Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2024-07-03 12:20:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3674.30 | 737.49 | 737.49 |
Net Site Energy | 3674.30 | 737.49 | 737.49 |
Total Source Energy | 7879.26 | 1581.49 | 1581.49 |
Net Source Energy | 7879.26 | 1581.49 | 1581.49 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1803.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 56.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 234.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 180.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 9.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 68.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1870.53 | 1803.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1803.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 56.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 234.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 180.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 9.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 68.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1803.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 56.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 234.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 180.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 9.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 68.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 62.91 | 362.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 375.44 | 362.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 62.91 | 362.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 375.44 | 362.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1870.532 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1870.532 | 100.00 |
Total On-Site and Utility Electric Sources | 1870.532 | 100.00 |
Total Electricity End Uses | 1870.532 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1107.83 |
Time Setpoint Not Met During Occupied Cooling | 11.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3577.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-15:09 | 27-FEB-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 437022.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48143.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24236.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5404.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 170582.04 | 437022.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 437022.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 48143.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 24236.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 5404.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1955.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 178.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 741.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 215.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5923.98 | 1955.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 392.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 148.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 114.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1189.03 | 392.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 392.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 148.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 114.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1189.03 | 392.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.45 | 0.217438 | 0.300000 | 1.03 | 0.579835 | 0.500000 | 0.001752 | 0.000185 | 1.03 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.84 | 0.264253 | 0.300000 | 0.850837 | 0.704675 | 0.500000 | 0.001442 | 0.000341 | 1.66 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 3.57 | 0.210139 | 0.300000 | 1.07 | 0.560371 | 0.500000 | 0.001813 | 0.000730 | 3.57 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.58 | 0.099770 | 0.300000 | 0.475068 | 0.300000 | 0.500000 | 0.003819 | 0.000323 | 1.58 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.03 | 0.096669 | 0.300000 | 0.310406 | 0.300000 | 0.500000 | 0.003941 | 0.000211 | 1.03 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.57 | 0.100380 | 0.300000 | 0.472180 | 0.300000 | 0.500000 | 0.003796 | 0.000321 | 1.57 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.03 | 0.097223 | 0.300000 | 0.308616 | 0.300000 | 0.500000 | 0.003919 | 0.000210 | 1.03 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.30 | 0.121854 | 0.300000 | 0.388968 | 0.324945 | 0.500000 | 0.003127 | 0.000265 | 1.30 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.854062 | 0.117113 | 0.300000 | 0.256219 | 0.312302 | 0.500000 | 0.003253 | 0.000174 | 0.854062 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.29 | 0.122617 | 0.300000 | 0.386549 | 0.326979 | 0.500000 | 0.003107 | 0.000263 | 1.29 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.848772 | 0.117835 | 0.300000 | 0.254632 | 0.314227 | 0.500000 | 0.003233 | 0.000173 | 0.848772 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 1.21 | 0.130899 | 0.300000 | 0.362093 | 0.349063 | 0.500000 | 0.002911 | 0.000247 | 1.21 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.954563 | 0.300000 | 0.500000 | 0.003636 | 0.000163 | 0.796084 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.45 | 0.108865 | 0.300000 | 0.435380 | 0.300000 | 0.500000 | 0.003500 | 0.000245 | 1.20 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.948420 | 0.105455 | 0.300000 | 0.284526 | 0.300000 | 0.500000 | 0.003613 | 0.000161 | 0.790481 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21148.56 | 0.000185 | 477.64 |
CORE_MID VAV BOX REHEAT COIL | 38999.52 | 0.000341 | 912.28 |
CORE_TOP VAV BOX REHEAT COIL | 83388.59 | 0.000730 | 1948.41 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 36958.17 | 0.000323 | 863.11 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24147.07 | 0.000211 | 563.91 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 36733.84 | 0.000321 | 857.87 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 24008.04 | 0.000210 | 560.67 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 30268.13 | 0.000265 | 706.92 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 19936.59 | 0.000174 | 465.62 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 30080.26 | 0.000263 | 702.54 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 19813.33 | 0.000173 | 462.74 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 28182.18 | 0.000247 | 658.24 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 18586.53 | 0.000163 | 434.11 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 27958.27 | 0.000245 | 653.01 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 18455.98 | 0.000161 | 431.06 |
PACU_VAV_BOT HEATING COIL | 57426.83 | 0.000502 | 894.85 |
PACU_VAV_MID HEATING COIL | 57877.67 | 0.000506 | 893.28 |
PACU_VAV_TOP HEATING COIL | 51397.06 | 0.000450 | 845.23 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.87 | 2.32 | 7.73 | 5.08 | 5.99 | 5.99 | 0.300000 | 0.848381 | 5.99 |
PACU_VAV_MID | 3.70 | 2.22 | 7.40 | 5.65 | 5.70 | 5.70 | 0.300000 | 0.991164 | 5.70 |
PACU_VAV_TOP | 4.39 | 2.64 | 8.79 | 8.79 | 6.40 | 8.79 | 0.300000 | 1.00 | 8.79 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.99 |
PACU_VAV_MID_OA_CONTROLLER | 5.70 |
PACU_VAV_TOP_OA_CONTROLLER | 8.79 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.99 | 99193.24 | 0.800655 | 2.00 | 33061.11 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.70 | 94396.15 | 0.800655 | 1.90 | 31462.24 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 8.79 | 145462.26 | 0.800655 | 2.93 | 48482.57 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.99 |
PACU_VAV_MID FAN | 5.70 |
PACU_VAV_TOP FAN | 8.79 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000502 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000506 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000450 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.005471 | 0.656518 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.005471 | 1647.62 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 625366.62 | 625366.62 | 0.005471 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 4.938 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2025 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 4.9377744 | 4.9377744 | 4.9377744 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
43 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
44 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
45 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
46 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
47 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
48 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
49 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
50 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
51 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
52 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
53 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
54 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
55 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
56 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
57 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
58 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
59 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
60 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
61 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
62 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
63 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
64 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
65 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
66 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
67 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
68 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
69 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
70 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
71 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
72 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
73 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
74 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
75 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
76 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
77 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
78 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
79 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
80 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
81 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
82 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
83 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
84 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
85 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
86 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
87 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
88 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
89 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
90 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
91 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
92 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
93 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
94 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
95 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
96 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
97 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.46_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.46_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40625.18581 | 46718.96369 | 2.99718 | 3.44675 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8808.14120 | 11010.17651 | 0.63667 | 0.79583 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 33453.50855 | 38471.53483 | 2.46619 | 2.83612 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18169.69583 | 22712.11979 | 1.32894 | 1.66118 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 33438.05164 | 38453.75939 | 2.48760 | 2.86074 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 26.99200 | 7.00652E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 38736.19281 | 48420.24101 | 2.85318 | 3.56647 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9003.69030 | 10354.24384 | 0.66980 | 0.77027 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 27.19600 | 7.00683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 17146.00679 | 21432.50849 | 1.26685 | 1.58356 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11082.71635 | 12745.12380 | 0.82446 | 0.94812 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 22.36800 | 6.99957E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 11202.18071 | 14002.72589 | 0.82775 | 1.03469 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 17948.18370 | 20640.41125 | 1.33519 | 1.53547 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 17042.04924 | 21302.56155 | 1.25915 | 1.57393 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11707.27227 | 13463.36311 | 0.87092 | 1.00156 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95200 | 7.00344E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 11137.75173 | 13922.18966 | 0.82298 | 1.02872 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7336.43040 | 8436.89496 | 0.54578 | 0.62764 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 21.07600 | 6.99765E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 14044.85243 | 17556.06554 | 1.03725 | 1.29656 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9133.90749 | 10503.99361 | 0.67461 | 0.77580 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 9250.38616 | 11562.98270 | 0.68325 | 0.85406 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 14415.52975 | 16577.85921 | 1.07240 | 1.23326 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 13957.80107 | 17447.25133 | 1.03080 | 1.28850 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9521.03946 | 10949.19538 | 0.70829 | 0.81453 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 23.23500 | 7.00086E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 9193.27080 | 11491.58850 | 0.67902 | 0.84877 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8435.06043 | 9700.31949 | 0.62750 | 0.72163 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 13078.92271 | 16348.65339 | 0.96558 | 1.20698 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11157.94270 | 12831.63411 | 0.83005 | 0.95456 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 22.07900 | 6.99914E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8625.21615 | 10781.52019 | 0.63687 | 0.79608 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 16963.88743 | 19508.47054 | 1.26197 | 1.45127 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12975.16939 | 16218.96174 | 0.95789 | 1.19737 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11086.12597 | 12749.04487 | 0.82471 | 0.94842 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8564.72464 | 10705.90581 | 0.63239 | 0.79048 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 83126.80 | 5.99226 | 5.99226 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 62014.88 | 5.08372 | 5.08372 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 79261.33 | 5.70247 | 5.70247 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 62193.42 | 5.65209 | 5.65209 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 88234.73 | 6.39512 | 6.39512 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 61879.01 | 8.78737 | 8.78737 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.44675 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21744 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.03403 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57983 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75222E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.85017E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.03403 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21148.55900 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85017E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 477.63637 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.83612 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26425 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.85084 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70468 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44180E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.41185E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.66118 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38999.52481 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.41185E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 912.28154 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.56647 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21014 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.06994 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56037 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81309E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.29520E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.56647 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 83388.59214 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.29520E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1948.41408 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58356 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.97698E-002 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47507 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81879E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.23326E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.58356 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36958.17484 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.23326E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 863.10813 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03469 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.66686E-002 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31041 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.94130E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.11249E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.03469 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24147.06953 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.11249E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 563.91479 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57393 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10038 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47218 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.79557E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.21364E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.57393 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36733.83754 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.21364E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 857.87129 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02872 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.72229E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30862 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.91883E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.10033E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.02872 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24008.03594 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10033E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 560.66922 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29656 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12185 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38897 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32495 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12668E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.64799E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.29656 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30268.13084 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64799E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 706.92415 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85406 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11711 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25622 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31230 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25327E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74414E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.85406 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19936.58701 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74414E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 465.61754 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28850 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12262 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38655 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32698 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10724E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.63155E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28850 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30080.26173 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.63155E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 702.53872 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84877 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11784 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25463 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31423 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23333E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73336E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84877 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19813.32707 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73336E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 462.74026 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20698 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13090 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36209 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34906 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91065E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.46550E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20698 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 28182.18047 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.46550E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 658.24059 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95456 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.63609E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62603E-004 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.79608 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18586.53112 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62603E-004 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 434.10865 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45127 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10886 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43538 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49975E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.44591E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19737 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27958.26661 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.44591E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 653.01378 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94842 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10545 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28453 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.61293E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.61461E-004 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.79048 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18455.98432 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61461E-004 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 431.06128 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.86732 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.32039 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.73464 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.08372 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.99226 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.99226 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.84838 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.69867 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.21920 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.39735 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.65209 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.70247 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.70247 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.99116 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.39369 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.63621 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.78737 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 8.78737 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.39512 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 8.78737 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.99226 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.70247 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 8.78737 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.99226 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.99226 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 99193.23715 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.99722 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33061.10594 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 57426.83274 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.02395E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 894.85239 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.99226 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.02395E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.70247 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.70247 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 94396.14831 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.90063 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31462.23623 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 57877.66920 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.06339E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 893.28085 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.70247 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.06339E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.78737 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 8.78737 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 145462.25734 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.92883 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 48482.57037 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 51397.05531 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.49644E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 845.22728 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 8.78737 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.49644E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.47098E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.65652 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.47098E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1647.61892 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 625366.62022 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 625366.62000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.47098E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20067.42 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 36997.69 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 79108.69 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35061.38 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22907.78 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34848.56 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22775.88 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 28714.68 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 18913.38 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 28536.45 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 18796.45 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 26735.78 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 17632.61 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 26523.36 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 17508.77 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 39290.40 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 38999.36 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 39456.31 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 97486.37 | 332637.30 | 11.07 | 2.87 | 3.17 | 3.33 | 3.51 | 9.79 | 10.81 | 11.37 | 11.99 | 6.8229 | 5.3968 | 3.6165 | 1.5072 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 92771.83 | 316550.61 | 11.07 | 2.87 | 3.17 | 3.33 | 3.51 | 9.79 | 10.81 | 11.37 | 11.99 | 6.4930 | 5.1358 | 3.4416 | 1.4343 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 142959.21 | 487797.09 | 11.07 | 2.87 | 3.17 | 3.33 | 3.51 | 9.79 | 10.81 | 11.37 | 11.99 | 10.0055 | 7.9141 | 5.3035 | 2.2102 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.384 | 0.363 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 4.938 | 4.938 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_NORTH_0.4 | N/A | 2.615 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_EAST_0.4 | N/A | 2.615 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_SOUTH_0.4 | N/A | 2.615 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.384 | 0.363 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_WEST_0.4 | N/A | 2.615 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.6765866851E-002 | 3.0845181488E-002 | Pass | Pass | 0.4869686839 | 0.4968550652 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.3656747203 | 0.2560213343 | Pass | Pass | 0.4857050789 | 0.4963620501 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1279449853 | 7.5421347950E-002 | Pass | Pass | 0.4884740506 | 0.4861769959 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1150879764 | 6.6975060003E-002 | Pass | Pass | 0.4843983500 | 0.4835598385 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.7354877169E-002 | 3.8980151596E-002 | Pass | Pass | 0.6624020394 | 0.6443679405 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2197539146 | 0.2158907399 | Pass | Pass | 0.6456176652 | 0.6387145227 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.8071209289 | 0.7906350692 | Pass | Pass | 0.5842825035 | 0.5931161943 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8327291641 | 0.8146887327 | Pass | Pass | 0.5820236700 | 0.5905488537 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7858479866 | 0.7724252029 | Pass | Pass | 0.5840460674 | 0.5938164000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8253474398 | 0.8083061263 | Pass | Pass | 0.5828046364 | 0.5912662643 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6961481073 | 0.6775318455 | Pass | Pass | 0.5979242514 | 0.6093721120 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7237566903 | 0.7040757848 | Pass | Pass | 0.5950668926 | 0.6083851710 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6741379513 | 0.6591814391 | Pass | Pass | 0.6004502845 | 0.6134435183 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7173834500 | 0.6981625210 | Pass | Pass | 0.5953984119 | 0.6088808583 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6356050601 | 0.6178689411 | Pass | Pass | 0.6079984572 | 0.5662779224 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6616068998 | 0.6529083145 | Pass | Pass | 0.6020032217 | 0.5690935876 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6151372442 | 0.6111402410 | Pass | Pass | 0.6029463013 | 0.5760706290 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6546264392 | 0.6468415413 | Pass | Pass | 0.6019741512 | 0.5698983283 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2470.13 | 175.86 | 0.00 | 2965.91 | 869.45 | 6481.35 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.46_SHGC_NORTH_0.4 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 2.615 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.46_SHGC_EAST_0.4 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 2.615 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 2.615 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.46_SHGC_WEST_0.4 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 2.615 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.46_SHGC_NORTH_0.4 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.46_SHGC_EAST_0.4 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.46_SHGC_EAST_0.4 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.46_SHGC_WEST_0.4 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.46_SHGC_WEST_0.4 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 2.615 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.46_SHGC_NORTH_0.4 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 2.615 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.46_SHGC_EAST_0.4 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 2.615 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.46_SHGC_SOUTH_0.4 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 2.615 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.46_SHGC_WEST_0.4 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 2.615 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 2.615 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 183.92 | 2.615 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 429.15 | 2.615 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.06 | 83.06 | 234.07 | |
Exterior Lighting Total | 15013.15 | 234.07 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 625366.62 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 99193.24 | 79419.59 | 19773.65 | 0.80 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 94396.15 | 75578.77 | 18817.38 | 0.80 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 145462.26 | 116465.12 | 28997.14 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 97486.4 | 2.87 | 9.79 | N/A | N/A | 11.07 | |
PACU_VAV_MID COOLING COIL | 92771.8 | 2.87 | 9.79 | N/A | N/A | 11.07 | |
PACU_VAV_TOP COOLING COIL | 142959.2 | 2.87 | 9.79 | N/A | N/A | 11.07 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 21148.56 | 20067.42 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 38999.52 | 36997.69 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 83388.59 | 79108.69 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 36958.17 | 35061.38 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 24147.07 | 22907.78 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 36733.84 | 34848.56 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 24008.04 | 22775.88 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 30268.13 | 28714.68 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19936.59 | 18913.38 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30080.26 | 28536.45 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 19813.33 | 18796.45 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 28182.18 | 26735.78 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 18586.53 | 17632.61 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 27958.27 | 26523.36 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 18455.98 | 17508.77 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 57426.83 | 39290.40 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 57877.67 | 38999.36 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 51397.06 | 39456.31 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.99 | 13254.65 | 2211.96 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.70 | 12613.64 | 2211.96 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 8.79 | 19312.73 | 2197.78 | 1.00 | 1.12 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.005471 | 1647.62 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 97486.37 | 2.87 | 9.79 | 11.07 | 6.8229 | 3.17 | 10.81 | 5.3968 | 3.33 | 11.37 | 3.6165 | 3.51 | 11.99 | 1.5072 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 92771.83 | 2.87 | 9.79 | 11.07 | 6.4930 | 3.17 | 10.81 | 5.1358 | 3.33 | 11.37 | 3.4416 | 3.51 | 11.99 | 1.4343 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 142959.21 | 2.87 | 9.79 | 11.07 | 10.0055 | 3.17 | 10.81 | 7.9141 | 3.33 | 11.37 | 5.3035 | 3.51 | 11.99 | 2.2102 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40625.19 | 46718.96 | 47.50 | 2.997 | 3.447 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_MID | 33453.51 | 38471.53 | 39.12 | 2.466 | 2.836 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_TOP | 33438.05 | 38453.76 | 39.10 | 2.488 | 2.861 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00886 | 26.99 | 0.00701 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9003.69 | 10354.24 | 49.94 | 0.670 | 0.770 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00872 | 27.20 | 0.00701 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11082.72 | 12745.12 | 97.10 | 0.824 | 0.948 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00861 | 22.37 | 0.00700 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17948.18 | 20640.41 | 99.55 | 1.335 | 1.535 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00861 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11707.27 | 13463.36 | 102.58 | 0.871 | 1.002 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00861 | 24.95 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7336.43 | 8436.89 | 40.69 | 0.546 | 0.628 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00880 | 21.08 | 0.00700 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9133.91 | 10503.99 | 80.02 | 0.675 | 0.776 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00865 | 19.85 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 14415.53 | 16577.86 | 79.96 | 1.072 | 1.233 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00866 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9521.04 | 10949.20 | 83.42 | 0.708 | 0.815 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 24.00 | 24.00 | 0.00865 | 23.23 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8435.06 | 9700.32 | 46.79 | 0.628 | 0.722 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00874 | 21.38 | 0.00700 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11157.94 | 12831.63 | 97.76 | 0.830 | 0.955 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00862 | 22.08 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 16963.89 | 19508.47 | 94.09 | 1.262 | 1.451 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00862 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11086.13 | 12749.04 | 97.13 | 0.825 | 0.948 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00862 | 24.70 | 0.00700 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8808.14 | 11010.18 | 11.19 | 0.637 | 0.796 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_MID | 18169.70 | 22712.12 | 23.09 | 1.329 | 1.661 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_TOP | 38736.19 | 48420.24 | 49.23 | 2.853 | 3.566 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 17146.01 | 21432.51 | 103.37 | 1.267 | 1.584 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11202.18 | 14002.73 | 106.68 | 0.828 | 1.035 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17042.05 | 21302.56 | 102.74 | 1.259 | 1.574 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11137.75 | 13922.19 | 106.07 | 0.823 | 1.029 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 14044.85 | 17556.07 | 84.67 | 1.037 | 1.297 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9250.39 | 11562.98 | 88.09 | 0.683 | 0.854 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 13957.80 | 17447.25 | 84.15 | 1.031 | 1.288 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9193.27 | 11491.59 | 87.55 | 0.679 | 0.849 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 13078.92 | 16348.65 | 78.85 | 0.966 | 1.207 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8625.22 | 10781.52 | 82.14 | 0.637 | 0.796 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12975.17 | 16218.96 | 78.22 | 0.958 | 1.197 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8564.72 | 10705.91 | 81.57 | 0.632 | 0.790 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.99 | 5.99 | 5.08 | 5.08 | 5.9923 | 5.0837 | 5.9923 | 0.8484 | 0.3000 |
PACU_VAV_MID | 5.70 | 5.70 | 5.65 | 5.65 | 5.7025 | 5.6521 | 5.7025 | 0.9912 | 0.3000 |
PACU_VAV_TOP | 6.40 | 6.40 | 8.79 | 8.79 | 6.3951 | 8.7874 | 8.7874 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21148.559 | 21148.559 | 1.034026 | 0.00018502 | 477.636 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21148.56 | 21148.56 | 1.034026 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 11010.18 | 0.00 | 21248.14 | 21248.14 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 38999.525 | 38999.525 | 1.661175 | 0.00034118 | 912.282 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38999.52 | 38999.52 | 1.661175 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 22712.12 | 0.00 | 39178.22 | 39178.22 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 83388.592 | 83388.592 | 3.566471 | 0.00072952 | 1948.414 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 83388.59 | 82870.22 | 3.566471 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 48420.24 | 0.00 | 83770.86 | 83770.86 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 36958.175 | 36958.175 | 1.583561 | 0.00032333 | 863.108 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36958.17 | 36795.49 | 1.583561 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798142 | 50.7967 | 21432.51 | 0.00 | 37127.63 | 37127.63 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 24147.070 | 24147.070 | 1.034687 | 0.00021125 | 563.915 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24147.07 | 24041.91 | 1.034687 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798103 | 50.7942 | 14002.73 | 0.00 | 24257.79 | 24257.79 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 36733.838 | 36733.838 | 1.573934 | 0.00032136 | 857.871 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36733.84 | 36571.80 | 1.573934 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798131 | 50.7960 | 21302.56 | 0.00 | 36902.27 | 36902.27 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 24008.036 | 24008.036 | 1.028721 | 0.00021003 | 560.669 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24008.04 | 23903.27 | 1.028721 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798092 | 50.7936 | 13922.19 | 0.00 | 24118.12 | 24118.12 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 30268.131 | 30268.131 | 1.296560 | 0.00026480 | 706.924 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30268.13 | 30126.76 | 1.296560 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798804 | 50.8381 | 17556.07 | 0.00 | 30406.91 | 30406.91 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 19936.587 | 19936.587 | 0.854062 | 0.00017441 | 465.618 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19936.59 | 19844.91 | 0.854062 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798789 | 50.8372 | 11562.98 | 0.00 | 20028.00 | 20028.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 30080.262 | 30080.262 | 1.288497 | 0.00026316 | 702.539 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30080.26 | 29939.41 | 1.288497 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798797 | 50.8377 | 17447.25 | 0.00 | 30218.18 | 30218.18 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 19813.327 | 19813.327 | 0.848772 | 0.00017334 | 462.740 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19813.33 | 19721.99 | 0.848772 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798782 | 50.8367 | 11491.59 | 0.00 | 19904.17 | 19904.17 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 28182.180 | 28182.180 | 1.206978 | 0.00024655 | 658.241 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28182.18 | 28045.23 | 1.206978 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797982 | 50.7866 | 16348.65 | 0.00 | 28311.39 | 28311.39 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 18586.531 | 18586.531 | 0.796084 | 0.00016260 | 434.109 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18586.53 | 18586.53 | 0.796084 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797960 | 50.7852 | 10781.52 | 0.00 | 18671.75 | 18671.75 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 27958.267 | 27958.267 | 1.197368 | 0.00024459 | 653.014 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27958.27 | 27958.27 | 1.197368 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797966 | 50.7856 | 16218.96 | 0.00 | 28086.45 | 28086.45 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 18455.984 | 18455.984 | 0.790481 | 0.00016146 | 431.061 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18455.98 | 18455.98 | 0.790481 | 12.89 | 11.49 | 0.00800000 | 32.11 | 18.56 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797945 | 50.7843 | 10705.91 | 0.00 | 18540.60 | 18540.60 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 99193.237 | 79419.587 | 5.992263 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 100758.49 | 100758.49 | 5.992263 | 24.54 | 16.41 | 0.00849152 | 11.06 | 11.06 | 0.00849152 | 27.40 | 0.00700714 | 16.15 | 15.9556 | 24.00 | 0.00877353 | 46.4771 | 69998.29 | 0.00 | 102281.54 | 79864.10 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 57426.833 | 57426.833 | 1.797679 | 0.00050239 | 894.852 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 57426.83 | 57426.83 | 1.797679 | -13.93 | -13.93 | 0.00376429 | 12.89 | 11.49 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 53.1852 | 18.48 | 0.00798225 | 59.3948 | 9523.04 | 0.00 | 47530.97 | 47530.97 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 94396.148 | 75578.773 | 5.702471 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 95885.71 | 95885.71 | 5.702471 | 24.57 | 16.41 | 0.00848240 | 11.06 | 11.06 | 0.00848240 | 27.40 | 0.00700714 | 16.15 | 16.7664 | 24.00 | 0.00877995 | 46.5105 | 66584.28 | 0.00 | 97335.10 | 76001.79 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 57877.669 | 57877.669 | 1.710741 | 0.00050634 | 893.281 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 57877.67 | 57877.67 | 1.710741 | -15.51 | -15.51 | 0.00354009 | 12.89 | 11.49 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 55.8880 | 17.72 | 0.00797173 | 62.2224 | 9032.07 | 0.00 | 47190.77 | 47190.77 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 145462.257 | 116465.121 | 8.787375 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 147835.47 | 147835.47 | 8.787375 | 24.49 | 16.39 | 0.00848583 | 11.07 | 11.07 | 0.00848583 | 27.30 | 0.00700699 | 16.11 | 10.8804 | 24.00 | 0.00874635 | 46.3348 | 74612.42 | 0.00 | 149991.11 | 117116.98 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 51397.055 | 51397.055 | 2.636212 | 0.00044964 | 845.227 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51397.06 | 51397.06 | 2.636212 | -3.48 | -3.48 | 0.00509713 | 12.89 | 11.49 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 36.2679 | 16.75 | 0.00798563 | 66.2835 | 9742.55 | 0.00 | 47759.43 | 47759.43 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 21148.559 | 21148.559 | 1.034026 | 0.00018502 | 477.636 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 3.3151 | 3.381786 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21148.56 | 21148.56 | 1.0000 | 1.22577487 | 1.034026 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.18499795 | 60.00 | 32.22 | 27.78 | 0.000 | 21148.56 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 11010.18 | 0.00 | 21248.14 | 21248.14 | 1.22577487 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.80 | 17.97 | 0.00800000 | 50394.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 38999.525 | 38999.525 | 1.661175 | 0.00034118 | 912.282 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 6.1132 | 6.236266 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38999.52 | 38999.52 | 1.0000 | 1.96922246 | 1.661175 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.34115005 | 60.00 | 32.22 | 27.78 | 0.000 | 38999.52 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 22712.12 | 0.00 | 39178.22 | 39178.22 | 1.96922246 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.31 | 18.80 | 0.00800000 | 52955.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 83388.592 | 83388.592 | 3.566471 | 0.00072952 | 1948.414 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 13.0713 | 13.334353 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 83388.59 | 82870.22 | 1.0000 | 4.22783509 | 3.566471 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.72944536 | 60.00 | 32.22 | 27.78 | 0.000 | 83388.59 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 48420.24 | 0.00 | 83770.86 | 83770.86 | 4.22783509 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52874.