Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:22
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:22:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2201.72 | 441.92 | 441.92 |
Net Site Energy | 2201.72 | 441.92 | 441.92 |
Total Source Energy | 6255.99 | 1255.67 | 1255.67 |
Net Source Energy | 6255.99 | 1255.67 | 1255.67 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 91.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 235.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 54.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1857.57 | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 91.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 235.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 151.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 54.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 344.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 91.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 235.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 151.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 54.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 60.03 | 69.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 372.84 | 69.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 60.03 | 69.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 372.84 | 69.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1857.572 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1857.572 | 100.00 |
Total On-Site and Utility Electric Sources | 1857.572 | 100.00 |
Total Electricity End Uses | 1857.572 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 282.33 |
Time Setpoint Not Met During Occupied Cooling | 22.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1921.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:22 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:50 | 02-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 20-JAN-12:09 |
Heating | 0.00 | 266214.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 64650.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 30391.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4248.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 192087.47 | 266214.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 266214.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 64650.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 30391.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4248.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 373.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 290.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 745.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 479.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 171.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5882.93 | 373.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 74.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 58.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 34.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1180.79 | 74.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 74.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 58.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 34.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1180.79 | 74.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.39 | 0.220837 | 0.300000 | 1.02 | 0.588900 | 0.500000 | 0.001725 | 0.000152 | 1.02 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.76 | 0.271657 | 0.300000 | 0.827647 | 0.724420 | 0.500000 | 0.001403 | 0.000268 | 1.30 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 3.05 | 0.245639 | 0.300000 | 0.915314 | 0.655036 | 0.500000 | 0.001551 | 0.000517 | 2.52 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.11 | 0.141861 | 0.300000 | 0.334112 | 0.378296 | 0.500000 | 0.002686 | 0.000228 | 1.11 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.951934 | 0.105072 | 0.300000 | 0.285580 | 0.300000 | 0.500000 | 0.003626 | 0.000149 | 0.727698 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.50 | 0.105621 | 0.300000 | 0.448750 | 0.300000 | 0.500000 | 0.003607 | 0.000226 | 1.10 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.08 | 0.092696 | 0.300000 | 0.323689 | 0.300000 | 0.500000 | 0.004110 | 0.000147 | 0.721108 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.835923 | 0.189003 | 0.300000 | 0.250777 | 0.504007 | 0.500000 | 0.002016 | 0.000171 | 0.835923 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.793053 | 0.126122 | 0.300000 | 0.237916 | 0.336326 | 0.500000 | 0.003021 | 0.000113 | 0.550628 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.20 | 0.131456 | 0.300000 | 0.360559 | 0.350549 | 0.500000 | 0.002898 | 0.000169 | 0.825577 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.888883 | 0.112518 | 0.300000 | 0.266665 | 0.300048 | 0.500000 | 0.003386 | 0.000111 | 0.544013 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.862322 | 0.183217 | 0.300000 | 0.258697 | 0.488578 | 0.500000 | 0.002080 | 0.000176 | 0.862322 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.965336 | 0.300000 | 0.500000 | 0.003677 | 0.000116 | 0.567858 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.37 | 0.115568 | 0.300000 | 0.410125 | 0.308182 | 0.500000 | 0.003297 | 0.000174 | 0.851866 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.997353 | 0.100281 | 0.300000 | 0.299206 | 0.300000 | 0.500000 | 0.003799 | 0.000115 | 0.561440 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17388.78 | 0.000152 | 378.16 |
CORE_MID VAV BOX REHEAT COIL | 30627.95 | 0.000268 | 716.87 |
CORE_TOP VAV BOX REHEAT COIL | 59105.80 | 0.000517 | 1381.58 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 26039.53 | 0.000228 | 608.20 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 17013.01 | 0.000149 | 397.36 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25795.05 | 0.000226 | 602.50 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16859.28 | 0.000147 | 393.77 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19558.91 | 0.000171 | 456.93 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12882.04 | 0.000113 | 300.94 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19317.57 | 0.000169 | 451.29 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12727.73 | 0.000111 | 297.33 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 20174.75 | 0.000176 | 471.30 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 13283.94 | 0.000116 | 310.32 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 19930.86 | 0.000174 | 465.61 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 13134.24 | 0.000115 | 306.82 |
PACU_VAV_BOT HEATING COIL | 13739.17 | 0.000120 | 240.93 |
PACU_VAV_MID HEATING COIL | 14623.05 | 0.000128 | 254.96 |
PACU_VAV_TOP HEATING COIL | 12938.69 | 0.000113 | 228.53 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.56 | 2.13 | 7.11 | 3.29 | 6.05 | 6.05 | 0.300000 | 0.544199 | 6.05 |
PACU_VAV_MID | 3.48 | 2.09 | 6.95 | 4.14 | 5.70 | 5.70 | 0.300000 | 0.726748 | 5.70 |
PACU_VAV_TOP | 3.85 | 2.31 | 7.69 | 6.19 | 6.76 | 6.76 | 0.300000 | 0.914592 | 6.76 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.05 |
PACU_VAV_MID_OA_CONTROLLER | 5.70 |
PACU_VAV_TOP_OA_CONTROLLER | 6.76 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.05 | 102669.89 | 0.800359 | 2.01 | 34219.87 | 0.800359 |
PACU_VAV_MID COOLING COIL | 5.70 | 97360.23 | 0.800414 | 1.90 | 32450.17 | 0.800414 |
PACU_VAV_TOP COOLING COIL | 6.76 | 113706.52 | 0.800062 | 2.25 | 37898.38 | 0.800062 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.05 |
PACU_VAV_MID FAN | 5.70 |
PACU_VAV_TOP FAN | 6.76 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000120 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000128 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000113 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003194 | 0.383329 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.003194 | 962.02 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 365140.36 | 365140.36 | 0.003194 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
43 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
44 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
45 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
46 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
47 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
48 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
49 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40053.54104 | 46061.57220 | 2.95104 | 3.39370 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5914.71781 | 7393.39726 | 0.42704 | 0.53379 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32587.05603 | 37475.11443 | 2.39898 | 2.75882 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 14290.44763 | 17863.05954 | 1.04017 | 1.30021 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 35709.22781 | 41065.61198 | 2.65308 | 3.05105 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 27484.32922 | 34355.41152 | 2.01682 | 2.52103 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9739.07867 | 11199.94047 | 0.72357 | 0.83211 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 12088.86881 | 15111.08601 | 0.89097 | 1.11371 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11141.57811 | 12812.81482 | 0.82777 | 0.95193 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 23.97467 | 8.81286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7897.94702 | 9872.43378 | 0.58216 | 0.72770 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 17507.42785 | 20133.54203 | 1.30072 | 1.49583 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 11975.58838 | 14969.48547 | 0.88258 | 1.10323 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12628.36057 | 14522.61465 | 0.93823 | 1.07896 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7826.70925 | 9783.38656 | 0.57689 | 0.72111 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7226.09447 | 8310.00864 | 0.53687 | 0.61740 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9084.04651 | 11355.05814 | 0.66874 | 0.83592 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9282.05935 | 10674.36826 | 0.68961 | 0.79305 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36267 | 8.81033E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5982.49731 | 7478.12164 | 0.44050 | 0.55063 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 14066.72597 | 16176.73487 | 1.04510 | 1.20186 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 8972.23787 | 11215.29734 | 0.66046 | 0.82558 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10403.60477 | 11964.14549 | 0.77294 | 0.88888 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90400 | 8.81750E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5911.00416 | 7388.75520 | 0.43521 | 0.54401 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8156.34325 | 9379.79473 | 0.60598 | 0.69688 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9370.56436 | 11713.20544 | 0.68986 | 0.86232 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11298.43687 | 12993.20240 | 0.83942 | 0.96534 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6169.49889 | 7711.87361 | 0.45429 | 0.56786 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 16000.50878 | 18400.58510 | 1.18877 | 1.36708 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 9257.56404 | 11571.95504 | 0.68149 | 0.85187 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11673.16308 | 13424.13755 | 0.86726 | 0.99735 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6100.13617 | 7625.17021 | 0.44915 | 0.56144 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 86270.73 | 6.04547 | 6.04547 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 19092.03 | 3.28993 | 3.28993 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 81715.32 | 5.70169 | 5.70169 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 19357.81 | 4.14369 | 4.14369 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 95775.20 | 6.76451 | 6.76451 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 19428.26 | 6.18677 | 6.18677 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.39370 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22084 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01811 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58890 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72525E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52125E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01811 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17388.77531 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52125E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 378.16014 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.75882 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27166 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82765 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72442 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40250E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.67947E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30021 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30627.95178 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.67947E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 716.86528 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.05105 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24564 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.91531 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65504 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55106E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.17083E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.52103 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 59105.80222 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.17083E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1381.58071 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11371 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14186 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33411 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37830 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68572E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.27805E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.11371 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26039.52696 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27805E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 608.20282 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95193 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10507 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28558 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.62608E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48837E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72770 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17013.01499 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48837E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 397.36318 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49583 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10562 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44875 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60723E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.25666E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.10323 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25795.05407 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25666E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 602.49628 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07896 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.26956E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32369 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.11023E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47492E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72111 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16859.27759 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47492E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.77459 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83592 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18900 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25078 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50401 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.01584E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.71110E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83592 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19558.90894 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71110E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 456.92793 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79305 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12612 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23792 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33633 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.02087E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12698E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55063 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12882.04200 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12698E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 300.93546 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20186 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13146 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36056 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35055 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.89831E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.68999E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82558 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19317.57061 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.68999E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 451.29465 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88888 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11252 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26666 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30005 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38613E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11348E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54401 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12727.72984 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11348E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 297.33351 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86232 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18322 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25870 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48858 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.07951E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76497E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.86232 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20174.74786 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76497E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 471.30298 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96534 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67713E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.16214E-004 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56786 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13283.94416 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16214E-004 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 310.31652 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36708 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11557 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41012 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30818 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29675E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74364E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.85187 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19930.85721 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74364E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 465.61013 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99735 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10028 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29921 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.79934E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14904E-004 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56144 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13134.24081 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14904E-004 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 306.82216 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.55671 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.13403 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.11342 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.28993 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.04547 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.04547 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.54420 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.47546 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.08528 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.95092 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.14369 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.70169 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.70169 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.72675 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.84574 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.30745 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.69149 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 6.18677 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.76451 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.76451 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.91459 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.04547 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.70169 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.76451 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.04547 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.04547 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 102669.88656 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80036 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.01495 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34219.87319 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80036 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 13739.17347 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20196E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 240.92685 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.04547 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.20196E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.70169 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.70169 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97360.23322 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80041 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.90037 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32450.16573 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80041 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 14623.05047 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27929E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 254.95874 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.70169 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.27929E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.76451 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.76451 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 113706.52209 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80006 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.25461 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37898.38381 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80006 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 12938.69268 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13193E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 228.53011 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.76451 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.13193E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.19441E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.38333 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.19441E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 962.01516 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 365140.36098 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 365140.36000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.19441E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16502.56 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 29055.68 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 56071.97 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 24703.03 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16139.81 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24471.11 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15993.97 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18555.02 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12220.85 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18326.07 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12074.46 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 19139.25 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 12602.13 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 18907.88 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 12460.11 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 11950.44 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 12583.01 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 11406.24 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 101024.46 | 344709.78 | 11.13 | 2.88 | 3.19 | 3.35 | 3.54 | 9.83 | 10.87 | 11.44 | 12.06 | 6.8925 | 5.4568 | 3.6590 | 1.5119 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 95823.97 | 326964.97 | 11.15 | 2.88 | 3.19 | 3.36 | 3.54 | 9.84 | 10.88 | 11.45 | 12.08 | 6.5006 | 5.1479 | 3.4516 | 1.4234 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 111830.72 | 381582.27 | 11.11 | 2.88 | 3.18 | 3.34 | 3.53 | 9.81 | 10.84 | 11.41 | 12.03 | 7.7123 | 6.1031 | 4.0911 | 1.6970 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1063374208 | 7.0096304363E-002 | Pass | Pass | 0.4129740144 | 0.4836819903 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1691319063 | 0.1037541449 | Pass | Pass | 0.5059813107 | 0.4736505448 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.9317457776E-002 | 4.4778630137E-002 | Pass | Pass | 0.4282709349 | 0.4864976324 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.2729073668E-002 | 4.5150339109E-002 | Pass | Pass | 0.4168171845 | 0.4628380747 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.7516067141E-002 | 1.8976806907E-002 | Pass | Pass | 0.6257239893 | 1.3645653728 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.1338806561E-002 | 3.6695120552E-002 | Pass | Pass | 8.8829060194 | 54.6554252786 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2778773320 | 0.2741133851 | Pass | Pass | 4.5743168169 | 13.2071507551 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2862642085 | 0.2843083835 | Pass | Pass | 4.2134645738 | 12.1873551381 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2727351591 | 0.2734557002 | Pass | Pass | 4.0947044863 | 11.7222463263 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2908037306 | 0.2867351162 | Pass | Pass | 4.1309170699 | 11.9593016852 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1526281903 | 0.1598361072 | Pass | Pass | 1.6121542412 | 3.5324921045 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1647488307 | 0.1725299586 | Pass | Pass | 1.2704455761 | 2.3203803626 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1465965886 | 0.1561327641 | Pass | Pass | 1.3515497868 | 2.5217064917 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1695390902 | 0.1770425393 | Pass | Pass | 1.2449452576 | 2.3372089463 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1810452265 | 0.1848302785 | Pass | Pass | 4.9377069062 | 13.6884986867 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1877958895 | 0.1947588710 | Pass | Pass | 4.1783812847 | 11.6810106324 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1732375430 | 0.1817605782 | Pass | Pass | 4.2167679406 | 11.5543286099 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1924841816 | 0.1992782980 | Pass | Pass | 4.0862540135 | 11.3487433274 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3132.08 | 118.77 | 0.00 | 2801.66 | 599.26 | 6651.77 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 183.92 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 429.15 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.55 | 83.55 | 235.45 | |
Exterior Lighting Total | 15013.15 | 235.45 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 365140.36 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 102669.89 | 82172.79 | 20497.09 | 0.80 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97360.23 | 77928.46 | 19431.78 | 0.80 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 113706.52 | 90972.28 | 22734.24 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 101024.5 | 2.88 | 9.83 | N/A | N/A | 11.13 | |
PACU_VAV_MID COOLING COIL | 95824.0 | 2.88 | 9.84 | N/A | N/A | 11.15 | |
PACU_VAV_TOP COOLING COIL | 111830.7 | 2.88 | 9.81 | N/A | N/A | 11.11 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17388.78 | 16502.56 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 30627.95 | 29055.68 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 59105.80 | 56071.97 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 26039.53 | 24703.03 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 17013.01 | 16139.81 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25795.05 | 24471.11 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 16859.28 | 15993.97 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19558.91 | 18555.02 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12882.04 | 12220.85 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19317.57 | 18326.07 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12727.73 | 12074.46 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20174.75 | 19139.25 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13283.94 | 12602.13 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19930.86 | 18907.88 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13134.24 | 12460.11 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 13739.17 | 11950.44 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 14623.05 | 12583.01 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 12938.69 | 11406.24 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1337.13 | 6.05 | 13372.33 | 2211.96 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.70 | 12611.92 | 2211.96 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.76 | 14866.92 | 2197.78 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003194 | 962.02 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101024.46 | 2.88 | 9.83 | 11.13 | 6.8925 | 3.19 | 10.87 | 5.4568 | 3.35 | 11.44 | 3.6590 | 3.54 | 12.06 | 1.5119 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95823.97 | 2.88 | 9.84 | 11.15 | 6.5006 | 3.19 | 10.88 | 5.1479 | 3.36 | 11.45 | 3.4516 | 3.54 | 12.08 | 1.4234 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 111830.72 | 2.88 | 9.81 | 11.11 | 7.7123 | 3.18 | 10.84 | 6.1031 | 3.34 | 11.41 | 4.0911 | 3.53 | 12.03 | 1.6970 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40053.54 | 46061.57 | 46.83 | 2.951 | 3.394 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_MID | 32587.06 | 37475.11 | 38.10 | 2.399 | 2.759 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_TOP | 35709.23 | 41065.61 | 41.75 | 2.653 | 3.051 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00883 | 29.30 | 0.00882 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9739.08 | 11199.94 | 54.02 | 0.724 | 0.832 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00876 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11141.58 | 12812.81 | 97.61 | 0.828 | 0.952 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00865 | 23.97 | 0.00881 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17507.43 | 20133.54 | 97.10 | 1.301 | 1.496 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00865 | 29.14 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12628.36 | 14522.61 | 110.65 | 0.938 | 1.079 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 24.00 | 24.00 | 0.00863 | 28.08 | 0.00882 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7226.09 | 8310.01 | 40.08 | 0.537 | 0.617 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00885 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9282.06 | 10674.37 | 81.32 | 0.690 | 0.793 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00867 | 22.36 | 0.00881 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 14066.73 | 16176.73 | 78.02 | 1.045 | 1.202 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00868 | 29.31 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10403.60 | 11964.15 | 91.15 | 0.773 | 0.889 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00865 | 26.90 | 0.00882 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8156.34 | 9379.79 | 45.24 | 0.606 | 0.697 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00881 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11298.44 | 12993.20 | 98.99 | 0.839 | 0.965 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00864 | 23.35 | 0.00881 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 16000.51 | 18400.59 | 88.75 | 1.189 | 1.367 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00866 | 29.05 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11673.16 | 13424.14 | 102.28 | 0.867 | 0.997 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 27.94 | 0.00882 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5914.72 | 7393.40 | 7.52 | 0.427 | 0.534 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_MID | 14290.45 | 17863.06 | 18.16 | 1.040 | 1.300 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_TOP | 27484.33 | 34355.41 | 34.93 | 2.017 | 2.521 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12088.87 | 15111.09 | 72.88 | 0.891 | 1.114 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7897.95 | 9872.43 | 75.21 | 0.582 | 0.728 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11975.59 | 14969.49 | 72.20 | 0.883 | 1.103 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7826.71 | 9783.39 | 74.54 | 0.577 | 0.721 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9084.05 | 11355.06 | 54.77 | 0.669 | 0.836 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5982.50 | 7478.12 | 56.97 | 0.441 | 0.551 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8972.24 | 11215.30 | 54.09 | 0.660 | 0.826 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5911.00 | 7388.76 | 56.29 | 0.435 | 0.544 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9370.56 | 11713.21 | 56.49 | 0.690 | 0.862 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6169.50 | 7711.87 | 58.75 | 0.454 | 0.568 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9257.56 | 11571.96 | 55.81 | 0.681 | 0.852 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6100.14 | 7625.17 | 58.09 | 0.449 | 0.561 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.05 | 6.05 | 3.29 | 3.29 | 6.0455 | 3.2899 | 6.0455 | 0.5442 | 0.3000 |
PACU_VAV_MID | 5.70 | 5.70 | 4.14 | 4.14 | 5.7017 | 4.1437 | 5.7017 | 0.7267 | 0.3000 |
PACU_VAV_TOP | 6.76 | 6.76 | 6.19 | 6.19 | 6.7645 | 6.1868 | 6.7645 | 0.9146 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17388.775 | 17388.775 | 1.018109 | 0.00015212 | 378.160 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17388.78 | 17388.78 | 1.018109 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9796 | 7393.40 | 0.00 | 17471.78 | 17471.78 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 30627.952 | 30627.952 | 1.300208 | 0.00026795 | 716.865 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 30627.95 | 30627.95 | 1.300208 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 17863.06 | 0.00 | 30768.26 | 30768.26 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 59105.802 | 59105.802 | 2.521028 | 0.00051708 | 1381.581 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 59105.80 | 59105.80 | 2.521028 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 34355.41 | 0.00 | 59376.71 | 59376.71 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 26039.527 | 26039.527 | 1.113706 | 0.00022781 | 608.203 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26039.53 | 25911.86 | 1.113706 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00779193 | 49.6731 | 15111.09 | 0.00 | 26158.91 | 26158.91 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 17013.015 | 17013.015 | 0.727698 | 0.00014884 | 397.363 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17013.01 | 17013.01 | 0.727698 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00778780 | 49.6472 | 9872.43 | 0.00 | 17091.02 | 17091.02 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 25795.054 | 25795.054 | 1.103227 | 0.00022567 | 602.496 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25795.05 | 25795.05 | 1.103227 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00779003 | 49.6612 | 14969.49 | 0.00 | 25913.32 | 25913.32 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 16859.278 | 16859.278 | 0.721108 | 0.00014749 | 393.775 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16859.28 | 16859.28 | 0.721108 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00778594 | 49.6355 | 9783.39 | 0.00 | 16936.58 | 16936.58 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 19558.909 | 19558.909 | 0.835923 | 0.00017111 | 456.928 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19558.91 | 19448.85 | 0.835923 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00784780 | 50.0237 | 11355.06 | 0.00 | 19648.58 | 19648.58 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12882.042 | 12882.042 | 0.550628 | 0.00011270 | 300.935 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12882.04 | 12882.04 | 0.550628 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00784737 | 50.0210 | 7478.12 | 0.00 | 12941.10 | 12941.10 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 19317.571 | 19317.571 | 0.825577 | 0.00016900 | 451.295 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19317.57 | 19317.57 | 0.825577 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00784536 | 50.0084 | 11215.30 | 0.00 | 19406.13 | 19406.13 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12727.730 | 12727.730 | 0.544013 | 0.00011135 | 297.334 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12727.73 | 12727.73 | 0.544013 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00784515 | 50.0071 | 7388.76 | 0.00 | 12786.08 | 12786.08 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 20174.748 | 20174.748 | 0.862322 | 0.00017650 | 471.303 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20174.75 | 20063.06 | 0.862322 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777578 | 49.5711 | 11713.21 | 0.00 | 20267.24 | 20267.24 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 13283.944 | 13283.944 | 0.567858 | 0.00011621 | 310.317 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13283.94 | 13283.94 | 0.567858 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777374 | 49.5584 | 7711.87 | 0.00 | 13344.85 | 13344.85 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 19930.857 | 19930.857 | 0.851866 | 0.00017436 | 465.610 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19930.86 | 19930.86 | 0.851866 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777288 | 49.5529 | 11571.96 | 0.00 | 20022.23 | 20022.23 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 13134.241 | 13134.241 | 0.561440 | 0.00011490 | 306.822 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13134.24 | 13134.24 | 0.561440 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777109 | 49.5417 | 7625.17 | 0.00 | 13194.46 | 13194.46 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 102669.887 | 82172.792 | 6.045465 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 103519.72 | 98235.21 | 6.045465 | 24.85 | 16.79 | 0.00879039 | 11.06 | 11.06 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 15.8152 | 24.00 | 0.00878454 | 46.5957 | 70756.09 | 0.00 | 105866.43 | 82701.79 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 13739.173 | 13739.173 | 1.813640 | 0.00012020 | 240.927 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13739.17 | 13739.17 | 1.813640 | 6.54 | 4.97 | 0.00483182 | 12.89 | 11.51 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 52.7172 | 18.97 | 0.00745213 | 53.8873 | 7650.07 | 0.00 | 14466.57 | 14466.57 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 97360.233 | 77928.458 | 5.701695 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 98216.19 | 92972.44 | 5.701695 | 24.90 | 16.82 | 0.00880561 | 11.06 | 11.06 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 16.7687 | 24.00 | 0.00880241 | 46.6891 | 66732.66 | 0.00 | 100391.47 | 78429.78 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 14623.050 | 14623.050 | 1.710508 | 0.00012793 | 254.959 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14623.05 | 14623.05 | 1.710508 | 5.72 | 4.41 | 0.00472587 | 12.89 | 11.51 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 55.8957 | 17.98 | 0.00757753 | 58.2889 | 8106.82 | 0.00 | 15231.98 | 15231.98 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 113706.522 | 90972.282 | 6.764513 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 114547.95 | 109152.35 | 6.764513 | 24.76 | 16.73 | 0.00876506 | 11.08 | 11.08 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 14.1341 | 24.00 | 0.00875577 | 46.4451 | 79150.69 | 0.00 | 117246.69 | 91558.64 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 12938.693 | 12938.693 | 2.029354 | 0.00011319 | 228.530 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12938.69 | 12938.69 | 2.029354 | 7.54 | 5.87 | 0.00514225 | 12.89 | 11.51 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 47.1135 | 16.46 | 0.00769066 | 65.1562 | 8450.00 | 0.00 | 13808.36 | 13808.36 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17388.775 | 17388.775 | 1.018109 | 0.00015212 | 378.160 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 4.6683 | 4.762217 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17388.78 | 17388.78 | 1.0000 | 1.20848592 | 1.018109 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.15210907 | 60.00 | 32.22 | 27.78 | 0.000 | 17388.78 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.66 | 0.00800000 | 21.00 | 0.00800000 | 50.9796 | 7393.40 | 0.00 | 17471.78 | 17471.78 | 1.20848592 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.98 | 17.01 | 0.00800000 | 47517.4 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 30627.952 | 30627.952 | 1.300208 | 0.00026795 | 716.865 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 8.2225 | 8.387994 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 30627.95 | 30627.95 | 1.0000 | 1.54333440 | 1.300208 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.26791935 | 60.00 | 32.22 | 27.78 | 0.000 | 30627.95 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 17863.06 | 0.00 | 30768.26 | 30768.26 | 1.54333440 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.35 | 18.81 | 0.00800000 | 52996.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 59105.802 | 59105.802 | 2.521028 | 0.00051708 | 1381.581 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 15.8678 | 16.187146 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 59105.80 | 59105.80 | 1.0000 | 2.99243650 | 2.521028 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.51703059 | 60.00 | 32.22 | 27.78 | 0.000 | 59105.80 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 34355.41 | 0.00 | 59376.71 | 59376.71 | 2.99243650 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.26 | 18.78 | 0.00800000 | 52902.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26039.527 | 26039.527 | 1.113706 | 0.00022781 | 608.203 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 6.9907 | 7.131375 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26039.53 | 25911.86 | 1.0000 | 1.32195929 | 1.113706 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.22778190 | 60.00 | 32.22 | 27.78 | 0.000 | 26039.53 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00779193 | 21.00 | 0.00779193 | 49.6731 | 15111.09 | 0.00 | 26158.91 | 26158.91 | 1.32195929 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52847.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17013.015 | 17013.015 | 0.727698 | 0.00014884 | 397.363 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 4.5674 | 4.659308 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17013.01 | 17013.01 | 1.0000 | 0.86377121 | 0.727698 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.14882209 | 60.00 | 32.22 | 27.78 | 0.000 | 17013.01 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778780 | 21.00 | 0.00778780 | 49.6472 | 9872.43 | 0.00 | 17091.02 | 17091.02 | 0.86377121 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52846.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25795.054 | 25795.054 | 1.103227 | 0.00022567 | 602.496 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 6.9251 | 7.064421 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25795.05 | 25795.05 | 1.0000 | 1.30951995 | 1.103227 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.22564337 | 60.00 | 32.22 | 27.78 | 0.000 | 25795.05 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00779003 | 21.00 | 0.00779003 | 49.6612 | 14969.49 | 0.00 | 25913.32 | 25913.32 | 1.30951995 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52848.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16859.278 | 16859.278 | 0.721108 | 0.00014749 | 393.775 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 4.5261 | 4.617205 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16859.28 | 16859.28 | 1.0000 | 0.85594882 | 0.721108 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.14747727 | 60.00 | 32.22 | 27.78 | 0.000 | 16859.28 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778594 | 21.00 | 0.00778594 | 49.6355 | 9783.39 | 0.00 | 16936.58 | 16936.58 | 0.85594882 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52846.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19558.909 | 19558.909 | 0.835923 | 0.00017111 | 456.928 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 5.2509 | 5.356545 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19558.91 | 19448.85 | 1.0000 | 0.99223263 | 0.835923 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.17109241 | 60.00 | 32.22 | 27.78 | 0.000 | 19558.91 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00784780 | 21.00 | 0.00784780 | 50.0237 | 11355.06 | 0.00 | 19648.58 | 19648.58 | 0.99223263 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52862.2 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12882.042 | 12882.042 | 0.550628 | 0.00011270 | 300.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 3.4584 | 3.527970 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12882.04 | 12882.04 | 1.0000 | 0.65359024 | 0.550628 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.11268623 | 60.00 | 32.22 | 27.78 | 0.000 | 12882.04 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00784737 | 21.00 | 0.00784737 | 50.0210 | 7478.12 | 0.00 | 12941.10 | 12941.10 | 0.65359024 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52859.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19317.571 | 19317.571 | 0.825577 | 0.00016900 | 451.295 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 5.1861 | 5.290451 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19317.57 | 19317.57 | 1.0000 | 0.97995215 | 0.825577 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.16898130 | 60.00 | 32.22 | 27.78 | 0.000 | 19317.57 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00784536 | 21.00 | 0.00784536 | 50.0084 | 11215.30 | 0.00 | 19406.13 | 19406.13 | 0.97995215 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52863.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12727.730 | 12727.730 | 0.544013 | 0.00011135 | 297.334 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 3.4169 | 3.485709 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12727.73 | 12727.73 | 1.0000 | 0.64573819 | 0.544013 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.11133637 | 60.00 | 32.22 | 27.78 | 0.000 | 12727.73 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00784515 | 21.00 | 0.00784515 | 50.0071 | 7388.76 | 0.00 | 12786.08 | 12786.08 | 0.64573819 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52860.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20174.748 | 20174.748 | 0.862322 | 0.00017650 | 471.303 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 5.4162 | 5.525203 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20174.75 | 20063.06 | 1.0000 | 1.02356788 | 0.862322 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.17647949 | 60.00 | 32.22 | 27.78 | 0.000 | 20174.75 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777578 | 21.00 | 0.00777578 | 49.5711 | 11713.21 | 0.00 | 20267.24 | 20267.24 | 1.02356788 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52860.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13283.944 | 13283.944 | 0.567858 | 0.00011621 | 310.317 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 3.5663 | 3.638038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13283.94 | 13283.94 | 1.0000 | 0.67404171 | 0.567858 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.11620188 | 60.00 | 32.22 | 27.78 | 0.000 | 13283.94 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777374 | 21.00 | 0.00777374 | 49.5584 | 7711.87 | 0.00 | 13344.85 | 13344.85 | 0.67404171 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52858.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19930.857 | 19930.857 | 0.851866 | 0.00017436 | 465.610 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 5.3507 | 5.458410 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19930.86 | 19930.86 | 1.0000 | 1.01115746 | 0.851866 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.17434605 | 60.00 | 32.22 | 27.78 | 0.000 | 19930.86 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777288 | 21.00 | 0.00777288 | 49.5529 | 11571.96 | 0.00 | 20022.23 | 20022.23 | 1.01115746 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52861.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13134.241 | 13134.241 | 0.561440 | 0.00011490 | 306.822 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 3.5261 | 3.597039 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13134.24 | 13134.24 | 1.0000 | 0.66642411 | 0.561440 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.11489235 | 60.00 | 32.22 | 27.78 | 0.000 | 13134.24 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777109 | 21.00 | 0.00777109 | 49.5417 | 7625.17 | 0.00 | 13194.46 | 13194.46 | 0.66642411 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52858.7 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 102669.887 | 82172.792 | 6.045465 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1809 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.045465 | 7.17591167 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 103519.72 | 98235.21 | 1.0083 | 7.17591167 | 6.045465 | 24.85 | 16.79 | 0.00879039 | 47363.7 | 11.06 | 11.06 | 0.00850000 | 32550.4 | -999.0 | -999.00 | -999.00 | -999.00 | 13372.329 | 90147.39 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 15.8152 | 24.00 | 0.00878454 | 24.00 | 0.00878454 | 46.5957 | 70756.09 | 0.00 | 105866.43 | 82701.79 | 6.89251740 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.94 | 14.27 | 0.00986695 | 39962.8 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 13739.173 | 13739.173 | 1.813640 | 0.00012020 | 240.927 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.045465 | 7.17591167 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 3.6885 | 3.762710 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13739.17 | 13739.17 | 1.0000 | 2.15277350 | 1.813640 | 6.54 | 4.97 | 0.00483182 | 18712.1 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 0.12018402 | 60.00 | 32.22 | 27.78 | 0.000 | 13739.17 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 52.7172 | 18.51 | 0.00721946 | 18.97 | 0.00745213 | 53.8873 | 7650.07 | 0.00 | 14466.57 | 14466.57 | 2.15277350 | 2.80 | 2.80 | 0.00483182 | 14922.8 | 9.43 | 6.53 | 0.00483182 | 21642.8 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97360.233 | 77928.458 | 5.701695 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2092 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.701695 | 6.76785918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 98216.19 | 92972.44 | 1.0088 | 6.76785918 | 5.701695 | 24.90 | 16.82 | 0.00880561 | 47455.1 | 11.06 | 11.06 | 0.00850000 | 32550.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12611.923 | 85604.27 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 16.7687 | 24.00 | 0.00880241 | 24.00 | 0.00880241 | 46.6891 | 66732.66 | 0.00 | 100391.47 | 78429.78 | 6.50057991 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.87 | 14.23 | 0.00986006 | 39878.9 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14623.050 | 14623.050 | 1.710508 | 0.00012793 | 254.959 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.701695 | 6.76785918 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 3.9258 | 4.004775 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14623.05 | 14623.05 | 1.0000 | 2.03035776 | 1.710508 | 5.72 | 4.41 | 0.00472587 | 17618.6 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 0.12791577 | 60.00 | 32.22 | 27.78 | 0.000 | 14623.05 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 55.8957 | 18.30 | 0.00730563 | 17.98 | 0.00757753 | 58.2889 | 8106.82 | 0.00 | 15231.98 | 15231.98 | 2.03035776 | 2.80 | 2.80 | 0.00472587 | 14657.3 | 10.20 | 6.79 | 0.00472587 | 22159.4 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 113706.522 | 90972.282 | 6.764513 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1338 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.764513 | 8.02941446 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 114547.95 | 109152.35 | 1.0074 | 8.02941446 | 6.764513 | 24.76 | 16.73 | 0.00876506 | 47206.7 | 11.08 | 11.08 | 0.00850000 | 32562.3 | -999.0 | -999.00 | -999.00 | -999.00 | 14866.918 | 99681.03 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 14.1341 | 24.00 | 0.00875577 | 24.00 | 0.00875577 | 46.4451 | 79150.69 | 0.00 | 117246.69 | 91558.64 | 7.71231328 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.06 | 14.32 | 0.00987874 | 40119.9 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 12938.693 | 12938.693 | 2.029354 | 0.00011319 | 228.530 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.764513 | 8.02941446 | 4197.9300 | 999.8980 | 3.19408130 | 54.44 | 82.22 | 27.78 | 372488.96 | 3.4736 | 3.543485 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12938.69 | 12938.69 | 1.0000 | 2.40882434 | 2.029354 | 7.54 | 5.87 | 0.00514225 | 20512.6 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 0.11318178 | 60.00 | 32.22 | 27.78 | 0.000 | 12938.69 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 47.1135 | 18.01 | 0.00732654 | 16.46 | 0.00769066 | 65.1562 | 8450.00 | 0.00 | 13808.36 | 13808.36 | 2.40882434 | 2.80 | 2.80 | 0.00514225 | 15700.8 | 8.45 | 6.43 | 0.00514225 | 21433.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.05 | - | |||
