30-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 228.94 | 0.00 | 01-JAN-00:40 | 29072.72 | 05-JUL-10:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 133.64 | 0.00 | 01-JAN-00:40 | 30629.35 | 06-JAN-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 95.35 | 0.00 | 01-JAN-00:40 | 30629.35 | 06-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 95.35 | 0.00 | 01-JAN-00:40 | 30629.35 | 06-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.29 | 0.00 | 01-JAN-00:10 | 17590.84 | 30-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.29 | 0.00 | 01-JAN-00:10 | 17590.84 | 30-JUN-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 40.00 | 0.00 | 01-JAN-00:40 | 13458.92 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.54 | 0.00 | 01-JAN-00:40 | 13458.92 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.54 | 0.00 | 01-JAN-00:40 | 13458.92 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.46 | 0.00 | 01-JAN-00:10 | 5744.01 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.46 | 0.00 | 01-JAN-00:10 | 5744.01 | 30-JUN-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 39.81 | 0.00 | 01-JAN-00:40 | 10930.85 | 02-JAN-09:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.25 | 0.00 | 01-JAN-00:40 | 10930.85 | 02-JAN-09:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.25 | 0.00 | 01-JAN-00:40 | 10930.85 | 02-JAN-09:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.55 | 0.00 | 01-JAN-00:10 | 5497.45 | 30-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.55 | 0.00 | 01-JAN-00:10 | 5497.45 | 30-JUN-15:50 |
EnergyTransfer:Zone:CORE_MID | 147.83 | 0.00 | 01-JAN-00:40 | 21123.54 | 05-JUL-10:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 3.75 | 0.00 | 01-JAN-00:40 | 18376.06 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 3.75 | 0.00 | 01-JAN-00:40 | 18376.06 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 144.08 | 0.00 | 01-JAN-00:20 | 21123.54 | 05-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 144.08 | 0.00 | 01-JAN-00:20 | 21123.54 | 05-JUL-10:50 |
EnergyTransfer:Zone:CORE_TOP | 160.18 | 0.00 | 01-JAN-00:40 | 31650.16 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 25.80 | 0.00 | 01-JAN-00:40 | 31650.16 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 25.80 | 0.00 | 01-JAN-00:40 | 31650.16 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 134.39 | 0.00 | 01-JAN-00:20 | 24300.16 | 30-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 134.39 | 0.00 | 01-JAN-00:20 | 24300.16 | 30-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 81.47 | 0.00 | 01-JAN-00:40 | 16450.11 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.28 | 0.00 | 01-JAN-00:40 | 16450.11 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.28 | 0.00 | 01-JAN-00:40 | 16450.11 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.19 | 0.00 | 01-JAN-00:10 | 8574.63 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.19 | 0.00 | 01-JAN-00:10 | 8574.63 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 58.22 | 0.00 | 01-JAN-00:40 | 10664.52 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.93 | 0.00 | 01-JAN-00:40 | 10664.52 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.93 | 0.00 | 01-JAN-00:40 | 10664.52 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.29 | 0.00 | 01-JAN-00:10 | 10264.43 | 24-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.29 | 0.00 | 01-JAN-00:10 | 10264.43 | 24-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.25 | 0.00 | 01-JAN-00:40 | 16364.40 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 33.83 | 0.00 | 01-JAN-00:40 | 16362.89 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 33.83 | 0.00 | 01-JAN-00:40 | 16362.89 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 54.41 | 0.00 | 01-JAN-00:10 | 16364.40 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 54.41 | 0.00 | 01-JAN-00:10 | 16364.40 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 60.50 | 0.00 | 01-JAN-00:40 | 11765.41 | 29-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 28.35 | 0.00 | 01-JAN-00:40 | 10993.83 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 28.35 | 0.00 | 01-JAN-00:40 | 10993.83 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.15 | 0.00 | 01-JAN-00:10 | 11765.41 | 29-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.15 | 0.00 | 01-JAN-00:10 | 11765.41 | 29-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 62.68 | 0.00 | 01-JAN-00:40 | 11889.50 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.18 | 0.00 | 01-JAN-00:40 | 11889.50 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.18 | 0.00 | 01-JAN-00:40 | 11889.50 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.51 | 0.00 | 01-JAN-00:10 | 5583.82 | 21-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.51 | 0.00 | 01-JAN-00:10 | 5583.82 | 21-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 44.67 | 0.00 | 01-JAN-00:40 | 7785.71 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.09 | 0.00 | 01-JAN-00:40 | 7785.71 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.09 | 0.00 | 01-JAN-00:40 | 7785.71 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.58 | 0.00 | 01-JAN-00:10 | 7655.74 | 24-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.58 | 0.00 | 01-JAN-00:10 | 7655.74 | 24-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 87.73 | 0.00 | 01-JAN-00:40 | 21298.12 | 09-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 51.20 | 0.00 | 01-JAN-00:40 | 21298.12 | 09-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 51.20 | 0.00 | 01-JAN-00:40 | 21298.12 | 09-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 36.52 | 0.00 | 01-JAN-00:10 | 14709.88 | 30-JUN-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 36.52 | 0.00 | 01-JAN-00:10 | 14709.88 | 30-JUN-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 45.53 | 0.00 | 01-JAN-00:40 | 8291.85 | 30-JUN-18:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.05 | 0.00 | 01-JAN-00:40 | 7962.60 | 05-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.05 | 0.00 | 01-JAN-00:40 | 7962.60 | 05-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.48 | 0.00 | 01-JAN-00:10 | 8291.85 | 30-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.48 | 0.00 | 01-JAN-00:10 | 8291.85 | 30-JUN-18:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 62.08 | 0.00 | 01-JAN-00:40 | 12267.61 | 13-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.66 | 0.00 | 01-JAN-00:40 | 12267.61 | 13-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.66 | 0.00 | 01-JAN-00:40 | 12267.61 | 13-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 34.42 | 0.00 | 01-JAN-00:10 | 7828.00 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 34.42 | 0.00 | 01-JAN-00:10 | 7828.00 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.12 | 0.00 | 01-JAN-00:40 | 10428.58 | 24-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 15.80 | 0.00 | 01-JAN-00:40 | 8423.59 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 15.80 | 0.00 | 01-JAN-00:40 | 8423.59 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.32 | 0.00 | 01-JAN-00:10 | 10428.58 | 24-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.32 | 0.00 | 01-JAN-00:10 | 10428.58 | 24-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 73.16 | 0.00 | 01-JAN-00:40 | 15936.66 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 18.11 | 0.00 | 01-JAN-00:40 | 12305.83 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 18.11 | 0.00 | 01-JAN-00:40 | 12305.83 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 55.05 | 0.00 | 01-JAN-00:10 | 15936.66 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 55.05 | 0.00 | 01-JAN-00:10 | 15936.66 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 50.78 | 0.00 | 01-JAN-00:40 | 11209.34 | 29-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 16.83 | 0.00 | 01-JAN-00:40 | 8582.91 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 16.83 | 0.00 | 01-JAN-00:40 | 8582.91 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.95 | 0.00 | 01-JAN-00:10 | 11209.34 | 29-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.95 | 0.00 | 01-JAN-00:10 | 11209.34 | 29-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 975.23 | 0.00 | 01-JAN-00:40 | 325879.98 | 09-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
EnergyTransfer:HVAC | 1496.92 | 0.00 | 01-JAN-00:40 | 394289.21 | 05-JUL-10:40 |
HeatingCoils:EnergyTransfer | 914.76 | 0.00 | 01-JAN-00:40 | 323424.43 | 09-JAN-07:20 |
PlantLoopHeatingDemand:HVAC | 914.76 | 0.00 | 01-JAN-00:40 | 323424.43 | 09-JAN-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 914.76 | 0.00 | 01-JAN-00:40 | 323424.43 | 09-JAN-07:20 |
CoolingCoils:EnergyTransfer | 582.16 | 0.00 | 01-JAN-00:10 | 394289.21 | 05-JUL-10:40 |
EnergyTransfer:Plant | 967.98 | 0.00 | 01-JAN-00:40 | 323954.21 | 09-JAN-07:20 |
WaterSystems:EnergyTransfer | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
Boilers:EnergyTransfer | 907.51 | 0.00 | 01-JAN-00:40 | 321498.66 | 09-JAN-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.339 | -228.941 | 0.000 | 0.000 | 33.874 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -177.058 |
CORE_MID | 0.000 | 0.000 | 3.752 | -144.078 | 0.000 | 0.000 | 35.123 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -122.009 |
CORE_TOP | 0.000 | 0.000 | 25.795 | -134.388 | 0.000 | 0.000 | 36.422 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -155.040 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 46.280 | -35.190 | 0.000 | 0.000 | 7.936 | 23.566 | 24.333 | 17.049 | 0.000 | 0.063 | 0.000 | 0.000 | -69.257 | 0.000 | -11.414 | -3.367 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 26.928 | -31.289 | 0.000 | 0.000 | 4.928 | 14.919 | 15.404 | 35.031 | 0.000 | 0.035 | 0.000 | 0.000 | -42.470 | 0.000 | -7.708 | -15.777 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 33.834 | -54.413 | 0.000 | 0.000 | 7.750 | 23.566 | 24.332 | 74.604 | 0.000 | 0.047 | 0.000 | 0.000 | -60.414 | 0.000 | -11.719 | -37.587 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 28.350 | -32.147 | 0.000 | 0.000 | 5.000 | 14.918 | 15.403 | 36.048 | 0.000 | 0.033 | 0.000 | 0.000 | -44.191 | 0.000 | -7.728 | -15.687 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 35.176 | -27.509 | 0.000 | 0.000 | 7.939 | 23.566 | 24.333 | 17.809 | 0.000 | 0.039 | 0.000 | 0.000 | -69.562 | 0.000 | -6.188 | -5.603 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 19.090 | -25.580 | 0.000 | 0.000 | 4.912 | 14.919 | 15.404 | 35.518 | 0.000 | 0.019 | 0.001 | 0.000 | -43.238 | 0.000 | -4.214 | -16.829 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 51.203 | -36.523 | 0.000 | 0.000 | 7.944 | 23.566 | 24.332 | 76.213 | 0.000 | 0.722 | 0.001 | 0.000 | -61.408 | 0.000 | -58.791 | -27.258 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 20.048 | -25.483 | 0.000 | 0.000 | 4.965 | 14.918 | 15.403 | 36.635 | 0.000 | 0.018 | 0.000 | 0.000 | -44.985 | 0.000 | -4.227 | -17.292 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 27.662 | -34.415 | 0.000 | 0.000 | 7.798 | 23.566 | 24.333 | 16.482 | 0.000 | 0.047 | 16.502 | 0.000 | -72.124 | 0.000 | -9.851 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 15.803 | -31.318 | 0.000 | 0.000 | 3.604 | 14.919 | 15.404 | 34.571 | 0.000 | 0.028 | 0.002 | 0.000 | -44.195 | 0.000 | -6.642 | -2.174 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 18.110 | -55.051 | 0.000 | 0.000 | 7.587 | 23.566 | 24.332 | 73.893 | 0.000 | 0.036 | 0.005 | 0.000 | -63.354 | 0.000 | -10.156 | -18.963 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 16.834 | -33.945 | 0.000 | 0.000 | 4.952 | 14.918 | 15.403 | 35.842 | 0.000 | 0.027 | 0.000 | 0.000 | -46.012 | 0.000 | -6.648 | -1.372 |
TOPFLOOR_PLENUM | 95.350 | -38.290 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.034 | 0.000 | 0.000 | 0.000 | 0.000 | -17.054 | -40.040 |
MIDFLOOR_PLENUM | 21.543 | -18.455 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.055 | 13.901 | 0.000 | 0.000 | 0.000 | -17.045 | -0.001 |
FIRSTFLOOR_PLENUM | 12.252 | -27.554 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.042 | 28.999 | 0.000 | 0.000 | 0.000 | -13.739 | -0.000 |
Total Facility | 129.145 | -84.299 | 369.202 | -930.270 | 0.000 | 0.000 | 180.735 | 566.263 | 729.266 | 489.696 | 0.000 | 1.245 | 59.413 | 0.000 | -661.208 | 0.000 | -193.123 | -656.057 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 31-JUL-05:12 | 0.00 | 0.00 | 0.00 | -48896.37 | 0.00 | 0.00 | 328.47 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 39749.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 30-JUN-05:02 | 0.00 | 0.00 | 0.00 | -32879.07 | 0.00 | 0.00 | 316.94 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 28451.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 30-JUN-04:01 | 0.00 | 0.00 | 0.00 | -43172.30 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 39645.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | -8574.44 | 0.00 | 0.00 | 737.23 | 2057.62 | 1435.25 | 5208.67 | 0.00 | 146.64 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1010.97 |
PERIMETER_TOP_ZN_2 | 18-JUN-09:12 | 0.00 | 0.00 | 0.00 | -19273.99 | 0.00 | 0.00 | 14.85 | 72.37 | 302.86 | 11635.86 | 0.00 | 0.00 | 7457.04 | 0.00 | -0.00 | 0.00 | -209.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 22-OCT-13:42 | 0.00 | 0.00 | 0.00 | -29766.46 | 0.00 | 0.00 | 23.60 | 114.31 | 478.41 | 18226.67 | 0.00 | 0.00 | 11185.47 | 0.00 | -0.00 | 0.00 | -262.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-JUL-16:12 | 0.00 | 0.00 | 0.00 | -19547.56 | 0.00 | 0.00 | 11.73 | 72.36 | 302.86 | 13259.83 | 0.00 | 64.75 | 5836.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | -5583.72 | 0.00 | 0.00 | 757.17 | 2057.62 | 1435.25 | 4931.35 | 0.00 | 23.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3620.83 |
PERIMETER_BOT_ZN_2 | 24-JUL-09:10 | 0.00 | 0.00 | 0.00 | -7655.92 | 0.00 | 0.00 | 479.36 | 1302.65 | 908.57 | 13116.91 | 0.00 | 2.76 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8154.33 |
PERIMETER_BOT_ZN_1 | 22-OCT-13:42 | 0.00 | 0.00 | 0.00 | -23640.81 | 0.00 | 0.00 | 23.97 | 114.31 | 478.41 | 18307.70 | 0.00 | 0.00 | 4859.44 | 0.00 | -0.00 | 0.00 | -143.02 | 0.00 |
PERIMETER_BOT_ZN_4 | 29-JUL-17:42 | 0.00 | 0.00 | 0.00 | -11408.07 | 0.00 | 0.00 | 15.15 | 72.36 | 302.86 | 10099.45 | 0.00 | 11.34 | 906.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 30-JUN-04:01 | 0.00 | 0.00 | 0.00 | -9860.81 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 14.73 | 9381.90 | 0.00 | -279.24 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-09:32 | 0.00 | 0.00 | 0.00 | -15859.50 | 0.00 | 0.00 | 13.49 | 72.37 | 302.86 | 11434.71 | 0.00 | 0.00 | 4050.22 | 0.00 | -0.00 | 0.00 | -14.14 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-12:42 | 0.00 | 0.00 | 0.00 | -23742.08 | 0.00 | 0.00 | 22.72 | 114.31 | 478.41 | 18452.66 | 0.00 | 0.00 | 5244.03 | 0.00 | -0.00 | 0.00 | -570.06 | 0.00 |
PERIMETER_MID_ZN_4 | 01-JUL-18:22 | 0.00 | 0.00 | 0.00 | -18941.73 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 10647.82 | 0.00 | 0.00 | 8105.95 | 0.00 | -0.00 | 0.00 | -128.83 | 0.00 |
TOPFLOOR_PLENUM | 30-JUN-14:05 | 0.00 | -17597.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.78 | 17485.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 21-JAN-05:01 | 0.00 | -7709.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7709.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 23-MAR-04:01 | 0.00 | -9244.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9244.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JUN-04:01 | 0.00 | 13084.54 | 0.00 | -203354.16 | 0.00 | 0.00 | 0.00 | 5493.69 | 15894.33 | 0.00 | 0.00 | 235.49 | 170871.81 | 0.00 | -2225.70 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 13691.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20742.12 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 22126.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25652.81 |
CORE_TOP | 01-JAN-03:21 | 0.00 | 0.00 | 38244.50 | 0.00 | 0.00 | 0.00 | 0.00 | 542.26 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -40618.30 |
PERIMETER_TOP_ZN_3 | 13-FEB-05:11 | 0.00 | 0.00 | 20284.24 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5968.54 | 0.00 | -2279.02 | -12780.11 |
PERIMETER_TOP_ZN_2 | 13-FEB-05:11 | 0.00 | 0.00 | 13269.60 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3798.62 | 0.00 | -1518.84 | -8422.77 |
PERIMETER_TOP_ZN_1 | 13-FEB-05:11 | 0.00 | 0.00 | 20394.99 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5719.28 | 0.00 | -2288.18 | -13130.95 |
PERIMETER_TOP_ZN_4 | 13-FEB-05:11 | 0.00 | 0.00 | 13941.09 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3976.57 | 0.00 | -1518.07 | -8917.07 |
PERIMETER_BOT_ZN_3 | 01-JAN-08:61 | 0.00 | 0.00 | 14628.10 | 0.00 | 0.00 | 0.00 | 61.20 | 114.31 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6006.16 | 0.00 | -911.39 | -8364.48 |
PERIMETER_BOT_ZN_2 | 01-JAN-08:61 | 0.00 | 0.00 | 9614.78 | 0.00 | 0.00 | 0.00 | 38.75 | 72.37 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4013.42 | 0.00 | -607.85 | -5407.49 |
PERIMETER_BOT_ZN_1 | 06-JAN-07:10 | 0.00 | 0.00 | 21667.69 | 0.00 | 0.00 | 0.00 | 212.95 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 23753.57 | 0.00 | -7533.96 | 0.00 | -39424.01 | 0.00 |
PERIMETER_BOT_ZN_4 | 01-JAN-08:61 | 0.00 | 0.00 | 9923.17 | 0.00 | 0.00 | 0.00 | 38.80 | 72.36 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4153.04 | 0.00 | -607.55 | -5576.60 |
PERIMETER_MID_ZN_3 | 10-DEC-19:02 | 0.00 | 0.00 | 14354.72 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6270.85 | 0.00 | -1198.64 | -7385.65 |
PERIMETER_MID_ZN_2 | 09-JAN-04:41 | 0.00 | 0.00 | 10721.05 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4699.91 | 0.00 | -842.58 | -5576.83 |
PERIMETER_MID_ZN_1 | 09-JAN-04:41 | 0.00 | 0.00 | 14509.98 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7337.33 | 0.00 | -1263.72 | -6538.05 |
PERIMETER_MID_ZN_4 | 09-JAN-04:41 | 0.00 | 0.00 | 11042.50 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4874.39 | 0.00 | -842.08 | -5724.30 |
TOPFLOOR_PLENUM | 14-FEB-06:12 | 32980.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -403.62 | -32577.04 |
MIDFLOOR_PLENUM | 02-JAN-08:13 | 13772.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -182.61 | -13590.22 |
FIRSTFLOOR_PLENUM | 02-JAN-09:30 | 11038.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -104.63 | -10933.90 |
Total Facility | 02-JAN-05:21 | 34614.31 | 0.00 | 232868.85 | 0.00 | 0.00 | 0.00 | 0.00 | 5493.69 | 15894.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49058.41 | 0.00 | -11981.90 | -227830.86 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 8.1271 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.2220 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 7.8248 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.0248 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 9.7806 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 7.2410 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.0636 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.4381 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.9124 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.3474 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.8903 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9342 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5113 | 3.5113 | 1.0534 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8843 | 2.8843 | 0.8653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8336 | 3.8336 | 1.1501 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7662 | 1.7662 | 0.5299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1548 | 1.1548 | 0.3464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7890 | 1.7890 | 0.5367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2370 | 1.2370 | 0.3711 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3742 | 1.3742 | 0.4122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9041 | 0.9041 | 0.2712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3966 | 1.3966 | 0.4190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9409 | 0.9409 | 0.2823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3388 | 1.3388 | 0.4016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1004 | 1.1004 | 0.3301 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3601 | 1.3601 | 0.4080 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1411 | 1.1411 | 0.3423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 8.1271 | 6.2220 | 8.1271 | 2.4381 | 0.0000 | 1.0000 |
PACU_VAV_MID | 7.8248 | 6.0248 | 7.8248 | 2.3474 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 9.7806 | 7.2410 | 9.7806 | 2.9342 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7557 | 1.7557 | 1.0534 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4422 | 1.4422 | 0.8653 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9168 | 1.9168 | 1.1501 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8831 | 0.8831 | 0.5299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5774 | 0.5774 | 0.3464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8945 | 0.8945 | 0.5367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6185 | 0.6185 | 0.3711 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6871 | 0.6871 | 0.4122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4521 | 0.4521 | 0.2712 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6983 | 0.6983 | 0.4190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4704 | 0.4704 | 0.2823 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6694 | 0.6694 | 0.4016 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5502 | 0.5502 | 0.3301 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6801 | 0.6801 | 0.4080 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5705 | 0.5705 | 0.3423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.0636 | 2.4381 | 2.4381 | 2.4381 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.9124 | 2.3474 | 2.3474 | 2.3474 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.8903 | 2.9342 | 2.9342 | 2.9342 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 634.33 |
Number of hours cooling loads not met | 33.33 |
Number of hours not met | 667.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1365.29 | 434518.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 139.67 | 87514.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 235.37 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 193.55 | 32080.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 6.99 | 1673.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 63.34 | 7751.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 1961.93 |
Natural Gas | 0.00 | 1365.29 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 3327.22 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 28.03 |
Fans (All) | 38.85 |
Service Water Heating | 12.71 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 393.79 |
Subtotal | 393.79 |
Natural Gas [MJ/m2] | |
Space Heating | 274.03 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 274.03 |
Subtotal | 274.03 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.02 |
Space Heating | 41.03 |
Space Cooling | 4.20 |
Fans (All) | 5.82 |
Service Water Heating | 1.90 |
Receptacle Equipment | 21.92 |
Miscellaneous | 8.11 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8521.67 | 238.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8731.50 | 28.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8731.83 | 28.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8521.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 238.33 | 0.00 | 0.00 | 0.00 |
Average | 8734.89 | 25.11 | 0.00 | 0.00 | 0.00 |
Sum | 157228.00 | 452.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128193.67 | 110.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 110.33 | 0.00 | 0.00 | 0.00 |
Average | 34137.20 | 6.13 | 0.00 | 0.00 | 0.00 |
Sum | 614469.67 | 110.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8195.50 | 564.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8487.17 | 272.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8723.33 | 36.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8671.83 | 88.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8637.33 | 122.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8642.33 | 117.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8595.00 | 165.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8688.83 | 71.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8621.00 | 139.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8609.17 | 150.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8548.67 | 211.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8597.33 | 162.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8570.50 | 189.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8546.33 | 213.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8516.67 | 243.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8453.17 | 306.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8594.67 | 165.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8547.50 | 212.50 | 0.00 | 0.00 | 0.00 |
Min | 8195.50 | 36.67 | 0.00 | 0.00 | 0.00 |
Max | 8723.33 | 564.50 | 0.00 | 0.00 | 0.00 |
Average | 8569.24 | 190.76 | 0.00 | 0.00 | 0.00 |
Sum | 154246.33 | 3433.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127963.50 | 340.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128181.33 | 122.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128272.67 | 31.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24868.00 | 41.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24906.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10133.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24906.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14015.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128272.67 | 340.50 | 0.00 | 0.00 | 0.00 |
Average | 34113.19 | 30.15 | 0.00 | 0.00 | 0.00 |
Sum | 614037.33 | 542.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:10
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129173E+11 | 10038.51 | 27-JAN-16:30 | -15.6 | -16.5 | 0.163675E+10 | 2486.94 | 27-JAN-16:40 | -15.9 | -16.8 |
February | 0.128115E+11 | 11355.42 | 10-FEB-17:00 | -12.8 | -14.1 | 0.157931E+10 | 2538.97 | 10-FEB-14:00 | -12.8 | -14.1 |
March | 0.152453E+11 | 15923.18 | 31-MAR-16:00 | 8.90 | 3.77 | 0.198953E+10 | 2606.65 | 29-MAR-09:20 | 8.90 | 3.77 |
April | 0.159226E+11 | 28331.93 | 20-APR-05:01 | -4.1 | -6.7 | 0.187634E+10 | 2606.65 | 18-APR-09:39 | -4.1 | -6.7 |
May | 0.223037E+11 | 38575.97 | 26-MAY-05:12 | 19.40 | 15.67 | 0.207487E+10 | 2606.71 | 24-MAY-09:09 | 19.40 | 15.67 |
June | 0.257330E+11 | 47534.82 | 30-JUN-04:01 | 26.10 | 22.87 | 0.207083E+10 | 2606.68 | 06-JUN-09:09 | 26.10 | 22.87 |
July | 0.278146E+11 | 48907.86 | 31-JUL-05:12 | 14.97 | 13.44 | 0.192789E+10 | 2650.12 | 05-JUL-10:50 | 14.97 | 13.44 |
August | 0.288958E+11 | 48904.48 | 28-AUG-05:12 | 13.90 | 13.22 | 0.216015E+10 | 2606.69 | 10-AUG-13:00 | 13.90 | 13.22 |
September | 0.227784E+11 | 46909.86 | 05-SEP-05:12 | 5.60 | 5.31 | 0.191707E+10 | 2606.67 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.176132E+11 | 39460.77 | 25-OCT-05:01 | -3.5 | -3.8 | 0.197594E+10 | 2606.67 | 25-OCT-09:30 | 1.65 | 1.53 |
November | 0.133796E+11 | 16380.36 | 17-NOV-16:20 | 8.90 | 2.59 | 0.187500E+10 | 2606.65 | 10-NOV-10:20 | 8.90 | 2.59 |
December | 0.135263E+11 | 11045.83 | 01-DEC-15:30 | -18.2 | -19.0 | 0.163684E+10 | 2547.43 | 01-DEC-14:00 | -18.2 | -19.0 |
Annual Sum or Average | 0.228941E+12 | 0.227205E+11 | ||||||||
Minimum of Months | 0.128115E+11 | 10038.51 | -18.2 | -19.0 | 0.157931E+10 | 2486.94 | -18.2 | -19.0 | ||
Maximum of Months | 0.288958E+11 | 48907.86 | 26.10 | 22.87 | 0.216015E+10 | 2650.12 | 26.10 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 30455830.72 | 1318.19 | 08-FEB-14:25 | 5.00 | -0.5 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | -0.5 |
March | 0.406694E+09 | 5131.00 | 26-MAR-14:00 | 8.90 | 4.59 | 0.00 | 0.00 | 01-MAR-00:10 | 8.90 | 4.59 |
April | 0.235128E+10 | 8753.72 | 23-APR-14:32 | 25.20 | 16.35 | 0.00 | 0.00 | 01-APR-00:10 | 25.20 | 16.35 |
May | 0.621651E+10 | 15333.39 | 18-MAY-14:00 | 28.50 | 16.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.50 | 16.75 |
June | 0.833450E+10 | 17597.47 | 30-JUN-14:05 | 31.28 | 23.89 | 0.00 | 0.00 | 01-JUN-00:10 | 31.28 | 23.89 |
July | 0.942635E+10 | 16070.40 | 24-JUL-14:05 | 29.40 | 19.77 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.77 |
August | 0.718867E+10 | 14673.08 | 08-AUG-14:05 | 30.10 | 22.94 | 0.00 | 0.00 | 01-AUG-00:10 | 30.10 | 22.94 |
September | 0.340744E+10 | 12434.36 | 01-SEP-14:00 | 25.60 | 18.11 | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 18.11 |
October | 0.861881E+09 | 6604.89 | 22-OCT-13:47 | 19.22 | 12.83 | 0.00 | 0.00 | 01-OCT-00:10 | 19.22 | 12.83 |
November | 66970865.38 | 2480.42 | 01-NOV-14:00 | 17.80 | 13.26 | 0.00 | 0.00 | 01-NOV-00:10 | 17.80 | 13.26 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.382908E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.00 | 0.00 | -21.9 | -22.1 | ||
Maximum of Months | 0.942635E+10 | 17597.47 | 31.28 | 23.89 | 0.00 | 0.00 | 31.28 | 23.89 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445841E+09 | 7709.64 | 21-JAN-05:01 | -22.2 | -22.4 | 0.00 | 0.00 | 01-JAN-00:10 | -22.2 | -22.4 |
February | 0.330225E+09 | 7028.53 | 10-FEB-05:11 | -20.4 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.4 | -20.7 |
March | 0.308067E+09 | 7356.73 | 08-MAR-05:01 | -20.3 | -20.6 | 0.00 | 0.00 | 01-MAR-00:10 | -20.3 | -20.6 |
April | 0.773313E+09 | 4622.64 | 05-APR-04:01 | -12.4 | -13.3 | 0.00 | 0.00 | 01-APR-00:10 | -12.4 | -13.3 |
May | 0.240453E+10 | 4217.35 | 18-MAY-16:00 | 28.50 | 16.32 | 0.00 | 0.00 | 01-MAY-00:10 | 28.50 | 16.32 |
June | 0.354419E+10 | 5744.01 | 30-JUN-16:00 | 31.70 | 24.66 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.66 |
July | 0.415884E+10 | 5225.40 | 24-JUL-16:00 | 28.90 | 18.68 | 0.00 | 0.00 | 01-JUL-00:10 | 28.90 | 18.68 |
August | 0.351133E+10 | 4133.56 | 08-AUG-16:00 | 30.60 | 22.99 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 22.99 |
September | 0.188156E+10 | 4153.62 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.628378E+09 | 4140.80 | 06-OCT-05:01 | -5.3 | -5.8 | 0.00 | 0.00 | 01-OCT-00:10 | -5.3 | -5.8 |
November | 0.155180E+09 | 4977.60 | 29-NOV-05:01 | -19.6 | -19.9 | 0.00 | 0.00 | 01-NOV-00:10 | -19.6 | -19.9 |
December | 0.313685E+09 | 6589.98 | 29-DEC-05:01 | -16.2 | -16.5 | 0.00 | 0.00 | 01-DEC-00:10 | -16.2 | -16.5 |
Annual Sum or Average | 0.184551E+11 | 0.00 | ||||||||
Minimum of Months | 0.155180E+09 | 4133.56 | -22.2 | -22.4 | 0.00 | 0.00 | -22.2 | -22.4 | ||
Maximum of Months | 0.415884E+10 | 7709.64 | 31.70 | 24.66 | 0.00 | 0.00 | 31.70 | 24.66 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.752619E+09 | 8423.83 | 21-JAN-05:01 | -22.2 | -22.4 | 0.00 | 0.00 | 01-JAN-00:10 | -22.2 | -22.4 |
February | 0.675847E+09 | 8683.41 | 10-FEB-05:01 | -20.2 | -20.5 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.5 |
March | 0.941380E+09 | 9244.34 | 23-MAR-04:01 | -16.2 | -16.5 | 0.00 | 0.00 | 01-MAR-00:10 | -16.2 | -16.5 |
April | 0.158031E+10 | 8316.47 | 05-APR-04:01 | -12.4 | -13.3 | 0.00 | 0.00 | 01-APR-00:10 | -12.4 | -13.3 |
May | 0.356642E+10 | 6399.98 | 01-MAY-05:01 | -3.4 | -5.9 | 0.00 | 0.00 | 01-MAY-00:10 | -3.4 | -5.9 |
June | 0.451535E+10 | 5497.45 | 30-JUN-15:50 | 31.78 | 24.63 | 0.00 | 0.00 | 01-JUN-00:10 | 31.78 | 24.63 |
July | 0.508447E+10 | 5366.22 | 24-JUL-16:00 | 28.90 | 18.68 | 0.00 | 0.00 | 01-JUL-00:10 | 28.90 | 18.68 |
August | 0.470888E+10 | 4938.04 | 28-AUG-06:08 | 14.08 | 13.35 | 0.00 | 0.00 | 01-AUG-00:10 | 14.08 | 13.35 |
September | 0.319057E+10 | 5181.75 | 05-SEP-06:07 | 6.05 | 5.72 | 0.00 | 0.00 | 01-SEP-00:10 | 6.05 | 5.72 |
October | 0.157774E+10 | 4653.56 | 25-OCT-06:02 | -4.2 | -4.4 | 0.00 | 0.00 | 01-OCT-00:10 | -4.2 | -4.4 |
November | 0.397175E+09 | 6424.69 | 29-NOV-05:01 | -19.6 | -19.9 | 0.00 | 0.00 | 01-NOV-00:10 | -19.6 | -19.9 |
December | 0.562957E+09 | 7365.65 | 08-DEC-05:01 | -20.3 | -20.7 | 0.00 | 0.00 | 01-DEC-00:10 | -20.3 | -20.7 |
Annual Sum or Average | 0.275537E+11 | 0.00 | ||||||||
Minimum of Months | 0.397175E+09 | 4653.56 | -22.2 | -22.4 | 0.00 | 0.00 | -22.2 | -22.4 | ||
Maximum of Months | 0.508447E+10 | 9244.34 | 31.78 | 24.63 | 0.00 | 0.00 | 31.78 | 24.63 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.621870E+10 | 7660.85 | 26-JAN-09:30 | -29.8 | -29.9 | 0.151031E+10 | 2269.10 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.678224E+10 | 7695.96 | 08-FEB-17:00 | 3.30 | -1.3 | 0.142085E+10 | 2352.46 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.918233E+10 | 8441.71 | 29-MAR-16:00 | 5.00 | 1.34 | 0.180051E+10 | 2536.82 | 29-MAR-13:00 | 5.00 | 1.34 |
April | 0.102998E+11 | 13042.20 | 14-APR-16:00 | 15.00 | 6.77 | 0.175027E+10 | 2606.65 | 19-APR-13:20 | 6.30 | 0.57 |
May | 0.154738E+11 | 20375.32 | 26-MAY-05:12 | 19.40 | 15.67 | 0.203909E+10 | 2606.70 | 24-MAY-09:09 | 19.40 | 15.67 |
June | 0.183878E+11 | 32880.87 | 30-JUN-05:02 | 26.20 | 22.42 | 0.205594E+10 | 2606.67 | 06-JUN-09:20 | 26.20 | 22.42 |
July | 0.195722E+11 | 31846.75 | 05-JUL-05:12 | 19.80 | 19.00 | 0.191919E+10 | 2612.95 | 05-JUL-10:50 | 24.13 | 22.97 |
August | 0.193274E+11 | 22553.45 | 09-AUG-05:12 | 18.50 | 17.39 | 0.214746E+10 | 2606.66 | 03-AUG-09:20 | 18.50 | 17.39 |
September | 0.138929E+11 | 18444.92 | 01-SEP-16:00 | 26.10 | 17.64 | 0.188212E+10 | 2606.66 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.104357E+11 | 13912.07 | 20-OCT-16:00 | 18.30 | 9.93 | 0.182435E+10 | 2606.66 | 19-OCT-13:20 | 18.30 | 9.93 |
November | 0.797499E+10 | 8342.10 | 17-NOV-16:20 | 8.90 | 2.59 | 0.164316E+10 | 2531.74 | 17-NOV-14:00 | 8.90 | 2.59 |
December | 0.653040E+10 | 7190.47 | 01-DEC-17:00 | -19.7 | -20.2 | 0.147777E+10 | 2301.69 | 01-DEC-14:00 | -19.7 | -20.2 |
Annual Sum or Average | 0.144078E+12 | 0.214710E+11 | ||||||||
Minimum of Months | 0.621870E+10 | 7190.47 | -29.8 | -29.9 | 0.142085E+10 | 2269.10 | -19.7 | -20.2 | ||
Maximum of Months | 0.195722E+11 | 32880.87 | 26.20 | 22.42 | 0.214746E+10 | 2612.95 | 26.20 | 22.97 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310803E+10 | 7908.47 | 27-JAN-16:00 | -14.4 | -15.6 | 0.145181E+10 | 2011.59 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.423631E+10 | 8964.06 | 08-FEB-17:00 | 3.30 | -1.3 | 0.132997E+10 | 2148.15 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.723681E+10 | 10019.91 | 31-MAR-16:00 | 8.90 | 3.77 | 0.163746E+10 | 2316.34 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.103126E+11 | 13117.31 | 13-APR-16:00 | 20.00 | 8.11 | 0.158928E+10 | 2606.62 | 14-APR-13:20 | 16.10 | 7.09 |
May | 0.165477E+11 | 21511.92 | 18-MAY-15:30 | 28.70 | 16.46 | 0.194530E+10 | 2606.66 | 19-MAY-09:20 | 15.77 | 12.03 |
June | 0.197892E+11 | 43170.25 | 30-JUN-04:01 | 26.10 | 22.87 | 0.201761E+10 | 2606.66 | 12-JUN-13:20 | 26.10 | 22.87 |
July | 0.207855E+11 | 23212.54 | 24-JUL-15:20 | 29.23 | 19.07 | 0.189229E+10 | 2606.69 | 27-JUL-13:39 | 16.33 | 15.15 |
August | 0.196490E+11 | 21351.48 | 09-AUG-15:20 | 27.43 | 21.40 | 0.209186E+10 | 2606.67 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.138912E+11 | 20450.73 | 01-SEP-16:00 | 26.10 | 17.64 | 0.173559E+10 | 2606.64 | 07-SEP-13:20 | 23.90 | 14.25 |
October | 0.945373E+10 | 12484.38 | 22-OCT-13:42 | 19.22 | 12.83 | 0.159855E+10 | 2572.04 | 20-OCT-13:00 | 19.22 | 12.83 |
November | 0.604727E+10 | 9332.95 | 17-NOV-16:10 | 9.45 | 2.90 | 0.148323E+10 | 2240.33 | 17-NOV-14:00 | 9.45 | 2.90 |
December | 0.333102E+10 | 7724.48 | 28-DEC-15:10 | -1.8 | -3.8 | 0.139949E+10 | 1999.79 | 28-DEC-14:00 | -1.8 | -3.8 |
Annual Sum or Average | 0.134388E+12 | 0.201724E+11 | ||||||||
Minimum of Months | 0.310803E+10 | 7724.48 | -14.4 | -15.6 | 0.132997E+10 | 1999.79 | -14.4 | -15.6 | ||
Maximum of Months | 0.207855E+11 | 43170.25 | 29.23 | 22.87 | 0.209186E+10 | 2606.69 | 26.10 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17861076.67 | 3021.29 | 21-JAN-17:01 | -5.0 | -7.1 | 0.303351E+09 | 406.88 | 04-JAN-14:30 | -5.0 | -7.1 |
February | 71981538.88 | 3059.18 | 04-FEB-17:02 | 6.83 | 1.98 | 0.276215E+09 | 406.88 | 13-FEB-10:09 | -23.8 | -24.3 |
March | 0.407938E+09 | 3413.00 | 31-MAR-16:00 | 8.90 | 3.77 | 0.331916E+09 | 406.83 | 21-MAR-13:30 | 8.90 | 3.77 |
April | 0.198547E+10 | 4477.42 | 13-APR-16:00 | 20.00 | 8.11 | 0.301995E+09 | 484.30 | 18-APR-13:00 | 17.80 | 10.49 |
May | 0.556340E+10 | 6791.29 | 18-MAY-15:00 | 28.90 | 16.60 | 0.372507E+09 | 549.50 | 17-MAY-13:20 | 28.90 | 16.60 |
June | 0.709547E+10 | 8574.63 | 29-JUN-15:00 | 34.40 | 24.01 | 0.399655E+09 | 549.50 | 21-JUN-13:50 | 34.40 | 24.01 |
July | 0.737792E+10 | 7869.36 | 21-JUL-13:30 | 28.60 | 22.53 | 0.381494E+09 | 549.50 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.683787E+10 | 6942.34 | 09-AUG-15:30 | 27.25 | 21.19 | 0.402289E+09 | 549.49 | 22-AUG-13:00 | 24.40 | 16.49 |
September | 0.408536E+10 | 5733.41 | 01-SEP-15:40 | 26.10 | 17.70 | 0.320819E+09 | 548.46 | 01-SEP-13:00 | 26.10 | 17.70 |
October | 0.144117E+10 | 5120.08 | 22-OCT-13:42 | 19.22 | 12.83 | 0.308805E+09 | 459.00 | 20-OCT-13:00 | 19.22 | 12.83 |
November | 0.283663E+09 | 3392.04 | 01-NOV-15:20 | 18.13 | 13.38 | 0.301959E+09 | 407.76 | 01-NOV-13:00 | 18.13 | 13.38 |
December | 22777181.89 | 3107.89 | 02-DEC-17:01 | -20.0 | -20.5 | 0.293081E+09 | 406.87 | 20-DEC-10:00 | -25.0 | -25.3 |
Annual Sum or Average | 0.351909E+11 | 0.399408E+10 | ||||||||
Minimum of Months | 17861076.67 | 3021.29 | -20.0 | -20.5 | 0.276215E+09 | 406.83 | -25.0 | -25.3 | ||
Maximum of Months | 0.737792E+10 | 8574.63 | 34.40 | 24.01 | 0.402289E+09 | 549.50 | 34.40 | 24.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11396733.32 | 1976.40 | 21-JAN-17:01 | -5.0 | -7.1 | 0.192243E+09 | 257.60 | 04-JAN-14:09 | -5.0 | -7.1 |
February | 0.161748E+09 | 2289.63 | 28-FEB-10:10 | -5.5 | -7.3 | 0.174998E+09 | 265.26 | 28-FEB-10:20 | -5.0 | -6.8 |
March | 0.792996E+09 | 3117.65 | 31-MAR-09:50 | 1.42 | -1.1 | 0.214148E+09 | 325.83 | 31-MAR-09:00 | 1.70 | -0.9 |
April | 0.231636E+10 | 6531.37 | 18-APR-09:20 | 17.97 | 10.84 | 0.211317E+09 | 347.88 | 18-APR-09:39 | 18.13 | 11.06 |
May | 0.468078E+10 | 8860.92 | 18-MAY-09:20 | 24.33 | 15.92 | 0.253710E+09 | 347.89 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.617128E+10 | 19277.58 | 18-JUN-09:12 | 22.23 | 15.20 | 0.265693E+09 | 347.89 | 14-JUN-13:00 | 22.23 | 15.20 |
July | 0.664136E+10 | 15392.19 | 23-JUL-09:32 | 26.13 | 22.79 | 0.251772E+09 | 347.89 | 11-JUL-09:00 | 26.13 | 22.79 |
August | 0.555644E+10 | 16415.90 | 20-AUG-09:12 | 21.33 | 15.66 | 0.266700E+09 | 347.88 | 08-AUG-09:30 | 21.33 | 15.66 |
September | 0.336578E+10 | 8551.28 | 01-SEP-09:10 | 20.28 | 17.76 | 0.216839E+09 | 347.88 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.124165E+10 | 3912.23 | 22-OCT-13:42 | 19.22 | 12.83 | 0.200463E+09 | 347.88 | 19-OCT-09:39 | 19.22 | 12.83 |
November | 0.330359E+09 | 2338.75 | 16-NOV-09:45 | 1.32 | -0.7 | 0.191305E+09 | 267.58 | 16-NOV-10:09 | 2.15 | -0.3 |
December | 19535734.89 | 2035.33 | 02-DEC-17:01 | -20.0 | -20.5 | 0.185587E+09 | 257.58 | 19-DEC-14:50 | -22.3 | -22.8 |
Annual Sum or Average | 0.312897E+11 | 0.262477E+10 | ||||||||
Minimum of Months | 11396733.32 | 1976.40 | -20.0 | -20.5 | 0.174998E+09 | 257.58 | -22.3 | -22.8 | ||
Maximum of Months | 0.664136E+10 | 19277.58 | 26.13 | 22.79 | 0.266700E+09 | 347.89 | 26.13 | 22.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.978714E+09 | 6380.30 | 27-JAN-13:50 | -14.6 | -15.8 | 0.312464E+09 | 549.50 | 25-JAN-14:20 | -14.6 | -15.8 |
February | 0.179054E+10 | 9516.69 | 28-FEB-13:40 | 3.33 | -0.5 | 0.293640E+09 | 549.50 | 28-FEB-14:20 | 4.63 | 0.62 |
March | 0.237530E+10 | 10151.83 | 31-MAR-14:00 | 8.30 | 3.10 | 0.356293E+09 | 549.50 | 20-MAR-13:30 | 8.30 | 3.10 |
April | 0.406909E+10 | 11342.06 | 13-APR-13:30 | 18.35 | 7.09 | 0.335703E+09 | 549.50 | 19-APR-13:20 | 6.30 | 0.57 |
May | 0.706806E+10 | 13428.71 | 18-MAY-13:10 | 28.25 | 16.75 | 0.390294E+09 | 549.51 | 10-MAY-13:00 | 28.25 | 16.75 |
June | 0.837007E+10 | 14095.02 | 30-JUN-13:10 | 31.60 | 24.35 | 0.403847E+09 | 549.52 | 14-JUN-13:00 | 31.60 | 24.35 |
July | 0.924220E+10 | 19057.03 | 23-JUL-13:32 | 30.00 | 22.59 | 0.384751E+09 | 549.52 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.904460E+10 | 26947.33 | 13-AUG-14:02 | 23.22 | 14.47 | 0.413796E+09 | 549.52 | 22-AUG-13:09 | 23.98 | 16.30 |
September | 0.618958E+10 | 16364.76 | 01-SEP-13:10 | 24.60 | 17.97 | 0.344328E+09 | 549.53 | 07-SEP-13:09 | 23.90 | 14.19 |
October | 0.317546E+10 | 29763.22 | 22-OCT-13:42 | 19.22 | 12.83 | 0.330708E+09 | 549.50 | 19-OCT-13:09 | 19.22 | 12.83 |
November | 0.148747E+10 | 8566.85 | 17-NOV-13:03 | 10.10 | 3.25 | 0.318103E+09 | 549.50 | 17-NOV-14:30 | 10.60 | 3.43 |
December | 0.622723E+09 | 4573.54 | 20-DEC-13:40 | -20.6 | -21.3 | 0.296142E+09 | 494.10 | 20-DEC-14:20 | -19.8 | -20.5 |
Annual Sum or Average | 0.544138E+11 | 0.418007E+10 | ||||||||
Minimum of Months | 0.622723E+09 | 4573.54 | -20.6 | -21.3 | 0.293640E+09 | 494.10 | -19.8 | -20.5 | ||
Maximum of Months | 0.924220E+10 | 29763.22 | 31.60 | 24.35 | 0.413796E+09 | 549.53 | 31.60 | 24.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87844464.98 | 2409.32 | 27-JAN-15:50 | -14.4 | -15.6 | 0.192138E+09 | 257.59 | 13-JAN-10:20 | -14.4 | -15.6 |
February | 0.322191E+09 | 3237.74 | 08-FEB-16:30 | 3.85 | -1.1 | 0.176447E+09 | 310.45 | 08-FEB-16:40 | 3.67 | -1.2 |
March | 0.847790E+09 | 5109.92 | 31-MAR-16:00 | 8.90 | 3.77 | 0.214565E+09 | 338.69 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.222948E+10 | 14139.01 | 23-APR-16:22 | 26.40 | 16.81 | 0.198953E+09 | 341.64 | 13-APR-13:00 | 26.40 | 16.81 |
