Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2024-07-03 12:21:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2092.33 | 419.96 | 419.96 |
Net Site Energy | 2092.33 | 419.96 | 419.96 |
Total Source Energy | 6479.86 | 1300.61 | 1300.61 |
Net Source Energy | 6479.86 | 1300.61 | 1300.61 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 70.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 237.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 236.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 176.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 48.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2021.98 | 70.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 70.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 237.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 236.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 176.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 48.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 70.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 237.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 236.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 176.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 48.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 92.91 | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 405.84 | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 92.91 | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 405.84 | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2021.978 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2021.978 | 100.00 |
Total On-Site and Utility Electric Sources | 2021.978 | 100.00 |
Total Electricity End Uses | 2021.978 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 32.33 |
Time Setpoint Not Met During Occupied Cooling | 108.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 748.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-10:00 | 09-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 14-FEB-12:09 |
Heating | 0.00 | 143987.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 78826.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20630.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4261.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 196515.56 | 143987.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 143987.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 78826.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 20630.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4261.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 76.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 750.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 747.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 559.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 154.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6403.61 | 76.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 150.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 112.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1285.30 | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 150.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 112.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1285.30 | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.39 | 0.221348 | 0.300000 | 1.02 | 0.590261 | 0.500000 | 0.001721 | 0.000138 | 1.02 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.75 | 0.272293 | 0.300000 | 0.825715 | 0.726115 | 0.500000 | 0.001399 | 0.000233 | 1.14 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 3.18 | 0.235826 | 0.300000 | 0.953398 | 0.628870 | 0.500000 | 0.001616 | 0.000442 | 2.16 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.00 | 0.157364 | 0.300000 | 0.301197 | 0.419637 | 0.500000 | 0.002421 | 0.000205 | 1.00 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.04 | 0.095866 | 0.300000 | 0.313006 | 0.300000 | 0.500000 | 0.003974 | 0.000136 | 0.667621 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.34 | 0.117795 | 0.300000 | 0.402374 | 0.314119 | 0.500000 | 0.003234 | 0.000208 | 1.02 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.20 | 0.083626 | 0.300000 | 0.358797 | 0.300000 | 0.500000 | 0.004556 | 0.000134 | 0.657157 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.763495 | 0.206932 | 0.300000 | 0.229048 | 0.551819 | 0.500000 | 0.001841 | 0.000156 | 0.763495 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.924910 | 0.108142 | 0.300000 | 0.277473 | 0.300000 | 0.500000 | 0.003523 | 0.000106 | 0.517843 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.10 | 0.144081 | 0.300000 | 0.328964 | 0.384216 | 0.500000 | 0.002644 | 0.000159 | 0.780753 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.995133 | 0.100504 | 0.300000 | 0.298540 | 0.300000 | 0.500000 | 0.003791 | 0.000103 | 0.506773 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.799672 | 0.197570 | 0.300000 | 0.239902 | 0.526855 | 0.500000 | 0.001928 | 0.000163 | 0.799672 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 1.04 | 0.300000 | 0.500000 | 0.003955 | 0.000110 | 0.537906 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.19 | 0.132616 | 0.300000 | 0.357404 | 0.353643 | 0.500000 | 0.002873 | 0.000166 | 0.814439 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.10 | 0.090768 | 0.300000 | 0.330564 | 0.300000 | 0.500000 | 0.004198 | 0.000108 | 0.527631 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15767.39 | 0.000138 | 337.46 |
CORE_MID VAV BOX REHEAT COIL | 26686.31 | 0.000233 | 624.86 |
CORE_TOP VAV BOX REHEAT COIL | 50478.95 | 0.000442 | 1180.19 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23380.13 | 0.000205 | 546.15 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15545.09 | 0.000136 | 363.11 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23728.90 | 0.000208 | 554.29 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15302.08 | 0.000134 | 357.44 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17792.55 | 0.000156 | 415.71 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12065.21 | 0.000106 | 281.88 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18193.40 | 0.000159 | 425.06 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11808.11 | 0.000103 | 275.87 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 18633.75 | 0.000163 | 435.35 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 12531.74 | 0.000110 | 292.77 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 18976.66 | 0.000166 | 443.35 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 12293.11 | 0.000108 | 287.20 |
PACU_VAV_BOT HEATING COIL | 2490.77 | 0.000022 | 45.44 |
PACU_VAV_MID HEATING COIL | 5642.82 | 0.000049 | 101.64 |
PACU_VAV_TOP HEATING COIL | 3055.61 | 0.000027 | 55.70 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.58 | 2.15 | 7.17 | 2.99 | 6.24 | 6.24 | 0.300000 | 0.479630 | 6.24 |
PACU_VAV_MID | 3.44 | 2.07 | 6.88 | 3.82 | 5.83 | 5.83 | 0.300000 | 0.654755 | 5.83 |
PACU_VAV_TOP | 3.88 | 2.33 | 7.76 | 5.51 | 7.09 | 7.09 | 0.300000 | 0.777117 | 7.09 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.24 |
PACU_VAV_MID_OA_CONTROLLER | 5.83 |
PACU_VAV_TOP_OA_CONTROLLER | 7.09 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.24 | 106954.38 | 0.800177 | 2.08 | 35647.89 | 0.800177 |
PACU_VAV_MID COOLING COIL | 5.83 | 100462.08 | 0.800061 | 1.94 | 33484.01 | 0.800061 |
PACU_VAV_TOP COOLING COIL | 7.09 | 120000.78 | 0.800504 | 2.36 | 39996.26 | 0.800504 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.24 |
PACU_VAV_MID FAN | 5.83 |
PACU_VAV_TOP FAN | 7.09 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000022 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000049 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000027 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002663 | 0.319534 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.002663 | 801.91 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 304372.59 | 304372.59 | 0.002663 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
43 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
44 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
45 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
46 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
47 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
48 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
49 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_1.22_SHGC_EAST_0.34 | 35 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.341 | ||
2 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 36 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.341 | ||
3 | WINDOW_U_1.22_SHGC_WEST_0.34 | 37 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.341 | ||
4 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 38 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.341 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.17779 | 0.27613 | 0.27613 | 0.37400 | 0.14055 | 0.18699 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.17779 | 0.27613 | 0.27613 | 0.37400 | 0.14055 | 0.18699 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.17779 | 0.27613 | 0.27613 | 0.37400 | 0.14055 | 0.18699 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.17779 | 0.27613 | 0.27613 | 0.37400 | 0.14055 | 0.18699 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39785.78072 | 45753.64783 | 2.94423 | 3.38587 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 4671.09273 | 5838.86591 | 0.33992 | 0.42490 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32368.41461 | 37223.67680 | 2.39338 | 2.75238 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 12463.95616 | 15579.94520 | 0.90901 | 1.13626 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 37031.70001 | 42586.45502 | 2.76347 | 3.17799 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 23486.40247 | 29358.00309 | 1.72866 | 2.16083 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 11050.50527 | 12708.08106 | 0.82462 | 0.94831 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10854.96172 | 13568.70215 | 0.80319 | 1.00399 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 12158.04893 | 13981.75627 | 0.90726 | 1.04335 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7216.64783 | 9020.80979 | 0.53410 | 0.66762 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15629.28688 | 17973.67991 | 1.16630 | 1.34125 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 11016.54625 | 13770.68282 | 0.81521 | 1.01901 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 13936.69034 | 16027.19389 | 1.03999 | 1.19599 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7104.05791 | 8880.07239 | 0.52573 | 0.65716 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8414.23105 | 9676.36571 | 0.62790 | 0.72208 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 8264.89148 | 10331.11435 | 0.61080 | 0.76349 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 10777.78492 | 12394.45265 | 0.80427 | 0.92491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5603.53401 | 7004.41752 | 0.41427 | 0.51784 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12777.78861 | 14694.45690 | 0.95352 | 1.09655 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 8450.60263 | 10563.25328 | 0.62460 | 0.78075 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 11596.07945 | 13335.49137 | 0.86533 | 0.99513 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 30.29133 | 8.23188E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5484.42225 | 6855.52781 | 0.40542 | 0.50677 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9185.40124 | 10563.21143 | 0.68544 | 0.78826 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8655.34098 | 10819.17622 | 0.63974 | 0.79967 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 12098.70308 | 13913.50854 | 0.90284 | 1.03826 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 26.12317 | 8.22530E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5820.11721 | 7275.14651 | 0.43033 | 0.53791 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 13882.50671 | 15964.88271 | 1.03595 | 1.19135 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.85500 | 8.23278E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8814.18852 | 11017.73566 | 0.65155 | 0.81444 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 12840.01640 | 14766.01886 | 0.95816 | 1.10188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5709.57364 | 7136.96705 | 0.42210 | 0.52763 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 90639.92 | 6.24182 | 6.24182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 10313.58 | 2.99376 | 2.99376 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 85180.37 | 5.82800 | 5.82800 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 9756.52 | 3.81591 | 3.81591 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 101811.01 | 7.08852 | 7.08852 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 9840.88 | 5.50860 | 5.50860 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.38587 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22135 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01576 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59026 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72127E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37940E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01576 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15767.39224 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37940E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 337.46056 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.75238 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27229 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.82572 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72611 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39923E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.33464E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13626 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26686.31417 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.33464E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 624.85738 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.17799 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23583 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.95340 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62887 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61560E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.41612E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.16083 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 50478.95385 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.41612E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1180.19475 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00399 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15736 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30120 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41964 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42114E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.04540E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.00399 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23380.13135 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.04540E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 546.14570 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04335 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.58656E-002 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31301 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.97431E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35995E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66762 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15545.09097 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35995E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 363.11124 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34125 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11779 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40237 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31412 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23444E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07591E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01901 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23728.90012 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07591E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 554.28653 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19599 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.36255E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35880 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.55602E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33869E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.65716 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15302.07885 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33869E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 357.43890 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76349 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20693 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22905 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55182 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.84118E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55657E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76349 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17792.55092 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55657E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 415.70678 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92491 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10814 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27747 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.52314E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05552E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51784 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12065.21435 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05552E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 281.87560 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.09655 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14408 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32896 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38422 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64435E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.59164E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78075 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18193.39579 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59164E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 425.06343 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99513 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10050 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29854 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.79088E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03303E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50677 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11808.11311 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03303E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 275.87432 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79967 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19757 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23990 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52685 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92843E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63016E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.79967 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18633.75176 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63016E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 435.34842 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03826 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95492E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09633E-004 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53791 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12531.73649 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09633E-004 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 292.76873 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19135 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13262 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35740 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35364 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87296E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66016E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81444 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18976.66287 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66016E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 443.35244 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10188 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.07679E-002 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33056 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.19752E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07546E-004 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52763 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12293.11166 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07546E-004 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.19887 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.58298 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.14979 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.16595 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.99376 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.24182 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.24182 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.47963 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.44177 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.06506 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.88354 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 3.81591 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.82800 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.82800 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.65476 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.88129 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.32877 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.76257 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 5.50860 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.08852 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 7.08852 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.77712 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.24182 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.82800 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 7.08852 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.24182 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.24182 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 106954.37524 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80018 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.08040 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35647.89327 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80018 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 2490.76561 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17903E-005 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 45.43544 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.24182 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.17903E-005 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.82800 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.82800 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 100462.07892 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80006 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.94247 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33484.01090 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80006 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 5642.81560 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.93658E-005 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 101.64446 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.82800 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.93658E-005 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.08852 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 7.08852 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 120000.77777 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80050 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.36260 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39996.25923 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80050 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 3055.60857 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.67318E-005 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 55.69855 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 7.08852 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.67318E-005 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.66278E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.31953 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.66278E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 801.91366 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 304372.58826 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 304372.59000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.66278E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 14965.04 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 25316.56 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 47888.29 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22180.31 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14747.35 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22511.18 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14516.81 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16879.46 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11446.05 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17259.73 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11202.14 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17677.49 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11888.63 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 18002.81 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11662.25 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 2328.17 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 5156.71 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 2852.46 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 105283.53 | 359242.33 | 11.17 | 2.89 | 3.19 | 3.36 | 3.55 | 9.85 | 10.90 | 11.47 | 12.10 | 7.0851 | 5.6110 | 3.7633 | 1.5511 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 98919.68 | 337527.95 | 11.18 | 2.89 | 3.20 | 3.37 | 3.55 | 9.86 | 10.92 | 11.49 | 12.12 | 6.6154 | 5.2408 | 3.5148 | 1.4457 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 118060.16 | 402837.98 | 11.14 | 2.88 | 3.19 | 3.35 | 3.54 | 9.83 | 10.87 | 11.44 | 12.06 | 8.0462 | 6.3694 | 4.2707 | 1.7664 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.34 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.34 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.34 | N/A | 6.926 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.34 | N/A | 6.926 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.34 | N/A | 6.926 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.34 | N/A | 6.926 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.34 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.34 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.34 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.34 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.0407711584E-003 | 5.5480318289E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.1952652376E-002 | 7.4139110404E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.1987369902E-002 | 8.1280989544E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.7466380491E-003 | 6.9005179363E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.2945475612E-003 | 6.4619581868E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.5242032049E-002 | 1.7844275376E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9129227815E-002 | 4.8384275895E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.2016856095E-002 | 0.1486697347 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1174986081 | 0.1312839519 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.9581947418E-002 | 6.9892601466E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.8547598840E-002 | 5.2144892449E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.0385566354E-002 | 0.1374994772 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.9637594903E-002 | 0.1181635404 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.5361139837E-002 | 7.0457330501E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.2422291506E-002 | 5.2453077127E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.2430443111E-002 | 0.1544487260 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1149102563 | 0.1339935885 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.2053081123E-002 | 7.1810911464E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5042.38 | 47.53 | 0.00 | 2693.81 | 1263.95 | 9047.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.34 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.341 | 0.376 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.34 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.341 | 0.376 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.341 | 0.376 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.34 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.341 | 0.376 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_1.22_SHGC_NORTH_0.34 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_1.22_SHGC_EAST_0.34 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_1.22_SHGC_EAST_0.34 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_1.22_SHGC_WEST_0.34 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_1.22_SHGC_WEST_0.34 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 6.926 | 0.341 | 0.376 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.34 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.341 | 0.376 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.34 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.341 | 0.376 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.34 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.341 | 0.376 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.34 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.341 | 0.376 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 6.926 | 0.341 | 0.376 | |||||||||||||||||
North Total or Average | 183.92 | 6.926 | 0.341 | 0.376 | |||||||||||||||||
Non-North Total or Average | 429.15 | 6.926 | 0.341 | 0.376 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.75 | 83.75 | 236.03 | |
Exterior Lighting Total | 15013.15 | 236.03 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 304372.59 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 106954.38 | 85582.43 | 21371.94 | 0.80 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 100462.08 | 80375.74 | 20086.34 | 0.80 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 120000.78 | 96061.05 | 23939.73 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 105283.5 | 2.89 | 9.85 | N/A | N/A | 11.17 | |
PACU_VAV_MID COOLING COIL | 98919.7 | 2.89 | 9.86 | N/A | N/A | 11.18 | |
PACU_VAV_TOP COOLING COIL | 118060.2 | 2.88 | 9.83 | N/A | N/A | 11.14 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15767.39 | 14965.04 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 26686.31 | 25316.56 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 50478.95 | 47888.29 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 23380.13 | 22180.31 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 15545.09 | 14747.35 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23728.90 | 22511.18 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15302.08 | 14516.81 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17792.55 | 16879.46 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12065.21 | 11446.05 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18193.40 | 17259.73 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11808.11 | 11202.14 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18633.75 | 17677.49 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12531.74 | 11888.63 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18976.66 | 18002.81 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12293.11 | 11662.25 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 2490.77 | 2328.17 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 5642.82 | 5156.71 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 3055.61 | 2852.46 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1337.13 | 6.24 | 13806.66 | 2211.96 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.83 | 12891.30 | 2211.96 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.09 | 15579.01 | 2197.78 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002663 | 801.91 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105283.53 | 2.89 | 9.85 | 11.17 | 7.0851 | 3.19 | 10.90 | 5.6110 | 3.36 | 11.47 | 3.7633 | 3.55 | 12.10 | 1.5511 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 98919.68 | 2.89 | 9.86 | 11.18 | 6.6154 | 3.20 | 10.92 | 5.2408 | 3.37 | 11.49 | 3.5148 | 3.55 | 12.12 | 1.4457 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 118060.16 | 2.88 | 9.83 | 11.14 | 8.0462 | 3.19 | 10.87 | 6.3694 | 3.35 | 11.44 | 4.2707 | 3.54 | 12.06 | 1.7664 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39785.78 | 45753.65 | 46.52 | 2.944 | 3.386 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_MID | 32368.41 | 37223.68 | 37.85 | 2.393 | 2.752 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_TOP | 37031.70 | 42586.46 | 43.30 | 2.763 | 3.178 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00882 | 31.30 | 0.00823 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11050.51 | 12708.08 | 61.29 | 0.825 | 0.948 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00871 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 12158.05 | 13981.76 | 106.52 | 0.907 | 1.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00862 | 26.66 | 0.00823 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15629.29 | 17973.68 | 86.69 | 1.166 | 1.341 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00865 | 31.00 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 13936.69 | 16027.19 | 122.11 | 1.040 | 1.196 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00861 | 30.53 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8414.23 | 9676.37 | 46.67 | 0.628 | 0.722 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00878 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 10777.78 | 12394.45 | 94.43 | 0.804 | 0.925 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00864 | 26.41 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12777.79 | 14694.46 | 70.87 | 0.954 | 1.097 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00869 | 30.93 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 11596.08 | 13335.49 | 101.60 | 0.865 | 0.995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 24.00 | 24.00 | 0.00863 | 30.29 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9185.40 | 10563.21 | 50.95 | 0.685 | 0.788 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00875 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 12098.70 | 13913.51 | 106.00 | 0.903 | 1.038 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00862 | 26.12 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13882.51 | 15964.88 | 77.00 | 1.036 | 1.191 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00867 | 30.86 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 12840.02 | 14766.02 | 112.50 | 0.958 | 1.102 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00862 | 30.41 | 0.00823 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 4671.09 | 5838.87 | 5.94 | 0.340 | 0.425 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_MID | 12463.96 | 15579.95 | 15.84 | 0.909 | 1.136 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_TOP | 23486.40 | 29358.00 | 29.85 | 1.729 | 2.161 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10854.96 | 13568.70 | 65.44 | 0.803 | 1.004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7216.65 | 9020.81 | 68.72 | 0.534 | 0.668 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11016.55 | 13770.68 | 66.42 | 0.815 | 1.019 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7104.06 | 8880.07 | 67.66 | 0.526 | 0.657 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8264.89 | 10331.11 | 49.83 | 0.611 | 0.763 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5603.53 | 7004.42 | 53.36 | 0.414 | 0.518 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8450.60 | 10563.25 | 50.95 | 0.625 | 0.781 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5484.42 | 6855.53 | 52.23 | 0.405 | 0.507 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8655.34 | 10819.18 | 52.18 | 0.640 | 0.800 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5820.12 | 7275.15 | 55.42 | 0.430 | 0.538 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8814.19 | 11017.74 | 53.14 | 0.652 | 0.814 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5709.57 | 7136.97 | 54.38 | 0.422 | 0.528 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 3.80 | 0.00506 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.24 | 6.24 | 2.99 | 2.99 | 6.2418 | 2.9938 | 6.2418 | 0.4796 | 0.3000 |
PACU_VAV_MID | 5.83 | 5.83 | 3.82 | 3.82 | 5.8280 | 3.8159 | 5.8280 | 0.6548 | 0.3000 |
PACU_VAV_TOP | 7.09 | 7.09 | 5.51 | 5.51 | 7.0885 | 5.5086 | 7.0885 | 0.7771 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15767.392 | 15767.392 | 1.015760 | 0.00013794 | 337.461 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15767.39 | 15767.39 | 1.015760 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 5838.87 | 0.00 | 15843.17 | 15843.17 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 26686.314 | 26686.314 | 1.136263 | 0.00023346 | 624.857 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26686.31 | 26686.31 | 1.136263 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 15579.95 | 0.00 | 26808.54 | 26808.54 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 50478.954 | 50478.954 | 2.160828 | 0.00044161 | 1180.195 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 50478.95 | 50478.95 | 2.160828 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 29358.00 | 0.00 | 50710.30 | 50710.30 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23380.131 | 23380.131 | 1.003990 | 0.00020454 | 546.146 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23380.13 | 23256.58 | 1.003990 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00791192 | 50.2052 | 13568.70 | 0.00 | 23487.32 | 23487.32 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15545.091 | 15545.091 | 0.667621 | 0.00013600 | 363.111 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15545.09 | 15545.09 | 0.667621 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00791195 | 50.2054 | 9020.81 | 0.00 | 15616.36 | 15616.36 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 23728.900 | 23728.900 | 1.019007 | 0.00020759 | 554.287 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23728.90 | 23728.90 | 1.019007 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00791328 | 50.2137 | 13770.68 | 0.00 | 23837.69 | 23837.69 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15302.079 | 15302.079 | 0.657157 | 0.00013387 | 357.439 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15302.08 | 15302.08 | 0.657157 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00791050 | 50.1963 | 8880.07 | 0.00 | 15372.23 | 15372.23 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17792.551 | 17792.551 | 0.763495 | 0.00015566 | 415.707 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17792.55 | 17685.72 | 0.763495 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00792535 | 50.2892 | 10331.11 | 0.00 | 17874.12 | 17874.12 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12065.214 | 12065.214 | 0.517843 | 0.00010555 | 281.876 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12065.21 | 12065.21 | 0.517843 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00793012 | 50.3191 | 7004.42 | 0.00 | 12120.53 | 12120.53 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18193.396 | 18193.396 | 0.780753 | 0.00015916 | 425.063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18193.40 | 18193.40 | 0.780753 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00792808 | 50.3062 | 10563.25 | 0.00 | 18276.80 | 18276.80 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11808.113 | 11808.113 | 0.506773 | 0.00010330 | 275.874 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11808.11 | 11808.11 | 0.506773 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00792756 | 50.3031 | 6855.53 | 0.00 | 11862.25 | 11862.25 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 18633.752 | 18633.752 | 0.799672 | 0.00016302 | 435.348 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18633.75 | 18523.74 | 0.799672 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00790084 | 50.1358 | 10819.18 | 0.00 | 18719.17 | 18719.17 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 12531.736 | 12531.736 | 0.537906 | 0.00010963 | 292.769 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12531.74 | 12531.74 | 0.537906 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00790507 | 50.1623 | 7275.15 | 0.00 | 12589.19 | 12589.19 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 18976.663 | 18976.663 | 0.814439 | 0.00016602 | 443.352 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18976.66 | 18976.66 | 0.814439 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00790384 | 50.1546 | 11017.74 | 0.00 | 19063.66 | 19063.66 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 12293.112 | 12293.112 | 0.527631 | 0.00010755 | 287.199 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12293.11 | 12293.11 | 0.527631 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00790228 | 50.1448 | 7136.97 | 0.00 | 12349.47 | 12349.47 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 106954.375 | 85582.431 | 6.241823 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 106486.32 | 102968.83 | 6.241823 | 25.12 | 16.75 | 0.00868889 | 11.06 | 11.06 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 15.3176 | 24.00 | 0.00877126 | 46.3218 | 72733.65 | 0.00 | 110284.32 | 85940.93 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 2490.766 | 2490.766 | 1.872547 | 0.00002179 | 45.435 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 2490.77 | 2490.77 | 1.872547 | 11.77 | 9.19 | 0.00630048 | 12.89 | 11.47 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 51.0588 | 19.85 | 0.00769844 | 52.4714 | 7567.05 | 0.00 | 2818.66 | 2818.66 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 100462.079 | 80375.742 | 5.827997 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 100081.54 | 96657.32 | 5.827997 | 25.20 | 16.78 | 0.00869700 | 11.06 | 11.06 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 16.4053 | 24.00 | 0.00878797 | 46.4087 | 67911.69 | 0.00 | 103589.89 | 80712.04 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 5642.816 | 5642.816 | 1.748399 | 0.00004937 | 101.644 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5642.82 | 5642.82 | 1.748399 | 10.17 | 8.33 | 0.00618374 | 12.89 | 11.47 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 54.6843 | 19.44 | 0.00738755 | 51.6830 | 11396.15 | 0.00 | 6243.14 | 6243.14 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 120000.778 | 96061.049 | 7.088516 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 119345.98 | 115789.07 | 7.088516 | 24.98 | 16.68 | 0.00866823 | 11.07 | 11.07 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 13.4880 | 24.00 | 0.00873601 | 46.1381 | 82600.28 | 0.00 | 123736.91 | 96459.85 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 3055.609 | 3055.609 | 2.126555 | 0.00002673 | 55.699 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3055.61 | 3055.61 | 2.126555 | 11.68 | 9.39 | 0.00651868 | 12.89 | 11.47 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 44.9600 | 16.31 | 0.00785890 | 66.9029 | 7753.36 | 0.00 | 3453.43 | 3453.43 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15767.392 | 15767.392 | 1.015760 | 0.00013794 | 337.461 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 5.0781 | 5.180293 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15767.39 | 15767.39 | 1.0000 | 1.20040400 | 1.015760 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.13792595 | 60.00 | 32.22 | 27.78 | 0.000 | 15767.39 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.72 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 5838.87 | 0.00 | 15843.17 | 15843.17 | 1.20040400 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.74 | 16.58 | 0.00800000 | 46258.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 26686.314 | 26686.314 | 1.136263 | 0.00023346 | 624.857 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 8.5947 | 8.767647 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26686.31 | 26686.31 | 1.0000 | 1.34281128 | 1.136263 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.23343970 | 60.00 | 32.22 | 27.78 | 0.000 | 26686.31 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 15579.95 | 0.00 | 26808.54 | 26808.54 | 1.34281128 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.38 | 18.82 | 0.00800000 | 53024.3 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 50478.954 | 50478.954 | 2.160828 | 0.00044161 | 1180.195 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 16.2574 | 16.584593 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 50478.95 | 50478.95 | 1.0000 | 2.55362045 | 2.160828 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.44156686 | 60.00 | 32.22 | 27.78 | 0.000 | 50478.95 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 29358.00 | 0.00 | 50710.30 | 50710.30 | 2.55362045 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.27 | 18.79 | 0.00800000 | 52918.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23380.131 | 23380.131 | 1.003990 | 0.00020454 | 546.146 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 7.5299 | 7.681418 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23380.13 | 23256.58 | 1.0000 | 1.18649342 | 1.003990 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.20451872 | 60.00 | 32.22 | 27.78 | 0.000 | 23380.13 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00791192 | 21.00 | 0.00791192 | 50.2052 | 13568.70 | 0.00 | 23487.32 | 23487.32 | 1.18649342 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52855.