Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2024-07-03 12:21:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2534.72 | 508.76 | 508.76 |
Net Site Energy | 2534.72 | 508.76 | 508.76 |
Total Source Energy | 8027.46 | 1611.23 | 1611.23 |
Net Source Energy | 8027.46 | 1611.23 | 1611.23 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 47.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 707.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 235.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 178.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 42.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2534.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 47.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 707.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 235.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 178.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 42.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 47.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 707.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 235.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 178.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 42.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 508.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 195.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 508.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2534.722 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2534.722 | 100.00 |
Total On-Site and Utility Electric Sources | 2534.722 | 100.00 |
Total Electricity End Uses | 2534.722 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 10.83 |
Time Setpoint Not Met During Occupied Cooling | 131.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1402.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| CORE_BOTTOM PIU FAN | PERIMETER_BOT_ZN_1 PIU FAN | PERIMETER_BOT_ZN_2 PIU FAN | PERIMETER_BOT_ZN_3 PIU FAN | PERIMETER_BOT_ZN_4 PIU FAN | CORE_MID PIU FAN | PERIMETER_MID_ZN_1 PIU FAN | PERIMETER_MID_ZN_2 PIU FAN | PERIMETER_MID_ZN_3 PIU FAN | PERIMETER_MID_ZN_4 PIU FAN | CORE_TOP PIU FAN | PERIMETER_TOP_ZN_1 PIU FAN | PERIMETER_TOP_ZN_2 PIU FAN | PERIMETER_TOP_ZN_3 PIU FAN | PERIMETER_TOP_ZN_4 PIU FAN | PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | - | 09-JAN-12:09 |
Heating | 169246.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5312.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16481.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22777.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1008.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18485.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1651.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 249983.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 169246.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5312.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 16481.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1008.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18485.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 1651.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 149.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2240.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 747.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 133.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8027.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 29.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 449.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 113.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1611.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 29.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 449.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 113.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1611.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
AirTerminal:SingleDuct:ParallelPIU:ReheatDesign Size Maximum Primary Air Flow Rate [m3/s] | Design Size Maximum Secondary Air Flow Rate [m3/s] | Design Size Minimum Primary Air Flow Fraction | User-Specified Minimum Primary Air Flow Fraction | |
CORE_BOTTOM VAV BOX COMPONENT | 3.28 | 3.28 | 0.129303 | 0.300000 |
CORE_MID VAV BOX COMPONENT | 2.67 | 2.67 | 0.158850 | 0.301000 |
CORE_TOP VAV BOX COMPONENT | 3.20 | 3.20 | 0.132778 | 0.300000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.991882 | 0.991882 | 0.090261 | 0.300000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.942819 | 0.942819 | 0.060117 | 0.300000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.20 | 1.20 | 0.074592 | 0.300000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.06 | 1.06 | 0.053240 | 0.300000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.808438 | 0.808438 | 0.110743 | 0.300000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.876364 | 0.876364 | 0.064675 | 0.300000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.02 | 1.02 | 0.087873 | 0.300000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.916091 | 0.916091 | 0.061866 | 0.300000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.814945 | 0.814945 | 0.109858 | 0.300000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.915829 | 0.915829 | 0.061888 | 0.300000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.03 | 1.03 | 0.086679 | 0.300000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.959053 | 0.959053 | 0.059095 | 0.300000 |
Design Size Maximum Flow Rate [m3/s] | |
CORE_BOTTOM PIU FAN | 3.28 |
CORE_MID PIU FAN | 2.67 |
CORE_TOP PIU FAN | 3.20 |
PERIMETER_TOP_ZN_3 PIU FAN | 0.991882 |
PERIMETER_TOP_ZN_2 PIU FAN | 0.942819 |
PERIMETER_TOP_ZN_1 PIU FAN | 1.20 |
PERIMETER_TOP_ZN_4 PIU FAN | 1.06 |
PERIMETER_BOT_ZN_3 PIU FAN | 0.808438 |
PERIMETER_BOT_ZN_2 PIU FAN | 0.876364 |
PERIMETER_BOT_ZN_1 PIU FAN | 1.02 |
PERIMETER_BOT_ZN_4 PIU FAN | 0.916091 |
PERIMETER_MID_ZN_3 PIU FAN | 0.814945 |
PERIMETER_MID_ZN_2 PIU FAN | 0.915829 |
PERIMETER_MID_ZN_1 PIU FAN | 1.03 |
PERIMETER_MID_ZN_4 PIU FAN | 0.959053 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 71822.08 |
CORE_MID VAV BOX REHEAT COIL | 58225.81 |
CORE_TOP VAV BOX REHEAT COIL | 69413.22 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21486.84 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20424.09 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 26000.40 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23060.51 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17512.31 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 18983.79 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 22070.06 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 19844.32 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17653.53 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 19838.97 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 22374.49 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 20775.27 |
PACU_VAV_BOT HEATING COIL | 741.27 |
PACU_VAV_MID HEATING COIL | 5118.50 |
PACU_VAV_TOP HEATING COIL | 2047.21 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.07 | 2.07 | 6.90 | 2.68 | 6.19 | 6.19 | 0.300000 | 0.433494 | 6.19 |
PACU_VAV_MID | 1.92 | 1.92 | 6.40 | 3.56 | 5.59 | 5.59 | 0.300000 | 0.636987 | 5.59 |
PACU_VAV_TOP | 2.22 | 2.22 | 7.40 | 5.20 | 6.98 | 6.98 | 0.300000 | 0.744622 | 6.98 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.19 |
PACU_VAV_MID_OA_CONTROLLER | 5.59 |
PACU_VAV_TOP_OA_CONTROLLER | 6.98 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.19 | 133626.53 | 0.747011 | 2.06 | 44537.72 | 0.747011 |
PACU_VAV_MID COOLING COIL | 5.59 | 124025.65 | 0.737483 | 1.86 | 41337.75 | 0.737483 |
PACU_VAV_TOP COOLING COIL | 6.98 | 146744.03 | 0.757494 | 2.33 | 48909.78 | 0.757494 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.19 |
PACU_VAV_MID FAN | 5.59 |
PACU_VAV_TOP FAN | 6.98 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
43 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
44 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
45 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
46 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
47 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
48 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
49 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_1.22_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
2 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
3 | WINDOW_U_1.22_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
4 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39294.66877 | 45188.86909 | 2.85606 | 3.28447 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 4024.54461 | 5030.68076 | 0.28833 | 0.42469 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32011.95201 | 36813.74481 | 2.32482 | 2.67354 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 11872.12342 | 14840.15427 | 0.84918 | 1.06148 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 37945.34111 | 43637.14228 | 2.78131 | 3.19851 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 22698.58628 | 28373.23285 | 1.64009 | 2.05011 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 11766.28065 | 13531.22275 | 0.86251 | 0.99188 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10547.94606 | 13184.93257 | 0.76644 | 0.95805 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11184.79511 | 12862.51438 | 0.81984 | 0.94282 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 31.09550 | 1.65311E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6904.46000 | 8630.57500 | 0.50177 | 0.62722 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14237.98823 | 16373.68646 | 1.04369 | 1.20024 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10394.35055 | 12992.93818 | 0.75523 | 0.94403 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12628.06271 | 14522.27211 | 0.92567 | 1.06452 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 32.89933 | 1.65345E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6805.74024 | 8507.17529 | 0.49456 | 0.61821 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 9590.50567 | 11029.08152 | 0.70299 | 0.80844 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7571.66141 | 9464.57676 | 0.54927 | 0.68659 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 10396.66112 | 11956.16029 | 0.76206 | 0.87636 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 30.89800 | 1.65307E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5022.22114 | 6277.77643 | 0.36443 | 0.45554 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12086.58959 | 13899.57803 | 0.88595 | 1.01884 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7408.36506 | 9260.45632 | 0.53734 | 0.67168 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10867.65455 | 12497.80273 | 0.79660 | 0.91609 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4914.11120 | 6142.63899 | 0.35654 | 0.44567 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9667.44481 | 11117.56153 | 0.70865 | 0.81494 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8381.53400 | 10476.91750 | 0.60831 | 0.76039 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10864.53422 | 12494.21436 | 0.79637 | 0.91583 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65303E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5533.34424 | 6916.68030 | 0.40170 | 0.50212 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12252.79299 | 14090.71194 | 0.89816 | 1.03288 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8223.82279 | 10279.77848 | 0.59679 | 0.74599 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11377.03126 | 13083.58595 | 0.83396 | 0.95905 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5434.49031 | 6793.11289 | 0.39448 | 0.49309 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 94508.59 | 6.19193 | 6.19193 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 9251.61 | 2.68417 | 2.68417 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 86384.36 | 5.59364 | 5.59364 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 9432.82 | 3.56308 | 3.56308 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 104999.70 | 6.98020 | 6.98020 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 8310.68 | 5.19762 | 5.19762 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 3.28447 |
2 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 3.28447 |
3 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.12930 |
4 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
5 | Fan:ConstantVolume | CORE_BOTTOM PIU FAN | Design Size Maximum Flow Rate [m3/s] | 3.28447 |
6 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 71822.07889 |
7 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 2.67354 |
8 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 2.67354 |
9 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.15885 |
10 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30100 |
11 | Fan:ConstantVolume | CORE_MID PIU FAN | Design Size Maximum Flow Rate [m3/s] | 2.67354 |
12 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 58225.80812 |
13 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 3.19851 |
14 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 3.19851 |
15 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.13278 |
16 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
17 | Fan:ConstantVolume | CORE_TOP PIU FAN | Design Size Maximum Flow Rate [m3/s] | 3.19851 |
18 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 69413.21727 |
19 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.99188 |
20 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.99188 |
21 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 9.02614E-002 |
22 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
23 | Fan:ConstantVolume | PERIMETER_TOP_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.99188 |
24 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21486.83804 |
25 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.94282 |
26 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.94282 |
27 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.01165E-002 |
28 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
29 | Fan:ConstantVolume | PERIMETER_TOP_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.94282 |
30 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20424.08953 |
31 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.20024 |
32 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.20024 |
33 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 7.45922E-002 |
34 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
35 | Fan:ConstantVolume | PERIMETER_TOP_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.20024 |
36 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26000.40202 |
37 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.06452 |
38 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.06452 |
39 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.32401E-002 |
40 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
41 | Fan:ConstantVolume | PERIMETER_TOP_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.06452 |
42 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23060.50670 |
43 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.80844 |
44 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.80844 |
45 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.11074 |
46 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
47 | Fan:ConstantVolume | PERIMETER_BOT_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.80844 |
48 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17512.30713 |
49 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.87636 |
50 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.87636 |
51 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.46752E-002 |
52 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
53 | Fan:ConstantVolume | PERIMETER_BOT_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.87636 |
54 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18983.79188 |
55 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.01884 |
56 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.01884 |
57 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 8.78727E-002 |
58 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
59 | Fan:ConstantVolume | PERIMETER_BOT_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.01884 |
60 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22070.06336 |
61 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.91609 |
62 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.91609 |
63 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.18665E-002 |
64 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
65 | Fan:ConstantVolume | PERIMETER_BOT_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.91609 |
66 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19844.32048 |
67 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.81494 |
68 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.81494 |
69 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.10986 |
70 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
71 | Fan:ConstantVolume | PERIMETER_MID_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.81494 |
72 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17653.52933 |
73 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.91583 |
74 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.91583 |
75 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.18882E-002 |
76 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
77 | Fan:ConstantVolume | PERIMETER_MID_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.91583 |
78 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19838.96933 |
79 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.03288 |
80 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.03288 |
81 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 8.66786E-002 |
82 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
83 | Fan:ConstantVolume | PERIMETER_MID_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.03288 |
84 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22374.48902 |
85 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.95905 |
86 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.95905 |
87 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.90951E-002 |
88 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
89 | Fan:ConstantVolume | PERIMETER_MID_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.95905 |
90 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20775.26855 |
91 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.07126 |
92 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.07126 |
93 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.90421 |
94 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.68417 |
95 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.19193 |
96 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.19193 |
97 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
98 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.43349 |
99 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.92155 |
100 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.92155 |
101 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.39625 |
102 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 3.56308 |
103 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.59364 |
104 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.59364 |
105 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
106 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.63699 |
107 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.21939 |
108 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.21939 |
109 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.39797 |
110 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 5.19762 |
111 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.98020 |
112 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.98020 |
113 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
114 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.74462 |
115 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.19193 |
116 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.59364 |
117 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.98020 |
118 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.19193 |
119 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.19193 |
120 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 133626.52993 |
121 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74701 |
122 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.06377 |
123 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 44537.72242 |
124 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74701 |
125 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 741.26922 |
126 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.19193 |
127 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.59364 |
128 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.59364 |
129 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 124025.64915 |
130 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73748 |
131 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.86436 |
132 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 41337.74886 |
133 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73748 |
134 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 5118.50118 |
135 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.59364 |
136 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.98020 |
137 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.98020 |
138 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 146744.02603 |
139 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75749 |
140 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.32650 |
141 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 48909.78387 |
142 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75749 |
143 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 2047.20576 |
144 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.98020 |
145 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
146 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
147 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
148 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
149 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 132781.30 | 453068.60 | 11.66 | 2.99 | 3.34 | 3.52 | 3.68 | 10.22 | 11.39 | 12.00 | 12.55 | 7.1557 | 5.6957 | 3.8337 | 1.5792 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 123359.78 | 420921.04 | 11.72 | 3.01 | 3.36 | 3.54 | 3.69 | 10.26 | 11.45 | 12.06 | 12.59 | 6.4643 | 5.1344 | 3.4618 | 1.4384 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 145676.29 | 497068.13 | 11.60 | 2.98 | 3.32 | 3.50 | 3.67 | 10.18 | 11.33 | 11.93 | 12.52 | 8.0667 | 6.4310 | 4.3284 | 1.7629 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1876628507 | 0.2999432923 | Pass | Pass | 0.1898199562 | 0.3897008366 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1366372274 | 0.1565707899 | Pass | Pass | 0.1630630513 | 0.3588133750 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.8518610057E-002 | 5.9673224315E-002 | Pass | Pass | 0.2009472297 | 0.4045548532 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.4510204179E-002 | 5.5097113518E-002 | Pass | Pass | 0.2080232795 | 0.3990899610 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1304242794 | 0.1928254507 | Pass | Pass | 0.1749666987 | 0.3786970909 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1410890398 | 0.2110453960 | Pass | Pass | 0.1607612590 | 0.3648524102 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1805399922 | 0.2791576343 | Pass | Pass | 0.1621047304 | 0.3638645245 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2991756973 | 0.4281050412 | Pass | Pass | 0.1654946234 | 0.3673718100 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3582373751 | 0.6106028783 | Pass | Pass | 0.1650886696 | 0.3634057049 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2838087933 | 0.4802526995 | Pass | Pass | 0.1626312913 | 0.3616741747 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1810783341 | 0.2934442085 | Pass | Pass | 0.1900338568 | 0.3880910679 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3278160897 | 0.5039636042 | Pass | Pass | 0.1943216776 | 0.3913334455 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3722268212 | 0.6296019680 | Pass | Pass | 0.2243721412 | 0.4488467406 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3090498799 | 0.5105572120 | Pass | Pass | 0.1912703949 | 0.3873806312 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1646239868 | 0.2446790534 | Pass | Pass | 0.1761836186 | 0.3773990280 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3111611299 | 0.4394612482 | Pass | Pass | 0.1813195247 | 0.3816020320 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3507710958 | 0.5803224890 | Pass | Pass | 0.1840481726 | 0.3869483432 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2777893072 | 0.4514056402 | Pass | Pass | 0.1773199590 | 0.3759799890 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4358.01 | -65.4 | 0.00 | -794.6 | 3618.16 | 7116.19 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_1.22_SHGC_EAST_0.25 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_1.22_SHGC_EAST_0.25 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_1.22_SHGC_WEST_0.25 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_1.22_SHGC_WEST_0.25 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
North Total or Average | 183.92 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
Non-North Total or Average | 429.15 | 6.926 | 0.251 | 0.277 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.73 | 83.73 | 235.95 | |
Exterior Lighting Total | 15013.15 | 235.95 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 133626.53 | 99820.43 | 33806.10 | 0.75 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 124025.65 | 91466.77 | 32558.88 | 0.74 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 146744.03 | 111157.73 | 35586.29 | 0.76 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 132781.3 | 2.99 | 10.22 | N/A | N/A | 11.66 | |
PACU_VAV_MID COOLING COIL | 123359.8 | 3.01 | 10.26 | N/A | N/A | 11.72 | |
PACU_VAV_TOP COOLING COIL | 145676.3 | 2.98 | 10.18 | N/A | N/A | 11.60 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 71822.08 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 58225.81 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 69413.22 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21486.84 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20424.09 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 26000.40 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23060.51 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17512.31 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18983.79 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22070.06 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19844.32 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17653.53 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19838.97 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22374.49 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20775.27 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 741.27 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 5118.50 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 2047.21 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CORE_BOTTOM PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 3.28 | 2434.63 | 741.25 | 1.00 | 1.23 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
CORE_MID PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 2.67 | 1981.77 | 741.25 | 1.00 | 1.25 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
CORE_TOP PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 3.20 | 2370.91 | 741.25 | 1.00 | 1.23 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PERIMETER_TOP_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.99 | 735.24 | 741.25 | 1.00 | 1.45 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PERIMETER_TOP_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.94 | 698.87 | 741.25 | 1.00 | 1.46 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 |
PERIMETER_TOP_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.20 | 889.68 | 741.25 | 1.00 | 1.40 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PERIMETER_TOP_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.06 | 789.08 | 741.25 | 1.00 | 1.43 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 |
PERIMETER_BOT_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.81 | 599.26 | 741.25 | 1.00 | 1.51 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
PERIMETER_BOT_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.88 | 649.61 | 741.25 | 1.00 | 1.48 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
PERIMETER_BOT_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.02 | 755.22 | 741.25 | 1.00 | 1.44 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PERIMETER_BOT_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.92 | 679.06 | 741.25 | 1.00 | 1.47 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PERIMETER_MID_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.81 | 604.08 | 741.25 | 1.00 | 1.51 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PERIMETER_MID_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.92 | 678.86 | 741.25 | 1.00 | 1.47 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 |
PERIMETER_MID_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.03 | 765.63 | 741.25 | 1.00 | 1.44 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PERIMETER_MID_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.96 | 710.90 | 741.25 | 1.00 | 1.46 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1337.13 | 6.19 | 13696.31 | 2211.96 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.59 | 12372.91 | 2211.96 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.98 | 15340.96 | 2197.78 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 132781.30 | 2.99 | 10.22 | 11.66 | 7.1557 | 3.34 | 11.39 | 5.6957 | 3.52 | 12.00 | 3.8337 | 3.68 | 12.55 | 1.5792 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 123359.78 | 3.01 | 10.26 | 11.72 | 6.4643 | 3.36 | 11.45 | 5.1344 | 3.54 | 12.06 | 3.4618 | 3.69 | 12.59 | 1.4384 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 145676.29 | 2.98 | 10.18 | 11.60 | 8.0667 | 3.32 | 11.33 | 6.4310 | 3.50 | 11.93 | 4.3284 | 3.67 | 12.52 | 1.7629 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39294.67 | 45188.87 | 45.95 | 2.856 | 3.284 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_MID | 32011.95 | 36813.74 | 37.43 | 2.325 | 2.674 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_TOP | 37945.34 | 43637.14 | 44.37 | 2.781 | 3.199 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00881 | 33.82 | 0.01654 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11766.28 | 13531.22 | 65.26 | 0.863 | 0.992 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00891 | 33.82 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11184.80 | 12862.51 | 97.99 | 0.820 | 0.943 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00878 | 31.10 | 0.01653 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14237.99 | 16373.69 | 78.97 | 1.044 | 1.200 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00884 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12628.06 | 14522.27 | 110.64 | 0.926 | 1.065 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 24.00 | 24.00 | 0.00875 | 32.90 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9590.51 | 11029.08 | 53.19 | 0.703 | 0.808 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00889 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 10396.66 | 11956.16 | 91.09 | 0.762 | 0.876 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 24.00 | 24.00 | 0.00873 | 30.90 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12086.59 | 13899.58 | 67.04 | 0.886 | 1.019 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00881 | 33.83 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10867.65 | 12497.80 | 95.22 | 0.797 | 0.916 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00872 | 32.79 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9667.44 | 11117.56 | 53.62 | 0.709 | 0.815 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00896 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10864.53 | 12494.21 | 95.19 | 0.796 | 0.916 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00877 | 30.67 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12252.79 | 14090.71 | 67.96 | 0.898 | 1.033 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00886 | 33.83 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11377.03 | 13083.59 | 99.68 | 0.834 | 0.959 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00875 | 32.79 | 0.01653 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 4024.54 | 5030.68 | 5.11 | 0.288 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_MID | 11872.12 | 14840.15 | 15.09 | 0.849 | 1.061 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_TOP | 22698.59 | 28373.23 | 28.85 | 1.640 | 2.050 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10547.95 | 13184.93 | 63.59 | 0.766 | 0.958 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6904.46 | 8630.58 | 65.75 | 0.502 | 0.627 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10394.35 | 12992.94 | 62.67 | 0.755 | 0.944 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6805.74 | 8507.18 | 64.81 | 0.495 | 0.618 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7571.66 | 9464.58 | 45.65 | 0.549 | 0.687 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5022.22 | 6277.78 | 47.83 | 0.364 | 0.456 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7408.37 | 9260.46 | 44.66 | 0.537 | 0.672 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4914.11 | 6142.64 | 46.80 | 0.357 | 0.446 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8381.53 | 10476.92 | 50.53 | 0.608 | 0.760 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5533.34 | 6916.68 | 52.69 | 0.402 | 0.502 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8223.82 | 10279.78 | 49.58 | 0.597 | 0.746 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5434.49 | 6793.11 | 51.76 | 0.394 | 0.493 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 4.60 | 0.00526 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.19 | 6.19 | 2.68 | 2.68 | 6.1919 | 2.6842 | 6.1919 | 0.4335 | 0.3000 |
PACU_VAV_MID | 5.59 | 5.59 | 3.56 | 3.56 | 5.5936 | 3.5631 | 5.5936 | 0.6370 | 0.3000 |
PACU_VAV_TOP | 6.98 | 6.98 | 5.20 | 5.20 | 6.9802 | 5.1976 | 6.9802 | 0.7446 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 71822.079 | 71822.079 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 71822.08 | 7143.68 | 0.424691 | 18.40 | 5.02 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 5030.68 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 58225.808 | 58225.808 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 58225.81 | 17768.94 | 1.061476 | 18.47 | 5.06 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 14840.15 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 69413.217 | 69413.217 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 69413.22 | 34223.77 | 2.050107 | 18.50 | 5.08 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 28373.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21486.838 | 21486.838 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21486.84 | 15964.66 | 0.958055 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00792785 | 51.2152 | 13184.93 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 20424.090 | 20424.090 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20424.09 | 10451.75 | 0.627217 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00792682 | 51.2086 | 8630.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 26000.402 | 26000.402 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26000.40 | 15730.97 | 0.944033 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00792665 | 51.2075 | 12992.94 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 23060.507 | 23060.507 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23060.51 | 10301.56 | 0.618205 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00792565 | 51.2012 | 8507.18 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17512.307 | 17512.307 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17512.31 | 11440.57 | 0.686585 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00792904 | 51.2228 | 9464.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 18983.792 | 18983.792 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18983.79 | 7590.68 | 0.455539 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00793164 | 51.2393 | 6277.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 22070.063 | 22070.063 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22070.06 | 11192.17 | 0.671679 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00792611 | 51.2041 | 9260.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 19844.320 | 19844.320 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19844.32 | 7426.23 | 0.445671 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00792891 | 51.2220 | 6142.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 17653.529 | 17653.529 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17653.53 | 12670.61 | 0.760392 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00791476 | 51.1318 | 10476.92 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 19838.969 | 19838.969 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19838.97 | 8366.98 | 0.502120 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00791694 | 51.1457 | 6916.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 22374.489 | 22374.489 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22374.49 | 12430.66 | 0.745993 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00791148 | 51.1110 | 10279.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 20775.269 | 20775.269 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20775.27 | 8216.58 | 0.493095 | 18.53 | 5.09 | -999.0 | 32.11 | 18.72 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00791412 | 51.1278 | 6793.11 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 133626.530 | 99820.434 | 6.191932 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 134430.12 | 105654.01 | 6.191932 | 25.53 | 18.17 | 0.01002098 | 11.09 | 11.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 15.4411 | 24.00 | 0.00882944 | 47.4694 | 73363.28 | 0.00 | 137786.89 | 101330.41 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 741.269 | 741.269 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 741.27 | 741.27 | 1.857580 | 12.56 | 9.96 | 0.00655063 | 12.89 | 11.62 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 51.4702 | 17.93 | 0.00787750 | 61.5890 | 6830.22 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 124025.649 | 91466.773 | 5.593641 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 125415.19 | 96305.39 | 5.593641 | 25.68 | 18.37 | 0.01020597 | 11.09 | 11.09 | 0.00850000 | 33.82 | 0.01653623 | 25.11 | 17.0926 | 24.00 | 0.00889877 | 47.8375 | 66268.23 | 0.00 | 127887.09 | 92887.45 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 5118.501 | 5118.501 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5118.50 | 5118.50 | 1.678092 | 10.37 | 8.62 | 0.00623223 | 12.89 | 11.62 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 56.9754 | 19.44 | 0.00733210 | 52.2042 | 10255.82 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 146744.026 | 111157.731 | 6.980205 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 147226.35 | 117550.23 | 6.980205 | 25.33 | 18.00 | 0.00989018 | 11.10 | 11.10 | 0.00850000 | 33.74 | 0.01653608 | 25.09 | 13.6973 | 24.00 | 0.00883516 | 47.5003 | 82790.36 | 0.00 | 151312.79 | 112813.31 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 2047.206 | 2047.206 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2047.21 | 2047.21 | 2.094061 | 12.08 | 9.81 | 0.00660947 | 12.89 | 11.62 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 45.6577 | 16.43 | 0.00787623 | 67.7245 | 6557.13 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 71822.079 | 71822.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 71822.08 | 7143.68 | 1.0000 | 0.51097426 | 0.424691 | 18.40 | 5.02 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71822.08 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.76 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 5030.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 58225.808 | 58225.808 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 58225.81 | 17768.94 | 1.0000 | 1.27713237 | 1.061476 | 18.47 | 5.06 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58225.81 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 14840.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 69413.217 | 69413.217 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 69413.22 | 34223.77 | 1.0000 | 2.46662114 | 2.050107 | 18.50 | 5.08 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69413.22 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 28373.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 21486.838 | 21486.838 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21486.84 | 15964.66 | 1.0000 | 1.15269998 | 0.958055 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21486.84 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00792785 | 21.00 | 0.00792785 | 51.2152 | 13184.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 20424.090 | 20424.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20424.09 | 10451.75 | 1.0000 | 0.75464696 | 0.627217 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20424.09 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00792682 | 21.00 | 0.00792682 | 51.2086 | 8630.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 26000.402 | 26000.402 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26000.40 | 15730.97 | 1.0000 | 1.13582919 | 0.944033 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26000.40 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00792665 | 21.00 | 0.00792665 | 51.2075 | 12992.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 23060.507 | 23060.507 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23060.51 | 10301.56 | 1.0000 | 0.74380382 | 0.618205 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23060.51 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00792565 | 21.00 | 0.00792565 | 51.2012 | 8507.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17512.307 | 17512.307 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17512.31 | 11440.57 | 1.0000 | 0.82607681 | 0.686585 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17512.31 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00792904 | 21.00 | 0.00792904 | 51.2228 | 9464.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 18983.792 | 18983.792 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18983.79 | 7590.68 | 1.0000 | 0.54808966 | 0.455539 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18983.79 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00793164 | 21.00 | 0.00793164 | 51.2393 | 6277.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 22070.063 | 22070.063 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22070.06 | 11192.17 | 1.0000 | 0.80814226 | 0.671679 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22070.06 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00792611 | 21.00 | 0.00792611 | 51.2041 | 9260.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 19844.320 | 19844.320 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19844.32 | 7426.23 | 1.0000 | 0.53621649 | 0.445671 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19844.32 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00792891 | 21.00 | 0.00792891 | 51.2220 | 6142.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17653.529 | 17653.529 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17653.53 | 12670.61 | 1.0000 | 0.91487870 | 0.760392 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17653.53 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791476 | 21.00 | 0.00791476 | 51.1318 | 10476.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 19838.969 | 19838.969 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19838.97 | 8366.98 | 1.0000 | 0.60413452 | 0.502120 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19838.97 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791694 | 21.00 | 0.00791694 | 51.1457 | 6916.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 22374.489 | 22374.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22374.49 | 12430.66 | 1.0000 | 0.89755376 | 0.745993 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22374.49 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791148 | 21.00 | 0.00791148 | 51.1110 | 10279.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 20775.269 | 20775.269 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20775.27 | 8216.58 | 1.0000 | 0.59327515 | 0.493095 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.72 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20775.27 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791412 | 21.00 | 0.00791412 | 51.1278 | 6793.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 133626.530 | 99820.434 | 6.191932 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4685 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.191932 | 7.44992750 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 134430.12 | 105654.01 | 1.0060 | 7.44992750 | 6.191932 | 25.53 | 18.17 | 0.01002098 | 51190.4 | 11.09 | 11.09 | 0.00850000 | 32579.6 | -999.0 | -999.00 | -999.00 | -999.00 | 13696.308 | 120733.81 | 33.90 | 0.01653638 | 25.13 | 0.95610000 | 15.4411 | 24.00 | 0.00882944 | 24.00 | 0.00882944 | 47.4694 | 73363.28 | 0.00 | 137786.89 | 101330.41 | 7.15571168 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.81 | 12.78 | 0.00918713 | 36066.9 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 741.269 | 741.269 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.191932 | 7.44992750 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 741.27 | 741.27 | 1.0000 | 2.23497825 | 1.857580 | 12.56 | 9.96 | 0.00655063 | 29155.3 | 12.89 | 11.62 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 741.27 | 4.60 | 0.00525715 | 4.60 | 0.95610000 | 51.4702 | 21.00 | 0.00792248 | 17.93 | 0.00787750 | 61.5890 | 6830.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 124025.649 | 91466.773 | 5.593641 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8124 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.593641 | 6.73008329 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 125415.19 | 96305.39 | 1.0112 | 6.73008329 | 5.593641 | 25.68 | 18.37 | 0.01020597 | 51815.6 | 11.09 | 11.09 | 0.00850000 | 32580.2 | -999.0 | -999.00 | -999.00 | -999.00 | 12372.911 | 113042.28 | 33.82 | 0.01653623 | 25.11 | 0.95610000 | 17.0926 | 24.00 | 0.00889877 | 24.00 | 0.00889877 | 47.8375 | 66268.23 | 0.00 | 127887.09 | 92887.45 | 6.46429587 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.60 | 12.58 | 0.00906183 | 35538.8 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5118.501 | 5118.501 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.593641 | 6.73008329 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5118.50 | 5118.50 | 1.0000 | 2.01902499 | 1.678092 | 10.37 | 8.62 | 0.00623223 | 26122.7 | 12.89 | 11.62 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5118.50 | 4.60 | 0.00525715 | 4.60 | 0.95610000 | 56.9754 | 18.00 | 0.00752347 | 19.44 | 0.00733210 | 52.2042 | 10255.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 146744.026 | 111157.731 | 6.980205 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2253 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.980205 | 8.39835145 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 147226.35 | 117550.23 | 1.0033 | 8.39835145 | 6.980205 | 25.33 | 18.00 | 0.00989018 | 50656.3 | 11.10 | 11.10 | 0.00850000 | 32590.9 | -999.0 | -999.00 | -999.00 | -999.00 | 15340.962 | 131885.39 | 33.74 | 0.01653608 | 25.09 | 0.95610000 | 13.6973 | 24.00 | 0.00883516 | 24.00 | 0.00883516 | 47.5003 | 82790.36 | 0.00 | 151312.79 | 112813.31 | 8.06668005 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.98 | 12.98 | 0.00931341 | 36564.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 2047.206 | 2047.206 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.980205 | 8.39835145 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2047.21 | 2047.21 | 1.0000 | 2.51950544 | 2.094061 | 12.08 | 9.81 | 0.00660947 | 28817.1 | 12.89 | 11.62 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2047.21 | 4.60 | 0.00525715 | 4.60 | 0.95610000 | 45.6577 | 18.37 | 0.00774568 | 16.43 | 0.00787623 | 67.7245 | 6557.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 4125.50 | 833.50 | 0.00 |