May | 0.505605E+10 | 12603.22 | 06-MAY-17:05 | 16.43 | 7.72 | 0.239392E+09 | 347.85 | 17-MAY-13:20 | 25.77 | 16.06 |
June | 0.606487E+10 | 18139.73 | 17-JUN-17:04 | 23.90 | 13.28 | 0.251124E+09 | 347.86 | 14-JUN-13:00 | 23.90 | 13.28 |
July | 0.654598E+10 | 19550.54 | 23-JUL-16:12 | 29.43 | 22.47 | 0.239797E+09 | 347.86 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.582846E+10 | 15796.43 | 13-AUG-15:22 | 22.50 | 14.78 | 0.254707E+09 | 347.85 | 22-AUG-13:00 | 24.40 | 16.49 |
September | 0.342746E+10 | 11013.16 | 03-SEP-17:22 | 21.15 | 15.79 | 0.206824E+09 | 347.84 | 01-SEP-13:20 | 21.15 | 15.79 |
October | 0.134450E+10 | 5854.47 | 19-OCT-16:00 | 21.70 | 13.55 | 0.200744E+09 | 338.68 | 20-OCT-15:39 | 18.50 | 9.98 |
November | 0.364162E+09 | 2897.33 | 17-NOV-15:40 | 10.20 | 3.28 | 0.191869E+09 | 287.14 | 17-NOV-15:50 | 10.10 | 3.24 |
December | 28264909.68 | 2197.51 | 02-DEC-17:01 | -20.0 | -20.5 | 0.185574E+09 | 257.59 | 18-DEC-14:39 | -22.8 | -23.5 |
Annual Sum or Average | 0.321471E+11 | 0.255213E+10 | ||||||||
Minimum of Months | 28264909.68 | 2197.51 | -20.0 | -20.5 | 0.176447E+09 | 257.59 | -22.8 | -23.5 | ||
Maximum of Months | 0.654598E+10 | 19550.54 | 29.43 | 22.47 | 0.254707E+09 | 347.86 | 26.40 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14918193.66 | 2382.87 | 21-JAN-17:01 | -5.0 | -7.1 | 0.302999E+09 | 406.85 | 03-JAN-10:39 | -5.0 | -7.1 |
February | 19365830.41 | 2372.74 | 04-FEB-17:02 | 6.83 | 1.98 | 0.276384E+09 | 406.85 | 13-FEB-14:50 | -19.1 | -20.0 |
March | 85142030.08 | 2381.72 | 25-MAR-16:02 | -0.1 | -1.5 | 0.331757E+09 | 406.84 | 13-MAR-13:30 | -0.1 | -1.5 |
April | 0.730816E+09 | 3100.62 | 23-APR-15:40 | 26.33 | 16.79 | 0.295772E+09 | 422.01 | 14-APR-13:09 | 26.33 | 16.79 |
May | 0.354740E+10 | 3866.50 | 26-MAY-13:40 | 22.17 | 17.18 | 0.351244E+09 | 525.76 | 26-MAY-13:50 | 21.83 | 16.91 |
June | 0.492082E+10 | 5530.37 | 29-JUN-15:00 | 34.40 | 24.01 | 0.384738E+09 | 549.49 | 27-JUN-13:20 | 34.40 | 24.01 |
July | 0.556513E+10 | 5583.82 | 21-JUL-14:00 | 28.90 | 22.62 | 0.382270E+09 | 549.49 | 05-JUL-13:20 | 28.90 | 22.62 |
August | 0.570589E+10 | 5313.29 | 09-AUG-15:30 | 27.25 | 21.19 | 0.417049E+09 | 549.49 | 23-AUG-13:20 | 25.77 | 20.28 |
September | 0.421924E+10 | 4403.38 | 03-SEP-11:22 | 19.45 | 15.45 | 0.337726E+09 | 545.29 | 01-SEP-13:00 | 19.45 | 15.45 |
October | 0.219555E+10 | 4336.00 | 22-OCT-13:42 | 19.22 | 12.83 | 0.314790E+09 | 466.71 | 20-OCT-13:00 | 19.22 | 12.83 |
November | 0.483947E+09 | 2858.14 | 01-NOV-14:02 | 17.88 | 13.29 | 0.303545E+09 | 428.44 | 01-NOV-13:00 | 17.88 | 13.29 |
December | 20520368.37 | 2388.29 | 30-DEC-17:02 | -3.3 | -3.3 | 0.293300E+09 | 406.85 | 12-DEC-14:50 | -3.3 | -3.3 |
Annual Sum or Average | 0.275087E+11 | 0.399157E+10 | ||||||||
Minimum of Months | 14918193.66 | 2372.74 | -5.0 | -7.1 | 0.276384E+09 | 406.84 | -19.1 | -20.0 | ||
Maximum of Months | 0.570589E+10 | 5583.82 | 34.40 | 24.01 | 0.417049E+09 | 549.49 | 34.40 | 24.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9836288.47 | 1569.26 | 21-JAN-17:01 | -5.0 | -7.1 | 0.192220E+09 | 257.57 | 10-JAN-14:09 | -5.0 | -7.1 |
February | 61114304.46 | 1569.13 | 04-FEB-17:02 | 6.83 | 1.98 | 0.175202E+09 | 257.56 | 16-FEB-10:50 | -16.1 | -16.6 |
March | 0.377498E+09 | 2058.95 | 31-MAR-09:50 | 1.42 | -1.1 | 0.211524E+09 | 289.16 | 31-MAR-09:00 | 1.70 | -0.9 |
April | 0.144293E+10 | 3269.53 | 18-APR-09:30 | 18.05 | 10.95 | 0.203382E+09 | 347.88 | 18-APR-09:39 | 18.13 | 11.06 |
May | 0.318260E+10 | 5744.74 | 18-MAY-09:30 | 24.55 | 16.00 | 0.247201E+09 | 347.89 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.445499E+10 | 6946.49 | 28-JUN-09:20 | 27.77 | 21.63 | 0.265431E+09 | 347.88 | 06-JUN-09:09 | 27.77 | 21.63 |
July | 0.539525E+10 | 7656.33 | 24-JUL-09:10 | 24.68 | 19.17 | 0.253718E+09 | 347.88 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.490309E+10 | 6902.38 | 25-AUG-09:30 | 21.70 | 17.32 | 0.276626E+09 | 347.88 | 04-AUG-09:00 | 21.70 | 17.32 |
September | 0.345261E+10 | 6254.01 | 01-SEP-09:20 | 20.57 | 17.76 | 0.229735E+09 | 347.88 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.177663E+10 | 3438.60 | 22-OCT-13:42 | 19.22 | 12.83 | 0.207311E+09 | 347.88 | 19-OCT-09:39 | 19.22 | 12.83 |
November | 0.505069E+09 | 1964.00 | 16-NOV-09:25 | 0.55 | -1.2 | 0.192930E+09 | 279.38 | 17-NOV-10:20 | 4.43 | 0.70 |
December | 18956474.90 | 1567.53 | 02-DEC-17:01 | -20.0 | -20.5 | 0.185835E+09 | 257.57 | 18-DEC-14:50 | -22.8 | -23.5 |
Annual Sum or Average | 0.255806E+11 | 0.264111E+10 | ||||||||
Minimum of Months | 9836288.47 | 1567.53 | -20.0 | -20.5 | 0.175202E+09 | 257.56 | -22.8 | -23.5 | ||
Maximum of Months | 0.539525E+10 | 7656.33 | 27.77 | 21.63 | 0.276626E+09 | 347.89 | 27.77 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97434121.41 | 2879.87 | 27-JAN-13:15 | -15.2 | -16.2 | 0.270021E+09 | 409.23 | 27-JAN-14:39 | -14.4 | -15.6 |
February | 0.455119E+09 | 3558.57 | 28-FEB-15:10 | 6.10 | 1.55 | 0.258822E+09 | 492.09 | 28-FEB-14:00 | 6.10 | 1.55 |
March | 0.585700E+09 | 3707.50 | 31-MAR-14:30 | 8.30 | 2.87 | 0.319673E+09 | 503.89 | 31-MAR-13:00 | 8.30 | 2.87 |
April | 0.172744E+10 | 6905.23 | 23-APR-15:39 | 26.33 | 16.79 | 0.309325E+09 | 549.50 | 13-APR-13:20 | 26.33 | 16.79 |
May | 0.421907E+10 | 10285.28 | 18-MAY-12:00 | 27.80 | 16.87 | 0.370472E+09 | 549.51 | 18-MAY-13:20 | 28.30 | 16.75 |
June | 0.568209E+10 | 14709.88 | 30-JUN-12:00 | 31.70 | 24.08 | 0.392874E+09 | 549.52 | 14-JUN-13:00 | 31.70 | 24.08 |
July | 0.709721E+10 | 12435.85 | 24-JUL-12:00 | 28.30 | 19.76 | 0.386989E+09 | 549.51 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.747385E+10 | 12799.43 | 08-AUG-16:10 | 30.40 | 23.01 | 0.424999E+09 | 549.52 | 22-AUG-13:09 | 23.98 | 16.30 |
September | 0.535550E+10 | 12618.78 | 01-SEP-13:30 | 25.00 | 18.03 | 0.353051E+09 | 549.52 | 07-SEP-13:09 | 23.90 | 14.19 |
October | 0.285847E+10 | 23637.62 | 22-OCT-13:42 | 19.22 | 12.83 | 0.330982E+09 | 549.50 | 18-OCT-13:20 | 19.22 | 12.83 |
November | 0.789953E+09 | 4601.22 | 17-NOV-13:50 | 10.50 | 3.40 | 0.303417E+09 | 549.50 | 17-NOV-14:20 | 10.60 | 3.43 |
December | 0.180914E+09 | 3452.17 | 02-DEC-13:50 | -18.3 | -19.0 | 0.265908E+09 | 406.81 | 27-DEC-14:30 | -5.3 | -5.8 |
Annual Sum or Average | 0.365227E+11 | 0.398653E+10 | ||||||||
Minimum of Months | 97434121.41 | 2879.87 | -18.3 | -19.0 | 0.258822E+09 | 406.81 | -14.4 | -15.6 | ||
Maximum of Months | 0.747385E+10 | 23637.62 | 31.70 | 24.08 | 0.424999E+09 | 549.52 | 31.70 | 24.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49070851.62 | 1792.11 | 27-JAN-15:50 | -14.4 | -15.6 | 0.191991E+09 | 257.56 | 12-JAN-10:39 | -14.4 | -15.6 |
February | 0.149843E+09 | 2280.95 | 08-FEB-16:40 | 3.67 | -1.2 | 0.175758E+09 | 293.96 | 08-FEB-16:49 | 3.48 | -1.2 |
March | 0.398625E+09 | 2671.13 | 28-MAR-17:10 | 7.20 | 3.39 | 0.211703E+09 | 306.76 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.128860E+10 | 5156.38 | 23-APR-15:39 | 26.33 | 16.79 | 0.194292E+09 | 338.67 | 13-APR-15:00 | 26.33 | 16.79 |
May | 0.338985E+10 | 7237.44 | 25-MAY-18:10 | 29.03 | 19.14 | 0.235952E+09 | 347.85 | 18-MAY-13:20 | 29.03 | 19.14 |
June | 0.422797E+10 | 9507.73 | 17-JUN-17:08 | 23.90 | 13.28 | 0.250340E+09 | 347.85 | 21-JUN-13:00 | 24.40 | 16.17 |
July | 0.515000E+10 | 11407.94 | 29-JUL-17:42 | 28.58 | 21.35 | 0.247896E+09 | 347.85 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.499727E+10 | 11278.70 | 05-AUG-17:06 | 22.70 | 14.24 | 0.271726E+09 | 347.85 | 28-AUG-13:20 | 20.60 | 18.71 |
September | 0.345896E+10 | 10807.92 | 03-SEP-17:22 | 21.15 | 15.79 | 0.221964E+09 | 347.85 | 07-SEP-13:20 | 23.90 | 14.25 |
October | 0.188263E+10 | 4898.50 | 19-OCT-16:00 | 21.70 | 13.55 | 0.206464E+09 | 338.68 | 20-OCT-15:00 | 18.30 | 9.93 |
November | 0.467850E+09 | 2349.15 | 17-NOV-15:50 | 10.10 | 3.24 | 0.193332E+09 | 300.23 | 17-NOV-15:00 | 10.00 | 3.20 |
December | 22153764.59 | 1642.06 | 02-DEC-17:01 | -20.0 | -20.5 | 0.185750E+09 | 257.58 | 18-DEC-10:09 | -21.8 | -22.5 |
Annual Sum or Average | 0.254828E+11 | 0.258717E+10 | ||||||||
Minimum of Months | 22153764.59 | 1642.06 | -20.0 | -20.5 | 0.175758E+09 | 257.56 | -21.8 | -22.5 | ||
Maximum of Months | 0.515000E+10 | 11407.94 | 29.03 | 21.35 | 0.271726E+09 | 347.85 | 29.03 | 19.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17958858.94 | 2346.16 | 21-JAN-17:01 | -5.0 | -7.1 | 0.303669E+09 | 406.85 | 04-JAN-14:39 | -5.0 | -7.1 |
February | 92955656.10 | 2365.06 | 04-FEB-17:02 | 6.83 | 1.98 | 0.276769E+09 | 406.82 | 01-FEB-10:39 | 6.83 | 1.98 |
March | 0.638375E+09 | 2858.53 | 31-MAR-16:00 | 8.90 | 3.77 | 0.333401E+09 | 430.05 | 28-MAR-13:00 | 8.90 | 3.77 |
April | 0.225988E+10 | 3603.79 | 13-APR-16:00 | 20.00 | 8.11 | 0.310877E+09 | 508.12 | 14-APR-13:20 | 16.10 | 7.09 |
May | 0.514508E+10 | 6139.00 | 26-MAY-13:30 | 22.50 | 17.44 | 0.395619E+09 | 549.50 | 25-MAY-09:00 | 22.50 | 17.44 |
June | 0.631572E+10 | 9867.71 | 30-JUN-04:01 | 26.10 | 22.87 | 0.420300E+09 | 549.51 | 14-JUN-13:00 | 26.10 | 22.87 |
July | 0.663420E+10 | 7281.87 | 21-JUL-13:30 | 28.60 | 22.53 | 0.397807E+09 | 549.50 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.618503E+10 | 6478.81 | 09-AUG-15:30 | 27.25 | 21.19 | 0.430739E+09 | 549.50 | 22-AUG-13:20 | 24.07 | 16.34 |
September | 0.427744E+10 | 5416.28 | 01-SEP-15:40 | 26.10 | 17.70 | 0.347828E+09 | 549.50 | 07-SEP-13:20 | 23.90 | 14.25 |
October | 0.224464E+10 | 3792.16 | 22-OCT-13:12 | 18.67 | 12.99 | 0.318508E+09 | 495.61 | 20-OCT-13:00 | 18.67 | 12.99 |
November | 0.582410E+09 | 2950.78 | 01-NOV-15:30 | 18.05 | 13.35 | 0.303393E+09 | 443.09 | 01-NOV-13:00 | 18.05 | 13.35 |
December | 21424048.56 | 2346.03 | 30-DEC-17:02 | -3.3 | -3.3 | 0.293357E+09 | 406.85 | 18-DEC-14:09 | -3.3 | -3.3 |
Annual Sum or Average | 0.344151E+11 | 0.413227E+10 | ||||||||
Minimum of Months | 17958858.94 | 2346.03 | -5.0 | -7.1 | 0.276769E+09 | 406.82 | -5.0 | -7.1 | ||
Maximum of Months | 0.663420E+10 | 9867.71 | 28.60 | 22.87 | 0.430739E+09 | 549.51 | 26.10 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22210658.61 | 2152.37 | 19-JAN-13:02 | -2.8 | -3.4 | 0.140884E+09 | 250.80 | 12-JAN-16:40 | -2.8 | -3.4 |
February | 0.192562E+09 | 2974.09 | 28-FEB-11:02 | -2.4 | -4.8 | 0.129074E+09 | 331.76 | 28-FEB-11:09 | -2.4 | -4.8 |
March | 0.817417E+09 | 4509.14 | 31-MAR-10:05 | 2.07 | -0.7 | 0.160889E+09 | 356.46 | 31-MAR-12:09 | 5.78 | 1.77 |
April | 0.239666E+10 | 7405.43 | 18-APR-10:05 | 18.12 | 11.26 | 0.160828E+09 | 356.46 | 18-APR-10:09 | 18.12 | 11.26 |
May | 0.456952E+10 | 11946.63 | 21-MAY-09:12 | 12.83 | 7.73 | 0.192237E+09 | 356.46 | 25-MAY-10:09 | 21.83 | 16.93 |
June | 0.592607E+10 | 14226.57 | 25-JUN-08:12 | 24.27 | 20.87 | 0.198780E+09 | 356.47 | 07-JUN-12:09 | 24.27 | 20.87 |
July | 0.644962E+10 | 15861.50 | 23-JUL-09:32 | 26.13 | 22.79 | 0.187946E+09 | 356.46 | 31-JUL-14:09 | 20.50 | 14.52 |
August | 0.539428E+10 | 10763.84 | 20-AUG-09:22 | 21.70 | 15.75 | 0.202403E+09 | 356.47 | 04-AUG-10:09 | 21.70 | 15.75 |
September | 0.352336E+10 | 9010.07 | 01-SEP-08:50 | 19.63 | 17.60 | 0.167742E+09 | 356.46 | 06-SEP-10:09 | 14.78 | 10.33 |
October | 0.154495E+10 | 5541.33 | 19-OCT-10:05 | 14.27 | 10.24 | 0.153541E+09 | 356.46 | 19-OCT-10:09 | 14.27 | 10.24 |
November | 0.449979E+09 | 3145.31 | 17-NOV-11:02 | 7.07 | 2.03 | 0.142696E+09 | 343.80 | 17-NOV-11:09 | 7.07 | 2.03 |
December | 31743649.79 | 2138.92 | 05-DEC-13:02 | -0.6 | -0.6 | 0.136076E+09 | 267.86 | 28-DEC-11:09 | -2.3 | -3.6 |
Annual Sum or Average | 0.313184E+11 | 0.197310E+10 | ||||||||
Minimum of Months | 22210658.61 | 2138.92 | -2.8 | -4.8 | 0.129074E+09 | 250.80 | -2.8 | -4.8 | ||
Maximum of Months | 0.644962E+10 | 15861.50 | 26.13 | 22.79 | 0.202403E+09 | 356.47 | 24.27 | 20.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112166E+10 | 7614.82 | 27-JAN-13:40 | -14.8 | -15.9 | 0.319708E+09 | 549.49 | 25-JAN-14:20 | -14.8 | -15.9 |
February | 0.191788E+10 | 10021.75 | 28-FEB-13:30 | 3.05 | -0.7 | 0.303172E+09 | 549.50 | 28-FEB-14:20 | 4.63 | 0.62 |
March | 0.263243E+10 | 10799.49 | 31-MAR-13:40 | 7.77 | 2.77 | 0.368626E+09 | 549.50 | 20-MAR-13:30 | 7.77 | 2.77 |
April | 0.433657E+10 | 11929.92 | 23-APR-14:42 | 25.40 | 16.41 | 0.349382E+09 | 549.50 | 19-APR-13:20 | 25.40 | 16.41 |
May | 0.676421E+10 | 12751.28 | 18-MAY-13:10 | 28.25 | 16.75 | 0.409226E+09 | 549.51 | 10-MAY-13:00 | 28.25 | 16.75 |
June | 0.773042E+10 | 17260.38 | 18-JUN-12:42 | 26.10 | 17.78 | 0.420435E+09 | 549.53 | 14-JUN-13:00 | 26.10 | 17.78 |
July | 0.864249E+10 | 17836.16 | 23-JUL-13:32 | 30.00 | 22.59 | 0.397417E+09 | 549.52 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.861694E+10 | 22920.59 | 13-AUG-13:32 | 23.13 | 14.35 | 0.436113E+09 | 550.02 | 08-AUG-13:20 | 23.13 | 14.35 |
September | 0.654959E+10 | 23742.21 | 04-SEP-12:42 | 16.02 | 9.65 | 0.366785E+09 | 549.98 | 01-SEP-13:20 | 16.02 | 9.65 |
October | 0.407835E+10 | 21681.80 | 22-OCT-13:12 | 18.67 | 12.99 | 0.344005E+09 | 549.52 | 19-OCT-13:09 | 18.67 | 12.99 |
November | 0.194237E+10 | 9897.66 | 17-NOV-13:03 | 10.10 | 3.25 | 0.326937E+09 | 549.50 | 17-NOV-10:30 | 10.10 | 3.25 |
December | 0.718745E+09 | 4506.32 | 20-DEC-13:13 | -21.1 | -21.6 | 0.302013E+09 | 549.50 | 20-DEC-14:20 | -19.8 | -20.5 |
Annual Sum or Average | 0.550516E+11 | 0.434382E+10 | ||||||||
Minimum of Months | 0.718745E+09 | 4506.32 | -21.1 | -21.6 | 0.302013E+09 | 549.49 | -19.8 | -20.5 | ||
Maximum of Months | 0.864249E+10 | 23742.21 | 30.00 | 22.59 | 0.436113E+09 | 550.02 | 28.25 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123712E+09 | 2436.05 | 27-JAN-15:50 | -14.4 | -15.6 | 0.192626E+09 | 269.99 | 27-JAN-15:00 | -14.4 | -15.6 |
February | 0.388923E+09 | 3148.86 | 08-FEB-16:30 | 3.85 | -1.1 | 0.177378E+09 | 322.42 | 08-FEB-16:40 | 3.67 | -1.2 |
March | 0.105382E+10 | 5329.13 | 31-MAR-16:00 | 8.90 | 3.77 | 0.216081E+09 | 338.69 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.254140E+10 | 13873.09 | 23-APR-16:42 | 26.20 | 16.72 | 0.201811E+09 | 345.44 | 13-APR-13:00 | 26.20 | 16.72 |
May | 0.515192E+10 | 13355.00 | 06-MAY-17:05 | 16.43 | 7.72 | 0.246289E+09 | 347.85 | 17-MAY-13:20 | 25.77 | 16.06 |
June | 0.594076E+10 | 17328.23 | 17-JUN-17:04 | 23.90 | 13.28 | 0.257476E+09 | 347.86 | 14-JUN-13:00 | 23.90 | 13.28 |
July | 0.641000E+10 | 18941.67 | 01-JUL-18:22 | 20.25 | 15.27 | 0.245779E+09 | 347.86 | 31-JUL-13:00 | 20.60 | 14.60 |
August | 0.585018E+10 | 16800.95 | 27-AUG-15:52 | 23.90 | 19.06 | 0.264471E+09 | 347.85 | 22-AUG-13:20 | 23.90 | 19.06 |
September | 0.389425E+10 | 12033.78 | 03-SEP-17:22 | 21.15 | 15.79 | 0.215263E+09 | 347.85 | 07-SEP-13:00 | 23.90 | 14.48 |
October | 0.196502E+10 | 5987.47 | 19-OCT-16:00 | 21.70 | 13.55 | 0.204563E+09 | 343.26 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.576647E+09 | 2921.92 | 17-NOV-15:40 | 10.20 | 3.28 | 0.193423E+09 | 305.27 | 17-NOV-15:50 | 10.10 | 3.24 |
December | 48398250.04 | 1993.12 | 02-DEC-17:01 | -20.0 | -20.5 | 0.185845E+09 | 257.56 | 18-DEC-10:09 | -21.8 | -22.5 |
Annual Sum or Average | 0.339450E+11 | 0.260100E+10 | ||||||||
Minimum of Months | 48398250.04 | 1993.12 | -20.0 | -20.5 | 0.177378E+09 | 257.56 | -21.8 | -22.5 | ||
Maximum of Months | 0.641000E+10 | 18941.67 | 26.20 | 19.06 | 0.264471E+09 | 347.86 | 26.20 | 19.06 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264391E+09 | 13691.56 | 02-JAN-05:01 | -18.2 |
February | 10658884.29 | 8954.50 | 21-FEB-06:11 | 2.80 |
March | 4504970.12 | 8089.39 | 06-MAR-06:01 | -19.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 2152426.41 | 7136.67 | 27-NOV-07:01 | -6.7 |
December | 57261510.14 | 10592.99 | 26-DEC-06:01 | -26.7 |
Annual Sum or Average | 0.338968E+09 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.264391E+09 | 13691.56 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242248E+11 | 32624.28 | 13-JAN-06:07 | -31.3 |
February | 0.161746E+11 | 32980.64 | 14-FEB-06:12 | -32.2 |
March | 0.111840E+11 | 29907.17 | 16-MAR-05:12 | -24.0 |
April | 0.393074E+10 | 22452.90 | 05-APR-05:03 | -13.4 |
May | 0.792631E+09 | 14661.96 | 02-MAY-05:02 | 0.10 |
June | 0.207851E+09 | 10740.18 | 17-JUN-05:03 | 5.55 |
July | 0.164342E+09 | 9809.09 | 18-JUL-05:02 | 8.27 |
August | 0.219149E+09 | 9276.99 | 25-AUG-05:02 | 7.88 |
September | 0.104551E+10 | 11213.98 | 06-SEP-05:03 | 1.28 |
October | 0.395114E+10 | 23282.45 | 30-OCT-05:15 | -9.8 |
November | 0.108361E+11 | 27225.98 | 25-NOV-06:05 | -19.4 |
December | 0.226194E+11 | 31287.41 | 21-DEC-06:06 | -27.3 |
Annual Sum or Average | 0.953503E+11 | |||
Minimum of Months | 0.164342E+09 | 9276.99 | -32.2 | |
Maximum of Months | 0.242248E+11 | 32980.64 | 8.27 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581264E+10 | 13772.65 | 02-JAN-08:13 | -19.6 |
February | 0.369575E+10 | 10510.83 | 27-FEB-07:15 | -19.0 |
March | 0.245455E+10 | 10490.89 | 06-MAR-07:03 | -19.3 |
April | 0.823871E+09 | 5657.93 | 23-APR-16:02 | 26.60 |
May | 0.121845E+09 | 5164.47 | 14-MAY-16:52 | 20.00 |
June | 23469143.86 | 5746.20 | 04-JUN-14:38 | 20.93 |
July | 25576076.65 | 4814.07 | 09-JUL-14:30 | 17.20 |
August | 22720327.16 | 5341.41 | 20-AUG-13:22 | 25.00 |
September | 51649779.91 | 6105.03 | 24-SEP-10:52 | 18.30 |
October | 0.797219E+09 | 7412.53 | 22-OCT-11:52 | 16.70 |
November | 0.256804E+10 | 11611.80 | 27-NOV-07:11 | -6.7 |
December | 0.514580E+10 | 13664.99 | 26-DEC-08:17 | -26.2 |
Annual Sum or Average | 0.215431E+11 | |||
Minimum of Months | 22720327.16 | 4814.07 | -26.2 | |
Maximum of Months | 0.581264E+10 | 13772.65 | 26.60 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391872E+10 | 11037.91 | 02-JAN-09:30 | -18.6 |
February | 0.215488E+10 | 6606.77 | 27-FEB-08:23 | -17.2 |
March | 0.128813E+10 | 6313.20 | 06-MAR-09:00 | -17.8 |
April | 0.275752E+09 | 3733.66 | 23-APR-15:39 | 26.33 |
May | 11445208.83 | 3528.50 | 21-MAY-15:12 | 22.67 |
June | 3622935.47 | 3470.28 | 30-JUN-04:01 | 26.10 |
July | 11529694.40 | 3702.40 | 09-JUL-15:07 | 18.48 |
August | 12461834.73 | 4320.52 | 27-AUG-11:17 | 19.27 |
September | 13922385.80 | 4050.42 | 24-SEP-11:12 | 18.87 |
October | 0.160451E+09 | 5450.74 | 04-OCT-05:01 | -0.5 |
November | 0.117247E+10 | 6078.48 | 27-NOV-07:01 | -6.7 |
December | 0.322800E+10 | 8551.49 | 26-DEC-09:50 | -24.6 |
Annual Sum or Average | 0.122514E+11 | |||
Minimum of Months | 3622935.47 | 3470.28 | -24.6 | |
Maximum of Months | 0.391872E+10 | 11037.91 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159303E+10 | 22126.25 | 02-JAN-05:01 | -18.2 |
February | 0.517327E+09 | 19590.46 | 27-FEB-05:01 | -17.4 |
March | 0.228608E+09 | 19315.50 | 06-MAR-05:11 | -18.5 |
April | 27591181.76 | 16139.41 | 10-APR-05:01 | -2.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 17291277.62 | 15844.31 | 30-OCT-05:01 | -9.9 |
November | 0.317349E+09 | 19617.80 | 27-NOV-05:01 | -7.2 |
December | 0.105078E+10 | 21699.52 | 26-DEC-05:11 | -26.1 |
Annual Sum or Average | 0.375198E+10 | |||
Minimum of Months | 0.00 | 0.00 | -26.1 | |
Maximum of Months | 0.159303E+10 | 22126.25 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.835175E+10 | 38244.54 | 01-JAN-03:21 | -26.7 |
February | 0.431048E+10 | 37545.86 | 13-FEB-05:11 | -23.5 |
March | 0.232201E+10 | 37201.69 | 06-MAR-05:11 | -18.5 |
April | 0.585460E+09 | 34025.91 | 03-APR-04:01 | -5.4 |
May | 37667828.06 | 29923.52 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 259559.08 | 1297.80 | 19-AUG-06:03 | 6.23 |
September | 12397681.80 | 16004.06 | 23-SEP-06:03 | 4.32 |
October | 0.522532E+09 | 35237.62 | 30-OCT-04:01 | -10.0 |
November | 0.255889E+10 | 36897.77 | 27-NOV-05:01 | -7.2 |
December | 0.709380E+10 | 38114.57 | 26-DEC-04:41 | -25.6 |
Annual Sum or Average | 0.257952E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.835175E+10 | 38244.54 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131268E+11 | 20071.78 | 06-JAN-05:11 | -34.8 |
February | 0.842021E+10 | 20284.89 | 13-FEB-05:11 | -23.5 |
March | 0.520997E+10 | 18511.28 | 05-MAR-23:12 | -13.5 |
April | 0.132937E+10 | 17029.72 | 10-APR-04:01 | -2.8 |
May | 92340137.79 | 14321.74 | 01-MAY-05:01 | -3.4 |
June | 1330043.05 | 4534.66 | 10-JUN-06:03 | 15.68 |
July | 583279.43 | 2424.72 | 08-JUL-06:03 | 11.97 |
August | 7805025.44 | 7636.95 | 19-AUG-05:13 | 4.80 |
September | 99922887.92 | 13164.01 | 23-SEP-05:12 | 4.80 |
October | 0.111766E+10 | 17540.19 | 30-OCT-04:01 | -10.0 |
November | 0.473448E+10 | 18075.07 | 25-NOV-05:11 | -19.1 |
December | 0.121399E+11 | 19744.96 | 18-DEC-05:11 | -15.4 |
Annual Sum or Average | 0.462804E+11 | |||
Minimum of Months | 583279.43 | 2424.72 | -34.8 | |
Maximum of Months | 0.131268E+11 | 20284.89 | 15.68 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787932E+10 | 13126.98 | 06-JAN-05:11 | -34.8 |
February | 0.466129E+10 | 13270.07 | 13-FEB-05:11 | -23.5 |
March | 0.272462E+10 | 12088.24 | 06-MAR-05:11 | -18.5 |
April | 0.622340E+09 | 11135.25 | 10-APR-04:01 | -2.8 |
May | 27146710.32 | 9310.94 | 01-MAY-05:01 | -3.4 |
June | 581644.59 | 2908.22 | 10-JUN-06:03 | 15.68 |
July | 320516.88 | 1602.58 | 08-JUL-06:03 | 11.97 |
August | 3209225.22 | 5090.40 | 19-AUG-05:13 | 4.80 |
September | 48555372.40 | 8640.41 | 23-SEP-05:12 | 4.80 |
October | 0.652414E+09 | 11497.54 | 30-OCT-04:01 | -10.0 |
November | 0.285197E+10 | 11826.45 | 25-NOV-05:11 | -19.1 |
December | 0.745674E+10 | 12919.93 | 18-DEC-05:11 | -15.4 |
Annual Sum or Average | 0.269285E+11 | |||
Minimum of Months | 320516.88 | 1602.58 | -34.8 | |
Maximum of Months | 0.787932E+10 | 13270.07 | 15.68 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.953811E+10 | 20123.44 | 06-JAN-05:11 | -34.8 |
February | 0.566181E+10 | 20395.65 | 13-FEB-05:11 | -23.5 |
March | 0.364974E+10 | 18614.89 | 05-MAR-05:12 | -27.9 |
April | 0.104874E+10 | 17204.96 | 10-APR-04:01 | -2.8 |
May | 96251728.97 | 14493.50 | 01-MAY-05:01 | -3.4 |
June | 6839080.75 | 4950.12 | 03-JUN-06:03 | 8.07 |
July | 1287594.73 | 4478.28 | 10-JUL-06:03 | 11.75 |
August | 8829820.45 | 7316.78 | 19-AUG-05:13 | 4.80 |
September | 83303975.98 | 13205.11 | 23-SEP-05:12 | 4.80 |
October | 0.878998E+09 | 17747.32 | 30-OCT-04:01 | -10.0 |
November | 0.363553E+10 | 18243.02 | 25-NOV-05:11 | -19.1 |
December | 0.922445E+10 | 19895.35 | 18-DEC-05:11 | -15.4 |
Annual Sum or Average | 0.338339E+11 | |||
Minimum of Months | 1287594.73 | 4478.28 | -34.8 | |
Maximum of Months | 0.953811E+10 | 20395.65 | 11.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.811919E+10 | 13797.53 | 06-JAN-05:11 | -34.8 |
February | 0.499826E+10 | 13941.59 | 13-FEB-05:11 | -23.5 |
March | 0.300698E+10 | 12668.36 | 06-MAR-05:11 | -18.5 |
April | 0.777379E+09 | 11605.16 | 10-APR-04:01 | -2.8 |
May | 63366073.59 | 9704.04 | 01-MAY-05:01 | -3.4 |
June | 4210067.15 | 2997.83 | 03-JUN-06:03 | 8.07 |
July | 636465.61 | 2300.77 | 10-JUL-06:03 | 11.75 |
August | 7085050.68 | 5454.39 | 19-AUG-05:13 | 4.80 |
September | 63118197.34 | 8830.26 | 23-SEP-05:12 | 4.80 |
October | 0.699442E+09 | 11985.72 | 30-OCT-04:01 | -10.0 |
November | 0.297768E+10 | 12389.76 | 25-NOV-05:11 | -19.1 |
December | 0.763219E+10 | 13569.45 | 18-DEC-05:11 | -15.4 |
Annual Sum or Average | 0.283495E+11 | |||
Minimum of Months | 636465.61 | 2300.77 | -34.8 | |
Maximum of Months | 0.811919E+10 | 13941.59 | 11.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105790E+11 | 14628.10 | 01-JAN-08:61 | -26.7 |
February | 0.686042E+10 | 14200.84 | 13-FEB-04:21 | -23.1 |
March | 0.560554E+10 | 13979.33 | 06-MAR-05:01 | -18.4 |
April | 0.151736E+10 | 13162.76 | 03-APR-04:11 | -5.2 |
May | 87641488.25 | 11249.09 | 01-MAY-05:01 | -3.4 |
June | 738971.40 | 2928.10 | 10-JUN-06:03 | 15.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 413268.24 | 2066.34 | 19-AUG-06:03 | 6.23 |
September | 8556910.34 | 5367.54 | 23-SEP-06:03 | 4.32 |
October | 0.204558E+09 | 11206.49 | 30-OCT-05:01 | -9.9 |
November | 0.201787E+10 | 13157.01 | 25-NOV-05:01 | -19.0 |
December | 0.829376E+10 | 14076.12 | 25-DEC-05:32 | -29.5 |
Annual Sum or Average | 0.351759E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.5 | |
Maximum of Months | 0.105790E+11 | 14628.10 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.618644E+10 | 9614.79 | 01-JAN-08:61 | -26.7 |
February | 0.353591E+10 | 9337.56 | 13-FEB-04:21 | -23.1 |
March | 0.260917E+10 | 9187.47 | 05-MAR-05:12 | -27.9 |
April | 0.516978E+09 | 8579.95 | 03-APR-04:11 | -5.2 |
May | 11255549.01 | 7328.09 | 01-MAY-05:01 | -3.4 |
June | 277710.97 | 1388.55 | 10-JUN-06:03 | 15.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 3800506.85 | 3213.24 | 29-SEP-06:03 | 7.30 |
October | 0.107876E+09 | 7365.35 | 30-OCT-05:01 | -9.9 |
November | 0.116941E+10 | 8679.85 | 25-NOV-05:01 | -19.0 |
December | 0.494890E+10 | 9282.51 | 25-DEC-05:32 | -29.5 |
Annual Sum or Average | 0.190900E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.5 | |
Maximum of Months | 0.618644E+10 | 9614.79 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130074E+11 | 21668.06 | 06-JAN-07:10 | -35.0 |
February | 0.811229E+10 | 21123.81 | 14-FEB-07:11 | -32.8 |
March | 0.751309E+10 | 18638.50 | 15-MAR-07:00 | -23.9 |
April | 0.294017E+10 | 15516.94 | 05-APR-06:10 | -13.5 |
May | 0.849507E+09 | 13039.05 | 01-MAY-06:10 | -3.5 |
June | 0.198047E+09 | 9718.51 | 02-JUN-06:03 | 9.08 |
July | 29289459.63 | 7227.12 | 10-JUL-06:03 | 11.75 |
August | 82016348.86 | 9001.96 | 18-AUG-06:03 | 11.10 |
September | 0.658088E+09 | 10092.06 | 21-SEP-06:10 | 5.10 |
October | 0.200587E+10 | 14639.03 | 30-OCT-06:50 | -9.4 |
November | 0.445847E+10 | 16738.22 | 29-NOV-07:50 | -16.6 |
December | 0.113487E+11 | 20466.30 | 20-DEC-08:00 | -29.2 |
Annual Sum or Average | 0.512030E+11 | |||
Minimum of Months | 29289459.63 | 7227.12 | -35.0 | |
Maximum of Months | 0.130074E+11 | 21668.06 | 11.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.637338E+10 | 9923.18 | 01-JAN-08:61 | -26.7 |
February | 0.374351E+10 | 9621.03 | 13-FEB-04:21 | -23.1 |
March | 0.279920E+10 | 9474.49 | 06-MAR-05:01 | -18.4 |
April | 0.661657E+09 | 8752.46 | 10-APR-04:01 | -2.8 |
May | 37773378.37 | 7572.17 | 01-MAY-05:01 | -3.4 |
June | 1533158.38 | 2746.40 | 01-JUN-06:03 | 15.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 525691.33 | 2628.46 | 19-AUG-06:03 | 6.23 |
September | 3744620.88 | 3060.37 | 21-SEP-06:03 | 5.10 |
October | 0.119179E+09 | 7557.71 | 30-OCT-05:01 | -9.9 |
November | 0.120770E+10 | 8993.49 | 25-NOV-05:01 | -19.0 |
December | 0.509988E+10 | 9514.50 | 10-DEC-23:51 | -27.8 |
Annual Sum or Average | 0.200481E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.8 | |
Maximum of Months | 0.637338E+10 | 9923.18 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.897227E+10 | 14295.65 | 09-JAN-04:41 | -33.1 |
February | 0.507976E+10 | 14054.76 | 13-FEB-04:21 | -23.1 |
March | 0.279043E+10 | 13751.43 | 06-MAR-05:11 | -18.5 |
April | 0.448182E+09 | 12346.57 | 03-APR-04:01 | -5.4 |
May | 13770142.83 | 10263.89 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 476611.03 | 2383.06 | 19-AUG-06:03 | 6.23 |
September | 12018484.93 | 5845.98 | 23-SEP-06:03 | 4.32 |
October | 0.300402E+09 | 12321.44 | 30-OCT-04:01 | -10.0 |
November | 0.217709E+10 | 13222.81 | 25-NOV-05:11 | -19.1 |
December | 0.786721E+10 | 14354.76 | 10-DEC-19:02 | -25.1 |
Annual Sum or Average | 0.276616E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.1 | |
Maximum of Months | 0.897227E+10 | 14354.76 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527095E+10 | 10721.05 | 09-JAN-04:41 | -33.1 |
February | 0.266448E+10 | 10490.26 | 13-FEB-04:21 | -23.1 |
March | 0.139175E+10 | 10227.70 | 06-MAR-05:11 | -18.5 |
April | 0.192020E+09 | 9044.72 | 03-APR-04:01 | -5.4 |
May | 3942124.32 | 7250.34 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 7611547.77 | 3557.63 | 28-SEP-06:03 | 6.70 |
October | 0.182711E+09 | 9170.71 | 30-OCT-04:01 | -10.0 |
November | 0.132888E+10 | 9821.39 | 25-NOV-05:11 | -19.1 |
December | 0.476076E+10 | 10695.96 | 25-DEC-04:31 | -29.9 |
Annual Sum or Average | 0.158031E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.1 | |
Maximum of Months | 0.527095E+10 | 10721.05 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.585875E+10 | 14509.97 | 09-JAN-04:41 | -33.1 |
February | 0.294906E+10 | 14161.88 | 13-FEB-04:21 | -23.1 |
March | 0.172271E+10 | 13820.40 | 06-MAR-05:11 | -18.5 |
April | 0.326407E+09 | 12060.47 | 10-APR-04:01 | -2.8 |
May | 16069368.97 | 10144.98 | 01-MAY-05:01 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 707432.62 | 3537.16 | 19-AUG-06:03 | 6.23 |
September | 9215215.50 | 5718.83 | 23-SEP-06:03 | 4.32 |
October | 0.228919E+09 | 12449.06 | 30-OCT-04:01 | -10.0 |
November | 0.157553E+10 | 13374.38 | 25-NOV-05:11 | -19.1 |
December | 0.542246E+10 | 14384.55 | 25-DEC-04:31 | -29.9 |
Annual Sum or Average | 0.181098E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.1 | |
Maximum of Months | 0.585875E+10 | 14509.97 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.551542E+10 | 11042.49 | 09-JAN-04:41 | -33.1 |
February | 0.295755E+10 | 10799.93 | 13-FEB-04:21 | -23.1 |
March | 0.156712E+10 | 10525.34 | 06-MAR-05:11 | -18.5 |
April | 0.259354E+09 | 9116.55 | 03-APR-04:01 | -5.4 |
May | 12660544.06 | 7410.58 | 01-MAY-05:01 | -3.4 |
June | 2870.51 | 14.35 | 10-JUN-06:03 | 15.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 889496.82 | 3133.79 | 19-AUG-06:03 | 6.23 |
September | 9523995.40 | 3600.72 | 23-SEP-06:03 | 4.32 |
October | 0.201285E+09 | 9373.45 | 30-OCT-04:01 | -10.0 |
November | 0.138798E+10 | 10114.31 | 25-NOV-05:11 | -19.1 |
December | 0.492179E+10 | 10943.75 | 25-DEC-04:31 | -29.9 |
Annual Sum or Average | 0.168336E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.1 | |
Maximum of Months | 0.551542E+10 | 11042.49 | 15.83 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197255E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167686E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113264E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6035669.43 | 0.991562E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4237406.33 | 0.476606E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19888458.63 | 0.250631E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22809742.64 | 0.183729E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9840974.02 | 0.241943E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 327658.84 | 0.433704E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.92 | 0.679008E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128239E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209220E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63140084.81 | 0.114138E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183729E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22809742.64 | 0.209220E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131474E+10 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111924E+10 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761604E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3443455.61 | 0.682615E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2588453.80 | 0.334198E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10853397.63 | 0.177873E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13057338.08 | 0.128124E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4604012.48 | 0.175964E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124532.20 | 0.303150E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459899E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856143E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139441E+10 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34671189.81 | 0.770795E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128124E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13057338.08 | 0.139441E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198101E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170851E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116957E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1644073.96 | 0.104747E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3774542.70 | 0.497176E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16633788.39 | 0.255740E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19303819.84 | 0.190013E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5805751.23 | 0.265340E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173094.83 | 0.477177E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717892E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130716E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210205E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47335070.94 | 0.117191E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190013E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19303819.84 | 0.210205E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131497E+10 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112340E+10 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767162E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 339489.71 | 0.684200E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2461347.52 | 0.337870E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11906619.16 | 0.174723E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13038086.82 | 0.133612E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5161138.67 | 0.175358E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 156939.47 | 0.304747E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461490E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855967E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139433E+10 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33063621.36 | 0.772783E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133612E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13038086.82 | 0.139433E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105422E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897776E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604574E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4169872.45 | 0.528096E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3597538.94 | 0.240839E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12472864.09 | 0.124666E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13212254.03 | 96904418.63 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5137221.22 | 0.138117E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 168499.65 | 0.253381E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.45 | 0.400468E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722828E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112602E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38758354.84 | 0.618788E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96904418.63 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13212254.03 | 0.112602E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702867E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600883E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407903E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1979608.06 | 0.367292E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1646176.87 | 0.174908E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6021731.57 | 95094838.38 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7157283.21 | 71014787.84 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2229328.82 | 0.104513E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65334.13 | 0.181096E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273768E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484399E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750471E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19099462.67 | 0.421421E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71014787.84 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7157283.21 | 0.750471E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107875E+11 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830998E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777469E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 966672.63 | 0.448023E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110889E+09 | 0.212016E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255465E+09 | 0.967183E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227294E+09 | 0.685230E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122585E+09 | 0.124028E+10 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5158677.68 | 0.254450E+10 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438995E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598120E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951054E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722359E+09 | 0.587914E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685230E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255465E+09 | 0.107875E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703009E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602681E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410230E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306285.31 | 0.367858E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1523198.59 | 0.178586E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6263416.34 | 92332774.78 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6885524.44 | 75723563.50 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2464720.78 | 0.105698E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65916.51 | 0.182189E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274357E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483978E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750552E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17509061.97 | 0.422720E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75723563.50 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6885524.44 | 0.750552E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165248E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141305E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970366E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4445804.29 | 0.879302E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3124963.42 | 0.426806E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15069325.39 | 0.229644E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17397326.90 | 0.168872E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6912326.96 | 0.226732E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 153479.11 | 0.398880E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614768E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111164E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175836E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47103226.07 | 0.985090E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168872E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17397326.90 | 0.175836E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110018E+10 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944357E+09 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654642E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2907433.88 | 0.606341E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2073047.75 | 0.295602E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8844692.58 | 0.159172E+09 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10788843.99 | 0.114263E+09 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3712266.73 | 0.160056E+09 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97419.53 | 0.275962E+09 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417182E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743521E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117039E+10 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28423704.46 | 0.664167E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114263E+09 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10788843.99 | 0.117039E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166520E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145532E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100887E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 826141.73 | 0.930346E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3029680.88 | 0.443614E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12571263.95 | 0.232976E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14986085.45 | 0.173794E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4642251.94 | 0.245791E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 146702.23 | 0.433768E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648318E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114203E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177567E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36202126.19 | 0.101557E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173794E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14986085.45 | 0.177567E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110142E+10 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948429E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657672E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 176389.64 | 0.604548E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2044294.71 | 0.297707E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9789133.73 | 0.156015E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10690118.47 | 0.119196E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4137150.31 | 0.158534E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116301.85 | 0.274529E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415929E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742215E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117133E+10 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26953388.72 | 0.664752E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119196E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10690118.47 | 0.117133E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220590E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194019E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133990E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2490790.71 | 0.126199E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3026919.52 | 0.604692E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14723836.22 | 0.324936E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16663271.43 | 0.242543E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4504491.96 | 0.341616E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95785.81 | 0.597411E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904791E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159224E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238264E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41505095.66 | 0.137388E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242543E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16663271.43 | 0.238264E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277824E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241850E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168295E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3961367.81 | 0.156193E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3666836.05 | 0.761317E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19228802.54 | 0.408868E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21797322.21 | 0.301682E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6646240.74 | 0.417225E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125444.12 | 0.721373E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108157E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193315E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297787E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55426013.46 | 0.170447E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301682E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21797322.21 | 0.297787E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287423E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247303E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169349E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922000.39 | 0.153074E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1624487.79 | 0.750982E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15197915.79 | 0.399688E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12989620.58 | 0.295108E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3045314.37 | 0.400151E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10737.32 | 0.690399E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101920E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188407E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304323E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33790076.24 | 0.170543E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295108E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15197915.79 | 0.304323E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3598.28 | 04-JAN-05:57 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4283.51 | 12-FEB-22:57 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2175.90 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.70 | 23-APR-15:50 | 1587.32 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 24-MAY-15:00 | 866.79 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.82 | 18-JUN-12:40 | 556.80 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 442.63 | 23-JUL-15:00 | 563.56 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.13 | 20-AUG-14:00 | 717.79 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 01-SEP-15:00 | 942.30 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 19-OCT-15:00 | 1447.37 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2267.31 | 21-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3493.33 | 16-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.80 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 462.70 | 4283.