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36958.175 | 36958.175 | 1.583561 | 0.00032333 | 863.108 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 5.7932 | 5.909841 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36958.17 | 36795.49 | 1.0000 | 1.87721575 | 1.583561 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.32329325 | 60.00 | 32.22 | 27.78 | 0.000 | 36958.17 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.94 | 0.00798142 | 21.00 | 0.00798142 | 50.7967 | 21432.51 | 0.00 | 37127.63 | 37127.63 | 1.87721575 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24147.070 | 24147.070 | 1.034687 | 0.00021125 | 563.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 3.7851 | 3.861266 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24147.07 | 24041.91 | 1.0000 | 1.22655904 | 1.034687 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.21122755 | 60.00 | 32.22 | 27.78 | 0.000 | 24147.07 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.94 | 0.00798103 | 21.00 | 0.00798103 | 50.7942 | 14002.73 | 0.00 | 24257.79 | 24257.79 | 1.22655904 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52836.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36733.838 | 36733.838 | 1.573934 | 0.00032136 | 857.871 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 5.7581 | 5.873968 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36733.84 | 36571.80 | 1.0000 | 1.86580336 | 1.573934 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.32133085 | 60.00 | 32.22 | 27.78 | 0.000 | 36733.84 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.94 | 0.00798131 | 21.00 | 0.00798131 | 50.7960 | 21302.56 | 0.00 | 36902.27 | 36902.27 | 1.86580336 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24008.036 | 24008.036 | 1.028721 | 0.00021003 | 560.669 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 3.7633 | 3.839034 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24008.04 | 23903.27 | 1.0000 | 1.21948634 | 1.028721 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.21001135 | 60.00 | 32.22 | 27.78 | 0.000 | 24008.04 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.94 | 0.00798092 | 21.00 | 0.00798092 | 50.7936 | 13922.19 | 0.00 | 24118.12 | 24118.12 | 1.21948634 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52837.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30268.131 | 30268.131 | 1.296560 | 0.00026480 | 706.924 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 4.7446 | 4.840062 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30268.13 | 30126.76 | 1.0000 | 1.53699340 | 1.296560 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.26477180 | 60.00 | 32.22 | 27.78 | 0.000 | 30268.13 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798804 | 21.00 | 0.00798804 | 50.8381 | 17556.07 | 0.00 | 30406.91 | 30406.91 | 1.53699340 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.2 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19936.587 | 19936.587 | 0.854062 | 0.00017441 | 465.618 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 3.1251 | 3.187984 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19936.59 | 19844.91 | 1.0000 | 1.01243832 | 0.854062 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.17439617 | 60.00 | 32.22 | 27.78 | 0.000 | 19936.59 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798789 | 21.00 | 0.00798789 | 50.8372 | 11562.98 | 0.00 | 20028.00 | 20028.00 | 1.01243832 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52841.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30080.262 | 30080.262 | 1.288497 | 0.00026316 | 702.539 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 4.7151 | 4.810020 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30080.26 | 29939.41 | 1.0000 | 1.52743522 | 1.288497 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.26312841 | 60.00 | 32.22 | 27.78 | 0.000 | 30080.26 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798797 | 21.00 | 0.00798797 | 50.8377 | 17447.25 | 0.00 | 30218.18 | 30218.18 | 1.52743522 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19813.327 | 19813.327 | 0.848772 | 0.00017334 | 462.740 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 3.1058 | 3.168274 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19813.33 | 19721.99 | 1.0000 | 1.00616746 | 0.848772 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.17331795 | 60.00 | 32.22 | 27.78 | 0.000 | 19813.33 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798782 | 21.00 | 0.00798782 | 50.8367 | 11491.59 | 0.00 | 19904.17 | 19904.17 | 1.00616746 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 28182.180 | 28182.180 | 1.206978 | 0.00024655 | 658.241 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 4.4176 | 4.506505 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28182.18 | 28045.23 | 1.0000 | 1.43079893 | 1.206978 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.24652486 | 60.00 | 32.22 | 27.78 | 0.000 | 28182.18 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797982 | 21.00 | 0.00797982 | 50.7866 | 16348.65 | 0.00 | 28311.39 | 28311.39 | 1.43079893 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52846.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18586.531 | 18586.531 | 0.796084 | 0.00016260 | 434.109 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 2.9135 | 2.972102 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18586.53 | 18586.53 | 1.0000 | 0.94370945 | 0.796084 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.16258650 | 60.00 | 32.22 | 27.78 | 0.000 | 18586.53 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797960 | 21.00 | 0.00797960 | 50.7852 | 10781.52 | 0.00 | 18671.75 | 18671.75 | 0.94370945 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52845.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27958.267 | 27958.267 | 1.197368 | 0.00024459 | 653.014 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 4.3825 | 4.470700 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27958.27 | 27958.27 | 1.0000 | 1.41940689 | 1.197368 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.24456616 | 60.00 | 32.22 | 27.78 | 0.000 | 27958.27 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797966 | 21.00 | 0.00797966 | 50.7856 | 16218.96 | 0.00 | 28086.45 | 28086.45 | 1.41940689 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52847.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18455.984 | 18455.984 | 0.790481 | 0.00016146 | 431.061 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 2.8930 | 2.951226 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18455.98 | 18455.98 | 1.0000 | 0.93706778 | 0.790481 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 32.11 | 18.56 | 0.00800000 | 52751.6 | 0.16144453 | 60.00 | 32.22 | 27.78 | 0.000 | 18455.98 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797945 | 21.00 | 0.00797945 | 50.7843 | 10705.91 | 0.00 | 18540.60 | 18540.60 | 0.93706778 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52845.6 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 99193.237 | 79419.587 | 5.992263 | -999.0 | -999.000 | -999.0000 | 1.05694 | 1.00000 | 1020.6253 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.992263 | 7.10346456 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 100758.49 | 100758.49 | 1.0158 | 7.10346456 | 5.992263 | 24.54 | 16.41 | 0.00849152 | 46284.9 | 11.06 | 11.06 | 0.00849152 | 32525.6 | -999.0 | -999.00 | -999.00 | -999.00 | 13254.649 | 87503.85 | 27.40 | 0.00700714 | 16.15 | 0.95610000 | 15.9556 | 24.00 | 0.00877353 | 24.00 | 0.00877353 | 46.4771 | 69998.29 | 0.00 | 102281.54 | 79864.10 | 6.82293141 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 57426.833 | 57426.833 | 1.797679 | 0.00050239 | 894.852 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.992263 | 7.10346456 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 9.0017 | 9.182907 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 57426.83 | 57426.83 | 1.0000 | 2.13103937 | 1.797679 | -13.93 | -13.93 | 0.00376429 | -4679.2 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 0.50234374 | 60.00 | 32.22 | 27.78 | 0.000 | 57426.83 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 53.1852 | 17.85 | 0.00796755 | 18.48 | 0.00798225 | 59.3948 | 9523.04 | 0.00 | 47530.97 | 47530.97 | 2.13103937 | 2.80 | 1.62 | 0.00376429 | 12247.4 | 24.84 | 12.30 | 0.00376429 | 34551.5 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 94396.148 | 75578.773 | 5.702471 | -999.0 | -999.000 | -999.0000 | 1.05485 | 1.00000 | 1020.6084 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.702471 | 6.75993357 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 95885.71 | 95885.71 | 1.0158 | 6.75993357 | 5.702471 | 24.57 | 16.41 | 0.00848240 | 46290.1 | 11.06 | 11.06 | 0.00848240 | 32502.6 | -999.0 | -999.00 | -999.00 | -999.00 | 12613.640 | 83272.07 | 27.40 | 0.00700714 | 16.15 | 0.95610000 | 16.7664 | 24.00 | 0.00877995 | 24.00 | 0.00877995 | 46.5105 | 66584.28 | 0.00 | 97335.10 | 76001.79 | 6.49296730 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 57877.669 | 57877.669 | 1.710741 | 0.00050634 | 893.281 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.702471 | 6.75993357 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 9.0724 | 9.254998 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 57877.67 | 57877.67 | 1.0000 | 2.02798007 | 1.710741 | -15.51 | -15.51 | 0.00354009 | -6836.3 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 0.50628745 | 60.00 | 32.22 | 27.78 | 0.000 | 57877.67 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 55.8880 | 17.92 | 0.00794353 | 17.72 | 0.00797173 | 62.2224 | 9032.07 | 0.00 | 47190.77 | 47190.77 | 2.02798007 | 2.80 | 1.30 | 0.00354009 | 11685.5 | 25.81 | 12.46 | 0.00354009 | 34955.4 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 145462.257 | 116465.121 | 8.787375 | -999.0 | -999.000 | -999.0000 | 1.06212 | 1.00000 | 1020.6147 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 8.787375 | 10.41689957 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 147835.47 | 147835.47 | 1.0163 | 10.41689957 | 8.787375 | 24.49 | 16.39 | 0.00848583 | 46220.6 | 11.07 | 11.07 | 0.00848583 | 32523.2 | -999.0 | -999.00 | -999.00 | -999.00 | 19312.726 | 128522.74 | 27.30 | 0.00700699 | 16.11 | 0.95610000 | 10.8804 | 24.00 | 0.00874635 | 24.00 | 0.00874635 | 46.3348 | 74612.42 | 0.00 | 149991.11 | 117116.98 | 10.00551079 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 51397.055 | 51397.055 | 2.636212 | 0.00044964 | 845.227 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 8.787375 | 10.41689957 | 4197.9300 | 999.8980 | 5.47042191 | 54.44 | 82.22 | 27.78 | 637952.37 | 8.0566 | 8.218708 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 51397.06 | 51397.06 | 1.0000 | 3.12506987 | 2.636212 | -3.48 | -3.48 | 0.00509713 | 9219.5 | 12.89 | 11.49 | 0.00800000 | 33150.5 | 0.44959799 | 60.00 | 32.22 | 27.78 | 0.000 | 51397.06 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 36.2679 | 18.39 | 0.00796104 | 16.75 | 0.00798563 | 66.2835 | 9742.55 | 0.00 | 47759.43 | 47759.43 | 3.12506987 | 2.80 | 2.80 | 0.00509713 | 15587.7 | 17.87 | 10.74 | 0.00509713 | 30870.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | FixedDryBulb | 0.00 | 5.99 | - | |||
PACU_VAV_MID_OA_CONTROLLER | FixedDryBulb | 0.00 | 5.70 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | FixedDryBulb | 0.00 | 8.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1930.83 | 3671.17 | 840.33 |
CORE_MID | 2538.00 | 4396.17 | 1986.67 |
CORE_TOP | 3223.67 | 4900.17 | 2876.83 |
PERIMETER_TOP_ZN_3 | 3636.50 | 5384.50 | 3419.67 |
PERIMETER_TOP_ZN_2 | 3882.67 | 4841.33 | 3176.83 |
PERIMETER_TOP_ZN_1 | 3784.33 | 4772.83 | 3044.67 |
PERIMETER_TOP_ZN_4 | 3811.50 | 5102.67 | 3321.83 |
PERIMETER_BOT_ZN_3 | 3470.50 | 5594.50 | 3383.83 |
PERIMETER_BOT_ZN_2 | 3779.17 | 4739.17 | 3079.00 |
PERIMETER_BOT_ZN_1 | 3570.50 | 4939.17 | 2985.33 |
PERIMETER_BOT_ZN_4 | 3594.17 | 5176.83 | 3202.00 |
PERIMETER_MID_ZN_3 | 3576.17 | 5002.50 | 3145.00 |
PERIMETER_MID_ZN_2 | 3188.33 | 3950.33 | 2533.17 |
PERIMETER_MID_ZN_1 | 3589.33 | 4538.83 | 2724.50 |
PERIMETER_MID_ZN_4 | 3654.17 | 4917.67 | 3055.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5198.17 | 5655.33 | 3577.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 3.00 | 0.00 | 3.00 | 0.00 |
CORE_MID | 15.67 | 0.00 | 14.83 | 0.00 |
CORE_TOP | 24.17 | 0.00 | 16.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 300.67 | 0.00 | 97.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 302.50 | 1.00 | 91.67 | 1.00 |
PERIMETER_TOP_ZN_1 | 262.50 | 2.67 | 74.83 | 2.67 |
PERIMETER_TOP_ZN_4 | 307.17 | 1.00 | 96.83 | 0.33 |
PERIMETER_BOT_ZN_3 | 164.50 | 0.00 | 70.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 166.83 | 0.33 | 69.17 | 0.33 |
PERIMETER_BOT_ZN_1 | 1127.33 | 1.67 | 1024.00 | 1.67 |
PERIMETER_BOT_ZN_4 | 172.17 | 0.00 | 75.00 | 0.00 |
PERIMETER_MID_ZN_3 | 152.17 | 0.00 | 62.67 | 0.00 |
PERIMETER_MID_ZN_2 | 147.83 | 3.50 | 51.50 | 3.00 |
PERIMETER_MID_ZN_1 | 114.33 | 3.50 | 39.83 | 3.50 |
PERIMETER_MID_ZN_4 | 149.17 | 1.33 | 53.50 | 0.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1432.83 | 12.67 | 1107.83 | 11.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.867 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.641 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.648 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 1.253 | 0.053 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.465 | 0.056 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 1.447 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.356 | 0.056 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 1.086 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 1.270 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 1.259 | 0.872 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 1.157 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 1.099 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 1.437 | 0.050 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 1.528 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.409 | 0.047 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.86 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13796596.55 | 0.00 | 13796596.55 | 0.00 | 13796596.55 | 13393058.27 | 6574.23 | 28.50 | 2157.27 | 512.66 |
CORE_MID | 10235214.77 | 0.00 | 10235214.77 | 0.00 | 10235214.77 | 13393058.27 | 6847.99 | 26.03 | 1885.99 | 475.06 |
CORE_TOP | 10264797.62 | 0.00 | 10264797.62 | 0.00 | 10264797.62 | 13393058.27 | 6766.98 | 16.05 | 1976.97 | 64.18 |
PERIMETER_TOP_ZN_3 | 4203711.15 | 0.00 | 4203711.15 | 370406.43 | 4574117.57 | 2823374.22 | 4217.00 | 6.42 | 4536.58 | 64.18 |
PERIMETER_TOP_ZN_2 | 3101372.17 | 0.00 | 3101372.17 | 246936.13 | 3348308.30 | 1787429.43 | 4209.91 | 0.89 | 4549.19 | 64.18 |
PERIMETER_TOP_ZN_1 | 4836546.52 | 0.00 | 4836546.52 | 370406.43 | 5206952.95 | 2823374.22 | 4211.73 | 0.74 | 4547.53 | 64.18 |
PERIMETER_TOP_ZN_4 | 2874919.78 | 0.00 | 2874919.78 | 246936.13 | 3121855.91 | 1787312.18 | 4211.20 | 1.27 | 4547.52 | 64.18 |
PERIMETER_BOT_ZN_3 | 3689576.32 | 0.00 | 3689576.32 | 196941.88 | 3886518.20 | 2823374.22 | 4262.31 | 3.48 | 4494.21 | 512.66 |
PERIMETER_BOT_ZN_2 | 2718023.70 | 0.00 | 2718023.70 | 131293.80 | 2849317.50 | 1787429.43 | 4208.97 | 6.10 | 4544.92 | 512.66 |
PERIMETER_BOT_ZN_1 | 4270735.80 | 0.00 | 4270735.80 | 3034889.02 | 7305624.83 | 2823374.22 | 4183.54 | 4.84 | 4571.62 | 512.66 |
PERIMETER_BOT_ZN_4 | 2483876.81 | 0.00 | 2483876.81 | 131293.80 | 2615170.61 | 1787312.18 | 4209.63 | 4.65 | 4545.73 | 512.66 |
PERIMETER_MID_ZN_3 | 3718335.49 | 0.00 | 3718335.49 | 308333.93 | 4026669.42 | 2823374.22 | 4180.31 | 4.67 | 4575.02 | 475.06 |
PERIMETER_MID_ZN_2 | 2985670.51 | 0.00 | 2985670.51 | 205554.72 | 3191225.23 | 1601953.02 | 4147.79 | 2.52 | 4609.68 | 1384.06 |
PERIMETER_MID_ZN_1 | 5150525.64 | 0.00 | 5150525.64 | 308333.93 | 5458859.56 | 2823374.22 | 4152.44 | 0.69 | 4606.87 | 475.06 |
PERIMETER_MID_ZN_4 | 3016235.05 | 0.00 | 3016235.05 | 205554.72 | 3221789.77 | 1787312.18 | 4150.20 | 3.34 | 4606.46 | 475.06 |
Total Facility | 77346137.88 | 0.00 | 77346137.88 | 5756880.91 | 83103018.80 | 67658168.57 | 6932.33 | 97.87 | 4663.52 | 1590.82 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6353 | 0.0000 | 0.6353 | 0.0000 | 0.6353 | 0.4247 | 3765.67 | 28.50 | 2148.83 |
CORE_MID | 0.4705 | 0.0000 | 0.4705 | 0.0000 | 0.4705 | 0.4247 | 4057.84 | 26.03 | 1859.13 |
CORE_TOP | 0.4757 | 0.0000 | 0.4757 | 0.0000 | 0.4757 | 0.4247 | 3971.09 | 16.05 | 1955.86 |
PERIMETER_TOP_ZN_3 | 0.1947 | 0.0000 | 0.1947 | 0.0083 | 0.2030 | 0.0895 | 1421.12 | 6.42 | 4515.46 |
PERIMETER_TOP_ZN_2 | 0.1438 | 0.0000 | 0.1438 | 0.0056 | 0.1493 | 0.0567 | 1414.03 | 0.89 | 4528.08 |
PERIMETER_TOP_ZN_1 | 0.2243 | 0.0000 | 0.2243 | 0.0083 | 0.2326 | 0.0895 | 1415.85 | 0.74 | 4526.41 |
PERIMETER_TOP_ZN_4 | 0.1332 | 0.0000 | 0.1332 | 0.0056 | 0.1387 | 0.0567 | 1415.32 | 1.27 | 4526.41 |
PERIMETER_BOT_ZN_3 | 0.1688 | 0.0000 | 0.1688 | 0.0044 | 0.1732 | 0.0895 | 1457.83 | 2.86 | 4482.31 |
PERIMETER_BOT_ZN_2 | 0.1246 | 0.0000 | 0.1246 | 0.0030 | 0.1276 | 0.0567 | 1405.77 | 5.41 | 4531.83 |
PERIMETER_BOT_ZN_1 | 0.1960 | 0.0000 | 0.1960 | 0.1371 | 0.3330 | 0.0895 | 1378.99 | 3.98 | 4560.02 |
PERIMETER_BOT_ZN_4 | 0.1137 | 0.0000 | 0.1137 | 0.0030 | 0.1166 | 0.0567 | 1406.07 | 4.12 | 4532.80 |
PERIMETER_MID_ZN_3 | 0.1704 | 0.0000 | 0.1704 | 0.0069 | 0.1774 | 0.0895 | 1390.56 | 4.67 | 4547.78 |
PERIMETER_MID_ZN_2 | 0.1410 | 0.0000 | 0.1410 | 0.0050 | 0.1460 | 0.0567 | 1358.53 | 2.37 | 3673.10 |
PERIMETER_MID_ZN_1 | 0.2367 | 0.0000 | 0.2367 | 0.0069 | 0.2436 | 0.0895 | 1362.78 | 0.65 | 4579.57 |
PERIMETER_MID_ZN_4 | 0.1383 | 0.0000 | 0.1383 | 0.0046 | 0.1429 | 0.0567 | 1360.87 | 3.25 | 4578.88 |
Total Facility | 3.5670 | 0.0000 | 3.5670 | 0.1986 | 3.7656 | 2.1513 | 4119.52 | 95.88 | 4623.89 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 37884306.56 | 0.00 | 37884306.56 | 22614548.33 | 4195.32 | 3.18 | 4561.50 | 512.66 |
PACU_VAV_MID | 35280590.17 | 0.00 | 35280590.17 | 22429071.92 | 4158.96 | 0.86 | 4600.18 | 475.06 |
PACU_VAV_TOP | 35527025.78 | 0.00 | 35527025.78 | 22614548.33 | 4212.61 | 0.63 | 4546.76 | 63.89 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.7402 | 0.0000 | 1.7402 | 0.7171 | 1391.79 | 2.44 | 4548.76 |
PACU_VAV_MID | 1.6201 | 0.0000 | 1.6201 | 0.7084 | 1368.95 | 0.84 | 4573.21 |
PACU_VAV_TOP | 1.6464 | 0.0000 | 1.6464 | 0.7171 | 1416.73 | 0.63 | 4525.64 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 11.63 | 3172.63 | 0.00 | 0.00 | 0.00 | 2171.26 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 33.74 | 2918.92 | 0.00 | 0.00 | 0.00 | 2389.19 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 16.54 | 2421.79 | 0.00 | 0.00 | 0.00 | 2329.25 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2867 | 2.9486 | 0.0000 | 0.0000 | 0.0000 | 1.1459 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2504 | 2.7527 | 0.0000 | 0.0000 | 0.0000 | 1.1980 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2027 | 3.0113 | 0.0000 | 0.0000 | 0.0000 | 1.1454 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1870.53 | 15934.24 | 18-MAR-18:10 | 170582.04 | 21-JUL-15:10 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 263.85 | 385.65 | 01-JAN-19:20 | 74233.81 | 30-JUN-14:30 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 06-JAN-17:20 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 06-JAN-17:20 |
ElectricityPurchased:Facility | 1870.53 | 15934.24 | 18-MAR-18:10 | 170582.04 | 21-JUL-15:10 |
ElectricityPurchased:Plant | 1870.53 | 15934.24 | 18-MAR-18:10 | 170582.04 | 21-JUL-15:10 |
Cogeneration:ElectricityPurchased | 1870.53 | 15934.24 | 18-MAR-18:10 | 170582.04 | 21-JUL-15:10 |
General:Cogeneration:ElectricityPurchased | 1870.53 | 15934.24 | 18-MAR-18:10 | 170582.04 | 21-JUL-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1870.53 | 15934.24 | 18-MAR-18:10 | 170582.04 | 21-JUL-15:10 |
ElectricityNet:Plant | 1870.53 | 15934.24 | 18-MAR-18:10 | 170582.04 | 21-JUL-15:10 |
Cogeneration:ElectricityNet | 1870.53 | 15934.24 | 18-MAR-18:10 | 170582.04 | 21-JUL-15:10 |
General:Cogeneration:ElectricityNet | 1870.53 | 15934.24 | 18-MAR-18:10 | 170582.04 | 21-JUL-15:10 |
Fans:Electricity | 180.13 | 0.00 | 01-JAN-00:40 | 25854.01 | 12-JUL-15:20 |
General:Fans:Electricity | 180.13 | 0.00 | 01-JAN-00:40 | 25854.01 | 12-JUL-15:20 |
ExteriorLights:Electricity | 234.07 | 0.00 | 01-JAN-11:20 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 234.07 | 0.00 | 01-JAN-11:20 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 56.22 | 0.00 | 01-JAN-00:10 | 49039.73 | 30-JUN-14:40 |
General:Cooling:Electricity | 56.22 | 0.00 | 01-JAN-00:10 | 49039.73 | 30-JUN-14:40 |
Electricity:Plant | 77.08 | 0.00 | 01-JAN-00:40 | 9129.19 | 12-JAN-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 68.07 | 0.00 | 01-JAN-00:10 | 7771.48 | 21-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 68.07 | 0.00 | 01-JAN-00:10 | 7771.48 | 21-FEB-12:40 |
Pumps:Electricity | 9.01 | 0.00 | 01-JAN-00:40 | 1645.14 | 27-FEB-07:30 |
General:Pumps:Electricity | 9.01 | 0.00 | 01-JAN-00:40 | 1645.14 | 27-FEB-07:30 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1803.77 | 0.00 | 01-JAN-00:40 | 437022.92 | 27-FEB-07:20 |
NaturalGas:Plant | 1803.77 | 0.00 | 01-JAN-00:40 | 437022.92 | 27-FEB-07:20 |
Heating:NaturalGas | 1803.77 | 0.00 | 01-JAN-00:40 | 437022.92 | 27-FEB-07:20 |
Boiler:Heating:NaturalGas | 1803.77 | 0.00 | 01-JAN-00:40 | 437022.92 | 27-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4247.82 | 0.00 | 01-JAN-00:40 | 844548.67 | 27-FEB-07:20 |
EnergyTransfer:Building | 1490.36 | 0.00 | 01-JAN-00:40 | 209404.71 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 218.52 | 0.00 | 01-JAN-00:40 | 26033.31 | 12-JUL-16:00 |
Heating:EnergyTransfer | 626.46 | 0.00 | 01-JAN-00:40 | 209404.71 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:20 | 10748.16 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 626.46 | 0.00 | 01-JAN-00:40 | 209404.71 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.54 | 0.00 | 01-JAN-00:20 | 10748.16 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 863.90 | 0.00 | 01-JAN-00:40 | 168281.61 | 12-JUL-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 217.98 | 0.00 | 01-JAN-00:40 | 26033.31 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer | 863.90 | 0.00 | 01-JAN-00:40 | 168281.61 | 12-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 217.98 | 0.00 | 01-JAN-00:40 | 26033.31 | 12-JUL-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 129.12 | 0.00 | 01-JAN-00:40 | 25012.54 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 106.41 | 0.00 | 01-JAN-00:40 | 25012.54 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 106.41 | 0.00 | 01-JAN-00:40 | 25012.54 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 22.71 | 0.00 | 01-JAN-00:10 | 10610.43 | 21-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 22.71 | 0.00 | 01-JAN-00:10 | 10610.43 | 21-JUL-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 41.50 | 0.00 | 01-JAN-00:40 | 13303.03 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.32 | 0.00 | 01-JAN-00:40 | 13303.03 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.32 | 0.00 | 01-JAN-00:40 | 13303.03 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.18 | 0.00 | 01-JAN-00:10 | 4780.92 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.18 | 0.00 | 01-JAN-00:10 | 4780.92 | 12-JUL-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 40.67 | 0.00 | 01-JAN-00:40 | 10709.52 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.33 | 0.00 | 01-JAN-00:40 | 10709.52 | 02-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.33 | 0.00 | 01-JAN-00:40 | 10709.52 | 02-JAN-08:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.34 | 0.00 | 01-JAN-00:10 | 5133.49 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.34 | 0.00 | 01-JAN-00:10 | 5133.49 | 12-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 138.11 | 0.00 | 01-JAN-00:40 | 19686.60 | 12-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 5.90 | 0.00 | 01-JAN-00:40 | 18245.22 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 5.90 | 0.00 | 01-JAN-00:40 | 18245.22 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 132.21 | 0.00 | 01-JAN-00:20 | 19686.60 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 132.21 | 0.00 | 01-JAN-00:20 | 19686.60 | 12-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 146.65 | 0.00 | 01-JAN-00:40 | 30636.81 | 21-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 32.61 | 0.00 | 01-JAN-00:40 | 30636.81 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 32.61 | 0.00 | 01-JAN-00:40 | 30636.81 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 114.04 | 0.00 | 01-JAN-00:20 | 21236.38 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 114.04 | 0.00 | 01-JAN-00:20 | 21236.38 | 12-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 81.64 | 0.00 | 01-JAN-00:40 | 14284.67 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 53.52 | 0.00 | 01-JAN-00:40 | 14284.67 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 53.52 | 0.00 | 01-JAN-00:40 | 14284.67 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.12 | 0.00 | 01-JAN-00:10 | 6632.20 | 30-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.12 | 0.00 | 01-JAN-00:10 | 6632.20 | 30-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 58.95 | 0.00 | 01-JAN-00:40 | 9818.02 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 32.83 | 0.00 | 01-JAN-00:40 | 9336.19 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 32.83 | 0.00 | 01-JAN-00:40 | 9336.19 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.11 | 0.00 | 01-JAN-00:10 | 9818.02 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.11 | 0.00 | 01-JAN-00:10 | 9818.02 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.68 | 0.00 | 01-JAN-00:40 | 14354.85 | 10-AUG-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.49 | 0.00 | 01-JAN-00:40 | 13939.67 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.49 | 0.00 | 01-JAN-00:40 | 13939.67 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.19 | 0.00 | 01-JAN-00:10 | 14354.85 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.19 | 0.00 | 01-JAN-00:10 | 14354.85 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.39 | 0.00 | 01-JAN-00:40 | 9294.44 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 34.40 | 0.00 | 01-JAN-00:40 | 9294.44 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 34.40 | 0.00 | 01-JAN-00:40 | 9294.44 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.99 | 0.00 | 01-JAN-00:10 | 8094.25 | 21-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.99 | 0.00 | 01-JAN-00:10 | 8094.25 | 21-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.95 | 0.00 | 01-JAN-00:40 | 11458.76 | 21-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 43.04 | 0.00 | 01-JAN-00:40 | 11458.76 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 43.04 | 0.00 | 01-JAN-00:40 | 11458.76 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.92 | 0.00 | 01-JAN-00:10 | 4890.96 | 11-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.92 | 0.00 | 01-JAN-00:10 | 4890.96 | 11-JUL-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 48.40 | 0.00 | 01-JAN-00:40 | 7495.12 | 21-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.19 | 0.00 | 01-JAN-00:40 | 7495.12 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.19 | 0.00 | 01-JAN-00:40 | 7495.12 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.21 | 0.00 | 01-JAN-00:10 | 7451.79 | 11-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.21 | 0.00 | 01-JAN-00:10 | 7451.79 | 11-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 103.33 | 0.00 | 01-JAN-00:40 | 21906.22 | 12-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 74.46 | 0.00 | 01-JAN-00:40 | 21906.22 | 12-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 74.46 | 0.00 | 01-JAN-00:40 | 21906.22 | 12-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.88 | 0.00 | 01-JAN-00:10 | 11516.13 | 11-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 28.88 | 0.00 | 01-JAN-00:10 | 11516.13 | 11-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 45.75 | 0.00 | 01-JAN-00:40 | 7502.29 | 21-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.70 | 0.00 | 01-JAN-00:40 | 7502.29 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.70 | 0.00 | 01-JAN-00:40 | 7502.29 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 18.05 | 0.00 | 01-JAN-00:10 | 5973.91 | 31-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 18.05 | 0.00 | 01-JAN-00:10 | 5973.91 | 31-JUL-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 60.64 | 0.00 | 01-JAN-00:40 | 11053.97 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.07 | 0.00 | 01-JAN-00:40 | 11053.97 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.07 | 0.00 | 01-JAN-00:40 | 11053.97 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.57 | 0.00 | 01-JAN-00:10 | 6279.50 | 30-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.57 | 0.00 | 01-JAN-00:10 | 6279.50 | 30-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 46.77 | 0.00 | 01-JAN-00:40 | 9999.51 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 20.58 | 0.00 | 01-JAN-00:40 | 7462.93 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 20.58 | 0.00 | 01-JAN-00:40 | 7462.93 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 26.20 | 0.00 | 01-JAN-00:10 | 9999.51 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 26.20 | 0.00 | 01-JAN-00:10 | 9999.51 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 74.24 | 0.00 | 01-JAN-00:40 | 14288.76 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 26.54 | 0.00 | 01-JAN-00:40 | 11193.52 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 26.54 | 0.00 | 01-JAN-00:40 | 11193.52 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 47.70 | 0.00 | 01-JAN-00:10 | 14288.76 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 47.70 | 0.00 | 01-JAN-00:10 | 14288.76 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 45.05 | 0.00 | 01-JAN-00:40 | 7872.96 | 11-JUL-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 21.53 | 0.00 | 01-JAN-00:40 | 7475.43 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 21.53 | 0.00 | 01-JAN-00:40 | 7475.43 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.51 | 0.00 | 01-JAN-00:10 | 7872.96 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.51 | 0.00 | 01-JAN-00:10 | 7872.96 | 11-JUL-17:40 |
PlantLoopHeatingDemand:Facility | 1299.08 | 0.00 | 01-JAN-00:40 | 327499.08 | 27-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:10 |
EnergyTransfer:HVAC | 1467.83 | 0.00 | 01-JAN-00:40 | 324943.66 | 27-FEB-07:20 |
HeatingCoils:EnergyTransfer | 1233.91 | 0.00 | 01-JAN-00:40 | 324943.66 | 27-FEB-07:20 |
PlantLoopHeatingDemand:HVAC | 1233.91 | 0.00 | 01-JAN-00:40 | 324943.66 | 27-FEB-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 1233.91 | 0.00 | 01-JAN-00:40 | 324943.66 | 27-FEB-07:20 |
CoolingCoils:EnergyTransfer | 233.92 | 0.00 | 01-JAN-00:10 | 201259.14 | 30-JUN-12:30 |
EnergyTransfer:Plant | 1289.64 | 0.00 | 01-JAN-00:40 | 326014.82 | 27-FEB-07:20 |
WaterSystems:EnergyTransfer | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:10 |
Boilers:EnergyTransfer | 1224.46 | 0.00 | 01-JAN-00:40 | 323459.40 | 27-FEB-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.535 | -217.980 | 0.000 | 0.000 | 34.357 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -188.698 |
CORE_MID | 0.000 | 0.000 | 5.904 | -132.207 | 0.000 | 0.000 | 35.589 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -136.497 |
CORE_TOP | 0.000 | 0.000 | 32.611 | -114.036 | 0.000 | 0.000 | 36.672 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -182.459 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 53.523 | -28.117 | 0.000 | 0.000 | 7.972 | 23.566 | 24.333 | 10.965 | 0.000 | 0.007 | 0.001 | 0.000 | -75.303 | 0.000 | -8.123 | -8.822 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 32.832 | -26.114 | 0.000 | 0.000 | 4.948 | 14.919 | 15.404 | 28.418 | 0.000 | 0.004 | 0.001 | 0.000 | -47.387 | 0.000 | -5.486 | -17.537 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 44.492 | -44.187 | 0.000 | 0.000 | 7.796 | 23.566 | 24.332 | 56.478 | 0.000 | 0.005 | 0.001 | 0.000 | -67.811 | 0.000 | -8.347 | -36.323 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 34.401 | -21.990 | 0.000 | 0.000 | 5.029 | 14.918 | 15.403 | 19.794 | 0.000 | 0.003 | 0.001 | 0.000 | -49.153 | 0.000 | -5.510 | -12.896 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 43.036 | -22.917 | 0.000 | 0.000 | 7.983 | 23.566 | 24.333 | 11.457 | 0.000 | 0.004 | 0.000 | 0.000 | -75.698 | 0.000 | -4.390 | -7.372 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 26.190 | -22.212 | 0.000 | 0.000 | 4.928 | 14.919 | 15.404 | 28.640 | 0.000 | 0.002 | 0.000 | 0.000 | -47.987 | 0.000 | -3.008 | -16.875 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 74.457 | -28.877 | 0.000 | 0.000 | 8.134 | 23.566 | 24.332 | 57.457 | 0.000 | 0.082 | 0.002 | 0.000 | -67.665 | 0.000 | -72.702 | -18.784 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 27.704 | -18.047 | 0.000 | 0.000 | 5.015 | 14.918 | 15.403 | 20.154 | 0.000 | 0.002 | 0.000 | 0.000 | -49.701 | 0.000 | -2.999 | -12.450 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 33.070 | -27.573 | 0.000 | 0.000 | 7.837 | 23.566 | 24.333 | 10.438 | 0.000 | 0.005 | 12.971 | 0.000 | -77.620 | 0.000 | -7.026 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 20.575 | -26.196 | 0.000 | 0.000 | 3.618 | 14.919 | 15.404 | 27.994 | 0.000 | 0.003 | 0.001 | 0.000 | -48.763 | 0.000 | -4.738 | -2.815 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 26.538 | -47.698 | 0.000 | 0.000 | 7.711 | 23.566 | 24.332 | 56.045 | 0.000 | 0.004 | 0.002 | 0.000 | -70.096 | 0.000 | -7.212 | -13.190 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 21.535 | -23.512 | 0.000 | 0.000 | 4.980 | 14.918 | 15.403 | 19.606 | 0.000 | 0.003 | 2.482 | 0.000 | -50.668 | 0.000 | -4.748 | -0.000 |
TOPFLOOR_PLENUM | 106.411 | -22.710 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -12.331 | -71.373 |
MIDFLOOR_PLENUM | 26.320 | -15.182 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.004 | 1.006 | 0.000 | 0.000 | 0.000 | -12.147 | -0.002 |
FIRSTFLOOR_PLENUM | 16.330 | -24.339 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 17.730 | 0.000 | 0.000 | 0.000 | -9.724 | -0.000 |
Total Facility | 149.060 | -62.231 | 477.402 | -801.664 | 0.000 | 0.000 | 182.569 | 566.263 | 729.266 | 347.444 | 0.000 | 0.136 | 34.197 | 0.000 | -727.851 | 0.000 | -168.491 | -726.095 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 17-JUL-05:12 | 0.00 | 0.00 | 0.00 | -49313.61 | 0.00 | 0.00 | 328.43 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 40166.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 22-JUN-05:12 | 0.00 | 0.00 | 0.00 | -32036.49 | 0.00 | 0.00 | 337.85 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 27588.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUL-16:00 | 0.00 | 0.00 | 0.00 | -21237.64 | 0.00 | 0.00 | 3497.08 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 1171.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 | -6632.06 | 0.00 | 0.00 | 737.22 | 2057.62 | 1435.25 | 3321.46 | 0.00 | 48.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -968.16 |
PERIMETER_TOP_ZN_2 | 14-MAY-09:42 | 0.00 | 0.00 | 0.00 | -12417.08 | 0.00 | 0.00 | 16.70 | 72.37 | 302.86 | 9476.24 | 0.00 | 0.00 | 2767.64 | 0.00 | -0.00 | 0.00 | -218.72 | 0.00 |
PERIMETER_TOP_ZN_1 | 23-JUL-13:22 | 0.00 | 0.00 | 0.00 | -21441.24 | 0.00 | 0.00 | 21.46 | 114.31 | 478.41 | 16271.80 | 0.00 | 0.00 | 4593.99 | 0.00 | -0.00 | 0.00 | -38.75 | 0.00 |
PERIMETER_TOP_ZN_4 | 10-JUN-17:07 | 0.00 | 0.00 | 0.00 | -8928.18 | 0.00 | 0.00 | 21.61 | 72.36 | 302.86 | 10426.01 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -81.27 | -1813.39 |
PERIMETER_BOT_ZN_3 | 13-JUN-05:12 | 0.00 | 0.00 | 0.00 | -5174.52 | 0.00 | 0.00 | 78.14 | 228.62 | 637.89 | 6426.93 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -28.41 | -2168.64 |
PERIMETER_BOT_ZN_2 | 21-JUL-06:03 | 0.00 | 0.00 | 0.00 | -9064.93 | 0.00 | 0.00 | 91.47 | 434.22 | 403.81 | 10550.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -21.09 | -2393.97 |
PERIMETER_BOT_ZN_1 | 27-AUG-13:42 | 0.00 | 0.00 | 0.00 | -17186.75 | 0.00 | 0.00 | 26.80 | 114.31 | 478.41 | 15044.15 | 0.00 | 0.00 | 1614.00 | 0.00 | -0.00 | 0.00 | -90.92 | 0.00 |
PERIMETER_BOT_ZN_4 | 31-JUL-18:30 | 0.00 | 0.00 | 0.00 | -5973.87 | 0.00 | 0.00 | 49.12 | 434.19 | 403.81 | 10009.44 | 0.00 | 0.60 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4923.29 |
PERIMETER_MID_ZN_3 | 22-JUN-05:12 | 0.00 | 0.00 | 0.00 | -9962.08 | 0.00 | 0.00 | 73.62 | 228.62 | 637.89 | 4684.12 | 0.00 | 0.00 | 4373.57 | 0.00 | -0.00 | 0.00 | -35.75 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-09:42 | 0.00 | 0.00 | 0.00 | -12258.94 | 0.00 | 0.00 | 14.37 | 72.37 | 302.86 | 10344.21 | 0.00 | 0.00 | 1588.96 | 0.00 | -0.00 | 0.00 | -63.82 | 0.00 |
PERIMETER_MID_ZN_1 | 27-AUG-13:32 | 0.00 | 0.00 | 0.00 | -24832.48 | 0.00 | 0.00 | 23.94 | 114.31 | 478.41 | 15322.28 | 0.00 | 0.00 | 9036.32 | 0.00 | -0.00 | 0.00 | -142.79 | 0.00 |
PERIMETER_MID_ZN_4 | 10-JUN-17:07 | 0.00 | 0.00 | 0.00 | -9515.86 | 0.00 | 0.00 | 21.29 | 72.36 | 302.86 | 10435.62 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -67.51 | -1248.76 |
TOPFLOOR_PLENUM | 21-JUL-14:30 | 0.00 | -10610.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 | 10602.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-05:01 | 0.00 | -6920.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7155.46 | 0.00 | -0.00 | 0.00 | -234.70 | 0.00 |
FIRSTFLOOR_PLENUM | 31-MAR-04:01 | 0.00 | -8157.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9398.13 | 0.00 | -0.00 | 0.00 | -1240.82 | 0.00 |
Total Facility | 12-JUL-15:20 | 0.00 | -19490.52 | 0.00 | -148804.34 | 0.00 | 0.00 | 17714.68 | 49443.18 | 41937.01 | 66465.44 | 0.00 | 114.49 | 0.00 | 0.00 | 0.00 | 0.00 | -27.02 | -7352.92 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 13771.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20821.78 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 21907.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25433.86 |
CORE_TOP | 01-JAN-05:22 | 0.00 | 0.00 | 36481.95 | 0.00 | 0.00 | 0.00 | 0.00 | 542.26 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -38855.75 |
PERIMETER_TOP_ZN_3 | 28-JAN-22:02 | 0.00 | 0.00 | 17718.34 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5253.33 | 0.00 | -2955.07 | -10010.36 |
PERIMETER_TOP_ZN_2 | 28-JAN-22:02 | 0.00 | 0.00 | 11632.20 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3496.63 | 0.00 | -1965.27 | -6487.09 |
PERIMETER_TOP_ZN_1 | 26-FEB-08:12 | 0.00 | 0.00 | 17517.30 | 0.00 | 0.00 | 0.00 | 60.59 | 114.31 | 478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5038.31 | 0.00 | -1308.11 | -11824.20 |
PERIMETER_TOP_ZN_4 | 26-FEB-08:12 | 0.00 | 0.00 | 11542.45 | 0.00 | 0.00 | 0.00 | 38.51 | 72.36 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3466.96 | 0.00 | -868.73 | -7620.49 |
PERIMETER_BOT_ZN_3 | 27-FEB-03:52 | 0.00 | 0.00 | 14193.52 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5890.93 | 0.00 | 0.00 | -8931.70 |
PERIMETER_BOT_ZN_2 | 27-FEB-03:52 | 0.00 | 0.00 | 9364.04 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3923.93 | 0.00 | 0.00 | -5838.38 |
PERIMETER_BOT_ZN_1 | 12-JAN-07:10 | 0.00 | 0.00 | 22185.39 | 0.00 | 0.00 | 0.00 | 220.37 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 25050.62 | 0.00 | -6622.37 | 0.00 | -42157.76 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-FEB-03:52 | 0.00 | 0.00 | 9304.12 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3925.73 | 0.00 | 0.00 | -5776.65 |
PERIMETER_MID_ZN_3 | 26-FEB-08:12 | 0.00 | 0.00 | 13056.16 | 0.00 | 0.00 | 0.00 | 59.48 | 114.31 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5335.55 | 0.00 | -1103.80 | -7269.01 |
PERIMETER_MID_ZN_2 | 27-NOV-05:11 | 0.00 | 0.00 | 9567.66 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3353.38 | 0.00 | 0.00 | -6684.91 |
PERIMETER_MID_ZN_1 | 27-NOV-05:11 | 0.00 | 0.00 | 14385.35 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5047.63 | 0.00 | 0.00 | -10081.15 |
PERIMETER_MID_ZN_4 | 26-FEB-08:12 | 0.00 | 0.00 | 9549.45 | 0.00 | 0.00 | 0.00 | 37.82 | 72.36 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3547.44 | 0.00 | -734.75 | -5680.30 |
TOPFLOOR_PLENUM | 29-NOV-06:07 | 27267.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27267.93 |
MIDFLOOR_PLENUM | 02-JAN-08:23 | 13421.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -351.10 | -13070.35 |
FIRSTFLOOR_PLENUM | 02-JAN-06:09 | 11040.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -37.09 | -11003.20 |
Total Facility | 21-FEB-06:01 | 29311.13 | 0.00 | 206737.51 | 0.00 | 0.00 | 0.00 | 2659.42 | 5493.69 | 20036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48904.96 | 0.00 | -6284.72 | -209048.42 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 7.7346 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9923 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 7.3973 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7025 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 8.7874 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.3951 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.8673 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.3204 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.6987 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2192 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.3937 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.6362 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4468 | 3.4468 | 1.0340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8361 | 2.8361 | 0.8508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5665 | 3.5665 | 1.0699 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5836 | 1.5836 | 0.4751 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0347 | 1.0347 | 0.3104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5739 | 1.5739 | 0.4722 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0287 | 1.0287 | 0.3086 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2966 | 1.2966 | 0.3890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8541 | 0.8541 | 0.2562 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2885 | 1.2885 | 0.3865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8488 | 0.8488 | 0.2546 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2070 | 1.2070 | 0.3621 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9546 | 0.9546 | 0.2864 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4513 | 1.4513 | 0.4354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9484 | 0.9484 | 0.2845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 7.7346 | 5.9923 | 7.7346 | 2.3204 | 0.0000 | 1.0000 |
PACU_VAV_MID | 7.3973 | 5.7025 | 7.3973 | 2.2192 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 8.7874 | 6.3951 | 8.7874 | 2.6362 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7234 | 1.7234 | 1.0340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4181 | 1.4181 | 0.8508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7832 | 1.7832 | 1.0699 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7918 | 0.7918 | 0.4751 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5173 | 0.5173 | 0.3104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7870 | 0.7870 | 0.4722 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5144 | 0.5144 | 0.3086 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6483 | 0.6483 | 0.3890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4270 | 0.4270 | 0.2562 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6442 | 0.6442 | 0.3865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4244 | 0.4244 | 0.2546 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6035 | 0.6035 | 0.3621 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4773 | 0.4773 | 0.2864 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7256 | 0.7256 | 0.4354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4742 | 0.4742 | 0.2845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.8673 | 2.3204 | 2.3204 | 2.3204 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.6987 | 2.2192 | 2.2192 | 2.2192 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.3937 | 2.6362 | 2.6362 | 2.6362 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 1107.83 |
Number of hours cooling loads not met | 11.00 |
Number of hours not met | 1118.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1803.77 | 437022.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 56.22 | 49039.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 234.07 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 180.13 | 25854.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 9.01 | 1645.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 68.07 | 7771.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 1870.53 |
Natural Gas | 0.00 | 1803.77 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 3674.30 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 11.28 |
Fans (All) | 36.16 |
Service Water Heating | 13.66 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 375.44 |
Subtotal | 375.44 |
Natural Gas [MJ/m2] | |
Space Heating | 362.04 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 362.04 |
Subtotal | 362.04 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.41 |
Space Heating | 49.09 |
Space Cooling | 1.53 |
Fans (All) | 4.90 |
Service Water Heating | 1.85 |
Receptacle Equipment | 19.85 |
Miscellaneous | 7.36 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8685.33 | 74.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8685.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 74.67 | 0.00 | 0.00 | 0.00 |
Average | 8753.84 | 6.16 | 0.00 | 0.00 | 0.00 |
Sum | 157569.17 | 110.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128263.67 | 40.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 40.33 | 0.00 | 0.00 | 0.00 |
Average | 34141.09 | 2.24 | 0.00 | 0.00 | 0.00 |
Sum | 614539.67 | 40.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8647.33 | 112.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8647.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 112.67 | 0.00 | 0.00 | 0.00 |
Average | 8751.06 | 8.94 | 0.00 | 0.00 | 0.00 |
Sum | 157519.17 | 160.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128234.00 | 70.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128303.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 70.00 | 0.00 | 0.00 | 0.00 |
Average | 34139.39 | 3.94 | 0.00 | 0.00 | 0.00 |
Sum | 614509.00 | 71.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121070E+11 | 9771.92 | 27-JAN-17:00 | -12.2 | -12.5 | 0.160685E+10 | 2416.24 | 27-JAN-16:00 | -12.2 | -12.5 |
February | 0.123608E+11 | 10294.51 | 10-FEB-17:00 | -0.6 | -2.2 | 0.152531E+10 | 2510.70 | 10-FEB-16:00 | -0.6 | -2.2 |
March | 0.145984E+11 | 13080.39 | 23-MAR-16:00 | -1.7 | -4.1 | 0.194797E+10 | 2606.61 | 23-MAR-13:20 | -1.7 | -4.1 |
April | 0.159985E+11 | 47904.06 | 24-APR-05:01 | -3.4 | -6.0 | 0.186379E+10 | 2606.66 | 12-APR-09:20 | -3.4 | -6.0 |
May | 0.228240E+11 | 28082.53 | 15-MAY-05:13 | 7.07 | 1.92 | 0.207521E+10 | 2606.67 | 19-MAY-13:39 | 13.87 | 8.18 |
June | 0.272154E+11 | 49058.42 | 19-JUN-05:12 | 8.73 | 7.50 | 0.207386E+10 | 2606.66 | 13-JUN-13:20 | 8.73 | 7.50 |
July | 0.270043E+11 | 49326.33 | 17-JUL-05:12 | 8.30 | 8.19 | 0.192863E+10 | 2607.02 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.274184E+11 | 49301.31 | 14-AUG-05:12 | 11.10 | 10.22 | 0.216236E+10 | 2606.66 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.189872E+11 | 46191.83 | 08-SEP-05:02 | 1.60 | 0.93 | 0.191187E+10 | 2606.71 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.142511E+11 | 17364.49 | 05-OCT-16:00 | 11.10 | 5.87 | 0.190800E+10 | 2606.65 | 13-OCT-09:20 | -8.2 | -9.0 |
November | 0.122665E+11 | 10287.86 | 03-NOV-16:00 | -11.1 | -11.5 | 0.168452E+10 | 2513.64 | 03-NOV-15:00 | -11.1 | -11.5 |
December | 0.129488E+11 | 9385.98 | 21-DEC-17:00 | -16.7 | -17.3 | 0.154887E+10 | 2347.86 | 22-DEC-16:00 | -21.7 | -22.0 |
Annual Sum or Average | 0.217980E+12 | 0.222372E+11 | ||||||||
Minimum of Months | 0.121070E+11 | 9385.98 | -16.7 | -17.3 | 0.152531E+10 | 2347.86 | -21.7 | -22.0 | ||
Maximum of Months | 0.274184E+11 | 49326.33 | 11.10 | 10.22 | 0.216236E+10 | 2607.02 | 17.38 | 14.45 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 38907931.47 | 1934.94 | 22-MAR-16:20 | 5.60 | 2.33 | 0.00 | 0.00 | 01-MAR-00:10 | 5.60 | 2.33 |
April | 0.140792E+10 | 4953.88 | 21-APR-16:10 | 14.40 | 5.51 | 0.00 | 0.00 | 01-APR-00:10 | 14.40 | 5.51 |
May | 0.387710E+10 | 8899.03 | 31-MAY-14:40 | 20.73 | 10.55 | 0.00 | 0.00 | 01-MAY-00:10 | 20.73 | 10.55 |
June | 0.624156E+10 | 10473.31 | 29-JUN-14:40 | 25.93 | 16.13 | 0.00 | 0.00 | 01-JUN-00:10 | 25.93 | 16.13 |
July | 0.610937E+10 | 10610.43 | 21-JUL-14:30 | 26.95 | 14.56 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 14.56 |
August | 0.414252E+10 | 8484.27 | 10-AUG-14:40 | 22.20 | 12.05 | 0.00 | 0.00 | 01-AUG-00:10 | 22.20 | 12.05 |
September | 0.861961E+09 | 3728.64 | 07-SEP-16:10 | 16.83 | 8.75 | 0.00 | 0.00 | 01-SEP-00:10 | 16.83 | 8.75 |
October | 30874440.01 | 1557.72 | 03-OCT-16:10 | 11.60 | 6.16 | 0.00 | 0.00 | 01-OCT-00:10 | 11.60 | 6.16 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.227102E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.624156E+10 | 10610.43 | 26.95 | 16.13 | 0.00 | 0.00 | 26.95 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233176E+09 | 6224.77 | 26-JAN-05:01 | -23.9 | -24.2 | 0.00 | 0.00 | 01-JAN-00:10 | -23.9 | -24.2 |