CORE_MID | 2880.67 | 2062.17 | 7.17 |
CORE_TOP | 2675.33 | 2557.83 | 116.83 |
PERIMETER_TOP_ZN_3 | 3136.67 | 3040.00 | 684.17 |
PERIMETER_TOP_ZN_2 | 2913.67 | 3185.33 | 576.50 |
PERIMETER_TOP_ZN_1 | 3298.67 | 2603.17 | 517.67 |
PERIMETER_TOP_ZN_4 | 2653.83 | 3448.50 | 633.67 |
PERIMETER_BOT_ZN_3 | 3161.83 | 2607.33 | 337.83 |
PERIMETER_BOT_ZN_2 | 2753.50 | 2852.50 | 286.17 |
PERIMETER_BOT_ZN_1 | 3709.33 | 2471.83 | 759.33 |
PERIMETER_BOT_ZN_4 | 2584.17 | 2973.83 | 283.50 |
PERIMETER_MID_ZN_3 | 3247.50 | 2678.00 | 466.17 |
PERIMETER_MID_ZN_2 | 2195.00 | 2801.00 | 406.33 |
PERIMETER_MID_ZN_1 | 3397.33 | 2194.50 | 358.83 |
PERIMETER_MID_ZN_4 | 2562.33 | 3228.00 | 422.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4948.17 | 4224.50 | 1402.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.50 | 2.50 | 0.50 | 2.17 |
PERIMETER_TOP_ZN_2 | 0.00 | 17.67 | 0.00 | 17.67 |
PERIMETER_TOP_ZN_1 | 0.17 | 18.83 | 0.17 | 18.67 |
PERIMETER_TOP_ZN_4 | 0.00 | 15.67 | 0.00 | 11.50 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 12.83 | 0.00 | 12.83 |
PERIMETER_BOT_ZN_1 | 10.33 | 75.50 | 10.33 | 75.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 9.67 | 0.00 | 8.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 15.33 | 0.00 | 15.33 |
PERIMETER_MID_ZN_1 | 0.00 | 19.00 | 0.00 | 18.83 |
PERIMETER_MID_ZN_4 | 0.00 | 12.50 | 0.00 | 9.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 10.83 | 136.83 | 10.83 | 131.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.436 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.394 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.390 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.589 | 0.065 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.852 | 0.069 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.736 | 0.065 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.933 | 0.068 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.480 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.759 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.667 | 1.272 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.777 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.594 | 0.054 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.940 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.778 | 0.054 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.995 | 0.057 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.24 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 7040206.03 | 0.00 | 7040206.03 | 0.00 | 7040206.03 | 13393058.27 | 8098.33 | 158.13 | 503.55 | 134.92 |
CORE_MID | 6316267.13 | 0.00 | 6316267.13 | 0.00 | 6316267.13 | 13393058.27 | 8755.33 | 0.32 | 4.35 | 90.52 |
CORE_TOP | 6251923.00 | 0.00 | 6251923.00 | 0.00 | 6251923.00 | 13393058.27 | 8757.50 | 0.09 | 2.42 | 86.99 |
PERIMETER_TOP_ZN_3 | 1992491.64 | 0.00 | 1992491.64 | 422189.62 | 2414681.26 | 2823374.22 | 3976.74 | 58.34 | 4724.92 | 86.99 |
PERIMETER_TOP_ZN_2 | 1828273.50 | 0.00 | 1828273.50 | 281458.05 | 2109731.55 | 1787429.43 | 3725.66 | 0.18 | 5034.16 | 86.99 |
PERIMETER_TOP_ZN_1 | 2487756.51 | 0.00 | 2487756.51 | 422189.62 | 2909946.13 | 2823374.22 | 3727.34 | 0.16 | 5032.49 | 86.99 |
PERIMETER_TOP_ZN_4 | 2003677.32 | 0.00 | 2003677.32 | 281458.05 | 2285135.37 | 1787312.18 | 3724.26 | 0.16 | 5035.58 | 86.99 |
PERIMETER_BOT_ZN_3 | 1637344.21 | 0.00 | 1637344.21 | 224477.40 | 1861821.61 | 2823374.22 | 5562.74 | 225.35 | 2971.91 | 134.92 |
PERIMETER_BOT_ZN_2 | 1645211.46 | 0.00 | 1645211.46 | 149650.70 | 1794862.16 | 1787429.43 | 3685.23 | 8.65 | 5066.12 | 134.92 |
PERIMETER_BOT_ZN_1 | 2266258.67 | 0.00 | 2266258.67 | 4323043.00 | 6589301.67 | 2823374.22 | 3821.38 | 47.16 | 4891.46 | 134.92 |
PERIMETER_BOT_ZN_4 | 1687269.91 | 0.00 | 1687269.91 | 149650.70 | 1836920.61 | 1787312.18 | 3681.56 | 16.88 | 5061.55 | 134.92 |
PERIMETER_MID_ZN_3 | 2006843.75 | 0.00 | 2006843.75 | 351441.55 | 2358285.30 | 2823374.22 | 3936.24 | 41.13 | 4782.63 | 90.52 |
PERIMETER_MID_ZN_2 | 2041455.70 | 0.00 | 2041455.70 | 234292.96 | 2275748.66 | 1601953.02 | 3719.37 | 0.40 | 5040.23 | 999.52 |
PERIMETER_MID_ZN_1 | 2626714.64 | 0.00 | 2626714.64 | 351441.55 | 2978156.19 | 2823374.22 | 3732.40 | 11.21 | 5016.39 | 90.52 |
PERIMETER_MID_ZN_4 | 2139380.28 | 0.00 | 2139380.28 | 234292.96 | 2373673.24 | 1787312.18 | 3718.42 | 0.21 | 5041.37 | 90.52 |
Total Facility | 43971073.75 | 0.00 | 43971073.75 | 7425586.18 | 51396659.92 | 67658168.57 | 8760.00 | 540.05 | 5217.35 | 1077.60 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3204 | 0.0000 | 0.3204 | 0.0000 | 0.3204 | 0.4247 | 5288.10 | 158.08 | 496.81 |
CORE_MID | 0.2898 | 0.0000 | 0.2898 | 0.0000 | 0.2898 | 0.4247 | 5939.82 | 0.26 | 2.93 |
CORE_TOP | 0.2871 | 0.0000 | 0.2871 | 0.0000 | 0.2871 | 0.4247 | 5941.13 | 0.07 | 1.80 |
PERIMETER_TOP_ZN_3 | 0.0915 | 0.0000 | 0.0915 | 0.0101 | 0.1017 | 0.0895 | 1244.99 | 58.30 | 4639.72 |
PERIMETER_TOP_ZN_2 | 0.0839 | 0.0000 | 0.0839 | 0.0067 | 0.0907 | 0.0567 | 994.71 | 0.14 | 4948.15 |
PERIMETER_TOP_ZN_1 | 0.1144 | 0.0000 | 0.1144 | 0.0101 | 0.1245 | 0.0895 | 995.79 | 0.14 | 4947.06 |
PERIMETER_TOP_ZN_4 | 0.0919 | 0.0000 | 0.0919 | 0.0067 | 0.0987 | 0.0567 | 993.60 | 0.14 | 4949.26 |
PERIMETER_BOT_ZN_3 | 0.0745 | 0.0000 | 0.0745 | 0.0054 | 0.0799 | 0.0895 | 2866.56 | 224.68 | 2851.76 |
PERIMETER_BOT_ZN_2 | 0.0747 | 0.0000 | 0.0747 | 0.0036 | 0.0783 | 0.0567 | 1000.32 | 8.50 | 4934.18 |
PERIMETER_BOT_ZN_1 | 0.1034 | 0.0000 | 0.1034 | 0.1969 | 0.3003 | 0.0895 | 1130.67 | 46.92 | 4765.41 |
PERIMETER_BOT_ZN_4 | 0.0766 | 0.0000 | 0.0766 | 0.0036 | 0.0801 | 0.0567 | 998.04 | 15.96 | 4929.01 |
PERIMETER_MID_ZN_3 | 0.0922 | 0.0000 | 0.0922 | 0.0084 | 0.1006 | 0.0895 | 1206.45 | 40.82 | 4695.74 |
PERIMETER_MID_ZN_2 | 0.0926 | 0.0000 | 0.0926 | 0.0060 | 0.0986 | 0.0567 | 991.95 | 0.29 | 4041.76 |
PERIMETER_MID_ZN_1 | 0.1207 | 0.0000 | 0.1207 | 0.0084 | 0.1291 | 0.0895 | 1002.88 | 11.11 | 4929.01 |
PERIMETER_MID_ZN_4 | 0.0981 | 0.0000 | 0.0981 | 0.0056 | 0.1037 | 0.0567 | 991.43 | 0.12 | 4951.45 |
Total Facility | 2.0118 | 0.0000 | 2.0118 | 0.2716 | 2.2834 | 2.1513 | 5943.00 | 537.42 | 5048.79 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 20666526.19 | 0.00 | 20666526.19 | 22614548.33 | 3673.90 | 0.26 | 5085.84 | 134.92 |
PACU_VAV_MID | 21903346.04 | 0.00 | 21903346.04 | 22429071.92 | 3719.92 | 0.07 | 5040.01 | 90.52 |
PACU_VAV_TOP | 21083191.20 | 0.00 | 21083191.20 | 22614548.33 | 3724.59 | 0.07 | 5035.34 | 86.99 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9403 | 0.0000 | 0.9403 | 0.7171 | 990.79 | 0.12 | 4952.09 |
PACU_VAV_MID | 1.0052 | 0.0000 | 1.0052 | 0.7084 | 991.99 | 0.02 | 4950.99 |
PACU_VAV_TOP | 0.9682 | 0.0000 | 0.9682 | 0.7171 | 993.90 | 0.05 | 4949.05 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 39.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5050.11 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 56.73 | 0.00 | 0.00 | 0.00 | 0.00 | 4986.81 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 27.04 | 0.00 | 0.00 | 0.00 | 0.00 | 5010.98 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.0377 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1288 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1505 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2069 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0996 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1627 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 842 |
Defaulted Fields | 530 |
Fields with Defaults | 2020 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2534.72 | 15934.24 | 20-FEB-18:10 | 249983.20 | 06-FEB-07:10 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 960.92 | 383.73 | 01-JAN-00:10 | 194053.37 | 06-FEB-07:10 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 03-JAN-13:10 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 03-JAN-13:10 |
ElectricityPurchased:Facility | 2534.72 | 15934.24 | 20-FEB-18:10 | 249983.20 | 06-FEB-07:10 |
ElectricityPurchased:Plant | 2534.72 | 15934.24 | 20-FEB-18:10 | 249983.20 | 06-FEB-07:10 |
Cogeneration:ElectricityPurchased | 2534.72 | 15934.24 | 20-FEB-18:10 | 249983.20 | 06-FEB-07:10 |
General:Cogeneration:ElectricityPurchased | 2534.72 | 15934.24 | 20-FEB-18:10 | 249983.20 | 06-FEB-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2534.72 | 15934.24 | 20-FEB-18:10 | 249983.20 | 06-FEB-07:10 |
ElectricityNet:Plant | 2534.72 | 15934.24 | 20-FEB-18:10 | 249983.20 | 06-FEB-07:10 |
Cogeneration:ElectricityNet | 2534.72 | 15934.24 | 20-FEB-18:10 | 249983.20 | 06-FEB-07:10 |
General:Cogeneration:ElectricityNet | 2534.72 | 15934.24 | 20-FEB-18:10 | 249983.20 | 06-FEB-07:10 |
Fans:Electricity | 178.80 | 0.00 | 01-JAN-00:10 | 21602.67 | 30-AUG-16:00 |
General:Fans:Electricity | 178.80 | 0.00 | 01-JAN-00:10 | 21602.67 | 30-AUG-16:00 |
Heating:Electricity | 47.15 | 0.00 | 01-JAN-00:10 | 169246.70 | 06-FEB-07:10 |
General:Heating:Electricity | 47.15 | 0.00 | 01-JAN-00:10 | 169246.70 | 06-FEB-07:10 |
ExteriorLights:Electricity | 235.95 | 0.00 | 01-JAN-07:30 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 235.95 | 0.00 | 01-JAN-07:30 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 707.47 | 0.00 | 01-JAN-00:10 | 93294.86 | 21-JUL-16:00 |
General:Cooling:Electricity | 707.47 | 0.00 | 01-JAN-00:10 | 93294.86 | 21-JUL-16:00 |
Electricity:Plant | 42.32 | 0.00 | 01-JAN-00:10 | 5362.54 | 23-JAN-12:50 |
WaterSystems:Electricity | 42.18 | 0.00 | 01-JAN-00:10 | 5355.69 | 23-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 42.18 | 0.00 | 01-JAN-00:10 | 5355.69 | 23-JAN-12:50 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 06-JAN-17:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 06-JAN-17:10 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5642.33 | 0.00 | 01-JAN-00:10 | 737792.15 | 06-FEB-07:10 |
EnergyTransfer:Building | 2645.07 | 0.00 | 01-JAN-00:10 | 549123.79 | 06-FEB-07:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 319.88 | 0.00 | 01-JAN-00:10 | 26558.97 | 10-OCT-16:00 |
Heating:EnergyTransfer | 805.91 | 0.00 | 01-JAN-00:10 | 535580.64 | 06-FEB-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 805.91 | 0.00 | 01-JAN-00:10 | 535580.64 | 06-FEB-07:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1839.16 | 0.00 | 01-JAN-00:10 | 203657.11 | 30-AUG-16:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 319.88 | 0.00 | 01-JAN-00:10 | 26558.97 | 10-OCT-16:00 |
General:Cooling:EnergyTransfer | 1839.16 | 0.00 | 01-JAN-00:10 | 203657.11 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 319.88 | 0.00 | 01-JAN-00:10 | 26558.97 | 10-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 495.98 | 0.00 | 01-JAN-00:10 | 192861.70 | 09-JAN-07:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 406.34 | 0.00 | 01-JAN-00:10 | 192861.70 | 09-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 406.34 | 0.00 | 01-JAN-00:10 | 192861.70 | 09-JAN-07:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 89.63 | 0.00 | 01-JAN-00:10 | 17781.19 | 07-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 89.63 | 0.00 | 01-JAN-00:10 | 17781.19 | 07-JUL-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 243.67 | 0.00 | 01-JAN-00:10 | 165034.31 | 09-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 207.19 | 0.00 | 01-JAN-00:10 | 165034.31 | 09-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 207.19 | 0.00 | 01-JAN-00:10 | 165034.31 | 09-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 36.48 | 0.00 | 01-JAN-00:10 | 5133.06 | 10-OCT-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 36.48 | 0.00 | 01-JAN-00:10 | 5133.06 | 10-OCT-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 218.98 | 0.00 | 01-JAN-00:10 | 95695.78 | 10-MAR-17:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 175.79 | 0.00 | 01-JAN-00:10 | 95695.78 | 10-MAR-17:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 175.79 | 0.00 | 01-JAN-00:10 | 95695.78 | 10-MAR-17:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 43.18 | 0.00 | 01-JAN-00:10 | 5636.74 | 10-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 43.18 | 0.00 | 01-JAN-00:10 | 5636.74 | 10-OCT-14:10 |
EnergyTransfer:Zone:CORE_MID | 226.59 | 0.00 | 01-JAN-00:10 | 20910.68 | 10-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.02 | 0.00 | 01-JAN-00:10 | 8732.34 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.02 | 0.00 | 01-JAN-00:10 | 8732.34 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 226.57 | 0.00 | 01-JAN-00:10 | 20910.68 | 10-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 226.57 | 0.00 | 01-JAN-00:10 | 20910.68 | 10-OCT-14:00 |
EnergyTransfer:Zone:CORE_TOP | 249.94 | 0.00 | 01-JAN-00:10 | 25545.65 | 05-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.47 | 0.00 | 01-JAN-00:10 | 20212.64 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.47 | 0.00 | 01-JAN-00:10 | 20212.64 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 249.47 | 0.00 | 01-JAN-00:10 | 25545.65 | 05-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 249.47 | 0.00 | 01-JAN-00:10 | 25545.65 | 05-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 75.62 | 0.00 | 01-JAN-00:10 | 10541.17 | 06-FEB-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.57 | 0.00 | 01-JAN-00:10 | 10541.17 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.57 | 0.00 | 01-JAN-00:10 | 10541.17 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.05 | 0.00 | 01-JAN-00:10 | 9842.39 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.05 | 0.00 | 01-JAN-00:10 | 9842.39 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 65.72 | 0.00 | 01-JAN-00:10 | 9232.17 | 20-JUL-09:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.29 | 0.00 | 01-JAN-00:10 | 6924.89 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.29 | 0.00 | 01-JAN-00:10 | 6924.89 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.43 | 0.00 | 01-JAN-00:10 | 9232.17 | 20-JUL-09:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.43 | 0.00 | 01-JAN-00:10 | 9232.17 | 20-JUL-09:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.65 | 0.00 | 01-JAN-00:10 | 14801.71 | 06-NOV-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.54 | 0.00 | 01-JAN-00:10 | 10695.66 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.54 | 0.00 | 01-JAN-00:10 | 10695.66 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 96.11 | 0.00 | 01-JAN-00:10 | 14801.71 | 06-NOV-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 96.11 | 0.00 | 01-JAN-00:10 | 14801.71 | 06-NOV-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 67.65 | 0.00 | 01-JAN-00:10 | 11313.09 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.53 | 0.00 | 01-JAN-00:10 | 7270.99 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.53 | 0.00 | 01-JAN-00:10 | 7270.99 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.12 | 0.00 | 01-JAN-00:10 | 11313.09 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.12 | 0.00 | 01-JAN-00:10 | 11313.09 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.47 | 0.00 | 01-JAN-00:10 | 9064.58 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.71 | 0.00 | 01-JAN-00:10 | 7319.03 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.71 | 0.00 | 01-JAN-00:10 | 7319.03 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 66.76 | 0.00 | 01-JAN-00:10 | 9064.58 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 66.76 | 0.00 | 01-JAN-00:10 | 9064.58 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 63.21 | 0.00 | 01-JAN-00:10 | 8381.81 | 20-JUL-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.33 | 0.00 | 01-JAN-00:10 | 4709.87 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.33 | 0.00 | 01-JAN-00:10 | 4709.87 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 62.88 | 0.00 | 01-JAN-00:10 | 8381.81 | 20-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 62.88 | 0.00 | 01-JAN-00:10 | 8381.81 | 20-JUL-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 103.05 | 0.00 | 01-JAN-00:10 | 23753.97 | 20-DEC-07:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.88 | 0.00 | 01-JAN-00:10 | 23753.97 | 20-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.88 | 0.00 | 01-JAN-00:10 | 23753.97 | 20-DEC-07:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 98.17 | 0.00 | 01-JAN-00:10 | 16340.19 | 30-AUG-16:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 98.17 | 0.00 | 01-JAN-00:10 | 16340.19 | 30-AUG-16:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 62.74 | 0.00 | 01-JAN-00:10 | 10032.03 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.35 | 0.00 | 01-JAN-00:10 | 4427.99 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.35 | 0.00 | 01-JAN-00:10 | 4427.99 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 62.39 | 0.00 | 01-JAN-00:10 | 10032.03 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 62.39 | 0.00 | 01-JAN-00:10 | 10032.03 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 68.31 | 0.00 | 01-JAN-00:10 | 8999.40 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.08 | 0.00 | 01-JAN-00:10 | 8904.57 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.08 | 0.00 | 01-JAN-00:10 | 8904.57 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 67.24 | 0.00 | 01-JAN-00:10 | 8999.40 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 67.24 | 0.00 | 01-JAN-00:10 | 8999.40 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 62.91 | 0.00 | 01-JAN-00:10 | 9199.77 | 20-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.58 | 0.00 | 01-JAN-00:10 | 6468.46 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.58 | 0.00 | 01-JAN-00:10 | 6468.46 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 62.32 | 0.00 | 01-JAN-00:10 | 9199.77 | 20-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 62.32 | 0.00 | 01-JAN-00:10 | 9199.77 | 20-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.75 | 0.00 | 01-JAN-00:10 | 14222.28 | 06-NOV-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.59 | 0.00 | 01-JAN-00:10 | 7547.44 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.59 | 0.00 | 01-JAN-00:10 | 7547.44 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.15 | 0.00 | 01-JAN-00:10 | 14222.28 | 06-NOV-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.15 | 0.00 | 01-JAN-00:10 | 14222.28 | 06-NOV-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 63.96 | 0.00 | 01-JAN-00:10 | 10667.65 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.65 | 0.00 | 01-JAN-00:10 | 6200.58 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.65 | 0.00 | 01-JAN-00:10 | 6200.58 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 63.31 | 0.00 | 01-JAN-00:10 | 10667.65 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 63.31 | 0.00 | 01-JAN-00:10 | 10667.65 | 30-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:10 |
EnergyTransfer:HVAC | 2957.83 | 0.00 | 01-JAN-00:10 | 334544.53 | 06-OCT-14:10 |
HeatingCoils:EnergyTransfer | 47.15 | 0.00 | 01-JAN-00:10 | 169246.70 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2910.69 | 0.00 | 01-JAN-00:10 | 334544.53 | 06-OCT-14:10 |
EnergyTransfer:Plant | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:10 |
WaterSystems:EnergyTransfer | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -319.883 | 0.000 | 0.000 | 32.803 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -84.706 |
CORE_MID | 0.000 | 0.000 | 0.018 | -226.573 | 0.000 | 0.000 | 33.482 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -34.138 |
CORE_TOP | 0.000 | 0.000 | 0.466 | -249.471 | 0.000 | 0.000 | 34.158 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -12.364 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.573 | -73.049 | 0.000 | 0.000 | 7.355 | 23.566 | 24.333 | 29.240 | 0.000 | 0.543 | 11.592 | 0.000 | -24.523 | 0.000 | -1.630 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.292 | -64.429 | 0.000 | 0.000 | 4.661 | 14.919 | 15.404 | 39.143 | 0.000 | 0.376 | 4.538 | 0.000 | -14.782 | 0.000 | -1.121 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.540 | -96.105 | 0.000 | 0.000 | 7.220 | 23.566 | 24.332 | 67.148 | 0.000 | 0.521 | 0.000 | 0.000 | -22.766 | 0.000 | -1.845 | -3.611 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.531 | -66.122 | 0.000 | 0.000 | 4.753 | 14.918 | 15.403 | 39.720 | 0.000 | 0.404 | 6.200 | 0.000 | -15.677 | 0.000 | -1.131 | 0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.707 | -66.759 | 0.000 | 0.000 | 7.266 | 23.566 | 24.333 | 29.633 | 0.000 | 0.285 | 8.732 | 0.000 | -26.776 | 0.000 | -0.986 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.328 | -62.877 | 0.000 | 0.000 | 4.624 | 14.919 | 15.404 | 39.808 | 0.000 | 0.201 | 4.637 | 0.000 | -16.364 | 0.000 | -0.679 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 4.877 | -98.171 | 0.000 | 0.000 | 7.144 | 23.566 | 24.332 | 68.078 | 0.000 | 11.651 | 0.001 | 0.000 | -26.026 | 0.000 | -13.300 | -2.150 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.351 | -62.390 | 0.000 | 0.000 | 4.680 | 14.918 | 15.403 | 40.299 | 0.000 | 0.205 | 4.681 | 0.000 | -17.461 | 0.000 | -0.687 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 1.079 | -67.233 | 0.000 | 0.000 | 7.262 | 23.566 | 24.333 | 29.255 | 0.000 | 0.438 | 9.379 | 0.000 | -26.583 | 0.000 | -1.495 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.583 | -62.322 | 0.000 | 0.000 | 3.440 | 14.919 | 15.404 | 39.331 | 0.000 | 0.317 | 5.126 | 0.000 | -15.787 | 0.000 | -1.010 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.591 | -91.152 | 0.000 | 0.000 | 7.127 | 23.566 | 24.332 | 67.232 | 0.000 | 0.422 | 0.005 | 0.000 | -24.667 | 0.000 | -1.678 | -5.772 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.646 | -63.312 | 0.000 | 0.000 | 4.707 | 14.918 | 15.403 | 39.903 | 0.000 | 0.326 | 5.366 | 0.000 | -16.932 | 0.000 | -1.026 | 0.000 |
TOPFLOOR_PLENUM | 8.146 | -96.998 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.510 | 90.936 | 0.000 | 0.000 | 0.000 | -2.593 | 0.000 |
MIDFLOOR_PLENUM | 0.703 | -43.766 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.639 | 45.235 | 0.000 | 0.000 | 0.000 | -2.812 | 0.000 |
FIRSTFLOOR_PLENUM | 0.283 | -52.511 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.473 | 54.143 | 0.000 | 0.000 | 0.000 | -2.388 | 0.000 |
Total Facility | 9.132 | -193.275 | 16.580 | -1669.849 | 0.000 | 0.000 | 170.683 | 566.263 | 729.266 | 528.789 | 0.000 | 17.310 | 250.573 | 0.000 | -248.342 | 0.000 | -34.380 | -142.742 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 07-AUG-04:02 | 0.00 | 0.00 | 0.00 | -53797.05 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 46746.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-04:02 | 0.00 | 0.00 | 0.00 | -43750.33 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 40223.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-AUG-04:01 | 0.00 | 0.00 | 0.00 | -49161.57 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 45635.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-14:51 | 0.00 | 0.00 | 0.00 | -16588.43 | 0.00 | 0.00 | 27.88 | 114.31 | 478.42 | 4053.85 | 0.00 | 70.13 | 11843.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 10-SEP-09:52 | 0.00 | 0.00 | 0.00 | -16722.62 | 0.00 | 0.00 | 12.61 | 72.37 | 302.86 | 8042.38 | 0.00 | 150.46 | 8141.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-JAN-14:01 | 0.00 | 0.00 | 0.00 | -23571.47 | 0.00 | 0.00 | 20.56 | 114.31 | 478.41 | 13187.21 | 0.00 | 0.00 | 9816.47 | 0.00 | -0.00 | 0.00 | -45.49 | 0.00 |
PERIMETER_TOP_ZN_4 | 28-MAY-16:01 | 0.00 | 0.00 | 0.00 | -19075.25 | 0.00 | 0.00 | 11.96 | 72.36 | 302.86 | 8786.72 | 0.00 | 99.40 | 9801.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 07-JUL-04:01 | 0.00 | 0.00 | 0.00 | -11671.43 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 11244.94 | 0.00 | -315.79 | 0.00 | -1.15 | 0.00 |
PERIMETER_BOT_ZN_2 | 03-SEP-09:21 | 0.00 | 0.00 | 0.00 | -16560.59 | 0.00 | 0.00 | 13.92 | 72.37 | 302.86 | 9104.32 | 0.00 | 11.27 | 7055.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-DEC-13:11 | 0.00 | 0.00 | 0.00 | -19743.98 | 0.00 | 0.00 | 22.00 | 114.31 | 478.41 | 14179.37 | 0.00 | 0.00 | 4970.72 | 0.00 | -0.00 | 0.00 | -20.83 | 0.00 |
PERIMETER_BOT_ZN_4 | 17-SEP-15:31 | 0.00 | 0.00 | 0.00 | -16395.89 | 0.00 | 0.00 | 15.20 | 72.36 | 302.86 | 8136.48 | 0.00 | 72.64 | 7796.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 26-JUN-04:01 | 0.00 | 0.00 | 0.00 | -12042.38 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 11910.50 | 0.00 | -611.55 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-08:41 | 0.00 | 0.00 | 0.00 | -17592.51 | 0.00 | 0.00 | 13.18 | 72.37 | 302.86 | 9098.04 | 0.00 | 0.00 | 8112.15 | 0.00 | -0.00 | 0.00 | -6.09 | 0.00 |
PERIMETER_MID_ZN_1 | 01-JAN-14:01 | 0.00 | 0.00 | 0.00 | -20410.60 | 0.00 | 0.00 | 20.88 | 114.31 | 478.41 | 13290.36 | 0.00 | 0.00 | 6545.21 | 0.00 | -0.00 | 0.00 | -38.58 | 0.00 |
PERIMETER_MID_ZN_4 | 29-MAY-16:41 | 0.00 | 0.00 | 0.00 | -18705.26 | 0.00 | 0.00 | 12.68 | 72.36 | 302.86 | 8358.51 | 0.00 | 35.05 | 9923.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-MAY-14:41 | 0.00 | -20425.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 20346.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 04-JAN-06:11 | 0.00 | -17130.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17316.49 | 0.00 | -0.00 | 0.00 | -185.83 | 0.00 |
FIRSTFLOOR_PLENUM | 04-JAN-06:11 | 0.00 | -18166.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18319.10 | 0.00 | -0.00 | 0.00 | -152.63 | 0.00 |
Total Facility | 24-JUL-04:01 | 0.00 | 12256.42 | 0.00 | -282870.09 | 0.00 | 0.00 | 0.00 | 5493.69 | 15894.33 | 0.00 | 0.00 | 2.45 | 252957.48 | 0.00 | -3734.16 | 0.00 | -0.12 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-FEB-07:03 | 0.00 | 0.00 | 26197.61 | 0.00 | 0.00 | 0.00 | 916.93 | 3253.54 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33394.00 |
CORE_TOP | 06-FEB-06:11 | 0.00 | 0.00 | 53579.60 | 0.00 | 0.00 | 0.00 | 505.29 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -58195.33 |
PERIMETER_TOP_ZN_3 | 23-JAN-06:11 | 0.00 | 0.00 | 19805.60 | 0.00 | 0.00 | 0.00 | 112.46 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2882.06 | 0.00 | -102.89 | -17799.63 |
PERIMETER_TOP_ZN_2 | 09-JAN-06:11 | 0.00 | 0.00 | 18479.88 | 0.00 | 0.00 | 0.00 | 71.54 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3602.03 | 0.00 | -91.57 | -15406.37 |
PERIMETER_TOP_ZN_1 | 09-JAN-06:11 | 0.00 | 0.00 | 23536.79 | 0.00 | 0.00 | 0.00 | 112.09 | 228.62 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5506.27 | 0.00 | -137.31 | -18871.81 |
PERIMETER_TOP_ZN_4 | 09-JAN-06:11 | 0.00 | 0.00 | 20687.75 | 0.00 | 0.00 | 0.00 | 71.33 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3607.37 | 0.00 | -92.43 | -17607.81 |
PERIMETER_BOT_ZN_3 | 06-FEB-06:11 | 0.00 | 0.00 | 19366.61 | 0.00 | 0.00 | 0.00 | 109.15 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3798.28 | 0.00 | -29.49 | -16514.50 |
PERIMETER_BOT_ZN_2 | 06-FEB-06:11 | 0.00 | 0.00 | 20141.33 | 0.00 | 0.00 | 0.00 | 69.27 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2568.86 | 0.00 | -20.48 | -18169.81 |
PERIMETER_BOT_ZN_1 | 20-DEC-07:10 | 0.00 | 0.00 | 23841.59 | 0.00 | 0.00 | 0.00 | 193.30 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 6541.31 | 0.00 | -8945.86 | 0.00 | -22954.09 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-06:11 | 0.00 | 0.00 | 20761.14 | 0.00 | 0.00 | 0.00 | 68.98 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2602.11 | 0.00 | -20.75 | -18755.80 |
PERIMETER_MID_ZN_3 | 04-JAN-06:11 | 0.00 | 0.00 | 18637.89 | 0.00 | 0.00 | 0.00 | 104.52 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4969.08 | 0.00 | -100.91 | -14538.93 |
PERIMETER_MID_ZN_2 | 04-JAN-06:11 | 0.00 | 0.00 | 20536.66 | 0.00 | 0.00 | 0.00 | 67.47 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3264.58 | 0.00 | -68.35 | -17819.76 |
PERIMETER_MID_ZN_1 | 04-JAN-06:11 | 0.00 | 0.00 | 22791.32 | 0.00 | 0.00 | 0.00 | 103.73 | 228.62 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4838.23 | 0.00 | -103.83 | -18819.50 |
PERIMETER_MID_ZN_4 | 04-JAN-06:11 | 0.00 | 0.00 | 21352.24 | 0.00 | 0.00 | 0.00 | 67.44 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3121.39 | 0.00 | -68.74 | -18778.10 |
TOPFLOOR_PLENUM | 17-FEB-06:04 | 35768.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -116.72 | -35651.35 |
MIDFLOOR_PLENUM | 06-FEB-06:15 | 11522.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -81.42 | -11441.01 |
FIRSTFLOOR_PLENUM | 25-OCT-04:01 | 5779.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5805.64 |
Total Facility | 06-FEB-06:11 | -32799.03 | 19537.56 | 300283.53 | -19537.56 | 0.00 | 0.00 | 2457.20 | 5493.69 | 20036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36311.13 | 0.00 | -3689.53 | -255471.08 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.9042 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.1919 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.3962 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5936 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 7.3980 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.9802 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.0713 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0713 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 1.9215 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.9215 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.2194 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2194 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 3.2845 | 3.2845 | 0.9853 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.6735 | 2.6735 | 0.8047 | No | 0.0000 | 0.0000 | 0.3010 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 3.1985 | 3.1985 | 0.9596 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9919 | 0.9919 | 0.2976 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9428 | 0.9428 | 0.2828 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.2002 | 1.2002 | 0.3601 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0645 | 1.0645 | 0.3194 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.8084 | 0.8084 | 0.2425 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.8764 | 0.8764 | 0.2629 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0188 | 1.0188 | 0.3057 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9161 | 0.9161 | 0.2748 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.8149 | 0.8149 | 0.2445 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9158 | 0.9158 | 0.2747 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0329 | 1.0329 | 0.3099 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9591 | 0.9591 | 0.2877 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.9042 | 6.1919 | 6.9042 | 2.0713 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.3962 | 5.5936 | 6.3962 | 1.9215 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 7.3980 | 6.9802 | 7.3980 | 2.2194 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9853 | 4.2698 | 0.9853 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.8047 | 3.4783 | 0.8047 | No | 0.0000 | 0.0000 | 0.2314 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9596 | 4.1581 | 0.9596 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2976 | 1.2894 | 0.2976 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2828 | 1.2257 | 0.2828 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3601 | 1.5603 | 0.3601 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3194 | 1.3839 | 0.3194 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2425 | 1.0510 | 0.2425 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2629 | 1.1393 | 0.2629 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3057 | 1.3245 | 0.3057 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2748 | 1.1909 | 0.2748 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2445 | 1.0594 | 0.2445 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2747 | 1.1906 | 0.2747 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3099 | 1.3427 | 0.3099 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2877 | 1.2468 | 0.2877 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.0713 | 2.0713 | 8.9755 | 2.0713 | 0.0000 | 1.0000 |
PACU_VAV_MID | 1.9215 | 1.9215 | 8.3178 | 1.9215 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.2194 | 2.2194 | 9.6174 | 2.2194 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 10.83 |
Number of hours cooling loads not met | 131.33 |
Number of hours not met | 142.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 47.15 | 169246.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 707.47 | 93294.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 235.95 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 178.80 | 21602.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 42.18 | 5355.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 2534.72 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2534.72 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 9.46 |
Space Cooling | 142.00 |
Fans (All) | 35.89 |
Service Water Heating | 8.47 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 508.76 |
Subtotal | 508.76 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 22.34 |
Space Heating | 1.86 |
Space Cooling | 27.91 |
Fans (All) | 7.05 |
Service Water Heating | 1.66 |
Receptacle Equipment | 28.77 |
Miscellaneous | 10.40 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7687.00 | 1073.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8601.50 | 158.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8573.33 | 186.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8552.00 | 208.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8522.17 | 237.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8671.67 | 88.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8615.17 | 144.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8545.17 | 214.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8570.00 | 190.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8607.67 | 152.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8588.83 | 171.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8553.50 | 206.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8514.50 | 245.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7840.50 | 919.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7687.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1073.00 | 0.00 | 0.00 | 0.00 |
Average | 8526.45 | 233.55 | 0.00 | 0.00 | 0.00 |
Sum | 153476.17 | 4203.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 127958.33 | 345.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128301.67 | 2.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 345.67 | 0.00 | 0.00 | 0.00 |
Average | 34124.00 | 19.33 | 0.00 | 0.00 | 0.00 |
Sum | 614232.00 | 348.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7533.50 | 1226.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7248.33 | 1511.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7287.00 | 1473.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7242.17 | 1517.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7306.67 | 1453.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7429.33 | 1330.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7478.17 | 1281.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6817.50 | 1942.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7443.50 | 1316.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7173.50 | 1586.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7300.33 | 1459.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7193.17 | 1566.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7272.17 | 1487.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 6689.50 | 2070.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7650.33 | 1109.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7793.83 | 966.17 | 0.00 | 0.00 | 0.00 |
Min | 6689.50 | 9.67 | 0.00 | 0.00 | 0.00 |
Max | 8750.33 | 2070.50 | 0.00 | 0.00 | 0.00 |
Average | 7463.77 | 1296.23 | 0.00 | 0.00 | 0.00 |
Sum | 134347.83 | 23332.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127869.33 | 434.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128296.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128300.33 | 3.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24883.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24893.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24902.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 22090.00 | 2819.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24883.00 | 26.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24895.67 | 13.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128300.33 | 2819.00 | 0.00 | 0.00 | 0.00 |
Average | 33957.12 | 186.21 | 0.00 | 0.00 | 0.00 |
Sum | 611228.17 | 3351.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204787E+11 | 38388.16 | 02-JAN-06:12 | 16.00 | 15.39 | 0.195615E+10 | 2606.69 | 20-JAN-14:39 | 13.67 | 10.76 |
February | 0.189014E+11 | 24224.86 | 28-FEB-06:12 | 18.47 | 17.93 | 0.177820E+10 | 2606.69 | 16-FEB-10:00 | 18.47 | 17.93 |
March | 0.233310E+11 | 33973.33 | 09-MAR-06:02 | 1.10 | -2.1 | 0.213443E+10 | 2606.69 | 03-MAR-10:20 | 1.10 | -2.1 |
April | 0.241514E+11 | 43336.54 | 28-APR-05:12 | 22.90 | 21.77 | 0.191495E+10 | 2606.69 | 10-APR-09:09 | 22.90 | 21.77 |
May | 0.311772E+11 | 53347.52 | 01-MAY-04:01 | 26.10 | 23.70 | 0.207695E+10 | 2606.69 | 09-MAY-09:30 | 28.60 | 23.11 |
June | 0.314147E+11 | 53298.57 | 19-JUN-04:01 | 25.50 | 24.30 | 0.206977E+10 | 2606.69 | 01-JUN-13:00 | 25.50 | 24.30 |
July | 0.312618E+11 | 53368.72 | 06-JUL-04:02 | 25.50 | 23.88 | 0.192280E+10 | 2606.69 | 03-JUL-09:09 | 25.50 | 23.88 |
August | 0.331840E+11 | 53797.51 | 07-AUG-04:02 | 24.83 | 24.08 | 0.215935E+10 | 2606.69 | 30-AUG-09:39 | 29.43 | 23.90 |
September | 0.301860E+11 | 52858.19 | 01-SEP-04:21 | 24.10 | 23.23 | 0.191675E+10 | 2606.69 | 07-SEP-09:09 | 28.90 | 25.09 |
October | 0.298640E+11 | 53620.92 | 06-OCT-04:02 | 25.10 | 25.10 | 0.199294E+10 | 2606.69 | 25-OCT-09:30 | 25.50 | 24.80 |
November | 0.241783E+11 | 45515.47 | 03-NOV-05:12 | 22.27 | 21.87 | 0.196638E+10 | 2606.69 | 22-NOV-10:00 | 16.10 | 6.87 |
December | 0.217552E+11 | 36082.64 | 15-DEC-06:12 | 21.00 | 21.00 | 0.190228E+10 | 2606.69 | 12-DEC-14:09 | 21.00 | 21.00 |
Annual Sum or Average | 0.319884E+12 | 0.237909E+11 | ||||||||
Minimum of Months | 0.189014E+11 | 24224.86 | 1.10 | -2.1 | 0.177820E+10 | 2606.69 | 1.10 | -2.1 | ||
Maximum of Months | 0.331840E+11 | 53797.51 | 26.10 | 25.10 | 0.215935E+10 | 2606.69 | 29.43 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209215E+10 | 9359.02 | 01-JAN-14:09 | 25.83 | 18.00 | 0.00 | 0.00 | 01-JAN-00:10 | 25.83 | 18.00 |
February | 0.306291E+10 | 10672.42 | 24-FEB-14:40 | 26.07 | 21.03 | 0.00 | 0.00 | 01-FEB-00:10 | 26.07 | 21.03 |
March | 0.459791E+10 | 11167.26 | 29-MAR-14:20 | 25.73 | 21.24 | 0.00 | 0.00 | 01-MAR-00:10 | 25.73 | 21.24 |
April | 0.748187E+10 | 15733.73 | 28-APR-14:50 | 33.20 | 23.05 | 0.00 | 0.00 | 01-APR-00:10 | 33.20 | 23.05 |
May | 0.112715E+11 | 20424.13 | 28-MAY-14:41 | 33.22 | 22.75 | 0.00 | 0.00 | 01-MAY-00:10 | 33.22 | 22.75 |
June | 0.123811E+11 | 19206.00 | 25-JUN-14:51 | 32.20 | 24.61 | 0.00 | 0.00 | 01-JUN-00:10 | 32.20 | 24.61 |
July | 0.117232E+11 | 17781.19 | 07-JUL-14:30 | 34.45 | 24.41 | 0.00 | 0.00 | 01-JUL-00:10 | 34.45 | 24.41 |
August | 0.117372E+11 | 17035.03 | 03-AUG-14:30 | 34.40 | 25.23 | 0.00 | 0.00 | 01-AUG-00:10 | 34.40 | 25.23 |
September | 0.925137E+10 | 15719.32 | 01-SEP-13:30 | 31.90 | 22.99 | 0.00 | 0.00 | 01-SEP-00:10 | 31.90 | 22.99 |
October | 0.874087E+10 | 15333.99 | 13-OCT-14:00 | 33.00 | 23.24 | 0.00 | 0.00 | 01-OCT-00:10 | 33.00 | 23.24 |
November | 0.444909E+10 | 12359.28 | 02-NOV-13:40 | 29.60 | 24.43 | 0.00 | 0.00 | 01-NOV-00:10 | 29.60 | 24.43 |
December | 0.284173E+10 | 10576.24 | 15-DEC-14:40 | 29.00 | 21.74 | 0.00 | 0.00 | 01-DEC-00:10 | 29.00 | 21.74 |
Annual Sum or Average | 0.896309E+11 | 0.00 | ||||||||
Minimum of Months | 0.209215E+10 | 9359.02 | 25.73 | 18.00 | 0.00 | 0.00 | 25.73 | 18.00 | ||
Maximum of Months | 0.123811E+11 | 20424.13 | 34.45 | 25.23 | 0.00 | 0.00 | 34.45 | 25.23 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534424E+09 | 3910.25 | 03-JAN-06:10 | 2.83 | 0.47 | 0.00 | 0.00 | 01-JAN-00:10 | 2.83 | 0.47 |
February | 0.844265E+09 | 3195.07 | 28-FEB-20:53 | 19.40 | 18.28 | 0.00 | 0.00 | 01-FEB-00:10 | 19.40 | 18.28 |
March | 0.129216E+10 | 3402.48 | 01-MAR-06:55 | 15.60 | 14.18 | 0.00 | 0.00 | 01-MAR-00:10 | 15.60 | 14.18 |
April | 0.259942E+10 | 3884.61 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.483382E+10 | 4568.72 | 04-MAY-16:00 | 32.80 | 21.58 | 0.00 | 0.00 | 01-MAY-00:10 | 32.80 | 21.58 |
June | 0.503598E+10 | 4646.09 | 14-JUN-15:30 | 31.95 | 25.43 | 0.00 | 0.00 | 01-JUN-00:10 | 31.95 | 25.43 |
July | 0.507509E+10 | 5004.84 | 05-JUL-15:00 | 31.70 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 31.70 | 25.84 |
August | 0.522942E+10 | 4956.21 | 30-AUG-16:00 | 36.30 | 23.74 | 0.00 | 0.00 | 01-AUG-00:10 | 36.30 | 23.74 |
September | 0.438168E+10 | 4947.92 | 11-SEP-14:30 | 28.55 | 24.74 | 0.00 | 0.00 | 01-SEP-00:10 | 28.55 | 24.74 |
October | 0.405892E+10 | 5133.06 | 10-OCT-15:30 | 30.00 | 22.39 | 0.00 | 0.00 | 01-OCT-00:10 | 30.00 | 22.39 |
November | 0.164086E+10 | 3410.02 | 03-NOV-05:10 | 22.28 | 21.91 | 0.00 | 0.00 | 01-NOV-00:10 | 22.28 | 21.91 |
December | 0.952986E+09 | 3618.70 | 18-DEC-06:10 | 3.67 | 0.69 | 0.00 | 0.00 | 01-DEC-00:10 | 3.67 | 0.69 |
Annual Sum or Average | 0.364790E+11 | 0.00 | ||||||||
Minimum of Months | 0.534424E+09 | 3195.07 | 2.83 | 0.47 | 0.00 | 0.00 | 2.83 | 0.47 | ||
Maximum of Months | 0.522942E+10 | 5133.06 | 36.30 | 25.84 | 0.00 | 0.00 | 36.30 | 25.84 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854588E+09 | 3842.12 | 03-JAN-06:10 | 2.83 | 0.47 | 0.00 | 0.00 | 01-JAN-00:10 | 2.83 | 0.47 |
February | 0.123025E+10 | 3232.32 | 02-FEB-06:43 | 16.60 | 15.88 | 0.00 | 0.00 | 01-FEB-00:10 | 16.60 | 15.88 |
March | 0.170496E+10 | 3602.73 | 31-MAR-05:20 | 16.50 | 16.50 | 0.00 | 0.00 | 01-MAR-00:10 | 16.50 | 16.50 |
April | 0.309169E+10 | 4230.94 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.534200E+10 | 4888.49 | 04-MAY-16:00 | 32.80 | 21.58 | 0.00 | 0.00 | 01-MAY-00:10 | 32.80 | 21.58 |
June | 0.553326E+10 | 4920.39 | 28-JUN-16:00 | 33.30 | 25.14 | 0.00 | 0.00 | 01-JUN-00:10 | 33.30 | 25.14 |
July | 0.555593E+10 | 5315.49 | 05-JUL-15:00 | 31.70 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 31.70 | 25.84 |
August | 0.589178E+10 | 5517.72 | 30-AUG-16:00 | 36.30 | 23.74 | 0.00 | 0.00 | 01-AUG-00:10 | 36.30 | 23.74 |
September | 0.502448E+10 | 5303.23 | 11-SEP-14:05 | 29.25 | 25.12 | 0.00 | 0.00 | 01-SEP-00:10 | 29.25 | 25.12 |
October | 0.484315E+10 | 5664.15 | 10-OCT-14:05 | 30.83 | 22.61 | 0.00 | 0.00 | 01-OCT-00:10 | 30.83 | 22.61 |
November | 0.263782E+10 | 4169.21 | 02-NOV-15:30 | 29.10 | 23.88 | 0.00 | 0.00 | 01-NOV-00:10 | 29.10 | 23.88 |
December | 0.147231E+10 | 3610.35 | 15-DEC-16:20 | 28.00 | 21.24 | 0.00 | 0.00 | 01-DEC-00:10 | 28.00 | 21.24 |
Annual Sum or Average | 0.431822E+11 | 0.00 | ||||||||
Minimum of Months | 0.854588E+09 | 3232.32 | 2.83 | 0.47 | 0.00 | 0.00 | 2.83 | 0.47 | ||
Maximum of Months | 0.589178E+10 | 5664.15 | 36.30 | 25.84 | 0.00 | 0.00 | 36.30 | 25.84 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139455E+11 | 16164.30 | 02-JAN-17:00 | 26.00 | 18.38 | 0.179106E+10 | 2606.69 | 20-JAN-14:39 | 13.67 | 10.76 |
February | 0.130136E+11 | 15841.57 | 28-FEB-17:00 | 23.80 | 20.44 | 0.166041E+10 | 2606.69 | 03-FEB-14:00 | 23.80 | 20.44 |
March | 0.160576E+11 | 16387.66 | 30-MAR-16:00 | 25.50 | 21.27 | 0.202573E+10 | 2606.69 | 08-MAR-10:00 | 25.50 | 21.27 |
April | 0.169004E+11 | 18571.53 | 28-APR-16:00 | 32.20 | 25.55 | 0.187981E+10 | 2606.69 | 06-APR-09:39 | 32.20 | 25.55 |
May | 0.229118E+11 | 40743.36 | 26-MAY-04:01 | 25.00 | 23.72 | 0.206792E+10 | 2606.69 | 18-MAY-09:30 | 25.00 | 23.72 |
June | 0.232628E+11 | 41168.88 | 30-JUN-04:01 | 24.40 | 22.94 | 0.206302E+10 | 2606.69 | 01-JUN-13:00 | 24.40 | 22.94 |
July | 0.231129E+11 | 43750.06 | 05-JUL-04:02 | 25.68 | 24.39 | 0.191581E+10 | 2606.69 | 05-JUL-13:39 | 31.87 | 26.28 |
August | 0.241834E+11 | 41310.36 | 30-AUG-04:01 | 24.45 | 22.91 | 0.215217E+10 | 2606.69 | 02-AUG-13:50 | 24.45 | 22.91 |
September | 0.216195E+11 | 41105.21 | 06-SEP-04:01 | 24.55 | 23.26 | 0.190619E+10 | 2606.69 | 08-SEP-09:50 | 29.80 | 25.46 |
October | 0.209892E+11 | 40630.76 | 05-OCT-04:01 | 24.00 | 22.62 | 0.197561E+10 | 2606.69 | 25-OCT-09:30 | 25.50 | 24.80 |
November | 0.160316E+11 | 18138.97 | 03-NOV-16:00 | 27.20 | 24.31 | 0.190429E+10 | 2606.69 | 03-NOV-09:30 | 27.20 | 24.31 |
December | 0.145455E+11 | 16988.90 | 15-DEC-17:00 | 28.00 | 21.24 | 0.177048E+10 | 2606.69 | 12-DEC-14:09 | 28.00 | 21.24 |
Annual Sum or Average | 0.226574E+12 | 0.231125E+11 | ||||||||
Minimum of Months | 0.130136E+11 | 15841.57 | 23.80 | 18.38 | 0.166041E+10 | 2606.69 | 13.67 | 10.76 | ||
Maximum of Months | 0.241834E+11 | 43750.06 | 32.20 | 25.55 | 0.215217E+10 | 2606.69 | 32.20 | 26.28 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137807E+11 | 16470.71 | 19-JAN-16:20 | 24.67 | 20.76 | 0.167132E+10 | 2606.69 | 02-JAN-14:00 | 24.67 | 20.76 |
February | 0.136778E+11 | 17328.02 | 24-FEB-16:20 | 25.13 | 21.19 | 0.157293E+10 | 2606.69 | 28-FEB-14:00 | 25.00 | 20.38 |
March | 0.173472E+11 | 18962.88 | 29-MAR-15:50 | 26.70 | 21.22 | 0.192231E+10 | 2606.69 | 07-MAR-14:09 | 26.70 | 21.22 |
April | 0.192306E+11 | 23220.69 | 28-APR-15:40 | 32.57 | 24.79 | 0.182206E+10 | 2606.69 | 25-APR-13:00 | 32.57 | 24.79 |
May | 0.261840E+11 | 48858.47 | 08-MAY-04:01 | 24.32 | 22.06 | 0.205800E+10 | 2606.69 | 02-MAY-13:09 | 24.32 | 22.06 |
June | 0.269619E+11 | 48709.80 | 14-JUN-04:01 | 25.00 | 22.70 | 0.205449E+10 | 2606.69 | 07-JUN-13:30 | 25.00 | 22.70 |
July | 0.265747E+11 | 49000.61 | 11-JUL-04:01 | 24.60 | 23.70 | 0.190913E+10 | 2606.69 | 03-JUL-09:39 | 24.60 | 23.70 |
August | 0.272978E+11 | 49162.57 | 25-AUG-04:01 | 24.28 | 22.05 | 0.214244E+10 | 2606.69 | 02-AUG-09:39 | 24.28 | 22.05 |
September | 0.238511E+11 | 48879.52 | 11-SEP-04:01 | 24.83 | 23.63 | 0.189106E+10 | 2606.69 | 01-SEP-13:30 | 24.83 | 23.63 |
October | 0.228247E+11 | 48334.35 | 06-OCT-04:01 | 25.10 | 25.10 | 0.194191E+10 | 2606.69 | 25-OCT-09:30 | 25.50 | 24.80 |
November | 0.170119E+11 | 20683.46 | 02-NOV-15:20 | 29.20 | 23.96 | 0.180290E+10 | 2606.69 | 02-NOV-13:20 | 29.20 | 23.96 |
December | 0.147294E+11 | 18658.56 | 15-DEC-15:50 | 28.17 | 21.30 | 0.164800E+10 | 2606.69 | 15-DEC-14:50 | 28.17 | 21.30 |
Annual Sum or Average | 0.249472E+12 | 0.224365E+11 | ||||||||
Minimum of Months | 0.136778E+11 | 16470.71 | 24.28 | 20.76 | 0.157293E+10 | 2606.69 | 24.28 | 20.38 | ||
Maximum of Months | 0.272978E+11 | 49162.57 | 32.57 | 25.10 | 0.214244E+10 | 2606.69 | 32.57 | 24.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243263E+10 | 4178.48 | 01-JAN-14:41 | 25.17 | 18.45 | 0.328798E+09 | 549.06 | 02-JAN-14:20 | 26.33 | 18.48 |
February | 0.298064E+10 | 4718.91 | 24-FEB-14:30 | 26.35 | 21.12 | 0.310549E+09 | 549.51 | 24-FEB-14:00 | 25.50 | 20.83 |
March | 0.412254E+10 | 6368.83 | 30-MAR-13:10 | 29.12 | 22.70 | 0.378473E+09 | 549.51 | 07-MAR-14:20 | 29.12 | 22.70 |
April | 0.558442E+10 | 8128.30 | 28-APR-15:00 | 33.30 | 23.06 | 0.368373E+09 | 549.51 | 21-APR-13:00 | 33.30 | 23.06 |