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15545.091 | 15545.091 | 0.667621 | 0.00013600 | 363.111 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 5.0065 | 5.107257 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15545.09 | 15545.09 | 1.0000 | 0.78898048 | 0.667621 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.13598136 | 60.00 | 32.22 | 27.78 | 0.000 | 15545.09 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00791195 | 21.00 | 0.00791195 | 50.2054 | 9020.81 | 0.00 | 15616.36 | 15616.36 | 0.78898048 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52852.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23728.900 | 23728.900 | 1.019007 | 0.00020759 | 554.287 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 7.6422 | 7.796004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23728.90 | 23728.90 | 1.0000 | 1.20424127 | 1.019007 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.20756959 | 60.00 | 32.22 | 27.78 | 0.000 | 23728.90 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00791328 | 21.00 | 0.00791328 | 50.2137 | 13770.68 | 0.00 | 23837.69 | 23837.69 | 1.20424127 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52854.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15302.079 | 15302.079 | 0.657157 | 0.00013387 | 357.439 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 4.9282 | 5.027417 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15302.08 | 15302.08 | 1.0000 | 0.77661460 | 0.657157 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.13385561 | 60.00 | 32.22 | 27.78 | 0.000 | 15302.08 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00791050 | 21.00 | 0.00791050 | 50.1963 | 8880.07 | 0.00 | 15372.23 | 15372.23 | 0.77661460 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52853.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17792.551 | 17792.551 | 0.763495 | 0.00015566 | 415.707 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 5.7303 | 5.845648 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17792.55 | 17685.72 | 1.0000 | 0.90228177 | 0.763495 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.15564112 | 60.00 | 32.22 | 27.78 | 0.000 | 17792.55 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00792535 | 21.00 | 0.00792535 | 50.2892 | 10331.11 | 0.00 | 17874.12 | 17874.12 | 0.90228177 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52869.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12065.214 | 12065.214 | 0.517843 | 0.00010555 | 281.876 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 3.8858 | 3.963962 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12065.21 | 12065.21 | 1.0000 | 0.61197575 | 0.517843 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.10554099 | 60.00 | 32.22 | 27.78 | 0.000 | 12065.21 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00793012 | 21.00 | 0.00793012 | 50.3191 | 7004.42 | 0.00 | 12120.53 | 12120.53 | 0.61197575 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52865.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18193.396 | 18193.396 | 0.780753 | 0.00015916 | 425.063 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 5.8594 | 5.977344 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18193.40 | 18193.40 | 1.0000 | 0.92267731 | 0.780753 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.15914753 | 60.00 | 32.22 | 27.78 | 0.000 | 18193.40 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00792808 | 21.00 | 0.00792808 | 50.3062 | 10563.25 | 0.00 | 18276.80 | 18276.80 | 0.92267731 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52868.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11808.113 | 11808.113 | 0.506773 | 0.00010330 | 275.874 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 3.8030 | 3.879493 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11808.11 | 11808.11 | 1.0000 | 0.59889365 | 0.506773 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.10329199 | 60.00 | 32.22 | 27.78 | 0.000 | 11808.11 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00792756 | 21.00 | 0.00792756 | 50.3031 | 6855.53 | 0.00 | 11862.25 | 11862.25 | 0.59889365 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52866.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18633.752 | 18633.752 | 0.799672 | 0.00016302 | 435.348 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 6.0012 | 6.122020 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18633.75 | 18523.74 | 1.0000 | 0.94503584 | 0.799672 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.16299956 | 60.00 | 32.22 | 27.78 | 0.000 | 18633.75 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00790084 | 21.00 | 0.00790084 | 50.1358 | 10819.18 | 0.00 | 18719.17 | 18719.17 | 0.94503584 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52867.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12531.736 | 12531.736 | 0.537906 | 0.00010963 | 292.769 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 4.0360 | 4.117236 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12531.74 | 12531.74 | 1.0000 | 0.63568632 | 0.537906 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.10962191 | 60.00 | 32.22 | 27.78 | 0.000 | 12531.74 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00790507 | 21.00 | 0.00790507 | 50.1623 | 7275.15 | 0.00 | 12589.19 | 12589.19 | 0.63568632 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52863.9 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18976.663 | 18976.663 | 0.814439 | 0.00016602 | 443.352 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 6.1117 | 6.234682 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18976.66 | 18976.66 | 1.0000 | 0.96248613 | 0.814439 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.16599919 | 60.00 | 32.22 | 27.78 | 0.000 | 18976.66 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00790384 | 21.00 | 0.00790384 | 50.1546 | 11017.74 | 0.00 | 19063.66 | 19063.66 | 0.96248613 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52866.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12293.112 | 12293.112 | 0.527631 | 0.00010755 | 287.199 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 3.9592 | 4.038837 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12293.11 | 12293.11 | 1.0000 | 0.62354319 | 0.527631 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.10753453 | 60.00 | 32.22 | 27.78 | 0.000 | 12293.11 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00790228 | 21.00 | 0.00790228 | 50.1448 | 7136.97 | 0.00 | 12349.47 | 12349.47 | 0.62354319 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52865.1 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 106954.375 | 85582.431 | 6.241823 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9922 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.241823 | 7.37645305 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 106486.32 | 102968.83 | 0.9956 | 7.37645305 | 6.241823 | 25.12 | 16.75 | 0.00868889 | 47374.9 | 11.06 | 11.06 | 0.00850000 | 32541.9 | -999.0 | -999.00 | -999.00 | -999.00 | 13806.664 | 92679.66 | 31.30 | 0.00823349 | 18.45 | 0.95610000 | 15.3176 | 24.00 | 0.00877126 | 24.00 | 0.00877126 | 46.3218 | 72733.65 | 0.00 | 110284.32 | 85940.93 | 7.08513892 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.81 | 14.19 | 0.00983755 | 39756.8 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 2490.766 | 2490.766 | 1.872547 | 0.00002179 | 45.435 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.241823 | 7.37645305 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 0.8022 | 0.818328 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 2490.77 | 2490.77 | 1.0000 | 2.21293592 | 1.872547 | 11.77 | 9.19 | 0.00630048 | 27720.7 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 0.02178808 | 60.00 | 32.22 | 27.78 | 0.000 | 2490.77 | 3.80 | 0.00505843 | 3.80 | 0.95610000 | 51.0588 | 20.08 | 0.00759627 | 19.85 | 0.00769844 | 52.4714 | 7567.05 | 0.00 | 2818.66 | 2818.66 | 2.21293592 | 2.80 | 2.80 | 0.00630048 | 18603.5 | 4.05 | 4.05 | 0.00630048 | 19877.2 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 100462.079 | 80375.742 | 5.827997 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0073 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.827997 | 6.88740306 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 100081.54 | 96657.32 | 0.9962 | 6.88740306 | 5.827997 | 25.20 | 16.78 | 0.00869700 | 47476.7 | 11.06 | 11.06 | 0.00850000 | 32541.9 | -999.0 | -999.00 | -999.00 | -999.00 | 12891.299 | 87190.24 | 31.30 | 0.00823349 | 18.45 | 0.95610000 | 16.4053 | 24.00 | 0.00878797 | 24.00 | 0.00878797 | 46.4087 | 67911.69 | 0.00 | 103589.89 | 80712.04 | 6.61540270 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.74 | 14.15 | 0.00982875 | 39663.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 5642.816 | 5642.816 | 1.748399 | 0.00004937 | 101.644 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.827997 | 6.88740306 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 1.8173 | 1.853917 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5642.82 | 5642.82 | 1.0000 | 2.06622092 | 1.748399 | 10.17 | 8.33 | 0.00618374 | 25802.4 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 0.04936078 | 60.00 | 32.22 | 27.78 | 0.000 | 5642.82 | 3.80 | 0.00505843 | 3.80 | 0.95610000 | 54.6843 | 17.86 | 0.00754171 | 19.44 | 0.00738755 | 51.6830 | 11396.15 | 0.00 | 6243.14 | 6243.14 | 2.06622092 | 2.80 | 2.80 | 0.00618374 | 18310.9 | 5.77 | 5.77 | 0.00618374 | 21332.4 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 120000.778 | 96061.049 | 7.088516 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9538 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 7.088516 | 8.37705650 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 119345.98 | 115789.07 | 0.9945 | 8.37705650 | 7.088516 | 24.98 | 16.68 | 0.00866823 | 47185.9 | 11.07 | 11.07 | 0.00850000 | 32553.8 | -999.0 | -999.00 | -999.00 | -999.00 | 15579.005 | 103766.97 | 31.30 | 0.00823349 | 18.45 | 0.95610000 | 13.4880 | 24.00 | 0.00873601 | 24.00 | 0.00873601 | 46.1381 | 82600.28 | 0.00 | 123736.91 | 96459.85 | 8.04622610 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.95 | 14.26 | 0.00985550 | 39944.1 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 3055.609 | 3055.609 | 2.126555 | 0.00002673 | 55.699 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 7.088516 | 8.37705650 | 4197.9300 | 999.8980 | 2.66251255 | 54.44 | 82.22 | 27.78 | 310498.21 | 0.9841 | 1.003904 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3055.61 | 3055.61 | 1.0000 | 2.51311695 | 2.126555 | 11.68 | 9.39 | 0.00651868 | 28179.8 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 0.02672907 | 60.00 | 32.22 | 27.78 | 0.000 | 3055.61 | 3.80 | 0.00505843 | 3.80 | 0.95610000 | 44.9600 | 18.11 | 0.00771150 | 16.31 | 0.00785890 | 66.9029 | 7753.36 | 0.00 | 3453.43 | 3453.43 | 2.51311695 | 2.80 | 2.80 | 0.00651868 | 19150.3 | 4.15 | 4.15 | 0.00651868 | 20524.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.24 | - | |||
PACU_VAV_MID_OA_CONTROLLER | FixedDryBulb | 0.00 | 5.83 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | FixedDryBulb | 0.00 | 7.09 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 3781.00 | 454.00 | 12.17 |
CORE_MID | 2025.00 | 2344.50 | 1.17 |
CORE_TOP | 1697.33 | 3303.67 | 53.00 |
PERIMETER_TOP_ZN_3 | 1691.67 | 4274.17 | 494.83 |
PERIMETER_TOP_ZN_2 | 1950.67 | 3892.50 | 355.67 |
PERIMETER_TOP_ZN_1 | 2429.50 | 3354.83 | 334.33 |
PERIMETER_TOP_ZN_4 | 1867.00 | 4221.17 | 542.17 |
PERIMETER_BOT_ZN_3 | 1214.17 | 4263.83 | 180.67 |
PERIMETER_BOT_ZN_2 | 1668.00 | 3826.33 | 113.67 |
PERIMETER_BOT_ZN_1 | 2114.33 | 3254.17 | 116.67 |
PERIMETER_BOT_ZN_4 | 1595.33 | 3923.33 | 172.83 |
PERIMETER_MID_ZN_3 | 1538.33 | 3897.83 | 195.83 |
PERIMETER_MID_ZN_2 | 1369.17 | 3366.33 | 173.67 |
PERIMETER_MID_ZN_1 | 2405.50 | 3055.50 | 178.50 |
PERIMETER_MID_ZN_4 | 1665.00 | 4037.50 | 270.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4923.17 | 5050.17 | 748.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 1.17 | 0.00 | 1.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.83 | 10.67 | 0.83 | 10.67 |
PERIMETER_TOP_ZN_1 | 0.67 | 19.67 | 0.67 | 19.67 |
PERIMETER_TOP_ZN_4 | 0.67 | 18.17 | 0.67 | 16.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 8.83 | 0.00 | 8.83 |
PERIMETER_BOT_ZN_1 | 31.17 | 30.67 | 31.17 | 30.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 12.00 | 0.00 | 10.83 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 12.67 | 0.00 | 12.67 |
PERIMETER_MID_ZN_1 | 0.00 | 25.67 | 0.00 | 25.67 |
PERIMETER_MID_ZN_4 | 0.00 | 16.67 | 0.00 | 15.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 32.33 | 111.83 | 32.33 | 108.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 1.564 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 1.025 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 1.097 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 1.509 | 0.057 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 2.579 | 0.061 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 2.460 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 2.992 | 0.060 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 1.159 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 2.306 | 0.032 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 2.019 | 0.828 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 2.511 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 1.278 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 2.488 | 0.052 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 2.350 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 2.838 | 0.050 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.60 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.81 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 24579852.26 | 0.00 | 24579852.26 | 0.00 | 24579852.26 | 13393058.27 | 4092.54 | 18.90 | 4648.55 | 22.22 |
CORE_MID | 16143560.15 | 0.00 | 16143560.15 | 0.00 | 16143560.15 | 13393058.27 | 4212.04 | 9.38 | 4538.58 | 23.84 |
CORE_TOP | 17301100.29 | 0.00 | 17301100.29 | 0.00 | 17301100.29 | 13393058.27 | 4260.35 | 8.58 | 4491.07 | 24.18 |
PERIMETER_TOP_ZN_3 | 5032574.66 | 0.00 | 5032574.66 | 331330.52 | 5363905.18 | 2823374.22 | 3956.21 | 16.61 | 4787.18 | 24.18 |
PERIMETER_TOP_ZN_2 | 5443565.52 | 0.00 | 5443565.52 | 220885.69 | 5664451.20 | 1787429.43 | 3858.69 | 0.67 | 4900.64 | 24.18 |
PERIMETER_TOP_ZN_1 | 8186839.61 | 0.00 | 8186839.61 | 331330.52 | 8518170.13 | 2823374.22 | 3862.19 | 0.69 | 4897.12 | 24.18 |
PERIMETER_TOP_ZN_4 | 6318761.55 | 0.00 | 6318761.55 | 220885.69 | 6539647.24 | 1787312.18 | 3857.79 | 0.08 | 4902.13 | 24.18 |
PERIMETER_BOT_ZN_3 | 3861352.25 | 0.00 | 3861352.25 | 176167.23 | 4037519.49 | 2823374.22 | 4161.49 | 0.64 | 4597.87 | 22.22 |
PERIMETER_BOT_ZN_2 | 4863548.67 | 0.00 | 4863548.67 | 117444.12 | 4980992.79 | 1787429.43 | 3870.16 | 2.58 | 4887.26 | 22.22 |
PERIMETER_BOT_ZN_1 | 6715579.81 | 0.00 | 6715579.81 | 2823248.61 | 9538828.42 | 2823374.22 | 3881.23 | 2.50 | 4876.27 | 22.22 |
PERIMETER_BOT_ZN_4 | 5297333.27 | 0.00 | 5297333.27 | 117444.12 | 5414777.39 | 1787312.18 | 3887.74 | 7.50 | 4864.76 | 22.22 |
PERIMETER_MID_ZN_3 | 4253720.13 | 0.00 | 4253720.13 | 275807.65 | 4529527.78 | 2823374.22 | 3944.64 | 8.05 | 4807.32 | 23.84 |
PERIMETER_MID_ZN_2 | 5013817.55 | 0.00 | 5013817.55 | 183870.66 | 5197688.21 | 1601953.02 | 3841.67 | 0.00 | 4918.33 | 932.84 |
PERIMETER_MID_ZN_1 | 7814092.47 | 0.00 | 7814092.47 | 275807.65 | 8089900.12 | 2823374.22 | 3843.09 | 0.42 | 4916.50 | 23.84 |
PERIMETER_MID_ZN_4 | 5988362.33 | 0.00 | 5988362.33 | 183870.66 | 6172232.99 | 1787312.18 | 3842.42 | 0.42 | 4917.16 | 23.84 |
Total Facility | 0.13E+09 | 0.00 | 0.13E+09 | 5258093.13 | 0.13E+09 | 67658168.57 | 4383.12 | 69.62 | 5013.71 | 943.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 1.1451 | 0.0000 | 1.1451 | 0.0000 | 1.1451 | 0.4247 | 1297.76 | 18.90 | 4626.34 |
CORE_MID | 0.7513 | 0.0000 | 0.7513 | 0.0000 | 0.7513 | 0.4247 | 1418.72 | 9.38 | 4514.90 |
CORE_TOP | 0.8048 | 0.0000 | 0.8048 | 0.0000 | 0.8048 | 0.4247 | 1467.53 | 8.58 | 4466.89 |
PERIMETER_TOP_ZN_3 | 0.2340 | 0.0000 | 0.2340 | 0.0089 | 0.2429 | 0.0895 | 1163.40 | 16.61 | 4763.00 |
PERIMETER_TOP_ZN_2 | 0.2532 | 0.0000 | 0.2532 | 0.0059 | 0.2591 | 0.0567 | 1065.88 | 0.67 | 4876.46 |
PERIMETER_TOP_ZN_1 | 0.3810 | 0.0000 | 0.3810 | 0.0089 | 0.3899 | 0.0895 | 1069.38 | 0.69 | 4872.94 |
PERIMETER_TOP_ZN_4 | 0.2939 | 0.0000 | 0.2939 | 0.0059 | 0.2998 | 0.0567 | 1064.97 | 0.08 | 4877.95 |
PERIMETER_BOT_ZN_3 | 0.1796 | 0.0000 | 0.1796 | 0.0047 | 0.1844 | 0.0895 | 1366.71 | 0.64 | 4575.65 |
PERIMETER_BOT_ZN_2 | 0.2263 | 0.0000 | 0.2263 | 0.0032 | 0.2295 | 0.0567 | 1075.37 | 2.58 | 4865.04 |
PERIMETER_BOT_ZN_1 | 0.3127 | 0.0000 | 0.3127 | 0.1285 | 0.4411 | 0.0895 | 1086.44 | 2.50 | 4854.06 |
PERIMETER_BOT_ZN_4 | 0.2465 | 0.0000 | 0.2465 | 0.0032 | 0.2496 | 0.0567 | 1092.96 | 7.50 | 4842.54 |
PERIMETER_MID_ZN_3 | 0.1979 | 0.0000 | 0.1979 | 0.0074 | 0.2053 | 0.0895 | 1151.48 | 8.05 | 4783.48 |
PERIMETER_MID_ZN_2 | 0.2442 | 0.0000 | 0.2442 | 0.0051 | 0.2493 | 0.0567 | 1048.51 | 0.00 | 3985.49 |
PERIMETER_MID_ZN_1 | 0.3638 | 0.0000 | 0.3638 | 0.0074 | 0.3712 | 0.0895 | 1049.93 | 0.42 | 4892.66 |
PERIMETER_MID_ZN_4 | 0.2785 | 0.0000 | 0.2785 | 0.0049 | 0.2835 | 0.0567 | 1049.26 | 0.42 | 4893.32 |
Total Facility | 5.9126 | 0.0000 | 5.9126 | 0.1942 | 6.1068 | 2.1513 | 1578.08 | 69.62 | 4978.87 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 63290689.42 | 0.00 | 63290689.42 | 22614548.33 | 3858.07 | 0.00 | 4901.93 | 22.22 |
PACU_VAV_MID | 54765679.37 | 0.00 | 54765679.37 | 22429071.92 | 3841.67 | 0.00 | 4918.33 | 23.84 |
PACU_VAV_TOP | 59052250.85 | 0.00 | 59052250.85 | 22614548.33 | 3861.06 | 0.51 | 4898.43 | 24.18 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 2.9471 | 0.0000 | 2.9471 | 0.7171 | 1063.29 | 0.00 | 4879.71 |
PACU_VAV_MID | 2.5482 | 0.0000 | 2.5482 | 0.7084 | 1048.51 | 0.00 | 4894.49 |
PACU_VAV_TOP | 2.7468 | 0.0000 | 2.7468 | 0.7171 | 1068.24 | 0.51 | 4874.25 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 20.64 | 4592.51 | 0.00 | 0.00 | 0.00 | 288.77 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 40.42 | 4606.11 | 0.00 | 0.00 | 0.00 | 271.80 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 22.28 | 4584.37 | 0.00 | 0.00 | 0.00 | 297.37 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3179 | 3.7563 | 0.0000 | 0.0000 | 0.0000 | 1.1166 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.3164 | 3.2270 | 0.0000 | 0.0000 | 0.0000 | 1.1253 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.3091 | 3.4992 | 0.0000 | 0.0000 | 0.0000 | 1.1422 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2021.98 | 15934.24 | 12-MAR-17:10 | 196515.56 | 16-OCT-11:00 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 441.13 | 383.73 | 01-JAN-00:10 | 100867.34 | 16-OCT-11:00 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 06-JAN-17:10 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 06-JAN-17:10 |
ElectricityPurchased:Facility | 2021.98 | 15934.24 | 12-MAR-17:10 | 196515.56 | 16-OCT-11:00 |
ElectricityPurchased:Plant | 2021.98 | 15934.24 | 12-MAR-17:10 | 196515.56 | 16-OCT-11:00 |
Cogeneration:ElectricityPurchased | 2021.98 | 15934.24 | 12-MAR-17:10 | 196515.56 | 16-OCT-11:00 |
General:Cogeneration:ElectricityPurchased | 2021.98 | 15934.24 | 12-MAR-17:10 | 196515.56 | 16-OCT-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2021.98 | 15934.24 | 12-MAR-17:10 | 196515.56 | 16-OCT-11:00 |
ElectricityNet:Plant | 2021.98 | 15934.24 | 12-MAR-17:10 | 196515.56 | 16-OCT-11:00 |
Cogeneration:ElectricityNet | 2021.98 | 15934.24 | 12-MAR-17:10 | 196515.56 | 16-OCT-11:00 |
General:Cogeneration:ElectricityNet | 2021.98 | 15934.24 | 12-MAR-17:10 | 196515.56 | 16-OCT-11:00 |
Fans:Electricity | 176.53 | 0.00 | 01-JAN-00:10 | 29812.10 | 29-SEP-15:50 |
General:Fans:Electricity | 176.53 | 0.00 | 01-JAN-00:10 | 29812.10 | 29-SEP-15:50 |
ExteriorLights:Electricity | 236.03 | 0.00 | 01-JAN-07:00 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 236.03 | 0.00 | 01-JAN-07:00 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 237.10 | 0.00 | 01-JAN-00:10 | 78826.62 | 16-OCT-11:00 |
General:Cooling:Electricity | 237.10 | 0.00 | 01-JAN-00:10 | 78826.62 | 16-OCT-11:00 |
Electricity:Plant | 49.29 | 0.00 | 01-JAN-00:10 | 5789.70 | 28-FEB-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 48.83 | 0.00 | 01-JAN-00:10 | 5763.72 | 02-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 48.83 | 0.00 | 01-JAN-00:10 | 5763.72 | 02-FEB-12:30 |
Pumps:Electricity | 0.46 | 0.00 | 01-JAN-00:10 | 618.12 | 09-JAN-07:10 |
General:Pumps:Electricity | 0.46 | 0.00 | 01-JAN-00:10 | 618.12 | 09-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 70.35 | 0.00 | 01-JAN-00:10 | 143987.28 | 09-JAN-06:20 |
NaturalGas:Plant | 70.35 | 0.00 | 01-JAN-00:10 | 143987.28 | 09-JAN-06:20 |
Heating:NaturalGas | 70.35 | 0.00 | 01-JAN-00:10 | 143987.28 | 09-JAN-06:20 |
Boiler:Heating:NaturalGas | 70.35 | 0.00 | 01-JAN-00:10 | 143987.28 | 09-JAN-06:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2587.61 | 0.00 | 01-JAN-00:10 | 456465.55 | 16-OCT-13:00 |
EnergyTransfer:Building | 1456.59 | 0.00 | 01-JAN-00:10 | 205452.38 | 16-OCT-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 279.63 | 0.00 | 01-JAN-00:10 | 26324.40 | 16-OCT-16:00 |
Heating:EnergyTransfer | 19.29 | 0.00 | 01-JAN-00:10 | 68116.34 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 19.29 | 0.00 | 01-JAN-00:10 | 68116.34 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1437.30 | 0.00 | 01-JAN-00:10 | 205452.38 | 16-OCT-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 279.63 | 0.00 | 01-JAN-00:10 | 26324.40 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer | 1437.30 | 0.00 | 01-JAN-00:10 | 205452.38 | 16-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 279.63 | 0.00 | 01-JAN-00:10 | 26324.40 | 16-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 80.08 | 0.00 | 01-JAN-00:10 | 16068.26 | 16-OCT-13:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.59 | 0.00 | 01-JAN-00:10 | 10704.40 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.59 | 0.00 | 01-JAN-00:10 | 10704.40 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 72.49 | 0.00 | 01-JAN-00:10 | 16068.26 | 16-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 72.49 | 0.00 | 01-JAN-00:10 | 16068.26 | 16-OCT-13:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.67 | 0.00 | 01-JAN-00:10 | 5354.29 | 16-OCT-15:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.98 | 0.00 | 01-JAN-00:10 | 3861.97 | 02-JAN-11:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.98 | 0.00 | 01-JAN-00:10 | 3861.97 | 02-JAN-11:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.70 | 0.00 | 01-JAN-00:10 | 5354.29 | 16-OCT-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.70 | 0.00 | 01-JAN-00:10 | 5354.29 | 16-OCT-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.93 | 0.00 | 01-JAN-00:10 | 5922.92 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.42 | 0.00 | 01-JAN-00:10 | 2050.55 | 08-JAN-10:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.42 | 0.00 | 01-JAN-00:10 | 2050.55 | 08-JAN-10:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.51 | 0.00 | 01-JAN-00:10 | 5922.92 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.51 | 0.00 | 01-JAN-00:10 | 5922.92 | 16-OCT-16:00 |
EnergyTransfer:Zone:CORE_MID | 178.60 | 0.00 | 01-JAN-00:10 | 19842.85 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 3890.31 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 3890.31 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 178.60 | 0.00 | 01-JAN-00:10 | 19842.85 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 178.60 | 0.00 | 01-JAN-00:10 | 19842.85 | 16-OCT-16:00 |
EnergyTransfer:Zone:CORE_TOP | 184.85 | 0.00 | 01-JAN-00:10 | 22734.66 | 16-OCT-13:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.21 | 0.00 | 01-JAN-00:10 | 10475.60 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.21 | 0.00 | 01-JAN-00:10 | 10475.60 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 184.64 | 0.00 | 01-JAN-00:10 | 22734.66 | 16-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 184.64 | 0.00 | 01-JAN-00:10 | 22734.66 | 16-OCT-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.10 | 0.00 | 01-JAN-00:10 | 8307.70 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.69 | 0.00 | 01-JAN-00:10 | 8307.70 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.69 | 0.00 | 01-JAN-00:10 | 8307.70 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.41 | 0.00 | 01-JAN-00:10 | 8093.46 | 29-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.41 | 0.00 | 01-JAN-00:10 | 8093.46 | 29-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.43 | 0.00 | 01-JAN-00:10 | 9269.43 | 16-OCT-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.69 | 0.00 | 01-JAN-00:10 | 5776.98 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.69 | 0.00 | 01-JAN-00:10 | 5776.98 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.74 | 0.00 | 01-JAN-00:10 | 9269.43 | 16-OCT-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.74 | 0.00 | 01-JAN-00:10 | 9269.43 | 16-OCT-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 83.98 | 0.00 | 01-JAN-00:10 | 18258.33 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.00 | 0.00 | 01-JAN-00:10 | 7827.83 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.00 | 0.00 | 01-JAN-00:10 | 7827.83 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 82.98 | 0.00 | 01-JAN-00:10 | 18258.33 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 82.98 | 0.00 | 01-JAN-00:10 | 18258.33 | 16-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.83 | 0.00 | 01-JAN-00:10 | 11287.24 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.10 | 0.00 | 01-JAN-00:10 | 5647.71 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.10 | 0.00 | 01-JAN-00:10 | 5647.71 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.73 | 0.00 | 01-JAN-00:10 | 11287.24 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.73 | 0.00 | 01-JAN-00:10 | 11287.24 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.42 | 0.00 | 01-JAN-00:10 | 6349.33 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.34 | 0.00 | 01-JAN-00:10 | 3659.14 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.34 | 0.00 | 01-JAN-00:10 | 3659.14 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.08 | 0.00 | 01-JAN-00:10 | 6349.33 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.08 | 0.00 | 01-JAN-00:10 | 6349.33 | 16-OCT-12:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 46.72 | 0.00 | 01-JAN-00:10 | 8424.64 | 16-OCT-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.12 | 0.00 | 01-JAN-00:10 | 2343.24 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.12 | 0.00 | 01-JAN-00:10 | 2343.24 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 46.59 | 0.00 | 01-JAN-00:10 | 8424.64 | 16-OCT-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 46.59 | 0.00 | 01-JAN-00:10 | 8424.64 | 16-OCT-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 71.80 | 0.00 | 01-JAN-00:10 | 18302.00 | 16-OCT-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.86 | 0.00 | 01-JAN-00:10 | 7616.86 | 30-MAR-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.86 | 0.00 | 01-JAN-00:10 | 7616.86 | 30-MAR-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 68.94 | 0.00 | 01-JAN-00:10 | 18302.00 | 16-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 68.94 | 0.00 | 01-JAN-00:10 | 18302.00 | 16-OCT-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 49.31 | 0.00 | 01-JAN-00:10 | 9589.77 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.19 | 0.00 | 01-JAN-00:10 | 2203.39 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.19 | 0.00 | 01-JAN-00:10 | 2203.39 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 49.12 | 0.00 | 01-JAN-00:10 | 9589.77 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 49.12 | 0.00 | 01-JAN-00:10 | 9589.77 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.70 | 0.00 | 01-JAN-00:10 | 7361.40 | 29-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.38 | 0.00 | 01-JAN-00:10 | 4752.56 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.38 | 0.00 | 01-JAN-00:10 | 4752.56 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.31 | 0.00 | 01-JAN-00:10 | 7361.40 | 29-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.31 | 0.00 | 01-JAN-00:10 | 7361.40 | 29-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 48.30 | 0.00 | 01-JAN-00:10 | 9493.76 | 29-SEP-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.19 | 0.00 | 01-JAN-00:10 | 3502.20 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.19 | 0.00 | 01-JAN-00:10 | 3502.20 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 48.11 | 0.00 | 01-JAN-00:10 | 9493.76 | 29-SEP-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 48.11 | 0.00 | 01-JAN-00:10 | 9493.76 | 29-SEP-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 83.52 | 0.00 | 01-JAN-00:10 | 16827.51 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.22 | 0.00 | 01-JAN-00:10 | 3801.72 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.22 | 0.00 | 01-JAN-00:10 | 3801.72 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 83.29 | 0.00 | 01-JAN-00:10 | 16827.51 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 83.29 | 0.00 | 01-JAN-00:10 | 16827.51 | 16-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 54.72 | 0.00 | 01-JAN-00:10 | 10921.74 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.30 | 0.00 | 01-JAN-00:10 | 3216.39 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.30 | 0.00 | 01-JAN-00:10 | 3216.39 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 54.41 | 0.00 | 01-JAN-00:10 | 10921.74 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 54.41 | 0.00 | 01-JAN-00:10 | 10921.74 | 29-SEP-15:30 |
PlantLoopHeatingDemand:Facility | 89.12 | 0.00 | 01-JAN-00:10 | 97118.74 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:40 |
EnergyTransfer:HVAC | 1042.25 | 0.00 | 01-JAN-00:10 | 262716.92 | 15-AUG-16:00 |
HeatingCoils:EnergyTransfer | 43.05 | 0.00 | 01-JAN-00:10 | 95308.20 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 43.05 | 0.00 | 01-JAN-00:10 | 95308.20 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 43.05 | 0.00 | 01-JAN-00:10 | 95308.20 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 999.20 | 0.00 | 01-JAN-00:10 | 262709.32 | 15-AUG-16:00 |
EnergyTransfer:Plant | 88.76 | 0.00 | 01-JAN-00:10 | 106112.57 | 02-JAN-07:10 |
WaterSystems:EnergyTransfer | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:40 |
Boilers:EnergyTransfer | 42.69 | 0.00 | 01-JAN-00:10 | 105085.76 | 09-JAN-06:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -279.630 | 0.000 | 0.000 | 32.706 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -124.862 |
CORE_MID | 0.000 | 0.000 | 0.002 | -178.602 | 0.000 | 0.000 | 33.131 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -81.743 |
CORE_TOP | 0.000 | 0.000 | 0.214 | -184.641 | 0.000 | 0.000 | 33.863 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -76.649 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.692 | -45.411 | 0.000 | 0.000 | 7.423 | 23.566 | 24.333 | 17.363 | 0.000 | 0.036 | 15.140 | 0.000 | -41.652 | 0.000 | -2.489 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.689 | -49.738 | 0.000 | 0.000 | 4.646 | 14.919 | 15.404 | 41.467 | 0.000 | 0.020 | 0.902 | 0.000 | -26.604 | 0.000 | -1.704 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.004 | -82.979 | 0.000 | 0.000 | 7.246 | 23.566 | 24.332 | 81.828 | 0.000 | 0.024 | 0.000 | 0.000 | -42.131 | 0.000 | -2.731 | -10.157 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.102 | -53.729 | 0.000 | 0.000 | 4.797 | 14.918 | 15.403 | 46.023 | 0.000 | 0.029 | 1.031 | 0.000 | -27.848 | 0.000 | -1.727 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.345 | -37.080 | 0.000 | 0.000 | 7.329 | 23.566 | 24.333 | 18.482 | 0.000 | 0.019 | 8.563 | 0.000 | -44.121 | 0.000 | -1.435 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.124 | -46.593 | 0.000 | 0.000 | 4.619 | 14.919 | 15.404 | 42.350 | 0.000 | 0.011 | 0.001 | 0.000 | -28.712 | 0.000 | -0.993 | -1.128 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.855 | -68.944 | 0.000 | 0.000 | 7.225 | 23.566 | 24.332 | 83.898 | 0.000 | 0.359 | 0.001 | 0.000 | -46.231 | 0.000 | -17.635 | -9.424 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.187 | -49.125 | 0.000 | 0.000 | 4.727 | 14.918 | 15.403 | 47.685 | 0.000 | 0.014 | 0.002 | 0.000 | -30.380 | 0.000 | -1.014 | -2.415 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.382 | -42.315 | 0.000 | 0.000 | 7.262 | 23.566 | 24.333 | 17.037 | 0.000 | 0.027 | 17.256 | 0.000 | -45.281 | 0.000 | -2.266 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.193 | -48.105 | 0.000 | 0.000 | 3.404 | 14.919 | 15.404 | 41.001 | 0.000 | 0.016 | 3.284 | 0.000 | -28.574 | 0.000 | -1.541 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.224 | -83.295 | 0.000 | 0.000 | 7.148 | 23.566 | 24.332 | 81.806 | 0.000 | 0.020 | 0.001 | 0.000 | -45.408 | 0.000 | -2.450 | -5.943 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.304 | -54.413 | 0.000 | 0.000 | 4.747 | 14.918 | 15.403 | 46.329 | 0.000 | 0.023 | 4.274 | 0.000 | -30.035 | 0.000 | -1.550 | -0.001 |
TOPFLOOR_PLENUM | 7.585 | -72.494 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.023 | 69.159 | 0.000 | 0.000 | 0.000 | -4.273 | -0.003 |
MIDFLOOR_PLENUM | 1.975 | -25.698 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.036 | 27.973 | 0.000 | 0.000 | 0.000 | -4.287 | -0.000 |
FIRSTFLOOR_PLENUM | 0.417 | -34.514 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.024 | 37.628 | 0.000 | 0.000 | 0.000 | -3.556 | -0.000 |
Total Facility | 9.978 | -132.705 | 9.316 | -1304.600 | 0.000 | 0.000 | 170.273 | 566.263 | 729.266 | 565.270 | 0.000 | 0.680 | 185.214 | 0.000 | -436.977 | 0.000 | -49.652 | -312.328 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | -48624.19 | 0.00 | 0.00 | 327.64 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 39477.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | -30394.80 | 0.00 | 0.00 | 338.81 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 25945.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 16-OCT-13:50 | 0.00 | 0.00 | 0.00 | -22736.01 | 0.00 | 0.00 | 3591.72 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 2575.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 29-SEP-13:10 | 0.00 | 0.00 | 0.00 | -8094.44 | 0.00 | 0.00 | 757.17 | 2057.62 | 1435.25 | 5380.39 | 0.00 | 106.82 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1642.81 |
PERIMETER_TOP_ZN_2 | 15-OCT-09:02 | 0.00 | 0.00 | 0.00 | -14666.11 | 0.00 | 0.00 | 13.24 | 72.37 | 302.86 | 10165.37 | 0.00 | 141.79 | 3970.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 19-NOV-10:51 | 0.00 | 0.00 | 0.00 | -25018.69 | 0.00 | 0.00 | 21.63 | 114.31 | 478.41 | 18796.84 | 0.00 | 0.00 | 5676.28 | 0.00 | -0.00 | 0.00 | -68.79 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-JUL-15:51 | 0.00 | 0.00 | 0.00 | -21236.58 | 0.00 | 0.00 | 14.06 | 72.36 | 302.86 | 9809.54 | 0.00 | 0.00 | 11224.96 | 0.00 | -0.00 | 0.00 | -187.21 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-OCT-12:05 | 0.00 | 0.00 | 0.00 | -6351.02 | 0.00 | 0.00 | 737.22 | 2057.62 | 1435.25 | 5000.97 | 0.00 | 75.20 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2955.24 |
PERIMETER_BOT_ZN_2 | 15-OCT-09:31 | 0.00 | 0.00 | 0.00 | -16766.12 | 0.00 | 0.00 | 14.07 | 72.37 | 302.86 | 8722.95 | 0.00 | 39.91 | 7613.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-11:31 | 0.00 | 0.00 | 0.00 | -21818.57 | 0.00 | 0.00 | 19.63 | 114.31 | 478.41 | 18090.70 | 0.00 | 45.68 | 3069.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 15-OCT-15:31 | 0.00 | 0.00 | 0.00 | -19175.91 | 0.00 | 0.00 | 12.36 | 72.36 | 302.86 | 11473.98 | 0.00 | 13.62 | 7300.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 29-SEP-13:10 | 0.00 | 0.00 | 0.00 | -7362.41 | 0.00 | 0.00 | 757.17 | 2057.62 | 1435.25 | 5430.56 | 0.00 | 89.12 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2407.32 |
PERIMETER_MID_ZN_2 | 15-OCT-08:11 | 0.00 | 0.00 | 0.00 | -18949.90 | 0.00 | 0.00 | 13.48 | 72.37 | 302.86 | 11453.93 | 0.00 | 39.90 | 7067.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-11:31 | 0.00 | 0.00 | 0.00 | -24063.35 | 0.00 | 0.00 | 18.31 | 114.31 | 478.41 | 17709.87 | 0.00 | 62.57 | 5679.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 15-OCT-15:31 | 0.00 | 0.00 | 0.00 | -21361.29 | 0.00 | 0.00 | 11.75 | 72.36 | 302.86 | 11193.92 | 0.00 | 18.55 | 9761.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-13:05 | 0.00 | -16096.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.04 | 15979.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 16-OCT-15:30 | 0.00 | -5354.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 5311.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 16-OCT-16:00 | 0.00 | -5923.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 | 5898.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-OCT-14:05 | 0.00 | -25829.98 | 0.00 | -180858.15 | 0.00 | 0.00 | 17661.54 | 49443.18 | 41937.01 | 90006.99 | 0.00 | 1531.69 | 6107.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:03 | 0.00 | 0.00 | 10471.39 | 0.00 | 0.00 | 0.00 | 907.81 | 3253.54 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17658.67 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 20449.29 | 0.00 | 0.00 | 0.00 | 482.11 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25041.83 |
PERIMETER_TOP_ZN_3 | 09-JAN-06:11 | 0.00 | 0.00 | 9675.67 | 0.00 | 0.00 | 0.00 | 112.14 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3832.55 | 0.00 | -100.27 | -6721.51 |
PERIMETER_TOP_ZN_2 | 09-JAN-06:11 | 0.00 | 0.00 | 8073.38 | 0.00 | 0.00 | 0.00 | 71.17 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2681.19 | 0.00 | -67.13 | -5944.78 |
PERIMETER_TOP_ZN_1 | 09-JAN-06:11 | 0.00 | 0.00 | 10816.32 | 0.00 | 0.00 | 0.00 | 110.34 | 228.62 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4215.73 | 0.00 | -104.86 | -7472.58 |
PERIMETER_TOP_ZN_4 | 09-JAN-06:11 | 0.00 | 0.00 | 8433.85 | 0.00 | 0.00 | 0.00 | 70.80 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2585.99 | 0.00 | -68.18 | -6399.01 |
PERIMETER_BOT_ZN_3 | 09-JAN-06:11 | 0.00 | 0.00 | 6335.92 | 0.00 | 0.00 | 0.00 | 103.86 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4447.61 | 0.00 | -61.80 | -2796.88 |
PERIMETER_BOT_ZN_2 | 03-JAN-06:11 | 0.00 | 0.00 | 5420.66 | 0.00 | 0.00 | 0.00 | 65.96 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2697.20 | 0.00 | -17.38 | -3320.59 |
PERIMETER_BOT_ZN_1 | 30-MAR-06:10 | 0.00 | 0.00 | 7965.20 | 0.00 | 0.00 | 0.00 | 193.28 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 4512.83 | 0.00 | -3571.26 | 0.00 | -10423.81 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-JAN-06:11 | 0.00 | 0.00 | 5413.10 | 0.00 | 0.00 | 0.00 | 65.72 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2640.94 | 0.00 | -17.53 | -3368.89 |
PERIMETER_MID_ZN_3 | 09-JAN-06:11 | 0.00 | 0.00 | 6860.46 | 0.00 | 0.00 | 0.00 | 105.66 | 228.62 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4368.14 | 0.00 | -94.05 | -3370.44 |
PERIMETER_MID_ZN_2 | 09-JAN-06:11 | 0.00 | 0.00 | 6242.80 | 0.00 | 0.00 | 0.00 | 67.67 | 144.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3026.19 | 0.00 | -62.24 | -3770.58 |
PERIMETER_MID_ZN_1 | 03-JAN-06:11 | 0.00 | 0.00 | 7935.95 | 0.00 | 0.00 | 0.00 | 104.34 | 228.62 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3928.66 | 0.00 | -40.51 | -4937.62 |
PERIMETER_MID_ZN_4 | 09-JAN-06:11 | 0.00 | 0.00 | 6181.63 | 0.00 | 0.00 | 0.00 | 67.28 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2921.12 | 0.00 | -63.01 | -3813.31 |
TOPFLOOR_PLENUM | 09-JAN-06:16 | 12611.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -157.07 | -12454.77 |
MIDFLOOR_PLENUM | 25-DEC-13:32 | 8272.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -16.55 | -8255.69 |
FIRSTFLOOR_PLENUM | 25-DEC-13:21 | 5908.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -35.35 | -5873.44 |
Total Facility | 09-JAN-06:11 | -16459.59 | 16348.57 | 107230.57 | -16348.57 | 0.00 | 0.00 | 2314.13 | 5493.69 | 20036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44146.96 | 0.00 | -3340.98 | -71127.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 7.1660 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.2418 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.8835 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.8280 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 7.7626 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 7.0885 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.5830 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.1498 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.4418 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0651 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.8813 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.3288 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3859 | 3.3859 | 1.0158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7524 | 2.7524 | 0.8257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1780 | 3.1780 | 0.9534 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0040 | 1.0040 | 0.3012 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0434 | 1.0434 | 0.3130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3412 | 1.3412 | 0.4024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1960 | 1.1960 | 0.3588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7635 | 0.7635 | 0.2290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9249 | 0.9249 | 0.2775 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0965 | 1.0965 | 0.3290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9951 | 0.9951 | 0.2985 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7997 | 0.7997 | 0.2399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0383 | 1.0383 | 0.3115 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1913 | 1.1913 | 0.3574 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1019 | 1.1019 | 0.3306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 7.1660 | 6.2418 | 7.1660 | 2.1498 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.8835 | 5.8280 | 6.8835 | 2.0651 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 7.7626 | 7.0885 | 7.7626 | 2.3288 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6929 | 1.6929 | 1.0158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3762 | 1.3762 | 0.8257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5890 | 1.5890 | 0.9534 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5020 | 0.5020 | 0.3012 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5217 | 0.5217 | 0.3130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6706 | 0.6706 | 0.4024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5980 | 0.5980 | 0.3588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3817 | 0.3817 | 0.2290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4625 | 0.4625 | 0.2775 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5483 | 0.5483 | 0.3290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4976 | 0.4976 | 0.2985 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3998 | 0.3998 | 0.2399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5191 | 0.5191 | 0.3115 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5957 | 0.5957 | 0.3574 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5509 | 0.5509 | 0.3306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.5830 | 2.1498 | 2.1498 | 2.1498 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.4418 | 2.0651 | 2.0651 | 2.0651 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.8813 | 2.3288 | 2.3288 | 2.3288 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 32.33 |
Number of hours cooling loads not met | 108.17 |
Number of hours not met | 140.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 70.35 | 143987.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 237.10 | 78826.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 236.03 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 176.53 | 29812.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.46 | 618.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 48.83 | 5763.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 2021.98 |
Natural Gas | 0.00 | 70.35 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2092.33 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 47.59 |
Fans (All) | 35.43 |
Service Water Heating | 9.80 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 405.84 |
Subtotal | 405.84 |
Natural Gas [MJ/m2] | |
Space Heating | 14.12 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 14.12 |
Subtotal | 14.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 27.06 |
Space Heating | 3.36 |
Space Cooling | 11.33 |
Fans (All) | 8.44 |
Service Water Heating | 2.33 |
Receptacle Equipment | 34.85 |
Miscellaneous | 12.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8705.50 | 54.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8728.67 | 31.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8728.67 | 31.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8728.17 | 31.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8730.50 | 29.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8551.50 | 208.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8551.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 208.50 | 0.00 | 0.00 | 0.00 |
Average | 8730.28 | 29.72 | 0.00 | 0.00 | 0.00 |
Sum | 157145.00 | 535.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 6.67 | 0.00 | 0.00 | 0.00 |
Average | 34142.96 | 0.37 | 0.00 | 0.00 | 0.00 |
Sum | 614573.33 | 6.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7768.17 | 991.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8455.33 | 304.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8697.33 | 62.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8703.33 | 56.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8684.33 | 75.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8700.83 | 59.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8700.67 | 59.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8686.33 | 73.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8689.17 | 70.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8694.67 | 65.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8676.00 | 84.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8050.17 | 709.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8724.17 | 35.83 | 0.00 | 0.00 | 0.00 |
Min | 7768.17 | 3.50 | 0.00 | 0.00 | 0.00 |
Max | 8756.50 | 991.83 | 0.00 | 0.00 | 0.00 |
Average | 8609.73 | 150.27 | 0.00 | 0.00 | 0.00 |
Sum | 154975.17 | 2704.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127881.00 | 423.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128194.50 | 109.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128300.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24902.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128300.67 | 423.00 | 0.00 | 0.00 | 0.00 |
Average | 34113.19 | 30.14 | 0.00 | 0.00 | 0.00 |
Sum | 614037.50 | 542.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198835E+11 | 22419.10 | 20-JAN-16:20 | 16.67 | 14.61 | 0.198500E+10 | 2606.78 | 10-JAN-14:09 | 16.67 | 14.61 |
February | 0.181831E+11 | 22090.42 | 03-FEB-17:00 | 18.00 | 9.93 | 0.180242E+10 | 2606.90 | 01-FEB-14:09 | 18.00 | 9.93 |