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2398.79 | 04-JAN-05:56 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2855.53 | 12-FEB-22:53 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1450.56 | 15-MAR-05:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.82 | 23-APR-15:50 | 1056.46 | 01-APR-18:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 | 24-MAY-15:00 | 609.38 | 14-MAY-08:20 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.82 | 24-JUN-17:02 | 370.35 | 18-JUN-07:10 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.21 | 23-JUL-15:00 | 369.35 | 06-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.75 | 20-AUG-14:00 | 487.71 | 27-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 01-SEP-15:00 | 626.24 | 20-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 964.49 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1510.01 | 21-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2328.95 | 16-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.35 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 295.82 | 2855.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3598.27 | 04-JAN-05:57 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4283.48 | 12-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2175.90 | 15-MAR-04:57 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.57 | 23-APR-17:50 | 1778.60 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 24-MAY-15:00 | 881.26 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.41 | 24-JUN-17:20 | 555.17 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.08 | 23-JUL-15:00 | 565.03 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 | 08-AUG-16:00 | 737.62 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 01-SEP-15:00 | 948.99 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1448.53 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2266.69 | 21-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3493.38 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.17 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 348.08 | 4283.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2398.82 | 04-JAN-05:59 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2855.66 | 12-FEB-22:55 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1450.58 | 15-MAR-04:57 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.74 | 23-APR-13:23 | 1066.90 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 | 24-MAY-15:00 | 590.52 | 29-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.00 | 18-JUN-12:00 | 369.45 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.22 | 23-JUL-15:00 | 438.55 | 16-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.94 | 20-AUG-11:00 | 492.04 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 01-SEP-15:00 | 623.23 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 963.90 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1509.13 | 21-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2329.00 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.45 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 211.22 | 2855.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1894.05 | 04-JAN-05:51 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2251.39 | 12-FEB-22:52 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1155.39 | 15-MAR-04:58 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.34 | 23-APR-16:00 | 862.94 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.02 | 24-MAY-17:20 | 438.91 | 20-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.32 | 24-JUN-17:02 | 284.60 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.86 | 23-JUL-14:41 | 300.35 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.73 | 20-AUG-14:00 | 413.32 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 01-SEP-15:00 | 567.69 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 19-OCT-15:00 | 774.67 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1305.29 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1832.04 | 16-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.60 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 296.34 | 2251.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1262.60 | 04-JAN-05:51 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1500.75 | 12-FEB-22:52 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 770.25 | 15-MAR-05:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.83 | 23-APR-16:00 | 579.61 | 01-APR-19:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 | 24-MAY-18:00 | 299.88 | 20-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.23 | 24-JUN-17:02 | 198.37 | 20-JUN-04:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.44 | 23-JUL-15:10 | 209.12 | 06-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 08-AUG-16:00 | 296.17 | 27-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 01-SEP-15:00 | 378.04 | 20-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 516.55 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 864.64 | 22-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1220.25 | 16-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.37 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 162.83 | 1500.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 50105.78 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 47938.24 | 14-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 37994.39 | 16-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.62 | 23-APR-17:40 | 29093.34 | 05-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.76 | 25-MAY-17:00 | 19801.49 | 01-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8239.94 | 29-JUN-16:10 | 9833.00 | 02-JUN-06:10 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4075.02 | 28-JUL-16:10 | 8021.36 | 18-JUL-06:05 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4966.42 | 08-AUG-16:10 | 9852.79 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.03 | 01-SEP-16:10 | 15437.20 | 06-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 25467.07 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 33972.08 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 44361.20 | 20-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8021.36 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8239.94 | 50105.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1262.24 | 04-JAN-05:51 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1500.85 | 12-FEB-22:52 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 770.26 | 15-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.78 | 23-APR-16:00 | 587.85 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 24-MAY-15:00 | 300.59 | 20-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 | 25-JUN-10:50 | 195.58 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 23-JUL-14:41 | 247.84 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.90 | 20-AUG-11:00 | 302.04 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 01-SEP-15:00 | 378.89 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 516.15 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 862.40 | 22-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1220.87 | 16-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.58 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 118.53 | 1500.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2963.87 | 04-JAN-05:51 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3518.48 | 12-FEB-22:52 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1810.08 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.01 | 23-APR-16:10 | 1415.82 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 24-MAY-15:00 | 738.03 | 20-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.46 | 24-JUN-17:02 | 504.94 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.37 | 23-JUL-15:00 | 505.90 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.47 | 20-AUG-14:10 | 658.30 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 | 01-SEP-15:00 | 862.68 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1210.98 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1952.95 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2905.80 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.94 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 361.01 | 3518.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1975.89 | 04-JAN-05:51 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2344.72 | 12-FEB-22:52 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1206.70 | 15-MAR-04:57 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.32 | 23-APR-16:10 | 941.33 | 01-APR-19:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 24-MAY-15:00 | 546.81 | 14-MAY-07:40 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.04 | 24-JUN-17:02 | 331.87 | 20-JUN-04:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.86 | 23-JUL-15:00 | 326.34 | 06-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.16 | 20-AUG-14:10 | 444.22 | 27-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 01-SEP-15:00 | 572.74 | 20-SEP-01:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 807.12 | 31-OCT-21:03 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1291.52 | 22-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1925.59 | 16-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.34 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 245.32 | 2344.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2966.11 | 04-JAN-05:51 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3523.11 | 12-FEB-22:52 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1810.08 | 15-MAR-04:55 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.85 | 23-APR-17:30 | 1602.99 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.70 | 24-MAY-15:00 | 745.44 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.42 | 24-JUN-17:02 | 503.29 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.96 | 23-JUL-15:00 | 506.82 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.16 | 08-AUG-16:00 | 672.69 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 01-SEP-15:00 | 868.85 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1212.12 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1947.81 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2905.80 | 16-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.29 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 254.96 | 3523.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1975.32 | 04-JAN-05:51 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2344.33 | 12-FEB-22:52 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1206.70 | 15-MAR-04:58 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 23-APR-13:30 | 948.18 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 24-MAY-15:00 | 499.60 | 29-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.20 | 18-JUN-12:10 | 333.30 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.64 | 23-JUL-15:00 | 373.33 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.26 | 20-AUG-10:50 | 448.19 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 01-SEP-15:00 | 567.98 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 806.77 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1284.70 | 22-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1937.20 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.30 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 171.64 | 2344.33 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3793.56 | 04-JAN-05:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4813.96 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2375.01 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.18 | 23-APR-16:00 | 2073.63 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.82 | 24-MAY-15:00 | 1058.22 | 20-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.17 | 24-JUN-17:02 | 712.28 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.24 | 23-JUL-14:52 | 701.66 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.90 | 08-AUG-16:00 | 976.27 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.13 | 01-SEP-15:00 | 1269.73 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1615.35 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2929.34 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3824.54 | 16-DEC-05:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.66 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.24 | 4813.96 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4830.31 | 04-JAN-05:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5909.67 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3005.63 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.74 | 23-APR-15:51 | 2559.32 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.24 | 24-MAY-15:00 | 1337.52 | 20-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.44 | 24-JUN-17:02 | 899.84 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.39 | 23-JUL-15:00 | 889.92 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.67 | 08-AUG-16:00 | 1200.51 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.85 | 01-SEP-15:00 | 1556.89 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2007.48 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3568.07 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4769.27 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.39 | 5909.67 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5045.25 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6044.62 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3058.55 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.10 | 23-APR-16:00 | 2450.85 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.45 | 24-MAY-16:00 | 1402.73 | 29-MAY-18:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.10 | 29-JUN-21:02 | 776.94 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.20 | 15-JUL-17:02 | 737.42 | 16-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.48 | 08-AUG-16:00 | 1069.32 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 01-SEP-16:00 | 1385.08 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2110.63 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3321.13 | 21-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4813.02 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.20 | 6044.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 10038.51 | 27-JAN-16:30 | 12070.02 | 19521.22 | 28515.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11355.42 | 10-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15923.18 | 31-MAR-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28331.93 | 20-APR-05:01 | 5082.11 | 8676.10 | 61874.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38575.97 | 26-MAY-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47534.82 | 30-JUN-04:01 | 0.00 | 7591.59 | 41762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 48907.86 | 31-JUL-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 48904.48 | 28-AUG-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46909.86 | 05-SEP-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39460.77 | 25-OCT-05:01 | 5082.11 | 8676.10 | 61874.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16380.36 | 17-NOV-16:20 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11045.83 | 01-DEC-15:30 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10038.51 | 0.00 | 4338.05 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48907.86 | 12070.02 | 19521.22 | 61874.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1724.28 |
February | 1318.19 | 08-FEB-14:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.17 |
March | 5131.00 | 26-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 859.32 |
April | 8753.72 | 23-APR-14:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.47 |
May | 15333.39 | 18-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 | 0.00 |
June | 17597.47 | 30-JUN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.78 | 0.00 |
July | 16070.40 | 24-JUL-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 | 0.00 |
August | 14673.08 | 08-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.67 | 0.00 |
September | 12434.36 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 |
October | 6604.89 | 22-OCT-13:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.59 |
November | 2480.42 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.79 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17597.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.78 | 1724.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7709.64 | 21-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7028.53 | 10-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1775.39 |
March | 7356.73 | 08-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.96 |
April | 4622.64 | 05-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 956.07 |
May | 4217.35 | 18-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.15 | 0.00 |
June | 5744.01 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.43 | 0.00 |
July | 5225.40 | 24-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.44 | 0.00 |
August | 4133.56 | 08-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.67 | 0.00 |
September | 4153.62 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 0.00 |
October | 4140.80 | 06-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.35 |
November | 4977.60 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 850.10 |
December | 6589.98 | 29-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4133.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7709.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.67 | 1775.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8423.83 | 21-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8683.41 | 10-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.00 |
March | 9244.34 | 23-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8316.47 | 05-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.08 |
May | 6399.98 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.43 |
June | 5497.45 | 30-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.02 | 0.00 |
July | 5366.22 | 24-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 | 0.00 |
August | 4938.04 | 28-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.76 |
September | 5181.75 | 05-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.97 |
October | 4653.56 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6424.69 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.02 |
December | 7365.65 | 08-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4653.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9244.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.02 | 1383.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7660.85 | 26-JAN-09:30 | 12070.02 | 19521.22 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7695.96 | 08-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8441.71 | 29-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13042.20 | 14-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20375.32 | 26-MAY-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32880.87 | 30-JUN-05:02 | 3811.58 | 6507.07 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31846.75 | 05-JUL-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22553.45 | 09-AUG-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18444.92 | 01-SEP-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13912.07 | 20-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8342.10 | 17-NOV-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7190.47 | 01-DEC-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7190.47 | 2541.06 | 4338.05 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32880.87 | 12070.02 | 19521.22 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7908.47 | 27-JAN-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8964.06 | 08-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10019.91 | 31-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13117.31 | 13-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21511.92 | 18-MAY-15:30 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43170.25 | 30-JUN-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23212.54 | 24-JUL-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21351.48 | 09-AUG-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20450.73 | 01-SEP-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12484.38 | 22-OCT-13:42 | 1905.79 | 3253.54 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9332.95 | 17-NOV-16:10 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7724.48 | 28-DEC-15:10 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7724.48 | 0.00 | 3253.54 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43170.25 | 6035.01 | 9760.61 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3021.29 | 21-JAN-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.99 |
February | 3059.18 | 04-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.61 |
March | 3413.00 | 31-MAR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.74 |
April | 4477.42 | 13-APR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 |
May | 6791.29 | 18-MAY-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.54 | 0.00 |
June | 8574.63 | 29-JUN-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 146.64 | 0.00 |
July | 7869.36 | 21-JUL-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 0.00 |
August | 6942.34 | 09-AUG-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 0.00 |
September | 5733.41 | 01-SEP-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 0.00 |
October | 5120.08 | 22-OCT-13:42 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.02 |
November | 3392.04 | 01-NOV-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.13 |
December | 3107.89 | 02-DEC-17:01 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3021.29 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8574.63 | 1306.65 | 2057.62 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 146.64 | 506.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1976.40 | 21-JAN-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.02 |
February | 2289.63 | 28-FEB-10:10 | 2481.66 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.34 |
March | 3117.65 | 31-MAR-09:50 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.76 |
April | 6531.37 | 18-APR-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 |
May | 8860.92 | 18-MAY-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
June | 19277.58 | 18-JUN-09:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.00 |
July | 15392.19 | 23-JUL-09:32 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 |
August | 16415.90 | 20-AUG-09:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.02 |
September | 8551.28 | 01-SEP-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
October | 3912.23 | 22-OCT-13:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.05 |
November | 2338.75 | 16-NOV-09:45 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 |
December | 2035.33 | 02-DEC-17:01 | 339.13 | 578.95 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1976.40 | 254.35 | 434.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19277.58 | 2481.66 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 338.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6380.30 | 27-JAN-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9516.69 | 28-FEB-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.22 |
March | 10151.83 | 31-MAR-14:00 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.79 |
April | 11342.06 | 13-APR-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.08 |
May | 13428.71 | 18-MAY-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 | 0.00 |
June | 14095.02 | 30-JUN-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 87.66 | 0.00 |
July | 19057.03 | 23-JUL-13:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 128.28 | 0.00 |
August | 26947.33 | 13-AUG-14:02 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.55 |
September | 16364.76 | 01-SEP-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | 0.00 |
October | 29763.22 | 22-OCT-13:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.00 |
November | 8566.85 | 17-NOV-13:03 | 7633.40 | 12345.73 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.98 |
December | 4573.54 | 20-DEC-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4573.54 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29763.22 | 7633.40 | 12345.73 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 128.28 | 387.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2409.32 | 27-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3237.74 | 08-FEB-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.65 |
March | 5109.92 | 31-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.23 |
April | 14139.01 | 23-APR-16:22 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 |
May | 12603.22 | 06-MAY-17:05 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.38 |
June | 18139.73 | 17-JUN-17:04 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.55 |
July | 19550.54 | 23-JUL-16:12 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 | 0.00 |
August | 15796.43 | 13-AUG-15:22 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.54 |
September | 11013.16 | 03-SEP-17:22 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.66 |
October | 5854.47 | 19-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 |
November | 2897.33 | 17-NOV-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.68 |
December | 2197.51 | 02-DEC-17:01 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2197.51 | 0.00 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19550.54 | 805.38 | 1302.56 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 | 311.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2382.87 | 21-JAN-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.72 |
February | 2372.74 | 04-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.21 |
March | 2381.72 | 25-MAR-16:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.37 |
April | 3100.62 | 23-APR-15:40 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 219.65 | 0.00 |
May | 3866.50 | 26-MAY-13:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 |
June | 5530.37 | 29-JUN-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 78.36 | 0.00 |
July | 5583.82 | 21-JUL-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 0.00 |
August | 5313.29 | 09-AUG-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 0.00 |
September | 4403.38 | 03-SEP-11:22 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.68 |
October | 4336.00 | 22-OCT-13:42 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.81 |
November | 2858.14 | 01-NOV-14:02 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.27 |
December | 2388.29 | 30-DEC-17:02 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2372.74 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5583.82 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 219.65 | 269.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1569.26 | 21-JAN-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.85 |
February | 1569.13 | 04-FEB-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.59 |
March | 2058.95 | 31-MAR-09:50 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.16 |
April | 3269.53 | 18-APR-09:30 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.47 |
May | 5744.74 | 18-MAY-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 0.00 |
June | 6946.49 | 28-JUN-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 | 0.00 |
July | 7656.33 | 24-JUL-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 | 0.00 |
August | 6902.38 | 25-AUG-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 |
September | 6254.01 | 01-SEP-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 |
October | 3438.60 | 22-OCT-13:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 |
November | 1964.00 | 16-NOV-09:25 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.57 |
December | 1567.53 | 02-DEC-17:01 | 339.13 | 578.95 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1567.53 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7656.33 | 1654.44 | 2605.29 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 | 179.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2879.87 | 27-JAN-13:15 | 5088.93 | 8230.49 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4344.89 |
February | 3558.57 | 28-FEB-15:10 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1964.65 |
March | 3707.50 | 31-MAR-14:30 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1686.78 |
April | 6905.23 | 23-APR-15:39 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 |
May | 10285.28 | 18-MAY-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2952.07 | 0.00 |
June | 14709.88 | 30-JUN-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5863.35 | 0.00 |
July | 12435.85 | 24-JUL-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3316.46 | 0.00 |
August | 12799.43 | 08-AUG-16:10 | 401.76 | 1143.12 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 4966.42 | 0.00 |
September | 12618.78 | 01-SEP-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 105.81 | 0.00 |
October | 23637.62 | 22-OCT-13:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.02 |
November | 4601.22 | 17-NOV-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1567.63 |
December | 3452.17 | 02-DEC-13:50 | 133.92 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2879.87 | 133.92 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23637.62 | 5088.93 | 8230.49 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 5863.35 | 4344.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1792.11 | 27-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2280.95 | 08-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.79 |
March | 2671.13 | 28-MAR-17:10 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 |
April | 5156.38 | 23-APR-15:39 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 |
May | 7237.44 | 25-MAY-18:10 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 0.00 |
June | 9507.73 | 17-JUN-17:08 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.16 |
July | 11407.94 | 29-JUL-17:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 0.00 |
August | 11278.70 | 05-AUG-17:06 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 |
September | 10807.92 | 03-SEP-17:22 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.71 |
October | 4898.50 | 19-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 |
November | 2349.15 | 17-NOV-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.43 |
December | 1642.06 | 02-DEC-17:01 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1642.06 | 0.00 | 361.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11407.94 | 805.38 | 1302.56 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 98.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2346.16 | 21-JAN-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.58 |
February | 2365.06 | 04-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.32 |
March | 2858.53 | 31-MAR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.01 |
April | 3603.79 | 13-APR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.20 |
May | 6139.00 | 26-MAY-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 |
June | 9867.71 | 30-JUN-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 | 0.00 |
July | 7281.87 | 21-JUL-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 | 0.00 |
August | 6478.81 | 09-AUG-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 0.00 |
September | 5416.28 | 01-SEP-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 0.00 |
October | 3792.16 | 22-OCT-13:12 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.65 |
November | 2950.78 | 01-NOV-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 |
December | 2346.03 | 30-DEC-17:02 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2346.03 | 0.00 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9867.71 | 1306.65 | 2057.62 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 | 423.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2152.37 | 19-JAN-13:02 | 8054.28 | 13026.45 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.68 |
February | 2974.09 | 28-FEB-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.13 |
March | 4509.14 | 31-MAR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.03 |
April | 7405.43 | 18-APR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.80 |
May | 11946.63 | 21-MAY-09:12 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.55 |
June | 14226.57 | 25-JUN-08:12 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 |
July | 15861.50 | 23-JUL-09:32 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 |
August | 10763.84 | 20-AUG-09:22 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.07 |
September | 9010.07 | 01-SEP-08:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 |
October | 5541.33 | 19-OCT-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 |
November | 3145.31 | 17-NOV-11:02 | 4027.14 | 6513.23 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.25 |
December | 2138.92 | 05-DEC-13:02 | 8054.28 | 13026.45 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2138.92 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | |
Maximum of Months | 15861.50 | 8054.28 | 13026.45 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7614.82 | 27-JAN-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10021.75 | 28-FEB-13:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.05 |
March | 10799.49 | 31-MAR-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.77 |
April | 11929.92 | 23-APR-14:42 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.37 |
May | 12751.28 | 18-MAY-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 28.51 | 0.00 |
June | 17260.38 | 18-JUN-12:42 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.86 |
July | 17836.16 | 23-JUL-13:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 109.08 | 0.00 |
August | 22920.59 | 13-AUG-13:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.90 |
September | 23742.21 | 04-SEP-12:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.06 |
October | 21681.80 | 22-OCT-13:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.31 |
November | 9897.66 | 17-NOV-13:03 | 7633.40 | 12345.73 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.41 |
December | 4506.32 | 20-DEC-13:13 | 7633.40 | 12345.73 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4506.32 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23742.21 | 7633.40 | 12345.73 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 109.08 | 570.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2436.05 | 27-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3148.86 | 08-FEB-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.25 |
March | 5329.13 | 31-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 |
April | 13873.09 | 23-APR-16:42 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.81 |
May | 13355.00 | 06-MAY-17:05 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.22 |
June | 17328.23 | 17-JUN-17:04 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 |
July | 18941.67 | 01-JUL-18:22 | 0.00 | 434.19 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.83 |
August | 16800.95 | 27-AUG-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.52 |
September | 12033.78 | 03-SEP-17:22 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.59 |
October | 5987.47 | 19-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 |
November | 2921.92 | 17-NOV-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.81 |
December | 1993.12 | 02-DEC-17:01 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1993.12 | 0.00 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18941.67 | 805.38 | 1302.56 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.22 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.162801E+12 | 131260.73 | 02-JAN-08:09 | 0.360567E+12 | 434518.68 | 09-JAN-07:19 |
February | 0.143080E+12 | 110711.17 | 13-FEB-08:09 | 0.236570E+12 | 401880.81 | 14-FEB-07:19 |
March | 0.159352E+12 | 109644.33 | 31-MAR-15:20 | 0.177296E+12 | 360463.11 | 06-MAR-07:10 |
April | 0.144006E+12 | 129578.73 | 13-APR-15:30 | 0.594886E+11 | 249465.35 | 03-APR-06:10 |
May | 0.165738E+12 | 176375.14 | 25-MAY-15:50 | 0.897925E+10 | 170530.27 | 01-MAY-06:10 |
June | 0.184015E+12 | 215067.27 | 29-JUN-15:00 | 0.167534E+10 | 61443.34 | 02-JUN-06:10 |
July | 0.192152E+12 | 215724.10 | 05-JUL-10:39 | 0.446012E+09 | 49413.33 | 10-JUL-06:10 |
August | 0.193697E+12 | 196276.36 | 08-AUG-15:20 | 0.132537E+10 | 68292.30 | 18-AUG-06:10 |
September | 0.153561E+12 | 176996.02 | 01-SEP-15:30 | 0.983580E+10 | 122018.20 | 28-SEP-06:10 |
October | 0.152288E+12 | 137070.15 | 19-OCT-15:20 | 0.508194E+11 | 280420.89 | 30-OCT-06:10 |
November | 0.151986E+12 | 122538.82 | 17-NOV-16:30 | 0.136360E+12 | 332207.00 | 25-NOV-07:10 |
December | 0.159254E+12 | 130755.42 | 26-DEC-08:09 | 0.321929E+12 | 414879.22 | 26-DEC-07:19 |
Annual Sum or Average | 0.196193E+13 | 0.136529E+13 | ||||
Minimum of Months | 0.143080E+12 | 109644.33 | 0.446012E+09 | 49413.33 | ||
Maximum of Months | 0.193697E+12 | 215724.10 | 0.360567E+12 | 434518.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.258256E+11 | 0.613996E+11 | 0.230900E+10 | 0.184307E+11 | 0.183903E+10 | 0.00 | 836498.10 | 0.00 | 0.00 | 0.00 | 0.574805E+10 | 0.00 |