PACU_VAV_MID_OA_CONTROLLER | FixedDryBulb | 0.00 | 5.70 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.76 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1972.17 | 2204.50 | 32.67 |
CORE_MID | 1166.33 | 3699.00 | 187.83 |
CORE_TOP | 1527.67 | 4396.00 | 798.00 |
PERIMETER_TOP_ZN_3 | 2322.33 | 4996.50 | 1763.67 |
PERIMETER_TOP_ZN_2 | 2530.00 | 4670.50 | 1620.17 |
PERIMETER_TOP_ZN_1 | 2422.17 | 4516.50 | 1406.50 |
PERIMETER_TOP_ZN_4 | 2451.33 | 4907.50 | 1712.17 |
PERIMETER_BOT_ZN_3 | 1753.33 | 5064.33 | 1349.67 |
PERIMETER_BOT_ZN_2 | 2125.33 | 4612.00 | 1225.67 |
PERIMETER_BOT_ZN_1 | 1941.83 | 4650.83 | 1069.17 |
PERIMETER_BOT_ZN_4 | 2024.33 | 4821.33 | 1276.50 |
PERIMETER_MID_ZN_3 | 1831.50 | 4626.33 | 1141.50 |
PERIMETER_MID_ZN_2 | 1752.33 | 3919.83 | 1038.00 |
PERIMETER_MID_ZN_1 | 2031.00 | 4242.50 | 882.83 |
PERIMETER_MID_ZN_4 | 1953.83 | 4746.67 | 1145.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4261.67 | 5383.17 | 1921.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.00 | 0.00 | 2.00 | 0.00 |
CORE_MID | 2.67 | 0.00 | 2.67 | 0.00 |
CORE_TOP | 5.67 | 0.00 | 5.17 | 0.00 |
PERIMETER_TOP_ZN_3 | 32.17 | 0.00 | 14.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 30.17 | 2.67 | 10.50 | 2.67 |
PERIMETER_TOP_ZN_1 | 20.83 | 4.00 | 7.83 | 4.00 |
PERIMETER_TOP_ZN_4 | 27.67 | 9.00 | 10.00 | 4.83 |
PERIMETER_BOT_ZN_3 | 4.17 | 0.00 | 4.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 2.33 | 0.67 | 2.17 | 0.67 |
PERIMETER_BOT_ZN_1 | 270.83 | 1.50 | 270.83 | 1.50 |
PERIMETER_BOT_ZN_4 | 2.17 | 4.00 | 2.00 | 1.17 |
PERIMETER_MID_ZN_3 | 4.50 | 0.00 | 4.00 | 0.00 |
PERIMETER_MID_ZN_2 | 2.33 | 4.50 | 1.83 | 4.50 |
PERIMETER_MID_ZN_1 | 2.17 | 4.17 | 1.83 | 4.17 |
PERIMETER_MID_ZN_4 | 2.33 | 8.17 | 1.83 | 4.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 303.33 | 31.00 | 282.33 | 22.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.52 | 52.94 | 2698.04 | 1.117 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.52 | 52.94 | 2698.04 | 0.749 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.52 | 52.94 | 2698.04 | 0.747 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 1.180 | 0.078 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.688 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 1.733 | 0.079 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.877 | 0.083 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.924 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 1.468 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 1.440 | 0.852 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 1.594 | 0.044 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 1.000 | 0.065 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 1.671 | 0.073 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 1.700 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.827 | 0.069 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.66 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 17590936.27 | 0.00 | 17590936.27 | 0.00 | 17590936.27 | 13393058.27 | 4646.05 | 72.24 | 4041.72 | 30.62 |
CORE_MID | 11840314.13 | 0.00 | 11840314.13 | 0.00 | 11840314.13 | 13393058.27 | 5513.36 | 53.57 | 3193.07 | 37.31 |
CORE_TOP | 11834322.65 | 0.00 | 11834322.65 | 0.00 | 11834322.65 | 13393058.27 | 5524.53 | 45.16 | 3190.30 | 34.00 |
PERIMETER_TOP_ZN_3 | 3951838.58 | 0.00 | 3951838.58 | 539250.78 | 4491089.36 | 2823374.22 | 4156.32 | 19.64 | 4584.04 | 34.00 |
PERIMETER_TOP_ZN_2 | 3575026.33 | 0.00 | 3575026.33 | 359498.36 | 3934524.69 | 1787429.43 | 4087.16 | 2.43 | 4670.41 | 34.00 |
PERIMETER_TOP_ZN_1 | 5795095.03 | 0.00 | 5795095.03 | 539250.78 | 6334345.81 | 2823374.22 | 4087.86 | 2.40 | 4669.74 | 34.00 |
PERIMETER_TOP_ZN_4 | 3980474.99 | 0.00 | 3980474.99 | 359498.36 | 4339973.35 | 1787312.18 | 4077.58 | 2.92 | 4679.50 | 34.00 |
PERIMETER_BOT_ZN_3 | 3088724.35 | 0.00 | 3088724.35 | 286716.78 | 3375441.12 | 2823374.22 | 4327.16 | 14.26 | 4418.58 | 30.62 |
PERIMETER_BOT_ZN_2 | 3105900.57 | 0.00 | 3105900.57 | 191143.37 | 3297043.94 | 1787429.43 | 4064.17 | 3.68 | 4692.15 | 30.62 |
PERIMETER_BOT_ZN_1 | 4817141.91 | 0.00 | 4817141.91 | 2993637.78 | 7810779.69 | 2823374.22 | 4054.64 | 1.76 | 4703.60 | 30.62 |
PERIMETER_BOT_ZN_4 | 3375104.77 | 0.00 | 3375104.77 | 191143.37 | 3566248.14 | 1787312.18 | 4073.41 | 2.77 | 4683.82 | 30.62 |
PERIMETER_MID_ZN_3 | 3342295.46 | 0.00 | 3342295.46 | 448884.86 | 3791180.32 | 2823374.22 | 4107.86 | 15.78 | 4636.36 | 37.31 |
PERIMETER_MID_ZN_2 | 3323617.53 | 0.00 | 3323617.53 | 299254.78 | 3622872.31 | 1601953.02 | 4021.71 | 0.18 | 4738.11 | 946.31 |
PERIMETER_MID_ZN_1 | 5681357.77 | 0.00 | 5681357.77 | 448884.86 | 6130242.63 | 2823374.22 | 4023.02 | 0.25 | 4736.73 | 37.31 |
PERIMETER_MID_ZN_4 | 3872190.18 | 0.00 | 3872190.18 | 299254.78 | 4171444.96 | 1787312.18 | 4023.21 | 3.54 | 4733.25 | 37.31 |
Total Facility | 89174340.51 | 0.00 | 89174340.51 | 6956418.86 | 96130759.38 | 67658168.57 | 5655.54 | 226.13 | 4775.25 | 968.55 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.8194 | 0.0000 | 0.8194 | 0.0000 | 0.8194 | 0.4247 | 1843.08 | 72.24 | 4027.68 |
CORE_MID | 0.5506 | 0.0000 | 0.5506 | 0.0000 | 0.5506 | 0.4247 | 2714.95 | 53.57 | 3174.49 |
CORE_TOP | 0.5500 | 0.0000 | 0.5500 | 0.0000 | 0.5500 | 0.4247 | 2727.04 | 45.16 | 3170.80 |
PERIMETER_TOP_ZN_3 | 0.1836 | 0.0000 | 0.1836 | 0.0123 | 0.1958 | 0.0895 | 1358.83 | 19.64 | 4564.53 |
PERIMETER_TOP_ZN_2 | 0.1661 | 0.0000 | 0.1661 | 0.0082 | 0.1743 | 0.0567 | 1289.67 | 2.43 | 4650.90 |
PERIMETER_TOP_ZN_1 | 0.2693 | 0.0000 | 0.2693 | 0.0123 | 0.2816 | 0.0895 | 1290.36 | 2.40 | 4650.23 |
PERIMETER_TOP_ZN_4 | 0.1849 | 0.0000 | 0.1849 | 0.0082 | 0.1931 | 0.0567 | 1280.09 | 2.92 | 4659.99 |
PERIMETER_BOT_ZN_3 | 0.1437 | 0.0000 | 0.1437 | 0.0065 | 0.1502 | 0.0895 | 1524.44 | 14.19 | 4404.37 |
PERIMETER_BOT_ZN_2 | 0.1445 | 0.0000 | 0.1445 | 0.0043 | 0.1489 | 0.0567 | 1262.50 | 3.68 | 4676.82 |
PERIMETER_BOT_ZN_1 | 0.2242 | 0.0000 | 0.2242 | 0.1330 | 0.3572 | 0.0895 | 1252.69 | 1.50 | 4688.81 |
PERIMETER_BOT_ZN_4 | 0.1570 | 0.0000 | 0.1570 | 0.0043 | 0.1613 | 0.0567 | 1273.61 | 2.75 | 4666.64 |
PERIMETER_MID_ZN_3 | 0.1553 | 0.0000 | 0.1553 | 0.0102 | 0.1655 | 0.0895 | 1309.98 | 15.78 | 4617.24 |
PERIMETER_MID_ZN_2 | 0.1645 | 0.0000 | 0.1645 | 0.0072 | 0.1717 | 0.0567 | 1224.45 | 0.18 | 3809.37 |
PERIMETER_MID_ZN_1 | 0.2642 | 0.0000 | 0.2642 | 0.0102 | 0.2744 | 0.0895 | 1225.68 | 0.17 | 4717.15 |
PERIMETER_MID_ZN_4 | 0.1799 | 0.0000 | 0.1799 | 0.0068 | 0.1867 | 0.0567 | 1225.93 | 3.50 | 4713.57 |
Total Facility | 4.1572 | 0.0000 | 4.1572 | 0.2235 | 4.3807 | 2.1513 | 2847.49 | 225.65 | 4746.93 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 45055040.29 | 0.00 | 45055040.29 | 22614548.33 | 4053.38 | 0.02 | 4706.59 | 30.62 |
PACU_VAV_MID | 39534739.26 | 0.00 | 39534739.26 | 22429071.92 | 4025.74 | 2.19 | 4732.08 | 37.31 |
PACU_VAV_TOP | 41052150.67 | 0.00 | 41052150.67 | 22614548.33 | 4099.91 | 1.88 | 4658.22 | 34.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 2.0975 | 0.0000 | 2.0975 | 0.7171 | 1251.75 | 0.02 | 4691.23 |
PACU_VAV_MID | 1.8378 | 0.0000 | 1.8378 | 0.7084 | 1227.86 | 2.14 | 4712.99 |
PACU_VAV_TOP | 1.9078 | 0.0000 | 1.9078 | 0.7171 | 1302.41 | 1.88 | 4638.71 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 19.69 | 4351.31 | 0.00 | 0.00 | 0.00 | 356.25 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 23.21 | 3890.67 | 0.00 | 0.00 | 0.00 | 849.32 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 22.09 | 3876.82 | 0.00 | 0.00 | 0.00 | 857.19 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2810 | 2.7882 | 0.0000 | 0.0000 | 0.0000 | 1.1131 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2648 | 2.5669 | 0.0000 | 0.0000 | 0.0000 | 1.1826 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2168 | 2.6821 | 0.0000 | 0.0000 | 0.0000 | 1.1742 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1857.57 | 15934.24 | 12-MAR-17:10 | 192087.47 | 10-AUG-15:50 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 270.58 | 385.65 | 01-JAN-18:20 | 96452.10 | 10-AUG-15:50 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 03-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 03-JAN-08:10 |
ElectricityPurchased:Facility | 1857.57 | 15934.24 | 12-MAR-17:10 | 192087.47 | 10-AUG-15:50 |
ElectricityPurchased:Plant | 1857.57 | 15934.24 | 12-MAR-17:10 | 192087.47 | 10-AUG-15:50 |
Cogeneration:ElectricityPurchased | 1857.57 | 15934.24 | 12-MAR-17:10 | 192087.47 | 10-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 1857.57 | 15934.24 | 12-MAR-17:10 | 192087.47 | 10-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1857.57 | 15934.24 | 12-MAR-17:10 | 192087.47 | 10-AUG-15:50 |
ElectricityNet:Plant | 1857.57 | 15934.24 | 12-MAR-17:10 | 192087.47 | 10-AUG-15:50 |
Cogeneration:ElectricityNet | 1857.57 | 15934.24 | 12-MAR-17:10 | 192087.47 | 10-AUG-15:50 |
General:Cogeneration:ElectricityNet | 1857.57 | 15934.24 | 12-MAR-17:10 | 192087.47 | 10-AUG-15:50 |
Fans:Electricity | 151.47 | 0.00 | 01-JAN-10:40 | 30475.76 | 10-AUG-15:30 |
General:Fans:Electricity | 151.47 | 0.00 | 01-JAN-10:40 | 30475.76 | 10-AUG-15:30 |
ExteriorLights:Electricity | 235.45 | 0.00 | 01-JAN-08:10 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 235.45 | 0.00 | 01-JAN-08:10 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 91.62 | 0.00 | 01-JAN-00:10 | 64742.39 | 10-AUG-16:00 |
General:Cooling:Electricity | 91.62 | 0.00 | 01-JAN-00:10 | 64742.39 | 10-AUG-16:00 |
Electricity:Plant | 56.01 | 0.00 | 01-JAN-18:20 | 6887.32 | 13-FEB-12:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 54.29 | 0.00 | 01-JAN-00:10 | 6518.00 | 13-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 54.29 | 0.00 | 01-JAN-00:10 | 6518.00 | 13-FEB-12:30 |
Pumps:Electricity | 1.72 | 0.00 | 01-JAN-18:20 | 893.29 | 02-JAN-07:00 |
General:Pumps:Electricity | 1.72 | 0.00 | 01-JAN-18:20 | 893.29 | 02-JAN-07:00 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 344.15 | 0.00 | 01-JAN-10:40 | 266214.58 | 02-JAN-06:20 |
NaturalGas:Plant | 344.15 | 0.00 | 01-JAN-10:40 | 266214.58 | 02-JAN-06:20 |
Heating:NaturalGas | 344.15 | 0.00 | 01-JAN-10:40 | 266214.58 | 02-JAN-06:20 |
Boiler:Heating:NaturalGas | 344.15 | 0.00 | 01-JAN-10:40 | 266214.58 | 02-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2004.17 | 0.00 | 01-JAN-18:20 | 531384.56 | 02-JAN-06:20 |
EnergyTransfer:Building | 1133.28 | 0.00 | 01-JAN-10:40 | 185435.14 | 10-AUG-15:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 237.29 | 0.00 | 01-JAN-00:40 | 25930.12 | 10-AUG-16:00 |
Heating:EnergyTransfer | 105.92 | 0.00 | 01-JAN-10:40 | 163214.63 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.08 | 0.00 | 01-JAN-00:10 | 7434.08 | 02-JAN-06:20 |
General:Heating:EnergyTransfer | 105.92 | 0.00 | 01-JAN-10:40 | 163214.63 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.08 | 0.00 | 01-JAN-00:10 | 7434.08 | 02-JAN-06:20 |
Cooling:EnergyTransfer | 1027.36 | 0.00 | 01-JAN-10:30 | 185435.14 | 10-AUG-15:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 237.21 | 0.00 | 01-JAN-00:40 | 25930.12 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer | 1027.36 | 0.00 | 01-JAN-10:30 | 185435.14 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 237.21 | 0.00 | 01-JAN-00:40 | 25930.12 | 10-AUG-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 64.24 | 0.00 | 01-JAN-00:40 | 16440.45 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.67 | 0.00 | 01-JAN-00:40 | 16440.45 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.67 | 0.00 | 01-JAN-00:40 | 16440.45 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.57 | 0.00 | 01-JAN-00:10 | 15907.87 | 10-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.57 | 0.00 | 01-JAN-00:10 | 15907.87 | 10-AUG-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 24.27 | 0.00 | 01-JAN-00:10 | 9939.40 | 02-JAN-08:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.81 | 0.00 | 01-JAN-00:10 | 9939.40 | 02-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.81 | 0.00 | 01-JAN-00:10 | 9939.40 | 02-JAN-08:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.46 | 0.00 | 01-JAN-00:10 | 5119.79 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.46 | 0.00 | 01-JAN-00:10 | 5119.79 | 10-AUG-15:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.06 | 0.00 | 01-JAN-00:40 | 9119.84 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.55 | 0.00 | 01-JAN-00:40 | 9119.84 | 02-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.55 | 0.00 | 01-JAN-00:40 | 9119.84 | 02-JAN-08:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 23.51 | 0.00 | 01-JAN-00:10 | 5604.25 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 23.51 | 0.00 | 01-JAN-00:10 | 5604.25 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 150.83 | 0.00 | 01-JAN-00:10 | 19573.07 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.62 | 0.00 | 01-JAN-00:10 | 16260.05 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.62 | 0.00 | 01-JAN-00:10 | 16260.05 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 150.22 | 0.00 | 01-JAN-00:10 | 19573.07 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 150.22 | 0.00 | 01-JAN-00:10 | 19573.07 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 143.27 | 0.00 | 01-JAN-00:40 | 24786.22 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.34 | 0.00 | 01-JAN-00:40 | 24786.22 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.34 | 0.00 | 01-JAN-00:40 | 24786.22 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 138.93 | 0.00 | 01-JAN-00:10 | 22853.27 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 138.93 | 0.00 | 01-JAN-00:10 | 22853.27 | 10-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 41.22 | 0.00 | 01-JAN-00:40 | 9528.58 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 9.17 | 0.00 | 01-JAN-00:40 | 9528.58 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 9.17 | 0.00 | 01-JAN-00:40 | 9528.58 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.05 | 0.00 | 01-JAN-00:10 | 7326.13 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.05 | 0.00 | 01-JAN-00:10 | 7326.13 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 35.78 | 0.00 | 01-JAN-00:40 | 9149.10 | 10-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.53 | 0.00 | 01-JAN-00:40 | 6826.90 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.53 | 0.00 | 01-JAN-00:40 | 6826.90 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.25 | 0.00 | 01-JAN-00:10 | 9149.10 | 10-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.25 | 0.00 | 01-JAN-00:10 | 9149.10 | 10-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.70 | 0.00 | 01-JAN-00:40 | 14505.91 | 29-AUG-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.23 | 0.00 | 01-JAN-00:40 | 10518.09 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.23 | 0.00 | 01-JAN-00:40 | 10518.09 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 53.46 | 0.00 | 01-JAN-00:10 | 14505.91 | 29-AUG-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 53.46 | 0.00 | 01-JAN-00:10 | 14505.91 | 29-AUG-12:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.83 | 0.00 | 01-JAN-00:40 | 10698.90 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.88 | 0.00 | 01-JAN-00:40 | 7019.12 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.88 | 0.00 | 01-JAN-00:40 | 7019.12 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.95 | 0.00 | 01-JAN-00:10 | 10698.90 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.95 | 0.00 | 01-JAN-00:10 | 10698.90 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 30.70 | 0.00 | 01-JAN-00:40 | 7306.12 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.97 | 0.00 | 01-JAN-00:40 | 7306.12 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.97 | 0.00 | 01-JAN-00:40 | 7306.12 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 26.73 | 0.00 | 01-JAN-00:10 | 5201.72 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 26.73 | 0.00 | 01-JAN-00:10 | 5201.72 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.94 | 0.00 | 01-JAN-00:40 | 7360.21 | 10-AUG-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.40 | 0.00 | 01-JAN-00:40 | 5480.84 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.40 | 0.00 | 01-JAN-00:40 | 5480.84 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.54 | 0.00 | 01-JAN-00:10 | 7360.21 | 10-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.54 | 0.00 | 01-JAN-00:10 | 7360.21 | 10-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 54.10 | 0.00 | 01-JAN-00:40 | 13683.62 | 10-AUG-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 14.92 | 0.00 | 01-JAN-00:40 | 10596.92 | 26-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 14.92 | 0.00 | 01-JAN-00:40 | 10596.92 | 26-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 39.19 | 0.00 | 01-JAN-00:10 | 13683.62 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 39.19 | 0.00 | 01-JAN-00:10 | 13683.62 | 10-AUG-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.12 | 0.00 | 01-JAN-00:40 | 8428.37 | 10-AUG-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.45 | 0.00 | 01-JAN-00:40 | 5671.59 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.45 | 0.00 | 01-JAN-00:40 | 5671.59 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.67 | 0.00 | 01-JAN-00:10 | 8428.37 | 10-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.67 | 0.00 | 01-JAN-00:10 | 8428.37 | 10-AUG-17:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 35.66 | 0.00 | 01-JAN-00:10 | 7502.57 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.34 | 0.00 | 01-JAN-00:10 | 7502.57 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.34 | 0.00 | 01-JAN-00:10 | 7502.57 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 32.33 | 0.00 | 01-JAN-00:10 | 6561.43 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 32.33 | 0.00 | 01-JAN-00:10 | 6561.43 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 32.69 | 0.00 | 01-JAN-00:10 | 9366.11 | 10-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.14 | 0.00 | 01-JAN-00:10 | 5932.68 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.14 | 0.00 | 01-JAN-00:10 | 5932.68 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.56 | 0.00 | 01-JAN-00:10 | 9366.11 | 10-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.56 | 0.00 | 01-JAN-00:10 | 9366.11 | 10-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 59.97 | 0.00 | 01-JAN-00:10 | 14153.37 | 04-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.61 | 0.00 | 01-JAN-00:10 | 8805.79 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.61 | 0.00 | 01-JAN-00:10 | 8805.79 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.37 | 0.00 | 01-JAN-00:10 | 14153.37 | 04-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.37 | 0.00 | 01-JAN-00:10 | 14153.37 | 04-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.59 | 0.00 | 01-JAN-00:10 | 10225.06 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.22 | 0.00 | 01-JAN-00:10 | 5917.61 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.22 | 0.00 | 01-JAN-00:10 | 5917.61 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.37 | 0.00 | 01-JAN-00:10 | 10225.06 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.37 | 0.00 | 01-JAN-00:10 | 10225.06 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 271.25 | 0.00 | 01-JAN-18:20 | 172495.40 | 02-JAN-07:40 |
PlantLoopHeatingDemand:Plant | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
EnergyTransfer:HVAC | 601.33 | 0.00 | 01-JAN-10:40 | 245115.04 | 10-AUG-15:20 |
HeatingCoils:EnergyTransfer | 219.76 | 0.00 | 01-JAN-10:40 | 170446.09 | 02-JAN-06:30 |
PlantLoopHeatingDemand:HVAC | 219.76 | 0.00 | 01-JAN-10:40 | 170446.09 | 02-JAN-06:30 |
HeatingCoils:PlantLoopHeatingDemand | 219.76 | 0.00 | 01-JAN-10:40 | 170446.09 | 02-JAN-06:30 |
CoolingCoils:EnergyTransfer | 381.56 | 0.00 | 01-JAN-00:10 | 245105.34 | 10-AUG-15:20 |
EnergyTransfer:Plant | 269.56 | 0.00 | 01-JAN-18:20 | 197858.06 | 02-JAN-06:20 |
WaterSystems:EnergyTransfer | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
Boilers:EnergyTransfer | 218.07 | 0.00 | 01-JAN-10:40 | 197103.03 | 02-JAN-06:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.078 | -237.210 | 0.000 | 0.000 | 33.012 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -167.667 |
CORE_MID | 0.000 | 0.000 | 0.616 | -150.218 | 0.000 | 0.000 | 34.219 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -111.828 |
CORE_TOP | 0.000 | 0.000 | 4.339 | -138.934 | 0.000 | 0.000 | 35.392 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -128.009 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 9.169 | -32.054 | 0.000 | 0.000 | 7.789 | 23.566 | 24.333 | 12.281 | 0.000 | 0.026 | 0.002 | 0.000 | -37.663 | 0.000 | -6.501 | -0.946 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 5.534 | -30.249 | 0.000 | 0.000 | 4.891 | 14.919 | 15.404 | 25.245 | 0.000 | 0.016 | 0.000 | 0.000 | -24.091 | 0.000 | -4.365 | -7.303 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 7.234 | -53.463 | 0.000 | 0.000 | 7.685 | 23.566 | 24.332 | 55.331 | 0.000 | 0.020 | 0.000 | 0.000 | -36.724 | 0.000 | -6.724 | -21.257 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.882 | -31.950 | 0.000 | 0.000 | 4.979 | 14.918 | 15.403 | 27.630 | 0.000 | 0.014 | 0.000 | 0.000 | -24.906 | 0.000 | -4.407 | -7.562 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 3.972 | -26.730 | 0.000 | 0.000 | 7.710 | 23.566 | 24.333 | 12.624 | 0.000 | 0.015 | 0.001 | 0.000 | -39.746 | 0.000 | -3.703 | -2.039 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.399 | -27.542 | 0.000 | 0.000 | 4.859 | 14.919 | 15.404 | 25.456 | 0.000 | 0.008 | 0.000 | 0.000 | -25.633 | 0.000 | -2.509 | -7.361 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 14.915 | -39.189 | 0.000 | 0.000 | 7.766 | 23.566 | 24.332 | 56.154 | 0.000 | 0.391 | 0.001 | 0.000 | -39.242 | 0.000 | -34.008 | -14.685 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.450 | -28.668 | 0.000 | 0.000 | 4.931 | 14.918 | 15.403 | 28.014 | 0.000 | 0.008 | 0.001 | 0.000 | -26.579 | 0.000 | -2.532 | -7.945 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.336 | -32.328 | 0.000 | 0.000 | 7.617 | 23.566 | 24.333 | 11.812 | 0.000 | 0.022 | 8.356 | 0.000 | -40.850 | 0.000 | -5.863 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.137 | -30.555 | 0.000 | 0.000 | 3.570 | 14.919 | 15.404 | 24.801 | 0.000 | 0.014 | 0.002 | 0.000 | -25.963 | 0.000 | -3.923 | -0.403 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.607 | -57.365 | 0.000 | 0.000 | 7.566 | 23.566 | 24.332 | 54.851 | 0.000 | 0.017 | 0.001 | 0.000 | -39.603 | 0.000 | -6.033 | -9.937 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.218 | -34.369 | 0.000 | 0.000 | 4.922 | 14.918 | 15.403 | 27.454 | 0.000 | 0.012 | 0.237 | 0.000 | -26.849 | 0.000 | -3.945 | -0.000 |
TOPFLOOR_PLENUM | 27.671 | -36.565 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.009 | 18.651 | 0.000 | 0.000 | 0.000 | -9.767 | -0.002 |
MIDFLOOR_PLENUM | 7.812 | -16.460 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.024 | 18.940 | 0.000 | 0.000 | 0.000 | -10.316 | -0.000 |
FIRSTFLOOR_PLENUM | 3.550 | -23.508 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.018 | 28.462 | 0.000 | 0.000 | 0.000 | -8.521 | -0.000 |
Total Facility | 39.034 | -76.534 | 66.885 | -950.824 | 0.000 | 0.000 | 176.906 | 566.263 | 729.266 | 361.653 | 0.000 | 0.614 | 74.652 | 0.000 | -387.849 | 0.000 | -113.117 | -486.945 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 25-AUG-05:12 | 0.00 | 0.00 | 0.00 | -48693.04 | 0.00 | 0.00 | 328.17 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 39546.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 10-AUG-05:12 | 0.00 | 0.00 | 0.00 | -25431.66 | 0.00 | 0.00 | 342.95 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 20978.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | -22853.03 | 0.00 | 0.00 | 3497.11 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 2786.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -7326.17 | 0.00 | 0.00 | 737.22 | 2057.62 | 1435.25 | 3810.76 | 0.00 | 44.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -759.44 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:22 | 0.00 | 0.00 | 0.00 | -11062.24 | 0.00 | 0.00 | 17.23 | 72.37 | 302.86 | 9286.94 | 0.00 | 0.00 | 1571.03 | 0.00 | -0.00 | 0.00 | -188.18 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:42 | 0.00 | 0.00 | 0.00 | -26153.09 | 0.00 | 0.00 | 23.50 | 114.31 | 478.41 | 13816.08 | 0.00 | 0.00 | 11856.96 | 0.00 | -0.00 | 0.00 | -136.18 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-16:42 | 0.00 | 0.00 | 0.00 | -18501.73 | 0.00 | 0.00 | 12.67 | 72.36 | 302.86 | 12533.48 | 0.00 | 0.00 | 5587.84 | 0.00 | -0.00 | 0.00 | -7.49 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -5201.69 | 0.00 | 0.00 | 737.22 | 2057.62 | 1435.25 | 3906.08 | 0.00 | 23.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2958.46 |
PERIMETER_BOT_ZN_2 | 10-AUG-09:10 | 0.00 | 0.00 | 0.00 | -7360.33 | 0.00 | 0.00 | 479.35 | 1302.65 | 908.57 | 11161.76 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2.42 | -6489.59 |
PERIMETER_BOT_ZN_1 | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | -13677.51 | 0.00 | 0.00 | 232.81 | 1143.12 | 797.35 | 4504.43 | 0.00 | 5689.70 | 1310.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-AUG-18:02 | 0.00 | 0.00 | 0.00 | -15409.34 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 9122.24 | 0.00 | 0.00 | 6026.62 | 0.00 | -0.00 | 0.00 | -56.31 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -6561.47 | 0.00 | 0.00 | 737.22 | 2057.62 | 1435.25 | 3849.64 | 0.00 | 37.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1555.66 |
PERIMETER_MID_ZN_2 | 06-AUG-09:22 | 0.00 | 0.00 | 0.00 | -14235.84 | 0.00 | 0.00 | 16.18 | 72.37 | 302.86 | 9245.31 | 0.00 | 0.00 | 4756.85 | 0.00 | -0.00 | 0.00 | -157.74 | 0.00 |
PERIMETER_MID_ZN_1 | 06-AUG-13:22 | 0.00 | 0.00 | 0.00 | -16624.87 | 0.00 | 0.00 | 27.40 | 114.31 | 478.41 | 12032.35 | 0.00 | 0.00 | 4099.40 | 0.00 | -0.00 | 0.00 | -127.01 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-16:42 | 0.00 | 0.00 | 0.00 | -17793.77 | 0.00 | 0.00 | 14.30 | 72.36 | 302.86 | 12166.40 | 0.00 | 0.00 | 5338.35 | 0.00 | -0.00 | 0.00 | -100.49 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:30 | 0.00 | -15907.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.54 | 15881.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-AUG-15:50 | 0.00 | -5119.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.53 | 5087.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 10-AUG-16:00 | 0.00 | -5604.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 | 5582.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-15:30 | 0.00 | -25875.24 | 0.00 | -159558.52 | 0.00 | 0.00 | 17714.92 | 49443.18 | 41937.01 | 71314.97 | 0.00 | 1055.04 | 3968.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:11 | 0.00 | 0.00 | 9002.83 | 0.00 | 0.00 | 0.00 | 503.92 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18325.61 |
CORE_MID | 02-JAN-06:11 | 0.00 | 0.00 | 18238.54 | 0.00 | 0.00 | 0.00 | 526.60 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22875.58 |
CORE_TOP | 17-JAN-05:01 | 0.00 | 0.00 | 27836.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31363.39 |
PERIMETER_TOP_ZN_3 | 17-JAN-05:01 | 0.00 | 0.00 | 11368.79 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2074.47 | 0.00 | -300.52 | -9737.23 |
PERIMETER_TOP_ZN_2 | 17-JAN-05:01 | 0.00 | 0.00 | 8564.61 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1380.70 | 0.00 | -201.46 | -7453.08 |
PERIMETER_TOP_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 13188.24 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2019.00 | 0.00 | -303.13 | -11609.54 |
PERIMETER_TOP_ZN_4 | 17-JAN-05:01 | 0.00 | 0.00 | 9085.48 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1339.37 | 0.00 | -202.16 | -8014.57 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 8244.33 | 0.00 | 0.00 | 0.00 | 113.18 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1438.91 | 0.00 | -77.79 | -7707.32 |
PERIMETER_BOT_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 6526.50 | 0.00 | 0.00 | 0.00 | 71.65 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -991.35 | 0.00 | -52.31 | -6103.04 |
PERIMETER_BOT_ZN_1 | 26-DEC-08:00 | 0.00 | 0.00 | 10596.22 | 0.00 | 0.00 | 0.00 | 230.15 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 4857.09 | 0.00 | -2727.82 | 0.00 | -14279.40 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 6893.50 | 0.00 | 0.00 | 0.00 | 71.65 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -956.68 | 0.00 | -52.44 | -6504.57 |
PERIMETER_MID_ZN_3 | 26-DEC-05:01 | 0.00 | 0.00 | 8591.88 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2398.87 | 0.00 | 0.00 | -6936.44 |
PERIMETER_MID_ZN_2 | 26-DEC-05:01 | 0.00 | 0.00 | 7484.79 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1589.09 | 0.00 | 0.00 | -6366.34 |
PERIMETER_MID_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 10767.08 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2181.91 | 0.00 | -261.49 | -9067.10 |
PERIMETER_MID_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 7546.62 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1591.08 | 0.00 | 0.00 | -6426.16 |
TOPFLOOR_PLENUM | 11-DEC-06:16 | 17573.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -42.28 | -17531.58 |
MIDFLOOR_PLENUM | 02-JAN-06:19 | 10377.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -211.31 | -10166.31 |
FIRSTFLOOR_PLENUM | 02-JAN-08:10 | 9500.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -112.39 | -9388.13 |
Total Facility | 02-JAN-06:11 | 9258.96 | 0.00 | 160856.59 | 0.00 | 0.00 | 0.00 | 2676.37 | 5493.69 | 20036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14655.91 | 0.00 | -2812.71 | -180853.33 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 7.1134 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.0455 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.9509 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7017 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 7.6915 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.7645 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.5567 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.1340 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.4755 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0853 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.8457 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.3074 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3937 | 3.3937 | 1.0181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7588 | 2.7588 | 0.8276 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0510 | 3.0510 | 0.9153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1137 | 1.1137 | 0.3341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9519 | 0.9519 | 0.2856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4958 | 1.4958 | 0.4487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0790 | 1.0790 | 0.3237 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8359 | 0.8359 | 0.2508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7931 | 0.7931 | 0.2379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2019 | 1.2019 | 0.3606 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8889 | 0.8889 | 0.2667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8623 | 0.8623 | 0.2587 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9653 | 0.9653 | 0.2896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3671 | 1.3671 | 0.4101 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9974 | 0.9974 | 0.2992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 7.1134 | 6.0455 | 7.1134 | 2.1340 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.9509 | 5.7017 | 6.9509 | 2.0853 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 7.6915 | 6.7645 | 7.6915 | 2.3074 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6968 | 1.6968 | 1.0181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3794 | 1.3794 | 0.8276 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5255 | 1.5255 | 0.9153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5569 | 0.5569 | 0.3341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4760 | 0.4760 | 0.2856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7479 | 0.7479 | 0.4487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5395 | 0.5395 | 0.3237 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4180 | 0.4180 | 0.2508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3965 | 0.3965 | 0.2379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6009 | 0.6009 | 0.3606 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4444 | 0.4444 | 0.2667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4312 | 0.4312 | 0.2587 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4827 | 0.4827 | 0.2896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6835 | 0.6835 | 0.4101 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4987 | 0.4987 | 0.2992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.5567 | 2.1340 | 2.1340 | 2.1340 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.4755 | 2.0853 | 2.0853 | 2.0853 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.8457 | 2.3074 | 2.3074 | 2.3074 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 282.33 |
Number of hours cooling loads not met | 22.83 |
Number of hours not met | 305.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 344.15 | 266214.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 91.62 | 64742.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 235.45 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 151.47 | 30475.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1.72 | 893.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 54.29 | 6518.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 1857.57 |
Natural Gas | 0.00 | 344.15 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2201.72 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 18.39 |
Fans (All) | 30.40 |
Service Water Heating | 10.90 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 372.84 |
Subtotal | 372.84 |
Natural Gas [MJ/m2] | |
Space Heating | 69.08 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 69.08 |
Subtotal | 69.08 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 25.72 |
Space Heating | 15.63 |
Space Cooling | 4.16 |
Fans (All) | 6.88 |
Service Water Heating | 2.47 |
Receptacle Equipment | 33.12 |
Miscellaneous | 12.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8646.67 | 113.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8715.17 | 44.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8646.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 113.33 | 0.00 | 0.00 | 0.00 |
Average | 8747.18 | 12.82 | 0.00 | 0.00 | 0.00 |
Sum | 157449.17 | 230.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128259.00 | 45.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 45.00 | 0.00 | 0.00 | 0.00 |
Average | 34140.83 | 2.50 | 0.00 | 0.00 | 0.00 |
Sum | 614535.00 | 45.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8572.00 | 188.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8737.33 | 22.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8688.17 | 71.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8572.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 188.00 | 0.00 | 0.00 | 0.00 |
Average | 8737.93 | 22.07 | 0.00 | 0.00 | 0.00 |
Sum | 157282.67 | 397.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128194.33 | 109.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.00 | 7.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128298.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128298.67 | 109.67 | 0.00 | 0.00 | 0.00 |
Average | 34136.56 | 6.78 | 0.00 | 0.00 | 0.00 |
Sum | 614458.00 | 122.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123896E+11 | 13771.22 | 13-JAN-17:00 | 2.20 | 1.77 | 0.183386E+10 | 2606.64 | 27-JAN-14:20 | 9.43 | 7.91 |
February | 0.129621E+11 | 16330.48 | 28-FEB-17:00 | 14.40 | 10.82 | 0.175132E+10 | 2606.66 | 08-FEB-10:20 | 14.40 | 10.82 |
March | 0.178277E+11 | 18650.78 | 02-MAR-17:00 | 12.80 | 8.57 | 0.213916E+10 | 2606.67 | 09-MAR-14:09 | 14.90 | 12.35 |
April | 0.183637E+11 | 27911.20 | 28-APR-05:13 | 11.10 | 9.98 | 0.191034E+10 | 2606.66 | 14-APR-09:20 | 11.10 | 9.98 |
May | 0.230198E+11 | 31428.87 | 08-MAY-05:13 | 9.60 | 9.49 | 0.207612E+10 | 2606.67 | 05-MAY-09:09 | 9.60 | 9.49 |
June | 0.252806E+11 | 36156.75 | 12-JUN-06:03 | 14.60 | 13.50 | 0.207223E+10 | 2606.70 | 05-JUN-13:00 | 14.60 | 13.50 |
July | 0.263571E+11 | 41089.90 | 25-JUL-06:03 | 13.98 | 13.26 | 0.192746E+10 | 2606.65 | 21-JUL-13:20 | 13.98 | 13.26 |
August | 0.288955E+11 | 48702.19 | 25-AUG-05:12 | 17.67 | 15.13 | 0.216182E+10 | 2606.89 | 09-AUG-09:00 | 17.67 | 15.13 |
September | 0.236407E+11 | 44586.95 | 14-SEP-05:12 | 12.43 | 12.07 | 0.191972E+10 | 2606.67 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.194317E+11 | 26706.27 | 10-OCT-05:13 | 12.20 | 11.16 | 0.198763E+10 | 2606.67 | 05-OCT-09:00 | 12.20 | 11.16 |
November | 0.153082E+11 | 18225.29 | 06-NOV-17:00 | 11.70 | 10.80 | 0.194737E+10 | 2606.66 | 03-NOV-09:20 | 11.70 | 10.80 |
December | 0.137344E+11 | 15651.01 | 06-DEC-15:50 | 3.58 | 3.15 | 0.185457E+10 | 2606.67 | 13-DEC-14:20 | 6.90 | 5.05 |
Annual Sum or Average | 0.237211E+12 | 0.235816E+11 | ||||||||
Minimum of Months | 0.123896E+11 | 13771.22 | 2.20 | 1.77 | 0.175132E+10 | 2606.64 | 6.90 | 5.05 | ||
Maximum of Months | 0.288955E+11 | 48702.19 | 17.67 | 15.13 | 0.216182E+10 | 2606.89 | 17.67 | 15.13 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7883528.83 | 650.73 | 20-JAN-14:15 | 6.87 | 4.79 | 0.00 | 0.00 | 01-JAN-00:10 | 6.87 | 4.79 |
February | 0.261191E+09 | 3755.99 | 27-FEB-14:50 | 19.72 | 12.05 | 0.00 | 0.00 | 01-FEB-00:10 | 19.72 | 12.05 |
March | 0.127494E+10 | 5861.47 | 14-MAR-13:40 | 15.20 | 10.17 | 0.00 | 0.00 | 01-MAR-00:10 | 15.20 | 10.17 |
April | 0.297210E+10 | 13125.64 | 27-APR-14:05 | 26.28 | 16.91 | 0.00 | 0.00 | 01-APR-00:10 | 26.28 | 16.91 |
May | 0.503907E+10 | 13717.98 | 04-MAY-14:05 | 23.98 | 15.25 | 0.00 | 0.00 | 01-MAY-00:10 | 23.98 | 15.25 |
June | 0.618314E+10 | 14105.10 | 28-JUN-14:05 | 25.18 | 15.64 | 0.00 | 0.00 | 01-JUN-00:10 | 25.18 | 15.64 |
July | 0.782530E+10 | 15437.24 | 24-JUL-13:50 | 29.22 | 18.16 | 0.00 | 0.00 | 01-JUL-00:10 | 29.22 | 18.16 |
August | 0.745246E+10 | 15907.87 | 10-AUG-14:30 | 29.80 | 19.03 | 0.00 | 0.00 | 01-AUG-00:10 | 29.80 | 19.03 |
September | 0.404225E+10 | 11736.94 | 14-SEP-14:20 | 23.90 | 17.07 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 17.07 |
October | 0.131892E+10 | 7678.59 | 04-OCT-14:00 | 21.10 | 11.41 | 0.00 | 0.00 | 01-OCT-00:10 | 21.10 | 11.41 |
November | 0.179620E+09 | 4429.48 | 04-NOV-13:50 | 21.02 | 15.96 | 0.00 | 0.00 | 01-NOV-00:10 | 21.02 | 15.96 |
December | 8832485.98 | 736.72 | 05-DEC-13:40 | 10.60 | 6.32 | 0.00 | 0.00 | 01-DEC-00:10 | 10.60 | 6.32 |
Annual Sum or Average | 0.365657E+11 | 0.00 | ||||||||
Minimum of Months | 7883528.83 | 650.73 | 6.87 | 4.79 | 0.00 | 0.00 | 6.87 | 4.79 | ||
Maximum of Months | 0.782530E+10 | 15907.87 | 29.80 | 19.03 | 0.00 | 0.00 | 29.80 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40707257.36 | 3196.98 | 14-JAN-06:11 | 2.20 | 1.14 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.14 |
February | 0.208331E+09 | 3230.48 | 11-FEB-06:11 | 3.30 | 1.84 | 0.00 | 0.00 | 01-FEB-00:10 | 3.30 | 1.84 |
March | 0.603314E+09 | 3895.33 | 25-MAR-05:11 | 2.20 | -2.6 | 0.00 | 0.00 | 01-MAR-00:10 | 2.20 | -2.6 |
April | 0.111158E+10 | 3467.90 | 08-APR-06:03 | 6.60 | 5.59 | 0.00 | 0.00 | 01-APR-00:10 | 6.60 | 5.59 |
May | 0.182335E+10 | 2838.51 | 06-MAY-06:05 | 14.60 | 12.60 | 0.00 | 0.00 | 01-MAY-00:10 | 14.60 | 12.60 |
June | 0.254219E+10 | 3785.75 | 28-JUN-16:00 | 26.10 | 16.29 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.29 |
July | 0.317803E+10 | 4483.60 | 31-JUL-16:00 | 28.90 | 19.18 | 0.00 | 0.00 | 01-JUL-00:10 | 28.90 | 19.18 |
August | 0.360047E+10 | 5119.79 | 10-AUG-15:50 | 31.03 | 18.78 | 0.00 | 0.00 | 01-AUG-00:10 | 31.03 | 18.78 |
September | 0.214452E+10 | 3821.74 | 14-SEP-15:50 | 24.32 | 17.03 | 0.00 | 0.00 | 01-SEP-00:10 | 24.32 | 17.03 |
October | 0.903747E+09 | 2949.29 | 31-OCT-05:11 | 8.87 | 8.29 | 0.00 | 0.00 | 01-OCT-00:10 | 8.87 | 8.29 |
November | 0.249302E+09 | 3012.96 | 22-NOV-06:11 | 3.13 | 2.35 | 0.00 | 0.00 | 01-NOV-00:10 | 3.13 | 2.35 |
December | 54836870.35 | 3068.10 | 02-DEC-06:11 | 4.97 | 2.41 | 0.00 | 0.00 | 01-DEC-00:10 | 4.97 | 2.41 |
Annual Sum or Average | 0.164604E+11 | 0.00 | ||||||||
Minimum of Months | 40707257.36 | 2838.51 | 2.20 | -2.6 | 0.00 | 0.00 | 2.20 | -2.6 | ||
Maximum of Months | 0.360047E+10 | 5119.79 | 31.03 | 19.18 | 0.00 | 0.00 | 31.03 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141500E+09 | 3792.76 | 13-JAN-06:11 | 3.13 | 2.22 | 0.00 | 0.00 | 01-JAN-00:10 | 3.13 | 2.22 |
February | 0.421470E+09 | 4206.74 | 10-FEB-06:11 | 2.07 | 1.09 | 0.00 | 0.00 | 01-FEB-00:10 | 2.07 | 1.09 |
March | 0.114842E+10 | 4536.42 | 23-MAR-05:11 | 3.70 | 3.32 | 0.00 | 0.00 | 01-MAR-00:10 | 3.70 | 3.32 |
April | 0.178490E+10 | 4364.45 | 18-APR-05:11 | 3.30 | 2.58 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.58 |
May | 0.272025E+10 | 3541.88 | 08-MAY-06:07 | 9.90 | 9.62 | 0.00 | 0.00 | 01-MAY-00:10 | 9.90 | 9.62 |
June | 0.335627E+10 | 4178.77 | 28-JUN-16:00 | 26.10 | 16.29 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.29 |
July | 0.392081E+10 | 4892.56 | 24-JUL-15:40 | 29.47 | 18.66 | 0.00 | 0.00 | 01-JUL-00:10 | 29.47 | 18.66 |
August | 0.444148E+10 | 5604.25 | 10-AUG-16:00 | 31.20 | 18.74 | 0.00 | 0.00 | 01-AUG-00:10 | 31.20 | 18.74 |
September | 0.304906E+10 | 4617.70 | 14-SEP-15:50 | 24.32 | 17.03 | 0.00 | 0.00 | 01-SEP-00:10 | 24.32 | 17.03 |
October | 0.166307E+10 | 3842.83 | 27-OCT-06:03 | 9.40 | 8.87 | 0.00 | 0.00 | 01-OCT-00:10 | 9.40 | 8.87 |
November | 0.617940E+09 | 3504.55 | 09-NOV-07:03 | 6.70 | 5.68 | 0.00 | 0.00 | 01-NOV-00:10 | 6.70 | 5.68 |
December | 0.243243E+09 | 3751.26 | 07-DEC-06:11 | 4.63 | 2.88 | 0.00 | 0.00 | 01-DEC-00:10 | 4.63 | 2.88 |