March | 0.211977E+11 | 22591.63 | 24-MAR-16:00 | 18.00 | 14.96 | 0.215341E+10 | 2606.73 | 01-MAR-14:09 | 18.00 | 14.96 |
April | 0.220691E+11 | 28544.56 | 27-APR-05:13 | 15.00 | 14.41 | 0.191480E+10 | 2606.82 | 13-APR-09:00 | 15.00 | 14.41 |
May | 0.238089E+11 | 29236.75 | 05-MAY-05:13 | 14.67 | 13.88 | 0.207547E+10 | 2606.73 | 24-MAY-09:50 | 20.50 | 11.60 |
June | 0.256177E+11 | 32734.19 | 30-JUN-05:13 | 17.00 | 16.37 | 0.207032E+10 | 2606.68 | 29-JUN-13:30 | 17.00 | 16.37 |
July | 0.268454E+11 | 36414.12 | 20-JUL-05:13 | 17.00 | 17.00 | 0.192429E+10 | 2606.64 | 11-JUL-09:20 | 17.00 | 17.00 |
August | 0.289690E+11 | 36027.45 | 18-AUG-05:13 | 17.83 | 17.37 | 0.215982E+10 | 2606.64 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.251226E+11 | 45491.25 | 30-SEP-05:12 | 23.80 | 13.84 | 0.191774E+10 | 2606.67 | 21-SEP-09:20 | 23.80 | 13.84 |
October | 0.259479E+11 | 48635.96 | 02-OCT-05:12 | 19.07 | 17.72 | 0.199396E+10 | 2606.79 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.214763E+11 | 26134.85 | 01-NOV-05:13 | 12.67 | 9.99 | 0.197232E+10 | 2606.96 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.205081E+11 | 22213.76 | 07-DEC-16:20 | 17.33 | 14.71 | 0.191842E+10 | 2607.09 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.279629E+12 | 0.238880E+11 | ||||||||
Minimum of Months | 0.181831E+11 | 22090.42 | 12.67 | 9.93 | 0.180242E+10 | 2606.64 | 15.00 | 9.93 | ||
Maximum of Months | 0.289690E+11 | 48635.96 | 23.80 | 17.72 | 0.215982E+10 | 2607.09 | 23.80 | 18.23 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308706E+10 | 9022.07 | 18-JAN-14:15 | 24.07 | 14.82 | 0.00 | 0.00 | 01-JAN-00:10 | 24.07 | 14.82 |
February | 0.289934E+10 | 8882.06 | 01-FEB-13:05 | 23.17 | 14.41 | 0.00 | 0.00 | 01-FEB-00:10 | 23.17 | 14.41 |
March | 0.423757E+10 | 11884.66 | 23-MAR-14:05 | 22.83 | 17.30 | 0.00 | 0.00 | 01-MAR-00:10 | 22.83 | 17.30 |
April | 0.686609E+10 | 15094.15 | 26-APR-13:30 | 26.50 | 16.94 | 0.00 | 0.00 | 01-APR-00:10 | 26.50 | 16.94 |
May | 0.681185E+10 | 14018.57 | 03-MAY-13:05 | 23.83 | 15.35 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 15.35 |
June | 0.844751E+10 | 13922.72 | 21-JUN-13:20 | 23.67 | 16.91 | 0.00 | 0.00 | 01-JUN-00:10 | 23.67 | 16.91 |
July | 0.101661E+11 | 15497.32 | 31-JUL-13:05 | 27.83 | 21.13 | 0.00 | 0.00 | 01-JUL-00:10 | 27.83 | 21.13 |
August | 0.102865E+11 | 14970.11 | 14-AUG-13:05 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.724100E+10 | 16050.34 | 29-SEP-14:05 | 33.83 | 17.79 | 0.00 | 0.00 | 01-SEP-00:10 | 33.83 | 17.79 |
October | 0.609329E+10 | 16096.26 | 16-OCT-13:05 | 33.75 | 16.65 | 0.00 | 0.00 | 01-OCT-00:10 | 33.75 | 16.65 |
November | 0.336850E+10 | 8429.72 | 10-NOV-13:40 | 20.33 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 20.33 | 15.94 |
December | 0.298880E+10 | 8252.71 | 19-DEC-13:20 | 25.00 | 11.01 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 11.01 |
Annual Sum or Average | 0.724936E+11 | 0.00 | ||||||||
Minimum of Months | 0.289934E+10 | 8252.71 | 20.33 | 11.01 | 0.00 | 0.00 | 20.33 | 11.01 | ||
Maximum of Months | 0.102865E+11 | 16096.26 | 33.83 | 21.13 | 0.00 | 0.00 | 33.83 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115747E+10 | 5155.32 | 13-JAN-06:11 | 6.67 | 5.71 | 0.00 | 0.00 | 01-JAN-00:10 | 6.67 | 5.71 |
February | 0.114497E+10 | 4110.23 | 04-FEB-07:03 | 9.50 | 2.54 | 0.00 | 0.00 | 01-FEB-00:10 | 9.50 | 2.54 |
March | 0.133300E+10 | 5288.66 | 08-MAR-06:11 | 5.33 | 4.40 | 0.00 | 0.00 | 01-MAR-00:10 | 5.33 | 4.40 |
April | 0.196978E+10 | 5029.31 | 01-APR-05:11 | 7.67 | 4.93 | 0.00 | 0.00 | 01-APR-00:10 | 7.67 | 4.93 |
May | 0.215537E+10 | 3186.95 | 26-MAY-05:25 | 12.00 | 10.91 | 0.00 | 0.00 | 01-MAY-00:10 | 12.00 | 10.91 |
June | 0.277990E+10 | 3246.37 | 30-JUN-16:00 | 22.70 | 17.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.70 | 17.88 |
July | 0.335092E+10 | 3695.07 | 19-JUL-16:00 | 25.00 | 20.20 | 0.00 | 0.00 | 01-JUL-00:10 | 25.00 | 20.20 |
August | 0.365883E+10 | 3769.30 | 17-AUG-16:00 | 25.00 | 20.20 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 20.20 |
September | 0.277966E+10 | 4602.81 | 29-SEP-15:40 | 32.33 | 17.07 | 0.00 | 0.00 | 01-SEP-00:10 | 32.33 | 17.07 |
October | 0.273435E+10 | 5354.29 | 16-OCT-15:30 | 29.50 | 15.76 | 0.00 | 0.00 | 01-OCT-00:10 | 29.50 | 15.76 |
November | 0.140318E+10 | 3957.17 | 03-NOV-06:03 | 11.00 | 8.06 | 0.00 | 0.00 | 01-NOV-00:10 | 11.00 | 8.06 |
December | 0.123027E+10 | 5263.25 | 23-DEC-06:11 | 5.33 | 2.46 | 0.00 | 0.00 | 01-DEC-00:10 | 5.33 | 2.46 |
Annual Sum or Average | 0.256977E+11 | 0.00 | ||||||||
Minimum of Months | 0.114497E+10 | 3186.95 | 5.33 | 2.46 | 0.00 | 0.00 | 5.33 | 2.46 | ||
Maximum of Months | 0.365883E+10 | 5354.29 | 32.33 | 20.20 | 0.00 | 0.00 | 32.33 | 20.20 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189174E+10 | 4565.05 | 09-JAN-06:11 | 2.33 | 0.02 | 0.00 | 0.00 | 01-JAN-00:10 | 2.33 | 0.02 |
February | 0.179249E+10 | 4395.98 | 25-FEB-07:03 | 12.00 | 11.46 | 0.00 | 0.00 | 01-FEB-00:10 | 12.00 | 11.46 |
March | 0.201737E+10 | 5272.29 | 08-MAR-06:11 | 5.33 | 4.40 | 0.00 | 0.00 | 01-MAR-00:10 | 5.33 | 4.40 |
April | 0.261186E+10 | 4401.41 | 18-APR-06:03 | 12.17 | 10.60 | 0.00 | 0.00 | 01-APR-00:10 | 12.17 | 10.60 |
May | 0.283956E+10 | 3300.33 | 05-MAY-05:20 | 14.67 | 13.88 | 0.00 | 0.00 | 01-MAY-00:10 | 14.67 | 13.88 |
June | 0.343415E+10 | 3621.89 | 30-JUN-16:00 | 22.70 | 17.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.70 | 17.88 |
July | 0.398460E+10 | 4154.61 | 19-JUL-16:00 | 25.00 | 20.20 | 0.00 | 0.00 | 01-JUL-00:10 | 25.00 | 20.20 |
August | 0.437670E+10 | 4301.88 | 18-AUG-15:30 | 25.50 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.50 | 20.42 |
September | 0.353153E+10 | 5237.21 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.362711E+10 | 5922.92 | 16-OCT-16:00 | 29.00 | 15.43 | 0.00 | 0.00 | 01-OCT-00:10 | 29.00 | 15.43 |
November | 0.233228E+10 | 3823.27 | 30-NOV-07:03 | 8.67 | 2.58 | 0.00 | 0.00 | 01-NOV-00:10 | 8.67 | 2.58 |
December | 0.207426E+10 | 4892.35 | 13-DEC-06:11 | 6.33 | 5.37 | 0.00 | 0.00 | 01-DEC-00:10 | 6.33 | 5.37 |
Annual Sum or Average | 0.345136E+11 | 0.00 | ||||||||
Minimum of Months | 0.179249E+10 | 3300.33 | 2.33 | 0.02 | 0.00 | 0.00 | 2.33 | 0.02 | ||
Maximum of Months | 0.437670E+10 | 5922.92 | 32.00 | 20.42 | 0.00 | 0.00 | 32.00 | 20.42 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119819E+11 | 14794.45 | 19-JAN-16:20 | 18.67 | 14.64 | 0.191100E+10 | 2606.69 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.111079E+11 | 14626.54 | 03-FEB-17:00 | 18.00 | 9.93 | 0.174178E+10 | 2606.87 | 01-FEB-14:09 | 18.00 | 9.93 |
March | 0.128689E+11 | 15452.82 | 24-MAR-16:00 | 18.00 | 14.96 | 0.208480E+10 | 2606.69 | 01-MAR-14:09 | 18.00 | 14.96 |
April | 0.142808E+11 | 16876.77 | 27-APR-16:00 | 18.00 | 14.37 | 0.188403E+10 | 2606.75 | 13-APR-09:00 | 18.00 | 14.37 |
May | 0.153101E+11 | 16941.32 | 04-MAY-16:00 | 22.00 | 15.83 | 0.204871E+10 | 2606.70 | 05-MAY-13:00 | 18.00 | 16.13 |
June | 0.169808E+11 | 17550.88 | 30-JUN-16:00 | 22.70 | 17.88 | 0.205462E+10 | 2606.65 | 08-JUN-09:30 | 22.70 | 17.88 |
July | 0.181152E+11 | 18025.13 | 19-JUL-16:00 | 25.00 | 20.20 | 0.191395E+10 | 2606.64 | 13-JUL-09:20 | 25.00 | 20.20 |
August | 0.195262E+11 | 18148.54 | 18-AUG-16:00 | 24.00 | 19.89 | 0.215008E+10 | 2606.63 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.163274E+11 | 18406.77 | 29-SEP-16:00 | 32.00 | 16.86 | 0.190208E+10 | 2606.67 | 21-SEP-09:20 | 32.00 | 16.86 |
October | 0.167912E+11 | 30393.23 | 02-OCT-05:12 | 19.07 | 17.72 | 0.197533E+10 | 2606.75 | 18-OCT-13:09 | 22.83 | 18.37 |
November | 0.129757E+11 | 15228.78 | 01-NOV-16:00 | 16.80 | 12.58 | 0.193371E+10 | 2606.85 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.123354E+11 | 14593.37 | 07-DEC-16:20 | 17.33 | 14.71 | 0.186313E+10 | 2606.99 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.178602E+12 | 0.234632E+11 | ||||||||
Minimum of Months | 0.111079E+11 | 14593.37 | 16.80 | 9.93 | 0.174178E+10 | 2606.63 | 16.83 | 9.93 | ||
Maximum of Months | 0.195262E+11 | 30393.23 | 32.00 | 20.20 | 0.215008E+10 | 2606.99 | 32.00 | 20.20 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114850E+11 | 14581.14 | 19-JAN-15:50 | 19.17 | 14.83 | 0.180233E+10 | 2606.70 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.109235E+11 | 14893.19 | 02-FEB-15:50 | 18.17 | 13.25 | 0.165142E+10 | 2606.87 | 01-FEB-14:09 | 18.17 | 13.25 |
March | 0.131154E+11 | 17274.56 | 24-MAR-15:20 | 18.00 | 15.28 | 0.197530E+10 | 2606.67 | 09-MAR-14:20 | 18.00 | 15.28 |
April | 0.152961E+11 | 19790.27 | 27-APR-14:50 | 19.37 | 15.15 | 0.183514E+10 | 2606.72 | 13-APR-13:00 | 19.37 | 15.15 |
May | 0.163662E+11 | 19993.91 | 03-MAY-14:50 | 22.17 | 15.60 | 0.200411E+10 | 2606.72 | 05-MAY-13:00 | 18.00 | 16.13 |
June | 0.185254E+11 | 20965.98 | 30-JUN-15:00 | 23.00 | 17.85 | 0.203031E+10 | 2606.67 | 29-JUN-13:30 | 23.00 | 17.85 |
July | 0.201186E+11 | 21552.92 | 19-JUL-15:00 | 27.00 | 20.17 | 0.189857E+10 | 2606.64 | 13-JUL-09:20 | 27.00 | 20.17 |
August | 0.212062E+11 | 21419.91 | 17-AUG-15:20 | 26.13 | 20.58 | 0.213147E+10 | 2606.63 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.169496E+11 | 21053.59 | 29-SEP-14:00 | 34.00 | 17.85 | 0.186980E+10 | 2606.66 | 13-SEP-09:09 | 34.00 | 17.85 |
October | 0.166252E+11 | 22734.66 | 16-OCT-13:50 | 32.35 | 16.00 | 0.193114E+10 | 2606.77 | 18-OCT-13:09 | 22.83 | 18.37 |
November | 0.123653E+11 | 14772.29 | 10-NOV-15:00 | 19.00 | 15.88 | 0.184533E+10 | 2606.85 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.116639E+11 | 14312.59 | 05-DEC-16:00 | 23.00 | 12.42 | 0.175574E+10 | 2606.98 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.184640E+12 | 0.227307E+11 | ||||||||
Minimum of Months | 0.109235E+11 | 14312.59 | 18.00 | 12.42 | 0.165142E+10 | 2606.63 | 16.83 | 10.63 | ||
Maximum of Months | 0.212062E+11 | 22734.66 | 34.00 | 20.58 | 0.213147E+10 | 2606.98 | 34.00 | 20.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228654E+10 | 3501.34 | 18-JAN-13:30 | 25.30 | 14.77 | 0.342662E+09 | 549.50 | 24-JAN-14:20 | 24.33 | 14.96 |
February | 0.218870E+10 | 3121.42 | 20-FEB-14:12 | 17.00 | 11.31 | 0.316087E+09 | 549.47 | 03-FEB-14:00 | 17.00 | 11.31 |
March | 0.275418E+10 | 4025.88 | 23-MAR-14:40 | 22.33 | 17.37 | 0.379700E+09 | 549.50 | 24-MAR-13:20 | 19.00 | 15.88 |
April | 0.367720E+10 | 5788.84 | 26-APR-14:00 | 26.00 | 16.74 | 0.366054E+09 | 549.51 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.422698E+10 | 6152.58 | 04-MAY-13:30 | 23.00 | 16.67 | 0.404042E+09 | 549.52 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.510644E+10 | 5814.39 | 30-JUN-14:00 | 23.00 | 17.85 | 0.417151E+09 | 549.51 | 29-JUN-13:30 | 23.00 | 17.85 |
July | 0.571935E+10 | 6718.48 | 19-JUL-14:30 | 27.00 | 20.51 | 0.393467E+09 | 549.50 | 14-JUL-13:30 | 27.00 | 20.51 |
August | 0.575246E+10 | 6647.18 | 17-AUG-14:00 | 28.00 | 21.19 | 0.438461E+09 | 549.50 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.444557E+10 | 8093.95 | 29-SEP-13:10 | 35.67 | 18.16 | 0.378026E+09 | 549.50 | 22-SEP-13:20 | 35.67 | 18.16 |
October | 0.427794E+10 | 8017.04 | 16-OCT-12:30 | 35.05 | 17.21 | 0.388680E+09 | 549.51 | 18-OCT-13:09 | 22.83 | 18.37 |
November | 0.266001E+10 | 3784.01 | 19-NOV-13:31 | 25.67 | 15.08 | 0.352199E+09 | 548.74 | 28-NOV-14:39 | 23.67 | 10.89 |
December | 0.231547E+10 | 3478.89 | 05-DEC-15:00 | 25.00 | 13.22 | 0.331319E+09 | 549.51 | 05-DEC-14:20 | 25.00 | 13.22 |
Annual Sum or Average | 0.454108E+11 | 0.450785E+10 | ||||||||
Minimum of Months | 0.218870E+10 | 3121.42 | 17.00 | 11.31 | 0.316087E+09 | 548.74 | 17.00 | 10.89 | ||
Maximum of Months | 0.575246E+10 | 8093.95 | 35.67 | 21.19 | 0.438461E+09 | 549.52 | 35.67 | 20.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262026E+10 | 4503.90 | 20-JAN-09:40 | 18.33 | 14.51 | 0.224176E+09 | 347.88 | 19-JAN-10:00 | 18.33 | 14.51 |
February | 0.234693E+10 | 4375.27 | 01-FEB-10:00 | 24.00 | 12.54 | 0.205584E+09 | 347.89 | 01-FEB-10:00 | 23.00 | 13.44 |
March | 0.307434E+10 | 7008.58 | 23-MAR-09:00 | 19.00 | 14.76 | 0.247484E+09 | 347.88 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.437939E+10 | 8326.67 | 26-APR-09:10 | 23.17 | 16.73 | 0.241643E+09 | 347.91 | 13-APR-09:50 | 23.17 | 16.73 |
May | 0.449572E+10 | 13083.54 | 28-MAY-08:22 | 18.50 | 14.07 | 0.258580E+09 | 347.90 | 04-MAY-09:00 | 18.50 | 14.07 |
June | 0.531969E+10 | 8700.66 | 25-JUN-09:13 | 22.33 | 16.69 | 0.263240E+09 | 347.89 | 22-JUN-09:50 | 22.33 | 16.69 |
July | 0.626668E+10 | 14249.82 | 23-JUL-08:52 | 25.00 | 19.60 | 0.251469E+09 | 347.88 | 17-JUL-09:50 | 25.00 | 19.60 |
August | 0.654253E+10 | 10109.37 | 06-AUG-09:13 | 23.67 | 19.41 | 0.281599E+09 | 347.88 | 04-AUG-09:20 | 23.67 | 19.41 |
September | 0.474572E+10 | 10876.53 | 03-SEP-08:12 | 18.67 | 14.63 | 0.241715E+09 | 347.89 | 13-SEP-09:09 | 22.17 | 18.15 |
October | 0.444671E+10 | 14665.83 | 15-OCT-09:02 | 32.67 | 16.02 | 0.248407E+09 | 347.91 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.286832E+10 | 4865.37 | 19-NOV-10:12 | 26.00 | 14.29 | 0.227177E+09 | 347.88 | 20-NOV-10:09 | 16.33 | 14.28 |
December | 0.263172E+10 | 4523.23 | 05-DEC-09:50 | 25.67 | 12.88 | 0.215841E+09 | 347.88 | 19-DEC-10:20 | 23.67 | 10.25 |
Annual Sum or Average | 0.497380E+11 | 0.290692E+10 | ||||||||
Minimum of Months | 0.234693E+10 | 4375.27 | 18.33 | 12.54 | 0.205584E+09 | 347.88 | 16.33 | 10.25 | ||
Maximum of Months | 0.654253E+10 | 14665.83 | 32.67 | 19.60 | 0.281599E+09 | 347.91 | 25.00 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.727501E+10 | 24338.84 | 22-JAN-13:12 | 17.33 | 12.40 | 0.392089E+09 | 549.94 | 18-JAN-14:00 | 17.33 | 12.40 |
February | 0.523427E+10 | 22824.95 | 20-FEB-13:32 | 17.00 | 10.76 | 0.344865E+09 | 549.56 | 01-FEB-14:09 | 17.00 | 10.76 |
March | 0.551463E+10 | 20065.98 | 19-MAR-13:22 | 19.50 | 14.94 | 0.401032E+09 | 549.53 | 01-MAR-14:09 | 19.50 | 14.94 |
April | 0.615584E+10 | 11226.45 | 26-APR-13:00 | 27.00 | 17.13 | 0.371987E+09 | 549.53 | 13-APR-09:00 | 27.00 | 17.13 |
May | 0.531200E+10 | 8092.68 | 04-MAY-12:30 | 23.50 | 16.62 | 0.396346E+09 | 549.52 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.596880E+10 | 7355.27 | 30-JUN-12:40 | 23.33 | 17.95 | 0.406080E+09 | 549.51 | 29-JUN-13:30 | 23.33 | 17.95 |
July | 0.694485E+10 | 10083.86 | 31-JUL-12:40 | 28.00 | 21.19 | 0.385852E+09 | 549.50 | 14-JUL-13:30 | 28.00 | 21.19 |
August | 0.843946E+10 | 12333.67 | 20-AUG-13:22 | 23.50 | 18.29 | 0.435228E+09 | 549.50 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.818517E+10 | 17889.03 | 29-SEP-13:00 | 36.00 | 18.20 | 0.382046E+09 | 549.82 | 29-SEP-13:00 | 34.00 | 17.85 |
October | 0.909046E+10 | 24569.65 | 15-OCT-12:22 | 32.00 | 16.37 | 0.399451E+09 | 553.06 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.728852E+10 | 25019.84 | 19-NOV-10:51 | 26.00 | 15.07 | 0.391568E+09 | 549.74 | 30-NOV-14:09 | 22.67 | 10.93 |
December | 0.756922E+10 | 23710.08 | 03-DEC-13:42 | 16.83 | 12.84 | 0.378357E+09 | 549.96 | 29-DEC-14:09 | 23.00 | 10.56 |
Annual Sum or Average | 0.829782E+11 | 0.468490E+10 | ||||||||
Minimum of Months | 0.523427E+10 | 7355.27 | 16.83 | 10.76 | 0.344865E+09 | 549.50 | 17.00 | 10.56 | ||
Maximum of Months | 0.909046E+10 | 25019.84 | 36.00 | 21.19 | 0.435228E+09 | 553.06 | 34.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267788E+10 | 6495.52 | 18-JAN-14:50 | 23.27 | 14.80 | 0.217720E+09 | 347.86 | 18-JAN-14:20 | 23.27 | 14.80 |
February | 0.256695E+10 | 6913.26 | 22-FEB-15:40 | 16.60 | 12.17 | 0.197386E+09 | 347.87 | 01-FEB-14:09 | 16.60 | 12.17 |
March | 0.332325E+10 | 10674.01 | 19-MAR-16:42 | 17.17 | 14.59 | 0.235050E+09 | 347.86 | 10-MAR-14:00 | 17.17 | 14.59 |
April | 0.473016E+10 | 10006.58 | 26-APR-15:50 | 22.17 | 16.38 | 0.221261E+09 | 347.87 | 13-APR-13:00 | 22.17 | 16.38 |
May | 0.491963E+10 | 15707.99 | 14-MAY-16:22 | 17.00 | 12.41 | 0.240986E+09 | 347.87 | 03-MAY-13:00 | 17.00 | 12.41 |
June | 0.591025E+10 | 21026.83 | 25-JUN-15:51 | 21.00 | 16.52 | 0.248736E+09 | 347.86 | 29-JUN-13:30 | 23.50 | 18.87 |
July | 0.664496E+10 | 21241.07 | 16-JUL-15:51 | 21.00 | 16.52 | 0.237375E+09 | 347.85 | 14-JUL-13:30 | 21.00 | 16.52 |
August | 0.685187E+10 | 16637.99 | 20-AUG-16:02 | 21.80 | 17.34 | 0.265014E+09 | 347.85 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.537322E+10 | 17672.12 | 03-SEP-16:12 | 19.00 | 15.88 | 0.227832E+09 | 347.85 | 05-SEP-13:20 | 21.67 | 17.97 |
October | 0.483467E+10 | 20381.64 | 15-OCT-15:02 | 30.83 | 15.40 | 0.233667E+09 | 347.86 | 31-OCT-13:20 | 26.67 | 16.70 |
November | 0.314238E+10 | 6475.80 | 07-NOV-15:30 | 19.00 | 14.51 | 0.220932E+09 | 347.92 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.275342E+10 | 6559.62 | 18-DEC-15:30 | 22.00 | 8.99 | 0.209501E+09 | 347.93 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.537286E+11 | 0.275546E+10 | ||||||||
Minimum of Months | 0.256695E+10 | 6475.80 | 16.60 | 8.99 | 0.197386E+09 | 347.85 | 16.60 | 12.17 | ||
Maximum of Months | 0.685187E+10 | 21241.07 | 30.83 | 17.34 | 0.265014E+09 | 347.93 | 26.67 | 18.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210578E+10 | 2912.13 | 18-JAN-13:00 | 26.00 | 14.69 | 0.351894E+09 | 549.50 | 19-JAN-14:20 | 20.67 | 15.33 |
February | 0.195782E+10 | 2375.89 | 20-FEB-14:22 | 17.00 | 11.46 | 0.319836E+09 | 535.91 | 03-FEB-14:00 | 17.00 | 11.46 |
March | 0.230884E+10 | 2325.40 | 23-MAR-14:50 | 22.17 | 17.39 | 0.383097E+09 | 546.29 | 23-MAR-13:00 | 22.17 | 17.39 |
April | 0.280476E+10 | 3780.53 | 26-APR-13:50 | 26.17 | 16.81 | 0.368702E+09 | 549.51 | 13-APR-13:00 | 26.17 | 16.81 |
May | 0.323192E+10 | 4355.18 | 04-MAY-14:10 | 22.83 | 16.63 | 0.412052E+09 | 549.51 | 05-MAY-13:00 | 18.00 | 16.13 |
June | 0.381480E+10 | 4238.88 | 29-JUN-16:00 | 23.00 | 18.43 | 0.424489E+09 | 549.50 | 12-JUN-13:20 | 23.00 | 18.43 |
July | 0.440485E+10 | 5094.06 | 19-JUL-14:50 | 27.00 | 20.29 | 0.399329E+09 | 549.50 | 11-JUL-09:20 | 27.00 | 20.29 |
August | 0.444715E+10 | 5071.77 | 18-AUG-15:00 | 27.00 | 20.85 | 0.446014E+09 | 549.50 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.355210E+10 | 6244.19 | 29-SEP-13:00 | 36.00 | 18.20 | 0.388935E+09 | 549.50 | 22-SEP-13:20 | 36.00 | 18.20 |
October | 0.369446E+10 | 6350.72 | 16-OCT-12:05 | 35.68 | 17.48 | 0.401087E+09 | 549.51 | 18-OCT-13:09 | 22.83 | 18.37 |
November | 0.251161E+10 | 2827.11 | 19-NOV-13:42 | 25.33 | 15.09 | 0.365383E+09 | 544.12 | 02-NOV-13:50 | 25.33 | 15.09 |
December | 0.224535E+10 | 2867.90 | 19-DEC-13:10 | 25.50 | 11.30 | 0.340871E+09 | 541.82 | 05-DEC-14:00 | 25.50 | 11.30 |
Annual Sum or Average | 0.370794E+11 | 0.460169E+10 | ||||||||
Minimum of Months | 0.195782E+10 | 2325.40 | 17.00 | 11.30 | 0.319836E+09 | 535.91 | 17.00 | 11.30 | ||
Maximum of Months | 0.444715E+10 | 6350.72 | 36.00 | 20.85 | 0.446014E+09 | 549.51 | 36.00 | 20.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276032E+10 | 4167.64 | 20-JAN-09:30 | 18.00 | 14.38 | 0.229060E+09 | 347.88 | 19-JAN-10:00 | 18.00 | 14.38 |
February | 0.238078E+10 | 3859.24 | 01-FEB-10:00 | 24.00 | 12.54 | 0.206203E+09 | 347.89 | 01-FEB-10:00 | 23.00 | 13.44 |
March | 0.296172E+10 | 5875.85 | 23-MAR-09:00 | 19.00 | 14.76 | 0.247458E+09 | 347.88 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.391499E+10 | 7090.11 | 26-APR-08:40 | 22.67 | 16.58 | 0.241449E+09 | 347.91 | 13-APR-09:00 | 22.67 | 16.58 |
May | 0.402409E+10 | 10319.17 | 28-MAY-08:52 | 19.00 | 14.25 | 0.259022E+09 | 347.89 | 24-MAY-09:39 | 19.00 | 14.25 |
June | 0.457717E+10 | 15693.89 | 25-JUN-09:02 | 22.17 | 16.55 | 0.264020E+09 | 347.88 | 02-JUN-09:00 | 22.17 | 16.55 |
July | 0.552341E+10 | 16057.83 | 02-JUL-09:02 | 22.00 | 16.84 | 0.252977E+09 | 347.88 | 17-JUL-09:20 | 21.67 | 16.98 |
August | 0.585592E+10 | 16158.05 | 13-AUG-09:12 | 24.00 | 19.51 | 0.283649E+09 | 347.88 | 23-AUG-09:20 | 21.67 | 16.23 |
September | 0.435533E+10 | 8955.18 | 10-SEP-08:32 | 21.00 | 17.14 | 0.244346E+09 | 347.88 | 12-SEP-09:20 | 21.67 | 16.41 |
October | 0.432077E+10 | 16766.25 | 15-OCT-09:31 | 31.67 | 16.34 | 0.252310E+09 | 347.90 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.305760E+10 | 3811.78 | 19-NOV-08:30 | 21.50 | 11.71 | 0.232925E+09 | 347.88 | 20-NOV-10:20 | 16.67 | 14.43 |
December | 0.286090E+10 | 4111.19 | 05-DEC-09:50 | 25.67 | 12.88 | 0.220581E+09 | 347.88 | 19-DEC-10:09 | 23.33 | 10.05 |
Annual Sum or Average | 0.465930E+11 | 0.293400E+10 | ||||||||
Minimum of Months | 0.238078E+10 | 3811.78 | 18.00 | 11.71 | 0.206203E+09 | 347.88 | 16.67 | 10.05 | ||
Maximum of Months | 0.585592E+10 | 16766.25 | 31.67 | 19.51 | 0.283649E+09 | 347.91 | 23.33 | 16.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.643155E+10 | 20100.06 | 22-JAN-12:02 | 17.00 | 11.99 | 0.397511E+09 | 549.87 | 18-JAN-14:00 | 17.00 | 11.99 |
February | 0.434370E+10 | 19173.39 | 20-FEB-13:42 | 17.00 | 10.89 | 0.344667E+09 | 549.54 | 01-FEB-14:09 | 17.00 | 10.89 |
March | 0.414858E+10 | 9920.82 | 23-MAR-13:30 | 22.50 | 17.06 | 0.396785E+09 | 549.52 | 01-MAR-14:09 | 22.50 | 17.06 |
April | 0.455713E+10 | 9476.89 | 26-APR-12:00 | 26.00 | 17.28 | 0.371274E+09 | 549.54 | 13-APR-09:00 | 26.00 | 17.28 |
May | 0.392620E+10 | 5920.86 | 04-MAY-12:30 | 23.50 | 16.62 | 0.389209E+09 | 549.52 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.429663E+10 | 5147.96 | 30-JUN-12:20 | 23.67 | 18.03 | 0.400304E+09 | 549.49 | 20-JUN-13:20 | 23.67 | 18.03 |
July | 0.533546E+10 | 10611.88 | 31-JUL-12:00 | 28.00 | 21.19 | 0.386872E+09 | 549.49 | 07-JUL-13:20 | 28.00 | 21.19 |
August | 0.683291E+10 | 11021.80 | 18-AUG-12:00 | 28.00 | 21.20 | 0.439078E+09 | 549.50 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.696576E+10 | 17903.76 | 04-SEP-13:22 | 21.50 | 16.68 | 0.388745E+09 | 655.60 | 29-SEP-12:09 | 36.00 | 18.21 |
October | 0.850751E+10 | 21818.38 | 15-OCT-11:31 | 32.00 | 16.72 | 0.409100E+09 | 678.68 | 16-OCT-12:09 | 35.68 | 17.48 |
November | 0.652517E+10 | 19928.98 | 23-NOV-13:22 | 20.00 | 7.61 | 0.397762E+09 | 549.94 | 29-NOV-14:09 | 21.33 | 10.32 |
December | 0.707254E+10 | 20200.26 | 25-DEC-12:42 | 22.17 | 9.14 | 0.384291E+09 | 549.78 | 07-DEC-14:50 | 22.17 | 9.14 |
Annual Sum or Average | 0.689432E+11 | 0.470560E+10 | ||||||||
Minimum of Months | 0.392620E+10 | 5147.96 | 17.00 | 7.61 | 0.344667E+09 | 549.49 | 17.00 | 9.14 | ||
Maximum of Months | 0.850751E+10 | 21818.38 | 32.00 | 21.20 | 0.439078E+09 | 678.68 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273879E+10 | 4987.82 | 18-JAN-15:00 | 23.00 | 14.79 | 0.221149E+09 | 347.86 | 18-JAN-14:20 | 23.00 | 14.79 |
February | 0.252514E+10 | 5398.61 | 22-FEB-16:20 | 15.33 | 12.12 | 0.199428E+09 | 347.86 | 01-FEB-14:20 | 15.33 | 12.12 |
March | 0.309067E+10 | 7101.71 | 23-MAR-16:00 | 21.00 | 17.19 | 0.237098E+09 | 347.86 | 10-MAR-14:00 | 21.00 | 17.19 |
April | 0.412368E+10 | 7967.29 | 26-APR-16:00 | 22.00 | 16.41 | 0.226029E+09 | 347.87 | 13-APR-13:00 | 22.00 | 16.41 |
May | 0.433287E+10 | 16620.79 | 28-MAY-16:32 | 19.33 | 14.37 | 0.247039E+09 | 347.87 | 03-MAY-13:00 | 19.33 | 14.37 |
June | 0.500461E+10 | 9161.36 | 25-JUN-16:42 | 21.00 | 16.52 | 0.254988E+09 | 347.86 | 29-JUN-13:30 | 23.50 | 18.87 |
July | 0.573358E+10 | 17861.71 | 23-JUL-16:51 | 24.00 | 18.72 | 0.245427E+09 | 347.85 | 14-JUL-13:30 | 24.00 | 18.72 |
August | 0.596909E+10 | 10633.62 | 19-AUG-17:07 | 23.83 | 17.59 | 0.274039E+09 | 347.85 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.483256E+10 | 16983.20 | 04-SEP-16:02 | 19.67 | 15.96 | 0.237055E+09 | 347.85 | 05-SEP-13:20 | 21.67 | 17.97 |
October | 0.456299E+10 | 19175.73 | 15-OCT-15:31 | 30.33 | 15.09 | 0.242859E+09 | 347.86 | 26-OCT-13:20 | 25.33 | 12.90 |
November | 0.328731E+10 | 5494.03 | 07-NOV-15:30 | 19.00 | 14.51 | 0.227111E+09 | 347.91 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.292336E+10 | 5541.04 | 18-DEC-15:30 | 22.00 | 8.99 | 0.213242E+09 | 347.92 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.491247E+11 | 0.282546E+10 | ||||||||
Minimum of Months | 0.252514E+10 | 4987.82 | 15.33 | 8.99 | 0.199428E+09 | 347.85 | 15.33 | 12.12 | ||
Maximum of Months | 0.596909E+10 | 19175.73 | 30.33 | 18.72 | 0.274039E+09 | 347.92 | 25.33 | 18.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234748E+10 | 3369.84 | 24-JAN-15:00 | 25.00 | 15.45 | 0.358767E+09 | 549.51 | 18-JAN-14:20 | 25.00 | 15.45 |
February | 0.222835E+10 | 3007.66 | 03-FEB-15:00 | 23.00 | 8.84 | 0.331219E+09 | 549.54 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.266560E+10 | 3523.30 | 23-MAR-14:30 | 22.50 | 17.35 | 0.396199E+09 | 549.50 | 10-MAR-14:20 | 22.50 | 17.35 |
April | 0.331025E+10 | 5038.05 | 26-APR-14:00 | 26.00 | 16.74 | 0.378194E+09 | 549.52 | 13-APR-09:00 | 26.00 | 16.74 |
May | 0.378456E+10 | 5439.79 | 04-MAY-14:10 | 22.83 | 16.63 | 0.417558E+09 | 549.51 | 03-MAY-13:00 | 22.83 | 16.63 |
June | 0.454506E+10 | 5163.19 | 29-JUN-16:00 | 23.00 | 18.43 | 0.426776E+09 | 549.50 | 29-JUN-13:30 | 23.00 | 18.43 |
July | 0.506086E+10 | 5891.96 | 31-JUL-13:10 | 27.83 | 21.13 | 0.399862E+09 | 549.50 | 13-JUL-09:20 | 27.83 | 21.13 |
August | 0.514033E+10 | 5908.36 | 17-AUG-14:00 | 28.00 | 21.19 | 0.447012E+09 | 549.50 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.404043E+10 | 7361.95 | 29-SEP-13:10 | 35.67 | 18.16 | 0.390254E+09 | 549.50 | 22-SEP-13:20 | 35.67 | 18.16 |
October | 0.405671E+10 | 7351.01 | 16-OCT-12:05 | 35.68 | 17.48 | 0.401866E+09 | 549.51 | 18-OCT-13:09 | 22.83 | 18.37 |
November | 0.268033E+10 | 3062.50 | 19-NOV-13:31 | 25.67 | 15.08 | 0.372357E+09 | 549.51 | 28-NOV-14:20 | 24.33 | 10.97 |
December | 0.245467E+10 | 3320.55 | 05-DEC-15:00 | 25.00 | 13.22 | 0.348625E+09 | 549.50 | 05-DEC-14:20 | 25.00 | 13.22 |
Annual Sum or Average | 0.423146E+11 | 0.466869E+10 | ||||||||
Minimum of Months | 0.222835E+10 | 3007.66 | 22.50 | 8.84 | 0.331219E+09 | 549.50 | 22.50 | 8.84 | ||
Maximum of Months | 0.514033E+10 | 7361.95 | 35.68 | 21.19 | 0.447012E+09 | 549.54 | 35.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257789E+10 | 5269.33 | 20-JAN-09:30 | 18.00 | 14.38 | 0.171071E+09 | 356.47 | 05-JAN-11:09 | 18.00 | 14.38 |
February | 0.234608E+10 | 4964.59 | 01-FEB-10:00 | 24.00 | 12.54 | 0.155570E+09 | 356.48 | 02-FEB-13:09 | 18.83 | 13.32 |
March | 0.299074E+10 | 7667.56 | 23-MAR-10:05 | 22.00 | 16.49 | 0.186032E+09 | 356.47 | 23-MAR-10:09 | 22.00 | 16.49 |
April | 0.426121E+10 | 9920.23 | 30-APR-08:53 | 22.00 | 15.39 | 0.177980E+09 | 356.50 | 13-APR-10:09 | 22.00 | 15.39 |
May | 0.427236E+10 | 7694.73 | 04-MAY-10:05 | 22.00 | 16.25 | 0.191589E+09 | 356.48 | 04-MAY-10:09 | 22.00 | 16.25 |
June | 0.498282E+10 | 18136.47 | 25-JUN-09:02 | 22.17 | 16.55 | 0.194946E+09 | 356.46 | 02-JUN-10:09 | 22.17 | 16.55 |
July | 0.591479E+10 | 18458.71 | 04-JUL-08:12 | 20.00 | 15.16 | 0.186195E+09 | 356.47 | 28-JUL-14:09 | 22.83 | 19.51 |
August | 0.623964E+10 | 18468.82 | 13-AUG-09:12 | 24.00 | 19.51 | 0.207800E+09 | 356.46 | 21-AUG-10:09 | 22.17 | 17.39 |
September | 0.457363E+10 | 12524.27 | 03-SEP-09:42 | 21.67 | 15.72 | 0.179163E+09 | 356.46 | 12-SEP-10:09 | 22.83 | 17.20 |
October | 0.441455E+10 | 18950.52 | 15-OCT-08:11 | 30.33 | 14.69 | 0.184682E+09 | 356.49 | 27-OCT-10:09 | 22.00 | 12.16 |
November | 0.287850E+10 | 7486.27 | 19-NOV-08:52 | 24.00 | 12.56 | 0.172964E+09 | 356.48 | 30-NOV-15:09 | 20.50 | 12.92 |
December | 0.265301E+10 | 5067.81 | 05-DEC-09:50 | 25.67 | 12.88 | 0.165258E+09 | 356.49 | 20-DEC-15:09 | 18.67 | 12.31 |
Annual Sum or Average | 0.481052E+11 | 0.217325E+10 | ||||||||
Minimum of Months | 0.234608E+10 | 4964.59 | 18.00 | 12.54 | 0.155570E+09 | 356.46 | 18.00 | 12.16 | ||
Maximum of Months | 0.623964E+10 | 18950.52 | 30.33 | 19.51 | 0.207800E+09 | 356.50 | 22.83 | 19.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.781380E+10 | 20617.83 | 08-JAN-13:02 | 17.00 | 10.26 | 0.399977E+09 | 549.99 | 18-JAN-14:30 | 23.80 | 14.82 |
February | 0.561955E+10 | 19523.54 | 19-FEB-14:12 | 16.00 | 13.03 | 0.352675E+09 | 549.89 | 02-FEB-14:30 | 16.00 | 13.03 |
March | 0.572598E+10 | 20047.13 | 19-MAR-12:02 | 20.83 | 15.83 | 0.411441E+09 | 549.53 | 01-MAR-14:09 | 20.83 | 15.83 |
April | 0.600328E+10 | 11562.72 | 30-APR-13:32 | 24.00 | 16.71 | 0.379415E+09 | 549.54 | 13-APR-09:00 | 24.00 | 16.71 |
May | 0.509950E+10 | 7381.61 | 04-MAY-12:30 | 23.50 | 16.62 | 0.405815E+09 | 549.52 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.550658E+10 | 6600.13 | 30-JUN-12:30 | 23.50 | 17.99 | 0.414748E+09 | 549.51 | 29-JUN-13:30 | 23.50 | 17.99 |
July | 0.635194E+10 | 11204.63 | 30-JUL-13:12 | 24.00 | 19.70 | 0.392328E+09 | 549.50 | 14-JUL-13:30 | 24.00 | 19.70 |
August | 0.794137E+10 | 10871.84 | 31-AUG-12:30 | 22.50 | 18.82 | 0.442163E+09 | 549.50 | 30-AUG-13:20 | 22.50 | 18.82 |
September | 0.800619E+10 | 19890.01 | 04-SEP-13:22 | 21.50 | 16.68 | 0.389744E+09 | 566.08 | 29-SEP-13:09 | 35.67 | 18.16 |
October | 0.920442E+10 | 24063.16 | 15-OCT-11:31 | 32.00 | 16.72 | 0.407450E+09 | 574.72 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.779010E+10 | 22689.15 | 19-NOV-10:51 | 26.00 | 15.07 | 0.399833E+09 | 550.06 | 30-NOV-14:50 | 21.33 | 12.71 |
December | 0.823126E+10 | 21016.49 | 24-DEC-12:02 | 16.17 | 10.43 | 0.386592E+09 | 550.12 | 05-DEC-14:30 | 16.17 | 10.43 |
Annual Sum or Average | 0.832940E+11 | 0.478218E+10 | ||||||||
Minimum of Months | 0.509950E+10 | 6600.13 | 16.00 | 10.26 | 0.352675E+09 | 549.50 | 16.00 | 10.43 | ||
Maximum of Months | 0.920442E+10 | 24063.16 | 32.00 | 19.70 | 0.442163E+09 | 574.72 | 35.67 | 19.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300151E+10 | 6337.44 | 18-JAN-15:00 | 23.00 | 14.79 | 0.221383E+09 | 347.86 | 04-JAN-14:00 | 23.00 | 14.79 |
February | 0.284288E+10 | 6798.03 | 22-FEB-15:40 | 16.60 | 12.17 | 0.200764E+09 | 347.88 | 01-FEB-14:09 | 16.60 | 12.17 |
March | 0.354147E+10 | 10688.82 | 19-MAR-16:42 | 17.17 | 14.59 | 0.238724E+09 | 347.86 | 10-MAR-14:00 | 17.17 | 14.59 |
April | 0.472510E+10 | 9603.56 | 26-APR-15:50 | 22.17 | 16.38 | 0.224639E+09 | 347.87 | 13-APR-13:00 | 22.17 | 16.38 |
May | 0.487573E+10 | 18794.28 | 28-MAY-16:22 | 19.50 | 14.42 | 0.245313E+09 | 347.87 | 03-MAY-13:00 | 19.50 | 14.42 |
June | 0.567894E+10 | 18843.14 | 18-JUN-16:42 | 21.17 | 17.23 | 0.253084E+09 | 347.86 | 29-JUN-13:30 | 23.50 | 18.87 |
July | 0.629727E+10 | 19972.32 | 04-JUL-16:51 | 19.00 | 15.26 | 0.241168E+09 | 347.85 | 14-JUL-13:30 | 23.50 | 18.59 |
August | 0.657384E+10 | 15789.59 | 20-AUG-16:02 | 21.80 | 17.34 | 0.269515E+09 | 347.85 | 30-AUG-13:20 | 23.67 | 18.23 |
September | 0.529744E+10 | 19025.83 | 04-SEP-16:02 | 19.67 | 15.96 | 0.232821E+09 | 347.85 | 05-SEP-13:20 | 21.67 | 17.97 |
October | 0.492898E+10 | 21361.14 | 15-OCT-15:31 | 30.33 | 15.09 | 0.239030E+09 | 347.86 | 31-OCT-13:20 | 26.67 | 16.70 |
November | 0.350000E+10 | 6474.35 | 07-NOV-15:30 | 19.00 | 14.51 | 0.225467E+09 | 347.92 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.314961E+10 | 6560.63 | 18-DEC-15:30 | 22.00 | 8.99 | 0.213135E+09 | 347.93 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.544128E+11 | 0.280504E+10 | ||||||||
Minimum of Months | 0.284288E+10 | 6337.44 | 16.60 | 8.99 | 0.200764E+09 | 347.85 | 16.60 | 12.17 | ||
Maximum of Months | 0.657384E+10 | 21361.14 | 30.33 | 17.34 | 0.269515E+09 | 347.93 | 26.67 | 18.87 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149855E+10 | 12611.94 | 09-JAN-06:16 | 2.33 |
February | 0.101375E+10 | 8411.97 | 06-FEB-07:03 | 9.50 |
March | 0.116204E+10 | 9971.71 | 30-MAR-05:23 | 5.10 |
April | 0.453549E+09 | 7385.75 | 01-APR-06:03 | 7.67 |
May | 0.317417E+09 | 6283.39 | 19-MAY-05:03 | 8.67 |
June | 0.115728E+09 | 6495.57 | 14-JUN-05:03 | 13.17 |
July | 55981216.90 | 5397.34 | 04-JUL-06:30 | 17.00 |
August | 66555714.29 | 5593.31 | 06-AUG-06:40 | 18.33 |
September | 0.166858E+09 | 5735.07 | 20-SEP-05:03 | 12.00 |
October | 0.445318E+09 | 6374.83 | 15-OCT-07:10 | 24.83 |
November | 0.921259E+09 | 7557.45 | 24-NOV-07:03 | 8.75 |
December | 0.136825E+10 | 9600.92 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 0.758526E+10 | |||
Minimum of Months | 55981216.90 | 5397.34 | 2.33 | |
Maximum of Months | 0.149855E+10 | 12611.94 | 24.83 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.556485E+09 | 7884.41 | 08-JAN-13:02 | 17.00 |
February | 0.266398E+09 | 5968.77 | 19-FEB-14:12 | 16.00 |
March | 0.315033E+09 | 5321.74 | 19-MAR-13:22 | 19.50 |
April | 70572714.08 | 5324.65 | 02-APR-11:47 | 23.83 |
May | 36403165.84 | 4757.92 | 14-MAY-13:58 | 19.00 |
June | 13408052.57 | 3784.71 | 18-JUN-09:32 | 22.00 |
July | 25798207.83 | 4119.03 | 09-JUL-16:02 | 20.67 |
August | 19258834.61 | 4050.06 | 13-AUG-08:31 | 23.33 |
September | 22187833.48 | 3977.91 | 17-SEP-11:12 | 19.67 |
October | 62878239.70 | 8063.94 | 15-OCT-09:31 | 31.67 |
November | 0.209311E+09 | 7138.99 | 19-NOV-10:12 | 26.00 |
December | 0.377735E+09 | 8272.67 | 25-DEC-13:32 | 22.00 |
Annual Sum or Average | 0.197547E+10 | |||
Minimum of Months | 13408052.57 | 3784.71 | 16.00 | |
Maximum of Months | 0.556485E+09 | 8272.67 | 31.67 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120984E+09 | 5133.74 | 08-JAN-13:02 | 17.00 |
February | 28573915.40 | 5110.55 | 19-FEB-10:27 | 15.50 |
March | 37443378.74 | 4218.91 | 12-MAR-10:58 | 21.00 |
April | 21317588.16 | 4908.67 | 02-APR-14:19 | 22.33 |
May | 18077633.02 | 3996.84 | 14-MAY-14:30 | 18.50 |
June | 10298776.89 | 3679.39 | 18-JUN-13:40 | 23.00 |
July | 22608405.73 | 3331.92 | 16-JUL-13:30 | 22.05 |
August | 20023381.07 | 3706.90 | 27-AUG-13:38 | 22.67 |
September | 15411383.70 | 4164.34 | 17-SEP-11:16 | 19.67 |
October | 33479499.58 | 5848.79 | 15-OCT-09:31 | 31.67 |
November | 32241061.31 | 5118.91 | 19-NOV-08:30 | 21.50 |
December | 57005282.33 | 5909.16 | 25-DEC-13:21 | 22.00 |
Annual Sum or Average | 0.417465E+09 | |||
Minimum of Months | 10298776.89 | 3331.92 | 15.50 | |
Maximum of Months | 0.120984E+09 | 5909.16 | 31.67 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2334187.36 | 10472.19 | 02-JAN-07:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 2334187.36 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 2334187.36 | 10472.19 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108685E+09 | 20451.63 | 02-JAN-06:11 | 11.00 |
February | 23892916.69 | 17822.17 | 06-FEB-07:03 | 9.50 |
March | 35244747.17 | 17940.24 | 30-MAR-06:02 | 5.58 |
April | 2552508.89 | 17016.73 | 01-APR-06:03 | 7.67 |
May | 283532.29 | 1890.22 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 11056919.75 | 17811.81 | 27-NOV-07:03 | 14.67 |
December | 32553352.58 | 17860.92 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 0.214269E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 0.108685E+09 | 20451.63 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484842E+09 | 9675.63 | 09-JAN-06:11 | 2.33 |
February | 0.258932E+09 | 8625.06 | 06-FEB-06:11 | 9.00 |
March | 0.343175E+09 | 9061.36 | 30-MAR-05:11 | 5.03 |
April | 57529120.24 | 8306.13 | 01-APR-05:11 | 7.67 |
May | 17211053.27 | 7317.83 | 15-MAY-05:12 | 9.00 |
June | 1317161.69 | 4191.29 | 01-JUN-06:03 | 13.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 3364340.74 | 6920.44 | 20-SEP-06:03 | 12.17 |
October | 35063512.63 | 7631.46 | 30-OCT-05:12 | 10.67 |
November | 0.153538E+09 | 8548.39 | 27-NOV-06:11 | 11.33 |
December | 0.337312E+09 | 8772.93 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.169228E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.484842E+09 | 9675.63 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191982E+09 | 8073.33 | 09-JAN-06:11 | 2.33 |
February | 0.125185E+09 | 7011.88 | 06-FEB-06:11 | 9.00 |
March | 0.142765E+09 | 7588.32 | 30-MAR-05:11 | 5.03 |
April | 24375034.67 | 6770.05 | 01-APR-05:11 | 7.67 |
May | 8091735.56 | 4770.17 | 12-MAY-06:03 | 12.17 |
June | 2285575.21 | 3126.55 | 12-JUN-06:03 | 14.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 4707010.48 | 4250.31 | 20-SEP-06:03 | 12.17 |
October | 17864121.59 | 6033.55 | 30-OCT-05:12 | 10.67 |
November | 49626295.74 | 6912.20 | 24-NOV-06:11 | 8.83 |
December | 0.122165E+09 | 7279.43 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.689046E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.191982E+09 | 8073.33 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232807E+09 | 10816.28 | 09-JAN-06:11 | 2.33 |
February | 0.169724E+09 | 9521.89 | 06-FEB-06:11 | 9.00 |
March | 0.263908E+09 | 10495.42 | 30-MAR-05:11 | 5.03 |
April | 61126016.91 | 9472.89 | 01-APR-05:11 | 7.67 |
May | 38339456.85 | 8638.26 | 15-MAY-05:12 | 9.00 |
June | 5734505.85 | 5111.62 | 13-JUN-06:03 | 13.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 4250856.81 | 7348.57 | 20-SEP-06:03 | 12.17 |
October | 21983197.97 | 7748.10 | 28-OCT-06:03 | 11.17 |
November | 65963378.65 | 9353.41 | 24-NOV-06:11 | 8.83 |
December | 0.139875E+09 | 10098.80 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.100371E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.263908E+09 | 10816.28 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290536E+09 | 8433.80 | 09-JAN-06:11 | 2.33 |
February | 0.169832E+09 | 7234.20 | 06-FEB-06:11 | 9.00 |
March | 0.217244E+09 | 7823.74 | 30-MAR-05:11 | 5.03 |
April | 44241881.80 | 7075.75 | 01-APR-05:11 | 7.67 |
May | 25158003.88 | 5850.24 | 13-MAY-05:12 | 10.67 |
June | 5647101.81 | 3215.80 | 01-JUN-06:03 | 13.17 |
July | 1784.26 | 5.95 | 06-JUL-06:05 | 16.00 |
August | 500485.14 | 1646.50 | 31-AUG-06:03 | 16.33 |
September | 6679740.94 | 4697.46 | 20-SEP-06:03 | 12.17 |
October | 28974952.08 | 6176.58 | 30-OCT-05:12 | 10.67 |
November | 0.103245E+09 | 7111.42 | 27-NOV-06:11 | 11.33 |
December | 0.210185E+09 | 7595.90 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.110225E+10 | |||
Minimum of Months | 1784.26 | 5.95 | 2.33 | |
Maximum of Months | 0.290536E+09 | 8433.80 | 16.33 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129488E+09 | 6336.03 | 09-JAN-06:11 | 2.33 |
February | 54151924.53 | 5779.94 | 06-FEB-06:11 | 9.00 |
March | 93434809.29 | 6123.88 | 30-MAR-05:11 | 5.03 |
April | 8625464.69 | 5739.52 | 01-APR-05:11 | 7.67 |
May | 133645.80 | 890.97 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 872083.24 | 3803.49 | 30-OCT-06:03 | 10.50 |
November | 11417902.23 | 5388.29 | 27-NOV-07:03 | 14.67 |
December | 46479010.26 | 5840.13 | 26-DEC-06:11 | 7.00 |
Annual Sum or Average | 0.344602E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.129488E+09 | 6336.03 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36849055.52 | 5420.72 | 03-JAN-06:11 | 4.33 |
February | 26616477.14 | 4721.83 | 06-FEB-06:11 | 9.00 |
March | 37797273.08 | 5413.57 | 30-MAR-05:11 | 5.03 |
April | 2956372.61 | 4814.17 | 01-APR-05:11 | 7.67 |
May | 653668.42 | 1867.65 | 12-MAY-06:03 | 12.17 |
June | 3830.55 | 19.15 | 12-JUN-06:03 | 14.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 7623.26 | 38.12 | 19-SEP-06:03 | 14.17 |
October | 1349338.69 | 2438.58 | 30-OCT-06:03 | 10.50 |
November | 2510185.08 | 3687.48 | 03-NOV-06:03 | 11.00 |
December | 15504556.78 | 5033.22 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.124248E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 37797273.08 | 5420.72 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393922E+09 | 7794.93 | 03-JAN-07:10 | 3.67 |
February | 0.397759E+09 | 7019.95 | 27-FEB-08:00 | 9.00 |
March | 0.764309E+09 | 7965.51 | 30-MAR-06:10 | 5.58 |
April | 0.311062E+09 | 6428.19 | 19-APR-06:03 | 10.33 |
May | 0.272344E+09 | 6415.85 | 15-MAY-06:03 | 11.33 |
June | 85595279.93 | 6018.97 | 13-JUN-06:03 | 13.67 |
July | 3148627.92 | 1961.53 | 17-JUL-06:10 | 15.12 |
August | 6827741.72 | 2728.50 | 28-AUG-06:10 | 14.00 |
September | 28429952.15 | 4966.78 | 20-SEP-06:03 | 12.17 |
October | 84848094.28 | 6283.08 | 12-OCT-06:03 | 9.67 |
November | 0.180482E+09 | 6242.71 | 03-NOV-06:03 | 11.00 |
December | 0.326455E+09 | 6958.57 | 13-DEC-07:10 | 7.17 |
Annual Sum or Average | 0.285518E+10 | |||
Minimum of Months | 3148627.92 | 1961.53 | 3.67 | |
Maximum of Months | 0.764309E+09 | 7965.51 | 15.12 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57724960.49 | 5413.16 | 03-JAN-06:11 | 4.33 |
February | 31679994.69 | 4295.44 | 25-FEB-07:03 | 12.00 |
March | 49766497.89 | 5257.84 | 30-MAR-05:11 | 5.03 |
April | 7024649.06 | 4844.03 | 01-APR-05:11 | 7.67 |
May | 2049478.66 | 4154.64 | 13-MAY-06:03 | 12.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 1928751.56 | 3290.98 | 25-OCT-06:03 | 11.33 |
November | 10880885.83 | 4200.95 | 24-NOV-07:03 | 8.75 |
December | 25666879.88 | 5008.19 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.186722E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 57724960.49 | 5413.16 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146299E+09 | 6860.53 | 09-JAN-06:11 | 2.33 |
February | 52196584.19 | 6130.25 | 06-FEB-06:11 | 9.00 |
March | 90030336.81 | 6585.20 | 30-MAR-05:11 | 5.03 |
April | 8676773.09 | 6072.25 | 01-APR-05:11 | 7.67 |
May | 263433.42 | 1756.22 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 3582977.09 | 5401.72 | 30-OCT-06:03 | 10.50 |
November | 19689401.89 | 6087.06 | 27-NOV-06:11 | 11.33 |
December | 60862498.62 | 6344.04 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.381601E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.146299E+09 | 6860.53 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63591667.77 | 6242.92 | 09-JAN-06:11 | 2.33 |
February | 32505510.36 | 5333.62 | 06-FEB-06:11 | 9.00 |
March | 44086846.59 | 6024.71 | 30-MAR-05:11 | 5.03 |
April | 6509379.67 | 5311.79 | 01-APR-05:11 | 7.67 |
May | 1632791.97 | 3554.78 | 12-MAY-06:03 | 12.17 |
June | 175393.34 | 545.99 | 01-JUN-06:03 | 13.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 342638.57 | 1002.15 | 19-SEP-06:03 | 14.17 |
October | 4722088.34 | 4436.82 | 28-OCT-06:03 | 11.17 |
November | 9503633.91 | 5223.09 | 27-NOV-06:11 | 11.33 |
December | 29730067.96 | 5703.28 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.192800E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 63591667.77 | 6242.92 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59749605.10 | 7935.98 | 03-JAN-06:11 | 4.33 |
February | 35307394.36 | 6464.62 | 25-FEB-07:03 | 12.00 |
March | 74954894.94 | 7917.39 | 30-MAR-05:11 | 5.03 |
April | 12959683.22 | 7136.07 | 01-APR-05:11 | 7.67 |
May | 5318787.58 | 6343.64 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 4207306.59 | 6097.86 | 12-OCT-06:03 | 9.67 |
November | 7759564.63 | 6335.95 | 03-NOV-06:03 | 11.00 |
December | 23643469.99 | 7548.17 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.223901E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 74954894.94 | 7935.98 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 96089835.50 | 6181.76 | 09-JAN-06:11 | 2.33 |
February | 43796886.69 | 5218.61 | 06-FEB-06:11 | 9.00 |
March | 68140653.22 | 5902.36 | 30-MAR-05:11 | 5.03 |
April | 13463446.18 | 5320.97 | 01-APR-05:11 | 7.67 |
May | 6001952.20 | 4370.07 | 15-MAY-06:03 | 11.33 |
June | 492327.04 | 1323.21 | 01-JUN-06:03 | 13.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 392932.33 | 2380.46 | 20-SEP-06:03 | 12.17 |
October | 6059451.83 | 4386.80 | 28-OCT-06:03 | 11.17 |
November | 20295218.90 | 5118.37 | 27-NOV-06:11 | 11.33 |
December | 48915931.65 | 5682.32 | 13-DEC-06:11 | 6.33 |