February | 0.238887E+09 | 6673.01 | 18-FEB-05:01 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 0.162368E+09 | 6920.77 | 04-MAR-05:01 | -26.1 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.1 | -26.5 |
April | 0.633862E+09 | 4185.40 | 08-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.202593E+10 | 2915.75 | 31-MAY-16:00 | 22.20 | 10.79 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 10.79 |
June | 0.373464E+10 | 4453.52 | 30-JUN-14:30 | 27.75 | 17.00 | 0.00 | 0.00 | 01-JUN-00:10 | 27.75 | 17.00 |
July | 0.366210E+10 | 4780.92 | 12-JUL-16:00 | 25.00 | 13.76 | 0.00 | 0.00 | 01-JUL-00:10 | 25.00 | 13.76 |
August | 0.286882E+10 | 3719.97 | 11-AUG-16:00 | 25.60 | 14.77 | 0.00 | 0.00 | 01-AUG-00:10 | 25.60 | 14.77 |
September | 0.893411E+09 | 3304.21 | 30-SEP-05:01 | -4.5 | -5.0 | 0.00 | 0.00 | 01-SEP-00:10 | -4.5 | -5.0 |
October | 0.177358E+09 | 5547.60 | 27-OCT-04:01 | -17.7 | -18.2 | 0.00 | 0.00 | 01-OCT-00:10 | -17.7 | -18.2 |
November | 0.190616E+09 | 6341.85 | 09-NOV-05:01 | -25.4 | -25.6 | 0.00 | 0.00 | 01-NOV-00:10 | -25.4 | -25.6 |
December | 0.361309E+09 | 5970.57 | 01-DEC-05:01 | -21.8 | -22.1 | 0.00 | 0.00 | 01-DEC-00:10 | -21.8 | -22.1 |
Annual Sum or Average | 0.151825E+11 | 0.00 | ||||||||
Minimum of Months | 0.162368E+09 | 2915.75 | -26.1 | -26.5 | 0.00 | 0.00 | -26.1 | -26.5 | ||
Maximum of Months | 0.373464E+10 | 6920.77 | 27.75 | 17.00 | 0.00 | 0.00 | 27.75 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.665163E+09 | 7136.88 | 25-JAN-05:01 | -21.8 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.8 | -22.1 |
February | 0.636196E+09 | 8028.28 | 17-FEB-05:01 | -21.0 | -21.2 | 0.00 | 0.00 | 01-FEB-00:10 | -21.0 | -21.2 |
March | 0.723273E+09 | 8157.25 | 31-MAR-04:01 | -24.5 | -25.0 | 0.00 | 0.00 | 01-MAR-00:10 | -24.5 | -25.0 |
April | 0.147093E+10 | 6079.82 | 08-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.338645E+10 | 4170.97 | 16-MAY-06:07 | 3.30 | 1.56 | 0.00 | 0.00 | 01-MAY-00:10 | 3.30 | 1.56 |
June | 0.464696E+10 | 5319.58 | 22-JUN-06:10 | 15.28 | 11.70 | 0.00 | 0.00 | 01-JUN-00:10 | 15.28 | 11.70 |
July | 0.462724E+10 | 5539.99 | 12-JUL-06:15 | 16.13 | 10.80 | 0.00 | 0.00 | 01-JUL-00:10 | 16.13 | 10.80 |
August | 0.417499E+10 | 4901.64 | 01-AUG-06:08 | 10.10 | 9.72 | 0.00 | 0.00 | 01-AUG-00:10 | 10.10 | 9.72 |
September | 0.203314E+10 | 3916.77 | 08-SEP-05:10 | 1.60 | 0.93 | 0.00 | 0.00 | 01-SEP-00:10 | 1.60 | 0.93 |
October | 0.572431E+09 | 4945.75 | 27-OCT-04:01 | -17.7 | -18.2 | 0.00 | 0.00 | 01-OCT-00:10 | -17.7 | -18.2 |
November | 0.511049E+09 | 6518.38 | 09-NOV-05:01 | -25.4 | -25.6 | 0.00 | 0.00 | 01-NOV-00:10 | -25.4 | -25.6 |
December | 0.891154E+09 | 6240.63 | 30-DEC-05:01 | -17.1 | -17.4 | 0.00 | 0.00 | 01-DEC-00:10 | -17.1 | -17.4 |
Annual Sum or Average | 0.243390E+11 | 0.00 | ||||||||
Minimum of Months | 0.511049E+09 | 3916.77 | -25.4 | -25.6 | 0.00 | 0.00 | -25.4 | -25.6 | ||
Maximum of Months | 0.464696E+10 | 8157.25 | 16.13 | 11.70 | 0.00 | 0.00 | 16.13 | 11.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515197E+10 | 7388.17 | 12-JAN-15:05 | -36.0 | -36.1 | 0.149248E+10 | 2163.91 | 20-JAN-14:00 | -11.1 | -11.3 |
February | 0.600586E+10 | 7421.10 | 09-FEB-16:30 | -0.8 | -1.5 | 0.139877E+10 | 2332.64 | 09-FEB-14:00 | -0.8 | -1.5 |
March | 0.847222E+10 | 7993.87 | 22-MAR-16:00 | 5.60 | 2.61 | 0.175521E+10 | 2428.04 | 23-MAR-13:00 | -1.7 | -4.1 |
April | 0.101807E+11 | 13426.76 | 21-APR-16:00 | 14.40 | 5.45 | 0.173806E+10 | 2606.64 | 27-APR-13:20 | 10.77 | 4.21 |
May | 0.155262E+11 | 16723.10 | 12-MAY-16:00 | 20.00 | 9.30 | 0.204684E+10 | 2606.67 | 16-MAY-09:20 | 6.33 | 4.90 |
June | 0.194558E+11 | 32032.92 | 22-JUN-05:12 | 14.27 | 11.49 | 0.206437E+10 | 2606.65 | 13-JUN-13:20 | 14.27 | 11.49 |
July | 0.188200E+11 | 30642.99 | 24-JUL-05:12 | 13.17 | 12.61 | 0.191904E+10 | 2606.93 | 19-JUL-09:09 | 13.17 | 12.61 |
August | 0.179333E+11 | 20507.13 | 03-AUG-05:12 | 14.80 | 12.99 | 0.214678E+10 | 2606.66 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.111599E+11 | 13784.65 | 01-SEP-16:00 | 15.60 | 10.82 | 0.182547E+10 | 2606.67 | 08-SEP-13:20 | 11.47 | 7.77 |
October | 0.850953E+10 | 8558.53 | 05-OCT-16:00 | 11.10 | 5.87 | 0.167453E+10 | 2567.72 | 04-OCT-13:00 | 11.10 | 5.87 |
November | 0.589667E+10 | 7002.35 | 02-NOV-16:00 | -8.9 | -9.4 | 0.150961E+10 | 2215.51 | 03-NOV-13:00 | -12.2 | -12.7 |
December | 0.509491E+10 | 6540.32 | 15-DEC-12:00 | -33.3 | -33.5 | 0.143413E+10 | 2116.70 | 21-DEC-14:00 | -14.4 | -15.0 |
Annual Sum or Average | 0.132207E+12 | 0.210053E+11 | ||||||||
Minimum of Months | 0.509491E+10 | 6540.32 | -36.0 | -36.1 | 0.139877E+10 | 2116.70 | -14.4 | -15.0 | ||
Maximum of Months | 0.194558E+11 | 32032.92 | 20.00 | 12.99 | 0.214678E+10 | 2606.93 | 14.27 | 12.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210284E+10 | 6713.40 | 07-JAN-17:01 | -9.0 | -9.0 | 0.144932E+10 | 1929.34 | 09-JAN-14:09 | -19.0 | -19.2 |
February | 0.326413E+10 | 7996.47 | 09-FEB-15:00 | 0.00 | -1.0 | 0.132321E+10 | 2102.40 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.634954E+10 | 9102.01 | 22-MAR-16:00 | 5.60 | 2.61 | 0.161703E+10 | 2233.57 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 0.979182E+10 | 12626.13 | 21-APR-16:00 | 14.40 | 5.45 | 0.158088E+10 | 2591.23 | 21-APR-13:00 | 14.40 | 5.45 |
May | 0.154935E+11 | 18529.28 | 31-MAY-16:00 | 22.20 | 10.79 | 0.196316E+10 | 2606.65 | 19-MAY-13:50 | 22.20 | 10.79 |
June | 0.197811E+11 | 20985.91 | 21-JUN-16:00 | 25.60 | 14.20 | 0.204177E+10 | 2606.65 | 13-JUN-13:20 | 25.60 | 14.20 |
July | 0.189390E+11 | 21236.38 | 12-JUL-16:00 | 25.00 | 13.76 | 0.189654E+10 | 2606.84 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.171464E+11 | 19149.99 | 11-AUG-16:00 | 25.60 | 14.77 | 0.208448E+10 | 2606.66 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.105468E+11 | 11547.37 | 01-SEP-16:00 | 15.60 | 10.82 | 0.162338E+10 | 2566.60 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.616158E+10 | 9258.93 | 04-OCT-16:00 | 10.00 | 4.57 | 0.150744E+10 | 2298.48 | 04-OCT-13:00 | 10.00 | 4.57 |
November | 0.255471E+10 | 7074.10 | 02-NOV-16:00 | -8.9 | -9.4 | 0.143654E+10 | 1929.98 | 02-NOV-13:00 | -8.9 | -9.4 |
December | 0.190469E+10 | 6689.52 | 23-DEC-17:02 | -2.6 | -3.4 | 0.139795E+10 | 1929.40 | 26-DEC-10:09 | -8.6 | -9.4 |
Annual Sum or Average | 0.114036E+12 | 0.199217E+11 | ||||||||
Minimum of Months | 0.190469E+10 | 6689.52 | -9.0 | -9.4 | 0.132321E+10 | 1929.34 | -19.0 | -19.2 | ||
Maximum of Months | 0.197811E+11 | 21236.38 | 25.60 | 14.77 | 0.208448E+10 | 2606.84 | 25.60 | 14.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16995614.55 | 2803.54 | 07-JAN-17:01 | -9.0 | -9.0 | 0.304179E+09 | 406.88 | 12-JAN-14:30 | -36.1 | -36.2 |
February | 19842240.64 | 2793.21 | 11-FEB-17:02 | -1.2 | -2.7 | 0.276272E+09 | 406.87 | 21-FEB-10:09 | -21.9 | -22.2 |
March | 0.154340E+09 | 2832.20 | 18-MAR-16:03 | 1.10 | -1.2 | 0.331636E+09 | 406.85 | 13-MAR-09:30 | 1.10 | -1.2 |
April | 0.180936E+10 | 3894.16 | 28-APR-16:00 | 12.20 | 5.13 | 0.299898E+09 | 462.75 | 28-APR-13:00 | 12.20 | 5.13 |
May | 0.505334E+10 | 5085.43 | 31-MAY-05:02 | 12.07 | 7.63 | 0.364419E+09 | 546.61 | 31-MAY-13:00 | 20.00 | 10.15 |
June | 0.664116E+10 | 6632.20 | 30-JUN-14:30 | 27.75 | 17.00 | 0.411076E+09 | 549.50 | 13-JUN-13:20 | 27.75 | 17.00 |
July | 0.642797E+10 | 6418.53 | 11-JUL-13:50 | 25.10 | 15.96 | 0.378467E+09 | 549.51 | 07-JUL-13:09 | 25.10 | 15.96 |
August | 0.553506E+10 | 5226.13 | 06-AUG-12:02 | 17.38 | 11.77 | 0.390375E+09 | 549.49 | 02-AUG-13:00 | 17.38 | 11.77 |
September | 0.210555E+10 | 3928.95 | 01-SEP-16:00 | 15.60 | 10.82 | 0.301763E+09 | 466.51 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.317040E+09 | 2904.94 | 04-OCT-15:10 | 10.92 | 4.77 | 0.305509E+09 | 406.82 | 30-OCT-13:30 | -11.6 | -12.7 |
November | 15397295.14 | 2796.00 | 18-NOV-17:01 | -13.0 | -13.3 | 0.301508E+09 | 406.87 | 30-NOV-10:39 | -28.7 | -28.9 |
December | 21496781.72 | 2795.79 | 30-DEC-17:01 | -10.0 | -10.4 | 0.293417E+09 | 406.88 | 11-DEC-10:50 | -10.0 | -10.4 |
Annual Sum or Average | 0.281176E+11 | 0.395852E+10 | ||||||||
Minimum of Months | 15397295.14 | 2793.21 | -13.0 | -13.3 | 0.276272E+09 | 406.82 | -36.1 | -36.2 | ||
Maximum of Months | 0.664116E+10 | 6632.20 | 27.75 | 17.00 | 0.411076E+09 | 549.51 | 27.75 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10740984.61 | 1825.15 | 07-JAN-17:01 | -9.0 | -9.0 | 0.192552E+09 | 257.60 | 11-JAN-14:39 | -34.0 | -34.1 |
February | 27698321.38 | 1822.90 | 11-FEB-17:02 | -1.2 | -2.7 | 0.174922E+09 | 257.56 | 27-FEB-14:00 | -28.3 | -28.5 |
March | 0.568482E+09 | 2660.58 | 22-MAR-10:30 | 2.25 | 0.43 | 0.211796E+09 | 304.16 | 22-MAR-09:00 | 2.25 | 0.43 |
April | 0.199929E+10 | 4209.85 | 21-APR-10:00 | 7.80 | 3.31 | 0.205988E+09 | 347.88 | 28-APR-09:20 | 6.70 | 3.17 |
May | 0.478505E+10 | 12417.26 | 14-MAY-09:42 | 15.92 | 8.37 | 0.261167E+09 | 347.88 | 19-MAY-09:09 | 12.15 | 6.94 |
June | 0.582441E+10 | 9410.35 | 13-JUN-08:30 | 18.30 | 11.46 | 0.269575E+09 | 347.88 | 13-JUN-13:20 | 24.07 | 13.42 |
July | 0.578064E+10 | 9818.02 | 07-JUL-08:30 | 20.00 | 14.14 | 0.249526E+09 | 347.90 | 19-JUL-09:20 | 17.57 | 14.42 |
August | 0.471549E+10 | 8491.61 | 10-AUG-08:50 | 14.22 | 9.95 | 0.269099E+09 | 347.88 | 25-AUG-09:50 | 15.22 | 11.63 |
September | 0.194777E+10 | 3803.02 | 10-SEP-11:22 | 15.00 | 8.08 | 0.200106E+09 | 345.16 | 12-SEP-09:50 | 8.12 | 6.34 |
October | 0.430814E+09 | 2565.25 | 03-OCT-10:20 | 4.63 | 3.18 | 0.194170E+09 | 298.53 | 03-OCT-09:00 | 4.63 | 3.18 |
November | 9900611.61 | 1822.09 | 18-NOV-17:01 | -13.0 | -13.3 | 0.190867E+09 | 257.60 | 27-NOV-14:30 | -23.9 | -24.2 |
December | 13379372.72 | 1821.03 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185737E+09 | 257.59 | 15-DEC-14:09 | -2.6 | -3.4 |
Annual Sum or Average | 0.261137E+11 | 0.260551E+10 | ||||||||
Minimum of Months | 9900611.61 | 1821.03 | -13.0 | -13.3 | 0.174922E+09 | 257.56 | -34.0 | -34.1 | ||
Maximum of Months | 0.582441E+10 | 12417.26 | 20.00 | 14.14 | 0.269575E+09 | 347.90 | 24.07 | 14.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41023990.05 | 2784.68 | 07-JAN-17:01 | -9.0 | -9.0 | 0.304224E+09 | 406.86 | 12-JAN-14:50 | -36.1 | -36.2 |
February | 0.528176E+09 | 4228.19 | 15-FEB-14:00 | -8.3 | -9.2 | 0.279306E+09 | 503.58 | 15-FEB-14:09 | -8.1 | -9.1 |
March | 0.191048E+10 | 6401.71 | 31-MAR-14:00 | -11.1 | -13.1 | 0.354738E+09 | 549.50 | 31-MAR-13:30 | -11.1 | -13.1 |
April | 0.442158E+10 | 12209.22 | 20-APR-14:00 | 14.40 | 6.23 | 0.343173E+09 | 549.50 | 27-APR-13:20 | 10.77 | 4.21 |
May | 0.701449E+10 | 16886.81 | 14-MAY-12:22 | 18.35 | 9.42 | 0.396800E+09 | 549.51 | 19-MAY-13:50 | 13.58 | 8.15 |
June | 0.861341E+10 | 13126.89 | 30-JUN-12:30 | 26.15 | 17.75 | 0.414769E+09 | 549.51 | 13-JUN-13:09 | 26.15 | 17.75 |
July | 0.853763E+10 | 21441.27 | 23-JUL-13:22 | 25.00 | 15.26 | 0.384542E+09 | 549.51 | 07-JUL-13:09 | 25.00 | 15.26 |
August | 0.795731E+10 | 14354.85 | 10-AUG-13:40 | 22.03 | 12.10 | 0.417252E+09 | 549.52 | 25-AUG-13:00 | 22.80 | 15.44 |
September | 0.373076E+10 | 9501.27 | 07-SEP-14:30 | 15.85 | 8.58 | 0.328569E+09 | 549.52 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.128422E+10 | 8104.55 | 03-OCT-13:25 | 10.85 | 6.24 | 0.315995E+09 | 549.50 | 13-OCT-13:30 | 0.55 | -2.7 |
November | 0.126565E+09 | 3575.60 | 08-NOV-13:50 | -13.4 | -14.2 | 0.301924E+09 | 447.82 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 21444072.43 | 2780.42 | 23-DEC-17:02 | -2.6 | -3.4 | 0.293422E+09 | 406.85 | 01-DEC-10:09 | -2.6 | -3.4 |
Annual Sum or Average | 0.441871E+11 | 0.413471E+10 | ||||||||
Minimum of Months | 21444072.43 | 2780.42 | -13.4 | -14.2 | 0.279306E+09 | 406.85 | -36.1 | -36.2 | ||
Maximum of Months | 0.861341E+10 | 21441.27 | 26.15 | 17.75 | 0.417252E+09 | 549.52 | 26.15 | 17.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10685308.28 | 1812.84 | 07-JAN-17:01 | -9.0 | -9.0 | 0.192528E+09 | 257.57 | 31-JAN-10:00 | -22.8 | -23.3 |
February | 27719629.52 | 1811.87 | 11-FEB-17:02 | -1.2 | -2.7 | 0.174894E+09 | 257.57 | 27-FEB-14:00 | -28.3 | -28.5 |
March | 0.312801E+09 | 2403.44 | 22-MAR-15:40 | 5.60 | 2.48 | 0.210453E+09 | 281.03 | 22-MAR-15:50 | 5.60 | 2.55 |
April | 0.193025E+10 | 5998.39 | 21-APR-17:00 | 14.40 | 5.83 | 0.197843E+09 | 338.68 | 28-APR-15:00 | 12.20 | 5.13 |
May | 0.374059E+10 | 7232.14 | 14-MAY-18:12 | 16.70 | 9.23 | 0.234832E+09 | 347.83 | 31-MAY-13:00 | 20.00 | 10.15 |
June | 0.510722E+10 | 8928.04 | 10-JUN-17:07 | 21.20 | 10.81 | 0.258335E+09 | 347.86 | 13-JUN-13:20 | 24.07 | 13.42 |
July | 0.479815E+10 | 8074.80 | 11-JUL-17:40 | 26.10 | 15.25 | 0.238216E+09 | 347.86 | 07-JUL-13:09 | 26.10 | 15.25 |
August | 0.411129E+10 | 7490.07 | 10-AUG-17:00 | 23.30 | 12.28 | 0.251086E+09 | 347.84 | 02-AUG-13:00 | 23.30 | 12.28 |
September | 0.164782E+10 | 3947.25 | 07-SEP-16:00 | 17.20 | 8.91 | 0.194853E+09 | 338.67 | 07-SEP-15:00 | 17.20 | 8.91 |
October | 0.279538E+09 | 2420.45 | 03-OCT-15:10 | 12.62 | 6.83 | 0.193708E+09 | 281.95 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 10256539.83 | 1814.32 | 18-NOV-17:01 | -13.0 | -13.3 | 0.190856E+09 | 257.57 | 17-NOV-14:09 | -13.0 | -13.3 |
December | 13388202.58 | 1810.75 | 30-DEC-17:01 | -10.0 | -10.4 | 0.185721E+09 | 257.58 | 15-DEC-14:50 | -10.0 | -10.4 |
Annual Sum or Average | 0.219897E+11 | 0.252332E+10 | ||||||||
Minimum of Months | 10256539.83 | 1810.75 | -13.0 | -13.3 | 0.174894E+09 | 257.57 | -28.3 | -28.5 | ||
Maximum of Months | 0.510722E+10 | 8928.04 | 26.10 | 15.25 | 0.258335E+09 | 347.86 | 26.10 | 15.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19222316.84 | 2310.81 | 07-JAN-17:01 | -9.0 | -9.0 | 0.303667E+09 | 406.85 | 12-JAN-14:09 | -36.1 | -36.2 |
February | 15630432.83 | 2289.91 | 11-FEB-17:02 | -1.2 | -2.7 | 0.275464E+09 | 406.88 | 21-FEB-14:30 | -18.1 | -18.5 |
March | 38709266.05 | 2307.69 | 25-MAR-16:02 | -11.7 | -12.7 | 0.331590E+09 | 406.81 | 13-MAR-09:20 | -11.7 | -12.7 |
April | 0.903831E+09 | 2749.07 | 28-APR-15:30 | 12.20 | 4.96 | 0.296094E+09 | 425.72 | 28-APR-13:00 | 12.20 | 4.96 |
May | 0.359321E+10 | 3680.07 | 31-MAY-05:02 | 12.07 | 7.63 | 0.347343E+09 | 490.15 | 31-MAY-13:00 | 20.00 | 10.15 |
June | 0.495888E+10 | 5174.43 | 13-JUN-05:12 | 12.40 | 9.24 | 0.398581E+09 | 549.49 | 22-JUN-13:20 | 22.43 | 12.71 |
July | 0.510906E+10 | 5162.07 | 14-JUL-05:12 | 12.07 | 10.69 | 0.378753E+09 | 549.50 | 12-JUL-13:20 | 12.07 | 10.69 |
August | 0.490307E+10 | 4590.91 | 03-AUG-05:12 | 14.80 | 12.99 | 0.402246E+09 | 545.49 | 02-AUG-13:00 | 14.80 | 12.99 |
September | 0.271691E+10 | 3335.24 | 08-SEP-05:02 | 1.60 | 0.93 | 0.311124E+09 | 470.65 | 01-SEP-13:00 | 1.60 | 0.93 |
October | 0.614274E+09 | 2678.94 | 04-OCT-15:00 | 11.10 | 4.80 | 0.307507E+09 | 420.43 | 06-OCT-13:00 | 10.60 | 4.48 |
November | 16335982.33 | 2323.21 | 18-NOV-17:01 | -13.0 | -13.3 | 0.301886E+09 | 406.84 | 28-NOV-10:30 | -28.9 | -29.1 |
December | 28344681.13 | 2311.43 | 30-DEC-17:01 | -10.0 | -10.4 | 0.293586E+09 | 406.86 | 05-DEC-14:30 | -10.0 | -10.4 |
Annual Sum or Average | 0.229175E+11 | 0.394784E+10 | ||||||||
Minimum of Months | 15630432.83 | 2289.91 | -13.0 | -13.3 | 0.275464E+09 | 406.81 | -36.1 | -36.2 | ||
Maximum of Months | 0.510906E+10 | 5174.43 | 14.80 | 12.99 | 0.402246E+09 | 549.50 | 22.43 | 12.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11268004.48 | 1514.85 | 07-JAN-17:01 | -9.0 | -9.0 | 0.192179E+09 | 257.59 | 11-JAN-10:39 | -34.0 | -34.1 |
February | 12679268.56 | 1505.50 | 11-FEB-17:02 | -1.2 | -2.7 | 0.174609E+09 | 257.57 | 22-FEB-14:30 | -17.2 | -18.0 |
March | 0.285679E+09 | 2005.29 | 31-MAR-09:10 | -17.5 | -18.6 | 0.210929E+09 | 290.62 | 31-MAR-09:20 | -17.2 | -18.4 |
April | 0.145246E+10 | 2592.55 | 28-APR-08:40 | 6.33 | 2.83 | 0.201245E+09 | 346.92 | 28-APR-09:09 | 6.70 | 3.13 |
May | 0.364258E+10 | 5592.07 | 12-MAY-09:20 | 15.17 | 7.86 | 0.259711E+09 | 347.88 | 19-MAY-09:09 | 12.15 | 6.94 |
June | 0.452078E+10 | 8072.64 | 13-JUN-06:03 | 13.27 | 9.79 | 0.268774E+09 | 347.88 | 13-JUN-13:20 | 24.07 | 13.42 |
July | 0.488033E+10 | 9065.99 | 21-JUL-06:03 | 13.87 | 9.79 | 0.252032E+09 | 347.92 | 19-JUL-09:09 | 13.87 | 9.79 |
August | 0.435776E+10 | 8049.44 | 11-AUG-06:02 | 10.97 | 7.10 | 0.278187E+09 | 347.88 | 09-AUG-09:20 | 10.97 | 7.10 |
September | 0.233222E+10 | 3390.80 | 10-SEP-08:32 | 10.17 | 5.74 | 0.212724E+09 | 347.87 | 12-SEP-09:20 | 7.57 | 6.07 |
October | 0.691322E+09 | 2362.33 | 03-OCT-09:40 | 2.97 | 2.01 | 0.197579E+09 | 324.76 | 03-OCT-09:50 | 3.43 | 2.35 |
November | 10220558.99 | 1527.32 | 18-NOV-17:01 | -13.0 | -13.3 | 0.191076E+09 | 257.58 | 28-NOV-14:09 | -25.1 | -25.4 |
December | 15028466.94 | 1516.70 | 30-DEC-17:01 | -10.0 | -10.4 | 0.185796E+09 | 257.58 | 18-DEC-14:00 | -10.0 | -10.4 |
Annual Sum or Average | 0.222123E+11 | 0.262484E+10 | ||||||||
Minimum of Months | 10220558.99 | 1505.50 | -17.5 | -18.6 | 0.174609E+09 | 257.57 | -34.0 | -34.1 | ||
Maximum of Months | 0.488033E+10 | 9065.99 | 15.17 | 9.79 | 0.278187E+09 | 347.92 | 24.07 | 13.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16573104.63 | 2292.53 | 28-JAN-17:01 | -21.8 | -22.5 | 0.241853E+09 | 406.77 | 25-JAN-14:09 | -21.8 | -22.5 |
February | 91772281.32 | 2688.83 | 15-FEB-13:17 | -9.0 | -9.9 | 0.241813E+09 | 406.80 | 13-FEB-10:39 | -9.0 | -9.9 |
March | 0.322463E+09 | 2970.08 | 22-MAR-14:40 | 5.60 | 2.12 | 0.308554E+09 | 440.61 | 22-MAR-13:00 | 5.60 | 2.12 |
April | 0.216418E+10 | 6244.08 | 21-APR-14:40 | 13.90 | 5.62 | 0.315178E+09 | 549.50 | 20-APR-13:20 | 13.90 | 5.62 |
May | 0.415841E+10 | 7967.73 | 12-MAY-13:30 | 20.60 | 9.86 | 0.375695E+09 | 549.50 | 22-MAY-13:20 | 17.40 | 8.45 |
June | 0.566060E+10 | 9123.03 | 30-JUN-12:30 | 26.15 | 17.75 | 0.404784E+09 | 549.51 | 13-JUN-13:20 | 26.15 | 17.75 |
July | 0.637850E+10 | 10982.52 | 21-JUL-16:10 | 29.03 | 15.05 | 0.382771E+09 | 549.51 | 12-JUL-13:09 | 29.03 | 15.05 |
August | 0.622062E+10 | 17187.10 | 27-AUG-13:42 | 19.13 | 14.11 | 0.418676E+09 | 549.51 | 25-AUG-13:50 | 19.13 | 14.11 |
September | 0.305109E+10 | 7031.25 | 09-SEP-14:00 | 13.90 | 8.84 | 0.325528E+09 | 549.52 | 08-SEP-13:09 | 13.90 | 8.84 |
October | 0.775378E+09 | 5280.56 | 03-OCT-13:50 | 11.42 | 6.47 | 0.300282E+09 | 549.50 | 03-OCT-13:30 | 11.42 | 6.47 |
November | 19249343.09 | 2317.80 | 18-NOV-17:01 | -13.0 | -13.3 | 0.257204E+09 | 406.82 | 03-NOV-13:50 | -13.0 | -13.3 |
December | 18137653.96 | 2286.69 | 30-DEC-17:01 | -10.0 | -10.4 | 0.224311E+09 | 406.59 | 29-DEC-14:00 | -10.0 | -10.4 |
Annual Sum or Average | 0.288770E+11 | 0.379665E+10 | ||||||||
Minimum of Months | 16573104.63 | 2286.69 | -21.8 | -22.5 | 0.224311E+09 | 406.59 | -21.8 | -22.5 | ||
Maximum of Months | 0.637850E+10 | 17187.10 | 29.03 | 17.75 | 0.418676E+09 | 549.52 | 29.03 | 17.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11190880.23 | 1505.49 | 07-JAN-17:01 | -9.0 | -9.0 | 0.192106E+09 | 257.57 | 03-JAN-14:00 | -9.0 | -9.0 |
February | 10566344.57 | 1496.05 | 18-FEB-17:01 | -14.1 | -15.6 | 0.174347E+09 | 257.56 | 22-FEB-10:00 | -25.0 | -25.2 |
March | 0.102048E+09 | 1655.22 | 22-MAR-16:00 | 5.60 | 2.61 | 0.210014E+09 | 257.55 | 01-MAR-10:39 | 5.60 | 2.61 |
April | 0.136694E+10 | 4072.95 | 21-APR-18:20 | 14.03 | 5.87 | 0.193912E+09 | 338.33 | 21-APR-15:00 | 14.03 | 5.87 |
May | 0.271697E+10 | 3878.35 | 31-MAY-16:00 | 22.20 | 10.79 | 0.229357E+09 | 338.68 | 31-MAY-15:09 | 22.20 | 10.79 |
June | 0.378516E+10 | 5604.95 | 21-JUN-16:00 | 25.60 | 14.20 | 0.257424E+09 | 347.85 | 22-JUN-13:20 | 22.43 | 12.71 |
July | 0.381803E+10 | 5973.91 | 31-JUL-18:30 | 25.00 | 14.57 | 0.242115E+09 | 347.86 | 12-JUL-13:20 | 25.00 | 14.57 |
August | 0.370360E+10 | 5669.97 | 10-AUG-18:10 | 22.62 | 12.07 | 0.263352E+09 | 347.85 | 03-AUG-13:20 | 22.62 | 12.07 |
September | 0.203779E+10 | 2828.58 | 08-SEP-16:00 | 14.40 | 9.03 | 0.202434E+09 | 338.63 | 07-SEP-15:00 | 14.40 | 9.03 |
October | 0.469119E+09 | 2051.85 | 03-OCT-15:20 | 12.43 | 6.74 | 0.195241E+09 | 287.48 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 10849980.41 | 1519.40 | 18-NOV-17:01 | -13.0 | -13.3 | 0.191066E+09 | 257.56 | 27-NOV-14:50 | -23.9 | -24.2 |
December | 15119958.12 | 1507.20 | 30-DEC-17:01 | -10.0 | -10.4 | 0.185775E+09 | 257.57 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.180474E+11 | 0.253714E+10 | ||||||||
Minimum of Months | 10566344.57 | 1496.05 | -14.1 | -15.6 | 0.174347E+09 | 257.55 | -25.0 | -25.2 | ||
Maximum of Months | 0.381803E+10 | 5973.91 | 25.60 | 14.57 | 0.263352E+09 | 347.86 | 25.00 | 14.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16707211.70 | 2181.48 | 07-JAN-17:01 | -9.0 | -9.0 | 0.304357E+09 | 406.84 | 09-JAN-14:09 | -19.0 | -19.2 |
February | 42683225.18 | 2185.17 | 11-FEB-17:02 | -1.2 | -2.7 | 0.276460E+09 | 406.82 | 21-FEB-14:50 | -17.9 | -18.3 |
March | 0.300066E+09 | 2510.36 | 22-MAR-15:30 | 5.60 | 2.42 | 0.332377E+09 | 419.56 | 22-MAR-13:00 | 5.60 | 2.42 |
April | 0.212287E+10 | 3262.45 | 28-APR-16:00 | 12.20 | 5.13 | 0.310098E+09 | 499.88 | 28-APR-13:00 | 12.20 | 5.13 |
May | 0.464546E+10 | 4660.48 | 31-MAY-16:00 | 22.20 | 10.79 | 0.396150E+09 | 549.49 | 12-MAY-13:20 | 22.20 | 10.79 |
June | 0.604527E+10 | 9961.25 | 22-JUN-05:12 | 14.27 | 11.49 | 0.428955E+09 | 549.50 | 13-JUN-13:20 | 14.27 | 11.49 |
July | 0.583535E+10 | 9401.91 | 11-JUL-06:03 | 16.38 | 12.49 | 0.397295E+09 | 549.50 | 12-JUL-13:20 | 23.90 | 13.55 |
August | 0.508577E+10 | 5151.94 | 02-AUG-15:40 | 22.93 | 14.75 | 0.423727E+09 | 549.49 | 24-AUG-13:20 | 22.23 | 14.95 |
September | 0.277797E+10 | 3372.36 | 01-SEP-16:00 | 15.60 | 10.82 | 0.319918E+09 | 512.03 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.665857E+09 | 2711.26 | 04-OCT-15:30 | 10.55 | 4.70 | 0.308316E+09 | 439.89 | 04-OCT-13:00 | 10.55 | 4.70 |
November | 14484383.93 | 2177.87 | 18-NOV-17:01 | -13.0 | -13.3 | 0.301760E+09 | 406.84 | 27-NOV-14:09 | -23.9 | -24.2 |
December | 20155873.75 | 2176.48 | 30-DEC-17:01 | -10.0 | -10.4 | 0.293667E+09 | 406.84 | 26-DEC-14:30 | -10.0 | -10.4 |
Annual Sum or Average | 0.275726E+11 | 0.409308E+10 | ||||||||
Minimum of Months | 14484383.93 | 2176.48 | -13.0 | -13.3 | 0.276460E+09 | 406.82 | -23.9 | -24.2 | ||
Maximum of Months | 0.604527E+10 | 9961.25 | 22.93 | 14.75 | 0.428955E+09 | 549.50 | 23.90 | 14.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12912347.32 | 1708.81 | 07-JAN-17:01 | -9.0 | -9.0 | 0.141057E+09 | 250.80 | 30-JAN-13:00 | -23.9 | -24.3 |
February | 64144843.96 | 2101.82 | 15-FEB-11:03 | -14.9 | -15.2 | 0.128359E+09 | 280.71 | 15-FEB-11:09 | -14.9 | -15.2 |
March | 0.610664E+09 | 3790.44 | 28-MAR-10:02 | -10.2 | -12.3 | 0.158879E+09 | 356.46 | 27-MAR-10:09 | -10.2 | -12.3 |
April | 0.201749E+10 | 6939.95 | 21-APR-12:02 | 11.88 | 4.74 | 0.159082E+09 | 356.45 | 28-APR-10:09 | 6.60 | 3.27 |
May | 0.483802E+10 | 8897.22 | 12-MAY-10:05 | 16.88 | 8.37 | 0.197357E+09 | 356.46 | 19-MAY-14:09 | 13.48 | 8.19 |
June | 0.565460E+10 | 10116.99 | 04-JUN-09:42 | 17.43 | 11.50 | 0.201322E+09 | 356.46 | 20-JUN-14:09 | 24.08 | 14.17 |
July | 0.562768E+10 | 12259.19 | 23-JUL-09:42 | 20.63 | 14.69 | 0.187451E+09 | 356.46 | 27-JUL-10:09 | 19.50 | 14.89 |
August | 0.466261E+10 | 9363.24 | 10-AUG-10:05 | 18.07 | 11.40 | 0.205257E+09 | 356.46 | 24-AUG-12:09 | 20.28 | 14.31 |
September | 0.212050E+10 | 6441.12 | 08-SEP-12:02 | 9.68 | 5.58 | 0.158317E+09 | 356.46 | 08-SEP-14:09 | 12.48 | 8.41 |
October | 0.560332E+09 | 4804.74 | 03-OCT-12:02 | 8.17 | 5.20 | 0.146400E+09 | 356.46 | 03-OCT-12:09 | 8.17 | 5.20 |
November | 12154420.59 | 1726.99 | 02-NOV-12:02 | -9.3 | -9.8 | 0.139843E+09 | 250.80 | 28-NOV-09:39 | -28.9 | -29.1 |
December | 15014622.88 | 1704.51 | 30-DEC-17:01 | -10.0 | -10.4 | 0.136094E+09 | 250.80 | 11-DEC-16:40 | -10.0 | -10.4 |
Annual Sum or Average | 0.261961E+11 | 0.195942E+10 | ||||||||
Minimum of Months | 12154420.59 | 1704.51 | -14.9 | -15.2 | 0.128359E+09 | 250.80 | -28.9 | -29.1 | ||
Maximum of Months | 0.565460E+10 | 12259.19 | 20.63 | 14.69 | 0.205257E+09 | 356.46 | 24.08 | 14.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94769515.82 | 2818.23 | 25-JAN-13:40 | -19.5 | -19.7 | 0.304627E+09 | 406.83 | 02-JAN-14:09 | -19.5 | -19.7 |
February | 0.761071E+09 | 4330.42 | 15-FEB-14:10 | -8.1 | -9.1 | 0.282730E+09 | 543.00 | 15-FEB-14:09 | -8.1 | -9.1 |
March | 0.228455E+10 | 7682.70 | 31-MAR-13:30 | -11.4 | -13.3 | 0.362517E+09 | 549.50 | 22-MAR-13:30 | -11.4 | -13.3 |
April | 0.499283E+10 | 12361.50 | 20-APR-14:00 | 14.40 | 6.23 | 0.352048E+09 | 549.50 | 27-APR-13:20 | 10.77 | 4.21 |
May | 0.739297E+10 | 12791.43 | 12-MAY-13:30 | 20.60 | 9.86 | 0.408379E+09 | 549.51 | 19-MAY-13:50 | 13.58 | 8.15 |
June | 0.857087E+10 | 12775.81 | 30-JUN-12:30 | 26.15 | 17.75 | 0.422658E+09 | 549.51 | 13-JUN-13:09 | 26.15 | 17.75 |
July | 0.853295E+10 | 21078.74 | 23-JUL-13:42 | 25.00 | 15.26 | 0.392729E+09 | 549.51 | 12-JUL-13:09 | 25.00 | 15.26 |
August | 0.831249E+10 | 24835.26 | 27-AUG-13:32 | 18.87 | 14.02 | 0.430578E+09 | 549.51 | 25-AUG-13:50 | 18.87 | 14.02 |
September | 0.466169E+10 | 10026.46 | 07-SEP-14:30 | 15.85 | 8.58 | 0.343291E+09 | 549.52 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.183998E+10 | 9236.32 | 03-OCT-13:25 | 10.85 | 6.24 | 0.323109E+09 | 549.50 | 03-OCT-13:30 | 10.85 | 6.24 |
November | 0.230538E+09 | 3730.20 | 08-NOV-13:50 | -13.4 | -14.2 | 0.302950E+09 | 487.24 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 23839444.68 | 2604.48 | 30-DEC-17:01 | -10.0 | -10.4 | 0.293762E+09 | 406.84 | 05-DEC-14:00 | -10.0 | -10.4 |
Annual Sum or Average | 0.476985E+11 | 0.421938E+10 | ||||||||
Minimum of Months | 23839444.68 | 2604.48 | -19.5 | -19.7 | 0.282730E+09 | 406.83 | -19.5 | -19.7 | ||
Maximum of Months | 0.857087E+10 | 24835.26 | 26.15 | 17.75 | 0.430578E+09 | 549.52 | 26.15 | 17.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12445094.96 | 1697.23 | 07-JAN-17:01 | -9.0 | -9.0 | 0.192747E+09 | 257.56 | 13-JAN-10:30 | -30.9 | -31.0 |
February | 60730227.53 | 1701.44 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175102E+09 | 257.56 | 27-FEB-14:50 | -28.4 | -28.6 |
March | 0.442495E+09 | 2324.53 | 22-MAR-15:40 | 5.60 | 2.48 | 0.211290E+09 | 289.91 | 22-MAR-15:50 | 5.60 | 2.55 |
April | 0.224043E+10 | 6099.88 | 21-APR-17:00 | 14.40 | 5.83 | 0.202051E+09 | 338.68 | 28-APR-15:00 | 12.20 | 5.13 |
May | 0.391397E+10 | 6790.46 | 10-MAY-17:00 | 18.30 | 8.78 | 0.244399E+09 | 347.83 | 31-MAY-13:00 | 20.00 | 10.15 |
June | 0.505683E+10 | 9515.71 | 10-JUN-17:07 | 21.20 | 10.81 | 0.264938E+09 | 347.86 | 13-JUN-13:20 | 24.07 | 13.42 |
July | 0.475249E+10 | 7872.96 | 11-JUL-17:40 | 26.10 | 15.25 | 0.245296E+09 | 347.86 | 12-JUL-13:20 | 23.90 | 13.55 |
August | 0.427056E+10 | 7442.86 | 10-AUG-17:00 | 23.30 | 12.28 | 0.262127E+09 | 347.85 | 03-AUG-13:20 | 23.30 | 12.28 |
September | 0.220372E+10 | 4312.54 | 08-SEP-16:00 | 14.40 | 9.03 | 0.202038E+09 | 338.68 | 18-SEP-15:00 | 16.10 | 9.39 |
October | 0.529102E+09 | 2414.50 | 03-OCT-15:10 | 12.62 | 6.83 | 0.195289E+09 | 297.38 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 14742571.90 | 1701.12 | 18-NOV-17:01 | -13.0 | -13.3 | 0.191055E+09 | 257.56 | 28-NOV-10:50 | -28.9 | -29.1 |
December | 14905099.83 | 1696.07 | 30-DEC-17:01 | -10.0 | -10.4 | 0.185918E+09 | 257.58 | 04-DEC-10:39 | -10.0 | -10.4 |
Annual Sum or Average | 0.235124E+11 | 0.257225E+10 | ||||||||
Minimum of Months | 12445094.96 | 1696.07 | -13.0 | -13.3 | 0.175102E+09 | 257.56 | -30.9 | -31.0 | ||
Maximum of Months | 0.505683E+10 | 9515.71 | 26.10 | 15.25 | 0.264938E+09 | 347.86 | 24.07 | 13.55 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381890E+09 | 13771.22 | 02-JAN-05:01 | -15.6 |
February | 62724842.65 | 9047.74 | 21-FEB-06:01 | -23.3 |
March | 5778399.62 | 7307.24 | 06-MAR-07:01 | -20.9 |
April | 55093.31 | 918.22 | 03-APR-06:01 | -21.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 339873.84 | 5664.56 | 30-OCT-06:01 | -15.1 |
November | 21365821.57 | 8726.73 | 27-NOV-06:01 | -26.7 |
December | 63141784.64 | 9201.59 | 18-DEC-06:01 | -16.7 |
Annual Sum or Average | 0.535296E+09 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.381890E+09 | 13771.22 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210956E+11 | 27087.43 | 12-JAN-06:12 | -38.3 |
February | 0.161314E+11 | 27238.58 | 27-FEB-05:41 | -36.1 |
March | 0.117792E+11 | 26395.84 | 01-MAR-06:06 | -28.4 |
April | 0.406025E+10 | 23934.52 | 03-APR-05:08 | -21.2 |
May | 0.514401E+09 | 8909.37 | 12-MAY-05:03 | 5.37 |
June | 75383518.07 | 8215.32 | 02-JUN-05:02 | 5.78 |
July | 77318924.08 | 7695.79 | 31-JUL-05:02 | 7.67 |
August | 0.371398E+09 | 9415.22 | 31-AUG-05:02 | -1.2 |
September | 0.212812E+10 | 12629.39 | 29-SEP-05:02 | -4.0 |
October | 0.871301E+10 | 22320.81 | 27-OCT-05:13 | -17.6 |
November | 0.193183E+11 | 27267.91 | 29-NOV-06:07 | -28.9 |
December | 0.221463E+11 | 26045.06 | 15-DEC-06:13 | -33.0 |
Annual Sum or Average | 0.106411E+12 | |||
Minimum of Months | 75383518.07 | 7695.79 | -38.3 | |
Maximum of Months | 0.221463E+11 | 27267.91 | 7.67 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.572190E+10 | 13421.35 | 02-JAN-08:23 | -15.0 |
February | 0.400983E+10 | 12437.76 | 21-FEB-08:06 | -22.8 |
March | 0.290774E+10 | 9907.47 | 06-MAR-07:25 | -20.6 |
April | 0.985718E+09 | 8877.03 | 03-APR-06:06 | -21.5 |
May | 65206510.66 | 5554.75 | 28-MAY-12:52 | 13.30 |
June | 15794739.69 | 3062.66 | 11-JUN-12:12 | 15.73 |
July | 23483999.22 | 3908.92 | 23-JUL-12:22 | 24.45 |
August | 19444823.37 | 5341.48 | 20-AUG-12:32 | 13.17 |
September | 0.275828E+09 | 4241.14 | 10-SEP-11:08 | 14.60 |
October | 0.222226E+10 | 10464.37 | 30-OCT-06:17 | -15.2 |
November | 0.461695E+10 | 11766.99 | 27-NOV-08:04 | -26.7 |
December | 0.545534E+10 | 12084.60 | 04-DEC-08:04 | -19.7 |
Annual Sum or Average | 0.263195E+11 | |||
Minimum of Months | 15794739.69 | 3062.66 | -26.7 | |
Maximum of Months | 0.572190E+10 | 13421.35 | 24.45 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.401225E+10 | 11040.30 | 02-JAN-06:09 | -15.4 |
February | 0.272873E+10 | 7188.91 | 21-FEB-07:01 | -23.2 |
March | 0.172116E+10 | 5715.16 | 06-MAR-08:30 | -17.8 |
April | 0.373056E+09 | 4622.79 | 24-APR-05:01 | -3.4 |
May | 4317519.38 | 2562.35 | 21-MAY-13:12 | 14.80 |
June | 9220823.06 | 3322.63 | 19-JUN-05:02 | 8.27 |
July | 13040293.21 | 3397.16 | 30-JUL-11:12 | 16.67 |
August | 6750767.90 | 5281.30 | 31-AUG-05:02 | -1.2 |
September | 28651964.25 | 6006.43 | 18-SEP-05:02 | 1.78 |
October | 0.102992E+10 | 5220.74 | 30-OCT-06:01 | -15.1 |
November | 0.286526E+10 | 7043.15 | 13-NOV-07:01 | -17.1 |
December | 0.353714E+10 | 7380.42 | 04-DEC-06:13 | -19.4 |
Annual Sum or Average | 0.163295E+11 | |||
Minimum of Months | 4317519.38 | 2562.35 | -23.2 | |
Maximum of Months | 0.401225E+10 | 11040.30 | 16.67 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181410E+10 | 21907.31 | 02-JAN-05:01 | -15.6 |
February | 0.100567E+10 | 20658.81 | 21-FEB-05:01 | -22.9 |
March | 0.318990E+09 | 18098.06 | 06-MAR-06:02 | -21.1 |
April | 64396315.62 | 17134.85 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 1176665.55 | 13727.76 | 25-SEP-06:01 | -1.8 |
October | 0.196235E+09 | 18174.88 | 30-OCT-05:01 | -14.5 |
November | 0.100496E+10 | 20468.51 | 13-NOV-05:01 | -20.2 |
December | 0.149831E+10 | 20528.96 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.590384E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.9 | |
Maximum of Months | 0.181410E+10 | 21907.31 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.803852E+10 | 36481.95 | 01-JAN-05:22 | -14.4 |
February | 0.511979E+10 | 35588.87 | 06-FEB-05:01 | -10.5 |
March | 0.273877E+10 | 35433.23 | 06-MAR-05:01 | -20.2 |
April | 0.675442E+09 | 34520.59 | 03-APR-04:11 | -21.1 |
May | 2095345.63 | 6899.10 | 01-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 280083.34 | 1867.22 | 31-AUG-06:03 | -1.5 |
September | 0.121111E+09 | 29324.80 | 25-SEP-05:01 | -1.2 |
October | 0.188571E+10 | 35423.88 | 30-OCT-04:01 | -14.4 |
November | 0.619558E+10 | 35316.16 | 24-NOV-05:01 | -9.6 |
December | 0.783348E+10 | 35696.94 | 18-DEC-05:01 | -17.1 |
Annual Sum or Average | 0.326108E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.1 | |
Maximum of Months | 0.803852E+10 | 36481.95 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114439E+11 | 17718.39 | 28-JAN-22:02 | -23.5 |
February | 0.849126E+10 | 17693.09 | 26-FEB-08:12 | -26.0 |
March | 0.590365E+10 | 17147.23 | 13-MAR-03:52 | -23.9 |
April | 0.171536E+10 | 17092.10 | 03-APR-03:32 | -21.1 |
May | 28039559.17 | 11973.75 | 27-MAY-05:02 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 26809856.89 | 11990.37 | 31-AUG-05:02 | -1.2 |
September | 0.499267E+09 | 13629.20 | 29-SEP-05:01 | -4.0 |
October | 0.402600E+10 | 16604.51 | 30-OCT-04:01 | -14.4 |
November | 0.969781E+10 | 17127.55 | 26-NOV-12:02 | -23.0 |
December | 0.116909E+11 | 17078.84 | 11-DEC-01:32 | -20.0 |
Annual Sum or Average | 0.535230E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.116909E+11 | 17718.39 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.749545E+10 | 11632.23 | 28-JAN-22:02 | -23.5 |
February | 0.507088E+10 | 11571.69 | 26-FEB-08:12 | -26.0 |
March | 0.284224E+10 | 11196.22 | 13-MAR-03:52 | -23.9 |
April | 0.793320E+09 | 11165.27 | 03-APR-03:32 | -21.1 |
May | 5086403.90 | 7333.53 | 27-MAY-05:02 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 9558033.42 | 7642.61 | 31-AUG-05:02 | -1.2 |
September | 0.228904E+09 | 8897.46 | 29-SEP-05:01 | -4.0 |
October | 0.229883E+10 | 10871.29 | 30-OCT-04:01 | -14.4 |
November | 0.631372E+10 | 11220.79 | 26-NOV-08:42 | -25.6 |
December | 0.777361E+10 | 11180.85 | 11-DEC-03:32 | -21.1 |
Annual Sum or Average | 0.328316E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.777361E+10 | 11632.23 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104163E+11 | 17506.00 | 30-JAN-05:21 | -25.6 |
February | 0.631441E+10 | 17517.25 | 26-FEB-08:12 | -26.0 |
March | 0.372834E+10 | 16782.70 | 13-MAR-03:52 | -23.9 |
April | 0.111551E+10 | 16667.27 | 03-APR-03:32 | -21.1 |
May | 37476415.82 | 11926.38 | 27-MAY-05:02 | 0.10 |
June | 400460.99 | 2002.30 | 26-JUN-06:03 | 13.30 |
July | 205325.65 | 1026.63 | 06-JUL-06:03 | 11.47 |
August | 20741667.53 | 9229.82 | 31-AUG-06:03 | -1.5 |
September | 0.340202E+09 | 13198.53 | 25-SEP-05:01 | -1.2 |
October | 0.296146E+10 | 16471.13 | 30-OCT-04:01 | -14.4 |
November | 0.823509E+10 | 16958.77 | 26-NOV-08:42 | -25.6 |
December | 0.113218E+11 | 16975.82 | 03-DEC-14:52 | -22.2 |
Annual Sum or Average | 0.444920E+11 | |||
Minimum of Months | 205325.65 | 1026.63 | -26.0 | |
Maximum of Months | 0.113218E+11 | 17517.25 | 13.30 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.756433E+10 | 11532.48 | 30-JAN-05:21 | -25.6 |
February | 0.540234E+10 | 11542.41 | 26-FEB-08:12 | -26.0 |
March | 0.350681E+10 | 11098.57 | 13-MAR-03:52 | -23.9 |
April | 0.929104E+09 | 10997.79 | 03-APR-03:32 | -21.1 |
May | 31823822.89 | 7932.64 | 27-MAY-05:02 | 0.10 |
June | 280987.23 | 1404.94 | 26-JUN-06:03 | 13.30 |
July | 168810.96 | 844.05 | 06-JUL-06:03 | 11.47 |
August | 16825889.64 | 6436.96 | 30-AUG-05:03 | 0.00 |
September | 0.306543E+09 | 8794.04 | 29-SEP-05:01 | -4.0 |
October | 0.256948E+10 | 10803.37 | 30-OCT-04:01 | -14.4 |
November | 0.629146E+10 | 11139.38 | 26-NOV-08:42 | -25.6 |
December | 0.778194E+10 | 11134.88 | 03-DEC-14:52 | -22.2 |
Annual Sum or Average | 0.344011E+11 | |||
Minimum of Months | 168810.96 | 844.05 | -26.0 | |
Maximum of Months | 0.778194E+10 | 11542.41 | 13.30 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.992425E+10 | 13952.21 | 01-JAN-05:22 | -14.4 |
February | 0.814058E+10 | 14193.54 | 27-FEB-03:52 | -34.4 |
March | 0.598038E+10 | 13817.52 | 13-MAR-04:11 | -23.9 |
April | 0.148677E+10 | 12735.70 | 04-APR-04:01 | -10.3 |
May | 13577568.50 | 6365.67 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 2539117.70 | 7847.34 | 31-AUG-06:03 | -1.5 |
September | 82765473.83 | 9700.83 | 30-SEP-05:01 | -4.5 |
October | 0.180105E+10 | 12804.56 | 23-OCT-04:01 | -11.1 |
November | 0.654210E+10 | 13371.24 | 27-NOV-04:23 | -25.9 |
December | 0.906212E+10 | 13436.50 | 11-DEC-03:32 | -21.1 |
Annual Sum or Average | 0.430361E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.4 | |
Maximum of Months | 0.992425E+10 | 14193.54 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.663265E+10 | 9209.68 | 01-JAN-05:22 | -14.4 |
February | 0.490028E+10 | 9364.05 | 27-FEB-03:52 | -34.4 |
March | 0.258624E+10 | 8991.70 | 13-MAR-04:11 | -23.9 |
April | 0.536248E+09 | 8287.26 | 03-APR-04:01 | -21.1 |
May | 663639.58 | 3318.20 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 748908.17 | 2672.20 | 31-AUG-06:03 | -1.5 |
September | 31067483.95 | 6100.25 | 28-SEP-06:01 | -2.8 |
October | 0.973714E+09 | 8374.26 | 30-OCT-04:01 | -14.4 |
November | 0.433696E+10 | 8833.38 | 27-NOV-04:23 | -25.9 |
December | 0.619112E+10 | 8887.06 | 11-DEC-03:32 | -21.1 |
Annual Sum or Average | 0.261897E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.4 | |
Maximum of Months | 0.663265E+10 | 9364.05 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158242E+11 | 22185.75 | 12-JAN-07:10 | -38.3 |
February | 0.112667E+11 | 21412.42 | 27-FEB-08:00 | -34.4 |
March | 0.841678E+10 | 19800.48 | 01-MAR-08:00 | -28.3 |
April | 0.269852E+10 | 17071.91 | 03-APR-07:00 | -20.6 |
May | 0.787940E+09 | 10086.87 | 04-MAY-06:10 | 4.18 |
June | 0.219185E+09 | 8941.83 | 02-JUN-06:05 | 7.15 |
July | 0.152654E+09 | 7089.81 | 17-JUL-06:07 | 8.48 |
August | 0.372937E+09 | 10640.74 | 31-AUG-06:10 | -1.5 |
September | 0.139330E+10 | 12131.83 | 29-SEP-07:00 | -5.6 |
October | 0.500709E+10 | 16717.74 | 31-OCT-07:00 | -19.4 |
November | 0.124440E+11 | 19593.13 | 29-NOV-08:00 | -28.9 |
December | 0.158737E+11 | 20910.79 | 15-DEC-07:10 | -33.4 |
Annual Sum or Average | 0.744569E+11 | |||
Minimum of Months | 0.152654E+09 | 7089.81 | -38.3 | |
Maximum of Months | 0.158737E+11 | 22185.75 | 8.48 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670660E+10 | 9143.90 | 01-JAN-05:22 | -14.4 |
February | 0.525741E+10 | 9304.13 | 27-FEB-03:52 | -34.4 |
March | 0.341967E+10 | 8960.43 | 13-MAR-04:11 | -23.9 |
April | 0.592501E+09 | 8222.01 | 03-APR-04:01 | -21.1 |
May | 12333601.69 | 4230.12 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 823758.42 | 2588.72 | 31-AUG-06:03 | -1.5 |
September | 42379823.57 | 6350.25 | 30-SEP-05:01 | -4.5 |
October | 0.114889E+10 | 8324.55 | 30-OCT-04:01 | -14.4 |
November | 0.432154E+10 | 8778.97 | 27-NOV-04:23 | -25.9 |
December | 0.620221E+10 | 8834.33 | 11-DEC-03:32 | -21.1 |
Annual Sum or Average | 0.277044E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.4 | |
Maximum of Months | 0.670660E+10 | 9304.13 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787347E+10 | 12936.14 | 01-JAN-00:05 | -14.9 |
February | 0.542407E+10 | 13056.14 | 26-FEB-08:12 | -26.0 |
March | 0.326325E+10 | 12394.55 | 06-MAR-05:01 | -20.2 |
April | 0.688549E+09 | 11806.21 | 03-APR-04:01 | -21.1 |
May | 1351316.63 | 5594.42 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 2574795.00 | 7779.95 | 31-AUG-06:03 | -1.5 |
September | 0.100613E+09 | 9532.98 | 25-SEP-05:01 | -1.2 |
October | 0.191274E+10 | 12306.58 | 30-OCT-04:01 | -14.4 |
November | 0.596004E+10 | 13042.84 | 27-NOV-05:11 | -26.0 |
December | 0.784301E+10 | 12785.86 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.330697E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.787347E+10 | 13056.14 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521658E+10 | 9453.45 | 01-JAN-00:05 | -14.9 |
February | 0.319208E+10 | 9554.59 | 26-FEB-08:12 | -26.0 |
March | 0.148628E+10 | 9030.17 | 06-MAR-05:01 | -20.2 |
April | 0.303637E+09 | 8528.69 | 03-APR-04:01 | -21.1 |
May | 470190.57 | 2350.95 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 1523329.48 | 4876.79 | 31-AUG-06:03 | -1.5 |
September | 54345613.04 | 6772.09 | 25-SEP-05:01 | -1.2 |
October | 0.109395E+10 | 8972.41 | 30-OCT-04:01 | -14.4 |
November | 0.392487E+10 | 9567.69 | 27-NOV-05:11 | -26.0 |
December | 0.530131E+10 | 9356.36 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.205751E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.530131E+10 | 9567.69 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.697056E+10 | 14265.29 | 01-JAN-00:05 | -14.9 |
February | 0.374456E+10 | 14310.60 | 26-FEB-08:12 | -26.0 |
March | 0.180624E+10 | 13572.79 | 06-MAR-05:01 | -20.2 |
April | 0.386009E+09 | 12884.35 | 03-APR-04:01 | -21.1 |
May | 3933012.01 | 5661.50 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 2305937.32 | 7110.79 | 31-AUG-06:03 | -1.5 |
September | 67875872.37 | 10102.84 | 25-SEP-05:01 | -1.2 |
October | 0.129085E+10 | 13498.56 | 30-OCT-04:01 | -14.4 |
November | 0.476503E+10 | 14385.40 | 27-NOV-05:11 | -26.0 |
December | 0.750100E+10 | 14084.31 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.265384E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.750100E+10 | 14385.40 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.528043E+10 | 9381.44 | 01-JAN-00:05 | -14.9 |
February | 0.346977E+10 | 9549.42 | 26-FEB-08:12 | -26.0 |
March | 0.190152E+10 | 8974.75 | 06-MAR-05:01 | -20.2 |
April | 0.356492E+09 | 8460.16 | 03-APR-04:01 | -21.1 |
May | 3492208.18 | 3779.93 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 1668636.34 | 4744.88 | 31-AUG-06:03 | -1.5 |
September | 66451009.92 | 6767.68 | 25-SEP-05:01 | -1.2 |
October | 0.123664E+10 | 8909.73 | 30-OCT-04:01 | -14.4 |
November | 0.390471E+10 | 9504.64 | 27-NOV-05:11 | -26.0 |
December | 0.531352E+10 | 9281.55 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.215347E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.0 | |
Maximum of Months | 0.531352E+10 | 9549.42 | 14.88 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940557E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754512E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110094E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118416E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682383E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1142208.89 | 0.414831E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5227933.22 | 0.308723E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1008496.02 | 0.352628E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422373E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934094E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345110E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682500E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7378638.13 | 0.812281E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308723E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5227933.22 | 0.118416E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626555E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502716E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736243E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804879E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477689E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 759419.65 | 0.282948E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2776049.78 | 0.212901E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 479643.40 | 0.243487E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289230E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624620E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229845E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454677E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4015112.83 | 0.548579E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212901E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2776049.78 | 0.804879E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941212E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757159E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112048E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125191E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725987E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070373.80 | 0.425918E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3461643.67 | 0.322005E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 535806.67 | 0.377429E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446136E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950591E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345563E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682643E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5067824.14 | 0.834704E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322005E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3461643.67 | 0.125191E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626567E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502614E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735404E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823115E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480315E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671934.19 | 0.286374E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2342293.46 | 0.214671E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 316279.24 | 0.246101E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287470E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623052E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229933E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454661E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3330506.90 | 0.551028E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214671E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2342293.46 | 0.823115E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502889E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402375E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589768E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635180E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357668E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 805662.59 | 0.216776E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2950795.71 | 0.164528E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 621817.66 | 0.197327E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241754E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528297E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187135E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366304E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4378275.95 | 0.439000E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164528E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2950795.71 | 0.635180E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334796E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268070E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396560E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439014E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262529E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 430166.40 | 0.155039E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1183672.41 | 0.118615E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 211496.91 | 0.140968E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169015E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355451E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124380E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243660E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1825335.73 | 0.300810E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118615E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1183672.41 | 0.439014E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103850E+11 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817981E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910316E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529324E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306540E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29121021.09 | 0.176782E+10 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43215028.74 | 0.136202E+10 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10106002.16 | 0.248383E+10 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384528E+10 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667423E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100704E+11 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104718E+11 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82442051.99 | 0.727020E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136202E+10 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43215028.74 | 0.104718E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334767E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267909E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394515E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447649E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255987E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375980.84 | 0.153821E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1256265.50 | 0.116595E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173391.34 | 0.139842E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166397E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352941E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124517E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243660E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1805637.69 | 