Annual Sum or Average | 0.235084E+11 | 0.00 | ||||||||
Minimum of Months | 0.141500E+09 | 3504.55 | 2.07 | 1.09 | 0.00 | 0.00 | 2.07 | 1.09 | ||
Maximum of Months | 0.444148E+10 | 5604.25 | 31.20 | 18.74 | 0.00 | 0.00 | 31.20 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.755224E+10 | 7778.18 | 12-JAN-17:00 | 7.20 | 5.41 | 0.163349E+10 | 2428.52 | 12-JAN-14:00 | 7.20 | 5.41 |
February | 0.804810E+10 | 8996.37 | 28-FEB-17:00 | 14.40 | 10.82 | 0.156105E+10 | 2585.92 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.108240E+11 | 10857.97 | 02-MAR-17:00 | 12.80 | 8.57 | 0.199452E+10 | 2606.64 | 02-MAR-14:30 | 12.80 | 8.57 |
April | 0.114752E+11 | 16492.01 | 27-APR-16:00 | 27.20 | 16.90 | 0.183775E+10 | 2606.67 | 14-APR-09:20 | 27.20 | 16.90 |
May | 0.147677E+11 | 16693.43 | 05-MAY-16:00 | 25.00 | 17.36 | 0.204567E+10 | 2606.67 | 26-MAY-13:20 | 12.77 | 11.65 |
June | 0.167645E+11 | 18058.84 | 21-JUN-16:00 | 25.00 | 16.17 | 0.205553E+10 | 2606.68 | 09-JUN-13:09 | 25.00 | 16.17 |
July | 0.176819E+11 | 18711.43 | 24-JUL-16:00 | 28.90 | 18.57 | 0.191604E+10 | 2606.65 | 11-JUL-09:20 | 28.90 | 18.57 |
August | 0.195187E+11 | 25431.79 | 10-AUG-05:12 | 17.27 | 14.45 | 0.215064E+10 | 2606.82 | 09-AUG-09:00 | 17.27 | 14.45 |
September | 0.148143E+11 | 18275.82 | 14-SEP-16:00 | 24.40 | 17.04 | 0.189568E+10 | 2606.67 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.114362E+11 | 15746.04 | 04-OCT-16:00 | 21.10 | 11.40 | 0.189947E+10 | 2606.67 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.906021E+10 | 8877.61 | 03-NOV-16:00 | 13.30 | 12.93 | 0.175760E+10 | 2594.97 | 06-NOV-14:00 | 11.10 | 10.22 |
December | 0.827515E+10 | 8070.85 | 06-DEC-16:10 | 2.93 | 2.59 | 0.162802E+10 | 2510.77 | 06-DEC-14:00 | 2.93 | 2.59 |
Annual Sum or Average | 0.150218E+12 | 0.223755E+11 | ||||||||
Minimum of Months | 0.755224E+10 | 7778.18 | 2.93 | 2.59 | 0.156105E+10 | 2428.52 | 2.93 | 2.59 | ||
Maximum of Months | 0.195187E+11 | 25431.79 | 28.90 | 18.57 | 0.215064E+10 | 2606.82 | 28.90 | 18.57 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541920E+10 | 7709.42 | 11-JAN-17:00 | 12.20 | 9.27 | 0.152096E+10 | 2252.99 | 11-JAN-14:00 | 12.20 | 9.27 |
February | 0.652179E+10 | 8808.70 | 28-FEB-17:00 | 14.40 | 10.82 | 0.143618E+10 | 2460.25 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.984436E+10 | 9456.81 | 02-MAR-16:50 | 12.88 | 8.54 | 0.182882E+10 | 2553.77 | 02-MAR-14:00 | 12.88 | 8.54 |
April | 0.110929E+11 | 18961.19 | 27-APR-15:30 | 27.20 | 17.10 | 0.173540E+10 | 2606.66 | 27-APR-13:20 | 27.20 | 17.10 |
May | 0.145975E+11 | 19391.56 | 04-MAY-15:40 | 24.07 | 14.71 | 0.198087E+10 | 2606.67 | 26-MAY-13:20 | 12.77 | 11.65 |
June | 0.168123E+11 | 21192.71 | 28-JUN-15:50 | 26.10 | 16.17 | 0.202365E+10 | 2606.69 | 09-JUN-13:09 | 26.10 | 16.17 |
July | 0.181468E+11 | 22012.83 | 24-JUL-15:20 | 30.03 | 18.73 | 0.189615E+10 | 2606.65 | 11-JUL-09:20 | 30.03 | 18.73 |
August | 0.194170E+11 | 22853.27 | 10-AUG-15:30 | 30.70 | 18.83 | 0.212760E+10 | 2606.80 | 09-AUG-09:00 | 30.70 | 18.83 |
September | 0.138706E+11 | 19838.13 | 14-SEP-15:30 | 24.15 | 17.00 | 0.182753E+10 | 2606.65 | 28-SEP-13:20 | 17.20 | 11.88 |
October | 0.102449E+11 | 15534.73 | 04-OCT-16:00 | 21.10 | 11.40 | 0.175160E+10 | 2606.65 | 03-OCT-13:20 | 21.10 | 11.40 |
November | 0.727581E+10 | 8687.92 | 02-NOV-15:40 | 13.30 | 10.98 | 0.158972E+10 | 2425.37 | 02-NOV-13:00 | 13.30 | 10.98 |
December | 0.569132E+10 | 7881.00 | 05-DEC-15:50 | 6.75 | 4.97 | 0.148407E+10 | 2288.93 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.138934E+12 | 0.212026E+11 | ||||||||
Minimum of Months | 0.541920E+10 | 7709.42 | 6.75 | 4.97 | 0.143618E+10 | 2252.99 | 5.00 | 4.36 | ||
Maximum of Months | 0.194170E+11 | 22853.27 | 30.70 | 18.83 | 0.212760E+10 | 2606.80 | 30.70 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252924E+09 | 2180.81 | 11-JAN-15:00 | 14.40 | 10.49 | 0.305141E+09 | 406.78 | 09-JAN-10:50 | 14.40 | 10.49 |
February | 0.681652E+09 | 2685.47 | 27-FEB-16:20 | 19.23 | 12.34 | 0.279755E+09 | 460.83 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.171507E+10 | 2894.00 | 10-MAR-14:50 | 16.20 | 11.59 | 0.344116E+09 | 488.15 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.267939E+10 | 5378.94 | 27-APR-15:20 | 27.20 | 17.16 | 0.328952E+09 | 549.50 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.409813E+10 | 5347.05 | 15-MAY-14:40 | 23.30 | 12.92 | 0.385571E+09 | 549.50 | 22-MAY-13:20 | 16.10 | 10.37 |
June | 0.480882E+10 | 6173.63 | 21-JUN-15:40 | 24.80 | 15.84 | 0.403872E+09 | 549.51 | 09-JUN-13:09 | 24.80 | 15.84 |
July | 0.529523E+10 | 7326.13 | 24-JUL-15:00 | 30.60 | 18.78 | 0.384839E+09 | 549.50 | 21-JUL-13:20 | 30.60 | 18.78 |
August | 0.555848E+10 | 6877.05 | 09-AUG-15:30 | 28.70 | 18.83 | 0.430230E+09 | 549.54 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.374501E+10 | 5059.26 | 14-SEP-15:50 | 24.32 | 17.03 | 0.352476E+09 | 549.50 | 12-SEP-13:00 | 24.32 | 17.03 |
October | 0.209620E+10 | 3287.92 | 04-OCT-15:40 | 21.30 | 11.43 | 0.326438E+09 | 526.64 | 04-OCT-13:00 | 21.30 | 11.43 |
November | 0.849230E+09 | 2575.36 | 02-NOV-14:40 | 13.67 | 11.26 | 0.305340E+09 | 447.35 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.274113E+09 | 2042.22 | 30-DEC-17:02 | 5.60 | 4.81 | 0.294661E+09 | 406.77 | 13-DEC-10:30 | 5.60 | 4.81 |
Annual Sum or Average | 0.320542E+11 | 0.414139E+10 | ||||||||
Minimum of Months | 0.252924E+09 | 2042.22 | 5.60 | 4.81 | 0.279755E+09 | 406.77 | 5.60 | 4.81 | ||
Maximum of Months | 0.555848E+10 | 7326.13 | 30.60 | 18.83 | 0.430230E+09 | 549.54 | 30.60 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223080E+09 | 1719.69 | 28-JAN-17:02 | 6.70 | 5.64 | 0.193221E+09 | 257.54 | 12-JAN-10:39 | 6.70 | 5.64 |
February | 0.677445E+09 | 2233.37 | 27-FEB-15:50 | 19.50 | 12.39 | 0.177179E+09 | 284.59 | 27-FEB-14:00 | 19.50 | 12.39 |
March | 0.166905E+10 | 2798.94 | 14-MAR-10:00 | 10.00 | 7.75 | 0.221894E+09 | 338.26 | 14-MAR-09:00 | 10.00 | 7.75 |
April | 0.266483E+10 | 6663.21 | 27-APR-09:30 | 18.35 | 12.60 | 0.219597E+09 | 347.88 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.371609E+10 | 6597.80 | 15-MAY-09:20 | 17.77 | 12.22 | 0.248796E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.459510E+10 | 9487.63 | 25-JUN-09:12 | 17.07 | 12.34 | 0.260732E+09 | 347.88 | 09-JUN-13:09 | 17.07 | 12.34 |
July | 0.495943E+10 | 8767.71 | 24-JUL-09:00 | 23.90 | 16.63 | 0.246059E+09 | 347.88 | 24-JUL-09:20 | 24.07 | 16.77 |
August | 0.535253E+10 | 11062.88 | 06-AUG-09:22 | 16.20 | 13.22 | 0.275642E+09 | 347.93 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.350734E+10 | 7940.65 | 10-SEP-09:02 | 16.28 | 13.48 | 0.227817E+09 | 347.88 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.190222E+10 | 4441.91 | 04-OCT-09:30 | 16.40 | 10.73 | 0.212071E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.704069E+09 | 2182.21 | 02-NOV-10:40 | 12.43 | 10.47 | 0.192879E+09 | 280.48 | 02-NOV-13:00 | 14.40 | 11.37 |
December | 0.277607E+09 | 1728.26 | 30-DEC-17:02 | 5.60 | 4.81 | 0.186586E+09 | 257.56 | 26-DEC-10:39 | 5.60 | 4.81 |
Annual Sum or Average | 0.302488E+11 | 0.266247E+10 | ||||||||
Minimum of Months | 0.223080E+09 | 1719.69 | 5.60 | 4.81 | 0.177179E+09 | 257.54 | 5.60 | 4.81 | ||
Maximum of Months | 0.535253E+10 | 11062.88 | 23.90 | 16.63 | 0.275642E+09 | 347.93 | 26.10 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101054E+10 | 7106.42 | 20-JAN-13:25 | 6.70 | 4.72 | 0.311302E+09 | 549.50 | 20-JAN-14:30 | 6.95 | 4.83 |
February | 0.180480E+10 | 9048.46 | 27-FEB-14:25 | 19.15 | 11.80 | 0.299261E+09 | 549.50 | 09-FEB-14:30 | 19.15 | 11.80 |
March | 0.351035E+10 | 10413.76 | 14-MAR-13:40 | 15.20 | 10.17 | 0.370167E+09 | 549.50 | 02-MAR-14:30 | 15.20 | 10.17 |
April | 0.456212E+10 | 12926.94 | 27-APR-13:10 | 26.10 | 16.37 | 0.346701E+09 | 549.51 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.591093E+10 | 11052.60 | 04-MAY-13:40 | 23.33 | 15.33 | 0.386345E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.653431E+10 | 10301.88 | 28-JUN-13:05 | 24.50 | 15.71 | 0.396867E+09 | 549.52 | 09-JUN-13:09 | 24.50 | 15.71 |
July | 0.759809E+10 | 19265.47 | 30-JUL-12:02 | 26.10 | 17.31 | 0.378944E+09 | 549.50 | 20-JUL-13:20 | 26.10 | 17.31 |
August | 0.859316E+10 | 14505.91 | 29-AUG-12:30 | 28.65 | 19.74 | 0.426187E+09 | 549.56 | 09-AUG-09:00 | 28.65 | 19.74 |
September | 0.680416E+10 | 26152.46 | 10-SEP-13:42 | 21.93 | 14.56 | 0.359899E+09 | 549.52 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.422414E+10 | 14093.29 | 04-OCT-13:07 | 20.68 | 11.25 | 0.349410E+09 | 549.50 | 03-OCT-13:20 | 20.68 | 11.25 |
November | 0.169734E+10 | 8730.31 | 04-NOV-13:25 | 20.85 | 16.00 | 0.314438E+09 | 549.50 | 15-NOV-14:30 | 9.45 | 6.68 |
December | 0.121342E+10 | 6791.74 | 05-DEC-12:25 | 10.30 | 6.13 | 0.305975E+09 | 549.50 | 05-DEC-14:30 | 10.30 | 6.71 |
Annual Sum or Average | 0.534634E+11 | 0.424550E+10 | ||||||||
Minimum of Months | 0.101054E+10 | 6791.74 | 6.70 | 4.72 | 0.299261E+09 | 549.50 | 6.95 | 4.83 | ||
Maximum of Months | 0.859316E+10 | 26152.46 | 28.65 | 19.74 | 0.426187E+09 | 549.56 | 28.65 | 19.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263301E+09 | 2309.60 | 05-JAN-15:50 | 6.20 | 4.71 | 0.193348E+09 | 264.88 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.674278E+09 | 3726.07 | 27-FEB-15:30 | 19.70 | 12.30 | 0.178978E+09 | 338.69 | 27-FEB-15:00 | 19.40 | 12.42 |
March | 0.161615E+10 | 5521.03 | 14-MAR-16:00 | 17.20 | 10.94 | 0.219234E+09 | 338.69 | 02-MAR-15:20 | 17.20 | 10.94 |
April | 0.264417E+10 | 8683.63 | 26-APR-16:00 | 24.40 | 14.49 | 0.205766E+09 | 347.85 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.408609E+10 | 12907.02 | 07-MAY-16:42 | 21.78 | 16.19 | 0.234624E+09 | 347.85 | 05-MAY-13:00 | 21.78 | 16.19 |
June | 0.466936E+10 | 18130.66 | 18-JUN-16:52 | 17.20 | 12.22 | 0.243498E+09 | 347.85 | 28-JUN-13:20 | 24.60 | 15.70 |
July | 0.559881E+10 | 18504.66 | 30-JUL-16:42 | 26.88 | 17.94 | 0.234656E+09 | 347.85 | 20-JUL-13:20 | 26.88 | 17.94 |
August | 0.563518E+10 | 13523.43 | 12-AUG-17:05 | 24.38 | 16.49 | 0.261469E+09 | 347.86 | 15-AUG-13:20 | 24.50 | 15.97 |
September | 0.385696E+10 | 18312.43 | 10-SEP-16:22 | 22.20 | 14.33 | 0.216220E+09 | 347.85 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.191565E+10 | 6856.70 | 04-OCT-16:00 | 21.10 | 11.40 | 0.205958E+09 | 347.80 | 04-OCT-13:00 | 21.10 | 11.40 |
November | 0.673181E+09 | 2979.08 | 04-NOV-15:40 | 20.37 | 15.93 | 0.193293E+09 | 291.39 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.316835E+09 | 2463.96 | 05-DEC-15:30 | 8.05 | 5.82 | 0.186928E+09 | 276.69 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.319499E+11 | 0.257397E+10 | ||||||||
Minimum of Months | 0.263301E+09 | 2309.60 | 6.20 | 4.71 | 0.178978E+09 | 264.88 | 6.10 | 4.61 | ||
Maximum of Months | 0.563518E+10 | 18504.66 | 26.88 | 17.94 | 0.261469E+09 | 347.86 | 26.88 | 17.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305891E+09 | 1691.71 | 11-JAN-15:00 | 14.40 | 10.49 | 0.306153E+09 | 414.69 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.627544E+09 | 1972.82 | 28-FEB-15:00 | 13.90 | 10.81 | 0.280877E+09 | 456.17 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.146882E+10 | 2073.61 | 10-MAR-14:40 | 16.30 | 11.68 | 0.344712E+09 | 472.53 | 10-MAR-14:50 | 16.20 | 11.59 |
April | 0.208530E+10 | 2821.08 | 27-APR-16:00 | 27.20 | 16.90 | 0.326157E+09 | 544.07 | 27-APR-13:00 | 27.20 | 16.90 |
May | 0.306235E+10 | 3468.39 | 05-MAY-15:30 | 24.70 | 17.20 | 0.388312E+09 | 549.49 | 15-MAY-13:20 | 22.97 | 13.71 |
June | 0.350379E+10 | 4287.48 | 21-JUN-15:40 | 24.80 | 15.84 | 0.411599E+09 | 549.50 | 09-JUN-13:20 | 24.80 | 15.84 |
July | 0.394771E+10 | 5201.72 | 24-JUL-15:00 | 30.60 | 18.78 | 0.393728E+09 | 549.50 | 12-JUL-13:20 | 30.60 | 18.78 |
August | 0.435348E+10 | 5167.72 | 09-AUG-15:30 | 28.70 | 18.83 | 0.441860E+09 | 549.53 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.315983E+10 | 3821.73 | 14-SEP-15:50 | 24.32 | 17.03 | 0.370957E+09 | 549.49 | 05-SEP-13:20 | 24.32 | 17.03 |
October | 0.235170E+10 | 2463.23 | 04-OCT-15:40 | 21.30 | 11.43 | 0.345067E+09 | 529.17 | 04-OCT-13:00 | 21.30 | 11.43 |
November | 0.135194E+10 | 2069.29 | 02-NOV-14:02 | 14.22 | 11.35 | 0.315280E+09 | 470.74 | 02-NOV-13:00 | 14.22 | 11.35 |
December | 0.512197E+09 | 1675.67 | 29-DEC-13:50 | 11.10 | 9.04 | 0.296296E+09 | 411.97 | 29-DEC-14:20 | 10.93 | 8.95 |
Annual Sum or Average | 0.267306E+11 | 0.422100E+10 | ||||||||
Minimum of Months | 0.305891E+09 | 1675.67 | 11.10 | 9.04 | 0.280877E+09 | 411.97 | 10.93 | 8.95 | ||
Maximum of Months | 0.435348E+10 | 5201.72 | 30.60 | 18.83 | 0.441860E+09 | 549.53 | 30.60 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264373E+09 | 1460.96 | 28-JAN-17:02 | 6.70 | 5.64 | 0.193828E+09 | 257.53 | 03-JAN-14:09 | 6.70 | 5.64 |
February | 0.644274E+09 | 1782.72 | 27-FEB-15:50 | 19.50 | 12.39 | 0.177922E+09 | 279.11 | 27-FEB-14:00 | 19.50 | 12.39 |
March | 0.153089E+10 | 2144.89 | 14-MAR-10:05 | 10.28 | 7.92 | 0.221528E+09 | 317.90 | 14-MAR-09:00 | 10.28 | 7.92 |
April | 0.228718E+10 | 4806.26 | 27-APR-09:30 | 18.35 | 12.60 | 0.218011E+09 | 347.88 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.303541E+10 | 5241.66 | 15-MAY-09:40 | 18.33 | 12.73 | 0.248792E+09 | 347.88 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.377585E+10 | 5979.20 | 28-JUN-09:30 | 20.00 | 13.97 | 0.263547E+09 | 347.88 | 09-JUN-13:09 | 20.00 | 13.97 |
July | 0.415230E+10 | 7119.80 | 24-JUL-09:10 | 23.98 | 16.70 | 0.249304E+09 | 347.88 | 24-JUL-09:20 | 24.07 | 16.77 |
August | 0.475177E+10 | 7360.49 | 10-AUG-09:10 | 22.62 | 17.13 | 0.280444E+09 | 347.93 | 09-AUG-09:00 | 22.62 | 17.13 |
September | 0.330872E+10 | 5675.97 | 14-SEP-09:30 | 17.75 | 15.56 | 0.235044E+09 | 347.88 | 12-SEP-13:00 | 17.75 | 15.56 |
October | 0.220873E+10 | 3763.45 | 04-OCT-09:30 | 16.40 | 10.73 | 0.220898E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.110548E+10 | 1949.45 | 02-NOV-10:40 | 12.43 | 10.47 | 0.196741E+09 | 289.79 | 02-NOV-09:00 | 12.43 | 10.47 |
December | 0.477393E+09 | 1653.11 | 05-DEC-10:20 | 7.23 | 5.22 | 0.187681E+09 | 267.76 | 05-DEC-10:30 | 7.50 | 5.28 |
Annual Sum or Average | 0.275424E+11 | 0.269374E+10 | ||||||||
Minimum of Months | 0.264373E+09 | 1460.96 | 6.70 | 5.22 | 0.177922E+09 | 257.53 | 6.70 | 5.28 | ||
Maximum of Months | 0.475177E+10 | 7360.49 | 23.98 | 17.13 | 0.280444E+09 | 347.93 | 26.10 | 17.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422871E+09 | 3283.66 | 20-JAN-13:50 | 6.70 | 4.72 | 0.299948E+09 | 504.37 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.104189E+10 | 5373.64 | 27-FEB-15:00 | 20.00 | 12.17 | 0.286451E+09 | 549.50 | 27-FEB-14:30 | 20.00 | 12.17 |
March | 0.211255E+10 | 5004.86 | 01-MAR-14:40 | 12.77 | 7.03 | 0.353288E+09 | 549.50 | 02-MAR-14:30 | 13.30 | 8.35 |
April | 0.296054E+10 | 9564.99 | 27-APR-13:40 | 26.10 | 16.65 | 0.329959E+09 | 549.51 | 27-APR-13:20 | 26.10 | 16.65 |
May | 0.393122E+10 | 7963.84 | 14-MAY-14:30 | 23.05 | 12.36 | 0.371387E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.450202E+10 | 7511.07 | 28-JUN-13:40 | 24.80 | 15.68 | 0.387807E+09 | 549.51 | 09-JUN-13:09 | 24.80 | 15.68 |
July | 0.566652E+10 | 11042.92 | 31-JUL-16:10 | 28.80 | 19.11 | 0.380364E+09 | 549.50 | 20-JUL-13:20 | 28.80 | 19.11 |
August | 0.722029E+10 | 13683.62 | 10-AUG-16:10 | 31.30 | 18.74 | 0.430754E+09 | 549.56 | 09-AUG-09:00 | 31.30 | 18.74 |
September | 0.552997E+10 | 11508.57 | 14-SEP-13:50 | 23.72 | 17.23 | 0.365301E+09 | 549.51 | 12-SEP-13:00 | 23.72 | 17.23 |
October | 0.364406E+10 | 11766.94 | 04-OCT-13:30 | 20.85 | 11.31 | 0.351583E+09 | 549.51 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.137785E+10 | 6567.90 | 04-NOV-13:40 | 20.93 | 15.98 | 0.310562E+09 | 537.57 | 15-NOV-14:09 | 9.82 | 6.80 |
December | 0.779284E+09 | 4178.87 | 05-DEC-12:00 | 10.00 | 6.07 | 0.297336E+09 | 543.74 | 05-DEC-14:50 | 10.10 | 6.91 |
Annual Sum or Average | 0.391891E+11 | 0.416474E+10 | ||||||||
Minimum of Months | 0.422871E+09 | 3283.66 | 6.70 | 4.72 | 0.286451E+09 | 504.37 | 6.78 | 4.76 | ||
Maximum of Months | 0.722029E+10 | 13683.62 | 31.30 | 19.11 | 0.430754E+09 | 549.56 | 31.30 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280343E+09 | 1884.76 | 05-JAN-15:50 | 6.20 | 4.71 | 0.193924E+09 | 263.30 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.636006E+09 | 2555.69 | 27-FEB-15:50 | 19.50 | 12.39 | 0.178917E+09 | 324.27 | 27-FEB-15:00 | 19.40 | 12.42 |
March | 0.148246E+10 | 2894.98 | 02-MAR-16:30 | 13.05 | 8.47 | 0.217642E+09 | 338.68 | 02-MAR-16:00 | 12.80 | 8.57 |
April | 0.221928E+10 | 5570.97 | 26-APR-17:00 | 24.40 | 13.95 | 0.204363E+09 | 347.85 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.333132E+10 | 11295.02 | 14-MAY-17:42 | 22.30 | 11.98 | 0.237826E+09 | 347.85 | 15-MAY-13:20 | 22.97 | 13.71 |
June | 0.378898E+10 | 6786.82 | 28-JUN-16:00 | 26.10 | 16.29 | 0.248826E+09 | 347.85 | 28-JUN-13:20 | 26.10 | 16.29 |
July | 0.462902E+10 | 14769.34 | 23-JUL-18:01 | 25.82 | 15.89 | 0.243736E+09 | 347.85 | 21-JUL-13:20 | 25.82 | 15.89 |
August | 0.486219E+10 | 15409.08 | 06-AUG-18:02 | 23.47 | 15.22 | 0.272178E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.357872E+10 | 7034.65 | 11-SEP-16:00 | 23.30 | 16.14 | 0.227582E+09 | 347.85 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.229795E+10 | 5909.90 | 04-OCT-16:00 | 21.10 | 11.40 | 0.212360E+09 | 347.79 | 04-OCT-13:00 | 21.10 | 11.40 |
November | 0.109251E+10 | 2483.38 | 04-NOV-15:40 | 20.37 | 15.93 | 0.195736E+09 | 293.76 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.469534E+09 | 2110.17 | 05-DEC-15:30 | 8.05 | 5.82 | 0.188170E+09 | 283.45 | 05-DEC-15:39 | 7.40 | 5.40 |
Annual Sum or Average | 0.286683E+11 | 0.262126E+10 | ||||||||
Minimum of Months | 0.280343E+09 | 1884.76 | 6.20 | 4.71 | 0.178917E+09 | 263.30 | 6.10 | 4.61 | ||
Maximum of Months | 0.486219E+10 | 15409.08 | 26.10 | 16.29 | 0.272178E+09 | 347.88 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523844E+09 | 1894.75 | 11-JAN-16:00 | 14.40 | 10.49 | 0.306766E+09 | 435.67 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.984955E+09 | 2281.90 | 28-FEB-15:00 | 13.90 | 10.81 | 0.285405E+09 | 493.03 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.212311E+10 | 2404.45 | 10-MAR-14:40 | 16.30 | 11.68 | 0.360780E+09 | 513.29 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.268547E+10 | 4858.32 | 27-APR-16:00 | 27.20 | 16.90 | 0.347653E+09 | 549.50 | 27-APR-13:20 | 27.20 | 16.90 |
May | 0.373937E+10 | 5102.72 | 05-MAY-15:30 | 24.70 | 17.20 | 0.408275E+09 | 549.51 | 05-MAY-09:20 | 24.70 | 17.20 |
June | 0.433651E+10 | 5641.99 | 21-JUN-15:40 | 24.80 | 15.84 | 0.422182E+09 | 549.51 | 09-JUN-13:09 | 24.80 | 15.84 |
July | 0.480962E+10 | 6561.43 | 24-JUL-15:00 | 30.60 | 18.78 | 0.397590E+09 | 549.50 | 14-JUL-09:20 | 30.60 | 18.78 |
August | 0.513740E+10 | 6244.59 | 09-AUG-15:30 | 28.70 | 18.83 | 0.445307E+09 | 549.54 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.354112E+10 | 4783.36 | 14-SEP-15:50 | 24.32 | 17.03 | 0.376939E+09 | 549.50 | 06-SEP-13:20 | 24.32 | 17.03 |
October | 0.244334E+10 | 3113.27 | 04-OCT-15:30 | 21.40 | 11.45 | 0.350321E+09 | 549.47 | 04-OCT-13:00 | 21.40 | 11.45 |
November | 0.134689E+10 | 2218.47 | 02-NOV-14:30 | 13.85 | 11.29 | 0.315923E+09 | 482.09 | 02-NOV-13:00 | 13.85 | 11.29 |
December | 0.656474E+09 | 1805.86 | 29-DEC-14:10 | 11.02 | 9.00 | 0.296473E+09 | 423.22 | 29-DEC-14:20 | 10.93 | 8.95 |
Annual Sum or Average | 0.323281E+11 | 0.431361E+10 | ||||||||
Minimum of Months | 0.523844E+09 | 1805.86 | 11.02 | 9.00 | 0.285405E+09 | 423.22 | 10.93 | 8.95 | ||
Maximum of Months | 0.513740E+10 | 6561.43 | 30.60 | 18.83 | 0.445307E+09 | 549.54 | 30.60 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335023E+09 | 2405.13 | 20-JAN-11:03 | 5.60 | 3.32 | 0.143056E+09 | 305.69 | 20-JAN-11:09 | 5.60 | 3.32 |
February | 0.741192E+09 | 3324.81 | 27-FEB-15:02 | 19.90 | 12.22 | 0.134022E+09 | 355.32 | 27-FEB-15:09 | 19.90 | 12.22 |
March | 0.173777E+10 | 5034.32 | 02-MAR-13:02 | 12.38 | 7.47 | 0.170534E+09 | 356.46 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.267806E+10 | 7649.11 | 27-APR-10:05 | 19.27 | 13.13 | 0.166461E+09 | 356.46 | 20-APR-10:09 | 19.27 | 13.13 |
May | 0.364692E+10 | 8698.76 | 14-MAY-09:42 | 18.53 | 12.07 | 0.187279E+09 | 356.47 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.446575E+10 | 8220.17 | 28-JUN-10:05 | 21.20 | 14.55 | 0.194724E+09 | 356.46 | 27-JUN-14:09 | 21.20 | 14.55 |
July | 0.476209E+10 | 9956.11 | 30-JUL-09:02 | 20.87 | 15.88 | 0.183860E+09 | 356.46 | 07-JUL-12:09 | 20.87 | 15.88 |
August | 0.519402E+10 | 14237.59 | 06-AUG-09:22 | 16.20 | 13.22 | 0.205910E+09 | 356.51 | 09-AUG-10:09 | 23.92 | 16.01 |
September | 0.356103E+10 | 11244.80 | 10-SEP-09:52 | 17.20 | 13.54 | 0.173153E+09 | 356.46 | 11-SEP-10:09 | 19.08 | 14.37 |
October | 0.209147E+10 | 5953.69 | 04-OCT-10:05 | 17.48 | 10.97 | 0.163422E+09 | 356.46 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.897395E+09 | 3490.41 | 04-NOV-10:02 | 16.38 | 13.96 | 0.146256E+09 | 356.44 | 02-NOV-10:09 | 16.38 | 13.96 |
December | 0.444446E+09 | 2568.94 | 05-DEC-11:02 | 8.58 | 5.53 | 0.138914E+09 | 317.93 | 05-DEC-11:09 | 8.58 | 5.53 |
Annual Sum or Average | 0.305552E+11 | 0.200759E+10 | ||||||||
Minimum of Months | 0.335023E+09 | 2405.13 | 5.60 | 3.32 | 0.134022E+09 | 305.69 | 5.60 | 3.32 | ||
Maximum of Months | 0.519402E+10 | 14237.59 | 21.20 | 15.88 | 0.205910E+09 | 356.51 | 23.92 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139821E+10 | 7917.54 | 20-JAN-13:13 | 6.70 | 4.72 | 0.315955E+09 | 549.50 | 20-JAN-14:20 | 6.87 | 4.79 |
February | 0.233051E+10 | 9384.35 | 27-FEB-14:25 | 19.15 | 11.80 | 0.306241E+09 | 549.50 | 09-FEB-14:30 | 19.15 | 11.80 |
March | 0.422825E+10 | 10633.57 | 01-MAR-13:40 | 11.33 | 6.09 | 0.380968E+09 | 549.50 | 02-MAR-14:30 | 13.30 | 8.35 |
April | 0.493445E+10 | 12338.55 | 27-APR-13:10 | 26.10 | 16.37 | 0.356773E+09 | 549.51 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.601166E+10 | 10580.58 | 14-MAY-12:32 | 21.83 | 12.33 | 0.398747E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.637713E+10 | 9630.24 | 28-JUN-13:05 | 24.50 | 15.71 | 0.408926E+09 | 549.51 | 09-JUN-13:09 | 24.50 | 15.71 |
July | 0.733886E+10 | 12227.53 | 31-JUL-13:10 | 27.38 | 18.36 | 0.388170E+09 | 549.50 | 21-JUL-13:20 | 27.38 | 18.36 |
August | 0.844398E+10 | 16624.11 | 06-AUG-13:22 | 22.15 | 15.53 | 0.436826E+09 | 549.56 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.712305E+10 | 15033.07 | 10-SEP-13:13 | 21.13 | 14.29 | 0.372924E+09 | 549.51 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.501208E+10 | 14230.55 | 04-OCT-13:10 | 20.68 | 11.25 | 0.362145E+09 | 549.81 | 04-OCT-13:50 | 21.02 | 11.37 |
November | 0.240788E+10 | 9091.38 | 04-NOV-13:25 | 20.85 | 16.00 | 0.324411E+09 | 549.50 | 15-NOV-14:30 | 9.45 | 6.68 |
December | 0.175960E+10 | 8087.54 | 05-DEC-12:25 | 10.30 | 6.13 | 0.312860E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.573657E+11 | 0.436495E+10 | ||||||||
Minimum of Months | 0.139821E+10 | 7917.54 | 6.70 | 4.72 | 0.306241E+09 | 549.50 | 6.87 | 4.79 | ||
Maximum of Months | 0.844398E+10 | 16624.11 | 27.38 | 18.36 | 0.436826E+09 | 549.81 | 27.38 | 18.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460721E+09 | 2295.23 | 05-JAN-15:50 | 6.20 | 4.71 | 0.194160E+09 | 277.41 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.935326E+09 | 3727.10 | 27-FEB-15:30 | 19.70 | 12.30 | 0.181107E+09 | 339.02 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.208749E+10 | 5353.31 | 14-MAR-16:00 | 17.20 | 10.94 | 0.222552E+09 | 346.47 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.292522E+10 | 8306.29 | 26-APR-16:00 | 24.40 | 14.49 | 0.210213E+09 | 347.85 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.418013E+10 | 17707.41 | 07-MAY-16:32 | 21.87 | 16.22 | 0.241774E+09 | 347.85 | 15-MAY-13:20 | 22.97 | 13.71 |
June | 0.459455E+10 | 8953.79 | 28-JUN-16:00 | 26.10 | 16.29 | 0.250762E+09 | 347.85 | 28-JUN-13:20 | 26.10 | 16.29 |
July | 0.542681E+10 | 15262.58 | 23-JUL-16:52 | 26.70 | 15.58 | 0.241033E+09 | 347.85 | 21-JUL-13:20 | 26.70 | 15.58 |
August | 0.552841E+10 | 17792.59 | 06-AUG-16:42 | 23.47 | 15.19 | 0.269252E+09 | 347.86 | 15-AUG-13:20 | 24.50 | 15.97 |
September | 0.407202E+10 | 8837.44 | 11-SEP-16:00 | 23.30 | 16.14 | 0.224583E+09 | 347.85 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.245338E+10 | 6893.39 | 04-OCT-16:00 | 21.10 | 11.40 | 0.211508E+09 | 347.82 | 04-OCT-13:00 | 21.10 | 11.40 |
November | 0.111971E+10 | 2857.90 | 04-NOV-15:40 | 20.37 | 15.93 | 0.195537E+09 | 304.99 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.585870E+09 | 2471.86 | 05-DEC-15:30 | 8.05 | 5.82 | 0.188340E+09 | 291.46 | 05-DEC-15:39 | 7.40 | 5.40 |
Annual Sum or Average | 0.343696E+11 | 0.263082E+10 | ||||||||
Minimum of Months | 0.460721E+09 | 2295.23 | 6.20 | 4.71 | 0.181107E+09 | 277.41 | 6.10 | 4.61 | ||
Maximum of Months | 0.552841E+10 | 17792.59 | 26.70 | 16.29 | 0.269252E+09 | 347.86 | 26.70 | 16.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78441654.81 | 9002.83 | 02-JAN-06:11 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 78441654.81 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 78441654.81 | 9002.83 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.674609E+10 | 17467.60 | 09-JAN-06:09 | -1.5 |
February | 0.426527E+10 | 17011.95 | 13-FEB-06:16 | 2.40 |
March | 0.251734E+10 | 15040.75 | 06-MAR-06:16 | 6.70 |
April | 0.131913E+10 | 10516.48 | 19-APR-05:03 | 1.78 |
May | 0.646063E+09 | 7992.07 | 11-MAY-05:03 | 5.10 |
June | 0.300130E+09 | 6826.76 | 19-JUN-05:03 | 11.20 |
July | 0.183117E+09 | 6445.50 | 07-JUL-05:03 | 11.47 |
August | 0.252667E+09 | 6030.46 | 21-AUG-05:03 | 11.20 |
September | 0.627035E+09 | 7920.60 | 10-SEP-07:48 | 14.03 |
October | 0.171466E+10 | 8728.20 | 16-OCT-05:13 | 7.03 |
November | 0.337331E+10 | 17301.78 | 24-NOV-06:16 | 1.83 |
December | 0.572645E+10 | 17573.80 | 11-DEC-06:16 | 4.60 |
Annual Sum or Average | 0.276713E+11 | |||
Minimum of Months | 0.183117E+09 | 6030.46 | -1.5 | |
Maximum of Months | 0.674609E+10 | 17573.80 | 14.03 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235235E+10 | 10377.62 | 02-JAN-06:19 | 6.10 |
February | 0.129300E+10 | 8873.88 | 21-FEB-07:08 | 1.60 |
March | 0.703060E+09 | 3896.61 | 06-MAR-07:08 | 6.70 |
April | 0.295432E+09 | 4437.46 | 02-APR-11:52 | 17.20 |
May | 59545745.36 | 5046.59 | 29-MAY-15:46 | 16.02 |
June | 15198487.99 | 3515.86 | 18-JUN-15:06 | 18.80 |
July | 18490807.95 | 4336.03 | 02-JUL-13:25 | 19.45 |
August | 10835883.08 | 3784.49 | 06-AUG-15:22 | 23.75 |
September | 46631448.10 | 3955.42 | 10-SEP-13:53 | 22.20 |
October | 0.328859E+09 | 4525.55 | 29-OCT-12:32 | 10.93 |
November | 0.994386E+09 | 4322.07 | 13-NOV-07:03 | 1.52 |
December | 0.169401E+10 | 9160.75 | 26-DEC-07:18 | -1.5 |
Annual Sum or Average | 0.781180E+10 | |||
Minimum of Months | 10835883.08 | 3515.86 | -1.5 | |
Maximum of Months | 0.235235E+10 | 10377.62 | 23.75 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152748E+10 | 9500.38 | 02-JAN-08:10 | 6.70 |
February | 0.593128E+09 | 4409.21 | 21-FEB-08:20 | 1.47 |
March | 0.146878E+09 | 2586.09 | 06-MAR-08:08 | 6.78 |
April | 24123694.12 | 1986.78 | 19-APR-07:08 | 4.18 |
May | 11160992.82 | 3456.90 | 29-MAY-16:55 | 16.70 |
June | 11073114.75 | 3473.79 | 25-JUN-14:42 | 21.60 |
July | 11794221.47 | 3166.79 | 09-JUL-14:42 | 20.13 |
August | 9948855.74 | 3044.12 | 06-AUG-15:25 | 23.75 |
September | 9708180.23 | 4148.49 | 04-SEP-16:12 | 17.60 |
October | 40739475.99 | 3401.98 | 08-OCT-11:32 | 16.87 |
November | 0.334339E+09 | 2509.28 | 24-NOV-08:08 | 1.97 |
December | 0.829864E+09 | 4443.56 | 26-DEC-09:10 | -0.9 |
Annual Sum or Average | 0.355023E+10 | |||
Minimum of Months | 9708180.23 | 1986.78 | -0.9 | |
Maximum of Months | 0.152748E+10 | 9500.38 | 23.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418725E+09 | 18238.54 | 02-JAN-06:11 | 6.10 |
February | 73846423.95 | 14655.47 | 21-FEB-06:01 | 1.70 |
March | 7665796.03 | 12166.78 | 06-MAR-07:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 16952726.18 | 12258.69 | 13-NOV-07:01 | 1.52 |
December | 98329585.00 | 14950.55 | 26-DEC-06:02 | -0.8 |
Annual Sum or Average | 0.615520E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.418725E+09 | 18238.54 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166959E+10 | 27836.82 | 17-JAN-05:01 | 1.60 |
February | 0.747899E+09 | 26782.80 | 21-FEB-05:51 | 1.70 |
March | 0.241552E+09 | 23704.54 | 06-MAR-06:11 | 6.70 |
April | 44637477.91 | 19934.90 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 67873053.46 | 21176.26 | 16-OCT-05:11 | 7.03 |
November | 0.471494E+09 | 24898.37 | 13-NOV-05:11 | 1.30 |
December | 0.109638E+10 | 27399.41 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.433943E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.166959E+10 | 27836.82 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291526E+10 | 11368.79 | 17-JAN-05:01 | 1.60 |
February | 0.168731E+10 | 11278.25 | 19-FEB-07:23 | -5.0 |
March | 0.649536E+09 | 10746.59 | 06-MAR-06:11 | 6.70 |
April | 0.241477E+09 | 9633.62 | 18-APR-05:11 | 3.30 |
May | 38138682.87 | 8658.16 | 18-MAY-05:12 | 5.60 |
June | 4532930.76 | 5770.69 | 14-JUN-06:03 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 459008.99 | 964.72 | 03-AUG-06:03 | 11.82 |
September | 23337692.07 | 6822.67 | 28-SEP-06:03 | 8.40 |
October | 0.282478E+09 | 9827.74 | 16-OCT-05:11 | 7.03 |
November | 0.105905E+10 | 11125.58 | 13-NOV-05:11 | 1.30 |
December | 0.226769E+10 | 11029.04 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.916927E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.291526E+10 | 11368.79 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180124E+10 | 8564.61 | 17-JAN-05:01 | 1.60 |
February | 0.979893E+09 | 8427.55 | 13-FEB-05:11 | 1.47 |
March | 0.352688E+09 | 8075.75 | 06-MAR-06:11 | 6.70 |
April | 0.116332E+09 | 7162.04 | 18-APR-05:11 | 3.30 |
May | 25502681.46 | 6357.65 | 18-MAY-05:12 | 5.60 |
June | 4412006.64 | 3689.59 | 14-JUN-06:03 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 1015348.41 | 2234.29 | 18-AUG-06:03 | 11.63 |
September | 14174920.38 | 4358.89 | 28-SEP-06:03 | 8.40 |
October | 0.173302E+09 | 7332.23 | 16-OCT-05:11 | 7.03 |
November | 0.661171E+09 | 8368.75 | 13-NOV-05:11 | 1.30 |
December | 0.140444E+10 | 8267.71 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.553417E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.180124E+10 | 8564.61 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228562E+10 | 13188.24 | 17-JAN-05:01 | 1.60 |
February | 0.118684E+10 | 12742.27 | 13-FEB-05:11 | 1.47 |
March | 0.520233E+09 | 12389.32 | 06-MAR-06:11 | 6.70 |
April | 0.226133E+09 | 10972.70 | 18-APR-05:11 | 3.30 |
May | 49164365.91 | 9738.22 | 18-MAY-05:12 | 5.60 |
June | 11105641.96 | 5724.41 | 14-JUN-06:03 | 10.10 |
July | 255286.91 | 1152.50 | 18-JUL-06:03 | 13.17 |
August | 3908559.08 | 3333.94 | 03-AUG-06:03 | 11.82 |
September | 23398064.10 | 6778.94 | 28-SEP-06:03 | 8.40 |
October | 0.229339E+09 | 11143.43 | 16-OCT-05:11 | 7.03 |
November | 0.866182E+09 | 12785.07 | 13-NOV-05:11 | 1.30 |
December | 0.183158E+10 | 12752.70 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.723377E+10 | |||
Minimum of Months | 255286.91 | 1152.50 | -0.6 | |
Maximum of Months | 0.228562E+10 | 13188.24 | 13.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185737E+10 | 9085.48 | 17-JAN-05:01 | 1.60 |
February | 0.103109E+10 | 8898.66 | 13-FEB-05:11 | 1.47 |
March | 0.419555E+09 | 8552.45 | 06-MAR-06:11 | 6.70 |
April | 0.166451E+09 | 7546.41 | 18-APR-05:11 | 3.30 |
May | 34795164.45 | 6661.23 | 18-MAY-05:12 | 5.60 |
June | 8045823.00 | 3587.35 | 14-JUN-06:03 | 10.10 |
July | 359732.74 | 1617.36 | 18-JUL-06:03 | 13.17 |
August | 3507025.66 | 2737.48 | 18-AUG-06:03 | 11.63 |
September | 18820157.69 | 4318.39 | 28-SEP-06:03 | 8.40 |
October | 0.190534E+09 | 7659.54 | 16-OCT-05:11 | 7.03 |
November | 0.693839E+09 | 8824.00 | 13-NOV-05:11 | 1.30 |
December | 0.145774E+10 | 8756.49 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.588210E+10 | |||
Minimum of Months | 359732.74 | 1617.36 | -0.6 | |
Maximum of Months | 0.185737E+10 | 9085.48 | 13.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173579E+10 | 8244.32 | 02-JAN-06:11 | 6.10 |
February | 0.825699E+09 | 7919.26 | 21-FEB-05:51 | 1.70 |
March | 0.231180E+09 | 7047.76 | 06-MAR-06:11 | 6.70 |
April | 64841388.81 | 6508.82 | 18-APR-05:11 | 3.30 |
May | 3945976.04 | 4951.26 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 377320.94 | 1342.46 | 28-SEP-06:03 | 8.40 |
October | 22348304.99 | 5915.18 | 30-OCT-06:03 | 7.20 |
November | 0.216530E+09 | 6792.36 | 24-NOV-06:11 | 1.83 |
December | 0.870940E+09 | 7813.81 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.397165E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.173579E+10 | 8244.32 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107213E+10 | 6526.50 | 02-JAN-06:11 | 6.10 |
February | 0.446253E+09 | 6125.81 | 21-FEB-05:51 | 1.70 |
March | 0.111352E+09 | 5469.32 | 06-MAR-06:11 | 6.70 |
April | 30003316.37 | 4993.51 | 18-APR-05:11 | 3.30 |
May | 4781395.82 | 3689.50 | 18-MAY-06:03 | 5.68 |
June | 93427.95 | 350.15 | 14-JUN-06:03 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 1037416.61 | 2798.28 | 28-SEP-06:03 | 8.40 |
October | 17786884.59 | 4318.42 | 28-OCT-06:03 | 7.80 |
November | 0.142770E+09 | 5272.90 | 24-NOV-06:11 | 1.83 |
December | 0.572706E+09 | 6162.95 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.239892E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.107213E+10 | 6526.50 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364409E+10 | 10379.58 | 06-JAN-08:00 | -2.8 |
February | 0.213540E+10 | 9803.88 | 21-FEB-08:00 | 1.10 |
March | 0.155049E+10 | 9286.55 | 01-MAR-07:10 | -0.1 |
April | 0.913008E+09 | 8957.97 | 18-APR-06:10 | 3.40 |
May | 0.589741E+09 | 7832.20 | 18-MAY-06:10 | 5.68 |
June | 0.309341E+09 | 6900.41 | 15-JUN-06:03 | 9.60 |
July | 79325699.14 | 4492.96 | 10-JUL-06:07 | 12.88 |
August | 84877114.41 | 5287.54 | 18-AUG-06:03 | 11.63 |
September | 0.266005E+09 | 7080.91 | 28-SEP-06:10 | 8.40 |
October | 0.768143E+09 | 7694.89 | 16-OCT-06:50 | 6.20 |
November | 0.179729E+10 | 9494.79 | 24-NOV-07:10 | 1.20 |
December | 0.277741E+10 | 10596.92 | 26-DEC-08:00 | -1.1 |
Annual Sum or Average | 0.149151E+11 | |||
Minimum of Months | 79325699.14 | 4492.96 | -2.8 | |
Maximum of Months | 0.364409E+10 | 10596.92 | 12.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109141E+10 | 6893.49 | 02-JAN-06:11 | 6.10 |
February | 0.452082E+09 | 6381.74 | 21-FEB-05:51 | 1.70 |
March | 0.134615E+09 | 5766.80 | 06-MAR-06:11 | 6.70 |
April | 41348107.32 | 5217.59 | 18-APR-05:11 | 3.30 |
May | 6192813.34 | 3719.24 | 18-MAY-06:03 | 5.68 |
June | 200063.28 | 499.46 | 07-JUN-06:03 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 991210.75 | 2617.55 | 28-SEP-06:03 | 8.40 |
October | 18424550.48 | 4429.50 | 28-OCT-06:03 | 7.80 |
November | 0.142431E+09 | 5490.89 | 24-NOV-06:11 | 1.83 |
December | 0.562266E+09 | 6476.51 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.244996E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.109141E+10 | 6893.49 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136604E+10 | 8541.71 | 17-JAN-05:01 | 1.60 |
February | 0.573131E+09 | 8386.22 | 21-FEB-05:51 | 1.70 |
March | 0.145288E+09 | 7407.13 | 06-MAR-06:11 | 6.70 |
April | 38227591.59 | 6677.92 | 18-APR-05:11 | 3.30 |
May | 1619790.49 | 4926.18 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 1024561.75 | 2750.57 | 28-SEP-06:03 | 8.40 |
October | 39294594.06 | 6662.92 | 30-OCT-05:11 | 7.20 |
November | 0.308782E+09 | 7485.81 | 13-NOV-06:01 | 1.70 |
December | 0.862690E+09 | 8591.90 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.333610E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.136604E+10 | 8591.90 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.861419E+09 | 7387.97 | 17-JAN-05:01 | 1.60 |
February | 0.345301E+09 | 7213.54 | 21-FEB-05:51 | 1.70 |
March | 85248915.65 | 6260.63 | 06-MAR-06:11 | 6.70 |
April | 24151444.48 | 5488.68 | 18-APR-05:11 | 3.30 |
May | 4497185.65 | 3639.05 | 18-MAY-06:03 | 5.68 |
June | 403840.05 | 1595.32 | 14-JUN-06:03 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 2604026.83 | 3368.10 | 28-SEP-06:03 | 8.40 |
October | 33853003.80 | 5442.33 | 16-OCT-05:11 | 7.03 |
November | 0.207698E+09 | 6319.35 | 24-NOV-06:11 | 1.83 |
December | 0.571605E+09 | 7484.88 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.213678E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.861419E+09 | 7484.88 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105046E+10 | 10767.04 | 17-JAN-05:01 | 1.60 |
February | 0.400654E+09 | 10192.53 | 21-FEB-05:51 | 1.70 |
March | 0.116989E+09 | 9077.40 | 06-MAR-06:11 | 6.70 |
April | 43467253.72 | 8001.94 | 18-APR-05:11 | 3.30 |
May | 7160658.23 | 5762.55 | 18-MAY-06:03 | 5.68 |
June | 456832.38 | 1294.95 | 14-JUN-06:03 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 2664510.26 | 5097.93 | 28-SEP-06:03 | 8.40 |
October | 38933699.49 | 7822.65 | 16-OCT-05:11 | 7.03 |
November | 0.242792E+09 | 9095.53 | 24-NOV-06:11 | 1.83 |
December | 0.703242E+09 | 10675.93 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.260682E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.105046E+10 | 10767.04 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.884776E+09 | 7467.45 | 17-JAN-05:01 | 1.60 |
February | 0.356606E+09 | 7218.76 | 21-FEB-05:51 | 1.70 |
March | 0.106415E+09 | 6325.24 | 06-MAR-06:11 | 6.70 |
April | 34563638.43 | 5554.59 | 18-APR-05:11 | 3.30 |
May | 6633207.36 | 3714.29 | 18-MAY-06:03 | 5.68 |
June | 567667.04 | 1435.67 | 14-JUN-06:03 | 10.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 2747385.14 | 3310.39 | 28-SEP-06:03 | 8.40 |
October | 34831867.83 | 5410.54 | 16-OCT-05:11 | 7.03 |
November | 0.215552E+09 | 6343.20 | 24-NOV-06:11 | 1.83 |
December | 0.574845E+09 | 7546.71 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.221754E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.884776E+09 | 7546.71 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789407E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702729E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675848E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2136672.83 | 0.651639E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69525.64 | 0.526384E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 470253.49 | 0.445912E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10505611.35 | 0.376848E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12886913.91 | 0.299502E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63637.36 | 0.238758E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528918E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.63 | 0.602925E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661837E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26132706.19 | 0.650071E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238758E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12886913.91 | 0.789407E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524839E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472148E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452394E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1371496.20 | 0.441236E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35685.43 | 0.355213E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 342362.45 | 0.302908E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6019942.68 | 0.253783E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8023878.03 | 0.203327E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37516.02 | 0.161802E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356247E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400997E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440510E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15830880.81 | 0.436540E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161802E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8023878.03 | 0.524839E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802643E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743847E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704641E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1351242.83 | 0.677219E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42717.87 | 0.539194E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 493555.09 | 0.449592E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6762846.62 | 0.381427E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10855503.55 | 0.306826E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43154.43 | 0.254057E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563845E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619752E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680779E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19549020.40 | 0.672382E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254057E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10855503.55 | 0.802643E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525926E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475675E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457127E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 693417.62 | 0.443950E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66413.89 | 0.363113E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 327805.45 | 0.301279E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4630777.04 | 0.262630E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7981153.29 | 0.206504E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28778.17 | 0.166487E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359840E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402899E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441801E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13728345.46 | 0.440723E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166487E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7981153.29 | 0.525926E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448825E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400127E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380337E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1381198.77 | 0.357507E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142009.95 | 0.288134E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 280873.24 | 0.245157E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6243116.59 | 0.208104E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7235893.24 | 0.168959E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37553.33 | 0.138138E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314973E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361706E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390576E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15320645.11 | 0.370254E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138138E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7235893.24 | 0.448825E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298613E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270255E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256841E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 772003.14 | 0.246302E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36170.88 | 0.197822E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 190843.34 | 0.171230E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3259089.69 | 0.142394E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4203199.36 | 0.117671E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20893.27 | 94415320.01 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213022E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240359E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260081E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8482199.67 | 0.250900E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94415320.01 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4203199.36 | 0.298613E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429974E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372460E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386179E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14672581.27 | 0.288528E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1739960.18 | 0.246727E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16102133.96 | 0.187703E+10 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96464296.00 | 0.123785E+10 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258864E+09 | 0.116261E+10 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3517984.60 | 0.176100E+10 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289698E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371741E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411671E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391361E+09 | 0.340083E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116261E+10 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258864E+09 | 0.429974E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299345E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271259E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258708E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 422155.52 | 0.246105E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58281.97 | 0.202932E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 195044.41 | 0.168581E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2546443.69 | 0.150999E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4304346.02 | 0.120324E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17440.06 | 97751435.04 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214160E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241128E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260806E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7543711.67 | 0.253210E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97751435.04 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4304346.02 | 0.299345E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697811E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627490E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611700E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1770809.92 | 0.585830E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43675.25 | 0.472217E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 400558.67 | 0.397833E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8809130.32 | 0.336385E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10460437.97 | 0.272243E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43084.09 | 0.219285E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488913E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552747E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600216E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21527696.21 | 0.586267E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219285E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10460437.97 | 0.697811E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463942E+09 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423565E+09 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411010E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1157365.81 | 0.395780E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48003.91 | 0.314641E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 319174.19 | 0.266323E+09 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5888196.90 | 0.223828E+09 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6963508.66 | 0.181737E+09 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36345.99 | 0.146340E+09 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328387E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367785E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399562E+09 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14412595.45 | 0.392290E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146340E+09 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6963508.66 | 0.463942E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713848E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667806E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634344E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1188069.55 | 0.603524E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38092.66 | 0.477351E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 426303.36 | 0.396984E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6052850.76 | 0.337678E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9105683.67 | 0.275289E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38401.13 | 0.228513E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514197E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565835E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617845E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16849401.13 | 0.603321E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228513E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9105683.67 | 0.713848E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464773E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424579E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410918E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 594155.80 | 0.394859E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56659.43 | 0.321167E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 284459.89 | 0.265761E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3987363.94 | 0.232350E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6659690.70 | 0.185320E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25608.02 | 0.149724E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327930E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367363E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400100E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11607937.77 | 0.394484E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149724E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6659690.70 | 0.464773E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100436E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921464E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893704E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1514884.26 | 0.843268E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3029.99 | 0.673219E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186158.88 | 0.562200E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6621188.96 | 0.476078E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9262093.21 | 0.393167E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.49 | 0.321953E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729040E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817898E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885041E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17588120.79 | 0.852140E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321953E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9262093.21 | 0.100436E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120855E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110362E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108442E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2399784.86 | 0.103398E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4620.20 | 0.834639E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247279.87 | 0.700465E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9463536.00 | 0.590928E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12381894.62 | 0.485430E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1443.33 | 0.391762E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865704E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965904E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105099E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24498558.88 | 0.103164E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391762E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12381894.62 | 0.120855E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113794E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104405E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100704E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 980316.45 | 0.997472E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828920E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12376.70 | 0.703344E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1791967.41 | 0.593353E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6356654.36 | 0.459715E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367766E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794998E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876318E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955831E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9141314.92 | 0.976674E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367766E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6356654.36 | 0.113794E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1349.34 | 12-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1270.04 | 16-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1112.37 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.62 | 01-APR-17:02 | 1266.00 | 10-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 14-MAY-15:00 | 892.24 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28-JUN-16:00 | 1164.46 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.36 | 23-JUL-16:00 | 576.93 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.31 | 13-AUG-14:50 | 869.78 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 14-SEP-17:00 | 546.16 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1166.80 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 04-NOV-14:13 | 1268.46 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1048.17 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.16 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 288.36 | 1349.