February | 0.428574E+11 | 0.212136E+11 | 0.556056E+11 | 0.209511E+10 | 0.147680E+11 | 0.121004E+10 | 0.00 | 1249010.39 | 0.00 | 0.00 | 0.00 | 0.532934E+10 | 0.00 |
March | 0.509265E+11 | 0.206191E+11 | 0.635880E+11 | 0.240664E+10 | 0.146559E+11 | 0.892287E+09 | 0.00 | 544437.23 | 0.00 | 0.00 | 0.00 | 0.626335E+10 | 0.00 |
April | 0.454877E+11 | 0.170700E+11 | 0.594055E+11 | 0.224272E+10 | 0.125668E+11 | 0.291069E+09 | 0.00 | 0.145774E+10 | 0.00 | 0.00 | 0.00 | 0.548500E+10 | 0.00 |
May | 0.490872E+11 | 0.150432E+11 | 0.624938E+11 | 0.235782E+10 | 0.159013E+11 | 58657693.73 | 0.00 | 0.152036E+11 | 0.00 | 0.00 | 0.00 | 0.559236E+10 | 0.00 |
June | 0.488499E+11 | 0.131515E+11 | 0.612808E+11 | 0.231841E+10 | 0.189547E+11 | 20386985.94 | 0.00 | 0.342022E+11 | 0.00 | 0.00 | 0.00 | 0.523710E+10 | 0.00 |
July | 0.457251E+11 | 0.142505E+11 | 0.606074E+11 | 0.228147E+10 | 0.208040E+11 | 14038838.33 | 0.00 | 0.437611E+11 | 0.00 | 0.00 | 0.00 | 0.470879E+10 | 0.00 |
August | 0.509265E+11 | 0.164754E+11 | 0.635880E+11 | 0.240664E+10 | 0.198628E+11 | 18169395.01 | 0.00 | 0.353736E+11 | 0.00 | 0.00 | 0.00 | 0.504574E+10 | 0.00 |
September | 0.454877E+11 | 0.186914E+11 | 0.593832E+11 | 0.224140E+10 | 0.149310E+11 | 58665376.57 | 0.00 | 0.818787E+10 | 0.00 | 0.00 | 0.00 | 0.458018E+10 | 0.00 |
October | 0.472479E+11 | 0.223035E+11 | 0.614108E+11 | 0.230966E+10 | 0.126231E+11 | 0.241230E+09 | 0.00 | 0.124606E+10 | 0.00 | 0.00 | 0.00 | 0.490597E+10 | 0.00 |
November | 0.466941E+11 | 0.242042E+11 | 0.599069E+11 | 0.224962E+10 | 0.129352E+11 | 0.671959E+09 | 0.00 | 0.230710E+09 | 0.00 | 0.00 | 0.00 | 0.509275E+10 | 0.00 |
December | 0.457251E+11 | 0.265192E+11 | 0.605962E+11 | 0.228081E+10 | 0.171123E+11 | 0.167147E+10 | 0.00 | 912206.14 | 0.00 | 0.00 | 0.00 | 0.534830E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.235367E+12 | 0.729266E+12 | 0.274993E+11 | 0.193546E+12 | 0.698701E+10 | 0.00 | 0.139666E+12 | 0.00 | 0.00 | 0.00 | 0.633369E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.131515E+11 | 0.556056E+11 | 0.209511E+10 | 0.125668E+11 | 14038838.33 | 0.00 | 544437.23 | 0.00 | 0.00 | 0.00 | 0.458018E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.265192E+11 | 0.635880E+11 | 0.240664E+10 | 0.208040E+11 | 0.183903E+10 | 0.00 | 0.437611E+11 | 0.00 | 0.00 | 0.00 | 0.626335E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.360567E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.236570E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.177296E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.594886E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.897925E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167534E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.446012E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.132537E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.983580E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.508194E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.136360E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.321929E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136529E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.446012E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.360567E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 02-JAN-12:20 | 19113.89 | 02-JAN-06:19 | 1673.64 | 09-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 01-FEB-12:20 | 18201.69 | 27-FEB-07:10 | 1576.25 | 14-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 01-MAR-12:09 | 17485.57 | 06-MAR-07:10 | 1482.07 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 03-APR-07:19 | 14156.12 | 21-APR-15:00 | 1283.96 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 01-MAY-11:09 | 24882.29 | 18-MAY-14:00 | 837.50 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 02-JUN-07:10 | 30699.36 | 30-JUN-14:00 | 299.57 | 02-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 32080.24 | 05-JUL-10:39 | 193.10 | 10-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:10 | 27541.55 | 08-AUG-15:20 | 286.26 | 19-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 12-SEP-11:09 | 27671.46 | 01-SEP-15:30 | 596.18 | 28-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 04-OCT-07:10 | 16258.50 | 20-OCT-14:30 | 1328.65 | 30-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 02-NOV-07:10 | 16707.93 | 27-NOV-07:10 | 1424.88 | 25-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 01-DEC-12:20 | 19113.89 | 26-DEC-07:30 | 1606.24 | 26-DEC-07:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 14156.12 | 193.10 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 32080.24 | 1673.64 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 257.05 | 21-JAN-06:30 | 0.00 | 0.00 | 0.00 | 7725.09 | 31-JAN-12:50 | 0.00 |
February | 174.43 | 05-FEB-09:50 | 0.00 | 0.00 | 0.00 | 7751.33 | 21-FEB-12:50 | 0.00 |
March | 111.25 | 06-MAR-06:19 | 0.00 | 0.00 | 0.00 | 7749.90 | 01-MAR-12:00 | 0.00 |
April | 23883.87 | 23-APR-16:30 | 0.00 | 0.00 | 0.00 | 7695.24 | 03-APR-11:00 | 0.00 |
May | 54751.07 | 25-MAY-15:50 | 0.00 | 0.00 | 0.00 | 7312.42 | 01-MAY-11:39 | 0.00 |
June | 87514.39 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 7052.73 | 02-JUN-11:00 | 0.00 |
July | 85456.35 | 05-JUL-10:39 | 0.00 | 0.00 | 0.00 | 6656.11 | 03-JUL-11:00 | 0.00 |
August | 71241.77 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 | 6254.90 | 01-AUG-11:00 | 0.00 |
September | 51621.53 | 01-SEP-15:30 | 0.00 | 0.00 | 0.00 | 6268.87 | 29-SEP-11:50 | 0.00 |
October | 24111.66 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 6693.08 | 31-OCT-11:50 | 0.00 |
November | 12153.95 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 7153.53 | 30-NOV-12:50 | 0.00 |
December | 226.21 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 | 7560.49 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 111.25 | 0.00 | 0.00 | 0.00 | 6254.90 | 0.00 | ||
Maximum of Months | 87514.39 | 0.00 | 0.00 | 0.00 | 7751.33 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 131260.73 | 02-JAN-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 17663.39 | 1513.20 | 0.00 | 0.00 | 0.00 |
February | 110711.17 | 13-FEB-08:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 11876.21 | 1425.04 | 0.00 | 0.00 | 0.00 |
March | 109644.33 | 31-MAR-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 10863.82 | 14.49 | 0.00 | 0.00 | 0.00 |
April | 129578.73 | 13-APR-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 13878.71 | 6.85 | 0.00 | 17095.79 | 0.00 |
May | 176375.14 | 25-MAY-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 23420.71 | 6.91 | 0.00 | 54751.07 | 0.00 |
June | 215067.27 | 29-JUN-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 29741.06 | 6.94 | 0.00 | 87514.39 | 0.00 |
July | 215724.10 | 05-JUL-10:39 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 32080.24 | 6.85 | 0.00 | 85456.35 | 0.00 |
August | 196276.36 | 08-AUG-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 27541.55 | 6.94 | 0.00 | 70975.19 | 0.00 |
September | 176996.02 | 01-SEP-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 27671.46 | 6.94 | 0.00 | 51621.53 | 0.00 |
October | 137070.15 | 19-OCT-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 15565.43 | 6.85 | 0.00 | 23702.40 | 0.00 |
November | 122538.82 | 17-NOV-16:30 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 9327.98 | 27.88 | 0.00 | 0.00 | 0.00 |
December | 130755.42 | 26-DEC-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 17092.25 | 1591.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 109644.33 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 9327.98 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 215724.10 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 32080.24 | 1591.60 | 0.00 | 87514.39 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 434518.68 | 09-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 401880.81 | 14-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 360463.11 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 249465.35 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 170530.27 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 61443.34 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 49413.33 | 10-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 68292.30 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 122018.20 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 280420.89 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 332207.00 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 414879.22 | 26-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 49413.33 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 434518.68 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.41 | 2.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.38 | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Annual Sum or Average | 2.33 | 19.40 | 2.33 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.41 | 2.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 19.24 | 5.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 0.67 | 19.20 | 0.67 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
March | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.16 | 0.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
December | 3.00 | 19.22 | 2.67 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Annual Sum or Average | 10.00 | 19.23 | 9.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 19.24 | 5.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.33 | 17.24 | 6.83 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
February | 3.33 | 18.36 | 2.17 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
March | 1.33 | 18.22 | 0.83 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
November | 2.17 | 17.86 | 1.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
December | 8.00 | 17.56 | 4.67 | 18.01 | 0.00 | 18.01 | 0.00 | 18.01 |
Annual Sum or Average | 29.33 | 17.56 | 15.67 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.33 | 19.40 | 6.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 91.00 | 15.25 | 34.83 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
February | 56.17 | 15.15 | 14.83 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
March | 23.83 | 15.15 | 4.67 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
April | 3.50 | 15.82 | 0.50 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.83 | 15.81 | 0.33 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
November | 29.50 | 14.94 | 8.67 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
December | 72.50 | 14.82 | 24.33 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
Annual Sum or Average | 278.33 | 15.09 | 88.17 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 91.00 | 15.82 | 34.83 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 91.67 | 15.16 | 34.67 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
February | 54.17 | 15.07 | 11.17 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
March | 22.67 | 15.14 | 3.00 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
April | 3.33 | 15.73 | 0.50 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.17 | 2.17 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.12 | 1.33 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.56 | 1.17 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.00 | 15.90 | 0.33 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
November | 29.17 | 14.94 | 8.33 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
December | 75.00 | 14.80 | 24.67 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
Annual Sum or Average | 278.00 | 15.03 | 82.67 | 15.31 | 4.67 | 15.47 | 4.67 | 15.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 91.67 | 15.90 | 34.67 | 16.37 | 2.17 | 28.17 | 2.17 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 79.17 | 15.25 | 26.50 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
February | 43.17 | 15.19 | 8.33 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
March | 17.00 | 15.22 | 2.50 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
April | 2.00 | 16.36 | 0.00 | 16.36 | 0.33 | 17.94 | 0.33 | 19.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.90 | 1.83 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.66 | 1.33 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.68 | 1.00 | 27.68 |
October | 1.33 | 16.15 | 0.33 | 16.79 | 0.67 | 20.00 | 0.67 | 21.78 |
November | 22.50 | 15.02 | 5.83 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
December | 62.50 | 14.85 | 16.83 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
Annual Sum or Average | 227.67 | 15.12 | 60.33 | 15.43 | 5.17 | 15.65 | 5.17 | 15.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.17 | 16.36 | 26.50 | 16.79 | 1.83 | 27.90 | 1.83 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 89.17 | 15.12 | 32.83 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
February | 52.33 | 15.00 | 12.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
March | 21.00 | 15.12 | 3.67 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
April | 3.00 | 15.73 | 0.83 | 15.58 | 0.83 | 17.88 | 0.50 | 18.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.84 | 1.00 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.05 | 0.17 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.18 | 3.00 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.62 | 1.17 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.98 | 0.50 | 27.96 |
October | 1.83 | 15.99 | 0.33 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
November | 29.17 | 14.94 | 8.50 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
December | 72.67 | 14.69 | 23.17 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
Annual Sum or Average | 269.17 | 14.97 | 81.33 | 15.22 | 10.67 | 15.60 | 6.33 | 15.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 | 0.00 | 14.91 |
Maximum of Months | 89.17 | 15.99 | 32.83 | 16.50 | 4.33 | 28.18 | 3.00 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.17 | 16.22 | 26.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
February | 28.67 | 16.16 | 9.83 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
March | 17.67 | 16.15 | 5.50 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
April | 0.83 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 17.06 | 0.17 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
December | 40.50 | 15.67 | 17.33 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
Annual Sum or Average | 146.17 | 16.06 | 58.83 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.17 | 17.06 | 26.00 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.33 | 16.03 | 22.17 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
February | 23.00 | 16.01 | 5.33 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
March | 11.67 | 15.60 | 1.67 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
April | 0.83 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 17.02 | 0.17 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
December | 40.33 | 15.54 | 14.67 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
Annual Sum or Average | 132.50 | 15.85 | 44.00 | 16.28 | 0.50 | 16.31 | 0.50 | 16.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.33 | 17.02 | 22.17 | 17.28 | 0.33 | 27.33 | 0.33 | 27.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 162.33 | 15.61 | 132.50 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
February | 100.17 | 16.32 | 90.67 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
March | 87.67 | 16.95 | 81.67 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
April | 35.83 | 18.09 | 35.33 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
May | 8.83 | 19.46 | 8.83 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3.33 | 20.27 | 3.33 | 20.27 | 0.83 | 21.09 | 0.83 | 21.74 |
October | 25.50 | 19.05 | 25.50 | 19.05 | 1.17 | 19.25 | 1.17 | 19.44 |
November | 54.50 | 17.90 | 53.50 | 17.91 | 0.00 | 17.91 | 0.00 | 17.91 |
December | 132.33 | 15.93 | 113.83 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
Annual Sum or Average | 610.50 | 16.57 | 545.17 | 16.64 | 2.00 | 16.66 | 2.00 | 16.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.33 | 20.27 | 132.50 | 20.27 | 1.17 | 21.09 | 1.17 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.83 | 16.06 | 23.17 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
February | 25.00 | 16.05 | 7.67 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
March | 11.50 | 15.93 | 2.83 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
April | 0.83 | 16.73 | 0.00 | 16.73 | 0.17 | 18.48 | 0.00 | 18.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.68 | 0.17 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.58 | 1.33 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 0.17 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.94 | 0.33 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 17.05 | 0.17 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
December | 38.67 | 15.60 | 14.33 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
Annual Sum or Average | 132.17 | 15.93 | 48.17 | 16.35 | 4.50 | 16.63 | 2.00 | 16.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.83 | 17.05 | 23.17 | 17.31 | 2.17 | 27.94 | 1.33 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.50 | 15.86 | 23.50 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
February | 26.50 | 15.74 | 7.00 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
March | 9.00 | 15.93 | 2.00 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
April | 0.33 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
November | 4.83 | 15.87 | 0.50 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
December | 52.00 | 15.43 | 20.00 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
Annual Sum or Average | 150.33 | 15.70 | 53.00 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.50 | 17.17 | 23.50 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.33 | 15.46 | 17.17 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
February | 22.33 | 15.34 | 2.83 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
March | 7.67 | 15.61 | 0.83 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
April | 0.50 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.17 | 2.67 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.92 | 2.17 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.86 | 2.50 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
November | 5.67 | 15.44 | 0.50 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
December | 50.33 | 15.18 | 17.00 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
Annual Sum or Average | 141.00 | 15.36 | 38.33 | 15.63 | 7.67 | 16.14 | 7.67 | 16.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.33 | 17.17 | 17.17 | 17.17 | 2.67 | 28.17 | 2.67 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.50 | 15.98 | 14.83 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
February | 16.17 | 15.81 | 3.33 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
March | 6.33 | 16.00 | 1.33 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.75 | 0.83 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.90 | 2.00 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.78 | 2.50 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.92 | 2.17 | 27.92 |
October | 0.17 | 17.11 | 0.00 | 17.11 | 1.33 | 26.95 | 1.33 | 27.53 |
November | 3.50 | 16.05 | 0.33 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
December | 38.83 | 15.51 | 11.50 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
Annual Sum or Average | 109.50 | 15.79 | 31.33 | 16.22 | 9.33 | 16.94 | 9.33 | 17.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.50 | 17.11 | 14.83 | 17.11 | 2.50 | 27.92 | 2.50 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.83 | 15.48 | 18.67 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
February | 23.17 | 15.25 | 4.50 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
March | 7.67 | 15.73 | 1.33 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
April | 0.50 | 17.19 | 0.00 | 17.19 | 1.00 | 24.61 | 0.50 | 25.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.81 | 1.33 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.20 | 0.17 | 28.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.17 | 3.00 | 28.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.64 | 1.33 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.14 | 0.67 | 28.11 |
October | 0.17 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
November | 5.67 | 15.46 | 0.17 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
December | 48.83 | 15.15 | 15.67 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
Annual Sum or Average | 139.83 | 15.35 | 40.33 | 15.61 | 11.67 | 16.36 | 7.00 | 16.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | 0.00 | 15.36 |
Maximum of Months | 53.83 | 17.19 | 18.67 | 17.19 | 4.17 | 28.20 | 3.00 | 28.30 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.50 | 217.67 | 21.22 | 217.67 | 21.07 |
February | 454.00 | 22.23 | 66.17 | 22.05 | 66.17 | 21.91 |
March | 513.00 | 22.86 | 31.67 | 22.75 | 31.67 | 22.65 |
April | 423.67 | 23.66 | 0.00 | 23.66 | 0.00 | 23.66 |
May | 101.33 | 23.86 | 192.00 | 24.50 | 0.00 | 24.50 |
June | 6.00 | 23.93 | 370.83 | 24.47 | 0.00 | 24.47 |
July | 0.50 | 26.26 | 493.67 | 24.54 | 0.50 | 24.54 |
August | 0.00 | 0.00 | 480.83 | 24.38 | 0.00 | 24.38 |
September | 22.00 | 23.83 | 225.33 | 24.69 | 0.00 | 24.69 |
October | 268.50 | 23.77 | 33.83 | 23.95 | 0.00 | 23.95 |
November | 469.50 | 23.29 | 5.00 | 23.26 | 4.83 | 23.24 |
December | 497.00 | 21.93 | 121.83 | 21.69 | 121.83 | 21.54 |
Annual Sum or Average | 3257.50 | 22.70 | 2238.83 | 23.15 | 442.67 | 22.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.22 | 0.00 | 21.07 |
Maximum of Months | 513.00 | 26.26 | 493.67 | 24.69 | 217.67 | 24.69 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.60 | 406.83 | 20.48 | 406.83 | 20.43 |
February | 454.00 | 21.05 | 280.17 | 20.85 | 280.17 | 20.76 |
March | 514.00 | 21.70 | 174.33 | 21.45 | 174.33 | 21.30 |
April | 481.17 | 22.68 | 16.67 | 22.62 | 16.67 | 22.56 |
May | 244.17 | 23.35 | 125.33 | 23.74 | 0.00 | 23.74 |
June | 80.50 | 23.30 | 261.67 | 24.02 | 0.00 | 24.02 |
July | 8.83 | 23.21 | 450.17 | 24.27 | 0.17 | 24.27 |
August | 46.83 | 23.16 | 383.67 | 24.08 | 0.00 | 24.08 |
September | 219.67 | 23.25 | 69.50 | 23.53 | 0.00 | 23.53 |
October | 472.00 | 22.63 | 4.67 | 22.61 | 4.67 | 22.59 |
November | 489.00 | 21.67 | 152.67 | 21.42 | 152.67 | 21.27 |
December | 497.00 | 20.77 | 359.17 | 20.61 | 359.17 | 20.54 |
Annual Sum or Average | 4009.17 | 21.83 | 2684.83 | 22.02 | 1394.67 | 21.75 |
Minimum of Months | 8.83 | 20.60 | 4.67 | 20.48 | 0.00 | 20.43 |
Maximum of Months | 514.00 | 23.35 | 450.17 | 24.27 | 406.83 | 24.27 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 491.83 | 20.04 | 491.83 | 20.03 |
February | 454.00 | 20.30 | 412.33 | 20.25 | 412.33 | 20.23 |
March | 514.00 | 20.80 | 342.33 | 20.65 | 342.33 | 20.58 |
April | 482.50 | 21.61 | 144.67 | 21.33 | 144.67 | 21.16 |
May | 330.17 | 22.64 | 107.50 | 22.98 | 9.83 | 22.93 |
June | 175.33 | 22.75 | 200.67 | 23.50 | 0.00 | 23.50 |
July | 82.67 | 22.83 | 331.33 | 23.94 | 0.00 | 23.94 |
August | 187.17 | 22.78 | 227.83 | 23.49 | 0.00 | 23.49 |
September | 402.83 | 22.46 | 26.50 | 22.53 | 3.00 | 22.52 |
October | 499.50 | 21.32 | 120.67 | 21.08 | 120.67 | 20.91 |
November | 489.00 | 20.51 | 327.00 | 20.33 | 327.00 | 20.26 |
December | 497.00 | 20.07 | 482.67 | 20.06 | 482.67 | 20.05 |
Annual Sum or Average | 4616.17 | 21.17 | 3215.33 | 21.20 | 2334.33 | 20.96 |
Minimum of Months | 82.67 | 20.05 | 26.50 | 20.04 | 0.00 | 20.03 |
Maximum of Months | 514.00 | 22.83 | 491.83 | 23.94 | 491.83 | 23.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.61 | 502.00 | 19.61 | 502.00 | 19.61 |
February | 454.00 | 19.76 | 454.00 | 19.76 | 454.00 | 19.76 |
March | 514.00 | 20.17 | 468.00 | 20.14 | 468.00 | 20.12 |
April | 485.00 | 20.59 | 281.17 | 20.40 | 281.17 | 20.31 |
May | 403.83 | 21.71 | 123.33 | 21.92 | 50.17 | 21.77 |
June | 266.50 | 22.10 | 153.17 | 22.77 | 4.50 | 22.78 |
July | 188.17 | 22.46 | 248.33 | 23.35 | 16.17 | 23.40 |
August | 338.00 | 21.92 | 116.17 | 22.39 | 1.00 | 22.39 |
September | 468.33 | 21.43 | 47.00 | 21.38 | 37.17 | 21.29 |
October | 502.00 | 20.42 | 257.50 | 20.21 | 257.50 | 20.11 |
November | 489.00 | 19.84 | 441.83 | 19.78 | 441.83 | 19.76 |
December | 497.00 | 19.63 | 497.00 | 19.63 | 497.00 | 19.63 |
Annual Sum or Average | 5107.83 | 20.60 | 3589.50 | 20.56 | 3010.50 | 20.37 |
Minimum of Months | 188.17 | 19.61 | 47.00 | 19.61 | 1.00 | 19.61 |
Maximum of Months | 514.00 | 22.46 | 502.00 | 23.35 | 502.00 | 23.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.61 | 502.00 | 19.61 | 502.00 | 19.61 |
February | 454.00 | 19.79 | 437.00 | 19.77 | 437.00 | 19.76 |
March | 514.00 | 20.38 | 413.83 | 20.27 | 413.83 | 20.23 |
April | 444.17 | 21.01 | 194.83 | 20.71 | 190.33 | 20.53 |
May | 294.83 | 21.85 | 163.17 | 22.55 | 24.83 | 22.43 |
June | 180.00 | 22.46 | 267.50 | 23.50 | 13.17 | 23.58 |
July | 127.83 | 23.01 | 353.00 | 23.89 | 25.83 | 23.99 |
August | 244.83 | 22.05 | 229.17 | 23.04 | 6.67 | 23.07 |
September | 380.17 | 21.49 | 87.00 | 21.76 | 28.33 | 21.66 |
October | 494.50 | 20.65 | 228.17 | 20.41 | 224.67 | 20.27 |
November | 489.00 | 19.87 | 417.33 | 19.79 | 417.33 | 19.75 |
December | 497.00 | 19.63 | 497.00 | 19.63 | 497.00 | 19.63 |
Annual Sum or Average | 4622.33 | 20.62 | 3790.00 | 20.80 | 2781.00 | 20.57 |
Minimum of Months | 127.83 | 19.61 | 87.00 | 19.61 | 6.67 | 19.61 |
Maximum of Months | 514.00 | 23.01 | 502.00 | 23.89 | 502.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.33 | 19.78 | 444.17 | 19.67 | 444.17 | 19.62 |
February | 435.67 | 20.12 | 342.83 | 19.93 | 341.17 | 19.85 |
March | 477.33 | 20.62 | 349.17 | 20.48 | 337.50 | 20.37 |
April | 413.00 | 20.95 | 231.33 | 20.84 | 201.83 | 20.66 |
May | 321.67 | 21.76 | 164.83 | 22.25 | 45.17 | 22.08 |
June | 241.83 | 21.96 | 208.67 | 22.92 | 8.83 | 22.91 |
July | 180.67 | 22.52 | 288.17 | 23.56 | 25.17 | 23.66 |
August | 257.50 | 21.97 | 218.17 | 22.95 | 6.67 | 22.99 |
September | 343.33 | 21.52 | 146.17 | 22.15 | 34.83 | 22.07 |
October | 440.67 | 20.67 | 252.50 | 20.73 | 203.50 | 20.56 |
November | 469.33 | 20.08 | 354.50 | 19.90 | 354.50 | 19.83 |
December | 497.00 | 19.77 | 460.17 | 19.70 | 460.17 | 19.67 |
Annual Sum or Average | 4576.33 | 20.74 | 3460.67 | 20.90 | 2463.50 | 20.66 |
Minimum of Months | 180.67 | 19.77 | 146.17 | 19.67 | 6.67 | 19.62 |
Maximum of Months | 498.33 | 22.52 | 460.17 | 23.56 | 460.17 | 23.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.62 | 496.50 | 19.61 | 496.50 | 19.61 |
February | 454.00 | 19.87 | 421.00 | 19.81 | 421.00 | 19.79 |
March | 499.83 | 20.34 | 408.33 | 20.24 | 405.67 | 20.19 |
April | 435.67 | 20.71 | 259.83 | 20.61 | 235.17 | 20.47 |
May | 331.33 | 21.72 | 180.00 | 22.29 | 48.67 | 22.15 |
June | 248.67 | 22.01 | 215.17 | 22.96 | 16.33 | 22.97 |
July | 183.00 | 22.65 | 287.17 | 23.64 | 34.50 | 23.77 |
August | 286.33 | 21.89 | 183.17 | 22.75 | 8.33 | 22.80 |
September | 400.50 | 21.41 | 94.83 | 21.68 | 37.17 | 21.60 |
October | 480.00 | 20.51 | 247.00 | 20.34 | 235.33 | 20.20 |
November | 489.00 | 19.89 | 420.50 | 19.80 | 420.50 | 19.76 |
December | 497.00 | 19.63 | 497.00 | 19.63 | 497.00 | 19.63 |
Annual Sum or Average | 4807.33 | 20.60 | 3710.50 | 20.72 | 2856.17 | 20.52 |
Minimum of Months | 183.00 | 19.62 | 94.83 | 19.61 | 8.33 | 19.61 |
Maximum of Months | 502.00 | 22.65 | 497.00 | 23.64 | 497.00 | 23.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.66 | 502.00 | 19.66 | 502.00 | 19.66 |
February | 454.00 | 19.85 | 454.00 | 19.85 | 454.00 | 19.85 |
March | 514.00 | 20.17 | 512.50 | 20.17 | 512.50 | 20.17 |
April | 485.00 | 20.48 | 427.67 | 20.44 | 427.67 | 20.43 |
May | 487.33 | 21.58 | 72.50 | 21.45 | 71.17 | 21.35 |
June | 393.33 | 22.18 | 66.00 | 22.44 | 1.17 | 22.45 |
July | 209.00 | 22.81 | 187.00 | 23.38 | 18.33 | 23.44 |
August | 307.33 | 22.40 | 120.33 | 22.81 | 0.00 | 22.81 |
September | 455.83 | 21.93 | 14.83 | 21.99 | 1.67 | 21.98 |
October | 502.00 | 20.94 | 147.00 | 20.80 | 147.00 | 20.72 |
November | 489.00 | 20.25 | 410.00 | 20.18 | 410.00 | 20.15 |
December | 497.00 | 19.77 | 497.00 | 19.77 | 497.00 | 19.77 |
Annual Sum or Average | 5295.83 | 20.83 | 3410.83 | 20.68 | 3042.50 | 20.52 |
Minimum of Months | 209.00 | 19.66 | 14.83 | 19.66 | 0.00 | 19.66 |
Maximum of Months | 514.00 | 22.81 | 512.50 | 23.38 | 512.50 | 23.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 502.00 | 19.68 | 502.00 | 19.68 |
February | 454.00 | 19.92 | 454.00 | 19.92 | 454.00 | 19.92 |
March | 514.00 | 20.35 | 466.33 | 20.30 | 466.33 | 20.29 |
April | 480.00 | 21.07 | 246.50 | 20.80 | 246.50 | 20.67 |
May | 367.83 | 22.01 | 95.83 | 22.32 | 19.33 | 22.24 |
June | 198.33 | 22.45 | 232.83 | 23.44 | 2.50 | 23.45 |
July | 87.17 | 23.58 | 386.83 | 24.12 | 25.50 | 24.20 |
August | 153.00 | 22.52 | 295.50 | 23.61 | 1.17 | 23.62 |
September | 320.83 | 22.09 | 91.83 | 22.58 | 2.17 | 22.57 |
October | 487.17 | 21.22 | 120.00 | 21.10 | 113.17 | 20.98 |
November | 489.00 | 20.33 | 376.17 | 20.23 | 376.17 | 20.19 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4550.33 | 20.82 | 3764.83 | 21.00 | 2705.83 | 20.77 |
Minimum of Months | 87.17 | 19.68 | 91.83 | 19.68 | 1.17 | 19.68 |
Maximum of Months | 514.00 | 23.58 | 502.00 | 24.12 | 502.00 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.51 | 487.50 | 18.47 | 487.50 | 18.46 |
February | 454.00 | 19.38 | 397.33 | 19.24 | 397.33 | 19.20 |
March | 514.00 | 20.01 | 409.33 | 19.82 | 409.33 | 19.75 |
April | 468.00 | 20.77 | 235.00 | 20.52 | 229.83 | 20.36 |
May | 406.33 | 21.72 | 107.00 | 21.90 | 43.00 | 21.77 |
June | 316.67 | 22.02 | 144.83 | 22.65 | 17.17 | 22.65 |
July | 163.67 | 22.76 | 299.33 | 23.70 | 32.83 | 23.75 |
August | 183.00 | 22.23 | 281.50 | 23.40 | 11.00 | 23.41 |
September | 292.00 | 21.84 | 144.67 | 22.73 | 5.67 | 22.74 |
October | 438.17 | 21.15 | 156.67 | 21.28 | 108.50 | 21.13 |
November | 486.50 | 20.30 | 312.83 | 20.06 | 312.83 | 19.96 |
December | 497.00 | 18.89 | 482.83 | 18.85 | 482.83 | 18.84 |
Annual Sum or Average | 4721.33 | 20.46 | 3458.83 | 20.54 | 2537.83 | 20.25 |
Minimum of Months | 163.67 | 18.51 | 107.00 | 18.47 | 5.67 | 18.46 |
Maximum of Months | 514.00 | 22.76 | 487.50 | 23.70 | 487.50 | 23.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 501.00 | 19.68 | 501.00 | 19.68 |
February | 454.00 | 19.96 | 441.17 | 19.94 | 441.17 | 19.93 |
March | 514.00 | 20.37 | 461.00 | 20.30 | 461.00 | 20.27 |
April | 467.83 | 20.82 | 285.50 | 20.64 | 282.17 | 20.54 |
May | 380.17 | 21.90 | 108.50 | 22.19 | 31.00 | 22.09 |
June | 271.50 | 22.17 | 166.00 | 22.93 | 3.17 | 22.93 |
July | 113.17 | 23.33 | 342.83 | 24.07 | 27.50 | 24.16 |
August | 169.33 | 22.43 | 273.50 | 23.51 | 2.50 | 23.53 |
September | 353.67 | 22.09 | 80.00 | 22.51 | 2.00 | 22.52 |
October | 481.00 | 21.17 | 131.33 | 21.04 | 123.67 | 20.92 |
November | 489.00 | 20.33 | 387.33 | 20.24 | 387.33 | 20.20 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4692.67 | 20.82 | 3675.17 | 20.94 | 2759.50 | 20.72 |
Minimum of Months | 113.17 | 19.68 | 80.00 | 19.68 | 2.00 | 19.68 |
Maximum of Months | 514.00 | 23.33 | 501.00 | 24.07 | 501.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 502.00 | 19.70 | 502.00 | 19.70 |
February | 454.00 | 19.93 | 449.83 | 19.93 | 449.83 | 19.92 |
March | 514.00 | 20.35 | 434.50 | 20.29 | 434.50 | 20.27 |
April | 485.00 | 20.98 | 203.67 | 20.76 | 203.67 | 20.64 |
May | 353.67 | 22.18 | 117.50 | 22.58 | 17.83 | 22.51 |
June | 184.67 | 22.65 | 224.67 | 23.42 | 3.00 | 23.43 |
July | 88.83 | 23.22 | 362.50 | 23.95 | 19.00 | 24.01 |
August | 227.50 | 22.47 | 209.17 | 23.18 | 0.00 | 23.18 |
September | 428.67 | 22.01 | 30.17 | 22.09 | 6.17 | 22.06 |
October | 502.00 | 20.90 | 153.83 | 20.70 | 153.83 | 20.57 |
November | 489.00 | 20.12 | 395.83 | 20.03 | 395.83 | 19.99 |
December | 497.00 | 19.74 | 497.00 | 19.74 | 497.00 | 19.74 |
Annual Sum or Average | 4726.33 | 20.81 | 3580.67 | 20.89 | 2682.67 | 20.67 |
Minimum of Months | 88.83 | 19.70 | 30.17 | 19.70 | 0.00 | 19.70 |
Maximum of Months | 514.00 | 23.22 | 502.00 | 23.95 | 502.00 | 24.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.49 | 427.00 | 19.49 | 427.00 | 19.49 |
February | 385.00 | 19.82 | 366.83 | 19.78 | 366.83 | 19.77 |
March | 431.83 | 20.54 | 321.67 | 20.39 | 321.67 | 20.33 |
April | 370.33 | 21.24 | 138.67 | 21.03 | 125.17 | 20.83 |
May | 240.00 | 22.14 | 134.83 | 22.96 | 6.17 | 22.92 |
June | 140.67 | 22.85 | 235.00 | 23.76 | 14.00 | 23.86 |
July | 91.67 | 23.55 | 314.17 | 24.13 | 26.83 | 24.25 |
August | 179.67 | 22.50 | 213.83 | 23.41 | 10.33 | 23.49 |
September | 299.17 | 21.83 | 69.50 | 22.24 | 6.67 | 22.21 |
October | 409.67 | 20.96 | 139.00 | 20.82 | 129.83 | 20.67 |
November | 417.00 | 20.05 | 324.33 | 19.91 | 324.33 | 19.85 |
December | 422.00 | 19.53 | 421.33 | 19.53 | 421.33 | 19.53 |
Annual Sum or Average | 3814.00 | 20.75 | 3106.17 | 20.95 | 2180.17 | 20.70 |
Minimum of Months | 91.67 | 19.49 | 69.50 | 19.49 | 6.17 | 19.49 |
Maximum of Months | 431.83 | 23.55 | 427.00 | 24.13 | 427.00 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.83 | 19.96 | 425.33 | 19.81 | 425.33 | 19.75 |
February | 428.17 | 20.51 | 317.33 | 20.27 | 315.17 | 20.17 |
March | 457.50 | 20.89 | 301.17 | 20.76 | 284.67 | 20.63 |
April | 393.17 | 21.41 | 167.33 | 21.32 | 135.50 | 21.13 |
May | 268.00 | 22.24 | 164.17 | 22.94 | 12.17 | 22.87 |
June | 175.00 | 22.49 | 261.17 | 23.50 | 5.33 | 23.53 |
July | 113.00 | 23.40 | 365.17 | 24.08 | 29.50 | 24.19 |
August | 172.33 | 22.69 | 292.17 | 23.65 | 10.67 | 23.72 |
September | 297.67 | 22.16 | 155.50 | 22.94 | 12.17 | 22.98 |
October | 429.33 | 21.22 | 172.33 | 21.38 | 115.00 | 21.22 |
November | 458.83 | 20.48 | 296.67 | 20.27 | 292.00 | 20.16 |
December | 497.00 | 20.05 | 448.67 | 19.93 | 448.67 | 19.89 |
Annual Sum or Average | 4180.83 | 21.07 | 3367.00 | 21.34 | 2086.17 | 21.07 |
Minimum of Months | 113.00 | 19.96 | 155.50 | 19.81 | 5.33 | 19.75 |
Maximum of Months | 497.00 | 23.40 | 448.67 | 24.08 | 448.67 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.73 | 491.50 | 19.71 | 491.50 | 19.71 |
February | 454.00 | 20.07 | 407.00 | 20.00 | 407.00 | 19.97 |
March | 496.83 | 20.53 | 373.33 | 20.42 | 368.50 | 20.36 |
April | 432.83 | 21.05 | 197.00 | 20.95 | 172.83 | 20.80 |
May | 311.33 | 22.05 | 162.33 | 22.73 | 19.17 | 22.68 |
June | 205.17 | 22.30 | 232.83 | 23.29 | 9.00 | 23.33 |
July | 135.00 | 23.21 | 339.83 | 23.97 | 32.67 | 24.10 |
August | 236.00 | 22.28 | 232.83 | 23.20 | 8.17 | 23.25 |
September | 379.17 | 21.80 | 82.00 | 22.21 | 8.00 | 22.21 |
October | 473.50 | 20.90 | 159.00 | 20.78 | 144.17 | 20.65 |
November | 489.00 | 20.19 | 372.17 | 20.06 | 372.17 | 20.01 |
December | 497.00 | 19.75 | 495.67 | 19.75 | 495.67 | 19.75 |
Annual Sum or Average | 4611.83 | 20.82 | 3545.50 | 21.00 | 2528.83 | 20.77 |
Minimum of Months | 135.00 | 19.73 | 82.00 | 19.71 | 8.00 | 19.71 |
Maximum of Months | 502.00 | 23.21 | 495.67 | 23.97 | 495.67 | 24.10 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.49598 | 10.64381 | -0.5262 | 12.27795 |
February | 454.00000 | 22.22802 | 12.20116 | -0.3297 | 8.13582 |
March | 514.00000 | 22.86483 | 15.70964 | -0.1423 | 6.49923 |
April | 485.00000 | 23.78904 | 18.00376 | 0.11773 | 5.72651 |
May | 508.00000 | 24.38957 | 31.28404 | -0.4706 | 10.72759 |
June | 496.00000 | 24.37756 | 43.55823 | -0.3459 | 8.08784 |
July | 497.00000 | 24.53126 | 49.20898 | -0.2329 | 6.91879 |
August | 514.00000 | 24.35283 | 48.92402 | -0.2935 | 7.30733 |
September | 485.00000 | 24.38247 | 36.66352 | -0.4150 | 9.29167 |
October | 502.00000 | 24.04711 | 28.60768 | 0.26336 | 6.79189 |
November | 489.00000 | 23.32072 | 19.27120 | -0.0099 | 5.93203 |
December | 497.00000 | 21.93104 | 12.01030 | -0.4033 | 9.50517 |
Annual Sum or Average | 5943.00000 | 23.48376 | 27.31376 | -0.2325 | 8.10563 |
Minimum of Months | 454.00000 | 21.49598 | 10.64381 | -0.5262 | 5.72651 |
Maximum of Months | 514.00000 | 24.53126 | 49.20898 | 0.26336 | 12.27795 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.60383 | 11.34435 | -0.7467 | 18.59982 |
February | 454.00000 | 21.04945 | 13.07530 | -0.6114 | 14.26031 |
March | 514.00000 | 21.69692 | 17.11420 | -0.4120 | 9.96286 |
April | 485.00000 | 22.69260 | 20.08514 | -0.1342 | 6.56441 |
May | 508.00000 | 23.83300 | 32.50755 | -0.6627 | 15.99148 |
June | 496.00000 | 24.00244 | 44.98260 | -0.4842 | 10.71925 |
July | 497.00000 | 24.24755 | 50.49768 | -0.3493 | 7.98613 |
August | 514.00000 | 24.04465 | 50.35413 | -0.4295 | 9.44402 |
September | 485.00000 | 23.72982 | 38.92123 | -0.6622 | 15.18735 |
October | 502.00000 | 22.71410 | 31.80715 | -0.0553 | 6.20670 |
November | 489.00000 | 21.66859 | 21.47344 | -0.3983 | 9.92524 |
December | 497.00000 | 20.76912 | 12.79657 | -0.6897 | 16.69580 |
Annual Sum or Average | 5943.00000 | 22.59965 | 28.88743 | -0.4689 | 11.78068 |
Minimum of Months | 454.00000 | 20.60383 | 11.34435 | -0.7467 | 6.20670 |
Maximum of Months | 514.00000 | 24.24755 | 50.49768 | -0.0553 | 18.59982 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05085 | 11.75943 | -0.9307 | 25.50459 |
February | 454.00000 | 20.30245 | 13.46016 | -0.8308 | 21.58461 |
March | 514.00000 | 20.79711 | 17.63289 | -0.6520 | 15.66840 |
April | 485.00000 | 21.62648 | 20.40729 | -0.3882 | 10.13039 |
May | 508.00000 | 23.18939 | 32.64166 | -0.8644 | 23.94451 |
June | 496.00000 | 23.58595 | 45.26766 | -0.6075 | 14.66615 |
July | 497.00000 | 23.88158 | 50.20141 | -0.4617 | 10.55175 |
August | 514.00000 | 23.52952 | 50.94642 | -0.5977 | 13.88995 |
September | 485.00000 | 22.70887 | 40.76233 | -0.9955 | 27.87775 |
October | 502.00000 | 21.33391 | 33.22218 | -0.3921 | 9.91957 |
November | 489.00000 | 20.50860 | 21.96248 | -0.7030 | 17.81216 |
December | 497.00000 | 20.07458 | 13.37551 | -0.9067 | 24.62128 |
Annual Sum or Average | 5943.00000 | 21.81268 | 29.44318 | -0.6931 | 17.97722 |
Minimum of Months | 454.00000 | 20.05085 | 11.75943 | -0.9955 | 9.91957 |
Maximum of Months | 514.00000 | 23.88158 | 50.94642 | -0.3882 | 27.87775 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.60609 | 11.38563 | -1.1712 | 35.52756 |
February | 454.00000 | 19.76391 | 13.29349 | -1.0624 | 31.03635 |
March | 514.00000 | 20.17484 | 17.57513 | -0.8813 | 23.53344 |
April | 485.00000 | 20.58824 | 20.77561 | -0.6463 | 16.05894 |
May | 508.00000 | 22.17989 | 33.84241 | -1.1316 | 35.76994 |
June | 496.00000 | 22.86628 | 46.95053 | -0.7597 | 20.63563 |
July | 497.00000 | 23.29336 | 52.51187 | -0.5682 | 14.32867 |
August | 514.00000 | 22.49852 | 54.00647 | -0.8587 | 23.35625 |
September | 485.00000 | 21.50914 | 43.15272 | -1.3516 | 44.12644 |
October | 502.00000 | 20.42120 | 33.26074 | -0.6378 | 15.73969 |
November | 489.00000 | 19.83862 | 22.01823 | -0.9340 | 26.41569 |
December | 497.00000 | 19.63049 | 13.05471 | -1.1416 | 34.25554 |
Annual Sum or Average | 5943.00000 | 21.04344 | 30.30100 | -0.9275 | 26.68482 |
Minimum of Months | 454.00000 | 19.60609 | 11.38563 | -1.3516 | 14.32867 |
Maximum of Months | 514.00000 | 23.29336 | 54.00647 | -0.5682 | 44.12644 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.61147 | 11.60624 | -1.1459 | 34.58973 |
February | 454.00000 | 19.79093 | 13.49686 | -1.0151 | 29.30948 |
March | 514.00000 | 20.37838 | 17.60343 | -0.7857 | 20.56267 |
April | 485.00000 | 21.25900 | 20.25708 | -0.4385 | 13.27377 |
May | 508.00000 | 22.85118 | 32.95294 | -0.8585 | 26.18338 |
June | 496.00000 | 23.41800 | 45.59955 | -0.5078 | 14.90199 |
July | 497.00000 | 23.73607 | 51.06951 | -0.3404 | 10.90092 |
August | 514.00000 | 23.02394 | 52.53934 | -0.6353 | 17.92715 |
September | 485.00000 | 22.05298 | 42.14336 | -1.1345 | 36.01114 |
October | 502.00000 | 20.69975 | 32.90043 | -0.5563 | 14.42462 |
November | 489.00000 | 19.87425 | 22.21356 | -0.9074 | 25.46145 |
December | 497.00000 | 19.63270 | 13.26492 | -1.1242 | 33.62904 |
Annual Sum or Average | 5943.00000 | 21.37522 | 29.77985 | -0.7855 | 23.03100 |
Minimum of Months | 454.00000 | 19.61147 | 11.60624 | -1.1459 | 10.90092 |
Maximum of Months | 514.00000 | 23.73607 | 52.53934 | -0.3404 | 36.01114 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81477 | 11.26608 | -1.0201 | 30.74573 |
February | 454.00000 | 20.27700 | 12.88160 | -0.8260 | 24.51107 |
March | 514.00000 | 20.89322 | 16.88481 | -0.6331 | 18.46363 |
April | 485.00000 | 21.42803 | 19.80304 | -0.3960 | 13.69038 |
May | 508.00000 | 22.63668 | 33.06860 | -0.9391 | 29.41093 |
June | 496.00000 | 22.98416 | 46.58235 | -0.6862 | 20.03616 |
July | 497.00000 | 23.44055 | 51.93163 | -0.4682 | 13.99628 |
August | 514.00000 | 22.94905 | 52.55170 | -0.6514 | 19.25556 |
September | 485.00000 | 22.31965 | 41.27105 | -1.0216 | 33.58120 |
October | 502.00000 | 21.13092 | 31.79827 | -0.4272 | 14.29867 |
November | 489.00000 | 20.24035 | 21.58301 | -0.7804 | 22.49249 |
December | 497.00000 | 19.77038 | 12.97969 | -1.0316 | 30.37035 |
Annual Sum or Average | 5943.00000 | 21.50193 | 29.52996 | -0.7393 | 22.54458 |
Minimum of Months | 454.00000 | 19.77038 | 11.26608 | -1.0316 | 13.69038 |
Maximum of Months | 514.00000 | 23.44055 | 52.55170 | -0.3960 | 33.58120 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.62108 | 11.50838 | -1.1465 | 34.65296 |
February | 454.00000 | 19.87077 | 13.33454 | -1.0021 | 29.06828 |
March | 514.00000 | 20.45210 | 17.45347 | -0.7800 | 21.43505 |
April | 485.00000 | 21.05758 | 20.43737 | -0.4993 | 15.15094 |
May | 508.00000 | 22.56448 | 33.33649 | -0.9424 | 30.49964 |
June | 496.00000 | 22.97976 | 46.73412 | -0.6590 | 19.96888 |
July | 497.00000 | 23.45938 | 52.03381 | -0.4377 | 14.12667 |