May | 0.866208E+10 | 15724.24 | 07-MAY-14:52 | 32.80 | 23.10 | 0.432565E+09 | 549.51 | 09-MAY-13:39 | 31.87 | 22.15 |
June | 0.935668E+10 | 16590.46 | 25-JUN-14:51 | 32.20 | 24.61 | 0.432773E+09 | 549.51 | 01-JUN-13:00 | 32.20 | 24.61 |
July | 0.912685E+10 | 14744.18 | 24-JUL-04:01 | 26.28 | 24.56 | 0.402496E+09 | 549.51 | 06-JUL-09:39 | 26.28 | 24.56 |
August | 0.912942E+10 | 13632.79 | 28-AUG-05:01 | 25.67 | 23.79 | 0.449329E+09 | 549.51 | 25-AUG-13:30 | 25.67 | 23.79 |
September | 0.750364E+10 | 15130.77 | 10-SEP-15:51 | 34.30 | 26.98 | 0.394084E+09 | 549.51 | 08-SEP-13:20 | 34.30 | 26.98 |
October | 0.689392E+10 | 12112.90 | 23-OCT-05:01 | 24.50 | 23.88 | 0.398227E+09 | 549.51 | 03-OCT-13:09 | 24.50 | 23.88 |
November | 0.429069E+10 | 6363.85 | 02-NOV-13:50 | 29.50 | 24.45 | 0.355451E+09 | 549.51 | 02-NOV-13:00 | 29.40 | 24.47 |
December | 0.296748E+10 | 5458.91 | 15-DEC-15:00 | 29.00 | 21.56 | 0.324540E+09 | 549.51 | 15-DEC-14:39 | 29.00 | 21.56 |
Annual Sum or Average | 0.730510E+11 | 0.457566E+10 | ||||||||
Minimum of Months | 0.243263E+10 | 4178.48 | 24.50 | 18.45 | 0.310549E+09 | 549.06 | 24.50 | 18.48 | ||
Maximum of Months | 0.935668E+10 | 16590.46 | 34.30 | 26.98 | 0.449329E+09 | 549.51 | 34.30 | 26.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252249E+10 | 4741.77 | 19-JAN-10:30 | 23.85 | 21.17 | 0.206754E+09 | 347.89 | 19-JAN-10:00 | 24.70 | 21.41 |
February | 0.285168E+10 | 5124.91 | 26-FEB-10:18 | 22.00 | 19.48 | 0.198886E+09 | 347.89 | 24-FEB-10:00 | 22.00 | 19.48 |
March | 0.391480E+10 | 7719.02 | 26-MAR-10:08 | 25.78 | 20.21 | 0.246263E+09 | 347.89 | 07-MAR-14:09 | 25.78 | 20.21 |
April | 0.515598E+10 | 7057.14 | 28-APR-10:20 | 28.47 | 23.32 | 0.238024E+09 | 347.89 | 11-APR-09:00 | 28.47 | 23.32 |
May | 0.750539E+10 | 16543.89 | 29-MAY-09:32 | 28.53 | 23.16 | 0.271900E+09 | 347.89 | 16-MAY-13:39 | 28.53 | 23.16 |
June | 0.787192E+10 | 12253.22 | 04-JUN-10:22 | 30.00 | 23.98 | 0.272412E+09 | 347.89 | 06-JUN-13:50 | 26.78 | 21.73 |
July | 0.777417E+10 | 16546.91 | 23-JUL-10:22 | 30.85 | 26.12 | 0.252116E+09 | 347.89 | 06-JUL-13:09 | 30.85 | 26.12 |
August | 0.764341E+10 | 10547.65 | 28-AUG-04:01 | 26.08 | 23.84 | 0.281425E+09 | 347.89 | 25-AUG-13:30 | 26.08 | 23.84 |
September | 0.642732E+10 | 16725.57 | 10-SEP-09:52 | 33.70 | 27.42 | 0.245821E+09 | 347.89 | 01-SEP-13:09 | 33.70 | 27.42 |
October | 0.606544E+10 | 8590.32 | 09-OCT-07:53 | 25.00 | 21.55 | 0.250810E+09 | 347.89 | 02-OCT-13:09 | 25.00 | 21.55 |
November | 0.392707E+10 | 6272.65 | 02-NOV-10:00 | 27.70 | 24.03 | 0.224815E+09 | 347.89 | 07-NOV-14:50 | 27.80 | 24.07 |
December | 0.277138E+10 | 4562.59 | 10-DEC-09:58 | 24.00 | 19.93 | 0.202710E+09 | 338.92 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.644310E+11 | 0.289194E+10 | ||||||||
Minimum of Months | 0.252249E+10 | 4562.59 | 22.00 | 19.48 | 0.198886E+09 | 338.92 | 22.00 | 19.48 | ||
Maximum of Months | 0.787192E+10 | 16725.57 | 33.70 | 27.42 | 0.281425E+09 | 347.89 | 33.70 | 27.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534957E+10 | 23573.72 | 01-JAN-14:01 | 25.83 | 18.00 | 0.369887E+09 | 549.51 | 23-JAN-14:39 | 14.33 | 8.33 |
February | 0.554240E+10 | 12466.77 | 24-FEB-14:00 | 27.20 | 21.39 | 0.339085E+09 | 549.51 | 02-FEB-14:09 | 27.20 | 21.39 |
March | 0.594321E+10 | 19776.11 | 26-MAR-13:52 | 30.00 | 19.88 | 0.397051E+09 | 549.51 | 06-MAR-14:30 | 30.00 | 19.88 |
April | 0.698345E+10 | 11568.48 | 23-APR-14:31 | 28.43 | 21.38 | 0.368244E+09 | 549.51 | 05-APR-13:00 | 28.43 | 21.38 |
May | 0.929696E+10 | 17076.78 | 07-MAY-14:52 | 32.80 | 23.10 | 0.426551E+09 | 549.51 | 01-MAY-13:09 | 32.80 | 23.10 |
June | 0.953673E+10 | 15892.37 | 25-JUN-14:51 | 32.20 | 24.61 | 0.427114E+09 | 549.51 | 05-JUN-13:50 | 32.20 | 24.61 |
July | 0.953903E+10 | 17435.34 | 24-JUL-04:01 | 26.28 | 24.56 | 0.397688E+09 | 549.51 | 06-JUL-13:09 | 26.28 | 24.56 |
August | 0.103672E+11 | 15435.94 | 28-AUG-04:01 | 26.08 | 23.84 | 0.444831E+09 | 549.51 | 25-AUG-13:30 | 26.08 | 23.84 |
September | 0.941719E+10 | 21205.27 | 10-SEP-13:52 | 35.80 | 27.24 | 0.391129E+09 | 549.51 | 05-SEP-13:20 | 35.80 | 27.24 |
October | 0.103422E+11 | 22250.93 | 01-OCT-13:32 | 27.73 | 18.51 | 0.403361E+09 | 549.51 | 10-OCT-13:09 | 31.00 | 22.17 |
November | 0.762586E+10 | 21820.56 | 05-NOV-13:22 | 27.20 | 20.74 | 0.386996E+09 | 549.51 | 09-NOV-14:09 | 21.10 | 11.54 |
December | 0.616424E+10 | 23041.03 | 10-DEC-13:11 | 27.00 | 20.22 | 0.358173E+09 | 549.51 | 26-DEC-14:09 | 13.72 | 5.48 |
Annual Sum or Average | 0.961080E+11 | 0.471011E+10 | ||||||||
Minimum of Months | 0.534957E+10 | 11568.48 | 25.83 | 18.00 | 0.339085E+09 | 549.51 | 13.72 | 5.48 | ||
Maximum of Months | 0.103672E+11 | 23573.72 | 35.80 | 27.24 | 0.444831E+09 | 549.51 | 35.80 | 27.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261013E+10 | 6215.80 | 19-JAN-16:00 | 25.00 | 20.82 | 0.208031E+09 | 347.78 | 19-JAN-14:00 | 25.00 | 20.82 |
February | 0.299278E+10 | 7441.67 | 27-FEB-16:30 | 24.95 | 20.41 | 0.194770E+09 | 347.86 | 24-FEB-14:00 | 24.95 | 20.41 |
March | 0.393217E+10 | 7528.89 | 06-MAR-16:30 | 25.55 | 21.32 | 0.234425E+09 | 347.86 | 06-MAR-14:00 | 25.55 | 21.32 |
April | 0.551397E+10 | 13421.79 | 16-APR-16:22 | 20.25 | 13.37 | 0.220618E+09 | 347.86 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.747090E+10 | 19076.44 | 28-MAY-16:01 | 33.43 | 24.55 | 0.261217E+09 | 347.86 | 01-MAY-13:50 | 33.43 | 24.55 |
June | 0.781193E+10 | 18821.58 | 11-JUN-16:42 | 33.12 | 21.82 | 0.263345E+09 | 347.86 | 02-JUN-13:20 | 33.12 | 21.82 |
July | 0.759423E+10 | 18682.91 | 16-JUL-15:11 | 31.70 | 25.48 | 0.244068E+09 | 347.86 | 05-JUL-13:30 | 31.70 | 25.48 |
August | 0.783637E+10 | 11313.09 | 30-AUG-16:00 | 36.30 | 23.74 | 0.272906E+09 | 347.86 | 28-AUG-13:30 | 36.30 | 23.74 |
September | 0.677548E+10 | 19066.01 | 10-SEP-15:51 | 34.30 | 26.98 | 0.235644E+09 | 347.86 | 01-SEP-13:00 | 34.30 | 26.98 |
October | 0.646270E+10 | 17178.95 | 08-OCT-16:02 | 30.67 | 25.13 | 0.240061E+09 | 347.86 | 05-OCT-13:00 | 30.67 | 25.13 |
November | 0.411330E+10 | 8055.51 | 06-NOV-16:00 | 28.30 | 20.26 | 0.219563E+09 | 347.86 | 07-NOV-14:00 | 27.70 | 24.03 |
December | 0.300989E+10 | 8148.06 | 10-DEC-15:52 | 27.00 | 20.22 | 0.204645E+09 | 347.86 | 15-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.661238E+11 | 0.279929E+10 | ||||||||
Minimum of Months | 0.261013E+10 | 6215.80 | 20.25 | 13.37 | 0.194770E+09 | 347.78 | 24.95 | 20.41 | ||
Maximum of Months | 0.783637E+10 | 19076.44 | 36.30 | 26.98 | 0.272906E+09 | 347.86 | 36.30 | 26.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251233E+10 | 3691.02 | 02-JAN-13:20 | 26.00 | 18.72 | 0.337727E+09 | 549.51 | 02-JAN-14:00 | 27.00 | 18.67 |
February | 0.271171E+10 | 3535.19 | 02-FEB-14:30 | 26.90 | 20.87 | 0.315562E+09 | 549.51 | 24-FEB-14:50 | 25.78 | 20.93 |
March | 0.359313E+10 | 4963.74 | 30-MAR-13:10 | 29.12 | 22.70 | 0.383103E+09 | 549.51 | 28-MAR-13:50 | 29.12 | 22.70 |
April | 0.445463E+10 | 6071.01 | 28-APR-15:00 | 33.30 | 23.06 | 0.373118E+09 | 549.51 | 21-APR-13:39 | 33.30 | 23.06 |
May | 0.724045E+10 | 8437.37 | 31-MAY-05:01 | 23.80 | 21.58 | 0.435068E+09 | 549.51 | 24-MAY-09:09 | 23.80 | 21.58 |
June | 0.800524E+10 | 9778.04 | 05-JUN-04:01 | 25.22 | 22.37 | 0.434743E+09 | 549.51 | 01-JUN-13:00 | 25.22 | 22.37 |
July | 0.821152E+10 | 11673.85 | 07-JUL-04:01 | 25.50 | 23.88 | 0.404637E+09 | 549.51 | 11-JUL-09:09 | 30.18 | 26.62 |
August | 0.870358E+10 | 11193.15 | 24-AUG-04:01 | 25.27 | 23.85 | 0.454194E+09 | 549.51 | 25-AUG-13:30 | 28.00 | 24.39 |
September | 0.720297E+10 | 10465.08 | 12-SEP-04:01 | 26.05 | 23.40 | 0.402168E+09 | 549.51 | 08-SEP-09:09 | 26.05 | 23.40 |
October | 0.663666E+10 | 10219.54 | 06-OCT-04:01 | 25.10 | 25.10 | 0.411818E+09 | 549.51 | 16-OCT-09:20 | 26.00 | 22.47 |
November | 0.431694E+10 | 5816.56 | 03-NOV-14:00 | 29.40 | 23.47 | 0.375133E+09 | 549.51 | 01-NOV-13:30 | 29.40 | 23.47 |
December | 0.317103E+10 | 4914.91 | 15-DEC-14:10 | 29.00 | 22.01 | 0.337384E+09 | 549.51 | 11-DEC-14:20 | 29.00 | 22.01 |
Annual Sum or Average | 0.667602E+11 | 0.466465E+10 | ||||||||
Minimum of Months | 0.251233E+10 | 3535.19 | 23.80 | 18.72 | 0.315562E+09 | 549.51 | 23.80 | 18.67 | ||
Maximum of Months | 0.870358E+10 | 11673.85 | 33.30 | 25.10 | 0.454194E+09 | 549.51 | 33.30 | 26.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285880E+10 | 4438.75 | 19-JAN-10:20 | 23.57 | 21.08 | 0.211879E+09 | 347.89 | 19-JAN-10:00 | 24.70 | 21.41 |
February | 0.291419E+10 | 4881.09 | 26-FEB-10:17 | 22.00 | 19.48 | 0.199421E+09 | 347.89 | 24-FEB-10:00 | 22.00 | 19.48 |
March | 0.378346E+10 | 6474.58 | 26-MAR-09:15 | 24.03 | 19.81 | 0.246134E+09 | 347.89 | 30-MAR-13:20 | 28.83 | 22.63 |
April | 0.466785E+10 | 14959.16 | 23-APR-09:42 | 25.82 | 20.99 | 0.237046E+09 | 347.89 | 11-APR-09:00 | 25.82 | 20.99 |
May | 0.675270E+10 | 15603.22 | 14-MAY-08:51 | 28.30 | 23.49 | 0.272414E+09 | 347.89 | 25-MAY-13:00 | 32.80 | 24.32 |
June | 0.709673E+10 | 7956.45 | 19-JUN-10:00 | 30.60 | 25.72 | 0.273203E+09 | 347.89 | 02-JUN-13:30 | 30.60 | 25.72 |
July | 0.728486E+10 | 15133.76 | 23-JUL-09:42 | 30.82 | 26.39 | 0.253520E+09 | 347.89 | 25-JUL-13:39 | 32.20 | 26.10 |
August | 0.747354E+10 | 15208.42 | 06-AUG-11:02 | 31.00 | 26.42 | 0.284634E+09 | 347.89 | 25-AUG-13:30 | 28.00 | 24.39 |
September | 0.637377E+10 | 16561.76 | 03-SEP-09:21 | 29.95 | 24.47 | 0.251009E+09 | 347.89 | 12-SEP-13:39 | 31.60 | 24.10 |
October | 0.619766E+10 | 11293.67 | 15-OCT-09:42 | 24.67 | 20.62 | 0.256324E+09 | 347.89 | 25-OCT-09:30 | 25.50 | 24.80 |
November | 0.431778E+10 | 7224.77 | 11-NOV-09:33 | 24.40 | 21.68 | 0.234116E+09 | 347.89 | 02-NOV-13:30 | 24.40 | 21.68 |
December | 0.315699E+10 | 4389.84 | 17-DEC-09:32 | 19.00 | 14.29 | 0.209270E+09 | 333.53 | 15-DEC-14:20 | 19.00 | 14.29 |
Annual Sum or Average | 0.628783E+11 | 0.292897E+10 | ||||||||
Minimum of Months | 0.285880E+10 | 4389.84 | 19.00 | 14.29 | 0.199421E+09 | 333.53 | 19.00 | 14.29 | ||
Maximum of Months | 0.747354E+10 | 16561.76 | 31.00 | 26.42 | 0.284634E+09 | 347.89 | 32.80 | 26.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479496E+10 | 18292.92 | 16-JAN-15:02 | 26.67 | 18.55 | 0.371445E+09 | 549.51 | 23-JAN-14:39 | 14.33 | 8.33 |
February | 0.487096E+10 | 14399.74 | 26-FEB-14:12 | 26.43 | 19.86 | 0.339086E+09 | 549.51 | 24-FEB-14:09 | 26.43 | 19.86 |
March | 0.500919E+10 | 11805.22 | 28-MAR-12:00 | 27.70 | 22.63 | 0.397186E+09 | 549.51 | 07-MAR-14:09 | 27.70 | 22.63 |
April | 0.616247E+10 | 14622.48 | 28-APR-12:00 | 31.10 | 23.31 | 0.372190E+09 | 556.05 | 28-APR-12:09 | 31.28 | 23.24 |
May | 0.958656E+10 | 14952.12 | 19-MAY-12:00 | 32.20 | 23.63 | 0.433036E+09 | 569.24 | 19-MAY-12:09 | 32.30 | 23.64 |
June | 0.101218E+11 | 15113.63 | 28-JUN-12:00 | 32.80 | 25.51 | 0.433324E+09 | 574.86 | 28-JUN-12:09 | 32.80 | 25.64 |
July | 0.102376E+11 | 16012.36 | 21-JUL-16:10 | 35.45 | 25.77 | 0.404696E+09 | 604.08 | 20-JUL-12:09 | 35.45 | 25.77 |
August | 0.117886E+11 | 16700.24 | 30-AUG-16:10 | 36.07 | 23.60 | 0.455220E+09 | 601.13 | 10-AUG-12:09 | 36.07 | 23.60 |
September | 0.102184E+11 | 18173.18 | 24-SEP-13:32 | 31.43 | 25.12 | 0.402088E+09 | 598.05 | 01-SEP-12:09 | 31.43 | 25.12 |
October | 0.113596E+11 | 19130.65 | 15-OCT-12:22 | 28.50 | 21.92 | 0.415249E+09 | 619.06 | 06-OCT-12:09 | 28.50 | 21.92 |
November | 0.789229E+10 | 18946.27 | 05-NOV-13:52 | 27.20 | 20.73 | 0.399062E+09 | 588.76 | 02-NOV-12:09 | 27.20 | 20.73 |
December | 0.612934E+10 | 19746.19 | 10-DEC-13:11 | 27.00 | 20.22 | 0.364081E+09 | 563.38 | 15-DEC-13:09 | 28.17 | 22.92 |
Annual Sum or Average | 0.981718E+11 | 0.478666E+10 | ||||||||
Minimum of Months | 0.479496E+10 | 11805.22 | 26.43 | 18.55 | 0.339086E+09 | 549.51 | 14.33 | 8.33 | ||
Maximum of Months | 0.117886E+11 | 19746.19 | 36.07 | 25.77 | 0.455220E+09 | 619.06 | 36.07 | 25.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284595E+10 | 5202.90 | 31-JAN-16:40 | 23.67 | 21.13 | 0.212807E+09 | 347.77 | 19-JAN-14:00 | 23.67 | 21.13 |
February | 0.296633E+10 | 9387.22 | 26-FEB-17:32 | 23.67 | 19.48 | 0.197093E+09 | 347.86 | 27-FEB-14:00 | 26.10 | 20.43 |
March | 0.368866E+10 | 6020.38 | 26-MAR-15:28 | 24.95 | 19.97 | 0.236081E+09 | 347.85 | 06-MAR-14:00 | 24.95 | 19.97 |
April | 0.482745E+10 | 9372.94 | 29-APR-17:07 | 28.53 | 23.28 | 0.222954E+09 | 347.86 | 28-APR-13:00 | 28.53 | 23.28 |
May | 0.645139E+10 | 15783.48 | 29-MAY-16:12 | 32.07 | 23.52 | 0.265230E+09 | 347.86 | 04-MAY-13:00 | 32.07 | 23.52 |
June | 0.680727E+10 | 15912.74 | 11-JUN-16:42 | 33.12 | 21.82 | 0.268000E+09 | 347.86 | 12-JUN-13:39 | 32.03 | 20.64 |
July | 0.683384E+10 | 11006.17 | 22-JUL-17:06 | 34.63 | 26.60 | 0.249734E+09 | 347.86 | 05-JUL-13:30 | 34.63 | 26.60 |
August | 0.739138E+10 | 10032.03 | 30-AUG-16:00 | 36.30 | 23.74 | 0.282028E+09 | 347.86 | 18-AUG-13:30 | 36.30 | 23.74 |
September | 0.643498E+10 | 16397.88 | 17-SEP-15:31 | 32.00 | 25.62 | 0.247076E+09 | 347.86 | 06-SEP-13:09 | 32.00 | 25.62 |
October | 0.633350E+10 | 15797.80 | 01-OCT-16:22 | 27.35 | 18.21 | 0.251648E+09 | 347.86 | 04-OCT-13:39 | 31.00 | 23.41 |
November | 0.444029E+10 | 9799.56 | 05-NOV-15:52 | 27.20 | 19.54 | 0.228216E+09 | 347.86 | 07-NOV-14:00 | 27.70 | 24.03 |
December | 0.337080E+10 | 6455.52 | 15-DEC-16:00 | 28.00 | 21.24 | 0.211170E+09 | 347.86 | 15-DEC-14:00 | 28.00 | 21.24 |
Annual Sum or Average | 0.623918E+11 | 0.287204E+10 | ||||||||
Minimum of Months | 0.284595E+10 | 5202.90 | 23.67 | 18.21 | 0.197093E+09 | 347.77 | 23.67 | 19.97 | ||
Maximum of Months | 0.739138E+10 | 16397.88 | 36.30 | 26.60 | 0.282028E+09 | 347.86 | 36.30 | 26.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246789E+10 | 4290.35 | 02-JAN-13:30 | 26.00 | 18.64 | 0.337456E+09 | 549.51 | 02-JAN-14:50 | 26.83 | 18.62 |
February | 0.287023E+10 | 4285.17 | 28-FEB-15:00 | 25.00 | 20.38 | 0.319658E+09 | 549.51 | 24-FEB-14:00 | 25.00 | 20.38 |
March | 0.389470E+10 | 5974.23 | 30-MAR-13:10 | 29.12 | 22.70 | 0.389800E+09 | 549.51 | 07-MAR-14:09 | 29.12 | 22.70 |
April | 0.494692E+10 | 7063.47 | 28-APR-15:00 | 33.30 | 23.06 | 0.380214E+09 | 549.51 | 13-APR-13:20 | 33.30 | 23.06 |
May | 0.781053E+10 | 11046.99 | 30-MAY-04:01 | 25.60 | 23.97 | 0.435631E+09 | 549.51 | 24-MAY-09:09 | 25.60 | 23.97 |
June | 0.842465E+10 | 12044.29 | 26-JUN-04:01 | 25.00 | 23.68 | 0.434957E+09 | 549.51 | 01-JUN-13:00 | 25.00 | 23.68 |
July | 0.822002E+10 | 11658.66 | 07-JUL-04:01 | 25.50 | 23.88 | 0.404492E+09 | 549.51 | 11-JUL-09:09 | 30.18 | 26.62 |
August | 0.830516E+10 | 11288.14 | 28-AUG-05:01 | 25.67 | 23.79 | 0.452949E+09 | 549.51 | 25-AUG-13:30 | 25.67 | 23.79 |
September | 0.681674E+10 | 10536.34 | 11-SEP-05:01 | 25.42 | 23.91 | 0.400071E+09 | 549.51 | 07-SEP-09:09 | 25.42 | 23.91 |
October | 0.633153E+10 | 10232.02 | 06-OCT-05:01 | 25.67 | 25.67 | 0.407964E+09 | 549.51 | 16-OCT-09:20 | 26.00 | 22.47 |
November | 0.414045E+10 | 5831.64 | 03-NOV-14:00 | 29.40 | 23.47 | 0.370977E+09 | 549.51 | 01-NOV-13:09 | 29.40 | 23.47 |
December | 0.300661E+10 | 5022.21 | 15-DEC-14:10 | 29.00 | 22.01 | 0.334296E+09 | 549.51 | 13-DEC-14:00 | 29.00 | 22.01 |
Annual Sum or Average | 0.672354E+11 | 0.466847E+10 | ||||||||
Minimum of Months | 0.246789E+10 | 4285.17 | 25.00 | 18.64 | 0.319658E+09 | 549.51 | 25.00 | 18.62 | ||
Maximum of Months | 0.842465E+10 | 12044.29 | 33.30 | 25.67 | 0.452949E+09 | 549.51 | 33.30 | 26.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275782E+10 | 5763.01 | 19-JAN-11:05 | 24.92 | 21.49 | 0.153268E+09 | 354.26 | 19-JAN-11:09 | 24.92 | 21.49 |
February | 0.300884E+10 | 5778.95 | 26-FEB-10:27 | 22.75 | 19.68 | 0.145972E+09 | 354.09 | 27-FEB-11:09 | 22.80 | 19.34 |
March | 0.398608E+10 | 7208.71 | 26-MAR-09:13 | 24.03 | 19.81 | 0.180371E+09 | 356.46 | 06-MAR-11:09 | 24.03 | 19.81 |
April | 0.499146E+10 | 16217.71 | 23-APR-09:42 | 25.82 | 20.99 | 0.174817E+09 | 356.46 | 28-APR-12:09 | 31.28 | 23.24 |
May | 0.698991E+10 | 17594.25 | 29-MAY-08:41 | 27.62 | 23.19 | 0.201149E+09 | 356.46 | 05-MAY-12:09 | 27.62 | 23.19 |
June | 0.724630E+10 | 11078.97 | 04-JUN-10:22 | 30.00 | 23.98 | 0.201371E+09 | 356.46 | 22-JUN-12:09 | 31.20 | 23.98 |
July | 0.719771E+10 | 15981.01 | 23-JUL-09:42 | 30.82 | 26.39 | 0.186753E+09 | 356.46 | 10-JUL-12:09 | 30.82 | 26.39 |
August | 0.711283E+10 | 9640.43 | 28-AUG-04:01 | 26.08 | 23.84 | 0.207754E+09 | 356.46 | 03-AUG-12:09 | 26.08 | 23.84 |
September | 0.608263E+10 | 16549.87 | 24-SEP-09:42 | 29.22 | 24.98 | 0.181903E+09 | 356.46 | 01-SEP-12:09 | 29.22 | 24.98 |
October | 0.586762E+10 | 16109.83 | 09-OCT-10:22 | 29.50 | 22.78 | 0.185591E+09 | 356.46 | 10-OCT-12:09 | 30.17 | 21.88 |
November | 0.407050E+10 | 7509.31 | 02-NOV-10:05 | 27.88 | 24.05 | 0.167395E+09 | 356.46 | 06-NOV-11:09 | 25.60 | 20.32 |
December | 0.301206E+10 | 4623.83 | 17-DEC-10:02 | 19.17 | 14.29 | 0.150659E+09 | 322.98 | 15-DEC-13:00 | 19.17 | 14.29 |
Annual Sum or Average | 0.623238E+11 | 0.213700E+10 | ||||||||
Minimum of Months | 0.275782E+10 | 4623.83 | 19.17 | 14.29 | 0.145972E+09 | 322.98 | 19.17 | 14.29 | ||
Maximum of Months | 0.724630E+10 | 17594.25 | 30.82 | 26.39 | 0.207754E+09 | 356.46 | 31.28 | 26.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.551837E+10 | 20411.30 | 01-JAN-14:01 | 25.83 | 18.00 | 0.381740E+09 | 549.51 | 23-JAN-14:09 | 14.83 | 8.55 |
February | 0.554534E+10 | 12370.85 | 26-FEB-13:43 | 26.52 | 19.51 | 0.348201E+09 | 549.51 | 09-FEB-14:09 | 26.52 | 19.51 |
March | 0.580828E+10 | 9846.67 | 26-MAR-15:25 | 24.95 | 19.97 | 0.407271E+09 | 549.51 | 14-MAR-13:09 | 24.95 | 19.97 |
April | 0.643890E+10 | 9745.58 | 23-APR-13:12 | 27.37 | 21.04 | 0.378059E+09 | 549.51 | 20-APR-13:50 | 27.37 | 21.04 |
May | 0.840814E+10 | 11388.89 | 28-MAY-13:20 | 32.40 | 23.53 | 0.431779E+09 | 549.51 | 25-MAY-13:09 | 32.40 | 23.53 |
June | 0.855636E+10 | 12097.94 | 29-JUN-04:01 | 25.50 | 24.67 | 0.431504E+09 | 549.51 | 05-JUN-13:20 | 25.50 | 24.67 |
July | 0.859170E+10 | 13821.16 | 24-JUL-04:01 | 26.28 | 24.56 | 0.401444E+09 | 549.51 | 07-JUL-13:39 | 26.28 | 24.56 |
August | 0.952444E+10 | 12964.59 | 22-AUG-04:01 | 25.67 | 24.57 | 0.449824E+09 | 549.51 | 25-AUG-13:30 | 28.00 | 24.39 |
September | 0.874806E+10 | 18320.91 | 10-SEP-13:52 | 35.80 | 27.24 | 0.397574E+09 | 549.51 | 01-SEP-13:50 | 35.80 | 27.24 |
October | 0.990483E+10 | 20022.21 | 09-OCT-11:41 | 30.83 | 23.19 | 0.410514E+09 | 549.51 | 25-OCT-09:30 | 25.50 | 24.80 |
November | 0.771979E+10 | 17968.70 | 11-NOV-13:32 | 26.27 | 22.81 | 0.397045E+09 | 549.55 | 06-NOV-14:09 | 26.27 | 22.81 |
December | 0.639036E+10 | 18676.82 | 17-DEC-13:22 | 19.00 | 12.64 | 0.368382E+09 | 549.51 | 12-DEC-14:09 | 19.00 | 12.64 |
Annual Sum or Average | 0.911546E+11 | 0.480334E+10 | ||||||||
Minimum of Months | 0.551837E+10 | 9745.58 | 19.00 | 12.64 | 0.348201E+09 | 549.51 | 14.83 | 8.55 | ||
Maximum of Months | 0.990483E+10 | 20411.30 | 35.80 | 27.24 | 0.449824E+09 | 549.55 | 35.80 | 27.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276231E+10 | 5933.61 | 31-JAN-16:30 | 24.00 | 21.24 | 0.210784E+09 | 347.85 | 19-JAN-14:00 | 24.00 | 21.24 |
February | 0.309072E+10 | 7088.85 | 27-FEB-16:30 | 24.95 | 20.41 | 0.196727E+09 | 347.86 | 24-FEB-14:00 | 24.95 | 20.41 |
March | 0.396761E+10 | 7078.86 | 06-MAR-16:30 | 25.55 | 21.32 | 0.236967E+09 | 347.86 | 06-MAR-14:00 | 25.55 | 21.32 |
April | 0.527208E+10 | 10885.93 | 29-APR-17:06 | 28.53 | 23.28 | 0.224446E+09 | 347.86 | 28-APR-13:00 | 28.53 | 23.28 |
May | 0.688482E+10 | 18709.27 | 29-MAY-16:41 | 30.97 | 23.75 | 0.265566E+09 | 347.86 | 09-MAY-13:50 | 30.97 | 23.75 |
June | 0.716929E+10 | 16869.12 | 25-JUN-16:11 | 32.60 | 24.55 | 0.267045E+09 | 347.86 | 14-JUN-13:00 | 32.60 | 24.55 |
July | 0.696331E+10 | 16706.21 | 16-JUL-15:11 | 31.70 | 25.48 | 0.247706E+09 | 347.86 | 05-JUL-13:30 | 31.70 | 25.48 |
August | 0.727784E+10 | 10667.65 | 30-AUG-16:00 | 36.30 | 23.74 | 0.277281E+09 | 347.86 | 11-AUG-13:30 | 36.30 | 23.74 |
September | 0.631340E+10 | 17327.18 | 17-SEP-15:31 | 32.00 | 25.62 | 0.241240E+09 | 347.86 | 01-SEP-13:00 | 32.00 | 25.62 |
October | 0.618622E+10 | 16486.09 | 09-OCT-14:21 | 30.00 | 23.21 | 0.245325E+09 | 347.86 | 05-OCT-13:20 | 30.00 | 23.21 |
November | 0.423118E+10 | 7774.54 | 06-NOV-16:00 | 28.30 | 20.26 | 0.224169E+09 | 347.86 | 07-NOV-14:00 | 27.70 | 24.03 |
December | 0.319514E+10 | 7015.02 | 15-DEC-15:40 | 28.33 | 21.35 | 0.208097E+09 | 347.86 | 15-DEC-14:00 | 28.33 | 21.35 |
Annual Sum or Average | 0.633139E+11 | 0.284535E+10 | ||||||||
Minimum of Months | 0.276231E+10 | 5933.61 | 24.00 | 20.26 | 0.196727E+09 | 347.85 | 24.00 | 20.41 | ||
Maximum of Months | 0.727784E+10 | 18709.27 | 36.30 | 25.62 | 0.277281E+09 | 347.86 | 36.30 | 25.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107484E+12 | 193687.77 | 04-JAN-07:10 | 1.17 |
February | 0.760424E+11 | 193718.08 | 13-FEB-07:10 | 4.08 |
March | 0.675342E+11 | 193373.34 | 13-MAR-06:10 | 5.92 |
April | 0.164355E+11 | 191454.84 | 03-APR-06:30 | 13.30 |
May | 17158281.55 | 6530.34 | 30-MAY-04:01 | 25.60 |
June | 0.113264E+09 | 27156.16 | 07-JUN-06:25 | 21.95 |
July | 33718344.98 | 26536.10 | 15-JUL-06:30 | 25.00 |
August | 39614334.63 | 26009.43 | 17-AUG-06:30 | 23.65 |
September | 0.266241E+09 | 50554.45 | 28-SEP-06:23 | 22.70 |
October | 0.840917E+10 | 191007.20 | 30-OCT-06:35 | 16.67 |
November | 0.401883E+11 | 193129.79 | 16-NOV-07:10 | 9.77 |
December | 0.897806E+11 | 194268.49 | 21-DEC-07:08 | 0.50 |
Annual Sum or Average | 0.406345E+12 | |||
Minimum of Months | 17158281.55 | 6530.34 | 0.50 | |
Maximum of Months | 0.107484E+12 | 194268.49 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.584429E+11 | 165139.77 | 09-JAN-07:15 | 5.00 |
February | 0.389162E+11 | 165953.48 | 06-FEB-07:10 | 3.90 |
March | 0.375588E+11 | 164885.12 | 13-MAR-06:15 | 5.73 |
April | 0.444507E+10 | 95638.30 | 03-APR-06:10 | 12.57 |
May | 13669455.04 | 3387.80 | 22-MAY-04:01 | 26.10 |
June | 9942420.12 | 2815.76 | 28-JUN-04:01 | 27.12 |
July | 12431875.46 | 3093.00 | 19-JUL-04:01 | 27.20 |
August | 9092104.63 | 3194.26 | 23-AUG-04:01 | 26.38 |
September | 18000114.55 | 4194.15 | 10-SEP-15:12 | 35.17 |
October | 0.246416E+10 | 95899.44 | 30-OCT-06:08 | 16.17 |
November | 0.164138E+11 | 96036.71 | 18-NOV-07:08 | 14.50 |
December | 0.488877E+11 | 164530.25 | 21-DEC-07:10 | 0.50 |
Annual Sum or Average | 0.207192E+12 | |||
Minimum of Months | 9092104.63 | 2815.76 | 0.50 | |
Maximum of Months | 0.584429E+11 | 165953.48 | 35.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523788E+11 | 95101.16 | 13-JAN-11:30 | 10.50 |
February | 0.349547E+11 | 95640.21 | 06-FEB-12:03 | 11.88 |
March | 0.357114E+11 | 95695.78 | 10-MAR-17:10 | 13.72 |
April | 0.468603E+10 | 94287.61 | 12-APR-07:00 | 15.50 |
May | 18738607.01 | 4955.43 | 01-MAY-04:01 | 26.10 |
June | 17979022.11 | 4503.13 | 02-JUN-04:01 | 24.40 |
July | 24210958.59 | 5019.05 | 13-JUL-04:01 | 26.78 |
August | 18809762.59 | 5434.32 | 23-AUG-04:01 | 26.38 |
September | 27820748.73 | 5567.21 | 07-SEP-04:01 | 25.60 |
October | 0.997318E+09 | 92444.72 | 28-OCT-06:15 | 10.00 |
November | 0.778939E+10 | 94431.44 | 15-NOV-19:00 | 9.40 |
December | 0.391678E+11 | 95184.35 | 21-DEC-12:04 | 13.17 |
Annual Sum or Average | 0.175793E+12 | |||
Minimum of Months | 17979022.11 | 4503.13 | 9.40 | |
Maximum of Months | 0.523788E+11 | 95695.78 | 26.78 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5019171.93 | 11002.04 | 23-JAN-07:03 | 6.17 |
February | 8745188.29 | 26197.01 | 06-FEB-07:03 | 3.90 |
March | 3640812.52 | 18204.06 | 13-MAR-06:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 908598.26 | 6057.32 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 18313770.98 | |||
Minimum of Months | 0.00 | 0.00 | 0.50 | |
Maximum of Months | 8745188.29 | 26197.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164451E+09 | 50619.93 | 23-JAN-06:11 | 6.67 |
February | 0.129129E+09 | 53582.94 | 06-FEB-06:11 | 3.07 |
March | 61064791.01 | 49874.76 | 13-MAR-05:11 | 6.57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 21142614.95 | 23030.80 | 16-NOV-07:03 | 9.77 |
December | 89720036.96 | 37894.08 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.465508E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.50 | |
Maximum of Months | 0.164451E+09 | 53582.94 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.918508E+09 | 19806.39 | 23-JAN-06:11 | 6.67 |
February | 0.534851E+09 | 19561.75 | 06-FEB-06:11 | 3.07 |
March | 0.382034E+09 | 19042.48 | 11-MAR-06:11 | 6.60 |
April | 16129394.09 | 7136.56 | 17-APR-06:03 | 12.98 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 12665726.30 | 8678.45 | 28-OCT-05:12 | 10.00 |
November | 0.100143E+09 | 18067.53 | 16-NOV-06:12 | 9.40 |
December | 0.608212E+09 | 19668.63 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.257254E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.67 | |
Maximum of Months | 0.918508E+09 | 19806.39 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443405E+09 | 18476.79 | 09-JAN-06:11 | 6.33 |
February | 0.235687E+09 | 18011.66 | 06-FEB-06:11 | 3.07 |
March | 0.223432E+09 | 17729.24 | 10-MAR-06:11 | 5.87 |
April | 9766956.93 | 6379.01 | 03-APR-05:12 | 12.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 8658838.44 | 7937.57 | 28-OCT-05:12 | 10.00 |
November | 41034568.75 | 16745.37 | 16-NOV-06:12 | 9.40 |
December | 0.329680E+09 | 18338.24 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.129166E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.67 | |
Maximum of Months | 0.443405E+09 | 18476.79 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.502157E+09 | 23533.92 | 09-JAN-06:11 | 6.33 |
February | 0.289781E+09 | 23317.58 | 06-FEB-06:11 | 3.07 |
March | 0.311357E+09 | 22510.16 | 11-MAR-06:11 | 6.60 |
April | 15691511.34 | 6686.04 | 17-APR-06:03 | 12.98 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 8398930.27 | 8389.31 | 28-OCT-05:12 | 10.00 |
November | 44454309.04 | 21045.57 | 16-NOV-06:12 | 9.40 |
December | 0.368055E+09 | 23209.87 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.153989E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.67 | |
Maximum of Months | 0.502157E+09 | 23533.92 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534979E+09 | 20684.02 | 09-JAN-06:11 | 6.33 |
February | 0.313138E+09 | 20099.00 | 06-FEB-06:11 | 3.07 |
March | 0.246041E+09 | 19626.95 | 11-MAR-06:11 | 6.60 |
April | 11603726.65 | 5814.86 | 03-APR-05:12 | 12.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 8243938.27 | 8020.04 | 28-OCT-05:12 | 10.00 |
November | 61494441.84 | 17675.74 | 16-NOV-06:12 | 9.40 |
December | 0.355512E+09 | 20468.36 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.153101E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.67 | |
Maximum of Months | 0.534979E+09 | 20684.02 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259258E+09 | 18838.59 | 10-JAN-06:11 | 3.00 |
February | 0.162596E+09 | 19366.80 | 06-FEB-06:11 | 3.07 |
March | 0.145021E+09 | 18328.92 | 10-MAR-06:11 | 5.87 |
April | 3133884.99 | 3742.96 | 11-APR-06:03 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 42685.91 | 284.57 | 28-OCT-06:03 | 10.00 |
November | 5781675.52 | 5993.96 | 13-NOV-07:03 | 9.27 |
December | 0.130821E+09 | 18305.63 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.706655E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.67 | |
Maximum of Months | 0.259258E+09 | 19366.80 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103306E+09 | 19848.15 | 10-JAN-06:11 | 3.00 |
February | 59167498.83 | 20141.88 | 06-FEB-06:11 | 3.07 |
March | 81950080.03 | 17536.89 | 13-MAR-05:11 | 6.57 |
April | 5042290.56 | 2663.25 | 17-APR-06:03 | 12.98 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 735216.49 | 2862.62 | 28-OCT-06:03 | 10.00 |
November | 5439165.90 | 3892.62 | 16-NOV-06:12 | 9.40 |
December | 72162481.26 | 15216.76 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.327803E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.67 | |
Maximum of Months | 0.103306E+09 | 20141.88 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136902E+10 | 23375.81 | 10-JAN-06:11 | 3.00 |
February | 0.765325E+09 | 23264.10 | 06-FEB-06:11 | 3.07 |
March | 0.110930E+10 | 23330.85 | 10-MAR-06:11 | 5.87 |
April | 0.198868E+09 | 19157.10 | 11-APR-06:03 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 22305840.00 | 3649.53 | 27-OCT-07:00 | 14.00 |
November | 0.285410E+09 | 18566.70 | 15-NOV-07:03 | 7.80 |
December | 0.112641E+10 | 23844.78 | 20-DEC-07:10 | 1.83 |
Annual Sum or Average | 0.487663E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.83 | |
Maximum of Months | 0.136902E+10 | 23844.78 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117776E+09 | 20555.71 | 10-JAN-06:11 | 3.00 |
February | 72865714.70 | 20761.75 | 06-FEB-06:11 | 3.07 |
March | 84412612.21 | 17304.61 | 13-MAR-05:11 | 6.57 |
April | 4032610.55 | 1587.94 | 03-APR-05:12 | 12.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 427780.35 | 2376.84 | 28-OCT-06:03 | 10.00 |
November | 6411905.22 | 3543.60 | 16-NOV-06:12 | 9.40 |
December | 64621395.56 | 14693.72 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.350548E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.67 | |
Maximum of Months | 0.117776E+09 | 20761.75 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415562E+09 | 18637.48 | 04-JAN-06:11 | 1.67 |
February | 0.213939E+09 | 18617.55 | 06-FEB-06:11 | 3.07 |
March | 0.172671E+09 | 18243.27 | 09-MAR-06:02 | 1.10 |
April | 3121230.99 | 4268.78 | 11-APR-06:03 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 1538610.98 | 6717.32 | 28-OCT-06:03 | 10.00 |
November | 17300168.41 | 8804.85 | 16-NOV-06:12 | 9.40 |
December | 0.255269E+09 | 18290.71 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.107940E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.10 | |
Maximum of Months | 0.415562E+09 | 18637.48 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208677E+09 | 20535.74 | 04-JAN-06:11 | 1.67 |
February | 99048941.72 | 20322.23 | 06-FEB-06:11 | 3.07 |
March | 0.107853E+09 | 19734.51 | 10-MAR-06:11 | 5.87 |
April | 5093892.18 | 2693.14 | 04-APR-06:03 | 16.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 2608202.81 | 2637.82 | 18-OCT-06:03 | 15.97 |
November | 9967812.23 | 9648.45 | 16-NOV-06:12 | 9.40 |
December | 0.149547E+09 | 20120.17 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.582797E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.67 | |
Maximum of Months | 0.208677E+09 | 20535.74 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202394E+09 | 22790.66 | 04-JAN-06:11 | 1.67 |
February | 98758625.14 | 22448.55 | 17-FEB-06:01 | 1.52 |
March | 0.136591E+09 | 22098.99 | 10-MAR-06:11 | 5.87 |
April | 3451285.07 | 3624.30 | 11-APR-06:03 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 882895.00 | 5011.37 | 28-OCT-06:03 | 10.00 |
November | 9225530.35 | 7255.10 | 16-NOV-06:12 | 9.40 |
December | 0.139309E+09 | 22645.14 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.590613E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.52 | |
Maximum of Months | 0.202394E+09 | 22790.66 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239107E+09 | 21351.23 | 04-JAN-06:11 | 1.67 |
February | 0.126932E+09 | 20936.81 | 06-FEB-06:11 | 3.07 |
March | 0.113055E+09 | 19761.69 | 13-MAR-05:11 | 6.57 |
April | 4137055.40 | 2494.68 | 04-APR-06:03 | 16.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 2000787.18 | 2748.18 | 28-OCT-06:03 | 10.00 |
November | 13350520.53 | 9168.25 | 16-NOV-06:12 | 9.40 |
December | 0.147876E+09 | 20951.98 | 20-DEC-06:11 | 2.67 |
Annual Sum or Average | 0.646458E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.67 | |
Maximum of Months | 0.239107E+09 | 21351.23 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5238701.53 | 0.333379E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5559094.99 | 0.256231E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13703683.76 | 0.271026E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19050552.56 | 0.118152E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74678361.91 | 20846078.15 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64585587.06 | 16012281.46 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90015097.50 | 6997186.36 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87643942.85 | 21181915.53 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84787882.10 | 29406484.88 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75866888.17 | 0.100022E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13328484.06 | 0.162612E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8622770.29 | 0.294025E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543081E+09 | 0.162989E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5238701.53 | 6997186.36 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90015097.50 | 0.333379E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3630857.65 | 0.229202E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3815378.26 | 0.177112E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8618208.22 | 0.188798E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13125227.77 | 83575407.24 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51402326.65 | 13489950.93 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45377064.16 | 10003368.57 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63142955.86 | 4546136.75 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61604747.71 | 13136060.49 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58705733.44 | 18565332.80 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51546299.45 | 67931677.68 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8782375.87 | 0.113859E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5771963.02 | 0.200292E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375523E+09 | 0.112051E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3630857.65 | 4546136.75 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63142955.86 | 0.229202E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1016998.19 | 0.386683E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2104839.76 | 0.293447E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8434457.31 | 0.291584E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18712160.98 | 0.126078E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80729360.25 | 19510756.84 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70257630.54 | 14483027.63 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97593952.18 | 6349400.26 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90704621.98 | 20486188.32 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81892180.74 | 30947160.39 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59591053.13 | 0.118750E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6317242.00 | 0.195039E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3618494.10 | 0.341426E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520973E+09 | 0.184478E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1016998.19 | 6349400.26 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97593952.18 | 0.386683E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3686384.51 | 0.231321E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3822552.26 | 0.179018E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10283619.85 | 0.186186E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13769337.54 | 84692092.46 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58040316.70 | 13591733.22 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47527132.25 | 10873379.32 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67653367.17 | 4750074.20 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65370661.51 | 14424858.25 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62506275.12 | 19460712.47 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55432450.97 | 71006158.80 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10243972.69 | 0.112823E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5936663.29 | 0.203294E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404273E+09 | 0.113144E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3686384.51 | 4750074.20 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67653367.17 | 0.231321E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2672478.99 | 0.201573E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3002120.83 | 0.151890E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7828140.27 | 0.156107E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10628163.67 | 66543161.58 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40556332.25 | 9403627.94 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34882281.80 | 8617152.86 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48911600.92 | 3710880.78 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45208603.35 | 14563786.21 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43005604.09 | 21372013.59 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38441348.83 | 66051805.92 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5918909.50 | 0.104529E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3936283.99 | 0.182136E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284992E+09 | 0.986497E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2672478.99 | 3710880.78 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48911600.92 | 0.201573E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1959833.65 | 0.139124E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2280793.31 | 0.105746E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5120807.25 | 0.109073E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7481899.32 | 47200503.01 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28535350.17 | 6419512.05 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24697113.33 | 5531315.62 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34543237.90 | 2591573.69 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32067011.59 | 9485610.50 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29920538.01 | 13801429.78 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27154071.66 | 44119822.44 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4243513.23 | 72440223.23 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2850103.20 | 0.123653E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200854E+09 | 0.679186E+09 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1959833.65 | 2591573.69 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34543237.90 | 0.139124E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36867769.84 | 0.349716E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62469305.57 | 0.212158E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163613E+09 | 0.226874E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565058E+09 | 0.642982E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190479E+10 | 11701845.11 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222095E+10 | 11163300.96 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194471E+10 | 10510014.56 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209977E+10 | 25865822.48 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109176E+10 | 66786039.14 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112436E+10 | 0.443192E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302844E+09 | 0.142448E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134225E+09 | 0.277553E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116514E+11 | 0.132997E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36867769.84 | 10510014.56 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222095E+10 | 0.349716E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1731774.15 | 0.140703E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1972657.08 | 0.106379E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5492258.91 | 0.108012E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7151411.21 | 47923909.97 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30940253.05 | 6260245.79 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24835957.81 | 6173232.32 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35675781.74 | 2588919.09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32780617.81 | 10422191.29 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30347427.51 | 14634662.29 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27026914.42 | 46075487.86 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4597259.24 | 71758536.01 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2672749.68 | 0.125995E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205225E+09 | 0.686925E+09 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1731774.15 | 2588919.09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35675781.74 | 0.140703E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3963257.24 | 0.303889E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4219642.01 | 0.231032E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10910897.78 | 0.244409E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15410690.85 | 0.107373E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59756623.97 | 18939897.52 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53119552.77 | 14863839.89 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74006516.78 | 6298904.54 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71479444.37 | 19802923.29 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67701666.81 | 29258930.07 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60634930.36 | 95293864.72 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9761611.08 | 0.153396E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6549666.49 | 0.270283E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437515E+09 | 0.149484E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3963257.24 | 6298904.54 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74006516.78 | 0.303889E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3296043.30 | 0.206533E+09 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3491905.21 | 0.158590E+09 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7792277.28 | 0.167190E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11575401.50 | 74059556.39 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42620337.20 | 11865988.99 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38150588.10 | 9008980.60 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53511299.40 | 3908244.23 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51690646.88 | 11977053.67 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48614993.57 | 17831378.48 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43876745.93 | 62731165.43 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7302503.62 | 0.104990E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4980944.03 | 0.181679E+09 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316904E+09 | 0.101037E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3296043.30 | 3908244.23 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53511299.40 | 0.206533E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 748219.95 | 0.350186E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1665383.64 | 0.264335E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6580320.50 | 0.261450E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15088150.96 | 0.113663E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64589913.01 | 17721745.93 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57788444.31 | 13438206.41 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80574343.84 | 5723130.38 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74006725.40 | 19166948.21 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64920180.62 | 30492719.48 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47892321.61 | 0.111085E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4798658.60 | 0.180312E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2859757.18 | 0.310505E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421512E+09 | 0.167808E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 748219.95 | 5723130.38 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80574343.84 | 0.350186E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2959134.50 | 0.209326E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3050398.84 | 0.160118E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8448664.06 | 0.165936E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11013819.40 | 75784384.34 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46322426.61 | 12377150.49 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38741146.34 | 10018971.73 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55410856.02 | 4275782.55 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53394275.99 | 13484688.49 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49517569.34 | 19208670.60 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44519257.41 | 66084965.76 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8013557.41 | 0.104535E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4633102.73 | 0.185051E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326024E+09 | 0.102620E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2959134.50 | 4275782.55 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55410856.02 | 0.209326E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1660823.53 | 0.484918E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2894199.81 | 0.372113E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9333022.48 | 0.385441E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15028075.34 | 0.171671E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67923051.72 | 23531976.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60612460.85 | 20146944.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90200072.17 | 7010031.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81621203.97 | 28194443.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74628256.61 | 45292945.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58027399.29 | 0.155872E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6419887.21 | 0.256928E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4389474.00 | 0.436384E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472738E+09 | 0.238750E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1660823.53 | 7010031.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90200072.17 | 0.484918E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3867738.99 | 0.571965E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5430648.44 | 0.440904E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14601461.07 | 0.462583E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20649601.33 | 0.204827E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89181798.23 | 27341808.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79164102.21 | 24279979.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118008E+09 | 7967584.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108910E+09 | 31760251.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100220E+09 | 49786988.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79954735.29 | 0.179461E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11036913.84 | 0.299227E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7751581.09 | 0.511470E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638776E+09 | 0.281157E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3867738.99 | 7967584.62 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118008E+09 | 0.571965E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405063.33 | 0.538896E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 669674.64 | 0.425717E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3223652.00 | 0.445939E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8548164.45 | 0.208037E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72340319.14 | 18967105.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67183211.50 | 15471761.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101104E+09 | 5821115.