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 898.24 | 12-JAN-22:03 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 845.89 | 16-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 746.84 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.74 | 01-APR-17:02 | 842.47 | 10-APR-21:03 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 05-MAY-16:00 | 588.85 | 22-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 28-JUN-16:00 | 767.82 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.39 | 23-JUL-16:00 | 396.66 | 02-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.47 | 13-AUG-17:30 | 578.89 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 14-SEP-17:00 | 359.49 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 776.90 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 844.61 | 29-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 698.01 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.49 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 183.74 | 898.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1349.09 | 12-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1270.13 | 16-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1156.38 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.07 | 01-APR-17:30 | 1267.16 | 10-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 05-MAY-16:00 | 889.08 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 28-JUN-16:00 | 1150.63 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.64 | 23-JUL-16:00 | 582.23 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.06 | 13-AUG-17:30 | 879.66 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 14-SEP-17:00 | 546.66 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1166.33 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1267.90 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1048.85 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.66 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 247.64 | 1349.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 897.84 | 12-JAN-22:03 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 845.47 | 16-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 742.89 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.51 | 01-APR-17:30 | 844.97 | 10-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 06-MAY-13:00 | 589.04 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 28-JUN-16:00 | 756.04 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.20 | 23-JUL-14:00 | 389.08 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.81 | 13-AUG-12:10 | 593.75 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 | 14-SEP-17:00 | 359.44 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 776.21 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 844.35 | 29-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 698.17 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.44 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 157.20 | 897.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 757.67 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 689.96 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 632.65 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.83 | 01-APR-17:02 | 676.35 | 10-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 | 14-MAY-15:50 | 515.07 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 28-JUN-16:00 | 688.10 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.34 | 23-JUL-15:50 | 341.72 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.57 | 13-AUG-15:10 | 496.47 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 14-SEP-17:00 | 325.97 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 627.51 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 732.02 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 575.09 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.97 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 168.83 | 757.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 501.44 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 456.54 | 16-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 436.27 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 | 01-APR-17:02 | 465.73 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 06-MAY-15:00 | 339.22 | 18-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 28-JUN-16:00 | 466.92 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.01 | 23-JUL-16:10 | 225.73 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 13-AUG-15:10 | 344.15 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 14-SEP-17:00 | 212.84 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 417.74 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 484.83 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 381.60 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.84 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 | 501.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 19187.29 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 17681.20 | 09-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 17266.13 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2399.67 | 27-APR-16:10 | 14905.50 | 19-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 509.46 | 05-MAY-16:10 | 11914.07 | 18-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2158.27 | 28-JUN-17:00 | 9124.76 | 01-JUN-06:10 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3822.96 | 31-JUL-16:10 | 7636.94 | 03-JUL-06:05 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6068.92 | 10-AUG-17:00 | 8435.16 | 01-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 804.65 | 14-SEP-17:00 | 9824.12 | 27-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11751.50 | 13-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16166.86 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18648.13 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7636.94 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6068.92 | 19187.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 500.43 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 454.28 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 427.73 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.06 | 01-APR-17:02 | 452.28 | 10-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 06-MAY-13:00 | 338.37 | 18-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 28-JUN-16:00 | 446.60 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 | 23-JUL-13:50 | 234.66 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.80 | 13-AUG-12:30 | 355.78 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 14-SEP-17:00 | 216.23 | 30-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 417.70 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 483.23 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 382.19 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.23 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 | 500.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1176.05 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1074.94 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1019.99 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.62 | 01-APR-17:02 | 1083.88 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 14-MAY-15:20 | 802.90 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 28-JUN-16:00 | 1074.71 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.17 | 23-JUL-16:00 | 535.10 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.63 | 13-AUG-15:10 | 778.02 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 14-SEP-17:00 | 505.49 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 981.01 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1116.94 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 892.92 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.49 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 227.17 | 1176.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 777.62 | 12-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 710.34 | 16-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 684.45 | 28-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.45 | 01-APR-17:02 | 725.08 | 07-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 14-MAY-16:00 | 527.85 | 18-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 28-JUN-16:00 | 706.29 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.02 | 23-JUL-15:40 | 354.85 | 02-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.12 | 13-AUG-15:10 | 516.99 | 11-AUG-04:00 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 14-SEP-17:00 | 329.24 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 652.86 | 31-OCT-21:03 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 739.01 | 29-NOV-23:00 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 591.25 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.24 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 161.02 | 777.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1174.66 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1156.53 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1053.88 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.86 | 01-APR-17:02 | 1094.66 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 | 05-MAY-16:00 | 795.51 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 28-JUN-16:00 | 1061.92 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.79 | 23-JUL-16:00 | 537.75 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.02 | 13-AUG-17:50 | 785.82 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 14-SEP-17:00 | 501.66 | 30-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 979.93 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1114.67 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 897.84 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.66 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 191.79 | 1174.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 774.78 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 708.05 | 16-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 678.65 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 01-APR-17:50 | 711.31 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 06-MAY-13:00 | 527.17 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 28-JUN-16:00 | 698.30 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.84 | 23-JUL-13:52 | 358.91 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.00 | 13-AUG-12:30 | 530.03 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 14-SEP-17:00 | 330.05 | 30-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 652.00 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 736.18 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 592.34 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.05 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 137.84 | 774.78 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1740.15 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1607.38 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1517.56 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.44 | 01-APR-17:02 | 1581.50 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 05-MAY-16:00 | 1186.75 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 28-JUN-15:00 | 1585.02 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.89 | 23-JUL-15:52 | 789.80 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.62 | 13-AUG-14:52 | 1112.26 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 14-SEP-17:00 | 733.51 | 30-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1380.31 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1637.33 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1314.85 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.44 | 1740.15 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2124.39 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1942.06 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1858.56 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.70 | 01-APR-17:02 | 1970.68 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 05-MAY-16:00 | 1453.36 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 28-JUN-15:00 | 1964.28 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.58 | 23-JUL-14:00 | 964.07 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.41 | 13-AUG-14:52 | 1402.10 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 14-SEP-17:00 | 891.33 | 30-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1679.77 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1981.71 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1608.84 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 891.33 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.70 | 2124.39 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1943.94 | 12-JAN-22:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1804.44 | 16-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1578.53 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.55 | 01-APR-17:02 | 1858.61 | 10-APR-21:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1284.15 | 17-MAY-21:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 28-JUN-17:00 | 1646.93 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.39 | 24-JUL-14:30 | 929.14 | 04-JUL-15:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 | 08-AUG-17:00 | 1235.03 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 788.06 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1695.05 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1843.95 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1572.20 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.06 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.55 | 1943.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13771.22 | 13-JAN-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16330.48 | 28-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18650.78 | 02-MAR-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27911.20 | 28-APR-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31428.87 | 08-MAY-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36156.75 | 12-JUN-06:03 | 3811.58 | 9760.61 | 31425.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41089.90 | 25-JUL-06:03 | 5082.11 | 13014.15 | 41900.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 48702.19 | 25-AUG-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44586.95 | 14-SEP-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26706.27 | 10-OCT-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18225.29 | 06-NOV-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15651.01 | 06-DEC-15:50 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13771.22 | 1905.79 | 3253.54 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48702.19 | 6035.01 | 13014.15 | 41900.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 650.73 | 20-JAN-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.16 |
February | 3755.99 | 27-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.03 |
March | 5861.47 | 14-MAR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.61 |
April | 13125.64 | 27-APR-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
May | 13717.98 | 04-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.45 |
June | 14105.10 | 28-JUN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 |
July | 15437.24 | 24-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 | 0.00 |
August | 15907.87 | 10-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.54 | 0.00 |
September | 11736.94 | 14-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 |
October | 7678.59 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.06 |
November | 4429.48 | 04-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 736.72 | 05-DEC-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 650.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15907.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 | 111.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3196.98 | 14-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.94 |
February | 3230.48 | 11-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.41 |
March | 3895.33 | 25-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.60 |
April | 3467.90 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.56 |
May | 2838.51 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.43 |
June | 3785.75 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 0.00 |
July | 4483.60 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 0.00 |
August | 5119.79 | 10-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.53 | 0.00 |
September | 3821.74 | 14-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 |
October | 2949.29 | 31-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.54 |
November | 3012.96 | 22-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.73 |
December | 3068.10 | 02-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2838.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5119.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 362.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3792.76 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.04 |
February | 4206.74 | 10-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.29 |
March | 4536.42 | 23-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.82 |
April | 4364.45 | 18-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.53 |
May | 3541.88 | 08-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.09 |
June | 4178.77 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 0.00 |
July | 4892.56 | 24-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 0.00 |
August | 5604.25 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 | 0.00 |
September | 4617.70 | 14-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
October | 3842.83 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.67 |
November | 3504.55 | 09-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.45 |
December | 3751.26 | 07-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3504.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5604.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 279.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7778.18 | 12-JAN-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8996.37 | 28-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10857.97 | 02-MAR-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16492.01 | 27-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16693.43 | 05-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18058.84 | 21-JUN-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18711.43 | 24-JUL-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25431.79 | 10-AUG-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18275.82 | 14-SEP-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15746.04 | 04-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8877.61 | 03-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8070.85 | 06-DEC-16:10 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7778.18 | 2541.06 | 4338.05 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25431.79 | 6035.01 | 9760.61 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7709.42 | 11-JAN-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8808.70 | 28-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9456.81 | 02-MAR-16:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18961.19 | 27-APR-15:30 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19391.56 | 04-MAY-15:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21192.71 | 28-JUN-15:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22012.83 | 24-JUL-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22853.27 | 10-AUG-15:30 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19838.13 | 14-SEP-15:30 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15534.73 | 04-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8687.92 | 02-NOV-15:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7881.00 | 05-DEC-15:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7709.42 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22853.27 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2180.81 | 11-JAN-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.26 |
February | 2685.47 | 27-FEB-16:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 |
March | 2894.00 | 10-MAR-14:50 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.54 |
April | 5378.94 | 27-APR-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 | 0.00 |
May | 5347.05 | 15-MAY-14:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
June | 6173.63 | 21-JUN-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 0.00 |
July | 7326.13 | 24-JUL-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.75 | 0.00 |
August | 6877.05 | 09-AUG-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 | 0.00 |
September | 5059.26 | 14-SEP-15:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 0.00 |
October | 3287.92 | 04-OCT-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 |
November | 2575.36 | 02-NOV-14:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.40 |
December | 2042.22 | 30-DEC-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2042.22 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7326.13 | 1306.65 | 2057.62 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 53.26 | 136.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1719.69 | 28-JAN-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.82 |
February | 2233.37 | 27-FEB-15:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
March | 2798.94 | 14-MAR-10:00 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 |
April | 6663.21 | 27-APR-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 |
May | 6597.80 | 15-MAY-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.73 |
June | 9487.63 | 25-JUN-09:12 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.90 |
July | 8767.71 | 24-JUL-09:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 11062.88 | 06-AUG-09:22 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.18 |
September | 7940.65 | 10-SEP-09:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.61 |
October | 4441.91 | 04-OCT-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.51 |
November | 2182.21 | 02-NOV-10:40 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.59 |
December | 1728.26 | 30-DEC-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1719.69 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | |
Maximum of Months | 11062.88 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7106.42 | 20-JAN-13:25 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.52 |
February | 9048.46 | 27-FEB-14:25 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 |
March | 10413.76 | 14-MAR-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 |
April | 12926.94 | 27-APR-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 | 0.00 |
May | 11052.60 | 04-MAY-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 |
June | 10301.88 | 28-JUN-13:05 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 0.00 |
July | 19265.47 | 30-JUL-12:02 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 |
August | 14505.91 | 29-AUG-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 | 0.00 |
September | 26152.46 | 10-SEP-13:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.18 |
October | 14093.29 | 04-OCT-13:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.35 |
November | 8730.31 | 04-NOV-13:25 | 275.09 | 685.87 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6791.74 | 05-DEC-12:25 | 1375.43 | 4115.24 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6791.74 | 275.09 | 571.56 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26152.46 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 | 136.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2309.60 | 05-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.08 |
February | 3726.07 | 27-FEB-15:30 | 1610.75 | 2605.12 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 |
March | 5521.03 | 14-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 |
April | 8683.63 | 26-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 |
May | 12907.02 | 07-MAY-16:42 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.47 |
June | 18130.66 | 18-JUN-16:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.24 |
July | 18504.66 | 30-JUL-16:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 |
August | 13523.43 | 12-AUG-17:05 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.43 |
September | 18312.43 | 10-SEP-16:22 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.58 |
October | 6856.70 | 04-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 |
November | 2979.08 | 04-NOV-15:40 | 84.78 | 217.09 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 |
December | 2463.96 | 05-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2309.60 | 84.78 | 217.09 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18504.66 | 1610.75 | 2605.12 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 313.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1691.71 | 11-JAN-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.86 |
February | 1972.82 | 28-FEB-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2073.61 | 10-MAR-14:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.70 |
April | 2821.08 | 27-APR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 0.00 |
May | 3468.39 | 05-MAY-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
June | 4287.48 | 21-JUN-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
July | 5201.72 | 24-JUL-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 |
August | 5167.72 | 09-AUG-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 | 0.00 |
September | 3821.73 | 14-SEP-15:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
October | 2463.23 | 04-OCT-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 |
November | 2069.29 | 02-NOV-14:02 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 |
December | 1675.67 | 29-DEC-13:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1675.67 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5201.72 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 | 77.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1460.96 | 28-JAN-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.19 |
February | 1782.72 | 27-FEB-15:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 |
March | 2144.89 | 14-MAR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 |
April | 4806.26 | 27-APR-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 |
May | 5241.66 | 15-MAY-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 |
June | 5979.20 | 28-JUN-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 |
July | 7119.80 | 24-JUL-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
August | 7360.49 | 10-AUG-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 |
September | 5675.97 | 14-SEP-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
October | 3763.45 | 04-OCT-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.45 |
November | 1949.45 | 02-NOV-10:40 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.60 |
December | 1653.11 | 05-DEC-10:20 | 2481.66 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1460.96 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | |
Maximum of Months | 7360.49 | 2481.66 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3283.66 | 20-JAN-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1880.20 |
February | 5373.64 | 27-FEB-15:00 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.25 |
March | 5004.86 | 01-MAR-14:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.89 |
April | 9564.99 | 27-APR-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 225.85 | 0.00 |
May | 7963.84 | 14-MAY-14:30 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.66 |
June | 7511.07 | 28-JUN-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 87.87 | 0.00 |
July | 11042.92 | 31-JUL-16:10 | 401.76 | 1143.12 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3822.96 | 0.00 |
August | 13683.62 | 10-AUG-16:10 | 401.76 | 1143.12 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5689.70 | 0.00 |
September | 11508.57 | 14-SEP-13:50 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.73 |
October | 11766.94 | 04-OCT-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.80 |
November | 6567.90 | 04-NOV-13:40 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4178.87 | 05-DEC-12:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1586.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3283.66 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13683.62 | 1306.65 | 2057.62 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 5689.70 | 1880.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1884.76 | 05-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.11 |
February | 2555.69 | 27-FEB-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 |
March | 2894.98 | 02-MAR-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
April | 5570.97 | 26-APR-17:00 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 | 0.00 |
May | 11295.02 | 14-MAY-17:42 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.32 |
June | 6786.82 | 28-JUN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
July | 14769.34 | 23-JUL-18:01 | 0.00 | 506.55 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 |
August | 15409.08 | 06-AUG-18:02 | 0.00 | 434.19 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.31 |
September | 7034.65 | 11-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 |
October | 5909.90 | 04-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
November | 2483.38 | 04-NOV-15:40 | 84.78 | 217.09 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
December | 2110.17 | 05-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1884.76 | 0.00 | 217.09 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15409.08 | 805.38 | 1302.56 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 66.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1894.75 | 11-JAN-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.50 |
February | 2281.90 | 28-FEB-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2404.45 | 10-MAR-14:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.20 |
April | 4858.32 | 27-APR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 0.00 |
May | 5102.72 | 05-MAY-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 0.00 |
June | 5641.99 | 21-JUN-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 | 0.00 |
July | 6561.43 | 24-JUL-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.40 | 0.00 |
August | 6244.59 | 09-AUG-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.58 | 0.00 |
September | 4783.36 | 14-SEP-15:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 0.00 |
October | 3113.27 | 04-OCT-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 |
November | 2218.47 | 02-NOV-14:30 | 2544.47 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.43 |
December | 1805.86 | 29-DEC-14:10 | 2613.31 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1805.86 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6561.43 | 2613.31 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 44.58 | 118.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2405.13 | 20-JAN-11:03 | 2416.29 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 |
February | 3324.81 | 27-FEB-15:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 |
March | 5034.32 | 02-MAR-13:02 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.30 |
April | 7649.11 | 27-APR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 |
May | 8698.76 | 14-MAY-09:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.30 |
June | 8220.17 | 28-JUN-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 |
July | 9956.11 | 30-JUL-09:02 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.53 |
August | 14237.59 | 06-AUG-09:22 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.74 |
September | 11244.80 | 10-SEP-09:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.81 |
October | 5953.69 | 04-OCT-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 |
November | 3490.41 | 04-NOV-10:02 | 1017.38 | 1736.86 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.48 |
December | 2568.94 | 05-DEC-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2405.13 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 | |
Maximum of Months | 14237.59 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7917.54 | 20-JAN-13:13 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 |
February | 9384.35 | 27-FEB-14:25 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.22 |
March | 10633.57 | 01-MAR-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 |
April | 12338.55 | 27-APR-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 0.00 |
May | 10580.58 | 14-MAY-12:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.11 |
June | 9630.24 | 28-JUN-13:05 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 0.00 |
July | 12227.53 | 31-JUL-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 0.00 |
August | 16624.11 | 06-AUG-13:22 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.01 |
September | 15033.07 | 10-SEP-13:13 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.11 |
October | 14230.55 | 04-OCT-13:10 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 |
November | 9091.38 | 04-NOV-13:25 | 275.09 | 685.87 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8087.54 | 05-DEC-12:25 | 1375.43 | 4115.24 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7917.54 | 267.84 | 457.25 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16624.11 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 272.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2295.23 | 05-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.34 |
February | 3727.10 | 27-FEB-15:30 | 1610.75 | 2605.12 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 |
March | 5353.31 | 14-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 |
April | 8306.29 | 26-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 0.00 |
May | 17707.41 | 07-MAY-16:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.44 |
June | 8953.79 | 28-JUN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 0.00 |
July | 15262.58 | 23-JUL-16:52 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 |
August | 17792.59 | 06-AUG-16:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.49 |
September | 8837.44 | 11-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 |
October | 6893.39 | 04-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 |
November | 2857.90 | 04-NOV-15:40 | 84.78 | 217.09 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 |
December | 2471.86 | 05-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2295.23 | 84.78 | 217.09 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17792.59 | 1610.75 | 2605.12 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 119.44 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.152541E+12 | 120418.54 | 13-JAN-16:49 | 0.927193E+11 | 266214.58 | 02-JAN-06:19 |
February | 0.135832E+12 | 118594.50 | 27-FEB-15:09 | 0.579542E+11 | 211061.21 | 21-FEB-07:10 |
March | 0.154153E+12 | 115247.47 | 14-MAR-15:00 | 0.330253E+11 | 170563.31 | 06-MAR-07:10 |
April | 0.143144E+12 | 161964.25 | 27-APR-15:09 | 0.140645E+11 | 128358.63 | 18-APR-06:10 |
May | 0.154196E+12 | 154927.99 | 15-MAY-15:00 | 0.481119E+10 | 98913.18 | 18-MAY-06:10 |
June | 0.158229E+12 | 164652.20 | 28-JUN-15:30 | 0.155332E+10 | 63530.45 | 14-JUN-06:10 |
July | 0.167565E+12 | 182574.37 | 24-JUL-15:09 | 0.456189E+09 | 17544.71 | 03-JUL-06:10 |
August | 0.188361E+12 | 192087.47 | 10-AUG-15:50 | 0.525823E+09 | 34030.23 | 18-AUG-06:10 |
September | 0.155967E+12 | 167382.36 | 14-SEP-15:20 | 0.293407E+10 | 89001.44 | 28-SEP-06:10 |
October | 0.150429E+12 | 140471.84 | 04-OCT-15:09 | 0.168494E+11 | 127905.21 | 16-OCT-06:10 |
November | 0.147516E+12 | 120828.45 | 06-NOV-16:00 | 0.452511E+11 | 183291.16 | 13-NOV-07:10 |
December | 0.149637E+12 | 120622.29 | 06-DEC-16:30 | 0.740084E+11 | 226065.47 | 26-DEC-07:19 |
Annual Sum or Average | 0.185757E+13 | 0.344153E+12 | ||||
Minimum of Months | 0.135832E+12 | 115247.47 | 0.456189E+09 | 17544.71 | ||
Maximum of Months | 0.188361E+12 | 192087.47 | 0.927193E+11 | 266214.58 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.256004E+11 | 0.613996E+11 | 0.230900E+10 | 0.107071E+11 | 0.445445E+09 | 0.00 | 535375.77 | 0.00 | 0.00 | 0.00 | 0.483069E+10 | 0.00 |
February | 0.428574E+11 | 0.211055E+11 | 0.556056E+11 | 0.209511E+10 | 0.923941E+10 | 0.276155E+09 | 0.00 | 0.240826E+09 | 0.00 | 0.00 | 0.00 | 0.441236E+10 | 0.00 |
March | 0.509265E+11 | 0.206010E+11 | 0.635880E+11 | 0.240664E+10 | 0.108981E+11 | 0.158647E+09 | 0.00 | 0.425743E+09 | 0.00 | 0.00 | 0.00 | 0.514817E+10 | 0.00 |
April | 0.454877E+11 | 0.171600E+11 | 0.594055E+11 | 0.224272E+10 | 0.110017E+11 | 76347668.91 | 0.00 | 0.324321E+10 | 0.00 | 0.00 | 0.00 | 0.452717E+10 | 0.00 |
May | 0.490872E+11 | 0.152413E+11 | 0.624938E+11 | 0.235782E+10 | 0.133396E+11 | 38069096.06 | 0.00 | 0.696045E+10 | 0.00 | 0.00 | 0.00 | 0.467785E+10 | 0.00 |
June | 0.488499E+11 | 0.134127E+11 | 0.612808E+11 | 0.231841E+10 | 0.151138E+11 | 21927786.02 | 0.00 | 0.127541E+11 | 0.00 | 0.00 | 0.00 | 0.447743E+10 | 0.00 |
July | 0.457251E+11 | 0.144757E+11 | 0.606074E+11 | 0.228147E+10 | 0.171112E+11 | 14494592.86 | 0.00 | 0.232214E+11 | 0.00 | 0.00 | 0.00 | 0.412871E+10 | 0.00 |
August | 0.509265E+11 | 0.166196E+11 | 0.635880E+11 | 0.240664E+10 | 0.193134E+11 | 15420323.55 | 0.00 | 0.309845E+11 | 0.00 | 0.00 | 0.00 | 0.450676E+10 | 0.00 |
September | 0.454877E+11 | 0.187274E+11 | 0.593832E+11 | 0.224140E+10 | 0.141810E+11 | 26167162.87 | 0.00 | 0.117963E+11 | 0.00 | 0.00 | 0.00 | 0.412374E+10 | 0.00 |
October | 0.472479E+11 | 0.222225E+11 | 0.614108E+11 | 0.230966E+10 | 0.111592E+11 | 86165155.59 | 0.00 | 0.160632E+10 | 0.00 | 0.00 | 0.00 | 0.438697E+10 | 0.00 |
November | 0.466941E+11 | 0.240240E+11 | 0.599069E+11 | 0.224962E+10 | 0.956867E+10 | 0.213615E+09 | 0.00 | 0.385422E+09 | 0.00 | 0.00 | 0.00 | 0.447388E+10 | 0.00 |
December | 0.457251E+11 | 0.262580E+11 | 0.605962E+11 | 0.228081E+10 | 0.983230E+10 | 0.352112E+09 | 0.00 | 275137.45 | 0.00 | 0.00 | 0.00 | 0.459241E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.235448E+12 | 0.729266E+12 | 0.274993E+11 | 0.151466E+12 | 0.172457E+10 | 0.00 | 0.916191E+11 | 0.00 | 0.00 | 0.00 | 0.542861E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.134127E+11 | 0.556056E+11 | 0.209511E+10 | 0.923941E+10 | 14494592.86 | 0.00 | 275137.45 | 0.00 | 0.00 | 0.00 | 0.412374E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.262580E+11 | 0.635880E+11 | 0.240664E+10 | 0.193134E+11 | 0.445445E+09 | 0.00 | 0.309845E+11 | 0.00 | 0.00 | 0.00 | 0.514817E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.927193E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.579542E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.330253E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.140645E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.481119E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.155332E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.456189E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.525823E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.293407E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.168494E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.452511E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.740084E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.344153E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.456189E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.927193E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 03-JAN-08:09 | 16174.82 | 02-JAN-06:30 | 893.29 | 02-JAN-06:00 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 02-FEB-08:09 | 14265.01 | 21-FEB-07:10 | 862.32 | 21-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 01-MAR-12:09 | 10299.57 | 02-MAR-15:30 | 771.01 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 04-APR-16:10 | 22021.21 | 27-APR-14:30 | 581.58 | 18-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 10-MAY-16:10 | 21506.71 | 15-MAY-15:20 | 436.56 | 18-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 13-JUN-16:10 | 23808.09 | 28-JUN-15:30 | 315.17 | 14-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 01-JUL-10:20 | 27169.25 | 31-JUL-15:20 | 92.76 | 03-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:10 | 30475.76 | 10-AUG-15:30 | 183.64 | 18-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 01-SEP-07:10 | 25119.65 | 14-SEP-14:50 | 389.55 | 28-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 11-OCT-11:09 | 19587.20 | 04-OCT-14:00 | 591.10 | 16-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 02-NOV-11:09 | 10747.03 | 24-NOV-07:10 | 792.63 | 13-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 04-DEC-12:09 | 14562.84 | 26-DEC-07:10 | 878.87 | 26-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 10299.57 | 92.76 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 30475.76 | 893.29 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 137.49 | 30-JAN-07:19 | 0.00 | 0.00 | 0.00 | 6491.58 | 31-JAN-12:50 | 0.00 |
February | 12796.99 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 6518.00 | 13-FEB-12:30 | 0.00 |
March | 11750.27 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 6437.96 | 01-MAR-12:30 | 0.00 |
April | 42983.99 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 6250.83 | 03-APR-11:39 | 0.00 |
May | 37017.92 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 6180.23 | 10-MAY-11:50 | 0.00 |
June | 43540.38 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 5815.83 | 01-JUN-11:30 | 0.00 |
July | 59305.36 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 5767.44 | 03-JUL-11:00 | 0.00 |
August | 64742.39 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 5660.72 | 25-AUG-11:39 | 0.00 |
September | 45922.54 | 14-SEP-14:09 | 0.00 | 0.00 | 0.00 | 5776.64 | 29-SEP-11:39 | 0.00 |
October | 24263.06 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 5828.94 | 31-OCT-11:20 | 0.00 |
November | 18507.81 | 04-NOV-14:09 | 0.00 | 0.00 | 0.00 | 6210.47 | 29-NOV-12:50 | 0.00 |
December | 139.71 | 17-DEC-21:10 | 0.00 | 0.00 | 0.00 | 6261.88 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 137.49 | 0.00 | 0.00 | 0.00 | 5660.72 | 0.00 | ||
Maximum of Months | 64742.39 | 0.00 | 0.00 | 0.00 | 6518.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 120418.54 | 13-JAN-16:49 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 7443.89 | 188.85 | 0.00 | 0.00 | 0.00 |
February | 118594.50 | 27-FEB-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 9412.07 | 6.85 | 0.00 | 12796.99 | 0.00 |
March | 115247.47 | 14-MAR-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 10054.24 | 6.85 | 0.00 | 7415.11 | 0.00 |
April | 161964.25 | 27-APR-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 21719.45 | 6.85 | 0.00 | 42837.22 | 0.00 |
May | 154927.99 | 15-MAY-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 21124.59 | 6.85 | 0.00 | 36497.78 | 0.00 |
June | 164652.20 | 28-JUN-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 23808.09 | 6.85 | 0.00 | 43540.38 | 0.00 |
July | 182574.37 | 24-JUL-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 26943.64 | 6.93 | 0.00 | 58638.43 | 0.00 |
August | 192087.47 | 10-AUG-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 30391.31 | 6.93 | 0.00 | 64650.50 | 0.00 |