Annual Sum or Average | 0.303649E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 96089835.50 | 6181.76 | 18.07 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1245803.92 | 0.256004E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106282.69 | 0.301750E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 202913.96 | 0.339534E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1667365.91 | 0.203074E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252840E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34834.59 | 0.138099E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2999285.12 | 97464897.30 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3667193.85 | 0.117108E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4148660.03 | 0.110631E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16957484.26 | 0.167441E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2493542.34 | 0.246742E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2607451.48 | 0.258599E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36130818.15 | 0.248929E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97464897.30 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16957484.26 | 0.339534E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 790593.72 | 0.175007E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43488.05 | 0.207041E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62650.88 | 0.231872E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 330052.30 | 0.142032E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172616E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21727.12 | 91758498.73 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1605983.40 | 67275593.58 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1919052.55 | 80670860.96 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2774112.58 | 76335219.34 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10123842.36 | 0.113728E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1114376.34 | 0.168626E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1088026.58 | 0.176704E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19873905.89 | 0.170366E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67275593.58 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10123842.36 | 0.231872E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 334235.21 | 0.295675E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55367.11 | 0.340541E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361357E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 423382.47 | 0.218607E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252445E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53639.53 | 0.131426E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2972756.78 | 94130941.74 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2728956.43 | 0.120643E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4089736.32 | 0.128982E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13205529.37 | 0.195987E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117813.65 | 0.286183E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 221951.88 | 0.305319E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24203368.75 | 0.273130E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94130941.74 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13205529.37 | 0.361357E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 801719.26 | 0.175764E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 169632.54 | 0.208268E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 199628.88 | 0.230563E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1549494.05 | 0.144702E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3644.00 | 0.176072E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 432427.62 | 92907130.22 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3185188.24 | 68698521.22 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4038156.90 | 83027249.91 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3244202.93 | 79894349.33 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11895281.52 | 0.116532E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1745681.05 | 0.171846E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1878814.64 | 0.178944E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29143871.63 | 0.172722E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3644.00 | 68698521.22 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11895281.52 | 0.230563E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 556357.65 | 0.153215E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51016.52 | 0.175631E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109965.55 | 0.192743E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 938563.98 | 0.112118E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 | 0.140132E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19577.28 | 75482543.10 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1659335.38 | 53482097.71 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1960782.01 | 65879393.88 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2192019.42 | 63179300.15 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8907013.19 | 0.100931E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1235998.34 | 0.147417E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1013576.77 | 0.154806E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18644237.55 | 0.143502E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 | 53482097.71 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8907013.19 | 0.192743E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398193.82 | 0.106221E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30602.65 | 0.121119E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40880.40 | 0.132767E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206729.13 | 80308273.30 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 96260585.01 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15887.01 | 50230142.33 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 898625.59 | 37923779.21 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1060073.12 | 47081619.29 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1485873.63 | 43807862.55 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5492172.78 | 69119582.25 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617685.81 | 0.101507E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522810.27 | 0.107087E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10769553.63 | 0.993433E+09 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 37923779.21 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5492172.78 | 0.132767E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5105224.62 | 0.216387E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2724450.36 | 0.198475E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.20 | 0.250431E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8409623.26 | 0.150674E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1019.52 | 0.142241E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1463446.12 | 0.959616E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54020616.94 | 0.575235E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54463928.52 | 0.685496E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83514601.87 | 0.968603E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141811E+09 | 0.977708E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 348105.38 | 0.193782E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7353251.73 | 0.194852E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359215E+09 | 0.176351E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.20 | 0.575235E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141811E+09 | 0.250431E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 344690.59 | 0.106004E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78876.45 | 0.122132E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87268.78 | 0.132514E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 656359.17 | 82610858.64 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4354.55 | 99758203.10 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116163.52 | 52358848.98 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1497427.19 | 39957402.35 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1719111.59 | 49214589.25 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1598076.82 | 47066027.52 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6035410.87 | 71215117.65 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 826060.12 | 0.103363E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 776566.47 | 0.108019E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13740366.13 | 0.101421E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4354.55 | 39957402.35 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6035410.87 | 0.132514E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 690400.32 | 0.238404E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52372.10 | 0.278191E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 128825.36 | 0.305847E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261943.65 | 0.180373E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222974E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28520.06 | 0.121080E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2424307.66 | 85617322.75 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2835901.74 | 0.105179E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3412158.95 | 0.100185E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13368113.34 | 0.156828E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1721617.56 | 0.229422E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1306756.20 | 0.242249E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27230916.94 | 0.226635E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85617322.75 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13368113.34 | 0.305847E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398416.67 | 0.163006E+09 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22917.47 | 0.190126E+09 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29185.13 | 0.208628E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 292658.65 | 0.124711E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151041E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11642.84 | 79790018.24 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1311824.91 | 57827851.45 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1654229.56 | 70874177.57 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2236929.30 | 67689000.10 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8420640.24 | 0.105097E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 783028.31 | 0.156256E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 594234.88 | 0.165503E+09 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15755707.95 | 0.154055E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57827851.45 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8420640.24 | 0.208628E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238188.10 | 0.269620E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47163.02 | 0.308505E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322543E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 298116.85 | 0.192289E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220835E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29492.28 | 0.114596E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2475258.28 | 82307989.06 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2184089.88 | 0.107461E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3389887.94 | 0.114186E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10837316.34 | 0.178828E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100769.75 | 0.259611E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189936.08 | 0.279199E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19790218.50 | 0.244998E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82307989.06 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10837316.34 | 0.322543E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 511460.81 | 0.161409E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113340.21 | 0.189024E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137117.80 | 0.205264E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1265755.08 | 0.126902E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5782.32 | 0.153552E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297177.54 | 80841636.32 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2601090.71 | 60267537.46 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3151629.03 | 73736432.43 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2599859.49 | 71072256.56 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9640639.10 | 0.106938E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1340964.34 | 0.156544E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1312801.73 | 0.164692E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22977618.16 | 0.155024E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5782.32 | 60267537.46 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9640639.10 | 0.205264E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404718.01 | 0.381856E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51818.37 | 0.443329E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8731.65 | 0.470379E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558534.74 | 0.278059E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330189E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7519.15 | 0.176706E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1949076.22 | 0.130631E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1816816.75 | 0.165985E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3818164.39 | 0.160218E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14368542.82 | 0.254465E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1008228.09 | 0.368918E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268502.43 | 0.395293E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24260652.63 | 0.355603E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130631E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14368542.82 | 0.470379E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1107023.95 | 0.452408E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91814.55 | 0.527190E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81430.66 | 0.570088E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1407305.81 | 0.339545E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404345E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12829.22 | 0.218735E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2783222.26 | 0.161299E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2746301.74 | 0.204265E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5054598.25 | 0.193414E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19581721.23 | 0.304582E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1910996.41 | 0.441718E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 975334.79 | 0.469465E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35752578.87 | 0.428706E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161299E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19581721.23 | 0.570088E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 882093.15 | 0.409359E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1431.93 | 0.494467E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557305E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2024.79 | 0.371059E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448909E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260348E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403744.39 | 0.206820E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281038.20 | 0.220260E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4593521.79 | 0.217254E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15785932.12 | 0.279489E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642747.28 | 0.399166E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285416.76 | 0.408286E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22877950.41 | 0.427272E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206820E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15785932.12 | 0.557305E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.75 | 15-JAN-09:55 | 577.05 | 06-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 01-FEB-12:00 | 552.04 | 08-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 12-MAR-10:00 | 741.07 | 28-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 | 30-APR-10:57 | 413.98 | 16-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 463.49 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 29-JUN-11:00 | 295.03 | 04-JUN-17:57 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.20 | 23-JUL-11:00 | 262.28 | 09-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.95 | 06-AUG-13:00 | 208.92 | 26-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.88 | 29-SEP-14:00 | 246.06 | 24-SEP-15:30 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.03 | 15-OCT-08:51 | 411.35 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.17 | 19-NOV-13:00 | 511.55 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.94 | 25-DEC-11:52 | 533.62 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.92 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 381.03 | 741.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.71 | 15-JAN-15:00 | 383.69 | 06-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 01-FEB-12:00 | 366.57 | 08-FEB-02:00 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 | 11-MAR-14:00 | 493.02 | 28-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.91 | 30-APR-12:00 | 289.81 | 16-APR-12:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 311.79 | 29-MAY-13:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 29-JUN-11:00 | 208.96 | 04-JUN-13:58 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.74 | 31-JUL-13:00 | 177.76 | 04-JUL-13:07 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.49 | 06-AUG-13:20 | 147.52 | 20-AUG-08:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.25 | 29-SEP-14:00 | 205.55 | 03-SEP-07:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.88 | 15-OCT-13:10 | 275.14 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.78 | 19-NOV-13:00 | 362.92 | 23-NOV-07:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.53 | 25-DEC-12:00 | 351.74 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.52 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 227.88 | 493.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 | 15-JAN-09:55 | 634.72 | 29-JAN-13:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 | 01-FEB-12:00 | 714.37 | 20-FEB-14:50 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 741.89 | 28-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.36 | 30-APR-10:13 | 502.30 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 481.65 | 29-MAY-13:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 | 25-JUN-10:00 | 302.38 | 04-JUN-13:58 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.47 | 23-JUL-11:00 | 253.34 | 09-JUL-12:20 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 | 17-AUG-14:00 | 210.40 | 26-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.80 | 29-SEP-14:00 | 339.74 | 04-SEP-14:10 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.98 | 15-OCT-08:51 | 443.93 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 19-NOV-12:54 | 544.18 | 23-NOV-16:33 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 | 05-DEC-10:00 | 584.37 | 03-DEC-11:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.40 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 274.98 | 741.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.04 | 15-JAN-09:55 | 391.14 | 06-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 | 01-FEB-12:00 | 413.91 | 26-FEB-16:40 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 12-MAR-10:00 | 493.62 | 28-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.82 | 30-APR-11:20 | 404.52 | 16-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 03-MAY-12:00 | 410.54 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.97 | 25-JUN-10:40 | 288.16 | 03-JUN-17:08 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.09 | 23-JUL-11:00 | 291.29 | 09-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.18 | 06-AUG-11:20 | 190.39 | 26-AUG-17:10 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.25 | 29-SEP-14:00 | 278.35 | 03-SEP-16:10 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.60 | 15-OCT-08:51 | 282.49 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.29 | 19-NOV-11:40 | 364.06 | 23-NOV-16:25 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 25-DEC-11:52 | 357.81 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 | 190.39 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 278.60 | 493.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.31 | 15-JAN-14:20 | 342.81 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 | 01-FEB-12:00 | 327.79 | 08-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.18 | 11-MAR-14:00 | 395.86 | 28-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.34 | 30-APR-11:20 | 231.73 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:40 | 237.80 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 29-JUN-11:00 | 158.56 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.72 | 23-JUL-11:00 | 124.74 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.91 | 06-AUG-12:52 | 113.89 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.73 | 29-SEP-14:00 | 129.91 | 24-SEP-15:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.84 | 15-OCT-09:00 | 249.14 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.35 | 19-NOV-12:51 | 329.52 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 | 25-DEC-11:52 | 314.90 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 113.89 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 190.84 | 395.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.87 | 15-JAN-14:50 | 228.16 | 27-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 | 01-FEB-12:10 | 222.12 | 08-FEB-06:00 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 | 11-MAR-14:00 | 263.49 | 28-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 | 30-APR-11:20 | 156.07 | 21-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:50 | 152.84 | 27-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 29-JUN-11:00 | 110.91 | 04-JUN-13:42 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 | 31-JUL-13:00 | 94.01 | 04-JUL-13:23 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 | 06-AUG-13:20 | 77.06 | 21-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 29-SEP-14:00 | 121.46 | 03-SEP-07:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.00 | 15-OCT-13:00 | 173.14 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.88 | 19-NOV-13:10 | 236.35 | 23-NOV-07:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.96 | 25-DEC-12:10 | 211.53 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.06 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 133.00 | 263.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1598.58 | 18-JAN-13:00 | 13725.06 | 09-JAN-07:03 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.90 | 01-FEB-12:07 | 10928.02 | 09-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 11920.18 | 30-MAR-06:02 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1596.33 | 26-APR-11:10 | 8582.31 | 03-APR-06:10 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 04-MAY-12:00 | 7616.57 | 30-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.08 | 29-JUN-11:10 | 6501.76 | 01-JUN-06:10 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3174.79 | 19-JUL-12:00 | 5035.75 | 27-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.73 | 18-AUG-12:00 | 5778.62 | 28-AUG-06:05 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8641.29 | 29-SEP-11:02 | 7337.17 | 20-SEP-06:08 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8857.97 | 16-OCT-11:02 | 9223.83 | 12-OCT-06:10 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.38 | 28-NOV-14:00 | 10198.65 | 24-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1382.78 | 19-DEC-13:00 | 12302.02 | 22-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 5035.75 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8857.97 | 13725.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 15-JAN-14:20 | 229.60 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 | 01-FEB-12:10 | 223.87 | 08-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 | 12-MAR-10:10 | 263.80 | 28-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 | 30-APR-11:00 | 205.11 | 16-APR-17:40 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 03-MAY-12:00 | 209.64 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 | 25-JUN-11:30 | 148.76 | 03-JUN-17:10 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.59 | 23-JUL-11:00 | 133.91 | 09-JUL-17:20 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.14 | 06-AUG-11:00 | 101.43 | 26-AUG-17:30 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 29-SEP-14:00 | 147.86 | 03-SEP-16:30 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.12 | 15-OCT-09:00 | 176.36 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 | 19-NOV-11:50 | 227.17 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.45 | 25-DEC-11:52 | 214.70 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 101.43 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 147.12 | 263.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.37 | 15-JAN-15:00 | 521.62 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 01-FEB-12:00 | 514.28 | 08-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 11-MAR-14:00 | 620.27 | 28-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.15 | 30-APR-11:00 | 368.81 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 390.84 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 29-JUN-11:00 | 249.62 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 23-JUL-11:00 | 201.46 | 16-JUL-18:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 | 06-AUG-13:00 | 179.34 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.70 | 29-SEP-14:00 | 201.36 | 24-SEP-15:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.60 | 15-OCT-09:00 | 385.36 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.32 | 19-NOV-13:00 | 498.97 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.37 | 25-DEC-11:52 | 486.04 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.34 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 290.60 | 620.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 15-JAN-15:00 | 343.06 | 27-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 01-FEB-12:00 | 337.48 | 08-FEB-06:00 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 | 11-MAR-14:00 | 412.44 | 28-MAR-21:03 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.14 | 30-APR-11:40 | 240.05 | 21-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 241.41 | 29-MAY-13:00 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 29-JUN-11:00 | 165.83 | 04-JUN-13:23 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 31-JUL-13:00 | 149.65 | 16-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.26 | 06-AUG-13:00 | 125.22 | 20-AUG-07:50 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.11 | 29-SEP-14:10 | 192.82 | 03-SEP-07:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.61 | 15-OCT-13:00 | 256.49 | 30-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.90 | 19-NOV-13:00 | 354.01 | 23-NOV-07:00 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.46 | 25-DEC-12:00 | 320.45 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.22 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 211.61 | 412.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 14-JAN-11:00 | 532.96 | 07-JAN-02:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 01-FEB-12:00 | 579.51 | 26-FEB-12:20 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 620.96 | 28-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 30-APR-09:53 | 414.39 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 376.86 | 07-MAY-13:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 29-JUN-11:00 | 246.31 | 07-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.73 | 23-JUL-11:00 | 200.01 | 04-JUL-13:30 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 | 17-AUG-14:00 | 178.38 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.45 | 29-SEP-14:00 | 286.11 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.87 | 15-OCT-08:54 | 410.87 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 | 19-NOV-12:54 | 516.48 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 05-DEC-10:00 | 501.14 | 03-DEC-11:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.38 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 222.87 | 620.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 | 15-JAN-09:55 | 346.58 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 | 01-FEB-12:00 | 348.16 | 26-FEB-16:40 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 | 12-MAR-10:10 | 413.12 | 28-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.29 | 30-APR-11:40 | 339.52 | 16-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | 03-MAY-12:00 | 344.81 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.41 | 18-JUN-11:02 | 237.25 | 03-JUN-17:08 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.81 | 23-JUL-11:20 | 217.16 | 09-JUL-17:20 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.66 | 06-AUG-11:00 | 155.65 | 26-AUG-17:10 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.14 | 29-SEP-14:00 | 232.83 | 03-SEP-16:20 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.37 | 15-OCT-09:00 | 262.81 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.71 | 19-NOV-11:40 | 333.09 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.84 | 25-DEC-11:52 | 324.73 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | 155.65 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 231.37 | 413.12 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.23 | 15-JAN-09:55 | 815.01 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 01-FEB-12:00 | 864.08 | 25-FEB-02:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 11-MAR-12:50 | 911.16 | 28-MAR-21:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 30-APR-10:53 | 552.06 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 535.66 | 27-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 29-JUN-11:00 | 372.33 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.76 | 23-JUL-11:00 | 289.42 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 | 06-AUG-12:52 | 269.20 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.51 | 29-SEP-13:50 | 315.31 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.72 | 15-OCT-13:00 | 613.28 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.22 | 19-NOV-12:51 | 839.96 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.59 | 04-DEC-10:00 | 765.57 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.20 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.72 | 911.16 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.76 | 15-JAN-09:55 | 1006.47 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.54 | 01-FEB-12:00 | 1047.28 | 25-FEB-02:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 | 11-MAR-13:00 | 1119.39 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.73 | 30-APR-10:53 | 684.02 | 21-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 663.74 | 27-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 | 29-JUN-11:00 | 465.40 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.33 | 23-JUL-11:00 | 361.93 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.52 | 06-AUG-12:52 | 334.67 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.91 | 29-SEP-13:50 | 382.87 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.70 | 15-OCT-09:00 | 740.93 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.77 | 19-NOV-12:51 | 1011.94 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.40 | 25-DEC-12:00 | 943.23 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.67 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.70 | 1119.39 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.89 | 15-JAN-09:55 | 872.92 | 06-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 01-FEB-12:00 | 959.36 | 26-FEB-12:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1122.60 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 26-APR-13:00 | 907.81 | 16-APR-12:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1021.48 | 29-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 746.84 | 04-JUN-13:58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 31-JUL-13:00 | 619.71 | 09-JUL-12:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 17-AUG-14:00 | 435.22 | 20-AUG-14:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.02 | 29-SEP-13:30 | 541.12 | 04-SEP-14:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.36 | 15-OCT-08:51 | 602.94 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.48 | 19-NOV-09:53 | 731.54 | 23-NOV-16:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.78 | 18-DEC-03:00 | 819.07 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.36 | 1122.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22419.10 | 20-JAN-16:20 | 12070.02 | 19521.22 | 28515.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22090.42 | 03-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22591.63 | 24-MAR-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28544.56 | 27-APR-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29236.75 | 05-MAY-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32734.19 | 30-JUN-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36414.12 | 20-JUL-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36027.45 | 18-AUG-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45491.25 | 30-SEP-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48635.96 | 02-OCT-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26134.85 | 01-NOV-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22213.76 | 07-DEC-16:20 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22090.42 | 1905.79 | 3253.54 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48635.96 | 12070.02 | 19521.22 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9022.07 | 18-JAN-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.11 |
February | 8882.06 | 01-FEB-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.61 |
March | 11884.66 | 23-MAR-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 |
April | 15094.15 | 26-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
May | 14018.57 | 03-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.98 |
June | 13922.72 | 21-JUN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 |
July | 15497.32 | 31-JUL-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.77 | 0.00 |
August | 14970.11 | 14-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 |
September | 16050.34 | 29-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.08 | 0.00 |
October | 16096.26 | 16-OCT-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.04 | 0.00 |
November | 8429.72 | 10-NOV-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.93 |
December | 8252.71 | 19-DEC-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8252.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16096.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.08 | 100.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5155.32 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.37 |
February | 4110.23 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.08 |
March | 5288.66 | 08-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.67 |
April | 5029.31 | 01-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.75 |
May | 3186.95 | 26-MAY-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.64 |
June | 3246.37 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 |
July | 3695.07 | 19-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 0.00 |
August | 3769.30 | 17-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 0.00 |
September | 4602.81 | 29-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.45 | 0.00 |
October | 5354.29 | 16-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 0.00 |
November | 3957.17 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 |
December | 5263.25 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3186.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5354.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.45 | 200.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4565.05 | 09-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.57 |
February | 4395.98 | 25-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.84 |
March | 5272.29 | 08-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.55 |
April | 4401.41 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.55 |
May | 3300.33 | 05-MAY-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 |
June | 3621.89 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 |
July | 4154.61 | 19-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
August | 4301.88 | 18-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 0.00 |
September | 5237.21 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.29 | 0.00 |
October | 5922.92 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 | 0.00 |
November | 3823.27 | 30-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.57 |
December | 4892.35 | 13-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3300.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5922.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.29 | 172.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14794.45 | 19-JAN-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14626.54 | 03-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15452.82 | 24-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16876.77 | 27-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16941.32 | 04-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17550.88 | 30-JUN-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18025.13 | 19-JUL-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18148.54 | 18-AUG-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18406.77 | 29-SEP-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30393.23 | 02-OCT-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15228.78 | 01-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14593.37 | 07-DEC-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14593.37 | 2541.06 | 4338.05 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30393.23 | 6035.01 | 9760.61 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14581.14 | 19-JAN-15:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14893.19 | 02-FEB-15:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17274.56 | 24-MAR-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19790.27 | 27-APR-14:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19993.91 | 03-MAY-14:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20965.98 | 30-JUN-15:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21552.92 | 19-JUL-15:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21419.91 | 17-AUG-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21053.59 | 29-SEP-14:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22734.66 | 16-OCT-13:50 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14772.29 | 10-NOV-15:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14312.59 | 05-DEC-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14312.59 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22734.66 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3501.34 | 18-JAN-13:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 0.00 |
February | 3121.42 | 20-FEB-14:12 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.58 |
March | 4025.88 | 23-MAR-14:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 |
April | 5788.84 | 26-APR-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 0.00 |
May | 6152.58 | 04-MAY-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 |
June | 5814.39 | 30-JUN-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 |
July | 6718.48 | 19-JUL-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.19 | 0.00 |
August | 6647.18 | 17-AUG-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 35.93 | 0.00 |
September | 8093.95 | 29-SEP-13:10 | 2613.31 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 106.82 | 0.00 |
October | 8017.04 | 16-OCT-12:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 | 0.00 |
November | 3784.01 | 19-NOV-13:31 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 76.52 | 0.00 |
December | 3478.89 | 05-DEC-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3121.42 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8093.95 | 2613.31 | 4115.24 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 | 265.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4503.90 | 20-JAN-09:40 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 |
February | 4375.27 | 01-FEB-10:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
March | 7008.58 | 23-MAR-09:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8326.67 | 26-APR-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 |
May | 13083.54 | 28-MAY-08:22 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.84 |
June | 8700.66 | 25-JUN-09:13 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.16 |
July | 14249.82 | 23-JUL-08:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.18 |
August | 10109.37 | 06-AUG-09:13 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.60 |
September | 10876.53 | 03-SEP-08:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.05 |
October | 14665.83 | 15-OCT-09:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 141.79 | 0.00 |
November | 4865.37 | 19-NOV-10:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 0.00 |
December | 4523.23 | 05-DEC-09:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4375.27 | 169.56 | 289.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14665.83 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 141.79 | 144.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24338.84 | 22-JAN-13:12 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.46 |
February | 22824.95 | 20-FEB-13:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.05 |
March | 20065.98 | 19-MAR-13:22 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.12 |
April | 11226.45 | 26-APR-13:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 0.00 |
May | 8092.68 | 04-MAY-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 |
June | 7355.27 | 30-JUN-12:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 |
July | 10083.86 | 31-JUL-12:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 0.00 |
August | 12333.67 | 20-AUG-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.12 |
September | 17889.03 | 29-SEP-13:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 105.48 | 0.00 |
October | 24569.65 | 15-OCT-12:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 181.27 | 0.00 |
November | 25019.84 | 19-NOV-10:51 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 |
December | 23710.08 | 03-DEC-13:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7355.27 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25019.84 | 1272.23 | 2057.62 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 181.27 | 534.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6495.52 | 18-JAN-14:50 | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.75 |
February | 6913.26 | 22-FEB-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.85 |
March | 10674.01 | 19-MAR-16:42 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.94 |
April | 10006.58 | 26-APR-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 |
May | 15707.99 | 14-MAY-16:22 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.75 |
June | 21026.83 | 25-JUN-15:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.17 |
July | 21241.07 | 16-JUL-15:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.21 |
August | 16637.99 | 20-AUG-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.76 |
September | 17672.12 | 03-SEP-16:12 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.72 |
October | 20381.64 | 15-OCT-15:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 81.98 | 0.00 |
November | 6475.80 | 07-NOV-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.85 |
December | 6559.62 | 18-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6475.80 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21241.07 | 827.17 | 1302.56 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 81.98 | 229.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2912.13 | 18-JAN-13:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 0.00 |
February | 2375.89 | 20-FEB-14:22 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.45 |
March | 2325.40 | 23-MAR-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 |
April | 3780.53 | 26-APR-13:50 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 | 0.00 |
May | 4355.18 | 04-MAY-14:10 | 2544.47 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 |
June | 4238.88 | 29-JUN-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
July | 5094.06 | 19-JUL-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 0.00 |
August | 5071.77 | 18-AUG-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 | 0.00 |
September | 6244.19 | 29-SEP-13:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 56.34 | 0.00 |
October | 6350.72 | 16-OCT-12:05 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 75.20 | 0.00 |
November | 2827.11 | 19-NOV-13:42 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 0.00 |
December | 2867.90 | 19-DEC-13:10 | 3816.70 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2325.40 | 334.80 | 571.56 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6350.72 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 75.20 | 144.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4167.64 | 20-JAN-09:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
February | 3859.24 | 01-FEB-10:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5875.85 | 23-MAR-09:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7090.11 | 26-APR-08:40 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 |
May | 10319.17 | 28-MAY-08:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.00 |
June | 15693.89 | 25-JUN-09:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.36 |
July | 16057.83 | 02-JUL-09:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.81 |
August | 16158.05 | 13-AUG-09:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.10 |
September | 8955.18 | 10-SEP-08:32 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 |
October | 16766.25 | 15-OCT-09:31 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 0.00 |
November | 3811.78 | 19-NOV-08:30 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.36 |
December | 4111.19 | 05-DEC-09:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3811.78 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16766.25 | 805.43 | 1302.65 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 78.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20100.06 | 22-JAN-12:02 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.46 |
February | 19173.39 | 20-FEB-13:42 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.26 |
March | 9920.82 | 23-MAR-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.89 |
April | 9476.89 | 26-APR-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1593.58 | 0.00 |
May | 5920.86 | 04-MAY-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.53 |
June | 5147.96 | 30-JUN-12:20 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.64 |
July | 10611.88 | 31-JUL-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3163.98 | 0.00 |
August | 11021.80 | 18-AUG-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.73 | 0.00 |
September | 17903.76 | 04-SEP-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.17 |
October | 21818.38 | 15-OCT-11:31 | 602.64 | 1028.81 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 45.68 | 0.00 |
November | 19928.98 | 23-NOV-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.17 |
December | 20200.26 | 25-DEC-12:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5147.96 | 334.80 | 571.56 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21818.38 | 1306.65 | 2057.62 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3176.73 | 292.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4987.82 | 18-JAN-15:00 | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
February | 5398.61 | 22-FEB-16:20 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.29 |
March | 7101.71 | 23-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
April | 7967.29 | 26-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
May | 16620.79 | 28-MAY-16:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.76 |
June | 9161.36 | 25-JUN-16:42 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.45 |
July | 17861.71 | 23-JUL-16:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 |
August | 10633.62 | 19-AUG-17:07 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 |
September | 16983.20 | 04-SEP-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.11 |
October | 19175.73 | 15-OCT-15:31 | 381.49 | 651.28 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 0.00 |
November | 5494.03 | 07-NOV-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 |
December | 5541.04 | 18-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4987.82 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19175.73 | 827.17 | 1302.56 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 112.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3369.84 | 24-JAN-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 0.00 |
February | 3007.66 | 03-FEB-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 |
March | 3523.30 | 23-MAR-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 |
April | 5038.05 | 26-APR-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 0.00 |
May | 5439.79 | 04-MAY-14:10 | 2544.47 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 |
June | 5163.19 | 29-JUN-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 |
July | 5891.96 | 31-JUL-13:10 | 2613.31 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 0.00 |
August | 5908.36 | 17-AUG-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 | 0.00 |
September | 7361.95 | 29-SEP-13:10 | 2613.31 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 0.00 |
October | 7351.01 | 16-OCT-12:05 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 117.48 | 0.00 |
November | 3062.50 | 19-NOV-13:31 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 0.00 |
December | 3320.55 | 05-DEC-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3007.66 | 468.72 | 800.19 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7361.95 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 117.48 | 14.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5269.33 | 20-JAN-09:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 |
February | 4964.59 | 01-FEB-10:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