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99471471.85 | 22529821.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91174797.44 | 32716209.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56813483.53 | 0.148514E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5575563.41 | 0.260542E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3290268.99 | 0.469657E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509800E+09 | 0.259281E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405063.33 | 5821115.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101104E+09 | 0.538896E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.64 | 15-JAN-13:54 | 712.87 | 09-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.89 | 20-FEB-15:10 | 1000.58 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 231.25 | 05-MAR-12:00 | 851.99 | 20-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.14 | 29-APR-17:50 | 463.90 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.30 | 21-MAY-13:40 | 91.97 | 06-MAY-20:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.97 | 10-JUN-17:01 | 159.32 | 18-JUN-14:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.16 | 22-JUL-18:50 | 93.41 | 30-JUL-11:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.36 | 20-AUG-14:00 | 208.24 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.94 | 09-SEP-23:00 | 213.63 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 573.97 | 09-OCT-14:00 | 348.50 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.78 | 05-NOV-12:50 | 574.23 | 12-NOV-06:55 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.70 | 10-DEC-11:00 | 782.09 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 135.64 | 91.97 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 573.97 | 1000.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.92 | 15-JAN-13:52 | 475.28 | 09-JAN-22:03 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.74 | 20-FEB-15:10 | 668.85 | 05-FEB-08:00 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 145.10 | 05-MAR-13:00 | 568.88 | 20-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.69 | 29-APR-17:50 | 310.84 | 01-APR-18:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.20 | 21-MAY-13:40 | 73.03 | 14-MAY-11:42 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.76 | 10-JUN-17:50 | 112.43 | 18-JUN-14:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 286.41 | 22-JUL-18:50 | 119.64 | 30-JUL-11:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.72 | 20-AUG-14:00 | 135.59 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.34 | 09-SEP-23:00 | 140.65 | 05-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.39 | 09-OCT-14:00 | 232.63 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.87 | 05-NOV-12:50 | 469.92 | 12-NOV-08:50 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 96.81 | 10-DEC-15:20 | 522.22 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 93.92 | 73.03 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 438.39 | 668.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 16-JAN-15:00 | 776.42 | 22-JAN-16:55 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.27 | 02-FEB-13:00 | 1000.58 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.13 | 26-MAR-14:00 | 857.25 | 20-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.98 | 29-APR-17:50 | 495.21 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.64 | 21-MAY-13:40 | 88.41 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.25 | 10-JUN-17:50 | 156.97 | 18-JUN-14:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.40 | 22-JUL-18:50 | 86.53 | 30-JUL-11:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.87 | 20-AUG-14:00 | 208.36 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.68 | 09-SEP-23:00 | 218.66 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 451.17 | 09-OCT-13:55 | 381.69 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.47 | 07-NOV-22:02 | 757.08 | 12-NOV-11:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.10 | 13-DEC-14:00 | 798.87 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 86.53 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 467.68 | 1000.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.00 | 16-JAN-12:40 | 476.61 | 22-JAN-16:55 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.82 | 26-FEB-11:53 | 667.05 | 05-FEB-08:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.62 | 05-MAR-12:00 | 569.34 | 20-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.78 | 23-APR-14:02 | 348.34 | 02-APR-17:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.29 | 21-MAY-13:22 | 76.70 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.60 | 10-JUN-17:09 | 113.83 | 18-JUN-14:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.41 | 16-JUL-12:42 | 61.71 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.28 | 20-AUG-14:00 | 140.53 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.71 | 09-SEP-23:00 | 140.55 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.98 | 09-OCT-12:00 | 243.54 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.05 | 11-NOV-12:40 | 384.06 | 12-NOV-06:55 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.27 | 10-DEC-11:00 | 519.29 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 85.82 | 61.71 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 452.98 | 667.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.28 | 16-JAN-14:50 | 407.21 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.65 | 20-FEB-15:10 | 563.93 | 05-FEB-07:55 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.18 | 05-MAR-12:40 | 468.24 | 20-MAR-21:13 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.66 | 29-APR-17:50 | 264.49 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.76 | 21-MAY-13:50 | 49.52 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.62 | 10-JUN-17:01 | 85.16 | 06-JUN-21:50 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.28 | 22-JUL-18:50 | 46.57 | 31-JUL-02:30 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.55 | 20-AUG-14:00 | 129.92 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.76 | 09-SEP-23:00 | 122.69 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.45 | 09-OCT-14:00 | 234.38 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.38 | 11-NOV-13:00 | 352.25 | 12-NOV-08:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.62 | 10-DEC-11:00 | 497.18 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.28 | 46.57 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 317.45 | 563.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.28 | 15-JAN-14:00 | 268.35 | 21-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 | 20-FEB-15:10 | 406.31 | 05-FEB-08:00 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 | 05-MAR-13:00 | 317.65 | 20-MAR-21:17 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.68 | 29-APR-17:50 | 177.04 | 01-APR-21:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.51 | 21-MAY-13:50 | 34.64 | 09-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.92 | 10-JUN-17:50 | 59.35 | 18-JUN-14:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.87 | 22-JUL-18:50 | 55.44 | 30-JUL-11:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.25 | 20-AUG-14:00 | 86.78 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.98 | 09-SEP-23:00 | 83.62 | 05-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.61 | 09-OCT-14:00 | 156.72 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 | 11-NOV-13:00 | 282.69 | 12-NOV-08:30 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.06 | 10-DEC-14:40 | 334.83 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 47.28 | 34.64 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 246.61 | 406.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2496.35 | 02-JAN-13:00 | 26147.02 | 05-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5295.68 | 02-FEB-13:00 | 24914.38 | 17-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5319.96 | 30-MAR-12:00 | 25426.25 | 09-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9455.36 | 28-APR-16:10 | 16091.38 | 11-APR-06:10 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10298.49 | 25-MAY-16:05 | 615.05 | 02-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10764.54 | 28-JUN-16:05 | 968.45 | 07-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13241.88 | 21-JUL-16:03 | 1190.42 | 13-JUL-11:10 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13770.10 | 30-AUG-16:02 | 1905.36 | 16-AUG-17:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9613.56 | 06-SEP-16:03 | 3435.66 | 07-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9430.95 | 05-OCT-17:00 | 9172.38 | 27-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5583.68 | 02-NOV-11:05 | 17571.86 | 15-NOV-07:10 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4993.84 | 13-DEC-13:00 | 26065.60 | 21-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2496.35 | 615.05 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13770.10 | 26147.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.94 | 16-JAN-12:32 | 270.61 | 21-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 | 26-FEB-13:40 | 376.32 | 05-FEB-08:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.73 | 05-MAR-12:40 | 316.92 | 20-MAR-21:13 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.39 | 23-APR-13:52 | 182.31 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.37 | 21-MAY-13:50 | 34.46 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.00 | 10-JUN-17:10 | 61.64 | 18-JUN-14:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.37 | 22-JUL-18:50 | 34.28 | 31-JUL-02:20 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.10 | 20-AUG-14:00 | 89.76 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.19 | 09-SEP-23:00 | 83.00 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.15 | 09-OCT-12:00 | 163.95 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.97 | 11-NOV-12:20 | 238.86 | 12-NOV-06:55 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.45 | 10-DEC-11:20 | 334.28 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 | 34.28 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 240.15 | 376.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.85 | 16-JAN-15:00 | 595.95 | 09-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.15 | 20-FEB-14:42 | 849.42 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.25 | 05-MAR-12:40 | 719.79 | 20-MAR-21:13 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.57 | 29-APR-17:50 | 400.96 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.14 | 21-MAY-13:42 | 84.50 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.88 | 10-JUN-17:01 | 129.68 | 06-JUN-21:50 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.65 | 22-JUL-18:50 | 74.81 | 31-JUL-02:30 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.43 | 20-AUG-14:00 | 187.19 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.39 | 09-SEP-23:00 | 186.61 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.28 | 09-OCT-14:00 | 332.64 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.26 | 05-NOV-13:00 | 521.05 | 12-NOV-06:55 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.60 | 10-DEC-10:53 | 719.85 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 102.85 | 74.81 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 467.28 | 849.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.15 | 15-JAN-14:10 | 397.26 | 09-JAN-22:03 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.50 | 20-FEB-15:10 | 608.59 | 05-FEB-10:00 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.57 | 05-MAR-13:00 | 481.24 | 20-MAR-21:13 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.08 | 29-APR-17:50 | 265.96 | 01-APR-21:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.77 | 21-MAY-13:42 | 54.92 | 07-MAY-06:50 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.75 | 10-JUN-17:50 | 89.91 | 18-JUN-14:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.91 | 22-JUL-18:50 | 91.75 | 30-JUL-11:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.68 | 20-AUG-14:00 | 121.21 | 25-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.45 | 09-SEP-23:00 | 122.56 | 05-SEP-03:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.61 | 09-OCT-13:50 | 220.78 | 29-OCT-02:00 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.45 | 05-NOV-13:00 | 425.85 | 12-NOV-08:50 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.14 | 10-DEC-15:30 | 479.60 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 83.15 | 54.92 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 374.61 | 608.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 | 19-JAN-12:10 | 661.52 | 22-JAN-16:55 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.99 | 02-FEB-13:00 | 871.63 | 05-FEB-10:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 92.14 | 26-MAR-12:30 | 739.94 | 20-MAR-21:13 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.93 | 29-APR-17:50 | 424.73 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.95 | 21-MAY-13:42 | 83.63 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.12 | 10-JUN-17:01 | 127.49 | 18-JUN-14:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.99 | 22-JUL-18:50 | 73.57 | 31-JUL-02:30 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 375.44 | 20-AUG-14:00 | 187.38 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.99 | 09-SEP-23:00 | 191.38 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.07 | 09-OCT-13:44 | 360.52 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.34 | 07-NOV-22:02 | 639.63 | 12-NOV-10:52 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.57 | 13-DEC-14:00 | 734.46 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 | 73.57 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 381.99 | 871.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.71 | 16-JAN-12:10 | 408.77 | 22-JAN-16:55 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 | 26-FEB-13:13 | 578.29 | 05-FEB-08:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.20 | 05-MAR-12:40 | 484.13 | 20-MAR-21:13 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.68 | 29-APR-18:40 | 287.00 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.20 | 21-MAY-13:42 | 53.81 | 09-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.13 | 10-JUN-17:10 | 92.92 | 18-JUN-14:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.00 | 22-JUL-18:50 | 53.49 | 31-JUL-02:70 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.38 | 20-AUG-14:00 | 126.22 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.97 | 09-SEP-23:00 | 123.59 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.57 | 09-OCT-11:50 | 230.84 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.28 | 11-NOV-12:20 | 348.19 | 12-NOV-06:55 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.58 | 10-DEC-10:53 | 477.36 | 20-DEC-01:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 | 53.49 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 360.57 | 578.29 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.96 | 16-JAN-14:52 | 950.34 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.09 | 20-FEB-14:52 | 1340.71 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.56 | 05-MAR-12:40 | 1145.57 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.81 | 29-APR-17:01 | 645.71 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.91 | 21-MAY-13:52 | 110.25 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.55 | 10-JUN-17:01 | 184.05 | 06-JUN-21:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.52 | 22-JUL-18:52 | 92.96 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.64 | 20-AUG-14:00 | 280.25 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.33 | 09-SEP-17:01 | 252.02 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.03 | 09-OCT-14:00 | 554.59 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.58 | 05-NOV-13:00 | 815.25 | 12-NOV-06:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.53 | 10-DEC-15:00 | 1226.84 | 20-DEC-00:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.96 | 92.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.03 | 1340.71 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.16 | 16-JAN-15:00 | 1164.59 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.36 | 20-FEB-14:52 | 1585.93 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.88 | 05-MAR-12:40 | 1413.50 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.61 | 29-APR-17:01 | 773.06 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.73 | 21-MAY-13:52 | 134.29 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.11 | 10-JUN-17:01 | 226.93 | 06-JUN-21:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.10 | 22-JUL-18:52 | 115.58 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.20 | 20-AUG-14:00 | 346.09 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.54 | 09-SEP-17:01 | 317.08 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.17 | 09-OCT-14:00 | 643.79 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.45 | 05-NOV-13:00 | 1006.26 | 12-NOV-06:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.25 | 10-DEC-15:00 | 1457.79 | 20-DEC-00:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.25 | 115.58 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 661.17 | 1585.93 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.44 | 16-JAN-15:00 | 1090.66 | 09-JAN-22:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.11 | 02-FEB-13:00 | 1481.86 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.28 | 26-MAR-14:00 | 1335.38 | 20-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.71 | 29-APR-17:01 | 841.26 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.96 | 21-MAY-13:42 | 309.18 | 14-MAY-11:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.49 | 10-JUN-17:01 | 261.96 | 18-JUN-13:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.80 | 22-JUL-18:50 | 307.00 | 30-JUL-11:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.97 | 20-AUG-14:00 | 290.42 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.58 | 09-SEP-23:00 | 298.74 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.19 | 09-OCT-12:00 | 513.30 | 28-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.35 | 07-NOV-22:02 | 981.47 | 12-NOV-11:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 | 10-DEC-10:53 | 1307.31 | 20-DEC-00:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.11 | 261.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.58 | 1481.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 38388.16 | 02-JAN-06:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24224.86 | 28-FEB-06:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33973.33 | 09-MAR-06:02 | 3811.58 | 6507.07 | 46406.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43336.54 | 28-APR-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53347.52 | 01-MAY-04:01 | 0.00 | 7591.59 | 41762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 53298.57 | 19-JUN-04:01 | 0.00 | 8676.10 | 47728.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 53368.72 | 06-JUL-04:02 | 0.00 | 8676.10 | 47728.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 53797.51 | 07-AUG-04:02 | 0.00 | 8676.10 | 47728.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 52858.19 | 01-SEP-04:21 | 0.00 | 7591.59 | 41762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 53620.92 | 06-OCT-04:02 | 0.00 | 8676.10 | 47728.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45515.47 | 03-NOV-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36082.64 | 15-DEC-06:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 24224.86 | 0.00 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53797.51 | 3811.58 | 8676.10 | 47728.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9359.02 | 01-JAN-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 |
February | 10672.42 | 24-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 |
March | 11167.26 | 29-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 |
April | 15733.73 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.61 | 0.00 |
May | 20424.13 | 28-MAY-14:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 0.00 |
June | 19206.00 | 25-JUN-14:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.97 | 0.00 |
July | 17781.19 | 07-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.56 | 0.00 |
August | 17035.03 | 03-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.92 | 0.00 |
September | 15719.32 | 01-SEP-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.39 | 0.00 |
October | 15333.99 | 13-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.01 | 0.00 |
November | 12359.28 | 02-NOV-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.92 | 0.00 |
December | 10576.24 | 15-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9359.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20424.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.92 | 34.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3910.25 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.13 |
February | 3195.07 | 28-FEB-20:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 |
March | 3402.48 | 01-MAR-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.35 |
April | 3884.61 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.84 | 0.00 |
May | 4568.72 | 04-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.62 | 0.00 |
June | 4646.09 | 14-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.25 | 0.00 |
July | 5004.84 | 05-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.21 | 0.00 |
August | 4956.21 | 30-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.37 | 0.00 |
September | 4947.92 | 11-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.79 | 0.00 |
October | 5133.06 | 10-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.33 | 0.00 |
November | 3410.02 | 03-NOV-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3618.70 | 18-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3195.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5133.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.33 | 215.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3842.12 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.83 |
February | 3232.32 | 02-FEB-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 |
March | 3602.73 | 31-MAR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
April | 4230.94 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.95 | 0.00 |
May | 4888.49 | 04-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 | 0.00 |
June | 4920.39 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 | 0.00 |
July | 5315.49 | 05-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 0.00 |
August | 5517.72 | 30-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.22 | 0.00 |
September | 5303.23 | 11-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.90 | 0.00 |
October | 5664.15 | 10-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.84 | 0.00 |
November | 4169.21 | 02-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.24 | 0.00 |
December | 3610.35 | 15-DEC-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3232.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5664.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.84 | 128.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16164.30 | 02-JAN-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15841.57 | 28-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16387.66 | 30-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18571.53 | 28-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40743.36 | 26-MAY-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41168.88 | 30-JUN-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43750.06 | 05-JUL-04:02 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41310.36 | 30-AUG-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41105.21 | 06-SEP-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40630.76 | 05-OCT-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18138.97 | 03-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16988.90 | 15-DEC-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15841.57 | 0.00 | 7591.59 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43750.06 | 6035.01 | 9760.61 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16470.71 | 19-JAN-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17328.02 | 24-FEB-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18962.88 | 29-MAR-15:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23220.69 | 28-APR-15:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48858.47 | 08-MAY-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48709.80 | 14-JUN-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 49000.61 | 11-JUL-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49162.57 | 25-AUG-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48879.52 | 11-SEP-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48334.35 | 06-OCT-04:01 | 0.00 | 8676.10 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20683.46 | 02-NOV-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18658.56 | 15-DEC-15:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16470.71 | 0.00 | 8676.10 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49162.57 | 6035.01 | 9760.61 | 19536.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4178.48 | 01-JAN-14:41 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 0.00 |
February | 4718.91 | 24-FEB-14:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 0.00 |
March | 6368.83 | 30-MAR-13:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.46 | 0.00 |
April | 8128.30 | 28-APR-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 84.43 | 0.00 |
May | 15724.24 | 07-MAY-14:52 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 140.29 | 0.00 |
June | 16590.46 | 25-JUN-14:51 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 70.13 | 0.00 |
July | 14744.18 | 24-JUL-04:01 | 0.00 | 1829.00 | 4118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
August | 13632.79 | 28-AUG-05:01 | 937.43 | 1600.37 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 0.00 |
September | 15130.77 | 10-SEP-15:51 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 153.12 | 0.00 |
October | 12112.90 | 23-OCT-05:01 | 1071.35 | 1829.00 | 5103.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 |
November | 6363.85 | 02-NOV-13:50 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | 0.00 |
December | 5458.91 | 15-DEC-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4178.48 | 0.00 | 685.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16590.46 | 1306.65 | 2057.62 | 5103.10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.12 | 2.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4741.77 | 19-JAN-10:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 |
February | 5124.91 | 26-FEB-10:18 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 |
March | 7719.02 | 26-MAR-10:08 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.25 |
April | 7057.14 | 28-APR-10:20 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 0.00 |
May | 16543.89 | 29-MAY-09:32 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | 0.00 |
June | 12253.22 | 04-JUN-10:22 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 | 0.00 |
July | 16546.91 | 23-JUL-10:22 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 | 0.00 |
August | 10547.65 | 28-AUG-04:01 | 0.00 | 1157.91 | 2607.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 0.00 |
September | 16725.57 | 10-SEP-09:52 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 150.46 | 0.00 |
October | 8590.32 | 09-OCT-07:53 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.80 |
November | 6272.65 | 02-NOV-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 0.00 |
December | 4562.59 | 10-DEC-09:58 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4562.59 | 0.00 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16725.57 | 827.22 | 1302.65 | 2607.15 | 0.00 | 0.00 | 0.00 | 0.00 | 150.46 | 84.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23573.72 | 01-JAN-14:01 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.49 |
February | 12466.77 | 24-FEB-14:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 | 0.00 |
March | 19776.11 | 26-MAR-13:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 86.91 | 0.00 |
April | 11568.48 | 23-APR-14:31 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 0.00 |
May | 17076.78 | 07-MAY-14:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 140.24 | 0.00 |
June | 15892.37 | 25-JUN-14:51 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 72.97 | 0.00 |
July | 17435.34 | 24-JUL-04:01 | 0.00 | 1829.00 | 4118.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 0.00 |
August | 15435.94 | 28-AUG-04:01 | 0.00 | 1829.00 | 4118.41 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | 0.00 |
September | 21205.27 | 10-SEP-13:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 175.62 | 0.00 |
October | 22250.93 | 01-OCT-13:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 |
November | 21820.56 | 05-NOV-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
December | 23041.03 | 10-DEC-13:11 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11568.48 | 0.00 | 685.87 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23573.72 | 1272.23 | 2057.62 | 4118.41 | 0.00 | 0.00 | 0.00 | 0.00 | 175.62 | 45.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6215.80 | 19-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | 0.00 |
February | 7441.67 | 27-FEB-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 | 0.00 |
March | 7528.89 | 06-MAR-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 0.00 |
April | 13421.79 | 16-APR-16:22 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.83 |
May | 19076.44 | 28-MAY-16:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 99.40 | 0.00 |
June | 18821.58 | 11-JUN-16:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 68.37 | 0.00 |
July | 18682.91 | 16-JUL-15:11 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 139.99 | 0.00 |
August | 11313.09 | 30-AUG-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 | 0.00 |
September | 19066.01 | 10-SEP-15:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 88.41 | 0.00 |
October | 17178.95 | 08-OCT-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 181.76 | 0.00 |
November | 8055.51 | 06-NOV-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.64 | 0.00 |
December | 8148.06 | 10-DEC-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6215.80 | 254.33 | 434.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19076.44 | 805.38 | 1302.56 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 181.76 | 206.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3691.02 | 02-JAN-13:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 |
February | 3535.19 | 02-FEB-14:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.81 | 0.00 |
March | 4963.74 | 30-MAR-13:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 0.00 |
April | 6071.01 | 28-APR-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 45.14 | 0.00 |
May | 8437.37 | 31-MAY-05:01 | 937.43 | 1600.37 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
June | 9778.04 | 05-JUN-04:01 | 0.00 | 1829.00 | 4118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 |
July | 11673.85 | 07-JUL-04:01 | 0.00 | 1829.00 | 4118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
August | 11193.15 | 24-AUG-04:01 | 0.00 | 1829.00 | 4118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
September | 10465.08 | 12-SEP-04:01 | 0.00 | 1829.00 | 4118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 | 0.00 |
October | 10219.54 | 06-OCT-04:01 | 0.00 | 1829.00 | 4118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
November | 5816.56 | 03-NOV-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 0.00 |
December | 4914.91 | 15-DEC-14:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3535.19 | 0.00 | 1600.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11673.85 | 1306.65 | 2057.62 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 45.14 | 10.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4438.75 | 19-JAN-10:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 |
February | 4881.09 | 26-FEB-10:17 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 |
March | 6474.58 | 26-MAR-09:15 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 |
April | 14959.16 | 23-APR-09:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
May | 15603.22 | 14-MAY-08:51 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 0.00 |
June | 7956.45 | 19-JUN-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15133.76 | 23-JUL-09:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 0.00 |
August | 15208.42 | 06-AUG-11:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 | 0.00 |
September | 16561.76 | 03-SEP-09:21 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 0.00 |
October | 11293.67 | 15-OCT-09:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.37 |
November | 7224.77 | 11-NOV-09:33 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
December | 4389.84 | 17-DEC-09:32 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4389.84 | 254.35 | 434.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16561.76 | 827.22 | 1302.65 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 | 155.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18292.92 | 16-JAN-15:02 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 |
February | 14399.74 | 26-FEB-14:12 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 |
March | 11805.22 | 28-MAR-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4604.99 | 0.00 |
April | 14622.48 | 28-APR-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8238.58 | 0.00 |
May | 14952.12 | 19-MAY-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9197.75 | 0.00 |
June | 15113.63 | 28-JUN-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9818.28 | 0.00 |
July | 16012.36 | 21-JUL-16:10 | 1607.03 | 4572.49 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 12044.71 | 0.00 |
August | 16700.24 | 30-AUG-16:10 | 2008.79 | 5715.62 | 3986.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12022.15 | 0.00 |
September | 18173.18 | 24-SEP-13:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 93.54 | 0.00 |
October | 19130.65 | 15-OCT-12:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 | 0.00 |
November | 18946.27 | 05-NOV-13:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 |
December | 19746.19 | 10-DEC-13:11 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11805.22 | 401.76 | 685.87 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19746.19 | 2008.79 | 5715.62 | 3986.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12044.71 | 20.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5202.90 | 31-JAN-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
February | 9387.22 | 26-FEB-17:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.36 |
March | 6020.38 | 26-MAR-15:28 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 |
April | 9372.94 | 29-APR-17:07 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 37.04 | 0.00 |
May | 15783.48 | 29-MAY-16:12 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 | 0.00 |
June | 15912.74 | 11-JUN-16:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 0.00 |
July | 11006.17 | 22-JUL-17:06 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 24.86 | 0.00 |
August | 10032.03 | 30-AUG-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | 0.00 |
September | 16397.88 | 17-SEP-15:31 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 0.00 |
October | 15797.80 | 01-OCT-16:22 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 | 0.00 |
November | 9799.56 | 05-NOV-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 0.00 |
December | 6455.52 | 15-DEC-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5202.90 | 254.33 | 434.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16397.88 | 805.38 | 1302.56 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 28.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4290.35 | 02-JAN-13:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
February | 4285.17 | 28-FEB-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 0.00 |
March | 5974.23 | 30-MAR-13:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 | 0.00 |
April | 7063.47 | 28-APR-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 | 0.00 |
May | 11046.99 | 30-MAY-04:01 | 0.00 | 1829.00 | 4118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12044.29 | 26-JUN-04:01 | 0.00 | 1829.00 | 4118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11658.66 | 07-JUL-04:01 | 0.00 | 1829.00 | 4118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 |
August | 11288.14 | 28-AUG-05:01 | 937.43 | 1600.37 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 2.29 | 0.00 |
September | 10536.34 | 11-SEP-05:01 | 937.43 | 1600.37 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
October | 10232.02 | 06-OCT-05:01 | 937.43 | 1600.37 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 0.00 |
November | 5831.64 | 03-NOV-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.34 | 0.00 |
December | 5022.21 | 15-DEC-14:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4285.17 | 0.00 | 1600.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12044.29 | 1306.65 | 2057.62 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 | 2.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5763.01 | 19-JAN-11:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 0.00 |
February | 5778.95 | 26-FEB-10:27 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 |
March | 7208.71 | 26-MAR-09:13 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.71 |
April | 16217.71 | 23-APR-09:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 |
May | 17594.25 | 29-MAY-08:41 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
June | 11078.97 | 04-JUN-10:22 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 0.00 |
July | 15981.01 | 23-JUL-09:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.00 |
August | 9640.43 | 28-AUG-04:01 | 0.00 | 1157.91 | 2607.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 0.00 |
September | 16549.87 | 24-SEP-09:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.43 | 0.00 |
October | 16109.83 | 09-OCT-10:22 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 | 0.00 |
November | 7509.31 | 02-NOV-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 0.00 |
December | 4623.83 | 17-DEC-10:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4623.83 | 0.00 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17594.25 | 1610.86 | 2605.29 | 2607.15 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 | 238.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20411.30 | 01-JAN-14:01 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.58 |
February | 12370.85 | 26-FEB-13:43 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 |
March | 9846.67 | 26-MAR-15:25 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 |
April | 9745.58 | 23-APR-13:12 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 | 0.00 |
May | 11388.89 | 28-MAY-13:20 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 122.12 | 0.00 |
June | 12097.94 | 29-JUN-04:01 | 0.00 | 1829.00 | 4118.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
July | 13821.16 | 24-JUL-04:01 | 0.00 | 1829.00 | 4118.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 0.00 |
August | 12964.59 | 22-AUG-04:01 | 0.00 | 1829.00 | 4118.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
September | 18320.91 | 10-SEP-13:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 148.63 | 0.00 |
October | 20022.21 | 09-OCT-11:41 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 149.01 | 0.00 |
November | 17968.70 | 11-NOV-13:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 |
December | 18676.82 | 17-DEC-13:22 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9745.58 | 0.00 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20411.30 | 468.72 | 1829.00 | 4118.41 | 0.00 | 0.00 | 0.00 | 0.00 | 149.01 | 384.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5933.61 | 31-JAN-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
February | 7088.85 | 27-FEB-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 0.00 |
March | 7078.86 | 06-MAR-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 0.00 |
April | 10885.93 | 29-APR-17:06 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 56.88 | 0.00 |
May | 18709.27 | 29-MAY-16:41 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 35.05 | 0.00 |
June | 16869.12 | 25-JUN-16:11 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 30.77 | 0.00 |
July | 16706.21 | 16-JUL-15:11 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 124.60 | 0.00 |
August | 10667.65 | 30-AUG-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 36.05 | 0.00 |
September | 17327.18 | 17-SEP-15:31 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 108.74 | 0.00 |
October | 16486.09 | 09-OCT-14:21 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 164.78 | 0.00 |
November | 7774.54 | 06-NOV-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
December | 7015.02 | 15-DEC-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5933.61 | 296.72 | 506.55 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18709.27 | 805.38 | 1302.56 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 164.78 | 0.18 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.195651E+12 | 219407.86 | 09-JAN-07:10 | 0.00 | 0.00 |
February | 0.175339E+12 | 249983.20 | 06-FEB-07:10 | 0.00 | 0.00 |
March | 0.200753E+12 | 208441.09 | 13-MAR-06:10 | 0.00 | 0.00 |
April | 0.187568E+12 | 191928.98 | 28-APR-15:00 | 0.00 | 0.00 |
May | 0.231048E+12 | 192106.57 | 18-MAY-15:30 | 0.00 | 0.00 |
June | 0.234729E+12 | 201065.29 | 28-JUN-14:30 | 0.00 | 0.00 |
July | 0.236012E+12 | 208567.35 | 21-JUL-15:50 | 0.00 | 0.00 |
August | 0.247733E+12 | 210457.63 | 30-AUG-15:00 | 0.00 | 0.00 |
September | 0.220891E+12 | 196572.28 | 01-SEP-14:00 | 0.00 | 0.00 |
October | 0.220181E+12 | 203957.78 | 05-OCT-14:00 | 0.00 | 0.00 |
November | 0.190264E+12 | 181839.71 | 02-NOV-14:30 | 0.00 | 0.00 |
December | 0.194554E+12 | 218518.60 | 20-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.253472E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.175339E+12 | 181839.71 | 0.00 | 0.00 | |
Maximum of Months | 0.247733E+12 | 249983.20 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.226639E+11 | 0.613996E+11 | 0.230900E+10 | 0.158812E+11 | 12379742.02 | 0.151750E+11 | 0.269896E+11 | 0.00 | 0.00 | 0.00 | 0.397223E+10 | 0.00 |
February | 0.428574E+11 | 0.195741E+11 | 0.556056E+11 | 0.209511E+10 | 0.132648E+11 | 11196021.66 | 0.868432E+10 | 0.296650E+11 | 0.00 | 0.00 | 0.00 | 0.358158E+10 | 0.00 |
March | 0.509265E+11 | 0.203218E+11 | 0.635880E+11 | 0.240664E+10 | 0.145857E+11 | 12675672.10 | 0.860159E+10 | 0.362372E+11 | 0.00 | 0.00 | 0.00 | 0.407336E+10 | 0.00 |
April | 0.454877E+11 | 0.183581E+11 | 0.594055E+11 | 0.224272E+10 | 0.116538E+11 | 11960507.72 | 0.732961E+09 | 0.462027E+11 | 0.00 | 0.00 | 0.00 | 0.347232E+10 | 0.00 |
May | 0.490872E+11 | 0.177906E+11 | 0.624938E+11 | 0.235782E+10 | 0.156594E+11 | 12527707.06 | 0.00 | 0.801685E+11 | 0.00 | 0.00 | 0.00 | 0.347772E+10 | 0.00 |
June | 0.488499E+11 | 0.165745E+11 | 0.612808E+11 | 0.231841E+10 | 0.164468E+11 | 12231776.97 | 0.00 | 0.859921E+11 | 0.00 | 0.00 | 0.00 | 0.325426E+10 | 0.00 |
July | 0.457251E+11 | 0.174663E+11 | 0.606074E+11 | 0.228147E+10 | 0.161551E+11 | 12256437.81 | 0.00 | 0.907669E+11 | 0.00 | 0.00 | 0.00 | 0.299761E+10 | 0.00 |
August | 0.509265E+11 | 0.184211E+11 | 0.635880E+11 | 0.240664E+10 | 0.173544E+11 | 12675672.10 | 0.00 | 0.917000E+11 | 0.00 | 0.00 | 0.00 | 0.332325E+10 | 0.00 |
September | 0.454877E+11 | 0.191147E+11 | 0.593832E+11 | 0.224140E+10 | 0.145567E+11 | 11960507.72 | 0.00 | 0.769485E+11 | 0.00 | 0.00 | 0.00 | 0.314703E+10 | 0.00 |
October | 0.472479E+11 | 0.211235E+11 | 0.614108E+11 | 0.230966E+10 | 0.152539E+11 | 12379742.02 | 0.317801E+09 | 0.690405E+11 | 0.00 | 0.00 | 0.00 | 0.346438E+10 | 0.00 |
November | 0.466941E+11 | 0.215829E+11 | 0.599069E+11 | 0.224962E+10 | 0.127601E+11 | 12059151.09 | 0.235939E+10 | 0.410680E+11 | 0.00 | 0.00 | 0.00 | 0.363032E+10 | 0.00 |
December | 0.457251E+11 | 0.229611E+11 | 0.605962E+11 | 0.228081E+10 | 0.152270E+11 | 12256437.81 | 0.112740E+11 | 0.326955E+11 | 0.00 | 0.00 | 0.00 | 0.378212E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.235953E+12 | 0.729266E+12 | 0.274993E+11 | 0.178799E+12 | 0.146559E+09 | 0.471451E+11 | 0.707475E+12 | 0.00 | 0.00 | 0.00 | 0.421762E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.165745E+11 | 0.556056E+11 | 0.209511E+10 | 0.116538E+11 | 11196021.66 | 0.00 | 0.269896E+11 | 0.00 | 0.00 | 0.00 | 0.299761E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.229611E+11 | 0.635880E+11 | 0.240664E+10 | 0.173544E+11 | 12675672.10 | 0.151750E+11 | 0.917000E+11 | 0.00 | 0.00 | 0.00 | 0.407336E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 03-JAN-13:09 | 19146.02 | 07-JAN-07:40 | 6.85 | 06-JAN-17:10 | 137766.07 | 09-JAN-07:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 13-FEB-12:09 | 19146.02 | 06-FEB-06:40 | 6.85 | 13-FEB-06:19 | 169246.70 | 06-FEB-07:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 01-MAR-09:09 | 19146.02 | 11-MAR-07:19 | 6.85 | 10-MAR-06:19 | 126889.64 | 13-MAR-06:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 01-APR-07:19 | 17467.25 | 28-APR-15:20 | 6.85 | 01-APR-05:10 | 52177.83 | 11-APR-06:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 06-MAY-07:49 | 18687.02 | 04-MAY-15:39 | 6.85 | 09-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 05-JUN-07:19 | 18729.76 | 28-JUN-15:00 | 6.85 | 04-JUN-14:20 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 05-JUL-12:09 | 19987.51 | 07-JUL-15:00 | 6.85 | 16-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 01-AUG-16:10 | 21602.67 | 30-AUG-15:00 | 6.85 | 05-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 06-SEP-16:10 | 19341.34 | 01-SEP-14:50 | 6.85 | 03-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 27-OCT-16:10 | 21222.26 | 05-OCT-14:00 | 6.85 | 01-OCT-14:50 | 32219.60 | 28-OCT-06:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 14-NOV-17:10 | 17164.25 | 15-NOV-07:19 | 6.85 | 01-NOV-05:10 | 72672.03 | 16-NOV-07:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 04-DEC-12:09 | 19146.02 | 21-DEC-07:19 | 6.85 | 18-DEC-17:10 | 141456.19 | 20-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 17164.25 | 6.85 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 21602.67 | 6.85 | 169246.70 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 47686.59 | 19-JAN-15:09 | 0.00 | 0.00 | 0.00 | 5355.69 | 23-JAN-12:50 | 0.00 |
February | 48552.70 | 24-FEB-13:00 | 0.00 | 0.00 | 0.00 | 5353.35 | 02-FEB-12:30 | 0.00 |
March | 52452.41 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 5127.28 | 01-MAR-12:20 | 0.00 |
April | 78733.22 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 4958.62 | 03-APR-11:00 | 0.00 |
May | 77677.43 | 18-MAY-15:30 | 0.00 | 0.00 | 0.00 | 4594.08 | 01-MAY-11:50 | 0.00 |
June | 87517.88 | 28-JUN-14:09 | 0.00 | 0.00 | 0.00 | 4236.56 | 01-JUN-11:39 | 0.00 |
July | 93294.86 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 4199.03 | 11-JUL-11:50 | 0.00 |
August | 92859.19 | 30-AUG-15:00 | 0.00 | 0.00 | 0.00 | 4217.25 | 31-AUG-11:20 | 0.00 |
September | 82174.77 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 4417.24 | 29-SEP-11:00 | 0.00 |
October | 87378.78 | 05-OCT-14:00 | 0.00 | 0.00 | 0.00 | 4622.63 | 31-OCT-11:20 | 0.00 |
November | 69738.45 | 02-NOV-14:09 | 0.00 | 0.00 | 0.00 | 4989.72 | 30-NOV-12:50 | 0.00 |
December | 58103.19 | 15-DEC-14:30 | 0.00 | 0.00 | 0.00 | 5343.34 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 47686.59 | 0.00 | 0.00 | 0.00 | 4199.03 | 0.00 | ||
Maximum of Months | 93294.86 | 0.00 | 0.00 | 0.00 | 5355.69 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 219407.86 | 09-JAN-07:10 | 16481.06 | 22777.10 | 15013.15 | 1008.91 | 17034.53 | 6.85 | 137766.07 | 7668.53 | 0.00 |
February | 249983.20 | 06-FEB-07:10 | 16481.06 | 22777.10 | 15013.15 | 1008.91 | 18485.43 | 6.85 | 169246.70 | 5312.33 | 0.00 |