September | 167382.36 | 14-SEP-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 25089.42 | 6.90 | 0.00 | 45183.60 | 0.00 |
October | 140471.84 | 04-OCT-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 19510.06 | 6.85 | 0.00 | 23912.39 | 0.00 |
November | 120828.45 | 06-NOV-16:00 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 8400.64 | 16.05 | 0.00 | 0.00 | 0.00 |
December | 120622.29 | 06-DEC-16:30 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 7803.16 | 65.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 115247.47 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 7443.89 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 192087.47 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 30391.31 | 188.85 | 0.00 | 64650.50 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 266214.58 | 02-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 211061.21 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 170563.31 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 128358.63 | 18-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 98913.18 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 63530.45 | 14-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 17544.71 | 03-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 34030.23 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 89001.44 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 127905.21 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 183291.16 | 13-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 226065.47 | 26-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 17544.71 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 266214.58 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.49 | 2.00 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 19.49 | 2.00 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.49 | 2.00 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.28 | 2.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 2.67 | 19.28 | 2.67 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.34 | 2.50 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 19.11 | 3.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
February | 0.67 | 19.37 | 0.67 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
March | 0.17 | 19.38 | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.37 | 0.50 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
December | 1.00 | 18.92 | 0.83 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Annual Sum or Average | 5.67 | 19.14 | 5.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.38 | 3.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.50 | 16.26 | 5.83 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
February | 7.67 | 16.04 | 3.33 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
March | 0.50 | 19.16 | 0.50 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 18.50 | 1.17 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
December | 6.00 | 17.42 | 3.33 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
Annual Sum or Average | 32.17 | 16.57 | 14.17 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.50 | 19.16 | 5.83 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.50 | 15.76 | 4.83 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
February | 6.17 | 15.89 | 2.00 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
March | 0.33 | 19.14 | 0.33 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.86 | 1.67 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.87 | 1.00 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 18.08 | 1.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
December | 5.67 | 16.88 | 2.33 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 |
Annual Sum or Average | 30.17 | 16.15 | 10.50 | 16.63 | 2.67 | 17.32 | 2.67 | 17.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.50 | 19.14 | 4.83 | 19.14 | 1.67 | 27.87 | 1.67 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.50 | 15.81 | 3.50 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
February | 3.17 | 16.43 | 1.50 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
March | 0.33 | 19.16 | 0.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.72 | 1.17 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.84 | 1.33 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.98 | 1.17 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 17.96 | 0.50 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
December | 4.00 | 17.20 | 2.00 | 17.90 | 0.00 | 17.90 | 0.00 | 17.90 |
Annual Sum or Average | 20.83 | 16.31 | 7.83 | 16.81 | 4.00 | 18.15 | 4.00 | 19.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.50 | 19.16 | 3.50 | 19.16 | 1.33 | 27.98 | 1.33 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.33 | 15.72 | 4.67 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
February | 5.67 | 15.73 | 2.33 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 |
March | 0.33 | 19.18 | 0.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.19 | 1.00 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.56 | 0.50 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.48 | 1.50 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.99 | 1.17 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.66 | 0.67 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 17.95 | 0.50 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
December | 5.50 | 16.84 | 2.17 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
Annual Sum or Average | 27.67 | 16.06 | 10.00 | 16.46 | 9.00 | 18.71 | 4.83 | 19.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.33 | 19.18 | 4.67 | 19.18 | 3.33 | 28.48 | 1.50 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 19.31 | 3.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
February | 0.50 | 19.62 | 0.50 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.90 | 0.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Annual Sum or Average | 4.17 | 19.39 | 4.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.90 | 3.17 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.33 | 2.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.39 | 0.67 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 19.33 | 2.17 | 19.41 | 0.67 | 20.44 | 0.67 | 21.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.33 | 2.17 | 19.41 | 0.67 | 27.39 | 0.67 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.83 | 18.61 | 65.83 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
February | 37.83 | 18.63 | 37.83 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
March | 30.50 | 19.09 | 30.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
April | 17.33 | 19.18 | 17.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
May | 9.50 | 19.91 | 9.50 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
June | 0.50 | 20.36 | 0.50 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
September | 2.00 | 19.99 | 2.00 | 19.99 | 1.00 | 21.53 | 1.00 | 22.55 |
October | 14.00 | 19.89 | 14.00 | 19.89 | 0.00 | 19.89 | 0.00 | 19.89 |
November | 37.33 | 19.25 | 37.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 56.00 | 18.77 | 56.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Annual Sum or Average | 270.83 | 18.95 | 270.83 | 18.95 | 1.50 | 18.97 | 1.50 | 19.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.83 | 20.36 | 65.83 | 20.36 | 1.00 | 27.41 | 1.00 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.39 | 2.00 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.00 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.86 | 0.83 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.77 | 0.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.17 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 19.39 | 2.00 | 19.49 | 4.00 | 23.55 | 1.17 | 24.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.39 | 2.00 | 19.49 | 2.67 | 27.86 | 0.83 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.20 | 2.83 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.50 | 19.55 | 0.50 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 19.16 | 0.67 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Annual Sum or Average | 4.50 | 19.23 | 4.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.55 | 2.83 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 18.50 | 1.33 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
February | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.46 | 0.33 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.98 | 2.00 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.91 | 1.67 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.50 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.54 | 0.33 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Annual Sum or Average | 2.33 | 18.57 | 1.83 | 18.77 | 4.50 | 23.49 | 4.50 | 24.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.35 | 1.33 | 19.35 | 2.00 | 27.98 | 2.00 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.24 | 1.50 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.64 | 1.00 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.77 | 1.17 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.96 | 1.33 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
December | 0.50 | 18.57 | 0.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Annual Sum or Average | 2.17 | 19.08 | 1.83 | 19.26 | 4.17 | 23.58 | 4.17 | 24.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.24 | 1.50 | 19.37 | 1.33 | 27.96 | 1.33 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 18.51 | 1.33 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
February | 0.17 | 19.43 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.09 | 0.67 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.60 | 0.50 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.37 | 1.33 | 28.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.93 | 1.17 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.80 | 0.50 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.55 | 0.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Annual Sum or Average | 2.33 | 18.59 | 1.83 | 18.79 | 8.17 | 24.95 | 4.17 | 25.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.43 | 1.33 | 19.43 | 3.17 | 28.37 | 1.33 | 28.42 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 22.84 | 32.67 | 22.64 | 32.67 | 22.47 |
February | 402.17 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
March | 319.83 | 23.76 | 6.17 | 23.79 | 0.00 | 23.79 |
April | 141.67 | 23.74 | 76.33 | 24.21 | 0.00 | 24.21 |
May | 12.00 | 23.86 | 205.00 | 24.80 | 0.00 | 24.80 |
June | 0.00 | 0.00 | 279.67 | 24.75 | 0.00 | 24.75 |
July | 0.00 | 0.00 | 425.33 | 24.61 | 0.00 | 24.61 |
August | 0.00 | 0.00 | 473.00 | 24.45 | 0.00 | 24.45 |
September | 0.00 | 0.00 | 353.17 | 24.65 | 0.00 | 24.65 |
October | 78.50 | 23.61 | 90.33 | 24.58 | 0.00 | 24.58 |
November | 283.33 | 23.64 | 30.50 | 23.78 | 0.00 | 23.78 |
December | 470.33 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
Annual Sum or Average | 2204.50 | 23.41 | 1972.17 | 23.97 | 32.67 | 23.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.64 | 0.00 | 22.47 |
Maximum of Months | 496.67 | 23.86 | 473.00 | 24.80 | 32.67 | 24.80 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.41 | 113.00 | 21.15 | 113.00 | 20.97 |
February | 451.17 | 22.02 | 41.67 | 21.87 | 41.67 | 21.75 |
March | 505.67 | 22.82 | 1.17 | 22.81 | 1.17 | 22.81 |
April | 375.67 | 23.12 | 25.00 | 23.21 | 0.00 | 23.21 |
May | 221.83 | 23.36 | 53.67 | 23.56 | 0.00 | 23.56 |
June | 104.83 | 23.45 | 130.17 | 23.98 | 0.00 | 23.98 |
July | 25.83 | 23.50 | 268.33 | 24.33 | 0.00 | 24.33 |
August | 46.00 | 23.39 | 341.33 | 24.18 | 0.00 | 24.18 |
September | 119.83 | 23.28 | 159.50 | 23.92 | 0.00 | 23.92 |
October | 375.17 | 22.99 | 0.50 | 22.99 | 0.00 | 22.99 |
November | 474.00 | 22.39 | 2.67 | 22.38 | 2.67 | 22.37 |
December | 497.00 | 21.82 | 29.33 | 21.73 | 29.33 | 21.65 |
Annual Sum or Average | 3699.00 | 22.47 | 1166.33 | 22.76 | 187.83 | 22.66 |
Minimum of Months | 25.83 | 21.41 | 0.50 | 21.15 | 0.00 | 20.97 |
Maximum of Months | 505.67 | 23.50 | 341.33 | 24.33 | 113.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.59 | 240.83 | 20.31 | 240.83 | 20.17 |
February | 454.00 | 21.07 | 155.00 | 20.79 | 155.00 | 20.62 |
March | 514.00 | 21.84 | 66.17 | 21.65 | 66.17 | 21.51 |
April | 416.00 | 22.39 | 26.67 | 22.37 | 13.83 | 22.31 |
May | 319.33 | 22.85 | 40.00 | 22.99 | 0.00 | 22.99 |
June | 195.17 | 23.14 | 99.33 | 23.51 | 0.00 | 23.51 |
July | 119.83 | 23.21 | 224.17 | 23.88 | 0.00 | 23.88 |
August | 133.50 | 23.12 | 265.17 | 23.82 | 0.00 | 23.82 |
September | 286.83 | 22.87 | 88.17 | 23.17 | 0.00 | 23.17 |
October | 469.33 | 22.14 | 23.00 | 22.05 | 23.00 | 21.98 |
November | 489.00 | 21.33 | 97.83 | 21.10 | 97.83 | 20.93 |
December | 497.00 | 20.82 | 201.33 | 20.57 | 201.33 | 20.44 |
Annual Sum or Average | 4396.00 | 21.81 | 1527.67 | 21.85 | 798.00 | 21.62 |
Minimum of Months | 119.83 | 20.59 | 23.00 | 20.31 | 0.00 | 20.17 |
Maximum of Months | 514.00 | 23.21 | 265.17 | 23.88 | 240.83 | 23.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.96 | 406.50 | 19.85 | 406.50 | 19.81 |
February | 454.00 | 20.24 | 287.17 | 20.05 | 287.17 | 19.96 |
March | 514.00 | 20.78 | 200.50 | 20.57 | 200.50 | 20.46 |
April | 466.67 | 21.47 | 91.33 | 21.32 | 81.50 | 21.17 |
May | 407.00 | 21.97 | 60.67 | 22.01 | 26.83 | 21.90 |
June | 308.17 | 22.44 | 85.67 | 22.77 | 2.00 | 22.76 |
July | 219.83 | 22.59 | 187.67 | 23.28 | 0.00 | 23.28 |
August | 243.00 | 22.43 | 196.33 | 23.18 | 0.00 | 23.18 |
September | 393.83 | 21.98 | 51.50 | 22.18 | 4.17 | 22.16 |
October | 502.00 | 21.12 | 104.33 | 20.90 | 104.33 | 20.76 |
November | 489.00 | 20.40 | 255.33 | 20.19 | 255.33 | 20.09 |
December | 497.00 | 20.07 | 395.33 | 19.97 | 395.33 | 19.93 |
Annual Sum or Average | 4996.50 | 21.09 | 2322.33 | 21.02 | 1763.67 | 20.79 |
Minimum of Months | 219.83 | 19.96 | 51.50 | 19.85 | 0.00 | 19.81 |
Maximum of Months | 514.00 | 22.59 | 406.50 | 23.28 | 406.50 | 23.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.98 | 393.50 | 19.85 | 393.50 | 19.80 |
February | 454.00 | 20.32 | 264.50 | 20.13 | 264.50 | 20.04 |
March | 512.50 | 20.89 | 159.50 | 20.65 | 159.50 | 20.50 |
April | 416.17 | 21.56 | 88.33 | 21.52 | 59.33 | 21.36 |
May | 344.83 | 21.81 | 115.83 | 22.20 | 24.50 | 22.09 |
June | 238.50 | 22.25 | 187.50 | 23.12 | 2.50 | 23.11 |
July | 195.50 | 22.55 | 250.50 | 23.52 | 7.00 | 23.57 |
August | 204.83 | 22.42 | 253.00 | 23.39 | 4.83 | 23.43 |
September | 331.33 | 21.81 | 115.33 | 22.39 | 4.83 | 22.37 |
October | 484.83 | 21.21 | 90.17 | 21.02 | 87.83 | 20.86 |
November | 489.00 | 20.42 | 240.83 | 20.21 | 240.83 | 20.10 |
December | 497.00 | 20.09 | 371.00 | 19.96 | 371.00 | 19.90 |
Annual Sum or Average | 4670.50 | 21.03 | 2530.00 | 21.17 | 1620.17 | 20.92 |
Minimum of Months | 195.50 | 19.98 | 88.33 | 19.85 | 2.50 | 19.80 |
Maximum of Months | 512.50 | 22.55 | 393.50 | 23.52 | 393.50 | 23.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.50 | 20.18 | 337.17 | 19.98 | 336.33 | 19.89 |
February | 423.83 | 20.65 | 222.00 | 20.46 | 212.83 | 20.32 |
March | 457.33 | 21.00 | 170.00 | 20.86 | 146.67 | 20.68 |
April | 373.83 | 21.40 | 131.00 | 21.58 | 68.00 | 21.41 |
May | 350.33 | 21.71 | 131.33 | 22.16 | 29.67 | 22.05 |
June | 293.17 | 22.09 | 139.00 | 22.77 | 3.83 | 22.76 |
July | 224.67 | 22.32 | 224.00 | 23.30 | 4.83 | 23.33 |
August | 235.67 | 22.27 | 232.00 | 23.24 | 6.67 | 23.29 |
September | 303.50 | 21.84 | 160.00 | 22.64 | 7.83 | 22.66 |
October | 406.00 | 21.18 | 141.67 | 21.43 | 71.17 | 21.25 |
November | 464.50 | 20.60 | 217.50 | 20.45 | 202.83 | 20.31 |
December | 485.17 | 20.34 | 316.50 | 20.12 | 315.83 | 20.02 |
Annual Sum or Average | 4516.50 | 21.13 | 2422.17 | 21.33 | 1406.50 | 21.09 |
Minimum of Months | 224.67 | 20.18 | 131.00 | 19.98 | 3.83 | 19.89 |
Maximum of Months | 498.50 | 22.32 | 337.17 | 23.30 | 336.33 | 23.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.99 | 398.17 | 19.87 | 398.17 | 19.82 |
February | 452.33 | 20.37 | 275.17 | 20.17 | 274.67 | 20.08 |
March | 500.33 | 20.81 | 187.67 | 20.62 | 181.50 | 20.49 |
April | 421.33 | 21.27 | 117.00 | 21.33 | 77.33 | 21.17 |
May | 391.00 | 21.71 | 112.00 | 22.07 | 32.00 | 22.00 |
June | 321.50 | 22.00 | 119.83 | 22.58 | 4.83 | 22.58 |
July | 232.67 | 22.28 | 207.17 | 23.24 | 9.17 | 23.31 |
August | 269.17 | 22.13 | 193.17 | 23.02 | 6.17 | 23.07 |
September | 359.67 | 21.72 | 103.50 | 22.26 | 7.00 | 22.27 |
October | 472.67 | 21.03 | 111.17 | 20.94 | 94.83 | 20.79 |
November | 487.83 | 20.46 | 245.67 | 20.24 | 245.67 | 20.14 |
December | 497.00 | 20.11 | 380.83 | 19.99 | 380.83 | 19.94 |
Annual Sum or Average | 4907.50 | 21.00 | 2451.33 | 21.08 | 1712.17 | 20.86 |
Minimum of Months | 232.67 | 19.99 | 103.50 | 19.87 | 4.83 | 19.82 |
Maximum of Months | 502.00 | 22.28 | 398.17 | 23.24 | 398.17 | 23.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.25 | 389.67 | 20.15 | 389.67 | 20.12 |
February | 454.00 | 20.51 | 267.00 | 20.37 | 267.00 | 20.30 |
March | 514.00 | 20.94 | 167.83 | 20.81 | 167.83 | 20.73 |
April | 477.67 | 21.53 | 50.17 | 21.42 | 49.67 | 21.33 |
May | 475.33 | 22.34 | 7.00 | 22.36 | 1.00 | 22.35 |
June | 357.00 | 22.91 | 35.50 | 23.02 | 0.00 | 23.02 |
July | 211.00 | 23.10 | 131.33 | 23.48 | 0.00 | 23.48 |
August | 204.50 | 22.97 | 188.67 | 23.51 | 0.00 | 23.51 |
September | 380.83 | 22.62 | 41.67 | 22.77 | 0.00 | 22.77 |
October | 502.00 | 21.74 | 12.83 | 21.70 | 12.83 | 21.66 |
November | 489.00 | 20.97 | 139.50 | 20.81 | 139.50 | 20.70 |
December | 497.00 | 20.50 | 322.17 | 20.40 | 322.17 | 20.35 |
Annual Sum or Average | 5064.33 | 21.50 | 1753.33 | 21.39 | 1349.67 | 21.19 |
Minimum of Months | 204.50 | 20.25 | 7.00 | 20.15 | 0.00 | 20.12 |
Maximum of Months | 514.00 | 23.10 | 389.67 | 23.51 | 389.67 | 23.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 379.17 | 20.16 | 379.17 | 20.12 |
February | 454.00 | 20.61 | 243.00 | 20.48 | 243.00 | 20.41 |
March | 514.00 | 21.07 | 113.83 | 20.92 | 113.83 | 20.81 |
April | 447.17 | 21.82 | 47.33 | 21.77 | 33.67 | 21.67 |
May | 390.67 | 22.18 | 59.83 | 22.46 | 2.00 | 22.45 |
June | 246.17 | 22.69 | 165.00 | 23.39 | 0.00 | 23.39 |
July | 168.33 | 22.83 | 252.00 | 23.71 | 1.33 | 23.72 |
August | 147.00 | 22.81 | 287.33 | 23.75 | 2.33 | 23.76 |
September | 295.17 | 22.30 | 122.50 | 22.89 | 0.00 | 22.89 |
October | 461.50 | 21.68 | 19.50 | 21.66 | 14.50 | 21.62 |
November | 489.00 | 20.93 | 129.00 | 20.78 | 129.00 | 20.68 |
December | 497.00 | 20.52 | 306.83 | 20.40 | 306.83 | 20.35 |
Annual Sum or Average | 4612.00 | 21.37 | 2125.33 | 21.55 | 1225.67 | 21.34 |
Minimum of Months | 147.00 | 20.26 | 19.50 | 20.16 | 0.00 | 20.12 |
Maximum of Months | 514.00 | 22.83 | 379.17 | 23.75 | 379.17 | 23.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.18 | 346.00 | 20.00 | 346.00 | 19.92 |
February | 444.67 | 20.76 | 171.67 | 20.51 | 171.17 | 20.36 |
March | 494.00 | 21.11 | 96.00 | 20.90 | 95.17 | 20.74 |
April | 420.67 | 21.46 | 74.17 | 21.49 | 45.17 | 21.35 |
May | 414.00 | 21.81 | 56.33 | 22.07 | 7.67 | 22.03 |
June | 352.17 | 22.22 | 76.00 | 22.66 | 0.00 | 22.66 |
July | 212.50 | 22.53 | 202.33 | 23.41 | 0.17 | 23.41 |
August | 195.67 | 22.48 | 251.67 | 23.50 | 2.00 | 23.51 |
September | 262.00 | 22.18 | 179.50 | 23.08 | 3.50 | 23.11 |
October | 396.00 | 21.62 | 82.83 | 22.05 | 10.33 | 22.00 |
November | 468.17 | 20.91 | 129.67 | 20.83 | 114.50 | 20.68 |
December | 489.00 | 20.51 | 275.67 | 20.31 | 273.50 | 20.20 |
Annual Sum or Average | 4650.83 | 21.30 | 1941.83 | 21.48 | 1069.17 | 21.25 |
Minimum of Months | 195.67 | 20.18 | 56.33 | 20.00 | 0.00 | 19.92 |
Maximum of Months | 502.00 | 22.53 | 346.00 | 23.50 | 346.00 | 23.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.27 | 385.00 | 20.17 | 385.00 | 20.13 |
February | 454.00 | 20.63 | 246.67 | 20.47 | 246.67 | 20.40 |
March | 510.00 | 21.01 | 131.50 | 20.87 | 131.50 | 20.78 |
April | 445.83 | 21.49 | 64.00 | 21.50 | 43.83 | 21.41 |
May | 411.17 | 22.05 | 58.33 | 22.33 | 3.50 | 22.31 |
June | 335.67 | 22.44 | 90.50 | 22.87 | 0.00 | 22.87 |
July | 180.50 | 22.82 | 237.00 | 23.71 | 4.33 | 23.74 |
August | 208.67 | 22.65 | 227.17 | 23.49 | 1.50 | 23.50 |
September | 316.67 | 22.27 | 112.00 | 22.82 | 0.50 | 22.83 |
October | 472.17 | 21.54 | 25.50 | 21.58 | 13.00 | 21.55 |
November | 487.67 | 20.92 | 134.33 | 20.78 | 134.33 | 20.69 |
December | 497.00 | 20.54 | 312.33 | 20.42 | 312.33 | 20.37 |
Annual Sum or Average | 4821.33 | 21.35 | 2024.33 | 21.46 | 1276.50 | 21.27 |
Minimum of Months | 180.50 | 20.27 | 25.50 | 20.17 | 0.00 | 20.13 |
Maximum of Months | 510.00 | 22.82 | 385.00 | 23.71 | 385.00 | 23.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.21 | 330.17 | 20.05 | 330.17 | 19.97 |
February | 454.00 | 20.58 | 214.67 | 20.36 | 214.67 | 20.25 |
March | 514.00 | 21.25 | 100.50 | 21.08 | 100.50 | 20.96 |
April | 447.17 | 21.95 | 38.50 | 21.90 | 27.17 | 21.82 |
May | 358.17 | 22.53 | 45.17 | 22.69 | 1.00 | 22.68 |
June | 235.67 | 22.97 | 92.17 | 23.29 | 0.00 | 23.29 |
July | 145.50 | 23.14 | 215.00 | 23.74 | 0.00 | 23.74 |
August | 166.00 | 22.99 | 261.83 | 23.69 | 0.00 | 23.69 |
September | 325.67 | 22.59 | 65.50 | 22.85 | 0.00 | 22.85 |
October | 492.17 | 21.74 | 29.83 | 21.65 | 29.83 | 21.57 |
November | 489.00 | 20.89 | 148.00 | 20.68 | 148.00 | 20.55 |
December | 497.00 | 20.43 | 290.17 | 20.27 | 290.17 | 20.20 |
Annual Sum or Average | 4626.33 | 21.47 | 1831.50 | 21.48 | 1141.50 | 21.25 |
Minimum of Months | 145.50 | 20.21 | 29.83 | 20.05 | 0.00 | 19.97 |
Maximum of Months | 514.00 | 23.14 | 330.17 | 23.74 | 330.17 | 23.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.08 | 294.67 | 19.92 | 294.67 | 19.84 |
February | 385.00 | 20.59 | 186.50 | 20.38 | 186.50 | 20.28 |
March | 429.83 | 21.19 | 79.00 | 21.01 | 79.00 | 20.88 |
April | 345.83 | 21.78 | 52.33 | 21.83 | 26.50 | 21.73 |
May | 299.67 | 22.09 | 71.33 | 22.51 | 2.00 | 22.50 |
June | 204.67 | 22.49 | 136.00 | 23.25 | 1.33 | 23.27 |
July | 165.67 | 22.84 | 195.00 | 23.67 | 7.83 | 23.74 |
August | 162.17 | 22.72 | 213.83 | 23.60 | 7.17 | 23.66 |
September | 268.33 | 22.14 | 84.83 | 22.67 | 2.00 | 22.68 |
October | 392.67 | 21.49 | 40.17 | 21.43 | 32.33 | 21.34 |
November | 417.00 | 20.78 | 138.83 | 20.58 | 138.83 | 20.45 |
December | 422.00 | 20.34 | 259.83 | 20.18 | 259.83 | 20.10 |
Annual Sum or Average | 3919.83 | 21.29 | 1752.33 | 21.43 | 1038.00 | 21.21 |
Minimum of Months | 162.17 | 20.08 | 40.17 | 19.92 | 1.33 | 19.84 |
Maximum of Months | 429.83 | 22.84 | 294.67 | 23.67 | 294.67 | 23.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.67 | 20.49 | 264.00 | 20.26 | 262.33 | 20.14 |
February | 411.17 | 20.96 | 162.17 | 20.86 | 144.17 | 20.71 |
March | 437.50 | 21.32 | 100.17 | 21.31 | 71.17 | 21.17 |
April | 350.00 | 21.70 | 95.00 | 22.01 | 27.50 | 21.91 |
May | 332.00 | 22.12 | 109.83 | 22.65 | 2.83 | 22.64 |
June | 261.33 | 22.44 | 140.17 | 23.10 | 0.00 | 23.10 |
July | 188.33 | 22.72 | 240.00 | 23.61 | 4.00 | 23.64 |
August | 189.83 | 22.67 | 263.17 | 23.60 | 5.33 | 23.64 |
September | 267.33 | 22.29 | 178.67 | 23.10 | 4.67 | 23.14 |
October | 382.33 | 21.60 | 111.33 | 22.06 | 22.67 | 21.98 |
November | 456.50 | 21.01 | 135.17 | 20.97 | 112.67 | 20.82 |
December | 471.50 | 20.68 | 231.33 | 20.49 | 225.50 | 20.37 |
Annual Sum or Average | 4242.50 | 21.46 | 2031.00 | 21.79 | 882.83 | 21.58 |
Minimum of Months | 188.33 | 20.49 | 95.00 | 20.26 | 0.00 | 20.14 |
Maximum of Months | 494.67 | 22.72 | 264.00 | 23.61 | 262.33 | 23.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.23 | 326.67 | 20.06 | 326.67 | 19.99 |
February | 452.00 | 20.67 | 202.83 | 20.46 | 202.17 | 20.34 |
March | 498.00 | 21.11 | 101.67 | 20.99 | 95.50 | 20.88 |
April | 409.17 | 21.53 | 73.33 | 21.67 | 34.83 | 21.57 |
May | 381.17 | 22.09 | 87.00 | 22.50 | 6.50 | 22.51 |
June | 303.33 | 22.38 | 119.67 | 22.92 | 1.33 | 22.93 |
July | 197.50 | 22.67 | 229.33 | 23.58 | 8.33 | 23.64 |
August | 227.83 | 22.51 | 219.50 | 23.38 | 5.67 | 23.42 |
September | 328.00 | 22.09 | 112.33 | 22.67 | 2.33 | 22.68 |
October | 464.83 | 21.40 | 54.00 | 21.43 | 34.17 | 21.34 |
November | 485.83 | 20.81 | 146.67 | 20.63 | 146.67 | 20.52 |
December | 497.00 | 20.46 | 280.83 | 20.29 | 280.83 | 20.21 |
Annual Sum or Average | 4746.67 | 21.30 | 1953.83 | 21.45 | 1145.00 | 21.25 |
Minimum of Months | 197.50 | 20.23 | 54.00 | 20.06 | 1.33 | 19.99 |
Maximum of Months | 502.00 | 22.67 | 326.67 | 23.58 | 326.67 | 23.64 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.85063 | 30.70736 | -0.0606 | 6.74623 |
February | 454.00000 | 23.53663 | 30.66324 | 0.12625 | 5.83202 |
March | 514.00000 | 23.96567 | 29.36567 | 0.24580 | 6.45606 |
April | 485.00000 | 24.22706 | 32.44718 | 0.34523 | 7.80207 |
May | 508.00000 | 24.37217 | 36.08557 | -0.4338 | 9.37790 |
June | 496.00000 | 24.43285 | 38.09341 | -0.3704 | 8.44119 |
July | 497.00000 | 24.52418 | 41.98806 | -0.3001 | 7.58978 |
August | 514.00000 | 24.41829 | 45.00197 | -0.3007 | 7.45432 |
September | 485.00000 | 24.47103 | 42.77934 | -0.3332 | 8.04292 |
October | 502.00000 | 24.27885 | 35.76416 | 0.38331 | 8.38676 |
November | 489.00000 | 23.92305 | 35.24786 | 0.26274 | 6.83467 |
December | 497.00000 | 23.48243 | 30.71237 | 0.10919 | 5.59855 |
Annual Sum or Average | 5943.00000 | 24.04341 | 35.77213 | -0.0292 | 7.39135 |
Minimum of Months | 454.00000 | 22.85063 | 29.36567 | -0.4338 | 5.59855 |
Maximum of Months | 514.00000 | 24.52418 | 45.00197 | 0.38331 | 9.37790 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.41435 | 33.67069 | -0.3897 | 10.05319 |
February | 454.00000 | 22.02861 | 33.94290 | -0.2222 | 7.38965 |
March | 514.00000 | 22.83664 | 32.42908 | -0.0220 | 5.75797 |
April | 485.00000 | 23.35786 | 35.02633 | 0.13630 | 6.12081 |
May | 508.00000 | 23.77999 | 38.05555 | -0.6507 | 14.60957 |
June | 496.00000 | 24.02638 | 39.53398 | -0.5303 | 11.28931 |
July | 497.00000 | 24.18219 | 43.20760 | -0.4414 | 9.44272 |
August | 514.00000 | 24.12937 | 46.22049 | -0.4287 | 9.26236 |
September | 485.00000 | 23.94897 | 44.74326 | -0.5379 | 11.64634 |
October | 502.00000 | 23.27054 | 38.92333 | 0.13533 | 6.09340 |
November | 489.00000 | 22.43933 | 39.41295 | -0.0851 | 6.17010 |
December | 497.00000 | 21.82014 | 34.54271 | -0.2753 | 7.46570 |
Annual Sum or Average | 5943.00000 | 23.11130 | 38.33456 | -0.2770 | 8.79015 |
Minimum of Months | 454.00000 | 21.41435 | 32.42908 | -0.6507 | 5.75797 |
Maximum of Months | 514.00000 | 24.18219 | 46.22049 | 0.13630 | 14.60957 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.59299 | 34.49350 | -0.6127 | 15.47280 |
February | 454.00000 | 21.07215 | 34.87080 | -0.4699 | 11.91009 |
March | 514.00000 | 21.83925 | 33.88772 | -0.2631 | 7.83914 |
April | 485.00000 | 22.62860 | 36.23262 | -0.0349 | 6.59389 |
May | 508.00000 | 23.28485 | 39.02398 | -0.8110 | 20.72862 |
June | 496.00000 | 23.72425 | 40.13642 | -0.6251 | 14.23900 |
July | 497.00000 | 23.92591 | 43.60473 | -0.5175 | 11.42049 |
August | 514.00000 | 23.85449 | 46.75599 | -0.5173 | 11.55030 |
September | 485.00000 | 23.35786 | 46.28614 | -0.7391 | 18.10485 |
October | 502.00000 | 22.25992 | 41.12652 | -0.1084 | 6.60287 |
November | 489.00000 | 21.32791 | 41.60481 | -0.3644 | 9.29099 |
December | 497.00000 | 20.81987 | 35.99873 | -0.5420 | 12.67768 |
Annual Sum or Average | 5943.00000 | 22.40163 | 39.52626 | -0.4675 | 12.20713 |
Minimum of Months | 454.00000 | 20.59299 | 33.88772 | -0.8110 | 6.59389 |
Maximum of Months | 514.00000 | 23.92591 | 46.75599 | -0.0349 | 20.72862 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.96266 | 34.98004 | -0.8219 | 22.07788 |
February | 454.00000 | 20.23620 | 35.50120 | -0.7089 | 18.30298 |
March | 514.00000 | 20.77861 | 35.42568 | -0.5254 | 12.29770 |
April | 485.00000 | 21.56091 | 37.81482 | -0.2754 | 8.67618 |
May | 508.00000 | 22.34401 | 41.01880 | -1.0830 | 32.58459 |
June | 496.00000 | 23.01234 | 41.90104 | -0.8182 | 21.62488 |
July | 497.00000 | 23.37074 | 44.88484 | -0.6587 | 16.38161 |
August | 514.00000 | 23.24885 | 48.72483 | -0.6773 | 17.18388 |
September | 485.00000 | 22.33939 | 49.05598 | -1.0462 | 30.75440 |
October | 502.00000 | 21.11608 | 43.44937 | -0.3772 | 9.36949 |
November | 489.00000 | 20.39600 | 42.49477 | -0.6189 | 15.10730 |
December | 497.00000 | 20.07397 | 36.76502 | -0.7757 | 19.87029 |
Annual Sum or Average | 5943.00000 | 21.54822 | 41.03234 | -0.6991 | 18.68704 |
Minimum of Months | 454.00000 | 19.96266 | 34.98004 | -1.0830 | 8.67618 |
Maximum of Months | 514.00000 | 23.37074 | 49.05598 | -0.2754 | 32.58459 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97525 | 34.89102 | -0.8122 | 21.72271 |
February | 454.00000 | 20.32090 | 35.31853 | -0.6721 | 16.89614 |
March | 514.00000 | 20.89494 | 35.18275 | -0.4719 | 11.47093 |
April | 485.00000 | 21.89187 | 37.06098 | -0.1593 | 8.39155 |
May | 508.00000 | 22.51445 | 40.51489 | -0.9734 | 29.32192 |
June | 496.00000 | 23.20621 | 41.18119 | -0.6814 | 18.68101 |
July | 497.00000 | 23.47445 | 44.45476 | -0.5506 | 15.00933 |
August | 514.00000 | 23.37844 | 48.11026 | -0.5527 | 15.05214 |
September | 485.00000 | 22.51523 | 48.41046 | -0.9309 | 27.90156 |
October | 502.00000 | 21.30199 | 42.93723 | -0.3113 | 8.98508 |
November | 489.00000 | 20.42116 | 42.41309 | -0.6045 | 14.69780 |
December | 497.00000 | 20.08980 | 36.70429 | -0.7633 | 19.47588 |
Annual Sum or Average | 5943.00000 | 21.67690 | 40.62832 | -0.6235 | 17.29915 |
Minimum of Months | 454.00000 | 19.97525 | 34.89102 | -0.9734 | 8.39155 |
Maximum of Months | 514.00000 | 23.47445 | 48.41046 | -0.1593 | 29.32192 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.20319 | 34.16277 | -0.7294 | 19.44843 |
February | 454.00000 | 20.87762 | 34.03024 | -0.5170 | 14.42160 |
March | 514.00000 | 21.32793 | 34.05329 | -0.3528 | 11.16236 |
April | 485.00000 | 22.02193 | 36.46420 | -0.1248 | 9.13011 |
May | 508.00000 | 22.44792 | 40.36527 | -0.9939 | 30.89993 |
June | 496.00000 | 22.89320 | 41.79491 | -0.8031 | 22.90168 |
July | 497.00000 | 23.29869 | 44.70225 | -0.6130 | 17.37969 |
August | 514.00000 | 23.23263 | 48.31660 | -0.5961 | 17.18380 |
September | 485.00000 | 22.68590 | 47.55345 | -0.8379 | 26.13037 |
October | 502.00000 | 21.76749 | 41.45007 | -0.1775 | 9.36582 |
November | 489.00000 | 20.78205 | 41.19269 | -0.5018 | 13.36452 |
December | 497.00000 | 20.42454 | 35.70135 | -0.6558 | 17.40312 |
Annual Sum or Average | 5943.00000 | 21.83857 | 40.01913 | -0.5761 | 17.42590 |
Minimum of Months | 454.00000 | 20.20319 | 34.03024 | -0.9939 | 9.13011 |
Maximum of Months | 514.00000 | 23.29869 | 48.31660 | -0.1248 | 30.89993 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.98824 | 34.70042 | -0.8105 | 21.67115 |
February | 454.00000 | 20.38055 | 35.03751 | -0.6636 | 17.05912 |
March | 514.00000 | 20.89522 | 34.99195 | -0.4795 | 12.00945 |
April | 485.00000 | 21.64744 | 37.44682 | -0.2219 | 9.21716 |
May | 508.00000 | 22.25219 | 40.99791 | -1.0451 | 33.17264 |
June | 496.00000 | 22.71226 | 42.37153 | -0.8403 | 24.37499 |
July | 497.00000 | 23.23124 | 45.02464 | -0.6043 | 17.94412 |
August | 514.00000 | 23.02145 | 49.14570 | -0.6599 | 19.16910 |
September | 485.00000 | 22.33041 | 48.80325 | -0.9761 | 30.23513 |
October | 502.00000 | 21.20997 | 42.98363 | -0.3350 | 9.40831 |
November | 489.00000 | 20.46164 | 42.14820 | -0.5996 | 14.66653 |
December | 497.00000 | 20.11141 | 36.48854 | -0.7600 | 19.45231 |
Annual Sum or Average | 5943.00000 | 21.53006 | 40.87972 | -0.6666 | 19.04872 |
Minimum of Months | 454.00000 | 19.98824 | 34.70042 | -1.0451 | 9.21716 |
Maximum of Months | 514.00000 | 23.23124 | 49.14570 | -0.2219 | 33.17264 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.24705 | 35.00862 | -0.7362 | 18.17905 |
February | 454.00000 | 20.50938 | 35.60068 | -0.6344 | 14.98982 |
March | 514.00000 | 20.94309 | 35.49018 | -0.4895 | 10.61945 |
April | 485.00000 | 21.56081 | 38.31706 | -0.2929 | 7.85758 |
May | 508.00000 | 22.44459 | 41.41893 | -1.0932 | 31.68260 |
June | 496.00000 | 23.22508 | 42.14696 | -0.8013 | 19.75786 |
July | 497.00000 | 23.62996 | 44.95257 | -0.6243 | 14.05430 |
August | 514.00000 | 23.58345 | 48.39554 | -0.6102 | 13.85208 |
September | 485.00000 | 22.91369 | 48.02747 | -0.8786 | 22.74953 |
October | 502.00000 | 21.73587 | 42.37244 | -0.2162 | 6.78769 |
November | 489.00000 | 20.96956 | 41.53882 | -0.4431 | 9.99333 |
December | 497.00000 | 20.50449 | 36.10779 | -0.6371 | 14.25169 |
Annual Sum or Average | 5943.00000 | 21.86672 | 40.81231 | -0.6219 | 15.41494 |
Minimum of Months | 454.00000 | 20.24705 | 35.00862 | -1.0932 | 6.78769 |
Maximum of Months | 514.00000 | 23.62996 | 48.39554 | -0.2162 | 31.68260 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26101 | 34.72584 | -0.7293 | 17.89193 |
February | 454.00000 | 20.61191 | 35.19469 | -0.5948 | 13.60820 |
March | 514.00000 | 21.06794 | 34.99753 | -0.4320 | 9.64210 |
April | 485.00000 | 21.97994 | 37.13977 | -0.1534 | 7.28139 |
May | 508.00000 | 22.63471 | 40.63305 | -0.9710 | 27.89002 |
June | 496.00000 | 23.46153 | 41.03619 | -0.6423 | 16.26559 |
July | 497.00000 | 23.71403 | 44.33039 | -0.5149 | 12.55956 |
August | 514.00000 | 23.70925 | 47.53575 | -0.4742 | 11.72719 |
September | 485.00000 | 23.00738 | 47.32381 | -0.7778 | 20.89418 |
October | 502.00000 | 21.86934 | 41.75107 | -0.1579 | 6.88414 |
November | 489.00000 | 20.92905 | 41.38532 | -0.4425 | 9.91656 |
December | 497.00000 | 20.51893 | 35.83071 | -0.6276 | 14.02063 |
Annual Sum or Average | 5943.00000 | 21.99142 | 40.18673 | -0.5433 | 14.06025 |
Minimum of Months | 454.00000 | 20.26101 | 34.72584 | -0.9710 | 6.88414 |
Maximum of Months | 514.00000 | 23.71403 | 47.53575 | -0.1534 | 27.89002 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.18180 | 33.67232 | -0.6985 | 17.27480 |
February | 454.00000 | 20.83262 | 33.70916 | -0.4886 | 12.15154 |
March | 514.00000 | 21.22115 | 33.71707 | -0.3522 | 9.32369 |
April | 485.00000 | 21.82398 | 36.58980 | -0.1662 | 7.97267 |
May | 508.00000 | 22.26452 | 40.81271 | -1.0674 | 32.15154 |
June | 496.00000 | 22.80834 | 42.17477 | -0.8591 | 23.49766 |
July | 497.00000 | 23.45406 | 44.74535 | -0.5989 | 15.10799 |
August | 514.00000 | 23.48854 | 48.03564 | -0.5331 | 13.75923 |
September | 485.00000 | 23.11579 | 46.50086 | -0.6897 | 19.36764 |
October | 502.00000 | 22.21499 | 40.10459 | -0.0356 | 7.62452 |
November | 489.00000 | 21.07681 | 39.88248 | -0.3743 | 9.81287 |
December | 497.00000 | 20.58024 | 34.52591 | -0.5658 | 13.62028 |
Annual Sum or Average | 5943.00000 | 21.93045 | 39.57795 | -0.5369 | 15.17839 |
Minimum of Months | 454.00000 | 20.18180 | 33.67232 | -1.0674 | 7.62452 |
Maximum of Months | 514.00000 | 23.48854 | 48.03564 | -0.0356 | 32.15154 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26882 | 34.51700 | -0.7282 | 17.88025 |
February | 454.00000 | 20.62769 | 34.94373 | -0.5933 | 13.89376 |
March | 514.00000 | 21.02980 | 34.83305 | -0.4460 | 10.07812 |
April | 485.00000 | 21.71185 | 37.52741 | -0.2208 | 7.92233 |
May | 508.00000 | 22.46295 | 40.83049 | -1.0131 | 29.80670 |
June | 496.00000 | 22.98976 | 42.13838 | -0.7959 | 21.08705 |
July | 497.00000 | 23.69110 | 44.28174 | -0.5020 | 12.68882 |
August | 514.00000 | 23.48981 | 48.18552 | -0.5428 | 13.67627 |
September | 485.00000 | 22.92417 | 47.41803 | -0.7921 | 21.44766 |
October | 502.00000 | 21.70606 | 41.95137 | -0.1932 | 7.10814 |
November | 489.00000 | 20.93052 | 41.20126 | -0.4446 | 9.98299 |
December | 497.00000 | 20.53794 | 35.59837 | -0.6246 | 14.02576 |
Annual Sum or Average | 5943.00000 | 21.87428 | 40.31836 | -0.5752 | 14.98670 |
Minimum of Months | 454.00000 | 20.26882 | 34.51700 | -1.0131 | 7.10814 |
Maximum of Months | 514.00000 | 23.69110 | 48.18552 | -0.1932 | 29.80670 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.21332 | 34.88716 | -0.7167 | 18.04508 |
February | 454.00000 | 20.57734 | 35.25868 | -0.5860 | 14.32981 |
March | 514.00000 | 21.25302 | 35.01129 | -0.3844 | 9.13091 |
April | 485.00000 | 22.10195 | 37.12876 | -0.1406 | 7.04359 |
May | 508.00000 | 22.95136 | 39.99879 | -0.8954 | 24.09586 |
June | 496.00000 | 23.52419 | 41.00277 | -0.6694 | 15.66084 |
July | 497.00000 | 23.79332 | 44.11346 | -0.5393 | 11.98218 |
August | 514.00000 | 23.71142 | 47.74640 | -0.5414 | 12.30442 |
September | 485.00000 | 23.05388 | 47.43749 | -0.8177 | 20.94631 |
October | 502.00000 | 21.78231 | 42.26051 | -0.2008 | 7.03904 |
November | 489.00000 | 20.88748 | 41.80112 | -0.4607 | 10.70572 |
December | 497.00000 | 20.42613 | 36.30618 | -0.6416 | 14.80357 |
Annual Sum or Average | 5943.00000 | 22.03509 | 40.27490 | -0.5496 | 13.83929 |
Minimum of Months | 454.00000 | 20.21332 | 34.88716 | -0.8954 | 7.03904 |
Maximum of Months | 514.00000 | 23.79332 | 47.74640 | -0.1406 | 24.09586 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.08474 | 34.29250 | -0.7465 | 19.04127 |
February | 385.00000 | 20.58846 | 34.42995 | -0.5764 | 13.80849 |
March | 433.00000 | 21.21280 | 34.42958 | -0.3724 | 9.20609 |
April | 410.00000 | 22.13106 | 36.28319 | -0.0942 | 7.41374 |
May | 430.00000 | 22.68790 | 39.83590 | -0.9147 | 26.26301 |
June | 418.00000 | 23.32785 | 40.86690 | -0.6489 | 17.06132 |
July | 422.00000 | 23.61533 | 43.98704 | -0.5200 | 13.47524 |
August | 433.00000 | 23.53900 | 47.58718 | -0.5119 | 13.34789 |
September | 410.00000 | 22.80391 | 47.41960 | -0.8274 | 23.15567 |
October | 427.00000 | 21.68860 | 41.87901 | -0.1973 | 7.44109 |
November | 417.00000 | 20.78246 | 41.31616 | -0.4810 | 11.12112 |
December | 422.00000 | 20.33823 | 35.79713 | -0.6605 | 15.43205 |
Annual Sum or Average | 5034.00000 | 21.90826 | 39.87321 | -0.5461 | 14.73673 |
Minimum of Months | 385.00000 | 20.08474 | 34.29250 | -0.9147 | 7.41374 |
Maximum of Months | 433.00000 | 23.61533 | 47.58718 | -0.0942 | 26.26301 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54173 | 33.62215 | -0.6096 | 15.52811 |
February | 454.00000 | 21.27476 | 33.42653 | -0.3854 | 11.41139 |
March | 514.00000 | 21.72342 | 33.42451 | -0.2287 | 8.80187 |
April | 485.00000 | 22.38642 | 35.80069 | -0.0240 | 7.92954 |
May | 508.00000 | 22.81342 | 39.59763 | -0.8694 | 24.90964 |
June | 496.00000 | 23.22695 | 41.11137 | -0.7006 | 18.32013 |
July | 497.00000 | 23.60224 | 44.09562 | -0.5243 | 13.54411 |
August | 514.00000 | 23.55469 | 47.58863 | -0.4962 | 13.22788 |
September | 485.00000 | 23.11788 | 46.40688 | -0.6836 | 19.52569 |
October | 502.00000 | 22.25206 | 40.32138 | -0.0371 | 8.07470 |
November | 489.00000 | 21.24866 | 40.28611 | -0.3504 | 9.98252 |
December | 497.00000 | 20.86487 | 34.76093 | -0.5078 | 12.98409 |
Annual Sum or Average | 5943.00000 | 22.22519 | 39.24031 | -0.4524 | 13.70946 |
Minimum of Months | 454.00000 | 20.54173 | 33.42451 | -0.8694 | 7.92954 |
Maximum of Months | 514.00000 | 23.60224 | 47.58863 | -0.0240 | 24.90964 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.22864 | 34.31388 | -0.7099 | 17.80175 |
February | 454.00000 | 20.67957 | 34.58141 | -0.5511 | 13.49239 |
March | 514.00000 | 21.19683 | 34.55014 | -0.3728 | 9.34639 |
April | 485.00000 | 21.94445 | 36.94269 | -0.1336 | 7.82201 |
May | 508.00000 | 22.59068 | 40.30164 | -0.9272 | 27.32637 |
June | 496.00000 | 23.02735 | 41.73341 | -0.7421 | 19.85179 |
July | 497.00000 | 23.54026 | 44.41466 | -0.5135 | 14.05345 |
August | 514.00000 | 23.35458 | 48.41216 | -0.5566 | 14.98302 |
September | 485.00000 | 22.74453 | 47.72188 | -0.8261 | 23.47774 |
October | 502.00000 | 21.60354 | 42.07911 | -0.2111 | 7.54742 |
November | 489.00000 | 20.83221 | 41.41899 | -0.4665 | 10.75524 |
December | 497.00000 | 20.46085 | 35.70104 | -0.6296 | 14.62486 |
Annual Sum or Average | 5943.00000 | 21.86017 | 40.21514 | -0.5538 | 15.10638 |
Minimum of Months | 454.00000 | 20.22864 | 34.31388 | -0.9272 | 7.54742 |
Maximum of Months | 514.00000 | 23.54026 | 48.41216 | -0.1336 | 27.32637 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.606805E+11 | 0.00 | 465.24 | 332425.65 | 02-JAN-06:11 | 0.00 | 33.07 | 49.90 | 0.24 | 0.00 | 0.06 | 0.91 | 02-JAN-06:11 |
February | 0.368342E+11 | 0.00 | 374.46 | 288550.74 | 27-FEB-06:11 | 0.00 | 31.07 | 46.80 | 0.15 | 0.00 | 0.04 | 0.79 | 27-FEB-06:11 |
March | 0.201067E+11 | 0.00 | 347.33 | 302977.88 | 27-MAR-05:11 | 0.00 | 27.43 | 41.70 | 0.07 | 0.00 | 0.02 | 0.83 | 27-MAR-05:11 |
April | 0.848393E+10 | 0.00 | 225.74 | 248180.48 | 17-APR-05:11 | 0.00 | 27.89 | 37.24 | 0.03 | 0.00 | 0.01 | 0.68 | 17-APR-05:11 |
May | 0.283015E+10 | 0.00 | 132.73 | 165876.87 | 18-MAY-06:03 | 0.00 | 32.52 | 37.13 | 0.01 | 0.00 | 0.00 | 0.45 | 18-MAY-06:03 |
June | 0.891288E+09 | 0.00 | 55.33 | 90094.08 | 14-JUN-06:03 | 0.00 | 37.77 | 39.47 | 0.00 | 0.00 | 0.00 | 0.25 | 14-JUN-06:03 |
July | 0.257888E+09 | 0.00 | 87.56 | 13547.27 | 10-JUL-06:07 | 0.00 | 31.89 | 35.33 | 0.00 | 0.00 | 0.00 | 0.04 | 10-JUL-06:07 |
August | 0.298428E+09 | 0.00 | 139.12 | 37367.77 | 18-AUG-06:03 | 0.00 | 31.79 | 37.23 | 0.00 | 0.00 | 0.00 | 0.10 | 18-AUG-06:03 |
September | 0.170713E+10 | 0.00 | 148.92 | 145778.85 | 28-SEP-06:03 | 0.00 | 30.14 | 36.31 | 0.01 | 0.00 | 0.00 | 0.40 | 28-SEP-06:03 |
October | 0.100417E+11 | 0.00 | 273.79 | 257729.87 | 16-OCT-05:11 | 0.00 | 26.76 | 38.12 | 0.03 | 0.00 | 0.01 | 0.71 | 16-OCT-05:11 |
November | 0.281707E+11 | 0.00 | 361.00 | 273019.61 | 20-NOV-06:11 | 0.00 | 28.65 | 43.70 | 0.10 | 0.00 | 0.03 | 0.75 | 20-NOV-06:11 |
December | 0.477720E+11 | 0.00 | 406.79 | 267866.41 | 04-DEC-06:11 | 0.00 | 31.09 | 46.65 | 0.18 | 0.00 | 0.05 | 0.73 | 04-DEC-06:11 |
Annual Sum or Average | 0.218075E+12 | 0.00 | 3018.00 | 0.00 | 30.83 | 40.77 | 0.07 | 0.00 | 0.02 | ||||
Minimum of Months | 0.257888E+09 | 0.00 | 55.33 | 13547.27 | 0.00 | 26.76 | 35.33 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.606805E+11 | 0.00 | 465.24 | 332425.65 | 0.00 | 37.77 | 49.90 | 0.24 | 0.00 | 0.06 | 0.91 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.304679E+09 | 79761204.23 | 9.67 | 0.277368E+09 | 27310300.04 | 0.00 | 0.54 | 27-FEB-15:05 | 0.00 | 01-FEB-00:10 | 16904.13 | 27-FEB-15:05 | 16904.13 | 27-FEB-15:05 | 1672.72 | 27-FEB-17:50 | 4257.85 | 27-FEB-15:05 | 0.00 |
March | 0.541788E+09 | 0.145728E+09 | 26.50 | 0.470803E+09 | 70985080.28 | 0.00 | 0.49 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 15052.38 | 18-MAR-16:00 | 15052.38 | 18-MAR-16:00 | 2145.82 | 09-MAR-12:00 | 3843.81 | 18-MAR-16:00 | 0.00 |
April | 0.425860E+10 | 0.104179E+10 | 74.00 | 0.404770E+10 | 0.210897E+09 | 0.00 | 1.00 | 26-APR-13:40 | 0.00 | 01-APR-00:10 | 55804.38 | 27-APR-16:00 | 55119.60 | 27-APR-15:10 | 5740.45 | 28-APR-13:00 | 13447.16 | 27-APR-16:00 | 0.00 |
May | 0.944000E+10 | 0.228401E+10 | 163.28 | 0.827113E+10 | 0.116887E+10 | 0.00 | 1.00 | 04-MAY-13:20 | 0.00 | 01-MAY-00:10 | 51685.72 | 15-MAY-16:00 | 51685.72 | 15-MAY-16:00 | 7295.55 | 06-MAY-10:05 | 11487.10 | 15-MAY-16:00 | 0.00 |
June | 0.176669E+11 | 0.427020E+10 | 269.29 | 0.162064E+11 | 0.146056E+10 | 0.00 | 1.00 | 09-JUN-14:20 | 0.00 | 01-JUN-00:10 | 58673.10 | 28-JUN-15:50 | 58673.10 | 28-JUN-15:50 | 8546.48 | 12-JUN-14:40 | 13747.37 | 28-JUN-15:50 | 0.00 |
July | 0.330661E+11 | 0.783281E+10 | 352.97 | 0.287625E+11 | 0.430359E+10 | 0.00 | 1.00 | 06-JUL-14:50 | 0.00 | 01-JUL-00:10 | 74122.08 | 31-JUL-16:00 | 69304.88 | 24-JUL-15:00 | 15228.55 | 31-JUL-10:05 | 19274.72 | 24-JUL-15:00 | 0.00 |
August | 0.447670E+11 | 0.106623E+11 | 381.46 | 0.385819E+11 | 0.618510E+10 | 0.00 | 1.00 | 06-AUG-17:22 | 0.00 | 01-AUG-00:10 | 79682.89 | 10-AUG-15:30 | 75379.53 | 10-AUG-16:00 | 24729.24 | 30-AUG-05:12 | 21229.20 | 10-AUG-16:00 | 0.00 |
September | 0.173690E+11 | 0.412318E+10 | 234.84 | 0.140501E+11 | 0.331890E+10 | 0.00 | 1.00 | 08-SEP-14:05 | 0.00 | 01-SEP-00:10 | 68694.37 | 14-SEP-14:05 | 61854.74 | 14-SEP-15:30 | 17877.42 | 14-SEP-11:00 | 15337.63 | 14-SEP-14:05 | 0.00 |
October | 0.230704E+10 | 0.584491E+09 | 66.75 | 0.214849E+10 | 0.158549E+09 | 0.00 | 1.00 | 04-OCT-14:05 | 0.00 | 01-OCT-00:10 | 38748.61 | 04-OCT-15:00 | 38748.61 | 04-OCT-15:00 | 3652.34 | 08-OCT-13:26 | 8592.94 | 04-OCT-15:00 | 0.00 |
November | 0.509743E+09 | 0.125241E+09 | 8.50 | 0.350847E+09 | 0.158896E+09 | 0.00 | 0.76 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 25057.97 | 04-NOV-14:00 | 18847.75 | 04-NOV-14:00 | 7170.30 | 04-NOV-16:00 | 5954.33 | 04-NOV-14:00 | 0.00 |
December | 30404.83 | 8713.22 | 0.02 | 27752.92 | 2651.91 | 0.00 | 0.02 | 19-DEC-08:09 | 0.00 | 01-DEC-00:10 | 456.07 | 19-DEC-08:09 | 416.29 | 19-DEC-08:09 | 39.78 | 19-DEC-08:09 | 130.70 | 19-DEC-08:09 | 0.00 |
Annual Sum or Average | 0.130231E+12 | 0.311495E+11 | 1587.29 | 0.113167E+12 | 0.170637E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.447670E+11 | 0.106623E+11 | 381.46 | 0.385819E+11 | 0.618510E+10 | 0.00 | 1.00 | 0.00 | 79682.89 | 75379.53 | 24729.24 | 21229.20 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 494542.11 | 140740.57 | 0.12 | 461781.32 | 32760.80 | 0.00 | 0.06 | 30-JAN-07:13 | 0.00 | 01-JAN-00:05 | 1452.24 | 30-JAN-07:13 | 1294.64 | 30-JAN-07:13 | 157.61 | 30-JAN-07:13 | 412.46 | 30-JAN-07:13 | 0.00 |
February | 0.290266E+09 | 76025410.75 | 9.86 | 0.265042E+09 | 25223940.03 | 0.00 | 0.56 | 27-FEB-15:05 | 0.00 | 01-FEB-00:10 | 16578.08 | 27-FEB-15:05 | 16578.08 | 27-FEB-15:05 | 1569.19 | 27-FEB-18:20 | 4158.03 | 27-FEB-15:05 | 0.00 |
March | 0.494761E+09 | 0.132650E+09 | 25.73 | 0.434195E+09 | 60565802.16 | 0.00 | 0.52 | 18-MAR-14:05 | 0.00 | 01-MAR-00:10 | 15336.21 | 18-MAR-14:05 | 15336.21 | 18-MAR-14:05 | 1969.32 | 09-MAR-12:00 | 3883.83 | 18-MAR-14:05 | 0.00 |
April | 0.419030E+10 | 0.102525E+10 | 75.82 | 0.399187E+10 | 0.198426E+09 | 0.00 | 1.00 | 26-APR-13:40 | 0.00 | 01-APR-00:10 | 55048.19 | 27-APR-14:05 | 55048.19 | 27-APR-14:05 | 5783.10 | 28-APR-13:00 | 13243.62 | 27-APR-15:00 | 0.00 |
May | 0.910081E+10 | 0.220524E+10 | 169.79 | 0.796482E+10 | 0.113599E+10 | 0.00 | 1.00 | 04-MAY-13:00 | 0.00 | 01-MAY-00:10 | 49925.87 | 04-MAY-14:05 | 49925.87 | 04-MAY-14:05 | 10753.53 | 07-MAY-16:32 | 11207.37 | 04-MAY-15:00 | 0.00 |
June | 0.164835E+11 | 0.399438E+10 | 273.91 | 0.150917E+11 | 0.139180E+10 | 0.00 | 1.00 | 09-JUN-14:05 | 0.00 | 01-JUN-00:10 | 56349.55 | 28-JUN-15:40 | 56349.55 | 28-JUN-15:40 | 7563.87 | 12-JUN-14:05 | 13201.36 | 28-JUN-15:40 | 0.00 |
July | 0.303865E+11 | 0.721859E+10 | 355.90 | 0.264247E+11 | 0.396179E+10 | 0.00 | 1.00 | 06-JUL-14:50 | 0.00 | 01-JUL-00:10 | 70879.70 | 31-JUL-14:05 | 65043.77 | 24-JUL-14:05 | 14666.25 | 31-JUL-10:05 | 18013.65 | 24-JUL-15:00 | 0.00 |
August | 0.401225E+11 | 0.959616E+10 | 381.86 | 0.345398E+11 | 0.558275E+10 | 0.00 | 1.00 | 06-AUG-15:22 | 0.00 | 01-AUG-00:10 | 75710.78 | 10-AUG-14:05 | 70576.57 | 10-AUG-15:50 | 20265.71 | 30-AUG-13:00 | 19865.22 | 10-AUG-16:00 | 0.00 |
September | 0.156551E+11 | 0.372973E+10 | 236.44 | 0.126104E+11 | 0.304469E+10 | 0.00 | 1.00 | 08-SEP-14:05 | 0.00 | 01-SEP-00:10 | 65634.11 | 14-SEP-14:05 | 57573.92 | 14-SEP-14:05 | 16699.87 | 14-SEP-12:05 | 14653.09 | 14-SEP-14:05 | 0.00 |
October | 0.202249E+10 | 0.514796E+09 | 65.82 | 0.186810E+10 | 0.154394E+09 | 0.00 | 1.00 | 04-OCT-14:30 | 0.00 | 01-OCT-00:10 | 35105.91 | 04-OCT-15:00 | 35105.91 | 04-OCT-15:00 | 3443.62 | 08-OCT-13:35 | 7785.74 | 04-OCT-15:00 | 0.00 |
November | 0.502037E+09 | 0.122544E+09 | 8.53 | 0.350552E+09 | 0.151485E+09 | 0.00 | 0.81 | 04-NOV-14:02 | 0.00 | 01-NOV-00:10 | 25511.88 | 04-NOV-14:02 | 19730.07 | 04-NOV-14:02 | 6889.09 | 04-NOV-13:00 | 5985.51 | 04-NOV-14:02 | 0.00 |
December | 75233.73 | 21523.04 | 0.03 | 69823.21 | 5410.52 | 0.00 | 0.02 | 05-DEC-07:04 | 0.00 | 01-DEC-00:10 | 626.95 | 05-DEC-07:04 | 581.86 | 05-DEC-07:04 | 45.09 | 05-DEC-07:04 | 179.36 | 05-DEC-07:04 | 0.00 |
Annual Sum or Average | 0.119249E+12 | 0.286155E+11 | 1603.81 | 0.103542E+12 | 0.157071E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 75233.73 | 21523.04 | 0.03 | 69823.21 | 5410.52 | 0.00 | 0.02 | 0.00 | 626.95 | 581.86 | 45.09 | 179.36 | 0.00 | ||||||
Maximum of Months | 0.401225E+11 | 0.959616E+10 | 381.86 | 0.345398E+11 | 0.558275E+10 | 0.00 | 1.00 | 0.00 | 75710.78 | 70576.57 | 20265.71 | 19865.22 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1378417.43 | 394635.21 | 0.71 | 1270637.89 | 107779.54 | 0.00 | 0.04 | 08-JAN-10:37 | 0.00 | 01-JAN-00:05 | 1144.41 | 08-JAN-10:37 | 1137.79 | 08-JAN-10:37 | 114.99 | 26-JAN-07:04 | 326.38 | 08-JAN-10:37 | 0.00 |
February | 0.323266E+09 | 85039283.80 | 9.97 | 0.288992E+09 | 34274138.01 | 0.00 | 0.51 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 17558.50 | 27-FEB-15:00 | 17514.61 | 27-FEB-15:00 | 1892.94 | 27-FEB-17:40 | 4457.11 | 27-FEB-15:00 | 0.00 |
March | 0.547466E+09 | 0.147366E+09 | 25.75 | 0.475043E+09 | 72423615.32 | 0.00 | 0.48 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 16245.61 | 18-MAR-14:00 | 16245.61 | 18-MAR-14:00 | 2297.46 | 09-MAR-12:00 | 4160.43 | 18-MAR-14:00 | 0.00 |
April | 0.480912E+10 | 0.117617E+10 | 74.42 | 0.455951E+10 | 0.249613E+09 | 0.00 | 1.00 | 26-APR-13:50 | 0.00 | 01-APR-00:10 | 68669.43 | 27-APR-14:40 | 68669.43 | 27-APR-14:40 | 5668.62 | 28-APR-13:00 | 16464.72 | 27-APR-15:00 | 0.00 |