0.299860E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116595E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1256265.50 | 0.447649E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789543E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635404E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938179E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103161E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609598E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 858703.82 | 0.369493E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3674771.66 | 0.274207E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 537092.29 | 0.319065E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379123E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815052E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291133E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573392E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5070567.76 | 0.702580E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274207E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3674771.66 | 0.103161E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525267E+09 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422956E+09 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630299E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705223E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421005E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 605378.55 | 0.248276E+09 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2206581.33 | 0.186066E+09 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 371307.79 | 0.217412E+09 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260556E+09 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546412E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193425E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381148E+09 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3183267.67 | 0.473804E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186066E+09 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2206581.33 | 0.705223E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790434E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639896E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964844E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109650E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636722E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 893440.50 | 0.372178E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2836138.02 | 0.280154E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 432757.17 | 0.333113E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398426E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833589E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292223E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573792E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4162335.69 | 0.721187E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280154E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2836138.02 | 0.109650E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525723E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423190E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627911E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718167E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422043E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 569451.83 | 0.250378E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1913563.60 | 0.187047E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 265474.53 | 0.217831E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256841E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543351E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193819E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381581E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2748489.96 | 0.474788E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187047E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1913563.60 | 0.718167E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104440E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849672E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129061E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146582E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862200E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612779.82 | 0.508848E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2513603.20 | 0.378954E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175552.13 | 0.458260E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547873E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115363E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398513E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765247E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3301935.14 | 0.972403E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378954E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2513603.20 | 0.146582E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132123E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107703E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162657E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182455E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108054E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750158.60 | 0.639598E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3505001.58 | 0.474468E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235889.47 | 0.567636E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665771E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140595E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497537E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966565E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4491049.65 | 0.121474E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474468E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3505001.58 | 0.182455E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137526E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111356E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165406E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183236E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108832E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374789.89 | 0.659315E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2400190.59 | 0.495018E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49729.26 | 0.564900E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643943E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139181E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508708E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100367E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2824709.73 | 0.123309E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495018E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2400190.59 | 0.183236E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4203.58 | 28-JAN-23:51 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2520.31 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1885.10 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2496.19 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1163.69 | 26-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1065.36 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.75 | 29-JUL-17:02 | 855.73 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.44 | 23-AUG-18:00 | 905.34 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 688.33 | 30-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1570.97 | 21-OCT-04:04 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1343.48 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1449.45 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.33 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 184.75 | 4203.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2800.57 | 28-JAN-23:51 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1680.17 | 25-FEB-00:58 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1256.71 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1657.62 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 779.49 | 26-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 707.39 | 24-JUN-21:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.90 | 29-JUL-17:02 | 573.89 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 23-AUG-18:00 | 603.42 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 458.84 | 30-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1047.09 | 21-OCT-04:04 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.34 | 09-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 966.27 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.84 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 109.90 | 2800.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4206.12 | 28-JAN-23:51 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2520.22 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1889.94 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2681.85 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1180.22 | 26-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1139.38 | 18-JUN-14:10 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 21-JUL-16:00 | 872.05 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 11-AUG-16:00 | 914.35 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 718.16 | 30-SEP-21:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1567.09 | 21-OCT-04:04 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1344.54 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1449.47 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.16 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 4206.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2801.30 | 28-JAN-23:51 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1680.19 | 25-FEB-00:58 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1257.14 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1988.77 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 776.36 | 26-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 705.19 | 24-JUN-21:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 21-JUL-16:00 | 581.26 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 11-AUG-16:00 | 601.77 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 458.86 | 30-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1047.74 | 21-OCT-04:04 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.61 | 09-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 966.32 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.86 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 2801.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2257.77 | 28-JAN-23:55 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1339.15 | 25-FEB-00:55 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1001.33 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1354.37 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 631.33 | 27-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 30-JUN-15:00 | 612.64 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.64 | 29-JUL-17:02 | 449.43 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 | 23-AUG-18:00 | 524.52 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 404.27 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 850.25 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 721.71 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 769.68 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.27 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 104.64 | 2257.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1505.16 | 28-JAN-23:56 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 892.72 | 25-FEB-00:55 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 668.09 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 910.00 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 438.42 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 412.41 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 | 29-JUL-17:02 | 310.74 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 23-AUG-18:00 | 358.43 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 280.88 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 567.27 | 21-OCT-04:01 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 479.08 | 10-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 513.14 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.88 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 | 1505.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 53867.02 | 12-JAN-12:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 48768.88 | 27-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 43862.76 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 37376.51 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 14302.90 | 16-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.38 | 21-JUN-17:00 | 11849.27 | 02-JUN-06:10 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.26 | 21-JUL-16:10 | 10718.00 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.87 | 11-AUG-16:10 | 18702.64 | 31-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20789.98 | 29-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 34809.75 | 27-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 44626.46 | 28-NOV-12:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 49666.58 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10718.00 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.26 | 53867.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1505.17 | 28-JAN-23:55 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 892.77 | 25-FEB-00:55 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 667.98 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1067.07 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 419.56 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 407.20 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.94 | 29-JUL-17:02 | 311.96 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 11-AUG-16:00 | 355.97 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 274.42 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 564.09 | 21-OCT-04:01 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 480.43 | 10-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 513.12 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.42 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 52.94 | 1505.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.03 | 28-JAN-23:54 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2096.64 | 25-FEB-00:55 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1572.87 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2168.10 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1036.78 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 988.06 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.84 | 29-JUL-17:02 | 743.74 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 | 23-AUG-18:00 | 817.23 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 627.10 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1288.87 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1120.75 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1205.74 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.10 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 143.84 | 3537.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2358.03 | 28-JAN-23:51 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1397.75 | 25-FEB-00:55 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1048.80 | 14-MAR-21:02 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1440.18 | 01-APR-18:55 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 693.89 | 26-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 658.81 | 25-JUN-06:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.41 | 29-JUL-17:02 | 498.06 | 04-JUL-17:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 23-AUG-18:00 | 543.55 | 30-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 422.18 | 04-SEP-14:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 857.33 | 21-OCT-04:01 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 746.82 | 09-NOV-22:01 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 803.78 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.18 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 91.41 | 2358.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.05 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2096.65 | 25-FEB-00:58 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1634.88 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2330.80 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1052.79 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 989.78 | 18-JUN-14:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 21-JUL-16:00 | 756.44 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 11-AUG-16:00 | 821.51 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 645.64 | 30-SEP-21:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1302.27 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1121.96 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1205.68 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.64 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 3537.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2358.02 | 28-JAN-23:57 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1397.75 | 25-FEB-00:53 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1048.91 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1720.31 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 691.45 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 644.34 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 21-JUL-16:00 | 504.32 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 11-AUG-16:00 | 540.92 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 415.71 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 853.92 | 21-OCT-04:01 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 747.03 | 09-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 803.78 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.71 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 2358.02 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4727.52 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2845.60 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2024.68 | 25-MAR-03:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3134.84 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1482.49 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.32 | 30-JUN-15:00 | 1418.24 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.81 | 29-JUL-17:02 | 978.26 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 11-AUG-16:00 | 1173.93 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 884.04 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1894.13 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1584.52 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1627.70 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 884.04 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.81 | 4727.52 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5940.34 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3629.48 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2575.13 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3904.69 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1865.63 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 | 30-JUN-15:00 | 1715.61 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.40 | 29-JUL-17:02 | 1213.16 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 11-AUG-16:00 | 1463.32 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1077.05 | 30-SEP-21:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2319.21 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1989.85 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2075.51 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.05 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.40 | 5940.34 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6083.88 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3768.06 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2773.51 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4098.44 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1777.89 | 26-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 | 30-JUN-15:00 | 1728.01 | 18-JUN-14:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.02 | 29-JUL-17:02 | 1391.56 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 11-AUG-18:00 | 1327.66 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1084.63 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2263.61 | 21-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2005.73 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2139.66 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.63 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.02 | 6083.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9771.92 | 27-JAN-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10294.51 | 10-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13080.39 | 23-MAR-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 47904.06 | 24-APR-05:01 | 5082.11 | 8676.10 | 61874.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28082.53 | 15-MAY-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49058.42 | 19-JUN-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 49326.33 | 17-JUL-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49301.31 | 14-AUG-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46191.83 | 08-SEP-05:02 | 3176.32 | 5422.56 | 38671.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17364.49 | 05-OCT-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10287.86 | 03-NOV-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9385.98 | 21-DEC-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9385.98 | 1905.79 | 3253.54 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49326.33 | 6035.01 | 9760.61 | 61874.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1234.08 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992.14 |
March | 1934.94 | 22-MAR-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4953.88 | 21-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.12 |
May | 8899.03 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.00 |
June | 10473.31 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 0.00 |
July | 10610.43 | 21-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 | 0.00 |
August | 8484.27 | 10-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.01 |
September | 3728.64 | 07-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.84 |
October | 1557.72 | 03-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.34 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1078.05 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10610.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 | 1234.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6224.77 | 26-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.28 |
February | 6673.01 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.61 |
March | 6920.77 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.70 |
April | 4185.40 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.62 |
May | 2915.75 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 |
June | 4453.52 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.56 | 0.00 |
July | 4780.92 | 12-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 | 0.00 |
August | 3719.97 | 11-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 0.00 |
September | 3304.21 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.94 |
October | 5547.60 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.25 |
November | 6341.85 | 09-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5970.57 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2915.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6920.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.56 | 2099.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7136.88 | 25-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8028.28 | 17-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.17 |
March | 8157.25 | 31-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.82 |
April | 6079.82 | 08-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.19 |
May | 4170.97 | 16-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.57 |
June | 5319.58 | 22-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.56 |
July | 5539.99 | 12-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.66 |
August | 4901.64 | 01-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3916.77 | 08-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.99 |
October | 4945.75 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1688.72 |
November | 6518.38 | 09-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6240.63 | 30-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3916.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8157.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1688.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7388.17 | 12-JAN-15:05 | 12070.02 | 19521.22 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7421.10 | 09-FEB-16:30 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7993.87 | 22-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13426.76 | 21-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16723.10 | 12-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32032.92 | 22-JUN-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30642.99 | 24-JUL-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20507.13 | 03-AUG-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13784.65 | 01-SEP-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8558.53 | 05-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7002.35 | 02-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6540.32 | 15-DEC-12:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6540.32 | 2541.06 | 4338.05 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32032.92 | 12070.02 | 19521.22 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6713.40 | 07-JAN-17:01 | 2223.42 | 3795.79 | 15886.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7996.47 | 09-FEB-15:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9102.01 | 22-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12626.13 | 21-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18529.28 | 31-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20985.91 | 21-JUN-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21236.38 | 12-JUL-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19149.99 | 11-AUG-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11547.37 | 01-SEP-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9258.93 | 04-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7074.10 | 02-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6689.52 | 23-DEC-17:02 | 1905.79 | 3253.54 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6689.52 | 1905.79 | 3253.54 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21236.38 | 6198.29 | 9760.61 | 15886.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2803.54 | 07-JAN-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.57 |
February | 2793.21 | 11-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.62 |
March | 2832.20 | 18-MAR-16:03 | 267.84 | 457.25 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3894.16 | 28-APR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.08 |
May | 5085.43 | 31-MAY-05:02 | 669.60 | 1143.12 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 |
June | 6632.20 | 30-JUN-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 48.68 | 0.00 |
July | 6418.53 | 11-JUL-13:50 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 |
August | 5226.13 | 06-AUG-12:02 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.66 |
September | 3928.95 | 01-SEP-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 |
October | 2904.94 | 04-OCT-15:10 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.06 |
November | 2796.00 | 18-NOV-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2795.79 | 30-DEC-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2793.21 | 267.84 | 457.25 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6632.20 | 1306.65 | 2057.62 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 48.68 | 235.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1825.15 | 07-JAN-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.95 |
February | 1822.90 | 11-FEB-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.73 |
March | 2660.58 | 22-MAR-10:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.87 |
April | 4209.85 | 21-APR-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.98 |
May | 12417.26 | 14-MAY-09:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.72 |
June | 9410.35 | 13-JUN-08:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.30 |
July | 9818.02 | 07-JUL-08:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 |
August | 8491.61 | 10-AUG-08:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
September | 3803.02 | 10-SEP-11:22 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.14 |
October | 2565.25 | 03-OCT-10:20 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.65 |
November | 1822.09 | 18-NOV-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1821.03 | 23-DEC-17:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1821.03 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12417.26 | 1610.86 | 2605.29 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2784.68 | 07-JAN-17:01 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.54 |
February | 4228.19 | 15-FEB-14:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6401.71 | 31-MAR-14:00 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.27 |
April | 12209.22 | 20-APR-14:00 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 |
May | 16886.81 | 14-MAY-12:22 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.77 |
June | 13126.89 | 30-JUN-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 10.75 | 0.00 |
July | 21441.27 | 23-JUL-13:22 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.75 |
August | 14354.85 | 10-AUG-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
September | 9501.27 | 07-SEP-14:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
October | 8104.55 | 03-OCT-13:25 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.47 |
November | 3575.60 | 08-NOV-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 |
December | 2780.42 | 23-DEC-17:02 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2780.42 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21441.27 | 2613.31 | 4115.24 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.75 | 295.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1812.84 | 07-JAN-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.92 |
February | 1811.87 | 11-FEB-17:02 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.73 |
March | 2403.44 | 22-MAR-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5998.39 | 21-APR-17:00 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 |
May | 7232.14 | 14-MAY-18:12 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.05 |
June | 8928.04 | 10-JUN-17:07 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.27 |
July | 8074.80 | 11-JUL-17:40 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 | 0.00 |
August | 7490.07 | 10-AUG-17:00 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 |
September | 3947.25 | 07-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 |
October | 2420.45 | 03-OCT-15:10 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.59 |
November | 1814.32 | 18-NOV-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1810.75 | 30-DEC-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1810.75 | 0.00 | 361.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8928.04 | 805.38 | 1302.56 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 | 410.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2310.81 | 07-JAN-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.17 |
February | 2289.91 | 11-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.96 |
March | 2307.69 | 25-MAR-16:02 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.80 |
April | 2749.07 | 28-APR-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.98 |
May | 3680.07 | 31-MAY-05:02 | 669.60 | 1143.12 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 |
June | 5174.43 | 13-JUN-05:12 | 535.68 | 914.50 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.41 |
July | 5162.07 | 14-JUL-05:12 | 535.68 | 914.50 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4590.91 | 03-AUG-05:12 | 535.68 | 914.50 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 |
September | 3335.24 | 08-SEP-05:02 | 669.60 | 1143.12 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.86 |
October | 2678.94 | 04-OCT-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.94 |
November | 2323.21 | 18-NOV-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2311.43 | 30-DEC-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2289.91 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5174.43 | 1272.23 | 2057.62 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1514.85 | 07-JAN-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.38 |
February | 1505.50 | 11-FEB-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.63 |
March | 2005.29 | 31-MAR-09:10 | 3308.88 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 |
April | 2592.55 | 28-APR-08:40 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.52 |
May | 5592.07 | 12-MAY-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 |
June | 8072.64 | 13-JUN-06:03 | 508.69 | 1302.65 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 |
July | 9065.99 | 21-JUL-06:03 | 678.26 | 1736.86 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 |
August | 8049.44 | 11-AUG-06:02 | 847.82 | 2171.08 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 |
September | 3390.80 | 10-SEP-08:32 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.39 |
October | 2362.33 | 03-OCT-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 |
November | 1527.32 | 18-NOV-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1516.70 | 30-DEC-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1505.50 | 169.56 | 289.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9065.99 | 3308.88 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2292.53 | 28-JAN-17:01 | 602.64 | 1028.81 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.85 |
February | 2688.83 | 15-FEB-13:17 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3602.10 |
March | 2970.08 | 22-MAR-14:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1827.88 |
April | 6244.08 | 21-APR-14:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1116.24 |
May | 7967.73 | 12-MAY-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.03 |
June | 9123.03 | 30-JUN-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 228.47 | 0.00 |
July | 10982.52 | 21-JUL-16:10 | 401.76 | 1143.12 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.26 | 0.00 |
August | 17187.10 | 27-AUG-13:42 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.92 |
September | 7031.25 | 09-SEP-14:00 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.44 |
October | 5280.56 | 03-OCT-13:50 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.40 |
November | 2317.80 | 18-NOV-17:01 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2286.69 | 30-DEC-17:01 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2286.69 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17187.10 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3959.26 | 3602.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1505.49 | 07-JAN-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.38 |
February | 1496.05 | 18-FEB-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.24 |
March | 1655.22 | 22-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4072.95 | 21-APR-18:20 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
May | 3878.35 | 31-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 |
June | 5604.95 | 21-JUN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
July | 5973.91 | 31-JUL-18:30 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
August | 5669.97 | 10-AUG-18:10 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 |
September | 2828.58 | 08-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 |
October | 2051.85 | 03-OCT-15:20 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 |
November | 1519.40 | 18-NOV-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1507.20 | 30-DEC-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1496.05 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5973.91 | 805.38 | 1302.56 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 83.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2181.48 | 07-JAN-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.61 |
February | 2185.17 | 11-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.45 |
March | 2510.36 | 22-MAR-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3262.45 | 28-APR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.89 |
May | 4660.48 | 31-MAY-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 |
June | 9961.25 | 22-JUN-05:12 | 535.68 | 914.50 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.75 |
July | 9401.91 | 11-JUL-06:03 | 803.52 | 2057.62 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 |
August | 5151.94 | 02-AUG-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 |
September | 3372.36 | 01-SEP-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.39 |
October | 2711.26 | 04-OCT-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.60 |
November | 2177.87 | 18-NOV-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2176.48 | 30-DEC-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2176.48 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9961.25 | 1272.23 | 2057.62 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1708.81 | 07-JAN-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.86 |
February | 2101.82 | 15-FEB-11:03 | 2416.29 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.37 |
March | 3790.44 | 28-MAR-10:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.01 |
April | 6939.95 | 21-APR-12:02 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.18 |
May | 8897.22 | 12-MAY-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 |
June | 10116.99 | 04-JUN-09:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.39 |
July | 12259.19 | 23-JUL-09:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.82 |
August | 9363.24 | 10-AUG-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51 |
September | 6441.12 | 08-SEP-12:02 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 |
October | 4804.74 | 03-OCT-12:02 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 |
November | 1726.99 | 02-NOV-12:02 | 8054.28 | 13026.45 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1704.51 | 30-DEC-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1704.51 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12259.19 | 8054.28 | 13026.45 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2818.23 | 25-JAN-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 |
February | 4330.42 | 15-FEB-14:10 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 |
March | 7682.70 | 31-MAR-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.91 |
April | 12361.50 | 20-APR-14:00 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 |
May | 12791.43 | 12-MAY-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 |
June | 12775.81 | 30-JUN-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 | 0.00 |
July | 21078.74 | 23-JUL-13:42 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 |
August | 24835.26 | 27-AUG-13:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.79 |
September | 10026.46 | 07-SEP-14:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.98 |
October | 9236.32 | 03-OCT-13:25 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.97 |
November | 3730.20 | 08-NOV-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.46 |
December | 2604.48 | 30-DEC-17:01 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2604.48 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24835.26 | 2613.31 | 4115.24 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 | 195.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1697.23 | 07-JAN-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.85 |
February | 1701.44 | 11-FEB-17:02 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.20 |
March | 2324.53 | 22-MAR-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6099.88 | 21-APR-17:00 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 |
May | 6790.46 | 10-MAY-17:00 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9515.71 | 10-JUN-17:07 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.51 |
July | 7872.96 | 11-JUL-17:40 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
August | 7442.86 | 10-AUG-17:00 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
September | 4312.54 | 08-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.82 |
October | 2414.50 | 03-OCT-15:10 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.48 |
November | 1701.12 | 18-NOV-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1696.07 | 30-DEC-17:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1696.07 | 84.78 | 361.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9515.71 | 805.38 | 1302.56 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 130.85 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.167708E+12 | 129373.41 | 02-JAN-08:09 | 0.368676E+12 | 421663.77 | 12-JAN-07:19 |
February | 0.145867E+12 | 128986.19 | 27-FEB-08:09 | 0.273723E+12 | 437022.92 | 27-FEB-07:19 |
March | 0.159276E+12 | 123220.20 | 01-MAR-08:09 | 0.219929E+12 | 385612.70 | 01-MAR-07:19 |
April | 0.140011E+12 | 113797.79 | 21-APR-15:50 | 0.652196E+11 | 353785.69 | 03-APR-06:19 |
May | 0.148229E+12 | 143378.55 | 31-MAY-15:00 | 0.629075E+10 | 111598.61 | 27-MAY-06:10 |
June | 0.159128E+12 | 169872.70 | 30-JUN-14:30 | 0.705630E+09 | 33421.13 | 01-JUN-06:10 |
July | 0.162462E+12 | 170582.04 | 21-JUL-15:09 | 0.543557E+09 | 40576.24 | 05-JUL-06:10 |
August | 0.165376E+12 | 163841.95 | 11-AUG-15:50 | 0.246546E+10 | 139968.26 | 31-AUG-06:10 |
September | 0.142301E+12 | 119015.91 | 07-SEP-15:00 | 0.283384E+11 | 187190.33 | 25-SEP-06:10 |
October | 0.153184E+12 | 121724.65 | 30-OCT-07:19 | 0.144038E+12 | 332488.12 | 30-OCT-06:19 |
November | 0.159604E+12 | 127920.07 | 27-NOV-08:09 | 0.317857E+12 | 399093.80 | 27-NOV-07:19 |
December | 0.167386E+12 | 126545.16 | 04-DEC-08:09 | 0.375982E+12 | 400821.31 | 15-DEC-07:19 |
Annual Sum or Average | 0.187053E+13 | 0.180377E+13 | ||||
Minimum of Months | 0.140011E+12 | 113797.79 | 0.543557E+09 | 33421.13 | ||
Maximum of Months | 0.167708E+12 | 170582.04 | 0.375982E+12 | 437022.92 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.323023E+11 | 0.613996E+11 | 0.230900E+10 | 0.166710E+11 | 0.184960E+10 | 0.00 | 498614.32 | 0.00 | 0.00 | 0.00 | 0.592779E+10 | 0.00 |
February | 0.428574E+11 | 0.241682E+11 | 0.556056E+11 | 0.209511E+10 | 0.143797E+11 | 0.137803E+10 | 0.00 | 543870.62 | 0.00 | 0.00 | 0.00 | 0.538239E+10 | 0.00 |
March | 0.509265E+11 | 0.210875E+11 | 0.635880E+11 | 0.240664E+10 | 0.138494E+11 | 0.106900E+10 | 0.00 | 546942.38 | 0.00 | 0.00 | 0.00 | 0.634887E+10 | 0.00 |
April | 0.454877E+11 | 0.148450E+11 | 0.594055E+11 | 0.224272E+10 | 0.119804E+11 | 0.316531E+09 | 0.00 | 12629627.56 | 0.00 | 0.00 | 0.00 | 0.572041E+10 | 0.00 |
May | 0.490872E+11 | 0.970150E+10 | 0.624938E+11 | 0.235782E+10 | 0.148475E+11 | 48739403.08 | 0.00 | 0.361446E+10 | 0.00 | 0.00 | 0.00 | 0.607818E+10 | 0.00 |
June | 0.488499E+11 | 0.540473E+10 | 0.612808E+11 | 0.231841E+10 | 0.184966E+11 | 17672806.16 | 0.00 | 0.169374E+11 | 0.00 | 0.00 | 0.00 | 0.582206E+10 | 0.00 |
July | 0.457251E+11 | 0.751258E+10 | 0.606074E+11 | 0.228147E+10 | 0.182958E+11 | 15934278.37 | 0.00 | 0.227149E+11 | 0.00 | 0.00 | 0.00 | 0.530872E+10 | 0.00 |
August | 0.509265E+11 | 0.129624E+11 | 0.635880E+11 | 0.240664E+10 | 0.170871E+11 | 26738492.24 | 0.00 | 0.126648E+11 | 0.00 | 0.00 | 0.00 | 0.571439E+10 | 0.00 |
September | 0.454877E+11 | 0.180248E+11 | 0.593832E+11 | 0.224140E+10 | 0.116060E+11 | 0.139134E+09 | 0.00 | 0.274316E+09 | 0.00 | 0.00 | 0.00 | 0.514458E+10 | 0.00 |
October | 0.472479E+11 | 0.243123E+11 | 0.614108E+11 | 0.230966E+10 | 0.118007E+11 | 0.681970E+09 | 0.00 | 1023501.29 | 0.00 | 0.00 | 0.00 | 0.541944E+10 | 0.00 |
November | 0.466941E+11 | 0.291585E+11 | 0.599069E+11 | 0.224962E+10 | 0.144874E+11 | 0.159020E+10 | 0.00 | 532179.10 | 0.00 | 0.00 | 0.00 | 0.551668E+10 | 0.00 |
December | 0.457251E+11 | 0.345903E+11 | 0.605962E+11 | 0.228081E+10 | 0.166310E+11 | 0.187683E+10 | 0.00 | 452257.23 | 0.00 | 0.00 | 0.00 | 0.568574E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.234070E+12 | 0.729266E+12 | 0.274993E+11 | 0.180133E+12 | 0.901038E+10 | 0.00 | 0.562221E+11 | 0.00 | 0.00 | 0.00 | 0.680693E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.540473E+10 | 0.556056E+11 | 0.209511E+10 | 0.116060E+11 | 15934278.37 | 0.00 | 452257.23 | 0.00 | 0.00 | 0.00 | 0.514458E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.345903E+11 | 0.635880E+11 | 0.240664E+10 | 0.184966E+11 | 0.187683E+10 | 0.00 | 0.227149E+11 | 0.00 | 0.00 | 0.00 | 0.634887E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.368676E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.273723E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.219929E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.652196E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.629075E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.705630E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.543557E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.246546E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.283384E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.144038E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.317857E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.375982E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180377E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.543557E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.375982E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 06-JAN-17:19 | 17880.49 | 02-JAN-06:19 | 1591.31 | 12-JAN-07:30 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 02-FEB-12:20 | 17880.49 | 21-FEB-07:10 | 1645.14 | 27-FEB-07:30 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 01-MAR-13:20 | 16995.45 | 06-MAR-07:10 | 1480.90 | 01-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 11-APR-16:10 | 15281.94 | 03-APR-06:10 | 1440.62 | 03-APR-06:40 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 01-MAY-16:10 | 19210.35 | 31-MAY-15:20 | 492.66 | 27-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 01-JUN-12:20 | 23784.54 | 30-JUN-14:30 | 259.78 | 02-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 01-JUL-10:20 | 25854.01 | 12-JUL-15:20 | 240.84 | 05-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 14-AUG-16:10 | 23899.95 | 11-AUG-15:30 | 644.45 | 31-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 01-SEP-11:09 | 13248.02 | 08-SEP-15:30 | 927.47 | 25-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 03-OCT-12:09 | 16220.64 | 30-OCT-06:10 | 1417.68 | 30-OCT-06:00 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:20 | 17349.46 | 27-NOV-07:10 | 1523.50 | 28-NOV-07:19 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 19-DEC-17:19 | 17526.47 | 04-DEC-07:10 | 1544.28 | 15-DEC-07:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 13248.02 | 240.84 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 25854.01 | 1645.14 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 136.79 | 10-JAN-06:19 | 0.00 | 0.00 | 0.00 | 7771.46 | 03-JAN-12:20 | 0.00 |
February | 132.26 | 21-FEB-06:30 | 0.00 | 0.00 | 0.00 | 7771.48 | 21-FEB-12:39 | 0.00 |
March | 142.07 | 11-MAR-23:40 | 0.00 | 0.00 | 0.00 | 7770.70 | 01-MAR-12:00 | 0.00 |
April | 2519.95 | 22-APR-13:00 | 0.00 | 0.00 | 0.00 | 7770.36 | 03-APR-11:00 | 0.00 |
May | 26049.49 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 7768.90 | 09-MAY-11:20 | 0.00 |
June | 49039.73 | 30-JUN-14:39 | 0.00 | 0.00 | 0.00 | 7700.65 | 01-JUN-11:50 | 0.00 |
July | 49022.30 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 7302.89 | 03-JUL-11:00 | 0.00 |
August | 42122.10 | 11-AUG-15:00 | 0.00 | 0.00 | 0.00 | 7176.85 | 01-AUG-11:39 | 0.00 |
September | 8225.47 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 7161.71 | 29-SEP-11:00 | 0.00 |
October | 172.04 | 09-OCT-19:40 | 0.00 | 0.00 | 0.00 | 7229.30 | 31-OCT-11:00 | 0.00 |
November | 314.84 | 02-NOV-04:30 | 0.00 | 0.00 | 0.00 | 7668.54 | 29-NOV-12:00 | 0.00 |
December | 111.72 | 12-DEC-06:19 | 0.00 | 0.00 | 0.00 | 7770.07 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 111.72 | 0.00 | 0.00 | 0.00 | 7161.71 | 0.00 | ||