March | 208441.09 | 13-MAR-06:10 | 16481.06 | 22777.10 | 15013.15 | 1008.91 | 17034.53 | 6.85 | 126889.64 | 7581.73 | 0.00 |
April | 191928.98 | 28-APR-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 16861.93 | 6.85 | 0.00 | 78733.22 | 0.00 |
May | 192106.57 | 18-MAY-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 18116.78 | 6.85 | 0.00 | 77677.43 | 0.00 |
June | 201065.29 | 28-JUN-14:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 18331.11 | 6.85 | 0.00 | 87397.29 | 0.00 |
July | 208567.35 | 21-JUL-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 19363.45 | 6.85 | 0.00 | 93219.26 | 0.00 |
August | 210457.63 | 30-AUG-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 21602.67 | 6.85 | 0.00 | 92859.19 | 0.00 |
September | 196572.28 | 01-SEP-14:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 19339.46 | 6.85 | 0.00 | 82174.77 | 0.00 |
October | 203957.78 | 05-OCT-14:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 21222.26 | 6.85 | 0.00 | 87378.78 | 0.00 |
November | 181839.71 | 02-NOV-14:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 16500.95 | 6.85 | 0.00 | 69679.49 | 0.00 |
December | 218518.60 | 20-DEC-07:10 | 16481.06 | 22777.10 | 15013.15 | 1008.91 | 16571.52 | 6.85 | 141456.19 | 3552.07 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 181839.71 | 16481.06 | 22777.10 | 0.00 | 1008.91 | 16500.95 | 6.85 | 0.00 | 3552.07 | 0.00 | |
Maximum of Months | 249983.20 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 21602.67 | 6.85 | 169246.70 | 93219.26 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.38 | 0.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 0.17 | 19.24 | 0.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.43 | 0.67 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.00 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.64 | 1.17 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.34 | 0.50 | 19.34 | 2.50 | 25.17 | 2.17 | 26.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.38 | 0.33 | 19.38 | 1.17 | 27.64 | 1.17 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.59 | 0.67 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.08 | 4.00 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.80 | 2.17 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.99 | 4.50 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.65 | 1.67 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.16 | 3.83 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.74 | 0.83 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.67 | 27.96 | 17.67 | 27.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.16 | 4.50 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.24 | 1.67 | 28.24 |
February | 0.17 | 19.39 | 0.17 | 19.39 | 0.67 | 24.90 | 0.67 | 26.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.49 | 0.50 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.11 | 5.00 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.42 | 5.83 | 28.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.94 | 2.33 | 27.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.06 | 2.33 | 28.06 |
Annual Sum or Average | 0.17 | 19.39 | 0.17 | 19.39 | 18.83 | 27.99 | 18.67 | 28.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.39 | 0.17 | 19.39 | 5.83 | 28.42 | 5.83 | 28.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.68 | 0.50 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.47 | 1.33 | 28.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.35 | 2.17 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.60 | 1.67 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.42 | 1.17 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.51 | 2.67 | 28.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.08 | 2.00 | 28.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.67 | 28.14 | 11.50 | 28.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.51 | 2.67 | 28.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.75 | 2.83 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.81 | 3.00 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.48 | 1.67 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.98 | 3.33 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.60 | 0.67 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.83 | 27.75 | 12.83 | 27.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.98 | 3.33 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 19.67 | 4.00 | 19.67 | 2.17 | 21.48 | 2.17 | 22.66 |
February | 2.33 | 19.66 | 2.33 | 19.66 | 0.67 | 20.66 | 0.67 | 21.43 |
March | 2.00 | 19.86 | 2.00 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.61 | 1.33 | 24.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.64 | 5.00 | 24.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 24.86 | 14.17 | 24.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 24.97 | 17.00 | 24.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.58 | 8.50 | 26.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 26.19 | 17.83 | 26.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.69 | 5.83 | 26.69 |
December | 2.00 | 19.06 | 2.00 | 19.06 | 2.83 | 22.74 | 2.83 | 24.27 |
Annual Sum or Average | 10.33 | 19.59 | 10.33 | 19.59 | 75.50 | 24.43 | 75.33 | 25.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.86 | 4.00 | 19.86 | 17.83 | 26.69 | 17.83 | 26.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.07 | 1.17 | 28.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.04 | 1.33 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.37 | 0.33 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.11 | 2.67 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 2.00 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.67 | 27.92 | 8.00 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.11 | 2.67 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.66 | 0.83 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.08 | 3.83 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.83 | 1.67 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.00 | 3.50 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.64 | 1.33 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.11 | 3.33 | 28.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.79 | 0.83 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.33 | 27.97 | 15.33 | 27.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.11 | 3.83 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.23 | 1.83 | 28.23 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 1.00 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.89 | 4.83 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.29 | 6.00 | 28.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.01 | 2.50 | 28.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.12 | 2.67 | 28.12 |
Annual Sum or Average | 0.00 | 0.00 | 19.00 | 28.08 | 18.83 | 28.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.29 | 6.00 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.55 | 0.33 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.29 | 1.17 | 28.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.06 | 2.00 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.20 | 2.83 | 28.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.80 | 2.17 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.50 | 28.02 | 9.50 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.29 | 2.83 | 28.38 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 255.50 | 23.40 | 83.67 | 23.64 | 0.00 | 23.64 |
February | 177.00 | 23.41 | 139.17 | 23.87 | 0.00 | 23.87 |
March | 157.83 | 23.40 | 167.33 | 23.98 | 0.00 | 23.98 |
April | 13.50 | 23.56 | 350.67 | 24.51 | 0.00 | 24.51 |
May | 0.00 | 0.00 | 508.00 | 24.39 | 0.00 | 24.39 |
June | 0.00 | 0.00 | 496.00 | 24.36 | 0.00 | 24.36 |
July | 0.00 | 0.00 | 497.00 | 24.37 | 0.00 | 24.37 |
August | 0.00 | 0.00 | 514.00 | 24.36 | 0.00 | 24.36 |
September | 0.00 | 0.00 | 485.00 | 24.35 | 0.00 | 24.35 |
October | 6.83 | 23.68 | 449.50 | 24.43 | 0.00 | 24.43 |
November | 61.50 | 23.48 | 276.33 | 24.32 | 0.00 | 24.32 |
December | 161.33 | 23.38 | 158.83 | 23.95 | 0.00 | 23.95 |
Annual Sum or Average | 833.50 | 23.41 | 4125.50 | 24.25 | 0.00 | 24.25 |
Minimum of Months | 0.00 | 0.00 | 83.67 | 23.64 | 0.00 | 23.64 |
Maximum of Months | 255.50 | 23.68 | 514.00 | 24.51 | 0.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 429.17 | 22.36 | 28.50 | 22.47 | 0.83 | 22.47 |
February | 347.33 | 22.47 | 57.00 | 22.66 | 6.00 | 22.63 |
March | 356.67 | 22.69 | 78.33 | 22.96 | 0.33 | 22.95 |
April | 171.33 | 23.18 | 174.17 | 23.76 | 0.00 | 23.76 |
May | 10.50 | 23.18 | 412.33 | 24.24 | 0.00 | 24.24 |
June | 0.83 | 23.23 | 422.17 | 24.24 | 0.00 | 24.24 |
July | 5.83 | 23.18 | 417.67 | 24.25 | 0.00 | 24.25 |
August | 2.67 | 23.22 | 439.67 | 24.24 | 0.00 | 24.24 |
September | 12.67 | 23.18 | 358.50 | 24.23 | 0.00 | 24.23 |
October | 63.33 | 23.07 | 319.00 | 24.11 | 0.00 | 24.11 |
November | 269.00 | 23.01 | 109.50 | 23.37 | 0.00 | 23.37 |
December | 392.83 | 22.59 | 63.83 | 22.82 | 0.00 | 22.82 |
Annual Sum or Average | 2062.17 | 22.67 | 2880.67 | 23.59 | 7.17 | 23.59 |
Minimum of Months | 0.83 | 22.36 | 28.50 | 22.47 | 0.00 | 22.47 |
Maximum of Months | 429.17 | 23.23 | 439.67 | 24.25 | 6.00 | 24.25 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.83 | 21.74 | 54.17 | 21.69 | 39.67 | 21.59 |
February | 389.50 | 21.92 | 69.17 | 21.96 | 32.50 | 21.84 |
March | 405.17 | 22.19 | 80.00 | 22.34 | 18.83 | 22.25 |
April | 226.17 | 22.71 | 160.33 | 23.34 | 0.00 | 23.34 |
May | 34.00 | 23.04 | 382.17 | 24.16 | 0.00 | 24.16 |
June | 11.83 | 23.05 | 403.67 | 24.20 | 0.00 | 24.20 |
July | 12.50 | 23.01 | 408.00 | 24.22 | 0.00 | 24.22 |
August | 17.33 | 23.02 | 402.17 | 24.19 | 0.00 | 24.19 |
September | 65.00 | 22.97 | 318.67 | 24.03 | 0.00 | 24.03 |
October | 123.17 | 22.68 | 274.17 | 23.77 | 0.00 | 23.77 |
November | 369.33 | 22.42 | 66.83 | 22.66 | 1.83 | 22.65 |
December | 437.00 | 21.92 | 56.00 | 21.97 | 24.00 | 21.88 |
Annual Sum or Average | 2557.83 | 22.17 | 2675.33 | 23.13 | 116.83 | 23.07 |
Minimum of Months | 11.83 | 21.74 | 54.17 | 21.69 | 0.00 | 21.59 |
Maximum of Months | 466.83 | 23.05 | 408.00 | 24.22 | 39.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 477.00 | 21.00 | 186.33 | 20.84 | 172.50 | 20.70 |
February | 409.67 | 21.14 | 129.17 | 21.05 | 99.50 | 20.85 |
March | 437.67 | 21.50 | 128.67 | 21.55 | 75.17 | 21.39 |
April | 285.83 | 22.20 | 164.33 | 22.82 | 19.50 | 22.82 |
May | 76.00 | 23.63 | 403.17 | 24.20 | 26.17 | 24.26 |
June | 37.83 | 23.77 | 422.17 | 24.27 | 13.67 | 24.31 |
July | 56.50 | 24.43 | 429.50 | 24.41 | 31.33 | 24.49 |
August | 69.67 | 23.62 | 421.00 | 24.20 | 27.50 | 24.24 |
September | 126.50 | 23.16 | 339.17 | 23.97 | 29.67 | 24.02 |
October | 196.17 | 22.48 | 280.17 | 23.45 | 32.33 | 23.47 |
November | 408.33 | 21.63 | 90.33 | 21.76 | 38.67 | 21.64 |
December | 458.83 | 21.25 | 142.67 | 21.18 | 118.17 | 21.05 |
Annual Sum or Average | 3040.00 | 21.74 | 3136.67 | 22.68 | 684.17 | 22.54 |
Minimum of Months | 37.83 | 21.00 | 90.33 | 20.84 | 13.67 | 20.70 |
Maximum of Months | 477.00 | 24.43 | 429.50 | 24.41 | 172.50 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 470.17 | 21.04 | 135.00 | 20.93 | 120.00 | 20.78 |
February | 391.83 | 21.21 | 109.33 | 21.21 | 68.00 | 21.02 |
March | 400.17 | 21.48 | 147.67 | 21.77 | 59.83 | 21.61 |
April | 247.17 | 22.02 | 205.00 | 22.94 | 20.00 | 22.96 |
May | 130.50 | 23.37 | 378.17 | 24.10 | 38.83 | 24.23 |
June | 87.17 | 23.23 | 391.00 | 24.11 | 20.17 | 24.20 |
July | 106.00 | 23.84 | 391.33 | 24.29 | 41.00 | 24.44 |
August | 117.50 | 23.09 | 384.50 | 24.01 | 31.50 | 24.09 |
September | 166.33 | 22.92 | 312.17 | 23.83 | 38.50 | 23.97 |
October | 216.33 | 22.31 | 277.33 | 23.36 | 32.00 | 23.42 |
November | 392.50 | 21.64 | 78.83 | 21.87 | 22.33 | 21.78 |
December | 459.67 | 21.29 | 103.33 | 21.23 | 84.33 | 21.11 |
Annual Sum or Average | 3185.33 | 21.81 | 2913.67 | 22.74 | 576.50 | 22.69 |
Minimum of Months | 87.17 | 21.04 | 78.83 | 20.93 | 20.00 | 20.78 |
Maximum of Months | 470.17 | 23.84 | 391.33 | 24.29 | 120.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.50 | 21.38 | 182.50 | 21.75 | 95.67 | 21.57 |
February | 313.00 | 21.42 | 168.67 | 21.94 | 58.50 | 21.74 |
March | 350.83 | 21.47 | 174.83 | 21.92 | 60.33 | 21.75 |
April | 264.33 | 22.04 | 184.50 | 22.88 | 18.33 | 22.88 |
May | 115.00 | 23.01 | 357.17 | 23.97 | 23.00 | 24.02 |
June | 80.83 | 22.89 | 377.83 | 24.01 | 11.00 | 24.04 |
July | 87.00 | 23.35 | 388.67 | 24.14 | 24.67 | 24.20 |
August | 103.83 | 23.21 | 391.00 | 24.05 | 28.33 | 24.11 |
September | 157.00 | 23.33 | 329.67 | 24.03 | 45.00 | 24.18 |
October | 183.17 | 23.12 | 320.33 | 23.95 | 49.67 | 24.11 |
November | 264.50 | 21.87 | 217.83 | 22.89 | 28.50 | 22.85 |
December | 328.17 | 21.57 | 205.67 | 22.22 | 74.67 | 22.09 |
Annual Sum or Average | 2603.17 | 22.04 | 3298.67 | 23.12 | 517.67 | 23.06 |
Minimum of Months | 80.83 | 21.38 | 168.67 | 21.75 | 11.00 | 21.57 |
Maximum of Months | 355.50 | 23.35 | 391.00 | 24.14 | 95.67 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.67 | 21.03 | 172.33 | 20.96 | 147.50 | 20.81 |
February | 389.83 | 21.09 | 135.67 | 21.17 | 85.00 | 20.98 |
March | 418.00 | 21.32 | 134.00 | 21.48 | 69.00 | 21.33 |
April | 312.00 | 21.86 | 154.17 | 22.57 | 23.00 | 22.61 |
May | 167.67 | 22.55 | 311.00 | 23.65 | 26.00 | 23.75 |
June | 126.00 | 22.72 | 342.67 | 23.83 | 20.83 | 23.92 |
July | 132.83 | 22.86 | 335.33 | 23.88 | 28.17 | 23.99 |
August | 141.33 | 22.56 | 342.00 | 23.72 | 25.00 | 23.78 |
September | 206.67 | 22.48 | 257.67 | 23.43 | 32.83 | 23.56 |
October | 262.00 | 22.22 | 225.00 | 23.11 | 36.33 | 23.20 |
November | 390.33 | 21.39 | 102.50 | 21.67 | 37.33 | 21.55 |
December | 435.17 | 21.18 | 141.50 | 21.22 | 102.67 | 21.08 |
Annual Sum or Average | 3448.50 | 21.65 | 2653.83 | 22.46 | 633.67 | 22.38 |
Minimum of Months | 126.00 | 21.03 | 102.50 | 20.96 | 20.83 | 20.81 |
Maximum of Months | 466.67 | 22.86 | 342.67 | 23.88 | 147.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.83 | 21.40 | 96.17 | 21.31 | 85.17 | 21.20 |
February | 418.33 | 21.52 | 79.67 | 21.38 | 67.83 | 21.22 |
March | 454.00 | 21.77 | 85.17 | 21.77 | 52.50 | 21.65 |
April | 299.17 | 22.54 | 114.50 | 22.97 | 11.67 | 23.02 |
May | 20.83 | 24.94 | 421.33 | 24.34 | 13.50 | 24.39 |
June | 6.67 | 24.26 | 454.83 | 24.30 | 3.17 | 24.31 |
July | 15.33 | 25.69 | 472.00 | 24.44 | 14.67 | 24.48 |
August | 12.67 | 25.73 | 494.50 | 24.36 | 12.67 | 24.40 |
September | 19.17 | 25.25 | 426.33 | 24.36 | 16.50 | 24.40 |
October | 101.33 | 22.99 | 355.67 | 23.99 | 13.50 | 24.03 |
November | 350.67 | 22.18 | 80.83 | 22.52 | 2.67 | 22.51 |
December | 432.33 | 21.67 | 80.83 | 21.76 | 44.00 | 21.69 |
Annual Sum or Average | 2607.33 | 21.94 | 3161.83 | 23.06 | 337.83 | 22.99 |
Minimum of Months | 6.67 | 21.40 | 79.67 | 21.31 | 2.67 | 21.20 |
Maximum of Months | 476.83 | 25.73 | 494.50 | 24.44 | 85.17 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.83 | 21.43 | 61.00 | 21.40 | 48.67 | 21.31 |
February | 403.00 | 21.54 | 60.83 | 21.50 | 42.83 | 21.38 |
March | 412.17 | 21.69 | 104.17 | 21.94 | 35.33 | 21.84 |
April | 265.17 | 22.21 | 158.83 | 22.98 | 11.50 | 23.03 |
May | 101.50 | 23.36 | 367.17 | 24.16 | 23.00 | 24.27 |
June | 54.33 | 23.05 | 395.17 | 24.15 | 7.00 | 24.18 |
July | 57.33 | 24.26 | 404.33 | 24.39 | 25.33 | 24.49 |
August | 48.33 | 23.84 | 415.50 | 24.28 | 16.33 | 24.35 |
September | 93.33 | 23.56 | 355.50 | 24.20 | 25.17 | 24.32 |
October | 150.00 | 22.70 | 300.50 | 23.79 | 16.83 | 23.86 |
November | 352.50 | 22.05 | 83.00 | 22.47 | 1.17 | 22.47 |
December | 442.00 | 21.66 | 47.50 | 21.69 | 33.00 | 21.64 |
Annual Sum or Average | 2852.50 | 22.00 | 2753.50 | 23.04 | 286.17 | 23.03 |
Minimum of Months | 48.33 | 21.43 | 47.50 | 21.40 | 1.17 | 21.31 |
Maximum of Months | 472.83 | 24.26 | 415.50 | 24.39 | 48.67 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 348.50 | 21.86 | 129.67 | 22.44 | 35.33 | 22.40 |
February | 311.50 | 21.84 | 139.33 | 22.45 | 25.67 | 22.37 |
March | 367.33 | 21.79 | 143.50 | 22.22 | 43.00 | 22.14 |
April | 275.67 | 22.41 | 189.17 | 23.12 | 27.83 | 23.17 |
May | 114.83 | 23.69 | 406.00 | 24.11 | 79.50 | 24.10 |
June | 92.67 | 23.79 | 424.17 | 24.14 | 77.00 | 24.12 |
July | 112.17 | 24.16 | 455.83 | 24.29 | 101.83 | 24.29 |
August | 102.83 | 24.25 | 489.33 | 24.32 | 100.17 | 24.32 |
September | 118.67 | 24.52 | 440.50 | 24.40 | 111.67 | 24.44 |
October | 132.33 | 24.13 | 418.17 | 24.43 | 81.83 | 24.53 |
November | 203.67 | 22.65 | 267.33 | 23.69 | 32.00 | 23.76 |
December | 291.67 | 22.02 | 206.33 | 22.94 | 43.50 | 22.97 |
Annual Sum or Average | 2471.83 | 22.60 | 3709.33 | 23.60 | 759.33 | 23.63 |
Minimum of Months | 92.67 | 21.79 | 129.67 | 22.22 | 25.67 | 22.14 |
Maximum of Months | 367.33 | 24.52 | 489.33 | 24.43 | 111.67 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 464.50 | 21.44 | 75.00 | 21.47 | 52.33 | 21.38 |
February | 396.50 | 21.47 | 92.83 | 21.55 | 50.33 | 21.41 |
March | 441.00 | 21.64 | 78.17 | 21.71 | 43.00 | 21.60 |
April | 321.67 | 22.13 | 122.17 | 22.76 | 11.33 | 22.83 |
May | 129.00 | 22.85 | 309.33 | 23.89 | 16.50 | 23.96 |
June | 80.83 | 22.85 | 356.17 | 24.02 | 8.17 | 24.06 |
July | 71.33 | 23.17 | 367.50 | 24.14 | 14.17 | 24.19 |
August | 48.00 | 23.38 | 410.33 | 24.18 | 11.50 | 24.23 |
September | 96.17 | 23.32 | 333.33 | 24.07 | 21.83 | 24.17 |
October | 154.50 | 22.74 | 279.17 | 23.74 | 19.00 | 23.83 |
November | 353.83 | 21.87 | 81.50 | 22.30 | 1.17 | 22.29 |
December | 416.50 | 21.60 | 78.67 | 21.78 | 34.17 | 21.72 |
Annual Sum or Average | 2973.83 | 21.92 | 2584.17 | 22.90 | 283.50 | 22.87 |
Minimum of Months | 48.00 | 21.44 | 75.00 | 21.47 | 1.17 | 21.38 |
Maximum of Months | 464.50 | 23.38 | 410.33 | 24.18 | 52.33 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.83 | 21.26 | 134.83 | 21.17 | 116.17 | 21.04 |
February | 403.00 | 21.45 | 106.50 | 21.39 | 72.00 | 21.20 |
March | 427.83 | 21.79 | 114.17 | 21.87 | 55.33 | 21.73 |
April | 250.67 | 22.57 | 174.33 | 23.21 | 12.00 | 23.25 |
May | 24.50 | 25.16 | 440.67 | 24.38 | 20.83 | 24.43 |
June | 14.50 | 24.91 | 464.00 | 24.33 | 10.67 | 24.36 |
July | 29.33 | 25.20 | 462.33 | 24.46 | 23.00 | 24.52 |
August | 31.00 | 24.57 | 462.17 | 24.32 | 21.83 | 24.36 |
September | 68.00 | 23.74 | 379.67 | 24.23 | 25.67 | 24.27 |
October | 140.83 | 22.83 | 320.00 | 23.82 | 22.83 | 23.86 |
November | 380.33 | 22.03 | 83.50 | 22.29 | 13.50 | 22.24 |
December | 440.17 | 21.52 | 105.33 | 21.55 | 72.33 | 21.44 |
Annual Sum or Average | 2678.00 | 21.93 | 3247.50 | 23.00 | 466.17 | 22.91 |
Minimum of Months | 14.50 | 21.26 | 83.50 | 21.17 | 10.67 | 21.04 |
Maximum of Months | 467.83 | 25.20 | 464.00 | 24.46 | 116.17 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.00 | 21.19 | 92.33 | 21.12 | 79.83 | 21.00 |
February | 344.17 | 21.35 | 69.17 | 21.29 | 50.17 | 21.13 |
March | 348.00 | 21.55 | 95.17 | 21.78 | 39.33 | 21.65 |
April | 233.83 | 22.15 | 137.67 | 22.97 | 14.17 | 23.05 |
May | 118.50 | 23.41 | 296.83 | 24.18 | 31.50 | 24.32 |
June | 80.83 | 23.26 | 311.33 | 24.14 | 16.83 | 24.23 |
July | 93.83 | 23.82 | 311.67 | 24.34 | 33.00 | 24.50 |
August | 105.00 | 23.08 | 297.67 | 24.04 | 21.83 | 24.13 |
September | 151.00 | 22.98 | 245.00 | 23.88 | 31.17 | 24.03 |
October | 196.17 | 22.46 | 211.33 | 23.45 | 23.50 | 23.55 |
November | 333.00 | 21.76 | 63.00 | 22.08 | 10.00 | 22.04 |
December | 393.67 | 21.45 | 63.83 | 21.40 | 55.00 | 21.31 |
Annual Sum or Average | 2801.00 | 21.94 | 2195.00 | 22.83 | 406.33 | 22.82 |
Minimum of Months | 80.83 | 21.19 | 63.00 | 21.12 | 10.00 | 21.00 |
Maximum of Months | 403.00 | 23.82 | 311.67 | 24.34 | 79.83 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 330.33 | 21.71 | 148.33 | 22.25 | 52.00 | 22.14 |
February | 292.83 | 21.77 | 156.83 | 22.35 | 38.17 | 22.20 |
March | 333.17 | 21.75 | 156.00 | 22.22 | 39.50 | 22.08 |
April | 238.00 | 22.37 | 193.67 | 23.22 | 11.50 | 23.26 |
May | 73.17 | 23.41 | 387.33 | 24.15 | 18.00 | 24.20 |
June | 43.50 | 23.37 | 398.33 | 24.18 | 9.50 | 24.20 |
July | 49.67 | 23.84 | 410.67 | 24.28 | 19.00 | 24.33 |
August | 56.33 | 23.58 | 415.33 | 24.22 | 18.50 | 24.26 |
September | 110.83 | 23.92 | 359.33 | 24.30 | 42.83 | 24.43 |
October | 139.83 | 23.66 | 349.50 | 24.25 | 46.17 | 24.42 |
November | 227.67 | 22.27 | 227.17 | 23.37 | 14.50 | 23.41 |
December | 299.17 | 21.89 | 194.83 | 22.66 | 49.17 | 22.61 |
Annual Sum or Average | 2194.50 | 22.30 | 3397.33 | 23.45 | 358.83 | 23.44 |
Minimum of Months | 43.50 | 21.71 | 148.33 | 22.22 | 9.50 | 22.08 |
Maximum of Months | 333.17 | 23.92 | 415.33 | 24.30 | 52.00 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 462.00 | 21.25 | 121.00 | 21.25 | 94.67 | 21.13 |
February | 390.17 | 21.31 | 109.17 | 21.42 | 59.67 | 21.25 |
March | 418.83 | 21.52 | 107.67 | 21.67 | 49.33 | 21.55 |
April | 304.33 | 22.08 | 145.50 | 22.81 | 12.67 | 22.88 |
May | 136.00 | 22.82 | 324.67 | 23.86 | 20.83 | 23.94 |
June | 101.33 | 22.98 | 351.00 | 23.99 | 17.33 | 24.07 |
July | 105.33 | 23.06 | 347.33 | 24.02 | 21.67 | 24.11 |
August | 108.67 | 22.75 | 357.00 | 23.89 | 16.33 | 23.94 |
September | 167.17 | 22.76 | 274.50 | 23.70 | 27.67 | 23.82 |
October | 230.17 | 22.47 | 233.33 | 23.39 | 26.83 | 23.50 |
November | 378.67 | 21.66 | 86.00 | 22.04 | 12.00 | 22.00 |
December | 425.33 | 21.38 | 105.17 | 21.50 | 63.50 | 21.40 |
Annual Sum or Average | 3228.00 | 21.83 | 2562.33 | 22.72 | 422.50 | 22.68 |
Minimum of Months | 101.33 | 21.25 | 86.00 | 21.25 | 12.00 | 21.13 |
Maximum of Months | 462.00 | 23.06 | 357.00 | 24.02 | 94.67 | 24.11 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.82670 | 34.98248 | 0.27723 | 7.13323 |
February | 454.00000 | 23.91184 | 38.38270 | 0.32461 | 7.81964 |
March | 514.00000 | 23.98566 | 38.43484 | 0.35578 | 8.21340 |
April | 485.00000 | 24.35064 | 43.47437 | 0.49658 | 10.54241 |
May | 508.00000 | 24.39385 | 46.91359 | -0.2726 | 7.13175 |
June | 496.00000 | 24.35578 | 46.89984 | -0.2783 | 7.13845 |
July | 497.00000 | 24.37324 | 46.89048 | -0.2739 | 7.10954 |
August | 514.00000 | 24.35966 | 46.90230 | -0.2715 | 7.08424 |
September | 485.00000 | 24.35230 | 46.90322 | -0.2818 | 7.14323 |
October | 502.00000 | 24.38387 | 44.42542 | 0.54352 | 11.54445 |
November | 489.00000 | 24.21871 | 40.54361 | 0.44378 | 9.51051 |
December | 497.00000 | 23.99291 | 37.60814 | 0.34840 | 8.16843 |
Annual Sum or Average | 5943.00000 | 24.21026 | 42.72270 | 0.11516 | 8.20700 |
Minimum of Months | 454.00000 | 23.82670 | 34.98248 | -0.2818 | 7.08424 |
Maximum of Months | 514.00000 | 24.39385 | 46.91359 | 0.54352 | 11.54445 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60413 | 37.86456 | -0.0113 | 6.33006 |
February | 454.00000 | 22.83416 | 41.14970 | 0.07074 | 6.68402 |
March | 514.00000 | 23.11032 | 40.72222 | 0.14371 | 6.72246 |
April | 485.00000 | 23.78596 | 45.34203 | 0.35484 | 8.13072 |
May | 508.00000 | 24.14594 | 48.11131 | -0.3732 | 8.29007 |
June | 496.00000 | 24.15582 | 47.97357 | -0.3640 | 8.12962 |
July | 497.00000 | 24.16123 | 47.97353 | -0.3624 | 8.17037 |
August | 514.00000 | 24.15705 | 48.06753 | -0.3618 | 8.11299 |
September | 485.00000 | 24.08610 | 48.24683 | -0.3943 | 8.66896 |
October | 502.00000 | 24.02645 | 45.80140 | 0.44284 | 9.62400 |
November | 489.00000 | 23.48387 | 42.52833 | 0.25412 | 7.14507 |
December | 497.00000 | 22.90292 | 40.44151 | 0.08589 | 6.56869 |
Annual Sum or Average | 5943.00000 | 23.62621 | 44.53725 | -0.0447 | 7.71995 |
Minimum of Months | 454.00000 | 22.60413 | 37.86456 | -0.3943 | 6.33006 |
Maximum of Months | 514.00000 | 24.16123 | 48.24683 | 0.44284 | 9.62400 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.88069 | 38.56686 | -0.1833 | 7.54587 |
February | 454.00000 | 22.18737 | 41.87318 | -0.0758 | 7.42229 |
March | 514.00000 | 22.56022 | 41.21197 | 0.02359 | 7.06869 |
April | 485.00000 | 23.42990 | 45.45424 | 0.28772 | 7.79651 |
May | 508.00000 | 24.03664 | 48.40810 | -0.3739 | 8.49097 |
June | 496.00000 | 24.08507 | 48.13204 | -0.3488 | 8.01737 |
July | 497.00000 | 24.11190 | 48.15270 | -0.3426 | 7.97553 |
August | 514.00000 | 24.06256 | 48.36655 | -0.3599 | 8.20253 |
September | 485.00000 | 23.91832 | 48.76717 | -0.4235 | 9.43444 |
October | 502.00000 | 23.73637 | 46.25077 | 0.39005 | 9.21618 |
November | 489.00000 | 22.78624 | 43.45173 | 0.09850 | 6.73007 |
December | 497.00000 | 22.15775 | 41.34341 | -0.0879 | 7.15557 |
Annual Sum or Average | 5943.00000 | 23.25359 | 45.01462 | -0.1175 | 7.92392 |
Minimum of Months | 454.00000 | 21.88069 | 38.56686 | -0.4235 | 6.73007 |
Maximum of Months | 514.00000 | 24.11190 | 48.76717 | 0.39005 | 9.43444 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.13151 | 42.04998 | -0.3822 | 10.79140 |
February | 454.00000 | 21.39683 | 43.92099 | -0.2712 | 10.28166 |
March | 514.00000 | 21.84151 | 43.35008 | -0.1454 | 8.78313 |
April | 485.00000 | 22.91020 | 48.36606 | 0.19983 | 8.08817 |
May | 508.00000 | 24.05284 | 50.98525 | -0.2952 | 8.10380 |
June | 496.00000 | 24.13486 | 49.70426 | -0.2511 | 7.37197 |
July | 497.00000 | 24.22872 | 50.69013 | -0.2201 | 7.43454 |
August | 514.00000 | 24.06748 | 51.24346 | -0.2794 | 7.92130 |
September | 485.00000 | 23.84635 | 52.33566 | -0.3812 | 9.90092 |
October | 502.00000 | 23.43177 | 50.20385 | 0.36616 | 10.10716 |
November | 489.00000 | 21.98986 | 46.16374 | -0.0759 | 7.74104 |
December | 497.00000 | 21.44300 | 44.85798 | -0.2671 | 9.42357 |
Annual Sum or Average | 5943.00000 | 22.88418 | 47.84255 | -0.1668 | 8.81824 |
Minimum of Months | 454.00000 | 21.13151 | 42.04998 | -0.3822 | 7.37197 |
Maximum of Months | 514.00000 | 24.22872 | 52.33566 | 0.36616 | 10.79140 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.21751 | 41.60939 | -0.3211 | 9.76576 |
February | 454.00000 | 21.54413 | 43.39119 | -0.1976 | 9.32597 |
March | 514.00000 | 22.03727 | 42.60325 | -0.0607 | 8.84010 |
April | 485.00000 | 22.97770 | 47.81895 | 0.26301 | 9.15902 |
May | 508.00000 | 23.88360 | 50.85187 | -0.2750 | 9.40195 |
June | 496.00000 | 23.94473 | 49.77639 | -0.2406 | 8.33748 |
July | 497.00000 | 24.02529 | 50.61337 | -0.2134 | 8.70309 |
August | 514.00000 | 23.83720 | 51.25696 | -0.2869 | 9.20809 |
September | 485.00000 | 23.61244 | 52.24931 | -0.3914 | 11.90901 |
October | 502.00000 | 23.27740 | 49.94203 | 0.37749 | 10.82877 |
November | 489.00000 | 22.07907 | 45.63227 | -0.0164 | 7.47913 |
December | 497.00000 | 21.46087 | 44.52561 | -0.2299 | 8.83694 |
Annual Sum or Average | 5943.00000 | 22.83458 | 47.54430 | -0.1329 | 9.31406 |
Minimum of Months | 454.00000 | 21.21751 | 41.60939 | -0.3914 | 7.47913 |
Maximum of Months | 514.00000 | 24.02529 | 52.24931 | 0.37749 | 11.90901 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.23817 | 39.21893 | -0.0587 | 10.44252 |
February | 454.00000 | 22.29866 | 41.46200 | -0.0048 | 10.31028 |
March | 514.00000 | 22.29424 | 41.92092 | -0.0060 | 9.38957 |
April | 485.00000 | 22.95245 | 47.85877 | 0.23574 | 8.88848 |
May | 508.00000 | 23.82526 | 51.34044 | -0.3530 | 9.44140 |
June | 496.00000 | 23.89954 | 50.21038 | -0.3230 | 8.64165 |
July | 497.00000 | 23.99492 | 51.07202 | -0.2861 | 8.43720 |
August | 514.00000 | 23.91843 | 51.24659 | -0.2980 | 8.73604 |
September | 485.00000 | 23.80962 | 51.78922 | -0.3437 | 10.73359 |
October | 502.00000 | 23.73412 | 48.58608 | 0.49465 | 13.11846 |
November | 489.00000 | 22.98398 | 43.18418 | 0.21404 | 10.12832 |
December | 497.00000 | 22.49652 | 41.81117 | 0.04207 | 10.62401 |
Annual Sum or Average | 5943.00000 | 23.21006 | 46.67416 | -0.0586 | 9.90247 |
Minimum of Months | 454.00000 | 22.23817 | 39.21893 | -0.3530 | 8.43720 |
Maximum of Months | 514.00000 | 23.99492 | 51.78922 | 0.49465 | 13.11846 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.24251 | 41.49488 | -0.3203 | 10.31870 |
February | 454.00000 | 21.50080 | 43.36162 | -0.2099 | 10.16923 |
March | 514.00000 | 21.78308 | 43.15768 | -0.1211 | 8.93686 |
April | 485.00000 | 22.60172 | 48.66848 | 0.18586 | 8.83187 |
May | 508.00000 | 23.48635 | 52.02462 | -0.4056 | 11.76583 |
June | 496.00000 | 23.64830 | 50.68907 | -0.3397 | 10.41641 |
July | 497.00000 | 23.67077 | 51.63481 | -0.3358 | 10.35910 |
August | 514.00000 | 23.57681 | 51.96273 | -0.3645 | 10.66295 |
September | 485.00000 | 23.25546 | 53.17968 | -0.4937 | 14.11958 |
October | 502.00000 | 23.00832 | 50.58731 | 0.32527 | 10.19655 |
November | 489.00000 | 21.91078 | 45.97022 | -0.0528 | 8.03530 |
December | 497.00000 | 21.50996 | 44.30846 | -0.2157 | 9.37351 |
Annual Sum or Average | 5943.00000 | 22.60825 | 48.11261 | -0.1962 | 10.26438 |
Minimum of Months | 454.00000 | 21.24251 | 41.49488 | -0.4937 | 8.03530 |
Maximum of Months | 514.00000 | 23.67077 | 53.17968 | 0.32527 | 14.11958 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.51628 | 41.34621 | -0.2703 | 8.44034 |
February | 454.00000 | 21.69687 | 43.92800 | -0.1985 | 8.44702 |
March | 514.00000 | 22.01271 | 43.86769 | -0.1101 | 7.52642 |
April | 485.00000 | 23.06062 | 48.82730 | 0.20759 | 7.26612 |
May | 508.00000 | 24.15516 | 49.99332 | -0.3185 | 7.82357 |
June | 496.00000 | 24.22820 | 48.74623 | -0.2741 | 7.10953 |
July | 497.00000 | 24.34955 | 49.13824 | -0.2249 | 6.86796 |
August | 514.00000 | 24.29820 | 49.12992 | -0.2339 | 6.80906 |
September | 485.00000 | 24.21442 | 49.85513 | -0.2865 | 7.45354 |
October | 502.00000 | 23.91817 | 48.16024 | 0.46329 | 10.63210 |
November | 489.00000 | 22.66051 | 45.42015 | 0.08921 | 6.95049 |
December | 497.00000 | 21.95649 | 43.84089 | -0.1252 | 7.75969 |
Annual Sum or Average | 5943.00000 | 23.18253 | 46.86743 | -0.1071 | 7.75471 |
Minimum of Months | 454.00000 | 21.51628 | 41.34621 | -0.3185 | 6.80906 |
Maximum of Months | 514.00000 | 24.34955 | 49.99332 | 0.46329 | 10.63210 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.57523 | 40.80501 | -0.2101 | 7.64477 |
February | 454.00000 | 21.77240 | 43.37626 | -0.1346 | 7.60497 |
March | 514.00000 | 22.14720 | 42.92890 | -0.0328 | 7.64744 |
April | 485.00000 | 23.01202 | 48.27324 | 0.25325 | 8.18894 |
May | 508.00000 | 23.93283 | 49.91381 | -0.3080 | 8.98834 |
June | 496.00000 | 23.99534 | 48.88452 | -0.2724 | 7.94584 |
July | 497.00000 | 24.12241 | 49.10449 | -0.2221 | 7.82100 |
August | 514.00000 | 24.05928 | 49.18885 | -0.2409 | 7.67728 |
September | 485.00000 | 23.94444 | 49.85282 | -0.3032 | 8.98670 |
October | 502.00000 | 23.64406 | 48.05035 | 0.45464 | 11.06763 |
November | 489.00000 | 22.58227 | 44.98130 | 0.12027 | 7.06890 |
December | 497.00000 | 21.88004 | 43.54249 | -0.1052 | 7.29584 |
Annual Sum or Average | 5943.00000 | 23.06483 | 46.58964 | -0.0839 | 8.16597 |
Minimum of Months | 454.00000 | 21.57523 | 40.80501 | -0.3080 | 7.06890 |
Maximum of Months | 514.00000 | 24.12241 | 49.91381 | 0.45464 | 11.06763 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.62460 | 39.37006 | 0.08140 | 8.91794 |
February | 454.00000 | 22.62134 | 43.29181 | 0.10408 | 8.92042 |
March | 514.00000 | 22.45465 | 44.04184 | 0.05109 | 8.36224 |
April | 485.00000 | 23.12370 | 51.02117 | 0.27121 | 8.39644 |
May | 508.00000 | 23.99911 | 56.96538 | -0.3108 | 7.96344 |
June | 496.00000 | 24.06632 | 56.47095 | -0.2786 | 7.31821 |
July | 497.00000 | 24.22377 | 57.28781 | -0.2082 | 6.77215 |
August | 514.00000 | 24.28189 | 56.85385 | -0.1594 | 6.38102 |
September | 485.00000 | 24.26118 | 56.48094 | -0.1691 | 7.04527 |
October | 502.00000 | 24.24651 | 50.71817 | 0.63707 | 15.26913 |
November | 489.00000 | 23.61771 | 44.71905 | 0.40466 | 10.97563 |
December | 497.00000 | 22.96780 | 42.49362 | 0.20326 | 10.10955 |
Annual Sum or Average | 5943.00000 | 23.54625 | 50.02266 | 0.05068 | 8.86616 |
Minimum of Months | 454.00000 | 22.45465 | 39.37006 | -0.3108 | 6.38102 |
Maximum of Months | 514.00000 | 24.28189 | 57.28781 | 0.63707 | 15.26913 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.63310 | 40.58572 | -0.2012 | 7.88298 |
February | 454.00000 | 21.78988 | 43.19800 | -0.1329 | 8.18172 |
March | 514.00000 | 21.95694 | 43.39710 | -0.0803 | 7.47187 |
April | 485.00000 | 22.77612 | 48.83307 | 0.20274 | 7.92475 |
May | 508.00000 | 23.67815 | 50.78502 | -0.4028 | 10.42126 |
June | 496.00000 | 23.85292 | 49.44614 | -0.3311 | 8.98848 |
July | 497.00000 | 23.93350 | 49.77503 | -0.3015 | 8.59333 |
August | 514.00000 | 23.98797 | 49.47584 | -0.2677 | 7.91754 |
September | 485.00000 | 23.81246 | 50.25076 | -0.3445 | 9.47469 |
October | 502.00000 | 23.57799 | 48.23250 | 0.44163 | 10.74542 |
November | 489.00000 | 22.43559 | 45.28421 | 0.08890 | 7.11401 |
December | 497.00000 | 21.96752 | 43.21321 | -0.0806 | 7.61710 |
Annual Sum or Average | 5943.00000 | 22.95862 | 46.89117 | -0.1182 | 8.53146 |
Minimum of Months | 454.00000 | 21.63310 | 40.58572 | -0.4028 | 7.11401 |
Maximum of Months | 514.00000 | 23.98797 | 50.78502 | 0.44163 | 10.74542 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.43180 | 41.84408 | -0.2929 | 9.16943 |
February | 454.00000 | 21.71870 | 43.77379 | -0.1872 | 9.08507 |
March | 514.00000 | 22.13739 | 43.23513 | -0.0734 | 7.87809 |
April | 485.00000 | 23.24722 | 48.13875 | 0.26411 | 7.97136 |
May | 508.00000 | 24.20853 | 50.42178 | -0.2771 | 7.39514 |
June | 496.00000 | 24.25066 | 49.21738 | -0.2482 | 6.93171 |
July | 497.00000 | 24.33980 | 50.14152 | -0.2181 | 7.00530 |
August | 514.00000 | 24.20993 | 50.51811 | -0.2650 | 7.27537 |
September | 485.00000 | 24.08113 | 51.51564 | -0.3322 | 8.37366 |
October | 502.00000 | 23.73552 | 49.51692 | 0.42166 | 10.29998 |
November | 489.00000 | 22.44295 | 45.65777 | 0.03223 | 7.14351 |
December | 497.00000 | 21.78344 | 44.54708 | -0.1718 | 8.28781 |
Annual Sum or Average | 5943.00000 | 23.14238 | 47.39543 | -0.1126 | 8.06044 |
Minimum of Months | 454.00000 | 21.43180 | 41.84408 | -0.3322 | 6.93171 |
Maximum of Months | 514.00000 | 24.33980 | 51.51564 | 0.42166 | 10.29998 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.35437 | 41.65316 | -0.2781 | 8.81498 |
February | 385.00000 | 21.60350 | 43.33737 | -0.1816 | 8.47969 |
March | 433.00000 | 22.03613 | 42.66688 | -0.0615 | 8.11503 |
April | 410.00000 | 22.95919 | 48.20981 | 0.24514 | 8.56472 |
May | 430.00000 | 23.90502 | 50.67548 | -0.3081 | 9.76379 |
June | 418.00000 | 23.93982 | 49.63095 | -0.2884 | 8.77385 |
July | 422.00000 | 24.02622 | 50.41461 | -0.2577 | 9.10042 |
August | 433.00000 | 23.83214 | 50.97865 | -0.3289 | 9.61712 |
September | 410.00000 | 23.64029 | 51.96856 | -0.4116 | 11.95297 |
October | 427.00000 | 23.32087 | 49.86201 | 0.37194 | 10.33630 |
November | 417.00000 | 22.24092 | 45.26233 | 0.02096 | 7.10057 |
December | 422.00000 | 21.60330 | 44.52007 | -0.1859 | 8.10709 |
Annual Sum or Average | 5034.00000 | 22.87973 | 47.44866 | -0.1388 | 9.06257 |
Minimum of Months | 385.00000 | 21.35437 | 41.65316 | -0.4116 | 7.10057 |
Maximum of Months | 433.00000 | 24.02622 | 51.96856 | 0.37194 | 11.95297 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.61992 | 38.66854 | 0.04382 | 9.47465 |
February | 454.00000 | 22.64755 | 41.05385 | 0.08327 | 9.41533 |
March | 514.00000 | 22.57576 | 41.64222 | 0.06258 | 8.55126 |
April | 485.00000 | 23.23955 | 47.58251 | 0.29033 | 8.67735 |
May | 508.00000 | 23.99973 | 50.66583 | -0.3299 | 8.42298 |
June | 496.00000 | 24.03552 | 49.64142 | -0.3148 | 7.93564 |
July | 497.00000 | 24.12080 | 50.41848 | -0.2804 | 7.79277 |
August | 514.00000 | 24.06986 | 50.41746 | -0.2811 | 7.86492 |
September | 485.00000 | 24.04062 | 50.85057 | -0.2955 | 9.03071 |
October | 502.00000 | 23.99320 | 47.81947 | 0.54143 | 13.29328 |
November | 489.00000 | 23.35992 | 42.60005 | 0.30689 | 10.12569 |
December | 497.00000 | 22.84737 | 41.30396 | 0.13785 | 10.06467 |
Annual Sum or Average | 5943.00000 | 23.46764 | 46.08649 | -0.0047 | 9.21621 |
Minimum of Months | 454.00000 | 22.57576 | 38.66854 | -0.3299 | 7.79277 |
Maximum of Months | 514.00000 | 24.12080 | 50.85057 | 0.54143 | 13.29328 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.47119 | 41.26082 | -0.2455 | 8.82118 |
February | 454.00000 | 21.69529 | 43.30639 | -0.1503 | 8.98082 |
March | 514.00000 | 21.94525 | 43.09238 | -0.0745 | 7.99948 |
April | 485.00000 | 22.80389 | 48.52737 | 0.22523 | 8.48384 |
May | 508.00000 | 23.66860 | 51.25272 | -0.3797 | 10.44746 |
June | 496.00000 | 23.79538 | 50.02757 | -0.3273 | 9.40983 |
July | 497.00000 | 23.81138 | 50.86570 | -0.3252 | 9.43038 |
August | 514.00000 | 23.73763 | 51.05093 | -0.3445 | 9.55702 |
September | 485.00000 | 23.49768 | 52.12923 | -0.4422 | 12.05315 |
October | 502.00000 | 23.25426 | 49.80524 | 0.36958 | 10.14703 |
November | 489.00000 | 22.18972 | 45.61215 | 0.02213 | 7.37294 |
December | 497.00000 | 21.74743 | 44.02822 | -0.1407 | 8.28897 |
Annual Sum or Average | 5943.00000 | 22.80982 | 47.60240 | -0.1519 | 9.24959 |
Minimum of Months | 454.00000 | 21.47119 | 41.26082 | -0.4422 | 7.37294 |
Maximum of Months | 514.00000 | 23.81138 | 52.12923 | 0.36958 | 12.05315 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.393696E+11 | 0.948661E+10 | 402.59 | 0.311059E+11 | 0.826375E+10 | 0.00 | 1.00 | 01-JAN-12:12 | 0.00 | 01-JAN-00:10 | 72409.29 | 19-JAN-15:10 | 51164.98 | 19-JAN-15:30 | 25010.72 | 19-JAN-13:10 | 16590.46 | 19-JAN-12:00 | 0.00 |
February | 0.433523E+11 | 0.102398E+11 | 360.13 | 0.326112E+11 | 0.107411E+11 | 0.00 | 1.00 | 01-FEB-13:10 | 0.00 | 01-FEB-00:10 | 73416.46 | 24-FEB-13:00 | 52602.51 | 27-FEB-15:30 | 21852.50 | 24-FEB-13:00 | 17735.17 | 24-FEB-13:00 | 0.00 |
March | 0.526624E+11 | 0.124961E+11 | 425.44 | 0.409405E+11 | 0.117218E+11 | 0.00 | 1.00 | 06-MAR-09:25 | 0.00 | 01-MAR-00:10 | 75814.75 | 28-MAR-12:00 | 51834.29 | 30-MAR-12:00 | 26557.08 | 07-MAR-13:10 | 18359.51 | 30-MAR-12:00 | 0.00 |
April | 0.664413E+11 | 0.156782E+11 | 394.62 | 0.502607E+11 | 0.161806E+11 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 97061.68 | 29-APR-05:12 | 70276.59 | 28-APR-15:00 | 36252.00 | 30-APR-14:51 | 25737.24 | 28-APR-16:00 | 0.00 |
May | 0.111810E+12 | 0.275283E+11 | 448.09 | 0.771909E+11 | 0.346191E+11 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 130064.85 | 23-MAY-04:02 | 87541.43 | 31-MAY-05:01 | 58155.01 | 23-MAY-04:02 | 29449.89 | 01-MAY-04:01 | 0.00 |
June | 0.118352E+12 | 0.295454E+11 | 450.20 | 0.810094E+11 | 0.373421E+11 | 0.00 | 1.00 | 01-JUN-05:12 | 0.00 | 01-JUN-00:10 | 147344.65 | 05-JUN-04:01 | 94575.74 | 29-JUN-04:01 | 55897.29 | 05-JUN-04:01 | 33457.89 | 05-JUN-04:01 | 0.00 |
July | 0.126704E+12 | 0.314496E+11 | 457.10 | 0.814468E+11 | 0.452575E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 151680.09 | 31-JUL-04:01 | 109138.22 | 24-JUL-04:01 | 70572.61 | 31-JUL-04:01 | 34622.59 | 03-JUL-04:02 | 0.00 |
August | 0.130926E+12 | 0.324334E+11 | 469.14 | 0.867261E+11 | 0.441998E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 149408.57 | 15-AUG-04:01 | 102772.77 | 28-AUG-04:01 | 64469.35 | 16-AUG-04:41 | 34013.26 | 23-AUG-04:01 | 0.00 |
September | 0.113860E+12 | 0.272432E+11 | 441.09 | 0.741930E+11 | 0.396673E+11 | 0.00 | 1.00 | 01-SEP-04:21 | 0.00 | 01-SEP-00:10 | 150239.51 | 18-SEP-04:01 | 101919.42 | 11-SEP-04:01 | 65060.43 | 18-SEP-04:02 | 33850.19 | 19-SEP-04:01 | 0.00 |
October | 0.102077E+12 | 0.246205E+11 | 438.26 | 0.723161E+11 | 0.297613E+11 | 0.00 | 1.00 | 01-OCT-11:02 | 0.00 | 01-OCT-00:10 | 147725.94 | 06-OCT-04:01 | 96265.36 | 06-OCT-04:01 | 64359.99 | 08-OCT-07:21 | 34450.72 | 25-OCT-04:01 | 0.00 |
November | 0.625662E+11 | 0.146959E+11 | 400.90 | 0.482908E+11 | 0.142753E+11 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 104675.97 | 08-NOV-06:12 | 67985.68 | 02-NOV-14:50 | 42071.50 | 08-NOV-06:12 | 24297.07 | 07-NOV-13:10 | 0.00 |
December | 0.488188E+11 | 0.116257E+11 | 401.67 | 0.375797E+11 | 0.112391E+11 | 0.00 | 1.00 | 01-DEC-13:40 | 0.00 | 01-DEC-00:10 | 86987.38 | 15-DEC-13:05 | 64055.09 | 15-DEC-15:10 | 31546.80 | 14-DEC-13:00 | 21149.05 | 15-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.101694E+13 | 0.247043E+12 | 5089.23 | 0.713671E+12 | 0.303269E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.393696E+11 | 0.948661E+10 | 360.13 | 0.311059E+11 | 0.826375E+10 | 0.00 | 1.00 | 0.00 | 72409.29 | 51164.98 | 21852.50 | 16590.46 | 0.00 | ||||||
Maximum of Months | 0.130926E+12 | 0.324334E+11 | 469.14 | 0.867261E+11 | 0.452575E+11 | 0.00 | 1.00 | 0.00 | 151680.09 | 109138.22 | 70572.61 | 34622.59 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.327849E+11 | 0.793837E+10 | 396.61 | 0.247790E+11 | 0.800585E+10 | 0.00 | 1.00 | 01-JAN-11:22 | 0.00 | 01-JAN-00:10 | 63925.04 | 19-JAN-15:10 | 44342.76 | 19-JAN-15:30 | 20889.62 | 19-JAN-11:05 | 14616.74 | 19-JAN-15:10 | 0.00 |
February | 0.378014E+11 | 0.896801E+10 | 359.88 | 0.273161E+11 | 0.104853E+11 | 0.00 | 1.00 | 01-FEB-13:40 | 0.00 | 01-FEB-00:10 | 62889.23 | 24-FEB-16:00 | 45690.52 | 24-FEB-14:30 | 20143.22 | 03-FEB-06:02 | 14963.83 | 24-FEB-14:00 | 0.00 |
March | 0.460058E+11 | 0.109689E+11 | 427.33 | 0.344033E+11 | 0.116025E+11 | 0.00 | 1.00 | 06-MAR-09:50 | 0.00 | 01-MAR-00:10 | 66342.96 | 07-MAR-11:05 | 46471.31 | 30-MAR-13:00 | 23529.28 | 07-MAR-11:05 | 16384.65 | 30-MAR-13:00 | 0.00 |
April | 0.597861E+11 | 0.141589E+11 | 397.95 | 0.436509E+11 | 0.161352E+11 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 91409.20 | 28-APR-16:00 | 65790.49 | 28-APR-15:00 | 33857.84 | 30-APR-14:31 | 24368.62 | 28-APR-16:00 | 0.00 |
May | 0.101357E+12 | 0.248712E+11 | 444.24 | 0.680325E+11 | 0.333243E+11 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 143054.58 | 22-MAY-04:01 | 88275.27 | 30-MAY-04:01 | 70993.59 | 22-MAY-04:02 | 32133.15 | 22-MAY-04:01 | 0.00 |
June | 0.106990E+12 | 0.265851E+11 | 446.14 | 0.712521E+11 | 0.357381E+11 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 137977.96 | 05-JUN-04:01 | 93530.76 | 29-JUN-04:01 | 52189.38 | 05-JUN-04:01 | 31219.07 | 05-JUN-04:01 | 0.00 |
July | 0.114114E+12 | 0.281329E+11 | 448.37 | 0.706712E+11 | 0.434424E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 144469.02 | 03-JUL-04:02 | 97823.37 | 24-JUL-04:01 | 73828.37 | 03-JUL-04:02 | 32441.39 | 03-JUL-04:02 | 0.00 |
August | 0.114588E+12 | 0.282239E+11 | 459.84 | 0.730394E+11 | 0.415482E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 140107.36 | 07-AUG-04:01 | 89744.77 | 22-AUG-04:01 | 62703.39 | 07-AUG-05:01 | 32300.39 | 10-AUG-05:01 | 0.00 |
September | 0.997870E+11 | 0.237923E+11 | 431.64 | 0.620542E+11 | 0.377327E+11 | 0.00 | 1.00 | 01-SEP-04:21 | 0.00 | 01-SEP-00:10 | 142659.17 | 05-SEP-05:12 | 88946.00 | 11-SEP-04:01 | 81018.13 | 05-SEP-05:12 | 31373.67 | 10-SEP-15:12 | 0.00 |
October | 0.882686E+11 | 0.212573E+11 | 429.08 | 0.599471E+11 | 0.283216E+11 | 0.00 | 1.00 | 01-OCT-13:13 | 0.00 | 01-OCT-00:10 | 139053.83 | 06-OCT-05:01 | 80539.59 | 06-OCT-04:01 | 61897.00 | 25-OCT-04:01 | 31560.10 | 06-OCT-05:01 | 0.00 |
November | 0.528684E+11 | 0.125057E+11 | 397.52 | 0.388588E+11 | 0.140096E+11 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 85693.80 | 02-NOV-14:10 | 59703.96 | 02-NOV-14:40 | 28107.29 | 01-NOV-11:00 | 21428.54 | 02-NOV-14:10 | 0.00 |
December | 0.409720E+11 | 0.980281E+10 | 397.64 | 0.300516E+11 | 0.109204E+11 | 0.00 | 1.00 | 08-DEC-12:30 | 0.00 | 01-DEC-00:10 | 71701.48 | 15-DEC-14:00 | 55616.34 | 15-DEC-15:00 | 27452.71 | 12-DEC-14:00 | 17885.24 | 15-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.895322E+12 | 0.217205E+12 | 5036.25 | 0.604056E+12 | 0.291266E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.327849E+11 | 0.793837E+10 | 359.88 | 0.247790E+11 | 0.800585E+10 | 0.00 | 1.00 | 0.00 | 62889.23 | 44342.76 | 20143.22 | 14616.74 | 0.00 | ||||||
Maximum of Months | 0.114588E+12 | 0.282239E+11 | 459.84 | 0.730394E+11 | 0.434424E+11 | 0.00 | 1.00 | 0.00 | 144469.02 | 97823.37 | 81018.13 | 32441.39 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.392844E+11 | 0.956462E+10 | 398.61 | 0.308734E+11 | 0.841098E+10 | 0.00 | 1.00 | 01-JAN-11:22 | 0.00 | 01-JAN-00:10 | 72581.96 | 19-JAN-15:00 | 58223.28 | 01-JAN-14:03 | 21419.62 | 20-JAN-06:02 | 16571.83 | 19-JAN-15:00 | 0.00 |
February | 0.438167E+11 | 0.104572E+11 | 360.16 | 0.330588E+11 | 0.107580E+11 | 0.00 | 1.00 | 01-FEB-14:10 | 0.00 | 01-FEB-00:10 | 73347.01 | 24-FEB-14:40 | 56522.61 | 24-FEB-14:40 | 23128.75 | 03-FEB-06:02 | 17207.10 | 24-FEB-14:20 | 0.00 |
March | 0.533925E+11 | 0.127721E+11 | 426.78 | 0.414376E+11 | 0.119549E+11 | 0.00 | 1.00 | 06-MAR-10:30 | 0.00 | 01-MAR-00:10 | 75846.23 | 29-MAR-15:00 | 61089.22 | 26-MAR-13:52 | 24522.45 | 07-MAR-06:12 | 18328.20 | 30-MAR-13:00 | 0.00 |
April | 0.687855E+11 | 0.163655E+11 | 399.53 | 0.522785E+11 | 0.165070E+11 | 0.00 | 1.00 | 04-APR-13:10 | 0.00 | 01-APR-00:10 | 107669.19 | 28-APR-16:00 | 84167.48 | 28-APR-15:00 | 39516.13 | 30-APR-14:31 | 28627.36 | 28-APR-16:00 | 0.00 |
May | 0.112730E+12 | 0.277690E+11 | 444.30 | 0.794846E+11 | 0.332451E+11 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 169411.38 | 22-MAY-04:01 | 107051.25 | 28-MAY-14:41 | 77748.99 | 24-MAY-05:01 | 38031.16 | 22-MAY-04:01 | 0.00 |
June | 0.119728E+12 | 0.298616E+11 | 447.05 | 0.841453E+11 | 0.355829E+11 | 0.00 | 1.00 | 01-JUN-07:30 | 0.00 | 01-JUN-00:10 | 163737.63 | 05-JUN-04:01 | 105701.75 | 25-JUN-14:51 | 67282.23 | 05-JUN-04:01 | 36999.83 | 05-JUN-04:01 | 0.00 |
July | 0.125900E+12 | 0.311844E+11 | 449.30 | 0.825360E+11 | 0.433642E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 170495.35 | 03-JUL-04:01 | 120487.25 | 24-JUL-04:01 | 83096.25 | 31-JUL-04:01 | 38355.58 | 03-JUL-04:01 | 0.00 |
August | 0.125549E+12 | 0.310427E+11 | 457.50 | 0.842131E+11 | 0.413364E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 166406.22 | 07-AUG-04:01 | 106302.75 | 28-AUG-04:01 | 81165.26 | 15-AUG-05:01 | 38285.40 | 10-AUG-05:01 | 0.00 |
September | 0.108348E+12 | 0.259130E+11 | 432.38 | 0.704500E+11 | 0.378977E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 166972.15 | 18-SEP-05:01 | 110872.87 | 10-SEP-15:12 | 83593.93 | 18-SEP-05:01 | 41466.18 | 10-SEP-15:12 | 0.00 |
October | 0.957761E+11 | 0.231628E+11 | 425.86 | 0.674810E+11 | 0.282951E+11 | 0.00 | 1.00 | 01-OCT-12:52 | 0.00 | 01-OCT-00:10 | 163822.80 | 07-OCT-05:01 | 98043.49 | 23-OCT-05:01 | 73935.63 | 07-OCT-05:01 | 37545.42 | 07-OCT-05:01 | 0.00 |
November | 0.583158E+11 | 0.138665E+11 | 395.05 | 0.439047E+11 | 0.144111E+11 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 98038.10 | 02-NOV-14:00 | 72042.11 | 02-NOV-14:30 | 29341.98 | 02-NOV-05:07 | 24419.56 | 02-NOV-14:00 | 0.00 |
December | 0.468001E+11 | 0.112670E+11 | 397.01 | 0.354888E+11 | 0.113113E+11 | 0.00 | 1.00 | 08-DEC-13:10 | 0.00 | 01-DEC-00:10 | 81535.19 | 15-DEC-14:30 | 65469.57 | 15-DEC-15:00 | 27495.03 | 12-DEC-14:30 | 20279.75 | 15-DEC-14:40 | 0.00 |
Annual Sum or Average | 0.998426E+12 | 0.243226E+12 | 5033.53 | 0.705352E+12 | 0.293075E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.392844E+11 | 0.956462E+10 | 360.16 | 0.308734E+11 | 0.841098E+10 | 0.00 | 1.00 | 0.00 | 72581.96 | 56522.61 | 21419.62 | 16571.83 | 0.00 | ||||||
Maximum of Months | 0.125900E+12 | 0.311844E+11 | 457.50 | 0.842131E+11 | 0.433642E+11 | 0.00 | 1.00 | 0.00 | 170495.35 | 120487.25 | 83593.93 | 41466.18 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.63 | 0.00 | 212.63 | 238.12 | 1820.57 | 12.83 | 0.00 | 0.00 |
February | 250.85 | 0.00 | 250.85 | 325.64 | 1491.04 | 0.67 | 0.00 | 0.00 |
March | 291.01 | 0.00 | 291.01 | 470.18 | 1292.09 | 1.33 | 0.00 | 0.00 |
April | 344.44 | 2.39 | 342.05 | 779.85 | 751.34 | 0.00 | 0.00 | 0.00 |
May | 394.79 | 19.99 | 374.80 | 1472.26 | 223.24 | 0.00 | 0.00 | 0.00 |
June | 452.26 | 40.49 | 411.77 | 1766.26 | 199.79 | 0.00 | 0.00 | 0.00 |
July | 435.27 | 22.30 | 412.97 | 1682.74 | 131.80 | 0.00 | 0.00 | 0.00 |
August | 386.08 | 4.63 | 381.45 | 1531.36 | 177.52 | 0.00 | 0.00 | 0.00 |
September | 332.12 | 0.05 | 332.07 | 1186.35 | 238.90 | 0.00 | 0.00 | 0.00 |
October | 288.59 | 0.00 | 288.59 | 952.70 | 467.18 | 0.00 | 0.00 | 0.00 |
November | 219.08 | 0.00 | 219.08 | 402.17 | 1053.49 | 0.17 | 0.00 | 0.00 |
December | 197.66 | 0.00 | 197.66 | 274.31 | 1525.46 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 317.39 | 7.51 | 309.88 | 927.20 | 777.61 | 16.17 | 0.00 | 0.00 |
Minimum of Months | 197.66 | 0.00 | 197.66 | 238.12 | 131.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 452.26 | 40.49 | 412.97 | 1766.26 | 1820.57 | 12.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 365.75 | 186.70 | 179.05 | 631.95 | 1071.57 | 12.83 | 0.00 | 0.00 |