May | 0.101730E+11 | 0.247120E+10 | 167.59 | 0.883548E+10 | 0.133755E+10 | 0.00 | 1.00 | 04-MAY-13:05 | 0.00 | 01-MAY-00:10 | 65291.19 | 04-MAY-14:50 | 65291.19 | 04-MAY-14:50 | 8395.09 | 05-MAY-18:00 | 14684.14 | 04-MAY-15:00 | 0.00 |
June | 0.184640E+11 | 0.448956E+10 | 271.78 | 0.167454E+11 | 0.171866E+10 | 0.00 | 1.00 | 09-JUN-14:05 | 0.00 | 01-JUN-00:10 | 70986.53 | 28-JUN-15:20 | 70986.53 | 28-JUN-15:20 | 7300.82 | 12-JUN-12:40 | 16641.06 | 28-JUN-15:20 | 0.00 |
July | 0.342620E+11 | 0.817000E+10 | 353.49 | 0.296813E+11 | 0.458066E+10 | 0.00 | 1.00 | 06-JUL-15:10 | 0.00 | 01-JUL-00:10 | 85761.51 | 31-JUL-14:40 | 80289.77 | 24-JUL-15:00 | 14577.01 | 31-JUL-10:05 | 22017.00 | 24-JUL-15:00 | 0.00 |
August | 0.445529E+11 | 0.107260E+11 | 378.89 | 0.383593E+11 | 0.619361E+10 | 0.00 | 1.00 | 07-AUG-10:20 | 0.00 | 01-AUG-00:10 | 90801.59 | 10-AUG-14:50 | 85634.58 | 10-AUG-15:20 | 20842.10 | 30-AUG-13:00 | 23680.26 | 10-AUG-15:40 | 0.00 |
September | 0.164305E+11 | 0.394339E+10 | 231.52 | 0.130325E+11 | 0.339799E+10 | 0.00 | 1.00 | 08-SEP-14:30 | 0.00 | 01-SEP-00:10 | 73145.10 | 14-SEP-14:00 | 66000.23 | 14-SEP-14:40 | 17072.29 | 14-SEP-13:00 | 16358.38 | 14-SEP-14:00 | 0.00 |
October | 0.195917E+10 | 0.507030E+09 | 63.07 | 0.177951E+10 | 0.179664E+09 | 0.00 | 0.91 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 34606.16 | 04-OCT-15:00 | 34606.16 | 04-OCT-15:00 | 4080.46 | 08-OCT-13:40 | 7884.38 | 04-OCT-15:00 | 0.00 |
November | 0.559982E+09 | 0.137637E+09 | 8.50 | 0.383438E+09 | 0.176543E+09 | 0.00 | 0.76 | 04-NOV-13:40 | 0.00 | 01-NOV-00:10 | 27958.10 | 04-NOV-13:40 | 20895.06 | 04-NOV-14:00 | 8065.83 | 04-NOV-13:00 | 6634.88 | 04-NOV-13:40 | 0.00 |
December | 854396.45 | 244901.20 | 0.53 | 717155.09 | 137241.36 | 0.00 | 0.02 | 11-DEC-06:13 | 0.00 | 01-DEC-00:10 | 685.13 | 11-DEC-06:13 | 634.02 | 11-DEC-06:13 | 125.60 | 17-DEC-20:20 | 196.07 | 11-DEC-06:13 | 0.00 |
Annual Sum or Average | 0.132084E+12 | 0.318541E+11 | 1586.23 | 0.114142E+12 | 0.179412E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 854396.45 | 244901.20 | 0.53 | 717155.09 | 107779.54 | 0.00 | 0.02 | 0.00 | 685.13 | 634.02 | 114.99 | 196.07 | 0.00 | ||||||
Maximum of Months | 0.445529E+11 | 0.107260E+11 | 378.89 | 0.383593E+11 | 0.619361E+10 | 0.00 | 1.00 | 0.00 | 90801.59 | 85634.58 | 20842.10 | 23680.26 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 252.09 | 0.00 | 252.09 | 3.18 | 1921.95 | 0.00 | 0.00 | 0.00 |
February | 392.26 | 0.00 | 392.26 | 51.21 | 1708.11 | 0.00 | 0.00 | 0.00 |
March | 577.93 | 0.00 | 577.93 | 170.00 | 1370.54 | 0.00 | 0.00 | 0.00 |
April | 817.83 | 2.90 | 814.93 | 437.44 | 1088.56 | 0.00 | 0.00 | 0.00 |
May | 1052.34 | 31.26 | 1021.08 | 732.11 | 879.48 | 0.00 | 0.00 | 0.00 |
June | 1106.51 | 73.07 | 1033.44 | 858.23 | 690.71 | 0.00 | 0.00 | 0.00 |
July | 1051.68 | 82.46 | 969.22 | 961.83 | 624.45 | 0.00 | 0.00 | 0.00 |
August | 851.34 | 23.01 | 828.33 | 809.34 | 606.10 | 0.00 | 0.00 | 0.00 |
September | 661.29 | 0.20 | 661.10 | 439.14 | 873.07 | 0.00 | 0.00 | 0.00 |
October | 453.09 | 0.00 | 453.09 | 158.01 | 1177.19 | 0.00 | 0.00 | 0.00 |
November | 285.40 | 0.00 | 285.40 | 24.53 | 1510.90 | 0.00 | 0.00 | 0.00 |
December | 214.21 | 0.00 | 214.21 | 1.94 | 1910.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 644.24 | 17.87 | 626.37 | 389.43 | 1194.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 214.21 | 0.00 | 214.21 | 1.94 | 606.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.51 | 82.46 | 1033.44 | 961.83 | 1921.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 270.05 | 68.47 | 201.58 | 70.83 | 1214.76 | 0.00 | 0.00 | 0.00 |
February | 495.51 | 175.86 | 319.64 | 272.11 | 1061.05 | 0.00 | 0.00 | 0.00 |
March | 739.83 | 267.82 | 472.00 | 538.26 | 863.95 | 0.00 | 0.00 | 0.00 |
April | 1146.86 | 476.53 | 670.32 | 1060.37 | 687.37 | 0.00 | 0.00 | 0.00 |
May | 1220.36 | 424.29 | 796.07 | 1192.73 | 584.23 | 0.00 | 0.00 | 0.00 |
June | 1461.52 | 635.91 | 825.60 | 1551.99 | 468.24 | 0.00 | 0.00 | 0.00 |
July | 1361.01 | 610.90 | 750.12 | 1532.23 | 414.16 | 0.00 | 0.00 | 0.00 |
August | 1337.68 | 669.18 | 668.50 | 1574.83 | 397.73 | 0.00 | 0.00 | 0.00 |
September | 989.02 | 456.14 | 532.88 | 1014.07 | 556.15 | 0.00 | 0.00 | 0.00 |
October | 644.64 | 273.91 | 370.73 | 529.80 | 750.35 | 0.00 | 0.00 | 0.00 |
November | 315.97 | 89.20 | 226.77 | 138.42 | 966.98 | 0.00 | 0.00 | 0.00 |
December | 259.16 | 83.43 | 175.73 | 97.66 | 1218.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 855.04 | 353.41 | 501.63 | 800.52 | 763.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 259.16 | 68.47 | 175.73 | 70.83 | 397.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1461.52 | 669.18 | 825.60 | 1574.83 | 1218.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1113.78 | 661.37 | 452.41 | 879.95 | 1707.69 | 0.00 | 0.00 | 0.00 |
February | 1712.83 | 1060.26 | 652.57 | 1585.17 | 1532.63 | 0.00 | 0.00 | 0.00 |
March | 1842.51 | 982.59 | 859.92 | 1800.12 | 1340.48 | 0.00 | 0.00 | 0.00 |
April | 1945.34 | 844.65 | 1100.69 | 2022.91 | 1136.88 | 0.00 | 0.00 | 0.00 |
May | 1778.77 | 529.91 | 1248.86 | 1861.78 | 951.55 | 0.00 | 0.00 | 0.00 |
June | 1627.40 | 436.93 | 1190.47 | 1737.44 | 765.25 | 0.00 | 0.00 | 0.00 |
July | 1774.75 | 650.00 | 1124.75 | 2147.86 | 692.72 | 0.00 | 0.00 | 0.00 |
August | 1906.75 | 889.14 | 1017.60 | 2424.27 | 660.28 | 0.00 | 0.00 | 0.00 |
September | 2112.59 | 1166.64 | 945.95 | 2500.84 | 889.16 | 0.00 | 0.00 | 0.00 |
October | 1913.65 | 1181.53 | 732.11 | 2038.26 | 1160.78 | 0.00 | 0.00 | 0.00 |
November | 1131.41 | 648.39 | 483.02 | 984.57 | 1407.33 | 0.00 | 0.00 | 0.00 |
December | 1183.78 | 766.07 | 417.71 | 1062.23 | 1750.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.58 | 816.62 | 852.96 | 1754.54 | 1164.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1113.78 | 436.93 | 417.71 | 879.95 | 660.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2112.59 | 1181.53 | 1248.86 | 2500.84 | 1750.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.83 | 83.99 | 200.84 | 95.37 | 1223.20 | 0.00 | 0.00 | 0.00 |
February | 510.68 | 191.93 | 318.75 | 310.47 | 1075.70 | 0.00 | 0.00 | 0.00 |
March | 715.60 | 241.53 | 474.06 | 526.90 | 887.33 | 0.00 | 0.00 | 0.00 |
April | 1088.70 | 416.25 | 672.45 | 1003.44 | 734.61 | 0.00 | 0.00 | 0.00 |
May | 1400.91 | 569.11 | 831.80 | 1438.71 | 619.32 | 0.00 | 0.00 | 0.00 |
June | 1347.29 | 523.10 | 824.19 | 1419.09 | 495.46 | 0.00 | 0.00 | 0.00 |
July | 1664.39 | 874.88 | 789.51 | 1966.85 | 457.56 | 0.00 | 0.00 | 0.00 |
August | 1376.85 | 703.06 | 673.79 | 1667.75 | 437.35 | 0.00 | 0.00 | 0.00 |
September | 1121.23 | 537.99 | 583.24 | 1230.11 | 589.19 | 0.00 | 0.00 | 0.00 |
October | 638.32 | 260.08 | 378.24 | 538.52 | 777.94 | 0.00 | 0.00 | 0.00 |
November | 317.88 | 89.66 | 228.23 | 147.48 | 969.10 | 0.00 | 0.00 | 0.00 |
December | 267.24 | 91.58 | 175.66 | 123.63 | 1226.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 896.83 | 383.38 | 513.45 | 876.13 | 789.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 267.24 | 83.99 | 175.66 | 95.37 | 437.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1664.39 | 874.88 | 831.80 | 1966.85 | 1226.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.03 | 0.00 | 84.03 | 0.70 | 668.31 | 0.00 | 0.00 | 0.00 |
February | 130.75 | 0.00 | 130.75 | 16.76 | 592.84 | 0.00 | 0.00 | 0.00 |
March | 192.64 | 0.00 | 192.64 | 60.92 | 472.38 | 0.00 | 0.00 | 0.00 |
April | 272.60 | 0.97 | 271.63 | 156.72 | 367.35 | 0.00 | 0.00 | 0.00 |
May | 350.77 | 10.42 | 340.35 | 257.03 | 298.62 | 0.00 | 0.00 | 0.00 |
June | 368.82 | 24.36 | 344.47 | 296.90 | 234.92 | 0.00 | 0.00 | 0.00 |
July | 350.55 | 27.48 | 323.06 | 328.56 | 213.84 | 0.00 | 0.00 | 0.00 |
August | 283.77 | 7.67 | 276.10 | 273.94 | 211.84 | 0.00 | 0.00 | 0.00 |
September | 220.42 | 0.06 | 220.36 | 145.58 | 315.20 | 0.00 | 0.00 | 0.00 |
October | 151.03 | 0.00 | 151.03 | 48.22 | 433.05 | 0.00 | 0.00 | 0.00 |
November | 95.13 | 0.00 | 95.13 | 6.58 | 557.38 | 0.00 | 0.00 | 0.00 |
December | 71.40 | 0.00 | 71.40 | 0.24 | 685.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.74 | 5.96 | 208.78 | 133.43 | 420.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.40 | 0.00 | 71.40 | 0.24 | 211.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.82 | 27.48 | 344.47 | 328.56 | 685.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.03 | 0.00 | 84.03 | 0.70 | 668.35 | 0.00 | 0.00 | 0.00 |
February | 130.75 | 0.00 | 130.75 | 16.76 | 592.88 | 0.00 | 0.00 | 0.00 |
March | 192.65 | 0.00 | 192.65 | 60.92 | 472.41 | 0.00 | 0.00 | 0.00 |
April | 272.61 | 0.97 | 271.65 | 156.73 | 367.38 | 0.00 | 0.00 | 0.00 |
May | 350.78 | 10.42 | 340.36 | 257.04 | 298.64 | 0.00 | 0.00 | 0.00 |
June | 368.84 | 24.36 | 344.48 | 296.92 | 234.93 | 0.00 | 0.00 | 0.00 |
July | 350.56 | 27.49 | 323.08 | 328.58 | 213.85 | 0.00 | 0.00 | 0.00 |
August | 283.78 | 7.67 | 276.11 | 273.95 | 211.85 | 0.00 | 0.00 | 0.00 |
September | 220.43 | 0.07 | 220.37 | 145.59 | 315.22 | 0.00 | 0.00 | 0.00 |
October | 151.03 | 0.00 | 151.03 | 48.22 | 433.07 | 0.00 | 0.00 | 0.00 |
November | 95.14 | 0.00 | 95.14 | 6.58 | 557.41 | 0.00 | 0.00 | 0.00 |
December | 71.40 | 0.00 | 71.40 | 0.24 | 685.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.75 | 5.96 | 208.79 | 133.43 | 420.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.40 | 0.00 | 71.40 | 0.24 | 211.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.84 | 27.49 | 344.48 | 328.58 | 685.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.03 | 0.00 | 84.03 | 0.70 | 668.35 | 0.00 | 0.00 | 0.00 |
February | 130.75 | 0.00 | 130.75 | 16.76 | 592.88 | 0.00 | 0.00 | 0.00 |
March | 192.65 | 0.00 | 192.65 | 60.92 | 472.41 | 0.00 | 0.00 | 0.00 |
April | 272.61 | 0.97 | 271.65 | 156.73 | 367.38 | 0.00 | 0.00 | 0.00 |
May | 350.78 | 10.42 | 340.36 | 257.04 | 298.64 | 0.00 | 0.00 | 0.00 |
June | 368.84 | 24.36 | 344.48 | 296.92 | 234.93 | 0.00 | 0.00 | 0.00 |
July | 350.56 | 27.49 | 323.08 | 328.58 | 213.85 | 0.00 | 0.00 | 0.00 |
August | 283.78 | 7.67 | 276.11 | 273.95 | 211.85 | 0.00 | 0.00 | 0.00 |
September | 220.43 | 0.07 | 220.37 | 145.59 | 315.22 | 0.00 | 0.00 | 0.00 |
October | 151.03 | 0.00 | 151.03 | 48.22 | 433.07 | 0.00 | 0.00 | 0.00 |
November | 95.14 | 0.00 | 95.14 | 6.58 | 557.41 | 0.00 | 0.00 | 0.00 |
December | 71.40 | 0.00 | 71.40 | 0.24 | 685.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 214.75 | 5.96 | 208.79 | 133.43 | 420.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.40 | 0.00 | 71.40 | 0.24 | 211.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.84 | 27.49 | 344.48 | 328.58 | 685.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 259.78 | 65.86 | 193.92 | 66.63 | 1218.92 | 0.00 | 0.00 | 0.00 |
February | 476.68 | 169.18 | 307.49 | 260.43 | 1067.11 | 0.00 | 0.00 | 0.00 |
March | 711.71 | 257.65 | 454.07 | 528.57 | 867.84 | 0.00 | 0.00 | 0.00 |
April | 1103.27 | 458.43 | 644.85 | 1040.57 | 685.06 | 0.00 | 0.00 | 0.00 |
May | 1173.98 | 408.17 | 765.82 | 1170.41 | 582.13 | 0.00 | 0.00 | 0.00 |
June | 1405.98 | 611.75 | 794.23 | 1512.90 | 473.41 | 0.00 | 0.00 | 0.00 |
July | 1309.29 | 587.68 | 721.61 | 1490.48 | 417.49 | 0.00 | 0.00 | 0.00 |
August | 1286.85 | 643.76 | 643.09 | 1523.35 | 411.78 | 0.00 | 0.00 | 0.00 |
September | 951.44 | 438.81 | 512.63 | 974.49 | 586.30 | 0.00 | 0.00 | 0.00 |
October | 620.14 | 263.50 | 356.64 | 500.28 | 801.03 | 0.00 | 0.00 | 0.00 |
November | 303.96 | 85.81 | 218.15 | 127.61 | 1027.09 | 0.00 | 0.00 | 0.00 |
December | 249.32 | 80.26 | 169.05 | 90.22 | 1260.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.55 | 339.98 | 482.56 | 776.51 | 781.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 249.32 | 65.86 | 169.05 | 66.63 | 411.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1405.98 | 643.76 | 794.23 | 1523.35 | 1260.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.27 | 2.60 | 7.67 | 2.63 | 48.20 | 0.00 | 0.00 | 0.00 |
February | 18.85 | 6.69 | 12.16 | 10.30 | 42.19 | 0.00 | 0.00 | 0.00 |
March | 28.14 | 10.19 | 17.95 | 20.90 | 34.31 | 0.00 | 0.00 | 0.00 |
April | 43.62 | 18.13 | 25.50 | 41.14 | 27.09 | 0.00 | 0.00 | 0.00 |
May | 46.42 | 16.14 | 30.28 | 46.28 | 23.02 | 0.00 | 0.00 | 0.00 |
June | 55.59 | 24.19 | 31.40 | 59.82 | 18.72 | 0.00 | 0.00 | 0.00 |
July | 51.77 | 23.24 | 28.53 | 58.93 | 16.51 | 0.00 | 0.00 | 0.00 |
August | 50.88 | 25.45 | 25.43 | 60.23 | 16.28 | 0.00 | 0.00 | 0.00 |
September | 37.62 | 17.35 | 20.27 | 38.53 | 23.18 | 0.00 | 0.00 | 0.00 |
October | 24.52 | 10.42 | 14.10 | 19.78 | 31.67 | 0.00 | 0.00 | 0.00 |
November | 12.02 | 3.39 | 8.63 | 5.05 | 40.61 | 0.00 | 0.00 | 0.00 |
December | 9.86 | 3.17 | 6.68 | 3.57 | 49.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.52 | 13.44 | 19.08 | 30.70 | 30.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.86 | 2.60 | 6.68 | 2.63 | 16.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.59 | 25.45 | 31.40 | 60.23 | 49.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 371.27 | 220.46 | 150.81 | 296.20 | 595.48 | 0.00 | 0.00 | 0.00 |
February | 570.96 | 353.43 | 217.53 | 534.85 | 542.65 | 0.00 | 0.00 | 0.00 |
March | 614.19 | 327.54 | 286.65 | 613.21 | 473.29 | 0.00 | 0.00 | 0.00 |
April | 648.46 | 281.56 | 366.91 | 692.71 | 391.94 | 0.00 | 0.00 | 0.00 |
May | 592.94 | 176.64 | 416.30 | 640.94 | 325.89 | 0.00 | 0.00 | 0.00 |
June | 542.48 | 145.65 | 396.83 | 598.32 | 261.18 | 0.00 | 0.00 | 0.00 |
July | 591.60 | 216.67 | 374.93 | 729.37 | 241.57 | 0.00 | 0.00 | 0.00 |
August | 635.60 | 296.39 | 339.21 | 817.11 | 237.66 | 0.00 | 0.00 | 0.00 |
September | 704.22 | 388.89 | 315.33 | 836.95 | 330.84 | 0.00 | 0.00 | 0.00 |
October | 637.90 | 393.85 | 244.04 | 680.11 | 437.48 | 0.00 | 0.00 | 0.00 |
November | 377.15 | 216.14 | 161.01 | 326.23 | 519.58 | 0.00 | 0.00 | 0.00 |
December | 394.60 | 255.36 | 139.24 | 353.60 | 627.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.54 | 272.21 | 284.33 | 593.56 | 414.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 371.27 | 145.65 | 139.24 | 296.20 | 237.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 704.22 | 393.85 | 416.30 | 836.95 | 627.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 371.27 | 220.46 | 150.81 | 296.20 | 595.48 | 0.00 | 0.00 | 0.00 |
February | 570.96 | 353.43 | 217.53 | 534.85 | 542.65 | 0.00 | 0.00 | 0.00 |
March | 614.19 | 327.54 | 286.65 | 613.21 | 473.29 | 0.00 | 0.00 | 0.00 |
April | 648.46 | 281.56 | 366.91 | 692.71 | 391.94 | 0.00 | 0.00 | 0.00 |
May | 592.94 | 176.64 | 416.30 | 640.94 | 325.89 | 0.00 | 0.00 | 0.00 |
June | 542.48 | 145.65 | 396.83 | 598.32 | 261.18 | 0.00 | 0.00 | 0.00 |
July | 591.60 | 216.67 | 374.93 | 729.37 | 241.57 | 0.00 | 0.00 | 0.00 |
August | 635.60 | 296.39 | 339.21 | 817.11 | 237.66 | 0.00 | 0.00 | 0.00 |
September | 704.22 | 388.89 | 315.33 | 836.95 | 330.84 | 0.00 | 0.00 | 0.00 |
October | 637.90 | 393.85 | 244.04 | 680.11 | 437.48 | 0.00 | 0.00 | 0.00 |
November | 377.15 | 216.14 | 161.01 | 326.23 | 519.58 | 0.00 | 0.00 | 0.00 |
December | 394.60 | 255.36 | 139.24 | 353.60 | 627.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.54 | 272.21 | 284.33 | 593.56 | 414.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 371.27 | 145.65 | 139.24 | 296.20 | 237.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 704.22 | 393.85 | 416.30 | 836.95 | 627.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 371.25 | 220.45 | 150.80 | 296.18 | 595.45 | 0.00 | 0.00 | 0.00 |
February | 570.92 | 353.41 | 217.51 | 534.82 | 542.62 | 0.00 | 0.00 | 0.00 |
March | 614.15 | 327.52 | 286.63 | 613.17 | 473.26 | 0.00 | 0.00 | 0.00 |
April | 648.42 | 281.54 | 366.88 | 692.67 | 391.91 | 0.00 | 0.00 | 0.00 |
May | 592.90 | 176.63 | 416.27 | 640.90 | 325.87 | 0.00 | 0.00 | 0.00 |
June | 542.45 | 145.64 | 396.81 | 598.28 | 261.16 | 0.00 | 0.00 | 0.00 |
July | 591.56 | 216.66 | 374.90 | 729.33 | 241.55 | 0.00 | 0.00 | 0.00 |
August | 635.56 | 296.37 | 339.19 | 817.05 | 237.65 | 0.00 | 0.00 | 0.00 |
September | 704.17 | 388.87 | 315.31 | 836.90 | 330.82 | 0.00 | 0.00 | 0.00 |
October | 637.86 | 393.83 | 244.03 | 680.07 | 437.45 | 0.00 | 0.00 | 0.00 |
November | 377.12 | 216.12 | 161.00 | 326.21 | 519.55 | 0.00 | 0.00 | 0.00 |
December | 394.58 | 255.35 | 139.23 | 353.58 | 627.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.50 | 272.20 | 284.31 | 593.52 | 414.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 371.25 | 145.64 | 139.23 | 296.18 | 237.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 704.17 | 393.83 | 416.27 | 836.90 | 627.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 274.01 | 80.80 | 193.21 | 92.69 | 1228.73 | 0.00 | 0.00 | 0.00 |
February | 491.27 | 184.63 | 306.64 | 303.74 | 1086.15 | 0.00 | 0.00 | 0.00 |
March | 688.40 | 232.35 | 456.05 | 523.91 | 893.48 | 0.00 | 0.00 | 0.00 |
April | 1047.33 | 400.43 | 646.89 | 995.97 | 729.07 | 0.00 | 0.00 | 0.00 |
May | 1347.67 | 547.48 | 800.18 | 1415.20 | 623.09 | 0.00 | 0.00 | 0.00 |
June | 1296.09 | 503.23 | 792.86 | 1393.04 | 498.40 | 0.00 | 0.00 | 0.00 |
July | 1601.14 | 841.64 | 759.50 | 1911.73 | 473.10 | 0.00 | 0.00 | 0.00 |
August | 1324.52 | 676.34 | 648.18 | 1616.60 | 456.39 | 0.00 | 0.00 | 0.00 |
September | 1078.62 | 517.55 | 561.08 | 1185.72 | 626.01 | 0.00 | 0.00 | 0.00 |
October | 614.06 | 250.20 | 363.86 | 515.31 | 828.00 | 0.00 | 0.00 | 0.00 |
November | 305.80 | 86.25 | 219.55 | 138.72 | 1030.25 | 0.00 | 0.00 | 0.00 |
December | 257.08 | 88.10 | 168.99 | 117.85 | 1271.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 862.75 | 368.82 | 493.94 | 854.52 | 810.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.08 | 80.80 | 168.99 | 92.69 | 456.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1601.14 | 841.64 | 800.18 | 1911.73 | 1271.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.83 | 3.19 | 7.64 | 3.66 | 48.58 | 0.00 | 0.00 | 0.00 |
February | 19.42 | 7.30 | 12.12 | 12.01 | 42.95 | 0.00 | 0.00 | 0.00 |
March | 27.22 | 9.19 | 18.03 | 20.71 | 35.33 | 0.00 | 0.00 | 0.00 |
April | 41.41 | 15.83 | 25.58 | 39.38 | 28.83 | 0.00 | 0.00 | 0.00 |
May | 53.29 | 21.65 | 31.64 | 55.96 | 24.64 | 0.00 | 0.00 | 0.00 |
June | 51.25 | 19.90 | 31.35 | 55.08 | 19.71 | 0.00 | 0.00 | 0.00 |
July | 63.31 | 33.28 | 30.03 | 75.59 | 18.71 | 0.00 | 0.00 | 0.00 |
August | 52.37 | 26.74 | 25.63 | 63.92 | 18.05 | 0.00 | 0.00 | 0.00 |
September | 42.65 | 20.46 | 22.18 | 46.88 | 24.75 | 0.00 | 0.00 | 0.00 |
October | 24.28 | 9.89 | 14.39 | 20.37 | 32.74 | 0.00 | 0.00 | 0.00 |
November | 12.09 | 3.41 | 8.68 | 5.48 | 40.74 | 0.00 | 0.00 | 0.00 |
December | 10.16 | 3.48 | 6.68 | 4.66 | 50.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.11 | 14.58 | 19.53 | 33.79 | 32.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.16 | 3.19 | 6.68 | 3.66 | 18.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.31 | 33.28 | 31.64 | 75.59 | 50.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 252.09 | 0.00 | 252.09 | 1.43 | 2041.17 | 0.00 | 0.00 | 0.00 |
February | 392.26 | 0.00 | 392.26 | 43.73 | 1835.96 | 0.00 | 0.00 | 0.00 |
March | 577.93 | 0.00 | 577.93 | 152.95 | 1491.32 | 0.00 | 0.00 | 0.00 |
April | 817.83 | 2.90 | 814.93 | 416.06 | 1180.22 | 0.00 | 0.00 | 0.00 |
May | 1052.34 | 31.26 | 1021.08 | 708.40 | 955.29 | 0.00 | 0.00 | 0.00 |
June | 1106.51 | 73.07 | 1033.44 | 836.75 | 743.34 | 0.00 | 0.00 | 0.00 |
July | 1051.68 | 82.46 | 969.22 | 947.52 | 670.21 | 0.00 | 0.00 | 0.00 |
August | 851.34 | 23.01 | 828.33 | 793.10 | 659.46 | 0.00 | 0.00 | 0.00 |
September | 661.29 | 0.20 | 661.10 | 414.66 | 966.62 | 0.00 | 0.00 | 0.00 |
October | 453.09 | 0.00 | 453.09 | 134.94 | 1307.15 | 0.00 | 0.00 | 0.00 |
November | 285.40 | 0.00 | 285.40 | 18.68 | 1663.07 | 0.00 | 0.00 | 0.00 |
December | 214.21 | 0.00 | 214.21 | 0.66 | 2062.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 644.24 | 17.87 | 626.37 | 374.57 | 1295.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 214.21 | 0.00 | 214.21 | 0.66 | 659.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.51 | 82.46 | 1033.44 | 947.52 | 2062.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 270.05 | 68.47 | 201.58 | 65.57 | 1290.08 | 0.00 | 0.00 | 0.00 |
February | 495.51 | 175.86 | 319.64 | 256.99 | 1141.39 | 0.00 | 0.00 | 0.00 |
March | 739.83 | 267.82 | 472.00 | 514.82 | 938.80 | 0.00 | 0.00 | 0.00 |
April | 1146.86 | 476.53 | 670.32 | 1038.68 | 738.16 | 0.00 | 0.00 | 0.00 |
May | 1220.36 | 424.29 | 796.07 | 1176.84 | 623.39 | 0.00 | 0.00 | 0.00 |
June | 1461.52 | 635.91 | 825.60 | 1542.49 | 495.69 | 0.00 | 0.00 | 0.00 |
July | 1361.01 | 610.90 | 750.12 | 1524.51 | 437.36 | 0.00 | 0.00 | 0.00 |
August | 1337.68 | 669.18 | 668.50 | 1564.00 | 423.41 | 0.00 | 0.00 | 0.00 |
September | 989.02 | 456.14 | 532.88 | 995.99 | 604.19 | 0.00 | 0.00 | 0.00 |
October | 644.64 | 273.91 | 370.73 | 505.54 | 825.75 | 0.00 | 0.00 | 0.00 |
November | 315.97 | 89.20 | 226.77 | 127.75 | 1063.89 | 0.00 | 0.00 | 0.00 |
December | 259.16 | 83.43 | 175.73 | 90.71 | 1315.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 855.04 | 353.41 | 501.63 | 786.42 | 823.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 259.16 | 68.47 | 175.73 | 65.57 | 423.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1461.52 | 669.18 | 825.60 | 1564.00 | 1315.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1113.78 | 661.37 | 452.41 | 862.52 | 1821.43 | 0.00 | 0.00 | 0.00 |
February | 1712.83 | 1060.26 | 652.57 | 1558.85 | 1647.91 | 0.00 | 0.00 | 0.00 |
March | 1842.51 | 982.59 | 859.92 | 1781.67 | 1450.37 | 0.00 | 0.00 | 0.00 |
April | 1945.34 | 844.65 | 1100.69 | 2008.80 | 1219.09 | 0.00 | 0.00 | 0.00 |
May | 1778.77 | 529.91 | 1248.86 | 1852.87 | 1020.43 | 0.00 | 0.00 | 0.00 |
June | 1627.40 | 436.93 | 1190.47 | 1732.34 | 818.02 | 0.00 | 0.00 | 0.00 |
July | 1774.75 | 650.00 | 1124.75 | 2146.04 | 738.85 | 0.00 | 0.00 | 0.00 |
August | 1906.75 | 889.14 | 1017.60 | 2418.66 | 709.77 | 0.00 | 0.00 | 0.00 |
September | 2112.59 | 1166.64 | 945.95 | 2485.20 | 966.92 | 0.00 | 0.00 | 0.00 |
October | 1913.65 | 1181.53 | 732.11 | 2013.96 | 1272.15 | 0.00 | 0.00 | 0.00 |
November | 1131.41 | 648.39 | 483.02 | 960.16 | 1538.51 | 0.00 | 0.00 | 0.00 |
December | 1183.78 | 766.07 | 417.71 | 1040.80 | 1888.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.58 | 816.62 | 852.96 | 1739.33 | 1255.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1113.78 | 436.93 | 417.71 | 862.52 | 709.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2112.59 | 1181.53 | 1248.86 | 2485.20 | 1888.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.83 | 83.99 | 200.84 | 92.05 | 1299.05 | 0.00 | 0.00 | 0.00 |
February | 510.68 | 191.93 | 318.75 | 302.54 | 1154.93 | 0.00 | 0.00 | 0.00 |
March | 715.60 | 241.53 | 474.06 | 519.43 | 960.47 | 0.00 | 0.00 | 0.00 |
April | 1088.70 | 416.25 | 672.45 | 997.29 | 788.82 | 0.00 | 0.00 | 0.00 |
May | 1400.91 | 569.11 | 831.80 | 1434.14 | 664.76 | 0.00 | 0.00 | 0.00 |
June | 1347.29 | 523.10 | 824.19 | 1416.93 | 530.16 | 0.00 | 0.00 | 0.00 |
July | 1664.39 | 874.88 | 789.51 | 1966.60 | 488.72 | 0.00 | 0.00 | 0.00 |
August | 1376.85 | 703.06 | 673.79 | 1663.73 | 470.29 | 0.00 | 0.00 | 0.00 |
September | 1121.23 | 537.99 | 583.24 | 1221.15 | 641.16 | 0.00 | 0.00 | 0.00 |
October | 638.32 | 260.08 | 378.24 | 526.97 | 852.13 | 0.00 | 0.00 | 0.00 |
November | 317.88 | 89.66 | 228.23 | 141.09 | 1060.63 | 0.00 | 0.00 | 0.00 |
December | 267.24 | 91.58 | 175.66 | 119.23 | 1322.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 896.83 | 383.38 | 513.45 | 870.55 | 851.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 267.24 | 83.99 | 175.66 | 92.05 | 470.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1664.39 | 874.88 | 831.80 | 1966.60 | 1322.21 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.675195E+09 | 0.00 | 0.675195E+09 | 8509742.19 | 0.514775E+10 |
February | 0.948948E+09 | 0.00 | 0.948948E+09 | 0.123878E+09 | 0.413226E+10 |
March | 0.154793E+10 | 0.00 | 0.154793E+10 | 0.455335E+09 | 0.367087E+10 |
April | 0.211981E+10 | 7519582.16 | 0.211229E+10 | 0.113385E+10 | 0.282156E+10 |
May | 0.281859E+10 | 83735716.19 | 0.273485E+10 | 0.196087E+10 | 0.235559E+10 |
June | 0.286807E+10 | 0.189395E+09 | 0.267868E+10 | 0.222453E+10 | 0.179033E+10 |
July | 0.281681E+10 | 0.220850E+09 | 0.259596E+10 | 0.257617E+10 | 0.167251E+10 |
August | 0.228023E+10 | 61641115.79 | 0.221859E+10 | 0.216773E+10 | 0.162339E+10 |
September | 0.171407E+10 | 505449.15 | 0.171356E+10 | 0.113824E+10 | 0.226299E+10 |
October | 0.121357E+10 | 0.00 | 0.121357E+10 | 0.423220E+09 | 0.315299E+10 |
November | 0.739768E+09 | 0.00 | 0.739768E+09 | 63571532.82 | 0.391624E+10 |
December | 0.573741E+09 | 0.00 | 0.573741E+09 | 5208766.04 | 0.511662E+10 |
Annual Sum or Average | 0.203167E+11 | 0.563647E+09 | 0.197531E+11 | 0.122811E+11 | 0.376631E+11 |
Minimum of Months | 0.573741E+09 | 0.00 | 0.573741E+09 | 5208766.04 | 0.162339E+10 |
Maximum of Months | 0.286807E+10 | 0.220850E+09 | 0.273485E+10 | 0.257617E+10 | 0.514775E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723289E+09 | 0.183377E+09 | 0.539912E+09 | 0.189722E+09 | 0.325360E+10 |
February | 0.119873E+10 | 0.425452E+09 | 0.773277E+09 | 0.658285E+09 | 0.256690E+10 |
March | 0.198155E+10 | 0.717334E+09 | 0.126422E+10 | 0.144167E+10 | 0.231401E+10 |
April | 0.297265E+10 | 0.123517E+10 | 0.173748E+10 | 0.274849E+10 | 0.178165E+10 |
May | 0.326861E+10 | 0.113641E+10 | 0.213220E+10 | 0.319461E+10 | 0.156480E+10 |
June | 0.378825E+10 | 0.164829E+10 | 0.213997E+10 | 0.402275E+10 | 0.121367E+10 |
July | 0.364534E+10 | 0.163623E+10 | 0.200911E+10 | 0.410394E+10 | 0.110929E+10 |
August | 0.358285E+10 | 0.179234E+10 | 0.179051E+10 | 0.421802E+10 | 0.106529E+10 |
September | 0.256354E+10 | 0.118232E+10 | 0.138122E+10 | 0.262847E+10 | 0.144153E+10 |
October | 0.172661E+10 | 0.733643E+09 | 0.992967E+09 | 0.141902E+10 | 0.200975E+10 |
November | 0.818989E+09 | 0.231208E+09 | 0.587782E+09 | 0.358774E+09 | 0.250641E+10 |
December | 0.694147E+09 | 0.223465E+09 | 0.470682E+09 | 0.261581E+09 | 0.326407E+10 |
Annual Sum or Average | 0.269646E+11 | 0.111452E+11 | 0.158193E+11 | 0.252453E+11 | 0.240910E+11 |
Minimum of Months | 0.694147E+09 | 0.183377E+09 | 0.470682E+09 | 0.189722E+09 | 0.106529E+10 |
Maximum of Months | 0.378825E+10 | 0.179234E+10 | 0.213997E+10 | 0.421802E+10 | 0.326407E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298316E+10 | 0.177141E+10 | 0.121175E+10 | 0.235686E+10 | 0.457387E+10 |
February | 0.414367E+10 | 0.256498E+10 | 0.157869E+10 | 0.383485E+10 | 0.370773E+10 |
March | 0.493498E+10 | 0.263176E+10 | 0.230322E+10 | 0.482143E+10 | 0.359033E+10 |
April | 0.504233E+10 | 0.218934E+10 | 0.285299E+10 | 0.524337E+10 | 0.294679E+10 |
May | 0.476426E+10 | 0.141931E+10 | 0.334495E+10 | 0.498659E+10 | 0.254862E+10 |
June | 0.421823E+10 | 0.113253E+10 | 0.308570E+10 | 0.450343E+10 | 0.198352E+10 |
July | 0.475350E+10 | 0.174097E+10 | 0.301253E+10 | 0.575282E+10 | 0.185538E+10 |
August | 0.510703E+10 | 0.238148E+10 | 0.272555E+10 | 0.649317E+10 | 0.176849E+10 |
September | 0.547584E+10 | 0.302393E+10 | 0.245191E+10 | 0.648218E+10 | 0.230469E+10 |
October | 0.512551E+10 | 0.316462E+10 | 0.196090E+10 | 0.545928E+10 | 0.310904E+10 |
November | 0.293262E+10 | 0.168063E+10 | 0.125199E+10 | 0.255200E+10 | 0.364779E+10 |
December | 0.317064E+10 | 0.205184E+10 | 0.111880E+10 | 0.284509E+10 | 0.468746E+10 |
Annual Sum or Average | 0.526517E+11 | 0.257528E+11 | 0.268989E+11 | 0.553311E+11 | 0.367237E+11 |
Minimum of Months | 0.293262E+10 | 0.113253E+10 | 0.111880E+10 | 0.235686E+10 | 0.176849E+10 |
Maximum of Months | 0.547584E+10 | 0.316462E+10 | 0.334495E+10 | 0.649317E+10 | 0.468746E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.762895E+09 | 0.224963E+09 | 0.537932E+09 | 0.255434E+09 | 0.327621E+10 |
February | 0.123544E+10 | 0.464312E+09 | 0.771130E+09 | 0.751086E+09 | 0.260232E+10 |
March | 0.191665E+10 | 0.646918E+09 | 0.126974E+10 | 0.141125E+10 | 0.237661E+10 |
April | 0.282192E+10 | 0.107892E+10 | 0.174300E+10 | 0.260092E+10 | 0.190412E+10 |
May | 0.375219E+10 | 0.152430E+10 | 0.222789E+10 | 0.385344E+10 | 0.165879E+10 |
June | 0.349218E+10 | 0.135589E+10 | 0.213629E+10 | 0.367828E+10 | 0.128424E+10 |
July | 0.445791E+10 | 0.234329E+10 | 0.211461E+10 | 0.526801E+10 | 0.122552E+10 |
August | 0.368776E+10 | 0.188306E+10 | 0.180469E+10 | 0.446691E+10 | 0.117139E+10 |
September | 0.290624E+10 | 0.139447E+10 | 0.151177E+10 | 0.318844E+10 | 0.152718E+10 |
October | 0.170968E+10 | 0.696610E+09 | 0.101307E+10 | 0.144237E+10 | 0.208363E+10 |
November | 0.823946E+09 | 0.232386E+09 | 0.591560E+09 | 0.382258E+09 | 0.251190E+10 |
December | 0.715776E+09 | 0.245277E+09 | 0.470499E+09 | 0.331130E+09 | 0.328423E+10 |
Annual Sum or Average | 0.282826E+11 | 0.120904E+11 | 0.161922E+11 | 0.276295E+11 | 0.249062E+11 |
Minimum of Months | 0.715776E+09 | 0.224963E+09 | 0.470499E+09 | 0.255434E+09 | 0.117139E+10 |
Maximum of Months | 0.445791E+10 | 0.234329E+10 | 0.222789E+10 | 0.526801E+10 | 0.328423E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225057E+09 | 0.00 | 0.225057E+09 | 1885297.13 | 0.179001E+10 |
February | 0.316305E+09 | 0.00 | 0.316305E+09 | 40556511.72 | 0.143419E+10 |
March | 0.515957E+09 | 0.00 | 0.515957E+09 | 0.163177E+09 | 0.126522E+10 |
April | 0.706578E+09 | 2506448.36 | 0.704072E+09 | 0.406225E+09 | 0.952180E+09 |
May | 0.939495E+09 | 27911025.41 | 0.911584E+09 | 0.688441E+09 | 0.799831E+09 |
June | 0.955989E+09 | 63129536.60 | 0.892860E+09 | 0.769575E+09 | 0.608911E+09 |
July | 0.938903E+09 | 73614410.82 | 0.865288E+09 | 0.880028E+09 | 0.572745E+09 |
August | 0.760048E+09 | 20546390.80 | 0.739502E+09 | 0.733721E+09 | 0.567384E+09 |
September | 0.571334E+09 | 168477.74 | 0.571166E+09 | 0.377349E+09 | 0.816988E+09 |
October | 0.404507E+09 | 0.00 | 0.404507E+09 | 0.129161E+09 | 0.115987E+10 |
November | 0.246581E+09 | 0.00 | 0.246581E+09 | 17065483.23 | 0.144472E+10 |
December | 0.191240E+09 | 0.00 | 0.191240E+09 | 636195.60 | 0.183604E+10 |
Annual Sum or Average | 0.677199E+10 | 0.187876E+09 | 0.658412E+10 | 0.420782E+10 | 0.132481E+11 |
Minimum of Months | 0.191240E+09 | 0.00 | 0.191240E+09 | 636195.60 | 0.567384E+09 |
Maximum of Months | 0.955989E+09 | 73614410.82 | 0.911584E+09 | 0.880028E+09 | 0.183604E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225067E+09 | 0.00 | 0.225067E+09 | 1885087.30 | 0.179012E+10 |
February | 0.316319E+09 | 0.00 | 0.316319E+09 | 40557020.40 | 0.143429E+10 |
March | 0.515981E+09 | 0.00 | 0.515981E+09 | 0.163180E+09 | 0.126530E+10 |
April | 0.706611E+09 | 2506545.14 | 0.704105E+09 | 0.406239E+09 | 0.952241E+09 |
May | 0.939539E+09 | 27912103.15 | 0.911627E+09 | 0.688467E+09 | 0.799881E+09 |
June | 0.956034E+09 | 63131974.25 | 0.892902E+09 | 0.769605E+09 | 0.608949E+09 |
July | 0.938947E+09 | 73617253.32 | 0.865330E+09 | 0.880066E+09 | 0.572780E+09 |
August | 0.760085E+09 | 20547184.17 | 0.739538E+09 | 0.733755E+09 | 0.567418E+09 |
September | 0.571361E+09 | 168484.24 | 0.571193E+09 | 0.377363E+09 | 0.817037E+09 |
October | 0.404526E+09 | 0.00 | 0.404526E+09 | 0.129164E+09 | 0.115994E+10 |
November | 0.246592E+09 | 0.00 | 0.246592E+09 | 17065491.32 | 0.144481E+10 |
December | 0.191249E+09 | 0.00 | 0.191249E+09 | 636129.48 | 0.183616E+10 |
Annual Sum or Average | 0.677231E+10 | 0.187884E+09 | 0.658443E+10 | 0.420799E+10 | 0.132489E+11 |
Minimum of Months | 0.191249E+09 | 0.00 | 0.191249E+09 | 636129.48 | 0.567418E+09 |
Maximum of Months | 0.956034E+09 | 73617253.32 | 0.911627E+09 | 0.880066E+09 | 0.183616E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225067E+09 | 0.00 | 0.225067E+09 | 1885087.30 | 0.179012E+10 |
February | 0.316319E+09 | 0.00 | 0.316319E+09 | 40557020.40 | 0.143429E+10 |
March | 0.515981E+09 | 0.00 | 0.515981E+09 | 0.163180E+09 | 0.126530E+10 |
April | 0.706611E+09 | 2506545.14 | 0.704105E+09 | 0.406239E+09 | 0.952241E+09 |
May | 0.939539E+09 | 27912103.15 | 0.911627E+09 | 0.688467E+09 | 0.799881E+09 |
June | 0.956034E+09 | 63131974.25 | 0.892902E+09 | 0.769605E+09 | 0.608949E+09 |
July | 0.938947E+09 | 73617253.32 | 0.865330E+09 | 0.880066E+09 | 0.572780E+09 |
August | 0.760085E+09 | 20547184.17 | 0.739538E+09 | 0.733755E+09 | 0.567418E+09 |
September | 0.571361E+09 | 168484.24 | 0.571193E+09 | 0.377363E+09 | 0.817037E+09 |
October | 0.404526E+09 | 0.00 | 0.404526E+09 | 0.129164E+09 | 0.115994E+10 |
November | 0.246592E+09 | 0.00 | 0.246592E+09 | 17065491.32 | 0.144481E+10 |
December | 0.191249E+09 | 0.00 | 0.191249E+09 | 636129.48 | 0.183616E+10 |
Annual Sum or Average | 0.677231E+10 | 0.187884E+09 | 0.658443E+10 | 0.420799E+10 | 0.132489E+11 |
Minimum of Months | 0.191249E+09 | 0.00 | 0.191249E+09 | 636129.48 | 0.567418E+09 |
Maximum of Months | 0.956034E+09 | 73617253.32 | 0.911627E+09 | 0.880066E+09 | 0.183616E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.695803E+09 | 0.176409E+09 | 0.519393E+09 | 0.178466E+09 | 0.326477E+10 |
February | 0.115318E+10 | 0.409286E+09 | 0.743889E+09 | 0.630042E+09 | 0.258154E+10 |
March | 0.190625E+10 | 0.690078E+09 | 0.121617E+10 | 0.141573E+10 | 0.232442E+10 |
April | 0.285969E+10 | 0.118824E+10 | 0.167144E+10 | 0.269716E+10 | 0.177567E+10 |
May | 0.314439E+10 | 0.109323E+10 | 0.205116E+10 | 0.313482E+10 | 0.155917E+10 |
June | 0.364429E+10 | 0.158566E+10 | 0.205863E+10 | 0.392143E+10 | 0.122709E+10 |
July | 0.350680E+10 | 0.157406E+10 | 0.193275E+10 | 0.399209E+10 | 0.111821E+10 |
August | 0.344670E+10 | 0.172424E+10 | 0.172246E+10 | 0.408013E+10 | 0.110292E+10 |
September | 0.246612E+10 | 0.113740E+10 | 0.132873E+10 | 0.252589E+10 | 0.151968E+10 |
October | 0.166100E+10 | 0.705767E+09 | 0.955229E+09 | 0.133994E+10 | 0.214547E+10 |
November | 0.787866E+09 | 0.222422E+09 | 0.565444E+09 | 0.330756E+09 | 0.266221E+10 |
December | 0.667768E+09 | 0.214974E+09 | 0.452794E+09 | 0.241637E+09 | 0.337712E+10 |
Annual Sum or Average | 0.259398E+11 | 0.107218E+11 | 0.152181E+11 | 0.244881E+11 | 0.246583E+11 |
Minimum of Months | 0.667768E+09 | 0.176409E+09 | 0.452794E+09 | 0.178466E+09 | 0.110292E+10 |
Maximum of Months | 0.364429E+10 | 0.172424E+10 | 0.205863E+10 | 0.408013E+10 | 0.337712E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27511406.14 | 6975055.52 | 20536350.63 | 7056403.83 | 0.129086E+09 |
February | 45595516.94 | 16182811.94 | 29412705.00 | 24911277.58 | 0.102072E+09 |
March | 75371288.78 | 27285051.50 | 48086237.28 | 55976568.65 | 91905283.84 |
April | 0.113069E+09 | 46982009.39 | 66087428.66 | 0.106643E+09 | 70208330.59 |
May | 0.124326E+09 | 43225475.32 | 81100993.92 | 0.123948E+09 | 61648153.05 |
June | 0.144092E+09 | 62695431.61 | 81396504.59 | 0.155050E+09 | 48517881.07 |
July | 0.138656E+09 | 62236719.63 | 76419098.64 | 0.157844E+09 | 44213038.69 |
August | 0.136279E+09 | 68174718.27 | 68104583.89 | 0.161325E+09 | 43608628.44 |
September | 97508291.40 | 44971671.77 | 52536619.63 | 99871379.43 | 60086774.99 |
October | 65674294.15 | 27905404.48 | 37768889.66 | 52980216.73 | 84829999.45 |
November | 31151520.61 | 8794384.52 | 22357136.09 | 13077788.41 | 0.105261E+09 |
December | 26402954.98 | 8499892.46 | 17903062.52 | 9554115.71 | 0.133528E+09 |
Annual Sum or Average | 0.102564E+10 | 0.423929E+09 | 0.601710E+09 | 0.968237E+09 | 0.974966E+09 |
Minimum of Months | 26402954.98 | 6975055.52 | 17903062.52 | 7056403.83 | 43608628.44 |
Maximum of Months | 0.144092E+09 | 68174718.27 | 81396504.59 | 0.161325E+09 | 0.133528E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.994411E+09 | 0.590485E+09 | 0.403926E+09 | 0.793333E+09 | 0.159494E+10 |
February | 0.138126E+10 | 0.855017E+09 | 0.526243E+09 | 0.129392E+10 | 0.131278E+10 |
March | 0.164503E+10 | 0.877277E+09 | 0.767758E+09 | 0.164241E+10 | 0.126765E+10 |
April | 0.168082E+10 | 0.729800E+09 | 0.951019E+09 | 0.179551E+10 | 0.101590E+10 |
May | 0.158813E+10 | 0.473116E+09 | 0.111501E+10 | 0.171670E+10 | 0.872871E+09 |
June | 0.140611E+10 | 0.377521E+09 | 0.102859E+10 | 0.155085E+10 | 0.676970E+09 |
July | 0.158454E+10 | 0.580339E+09 | 0.100420E+10 | 0.195355E+10 | 0.647010E+09 |
August | 0.170238E+10 | 0.793847E+09 | 0.908538E+09 | 0.218854E+10 | 0.636554E+09 |
September | 0.182533E+10 | 0.100800E+10 | 0.817323E+09 | 0.216938E+10 | 0.857540E+09 |
October | 0.170855E+10 | 0.105490E+10 | 0.653648E+09 | 0.182160E+10 | 0.117174E+10 |
November | 0.977565E+09 | 0.560226E+09 | 0.417339E+09 | 0.845584E+09 | 0.134675E+10 |
December | 0.105691E+10 | 0.683965E+09 | 0.372941E+09 | 0.947075E+09 | 0.168017E+10 |
Annual Sum or Average | 0.175510E+11 | 0.858450E+10 | 0.896653E+10 | 0.187184E+11 | 0.130809E+11 |
Minimum of Months | 0.977565E+09 | 0.377521E+09 | 0.372941E+09 | 0.793333E+09 | 0.636554E+09 |
Maximum of Months | 0.182533E+10 | 0.105490E+10 | 0.111501E+10 | 0.218854E+10 | 0.168017E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.994411E+09 | 0.590485E+09 | 0.403926E+09 | 0.793333E+09 | 0.159494E+10 |
February | 0.138126E+10 | 0.855017E+09 | 0.526243E+09 | 0.129392E+10 | 0.131278E+10 |
March | 0.164503E+10 | 0.877277E+09 | 0.767758E+09 | 0.164241E+10 | 0.126765E+10 |
April | 0.168082E+10 | 0.729800E+09 | 0.951019E+09 | 0.179551E+10 | 0.101590E+10 |
May | 0.158813E+10 | 0.473116E+09 | 0.111501E+10 | 0.171670E+10 | 0.872871E+09 |
June | 0.140611E+10 | 0.377521E+09 | 0.102859E+10 | 0.155085E+10 | 0.676970E+09 |
July | 0.158454E+10 | 0.580339E+09 | 0.100420E+10 | 0.195355E+10 | 0.647010E+09 |
August | 0.170238E+10 | 0.793847E+09 | 0.908538E+09 | 0.218854E+10 | 0.636554E+09 |
September | 0.182533E+10 | 0.100800E+10 | 0.817323E+09 | 0.216938E+10 | 0.857540E+09 |
October | 0.170855E+10 | 0.105490E+10 | 0.653648E+09 | 0.182160E+10 | 0.117174E+10 |
November | 0.977565E+09 | 0.560226E+09 | 0.417339E+09 | 0.845584E+09 | 0.134675E+10 |
December | 0.105691E+10 | 0.683965E+09 | 0.372941E+09 | 0.947075E+09 | 0.168017E+10 |
Annual Sum or Average | 0.175510E+11 | 0.858450E+10 | 0.896653E+10 | 0.187184E+11 | 0.130809E+11 |
Minimum of Months | 0.977565E+09 | 0.377521E+09 | 0.372941E+09 | 0.793333E+09 | 0.636554E+09 |
Maximum of Months | 0.182533E+10 | 0.105490E+10 | 0.111501E+10 | 0.218854E+10 | 0.168017E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.994349E+09 | 0.590448E+09 | 0.403901E+09 | 0.793282E+09 | 0.159484E+10 |
February | 0.138117E+10 | 0.854963E+09 | 0.526209E+09 | 0.129384E+10 | 0.131270E+10 |
March | 0.164493E+10 | 0.877221E+09 | 0.767709E+09 | 0.164231E+10 | 0.126757E+10 |
April | 0.168071E+10 | 0.729754E+09 | 0.950959E+09 | 0.179540E+10 | 0.101584E+10 |
May | 0.158802E+10 | 0.473086E+09 | 0.111494E+10 | 0.171659E+10 | 0.872816E+09 |
June | 0.140602E+10 | 0.377497E+09 | 0.102852E+10 | 0.155075E+10 | 0.676927E+09 |
July | 0.158444E+10 | 0.580303E+09 | 0.100414E+10 | 0.195343E+10 | 0.646969E+09 |
August | 0.170228E+10 | 0.793797E+09 | 0.908480E+09 | 0.218840E+10 | 0.636514E+09 |
September | 0.182521E+10 | 0.100794E+10 | 0.817272E+09 | 0.216924E+10 | 0.857486E+09 |
October | 0.170844E+10 | 0.105483E+10 | 0.653607E+09 | 0.182149E+10 | 0.117167E+10 |
November | 0.977504E+09 | 0.560191E+09 | 0.417313E+09 | 0.845530E+09 | 0.134667E+10 |
December | 0.105684E+10 | 0.683922E+09 | 0.372918E+09 | 0.947015E+09 | 0.168006E+10 |
Annual Sum or Average | 0.175499E+11 | 0.858396E+10 | 0.896597E+10 | 0.187173E+11 | 0.130801E+11 |
Minimum of Months | 0.977504E+09 | 0.377497E+09 | 0.372918E+09 | 0.793282E+09 | 0.636514E+09 |
Maximum of Months | 0.182521E+10 | 0.105483E+10 | 0.111494E+10 | 0.218840E+10 | 0.168006E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.733902E+09 | 0.216414E+09 | 0.517488E+09 | 0.248252E+09 | 0.329103E+10 |
February | 0.118849E+10 | 0.446668E+09 | 0.741822E+09 | 0.734813E+09 | 0.262761E+10 |
March | 0.184381E+10 | 0.622336E+09 | 0.122148E+10 | 0.140323E+10 | 0.239309E+10 |
April | 0.271467E+10 | 0.103792E+10 | 0.167675E+10 | 0.258156E+10 | 0.188976E+10 |
May | 0.360959E+10 | 0.146638E+10 | 0.214321E+10 | 0.379047E+10 | 0.166888E+10 |
June | 0.335945E+10 | 0.130436E+10 | 0.205509E+10 | 0.361077E+10 | 0.129186E+10 |
July | 0.428849E+10 | 0.225425E+10 | 0.203424E+10 | 0.512038E+10 | 0.126716E+10 |
August | 0.354761E+10 | 0.181151E+10 | 0.173610E+10 | 0.432991E+10 | 0.122241E+10 |
September | 0.279579E+10 | 0.134148E+10 | 0.145431E+10 | 0.307339E+10 | 0.162261E+10 |
October | 0.164471E+10 | 0.670140E+09 | 0.974568E+09 | 0.138020E+10 | 0.221771E+10 |
November | 0.792633E+09 | 0.223555E+09 | 0.569078E+09 | 0.359562E+09 | 0.267040E+10 |
December | 0.688573E+09 | 0.235957E+09 | 0.452617E+09 | 0.315653E+09 | 0.340542E+10 |
Annual Sum or Average | 0.272077E+11 | 0.116310E+11 | 0.155767E+11 | 0.269482E+11 | 0.255679E+11 |
Minimum of Months | 0.688573E+09 | 0.216414E+09 | 0.452617E+09 | 0.248252E+09 | 0.122241E+10 |
Maximum of Months | 0.428849E+10 | 0.225425E+10 | 0.214321E+10 | 0.512038E+10 | 0.340542E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 29017830.29 | 8556830.13 | 20461000.16 | 9815644.96 | 0.130124E+09 |
February | 46991849.05 | 17660860.22 | 29330988.83 | 29053862.47 | 0.103893E+09 |
March | 72902677.81 | 24606606.33 | 48296071.48 | 55482640.18 | 94620557.63 |
April | 0.107336E+09 | 41038575.68 | 66297148.76 | 0.102072E+09 | 74719334.77 |
May | 0.142720E+09 | 57979403.98 | 84740578.40 | 0.149872E+09 | 65985853.44 |
June | 0.132830E+09 | 51573417.70 | 81256400.73 | 0.142766E+09 | 51078957.50 |
July | 0.169563E+09 | 89130945.21 | 80431978.00 | 0.202455E+09 | 50102404.09 |
August | 0.140269E+09 | 71625467.90 | 68643659.86 | 0.171201E+09 | 48332865.38 |
September | 0.110543E+09 | 53040965.04 | 57502084.26 | 0.121519E+09 | 64156386.07 |
October | 65030251.66 | 26496725.49 | 38533526.17 | 54572047.50 | 87686106.16 |
November | 31339996.48 | 8839182.66 | 22500813.82 | 14216775.21 | 0.105585E+09 |
December | 27225573.32 | 9329511.87 | 17896061.45 | 12480630.01 | 0.134647E+09 |
Annual Sum or Average | 0.107577E+10 | 0.459878E+09 | 0.615890E+09 | 0.106551E+10 | 0.101093E+10 |
Minimum of Months | 27225573.32 | 8556830.13 | 17896061.45 | 9815644.96 | 48332865.38 |
Maximum of Months | 0.169563E+09 | 89130945.21 | 84740578.40 | 0.202455E+09 | 0.134647E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.675195E+09 | 0.00 | 0.675195E+09 | 3827537.30 | 0.546707E+10 |
February | 0.948948E+09 | 0.00 | 0.948948E+09 | 0.105796E+09 | 0.444155E+10 |
March | 0.154793E+10 | 0.00 | 0.154793E+10 | 0.409652E+09 | 0.399434E+10 |
April | 0.211981E+10 | 7519582.16 | 0.211229E+10 | 0.107842E+10 | 0.305913E+10 |
May | 0.281859E+10 | 83735716.19 | 0.273485E+10 | 0.189739E+10 | 0.255864E+10 |
June | 0.286807E+10 | 0.189395E+09 | 0.267868E+10 | 0.216886E+10 | 0.192675E+10 |
July | 0.281681E+10 | 0.220850E+09 | 0.259596E+10 | 0.253784E+10 | 0.179509E+10 |
August | 0.228023E+10 | 61641115.79 | 0.221859E+10 | 0.212424E+10 | 0.176630E+10 |
September | 0.171407E+10 | 505449.15 | 0.171356E+10 | 0.107479E+10 | 0.250549E+10 |
October | 0.121357E+10 | 0.00 | 0.121357E+10 | 0.361436E+09 | 0.350108E+10 |
November | 0.739768E+09 | 0.00 | 0.739768E+09 | 48414290.65 | 0.431068E+10 |
December | 0.573741E+09 | 0.00 | 0.573741E+09 | 1770411.31 | 0.552395E+10 |
Annual Sum or Average | 0.203167E+11 | 0.563647E+09 | 0.197531E+11 | 0.118124E+11 | 0.408501E+11 |
Minimum of Months | 0.573741E+09 | 0.00 | 0.573741E+09 | 1770411.31 | 0.176630E+10 |
Maximum of Months | 0.286807E+10 | 0.220850E+09 | 0.273485E+10 | 0.253784E+10 | 0.552395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723289E+09 | 0.183377E+09 | 0.539912E+09 | 0.175618E+09 | 0.345534E+10 |
February | 0.119873E+10 | 0.425452E+09 | 0.773277E+09 | 0.621712E+09 | 0.276126E+10 |
March | 0.198155E+10 | 0.717334E+09 | 0.126422E+10 | 0.137889E+10 | 0.251449E+10 |
April | 0.297265E+10 | 0.123517E+10 | 0.173748E+10 | 0.269225E+10 | 0.191330E+10 |
May | 0.326861E+10 | 0.113641E+10 | 0.213220E+10 | 0.315205E+10 | 0.166970E+10 |
June | 0.378825E+10 | 0.164829E+10 | 0.213997E+10 | 0.399814E+10 | 0.128484E+10 |
July | 0.364534E+10 | 0.163623E+10 | 0.200911E+10 | 0.408325E+10 | 0.117143E+10 |
August | 0.358285E+10 | 0.179234E+10 | 0.179051E+10 | 0.418902E+10 | 0.113407E+10 |
September | 0.256354E+10 | 0.118232E+10 | 0.138122E+10 | 0.258160E+10 | 0.156607E+10 |
October | 0.172661E+10 | 0.733643E+09 | 0.992967E+09 | 0.135404E+10 | 0.221169E+10 |
November | 0.818989E+09 | 0.231208E+09 | 0.587782E+09 | 0.331137E+09 | 0.275759E+10 |
December | 0.694147E+09 | 0.223465E+09 | 0.470682E+09 | 0.242944E+09 | 0.352335E+10 |
Annual Sum or Average | 0.269646E+11 | 0.111452E+11 | 0.158193E+11 | 0.248007E+11 | 0.259631E+11 |
Minimum of Months | 0.694147E+09 | 0.183377E+09 | 0.470682E+09 | 0.175618E+09 | 0.113407E+10 |
Maximum of Months | 0.378825E+10 | 0.179234E+10 | 0.213997E+10 | 0.418902E+10 | 0.352335E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298316E+10 | 0.177141E+10 | 0.121175E+10 | 0.231017E+10 | 0.487853E+10 |
February | 0.414367E+10 | 0.256498E+10 | 0.157869E+10 | 0.377116E+10 | 0.398663E+10 |
March | 0.493498E+10 | 0.263176E+10 | 0.230322E+10 | 0.477202E+10 | 0.388466E+10 |
April | 0.504233E+10 | 0.218934E+10 | 0.285299E+10 | 0.520681E+10 | 0.315988E+10 |
May | 0.476426E+10 | 0.141931E+10 | 0.334495E+10 | 0.496273E+10 | 0.273311E+10 |
June | 0.421823E+10 | 0.113253E+10 | 0.308570E+10 | 0.449022E+10 | 0.212030E+10 |
July | 0.475350E+10 | 0.174097E+10 | 0.301253E+10 | 0.574796E+10 | 0.197894E+10 |
August | 0.510703E+10 | 0.238148E+10 | 0.272555E+10 | 0.647815E+10 | 0.190105E+10 |
September | 0.547584E+10 | 0.302393E+10 | 0.245191E+10 | 0.644163E+10 | 0.250626E+10 |
October | 0.512551E+10 | 0.316462E+10 | 0.196090E+10 | 0.539420E+10 | 0.340734E+10 |
November | 0.293262E+10 | 0.168063E+10 | 0.125199E+10 | 0.248874E+10 | 0.398782E+10 |
December | 0.317064E+10 | 0.205184E+10 | 0.111880E+10 | 0.278767E+10 | 0.505897E+10 |
Annual Sum or Average | 0.526517E+11 | 0.257528E+11 | 0.268989E+11 | 0.548514E+11 | 0.396035E+11 |
Minimum of Months | 0.293262E+10 | 0.113253E+10 | 0.111880E+10 | 0.231017E+10 | 0.190105E+10 |
Maximum of Months | 0.547584E+10 | 0.316462E+10 | 0.334495E+10 | 0.647815E+10 | 0.505897E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.762895E+09 | 0.224963E+09 | 0.537932E+09 | 0.246560E+09 | 0.347939E+10 |
February | 0.123544E+10 | 0.464312E+09 | 0.771130E+09 | 0.731914E+09 | 0.279402E+10 |
March | 0.191665E+10 | 0.646918E+09 | 0.126974E+10 | 0.139124E+10 | 0.257251E+10 |
April | 0.282192E+10 | 0.107892E+10 | 0.174300E+10 | 0.258497E+10 | 0.204463E+10 |
May | 0.375219E+10 | 0.152430E+10 | 0.222789E+10 | 0.384120E+10 | 0.178051E+10 |
June | 0.349218E+10 | 0.135589E+10 | 0.213629E+10 | 0.367268E+10 | 0.137417E+10 |
July | 0.445791E+10 | 0.234329E+10 | 0.211461E+10 | 0.526734E+10 | 0.130898E+10 |
August | 0.368776E+10 | 0.188306E+10 | 0.180469E+10 | 0.445614E+10 | 0.125964E+10 |
September | 0.290624E+10 | 0.139447E+10 | 0.151177E+10 | 0.316523E+10 | 0.166188E+10 |
October | 0.170968E+10 | 0.696610E+09 | 0.101307E+10 | 0.141144E+10 | 0.228234E+10 |
November | 0.823946E+09 | 0.232386E+09 | 0.591560E+09 | 0.365713E+09 | 0.274916E+10 |
December | 0.715776E+09 | 0.245277E+09 | 0.470499E+09 | 0.319347E+09 | 0.354140E+10 |
Annual Sum or Average | 0.282826E+11 | 0.120904E+11 | 0.161922E+11 | 0.274538E+11 | 0.268486E+11 |
Minimum of Months | 0.715776E+09 | 0.224963E+09 | 0.470499E+09 | 0.246560E+09 | 0.125964E+10 |
Maximum of Months | 0.445791E+10 | 0.234329E+10 | 0.222789E+10 | 0.526734E+10 | 0.354140E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.18 | 1921.95 | 252.09 | 0.00 | 252.09 | 0.00 | 0.00 |
February | 51.21 | 1708.11 | 392.26 | 0.00 | 392.26 | 0.00 | 0.00 |
March | 170.00 | 1370.54 | 577.93 | 0.00 | 577.93 | 0.00 | 0.00 |
April | 437.44 | 1088.56 | 817.83 | 2.90 | 814.93 | 0.00 | 0.00 |
May | 732.11 | 879.48 | 1052.34 | 31.26 | 1021.08 | 0.00 | 0.00 |
June | 858.23 | 690.71 | 1106.51 | 73.07 | 1033.44 | 0.00 | 0.00 |
July | 961.83 | 624.45 | 1051.68 | 82.46 | 969.22 | 0.00 | 0.00 |
August | 809.34 | 606.10 | 851.34 | 23.01 | 828.33 | 0.00 | 0.00 |
September | 439.14 | 873.07 | 661.29 | 0.20 | 661.10 | 0.00 | 0.00 |
October | 158.01 | 1177.19 | 453.09 | 0.00 | 453.09 | 0.00 | 0.00 |
November | 24.53 | 1510.90 | 285.40 | 0.00 | 285.40 | 0.00 | 0.00 |
December | 1.94 | 1910.33 | 214.21 | 0.00 | 214.21 | 0.00 | 0.00 |
Annual Sum or Average | 389.43 | 1194.29 | 644.24 | 17.87 | 626.37 | 0.00 | 0.00 |
Minimum of Months | 1.94 | 606.10 | 214.21 | 0.00 | 214.21 | 0.00 | 0.00 |
Maximum of Months | 961.83 | 1921.95 | 1106.51 | 82.46 | 1033.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 70.83 | 1214.76 | 270.05 | 68.47 | 201.58 | 0.00 | 0.00 |
February | 272.11 | 1061.05 | 495.51 | 175.86 | 319.64 | 0.00 | 0.00 |
March | 538.26 | 863.95 | 739.83 | 267.82 | 472.00 | 0.00 | 0.00 |
April | 1060.37 | 687.37 | 1146.86 | 476.53 | 670.32 | 0.00 | 0.00 |
May | 1192.73 | 584.23 | 1220.36 | 424.29 | 796.07 | 0.00 | 0.00 |
June | 1551.99 | 468.24 | 1461.52 | 635.91 | 825.60 | 0.00 | 0.00 |
July | 1532.23 | 414.16 | 1361.01 | 610.90 | 750.12 | 0.00 | 0.00 |
August | 1574.83 | 397.73 | 1337.68 | 669.18 | 668.50 | 0.00 | 0.00 |
September | 1014.07 | 556.15 | 989.02 | 456.14 | 532.88 | 0.00 | 0.00 |
October | 529.80 | 750.35 | 644.64 | 273.91 | 370.73 | 0.00 | 0.00 |
November | 138.42 | 966.98 | 315.97 | 89.20 | 226.77 | 0.00 | 0.00 |
December | 97.66 | 1218.66 | 259.16 | 83.43 | 175.73 | 0.00 | 0.00 |