Maximum of Months | 49039.73 | 0.00 | 0.00 | 0.00 | 7771.48 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 129373.41 | 02-JAN-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 15514.07 | 1430.64 | 0.00 | 0.00 | 0.00 |
February | 128986.19 | 27-FEB-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 14943.31 | 1614.69 | 0.00 | 0.00 | 0.00 |
March | 123220.20 | 01-MAR-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 9417.72 | 1369.87 | 0.00 | 0.00 | 0.00 |
April | 113797.79 | 21-APR-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 14795.16 | 6.85 | 0.00 | 0.00 | 0.00 |
May | 143378.55 | 31-MAY-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 18688.22 | 6.85 | 0.00 | 26049.49 | 0.00 |
June | 169872.70 | 30-JUN-14:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 23784.54 | 6.92 | 0.00 | 49038.98 | 0.00 |
July | 170582.04 | 21-JUL-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 24236.59 | 6.85 | 0.00 | 48143.39 | 0.00 |
August | 163841.95 | 11-AUG-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 23671.02 | 6.85 | 0.00 | 41958.96 | 0.00 |
September | 119015.91 | 07-SEP-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 12587.24 | 6.85 | 0.00 | 8225.47 | 0.00 |
October | 121724.65 | 30-OCT-07:19 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 8039.25 | 1289.49 | 0.00 | 0.00 | 0.00 |
November | 127920.07 | 27-NOV-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 14201.44 | 1500.23 | 0.00 | 0.00 | 0.00 |
December | 126545.16 | 04-DEC-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 12741.50 | 1411.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 113797.79 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 8039.25 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 170582.04 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 24236.59 | 1614.69 | 0.00 | 49038.98 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 421663.77 | 12-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 437022.92 | 27-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 385612.70 | 01-MAR-07:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 353785.69 | 03-APR-06:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 111598.61 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 33421.13 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 40576.24 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 139968.26 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 187190.33 | 25-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 332488.12 | 30-OCT-06:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 399093.80 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 400821.31 | 15-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 33421.13 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 437022.92 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 19.42 | 3.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.00 | 19.42 | 3.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.42 | 3.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 19.31 | 6.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 3.17 | 19.80 | 3.17 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
March | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.20 | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
November | 2.33 | 19.46 | 2.17 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
December | 3.33 | 19.58 | 3.17 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
Annual Sum or Average | 15.67 | 19.49 | 14.83 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 19.80 | 6.00 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 18.54 | 4.83 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
February | 4.67 | 18.78 | 3.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
March | 1.17 | 18.31 | 0.67 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
April | 0.33 | 17.58 | 0.17 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 18.09 | 0.33 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
November | 5.00 | 18.66 | 3.50 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
December | 5.17 | 18.67 | 3.67 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Annual Sum or Average | 24.17 | 18.60 | 16.50 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.17 | 18.78 | 4.83 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 65.00 | 15.01 | 23.00 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
February | 52.50 | 15.00 | 18.00 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
March | 30.17 | 15.35 | 6.00 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
April | 8.50 | 15.30 | 2.83 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17.83 | 15.06 | 5.83 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
November | 59.33 | 15.09 | 22.33 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
December | 67.33 | 14.99 | 19.50 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 |
Annual Sum or Average | 300.67 | 15.06 | 97.50 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.33 | 15.35 | 23.00 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.17 | 14.98 | 23.17 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
February | 52.50 | 15.02 | 16.50 | 15.23 | 0.00 | 15.23 | 0.00 | 15.23 |
March | 27.67 | 15.38 | 4.17 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
April | 6.17 | 15.46 | 1.00 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.51 | 0.17 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.89 | 0.83 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16.17 | 15.06 | 3.67 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
November | 62.33 | 15.06 | 22.33 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
December | 70.50 | 14.94 | 20.83 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
Annual Sum or Average | 302.50 | 15.04 | 91.67 | 15.21 | 1.00 | 15.25 | 1.00 | 15.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.50 | 15.46 | 23.17 | 15.70 | 0.83 | 27.89 | 0.83 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.33 | 15.04 | 21.83 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
February | 42.00 | 15.18 | 10.50 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
March | 19.83 | 15.56 | 2.67 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
April | 4.33 | 15.41 | 0.83 | 15.44 | 0.00 | 15.44 | 0.00 | 15.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.25 | 1.33 | 28.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.64 | 1.00 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13.83 | 15.17 | 2.83 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
November | 52.33 | 15.14 | 16.67 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
December | 66.83 | 15.01 | 19.50 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
Annual Sum or Average | 262.50 | 15.13 | 74.83 | 15.30 | 2.67 | 15.40 | 2.67 | 15.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.83 | 15.56 | 21.83 | 15.84 | 1.33 | 28.25 | 1.33 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.17 | 14.98 | 23.67 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
February | 54.33 | 15.00 | 18.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
March | 28.50 | 15.36 | 5.50 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
April | 6.33 | 15.31 | 2.00 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.33 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.00 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17.67 | 15.06 | 4.83 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
November | 62.00 | 15.06 | 22.33 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
December | 70.17 | 14.96 | 20.50 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 |
Annual Sum or Average | 307.17 | 15.04 | 96.83 | 15.20 | 1.00 | 15.23 | 0.33 | 15.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.17 | 15.36 | 23.67 | 15.59 | 0.83 | 27.54 | 0.33 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.67 | 15.99 | 26.33 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
February | 47.00 | 16.16 | 22.33 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
March | 16.67 | 16.90 | 5.33 | 17.60 | 0.00 | 17.60 | 0.00 | 17.60 |
April | 3.67 | 16.40 | 0.83 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 17.15 | 0.17 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
November | 14.17 | 16.29 | 5.17 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
December | 27.33 | 16.18 | 10.67 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
Annual Sum or Average | 164.50 | 16.21 | 70.83 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.67 | 17.15 | 26.33 | 17.60 | 0.00 | 17.60 | 0.00 | 17.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.67 | 16.02 | 28.00 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
February | 44.33 | 16.08 | 18.83 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
March | 13.83 | 16.68 | 3.50 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
April | 1.67 | 16.78 | 0.33 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 17.15 | 0.17 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
November | 15.67 | 16.26 | 5.67 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
December | 31.67 | 16.06 | 12.67 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
Annual Sum or Average | 166.83 | 16.13 | 69.17 | 16.54 | 0.33 | 16.56 | 0.33 | 16.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.67 | 17.15 | 28.00 | 17.44 | 0.33 | 27.44 | 0.33 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 270.33 | 16.31 | 235.50 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
February | 156.83 | 16.17 | 133.83 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
March | 109.50 | 16.49 | 103.33 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
April | 32.50 | 17.44 | 32.17 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
May | 8.50 | 19.95 | 8.50 | 19.95 | 0.00 | 19.95 | 0.00 | 19.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
August | 2.33 | 19.04 | 2.33 | 19.04 | 0.83 | 20.30 | 0.83 | 21.23 |
September | 23.00 | 19.32 | 23.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
October | 64.50 | 17.28 | 64.00 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
November | 178.50 | 16.39 | 167.50 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
December | 281.33 | 16.58 | 253.83 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
Annual Sum or Average | 1127.33 | 16.57 | 1024.00 | 16.64 | 1.67 | 16.65 | 1.67 | 16.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.33 | 19.95 | 253.83 | 19.95 | 0.83 | 27.51 | 0.83 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 60.33 | 16.10 | 29.67 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
February | 47.67 | 16.17 | 22.00 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
March | 14.67 | 16.77 | 4.17 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
April | 0.83 | 17.20 | 0.17 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 17.12 | 0.17 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 |
November | 16.00 | 16.29 | 6.00 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
December | 31.67 | 16.05 | 12.83 | 16.39 | 0.00 | 16.39 | 0.00 | 16.39 |
Annual Sum or Average | 172.17 | 16.20 | 75.00 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.33 | 17.20 | 29.67 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.00 | 15.68 | 22.50 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 |
February | 33.83 | 15.78 | 14.50 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
March | 7.67 | 16.69 | 1.67 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
April | 2.00 | 16.21 | 0.33 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.50 | 16.03 | 0.50 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
November | 23.00 | 16.08 | 9.67 | 16.39 | 0.00 | 16.39 | 0.00 | 16.39 |
December | 33.17 | 16.07 | 13.50 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
Annual Sum or Average | 152.17 | 15.91 | 62.67 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.00 | 16.69 | 22.50 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.83 | 15.35 | 20.17 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
February | 30.83 | 15.62 | 10.17 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
March | 6.33 | 16.21 | 0.83 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
April | 1.33 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.65 | 1.50 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.17 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.92 | 1.17 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.17 | 15.61 | 0.17 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
November | 23.17 | 15.76 | 8.17 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
December | 35.17 | 15.56 | 12.00 | 15.75 | 0.00 | 15.75 | 0.00 | 15.75 |
Annual Sum or Average | 147.83 | 15.56 | 51.50 | 15.79 | 3.50 | 15.99 | 3.00 | 16.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.83 | 16.21 | 20.17 | 16.60 | 1.50 | 27.92 | 1.50 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.67 | 15.49 | 16.83 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
February | 21.33 | 16.02 | 7.00 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 |
March | 3.83 | 16.71 | 0.50 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
April | 0.17 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.39 | 0.83 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.37 | 1.17 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.75 | 1.33 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.50 | 16.22 | 0.17 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
November | 16.00 | 16.16 | 5.50 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
December | 28.83 | 15.75 | 9.83 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
Annual Sum or Average | 114.33 | 15.80 | 39.83 | 16.08 | 3.50 | 16.34 | 3.50 | 16.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.67 | 16.71 | 16.83 | 17.02 | 1.33 | 28.37 | 1.33 | 28.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.50 | 15.39 | 20.50 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
February | 32.33 | 15.60 | 11.67 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
March | 6.33 | 16.35 | 0.83 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
April | 0.67 | 15.88 | 0.00 | 15.88 | 0.00 | 15.88 | 0.00 | 15.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.65 | 0.33 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.67 | 15.63 | 0.17 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
November | 23.33 | 15.78 | 8.33 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
December | 34.33 | 15.58 | 12.00 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
Annual Sum or Average | 149.17 | 15.59 | 53.50 | 15.81 | 1.33 | 15.89 | 0.33 | 15.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.50 | 16.35 | 20.50 | 16.72 | 0.83 | 27.65 | 0.33 | 27.64 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.33 | 246.00 | 21.07 | 246.00 | 20.93 |
February | 454.00 | 21.83 | 157.33 | 21.54 | 157.33 | 21.37 |
March | 514.00 | 22.64 | 42.50 | 22.52 | 42.50 | 22.42 |
April | 429.33 | 23.56 | 5.33 | 23.57 | 2.00 | 23.56 |
May | 127.17 | 23.97 | 42.17 | 24.49 | 0.00 | 24.49 |
June | 0.00 | 0.00 | 242.33 | 24.97 | 0.00 | 24.97 |
July | 0.00 | 0.00 | 433.50 | 24.65 | 0.00 | 24.65 |
August | 12.50 | 24.01 | 305.83 | 24.70 | 0.00 | 24.70 |
September | 161.67 | 23.83 | 63.33 | 24.43 | 0.00 | 24.43 |
October | 484.50 | 23.42 | 3.00 | 23.40 | 3.00 | 23.39 |
November | 489.00 | 22.05 | 115.00 | 21.83 | 115.00 | 21.68 |
December | 497.00 | 21.40 | 274.50 | 21.21 | 274.50 | 21.12 |
Annual Sum or Average | 3671.17 | 22.43 | 1930.83 | 22.65 | 840.33 | 22.41 |
Minimum of Months | 0.00 | 0.00 | 3.00 | 21.07 | 0.00 | 20.93 |
Maximum of Months | 514.00 | 24.01 | 433.50 | 24.97 | 274.50 | 24.97 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.53 | 441.83 | 20.46 | 441.83 | 20.43 |
February | 454.00 | 20.86 | 308.17 | 20.67 | 308.17 | 20.59 |
March | 514.00 | 21.48 | 223.83 | 21.27 | 223.83 | 21.16 |
April | 484.00 | 22.65 | 57.67 | 22.46 | 57.67 | 22.31 |
May | 367.33 | 23.59 | 1.00 | 23.59 | 0.00 | 23.59 |
June | 40.00 | 23.61 | 127.83 | 24.44 | 0.00 | 24.44 |
July | 8.50 | 23.52 | 272.67 | 24.47 | 0.00 | 24.47 |
August | 113.33 | 23.58 | 149.83 | 24.14 | 0.00 | 24.14 |
September | 425.00 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
October | 502.00 | 21.80 | 112.83 | 21.59 | 112.83 | 21.44 |
November | 489.00 | 20.82 | 379.83 | 20.70 | 379.83 | 20.65 |
December | 497.00 | 20.58 | 462.50 | 20.54 | 462.50 | 20.53 |
Annual Sum or Average | 4396.17 | 21.71 | 2538.00 | 21.60 | 1986.67 | 21.36 |
Minimum of Months | 8.50 | 20.53 | 0.00 | 20.46 | 0.00 | 20.43 |
Maximum of Months | 514.00 | 23.61 | 462.50 | 24.47 | 462.50 | 24.47 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 502.00 | 20.06 | 502.00 | 20.06 |
February | 454.00 | 20.19 | 428.50 | 20.16 | 428.50 | 20.15 |
March | 514.00 | 20.67 | 410.00 | 20.58 | 410.00 | 20.54 |
April | 485.00 | 21.62 | 164.00 | 21.30 | 164.00 | 21.10 |
May | 432.50 | 22.95 | 4.83 | 22.93 | 4.83 | 22.90 |
June | 161.50 | 23.28 | 83.17 | 23.67 | 0.00 | 23.67 |
July | 110.17 | 23.16 | 191.17 | 23.94 | 0.00 | 23.94 |
August | 271.00 | 23.00 | 72.83 | 23.27 | 0.33 | 23.27 |
September | 482.00 | 21.99 | 45.83 | 21.87 | 45.83 | 21.77 |
October | 502.00 | 20.69 | 335.33 | 20.53 | 335.33 | 20.47 |
November | 489.00 | 20.11 | 489.00 | 20.11 | 489.00 | 20.11 |
December | 497.00 | 20.05 | 497.00 | 20.05 | 497.00 | 20.05 |
Annual Sum or Average | 4900.17 | 21.14 | 3223.67 | 20.94 | 2876.83 | 20.75 |
Minimum of Months | 110.17 | 20.05 | 4.83 | 20.05 | 0.00 | 20.05 |
Maximum of Months | 514.00 | 23.28 | 502.00 | 23.94 | 502.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 502.00 | 19.69 | 502.00 | 19.69 |
February | 454.00 | 19.79 | 454.00 | 19.79 | 454.00 | 19.79 |
March | 514.00 | 20.09 | 504.67 | 20.08 | 504.67 | 20.08 |
April | 485.00 | 20.53 | 294.50 | 20.36 | 294.50 | 20.28 |
May | 503.00 | 21.84 | 37.00 | 21.74 | 37.00 | 21.66 |
June | 271.33 | 22.66 | 68.83 | 22.97 | 0.00 | 22.97 |
July | 241.00 | 22.55 | 122.00 | 23.11 | 0.00 | 23.11 |
August | 441.17 | 22.06 | 39.67 | 22.14 | 13.67 | 22.10 |
September | 485.00 | 20.92 | 172.17 | 20.78 | 172.17 | 20.70 |
October | 502.00 | 20.04 | 455.67 | 19.99 | 455.67 | 19.97 |
November | 489.00 | 19.72 | 489.00 | 19.72 | 489.00 | 19.72 |
December | 497.00 | 19.66 | 497.00 | 19.66 | 497.00 | 19.66 |
Annual Sum or Average | 5384.50 | 20.63 | 3636.50 | 20.43 | 3419.67 | 20.28 |
Minimum of Months | 241.00 | 19.66 | 37.00 | 19.66 | 0.00 | 19.66 |
Maximum of Months | 514.00 | 22.66 | 504.67 | 23.11 | 504.67 | 23.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 502.00 | 19.68 | 502.00 | 19.68 |
February | 454.00 | 19.79 | 453.17 | 19.79 | 453.17 | 19.79 |
March | 514.00 | 20.22 | 457.67 | 20.15 | 457.67 | 20.13 |
April | 466.33 | 21.02 | 217.33 | 20.72 | 216.83 | 20.56 |
May | 331.50 | 22.26 | 85.00 | 22.54 | 15.00 | 22.47 |
June | 164.50 | 22.65 | 215.67 | 23.55 | 0.00 | 23.55 |
July | 141.17 | 22.61 | 288.17 | 23.74 | 3.33 | 23.76 |
August | 309.17 | 22.31 | 136.00 | 22.86 | 4.00 | 22.83 |
September | 470.67 | 21.24 | 116.67 | 21.08 | 113.83 | 20.95 |
October | 502.00 | 20.11 | 425.00 | 20.03 | 425.00 | 20.00 |
November | 489.00 | 19.71 | 489.00 | 19.71 | 489.00 | 19.71 |
December | 497.00 | 19.65 | 497.00 | 19.65 | 497.00 | 19.65 |
Annual Sum or Average | 4841.33 | 20.60 | 3882.67 | 20.62 | 3176.83 | 20.42 |
Minimum of Months | 141.17 | 19.65 | 85.00 | 19.65 | 0.00 | 19.65 |
Maximum of Months | 514.00 | 22.65 | 502.00 | 23.74 | 502.00 | 23.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 502.00 | 19.70 | 502.00 | 19.70 |
February | 454.00 | 19.95 | 426.83 | 19.89 | 426.83 | 19.87 |
March | 498.50 | 20.54 | 378.00 | 20.35 | 378.00 | 20.27 |
April | 388.00 | 21.10 | 223.00 | 20.99 | 190.67 | 20.79 |
May | 338.00 | 21.91 | 121.50 | 22.24 | 39.83 | 22.08 |
June | 215.17 | 22.47 | 193.17 | 23.31 | 0.67 | 23.32 |
July | 191.33 | 22.49 | 242.33 | 23.53 | 5.83 | 23.58 |
August | 289.67 | 22.11 | 175.00 | 22.88 | 12.50 | 22.85 |
September | 417.50 | 21.28 | 149.67 | 21.26 | 118.00 | 21.11 |
October | 492.67 | 20.29 | 390.67 | 20.16 | 388.17 | 20.11 |
November | 489.00 | 19.75 | 485.17 | 19.75 | 485.17 | 19.74 |
December | 497.00 | 19.67 | 497.00 | 19.67 | 497.00 | 19.67 |
Annual Sum or Average | 4772.83 | 20.67 | 3784.33 | 20.71 | 3044.67 | 20.49 |
Minimum of Months | 191.33 | 19.67 | 121.50 | 19.67 | 0.67 | 19.67 |
Maximum of Months | 502.00 | 22.49 | 502.00 | 23.53 | 502.00 | 23.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 502.00 | 19.68 | 502.00 | 19.68 |
February | 454.00 | 19.79 | 452.17 | 19.78 | 452.17 | 19.78 |
March | 514.00 | 20.15 | 482.83 | 20.12 | 482.83 | 20.10 |
April | 443.33 | 20.82 | 249.00 | 20.60 | 239.83 | 20.46 |
May | 427.00 | 21.90 | 76.17 | 21.90 | 47.67 | 21.77 |
June | 231.83 | 22.45 | 162.17 | 23.23 | 0.83 | 23.24 |
July | 216.17 | 22.36 | 195.33 | 23.28 | 0.17 | 23.28 |
August | 355.17 | 22.01 | 105.17 | 22.43 | 11.33 | 22.38 |
September | 471.17 | 21.06 | 158.83 | 20.91 | 157.17 | 20.81 |
October | 502.00 | 20.05 | 441.83 | 19.99 | 441.83 | 19.97 |
November | 489.00 | 19.71 | 489.00 | 19.71 | 489.00 | 19.71 |
December | 497.00 | 19.65 | 497.00 | 19.65 | 497.00 | 19.65 |
Annual Sum or Average | 5102.67 | 20.59 | 3811.50 | 20.52 | 3321.83 | 20.34 |
Minimum of Months | 216.17 | 19.65 | 76.17 | 19.65 | 0.17 | 19.65 |
Maximum of Months | 514.00 | 22.45 | 502.00 | 23.28 | 502.00 | 23.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.73 | 502.00 | 19.73 | 502.00 | 19.73 |
February | 454.00 | 19.79 | 454.00 | 19.79 | 454.00 | 19.79 |
March | 514.00 | 20.12 | 514.00 | 20.12 | 514.00 | 20.12 |
April | 485.00 | 20.50 | 390.33 | 20.44 | 390.33 | 20.41 |
May | 508.00 | 21.52 | 45.50 | 21.45 | 45.50 | 21.39 |
June | 416.83 | 22.78 | 8.33 | 22.81 | 0.00 | 22.81 |
July | 291.50 | 22.81 | 61.67 | 23.09 | 0.00 | 23.09 |
August | 450.17 | 22.48 | 19.83 | 22.54 | 3.17 | 22.52 |
September | 485.00 | 21.32 | 77.17 | 21.23 | 77.17 | 21.16 |
October | 502.00 | 20.46 | 411.67 | 20.40 | 411.67 | 20.38 |
November | 489.00 | 19.85 | 489.00 | 19.85 | 489.00 | 19.85 |
December | 497.00 | 19.75 | 497.00 | 19.75 | 497.00 | 19.75 |
Annual Sum or Average | 5594.50 | 20.82 | 3470.50 | 20.55 | 3383.83 | 20.40 |
Minimum of Months | 291.50 | 19.73 | 8.33 | 19.73 | 0.00 | 19.73 |
Maximum of Months | 514.00 | 22.81 | 514.00 | 23.09 | 514.00 | 23.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 502.00 | 19.71 | 502.00 | 19.71 |
February | 454.00 | 19.81 | 454.00 | 19.81 | 454.00 | 19.81 |
March | 514.00 | 20.28 | 496.67 | 20.26 | 496.67 | 20.26 |
April | 481.00 | 21.09 | 247.67 | 20.85 | 247.67 | 20.73 |
May | 360.17 | 22.49 | 31.33 | 22.65 | 5.00 | 22.62 |
June | 183.33 | 22.83 | 178.33 | 23.58 | 0.00 | 23.58 |
July | 97.33 | 22.82 | 320.33 | 24.03 | 1.67 | 24.04 |
August | 213.83 | 22.80 | 169.17 | 23.46 | 1.33 | 23.45 |
September | 445.50 | 21.79 | 46.00 | 21.78 | 37.00 | 21.69 |
October | 502.00 | 20.62 | 347.67 | 20.51 | 347.67 | 20.46 |
November | 489.00 | 19.83 | 489.00 | 19.83 | 489.00 | 19.83 |
December | 497.00 | 19.73 | 497.00 | 19.73 | 497.00 | 19.73 |
Annual Sum or Average | 4739.17 | 20.76 | 3779.17 | 20.78 | 3079.00 | 20.56 |
Minimum of Months | 97.33 | 19.71 | 31.33 | 19.71 | 0.00 | 19.71 |
Maximum of Months | 514.00 | 22.83 | 502.00 | 24.03 | 502.00 | 24.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.80 | 502.00 | 17.80 | 502.00 | 17.80 |
February | 454.00 | 18.65 | 448.17 | 18.64 | 448.17 | 18.63 |
March | 514.00 | 19.55 | 459.83 | 19.46 | 459.83 | 19.42 |
April | 452.50 | 20.99 | 193.17 | 20.72 | 187.17 | 20.53 |
May | 423.50 | 21.94 | 44.83 | 22.01 | 24.83 | 21.92 |
June | 276.33 | 22.52 | 107.33 | 23.07 | 0.00 | 23.07 |
July | 166.83 | 22.44 | 239.00 | 23.64 | 3.00 | 23.66 |
August | 251.00 | 22.28 | 186.50 | 23.19 | 4.67 | 23.17 |
September | 414.00 | 21.56 | 74.33 | 21.67 | 40.33 | 21.54 |
October | 499.00 | 20.32 | 329.33 | 20.09 | 329.33 | 19.99 |
November | 489.00 | 18.34 | 489.00 | 18.34 | 489.00 | 18.34 |
December | 497.00 | 17.62 | 497.00 | 17.62 | 497.00 | 17.62 |
Annual Sum or Average | 4939.17 | 19.96 | 3570.50 | 19.81 | 2985.33 | 19.50 |
Minimum of Months | 166.83 | 17.62 | 44.83 | 17.62 | 0.00 | 17.62 |
Maximum of Months | 514.00 | 22.52 | 502.00 | 23.64 | 502.00 | 23.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 502.00 | 19.71 | 502.00 | 19.71 |
February | 454.00 | 19.78 | 454.00 | 19.78 | 454.00 | 19.78 |
March | 514.00 | 20.16 | 508.50 | 20.16 | 508.50 | 20.16 |
April | 473.83 | 20.98 | 264.17 | 20.76 | 263.50 | 20.65 |
May | 473.00 | 21.95 | 34.17 | 21.88 | 31.50 | 21.80 |
June | 279.17 | 22.73 | 100.00 | 23.17 | 0.00 | 23.17 |
July | 201.33 | 22.71 | 179.83 | 23.49 | 0.00 | 23.49 |
August | 318.33 | 22.59 | 109.00 | 23.02 | 1.67 | 23.01 |
September | 473.17 | 21.61 | 60.00 | 21.52 | 58.33 | 21.44 |
October | 502.00 | 20.49 | 396.50 | 20.42 | 396.50 | 20.39 |
November | 489.00 | 19.83 | 489.00 | 19.83 | 489.00 | 19.83 |
December | 497.00 | 19.73 | 497.00 | 19.73 | 497.00 | 19.73 |
Annual Sum or Average | 5176.83 | 20.80 | 3594.17 | 20.66 | 3202.00 | 20.47 |
Minimum of Months | 201.33 | 19.71 | 34.17 | 19.71 | 0.00 | 19.71 |
Maximum of Months | 514.00 | 22.73 | 508.50 | 23.49 | 508.50 | 23.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 502.00 | 19.79 | 502.00 | 19.79 |
February | 454.00 | 19.89 | 454.00 | 19.89 | 454.00 | 19.89 |
March | 514.00 | 20.27 | 485.33 | 20.25 | 485.33 | 20.24 |
April | 485.00 | 20.93 | 230.67 | 20.69 | 230.67 | 20.57 |
May | 482.50 | 22.59 | 4.83 | 22.57 | 4.83 | 22.55 |
June | 157.83 | 23.12 | 124.17 | 23.65 | 0.00 | 23.65 |
July | 105.17 | 22.99 | 236.33 | 23.87 | 0.00 | 23.87 |
August | 329.00 | 22.64 | 73.67 | 22.91 | 3.00 | 22.89 |
September | 485.00 | 21.47 | 79.83 | 21.35 | 79.83 | 21.25 |
October | 502.00 | 20.36 | 399.33 | 20.28 | 399.33 | 20.24 |
November | 489.00 | 19.81 | 489.00 | 19.81 | 489.00 | 19.81 |
December | 497.00 | 19.77 | 497.00 | 19.77 | 497.00 | 19.77 |
Annual Sum or Average | 5002.50 | 20.81 | 3576.17 | 20.68 | 3145.00 | 20.49 |
Minimum of Months | 105.17 | 19.77 | 4.83 | 19.77 | 0.00 | 19.77 |
Maximum of Months | 514.00 | 23.12 | 502.00 | 23.87 | 502.00 | 23.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.57 | 427.00 | 19.57 | 427.00 | 19.57 |
February | 385.00 | 19.73 | 380.83 | 19.72 | 380.83 | 19.72 |
March | 433.00 | 20.39 | 364.17 | 20.30 | 364.17 | 20.26 |
April | 387.17 | 21.35 | 154.50 | 21.08 | 150.33 | 20.90 |
May | 262.50 | 22.60 | 69.50 | 22.98 | 3.50 | 23.00 |
June | 122.33 | 22.97 | 186.33 | 23.81 | 0.50 | 23.82 |
July | 88.67 | 23.05 | 264.50 | 24.11 | 6.50 | 24.16 |
August | 203.17 | 22.58 | 132.83 | 23.24 | 2.33 | 23.22 |
September | 375.67 | 21.64 | 59.83 | 21.60 | 49.17 | 21.48 |
October | 426.83 | 20.39 | 309.83 | 20.25 | 309.83 | 20.19 |
November | 417.00 | 19.59 | 417.00 | 19.59 | 417.00 | 19.59 |
December | 422.00 | 19.53 | 422.00 | 19.53 | 422.00 | 19.53 |
Annual Sum or Average | 3950.33 | 20.67 | 3188.33 | 20.71 | 2533.17 | 20.48 |
Minimum of Months | 88.67 | 19.53 | 59.83 | 19.53 | 0.50 | 19.53 |
Maximum of Months | 433.00 | 23.05 | 427.00 | 24.11 | 427.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 501.50 | 19.82 | 501.50 | 19.82 |
February | 454.00 | 20.19 | 411.67 | 20.11 | 411.67 | 20.08 |
March | 488.67 | 20.86 | 338.50 | 20.63 | 338.50 | 20.53 |
April | 366.00 | 21.47 | 170.00 | 21.45 | 126.33 | 21.23 |
May | 314.50 | 22.35 | 95.17 | 22.79 | 7.83 | 22.75 |
June | 171.00 | 22.78 | 209.67 | 23.61 | 0.67 | 23.62 |
July | 140.50 | 22.82 | 280.33 | 23.88 | 5.83 | 23.93 |
August | 242.83 | 22.55 | 202.17 | 23.36 | 6.50 | 23.37 |
September | 387.17 | 21.69 | 92.67 | 21.89 | 41.67 | 21.78 |
October | 486.17 | 20.71 | 307.83 | 20.54 | 304.17 | 20.45 |
November | 489.00 | 19.91 | 482.83 | 19.90 | 482.83 | 19.89 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4538.83 | 20.89 | 3589.33 | 20.97 | 2724.50 | 20.73 |
Minimum of Months | 140.50 | 19.78 | 92.67 | 19.78 | 0.67 | 19.78 |
Maximum of Months | 502.00 | 22.82 | 501.50 | 23.88 | 501.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.78 | 502.00 | 19.78 | 502.00 | 19.78 |
February | 454.00 | 19.90 | 450.67 | 19.90 | 450.67 | 19.89 |
March | 514.00 | 20.35 | 457.33 | 20.29 | 457.33 | 20.27 |
April | 434.33 | 21.15 | 194.83 | 20.94 | 184.17 | 20.77 |
May | 406.33 | 22.32 | 38.50 | 22.42 | 9.17 | 22.38 |
June | 184.17 | 22.77 | 183.33 | 23.58 | 0.67 | 23.58 |
July | 159.67 | 22.66 | 246.00 | 23.68 | 0.33 | 23.68 |
August | 312.83 | 22.44 | 127.33 | 22.95 | 3.17 | 22.93 |
September | 462.33 | 21.47 | 78.83 | 21.39 | 73.00 | 21.29 |
October | 502.00 | 20.38 | 389.33 | 20.28 | 389.33 | 20.24 |
November | 489.00 | 19.80 | 489.00 | 19.80 | 489.00 | 19.80 |
December | 497.00 | 19.75 | 497.00 | 19.75 | 497.00 | 19.75 |
Annual Sum or Average | 4917.67 | 20.78 | 3654.17 | 20.74 | 3055.83 | 20.53 |
Minimum of Months | 159.67 | 19.75 | 38.50 | 19.75 | 0.33 | 19.75 |
Maximum of Months | 514.00 | 22.77 | 502.00 | 23.68 | 502.00 | 23.68 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.32514 | 10.59497 | -0.5707 | 13.37564 |
February | 454.00000 | 21.82623 | 11.89888 | -0.4288 | 10.25902 |
March | 514.00000 | 22.64067 | 12.73190 | -0.2219 | 6.90320 |
April | 485.00000 | 23.74729 | 14.92579 | 0.08706 | 5.99463 |
May | 508.00000 | 24.34661 | 20.77656 | -0.5515 | 11.76624 |
June | 496.00000 | 24.48170 | 32.63739 | -0.3739 | 8.62407 |
July | 497.00000 | 24.56850 | 40.90170 | -0.2856 | 7.57678 |
August | 514.00000 | 24.44886 | 36.02758 | -0.3683 | 8.58736 |
September | 485.00000 | 24.27651 | 26.58502 | -0.5640 | 12.41353 |
October | 502.00000 | 23.45604 | 18.94645 | 0.02597 | 5.79375 |
November | 489.00000 | 22.05225 | 10.10180 | -0.3905 | 9.02506 |
December | 497.00000 | 21.40135 | 9.31284 | -0.5537 | 12.07263 |
Annual Sum or Average | 5943.00000 | 23.22504 | 20.53947 | -0.3494 | 9.35631 |
Minimum of Months | 454.00000 | 21.32514 | 9.31284 | -0.5707 | 5.79375 |
Maximum of Months | 514.00000 | 24.56850 | 40.90170 | 0.08706 | 13.37564 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.53200 | 11.31776 | -0.7711 | 19.31160 |
February | 454.00000 | 20.85504 | 12.77172 | -0.6675 | 16.14308 |
March | 514.00000 | 21.48250 | 13.80477 | -0.4922 | 11.07984 |
April | 485.00000 | 22.65830 | 16.39647 | -0.1666 | 7.25207 |
May | 508.00000 | 23.76669 | 22.04421 | -0.7562 | 17.79866 |
June | 496.00000 | 24.19039 | 33.64918 | -0.4905 | 10.38377 |
July | 497.00000 | 24.25028 | 41.95839 | -0.4155 | 8.96168 |
August | 514.00000 | 24.07187 | 37.38215 | -0.5260 | 11.39937 |
September | 485.00000 | 23.26061 | 29.22386 | -0.9195 | 24.19173 |
October | 502.00000 | 21.79933 | 20.91178 | -0.3649 | 9.15619 |
November | 489.00000 | 20.82071 | 10.77832 | -0.6930 | 16.29534 |
December | 497.00000 | 20.58148 | 10.03463 | -0.7682 | 18.59076 |
Annual Sum or Average | 5943.00000 | 22.36896 | 21.77572 | -0.5852 | 14.18112 |
Minimum of Months | 454.00000 | 20.53200 | 10.03463 | -0.9195 | 7.25207 |
Maximum of Months | 514.00000 | 24.25028 | 41.95839 | -0.1666 | 24.19173 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05766 | 11.81023 | -0.9364 | 25.62252 |
February | 454.00000 | 20.19237 | 13.38348 | -0.8683 | 23.19713 |
March | 514.00000 | 20.67249 | 14.07856 | -0.7160 | 17.29321 |
April | 485.00000 | 21.61597 | 16.59166 | -0.4184 | 11.10000 |
May | 508.00000 | 23.11343 | 22.72623 | -0.9679 | 26.42180 |
June | 496.00000 | 23.88804 | 34.04888 | -0.5847 | 12.91284 |
July | 497.00000 | 23.93074 | 42.26770 | -0.5193 | 11.28265 |
August | 514.00000 | 23.52768 | 38.21796 | -0.7112 | 17.21283 |
September | 485.00000 | 22.00209 | 30.87416 | -1.3413 | 43.24964 |
October | 502.00000 | 20.69417 | 21.67177 | -0.6570 | 15.90463 |
November | 489.00000 | 20.10986 | 11.48161 | -0.9136 | 24.61574 |
December | 497.00000 | 20.05010 | 10.67310 | -0.9479 | 25.87426 |
Annual Sum or Average | 5943.00000 | 21.66931 | 22.40361 | -0.7974 | 21.16859 |
Minimum of Months | 454.00000 | 20.05010 | 10.67310 | -1.3413 | 11.10000 |
Maximum of Months | 514.00000 | 23.93074 | 42.26770 | -0.4184 | 43.24964 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68692 | 11.41129 | -1.1572 | 34.72257 |
February | 454.00000 | 19.78624 | 13.03592 | -1.0890 | 31.98113 |
March | 514.00000 | 20.09291 | 13.79173 | -0.9480 | 26.00993 |
April | 485.00000 | 20.53139 | 16.81839 | -0.6933 | 17.46285 |
May | 508.00000 | 21.86248 | 23.57466 | -1.3176 | 42.08604 |
June | 496.00000 | 23.24012 | 35.39828 | -0.7230 | 17.62131 |
July | 497.00000 | 23.25464 | 43.64328 | -0.6719 | 16.03892 |
August | 514.00000 | 22.32061 | 40.69755 | -1.0472 | 30.32784 |
September | 485.00000 | 20.91582 | 32.20304 | -1.7164 | 61.80690 |
October | 502.00000 | 20.03587 | 21.73045 | -0.8884 | 23.94818 |
November | 489.00000 | 19.71576 | 11.10246 | -1.1393 | 33.98882 |
December | 497.00000 | 19.66238 | 10.29083 | -1.1780 | 35.60533 |
Annual Sum or Average | 5943.00000 | 20.93728 | 22.90193 | -1.0466 | 30.92431 |
Minimum of Months | 454.00000 | 19.66238 | 10.29083 | -1.7164 | 16.03892 |
Maximum of Months | 514.00000 | 23.25464 | 43.64328 | -0.6719 | 61.80690 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67776 | 11.64908 | -1.1586 | 34.80534 |
February | 454.00000 | 19.79380 | 13.26632 | -1.0673 | 31.18596 |
March | 514.00000 | 20.21530 | 13.94753 | -0.8596 | 22.97307 |
April | 485.00000 | 21.14334 | 16.47665 | -0.5017 | 14.03115 |
May | 508.00000 | 22.90741 | 22.29915 | -0.9036 | 26.24746 |
June | 496.00000 | 23.61655 | 34.57102 | -0.5293 | 13.37381 |
July | 497.00000 | 23.72255 | 42.40560 | -0.4451 | 11.90109 |
August | 514.00000 | 22.99392 | 39.30474 | -0.7724 | 21.10714 |
September | 485.00000 | 21.33728 | 31.76673 | -1.5339 | 53.17042 |
October | 502.00000 | 20.10911 | 21.90675 | -0.8462 | 22.51989 |
November | 489.00000 | 19.70714 | 11.34829 | -1.1391 | 34.01434 |
December | 497.00000 | 19.65141 | 10.52711 | -1.1833 | 35.84554 |
Annual Sum or Average | 5943.00000 | 21.25466 | 22.54244 | -0.9095 | 26.67270 |
Minimum of Months | 454.00000 | 19.65141 | 10.52711 | -1.5339 | 11.90109 |
Maximum of Months | 514.00000 | 23.72255 | 42.40560 | -0.4451 | 53.17042 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70047 | 11.41018 | -1.1330 | 33.80240 |
February | 454.00000 | 19.94554 | 12.91278 | -0.9855 | 28.18707 |
March | 514.00000 | 20.64838 | 13.39606 | -0.7246 | 20.08487 |
April | 485.00000 | 21.72077 | 15.60780 | -0.3421 | 13.26375 |
May | 508.00000 | 22.69090 | 22.35341 | -0.9907 | 30.82956 |
June | 496.00000 | 23.41118 | 34.84516 | -0.6103 | 16.29521 |
July | 497.00000 | 23.51941 | 42.79266 | -0.5254 | 14.49097 |
August | 514.00000 | 23.01066 | 39.01992 | -0.7545 | 22.23103 |
September | 485.00000 | 21.68837 | 30.83410 | -1.3985 | 47.87901 |
October | 502.00000 | 20.35710 | 21.32751 | -0.7624 | 20.45900 |
November | 489.00000 | 19.75276 | 11.08279 | -1.0962 | 32.34965 |
December | 497.00000 | 19.66514 | 10.29574 | -1.1705 | 35.31124 |
Annual Sum or Average | 5943.00000 | 21.35607 | 22.24567 | -0.8730 | 26.20819 |
Minimum of Months | 454.00000 | 19.66514 | 10.29574 | -1.3985 | 13.26375 |
Maximum of Months | 514.00000 | 23.51941 | 42.79266 | -0.3421 | 47.87901 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67629 | 11.65634 | -1.1613 | 34.90741 |
February | 454.00000 | 19.78644 | 13.27914 | -1.0816 | 31.73005 |
March | 514.00000 | 20.14954 | 14.02268 | -0.9123 | 24.79932 |
April | 485.00000 | 21.09925 | 16.51881 | -0.5248 | 15.44068 |
May | 508.00000 | 22.26085 | 23.26967 | -1.1652 | 36.65971 |
June | 496.00000 | 23.35894 | 35.31506 | -0.6462 | 17.07383 |
July | 497.00000 | 23.34317 | 43.57642 | -0.6126 | 15.80059 |
August | 514.00000 | 22.63857 | 40.25775 | -0.9178 | 26.49549 |
September | 485.00000 | 21.14666 | 32.10152 | -1.6206 | 57.36095 |
October | 502.00000 | 20.05249 | 22.00743 | -0.8767 | 23.61757 |
November | 489.00000 | 19.70888 | 11.35523 | -1.1381 | 33.97689 |
December | 497.00000 | 19.65065 | 10.53532 | -1.1838 | 35.86575 |
Annual Sum or Average | 5943.00000 | 21.08520 | 22.91645 | -0.9855 | 29.42015 |
Minimum of Months | 454.00000 | 19.65065 | 10.53532 | -1.6206 | 15.44068 |
Maximum of Months | 514.00000 | 23.35894 | 43.57642 | -0.5248 | 57.36095 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.72712 | 11.03361 | -1.1504 | 34.27122 |
February | 454.00000 | 19.78551 | 12.67770 | -1.1129 | 32.77279 |
March | 514.00000 | 20.12213 | 13.81028 | -0.9782 | 26.75703 |
April | 485.00000 | 20.50006 | 17.13579 | -0.7455 | 18.15961 |
May | 508.00000 | 21.51559 | 24.33213 | -1.4920 | 50.58044 |
June | 496.00000 | 22.95939 | 36.42290 | -0.8739 | 22.12174 |
July | 497.00000 | 23.29449 | 44.41742 | -0.7010 | 16.29028 |
August | 514.00000 | 22.67263 | 40.38641 | -0.9506 | 25.64740 |
September | 485.00000 | 21.32309 | 31.42079 | -1.5372 | 52.96949 |
October | 502.00000 | 20.45962 | 21.31844 | -0.7421 | 17.94514 |
November | 489.00000 | 19.84659 | 10.73967 | -1.0699 | 30.74001 |
December | 497.00000 | 19.75040 | 9.77962 | -1.1394 | 33.69534 |
Annual Sum or Average | 5943.00000 | 21.00844 | 22.88702 | -1.0404 | 30.13073 |
Minimum of Months | 454.00000 | 19.72712 | 9.77962 | -1.5372 | 16.29028 |
Maximum of Months | 514.00000 | 23.29449 | 44.41742 | -0.7010 | 52.96949 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71151 | 11.33393 | -1.1572 | 34.59153 |
February | 454.00000 | 19.80754 | 12.97525 | -1.0921 | 31.92254 |
March | 514.00000 | 20.28019 | 14.03893 | -0.8846 | 23.12212 |
April | 485.00000 | 21.12304 | 16.89085 | -0.5386 | 13.54170 |
May | 508.00000 | 23.00034 | 22.57335 | -0.9329 | 26.40476 |
June | 496.00000 | 23.67586 | 34.95425 | -0.5735 | 13.74803 |
July | 497.00000 | 23.96981 | 42.58351 | -0.4044 | 10.23659 |
August | 514.00000 | 23.54534 | 38.54780 | -0.6082 | 14.84669 |
September | 485.00000 | 22.02737 | 30.54962 | -1.2706 | 40.85088 |
October | 502.00000 | 20.62287 | 21.49827 | -0.6804 | 16.26119 |
November | 489.00000 | 19.82889 | 11.12263 | -1.0746 | 30.97618 |
December | 497.00000 | 19.72709 | 10.08178 | -1.1514 | 34.24885 |
Annual Sum or Average | 5943.00000 | 21.45984 | 22.35048 | -0.8615 | 24.13033 |
Minimum of Months | 454.00000 | 19.71151 | 10.08178 | -1.2706 | 10.23659 |
Maximum of Months | 514.00000 | 23.96981 | 42.58351 | -0.4044 | 40.85088 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.80442 | 10.84048 | -1.4965 | 49.64333 |
February | 454.00000 | 18.65288 | 12.23058 | -1.2565 | 39.15722 |
March | 514.00000 | 19.55258 | 12.92563 | -0.9631 | 26.93835 |
April | 485.00000 | 21.23331 | 15.68109 | -0.4443 | 13.05850 |
May | 508.00000 | 22.36306 | 22.82009 | -1.1270 | 34.85076 |
June | 496.00000 | 23.25995 | 35.43228 | -0.7114 | 18.20185 |
July | 497.00000 | 23.62155 | 43.17032 | -0.5246 | 13.46152 |
August | 514.00000 | 23.28894 | 38.56867 | -0.6552 | 17.71931 |
September | 485.00000 | 21.99936 | 29.62932 | -1.2265 | 39.59664 |
October | 502.00000 | 20.33729 | 20.39213 | -0.6947 | 17.98215 |
November | 489.00000 | 18.33503 | 10.21895 | -1.3250 | 42.20308 |
December | 497.00000 | 17.61690 | 9.50598 | -1.5435 | 51.59015 |
Annual Sum or Average | 5943.00000 | 20.69033 | 21.87772 | -0.9951 | 30.27384 |
Minimum of Months | 454.00000 | 17.61690 | 9.50598 | -1.5435 | 13.05850 |
Maximum of Months | 514.00000 | 23.62155 | 43.17032 | -0.4443 | 51.59015 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70734 | 11.33674 | -1.1606 | 34.73288 |
February | 454.00000 | 19.77995 | 12.98947 | -1.1112 | 32.73329 |
March | 514.00000 | 20.16494 | 14.13843 | -0.9480 | 25.58557 |
April | 485.00000 | 21.05405 | 16.94443 | -0.5616 | 14.38549 |
May | 508.00000 | 22.10520 | 23.86565 | -1.2719 | 40.42739 |
June | 496.00000 | 23.36620 | 35.76828 | -0.7093 | 17.69327 |
July | 497.00000 | 23.55108 | 43.94542 | -0.5899 | 13.96334 |
August | 514.00000 | 23.16636 | 39.56458 | -0.7621 | 19.54116 |
September | 485.00000 | 21.67392 | 31.15580 | -1.4029 | 46.58921 |
October | 502.00000 | 20.49285 | 21.66731 | -0.7281 | 17.59305 |
November | 489.00000 | 19.83132 | 11.13105 | -1.0736 | 30.93366 |
December | 497.00000 | 19.72592 | 10.09178 | -1.1520 | 34.27463 |
Annual Sum or Average | 5943.00000 | 21.23190 | 22.81030 | -0.9546 | 27.31116 |
Minimum of Months | 454.00000 | 19.70734 | 10.09178 | -1.4029 | 13.96334 |
Maximum of Months | 514.00000 | 23.55108 | 43.94542 | -0.5616 | 46.58921 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78975 | 11.01065 | -1.0842 | 31.55404 |
February | 454.00000 | 19.89339 | 12.56739 | -1.0127 | 28.76305 |
March | 514.00000 | 20.27062 | 13.53012 | -0.8598 | 22.29169 |
April | 485.00000 | 20.92776 | 16.74141 | -0.5684 | 13.93942 |
May | 508.00000 | 22.65446 | 22.91481 | -1.0713 | 30.53600 |
June | 496.00000 | 23.80137 | 34.54930 | -0.5610 | 12.46495 |
July | 497.00000 | 23.84441 | 42.74026 | -0.4979 | 10.93550 |
August | 514.00000 | 23.12236 | 39.39064 | -0.7973 | 20.40219 |
September | 485.00000 | 21.47336 | 31.46837 | -1.4832 | 50.27128 |
October | 502.00000 | 20.36326 | 21.18157 | -0.7568 | 18.87339 |
November | 489.00000 | 19.81036 | 10.56234 | -1.0575 | 30.45729 |
December | 497.00000 | 19.76590 | 9.79470 | -1.1017 | 32.21180 |
Annual Sum or Average | 5943.00000 | 21.32466 | 22.29533 | -0.9028 | 25.15439 |
Minimum of Months | 454.00000 | 19.76590 | 9.79470 | -1.4832 | 10.93550 |
Maximum of Months | 514.00000 | 23.84441 | 42.74026 | -0.4979 | 50.27128 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.56773 | 10.89767 | -1.1347 | 33.90812 |
February | 385.00000 | 19.73007 | 12.45296 | -1.0358 | 29.88971 |
March | 433.00000 | 20.39460 | 13.37443 | -0.7871 | 20.09292 |
April | 410.00000 | 21.52402 | 15.97065 | -0.3955 | 11.72239 |
May | 430.00000 | 23.22637 | 21.68973 | -0.8008 | 22.10733 |
June | 418.00000 | 23.83755 | 34.14638 | -0.4734 | 11.61849 |
July | 422.00000 | 23.99225 | 42.13851 | -0.3716 | 10.03003 |
August | 433.00000 | 23.37810 | 38.49140 | -0.6501 | 16.63185 |
September | 410.00000 | 21.89371 | 30.70484 | -1.3145 | 43.30157 |
October | 427.00000 | 20.39315 | 21.08609 | -0.7348 | 18.50128 |
November | 417.00000 | 19.59042 | 10.50566 | -1.1062 | 32.72255 |
December | 422.00000 | 19.52760 | 9.73986 | -1.1565 | 34.78680 |
Annual Sum or Average | 5034.00000 | 21.43429 | 21.83544 | -0.8281 | 23.69263 |
Minimum of Months | 385.00000 | 19.52760 | 9.73986 | -1.3145 | 10.03003 |
Maximum of Months | 433.00000 | 23.99225 | 42.13851 | -0.3716 | 43.30157 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82391 | 10.73238 | -1.0562 | 30.45631 |
February | 454.00000 | 20.18933 | 12.10434 | -0.8828 | 24.11362 |
March | 514.00000 | 21.01721 | 12.76648 | -0.6006 | 16.30303 |
April | 485.00000 | 22.15948 | 15.25953 | -0.2109 | 10.80351 |
May | 508.00000 | 23.07330 | 21.90709 | -0.8523 | 24.60950 |
June | 496.00000 | 23.68472 | 34.41209 | -0.5240 | 13.01382 |
July | 497.00000 | 23.80452 | 42.47181 | -0.4316 | 11.37819 |
August | 514.00000 | 23.40327 | 38.34949 | -0.6132 | 16.72330 |
September | 485.00000 | 22.21377 | 29.92040 | -1.1767 | 37.92231 |
October | 502.00000 | 20.81633 | 20.43326 | -0.6076 | 15.52431 |
November | 489.00000 | 19.90831 | 10.22450 | -1.0028 | 28.33315 |
December | 497.00000 | 19.77754 | 9.53460 | -1.0936 | 31.88019 |
Annual Sum or Average | 5943.00000 | 21.67000 | 21.60030 | -0.7528 | 21.69750 |
Minimum of Months | 454.00000 | 19.77754 | 9.53460 | -1.1767 | 10.80351 |
Maximum of Months | 514.00000 | 23.80452 | 42.47181 | -0.2109 | 37.92231 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78245 | 11.04795 | -1.0900 | 31.80369 |
February | 454.00000 | 19.89926 | 12.59044 | -1.0062 | 28.53011 |
March | 514.00000 | 20.34667 | 13.54210 | -0.8225 | 21.13014 |
April | 485.00000 | 21.46101 | 16.26221 | -0.4082 | 12.43731 |
May | 508.00000 | 22.68873 | 22.81958 | -1.0146 | 29.59451 |
June | 496.00000 | 23.65976 | 34.87637 | -0.5520 | 13.57888 |
July | 497.00000 | 23.66669 | 43.20754 | -0.5082 | 12.30802 |
August | 514.00000 | 23.08127 | 39.51483 | -0.7629 | 20.16669 |
September | 485.00000 | 21.60119 | 31.32711 | -1.4173 | 47.61835 |
October | 502.00000 | 20.37874 | 21.25125 | -0.7482 | 18.66015 |
November | 489.00000 | 19.80359 | 10.59214 | -1.0589 | 30.54685 |
December | 497.00000 | 19.75267 | 9.82493 | -1.1104 | 32.59765 |
Annual Sum or Average | 5943.00000 | 21.35736 | 22.33048 | -0.8735 | 24.84667 |
Minimum of Months | 454.00000 | 19.75267 | 9.82493 | -1.4173 | 12.30802 |
Maximum of Months | 514.00000 | 23.66669 | 43.20754 | -0.4082 | 47.61835 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.257446E+12 | 0.00 | 636.84 | 363928.02 | 19-JAN-06:01 | 0.00 | 40.82 | 56.88 | 1.34 | 0.00 | 0.15 | 0.58 | 19-JAN-06:01 |
February | 0.186847E+12 | 0.00 | 552.18 | 358092.03 | 09-FEB-06:01 | 0.00 | 38.89 | 55.82 | 1.01 | 0.00 | 0.12 | 0.57 | 09-FEB-06:01 |
March | 0.142178E+12 | 0.00 | 557.62 | 381136.79 | 23-MAR-05:01 | 0.00 | 35.47 | 53.51 | 0.61 | 0.00 | 0.08 | 0.61 | 23-MAR-05:01 |
April | 0.400920E+11 | 0.00 | 405.84 | 386889.19 | 06-APR-05:01 | 0.00 | 29.81 | 45.56 | 0.16 | 0.00 | 0.02 | 0.62 | 06-APR-05:01 |
May | 0.359799E+10 | 0.00 | 147.54 | 193464.70 | 27-MAY-06:03 | 0.00 | 37.27 | 42.04 | 0.01 | 0.00 | 0.00 | 0.31 | 27-MAY-06:03 |
June | 0.397674E+09 | 0.00 | 35.19 | 36790.79 | 26-JUN-06:03 | 0.00 | 40.48 | 41.50 | 0.00 | 0.00 | 0.00 | 0.06 | 26-JUN-06:03 |
July | 0.306227E+09 | 0.00 | 42.41 | 26966.15 | 17-JUL-06:07 | 0.00 | 38.14 | 39.36 | 0.00 | 0.00 | 0.00 | 0.04 | 17-JUL-06:07 |
August | 0.142050E+10 | 0.00 | 71.28 | 260286.47 | 31-AUG-06:03 | 0.00 | 36.49 | 38.97 | 0.01 | 0.00 | 0.00 | 0.42 | 31-AUG-06:03 |
September | 0.165696E+11 | 0.00 | 304.33 | 361223.47 | 30-SEP-05:01 | 0.00 | 27.47 | 40.02 | 0.06 | 0.00 | 0.01 | 0.58 | 30-SEP-05:01 |
October | 0.910353E+11 | 0.00 | 467.03 | 368892.07 | 20-OCT-05:01 | 0.00 | 31.41 | 48.27 | 0.35 | 0.00 | 0.05 | 0.59 | 20-OCT-05:01 |
November | 0.219010E+12 | 0.00 | 597.96 | 353320.54 | 18-NOV-06:01 | 0.00 | 40.22 | 56.41 | 1.10 | 0.00 | 0.14 | 0.56 | 18-NOV-06:01 |
December | 0.265563E+12 | 0.00 | 654.72 | 316806.57 | 27-DEC-05:01 | 0.00 | 41.25 | 57.47 | 1.42 | 0.00 | 0.16 | 0.51 | 27-DEC-05:01 |
Annual Sum or Average | 0.122446E+13 | 0.00 | 4472.94 | 0.00 | 36.48 | 47.94 | 0.50 | 0.00 | 0.06 | ||||
Minimum of Months | 0.306227E+09 | 0.00 | 35.19 | 26966.15 | 0.00 | 27.47 | 38.97 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.265563E+12 | 0.00 | 654.72 | 386889.19 | 0.00 | 41.25 | 57.47 | 1.42 | 0.00 | 0.16 | 0.62 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 117997.87 | 33786.87 | 0.06 | 117997.87 | -0.0 | 0.00 | 0.02 | 01-JAN-20:02 | 0.00 | 01-JAN-00:02 | 552.21 | 01-JAN-20:02 | 552.21 | 01-JAN-20:02 | 0.00 | 01-JAN-20:02 | 158.10 | 01-JAN-20:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 14048867.72 | 3978072.01 | 2.83 | 14048867.72 | -0.0 | 0.00 | 0.11 | 22-APR-14:00 | 0.00 | 01-APR-00:10 | 2911.00 | 22-APR-14:00 | 2911.00 | 22-APR-14:00 | 0.00 | 22-APR-14:30 | 816.73 | 22-APR-14:00 | 0.00 |
May | 0.465280E+10 | 0.118511E+10 | 134.17 | 0.465061E+10 | 2187360.68 | 0.00 | 1.00 | 31-MAY-15:30 | 0.00 | 01-MAY-00:10 | 37276.74 | 31-MAY-16:00 | 37276.74 | 31-MAY-16:00 | 254.11 | 31-MAY-21:00 | 8266.60 | 31-MAY-16:00 | 0.00 |
June | 0.233321E+11 | 0.556372E+10 | 305.77 | 0.223059E+11 | 0.102621E+10 | 0.00 | 1.00 | 12-JUN-14:00 | 0.00 | 01-JUN-00:10 | 63879.42 | 30-JUN-14:30 | 60898.58 | 30-JUN-14:40 | 13252.40 | 30-JUN-18:50 | 15663.47 | 30-JUN-14:50 | 0.00 |
July | 0.326762E+11 | 0.759489E+10 | 320.98 | 0.299392E+11 | 0.273703E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 66120.44 | 11-JUL-16:00 | 65209.21 | 12-JUL-16:00 | 34267.80 | 03-JUL-15:00 | 16607.06 | 21-JUL-16:00 | 0.00 |
August | 0.184641E+11 | 0.437139E+10 | 245.66 | 0.169959E+11 | 0.146818E+10 | 0.00 | 1.00 | 02-AUG-12:05 | 0.00 | 01-AUG-00:10 | 63303.38 | 11-AUG-16:00 | 63303.38 | 11-AUG-16:00 | 11474.22 | 03-AUG-05:12 | 14639.50 | 11-AUG-16:00 | 0.00 |
September | 0.376694E+09 | 0.103704E+09 | 27.33 | 0.358873E+09 | 17821169.52 | 0.00 | 0.41 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 12002.61 | 07-SEP-16:00 | 12002.61 | 07-SEP-16:00 | 828.75 | 02-SEP-14:13 | 3126.35 | 07-SEP-16:00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.795161E+11 | 0.188228E+11 | 1036.81 | 0.742646E+11 | 0.525143E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.326762E+11 | 0.759489E+10 | 320.98 | 0.299392E+11 | 0.273703E+10 | 0.00 | 1.00 | 0.00 | 66120.44 | 65209.21 | 34267.80 | 16607.06 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 53710.67 | 15388.09 | 0.03 | 53710.67 | 0.00 | 0.00 | 0.02 | 30-JAN-03:32 | 0.00 | 01-JAN-00:02 | 447.59 | 30-JAN-03:32 | 447.59 | 30-JAN-03:32 | 0.00 | 30-JAN-03:32 | 128.23 | 30-JAN-03:32 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 16576571.10 | 4686438.90 | 3.17 | 16576571.10 | -0.0 | 0.00 | 0.11 | 22-APR-14:00 | 0.00 | 01-APR-00:10 | 2947.70 | 22-APR-14:00 | 2947.70 | 22-APR-14:00 | 0.00 | 22-APR-15:50 | 825.72 | 22-APR-14:00 | 0.00 |
May | 0.469459E+10 | 0.119616E+10 | 145.83 | 0.469124E+10 | 3347585.18 | 0.00 | 1.00 | 31-MAY-14:50 | 0.00 | 01-MAY-00:10 | 38487.44 | 31-MAY-16:00 | 38487.44 | 31-MAY-16:00 | 268.45 | 31-MAY-21:00 | 8533.84 | 31-MAY-16:00 | 0.00 |
June | 0.228225E+11 | 0.544339E+10 | 317.10 | 0.218154E+11 | 0.100704E+10 | 0.00 | 1.00 | 12-JUN-13:50 | 0.00 | 01-JUN-00:10 | 69009.94 | 30-JUN-12:05 | 62972.32 | 30-JUN-14:30 | 12718.25 | 30-JUN-11:00 | 16095.64 | 30-JUN-14:30 | 0.00 |