February | 407.14 | 197.02 | 210.11 | 765.83 | 883.09 | 0.50 | 0.00 | 0.00 |
March | 474.85 | 227.45 | 247.40 | 983.97 | 784.11 | 0.83 | 0.00 | 0.00 |
April | 522.82 | 235.59 | 287.23 | 1289.76 | 471.67 | 0.00 | 0.00 | 0.00 |
May | 538.01 | 231.87 | 306.14 | 1749.98 | 140.63 | 0.00 | 0.00 | 0.00 |
June | 547.23 | 216.45 | 330.78 | 1895.71 | 124.44 | 0.00 | 0.00 | 0.00 |
July | 527.43 | 192.33 | 335.11 | 1827.19 | 78.79 | 0.00 | 0.00 | 0.00 |
August | 486.00 | 166.43 | 319.57 | 1666.97 | 108.66 | 0.00 | 0.00 | 0.00 |
September | 430.23 | 147.14 | 283.09 | 1388.71 | 144.56 | 0.00 | 0.00 | 0.00 |
October | 426.15 | 179.74 | 246.41 | 1270.14 | 287.38 | 0.00 | 0.00 | 0.00 |
November | 378.62 | 193.72 | 184.89 | 828.64 | 631.60 | 0.17 | 0.00 | 0.00 |
December | 299.90 | 137.34 | 162.56 | 563.73 | 922.02 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 450.49 | 192.55 | 257.93 | 1241.20 | 468.72 | 15.50 | 0.00 | 0.00 |
Minimum of Months | 299.90 | 137.34 | 162.56 | 563.73 | 78.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 547.23 | 235.59 | 335.11 | 1895.71 | 1071.57 | 12.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1210.27 | 857.75 | 352.52 | 2609.30 | 1579.58 | 11.17 | 0.00 | 0.00 |
February | 1117.57 | 724.42 | 393.16 | 2457.33 | 1335.55 | 0.67 | 0.00 | 0.00 |
March | 742.97 | 352.51 | 390.46 | 1694.82 | 1225.30 | 1.17 | 0.00 | 0.00 |
April | 563.01 | 159.16 | 403.85 | 1483.14 | 758.62 | 0.00 | 0.00 | 0.00 |
May | 413.58 | 27.70 | 385.88 | 1555.64 | 218.04 | 0.00 | 0.00 | 0.00 |
June | 401.42 | 7.03 | 394.39 | 1630.50 | 194.29 | 0.00 | 0.00 | 0.00 |
July | 422.13 | 13.05 | 409.09 | 1659.14 | 121.06 | 0.00 | 0.00 | 0.00 |
August | 509.23 | 77.80 | 431.43 | 1953.24 | 176.51 | 0.00 | 0.00 | 0.00 |
September | 613.78 | 180.56 | 433.22 | 2075.37 | 243.14 | 0.00 | 0.00 | 0.00 |
October | 928.29 | 491.03 | 437.26 | 2843.01 | 475.78 | 0.00 | 0.00 | 0.00 |
November | 1149.85 | 788.07 | 361.78 | 2863.68 | 990.58 | 0.17 | 0.00 | 0.00 |
December | 1177.06 | 838.58 | 338.48 | 2742.74 | 1381.19 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 768.88 | 374.63 | 394.26 | 2129.26 | 721.91 | 14.33 | 0.00 | 0.00 |
Minimum of Months | 401.42 | 7.03 | 338.48 | 1483.14 | 121.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1210.27 | 857.75 | 437.26 | 2863.68 | 1579.58 | 11.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 388.81 | 210.60 | 178.21 | 746.63 | 1134.93 | 14.00 | 0.00 | 0.00 |
February | 439.57 | 222.60 | 216.98 | 884.84 | 944.69 | 0.50 | 0.00 | 0.00 |
March | 432.03 | 190.70 | 241.33 | 934.90 | 827.58 | 1.00 | 0.00 | 0.00 |
April | 535.26 | 244.84 | 290.41 | 1390.32 | 502.49 | 0.00 | 0.00 | 0.00 |
May | 447.21 | 145.64 | 301.56 | 1574.74 | 149.38 | 0.00 | 0.00 | 0.00 |
June | 496.60 | 173.97 | 322.63 | 1785.82 | 134.96 | 0.00 | 0.00 | 0.00 |
July | 454.16 | 126.43 | 327.73 | 1631.62 | 84.00 | 0.00 | 0.00 | 0.00 |
August | 458.16 | 139.95 | 318.20 | 1658.44 | 117.51 | 0.00 | 0.00 | 0.00 |
September | 421.46 | 144.05 | 277.42 | 1424.28 | 152.07 | 0.00 | 0.00 | 0.00 |
October | 431.74 | 186.22 | 245.52 | 1382.72 | 306.67 | 0.33 | 0.00 | 0.00 |
November | 371.74 | 187.41 | 184.33 | 908.94 | 679.83 | 0.17 | 0.00 | 0.00 |
December | 358.01 | 191.12 | 166.89 | 769.74 | 957.81 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 435.98 | 179.87 | 256.12 | 1259.50 | 497.11 | 17.17 | 0.00 | 0.00 |
Minimum of Months | 358.01 | 126.43 | 166.89 | 746.63 | 84.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 535.26 | 244.84 | 327.73 | 1785.82 | 1134.93 | 14.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.87 | 0.00 | 70.87 | 78.81 | 657.53 | 9.00 | 0.00 | 0.00 |
February | 83.61 | 0.00 | 83.61 | 112.38 | 531.24 | 2.50 | 0.00 | 0.00 |
March | 97.00 | 0.00 | 97.00 | 168.52 | 449.39 | 1.33 | 0.00 | 0.00 |
April | 114.81 | 0.80 | 114.01 | 274.78 | 256.75 | 0.00 | 0.00 | 0.00 |
May | 131.59 | 6.66 | 124.93 | 504.20 | 71.56 | 0.00 | 0.00 | 0.00 |
June | 150.75 | 13.50 | 137.25 | 602.52 | 66.19 | 0.00 | 0.00 | 0.00 |
July | 145.08 | 7.43 | 137.65 | 569.74 | 45.83 | 0.00 | 0.00 | 0.00 |
August | 128.69 | 1.54 | 127.14 | 511.43 | 71.31 | 0.00 | 0.00 | 0.00 |
September | 110.70 | 0.02 | 110.69 | 394.25 | 101.53 | 0.00 | 0.00 | 0.00 |
October | 96.19 | 0.00 | 96.19 | 314.02 | 185.77 | 0.00 | 0.00 | 0.00 |
November | 73.02 | 0.00 | 73.02 | 126.70 | 407.55 | 0.00 | 0.00 | 0.00 |
December | 65.89 | 0.00 | 65.89 | 86.45 | 565.75 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 105.79 | 2.50 | 103.29 | 313.21 | 283.01 | 14.00 | 0.00 | 0.00 |
Minimum of Months | 65.89 | 0.00 | 65.89 | 78.81 | 45.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.75 | 13.50 | 137.65 | 602.52 | 657.53 | 9.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.88 | 0.00 | 70.88 | 78.82 | 657.57 | 9.00 | 0.00 | 0.00 |
February | 83.62 | 0.00 | 83.62 | 112.38 | 531.28 | 2.50 | 0.00 | 0.00 |
March | 97.00 | 0.00 | 97.00 | 168.53 | 449.42 | 1.33 | 0.00 | 0.00 |
April | 114.81 | 0.80 | 114.02 | 274.79 | 256.76 | 0.00 | 0.00 | 0.00 |
May | 131.60 | 6.66 | 124.93 | 504.23 | 71.56 | 0.00 | 0.00 | 0.00 |
June | 150.76 | 13.50 | 137.26 | 602.56 | 66.20 | 0.00 | 0.00 | 0.00 |
July | 145.09 | 7.43 | 137.66 | 569.77 | 45.83 | 0.00 | 0.00 | 0.00 |
August | 128.69 | 1.54 | 127.15 | 511.46 | 71.32 | 0.00 | 0.00 | 0.00 |
September | 110.71 | 0.02 | 110.69 | 394.27 | 101.53 | 0.00 | 0.00 | 0.00 |
October | 96.20 | 0.00 | 96.20 | 314.03 | 185.79 | 0.00 | 0.00 | 0.00 |
November | 73.03 | 0.00 | 73.03 | 126.71 | 407.57 | 0.00 | 0.00 | 0.00 |
December | 65.89 | 0.00 | 65.89 | 86.45 | 565.79 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 105.80 | 2.50 | 103.29 | 313.23 | 283.02 | 14.00 | 0.00 | 0.00 |
Minimum of Months | 65.89 | 0.00 | 65.89 | 78.82 | 45.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.76 | 13.50 | 137.66 | 602.56 | 657.57 | 9.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.88 | 0.00 | 70.88 | 78.82 | 657.57 | 9.00 | 0.00 | 0.00 |
February | 83.62 | 0.00 | 83.62 | 112.38 | 531.28 | 2.50 | 0.00 | 0.00 |
March | 97.00 | 0.00 | 97.00 | 168.53 | 449.42 | 1.33 | 0.00 | 0.00 |
April | 114.81 | 0.80 | 114.02 | 274.79 | 256.76 | 0.00 | 0.00 | 0.00 |
May | 131.60 | 6.66 | 124.93 | 504.23 | 71.56 | 0.00 | 0.00 | 0.00 |
June | 150.76 | 13.50 | 137.26 | 602.56 | 66.20 | 0.00 | 0.00 | 0.00 |
July | 145.09 | 7.43 | 137.66 | 569.77 | 45.83 | 0.00 | 0.00 | 0.00 |
August | 128.69 | 1.54 | 127.15 | 511.46 | 71.32 | 0.00 | 0.00 | 0.00 |
September | 110.71 | 0.02 | 110.69 | 394.27 | 101.53 | 0.00 | 0.00 | 0.00 |
October | 96.20 | 0.00 | 96.20 | 314.03 | 185.79 | 0.00 | 0.00 | 0.00 |
November | 73.03 | 0.00 | 73.03 | 126.71 | 407.57 | 0.00 | 0.00 | 0.00 |
December | 65.89 | 0.00 | 65.89 | 86.45 | 565.79 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 105.80 | 2.50 | 103.29 | 313.23 | 283.02 | 14.00 | 0.00 | 0.00 |
Minimum of Months | 65.89 | 0.00 | 65.89 | 78.82 | 45.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.76 | 13.50 | 137.66 | 602.56 | 657.57 | 9.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 351.85 | 179.61 | 172.24 | 611.49 | 1136.85 | 9.50 | 0.00 | 0.00 |
February | 391.66 | 189.54 | 202.13 | 752.72 | 923.71 | 1.83 | 0.00 | 0.00 |
March | 456.80 | 218.81 | 238.00 | 985.02 | 800.28 | 0.83 | 0.00 | 0.00 |
April | 502.95 | 226.64 | 276.31 | 1290.82 | 473.05 | 0.00 | 0.00 | 0.00 |
May | 517.56 | 223.06 | 294.50 | 1732.98 | 134.45 | 0.00 | 0.00 | 0.00 |
June | 526.44 | 208.23 | 318.21 | 1864.73 | 121.45 | 0.00 | 0.00 | 0.00 |
July | 507.39 | 185.02 | 322.37 | 1786.28 | 82.20 | 0.00 | 0.00 | 0.00 |
August | 467.53 | 160.10 | 307.43 | 1615.00 | 127.71 | 0.00 | 0.00 | 0.00 |
September | 413.88 | 141.55 | 272.33 | 1342.58 | 181.40 | 0.00 | 0.00 | 0.00 |
October | 409.96 | 172.91 | 237.05 | 1232.92 | 330.52 | 0.00 | 0.00 | 0.00 |
November | 364.23 | 186.36 | 177.87 | 787.72 | 706.93 | 0.00 | 0.00 | 0.00 |
December | 288.50 | 132.12 | 156.38 | 538.46 | 996.03 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 433.37 | 185.24 | 248.13 | 1214.30 | 499.17 | 13.33 | 0.00 | 0.00 |
Minimum of Months | 288.50 | 132.12 | 156.38 | 538.46 | 82.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 526.44 | 226.64 | 322.37 | 1864.73 | 1136.85 | 9.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.91 | 7.10 | 6.81 | 24.18 | 44.95 | 9.50 | 0.00 | 0.00 |
February | 15.49 | 7.49 | 7.99 | 29.76 | 36.52 | 1.83 | 0.00 | 0.00 |
March | 18.06 | 8.65 | 9.41 | 38.95 | 31.64 | 0.83 | 0.00 | 0.00 |
April | 19.89 | 8.96 | 10.93 | 51.04 | 18.70 | 0.00 | 0.00 | 0.00 |
May | 20.46 | 8.82 | 11.64 | 68.52 | 5.32 | 0.00 | 0.00 | 0.00 |
June | 20.81 | 8.23 | 12.58 | 73.73 | 4.80 | 0.00 | 0.00 | 0.00 |
July | 20.06 | 7.32 | 12.75 | 70.63 | 3.25 | 0.00 | 0.00 | 0.00 |
August | 18.49 | 6.33 | 12.16 | 63.86 | 5.05 | 0.00 | 0.00 | 0.00 |
September | 16.36 | 5.60 | 10.77 | 53.08 | 7.17 | 0.00 | 0.00 | 0.00 |
October | 16.21 | 6.84 | 9.37 | 48.75 | 13.07 | 0.00 | 0.00 | 0.00 |
November | 14.40 | 7.37 | 7.03 | 31.15 | 27.95 | 0.00 | 0.00 | 0.00 |
December | 11.41 | 5.22 | 6.18 | 21.29 | 39.38 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 17.13 | 7.32 | 9.81 | 48.01 | 19.74 | 13.33 | 0.00 | 0.00 |
Minimum of Months | 11.41 | 5.22 | 6.18 | 21.29 | 3.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.81 | 8.96 | 12.75 | 73.73 | 44.95 | 9.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 403.43 | 285.93 | 117.51 | 883.99 | 605.65 | 5.67 | 0.00 | 0.00 |
February | 372.53 | 241.48 | 131.06 | 838.11 | 503.79 | 1.83 | 0.00 | 0.00 |
March | 247.66 | 117.51 | 130.16 | 587.66 | 441.60 | 0.83 | 0.00 | 0.00 |
April | 187.67 | 53.05 | 134.62 | 514.22 | 265.00 | 0.00 | 0.00 | 0.00 |
May | 137.86 | 9.23 | 128.63 | 531.36 | 70.25 | 0.00 | 0.00 | 0.00 |
June | 133.81 | 2.34 | 131.47 | 553.73 | 63.44 | 0.00 | 0.00 | 0.00 |
July | 140.71 | 4.35 | 136.37 | 558.82 | 42.60 | 0.00 | 0.00 | 0.00 |
August | 169.75 | 25.93 | 143.81 | 650.52 | 73.53 | 0.00 | 0.00 | 0.00 |
September | 204.60 | 60.19 | 144.41 | 692.66 | 108.53 | 0.00 | 0.00 | 0.00 |
October | 309.44 | 163.68 | 145.76 | 952.21 | 197.95 | 0.00 | 0.00 | 0.00 |
November | 383.29 | 262.70 | 120.60 | 955.26 | 402.95 | 0.00 | 0.00 | 0.00 |
December | 392.36 | 279.54 | 112.83 | 922.78 | 539.63 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 256.30 | 124.88 | 131.42 | 719.59 | 275.10 | 9.50 | 0.00 | 0.00 |
Minimum of Months | 133.81 | 2.34 | 112.83 | 514.22 | 42.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.43 | 285.93 | 145.76 | 955.26 | 605.65 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 403.43 | 285.93 | 117.51 | 883.99 | 605.65 | 5.67 | 0.00 | 0.00 |
February | 372.53 | 241.48 | 131.06 | 838.11 | 503.79 | 1.83 | 0.00 | 0.00 |
March | 247.66 | 117.51 | 130.16 | 587.66 | 441.60 | 0.83 | 0.00 | 0.00 |
April | 187.67 | 53.05 | 134.62 | 514.22 | 265.00 | 0.00 | 0.00 | 0.00 |
May | 137.86 | 9.23 | 128.63 | 531.36 | 70.25 | 0.00 | 0.00 | 0.00 |
June | 133.81 | 2.34 | 131.47 | 553.73 | 63.44 | 0.00 | 0.00 | 0.00 |
July | 140.71 | 4.35 | 136.37 | 558.82 | 42.60 | 0.00 | 0.00 | 0.00 |
August | 169.75 | 25.93 | 143.81 | 650.52 | 73.53 | 0.00 | 0.00 | 0.00 |
September | 204.60 | 60.19 | 144.41 | 692.66 | 108.53 | 0.00 | 0.00 | 0.00 |
October | 309.44 | 163.68 | 145.76 | 952.21 | 197.95 | 0.00 | 0.00 | 0.00 |
November | 383.29 | 262.70 | 120.60 | 955.26 | 402.95 | 0.00 | 0.00 | 0.00 |
December | 392.36 | 279.54 | 112.83 | 922.78 | 539.63 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 256.30 | 124.88 | 131.42 | 719.59 | 275.10 | 9.50 | 0.00 | 0.00 |
Minimum of Months | 133.81 | 2.34 | 112.83 | 514.22 | 42.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.43 | 285.93 | 145.76 | 955.26 | 605.65 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 403.41 | 285.91 | 117.50 | 883.94 | 605.61 | 5.67 | 0.00 | 0.00 |
February | 372.51 | 241.46 | 131.05 | 838.05 | 503.75 | 1.83 | 0.00 | 0.00 |
March | 247.65 | 117.50 | 130.15 | 587.63 | 441.57 | 0.83 | 0.00 | 0.00 |
April | 187.66 | 53.05 | 134.61 | 514.19 | 264.99 | 0.00 | 0.00 | 0.00 |
May | 137.85 | 9.23 | 128.62 | 531.32 | 70.25 | 0.00 | 0.00 | 0.00 |
June | 133.80 | 2.34 | 131.46 | 553.69 | 63.44 | 0.00 | 0.00 | 0.00 |
July | 140.71 | 4.35 | 136.36 | 558.79 | 42.60 | 0.00 | 0.00 | 0.00 |
August | 169.74 | 25.93 | 143.80 | 650.48 | 73.53 | 0.00 | 0.00 | 0.00 |
September | 204.59 | 60.18 | 144.40 | 692.62 | 108.52 | 0.00 | 0.00 | 0.00 |
October | 309.42 | 163.67 | 145.75 | 952.15 | 197.93 | 0.00 | 0.00 | 0.00 |
November | 383.27 | 262.68 | 120.59 | 955.20 | 402.93 | 0.00 | 0.00 | 0.00 |
December | 392.34 | 279.52 | 112.82 | 922.72 | 539.60 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 256.29 | 124.87 | 131.41 | 719.55 | 275.08 | 9.50 | 0.00 | 0.00 |
Minimum of Months | 133.80 | 2.34 | 112.82 | 514.19 | 42.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.41 | 285.91 | 145.75 | 955.20 | 605.61 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 374.03 | 202.60 | 171.43 | 737.01 | 1210.70 | 9.83 | 0.00 | 0.00 |
February | 422.87 | 214.14 | 208.73 | 883.34 | 993.99 | 2.17 | 0.00 | 0.00 |
March | 415.61 | 183.45 | 232.16 | 943.98 | 848.72 | 1.17 | 0.00 | 0.00 |
April | 514.91 | 235.54 | 279.37 | 1388.77 | 507.46 | 0.00 | 0.00 | 0.00 |
May | 430.21 | 140.11 | 290.10 | 1544.32 | 142.29 | 0.00 | 0.00 | 0.00 |
June | 477.73 | 167.36 | 310.37 | 1747.23 | 133.48 | 0.00 | 0.00 | 0.00 |
July | 436.90 | 121.63 | 315.28 | 1586.25 | 86.37 | 0.00 | 0.00 | 0.00 |
August | 440.74 | 134.63 | 306.11 | 1593.07 | 140.02 | 0.00 | 0.00 | 0.00 |
September | 405.45 | 138.57 | 266.87 | 1361.60 | 193.54 | 0.00 | 0.00 | 0.00 |
October | 415.33 | 179.14 | 236.19 | 1324.20 | 353.87 | 0.00 | 0.00 | 0.00 |
November | 357.61 | 180.29 | 177.32 | 874.54 | 764.03 | 0.00 | 0.00 | 0.00 |
December | 344.40 | 183.86 | 160.55 | 748.02 | 1044.40 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 419.41 | 173.03 | 246.38 | 1229.26 | 532.61 | 14.33 | 0.00 | 0.00 |
Minimum of Months | 344.40 | 121.63 | 160.55 | 737.01 | 86.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 514.91 | 235.54 | 315.28 | 1747.23 | 1210.70 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.79 | 8.01 | 6.78 | 29.14 | 47.87 | 9.83 | 0.00 | 0.00 |
February | 16.72 | 8.47 | 8.25 | 34.93 | 39.30 | 2.17 | 0.00 | 0.00 |
March | 16.43 | 7.25 | 9.18 | 37.32 | 33.56 | 1.17 | 0.00 | 0.00 |
April | 20.36 | 9.31 | 11.05 | 54.91 | 20.06 | 0.00 | 0.00 | 0.00 |
May | 17.01 | 5.54 | 11.47 | 61.06 | 5.63 | 0.00 | 0.00 | 0.00 |
June | 18.89 | 6.62 | 12.27 | 69.08 | 5.28 | 0.00 | 0.00 | 0.00 |
July | 17.27 | 4.81 | 12.47 | 62.72 | 3.42 | 0.00 | 0.00 | 0.00 |
August | 17.43 | 5.32 | 12.10 | 62.99 | 5.54 | 0.00 | 0.00 | 0.00 |
September | 16.03 | 5.48 | 10.55 | 53.84 | 7.65 | 0.00 | 0.00 | 0.00 |
October | 16.42 | 7.08 | 9.34 | 52.36 | 13.99 | 0.00 | 0.00 | 0.00 |
November | 14.14 | 7.13 | 7.01 | 34.58 | 30.21 | 0.00 | 0.00 | 0.00 |
December | 13.62 | 7.27 | 6.35 | 29.58 | 41.29 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 16.58 | 6.84 | 9.74 | 48.60 | 21.06 | 14.33 | 0.00 | 0.00 |
Minimum of Months | 13.62 | 4.81 | 6.35 | 29.14 | 3.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.36 | 9.31 | 12.47 | 69.08 | 47.87 | 9.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.63 | 0.00 | 212.63 | 228.41 | 1954.61 | 11.17 | 0.00 | 0.00 |
February | 250.85 | 0.00 | 250.85 | 316.70 | 1606.48 | 1.50 | 0.00 | 0.00 |
March | 291.01 | 0.00 | 291.01 | 468.09 | 1386.21 | 1.50 | 0.00 | 0.00 |
April | 344.44 | 2.39 | 342.05 | 777.37 | 812.42 | 0.00 | 0.00 | 0.00 |
May | 394.79 | 19.99 | 374.80 | 1482.52 | 237.14 | 0.00 | 0.00 | 0.00 |
June | 452.26 | 40.49 | 411.77 | 1784.91 | 211.15 | 0.00 | 0.00 | 0.00 |
July | 435.27 | 22.30 | 412.97 | 1699.96 | 139.07 | 0.00 | 0.00 | 0.00 |
August | 386.08 | 4.63 | 381.45 | 1543.86 | 193.02 | 0.00 | 0.00 | 0.00 |
September | 332.12 | 0.05 | 332.07 | 1190.26 | 271.86 | 0.00 | 0.00 | 0.00 |
October | 288.59 | 0.00 | 288.59 | 950.01 | 519.62 | 0.00 | 0.00 | 0.00 |
November | 219.08 | 0.00 | 219.08 | 383.27 | 1172.76 | 0.17 | 0.00 | 0.00 |
December | 197.66 | 0.00 | 197.66 | 261.10 | 1655.52 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 317.39 | 7.51 | 309.88 | 927.66 | 842.93 | 15.50 | 0.00 | 0.00 |
Minimum of Months | 197.66 | 0.00 | 197.66 | 228.41 | 139.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 452.26 | 40.49 | 412.97 | 1784.91 | 1954.61 | 11.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 365.75 | 186.70 | 179.05 | 625.07 | 1142.81 | 10.50 | 0.00 | 0.00 |
February | 407.14 | 197.02 | 210.11 | 762.55 | 942.93 | 1.17 | 0.00 | 0.00 |
March | 474.85 | 227.45 | 247.40 | 989.84 | 829.85 | 1.00 | 0.00 | 0.00 |
April | 522.82 | 235.59 | 287.23 | 1300.48 | 499.02 | 0.00 | 0.00 | 0.00 |
May | 538.01 | 231.87 | 306.14 | 1765.89 | 145.96 | 0.00 | 0.00 | 0.00 |
June | 547.23 | 216.45 | 330.78 | 1912.20 | 128.55 | 0.00 | 0.00 | 0.00 |
July | 527.43 | 192.33 | 335.11 | 1844.98 | 80.55 | 0.00 | 0.00 | 0.00 |
August | 486.00 | 166.43 | 319.57 | 1679.91 | 113.58 | 0.00 | 0.00 | 0.00 |
September | 430.23 | 147.14 | 283.09 | 1399.02 | 158.63 | 0.00 | 0.00 | 0.00 |
October | 426.15 | 179.74 | 246.41 | 1278.40 | 311.23 | 0.00 | 0.00 | 0.00 |
November | 378.62 | 193.72 | 184.89 | 818.21 | 689.00 | 0.17 | 0.00 | 0.00 |
December | 299.90 | 137.34 | 162.56 | 556.89 | 990.83 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 450.49 | 192.55 | 257.93 | 1247.18 | 500.59 | 14.00 | 0.00 | 0.00 |
Minimum of Months | 299.90 | 137.34 | 162.56 | 556.89 | 80.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 547.23 | 235.59 | 335.11 | 1912.20 | 1142.81 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1210.27 | 857.75 | 352.52 | 2594.17 | 1704.92 | 9.00 | 0.00 | 0.00 |
February | 1117.57 | 724.42 | 393.16 | 2450.04 | 1446.35 | 1.50 | 0.00 | 0.00 |
March | 742.97 | 352.51 | 390.46 | 1697.71 | 1314.16 | 1.33 | 0.00 | 0.00 |
April | 563.01 | 159.16 | 403.85 | 1488.09 | 816.21 | 0.00 | 0.00 | 0.00 |
May | 413.58 | 27.70 | 385.88 | 1566.07 | 232.48 | 0.00 | 0.00 | 0.00 |
June | 401.42 | 7.03 | 394.39 | 1646.09 | 205.73 | 0.00 | 0.00 | 0.00 |
July | 422.13 | 13.05 | 409.09 | 1675.17 | 128.41 | 0.00 | 0.00 | 0.00 |
August | 509.23 | 77.80 | 431.43 | 1967.29 | 190.91 | 0.00 | 0.00 | 0.00 |
September | 613.78 | 180.56 | 433.22 | 2083.32 | 274.64 | 0.00 | 0.00 | 0.00 |
October | 928.29 | 491.03 | 437.26 | 2851.83 | 521.56 | 0.00 | 0.00 | 0.00 |
November | 1149.85 | 788.07 | 361.78 | 2848.61 | 1091.29 | 0.17 | 0.00 | 0.00 |
December | 1177.06 | 838.58 | 338.48 | 2730.52 | 1500.11 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 768.88 | 374.63 | 394.26 | 2131.92 | 782.20 | 13.17 | 0.00 | 0.00 |
Minimum of Months | 401.42 | 7.03 | 338.48 | 1488.09 | 128.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1210.27 | 857.75 | 437.26 | 2851.83 | 1704.92 | 9.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 388.81 | 210.60 | 178.21 | 747.83 | 1219.44 | 11.33 | 0.00 | 0.00 |
February | 439.57 | 222.60 | 216.98 | 891.07 | 1016.78 | 1.17 | 0.00 | 0.00 |
March | 432.03 | 190.70 | 241.33 | 945.94 | 884.56 | 1.33 | 0.00 | 0.00 |
April | 535.26 | 244.84 | 290.41 | 1402.51 | 539.46 | 0.00 | 0.00 | 0.00 |
May | 447.21 | 145.64 | 301.56 | 1581.86 | 158.82 | 0.00 | 0.00 | 0.00 |
June | 496.60 | 173.97 | 322.63 | 1798.60 | 142.78 | 0.00 | 0.00 | 0.00 |
July | 454.16 | 126.43 | 327.73 | 1642.95 | 88.74 | 0.00 | 0.00 | 0.00 |
August | 458.16 | 139.95 | 318.20 | 1666.55 | 125.90 | 0.00 | 0.00 | 0.00 |
September | 421.46 | 144.05 | 277.42 | 1425.83 | 171.59 | 0.00 | 0.00 | 0.00 |
October | 431.74 | 186.22 | 245.52 | 1384.36 | 335.57 | 0.00 | 0.00 | 0.00 |
November | 371.74 | 187.41 | 184.33 | 906.24 | 749.92 | 0.17 | 0.00 | 0.00 |
December | 358.01 | 191.12 | 166.89 | 768.96 | 1038.07 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 435.98 | 179.87 | 256.12 | 1265.31 | 536.89 | 15.17 | 0.00 | 0.00 |
Minimum of Months | 358.01 | 126.43 | 166.89 | 747.83 | 88.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 535.26 | 244.84 | 327.73 | 1798.60 | 1219.44 | 11.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.569506E+09 | 0.00 | 0.569506E+09 | 0.637791E+09 | 0.487623E+10 |
February | 0.606859E+09 | 0.00 | 0.606859E+09 | 0.787794E+09 | 0.360713E+10 |
March | 0.779439E+09 | 0.00 | 0.779439E+09 | 0.125934E+10 | 0.346073E+10 |
April | 0.892785E+09 | 6203721.83 | 0.886582E+09 | 0.202137E+10 | 0.194747E+10 |
May | 0.105740E+10 | 53538375.48 | 0.100386E+10 | 0.394329E+10 | 0.597933E+09 |
June | 0.117227E+10 | 0.104945E+09 | 0.106732E+10 | 0.457814E+10 | 0.517864E+09 |
July | 0.116582E+10 | 59719335.86 | 0.110610E+10 | 0.450704E+10 | 0.353001E+09 |
August | 0.103407E+10 | 12398667.89 | 0.102167E+10 | 0.410160E+10 | 0.475464E+09 |
September | 0.860862E+09 | 134318.81 | 0.860728E+09 | 0.307503E+10 | 0.619236E+09 |
October | 0.772948E+09 | 0.00 | 0.772948E+09 | 0.255171E+10 | 0.125129E+10 |
November | 0.567862E+09 | 0.00 | 0.567862E+09 | 0.104241E+10 | 0.273065E+10 |
December | 0.529421E+09 | 0.00 | 0.529421E+09 | 0.734714E+09 | 0.408579E+10 |
Annual Sum or Average | 0.100092E+11 | 0.236940E+09 | 0.977230E+10 | 0.292402E+11 | 0.245228E+11 |
Minimum of Months | 0.529421E+09 | 0.00 | 0.529421E+09 | 0.637791E+09 | 0.353001E+09 |
Maximum of Months | 0.117227E+10 | 0.104945E+09 | 0.110610E+10 | 0.457814E+10 | 0.487623E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.979623E+09 | 0.500059E+09 | 0.479565E+09 | 0.169261E+10 | 0.287010E+10 |
February | 0.984943E+09 | 0.476636E+09 | 0.508307E+09 | 0.185270E+10 | 0.213637E+10 |
March | 0.127184E+10 | 0.609195E+09 | 0.662642E+09 | 0.263547E+10 | 0.210017E+10 |
April | 0.135514E+10 | 0.610651E+09 | 0.744493E+09 | 0.334305E+10 | 0.122257E+10 |
May | 0.144100E+10 | 0.621048E+09 | 0.819955E+09 | 0.468714E+10 | 0.376670E+09 |
June | 0.141843E+10 | 0.561041E+09 | 0.857385E+09 | 0.491369E+10 | 0.322555E+09 |
July | 0.141267E+10 | 0.515123E+09 | 0.897550E+09 | 0.489393E+10 | 0.211020E+09 |
August | 0.130170E+10 | 0.445759E+09 | 0.855942E+09 | 0.446482E+10 | 0.291025E+09 |
September | 0.111515E+10 | 0.381390E+09 | 0.733761E+09 | 0.359955E+10 | 0.374707E+09 |
October | 0.114141E+10 | 0.481423E+09 | 0.659986E+09 | 0.340195E+10 | 0.769707E+09 |
November | 0.981375E+09 | 0.502133E+09 | 0.479242E+09 | 0.214784E+10 | 0.163710E+10 |
December | 0.803248E+09 | 0.367845E+09 | 0.435403E+09 | 0.150989E+10 | 0.246953E+10 |
Annual Sum or Average | 0.142065E+11 | 0.607230E+10 | 0.813423E+10 | 0.391426E+11 | 0.147815E+11 |
Minimum of Months | 0.803248E+09 | 0.367845E+09 | 0.435403E+09 | 0.150989E+10 | 0.211020E+09 |
Maximum of Months | 0.144100E+10 | 0.621048E+09 | 0.897550E+09 | 0.491369E+10 | 0.287010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324158E+10 | 0.229741E+10 | 0.944176E+09 | 0.698875E+10 | 0.423076E+10 |
February | 0.270363E+10 | 0.175251E+10 | 0.951124E+09 | 0.594476E+10 | 0.323097E+10 |
March | 0.198997E+10 | 0.944152E+09 | 0.104582E+10 | 0.453941E+10 | 0.328185E+10 |
April | 0.145932E+10 | 0.412538E+09 | 0.104678E+10 | 0.384429E+10 | 0.196636E+10 |
May | 0.110772E+10 | 74185018.44 | 0.103354E+10 | 0.416663E+10 | 0.584007E+09 |
June | 0.104047E+10 | 18212582.80 | 0.102226E+10 | 0.422625E+10 | 0.503602E+09 |
July | 0.113064E+10 | 34944871.77 | 0.109570E+10 | 0.444385E+10 | 0.324257E+09 |
August | 0.136392E+10 | 0.208371E+09 | 0.115554E+10 | 0.523155E+10 | 0.472765E+09 |
September | 0.159092E+10 | 0.468006E+09 | 0.112291E+10 | 0.537936E+10 | 0.630231E+09 |
October | 0.248633E+10 | 0.131518E+10 | 0.117115E+10 | 0.761472E+10 | 0.127432E+10 |
November | 0.298041E+10 | 0.204268E+10 | 0.937725E+09 | 0.742266E+10 | 0.256757E+10 |
December | 0.315264E+10 | 0.224606E+10 | 0.906579E+09 | 0.734616E+10 | 0.369939E+10 |
Annual Sum or Average | 0.242475E+11 | 0.118142E+11 | 0.124333E+11 | 0.671484E+11 | 0.227661E+11 |
Minimum of Months | 0.104047E+10 | 18212582.80 | 0.906579E+09 | 0.384429E+10 | 0.324257E+09 |
Maximum of Months | 0.324158E+10 | 0.229741E+10 | 0.117115E+10 | 0.761472E+10 | 0.423076E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104138E+10 | 0.564072E+09 | 0.477312E+09 | 0.199978E+10 | 0.303979E+10 |
February | 0.106342E+10 | 0.538509E+09 | 0.524907E+09 | 0.214062E+10 | 0.228540E+10 |
March | 0.115715E+10 | 0.510764E+09 | 0.646384E+09 | 0.250404E+10 | 0.221659E+10 |
April | 0.138739E+10 | 0.634635E+09 | 0.752750E+09 | 0.360371E+10 | 0.130244E+10 |
May | 0.119780E+10 | 0.390086E+09 | 0.807711E+09 | 0.421780E+10 | 0.400107E+09 |
June | 0.128720E+10 | 0.450928E+09 | 0.836269E+09 | 0.462885E+10 | 0.349804E+09 |
July | 0.121643E+10 | 0.338634E+09 | 0.877798E+09 | 0.437013E+10 | 0.224992E+09 |
August | 0.122712E+10 | 0.374847E+09 | 0.852277E+09 | 0.444196E+10 | 0.314730E+09 |
September | 0.109243E+10 | 0.373372E+09 | 0.719061E+09 | 0.369174E+10 | 0.394165E+09 |
October | 0.115638E+10 | 0.498774E+09 | 0.657606E+09 | 0.370348E+10 | 0.821376E+09 |
November | 0.963556E+09 | 0.485777E+09 | 0.477779E+09 | 0.235597E+10 | 0.176211E+10 |
December | 0.958890E+09 | 0.511891E+09 | 0.446999E+09 | 0.206166E+10 | 0.256540E+10 |
Annual Sum or Average | 0.137491E+11 | 0.567229E+10 | 0.807685E+10 | 0.397197E+11 | 0.156769E+11 |
Minimum of Months | 0.958890E+09 | 0.338634E+09 | 0.446999E+09 | 0.199978E+10 | 0.224992E+09 |
Maximum of Months | 0.138739E+10 | 0.634635E+09 | 0.877798E+09 | 0.462885E+10 | 0.303979E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189828E+09 | 0.00 | 0.189828E+09 | 0.211095E+09 | 0.176113E+10 |
February | 0.202279E+09 | 0.00 | 0.202279E+09 | 0.271863E+09 | 0.128518E+10 |
March | 0.259803E+09 | 0.00 | 0.259803E+09 | 0.451355E+09 | 0.120365E+10 |
April | 0.297584E+09 | 2067842.08 | 0.295516E+09 | 0.712220E+09 | 0.665488E+09 |
May | 0.352453E+09 | 17845562.52 | 0.334607E+09 | 0.135046E+10 | 0.191667E+09 |
June | 0.390741E+09 | 34980691.76 | 0.355760E+09 | 0.156174E+10 | 0.171571E+09 |
July | 0.388593E+09 | 19905817.69 | 0.368688E+09 | 0.152599E+10 | 0.122751E+09 |
August | 0.344676E+09 | 4132759.00 | 0.340543E+09 | 0.136982E+10 | 0.191007E+09 |
September | 0.286944E+09 | 44771.53 | 0.286899E+09 | 0.102190E+10 | 0.263165E+09 |
October | 0.257639E+09 | 0.00 | 0.257639E+09 | 0.841059E+09 | 0.497579E+09 |
November | 0.189280E+09 | 0.00 | 0.189280E+09 | 0.328412E+09 | 0.105637E+10 |
December | 0.176467E+09 | 0.00 | 0.176467E+09 | 0.231539E+09 | 0.151532E+10 |
Annual Sum or Average | 0.333629E+10 | 78977444.58 | 0.325731E+10 | 0.987745E+10 | 0.892488E+10 |
Minimum of Months | 0.176467E+09 | 0.00 | 0.176467E+09 | 0.211095E+09 | 0.122751E+09 |
Maximum of Months | 0.390741E+09 | 34980691.76 | 0.368688E+09 | 0.156174E+10 | 0.176113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189837E+09 | 0.00 | 0.189837E+09 | 0.211105E+09 | 0.176124E+10 |
February | 0.202289E+09 | 0.00 | 0.202289E+09 | 0.271877E+09 | 0.128526E+10 |
March | 0.259816E+09 | 0.00 | 0.259816E+09 | 0.451377E+09 | 0.120372E+10 |
April | 0.297598E+09 | 2067921.93 | 0.295530E+09 | 0.712257E+09 | 0.665527E+09 |
May | 0.352470E+09 | 17846251.60 | 0.334623E+09 | 0.135053E+10 | 0.191676E+09 |
June | 0.390759E+09 | 34982042.48 | 0.355777E+09 | 0.156183E+10 | 0.171579E+09 |
July | 0.388611E+09 | 19906586.32 | 0.368705E+09 | 0.152607E+10 | 0.122756E+09 |
August | 0.344693E+09 | 4132918.58 | 0.340560E+09 | 0.136989E+10 | 0.191016E+09 |
September | 0.286957E+09 | 44773.26 | 0.286912E+09 | 0.102195E+10 | 0.263178E+09 |
October | 0.257652E+09 | 0.00 | 0.257652E+09 | 0.841104E+09 | 0.497607E+09 |
November | 0.189289E+09 | 0.00 | 0.189289E+09 | 0.328429E+09 | 0.105643E+10 |
December | 0.176475E+09 | 0.00 | 0.176475E+09 | 0.231550E+09 | 0.151541E+10 |
Annual Sum or Average | 0.333645E+10 | 78980494.16 | 0.325747E+10 | 0.987797E+10 | 0.892540E+10 |
Minimum of Months | 0.176475E+09 | 0.00 | 0.176475E+09 | 0.211105E+09 | 0.122756E+09 |
Maximum of Months | 0.390759E+09 | 34982042.48 | 0.368705E+09 | 0.156183E+10 | 0.176124E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189837E+09 | 0.00 | 0.189837E+09 | 0.211105E+09 | 0.176124E+10 |
February | 0.202289E+09 | 0.00 | 0.202289E+09 | 0.271877E+09 | 0.128526E+10 |
March | 0.259816E+09 | 0.00 | 0.259816E+09 | 0.451377E+09 | 0.120372E+10 |
April | 0.297598E+09 | 2067921.93 | 0.295530E+09 | 0.712257E+09 | 0.665527E+09 |
May | 0.352470E+09 | 17846251.60 | 0.334623E+09 | 0.135053E+10 | 0.191676E+09 |
June | 0.390759E+09 | 34982042.48 | 0.355777E+09 | 0.156183E+10 | 0.171579E+09 |
July | 0.388611E+09 | 19906586.32 | 0.368705E+09 | 0.152607E+10 | 0.122756E+09 |
August | 0.344693E+09 | 4132918.58 | 0.340560E+09 | 0.136989E+10 | 0.191016E+09 |
September | 0.286957E+09 | 44773.26 | 0.286912E+09 | 0.102195E+10 | 0.263178E+09 |
October | 0.257652E+09 | 0.00 | 0.257652E+09 | 0.841104E+09 | 0.497607E+09 |
November | 0.189289E+09 | 0.00 | 0.189289E+09 | 0.328429E+09 | 0.105643E+10 |
December | 0.176475E+09 | 0.00 | 0.176475E+09 | 0.231550E+09 | 0.151541E+10 |
Annual Sum or Average | 0.333645E+10 | 78980494.16 | 0.325747E+10 | 0.987797E+10 | 0.892540E+10 |
Minimum of Months | 0.176475E+09 | 0.00 | 0.176475E+09 | 0.211105E+09 | 0.122756E+09 |
Maximum of Months | 0.390759E+09 | 34982042.48 | 0.368705E+09 | 0.156183E+10 | 0.176124E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.942396E+09 | 0.481058E+09 | 0.461338E+09 | 0.163783E+10 | 0.304493E+10 |
February | 0.947513E+09 | 0.458525E+09 | 0.488988E+09 | 0.182099E+10 | 0.223465E+10 |
March | 0.122350E+10 | 0.586048E+09 | 0.637457E+09 | 0.263828E+10 | 0.214348E+10 |
April | 0.130364E+10 | 0.587449E+09 | 0.716196E+09 | 0.334580E+10 | 0.122614E+10 |
May | 0.138624E+10 | 0.597450E+09 | 0.788791E+09 | 0.464161E+10 | 0.360104E+09 |
June | 0.136452E+10 | 0.539724E+09 | 0.824799E+09 | 0.483337E+10 | 0.314809E+09 |
July | 0.135899E+10 | 0.495551E+09 | 0.863437E+09 | 0.478438E+10 | 0.220173E+09 |
August | 0.125223E+10 | 0.428822E+09 | 0.823411E+09 | 0.432561E+10 | 0.342067E+09 |
September | 0.107277E+10 | 0.366898E+09 | 0.705874E+09 | 0.347997E+10 | 0.470182E+09 |
October | 0.109803E+10 | 0.463130E+09 | 0.634902E+09 | 0.330225E+10 | 0.885262E+09 |
November | 0.944081E+09 | 0.483054E+09 | 0.461027E+09 | 0.204178E+10 | 0.183236E+10 |
December | 0.772722E+09 | 0.353868E+09 | 0.418854E+09 | 0.144222E+10 | 0.266776E+10 |
Annual Sum or Average | 0.136666E+11 | 0.584158E+10 | 0.782507E+10 | 0.382941E+11 | 0.157419E+11 |
Minimum of Months | 0.772722E+09 | 0.353868E+09 | 0.418854E+09 | 0.144222E+10 | 0.220173E+09 |
Maximum of Months | 0.138624E+10 | 0.597450E+09 | 0.863437E+09 | 0.483337E+10 | 0.304493E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37261487.47 | 19020613.03 | 18240874.45 | 64758199.06 | 0.120394E+09 |
February | 37463803.12 | 18129675.19 | 19334127.93 | 72000341.77 | 88355943.10 |
March | 48376251.28 | 23171790.88 | 25204460.40 | 0.104315E+09 | 84751168.53 |
April | 51544925.44 | 23227185.61 | 28317739.83 | 0.132290E+09 | 48480608.83 |
May | 54810732.98 | 23622652.62 | 31188080.36 | 0.183525E+09 | 14238181.71 |
June | 53951995.89 | 21340196.04 | 32611799.85 | 0.191107E+09 | 12447250.86 |
July | 53733158.82 | 19593626.57 | 34139532.25 | 0.189170E+09 | 8705444.08 |
August | 49512162.10 | 16955243.67 | 32556918.43 | 0.171031E+09 | 13525034.09 |
September | 42416437.50 | 14506824.65 | 27909612.85 | 0.137595E+09 | 18590578.44 |
October | 43415207.89 | 18311757.44 | 25103450.45 | 0.130568E+09 | 35002470.27 |
November | 37328105.87 | 19099514.66 | 18228591.21 | 80730129.16 | 72449925.06 |
December | 30552745.48 | 13991630.63 | 16561114.85 | 57024116.32 | 0.105481E+09 |
Annual Sum or Average | 0.540367E+09 | 0.230971E+09 | 0.309396E+09 | 0.151411E+10 | 0.622421E+09 |
Minimum of Months | 30552745.48 | 13991630.63 | 16561114.85 | 57024116.32 | 8705444.08 |
Maximum of Months | 54810732.98 | 23622652.62 | 34139532.25 | 0.191107E+09 | 0.120394E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108056E+10 | 0.765823E+09 | 0.314733E+09 | 0.236769E+10 | 0.162217E+10 |
February | 0.901233E+09 | 0.584184E+09 | 0.317049E+09 | 0.202755E+10 | 0.121876E+10 |
March | 0.663340E+09 | 0.314726E+09 | 0.348615E+09 | 0.157400E+10 | 0.118277E+10 |
April | 0.486452E+09 | 0.137517E+09 | 0.348935E+09 | 0.133286E+10 | 0.686891E+09 |
May | 0.369249E+09 | 24729010.14 | 0.344520E+09 | 0.142319E+10 | 0.188170E+09 |
June | 0.346832E+09 | 6071025.58 | 0.340761E+09 | 0.143526E+10 | 0.164449E+09 |
July | 0.376889E+09 | 11648606.51 | 0.365241E+09 | 0.149675E+10 | 0.114104E+09 |
August | 0.454649E+09 | 69458921.01 | 0.385191E+09 | 0.174236E+10 | 0.196948E+09 |
September | 0.530319E+09 | 0.156006E+09 | 0.374313E+09 | 0.179537E+10 | 0.281314E+09 |
October | 0.828798E+09 | 0.438404E+09 | 0.390394E+09 | 0.255039E+10 | 0.530182E+09 |
November | 0.993496E+09 | 0.680913E+09 | 0.312582E+09 | 0.247604E+10 | 0.104446E+10 |
December | 0.105091E+10 | 0.748708E+09 | 0.302200E+09 | 0.247157E+10 | 0.144536E+10 |
Annual Sum or Average | 0.808272E+10 | 0.393819E+10 | 0.414453E+10 | 0.226930E+11 | 0.867557E+10 |
Minimum of Months | 0.346832E+09 | 6071025.58 | 0.302200E+09 | 0.133286E+10 | 0.114104E+09 |
Maximum of Months | 0.108056E+10 | 0.765823E+09 | 0.390394E+09 | 0.255039E+10 | 0.162217E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108056E+10 | 0.765823E+09 | 0.314733E+09 | 0.236769E+10 | 0.162217E+10 |
February | 0.901233E+09 | 0.584184E+09 | 0.317049E+09 | 0.202755E+10 | 0.121876E+10 |
March | 0.663340E+09 | 0.314726E+09 | 0.348615E+09 | 0.157400E+10 | 0.118277E+10 |
April | 0.486452E+09 | 0.137517E+09 | 0.348935E+09 | 0.133286E+10 | 0.686891E+09 |
May | 0.369249E+09 | 24729010.14 | 0.344520E+09 | 0.142319E+10 | 0.188170E+09 |
June | 0.346832E+09 | 6071025.58 | 0.340761E+09 | 0.143526E+10 | 0.164449E+09 |
July | 0.376889E+09 | 11648606.51 | 0.365241E+09 | 0.149675E+10 | 0.114104E+09 |
August | 0.454649E+09 | 69458921.01 | 0.385191E+09 | 0.174236E+10 | 0.196948E+09 |
September | 0.530319E+09 | 0.156006E+09 | 0.374313E+09 | 0.179537E+10 | 0.281314E+09 |
October | 0.828798E+09 | 0.438404E+09 | 0.390394E+09 | 0.255039E+10 | 0.530182E+09 |
November | 0.993496E+09 | 0.680913E+09 | 0.312582E+09 | 0.247604E+10 | 0.104446E+10 |
December | 0.105091E+10 | 0.748708E+09 | 0.302200E+09 | 0.247157E+10 | 0.144536E+10 |
Annual Sum or Average | 0.808272E+10 | 0.393819E+10 | 0.414453E+10 | 0.226930E+11 | 0.867557E+10 |
Minimum of Months | 0.346832E+09 | 6071025.58 | 0.302200E+09 | 0.133286E+10 | 0.114104E+09 |
Maximum of Months | 0.108056E+10 | 0.765823E+09 | 0.390394E+09 | 0.255039E+10 | 0.162217E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108049E+10 | 0.765774E+09 | 0.314713E+09 | 0.236754E+10 | 0.162207E+10 |
February | 0.901176E+09 | 0.584147E+09 | 0.317029E+09 | 0.202742E+10 | 0.121868E+10 |
March | 0.663299E+09 | 0.314706E+09 | 0.348593E+09 | 0.157390E+10 | 0.118270E+10 |
April | 0.486421E+09 | 0.137508E+09 | 0.348913E+09 | 0.133278E+10 | 0.686848E+09 |
May | 0.369225E+09 | 24727447.41 | 0.344498E+09 | 0.142310E+10 | 0.188158E+09 |
June | 0.346810E+09 | 6070641.93 | 0.340739E+09 | 0.143517E+10 | 0.164439E+09 |
July | 0.376866E+09 | 11647870.38 | 0.365218E+09 | 0.149666E+10 | 0.114097E+09 |
August | 0.454621E+09 | 69454531.60 | 0.385166E+09 | 0.174225E+10 | 0.196936E+09 |
September | 0.530286E+09 | 0.155996E+09 | 0.374290E+09 | 0.179526E+10 | 0.281297E+09 |
October | 0.828746E+09 | 0.438376E+09 | 0.390369E+09 | 0.255023E+10 | 0.530148E+09 |
November | 0.993433E+09 | 0.680870E+09 | 0.312563E+09 | 0.247588E+10 | 0.104439E+10 |
December | 0.105084E+10 | 0.748661E+09 | 0.302181E+09 | 0.247141E+10 | 0.144527E+10 |
Annual Sum or Average | 0.808221E+10 | 0.393794E+10 | 0.414427E+10 | 0.226916E+11 | 0.867503E+10 |
Minimum of Months | 0.346810E+09 | 6070641.93 | 0.302181E+09 | 0.133278E+10 | 0.114097E+09 |
Maximum of Months | 0.108049E+10 | 0.765774E+09 | 0.390369E+09 | 0.255023E+10 | 0.162207E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100181E+10 | 0.542638E+09 | 0.459170E+09 | 0.197400E+10 | 0.324273E+10 |
February | 0.102300E+10 | 0.518046E+09 | 0.504956E+09 | 0.213696E+10 | 0.240466E+10 |
March | 0.111317E+10 | 0.491355E+09 | 0.621815E+09 | 0.252835E+10 | 0.227320E+10 |
April | 0.133466E+10 | 0.610520E+09 | 0.724138E+09 | 0.359970E+10 | 0.131533E+10 |
May | 0.115227E+10 | 0.375263E+09 | 0.777011E+09 | 0.413631E+10 | 0.381122E+09 |
June | 0.123828E+10 | 0.433793E+09 | 0.804483E+09 | 0.452882E+10 | 0.345972E+09 |
July | 0.117020E+10 | 0.325766E+09 | 0.844434E+09 | 0.424862E+10 | 0.231334E+09 |
August | 0.118049E+10 | 0.360604E+09 | 0.819884E+09 | 0.426688E+10 | 0.375039E+09 |
September | 0.105091E+10 | 0.359184E+09 | 0.691731E+09 | 0.352926E+10 | 0.501658E+09 |
October | 0.111243E+10 | 0.479821E+09 | 0.632611E+09 | 0.354674E+10 | 0.947793E+09 |
November | 0.926937E+09 | 0.467317E+09 | 0.459619E+09 | 0.226682E+10 | 0.198035E+10 |
December | 0.922448E+09 | 0.492439E+09 | 0.430009E+09 | 0.200351E+10 | 0.279732E+10 |
Annual Sum or Average | 0.132266E+11 | 0.545675E+10 | 0.776986E+10 | 0.387660E+11 | 0.167965E+11 |
Minimum of Months | 0.922448E+09 | 0.325766E+09 | 0.430009E+09 | 0.197400E+10 | 0.231334E+09 |
Maximum of Months | 0.133466E+10 | 0.610520E+09 | 0.844434E+09 | 0.452882E+10 | 0.324273E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39610569.67 | 21455406.69 | 18155162.98 | 78050288.22 | 0.128215E+09 |
February | 40448570.57 | 20483083.50 | 19965487.07 | 84493662.27 | 95078197.30 |
March | 44013754.07 | 19427750.25 | 24586003.82 | 99968520.60 | 89880273.46 |
April | 52771171.30 | 24139399.61 | 28631771.70 | 0.142329E+09 | 52007072.40 |
May | 45559870.82 | 14837562.45 | 30722308.37 | 0.163546E+09 | 15069217.03 |
June | 48960335.62 | 17151802.41 | 31808533.21 | 0.179066E+09 | 13679423.24 |
July | 46268665.38 | 12880506.70 | 33388158.67 | 0.167987E+09 | 9146745.41 |
August | 46675413.70 | 14257940.61 | 32417473.08 | 0.168709E+09 | 14828718.79 |
September | 41552224.93 | 14201818.42 | 27350406.51 | 0.139544E+09 | 19835122.44 |
October | 43984561.35 | 18971698.08 | 25012863.27 | 0.140235E+09 | 37474892.94 |
November | 36650235.12 | 18477312.72 | 18172922.41 | 89627928.88 | 78301410.78 |
December | 36472779.68 | 19470600.80 | 17002178.88 | 79216931.55 | 0.110603E+09 |
Annual Sum or Average | 0.522968E+09 | 0.215755E+09 | 0.307213E+09 | 0.153277E+10 | 0.664119E+09 |
Minimum of Months | 36472779.68 | 12880506.70 | 17002178.88 | 78050288.22 | 9146745.41 |
Maximum of Months | 52771171.30 | 24139399.61 | 33388158.67 | 0.179066E+09 | 0.128215E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.569506E+09 | 0.00 | 0.569506E+09 | 0.611785E+09 | 0.523523E+10 |
February | 0.606859E+09 | 0.00 | 0.606859E+09 | 0.766155E+09 | 0.388640E+10 |
March | 0.779439E+09 | 0.00 | 0.779439E+09 | 0.125373E+10 | 0.371283E+10 |
April | 0.892785E+09 | 6203721.83 | 0.886582E+09 | 0.201495E+10 | 0.210579E+10 |
May | 0.105740E+10 | 53538375.48 | 0.100386E+10 | 0.397077E+10 | 0.635159E+09 |
June | 0.117227E+10 | 0.104945E+09 | 0.106732E+10 | 0.462650E+10 | 0.547300E+09 |
July | 0.116582E+10 | 59719335.86 | 0.110610E+10 | 0.455316E+10 | 0.372481E+09 |
August | 0.103407E+10 | 12398667.89 | 0.102167E+10 | 0.413507E+10 | 0.516990E+09 |
September | 0.860862E+09 | 134318.81 | 0.860728E+09 | 0.308514E+10 | 0.704667E+09 |
October | 0.772948E+09 | 0.00 | 0.772948E+09 | 0.254449E+10 | 0.139174E+10 |
November | 0.567862E+09 | 0.00 | 0.567862E+09 | 0.993442E+09 | 0.303980E+10 |
December | 0.529421E+09 | 0.00 | 0.529421E+09 | 0.699333E+09 | 0.443415E+10 |
Annual Sum or Average | 0.100092E+11 | 0.236940E+09 | 0.977230E+10 | 0.292545E+11 | 0.265825E+11 |
Minimum of Months | 0.529421E+09 | 0.00 | 0.529421E+09 | 0.611785E+09 | 0.372481E+09 |
Maximum of Months | 0.117227E+10 | 0.104945E+09 | 0.110610E+10 | 0.462650E+10 | 0.523523E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.979623E+09 | 0.500059E+09 | 0.479565E+09 | 0.167418E+10 | 0.306090E+10 |
February | 0.984943E+09 | 0.476636E+09 | 0.508307E+09 | 0.184477E+10 | 0.228115E+10 |
March | 0.127184E+10 | 0.609195E+09 | 0.662642E+09 | 0.265119E+10 | 0.222267E+10 |
April | 0.135514E+10 | 0.610651E+09 | 0.744493E+09 | 0.337085E+10 | 0.129347E+10 |
May | 0.144100E+10 | 0.621048E+09 | 0.819955E+09 | 0.472977E+10 | 0.390946E+09 |
June | 0.141843E+10 | 0.561041E+09 | 0.857385E+09 | 0.495642E+10 | 0.333206E+09 |
July | 0.141267E+10 | 0.515123E+09 | 0.897550E+09 | 0.494159E+10 | 0.215734E+09 |
August | 0.130170E+10 | 0.445759E+09 | 0.855942E+09 | 0.449946E+10 | 0.304205E+09 |
September | 0.111515E+10 | 0.381390E+09 | 0.733761E+09 | 0.362626E+10 | 0.411167E+09 |
October | 0.114141E+10 | 0.481423E+09 | 0.659986E+09 | 0.342407E+10 | 0.833589E+09 |
November | 0.981375E+09 | 0.502133E+09 | 0.479242E+09 | 0.212081E+10 | 0.178589E+10 |
December | 0.803248E+09 | 0.367845E+09 | 0.435403E+09 | 0.149158E+10 | 0.265383E+10 |
Annual Sum or Average | 0.142065E+11 | 0.607230E+10 | 0.813423E+10 | 0.393310E+11 | 0.157868E+11 |
Minimum of Months | 0.803248E+09 | 0.367845E+09 | 0.435403E+09 | 0.149158E+10 | 0.215734E+09 |
Maximum of Months | 0.144100E+10 | 0.621048E+09 | 0.897550E+09 | 0.495642E+10 | 0.306090E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324158E+10 | 0.229741E+10 | 0.944176E+09 | 0.694823E+10 | 0.456647E+10 |
February | 0.270363E+10 | 0.175251E+10 | 0.951124E+09 | 0.592714E+10 | 0.349901E+10 |
March | 0.198997E+10 | 0.944152E+09 | 0.104582E+10 | 0.454714E+10 | 0.351984E+10 |
April | 0.145932E+10 | 0.412538E+09 | 0.104678E+10 | 0.385714E+10 | 0.211563E+10 |
May | 0.110772E+10 | 74185018.44 | 0.103354E+10 | 0.419457E+10 | 0.622665E+09 |
June | 0.104047E+10 | 18212582.80 | 0.102226E+10 | 0.426668E+10 | 0.533263E+09 |
July | 0.113064E+10 | 34944871.77 | 0.109570E+10 | 0.448677E+10 | 0.343935E+09 |
August | 0.136392E+10 | 0.208371E+09 | 0.115554E+10 | 0.526920E+10 | 0.511341E+09 |
September | 0.159092E+10 | 0.468006E+09 | 0.112291E+10 | 0.539998E+10 | 0.711875E+09 |
October | 0.248633E+10 | 0.131518E+10 | 0.117115E+10 | 0.763833E+10 | 0.139694E+10 |
November | 0.298041E+10 | 0.204268E+10 | 0.937725E+09 | 0.738361E+10 | 0.282862E+10 |
December | 0.315264E+10 | 0.224606E+10 | 0.906579E+09 | 0.731343E+10 | 0.401790E+10 |
Annual Sum or Average | 0.242475E+11 | 0.118142E+11 | 0.124333E+11 | 0.672322E+11 | 0.246675E+11 |
Minimum of Months | 0.104047E+10 | 18212582.80 | 0.906579E+09 | 0.385714E+10 | 0.343935E+09 |
Maximum of Months | 0.324158E+10 | 0.229741E+10 | 0.117115E+10 | 0.763833E+10 | 0.456647E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104138E+10 | 0.564072E+09 | 0.477312E+09 | 0.200298E+10 | 0.326615E+10 |
February | 0.106342E+10 | 0.538509E+09 | 0.524907E+09 | 0.215568E+10 | 0.245980E+10 |
March | 0.115715E+10 | 0.510764E+09 | 0.646384E+09 | 0.253362E+10 | 0.236921E+10 |
April | 0.138739E+10 | 0.634635E+09 | 0.752750E+09 | 0.363531E+10 | 0.139827E+10 |
May | 0.119780E+10 | 0.390086E+09 | 0.807711E+09 | 0.423685E+10 | 0.425392E+09 |
June | 0.128720E+10 | 0.450928E+09 | 0.836269E+09 | 0.466196E+10 | 0.370073E+09 |
July | 0.121643E+10 | 0.338634E+09 | 0.877798E+09 | 0.440048E+10 | 0.237674E+09 |
August | 0.122712E+10 | 0.374847E+09 | 0.852277E+09 | 0.446368E+10 | 0.337212E+09 |
September | 0.109243E+10 | 0.373372E+09 | 0.719061E+09 | 0.369574E+10 | 0.444753E+09 |
October | 0.115638E+10 | 0.498774E+09 | 0.657606E+09 | 0.370788E+10 | 0.898799E+09 |
November | 0.963556E+09 | 0.485777E+09 | 0.477779E+09 | 0.234899E+10 | 0.194379E+10 |
December | 0.958890E+09 | 0.511891E+09 | 0.446999E+09 | 0.205957E+10 | 0.278036E+10 |
Annual Sum or Average | 0.137491E+11 | 0.567229E+10 | 0.807685E+10 | 0.399027E+11 | 0.169315E+11 |
Minimum of Months | 0.958890E+09 | 0.338634E+09 | 0.446999E+09 | 0.200298E+10 | 0.237674E+09 |
Maximum of Months | 0.138739E+10 | 0.634635E+09 | 0.877798E+09 | 0.466196E+10 | 0.326615E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 238.12 | 1820.57 | 212.63 | 0.00 | 212.63 | 0.00 | 0.00 |
February | 325.64 | 1491.04 | 250.85 | 0.00 | 250.85 | 0.00 | 0.00 |
March | 470.18 | 1292.09 | 291.01 | 0.00 | 291.01 | 0.00 | 0.00 |
April | 779.85 | 751.34 | 344.44 | 2.39 | 342.05 | 0.00 | 0.00 |
May | 1472.26 | 223.24 | 394.79 | 19.99 | 374.80 | 0.00 | 0.00 |
June | 1766.26 | 199.79 | 452.26 | 40.49 | 411.77 | 0.00 | 0.00 |
July | 1682.74 | 131.80 | 435.27 | 22.30 | 412.97 | 0.00 | 0.00 |
August | 1531.36 | 177.52 | 386.08 | 4.63 | 381.45 | 0.00 | 0.00 |
September | 1186.35 | 238.90 | 332.12 | 0.05 | 332.07 | 0.00 | 0.00 |
October | 952.70 | 467.18 | 288.59 | 0.00 | 288.59 | 0.00 | 0.00 |
November | 402.17 | 1053.49 | 219.08 | 0.00 | 219.08 | 0.00 | 0.00 |
December | 274.31 | 1525.46 | 197.66 | 0.00 | 197.66 | 0.00 | 0.00 |
Annual Sum or Average | 927.20 | 777.61 | 317.39 | 7.51 | 309.88 | 0.00 | 0.00 |
Minimum of Months | 238.12 | 131.80 | 197.66 | 0.00 | 197.66 | 0.00 | 0.00 |
Maximum of Months | 1766.26 | 1820.57 | 452.26 | 40.49 | 412.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 631.95 | 1071.57 | 365.75 | 186.70 | 179.05 | 0.00 | 0.00 |
February | 765.83 | 883.09 | 407.14 | 197.02 | 210.11 | 0.00 | 0.00 |
March | 983.97 | 784.11 | 474.85 | 227.45 | 247.40 | 0.00 | 0.00 |
April | 1289.76 | 471.67 | 522.82 | 235.59 | 287.23 | 0.00 | 0.00 |
May | 1749.98 | 140.63 | 538.01 | 231.87 | 306.14 | 0.00 | 0.00 |
June | 1895.71 | 124.44 | 547.23 | 216.45 | 330.78 | 0.00 | 0.00 |
July | 1827.19 | 78.79 | 527.43 | 192.33 | 335.11 | 0.00 | 0.00 |
August | 1666.97 | 108.66 | 486.00 | 166.43 | 319.57 | 0.00 | 0.00 |
September | 1388.71 | 144.56 | 430.23 | 147.14 | 283.09 | 0.00 | 0.00 |
October | 1270.14 | 287.38 | 426.15 | 179.74 | 246.41 | 0.00 | 0.00 |
November | 828.64 | 631.60 | 378.62 | 193.72 | 184.89 | 0.00 | 0.00 |
December | 563.73 | 922.02 | 299.90 | 137.34 | 162.56 | 0.00 | 0.00 |
Annual Sum or Average | 1241.20 | 468.72 | 450.49 | 192.55 | 257.93 | 0.00 | 0.00 |
Minimum of Months | 563.73 | 78.79 | 299.90 | 137.34 | 162.56 | 0.00 | 0.00 |
Maximum of Months | 1895.71 | 1071.57 | 547.23 | 235.59 | 335.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2609.30 | 1579.58 | 1210.27 | 857.75 | 352.52 | 0.00 | 0.00 |
February | 2457.33 | 1335.55 | 1117.57 | 724.42 | 393.16 | 0.00 | 0.00 |
March | 1694.82 | 1225.30 | 742.97 | 352.51 | 390.46 | 0.00 | 0.00 |
April | 1483.14 | 758.62 | 563.01 | 159.16 | 403.85 | 0.00 | 0.00 |
May | 1555.64 | 218.04 | 413.58 | 27.70 | 385.88 | 0.00 | 0.00 |
June | 1630.50 | 194.29 | 401.42 | 7.03 | 394.39 | 0.00 | 0.00 |
July | 1659.14 | 121.06 | 422.13 | 13.05 | 409.09 | 0.00 | 0.00 |
August | 1953.24 | 176.51 | 509.23 | 77.80 | 431.43 | 0.00 | 0.00 |
September | 2075.37 | 243.14 | 613.78 | 180.56 | 433.22 | 0.00 | 0.00 |
October | 2843.01 | 475.78 | 928.29 | 491.03 | 437.26 | 0.00 | 0.00 |
November | 2863.68 | 990.58 | 1149.85 | 788.07 | 361.78 | 0.00 | 0.00 |
December | 2742.74 | 1381.19 | 1177.06 | 838.58 | 338.48 | 0.00 | 0.00 |
Annual Sum or Average | 2129.26 | 721.91 | 768.88 | 374.63 | 394.26 | 0.00 | 0.00 |
Minimum of Months | 1483.14 | 121.06 | 401.42 | 7.03 | 338.48 | 0.00 | 0.00 |
Maximum of Months | 2863.68 | 1579.58 | 1210.27 | 857.75 | 437.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 746.63 | 1134.93 | 388.81 | 210.60 | 178.21 | 0.00 | 0.00 |
February | 884.84 | 944.69 | 439.57 | 222.60 | 216.98 | 0.00 | 0.00 |
March | 934.90 | 827.58 | 432.03 | 190.70 | 241.33 | 0.00 | 0.00 |
April | 1390.32 | 502.49 | 535.26 | 244.84 | 290.41 | 0.00 | 0.00 |
May | 1574.74 | 149.38 | 447.21 | 145.64 | 301.56 | 0.00 | 0.00 |
June | 1785.82 | 134.96 | 496.60 | 173.97 | 322.63 | 0.00 | 0.00 |
July | 1631.62 | 84.00 | 454.16 | 126.43 | 327.73 | 0.00 | 0.00 |
August | 1658.44 | 117.51 | 458.16 | 139.95 | 318.20 | 0.00 | 0.00 |
September | 1424.28 | 152.07 | 421.46 | 144.05 | 277.42 | 0.00 | 0.00 |
October | 1382.72 | 306.67 | 431.74 | 186.22 | 245.52 | 0.00 | 0.00 |
November | 908.94 | 679.83 | 371.74 | 187.41 | 184.33 | 0.00 | 0.00 |
December | 769.74 | 957.81 | 358.01 | 191.12 | 166.89 | 0.00 | 0.00 |
Annual Sum or Average | 1259.50 | 497.11 | 435.98 | 179.87 | 256.12 | 0.00 | 0.00 |
Minimum of Months | 746.63 | 84.00 | 358.01 | 126.43 | 166.89 | 0.00 | 0.00 |
Maximum of Months | 1785.82 | 1134.93 | 535.26 | 244.84 | 327.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.45 | 1972.67 | 212.63 | 0.00 | 212.63 | 0.00 | 0.00 |
February | 337.14 | 1593.79 | 250.85 | 0.00 | 250.85 | 0.00 | 0.00 |
March | 505.57 | 1348.23 | 291.01 | 0.00 | 291.01 | 0.00 | 0.00 |
April | 824.36 | 770.27 | 344.44 | 2.39 | 342.04 | 0.00 | 0.00 |