March | 7667.56 | 23-MAR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 |
April | 9920.23 | 30-APR-08:53 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.20 |
May | 7694.73 | 04-MAY-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 |
June | 18136.47 | 25-JUN-09:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.50 |
July | 18458.71 | 04-JUL-08:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.91 |
August | 18468.82 | 13-AUG-09:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.34 |
September | 12524.27 | 03-SEP-09:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.93 |
October | 18950.52 | 15-OCT-08:11 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 0.00 |
November | 7486.27 | 19-NOV-08:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 |
December | 5067.81 | 05-DEC-09:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4964.59 | 169.56 | 289.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18950.52 | 1610.86 | 2605.29 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 | 84.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20617.83 | 08-JAN-13:02 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.57 |
February | 19523.54 | 19-FEB-14:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.50 |
March | 20047.13 | 19-MAR-12:02 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.40 |
April | 11562.72 | 30-APR-13:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.46 |
May | 7381.61 | 04-MAY-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
June | 6600.13 | 30-JUN-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 |
July | 11204.63 | 30-JUL-13:12 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 |
August | 10871.84 | 31-AUG-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 |
September | 19890.01 | 04-SEP-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.27 |
October | 24063.16 | 15-OCT-11:31 | 602.64 | 1028.81 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 62.57 | 0.00 |
November | 22689.15 | 19-NOV-10:51 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.58 |
December | 21016.49 | 24-DEC-12:02 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6600.13 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24063.16 | 1272.23 | 2057.62 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 62.57 | 356.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6337.44 | 18-JAN-15:00 | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
February | 6798.03 | 22-FEB-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 |
March | 10688.82 | 19-MAR-16:42 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.73 |
April | 9603.56 | 26-APR-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 |
May | 18794.28 | 28-MAY-16:22 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.75 |
June | 18843.14 | 18-JUN-16:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.23 |
July | 19972.32 | 04-JUL-16:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15789.59 | 20-AUG-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.45 |
September | 19025.83 | 04-SEP-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.92 |
October | 21361.14 | 15-OCT-15:31 | 381.49 | 651.28 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 0.00 |
November | 6474.35 | 07-NOV-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 |
December | 6560.63 | 18-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6337.44 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21361.14 | 827.17 | 1302.56 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 190.75 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.159580E+12 | 143868.80 | 18-JAN-13:00 | 0.141596E+11 | 143987.28 | 09-JAN-06:19 |
February | 0.140537E+12 | 142436.47 | 01-FEB-11:00 | 0.125564E+11 | 110312.06 | 13-FEB-07:10 |
March | 0.160912E+12 | 152285.96 | 23-MAR-15:09 | 0.150688E+11 | 123844.81 | 30-MAR-06:10 |
April | 0.156787E+12 | 161814.28 | 26-APR-14:09 | 0.421964E+10 | 98343.75 | 01-APR-06:10 |
May | 0.163659E+12 | 145766.00 | 04-MAY-14:09 | 0.291673E+10 | 68992.57 | 15-MAY-06:10 |
June | 0.173610E+12 | 163250.05 | 29-JUN-15:00 | 0.699494E+09 | 44289.14 | 01-JUN-06:10 |
July | 0.186544E+12 | 175874.19 | 31-JUL-14:09 | 0.119200E+09 | 10690.17 | 17-JUL-06:10 |
August | 0.204116E+12 | 179487.30 | 17-AUG-14:09 | 0.146860E+09 | 12795.34 | 28-AUG-06:10 |
September | 0.175833E+12 | 193735.75 | 29-SEP-15:30 | 0.663803E+09 | 53190.93 | 20-SEP-06:10 |
October | 0.184229E+12 | 196515.56 | 16-OCT-10:00 | 0.174420E+10 | 79087.16 | 30-OCT-06:10 |
November | 0.157335E+12 | 141846.00 | 28-NOV-13:00 | 0.648660E+10 | 94370.38 | 24-NOV-07:10 |
December | 0.158837E+12 | 147153.22 | 05-DEC-15:09 | 0.115673E+11 | 112300.32 | 26-DEC-07:10 |
Annual Sum or Average | 0.202198E+13 | 0.703485E+11 | ||||
Minimum of Months | 0.140537E+12 | 141846.00 | 0.119200E+09 | 10690.17 | ||
Maximum of Months | 0.204116E+12 | 196515.56 | 0.150688E+11 | 143987.28 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.232584E+11 | 0.613996E+11 | 0.230900E+10 | 0.125556E+11 | 75293607.38 | 0.00 | 0.847802E+10 | 0.00 | 0.00 | 0.00 | 0.425630E+10 | 0.00 |
February | 0.428574E+11 | 0.198804E+11 | 0.556056E+11 | 0.209511E+10 | 0.109715E+11 | 64747536.89 | 0.00 | 0.519085E+10 | 0.00 | 0.00 | 0.00 | 0.387124E+10 | 0.00 |
March | 0.509265E+11 | 0.203758E+11 | 0.635880E+11 | 0.240664E+10 | 0.125981E+11 | 80914175.84 | 0.00 | 0.641532E+10 | 0.00 | 0.00 | 0.00 | 0.452042E+10 | 0.00 |
April | 0.454877E+11 | 0.181149E+11 | 0.594055E+11 | 0.224272E+10 | 0.137987E+11 | 32319689.78 | 0.00 | 0.137012E+11 | 0.00 | 0.00 | 0.00 | 0.400419E+10 | 0.00 |
May | 0.490872E+11 | 0.172951E+11 | 0.624938E+11 | 0.235782E+10 | 0.139867E+11 | 27034445.84 | 0.00 | 0.142266E+11 | 0.00 | 0.00 | 0.00 | 0.418480E+10 | 0.00 |
June | 0.488499E+11 | 0.160340E+11 | 0.612808E+11 | 0.231841E+10 | 0.158621E+11 | 15588270.83 | 0.00 | 0.251855E+11 | 0.00 | 0.00 | 0.00 | 0.406372E+10 | 0.00 |
July | 0.457251E+11 | 0.168808E+11 | 0.606074E+11 | 0.228147E+10 | 0.179476E+11 | 12712637.53 | 0.00 | 0.392932E+11 | 0.00 | 0.00 | 0.00 | 0.379580E+10 | 0.00 |
August | 0.509265E+11 | 0.180788E+11 | 0.635880E+11 | 0.240664E+10 | 0.200277E+11 | 13247216.48 | 0.00 | 0.449072E+11 | 0.00 | 0.00 | 0.00 | 0.416796E+10 | 0.00 |
September | 0.454877E+11 | 0.190337E+11 | 0.593832E+11 | 0.224140E+10 | 0.163960E+11 | 14685243.27 | 0.00 | 0.294663E+11 | 0.00 | 0.00 | 0.00 | 0.380993E+10 | 0.00 |
October | 0.472479E+11 | 0.213307E+11 | 0.614108E+11 | 0.230966E+10 | 0.166199E+11 | 20249528.78 | 0.00 | 0.312728E+11 | 0.00 | 0.00 | 0.00 | 0.401701E+10 | 0.00 |
November | 0.466941E+11 | 0.220964E+11 | 0.599069E+11 | 0.224962E+10 | 0.129209E+11 | 39559702.47 | 0.00 | 0.938356E+10 | 0.00 | 0.00 | 0.00 | 0.404361E+10 | 0.00 |
December | 0.457251E+11 | 0.236547E+11 | 0.605962E+11 | 0.228081E+10 | 0.128480E+11 | 62061848.44 | 0.00 | 0.957459E+10 | 0.00 | 0.00 | 0.00 | 0.409538E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.236034E+12 | 0.729266E+12 | 0.274993E+11 | 0.176533E+12 | 0.458414E+09 | 0.00 | 0.237095E+12 | 0.00 | 0.00 | 0.00 | 0.488304E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.160340E+11 | 0.556056E+11 | 0.209511E+10 | 0.109715E+11 | 12712637.53 | 0.00 | 0.519085E+10 | 0.00 | 0.00 | 0.00 | 0.379580E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.236547E+11 | 0.635880E+11 | 0.240664E+10 | 0.200277E+11 | 80914175.84 | 0.00 | 0.449072E+11 | 0.00 | 0.00 | 0.00 | 0.452042E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.141596E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.125564E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.150688E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.421964E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.291673E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.699494E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.119200E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.146860E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.663803E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.174420E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.648660E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.115673E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.703485E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.119200E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.150688E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 06-JAN-17:10 | 18677.34 | 18-JAN-15:09 | 618.12 | 09-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 06-FEB-17:10 | 17483.25 | 03-FEB-15:09 | 495.36 | 27-FEB-07:30 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 01-MAR-17:10 | 19650.08 | 23-MAR-15:20 | 574.90 | 30-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 17-APR-16:10 | 22205.56 | 26-APR-14:09 | 398.61 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 01-MAY-07:10 | 19241.09 | 03-MAY-14:50 | 307.67 | 15-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 01-JUN-07:10 | 20958.55 | 30-JUN-15:00 | 222.23 | 01-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 24475.82 | 31-JUL-14:30 | 45.22 | 17-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:10 | 25382.58 | 18-AUG-14:00 | 53.47 | 28-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 01-SEP-07:10 | 29812.10 | 29-SEP-15:50 | 243.02 | 20-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 02-OCT-07:10 | 29121.14 | 16-OCT-15:30 | 360.46 | 30-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 13-NOV-17:10 | 16870.60 | 10-NOV-13:00 | 408.00 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 11-DEC-17:10 | 18219.29 | 19-DEC-15:20 | 509.16 | 26-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 16870.60 | 45.22 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 29812.10 | 618.12 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 34230.60 | 18-JAN-13:09 | 0.00 | 0.00 | 0.00 | 5763.63 | 30-JAN-12:00 | 0.00 |
February | 30558.23 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 5763.72 | 02-FEB-12:30 | 0.00 |
March | 36226.35 | 23-MAR-14:39 | 0.00 | 0.00 | 0.00 | 5756.21 | 03-MAR-12:00 | 0.00 |
April | 43626.26 | 26-APR-13:39 | 0.00 | 0.00 | 0.00 | 5456.31 | 03-APR-11:20 | 0.00 |
May | 33161.85 | 03-MAY-12:00 | 0.00 | 0.00 | 0.00 | 5388.49 | 01-MAY-11:30 | 0.00 |
June | 45988.22 | 29-JUN-13:20 | 0.00 | 0.00 | 0.00 | 5358.79 | 01-JUN-11:00 | 0.00 |
July | 56100.68 | 31-JUL-12:00 | 0.00 | 0.00 | 0.00 | 5261.99 | 06-JUL-11:30 | 0.00 |
August | 58626.62 | 17-AUG-14:09 | 0.00 | 0.00 | 0.00 | 5237.82 | 30-AUG-11:39 | 0.00 |
September | 76044.93 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 5351.65 | 28-SEP-11:39 | 0.00 |
October | 78826.62 | 16-OCT-10:00 | 0.00 | 0.00 | 0.00 | 5382.02 | 31-OCT-11:30 | 0.00 |
November | 31741.42 | 28-NOV-13:00 | 0.00 | 0.00 | 0.00 | 5411.01 | 30-NOV-12:30 | 0.00 |
December | 34195.03 | 19-DEC-13:09 | 0.00 | 0.00 | 0.00 | 5751.93 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 30558.23 | 0.00 | 0.00 | 0.00 | 5237.82 | 0.00 | ||
Maximum of Months | 78826.62 | 0.00 | 0.00 | 0.00 | 5763.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 143868.80 | 18-JAN-13:00 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 14525.04 | 6.85 | 0.00 | 33916.64 | 0.00 |
February | 142436.47 | 01-FEB-11:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 14464.07 | 6.85 | 0.00 | 30558.23 | 0.00 |
March | 152285.96 | 23-MAR-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 19640.72 | 6.91 | 0.00 | 35776.27 | 0.00 |
April | 161814.28 | 26-APR-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 22205.56 | 6.94 | 0.00 | 43614.41 | 0.00 |
May | 145766.00 | 04-MAY-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 18607.02 | 6.93 | 0.00 | 31276.09 | 0.00 |
June | 163250.05 | 29-JUN-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 20520.18 | 6.88 | 0.00 | 45855.57 | 0.00 |
July | 175874.19 | 31-JUL-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 24259.63 | 6.90 | 0.00 | 55929.76 | 0.00 |
August | 179487.30 | 17-AUG-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 25039.99 | 6.92 | 0.00 | 58626.62 | 0.00 |
September | 193735.75 | 29-SEP-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 29081.76 | 6.85 | 0.00 | 67950.09 | 0.00 |
October | 196515.56 | 16-OCT-10:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 20630.43 | 6.85 | 0.00 | 78826.62 | 0.00 |
November | 141846.00 | 28-NOV-13:00 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 15015.83 | 6.85 | 0.00 | 31741.42 | 0.00 |
December | 147153.22 | 05-DEC-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 17966.51 | 6.85 | 0.00 | 33185.64 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 141846.00 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 14464.07 | 6.85 | 0.00 | 30558.23 | 0.00 | |
Maximum of Months | 196515.56 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 29081.76 | 6.94 | 0.00 | 78826.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 143987.28 | 09-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 110312.06 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 123844.81 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 98343.75 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 68992.57 | 15-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 44289.14 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 10690.17 | 17-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 12795.34 | 28-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 53190.93 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 79087.16 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 94370.38 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 112300.32 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 10690.17 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 143987.28 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.06 | 0.83 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.33 | 0.33 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 19.13 | 1.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.33 | 0.83 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.20 | 0.67 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.28 | 0.17 | 19.28 | 0.17 | 21.94 | 0.17 | 23.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.75 | 0.67 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.78 | 1.50 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.06 | 4.00 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.92 | 2.67 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.91 | 0.67 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.26 | 1.00 | 28.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.22 | 0.83 | 19.22 | 10.67 | 26.78 | 10.67 | 27.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.28 | 0.67 | 19.28 | 4.00 | 28.26 | 4.00 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.26 | 0.50 | 19.26 | 1.83 | 24.89 | 1.83 | 26.09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.65 | 1.50 | 27.65 |
March | 0.17 | 19.32 | 0.17 | 19.32 | 0.50 | 24.23 | 0.50 | 25.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 1.17 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.35 | 6.50 | 28.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.12 | 3.67 | 28.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.93 | 4.17 | 27.93 |
Annual Sum or Average | 0.67 | 19.28 | 0.67 | 19.28 | 19.67 | 27.48 | 19.67 | 27.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.32 | 0.50 | 19.32 | 6.50 | 28.35 | 6.50 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.24 | 0.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.43 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.74 | 2.00 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.69 | 1.67 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.91 | 1.67 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.26 | 4.67 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.31 | 2.67 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.87 | 1.67 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.55 | 1.67 | 28.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 19.29 | 0.67 | 19.29 | 18.17 | 27.50 | 16.00 | 27.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.43 | 0.50 | 19.43 | 5.50 | 28.55 | 4.67 | 28.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.59 | 0.67 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.83 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.83 | 3.17 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.74 | 2.33 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.71 | 0.67 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.03 | 1.17 | 28.03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.83 | 27.78 | 8.83 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.03 | 3.17 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 19.70 | 8.33 | 19.70 | 3.17 | 21.01 | 3.17 | 21.96 |
February | 3.83 | 19.89 | 3.83 | 19.89 | 1.67 | 21.28 | 1.67 | 22.25 |
March | 13.17 | 19.65 | 13.17 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
April | 1.17 | 20.32 | 1.17 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
May | 0.33 | 20.30 | 0.33 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.61 | 3.00 | 25.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.83 | 13.00 | 26.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.08 | 4.50 | 28.08 |
December | 4.33 | 19.99 | 4.33 | 19.99 | 5.33 | 23.07 | 5.33 | 24.46 |
Annual Sum or Average | 31.17 | 19.77 | 31.17 | 19.77 | 30.67 | 22.24 | 30.67 | 23.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.17 | 20.32 | 13.17 | 20.32 | 13.00 | 28.08 | 13.00 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.50 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.53 | 1.00 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.82 | 3.83 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.86 | 2.33 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.54 | 1.33 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.29 | 1.33 | 28.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 27.79 | 10.83 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.29 | 3.83 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.15 | 0.67 | 28.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.52 | 0.67 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.96 | 1.67 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.19 | 4.00 | 28.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.98 | 3.33 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.87 | 1.33 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.40 | 1.00 | 28.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.67 | 28.05 | 12.67 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.40 | 4.00 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.05 | 3.17 | 28.05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.77 | 2.67 | 27.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.60 | 0.67 | 27.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.44 | 1.50 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.09 | 7.67 | 28.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.20 | 4.67 | 28.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.19 | 5.33 | 28.19 |
Annual Sum or Average | 0.00 | 0.00 | 25.67 | 28.04 | 25.67 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.20 | 7.67 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.59 | 2.33 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.64 | 1.33 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.86 | 1.33 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.19 | 4.00 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.18 | 2.67 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.83 | 1.67 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.42 | 1.67 | 28.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 28.01 | 15.00 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.42 | 4.00 | 28.42 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 130.17 | 23.80 | 164.17 | 24.29 | 12.17 | 24.27 |
February | 66.00 | 23.80 | 145.83 | 24.40 | 0.00 | 24.40 |
March | 45.17 | 23.71 | 208.33 | 24.38 | 0.00 | 24.38 |
April | 16.67 | 23.72 | 325.00 | 24.40 | 0.00 | 24.40 |
May | 0.33 | 23.72 | 341.33 | 24.50 | 0.00 | 24.50 |
June | 0.00 | 0.00 | 466.83 | 24.38 | 0.00 | 24.38 |
July | 0.00 | 0.00 | 497.00 | 24.39 | 0.00 | 24.39 |
August | 0.00 | 0.00 | 514.00 | 24.34 | 0.00 | 24.34 |
September | 0.00 | 0.00 | 458.17 | 24.40 | 0.00 | 24.40 |
October | 1.00 | 24.00 | 318.00 | 24.60 | 0.00 | 24.60 |
November | 62.67 | 23.98 | 227.17 | 24.51 | 0.00 | 24.51 |
December | 132.00 | 23.91 | 115.17 | 24.33 | 0.00 | 24.33 |
Annual Sum or Average | 454.00 | 23.84 | 3781.00 | 24.41 | 12.17 | 24.40 |
Minimum of Months | 0.00 | 0.00 | 115.17 | 24.29 | 0.00 | 24.27 |
Maximum of Months | 132.00 | 24.00 | 514.00 | 24.60 | 12.17 | 24.60 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 364.00 | 23.03 | 25.33 | 23.10 | 1.17 | 23.09 |
February | 319.67 | 23.04 | 17.33 | 23.09 | 0.00 | 23.09 |
March | 341.33 | 23.11 | 39.67 | 23.21 | 0.00 | 23.21 |
April | 190.33 | 23.10 | 128.83 | 23.54 | 0.00 | 23.54 |
May | 168.00 | 23.22 | 130.67 | 23.65 | 0.00 | 23.65 |
June | 70.83 | 23.31 | 295.83 | 24.03 | 0.00 | 24.03 |
July | 5.50 | 23.41 | 396.17 | 24.18 | 0.00 | 24.18 |
August | 0.00 | 0.00 | 436.17 | 24.16 | 0.00 | 24.16 |
September | 58.33 | 23.34 | 296.00 | 24.06 | 0.00 | 24.06 |
October | 154.67 | 23.46 | 186.67 | 23.90 | 0.00 | 23.90 |
November | 274.50 | 23.28 | 59.50 | 23.46 | 0.00 | 23.46 |
December | 397.33 | 23.20 | 12.83 | 23.23 | 0.00 | 23.23 |
Annual Sum or Average | 2344.50 | 23.16 | 2025.00 | 23.64 | 1.17 | 23.64 |
Minimum of Months | 0.00 | 0.00 | 12.83 | 23.09 | 0.00 | 23.09 |
Maximum of Months | 397.33 | 23.46 | 436.17 | 24.18 | 1.17 | 24.18 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 436.33 | 22.24 | 34.50 | 22.19 | 21.50 | 22.10 |
February | 380.17 | 22.30 | 21.00 | 22.34 | 6.00 | 22.31 |
March | 412.50 | 22.42 | 42.17 | 22.52 | 5.17 | 22.50 |
April | 276.50 | 22.72 | 113.33 | 23.09 | 0.00 | 23.09 |
May | 256.50 | 22.84 | 128.67 | 23.26 | 0.00 | 23.26 |
June | 137.67 | 23.00 | 242.33 | 23.70 | 0.00 | 23.70 |
July | 68.83 | 23.08 | 352.67 | 23.95 | 0.00 | 23.95 |
August | 74.83 | 23.02 | 363.50 | 23.89 | 0.00 | 23.89 |
September | 169.83 | 23.00 | 206.50 | 23.59 | 0.00 | 23.59 |
October | 253.67 | 22.95 | 140.83 | 23.37 | 0.00 | 23.37 |
November | 382.00 | 22.59 | 29.67 | 22.66 | 4.33 | 22.63 |
December | 454.83 | 22.35 | 22.17 | 22.31 | 16.00 | 22.26 |
Annual Sum or Average | 3303.67 | 22.57 | 1697.33 | 23.05 | 53.00 | 23.02 |
Minimum of Months | 68.83 | 22.24 | 21.00 | 22.19 | 0.00 | 22.10 |
Maximum of Months | 454.83 | 23.08 | 363.50 | 23.95 | 21.50 | 23.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.50 | 21.21 | 123.33 | 20.95 | 121.33 | 20.78 |
February | 443.00 | 21.36 | 74.00 | 21.16 | 72.50 | 21.01 |
March | 474.83 | 21.44 | 84.33 | 21.32 | 69.00 | 21.16 |
April | 358.83 | 21.85 | 90.67 | 22.14 | 15.83 | 22.07 |
May | 333.67 | 22.04 | 109.17 | 22.49 | 5.17 | 22.46 |
June | 224.50 | 22.45 | 203.83 | 23.20 | 0.00 | 23.20 |
July | 163.50 | 22.66 | 279.33 | 23.55 | 0.00 | 23.55 |
August | 206.33 | 22.50 | 265.83 | 23.34 | 0.00 | 23.34 |
September | 284.67 | 22.24 | 151.33 | 22.85 | 0.00 | 22.85 |
October | 329.33 | 22.08 | 114.50 | 22.44 | 18.00 | 22.35 |
November | 479.00 | 21.62 | 68.67 | 21.45 | 66.33 | 21.31 |
December | 492.00 | 21.23 | 126.67 | 20.99 | 126.67 | 20.82 |
Annual Sum or Average | 4274.17 | 21.74 | 1691.67 | 22.05 | 494.83 | 21.89 |
Minimum of Months | 163.50 | 21.21 | 68.67 | 20.95 | 0.00 | 20.78 |
Maximum of Months | 492.00 | 22.66 | 279.33 | 23.55 | 126.67 | 23.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.50 | 21.43 | 87.33 | 21.26 | 75.83 | 21.09 |
February | 407.00 | 21.40 | 65.33 | 21.32 | 50.67 | 21.17 |
March | 427.33 | 21.44 | 100.00 | 21.53 | 51.33 | 21.38 |
April | 258.83 | 21.63 | 185.33 | 22.63 | 10.00 | 22.59 |
May | 285.67 | 21.74 | 171.00 | 22.70 | 3.33 | 22.69 |
June | 232.67 | 22.18 | 221.83 | 23.15 | 5.67 | 23.20 |
July | 165.17 | 22.79 | 323.17 | 23.76 | 19.50 | 23.88 |
August | 185.50 | 22.49 | 319.50 | 23.53 | 13.17 | 23.61 |
September | 244.33 | 21.95 | 209.67 | 22.93 | 4.17 | 22.96 |
October | 290.33 | 21.91 | 150.83 | 22.58 | 14.67 | 22.54 |
November | 449.67 | 21.72 | 49.17 | 21.64 | 40.00 | 21.52 |
December | 480.50 | 21.47 | 67.50 | 21.28 | 67.33 | 21.12 |
Annual Sum or Average | 3892.50 | 21.72 | 1950.67 | 22.32 | 355.67 | 22.23 |
Minimum of Months | 165.17 | 21.40 | 49.17 | 21.26 | 3.33 | 21.09 |
Maximum of Months | 480.50 | 22.79 | 323.17 | 23.76 | 75.83 | 23.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.49 | 214.00 | 22.20 | 59.83 | 22.02 |
February | 305.00 | 21.36 | 158.00 | 21.96 | 48.50 | 21.79 |
March | 372.83 | 21.41 | 168.33 | 21.85 | 56.00 | 21.68 |
April | 278.33 | 21.62 | 180.00 | 22.52 | 14.67 | 22.44 |
May | 342.33 | 21.77 | 131.50 | 22.35 | 12.00 | 22.29 |
June | 276.17 | 22.11 | 161.50 | 22.82 | 0.00 | 22.82 |
July | 207.50 | 22.33 | 248.33 | 23.29 | 0.67 | 23.29 |
August | 212.00 | 22.30 | 270.33 | 23.30 | 1.67 | 23.31 |
September | 230.17 | 22.23 | 237.17 | 23.26 | 8.17 | 23.32 |
October | 254.83 | 22.52 | 238.33 | 23.37 | 37.33 | 23.47 |
November | 281.50 | 21.72 | 209.33 | 22.62 | 38.17 | 22.53 |
December | 294.17 | 21.58 | 212.67 | 22.36 | 57.33 | 22.19 |
Annual Sum or Average | 3354.83 | 21.82 | 2429.50 | 22.64 | 334.33 | 22.56 |
Minimum of Months | 207.50 | 21.36 | 131.50 | 21.85 | 0.00 | 21.68 |
Maximum of Months | 372.83 | 22.52 | 270.33 | 23.37 | 59.83 | 23.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 445.17 | 21.08 | 142.17 | 21.02 | 110.17 | 20.85 |
February | 390.83 | 21.07 | 116.33 | 21.19 | 72.33 | 21.03 |
March | 434.50 | 21.13 | 130.83 | 21.34 | 66.00 | 21.19 |
April | 344.00 | 21.62 | 141.17 | 22.27 | 22.33 | 22.26 |
May | 351.33 | 21.72 | 142.17 | 22.41 | 15.67 | 22.41 |
June | 282.50 | 22.10 | 175.33 | 22.88 | 9.33 | 22.95 |
July | 236.50 | 22.56 | 233.17 | 23.41 | 24.00 | 23.57 |
August | 254.00 | 22.28 | 224.83 | 23.12 | 14.67 | 23.23 |
September | 297.17 | 21.94 | 157.00 | 22.73 | 7.67 | 22.79 |
October | 343.83 | 21.80 | 146.67 | 22.38 | 25.17 | 22.36 |
November | 399.17 | 21.24 | 123.83 | 21.43 | 63.67 | 21.29 |
December | 442.17 | 21.09 | 133.50 | 21.00 | 111.17 | 20.84 |
Annual Sum or Average | 4221.17 | 21.54 | 1867.00 | 22.04 | 542.17 | 21.94 |
Minimum of Months | 236.50 | 21.07 | 116.33 | 21.00 | 7.67 | 20.84 |
Maximum of Months | 445.17 | 22.56 | 233.17 | 23.41 | 111.17 | 23.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.17 | 21.63 | 61.50 | 21.48 | 61.50 | 21.36 |
February | 454.00 | 21.65 | 25.67 | 21.57 | 25.67 | 21.50 |
March | 502.17 | 21.74 | 31.50 | 21.66 | 29.67 | 21.58 |
April | 416.17 | 22.30 | 27.67 | 22.37 | 3.67 | 22.36 |
May | 375.33 | 22.61 | 34.50 | 22.73 | 0.00 | 22.73 |
June | 221.17 | 22.93 | 167.17 | 23.40 | 0.00 | 23.40 |
July | 100.00 | 23.04 | 298.67 | 23.81 | 0.00 | 23.81 |
August | 158.00 | 22.93 | 266.33 | 23.60 | 0.00 | 23.60 |
September | 265.17 | 22.80 | 142.00 | 23.22 | 0.00 | 23.22 |
October | 307.50 | 22.70 | 99.00 | 23.05 | 0.00 | 23.05 |
November | 480.17 | 22.10 | 15.33 | 22.05 | 15.33 | 22.00 |
December | 497.00 | 21.66 | 44.83 | 21.55 | 44.83 | 21.45 |
Annual Sum or Average | 4263.83 | 22.15 | 1214.17 | 22.44 | 180.67 | 22.38 |
Minimum of Months | 100.00 | 21.63 | 15.33 | 21.48 | 0.00 | 21.36 |
Maximum of Months | 502.17 | 23.04 | 298.67 | 23.81 | 61.50 | 23.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.17 | 21.84 | 35.00 | 21.79 | 25.50 | 21.71 |
February | 421.33 | 21.66 | 26.83 | 21.67 | 17.33 | 21.60 |
March | 445.00 | 21.69 | 49.33 | 21.82 | 15.50 | 21.76 |
April | 277.50 | 22.03 | 148.67 | 22.82 | 2.17 | 22.81 |
May | 309.50 | 22.17 | 142.50 | 22.89 | 0.00 | 22.89 |
June | 237.33 | 22.43 | 203.50 | 23.26 | 1.33 | 23.27 |
July | 115.50 | 22.96 | 341.00 | 23.94 | 11.00 | 24.01 |
August | 133.83 | 22.81 | 339.50 | 23.77 | 8.17 | 23.82 |
September | 229.33 | 22.41 | 209.33 | 23.22 | 2.67 | 23.24 |
October | 261.67 | 22.38 | 131.33 | 23.03 | 2.33 | 23.06 |
November | 444.67 | 22.09 | 19.33 | 22.13 | 6.00 | 22.11 |
December | 484.50 | 21.85 | 21.67 | 21.77 | 21.67 | 21.70 |
Annual Sum or Average | 3826.33 | 22.05 | 1668.00 | 22.65 | 113.67 | 22.63 |
Minimum of Months | 115.50 | 21.66 | 19.33 | 21.67 | 0.00 | 21.60 |
Maximum of Months | 484.50 | 22.96 | 341.00 | 23.94 | 25.50 | 24.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 276.00 | 22.11 | 187.00 | 22.93 | 22.00 | 22.89 |
February | 307.83 | 21.72 | 109.50 | 22.38 | 10.00 | 22.36 |
March | 387.50 | 21.60 | 109.83 | 21.99 | 21.83 | 21.90 |
April | 310.83 | 22.02 | 134.83 | 22.71 | 1.17 | 22.70 |
May | 399.83 | 22.00 | 59.33 | 22.29 | 1.00 | 22.29 |
June | 343.33 | 22.32 | 93.67 | 22.69 | 0.00 | 22.69 |
July | 201.33 | 22.55 | 219.17 | 23.34 | 1.00 | 23.34 |
August | 161.67 | 22.49 | 287.17 | 23.49 | 2.50 | 23.48 |
September | 166.33 | 22.55 | 260.67 | 23.60 | 6.00 | 23.62 |
October | 178.00 | 23.21 | 278.00 | 24.03 | 29.50 | 24.18 |
November | 253.83 | 22.38 | 189.83 | 23.32 | 7.50 | 23.39 |
December | 267.67 | 22.26 | 185.33 | 23.18 | 14.17 | 23.21 |
Annual Sum or Average | 3254.17 | 22.17 | 2114.33 | 22.99 | 116.67 | 23.00 |
Minimum of Months | 161.67 | 21.60 | 59.33 | 21.99 | 0.00 | 21.90 |
Maximum of Months | 399.83 | 23.21 | 287.17 | 24.03 | 29.50 | 24.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 451.83 | 21.49 | 66.17 | 21.49 | 43.67 | 21.39 |
February | 404.00 | 21.42 | 52.00 | 21.54 | 22.50 | 21.48 |
March | 447.00 | 21.43 | 70.83 | 21.64 | 22.17 | 21.58 |
April | 343.67 | 22.01 | 116.50 | 22.59 | 4.17 | 22.58 |
May | 343.83 | 22.13 | 120.67 | 22.72 | 0.67 | 22.73 |
June | 243.17 | 22.42 | 178.67 | 23.18 | 2.83 | 23.20 |
July | 139.83 | 22.95 | 296.33 | 23.85 | 14.00 | 23.94 |
August | 157.33 | 22.73 | 281.67 | 23.62 | 9.67 | 23.69 |
September | 237.83 | 22.48 | 167.17 | 23.21 | 3.67 | 23.24 |
October | 302.50 | 22.34 | 139.17 | 22.96 | 4.67 | 23.00 |
November | 401.67 | 21.72 | 59.83 | 21.96 | 10.67 | 21.92 |
December | 450.67 | 21.51 | 46.33 | 21.49 | 34.17 | 21.42 |
Annual Sum or Average | 3923.33 | 21.89 | 1595.33 | 22.47 | 172.83 | 22.45 |
Minimum of Months | 139.83 | 21.42 | 46.33 | 21.49 | 0.67 | 21.39 |
Maximum of Months | 451.83 | 22.95 | 296.33 | 23.85 | 43.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 471.83 | 21.66 | 69.00 | 21.49 | 64.83 | 21.35 |
February | 431.83 | 21.77 | 30.17 | 21.68 | 28.17 | 21.60 |
March | 462.83 | 21.83 | 46.50 | 21.80 | 29.83 | 21.71 |
April | 343.33 | 22.27 | 68.17 | 22.52 | 3.33 | 22.51 |
May | 306.00 | 22.52 | 96.50 | 22.89 | 0.00 | 22.89 |
June | 171.83 | 22.88 | 221.67 | 23.53 | 0.00 | 23.53 |
July | 87.33 | 22.98 | 328.17 | 23.85 | 0.00 | 23.85 |
August | 139.67 | 22.90 | 305.67 | 23.66 | 0.00 | 23.66 |
September | 244.17 | 22.76 | 177.67 | 23.29 | 0.00 | 23.29 |
October | 290.33 | 22.60 | 120.67 | 23.05 | 0.33 | 23.05 |
November | 458.00 | 22.11 | 25.33 | 22.05 | 20.50 | 21.98 |
December | 490.67 | 21.75 | 48.83 | 21.61 | 48.83 | 21.49 |
Annual Sum or Average | 3897.83 | 22.15 | 1538.33 | 22.54 | 195.83 | 22.46 |
Minimum of Months | 87.33 | 21.66 | 25.33 | 21.49 | 0.00 | 21.35 |
Maximum of Months | 490.67 | 22.98 | 328.17 | 23.85 | 64.83 | 23.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 385.83 | 21.63 | 47.33 | 21.58 | 33.67 | 21.46 |
February | 340.50 | 21.53 | 38.50 | 21.59 | 20.67 | 21.50 |
March | 355.17 | 21.54 | 62.17 | 21.72 | 21.83 | 21.63 |
April | 251.33 | 21.86 | 122.33 | 22.66 | 5.33 | 22.68 |
May | 263.83 | 21.97 | 123.33 | 22.80 | 1.33 | 22.81 |
June | 211.00 | 22.34 | 165.50 | 23.20 | 6.17 | 23.26 |
July | 148.67 | 22.90 | 245.33 | 23.80 | 18.67 | 23.94 |
August | 167.50 | 22.66 | 238.50 | 23.55 | 13.83 | 23.65 |
September | 227.83 | 22.22 | 151.67 | 23.00 | 4.50 | 23.04 |
October | 255.67 | 22.13 | 112.67 | 22.77 | 7.67 | 22.77 |
November | 361.33 | 21.81 | 29.00 | 21.88 | 11.00 | 21.83 |
December | 397.67 | 21.67 | 32.83 | 21.57 | 29.00 | 21.47 |
Annual Sum or Average | 3366.33 | 21.91 | 1369.17 | 22.49 | 173.67 | 22.47 |
Minimum of Months | 148.67 | 21.53 | 29.00 | 21.57 | 1.33 | 21.46 |
Maximum of Months | 397.67 | 22.90 | 245.33 | 23.80 | 33.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 278.50 | 21.93 | 204.00 | 22.76 | 32.00 | 22.70 |
February | 288.33 | 21.73 | 141.17 | 22.45 | 24.50 | 22.41 |
March | 355.17 | 21.72 | 145.83 | 22.25 | 26.83 | 22.16 |
April | 270.33 | 21.99 | 171.00 | 22.84 | 4.17 | 22.81 |
May | 334.33 | 22.13 | 115.00 | 22.66 | 1.67 | 22.65 |
June | 258.83 | 22.48 | 160.67 | 23.08 | 0.00 | 23.08 |
July | 168.00 | 22.61 | 258.00 | 23.51 | 0.00 | 23.51 |
August | 163.00 | 22.56 | 291.67 | 23.54 | 0.17 | 23.54 |
September | 191.17 | 22.60 | 254.67 | 23.56 | 6.33 | 23.60 |
October | 218.33 | 23.01 | 256.00 | 23.82 | 27.67 | 24.00 |
November | 255.50 | 22.20 | 205.00 | 23.15 | 21.00 | 23.18 |
December | 274.00 | 22.08 | 202.50 | 22.94 | 34.17 | 22.91 |
Annual Sum or Average | 3055.50 | 22.19 | 2405.50 | 23.04 | 178.50 | 23.04 |
Minimum of Months | 163.00 | 21.72 | 115.00 | 22.25 | 0.00 | 22.16 |
Maximum of Months | 355.17 | 23.01 | 291.67 | 23.82 | 34.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 438.83 | 21.36 | 89.67 | 21.40 | 55.17 | 21.27 |
February | 387.33 | 21.33 | 73.33 | 21.53 | 29.33 | 21.45 |
March | 432.83 | 21.37 | 95.67 | 21.64 | 31.50 | 21.55 |
April | 343.17 | 21.88 | 127.17 | 22.51 | 10.67 | 22.54 |
May | 344.17 | 21.98 | 130.83 | 22.64 | 4.67 | 22.68 |
June | 256.50 | 22.32 | 180.17 | 23.08 | 7.33 | 23.14 |
July | 194.50 | 22.77 | 251.67 | 23.62 | 21.83 | 23.76 |
August | 214.33 | 22.51 | 247.17 | 23.36 | 12.67 | 23.45 |
September | 276.67 | 22.28 | 161.50 | 23.00 | 7.33 | 23.06 |
October | 321.33 | 22.11 | 141.00 | 22.74 | 10.17 | 22.77 |
November | 393.33 | 21.53 | 87.50 | 21.81 | 24.33 | 21.74 |
December | 434.50 | 21.36 | 79.33 | 21.36 | 55.33 | 21.24 |
Annual Sum or Average | 4037.50 | 21.78 | 1665.00 | 22.35 | 270.33 | 22.32 |
Minimum of Months | 194.50 | 21.33 | 73.33 | 21.36 | 4.67 | 21.24 |
Maximum of Months | 438.83 | 22.77 | 251.67 | 23.62 | 55.33 | 23.76 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.20820 | 36.16554 | 0.37377 | 8.27031 |
February | 454.00000 | 24.20506 | 38.09443 | 0.38876 | 8.37537 |
March | 514.00000 | 24.19742 | 40.83067 | 0.40916 | 8.71603 |
April | 485.00000 | 24.29768 | 43.32460 | 0.46910 | 9.83902 |
May | 508.00000 | 24.33953 | 42.58138 | -0.3886 | 8.55237 |
June | 496.00000 | 24.35347 | 47.23773 | -0.3270 | 7.65765 |
July | 497.00000 | 24.39382 | 50.42329 | -0.2753 | 7.01485 |
August | 514.00000 | 24.34134 | 51.64120 | -0.2754 | 6.97130 |
September | 485.00000 | 24.37918 | 48.33275 | -0.3057 | 7.40870 |
October | 502.00000 | 24.39512 | 40.01376 | 0.49243 | 10.47235 |
November | 489.00000 | 24.35040 | 35.95785 | 0.42396 | 9.20530 |
December | 497.00000 | 24.22848 | 31.38625 | 0.35357 | 7.93632 |
Annual Sum or Average | 5943.00000 | 24.30786 | 42.20515 | 0.10869 | 8.36523 |
Minimum of Months | 454.00000 | 24.19742 | 31.38625 | -0.3886 | 6.97130 |
Maximum of Months | 514.00000 | 24.39512 | 51.64120 | 0.49243 | 10.47235 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.30499 | 38.80275 | 0.14909 | 6.28872 |
February | 454.00000 | 23.33266 | 40.97138 | 0.17309 | 6.23621 |
March | 514.00000 | 23.41227 | 43.72000 | 0.21213 | 6.48550 |
April | 485.00000 | 23.67893 | 45.45436 | 0.31107 | 7.56660 |
May | 508.00000 | 23.79369 | 44.55423 | -0.5937 | 13.05474 |
June | 496.00000 | 23.99047 | 48.75676 | -0.4759 | 10.13227 |
July | 497.00000 | 24.09937 | 51.81992 | -0.4024 | 8.65657 |
August | 514.00000 | 24.08873 | 53.01660 | -0.3924 | 8.46144 |
September | 485.00000 | 23.98961 | 50.03729 | -0.4672 | 9.94080 |
October | 502.00000 | 23.95984 | 41.69873 | 0.36908 | 8.27469 |
November | 489.00000 | 23.63833 | 38.31636 | 0.23932 | 6.78822 |
December | 497.00000 | 23.36653 | 33.91883 | 0.13763 | 6.02220 |
Annual Sum or Average | 5943.00000 | 23.72386 | 44.28985 | -0.0643 | 8.17568 |
Minimum of Months | 454.00000 | 23.30499 | 33.91883 | -0.5937 | 6.02220 |
Maximum of Months | 514.00000 | 24.09937 | 53.01660 | 0.36908 | 13.05474 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.46084 | 40.53122 | -0.0495 | 6.72421 |
February | 454.00000 | 22.56802 | 42.70691 | -0.0037 | 6.37646 |
March | 514.00000 | 22.71800 | 45.13650 | 0.05422 | 6.40015 |
April | 485.00000 | 23.25362 | 46.39896 | 0.22347 | 7.13934 |
May | 508.00000 | 23.41872 | 45.30781 | -0.7014 | 17.01865 |
June | 496.00000 | 23.73459 | 49.23693 | -0.5397 | 12.03561 |
July | 497.00000 | 23.90944 | 52.17344 | -0.4394 | 9.59953 |
August | 514.00000 | 23.85939 | 53.58848 | -0.4463 | 9.72589 |
September | 485.00000 | 23.62879 | 50.92942 | -0.5743 | 12.90585 |
October | 502.00000 | 23.49176 | 42.67255 | 0.26243 | 7.40418 |
November | 489.00000 | 22.89065 | 40.04210 | 0.06429 | 6.40391 |
December | 497.00000 | 22.48900 | 35.75893 | -0.0681 | 6.49172 |
Annual Sum or Average | 5943.00000 | 23.20637 | 45.40249 | -0.1870 | 9.04292 |
Minimum of Months | 454.00000 | 22.46084 | 35.75893 | -0.7014 | 6.37646 |
Maximum of Months | 514.00000 | 23.90944 | 53.58848 | 0.26243 | 17.01865 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29485 | 41.83425 | -0.3379 | 9.80827 |
February | 454.00000 | 21.41396 | 44.97512 | -0.2797 | 8.54029 |
March | 514.00000 | 21.61409 | 47.63728 | -0.2078 | 8.15100 |
April | 485.00000 | 22.37603 | 49.01565 | 0.02651 | 7.21791 |
May | 508.00000 | 22.70040 | 47.41333 | -0.9155 | 25.98503 |
June | 496.00000 | 23.25977 | 50.96011 | -0.6656 | 16.70427 |
July | 497.00000 | 23.55224 | 53.78780 | -0.5235 | 12.53785 |
August | 514.00000 | 23.34939 | 55.92799 | -0.5869 | 14.30918 |
September | 485.00000 | 22.91935 | 53.60136 | -0.7858 | 20.76988 |
October | 502.00000 | 22.73781 | 44.65052 | 0.09738 | 7.47363 |
November | 489.00000 | 21.66621 | 42.32745 | -0.2229 | 8.03209 |
December | 497.00000 | 21.26003 | 37.26526 | -0.3678 | 9.75236 |
Annual Sum or Average | 5943.00000 | 22.35251 | 47.47595 | -0.3991 | 12.47906 |
Minimum of Months | 454.00000 | 21.26003 | 37.26526 | -0.9155 | 7.21791 |
Maximum of Months | 514.00000 | 23.55224 | 55.92799 | 0.09738 | 25.98503 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.59417 | 40.79742 | -0.2245 | 8.44458 |
February | 454.00000 | 21.65996 | 44.10666 | -0.1858 | 8.00503 |
March | 514.00000 | 21.86314 | 46.56153 | -0.1049 | 8.21068 |
April | 485.00000 | 22.74990 | 47.59095 | 0.17746 | 8.80357 |
May | 508.00000 | 22.79969 | 46.78855 | -0.8044 | 23.78809 |
June | 496.00000 | 23.13680 | 50.95900 | -0.6163 | 17.47378 |
July | 497.00000 | 23.61278 | 53.17925 | -0.3941 | 12.44756 |
August | 514.00000 | 23.43142 | 55.08754 | -0.4422 | 13.28452 |
September | 485.00000 | 22.93135 | 53.13237 | -0.6949 | 19.76203 |
October | 502.00000 | 22.79217 | 44.31073 | 0.16478 | 8.09041 |
November | 489.00000 | 21.88477 | 41.50997 | -0.1297 | 7.34752 |
December | 497.00000 | 21.54526 | 36.35707 | -0.2579 | 8.27089 |
Annual Sum or Average | 5943.00000 | 22.50642 | 46.72544 | -0.2942 | 12.02743 |
Minimum of Months | 454.00000 | 21.54526 | 36.35707 | -0.8044 | 7.34752 |
Maximum of Months | 514.00000 | 23.61278 | 55.08754 | 0.17746 | 23.78809 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.58316 | 38.39753 | 0.06017 | 10.27275 |
February | 454.00000 | 22.31388 | 42.38155 | -0.0040 | 9.60784 |
March | 514.00000 | 22.14131 | 45.63245 | -0.0312 | 9.31223 |
April | 485.00000 | 22.68374 | 47.64820 | 0.14686 | 8.93719 |
May | 508.00000 | 22.52223 | 47.49918 | -0.9427 | 28.09951 |
June | 496.00000 | 22.89105 | 51.76677 | -0.7594 | 20.41616 |
July | 497.00000 | 23.28567 | 54.34147 | -0.5750 | 14.97234 |
August | 514.00000 | 23.28850 | 55.60457 | -0.5343 | 14.64023 |
September | 485.00000 | 23.21515 | 52.04654 | -0.5851 | 17.71062 |
October | 502.00000 | 23.30924 | 42.67189 | 0.31844 | 11.09509 |
November | 489.00000 | 22.81579 | 39.13442 | 0.13491 | 10.05156 |
December | 497.00000 | 22.70895 | 33.76486 | 0.07111 | 10.37287 |
Annual Sum or Average | 5943.00000 | 22.81539 | 45.94604 | -0.2280 | 13.83764 |
Minimum of Months | 454.00000 | 22.14131 | 33.76486 | -0.9427 | 8.93719 |
Maximum of Months | 514.00000 | 23.30924 | 55.60457 | 0.31844 | 28.09951 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.39523 | 41.06443 | -0.2739 | 9.82631 |
February | 454.00000 | 21.49150 | 44.19724 | -0.2203 | 9.11361 |
March | 514.00000 | 21.57718 | 47.12391 | -0.1671 | 8.95409 |
April | 485.00000 | 22.32742 | 48.53840 | 0.08994 | 9.11857 |
May | 508.00000 | 22.45964 | 47.48419 | -0.8980 | 28.26756 |
June | 496.00000 | 22.85401 | 51.67451 | -0.6828 | 20.30334 |
July | 497.00000 | 23.23656 | 54.38974 | -0.5005 | 15.82237 |
August | 514.00000 | 23.03700 | 56.41469 | -0.5576 | 16.85960 |
September | 485.00000 | 22.70288 | 53.67902 | -0.7416 | 22.25006 |
October | 502.00000 | 22.48437 | 44.71896 | 0.10470 | 8.66853 |
November | 489.00000 | 21.75013 | 41.49233 | -0.1560 | 8.75302 |
December | 497.00000 | 21.41133 | 36.33109 | -0.2912 | 9.79626 |
Annual Sum or Average | 5943.00000 | 22.23237 | 47.29154 | -0.3598 | 14.02441 |
Minimum of Months | 454.00000 | 21.39523 | 36.33109 | -0.8980 | 8.66853 |
Maximum of Months | 514.00000 | 23.23656 | 56.41469 | 0.10470 | 28.26756 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.69891 | 41.52938 | -0.2385 | 7.71855 |
February | 454.00000 | 21.64510 | 45.01602 | -0.2270 | 7.04784 |
March | 514.00000 | 21.78467 | 47.82421 | -0.1752 | 6.88572 |
April | 485.00000 | 22.52080 | 49.36669 | 0.03495 | 6.18241 |
May | 508.00000 | 22.95879 | 47.52150 | -0.8715 | 22.66398 |
June | 496.00000 | 23.49382 | 50.96344 | -0.6400 | 14.62531 |
July | 497.00000 | 23.78077 | 53.35498 | -0.4997 | 10.81674 |
August | 514.00000 | 23.61270 | 55.28041 | -0.5498 | 12.08306 |
September | 485.00000 | 23.31080 | 52.86543 | -0.6933 | 16.29568 |
October | 502.00000 | 23.21331 | 43.97934 | 0.19410 | 6.95885 |
November | 489.00000 | 22.12680 | 41.91938 | -0.1138 | 6.43331 |
December | 497.00000 | 21.65906 | 37.02719 | -0.2667 | 7.51212 |
Annual Sum or Average | 5943.00000 | 22.65775 | 47.24521 | -0.3389 | 10.47323 |
Minimum of Months | 454.00000 | 21.64510 | 37.02719 | -0.8715 | 6.18241 |
Maximum of Months | 514.00000 | 23.78077 | 55.28041 | 0.19410 | 22.66398 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.97861 | 40.15607 | -0.1223 | 6.82432 |
February | 454.00000 | 21.84746 | 43.84208 | -0.1359 | 6.81842 |
March | 514.00000 | 22.01096 | 46.36910 | -0.0718 | 7.09663 |
April | 485.00000 | 22.92006 | 47.39918 | 0.19788 | 7.84470 |
May | 508.00000 | 22.97297 | 46.64571 | -0.7752 | 21.01778 |
June | 496.00000 | 23.27742 | 50.86243 | -0.6114 | 15.83744 |
July | 497.00000 | 23.82135 | 52.52179 | -0.3687 | 10.22050 |
August | 514.00000 | 23.68656 | 54.11454 | -0.3966 | 10.51407 |
September | 485.00000 | 23.22542 | 52.31229 | -0.6210 | 15.79555 |
October | 502.00000 | 23.16896 | 43.48842 | 0.24723 | 7.72174 |
November | 489.00000 | 22.26551 | 40.78188 | -0.0308 | 6.30671 |
December | 497.00000 | 21.90670 | 35.78215 | -0.1591 | 6.66583 |
Annual Sum or Average | 5943.00000 | 22.76333 | 46.21499 | -0.2388 | 10.25139 |
Minimum of Months | 454.00000 | 21.84746 | 35.78215 | -0.7752 | 6.30671 |
Maximum of Months | 514.00000 | 23.82135 | 54.11454 | 0.24723 | 21.01778 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.09615 | 37.18883 | 0.20382 | 8.93791 |
February | 454.00000 | 22.56617 | 41.74583 | 0.07269 | 8.10512 |
March | 514.00000 | 22.22714 | 45.40621 | -0.0010 | 7.88771 |
April | 485.00000 | 22.79627 | 47.70152 | 0.15929 | 7.60284 |
May | 508.00000 | 22.44048 | 48.11492 | -0.9847 | 27.90034 |
June | 496.00000 | 22.79072 | 52.94340 | -0.8236 | 21.20323 |
July | 497.00000 | 23.36108 | 55.39091 | -0.5868 | 13.91364 |
August | 514.00000 | 23.49499 | 56.20877 | -0.4960 | 12.05563 |
September | 485.00000 | 23.58150 | 51.61908 | -0.4776 | 12.71236 |
October | 502.00000 | 23.83066 | 41.89989 | 0.44308 | 11.34842 |
November | 489.00000 | 23.33146 | 37.95416 | 0.27603 | 9.10667 |
December | 497.00000 | 23.24215 | 32.62834 | 0.22115 | 9.00272 |
Annual Sum or Average | 5943.00000 | 23.06437 | 45.77876 | -0.1695 | 12.53575 |
Minimum of Months | 454.00000 | 22.22714 | 32.62834 | -0.9847 | 7.60284 |
Maximum of Months | 514.00000 | 23.83066 | 56.20877 | 0.44308 | 27.90034 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.74118 | 40.52986 | -0.1795 | 7.57479 |
February | 454.00000 | 21.71981 | 43.85860 | -0.1610 | 7.34245 |
March | 514.00000 | 21.77728 | 46.83130 | -0.1219 | 7.35255 |
April | 485.00000 | 22.65146 | 47.94563 | 0.14240 | 7.78078 |
May | 508.00000 | 22.79682 | 46.93195 | -0.8186 | 22.95086 |
June | 496.00000 | 23.20733 | 50.94846 | -0.6152 | 15.99615 |
July | 497.00000 | 23.68321 | 52.99574 | -0.4051 | 10.96845 |
August | 514.00000 | 23.51003 | 54.76411 | -0.4499 | 11.66604 |
September | 485.00000 | 23.22782 | 52.16740 | -0.5995 | 15.35255 |
October | 502.00000 | 23.00261 | 43.60931 | 0.21604 | 7.97417 |
November | 489.00000 | 22.14258 | 40.77062 | -0.0529 | 7.00131 |
December | 497.00000 | 21.74535 | 35.84152 | -0.1961 | 7.45057 |
Annual Sum or Average | 5943.00000 | 22.60620 | 46.46228 | -0.2719 | 10.82034 |
Minimum of Months | 454.00000 | 21.71981 | 35.84152 | -0.8186 | 7.00131 |
Maximum of Months | 514.00000 | 23.68321 | 54.76411 | 0.21604 | 22.95086 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.79612 | 40.99335 | -0.2074 | 7.82931 |
February | 454.00000 | 21.87443 | 44.22101 | -0.1612 | 7.01973 |
March | 514.00000 | 22.03438 | 46.99035 | -0.1022 | 6.95284 |
April | 485.00000 | 22.75396 | 48.34138 | 0.10627 | 6.65849 |
May | 508.00000 | 23.10098 | 46.72950 | -0.8005 | 20.54361 |
June | 496.00000 | 23.58984 | 50.32178 | -0.5799 | 13.17732 |
July | 497.00000 | 23.81728 | 53.18364 | -0.4632 | 10.20262 |
August | 514.00000 | 23.65613 | 55.11054 | -0.5104 | 11.32537 |
September | 485.00000 | 23.34629 | 52.58765 | -0.6624 | 15.67818 |
October | 502.00000 | 23.20960 | 43.82523 | 0.20289 | 7.27029 |
November | 489.00000 | 22.21947 | 41.41916 | -0.0864 | 6.70217 |
December | 497.00000 | 21.78064 | 36.49924 | -0.2314 | 7.53245 |
Annual Sum or Average | 5943.00000 | 22.77145 | 46.71214 | -0.2931 | 10.10584 |
Minimum of Months | 454.00000 | 21.78064 | 36.49924 | -0.8005 | 6.65849 |
Maximum of Months | 514.00000 | 23.81728 | 55.11054 | 0.20289 | 20.54361 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.84551 | 40.51464 | -0.1514 | 7.48342 |
February | 385.00000 | 21.82532 | 43.86153 | -0.1314 | 7.29618 |
March | 433.00000 | 21.97724 | 46.17160 | -0.0687 | 7.56373 |
April | 410.00000 | 22.73650 | 47.74710 | 0.17058 | 8.18915 |
May | 430.00000 | 22.85964 | 46.85003 | -0.7927 | 22.66343 |
June | 418.00000 | 23.16732 | 51.07648 | -0.6259 | 17.10289 |
July | 422.00000 | 23.62109 | 53.23754 | -0.4197 | 12.54689 |
August | 433.00000 | 23.42706 | 55.18232 | -0.4684 | 13.22235 |
September | 410.00000 | 22.98447 | 53.05043 | -0.6879 | 18.67308 |
October | 427.00000 | 22.90389 | 44.41108 | 0.19332 | 7.82210 |
November | 417.00000 | 22.10537 | 41.20295 | -0.0635 | 6.86932 |
December | 422.00000 | 21.80444 | 35.81368 | -0.1805 | 7.30014 |
Annual Sum or Average | 5034.00000 | 22.60975 | 46.60706 | -0.2701 | 11.42086 |
Minimum of Months | 385.00000 | 21.80444 | 35.81368 | -0.7927 | 6.86932 |
Maximum of Months | 433.00000 | 23.62109 | 55.18232 | 0.19332 | 22.66343 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.95718 | 37.49319 | 0.16599 | 9.60978 |