July | 0.305694E+11 | 0.713644E+10 | 331.06 | 0.279703E+11 | 0.259911E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 63463.21 | 11-JUL-15:50 | 63147.43 | 21-JUL-14:05 | 32446.87 | 03-JUL-15:00 | 15540.47 | 21-JUL-16:00 | 0.00 |
August | 0.164733E+11 | 0.392590E+10 | 247.46 | 0.150428E+11 | 0.143051E+10 | 0.00 | 1.00 | 02-AUG-12:05 | 0.00 | 01-AUG-00:10 | 58222.55 | 11-AUG-15:40 | 58222.55 | 11-AUG-15:40 | 8605.81 | 03-AUG-12:03 | 13415.89 | 11-AUG-16:00 | 0.00 |
September | 0.315393E+09 | 87050530.03 | 26.50 | 0.298753E+09 | 16640010.57 | 0.00 | 0.37 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 10210.90 | 07-SEP-16:00 | 10210.90 | 07-SEP-16:00 | 767.99 | 02-SEP-14:02 | 2686.59 | 07-SEP-16:00 | 0.00 |
October | 37463.67 | 10746.58 | 0.03 | 37463.67 | 0.00 | 0.00 | 0.01 | 05-OCT-06:04 | 0.00 | 01-OCT-00:10 | 312.20 | 05-OCT-06:04 | 312.20 | 05-OCT-06:04 | 0.00 | 05-OCT-06:04 | 89.55 | 05-OCT-06:04 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.748918E+11 | 0.177936E+11 | 1071.18 | 0.698352E+11 | 0.505664E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.305694E+11 | 0.713644E+10 | 331.06 | 0.279703E+11 | 0.259911E+10 | 0.00 | 1.00 | 0.00 | 69009.94 | 63147.43 | 32446.87 | 16095.64 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1574001.17 | 449439.36 | 0.40 | 1574001.17 | -0.0 | 0.00 | 0.05 | 10-JAN-06:17 | 0.00 | 01-JAN-00:02 | 1923.70 | 10-JAN-06:17 | 1923.70 | 10-JAN-06:17 | 0.00 | 10-JAN-06:08 | 547.15 | 10-JAN-06:17 | 0.00 |
February | 1900867.26 | 543870.62 | 0.74 | 1900867.26 | -0.0 | 0.00 | 0.04 | 06-FEB-06:06 | 0.00 | 01-FEB-00:05 | 1406.32 | 06-FEB-06:06 | 1406.32 | 06-FEB-06:06 | 0.00 | 08-FEB-05:07 | 401.21 | 06-FEB-06:06 | 0.00 |
March | 1907717.17 | 546942.38 | 1.00 | 1907717.17 | 0.00 | 0.00 | 0.03 | 08-MAR-06:03 | 0.00 | 01-MAR-00:03 | 1044.12 | 08-MAR-06:03 | 1044.12 | 08-MAR-06:03 | 0.00 | 06-MAR-06:08 | 298.52 | 08-MAR-06:03 | 0.00 |
April | 13938093.36 | 3965116.65 | 2.94 | 13938093.36 | -0.0 | 0.00 | 0.08 | 22-APR-14:00 | 0.00 | 01-APR-00:10 | 3106.58 | 22-APR-14:00 | 3106.58 | 22-APR-14:00 | 0.00 | 10-APR-04:47 | 877.50 | 22-APR-14:00 | 0.00 |
May | 0.467137E+10 | 0.123320E+10 | 137.29 | 0.464767E+10 | 23694821.75 | 0.00 | 0.83 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 | 39729.78 | 31-MAY-16:00 | 39729.78 | 31-MAY-16:00 | 892.02 | 31-MAY-09:00 | 9249.05 | 31-MAY-16:00 | 0.00 |
June | 0.239426E+11 | 0.593034E+10 | 309.60 | 0.223998E+11 | 0.154285E+10 | 0.00 | 1.00 | 13-JUN-12:50 | 0.00 | 01-JUN-00:10 | 71967.68 | 30-JUN-12:30 | 68544.67 | 30-JUN-14:30 | 14607.82 | 30-JUN-19:00 | 17344.34 | 30-JUN-14:40 | 0.00 |
July | 0.329502E+11 | 0.798360E+10 | 324.62 | 0.291404E+11 | 0.380980E+10 | 0.00 | 1.00 | 03-JUL-15:00 | 0.00 | 01-JUL-00:10 | 69021.23 | 21-JUL-14:40 | 69021.23 | 21-JUL-14:40 | 31037.95 | 03-JUL-15:00 | 16901.47 | 21-JUL-15:40 | 0.00 |
August | 0.176237E+11 | 0.436746E+10 | 237.87 | 0.152923E+11 | 0.233142E+10 | 0.00 | 1.00 | 11-AUG-14:00 | 0.00 | 01-AUG-00:10 | 60991.93 | 11-AUG-15:30 | 60991.93 | 11-AUG-15:30 | 10784.66 | 03-AUG-15:00 | 14066.71 | 11-AUG-16:00 | 0.00 |
September | 0.299000E+09 | 83561223.65 | 23.50 | 0.267664E+09 | 31335785.78 | 0.00 | 0.22 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 8825.51 | 07-SEP-16:00 | 8825.51 | 07-SEP-16:00 | 1298.21 | 02-SEP-15:00 | 2412.53 | 07-SEP-16:00 | 0.00 |
October | 3533004.88 | 1012754.71 | 1.84 | 3417956.87 | 115048.01 | 0.00 | 0.04 | 23-OCT-05:04 | 0.00 | 01-OCT-00:10 | 1432.39 | 23-OCT-05:04 | 1432.39 | 23-OCT-05:04 | 44.52 | 09-OCT-19:40 | 408.59 | 23-OCT-05:04 | 0.00 |
November | 1859336.16 | 532179.10 | 0.71 | 1859336.16 | 0.00 | 0.00 | 0.03 | 18-NOV-06:01 | 0.00 | 01-NOV-00:10 | 1319.06 | 18-NOV-06:01 | 1319.06 | 18-NOV-06:01 | 0.00 | 04-NOV-05:01 | 376.51 | 18-NOV-06:01 | 0.00 |
December | 1581708.17 | 452257.23 | 0.57 | 1581708.17 | 0.00 | 0.00 | 0.04 | 12-DEC-06:17 | 0.00 | 01-DEC-00:05 | 1567.84 | 12-DEC-06:17 | 1567.84 | 12-DEC-06:17 | 0.00 | 11-DEC-06:10 | 446.87 | 12-DEC-06:17 | 0.00 |
Annual Sum or Average | 0.795132E+11 | 0.196057E+11 | 1041.08 | 0.717740E+11 | 0.773922E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1574001.17 | 449439.36 | 0.40 | 1574001.17 | -0.0 | 0.00 | 0.03 | 0.00 | 1044.12 | 1044.12 | 0.00 | 298.52 | 0.00 | ||||||
Maximum of Months | 0.329502E+11 | 0.798360E+10 | 324.62 | 0.291404E+11 | 0.380980E+10 | 0.00 | 1.00 | 0.00 | 71967.68 | 69021.23 | 31037.95 | 17344.34 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.91 | 0.00 | 37.91 | 0.00 | 4490.80 | 0.00 | 0.00 | 0.00 |
February | 167.59 | 0.00 | 167.59 | 0.00 | 4113.91 | 0.00 | 0.00 | 0.00 |
March | 448.22 | 0.00 | 448.22 | 6.46 | 3222.92 | 0.00 | 0.00 | 0.00 |
April | 810.64 | 17.53 | 793.10 | 167.49 | 1737.33 | 0.00 | 0.00 | 0.00 |
May | 1241.49 | 196.18 | 1045.31 | 717.95 | 705.74 | 0.00 | 0.00 | 0.00 |
June | 1620.51 | 359.49 | 1261.02 | 1368.14 | 332.34 | 0.00 | 0.00 | 0.00 |
July | 1359.97 | 220.15 | 1139.81 | 1214.03 | 406.31 | 0.00 | 0.00 | 0.00 |
August | 868.51 | 48.00 | 820.51 | 570.92 | 655.04 | 0.00 | 0.00 | 0.00 |
September | 484.83 | 0.47 | 484.36 | 98.43 | 1390.88 | 0.00 | 0.00 | 0.00 |
October | 235.92 | 0.00 | 235.92 | 3.17 | 2614.44 | 0.00 | 0.00 | 0.00 |
November | 73.22 | 0.00 | 73.22 | 0.00 | 4389.69 | 0.00 | 0.00 | 0.00 |
December | 11.50 | 0.00 | 11.50 | 0.00 | 4706.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 615.56 | 70.46 | 545.09 | 347.70 | 2387.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.50 | 0.00 | 11.50 | 0.00 | 332.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1620.51 | 359.49 | 1261.02 | 1368.14 | 4706.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.37 | 20.74 | 45.63 | 0.63 | 2924.40 | 0.00 | 0.00 | 0.00 |
February | 367.35 | 175.03 | 192.32 | 117.10 | 2484.40 | 0.00 | 0.00 | 0.00 |
March | 1049.87 | 531.97 | 517.90 | 730.27 | 1844.74 | 0.00 | 0.00 | 0.00 |
April | 1443.63 | 731.00 | 712.62 | 1151.24 | 1005.74 | 0.00 | 0.00 | 0.00 |
May | 2098.14 | 1182.44 | 915.70 | 2139.60 | 501.77 | 0.00 | 0.00 | 0.00 |
June | 1929.11 | 899.52 | 1029.59 | 2059.17 | 254.32 | 0.00 | 0.00 | 0.00 |
July | 1832.79 | 888.48 | 944.31 | 2045.21 | 290.19 | 0.00 | 0.00 | 0.00 |
August | 1452.00 | 707.04 | 744.96 | 1512.53 | 431.30 | 0.00 | 0.00 | 0.00 |
September | 897.79 | 393.35 | 504.43 | 728.25 | 829.79 | 0.00 | 0.00 | 0.00 |
October | 473.72 | 189.99 | 283.73 | 262.76 | 1560.56 | 0.00 | 0.00 | 0.00 |
November | 100.52 | 34.94 | 65.58 | 1.69 | 2844.55 | 0.00 | 0.00 | 0.00 |
December | 14.35 | 3.39 | 10.95 | 0.00 | 3119.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 980.88 | 481.95 | 498.93 | 901.12 | 1502.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.35 | 3.39 | 10.95 | 0.00 | 254.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2098.14 | 1182.44 | 1029.59 | 2139.60 | 3119.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.68 | 301.51 | 155.16 | 171.34 | 4068.20 | 0.00 | 0.00 | 0.00 |
February | 1570.01 | 1093.63 | 476.39 | 1061.96 | 3263.20 | 0.00 | 0.00 | 0.00 |
March | 2691.60 | 1825.73 | 865.87 | 2295.07 | 2508.99 | 0.00 | 0.00 | 0.00 |
April | 3278.23 | 2039.24 | 1238.99 | 3345.28 | 1630.92 | 0.00 | 0.00 | 0.00 |
May | 2699.65 | 1396.98 | 1302.67 | 2891.05 | 910.89 | 0.00 | 0.00 | 0.00 |
June | 2464.38 | 1007.72 | 1456.67 | 2733.57 | 516.68 | 0.00 | 0.00 | 0.00 |
July | 2374.91 | 1032.40 | 1342.51 | 2747.16 | 535.56 | 0.00 | 0.00 | 0.00 |
August | 2461.68 | 1356.12 | 1105.56 | 2783.23 | 740.29 | 0.00 | 0.00 | 0.00 |
September | 1991.98 | 1200.27 | 791.71 | 1956.72 | 1262.57 | 0.00 | 0.00 | 0.00 |
October | 1436.52 | 912.66 | 523.85 | 1116.60 | 2125.82 | 0.00 | 0.00 | 0.00 |
November | 771.47 | 539.62 | 231.86 | 350.27 | 3781.05 | 0.00 | 0.00 | 0.00 |
December | 137.04 | 96.79 | 40.26 | 7.36 | 4521.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1860.66 | 1065.25 | 795.42 | 1790.89 | 2150.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.04 | 96.79 | 40.26 | 7.36 | 516.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3278.23 | 2039.24 | 1456.67 | 3345.28 | 4521.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 6.16 | 28.77 | 0.00 | 2960.94 | 0.00 | 0.00 | 0.00 |
February | 206.33 | 71.47 | 134.85 | 14.25 | 2592.22 | 0.00 | 0.00 | 0.00 |
March | 620.23 | 266.45 | 353.78 | 261.43 | 1951.84 | 0.00 | 0.00 | 0.00 |
April | 1473.94 | 764.50 | 709.44 | 1255.30 | 1087.50 | 0.00 | 0.00 | 0.00 |
May | 1433.06 | 653.31 | 779.74 | 1334.10 | 557.92 | 0.00 | 0.00 | 0.00 |
June | 1570.15 | 670.05 | 900.11 | 1641.05 | 320.62 | 0.00 | 0.00 | 0.00 |
July | 1313.64 | 497.36 | 816.28 | 1400.99 | 335.50 | 0.00 | 0.00 | 0.00 |
August | 1079.72 | 457.58 | 622.14 | 1066.37 | 474.29 | 0.00 | 0.00 | 0.00 |
September | 653.14 | 273.56 | 379.58 | 460.83 | 880.89 | 0.00 | 0.00 | 0.00 |
October | 255.43 | 76.56 | 178.87 | 62.45 | 1651.87 | 0.00 | 0.00 | 0.00 |
November | 102.05 | 36.90 | 65.15 | 3.08 | 2829.72 | 0.00 | 0.00 | 0.00 |
December | 9.17 | 0.95 | 8.22 | 0.00 | 3124.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 731.20 | 315.24 | 415.96 | 627.65 | 1558.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.17 | 0.95 | 8.22 | 0.00 | 320.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1570.15 | 764.50 | 900.11 | 1641.05 | 3124.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.64 | 0.00 | 12.64 | 0.00 | 1493.51 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 0.00 | 55.86 | 0.00 | 1359.03 | 0.00 | 0.00 | 0.00 |
March | 149.40 | 0.00 | 149.40 | 2.45 | 1058.84 | 0.00 | 0.00 | 0.00 |
April | 270.20 | 5.84 | 264.36 | 64.22 | 568.39 | 0.00 | 0.00 | 0.00 |
May | 413.82 | 65.39 | 348.42 | 262.01 | 225.73 | 0.00 | 0.00 | 0.00 |
June | 540.15 | 119.83 | 420.33 | 480.01 | 105.08 | 0.00 | 0.00 | 0.00 |
July | 453.31 | 73.38 | 379.92 | 414.78 | 134.18 | 0.00 | 0.00 | 0.00 |
August | 289.49 | 16.00 | 273.49 | 189.95 | 227.66 | 0.00 | 0.00 | 0.00 |
September | 161.61 | 0.16 | 161.45 | 30.45 | 494.06 | 0.00 | 0.00 | 0.00 |
October | 78.64 | 0.00 | 78.64 | 0.44 | 910.36 | 0.00 | 0.00 | 0.00 |
November | 24.40 | 0.00 | 24.40 | 0.00 | 1485.75 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 0.00 | 3.83 | 0.00 | 1574.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.18 | 23.49 | 181.69 | 121.09 | 800.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.83 | 0.00 | 3.83 | 0.00 | 105.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 540.15 | 119.83 | 420.33 | 480.01 | 1574.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.64 | 0.00 | 12.64 | 0.00 | 1493.61 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 0.00 | 55.86 | 0.00 | 1359.12 | 0.00 | 0.00 | 0.00 |
March | 149.41 | 0.00 | 149.41 | 2.45 | 1058.91 | 0.00 | 0.00 | 0.00 |
April | 270.21 | 5.84 | 264.37 | 64.22 | 568.42 | 0.00 | 0.00 | 0.00 |
May | 413.83 | 65.39 | 348.44 | 262.02 | 225.74 | 0.00 | 0.00 | 0.00 |
June | 540.18 | 119.83 | 420.35 | 480.02 | 105.09 | 0.00 | 0.00 | 0.00 |
July | 453.33 | 73.38 | 379.94 | 414.80 | 134.19 | 0.00 | 0.00 | 0.00 |
August | 289.51 | 16.00 | 273.51 | 189.96 | 227.68 | 0.00 | 0.00 | 0.00 |
September | 161.61 | 0.16 | 161.46 | 30.45 | 494.09 | 0.00 | 0.00 | 0.00 |
October | 78.64 | 0.00 | 78.64 | 0.44 | 910.41 | 0.00 | 0.00 | 0.00 |
November | 24.41 | 0.00 | 24.41 | 0.00 | 1485.84 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 0.00 | 3.83 | 0.00 | 1575.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.19 | 23.49 | 181.70 | 121.10 | 800.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.83 | 0.00 | 3.83 | 0.00 | 105.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 540.18 | 119.83 | 420.35 | 480.02 | 1575.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.64 | 0.00 | 12.64 | 0.00 | 1493.61 | 0.00 | 0.00 | 0.00 |
February | 55.86 | 0.00 | 55.86 | 0.00 | 1359.12 | 0.00 | 0.00 | 0.00 |
March | 149.41 | 0.00 | 149.41 | 2.45 | 1058.91 | 0.00 | 0.00 | 0.00 |
April | 270.21 | 5.84 | 264.37 | 64.22 | 568.42 | 0.00 | 0.00 | 0.00 |
May | 413.83 | 65.39 | 348.44 | 262.02 | 225.74 | 0.00 | 0.00 | 0.00 |
June | 540.18 | 119.83 | 420.35 | 480.02 | 105.09 | 0.00 | 0.00 | 0.00 |
July | 453.33 | 73.38 | 379.94 | 414.80 | 134.19 | 0.00 | 0.00 | 0.00 |
August | 289.51 | 16.00 | 273.51 | 189.96 | 227.68 | 0.00 | 0.00 | 0.00 |
September | 161.61 | 0.16 | 161.46 | 30.45 | 494.09 | 0.00 | 0.00 | 0.00 |
October | 78.64 | 0.00 | 78.64 | 0.44 | 910.41 | 0.00 | 0.00 | 0.00 |
November | 24.41 | 0.00 | 24.41 | 0.00 | 1485.84 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 0.00 | 3.83 | 0.00 | 1575.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.19 | 23.49 | 181.70 | 121.10 | 800.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.83 | 0.00 | 3.83 | 0.00 | 105.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 540.18 | 119.83 | 420.35 | 480.02 | 1575.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.85 | 19.96 | 43.89 | 0.75 | 2805.14 | 0.00 | 0.00 | 0.00 |
February | 353.39 | 168.38 | 185.02 | 115.26 | 2369.78 | 0.00 | 0.00 | 0.00 |
March | 1009.98 | 511.76 | 498.22 | 715.95 | 1761.97 | 0.00 | 0.00 | 0.00 |
April | 1388.77 | 703.23 | 685.54 | 1132.13 | 971.03 | 0.00 | 0.00 | 0.00 |
May | 2018.41 | 1137.51 | 880.90 | 2086.33 | 490.28 | 0.00 | 0.00 | 0.00 |
June | 1855.80 | 865.34 | 990.46 | 2008.98 | 245.30 | 0.00 | 0.00 | 0.00 |
July | 1763.15 | 854.72 | 908.42 | 1978.34 | 290.25 | 0.00 | 0.00 | 0.00 |
August | 1396.83 | 680.18 | 716.65 | 1448.93 | 448.51 | 0.00 | 0.00 | 0.00 |
September | 863.67 | 378.41 | 485.26 | 685.60 | 869.86 | 0.00 | 0.00 | 0.00 |
October | 455.72 | 182.77 | 272.95 | 247.02 | 1580.75 | 0.00 | 0.00 | 0.00 |
November | 96.70 | 33.61 | 63.09 | 1.70 | 2777.66 | 0.00 | 0.00 | 0.00 |
December | 13.80 | 3.26 | 10.54 | 0.00 | 3010.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 943.61 | 463.64 | 479.97 | 873.63 | 1463.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.80 | 3.26 | 10.54 | 0.00 | 245.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2018.41 | 1137.51 | 990.46 | 2086.33 | 3010.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.52 | 0.79 | 1.74 | 0.03 | 110.91 | 0.00 | 0.00 | 0.00 |
February | 13.97 | 6.66 | 7.32 | 4.56 | 93.70 | 0.00 | 0.00 | 0.00 |
March | 39.93 | 20.23 | 19.70 | 28.31 | 69.67 | 0.00 | 0.00 | 0.00 |
April | 54.91 | 27.80 | 27.11 | 44.76 | 38.39 | 0.00 | 0.00 | 0.00 |
May | 79.81 | 44.98 | 34.83 | 82.49 | 19.39 | 0.00 | 0.00 | 0.00 |
June | 73.38 | 34.21 | 39.16 | 79.43 | 9.70 | 0.00 | 0.00 | 0.00 |
July | 69.71 | 33.79 | 35.92 | 78.22 | 11.48 | 0.00 | 0.00 | 0.00 |
August | 55.23 | 26.89 | 28.34 | 57.29 | 17.73 | 0.00 | 0.00 | 0.00 |
September | 34.15 | 14.96 | 19.19 | 27.11 | 34.39 | 0.00 | 0.00 | 0.00 |
October | 18.02 | 7.23 | 10.79 | 9.77 | 62.50 | 0.00 | 0.00 | 0.00 |
November | 3.82 | 1.33 | 2.49 | 0.07 | 109.83 | 0.00 | 0.00 | 0.00 |
December | 0.55 | 0.13 | 0.42 | 0.00 | 119.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.31 | 18.33 | 18.98 | 34.54 | 57.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.55 | 0.13 | 0.42 | 0.00 | 9.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.81 | 44.98 | 39.16 | 82.49 | 119.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.23 | 100.51 | 51.72 | 61.36 | 1309.45 | 0.00 | 0.00 | 0.00 |
February | 523.35 | 364.55 | 158.80 | 366.36 | 1060.34 | 0.00 | 0.00 | 0.00 |
March | 897.22 | 608.59 | 288.63 | 789.79 | 825.06 | 0.00 | 0.00 | 0.00 |
April | 1092.77 | 679.77 | 413.01 | 1137.70 | 557.64 | 0.00 | 0.00 | 0.00 |
May | 899.91 | 465.67 | 434.23 | 986.32 | 308.53 | 0.00 | 0.00 | 0.00 |
June | 821.48 | 335.91 | 485.57 | 930.54 | 172.14 | 0.00 | 0.00 | 0.00 |
July | 791.66 | 344.14 | 447.51 | 926.10 | 185.54 | 0.00 | 0.00 | 0.00 |
August | 820.58 | 452.05 | 368.53 | 932.96 | 269.16 | 0.00 | 0.00 | 0.00 |
September | 664.01 | 400.10 | 263.91 | 651.14 | 461.58 | 0.00 | 0.00 | 0.00 |
October | 478.85 | 304.23 | 174.62 | 370.80 | 743.79 | 0.00 | 0.00 | 0.00 |
November | 257.16 | 179.88 | 77.29 | 121.17 | 1249.98 | 0.00 | 0.00 | 0.00 |
December | 45.68 | 32.26 | 13.42 | 3.62 | 1459.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 620.24 | 355.09 | 265.15 | 607.33 | 715.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.68 | 32.26 | 13.42 | 3.62 | 172.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1092.77 | 679.77 | 485.57 | 1137.70 | 1459.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.23 | 100.51 | 51.72 | 61.36 | 1309.45 | 0.00 | 0.00 | 0.00 |
February | 523.35 | 364.55 | 158.80 | 366.36 | 1060.34 | 0.00 | 0.00 | 0.00 |
March | 897.22 | 608.59 | 288.63 | 789.79 | 825.06 | 0.00 | 0.00 | 0.00 |
April | 1092.77 | 679.77 | 413.01 | 1137.70 | 557.64 | 0.00 | 0.00 | 0.00 |
May | 899.91 | 465.67 | 434.23 | 986.32 | 308.53 | 0.00 | 0.00 | 0.00 |
June | 821.48 | 335.91 | 485.57 | 930.54 | 172.14 | 0.00 | 0.00 | 0.00 |
July | 791.66 | 344.14 | 447.51 | 926.10 | 185.54 | 0.00 | 0.00 | 0.00 |
August | 820.58 | 452.05 | 368.53 | 932.96 | 269.16 | 0.00 | 0.00 | 0.00 |
September | 664.01 | 400.10 | 263.91 | 651.14 | 461.58 | 0.00 | 0.00 | 0.00 |
October | 478.85 | 304.23 | 174.62 | 370.80 | 743.79 | 0.00 | 0.00 | 0.00 |
November | 257.16 | 179.88 | 77.29 | 121.17 | 1249.98 | 0.00 | 0.00 | 0.00 |
December | 45.68 | 32.26 | 13.42 | 3.62 | 1459.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 620.24 | 355.09 | 265.15 | 607.33 | 715.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.68 | 32.26 | 13.42 | 3.62 | 172.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1092.77 | 679.77 | 485.57 | 1137.70 | 1459.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.22 | 100.50 | 51.72 | 61.35 | 1309.37 | 0.00 | 0.00 | 0.00 |
February | 523.32 | 364.53 | 158.79 | 366.33 | 1060.27 | 0.00 | 0.00 | 0.00 |
March | 897.17 | 608.56 | 288.61 | 789.74 | 825.01 | 0.00 | 0.00 | 0.00 |
April | 1092.70 | 679.72 | 412.98 | 1137.63 | 557.60 | 0.00 | 0.00 | 0.00 |
May | 899.85 | 465.64 | 434.21 | 986.26 | 308.51 | 0.00 | 0.00 | 0.00 |
June | 821.43 | 335.89 | 485.54 | 930.48 | 172.13 | 0.00 | 0.00 | 0.00 |
July | 791.61 | 344.12 | 447.49 | 926.05 | 185.53 | 0.00 | 0.00 | 0.00 |
August | 820.53 | 452.02 | 368.51 | 932.90 | 269.14 | 0.00 | 0.00 | 0.00 |
September | 663.97 | 400.08 | 263.89 | 651.10 | 461.55 | 0.00 | 0.00 | 0.00 |
October | 478.82 | 304.21 | 174.61 | 370.78 | 743.74 | 0.00 | 0.00 | 0.00 |
November | 257.15 | 179.87 | 77.28 | 121.16 | 1249.90 | 0.00 | 0.00 | 0.00 |
December | 45.68 | 32.26 | 13.42 | 3.61 | 1459.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 620.20 | 355.07 | 265.13 | 607.29 | 715.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 45.68 | 32.26 | 13.42 | 3.61 | 172.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1092.70 | 679.72 | 485.54 | 1137.63 | 1459.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.61 | 5.93 | 27.68 | 0.00 | 2841.52 | 0.00 | 0.00 | 0.00 |
February | 198.49 | 68.76 | 129.73 | 15.08 | 2473.24 | 0.00 | 0.00 | 0.00 |
March | 596.66 | 256.32 | 340.34 | 262.21 | 1857.28 | 0.00 | 0.00 | 0.00 |
April | 1417.93 | 735.45 | 682.48 | 1242.04 | 1057.09 | 0.00 | 0.00 | 0.00 |
May | 1378.59 | 628.49 | 750.10 | 1324.76 | 535.01 | 0.00 | 0.00 | 0.00 |
June | 1510.48 | 644.58 | 865.90 | 1612.64 | 305.24 | 0.00 | 0.00 | 0.00 |
July | 1263.71 | 478.46 | 785.26 | 1365.00 | 329.50 | 0.00 | 0.00 | 0.00 |
August | 1038.69 | 440.19 | 598.50 | 1026.34 | 489.96 | 0.00 | 0.00 | 0.00 |
September | 628.32 | 263.16 | 365.16 | 437.33 | 916.38 | 0.00 | 0.00 | 0.00 |
October | 245.72 | 73.65 | 172.07 | 57.68 | 1665.69 | 0.00 | 0.00 | 0.00 |
November | 98.17 | 35.50 | 62.67 | 2.93 | 2766.09 | 0.00 | 0.00 | 0.00 |
December | 8.82 | 0.91 | 7.91 | 0.00 | 3015.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.41 | 303.26 | 400.15 | 614.76 | 1516.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.82 | 0.91 | 7.91 | 0.00 | 305.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1510.48 | 735.45 | 865.90 | 1612.64 | 3015.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.33 | 0.23 | 1.09 | 0.00 | 112.35 | 0.00 | 0.00 | 0.00 |
February | 7.85 | 2.72 | 5.13 | 0.60 | 97.79 | 0.00 | 0.00 | 0.00 |
March | 23.59 | 10.13 | 13.46 | 10.37 | 73.44 | 0.00 | 0.00 | 0.00 |
April | 56.06 | 29.08 | 26.98 | 49.11 | 41.80 | 0.00 | 0.00 | 0.00 |
May | 54.51 | 24.85 | 29.66 | 52.38 | 21.15 | 0.00 | 0.00 | 0.00 |
June | 59.72 | 25.49 | 34.24 | 63.76 | 12.07 | 0.00 | 0.00 | 0.00 |
July | 49.97 | 18.92 | 31.05 | 53.97 | 13.03 | 0.00 | 0.00 | 0.00 |
August | 41.07 | 17.40 | 23.66 | 40.58 | 19.37 | 0.00 | 0.00 | 0.00 |
September | 24.84 | 10.41 | 14.44 | 17.29 | 36.23 | 0.00 | 0.00 | 0.00 |
October | 9.72 | 2.91 | 6.80 | 2.28 | 65.86 | 0.00 | 0.00 | 0.00 |
November | 3.88 | 1.40 | 2.48 | 0.12 | 109.37 | 0.00 | 0.00 | 0.00 |
December | 0.35 | 0.04 | 0.31 | 0.00 | 119.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.81 | 11.99 | 15.82 | 24.31 | 59.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.35 | 0.04 | 0.31 | 0.00 | 12.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.72 | 29.08 | 34.24 | 63.76 | 119.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.91 | 0.00 | 37.91 | 0.00 | 4560.04 | 0.00 | 0.00 | 0.00 |
February | 167.59 | 0.00 | 167.59 | 0.00 | 4191.03 | 0.00 | 0.00 | 0.00 |
March | 448.22 | 0.00 | 448.22 | 4.93 | 3309.02 | 0.00 | 0.00 | 0.00 |
April | 810.64 | 17.53 | 793.10 | 153.24 | 1831.99 | 0.00 | 0.00 | 0.00 |
May | 1241.49 | 196.18 | 1045.31 | 667.47 | 758.33 | 0.00 | 0.00 | 0.00 |
June | 1620.51 | 359.49 | 1261.02 | 1329.72 | 355.20 | 0.00 | 0.00 | 0.00 |
July | 1359.97 | 220.15 | 1139.81 | 1177.87 | 434.68 | 0.00 | 0.00 | 0.00 |
August | 868.51 | 48.00 | 820.51 | 531.57 | 712.93 | 0.00 | 0.00 | 0.00 |
September | 484.83 | 0.47 | 484.36 | 81.31 | 1502.76 | 0.00 | 0.00 | 0.00 |
October | 235.92 | 0.00 | 235.92 | 1.28 | 2737.36 | 0.00 | 0.00 | 0.00 |
November | 73.22 | 0.00 | 73.22 | 0.00 | 4477.76 | 0.00 | 0.00 | 0.00 |
December | 11.50 | 0.00 | 11.50 | 0.00 | 4777.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 615.56 | 70.46 | 545.09 | 330.97 | 2461.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.50 | 0.00 | 11.50 | 0.00 | 355.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1620.51 | 359.49 | 1261.02 | 1329.72 | 4777.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.37 | 20.74 | 45.63 | 0.66 | 2965.53 | 0.00 | 0.00 | 0.00 |
February | 367.35 | 175.03 | 192.32 | 113.99 | 2530.91 | 0.00 | 0.00 | 0.00 |
March | 1049.87 | 531.97 | 517.90 | 716.30 | 1899.74 | 0.00 | 0.00 | 0.00 |
April | 1443.63 | 731.00 | 712.62 | 1123.80 | 1061.34 | 0.00 | 0.00 | 0.00 |
May | 2098.14 | 1182.44 | 915.70 | 2115.02 | 530.10 | 0.00 | 0.00 | 0.00 |
June | 1929.11 | 899.52 | 1029.59 | 2043.77 | 267.77 | 0.00 | 0.00 | 0.00 |
July | 1832.79 | 888.48 | 944.31 | 2030.37 | 306.22 | 0.00 | 0.00 | 0.00 |
August | 1452.00 | 707.04 | 744.96 | 1489.73 | 460.61 | 0.00 | 0.00 | 0.00 |
September | 897.79 | 393.35 | 504.43 | 700.08 | 897.04 | 0.00 | 0.00 | 0.00 |
October | 473.72 | 189.99 | 283.73 | 252.11 | 1638.05 | 0.00 | 0.00 | 0.00 |
November | 100.52 | 34.94 | 65.58 | 1.63 | 2897.54 | 0.00 | 0.00 | 0.00 |
December | 14.35 | 3.39 | 10.95 | 0.00 | 3161.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 980.88 | 481.95 | 498.93 | 887.67 | 1546.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.35 | 3.39 | 10.95 | 0.00 | 267.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2098.14 | 1182.44 | 1029.59 | 2115.02 | 3161.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.68 | 301.51 | 155.16 | 168.53 | 4139.33 | 0.00 | 0.00 | 0.00 |
February | 1570.01 | 1093.63 | 476.39 | 1046.68 | 3341.55 | 0.00 | 0.00 | 0.00 |
March | 2691.60 | 1825.73 | 865.87 | 2273.26 | 2596.64 | 0.00 | 0.00 | 0.00 |
April | 3278.23 | 2039.24 | 1238.99 | 3322.27 | 1718.51 | 0.00 | 0.00 | 0.00 |
May | 2699.65 | 1396.98 | 1302.67 | 2878.48 | 970.34 | 0.00 | 0.00 | 0.00 |
June | 2464.38 | 1007.72 | 1456.67 | 2726.57 | 548.14 | 0.00 | 0.00 | 0.00 |
July | 2374.91 | 1032.40 | 1342.51 | 2738.78 | 568.37 | 0.00 | 0.00 | 0.00 |
August | 2461.68 | 1356.12 | 1105.56 | 2768.76 | 792.06 | 0.00 | 0.00 | 0.00 |
September | 1991.98 | 1200.27 | 791.71 | 1928.84 | 1358.45 | 0.00 | 0.00 | 0.00 |
October | 1436.52 | 912.66 | 523.85 | 1092.09 | 2237.01 | 0.00 | 0.00 | 0.00 |
November | 771.47 | 539.62 | 231.86 | 343.17 | 3870.85 | 0.00 | 0.00 | 0.00 |
December | 137.04 | 96.79 | 40.26 | 7.13 | 4594.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1860.66 | 1065.25 | 795.42 | 1777.18 | 2222.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 137.04 | 96.79 | 40.26 | 7.13 | 548.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3278.23 | 2039.24 | 1456.67 | 3322.27 | 4594.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 6.16 | 28.77 | 0.00 | 3006.39 | 0.00 | 0.00 | 0.00 |
February | 206.33 | 71.47 | 134.85 | 13.60 | 2643.45 | 0.00 | 0.00 | 0.00 |
March | 620.23 | 266.45 | 353.78 | 258.29 | 2008.21 | 0.00 | 0.00 | 0.00 |
April | 1473.94 | 764.50 | 709.44 | 1244.64 | 1146.97 | 0.00 | 0.00 | 0.00 |
May | 1433.06 | 653.31 | 779.74 | 1321.91 | 596.85 | 0.00 | 0.00 | 0.00 |
June | 1570.15 | 670.05 | 900.11 | 1633.99 | 340.97 | 0.00 | 0.00 | 0.00 |
July | 1313.64 | 497.36 | 816.28 | 1392.59 | 356.91 | 0.00 | 0.00 | 0.00 |
August | 1079.72 | 457.58 | 622.14 | 1054.20 | 509.32 | 0.00 | 0.00 | 0.00 |
September | 653.14 | 273.56 | 379.58 | 448.12 | 948.13 | 0.00 | 0.00 | 0.00 |
October | 255.43 | 76.56 | 178.87 | 58.58 | 1729.96 | 0.00 | 0.00 | 0.00 |
November | 102.05 | 36.90 | 65.15 | 2.90 | 2887.39 | 0.00 | 0.00 | 0.00 |
December | 9.17 | 0.95 | 8.22 | 0.00 | 3170.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 731.20 | 315.24 | 415.96 | 621.71 | 1606.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.17 | 0.95 | 8.22 | 0.00 | 340.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1570.15 | 764.50 | 900.11 | 1633.99 | 3170.07 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101541E+09 | 0.00 | 0.101541E+09 | 0.00 | 0.120282E+11 |
February | 0.405424E+09 | 0.00 | 0.405424E+09 | 0.00 | 0.995237E+10 |
March | 0.120051E+10 | 0.00 | 0.120051E+10 | 17301421.20 | 0.863228E+10 |
April | 0.210117E+10 | 45444922.18 | 0.205572E+10 | 0.434136E+09 | 0.450317E+10 |
May | 0.332521E+10 | 0.525449E+09 | 0.279976E+10 | 0.192295E+10 | 0.189025E+10 |
June | 0.420037E+10 | 0.931794E+09 | 0.326858E+10 | 0.354623E+10 | 0.861416E+09 |
July | 0.364253E+10 | 0.589657E+09 | 0.305288E+10 | 0.325166E+10 | 0.108827E+10 |
August | 0.232623E+10 | 0.128573E+09 | 0.219765E+10 | 0.152915E+10 | 0.175446E+10 |
September | 0.125669E+10 | 1224429.65 | 0.125547E+10 | 0.255121E+09 | 0.360516E+10 |
October | 0.631895E+09 | 0.00 | 0.631895E+09 | 8482603.00 | 0.700251E+10 |
November | 0.189774E+09 | 0.00 | 0.189774E+09 | 0.00 | 0.113781E+11 |
December | 30802333.82 | 0.00 | 30802333.82 | 0.00 | 0.126070E+11 |
Annual Sum or Average | 0.194121E+11 | 0.222214E+10 | 0.171900E+11 | 0.109650E+11 | 0.753032E+11 |
Minimum of Months | 30802333.82 | 0.00 | 30802333.82 | 0.00 | 0.861416E+09 |
Maximum of Months | 0.420037E+10 | 0.931794E+09 | 0.326858E+10 | 0.354623E+10 | 0.126070E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177764E+09 | 55560949.23 | 0.122203E+09 | 1688337.69 | 0.783272E+10 |
February | 0.888703E+09 | 0.423432E+09 | 0.465270E+09 | 0.283283E+09 | 0.601026E+10 |
March | 0.281197E+10 | 0.142483E+10 | 0.138714E+10 | 0.195596E+10 | 0.494094E+10 |
April | 0.374188E+10 | 0.189476E+10 | 0.184712E+10 | 0.298401E+10 | 0.260689E+10 |
May | 0.561966E+10 | 0.316705E+10 | 0.245261E+10 | 0.573071E+10 | 0.134395E+10 |
June | 0.500025E+10 | 0.233155E+10 | 0.266869E+10 | 0.533738E+10 | 0.659197E+09 |
July | 0.490895E+10 | 0.237971E+10 | 0.252925E+10 | 0.547789E+10 | 0.777247E+09 |
August | 0.388905E+10 | 0.189374E+10 | 0.199531E+10 | 0.405115E+10 | 0.115518E+10 |
September | 0.232707E+10 | 0.101957E+10 | 0.130749E+10 | 0.188763E+10 | 0.215081E+10 |
October | 0.126882E+10 | 0.508864E+09 | 0.759955E+09 | 0.703786E+09 | 0.417981E+10 |
November | 0.260543E+09 | 90564865.42 | 0.169979E+09 | 4391606.98 | 0.737308E+10 |
December | 38424144.44 | 9084861.42 | 29339283.02 | 0.00 | 0.835659E+10 |
Annual Sum or Average | 0.309331E+11 | 0.151987E+11 | 0.157344E+11 | 0.284179E+11 | 0.473867E+11 |
Minimum of Months | 38424144.44 | 9084861.42 | 29339283.02 | 0.00 | 0.659197E+09 |
Maximum of Months | 0.561966E+10 | 0.316705E+10 | 0.266869E+10 | 0.573071E+10 | 0.835659E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122316E+10 | 0.807575E+09 | 0.415589E+09 | 0.458915E+09 | 0.108963E+11 |
February | 0.379817E+10 | 0.264570E+10 | 0.115247E+10 | 0.256910E+10 | 0.789433E+10 |
March | 0.720918E+10 | 0.489004E+10 | 0.231914E+10 | 0.614712E+10 | 0.672008E+10 |
April | 0.849716E+10 | 0.528571E+10 | 0.321145E+10 | 0.867098E+10 | 0.422735E+10 |
May | 0.723074E+10 | 0.374168E+10 | 0.348907E+10 | 0.774340E+10 | 0.243972E+10 |
June | 0.638768E+10 | 0.261200E+10 | 0.377568E+10 | 0.708543E+10 | 0.133923E+10 |
July | 0.636097E+10 | 0.276519E+10 | 0.359578E+10 | 0.735799E+10 | 0.143444E+10 |
August | 0.659336E+10 | 0.363223E+10 | 0.296113E+10 | 0.745459E+10 | 0.198279E+10 |
September | 0.516321E+10 | 0.311111E+10 | 0.205210E+10 | 0.507182E+10 | 0.327258E+10 |
October | 0.384756E+10 | 0.244448E+10 | 0.140308E+10 | 0.299071E+10 | 0.569381E+10 |
November | 0.199966E+10 | 0.139868E+10 | 0.600975E+09 | 0.907895E+09 | 0.980047E+10 |
December | 0.367058E+09 | 0.259237E+09 | 0.107821E+09 | 19710175.81 | 0.121101E+11 |
Annual Sum or Average | 0.586779E+11 | 0.335936E+11 | 0.250843E+11 | 0.564777E+11 | 0.678111E+11 |
Minimum of Months | 0.367058E+09 | 0.259237E+09 | 0.107821E+09 | 19710175.81 | 0.133923E+10 |
Maximum of Months | 0.849716E+10 | 0.528571E+10 | 0.377568E+10 | 0.867098E+10 | 0.121101E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93575522.41 | 16511016.07 | 77064506.34 | 0.00 | 0.793059E+10 |
February | 0.499147E+09 | 0.172908E+09 | 0.326239E+09 | 34483319.88 | 0.627109E+10 |
March | 0.166123E+10 | 0.713656E+09 | 0.947572E+09 | 0.700223E+09 | 0.522782E+10 |
April | 0.382046E+10 | 0.198159E+10 | 0.183887E+10 | 0.325373E+10 | 0.281881E+10 |
May | 0.383830E+10 | 0.174984E+10 | 0.208846E+10 | 0.357324E+10 | 0.149434E+10 |
June | 0.406984E+10 | 0.173676E+10 | 0.233308E+10 | 0.425359E+10 | 0.831053E+09 |
July | 0.351845E+10 | 0.133212E+10 | 0.218633E+10 | 0.375242E+10 | 0.898593E+09 |
August | 0.289193E+10 | 0.122559E+10 | 0.166635E+10 | 0.285616E+10 | 0.127034E+10 |
September | 0.169294E+10 | 0.709059E+09 | 0.983879E+09 | 0.119448E+10 | 0.228326E+10 |
October | 0.684133E+09 | 0.205053E+09 | 0.479081E+09 | 0.167270E+09 | 0.442438E+10 |
November | 0.264520E+09 | 95652676.76 | 0.168867E+09 | 7988574.12 | 0.733463E+10 |
December | 24555174.47 | 2535849.60 | 22019324.87 | 0.00 | 0.836787E+10 |
Annual Sum or Average | 0.230591E+11 | 0.994126E+10 | 0.131178E+11 | 0.197936E+11 | 0.491528E+11 |
Minimum of Months | 24555174.47 | 2535849.60 | 22019324.87 | 0.00 | 0.831053E+09 |
Maximum of Months | 0.406984E+10 | 0.198159E+10 | 0.233308E+10 | 0.425359E+10 | 0.836787E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33845933.93 | 0.00 | 33845933.93 | 0.00 | 0.400022E+10 |
February | 0.135136E+09 | 0.00 | 0.135136E+09 | 0.00 | 0.328777E+10 |
March | 0.400156E+09 | 0.00 | 0.400156E+09 | 6569274.81 | 0.283600E+10 |
April | 0.700363E+09 | 15147829.81 | 0.685215E+09 | 0.166465E+09 | 0.147326E+10 |
May | 0.110836E+10 | 0.175144E+09 | 0.933220E+09 | 0.701762E+09 | 0.604582E+09 |
June | 0.140007E+10 | 0.310588E+09 | 0.108949E+10 | 0.124418E+10 | 0.272380E+09 |
July | 0.121413E+10 | 0.196546E+09 | 0.101759E+10 | 0.111096E+10 | 0.359380E+09 |
August | 0.775381E+09 | 42856315.69 | 0.732525E+09 | 0.508765E+09 | 0.609773E+09 |
September | 0.418881E+09 | 408130.35 | 0.418473E+09 | 78920483.88 | 0.128061E+10 |
October | 0.210624E+09 | 0.00 | 0.210624E+09 | 1190964.75 | 0.243830E+10 |
November | 63255638.32 | 0.00 | 63255638.32 | 0.00 | 0.385105E+10 |
December | 10267089.29 | 0.00 | 10267089.29 | 0.00 | 0.421835E+10 |
Annual Sum or Average | 0.647048E+10 | 0.740691E+09 | 0.572979E+10 | 0.381881E+10 | 0.252317E+11 |
Minimum of Months | 10267089.29 | 0.00 | 10267089.29 | 0.00 | 0.272380E+09 |
Maximum of Months | 0.140007E+10 | 0.310588E+09 | 0.108949E+10 | 0.124418E+10 | 0.421835E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33847431.24 | 0.00 | 33847431.24 | 0.00 | 0.400047E+10 |
February | 0.135142E+09 | 0.00 | 0.135142E+09 | 0.00 | 0.328798E+10 |
March | 0.400175E+09 | 0.00 | 0.400175E+09 | 6569081.94 | 0.283618E+10 |
April | 0.700396E+09 | 15148414.72 | 0.685247E+09 | 0.166469E+09 | 0.147335E+10 |
May | 0.110841E+10 | 0.175151E+09 | 0.933264E+09 | 0.701784E+09 | 0.604621E+09 |
June | 0.140014E+10 | 0.310600E+09 | 0.108954E+10 | 0.124422E+10 | 0.272397E+09 |
July | 0.121419E+10 | 0.196554E+09 | 0.101764E+10 | 0.111100E+10 | 0.359402E+09 |
August | 0.775417E+09 | 42857970.52 | 0.732559E+09 | 0.508782E+09 | 0.609811E+09 |
September | 0.418901E+09 | 408146.11 | 0.418492E+09 | 78921552.95 | 0.128069E+10 |
October | 0.210634E+09 | 0.00 | 0.210634E+09 | 1190814.99 | 0.243845E+10 |
November | 63258436.73 | 0.00 | 63258436.73 | 0.00 | 0.385129E+10 |
December | 10267534.97 | 0.00 | 10267534.97 | 0.00 | 0.421861E+10 |
Annual Sum or Average | 0.647078E+10 | 0.740719E+09 | 0.573006E+10 | 0.381894E+10 | 0.252333E+11 |
Minimum of Months | 10267534.97 | 0.00 | 10267534.97 | 0.00 | 0.272397E+09 |
Maximum of Months | 0.140014E+10 | 0.310600E+09 | 0.108954E+10 | 0.124422E+10 | 0.421861E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33847431.24 | 0.00 | 33847431.24 | 0.00 | 0.400047E+10 |
February | 0.135142E+09 | 0.00 | 0.135142E+09 | 0.00 | 0.328798E+10 |
March | 0.400175E+09 | 0.00 | 0.400175E+09 | 6569081.94 | 0.283618E+10 |
April | 0.700396E+09 | 15148414.72 | 0.685247E+09 | 0.166469E+09 | 0.147335E+10 |
May | 0.110841E+10 | 0.175151E+09 | 0.933264E+09 | 0.701784E+09 | 0.604621E+09 |
June | 0.140014E+10 | 0.310600E+09 | 0.108954E+10 | 0.124422E+10 | 0.272397E+09 |
July | 0.121419E+10 | 0.196554E+09 | 0.101764E+10 | 0.111100E+10 | 0.359402E+09 |
August | 0.775417E+09 | 42857970.52 | 0.732559E+09 | 0.508782E+09 | 0.609811E+09 |
September | 0.418901E+09 | 408146.11 | 0.418492E+09 | 78921552.95 | 0.128069E+10 |
October | 0.210634E+09 | 0.00 | 0.210634E+09 | 1190814.99 | 0.243845E+10 |
November | 63258436.73 | 0.00 | 63258436.73 | 0.00 | 0.385129E+10 |
December | 10267534.97 | 0.00 | 10267534.97 | 0.00 | 0.421861E+10 |
Annual Sum or Average | 0.647078E+10 | 0.740719E+09 | 0.573006E+10 | 0.381894E+10 | 0.252333E+11 |
Minimum of Months | 10267534.97 | 0.00 | 10267534.97 | 0.00 | 0.272397E+09 |
Maximum of Months | 0.140014E+10 | 0.310600E+09 | 0.108954E+10 | 0.124422E+10 | 0.421861E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171009E+09 | 53449836.89 | 0.117559E+09 | 2010572.50 | 0.751328E+10 |
February | 0.854933E+09 | 0.407344E+09 | 0.447589E+09 | 0.278830E+09 | 0.573298E+10 |
March | 0.270512E+10 | 0.137069E+10 | 0.133442E+10 | 0.191760E+10 | 0.471926E+10 |
April | 0.359969E+10 | 0.182276E+10 | 0.177692E+10 | 0.293449E+10 | 0.251692E+10 |
May | 0.540612E+10 | 0.304672E+10 | 0.235940E+10 | 0.558802E+10 | 0.131317E+10 |
June | 0.481023E+10 | 0.224296E+10 | 0.256727E+10 | 0.520729E+10 | 0.635811E+09 |
July | 0.472241E+10 | 0.228929E+10 | 0.243312E+10 | 0.529879E+10 | 0.777397E+09 |
August | 0.374126E+10 | 0.182178E+10 | 0.191948E+10 | 0.388082E+10 | 0.120128E+10 |
September | 0.223864E+10 | 0.980834E+09 | 0.125780E+10 | 0.177707E+10 | 0.225468E+10 |
October | 0.122061E+10 | 0.489530E+09 | 0.731076E+09 | 0.661612E+09 | 0.423387E+10 |
November | 0.250643E+09 | 87123732.61 | 0.163519E+09 | 4418492.14 | 0.719971E+10 |
December | 36964029.83 | 8739669.99 | 28224359.83 | 0.00 | 0.806346E+10 |
Annual Sum or Average | 0.297576E+11 | 0.146212E+11 | 0.151364E+11 | 0.275509E+11 | 0.461618E+11 |
Minimum of Months | 36964029.83 | 8739669.99 | 28224359.83 | 0.00 | 0.635811E+09 |
Maximum of Months | 0.540612E+10 | 0.304672E+10 | 0.256727E+10 | 0.558802E+10 | 0.806346E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6761543.75 | 2113358.43 | 4648185.32 | 79496.23 | 0.297069E+09 |
February | 33803261.44 | 16105995.83 | 17697265.60 | 11024670.71 | 0.226677E+09 |
March | 0.106958E+09 | 54195992.00 | 52761909.37 | 75820109.95 | 0.186595E+09 |
April | 0.142328E+09 | 72070436.71 | 70257936.26 | 0.116027E+09 | 99516556.98 |
May | 0.213753E+09 | 0.120464E+09 | 93288514.90 | 0.220945E+09 | 51921597.31 |
June | 0.190192E+09 | 88684731.19 | 0.101508E+09 | 0.205891E+09 | 25139411.37 |
July | 0.186720E+09 | 90516345.22 | 96203501.21 | 0.209509E+09 | 30737577.90 |
August | 0.147926E+09 | 72031727.52 | 75894465.23 | 0.153444E+09 | 47497364.14 |
September | 88513704.28 | 38781285.33 | 49732418.95 | 70263735.44 | 89148060.21 |
October | 48261643.20 | 19355555.97 | 28906087.23 | 26159546.15 | 0.167403E+09 |
November | 9910186.23 | 3444793.95 | 6465392.28 | 174703.20 | 0.284670E+09 |
December | 1461524.46 | 345558.68 | 1115965.78 | 0.00 | 0.318822E+09 |
Annual Sum or Average | 0.117659E+10 | 0.578110E+09 | 0.598479E+09 | 0.108934E+10 | 0.182520E+10 |
Minimum of Months | 1461524.46 | 345558.68 | 1115965.78 | 0.00 | 25139411.37 |
Maximum of Months | 0.213753E+09 | 0.120464E+09 | 0.101508E+09 | 0.220945E+09 | 0.318822E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407732E+09 | 0.269199E+09 | 0.138533E+09 | 0.164338E+09 | 0.350724E+10 |
February | 0.126609E+10 | 0.881924E+09 | 0.384167E+09 | 0.886289E+09 | 0.256517E+10 |
March | 0.240312E+10 | 0.163006E+10 | 0.773067E+09 | 0.211538E+10 | 0.220985E+10 |
April | 0.283246E+10 | 0.176195E+10 | 0.107051E+10 | 0.294891E+10 | 0.144540E+10 |
May | 0.241031E+10 | 0.124726E+10 | 0.116305E+10 | 0.264177E+10 | 0.826373E+09 |
June | 0.212928E+10 | 0.870690E+09 | 0.125859E+10 | 0.241196E+10 | 0.446177E+09 |
July | 0.212038E+10 | 0.921756E+09 | 0.119862E+10 | 0.248048E+10 | 0.496946E+09 |
August | 0.219784E+10 | 0.121078E+10 | 0.987067E+09 | 0.249883E+10 | 0.720910E+09 |
September | 0.172111E+10 | 0.103706E+10 | 0.684050E+09 | 0.168775E+10 | 0.119641E+10 |
October | 0.128255E+10 | 0.814848E+09 | 0.467706E+09 | 0.993157E+09 | 0.199217E+10 |
November | 0.666571E+09 | 0.466241E+09 | 0.200330E+09 | 0.314080E+09 | 0.323995E+10 |
December | 0.122356E+09 | 86414669.12 | 35941380.72 | 9682975.82 | 0.390882E+10 |
Annual Sum or Average | 0.195598E+11 | 0.111982E+11 | 0.836164E+10 | 0.191526E+11 | 0.225554E+11 |
Minimum of Months | 0.122356E+09 | 86414669.12 | 35941380.72 | 9682975.82 | 0.446177E+09 |
Maximum of Months | 0.283246E+10 | 0.176195E+10 | 0.125859E+10 | 0.294891E+10 | 0.390882E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407732E+09 | 0.269199E+09 | 0.138533E+09 | 0.164338E+09 | 0.350724E+10 |
February | 0.126609E+10 | 0.881924E+09 | 0.384167E+09 | 0.886289E+09 | 0.256517E+10 |
March | 0.240312E+10 | 0.163006E+10 | 0.773067E+09 | 0.211538E+10 | 0.220985E+10 |
April | 0.283246E+10 | 0.176195E+10 | 0.107051E+10 | 0.294891E+10 | 0.144540E+10 |
May | 0.241031E+10 | 0.124726E+10 | 0.116305E+10 | 0.264177E+10 | 0.826373E+09 |
June | 0.212928E+10 | 0.870690E+09 | 0.125859E+10 | 0.241196E+10 | 0.446177E+09 |
July | 0.212038E+10 | 0.921756E+09 | 0.119862E+10 | 0.248048E+10 | 0.496946E+09 |
August | 0.219784E+10 | 0.121078E+10 | 0.987067E+09 | 0.249883E+10 | 0.720910E+09 |
September | 0.172111E+10 | 0.103706E+10 | 0.684050E+09 | 0.168775E+10 | 0.119641E+10 |
October | 0.128255E+10 | 0.814848E+09 | 0.467706E+09 | 0.993157E+09 | 0.199217E+10 |
November | 0.666571E+09 | 0.466241E+09 | 0.200330E+09 | 0.314080E+09 | 0.323995E+10 |
December | 0.122356E+09 | 86414669.12 | 35941380.72 | 9682975.82 | 0.390882E+10 |
Annual Sum or Average | 0.195598E+11 | 0.111982E+11 | 0.836164E+10 | 0.191526E+11 | 0.225554E+11 |
Minimum of Months | 0.122356E+09 | 86414669.12 | 35941380.72 | 9682975.82 | 0.446177E+09 |
Maximum of Months | 0.283246E+10 | 0.176195E+10 | 0.125859E+10 | 0.294891E+10 | 0.390882E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407706E+09 | 0.269182E+09 | 0.138525E+09 | 0.164328E+09 | 0.350702E+10 |
February | 0.126601E+10 | 0.881868E+09 | 0.384143E+09 | 0.886233E+09 | 0.256501E+10 |
March | 0.240297E+10 | 0.162995E+10 | 0.773018E+09 | 0.211524E+10 | 0.220971E+10 |
April | 0.283228E+10 | 0.176184E+10 | 0.107044E+10 | 0.294873E+10 | 0.144531E+10 |
May | 0.241016E+10 | 0.124718E+10 | 0.116298E+10 | 0.264160E+10 | 0.826321E+09 |
June | 0.212915E+10 | 0.870634E+09 | 0.125851E+10 | 0.241181E+10 | 0.446149E+09 |
July | 0.212024E+10 | 0.921697E+09 | 0.119855E+10 | 0.248032E+10 | 0.496915E+09 |
August | 0.219770E+10 | 0.121070E+10 | 0.987005E+09 | 0.249868E+10 | 0.720865E+09 |
September | 0.172101E+10 | 0.103700E+10 | 0.684007E+09 | 0.168764E+10 | 0.119634E+10 |
October | 0.128247E+10 | 0.814797E+09 | 0.467677E+09 | 0.993095E+09 | 0.199204E+10 |
November | 0.666529E+09 | 0.466211E+09 | 0.200317E+09 | 0.314060E+09 | 0.323974E+10 |
December | 0.122348E+09 | 86409208.20 | 35939109.43 | 9682363.91 | 0.390858E+10 |
Annual Sum or Average | 0.195586E+11 | 0.111975E+11 | 0.836111E+10 | 0.191514E+11 | 0.225540E+11 |
Minimum of Months | 0.122348E+09 | 86409208.20 | 35939109.43 | 9682363.91 | 0.446149E+09 |
Maximum of Months | 0.283228E+10 | 0.176184E+10 | 0.125851E+10 | 0.294873E+10 | 0.390858E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90019236.12 | 15883610.27 | 74135625.85 | 0.00 | 0.761073E+10 |
February | 0.480177E+09 | 0.166338E+09 | 0.313840E+09 | 36482464.73 | 0.598327E+10 |
March | 0.159809E+10 | 0.686538E+09 | 0.911557E+09 | 0.702313E+09 | 0.497455E+10 |
April | 0.367527E+10 | 0.190629E+10 | 0.176898E+10 | 0.321937E+10 | 0.273997E+10 |
May | 0.369243E+10 | 0.168335E+10 | 0.200908E+10 | 0.354823E+10 | 0.143297E+10 |
June | 0.391517E+10 | 0.167076E+10 | 0.224440E+10 | 0.417996E+10 | 0.791173E+09 |
July | 0.338473E+10 | 0.128150E+10 | 0.210323E+10 | 0.365601E+10 | 0.882531E+09 |
August | 0.278203E+10 | 0.117902E+10 | 0.160301E+10 | 0.274895E+10 | 0.131230E+10 |
September | 0.162860E+10 | 0.682115E+09 | 0.946484E+09 | 0.113357E+10 | 0.237526E+10 |
October | 0.658133E+09 | 0.197261E+09 | 0.460872E+09 | 0.154490E+09 | 0.446138E+10 |
November | 0.254468E+09 | 92017949.24 | 0.162450E+09 | 7591473.96 | 0.716971E+10 |
December | 23621970.45 | 2439489.28 | 21182481.16 | 0.00 | 0.807662E+10 |
Annual Sum or Average | 0.221827E+11 | 0.956350E+10 | 0.126192E+11 | 0.193870E+11 | 0.478104E+11 |
Minimum of Months | 23621970.45 | 2439489.28 | 21182481.16 | 0.00 | 0.791173E+09 |
Maximum of Months | 0.391517E+10 | 0.190629E+10 | 0.224440E+10 | 0.417996E+10 | 0.807662E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 3559279.55 | 628023.65 | 2931255.90 | 0.00 | 0.300921E+09 |
February | 18985780.91 | 6576847.75 | 12408933.16 | 1442483.81 | 0.236573E+09 |
March | 63187220.81 | 27145095.62 | 36042125.19 | 27768809.88 | 0.196689E+09 |
April | 0.145317E+09 | 75372892.66 | 69943988.21 | 0.127291E+09 | 0.108336E+09 |
May | 0.145995E+09 | 66557959.97 | 79437217.53 | 0.140294E+09 | 56658305.10 |
June | 0.154802E+09 | 66060445.00 | 88741704.53 | 0.165272E+09 | 31282282.35 |
July | 0.133829E+09 | 50669322.20 | 83159803.86 | 0.144555E+09 | 34894496.28 |
August | 0.109999E+09 | 46617210.87 | 63381703.69 | 0.108691E+09 | 51886989.25 |
September | 64393376.75 | 26970232.48 | 37423144.28 | 44820139.55 | 93915608.42 |
October | 26021989.43 | 7799511.82 | 18222477.61 | 6108411.71 | 0.176399E+09 |
November | 10061418.95 | 3638306.87 | 6423112.09 | 300160.05 | 0.283484E+09 |
December | 933991.44 | 96455.21 | 837536.23 | 0.00 | 0.319342E+09 |
Annual Sum or Average | 0.877085E+09 | 0.378132E+09 | 0.498953E+09 | 0.766543E+09 | 0.189038E+10 |
Minimum of Months | 933991.44 | 96455.21 | 837536.23 | 0.00 | 31282282.35 |
Maximum of Months | 0.154802E+09 | 75372892.66 | 88741704.53 | 0.165272E+09 | 0.319342E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101541E+09 | 0.00 | 0.101541E+09 | 0.00 | 0.122136E+11 |
February | 0.405424E+09 | 0.00 | 0.405424E+09 | 0.00 | 0.101389E+11 |
March | 0.120051E+10 | 0.00 | 0.120051E+10 | 13199258.48 | 0.886288E+10 |
April | 0.210117E+10 | 45444922.18 | 0.205572E+10 | 0.397204E+09 | 0.474852E+10 |
May | 0.332521E+10 | 0.525449E+09 | 0.279976E+10 | 0.178776E+10 | 0.203111E+10 |
June | 0.420037E+10 | 0.931794E+09 | 0.326858E+10 | 0.344663E+10 | 0.920681E+09 |
July | 0.364253E+10 | 0.589657E+09 | 0.305288E+10 | 0.315482E+10 | 0.116425E+10 |
August | 0.232623E+10 | 0.128573E+09 | 0.219765E+10 | 0.142375E+10 | 0.190950E+10 |
September | 0.125669E+10 | 1224429.65 | 0.125547E+10 | 0.210744E+09 | 0.389516E+10 |
October | 0.631895E+09 | 0.00 | 0.631895E+09 | 3416165.75 | 0.733174E+10 |
November | 0.189774E+09 | 0.00 | 0.189774E+09 | 0.00 | 0.116063E+11 |
December | 30802333.82 | 0.00 | 30802333.82 | 0.00 | 0.127974E+11 |
Annual Sum or Average | 0.194121E+11 | 0.222214E+10 | 0.171900E+11 | 0.104375E+11 | 0.776201E+11 |
Minimum of Months | 30802333.82 | 0.00 | 30802333.82 | 0.00 | 0.920681E+09 |
Maximum of Months | 0.420037E+10 | 0.931794E+09 | 0.326858E+10 | 0.344663E+10 | 0.127974E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177764E+09 | 55560949.23 | 0.122203E+09 | 1771309.18 | 0.794287E+10 |
February | 0.888703E+09 | 0.423432E+09 | 0.465270E+09 | 0.275775E+09 | 0.612277E+10 |
March | 0.281197E+10 | 0.142483E+10 | 0.138714E+10 | 0.191853E+10 | 0.508827E+10 |
April | 0.374188E+10 | 0.189476E+10 | 0.184712E+10 | 0.291290E+10 | 0.275099E+10 |
May | 0.561966E+10 | 0.316705E+10 | 0.245261E+10 | 0.566487E+10 | 0.141983E+10 |
June | 0.500025E+10 | 0.233155E+10 | 0.266869E+10 | 0.529744E+10 | 0.694067E+09 |
July | 0.490895E+10 | 0.237971E+10 | 0.252925E+10 | 0.543814E+10 | 0.820169E+09 |
August | 0.388905E+10 | 0.189374E+10 | 0.199531E+10 | 0.399010E+10 | 0.123369E+10 |
September | 0.232707E+10 | 0.101957E+10 | 0.130749E+10 | 0.181461E+10 | 0.232512E+10 |
October | 0.126882E+10 | 0.508864E+09 | 0.759955E+09 | 0.675258E+09 | 0.438734E+10 |
November | 0.260543E+09 | 90564865.42 | 0.169979E+09 | 4235939.89 | 0.751042E+10 |
December | 38424144.44 | 9084861.42 | 29339283.02 | 0.00 | 0.846733E+10 |
Annual Sum or Average | 0.309331E+11 | 0.151987E+11 | 0.157344E+11 | 0.279936E+11 | 0.487629E+11 |
Minimum of Months | 38424144.44 | 9084861.42 | 29339283.02 | 0.00 | 0.694067E+09 |
Maximum of Months | 0.561966E+10 | 0.316705E+10 | 0.266869E+10 | 0.566487E+10 | 0.846733E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122316E+10 | 0.807575E+09 | 0.415589E+09 | 0.451397E+09 | 0.110868E+11 |
February | 0.379817E+10 | 0.264570E+10 | 0.115247E+10 | 0.253212E+10 | 0.808389E+10 |
March | 0.720918E+10 | 0.489004E+10 | 0.231914E+10 | 0.608869E+10 | 0.695483E+10 |
April | 0.849716E+10 | 0.528571E+10 | 0.321145E+10 | 0.861131E+10 | 0.445438E+10 |
May | 0.723074E+10 | 0.374168E+10 | 0.348907E+10 | 0.770973E+10 | 0.259895E+10 |
June | 0.638768E+10 | 0.261200E+10 | 0.377568E+10 | 0.706728E+10 | 0.142078E+10 |
July | 0.636097E+10 | 0.276519E+10 | 0.359578E+10 | 0.733554E+10 | 0.152233E+10 |
August | 0.659336E+10 | 0.363223E+10 | 0.296113E+10 | 0.741585E+10 | 0.212146E+10 |
September | 0.516321E+10 | 0.311111E+10 | 0.205210E+10 | 0.499954E+10 | 0.352109E+10 |
October | 0.384756E+10 | 0.244448E+10 | 0.140308E+10 | 0.292506E+10 | 0.599160E+10 |
November | 0.199966E+10 | 0.139868E+10 | 0.600975E+09 | 0.889508E+09 | 0.100332E+11 |
December | 0.367058E+09 | 0.259237E+09 | 0.107821E+09 | 19102121.80 | 0.123067E+11 |
Annual Sum or Average | 0.586779E+11 | 0.335936E+11 | 0.250843E+11 | 0.560451E+11 | 0.700960E+11 |
Minimum of Months | 0.367058E+09 | 0.259237E+09 | 0.107821E+09 | 19102121.80 | 0.142078E+10 |
Maximum of Months | 0.849716E+10 | 0.528571E+10 | 0.377568E+10 | 0.861131E+10 | 0.123067E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93575522.41 | 16511016.07 | 77064506.34 | 0.00 | 0.805231E+10 |
February | 0.499147E+09 | 0.172908E+09 | 0.326239E+09 | 32902719.52 | 0.639504E+10 |
March | 0.166123E+10 | 0.713656E+09 | 0.947572E+09 | 0.691807E+09 | 0.537880E+10 |
April | 0.382046E+10 | 0.198159E+10 | 0.183887E+10 | 0.322610E+10 | 0.297295E+10 |
May | 0.383830E+10 | 0.174984E+10 | 0.208846E+10 | 0.354060E+10 | 0.159861E+10 |
June | 0.406984E+10 | 0.173676E+10 | 0.233308E+10 | 0.423530E+10 | 0.883781E+09 |
July | 0.351845E+10 | 0.133212E+10 | 0.218633E+10 | 0.372991E+10 | 0.955948E+09 |
August | 0.289193E+10 | 0.122559E+10 | 0.166635E+10 | 0.282358E+10 | 0.136417E+10 |
September | 0.169294E+10 | 0.709059E+09 | 0.983879E+09 | 0.116152E+10 | 0.245755E+10 |
October | 0.684133E+09 | 0.205053E+09 | 0.479081E+09 | 0.156914E+09 | 0.463352E+10 |
November | 0.264520E+09 | 95652676.76 | 0.168867E+09 | 7528383.01 | 0.748412E+10 |
December | 24555174.47 | 2535849.60 | 22019324.87 | 0.00 | 0.849071E+10 |
Annual Sum or Average | 0.230591E+11 | 0.994126E+10 | 0.131178E+11 | 0.196062E+11 | 0.506675E+11 |
Minimum of Months | 24555174.47 | 2535849.60 | 22019324.87 | 0.00 | 0.883781E+09 |
Maximum of Months | 0.406984E+10 | 0.198159E+10 | 0.233308E+10 | 0.423530E+10 | 0.849071E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4490.80 | 37.91 | 0.00 | 37.91 | 0.00 | 0.00 |
February | 0.00 | 4113.91 | 167.59 | 0.00 | 167.59 | 0.00 | 0.00 |
March | 6.46 | 3222.92 | 448.22 | 0.00 | 448.22 | 0.00 | 0.00 |
April | 167.49 | 1737.33 | 810.64 | 17.53 | 793.10 | 0.00 | 0.00 |
May | 717.95 | 705.74 | 1241.49 | 196.18 | 1045.31 | 0.00 | 0.00 |
June | 1368.14 | 332.34 | 1620.51 | 359.49 | 1261.02 | 0.00 | 0.00 |
July | 1214.03 | 406.31 | 1359.97 | 220.15 | 1139.81 | 0.00 | 0.00 |
August | 570.92 | 655.04 | 868.51 | 48.00 | 820.51 | 0.00 | 0.00 |
September | 98.43 | 1390.88 | 484.83 | 0.47 | 484.36 | 0.00 | 0.00 |
October | 3.17 | 2614.44 | 235.92 | 0.00 | 235.92 | 0.00 | 0.00 |
November | 0.00 | 4389.69 | 73.22 | 0.00 | 73.22 | 0.00 | 0.00 |
December | 0.00 | 4706.93 | 11.50 | 0.00 | 11.50 | 0.00 | 0.00 |