August | 514.00000 | 22.75919 | 53.30403 | -0.7134 | 21.16935 |
September | 485.00000 | 21.87135 | 42.47004 | -1.1936 | 39.04166 |
October | 502.00000 | 20.66339 | 32.95178 | -0.5632 | 15.12629 |
November | 489.00000 | 19.88593 | 22.12115 | -0.9085 | 25.55514 |
December | 497.00000 | 19.63413 | 13.18464 | -1.1274 | 33.75725 |
Annual Sum or Average | 5943.00000 | 21.24814 | 30.05186 | -0.8295 | 24.91358 |
Minimum of Months | 454.00000 | 19.62108 | 11.50838 | -1.1936 | 14.12667 |
Maximum of Months | 514.00000 | 23.45938 | 53.30403 | -0.4377 | 39.04166 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.66043 | 11.20394 | -1.1551 | 34.60226 |
February | 454.00000 | 19.84728 | 13.28295 | -1.0576 | 30.33191 |
March | 514.00000 | 20.17031 | 17.52810 | -0.9343 | 25.07751 |
April | 485.00000 | 20.48006 | 21.10911 | -0.7403 | 17.68321 |
May | 508.00000 | 21.66048 | 35.99040 | -1.3833 | 45.79384 |
June | 496.00000 | 22.50678 | 48.92629 | -0.9538 | 26.36929 |
July | 497.00000 | 23.32495 | 53.79251 | -0.6144 | 14.21046 |
August | 514.00000 | 22.90304 | 53.65266 | -0.7584 | 18.67507 |
September | 485.00000 | 22.04284 | 42.16970 | -1.1648 | 34.96513 |
October | 502.00000 | 20.94002 | 32.36792 | -0.4710 | 10.37793 |
November | 489.00000 | 20.24858 | 21.72842 | -0.7923 | 20.06129 |
December | 497.00000 | 19.76746 | 12.92372 | -1.0817 | 31.43823 |
Annual Sum or Average | 5943.00000 | 21.14097 | 30.54255 | -0.9249 | 25.78055 |
Minimum of Months | 454.00000 | 19.66043 | 11.20394 | -1.3833 | 10.37793 |
Maximum of Months | 514.00000 | 23.32495 | 53.79251 | -0.4710 | 45.79384 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67678 | 11.50591 | -1.1282 | 33.53069 |
February | 454.00000 | 19.91815 | 13.55365 | -1.0033 | 28.11204 |
March | 514.00000 | 20.34734 | 17.68311 | -0.8407 | 21.61831 |
April | 485.00000 | 21.09542 | 20.72705 | -0.5259 | 13.39553 |
May | 508.00000 | 22.61463 | 34.48404 | -1.0132 | 30.49185 |
June | 496.00000 | 23.44739 | 46.57040 | -0.5798 | 15.36652 |
July | 497.00000 | 23.96969 | 51.60318 | -0.3178 | 8.93364 |
August | 514.00000 | 23.57257 | 51.65737 | -0.4824 | 12.23925 |
September | 485.00000 | 22.77663 | 40.72519 | -0.8873 | 25.19374 |
October | 502.00000 | 21.32413 | 31.92554 | -0.3654 | 9.52018 |
November | 489.00000 | 20.32730 | 22.00747 | -0.7561 | 18.87170 |
December | 497.00000 | 19.77835 | 13.22233 | -1.0630 | 30.69463 |
Annual Sum or Average | 5943.00000 | 21.58489 | 29.78261 | -0.7452 | 20.61722 |
Minimum of Months | 454.00000 | 19.67678 | 11.50591 | -1.1282 | 8.93364 |
Maximum of Months | 514.00000 | 23.96969 | 51.65737 | -0.3178 | 33.53069 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.50815 | 10.71811 | -1.2594 | 39.52006 |
February | 454.00000 | 19.37629 | 12.40487 | -0.9976 | 28.86613 |
March | 514.00000 | 20.00528 | 16.59446 | -0.8312 | 22.79252 |
April | 485.00000 | 20.90079 | 19.87691 | -0.5385 | 14.41225 |
May | 508.00000 | 22.20281 | 34.52833 | -1.1430 | 36.02893 |
June | 496.00000 | 22.74073 | 48.76175 | -0.8351 | 23.61393 |
July | 497.00000 | 23.59416 | 53.44250 | -0.4642 | 12.08161 |
August | 514.00000 | 23.37853 | 52.75630 | -0.5199 | 13.99696 |
September | 485.00000 | 22.84213 | 40.06759 | -0.8174 | 24.68725 |
October | 502.00000 | 21.58746 | 30.37648 | -0.2573 | 10.15868 |
November | 489.00000 | 20.32095 | 20.78795 | -0.6920 | 18.06363 |
December | 497.00000 | 18.88849 | 12.45284 | -1.1635 | 35.37562 |
Annual Sum or Average | 5943.00000 | 21.20961 | 29.55110 | -0.7923 | 23.27975 |
Minimum of Months | 454.00000 | 18.50815 | 10.71811 | -1.2594 | 10.15868 |
Maximum of Months | 514.00000 | 23.59416 | 53.44250 | -0.2573 | 39.52006 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68240 | 11.41889 | -1.1303 | 33.64214 |
February | 454.00000 | 19.96280 | 13.43503 | -0.9965 | 27.95385 |
March | 514.00000 | 20.37226 | 17.57476 | -0.8418 | 22.15523 |
April | 485.00000 | 20.94830 | 20.85588 | -0.5756 | 14.80626 |
May | 508.00000 | 22.45496 | 34.62369 | -1.0595 | 32.93338 |
June | 496.00000 | 23.00480 | 47.68597 | -0.7375 | 20.50465 |
July | 497.00000 | 23.87160 | 52.08114 | -0.3626 | 10.09778 |
August | 514.00000 | 23.46843 | 51.95916 | -0.5141 | 13.41984 |
September | 485.00000 | 22.63504 | 40.98805 | -0.9336 | 26.90963 |
October | 502.00000 | 21.28665 | 31.92255 | -0.3706 | 9.62995 |
November | 489.00000 | 20.32949 | 21.94107 | -0.7596 | 19.02216 |
December | 497.00000 | 19.77760 | 13.15621 | -1.0672 | 30.87123 |
Annual Sum or Average | 5943.00000 | 21.49653 | 29.94866 | -0.7775 | 21.78956 |
Minimum of Months | 454.00000 | 19.68240 | 11.41889 | -1.1303 | 9.62995 |
Maximum of Months | 514.00000 | 23.87160 | 52.08114 | -0.3626 | 33.64214 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70107 | 11.01406 | -1.0972 | 32.28728 |
February | 454.00000 | 19.93122 | 13.02852 | -0.9737 | 27.09267 |
March | 514.00000 | 20.35327 | 17.28975 | -0.7918 | 20.02229 |
April | 485.00000 | 20.97970 | 20.65171 | -0.5244 | 12.40351 |
May | 508.00000 | 22.77180 | 33.47505 | -0.9451 | 27.78032 |
June | 496.00000 | 23.46073 | 46.21667 | -0.5887 | 14.41718 |
July | 497.00000 | 23.84085 | 52.11352 | -0.4083 | 9.73074 |
August | 514.00000 | 23.22190 | 52.71388 | -0.6385 | 15.41511 |
September | 485.00000 | 22.21614 | 41.88291 | -1.1046 | 32.71794 |
October | 502.00000 | 20.90105 | 32.53184 | -0.4781 | 11.12426 |
November | 489.00000 | 20.12265 | 21.76287 | -0.8087 | 21.24288 |
December | 497.00000 | 19.74296 | 12.68782 | -1.0581 | 30.69539 |
Annual Sum or Average | 5943.00000 | 21.45118 | 29.75993 | -0.7832 | 21.19035 |
Minimum of Months | 454.00000 | 19.70107 | 11.01406 | -1.1046 | 9.73074 |
Maximum of Months | 514.00000 | 23.84085 | 52.71388 | -0.4083 | 32.71794 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.48784 | 10.94967 | -1.1263 | 33.82318 |
February | 385.00000 | 19.81698 | 12.94868 | -0.9676 | 27.06049 |
March | 433.00000 | 20.55188 | 16.86275 | -0.7124 | 18.07991 |
April | 410.00000 | 21.53572 | 19.87381 | -0.3529 | 11.16349 |
May | 430.00000 | 23.11193 | 32.64294 | -0.7738 | 22.66551 |
June | 418.00000 | 23.63094 | 45.61561 | -0.4504 | 12.99988 |
July | 422.00000 | 23.92936 | 51.56964 | -0.2903 | 9.48995 |
August | 433.00000 | 23.31913 | 52.17839 | -0.5410 | 14.65173 |
September | 410.00000 | 22.44889 | 41.30075 | -0.9831 | 29.42827 |
October | 427.00000 | 21.11193 | 31.81722 | -0.4203 | 11.04651 |
November | 417.00000 | 20.04536 | 21.42777 | -0.8168 | 21.76929 |
December | 422.00000 | 19.52947 | 12.60212 | -1.0932 | 32.40120 |
Annual Sum or Average | 5034.00000 | 21.55540 | 29.26952 | -0.7089 | 20.32758 |
Minimum of Months | 385.00000 | 19.48784 | 10.94967 | -1.1263 | 9.48995 |
Maximum of Months | 433.00000 | 23.92936 | 52.17839 | -0.2903 | 33.82318 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04742 | 10.81252 | -0.9169 | 26.97984 |
February | 454.00000 | 20.70959 | 12.41518 | -0.6865 | 19.85579 |
March | 514.00000 | 21.29373 | 16.39489 | -0.5014 | 15.06639 |
April | 485.00000 | 21.93515 | 19.47595 | -0.2527 | 10.75484 |
May | 508.00000 | 23.17574 | 32.73509 | -0.7662 | 22.23589 |
June | 496.00000 | 23.50021 | 45.94874 | -0.5357 | 14.39222 |
July | 497.00000 | 23.91614 | 51.65928 | -0.3269 | 9.75521 |
August | 514.00000 | 23.56250 | 51.50450 | -0.4597 | 12.79084 |
September | 485.00000 | 22.96874 | 40.01463 | -0.7902 | 24.13477 |
October | 502.00000 | 21.68868 | 30.94622 | -0.2541 | 10.73036 |
November | 489.00000 | 20.69388 | 21.12716 | -0.6240 | 17.43461 |
December | 497.00000 | 20.05083 | 12.51409 | -0.9141 | 25.87607 |
Annual Sum or Average | 5943.00000 | 21.97349 | 28.94126 | -0.5849 | 17.47497 |
Minimum of Months | 454.00000 | 20.04742 | 10.81252 | -0.9169 | 9.75521 |
Maximum of Months | 514.00000 | 23.91614 | 51.65928 | -0.2527 | 26.97984 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.72728 | 10.92248 | -1.0713 | 31.38960 |
February | 454.00000 | 20.07222 | 12.85329 | -0.9086 | 25.03219 |
March | 514.00000 | 20.65833 | 16.91829 | -0.6871 | 18.12416 |
April | 485.00000 | 21.37956 | 20.16469 | -0.3915 | 11.95110 |
May | 508.00000 | 22.87784 | 33.29142 | -0.8284 | 25.43495 |
June | 496.00000 | 23.27333 | 46.61463 | -0.5657 | 16.09098 |
July | 497.00000 | 23.75438 | 52.24026 | -0.3427 | 10.94427 |
August | 514.00000 | 23.14782 | 52.84453 | -0.5800 | 16.09572 |
September | 485.00000 | 22.29620 | 41.63004 | -1.0214 | 31.17572 |
October | 502.00000 | 21.08022 | 32.12214 | -0.4177 | 11.00530 |
November | 489.00000 | 20.19090 | 21.66885 | -0.7819 | 20.44610 |
December | 497.00000 | 19.75166 | 12.62551 | -1.0443 | 30.20345 |
Annual Sum or Average | 5943.00000 | 21.53098 | 29.63816 | -0.7184 | 20.61299 |
Minimum of Months | 454.00000 | 19.72728 | 10.92248 | -1.0713 | 10.94427 |
Maximum of Months | 514.00000 | 23.75438 | 52.84453 | -0.3427 | 31.38960 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.249080E+12 | 0.00 | 668.85 | 385883.27 | 19-JAN-06:01 | 0.00 | 40.67 | 57.85 | 1.32 | 0.00 | 0.15 | 0.62 | 19-JAN-06:01 |
February | 0.158278E+12 | 0.00 | 564.59 | 368055.34 | 28-FEB-06:01 | 0.00 | 37.90 | 56.05 | 0.84 | 0.00 | 0.11 | 0.60 | 28-FEB-06:01 |
March | 0.114601E+12 | 0.00 | 533.86 | 397662.92 | 29-MAR-05:01 | 0.00 | 34.80 | 52.37 | 0.49 | 0.00 | 0.07 | 0.64 | 29-MAR-05:01 |
April | 0.361712E+11 | 0.00 | 391.62 | 402794.53 | 11-APR-05:01 | 0.00 | 28.63 | 44.57 | 0.14 | 0.00 | 0.02 | 0.65 | 11-APR-05:01 |
May | 0.527099E+10 | 0.00 | 191.27 | 399130.74 | 01-MAY-05:01 | 0.00 | 31.56 | 38.59 | 0.02 | 0.00 | 0.00 | 0.65 | 01-MAY-05:01 |
June | 0.956770E+09 | 0.00 | 119.28 | 71514.32 | 12-JUN-06:03 | 0.00 | 32.44 | 37.18 | 0.00 | 0.00 | 0.00 | 0.12 | 12-JUN-06:03 |
July | 0.253451E+09 | 0.00 | 146.33 | 63625.81 | 10-JUL-06:03 | 0.00 | 29.20 | 35.28 | 0.00 | 0.00 | 0.00 | 0.10 | 10-JUL-06:03 |
August | 0.759857E+09 | 0.00 | 134.46 | 101836.72 | 19-AUG-06:03 | 0.00 | 26.44 | 32.52 | 0.00 | 0.00 | 0.00 | 0.16 | 19-AUG-06:03 |
September | 0.569885E+10 | 0.00 | 199.33 | 192885.72 | 23-SEP-06:03 | 0.00 | 27.79 | 36.22 | 0.02 | 0.00 | 0.00 | 0.31 | 23-SEP-06:03 |
October | 0.303287E+11 | 0.00 | 360.23 | 426111.05 | 16-OCT-05:11 | 0.00 | 27.61 | 42.18 | 0.10 | 0.00 | 0.02 | 0.69 | 16-OCT-05:11 |
November | 0.869045E+11 | 0.00 | 510.01 | 382599.73 | 15-NOV-06:01 | 0.00 | 33.42 | 51.96 | 0.36 | 0.00 | 0.05 | 0.62 | 15-NOV-06:01 |
December | 0.219210E+12 | 0.00 | 656.54 | 386839.27 | 28-DEC-06:01 | 0.00 | 39.76 | 57.28 | 1.10 | 0.00 | 0.13 | 0.63 | 28-DEC-06:01 |
Annual Sum or Average | 0.907514E+12 | 0.00 | 4476.39 | 0.00 | 32.50 | 45.11 | 0.37 | 0.00 | 0.05 | ||||
Minimum of Months | 0.253451E+09 | 0.00 | 119.28 | 63625.81 | 0.00 | 26.44 | 32.52 | 0.00 | 0.00 | 0.00 | 0.10 | ||
Maximum of Months | 0.249080E+12 | 0.00 | 668.85 | 426111.05 | 0.00 | 40.67 | 57.85 | 1.32 | 0.00 | 0.15 | 0.69 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 195708.88 | 55537.62 | 0.04 | 195708.88 | 0.00 | 0.00 | 0.07 | 30-JAN-07:03 | 0.00 | 01-JAN-00:01 | 2308.50 | 30-JAN-07:03 | 2308.50 | 30-JAN-07:03 | 0.00 | 01-JAN-10:01 | 652.75 | 30-JAN-07:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.157656E+10 | 0.414065E+09 | 49.71 | 0.157105E+10 | 5505417.22 | 0.00 | 0.77 | 23-APR-17:32 | 0.00 | 01-APR-00:10 | 28321.21 | 23-APR-17:32 | 28321.21 | 23-APR-17:32 | 2025.36 | 23-APR-13:20 | 7092.85 | 23-APR-15:51 | 0.00 |
May | 0.194834E+11 | 0.469890E+10 | 212.62 | 0.181292E+11 | 0.135415E+10 | 0.00 | 1.00 | 16-MAY-12:05 | 0.00 | 01-MAY-00:10 | 65685.80 | 26-MAY-10:50 | 61200.89 | 18-MAY-15:20 | 22912.57 | 26-MAY-10:50 | 16413.16 | 25-MAY-16:00 | 0.00 |
June | 0.458232E+11 | 0.109427E+11 | 342.55 | 0.352021E+11 | 0.106210E+11 | 0.00 | 1.00 | 06-JUN-10:00 | 0.00 | 01-JUN-00:10 | 127997.93 | 30-JUN-04:01 | 75959.46 | 29-JUN-16:00 | 66555.99 | 29-JUN-05:12 | 29313.04 | 30-JUN-04:01 | 0.00 |
July | 0.613706E+11 | 0.143671E+11 | 386.77 | 0.460977E+11 | 0.152730E+11 | 0.00 | 1.00 | 03-JUL-05:12 | 0.00 | 01-JUL-00:10 | 134824.94 | 05-JUL-10:30 | 72014.10 | 21-JUL-15:40 | 86880.21 | 05-JUL-10:35 | 29198.27 | 05-JUL-10:35 | 0.00 |
August | 0.516470E+11 | 0.120536E+11 | 389.55 | 0.364251E+11 | 0.152220E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 94080.95 | 30-AUG-09:40 | 72287.91 | 08-AUG-15:30 | 51569.45 | 01-AUG-05:12 | 23431.19 | 08-AUG-15:00 | 0.00 |
September | 0.116445E+11 | 0.282452E+10 | 160.80 | 0.960278E+10 | 0.204176E+10 | 0.00 | 1.00 | 01-SEP-08:30 | 0.00 | 01-SEP-00:10 | 73278.86 | 01-SEP-15:30 | 68492.85 | 01-SEP-15:30 | 23837.79 | 01-SEP-09:00 | 17176.65 | 01-SEP-15:30 | 0.00 |
October | 0.167672E+10 | 0.421852E+09 | 35.06 | 0.161003E+10 | 66693599.98 | 0.00 | 0.96 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 37383.54 | 19-OCT-15:00 | 37383.54 | 19-OCT-15:00 | 3756.40 | 22-OCT-11:42 | 8393.63 | 19-OCT-15:00 | 0.00 |
November | 0.288756E+09 | 76269630.94 | 8.17 | 0.216660E+09 | 72095881.04 | 0.00 | 0.46 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 15752.98 | 01-NOV-15:00 | 12517.29 | 01-NOV-15:00 | 3247.66 | 01-NOV-14:30 | 4051.55 | 01-NOV-15:00 | 0.00 |
December | 492032.95 | 135727.96 | 0.04 | 492032.95 | 0.00 | 0.00 | 0.20 | 28-DEC-07:02 | 0.00 | 01-DEC-00:10 | 6427.90 | 28-DEC-07:02 | 6427.90 | 28-DEC-07:02 | 0.00 | 28-DEC-07:03 | 1763.83 | 28-DEC-07:02 | 0.00 |
Annual Sum or Average | 0.193511E+12 | 0.457991E+11 | 1585.31 | 0.148855E+12 | 0.446562E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.613706E+11 | 0.143671E+11 | 389.55 | 0.460977E+11 | 0.152730E+11 | 0.00 | 1.00 | 0.00 | 134824.94 | 75959.46 | 86880.21 | 29313.04 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 48575.64 | 13907.02 | 0.02 | 48575.64 | 0.00 | 0.00 | 0.02 | 02-JAN-05:21 | 0.00 | 01-JAN-00:01 | 647.68 | 02-JAN-05:21 | 647.68 | 02-JAN-05:21 | 0.00 | 02-JAN-05:21 | 185.43 | 02-JAN-05:21 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 94686.89 | 27143.42 | 0.06 | 94686.89 | 0.00 | 0.00 | 0.02 | 23-MAR-13:03 | 0.00 | 01-MAR-00:10 | 473.43 | 23-MAR-13:03 | 473.43 | 23-MAR-13:03 | 0.00 | 23-MAR-13:03 | 135.72 | 23-MAR-13:03 | 0.00 |
April | 0.183898E+10 | 0.480683E+09 | 52.88 | 0.181871E+10 | 20268452.63 | 0.00 | 0.87 | 23-APR-16:42 | 0.00 | 01-APR-00:10 | 33081.16 | 23-APR-16:42 | 33081.16 | 23-APR-16:42 | 3373.56 | 23-APR-11:43 | 8081.82 | 23-APR-16:42 | 0.00 |
May | 0.194610E+11 | 0.472076E+10 | 220.39 | 0.180877E+11 | 0.137328E+10 | 0.00 | 1.00 | 16-MAY-12:05 | 0.00 | 01-MAY-00:10 | 69941.77 | 25-MAY-16:00 | 65808.14 | 18-MAY-14:05 | 23099.73 | 26-MAY-10:50 | 17566.30 | 25-MAY-16:00 | 0.00 |
June | 0.443200E+11 | 0.106527E+11 | 351.52 | 0.345199E+11 | 0.980006E+10 | 0.00 | 1.00 | 06-JUN-10:05 | 0.00 | 01-JUN-00:10 | 131565.25 | 30-JUN-04:01 | 78320.60 | 29-JUN-16:00 | 54809.72 | 30-JUN-05:02 | 29905.16 | 30-JUN-04:01 | 0.00 |
July | 0.574508E+11 | 0.135250E+11 | 392.16 | 0.432479E+11 | 0.142030E+11 | 0.00 | 1.00 | 03-JUL-12:00 | 0.00 | 01-JUL-00:10 | 136688.20 | 05-JUL-10:30 | 71533.15 | 24-JUL-14:05 | 88069.21 | 05-JUL-10:40 | 29601.78 | 05-JUL-10:35 | 0.00 |
August | 0.456244E+11 | 0.107585E+11 | 389.50 | 0.323408E+11 | 0.132836E+11 | 0.00 | 1.00 | 04-AUG-12:50 | 0.00 | 01-AUG-00:10 | 88661.97 | 31-AUG-12:40 | 68528.88 | 08-AUG-15:20 | 47846.92 | 31-AUG-12:40 | 22319.63 | 08-AUG-15:00 | 0.00 |
September | 0.102218E+11 | 0.251520E+10 | 160.10 | 0.839025E+10 | 0.183154E+10 | 0.00 | 1.00 | 01-SEP-08:40 | 0.00 | 01-SEP-00:10 | 68622.74 | 01-SEP-15:30 | 65450.76 | 01-SEP-15:30 | 22930.27 | 01-SEP-09:00 | 16088.25 | 01-SEP-15:30 | 0.00 |
October | 0.150627E+10 | 0.384787E+09 | 35.03 | 0.143682E+10 | 69458688.33 | 0.00 | 0.86 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 33079.19 | 19-OCT-15:00 | 33079.19 | 19-OCT-15:00 | 3477.33 | 22-OCT-12:32 | 7640.51 | 19-OCT-15:00 | 0.00 |
November | 0.248223E+09 | 66358998.04 | 8.08 | 0.177678E+09 | 70545330.48 | 0.00 | 0.40 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 13421.46 | 01-NOV-15:00 | 10014.04 | 01-NOV-15:00 | 3407.42 | 01-NOV-15:00 | 3511.28 | 01-NOV-15:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.180672E+12 | 0.431041E+11 | 1609.74 | 0.140020E+12 | 0.406517E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.574508E+11 | 0.135250E+11 | 392.16 | 0.432479E+11 | 0.142030E+11 | 0.00 | 1.00 | 0.00 | 136688.20 | 78320.60 | 88069.21 | 29905.16 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2678974.97 | 767053.46 | 0.87 | 2674259.05 | 4715.92 | 0.00 | 0.03 | 31-JAN-06:06 | 0.00 | 01-JAN-00:01 | 1595.95 | 31-JAN-06:06 | 1595.95 | 31-JAN-06:06 | 13.12 | 19-JAN-05:20 | 455.53 | 31-JAN-06:06 | 0.00 |
February | 4358084.90 | 1249010.39 | 1.86 | 4357645.05 | 439.85 | 0.00 | 0.03 | 27-FEB-06:16 | 0.00 | 01-FEB-00:03 | 1615.43 | 27-FEB-06:16 | 1615.43 | 27-FEB-06:16 | 2.20 | 08-FEB-05:50 | 461.05 | 27-FEB-06:16 | 0.00 |
March | 1804206.04 | 517293.81 | 0.86 | 1792967.91 | 11238.13 | 0.00 | 0.02 | 06-MAR-06:20 | 0.00 | 01-MAR-00:10 | 1166.79 | 06-MAR-06:20 | 1166.79 | 06-MAR-06:20 | 20.87 | 27-MAR-04:07 | 333.74 | 06-MAR-06:20 | 0.00 |
April | 0.212428E+10 | 0.562988E+09 | 51.67 | 0.205125E+10 | 73021760.58 | 0.00 | 0.85 | 23-APR-16:22 | 0.00 | 01-APR-00:10 | 48309.09 | 23-APR-16:22 | 48309.09 | 23-APR-16:22 | 6427.53 | 23-APR-12:32 | 11934.92 | 23-APR-16:22 | 0.00 |
May | 0.233466E+11 | 0.578395E+10 | 217.44 | 0.208758E+11 | 0.247081E+10 | 0.00 | 1.00 | 16-MAY-13:50 | 0.00 | 01-MAY-00:10 | 83572.85 | 25-MAY-15:20 | 79008.42 | 18-MAY-14:50 | 23105.94 | 26-MAY-10:50 | 20879.55 | 25-MAY-15:20 | 0.00 |
June | 0.512242E+11 | 0.126067E+11 | 349.20 | 0.391865E+11 | 0.120376E+11 | 0.00 | 1.00 | 08-JUN-12:50 | 0.00 | 01-JUN-00:10 | 152075.40 | 30-JUN-04:01 | 93232.46 | 30-JUN-15:00 | 69351.13 | 30-JUN-04:01 | 34661.79 | 30-JUN-04:01 | 0.00 |
July | 0.660331E+11 | 0.158691E+11 | 389.64 | 0.488345E+11 | 0.171986E+11 | 0.00 | 1.00 | 03-JUL-12:40 | 0.00 | 01-JUL-00:10 | 128686.11 | 05-JUL-13:00 | 84705.09 | 24-JUL-14:50 | 80234.07 | 05-JUL-10:40 | 28189.35 | 05-JUL-13:00 | 0.00 |
August | 0.519818E+11 | 0.125616E+11 | 384.97 | 0.355558E+11 | 0.164259E+11 | 0.00 | 1.00 | 07-AUG-15:00 | 0.00 | 01-AUG-00:10 | 99060.74 | 08-AUG-15:00 | 81120.40 | 08-AUG-15:00 | 42748.17 | 31-AUG-12:40 | 25490.95 | 08-AUG-15:00 | 0.00 |
September | 0.112553E+11 | 0.284815E+10 | 155.03 | 0.871891E+10 | 0.253635E+10 | 0.00 | 1.00 | 01-SEP-10:40 | 0.00 | 01-SEP-00:10 | 78291.47 | 01-SEP-15:30 | 73581.76 | 01-SEP-15:30 | 23295.00 | 01-SEP-09:00 | 18356.63 | 01-SEP-15:30 | 0.00 |
October | 0.166974E+10 | 0.439416E+09 | 32.88 | 0.149482E+10 | 0.174919E+09 | 0.00 | 0.71 | 22-OCT-13:42 | 0.00 | 01-OCT-00:10 | 39551.54 | 22-OCT-13:42 | 35624.59 | 22-OCT-13:42 | 4669.14 | 22-OCT-13:03 | 9524.30 | 22-OCT-13:42 | 0.00 |
November | 0.326466E+09 | 88081014.84 | 9.21 | 0.223680E+09 | 0.102786E+09 | 0.00 | 0.34 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 17319.67 | 01-NOV-15:00 | 12082.92 | 01-NOV-15:00 | 5236.76 | 01-NOV-15:00 | 4591.12 | 01-NOV-15:00 | 0.00 |
December | 2710316.14 | 776478.18 | 1.08 | 2698480.66 | 11835.48 | 0.00 | 0.04 | 15-DEC-06:04 | 0.00 | 01-DEC-00:10 | 1659.07 | 15-DEC-06:04 | 1659.07 | 15-DEC-06:04 | 20.00 | 05-DEC-05:47 | 473.40 | 15-DEC-06:04 | 0.00 |
Annual Sum or Average | 0.207973E+12 | 0.507633E+11 | 1594.70 | 0.156953E+12 | 0.510201E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1804206.04 | 517293.81 | 0.86 | 1792967.91 | 439.85 | 0.00 | 0.02 | 0.00 | 1166.79 | 1166.79 | 2.20 | 333.74 | 0.00 | ||||||
Maximum of Months | 0.660331E+11 | 0.158691E+11 | 389.64 | 0.488345E+11 | 0.171986E+11 | 0.00 | 1.00 | 0.00 | 152075.40 | 93232.46 | 80234.07 | 34661.79 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 404.51 | 0.00 | 404.51 | 0.94 | 4861.29 | 0.00 | 0.00 | 0.00 |
February | 621.35 | 0.00 | 621.35 | 19.19 | 3911.44 | 0.00 | 0.00 | 0.00 |
March | 764.46 | 0.00 | 764.46 | 48.14 | 3057.74 | 0.00 | 0.00 | 0.00 |
April | 1002.17 | 7.82 | 994.34 | 321.97 | 1749.05 | 0.00 | 0.00 | 0.00 |
May | 1409.51 | 75.90 | 1333.61 | 1080.82 | 869.85 | 0.00 | 0.00 | 0.00 |
June | 1573.03 | 172.92 | 1400.12 | 1569.36 | 599.38 | 0.00 | 0.00 | 0.00 |
July | 1502.49 | 128.94 | 1373.55 | 1591.50 | 559.86 | 0.00 | 0.00 | 0.00 |
August | 1141.19 | 19.60 | 1121.59 | 1084.14 | 641.12 | 0.00 | 0.00 | 0.00 |
September | 889.30 | 0.22 | 889.08 | 572.37 | 1064.72 | 0.00 | 0.00 | 0.00 |
October | 617.48 | 0.00 | 617.48 | 140.56 | 1708.07 | 0.00 | 0.00 | 0.00 |
November | 408.85 | 0.00 | 408.85 | 18.45 | 2783.31 | 0.00 | 0.00 | 0.00 |
December | 342.73 | 0.00 | 342.73 | 0.00 | 4630.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 891.10 | 33.94 | 857.17 | 540.63 | 2196.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.73 | 0.00 | 342.73 | 0.00 | 559.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1573.03 | 172.92 | 1400.12 | 1591.50 | 4861.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 591.22 | 246.79 | 344.43 | 134.45 | 2915.58 | 0.00 | 0.00 | 0.00 |
February | 929.05 | 396.29 | 532.76 | 406.06 | 2300.38 | 0.00 | 0.00 | 0.00 |
March | 1265.89 | 634.99 | 630.91 | 786.81 | 1822.22 | 0.00 | 0.00 | 0.00 |
April | 1754.90 | 946.55 | 808.35 | 1468.45 | 1069.99 | 0.00 | 0.00 | 0.00 |
May | 1899.31 | 834.96 | 1064.36 | 1881.39 | 586.76 | 0.00 | 0.00 | 0.00 |
June | 2150.15 | 1028.53 | 1121.62 | 2399.57 | 415.90 | 0.00 | 0.00 | 0.00 |
July | 2106.36 | 989.01 | 1117.35 | 2436.18 | 382.53 | 0.00 | 0.00 | 0.00 |
August | 1624.01 | 709.80 | 914.21 | 1786.95 | 433.99 | 0.00 | 0.00 | 0.00 |
September | 1300.56 | 582.12 | 718.44 | 1224.86 | 680.07 | 0.00 | 0.00 | 0.00 |
October | 787.51 | 298.62 | 488.89 | 500.34 | 1068.99 | 0.00 | 0.00 | 0.00 |
November | 501.34 | 167.61 | 333.73 | 179.83 | 1702.40 | 0.00 | 0.00 | 0.00 |
December | 457.46 | 169.09 | 288.38 | 83.52 | 2825.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1281.94 | 584.17 | 697.77 | 1110.82 | 1346.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.46 | 167.61 | 288.38 | 83.52 | 382.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2150.15 | 1028.53 | 1121.62 | 2436.18 | 2915.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2785.38 | 1937.72 | 847.66 | 1903.25 | 3806.17 | 0.00 | 0.00 | 0.00 |
February | 3526.96 | 2382.23 | 1144.73 | 2856.61 | 3155.58 | 0.00 | 0.00 | 0.00 |
March | 3107.68 | 1966.73 | 1140.96 | 2611.36 | 2641.60 | 0.00 | 0.00 | 0.00 |
April | 2815.47 | 1528.15 | 1287.32 | 2658.08 | 1720.74 | 0.00 | 0.00 | 0.00 |
May | 2367.07 | 809.24 | 1557.83 | 2486.36 | 969.00 | 0.00 | 0.00 | 0.00 |
June | 2123.93 | 566.12 | 1557.81 | 2439.39 | 667.20 | 0.00 | 0.00 | 0.00 |
July | 2322.14 | 735.64 | 1586.50 | 2812.91 | 616.18 | 0.00 | 0.00 | 0.00 |
August | 2479.91 | 1037.32 | 1442.59 | 2899.82 | 696.71 | 0.00 | 0.00 | 0.00 |
September | 2656.35 | 1414.70 | 1241.65 | 2817.67 | 1088.98 | 0.00 | 0.00 | 0.00 |
October | 2268.33 | 1334.12 | 934.22 | 2059.77 | 1607.28 | 0.00 | 0.00 | 0.00 |
November | 2020.58 | 1268.12 | 752.47 | 1553.02 | 2366.72 | 0.00 | 0.00 | 0.00 |
December | 2150.65 | 1410.20 | 740.44 | 1337.49 | 3713.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2545.65 | 1359.38 | 1186.26 | 2365.67 | 1915.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2020.58 | 566.12 | 740.44 | 1337.49 | 616.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3526.96 | 2382.23 | 1586.50 | 2899.82 | 3806.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 597.55 | 250.22 | 347.33 | 164.61 | 2995.67 | 0.00 | 0.00 | 0.00 |
February | 973.59 | 444.67 | 528.92 | 501.26 | 2400.78 | 0.00 | 0.00 | 0.00 |
March | 1281.17 | 655.56 | 625.61 | 849.54 | 1890.79 | 0.00 | 0.00 | 0.00 |
April | 1636.62 | 828.93 | 807.69 | 1371.74 | 1142.91 | 0.00 | 0.00 | 0.00 |
May | 2010.88 | 959.19 | 1051.69 | 2094.26 | 636.79 | 0.00 | 0.00 | 0.00 |
June | 1940.45 | 839.03 | 1101.42 | 2184.23 | 442.80 | 0.00 | 0.00 | 0.00 |
July | 2071.62 | 963.09 | 1108.54 | 2421.80 | 419.60 | 0.00 | 0.00 | 0.00 |
August | 1704.81 | 774.65 | 930.16 | 1924.07 | 463.80 | 0.00 | 0.00 | 0.00 |
September | 1332.37 | 598.61 | 733.76 | 1290.86 | 719.56 | 0.00 | 0.00 | 0.00 |
October | 841.67 | 337.88 | 503.79 | 589.26 | 1107.85 | 0.00 | 0.00 | 0.00 |
November | 511.19 | 172.35 | 338.84 | 194.37 | 1748.35 | 0.00 | 0.00 | 0.00 |
December | 455.70 | 159.50 | 296.20 | 83.92 | 2893.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1281.49 | 582.80 | 698.69 | 1143.08 | 1401.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 455.70 | 159.50 | 296.20 | 83.92 | 419.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2071.62 | 963.09 | 1108.54 | 2421.80 | 2995.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.83 | 0.00 | 134.83 | 0.22 | 1608.32 | 0.00 | 0.00 | 0.00 |
February | 207.11 | 0.00 | 207.11 | 7.06 | 1290.83 | 0.00 | 0.00 | 0.00 |
March | 254.81 | 0.00 | 254.81 | 19.39 | 992.77 | 0.00 | 0.00 | 0.00 |
April | 334.04 | 2.61 | 331.44 | 125.38 | 563.44 | 0.00 | 0.00 | 0.00 |
May | 469.82 | 25.30 | 444.52 | 396.02 | 271.86 | 0.00 | 0.00 | 0.00 |
June | 524.33 | 57.64 | 466.69 | 553.53 | 187.71 | 0.00 | 0.00 | 0.00 |
July | 500.81 | 42.98 | 457.83 | 544.61 | 184.57 | 0.00 | 0.00 | 0.00 |
August | 380.38 | 6.53 | 373.85 | 362.79 | 226.10 | 0.00 | 0.00 | 0.00 |
September | 296.42 | 0.07 | 296.35 | 186.94 | 383.54 | 0.00 | 0.00 | 0.00 |
October | 205.82 | 0.00 | 205.82 | 43.24 | 620.89 | 0.00 | 0.00 | 0.00 |
November | 136.28 | 0.00 | 136.28 | 6.00 | 971.97 | 0.00 | 0.00 | 0.00 |
December | 114.24 | 0.00 | 114.24 | 0.00 | 1547.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 297.02 | 11.31 | 285.71 | 188.24 | 735.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.24 | 0.00 | 114.24 | 0.00 | 184.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 524.33 | 57.64 | 466.69 | 553.53 | 1608.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.84 | 0.00 | 134.84 | 0.22 | 1608.42 | 0.00 | 0.00 | 0.00 |
February | 207.12 | 0.00 | 207.12 | 7.06 | 1290.91 | 0.00 | 0.00 | 0.00 |
March | 254.82 | 0.00 | 254.82 | 19.39 | 992.83 | 0.00 | 0.00 | 0.00 |
April | 334.06 | 2.61 | 331.45 | 125.39 | 563.48 | 0.00 | 0.00 | 0.00 |
May | 469.84 | 25.30 | 444.54 | 396.04 | 271.88 | 0.00 | 0.00 | 0.00 |
June | 524.35 | 57.64 | 466.71 | 553.56 | 187.72 | 0.00 | 0.00 | 0.00 |
July | 500.84 | 42.98 | 457.86 | 544.63 | 184.58 | 0.00 | 0.00 | 0.00 |
August | 380.40 | 6.53 | 373.87 | 362.81 | 226.11 | 0.00 | 0.00 | 0.00 |
September | 296.44 | 0.07 | 296.36 | 186.94 | 383.56 | 0.00 | 0.00 | 0.00 |
October | 205.83 | 0.00 | 205.83 | 43.25 | 620.93 | 0.00 | 0.00 | 0.00 |
November | 136.29 | 0.00 | 136.29 | 6.00 | 972.03 | 0.00 | 0.00 | 0.00 |
December | 114.24 | 0.00 | 114.24 | 0.00 | 1547.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 297.04 | 11.31 | 285.72 | 188.25 | 735.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.24 | 0.00 | 114.24 | 0.00 | 184.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 524.35 | 57.64 | 466.71 | 553.56 | 1608.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.84 | 0.00 | 134.84 | 0.22 | 1608.42 | 0.00 | 0.00 | 0.00 |
February | 207.12 | 0.00 | 207.12 | 7.06 | 1290.91 | 0.00 | 0.00 | 0.00 |
March | 254.82 | 0.00 | 254.82 | 19.39 | 992.83 | 0.00 | 0.00 | 0.00 |
April | 334.06 | 2.61 | 331.45 | 125.39 | 563.48 | 0.00 | 0.00 | 0.00 |
May | 469.84 | 25.30 | 444.54 | 396.04 | 271.88 | 0.00 | 0.00 | 0.00 |
June | 524.35 | 57.64 | 466.71 | 553.56 | 187.72 | 0.00 | 0.00 | 0.00 |
July | 500.84 | 42.98 | 457.86 | 544.63 | 184.58 | 0.00 | 0.00 | 0.00 |
August | 380.40 | 6.53 | 373.87 | 362.81 | 226.11 | 0.00 | 0.00 | 0.00 |
September | 296.44 | 0.07 | 296.36 | 186.94 | 383.56 | 0.00 | 0.00 | 0.00 |
October | 205.83 | 0.00 | 205.83 | 43.25 | 620.93 | 0.00 | 0.00 | 0.00 |
November | 136.29 | 0.00 | 136.29 | 6.00 | 972.03 | 0.00 | 0.00 | 0.00 |
December | 114.24 | 0.00 | 114.24 | 0.00 | 1547.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 297.04 | 11.31 | 285.72 | 188.25 | 735.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.24 | 0.00 | 114.24 | 0.00 | 184.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 524.35 | 57.64 | 466.71 | 553.56 | 1608.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 568.75 | 237.42 | 331.34 | 133.87 | 2792.19 | 0.00 | 0.00 | 0.00 |
February | 893.75 | 381.23 | 512.51 | 401.22 | 2204.88 | 0.00 | 0.00 | 0.00 |
March | 1217.79 | 610.86 | 606.93 | 779.68 | 1725.73 | 0.00 | 0.00 | 0.00 |
April | 1688.21 | 910.59 | 777.62 | 1458.23 | 1021.26 | 0.00 | 0.00 | 0.00 |
May | 1827.14 | 803.23 | 1023.91 | 1868.11 | 551.16 | 0.00 | 0.00 | 0.00 |
June | 2068.45 | 989.45 | 1078.99 | 2350.76 | 398.85 | 0.00 | 0.00 | 0.00 |
July | 2026.31 | 951.43 | 1074.88 | 2363.39 | 383.39 | 0.00 | 0.00 | 0.00 |
August | 1562.29 | 682.83 | 879.46 | 1719.67 | 462.25 | 0.00 | 0.00 | 0.00 |
September | 1251.13 | 560.00 | 691.13 | 1165.49 | 727.80 | 0.00 | 0.00 | 0.00 |
October | 757.58 | 287.27 | 470.31 | 468.72 | 1136.48 | 0.00 | 0.00 | 0.00 |
November | 482.28 | 161.24 | 321.05 | 170.74 | 1729.31 | 0.00 | 0.00 | 0.00 |
December | 440.08 | 162.66 | 277.42 | 81.38 | 2734.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1233.22 | 561.97 | 671.25 | 1083.42 | 1318.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 440.08 | 161.24 | 277.42 | 81.38 | 383.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2068.45 | 989.45 | 1078.99 | 2363.39 | 2792.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.49 | 9.39 | 13.10 | 5.29 | 110.40 | 0.00 | 0.00 | 0.00 |
February | 35.34 | 15.07 | 20.26 | 15.86 | 87.18 | 0.00 | 0.00 | 0.00 |
March | 48.15 | 24.15 | 24.00 | 30.83 | 68.23 | 0.00 | 0.00 | 0.00 |
April | 66.75 | 36.00 | 30.75 | 57.66 | 40.38 | 0.00 | 0.00 | 0.00 |
May | 72.24 | 31.76 | 40.48 | 73.86 | 21.79 | 0.00 | 0.00 | 0.00 |
June | 81.78 | 39.12 | 42.66 | 92.95 | 15.77 | 0.00 | 0.00 | 0.00 |
July | 80.12 | 37.62 | 42.50 | 93.45 | 15.16 | 0.00 | 0.00 | 0.00 |
August | 61.77 | 27.00 | 34.77 | 67.99 | 18.28 | 0.00 | 0.00 | 0.00 |
September | 49.47 | 22.14 | 27.33 | 46.08 | 28.78 | 0.00 | 0.00 | 0.00 |
October | 29.95 | 11.36 | 18.60 | 18.53 | 44.94 | 0.00 | 0.00 | 0.00 |
November | 19.07 | 6.38 | 12.69 | 6.75 | 68.38 | 0.00 | 0.00 | 0.00 |
December | 17.40 | 6.43 | 10.97 | 3.22 | 108.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.76 | 22.22 | 26.54 | 42.84 | 52.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.40 | 6.38 | 10.97 | 3.22 | 15.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 81.78 | 39.12 | 42.66 | 93.45 | 110.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 928.48 | 645.93 | 282.56 | 658.14 | 1243.37 | 0.00 | 0.00 | 0.00 |
February | 1175.68 | 794.10 | 381.59 | 982.22 | 1049.74 | 0.00 | 0.00 | 0.00 |
March | 1035.92 | 655.59 | 380.33 | 900.97 | 872.86 | 0.00 | 0.00 | 0.00 |
April | 938.51 | 509.40 | 429.12 | 915.77 | 573.57 | 0.00 | 0.00 | 0.00 |
May | 789.04 | 269.75 | 519.29 | 860.87 | 314.76 | 0.00 | 0.00 | 0.00 |
June | 707.99 | 188.71 | 519.28 | 840.00 | 214.64 | 0.00 | 0.00 | 0.00 |
July | 774.07 | 245.22 | 528.85 | 951.09 | 211.92 | 0.00 | 0.00 | 0.00 |
August | 826.66 | 345.78 | 480.87 | 971.83 | 257.60 | 0.00 | 0.00 | 0.00 |
September | 885.47 | 471.58 | 413.89 | 940.25 | 408.04 | 0.00 | 0.00 | 0.00 |
October | 756.13 | 444.72 | 311.41 | 684.21 | 600.01 | 0.00 | 0.00 | 0.00 |
November | 673.55 | 422.72 | 250.83 | 521.73 | 837.07 | 0.00 | 0.00 | 0.00 |
December | 716.90 | 470.08 | 246.82 | 456.90 | 1226.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 848.57 | 453.14 | 395.43 | 805.59 | 649.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 673.55 | 188.71 | 246.82 | 456.90 | 211.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1175.68 | 794.10 | 528.85 | 982.22 | 1243.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 928.48 | 645.93 | 282.56 | 658.14 | 1243.37 | 0.00 | 0.00 | 0.00 |
February | 1175.68 | 794.10 | 381.59 | 982.22 | 1049.74 | 0.00 | 0.00 | 0.00 |
March | 1035.92 | 655.59 | 380.33 | 900.97 | 872.86 | 0.00 | 0.00 | 0.00 |
April | 938.51 | 509.40 | 429.12 | 915.77 | 573.57 | 0.00 | 0.00 | 0.00 |
May | 789.04 | 269.75 | 519.29 | 860.87 | 314.76 | 0.00 | 0.00 | 0.00 |
June | 707.99 | 188.71 | 519.28 | 840.00 | 214.64 | 0.00 | 0.00 | 0.00 |
July | 774.07 | 245.22 | 528.85 | 951.09 | 211.92 | 0.00 | 0.00 | 0.00 |
August | 826.66 | 345.78 | 480.87 | 971.83 | 257.60 | 0.00 | 0.00 | 0.00 |
September | 885.47 | 471.58 | 413.89 | 940.25 | 408.04 | 0.00 | 0.00 | 0.00 |
October | 756.13 | 444.72 | 311.41 | 684.21 | 600.01 | 0.00 | 0.00 | 0.00 |
November | 673.55 | 422.72 | 250.83 | 521.73 | 837.07 | 0.00 | 0.00 | 0.00 |
December | 716.90 | 470.08 | 246.82 | 456.90 | 1226.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 848.57 | 453.14 | 395.43 | 805.59 | 649.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 673.55 | 188.71 | 246.82 | 456.90 | 211.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1175.68 | 794.10 | 528.85 | 982.22 | 1243.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 928.43 | 645.88 | 282.54 | 658.10 | 1243.29 | 0.00 | 0.00 | 0.00 |
February | 1175.61 | 794.05 | 381.56 | 982.16 | 1049.67 | 0.00 | 0.00 | 0.00 |
March | 1035.86 | 655.55 | 380.30 | 900.91 | 872.80 | 0.00 | 0.00 | 0.00 |
April | 938.45 | 509.36 | 429.09 | 915.71 | 573.53 | 0.00 | 0.00 | 0.00 |
May | 788.99 | 269.74 | 519.26 | 860.82 | 314.74 | 0.00 | 0.00 | 0.00 |
June | 707.95 | 188.70 | 519.25 | 839.95 | 214.63 | 0.00 | 0.00 | 0.00 |
July | 774.02 | 245.20 | 528.81 | 951.03 | 211.90 | 0.00 | 0.00 | 0.00 |
August | 826.61 | 345.76 | 480.84 | 971.77 | 257.59 | 0.00 | 0.00 | 0.00 |
September | 885.42 | 471.55 | 413.87 | 940.19 | 408.01 | 0.00 | 0.00 | 0.00 |
October | 756.08 | 444.69 | 311.39 | 684.17 | 599.97 | 0.00 | 0.00 | 0.00 |
November | 673.50 | 422.69 | 250.81 | 521.70 | 837.02 | 0.00 | 0.00 | 0.00 |
December | 716.86 | 470.05 | 246.81 | 456.87 | 1226.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 848.52 | 453.11 | 395.41 | 805.54 | 649.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 673.50 | 188.70 | 246.81 | 456.87 | 211.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1175.61 | 794.05 | 528.81 | 982.16 | 1243.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 574.84 | 240.71 | 334.13 | 165.87 | 2862.11 | 0.00 | 0.00 | 0.00 |
February | 936.59 | 427.77 | 508.82 | 501.92 | 2300.79 | 0.00 | 0.00 | 0.00 |
March | 1232.48 | 630.65 | 601.83 | 848.93 | 1796.23 | 0.00 | 0.00 | 0.00 |
April | 1574.42 | 797.43 | 776.99 | 1370.65 | 1093.07 | 0.00 | 0.00 | 0.00 |
May | 1934.46 | 922.75 | 1011.71 | 2068.77 | 607.03 | 0.00 | 0.00 | 0.00 |
June | 1866.71 | 807.15 | 1059.56 | 2146.71 | 422.35 | 0.00 | 0.00 | 0.00 |
July | 1992.89 | 926.49 | 1066.40 | 2347.48 | 425.41 | 0.00 | 0.00 | 0.00 |
August | 1640.02 | 745.21 | 894.80 | 1849.80 | 496.50 | 0.00 | 0.00 | 0.00 |
September | 1281.74 | 575.87 | 705.87 | 1233.58 | 768.87 | 0.00 | 0.00 | 0.00 |
October | 809.68 | 325.04 | 484.64 | 560.40 | 1178.04 | 0.00 | 0.00 | 0.00 |
November | 491.76 | 165.80 | 325.96 | 187.53 | 1769.17 | 0.00 | 0.00 | 0.00 |
December | 438.38 | 153.44 | 284.94 | 83.90 | 2790.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1232.79 | 560.65 | 672.14 | 1117.50 | 1372.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 438.38 | 153.44 | 284.94 | 83.90 | 422.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1992.89 | 926.49 | 1066.40 | 2347.48 | 2862.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.73 | 9.52 | 13.21 | 6.56 | 113.17 | 0.00 | 0.00 | 0.00 |
February | 37.03 | 16.91 | 20.12 | 19.85 | 90.97 | 0.00 | 0.00 | 0.00 |
March | 48.73 | 24.94 | 23.80 | 33.57 | 71.02 | 0.00 | 0.00 | 0.00 |
April | 62.25 | 31.53 | 30.72 | 54.19 | 43.22 | 0.00 | 0.00 | 0.00 |
May | 76.49 | 36.48 | 40.00 | 81.80 | 24.00 | 0.00 | 0.00 | 0.00 |
June | 73.81 | 31.91 | 41.89 | 84.88 | 16.70 | 0.00 | 0.00 | 0.00 |
July | 78.80 | 36.63 | 42.16 | 92.82 | 16.82 | 0.00 | 0.00 | 0.00 |
August | 64.84 | 29.47 | 35.38 | 73.14 | 19.63 | 0.00 | 0.00 | 0.00 |
September | 50.68 | 22.77 | 27.91 | 48.77 | 30.40 | 0.00 | 0.00 | 0.00 |
October | 32.01 | 12.85 | 19.16 | 22.16 | 46.58 | 0.00 | 0.00 | 0.00 |
November | 19.44 | 6.56 | 12.89 | 7.41 | 69.95 | 0.00 | 0.00 | 0.00 |
December | 17.33 | 6.07 | 11.27 | 3.32 | 110.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.74 | 22.17 | 26.58 | 44.18 | 54.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.33 | 6.07 | 11.27 | 3.32 | 16.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.80 | 36.63 | 42.16 | 92.82 | 113.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 404.51 | 0.00 | 404.51 | 0.55 | 4934.64 | 0.00 | 0.00 | 0.00 |
February | 621.35 | 0.00 | 621.35 | 17.19 | 4002.66 | 0.00 | 0.00 | 0.00 |
March | 764.46 | 0.00 | 764.46 | 43.49 | 3163.57 | 0.00 | 0.00 | 0.00 |
April | 1002.17 | 7.82 | 994.34 | 305.91 | 1865.31 | 0.00 | 0.00 | 0.00 |
May | 1409.51 | 75.90 | 1333.61 | 1048.61 | 937.29 | 0.00 | 0.00 | 0.00 |
June | 1573.03 | 172.92 | 1400.12 | 1533.16 | 646.32 | 0.00 | 0.00 | 0.00 |
July | 1502.49 | 128.94 | 1373.55 | 1559.94 | 602.21 | 0.00 | 0.00 | 0.00 |
August | 1141.19 | 19.60 | 1121.59 | 1048.28 | 708.29 | 0.00 | 0.00 | 0.00 |
September | 889.30 | 0.22 | 889.08 | 536.02 | 1166.91 | 0.00 | 0.00 | 0.00 |
October | 617.48 | 0.00 | 617.48 | 122.61 | 1858.82 | 0.00 | 0.00 | 0.00 |
November | 408.85 | 0.00 | 408.85 | 16.89 | 2924.04 | 0.00 | 0.00 | 0.00 |
December | 342.73 | 0.00 | 342.73 | 0.00 | 4718.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 891.10 | 33.94 | 857.17 | 522.65 | 2287.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.73 | 0.00 | 342.73 | 0.00 | 602.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1573.03 | 172.92 | 1400.12 | 1559.94 | 4934.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 591.22 | 246.79 | 344.43 | 132.48 | 2959.25 | 0.00 | 0.00 | 0.00 |
February | 929.05 | 396.29 | 532.76 | 398.68 | 2356.32 | 0.00 | 0.00 | 0.00 |
March | 1265.89 | 634.99 | 630.91 | 770.77 | 1890.71 | 0.00 | 0.00 | 0.00 |
April | 1754.90 | 946.55 | 808.35 | 1443.30 | 1140.12 | 0.00 | 0.00 | 0.00 |
May | 1899.31 | 834.96 | 1064.36 | 1860.69 | 623.20 | 0.00 | 0.00 | 0.00 |
June | 2150.15 | 1028.53 | 1121.62 | 2386.29 | 442.49 | 0.00 | 0.00 | 0.00 |
July | 2106.36 | 989.01 | 1117.35 | 2426.13 | 405.93 | 0.00 | 0.00 | 0.00 |
August | 1624.01 | 709.80 | 914.21 | 1769.81 | 470.45 | 0.00 | 0.00 | 0.00 |
September | 1300.56 | 582.12 | 718.44 | 1196.04 | 738.20 | 0.00 | 0.00 | 0.00 |
October | 787.51 | 298.62 | 488.89 | 475.84 | 1163.78 | 0.00 | 0.00 | 0.00 |
November | 501.34 | 167.61 | 333.73 | 171.94 | 1792.72 | 0.00 | 0.00 | 0.00 |
December | 457.46 | 169.09 | 288.38 | 81.48 | 2877.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1281.94 | 584.17 | 697.77 | 1096.23 | 1401.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.46 | 167.61 | 288.38 | 81.48 | 405.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2150.15 | 1028.53 | 1121.62 | 2426.13 | 2959.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2785.38 | 1937.72 | 847.66 | 1888.99 | 3882.16 | 0.00 | 0.00 | 0.00 |
February | 3526.96 | 2382.23 | 1144.73 | 2834.55 | 3255.67 | 0.00 | 0.00 | 0.00 |
March | 3107.68 | 1966.73 | 1140.96 | 2588.74 | 2754.49 | 0.00 | 0.00 | 0.00 |
April | 2815.47 | 1528.15 | 1287.32 | 2634.36 | 1838.35 | 0.00 | 0.00 | 0.00 |
May | 2367.07 | 809.24 | 1557.83 | 2464.97 | 1042.44 | 0.00 | 0.00 | 0.00 |
June | 2123.93 | 566.12 | 1557.81 | 2419.10 | 722.87 | 0.00 | 0.00 | 0.00 |
July | 2322.14 | 735.64 | 1586.50 | 2795.96 | 666.33 | 0.00 | 0.00 | 0.00 |
August | 2479.91 | 1037.32 | 1442.59 | 2877.38 | 766.80 | 0.00 | 0.00 | 0.00 |
September | 2656.35 | 1414.70 | 1241.65 | 2785.71 | 1188.24 | 0.00 | 0.00 | 0.00 |
October | 2268.33 | 1334.12 | 934.22 | 2027.08 | 1747.29 | 0.00 | 0.00 | 0.00 |
November | 2020.58 | 1268.12 | 752.47 | 1528.06 | 2502.43 | 0.00 | 0.00 | 0.00 |
December | 2150.65 | 1410.20 | 740.44 | 1320.24 | 3803.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2545.65 | 1359.38 | 1186.26 | 2343.15 | 2008.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2020.58 | 566.12 | 740.44 | 1320.24 | 666.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3526.96 | 2382.23 | 1586.50 | 2877.38 | 3882.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 597.55 | 250.22 | 347.33 | 163.42 | 3042.13 | 0.00 | 0.00 | 0.00 |
February | 973.59 | 444.67 | 528.92 | 499.14 | 2461.52 | 0.00 | 0.00 | 0.00 |
March | 1281.17 | 655.56 | 625.61 | 845.35 | 1962.10 | 0.00 | 0.00 | 0.00 |
April | 1636.62 | 828.93 | 807.69 | 1363.77 | 1217.42 | 0.00 | 0.00 | 0.00 |
May | 2010.88 | 959.19 | 1051.69 | 2087.06 | 679.88 | 0.00 | 0.00 | 0.00 |
June | 1940.45 | 839.03 | 1101.42 | 2178.00 | 473.98 | 0.00 | 0.00 | 0.00 |
July | 2071.62 | 963.09 | 1108.54 | 2416.45 | 448.04 | 0.00 | 0.00 | 0.00 |
August | 1704.81 | 774.65 | 930.16 | 1914.28 | 502.68 | 0.00 | 0.00 | 0.00 |
September | 1332.37 | 598.61 | 733.76 | 1275.94 | 779.96 | 0.00 | 0.00 | 0.00 |
October | 841.67 | 337.88 | 503.79 | 576.54 | 1202.27 | 0.00 | 0.00 | 0.00 |
November | 511.19 | 172.35 | 338.84 | 188.82 | 1837.23 | 0.00 | 0.00 | 0.00 |
December | 455.70 | 159.50 | 296.20 | 83.05 | 2948.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1281.49 | 582.80 | 698.69 | 1136.56 | 1459.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 455.70 | 159.50 | 296.20 | 83.05 | 448.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2071.62 | 963.09 | 1108.54 | 2416.45 | 3042.13 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108343E+10 | 0.00 | 0.108343E+10 | 2507156.34 | 0.130205E+11 |
February | 0.150317E+10 | 0.00 | 0.150317E+10 | 46415590.65 | 0.946257E+10 |
March | 0.204754E+10 | 0.00 | 0.204754E+10 | 0.128938E+09 | 0.818984E+10 |
April | 0.259761E+10 | 20273950.62 | 0.257734E+10 | 0.834545E+09 | 0.453355E+10 |
May | 0.377523E+10 | 0.203289E+09 | 0.357194E+10 | 0.289488E+10 | 0.232979E+10 |
June | 0.407730E+10 | 0.448202E+09 | 0.362910E+10 | 0.406778E+10 | 0.155360E+10 |
July | 0.402428E+10 | 0.345358E+09 | 0.367892E+10 | 0.426266E+10 | 0.149952E+10 |
August | 0.305657E+10 | 52490347.80 | 0.300408E+10 | 0.290376E+10 | 0.171716E+10 |
September | 0.230506E+10 | 565041.23 | 0.230449E+10 | 0.148360E+10 | 0.275975E+10 |