February | 454.00000 | 22.64665 | 41.57097 | 0.09009 | 8.86525 |
March | 514.00000 | 22.45460 | 44.92423 | 0.05363 | 8.42750 |
April | 485.00000 | 22.95060 | 47.01654 | 0.20557 | 8.35069 |
May | 508.00000 | 22.79136 | 46.97540 | -0.8615 | 23.81612 |
June | 496.00000 | 23.15652 | 51.21821 | -0.6907 | 17.08810 |
July | 497.00000 | 23.51148 | 53.75616 | -0.5251 | 12.52087 |
August | 514.00000 | 23.53679 | 54.81860 | -0.4729 | 11.83301 |
September | 485.00000 | 23.52293 | 51.18283 | -0.4921 | 13.72444 |
October | 502.00000 | 23.64513 | 41.93971 | 0.39901 | 11.18963 |
November | 489.00000 | 23.19088 | 38.18820 | 0.23690 | 9.64947 |
December | 497.00000 | 23.08621 | 32.93795 | 0.17994 | 9.76111 |
Annual Sum or Average | 5943.00000 | 23.12270 | 45.20811 | -0.1457 | 12.10727 |
Minimum of Months | 454.00000 | 22.45460 | 32.93795 | -0.8615 | 8.35069 |
Maximum of Months | 514.00000 | 23.64513 | 54.81860 | 0.39901 | 23.81612 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.68432 | 40.35100 | -0.1839 | 8.17217 |
February | 454.00000 | 21.73540 | 43.58555 | -0.1429 | 7.82198 |
March | 514.00000 | 21.79111 | 46.65100 | -0.1005 | 7.82664 |
April | 485.00000 | 22.52946 | 48.06255 | 0.13721 | 8.45990 |
May | 508.00000 | 22.67664 | 47.04450 | -0.8293 | 24.46297 |
June | 496.00000 | 23.08277 | 51.17056 | -0.6217 | 17.19382 |
July | 497.00000 | 23.45216 | 53.78270 | -0.4512 | 13.25025 |
August | 514.00000 | 23.26942 | 55.66332 | -0.4987 | 13.99257 |
September | 485.00000 | 22.98281 | 52.90453 | -0.6552 | 18.23482 |
October | 502.00000 | 22.78353 | 44.08518 | 0.17842 | 8.31131 |
November | 489.00000 | 22.02433 | 40.77572 | -0.0725 | 7.62196 |
December | 497.00000 | 21.69308 | 35.66078 | -0.2002 | 8.07403 |
Annual Sum or Average | 5943.00000 | 22.48043 | 46.67766 | -0.2887 | 11.99201 |
Minimum of Months | 454.00000 | 21.68432 | 35.66078 | -0.8293 | 7.62196 |
Maximum of Months | 514.00000 | 23.45216 | 55.66332 | 0.17842 | 24.46297 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.879070E+10 | 0.00 | 228.55 | 277437.36 | 09-JAN-06:11 | 0.00 | 27.36 | 37.21 | 0.03 | 0.00 | 0.01 | 0.91 | 09-JAN-06:11 |
February | 0.758857E+10 | 0.00 | 205.23 | 203286.68 | 13-FEB-07:03 | 0.00 | 26.48 | 36.07 | 0.03 | 0.00 | 0.01 | 0.67 | 13-FEB-07:03 |
March | 0.926608E+10 | 0.00 | 241.64 | 202087.88 | 27-MAR-06:03 | 0.00 | 28.23 | 37.91 | 0.03 | 0.00 | 0.01 | 0.66 | 27-MAR-06:03 |
April | 0.252381E+10 | 0.00 | 143.50 | 197647.21 | 01-APR-05:11 | 0.00 | 30.46 | 35.87 | 0.01 | 0.00 | 0.00 | 0.65 | 01-APR-05:11 |
May | 0.171530E+10 | 0.00 | 114.59 | 131996.28 | 10-MAY-06:03 | 0.00 | 30.66 | 34.91 | 0.01 | 0.00 | 0.00 | 0.43 | 10-MAY-06:03 |
June | 0.405168E+09 | 0.00 | 120.62 | 66605.30 | 01-JUN-06:03 | 0.00 | 29.21 | 34.48 | 0.00 | 0.00 | 0.00 | 0.22 | 01-JUN-06:03 |
July | 67529397.03 | 0.00 | 183.49 | 6292.12 | 17-JUL-06:10 | 0.00 | 25.81 | 34.28 | 0.00 | 0.00 | 0.00 | 0.02 | 17-JUL-06:10 |
August | 83306095.80 | 0.00 | 226.64 | 8722.61 | 28-AUG-06:10 | 0.00 | 25.52 | 36.01 | 0.00 | 0.00 | 0.00 | 0.03 | 28-AUG-06:10 |
September | 0.383782E+09 | 0.00 | 139.09 | 102876.75 | 20-SEP-06:03 | 0.00 | 25.50 | 32.07 | 0.00 | 0.00 | 0.00 | 0.34 | 20-SEP-06:03 |
October | 0.104529E+10 | 0.00 | 134.46 | 146254.30 | 25-OCT-06:03 | 0.00 | 26.55 | 32.44 | 0.00 | 0.00 | 0.00 | 0.48 | 25-OCT-06:03 |
November | 0.385150E+10 | 0.00 | 184.09 | 183781.24 | 06-NOV-07:03 | 0.00 | 25.83 | 34.00 | 0.01 | 0.00 | 0.00 | 0.60 | 06-NOV-07:03 |
December | 0.697199E+10 | 0.00 | 221.83 | 190759.60 | 27-DEC-07:03 | 0.00 | 25.62 | 35.22 | 0.02 | 0.00 | 0.01 | 0.63 | 27-DEC-07:03 |
Annual Sum or Average | 0.426930E+11 | 0.00 | 2143.72 | 0.00 | 27.27 | 35.04 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 67529397.03 | 0.00 | 114.59 | 6292.12 | 0.00 | 25.50 | 32.07 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.926608E+10 | 0.00 | 241.64 | 277437.36 | 0.00 | 30.66 | 37.91 | 0.03 | 0.00 | 0.01 | 0.91 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.124815E+11 | 0.304662E+10 | 215.61 | 0.112247E+11 | 0.125680E+10 | 0.00 | 1.00 | 13-JAN-11:30 | 0.00 | 01-JAN-00:10 | 50676.46 | 18-JAN-13:10 | 50676.46 | 18-JAN-13:10 | 9401.27 | 20-JAN-13:03 | 11776.81 | 18-JAN-13:10 | 0.00 |
February | 0.744842E+10 | 0.187326E+10 | 169.11 | 0.616223E+10 | 0.128620E+10 | 0.00 | 1.00 | 01-FEB-10:00 | 0.00 | 01-FEB-00:10 | 47571.52 | 01-FEB-12:00 | 47571.52 | 01-FEB-12:00 | 11047.55 | 01-FEB-16:00 | 11121.27 | 01-FEB-12:00 | 0.00 |
March | 0.916729E+10 | 0.224497E+10 | 167.36 | 0.695946E+10 | 0.220783E+10 | 0.00 | 1.00 | 10-MAR-12:00 | 0.00 | 01-MAR-00:10 | 54623.85 | 23-MAR-14:50 | 42067.14 | 23-MAR-14:10 | 16723.89 | 23-MAR-15:50 | 12173.73 | 23-MAR-14:50 | 0.00 |
April | 0.193015E+11 | 0.464226E+10 | 270.23 | 0.154379E+11 | 0.386361E+10 | 0.00 | 1.00 | 04-APR-12:05 | 0.00 | 01-APR-00:10 | 59280.92 | 26-APR-14:05 | 55719.13 | 26-APR-14:10 | 10503.24 | 13-APR-16:00 | 13705.36 | 26-APR-14:05 | 0.00 |
May | 0.202920E+11 | 0.494558E+10 | 321.39 | 0.162583E+11 | 0.403374E+10 | 0.00 | 1.00 | 02-MAY-13:00 | 0.00 | 01-MAY-00:10 | 47407.76 | 04-MAY-14:10 | 45539.93 | 03-MAY-13:10 | 15858.95 | 05-MAY-15:00 | 10516.38 | 04-MAY-14:10 | 0.00 |
June | 0.369623E+11 | 0.865990E+10 | 398.08 | 0.266894E+11 | 0.102729E+11 | 0.00 | 1.00 | 13-JUN-11:00 | 0.00 | 01-JUN-00:10 | 70485.02 | 28-JUN-10:50 | 48089.04 | 29-JUN-11:00 | 27299.93 | 28-JUN-10:50 | 15733.89 | 28-JUN-10:50 | 0.00 |
July | 0.587945E+11 | 0.135054E+11 | 428.74 | 0.395120E+11 | 0.192825E+11 | 0.00 | 1.00 | 01-JUL-10:05 | 0.00 | 01-JUL-00:10 | 84482.07 | 28-JUL-14:10 | 61850.99 | 31-JUL-14:20 | 40168.90 | 28-JUL-14:30 | 18812.21 | 28-JUL-14:10 | 0.00 |
August | 0.679523E+11 | 0.155403E+11 | 447.74 | 0.442041E+11 | 0.237482E+11 | 0.00 | 1.00 | 01-AUG-09:30 | 0.00 | 01-AUG-00:10 | 90194.42 | 15-AUG-16:00 | 64346.21 | 18-AUG-15:00 | 41996.33 | 15-AUG-16:00 | 20076.23 | 15-AUG-16:00 | 0.00 |
September | 0.438100E+11 | 0.103658E+11 | 391.59 | 0.304271E+11 | 0.133828E+11 | 0.00 | 1.00 | 01-SEP-10:05 | 0.00 | 01-SEP-00:10 | 78816.95 | 29-SEP-14:40 | 78816.95 | 29-SEP-14:40 | 43563.47 | 22-SEP-10:20 | 23989.02 | 29-SEP-13:00 | 0.00 |
October | 0.466706E+11 | 0.111374E+11 | 390.34 | 0.367900E+11 | 0.988063E+10 | 0.00 | 1.00 | 01-OCT-10:32 | 0.00 | 01-OCT-00:10 | 93155.32 | 04-OCT-10:50 | 81396.70 | 16-OCT-11:00 | 50118.44 | 05-OCT-05:12 | 26086.36 | 16-OCT-11:00 | 0.00 |
November | 0.140024E+11 | 0.342409E+10 | 244.17 | 0.121538E+11 | 0.184859E+10 | 0.00 | 1.00 | 08-NOV-10:30 | 0.00 | 01-NOV-00:10 | 49240.03 | 29-NOV-12:00 | 49240.03 | 29-NOV-12:00 | 11237.94 | 10-NOV-15:03 | 10970.75 | 29-NOV-12:00 | 0.00 |
December | 0.144690E+11 | 0.347414E+10 | 221.40 | 0.139227E+11 | 0.546366E+09 | 0.00 | 1.00 | 04-DEC-09:50 | 0.00 | 01-DEC-00:10 | 51663.61 | 19-DEC-12:00 | 51663.61 | 19-DEC-12:00 | 8796.55 | 07-DEC-15:30 | 11869.85 | 19-DEC-13:10 | 0.00 |
Annual Sum or Average | 0.351352E+12 | 0.828597E+11 | 3665.76 | 0.259742E+12 | 0.916102E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.744842E+10 | 0.187326E+10 | 167.36 | 0.616223E+10 | 0.546366E+09 | 0.00 | 1.00 | 0.00 | 47407.76 | 42067.14 | 8796.55 | 10516.38 | 0.00 | ||||||
Maximum of Months | 0.679523E+11 | 0.155403E+11 | 447.74 | 0.442041E+11 | 0.237482E+11 | 0.00 | 1.00 | 0.00 | 93155.32 | 81396.70 | 50118.44 | 26086.36 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.105765E+11 | 0.261027E+10 | 215.43 | 0.938085E+10 | 0.119563E+10 | 0.00 | 1.00 | 13-JAN-13:02 | 0.00 | 01-JAN-00:10 | 46303.50 | 18-JAN-13:03 | 46303.50 | 18-JAN-13:03 | 9607.27 | 20-JAN-13:03 | 10761.21 | 18-JAN-13:03 | 0.00 |
February | 0.630347E+10 | 0.159831E+10 | 167.70 | 0.518102E+10 | 0.112245E+10 | 0.00 | 1.00 | 01-FEB-11:05 | 0.00 | 01-FEB-00:10 | 39345.52 | 01-FEB-12:00 | 39345.52 | 01-FEB-12:00 | 9897.32 | 01-FEB-16:00 | 9200.46 | 01-FEB-12:00 | 0.00 |
March | 0.806423E+10 | 0.198062E+10 | 167.85 | 0.610802E+10 | 0.195621E+10 | 0.00 | 1.00 | 19-MAR-12:02 | 0.00 | 01-MAR-00:10 | 52232.98 | 23-MAR-14:05 | 40976.91 | 23-MAR-14:05 | 15546.28 | 23-MAR-15:40 | 11635.01 | 23-MAR-14:05 | 0.00 |
April | 0.174866E+11 | 0.422896E+10 | 275.62 | 0.139280E+11 | 0.355857E+10 | 0.00 | 1.00 | 04-APR-12:05 | 0.00 | 01-APR-00:10 | 57648.93 | 26-APR-14:05 | 54094.96 | 26-APR-14:05 | 9719.89 | 13-APR-16:00 | 13327.37 | 26-APR-14:05 | 0.00 |
May | 0.176922E+11 | 0.434608E+10 | 323.96 | 0.140186E+11 | 0.367356E+10 | 0.00 | 1.00 | 02-MAY-13:00 | 0.00 | 01-MAY-00:10 | 44844.71 | 04-MAY-14:05 | 43114.92 | 03-MAY-13:00 | 12998.78 | 05-MAY-15:00 | 9947.68 | 04-MAY-14:05 | 0.00 |
June | 0.327967E+11 | 0.772440E+10 | 400.10 | 0.235813E+11 | 0.921544E+10 | 0.00 | 1.00 | 13-JUN-14:05 | 0.00 | 01-JUN-00:10 | 64169.00 | 29-JUN-16:00 | 43491.63 | 21-JUN-13:00 | 24873.46 | 28-JUN-13:00 | 14330.91 | 29-JUN-16:00 | 0.00 |
July | 0.519163E+11 | 0.119819E+11 | 431.19 | 0.349533E+11 | 0.169629E+11 | 0.00 | 1.00 | 02-JUL-07:42 | 0.00 | 01-JUL-00:10 | 79402.42 | 28-JUL-14:05 | 58456.40 | 31-JUL-14:05 | 37208.49 | 28-JUL-14:05 | 17681.05 | 28-JUL-14:05 | 0.00 |
August | 0.601000E+11 | 0.137978E+11 | 450.21 | 0.391976E+11 | 0.209024E+11 | 0.00 | 1.00 | 01-AUG-09:40 | 0.00 | 01-AUG-00:10 | 82140.66 | 15-AUG-16:00 | 60733.76 | 17-AUG-14:05 | 38147.96 | 15-AUG-16:00 | 18285.60 | 15-AUG-16:00 | 0.00 |
September | 0.383496E+11 | 0.912984E+10 | 392.47 | 0.266862E+11 | 0.116634E+11 | 0.00 | 1.00 | 01-SEP-10:30 | 0.00 | 01-SEP-00:10 | 77393.93 | 29-SEP-14:05 | 77393.93 | 29-SEP-14:05 | 34802.62 | 22-SEP-10:20 | 23446.15 | 29-SEP-13:00 | 0.00 |
October | 0.401623E+11 | 0.966323E+10 | 389.64 | 0.317281E+11 | 0.843418E+10 | 0.00 | 1.00 | 01-OCT-10:36 | 0.00 | 01-OCT-00:10 | 81436.49 | 04-OCT-10:30 | 79368.63 | 16-OCT-12:02 | 38059.36 | 01-OCT-14:32 | 24491.24 | 16-OCT-11:00 | 0.00 |
November | 0.117317E+11 | 0.290205E+10 | 242.24 | 0.100735E+11 | 0.165824E+10 | 0.00 | 1.00 | 10-NOV-13:03 | 0.00 | 01-NOV-00:10 | 42494.01 | 28-NOV-14:00 | 42494.01 | 28-NOV-14:00 | 10219.36 | 10-NOV-13:03 | 10069.75 | 19-NOV-12:51 | 0.00 |
December | 0.122249E+11 | 0.296669E+10 | 218.02 | 0.117319E+11 | 0.492952E+09 | 0.00 | 1.00 | 05-DEC-09:40 | 0.00 | 01-DEC-00:10 | 46590.57 | 19-DEC-13:07 | 46590.57 | 19-DEC-13:07 | 9992.34 | 07-DEC-13:02 | 10756.73 | 19-DEC-13:07 | 0.00 |
Annual Sum or Average | 0.307404E+12 | 0.729302E+11 | 3674.45 | 0.226568E+12 | 0.808360E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.630347E+10 | 0.159831E+10 | 167.70 | 0.518102E+10 | 0.492952E+09 | 0.00 | 1.00 | 0.00 | 39345.52 | 39345.52 | 9607.27 | 9200.46 | 0.00 | ||||||
Maximum of Months | 0.601000E+11 | 0.137978E+11 | 450.21 | 0.391976E+11 | 0.209024E+11 | 0.00 | 1.00 | 0.00 | 82140.66 | 79368.63 | 38147.96 | 24491.24 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.112969E+11 | 0.282113E+10 | 211.77 | 0.987959E+10 | 0.141727E+10 | 0.00 | 1.00 | 13-JAN-13:02 | 0.00 | 01-JAN-00:10 | 53982.12 | 18-JAN-14:15 | 53982.12 | 18-JAN-14:15 | 9083.44 | 20-JAN-13:03 | 12096.81 | 18-JAN-14:02 | 0.00 |
February | 0.670064E+10 | 0.171928E+10 | 164.47 | 0.539931E+10 | 0.130133E+10 | 0.00 | 1.00 | 01-FEB-11:50 | 0.00 | 01-FEB-00:10 | 43921.08 | 01-FEB-13:05 | 43921.08 | 01-FEB-13:05 | 11052.63 | 01-FEB-16:00 | 10236.50 | 01-FEB-12:00 | 0.00 |
March | 0.885037E+10 | 0.218973E+10 | 164.90 | 0.660790E+10 | 0.224247E+10 | 0.00 | 1.00 | 22-MAR-12:20 | 0.00 | 01-MAR-00:10 | 56494.40 | 23-MAR-14:40 | 43944.66 | 23-MAR-14:00 | 17025.04 | 23-MAR-15:30 | 12591.73 | 23-MAR-14:40 | 0.00 |
April | 0.198769E+11 | 0.483000E+10 | 273.36 | 0.156276E+11 | 0.424922E+10 | 0.00 | 1.00 | 04-APR-12:30 | 0.00 | 01-APR-00:10 | 73689.84 | 26-APR-14:00 | 70294.16 | 26-APR-14:00 | 11087.39 | 11-APR-15:00 | 17315.84 | 26-APR-13:40 | 0.00 |
May | 0.199986E+11 | 0.493497E+10 | 321.19 | 0.155738E+11 | 0.442486E+10 | 0.00 | 1.00 | 02-MAY-13:05 | 0.00 | 01-MAY-00:10 | 60211.59 | 03-MAY-13:00 | 60211.59 | 03-MAY-13:00 | 13451.75 | 05-MAY-15:00 | 13442.07 | 03-MAY-13:00 | 0.00 |
June | 0.372058E+11 | 0.880115E+10 | 400.29 | 0.264815E+11 | 0.107243E+11 | 0.00 | 1.00 | 13-JUN-14:20 | 0.00 | 01-JUN-00:10 | 75528.19 | 29-JUN-13:20 | 60305.30 | 21-JUN-13:00 | 29359.11 | 28-JUN-13:00 | 16858.16 | 29-JUN-13:20 | 0.00 |
July | 0.595611E+11 | 0.138059E+11 | 434.09 | 0.407340E+11 | 0.188271E+11 | 0.00 | 1.00 | 03-JUL-10:05 | 0.00 | 01-JUL-00:10 | 88352.50 | 31-JUL-13:50 | 74090.98 | 31-JUL-13:50 | 41349.67 | 28-JUL-14:30 | 21240.73 | 31-JUL-13:05 | 0.00 |
August | 0.675478E+11 | 0.155691E+11 | 449.81 | 0.449207E+11 | 0.226270E+11 | 0.00 | 1.00 | 01-AUG-10:05 | 0.00 | 01-AUG-00:10 | 90374.24 | 15-AUG-16:00 | 75318.00 | 17-AUG-14:00 | 42030.38 | 15-AUG-16:00 | 21768.35 | 17-AUG-14:00 | 0.00 |
September | 0.414832E+11 | 0.997071E+10 | 391.14 | 0.286285E+11 | 0.128547E+11 | 0.00 | 1.00 | 01-SEP-12:30 | 0.00 | 01-SEP-00:10 | 92831.47 | 29-SEP-13:40 | 92831.47 | 29-SEP-13:40 | 34541.35 | 22-SEP-10:00 | 28609.75 | 29-SEP-13:00 | 0.00 |
October | 0.430237E+11 | 0.104722E+11 | 385.85 | 0.339612E+11 | 0.906254E+10 | 0.00 | 1.00 | 01-OCT-10:40 | 0.00 | 01-OCT-00:10 | 93069.23 | 16-OCT-13:05 | 93069.23 | 16-OCT-13:05 | 36541.62 | 04-OCT-10:50 | 28249.01 | 16-OCT-11:00 | 0.00 |
November | 0.121876E+11 | 0.305743E+10 | 237.82 | 0.103221E+11 | 0.186543E+10 | 0.00 | 1.00 | 19-NOV-10:12 | 0.00 | 01-NOV-00:10 | 58833.28 | 19-NOV-13:31 | 58833.28 | 19-NOV-13:31 | 11456.68 | 10-NOV-15:00 | 13958.93 | 19-NOV-12:51 | 0.00 |
December | 0.127092E+11 | 0.313375E+10 | 214.55 | 0.121377E+11 | 0.571417E+09 | 0.00 | 1.00 | 05-DEC-11:10 | 0.00 | 01-DEC-00:10 | 52650.87 | 19-DEC-13:10 | 52650.87 | 19-DEC-13:10 | 9265.24 | 07-DEC-13:00 | 12157.32 | 19-DEC-13:10 | 0.00 |
Annual Sum or Average | 0.340442E+12 | 0.813054E+11 | 3649.23 | 0.250274E+12 | 0.901677E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.670064E+10 | 0.171928E+10 | 164.47 | 0.539931E+10 | 0.571417E+09 | 0.00 | 1.00 | 0.00 | 43921.08 | 43921.08 | 9083.44 | 10236.50 | 0.00 | ||||||
Maximum of Months | 0.675478E+11 | 0.155691E+11 | 449.81 | 0.449207E+11 | 0.226270E+11 | 0.00 | 1.00 | 0.00 | 93069.23 | 93069.23 | 42030.38 | 28609.75 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 322.19 | 0.00 | 322.19 | 243.80 | 1771.75 | 0.00 | 0.00 | 0.00 |
February | 404.43 | 0.00 | 404.43 | 268.02 | 1666.04 | 4.67 | 0.00 | 0.00 |
March | 495.60 | 0.00 | 495.60 | 385.37 | 1739.45 | 8.50 | 0.00 | 0.00 |
April | 572.44 | 3.64 | 568.80 | 543.90 | 1352.63 | 2.83 | 0.00 | 0.00 |
May | 697.33 | 43.13 | 654.20 | 699.28 | 1185.17 | 0.00 | 0.00 | 0.00 |
June | 750.21 | 90.56 | 659.65 | 913.04 | 922.79 | 0.00 | 0.00 | 0.00 |
July | 710.16 | 75.92 | 634.24 | 1006.96 | 823.15 | 0.00 | 0.00 | 0.00 |
August | 580.43 | 17.04 | 563.39 | 804.14 | 865.17 | 0.00 | 0.00 | 0.00 |
September | 486.67 | 0.15 | 486.52 | 623.58 | 1014.14 | 0.00 | 0.00 | 0.00 |
October | 385.98 | 0.00 | 385.98 | 587.84 | 1127.40 | 0.00 | 0.00 | 0.00 |
November | 349.48 | 0.00 | 349.48 | 277.45 | 1621.57 | 5.33 | 0.00 | 0.00 |
December | 299.93 | 0.00 | 299.93 | 231.31 | 1781.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.01 | 19.31 | 485.70 | 550.59 | 1320.77 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 299.93 | 0.00 | 299.93 | 231.31 | 823.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 750.21 | 90.56 | 659.65 | 1006.96 | 1781.44 | 8.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 582.31 | 312.80 | 269.52 | 898.63 | 1104.13 | 0.00 | 0.00 | 0.00 |
February | 611.37 | 280.17 | 331.20 | 839.52 | 1052.14 | 4.67 | 0.00 | 0.00 |
March | 738.53 | 326.89 | 411.64 | 1076.89 | 1094.34 | 6.50 | 0.00 | 0.00 |
April | 945.92 | 472.78 | 473.14 | 1615.21 | 866.60 | 2.33 | 0.00 | 0.00 |
May | 893.35 | 371.42 | 521.93 | 1437.92 | 795.03 | 0.00 | 0.00 | 0.00 |
June | 889.87 | 385.93 | 503.94 | 1580.13 | 621.29 | 0.00 | 0.00 | 0.00 |
July | 1006.99 | 499.58 | 507.41 | 1969.05 | 554.67 | 0.00 | 0.00 | 0.00 |
August | 992.86 | 525.85 | 467.01 | 1973.70 | 566.50 | 0.00 | 0.00 | 0.00 |
September | 725.70 | 332.79 | 392.91 | 1357.98 | 641.37 | 0.00 | 0.00 | 0.00 |
October | 641.47 | 329.46 | 312.01 | 1232.04 | 710.76 | 0.00 | 0.00 | 0.00 |
November | 587.02 | 299.11 | 287.91 | 892.08 | 1020.32 | 5.50 | 0.00 | 0.00 |
December | 562.55 | 314.44 | 248.10 | 865.87 | 1109.23 | 0.17 | 0.00 | 0.00 |
Annual Sum or Average | 765.84 | 371.66 | 394.18 | 1314.92 | 843.62 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 562.55 | 280.17 | 248.10 | 839.52 | 554.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1006.99 | 525.85 | 521.93 | 1973.70 | 1109.23 | 6.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2081.82 | 1515.29 | 566.53 | 3980.97 | 1723.31 | 0.00 | 0.00 | 0.00 |
February | 1663.80 | 1022.02 | 641.78 | 2821.47 | 1635.19 | 4.17 | 0.00 | 0.00 |
March | 1364.92 | 676.21 | 688.70 | 2279.46 | 1742.57 | 5.83 | 0.00 | 0.00 |
April | 1193.19 | 504.51 | 688.68 | 2120.83 | 1409.53 | 2.33 | 0.00 | 0.00 |
May | 832.76 | 137.67 | 695.09 | 1142.45 | 1289.07 | 0.00 | 0.00 | 0.00 |
June | 720.15 | 66.78 | 653.36 | 1035.18 | 978.75 | 0.00 | 0.00 | 0.00 |
July | 776.61 | 122.96 | 653.65 | 1353.77 | 859.68 | 0.00 | 0.00 | 0.00 |
August | 1020.77 | 372.98 | 647.78 | 2054.38 | 905.88 | 0.00 | 0.00 | 0.00 |
September | 1376.49 | 727.00 | 649.49 | 2808.14 | 1038.26 | 0.00 | 0.00 | 0.00 |
October | 1681.82 | 1126.75 | 555.07 | 3538.04 | 1140.37 | 0.00 | 0.00 | 0.00 |
November | 2003.22 | 1404.82 | 598.40 | 3750.04 | 1595.00 | 4.83 | 0.00 | 0.00 |
December | 2218.40 | 1675.82 | 542.58 | 4252.60 | 1732.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1410.05 | 778.54 | 631.51 | 2594.74 | 1335.98 | 17.17 | 0.00 | 0.00 |
Minimum of Months | 720.15 | 66.78 | 542.58 | 1035.18 | 859.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2218.40 | 1675.82 | 695.09 | 4252.60 | 1742.57 | 5.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 555.05 | 281.71 | 273.33 | 872.68 | 1155.23 | 0.00 | 0.00 | 0.00 |
February | 656.27 | 302.08 | 354.19 | 946.26 | 1090.53 | 4.50 | 0.00 | 0.00 |
March | 750.77 | 330.27 | 420.50 | 1103.56 | 1134.42 | 6.33 | 0.00 | 0.00 |
April | 1034.45 | 536.16 | 498.29 | 1758.19 | 916.15 | 2.00 | 0.00 | 0.00 |
May | 1016.55 | 467.03 | 549.53 | 1641.79 | 835.59 | 0.00 | 0.00 | 0.00 |
June | 1076.02 | 535.05 | 540.96 | 1887.93 | 647.59 | 0.00 | 0.00 | 0.00 |
July | 1139.32 | 606.87 | 532.44 | 2169.18 | 584.21 | 0.00 | 0.00 | 0.00 |
August | 1068.68 | 576.52 | 492.16 | 2072.15 | 605.60 | 0.00 | 0.00 | 0.00 |
September | 915.16 | 487.46 | 427.70 | 1703.17 | 673.56 | 0.00 | 0.00 | 0.00 |
October | 702.05 | 382.74 | 319.31 | 1377.71 | 745.42 | 0.00 | 0.00 | 0.00 |
November | 636.79 | 333.82 | 302.97 | 1026.96 | 1058.26 | 5.50 | 0.00 | 0.00 |
December | 564.83 | 304.70 | 260.12 | 920.85 | 1162.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 843.73 | 429.25 | 414.48 | 1459.39 | 883.07 | 18.33 | 0.00 | 0.00 |
Minimum of Months | 555.05 | 281.71 | 260.12 | 872.68 | 584.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1139.32 | 606.87 | 549.53 | 2169.18 | 1162.68 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.39 | 0.00 | 107.39 | 81.58 | 636.09 | 0.67 | 0.00 | 0.00 |
February | 134.81 | 0.00 | 134.81 | 95.88 | 585.48 | 2.83 | 0.00 | 0.00 |
March | 165.19 | 0.00 | 165.19 | 141.15 | 602.19 | 9.33 | 0.00 | 0.00 |
April | 190.80 | 1.21 | 189.59 | 202.93 | 463.27 | 3.33 | 0.00 | 0.00 |
May | 232.44 | 14.38 | 218.06 | 253.31 | 412.13 | 0.00 | 0.00 | 0.00 |
June | 250.06 | 30.19 | 219.87 | 330.42 | 318.23 | 0.00 | 0.00 | 0.00 |
July | 236.71 | 25.31 | 211.41 | 358.43 | 286.87 | 0.00 | 0.00 | 0.00 |
August | 193.47 | 5.68 | 187.79 | 286.80 | 301.27 | 0.00 | 0.00 | 0.00 |
September | 162.22 | 0.05 | 162.17 | 218.45 | 361.31 | 0.00 | 0.00 | 0.00 |
October | 128.66 | 0.00 | 128.66 | 198.86 | 409.61 | 0.00 | 0.00 | 0.00 |
November | 116.49 | 0.00 | 116.49 | 92.45 | 586.22 | 3.67 | 0.00 | 0.00 |
December | 99.97 | 0.00 | 99.97 | 76.33 | 640.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 168.33 | 6.44 | 161.89 | 195.35 | 466.34 | 19.83 | 0.00 | 0.00 |
Minimum of Months | 99.97 | 0.00 | 99.97 | 76.33 | 286.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.06 | 30.19 | 219.87 | 358.43 | 640.50 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 0.00 | 107.40 | 81.59 | 636.12 | 0.67 | 0.00 | 0.00 |
February | 134.81 | 0.00 | 134.81 | 95.89 | 585.51 | 2.83 | 0.00 | 0.00 |
March | 165.20 | 0.00 | 165.20 | 141.16 | 602.23 | 9.33 | 0.00 | 0.00 |
April | 190.81 | 1.21 | 189.60 | 202.94 | 463.30 | 3.33 | 0.00 | 0.00 |
May | 232.45 | 14.38 | 218.07 | 253.32 | 412.16 | 0.00 | 0.00 | 0.00 |
June | 250.07 | 30.19 | 219.89 | 330.43 | 318.25 | 0.00 | 0.00 | 0.00 |
July | 236.72 | 25.31 | 211.42 | 358.45 | 286.88 | 0.00 | 0.00 | 0.00 |
August | 193.48 | 5.68 | 187.80 | 286.81 | 301.28 | 0.00 | 0.00 | 0.00 |
September | 162.23 | 0.05 | 162.18 | 218.46 | 361.33 | 0.00 | 0.00 | 0.00 |
October | 128.66 | 0.00 | 128.66 | 198.87 | 409.64 | 0.00 | 0.00 | 0.00 |
November | 116.49 | 0.00 | 116.49 | 92.46 | 586.26 | 3.67 | 0.00 | 0.00 |
December | 99.98 | 0.00 | 99.98 | 76.34 | 640.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 168.34 | 6.44 | 161.90 | 195.36 | 466.36 | 19.83 | 0.00 | 0.00 |
Minimum of Months | 99.98 | 0.00 | 99.98 | 76.34 | 286.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.07 | 30.19 | 219.89 | 358.45 | 640.53 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 0.00 | 107.40 | 81.59 | 636.12 | 0.67 | 0.00 | 0.00 |
February | 134.81 | 0.00 | 134.81 | 95.89 | 585.51 | 2.83 | 0.00 | 0.00 |
March | 165.20 | 0.00 | 165.20 | 141.16 | 602.23 | 9.33 | 0.00 | 0.00 |
April | 190.81 | 1.21 | 189.60 | 202.94 | 463.30 | 3.33 | 0.00 | 0.00 |
May | 232.45 | 14.38 | 218.07 | 253.32 | 412.16 | 0.00 | 0.00 | 0.00 |
June | 250.07 | 30.19 | 219.89 | 330.43 | 318.25 | 0.00 | 0.00 | 0.00 |
July | 236.72 | 25.31 | 211.42 | 358.45 | 286.88 | 0.00 | 0.00 | 0.00 |
August | 193.48 | 5.68 | 187.80 | 286.81 | 301.28 | 0.00 | 0.00 | 0.00 |
September | 162.23 | 0.05 | 162.18 | 218.46 | 361.33 | 0.00 | 0.00 | 0.00 |
October | 128.66 | 0.00 | 128.66 | 198.87 | 409.64 | 0.00 | 0.00 | 0.00 |
November | 116.49 | 0.00 | 116.49 | 92.46 | 586.26 | 3.67 | 0.00 | 0.00 |
December | 99.98 | 0.00 | 99.98 | 76.34 | 640.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 168.34 | 6.44 | 161.90 | 195.36 | 466.36 | 19.83 | 0.00 | 0.00 |
Minimum of Months | 99.98 | 0.00 | 99.98 | 76.34 | 286.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.07 | 30.19 | 219.89 | 358.45 | 640.53 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.18 | 300.91 | 259.27 | 863.08 | 1163.81 | 1.17 | 0.00 | 0.00 |
February | 588.13 | 269.52 | 318.61 | 830.49 | 1082.67 | 1.83 | 0.00 | 0.00 |
March | 710.46 | 314.47 | 395.99 | 1067.08 | 1111.96 | 6.00 | 0.00 | 0.00 |
April | 909.97 | 454.81 | 455.16 | 1599.63 | 885.95 | 2.33 | 0.00 | 0.00 |
May | 859.40 | 357.31 | 502.09 | 1427.57 | 808.21 | 0.00 | 0.00 | 0.00 |
June | 856.05 | 371.26 | 484.79 | 1570.01 | 626.58 | 0.00 | 0.00 | 0.00 |
July | 968.72 | 480.60 | 488.13 | 1938.26 | 577.74 | 0.00 | 0.00 | 0.00 |
August | 955.13 | 505.87 | 449.26 | 1939.89 | 593.68 | 0.00 | 0.00 | 0.00 |
September | 698.12 | 320.14 | 377.97 | 1332.77 | 674.79 | 0.00 | 0.00 | 0.00 |
October | 617.10 | 316.94 | 300.16 | 1201.12 | 756.62 | 0.00 | 0.00 | 0.00 |
November | 564.71 | 287.74 | 276.97 | 860.79 | 1074.85 | 3.17 | 0.00 | 0.00 |
December | 541.17 | 302.49 | 238.67 | 833.09 | 1165.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 736.74 | 357.54 | 379.20 | 1291.84 | 875.82 | 14.50 | 0.00 | 0.00 |
Minimum of Months | 541.17 | 269.52 | 238.67 | 830.49 | 577.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 968.72 | 505.87 | 502.09 | 1939.89 | 1165.21 | 6.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.15 | 11.90 | 10.25 | 34.13 | 46.02 | 1.17 | 0.00 | 0.00 |
February | 23.25 | 10.66 | 12.60 | 32.84 | 42.81 | 1.83 | 0.00 | 0.00 |
March | 28.09 | 12.43 | 15.66 | 42.19 | 43.97 | 6.00 | 0.00 | 0.00 |
April | 35.98 | 17.98 | 18.00 | 63.25 | 35.03 | 2.33 | 0.00 | 0.00 |
May | 33.98 | 14.13 | 19.85 | 56.44 | 31.96 | 0.00 | 0.00 | 0.00 |
June | 33.85 | 14.68 | 19.17 | 62.08 | 24.77 | 0.00 | 0.00 | 0.00 |
July | 38.30 | 19.00 | 19.30 | 76.64 | 22.84 | 0.00 | 0.00 | 0.00 |
August | 37.76 | 20.00 | 17.76 | 76.70 | 23.47 | 0.00 | 0.00 | 0.00 |
September | 27.60 | 12.66 | 14.94 | 52.70 | 26.68 | 0.00 | 0.00 | 0.00 |
October | 24.40 | 12.53 | 11.87 | 47.49 | 29.92 | 0.00 | 0.00 | 0.00 |
November | 22.33 | 11.38 | 10.95 | 34.03 | 42.50 | 3.17 | 0.00 | 0.00 |
December | 21.40 | 11.96 | 9.44 | 32.94 | 46.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.13 | 14.14 | 14.99 | 51.08 | 34.63 | 14.50 | 0.00 | 0.00 |
Minimum of Months | 21.40 | 10.66 | 9.44 | 32.84 | 22.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.30 | 20.00 | 19.85 | 76.70 | 46.07 | 6.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 693.96 | 505.11 | 188.85 | 1337.04 | 660.04 | 0.83 | 0.00 | 0.00 |
February | 554.61 | 340.68 | 213.93 | 966.36 | 604.39 | 0.83 | 0.00 | 0.00 |
March | 454.98 | 225.41 | 229.57 | 786.17 | 620.69 | 4.67 | 0.00 | 0.00 |
April | 397.74 | 168.17 | 229.56 | 735.39 | 495.65 | 1.83 | 0.00 | 0.00 |
May | 277.59 | 45.89 | 231.70 | 412.82 | 440.45 | 0.00 | 0.00 | 0.00 |
June | 240.05 | 22.26 | 217.79 | 375.73 | 328.60 | 0.00 | 0.00 | 0.00 |
July | 258.88 | 40.99 | 217.89 | 475.13 | 296.94 | 0.00 | 0.00 | 0.00 |
August | 340.26 | 124.33 | 215.93 | 707.53 | 321.95 | 0.00 | 0.00 | 0.00 |
September | 458.84 | 242.34 | 216.50 | 955.56 | 386.33 | 0.00 | 0.00 | 0.00 |
October | 560.62 | 375.59 | 185.03 | 1194.23 | 437.91 | 0.00 | 0.00 | 0.00 |
November | 667.76 | 468.29 | 199.47 | 1265.84 | 612.02 | 2.67 | 0.00 | 0.00 |
December | 739.49 | 558.62 | 180.87 | 1430.69 | 666.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 470.03 | 259.52 | 210.51 | 886.81 | 488.67 | 10.83 | 0.00 | 0.00 |
Minimum of Months | 240.05 | 22.26 | 180.87 | 375.73 | 296.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 739.49 | 558.62 | 231.70 | 1430.69 | 666.05 | 4.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 693.96 | 505.11 | 188.85 | 1337.04 | 660.04 | 0.83 | 0.00 | 0.00 |
February | 554.61 | 340.68 | 213.93 | 966.36 | 604.39 | 0.83 | 0.00 | 0.00 |
March | 454.98 | 225.41 | 229.57 | 786.17 | 620.69 | 4.67 | 0.00 | 0.00 |
April | 397.74 | 168.17 | 229.56 | 735.39 | 495.65 | 1.83 | 0.00 | 0.00 |
May | 277.59 | 45.89 | 231.70 | 412.82 | 440.45 | 0.00 | 0.00 | 0.00 |
June | 240.05 | 22.26 | 217.79 | 375.73 | 328.60 | 0.00 | 0.00 | 0.00 |
July | 258.88 | 40.99 | 217.89 | 475.13 | 296.94 | 0.00 | 0.00 | 0.00 |
August | 340.26 | 124.33 | 215.93 | 707.53 | 321.95 | 0.00 | 0.00 | 0.00 |
September | 458.84 | 242.34 | 216.50 | 955.56 | 386.33 | 0.00 | 0.00 | 0.00 |
October | 560.62 | 375.59 | 185.03 | 1194.23 | 437.91 | 0.00 | 0.00 | 0.00 |
November | 667.76 | 468.29 | 199.47 | 1265.84 | 612.02 | 2.67 | 0.00 | 0.00 |
December | 739.49 | 558.62 | 180.87 | 1430.69 | 666.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 470.03 | 259.52 | 210.51 | 886.81 | 488.67 | 10.83 | 0.00 | 0.00 |
Minimum of Months | 240.05 | 22.26 | 180.87 | 375.73 | 296.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 739.49 | 558.62 | 231.70 | 1430.69 | 666.05 | 4.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 693.92 | 505.08 | 188.84 | 1336.96 | 660.00 | 0.83 | 0.00 | 0.00 |
February | 554.58 | 340.66 | 213.92 | 966.30 | 604.36 | 0.83 | 0.00 | 0.00 |
March | 454.96 | 225.40 | 229.56 | 786.12 | 620.65 | 4.67 | 0.00 | 0.00 |
April | 397.71 | 168.16 | 229.55 | 735.34 | 495.62 | 1.83 | 0.00 | 0.00 |
May | 277.57 | 45.89 | 231.69 | 412.80 | 440.42 | 0.00 | 0.00 | 0.00 |
June | 240.04 | 22.26 | 217.78 | 375.70 | 328.58 | 0.00 | 0.00 | 0.00 |
July | 258.86 | 40.99 | 217.87 | 475.10 | 296.92 | 0.00 | 0.00 | 0.00 |
August | 340.24 | 124.32 | 215.92 | 707.48 | 321.93 | 0.00 | 0.00 | 0.00 |
September | 458.81 | 242.32 | 216.49 | 955.50 | 386.30 | 0.00 | 0.00 | 0.00 |
October | 560.58 | 375.57 | 185.02 | 1194.16 | 437.88 | 0.00 | 0.00 | 0.00 |
November | 667.71 | 468.26 | 199.46 | 1265.76 | 611.98 | 2.67 | 0.00 | 0.00 |
December | 739.44 | 558.59 | 180.85 | 1430.60 | 666.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 470.00 | 259.50 | 210.49 | 886.75 | 488.64 | 10.83 | 0.00 | 0.00 |
Minimum of Months | 240.04 | 22.26 | 180.85 | 375.70 | 296.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 739.44 | 558.59 | 231.69 | 1430.60 | 666.01 | 4.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 533.95 | 271.01 | 262.95 | 865.45 | 1219.94 | 1.17 | 0.00 | 0.00 |
February | 631.33 | 290.60 | 340.72 | 954.10 | 1131.89 | 1.50 | 0.00 | 0.00 |
March | 722.24 | 317.72 | 404.51 | 1117.65 | 1162.07 | 5.33 | 0.00 | 0.00 |
April | 995.13 | 515.78 | 479.35 | 1765.67 | 945.90 | 2.00 | 0.00 | 0.00 |
May | 977.92 | 449.28 | 528.64 | 1652.79 | 864.47 | 0.00 | 0.00 | 0.00 |
June | 1035.12 | 514.72 | 520.40 | 1894.57 | 668.52 | 0.00 | 0.00 | 0.00 |
July | 1096.02 | 583.81 | 512.21 | 2151.84 | 617.92 | 0.00 | 0.00 | 0.00 |
August | 1028.06 | 554.61 | 473.45 | 2055.35 | 641.89 | 0.00 | 0.00 | 0.00 |
September | 880.38 | 468.94 | 411.44 | 1686.80 | 724.02 | 0.00 | 0.00 | 0.00 |
October | 675.37 | 368.20 | 307.17 | 1354.22 | 800.71 | 0.00 | 0.00 | 0.00 |
November | 612.59 | 321.13 | 291.46 | 1015.95 | 1126.38 | 3.33 | 0.00 | 0.00 |
December | 543.36 | 293.12 | 250.24 | 909.60 | 1228.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 811.67 | 412.94 | 398.72 | 1454.57 | 926.69 | 13.33 | 0.00 | 0.00 |
Minimum of Months | 533.95 | 271.01 | 250.24 | 865.45 | 617.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1096.02 | 583.81 | 528.64 | 2151.84 | 1228.63 | 5.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.11 | 10.72 | 10.40 | 34.22 | 48.24 | 1.17 | 0.00 | 0.00 |
February | 24.96 | 11.49 | 13.47 | 37.72 | 44.75 | 1.50 | 0.00 | 0.00 |
March | 28.56 | 12.56 | 15.99 | 44.19 | 45.95 | 5.33 | 0.00 | 0.00 |
April | 39.35 | 20.39 | 18.95 | 69.81 | 37.40 | 2.00 | 0.00 | 0.00 |
May | 38.67 | 17.76 | 20.90 | 65.35 | 34.18 | 0.00 | 0.00 | 0.00 |
June | 40.93 | 20.35 | 20.58 | 74.91 | 26.43 | 0.00 | 0.00 | 0.00 |
July | 43.34 | 23.08 | 20.25 | 85.08 | 24.43 | 0.00 | 0.00 | 0.00 |
August | 40.65 | 21.93 | 18.72 | 81.27 | 25.38 | 0.00 | 0.00 | 0.00 |
September | 34.81 | 18.54 | 16.27 | 66.69 | 28.63 | 0.00 | 0.00 | 0.00 |
October | 26.70 | 14.56 | 12.15 | 53.54 | 31.66 | 0.00 | 0.00 | 0.00 |
November | 24.22 | 12.70 | 11.52 | 40.17 | 44.54 | 3.33 | 0.00 | 0.00 |
December | 21.48 | 11.59 | 9.89 | 35.96 | 48.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.09 | 16.33 | 15.77 | 57.51 | 36.64 | 13.33 | 0.00 | 0.00 |
Minimum of Months | 21.11 | 10.72 | 9.89 | 34.22 | 24.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.34 | 23.08 | 20.90 | 85.08 | 48.58 | 5.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 322.19 | 0.00 | 322.19 | 219.40 | 1941.87 | 0.00 | 0.00 | 0.00 |
February | 404.43 | 0.00 | 404.43 | 246.27 | 1820.91 | 3.17 | 0.00 | 0.00 |
March | 495.60 | 0.00 | 495.60 | 367.85 | 1874.47 | 8.33 | 0.00 | 0.00 |
April | 572.44 | 3.64 | 568.80 | 542.43 | 1453.19 | 3.33 | 0.00 | 0.00 |
May | 697.33 | 43.13 | 654.20 | 691.38 | 1273.68 | 0.00 | 0.00 | 0.00 |
June | 750.21 | 90.56 | 659.65 | 917.47 | 987.89 | 0.00 | 0.00 | 0.00 |
July | 710.16 | 75.92 | 634.24 | 1019.25 | 880.27 | 0.00 | 0.00 | 0.00 |
August | 580.43 | 17.04 | 563.39 | 811.27 | 930.49 | 0.00 | 0.00 | 0.00 |
September | 486.67 | 0.15 | 486.52 | 617.13 | 1107.01 | 0.00 | 0.00 | 0.00 |
October | 385.98 | 0.00 | 385.98 | 571.19 | 1239.97 | 0.00 | 0.00 | 0.00 |
November | 349.48 | 0.00 | 349.48 | 250.66 | 1784.89 | 3.17 | 0.00 | 0.00 |
December | 299.93 | 0.00 | 299.93 | 205.64 | 1959.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.01 | 19.31 | 485.70 | 540.25 | 1435.84 | 18.00 | 0.00 | 0.00 |
Minimum of Months | 299.93 | 0.00 | 299.93 | 205.64 | 880.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 750.21 | 90.56 | 659.65 | 1019.25 | 1959.51 | 8.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 582.31 | 312.80 | 269.52 | 862.15 | 1203.35 | 0.00 | 0.00 | 0.00 |
February | 611.37 | 280.17 | 331.20 | 812.96 | 1140.62 | 4.17 | 0.00 | 0.00 |
March | 738.53 | 326.89 | 411.64 | 1052.59 | 1170.27 | 6.00 | 0.00 | 0.00 |
April | 945.92 | 472.78 | 473.14 | 1611.05 | 917.07 | 2.33 | 0.00 | 0.00 |
May | 893.35 | 371.42 | 521.93 | 1428.41 | 839.29 | 0.00 | 0.00 | 0.00 |
June | 889.87 | 385.93 | 503.94 | 1578.70 | 654.09 | 0.00 | 0.00 | 0.00 |
July | 1006.99 | 499.58 | 507.41 | 1978.05 | 584.23 | 0.00 | 0.00 | 0.00 |
August | 992.86 | 525.85 | 467.01 | 1979.88 | 598.79 | 0.00 | 0.00 | 0.00 |
September | 725.70 | 332.79 | 392.91 | 1351.84 | 689.09 | 0.00 | 0.00 | 0.00 |
October | 641.47 | 329.46 | 312.01 | 1217.10 | 768.26 | 0.00 | 0.00 | 0.00 |
November | 587.02 | 299.11 | 287.91 | 859.09 | 1110.38 | 3.00 | 0.00 | 0.00 |
December | 562.55 | 314.44 | 248.10 | 829.07 | 1211.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 765.84 | 371.66 | 394.18 | 1300.13 | 906.08 | 15.50 | 0.00 | 0.00 |
Minimum of Months | 562.55 | 280.17 | 248.10 | 812.96 | 584.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1006.99 | 525.85 | 521.93 | 1979.88 | 1211.97 | 6.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2081.82 | 1515.29 | 566.53 | 3960.03 | 1872.02 | 0.00 | 0.00 | 0.00 |
February | 1663.80 | 1022.02 | 641.78 | 2813.92 | 1774.63 | 2.33 | 0.00 | 0.00 |
March | 1364.92 | 676.21 | 688.70 | 2272.26 | 1867.35 | 5.83 | 0.00 | 0.00 |
April | 1193.19 | 504.51 | 688.68 | 2130.61 | 1502.63 | 2.33 | 0.00 | 0.00 |
May | 832.76 | 137.67 | 695.09 | 1150.19 | 1373.55 | 0.00 | 0.00 | 0.00 |
June | 720.15 | 66.78 | 653.36 | 1042.41 | 1042.06 | 0.00 | 0.00 | 0.00 |
July | 776.61 | 122.96 | 653.65 | 1367.29 | 915.55 | 0.00 | 0.00 | 0.00 |
August | 1020.77 | 372.98 | 647.78 | 2068.76 | 968.89 | 0.00 | 0.00 | 0.00 |
September | 1376.49 | 727.00 | 649.49 | 2815.91 | 1123.09 | 0.00 | 0.00 | 0.00 |
October | 1681.82 | 1126.75 | 555.07 | 3537.04 | 1239.06 | 0.00 | 0.00 | 0.00 |
November | 2003.22 | 1404.82 | 598.40 | 3737.32 | 1735.51 | 2.67 | 0.00 | 0.00 |
December | 2218.40 | 1675.82 | 542.58 | 4233.35 | 1885.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1410.05 | 778.54 | 631.51 | 2594.06 | 1439.87 | 13.17 | 0.00 | 0.00 |
Minimum of Months | 720.15 | 66.78 | 542.58 | 1042.41 | 915.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2218.40 | 1675.82 | 695.09 | 4233.35 | 1885.02 | 5.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 555.05 | 281.71 | 273.33 | 868.56 | 1256.34 | 0.00 | 0.00 | 0.00 |
February | 656.27 | 302.08 | 354.19 | 947.16 | 1182.33 | 3.33 | 0.00 | 0.00 |
March | 750.77 | 330.27 | 420.50 | 1109.34 | 1215.42 | 5.17 | 0.00 | 0.00 |
April | 1034.45 | 536.16 | 498.29 | 1778.05 | 976.87 | 2.00 | 0.00 | 0.00 |
May | 1016.55 | 467.03 | 549.53 | 1660.52 | 890.87 | 0.00 | 0.00 | 0.00 |
June | 1076.02 | 535.05 | 540.96 | 1909.57 | 690.81 | 0.00 | 0.00 | 0.00 |
July | 1139.32 | 606.87 | 532.44 | 2192.99 | 624.56 | 0.00 | 0.00 | 0.00 |
August | 1068.68 | 576.52 | 492.16 | 2093.31 | 648.19 | 0.00 | 0.00 | 0.00 |
September | 915.16 | 487.46 | 427.70 | 1715.23 | 729.39 | 0.00 | 0.00 | 0.00 |
October | 702.05 | 382.74 | 319.31 | 1379.91 | 810.16 | 0.00 | 0.00 | 0.00 |
November | 636.79 | 333.82 | 302.97 | 1025.07 | 1151.09 | 3.17 | 0.00 | 0.00 |
December | 564.83 | 304.70 | 260.12 | 916.44 | 1266.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 843.73 | 429.25 | 414.48 | 1469.07 | 952.39 | 13.67 | 0.00 | 0.00 |
Minimum of Months | 555.05 | 281.71 | 260.12 | 868.56 | 624.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1139.32 | 606.87 | 549.53 | 2192.99 | 1266.47 | 5.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862955E+09 | 0.00 | 0.862955E+09 | 0.652994E+09 | 0.474545E+10 |
February | 0.978409E+09 | 0.00 | 0.978409E+09 | 0.648402E+09 | 0.403048E+10 |
March | 0.132742E+10 | 0.00 | 0.132742E+10 | 0.103218E+10 | 0.465894E+10 |
April | 0.148376E+10 | 9436248.24 | 0.147432E+10 | 0.140980E+10 | 0.350601E+10 |
May | 0.186774E+10 | 0.115524E+09 | 0.175221E+10 | 0.187296E+10 | 0.317437E+10 |
June | 0.194455E+10 | 0.234737E+09 | 0.170981E+10 | 0.236660E+10 | 0.239186E+10 |
July | 0.190210E+10 | 0.203348E+09 | 0.169875E+10 | 0.269704E+10 | 0.220472E+10 |
August | 0.155463E+10 | 45639358.80 | 0.150899E+10 | 0.215381E+10 | 0.231727E+10 |
September | 0.126145E+10 | 389802.64 | 0.126106E+10 | 0.161632E+10 | 0.262866E+10 |
October | 0.103382E+10 | 0.00 | 0.103382E+10 | 0.157447E+10 | 0.301962E+10 |
November | 0.905854E+09 | 0.00 | 0.905854E+09 | 0.719146E+09 | 0.420312E+10 |
December | 0.803337E+09 | 0.00 | 0.803337E+09 | 0.619529E+09 | 0.477141E+10 |
Annual Sum or Average | 0.159260E+11 | 0.609074E+09 | 0.153169E+11 | 0.173633E+11 | 0.416519E+11 |
Minimum of Months | 0.803337E+09 | 0.00 | 0.803337E+09 | 0.619529E+09 | 0.220472E+10 |
Maximum of Months | 0.194455E+10 | 0.234737E+09 | 0.175221E+10 | 0.269704E+10 | 0.477141E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155966E+10 | 0.837793E+09 | 0.721869E+09 | 0.240688E+10 | 0.295731E+10 |
February | 0.147902E+10 | 0.677783E+09 | 0.801235E+09 | 0.203097E+10 | 0.254533E+10 |
March | 0.197808E+10 | 0.875552E+09 | 0.110252E+10 | 0.288435E+10 | 0.293109E+10 |
April | 0.245182E+10 | 0.122544E+10 | 0.122639E+10 | 0.418663E+10 | 0.224624E+10 |
May | 0.239275E+10 | 0.994813E+09 | 0.139794E+10 | 0.385134E+10 | 0.212942E+10 |
June | 0.230654E+10 | 0.100033E+10 | 0.130621E+10 | 0.409569E+10 | 0.161038E+10 |
July | 0.269713E+10 | 0.133807E+10 | 0.135906E+10 | 0.527391E+10 | 0.148562E+10 |
August | 0.265928E+10 | 0.140845E+10 | 0.125083E+10 | 0.528636E+10 | 0.151730E+10 |
September | 0.188101E+10 | 0.862587E+09 | 0.101842E+10 | 0.351988E+10 | 0.166243E+10 |
October | 0.171813E+10 | 0.882425E+09 | 0.835700E+09 | 0.329989E+10 | 0.190371E+10 |
November | 0.152155E+10 | 0.775285E+09 | 0.746262E+09 | 0.231228E+10 | 0.264467E+10 |
December | 0.150672E+10 | 0.842202E+09 | 0.664519E+09 | 0.231916E+10 | 0.297096E+10 |
Annual Sum or Average | 0.241517E+11 | 0.117207E+11 | 0.124310E+11 | 0.414673E+11 | 0.266044E+11 |
Minimum of Months | 0.147902E+10 | 0.677783E+09 | 0.664519E+09 | 0.203097E+10 | 0.148562E+10 |
Maximum of Months | 0.269713E+10 | 0.140845E+10 | 0.139794E+10 | 0.528636E+10 | 0.297096E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.557596E+10 | 0.405855E+10 | 0.151740E+10 | 0.106626E+11 | 0.461571E+10 |
February | 0.402507E+10 | 0.247247E+10 | 0.155260E+10 | 0.682569E+10 | 0.395585E+10 |
March | 0.365579E+10 | 0.181117E+10 | 0.184463E+10 | 0.610532E+10 | 0.466730E+10 |
April | 0.309274E+10 | 0.130768E+10 | 0.178505E+10 | 0.549719E+10 | 0.365351E+10 |
May | 0.223045E+10 | 0.368737E+09 | 0.186172E+10 | 0.305994E+10 | 0.345263E+10 |
June | 0.186662E+10 | 0.173097E+09 | 0.169352E+10 | 0.268319E+10 | 0.253693E+10 |
July | 0.208007E+10 | 0.329341E+09 | 0.175073E+10 | 0.362593E+10 | 0.230255E+10 |
August | 0.273402E+10 | 0.998998E+09 | 0.173502E+10 | 0.550245E+10 | 0.242630E+10 |
September | 0.356786E+10 | 0.188437E+10 | 0.168349E+10 | 0.727870E+10 | 0.269118E+10 |
October | 0.450457E+10 | 0.301787E+10 | 0.148670E+10 | 0.947630E+10 | 0.305437E+10 |
November | 0.519234E+10 | 0.364130E+10 | 0.155104E+10 | 0.972011E+10 | 0.413424E+10 |
December | 0.594177E+10 | 0.448852E+10 | 0.145325E+10 | 0.113902E+11 | 0.464075E+10 |
Annual Sum or Average | 0.444673E+11 | 0.245521E+11 | 0.199152E+11 | 0.818276E+11 | 0.421313E+11 |
Minimum of Months | 0.186662E+10 | 0.173097E+09 | 0.145325E+10 | 0.268319E+10 | 0.230255E+10 |
Maximum of Months | 0.594177E+10 | 0.448852E+10 | 0.186172E+10 | 0.113902E+11 | 0.466730E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148664E+10 | 0.754544E+09 | 0.732099E+09 | 0.233739E+10 | 0.309416E+10 |
February | 0.158765E+10 | 0.730798E+09 | 0.856848E+09 | 0.228919E+10 | 0.263820E+10 |
March | 0.201086E+10 | 0.884601E+09 | 0.112626E+10 | 0.295577E+10 | 0.303842E+10 |
April | 0.268129E+10 | 0.138971E+10 | 0.129158E+10 | 0.455723E+10 | 0.237467E+10 |
May | 0.272274E+10 | 0.125088E+10 | 0.147186E+10 | 0.439736E+10 | 0.223804E+10 |
June | 0.278904E+10 | 0.138686E+10 | 0.140218E+10 | 0.489352E+10 | 0.167856E+10 |
July | 0.305154E+10 | 0.162545E+10 | 0.142610E+10 | 0.580993E+10 | 0.156476E+10 |
August | 0.286234E+10 | 0.154415E+10 | 0.131820E+10 | 0.555005E+10 | 0.162205E+10 |
September | 0.237209E+10 | 0.126349E+10 | 0.110860E+10 | 0.441462E+10 | 0.174587E+10 |
October | 0.188037E+10 | 0.102513E+10 | 0.855244E+09 | 0.369006E+10 | 0.199654E+10 |
November | 0.165056E+10 | 0.865257E+09 | 0.785305E+09 | 0.266189E+10 | 0.274301E+10 |
December | 0.151283E+10 | 0.816111E+09 | 0.696719E+09 | 0.246642E+10 | 0.311411E+10 |
Annual Sum or Average | 0.266080E+11 | 0.135370E+11 | 0.130710E+11 | 0.460234E+11 | 0.278484E+11 |
Minimum of Months | 0.148664E+10 | 0.730798E+09 | 0.696719E+09 | 0.228919E+10 | 0.156476E+10 |
Maximum of Months | 0.305154E+10 | 0.162545E+10 | 0.147186E+10 | 0.580993E+10 | 0.311411E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287641E+09 | 0.00 | 0.287641E+09 | 0.218517E+09 | 0.170369E+10 |
February | 0.326124E+09 | 0.00 | 0.326124E+09 | 0.231961E+09 | 0.141639E+10 |
March | 0.442458E+09 | 0.00 | 0.442458E+09 | 0.378061E+09 | 0.161291E+10 |
April | 0.494566E+09 | 3145316.91 | 0.491421E+09 | 0.525993E+09 | 0.120080E+10 |
May | 0.622555E+09 | 38506642.93 | 0.584049E+09 | 0.678469E+09 | 0.110386E+10 |
June | 0.648159E+09 | 78243181.45 | 0.569916E+09 | 0.856447E+09 | 0.824860E+09 |
July | 0.634010E+09 | 67780532.82 | 0.566229E+09 | 0.960021E+09 | 0.768345E+09 |
August | 0.518189E+09 | 15212639.97 | 0.502976E+09 | 0.768158E+09 | 0.806911E+09 |
September | 0.420467E+09 | 129930.12 | 0.420337E+09 | 0.566222E+09 | 0.936504E+09 |
October | 0.344593E+09 | 0.00 | 0.344593E+09 | 0.532614E+09 | 0.109711E+10 |
November | 0.301940E+09 | 0.00 | 0.301940E+09 | 0.239639E+09 | 0.151948E+10 |
December | 0.267769E+09 | 0.00 | 0.267769E+09 | 0.204450E+09 | 0.171550E+10 |
Annual Sum or Average | 0.530847E+10 | 0.203018E+09 | 0.510545E+10 | 0.616055E+10 | 0.147064E+11 |
Minimum of Months | 0.267769E+09 | 0.00 | 0.267769E+09 | 0.204450E+09 | 0.768345E+09 |
Maximum of Months | 0.648159E+09 | 78243181.45 | 0.584049E+09 | 0.960021E+09 | 0.171550E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287655E+09 | 0.00 | 0.287655E+09 | 0.218526E+09 | 0.170379E+10 |
February | 0.326140E+09 | 0.00 | 0.326140E+09 | 0.231969E+09 | 0.141648E+10 |
March | 0.442479E+09 | 0.00 | 0.442479E+09 | 0.378075E+09 | 0.161301E+10 |
April | 0.494591E+09 | 3145438.37 | 0.491446E+09 | 0.526018E+09 | 0.120087E+10 |
May | 0.622585E+09 | 38508129.80 | 0.584077E+09 | 0.678495E+09 | 0.110393E+10 |
June | 0.648190E+09 | 78246202.68 | 0.569944E+09 | 0.856483E+09 | 0.824910E+09 |
July | 0.634041E+09 | 67783150.05 | 0.566258E+09 | 0.960066E+09 | 0.768391E+09 |
August | 0.518215E+09 | 15213227.38 | 0.503002E+09 | 0.768197E+09 | 0.806959E+09 |
September | 0.420488E+09 | 129935.13 | 0.420358E+09 | 0.566250E+09 | 0.936560E+09 |
October | 0.344610E+09 | 0.00 | 0.344610E+09 | 0.532641E+09 | 0.109717E+10 |
November | 0.301955E+09 | 0.00 | 0.301955E+09 | 0.239649E+09 | 0.151958E+10 |
December | 0.267782E+09 | 0.00 | 0.267782E+09 | 0.204459E+09 | 0.171561E+10 |
Annual Sum or Average | 0.530873E+10 | 0.203026E+09 | 0.510570E+10 | 0.616083E+10 | 0.147073E+11 |
Minimum of Months | 0.267782E+09 | 0.00 | 0.267782E+09 | 0.204459E+09 | 0.768391E+09 |
Maximum of Months | 0.648190E+09 | 78246202.68 | 0.584077E+09 | 0.960066E+09 | 0.171561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287655E+09 | 0.00 | 0.287655E+09 | 0.218526E+09 | 0.170379E+10 |
February | 0.326140E+09 | 0.00 | 0.326140E+09 | 0.231969E+09 | 0.141648E+10 |
March | 0.442479E+09 | 0.00 | 0.442479E+09 | 0.378075E+09 | 0.161301E+10 |
April | 0.494591E+09 | 3145438.37 | 0.491446E+09 | 0.526018E+09 | 0.120087E+10 |
May | 0.622585E+09 | 38508129.80 | 0.584077E+09 | 0.678495E+09 | 0.110393E+10 |
June | 0.648190E+09 | 78246202.68 | 0.569944E+09 | 0.856483E+09 | 0.824910E+09 |
July | 0.634041E+09 | 67783150.05 | 0.566258E+09 | 0.960066E+09 | 0.768391E+09 |
August | 0.518215E+09 | 15213227.38 | 0.503002E+09 | 0.768197E+09 | 0.806959E+09 |
September | 0.420488E+09 | 129935.13 | 0.420358E+09 | 0.566250E+09 | 0.936560E+09 |
October | 0.344610E+09 | 0.00 | 0.344610E+09 | 0.532641E+09 | 0.109717E+10 |
November | 0.301955E+09 | 0.00 | 0.301955E+09 | 0.239649E+09 | 0.151958E+10 |
December | 0.267782E+09 | 0.00 | 0.267782E+09 | 0.204459E+09 | 0.171561E+10 |
Annual Sum or Average | 0.530873E+10 | 0.203026E+09 | 0.510570E+10 | 0.616083E+10 | 0.147073E+11 |
Minimum of Months | 0.267782E+09 | 0.00 | 0.267782E+09 | 0.204459E+09 | 0.768391E+09 |
Maximum of Months | 0.648190E+09 | 78246202.68 | 0.584077E+09 | 0.960066E+09 | 0.171561E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150039E+10 | 0.805960E+09 | 0.694433E+09 | 0.231167E+10 | 0.311714E+10 |
February | 0.142281E+10 | 0.652030E+09 | 0.770782E+09 | 0.200912E+10 | 0.261920E+10 |
March | 0.190290E+10 | 0.842284E+09 | 0.106062E+10 | 0.285806E+10 | 0.297828E+10 |
April | 0.235865E+10 | 0.117887E+10 | 0.117977E+10 | 0.414624E+10 | 0.229637E+10 |
May | 0.230182E+10 | 0.957014E+09 | 0.134480E+10 | 0.382360E+10 | 0.216472E+10 |
June | 0.221888E+10 | 0.962317E+09 | 0.125657E+10 | 0.406946E+10 | 0.162410E+10 |
July | 0.259463E+10 | 0.128723E+10 | 0.130740E+10 | 0.519144E+10 | 0.154743E+10 |
August | 0.255822E+10 | 0.135493E+10 | 0.120329E+10 | 0.519579E+10 | 0.159012E+10 |
September | 0.180952E+10 | 0.829812E+09 | 0.979710E+09 | 0.345454E+10 | 0.174905E+10 |
October | 0.165283E+10 | 0.848897E+09 | 0.803936E+09 | 0.321709E+10 | 0.202653E+10 |
November | 0.146373E+10 | 0.745827E+09 | 0.717899E+09 | 0.223116E+10 | 0.278602E+10 |
December | 0.144946E+10 | 0.810202E+09 | 0.639262E+09 | 0.223136E+10 | 0.312089E+10 |
Annual Sum or Average | 0.232339E+11 | 0.112754E+11 | 0.119585E+11 | 0.407395E+11 | 0.276198E+11 |
Minimum of Months | 0.142281E+10 | 0.652030E+09 | 0.639262E+09 | 0.200912E+10 | 0.154743E+10 |
Maximum of Months | 0.259463E+10 | 0.135493E+10 | 0.134480E+10 | 0.519579E+10 | 0.312089E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59324172.17 | 31866916.92 | 27457255.25 | 91401370.37 | 0.123249E+09 |
February | 56256706.25 | 25780663.45 | 30476042.80 | 79438819.14 | 0.103561E+09 |
March | 75239139.43 | 33303154.31 | 41935985.12 | 0.113005E+09 | 0.117758E+09 |
April | 93258736.44 | 46611616.77 | 46647119.67 | 0.163939E+09 | 90796579.10 |
May | 91011828.56 | 37839453.16 | 53172375.40 | 0.151182E+09 | 85591111.08 |
June | 87732595.42 | 38049145.96 | 49683449.46 | 0.160903E+09 | 64215354.55 |
July | 0.102589E+09 | 50895871.32 | 51693495.96 | 0.205265E+09 | 61183983.48 |
August | 0.101150E+09 | 53572861.05 | 47576897.56 | 0.205437E+09 | 62871937.19 |
September | 71546862.59 | 32810007.37 | 38736855.22 | 0.136590E+09 | 69155709.09 |
October | 65351522.76 | 33564605.67 | 31786917.08 | 0.127201E+09 | 80127118.69 |
November | 57874402.03 | 29489329.29 | 28385072.73 | 88218121.92 | 0.110157E+09 |
December | 57310485.80 | 32034646.76 | 25275839.04 | 88225793.87 | 0.123397E+09 |
Annual Sum or Average | 0.918646E+09 | 0.445818E+09 | 0.472827E+09 | 0.161080E+10 | 0.109206E+10 |
Minimum of Months | 56256706.25 | 25780663.45 | 25275839.04 | 79438819.14 | 61183983.48 |
Maximum of Months | 0.102589E+09 | 53572861.05 | 53172375.40 | 0.205437E+09 | 0.123397E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185870E+10 | 0.135289E+10 | 0.505814E+09 | 0.358113E+10 | 0.176786E+10 |
February | 0.134172E+10 | 0.824179E+09 | 0.517545E+09 | 0.233782E+10 | 0.146215E+10 |