Annual Sum or Average | 347.70 | 2387.85 | 615.56 | 70.46 | 545.09 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 332.34 | 11.50 | 0.00 | 11.50 | 0.00 | 0.00 |
Maximum of Months | 1368.14 | 4706.93 | 1620.51 | 359.49 | 1261.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.63 | 2924.40 | 66.37 | 20.74 | 45.63 | 0.00 | 0.00 |
February | 117.10 | 2484.40 | 367.35 | 175.03 | 192.32 | 0.00 | 0.00 |
March | 730.27 | 1844.74 | 1049.87 | 531.97 | 517.90 | 0.00 | 0.00 |
April | 1151.24 | 1005.74 | 1443.63 | 731.00 | 712.62 | 0.00 | 0.00 |
May | 2139.60 | 501.77 | 2098.14 | 1182.44 | 915.70 | 0.00 | 0.00 |
June | 2059.17 | 254.32 | 1929.11 | 899.52 | 1029.59 | 0.00 | 0.00 |
July | 2045.21 | 290.19 | 1832.79 | 888.48 | 944.31 | 0.00 | 0.00 |
August | 1512.53 | 431.30 | 1452.00 | 707.04 | 744.96 | 0.00 | 0.00 |
September | 728.25 | 829.79 | 897.79 | 393.35 | 504.43 | 0.00 | 0.00 |
October | 262.76 | 1560.56 | 473.72 | 189.99 | 283.73 | 0.00 | 0.00 |
November | 1.69 | 2844.55 | 100.52 | 34.94 | 65.58 | 0.00 | 0.00 |
December | 0.00 | 3119.99 | 14.35 | 3.39 | 10.95 | 0.00 | 0.00 |
Annual Sum or Average | 901.12 | 1502.62 | 980.88 | 481.95 | 498.93 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 254.32 | 14.35 | 3.39 | 10.95 | 0.00 | 0.00 |
Maximum of Months | 2139.60 | 3119.99 | 2098.14 | 1182.44 | 1029.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.34 | 4068.20 | 456.68 | 301.51 | 155.16 | 0.00 | 0.00 |
February | 1061.96 | 3263.20 | 1570.01 | 1093.63 | 476.39 | 0.00 | 0.00 |
March | 2295.07 | 2508.99 | 2691.60 | 1825.73 | 865.87 | 0.00 | 0.00 |
April | 3345.28 | 1630.92 | 3278.23 | 2039.24 | 1238.99 | 0.00 | 0.00 |
May | 2891.05 | 910.89 | 2699.65 | 1396.98 | 1302.67 | 0.00 | 0.00 |
June | 2733.57 | 516.68 | 2464.38 | 1007.72 | 1456.67 | 0.00 | 0.00 |
July | 2747.16 | 535.56 | 2374.91 | 1032.40 | 1342.51 | 0.00 | 0.00 |
August | 2783.23 | 740.29 | 2461.68 | 1356.12 | 1105.56 | 0.00 | 0.00 |
September | 1956.72 | 1262.57 | 1991.98 | 1200.27 | 791.71 | 0.00 | 0.00 |
October | 1116.60 | 2125.82 | 1436.52 | 912.66 | 523.85 | 0.00 | 0.00 |
November | 350.27 | 3781.05 | 771.47 | 539.62 | 231.86 | 0.00 | 0.00 |
December | 7.36 | 4521.38 | 137.04 | 96.79 | 40.26 | 0.00 | 0.00 |
Annual Sum or Average | 1790.89 | 2150.28 | 1860.66 | 1065.25 | 795.42 | 0.00 | 0.00 |
Minimum of Months | 7.36 | 516.68 | 137.04 | 96.79 | 40.26 | 0.00 | 0.00 |
Maximum of Months | 3345.28 | 4521.38 | 3278.23 | 2039.24 | 1456.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2960.94 | 34.94 | 6.16 | 28.77 | 0.00 | 0.00 |
February | 14.25 | 2592.22 | 206.33 | 71.47 | 134.85 | 0.00 | 0.00 |
March | 261.43 | 1951.84 | 620.23 | 266.45 | 353.78 | 0.00 | 0.00 |
April | 1255.30 | 1087.50 | 1473.94 | 764.50 | 709.44 | 0.00 | 0.00 |
May | 1334.10 | 557.92 | 1433.06 | 653.31 | 779.74 | 0.00 | 0.00 |
June | 1641.05 | 320.62 | 1570.15 | 670.05 | 900.11 | 0.00 | 0.00 |
July | 1400.99 | 335.50 | 1313.64 | 497.36 | 816.28 | 0.00 | 0.00 |
August | 1066.37 | 474.29 | 1079.72 | 457.58 | 622.14 | 0.00 | 0.00 |
September | 460.83 | 880.89 | 653.14 | 273.56 | 379.58 | 0.00 | 0.00 |
October | 62.45 | 1651.87 | 255.43 | 76.56 | 178.87 | 0.00 | 0.00 |
November | 3.08 | 2829.72 | 102.05 | 36.90 | 65.15 | 0.00 | 0.00 |
December | 0.00 | 3124.20 | 9.17 | 0.95 | 8.22 | 0.00 | 0.00 |
Annual Sum or Average | 627.65 | 1558.62 | 731.20 | 315.24 | 415.96 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 320.62 | 9.17 | 0.95 | 8.22 | 0.00 | 0.00 |
Maximum of Months | 1641.05 | 3124.20 | 1570.15 | 764.50 | 900.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4480.72 | 37.91 | 0.00 | 37.91 | 0.00 | 0.00 |
February | 0.00 | 4077.27 | 167.58 | 0.00 | 167.58 | 0.00 | 0.00 |
March | 7.36 | 3176.65 | 448.22 | 0.00 | 448.22 | 0.00 | 0.00 |
April | 192.67 | 1705.23 | 810.63 | 17.53 | 793.10 | 0.00 | 0.00 |
May | 786.04 | 677.20 | 1241.49 | 196.18 | 1045.31 | 0.00 | 0.00 |
June | 1440.06 | 315.27 | 1620.50 | 359.49 | 1261.02 | 0.00 | 0.00 |
July | 1244.39 | 402.55 | 1359.96 | 220.15 | 1139.81 | 0.00 | 0.00 |
August | 569.87 | 683.02 | 868.51 | 48.00 | 820.51 | 0.00 | 0.00 |
September | 91.34 | 1482.25 | 484.83 | 0.47 | 484.36 | 0.00 | 0.00 |
October | 1.33 | 2731.18 | 235.92 | 0.00 | 235.92 | 0.00 | 0.00 |
November | 0.00 | 4457.42 | 73.21 | 0.00 | 73.21 | 0.00 | 0.00 |
December | 0.00 | 4725.05 | 11.50 | 0.00 | 11.50 | 0.00 | 0.00 |
Annual Sum or Average | 363.29 | 2400.37 | 615.55 | 70.46 | 545.09 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 315.27 | 11.50 | 0.00 | 11.50 | 0.00 | 0.00 |
Maximum of Months | 1440.06 | 4725.05 | 1620.50 | 359.49 | 1261.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.78 | 2916.05 | 66.37 | 20.74 | 45.63 | 0.00 | 0.00 |
February | 119.81 | 2463.48 | 367.37 | 175.04 | 192.33 | 0.00 | 0.00 |
March | 744.26 | 1831.64 | 1049.91 | 531.99 | 517.92 | 0.00 | 0.00 |
April | 1176.90 | 1009.43 | 1443.68 | 731.03 | 712.65 | 0.00 | 0.00 |
May | 2168.82 | 509.67 | 2098.22 | 1182.49 | 915.73 | 0.00 | 0.00 |
June | 2088.42 | 255.00 | 1929.18 | 899.56 | 1029.62 | 0.00 | 0.00 |
July | 2056.56 | 301.72 | 1832.86 | 888.52 | 944.34 | 0.00 | 0.00 |
August | 1506.22 | 466.24 | 1452.06 | 707.07 | 744.99 | 0.00 | 0.00 |
September | 712.71 | 904.26 | 897.82 | 393.37 | 504.45 | 0.00 | 0.00 |
October | 256.78 | 1643.25 | 473.74 | 190.00 | 283.74 | 0.00 | 0.00 |
November | 1.77 | 2887.49 | 100.52 | 34.94 | 65.58 | 0.00 | 0.00 |
December | 0.00 | 3129.59 | 14.35 | 3.39 | 10.95 | 0.00 | 0.00 |
Annual Sum or Average | 908.18 | 1521.66 | 980.92 | 481.97 | 498.95 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 255.00 | 14.35 | 3.39 | 10.95 | 0.00 | 0.00 |
Maximum of Months | 2168.82 | 3129.59 | 2098.22 | 1182.49 | 1029.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 184.07 | 3928.28 | 456.68 | 301.52 | 155.16 | 0.00 | 0.00 |
February | 1099.05 | 3180.94 | 1570.02 | 1093.63 | 476.39 | 0.00 | 0.00 |
March | 2369.33 | 2475.13 | 2691.61 | 1825.74 | 865.87 | 0.00 | 0.00 |
April | 3413.02 | 1672.88 | 3278.24 | 2039.25 | 1238.99 | 0.00 | 0.00 |
May | 2958.91 | 925.58 | 2699.66 | 1396.99 | 1302.67 | 0.00 | 0.00 |
June | 2791.56 | 516.40 | 2464.39 | 1007.72 | 1456.67 | 0.00 | 0.00 |
July | 2778.25 | 556.60 | 2374.93 | 1032.41 | 1342.51 | 0.00 | 0.00 |
August | 2798.81 | 807.45 | 2461.69 | 1356.13 | 1105.56 | 0.00 | 0.00 |
September | 1953.37 | 1384.71 | 1991.99 | 1200.28 | 791.71 | 0.00 | 0.00 |
October | 1112.38 | 2231.32 | 1436.52 | 912.67 | 523.85 | 0.00 | 0.00 |
November | 363.51 | 3749.86 | 771.48 | 539.62 | 231.86 | 0.00 | 0.00 |
December | 10.85 | 4378.07 | 137.04 | 96.79 | 40.26 | 0.00 | 0.00 |
Annual Sum or Average | 1821.94 | 2145.64 | 1860.67 | 1065.25 | 795.42 | 0.00 | 0.00 |
Minimum of Months | 10.85 | 516.40 | 137.04 | 96.79 | 40.26 | 0.00 | 0.00 |
Maximum of Months | 3413.02 | 4378.07 | 3278.24 | 2039.25 | 1456.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2953.87 | 34.94 | 6.16 | 28.77 | 0.00 | 0.00 |
February | 15.68 | 2571.03 | 206.33 | 71.48 | 134.86 | 0.00 | 0.00 |
March | 272.58 | 1930.72 | 620.25 | 266.46 | 353.79 | 0.00 | 0.00 |
April | 1291.15 | 1098.88 | 1473.99 | 764.53 | 709.46 | 0.00 | 0.00 |
May | 1377.14 | 556.16 | 1433.10 | 653.34 | 779.76 | 0.00 | 0.00 |
June | 1676.40 | 317.31 | 1570.20 | 670.07 | 900.13 | 0.00 | 0.00 |
July | 1418.97 | 342.53 | 1313.68 | 497.37 | 816.30 | 0.00 | 0.00 |
August | 1066.92 | 509.33 | 1079.76 | 457.60 | 622.16 | 0.00 | 0.00 |
September | 454.62 | 952.61 | 653.16 | 273.57 | 379.59 | 0.00 | 0.00 |
October | 59.96 | 1731.55 | 255.43 | 76.56 | 178.87 | 0.00 | 0.00 |
November | 3.04 | 2875.46 | 102.06 | 36.90 | 65.15 | 0.00 | 0.00 |
December | 0.00 | 3134.69 | 9.17 | 0.95 | 8.22 | 0.00 | 0.00 |
Annual Sum or Average | 639.06 | 1576.00 | 731.22 | 315.25 | 415.97 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 317.31 | 9.17 | 0.95 | 8.22 | 0.00 | 0.00 |
Maximum of Months | 1676.40 | 3134.69 | 1570.20 | 764.53 | 900.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4560.04 | 37.91 | 0.00 | 37.91 | 0.00 | 0.00 |
February | 0.00 | 4191.03 | 167.59 | 0.00 | 167.59 | 0.00 | 0.00 |
March | 4.93 | 3309.02 | 448.22 | 0.00 | 448.22 | 0.00 | 0.00 |
April | 153.24 | 1831.99 | 810.64 | 17.53 | 793.10 | 0.00 | 0.00 |
May | 667.47 | 758.33 | 1241.49 | 196.18 | 1045.31 | 0.00 | 0.00 |
June | 1329.72 | 355.20 | 1620.51 | 359.49 | 1261.02 | 0.00 | 0.00 |
July | 1177.87 | 434.68 | 1359.97 | 220.15 | 1139.81 | 0.00 | 0.00 |
August | 531.57 | 712.93 | 868.51 | 48.00 | 820.51 | 0.00 | 0.00 |
September | 81.31 | 1502.76 | 484.83 | 0.47 | 484.36 | 0.00 | 0.00 |
October | 1.28 | 2737.36 | 235.92 | 0.00 | 235.92 | 0.00 | 0.00 |
November | 0.00 | 4477.76 | 73.22 | 0.00 | 73.22 | 0.00 | 0.00 |
December | 0.00 | 4777.99 | 11.50 | 0.00 | 11.50 | 0.00 | 0.00 |
Annual Sum or Average | 330.97 | 2461.32 | 615.56 | 70.46 | 545.09 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 355.20 | 11.50 | 0.00 | 11.50 | 0.00 | 0.00 |
Maximum of Months | 1329.72 | 4777.99 | 1620.51 | 359.49 | 1261.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.66 | 2965.53 | 66.37 | 20.74 | 45.63 | 0.00 | 0.00 |
February | 113.99 | 2530.91 | 367.35 | 175.03 | 192.32 | 0.00 | 0.00 |
March | 716.30 | 1899.74 | 1049.87 | 531.97 | 517.90 | 0.00 | 0.00 |
April | 1123.80 | 1061.34 | 1443.63 | 731.00 | 712.62 | 0.00 | 0.00 |
May | 2115.02 | 530.10 | 2098.14 | 1182.44 | 915.70 | 0.00 | 0.00 |
June | 2043.77 | 267.77 | 1929.11 | 899.52 | 1029.59 | 0.00 | 0.00 |
July | 2030.37 | 306.22 | 1832.79 | 888.48 | 944.31 | 0.00 | 0.00 |
August | 1489.73 | 460.61 | 1452.00 | 707.04 | 744.96 | 0.00 | 0.00 |
September | 700.08 | 897.04 | 897.79 | 393.35 | 504.43 | 0.00 | 0.00 |
October | 252.11 | 1638.05 | 473.72 | 189.99 | 283.73 | 0.00 | 0.00 |
November | 1.63 | 2897.54 | 100.52 | 34.94 | 65.58 | 0.00 | 0.00 |
December | 0.00 | 3161.34 | 14.35 | 3.39 | 10.95 | 0.00 | 0.00 |
Annual Sum or Average | 887.67 | 1546.26 | 980.88 | 481.95 | 498.93 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 267.77 | 14.35 | 3.39 | 10.95 | 0.00 | 0.00 |
Maximum of Months | 2115.02 | 3161.34 | 2098.14 | 1182.44 | 1029.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.53 | 4139.33 | 456.68 | 301.51 | 155.16 | 0.00 | 0.00 |
February | 1046.68 | 3341.55 | 1570.01 | 1093.63 | 476.39 | 0.00 | 0.00 |
March | 2273.26 | 2596.64 | 2691.60 | 1825.73 | 865.87 | 0.00 | 0.00 |
April | 3322.27 | 1718.51 | 3278.23 | 2039.24 | 1238.99 | 0.00 | 0.00 |
May | 2878.48 | 970.34 | 2699.65 | 1396.98 | 1302.67 | 0.00 | 0.00 |
June | 2726.57 | 548.14 | 2464.38 | 1007.72 | 1456.67 | 0.00 | 0.00 |
July | 2738.78 | 568.37 | 2374.91 | 1032.40 | 1342.51 | 0.00 | 0.00 |
August | 2768.76 | 792.06 | 2461.68 | 1356.12 | 1105.56 | 0.00 | 0.00 |
September | 1928.84 | 1358.45 | 1991.98 | 1200.27 | 791.71 | 0.00 | 0.00 |
October | 1092.09 | 2237.01 | 1436.52 | 912.66 | 523.85 | 0.00 | 0.00 |
November | 343.17 | 3870.85 | 771.47 | 539.62 | 231.86 | 0.00 | 0.00 |
December | 7.13 | 4594.79 | 137.04 | 96.79 | 40.26 | 0.00 | 0.00 |
Annual Sum or Average | 1777.18 | 2222.73 | 1860.66 | 1065.25 | 795.42 | 0.00 | 0.00 |
Minimum of Months | 7.13 | 548.14 | 137.04 | 96.79 | 40.26 | 0.00 | 0.00 |
Maximum of Months | 3322.27 | 4594.79 | 3278.23 | 2039.24 | 1456.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3006.39 | 34.94 | 6.16 | 28.77 | 0.00 | 0.00 |
February | 13.60 | 2643.45 | 206.33 | 71.47 | 134.85 | 0.00 | 0.00 |
March | 258.29 | 2008.21 | 620.23 | 266.45 | 353.78 | 0.00 | 0.00 |
April | 1244.64 | 1146.97 | 1473.94 | 764.50 | 709.44 | 0.00 | 0.00 |
May | 1321.91 | 596.85 | 1433.06 | 653.31 | 779.74 | 0.00 | 0.00 |
June | 1633.99 | 340.97 | 1570.15 | 670.05 | 900.11 | 0.00 | 0.00 |
July | 1392.59 | 356.91 | 1313.64 | 497.36 | 816.28 | 0.00 | 0.00 |
August | 1054.20 | 509.32 | 1079.72 | 457.58 | 622.14 | 0.00 | 0.00 |
September | 448.12 | 948.13 | 653.14 | 273.56 | 379.58 | 0.00 | 0.00 |
October | 58.58 | 1729.96 | 255.43 | 76.56 | 178.87 | 0.00 | 0.00 |
November | 2.90 | 2887.39 | 102.05 | 36.90 | 65.15 | 0.00 | 0.00 |
December | 0.00 | 3170.07 | 9.17 | 0.95 | 8.22 | 0.00 | 0.00 |
Annual Sum or Average | 621.71 | 1606.66 | 731.20 | 315.24 | 415.96 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 340.97 | 9.17 | 0.95 | 8.22 | 0.00 | 0.00 |
Maximum of Months | 1633.99 | 3170.07 | 1570.15 | 764.50 | 900.11 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.120282E+11 | 0.101541E+09 | 0.00 | 0.101541E+09 | 0.00 | 0.00 |
February | 0.00 | 0.995237E+10 | 0.405424E+09 | 0.00 | 0.405424E+09 | 0.00 | 0.00 |
March | 17301421.20 | 0.863228E+10 | 0.120051E+10 | 0.00 | 0.120051E+10 | 0.00 | 0.00 |
April | 0.434136E+09 | 0.450317E+10 | 0.210117E+10 | 45444922.18 | 0.205572E+10 | 0.00 | 0.00 |
May | 0.192295E+10 | 0.189025E+10 | 0.332521E+10 | 0.525449E+09 | 0.279976E+10 | 0.00 | 0.00 |
June | 0.354623E+10 | 0.861416E+09 | 0.420037E+10 | 0.931794E+09 | 0.326858E+10 | 0.00 | 0.00 |
July | 0.325166E+10 | 0.108827E+10 | 0.364253E+10 | 0.589657E+09 | 0.305288E+10 | 0.00 | 0.00 |
August | 0.152915E+10 | 0.175446E+10 | 0.232623E+10 | 0.128573E+09 | 0.219765E+10 | 0.00 | 0.00 |
September | 0.255121E+09 | 0.360516E+10 | 0.125669E+10 | 1224429.65 | 0.125547E+10 | 0.00 | 0.00 |
October | 8482603.00 | 0.700251E+10 | 0.631895E+09 | 0.00 | 0.631895E+09 | 0.00 | 0.00 |
November | 0.00 | 0.113781E+11 | 0.189774E+09 | 0.00 | 0.189774E+09 | 0.00 | 0.00 |
December | 0.00 | 0.126070E+11 | 30802333.82 | 0.00 | 30802333.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.109650E+11 | 0.753032E+11 | 0.194121E+11 | 0.222214E+10 | 0.171900E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.861416E+09 | 30802333.82 | 0.00 | 30802333.82 | 0.00 | 0.00 |
Maximum of Months | 0.354623E+10 | 0.126070E+11 | 0.420037E+10 | 0.931794E+09 | 0.326858E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1688337.69 | 0.783272E+10 | 0.177764E+09 | 55560949.23 | 0.122203E+09 | 0.00 | 0.00 |
February | 0.283283E+09 | 0.601026E+10 | 0.888703E+09 | 0.423432E+09 | 0.465270E+09 | 0.00 | 0.00 |
March | 0.195596E+10 | 0.494094E+10 | 0.281197E+10 | 0.142483E+10 | 0.138714E+10 | 0.00 | 0.00 |
April | 0.298401E+10 | 0.260689E+10 | 0.374188E+10 | 0.189476E+10 | 0.184712E+10 | 0.00 | 0.00 |
May | 0.573071E+10 | 0.134395E+10 | 0.561966E+10 | 0.316705E+10 | 0.245261E+10 | 0.00 | 0.00 |
June | 0.533738E+10 | 0.659197E+09 | 0.500025E+10 | 0.233155E+10 | 0.266869E+10 | 0.00 | 0.00 |
July | 0.547789E+10 | 0.777247E+09 | 0.490895E+10 | 0.237971E+10 | 0.252925E+10 | 0.00 | 0.00 |
August | 0.405115E+10 | 0.115518E+10 | 0.388905E+10 | 0.189374E+10 | 0.199531E+10 | 0.00 | 0.00 |
September | 0.188763E+10 | 0.215081E+10 | 0.232707E+10 | 0.101957E+10 | 0.130749E+10 | 0.00 | 0.00 |
October | 0.703786E+09 | 0.417981E+10 | 0.126882E+10 | 0.508864E+09 | 0.759955E+09 | 0.00 | 0.00 |
November | 4391606.98 | 0.737308E+10 | 0.260543E+09 | 90564865.42 | 0.169979E+09 | 0.00 | 0.00 |
December | 0.00 | 0.835659E+10 | 38424144.44 | 9084861.42 | 29339283.02 | 0.00 | 0.00 |
Annual Sum or Average | 0.284179E+11 | 0.473867E+11 | 0.309331E+11 | 0.151987E+11 | 0.157344E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.659197E+09 | 38424144.44 | 9084861.42 | 29339283.02 | 0.00 | 0.00 |
Maximum of Months | 0.573071E+10 | 0.835659E+10 | 0.561966E+10 | 0.316705E+10 | 0.266869E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.458915E+09 | 0.108963E+11 | 0.122316E+10 | 0.807575E+09 | 0.415589E+09 | 0.00 | 0.00 |
February | 0.256910E+10 | 0.789433E+10 | 0.379817E+10 | 0.264570E+10 | 0.115247E+10 | 0.00 | 0.00 |
March | 0.614712E+10 | 0.672008E+10 | 0.720918E+10 | 0.489004E+10 | 0.231914E+10 | 0.00 | 0.00 |
April | 0.867098E+10 | 0.422735E+10 | 0.849716E+10 | 0.528571E+10 | 0.321145E+10 | 0.00 | 0.00 |
May | 0.774340E+10 | 0.243972E+10 | 0.723074E+10 | 0.374168E+10 | 0.348907E+10 | 0.00 | 0.00 |
June | 0.708543E+10 | 0.133923E+10 | 0.638768E+10 | 0.261200E+10 | 0.377568E+10 | 0.00 | 0.00 |
July | 0.735799E+10 | 0.143444E+10 | 0.636097E+10 | 0.276519E+10 | 0.359578E+10 | 0.00 | 0.00 |
August | 0.745459E+10 | 0.198279E+10 | 0.659336E+10 | 0.363223E+10 | 0.296113E+10 | 0.00 | 0.00 |
September | 0.507182E+10 | 0.327258E+10 | 0.516321E+10 | 0.311111E+10 | 0.205210E+10 | 0.00 | 0.00 |
October | 0.299071E+10 | 0.569381E+10 | 0.384756E+10 | 0.244448E+10 | 0.140308E+10 | 0.00 | 0.00 |
November | 0.907895E+09 | 0.980047E+10 | 0.199966E+10 | 0.139868E+10 | 0.600975E+09 | 0.00 | 0.00 |
December | 19710175.81 | 0.121101E+11 | 0.367058E+09 | 0.259237E+09 | 0.107821E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.564777E+11 | 0.678111E+11 | 0.586779E+11 | 0.335936E+11 | 0.250843E+11 | 0.00 | 0.00 |
Minimum of Months | 19710175.81 | 0.133923E+10 | 0.367058E+09 | 0.259237E+09 | 0.107821E+09 | 0.00 | 0.00 |
Maximum of Months | 0.867098E+10 | 0.121101E+11 | 0.849716E+10 | 0.528571E+10 | 0.377568E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.793059E+10 | 93575522.41 | 16511016.07 | 77064506.34 | 0.00 | 0.00 |
February | 34483319.88 | 0.627109E+10 | 0.499147E+09 | 0.172908E+09 | 0.326239E+09 | 0.00 | 0.00 |
March | 0.700223E+09 | 0.522782E+10 | 0.166123E+10 | 0.713656E+09 | 0.947572E+09 | 0.00 | 0.00 |
April | 0.325373E+10 | 0.281881E+10 | 0.382046E+10 | 0.198159E+10 | 0.183887E+10 | 0.00 | 0.00 |
May | 0.357324E+10 | 0.149434E+10 | 0.383830E+10 | 0.174984E+10 | 0.208846E+10 | 0.00 | 0.00 |
June | 0.425359E+10 | 0.831053E+09 | 0.406984E+10 | 0.173676E+10 | 0.233308E+10 | 0.00 | 0.00 |
July | 0.375242E+10 | 0.898593E+09 | 0.351845E+10 | 0.133212E+10 | 0.218633E+10 | 0.00 | 0.00 |
August | 0.285616E+10 | 0.127034E+10 | 0.289193E+10 | 0.122559E+10 | 0.166635E+10 | 0.00 | 0.00 |
September | 0.119448E+10 | 0.228326E+10 | 0.169294E+10 | 0.709059E+09 | 0.983879E+09 | 0.00 | 0.00 |
October | 0.167270E+09 | 0.442438E+10 | 0.684133E+09 | 0.205053E+09 | 0.479081E+09 | 0.00 | 0.00 |
November | 7988574.12 | 0.733463E+10 | 0.264520E+09 | 95652676.76 | 0.168867E+09 | 0.00 | 0.00 |
December | 0.00 | 0.836787E+10 | 24555174.47 | 2535849.60 | 22019324.87 | 0.00 | 0.00 |
Annual Sum or Average | 0.197936E+11 | 0.491528E+11 | 0.230591E+11 | 0.994126E+10 | 0.131178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.831053E+09 | 24555174.47 | 2535849.60 | 22019324.87 | 0.00 | 0.00 |
Maximum of Months | 0.425359E+10 | 0.836787E+10 | 0.406984E+10 | 0.198159E+10 | 0.233308E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.120012E+11 | 0.101541E+09 | 0.00 | 0.101541E+09 | 0.00 | 0.00 |
February | 0.00 | 0.986373E+10 | 0.405421E+09 | 0.00 | 0.405421E+09 | 0.00 | 0.00 |
March | 19707438.70 | 0.850835E+10 | 0.120051E+10 | 0.00 | 0.120051E+10 | 0.00 | 0.00 |
April | 0.499402E+09 | 0.441996E+10 | 0.210115E+10 | 45444659.24 | 0.205571E+10 | 0.00 | 0.00 |
May | 0.210533E+10 | 0.181382E+10 | 0.332519E+10 | 0.525446E+09 | 0.279975E+10 | 0.00 | 0.00 |
June | 0.373262E+10 | 0.817174E+09 | 0.420035E+10 | 0.931788E+09 | 0.326856E+10 | 0.00 | 0.00 |
July | 0.333296E+10 | 0.107818E+10 | 0.364251E+10 | 0.589653E+09 | 0.305286E+10 | 0.00 | 0.00 |
August | 0.152633E+10 | 0.182939E+10 | 0.232621E+10 | 0.128572E+09 | 0.219764E+10 | 0.00 | 0.00 |
September | 0.236764E+09 | 0.384200E+10 | 0.125668E+10 | 1224422.57 | 0.125546E+10 | 0.00 | 0.00 |
October | 3572594.74 | 0.731521E+10 | 0.631891E+09 | 0.00 | 0.631891E+09 | 0.00 | 0.00 |
November | 0.00 | 0.115536E+11 | 0.189773E+09 | 0.00 | 0.189773E+09 | 0.00 | 0.00 |
December | 0.00 | 0.126556E+11 | 30802159.23 | 0.00 | 30802159.23 | 0.00 | 0.00 |
Annual Sum or Average | 0.114567E+11 | 0.756982E+11 | 0.194120E+11 | 0.222213E+10 | 0.171899E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.817174E+09 | 30802159.23 | 0.00 | 30802159.23 | 0.00 | 0.00 |
Maximum of Months | 0.373262E+10 | 0.126556E+11 | 0.420035E+10 | 0.931788E+09 | 0.326856E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2090068.73 | 0.781035E+10 | 0.177771E+09 | 55563195.32 | 0.122207E+09 | 0.00 | 0.00 |
February | 0.289854E+09 | 0.595965E+10 | 0.888736E+09 | 0.423450E+09 | 0.465286E+09 | 0.00 | 0.00 |
March | 0.199342E+10 | 0.490586E+10 | 0.281208E+10 | 0.142489E+10 | 0.138719E+10 | 0.00 | 0.00 |
April | 0.305051E+10 | 0.261643E+10 | 0.374202E+10 | 0.189483E+10 | 0.184718E+10 | 0.00 | 0.00 |
May | 0.580897E+10 | 0.136509E+10 | 0.561987E+10 | 0.316718E+10 | 0.245269E+10 | 0.00 | 0.00 |
June | 0.541318E+10 | 0.660951E+09 | 0.500043E+10 | 0.233165E+10 | 0.266878E+10 | 0.00 | 0.00 |
July | 0.550830E+10 | 0.808135E+09 | 0.490913E+10 | 0.237980E+10 | 0.252933E+10 | 0.00 | 0.00 |
August | 0.403427E+10 | 0.124877E+10 | 0.388919E+10 | 0.189382E+10 | 0.199537E+10 | 0.00 | 0.00 |
September | 0.184733E+10 | 0.234383E+10 | 0.232715E+10 | 0.101962E+10 | 0.130754E+10 | 0.00 | 0.00 |
October | 0.687772E+09 | 0.440127E+10 | 0.126887E+10 | 0.508885E+09 | 0.759982E+09 | 0.00 | 0.00 |
November | 4593195.34 | 0.748438E+10 | 0.260553E+09 | 90568526.56 | 0.169984E+09 | 0.00 | 0.00 |
December | 0.00 | 0.838228E+10 | 38425554.28 | 9085228.68 | 29340325.61 | 0.00 | 0.00 |
Annual Sum or Average | 0.286403E+11 | 0.479870E+11 | 0.309342E+11 | 0.151993E+11 | 0.157349E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.660951E+09 | 38425554.28 | 9085228.68 | 29340325.61 | 0.00 | 0.00 |
Maximum of Months | 0.580897E+10 | 0.838228E+10 | 0.561987E+10 | 0.316718E+10 | 0.266878E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.493004E+09 | 0.105215E+11 | 0.122317E+10 | 0.807580E+09 | 0.415591E+09 | 0.00 | 0.00 |
February | 0.265881E+10 | 0.769534E+10 | 0.379819E+10 | 0.264572E+10 | 0.115248E+10 | 0.00 | 0.00 |
March | 0.634600E+10 | 0.662940E+10 | 0.720922E+10 | 0.489007E+10 | 0.231915E+10 | 0.00 | 0.00 |
April | 0.884656E+10 | 0.433610E+10 | 0.849721E+10 | 0.528574E+10 | 0.321146E+10 | 0.00 | 0.00 |
May | 0.792514E+10 | 0.247907E+10 | 0.723078E+10 | 0.374170E+10 | 0.348908E+10 | 0.00 | 0.00 |
June | 0.723573E+10 | 0.133850E+10 | 0.638771E+10 | 0.261201E+10 | 0.377569E+10 | 0.00 | 0.00 |
July | 0.744128E+10 | 0.149081E+10 | 0.636100E+10 | 0.276521E+10 | 0.359579E+10 | 0.00 | 0.00 |
August | 0.749634E+10 | 0.216269E+10 | 0.659339E+10 | 0.363225E+10 | 0.296114E+10 | 0.00 | 0.00 |
September | 0.506314E+10 | 0.358916E+10 | 0.516323E+10 | 0.311113E+10 | 0.205211E+10 | 0.00 | 0.00 |
October | 0.297941E+10 | 0.597637E+10 | 0.384758E+10 | 0.244449E+10 | 0.140309E+10 | 0.00 | 0.00 |
November | 0.942219E+09 | 0.971963E+10 | 0.199967E+10 | 0.139869E+10 | 0.600978E+09 | 0.00 | 0.00 |
December | 29048315.54 | 0.117262E+11 | 0.367060E+09 | 0.259239E+09 | 0.107822E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.574567E+11 | 0.676648E+11 | 0.586782E+11 | 0.335938E+11 | 0.250844E+11 | 0.00 | 0.00 |
Minimum of Months | 29048315.54 | 0.133850E+10 | 0.367060E+09 | 0.259239E+09 | 0.107822E+09 | 0.00 | 0.00 |
Maximum of Months | 0.884656E+10 | 0.117262E+11 | 0.849721E+10 | 0.528574E+10 | 0.377569E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.791165E+10 | 93578515.67 | 16511633.92 | 77066881.75 | 0.00 | 0.00 |
February | 37924948.54 | 0.621984E+10 | 0.499163E+09 | 0.172915E+09 | 0.326248E+09 | 0.00 | 0.00 |
March | 0.730081E+09 | 0.517124E+10 | 0.166128E+10 | 0.713683E+09 | 0.947599E+09 | 0.00 | 0.00 |
April | 0.334666E+10 | 0.284830E+10 | 0.382059E+10 | 0.198166E+10 | 0.183893E+10 | 0.00 | 0.00 |
May | 0.368853E+10 | 0.148963E+10 | 0.383842E+10 | 0.174990E+10 | 0.208852E+10 | 0.00 | 0.00 |
June | 0.434523E+10 | 0.822456E+09 | 0.406997E+10 | 0.173682E+10 | 0.233315E+10 | 0.00 | 0.00 |
July | 0.380057E+10 | 0.917426E+09 | 0.351856E+10 | 0.133217E+10 | 0.218639E+10 | 0.00 | 0.00 |
August | 0.285764E+10 | 0.136418E+10 | 0.289203E+10 | 0.122563E+10 | 0.166640E+10 | 0.00 | 0.00 |
September | 0.117839E+10 | 0.246917E+10 | 0.169299E+10 | 0.709086E+09 | 0.983908E+09 | 0.00 | 0.00 |
October | 0.160599E+09 | 0.463778E+10 | 0.684155E+09 | 0.205060E+09 | 0.479095E+09 | 0.00 | 0.00 |
November | 7891634.01 | 0.745319E+10 | 0.264529E+09 | 95656256.11 | 0.168873E+09 | 0.00 | 0.00 |
December | 0.00 | 0.839596E+10 | 24555961.89 | 2535944.49 | 22020017.40 | 0.00 | 0.00 |
Annual Sum or Average | 0.201535E+11 | 0.497008E+11 | 0.230598E+11 | 0.994164E+10 | 0.131182E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.822456E+09 | 24555961.89 | 2535944.49 | 22020017.40 | 0.00 | 0.00 |
Maximum of Months | 0.434523E+10 | 0.839596E+10 | 0.406997E+10 | 0.198166E+10 | 0.233315E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.122136E+11 | 0.101541E+09 | 0.00 | 0.101541E+09 | 0.00 | 0.00 |
February | 0.00 | 0.101389E+11 | 0.405424E+09 | 0.00 | 0.405424E+09 | 0.00 | 0.00 |
March | 13199258.48 | 0.886288E+10 | 0.120051E+10 | 0.00 | 0.120051E+10 | 0.00 | 0.00 |
April | 0.397204E+09 | 0.474852E+10 | 0.210117E+10 | 45444922.18 | 0.205572E+10 | 0.00 | 0.00 |
May | 0.178776E+10 | 0.203111E+10 | 0.332521E+10 | 0.525449E+09 | 0.279976E+10 | 0.00 | 0.00 |
June | 0.344663E+10 | 0.920681E+09 | 0.420037E+10 | 0.931794E+09 | 0.326858E+10 | 0.00 | 0.00 |
July | 0.315482E+10 | 0.116425E+10 | 0.364253E+10 | 0.589657E+09 | 0.305288E+10 | 0.00 | 0.00 |
August | 0.142375E+10 | 0.190950E+10 | 0.232623E+10 | 0.128573E+09 | 0.219765E+10 | 0.00 | 0.00 |
September | 0.210744E+09 | 0.389516E+10 | 0.125669E+10 | 1224429.65 | 0.125547E+10 | 0.00 | 0.00 |
October | 3416165.75 | 0.733174E+10 | 0.631895E+09 | 0.00 | 0.631895E+09 | 0.00 | 0.00 |
November | 0.00 | 0.116063E+11 | 0.189774E+09 | 0.00 | 0.189774E+09 | 0.00 | 0.00 |
December | 0.00 | 0.127974E+11 | 30802333.82 | 0.00 | 30802333.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.104375E+11 | 0.776201E+11 | 0.194121E+11 | 0.222214E+10 | 0.171900E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.920681E+09 | 30802333.82 | 0.00 | 30802333.82 | 0.00 | 0.00 |
Maximum of Months | 0.344663E+10 | 0.127974E+11 | 0.420037E+10 | 0.931794E+09 | 0.326858E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1771309.18 | 0.794287E+10 | 0.177764E+09 | 55560949.23 | 0.122203E+09 | 0.00 | 0.00 |
February | 0.275775E+09 | 0.612277E+10 | 0.888703E+09 | 0.423432E+09 | 0.465270E+09 | 0.00 | 0.00 |
March | 0.191853E+10 | 0.508827E+10 | 0.281197E+10 | 0.142483E+10 | 0.138714E+10 | 0.00 | 0.00 |
April | 0.291290E+10 | 0.275099E+10 | 0.374188E+10 | 0.189476E+10 | 0.184712E+10 | 0.00 | 0.00 |
May | 0.566487E+10 | 0.141983E+10 | 0.561966E+10 | 0.316705E+10 | 0.245261E+10 | 0.00 | 0.00 |
June | 0.529744E+10 | 0.694067E+09 | 0.500025E+10 | 0.233155E+10 | 0.266869E+10 | 0.00 | 0.00 |
July | 0.543814E+10 | 0.820169E+09 | 0.490895E+10 | 0.237971E+10 | 0.252925E+10 | 0.00 | 0.00 |
August | 0.399010E+10 | 0.123369E+10 | 0.388905E+10 | 0.189374E+10 | 0.199531E+10 | 0.00 | 0.00 |
September | 0.181461E+10 | 0.232512E+10 | 0.232707E+10 | 0.101957E+10 | 0.130749E+10 | 0.00 | 0.00 |
October | 0.675258E+09 | 0.438734E+10 | 0.126882E+10 | 0.508864E+09 | 0.759955E+09 | 0.00 | 0.00 |
November | 4235939.89 | 0.751042E+10 | 0.260543E+09 | 90564865.42 | 0.169979E+09 | 0.00 | 0.00 |
December | 0.00 | 0.846733E+10 | 38424144.44 | 9084861.42 | 29339283.02 | 0.00 | 0.00 |
Annual Sum or Average | 0.279936E+11 | 0.487629E+11 | 0.309331E+11 | 0.151987E+11 | 0.157344E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.694067E+09 | 38424144.44 | 9084861.42 | 29339283.02 | 0.00 | 0.00 |
Maximum of Months | 0.566487E+10 | 0.846733E+10 | 0.561966E+10 | 0.316705E+10 | 0.266869E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.451397E+09 | 0.110868E+11 | 0.122316E+10 | 0.807575E+09 | 0.415589E+09 | 0.00 | 0.00 |
February | 0.253212E+10 | 0.808389E+10 | 0.379817E+10 | 0.264570E+10 | 0.115247E+10 | 0.00 | 0.00 |
March | 0.608869E+10 | 0.695483E+10 | 0.720918E+10 | 0.489004E+10 | 0.231914E+10 | 0.00 | 0.00 |
April | 0.861131E+10 | 0.445438E+10 | 0.849716E+10 | 0.528571E+10 | 0.321145E+10 | 0.00 | 0.00 |
May | 0.770973E+10 | 0.259895E+10 | 0.723074E+10 | 0.374168E+10 | 0.348907E+10 | 0.00 | 0.00 |
June | 0.706728E+10 | 0.142078E+10 | 0.638768E+10 | 0.261200E+10 | 0.377568E+10 | 0.00 | 0.00 |
July | 0.733554E+10 | 0.152233E+10 | 0.636097E+10 | 0.276519E+10 | 0.359578E+10 | 0.00 | 0.00 |
August | 0.741585E+10 | 0.212146E+10 | 0.659336E+10 | 0.363223E+10 | 0.296113E+10 | 0.00 | 0.00 |
September | 0.499954E+10 | 0.352109E+10 | 0.516321E+10 | 0.311111E+10 | 0.205210E+10 | 0.00 | 0.00 |
October | 0.292506E+10 | 0.599160E+10 | 0.384756E+10 | 0.244448E+10 | 0.140308E+10 | 0.00 | 0.00 |
November | 0.889508E+09 | 0.100332E+11 | 0.199966E+10 | 0.139868E+10 | 0.600975E+09 | 0.00 | 0.00 |
December | 19102121.80 | 0.123067E+11 | 0.367058E+09 | 0.259237E+09 | 0.107821E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.560451E+11 | 0.700960E+11 | 0.586779E+11 | 0.335936E+11 | 0.250843E+11 | 0.00 | 0.00 |
Minimum of Months | 19102121.80 | 0.142078E+10 | 0.367058E+09 | 0.259237E+09 | 0.107821E+09 | 0.00 | 0.00 |
Maximum of Months | 0.861131E+10 | 0.123067E+11 | 0.849716E+10 | 0.528571E+10 | 0.377568E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.805231E+10 | 93575522.41 | 16511016.07 | 77064506.34 | 0.00 | 0.00 |
February | 32902719.52 | 0.639504E+10 | 0.499147E+09 | 0.172908E+09 | 0.326239E+09 | 0.00 | 0.00 |
March | 0.691807E+09 | 0.537880E+10 | 0.166123E+10 | 0.713656E+09 | 0.947572E+09 | 0.00 | 0.00 |
April | 0.322610E+10 | 0.297295E+10 | 0.382046E+10 | 0.198159E+10 | 0.183887E+10 | 0.00 | 0.00 |
May | 0.354060E+10 | 0.159861E+10 | 0.383830E+10 | 0.174984E+10 | 0.208846E+10 | 0.00 | 0.00 |
June | 0.423530E+10 | 0.883781E+09 | 0.406984E+10 | 0.173676E+10 | 0.233308E+10 | 0.00 | 0.00 |
July | 0.372991E+10 | 0.955948E+09 | 0.351845E+10 | 0.133212E+10 | 0.218633E+10 | 0.00 | 0.00 |
August | 0.282358E+10 | 0.136417E+10 | 0.289193E+10 | 0.122559E+10 | 0.166635E+10 | 0.00 | 0.00 |
September | 0.116152E+10 | 0.245755E+10 | 0.169294E+10 | 0.709059E+09 | 0.983879E+09 | 0.00 | 0.00 |
October | 0.156914E+09 | 0.463352E+10 | 0.684133E+09 | 0.205053E+09 | 0.479081E+09 | 0.00 | 0.00 |
November | 7528383.01 | 0.748412E+10 | 0.264520E+09 | 95652676.76 | 0.168867E+09 | 0.00 | 0.00 |
December | 0.00 | 0.849071E+10 | 24555174.47 | 2535849.60 | 22019324.87 | 0.00 | 0.00 |
Annual Sum or Average | 0.196062E+11 | 0.506675E+11 | 0.230591E+11 | 0.994126E+10 | 0.131178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.883781E+09 | 24555174.47 | 2535849.60 | 22019324.87 | 0.00 | 0.00 |
Maximum of Months | 0.423530E+10 | 0.849071E+10 | 0.406984E+10 | 0.198159E+10 | 0.233308E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.592786E+10 | -0.566902E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -258834951.7 | 60.05 | 0.00 | 0.00 |
February | 0.538236E+10 | -0.515214E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -230222425.9 | 60.05 | 0.00 | 0.00 |
March | 0.634893E+10 | -0.610038E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -248543615.5 | 60.05 | 0.00 | 0.00 |
April | 0.572032E+10 | -0.548883E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -231487249.9 | 60.05 | 0.00 | 0.00 |
May | 0.607832E+10 | -0.584474E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233580726.3 | 60.05 | 0.00 | 0.00 |
June | 0.582204E+10 | -0.559779E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224246205.8 | 60.05 | 0.00 | 0.00 |
July | 0.530864E+10 | -0.507786E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -230777700.0 | 60.05 | 0.00 | 0.00 |
August | 0.571433E+10 | -0.548231E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232025967.9 | 60.05 | 0.00 | 0.00 |
September | 0.514467E+10 | -0.491783E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226838437.6 | 60.05 | 0.00 | 0.00 |
October | 0.541942E+10 | -0.517772E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241699571.5 | 60.05 | 0.00 | 0.00 |
November | 0.551660E+10 | -0.527198E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -244623392.7 | 60.05 | 0.00 | 0.00 |
December | 0.568580E+10 | -0.542781E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -257986940.8 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.680693E+11 | -0.652084E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.286087E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.514467E+10 | -0.610038E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -258834951.7 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.634893E+10 | -0.491783E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -224246205.8 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.274890E+11 | 43712.92 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189907E+11 | 43370.44 | 27-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148466E+11 | 35129.29 | 01-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215043E+10 | 25699.72 | 03-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 140187.25 | 5.36 | 30-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 206668.14 | 5.38 | 11-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13636.28 | 3.83 | 25-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122521E+09 | 5795.30 | 30-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.667352E+10 | 24424.98 | 31-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253274E+11 | 35603.32 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306120E+11 | 41006.35 | 15-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.306120E+11 | 43712.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168408E+10 | 16383.93 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.591013E+09 | 16338.05 | 07-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54624844.96 | 16334.17 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 454462.34 | 7574.37 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 976543.06 | 16275.72 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287376E+09 | 16336.25 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.775659E+09 | 16337.30 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168408E+10 | 16383.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182274E+11 | 13141.88 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138169E+11 | 13034.23 | 27-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113103E+11 | 12976.27 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.428929E+10 | 12974.40 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137600E+10 | 13014.15 | 10-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.394364E+09 | 12920.40 | 02-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.292709E+09 | 10166.04 | 17-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.630785E+09 | 13086.42 | 28-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247428E+10 | 12997.02 | 05-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.752326E+10 | 12980.57 | 03-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149802E+11 | 12977.26 | 14-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182318E+11 | 12975.06 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.292709E+09 | 10166.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182318E+11 | 13141.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.909098E+10 | 8710.17 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.710914E+10 | 8638.82 | 27-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.484457E+10 | 8599.40 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151603E+10 | 8577.96 | 04-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62385505.96 | 4958.60 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1667623.40 | 4300.83 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327625E+09 | 8547.30 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259261E+10 | 8598.41 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.660631E+10 | 8598.53 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.855632E+10 | 8599.61 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.909098E+10 | 8710.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136421E+11 | 13223.96 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115405E+11 | 13115.64 | 27-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.980637E+10 | 13055.78 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.400955E+10 | 13563.87 | 24-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425166E+09 | 8856.35 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35588.39 | 59.31 | 26-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33169086.25 | 10911.33 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.966754E+09 | 12981.15 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.464464E+10 | 13054.28 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.998069E+10 | 13054.46 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126317E+11 | 13056.10 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.676808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136421E+11 | 13563.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.916677E+10 | 8656.32 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748061E+10 | 8585.41 | 27-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.584384E+10 | 8546.23 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165885E+10 | 8524.93 | 04-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187043E+09 | 5859.50 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1074913.02 | 1370.26 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8171565.88 | 4207.06 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.493037E+09 | 8497.38 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295062E+10 | 8545.25 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657742E+10 | 8547.89 | 14-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.855616E+10 | 8546.44 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.916677E+10 | 8656.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.322445E+11 | 44474.42 | 12-JAN-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237050E+11 | 44173.08 | 27-FEB-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204150E+11 | 37301.04 | 01-MAR-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.422393E+10 | 30465.73 | 03-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57559146.95 | 3600.06 | 27-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 150391.03 | 5.36 | 29-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 198448.58 | 5.23 | 24-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34593125.93 | 5275.04 | 31-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104698E+10 | 10853.66 | 30-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114574E+11 | 27655.92 | 31-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307478E+11 | 38954.30 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355601E+11 | 42458.33 | 15-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 150391.03 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.355601E+11 | 44474.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.572448E+10 | 22467.17 | 17-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350934E+10 | 22483.32 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155402E+10 | 22472.45 | 09-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289751E+09 | 22476.68 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4998057.29 | 22188.72 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.932103E+09 | 22478.87 | 24-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.388030E+10 | 22471.30 | 02-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.549546E+10 | 22469.58 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.572448E+10 | 22483.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109402E+11 | 13625.14 | 12-JAN-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.674929E+10 | 13527.93 | 27-FEB-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.429168E+10 | 13400.02 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128785E+10 | 13393.15 | 04-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84410282.39 | 8445.94 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21703415.23 | 9873.42 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.620644E+09 | 13294.34 | 27-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.365993E+10 | 13394.45 | 30-OCT-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.839801E+10 | 13395.61 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114163E+11 | 13397.58 | 26-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114163E+11 | 13625.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.752674E+10 | 9132.80 | 12-JAN-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.512350E+10 | 8942.16 | 27-FEB-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320744E+10 | 8866.62 | 16-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.931022E+09 | 8873.96 | 03-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23830506.28 | 4185.61 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6761688.47 | 6809.49 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.426194E+09 | 8787.88 | 27-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265293E+10 | 8856.62 | 30-OCT-06:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.606976E+10 | 8854.74 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.755671E+10 | 8935.78 | 15-DEC-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.335249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.755671E+10 | 9132.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112760E+11 | 12514.42 | 12-JAN-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.842931E+10 | 12371.71 | 27-FEB-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.651707E+10 | 12191.27 | 29-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196427E+10 | 12174.94 | 03-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61806278.40 | 7915.66 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17809847.15 | 11051.56 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.802759E+09 | 12087.73 | 29-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.449453E+10 | 12192.15 | 27-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.915907E+10 | 12193.28 | 07-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111373E+11 | 12190.96 | 18-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.538599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112760E+11 | 12514.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.792839E+10 | 9016.93 | 12-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.578791E+10 | 8942.33 | 27-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.425462E+10 | 8807.18 | 16-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118547E+10 | 8794.69 | 03-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76572952.55 | 5598.66 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21950580.62 | 6586.48 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.656913E+09 | 8728.96 | 27-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325663E+10 | 8797.25 | 30-OCT-06:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.640064E+10 | 8795.38 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.787768E+10 | 8800.40 | 02-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.792839E+10 | 9016.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354695E+11 | 39192.41 | 12-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258086E+11 | 38837.33 | 27-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193915E+11 | 36840.94 | 01-MAR-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379496E+10 | 28824.76 | 03-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35173600.39 | 4476.33 | 27-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 104029.99 | 5.66 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45579.99 | 5.05 | 07-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 57310881.70 | 7521.32 | 31-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.873921E+09 | 12489.23 | 30-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108776E+11 | 27883.08 | 31-OCT-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.335267E+11 | 36857.38 | 29-NOV-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.390424E+11 | 38589.49 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168878E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 45579.99 | 5.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390424E+11 | 39192.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169249E+11 | 36556.67 | 12-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116142E+11 | 36214.29 | 27-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802090E+10 | 35979.85 | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231201E+10 | 35983.35 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40389093.29 | 13799.49 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2779705.96 | 8697.04 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.828053E+09 | 35999.20 | 25-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.618282E+10 | 36001.66 | 10-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141270E+11 | 35977.53 | 02-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168953E+11 | 35985.63 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169249E+11 | 36556.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149516E+11 | 16670.04 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.986601E+10 | 16296.01 | 27-FEB-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687660E+10 | 16032.98 | 01-MAR-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255771E+10 | 15834.65 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.377228E+09 | 15740.00 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6393593.32 | 5056.82 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5174787.62 | 4083.99 | 06-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160423E+09 | 12708.30 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167628E+10 | 15839.06 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.613076E+10 | 15841.23 | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124068E+11 | 16040.96 | 29-NOV-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157371E+11 | 16374.69 | 15-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5174787.62 | 4083.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157371E+11 | 16670.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105062E+11 | 10958.09 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767660E+10 | 10712.22 | 27-FEB-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537700E+10 | 10539.32 | 01-MAR-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188542E+10 | 10409.34 | 03-APR-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119712E+09 | 9591.71 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3809.37 | 19.05 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1633295.10 | 1515.92 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 58460913.79 | 10174.05 | 31-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120855E+10 | 10411.84 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466568E+10 | 10413.27 | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.912291E+10 | 10544.56 | 29-NOV-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106795E+11 | 10763.94 | 15-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3809.37 | 19.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106795E+11 | 10958.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160416E+11 | 16771.84 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125068E+11 | 16493.22 | 27-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104396E+11 | 16130.90 | 01-MAR-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.419159E+10 | 15931.97 | 03-APR-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.389577E+09 | 15836.13 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2160621.01 | 2463.63 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2206275.27 | 2278.64 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.243468E+09 | 15857.75 | 31-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.264286E+10 | 15935.79 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.797302E+10 | 15940.51 | 10-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139941E+11 | 16138.92 | 29-NOV-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161325E+11 | 16474.70 | 15-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2160621.01 | 2278.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161325E+11 | 16771.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105648E+11 | 10894.99 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.799810E+10 | 10714.00 | 27-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.625599E+10 | 10478.63 | 01-MAR-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218456E+10 | 10349.01 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.292346E+09 | 10287.15 | 27-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4517075.16 | 3398.80 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4282116.15 | 2840.83 | 06-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154384E+09 | 8292.82 | 30-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153309E+10 | 10351.89 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.506473E+10 | 10353.31 | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.908523E+10 | 10483.85 | 29-NOV-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106733E+11 | 10715.74 | 15-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.538153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4282116.15 | 2840.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106733E+11 | 10894.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 117997.87 | 117997.87 | 552.21 | 01-JAN-20:02 | 552.21 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 14048867.72 | 14048867.72 | 2911.00 | 22-APR-14:00 | 2911.00 | 0.00 |
May | 0.00 | 0.00 | 0.465280E+10 | 0.465061E+10 | 37276.74 | 31-MAY-16:00 | 37276.74 | 0.00 |