May | 1512.66 | 214.69 | 394.78 | 19.99 | 374.80 | 0.00 | 0.00 |
June | 1807.64 | 198.58 | 452.26 | 40.49 | 411.77 | 0.00 | 0.00 |
July | 1709.28 | 137.49 | 435.27 | 22.30 | 412.97 | 0.00 | 0.00 |
August | 1534.35 | 213.95 | 386.07 | 4.63 | 381.45 | 0.00 | 0.00 |
September | 1182.79 | 304.60 | 332.12 | 0.05 | 332.07 | 0.00 | 0.00 |
October | 942.08 | 557.35 | 288.58 | 0.00 | 288.58 | 0.00 | 0.00 |
November | 380.12 | 1222.70 | 219.08 | 0.00 | 219.08 | 0.00 | 0.00 |
December | 259.35 | 1697.33 | 197.66 | 0.00 | 197.66 | 0.00 | 0.00 |
Annual Sum or Average | 939.67 | 849.05 | 317.39 | 7.51 | 309.88 | 0.00 | 0.00 |
Minimum of Months | 236.45 | 137.49 | 197.66 | 0.00 | 197.66 | 0.00 | 0.00 |
Maximum of Months | 1807.64 | 1972.67 | 452.26 | 40.49 | 412.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 635.67 | 1181.80 | 365.76 | 186.71 | 179.05 | 0.00 | 0.00 |
February | 782.49 | 960.24 | 407.15 | 197.03 | 210.12 | 0.00 | 0.00 |
March | 1023.97 | 831.93 | 474.87 | 227.46 | 247.41 | 0.00 | 0.00 |
April | 1341.86 | 491.75 | 522.84 | 235.60 | 287.24 | 0.00 | 0.00 |
May | 1801.50 | 139.76 | 538.03 | 231.88 | 306.15 | 0.00 | 0.00 |
June | 1938.46 | 126.26 | 547.25 | 216.46 | 330.79 | 0.00 | 0.00 |
July | 1856.91 | 85.45 | 527.45 | 192.33 | 335.12 | 0.00 | 0.00 |
August | 1678.85 | 132.76 | 486.02 | 166.43 | 319.58 | 0.00 | 0.00 |
September | 1395.66 | 188.57 | 430.24 | 147.15 | 283.10 | 0.00 | 0.00 |
October | 1281.67 | 343.59 | 426.17 | 179.75 | 246.42 | 0.00 | 0.00 |
November | 818.87 | 734.88 | 378.63 | 193.73 | 184.90 | 0.00 | 0.00 |
December | 559.75 | 1035.41 | 299.91 | 137.34 | 162.57 | 0.00 | 0.00 |
Annual Sum or Average | 1262.31 | 518.91 | 450.50 | 192.56 | 257.94 | 0.00 | 0.00 |
Minimum of Months | 559.75 | 85.45 | 299.91 | 137.34 | 162.57 | 0.00 | 0.00 |
Maximum of Months | 1938.46 | 1181.80 | 547.25 | 235.60 | 335.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2651.92 | 1816.91 | 1210.27 | 857.76 | 352.52 | 0.00 | 0.00 |
February | 2514.27 | 1511.32 | 1117.58 | 724.42 | 393.16 | 0.00 | 0.00 |
March | 1762.95 | 1324.76 | 742.97 | 352.51 | 390.47 | 0.00 | 0.00 |
April | 1542.63 | 795.00 | 563.01 | 159.16 | 403.85 | 0.00 | 0.00 |
May | 1594.04 | 210.76 | 413.58 | 27.70 | 385.88 | 0.00 | 0.00 |
June | 1661.15 | 190.33 | 401.42 | 7.03 | 394.39 | 0.00 | 0.00 |
July | 1676.43 | 127.80 | 422.13 | 13.05 | 409.09 | 0.00 | 0.00 |
August | 1951.52 | 220.59 | 509.23 | 77.80 | 431.43 | 0.00 | 0.00 |
September | 2077.93 | 325.59 | 613.78 | 180.56 | 433.22 | 0.00 | 0.00 |
October | 2856.56 | 593.83 | 928.29 | 491.03 | 437.26 | 0.00 | 0.00 |
November | 2865.73 | 1208.84 | 1149.85 | 788.08 | 361.78 | 0.00 | 0.00 |
December | 2768.28 | 1618.87 | 1177.07 | 838.59 | 338.48 | 0.00 | 0.00 |
Annual Sum or Average | 2158.73 | 825.28 | 768.89 | 374.63 | 394.26 | 0.00 | 0.00 |
Minimum of Months | 1542.63 | 127.80 | 401.42 | 7.03 | 338.48 | 0.00 | 0.00 |
Maximum of Months | 2865.73 | 1816.91 | 1210.27 | 857.76 | 437.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 766.15 | 1258.57 | 388.82 | 210.61 | 178.21 | 0.00 | 0.00 |
February | 918.26 | 1033.29 | 439.59 | 222.61 | 216.98 | 0.00 | 0.00 |
March | 981.30 | 882.27 | 432.04 | 190.70 | 241.34 | 0.00 | 0.00 |
April | 1443.68 | 527.52 | 535.27 | 244.85 | 290.42 | 0.00 | 0.00 |
May | 1605.38 | 147.92 | 447.22 | 145.65 | 301.57 | 0.00 | 0.00 |
June | 1816.31 | 138.75 | 496.62 | 173.98 | 322.64 | 0.00 | 0.00 |
July | 1648.97 | 89.79 | 454.18 | 126.44 | 327.74 | 0.00 | 0.00 |
August | 1656.06 | 145.56 | 458.17 | 139.96 | 318.21 | 0.00 | 0.00 |
September | 1415.43 | 201.19 | 421.48 | 144.05 | 277.42 | 0.00 | 0.00 |
October | 1376.56 | 367.86 | 431.76 | 186.23 | 245.53 | 0.00 | 0.00 |
November | 909.12 | 794.23 | 371.75 | 187.42 | 184.33 | 0.00 | 0.00 |
December | 777.60 | 1085.69 | 358.02 | 191.13 | 166.89 | 0.00 | 0.00 |
Annual Sum or Average | 1277.86 | 553.67 | 436.00 | 179.87 | 256.12 | 0.00 | 0.00 |
Minimum of Months | 766.15 | 89.79 | 358.02 | 126.44 | 166.89 | 0.00 | 0.00 |
Maximum of Months | 1816.31 | 1258.57 | 535.27 | 244.85 | 327.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 228.41 | 1954.61 | 212.63 | 0.00 | 212.63 | 0.00 | 0.00 |
February | 316.70 | 1606.48 | 250.85 | 0.00 | 250.85 | 0.00 | 0.00 |
March | 468.09 | 1386.21 | 291.01 | 0.00 | 291.01 | 0.00 | 0.00 |
April | 777.37 | 812.42 | 344.44 | 2.39 | 342.05 | 0.00 | 0.00 |
May | 1482.52 | 237.14 | 394.79 | 19.99 | 374.80 | 0.00 | 0.00 |
June | 1784.91 | 211.15 | 452.26 | 40.49 | 411.77 | 0.00 | 0.00 |
July | 1699.96 | 139.07 | 435.27 | 22.30 | 412.97 | 0.00 | 0.00 |
August | 1543.86 | 193.02 | 386.08 | 4.63 | 381.45 | 0.00 | 0.00 |
September | 1190.26 | 271.86 | 332.12 | 0.05 | 332.07 | 0.00 | 0.00 |
October | 950.01 | 519.62 | 288.59 | 0.00 | 288.59 | 0.00 | 0.00 |
November | 383.27 | 1172.76 | 219.08 | 0.00 | 219.08 | 0.00 | 0.00 |
December | 261.10 | 1655.52 | 197.66 | 0.00 | 197.66 | 0.00 | 0.00 |
Annual Sum or Average | 927.66 | 842.93 | 317.39 | 7.51 | 309.88 | 0.00 | 0.00 |
Minimum of Months | 228.41 | 139.07 | 197.66 | 0.00 | 197.66 | 0.00 | 0.00 |
Maximum of Months | 1784.91 | 1954.61 | 452.26 | 40.49 | 412.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 625.07 | 1142.81 | 365.75 | 186.70 | 179.05 | 0.00 | 0.00 |
February | 762.55 | 942.93 | 407.14 | 197.02 | 210.11 | 0.00 | 0.00 |
March | 989.84 | 829.85 | 474.85 | 227.45 | 247.40 | 0.00 | 0.00 |
April | 1300.48 | 499.02 | 522.82 | 235.59 | 287.23 | 0.00 | 0.00 |
May | 1765.89 | 145.96 | 538.01 | 231.87 | 306.14 | 0.00 | 0.00 |
June | 1912.20 | 128.55 | 547.23 | 216.45 | 330.78 | 0.00 | 0.00 |
July | 1844.98 | 80.55 | 527.43 | 192.33 | 335.11 | 0.00 | 0.00 |
August | 1679.91 | 113.58 | 486.00 | 166.43 | 319.57 | 0.00 | 0.00 |
September | 1399.02 | 158.63 | 430.23 | 147.14 | 283.09 | 0.00 | 0.00 |
October | 1278.40 | 311.23 | 426.15 | 179.74 | 246.41 | 0.00 | 0.00 |
November | 818.21 | 689.00 | 378.62 | 193.72 | 184.89 | 0.00 | 0.00 |
December | 556.89 | 990.83 | 299.90 | 137.34 | 162.56 | 0.00 | 0.00 |
Annual Sum or Average | 1247.18 | 500.59 | 450.49 | 192.55 | 257.93 | 0.00 | 0.00 |
Minimum of Months | 556.89 | 80.55 | 299.90 | 137.34 | 162.56 | 0.00 | 0.00 |
Maximum of Months | 1912.20 | 1142.81 | 547.23 | 235.59 | 335.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2594.17 | 1704.92 | 1210.27 | 857.75 | 352.52 | 0.00 | 0.00 |
February | 2450.04 | 1446.35 | 1117.57 | 724.42 | 393.16 | 0.00 | 0.00 |
March | 1697.71 | 1314.16 | 742.97 | 352.51 | 390.46 | 0.00 | 0.00 |
April | 1488.09 | 816.21 | 563.01 | 159.16 | 403.85 | 0.00 | 0.00 |
May | 1566.07 | 232.48 | 413.58 | 27.70 | 385.88 | 0.00 | 0.00 |
June | 1646.09 | 205.73 | 401.42 | 7.03 | 394.39 | 0.00 | 0.00 |
July | 1675.17 | 128.41 | 422.13 | 13.05 | 409.09 | 0.00 | 0.00 |
August | 1967.29 | 190.91 | 509.23 | 77.80 | 431.43 | 0.00 | 0.00 |
September | 2083.32 | 274.64 | 613.78 | 180.56 | 433.22 | 0.00 | 0.00 |
October | 2851.83 | 521.56 | 928.29 | 491.03 | 437.26 | 0.00 | 0.00 |
November | 2848.61 | 1091.29 | 1149.85 | 788.07 | 361.78 | 0.00 | 0.00 |
December | 2730.52 | 1500.11 | 1177.06 | 838.58 | 338.48 | 0.00 | 0.00 |
Annual Sum or Average | 2131.92 | 782.20 | 768.88 | 374.63 | 394.26 | 0.00 | 0.00 |
Minimum of Months | 1488.09 | 128.41 | 401.42 | 7.03 | 338.48 | 0.00 | 0.00 |
Maximum of Months | 2851.83 | 1704.92 | 1210.27 | 857.75 | 437.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 747.83 | 1219.44 | 388.81 | 210.60 | 178.21 | 0.00 | 0.00 |
February | 891.07 | 1016.78 | 439.57 | 222.60 | 216.98 | 0.00 | 0.00 |
March | 945.94 | 884.56 | 432.03 | 190.70 | 241.33 | 0.00 | 0.00 |
April | 1402.51 | 539.46 | 535.26 | 244.84 | 290.41 | 0.00 | 0.00 |
May | 1581.86 | 158.82 | 447.21 | 145.64 | 301.56 | 0.00 | 0.00 |
June | 1798.60 | 142.78 | 496.60 | 173.97 | 322.63 | 0.00 | 0.00 |
July | 1642.95 | 88.74 | 454.16 | 126.43 | 327.73 | 0.00 | 0.00 |
August | 1666.55 | 125.90 | 458.16 | 139.95 | 318.20 | 0.00 | 0.00 |
September | 1425.83 | 171.59 | 421.46 | 144.05 | 277.42 | 0.00 | 0.00 |
October | 1384.36 | 335.57 | 431.74 | 186.22 | 245.52 | 0.00 | 0.00 |
November | 906.24 | 749.92 | 371.74 | 187.41 | 184.33 | 0.00 | 0.00 |
December | 768.96 | 1038.07 | 358.01 | 191.12 | 166.89 | 0.00 | 0.00 |
Annual Sum or Average | 1265.31 | 536.89 | 435.98 | 179.87 | 256.12 | 0.00 | 0.00 |
Minimum of Months | 747.83 | 88.74 | 358.01 | 126.43 | 166.89 | 0.00 | 0.00 |
Maximum of Months | 1798.60 | 1219.44 | 535.26 | 244.84 | 327.73 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.637791E+09 | 0.487623E+10 | 0.569506E+09 | 0.00 | 0.569506E+09 | 0.00 | 0.00 |
February | 0.787794E+09 | 0.360713E+10 | 0.606859E+09 | 0.00 | 0.606859E+09 | 0.00 | 0.00 |
March | 0.125934E+10 | 0.346073E+10 | 0.779439E+09 | 0.00 | 0.779439E+09 | 0.00 | 0.00 |
April | 0.202137E+10 | 0.194747E+10 | 0.892785E+09 | 6203721.83 | 0.886582E+09 | 0.00 | 0.00 |
May | 0.394329E+10 | 0.597933E+09 | 0.105740E+10 | 53538375.48 | 0.100386E+10 | 0.00 | 0.00 |
June | 0.457814E+10 | 0.517864E+09 | 0.117227E+10 | 0.104945E+09 | 0.106732E+10 | 0.00 | 0.00 |
July | 0.450704E+10 | 0.353001E+09 | 0.116582E+10 | 59719335.86 | 0.110610E+10 | 0.00 | 0.00 |
August | 0.410160E+10 | 0.475464E+09 | 0.103407E+10 | 12398667.89 | 0.102167E+10 | 0.00 | 0.00 |
September | 0.307503E+10 | 0.619236E+09 | 0.860862E+09 | 134318.81 | 0.860728E+09 | 0.00 | 0.00 |
October | 0.255171E+10 | 0.125129E+10 | 0.772948E+09 | 0.00 | 0.772948E+09 | 0.00 | 0.00 |
November | 0.104241E+10 | 0.273065E+10 | 0.567862E+09 | 0.00 | 0.567862E+09 | 0.00 | 0.00 |
December | 0.734714E+09 | 0.408579E+10 | 0.529421E+09 | 0.00 | 0.529421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292402E+11 | 0.245228E+11 | 0.100092E+11 | 0.236940E+09 | 0.977230E+10 | 0.00 | 0.00 |
Minimum of Months | 0.637791E+09 | 0.353001E+09 | 0.529421E+09 | 0.00 | 0.529421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.457814E+10 | 0.487623E+10 | 0.117227E+10 | 0.104945E+09 | 0.110610E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.169261E+10 | 0.287010E+10 | 0.979623E+09 | 0.500059E+09 | 0.479565E+09 | 0.00 | 0.00 |
February | 0.185270E+10 | 0.213637E+10 | 0.984943E+09 | 0.476636E+09 | 0.508307E+09 | 0.00 | 0.00 |
March | 0.263547E+10 | 0.210017E+10 | 0.127184E+10 | 0.609195E+09 | 0.662642E+09 | 0.00 | 0.00 |
April | 0.334305E+10 | 0.122257E+10 | 0.135514E+10 | 0.610651E+09 | 0.744493E+09 | 0.00 | 0.00 |
May | 0.468714E+10 | 0.376670E+09 | 0.144100E+10 | 0.621048E+09 | 0.819955E+09 | 0.00 | 0.00 |
June | 0.491369E+10 | 0.322555E+09 | 0.141843E+10 | 0.561041E+09 | 0.857385E+09 | 0.00 | 0.00 |
July | 0.489393E+10 | 0.211020E+09 | 0.141267E+10 | 0.515123E+09 | 0.897550E+09 | 0.00 | 0.00 |
August | 0.446482E+10 | 0.291025E+09 | 0.130170E+10 | 0.445759E+09 | 0.855942E+09 | 0.00 | 0.00 |
September | 0.359955E+10 | 0.374707E+09 | 0.111515E+10 | 0.381390E+09 | 0.733761E+09 | 0.00 | 0.00 |
October | 0.340195E+10 | 0.769707E+09 | 0.114141E+10 | 0.481423E+09 | 0.659986E+09 | 0.00 | 0.00 |
November | 0.214784E+10 | 0.163710E+10 | 0.981375E+09 | 0.502133E+09 | 0.479242E+09 | 0.00 | 0.00 |
December | 0.150989E+10 | 0.246953E+10 | 0.803248E+09 | 0.367845E+09 | 0.435403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.391426E+11 | 0.147815E+11 | 0.142065E+11 | 0.607230E+10 | 0.813423E+10 | 0.00 | 0.00 |
Minimum of Months | 0.150989E+10 | 0.211020E+09 | 0.803248E+09 | 0.367845E+09 | 0.435403E+09 | 0.00 | 0.00 |
Maximum of Months | 0.491369E+10 | 0.287010E+10 | 0.144100E+10 | 0.621048E+09 | 0.897550E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.698875E+10 | 0.423076E+10 | 0.324158E+10 | 0.229741E+10 | 0.944176E+09 | 0.00 | 0.00 |
February | 0.594476E+10 | 0.323097E+10 | 0.270363E+10 | 0.175251E+10 | 0.951124E+09 | 0.00 | 0.00 |
March | 0.453941E+10 | 0.328185E+10 | 0.198997E+10 | 0.944152E+09 | 0.104582E+10 | 0.00 | 0.00 |
April | 0.384429E+10 | 0.196636E+10 | 0.145932E+10 | 0.412538E+09 | 0.104678E+10 | 0.00 | 0.00 |
May | 0.416663E+10 | 0.584007E+09 | 0.110772E+10 | 74185018.44 | 0.103354E+10 | 0.00 | 0.00 |
June | 0.422625E+10 | 0.503602E+09 | 0.104047E+10 | 18212582.80 | 0.102226E+10 | 0.00 | 0.00 |
July | 0.444385E+10 | 0.324257E+09 | 0.113064E+10 | 34944871.77 | 0.109570E+10 | 0.00 | 0.00 |
August | 0.523155E+10 | 0.472765E+09 | 0.136392E+10 | 0.208371E+09 | 0.115554E+10 | 0.00 | 0.00 |
September | 0.537936E+10 | 0.630231E+09 | 0.159092E+10 | 0.468006E+09 | 0.112291E+10 | 0.00 | 0.00 |
October | 0.761472E+10 | 0.127432E+10 | 0.248633E+10 | 0.131518E+10 | 0.117115E+10 | 0.00 | 0.00 |
November | 0.742266E+10 | 0.256757E+10 | 0.298041E+10 | 0.204268E+10 | 0.937725E+09 | 0.00 | 0.00 |
December | 0.734616E+10 | 0.369939E+10 | 0.315264E+10 | 0.224606E+10 | 0.906579E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.671484E+11 | 0.227661E+11 | 0.242475E+11 | 0.118142E+11 | 0.124333E+11 | 0.00 | 0.00 |
Minimum of Months | 0.384429E+10 | 0.324257E+09 | 0.104047E+10 | 18212582.80 | 0.906579E+09 | 0.00 | 0.00 |
Maximum of Months | 0.761472E+10 | 0.423076E+10 | 0.324158E+10 | 0.229741E+10 | 0.117115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199978E+10 | 0.303979E+10 | 0.104138E+10 | 0.564072E+09 | 0.477312E+09 | 0.00 | 0.00 |
February | 0.214062E+10 | 0.228540E+10 | 0.106342E+10 | 0.538509E+09 | 0.524907E+09 | 0.00 | 0.00 |
March | 0.250404E+10 | 0.221659E+10 | 0.115715E+10 | 0.510764E+09 | 0.646384E+09 | 0.00 | 0.00 |
April | 0.360371E+10 | 0.130244E+10 | 0.138739E+10 | 0.634635E+09 | 0.752750E+09 | 0.00 | 0.00 |
May | 0.421780E+10 | 0.400107E+09 | 0.119780E+10 | 0.390086E+09 | 0.807711E+09 | 0.00 | 0.00 |
June | 0.462885E+10 | 0.349804E+09 | 0.128720E+10 | 0.450928E+09 | 0.836269E+09 | 0.00 | 0.00 |
July | 0.437013E+10 | 0.224992E+09 | 0.121643E+10 | 0.338634E+09 | 0.877798E+09 | 0.00 | 0.00 |
August | 0.444196E+10 | 0.314730E+09 | 0.122712E+10 | 0.374847E+09 | 0.852277E+09 | 0.00 | 0.00 |
September | 0.369174E+10 | 0.394165E+09 | 0.109243E+10 | 0.373372E+09 | 0.719061E+09 | 0.00 | 0.00 |
October | 0.370348E+10 | 0.821376E+09 | 0.115638E+10 | 0.498774E+09 | 0.657606E+09 | 0.00 | 0.00 |
November | 0.235597E+10 | 0.176211E+10 | 0.963556E+09 | 0.485777E+09 | 0.477779E+09 | 0.00 | 0.00 |
December | 0.206166E+10 | 0.256540E+10 | 0.958890E+09 | 0.511891E+09 | 0.446999E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.397197E+11 | 0.156769E+11 | 0.137491E+11 | 0.567229E+10 | 0.807685E+10 | 0.00 | 0.00 |
Minimum of Months | 0.199978E+10 | 0.224992E+09 | 0.958890E+09 | 0.338634E+09 | 0.446999E+09 | 0.00 | 0.00 |
Maximum of Months | 0.462885E+10 | 0.303979E+10 | 0.138739E+10 | 0.634635E+09 | 0.877798E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.633306E+09 | 0.528361E+10 | 0.569503E+09 | 0.00 | 0.569503E+09 | 0.00 | 0.00 |
February | 0.815616E+09 | 0.385571E+10 | 0.606856E+09 | 0.00 | 0.606856E+09 | 0.00 | 0.00 |
March | 0.135411E+10 | 0.361109E+10 | 0.779435E+09 | 0.00 | 0.779435E+09 | 0.00 | 0.00 |
April | 0.213673E+10 | 0.199654E+10 | 0.892781E+09 | 6203685.94 | 0.886577E+09 | 0.00 | 0.00 |
May | 0.405151E+10 | 0.575020E+09 | 0.105739E+10 | 53538065.71 | 0.100385E+10 | 0.00 | 0.00 |
June | 0.468539E+10 | 0.514730E+09 | 0.117226E+10 | 0.104945E+09 | 0.106731E+10 | 0.00 | 0.00 |
July | 0.457814E+10 | 0.368263E+09 | 0.116582E+10 | 59718990.33 | 0.110610E+10 | 0.00 | 0.00 |
August | 0.410961E+10 | 0.573039E+09 | 0.103406E+10 | 12398596.15 | 0.102166E+10 | 0.00 | 0.00 |
September | 0.306579E+10 | 0.789522E+09 | 0.860858E+09 | 134318.04 | 0.860723E+09 | 0.00 | 0.00 |
October | 0.252327E+10 | 0.149279E+10 | 0.772943E+09 | 0.00 | 0.772943E+09 | 0.00 | 0.00 |
November | 0.985270E+09 | 0.316924E+10 | 0.567859E+09 | 0.00 | 0.567859E+09 | 0.00 | 0.00 |
December | 0.694639E+09 | 0.454613E+10 | 0.529418E+09 | 0.00 | 0.529418E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.296334E+11 | 0.267757E+11 | 0.100092E+11 | 0.236938E+09 | 0.977224E+10 | 0.00 | 0.00 |
Minimum of Months | 0.633306E+09 | 0.368263E+09 | 0.529418E+09 | 0.00 | 0.529418E+09 | 0.00 | 0.00 |
Maximum of Months | 0.468539E+10 | 0.528361E+10 | 0.117226E+10 | 0.104945E+09 | 0.110610E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170259E+10 | 0.316532E+10 | 0.979657E+09 | 0.500079E+09 | 0.479579E+09 | 0.00 | 0.00 |
February | 0.189299E+10 | 0.232300E+10 | 0.984977E+09 | 0.476655E+09 | 0.508322E+09 | 0.00 | 0.00 |
March | 0.274259E+10 | 0.222823E+10 | 0.127188E+10 | 0.609219E+09 | 0.662661E+09 | 0.00 | 0.00 |
April | 0.347809E+10 | 0.127462E+10 | 0.135519E+10 | 0.610676E+09 | 0.744514E+09 | 0.00 | 0.00 |
May | 0.482514E+10 | 0.374342E+09 | 0.144105E+10 | 0.621073E+09 | 0.819979E+09 | 0.00 | 0.00 |
June | 0.502448E+10 | 0.327256E+09 | 0.141847E+10 | 0.561064E+09 | 0.857411E+09 | 0.00 | 0.00 |
July | 0.497355E+10 | 0.228878E+09 | 0.141272E+10 | 0.515144E+09 | 0.897577E+09 | 0.00 | 0.00 |
August | 0.449664E+10 | 0.355592E+09 | 0.130175E+10 | 0.445777E+09 | 0.855968E+09 | 0.00 | 0.00 |
September | 0.361756E+10 | 0.488773E+09 | 0.111519E+10 | 0.381405E+09 | 0.733783E+09 | 0.00 | 0.00 |
October | 0.343282E+10 | 0.920265E+09 | 0.114145E+10 | 0.481442E+09 | 0.660005E+09 | 0.00 | 0.00 |
November | 0.212251E+10 | 0.190481E+10 | 0.981409E+09 | 0.502153E+09 | 0.479256E+09 | 0.00 | 0.00 |
December | 0.149925E+10 | 0.277324E+10 | 0.803275E+09 | 0.367860E+09 | 0.435415E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.398082E+11 | 0.163643E+11 | 0.142070E+11 | 0.607255E+10 | 0.813447E+10 | 0.00 | 0.00 |
Minimum of Months | 0.149925E+10 | 0.228878E+09 | 0.803275E+09 | 0.367860E+09 | 0.435415E+09 | 0.00 | 0.00 |
Maximum of Months | 0.502448E+10 | 0.316532E+10 | 0.144105E+10 | 0.621073E+09 | 0.897577E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.710291E+10 | 0.486641E+10 | 0.324160E+10 | 0.229742E+10 | 0.944179E+09 | 0.00 | 0.00 |
February | 0.608251E+10 | 0.365620E+10 | 0.270364E+10 | 0.175252E+10 | 0.951127E+09 | 0.00 | 0.00 |
March | 0.472190E+10 | 0.354824E+10 | 0.198998E+10 | 0.944158E+09 | 0.104582E+10 | 0.00 | 0.00 |
April | 0.399850E+10 | 0.206063E+10 | 0.145932E+10 | 0.412541E+09 | 0.104678E+10 | 0.00 | 0.00 |
May | 0.426948E+10 | 0.564498E+09 | 0.110772E+10 | 74185467.68 | 0.103354E+10 | 0.00 | 0.00 |
June | 0.430569E+10 | 0.493337E+09 | 0.104047E+10 | 18212693.09 | 0.102226E+10 | 0.00 | 0.00 |
July | 0.449016E+10 | 0.342304E+09 | 0.113064E+10 | 34945083.39 | 0.109570E+10 | 0.00 | 0.00 |
August | 0.522696E+10 | 0.590832E+09 | 0.136392E+10 | 0.208372E+09 | 0.115555E+10 | 0.00 | 0.00 |
September | 0.538600E+10 | 0.843925E+09 | 0.159092E+10 | 0.468009E+09 | 0.112292E+10 | 0.00 | 0.00 |
October | 0.765101E+10 | 0.159051E+10 | 0.248634E+10 | 0.131518E+10 | 0.117116E+10 | 0.00 | 0.00 |
November | 0.742796E+10 | 0.313331E+10 | 0.298042E+10 | 0.204270E+10 | 0.937728E+09 | 0.00 | 0.00 |
December | 0.741456E+10 | 0.433598E+10 | 0.315266E+10 | 0.224608E+10 | 0.906582E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.680776E+11 | 0.260262E+11 | 0.242477E+11 | 0.118143E+11 | 0.124333E+11 | 0.00 | 0.00 |
Minimum of Months | 0.399850E+10 | 0.342304E+09 | 0.104047E+10 | 18212693.09 | 0.906582E+09 | 0.00 | 0.00 |
Maximum of Months | 0.765101E+10 | 0.486641E+10 | 0.324160E+10 | 0.229742E+10 | 0.117116E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205205E+10 | 0.337095E+10 | 0.104142E+10 | 0.564093E+09 | 0.477325E+09 | 0.00 | 0.00 |
February | 0.222146E+10 | 0.249974E+10 | 0.106345E+10 | 0.538529E+09 | 0.524921E+09 | 0.00 | 0.00 |
March | 0.262831E+10 | 0.236308E+10 | 0.115718E+10 | 0.510783E+09 | 0.646401E+09 | 0.00 | 0.00 |
April | 0.374203E+10 | 0.136734E+10 | 0.138743E+10 | 0.634659E+09 | 0.752770E+09 | 0.00 | 0.00 |
May | 0.429985E+10 | 0.396191E+09 | 0.119783E+10 | 0.390101E+09 | 0.807733E+09 | 0.00 | 0.00 |
June | 0.470789E+10 | 0.359651E+09 | 0.128724E+10 | 0.450945E+09 | 0.836292E+09 | 0.00 | 0.00 |
July | 0.441661E+10 | 0.240481E+09 | 0.121647E+10 | 0.338647E+09 | 0.877822E+09 | 0.00 | 0.00 |
August | 0.443559E+10 | 0.389868E+09 | 0.122716E+10 | 0.374862E+09 | 0.852301E+09 | 0.00 | 0.00 |
September | 0.366880E+10 | 0.521494E+09 | 0.109247E+10 | 0.373386E+09 | 0.719081E+09 | 0.00 | 0.00 |
October | 0.368698E+10 | 0.985268E+09 | 0.115642E+10 | 0.498793E+09 | 0.657624E+09 | 0.00 | 0.00 |
November | 0.235645E+10 | 0.205866E+10 | 0.963587E+09 | 0.485795E+09 | 0.477792E+09 | 0.00 | 0.00 |
December | 0.208273E+10 | 0.290792E+10 | 0.958921E+09 | 0.511910E+09 | 0.447011E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.402987E+11 | 0.174606E+11 | 0.137496E+11 | 0.567250E+10 | 0.807707E+10 | 0.00 | 0.00 |
Minimum of Months | 0.205205E+10 | 0.240481E+09 | 0.958921E+09 | 0.338647E+09 | 0.447011E+09 | 0.00 | 0.00 |
Maximum of Months | 0.470789E+10 | 0.337095E+10 | 0.138743E+10 | 0.634659E+09 | 0.877822E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.611785E+09 | 0.523523E+10 | 0.569506E+09 | 0.00 | 0.569506E+09 | 0.00 | 0.00 |
February | 0.766155E+09 | 0.388640E+10 | 0.606859E+09 | 0.00 | 0.606859E+09 | 0.00 | 0.00 |
March | 0.125373E+10 | 0.371283E+10 | 0.779439E+09 | 0.00 | 0.779439E+09 | 0.00 | 0.00 |
April | 0.201495E+10 | 0.210579E+10 | 0.892785E+09 | 6203721.83 | 0.886582E+09 | 0.00 | 0.00 |
May | 0.397077E+10 | 0.635159E+09 | 0.105740E+10 | 53538375.48 | 0.100386E+10 | 0.00 | 0.00 |
June | 0.462650E+10 | 0.547300E+09 | 0.117227E+10 | 0.104945E+09 | 0.106732E+10 | 0.00 | 0.00 |
July | 0.455316E+10 | 0.372481E+09 | 0.116582E+10 | 59719335.86 | 0.110610E+10 | 0.00 | 0.00 |
August | 0.413507E+10 | 0.516990E+09 | 0.103407E+10 | 12398667.89 | 0.102167E+10 | 0.00 | 0.00 |
September | 0.308514E+10 | 0.704667E+09 | 0.860862E+09 | 134318.81 | 0.860728E+09 | 0.00 | 0.00 |
October | 0.254449E+10 | 0.139174E+10 | 0.772948E+09 | 0.00 | 0.772948E+09 | 0.00 | 0.00 |
November | 0.993442E+09 | 0.303980E+10 | 0.567862E+09 | 0.00 | 0.567862E+09 | 0.00 | 0.00 |
December | 0.699333E+09 | 0.443415E+10 | 0.529421E+09 | 0.00 | 0.529421E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292545E+11 | 0.265825E+11 | 0.100092E+11 | 0.236940E+09 | 0.977230E+10 | 0.00 | 0.00 |
Minimum of Months | 0.611785E+09 | 0.372481E+09 | 0.529421E+09 | 0.00 | 0.529421E+09 | 0.00 | 0.00 |
Maximum of Months | 0.462650E+10 | 0.523523E+10 | 0.117227E+10 | 0.104945E+09 | 0.110610E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167418E+10 | 0.306090E+10 | 0.979623E+09 | 0.500059E+09 | 0.479565E+09 | 0.00 | 0.00 |
February | 0.184477E+10 | 0.228115E+10 | 0.984943E+09 | 0.476636E+09 | 0.508307E+09 | 0.00 | 0.00 |
March | 0.265119E+10 | 0.222267E+10 | 0.127184E+10 | 0.609195E+09 | 0.662642E+09 | 0.00 | 0.00 |
April | 0.337085E+10 | 0.129347E+10 | 0.135514E+10 | 0.610651E+09 | 0.744493E+09 | 0.00 | 0.00 |
May | 0.472977E+10 | 0.390946E+09 | 0.144100E+10 | 0.621048E+09 | 0.819955E+09 | 0.00 | 0.00 |
June | 0.495642E+10 | 0.333206E+09 | 0.141843E+10 | 0.561041E+09 | 0.857385E+09 | 0.00 | 0.00 |
July | 0.494159E+10 | 0.215734E+09 | 0.141267E+10 | 0.515123E+09 | 0.897550E+09 | 0.00 | 0.00 |
August | 0.449946E+10 | 0.304205E+09 | 0.130170E+10 | 0.445759E+09 | 0.855942E+09 | 0.00 | 0.00 |
September | 0.362626E+10 | 0.411167E+09 | 0.111515E+10 | 0.381390E+09 | 0.733761E+09 | 0.00 | 0.00 |
October | 0.342407E+10 | 0.833589E+09 | 0.114141E+10 | 0.481423E+09 | 0.659986E+09 | 0.00 | 0.00 |
November | 0.212081E+10 | 0.178589E+10 | 0.981375E+09 | 0.502133E+09 | 0.479242E+09 | 0.00 | 0.00 |
December | 0.149158E+10 | 0.265383E+10 | 0.803248E+09 | 0.367845E+09 | 0.435403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.393310E+11 | 0.157868E+11 | 0.142065E+11 | 0.607230E+10 | 0.813423E+10 | 0.00 | 0.00 |
Minimum of Months | 0.149158E+10 | 0.215734E+09 | 0.803248E+09 | 0.367845E+09 | 0.435403E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495642E+10 | 0.306090E+10 | 0.144100E+10 | 0.621048E+09 | 0.897550E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.694823E+10 | 0.456647E+10 | 0.324158E+10 | 0.229741E+10 | 0.944176E+09 | 0.00 | 0.00 |
February | 0.592714E+10 | 0.349901E+10 | 0.270363E+10 | 0.175251E+10 | 0.951124E+09 | 0.00 | 0.00 |
March | 0.454714E+10 | 0.351984E+10 | 0.198997E+10 | 0.944152E+09 | 0.104582E+10 | 0.00 | 0.00 |
April | 0.385714E+10 | 0.211563E+10 | 0.145932E+10 | 0.412538E+09 | 0.104678E+10 | 0.00 | 0.00 |
May | 0.419457E+10 | 0.622665E+09 | 0.110772E+10 | 74185018.44 | 0.103354E+10 | 0.00 | 0.00 |
June | 0.426668E+10 | 0.533263E+09 | 0.104047E+10 | 18212582.80 | 0.102226E+10 | 0.00 | 0.00 |
July | 0.448677E+10 | 0.343935E+09 | 0.113064E+10 | 34944871.77 | 0.109570E+10 | 0.00 | 0.00 |
August | 0.526920E+10 | 0.511341E+09 | 0.136392E+10 | 0.208371E+09 | 0.115554E+10 | 0.00 | 0.00 |
September | 0.539998E+10 | 0.711875E+09 | 0.159092E+10 | 0.468006E+09 | 0.112291E+10 | 0.00 | 0.00 |
October | 0.763833E+10 | 0.139694E+10 | 0.248633E+10 | 0.131518E+10 | 0.117115E+10 | 0.00 | 0.00 |
November | 0.738361E+10 | 0.282862E+10 | 0.298041E+10 | 0.204268E+10 | 0.937725E+09 | 0.00 | 0.00 |
December | 0.731343E+10 | 0.401790E+10 | 0.315264E+10 | 0.224606E+10 | 0.906579E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.672322E+11 | 0.246675E+11 | 0.242475E+11 | 0.118142E+11 | 0.124333E+11 | 0.00 | 0.00 |
Minimum of Months | 0.385714E+10 | 0.343935E+09 | 0.104047E+10 | 18212582.80 | 0.906579E+09 | 0.00 | 0.00 |
Maximum of Months | 0.763833E+10 | 0.456647E+10 | 0.324158E+10 | 0.229741E+10 | 0.117115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200298E+10 | 0.326615E+10 | 0.104138E+10 | 0.564072E+09 | 0.477312E+09 | 0.00 | 0.00 |
February | 0.215568E+10 | 0.245980E+10 | 0.106342E+10 | 0.538509E+09 | 0.524907E+09 | 0.00 | 0.00 |
March | 0.253362E+10 | 0.236921E+10 | 0.115715E+10 | 0.510764E+09 | 0.646384E+09 | 0.00 | 0.00 |
April | 0.363531E+10 | 0.139827E+10 | 0.138739E+10 | 0.634635E+09 | 0.752750E+09 | 0.00 | 0.00 |
May | 0.423685E+10 | 0.425392E+09 | 0.119780E+10 | 0.390086E+09 | 0.807711E+09 | 0.00 | 0.00 |
June | 0.466196E+10 | 0.370073E+09 | 0.128720E+10 | 0.450928E+09 | 0.836269E+09 | 0.00 | 0.00 |
July | 0.440048E+10 | 0.237674E+09 | 0.121643E+10 | 0.338634E+09 | 0.877798E+09 | 0.00 | 0.00 |
August | 0.446368E+10 | 0.337212E+09 | 0.122712E+10 | 0.374847E+09 | 0.852277E+09 | 0.00 | 0.00 |
September | 0.369574E+10 | 0.444753E+09 | 0.109243E+10 | 0.373372E+09 | 0.719061E+09 | 0.00 | 0.00 |
October | 0.370788E+10 | 0.898799E+09 | 0.115638E+10 | 0.498774E+09 | 0.657606E+09 | 0.00 | 0.00 |
November | 0.234899E+10 | 0.194379E+10 | 0.963556E+09 | 0.485777E+09 | 0.477779E+09 | 0.00 | 0.00 |
December | 0.205957E+10 | 0.278036E+10 | 0.958890E+09 | 0.511891E+09 | 0.446999E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.399027E+11 | 0.169315E+11 | 0.137491E+11 | 0.567229E+10 | 0.807685E+10 | 0.00 | 0.00 |
Minimum of Months | 0.200298E+10 | 0.237674E+09 | 0.958890E+09 | 0.338634E+09 | 0.446999E+09 | 0.00 | 0.00 |
Maximum of Months | 0.466196E+10 | 0.326615E+10 | 0.138739E+10 | 0.634635E+09 | 0.877798E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.397226E+10 | -0.373481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -237444131.5 | 60.05 | 0.00 | 0.00 |
February | 0.358159E+10 | -0.336766E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -213929509.4 | 60.05 | 0.00 | 0.00 |
March | 0.407338E+10 | -0.383734E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -236040072.7 | 60.05 | 0.00 | 0.00 |
April | 0.347230E+10 | -0.324696E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225339241.4 | 60.05 | 0.00 | 0.00 |
May | 0.347775E+10 | -0.324585E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231896598.8 | 60.05 | 0.00 | 0.00 |
June | 0.325432E+10 | -0.302960E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224718715.6 | 60.05 | 0.00 | 0.00 |
July | 0.299748E+10 | -0.276547E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232007045.3 | 60.05 | 0.00 | 0.00 |
August | 0.332337E+10 | -0.309126E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232108923.3 | 60.05 | 0.00 | 0.00 |
September | 0.314697E+10 | -0.292240E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224568227.0 | 60.05 | 0.00 | 0.00 |
October | 0.346434E+10 | -0.323242E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231926864.6 | 60.05 | 0.00 | 0.00 |
November | 0.363031E+10 | -0.340406E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226255016.5 | 60.05 | 0.00 | 0.00 |
December | 0.378210E+10 | -0.354630E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235793505.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.421761E+11 | -0.394241E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.275203E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.299748E+10 | -0.383734E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -237444131.5 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.407338E+10 | -0.276547E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -213929509.4 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 307.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 295.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 347.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 353.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 390.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 342.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 330.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 308.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4027.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152071E+10 | 22070.06 | 03-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.886157E+09 | 22070.06 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128876E+10 | 22070.06 | 09-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198644E+09 | 19781.98 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12965092.91 | 2916.09 | 27-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300350E+09 | 19117.73 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126498E+10 | 22070.06 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152071E+10 | 22070.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.300522E+09 | 18983.79 | 10-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173195E+09 | 18983.79 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206166E+09 | 17492.24 | 13-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1606158.81 | 2169.54 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 319565.56 | 2130.44 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1812717.33 | 2244.38 | 16-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211820E+09 | 14387.37 | 20-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.895442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.300522E+09 | 18983.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.529246E+09 | 17512.31 | 07-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340673E+09 | 17512.31 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286620E+09 | 17512.31 | 10-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3376809.69 | 4246.31 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8826970.56 | 5821.01 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298619E+09 | 17512.31 | 20-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.529246E+09 | 17512.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.383639E+09 | 19844.32 | 10-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252062E+09 | 19844.32 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231952E+09 | 17248.76 | 13-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1455505.67 | 1875.12 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 242779.73 | 1618.53 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6276475.13 | 2293.84 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229160E+09 | 13822.53 | 20-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.383639E+09 | 19844.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7722713.43 | 1611.67 | 05-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 968208.37 | 1076.81 | 06-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6407506.08 | 1911.55 | 21-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15098427.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7722713.43 | 1911.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 30713810.77 | 19889.17 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50040804.23 | 35983.52 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41866554.87 | 26900.98 | 13-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4567725.23 | 14608.65 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50040804.23 | 35983.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.552922E+09 | 22374.49 | 04-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298322E+09 | 22374.49 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.390997E+09 | 22374.49 | 10-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8817483.30 | 4978.42 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3582134.94 | 6083.29 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24035807.21 | 7120.96 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.418154E+09 | 22374.49 | 20-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.552922E+09 | 22374.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.695551E+09 | 19838.97 | 04-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.357278E+09 | 19838.97 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347037E+09 | 19838.97 | 10-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5488130.91 | 3208.60 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4970716.00 | 3395.97 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35378288.54 | 9113.83 | 16-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537295E+09 | 19838.97 | 20-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.695551E+09 | 19838.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101107E+10 | 17653.53 | 04-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.531909E+09 | 17653.53 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409713E+09 | 17653.53 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6500676.42 | 5364.36 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4967696.69 | 7569.98 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56491457.56 | 8469.64 | 16-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.660408E+09 | 17653.53 | 20-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101107E+10 | 17653.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.947835E+09 | 20775.27 | 04-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.509307E+09 | 20775.27 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416602E+09 | 20775.27 | 13-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9927671.03 | 2988.51 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7616718.28 | 3720.19 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68309557.39 | 8622.00 | 16-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.644726E+09 | 20775.27 | 20-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.947835E+09 | 20775.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16426403.07 | 2047.21 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1985556.16 | 2047.21 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4509766.45 | 2047.21 | 09-MAR-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4910212.82 | 2047.21 | 21-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27831938.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16426403.07 | 2047.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155305E+10 | 69413.22 | 10-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.837555E+09 | 69413.22 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.673231E+09 | 69413.22 | 13-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8164403.52 | 7437.00 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4067952.94 | 3262.45 | 28-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156391E+09 | 36138.45 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.998929E+09 | 52558.83 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155305E+10 | 69413.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170835E+10 | 26000.40 | 04-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101016E+10 | 26000.40 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115065E+10 | 26000.40 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139036E+09 | 10605.91 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 61303869.29 | 12106.26 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342839E+09 | 26000.40 | 16-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133928E+10 | 26000.40 | 04-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170835E+10 | 26000.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153698E+10 | 20424.09 | 04-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.889448E+09 | 20424.09 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.875650E+09 | 20424.09 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89441560.13 | 8325.47 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 58726402.26 | 9906.40 | 28-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355137E+09 | 20424.09 | 16-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129731E+10 | 20424.09 | 04-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153698E+10 | 20424.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232978E+10 | 21486.84 | 04-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133051E+10 | 21486.84 | 04-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115032E+10 | 21486.84 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109319E+09 | 10412.53 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71121315.17 | 11996.51 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.469379E+09 | 21486.84 | 16-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174352E+10 | 21486.84 | 04-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.720394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232978E+10 | 21486.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205046E+10 | 23060.51 | 04-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121475E+10 | 23060.51 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112751E+10 | 23060.51 | 10-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151183E+09 | 8039.66 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87916592.11 | 10213.24 | 28-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.534164E+09 | 22014.41 | 16-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161392E+10 | 23060.51 | 04-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.677991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205046E+10 | 23060.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.393696E+11 | 0.311059E+11 | 72409.29 | 19-JAN-15:10 | 50659.96 | 0.00 |
February | 0.00 | 0.00 | 0.433523E+11 | 0.326112E+11 | 73416.46 | 24-FEB-13:00 | 51563.95 | 0.00 |
March | 0.00 | 0.00 | 0.526624E+11 | 0.409405E+11 | 75814.75 | 28-MAR-12:00 | 50278.41 | 0.00 |
April | 0.00 | 0.00 | 0.664413E+11 | 0.502607E+11 | 97061.68 | 29-APR-05:12 | 62721.31 | 0.00 |
May | 0.00 | 0.00 | 0.111810E+12 | 0.771909E+11 | 130064.85 | 23-MAY-04:02 | 71909.83 | 0.00 |
June | 0.00 | 0.00 | 0.118352E+12 | 0.810094E+11 | 147344.65 | 05-JUN-04:01 | 91447.36 | 0.00 |
July | 0.00 | 0.00 | 0.126704E+12 | 0.814468E+11 | 151680.09 | 31-JUL-04:01 | 81107.48 | 0.00 |
August | 0.00 | 0.00 | 0.130926E+12 | 0.867261E+11 | 149408.57 | 15-AUG-04:01 | 86010.62 | 0.00 |
September | 0.00 | 0.00 | 0.113860E+12 | 0.741930E+11 | 150239.51 | 18-SEP-04:01 | 88804.79 | 0.00 |
October | 0.00 | 0.00 | 0.102077E+12 | 0.723161E+11 | 147725.94 | 06-OCT-04:01 | 96265.36 | 0.00 |
November | 0.00 | 0.00 | 0.625662E+11 | 0.482908E+11 | 104675.97 | 08-NOV-06:12 | 62604.46 | 0.00 |
December | 0.00 | 0.00 | 0.488188E+11 | 0.375797E+11 | 86987.38 | 15-DEC-13:05 | 58852.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101694E+13 | 0.713671E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.393696E+11 | 0.311059E+11 | 72409.29 | 50278.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.130926E+12 | 0.867261E+11 | 151680.09 | 96265.36 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.327849E+11 | 0.247790E+11 | 63925.04 | 19-JAN-15:10 | 43878.71 | 0.00 |
February | 0.00 | 0.00 | 0.378014E+11 | 0.273161E+11 | 62889.23 | 24-FEB-16:00 | 45001.74 | 0.00 |
March | 0.00 | 0.00 | 0.460058E+11 | 0.344033E+11 | 66342.96 | 07-MAR-11:05 | 42813.68 | 0.00 |
April | 0.00 | 0.00 | 0.597861E+11 | 0.436509E+11 | 91409.20 | 28-APR-16:00 | 63808.75 | 0.00 |
May | 0.00 | 0.00 | 0.101357E+12 | 0.680325E+11 | 143054.58 | 22-MAY-04:01 | 76590.52 | 0.00 |
June | 0.00 | 0.00 | 0.106990E+12 | 0.712521E+11 | 137977.96 | 05-JUN-04:01 | 85788.58 | 0.00 |
July | 0.00 | 0.00 | 0.114114E+12 | 0.706712E+11 | 144469.02 | 03-JUL-04:02 | 70640.66 | 0.00 |
August | 0.00 | 0.00 | 0.114588E+12 | 0.730394E+11 | 140107.36 | 07-AUG-04:01 | 82006.28 | 0.00 |
September | 0.00 | 0.00 | 0.997870E+11 | 0.620542E+11 | 142659.17 | 05-SEP-05:12 | 61641.05 | 0.00 |
October | 0.00 | 0.00 | 0.882686E+11 | 0.599471E+11 | 139053.83 | 06-OCT-05:01 | 79002.40 | 0.00 |
November | 0.00 | 0.00 | 0.528684E+11 | 0.388588E+11 | 85693.80 | 02-NOV-14:10 | 59344.20 | 0.00 |
December | 0.00 | 0.00 | 0.409720E+11 | 0.300516E+11 | 71701.48 | 15-DEC-14:00 | 53960.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.895322E+12 | 0.604056E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.327849E+11 | 0.247790E+11 | 62889.23 | 42813.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114588E+12 | 0.730394E+11 | 144469.02 | 85788.58 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.392844E+11 | 0.308734E+11 | 72581.96 | 19-JAN-15:00 | 52313.69 | 0.00 |
February | 0.00 | 0.00 | 0.438167E+11 | 0.330588E+11 | 73347.01 | 24-FEB-14:40 | 56522.61 | 0.00 |
March | 0.00 | 0.00 | 0.533925E+11 | 0.414376E+11 | 75846.23 | 29-MAR-15:00 | 59348.38 | 0.00 |
April | 0.00 | 0.00 | 0.687855E+11 | 0.522785E+11 | 107669.19 | 28-APR-16:00 | 80668.97 | 0.00 |
May | 0.00 | 0.00 | 0.112730E+12 | 0.794846E+11 | 169411.38 | 22-MAY-04:01 | 92815.30 | 0.00 |
June | 0.00 | 0.00 | 0.119728E+12 | 0.841453E+11 | 163737.63 | 05-JUN-04:01 | 96455.41 | 0.00 |
July | 0.00 | 0.00 | 0.125900E+12 | 0.825360E+11 | 170495.35 | 03-JUL-04:01 | 89932.82 | 0.00 |
August | 0.00 | 0.00 | 0.125549E+12 | 0.842131E+11 | 166406.22 | 07-AUG-04:01 | 90080.14 | 0.00 |
September | 0.00 | 0.00 | 0.108348E+12 | 0.704500E+11 | 166972.15 | 18-SEP-05:01 | 83378.22 | 0.00 |
October | 0.00 | 0.00 | 0.957761E+11 | 0.674810E+11 | 163822.80 | 07-OCT-05:01 | 89887.17 | 0.00 |
November | 0.00 | 0.00 | 0.583158E+11 | 0.439047E+11 | 98038.10 | 02-NOV-14:00 | 71804.44 | 0.00 |
December | 0.00 | 0.00 | 0.468001E+11 | 0.354888E+11 | 81535.19 | 15-DEC-14:30 | 64762.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.998426E+12 | 0.705352E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.392844E+11 | 0.308734E+11 | 72581.96 | 52313.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125900E+12 | 0.842131E+11 | 170495.35 | 96455.41 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1385.48 | 5050.50 | 23-JAN-12:45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1383.11 | 5042.65 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1423.55 | 4927.79 | 01-MAR-12:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1243.96 | 4652.39 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1203.09 | 4360.97 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1160.06 | 4060.80 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1024.13 | 3860.90 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1145.37 | 3945.78 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1118.91 | 4183.61 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1198.16 | 4514.44 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1304.42 | 4805.35 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1315.27 | 4995.39 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1241.35 | ||||
Minimum of Months | 0.00 | 0.00 | 1024.13 | 3860.90 | ||
Maximum of Months | 0.00 | 0.00 | 1423.55 | 5050.50 |
Report: FanReportMonthly
For: CORE_BOTTOM PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.315375E+09 | 0.09 | 755.22 | 02-JAN-07:06 | 0.60 |
February | 0.216761E+09 | 0.07 | 755.22 | 01-FEB-07:03 | 0.60 |
March | 0.286655E+09 | 0.09 | 755.22 | 01-MAR-07:03 | 0.60 |
April | 53129882.96 | 0.02 | 755.22 | 03-APR-05:12 | 0.61 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 13707283.24 | 0.00 | 755.22 | 17-OCT-06:05 | 0.60 |
November | 44739364.13 | 0.01 | 755.22 | 09-NOV-07:03 | 0.61 |
December | 0.222628E+09 | 0.07 | 755.22 | 01-DEC-07:03 | 0.61 |
Annual Sum or Average | 0.115300E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.315375E+09 | 0.09 | 755.22 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.368886E+09 | 0.13 | 649.61 | 02-JAN-21:40 | 0.61 |
February | 0.257678E+09 | 0.10 | 649.61 | 01-FEB-07:03 | 0.60 |
March | 0.241023E+09 | 0.08 | 649.61 | 01-MAR-07:03 | 0.60 |
April | 30174297.29 | 0.01 | 649.61 | 03-APR-05:12 | 0.61 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 4937021.73 | 0.00 | 649.61 | 18-OCT-06:03 | 0.60 |
November | 61868677.58 | 0.02 | 649.61 | 09-NOV-07:03 | 0.61 |
December | 0.311852E+09 | 0.11 | 649.61 | 01-DEC-06:40 | 0.61 |
Annual Sum or Average | 0.127642E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.368886E+09 | 0.13 | 649.61 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.373460E+09 | 0.14 | 599.26 | 03-JAN-06:40 | 0.61 |
February | 0.227906E+09 | 0.10 | 599.26 | 03-FEB-19:15 | 0.61 |
March | 0.193182E+09 | 0.07 | 599.26 | 01-MAR-19:00 | 0.60 |
April | 12854081.86 | 0.01 | 599.26 | 03-APR-06:00 | 0.61 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 988775.53 | 0.00 | 599.26 | 28-OCT-06:03 | 0.61 |
November | 30496234.30 | 0.01 | 599.26 | 09-NOV-07:03 | 0.61 |
December | 0.246088E+09 | 0.09 | 599.26 | 01-DEC-07:03 | 0.61 |
Annual Sum or Average | 0.108498E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.373460E+09 | 0.14 | 599.26 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.450177E+09 | 0.15 | 679.06 | 02-JAN-21:57 | 0.61 |
February | 0.306015E+09 | 0.11 | 679.06 | 01-FEB-07:03 | 0.60 |
March | 0.310915E+09 | 0.10 | 679.06 | 01-MAR-07:03 | 0.60 |
April | 41727985.07 | 0.01 | 679.06 | 01-APR-06:03 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 9506782.60 | 0.00 | 679.06 | 27-OCT-20:37 | 0.61 |
November | 90782983.31 | 0.03 | 679.06 | 08-NOV-21:38 | 0.61 |
December | 0.346113E+09 | 0.12 | 679.06 | 01-DEC-07:03 | 0.61 |
Annual Sum or Average | 0.155524E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.450177E+09 | 0.15 | 679.06 | 0.61 |
Report: FanReportMonthly
For: CORE_MID PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 45382568.39 | 0.01 | 1981.77 | 07-JAN-07:40 | 0.61 |
February | 68252212.03 | 0.01 | 1981.77 | 06-FEB-06:15 | 0.61 |
March | 61236740.76 | 0.01 | 1981.77 | 11-MAR-07:03 | 0.61 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 53706008.89 | 0.01 | 1981.77 | 21-DEC-07:03 | 0.61 |
Annual Sum or Average | 0.228578E+09 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68252212.03 | 0.01 | 1981.77 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.275111E+09 | 0.08 | 765.63 | 03-JAN-06:12 | 0.61 |
February | 0.182005E+09 | 0.06 | 765.63 | 01-FEB-07:03 | 0.60 |
March | 0.219006E+09 | 0.06 | 765.63 | 01-MAR-07:30 | 0.60 |
April | 22394582.02 | 0.01 | 765.63 | 03-APR-05:30 | 0.61 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 7962518.05 | 0.00 | 765.63 | 18-OCT-06:03 | 0.60 |
November | 54673405.19 | 0.02 | 765.63 | 09-NOV-06:35 | 0.61 |
December | 0.229308E+09 | 0.07 | 765.63 | 01-DEC-06:55 | 0.61 |
Annual Sum or Average | 0.990461E+09 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275111E+09 | 0.08 | 765.63 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.439227E+09 | 0.15 | 678.86 | 02-JAN-07:02 | 0.60 |
February | 0.291130E+09 | 0.11 | 678.86 | 01-FEB-07:03 | 0.60 |
March | 0.270400E+09 | 0.09 | 678.86 | 01-MAR-07:03 | 0.60 |
April | 40256523.81 | 0.01 | 678.86 | 01-APR-06:03 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 24065662.21 | 0.01 | 678.86 | 02-OCT-06:03 | 0.60 |
November | 0.154156E+09 | 0.05 | 678.86 | 04-NOV-06:50 | 0.60 |
December | 0.384276E+09 | 0.13 | 678.86 | 01-DEC-06:15 | 0.61 |
Annual Sum or Average | 0.160351E+10 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.439227E+09 | 0.15 | 678.86 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.409972E+09 | 0.15 | 604.08 | 03-JAN-06:12 | 0.61 |