March | 0.121863E+10 | 0.603739E+09 | 0.614890E+09 | 0.210567E+10 | 0.166246E+10 |
April | 0.103094E+10 | 0.435906E+09 | 0.595032E+09 | 0.190613E+10 | 0.128472E+10 |
May | 0.743502E+09 | 0.122916E+09 | 0.620586E+09 | 0.110571E+10 | 0.117970E+10 |
June | 0.622221E+09 | 57700617.36 | 0.564520E+09 | 0.973882E+09 | 0.851724E+09 |
July | 0.693374E+09 | 0.109783E+09 | 0.583590E+09 | 0.127258E+10 | 0.795313E+09 |
August | 0.911362E+09 | 0.333009E+09 | 0.578353E+09 | 0.189504E+10 | 0.862319E+09 |
September | 0.118932E+10 | 0.628141E+09 | 0.561175E+09 | 0.247681E+10 | 0.100136E+10 |
October | 0.150156E+10 | 0.100599E+10 | 0.495578E+09 | 0.319863E+10 | 0.117289E+10 |
November | 0.173083E+10 | 0.121380E+10 | 0.517027E+09 | 0.328105E+10 | 0.158636E+10 |
December | 0.198064E+10 | 0.149621E+10 | 0.484429E+09 | 0.383197E+10 | 0.178395E+10 |
Annual Sum or Average | 0.148228E+11 | 0.818426E+10 | 0.663854E+10 | 0.279664E+11 | 0.154108E+11 |
Minimum of Months | 0.622221E+09 | 57700617.36 | 0.484429E+09 | 0.973882E+09 | 0.795313E+09 |
Maximum of Months | 0.198064E+10 | 0.149621E+10 | 0.620586E+09 | 0.383197E+10 | 0.178395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185870E+10 | 0.135289E+10 | 0.505814E+09 | 0.358113E+10 | 0.176786E+10 |
February | 0.134172E+10 | 0.824179E+09 | 0.517545E+09 | 0.233782E+10 | 0.146215E+10 |
March | 0.121863E+10 | 0.603739E+09 | 0.614890E+09 | 0.210567E+10 | 0.166246E+10 |
April | 0.103094E+10 | 0.435906E+09 | 0.595032E+09 | 0.190613E+10 | 0.128472E+10 |
May | 0.743502E+09 | 0.122916E+09 | 0.620586E+09 | 0.110571E+10 | 0.117970E+10 |
June | 0.622221E+09 | 57700617.36 | 0.564520E+09 | 0.973882E+09 | 0.851724E+09 |
July | 0.693374E+09 | 0.109783E+09 | 0.583590E+09 | 0.127258E+10 | 0.795313E+09 |
August | 0.911362E+09 | 0.333009E+09 | 0.578353E+09 | 0.189504E+10 | 0.862319E+09 |
September | 0.118932E+10 | 0.628141E+09 | 0.561175E+09 | 0.247681E+10 | 0.100136E+10 |
October | 0.150156E+10 | 0.100599E+10 | 0.495578E+09 | 0.319863E+10 | 0.117289E+10 |
November | 0.173083E+10 | 0.121380E+10 | 0.517027E+09 | 0.328105E+10 | 0.158636E+10 |
December | 0.198064E+10 | 0.149621E+10 | 0.484429E+09 | 0.383197E+10 | 0.178395E+10 |
Annual Sum or Average | 0.148228E+11 | 0.818426E+10 | 0.663854E+10 | 0.279664E+11 | 0.154108E+11 |
Minimum of Months | 0.622221E+09 | 57700617.36 | 0.484429E+09 | 0.973882E+09 | 0.795313E+09 |
Maximum of Months | 0.198064E+10 | 0.149621E+10 | 0.620586E+09 | 0.383197E+10 | 0.178395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185858E+10 | 0.135280E+10 | 0.505782E+09 | 0.358091E+10 | 0.176774E+10 |
February | 0.134164E+10 | 0.824127E+09 | 0.517512E+09 | 0.233768E+10 | 0.146206E+10 |
March | 0.121855E+10 | 0.603701E+09 | 0.614851E+09 | 0.210554E+10 | 0.166236E+10 |
April | 0.103087E+10 | 0.435879E+09 | 0.594994E+09 | 0.190601E+10 | 0.128463E+10 |
May | 0.743455E+09 | 0.122908E+09 | 0.620547E+09 | 0.110564E+10 | 0.117963E+10 |
June | 0.622181E+09 | 57696971.01 | 0.564484E+09 | 0.973821E+09 | 0.851670E+09 |
July | 0.693330E+09 | 0.109777E+09 | 0.583554E+09 | 0.127250E+10 | 0.795263E+09 |
August | 0.911304E+09 | 0.332987E+09 | 0.578317E+09 | 0.189492E+10 | 0.862264E+09 |
September | 0.118924E+10 | 0.628101E+09 | 0.561140E+09 | 0.247665E+10 | 0.100129E+10 |
October | 0.150147E+10 | 0.100592E+10 | 0.495547E+09 | 0.319843E+10 | 0.117282E+10 |
November | 0.173072E+10 | 0.121372E+10 | 0.516994E+09 | 0.328084E+10 | 0.158626E+10 |
December | 0.198052E+10 | 0.149612E+10 | 0.484399E+09 | 0.383173E+10 | 0.178384E+10 |
Annual Sum or Average | 0.148219E+11 | 0.818374E+10 | 0.663812E+10 | 0.279647E+11 | 0.154098E+11 |
Minimum of Months | 0.622181E+09 | 57696971.01 | 0.484399E+09 | 0.973821E+09 | 0.795263E+09 |
Maximum of Months | 0.198052E+10 | 0.149612E+10 | 0.620547E+09 | 0.383173E+10 | 0.178384E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143014E+10 | 0.725872E+09 | 0.704272E+09 | 0.231803E+10 | 0.326749E+10 |
February | 0.152731E+10 | 0.703028E+09 | 0.824281E+09 | 0.230816E+10 | 0.273827E+10 |
March | 0.193443E+10 | 0.850986E+09 | 0.108345E+10 | 0.299351E+10 | 0.311248E+10 |
April | 0.257939E+10 | 0.133691E+10 | 0.124248E+10 | 0.457661E+10 | 0.245176E+10 |
May | 0.261926E+10 | 0.120335E+10 | 0.141591E+10 | 0.442684E+10 | 0.231539E+10 |
June | 0.268304E+10 | 0.133416E+10 | 0.134888E+10 | 0.491072E+10 | 0.173280E+10 |
July | 0.293557E+10 | 0.156368E+10 | 0.137189E+10 | 0.576350E+10 | 0.165504E+10 |
August | 0.275356E+10 | 0.148547E+10 | 0.126809E+10 | 0.550505E+10 | 0.171924E+10 |
September | 0.228194E+10 | 0.121548E+10 | 0.106646E+10 | 0.437218E+10 | 0.187665E+10 |
October | 0.180891E+10 | 0.986173E+09 | 0.822736E+09 | 0.362715E+10 | 0.214463E+10 |
November | 0.158783E+10 | 0.832378E+09 | 0.755456E+09 | 0.263334E+10 | 0.291958E+10 |
December | 0.145534E+10 | 0.785100E+09 | 0.670237E+09 | 0.243628E+10 | 0.329075E+10 |
Annual Sum or Average | 0.255967E+11 | 0.130226E+11 | 0.125741E+11 | 0.458714E+11 | 0.292241E+11 |
Minimum of Months | 0.143014E+10 | 0.703028E+09 | 0.670237E+09 | 0.230816E+10 | 0.165504E+10 |
Maximum of Months | 0.293557E+10 | 0.156368E+10 | 0.141591E+10 | 0.576350E+10 | 0.329075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56546586.61 | 28700305.94 | 27846280.67 | 91652949.01 | 0.129194E+09 |
February | 60388431.78 | 27797097.90 | 32591333.88 | 91262755.16 | 0.108269E+09 |
March | 76485798.52 | 33647235.24 | 42838563.28 | 0.118361E+09 | 0.123065E+09 |
April | 0.101987E+09 | 52860060.97 | 49126628.37 | 0.180955E+09 | 96940424.47 |
May | 0.103563E+09 | 47579349.51 | 55983918.66 | 0.175033E+09 | 91548521.29 |
June | 0.106085E+09 | 52751336.18 | 53333604.43 | 0.194165E+09 | 68513174.97 |
July | 0.116070E+09 | 61826539.42 | 54243309.62 | 0.227884E+09 | 65438783.94 |
August | 0.108873E+09 | 58734240.96 | 50139099.61 | 0.217665E+09 | 67977217.19 |
September | 90225930.53 | 48059003.84 | 42166926.70 | 0.172872E+09 | 74201091.35 |
October | 71522648.20 | 38992411.97 | 32530236.23 | 0.143414E+09 | 84796803.14 |
November | 62781545.26 | 32911479.26 | 29870066.00 | 0.104120E+09 | 0.115438E+09 |
December | 57542693.68 | 31042138.25 | 26500555.43 | 96328168.44 | 0.130113E+09 |
Annual Sum or Average | 0.101207E+10 | 0.514901E+09 | 0.497171E+09 | 0.181371E+10 | 0.115549E+10 |
Minimum of Months | 56546586.61 | 27797097.90 | 26500555.43 | 91262755.16 | 65438783.94 |
Maximum of Months | 0.116070E+09 | 61826539.42 | 55983918.66 | 0.227884E+09 | 0.130113E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.862955E+09 | 0.00 | 0.862955E+09 | 0.587639E+09 | 0.520111E+10 |
February | 0.978409E+09 | 0.00 | 0.978409E+09 | 0.595770E+09 | 0.440516E+10 |
March | 0.132742E+10 | 0.00 | 0.132742E+10 | 0.985253E+09 | 0.502058E+10 |
April | 0.148376E+10 | 9436248.24 | 0.147432E+10 | 0.140598E+10 | 0.376666E+10 |
May | 0.186774E+10 | 0.115524E+09 | 0.175221E+10 | 0.185180E+10 | 0.341143E+10 |
June | 0.194455E+10 | 0.234737E+09 | 0.170981E+10 | 0.237809E+10 | 0.256062E+10 |
July | 0.190210E+10 | 0.203348E+09 | 0.169875E+10 | 0.272995E+10 | 0.235770E+10 |
August | 0.155463E+10 | 45639358.80 | 0.150899E+10 | 0.217290E+10 | 0.249222E+10 |
September | 0.126145E+10 | 389802.64 | 0.126106E+10 | 0.159959E+10 | 0.286937E+10 |
October | 0.103382E+10 | 0.00 | 0.103382E+10 | 0.152989E+10 | 0.332114E+10 |
November | 0.905854E+09 | 0.00 | 0.905854E+09 | 0.649722E+09 | 0.462643E+10 |
December | 0.803337E+09 | 0.00 | 0.803337E+09 | 0.550784E+09 | 0.524836E+10 |
Annual Sum or Average | 0.159260E+11 | 0.609074E+09 | 0.153169E+11 | 0.170374E+11 | 0.452808E+11 |
Minimum of Months | 0.803337E+09 | 0.00 | 0.803337E+09 | 0.550784E+09 | 0.235770E+10 |
Maximum of Months | 0.194455E+10 | 0.234737E+09 | 0.175221E+10 | 0.272995E+10 | 0.524836E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.155966E+10 | 0.837793E+09 | 0.721869E+09 | 0.230917E+10 | 0.322305E+10 |
February | 0.147902E+10 | 0.677783E+09 | 0.801235E+09 | 0.196671E+10 | 0.275940E+10 |
March | 0.197808E+10 | 0.875552E+09 | 0.110252E+10 | 0.281925E+10 | 0.313445E+10 |
April | 0.245182E+10 | 0.122544E+10 | 0.122639E+10 | 0.417583E+10 | 0.237704E+10 |
May | 0.239275E+10 | 0.994813E+09 | 0.139794E+10 | 0.382584E+10 | 0.224795E+10 |
June | 0.230654E+10 | 0.100033E+10 | 0.130621E+10 | 0.409198E+10 | 0.169540E+10 |
July | 0.269713E+10 | 0.133807E+10 | 0.135906E+10 | 0.529801E+10 | 0.156481E+10 |
August | 0.265928E+10 | 0.140845E+10 | 0.125083E+10 | 0.530292E+10 | 0.160379E+10 |
September | 0.188101E+10 | 0.862587E+09 | 0.101842E+10 | 0.350396E+10 | 0.178612E+10 |
October | 0.171813E+10 | 0.882425E+09 | 0.835700E+09 | 0.325988E+10 | 0.205772E+10 |
November | 0.152155E+10 | 0.775285E+09 | 0.746262E+09 | 0.222675E+10 | 0.287811E+10 |
December | 0.150672E+10 | 0.842202E+09 | 0.664519E+09 | 0.222058E+10 | 0.324615E+10 |
Annual Sum or Average | 0.241517E+11 | 0.117207E+11 | 0.124310E+11 | 0.410009E+11 | 0.285740E+11 |
Minimum of Months | 0.147902E+10 | 0.677783E+09 | 0.664519E+09 | 0.196671E+10 | 0.156481E+10 |
Maximum of Months | 0.269713E+10 | 0.140845E+10 | 0.139794E+10 | 0.530292E+10 | 0.324615E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.557596E+10 | 0.405855E+10 | 0.151740E+10 | 0.106065E+11 | 0.501402E+10 |
February | 0.402507E+10 | 0.247247E+10 | 0.155260E+10 | 0.680743E+10 | 0.429318E+10 |
March | 0.365579E+10 | 0.181117E+10 | 0.184463E+10 | 0.608603E+10 | 0.500151E+10 |
April | 0.309274E+10 | 0.130768E+10 | 0.178505E+10 | 0.552255E+10 | 0.389481E+10 |
May | 0.223045E+10 | 0.368737E+09 | 0.186172E+10 | 0.308067E+10 | 0.367890E+10 |
June | 0.186662E+10 | 0.173097E+09 | 0.169352E+10 | 0.270193E+10 | 0.270103E+10 |
July | 0.208007E+10 | 0.329341E+09 | 0.175073E+10 | 0.366214E+10 | 0.245221E+10 |
August | 0.273402E+10 | 0.998998E+09 | 0.173502E+10 | 0.554096E+10 | 0.259508E+10 |
September | 0.356786E+10 | 0.188437E+10 | 0.168349E+10 | 0.729883E+10 | 0.291105E+10 |
October | 0.450457E+10 | 0.301787E+10 | 0.148670E+10 | 0.947360E+10 | 0.331870E+10 |
November | 0.519234E+10 | 0.364130E+10 | 0.155104E+10 | 0.968714E+10 | 0.449845E+10 |
December | 0.594177E+10 | 0.448852E+10 | 0.145325E+10 | 0.113386E+11 | 0.504885E+10 |
Annual Sum or Average | 0.444673E+11 | 0.245521E+11 | 0.199152E+11 | 0.818064E+11 | 0.454078E+11 |
Minimum of Months | 0.186662E+10 | 0.173097E+09 | 0.145325E+10 | 0.270193E+10 | 0.245221E+10 |
Maximum of Months | 0.594177E+10 | 0.448852E+10 | 0.186172E+10 | 0.113386E+11 | 0.504885E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148664E+10 | 0.754544E+09 | 0.732099E+09 | 0.232634E+10 | 0.336498E+10 |
February | 0.158765E+10 | 0.730798E+09 | 0.856848E+09 | 0.229138E+10 | 0.286029E+10 |
March | 0.201086E+10 | 0.884601E+09 | 0.112626E+10 | 0.297126E+10 | 0.325538E+10 |
April | 0.268129E+10 | 0.138971E+10 | 0.129158E+10 | 0.460871E+10 | 0.253204E+10 |
May | 0.272274E+10 | 0.125088E+10 | 0.147186E+10 | 0.444754E+10 | 0.238610E+10 |
June | 0.278904E+10 | 0.138686E+10 | 0.140218E+10 | 0.494961E+10 | 0.179058E+10 |
July | 0.305154E+10 | 0.162545E+10 | 0.142610E+10 | 0.587371E+10 | 0.167281E+10 |
August | 0.286234E+10 | 0.154415E+10 | 0.131820E+10 | 0.560671E+10 | 0.173612E+10 |
September | 0.237209E+10 | 0.126349E+10 | 0.110860E+10 | 0.444588E+10 | 0.189058E+10 |
October | 0.188037E+10 | 0.102513E+10 | 0.855244E+09 | 0.369594E+10 | 0.216992E+10 |
November | 0.165056E+10 | 0.865257E+09 | 0.785305E+09 | 0.265697E+10 | 0.298362E+10 |
December | 0.151283E+10 | 0.816111E+09 | 0.696719E+09 | 0.245459E+10 | 0.339212E+10 |
Annual Sum or Average | 0.266080E+11 | 0.135370E+11 | 0.130710E+11 | 0.463286E+11 | 0.300345E+11 |
Minimum of Months | 0.148664E+10 | 0.730798E+09 | 0.696719E+09 | 0.229138E+10 | 0.167281E+10 |
Maximum of Months | 0.305154E+10 | 0.162545E+10 | 0.147186E+10 | 0.587371E+10 | 0.339212E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 243.80 | 1771.75 | 322.19 | 0.00 | 322.19 | 0.00 | 0.00 |
February | 268.02 | 1666.04 | 404.43 | 0.00 | 404.43 | 0.00 | 0.00 |
March | 385.37 | 1739.45 | 495.60 | 0.00 | 495.60 | 0.00 | 0.00 |
April | 543.90 | 1352.63 | 572.44 | 3.64 | 568.80 | 0.00 | 0.00 |
May | 699.28 | 1185.17 | 697.33 | 43.13 | 654.20 | 0.00 | 0.00 |
June | 913.04 | 922.79 | 750.21 | 90.56 | 659.65 | 0.00 | 0.00 |
July | 1006.96 | 823.15 | 710.16 | 75.92 | 634.24 | 0.00 | 0.00 |
August | 804.14 | 865.17 | 580.43 | 17.04 | 563.39 | 0.00 | 0.00 |
September | 623.58 | 1014.14 | 486.67 | 0.15 | 486.52 | 0.00 | 0.00 |
October | 587.84 | 1127.40 | 385.98 | 0.00 | 385.98 | 0.00 | 0.00 |
November | 277.45 | 1621.57 | 349.48 | 0.00 | 349.48 | 0.00 | 0.00 |
December | 231.31 | 1781.44 | 299.93 | 0.00 | 299.93 | 0.00 | 0.00 |
Annual Sum or Average | 550.59 | 1320.77 | 505.01 | 19.31 | 485.70 | 0.00 | 0.00 |
Minimum of Months | 231.31 | 823.15 | 299.93 | 0.00 | 299.93 | 0.00 | 0.00 |
Maximum of Months | 1006.96 | 1781.44 | 750.21 | 90.56 | 659.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 898.63 | 1104.13 | 582.31 | 312.80 | 269.52 | 0.00 | 0.00 |
February | 839.52 | 1052.14 | 611.37 | 280.17 | 331.20 | 0.00 | 0.00 |
March | 1076.89 | 1094.34 | 738.53 | 326.89 | 411.64 | 0.00 | 0.00 |
April | 1615.21 | 866.60 | 945.92 | 472.78 | 473.14 | 0.00 | 0.00 |
May | 1437.92 | 795.03 | 893.35 | 371.42 | 521.93 | 0.00 | 0.00 |
June | 1580.13 | 621.29 | 889.87 | 385.93 | 503.94 | 0.00 | 0.00 |
July | 1969.05 | 554.67 | 1006.99 | 499.58 | 507.41 | 0.00 | 0.00 |
August | 1973.70 | 566.50 | 992.86 | 525.85 | 467.01 | 0.00 | 0.00 |
September | 1357.98 | 641.37 | 725.70 | 332.79 | 392.91 | 0.00 | 0.00 |
October | 1232.04 | 710.76 | 641.47 | 329.46 | 312.01 | 0.00 | 0.00 |
November | 892.08 | 1020.32 | 587.02 | 299.11 | 287.91 | 0.00 | 0.00 |
December | 865.87 | 1109.23 | 562.55 | 314.44 | 248.10 | 0.00 | 0.00 |
Annual Sum or Average | 1314.92 | 843.62 | 765.84 | 371.66 | 394.18 | 0.00 | 0.00 |
Minimum of Months | 839.52 | 554.67 | 562.55 | 280.17 | 248.10 | 0.00 | 0.00 |
Maximum of Months | 1973.70 | 1109.23 | 1006.99 | 525.85 | 521.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3980.97 | 1723.31 | 2081.82 | 1515.29 | 566.53 | 0.00 | 0.00 |
February | 2821.47 | 1635.19 | 1663.80 | 1022.02 | 641.78 | 0.00 | 0.00 |
March | 2279.46 | 1742.57 | 1364.92 | 676.21 | 688.70 | 0.00 | 0.00 |
April | 2120.83 | 1409.53 | 1193.19 | 504.51 | 688.68 | 0.00 | 0.00 |
May | 1142.45 | 1289.07 | 832.76 | 137.67 | 695.09 | 0.00 | 0.00 |
June | 1035.18 | 978.75 | 720.15 | 66.78 | 653.36 | 0.00 | 0.00 |
July | 1353.77 | 859.68 | 776.61 | 122.96 | 653.65 | 0.00 | 0.00 |
August | 2054.38 | 905.88 | 1020.77 | 372.98 | 647.78 | 0.00 | 0.00 |
September | 2808.14 | 1038.26 | 1376.49 | 727.00 | 649.49 | 0.00 | 0.00 |
October | 3538.04 | 1140.37 | 1681.82 | 1126.75 | 555.07 | 0.00 | 0.00 |
November | 3750.04 | 1595.00 | 2003.22 | 1404.82 | 598.40 | 0.00 | 0.00 |
December | 4252.60 | 1732.66 | 2218.40 | 1675.82 | 542.58 | 0.00 | 0.00 |
Annual Sum or Average | 2594.74 | 1335.98 | 1410.05 | 778.54 | 631.51 | 0.00 | 0.00 |
Minimum of Months | 1035.18 | 859.68 | 720.15 | 66.78 | 542.58 | 0.00 | 0.00 |
Maximum of Months | 4252.60 | 1742.57 | 2218.40 | 1675.82 | 695.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 872.68 | 1155.23 | 555.05 | 281.71 | 273.33 | 0.00 | 0.00 |
February | 946.26 | 1090.53 | 656.27 | 302.08 | 354.19 | 0.00 | 0.00 |
March | 1103.56 | 1134.42 | 750.77 | 330.27 | 420.50 | 0.00 | 0.00 |
April | 1758.19 | 916.15 | 1034.45 | 536.16 | 498.29 | 0.00 | 0.00 |
May | 1641.79 | 835.59 | 1016.55 | 467.03 | 549.53 | 0.00 | 0.00 |
June | 1887.93 | 647.59 | 1076.02 | 535.05 | 540.96 | 0.00 | 0.00 |
July | 2169.18 | 584.21 | 1139.32 | 606.87 | 532.44 | 0.00 | 0.00 |
August | 2072.15 | 605.60 | 1068.68 | 576.52 | 492.16 | 0.00 | 0.00 |
September | 1703.17 | 673.56 | 915.16 | 487.46 | 427.70 | 0.00 | 0.00 |
October | 1377.71 | 745.42 | 702.05 | 382.74 | 319.31 | 0.00 | 0.00 |
November | 1026.96 | 1058.26 | 636.79 | 333.82 | 302.97 | 0.00 | 0.00 |
December | 920.85 | 1162.68 | 564.83 | 304.70 | 260.12 | 0.00 | 0.00 |
Annual Sum or Average | 1459.39 | 883.07 | 843.73 | 429.25 | 414.48 | 0.00 | 0.00 |
Minimum of Months | 872.68 | 584.21 | 555.05 | 281.71 | 260.12 | 0.00 | 0.00 |
Maximum of Months | 2169.18 | 1162.68 | 1139.32 | 606.87 | 549.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 244.76 | 1908.33 | 322.19 | 0.00 | 322.19 | 0.00 | 0.00 |
February | 287.66 | 1756.51 | 404.43 | 0.00 | 404.43 | 0.00 | 0.00 |
March | 423.47 | 1806.65 | 495.60 | 0.00 | 495.60 | 0.00 | 0.00 |
April | 608.81 | 1389.87 | 572.43 | 3.64 | 568.79 | 0.00 | 0.00 |
May | 759.95 | 1236.45 | 697.33 | 43.13 | 654.20 | 0.00 | 0.00 |
June | 991.29 | 954.74 | 750.21 | 90.56 | 659.65 | 0.00 | 0.00 |
July | 1075.33 | 860.64 | 710.16 | 75.92 | 634.24 | 0.00 | 0.00 |
August | 860.42 | 903.83 | 580.43 | 17.04 | 563.39 | 0.00 | 0.00 |
September | 655.37 | 1083.96 | 486.67 | 0.15 | 486.52 | 0.00 | 0.00 |
October | 596.59 | 1228.89 | 385.98 | 0.00 | 385.98 | 0.00 | 0.00 |
November | 277.37 | 1758.73 | 349.48 | 0.00 | 349.48 | 0.00 | 0.00 |
December | 229.01 | 1921.56 | 299.93 | 0.00 | 299.93 | 0.00 | 0.00 |
Annual Sum or Average | 586.07 | 1399.06 | 505.01 | 19.31 | 485.69 | 0.00 | 0.00 |
Minimum of Months | 229.01 | 860.64 | 299.93 | 0.00 | 299.93 | 0.00 | 0.00 |
Maximum of Months | 1075.33 | 1921.56 | 750.21 | 90.56 | 659.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 897.20 | 1209.82 | 582.33 | 312.81 | 269.52 | 0.00 | 0.00 |
February | 863.33 | 1125.48 | 611.39 | 280.18 | 331.21 | 0.00 | 0.00 |
March | 1109.27 | 1155.93 | 738.55 | 326.91 | 411.65 | 0.00 | 0.00 |
April | 1662.88 | 920.98 | 945.95 | 472.80 | 473.16 | 0.00 | 0.00 |
May | 1484.02 | 840.17 | 893.38 | 371.44 | 521.94 | 0.00 | 0.00 |
June | 1632.08 | 651.36 | 889.90 | 385.94 | 503.95 | 0.00 | 0.00 |
July | 2014.90 | 600.59 | 1007.03 | 499.60 | 507.43 | 0.00 | 0.00 |
August | 2016.59 | 617.16 | 992.90 | 525.88 | 467.02 | 0.00 | 0.00 |
September | 1385.47 | 701.47 | 725.72 | 332.80 | 392.92 | 0.00 | 0.00 |
October | 1248.62 | 786.54 | 641.50 | 329.47 | 312.02 | 0.00 | 0.00 |
November | 894.82 | 1117.35 | 587.04 | 299.12 | 287.92 | 0.00 | 0.00 |
December | 866.03 | 1211.28 | 562.56 | 314.46 | 248.11 | 0.00 | 0.00 |
Annual Sum or Average | 1342.92 | 910.45 | 765.87 | 371.68 | 394.19 | 0.00 | 0.00 |
Minimum of Months | 863.33 | 600.59 | 562.56 | 280.18 | 248.11 | 0.00 | 0.00 |
Maximum of Months | 2016.59 | 1211.28 | 1007.03 | 525.88 | 521.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4011.04 | 1980.08 | 2081.83 | 1515.30 | 566.54 | 0.00 | 0.00 |
February | 2899.03 | 1813.14 | 1663.81 | 1022.03 | 641.78 | 0.00 | 0.00 |
March | 2358.45 | 1862.04 | 1364.92 | 676.22 | 688.71 | 0.00 | 0.00 |
April | 2206.12 | 1486.91 | 1193.19 | 504.51 | 688.68 | 0.00 | 0.00 |
May | 1238.45 | 1321.33 | 832.76 | 137.67 | 695.09 | 0.00 | 0.00 |
June | 1127.15 | 985.77 | 720.15 | 66.78 | 653.37 | 0.00 | 0.00 |
July | 1425.35 | 890.79 | 776.61 | 122.96 | 653.65 | 0.00 | 0.00 |
August | 2122.54 | 965.84 | 1020.77 | 372.99 | 647.78 | 0.00 | 0.00 |
September | 2866.61 | 1158.95 | 1376.49 | 727.00 | 649.49 | 0.00 | 0.00 |
October | 3582.62 | 1313.70 | 1681.82 | 1126.75 | 555.07 | 0.00 | 0.00 |
November | 3797.43 | 1836.02 | 2003.23 | 1404.83 | 598.40 | 0.00 | 0.00 |
December | 4291.99 | 1998.11 | 2218.42 | 1675.83 | 542.58 | 0.00 | 0.00 |
Annual Sum or Average | 2660.37 | 1465.99 | 1410.05 | 778.55 | 631.51 | 0.00 | 0.00 |
Minimum of Months | 1127.15 | 890.79 | 720.15 | 66.78 | 542.58 | 0.00 | 0.00 |
Maximum of Months | 4291.99 | 1998.11 | 2218.42 | 1675.83 | 695.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 899.67 | 1268.18 | 555.07 | 281.72 | 273.34 | 0.00 | 0.00 |
February | 991.83 | 1176.64 | 656.29 | 302.09 | 354.20 | 0.00 | 0.00 |
March | 1161.84 | 1208.01 | 750.79 | 330.28 | 420.51 | 0.00 | 0.00 |
April | 1835.48 | 983.30 | 1034.48 | 536.18 | 498.31 | 0.00 | 0.00 |
May | 1718.14 | 898.65 | 1016.59 | 467.04 | 549.54 | 0.00 | 0.00 |
June | 1969.48 | 694.95 | 1076.05 | 535.07 | 540.98 | 0.00 | 0.00 |
July | 2236.93 | 642.35 | 1139.35 | 606.89 | 532.46 | 0.00 | 0.00 |
August | 2136.62 | 667.27 | 1068.71 | 576.54 | 492.17 | 0.00 | 0.00 |
September | 1753.49 | 752.64 | 915.19 | 487.48 | 427.71 | 0.00 | 0.00 |
October | 1407.77 | 832.37 | 702.07 | 382.75 | 319.32 | 0.00 | 0.00 |
November | 1056.12 | 1170.92 | 636.81 | 333.83 | 302.98 | 0.00 | 0.00 |
December | 945.57 | 1277.20 | 564.84 | 304.71 | 260.13 | 0.00 | 0.00 |
Annual Sum or Average | 1512.08 | 963.33 | 843.76 | 429.27 | 414.49 | 0.00 | 0.00 |
Minimum of Months | 899.67 | 642.35 | 555.07 | 281.72 | 260.13 | 0.00 | 0.00 |
Maximum of Months | 2236.93 | 1277.20 | 1139.35 | 606.89 | 549.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 219.40 | 1941.87 | 322.19 | 0.00 | 322.19 | 0.00 | 0.00 |
February | 246.27 | 1820.91 | 404.43 | 0.00 | 404.43 | 0.00 | 0.00 |
March | 367.85 | 1874.47 | 495.60 | 0.00 | 495.60 | 0.00 | 0.00 |
April | 542.43 | 1453.19 | 572.44 | 3.64 | 568.80 | 0.00 | 0.00 |
May | 691.38 | 1273.68 | 697.33 | 43.13 | 654.20 | 0.00 | 0.00 |
June | 917.47 | 987.89 | 750.21 | 90.56 | 659.65 | 0.00 | 0.00 |
July | 1019.25 | 880.27 | 710.16 | 75.92 | 634.24 | 0.00 | 0.00 |
August | 811.27 | 930.49 | 580.43 | 17.04 | 563.39 | 0.00 | 0.00 |
September | 617.13 | 1107.01 | 486.67 | 0.15 | 486.52 | 0.00 | 0.00 |
October | 571.19 | 1239.97 | 385.98 | 0.00 | 385.98 | 0.00 | 0.00 |
November | 250.66 | 1784.89 | 349.48 | 0.00 | 349.48 | 0.00 | 0.00 |
December | 205.64 | 1959.51 | 299.93 | 0.00 | 299.93 | 0.00 | 0.00 |
Annual Sum or Average | 540.25 | 1435.84 | 505.01 | 19.31 | 485.70 | 0.00 | 0.00 |
Minimum of Months | 205.64 | 880.27 | 299.93 | 0.00 | 299.93 | 0.00 | 0.00 |
Maximum of Months | 1019.25 | 1959.51 | 750.21 | 90.56 | 659.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 862.15 | 1203.35 | 582.31 | 312.80 | 269.52 | 0.00 | 0.00 |
February | 812.96 | 1140.62 | 611.37 | 280.17 | 331.20 | 0.00 | 0.00 |
March | 1052.59 | 1170.27 | 738.53 | 326.89 | 411.64 | 0.00 | 0.00 |
April | 1611.05 | 917.07 | 945.92 | 472.78 | 473.14 | 0.00 | 0.00 |
May | 1428.41 | 839.29 | 893.35 | 371.42 | 521.93 | 0.00 | 0.00 |
June | 1578.70 | 654.09 | 889.87 | 385.93 | 503.94 | 0.00 | 0.00 |
July | 1978.05 | 584.23 | 1006.99 | 499.58 | 507.41 | 0.00 | 0.00 |
August | 1979.88 | 598.79 | 992.86 | 525.85 | 467.01 | 0.00 | 0.00 |
September | 1351.84 | 689.09 | 725.70 | 332.79 | 392.91 | 0.00 | 0.00 |
October | 1217.10 | 768.26 | 641.47 | 329.46 | 312.01 | 0.00 | 0.00 |
November | 859.09 | 1110.38 | 587.02 | 299.11 | 287.91 | 0.00 | 0.00 |
December | 829.07 | 1211.97 | 562.55 | 314.44 | 248.10 | 0.00 | 0.00 |
Annual Sum or Average | 1300.13 | 906.08 | 765.84 | 371.66 | 394.18 | 0.00 | 0.00 |
Minimum of Months | 812.96 | 584.23 | 562.55 | 280.17 | 248.10 | 0.00 | 0.00 |
Maximum of Months | 1979.88 | 1211.97 | 1006.99 | 525.85 | 521.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3960.03 | 1872.02 | 2081.82 | 1515.29 | 566.53 | 0.00 | 0.00 |
February | 2813.92 | 1774.63 | 1663.80 | 1022.02 | 641.78 | 0.00 | 0.00 |
March | 2272.26 | 1867.35 | 1364.92 | 676.21 | 688.70 | 0.00 | 0.00 |
April | 2130.61 | 1502.63 | 1193.19 | 504.51 | 688.68 | 0.00 | 0.00 |
May | 1150.19 | 1373.55 | 832.76 | 137.67 | 695.09 | 0.00 | 0.00 |
June | 1042.41 | 1042.06 | 720.15 | 66.78 | 653.36 | 0.00 | 0.00 |
July | 1367.29 | 915.55 | 776.61 | 122.96 | 653.65 | 0.00 | 0.00 |
August | 2068.76 | 968.89 | 1020.77 | 372.98 | 647.78 | 0.00 | 0.00 |
September | 2815.91 | 1123.09 | 1376.49 | 727.00 | 649.49 | 0.00 | 0.00 |
October | 3537.04 | 1239.06 | 1681.82 | 1126.75 | 555.07 | 0.00 | 0.00 |
November | 3737.32 | 1735.51 | 2003.22 | 1404.82 | 598.40 | 0.00 | 0.00 |
December | 4233.35 | 1885.02 | 2218.40 | 1675.82 | 542.58 | 0.00 | 0.00 |
Annual Sum or Average | 2594.06 | 1439.87 | 1410.05 | 778.54 | 631.51 | 0.00 | 0.00 |
Minimum of Months | 1042.41 | 915.55 | 720.15 | 66.78 | 542.58 | 0.00 | 0.00 |
Maximum of Months | 4233.35 | 1885.02 | 2218.40 | 1675.82 | 695.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 868.56 | 1256.34 | 555.05 | 281.71 | 273.33 | 0.00 | 0.00 |
February | 947.16 | 1182.33 | 656.27 | 302.08 | 354.19 | 0.00 | 0.00 |
March | 1109.34 | 1215.42 | 750.77 | 330.27 | 420.50 | 0.00 | 0.00 |
April | 1778.05 | 976.87 | 1034.45 | 536.16 | 498.29 | 0.00 | 0.00 |
May | 1660.52 | 890.87 | 1016.55 | 467.03 | 549.53 | 0.00 | 0.00 |
June | 1909.57 | 690.81 | 1076.02 | 535.05 | 540.96 | 0.00 | 0.00 |
July | 2192.99 | 624.56 | 1139.32 | 606.87 | 532.44 | 0.00 | 0.00 |
August | 2093.31 | 648.19 | 1068.68 | 576.52 | 492.16 | 0.00 | 0.00 |
September | 1715.23 | 729.39 | 915.16 | 487.46 | 427.70 | 0.00 | 0.00 |
October | 1379.91 | 810.16 | 702.05 | 382.74 | 319.31 | 0.00 | 0.00 |
November | 1025.07 | 1151.09 | 636.79 | 333.82 | 302.97 | 0.00 | 0.00 |
December | 916.44 | 1266.47 | 564.83 | 304.70 | 260.12 | 0.00 | 0.00 |
Annual Sum or Average | 1469.07 | 952.39 | 843.73 | 429.25 | 414.48 | 0.00 | 0.00 |
Minimum of Months | 868.56 | 624.56 | 555.05 | 281.71 | 260.12 | 0.00 | 0.00 |
Maximum of Months | 2192.99 | 1266.47 | 1139.32 | 606.87 | 549.53 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.652994E+09 | 0.474545E+10 | 0.862955E+09 | 0.00 | 0.862955E+09 | 0.00 | 0.00 |
February | 0.648402E+09 | 0.403048E+10 | 0.978409E+09 | 0.00 | 0.978409E+09 | 0.00 | 0.00 |
March | 0.103218E+10 | 0.465894E+10 | 0.132742E+10 | 0.00 | 0.132742E+10 | 0.00 | 0.00 |
April | 0.140980E+10 | 0.350601E+10 | 0.148376E+10 | 9436248.24 | 0.147432E+10 | 0.00 | 0.00 |
May | 0.187296E+10 | 0.317437E+10 | 0.186774E+10 | 0.115524E+09 | 0.175221E+10 | 0.00 | 0.00 |
June | 0.236660E+10 | 0.239186E+10 | 0.194455E+10 | 0.234737E+09 | 0.170981E+10 | 0.00 | 0.00 |
July | 0.269704E+10 | 0.220472E+10 | 0.190210E+10 | 0.203348E+09 | 0.169875E+10 | 0.00 | 0.00 |
August | 0.215381E+10 | 0.231727E+10 | 0.155463E+10 | 45639358.80 | 0.150899E+10 | 0.00 | 0.00 |
September | 0.161632E+10 | 0.262866E+10 | 0.126145E+10 | 389802.64 | 0.126106E+10 | 0.00 | 0.00 |
October | 0.157447E+10 | 0.301962E+10 | 0.103382E+10 | 0.00 | 0.103382E+10 | 0.00 | 0.00 |
November | 0.719146E+09 | 0.420312E+10 | 0.905854E+09 | 0.00 | 0.905854E+09 | 0.00 | 0.00 |
December | 0.619529E+09 | 0.477141E+10 | 0.803337E+09 | 0.00 | 0.803337E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173633E+11 | 0.416519E+11 | 0.159260E+11 | 0.609074E+09 | 0.153169E+11 | 0.00 | 0.00 |
Minimum of Months | 0.619529E+09 | 0.220472E+10 | 0.803337E+09 | 0.00 | 0.803337E+09 | 0.00 | 0.00 |
Maximum of Months | 0.269704E+10 | 0.477141E+10 | 0.194455E+10 | 0.234737E+09 | 0.175221E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.240688E+10 | 0.295731E+10 | 0.155966E+10 | 0.837793E+09 | 0.721869E+09 | 0.00 | 0.00 |
February | 0.203097E+10 | 0.254533E+10 | 0.147902E+10 | 0.677783E+09 | 0.801235E+09 | 0.00 | 0.00 |
March | 0.288435E+10 | 0.293109E+10 | 0.197808E+10 | 0.875552E+09 | 0.110252E+10 | 0.00 | 0.00 |
April | 0.418663E+10 | 0.224624E+10 | 0.245182E+10 | 0.122544E+10 | 0.122639E+10 | 0.00 | 0.00 |
May | 0.385134E+10 | 0.212942E+10 | 0.239275E+10 | 0.994813E+09 | 0.139794E+10 | 0.00 | 0.00 |
June | 0.409569E+10 | 0.161038E+10 | 0.230654E+10 | 0.100033E+10 | 0.130621E+10 | 0.00 | 0.00 |
July | 0.527391E+10 | 0.148562E+10 | 0.269713E+10 | 0.133807E+10 | 0.135906E+10 | 0.00 | 0.00 |
August | 0.528636E+10 | 0.151730E+10 | 0.265928E+10 | 0.140845E+10 | 0.125083E+10 | 0.00 | 0.00 |
September | 0.351988E+10 | 0.166243E+10 | 0.188101E+10 | 0.862587E+09 | 0.101842E+10 | 0.00 | 0.00 |
October | 0.329989E+10 | 0.190371E+10 | 0.171813E+10 | 0.882425E+09 | 0.835700E+09 | 0.00 | 0.00 |
November | 0.231228E+10 | 0.264467E+10 | 0.152155E+10 | 0.775285E+09 | 0.746262E+09 | 0.00 | 0.00 |
December | 0.231916E+10 | 0.297096E+10 | 0.150672E+10 | 0.842202E+09 | 0.664519E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.414673E+11 | 0.266044E+11 | 0.241517E+11 | 0.117207E+11 | 0.124310E+11 | 0.00 | 0.00 |
Minimum of Months | 0.203097E+10 | 0.148562E+10 | 0.147902E+10 | 0.677783E+09 | 0.664519E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528636E+10 | 0.297096E+10 | 0.269713E+10 | 0.140845E+10 | 0.139794E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106626E+11 | 0.461571E+10 | 0.557596E+10 | 0.405855E+10 | 0.151740E+10 | 0.00 | 0.00 |
February | 0.682569E+10 | 0.395585E+10 | 0.402507E+10 | 0.247247E+10 | 0.155260E+10 | 0.00 | 0.00 |
March | 0.610532E+10 | 0.466730E+10 | 0.365579E+10 | 0.181117E+10 | 0.184463E+10 | 0.00 | 0.00 |
April | 0.549719E+10 | 0.365351E+10 | 0.309274E+10 | 0.130768E+10 | 0.178505E+10 | 0.00 | 0.00 |
May | 0.305994E+10 | 0.345263E+10 | 0.223045E+10 | 0.368737E+09 | 0.186172E+10 | 0.00 | 0.00 |
June | 0.268319E+10 | 0.253693E+10 | 0.186662E+10 | 0.173097E+09 | 0.169352E+10 | 0.00 | 0.00 |
July | 0.362593E+10 | 0.230255E+10 | 0.208007E+10 | 0.329341E+09 | 0.175073E+10 | 0.00 | 0.00 |
August | 0.550245E+10 | 0.242630E+10 | 0.273402E+10 | 0.998998E+09 | 0.173502E+10 | 0.00 | 0.00 |
September | 0.727870E+10 | 0.269118E+10 | 0.356786E+10 | 0.188437E+10 | 0.168349E+10 | 0.00 | 0.00 |
October | 0.947630E+10 | 0.305437E+10 | 0.450457E+10 | 0.301787E+10 | 0.148670E+10 | 0.00 | 0.00 |
November | 0.972011E+10 | 0.413424E+10 | 0.519234E+10 | 0.364130E+10 | 0.155104E+10 | 0.00 | 0.00 |
December | 0.113902E+11 | 0.464075E+10 | 0.594177E+10 | 0.448852E+10 | 0.145325E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.818276E+11 | 0.421313E+11 | 0.444673E+11 | 0.245521E+11 | 0.199152E+11 | 0.00 | 0.00 |
Minimum of Months | 0.268319E+10 | 0.230255E+10 | 0.186662E+10 | 0.173097E+09 | 0.145325E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113902E+11 | 0.466730E+10 | 0.594177E+10 | 0.448852E+10 | 0.186172E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.233739E+10 | 0.309416E+10 | 0.148664E+10 | 0.754544E+09 | 0.732099E+09 | 0.00 | 0.00 |
February | 0.228919E+10 | 0.263820E+10 | 0.158765E+10 | 0.730798E+09 | 0.856848E+09 | 0.00 | 0.00 |
March | 0.295577E+10 | 0.303842E+10 | 0.201086E+10 | 0.884601E+09 | 0.112626E+10 | 0.00 | 0.00 |
April | 0.455723E+10 | 0.237467E+10 | 0.268129E+10 | 0.138971E+10 | 0.129158E+10 | 0.00 | 0.00 |
May | 0.439736E+10 | 0.223804E+10 | 0.272274E+10 | 0.125088E+10 | 0.147186E+10 | 0.00 | 0.00 |
June | 0.489352E+10 | 0.167856E+10 | 0.278904E+10 | 0.138686E+10 | 0.140218E+10 | 0.00 | 0.00 |
July | 0.580993E+10 | 0.156476E+10 | 0.305154E+10 | 0.162545E+10 | 0.142610E+10 | 0.00 | 0.00 |
August | 0.555005E+10 | 0.162205E+10 | 0.286234E+10 | 0.154415E+10 | 0.131820E+10 | 0.00 | 0.00 |
September | 0.441462E+10 | 0.174587E+10 | 0.237209E+10 | 0.126349E+10 | 0.110860E+10 | 0.00 | 0.00 |
October | 0.369006E+10 | 0.199654E+10 | 0.188037E+10 | 0.102513E+10 | 0.855244E+09 | 0.00 | 0.00 |
November | 0.266189E+10 | 0.274301E+10 | 0.165056E+10 | 0.865257E+09 | 0.785305E+09 | 0.00 | 0.00 |
December | 0.246642E+10 | 0.311411E+10 | 0.151283E+10 | 0.816111E+09 | 0.696719E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.460234E+11 | 0.278484E+11 | 0.266080E+11 | 0.135370E+11 | 0.130710E+11 | 0.00 | 0.00 |
Minimum of Months | 0.228919E+10 | 0.156476E+10 | 0.148664E+10 | 0.730798E+09 | 0.696719E+09 | 0.00 | 0.00 |
Maximum of Months | 0.580993E+10 | 0.311411E+10 | 0.305154E+10 | 0.162545E+10 | 0.147186E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.655570E+09 | 0.511128E+10 | 0.862950E+09 | 0.00 | 0.862950E+09 | 0.00 | 0.00 |
February | 0.695900E+09 | 0.424934E+10 | 0.978403E+09 | 0.00 | 0.978403E+09 | 0.00 | 0.00 |
March | 0.113421E+10 | 0.483893E+10 | 0.132742E+10 | 0.00 | 0.132742E+10 | 0.00 | 0.00 |
April | 0.157803E+10 | 0.360255E+10 | 0.148375E+10 | 9436193.65 | 0.147431E+10 | 0.00 | 0.00 |
May | 0.203546E+10 | 0.331172E+10 | 0.186773E+10 | 0.115523E+09 | 0.175220E+10 | 0.00 | 0.00 |
June | 0.256941E+10 | 0.247468E+10 | 0.194454E+10 | 0.234736E+09 | 0.170980E+10 | 0.00 | 0.00 |
July | 0.288015E+10 | 0.230513E+10 | 0.190209E+10 | 0.203347E+09 | 0.169875E+10 | 0.00 | 0.00 |
August | 0.230455E+10 | 0.242083E+10 | 0.155462E+10 | 45639094.74 | 0.150898E+10 | 0.00 | 0.00 |
September | 0.169872E+10 | 0.280962E+10 | 0.126144E+10 | 389800.39 | 0.126105E+10 | 0.00 | 0.00 |
October | 0.159790E+10 | 0.329145E+10 | 0.103381E+10 | 0.00 | 0.103381E+10 | 0.00 | 0.00 |
November | 0.718936E+09 | 0.455864E+10 | 0.905849E+09 | 0.00 | 0.905849E+09 | 0.00 | 0.00 |
December | 0.613368E+09 | 0.514672E+10 | 0.803333E+09 | 0.00 | 0.803333E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.184822E+11 | 0.441209E+11 | 0.159259E+11 | 0.609070E+09 | 0.153169E+11 | 0.00 | 0.00 |
Minimum of Months | 0.613368E+09 | 0.230513E+10 | 0.803333E+09 | 0.00 | 0.803333E+09 | 0.00 | 0.00 |
Maximum of Months | 0.288015E+10 | 0.514672E+10 | 0.194454E+10 | 0.234736E+09 | 0.175220E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.240307E+10 | 0.324039E+10 | 0.155972E+10 | 0.837827E+09 | 0.721890E+09 | 0.00 | 0.00 |
February | 0.208856E+10 | 0.272276E+10 | 0.147907E+10 | 0.677810E+09 | 0.801258E+09 | 0.00 | 0.00 |
March | 0.297107E+10 | 0.309604E+10 | 0.197814E+10 | 0.875587E+09 | 0.110256E+10 | 0.00 | 0.00 |
April | 0.431018E+10 | 0.238717E+10 | 0.245190E+10 | 0.122549E+10 | 0.122642E+10 | 0.00 | 0.00 |
May | 0.397479E+10 | 0.225031E+10 | 0.239283E+10 | 0.994853E+09 | 0.139798E+10 | 0.00 | 0.00 |
June | 0.423036E+10 | 0.168831E+10 | 0.230661E+10 | 0.100037E+10 | 0.130625E+10 | 0.00 | 0.00 |
July | 0.539671E+10 | 0.160861E+10 | 0.269722E+10 | 0.133812E+10 | 0.135910E+10 | 0.00 | 0.00 |
August | 0.540123E+10 | 0.165299E+10 | 0.265937E+10 | 0.140851E+10 | 0.125086E+10 | 0.00 | 0.00 |
September | 0.359113E+10 | 0.181820E+10 | 0.188107E+10 | 0.862622E+09 | 0.101845E+10 | 0.00 | 0.00 |
October | 0.334429E+10 | 0.210666E+10 | 0.171818E+10 | 0.882461E+09 | 0.835723E+09 | 0.00 | 0.00 |
November | 0.231938E+10 | 0.289618E+10 | 0.152160E+10 | 0.775316E+09 | 0.746284E+09 | 0.00 | 0.00 |
December | 0.231958E+10 | 0.324428E+10 | 0.150677E+10 | 0.842236E+09 | 0.664538E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.423503E+11 | 0.287119E+11 | 0.241525E+11 | 0.117212E+11 | 0.124313E+11 | 0.00 | 0.00 |
Minimum of Months | 0.208856E+10 | 0.160861E+10 | 0.147907E+10 | 0.677810E+09 | 0.664538E+09 | 0.00 | 0.00 |
Maximum of Months | 0.540123E+10 | 0.324428E+10 | 0.269722E+10 | 0.140851E+10 | 0.139798E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107432E+11 | 0.530346E+10 | 0.557599E+10 | 0.405858E+10 | 0.151741E+10 | 0.00 | 0.00 |
February | 0.701332E+10 | 0.438635E+10 | 0.402509E+10 | 0.247249E+10 | 0.155260E+10 | 0.00 | 0.00 |
March | 0.631688E+10 | 0.498728E+10 | 0.365581E+10 | 0.181118E+10 | 0.184463E+10 | 0.00 | 0.00 |
April | 0.571828E+10 | 0.385407E+10 | 0.309275E+10 | 0.130769E+10 | 0.178506E+10 | 0.00 | 0.00 |
May | 0.331706E+10 | 0.353904E+10 | 0.223046E+10 | 0.368739E+09 | 0.186172E+10 | 0.00 | 0.00 |
June | 0.292159E+10 | 0.255512E+10 | 0.186662E+10 | 0.173098E+09 | 0.169352E+10 | 0.00 | 0.00 |
July | 0.381766E+10 | 0.238589E+10 | 0.208008E+10 | 0.329343E+09 | 0.175073E+10 | 0.00 | 0.00 |
August | 0.568501E+10 | 0.258690E+10 | 0.273403E+10 | 0.999004E+09 | 0.173502E+10 | 0.00 | 0.00 |
September | 0.743026E+10 | 0.300400E+10 | 0.356787E+10 | 0.188438E+10 | 0.168349E+10 | 0.00 | 0.00 |
October | 0.959568E+10 | 0.351861E+10 | 0.450460E+10 | 0.301789E+10 | 0.148670E+10 | 0.00 | 0.00 |
November | 0.984295E+10 | 0.475897E+10 | 0.519237E+10 | 0.364132E+10 | 0.155105E+10 | 0.00 | 0.00 |
December | 0.114957E+11 | 0.535173E+10 | 0.594181E+10 | 0.448855E+10 | 0.145326E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.838975E+11 | 0.462314E+11 | 0.444675E+11 | 0.245523E+11 | 0.199152E+11 | 0.00 | 0.00 |
Minimum of Months | 0.292159E+10 | 0.238589E+10 | 0.186662E+10 | 0.173098E+09 | 0.145326E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114957E+11 | 0.535173E+10 | 0.594181E+10 | 0.448855E+10 | 0.186172E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.240969E+10 | 0.339669E+10 | 0.148669E+10 | 0.754572E+09 | 0.732118E+09 | 0.00 | 0.00 |
February | 0.239943E+10 | 0.284654E+10 | 0.158770E+10 | 0.730825E+09 | 0.856872E+09 | 0.00 | 0.00 |
March | 0.311187E+10 | 0.323554E+10 | 0.201092E+10 | 0.884634E+09 | 0.112629E+10 | 0.00 | 0.00 |
April | 0.475756E+10 | 0.254870E+10 | 0.268137E+10 | 0.138977E+10 | 0.129161E+10 | 0.00 | 0.00 |
May | 0.460187E+10 | 0.240694E+10 | 0.272283E+10 | 0.125093E+10 | 0.147190E+10 | 0.00 | 0.00 |
June | 0.510488E+10 | 0.180131E+10 | 0.278912E+10 | 0.138691E+10 | 0.140222E+10 | 0.00 | 0.00 |
July | 0.599138E+10 | 0.172048E+10 | 0.305164E+10 | 0.162551E+10 | 0.142613E+10 | 0.00 | 0.00 |
August | 0.572272E+10 | 0.178722E+10 | 0.286243E+10 | 0.154421E+10 | 0.131823E+10 | 0.00 | 0.00 |
September | 0.454505E+10 | 0.195085E+10 | 0.237217E+10 | 0.126354E+10 | 0.110863E+10 | 0.00 | 0.00 |
October | 0.377056E+10 | 0.222943E+10 | 0.188043E+10 | 0.102517E+10 | 0.855266E+09 | 0.00 | 0.00 |
November | 0.273746E+10 | 0.303502E+10 | 0.165062E+10 | 0.865290E+09 | 0.785326E+09 | 0.00 | 0.00 |
December | 0.253260E+10 | 0.342086E+10 | 0.151288E+10 | 0.816142E+09 | 0.696737E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.476851E+11 | 0.303796E+11 | 0.266088E+11 | 0.135375E+11 | 0.130713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.239943E+10 | 0.172048E+10 | 0.148669E+10 | 0.730825E+09 | 0.696737E+09 | 0.00 | 0.00 |
Maximum of Months | 0.599138E+10 | 0.342086E+10 | 0.305164E+10 | 0.162551E+10 | 0.147190E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.587639E+09 | 0.520111E+10 | 0.862955E+09 | 0.00 | 0.862955E+09 | 0.00 | 0.00 |
February | 0.595770E+09 | 0.440516E+10 | 0.978409E+09 | 0.00 | 0.978409E+09 | 0.00 | 0.00 |
March | 0.985253E+09 | 0.502058E+10 | 0.132742E+10 | 0.00 | 0.132742E+10 | 0.00 | 0.00 |
April | 0.140598E+10 | 0.376666E+10 | 0.148376E+10 | 9436248.24 | 0.147432E+10 | 0.00 | 0.00 |
May | 0.185180E+10 | 0.341143E+10 | 0.186774E+10 | 0.115524E+09 | 0.175221E+10 | 0.00 | 0.00 |
June | 0.237809E+10 | 0.256062E+10 | 0.194455E+10 | 0.234737E+09 | 0.170981E+10 | 0.00 | 0.00 |
July | 0.272995E+10 | 0.235770E+10 | 0.190210E+10 | 0.203348E+09 | 0.169875E+10 | 0.00 | 0.00 |
August | 0.217290E+10 | 0.249222E+10 | 0.155463E+10 | 45639358.80 | 0.150899E+10 | 0.00 | 0.00 |
September | 0.159959E+10 | 0.286937E+10 | 0.126145E+10 | 389802.64 | 0.126106E+10 | 0.00 | 0.00 |
October | 0.152989E+10 | 0.332114E+10 | 0.103382E+10 | 0.00 | 0.103382E+10 | 0.00 | 0.00 |
November | 0.649722E+09 | 0.462643E+10 | 0.905854E+09 | 0.00 | 0.905854E+09 | 0.00 | 0.00 |
December | 0.550784E+09 | 0.524836E+10 | 0.803337E+09 | 0.00 | 0.803337E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170374E+11 | 0.452808E+11 | 0.159260E+11 | 0.609074E+09 | 0.153169E+11 | 0.00 | 0.00 |
Minimum of Months | 0.550784E+09 | 0.235770E+10 | 0.803337E+09 | 0.00 | 0.803337E+09 | 0.00 | 0.00 |
Maximum of Months | 0.272995E+10 | 0.524836E+10 | 0.194455E+10 | 0.234737E+09 | 0.175221E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.230917E+10 | 0.322305E+10 | 0.155966E+10 | 0.837793E+09 | 0.721869E+09 | 0.00 | 0.00 |
February | 0.196671E+10 | 0.275940E+10 | 0.147902E+10 | 0.677783E+09 | 0.801235E+09 | 0.00 | 0.00 |
March | 0.281925E+10 | 0.313445E+10 | 0.197808E+10 | 0.875552E+09 | 0.110252E+10 | 0.00 | 0.00 |
April | 0.417583E+10 | 0.237704E+10 | 0.245182E+10 | 0.122544E+10 | 0.122639E+10 | 0.00 | 0.00 |
May | 0.382584E+10 | 0.224795E+10 | 0.239275E+10 | 0.994813E+09 | 0.139794E+10 | 0.00 | 0.00 |
June | 0.409198E+10 | 0.169540E+10 | 0.230654E+10 | 0.100033E+10 | 0.130621E+10 | 0.00 | 0.00 |
July | 0.529801E+10 | 0.156481E+10 | 0.269713E+10 | 0.133807E+10 | 0.135906E+10 | 0.00 | 0.00 |
August | 0.530292E+10 | 0.160379E+10 | 0.265928E+10 | 0.140845E+10 | 0.125083E+10 | 0.00 | 0.00 |
September | 0.350396E+10 | 0.178612E+10 | 0.188101E+10 | 0.862587E+09 | 0.101842E+10 | 0.00 | 0.00 |
October | 0.325988E+10 | 0.205772E+10 | 0.171813E+10 | 0.882425E+09 | 0.835700E+09 | 0.00 | 0.00 |
November | 0.222675E+10 | 0.287811E+10 | 0.152155E+10 | 0.775285E+09 | 0.746262E+09 | 0.00 | 0.00 |
December | 0.222058E+10 | 0.324615E+10 | 0.150672E+10 | 0.842202E+09 | 0.664519E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.410009E+11 | 0.285740E+11 | 0.241517E+11 | 0.117207E+11 | 0.124310E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196671E+10 | 0.156481E+10 | 0.147902E+10 | 0.677783E+09 | 0.664519E+09 | 0.00 | 0.00 |
Maximum of Months | 0.530292E+10 | 0.324615E+10 | 0.269713E+10 | 0.140845E+10 | 0.139794E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106065E+11 | 0.501402E+10 | 0.557596E+10 | 0.405855E+10 | 0.151740E+10 | 0.00 | 0.00 |
February | 0.680743E+10 | 0.429318E+10 | 0.402507E+10 | 0.247247E+10 | 0.155260E+10 | 0.00 | 0.00 |
March | 0.608603E+10 | 0.500151E+10 | 0.365579E+10 | 0.181117E+10 | 0.184463E+10 | 0.00 | 0.00 |
April | 0.552255E+10 | 0.389481E+10 | 0.309274E+10 | 0.130768E+10 | 0.178505E+10 | 0.00 | 0.00 |
May | 0.308067E+10 | 0.367890E+10 | 0.223045E+10 | 0.368737E+09 | 0.186172E+10 | 0.00 | 0.00 |
June | 0.270193E+10 | 0.270103E+10 | 0.186662E+10 | 0.173097E+09 | 0.169352E+10 | 0.00 | 0.00 |
July | 0.366214E+10 | 0.245221E+10 | 0.208007E+10 | 0.329341E+09 | 0.175073E+10 | 0.00 | 0.00 |
August | 0.554096E+10 | 0.259508E+10 | 0.273402E+10 | 0.998998E+09 | 0.173502E+10 | 0.00 | 0.00 |
September | 0.729883E+10 | 0.291105E+10 | 0.356786E+10 | 0.188437E+10 | 0.168349E+10 | 0.00 | 0.00 |
October | 0.947360E+10 | 0.331870E+10 | 0.450457E+10 | 0.301787E+10 | 0.148670E+10 | 0.00 | 0.00 |
November | 0.968714E+10 | 0.449845E+10 | 0.519234E+10 | 0.364130E+10 | 0.155104E+10 | 0.00 | 0.00 |
December | 0.113386E+11 | 0.504885E+10 | 0.594177E+10 | 0.448852E+10 | 0.145325E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.818064E+11 | 0.454078E+11 | 0.444673E+11 | 0.245521E+11 | 0.199152E+11 | 0.00 | 0.00 |
Minimum of Months | 0.270193E+10 | 0.245221E+10 | 0.186662E+10 | 0.173097E+09 | 0.145325E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113386E+11 | 0.504885E+10 | 0.594177E+10 | 0.448852E+10 | 0.186172E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232634E+10 | 0.336498E+10 | 0.148664E+10 | 0.754544E+09 | 0.732099E+09 | 0.00 | 0.00 |
February | 0.229138E+10 | 0.286029E+10 | 0.158765E+10 | 0.730798E+09 | 0.856848E+09 | 0.00 | 0.00 |
March | 0.297126E+10 | 0.325538E+10 | 0.201086E+10 | 0.884601E+09 | 0.112626E+10 | 0.00 | 0.00 |
April | 0.460871E+10 | 0.253204E+10 | 0.268129E+10 | 0.138971E+10 | 0.129158E+10 | 0.00 | 0.00 |
May | 0.444754E+10 | 0.238610E+10 | 0.272274E+10 | 0.125088E+10 | 0.147186E+10 | 0.00 | 0.00 |
June | 0.494961E+10 | 0.179058E+10 | 0.278904E+10 | 0.138686E+10 | 0.140218E+10 | 0.00 | 0.00 |
July | 0.587371E+10 | 0.167281E+10 | 0.305154E+10 | 0.162545E+10 | 0.142610E+10 | 0.00 | 0.00 |
August | 0.560671E+10 | 0.173612E+10 | 0.286234E+10 | 0.154415E+10 | 0.131820E+10 | 0.00 | 0.00 |
September | 0.444588E+10 | 0.189058E+10 | 0.237209E+10 | 0.126349E+10 | 0.110860E+10 | 0.00 | 0.00 |
October | 0.369594E+10 | 0.216992E+10 | 0.188037E+10 | 0.102513E+10 | 0.855244E+09 | 0.00 | 0.00 |
November | 0.265697E+10 | 0.298362E+10 | 0.165056E+10 | 0.865257E+09 | 0.785305E+09 | 0.00 | 0.00 |
December | 0.245459E+10 | 0.339212E+10 | 0.151283E+10 | 0.816111E+09 | 0.696719E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.463286E+11 | 0.300345E+11 | 0.266080E+11 | 0.135370E+11 | 0.130710E+11 | 0.00 | 0.00 |
Minimum of Months | 0.229138E+10 | 0.167281E+10 | 0.148664E+10 | 0.730798E+09 | 0.696719E+09 | 0.00 | 0.00 |
Maximum of Months | 0.587371E+10 | 0.339212E+10 | 0.305154E+10 | 0.162545E+10 | 0.147186E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.425643E+10 | -0.402133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235095893.7 | 60.05 | 0.00 | 0.00 |
February | 0.387118E+10 | -0.365887E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -212314558.1 | 60.05 | 0.00 | 0.00 |
March | 0.452048E+10 | -0.428537E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235111767.3 | 60.05 | 0.00 | 0.00 |
April | 0.400405E+10 | -0.377777E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226280092.3 | 60.05 | 0.00 | 0.00 |
May | 0.418480E+10 | -0.395127E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233536149.1 | 60.05 | 0.00 | 0.00 |
June | 0.406379E+10 | -0.383830E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225489044.4 | 60.05 | 0.00 | 0.00 |
July | 0.379581E+10 | -0.356362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232186207.1 | 60.05 | 0.00 | 0.00 |
August | 0.416797E+10 | -0.393536E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232608557.7 | 60.05 | 0.00 | 0.00 |
September | 0.380997E+10 | -0.358509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224883727.9 | 60.05 | 0.00 | 0.00 |
October | 0.401686E+10 | -0.378453E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232329265.1 | 60.05 | 0.00 | 0.00 |
November | 0.404360E+10 | -0.381753E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226067871.7 | 60.05 | 0.00 | 0.00 |