Annual Sum or Average | 800.52 | 763.92 | 855.04 | 353.41 | 501.63 | 0.00 | 0.00 |
Minimum of Months | 70.83 | 397.73 | 259.16 | 68.47 | 175.73 | 0.00 | 0.00 |
Maximum of Months | 1574.83 | 1218.66 | 1461.52 | 669.18 | 825.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 879.95 | 1707.69 | 1113.78 | 661.37 | 452.41 | 0.00 | 0.00 |
February | 1585.17 | 1532.63 | 1712.83 | 1060.26 | 652.57 | 0.00 | 0.00 |
March | 1800.12 | 1340.48 | 1842.51 | 982.59 | 859.92 | 0.00 | 0.00 |
April | 2022.91 | 1136.88 | 1945.34 | 844.65 | 1100.69 | 0.00 | 0.00 |
May | 1861.78 | 951.55 | 1778.77 | 529.91 | 1248.86 | 0.00 | 0.00 |
June | 1737.44 | 765.25 | 1627.40 | 436.93 | 1190.47 | 0.00 | 0.00 |
July | 2147.86 | 692.72 | 1774.75 | 650.00 | 1124.75 | 0.00 | 0.00 |
August | 2424.27 | 660.28 | 1906.75 | 889.14 | 1017.60 | 0.00 | 0.00 |
September | 2500.84 | 889.16 | 2112.59 | 1166.64 | 945.95 | 0.00 | 0.00 |
October | 2038.26 | 1160.78 | 1913.65 | 1181.53 | 732.11 | 0.00 | 0.00 |
November | 984.57 | 1407.33 | 1131.41 | 648.39 | 483.02 | 0.00 | 0.00 |
December | 1062.23 | 1750.10 | 1183.78 | 766.07 | 417.71 | 0.00 | 0.00 |
Annual Sum or Average | 1754.54 | 1164.50 | 1669.58 | 816.62 | 852.96 | 0.00 | 0.00 |
Minimum of Months | 879.95 | 660.28 | 1113.78 | 436.93 | 417.71 | 0.00 | 0.00 |
Maximum of Months | 2500.84 | 1750.10 | 2112.59 | 1181.53 | 1248.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 95.37 | 1223.20 | 284.83 | 83.99 | 200.84 | 0.00 | 0.00 |
February | 310.47 | 1075.70 | 510.68 | 191.93 | 318.75 | 0.00 | 0.00 |
March | 526.90 | 887.33 | 715.60 | 241.53 | 474.06 | 0.00 | 0.00 |
April | 1003.44 | 734.61 | 1088.70 | 416.25 | 672.45 | 0.00 | 0.00 |
May | 1438.71 | 619.32 | 1400.91 | 569.11 | 831.80 | 0.00 | 0.00 |
June | 1419.09 | 495.46 | 1347.29 | 523.10 | 824.19 | 0.00 | 0.00 |
July | 1966.85 | 457.56 | 1664.39 | 874.88 | 789.51 | 0.00 | 0.00 |
August | 1667.75 | 437.35 | 1376.85 | 703.06 | 673.79 | 0.00 | 0.00 |
September | 1230.11 | 589.19 | 1121.23 | 537.99 | 583.24 | 0.00 | 0.00 |
October | 538.52 | 777.94 | 638.32 | 260.08 | 378.24 | 0.00 | 0.00 |
November | 147.48 | 969.10 | 317.88 | 89.66 | 228.23 | 0.00 | 0.00 |
December | 123.63 | 1226.19 | 267.24 | 91.58 | 175.66 | 0.00 | 0.00 |
Annual Sum or Average | 876.13 | 789.77 | 896.83 | 383.38 | 513.45 | 0.00 | 0.00 |
Minimum of Months | 95.37 | 437.35 | 267.24 | 83.99 | 175.66 | 0.00 | 0.00 |
Maximum of Months | 1966.85 | 1226.19 | 1664.39 | 874.88 | 831.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.11 | 2005.02 | 252.09 | 0.00 | 252.09 | 0.00 | 0.00 |
February | 50.29 | 1778.59 | 392.25 | 0.00 | 392.25 | 0.00 | 0.00 |
March | 182.77 | 1417.20 | 577.93 | 0.00 | 577.93 | 0.00 | 0.00 |
April | 470.18 | 1102.11 | 817.82 | 2.90 | 814.92 | 0.00 | 0.00 |
May | 771.12 | 895.91 | 1052.33 | 31.26 | 1021.07 | 0.00 | 0.00 |
June | 890.73 | 704.79 | 1106.50 | 73.07 | 1033.44 | 0.00 | 0.00 |
July | 985.72 | 641.54 | 1051.67 | 82.46 | 969.22 | 0.00 | 0.00 |
August | 821.85 | 635.54 | 851.34 | 23.01 | 828.32 | 0.00 | 0.00 |
September | 436.76 | 945.63 | 661.29 | 0.20 | 661.09 | 0.00 | 0.00 |
October | 144.67 | 1299.19 | 453.09 | 0.00 | 453.09 | 0.00 | 0.00 |
November | 19.75 | 1672.20 | 285.40 | 0.00 | 285.40 | 0.00 | 0.00 |
December | 0.71 | 2056.59 | 214.21 | 0.00 | 214.21 | 0.00 | 0.00 |
Annual Sum or Average | 400.30 | 1260.34 | 644.24 | 17.87 | 626.36 | 0.00 | 0.00 |
Minimum of Months | 0.71 | 635.54 | 214.21 | 0.00 | 214.21 | 0.00 | 0.00 |
Maximum of Months | 985.72 | 2056.59 | 1106.50 | 82.46 | 1033.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 69.27 | 1267.12 | 270.05 | 68.47 | 201.59 | 0.00 | 0.00 |
February | 270.73 | 1109.30 | 495.52 | 175.87 | 319.65 | 0.00 | 0.00 |
March | 549.47 | 902.15 | 739.85 | 267.83 | 472.02 | 0.00 | 0.00 |
April | 1081.71 | 712.14 | 1146.90 | 476.55 | 670.34 | 0.00 | 0.00 |
May | 1216.68 | 605.14 | 1220.40 | 424.31 | 796.09 | 0.00 | 0.00 |
June | 1572.72 | 492.13 | 1461.57 | 635.94 | 825.63 | 0.00 | 0.00 |
July | 1549.41 | 434.00 | 1361.06 | 610.92 | 750.14 | 0.00 | 0.00 |
August | 1583.58 | 428.07 | 1337.73 | 669.21 | 668.52 | 0.00 | 0.00 |
September | 1013.02 | 609.48 | 989.06 | 456.16 | 532.89 | 0.00 | 0.00 |
October | 520.06 | 832.70 | 644.66 | 273.92 | 370.74 | 0.00 | 0.00 |
November | 132.65 | 1067.70 | 315.98 | 89.20 | 226.78 | 0.00 | 0.00 |
December | 93.78 | 1310.73 | 259.17 | 83.44 | 175.74 | 0.00 | 0.00 |
Annual Sum or Average | 807.21 | 812.82 | 855.07 | 353.43 | 501.64 | 0.00 | 0.00 |
Minimum of Months | 69.27 | 428.07 | 259.17 | 68.47 | 175.74 | 0.00 | 0.00 |
Maximum of Months | 1583.58 | 1310.73 | 1461.57 | 669.21 | 825.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 888.57 | 1786.41 | 1113.79 | 661.37 | 452.42 | 0.00 | 0.00 |
February | 1604.53 | 1627.92 | 1712.84 | 1060.27 | 652.57 | 0.00 | 0.00 |
March | 1839.58 | 1419.83 | 1842.52 | 982.59 | 859.93 | 0.00 | 0.00 |
April | 2078.09 | 1175.79 | 1945.35 | 844.66 | 1100.69 | 0.00 | 0.00 |
May | 1922.79 | 977.66 | 1778.78 | 529.91 | 1248.86 | 0.00 | 0.00 |
June | 1794.92 | 783.51 | 1627.41 | 436.94 | 1190.47 | 0.00 | 0.00 |
July | 2188.07 | 724.68 | 1774.76 | 650.01 | 1124.75 | 0.00 | 0.00 |
August | 2451.27 | 712.97 | 1906.75 | 889.15 | 1017.61 | 0.00 | 0.00 |
September | 2510.80 | 992.50 | 2112.60 | 1166.65 | 945.96 | 0.00 | 0.00 |
October | 2040.28 | 1312.41 | 1913.66 | 1181.54 | 732.12 | 0.00 | 0.00 |
November | 978.66 | 1558.71 | 1131.42 | 648.40 | 483.02 | 0.00 | 0.00 |
December | 1060.77 | 1881.87 | 1183.79 | 766.07 | 417.71 | 0.00 | 0.00 |
Annual Sum or Average | 1780.64 | 1244.35 | 1669.58 | 816.62 | 852.96 | 0.00 | 0.00 |
Minimum of Months | 888.57 | 712.97 | 1113.79 | 436.94 | 417.71 | 0.00 | 0.00 |
Maximum of Months | 2510.80 | 1881.87 | 2112.60 | 1181.54 | 1248.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 96.35 | 1277.31 | 284.84 | 83.99 | 200.85 | 0.00 | 0.00 |
February | 315.75 | 1129.10 | 510.70 | 191.93 | 318.76 | 0.00 | 0.00 |
March | 544.62 | 928.80 | 715.62 | 241.54 | 474.08 | 0.00 | 0.00 |
April | 1035.35 | 757.90 | 1088.74 | 416.27 | 672.47 | 0.00 | 0.00 |
May | 1471.16 | 647.72 | 1400.95 | 569.13 | 831.82 | 0.00 | 0.00 |
June | 1448.12 | 518.11 | 1347.33 | 523.12 | 824.21 | 0.00 | 0.00 |
July | 1987.32 | 491.81 | 1664.45 | 874.92 | 789.53 | 0.00 | 0.00 |
August | 1680.52 | 474.44 | 1376.89 | 703.08 | 673.81 | 0.00 | 0.00 |
September | 1232.60 | 650.76 | 1121.27 | 538.01 | 583.26 | 0.00 | 0.00 |
October | 535.68 | 860.73 | 638.34 | 260.09 | 378.25 | 0.00 | 0.00 |
November | 144.20 | 1070.98 | 317.89 | 89.66 | 228.23 | 0.00 | 0.00 |
December | 122.51 | 1321.71 | 267.25 | 91.58 | 175.67 | 0.00 | 0.00 |
Annual Sum or Average | 888.31 | 842.81 | 896.86 | 383.40 | 513.46 | 0.00 | 0.00 |
Minimum of Months | 96.35 | 474.44 | 267.25 | 83.99 | 175.67 | 0.00 | 0.00 |
Maximum of Months | 1987.32 | 1321.71 | 1664.45 | 874.92 | 831.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.43 | 2041.17 | 252.09 | 0.00 | 252.09 | 0.00 | 0.00 |
February | 43.73 | 1835.96 | 392.26 | 0.00 | 392.26 | 0.00 | 0.00 |
March | 152.95 | 1491.32 | 577.93 | 0.00 | 577.93 | 0.00 | 0.00 |
April | 416.06 | 1180.22 | 817.83 | 2.90 | 814.93 | 0.00 | 0.00 |
May | 708.40 | 955.29 | 1052.34 | 31.26 | 1021.08 | 0.00 | 0.00 |
June | 836.75 | 743.34 | 1106.51 | 73.07 | 1033.44 | 0.00 | 0.00 |
July | 947.52 | 670.21 | 1051.68 | 82.46 | 969.22 | 0.00 | 0.00 |
August | 793.10 | 659.46 | 851.34 | 23.01 | 828.33 | 0.00 | 0.00 |
September | 414.66 | 966.62 | 661.29 | 0.20 | 661.10 | 0.00 | 0.00 |
October | 134.94 | 1307.15 | 453.09 | 0.00 | 453.09 | 0.00 | 0.00 |
November | 18.68 | 1663.07 | 285.40 | 0.00 | 285.40 | 0.00 | 0.00 |
December | 0.66 | 2062.41 | 214.21 | 0.00 | 214.21 | 0.00 | 0.00 |
Annual Sum or Average | 374.57 | 1295.35 | 644.24 | 17.87 | 626.37 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 659.46 | 214.21 | 0.00 | 214.21 | 0.00 | 0.00 |
Maximum of Months | 947.52 | 2062.41 | 1106.51 | 82.46 | 1033.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 65.57 | 1290.08 | 270.05 | 68.47 | 201.58 | 0.00 | 0.00 |
February | 256.99 | 1141.39 | 495.51 | 175.86 | 319.64 | 0.00 | 0.00 |
March | 514.82 | 938.80 | 739.83 | 267.82 | 472.00 | 0.00 | 0.00 |
April | 1038.68 | 738.16 | 1146.86 | 476.53 | 670.32 | 0.00 | 0.00 |
May | 1176.84 | 623.39 | 1220.36 | 424.29 | 796.07 | 0.00 | 0.00 |
June | 1542.49 | 495.69 | 1461.52 | 635.91 | 825.60 | 0.00 | 0.00 |
July | 1524.51 | 437.36 | 1361.01 | 610.90 | 750.12 | 0.00 | 0.00 |
August | 1564.00 | 423.41 | 1337.68 | 669.18 | 668.50 | 0.00 | 0.00 |
September | 995.99 | 604.19 | 989.02 | 456.14 | 532.88 | 0.00 | 0.00 |
October | 505.54 | 825.75 | 644.64 | 273.91 | 370.73 | 0.00 | 0.00 |
November | 127.75 | 1063.89 | 315.97 | 89.20 | 226.77 | 0.00 | 0.00 |
December | 90.71 | 1315.47 | 259.16 | 83.43 | 175.73 | 0.00 | 0.00 |
Annual Sum or Average | 786.42 | 823.29 | 855.04 | 353.41 | 501.63 | 0.00 | 0.00 |
Minimum of Months | 65.57 | 423.41 | 259.16 | 68.47 | 175.73 | 0.00 | 0.00 |
Maximum of Months | 1564.00 | 1315.47 | 1461.52 | 669.18 | 825.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 862.52 | 1821.43 | 1113.78 | 661.37 | 452.41 | 0.00 | 0.00 |
February | 1558.85 | 1647.91 | 1712.83 | 1060.26 | 652.57 | 0.00 | 0.00 |
March | 1781.67 | 1450.37 | 1842.51 | 982.59 | 859.92 | 0.00 | 0.00 |
April | 2008.80 | 1219.09 | 1945.34 | 844.65 | 1100.69 | 0.00 | 0.00 |
May | 1852.87 | 1020.43 | 1778.77 | 529.91 | 1248.86 | 0.00 | 0.00 |
June | 1732.34 | 818.02 | 1627.40 | 436.93 | 1190.47 | 0.00 | 0.00 |
July | 2146.04 | 738.85 | 1774.75 | 650.00 | 1124.75 | 0.00 | 0.00 |
August | 2418.66 | 709.77 | 1906.75 | 889.14 | 1017.60 | 0.00 | 0.00 |
September | 2485.20 | 966.92 | 2112.59 | 1166.64 | 945.95 | 0.00 | 0.00 |
October | 2013.96 | 1272.15 | 1913.65 | 1181.53 | 732.11 | 0.00 | 0.00 |
November | 960.16 | 1538.51 | 1131.41 | 648.39 | 483.02 | 0.00 | 0.00 |
December | 1040.80 | 1888.80 | 1183.78 | 766.07 | 417.71 | 0.00 | 0.00 |
Annual Sum or Average | 1739.33 | 1255.82 | 1669.58 | 816.62 | 852.96 | 0.00 | 0.00 |
Minimum of Months | 862.52 | 709.77 | 1113.78 | 436.93 | 417.71 | 0.00 | 0.00 |
Maximum of Months | 2485.20 | 1888.80 | 2112.59 | 1181.53 | 1248.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 92.05 | 1299.05 | 284.83 | 83.99 | 200.84 | 0.00 | 0.00 |
February | 302.54 | 1154.93 | 510.68 | 191.93 | 318.75 | 0.00 | 0.00 |
March | 519.43 | 960.47 | 715.60 | 241.53 | 474.06 | 0.00 | 0.00 |
April | 997.29 | 788.82 | 1088.70 | 416.25 | 672.45 | 0.00 | 0.00 |
May | 1434.14 | 664.76 | 1400.91 | 569.11 | 831.80 | 0.00 | 0.00 |
June | 1416.93 | 530.16 | 1347.29 | 523.10 | 824.19 | 0.00 | 0.00 |
July | 1966.60 | 488.72 | 1664.39 | 874.88 | 789.51 | 0.00 | 0.00 |
August | 1663.73 | 470.29 | 1376.85 | 703.06 | 673.79 | 0.00 | 0.00 |
September | 1221.15 | 641.16 | 1121.23 | 537.99 | 583.24 | 0.00 | 0.00 |
October | 526.97 | 852.13 | 638.32 | 260.08 | 378.24 | 0.00 | 0.00 |
November | 141.09 | 1060.63 | 317.88 | 89.66 | 228.23 | 0.00 | 0.00 |
December | 119.23 | 1322.21 | 267.24 | 91.58 | 175.66 | 0.00 | 0.00 |
Annual Sum or Average | 870.55 | 851.36 | 896.83 | 383.38 | 513.45 | 0.00 | 0.00 |
Minimum of Months | 92.05 | 470.29 | 267.24 | 83.99 | 175.66 | 0.00 | 0.00 |
Maximum of Months | 1966.60 | 1322.21 | 1664.39 | 874.88 | 831.80 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8509742.19 | 0.514775E+10 | 0.675195E+09 | 0.00 | 0.675195E+09 | 0.00 | 0.00 |
February | 0.123878E+09 | 0.413226E+10 | 0.948948E+09 | 0.00 | 0.948948E+09 | 0.00 | 0.00 |
March | 0.455335E+09 | 0.367087E+10 | 0.154793E+10 | 0.00 | 0.154793E+10 | 0.00 | 0.00 |
April | 0.113385E+10 | 0.282156E+10 | 0.211981E+10 | 7519582.16 | 0.211229E+10 | 0.00 | 0.00 |
May | 0.196087E+10 | 0.235559E+10 | 0.281859E+10 | 83735716.19 | 0.273485E+10 | 0.00 | 0.00 |
June | 0.222453E+10 | 0.179033E+10 | 0.286807E+10 | 0.189395E+09 | 0.267868E+10 | 0.00 | 0.00 |
July | 0.257617E+10 | 0.167251E+10 | 0.281681E+10 | 0.220850E+09 | 0.259596E+10 | 0.00 | 0.00 |
August | 0.216773E+10 | 0.162339E+10 | 0.228023E+10 | 61641115.79 | 0.221859E+10 | 0.00 | 0.00 |
September | 0.113824E+10 | 0.226299E+10 | 0.171407E+10 | 505449.15 | 0.171356E+10 | 0.00 | 0.00 |
October | 0.423220E+09 | 0.315299E+10 | 0.121357E+10 | 0.00 | 0.121357E+10 | 0.00 | 0.00 |
November | 63571532.82 | 0.391624E+10 | 0.739768E+09 | 0.00 | 0.739768E+09 | 0.00 | 0.00 |
December | 5208766.04 | 0.511662E+10 | 0.573741E+09 | 0.00 | 0.573741E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.122811E+11 | 0.376631E+11 | 0.203167E+11 | 0.563647E+09 | 0.197531E+11 | 0.00 | 0.00 |
Minimum of Months | 5208766.04 | 0.162339E+10 | 0.573741E+09 | 0.00 | 0.573741E+09 | 0.00 | 0.00 |
Maximum of Months | 0.257617E+10 | 0.514775E+10 | 0.286807E+10 | 0.220850E+09 | 0.273485E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.189722E+09 | 0.325360E+10 | 0.723289E+09 | 0.183377E+09 | 0.539912E+09 | 0.00 | 0.00 |
February | 0.658285E+09 | 0.256690E+10 | 0.119873E+10 | 0.425452E+09 | 0.773277E+09 | 0.00 | 0.00 |
March | 0.144167E+10 | 0.231401E+10 | 0.198155E+10 | 0.717334E+09 | 0.126422E+10 | 0.00 | 0.00 |
April | 0.274849E+10 | 0.178165E+10 | 0.297265E+10 | 0.123517E+10 | 0.173748E+10 | 0.00 | 0.00 |
May | 0.319461E+10 | 0.156480E+10 | 0.326861E+10 | 0.113641E+10 | 0.213220E+10 | 0.00 | 0.00 |
June | 0.402275E+10 | 0.121367E+10 | 0.378825E+10 | 0.164829E+10 | 0.213997E+10 | 0.00 | 0.00 |
July | 0.410394E+10 | 0.110929E+10 | 0.364534E+10 | 0.163623E+10 | 0.200911E+10 | 0.00 | 0.00 |
August | 0.421802E+10 | 0.106529E+10 | 0.358285E+10 | 0.179234E+10 | 0.179051E+10 | 0.00 | 0.00 |
September | 0.262847E+10 | 0.144153E+10 | 0.256354E+10 | 0.118232E+10 | 0.138122E+10 | 0.00 | 0.00 |
October | 0.141902E+10 | 0.200975E+10 | 0.172661E+10 | 0.733643E+09 | 0.992967E+09 | 0.00 | 0.00 |
November | 0.358774E+09 | 0.250641E+10 | 0.818989E+09 | 0.231208E+09 | 0.587782E+09 | 0.00 | 0.00 |
December | 0.261581E+09 | 0.326407E+10 | 0.694147E+09 | 0.223465E+09 | 0.470682E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.252453E+11 | 0.240910E+11 | 0.269646E+11 | 0.111452E+11 | 0.158193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.189722E+09 | 0.106529E+10 | 0.694147E+09 | 0.183377E+09 | 0.470682E+09 | 0.00 | 0.00 |
Maximum of Months | 0.421802E+10 | 0.326407E+10 | 0.378825E+10 | 0.179234E+10 | 0.213997E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.235686E+10 | 0.457387E+10 | 0.298316E+10 | 0.177141E+10 | 0.121175E+10 | 0.00 | 0.00 |
February | 0.383485E+10 | 0.370773E+10 | 0.414367E+10 | 0.256498E+10 | 0.157869E+10 | 0.00 | 0.00 |
March | 0.482143E+10 | 0.359033E+10 | 0.493498E+10 | 0.263176E+10 | 0.230322E+10 | 0.00 | 0.00 |
April | 0.524337E+10 | 0.294679E+10 | 0.504233E+10 | 0.218934E+10 | 0.285299E+10 | 0.00 | 0.00 |
May | 0.498659E+10 | 0.254862E+10 | 0.476426E+10 | 0.141931E+10 | 0.334495E+10 | 0.00 | 0.00 |
June | 0.450343E+10 | 0.198352E+10 | 0.421823E+10 | 0.113253E+10 | 0.308570E+10 | 0.00 | 0.00 |
July | 0.575282E+10 | 0.185538E+10 | 0.475350E+10 | 0.174097E+10 | 0.301253E+10 | 0.00 | 0.00 |
August | 0.649317E+10 | 0.176849E+10 | 0.510703E+10 | 0.238148E+10 | 0.272555E+10 | 0.00 | 0.00 |
September | 0.648218E+10 | 0.230469E+10 | 0.547584E+10 | 0.302393E+10 | 0.245191E+10 | 0.00 | 0.00 |
October | 0.545928E+10 | 0.310904E+10 | 0.512551E+10 | 0.316462E+10 | 0.196090E+10 | 0.00 | 0.00 |
November | 0.255200E+10 | 0.364779E+10 | 0.293262E+10 | 0.168063E+10 | 0.125199E+10 | 0.00 | 0.00 |
December | 0.284509E+10 | 0.468746E+10 | 0.317064E+10 | 0.205184E+10 | 0.111880E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.553311E+11 | 0.367237E+11 | 0.526517E+11 | 0.257528E+11 | 0.268989E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235686E+10 | 0.176849E+10 | 0.293262E+10 | 0.113253E+10 | 0.111880E+10 | 0.00 | 0.00 |
Maximum of Months | 0.649317E+10 | 0.468746E+10 | 0.547584E+10 | 0.316462E+10 | 0.334495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.255434E+09 | 0.327621E+10 | 0.762895E+09 | 0.224963E+09 | 0.537932E+09 | 0.00 | 0.00 |
February | 0.751086E+09 | 0.260232E+10 | 0.123544E+10 | 0.464312E+09 | 0.771130E+09 | 0.00 | 0.00 |
March | 0.141125E+10 | 0.237661E+10 | 0.191665E+10 | 0.646918E+09 | 0.126974E+10 | 0.00 | 0.00 |
April | 0.260092E+10 | 0.190412E+10 | 0.282192E+10 | 0.107892E+10 | 0.174300E+10 | 0.00 | 0.00 |
May | 0.385344E+10 | 0.165879E+10 | 0.375219E+10 | 0.152430E+10 | 0.222789E+10 | 0.00 | 0.00 |
June | 0.367828E+10 | 0.128424E+10 | 0.349218E+10 | 0.135589E+10 | 0.213629E+10 | 0.00 | 0.00 |
July | 0.526801E+10 | 0.122552E+10 | 0.445791E+10 | 0.234329E+10 | 0.211461E+10 | 0.00 | 0.00 |
August | 0.446691E+10 | 0.117139E+10 | 0.368776E+10 | 0.188306E+10 | 0.180469E+10 | 0.00 | 0.00 |
September | 0.318844E+10 | 0.152718E+10 | 0.290624E+10 | 0.139447E+10 | 0.151177E+10 | 0.00 | 0.00 |
October | 0.144237E+10 | 0.208363E+10 | 0.170968E+10 | 0.696610E+09 | 0.101307E+10 | 0.00 | 0.00 |
November | 0.382258E+09 | 0.251190E+10 | 0.823946E+09 | 0.232386E+09 | 0.591560E+09 | 0.00 | 0.00 |
December | 0.331130E+09 | 0.328423E+10 | 0.715776E+09 | 0.245277E+09 | 0.470499E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.276295E+11 | 0.249062E+11 | 0.282826E+11 | 0.120904E+11 | 0.161922E+11 | 0.00 | 0.00 |
Minimum of Months | 0.255434E+09 | 0.117139E+10 | 0.715776E+09 | 0.224963E+09 | 0.470499E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526801E+10 | 0.328423E+10 | 0.445791E+10 | 0.234329E+10 | 0.222789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5655471.74 | 0.537024E+10 | 0.675191E+09 | 0.00 | 0.675191E+09 | 0.00 | 0.00 |
February | 0.121671E+09 | 0.430276E+10 | 0.948943E+09 | 0.00 | 0.948943E+09 | 0.00 | 0.00 |
March | 0.489538E+09 | 0.379582E+10 | 0.154792E+10 | 0.00 | 0.154792E+10 | 0.00 | 0.00 |
April | 0.121870E+10 | 0.285666E+10 | 0.211980E+10 | 7519538.65 | 0.211228E+10 | 0.00 | 0.00 |
May | 0.206538E+10 | 0.239959E+10 | 0.281857E+10 | 83735231.71 | 0.273484E+10 | 0.00 | 0.00 |
June | 0.230878E+10 | 0.182681E+10 | 0.286806E+10 | 0.189393E+09 | 0.267866E+10 | 0.00 | 0.00 |
July | 0.264016E+10 | 0.171830E+10 | 0.281680E+10 | 0.220849E+09 | 0.259595E+10 | 0.00 | 0.00 |
August | 0.220123E+10 | 0.170222E+10 | 0.228022E+10 | 61640759.14 | 0.221858E+10 | 0.00 | 0.00 |
September | 0.113208E+10 | 0.245106E+10 | 0.171406E+10 | 505446.22 | 0.171355E+10 | 0.00 | 0.00 |
October | 0.387489E+09 | 0.347975E+10 | 0.121356E+10 | 0.00 | 0.121356E+10 | 0.00 | 0.00 |
November | 51196465.87 | 0.433434E+10 | 0.739764E+09 | 0.00 | 0.739764E+09 | 0.00 | 0.00 |
December | 1908454.56 | 0.550836E+10 | 0.573738E+09 | 0.00 | 0.573738E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126238E+11 | 0.397459E+11 | 0.203166E+11 | 0.563643E+09 | 0.197530E+11 | 0.00 | 0.00 |
Minimum of Months | 1908454.56 | 0.170222E+10 | 0.573738E+09 | 0.00 | 0.573738E+09 | 0.00 | 0.00 |
Maximum of Months | 0.264016E+10 | 0.550836E+10 | 0.286806E+10 | 0.220849E+09 | 0.273484E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.185523E+09 | 0.339385E+10 | 0.723314E+09 | 0.183384E+09 | 0.539930E+09 | 0.00 | 0.00 |
February | 0.654953E+09 | 0.268361E+10 | 0.119877E+10 | 0.425469E+09 | 0.773302E+09 | 0.00 | 0.00 |
March | 0.147170E+10 | 0.241632E+10 | 0.198162E+10 | 0.717363E+09 | 0.126426E+10 | 0.00 | 0.00 |
April | 0.280381E+10 | 0.184588E+10 | 0.297276E+10 | 0.123522E+10 | 0.173753E+10 | 0.00 | 0.00 |
May | 0.325877E+10 | 0.162082E+10 | 0.326872E+10 | 0.113646E+10 | 0.213226E+10 | 0.00 | 0.00 |
June | 0.407648E+10 | 0.127560E+10 | 0.378838E+10 | 0.164835E+10 | 0.214003E+10 | 0.00 | 0.00 |
July | 0.414993E+10 | 0.116242E+10 | 0.364546E+10 | 0.163629E+10 | 0.200917E+10 | 0.00 | 0.00 |
August | 0.424145E+10 | 0.114653E+10 | 0.358298E+10 | 0.179241E+10 | 0.179057E+10 | 0.00 | 0.00 |
September | 0.262576E+10 | 0.157977E+10 | 0.256363E+10 | 0.118237E+10 | 0.138126E+10 | 0.00 | 0.00 |
October | 0.139293E+10 | 0.223030E+10 | 0.172667E+10 | 0.733673E+09 | 0.992998E+09 | 0.00 | 0.00 |
November | 0.343834E+09 | 0.276747E+10 | 0.819018E+09 | 0.231217E+09 | 0.587801E+09 | 0.00 | 0.00 |
December | 0.251191E+09 | 0.351065E+10 | 0.694171E+09 | 0.223474E+09 | 0.470697E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.254563E+11 | 0.256332E+11 | 0.269655E+11 | 0.111457E+11 | 0.158198E+11 | 0.00 | 0.00 |
Minimum of Months | 0.185523E+09 | 0.114653E+10 | 0.694171E+09 | 0.183384E+09 | 0.470697E+09 | 0.00 | 0.00 |
Maximum of Months | 0.424145E+10 | 0.351065E+10 | 0.378838E+10 | 0.179241E+10 | 0.214003E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.237995E+10 | 0.478472E+10 | 0.298317E+10 | 0.177142E+10 | 0.121175E+10 | 0.00 | 0.00 |
February | 0.388167E+10 | 0.393827E+10 | 0.414369E+10 | 0.256500E+10 | 0.157869E+10 | 0.00 | 0.00 |
March | 0.492714E+10 | 0.380286E+10 | 0.493500E+10 | 0.263178E+10 | 0.230322E+10 | 0.00 | 0.00 |
April | 0.538642E+10 | 0.304765E+10 | 0.504235E+10 | 0.218935E+10 | 0.285300E+10 | 0.00 | 0.00 |
May | 0.514999E+10 | 0.261856E+10 | 0.476428E+10 | 0.141932E+10 | 0.334496E+10 | 0.00 | 0.00 |
June | 0.465244E+10 | 0.203087E+10 | 0.421824E+10 | 0.113254E+10 | 0.308570E+10 | 0.00 | 0.00 |
July | 0.586052E+10 | 0.194099E+10 | 0.475352E+10 | 0.174098E+10 | 0.301253E+10 | 0.00 | 0.00 |
August | 0.656548E+10 | 0.190962E+10 | 0.510705E+10 | 0.238149E+10 | 0.272556E+10 | 0.00 | 0.00 |
September | 0.650800E+10 | 0.257257E+10 | 0.547586E+10 | 0.302394E+10 | 0.245192E+10 | 0.00 | 0.00 |
October | 0.546470E+10 | 0.351515E+10 | 0.512554E+10 | 0.316464E+10 | 0.196090E+10 | 0.00 | 0.00 |
November | 0.253670E+10 | 0.404017E+10 | 0.293263E+10 | 0.168064E+10 | 0.125199E+10 | 0.00 | 0.00 |
December | 0.284117E+10 | 0.504040E+10 | 0.317065E+10 | 0.205185E+10 | 0.111880E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.561542E+11 | 0.392418E+11 | 0.526520E+11 | 0.257530E+11 | 0.268990E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237995E+10 | 0.190962E+10 | 0.293263E+10 | 0.113254E+10 | 0.111880E+10 | 0.00 | 0.00 |
Maximum of Months | 0.656548E+10 | 0.504040E+10 | 0.547586E+10 | 0.316464E+10 | 0.334496E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258067E+09 | 0.342115E+10 | 0.762920E+09 | 0.224971E+09 | 0.537949E+09 | 0.00 | 0.00 |
February | 0.763867E+09 | 0.273151E+10 | 0.123548E+10 | 0.464329E+09 | 0.771153E+09 | 0.00 | 0.00 |
March | 0.145872E+10 | 0.248771E+10 | 0.191671E+10 | 0.646943E+09 | 0.126977E+10 | 0.00 | 0.00 |
April | 0.268363E+10 | 0.196448E+10 | 0.282201E+10 | 0.107896E+10 | 0.174305E+10 | 0.00 | 0.00 |
May | 0.394035E+10 | 0.173486E+10 | 0.375231E+10 | 0.152436E+10 | 0.222795E+10 | 0.00 | 0.00 |
June | 0.375353E+10 | 0.134294E+10 | 0.349228E+10 | 0.135594E+10 | 0.213635E+10 | 0.00 | 0.00 |
July | 0.532283E+10 | 0.131726E+10 | 0.445805E+10 | 0.234338E+10 | 0.211467E+10 | 0.00 | 0.00 |
August | 0.450111E+10 | 0.127074E+10 | 0.368787E+10 | 0.188314E+10 | 0.180474E+10 | 0.00 | 0.00 |
September | 0.319491E+10 | 0.168676E+10 | 0.290633E+10 | 0.139452E+10 | 0.151181E+10 | 0.00 | 0.00 |
October | 0.143478E+10 | 0.230539E+10 | 0.170974E+10 | 0.696637E+09 | 0.101310E+10 | 0.00 | 0.00 |
November | 0.373779E+09 | 0.277599E+10 | 0.823973E+09 | 0.232395E+09 | 0.591578E+09 | 0.00 | 0.00 |
December | 0.328133E+09 | 0.354006E+10 | 0.715799E+09 | 0.245286E+09 | 0.470513E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.280137E+11 | 0.265789E+11 | 0.282835E+11 | 0.120909E+11 | 0.161926E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258067E+09 | 0.127074E+10 | 0.715799E+09 | 0.224971E+09 | 0.470513E+09 | 0.00 | 0.00 |
Maximum of Months | 0.532283E+10 | 0.354006E+10 | 0.445805E+10 | 0.234338E+10 | 0.222795E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 3827537.30 | 0.546707E+10 | 0.675195E+09 | 0.00 | 0.675195E+09 | 0.00 | 0.00 |
February | 0.105796E+09 | 0.444155E+10 | 0.948948E+09 | 0.00 | 0.948948E+09 | 0.00 | 0.00 |
March | 0.409652E+09 | 0.399434E+10 | 0.154793E+10 | 0.00 | 0.154793E+10 | 0.00 | 0.00 |
April | 0.107842E+10 | 0.305913E+10 | 0.211981E+10 | 7519582.16 | 0.211229E+10 | 0.00 | 0.00 |
May | 0.189739E+10 | 0.255864E+10 | 0.281859E+10 | 83735716.19 | 0.273485E+10 | 0.00 | 0.00 |
June | 0.216886E+10 | 0.192675E+10 | 0.286807E+10 | 0.189395E+09 | 0.267868E+10 | 0.00 | 0.00 |
July | 0.253784E+10 | 0.179509E+10 | 0.281681E+10 | 0.220850E+09 | 0.259596E+10 | 0.00 | 0.00 |
August | 0.212424E+10 | 0.176630E+10 | 0.228023E+10 | 61641115.79 | 0.221859E+10 | 0.00 | 0.00 |
September | 0.107479E+10 | 0.250549E+10 | 0.171407E+10 | 505449.15 | 0.171356E+10 | 0.00 | 0.00 |
October | 0.361436E+09 | 0.350108E+10 | 0.121357E+10 | 0.00 | 0.121357E+10 | 0.00 | 0.00 |
November | 48414290.65 | 0.431068E+10 | 0.739768E+09 | 0.00 | 0.739768E+09 | 0.00 | 0.00 |
December | 1770411.31 | 0.552395E+10 | 0.573741E+09 | 0.00 | 0.573741E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118124E+11 | 0.408501E+11 | 0.203167E+11 | 0.563647E+09 | 0.197531E+11 | 0.00 | 0.00 |
Minimum of Months | 1770411.31 | 0.176630E+10 | 0.573741E+09 | 0.00 | 0.573741E+09 | 0.00 | 0.00 |
Maximum of Months | 0.253784E+10 | 0.552395E+10 | 0.286807E+10 | 0.220850E+09 | 0.273485E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175618E+09 | 0.345534E+10 | 0.723289E+09 | 0.183377E+09 | 0.539912E+09 | 0.00 | 0.00 |
February | 0.621712E+09 | 0.276126E+10 | 0.119873E+10 | 0.425452E+09 | 0.773277E+09 | 0.00 | 0.00 |
March | 0.137889E+10 | 0.251449E+10 | 0.198155E+10 | 0.717334E+09 | 0.126422E+10 | 0.00 | 0.00 |
April | 0.269225E+10 | 0.191330E+10 | 0.297265E+10 | 0.123517E+10 | 0.173748E+10 | 0.00 | 0.00 |
May | 0.315205E+10 | 0.166970E+10 | 0.326861E+10 | 0.113641E+10 | 0.213220E+10 | 0.00 | 0.00 |
June | 0.399814E+10 | 0.128484E+10 | 0.378825E+10 | 0.164829E+10 | 0.213997E+10 | 0.00 | 0.00 |
July | 0.408325E+10 | 0.117143E+10 | 0.364534E+10 | 0.163623E+10 | 0.200911E+10 | 0.00 | 0.00 |
August | 0.418902E+10 | 0.113407E+10 | 0.358285E+10 | 0.179234E+10 | 0.179051E+10 | 0.00 | 0.00 |
September | 0.258160E+10 | 0.156607E+10 | 0.256354E+10 | 0.118232E+10 | 0.138122E+10 | 0.00 | 0.00 |
October | 0.135404E+10 | 0.221169E+10 | 0.172661E+10 | 0.733643E+09 | 0.992967E+09 | 0.00 | 0.00 |
November | 0.331137E+09 | 0.275759E+10 | 0.818989E+09 | 0.231208E+09 | 0.587782E+09 | 0.00 | 0.00 |
December | 0.242944E+09 | 0.352335E+10 | 0.694147E+09 | 0.223465E+09 | 0.470682E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.248007E+11 | 0.259631E+11 | 0.269646E+11 | 0.111452E+11 | 0.158193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.175618E+09 | 0.113407E+10 | 0.694147E+09 | 0.183377E+09 | 0.470682E+09 | 0.00 | 0.00 |
Maximum of Months | 0.418902E+10 | 0.352335E+10 | 0.378825E+10 | 0.179234E+10 | 0.213997E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.231017E+10 | 0.487853E+10 | 0.298316E+10 | 0.177141E+10 | 0.121175E+10 | 0.00 | 0.00 |
February | 0.377116E+10 | 0.398663E+10 | 0.414367E+10 | 0.256498E+10 | 0.157869E+10 | 0.00 | 0.00 |
March | 0.477202E+10 | 0.388466E+10 | 0.493498E+10 | 0.263176E+10 | 0.230322E+10 | 0.00 | 0.00 |
April | 0.520681E+10 | 0.315988E+10 | 0.504233E+10 | 0.218934E+10 | 0.285299E+10 | 0.00 | 0.00 |
May | 0.496273E+10 | 0.273311E+10 | 0.476426E+10 | 0.141931E+10 | 0.334495E+10 | 0.00 | 0.00 |
June | 0.449022E+10 | 0.212030E+10 | 0.421823E+10 | 0.113253E+10 | 0.308570E+10 | 0.00 | 0.00 |
July | 0.574796E+10 | 0.197894E+10 | 0.475350E+10 | 0.174097E+10 | 0.301253E+10 | 0.00 | 0.00 |
August | 0.647815E+10 | 0.190105E+10 | 0.510703E+10 | 0.238148E+10 | 0.272555E+10 | 0.00 | 0.00 |
September | 0.644163E+10 | 0.250626E+10 | 0.547584E+10 | 0.302393E+10 | 0.245191E+10 | 0.00 | 0.00 |
October | 0.539420E+10 | 0.340734E+10 | 0.512551E+10 | 0.316462E+10 | 0.196090E+10 | 0.00 | 0.00 |
November | 0.248874E+10 | 0.398782E+10 | 0.293262E+10 | 0.168063E+10 | 0.125199E+10 | 0.00 | 0.00 |
December | 0.278767E+10 | 0.505897E+10 | 0.317064E+10 | 0.205184E+10 | 0.111880E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.548514E+11 | 0.396035E+11 | 0.526517E+11 | 0.257528E+11 | 0.268989E+11 | 0.00 | 0.00 |
Minimum of Months | 0.231017E+10 | 0.190105E+10 | 0.293262E+10 | 0.113253E+10 | 0.111880E+10 | 0.00 | 0.00 |
Maximum of Months | 0.647815E+10 | 0.505897E+10 | 0.547584E+10 | 0.316462E+10 | 0.334495E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246560E+09 | 0.347939E+10 | 0.762895E+09 | 0.224963E+09 | 0.537932E+09 | 0.00 | 0.00 |
February | 0.731914E+09 | 0.279402E+10 | 0.123544E+10 | 0.464312E+09 | 0.771130E+09 | 0.00 | 0.00 |
March | 0.139124E+10 | 0.257251E+10 | 0.191665E+10 | 0.646918E+09 | 0.126974E+10 | 0.00 | 0.00 |
April | 0.258497E+10 | 0.204463E+10 | 0.282192E+10 | 0.107892E+10 | 0.174300E+10 | 0.00 | 0.00 |
May | 0.384120E+10 | 0.178051E+10 | 0.375219E+10 | 0.152430E+10 | 0.222789E+10 | 0.00 | 0.00 |
June | 0.367268E+10 | 0.137417E+10 | 0.349218E+10 | 0.135589E+10 | 0.213629E+10 | 0.00 | 0.00 |
July | 0.526734E+10 | 0.130898E+10 | 0.445791E+10 | 0.234329E+10 | 0.211461E+10 | 0.00 | 0.00 |
August | 0.445614E+10 | 0.125964E+10 | 0.368776E+10 | 0.188306E+10 | 0.180469E+10 | 0.00 | 0.00 |
September | 0.316523E+10 | 0.166188E+10 | 0.290624E+10 | 0.139447E+10 | 0.151177E+10 | 0.00 | 0.00 |
October | 0.141144E+10 | 0.228234E+10 | 0.170968E+10 | 0.696610E+09 | 0.101307E+10 | 0.00 | 0.00 |
November | 0.365713E+09 | 0.274916E+10 | 0.823946E+09 | 0.232386E+09 | 0.591560E+09 | 0.00 | 0.00 |
December | 0.319347E+09 | 0.354140E+10 | 0.715776E+09 | 0.245277E+09 | 0.470499E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.274538E+11 | 0.268486E+11 | 0.282826E+11 | 0.120904E+11 | 0.161922E+11 | 0.00 | 0.00 |
Minimum of Months | 0.246560E+09 | 0.125964E+10 | 0.715776E+09 | 0.224963E+09 | 0.470499E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526734E+10 | 0.354140E+10 | 0.445791E+10 | 0.234329E+10 | 0.222789E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.483074E+10 | -0.458408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -246655947.1 | 60.05 | 0.00 | 0.00 |
February | 0.441240E+10 | -0.419457E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -217832976.4 | 60.05 | 0.00 | 0.00 |
March | 0.514811E+10 | -0.491064E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -237465150.2 | 60.05 | 0.00 | 0.00 |
April | 0.452724E+10 | -0.429981E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -227430763.6 | 60.05 | 0.00 | 0.00 |
May | 0.467774E+10 | -0.444432E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233418914.7 | 60.05 | 0.00 | 0.00 |
June | 0.447746E+10 | -0.425257E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224889697.3 | 60.05 | 0.00 | 0.00 |
July | 0.412879E+10 | -0.389744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231356236.2 | 60.05 | 0.00 | 0.00 |
August | 0.450673E+10 | -0.427461E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232115902.9 | 60.05 | 0.00 | 0.00 |
September | 0.412374E+10 | -0.389919E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224548544.0 | 60.05 | 0.00 | 0.00 |
October | 0.438694E+10 | -0.415238E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234562126.3 | 60.05 | 0.00 | 0.00 |
November | 0.447395E+10 | -0.424363E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -230316246.0 | 60.05 | 0.00 | 0.00 |
December | 0.459238E+10 | -0.435083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241550088.3 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.542862E+11 | -0.515041E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.278214E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.412374E+10 | -0.491064E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -246655947.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.514811E+10 | -0.389744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -217832976.4 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.567321E+09 | 7025.43 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.229779E+09 | 5148.86 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1058253.83 | 945.84 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17934.98 | 4.13 | 27-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26765.30 | 4.02 | 05-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 608.57 | 1.01 | 21-JUN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 476620.53 | 5.80 | 24-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1081292.01 | 6.16 | 10-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 271283.34 | 5.66 | 14-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20487225.51 | 2671.28 | 13-NOV-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201703E+09 | 6821.90 | 26-DEC-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.567321E+09 | 7025.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.436086E+09 | 13367.84 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.436086E+09 | 13367.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.644224E+10 | 10217.20 | 03-JAN-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418208E+10 | 10193.21 | 24-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327865E+10 | 10193.25 | 10-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184533E+10 | 10187.68 | 04-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109096E+10 | 10207.34 | 17-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.570760E+09 | 10221.53 | 06-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.225404E+09 | 7112.16 | 10-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189029E+09 | 7552.77 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.510969E+09 | 10193.01 | 20-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149727E+10 | 10213.04 | 05-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.377693E+10 | 10191.37 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527530E+10 | 10186.99 | 29-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.189029E+09 | 7112.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.644224E+10 | 10221.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292549E+10 | 6748.88 | 17-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175140E+10 | 6738.13 | 10-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.983055E+09 | 6736.17 | 14-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288926E+09 | 6716.28 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59451848.89 | 5349.83 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1473870.76 | 1865.17 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14695177.69 | 4333.48 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300930E+09 | 6717.66 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112990E+10 | 6735.88 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218310E+10 | 6737.92 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.963842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292549E+10 | 6748.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.367252E+10 | 8455.14 | 04-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226102E+10 | 8439.73 | 07-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125439E+10 | 8437.29 | 27-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.449394E+09 | 8402.72 | 07-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29481258.90 | 6876.18 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3617054.69 | 2971.74 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.240736E+09 | 8399.49 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110943E+10 | 8422.09 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256223E+10 | 8439.54 | 05-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.367252E+10 | 8455.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.318512E+10 | 7155.64 | 17-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201257E+10 | 7141.41 | 11-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131514E+10 | 7136.11 | 13-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.549865E+09 | 7123.98 | 07-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92028849.15 | 5445.63 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7532290.01 | 2200.57 | 07-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17123379.08 | 4337.54 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.433314E+09 | 7121.47 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138189E+10 | 7140.84 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243721E+10 | 7142.48 | 02-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318512E+10 | 7155.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247350E+10 | 10095.44 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163376E+10 | 9416.83 | 18-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164511E+09 | 6164.43 | 01-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34101002.05 | 3694.58 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32534.02 | 4.13 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 418554.14 | 4.99 | 31-JUL-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 914460.27 | 5.74 | 09-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 238851.43 | 5.34 | 12-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 399690.75 | 229.01 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.448267E+09 | 7449.69 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151654E+10 | 10303.97 | 26-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.627268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247350E+10 | 10303.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137696E+10 | 19713.17 | 04-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319167E+09 | 19728.56 | 22-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35769641.83 | 19723.55 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128343E+09 | 19740.28 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.484689E+09 | 19724.66 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137696E+10 | 19740.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.345590E+10 | 11100.61 | 03-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195797E+10 | 11091.27 | 17-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102020E+10 | 11066.31 | 06-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.414893E+09 | 11036.79 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89148069.75 | 8404.28 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7236974.76 | 3954.72 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40674384.11 | 7740.74 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.526793E+09 | 11020.28 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176207E+10 | 11072.57 | 27-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.283659E+10 | 11102.07 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.345590E+10 | 11102.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.261574E+10 | 7632.88 | 03-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154999E+10 | 7626.71 | 17-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.848424E+09 | 7616.98 | 27-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.267683E+09 | 7582.29 | 12-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64624123.20 | 5497.32 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4688472.75 | 3468.35 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34697.58 | 142.05 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44519596.74 | 5232.05 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.489544E+09 | 7584.41 | 30-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137752E+10 | 7621.30 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218415E+10 | 7630.52 | 18-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.944692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.261574E+10 | 7632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.315784E+10 | 8737.50 | 05-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175409E+10 | 8737.46 | 15-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.736095E+09 | 8714.00 | 13-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217689E+09 | 8651.10 | 19-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11725454.76 | 6782.19 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6048243.03 | 4428.69 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304293E+09 | 8654.58 | 30-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128640E+10 | 8738.43 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.248561E+10 | 8738.73 | 18-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.995979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.315784E+10 | 8738.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.308890E+10 | 7724.61 | 03-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191823E+10 | 7718.56 | 17-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112744E+10 | 7700.78 | 06-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.452688E+09 | 7678.69 | 22-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98160543.11 | 5633.58 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10511541.94 | 3370.61 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 118511.19 | 284.35 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54244846.33 | 5235.02 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.638164E+09 | 7675.52 | 30-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171430E+10 | 7712.88 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262418E+10 | 7722.29 | 18-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.308890E+10 | 7724.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.289952E+10 | 9070.42 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195341E+10 | 9060.40 | 08-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.429825E+09 | 8737.68 | 01-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114515E+09 | 6867.21 | 19-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5139318.15 | 1734.90 | 18-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1383.64 | 2.31 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 492965.70 | 6.04 | 31-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 942298.09 | 6.20 | 29-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 209737.88 | 5.61 | 14-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21184878.51 | 2297.41 | 16-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.609324E+09 | 8011.41 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195450E+10 | 8985.69 | 26-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.798905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1383.64 | 2.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.289952E+10 | 9070.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.514611E+10 | 28363.23 | 03-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267016E+10 | 28363.35 | 22-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.907067E+09 | 28350.10 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220537E+09 | 28354.64 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1980036.03 | 5642.68 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1716770.27 | 3494.82 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355773E+09 | 28057.89 | 16-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202110E+10 | 28349.62 | 27-NOV-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409172E+10 | 28335.76 | 26-DEC-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.514611E+10 | 28363.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.539891E+10 | 13111.85 | 18-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.345812E+10 | 13109.69 | 22-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223974E+10 | 13104.00 | 13-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110798E+10 | 13067.89 | 17-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.449513E+09 | 13009.45 | 18-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123810E+09 | 8616.16 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16944265.82 | 4056.82 | 18-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44079437.16 | 6239.96 | 03-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.315710E+09 | 9656.81 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142179E+10 | 13107.48 | 23-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326650E+10 | 13111.13 | 24-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.473836E+10 | 13102.50 | 20-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16944265.82 | 4056.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.539891E+10 | 13111.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413772E+10 | 8501.60 | 21-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265804E+10 | 8506.49 | 06-FEB-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157478E+10 | 8487.54 | 13-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605033E+09 | 8464.20 | 17-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225026E+09 | 8426.35 | 18-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43049894.89 | 5529.30 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2203220.74 | 1103.25 | 13-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10352270.90 | 4082.48 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.203690E+09 | 6188.64 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108199E+10 | 8489.88 | 23-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242241E+10 | 8496.06 | 24-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363660E+10 | 8507.00 | 11-DEC-06:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2203220.74 | 1103.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413772E+10 | 8507.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.566998E+10 | 11343.54 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376861E+10 | 11267.34 | 14-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225368E+10 | 11273.64 | 06-MAR-06:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.963279E+09 | 11239.00 | 19-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239671E+09 | 11156.92 | 18-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30182346.62 | 7930.23 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9314531.38 | 3141.49 | 03-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197425E+09 | 9557.62 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136946E+10 | 11244.58 | 16-OCT-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310645E+10 | 11272.22 | 13-NOV-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.494041E+10 | 11272.15 | 27-DEC-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.566998E+10 | 11343.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.449180E+10 | 9028.05 | 04-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304423E+10 | 9029.40 | 27-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209255E+10 | 9028.40 | 13-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102028E+10 | 9003.73 | 17-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.386053E+09 | 8962.98 | 18-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108783E+09 | 5669.09 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20105310.78 | 3704.35 | 18-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44784455.92 | 4826.12 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317131E+09 | 6389.97 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143348E+10 | 9032.08 | 23-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282366E+10 | 9029.87 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398651E+10 | 9026.81 | 20-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20105310.78 | 3704.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.449180E+10 | 9032.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.304679E+09 | 0.277368E+09 | 16904.13 | 27-FEB-15:05 | 16904.13 | 0.00 |
March | 0.00 | 0.00 | 0.541788E+09 | 0.470803E+09 | 15052.38 | 18-MAR-16:00 | 15052.38 | 0.00 |
April | 0.00 | 0.00 | 0.425860E+10 | 0.404770E+10 | 55804.38 | 27-APR-16:00 | 54871.55 | 0.00 |
May | 0.00 | 0.00 | 0.944000E+10 | 0.827113E+10 | 51685.72 | 15-MAY-16:00 | 51685.72 | 0.00 |
June | 0.00 | 0.00 | 0.176669E+11 | 0.162064E+11 | 58673.10 | 28-JUN-15:50 | 58673.10 | 0.00 |
July | 0.00 | 0.00 | 0.330661E+11 | 0.287625E+11 | 74122.08 | 31-JUL-16:00 | 67341.45 | 0.00 |
August | 0.00 | 0.00 | 0.447670E+11 | 0.385819E+11 | 79682.89 | 10-AUG-15:30 | 74798.65 | 0.00 |
September | 0.00 | 0.00 | 0.173690E+11 | 0.140501E+11 | 68694.37 | 14-SEP-14:05 | 60180.69 | 0.00 |
October | 0.00 | 0.00 | 0.230704E+10 | 0.214849E+10 | 38748.61 | 04-OCT-15:00 | 38748.61 | 0.00 |
November | 0.00 | 0.00 | 0.509743E+09 | 0.350847E+09 | 25057.97 | 04-NOV-14:00 | 18847.75 | 0.00 |
December | 0.00 | 0.00 | 30404.83 | 27752.92 | 456.07 | 19-DEC-08:09 | 416.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130231E+12 | 0.113167E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.447670E+11 | 0.385819E+11 | 79682.89 | 74798.65 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 494542.11 | 461781.32 | 1452.24 | 30-JAN-07:13 | 1294.64 | 0.00 |
February | 0.00 | 0.00 | 0.290266E+09 | 0.265042E+09 | 16578.08 | 27-FEB-15:05 | 16578.08 | 0.00 |
March | 0.00 | 0.00 | 0.494761E+09 | 0.434195E+09 | 15336.21 | 18-MAR-14:05 | 15336.21 | 0.00 |
April | 0.00 | 0.00 | 0.419030E+10 | 0.399187E+10 | 55048.19 | 27-APR-14:05 | 55048.19 | 0.00 |
May | 0.00 | 0.00 | 0.910081E+10 | 0.796482E+10 | 49925.87 | 04-MAY-14:05 | 49925.87 | 0.00 |
June | 0.00 | 0.00 | 0.164835E+11 | 0.150917E+11 | 56349.55 | 28-JUN-15:40 | 56349.55 | 0.00 |