February | 0.232325E+09 | 0.10 | 604.08 | 02-FEB-07:03 | 0.60 |
March | 0.191668E+09 | 0.07 | 604.08 | 01-MAR-19:00 | 0.60 |
April | 12172233.24 | 0.00 | 604.08 | 03-APR-05:40 | 0.61 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 9212236.08 | 0.00 | 604.08 | 27-OCT-20:55 | 0.61 |
November | 68357812.08 | 0.03 | 604.08 | 09-NOV-06:50 | 0.61 |
December | 0.302075E+09 | 0.11 | 604.08 | 01-DEC-06:55 | 0.61 |
Annual Sum or Average | 0.122578E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.409972E+09 | 0.15 | 604.08 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.521595E+09 | 0.17 | 710.90 | 02-JAN-07:02 | 0.60 |
February | 0.356678E+09 | 0.13 | 710.90 | 01-FEB-07:03 | 0.60 |
March | 0.350463E+09 | 0.11 | 710.90 | 01-MAR-07:03 | 0.60 |
April | 57654109.72 | 0.02 | 710.90 | 01-APR-06:03 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 31386300.17 | 0.01 | 710.90 | 02-OCT-06:25 | 0.60 |
November | 0.203837E+09 | 0.07 | 710.90 | 04-NOV-06:35 | 0.60 |
December | 0.445986E+09 | 0.14 | 710.90 | 01-DEC-06:15 | 0.61 |
Annual Sum or Average | 0.196760E+10 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.521595E+09 | 0.17 | 710.90 | 0.61 |
Report: FanReportMonthly
For: CORE_TOP PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.877166E+09 | 0.08 | 2370.91 | 03-JAN-07:03 | 0.61 |
February | 0.488166E+09 | 0.05 | 2370.91 | 04-FEB-07:03 | 0.61 |
March | 0.312081E+09 | 0.03 | 2370.91 | 02-MAR-07:03 | 0.60 |
April | 13751261.58 | 0.00 | 2370.91 | 03-APR-06:03 | 0.61 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 9957810.11 | 0.00 | 2370.91 | 28-OCT-06:03 | 0.61 |
November | 0.104130E+09 | 0.01 | 2370.91 | 13-NOV-07:03 | 0.61 |
December | 0.611230E+09 | 0.06 | 2370.91 | 01-DEC-07:03 | 0.61 |
Annual Sum or Average | 0.241648E+10 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.877166E+09 | 0.08 | 2370.91 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.433947E+09 | 0.11 | 889.68 | 02-JAN-07:02 | 0.60 |
February | 0.359859E+09 | 0.10 | 889.68 | 01-FEB-07:03 | 0.60 |
March | 0.403489E+09 | 0.10 | 889.68 | 01-MAR-07:03 | 0.60 |
April | 0.112589E+09 | 0.03 | 889.68 | 01-APR-06:03 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 41815096.64 | 0.01 | 889.68 | 02-OCT-06:03 | 0.60 |
November | 0.196736E+09 | 0.05 | 889.68 | 04-NOV-06:38 | 0.60 |
December | 0.408765E+09 | 0.10 | 889.68 | 01-DEC-06:12 | 0.61 |
Annual Sum or Average | 0.195720E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.433947E+09 | 0.11 | 889.68 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.550398E+09 | 0.18 | 698.87 | 02-JAN-07:02 | 0.60 |
February | 0.419628E+09 | 0.15 | 698.87 | 01-FEB-06:30 | 0.60 |
March | 0.358002E+09 | 0.12 | 698.87 | 01-MAR-06:30 | 0.60 |
April | 95430449.63 | 0.03 | 698.87 | 01-APR-06:03 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 559094.54 | 0.00 | 698.87 | 07-JUN-06:07 | 0.60 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 349434.09 | 0.00 | 698.87 | 07-SEP-20:55 | 0.60 |
October | 58215719.18 | 0.02 | 698.87 | 02-OCT-06:03 | 0.60 |
November | 0.245743E+09 | 0.08 | 698.87 | 01-NOV-06:03 | 0.60 |
December | 0.484978E+09 | 0.16 | 698.87 | 01-DEC-06:12 | 0.61 |
Annual Sum or Average | 0.221330E+10 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.550398E+09 | 0.18 | 698.87 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587794E+09 | 0.18 | 735.24 | 02-JAN-07:02 | 0.60 |
February | 0.428730E+09 | 0.15 | 735.24 | 01-FEB-07:03 | 0.60 |
March | 0.360989E+09 | 0.11 | 735.24 | 01-MAR-07:03 | 0.60 |
April | 68854883.38 | 0.02 | 735.24 | 01-APR-06:40 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 42202566.00 | 0.01 | 735.24 | 02-OCT-06:03 | 0.60 |
November | 0.237298E+09 | 0.08 | 735.24 | 06-NOV-07:03 | 0.60 |
December | 0.494040E+09 | 0.15 | 735.24 | 01-DEC-06:12 | 0.61 |
Annual Sum or Average | 0.221991E+10 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.587794E+09 | 0.18 | 735.24 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.669257E+09 | 0.19 | 789.08 | 02-JAN-06:50 | 0.60 |
February | 0.549994E+09 | 0.17 | 789.08 | 01-FEB-06:20 | 0.60 |
March | 0.521591E+09 | 0.15 | 789.08 | 01-MAR-06:20 | 0.60 |
April | 0.184014E+09 | 0.05 | 789.08 | 01-APR-06:03 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 2209429.70 | 0.00 | 789.08 | 01-JUN-06:03 | 0.60 |
July | 394541.02 | 0.00 | 789.08 | 15-JUL-06:03 | 0.60 |
August | 631265.63 | 0.00 | 789.08 | 17-AUG-06:03 | 0.60 |
September | 7259554.73 | 0.00 | 789.08 | 07-SEP-19:57 | 0.60 |
October | 90981158.76 | 0.03 | 789.08 | 02-OCT-06:03 | 0.60 |
November | 0.380637E+09 | 0.11 | 789.08 | 01-NOV-06:03 | 0.60 |
December | 0.599873E+09 | 0.17 | 789.08 | 01-DEC-06:12 | 0.61 |
Annual Sum or Average | 0.300684E+10 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.669257E+09 | 0.19 | 789.08 | 0.61 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.333927E+10 | 0.46 | 5656.09 | 02-JAN-06:12 | 1.23 |
February | 0.310673E+10 | 0.47 | 4455.18 | 27-FEB-15:30 | 1.12 |
March | 0.371700E+10 | 0.50 | 4905.28 | 09-MAR-06:02 | 1.17 |
April | 0.390061E+10 | 0.50 | 6619.13 | 28-APR-05:12 | 1.32 |
May | 0.571016E+10 | 0.60 | 10027.21 | 31-MAY-05:01 | 1.57 |
June | 0.600995E+10 | 0.64 | 10978.15 | 29-JUN-04:01 | 1.64 |
July | 0.598769E+10 | 0.62 | 13683.98 | 03-JUL-04:01 | 1.79 |
August | 0.664350E+10 | 0.66 | 13683.98 | 07-AUG-04:01 | 1.80 |
September | 0.559262E+10 | 0.61 | 13683.98 | 11-SEP-04:01 | 1.80 |
October | 0.573722E+10 | 0.59 | 13683.98 | 06-OCT-04:01 | 1.80 |
November | 0.409331E+10 | 0.51 | 7069.35 | 03-NOV-05:12 | 1.36 |
December | 0.363068E+10 | 0.48 | 5653.89 | 15-DEC-15:10 | 1.23 |
Annual Sum or Average | 0.574687E+11 | 0.55 | |||
Minimum of Months | 0.310673E+10 | 0.46 | 4455.18 | 1.12 | |
Maximum of Months | 0.664350E+10 | 0.66 | 13683.98 | 1.80 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.301553E+10 | 0.46 | 3741.45 | 19-JAN-15:30 | 1.08 |
February | 0.280003E+10 | 0.47 | 3794.80 | 27-FEB-15:30 | 1.09 |
March | 0.328291E+10 | 0.50 | 3654.03 | 29-MAR-15:20 | 1.07 |
April | 0.338469E+10 | 0.49 | 5487.28 | 28-APR-15:20 | 1.27 |
May | 0.486703E+10 | 0.59 | 12361.78 | 22-MAY-04:01 | 1.79 |
June | 0.507840E+10 | 0.62 | 12361.78 | 05-JUN-04:01 | 1.80 |
July | 0.497610E+10 | 0.59 | 12361.78 | 03-JUL-04:01 | 1.79 |
August | 0.528425E+10 | 0.62 | 12361.78 | 14-AUG-04:01 | 1.79 |
September | 0.446314E+10 | 0.58 | 12361.78 | 11-SEP-04:01 | 1.80 |
October | 0.459251E+10 | 0.56 | 10446.89 | 06-OCT-04:01 | 1.67 |
November | 0.336761E+10 | 0.49 | 5157.40 | 02-NOV-14:30 | 1.24 |
December | 0.315942E+10 | 0.47 | 4734.32 | 15-DEC-15:00 | 1.20 |
Annual Sum or Average | 0.482716E+11 | 0.54 | |||
Minimum of Months | 0.280003E+10 | 0.46 | 3654.03 | 1.07 | |
Maximum of Months | 0.528425E+10 | 0.62 | 12361.78 | 1.80 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.320861E+10 | 0.43 | 3681.24 | 01-JAN-11:22 | 0.98 |
February | 0.297295E+10 | 0.44 | 3854.04 | 27-FEB-15:30 | 1.00 |
March | 0.350506E+10 | 0.47 | 3956.74 | 29-MAR-15:00 | 1.01 |
April | 0.362351E+10 | 0.46 | 6085.53 | 28-APR-15:20 | 1.21 |
May | 0.508218E+10 | 0.54 | 15327.16 | 22-MAY-04:01 | 1.78 |
June | 0.535572E+10 | 0.58 | 13061.39 | 05-JUN-04:01 | 1.67 |
July | 0.519091E+10 | 0.55 | 15327.16 | 03-JUL-04:01 | 1.78 |
August | 0.542605E+10 | 0.57 | 15327.16 | 28-AUG-04:01 | 1.78 |
September | 0.449333E+10 | 0.53 | 13745.97 | 19-SEP-05:01 | 1.70 |
October | 0.457926E+10 | 0.51 | 14908.45 | 23-OCT-05:01 | 1.76 |
November | 0.342571E+10 | 0.45 | 5257.49 | 02-NOV-14:30 | 1.13 |
December | 0.329596E+10 | 0.44 | 4580.80 | 15-DEC-15:00 | 1.07 |
Annual Sum or Average | 0.501592E+11 | 0.50 | |||
Minimum of Months | 0.297295E+10 | 0.43 | 3681.24 | 0.98 | |
Maximum of Months | 0.542605E+10 | 0.58 | 15327.16 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.48 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:02 | 2.06 | 2.06 | 57.63 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:02 | 2.06 | 2.06 | 57.69 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:02 | 2.06 | 2.06 | 57.85 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:01 | 2.06 | 2.06 | 58.20 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:02 | 2.06 | 2.06 | 58.15 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:01 | 2.06 | 2.06 | 58.25 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:01 | 2.06 | 2.06 | 58.27 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:01 | 2.06 | 2.06 | 58.21 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.64 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:02 | 2.06 | 2.06 | 57.92 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:02 | 2.06 | 2.06 | 57.75 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.63 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.64 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.48 | 58.48 | 1385.48 | 5050.50 | 23-JAN-12:45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.08 | 58.08 | 1383.11 | 5042.65 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.12 | 58.12 | 1423.55 | 4927.79 | 01-MAR-12:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.22 | 58.22 | 1243.96 | 4652.39 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.67 | 58.67 | 1203.09 | 4360.97 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.47 | 58.47 | 1160.06 | 4060.80 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.53 | 58.53 | 1024.13 | 3860.90 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.56 | 58.56 | 1145.37 | 3945.78 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.50 | 58.50 | 1118.91 | 4183.61 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.75 | 57.75 | 1198.16 | 4514.44 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.29 | 58.29 | 1304.42 | 4805.35 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.17 | 58.17 | 1315.27 | 4995.39 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1241.35 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.75 | 57.75 | 1024.13 | 3860.90 | ||
Maximum of Months | 0.00 | 0.00 | 58.67 | 58.67 | 1423.55 | 5050.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.170679E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160070E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.192584E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.199218E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.332385E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.355554E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.374373E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.390769E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.328358E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.304004E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.193343E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.183876E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.318521E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160070E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.390769E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158910E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.146463E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.169508E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.177068E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.297382E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.316635E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.331090E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.335081E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.282554E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.259436E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.165386E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166491E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.280600E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.146463E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.335081E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.250869E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.209609E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.232152E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.209608E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.328512E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.352201E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.363757E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.364694E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.304139E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.282683E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.203146E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.241597E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.334297E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.203146E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.364694E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.484717E+10 | 0.393696E+11 | 0.273411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411509E+10 | 0.433523E+11 | 0.165209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.474877E+10 | 0.526624E+11 | 0.201350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.403850E+10 | 0.664413E+11 | 0.205083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571016E+10 | 0.111810E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.600995E+10 | 0.118352E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.598769E+10 | 0.126704E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.664350E+10 | 0.130926E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.559262E+10 | 0.113860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.576636E+10 | 0.102077E+12 | 13527438.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.432119E+10 | 0.625662E+11 | 0.317266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.475736E+10 | 0.488188E+11 | 0.200458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625384E+11 | 0.101694E+13 | 0.894016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.403850E+10 | 0.393696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.664350E+10 | 0.130926E+12 | 0.273411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.470682E+10 | 0.327849E+11 | 0.324581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393042E+10 | 0.378014E+11 | 0.174782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.437568E+10 | 0.460058E+11 | 0.160622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351716E+10 | 0.597861E+11 | 30733961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.486703E+10 | 0.101357E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.507840E+10 | 0.106990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.497610E+10 | 0.114114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.528425E+10 | 0.114588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.446314E+10 | 0.997870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466514E+10 | 0.882686E+11 | 21137265.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384864E+10 | 0.528684E+11 | 0.184215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.457477E+10 | 0.409720E+11 | 0.227156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.542876E+11 | 0.895322E+12 | 0.910750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.351716E+10 | 0.327849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.528425E+10 | 0.114588E+12 | 0.324581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.632718E+10 | 0.392844E+11 | 0.919505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.521933E+10 | 0.438167E+11 | 0.528441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.546121E+10 | 0.533925E+11 | 0.498187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.409815E+10 | 0.687855E+11 | 0.497144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.508218E+10 | 0.112730E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.535849E+10 | 0.119728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.519130E+10 | 0.125900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.542668E+10 | 0.125549E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.450094E+10 | 0.108348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.482243E+10 | 0.957761E+11 | 0.283136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459025E+10 | 0.583158E+11 | 0.185791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.589484E+10 | 0.468001E+11 | 0.699787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.619730E+11 | 0.998426E+12 | 0.290974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.409815E+10 | 0.392844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.632718E+10 | 0.125900E+12 | 0.919505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.484717E+10 | 0.00 | 0.00 | 0.00 | 0.948661E+10 | 0.273411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411509E+10 | 0.00 | 0.00 | 0.00 | 0.102398E+11 | 0.165209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.474877E+10 | 0.00 | 0.00 | 0.00 | 0.124961E+11 | 0.201350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.403850E+10 | 0.00 | 0.00 | 0.00 | 0.156782E+11 | 0.205083E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571016E+10 | 0.00 | 0.00 | 0.00 | 0.275283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.600995E+10 | 0.00 | 0.00 | 0.00 | 0.295454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.598769E+10 | 0.00 | 0.00 | 0.00 | 0.314496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.664350E+10 | 0.00 | 0.00 | 0.00 | 0.324334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.559262E+10 | 0.00 | 0.00 | 0.00 | 0.272432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.576636E+10 | 0.00 | 0.00 | 0.00 | 0.246205E+11 | 13527438.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.432119E+10 | 0.00 | 0.00 | 0.00 | 0.146959E+11 | 0.317266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.475736E+10 | 0.00 | 0.00 | 0.00 | 0.116257E+11 | 0.200458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625384E+11 | 0.00 | 0.00 | 0.00 | 0.247043E+12 | 0.894016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.403850E+10 | 0.00 | 0.00 | 0.00 | 0.948661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.664350E+10 | 0.00 | 0.00 | 0.00 | 0.324334E+11 | 0.273411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.470682E+10 | 0.00 | 0.00 | 0.00 | 0.793837E+10 | 0.324581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.393042E+10 | 0.00 | 0.00 | 0.00 | 0.896801E+10 | 0.174782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.437568E+10 | 0.00 | 0.00 | 0.00 | 0.109689E+11 | 0.160622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351716E+10 | 0.00 | 0.00 | 0.00 | 0.141589E+11 | 30733961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.486703E+10 | 0.00 | 0.00 | 0.00 | 0.248712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.507840E+10 | 0.00 | 0.00 | 0.00 | 0.265851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.497610E+10 | 0.00 | 0.00 | 0.00 | 0.281329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.528425E+10 | 0.00 | 0.00 | 0.00 | 0.282239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.446314E+10 | 0.00 | 0.00 | 0.00 | 0.237923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466514E+10 | 0.00 | 0.00 | 0.00 | 0.212573E+11 | 21137265.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384864E+10 | 0.00 | 0.00 | 0.00 | 0.125057E+11 | 0.184215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.457477E+10 | 0.00 | 0.00 | 0.00 | 0.980281E+10 | 0.227156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.542876E+11 | 0.00 | 0.00 | 0.00 | 0.217205E+12 | 0.910750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.351716E+10 | 0.00 | 0.00 | 0.00 | 0.793837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.528425E+10 | 0.00 | 0.00 | 0.00 | 0.282239E+11 | 0.324581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.632718E+10 | 0.00 | 0.00 | 0.00 | 0.956462E+10 | 0.919505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.521933E+10 | 0.00 | 0.00 | 0.00 | 0.104572E+11 | 0.528441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.546121E+10 | 0.00 | 0.00 | 0.00 | 0.127721E+11 | 0.498187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.409815E+10 | 0.00 | 0.00 | 0.00 | 0.163655E+11 | 0.497144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.508218E+10 | 0.00 | 0.00 | 0.00 | 0.277690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.535849E+10 | 0.00 | 0.00 | 0.00 | 0.298616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.519130E+10 | 0.00 | 0.00 | 0.00 | 0.311844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.542668E+10 | 0.00 | 0.00 | 0.00 | 0.310427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.450094E+10 | 0.00 | 0.00 | 0.00 | 0.259130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.482243E+10 | 0.00 | 0.00 | 0.00 | 0.231628E+11 | 0.283136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459025E+10 | 0.00 | 0.00 | 0.00 | 0.138665E+11 | 0.185791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.589484E+10 | 0.00 | 0.00 | 0.00 | 0.112670E+11 | 0.699787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.619730E+11 | 0.00 | 0.00 | 0.00 | 0.243226E+12 | 0.290974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.409815E+10 | 0.00 | 0.00 | 0.00 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.632718E+10 | 0.00 | 0.00 | 0.00 | 0.311844E+11 | 0.919505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213663E+10 | 0.105039E+10 | 0.00 | 20027263.08 | 0.392350E+09 | 0.00 | 0.323457E+10 | 0.00 | 0.28 |
February | 0.119271E+10 | 0.162088E+10 | 0.00 | 11437170.90 | 0.373556E+09 | 0.00 | 0.151124E+10 | 0.00 | 0.28 |
March | 0.105980E+10 | 0.250210E+10 | 0.00 | 20414228.56 | 0.283114E+09 | 0.00 | 0.237774E+10 | 0.00 | 0.31 |
April | 0.169675E+09 | 0.460913E+10 | 0.00 | 8270640.17 | 0.455263E+09 | 0.00 | 0.672289E+09 | 0.00 | 0.30 |
May | 0.00 | 0.127413E+11 | 0.00 | 0.00 | 0.181540E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.140342E+11 | 0.00 | 0.00 | 0.206107E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.154095E+11 | 0.00 | 0.00 | 0.376649E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.153925E+11 | 0.00 | 0.00 | 0.248359E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.126288E+11 | 0.00 | 0.00 | 0.289478E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 94721959.44 | 0.931176E+10 | 0.00 | 9383717.09 | 0.158579E+10 | 0.00 | 0.793247E+09 | 0.00 | 0.31 |
November | 0.494042E+09 | 0.344130E+10 | 0.00 | 20155708.50 | 0.467023E+09 | 0.00 | 0.172824E+10 | 0.00 | 0.30 |
December | 0.155894E+10 | 0.248552E+10 | 0.00 | 19640216.62 | 0.324874E+09 | 0.00 | 0.263454E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.670652E+10 | 0.952274E+11 | 0.00 | 0.109329E+09 | 0.169033E+11 | 0.00 | 0.129519E+11 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.105039E+10 | 0.00 | 0.00 | 0.283114E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.213663E+10 | 0.154095E+11 | 0.00 | 20414228.56 | 0.376649E+10 | 0.00 | 0.323457E+10 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.428364E+10 | 0.670236E+09 | 0.00 | 2062152.71 | 0.747776E+09 | 3159967.73 | 0.398747E+09 | 0.00 | 0.26 |
February | 0.212750E+10 | 0.102044E+10 | 0.00 | 896115.48 | 0.916287E+09 | 6214595.70 | 0.193446E+09 | 0.00 | 0.25 |
March | 0.234241E+10 | 0.163026E+10 | 0.00 | 3123908.80 | 0.968530E+09 | 798728.67 | 0.550093E+09 | 0.00 | 0.27 |
April | 0.367747E+09 | 0.320236E+10 | 0.00 | 2366182.21 | 0.148190E+10 | 0.00 | 0.323596E+09 | 0.00 | 0.26 |
May | 0.00 | 0.109391E+11 | 0.00 | 0.00 | 0.226099E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.126864E+11 | 0.00 | 0.00 | 0.214167E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.138579E+11 | 0.00 | 0.00 | 0.379080E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.141648E+11 | 0.00 | 0.00 | 0.236874E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.108493E+11 | 0.00 | 0.00 | 0.336915E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.294232E+09 | 0.819832E+10 | 0.00 | 3719609.94 | 0.180419E+10 | 0.00 | 0.423278E+09 | 0.00 | 0.27 |
November | 0.110576E+10 | 0.268991E+10 | 0.00 | 4349968.25 | 0.106778E+10 | 0.00 | 0.564764E+09 | 0.00 | 0.26 |
December | 0.328034E+10 | 0.147936E+10 | 0.00 | 1310553.76 | 0.117654E+10 | 895249.12 | 0.280014E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.138016E+11 | 0.813883E+11 | 0.00 | 17828491.14 | 0.220944E+11 | 11068541.22 | 0.273394E+10 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.670236E+09 | 0.00 | 0.00 | 0.747776E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.428364E+10 | 0.141648E+11 | 0.00 | 4349968.25 | 0.379080E+10 | 6214595.70 | 0.564764E+09 | 0.00 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.385136E+10 | 0.402751E+09 | 435423.72 | 113499.65 | 0.991536E+09 | 0.149561E+09 | 97263589.56 | 3937.03 | 0.24 |
February | 0.195635E+10 | 0.675221E+09 | 157879.10 | 380351.85 | 0.130457E+10 | 66592494.28 | 91881245.19 | 15164.70 | 0.24 |
March | 0.230728E+10 | 0.129538E+10 | 0.00 | 1555910.88 | 0.122972E+10 | 38346195.53 | 0.366307E+09 | 0.00 | 0.27 |
April | 0.450285E+09 | 0.257865E+10 | 0.00 | 2912713.52 | 0.197587E+10 | 0.00 | 0.326910E+09 | 0.00 | 0.26 |
May | 0.00 | 0.971118E+10 | 0.00 | 0.00 | 0.303711E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.117543E+11 | 0.00 | 0.00 | 0.256590E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.130678E+11 | 0.00 | 0.00 | 0.410195E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.130568E+11 | 0.00 | 0.00 | 0.296555E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.906198E+10 | 0.00 | 0.00 | 0.481151E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.307250E+09 | 0.698249E+10 | 0.00 | 2563757.13 | 0.266656E+10 | 0.00 | 0.308654E+09 | 0.00 | 0.27 |
November | 0.112555E+10 | 0.193046E+10 | 51347.90 | 2145757.20 | 0.185718E+10 | 2922946.68 | 0.383199E+09 | 26805.20 | 0.26 |
December | 0.295563E+10 | 0.109197E+10 | 0.00 | 369008.63 | 0.159714E+10 | 60778545.76 | 93239516.69 | 0.00 | 0.24 |
Annual Sum or Average | 0.129537E+11 | 0.716090E+11 | 644650.72 | 10040998.86 | 0.291046E+11 | 0.318201E+09 | 0.166745E+10 | 45906.93 | 0.27 |
Minimum of Months | 0.00 | 0.402751E+09 | 0.00 | 0.00 | 0.991536E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.385136E+10 | 0.130678E+11 | 435423.72 | 2912713.52 | 0.481151E+10 | 0.149561E+09 | 0.383199E+09 | 26805.20 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.666698E+09 | 0.104187E+09 | 1265033.57 | 778.11 | 0.322379E+09 | 0.604150E+09 | 64534.68 | 27400.76 | 0.35 |
February | 0.371393E+09 | 0.168661E+09 | 2066929.76 | 6489.84 | 0.432254E+09 | 0.284378E+09 | 164641.16 | 59732.49 | 0.36 |
March | 0.578065E+09 | 0.338616E+09 | 380705.09 | 148764.46 | 0.441087E+09 | 0.237698E+09 | 24344154.15 | 23338.14 | 0.39 |
April | 0.160575E+09 | 0.760543E+09 | 452459.89 | 605370.88 | 0.665942E+09 | 12726369.30 | 63797146.38 | 23080.56 | 0.39 |
May | 0.00 | 0.322862E+10 | 0.00 | 0.00 | 0.944299E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.414154E+10 | 0.00 | 0.00 | 0.795721E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.459095E+10 | 0.00 | 0.00 | 0.124220E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.431594E+10 | 0.00 | 0.00 | 0.101151E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.290490E+10 | 0.00 | 0.00 | 0.148183E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.124264E+09 | 0.218510E+10 | 82031.49 | 353871.26 | 0.887477E+09 | 13978242.15 | 45804678.63 | 963.84 | 0.40 |
November | 0.374840E+09 | 0.476027E+09 | 1739158.74 | 111399.64 | 0.686980E+09 | 69964287.40 | 22049949.12 | 71929.74 | 0.37 |
December | 0.539171E+09 | 0.244549E+09 | 1564367.30 | 1332.24 | 0.578250E+09 | 0.422569E+09 | 2586625.34 | 62038.95 | 0.35 |
Annual Sum or Average | 0.281501E+10 | 0.234596E+11 | 7550685.82 | 1228006.43 | 0.948993E+10 | 0.164546E+10 | 0.158812E+09 | 268484.49 | 0.41 |
Minimum of Months | 0.00 | 0.104187E+09 | 0.00 | 0.00 | 0.322379E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.666698E+09 | 0.459095E+10 | 2066929.76 | 605370.88 | 0.148183E+10 | 0.604150E+09 | 63797146.38 | 71929.74 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.823723E+09 | 0.106167E+09 | 1188239.71 | 1940.26 | 0.301202E+09 | 0.384288E+09 | 35668.41 | 19473.63 | 0.53 |
February | 0.438062E+09 | 0.203524E+09 | 1551393.94 | 13608.41 | 0.366168E+09 | 0.182843E+09 | 2578073.76 | 36834.88 | 0.53 |
March | 0.575949E+09 | 0.386636E+09 | 924639.96 | 217843.60 | 0.349936E+09 | 0.178107E+09 | 44222784.44 | 23057.11 | 0.59 |
April | 0.105430E+09 | 0.777381E+09 | 1379545.30 | 918769.17 | 0.583335E+09 | 6585534.47 | 0.114295E+09 | 29974.16 | 0.58 |
May | 0.00 | 0.270709E+10 | 0.00 | 0.00 | 0.105657E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.00 | 0.330507E+10 | 0.00 | 0.00 | 0.995290E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.384652E+10 | 0.00 | 0.00 | 0.133863E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.344545E+10 | 0.00 | 0.00 | 0.120696E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 0.00 | 0.244089E+10 | 0.00 | 0.00 | 0.149268E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.135077E+09 | 0.182229E+10 | 77968.49 | 242653.76 | 0.981252E+09 | 8035782.32 | 29894705.91 | 921.51 | 0.58 |
November | 0.377516E+09 | 0.432663E+09 | 1525324.13 | 99092.23 | 0.649423E+09 | 45603385.38 | 20578796.93 | 40210.95 | 0.56 |
December | 0.626980E+09 | 0.210694E+09 | 1874097.58 | 323.42 | 0.558225E+09 | 0.289035E+09 | 612115.57 | 43724.08 | 0.53 |
Annual Sum or Average | 0.308274E+10 | 0.196844E+11 | 8521209.10 | 1494230.86 | 0.987966E+10 | 0.109450E+10 | 0.212217E+09 | 194196.32 | 0.59 |
Minimum of Months | 0.00 | 0.106167E+09 | 0.00 | 0.00 | 0.301202E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.823723E+09 | 0.384652E+10 | 1874097.58 | 918769.17 | 0.149268E+10 | 0.384288E+09 | 0.114295E+09 | 43724.08 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.761935E+09 | 0.304938E+09 | 1120978.96 | 4530920.13 | 0.296969E+09 | 0.341476E+09 | 0.502506E+09 | 26563.37 | 0.46 |
February | 0.430654E+09 | 0.510815E+09 | 1309182.20 | 2436131.27 | 0.394864E+09 | 0.161317E+09 | 0.225234E+09 | 53689.09 | 0.49 |
March | 0.567137E+09 | 0.576371E+09 | 815605.45 | 2199390.15 | 0.440833E+09 | 0.222756E+09 | 0.265401E+09 | 27779.37 | 0.50 |
April | 0.160823E+09 | 0.927215E+09 | 618753.38 | 1209207.17 | 0.851603E+09 | 10841688.24 | 0.121954E+09 | 31460.66 | 0.49 |
May | 0.00 | 0.313920E+10 | 0.00 | 0.00 | 0.147705E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.378112E+10 | 0.00 | 0.00 | 0.140473E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.430817E+10 | 0.00 | 0.00 | 0.197372E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.458706E+10 | 0.00 | 0.00 | 0.152082E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.373906E+10 | 0.00 | 0.00 | 0.177088E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.130028E+09 | 0.345290E+10 | 99089.29 | 1095924.87 | 0.877355E+09 | 6161427.87 | 0.104513E+09 | 1340.35 | 0.56 |
November | 0.296886E+09 | 0.114557E+10 | 1216705.53 | 3652211.56 | 0.586639E+09 | 39024539.36 | 0.330676E+09 | 42678.50 | 0.54 |
December | 0.618130E+09 | 0.761479E+09 | 911760.27 | 3618240.34 | 0.484468E+09 | 0.253327E+09 | 0.357655E+09 | 43655.96 | 0.50 |
Annual Sum or Average | 0.296559E+10 | 0.272339E+11 | 6092075.07 | 18742025.49 | 0.120799E+11 | 0.103490E+10 | 0.190794E+10 | 227167.29 | 0.51 |
Minimum of Months | 0.00 | 0.304938E+09 | 0.00 | 0.00 | 0.296969E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.761935E+09 | 0.458706E+10 | 1309182.20 | 4530920.13 | 0.197372E+10 | 0.341476E+09 | 0.502506E+09 | 53689.09 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.790269E+09 | 94046659.42 | 1214226.91 | 67023.14 | 0.371304E+09 | 0.540051E+09 | 33603408.61 | 16421.72 | 0.60 |
February | 0.421614E+09 | 0.164183E+09 | 2346347.16 | 194051.89 | 0.493188E+09 | 0.254217E+09 | 28209031.86 | 37934.99 | 0.61 |
March | 0.535882E+09 | 0.244496E+09 | 1389463.07 | 1042039.61 | 0.562473E+09 | 0.235213E+09 | 0.138743E+09 | 24560.87 | 0.66 |
April | 0.167397E+09 | 0.658613E+09 | 1556404.18 | 870468.85 | 0.874985E+09 | 12436082.12 | 83428426.67 | 35064.03 | 0.66 |
May | 0.00 | 0.237210E+10 | 0.00 | 0.00 | 0.153671E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
June | 0.00 | 0.299753E+10 | 0.00 | 0.00 | 0.138970E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 0.00 | 0.324839E+10 | 0.00 | 0.00 | 0.198771E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.324742E+10 | 0.00 | 0.00 | 0.164640E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.227019E+10 | 0.00 | 0.00 | 0.202830E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.139597E+09 | 0.165962E+10 | 374797.17 | 333300.10 | 0.137905E+10 | 14314599.74 | 44290951.97 | 1298.69 | 0.64 |
November | 0.345947E+09 | 0.381307E+09 | 2874922.61 | 485469.11 | 0.845313E+09 | 67282266.29 | 89915109.05 | 49470.84 | 0.63 |
December | 0.605910E+09 | 0.235604E+09 | 3563861.19 | 241933.11 | 0.654253E+09 | 0.384327E+09 | 45168718.12 | 51927.89 | 0.60 |
Annual Sum or Average | 0.300662E+10 | 0.175735E+11 | 13320022.29 | 3234285.80 | 0.137694E+11 | 0.150784E+10 | 0.463359E+09 | 216679.03 | 0.64 |
Minimum of Months | 0.00 | 94046659.42 | 0.00 | 0.00 | 0.371304E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.790269E+09 | 0.324839E+10 | 3563861.19 | 1042039.61 | 0.202830E+10 | 0.540051E+09 | 0.138743E+09 | 51927.89 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.862938E+09 | 99188405.42 | 93166.28 | 406.24 | 0.211219E+09 | 0.393072E+09 | 31274.38 | 2303.31 | 0.30 |
February | 0.430763E+09 | 0.139321E+09 | 115263.58 | 0.00 | 0.273313E+09 | 0.209903E+09 | 0.00 | 5733.29 | 0.30 |
March | 0.602020E+09 | 0.252883E+09 | 0.00 | 12320.99 | 0.325918E+09 | 0.170343E+09 | 555564.32 | 0.00 | 0.32 |
April | 0.158477E+09 | 0.604059E+09 | 0.00 | 206284.25 | 0.461932E+09 | 1460644.66 | 15012676.26 | 0.00 | 0.29 |
May | 0.00 | 0.281046E+10 | 0.00 | 0.00 | 0.604760E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.351608E+10 | 0.00 | 0.00 | 0.612363E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.402529E+10 | 0.00 | 0.00 | 0.100960E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.399583E+10 | 0.00 | 0.00 | 0.694002E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.296361E+10 | 0.00 | 0.00 | 0.810365E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.106420E+09 | 0.211144E+10 | 0.00 | 588662.45 | 0.503094E+09 | 0.00 | 66575678.78 | 0.00 | 0.33 |
November | 0.433248E+09 | 0.556078E+09 | 0.00 | 209393.00 | 0.268085E+09 | 4760252.09 | 32375275.15 | 0.00 | 0.30 |
December | 0.753804E+09 | 0.297235E+09 | 78185.92 | 12809.10 | 0.288173E+09 | 0.212978E+09 | 3052823.08 | 644.06 | 0.30 |
Annual Sum or Average | 0.334767E+10 | 0.213715E+11 | 286615.78 | 1029876.02 | 0.606282E+10 | 0.992516E+09 | 0.117603E+09 | 8680.67 | 0.33 |
Minimum of Months | 0.00 | 99188405.42 | 0.00 | 0.00 | 0.211219E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.862938E+09 | 0.402529E+10 | 115263.58 | 588662.45 | 0.100960E+10 | 0.393072E+09 | 66575678.78 | 5733.29 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110610E+10 | 86938405.33 | 154267.03 | 774.02 | 0.250915E+09 | 0.255429E+09 | 46584.75 | 4567.74 | 0.52 |
February | 0.553771E+09 | 0.156743E+09 | 283868.30 | 19292.08 | 0.291288E+09 | 0.133163E+09 | 7542715.85 | 9541.79 | 0.51 |
March | 0.657099E+09 | 0.303318E+09 | 0.00 | 125360.50 | 0.318057E+09 | 0.146929E+09 | 33748282.12 | 0.00 | 0.54 |
April | 0.115836E+09 | 0.658001E+09 | 107044.51 | 622162.42 | 0.493551E+09 | 1210707.13 | 73766228.04 | 4399.89 | 0.50 |
May | 0.00 | 0.237417E+10 | 0.00 | 0.00 | 0.956790E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.00 | 0.298971E+10 | 0.00 | 0.00 | 0.806421E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.349857E+10 | 0.00 | 0.00 | 0.118639E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.332305E+10 | 0.00 | 0.00 | 0.867915E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.240258E+10 | 0.00 | 0.00 | 0.111489E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.121936E+09 | 0.181153E+10 | 0.00 | 392116.00 | 0.684027E+09 | 354595.67 | 61082434.01 | 0.00 | 0.51 |
November | 0.459733E+09 | 0.419775E+09 | 0.00 | 246924.72 | 0.416699E+09 | 2415455.03 | 47335074.22 | 0.00 | 0.50 |
December | 0.892788E+09 | 0.217893E+09 | 83020.15 | 9602.73 | 0.387304E+09 | 0.155251E+09 | 3286272.38 | 2433.20 | 0.50 |
Annual Sum or Average | 0.390726E+10 | 0.182423E+11 | 628199.99 | 1416232.48 | 0.777425E+10 | 0.694752E+09 | 0.226808E+09 | 20942.60 | 0.53 |
Minimum of Months | 0.00 | 86938405.33 | 0.00 | 0.00 | 0.250915E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.110610E+10 | 0.349857E+10 | 283868.30 | 622162.42 | 0.118639E+10 | 0.255429E+09 | 73766228.04 | 9541.79 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.987962E+09 | 0.325957E+09 | 3981069.05 | 1807599.99 | 0.171928E+09 | 0.369882E+09 | 0.244224E+09 | 22925.53 | 0.42 |
February | 0.552684E+09 | 0.496268E+09 | 6601179.36 | 820393.35 | 0.220446E+09 | 0.194668E+09 | 63488329.32 | 105445.01 | 0.43 |
March | 0.573717E+09 | 0.563486E+09 | 1751973.65 | 740015.95 | 0.292262E+09 | 0.326196E+09 | 80259393.78 | 40888.23 | 0.42 |
April | 0.154872E+09 | 0.959563E+09 | 3339050.68 | 514843.70 | 0.577801E+09 | 22564562.53 | 44580854.88 | 93364.59 | 0.41 |
May | 0.00 | 0.347934E+10 | 0.00 | 0.00 | 0.984488E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.428850E+10 | 0.00 | 0.00 | 0.868386E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.482333E+10 | 0.00 | 0.00 | 0.139166E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.531121E+10 | 0.00 | 0.00 | 0.890858E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.437051E+10 | 0.00 | 0.00 | 0.896117E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.132421E+09 | 0.384564E+10 | 0.00 | 1227160.26 | 0.440315E+09 | 12058224.81 | 84331958.67 | 0.00 | 0.53 |
November | 0.362570E+09 | 0.128381E+10 | 0.00 | 3448395.63 | 0.204659E+09 | 54193083.32 | 0.244256E+09 | 0.00 | 0.47 |
December | 0.771807E+09 | 0.860452E+09 | 2226322.73 | 2404917.73 | 0.201415E+09 | 0.285621E+09 | 0.202375E+09 | 15715.74 | 0.45 |
Annual Sum or Average | 0.353603E+10 | 0.306081E+11 | 17899595.47 | 10963326.62 | 0.714034E+10 | 0.126518E+10 | 0.963516E+09 | 278339.10 | 0.46 |
Minimum of Months | 0.00 | 0.325957E+09 | 0.00 | 0.00 | 0.171928E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.987962E+09 | 0.531121E+10 | 6601179.36 | 3448395.63 | 0.139166E+10 | 0.369882E+09 | 0.244256E+09 | 105445.01 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110416E+10 | 90108545.65 | 105169.09 | 58521.00 | 0.267770E+09 | 0.295489E+09 | 23592698.79 | 3013.37 | 0.55 |
February | 0.539130E+09 | 0.151799E+09 | 202478.58 | 72155.68 | 0.328119E+09 | 0.173452E+09 | 13325409.70 | 6636.10 | 0.54 |
March | 0.649926E+09 | 0.201780E+09 | 6984.80 | 496163.74 | 0.439463E+09 | 0.165830E+09 | 60814088.57 | 598.50 | 0.56 |
April | 0.162290E+09 | 0.585239E+09 | 136062.47 | 457275.11 | 0.645136E+09 | 1265590.42 | 36606743.16 | 3826.39 | 0.53 |
May | 0.00 | 0.211893E+10 | 0.00 | 0.00 | 0.116929E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.00 | 0.270674E+10 | 0.00 | 0.00 | 0.999737E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.302322E+10 | 0.00 | 0.00 | 0.146617E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.321162E+10 | 0.00 | 0.00 | 0.975127E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.240110E+10 | 0.00 | 0.00 | 0.119523E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.147902E+09 | 0.181499E+10 | 0.00 | 414908.35 | 0.725269E+09 | 290917.20 | 44772249.21 | 0.00 | 0.53 |
November | 0.464713E+09 | 0.417424E+09 | 0.00 | 495143.79 | 0.469087E+09 | 3049261.71 | 66786920.73 | 0.00 | 0.52 |
December | 0.900643E+09 | 0.247042E+09 | 87387.82 | 244799.33 | 0.409212E+09 | 0.164076E+09 | 34545576.26 | 1939.27 | 0.53 |
Annual Sum or Average | 0.396876E+10 | 0.169700E+11 | 538082.76 | 2238967.00 | 0.908961E+10 | 0.803453E+09 | 0.280444E+09 | 16013.62 | 0.54 |
Minimum of Months | 0.00 | 90108545.65 | 0.00 | 0.00 | 0.267770E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.110416E+10 | 0.321162E+10 | 202478.58 | 496163.74 | 0.146617E+10 | 0.295489E+09 | 66786920.73 | 6636.10 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.859886E+09 | 0.149039E+09 | 129793.26 | 1146.18 | 0.273437E+09 | 0.558447E+09 | 40446.79 | 6088.91 | 0.36 |
February | 0.421051E+09 | 0.229910E+09 | 151937.74 | 0.00 | 0.343456E+09 | 0.283249E+09 | 0.00 | 5857.47 | 0.36 |
March | 0.678957E+09 | 0.423430E+09 | 0.00 | 55956.87 | 0.366503E+09 | 0.189056E+09 | 5675984.11 | 0.00 | 0.39 |
April | 0.165500E+09 | 0.971433E+09 | 0.00 | 366154.92 | 0.481845E+09 | 1606800.49 | 40675852.30 | 0.00 | 0.38 |
May | 0.00 | 0.382848E+10 | 0.00 | 0.00 | 0.630610E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.468125E+10 | 0.00 | 0.00 | 0.665738E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.511537E+10 | 0.00 | 0.00 | 0.110274E+10 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.485886E+10 | 0.00 | 0.00 | 0.807739E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.340161E+10 | 0.00 | 0.00 | 0.110778E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.140499E+09 | 0.255504E+10 | 0.00 | 428461.42 | 0.645298E+09 | 2125603.24 | 52683542.60 | 0.00 | 0.39 |
November | 0.447498E+09 | 0.631438E+09 | 30346.44 | 167198.13 | 0.484317E+09 | 24303687.33 | 27491919.65 | 216.29 | 0.37 |
December | 0.701739E+09 | 0.360683E+09 | 165453.35 | 13224.30 | 0.421585E+09 | 0.376770E+09 | 2658034.56 | 2755.65 | 0.36 |
Annual Sum or Average | 0.341513E+10 | 0.272065E+11 | 477530.79 | 1032141.82 | 0.733104E+10 | 0.143556E+10 | 0.129226E+09 | 14918.32 | 0.41 |
Minimum of Months | 0.00 | 0.149039E+09 | 0.00 | 0.00 | 0.273437E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.859886E+09 | 0.511537E+10 | 165453.35 | 428461.42 | 0.110778E+10 | 0.558447E+09 | 52683542.60 | 6088.91 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115094E+10 | 90558112.94 | 583655.71 | 4803.19 | 0.381286E+09 | 0.442854E+09 | 159863.19 | 10567.61 | 0.64 |
February | 0.595992E+09 | 0.224171E+09 | 457480.10 | 28206.25 | 0.408208E+09 | 0.189042E+09 | 6424731.16 | 20779.63 | 0.63 |
March | 0.766832E+09 | 0.416528E+09 | 10778.42 | 153870.23 | 0.421829E+09 | 0.179228E+09 | 35666601.01 | 746.13 | 0.68 |
April | 0.136259E+09 | 0.879289E+09 | 180245.67 | 642974.66 | 0.648376E+09 | 1946927.19 | 98502079.60 | 11682.45 | 0.65 |
May | 0.00 | 0.295177E+10 | 0.00 | 0.00 | 0.124568E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 0.00 | 0.361895E+10 | 0.00 | 0.00 | 0.115799E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.00 | 0.416504E+10 | 0.00 | 0.00 | 0.158029E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.369120E+10 | 0.00 | 0.00 | 0.141257E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.259070E+10 | 0.00 | 0.00 | 0.171372E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 0.177346E+09 | 0.192547E+10 | 30824.97 | 210313.67 | 0.116539E+10 | 3949198.81 | 33660679.28 | 567.40 | 0.63 |
November | 0.518628E+09 | 0.430866E+09 | 131595.04 | 123248.43 | 0.729945E+09 | 16088740.88 | 26196069.96 | 2096.85 | 0.63 |
December | 0.893696E+09 | 0.175503E+09 | 250138.30 | 6278.92 | 0.658639E+09 | 0.319430E+09 | 1890103.92 | 4262.70 | 0.63 |
Annual Sum or Average | 0.423969E+10 | 0.211600E+11 | 1644718.21 | 1169695.35 | 0.115239E+11 | 0.115254E+10 | 0.202500E+09 | 50702.77 | 0.66 |
Minimum of Months | 0.00 | 90558112.94 | 0.00 | 0.00 | 0.381286E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.115094E+10 | 0.416504E+10 | 583655.71 | 642974.66 | 0.171372E+10 | 0.442854E+09 | 98502079.60 | 20779.63 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.987851E+09 | 0.413663E+09 | 168829.53 | 5277999.98 | 0.255237E+09 | 0.298167E+09 | 0.658320E+09 | 3390.78 | 0.53 |
February | 0.546199E+09 | 0.698282E+09 | 141357.20 | 2764996.81 | 0.304319E+09 | 0.124025E+09 | 0.260625E+09 | 6109.75 | 0.54 |
March | 0.731702E+09 | 0.752981E+09 | 0.00 | 1896023.29 | 0.356826E+09 | 0.190452E+09 | 0.221030E+09 | 0.00 | 0.53 |
April | 0.180400E+09 | 0.122777E+10 | 14692.35 | 780334.44 | 0.672643E+09 | 2036497.27 | 85959305.53 | 379.70 | 0.50 |
May | 0.00 | 0.368824E+10 | 0.00 | 0.00 | 0.124779E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.444426E+10 | 0.00 | 0.00 | 0.113266E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.494865E+10 | 0.00 | 0.00 | 0.174161E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.530998E+10 | 0.00 | 0.00 | 0.124965E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.440915E+10 | 0.00 | 0.00 | 0.142952E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.152399E+09 | 0.406393E+10 | 0.00 | 1217862.76 | 0.688896E+09 | 1075492.05 | 0.115507E+09 | 0.00 | 0.58 |
November | 0.398068E+09 | 0.142727E+10 | 0.00 | 3869193.19 | 0.409280E+09 | 5432879.21 | 0.360011E+09 | 0.00 | 0.59 |
December | 0.804510E+09 | 0.980958E+09 | 130876.97 | 4397023.71 | 0.352295E+09 | 0.218896E+09 | 0.459355E+09 | 2724.75 | 0.56 |
Annual Sum or Average | 0.380113E+10 | 0.323651E+11 | 455756.04 | 20203434.18 | 0.984073E+10 | 0.840084E+09 | 0.216081E+10 | 12604.99 | 0.54 |
Minimum of Months | 0.00 | 0.413663E+09 | 0.00 | 0.00 | 0.255237E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.987851E+09 | 0.530998E+10 | 168829.53 | 5277999.98 | 0.174161E+10 | 0.298167E+09 | 0.658320E+09 | 6109.75 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108808E+10 | 0.123973E+09 | 567018.74 | 109448.66 | 0.379860E+09 | 0.541208E+09 | 39794609.69 | 9899.16 | 0.68 |
February | 0.543132E+09 | 0.217990E+09 | 560884.55 | 150944.20 | 0.468258E+09 | 0.265066E+09 | 20733990.41 | 19361.73 | 0.67 |
March | 0.716329E+09 | 0.319339E+09 | 211911.34 | 814041.22 | 0.548107E+09 | 0.213847E+09 | 0.103567E+09 | 2948.68 | 0.72 |
April | 0.191679E+09 | 0.893100E+09 | 189470.64 | 570003.36 | 0.781598E+09 | 2497326.85 | 56441620.00 | 11515.65 | 0.70 |
May | 0.00 | 0.282155E+10 | 0.00 | 0.00 | 0.145675E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
June | 0.00 | 0.349856E+10 | 0.00 | 0.00 | 0.134634E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.369246E+10 | 0.00 | 0.00 | 0.201045E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.372770E+10 | 0.00 | 0.00 | 0.159859E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.268032E+10 | 0.00 | 0.00 | 0.186432E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.180752E+09 | 0.203683E+10 | 32725.95 | 349587.06 | 0.124027E+10 | 3242022.84 | 44025921.14 | 148.00 | 0.67 |
November | 0.489052E+09 | 0.474941E+09 | 173652.28 | 494766.29 | 0.773804E+09 | 21896943.88 | 80447137.49 | 2316.47 | 0.67 |
December | 0.877287E+09 | 0.304154E+09 | 336012.99 | 221825.10 | 0.603623E+09 | 0.353680E+09 | 41925589.99 | 4296.05 | 0.67 |
Annual Sum or Average | 0.408631E+10 | 0.207909E+11 | 2071676.50 | 2710615.91 | 0.130720E+11 | 0.140144E+10 | 0.386936E+09 | 50485.75 | 0.69 |
Minimum of Months | 0.00 | 0.123973E+09 | 0.00 | 0.00 | 0.379860E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.108808E+10 | 0.372770E+10 | 567018.74 | 814041.22 | 0.201045E+10 | 0.541208E+09 | 0.103567E+09 | 19361.73 | 0.72 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.324164E+12 | 0.611588E+10 | 0.00 | 0.420006E+11 | 0.138428E+12 |
February | 0.341166E+12 | 0.358068E+10 | 0.00 | 0.153245E+11 | 0.154635E+12 |
March | 0.378807E+12 | 0.310598E+10 | 0.00 | 0.125647E+11 | 0.188298E+12 |
April | 0.420455E+12 | -0.222578E+10 | 0.00 | -0.322263E+11 | 0.241216E+12 |
May | 0.408806E+12 | -0.127177E+11 | 0.00 | -0.129445E+12 | 0.406065E+12 |
June | 0.407119E+12 | -0.120615E+11 | 0.00 | -0.144882E+12 | 0.431062E+12 |
July | 0.420257E+12 | -0.157442E+11 | 0.00 | -0.179425E+12 | 0.457485E+12 |
August | 0.391871E+12 | -0.159577E+11 | 0.00 | -0.158846E+12 | 0.462763E+12 |
September | 0.338461E+12 | -0.140202E+11 | 0.00 | -0.139987E+12 | 0.398944E+12 |
October | 0.349158E+12 | -0.991276E+10 | 0.00 | -0.897012E+11 | 0.355163E+12 |
November | 0.286470E+12 | 0.237689E+09 | 0.00 | -0.102303E+11 | 0.214818E+12 |
December | 0.291274E+12 | 0.417544E+10 | 0.00 | 0.202732E+11 | 0.169286E+12 |
Annual Sum or Average | 0.435801E+13 | -0.654239E+11 | 0.00 | -0.794579E+12 | 0.361816E+13 |
Minimum of Months | 0.286470E+12 | -0.159577E+11 | 0.00 | -0.179425E+12 | 0.138428E+12 |
Maximum of Months | 0.420455E+12 | 0.611588E+10 | 0.00 | 0.420006E+11 | 0.462763E+12 |