October | 0.165387E+10 | 0.00 | 0.165387E+10 | 0.376488E+09 | 0.457490E+10 |
November | 0.105974E+10 | 0.00 | 0.105974E+10 | 47813300.53 | 0.721433E+10 |
December | 0.917965E+09 | 0.00 | 0.917965E+09 | 0.00 | 0.124010E+11 |
Annual Sum or Average | 0.281018E+11 | 0.107018E+10 | 0.270316E+11 | 0.170494E+11 | 0.692565E+11 |
Minimum of Months | 0.917965E+09 | 0.00 | 0.917965E+09 | 0.00 | 0.149952E+10 |
Maximum of Months | 0.407730E+10 | 0.448202E+09 | 0.367892E+10 | 0.426266E+10 | 0.130205E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158353E+10 | 0.661011E+09 | 0.922518E+09 | 0.360108E+09 | 0.780909E+10 |
February | 0.224756E+10 | 0.958706E+09 | 0.128886E+10 | 0.982331E+09 | 0.556509E+10 |
March | 0.339057E+10 | 0.170075E+10 | 0.168982E+10 | 0.210739E+10 | 0.488063E+10 |
April | 0.454869E+10 | 0.245346E+10 | 0.209523E+10 | 0.380621E+10 | 0.277341E+10 |
May | 0.508712E+10 | 0.223634E+10 | 0.285078E+10 | 0.503911E+10 | 0.157157E+10 |
June | 0.557320E+10 | 0.266596E+10 | 0.290724E+10 | 0.621970E+10 | 0.107801E+10 |
July | 0.564167E+10 | 0.264896E+10 | 0.299271E+10 | 0.652508E+10 | 0.102457E+10 |
August | 0.434974E+10 | 0.190113E+10 | 0.244861E+10 | 0.478617E+10 | 0.116239E+10 |
September | 0.337104E+10 | 0.150885E+10 | 0.186219E+10 | 0.317483E+10 | 0.176273E+10 |
October | 0.210927E+10 | 0.799826E+09 | 0.130944E+10 | 0.134010E+10 | 0.286319E+10 |
November | 0.129946E+10 | 0.434437E+09 | 0.865024E+09 | 0.466124E+09 | 0.441263E+10 |
December | 0.122527E+10 | 0.452877E+09 | 0.772393E+09 | 0.223707E+09 | 0.756676E+10 |
Annual Sum or Average | 0.404271E+11 | 0.184223E+11 | 0.220048E+11 | 0.350309E+11 | 0.424701E+11 |
Minimum of Months | 0.122527E+10 | 0.434437E+09 | 0.772393E+09 | 0.223707E+09 | 0.102457E+10 |
Maximum of Months | 0.564167E+10 | 0.266596E+10 | 0.299271E+10 | 0.652508E+10 | 0.780909E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746036E+10 | 0.519000E+10 | 0.227036E+10 | 0.509765E+10 | 0.101944E+11 |
February | 0.853242E+10 | 0.576308E+10 | 0.276934E+10 | 0.691072E+10 | 0.763398E+10 |
March | 0.832362E+10 | 0.526768E+10 | 0.305594E+10 | 0.699426E+10 | 0.707526E+10 |
April | 0.729769E+10 | 0.396096E+10 | 0.333673E+10 | 0.688973E+10 | 0.446016E+10 |
May | 0.633997E+10 | 0.216747E+10 | 0.417250E+10 | 0.665947E+10 | 0.259537E+10 |
June | 0.550523E+10 | 0.146737E+10 | 0.403785E+10 | 0.632289E+10 | 0.172939E+10 |
July | 0.621963E+10 | 0.197033E+10 | 0.424929E+10 | 0.753410E+10 | 0.165037E+10 |
August | 0.664220E+10 | 0.277836E+10 | 0.386383E+10 | 0.776688E+10 | 0.186606E+10 |
September | 0.688526E+10 | 0.366690E+10 | 0.321836E+10 | 0.730341E+10 | 0.282265E+10 |
October | 0.607550E+10 | 0.357330E+10 | 0.250221E+10 | 0.551689E+10 | 0.430494E+10 |
November | 0.523735E+10 | 0.328696E+10 | 0.195039E+10 | 0.402543E+10 | 0.613454E+10 |
December | 0.576029E+10 | 0.377709E+10 | 0.198321E+10 | 0.358234E+10 | 0.994689E+10 |
Annual Sum or Average | 0.802795E+11 | 0.428695E+11 | 0.374100E+11 | 0.746038E+11 | 0.604141E+11 |
Minimum of Months | 0.523735E+10 | 0.146737E+10 | 0.195039E+10 | 0.358234E+10 | 0.165037E+10 |
Maximum of Months | 0.853242E+10 | 0.576308E+10 | 0.424929E+10 | 0.776688E+10 | 0.101944E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160048E+10 | 0.670185E+09 | 0.930298E+09 | 0.440903E+09 | 0.802360E+10 |
February | 0.235530E+10 | 0.107574E+10 | 0.127956E+10 | 0.121266E+10 | 0.580797E+10 |
March | 0.343148E+10 | 0.175586E+10 | 0.167562E+10 | 0.227541E+10 | 0.506430E+10 |
April | 0.424212E+10 | 0.214858E+10 | 0.209354E+10 | 0.355555E+10 | 0.296242E+10 |
May | 0.538594E+10 | 0.256911E+10 | 0.281683E+10 | 0.560928E+10 | 0.170557E+10 |
June | 0.502966E+10 | 0.217477E+10 | 0.285489E+10 | 0.566151E+10 | 0.114774E+10 |
July | 0.554863E+10 | 0.257953E+10 | 0.296911E+10 | 0.648655E+10 | 0.112385E+10 |
August | 0.456616E+10 | 0.207482E+10 | 0.249133E+10 | 0.515342E+10 | 0.124225E+10 |
September | 0.345351E+10 | 0.155160E+10 | 0.190191E+10 | 0.334590E+10 | 0.186510E+10 |
October | 0.225432E+10 | 0.904981E+09 | 0.134934E+10 | 0.157827E+10 | 0.296727E+10 |
November | 0.132500E+10 | 0.446737E+09 | 0.878262E+09 | 0.503808E+09 | 0.453171E+10 |
December | 0.122053E+10 | 0.427194E+09 | 0.793341E+09 | 0.224784E+09 | 0.774896E+10 |
Annual Sum or Average | 0.404131E+11 | 0.183791E+11 | 0.220340E+11 | 0.360481E+11 | 0.441907E+11 |
Minimum of Months | 0.122053E+10 | 0.427194E+09 | 0.793341E+09 | 0.224784E+09 | 0.112385E+10 |
Maximum of Months | 0.554863E+10 | 0.257953E+10 | 0.296911E+10 | 0.648655E+10 | 0.802360E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.361129E+09 | 0.00 | 0.361129E+09 | 576367.69 | 0.430772E+10 |
February | 0.501039E+09 | 0.00 | 0.501039E+09 | 17070563.18 | 0.312278E+10 |
March | 0.682489E+09 | 0.00 | 0.682489E+09 | 51938077.45 | 0.265903E+10 |
April | 0.865839E+09 | 6757770.48 | 0.859081E+09 | 0.324991E+09 | 0.146045E+10 |
May | 0.125836E+10 | 67760950.87 | 0.119060E+10 | 0.106070E+10 | 0.728153E+09 |
June | 0.135905E+10 | 0.149396E+09 | 0.120965E+10 | 0.143475E+10 | 0.486552E+09 |
July | 0.134138E+10 | 0.115116E+09 | 0.122626E+10 | 0.145868E+10 | 0.494352E+09 |
August | 0.101882E+10 | 17496230.97 | 0.100132E+10 | 0.971700E+09 | 0.605578E+09 |
September | 0.768325E+09 | 188341.14 | 0.768136E+09 | 0.484543E+09 | 0.994132E+09 |
October | 0.551268E+09 | 0.00 | 0.551268E+09 | 0.115827E+09 | 0.166298E+10 |
November | 0.353235E+09 | 0.00 | 0.353235E+09 | 15539623.94 | 0.251934E+10 |
December | 0.305977E+09 | 0.00 | 0.305977E+09 | 0.00 | 0.414516E+10 |
Annual Sum or Average | 0.936691E+10 | 0.356715E+09 | 0.901020E+10 | 0.593632E+10 | 0.231862E+11 |
Minimum of Months | 0.305977E+09 | 0.00 | 0.305977E+09 | 0.00 | 0.486552E+09 |
Maximum of Months | 0.135905E+10 | 0.149396E+09 | 0.122626E+10 | 0.145868E+10 | 0.430772E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.361146E+09 | 0.00 | 0.361146E+09 | 576310.52 | 0.430799E+10 |
February | 0.501063E+09 | 0.00 | 0.501063E+09 | 17070334.85 | 0.312298E+10 |
March | 0.682521E+09 | 0.00 | 0.682521E+09 | 51938609.13 | 0.265920E+10 |
April | 0.865881E+09 | 6758031.42 | 0.859123E+09 | 0.325003E+09 | 0.146054E+10 |
May | 0.125842E+10 | 67763567.35 | 0.119066E+10 | 0.106075E+10 | 0.728198E+09 |
June | 0.135911E+10 | 0.149402E+09 | 0.120971E+10 | 0.143482E+10 | 0.486581E+09 |
July | 0.134144E+10 | 0.115120E+09 | 0.122632E+10 | 0.145875E+10 | 0.494381E+09 |
August | 0.101887E+10 | 17496906.56 | 0.100137E+10 | 0.971744E+09 | 0.605614E+09 |
September | 0.768361E+09 | 188348.41 | 0.768172E+09 | 0.484561E+09 | 0.994194E+09 |
October | 0.551294E+09 | 0.00 | 0.551294E+09 | 0.115829E+09 | 0.166309E+10 |
November | 0.353251E+09 | 0.00 | 0.353251E+09 | 15539968.23 | 0.251950E+10 |
December | 0.305991E+09 | 0.00 | 0.305991E+09 | 0.00 | 0.414542E+10 |
Annual Sum or Average | 0.936735E+10 | 0.356729E+09 | 0.901062E+10 | 0.593657E+10 | 0.231877E+11 |
Minimum of Months | 0.305991E+09 | 0.00 | 0.305991E+09 | 0.00 | 0.486581E+09 |
Maximum of Months | 0.135911E+10 | 0.149402E+09 | 0.122632E+10 | 0.145875E+10 | 0.430799E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.361146E+09 | 0.00 | 0.361146E+09 | 576310.52 | 0.430799E+10 |
February | 0.501063E+09 | 0.00 | 0.501063E+09 | 17070334.85 | 0.312298E+10 |
March | 0.682521E+09 | 0.00 | 0.682521E+09 | 51938609.13 | 0.265920E+10 |
April | 0.865881E+09 | 6758031.42 | 0.859123E+09 | 0.325003E+09 | 0.146054E+10 |
May | 0.125842E+10 | 67763567.35 | 0.119066E+10 | 0.106075E+10 | 0.728198E+09 |
June | 0.135911E+10 | 0.149402E+09 | 0.120971E+10 | 0.143482E+10 | 0.486581E+09 |
July | 0.134144E+10 | 0.115120E+09 | 0.122632E+10 | 0.145875E+10 | 0.494381E+09 |
August | 0.101887E+10 | 17496906.56 | 0.100137E+10 | 0.971744E+09 | 0.605614E+09 |
September | 0.768361E+09 | 188348.41 | 0.768172E+09 | 0.484561E+09 | 0.994194E+09 |
October | 0.551294E+09 | 0.00 | 0.551294E+09 | 0.115829E+09 | 0.166309E+10 |
November | 0.353251E+09 | 0.00 | 0.353251E+09 | 15539968.23 | 0.251950E+10 |
December | 0.305991E+09 | 0.00 | 0.305991E+09 | 0.00 | 0.414542E+10 |
Annual Sum or Average | 0.936735E+10 | 0.356729E+09 | 0.901062E+10 | 0.593657E+10 | 0.231877E+11 |
Minimum of Months | 0.305991E+09 | 0.00 | 0.305991E+09 | 0.00 | 0.486581E+09 |
Maximum of Months | 0.135911E+10 | 0.149402E+09 | 0.122632E+10 | 0.145875E+10 | 0.430799E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152335E+10 | 0.635895E+09 | 0.887458E+09 | 0.358567E+09 | 0.747861E+10 |
February | 0.216215E+10 | 0.922278E+09 | 0.123988E+10 | 0.970637E+09 | 0.533405E+10 |
March | 0.326172E+10 | 0.163613E+10 | 0.162559E+10 | 0.208831E+10 | 0.462218E+10 |
April | 0.437583E+10 | 0.236024E+10 | 0.201560E+10 | 0.377972E+10 | 0.264712E+10 |
May | 0.489380E+10 | 0.215137E+10 | 0.274243E+10 | 0.500354E+10 | 0.147622E+10 |
June | 0.536141E+10 | 0.256466E+10 | 0.279675E+10 | 0.609316E+10 | 0.103381E+10 |
July | 0.542728E+10 | 0.254831E+10 | 0.287897E+10 | 0.633009E+10 | 0.102687E+10 |
August | 0.418444E+10 | 0.182889E+10 | 0.235555E+10 | 0.460597E+10 | 0.123809E+10 |
September | 0.324294E+10 | 0.145152E+10 | 0.179142E+10 | 0.302094E+10 | 0.188646E+10 |
October | 0.202911E+10 | 0.769436E+09 | 0.125968E+10 | 0.125542E+10 | 0.304394E+10 |
November | 0.125008E+10 | 0.417930E+09 | 0.832149E+09 | 0.442558E+09 | 0.448238E+10 |
December | 0.117871E+10 | 0.435670E+09 | 0.743040E+09 | 0.217956E+09 | 0.732328E+10 |
Annual Sum or Average | 0.388908E+11 | 0.177223E+11 | 0.211685E+11 | 0.341669E+11 | 0.415930E+11 |
Minimum of Months | 0.117871E+10 | 0.417930E+09 | 0.743040E+09 | 0.217956E+09 | 0.102687E+10 |
Maximum of Months | 0.542728E+10 | 0.256466E+10 | 0.287897E+10 | 0.633009E+10 | 0.747861E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60232013.44 | 25142719.21 | 35089294.23 | 14177406.77 | 0.295697E+09 |
February | 85489631.95 | 36466056.94 | 49023575.00 | 38378118.84 | 0.210903E+09 |
March | 0.128966E+09 | 64691099.16 | 64274534.64 | 82569758.55 | 0.182757E+09 |
April | 0.173017E+09 | 93321662.24 | 79694863.49 | 0.149447E+09 | 0.104665E+09 |
May | 0.193497E+09 | 85063269.28 | 0.108433E+09 | 0.197835E+09 | 58368336.54 |
June | 0.211985E+09 | 0.101404E+09 | 0.110581E+09 | 0.240918E+09 | 40875856.78 |
July | 0.214590E+09 | 0.100758E+09 | 0.113832E+09 | 0.250286E+09 | 40601358.52 |
August | 0.165449E+09 | 72312861.13 | 93136241.42 | 0.182116E+09 | 48952920.20 |
September | 0.128223E+09 | 57391917.18 | 70830991.66 | 0.119445E+09 | 74589057.22 |
October | 80229294.60 | 30422795.94 | 49806498.66 | 49638355.11 | 0.120355E+09 |
November | 49427023.34 | 16524587.73 | 32902435.61 | 17498349.52 | 0.177229E+09 |
December | 46605102.29 | 17225987.67 | 29379114.62 | 8617796.00 | 0.289556E+09 |
Annual Sum or Average | 0.153771E+10 | 0.700725E+09 | 0.836984E+09 | 0.135093E+10 | 0.164455E+10 |
Minimum of Months | 46605102.29 | 16524587.73 | 29379114.62 | 8617796.00 | 40601358.52 |
Maximum of Months | 0.214590E+09 | 0.101404E+09 | 0.113832E+09 | 0.250286E+09 | 0.295697E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248685E+10 | 0.173005E+10 | 0.756807E+09 | 0.176276E+10 | 0.333024E+10 |
February | 0.284422E+10 | 0.192108E+10 | 0.923136E+09 | 0.237620E+10 | 0.253952E+10 |
March | 0.277461E+10 | 0.175594E+10 | 0.101867E+10 | 0.241315E+10 | 0.233787E+10 |
April | 0.243263E+10 | 0.132036E+10 | 0.111227E+10 | 0.237367E+10 | 0.148670E+10 |
May | 0.211338E+10 | 0.722510E+09 | 0.139087E+10 | 0.230576E+10 | 0.843061E+09 |
June | 0.183512E+10 | 0.489137E+09 | 0.134598E+10 | 0.217728E+10 | 0.556357E+09 |
July | 0.207326E+10 | 0.656796E+09 | 0.141646E+10 | 0.254740E+10 | 0.567595E+09 |
August | 0.221412E+10 | 0.926147E+09 | 0.128797E+10 | 0.260295E+10 | 0.689966E+09 |
September | 0.229515E+10 | 0.122233E+10 | 0.107281E+10 | 0.243713E+10 | 0.105763E+10 |
October | 0.202522E+10 | 0.119113E+10 | 0.834090E+09 | 0.183259E+10 | 0.160707E+10 |
November | 0.174583E+10 | 0.109568E+10 | 0.650147E+09 | 0.135233E+10 | 0.216969E+10 |
December | 0.192015E+10 | 0.125906E+10 | 0.661086E+09 | 0.122376E+10 | 0.328422E+10 |
Annual Sum or Average | 0.267605E+11 | 0.142902E+11 | 0.124703E+11 | 0.254050E+11 | 0.204699E+11 |
Minimum of Months | 0.174583E+10 | 0.489137E+09 | 0.650147E+09 | 0.122376E+10 | 0.556357E+09 |
Maximum of Months | 0.284422E+10 | 0.192108E+10 | 0.141646E+10 | 0.260295E+10 | 0.333024E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248685E+10 | 0.173005E+10 | 0.756807E+09 | 0.176276E+10 | 0.333024E+10 |
February | 0.284422E+10 | 0.192108E+10 | 0.923136E+09 | 0.237620E+10 | 0.253952E+10 |
March | 0.277461E+10 | 0.175594E+10 | 0.101867E+10 | 0.241315E+10 | 0.233787E+10 |
April | 0.243263E+10 | 0.132036E+10 | 0.111227E+10 | 0.237367E+10 | 0.148670E+10 |
May | 0.211338E+10 | 0.722510E+09 | 0.139087E+10 | 0.230576E+10 | 0.843061E+09 |
June | 0.183512E+10 | 0.489137E+09 | 0.134598E+10 | 0.217728E+10 | 0.556357E+09 |
July | 0.207326E+10 | 0.656796E+09 | 0.141646E+10 | 0.254740E+10 | 0.567595E+09 |
August | 0.221412E+10 | 0.926147E+09 | 0.128797E+10 | 0.260295E+10 | 0.689966E+09 |
September | 0.229515E+10 | 0.122233E+10 | 0.107281E+10 | 0.243713E+10 | 0.105763E+10 |
October | 0.202522E+10 | 0.119113E+10 | 0.834090E+09 | 0.183259E+10 | 0.160707E+10 |
November | 0.174583E+10 | 0.109568E+10 | 0.650147E+09 | 0.135233E+10 | 0.216969E+10 |
December | 0.192015E+10 | 0.125906E+10 | 0.661086E+09 | 0.122376E+10 | 0.328422E+10 |
Annual Sum or Average | 0.267605E+11 | 0.142902E+11 | 0.124703E+11 | 0.254050E+11 | 0.204699E+11 |
Minimum of Months | 0.174583E+10 | 0.489137E+09 | 0.650147E+09 | 0.122376E+10 | 0.556357E+09 |
Maximum of Months | 0.284422E+10 | 0.192108E+10 | 0.141646E+10 | 0.260295E+10 | 0.333024E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248670E+10 | 0.172994E+10 | 0.756759E+09 | 0.176265E+10 | 0.333003E+10 |
February | 0.284404E+10 | 0.192096E+10 | 0.923078E+09 | 0.237605E+10 | 0.253936E+10 |
March | 0.277444E+10 | 0.175583E+10 | 0.101861E+10 | 0.241300E+10 | 0.233772E+10 |
April | 0.243247E+10 | 0.132027E+10 | 0.111220E+10 | 0.237352E+10 | 0.148660E+10 |
May | 0.211324E+10 | 0.722464E+09 | 0.139078E+10 | 0.230561E+10 | 0.843008E+09 |
June | 0.183500E+10 | 0.489106E+09 | 0.134590E+10 | 0.217714E+10 | 0.556322E+09 |
July | 0.207313E+10 | 0.656754E+09 | 0.141638E+10 | 0.254724E+10 | 0.567559E+09 |
August | 0.221398E+10 | 0.926088E+09 | 0.128789E+10 | 0.260278E+10 | 0.689922E+09 |
September | 0.229500E+10 | 0.122226E+10 | 0.107274E+10 | 0.243698E+10 | 0.105756E+10 |
October | 0.202509E+10 | 0.119106E+10 | 0.834037E+09 | 0.183248E+10 | 0.160697E+10 |
November | 0.174572E+10 | 0.109561E+10 | 0.650106E+09 | 0.135224E+10 | 0.216955E+10 |
December | 0.192003E+10 | 0.125898E+10 | 0.661044E+09 | 0.122368E+10 | 0.328401E+10 |
Annual Sum or Average | 0.267588E+11 | 0.142893E+11 | 0.124695E+11 | 0.254034E+11 | 0.204686E+11 |
Minimum of Months | 0.174572E+10 | 0.489106E+09 | 0.650106E+09 | 0.122368E+10 | 0.556322E+09 |
Maximum of Months | 0.284404E+10 | 0.192096E+10 | 0.141638E+10 | 0.260278E+10 | 0.333003E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.153966E+10 | 0.644718E+09 | 0.894940E+09 | 0.444260E+09 | 0.766587E+10 |
February | 0.226579E+10 | 0.103486E+10 | 0.123093E+10 | 0.121426E+10 | 0.556608E+10 |
March | 0.330107E+10 | 0.168913E+10 | 0.161193E+10 | 0.227379E+10 | 0.481103E+10 |
April | 0.408090E+10 | 0.206694E+10 | 0.201396E+10 | 0.355273E+10 | 0.283324E+10 |
May | 0.518125E+10 | 0.247148E+10 | 0.270977E+10 | 0.554099E+10 | 0.162588E+10 |
June | 0.483851E+10 | 0.209213E+10 | 0.274638E+10 | 0.556427E+10 | 0.109474E+10 |
July | 0.533776E+10 | 0.248151E+10 | 0.285626E+10 | 0.628750E+10 | 0.113943E+10 |
August | 0.439262E+10 | 0.199598E+10 | 0.239664E+10 | 0.495450E+10 | 0.132983E+10 |
September | 0.332226E+10 | 0.149264E+10 | 0.182962E+10 | 0.319744E+10 | 0.199291E+10 |
October | 0.216865E+10 | 0.870592E+09 | 0.129806E+10 | 0.150098E+10 | 0.315526E+10 |
November | 0.127464E+10 | 0.429762E+09 | 0.844883E+09 | 0.486075E+09 | 0.458568E+10 |
December | 0.117415E+10 | 0.410961E+09 | 0.763189E+09 | 0.224706E+09 | 0.747425E+10 |
Annual Sum or Average | 0.388773E+11 | 0.176807E+11 | 0.211966E+11 | 0.352415E+11 | 0.432742E+11 |
Minimum of Months | 0.117415E+10 | 0.410961E+09 | 0.763189E+09 | 0.224706E+09 | 0.109474E+10 |
Maximum of Months | 0.533776E+10 | 0.248151E+10 | 0.285626E+10 | 0.628750E+10 | 0.766587E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 60876727.05 | 25491585.59 | 35385141.46 | 17565631.47 | 0.303102E+09 |
February | 89587439.01 | 40917585.50 | 48669853.51 | 48010623.23 | 0.220078E+09 |
March | 0.130521E+09 | 66786871.96 | 63734382.66 | 89903434.20 | 0.190224E+09 |
April | 0.161355E+09 | 81724857.16 | 79630361.11 | 0.140472E+09 | 0.112024E+09 |
May | 0.204862E+09 | 97720159.94 | 0.107142E+09 | 0.219086E+09 | 64285646.74 |
June | 0.191310E+09 | 82721080.61 | 0.108589E+09 | 0.220006E+09 | 43284980.02 |
July | 0.211050E+09 | 98116553.85 | 0.112934E+09 | 0.248602E+09 | 45051929.88 |
August | 0.173680E+09 | 78919330.40 | 94761031.83 | 0.195896E+09 | 52580468.65 |
September | 0.131359E+09 | 59017748.65 | 72341445.96 | 0.126424E+09 | 78798013.81 |
October | 85746541.27 | 34422425.41 | 51324115.86 | 59347272.51 | 0.124756E+09 |
November | 50398290.36 | 16992388.74 | 33405901.62 | 19218976.52 | 0.181314E+09 |
December | 46424833.88 | 16249020.11 | 30175813.77 | 8884665.26 | 0.295525E+09 |
Annual Sum or Average | 0.153717E+10 | 0.699080E+09 | 0.838093E+09 | 0.139342E+10 | 0.171102E+10 |
Minimum of Months | 46424833.88 | 16249020.11 | 30175813.77 | 8884665.26 | 43284980.02 |
Maximum of Months | 0.211050E+09 | 98116553.85 | 0.112934E+09 | 0.248602E+09 | 0.303102E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108343E+10 | 0.00 | 0.108343E+10 | 1470420.37 | 0.132169E+11 |
February | 0.150317E+10 | 0.00 | 0.150317E+10 | 41575413.14 | 0.968325E+10 |
March | 0.204754E+10 | 0.00 | 0.204754E+10 | 0.116474E+09 | 0.847331E+10 |
April | 0.259761E+10 | 20273950.62 | 0.257734E+10 | 0.792914E+09 | 0.483489E+10 |
May | 0.377523E+10 | 0.203289E+09 | 0.357194E+10 | 0.280861E+10 | 0.251044E+10 |
June | 0.407730E+10 | 0.448202E+09 | 0.362910E+10 | 0.397394E+10 | 0.167527E+10 |
July | 0.402428E+10 | 0.345358E+09 | 0.367892E+10 | 0.417814E+10 | 0.161296E+10 |
August | 0.305657E+10 | 52490347.80 | 0.300408E+10 | 0.280770E+10 | 0.189709E+10 |
September | 0.230506E+10 | 565041.23 | 0.230449E+10 | 0.138936E+10 | 0.302463E+10 |
October | 0.165387E+10 | 0.00 | 0.165387E+10 | 0.328389E+09 | 0.497866E+10 |
November | 0.105974E+10 | 0.00 | 0.105974E+10 | 43771419.34 | 0.757910E+10 |
December | 0.917965E+09 | 0.00 | 0.917965E+09 | 0.00 | 0.126371E+11 |
Annual Sum or Average | 0.281018E+11 | 0.107018E+10 | 0.270316E+11 | 0.164823E+11 | 0.721237E+11 |
Minimum of Months | 0.917965E+09 | 0.00 | 0.917965E+09 | 0.00 | 0.161296E+10 |
Maximum of Months | 0.407730E+10 | 0.448202E+09 | 0.367892E+10 | 0.417814E+10 | 0.132169E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158353E+10 | 0.661011E+09 | 0.922518E+09 | 0.354831E+09 | 0.792606E+10 |
February | 0.224756E+10 | 0.958706E+09 | 0.128886E+10 | 0.964484E+09 | 0.570040E+10 |
March | 0.339057E+10 | 0.170075E+10 | 0.168982E+10 | 0.206443E+10 | 0.506407E+10 |
April | 0.454869E+10 | 0.245346E+10 | 0.209523E+10 | 0.374104E+10 | 0.295520E+10 |
May | 0.508712E+10 | 0.223634E+10 | 0.285078E+10 | 0.498368E+10 | 0.166917E+10 |
June | 0.557320E+10 | 0.266596E+10 | 0.290724E+10 | 0.618526E+10 | 0.114694E+10 |
July | 0.564167E+10 | 0.264896E+10 | 0.299271E+10 | 0.649814E+10 | 0.108724E+10 |
August | 0.434974E+10 | 0.190113E+10 | 0.244861E+10 | 0.474027E+10 | 0.126007E+10 |
September | 0.337104E+10 | 0.150885E+10 | 0.186219E+10 | 0.310014E+10 | 0.191341E+10 |
October | 0.210927E+10 | 0.799826E+09 | 0.130944E+10 | 0.127448E+10 | 0.311706E+10 |
November | 0.129946E+10 | 0.434437E+09 | 0.865024E+09 | 0.445664E+09 | 0.464672E+10 |
December | 0.122527E+10 | 0.452877E+09 | 0.772393E+09 | 0.218228E+09 | 0.770841E+10 |
Annual Sum or Average | 0.404271E+11 | 0.184223E+11 | 0.220048E+11 | 0.345706E+11 | 0.441947E+11 |
Minimum of Months | 0.122527E+10 | 0.434437E+09 | 0.772393E+09 | 0.218228E+09 | 0.108724E+10 |
Maximum of Months | 0.564167E+10 | 0.266596E+10 | 0.299271E+10 | 0.649814E+10 | 0.792606E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746036E+10 | 0.519000E+10 | 0.227036E+10 | 0.505946E+10 | 0.103980E+11 |
February | 0.853242E+10 | 0.576308E+10 | 0.276934E+10 | 0.685733E+10 | 0.787611E+10 |
March | 0.832362E+10 | 0.526768E+10 | 0.305594E+10 | 0.693368E+10 | 0.737763E+10 |
April | 0.729769E+10 | 0.396096E+10 | 0.333673E+10 | 0.682825E+10 | 0.476501E+10 |
May | 0.633997E+10 | 0.216747E+10 | 0.417250E+10 | 0.660219E+10 | 0.279207E+10 |
June | 0.550523E+10 | 0.146737E+10 | 0.403785E+10 | 0.627031E+10 | 0.187367E+10 |
July | 0.621963E+10 | 0.197033E+10 | 0.424929E+10 | 0.748871E+10 | 0.178470E+10 |
August | 0.664220E+10 | 0.277836E+10 | 0.386383E+10 | 0.770677E+10 | 0.205379E+10 |
September | 0.688526E+10 | 0.366690E+10 | 0.321836E+10 | 0.722057E+10 | 0.307991E+10 |
October | 0.607550E+10 | 0.357330E+10 | 0.250221E+10 | 0.542933E+10 | 0.467993E+10 |
November | 0.523735E+10 | 0.328696E+10 | 0.195039E+10 | 0.396072E+10 | 0.648631E+10 |
December | 0.576029E+10 | 0.377709E+10 | 0.198321E+10 | 0.353614E+10 | 0.101867E+11 |
Annual Sum or Average | 0.802795E+11 | 0.428695E+11 | 0.374100E+11 | 0.738935E+11 | 0.633538E+11 |
Minimum of Months | 0.523735E+10 | 0.146737E+10 | 0.195039E+10 | 0.353614E+10 | 0.178470E+10 |
Maximum of Months | 0.853242E+10 | 0.576308E+10 | 0.424929E+10 | 0.770677E+10 | 0.103980E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160048E+10 | 0.670185E+09 | 0.930298E+09 | 0.437717E+09 | 0.814803E+10 |
February | 0.235530E+10 | 0.107574E+10 | 0.127956E+10 | 0.120752E+10 | 0.595491E+10 |
March | 0.343148E+10 | 0.175586E+10 | 0.167562E+10 | 0.226420E+10 | 0.525529E+10 |
April | 0.424212E+10 | 0.214858E+10 | 0.209354E+10 | 0.353489E+10 | 0.315555E+10 |
May | 0.538594E+10 | 0.256911E+10 | 0.281683E+10 | 0.558998E+10 | 0.182100E+10 |
June | 0.502966E+10 | 0.217477E+10 | 0.285489E+10 | 0.564537E+10 | 0.122856E+10 |
July | 0.554863E+10 | 0.257953E+10 | 0.296911E+10 | 0.647222E+10 | 0.120002E+10 |
August | 0.456616E+10 | 0.207482E+10 | 0.249133E+10 | 0.512722E+10 | 0.134638E+10 |
September | 0.345351E+10 | 0.155160E+10 | 0.190191E+10 | 0.330723E+10 | 0.202165E+10 |
October | 0.225432E+10 | 0.904981E+09 | 0.134934E+10 | 0.154421E+10 | 0.322015E+10 |
November | 0.132500E+10 | 0.446737E+09 | 0.878262E+09 | 0.489433E+09 | 0.476210E+10 |
December | 0.122053E+10 | 0.427194E+09 | 0.793341E+09 | 0.222435E+09 | 0.789817E+10 |
Annual Sum or Average | 0.404131E+11 | 0.183791E+11 | 0.220340E+11 | 0.358424E+11 | 0.460118E+11 |
Minimum of Months | 0.122053E+10 | 0.427194E+09 | 0.793341E+09 | 0.222435E+09 | 0.120002E+10 |
Maximum of Months | 0.554863E+10 | 0.257953E+10 | 0.296911E+10 | 0.647222E+10 | 0.814803E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.94 | 4861.29 | 404.51 | 0.00 | 404.51 | 0.00 | 0.00 |
February | 19.19 | 3911.44 | 621.35 | 0.00 | 621.35 | 0.00 | 0.00 |
March | 48.14 | 3057.74 | 764.46 | 0.00 | 764.46 | 0.00 | 0.00 |
April | 321.97 | 1749.05 | 1002.17 | 7.82 | 994.34 | 0.00 | 0.00 |
May | 1080.82 | 869.85 | 1409.51 | 75.90 | 1333.61 | 0.00 | 0.00 |
June | 1569.36 | 599.38 | 1573.03 | 172.92 | 1400.12 | 0.00 | 0.00 |
July | 1591.50 | 559.86 | 1502.49 | 128.94 | 1373.55 | 0.00 | 0.00 |
August | 1084.14 | 641.12 | 1141.19 | 19.60 | 1121.59 | 0.00 | 0.00 |
September | 572.37 | 1064.72 | 889.30 | 0.22 | 889.08 | 0.00 | 0.00 |
October | 140.56 | 1708.07 | 617.48 | 0.00 | 617.48 | 0.00 | 0.00 |
November | 18.45 | 2783.31 | 408.85 | 0.00 | 408.85 | 0.00 | 0.00 |
December | 0.00 | 4630.01 | 342.73 | 0.00 | 342.73 | 0.00 | 0.00 |
Annual Sum or Average | 540.63 | 2196.11 | 891.10 | 33.94 | 857.17 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 559.86 | 342.73 | 0.00 | 342.73 | 0.00 | 0.00 |
Maximum of Months | 1591.50 | 4861.29 | 1573.03 | 172.92 | 1400.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 134.45 | 2915.58 | 591.22 | 246.79 | 344.43 | 0.00 | 0.00 |
February | 406.06 | 2300.38 | 929.05 | 396.29 | 532.76 | 0.00 | 0.00 |
March | 786.81 | 1822.22 | 1265.89 | 634.99 | 630.91 | 0.00 | 0.00 |
April | 1468.45 | 1069.99 | 1754.90 | 946.55 | 808.35 | 0.00 | 0.00 |
May | 1881.39 | 586.76 | 1899.31 | 834.96 | 1064.36 | 0.00 | 0.00 |
June | 2399.57 | 415.90 | 2150.15 | 1028.53 | 1121.62 | 0.00 | 0.00 |
July | 2436.18 | 382.53 | 2106.36 | 989.01 | 1117.35 | 0.00 | 0.00 |
August | 1786.95 | 433.99 | 1624.01 | 709.80 | 914.21 | 0.00 | 0.00 |
September | 1224.86 | 680.07 | 1300.56 | 582.12 | 718.44 | 0.00 | 0.00 |
October | 500.34 | 1068.99 | 787.51 | 298.62 | 488.89 | 0.00 | 0.00 |
November | 179.83 | 1702.40 | 501.34 | 167.61 | 333.73 | 0.00 | 0.00 |
December | 83.52 | 2825.10 | 457.46 | 169.09 | 288.38 | 0.00 | 0.00 |
Annual Sum or Average | 1110.82 | 1346.72 | 1281.94 | 584.17 | 697.77 | 0.00 | 0.00 |
Minimum of Months | 83.52 | 382.53 | 457.46 | 167.61 | 288.38 | 0.00 | 0.00 |
Maximum of Months | 2436.18 | 2915.58 | 2150.15 | 1028.53 | 1121.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1903.25 | 3806.17 | 2785.38 | 1937.72 | 847.66 | 0.00 | 0.00 |
February | 2856.61 | 3155.58 | 3526.96 | 2382.23 | 1144.73 | 0.00 | 0.00 |
March | 2611.36 | 2641.60 | 3107.68 | 1966.73 | 1140.96 | 0.00 | 0.00 |
April | 2658.08 | 1720.74 | 2815.47 | 1528.15 | 1287.32 | 0.00 | 0.00 |
May | 2486.36 | 969.00 | 2367.07 | 809.24 | 1557.83 | 0.00 | 0.00 |
June | 2439.39 | 667.20 | 2123.93 | 566.12 | 1557.81 | 0.00 | 0.00 |
July | 2812.91 | 616.18 | 2322.14 | 735.64 | 1586.50 | 0.00 | 0.00 |
August | 2899.82 | 696.71 | 2479.91 | 1037.32 | 1442.59 | 0.00 | 0.00 |
September | 2817.67 | 1088.98 | 2656.35 | 1414.70 | 1241.65 | 0.00 | 0.00 |
October | 2059.77 | 1607.28 | 2268.33 | 1334.12 | 934.22 | 0.00 | 0.00 |
November | 1553.02 | 2366.72 | 2020.58 | 1268.12 | 752.47 | 0.00 | 0.00 |
December | 1337.49 | 3713.74 | 2150.65 | 1410.20 | 740.44 | 0.00 | 0.00 |
Annual Sum or Average | 2365.67 | 1915.72 | 2545.65 | 1359.38 | 1186.26 | 0.00 | 0.00 |
Minimum of Months | 1337.49 | 616.18 | 2020.58 | 566.12 | 740.44 | 0.00 | 0.00 |
Maximum of Months | 2899.82 | 3806.17 | 3526.96 | 2382.23 | 1586.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 164.61 | 2995.67 | 597.55 | 250.22 | 347.33 | 0.00 | 0.00 |
February | 501.26 | 2400.78 | 973.59 | 444.67 | 528.92 | 0.00 | 0.00 |
March | 849.54 | 1890.79 | 1281.17 | 655.56 | 625.61 | 0.00 | 0.00 |
April | 1371.74 | 1142.91 | 1636.62 | 828.93 | 807.69 | 0.00 | 0.00 |
May | 2094.26 | 636.79 | 2010.88 | 959.19 | 1051.69 | 0.00 | 0.00 |
June | 2184.23 | 442.80 | 1940.45 | 839.03 | 1101.42 | 0.00 | 0.00 |
July | 2421.80 | 419.60 | 2071.62 | 963.09 | 1108.54 | 0.00 | 0.00 |
August | 1924.07 | 463.80 | 1704.81 | 774.65 | 930.16 | 0.00 | 0.00 |
September | 1290.86 | 719.56 | 1332.37 | 598.61 | 733.76 | 0.00 | 0.00 |
October | 589.26 | 1107.85 | 841.67 | 337.88 | 503.79 | 0.00 | 0.00 |
November | 194.37 | 1748.35 | 511.19 | 172.35 | 338.84 | 0.00 | 0.00 |
December | 83.92 | 2893.13 | 455.70 | 159.50 | 296.20 | 0.00 | 0.00 |
Annual Sum or Average | 1143.08 | 1401.28 | 1281.49 | 582.80 | 698.69 | 0.00 | 0.00 |
Minimum of Months | 83.92 | 419.60 | 455.70 | 159.50 | 296.20 | 0.00 | 0.00 |
Maximum of Months | 2421.80 | 2995.67 | 2071.62 | 963.09 | 1108.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.65 | 4825.16 | 404.50 | 0.00 | 404.50 | 0.00 | 0.00 |
February | 21.17 | 3872.66 | 621.35 | 0.00 | 621.35 | 0.00 | 0.00 |
March | 58.17 | 2978.43 | 764.46 | 0.00 | 764.46 | 0.00 | 0.00 |
April | 376.16 | 1690.40 | 1002.16 | 7.82 | 994.34 | 0.00 | 0.00 |
May | 1188.09 | 815.62 | 1409.50 | 75.90 | 1333.60 | 0.00 | 0.00 |
June | 1660.64 | 563.16 | 1573.02 | 172.92 | 1400.11 | 0.00 | 0.00 |
July | 1633.88 | 553.73 | 1502.49 | 128.94 | 1373.54 | 0.00 | 0.00 |
August | 1088.41 | 678.32 | 1141.19 | 19.60 | 1121.59 | 0.00 | 0.00 |
September | 560.83 | 1150.66 | 889.29 | 0.22 | 889.07 | 0.00 | 0.00 |
October | 129.74 | 1862.74 | 617.48 | 0.00 | 617.48 | 0.00 | 0.00 |
November | 17.99 | 2916.03 | 408.85 | 0.00 | 408.85 | 0.00 | 0.00 |
December | 0.00 | 4643.07 | 342.73 | 0.00 | 342.73 | 0.00 | 0.00 |
Annual Sum or Average | 564.73 | 2205.78 | 891.10 | 33.93 | 857.16 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 553.73 | 342.73 | 0.00 | 342.73 | 0.00 | 0.00 |
Maximum of Months | 1660.64 | 4825.16 | 1573.02 | 172.92 | 1400.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 139.17 | 2902.59 | 591.24 | 246.80 | 344.44 | 0.00 | 0.00 |
February | 417.09 | 2292.06 | 929.09 | 396.31 | 532.78 | 0.00 | 0.00 |
March | 810.51 | 1793.96 | 1265.94 | 635.01 | 630.92 | 0.00 | 0.00 |
April | 1515.88 | 1061.64 | 1754.96 | 946.59 | 808.37 | 0.00 | 0.00 |
May | 1941.97 | 572.95 | 1899.38 | 834.99 | 1064.39 | 0.00 | 0.00 |
June | 2443.70 | 414.62 | 2150.23 | 1028.57 | 1121.66 | 0.00 | 0.00 |
July | 2456.83 | 398.55 | 2106.43 | 989.05 | 1117.38 | 0.00 | 0.00 |
August | 1787.67 | 480.53 | 1624.06 | 709.83 | 914.23 | 0.00 | 0.00 |
September | 1211.57 | 756.58 | 1300.60 | 582.14 | 718.46 | 0.00 | 0.00 |
October | 487.25 | 1181.41 | 787.54 | 298.63 | 488.91 | 0.00 | 0.00 |
November | 177.49 | 1797.69 | 501.35 | 167.61 | 333.74 | 0.00 | 0.00 |
December | 84.59 | 2842.31 | 457.48 | 169.09 | 288.39 | 0.00 | 0.00 |
Annual Sum or Average | 1126.26 | 1371.05 | 1281.98 | 584.19 | 697.79 | 0.00 | 0.00 |
Minimum of Months | 84.59 | 398.55 | 457.48 | 167.61 | 288.39 | 0.00 | 0.00 |
Maximum of Months | 2456.83 | 2902.59 | 2150.23 | 1028.57 | 1121.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1974.37 | 3730.03 | 2785.40 | 1937.74 | 847.66 | 0.00 | 0.00 |
February | 2946.61 | 3149.14 | 3526.98 | 2382.24 | 1144.74 | 0.00 | 0.00 |
March | 2702.85 | 2618.52 | 3107.70 | 1966.74 | 1140.96 | 0.00 | 0.00 |
April | 2747.24 | 1720.68 | 2815.48 | 1528.16 | 1287.32 | 0.00 | 0.00 |
May | 2582.56 | 944.27 | 2367.08 | 809.25 | 1557.84 | 0.00 | 0.00 |
June | 2519.94 | 643.92 | 2123.94 | 566.12 | 1557.82 | 0.00 | 0.00 |
July | 2853.21 | 635.73 | 2322.15 | 735.64 | 1586.51 | 0.00 | 0.00 |
August | 2915.43 | 772.79 | 2479.92 | 1037.33 | 1442.59 | 0.00 | 0.00 |
September | 2820.69 | 1224.08 | 2656.36 | 1414.71 | 1241.66 | 0.00 | 0.00 |
October | 2052.59 | 1799.99 | 2268.35 | 1334.12 | 934.22 | 0.00 | 0.00 |
November | 1565.16 | 2511.16 | 2020.59 | 1268.13 | 752.47 | 0.00 | 0.00 |
December | 1370.67 | 3678.48 | 2150.66 | 1410.21 | 740.45 | 0.00 | 0.00 |
Annual Sum or Average | 2416.71 | 1947.25 | 2545.66 | 1359.39 | 1186.27 | 0.00 | 0.00 |
Minimum of Months | 1370.67 | 635.73 | 2020.59 | 566.12 | 740.45 | 0.00 | 0.00 |
Maximum of Months | 2946.61 | 3730.03 | 3526.98 | 2382.24 | 1586.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.43 | 2975.27 | 597.57 | 250.23 | 347.34 | 0.00 | 0.00 |
February | 521.77 | 2391.76 | 973.62 | 444.68 | 528.94 | 0.00 | 0.00 |
March | 882.50 | 1867.25 | 1281.21 | 655.59 | 625.62 | 0.00 | 0.00 |
April | 1424.85 | 1136.29 | 1636.67 | 828.96 | 807.71 | 0.00 | 0.00 |
May | 2150.57 | 631.03 | 2010.94 | 959.23 | 1051.71 | 0.00 | 0.00 |
June | 2231.59 | 439.05 | 1940.52 | 839.06 | 1101.45 | 0.00 | 0.00 |
July | 2440.30 | 442.23 | 2071.69 | 963.12 | 1108.57 | 0.00 | 0.00 |
August | 1922.94 | 516.13 | 1704.86 | 774.68 | 930.18 | 0.00 | 0.00 |
September | 1282.36 | 799.27 | 1332.42 | 598.63 | 733.78 | 0.00 | 0.00 |
October | 582.56 | 1224.62 | 841.70 | 337.89 | 503.80 | 0.00 | 0.00 |
November | 194.94 | 1839.12 | 511.20 | 172.36 | 338.85 | 0.00 | 0.00 |
December | 87.21 | 2900.90 | 455.71 | 159.50 | 296.21 | 0.00 | 0.00 |
Annual Sum or Average | 1161.69 | 1426.47 | 1281.53 | 582.82 | 698.71 | 0.00 | 0.00 |
Minimum of Months | 87.21 | 439.05 | 455.71 | 159.50 | 296.21 | 0.00 | 0.00 |
Maximum of Months | 2440.30 | 2975.27 | 2071.69 | 963.12 | 1108.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.55 | 4934.64 | 404.51 | 0.00 | 404.51 | 0.00 | 0.00 |
February | 17.19 | 4002.66 | 621.35 | 0.00 | 621.35 | 0.00 | 0.00 |
March | 43.49 | 3163.57 | 764.46 | 0.00 | 764.46 | 0.00 | 0.00 |
April | 305.91 | 1865.31 | 1002.17 | 7.82 | 994.34 | 0.00 | 0.00 |
May | 1048.61 | 937.29 | 1409.51 | 75.90 | 1333.61 | 0.00 | 0.00 |
June | 1533.16 | 646.32 | 1573.03 | 172.92 | 1400.12 | 0.00 | 0.00 |
July | 1559.94 | 602.21 | 1502.49 | 128.94 | 1373.55 | 0.00 | 0.00 |
August | 1048.28 | 708.29 | 1141.19 | 19.60 | 1121.59 | 0.00 | 0.00 |
September | 536.02 | 1166.91 | 889.30 | 0.22 | 889.08 | 0.00 | 0.00 |
October | 122.61 | 1858.82 | 617.48 | 0.00 | 617.48 | 0.00 | 0.00 |
November | 16.89 | 2924.04 | 408.85 | 0.00 | 408.85 | 0.00 | 0.00 |
December | 0.00 | 4718.16 | 342.73 | 0.00 | 342.73 | 0.00 | 0.00 |
Annual Sum or Average | 522.65 | 2287.03 | 891.10 | 33.94 | 857.17 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 602.21 | 342.73 | 0.00 | 342.73 | 0.00 | 0.00 |
Maximum of Months | 1559.94 | 4934.64 | 1573.03 | 172.92 | 1400.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 132.48 | 2959.25 | 591.22 | 246.79 | 344.43 | 0.00 | 0.00 |
February | 398.68 | 2356.32 | 929.05 | 396.29 | 532.76 | 0.00 | 0.00 |
March | 770.77 | 1890.71 | 1265.89 | 634.99 | 630.91 | 0.00 | 0.00 |
April | 1443.30 | 1140.12 | 1754.90 | 946.55 | 808.35 | 0.00 | 0.00 |
May | 1860.69 | 623.20 | 1899.31 | 834.96 | 1064.36 | 0.00 | 0.00 |
June | 2386.29 | 442.49 | 2150.15 | 1028.53 | 1121.62 | 0.00 | 0.00 |
July | 2426.13 | 405.93 | 2106.36 | 989.01 | 1117.35 | 0.00 | 0.00 |
August | 1769.81 | 470.45 | 1624.01 | 709.80 | 914.21 | 0.00 | 0.00 |
September | 1196.04 | 738.20 | 1300.56 | 582.12 | 718.44 | 0.00 | 0.00 |
October | 475.84 | 1163.78 | 787.51 | 298.62 | 488.89 | 0.00 | 0.00 |
November | 171.94 | 1792.72 | 501.34 | 167.61 | 333.73 | 0.00 | 0.00 |
December | 81.48 | 2877.99 | 457.46 | 169.09 | 288.38 | 0.00 | 0.00 |
Annual Sum or Average | 1096.23 | 1401.41 | 1281.94 | 584.17 | 697.77 | 0.00 | 0.00 |
Minimum of Months | 81.48 | 405.93 | 457.46 | 167.61 | 288.38 | 0.00 | 0.00 |
Maximum of Months | 2426.13 | 2959.25 | 2150.15 | 1028.53 | 1121.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1888.99 | 3882.16 | 2785.38 | 1937.72 | 847.66 | 0.00 | 0.00 |
February | 2834.55 | 3255.67 | 3526.96 | 2382.23 | 1144.73 | 0.00 | 0.00 |
March | 2588.74 | 2754.49 | 3107.68 | 1966.73 | 1140.96 | 0.00 | 0.00 |
April | 2634.36 | 1838.35 | 2815.47 | 1528.15 | 1287.32 | 0.00 | 0.00 |
May | 2464.97 | 1042.44 | 2367.07 | 809.24 | 1557.83 | 0.00 | 0.00 |
June | 2419.10 | 722.87 | 2123.93 | 566.12 | 1557.81 | 0.00 | 0.00 |
July | 2795.96 | 666.33 | 2322.14 | 735.64 | 1586.50 | 0.00 | 0.00 |
August | 2877.38 | 766.80 | 2479.91 | 1037.32 | 1442.59 | 0.00 | 0.00 |
September | 2785.71 | 1188.24 | 2656.35 | 1414.70 | 1241.65 | 0.00 | 0.00 |
October | 2027.08 | 1747.29 | 2268.33 | 1334.12 | 934.22 | 0.00 | 0.00 |
November | 1528.06 | 2502.43 | 2020.58 | 1268.12 | 752.47 | 0.00 | 0.00 |
December | 1320.24 | 3803.28 | 2150.65 | 1410.20 | 740.44 | 0.00 | 0.00 |
Annual Sum or Average | 2343.15 | 2008.94 | 2545.65 | 1359.38 | 1186.26 | 0.00 | 0.00 |
Minimum of Months | 1320.24 | 666.33 | 2020.58 | 566.12 | 740.44 | 0.00 | 0.00 |
Maximum of Months | 2877.38 | 3882.16 | 3526.96 | 2382.23 | 1586.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.42 | 3042.13 | 597.55 | 250.22 | 347.33 | 0.00 | 0.00 |
February | 499.14 | 2461.52 | 973.59 | 444.67 | 528.92 | 0.00 | 0.00 |
March | 845.35 | 1962.10 | 1281.17 | 655.56 | 625.61 | 0.00 | 0.00 |
April | 1363.77 | 1217.42 | 1636.62 | 828.93 | 807.69 | 0.00 | 0.00 |
May | 2087.06 | 679.88 | 2010.88 | 959.19 | 1051.69 | 0.00 | 0.00 |
June | 2178.00 | 473.98 | 1940.45 | 839.03 | 1101.42 | 0.00 | 0.00 |
July | 2416.45 | 448.04 | 2071.62 | 963.09 | 1108.54 | 0.00 | 0.00 |
August | 1914.28 | 502.68 | 1704.81 | 774.65 | 930.16 | 0.00 | 0.00 |
September | 1275.94 | 779.96 | 1332.37 | 598.61 | 733.76 | 0.00 | 0.00 |
October | 576.54 | 1202.27 | 841.67 | 337.88 | 503.79 | 0.00 | 0.00 |
November | 188.82 | 1837.23 | 511.19 | 172.35 | 338.84 | 0.00 | 0.00 |
December | 83.05 | 2948.84 | 455.70 | 159.50 | 296.20 | 0.00 | 0.00 |
Annual Sum or Average | 1136.56 | 1459.03 | 1281.49 | 582.80 | 698.69 | 0.00 | 0.00 |
Minimum of Months | 83.05 | 448.04 | 455.70 | 159.50 | 296.20 | 0.00 | 0.00 |
Maximum of Months | 2416.45 | 3042.13 | 2071.62 | 963.09 | 1108.54 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2507156.34 | 0.130205E+11 | 0.108343E+10 | 0.00 | 0.108343E+10 | 0.00 | 0.00 |
February | 46415590.65 | 0.946257E+10 | 0.150317E+10 | 0.00 | 0.150317E+10 | 0.00 | 0.00 |
March | 0.128938E+09 | 0.818984E+10 | 0.204754E+10 | 0.00 | 0.204754E+10 | 0.00 | 0.00 |
April | 0.834545E+09 | 0.453355E+10 | 0.259761E+10 | 20273950.62 | 0.257734E+10 | 0.00 | 0.00 |
May | 0.289488E+10 | 0.232979E+10 | 0.377523E+10 | 0.203289E+09 | 0.357194E+10 | 0.00 | 0.00 |
June | 0.406778E+10 | 0.155360E+10 | 0.407730E+10 | 0.448202E+09 | 0.362910E+10 | 0.00 | 0.00 |
July | 0.426266E+10 | 0.149952E+10 | 0.402428E+10 | 0.345358E+09 | 0.367892E+10 | 0.00 | 0.00 |
August | 0.290376E+10 | 0.171716E+10 | 0.305657E+10 | 52490347.80 | 0.300408E+10 | 0.00 | 0.00 |
September | 0.148360E+10 | 0.275975E+10 | 0.230506E+10 | 565041.23 | 0.230449E+10 | 0.00 | 0.00 |
October | 0.376488E+09 | 0.457490E+10 | 0.165387E+10 | 0.00 | 0.165387E+10 | 0.00 | 0.00 |
November | 47813300.53 | 0.721433E+10 | 0.105974E+10 | 0.00 | 0.105974E+10 | 0.00 | 0.00 |
December | 0.00 | 0.124010E+11 | 0.917965E+09 | 0.00 | 0.917965E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170494E+11 | 0.692565E+11 | 0.281018E+11 | 0.107018E+10 | 0.270316E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.149952E+10 | 0.917965E+09 | 0.00 | 0.917965E+09 | 0.00 | 0.00 |
Maximum of Months | 0.426266E+10 | 0.130205E+11 | 0.407730E+10 | 0.448202E+09 | 0.367892E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.360108E+09 | 0.780909E+10 | 0.158353E+10 | 0.661011E+09 | 0.922518E+09 | 0.00 | 0.00 |
February | 0.982331E+09 | 0.556509E+10 | 0.224756E+10 | 0.958706E+09 | 0.128886E+10 | 0.00 | 0.00 |
March | 0.210739E+10 | 0.488063E+10 | 0.339057E+10 | 0.170075E+10 | 0.168982E+10 | 0.00 | 0.00 |
April | 0.380621E+10 | 0.277341E+10 | 0.454869E+10 | 0.245346E+10 | 0.209523E+10 | 0.00 | 0.00 |
May | 0.503911E+10 | 0.157157E+10 | 0.508712E+10 | 0.223634E+10 | 0.285078E+10 | 0.00 | 0.00 |
June | 0.621970E+10 | 0.107801E+10 | 0.557320E+10 | 0.266596E+10 | 0.290724E+10 | 0.00 | 0.00 |
July | 0.652508E+10 | 0.102457E+10 | 0.564167E+10 | 0.264896E+10 | 0.299271E+10 | 0.00 | 0.00 |
August | 0.478617E+10 | 0.116239E+10 | 0.434974E+10 | 0.190113E+10 | 0.244861E+10 | 0.00 | 0.00 |
September | 0.317483E+10 | 0.176273E+10 | 0.337104E+10 | 0.150885E+10 | 0.186219E+10 | 0.00 | 0.00 |
October | 0.134010E+10 | 0.286319E+10 | 0.210927E+10 | 0.799826E+09 | 0.130944E+10 | 0.00 | 0.00 |
November | 0.466124E+09 | 0.441263E+10 | 0.129946E+10 | 0.434437E+09 | 0.865024E+09 | 0.00 | 0.00 |
December | 0.223707E+09 | 0.756676E+10 | 0.122527E+10 | 0.452877E+09 | 0.772393E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.350309E+11 | 0.424701E+11 | 0.404271E+11 | 0.184223E+11 | 0.220048E+11 | 0.00 | 0.00 |
Minimum of Months | 0.223707E+09 | 0.102457E+10 | 0.122527E+10 | 0.434437E+09 | 0.772393E+09 | 0.00 | 0.00 |
Maximum of Months | 0.652508E+10 | 0.780909E+10 | 0.564167E+10 | 0.266596E+10 | 0.299271E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.509765E+10 | 0.101944E+11 | 0.746036E+10 | 0.519000E+10 | 0.227036E+10 | 0.00 | 0.00 |
February | 0.691072E+10 | 0.763398E+10 | 0.853242E+10 | 0.576308E+10 | 0.276934E+10 | 0.00 | 0.00 |
March | 0.699426E+10 | 0.707526E+10 | 0.832362E+10 | 0.526768E+10 | 0.305594E+10 | 0.00 | 0.00 |
April | 0.688973E+10 | 0.446016E+10 | 0.729769E+10 | 0.396096E+10 | 0.333673E+10 | 0.00 | 0.00 |
May | 0.665947E+10 | 0.259537E+10 | 0.633997E+10 | 0.216747E+10 | 0.417250E+10 | 0.00 | 0.00 |
June | 0.632289E+10 | 0.172939E+10 | 0.550523E+10 | 0.146737E+10 | 0.403785E+10 | 0.00 | 0.00 |
July | 0.753410E+10 | 0.165037E+10 | 0.621963E+10 | 0.197033E+10 | 0.424929E+10 | 0.00 | 0.00 |
August | 0.776688E+10 | 0.186606E+10 | 0.664220E+10 | 0.277836E+10 | 0.386383E+10 | 0.00 | 0.00 |
September | 0.730341E+10 | 0.282265E+10 | 0.688526E+10 | 0.366690E+10 | 0.321836E+10 | 0.00 | 0.00 |
October | 0.551689E+10 | 0.430494E+10 | 0.607550E+10 | 0.357330E+10 | 0.250221E+10 | 0.00 | 0.00 |
November | 0.402543E+10 | 0.613454E+10 | 0.523735E+10 | 0.328696E+10 | 0.195039E+10 | 0.00 | 0.00 |
December | 0.358234E+10 | 0.994689E+10 | 0.576029E+10 | 0.377709E+10 | 0.198321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.746038E+11 | 0.604141E+11 | 0.802795E+11 | 0.428695E+11 | 0.374100E+11 | 0.00 | 0.00 |
Minimum of Months | 0.358234E+10 | 0.165037E+10 | 0.523735E+10 | 0.146737E+10 | 0.195039E+10 | 0.00 | 0.00 |
Maximum of Months | 0.776688E+10 | 0.101944E+11 | 0.853242E+10 | 0.576308E+10 | 0.424929E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.440903E+09 | 0.802360E+10 | 0.160048E+10 | 0.670185E+09 | 0.930298E+09 | 0.00 | 0.00 |
February | 0.121266E+10 | 0.580797E+10 | 0.235530E+10 | 0.107574E+10 | 0.127956E+10 | 0.00 | 0.00 |
March | 0.227541E+10 | 0.506430E+10 | 0.343148E+10 | 0.175586E+10 | 0.167562E+10 | 0.00 | 0.00 |
April | 0.355555E+10 | 0.296242E+10 | 0.424212E+10 | 0.214858E+10 | 0.209354E+10 | 0.00 | 0.00 |
May | 0.560928E+10 | 0.170557E+10 | 0.538594E+10 | 0.256911E+10 | 0.281683E+10 | 0.00 | 0.00 |
June | 0.566151E+10 | 0.114774E+10 | 0.502966E+10 | 0.217477E+10 | 0.285489E+10 | 0.00 | 0.00 |
July | 0.648655E+10 | 0.112385E+10 | 0.554863E+10 | 0.257953E+10 | 0.296911E+10 | 0.00 | 0.00 |
August | 0.515342E+10 | 0.124225E+10 | 0.456616E+10 | 0.207482E+10 | 0.249133E+10 | 0.00 | 0.00 |
September | 0.334590E+10 | 0.186510E+10 | 0.345351E+10 | 0.155160E+10 | 0.190191E+10 | 0.00 | 0.00 |
October | 0.157827E+10 | 0.296727E+10 | 0.225432E+10 | 0.904981E+09 | 0.134934E+10 | 0.00 | 0.00 |
November | 0.503808E+09 | 0.453171E+10 | 0.132500E+10 | 0.446737E+09 | 0.878262E+09 | 0.00 | 0.00 |