June | 0.00 | 0.00 | 0.233321E+11 | 0.223059E+11 | 63879.42 | 30-JUN-14:30 | 60859.58 | 0.00 |
July | 0.00 | 0.00 | 0.326762E+11 | 0.299392E+11 | 66120.44 | 11-JUL-16:00 | 64339.86 | 0.00 |
August | 0.00 | 0.00 | 0.184641E+11 | 0.169959E+11 | 63303.38 | 11-AUG-16:00 | 63303.38 | 0.00 |
September | 0.00 | 0.00 | 0.376694E+09 | 0.358873E+09 | 12002.61 | 07-SEP-16:00 | 12002.61 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.795161E+11 | 0.742646E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.326762E+11 | 0.299392E+11 | 66120.44 | 64339.86 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 53710.67 | 53710.67 | 447.59 | 30-JAN-03:32 | 447.59 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 16576571.10 | 16576571.10 | 2947.70 | 22-APR-14:00 | 2947.70 | 0.00 |
May | 0.00 | 0.00 | 0.469459E+10 | 0.469124E+10 | 38487.44 | 31-MAY-16:00 | 38487.44 | 0.00 |
June | 0.00 | 0.00 | 0.228225E+11 | 0.218154E+11 | 69009.94 | 30-JUN-12:05 | 60936.26 | 0.00 |
July | 0.00 | 0.00 | 0.305694E+11 | 0.279703E+11 | 63463.21 | 11-JUL-15:50 | 61558.43 | 0.00 |
August | 0.00 | 0.00 | 0.164733E+11 | 0.150428E+11 | 58222.55 | 11-AUG-15:40 | 58222.55 | 0.00 |
September | 0.00 | 0.00 | 0.315393E+09 | 0.298753E+09 | 10210.90 | 07-SEP-16:00 | 10210.90 | 0.00 |
October | 0.00 | 0.00 | 37463.67 | 37463.67 | 312.20 | 05-OCT-06:04 | 312.20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.748918E+11 | 0.698352E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.305694E+11 | 0.279703E+11 | 69009.94 | 61558.43 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1574001.17 | 1574001.17 | 1923.70 | 10-JAN-06:17 | 1923.70 | 0.00 |
February | 0.00 | 0.00 | 1900867.26 | 1900867.26 | 1406.32 | 06-FEB-06:06 | 1406.32 | 0.00 |
March | 0.00 | 0.00 | 1907717.17 | 1907717.17 | 1044.12 | 08-MAR-06:03 | 1044.12 | 0.00 |
April | 0.00 | 0.00 | 13938093.36 | 13938093.36 | 3106.58 | 22-APR-14:00 | 3106.58 | 0.00 |
May | 0.00 | 0.00 | 0.467137E+10 | 0.464767E+10 | 39729.78 | 31-MAY-16:00 | 39729.78 | 0.00 |
June | 0.00 | 0.00 | 0.239426E+11 | 0.223998E+11 | 71967.68 | 30-JUN-12:30 | 66106.38 | 0.00 |
July | 0.00 | 0.00 | 0.329502E+11 | 0.291404E+11 | 69021.23 | 21-JUL-14:40 | 69021.23 | 0.00 |
August | 0.00 | 0.00 | 0.176237E+11 | 0.152923E+11 | 60991.93 | 11-AUG-15:30 | 60991.93 | 0.00 |
September | 0.00 | 0.00 | 0.299000E+09 | 0.267664E+09 | 8825.51 | 07-SEP-16:00 | 8825.51 | 0.00 |
October | 0.00 | 0.00 | 3533004.88 | 3417956.87 | 1432.39 | 23-OCT-05:04 | 1432.39 | 0.00 |
November | 0.00 | 0.00 | 1859336.16 | 1859336.16 | 1319.06 | 18-NOV-06:01 | 1319.06 | 0.00 |
December | 0.00 | 0.00 | 1581708.17 | 1581708.17 | 1567.84 | 12-DEC-06:17 | 1567.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.795132E+11 | 0.717740E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1574001.17 | 1574001.17 | 1044.12 | 1044.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.329502E+11 | 0.291404E+11 | 71967.68 | 69021.23 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 96119.33 | 363928.02 | 19-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 77235.06 | 358092.03 | 09-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 53083.09 | 381136.79 | 23-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15467.61 | 386889.19 | 06-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1343.34 | 193464.70 | 27-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 153.42 | 36790.79 | 26-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 114.33 | 26966.15 | 17-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 530.36 | 260286.47 | 31-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 6392.57 | 361223.47 | 30-SEP-05:01 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 33988.70 | 368892.07 | 20-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 84494.54 | 353320.54 | 18-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 99149.72 | 316806.57 | 27-DEC-05:01 |
Annual Sum or Average | 0.00 | 38827.45 | ||||
Minimum of Months | 0.00 | 0.00 | 114.33 | 26966.15 | ||
Maximum of Months | 0.00 | 0.00 | 99149.72 | 386889.19 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2106.65 | 7651.72 | 19-JAN-12:19 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 2119.74 | 7651.73 | 17-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2267.31 | 7651.70 | 07-MAR-12:16 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2107.69 | 7651.62 | 06-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2172.08 | 7651.57 | 08-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2149.54 | 7461.23 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1886.34 | 7150.92 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2036.91 | 6936.48 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1887.74 | 6889.78 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1923.50 | 7094.20 | 31-OCT-11:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 2024.11 | 7375.23 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2016.79 | 7651.62 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 2057.87 | ||||
Minimum of Months | 0.00 | 0.00 | 1886.34 | 6889.78 | ||
Maximum of Months | 0.00 | 0.00 | 2267.31 | 7651.73 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.607232E+10 | 0.74 | 6167.26 | 02-JAN-05:01 | 1.34 |
February | 0.518351E+10 | 0.72 | 6167.26 | 01-FEB-07:01 | 1.34 |
March | 0.482427E+10 | 0.62 | 6167.26 | 01-MAR-07:01 | 1.34 |
April | 0.421826E+10 | 0.54 | 9621.54 | 24-APR-05:01 | 1.61 |
May | 0.555145E+10 | 0.59 | 6600.73 | 15-MAY-06:03 | 1.37 |
June | 0.685757E+10 | 0.66 | 10376.19 | 13-JUN-06:03 | 1.65 |
July | 0.705474E+10 | 0.64 | 10620.22 | 11-JUL-06:03 | 1.67 |
August | 0.692474E+10 | 0.66 | 9950.69 | 11-AUG-06:02 | 1.63 |
September | 0.461425E+10 | 0.54 | 8765.39 | 08-SEP-05:02 | 1.54 |
October | 0.396226E+10 | 0.50 | 6167.26 | 30-OCT-06:01 | 1.34 |
November | 0.475041E+10 | 0.62 | 6167.26 | 06-NOV-07:01 | 1.34 |
December | 0.596139E+10 | 0.74 | 6167.26 | 01-DEC-07:01 | 1.34 |
Annual Sum or Average | 0.659752E+11 | 0.63 | |||
Minimum of Months | 0.396226E+10 | 0.50 | 6167.26 | 1.34 | |
Maximum of Months | 0.705474E+10 | 0.74 | 10620.22 | 1.67 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.495883E+10 | 0.68 | 5919.90 | 02-JAN-05:01 | 1.34 |
February | 0.430238E+10 | 0.66 | 5919.90 | 01-FEB-06:01 | 1.34 |
March | 0.404737E+10 | 0.57 | 5919.90 | 01-MAR-06:01 | 1.34 |
April | 0.377323E+10 | 0.52 | 5919.90 | 01-APR-06:03 | 1.34 |
May | 0.498963E+10 | 0.59 | 7152.09 | 31-MAY-14:05 | 1.45 |
June | 0.642323E+10 | 0.66 | 10970.19 | 22-JUN-06:03 | 1.73 |
July | 0.620989E+10 | 0.62 | 9744.33 | 12-JUL-06:03 | 1.64 |
August | 0.559846E+10 | 0.61 | 8418.95 | 11-AUG-15:30 | 1.54 |
September | 0.352373E+10 | 0.50 | 5919.90 | 25-SEP-06:01 | 1.33 |
October | 0.360827E+10 | 0.51 | 5919.90 | 10-OCT-06:01 | 1.33 |
November | 0.440271E+10 | 0.63 | 5919.90 | 01-NOV-05:01 | 1.34 |
December | 0.491085E+10 | 0.68 | 5919.90 | 01-DEC-06:01 | 1.34 |
Annual Sum or Average | 0.567486E+11 | 0.60 | |||
Minimum of Months | 0.352373E+10 | 0.50 | 5919.90 | 1.33 | |
Maximum of Months | 0.642323E+10 | 0.68 | 10970.19 | 1.73 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.563986E+10 | 0.64 | 5793.34 | 02-JAN-07:10 | 1.10 |
February | 0.489385E+10 | 0.62 | 5793.34 | 02-FEB-06:13 | 1.10 |
March | 0.497773E+10 | 0.58 | 5793.34 | 03-MAR-07:04 | 1.11 |
April | 0.398887E+10 | 0.47 | 5793.34 | 01-APR-06:03 | 1.11 |
May | 0.430639E+10 | 0.47 | 5806.96 | 31-MAY-15:20 | 1.10 |
June | 0.521578E+10 | 0.51 | 6990.09 | 30-JUN-14:30 | 1.18 |
July | 0.503117E+10 | 0.48 | 7219.99 | 12-JUL-15:20 | 1.20 |
August | 0.456394E+10 | 0.48 | 6310.18 | 11-AUG-15:30 | 1.13 |
September | 0.346799E+10 | 0.42 | 5793.34 | 25-SEP-05:01 | 1.10 |
October | 0.423017E+10 | 0.49 | 5793.34 | 14-OCT-05:01 | 1.10 |
November | 0.533432E+10 | 0.64 | 5793.34 | 08-NOV-07:02 | 1.10 |
December | 0.575874E+10 | 0.66 | 5793.34 | 02-DEC-07:03 | 1.11 |
Annual Sum or Average | 0.574088E+11 | 0.54 | |||
Minimum of Months | 0.346799E+10 | 0.42 | 5793.34 | 1.10 | |
Maximum of Months | 0.575874E+10 | 0.66 | 7219.99 | 1.20 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.183722E+10 | 0.165350E+10 | 1592.08 | 12-JAN-07:12 | 1432.87 | 1432.87 | 45.26 | 5.11 |
February | 0.136683E+10 | 0.123015E+10 | 1656.40 | 27-FEB-08:08 | 1490.76 | 1490.76 | 45.65 | 5.30 |
March | 0.105633E+10 | 0.950696E+09 | 1505.70 | 01-MAR-07:01 | 1355.13 | 1355.13 | 47.65 | 4.80 |
April | 0.304571E+09 | 0.274114E+09 | 1443.40 | 03-APR-06:01 | 1299.06 | 1299.06 | 47.89 | 4.51 |
May | 36211696.02 | 32590526.42 | 1071.56 | 27-MAY-06:03 | 964.40 | 964.40 | 34.55 | 1.82 |
June | 5441029.18 | 4896926.26 | 320.64 | 26-JUN-06:03 | 288.57 | 288.57 | 35.49 | 0.36 |
July | 3677840.55 | 3310056.50 | 250.49 | 05-JUL-06:03 | 225.44 | 225.44 | 36.95 | 0.27 |
August | 14062820.14 | 12656538.12 | 1234.57 | 31-AUG-06:03 | 1111.11 | 1111.11 | 36.51 | 2.65 |
September | 0.127173E+09 | 0.114456E+09 | 1349.98 | 25-SEP-06:01 | 1214.98 | 1214.98 | 38.14 | 3.84 |
October | 0.669591E+09 | 0.602632E+09 | 1418.35 | 30-OCT-06:01 | 1276.51 | 1276.51 | 48.45 | 4.36 |
November | 0.157814E+10 | 0.142032E+10 | 1539.37 | 28-NOV-07:25 | 1385.44 | 1385.44 | 45.82 | 4.93 |
December | 0.186457E+10 | 0.167811E+10 | 1552.61 | 15-DEC-07:05 | 1397.35 | 1397.35 | 45.58 | 4.98 |
Annual Sum or Average | 0.886382E+10 | 0.797744E+10 | ||||||
Minimum of Months | 3677840.55 | 3310056.50 | 250.49 | 225.44 | 225.44 | 34.55 | 0.27 | |
Maximum of Months | 0.186457E+10 | 0.167811E+10 | 1656.40 | 1490.76 | 1490.76 | 48.45 | 5.30 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:02 | 2.06 | 2.06 | 57.66 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.59 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.55 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 56.50 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.52 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:02 | 2.06 | 2.06 | 56.46 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:02 | 2.06 | 2.06 | 56.60 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:02 | 2.06 | 2.06 | 56.73 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 56.77 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.73 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:01 | 2.06 | 2.06 | 56.76 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 56.62 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.46 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.73 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 37.77 | 37.77 | 96119.33 | 363928.02 | 19-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 42.44 | 60.00 | 77235.06 | 358092.03 | 09-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 40.52 | 60.00 | 53083.09 | 381136.79 | 23-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34.04 | 34.04 | 15467.61 | 386889.19 | 06-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.30 | 21.30 | 1343.34 | 193464.70 | 27-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 40.12 | 40.12 | 153.42 | 36790.79 | 26-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 35.82 | 35.82 | 114.33 | 26966.15 | 17-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 38.33 | 38.33 | 530.36 | 260286.47 | 31-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.83 | 24.83 | 6392.57 | 361223.47 | 30-SEP-05:01 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24.61 | 24.61 | 33988.70 | 368892.07 | 20-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 35.81 | 35.81 | 84494.54 | 353320.54 | 18-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 45.23 | 60.00 | 99149.72 | 316806.57 | 27-DEC-05:01 |
Annual Sum or Average | 0.00 | 38827.45 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.30 | 21.30 | 114.33 | 26966.15 | ||
Maximum of Months | 0.00 | 0.00 | 45.23 | 60.00 | 99149.72 | 386889.19 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.66 | 57.66 | 2106.65 | 7651.72 | 19-JAN-12:19 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 57.06 | 57.06 | 2119.74 | 7651.73 | 17-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 57.06 | 57.06 | 2267.31 | 7651.70 | 07-MAR-12:16 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.06 | 57.06 | 2107.69 | 7651.62 | 06-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.66 | 57.66 | 2172.08 | 7651.57 | 08-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.13 | 57.13 | 2149.54 | 7461.23 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.24 | 57.24 | 1886.34 | 7150.92 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.34 | 57.34 | 2036.91 | 6936.48 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.37 | 57.37 | 1887.74 | 6889.78 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.28 | 56.28 | 1923.50 | 7094.20 | 31-OCT-11:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.28 | 57.28 | 2024.11 | 7375.23 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 57.16 | 57.16 | 2016.79 | 7651.62 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 2057.87 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.28 | 56.28 | 1886.34 | 6889.78 | ||
Maximum of Months | 0.00 | 0.00 | 57.66 | 57.66 | 2267.31 | 7651.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.793004E+11 | 0.00 | 0.00 | 0.607236E+10 | 0.00 | 0.00 |
February | 0.595289E+11 | 0.00 | 0.00 | 0.518351E+10 | 0.00 | 0.00 |
March | 0.467063E+11 | 0.00 | 0.00 | 0.482427E+10 | 0.00 | 0.00 |
April | 0.136246E+11 | 0.00 | 0.00 | 0.422224E+10 | 0.00 | 0.00 |
May | 0.205060E+10 | 0.00 | 0.00 | 0.673656E+10 | 0.00 | 0.00 |
June | 0.395615E+09 | 0.00 | 0.00 | 0.124213E+11 | 0.00 | 0.00 |
July | 0.292916E+09 | 0.00 | 0.00 | 0.146496E+11 | 0.00 | 0.00 |
August | 0.673807E+09 | 0.00 | 0.00 | 0.112961E+11 | 0.00 | 0.00 |
September | 0.438422E+10 | 0.00 | 0.00 | 0.471796E+10 | 0.00 | 0.00 |
October | 0.243856E+11 | 0.00 | 0.00 | 0.396226E+10 | 0.00 | 0.00 |
November | 0.637593E+11 | 0.00 | 0.00 | 0.475041E+10 | 0.00 | 0.00 |
December | 0.793637E+11 | 0.00 | 0.00 | 0.596139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.374466E+12 | 0.00 | 0.00 | 0.847980E+11 | 0.00 | 0.00 |
Minimum of Months | 0.292916E+09 | 0.00 | 0.00 | 0.396226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.793637E+11 | 0.00 | 0.00 | 0.146496E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.756402E+11 | 0.00 | 0.00 | 0.495884E+10 | 0.00 | 0.00 |
February | 0.533043E+11 | 0.00 | 0.00 | 0.430238E+10 | 0.00 | 0.00 |
March | 0.402398E+11 | 0.00 | 0.00 | 0.404737E+10 | 0.00 | 0.00 |
April | 0.988230E+10 | 0.00 | 0.00 | 0.377791E+10 | 0.00 | 0.00 |
May | 0.304179E+09 | 0.00 | 0.00 | 0.618579E+10 | 0.00 | 0.00 |
June | 150391.03 | 0.00 | 0.00 | 0.118666E+11 | 0.00 | 0.00 |
July | 198448.58 | 0.00 | 0.00 | 0.133463E+11 | 0.00 | 0.00 |
August | 0.102819E+09 | 0.00 | 0.00 | 0.952436E+10 | 0.00 | 0.00 |
September | 0.355849E+10 | 0.00 | 0.00 | 0.361078E+10 | 0.00 | 0.00 |
October | 0.264535E+11 | 0.00 | 0.00 | 0.360828E+10 | 0.00 | 0.00 |
November | 0.646556E+11 | 0.00 | 0.00 | 0.440271E+10 | 0.00 | 0.00 |
December | 0.790437E+11 | 0.00 | 0.00 | 0.491085E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.353185E+12 | 0.00 | 0.00 | 0.745422E+11 | 0.00 | 0.00 |
Minimum of Months | 150391.03 | 0.00 | 0.00 | 0.360828E+10 | 0.00 | 0.00 |
Maximum of Months | 0.790437E+11 | 0.00 | 0.00 | 0.133463E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.104459E+12 | 0.00 | 0.00 | 0.564031E+10 | 0.00 | 0.00 |
February | 0.754703E+11 | 0.00 | 0.00 | 0.489440E+10 | 0.00 | 0.00 |
March | 0.563615E+11 | 0.00 | 0.00 | 0.497827E+10 | 0.00 | 0.00 |
April | 0.169263E+11 | 0.00 | 0.00 | 0.399283E+10 | 0.00 | 0.00 |
May | 0.125443E+10 | 0.00 | 0.00 | 0.553959E+10 | 0.00 | 0.00 |
June | 13179128.85 | 0.00 | 0.00 | 0.111461E+11 | 0.00 | 0.00 |
July | 13342054.14 | 0.00 | 0.00 | 0.130148E+11 | 0.00 | 0.00 |
August | 0.676827E+09 | 0.00 | 0.00 | 0.893140E+10 | 0.00 | 0.00 |
September | 0.876275E+10 | 0.00 | 0.00 | 0.355155E+10 | 0.00 | 0.00 |
October | 0.408946E+11 | 0.00 | 0.00 | 0.423119E+10 | 0.00 | 0.00 |
November | 0.922627E+11 | 0.00 | 0.00 | 0.533485E+10 | 0.00 | 0.00 |
December | 0.109160E+12 | 0.00 | 0.00 | 0.575920E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.506255E+12 | 0.00 | 0.00 | 0.770145E+11 | 0.00 | 0.00 |
Minimum of Months | 13179128.85 | 0.00 | 0.00 | 0.355155E+10 | 0.00 | 0.00 |
Maximum of Months | 0.109160E+12 | 0.00 | 0.00 | 0.130148E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.607232E+10 | 117997.87 | 0.793004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518351E+10 | 0.00 | 0.595289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482427E+10 | 0.00 | 0.467063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.421826E+10 | 14048867.72 | 0.136246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555145E+10 | 0.465280E+10 | 0.205060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.685757E+10 | 0.233321E+11 | 0.395615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.705474E+10 | 0.326762E+11 | 0.292916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.692474E+10 | 0.184641E+11 | 0.673807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.461425E+10 | 0.376694E+09 | 0.438422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.396226E+10 | 0.00 | 0.243856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.475041E+10 | 0.00 | 0.637593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.596139E+10 | 0.00 | 0.793637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659752E+11 | 0.795161E+11 | 0.374466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.396226E+10 | 0.00 | 0.292916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.705474E+10 | 0.326762E+11 | 0.793637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.495883E+10 | 53710.67 | 0.756402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.430238E+10 | 0.00 | 0.533043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404737E+10 | 0.00 | 0.402398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377323E+10 | 16576571.10 | 0.988230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.498963E+10 | 0.469459E+10 | 0.304179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.642323E+10 | 0.228225E+11 | 150391.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.620989E+10 | 0.305694E+11 | 198448.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.559846E+10 | 0.164733E+11 | 0.102819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.352373E+10 | 0.315393E+09 | 0.355849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360827E+10 | 37463.67 | 0.264535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.440271E+10 | 0.00 | 0.646556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491085E+10 | 0.00 | 0.790437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.567486E+11 | 0.748918E+11 | 0.353185E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.352373E+10 | 0.00 | 150391.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.642323E+10 | 0.305694E+11 | 0.790437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.563986E+10 | 1574001.17 | 0.104459E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489385E+10 | 1900867.26 | 0.754703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.497773E+10 | 1907717.17 | 0.563615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398887E+10 | 13938093.36 | 0.169263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.430639E+10 | 0.467137E+10 | 0.125443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.521578E+10 | 0.239426E+11 | 13179128.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.503117E+10 | 0.329502E+11 | 13342054.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.456394E+10 | 0.176237E+11 | 0.676827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346799E+10 | 0.299000E+09 | 0.876275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.423017E+10 | 3533004.88 | 0.408946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.533432E+10 | 1859336.16 | 0.922627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.575874E+10 | 1581708.17 | 0.109160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.574088E+11 | 0.795132E+11 | 0.506255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.346799E+10 | 1574001.17 | 13179128.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.575874E+10 | 0.329502E+11 | 0.109160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.607232E+10 | 0.793004E+11 | 0.00 | 0.00 | 33786.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518351E+10 | 0.595289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482427E+10 | 0.467063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.421826E+10 | 0.136246E+11 | 0.00 | 0.00 | 3978072.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.555145E+10 | 0.205060E+10 | 0.00 | 0.00 | 0.118511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.685757E+10 | 0.395615E+09 | 0.00 | 0.00 | 0.556372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.705474E+10 | 0.292916E+09 | 0.00 | 0.00 | 0.759489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.692474E+10 | 0.673807E+09 | 0.00 | 0.00 | 0.437139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.461425E+10 | 0.438422E+10 | 0.00 | 0.00 | 0.103704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.396226E+10 | 0.243856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.475041E+10 | 0.637593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.596139E+10 | 0.793637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659752E+11 | 0.374466E+12 | 0.00 | 0.00 | 0.188228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.396226E+10 | 0.292916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.705474E+10 | 0.793637E+11 | 0.00 | 0.00 | 0.759489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.495883E+10 | 0.756402E+11 | 0.00 | 0.00 | 15388.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.430238E+10 | 0.533043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404737E+10 | 0.402398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377323E+10 | 0.988230E+10 | 0.00 | 0.00 | 4686438.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.498963E+10 | 0.304179E+09 | 0.00 | 0.00 | 0.119616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.642323E+10 | 150391.03 | 0.00 | 0.00 | 0.544339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.620989E+10 | 198448.58 | 0.00 | 0.00 | 0.713644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.559846E+10 | 0.102819E+09 | 0.00 | 0.00 | 0.392590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.352373E+10 | 0.355849E+10 | 0.00 | 0.00 | 87050530.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360827E+10 | 0.264535E+11 | 0.00 | 0.00 | 10746.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.440271E+10 | 0.646556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491085E+10 | 0.790437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.567486E+11 | 0.353185E+12 | 0.00 | 0.00 | 0.177936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.352373E+10 | 150391.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.642323E+10 | 0.790437E+11 | 0.00 | 0.00 | 0.713644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.563986E+10 | 0.104459E+12 | 0.00 | 0.00 | 449439.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489385E+10 | 0.754703E+11 | 0.00 | 0.00 | 543870.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.497773E+10 | 0.563615E+11 | 0.00 | 0.00 | 546942.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398887E+10 | 0.169263E+11 | 0.00 | 0.00 | 3965116.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.430639E+10 | 0.125443E+10 | 0.00 | 0.00 | 0.123320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.521578E+10 | 13179128.85 | 0.00 | 0.00 | 0.593034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.503117E+10 | 13342054.14 | 0.00 | 0.00 | 0.798360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.456394E+10 | 0.676827E+09 | 0.00 | 0.00 | 0.436746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346799E+10 | 0.876275E+10 | 0.00 | 0.00 | 83561223.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.423017E+10 | 0.408946E+11 | 0.00 | 0.00 | 1012754.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.533432E+10 | 0.922627E+11 | 0.00 | 0.00 | 532179.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.575874E+10 | 0.109160E+12 | 0.00 | 0.00 | 452257.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.574088E+11 | 0.506255E+12 | 0.00 | 0.00 | 0.196057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.346799E+10 | 13179128.85 | 0.00 | 0.00 | 449439.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.575874E+10 | 0.109160E+12 | 0.00 | 0.00 | 0.798360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.221378E+11 | 0.00 | 0.00 | 38672.85 | 0.00 | 0.922231E+09 | 0.261311E+09 | 0.00 | 0.25 |
February | 0.184703E+11 | 0.00 | 0.00 | 591782.94 | 0.00 | 0.196254E+09 | 0.115975E+10 | 0.00 | 0.26 |
March | 0.171410E+11 | 0.00 | 0.00 | 3458149.08 | 0.00 | 16813169.31 | 0.380886E+10 | 0.00 | 0.27 |
April | 0.559745E+10 | 0.00 | 0.00 | 24387098.91 | 0.00 | 851666.67 | 0.127906E+11 | 0.00 | 0.43 |
May | 0.111810E+10 | 0.00 | 0.00 | 45626080.30 | 0.00 | 0.00 | 0.237916E+11 | 0.00 | 0.95 |
June | 0.623805E+09 | 8728380.76 | 0.00 | 53303280.57 | 0.00 | 0.00 | 0.213588E+11 | 0.00 | 1.26 |
July | 0.944211E+09 | 93273986.01 | 0.00 | 50865004.03 | 8857979.84 | 0.00 | 0.162774E+11 | 0.00 | 1.13 |
August | 0.806243E+09 | 454182.65 | 0.00 | 56489859.89 | 0.00 | 0.00 | 0.239173E+11 | 0.00 | 1.18 |
September | 0.175036E+10 | 0.00 | 0.00 | 40443489.16 | 0.00 | 0.00 | 0.197507E+11 | 0.00 | 0.61 |
October | 0.866201E+10 | 0.00 | 0.00 | 14055775.09 | 0.00 | 889031.53 | 0.889885E+10 | 0.00 | 0.30 |
November | 0.208607E+11 | 0.00 | 0.00 | 493819.98 | 0.00 | 97547399.20 | 0.145127E+10 | 0.00 | 0.24 |
December | 0.245893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232301E+09 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.122701E+12 | 0.102457E+09 | 0.00 | 0.289753E+09 | 8857979.84 | 0.146689E+10 | 0.133466E+12 | 0.00 | 0.60 |
Minimum of Months | 0.623805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.245893E+11 | 93273986.01 | 0.00 | 56489859.89 | 8857979.84 | 0.922231E+09 | 0.239173E+11 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469918E+10 | 0.00 | 0.00 | 0.23 |
February | 0.151471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303387E+10 | 0.00 | 0.00 | 0.24 |
March | 0.181012E+11 | 0.00 | 0.00 | 902.90 | 0.00 | 0.727426E+09 | 16857073.44 | 0.00 | 0.25 |
April | 0.970732E+10 | 0.00 | 0.00 | 5655479.01 | 0.00 | 0.103483E+09 | 0.397717E+10 | 0.00 | 0.32 |
May | 0.440042E+10 | 0.00 | 0.00 | 22417401.19 | 0.00 | 0.00 | 0.129937E+11 | 0.00 | 0.67 |
June | 0.159629E+10 | 7366995.10 | 0.00 | 33658348.31 | 0.00 | 0.00 | 0.142357E+11 | 0.00 | 0.91 |
July | 0.164684E+10 | 67260200.73 | 0.00 | 31395432.04 | 8675095.77 | 0.00 | 0.102159E+11 | 0.00 | 0.79 |
August | 0.222178E+10 | 873970.29 | 0.00 | 30429700.97 | 0.00 | 0.00 | 0.137245E+11 | 0.00 | 0.79 |
September | 0.730182E+10 | 0.00 | 0.00 | 10534271.26 | 0.00 | 925166.28 | 0.602247E+10 | 0.00 | 0.38 |
October | 0.138020E+11 | 0.00 | 0.00 | 521477.38 | 0.00 | 0.301986E+09 | 0.658157E+09 | 0.00 | 0.25 |
November | 0.176027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355066E+10 | 0.00 | 0.00 | 0.23 |
December | 0.170301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597431E+10 | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.125597E+12 | 75501166.11 | 0.00 | 0.134613E+09 | 8675095.77 | 0.183918E+11 | 0.618444E+11 | 0.00 | 0.44 |
Minimum of Months | 0.159629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.181012E+11 | 67260200.73 | 0.00 | 33658348.31 | 8675095.77 | 0.597431E+10 | 0.142357E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.628985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132387E+11 | 0.00 | 0.00 | 0.22 |
February | 0.742715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872492E+10 | 0.00 | 0.00 | 0.22 |
March | 0.126816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472533E+10 | 0.00 | 0.00 | 0.24 |
April | 0.120506E+11 | 0.00 | 0.00 | 887078.69 | 0.00 | 0.930199E+09 | 0.112745E+10 | 0.00 | 0.34 |
May | 0.828979E+10 | 0.00 | 0.00 | 12883536.38 | 0.00 | 2800815.48 | 0.921249E+10 | 0.00 | 0.69 |
June | 0.399932E+10 | 7837990.17 | 0.00 | 27584919.68 | 0.00 | 0.00 | 0.119239E+11 | 0.00 | 0.93 |
July | 0.378058E+10 | 65012221.09 | 0.00 | 24065433.98 | 16908314.94 | 0.00 | 0.749356E+10 | 0.00 | 0.80 |
August | 0.566712E+10 | 6236336.38 | 0.00 | 18036737.02 | 1238571.74 | 1126527.23 | 0.861732E+10 | 0.00 | 0.77 |
September | 0.117158E+11 | 0.00 | 0.00 | 609153.45 | 0.00 | 0.213370E+09 | 0.111228E+10 | 0.00 | 0.41 |
October | 0.103705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342410E+10 | 0.00 | 0.00 | 0.25 |
November | 0.747395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114617E+11 | 0.00 | 0.00 | 0.22 |
December | 0.567574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147541E+11 | 0.00 | 0.00 | 0.21 |
Annual Sum or Average | 0.954220E+11 | 79086547.64 | 0.00 | 84066859.21 | 18146886.69 | 0.574763E+11 | 0.394870E+11 | 0.00 | 0.44 |
Minimum of Months | 0.378058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Maximum of Months | 0.126816E+11 | 65012221.09 | 0.00 | 27584919.68 | 16908314.94 | 0.147541E+11 | 0.119239E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75668923.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880254E+10 | 0.00 | 0.00 | 0.46 |
February | 0.133329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714415E+10 | 0.00 | 0.00 | 0.47 |
March | 0.802975E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701015E+10 | 0.00 | 0.00 | 0.51 |
April | 0.423290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203315E+10 | 0.00 | 0.00 | 0.72 |
May | 0.626106E+10 | 0.00 | 0.00 | 411631.19 | 0.00 | 0.123688E+09 | 0.944411E+09 | 0.00 | 1.35 |
June | 0.281662E+10 | 3173412.75 | 0.00 | 4946775.07 | 0.00 | 0.00 | 0.298189E+10 | 0.00 | 1.60 |
July | 0.256272E+10 | 17038087.04 | 0.00 | 4293968.83 | 15573366.06 | 0.00 | 0.171873E+10 | 0.00 | 1.41 |
August | 0.481091E+10 | 0.00 | 0.00 | 1215210.78 | 3318959.93 | 47079160.42 | 0.961222E+09 | 0.00 | 1.45 |
September | 0.462723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116357E+10 | 0.00 | 0.00 | 0.85 |
October | 0.126080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487275E+10 | 0.00 | 0.00 | 0.53 |
November | 64004310.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842730E+10 | 0.00 | 0.00 | 0.46 |
December | 0.102554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910412E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.277508E+11 | 20211499.79 | 0.00 | 10867585.86 | 18892326.00 | 0.487285E+11 | 0.660624E+10 | 0.00 | 0.86 |
Minimum of Months | 64004310.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.626106E+10 | 17038087.04 | 0.00 | 4946775.07 | 15573366.06 | 0.910412E+10 | 0.298189E+10 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 48542878.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576557E+10 | 0.00 | 0.00 | 0.48 |
February | 0.168065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457746E+10 | 0.00 | 0.00 | 0.48 |
March | 0.193275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316937E+10 | 0.00 | 0.00 | 0.53 |
April | 0.269458E+10 | 0.00 | 0.00 | 581901.40 | 0.00 | 0.850798E+09 | 0.566212E+09 | 0.00 | 0.75 |
May | 0.213716E+10 | 0.00 | 0.00 | 5487751.91 | 0.00 | 25114644.04 | 0.345052E+10 | 0.00 | 1.63 |
June | 0.104046E+10 | 2296995.50 | 0.00 | 8311503.25 | 0.00 | 0.00 | 0.394491E+10 | 0.00 | 2.11 |
July | 0.112984E+10 | 15816799.96 | 0.00 | 7924115.29 | 6441519.40 | 0.00 | 0.250137E+10 | 0.00 | 1.92 |
August | 0.190326E+10 | 0.00 | 0.00 | 4499889.61 | 2168584.14 | 13297010.94 | 0.242989E+10 | 0.00 | 1.70 |
September | 0.315102E+10 | 0.00 | 0.00 | 162959.80 | 0.00 | 0.447203E+09 | 0.185189E+09 | 0.00 | 0.88 |
October | 0.127564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273155E+10 | 0.00 | 0.00 | 0.55 |
November | 41819948.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551046E+10 | 0.00 | 0.00 | 0.47 |
December | 65700582.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595686E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.155888E+11 | 18113795.45 | 0.00 | 26968121.26 | 8610103.54 | 0.290477E+11 | 0.130781E+11 | 0.00 | 1.00 |
Minimum of Months | 41819948.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.315102E+10 | 15816799.96 | 0.00 | 8311503.25 | 6441519.40 | 0.595686E+10 | 0.394491E+10 | 0.00 | 2.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.281588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851664E+10 | 0.00 | 0.00 | 0.46 |
February | 0.152194E+10 | 0.00 | 0.00 | 7385.30 | 0.00 | 0.564185E+10 | 39331732.62 | 0.00 | 0.46 |
March | 0.310011E+10 | 0.00 | 0.00 | 894205.31 | 0.00 | 0.393316E+10 | 0.737071E+09 | 0.00 | 0.51 |
April | 0.283301E+10 | 0.00 | 0.00 | 6232721.98 | 0.00 | 0.118096E+10 | 0.317892E+10 | 0.00 | 0.86 |
May | 0.363787E+10 | 0.00 | 0.00 | 8678661.34 | 0.00 | 91317487.14 | 0.494777E+10 | 0.00 | 1.64 |
June | 0.241397E+10 | 3872734.48 | 0.00 | 10999177.91 | 0.00 | 824986.29 | 0.463965E+10 | 0.00 | 1.99 |
July | 0.231985E+10 | 40953018.69 | 0.00 | 9962225.49 | 4855668.79 | 844105.60 | 0.268148E+10 | 0.00 | 1.74 |
August | 0.317615E+10 | 757493.82 | 0.00 | 9420301.59 | 2541288.75 | 46422420.49 | 0.375359E+10 | 0.00 | 1.82 |
September | 0.372570E+10 | 0.00 | 0.00 | 3187636.40 | 0.00 | 0.713710E+09 | 0.165376E+10 | 0.00 | 0.91 |
October | 0.243763E+10 | 0.00 | 0.00 | 592231.24 | 0.00 | 0.339400E+10 | 0.297575E+09 | 0.00 | 0.53 |
November | 0.540446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789547E+10 | 0.00 | 0.00 | 0.46 |
December | 0.101931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904974E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.260902E+11 | 45583247.00 | 0.00 | 49974546.56 | 7396957.54 | 0.404649E+11 | 0.219291E+11 | 0.00 | 0.99 |
Minimum of Months | 0.101931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 824986.29 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.372570E+10 | 40953018.69 | 0.00 | 10999177.91 | 4855668.79 | 0.904974E+10 | 0.494777E+10 | 0.00 | 1.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49156426.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574509E+10 | 0.00 | 0.00 | 0.48 |
February | 0.169398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456080E+10 | 0.00 | 0.00 | 0.48 |
March | 0.110878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396291E+10 | 0.00 | 0.00 | 0.52 |
April | 0.230722E+10 | 0.00 | 0.00 | 1338877.52 | 0.00 | 0.106527E+10 | 0.850221E+09 | 0.00 | 0.78 |
May | 0.323870E+10 | 0.00 | 0.00 | 2254792.57 | 0.00 | 0.102537E+09 | 0.166086E+10 | 0.00 | 1.48 |
June | 0.176863E+10 | 2582568.19 | 0.00 | 5556847.77 | 0.00 | 539209.83 | 0.232709E+10 | 0.00 | 1.86 |
July | 0.167013E+10 | 20118880.58 | 0.00 | 4311009.15 | 5142462.59 | 1096872.71 | 0.122260E+10 | 0.00 | 1.55 |
August | 0.275852E+10 | 1603774.44 | 0.00 | 2681727.63 | 552305.00 | 34900076.31 | 0.111234E+10 | 0.00 | 1.59 |
September | 0.283755E+10 | 0.00 | 0.00 | 236467.97 | 0.00 | 0.685006E+09 | 0.243875E+09 | 0.00 | 0.88 |
October | 0.924212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306017E+10 | 0.00 | 0.00 | 0.54 |
November | 54479947.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546758E+10 | 0.00 | 0.00 | 0.47 |
December | 65321733.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592626E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.169521E+11 | 24305223.22 | 0.00 | 16379722.62 | 5694767.59 | 0.306122E+11 | 0.741698E+10 | 0.00 | 0.93 |
Minimum of Months | 49156426.39 | 0.00 | 0.00 | 0.00 | 0.00 | 539209.83 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.323870E+10 | 20118880.58 | 0.00 | 5556847.77 | 5142462.59 | 0.592626E+10 | 0.232709E+10 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916509E+10 | 0.00 | 0.00 | 0.47 |
February | 0.130863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795726E+10 | 0.00 | 0.00 | 0.49 |
March | 0.264959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784463E+10 | 0.00 | 0.00 | 0.50 |
April | 0.315942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283835E+10 | 0.00 | 0.00 | 0.64 |
May | 0.614957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83245922.92 | 0.00 | 0.00 | 1.10 |
June | 0.332843E+10 | 1205281.97 | 0.00 | 1570679.82 | 592205.16 | 0.00 | 0.134746E+10 | 0.00 | 1.27 |
July | 0.258250E+10 | 9571852.65 | 0.00 | 2547844.42 | 15697344.27 | 0.00 | 0.113015E+10 | 0.00 | 1.13 |
August | 0.457216E+10 | 0.00 | 0.00 | 813402.06 | 133102.00 | 4589970.50 | 0.859824E+09 | 0.00 | 1.23 |
September | 0.551741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472257E+09 | 0.00 | 0.00 | 0.79 |
October | 0.227522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398441E+10 | 0.00 | 0.00 | 0.50 |
November | 0.122936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850095E+10 | 0.00 | 0.00 | 0.44 |
December | 0.320977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936521E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.286131E+11 | 10777134.62 | 0.00 | 4931926.30 | 16422651.43 | 0.502160E+11 | 0.333743E+10 | 0.00 | 0.75 |
Minimum of Months | 0.122936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.614957E+10 | 9571852.65 | 0.00 | 2547844.42 | 15697344.27 | 0.936521E+10 | 0.134746E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608681E+10 | 0.00 | 0.00 | 0.49 |
February | 0.127281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511226E+10 | 0.00 | 0.00 | 0.50 |
March | 0.126779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403410E+10 | 0.00 | 0.00 | 0.51 |
April | 0.264044E+10 | 0.00 | 0.00 | 127636.09 | 0.00 | 0.112505E+10 | 0.175829E+09 | 0.00 | 0.67 |
May | 0.213772E+10 | 0.00 | 0.00 | 3619866.94 | 0.00 | 505452.65 | 0.242553E+10 | 0.00 | 1.28 |
June | 0.954359E+09 | 1606685.42 | 0.00 | 6197305.13 | 69477.35 | 0.00 | 0.296090E+10 | 0.00 | 1.66 |
July | 0.871653E+09 | 14654732.90 | 0.00 | 7027972.02 | 2926815.70 | 0.00 | 0.231300E+10 | 0.00 | 1.59 |
August | 0.134654E+10 | 0.00 | 0.00 | 5160870.47 | 87676.09 | 974285.65 | 0.287112E+10 | 0.00 | 1.51 |
September | 0.335473E+10 | 0.00 | 0.00 | 383966.01 | 0.00 | 0.141559E+09 | 0.453395E+09 | 0.00 | 0.83 |
October | 0.181397E+10 | 0.00 | 0.00 | 2352.53 | 0.00 | 0.229965E+10 | 8213793.40 | 0.00 | 0.52 |
November | 73915280.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561849E+10 | 0.00 | 0.00 | 0.46 |
December | 0.173157E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624454E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.148672E+11 | 16261418.32 | 0.00 | 22519969.19 | 3083969.13 | 0.306640E+11 | 0.112080E+11 | 0.00 | 0.88 |
Minimum of Months | 73915280.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.335473E+10 | 14654732.90 | 0.00 | 7027972.02 | 2926815.70 | 0.624454E+10 | 0.296090E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123841E+11 | 0.00 | 0.00 | 0.62 |
February | 0.397001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938423E+10 | 0.00 | 0.00 | 0.58 |
March | 0.101382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817196E+10 | 0.00 | 0.00 | 0.56 |
April | 0.304735E+10 | 0.00 | 0.00 | 866942.01 | 0.00 | 0.271757E+10 | 0.669577E+09 | 0.00 | 0.69 |
May | 0.440827E+10 | 0.00 | 0.00 | 2158130.67 | 0.00 | 0.739807E+09 | 0.139240E+10 | 0.00 | 1.17 |
June | 0.276295E+10 | 3035497.24 | 0.00 | 5080288.11 | 0.00 | 0.264773E+09 | 0.195364E+10 | 0.00 | 1.40 |
July | 0.217902E+10 | 30705341.22 | 0.00 | 6802566.39 | 3311372.43 | 0.227260E+09 | 0.161344E+10 | 0.00 | 1.32 |
August | 0.306760E+10 | 132274.27 | 0.00 | 6526684.79 | 0.00 | 0.433226E+09 | 0.254180E+10 | 0.00 | 1.47 |
September | 0.400710E+10 | 0.00 | 0.00 | 1568094.26 | 0.00 | 0.144719E+10 | 0.952186E+09 | 0.00 | 0.85 |
October | 0.152519E+10 | 0.00 | 0.00 | 162655.42 | 0.00 | 0.538622E+10 | 0.109365E+09 | 0.00 | 0.55 |
November | 0.134366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113355E+11 | 0.00 | 0.00 | 0.58 |
December | 0.181361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136621E+11 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.228689E+11 | 33873112.73 | 0.00 | 23165361.67 | 3311372.43 | 0.661540E+11 | 0.923241E+10 | 0.00 | 0.87 |
Minimum of Months | 0.134366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227260E+09 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.440827E+10 | 30705341.22 | 0.00 | 6802566.39 | 3311372.43 | 0.136621E+11 | 0.254180E+10 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609790E+10 | 0.00 | 0.00 | 0.49 |
February | 98413715.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519265E+10 | 0.00 | 0.00 | 0.50 |
March | 0.488111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480413E+10 | 0.00 | 0.00 | 0.51 |
April | 0.244059E+10 | 0.00 | 0.00 | 331594.56 | 0.00 | 0.118800E+10 | 0.310238E+09 | 0.00 | 0.67 |
May | 0.350056E+10 | 0.00 | 0.00 | 734807.31 | 0.00 | 72611290.70 | 0.535847E+09 | 0.00 | 1.15 |
June | 0.174423E+10 | 1412528.17 | 0.00 | 3239827.05 | 0.00 | 0.00 | 0.143538E+10 | 0.00 | 1.41 |
July | 0.148340E+10 | 14773347.10 | 0.00 | 3254603.73 | 3955373.19 | 0.00 | 0.999142E+09 | 0.00 | 1.23 |
August | 0.243134E+10 | 87133.04 | 0.00 | 2501172.92 | 0.00 | 968251.11 | 0.121005E+10 | 0.00 | 1.34 |
September | 0.350650E+10 | 0.00 | 0.00 | 168148.22 | 0.00 | 0.217628E+09 | 0.197350E+09 | 0.00 | 0.82 |
October | 0.158356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251413E+10 | 0.00 | 0.00 | 0.51 |
November | 91493058.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556883E+10 | 0.00 | 0.00 | 0.46 |
December | 0.172078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621499E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.176443E+11 | 16273008.30 | 0.00 | 10230153.79 | 3955373.19 | 0.318718E+11 | 0.468801E+10 | 0.00 | 0.80 |
Minimum of Months | 91493058.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.350650E+10 | 14773347.10 | 0.00 | 3254603.73 | 3955373.19 | 0.621499E+10 | 0.143538E+10 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937519E+10 | 0.00 | 0.00 | 0.48 |
February | 0.333505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757334E+10 | 0.00 | 0.00 | 0.49 |
March | 0.157464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655749E+10 | 0.00 | 0.00 | 0.51 |
April | 0.415954E+10 | 0.00 | 0.00 | 286.44 | 0.00 | 0.155130E+10 | 17260812.49 | 0.00 | 0.62 |
May | 0.434652E+10 | 0.00 | 0.00 | 1514086.27 | 0.00 | 3728703.77 | 0.168730E+10 | 0.00 | 1.08 |
June | 0.117433E+10 | 2450285.94 | 0.00 | 7996297.33 | 0.00 | 0.00 | 0.381489E+10 | 0.00 | 1.37 |
July | 0.135506E+10 | 23111096.19 | 0.00 | 6850003.26 | 4298922.10 | 0.00 | 0.241490E+10 | 0.00 | 1.20 |
August | 0.304857E+10 | 15781.24 | 0.00 | 3146367.12 | 356157.02 | 3553157.80 | 0.199963E+10 | 0.00 | 1.18 |
September | 0.489906E+10 | 0.00 | 0.00 | 10122.53 | 0.00 | 0.455591E+09 | 41005390.77 | 0.00 | 0.72 |
October | 0.221253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409568E+10 | 0.00 | 0.00 | 0.50 |
November | 94619756.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903434E+10 | 0.00 | 0.00 | 0.48 |
December | 0.144951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984671E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.234511E+11 | 25577163.38 | 0.00 | 19517162.94 | 4655079.12 | 0.484969E+11 | 0.997499E+10 | 0.00 | 0.76 |
Minimum of Months | 94619756.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.489906E+10 | 23111096.19 | 0.00 | 7996297.33 | 4298922.10 | 0.984671E+10 | 0.381489E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 90964565.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638510E+10 | 0.00 | 0.00 | 0.51 |
February | 0.501043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469285E+10 | 0.00 | 0.00 | 0.50 |
March | 0.206985E+10 | 0.00 | 0.00 | 75933.57 | 0.00 | 0.307138E+10 | 68296759.61 | 0.00 | 0.51 |
April | 0.237158E+10 | 0.00 | 0.00 | 1423925.20 | 0.00 | 0.674395E+09 | 0.901283E+09 | 0.00 | 0.68 |
May | 0.180024E+10 | 0.00 | 0.00 | 6665070.19 | 0.00 | 598377.38 | 0.382231E+10 | 0.00 | 1.59 |
June | 0.775969E+09 | 2071763.40 | 0.00 | 8916615.33 | 0.00 | 0.00 | 0.406335E+10 | 0.00 | 2.01 |
July | 0.862296E+09 | 18410529.38 | 0.00 | 8525577.09 | 3105288.96 | 0.00 | 0.280016E+10 | 0.00 | 1.84 |
August | 0.140648E+10 | 0.00 | 0.00 | 5986147.55 | 294154.85 | 1668237.59 | 0.301325E+10 | 0.00 | 1.60 |
September | 0.279324E+10 | 0.00 | 0.00 | 896417.62 | 0.00 | 0.201175E+09 | 0.589842E+09 | 0.00 | 0.77 |
October | 0.155494E+10 | 0.00 | 0.00 | 41678.27 | 0.00 | 0.245521E+10 | 21095387.91 | 0.00 | 0.51 |
November | 89610036.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606731E+10 | 0.00 | 0.00 | 0.51 |
December | 0.115163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680448E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.144314E+11 | 20482292.78 | 0.00 | 32531364.82 | 3399443.81 | 0.303542E+11 | 0.152796E+11 | 0.00 | 0.97 |
Minimum of Months | 89610036.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.279324E+10 | 18410529.38 | 0.00 | 8916615.33 | 3105288.96 | 0.680448E+10 | 0.406335E+10 | 0.00 | 2.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.664671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105872E+11 | 0.00 | 0.00 | 0.57 |
February | 0.261247E+10 | 0.00 | 0.00 | 69396.14 | 0.00 | 0.665569E+10 | 0.118642E+09 | 0.00 | 0.58 |
March | 0.426284E+10 | 0.00 | 0.00 | 1673193.64 | 0.00 | 0.424721E+10 | 0.134935E+10 | 0.00 | 0.62 |
April | 0.342031E+10 | 0.00 | 0.00 | 7565948.62 | 0.00 | 0.985377E+09 | 0.376828E+10 | 0.00 | 0.94 |
May | 0.353630E+10 | 0.00 | 0.00 | 9818235.66 | 0.00 | 9441076.07 | 0.531290E+10 | 0.00 | 1.66 |
June | 0.206790E+10 | 4449031.01 | 0.00 | 11632565.95 | 0.00 | 0.00 | 0.481638E+10 | 0.00 | 1.96 |
July | 0.216081E+10 | 44897655.37 | 0.00 | 10592359.15 | 4285508.75 | 0.00 | 0.290403E+10 | 0.00 | 1.72 |
August | 0.291789E+10 | 447217.07 | 0.00 | 10981746.21 | 0.00 | 4043041.26 | 0.453167E+10 | 0.00 | 1.84 |
September | 0.446084E+10 | 0.00 | 0.00 | 4580738.08 | 0.00 | 0.239736E+09 | 0.241144E+10 | 0.00 | 0.98 |
October | 0.372861E+10 | 0.00 | 0.00 | 1052011.91 | 0.00 | 0.340582E+10 | 0.543509E+09 | 0.00 | 0.62 |
November | 0.134856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954924E+10 | 0.00 | 0.00 | 0.57 |
December | 0.174166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117146E+11 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.313554E+11 | 49793903.45 | 0.00 | 57966195.34 | 4285508.75 | 0.473984E+11 | 0.257562E+11 | 0.00 | 1.05 |
Minimum of Months | 0.174166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.446084E+10 | 44897655.37 | 0.00 | 11632565.95 | 4285508.75 | 0.117146E+11 | 0.531290E+10 | 0.00 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 84839243.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728933E+10 | 0.00 | 0.00 | 0.59 |
February | 0.430151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573164E+10 | 0.00 | 0.00 | 0.60 |
March | 0.192696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442155E+10 | 0.00 | 0.00 | 0.63 |
April | 0.273397E+10 | 0.00 | 0.00 | 1585936.32 | 0.00 | 0.984994E+09 | 0.993195E+09 | 0.00 | 0.82 |
May | 0.314022E+10 | 0.00 | 0.00 | 2593591.89 | 0.00 | 12219243.07 | 0.186057E+10 | 0.00 | 1.45 |
June | 0.143877E+10 | 1948631.79 | 0.00 | 6097184.92 | 0.00 | 0.00 | 0.253946E+10 | 0.00 | 1.81 |
July | 0.151386E+10 | 22339897.87 | 0.00 | 4874162.94 | 3977183.64 | 0.00 | 0.140391E+10 | 0.00 | 1.51 |
August | 0.257742E+10 | 292261.86 | 0.00 | 3281606.17 | 0.00 | 4928530.21 | 0.150923E+10 | 0.00 | 1.55 |
September | 0.356678E+10 | 0.00 | 0.00 | 419134.76 | 0.00 | 0.313593E+09 | 0.378515E+09 | 0.00 | 0.91 |
October | 0.185077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309657E+10 | 0.00 | 0.00 | 0.62 |
November | 0.113326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701847E+10 | 0.00 | 0.00 | 0.59 |
December | 0.113944E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767042E+10 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.194910E+11 | 24580791.52 | 0.00 | 18851617.01 | 3977183.64 | 0.365437E+11 | 0.868489E+10 | 0.00 | 0.97 |
Minimum of Months | 84839243.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.356678E+10 | 22339897.87 | 0.00 | 6097184.92 | 3977183.64 | 0.767042E+10 | 0.253946E+10 | 0.00 | 1.81 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.247738E+10 | 0.218054E+11 | 0.00 | 0.193582E+12 | 0.111232E+12 |
February | 0.575718E+11 | 0.175004E+11 | 0.00 | 0.171947E+12 | 0.868788E+11 |
March | 0.219451E+12 | 0.230317E+11 | 0.00 | 0.206496E+12 | 0.777540E+11 |
April | 0.362829E+12 | 0.204187E+11 | 0.00 | 0.245074E+12 | 0.251847E+11 |
May | 0.436049E+12 | 0.120024E+11 | 0.00 | 0.330000E+12 | 0.203260E+11 |
June | 0.444791E+12 | 0.675719E+10 | 0.00 | 0.298830E+12 | 0.873426E+11 |
July | 0.404021E+12 | 0.525801E+10 | 0.00 | 0.314343E+12 | 0.119148E+12 |
August | 0.306585E+12 | 0.717420E+10 | 0.00 | 0.311098E+12 | 0.662708E+11 |
September | 0.151452E+12 | 0.960241E+10 | 0.00 | 0.281313E+12 | 0.130343E+11 |
October | 0.741023E+11 | 0.187852E+11 | 0.00 | 0.210608E+12 | 0.530069E+11 |
November | 0.173313E+11 | 0.146202E+11 | 0.00 | 0.201352E+12 | 0.988499E+11 |
December | -0.653437E+10 | 0.189080E+11 | 0.00 | 0.201267E+12 | 0.110422E+12 |
Annual Sum or Average | 0.247013E+13 | 0.175864E+12 | 0.00 | 0.296591E+13 | 0.869450E+12 |
Minimum of Months | -0.653437E+10 | 0.525801E+10 | 0.00 | 0.171947E+12 | 0.130343E+11 |
Maximum of Months | 0.444791E+12 | 0.230317E+11 | 0.00 | 0.330000E+12 | 0.119148E+12 |