July | 0.00 | 0.00 | 0.303865E+11 | 0.264247E+11 | 70879.70 | 31-JUL-14:05 | 63757.91 | 0.00 |
August | 0.00 | 0.00 | 0.401225E+11 | 0.345398E+11 | 75710.78 | 10-AUG-14:05 | 69035.87 | 0.00 |
September | 0.00 | 0.00 | 0.156551E+11 | 0.126104E+11 | 65634.11 | 14-SEP-14:05 | 57573.92 | 0.00 |
October | 0.00 | 0.00 | 0.202249E+10 | 0.186810E+10 | 35105.91 | 04-OCT-15:00 | 35105.91 | 0.00 |
November | 0.00 | 0.00 | 0.502037E+09 | 0.350552E+09 | 25511.88 | 04-NOV-14:02 | 19730.07 | 0.00 |
December | 0.00 | 0.00 | 75233.73 | 69823.21 | 626.95 | 05-DEC-07:04 | 581.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119249E+12 | 0.103542E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 75233.73 | 69823.21 | 626.95 | 581.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.401225E+11 | 0.345398E+11 | 75710.78 | 69035.87 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1378417.43 | 1270637.89 | 1144.41 | 08-JAN-10:37 | 1137.79 | 0.00 |
February | 0.00 | 0.00 | 0.323266E+09 | 0.288992E+09 | 17558.50 | 27-FEB-15:00 | 17514.61 | 0.00 |
March | 0.00 | 0.00 | 0.547466E+09 | 0.475043E+09 | 16245.61 | 18-MAR-14:00 | 16245.61 | 0.00 |
April | 0.00 | 0.00 | 0.480912E+10 | 0.455951E+10 | 68669.43 | 27-APR-14:40 | 68669.43 | 0.00 |
May | 0.00 | 0.00 | 0.101730E+11 | 0.883548E+10 | 65291.19 | 04-MAY-14:50 | 65291.19 | 0.00 |
June | 0.00 | 0.00 | 0.184640E+11 | 0.167454E+11 | 70986.53 | 28-JUN-15:20 | 70986.53 | 0.00 |
July | 0.00 | 0.00 | 0.342620E+11 | 0.296813E+11 | 85761.51 | 31-JUL-14:40 | 78593.78 | 0.00 |
August | 0.00 | 0.00 | 0.445529E+11 | 0.383593E+11 | 90801.59 | 10-AUG-14:50 | 85101.83 | 0.00 |
September | 0.00 | 0.00 | 0.164305E+11 | 0.130325E+11 | 73145.10 | 14-SEP-14:00 | 64898.53 | 0.00 |
October | 0.00 | 0.00 | 0.195917E+10 | 0.177951E+10 | 34606.16 | 04-OCT-15:00 | 34606.16 | 0.00 |
November | 0.00 | 0.00 | 0.559982E+09 | 0.383438E+09 | 27958.10 | 04-NOV-13:40 | 20579.01 | 0.00 |
December | 0.00 | 0.00 | 854396.45 | 717155.09 | 685.13 | 11-DEC-06:13 | 634.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132084E+12 | 0.114142E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 854396.45 | 717155.09 | 685.13 | 634.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.445529E+11 | 0.383593E+11 | 90801.59 | 85101.83 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 22655.49 | 332425.65 | 02-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15225.78 | 288550.74 | 27-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7506.99 | 302977.88 | 27-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3273.12 | 248180.48 | 17-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1056.66 | 165876.87 | 18-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 343.86 | 90094.08 | 14-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 96.28 | 13547.27 | 10-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 111.42 | 37367.77 | 18-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 658.62 | 145778.85 | 28-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3749.14 | 257729.87 | 16-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10868.31 | 273019.61 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 17836.02 | 267866.41 | 04-DEC-06:11 |
Annual Sum or Average | 0.00 | 6915.10 | ||||
Minimum of Months | 0.00 | 0.00 | 96.28 | 13547.27 | ||
Maximum of Months | 0.00 | 0.00 | 22655.49 | 332425.65 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1702.15 | 6226.66 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1724.48 | 6234.19 | 10-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1823.75 | 6212.90 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1649.61 | 6074.31 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1649.95 | 5884.96 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1631.24 | 5653.24 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1446.19 | 5455.79 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1586.59 | 5376.20 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1495.25 | 5493.64 | 29-SEP-11:18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1541.18 | 5706.32 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1627.90 | 5930.81 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1615.25 | 6114.39 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 1623.90 | ||||
Minimum of Months | 0.00 | 0.00 | 1446.19 | 5376.20 | ||
Maximum of Months | 0.00 | 0.00 | 1823.75 | 6234.19 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.345108E+10 | 0.48 | 5302.00 | 02-JAN-06:11 | 1.24 |
February | 0.307111E+10 | 0.47 | 3690.03 | 01-FEB-06:11 | 1.06 |
March | 0.394897E+10 | 0.52 | 3876.21 | 02-MAR-16:50 | 1.09 |
April | 0.402382E+10 | 0.51 | 6934.00 | 27-APR-14:50 | 1.38 |
May | 0.495684E+10 | 0.56 | 7022.22 | 15-MAY-15:20 | 1.39 |
June | 0.560849E+10 | 0.60 | 8003.11 | 12-JUN-06:03 | 1.46 |
July | 0.628605E+10 | 0.61 | 9286.72 | 24-JUL-15:00 | 1.56 |
August | 0.724380E+10 | 0.67 | 10480.98 | 10-AUG-15:50 | 1.64 |
September | 0.547190E+10 | 0.58 | 8952.30 | 14-SEP-15:20 | 1.54 |
October | 0.427614E+10 | 0.51 | 7405.16 | 04-OCT-15:40 | 1.43 |
November | 0.345754E+10 | 0.47 | 3754.87 | 06-NOV-17:00 | 1.07 |
December | 0.330318E+10 | 0.46 | 3690.03 | 01-DEC-06:11 | 1.07 |
Annual Sum or Average | 0.550989E+11 | 0.54 | |||
Minimum of Months | 0.307111E+10 | 0.46 | 3690.03 | 1.06 | |
Maximum of Months | 0.724380E+10 | 0.67 | 10480.98 | 1.64 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321752E+10 | 0.48 | 5315.87 | 02-JAN-06:11 | 1.27 |
February | 0.278273E+10 | 0.46 | 5315.87 | 06-FEB-07:02 | 1.27 |
March | 0.334082E+10 | 0.50 | 5315.87 | 06-MAR-07:03 | 1.27 |
April | 0.341998E+10 | 0.49 | 7505.95 | 27-APR-14:05 | 1.46 |
May | 0.417279E+10 | 0.54 | 7010.86 | 15-MAY-14:05 | 1.43 |
June | 0.478351E+10 | 0.59 | 7673.17 | 28-JUN-15:30 | 1.48 |
July | 0.544843E+10 | 0.59 | 8809.32 | 31-JUL-14:05 | 1.56 |
August | 0.615536E+10 | 0.64 | 9727.03 | 10-AUG-15:30 | 1.63 |
September | 0.446334E+10 | 0.55 | 8457.26 | 14-SEP-14:05 | 1.54 |
October | 0.341069E+10 | 0.48 | 6603.15 | 04-OCT-14:05 | 1.39 |
November | 0.291057E+10 | 0.45 | 5315.87 | 13-NOV-07:01 | 1.27 |
December | 0.298048E+10 | 0.45 | 5315.87 | 04-DEC-07:02 | 1.27 |
Annual Sum or Average | 0.470862E+11 | 0.52 | |||
Minimum of Months | 0.278273E+10 | 0.45 | 5315.87 | 1.27 | |
Maximum of Months | 0.615536E+10 | 0.64 | 9727.03 | 1.63 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.403854E+10 | 0.53 | 5556.94 | 09-JAN-06:12 | 1.20 |
February | 0.338557E+10 | 0.50 | 5556.94 | 07-FEB-06:11 | 1.20 |
March | 0.360828E+10 | 0.48 | 5556.94 | 01-MAR-07:01 | 1.20 |
April | 0.355792E+10 | 0.46 | 7731.97 | 27-APR-14:30 | 1.37 |
May | 0.420995E+10 | 0.51 | 7531.69 | 15-MAY-15:10 | 1.36 |
June | 0.472183E+10 | 0.54 | 8270.48 | 28-JUN-15:20 | 1.41 |
July | 0.537670E+10 | 0.54 | 9329.79 | 31-JUL-15:00 | 1.48 |
August | 0.591428E+10 | 0.58 | 10294.93 | 10-AUG-15:20 | 1.55 |
September | 0.424574E+10 | 0.50 | 7994.87 | 14-SEP-14:50 | 1.39 |
October | 0.347235E+10 | 0.45 | 5776.37 | 04-OCT-14:50 | 1.22 |
November | 0.320057E+10 | 0.44 | 5556.94 | 01-NOV-06:03 | 1.20 |
December | 0.354865E+10 | 0.47 | 5556.94 | 09-DEC-06:02 | 1.20 |
Annual Sum or Average | 0.492804E+11 | 0.50 | |||
Minimum of Months | 0.320057E+10 | 0.44 | 5556.94 | 1.20 | |
Maximum of Months | 0.591428E+10 | 0.58 | 10294.93 | 1.55 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.433065E+09 | 0.389759E+09 | 891.86 | 17-JAN-07:01 | 802.67 | 802.67 | 47.06 | 2.85 |
February | 0.264959E+09 | 0.238463E+09 | 858.86 | 18-FEB-07:03 | 772.97 | 772.97 | 42.39 | 2.72 |
March | 0.145971E+09 | 0.131374E+09 | 851.22 | 06-MAR-07:03 | 766.10 | 766.10 | 43.19 | 2.68 |
April | 64387161.18 | 57948445.07 | 807.67 | 19-APR-06:02 | 726.90 | 726.90 | 37.37 | 2.42 |
May | 25541389.00 | 22987250.10 | 758.50 | 18-MAY-06:03 | 682.65 | 682.65 | 39.25 | 1.91 |
June | 9696009.05 | 8726408.15 | 546.71 | 14-JUN-06:03 | 492.04 | 492.04 | 33.90 | 0.83 |
July | 2238155.05 | 2014339.55 | 117.60 | 10-JUL-06:07 | 105.84 | 105.84 | 34.43 | 0.13 |
August | 2744651.45 | 2470186.30 | 290.88 | 18-AUG-06:03 | 261.79 | 261.79 | 34.32 | 0.35 |
September | 14206655.15 | 12785989.63 | 698.87 | 28-SEP-06:03 | 628.98 | 628.98 | 35.05 | 1.40 |
October | 73785413.57 | 66406872.21 | 807.56 | 16-OCT-06:03 | 726.80 | 726.80 | 39.79 | 2.41 |
November | 0.201555E+09 | 0.181400E+09 | 856.99 | 24-NOV-07:01 | 771.29 | 771.29 | 43.77 | 2.71 |
December | 0.339856E+09 | 0.305870E+09 | 876.70 | 26-DEC-07:01 | 789.03 | 789.03 | 47.06 | 2.79 |
Annual Sum or Average | 0.157801E+10 | 0.142021E+10 | ||||||
Minimum of Months | 2238155.05 | 2014339.55 | 117.60 | 105.84 | 105.84 | 33.90 | 0.13 | |
Maximum of Months | 0.433065E+09 | 0.389759E+09 | 891.86 | 802.67 | 802.67 | 47.06 | 2.85 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 58.14 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 56.83 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 57.20 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.91 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.23 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.28 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.38 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:02 | 2.06 | 2.06 | 57.47 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.41 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.20 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.18 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.07 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.83 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.20 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 28.61 | 60.00 | 22655.49 | 332425.65 | 02-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 30.92 | 30.92 | 15225.78 | 288550.74 | 27-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.30 | 25.30 | 7506.99 | 302977.88 | 27-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.78 | 26.78 | 3273.12 | 248180.48 | 17-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 27.14 | 27.14 | 1056.66 | 165876.87 | 18-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 44.08 | 44.08 | 343.86 | 90094.08 | 14-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 35.43 | 35.43 | 96.28 | 13547.27 | 10-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.16 | 28.16 | 111.42 | 37367.77 | 18-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.92 | 28.92 | 658.62 | 145778.85 | 28-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.13 | 21.13 | 3749.14 | 257729.87 | 16-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28.26 | 28.26 | 10868.31 | 273019.61 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 31.24 | 31.24 | 17836.02 | 267866.41 | 04-DEC-06:11 |
Annual Sum or Average | 0.00 | 6915.10 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.13 | 21.13 | 96.28 | 13547.27 | ||
Maximum of Months | 0.00 | 0.00 | 44.08 | 60.00 | 22655.49 | 332425.65 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.14 | 58.14 | 1702.15 | 6226.66 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.62 | 57.62 | 1724.48 | 6234.19 | 10-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.62 | 57.62 | 1823.75 | 6212.90 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.67 | 57.67 | 1649.61 | 6074.31 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.21 | 58.21 | 1649.95 | 5884.96 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.84 | 57.84 | 1631.24 | 5653.24 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.91 | 57.91 | 1446.19 | 5455.79 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.95 | 57.95 | 1586.59 | 5376.20 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 1495.25 | 5493.64 | 29-SEP-11:18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.04 | 57.04 | 1541.18 | 5706.32 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.82 | 57.82 | 1627.90 | 5930.81 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.73 | 57.73 | 1615.25 | 6114.39 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 1623.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.04 | 57.04 | 1446.19 | 5376.20 | ||
Maximum of Months | 0.00 | 0.00 | 58.21 | 58.21 | 1823.75 | 6234.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.172288E+11 | 0.00 | 0.00 | 0.345108E+10 | 0.00 | 0.00 |
February | 0.104369E+11 | 0.00 | 0.00 | 0.315087E+10 | 0.00 | 0.00 |
March | 0.683230E+10 | 0.00 | 0.00 | 0.409470E+10 | 0.00 | 0.00 |
April | 0.313353E+10 | 0.00 | 0.00 | 0.506562E+10 | 0.00 | 0.00 |
May | 0.127195E+10 | 0.00 | 0.00 | 0.724085E+10 | 0.00 | 0.00 |
June | 0.579767E+09 | 0.00 | 0.00 | 0.987869E+10 | 0.00 | 0.00 |
July | 0.225881E+09 | 0.00 | 0.00 | 0.141189E+11 | 0.00 | 0.00 |
August | 0.190110E+09 | 0.00 | 0.00 | 0.179061E+11 | 0.00 | 0.00 |
September | 0.546676E+09 | 0.00 | 0.00 | 0.959508E+10 | 0.00 | 0.00 |
October | 0.247225E+10 | 0.00 | 0.00 | 0.486063E+10 | 0.00 | 0.00 |
November | 0.741864E+10 | 0.00 | 0.00 | 0.358278E+10 | 0.00 | 0.00 |
December | 0.126595E+11 | 0.00 | 0.00 | 0.330319E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.629963E+11 | 0.00 | 0.00 | 0.862485E+11 | 0.00 | 0.00 |
Minimum of Months | 0.190110E+09 | 0.00 | 0.00 | 0.315087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.172288E+11 | 0.00 | 0.00 | 0.179061E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.161688E+11 | 0.00 | 0.00 | 0.321766E+10 | 0.00 | 0.00 |
February | 0.913321E+10 | 0.00 | 0.00 | 0.285876E+10 | 0.00 | 0.00 |
March | 0.393245E+10 | 0.00 | 0.00 | 0.347347E+10 | 0.00 | 0.00 |
April | 0.138705E+10 | 0.00 | 0.00 | 0.444523E+10 | 0.00 | 0.00 |
May | 0.263691E+09 | 0.00 | 0.00 | 0.637803E+10 | 0.00 | 0.00 |
June | 22436989.44 | 0.00 | 0.00 | 0.877789E+10 | 0.00 | 0.00 |
July | 418554.14 | 0.00 | 0.00 | 0.126670E+11 | 0.00 | 0.00 |
August | 1067669.04 | 0.00 | 0.00 | 0.157515E+11 | 0.00 | 0.00 |
September | 0.145726E+09 | 0.00 | 0.00 | 0.819307E+10 | 0.00 | 0.00 |
October | 0.195919E+10 | 0.00 | 0.00 | 0.392548E+10 | 0.00 | 0.00 |
November | 0.671690E+10 | 0.00 | 0.00 | 0.303311E+10 | 0.00 | 0.00 |
December | 0.121317E+11 | 0.00 | 0.00 | 0.298050E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.518627E+11 | 0.00 | 0.00 | 0.757017E+11 | 0.00 | 0.00 |
Minimum of Months | 418554.14 | 0.00 | 0.00 | 0.285876E+10 | 0.00 | 0.00 |
Maximum of Months | 0.161688E+11 | 0.00 | 0.00 | 0.157515E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.277440E+11 | 0.00 | 0.00 | 0.403894E+10 | 0.00 | 0.00 |
February | 0.175526E+11 | 0.00 | 0.00 | 0.347061E+10 | 0.00 | 0.00 |
March | 0.949764E+10 | 0.00 | 0.00 | 0.375565E+10 | 0.00 | 0.00 |
April | 0.403162E+10 | 0.00 | 0.00 | 0.473409E+10 | 0.00 | 0.00 |
May | 0.130738E+10 | 0.00 | 0.00 | 0.668116E+10 | 0.00 | 0.00 |
June | 0.305827E+09 | 0.00 | 0.00 | 0.921139E+10 | 0.00 | 0.00 |
July | 39745763.03 | 0.00 | 0.00 | 0.135467E+11 | 0.00 | 0.00 |
August | 0.109473E+09 | 0.00 | 0.00 | 0.166403E+11 | 0.00 | 0.00 |
September | 0.103588E+10 | 0.00 | 0.00 | 0.818912E+10 | 0.00 | 0.00 |
October | 0.568367E+10 | 0.00 | 0.00 | 0.397938E+10 | 0.00 | 0.00 |
November | 0.142494E+11 | 0.00 | 0.00 | 0.333821E+10 | 0.00 | 0.00 |
December | 0.233481E+11 | 0.00 | 0.00 | 0.354889E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.104905E+12 | 0.00 | 0.00 | 0.811344E+11 | 0.00 | 0.00 |
Minimum of Months | 39745763.03 | 0.00 | 0.00 | 0.333821E+10 | 0.00 | 0.00 |
Maximum of Months | 0.277440E+11 | 0.00 | 0.00 | 0.166403E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.345108E+10 | 0.00 | 0.172288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307111E+10 | 0.304679E+09 | 0.104369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394897E+10 | 0.541788E+09 | 0.683230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.402382E+10 | 0.425860E+10 | 0.313353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.495684E+10 | 0.944000E+10 | 0.127195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.560849E+10 | 0.176669E+11 | 0.579767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.628605E+10 | 0.330661E+11 | 0.225881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.724380E+10 | 0.447670E+11 | 0.190110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.547190E+10 | 0.173690E+11 | 0.546676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.427614E+10 | 0.230704E+10 | 0.247225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345754E+10 | 0.509743E+09 | 0.741864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330318E+10 | 30404.83 | 0.126595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550989E+11 | 0.130231E+12 | 0.629963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307111E+10 | 0.00 | 0.190110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.724380E+10 | 0.447670E+11 | 0.172288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.321752E+10 | 494542.11 | 0.161688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278273E+10 | 0.290266E+09 | 0.913321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334082E+10 | 0.494761E+09 | 0.393245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341998E+10 | 0.419030E+10 | 0.138705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.417279E+10 | 0.910081E+10 | 0.263691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.478351E+10 | 0.164835E+11 | 22436989.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.544843E+10 | 0.303865E+11 | 418554.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.615536E+10 | 0.401225E+11 | 1067669.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.446334E+10 | 0.156551E+11 | 0.145726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341069E+10 | 0.202249E+10 | 0.195919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.291057E+10 | 0.502037E+09 | 0.671690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298048E+10 | 75233.73 | 0.121317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.470862E+11 | 0.119249E+12 | 0.518627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278273E+10 | 75233.73 | 418554.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.615536E+10 | 0.401225E+11 | 0.161688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.403854E+10 | 1378417.43 | 0.277440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338557E+10 | 0.323266E+09 | 0.175526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360828E+10 | 0.547466E+09 | 0.949764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.355792E+10 | 0.480912E+10 | 0.403162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420995E+10 | 0.101730E+11 | 0.130738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472183E+10 | 0.184640E+11 | 0.305827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.537670E+10 | 0.342620E+11 | 39745763.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.591428E+10 | 0.445529E+11 | 0.109473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.424574E+10 | 0.164305E+11 | 0.103588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347235E+10 | 0.195917E+10 | 0.568367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320057E+10 | 0.559982E+09 | 0.142494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354865E+10 | 854396.45 | 0.233481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.492804E+11 | 0.132084E+12 | 0.104905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.320057E+10 | 854396.45 | 39745763.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.591428E+10 | 0.445529E+11 | 0.277440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.345108E+10 | 0.172288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307111E+10 | 0.104369E+11 | 0.00 | 0.00 | 79761204.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.394897E+10 | 0.683230E+10 | 0.00 | 0.00 | 0.145728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.402382E+10 | 0.313353E+10 | 0.00 | 0.00 | 0.104179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.495684E+10 | 0.127195E+10 | 0.00 | 0.00 | 0.228401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.560849E+10 | 0.579767E+09 | 0.00 | 0.00 | 0.427020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.628605E+10 | 0.225881E+09 | 0.00 | 0.00 | 0.783281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.724380E+10 | 0.190110E+09 | 0.00 | 0.00 | 0.106623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.547190E+10 | 0.546676E+09 | 0.00 | 0.00 | 0.412318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.427614E+10 | 0.247225E+10 | 0.00 | 0.00 | 0.584491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345754E+10 | 0.741864E+10 | 0.00 | 0.00 | 0.125241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330318E+10 | 0.126595E+11 | 0.00 | 0.00 | 8713.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550989E+11 | 0.629963E+11 | 0.00 | 0.00 | 0.311495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307111E+10 | 0.190110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.724380E+10 | 0.172288E+11 | 0.00 | 0.00 | 0.106623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.321752E+10 | 0.161688E+11 | 0.00 | 0.00 | 140740.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278273E+10 | 0.913321E+10 | 0.00 | 0.00 | 76025410.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334082E+10 | 0.393245E+10 | 0.00 | 0.00 | 0.132650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341998E+10 | 0.138705E+10 | 0.00 | 0.00 | 0.102525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.417279E+10 | 0.263691E+09 | 0.00 | 0.00 | 0.220524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.478351E+10 | 22436989.44 | 0.00 | 0.00 | 0.399438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.544843E+10 | 418554.14 | 0.00 | 0.00 | 0.721859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.615536E+10 | 1067669.04 | 0.00 | 0.00 | 0.959616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.446334E+10 | 0.145726E+09 | 0.00 | 0.00 | 0.372973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341069E+10 | 0.195919E+10 | 0.00 | 0.00 | 0.514796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.291057E+10 | 0.671690E+10 | 0.00 | 0.00 | 0.122544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298048E+10 | 0.121317E+11 | 0.00 | 0.00 | 21523.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.470862E+11 | 0.518627E+11 | 0.00 | 0.00 | 0.286155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278273E+10 | 418554.14 | 0.00 | 0.00 | 21523.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.615536E+10 | 0.161688E+11 | 0.00 | 0.00 | 0.959616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.403854E+10 | 0.277440E+11 | 0.00 | 0.00 | 394635.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338557E+10 | 0.175526E+11 | 0.00 | 0.00 | 85039283.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360828E+10 | 0.949764E+10 | 0.00 | 0.00 | 0.147366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.355792E+10 | 0.403162E+10 | 0.00 | 0.00 | 0.117617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.420995E+10 | 0.130738E+10 | 0.00 | 0.00 | 0.247120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472183E+10 | 0.305827E+09 | 0.00 | 0.00 | 0.448956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.537670E+10 | 39745763.03 | 0.00 | 0.00 | 0.817000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.591428E+10 | 0.109473E+09 | 0.00 | 0.00 | 0.107260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.424574E+10 | 0.103588E+10 | 0.00 | 0.00 | 0.394339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347235E+10 | 0.568367E+10 | 0.00 | 0.00 | 0.507030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320057E+10 | 0.142494E+11 | 0.00 | 0.00 | 0.137637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354865E+10 | 0.233481E+11 | 0.00 | 0.00 | 244901.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.492804E+11 | 0.104905E+12 | 0.00 | 0.00 | 0.318541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.320057E+10 | 39745763.03 | 0.00 | 0.00 | 244901.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.591428E+10 | 0.277440E+11 | 0.00 | 0.00 | 0.107260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.840066E+10 | 0.00 | 0.00 | 6216089.92 | 0.00 | 0.222687E+09 | 0.477576E+10 | 0.00 | 0.32 |
February | 0.553010E+10 | 0.00 | 0.00 | 14625829.43 | 0.00 | 0.00 | 0.811935E+10 | 0.00 | 0.41 |
March | 0.266953E+10 | 0.00 | 0.00 | 31979487.21 | 0.00 | 0.00 | 0.166861E+11 | 0.00 | 0.58 |
April | 0.133445E+10 | 12268842.10 | 0.00 | 35534541.88 | 4363864.42 | 0.00 | 0.176254E+11 | 0.00 | 0.69 |
May | 0.104984E+10 | 13397805.91 | 0.00 | 47457602.30 | 0.00 | 0.00 | 0.215310E+11 | 0.00 | 0.98 |
June | 0.675700E+09 | 1746136.37 | 0.00 | 51141597.04 | 3727350.15 | 0.00 | 0.209588E+11 | 0.00 | 1.18 |
July | 0.532712E+09 | 0.170838E+09 | 0.00 | 45594602.82 | 17087076.49 | 0.00 | 0.151097E+11 | 0.00 | 1.13 |
August | 0.526619E+09 | 0.480192E+09 | 0.00 | 44856313.79 | 5373186.18 | 0.00 | 0.129386E+11 | 0.00 | 1.08 |
September | 0.848241E+09 | 18405625.93 | 0.00 | 49929065.73 | 0.00 | 0.00 | 0.191235E+11 | 0.00 | 1.11 |
October | 0.139082E+10 | 0.00 | 0.00 | 40039756.02 | 0.00 | 0.00 | 0.199539E+11 | 0.00 | 0.78 |
November | 0.372202E+10 | 0.00 | 0.00 | 23462513.00 | 0.00 | 0.00 | 0.125135E+11 | 0.00 | 0.49 |
December | 0.679544E+10 | 0.00 | 0.00 | 12930051.15 | 0.00 | 0.00 | 0.753862E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.334761E+11 | 0.696849E+09 | 0.00 | 0.403767E+09 | 30551477.24 | 0.222687E+09 | 0.176874E+12 | 0.00 | 0.76 |
Minimum of Months | 0.526619E+09 | 0.00 | 0.00 | 6216089.92 | 0.00 | 0.00 | 0.477576E+10 | 0.00 | 0.32 |
Maximum of Months | 0.840066E+10 | 0.480192E+09 | 0.00 | 51141597.04 | 17087076.49 | 0.222687E+09 | 0.215310E+11 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451258E+09 | 0.00 | 0.00 | 0.26 |
February | 0.928101E+10 | 0.00 | 0.00 | 491166.69 | 0.00 | 60600927.83 | 0.692278E+09 | 0.00 | 0.31 |
March | 0.905002E+10 | 0.00 | 0.00 | 3789661.57 | 0.00 | 6637235.14 | 0.339909E+10 | 0.00 | 0.38 |
April | 0.590461E+10 | 6015632.83 | 0.00 | 10828722.74 | 11564996.19 | 0.00 | 0.624815E+10 | 0.00 | 0.45 |
May | 0.388053E+10 | 1520643.00 | 0.00 | 21764084.64 | 10686089.34 | 0.00 | 0.106618E+11 | 0.00 | 0.65 |
June | 0.225064E+10 | 964934.31 | 0.00 | 27321828.57 | 3327236.34 | 0.00 | 0.119869E+11 | 0.00 | 0.80 |
July | 0.128634E+10 | 0.131428E+09 | 0.00 | 25929724.45 | 19503985.06 | 0.00 | 0.881805E+10 | 0.00 | 0.76 |
August | 0.139603E+10 | 0.377321E+09 | 0.00 | 25225833.62 | 8052589.13 | 0.00 | 0.726362E+10 | 0.00 | 0.73 |
September | 0.308772E+10 | 2865214.98 | 0.00 | 22801429.16 | 13428889.11 | 0.00 | 0.899718E+10 | 0.00 | 0.71 |
October | 0.649886E+10 | 0.00 | 0.00 | 10946721.47 | 0.00 | 0.00 | 0.621478E+10 | 0.00 | 0.48 |
November | 0.877801E+10 | 0.00 | 0.00 | 1559807.68 | 323917.42 | 25650795.93 | 0.160033E+10 | 0.00 | 0.32 |
December | 0.100603E+11 | 0.00 | 0.00 | 70834.75 | 0.00 | 0.118172E+09 | 0.192197E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.715544E+11 | 0.520116E+09 | 0.00 | 0.150730E+09 | 66887702.59 | 0.662318E+09 | 0.660743E+11 | 0.00 | 0.51 |
Minimum of Months | 0.128634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.100804E+11 | 0.377321E+09 | 0.00 | 27321828.57 | 19503985.06 | 0.451258E+09 | 0.119869E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.791649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178596E+10 | 0.00 | 0.00 | 0.25 |
February | 0.858644E+10 | 0.00 | 0.00 | 23854.93 | 0.00 | 0.807623E+09 | 99641401.99 | 0.00 | 0.31 |
March | 0.107749E+11 | 0.00 | 0.00 | 654351.21 | 0.00 | 0.238673E+09 | 0.114183E+10 | 0.00 | 0.40 |
April | 0.790273E+10 | 57683.93 | 0.00 | 6537765.76 | 56740.14 | 60345351.57 | 0.419085E+10 | 0.00 | 0.46 |
May | 0.592921E+10 | 3063134.61 | 0.00 | 15926642.75 | 207916.26 | 0.00 | 0.888292E+10 | 0.00 | 0.65 |
June | 0.400659E+10 | 0.00 | 0.00 | 23272127.31 | 2364790.99 | 0.00 | 0.105373E+11 | 0.00 | 0.80 |
July | 0.253481E+10 | 80091544.27 | 0.00 | 23201213.22 | 4141995.14 | 0.00 | 0.795249E+10 | 0.00 | 0.78 |
August | 0.239017E+10 | 0.266305E+09 | 0.00 | 20404344.98 | 10227206.49 | 0.00 | 0.547844E+10 | 0.00 | 0.71 |
September | 0.549294E+10 | 0.00 | 0.00 | 13775997.66 | 3696127.02 | 0.00 | 0.561808E+10 | 0.00 | 0.69 |
October | 0.922821E+10 | 0.00 | 0.00 | 3322820.09 | 0.00 | 82346437.20 | 0.232375E+10 | 0.00 | 0.47 |
November | 0.914100E+10 | 0.00 | 0.00 | 6505.40 | 0.00 | 0.409087E+09 | 53039558.99 | 0.00 | 0.33 |
December | 0.814355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126057E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.820471E+11 | 0.349517E+09 | 0.00 | 0.107126E+09 | 20694776.03 | 0.464460E+10 | 0.462783E+11 | 0.00 | 0.51 |
Minimum of Months | 0.239017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.107749E+11 | 0.266305E+09 | 0.00 | 23272127.31 | 10227206.49 | 0.178596E+10 | 0.105373E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252251E+10 | 0.00 | 0.00 | 0.44 |
February | 0.171995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175595E+10 | 0.00 | 0.00 | 0.55 |
March | 0.355208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889566E+09 | 0.00 | 0.00 | 0.68 |
April | 0.360952E+10 | 16223.55 | 0.00 | 474085.93 | 20711.54 | 0.337610E+09 | 0.335218E+09 | 0.00 | 0.76 |
May | 0.341394E+10 | 1193856.47 | 0.00 | 2025444.61 | 0.00 | 59792165.37 | 0.141168E+10 | 0.00 | 1.02 |
June | 0.250379E+10 | 0.00 | 0.00 | 3952582.28 | 863206.46 | 5243133.90 | 0.199657E+10 | 0.00 | 1.18 |
July | 0.149307E+10 | 23828467.09 | 0.00 | 4866802.94 | 3139582.68 | 0.00 | 0.171656E+10 | 0.00 | 1.13 |
August | 0.145590E+10 | 78641104.43 | 0.00 | 3557744.93 | 6889568.68 | 1923951.57 | 0.989485E+09 | 0.00 | 1.04 |
September | 0.292374E+10 | 0.00 | 0.00 | 1615115.38 | 1349176.62 | 37024282.13 | 0.726615E+09 | 0.00 | 1.06 |
October | 0.356420E+10 | 0.00 | 0.00 | 57964.85 | 0.00 | 0.488605E+09 | 0.109498E+09 | 0.00 | 0.79 |
November | 0.204828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146568E+10 | 0.00 | 0.00 | 0.57 |
December | 0.113903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230489E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.284545E+11 | 0.103680E+09 | 0.00 | 16549740.91 | 12262245.98 | 0.986879E+10 | 0.728563E+10 | 0.00 | 0.81 |
Minimum of Months | 0.103097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.360952E+10 | 78641104.43 | 0.00 | 4866802.94 | 6889568.68 | 0.252251E+10 | 0.199657E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196124E+10 | 0.00 | 0.00 | 0.59 |
February | 0.164399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131981E+10 | 0.00 | 0.00 | 0.73 |
March | 0.315420E+10 | 0.00 | 0.00 | 33729.63 | 0.00 | 0.586763E+09 | 54150412.27 | 0.00 | 0.92 |
April | 0.247697E+10 | 13091.16 | 0.00 | 1387025.77 | 17703.07 | 0.189883E+09 | 0.107812E+10 | 0.00 | 1.06 |
May | 0.248665E+10 | 1020442.24 | 0.00 | 2989943.28 | 0.00 | 42365360.98 | 0.183245E+10 | 0.00 | 1.44 |
June | 0.167321E+10 | 0.00 | 0.00 | 5385242.84 | 737820.97 | 5212622.31 | 0.263362E+10 | 0.00 | 1.77 |
July | 0.114683E+10 | 17163399.78 | 0.00 | 5723219.26 | 4541917.64 | 0.00 | 0.188783E+10 | 0.00 | 1.69 |
August | 0.103565E+10 | 61944352.25 | 0.00 | 4931367.29 | 9197361.31 | 1672197.34 | 0.126604E+10 | 0.00 | 1.61 |
September | 0.209189E+10 | 846100.59 | 0.00 | 2889391.34 | 307100.70 | 29479319.43 | 0.124096E+10 | 0.00 | 1.54 |
October | 0.285643E+10 | 0.00 | 0.00 | 420455.48 | 0.00 | 0.340488E+09 | 0.380356E+09 | 0.00 | 1.08 |
November | 0.184695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115237E+10 | 0.00 | 0.00 | 0.77 |
December | 0.115206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178446E+10 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.226311E+11 | 80987386.02 | 0.00 | 23760374.90 | 14801903.70 | 0.741374E+10 | 0.103735E+11 | 0.00 | 1.15 |
Minimum of Months | 0.103565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.315420E+10 | 61944352.25 | 0.00 | 5723219.26 | 9197361.31 | 0.196124E+10 | 0.263362E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213785E+10 | 0.00 | 0.00 | 213968.97 | 0.00 | 0.252383E+10 | 0.105058E+09 | 0.00 | 0.59 |
February | 0.247718E+10 | 0.00 | 0.00 | 1539166.75 | 0.00 | 0.161725E+10 | 0.676988E+09 | 0.00 | 0.75 |
March | 0.374226E+10 | 0.00 | 0.00 | 3633642.27 | 0.00 | 0.801886E+09 | 0.185071E+10 | 0.00 | 0.99 |
April | 0.340910E+10 | 68859.72 | 0.00 | 4860965.66 | 0.00 | 0.373831E+09 | 0.245880E+10 | 0.00 | 1.13 |
May | 0.394085E+10 | 1771811.99 | 0.00 | 5598766.81 | 0.00 | 98105393.04 | 0.301281E+10 | 0.00 | 1.48 |
June | 0.331467E+10 | 0.00 | 0.00 | 6207558.09 | 1159383.46 | 15112406.32 | 0.298163E+10 | 0.00 | 1.66 |
July | 0.215168E+10 | 32985067.61 | 0.00 | 7607822.05 | 6738902.11 | 1423956.50 | 0.245743E+10 | 0.00 | 1.63 |
August | 0.195122E+10 | 0.129612E+09 | 0.00 | 6486425.51 | 11413238.92 | 5088657.45 | 0.153413E+10 | 0.00 | 1.52 |
September | 0.314999E+10 | 3699938.71 | 0.00 | 8312306.97 | 0.00 | 44527776.08 | 0.269906E+10 | 0.00 | 1.79 |
October | 0.360336E+10 | 0.00 | 0.00 | 4699105.94 | 0.00 | 0.481650E+09 | 0.230076E+10 | 0.00 | 1.24 |
November | 0.290518E+10 | 0.00 | 0.00 | 908196.36 | 0.00 | 0.156195E+10 | 0.280620E+09 | 0.00 | 0.78 |
December | 0.202688E+10 | 0.00 | 0.00 | 526239.46 | 0.00 | 0.229803E+10 | 0.303929E+09 | 0.00 | 0.59 |
Annual Sum or Average | 0.348102E+11 | 0.168137E+09 | 0.00 | 50594164.84 | 19311524.49 | 0.982268E+10 | 0.206619E+11 | 0.00 | 1.18 |
Minimum of Months | 0.195122E+10 | 0.00 | 0.00 | 213968.97 | 0.00 | 1423956.50 | 0.105058E+09 | 0.00 | 0.59 |
Maximum of Months | 0.394085E+10 | 0.129612E+09 | 0.00 | 8312306.97 | 11413238.92 | 0.252383E+10 | 0.301281E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233686E+10 | 0.00 | 0.00 | 0.67 |
February | 0.171919E+10 | 0.00 | 0.00 | 48428.10 | 0.00 | 0.160484E+10 | 33273037.32 | 0.00 | 0.83 |
March | 0.323612E+10 | 0.00 | 0.00 | 387849.13 | 0.00 | 0.799407E+09 | 0.296038E+09 | 0.00 | 1.05 |
April | 0.304847E+10 | 42851.69 | 0.00 | 1585829.83 | 0.00 | 0.322358E+09 | 0.903899E+09 | 0.00 | 1.21 |
May | 0.335303E+10 | 957723.12 | 0.00 | 3153258.92 | 198891.37 | 74395021.33 | 0.158251E+10 | 0.00 | 1.67 |
June | 0.279913E+10 | 0.00 | 0.00 | 3817115.55 | 836279.01 | 12299584.58 | 0.164437E+10 | 0.00 | 1.87 |
July | 0.163568E+10 | 35917257.33 | 0.00 | 4913311.88 | 259202.34 | 1027119.13 | 0.164354E+10 | 0.00 | 1.88 |
August | 0.158829E+10 | 92431302.78 | 0.00 | 3367261.81 | 6859266.29 | 4299935.41 | 0.836944E+09 | 0.00 | 1.64 |
September | 0.273959E+10 | 1252915.16 | 0.00 | 2822457.22 | 54174.33 | 41322363.55 | 0.999031E+09 | 0.00 | 1.75 |
October | 0.321498E+10 | 0.00 | 0.00 | 601488.92 | 0.00 | 0.461261E+09 | 0.412609E+09 | 0.00 | 1.24 |
November | 0.200097E+10 | 0.00 | 0.00 | 5554.96 | 0.00 | 0.139638E+10 | 926704.17 | 0.00 | 0.87 |
December | 0.119933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212640E+10 | 0.00 | 0.00 | 0.67 |
Annual Sum or Average | 0.276259E+11 | 0.130602E+09 | 0.00 | 20702556.30 | 8207813.34 | 0.918086E+10 | 0.835315E+10 | 0.00 | 1.28 |
Minimum of Months | 0.109107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1027119.13 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.335303E+10 | 92431302.78 | 0.00 | 4913311.88 | 6859266.29 | 0.233686E+10 | 0.164437E+10 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218111E+10 | 0.00 | 0.00 | 0.37 |
February | 0.168131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148932E+10 | 0.00 | 0.00 | 0.45 |
March | 0.327748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714269E+09 | 0.00 | 0.00 | 0.56 |
April | 0.329316E+10 | 1113847.68 | 0.00 | 45403.23 | 1811954.34 | 0.225547E+09 | 31688448.88 | 0.00 | 0.60 |
May | 0.320827E+10 | 248798.57 | 0.00 | 567044.08 | 2487698.34 | 8740750.00 | 0.476107E+09 | 0.00 | 0.75 |
June | 0.207921E+10 | 297784.48 | 0.00 | 2360042.79 | 918107.13 | 0.00 | 0.118983E+10 | 0.00 | 0.86 |
July | 0.113602E+10 | 28167150.09 | 0.00 | 3526120.26 | 6236041.01 | 0.00 | 0.121594E+10 | 0.00 | 0.83 |
August | 0.118575E+10 | 85831912.11 | 0.00 | 2866776.61 | 1613846.05 | 0.00 | 0.870418E+09 | 0.00 | 0.80 |
September | 0.248215E+10 | 518909.14 | 0.00 | 1371096.88 | 3158652.16 | 1069432.65 | 0.633016E+09 | 0.00 | 0.82 |
October | 0.364755E+10 | 0.00 | 0.00 | 64532.79 | 0.00 | 66810142.84 | 0.109815E+09 | 0.00 | 0.65 |
November | 0.273945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712318E+09 | 0.00 | 0.00 | 0.49 |
December | 0.154611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181959E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.273792E+11 | 0.116178E+09 | 0.00 | 10801016.63 | 16226299.03 | 0.721878E+10 | 0.452682E+10 | 0.00 | 0.63 |
Minimum of Months | 0.110277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.364755E+10 | 85831912.11 | 0.00 | 3526120.26 | 6236041.01 | 0.218111E+10 | 0.121594E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188702E+10 | 0.00 | 0.00 | 0.55 |
February | 0.174841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125275E+10 | 0.00 | 0.00 | 0.67 |
March | 0.329452E+10 | 0.00 | 0.00 | 328.10 | 0.00 | 0.485669E+09 | 6021748.32 | 0.00 | 0.84 |
April | 0.272570E+10 | 1407048.59 | 0.00 | 664663.71 | 1704147.06 | 0.131976E+09 | 0.551707E+09 | 0.00 | 0.92 |
May | 0.256884E+10 | 2282182.32 | 0.00 | 1669853.90 | 309474.29 | 9193243.36 | 0.102685E+10 | 0.00 | 1.18 |
June | 0.151665E+10 | 282512.85 | 0.00 | 4183231.15 | 871022.75 | 1015614.56 | 0.194062E+10 | 0.00 | 1.44 |
July | 0.100807E+10 | 29020123.32 | 0.00 | 4483470.56 | 6189717.84 | 0.00 | 0.146463E+10 | 0.00 | 1.38 |
August | 0.910489E+09 | 87117095.20 | 0.00 | 4266123.94 | 1341709.51 | 0.00 | 0.124718E+10 | 0.00 | 1.38 |
September | 0.202795E+10 | 2483402.96 | 0.00 | 2820089.63 | 1006447.21 | 1561375.24 | 0.115236E+10 | 0.00 | 1.34 |
October | 0.316759E+10 | 0.00 | 0.00 | 552322.16 | 0.00 | 70148105.11 | 0.424058E+09 | 0.00 | 0.98 |
November | 0.261308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661731E+09 | 0.00 | 0.00 | 0.73 |
December | 0.162155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156875E+10 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.244193E+11 | 0.122592E+09 | 0.00 | 18640083.15 | 11422518.66 | 0.606982E+10 | 0.781342E+10 | 0.00 | 1.00 |
Minimum of Months | 0.910489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.329452E+10 | 87117095.20 | 0.00 | 4483470.56 | 6189717.84 | 0.188702E+10 | 0.194062E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107720E+10 | 0.00 | 0.00 | 175.28 | 0.00 | 0.416338E+10 | 2193454.42 | 0.00 | 0.59 |
February | 0.223499E+10 | 0.00 | 0.00 | 196265.79 | 0.00 | 0.260911E+10 | 0.108967E+09 | 0.00 | 0.69 |
March | 0.376687E+10 | 0.00 | 0.00 | 647077.74 | 0.00 | 0.192071E+10 | 0.434021E+09 | 0.00 | 0.86 |
April | 0.370736E+10 | 6617571.40 | 0.00 | 1092853.13 | 0.00 | 0.112165E+10 | 0.538133E+09 | 0.00 | 0.91 |
May | 0.409409E+10 | 3781055.07 | 0.00 | 1608636.24 | 198684.86 | 0.682506E+09 | 0.739898E+09 | 0.00 | 1.13 |
June | 0.341491E+10 | 261332.45 | 0.00 | 2501326.16 | 1490140.10 | 0.420588E+09 | 0.919366E+09 | 0.00 | 1.25 |
July | 0.203635E+10 | 58099409.73 | 0.00 | 4238961.62 | 7282079.10 | 0.211406E+09 | 0.114028E+10 | 0.00 | 1.23 |
August | 0.191132E+10 | 0.190732E+09 | 0.00 | 4145582.32 | 2281340.14 | 0.125985E+09 | 0.936157E+09 | 0.00 | 1.22 |
September | 0.299040E+10 | 10688799.53 | 0.00 | 5825807.06 | 0.00 | 0.345207E+09 | 0.161667E+10 | 0.00 | 1.44 |
October | 0.387597E+10 | 0.00 | 0.00 | 2808905.91 | 0.00 | 0.813781E+09 | 0.140578E+10 | 0.00 | 1.07 |
November | 0.298831E+10 | 0.00 | 0.00 | 325950.31 | 0.00 | 0.237073E+10 | 56860522.21 | 0.00 | 0.76 |
December | 0.164269E+10 | 0.00 | 0.00 | 122982.93 | 0.00 | 0.360042E+10 | 0.107209E+09 | 0.00 | 0.61 |
Annual Sum or Average | 0.337405E+11 | 0.270180E+09 | 0.00 | 23514524.50 | 11252244.21 | 0.183855E+11 | 0.800554E+10 | 0.00 | 0.98 |
Minimum of Months | 0.107720E+10 | 0.00 | 0.00 | 175.28 | 0.00 | 0.125985E+09 | 2193454.42 | 0.00 | 0.59 |
Maximum of Months | 0.409409E+10 | 0.190732E+09 | 0.00 | 5825807.06 | 7282079.10 | 0.416338E+10 | 0.161667E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223605E+10 | 0.00 | 0.00 | 0.62 |
February | 0.194792E+10 | 0.00 | 0.00 | 6825.46 | 0.00 | 0.140693E+10 | 7224984.32 | 0.00 | 0.75 |
March | 0.356446E+10 | 0.00 | 0.00 | 107678.82 | 0.00 | 0.575204E+09 | 0.103804E+09 | 0.00 | 0.94 |
April | 0.326771E+10 | 1835050.86 | 0.00 | 630116.52 | 1711080.47 | 0.194311E+09 | 0.335180E+09 | 0.00 | 1.02 |
May | 0.327150E+10 | 1248114.21 | 0.00 | 1576991.42 | 1658843.81 | 10360159.08 | 0.740777E+09 | 0.00 | 1.33 |
June | 0.242499E+10 | 583872.55 | 0.00 | 2500319.43 | 976274.34 | 2392852.46 | 0.109769E+10 | 0.00 | 1.49 |
July | 0.125536E+10 | 49793373.22 | 0.00 | 3856764.71 | 1568061.67 | 0.00 | 0.133031E+10 | 0.00 | 1.50 |
August | 0.136337E+10 | 0.108854E+09 | 0.00 | 2715758.60 | 2497015.01 | 0.00 | 0.818813E+09 | 0.00 | 1.35 |
September | 0.257765E+10 | 2926007.49 | 0.00 | 2256278.93 | 1170145.33 | 2335190.74 | 0.840940E+09 | 0.00 | 1.46 |
October | 0.368258E+10 | 0.00 | 0.00 | 480063.83 | 0.00 | 88063699.17 | 0.335261E+09 | 0.00 | 1.11 |
November | 0.295585E+10 | 0.00 | 0.00 | 3709.07 | 0.00 | 0.713711E+09 | 775676.80 | 0.00 | 0.82 |
December | 0.174871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182558E+10 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.293005E+11 | 0.165241E+09 | 0.00 | 14134506.78 | 9581420.64 | 0.705494E+10 | 0.561078E+10 | 0.00 | 1.09 |
Minimum of Months | 0.124042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.368258E+10 | 0.108854E+09 | 0.00 | 3856764.71 | 2497015.01 | 0.223605E+10 | 0.133031E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193114E+10 | 0.00 | 0.00 | 0.38 |
February | 0.201002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113856E+10 | 0.00 | 0.00 | 0.46 |
March | 0.356258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314766E+09 | 0.00 | 0.00 | 0.56 |
April | 0.299001E+10 | 1726990.92 | 0.00 | 658527.83 | 3614856.08 | 82371252.60 | 0.491219E+09 | 0.00 | 0.62 |
May | 0.231997E+10 | 3813181.84 | 0.00 | 3032999.62 | 0.00 | 3549109.49 | 0.162510E+10 | 0.00 | 0.84 |
June | 0.149054E+10 | 322515.63 | 0.00 | 5198721.83 | 1039990.01 | 0.00 | 0.219871E+10 | 0.00 | 1.01 |
July | 0.918499E+09 | 42798147.92 | 0.00 | 5465184.40 | 5462809.98 | 0.00 | 0.174020E+10 | 0.00 | 0.99 |
August | 0.100087E+10 | 0.116362E+09 | 0.00 | 4440958.49 | 2296034.98 | 0.00 | 0.120240E+10 | 0.00 | 0.91 |
September | 0.215773E+10 | 737542.45 | 0.00 | 2553138.09 | 4197450.71 | 967623.93 | 0.102575E+10 | 0.00 | 0.88 |
October | 0.335466E+10 | 0.00 | 0.00 | 267356.90 | 0.00 | 99795486.51 | 0.238409E+09 | 0.00 | 0.65 |
November | 0.250889E+10 | 0.00 | 0.00 | 0.00 | 101246.46 | 0.748183E+09 | 0.00 | 0.00 | 0.48 |
December | 0.155856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169824E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.252488E+11 | 0.165760E+09 | 0.00 | 21616887.15 | 16712388.22 | 0.601757E+10 | 0.852179E+10 | 0.00 | 0.68 |
Minimum of Months | 0.918499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.356258E+10 | 0.116362E+09 | 0.00 | 5465184.40 | 5462809.98 | 0.193114E+10 | 0.219871E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181351E+10 | 0.00 | 0.00 | 0.54 |
February | 0.178737E+10 | 0.00 | 0.00 | 15851.24 | 0.00 | 0.103940E+10 | 3539608.91 | 0.00 | 0.65 |
March | 0.303777E+10 | 0.00 | 0.00 | 366241.99 | 0.00 | 0.300016E+09 | 0.209049E+09 | 0.00 | 0.81 |
April | 0.229479E+10 | 1412119.63 | 0.00 | 1905807.84 | 2655736.31 | 69182457.91 | 0.116886E+10 | 0.00 | 0.98 |
May | 0.223214E+10 | 3997666.44 | 0.00 | 3337418.78 | 20161.90 | 9461664.80 | 0.175410E+10 | 0.00 | 1.35 |
June | 0.153009E+10 | 294472.81 | 0.00 | 5552618.79 | 1164229.08 | 1113833.42 | 0.247414E+10 | 0.00 | 1.69 |
July | 0.111639E+10 | 33878186.87 | 0.00 | 5596300.05 | 8847087.74 | 0.00 | 0.170764E+10 | 0.00 | 1.60 |
August | 0.100639E+10 | 94270467.96 | 0.00 | 5006541.80 | 4702599.24 | 0.00 | 0.135445E+10 | 0.00 | 1.56 |
September | 0.197793E+10 | 3292421.86 | 0.00 | 3409237.45 | 215579.71 | 4499984.98 | 0.132576E+10 | 0.00 | 1.46 |
October | 0.274989E+10 | 0.00 | 0.00 | 908821.23 | 0.00 | 0.127421E+09 | 0.602955E+09 | 0.00 | 0.98 |
November | 0.215711E+10 | 0.00 | 0.00 | 13566.13 | 68291.74 | 0.788138E+09 | 2037436.50 | 0.00 | 0.68 |
December | 0.135096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159064E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.224179E+11 | 0.137145E+09 | 0.00 | 26112405.32 | 17673685.73 | 0.574338E+10 | 0.106025E+11 | 0.00 | 1.07 |
Minimum of Months | 0.100639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.303777E+10 | 94270467.96 | 0.00 | 5596300.05 | 8847087.74 | 0.181351E+10 | 0.247414E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.281967E+10 | 0.00 | 0.00 | 311289.55 | 0.00 | 0.227508E+10 | 0.156122E+09 | 0.00 | 0.61 |
February | 0.324303E+10 | 0.00 | 0.00 | 2197565.76 | 0.00 | 0.107496E+10 | 0.877585E+09 | 0.00 | 0.77 |
March | 0.421913E+10 | 0.00 | 0.00 | 4640768.61 | 0.00 | 0.407291E+09 | 0.209187E+10 | 0.00 | 0.99 |
April | 0.363873E+10 | 12150180.92 | 0.00 | 4945355.87 | 46212.96 | 0.138846E+09 | 0.238253E+10 | 0.00 | 1.11 |
May | 0.370481E+10 | 6833619.84 | 0.00 | 5860438.58 | 0.00 | 15099435.68 | 0.281282E+10 | 0.00 | 1.41 |
June | 0.296166E+10 | 419177.94 | 0.00 | 6552735.90 | 1648750.10 | 1577381.11 | 0.274333E+10 | 0.00 | 1.57 |
July | 0.201106E+10 | 68318096.36 | 0.00 | 7311958.12 | 10413476.04 | 0.00 | 0.210795E+10 | 0.00 | 1.55 |
August | 0.183471E+10 | 0.210294E+09 | 0.00 | 6117051.01 | 4841745.95 | 0.00 | 0.160047E+10 | 0.00 | 1.47 |
September | 0.320636E+10 | 16008575.85 | 0.00 | 8643580.02 | 0.00 | 3993339.02 | 0.260862E+10 | 0.00 | 1.76 |
October | 0.402481E+10 | 0.00 | 0.00 | 5728970.50 | 0.00 | 0.141025E+09 | 0.268021E+10 | 0.00 | 1.26 |
November | 0.397180E+10 | 342727.88 | 0.00 | 1269561.12 | 0.00 | 0.869719E+09 | 0.394837E+09 | 0.00 | 0.79 |
December | 0.282338E+10 | 0.00 | 0.00 | 1113036.60 | 0.00 | 0.189497E+10 | 0.507604E+09 | 0.00 | 0.62 |
Annual Sum or Average | 0.384591E+11 | 0.314366E+09 | 0.00 | 54692311.63 | 16950185.05 | 0.682255E+10 | 0.209640E+11 | 0.00 | 1.16 |
Minimum of Months | 0.183471E+10 | 0.00 | 0.00 | 311289.55 | 0.00 | 0.00 | 0.156122E+09 | 0.00 | 0.61 |
Maximum of Months | 0.421913E+10 | 0.210294E+09 | 0.00 | 8643580.02 | 10413476.04 | 0.227508E+10 | 0.281282E+10 | 0.00 | 1.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212382E+10 | 0.00 | 0.00 | 0.69 |
February | 0.241874E+10 | 0.00 | 0.00 | 74030.71 | 0.00 | 0.115915E+10 | 56379336.83 | 0.00 | 0.84 |
March | 0.379717E+10 | 0.00 | 0.00 | 455692.55 | 0.00 | 0.386141E+09 | 0.339566E+09 | 0.00 | 1.04 |
April | 0.328508E+10 | 3718311.50 | 0.00 | 1487868.62 | 2709413.53 | 0.124124E+09 | 0.817675E+09 | 0.00 | 1.17 |
May | 0.321497E+10 | 3108238.11 | 0.00 | 3128786.82 | 1280232.76 | 12382881.29 | 0.143304E+10 | 0.00 | 1.60 |
June | 0.250290E+10 | 647031.44 | 0.00 | 3761181.22 | 1202842.82 | 2375680.64 | 0.157382E+10 | 0.00 | 1.77 |
July | 0.147023E+10 | 67492024.93 | 0.00 | 4600186.93 | 1614839.64 | 0.00 | 0.148554E+10 | 0.00 | 1.78 |
August | 0.149756E+10 | 0.139779E+09 | 0.00 | 3258902.41 | 4382536.68 | 0.00 | 0.915664E+09 | 0.00 | 1.57 |
September | 0.285054E+10 | 5020982.88 | 0.00 | 2831497.86 | 999245.44 | 4649235.03 | 0.919568E+09 | 0.00 | 1.68 |
October | 0.372829E+10 | 0.00 | 0.00 | 747472.16 | 0.00 | 0.150894E+09 | 0.460468E+09 | 0.00 | 1.22 |
November | 0.290345E+10 | 0.00 | 0.00 | 10682.34 | 117100.71 | 0.861936E+09 | 239276.88 | 0.00 | 0.88 |
December | 0.195775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180116E+10 | 0.00 | 0.00 | 0.70 |
Annual Sum or Average | 0.313138E+11 | 0.219766E+09 | 0.00 | 20356301.62 | 12306211.58 | 0.662664E+10 | 0.800196E+10 | 0.00 | 1.25 |
Minimum of Months | 0.147023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
Maximum of Months | 0.379717E+10 | 0.139779E+09 | 0.00 | 4600186.93 | 4382536.68 | 0.212382E+10 | 0.157382E+10 | 0.00 | 1.78 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:07
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.757199E+11 | 0.147979E+11 | 0.00 | 0.164110E+12 | 0.320361E+11 |
February | 0.136382E+12 | 0.131748E+11 | 0.00 | 0.178811E+12 | 0.222791E+11 |
March | 0.230264E+12 | 0.127767E+11 | 0.00 | 0.229976E+12 | 0.149283E+11 |
April | 0.347404E+12 | 0.114133E+11 | 0.00 | 0.257494E+12 | 0.220818E+11 |
May | 0.448992E+12 | 0.922264E+10 | 0.00 | 0.284352E+12 | 0.376553E+11 |
June | 0.449941E+12 | 0.745552E+10 | 0.00 | 0.273370E+12 | 0.660306E+11 |
July | 0.475497E+12 | 0.562052E+10 | 0.00 | 0.268730E+12 | 0.121134E+12 |
August | 0.375646E+12 | 0.415558E+10 | 0.00 | 0.205977E+12 | 0.160654E+12 |
September | 0.270862E+12 | 0.483063E+10 | 0.00 | 0.274809E+12 | 0.624779E+11 |
October | 0.178566E+12 | 0.101049E+11 | 0.00 | 0.268604E+12 | 0.147027E+11 |
November | 0.810721E+11 | 0.120686E+11 | 0.00 | 0.213225E+12 | 0.190376E+11 |
December | 0.617361E+11 | 0.131440E+11 | 0.00 | 0.182201E+12 | 0.262377E+11 |
Annual Sum or Average | 0.313208E+13 | 0.118765E+12 | 0.00 | 0.280166E+13 | 0.599256E+12 |
Minimum of Months | 0.617361E+11 | 0.415558E+10 | 0.00 | 0.164110E+12 | 0.147027E+11 |
Maximum of Months | 0.475497E+12 | 0.147979E+11 | 0.00 | 0.284352E+12 | 0.160654E+12 |