December | 0.224784E+09 | 0.774896E+10 | 0.122053E+10 | 0.427194E+09 | 0.793341E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.360481E+11 | 0.441907E+11 | 0.404131E+11 | 0.183791E+11 | 0.220340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.224784E+09 | 0.112385E+10 | 0.122053E+10 | 0.427194E+09 | 0.793341E+09 | 0.00 | 0.00 |
Maximum of Months | 0.648655E+10 | 0.802360E+10 | 0.554863E+10 | 0.257953E+10 | 0.296911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1728988.73 | 0.129237E+11 | 0.108342E+10 | 0.00 | 0.108342E+10 | 0.00 | 0.00 |
February | 51211232.87 | 0.936874E+10 | 0.150316E+10 | 0.00 | 0.150316E+10 | 0.00 | 0.00 |
March | 0.155815E+09 | 0.797744E+10 | 0.204753E+10 | 0.00 | 0.204753E+10 | 0.00 | 0.00 |
April | 0.974997E+09 | 0.438153E+10 | 0.259760E+10 | 20273833.32 | 0.257733E+10 | 0.00 | 0.00 |
May | 0.318219E+10 | 0.218455E+10 | 0.377520E+10 | 0.203288E+09 | 0.357192E+10 | 0.00 | 0.00 |
June | 0.430438E+10 | 0.145971E+10 | 0.407728E+10 | 0.448200E+09 | 0.362908E+10 | 0.00 | 0.00 |
July | 0.437618E+10 | 0.148311E+10 | 0.402426E+10 | 0.345356E+09 | 0.367890E+10 | 0.00 | 0.00 |
August | 0.291519E+10 | 0.181681E+10 | 0.305655E+10 | 52490044.10 | 0.300406E+10 | 0.00 | 0.00 |
September | 0.145366E+10 | 0.298252E+10 | 0.230505E+10 | 565037.96 | 0.230448E+10 | 0.00 | 0.00 |
October | 0.347485E+09 | 0.498915E+10 | 0.165386E+10 | 0.00 | 0.165386E+10 | 0.00 | 0.00 |
November | 46619560.41 | 0.755835E+10 | 0.105974E+10 | 0.00 | 0.105974E+10 | 0.00 | 0.00 |
December | 0.00 | 0.124360E+11 | 0.917960E+09 | 0.00 | 0.917960E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.178095E+11 | 0.695616E+11 | 0.281016E+11 | 0.107017E+10 | 0.270314E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.145971E+10 | 0.917960E+09 | 0.00 | 0.917960E+09 | 0.00 | 0.00 |
Maximum of Months | 0.437618E+10 | 0.129237E+11 | 0.407728E+10 | 0.448200E+09 | 0.367890E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.372744E+09 | 0.777430E+10 | 0.158359E+10 | 0.661038E+09 | 0.922547E+09 | 0.00 | 0.00 |
February | 0.100902E+10 | 0.554495E+10 | 0.224764E+10 | 0.958744E+09 | 0.128890E+10 | 0.00 | 0.00 |
March | 0.217088E+10 | 0.480494E+10 | 0.339069E+10 | 0.170082E+10 | 0.168987E+10 | 0.00 | 0.00 |
April | 0.392917E+10 | 0.275178E+10 | 0.454885E+10 | 0.245356E+10 | 0.209529E+10 | 0.00 | 0.00 |
May | 0.520137E+10 | 0.153459E+10 | 0.508730E+10 | 0.223643E+10 | 0.285086E+10 | 0.00 | 0.00 |
June | 0.633408E+10 | 0.107468E+10 | 0.557339E+10 | 0.266606E+10 | 0.290733E+10 | 0.00 | 0.00 |
July | 0.658038E+10 | 0.106747E+10 | 0.564187E+10 | 0.264907E+10 | 0.299280E+10 | 0.00 | 0.00 |
August | 0.478809E+10 | 0.128704E+10 | 0.434989E+10 | 0.190121E+10 | 0.244868E+10 | 0.00 | 0.00 |
September | 0.314039E+10 | 0.196105E+10 | 0.337116E+10 | 0.150892E+10 | 0.186225E+10 | 0.00 | 0.00 |
October | 0.130506E+10 | 0.316429E+10 | 0.210934E+10 | 0.799859E+09 | 0.130948E+10 | 0.00 | 0.00 |
November | 0.460056E+09 | 0.465961E+10 | 0.129951E+10 | 0.434455E+09 | 0.865052E+09 | 0.00 | 0.00 |
December | 0.226574E+09 | 0.761283E+10 | 0.122531E+10 | 0.452896E+09 | 0.772419E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.355178E+11 | 0.432375E+11 | 0.404286E+11 | 0.184231E+11 | 0.220055E+11 | 0.00 | 0.00 |
Minimum of Months | 0.226574E+09 | 0.106747E+10 | 0.122531E+10 | 0.434455E+09 | 0.772419E+09 | 0.00 | 0.00 |
Maximum of Months | 0.658038E+10 | 0.777430E+10 | 0.564187E+10 | 0.266606E+10 | 0.299280E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.528816E+10 | 0.999050E+10 | 0.746040E+10 | 0.519003E+10 | 0.227037E+10 | 0.00 | 0.00 |
February | 0.712844E+10 | 0.761841E+10 | 0.853247E+10 | 0.576312E+10 | 0.276935E+10 | 0.00 | 0.00 |
March | 0.723930E+10 | 0.701345E+10 | 0.832366E+10 | 0.526771E+10 | 0.305595E+10 | 0.00 | 0.00 |
April | 0.712085E+10 | 0.445999E+10 | 0.729772E+10 | 0.396099E+10 | 0.333674E+10 | 0.00 | 0.00 |
May | 0.691712E+10 | 0.252913E+10 | 0.633999E+10 | 0.216748E+10 | 0.417251E+10 | 0.00 | 0.00 |
June | 0.653170E+10 | 0.166904E+10 | 0.550525E+10 | 0.146738E+10 | 0.403786E+10 | 0.00 | 0.00 |
July | 0.764205E+10 | 0.170275E+10 | 0.621965E+10 | 0.197035E+10 | 0.424931E+10 | 0.00 | 0.00 |
August | 0.780868E+10 | 0.206985E+10 | 0.664222E+10 | 0.277838E+10 | 0.386384E+10 | 0.00 | 0.00 |
September | 0.731124E+10 | 0.317282E+10 | 0.688530E+10 | 0.366693E+10 | 0.321837E+10 | 0.00 | 0.00 |
October | 0.549767E+10 | 0.482110E+10 | 0.607554E+10 | 0.357332E+10 | 0.250222E+10 | 0.00 | 0.00 |
November | 0.405690E+10 | 0.650893E+10 | 0.523738E+10 | 0.328698E+10 | 0.195040E+10 | 0.00 | 0.00 |
December | 0.367121E+10 | 0.985245E+10 | 0.576033E+10 | 0.377711E+10 | 0.198321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.762133E+11 | 0.614084E+11 | 0.802799E+11 | 0.428698E+11 | 0.374101E+11 | 0.00 | 0.00 |
Minimum of Months | 0.367121E+10 | 0.166904E+10 | 0.523738E+10 | 0.146738E+10 | 0.195040E+10 | 0.00 | 0.00 |
Maximum of Months | 0.780868E+10 | 0.999050E+10 | 0.853247E+10 | 0.576312E+10 | 0.424931E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.461825E+09 | 0.796897E+10 | 0.160054E+10 | 0.670210E+09 | 0.930326E+09 | 0.00 | 0.00 |
February | 0.126227E+10 | 0.578616E+10 | 0.235538E+10 | 0.107578E+10 | 0.127960E+10 | 0.00 | 0.00 |
March | 0.236369E+10 | 0.500125E+10 | 0.343159E+10 | 0.175592E+10 | 0.167567E+10 | 0.00 | 0.00 |
April | 0.369320E+10 | 0.294526E+10 | 0.424226E+10 | 0.214866E+10 | 0.209360E+10 | 0.00 | 0.00 |
May | 0.576008E+10 | 0.169016E+10 | 0.538611E+10 | 0.256920E+10 | 0.281691E+10 | 0.00 | 0.00 |
June | 0.578428E+10 | 0.113802E+10 | 0.502982E+10 | 0.217485E+10 | 0.285497E+10 | 0.00 | 0.00 |
July | 0.653610E+10 | 0.118448E+10 | 0.554881E+10 | 0.257962E+10 | 0.296919E+10 | 0.00 | 0.00 |
August | 0.515040E+10 | 0.138242E+10 | 0.456630E+10 | 0.207490E+10 | 0.249140E+10 | 0.00 | 0.00 |
September | 0.332387E+10 | 0.207171E+10 | 0.345362E+10 | 0.155166E+10 | 0.190196E+10 | 0.00 | 0.00 |
October | 0.156032E+10 | 0.328002E+10 | 0.225440E+10 | 0.905014E+09 | 0.134938E+10 | 0.00 | 0.00 |
November | 0.505294E+09 | 0.476699E+10 | 0.132504E+10 | 0.446754E+09 | 0.878289E+09 | 0.00 | 0.00 |
December | 0.233590E+09 | 0.776977E+10 | 0.122057E+10 | 0.427210E+09 | 0.793365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.366349E+11 | 0.449852E+11 | 0.404144E+11 | 0.183798E+11 | 0.220347E+11 | 0.00 | 0.00 |
Minimum of Months | 0.233590E+09 | 0.113802E+10 | 0.122057E+10 | 0.427210E+09 | 0.793365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.653610E+10 | 0.796897E+10 | 0.554881E+10 | 0.257962E+10 | 0.296919E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1470420.37 | 0.132169E+11 | 0.108343E+10 | 0.00 | 0.108343E+10 | 0.00 | 0.00 |
February | 41575413.14 | 0.968325E+10 | 0.150317E+10 | 0.00 | 0.150317E+10 | 0.00 | 0.00 |
March | 0.116474E+09 | 0.847331E+10 | 0.204754E+10 | 0.00 | 0.204754E+10 | 0.00 | 0.00 |
April | 0.792914E+09 | 0.483489E+10 | 0.259761E+10 | 20273950.62 | 0.257734E+10 | 0.00 | 0.00 |
May | 0.280861E+10 | 0.251044E+10 | 0.377523E+10 | 0.203289E+09 | 0.357194E+10 | 0.00 | 0.00 |
June | 0.397394E+10 | 0.167527E+10 | 0.407730E+10 | 0.448202E+09 | 0.362910E+10 | 0.00 | 0.00 |
July | 0.417814E+10 | 0.161296E+10 | 0.402428E+10 | 0.345358E+09 | 0.367892E+10 | 0.00 | 0.00 |
August | 0.280770E+10 | 0.189709E+10 | 0.305657E+10 | 52490347.80 | 0.300408E+10 | 0.00 | 0.00 |
September | 0.138936E+10 | 0.302463E+10 | 0.230506E+10 | 565041.23 | 0.230449E+10 | 0.00 | 0.00 |
October | 0.328389E+09 | 0.497866E+10 | 0.165387E+10 | 0.00 | 0.165387E+10 | 0.00 | 0.00 |
November | 43771419.34 | 0.757910E+10 | 0.105974E+10 | 0.00 | 0.105974E+10 | 0.00 | 0.00 |
December | 0.00 | 0.126371E+11 | 0.917965E+09 | 0.00 | 0.917965E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164823E+11 | 0.721237E+11 | 0.281018E+11 | 0.107018E+10 | 0.270316E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.161296E+10 | 0.917965E+09 | 0.00 | 0.917965E+09 | 0.00 | 0.00 |
Maximum of Months | 0.417814E+10 | 0.132169E+11 | 0.407730E+10 | 0.448202E+09 | 0.367892E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.354831E+09 | 0.792606E+10 | 0.158353E+10 | 0.661011E+09 | 0.922518E+09 | 0.00 | 0.00 |
February | 0.964484E+09 | 0.570040E+10 | 0.224756E+10 | 0.958706E+09 | 0.128886E+10 | 0.00 | 0.00 |
March | 0.206443E+10 | 0.506407E+10 | 0.339057E+10 | 0.170075E+10 | 0.168982E+10 | 0.00 | 0.00 |
April | 0.374104E+10 | 0.295520E+10 | 0.454869E+10 | 0.245346E+10 | 0.209523E+10 | 0.00 | 0.00 |
May | 0.498368E+10 | 0.166917E+10 | 0.508712E+10 | 0.223634E+10 | 0.285078E+10 | 0.00 | 0.00 |
June | 0.618526E+10 | 0.114694E+10 | 0.557320E+10 | 0.266596E+10 | 0.290724E+10 | 0.00 | 0.00 |
July | 0.649814E+10 | 0.108724E+10 | 0.564167E+10 | 0.264896E+10 | 0.299271E+10 | 0.00 | 0.00 |
August | 0.474027E+10 | 0.126007E+10 | 0.434974E+10 | 0.190113E+10 | 0.244861E+10 | 0.00 | 0.00 |
September | 0.310014E+10 | 0.191341E+10 | 0.337104E+10 | 0.150885E+10 | 0.186219E+10 | 0.00 | 0.00 |
October | 0.127448E+10 | 0.311706E+10 | 0.210927E+10 | 0.799826E+09 | 0.130944E+10 | 0.00 | 0.00 |
November | 0.445664E+09 | 0.464672E+10 | 0.129946E+10 | 0.434437E+09 | 0.865024E+09 | 0.00 | 0.00 |
December | 0.218228E+09 | 0.770841E+10 | 0.122527E+10 | 0.452877E+09 | 0.772393E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.345706E+11 | 0.441947E+11 | 0.404271E+11 | 0.184223E+11 | 0.220048E+11 | 0.00 | 0.00 |
Minimum of Months | 0.218228E+09 | 0.108724E+10 | 0.122527E+10 | 0.434437E+09 | 0.772393E+09 | 0.00 | 0.00 |
Maximum of Months | 0.649814E+10 | 0.792606E+10 | 0.564167E+10 | 0.266596E+10 | 0.299271E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.505946E+10 | 0.103980E+11 | 0.746036E+10 | 0.519000E+10 | 0.227036E+10 | 0.00 | 0.00 |
February | 0.685733E+10 | 0.787611E+10 | 0.853242E+10 | 0.576308E+10 | 0.276934E+10 | 0.00 | 0.00 |
March | 0.693368E+10 | 0.737763E+10 | 0.832362E+10 | 0.526768E+10 | 0.305594E+10 | 0.00 | 0.00 |
April | 0.682825E+10 | 0.476501E+10 | 0.729769E+10 | 0.396096E+10 | 0.333673E+10 | 0.00 | 0.00 |
May | 0.660219E+10 | 0.279207E+10 | 0.633997E+10 | 0.216747E+10 | 0.417250E+10 | 0.00 | 0.00 |
June | 0.627031E+10 | 0.187367E+10 | 0.550523E+10 | 0.146737E+10 | 0.403785E+10 | 0.00 | 0.00 |
July | 0.748871E+10 | 0.178470E+10 | 0.621963E+10 | 0.197033E+10 | 0.424929E+10 | 0.00 | 0.00 |
August | 0.770677E+10 | 0.205379E+10 | 0.664220E+10 | 0.277836E+10 | 0.386383E+10 | 0.00 | 0.00 |
September | 0.722057E+10 | 0.307991E+10 | 0.688526E+10 | 0.366690E+10 | 0.321836E+10 | 0.00 | 0.00 |
October | 0.542933E+10 | 0.467993E+10 | 0.607550E+10 | 0.357330E+10 | 0.250221E+10 | 0.00 | 0.00 |
November | 0.396072E+10 | 0.648631E+10 | 0.523735E+10 | 0.328696E+10 | 0.195039E+10 | 0.00 | 0.00 |
December | 0.353614E+10 | 0.101867E+11 | 0.576029E+10 | 0.377709E+10 | 0.198321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.738935E+11 | 0.633538E+11 | 0.802795E+11 | 0.428695E+11 | 0.374100E+11 | 0.00 | 0.00 |
Minimum of Months | 0.353614E+10 | 0.178470E+10 | 0.523735E+10 | 0.146737E+10 | 0.195039E+10 | 0.00 | 0.00 |
Maximum of Months | 0.770677E+10 | 0.103980E+11 | 0.853242E+10 | 0.576308E+10 | 0.424929E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.437717E+09 | 0.814803E+10 | 0.160048E+10 | 0.670185E+09 | 0.930298E+09 | 0.00 | 0.00 |
February | 0.120752E+10 | 0.595491E+10 | 0.235530E+10 | 0.107574E+10 | 0.127956E+10 | 0.00 | 0.00 |
March | 0.226420E+10 | 0.525529E+10 | 0.343148E+10 | 0.175586E+10 | 0.167562E+10 | 0.00 | 0.00 |
April | 0.353489E+10 | 0.315555E+10 | 0.424212E+10 | 0.214858E+10 | 0.209354E+10 | 0.00 | 0.00 |
May | 0.558998E+10 | 0.182100E+10 | 0.538594E+10 | 0.256911E+10 | 0.281683E+10 | 0.00 | 0.00 |
June | 0.564537E+10 | 0.122856E+10 | 0.502966E+10 | 0.217477E+10 | 0.285489E+10 | 0.00 | 0.00 |
July | 0.647222E+10 | 0.120002E+10 | 0.554863E+10 | 0.257953E+10 | 0.296911E+10 | 0.00 | 0.00 |
August | 0.512722E+10 | 0.134638E+10 | 0.456616E+10 | 0.207482E+10 | 0.249133E+10 | 0.00 | 0.00 |
September | 0.330723E+10 | 0.202165E+10 | 0.345351E+10 | 0.155160E+10 | 0.190191E+10 | 0.00 | 0.00 |
October | 0.154421E+10 | 0.322015E+10 | 0.225432E+10 | 0.904981E+09 | 0.134934E+10 | 0.00 | 0.00 |
November | 0.489433E+09 | 0.476210E+10 | 0.132500E+10 | 0.446737E+09 | 0.878262E+09 | 0.00 | 0.00 |
December | 0.222435E+09 | 0.789817E+10 | 0.122053E+10 | 0.427194E+09 | 0.793341E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.358424E+11 | 0.460118E+11 | 0.404131E+11 | 0.183791E+11 | 0.220340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.222435E+09 | 0.120002E+10 | 0.122053E+10 | 0.427194E+09 | 0.793341E+09 | 0.00 | 0.00 |
Maximum of Months | 0.647222E+10 | 0.814803E+10 | 0.554863E+10 | 0.257953E+10 | 0.296911E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.574810E+10 | -0.549024E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -257864054.0 | 60.05 | 0.00 | 0.00 |
February | 0.532932E+10 | -0.510162E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -227695349.3 | 60.05 | 0.00 | 0.00 |
March | 0.626334E+10 | -0.601659E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -246751520.8 | 60.05 | 0.00 | 0.00 |
April | 0.548500E+10 | -0.525371E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -231288952.1 | 60.05 | 0.00 | 0.00 |
May | 0.559243E+10 | -0.535901E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233420110.1 | 60.05 | 0.00 | 0.00 |
June | 0.523715E+10 | -0.501176E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225388074.5 | 60.05 | 0.00 | 0.00 |
July | 0.470877E+10 | -0.447756E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231210345.9 | 60.05 | 0.00 | 0.00 |
August | 0.504563E+10 | -0.481309E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232541220.2 | 60.05 | 0.00 | 0.00 |
September | 0.458015E+10 | -0.435482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225331582.9 | 60.05 | 0.00 | 0.00 |
October | 0.490610E+10 | -0.466946E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -236643559.5 | 60.05 | 0.00 | 0.00 |
November | 0.509266E+10 | -0.485746E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -235202495.1 | 60.05 | 0.00 | 0.00 |
December | 0.534825E+10 | -0.509420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -254044594.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.633369E+11 | -0.604995E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.283738E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.458015E+10 | -0.601659E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -257864054.0 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.626334E+10 | -0.435482E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -225331582.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245944E+11 | 35541.30 | 09-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145521E+11 | 34904.17 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.791795E+10 | 27292.11 | 15-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661073E+09 | 14382.13 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8965763.45 | 3123.96 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 564888.70 | 6.13 | 29-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1142970.20 | 5.95 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 803907.39 | 5.89 | 09-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88956.31 | 5.72 | 01-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129099E+09 | 11044.83 | 30-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.364511E+10 | 21138.02 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197037E+11 | 34416.64 | 26-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.712150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 88956.31 | 5.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245944E+11 | 35541.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120997E+10 | 16626.65 | 17-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106771E+09 | 16603.41 | 21-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37471944.47 | 16590.22 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12640736.17 | 16593.60 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399972E+09 | 16597.30 | 28-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120997E+10 | 16626.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157031E+11 | 14122.21 | 09-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105926E+11 | 13860.73 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106710E+11 | 13694.34 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.506085E+10 | 13694.70 | 26-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163369E+10 | 13750.26 | 30-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.445805E+09 | 13651.58 | 12-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103318E+09 | 9787.81 | 10-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.238323E+09 | 12902.71 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117531E+10 | 13760.52 | 06-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.371891E+10 | 13692.33 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.718384E+10 | 13696.01 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141922E+11 | 13738.94 | 28-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.103318E+09 | 9787.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157031E+11 | 14122.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.866973E+10 | 9141.56 | 09-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.569737E+10 | 8972.30 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.483754E+10 | 8858.65 | 08-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162921E+10 | 8844.13 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165040E+09 | 8831.03 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22130201.31 | 3081.79 | 10-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 57336.05 | 95.56 | 18-AUG-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66841394.15 | 4911.96 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.901333E+09 | 8832.35 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294843E+10 | 8861.10 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.732651E+10 | 8864.86 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.866973E+10 | 9141.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144629E+11 | 13895.30 | 09-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102537E+11 | 13638.02 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.948745E+10 | 13472.33 | 28-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.434772E+10 | 13550.81 | 20-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.750036E+09 | 13423.28 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 61060307.11 | 5499.39 | 10-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6083733.74 | 4648.95 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158168E+09 | 7942.70 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171622E+10 | 13453.09 | 10-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.499447E+10 | 13468.98 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119523E+11 | 13476.26 | 20-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.581902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144629E+11 | 13895.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.894251E+10 | 9416.10 | 09-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.592512E+10 | 9241.66 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.514190E+10 | 9124.48 | 08-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202158E+10 | 9109.41 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266887E+09 | 9095.94 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34251305.15 | 4486.10 | 01-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8936929.52 | 4388.67 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80078475.57 | 4825.30 | 21-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.946168E+09 | 9097.28 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312028E+10 | 9126.96 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.757954E+10 | 9132.00 | 20-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.894251E+10 | 9416.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.293871E+11 | 35604.94 | 06-JAN-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191022E+11 | 34993.06 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128322E+11 | 30673.70 | 15-MAR-06:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.207343E+10 | 20061.95 | 05-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43613335.11 | 8898.81 | 01-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 574751.97 | 6.04 | 30-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 924259.74 | 6.06 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 546607.05 | 5.65 | 24-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82437.86 | 5.50 | 01-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100508E+10 | 17151.67 | 30-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725095E+10 | 25761.42 | 25-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250782E+11 | 34406.09 | 20-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.967750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 82437.86 | 5.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.293871E+11 | 35604.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.516777E+10 | 22751.54 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241261E+10 | 22734.84 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106777E+10 | 22738.37 | 17-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130543E+09 | 22742.59 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 139871.38 | 1864.95 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84903065.27 | 22660.78 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127842E+10 | 22747.66 | 30-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396547E+10 | 22751.71 | 28-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.516777E+10 | 22751.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.884024E+10 | 13902.11 | 09-JAN-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503469E+10 | 13613.27 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384435E+10 | 13332.97 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129682E+10 | 13336.69 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101968E+09 | 13237.12 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6302280.11 | 6099.40 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123604E+09 | 8268.53 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124570E+10 | 13327.42 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.362671E+10 | 13342.83 | 25-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.850358E+10 | 13376.73 | 20-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.884024E+10 | 13902.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.783804E+10 | 10184.42 | 06-JAN-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.469182E+10 | 9970.33 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325430E+10 | 9763.74 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.938243E+09 | 9758.88 | 10-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56589554.79 | 9677.33 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3458056.24 | 1916.29 | 10-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5132407.53 | 1366.28 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172025E+09 | 5614.65 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124450E+10 | 9758.35 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316375E+10 | 9759.81 | 29-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.717800E+10 | 9796.19 | 20-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.783804E+10 | 10184.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127917E+11 | 14012.05 | 06-JAN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.829169E+10 | 13644.83 | 14-FEB-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.597701E+10 | 13149.36 | 13-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188636E+10 | 13128.21 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109572E+09 | 13030.20 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4745928.60 | 4910.64 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168814E+09 | 8355.87 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174086E+10 | 13130.51 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.498640E+10 | 13160.12 | 28-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114440E+11 | 13537.85 | 20-DEC-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127917E+11 | 14012.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.859104E+10 | 10617.96 | 06-JAN-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.539729E+10 | 10397.93 | 14-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.392967E+10 | 10021.38 | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138820E+10 | 10025.25 | 10-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137537E+09 | 9950.64 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12365100.01 | 2183.86 | 10-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24534493.46 | 5272.45 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251591E+09 | 5733.71 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151476E+10 | 10024.71 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371009E+10 | 10021.35 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.790758E+10 | 10213.44 | 26-DEC-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.859104E+10 | 10617.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.318529E+11 | 30831.16 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197448E+11 | 30622.91 | 14-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112934E+11 | 29638.17 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146783E+10 | 21809.98 | 05-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39903702.86 | 9890.47 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401685.06 | 6.69 | 30-JUN-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 532708.10 | 6.45 | 21-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 305971.83 | 5.98 | 11-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2938845.02 | 1927.74 | 06-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.777492E+09 | 17162.62 | 30-OCT-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.713276E+10 | 27100.09 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279535E+11 | 30176.38 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100267E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 305971.83 | 5.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318529E+11 | 30831.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174560E+11 | 39000.05 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108010E+11 | 38732.17 | 14-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.720549E+10 | 37661.78 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219918E+10 | 37662.68 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137377E+09 | 37653.30 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6947768.01 | 8579.94 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 89439482.33 | 23229.35 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244610E+10 | 37671.12 | 16-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.736227E+10 | 37671.07 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154041E+11 | 38155.11 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.631079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174560E+11 | 39000.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139932E+11 | 18647.37 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.885252E+10 | 18402.99 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.701454E+10 | 17747.77 | 16-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302724E+10 | 17519.74 | 10-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.572959E+09 | 17486.39 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137032E+09 | 8294.16 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 51835707.19 | 7844.15 | 10-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137713E+09 | 10048.98 | 19-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.904997E+09 | 17414.61 | 23-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340922E+10 | 17532.94 | 31-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.702190E+10 | 17516.64 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136387E+11 | 18203.12 | 20-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.587619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 51835707.19 | 7844.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139932E+11 | 18647.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113058E+11 | 12036.14 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.741397E+10 | 11872.37 | 14-FEB-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.531331E+10 | 11475.92 | 16-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185471E+10 | 11308.30 | 10-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216993E+09 | 11236.90 | 09-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45782317.41 | 5085.22 | 10-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24774005.26 | 3779.44 | 08-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 56827273.89 | 6848.63 | 19-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.587244E+09 | 11240.44 | 23-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255434E+10 | 11316.82 | 31-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.545854E+10 | 11323.13 | 29-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106341E+11 | 11762.32 | 21-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 24774005.26 | 3779.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113058E+11 | 12036.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184702E+11 | 18645.55 | 06-JAN-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128439E+11 | 18300.84 | 14-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.987431E+10 | 17552.84 | 16-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407794E+10 | 17314.92 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.642368E+09 | 17263.54 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87098172.93 | 7867.41 | 10-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40029417.85 | 5755.59 | 08-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147383E+09 | 10331.86 | 19-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119181E+10 | 17192.68 | 23-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.434407E+10 | 17320.14 | 11-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.893775E+10 | 17300.95 | 18-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170507E+11 | 18133.30 | 20-DEC-08:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.777076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 40029417.85 | 5755.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184702E+11 | 18645.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117422E+11 | 12749.43 | 06-JAN-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.784618E+10 | 12513.41 | 14-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.583772E+10 | 11959.33 | 16-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241095E+10 | 11825.28 | 10-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.432257E+09 | 11750.40 | 09-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106725E+09 | 5308.11 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35670572.34 | 4626.13 | 10-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124704E+09 | 7334.98 | 19-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.781754E+09 | 11753.96 | 23-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.278211E+10 | 11833.81 | 31-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.576794E+10 | 11820.53 | 28-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110431E+11 | 12398.71 | 20-DEC-08:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 35670572.34 | 4626.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117422E+11 | 12749.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 195708.88 | 195708.88 | 2308.50 | 30-JAN-07:03 | 2308.50 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.157656E+10 | 0.157105E+10 | 28321.21 | 23-APR-17:32 | 28321.21 | 0.00 |
May | 0.00 | 0.00 | 0.194834E+11 | 0.181292E+11 | 65685.80 | 26-MAY-10:50 | 42773.23 | 0.00 |
June | 0.00 | 0.00 | 0.458232E+11 | 0.352021E+11 | 127997.93 | 30-JUN-04:01 | 74132.44 | 0.00 |
July | 0.00 | 0.00 | 0.613706E+11 | 0.460977E+11 | 134824.94 | 05-JUL-10:30 | 48245.42 | 0.00 |
August | 0.00 | 0.00 | 0.516470E+11 | 0.364251E+11 | 94080.95 | 30-AUG-09:40 | 46465.38 | 0.00 |
September | 0.00 | 0.00 | 0.116445E+11 | 0.960278E+10 | 73278.86 | 01-SEP-15:30 | 68492.85 | 0.00 |
October | 0.00 | 0.00 | 0.167672E+10 | 0.161003E+10 | 37383.54 | 19-OCT-15:00 | 37383.54 | 0.00 |
November | 0.00 | 0.00 | 0.288756E+09 | 0.216660E+09 | 15752.98 | 01-NOV-15:00 | 12517.29 | 0.00 |
December | 0.00 | 0.00 | 492032.95 | 492032.95 | 6427.90 | 28-DEC-07:02 | 6427.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193511E+12 | 0.148855E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.613706E+11 | 0.460977E+11 | 134824.94 | 74132.44 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 48575.64 | 48575.64 | 647.68 | 02-JAN-05:21 | 647.68 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 94686.89 | 94686.89 | 473.43 | 23-MAR-13:03 | 473.43 | 0.00 |
April | 0.00 | 0.00 | 0.183898E+10 | 0.181871E+10 | 33081.16 | 23-APR-16:42 | 33081.16 | 0.00 |
May | 0.00 | 0.00 | 0.194610E+11 | 0.180877E+11 | 69941.77 | 25-MAY-16:00 | 63459.15 | 0.00 |
June | 0.00 | 0.00 | 0.443200E+11 | 0.345199E+11 | 131565.25 | 30-JUN-04:01 | 77787.13 | 0.00 |
July | 0.00 | 0.00 | 0.574508E+11 | 0.432479E+11 | 136688.20 | 05-JUL-10:30 | 49202.68 | 0.00 |
August | 0.00 | 0.00 | 0.456244E+11 | 0.323408E+11 | 88661.97 | 31-AUG-12:40 | 40815.06 | 0.00 |
September | 0.00 | 0.00 | 0.102218E+11 | 0.839025E+10 | 68622.74 | 01-SEP-15:30 | 65450.76 | 0.00 |
October | 0.00 | 0.00 | 0.150627E+10 | 0.143682E+10 | 33079.19 | 19-OCT-15:00 | 33079.19 | 0.00 |
November | 0.00 | 0.00 | 0.248223E+09 | 0.177678E+09 | 13421.46 | 01-NOV-15:00 | 10014.04 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180672E+12 | 0.140020E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.574508E+11 | 0.432479E+11 | 136688.20 | 77787.13 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2678974.97 | 2674259.05 | 1595.95 | 31-JAN-06:06 | 1595.95 | 0.00 |
February | 0.00 | 0.00 | 4358084.90 | 4357645.05 | 1615.43 | 27-FEB-06:16 | 1615.43 | 0.00 |
March | 0.00 | 0.00 | 1804206.04 | 1792967.91 | 1166.79 | 06-MAR-06:20 | 1166.79 | 0.00 |
April | 0.00 | 0.00 | 0.212428E+10 | 0.205125E+10 | 48309.09 | 23-APR-16:22 | 48309.09 | 0.00 |
May | 0.00 | 0.00 | 0.233466E+11 | 0.208758E+11 | 83572.85 | 25-MAY-15:20 | 76555.18 | 0.00 |
June | 0.00 | 0.00 | 0.512242E+11 | 0.391865E+11 | 152075.40 | 30-JUN-04:01 | 82724.28 | 0.00 |
July | 0.00 | 0.00 | 0.660331E+11 | 0.488345E+11 | 128686.11 | 05-JUL-13:00 | 51743.90 | 0.00 |
August | 0.00 | 0.00 | 0.519818E+11 | 0.355558E+11 | 99060.74 | 08-AUG-15:00 | 81120.40 | 0.00 |
September | 0.00 | 0.00 | 0.112553E+11 | 0.871891E+10 | 78291.47 | 01-SEP-15:30 | 73581.76 | 0.00 |
October | 0.00 | 0.00 | 0.166974E+10 | 0.149482E+10 | 39551.54 | 22-OCT-13:42 | 35624.59 | 0.00 |
November | 0.00 | 0.00 | 0.326466E+09 | 0.223680E+09 | 17319.67 | 01-NOV-15:00 | 12082.92 | 0.00 |
December | 0.00 | 0.00 | 2710316.14 | 2698480.66 | 1659.07 | 15-DEC-06:04 | 1659.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207973E+12 | 0.156953E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1804206.04 | 1792967.91 | 1166.79 | 1166.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.660331E+11 | 0.488345E+11 | 152075.40 | 82724.28 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 92995.93 | 385883.27 | 19-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 65425.70 | 368055.34 | 28-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 42787.30 | 397662.92 | 29-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13954.92 | 402794.53 | 11-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1967.96 | 399130.74 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 369.12 | 71514.32 | 12-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 94.63 | 63625.81 | 10-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 283.70 | 101836.72 | 19-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2198.63 | 192885.72 | 23-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11323.45 | 426111.05 | 16-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 33527.95 | 382599.73 | 15-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 81843.73 | 386839.27 | 28-DEC-06:01 |
Annual Sum or Average | 0.00 | 28777.09 | ||||
Minimum of Months | 0.00 | 0.00 | 94.63 | 63625.81 | ||
Maximum of Months | 0.00 | 0.00 | 92995.93 | 426111.05 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 2040.00 | 7525.83 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 2098.89 | 7598.27 | 24-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2236.08 | 7596.57 | 01-MAR-12:18 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2017.13 | 7443.90 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1991.01 | 7153.39 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1923.77 | 6743.20 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1662.51 | 6338.91 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1787.37 | 6089.26 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1670.81 | 6140.68 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1733.99 | 6464.53 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1864.42 | 6862.19 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1892.43 | 7233.54 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1908.76 | ||||
Minimum of Months | 0.00 | 0.00 | 1662.51 | 6089.26 | ||
Maximum of Months | 0.00 | 0.00 | 2236.08 | 7598.27 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.627084E+10 | 0.77 | 6536.85 | 02-JAN-05:01 | 1.39 |
February | 0.491577E+10 | 0.68 | 6536.85 | 06-FEB-07:01 | 1.38 |
March | 0.511344E+10 | 0.64 | 6536.85 | 06-MAR-06:01 | 1.38 |
April | 0.439310E+10 | 0.55 | 8228.69 | 20-APR-05:01 | 1.53 |
May | 0.579289E+10 | 0.60 | 9961.98 | 30-MAY-06:03 | 1.64 |
June | 0.691498E+10 | 0.67 | 10302.92 | 30-JUN-15:00 | 1.65 |
July | 0.788716E+10 | 0.69 | 13750.44 | 05-JUL-10:40 | 1.86 |
August | 0.792195E+10 | 0.72 | 10250.16 | 08-AUG-15:30 | 1.65 |
September | 0.604443E+10 | 0.62 | 10303.65 | 01-SEP-15:30 | 1.65 |
October | 0.472584E+10 | 0.55 | 9041.64 | 04-OCT-05:01 | 1.58 |
November | 0.405899E+10 | 0.53 | 6536.85 | 27-NOV-07:01 | 1.38 |
December | 0.562014E+10 | 0.70 | 6536.85 | 04-DEC-07:01 | 1.38 |
Annual Sum or Average | 0.696595E+11 | 0.64 | |||
Minimum of Months | 0.405899E+10 | 0.53 | 6536.85 | 1.38 | |
Maximum of Months | 0.792195E+10 | 0.77 | 13750.44 | 1.86 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.549804E+10 | 0.73 | 6097.84 | 23-JAN-06:09 | 1.34 |
February | 0.429492E+10 | 0.64 | 6097.84 | 27-FEB-06:06 | 1.34 |
March | 0.424268E+10 | 0.58 | 6097.84 | 01-MAR-07:01 | 1.34 |
April | 0.386520E+10 | 0.52 | 6097.84 | 03-APR-05:01 | 1.34 |
May | 0.519359E+10 | 0.59 | 9165.95 | 18-MAY-14:05 | 1.57 |
June | 0.634089E+10 | 0.65 | 13823.11 | 30-JUN-04:01 | 1.87 |
July | 0.693982E+10 | 0.65 | 13823.11 | 05-JUL-10:30 | 1.86 |
August | 0.637670E+10 | 0.66 | 9400.59 | 08-AUG-14:05 | 1.59 |
September | 0.457138E+10 | 0.56 | 9620.06 | 01-SEP-15:30 | 1.60 |
October | 0.375049E+10 | 0.50 | 6097.84 | 30-OCT-05:01 | 1.34 |
November | 0.377613E+10 | 0.53 | 6097.84 | 29-NOV-06:01 | 1.34 |
December | 0.507480E+10 | 0.68 | 6097.84 | 11-DEC-06:15 | 1.34 |
Annual Sum or Average | 0.599246E+11 | 0.61 | |||
Minimum of Months | 0.375049E+10 | 0.50 | 6097.84 | 1.34 | |
Maximum of Months | 0.693982E+10 | 0.73 | 13823.11 | 1.87 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.666185E+10 | 0.70 | 6479.20 | 02-JAN-08:00 | 1.14 |
February | 0.555732E+10 | 0.65 | 6479.20 | 06-FEB-07:15 | 1.14 |
March | 0.529977E+10 | 0.57 | 6479.20 | 02-MAR-06:01 | 1.14 |
April | 0.430846E+10 | 0.47 | 6479.20 | 05-APR-06:01 | 1.14 |
May | 0.491479E+10 | 0.48 | 7808.48 | 18-MAY-15:00 | 1.21 |
June | 0.569886E+10 | 0.53 | 10822.43 | 30-JUN-04:01 | 1.39 |
July | 0.597701E+10 | 0.51 | 8658.47 | 24-JUL-15:00 | 1.27 |
August | 0.556420E+10 | 0.52 | 7946.87 | 08-AUG-15:20 | 1.22 |
September | 0.431516E+10 | 0.46 | 7747.76 | 01-SEP-15:30 | 1.21 |
October | 0.414675E+10 | 0.44 | 6479.20 | 13-OCT-06:02 | 1.14 |
November | 0.510010E+10 | 0.57 | 6479.20 | 13-NOV-07:02 | 1.14 |
December | 0.641736E+10 | 0.68 | 6479.20 | 05-DEC-07:01 | 1.14 |
Annual Sum or Average | 0.639616E+11 | 0.55 | |||
Minimum of Months | 0.414675E+10 | 0.44 | 6479.20 | 1.14 | |
Maximum of Months | 0.666185E+10 | 0.70 | 10822.43 | 1.39 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.182665E+10 | 0.164399E+10 | 1682.70 | 09-JAN-07:12 | 1514.43 | 1514.43 | 45.53 | 5.35 |
February | 0.119885E+10 | 0.107896E+10 | 1593.95 | 14-FEB-07:05 | 1434.56 | 1434.56 | 45.83 | 5.11 |
March | 0.879611E+09 | 0.791650E+09 | 1503.10 | 07-MAR-07:01 | 1352.79 | 1352.79 | 47.58 | 4.80 |
April | 0.279109E+09 | 0.251198E+09 | 1412.87 | 05-APR-06:01 | 1271.58 | 1271.58 | 43.43 | 4.38 |
May | 46129986.67 | 41516988.01 | 1335.77 | 01-MAY-06:01 | 1202.19 | 1202.19 | 37.65 | 3.81 |
June | 8155208.97 | 7339688.07 | 415.99 | 01-JUN-06:03 | 374.39 | 374.39 | 27.53 | 0.48 |
July | 1782400.52 | 1604160.47 | 363.94 | 10-JUL-06:03 | 327.54 | 327.54 | 23.40 | 0.42 |
August | 5493722.90 | 4944350.61 | 657.89 | 19-AUG-06:03 | 592.10 | 592.10 | 31.27 | 0.85 |
September | 46704868.84 | 42034381.96 | 1077.85 | 23-SEP-06:03 | 970.06 | 970.06 | 35.26 | 1.87 |
October | 0.228850E+09 | 0.205965E+09 | 1399.31 | 30-OCT-06:01 | 1259.38 | 1259.38 | 45.13 | 4.30 |
November | 0.659900E+09 | 0.593910E+09 | 1470.58 | 25-NOV-07:15 | 1323.52 | 1323.52 | 46.52 | 4.67 |
December | 0.165921E+10 | 0.149329E+10 | 1599.39 | 26-DEC-08:00 | 1439.45 | 1439.45 | 45.80 | 5.13 |
Annual Sum or Average | 0.684045E+10 | 0.615641E+10 | ||||||
Minimum of Months | 1782400.52 | 1604160.47 | 363.94 | 327.54 | 327.54 | 23.40 | 0.42 | |
Maximum of Months | 0.182665E+10 | 0.164399E+10 | 1682.70 | 1514.43 | 1514.43 | 47.58 | 5.35 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:01 | 2.06 | 2.06 | 57.78 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.64 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.53 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 56.58 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:01 | 2.06 | 2.06 | 57.02 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.74 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.93 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:02 | 2.06 | 2.06 | 57.12 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 57.17 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.98 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.80 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 56.94 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.53 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.98 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 41.70 | 41.70 | 92995.93 | 385883.27 | 19-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 42.38 | 60.00 | 65425.70 | 368055.34 | 28-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 30.70 | 30.70 | 42787.30 | 397662.92 | 29-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.14 | 26.14 | 13954.92 | 402794.53 | 11-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.87 | 22.87 | 1967.96 | 399130.74 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.17 | 25.17 | 369.12 | 71514.32 | 12-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.06 | 31.06 | 94.63 | 63625.81 | 10-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.95 | 28.95 | 283.70 | 101836.72 | 19-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.33 | 26.33 | 2198.63 | 192885.72 | 23-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.36 | 21.36 | 11323.45 | 426111.05 | 16-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 30.29 | 30.29 | 33527.95 | 382599.73 | 15-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 31.59 | 31.59 | 81843.73 | 386839.27 | 28-DEC-06:01 |
Annual Sum or Average | 0.00 | 28777.09 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.36 | 21.36 | 94.63 | 63625.81 | ||
Maximum of Months | 0.00 | 0.00 | 42.38 | 60.00 | 92995.93 | 426111.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 57.78 | 57.78 | 2040.00 | 7525.83 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 57.11 | 57.11 | 2098.89 | 7598.27 | 24-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.08 | 57.08 | 2236.08 | 7596.57 | 01-MAR-12:18 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.13 | 57.13 | 2017.13 | 7443.90 | 03-APR-11:15 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.81 | 57.81 | 1991.01 | 7153.39 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.41 | 57.41 | 1923.77 | 6743.20 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.56 | 57.56 | 1662.51 | 6338.91 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.66 | 57.66 | 1787.37 | 6089.26 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.70 | 57.70 | 1670.81 | 6140.68 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.68 | 56.68 | 1733.99 | 6464.53 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.52 | 57.52 | 1864.42 | 6862.19 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.37 | 57.37 | 1892.43 | 7233.54 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1908.76 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.68 | 56.68 | 1662.51 | 6089.26 | ||
Maximum of Months | 0.00 | 0.00 | 57.81 | 57.81 | 2236.08 | 7598.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.735826E+11 | 0.00 | 0.00 | 0.627090E+10 | 0.00 | 0.00 |
February | 0.471277E+11 | 0.00 | 0.00 | 0.491577E+10 | 0.00 | 0.00 |
March | 0.380933E+11 | 0.00 | 0.00 | 0.511344E+10 | 0.00 | 0.00 |
April | 0.137204E+11 | 0.00 | 0.00 | 0.480716E+10 | 0.00 | 0.00 |
May | 0.282462E+10 | 0.00 | 0.00 | 0.104918E+11 | 0.00 | 0.00 |
June | 0.563812E+09 | 0.00 | 0.00 | 0.178577E+11 | 0.00 | 0.00 |
July | 0.104461E+09 | 0.00 | 0.00 | 0.222542E+11 | 0.00 | 0.00 |
August | 0.254205E+09 | 0.00 | 0.00 | 0.199755E+11 | 0.00 | 0.00 |
September | 0.148049E+10 | 0.00 | 0.00 | 0.886895E+10 | 0.00 | 0.00 |
October | 0.741173E+10 | 0.00 | 0.00 | 0.514769E+10 | 0.00 | 0.00 |
November | 0.219048E+11 | 0.00 | 0.00 | 0.413526E+10 | 0.00 | 0.00 |
December | 0.611543E+11 | 0.00 | 0.00 | 0.562027E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.268222E+12 | 0.00 | 0.00 | 0.115459E+12 | 0.00 | 0.00 |
Minimum of Months | 0.104461E+09 | 0.00 | 0.00 | 0.413526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.735826E+11 | 0.00 | 0.00 | 0.222542E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.726159E+11 | 0.00 | 0.00 | 0.549805E+10 | 0.00 | 0.00 |
February | 0.449303E+11 | 0.00 | 0.00 | 0.429492E+10 | 0.00 | 0.00 |
March | 0.309053E+11 | 0.00 | 0.00 | 0.424270E+10 | 0.00 | 0.00 |
April | 0.771359E+10 | 0.00 | 0.00 | 0.434588E+10 | 0.00 | 0.00 |
May | 0.449420E+09 | 0.00 | 0.00 | 0.991436E+10 | 0.00 | 0.00 |
June | 16397908.22 | 0.00 | 0.00 | 0.169936E+11 | 0.00 | 0.00 |
July | 924259.74 | 0.00 | 0.00 | 0.204648E+11 | 0.00 | 0.00 |
August | 41261716.76 | 0.00 | 0.00 | 0.171352E+11 | 0.00 | 0.00 |
September | 0.716117E+09 | 0.00 | 0.00 | 0.708658E+10 | 0.00 | 0.00 |
October | 0.683580E+10 | 0.00 | 0.00 | 0.413528E+10 | 0.00 | 0.00 |
November | 0.240163E+11 | 0.00 | 0.00 | 0.384249E+10 | 0.00 | 0.00 |
December | 0.640768E+11 | 0.00 | 0.00 | 0.507480E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.252318E+12 | 0.00 | 0.00 | 0.103029E+12 | 0.00 | 0.00 |
Minimum of Months | 924259.74 | 0.00 | 0.00 | 0.384249E+10 | 0.00 | 0.00 |
Maximum of Months | 0.726159E+11 | 0.00 | 0.00 | 0.204648E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.104820E+12 | 0.00 | 0.00 | 0.666262E+10 | 0.00 | 0.00 |
February | 0.675024E+11 | 0.00 | 0.00 | 0.555857E+10 | 0.00 | 0.00 |
March | 0.465388E+11 | 0.00 | 0.00 | 0.530029E+10 | 0.00 | 0.00 |
April | 0.150379E+11 | 0.00 | 0.00 | 0.487145E+10 | 0.00 | 0.00 |
May | 0.204186E+10 | 0.00 | 0.00 | 0.106987E+11 | 0.00 | 0.00 |
June | 0.377039E+09 | 0.00 | 0.00 | 0.183056E+11 | 0.00 | 0.00 |
July | 0.152842E+09 | 0.00 | 0.00 | 0.218461E+11 | 0.00 | 0.00 |
August | 0.473881E+09 | 0.00 | 0.00 | 0.181258E+11 | 0.00 | 0.00 |
September | 0.355819E+10 | 0.00 | 0.00 | 0.716331E+10 | 0.00 | 0.00 |
October | 0.163133E+11 | 0.00 | 0.00 | 0.458616E+10 | 0.00 | 0.00 |
November | 0.416812E+11 | 0.00 | 0.00 | 0.518818E+10 | 0.00 | 0.00 |
December | 0.957242E+11 | 0.00 | 0.00 | 0.641813E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.394222E+12 | 0.00 | 0.00 | 0.114725E+12 | 0.00 | 0.00 |
Minimum of Months | 0.152842E+09 | 0.00 | 0.00 | 0.458616E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104820E+12 | 0.00 | 0.00 | 0.218461E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.627084E+10 | 195708.88 | 0.735826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491577E+10 | 0.00 | 0.471277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511344E+10 | 0.00 | 0.380933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.439310E+10 | 0.157656E+10 | 0.137204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.579289E+10 | 0.194834E+11 | 0.282462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.691498E+10 | 0.458232E+11 | 0.563812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.788716E+10 | 0.613706E+11 | 0.104461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.792195E+10 | 0.516470E+11 | 0.254205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.604443E+10 | 0.116445E+11 | 0.148049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.472584E+10 | 0.167672E+10 | 0.741173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405899E+10 | 0.288756E+09 | 0.219048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.562014E+10 | 492032.95 | 0.611543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.696595E+11 | 0.193511E+12 | 0.268222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.405899E+10 | 0.00 | 0.104461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.792195E+10 | 0.613706E+11 | 0.735826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.549804E+10 | 48575.64 | 0.726159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429492E+10 | 0.00 | 0.449303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424268E+10 | 94686.89 | 0.309053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.386520E+10 | 0.183898E+10 | 0.771359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.519359E+10 | 0.194610E+11 | 0.449420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.634089E+10 | 0.443200E+11 | 16397908.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.693982E+10 | 0.574508E+11 | 924259.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.637670E+10 | 0.456244E+11 | 41261716.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.457138E+10 | 0.102218E+11 | 0.716117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375049E+10 | 0.150627E+10 | 0.683580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.377613E+10 | 0.248223E+09 | 0.240163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.507480E+10 | 0.00 | 0.640768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.599246E+11 | 0.180672E+12 | 0.252318E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375049E+10 | 0.00 | 924259.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.693982E+10 | 0.574508E+11 | 0.726159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.666185E+10 | 2678974.97 | 0.104820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.555732E+10 | 4358084.90 | 0.675024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.529977E+10 | 1804206.04 | 0.465388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430846E+10 | 0.212428E+10 | 0.150379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491479E+10 | 0.233466E+11 | 0.204186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.569886E+10 | 0.512242E+11 | 0.377039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.597701E+10 | 0.660331E+11 | 0.152842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.556420E+10 | 0.519818E+11 | 0.473881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.431516E+10 | 0.112553E+11 | 0.355819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.414675E+10 | 0.166974E+10 | 0.163133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.510010E+10 | 0.326466E+09 | 0.416812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.641736E+10 | 2710316.14 | 0.957242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639616E+11 | 0.207973E+12 | 0.394222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.414675E+10 | 1804206.04 | 0.152842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.666185E+10 | 0.660331E+11 | 0.104820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.627084E+10 | 0.735826E+11 | 0.00 | 0.00 | 55537.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491577E+10 | 0.471277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511344E+10 | 0.380933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.439310E+10 | 0.137204E+11 | 0.00 | 0.00 | 0.414065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.579289E+10 | 0.282462E+10 | 0.00 | 0.00 | 0.469890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.691498E+10 | 0.563812E+09 | 0.00 | 0.00 | 0.109427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.788716E+10 | 0.104461E+09 | 0.00 | 0.00 | 0.143671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.792195E+10 | 0.254205E+09 | 0.00 | 0.00 | 0.120536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.604443E+10 | 0.148049E+10 | 0.00 | 0.00 | 0.282452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.472584E+10 | 0.741173E+10 | 0.00 | 0.00 | 0.421852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405899E+10 | 0.219048E+11 | 0.00 | 0.00 | 76269630.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.562014E+10 | 0.611543E+11 | 0.00 | 0.00 | 135727.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.696595E+11 | 0.268222E+12 | 0.00 | 0.00 | 0.457991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.405899E+10 | 0.104461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.792195E+10 | 0.735826E+11 | 0.00 | 0.00 | 0.143671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.549804E+10 | 0.726159E+11 | 0.00 | 0.00 | 13907.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429492E+10 | 0.449303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424268E+10 | 0.309053E+11 | 0.00 | 0.00 | 27143.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.386520E+10 | 0.771359E+10 | 0.00 | 0.00 | 0.480683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.519359E+10 | 0.449420E+09 | 0.00 | 0.00 | 0.472076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.634089E+10 | 16397908.22 | 0.00 | 0.00 | 0.106527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.693982E+10 | 924259.74 | 0.00 | 0.00 | 0.135250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.637670E+10 | 41261716.76 | 0.00 | 0.00 | 0.107585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.457138E+10 | 0.716117E+09 | 0.00 | 0.00 | 0.251520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375049E+10 | 0.683580E+10 | 0.00 | 0.00 | 0.384787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.377613E+10 | 0.240163E+11 | 0.00 | 0.00 | 66358998.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.507480E+10 | 0.640768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.599246E+11 | 0.252318E+12 | 0.00 | 0.00 | 0.431041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375049E+10 | 924259.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.693982E+10 | 0.726159E+11 | 0.00 | 0.00 | 0.135250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.666185E+10 | 0.104820E+12 | 0.00 | 0.00 | 767053.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.555732E+10 | 0.675024E+11 | 0.00 | 0.00 | 1249010.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.529977E+10 | 0.465388E+11 | 0.00 | 0.00 | 517293.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430846E+10 | 0.150379E+11 | 0.00 | 0.00 | 0.562988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491479E+10 | 0.204186E+10 | 0.00 | 0.00 | 0.578395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.569886E+10 | 0.377039E+09 | 0.00 | 0.00 | 0.126067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.597701E+10 | 0.152842E+09 | 0.00 | 0.00 | 0.158691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.556420E+10 | 0.473881E+09 | 0.00 | 0.00 | 0.125616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.431516E+10 | 0.355819E+10 | 0.00 | 0.00 | 0.284815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.414675E+10 | 0.163133E+11 | 0.00 | 0.00 | 0.439416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.510010E+10 | 0.416812E+11 | 0.00 | 0.00 | 88081014.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.641736E+10 | 0.957242E+11 | 0.00 | 0.00 | 776478.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639616E+11 | 0.394222E+12 | 0.00 | 0.00 | 0.507633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.414675E+10 | 0.152842E+09 | 0.00 | 0.00 | 517293.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.666185E+10 | 0.104820E+12 | 0.00 | 0.00 | 0.158691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216017E+11 | 0.00 | 0.00 | 174572.55 | 0.00 | 0.678393E+09 | 0.432742E+09 | 0.00 | 0.25 |
February | 0.166082E+11 | 0.00 | 0.00 | 949959.66 | 0.00 | 20520286.85 | 0.178184E+10 | 0.00 | 0.27 |
March | 0.136741E+11 | 0.00 | 0.00 | 7555960.61 | 0.00 | 9868128.75 | 0.511164E+10 | 0.00 | 0.29 |
April | 0.468834E+10 | 0.00 | 0.00 | 23713798.24 | 19748061.26 | 0.00 | 0.122746E+11 | 0.00 | 0.48 |
May | 0.136161E+10 | 0.103753E+09 | 0.00 | 41483855.80 | 0.00 | 0.00 | 0.151567E+11 | 0.00 | 0.84 |
June | 0.583751E+09 | 0.251402E+10 | 0.00 | 34232054.84 | 97872262.96 | 0.00 | 0.105052E+11 | 0.00 | 1.04 |
July | 0.578954E+09 | 0.365739E+10 | 0.00 | 27740096.33 | 0.126604E+09 | 0.00 | 0.754436E+10 | 0.00 | 0.96 |
August | 0.791105E+09 | 0.222834E+10 | 0.00 | 39703128.81 | 58726170.64 | 0.00 | 0.114648E+11 | 0.00 | 1.20 |
September | 0.135475E+10 | 20268550.13 | 0.00 | 47023713.28 | 0.00 | 0.00 | 0.203331E+11 | 0.00 | 0.98 |
October | 0.297332E+10 | 0.00 | 0.00 | 32661583.40 | 0.00 | 0.00 | 0.158313E+11 | 0.00 | 0.52 |
November | 0.790585E+10 | 0.00 | 0.00 | 12125410.15 | 0.00 | 3550310.34 | 0.722191E+10 | 0.00 | 0.31 |
December | 0.195342E+11 | 0.00 | 0.00 | 635705.70 | 0.00 | 0.112249E+09 | 0.126542E+10 | 0.00 | 0.25 |
Annual Sum or Average | 0.916558E+11 | 0.852376E+10 | 0.00 | 0.268000E+09 | 0.302950E+09 | 0.824580E+09 | 0.108924E+12 | 0.00 | 0.62 |
Minimum of Months | 0.578954E+09 | 0.00 | 0.00 | 174572.55 | 0.00 | 0.00 | 0.432742E+09 | 0.00 | 0.25 |
Maximum of Months | 0.216017E+11 | 0.365739E+10 | 0.00 | 47023713.28 | 0.126604E+09 | 0.678393E+09 | 0.203331E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393813E+10 | 0.00 | 0.00 | 0.23 |
February | 0.153162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100292E+10 | 0.00 | 0.00 | 0.23 |
March | 0.152673E+11 | 0.00 | 0.00 | 213569.29 | 0.00 | 0.439368E+09 | 0.405977E+09 | 0.00 | 0.25 |
April | 0.846660E+10 | 0.00 | 0.00 | 5977238.34 | 34096595.27 | 77369095.33 | 0.380388E+10 | 0.00 | 0.35 |
May | 0.421041E+10 | 72963466.30 | 0.00 | 20357812.23 | 0.00 | 0.00 | 0.749056E+10 | 0.00 | 0.60 |
June | 0.159764E+10 | 0.175758E+10 | 0.00 | 19661858.59 | 0.218662E+09 | 0.00 | 0.628571E+10 | 0.00 | 0.74 |
July | 0.101471E+10 | 0.266835E+10 | 0.00 | 16665810.27 | 0.142966E+09 | 0.00 | 0.445877E+10 | 0.00 | 0.68 |
August | 0.170572E+10 | 0.163624E+10 | 0.00 | 20933237.16 | 56074963.10 | 0.00 | 0.607381E+10 | 0.00 | 0.81 |
September | 0.428796E+10 | 15541565.41 | 0.00 | 18818498.92 | 1080578.09 | 0.00 | 0.862501E+10 | 0.00 | 0.62 |
October | 0.833633E+10 | 0.00 | 0.00 | 5558189.81 | 0.00 | 50883227.78 | 0.347292E+10 | 0.00 | 0.34 |
November | 0.110590E+11 | 0.00 | 0.00 | 168485.02 | 0.00 | 0.925640E+09 | 0.388597E+09 | 0.00 | 0.26 |
December | 0.162813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258806E+10 | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.104299E+12 | 0.615068E+10 | 0.00 | 0.108355E+09 | 0.452880E+09 | 0.902237E+10 | 0.410052E+11 | 0.00 | 0.45 |
Minimum of Months | 0.101471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.167557E+11 | 0.266835E+10 | 0.00 | 20933237.16 | 0.218662E+09 | 0.393813E+10 | 0.862501E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.716634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108031E+11 | 0.00 | 0.00 | 0.21 |
February | 0.803032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654666E+10 | 0.00 | 0.00 | 0.22 |
March | 0.118329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327339E+10 | 0.00 | 0.00 | 0.25 |
April | 0.111888E+11 | 0.00 | 0.00 | 1579259.25 | 27417699.06 | 0.545300E+09 | 0.169420E+10 | 0.00 | 0.40 |
May | 0.766125E+10 | 85990402.12 | 0.00 | 12241617.68 | 1394317.94 | 51170367.01 | 0.463513E+10 | 0.00 | 0.67 |
June | 0.309946E+10 | 0.168560E+10 | 0.00 | 15247085.56 | 0.567684E+09 | 0.00 | 0.513655E+10 | 0.00 | 0.81 |
July | 0.182199E+10 | 0.234909E+10 | 0.00 | 12026489.20 | 0.697710E+09 | 0.00 | 0.331998E+10 | 0.00 | 0.71 |
August | 0.369604E+10 | 0.156031E+10 | 0.00 | 10285511.17 | 0.384474E+09 | 1448444.03 | 0.325304E+10 | 0.00 | 0.85 |
September | 0.973823E+10 | 7771962.64 | 0.00 | 5581694.50 | 31216.18 | 8747713.50 | 0.309067E+10 | 0.00 | 0.66 |
October | 0.113520E+11 | 0.00 | 0.00 | 367497.12 | 0.00 | 0.549726E+09 | 0.320487E+09 | 0.00 | 0.38 |
November | 0.867872E+10 | 0.00 | 603203.31 | 0.00 | 1068526.13 | 0.308565E+10 | 0.00 | 45126.75 | 0.27 |
December | 0.666353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969657E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.909296E+11 | 0.568876E+10 | 603203.31 | 57329154.48 | 0.167978E+10 | 0.345618E+11 | 0.214501E+11 | 45126.75 | 0.47 |
Minimum of Months | 0.182199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.118329E+11 | 0.234909E+10 | 603203.31 | 15247085.56 | 0.697710E+09 | 0.108031E+11 | 0.513655E+10 | 45126.75 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68505494.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860856E+10 | 0.00 | 0.00 | 0.47 |
February | 0.445520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641112E+10 | 0.00 | 0.00 | 0.49 |
March | 0.166528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532734E+10 | 0.00 | 0.00 | 0.55 |
April | 0.437046E+10 | 0.00 | 0.00 | 919.44 | 12631705.15 | 0.179332E+10 | 12189496.74 | 0.00 | 0.88 |
May | 0.471706E+10 | 26936001.27 | 0.00 | 1752652.03 | 3293900.87 | 0.137354E+09 | 0.634431E+09 | 0.00 | 1.37 |
June | 0.224341E+10 | 0.573657E+09 | 0.00 | 2722072.85 | 0.326535E+09 | 2389333.66 | 0.116311E+10 | 0.00 | 1.56 |
July | 0.111813E+10 | 0.756808E+09 | 0.00 | 2369037.81 | 0.457109E+09 | 1411094.21 | 0.880123E+09 | 0.00 | 1.33 |
August | 0.249725E+10 | 0.394287E+09 | 0.00 | 1215756.54 | 0.392417E+09 | 20818236.67 | 0.492425E+09 | 0.00 | 1.70 |
September | 0.533564E+10 | 1263707.80 | 0.00 | 288960.13 | 2187302.08 | 0.253203E+09 | 0.227384E+09 | 0.00 | 1.41 |
October | 0.367942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195214E+10 | 0.00 | 0.00 | 0.83 |
November | 0.123040E+10 | 0.00 | 412818.42 | 0.00 | 332715.99 | 0.419402E+10 | 0.00 | 70309.55 | 0.59 |
December | 85401812.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764048E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.274565E+11 | 0.175295E+10 | 412818.42 | 8349398.81 | 0.119451E+10 | 0.363422E+11 | 0.340966E+10 | 70309.55 | 0.97 |
Minimum of Months | 68505494.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1411094.21 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.533564E+10 | 0.756808E+09 | 412818.42 | 2722072.85 | 0.457109E+09 | 0.860856E+10 | 0.116311E+10 | 70309.55 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 43515887.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552218E+10 | 0.00 | 0.00 | 0.47 |
February | 0.617941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381557E+10 | 0.00 | 0.00 | 0.50 |
March | 0.178871E+10 | 0.00 | 0.00 | 10505.14 | 0.00 | 0.273955E+10 | 30051309.77 | 0.00 | 0.56 |
April | 0.237789E+10 | 0.00 | 0.00 | 1481787.90 | 8258871.70 | 0.776560E+09 | 0.999099E+09 | 0.00 | 0.94 |
May | 0.236461E+10 | 21098213.38 | 0.00 | 4135320.62 | 1662938.82 | 33000767.24 | 0.140678E+10 | 0.00 | 1.56 |
June | 0.918225E+09 | 0.494871E+09 | 0.00 | 5509491.15 | 0.168976E+09 | 301970.28 | 0.187800E+10 | 0.00 | 1.98 |
July | 0.493194E+09 | 0.746228E+09 | 0.00 | 4737627.06 | 0.208331E+09 | 459563.13 | 0.122152E+10 | 0.00 | 1.81 |
August | 0.136158E+10 | 0.355723E+09 | 0.00 | 3219954.26 | 0.218718E+09 | 4763582.93 | 0.768718E+09 | 0.00 | 1.98 |
September | 0.281414E+10 | 2004499.89 | 0.00 | 2068058.91 | 369947.68 | 0.113439E+09 | 0.102172E+10 | 0.00 | 1.53 |
October | 0.247512E+10 | 0.00 | 0.00 | 132730.05 | 0.00 | 0.106275E+10 | 0.145553E+09 | 0.00 | 0.86 |
November | 0.117042E+10 | 0.00 | 268901.49 | 0.00 | 217536.64 | 0.237621E+10 | 0.00 | 46369.88 | 0.60 |
December | 0.106799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489572E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.165321E+11 | 0.161992E+10 | 268901.49 | 21295475.10 | 0.606534E+09 | 0.213405E+11 | 0.747143E+10 | 46369.88 | 1.11 |
Minimum of Months | 43515887.84 | 0.00 | 0.00 | 0.00 | 0.00 | 301970.28 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.281414E+10 | 0.746228E+09 | 268901.49 | 5509491.15 | 0.218718E+09 | 0.552218E+10 | 0.187800E+10 | 46369.88 | 1.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196007E+10 | 0.00 | 0.00 | 418009.82 | 0.00 | 0.624617E+10 | 0.348277E+09 | 0.00 | 0.46 |
February | 0.214332E+10 | 0.00 | 0.00 | 1239652.31 | 0.00 | 0.414485E+10 | 0.688959E+09 | 0.00 | 0.51 |
March | 0.267104E+10 | 0.00 | 0.00 | 2090815.45 | 0.00 | 0.352651E+10 | 0.105027E+10 | 0.00 | 0.57 |
April | 0.306345E+10 | 3103698.85 | 0.00 | 5002482.24 | 9691271.46 | 0.130731E+10 | 0.258581E+10 | 0.00 | 1.03 |
May | 0.366202E+10 | 35390321.16 | 0.00 | 6212746.79 | 2558993.97 | 0.141639E+09 | 0.207171E+10 | 0.00 | 1.50 |
June | 0.204968E+10 | 0.682418E+09 | 0.00 | 5380305.12 | 0.326712E+09 | 8560410.51 | 0.173377E+10 | 0.00 | 1.74 |
July | 0.109031E+10 | 0.968975E+09 | 0.00 | 4557557.96 | 0.438766E+09 | 2758222.75 | 0.125184E+10 | 0.00 | 1.53 |
August | 0.222833E+10 | 0.643772E+09 | 0.00 | 4515086.55 | 0.299882E+09 | 28047859.69 | 0.106755E+10 | 0.00 | 1.94 |
September | 0.402627E+10 | 3858622.35 | 0.00 | 5896923.73 | 14567.60 | 0.190742E+09 | 0.243264E+10 | 0.00 | 1.66 |
October | 0.349367E+10 | 0.00 | 0.00 | 3860374.42 | 0.00 | 0.134056E+10 | 0.135171E+10 | 0.00 | 0.97 |
November | 0.199159E+10 | 0.00 | 412432.44 | 1508022.53 | 337016.36 | 0.297859E+10 | 0.585082E+09 | 68701.41 | 0.60 |
December | 0.141755E+10 | 0.00 | 0.00 | 2434.27 | 0.00 | 0.628041E+10 | 27066608.34 | 0.00 | 0.46 |
Annual Sum or Average | 0.297973E+11 | 0.233752E+10 | 412432.44 | 40684411.19 | 0.107796E+10 | 0.261961E+11 | 0.151947E+11 | 68701.41 | 1.08 |
Minimum of Months | 0.109031E+10 | 0.00 | 0.00 | 2434.27 | 0.00 | 2758222.75 | 27066608.34 | 0.00 | 0.46 |
Maximum of Months | 0.402627E+10 | 0.968975E+09 | 412432.44 | 6212746.79 | 0.438766E+09 | 0.628041E+10 | 0.258581E+10 | 68701.41 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.380486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562554E+10 | 0.00 | 0.00 | 0.51 |
February | 0.817969E+09 | 0.00 | 0.00 | 12364.55 | 0.00 | 0.392153E+10 | 44361789.06 | 0.00 | 0.54 |
March | 0.155807E+10 | 0.00 | 0.00 | 406035.51 | 0.00 | 0.308449E+10 | 0.260987E+09 | 0.00 | 0.61 |
April | 0.241950E+10 | 0.00 | 0.00 | 1856701.32 | 8847159.75 | 0.110156E+10 | 0.110998E+10 | 0.00 | 1.06 |
May | 0.272984E+10 | 30080867.27 | 0.00 | 4208911.57 | 1271254.63 | 0.101213E+09 | 0.133745E+10 | 0.00 | 1.69 |
June | 0.146578E+10 | 0.519988E+09 | 0.00 | 3840670.96 | 0.208234E+09 | 6309773.89 | 0.119443E+10 | 0.00 | 1.96 |
July | 0.745183E+09 | 0.732512E+09 | 0.00 | 3169623.79 | 0.266201E+09 | 1907189.84 | 0.860429E+09 | 0.00 | 1.70 |
August | 0.164613E+10 | 0.424151E+09 | 0.00 | 2223191.37 | 0.209677E+09 | 19123342.08 | 0.600343E+09 | 0.00 | 2.05 |
September | 0.326907E+10 | 3073033.52 | 0.00 | 1740408.98 | 10072.86 | 0.162588E+09 | 0.855891E+09 | 0.00 | 1.66 |
October | 0.246822E+10 | 0.00 | 0.00 | 491981.75 | 0.00 | 0.120278E+10 | 0.296828E+09 | 0.00 | 0.93 |
November | 0.113268E+10 | 0.00 | 284324.34 | 0.00 | 233032.00 | 0.266242E+10 | 0.00 | 46568.22 | 0.65 |
December | 0.174281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520781E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.188072E+11 | 0.170981E+10 | 284324.34 | 17949889.79 | 0.694474E+09 | 0.230973E+11 | 0.656070E+10 | 46568.22 | 1.16 |
Minimum of Months | 0.174281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1907189.84 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.326907E+10 | 0.732512E+09 | 284324.34 | 4208911.57 | 0.266201E+09 | 0.562554E+10 | 0.133745E+10 | 46568.22 | 2.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951386E+10 | 0.00 | 0.00 | 0.50 |
February | 0.158021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736019E+10 | 0.00 | 0.00 | 0.51 |
March | 0.567073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684623E+10 | 0.00 | 0.00 | 0.53 |
April | 0.252761E+10 | 0.00 | 0.00 | 0.00 | 7728415.52 | 0.322760E+10 | 0.00 | 0.00 | 0.75 |
May | 0.433952E+10 | 13690470.96 | 0.00 | 87652.19 | 7243944.94 | 0.257287E+09 | 39315362.15 | 0.00 | 1.06 |
June | 0.259114E+10 | 0.306042E+09 | 0.00 | 328778.30 | 0.310160E+09 | 2139857.08 | 0.217391E+09 | 0.00 | 1.19 |
July | 0.127304E+10 | 0.538188E+09 | 0.00 | 1021212.24 | 0.311981E+09 | 0.00 | 0.624995E+09 | 0.00 | 1.02 |
August | 0.252313E+10 | 0.323131E+09 | 0.00 | 763389.72 | 0.184971E+09 | 999298.27 | 0.434315E+09 | 0.00 | 1.34 |
September | 0.544084E+10 | 3832903.19 | 0.00 | 122059.75 | 27289.65 | 14941837.54 | 0.194834E+09 | 0.00 | 1.18 |
October | 0.504955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879756E+09 | 0.00 | 0.00 | 0.76 |
November | 0.191898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377717E+10 | 0.00 | 0.00 | 0.55 |
December | 0.140677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838416E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.266576E+11 | 0.118488E+10 | 0.00 | 2323092.20 | 0.822112E+09 | 0.402643E+11 | 0.151085E+10 | 0.00 | 0.82 |
Minimum of Months | 0.128052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.544084E+10 | 0.538188E+09 | 0.00 | 1021212.24 | 0.311981E+09 | 0.951386E+10 | 0.624995E+09 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 83847994.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606622E+10 | 0.00 | 0.00 | 0.51 |
February | 0.388414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447478E+10 | 0.00 | 0.00 | 0.52 |
March | 0.110854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370989E+10 | 0.00 | 0.00 | 0.55 |
April | 0.228374E+10 | 0.00 | 0.00 | 359173.19 | 5084776.84 | 0.115855E+10 | 0.342968E+09 | 0.00 | 0.78 |
May | 0.244209E+10 | 12585833.14 | 0.00 | 1880764.46 | 1676031.01 | 31264609.34 | 0.636312E+09 | 0.00 | 1.16 |
June | 0.941886E+09 | 0.338721E+09 | 0.00 | 3645012.78 | 0.137334E+09 | 367672.26 | 0.120960E+10 | 0.00 | 1.46 |
July | 0.502766E+09 | 0.626483E+09 | 0.00 | 3959409.93 | 89358888.98 | 0.00 | 0.113107E+10 | 0.00 | 1.43 |
August | 0.119455E+10 | 0.351591E+09 | 0.00 | 3186831.52 | 63151119.79 | 0.00 | 0.964821E+09 | 0.00 | 1.63 |
September | 0.267615E+10 | 4019660.17 | 0.00 | 2487105.85 | 0.00 | 4444379.47 | 0.129975E+10 | 0.00 | 1.34 |
October | 0.326754E+10 | 0.00 | 0.00 | 201539.94 | 0.00 | 0.456690E+09 | 0.179042E+09 | 0.00 | 0.79 |
November | 0.157368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217388E+10 | 0.00 | 0.00 | 0.57 |
December | 0.160525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537716E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.166237E+11 | 0.133340E+10 | 0.00 | 15719837.67 | 0.296605E+09 | 0.234532E+11 | 0.576356E+10 | 0.00 | 0.94 |
Minimum of Months | 83847994.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.326754E+10 | 0.626483E+09 | 0.00 | 3959409.93 | 0.137334E+09 | 0.606622E+10 | 0.129975E+10 | 0.00 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.521253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107314E+11 | 0.00 | 0.00 | 0.58 |
February | 0.113551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750573E+10 | 0.00 | 0.00 | 0.58 |
March | 0.139681E+10 | 0.00 | 0.00 | 699.82 | 0.00 | 0.703884E+10 | 9066470.65 | 0.00 | 0.60 |
April | 0.264699E+10 | 554365.02 | 0.00 | 577741.79 | 7300476.24 | 0.313784E+10 | 0.469791E+09 | 0.00 | 0.80 |
May | 0.367988E+10 | 28285003.65 | 0.00 | 1966825.55 | 217854.69 | 0.827498E+09 | 0.337473E+09 | 0.00 | 1.12 |
June | 0.215405E+10 | 0.530694E+09 | 0.00 | 2131771.76 | 0.249787E+09 | 0.271186E+09 | 0.486827E+09 | 0.00 | 1.26 |
July | 0.122049E+10 | 0.832054E+09 | 0.00 | 2392496.12 | 0.228429E+09 | 68823415.25 | 0.782226E+09 | 0.00 | 1.15 |
August | 0.208629E+10 | 0.629313E+09 | 0.00 | 3175973.04 | 78119254.40 | 0.186007E+09 | 0.888253E+09 | 0.00 | 1.53 |
September | 0.368048E+10 | 9099628.41 | 0.00 | 4683387.31 | 0.00 | 0.612733E+09 | 0.209198E+10 | 0.00 | 1.40 |
October | 0.352113E+10 | 0.00 | 0.00 | 2475540.54 | 0.00 | 0.223590E+10 | 0.933467E+09 | 0.00 | 0.90 |
November | 0.175268E+10 | 0.00 | 0.00 | 87931.40 | 0.00 | 0.459705E+10 | 73414196.58 | 0.00 | 0.61 |
December | 0.564374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961039E+10 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.243599E+11 | 0.203000E+10 | 0.00 | 17492367.32 | 0.563853E+09 | 0.468234E+11 | 0.607250E+10 | 0.00 | 0.93 |
Minimum of Months | 0.521253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68823415.25 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.368048E+10 | 0.832054E+09 | 0.00 | 4683387.31 | 0.249787E+09 | 0.107314E+11 | 0.209198E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.282002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618078E+10 | 0.00 | 0.00 | 0.53 |
February | 0.524861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456769E+10 | 0.00 | 0.00 | 0.54 |
March | 0.106713E+10 | 0.00 | 0.00 | 26128.30 | 0.00 | 0.391946E+10 | 46385014.78 | 0.00 | 0.57 |
April | 0.207903E+10 | 0.00 | 0.00 | 490360.30 | 5291459.14 | 0.152343E+10 | 0.366900E+09 | 0.00 | 0.82 |
May | 0.266739E+10 | 22044780.17 | 0.00 | 1923852.19 | 340076.49 | 99565220.97 | 0.475611E+09 | 0.00 | 1.21 |
June | 0.147783E+10 | 0.369144E+09 | 0.00 | 1940790.39 | 0.141999E+09 | 3311936.40 | 0.526978E+09 | 0.00 | 1.40 |
July | 0.677177E+09 | 0.647224E+09 | 0.00 | 2504937.98 | 83883576.92 | 0.00 | 0.784521E+09 | 0.00 | 1.30 |
August | 0.136184E+10 | 0.384773E+09 | 0.00 | 2226223.78 | 49203879.35 | 684195.35 | 0.800435E+09 | 0.00 | 1.60 |
September | 0.310118E+10 | 3638510.68 | 0.00 | 1589666.00 | 0.00 | 4524381.81 | 0.940773E+09 | 0.00 | 1.37 |
October | 0.334446E+10 | 0.00 | 0.00 | 399268.36 | 0.00 | 0.492651E+09 | 0.240646E+09 | 0.00 | 0.84 |
November | 0.156012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233752E+10 | 0.00 | 0.00 | 0.59 |
December | 0.187781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559790E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.183308E+11 | 0.142683E+10 | 0.00 | 11101227.29 | 0.280718E+09 | 0.247275E+11 | 0.418225E+10 | 0.00 | 0.94 |
Minimum of Months | 0.187781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.334446E+10 | 0.647224E+09 | 0.00 | 2504937.98 | 0.141999E+09 | 0.618078E+10 | 0.940773E+09 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989138E+10 | 0.00 | 0.00 | 0.52 |
February | 0.549696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719669E+10 | 0.00 | 0.00 | 0.52 |
March | 0.232021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520957E+10 | 0.00 | 0.00 | 0.55 |
April | 0.426629E+10 | 0.00 | 0.00 | 30992.88 | 15826309.58 | 0.117292E+10 | 0.119758E+09 | 0.00 | 0.74 |
May | 0.363954E+10 | 25141799.21 | 0.00 | 2747950.06 | 0.00 | 39034095.75 | 0.100833E+10 | 0.00 | 1.11 |
June | 0.147057E+10 | 0.645678E+09 | 0.00 | 3945993.23 | 0.105480E+09 | 0.00 | 0.141172E+10 | 0.00 | 1.26 |
July | 0.876946E+09 | 0.892955E+09 | 0.00 | 3378328.78 | 0.129284E+09 | 0.00 | 0.102998E+10 | 0.00 | 1.11 |
August | 0.199253E+10 | 0.478369E+09 | 0.00 | 2168118.72 | 0.109949E+09 | 874617.28 | 0.809499E+09 | 0.00 | 1.35 |
September | 0.457991E+10 | 4307696.26 | 0.00 | 688420.78 | 501562.20 | 24930980.99 | 0.572243E+09 | 0.00 | 1.13 |
October | 0.448645E+10 | 0.00 | 0.00 | 31.03 | 0.00 | 0.910274E+09 | 3664544.62 | 0.00 | 0.72 |
November | 0.191338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385068E+10 | 0.00 | 0.00 | 0.56 |
December | 0.185199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879321E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.264442E+11 | 0.204645E+10 | 0.00 | 12959835.47 | 0.361041E+09 | 0.370896E+11 | 0.495520E+10 | 0.00 | 0.84 |
Minimum of Months | 0.163513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.457991E+10 | 0.892955E+09 | 0.00 | 3945993.23 | 0.129284E+09 | 0.989138E+10 | 0.141172E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231714E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658008E+10 | 0.00 | 0.00 | 0.56 |
February | 0.857464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434483E+10 | 0.00 | 0.00 | 0.55 |
March | 0.202852E+10 | 0.00 | 0.00 | 258941.78 | 0.00 | 0.287578E+10 | 0.170290E+09 | 0.00 | 0.59 |
April | 0.237807E+10 | 0.00 | 0.00 | 2183690.63 | 13008518.47 | 0.564394E+09 | 0.119690E+10 | 0.00 | 0.89 |
May | 0.206817E+10 | 18227175.27 | 0.00 | 4895991.92 | 0.00 | 5908473.24 | 0.169404E+10 | 0.00 | 1.47 |
June | 0.843509E+09 | 0.499225E+09 | 0.00 | 5901531.91 | 94408444.84 | 0.00 | 0.200198E+10 | 0.00 | 1.87 |
July | 0.550461E+09 | 0.755963E+09 | 0.00 | 5170226.11 | 0.127428E+09 | 0.00 | 0.139491E+10 | 0.00 | 1.77 |
August | 0.124564E+10 | 0.373286E+09 | 0.00 | 4008685.57 | 0.120325E+09 | 0.00 | 0.107607E+10 | 0.00 | 1.84 |
September | 0.263496E+10 | 4163108.69 | 0.00 | 2804143.60 | 412261.69 | 16598975.20 | 0.132954E+10 | 0.00 | 1.41 |
October | 0.276917E+10 | 0.00 | 0.00 | 484362.01 | 0.00 | 0.663809E+09 | 0.238951E+09 | 0.00 | 0.78 |
November | 0.135214E+10 | 0.00 | 0.00 | 2462.74 | 0.00 | 0.252222E+10 | 812192.35 | 0.00 | 0.59 |
December | 0.244491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587581E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.172043E+11 | 0.165086E+10 | 0.00 | 25710036.27 | 0.355582E+09 | 0.234494E+11 | 0.910349E+10 | 0.00 | 1.07 |
Minimum of Months | 0.231714E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.276917E+10 | 0.755963E+09 | 0.00 | 5901531.91 | 0.127428E+09 | 0.658008E+10 | 0.200198E+10 | 0.00 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234992E+10 | 0.00 | 0.00 | 1174802.54 | 0.00 | 0.699332E+10 | 0.780469E+09 | 0.00 | 0.53 |
February | 0.257030E+10 | 0.00 | 0.00 | 2168338.55 | 0.00 | 0.436504E+10 | 0.114256E+10 | 0.00 | 0.56 |
March | 0.316322E+10 | 0.00 | 0.00 | 3243922.17 | 0.00 | 0.334589E+10 | 0.153209E+10 | 0.00 | 0.60 |
April | 0.314580E+10 | 11667503.33 | 0.00 | 6068310.66 | 5098208.24 | 0.769257E+09 | 0.274473E+10 | 0.00 | 0.96 |
May | 0.280811E+10 | 35102583.24 | 0.00 | 7555413.72 | 0.00 | 40805362.09 | 0.237811E+10 | 0.00 | 1.31 |
June | 0.155434E+10 | 0.774746E+09 | 0.00 | 6211202.50 | 0.116550E+09 | 0.00 | 0.172340E+10 | 0.00 | 1.50 |
July | 0.961694E+09 | 0.117134E+10 | 0.00 | 5001300.88 | 0.138127E+09 | 0.00 | 0.131633E+10 | 0.00 | 1.35 |
August | 0.181976E+10 | 0.753217E+09 | 0.00 | 5628892.99 | 77829716.47 | 888531.28 | 0.137009E+10 | 0.00 | 1.69 |
September | 0.343851E+10 | 12721913.86 | 0.00 | 7567885.55 | 509541.39 | 14002802.46 | 0.296093E+10 | 0.00 | 1.53 |
October | 0.396025E+10 | 0.00 | 0.00 | 4971727.89 | 0.00 | 0.649057E+09 | 0.169901E+10 | 0.00 | 0.93 |
November | 0.245461E+10 | 0.00 | 0.00 | 2367077.71 | 0.00 | 0.278816E+10 | 0.926333E+09 | 0.00 | 0.60 |
December | 0.191234E+10 | 0.00 | 0.00 | 220166.44 | 0.00 | 0.682017E+10 | 0.284880E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.301388E+11 | 0.275879E+10 | 0.00 | 52179041.62 | 0.338114E+09 | 0.257866E+11 | 0.188589E+11 | 0.00 | 1.01 |
Minimum of Months | 0.961694E+09 | 0.00 | 0.00 | 220166.44 | 0.00 | 0.00 | 0.284880E+09 | 0.00 | 0.51 |
Maximum of Months | 0.396025E+10 | 0.117134E+10 | 0.00 | 7567885.55 | 0.138127E+09 | 0.699332E+10 | 0.296093E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.647398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771887E+10 | 0.00 | 0.00 | 0.69 |
February | 0.117580E+10 | 0.00 | 0.00 | 29024.80 | 0.00 | 0.528697E+10 | 62276972.36 | 0.00 | 0.70 |
March | 0.237560E+10 | 0.00 | 0.00 | 519828.82 | 0.00 | 0.373928E+10 | 0.312865E+09 | 0.00 | 0.75 |
April | 0.315855E+10 | 85440.09 | 0.00 | 1951346.29 | 13405554.51 | 0.810409E+09 | 0.109124E+10 | 0.00 | 1.10 |
May | 0.277026E+10 | 31007154.53 | 0.00 | 4484424.00 | 0.00 | 39990891.97 | 0.145841E+10 | 0.00 | 1.66 |
June | 0.141036E+10 | 0.575854E+09 | 0.00 | 3996741.72 | 0.121335E+09 | 433276.25 | 0.123145E+10 | 0.00 | 1.87 |
July | 0.789501E+09 | 0.830706E+09 | 0.00 | 3371300.70 | 0.153779E+09 | 0.00 | 0.955123E+09 | 0.00 | 1.65 |
August | 0.176938E+10 | 0.474278E+09 | 0.00 | 2426623.83 | 91606236.67 | 2482095.82 | 0.745383E+09 | 0.00 | 1.96 |
September | 0.366489E+10 | 4621156.83 | 0.00 | 1891660.79 | 407852.64 | 30436684.68 | 0.950252E+09 | 0.00 | 1.64 |
October | 0.357526E+10 | 0.00 | 0.00 | 670725.96 | 0.00 | 0.724232E+09 | 0.345217E+09 | 0.00 | 0.99 |
November | 0.183752E+10 | 0.00 | 0.00 | 1057.15 | 0.00 | 0.305187E+10 | 9129387.65 | 0.00 | 0.75 |
December | 0.443424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710864E+10 | 0.00 | 0.00 | 0.68 |
Annual Sum or Average | 0.236179E+11 | 0.191655E+10 | 0.00 | 19342734.07 | 0.380533E+09 | 0.285136E+11 | 0.716135E+10 | 0.00 | 1.21 |
Minimum of Months | 0.443424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
Maximum of Months | 0.366489E+10 | 0.830706E+09 | 0.00 | 4484424.00 | 0.153779E+09 | 0.771887E+10 | 0.145841E+10 | 0.00 | 1.96 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:10
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.190393E+12 | 0.342509E+11 | 0.00 | 0.185804E+12 | 0.111491E+12 |
February | 0.244495E+12 | 0.286735E+11 | 0.00 | 0.168032E+12 | 0.782980E+11 |
March | 0.323117E+12 | 0.221944E+11 | 0.00 | 0.205008E+12 | 0.626971E+11 |
April | 0.377959E+12 | 0.172668E+11 | 0.00 | 0.232962E+12 | 0.303150E+11 |
May | 0.423232E+12 | 0.831874E+10 | 0.00 | 0.300134E+12 | 0.812028E+11 |
June | 0.428313E+12 | 0.221534E+10 | 0.00 | 0.191290E+12 | 0.176288E+12 |
July | 0.435959E+12 | 0.476252E+09 | 0.00 | 0.138041E+12 | 0.228808E+12 |
August | 0.368256E+12 | 0.300063E+10 | 0.00 | 0.203132E+12 | 0.185192E+12 |
September | 0.279318E+12 | 0.828684E+10 | 0.00 | 0.298060E+12 | 0.454464E+11 |
October | 0.173452E+12 | 0.137749E+11 | 0.00 | 0.259793E+12 | 0.265894E+11 |
November | 0.107731E+12 | 0.221927E+11 | 0.00 | 0.180647E+12 | 0.505492E+11 |
December | 0.143615E+12 | 0.345972E+11 | 0.00 | 0.181570E+12 | 0.102723E+12 |
Annual Sum or Average | 0.349584E+13 | 0.195248E+12 | 0.00 | 0.254447E+13 | 0.117960E+13 |
Minimum of Months | 0.107731E+12 | 0.476252E+09 | 0.00 | 0.138041E+12 | 0.265894E+11 |
Maximum of Months | 0.435959E+12 | 0.345972E+11 | 0.00 | 0.300134E+12 | 0.228808E+12 |