December | 0.409540E+10 | -0.386073E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234669946.4 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.488303E+11 | -0.460798E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.275057E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.379581E+10 | -0.428537E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -235111767.3 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.452048E+10 | -0.356362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -212314558.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16437.36 | 4.60 | 20-JAN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47256.27 | 4.86 | 23-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 133003.54 | 5.16 | 26-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68637.87 | 4.77 | 04-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 509089.17 | 4.85 | 28-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1105805.79 | 5.42 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1465357.26 | 5.45 | 31-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 612653.53 | 5.20 | 12-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 354192.15 | 5.50 | 18-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2508.76 | 3.07 | 10-NOV-13:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5340.79 | 1.66 | 07-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4320282.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1465357.26 | 5.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.698067E+09 | 9408.10 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.841718E+09 | 9415.78 | 13-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146589E+10 | 9411.56 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.546014E+09 | 9409.94 | 18-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511722E+09 | 9431.12 | 26-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.216576E+09 | 9361.48 | 01-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45687011.69 | 4236.07 | 17-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 43121423.57 | 5006.09 | 28-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102618E+09 | 7029.59 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165078E+09 | 9442.04 | 12-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.354109E+09 | 9444.97 | 02-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582309E+09 | 9405.77 | 13-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.557291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 43121423.57 | 4236.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146589E+10 | 9444.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.349502E+09 | 7107.11 | 03-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.402450E+09 | 7085.02 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.430517E+09 | 7099.62 | 30-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46307058.97 | 7078.68 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28547550.84 | 3639.88 | 12-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3847775.50 | 1757.74 | 12-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2699574.43 | 1792.72 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4139320.23 | 4197.60 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80981101.71 | 5491.58 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253997E+09 | 7084.57 | 14-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.430517E+09 | 7107.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.488073E+09 | 7674.73 | 02-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326522E+09 | 7651.71 | 21-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.434324E+09 | 7677.87 | 08-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41685183.29 | 7640.93 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1353608.73 | 2377.39 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5278914.25 | 5259.99 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64803154.43 | 7646.95 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297545E+09 | 7646.40 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.488073E+09 | 7677.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.550347E+09 | 7304.50 | 02-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492991E+09 | 7277.68 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.557529E+09 | 7286.62 | 17-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102557E+09 | 7271.59 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52070339.44 | 7278.49 | 13-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3025506.05 | 1769.02 | 01-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5506.71 | 36.71 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22939314.04 | 5160.57 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159376E+09 | 7277.47 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434742E+09 | 7286.40 | 02-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.557529E+09 | 7304.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10584530.28 | 3286.59 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 397229.00 | 609.45 | 30-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 112578.98 | 4.62 | 26-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50861.36 | 4.46 | 03-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 415509.87 | 4.55 | 29-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 861924.53 | 5.01 | 31-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1267608.72 | 5.10 | 15-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 460262.16 | 4.78 | 07-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 235685.08 | 4.98 | 03-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6085.03 | 3.15 | 28-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1109.65 | 3.73 | 07-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14393384.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10584530.28 | 3286.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 12392537.71 | 18068.71 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12392537.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12392537.71 | 18068.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.259456E+09 | 10006.88 | 02-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298955E+09 | 9978.83 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455954E+09 | 10002.62 | 29-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95589796.10 | 9987.14 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53337604.65 | 9988.07 | 13-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 648196.26 | 1397.66 | 13-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 532022.12 | 2052.29 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12983301.03 | 9482.70 | 12-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35990320.09 | 9966.76 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142488E+09 | 10004.23 | 13-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.455954E+09 | 10006.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.492401E+09 | 7685.00 | 03-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.441261E+09 | 7661.53 | 10-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.480959E+09 | 7692.93 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96980746.84 | 7637.02 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51851796.22 | 5560.07 | 12-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6211302.36 | 2562.93 | 01-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10622763.89 | 3014.02 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26557754.49 | 7647.42 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202003E+09 | 7638.63 | 03-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378474E+09 | 7667.61 | 13-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.492401E+09 | 7692.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.470706E+09 | 8045.96 | 03-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275915E+09 | 7997.71 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.370912E+09 | 8048.06 | 07-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37790562.23 | 7997.85 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1803599.71 | 3276.29 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16374815.41 | 7853.27 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100928E+09 | 8007.51 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303509E+09 | 8019.15 | 13-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.470706E+09 | 8048.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.753698E+09 | 7839.40 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.621240E+09 | 7799.07 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691089E+09 | 7819.59 | 29-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190055E+09 | 7789.01 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113862E+09 | 7803.89 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9659698.67 | 3457.98 | 01-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9881492.19 | 4513.65 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81925809.82 | 7801.93 | 12-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373117E+09 | 7808.51 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.643845E+09 | 7820.57 | 13-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.753698E+09 | 7839.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 30192938.22 | 2178.33 | 09-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 193296.22 | 589.74 | 09-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8966111.97 | 2071.66 | 30-MAR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 138920.19 | 122.24 | 01-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48606.76 | 4.65 | 02-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 390988.80 | 5.26 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 967462.65 | 5.84 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1269608.19 | 5.73 | 17-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 410071.17 | 5.25 | 13-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 183942.07 | 5.41 | 18-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6627130.70 | 2032.62 | 22-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49389076.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30192938.22 | 2178.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.387530E+09 | 26788.77 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137529E+09 | 26552.09 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159563E+09 | 26738.91 | 30-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15519460.29 | 26510.32 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1279963.02 | 7903.16 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 60446762.96 | 26533.19 | 06-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169266E+09 | 26526.75 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.931134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.387530E+09 | 26788.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.784578E+09 | 11878.76 | 02-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.848804E+09 | 11843.14 | 21-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109709E+10 | 11863.86 | 30-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383165E+09 | 11842.36 | 01-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.305253E+09 | 11815.82 | 15-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45967591.46 | 7705.38 | 13-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1798593.15 | 1865.46 | 06-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3554116.01 | 2413.20 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50202385.41 | 11093.41 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138069E+09 | 11806.95 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.375185E+09 | 11839.41 | 27-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.625820E+09 | 11855.29 | 13-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1798593.15 | 1865.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109709E+10 | 11878.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.892149E+09 | 8533.19 | 02-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.841859E+09 | 8529.85 | 10-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.855783E+09 | 8513.25 | 30-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244689E+09 | 8506.00 | 01-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147368E+09 | 7123.87 | 12-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34493266.47 | 5139.62 | 12-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4011961.39 | 1742.88 | 14-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4134653.75 | 1789.41 | 29-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67097565.29 | 6231.15 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128942E+09 | 8481.75 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.522963E+09 | 8502.96 | 27-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.787259E+09 | 8526.69 | 15-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4011961.39 | 1742.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.892149E+09 | 8533.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129510E+10 | 10262.52 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.941243E+09 | 10099.99 | 11-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105740E+10 | 10096.16 | 09-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264126E+09 | 10062.06 | 01-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104831E+09 | 10050.00 | 16-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6048439.76 | 6141.79 | 01-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 106706.32 | 533.53 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25047142.56 | 10051.16 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152152E+09 | 10051.17 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.650067E+09 | 10095.86 | 18-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110571E+10 | 10095.99 | 14-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.560182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129510E+10 | 10262.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140782E+10 | 9114.47 | 02-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117267E+10 | 9086.38 | 21-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127484E+10 | 9094.04 | 07-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.479290E+09 | 9085.63 | 01-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.353674E+09 | 8821.10 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84049683.34 | 5521.22 | 01-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14283989.74 | 2314.98 | 06-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28795220.36 | 3959.39 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118042E+09 | 7046.35 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.296371E+09 | 9059.50 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.903616E+09 | 9082.70 | 27-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129439E+10 | 9091.61 | 11-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 14283989.74 | 2314.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140782E+10 | 9114.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.124815E+11 | 0.112247E+11 | 50676.46 | 18-JAN-13:10 | 50676.46 | 0.00 |
February | 0.00 | 0.00 | 0.744842E+10 | 0.616223E+10 | 47571.52 | 01-FEB-12:00 | 47571.52 | 0.00 |
March | 0.00 | 0.00 | 0.916729E+10 | 0.695946E+10 | 54623.85 | 23-MAR-14:50 | 39495.73 | 0.00 |
April | 0.00 | 0.00 | 0.193015E+11 | 0.154379E+11 | 59280.92 | 26-APR-14:05 | 55698.79 | 0.00 |
May | 0.00 | 0.00 | 0.202920E+11 | 0.162583E+11 | 47407.76 | 04-MAY-14:10 | 41462.62 | 0.00 |
June | 0.00 | 0.00 | 0.369623E+11 | 0.266894E+11 | 70485.02 | 28-JUN-10:50 | 43185.09 | 0.00 |
July | 0.00 | 0.00 | 0.587945E+11 | 0.395120E+11 | 84482.07 | 28-JUL-14:10 | 44821.90 | 0.00 |
August | 0.00 | 0.00 | 0.679523E+11 | 0.442041E+11 | 90194.42 | 15-AUG-16:00 | 48198.08 | 0.00 |
September | 0.00 | 0.00 | 0.438100E+11 | 0.304271E+11 | 78816.95 | 29-SEP-14:40 | 78816.95 | 0.00 |
October | 0.00 | 0.00 | 0.466706E+11 | 0.367900E+11 | 93155.32 | 04-OCT-10:50 | 51520.82 | 0.00 |
November | 0.00 | 0.00 | 0.140024E+11 | 0.121538E+11 | 49240.03 | 29-NOV-12:00 | 49240.03 | 0.00 |
December | 0.00 | 0.00 | 0.144690E+11 | 0.139227E+11 | 51663.61 | 19-DEC-12:00 | 51663.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.351352E+12 | 0.259742E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.744842E+10 | 0.616223E+10 | 47407.76 | 39495.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.679523E+11 | 0.442041E+11 | 93155.32 | 78816.95 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.105765E+11 | 0.938085E+10 | 46303.50 | 18-JAN-13:03 | 46303.50 | 0.00 |
February | 0.00 | 0.00 | 0.630347E+10 | 0.518102E+10 | 39345.52 | 01-FEB-12:00 | 39345.52 | 0.00 |
March | 0.00 | 0.00 | 0.806423E+10 | 0.610802E+10 | 52232.98 | 23-MAR-14:05 | 40976.91 | 0.00 |
April | 0.00 | 0.00 | 0.174866E+11 | 0.139280E+11 | 57648.93 | 26-APR-14:05 | 54094.96 | 0.00 |
May | 0.00 | 0.00 | 0.176922E+11 | 0.140186E+11 | 44844.71 | 04-MAY-14:05 | 39447.81 | 0.00 |
June | 0.00 | 0.00 | 0.327967E+11 | 0.235813E+11 | 64169.00 | 29-JUN-16:00 | 41913.95 | 0.00 |
July | 0.00 | 0.00 | 0.519163E+11 | 0.349533E+11 | 79402.42 | 28-JUL-14:05 | 42193.93 | 0.00 |
August | 0.00 | 0.00 | 0.601000E+11 | 0.391976E+11 | 82140.66 | 15-AUG-16:00 | 43992.71 | 0.00 |
September | 0.00 | 0.00 | 0.383496E+11 | 0.266862E+11 | 77393.93 | 29-SEP-14:05 | 77393.93 | 0.00 |
October | 0.00 | 0.00 | 0.401623E+11 | 0.317281E+11 | 81436.49 | 04-OCT-10:30 | 44634.09 | 0.00 |
November | 0.00 | 0.00 | 0.117317E+11 | 0.100735E+11 | 42494.01 | 28-NOV-14:00 | 42494.01 | 0.00 |
December | 0.00 | 0.00 | 0.122249E+11 | 0.117319E+11 | 46590.57 | 19-DEC-13:07 | 46590.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.307404E+12 | 0.226568E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.630347E+10 | 0.518102E+10 | 39345.52 | 39345.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.601000E+11 | 0.391976E+11 | 82140.66 | 77393.93 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112969E+11 | 0.987959E+10 | 53982.12 | 18-JAN-14:15 | 53982.12 | 0.00 |
February | 0.00 | 0.00 | 0.670064E+10 | 0.539931E+10 | 43921.08 | 01-FEB-13:05 | 43921.08 | 0.00 |
March | 0.00 | 0.00 | 0.885037E+10 | 0.660790E+10 | 56494.40 | 23-MAR-14:40 | 41476.23 | 0.00 |
April | 0.00 | 0.00 | 0.198769E+11 | 0.156276E+11 | 73689.84 | 26-APR-14:00 | 70294.16 | 0.00 |
May | 0.00 | 0.00 | 0.199986E+11 | 0.155738E+11 | 60211.59 | 03-MAY-13:00 | 60211.59 | 0.00 |
June | 0.00 | 0.00 | 0.372058E+11 | 0.264815E+11 | 75528.19 | 29-JUN-13:20 | 47333.74 | 0.00 |
July | 0.00 | 0.00 | 0.595611E+11 | 0.407340E+11 | 88352.50 | 31-JUL-13:50 | 74090.98 | 0.00 |
August | 0.00 | 0.00 | 0.675478E+11 | 0.449207E+11 | 90374.24 | 15-AUG-16:00 | 48343.86 | 0.00 |
September | 0.00 | 0.00 | 0.414832E+11 | 0.286285E+11 | 92831.47 | 29-SEP-13:40 | 92831.47 | 0.00 |
October | 0.00 | 0.00 | 0.430237E+11 | 0.339612E+11 | 93069.23 | 16-OCT-13:05 | 93069.23 | 0.00 |
November | 0.00 | 0.00 | 0.121876E+11 | 0.103221E+11 | 58833.28 | 19-NOV-13:31 | 58833.28 | 0.00 |
December | 0.00 | 0.00 | 0.127092E+11 | 0.121377E+11 | 52650.87 | 19-DEC-13:10 | 52650.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.340442E+12 | 0.250274E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.670064E+10 | 0.539931E+10 | 43921.08 | 41476.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.675478E+11 | 0.449207E+11 | 93069.23 | 93069.23 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 3282.07 | 277437.36 | 09-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 3136.81 | 203286.68 | 13-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3459.56 | 202087.88 | 27-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 973.69 | 197647.21 | 01-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 640.42 | 131996.28 | 10-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 156.31 | 66605.30 | 01-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.21 | 6292.12 | 17-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 31.10 | 8722.61 | 28-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 148.06 | 102876.75 | 20-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 390.27 | 146254.30 | 25-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1485.92 | 183781.24 | 06-NOV-07:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2603.04 | 190759.60 | 27-DEC-07:03 |
Annual Sum or Average | 0.00 | 1353.79 | ||||
Minimum of Months | 0.00 | 0.00 | 25.21 | 6292.12 | ||
Maximum of Months | 0.00 | 0.00 | 3459.56 | 277437.36 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1492.31 | 5440.33 | 31-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1503.33 | 5440.48 | 02-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1590.60 | 5413.65 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1448.47 | 5315.63 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1466.11 | 5198.28 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1471.63 | 5065.37 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1321.73 | 4962.71 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1460.09 | 4952.99 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1374.23 | 5036.79 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1404.02 | 5169.38 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1463.72 | 5298.13 | 30-NOV-12:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1432.51 | 5394.35 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1452.12 | ||||
Minimum of Months | 0.00 | 0.00 | 1321.73 | 4952.99 | ||
Maximum of Months | 0.00 | 0.00 | 1590.60 | 5440.48 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.474449E+10 | 0.53 | 6972.92 | 18-JAN-15:07 | 1.37 |
February | 0.412791E+10 | 0.53 | 6522.17 | 03-FEB-15:10 | 1.35 |
March | 0.471074E+10 | 0.55 | 6752.74 | 23-MAR-15:30 | 1.35 |
April | 0.501699E+10 | 0.56 | 7407.02 | 26-APR-14:10 | 1.40 |
May | 0.522446E+10 | 0.57 | 6439.90 | 03-MAY-15:20 | 1.32 |
June | 0.583431E+10 | 0.62 | 7136.14 | 30-JUN-16:00 | 1.38 |
July | 0.658112E+10 | 0.63 | 8431.48 | 31-JUL-14:30 | 1.48 |
August | 0.737896E+10 | 0.68 | 8866.01 | 18-AUG-15:00 | 1.51 |
September | 0.616473E+10 | 0.62 | 9858.84 | 29-SEP-16:00 | 1.59 |
October | 0.636628E+10 | 0.62 | 10490.59 | 17-OCT-16:00 | 1.63 |
November | 0.504059E+10 | 0.56 | 6485.89 | 30-NOV-15:03 | 1.33 |
December | 0.492289E+10 | 0.55 | 7105.15 | 19-DEC-15:30 | 1.40 |
Annual Sum or Average | 0.661135E+11 | 0.59 | |||
Minimum of Months | 0.412791E+10 | 0.53 | 6439.90 | 1.32 | |
Maximum of Months | 0.737896E+10 | 0.68 | 10490.59 | 1.63 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.387350E+10 | 0.51 | 6319.85 | 18-JAN-15:03 | 1.35 |
February | 0.338488E+10 | 0.50 | 5841.80 | 03-FEB-15:05 | 1.32 |
March | 0.384564E+10 | 0.53 | 6527.96 | 23-MAR-14:05 | 1.37 |
April | 0.430631E+10 | 0.55 | 7416.21 | 26-APR-14:05 | 1.45 |
May | 0.428529E+10 | 0.55 | 6206.30 | 03-MAY-14:05 | 1.34 |
June | 0.491211E+10 | 0.59 | 6678.13 | 30-JUN-16:00 | 1.38 |
July | 0.557514E+10 | 0.61 | 7945.87 | 31-JUL-14:05 | 1.49 |
August | 0.627648E+10 | 0.65 | 8249.75 | 17-AUG-14:05 | 1.51 |
September | 0.514443E+10 | 0.59 | 10338.17 | 29-SEP-15:50 | 1.67 |
October | 0.521498E+10 | 0.58 | 10373.11 | 16-OCT-15:30 | 1.68 |
November | 0.397525E+10 | 0.52 | 5636.72 | 10-NOV-14:00 | 1.29 |
December | 0.394581E+10 | 0.51 | 6207.92 | 19-DEC-15:03 | 1.36 |
Annual Sum or Average | 0.547398E+11 | 0.56 | |||
Minimum of Months | 0.338488E+10 | 0.50 | 5636.72 | 1.29 | |
Maximum of Months | 0.627648E+10 | 0.65 | 10373.11 | 1.68 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.393764E+10 | 0.47 | 5824.22 | 18-JAN-14:50 | 1.20 |
February | 0.345868E+10 | 0.47 | 5458.92 | 13-FEB-07:03 | 1.16 |
March | 0.404176E+10 | 0.49 | 6517.87 | 23-MAR-14:50 | 1.25 |
April | 0.447542E+10 | 0.52 | 7722.54 | 26-APR-14:00 | 1.35 |
May | 0.447699E+10 | 0.51 | 6751.93 | 03-MAY-14:50 | 1.28 |
June | 0.511567E+10 | 0.55 | 7159.52 | 30-JUN-15:30 | 1.30 |
July | 0.579130E+10 | 0.57 | 8314.78 | 31-JUL-14:30 | 1.39 |
August | 0.637221E+10 | 0.60 | 8505.02 | 17-AUG-14:40 | 1.40 |
September | 0.508685E+10 | 0.54 | 10787.99 | 29-SEP-15:30 | 1.56 |
October | 0.503864E+10 | 0.53 | 10755.50 | 16-OCT-15:10 | 1.56 |
November | 0.390502E+10 | 0.48 | 5305.72 | 10-NOV-13:50 | 1.15 |
December | 0.397925E+10 | 0.47 | 5602.14 | 19-DEC-14:40 | 1.19 |
Annual Sum or Average | 0.556794E+11 | 0.52 | |||
Minimum of Months | 0.345868E+10 | 0.47 | 5305.72 | 1.15 | |
Maximum of Months | 0.637221E+10 | 0.60 | 10787.99 | 1.56 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 62913865.36 | 56622478.82 | 755.14 | 02-JAN-07:03 | 679.63 | 679.63 | 40.97 | 2.43 |
February | 53551515.23 | 48196363.70 | 701.13 | 06-FEB-07:03 | 631.02 | 631.02 | 39.93 | 2.19 |
March | 68238503.74 | 61414653.37 | 701.32 | 30-MAR-06:02 | 631.18 | 631.18 | 41.10 | 2.19 |
April | 20359182.05 | 18323263.85 | 701.03 | 01-APR-06:03 | 630.93 | 630.93 | 39.27 | 2.19 |
May | 14506738.78 | 13056064.90 | 584.60 | 15-MAY-06:03 | 526.14 | 526.14 | 34.16 | 1.18 |
June | 3356493.85 | 3020844.47 | 423.08 | 01-JUN-06:03 | 380.77 | 380.77 | 33.88 | 0.61 |
July | 456199.71 | 410579.74 | 40.30 | 17-JUL-06:10 | 36.27 | 36.27 | 24.19 | 0.04 |
August | 571544.37 | 514389.94 | 56.67 | 28-AUG-06:10 | 51.00 | 51.00 | 25.03 | 0.06 |
September | 2724735.55 | 2452261.99 | 528.97 | 20-SEP-06:03 | 476.08 | 476.08 | 33.04 | 0.91 |
October | 7869786.77 | 7082808.09 | 616.49 | 30-OCT-06:03 | 554.84 | 554.84 | 38.39 | 1.43 |
November | 27500551.38 | 24750496.24 | 689.41 | 24-NOV-07:03 | 620.47 | 620.47 | 39.74 | 2.12 |
December | 49805410.62 | 44824869.56 | 701.18 | 26-DEC-07:03 | 631.06 | 631.06 | 40.23 | 2.19 |
Annual Sum or Average | 0.311855E+09 | 0.280669E+09 | ||||||
Minimum of Months | 456199.71 | 410579.74 | 40.30 | 36.27 | 36.27 | 24.19 | 0.04 | |
Maximum of Months | 68238503.74 | 61414653.37 | 755.14 | 679.63 | 679.63 | 41.10 | 2.43 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.36 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.32 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.33 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 57.30 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.65 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.51 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.62 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.64 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.62 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.36 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.52 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.45 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.30 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.36 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 60.00 | 60.00 | 3282.07 | 277437.36 | 09-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23.75 | 23.75 | 3136.81 | 203286.68 | 13-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 28.29 | 28.29 | 3459.56 | 202087.88 | 27-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.16 | 25.16 | 973.69 | 197647.21 | 01-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.81 | 26.81 | 640.42 | 131996.28 | 10-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 31.84 | 31.84 | 156.31 | 66605.30 | 01-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.12 | 27.12 | 25.21 | 6292.12 | 17-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 26.09 | 26.09 | 31.10 | 8722.61 | 28-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.42 | 26.42 | 148.06 | 102876.75 | 20-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24.20 | 24.20 | 390.27 | 146254.30 | 25-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.32 | 27.32 | 1485.92 | 183781.24 | 06-NOV-07:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.59 | 23.59 | 2603.04 | 190759.60 | 27-DEC-07:03 |
Annual Sum or Average | 0.00 | 1353.79 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.59 | 23.59 | 25.21 | 6292.12 | ||
Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 3459.56 | 277437.36 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.37 | 58.37 | 1492.31 | 5440.33 | 31-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.92 | 57.92 | 1503.33 | 5440.48 | 02-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.93 | 57.93 | 1590.60 | 5413.65 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.97 | 57.97 | 1448.47 | 5315.63 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.43 | 58.43 | 1466.11 | 5198.28 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.07 | 58.07 | 1471.63 | 5065.37 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.11 | 58.11 | 1321.73 | 4962.71 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.13 | 58.13 | 1460.09 | 4952.99 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.12 | 58.12 | 1374.23 | 5036.79 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.29 | 57.29 | 1404.02 | 5169.38 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.03 | 58.03 | 1463.72 | 5298.13 | 30-NOV-12:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.98 | 57.98 | 1432.51 | 5394.35 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1452.12 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.29 | 57.29 | 1321.73 | 4952.99 | ||
Maximum of Months | 0.00 | 0.00 | 58.43 | 58.43 | 1590.60 | 5440.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.208601E+10 | 0.00 | 0.00 | 0.779111E+10 | 0.00 | 0.00 |
February | 0.206368E+10 | 0.00 | 0.00 | 0.600117E+10 | 0.00 | 0.00 |
March | 0.288831E+10 | 0.00 | 0.00 | 0.695571E+10 | 0.00 | 0.00 |
April | 0.736696E+09 | 0.00 | 0.00 | 0.965925E+10 | 0.00 | 0.00 |
May | 0.593762E+09 | 0.00 | 0.00 | 0.101700E+11 | 0.00 | 0.00 |
June | 0.223958E+09 | 0.00 | 0.00 | 0.144942E+11 | 0.00 | 0.00 |
July | 46792817.48 | 0.00 | 0.00 | 0.200865E+11 | 0.00 | 0.00 |
August | 44586780.83 | 0.00 | 0.00 | 0.229193E+11 | 0.00 | 0.00 |
September | 0.105936E+09 | 0.00 | 0.00 | 0.165305E+11 | 0.00 | 0.00 |
October | 0.197790E+09 | 0.00 | 0.00 | 0.175037E+11 | 0.00 | 0.00 |
November | 0.659271E+09 | 0.00 | 0.00 | 0.846468E+10 | 0.00 | 0.00 |
December | 0.156860E+10 | 0.00 | 0.00 | 0.839704E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112154E+11 | 0.00 | 0.00 | 0.148973E+12 | 0.00 | 0.00 |
Minimum of Months | 44586780.83 | 0.00 | 0.00 | 0.600117E+10 | 0.00 | 0.00 |
Maximum of Months | 0.288831E+10 | 0.00 | 0.00 | 0.229193E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.199924E+10 | 0.00 | 0.00 | 0.648378E+10 | 0.00 | 0.00 |
February | 0.163737E+10 | 0.00 | 0.00 | 0.498320E+10 | 0.00 | 0.00 |
March | 0.199931E+10 | 0.00 | 0.00 | 0.582625E+10 | 0.00 | 0.00 |
April | 0.420529E+09 | 0.00 | 0.00 | 0.853527E+10 | 0.00 | 0.00 |
May | 0.220906E+09 | 0.00 | 0.00 | 0.863137E+10 | 0.00 | 0.00 |
June | 16934707.16 | 0.00 | 0.00 | 0.126365E+11 | 0.00 | 0.00 |
July | 861924.53 | 0.00 | 0.00 | 0.175570E+11 | 0.00 | 0.00 |
August | 1267608.72 | 0.00 | 0.00 | 0.200743E+11 | 0.00 | 0.00 |
September | 21496540.36 | 0.00 | 0.00 | 0.142743E+11 | 0.00 | 0.00 |
October | 0.138077E+09 | 0.00 | 0.00 | 0.148782E+11 | 0.00 | 0.00 |
November | 0.712044E+09 | 0.00 | 0.00 | 0.687730E+10 | 0.00 | 0.00 |
December | 0.146832E+10 | 0.00 | 0.00 | 0.691250E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.863635E+10 | 0.00 | 0.00 | 0.127670E+12 | 0.00 | 0.00 |
Minimum of Months | 861924.53 | 0.00 | 0.00 | 0.498320E+10 | 0.00 | 0.00 |
Maximum of Months | 0.199931E+10 | 0.00 | 0.00 | 0.200743E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.479737E+10 | 0.00 | 0.00 | 0.675877E+10 | 0.00 | 0.00 |
February | 0.394230E+10 | 0.00 | 0.00 | 0.517796E+10 | 0.00 | 0.00 |
March | 0.445364E+10 | 0.00 | 0.00 | 0.623150E+10 | 0.00 | 0.00 |
April | 0.138693E+10 | 0.00 | 0.00 | 0.930543E+10 | 0.00 | 0.00 |
May | 0.912455E+09 | 0.00 | 0.00 | 0.941195E+10 | 0.00 | 0.00 |
June | 0.170950E+09 | 0.00 | 0.00 | 0.139168E+11 | 0.00 | 0.00 |
July | 21062006.92 | 0.00 | 0.00 | 0.195972E+11 | 0.00 | 0.00 |
August | 37860304.64 | 0.00 | 0.00 | 0.219413E+11 | 0.00 | 0.00 |
September | 0.260799E+09 | 0.00 | 0.00 | 0.150576E+11 | 0.00 | 0.00 |
October | 0.715718E+09 | 0.00 | 0.00 | 0.155108E+11 | 0.00 | 0.00 |
November | 0.251228E+10 | 0.00 | 0.00 | 0.696245E+10 | 0.00 | 0.00 |
December | 0.398907E+10 | 0.00 | 0.00 | 0.711300E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.232004E+11 | 0.00 | 0.00 | 0.136985E+12 | 0.00 | 0.00 |
Minimum of Months | 21062006.92 | 0.00 | 0.00 | 0.517796E+10 | 0.00 | 0.00 |
Maximum of Months | 0.479737E+10 | 0.00 | 0.00 | 0.219413E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.474449E+10 | 0.124815E+11 | 0.208601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.412791E+10 | 0.744842E+10 | 0.206368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.471074E+10 | 0.916729E+10 | 0.288831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.501699E+10 | 0.193015E+11 | 0.736696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.522446E+10 | 0.202920E+11 | 0.593762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583431E+10 | 0.369623E+11 | 0.223958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658112E+10 | 0.587945E+11 | 46792817.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.737896E+10 | 0.679523E+11 | 44586780.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.616473E+10 | 0.438100E+11 | 0.105936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.636628E+10 | 0.466706E+11 | 0.197790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504059E+10 | 0.140024E+11 | 0.659271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492289E+10 | 0.144690E+11 | 0.156860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.661135E+11 | 0.351352E+12 | 0.112154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.412791E+10 | 0.744842E+10 | 44586780.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737896E+10 | 0.679523E+11 | 0.288831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.387350E+10 | 0.105765E+11 | 0.199924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338488E+10 | 0.630347E+10 | 0.163737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384564E+10 | 0.806423E+10 | 0.199931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430631E+10 | 0.174866E+11 | 0.420529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.428529E+10 | 0.176922E+11 | 0.220906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.491211E+10 | 0.327967E+11 | 16934707.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.557514E+10 | 0.519163E+11 | 861924.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.627648E+10 | 0.601000E+11 | 1267608.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.514443E+10 | 0.383496E+11 | 21496540.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.521498E+10 | 0.401623E+11 | 0.138077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397525E+10 | 0.117317E+11 | 0.712044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394581E+10 | 0.122249E+11 | 0.146832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547398E+11 | 0.307404E+12 | 0.863635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.338488E+10 | 0.630347E+10 | 861924.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.627648E+10 | 0.601000E+11 | 0.199931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.393764E+10 | 0.112969E+11 | 0.479737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.345868E+10 | 0.670064E+10 | 0.394230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404176E+10 | 0.885037E+10 | 0.445364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.447542E+10 | 0.198769E+11 | 0.138693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.447699E+10 | 0.199986E+11 | 0.912455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.511567E+10 | 0.372058E+11 | 0.170950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.579130E+10 | 0.595611E+11 | 21062006.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.637221E+10 | 0.675478E+11 | 37860304.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.508685E+10 | 0.414832E+11 | 0.260799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.503864E+10 | 0.430237E+11 | 0.715718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390502E+10 | 0.121876E+11 | 0.251228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397925E+10 | 0.127092E+11 | 0.398907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556794E+11 | 0.340442E+12 | 0.232004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345868E+10 | 0.670064E+10 | 21062006.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.637221E+10 | 0.675478E+11 | 0.479737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.474449E+10 | 0.208601E+10 | 0.00 | 0.00 | 0.304662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.412791E+10 | 0.206368E+10 | 0.00 | 0.00 | 0.187326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.471074E+10 | 0.288831E+10 | 0.00 | 0.00 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.501699E+10 | 0.736696E+09 | 0.00 | 0.00 | 0.464226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.522446E+10 | 0.593762E+09 | 0.00 | 0.00 | 0.494558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583431E+10 | 0.223958E+09 | 0.00 | 0.00 | 0.865990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.658112E+10 | 46792817.48 | 0.00 | 0.00 | 0.135054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.737896E+10 | 44586780.83 | 0.00 | 0.00 | 0.155403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.616473E+10 | 0.105936E+09 | 0.00 | 0.00 | 0.103658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.636628E+10 | 0.197790E+09 | 0.00 | 0.00 | 0.111374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504059E+10 | 0.659271E+09 | 0.00 | 0.00 | 0.342409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492289E+10 | 0.156860E+10 | 0.00 | 0.00 | 0.347414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.661135E+11 | 0.112154E+11 | 0.00 | 0.00 | 0.828597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.412791E+10 | 44586780.83 | 0.00 | 0.00 | 0.187326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.737896E+10 | 0.288831E+10 | 0.00 | 0.00 | 0.155403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.387350E+10 | 0.199924E+10 | 0.00 | 0.00 | 0.261027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338488E+10 | 0.163737E+10 | 0.00 | 0.00 | 0.159831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384564E+10 | 0.199931E+10 | 0.00 | 0.00 | 0.198062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.430631E+10 | 0.420529E+09 | 0.00 | 0.00 | 0.422896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.428529E+10 | 0.220906E+09 | 0.00 | 0.00 | 0.434608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.491211E+10 | 16934707.16 | 0.00 | 0.00 | 0.772440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.557514E+10 | 861924.53 | 0.00 | 0.00 | 0.119819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.627648E+10 | 1267608.72 | 0.00 | 0.00 | 0.137978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.514443E+10 | 21496540.36 | 0.00 | 0.00 | 0.912984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.521498E+10 | 0.138077E+09 | 0.00 | 0.00 | 0.966323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397525E+10 | 0.712044E+09 | 0.00 | 0.00 | 0.290205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394581E+10 | 0.146832E+10 | 0.00 | 0.00 | 0.296669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547398E+11 | 0.863635E+10 | 0.00 | 0.00 | 0.729302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.338488E+10 | 861924.53 | 0.00 | 0.00 | 0.159831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.627648E+10 | 0.199931E+10 | 0.00 | 0.00 | 0.137978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.393764E+10 | 0.479737E+10 | 0.00 | 0.00 | 0.282113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.345868E+10 | 0.394230E+10 | 0.00 | 0.00 | 0.171928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404176E+10 | 0.445364E+10 | 0.00 | 0.00 | 0.218973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.447542E+10 | 0.138693E+10 | 0.00 | 0.00 | 0.483000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.447699E+10 | 0.912455E+09 | 0.00 | 0.00 | 0.493497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.511567E+10 | 0.170950E+09 | 0.00 | 0.00 | 0.880115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.579130E+10 | 21062006.92 | 0.00 | 0.00 | 0.138059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.637221E+10 | 37860304.64 | 0.00 | 0.00 | 0.155691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.508685E+10 | 0.260799E+09 | 0.00 | 0.00 | 0.997071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.503864E+10 | 0.715718E+09 | 0.00 | 0.00 | 0.104722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.390502E+10 | 0.251228E+10 | 0.00 | 0.00 | 0.305743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397925E+10 | 0.398907E+10 | 0.00 | 0.00 | 0.313375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556794E+11 | 0.232004E+11 | 0.00 | 0.00 | 0.813054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345868E+10 | 21062006.92 | 0.00 | 0.00 | 0.171928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.637221E+10 | 0.479737E+10 | 0.00 | 0.00 | 0.155691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207694E+10 | 31834258.42 | 0.00 | 43549398.40 | 1526143.42 | 0.00 | 0.149356E+11 | 0.00 | 0.87 |
February | 0.169784E+10 | 14167630.83 | 0.00 | 38947952.90 | 0.00 | 0.00 | 0.156409E+11 | 0.00 | 0.92 |
March | 0.138372E+10 | 601071.10 | 0.00 | 45374621.21 | 21064250.90 | 0.00 | 0.185370E+11 | 0.00 | 0.94 |
April | 0.139013E+10 | 30680330.26 | 0.00 | 43118309.26 | 32949967.87 | 0.00 | 0.150452E+11 | 0.00 | 1.08 |
May | 0.137561E+10 | 14975328.93 | 0.00 | 48069023.75 | 34557.51 | 0.00 | 0.161985E+11 | 0.00 | 1.16 |
June | 0.708407E+09 | 0.507241E+09 | 0.00 | 44156145.35 | 35785765.79 | 0.00 | 0.112653E+11 | 0.00 | 1.29 |
July | 0.541820E+09 | 0.243715E+10 | 0.00 | 27093184.43 | 0.171048E+09 | 0.00 | 0.467281E+10 | 0.00 | 1.12 |
August | 0.248671E+09 | 0.332210E+10 | 0.00 | 25547458.49 | 0.222031E+09 | 0.00 | 0.441444E+10 | 0.00 | 1.20 |
September | 0.552126E+09 | 0.105263E+10 | 0.00 | 38738722.54 | 56708530.87 | 0.00 | 0.914854E+10 | 0.00 | 1.21 |
October | 0.689141E+09 | 0.165002E+10 | 0.00 | 35817822.14 | 0.121207E+09 | 0.00 | 0.918627E+10 | 0.00 | 1.06 |
November | 0.151671E+10 | 6825578.30 | 0.00 | 50623952.33 | 14165922.85 | 0.00 | 0.171328E+11 | 0.00 | 1.03 |
December | 0.193428E+10 | 7057813.33 | 0.00 | 46848221.72 | 0.00 | 0.00 | 0.150281E+11 | 0.00 | 0.89 |
Annual Sum or Average | 0.141154E+11 | 0.907528E+10 | 0.00 | 0.487885E+09 | 0.676522E+09 | 0.00 | 0.151205E+12 | 0.00 | 1.06 |
Minimum of Months | 0.248671E+09 | 601071.10 | 0.00 | 25547458.49 | 0.00 | 0.00 | 0.441444E+10 | 0.00 | 0.87 |
Maximum of Months | 0.207694E+10 | 0.332210E+10 | 0.00 | 50623952.33 | 0.222031E+09 | 0.00 | 0.185370E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.615650E+10 | 14336275.02 | 0.00 | 12583443.30 | 25107187.10 | 3185322.92 | 0.432445E+10 | 0.00 | 0.55 |
February | 0.559750E+10 | 10029643.67 | 0.00 | 12633030.53 | 0.00 | 0.00 | 0.528152E+10 | 0.00 | 0.59 |
March | 0.631177E+10 | 1161439.53 | 0.00 | 13347404.71 | 24166817.24 | 0.00 | 0.605258E+10 | 0.00 | 0.60 |
April | 0.374685E+10 | 9797696.70 | 0.00 | 19033311.85 | 58055164.93 | 0.00 | 0.691915E+10 | 0.00 | 0.72 |
May | 0.355774E+10 | 11700844.89 | 0.00 | 22024301.02 | 1059247.71 | 0.00 | 0.779110E+10 | 0.00 | 0.77 |
June | 0.157864E+10 | 0.357208E+09 | 0.00 | 22407811.92 | 51529716.19 | 0.00 | 0.616941E+10 | 0.00 | 0.87 |
July | 0.833755E+09 | 0.173444E+10 | 0.00 | 13826317.82 | 0.161771E+09 | 0.00 | 0.245222E+10 | 0.00 | 0.76 |
August | 0.619573E+09 | 0.238404E+10 | 0.00 | 12751365.28 | 0.225854E+09 | 0.00 | 0.225375E+10 | 0.00 | 0.82 |
September | 0.149666E+10 | 0.721023E+09 | 0.00 | 18256003.58 | 0.119375E+09 | 0.00 | 0.449648E+10 | 0.00 | 0.80 |
October | 0.203046E+10 | 0.117062E+10 | 0.00 | 15360880.09 | 0.156803E+09 | 0.00 | 0.398372E+10 | 0.00 | 0.70 |
November | 0.466557E+10 | 4491940.79 | 0.00 | 19735383.58 | 17927325.14 | 0.00 | 0.668134E+10 | 0.00 | 0.64 |
December | 0.554496E+10 | 6614975.17 | 0.00 | 14890851.82 | 3285003.57 | 0.00 | 0.478729E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.421400E+11 | 0.642547E+10 | 0.00 | 0.196850E+09 | 0.844933E+09 | 3185322.92 | 0.611930E+11 | 0.00 | 0.70 |
Minimum of Months | 0.619573E+09 | 1161439.53 | 0.00 | 12583443.30 | 0.00 | 0.00 | 0.225375E+10 | 0.00 | 0.55 |
Maximum of Months | 0.631177E+10 | 0.238404E+10 | 0.00 | 22407811.92 | 0.225854E+09 | 3185322.92 | 0.779110E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.777648E+10 | 5552876.89 | 0.00 | 6612742.45 | 20697677.37 | 0.121438E+09 | 0.269668E+10 | 0.00 | 0.58 |
February | 0.737605E+10 | 364696.26 | 0.00 | 7562001.06 | 383148.77 | 21263495.67 | 0.383653E+10 | 0.00 | 0.62 |
March | 0.891762E+10 | 0.00 | 0.00 | 8279120.43 | 10413506.51 | 30638266.42 | 0.448745E+10 | 0.00 | 0.64 |
April | 0.549910E+10 | 604149.18 | 0.00 | 17373634.92 | 7140553.11 | 1532066.74 | 0.711787E+10 | 0.00 | 0.79 |
May | 0.520700E+10 | 1776764.79 | 0.00 | 19876091.50 | 0.00 | 689700.62 | 0.819558E+10 | 0.00 | 0.84 |
June | 0.268735E+10 | 0.104204E+09 | 0.00 | 23246801.02 | 2480450.42 | 0.00 | 0.678596E+10 | 0.00 | 0.97 |
July | 0.147698E+10 | 0.106441E+10 | 0.00 | 14023766.66 | 0.138837E+09 | 0.00 | 0.261188E+10 | 0.00 | 0.84 |
August | 0.105069E+10 | 0.138568E+10 | 0.00 | 13069039.24 | 0.249977E+09 | 0.00 | 0.198929E+10 | 0.00 | 0.88 |
September | 0.263349E+10 | 0.356445E+09 | 0.00 | 16270448.24 | 0.126624E+09 | 0.00 | 0.411531E+10 | 0.00 | 0.86 |
October | 0.323966E+10 | 0.936882E+09 | 0.00 | 10805300.94 | 0.223618E+09 | 0.00 | 0.261851E+10 | 0.00 | 0.71 |
November | 0.657947E+10 | 86387.10 | 0.00 | 11153476.49 | 4441173.35 | 17752820.85 | 0.458883E+10 | 0.00 | 0.65 |
December | 0.734667E+10 | 242321.58 | 0.00 | 7060900.69 | 1022637.71 | 29637732.57 | 0.273212E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.597906E+11 | 0.385625E+10 | 0.00 | 0.155333E+09 | 0.785636E+09 | 0.222952E+09 | 0.517760E+11 | 0.00 | 0.75 |
Minimum of Months | 0.105069E+10 | 0.00 | 0.00 | 6612742.45 | 0.00 | 0.00 | 0.198929E+10 | 0.00 | 0.58 |
Maximum of Months | 0.891762E+10 | 0.138568E+10 | 0.00 | 23246801.02 | 0.249977E+09 | 0.121438E+09 | 0.819558E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261170E+10 | 212583.48 | 0.00 | 313532.10 | 8078721.60 | 0.560354E+09 | 0.104235E+09 | 0.00 | 0.84 |
February | 0.279378E+10 | 85601.89 | 0.00 | 246906.72 | 121044.07 | 0.393923E+09 | 0.227247E+09 | 0.00 | 0.89 |
March | 0.324959E+10 | 0.00 | 0.00 | 618017.89 | 3289827.18 | 0.452058E+09 | 0.396627E+09 | 0.00 | 0.91 |
April | 0.231440E+10 | 167582.61 | 0.00 | 2604966.02 | 2255838.19 | 81460614.52 | 0.116182E+10 | 0.00 | 1.05 |
May | 0.219154E+10 | 472002.92 | 0.00 | 3805425.53 | 0.00 | 18252859.25 | 0.163716E+10 | 0.00 | 1.14 |
June | 0.120126E+10 | 29966211.85 | 0.00 | 5309562.43 | 783622.04 | 894689.12 | 0.154714E+10 | 0.00 | 1.32 |
July | 0.626848E+09 | 0.312722E+09 | 0.00 | 3093634.64 | 52722418.64 | 0.00 | 0.565332E+09 | 0.00 | 1.15 |
August | 0.536404E+09 | 0.369122E+09 | 0.00 | 2407403.63 | 99376612.19 | 0.00 | 0.335367E+09 | 0.00 | 1.17 |
September | 0.123237E+10 | 0.108918E+09 | 0.00 | 2785274.21 | 42967313.71 | 4729536.39 | 0.663627E+09 | 0.00 | 1.14 |
October | 0.124531E+10 | 0.234823E+09 | 0.00 | 1595230.02 | 0.102437E+09 | 83252758.91 | 0.373068E+09 | 0.00 | 0.96 |
November | 0.286593E+10 | 0.00 | 0.00 | 269975.15 | 1430343.51 | 0.244026E+09 | 0.238942E+09 | 0.00 | 0.92 |
December | 0.260362E+10 | 0.00 | 0.00 | 188238.93 | 399624.99 | 0.437346E+09 | 92735589.92 | 0.00 | 0.85 |
Annual Sum or Average | 0.234727E+11 | 0.105649E+10 | 0.00 | 23238167.27 | 0.313862E+09 | 0.227630E+10 | 0.734330E+10 | 0.00 | 1.03 |
Minimum of Months | 0.536404E+09 | 0.00 | 0.00 | 188238.93 | 0.00 | 0.00 | 92735589.92 | 0.00 | 0.84 |
Maximum of Months | 0.324959E+10 | 0.369122E+09 | 0.00 | 5309562.43 | 0.102437E+09 | 0.560354E+09 | 0.163716E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267201E+10 | 739342.02 | 0.00 | 633385.41 | 7877047.63 | 0.353529E+09 | 0.378367E+09 | 0.00 | 1.38 |
February | 0.262596E+10 | 88861.95 | 0.00 | 870779.36 | 125789.95 | 0.297622E+09 | 0.636710E+09 | 0.00 | 1.47 |
March | 0.308127E+10 | 144398.98 | 0.00 | 1757855.95 | 3280999.13 | 0.327206E+09 | 0.898017E+09 | 0.00 | 1.53 |
April | 0.192183E+10 | 780021.36 | 0.00 | 5022383.20 | 1811477.14 | 39299480.02 | 0.199540E+10 | 0.00 | 1.88 |
May | 0.215939E+10 | 599301.36 | 0.00 | 4674921.01 | 0.00 | 16417603.83 | 0.193906E+10 | 0.00 | 1.94 |
June | 0.137444E+10 | 29185570.97 | 0.00 | 5815160.47 | 249256.89 | 3012994.02 | 0.150016E+10 | 0.00 | 2.23 |
July | 0.585900E+09 | 0.343404E+09 | 0.00 | 4778619.17 | 41116497.97 | 0.00 | 0.729742E+09 | 0.00 | 2.07 |
August | 0.505420E+09 | 0.551194E+09 | 0.00 | 3536994.21 | 43209863.07 | 0.00 | 0.485036E+09 | 0.00 | 2.16 |
September | 0.116058E+10 | 0.106221E+09 | 0.00 | 4008036.28 | 48038151.56 | 5731818.69 | 0.883052E+09 | 0.00 | 1.94 |
October | 0.121551E+10 | 0.200801E+09 | 0.00 | 2340008.68 | 0.115697E+09 | 37087518.35 | 0.568532E+09 | 0.00 | 1.57 |
November | 0.286526E+10 | 0.00 | 0.00 | 643307.76 | 1486424.25 | 87915143.43 | 0.525172E+09 | 0.00 | 1.51 |
December | 0.279056E+10 | 375571.61 | 0.00 | 446636.38 | 139177.28 | 0.256409E+09 | 0.207712E+09 | 0.00 | 1.40 |
Annual Sum or Average | 0.229581E+11 | 0.123353E+10 | 0.00 | 34528087.87 | 0.263031E+09 | 0.142423E+10 | 0.107470E+11 | 0.00 | 1.76 |
Minimum of Months | 0.505420E+09 | 0.00 | 0.00 | 446636.38 | 0.00 | 0.00 | 0.207712E+09 | 0.00 | 1.38 |
Maximum of Months | 0.308127E+10 | 0.551194E+09 | 0.00 | 5815160.47 | 0.115697E+09 | 0.353529E+09 | 0.199540E+10 | 0.00 | 2.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197311E+10 | 21395657.41 | 0.00 | 14777435.09 | 1539863.79 | 0.272441E+09 | 0.419239E+10 | 0.00 | 1.74 |
February | 0.249646E+10 | 335977.04 | 0.00 | 8480598.82 | 161704.66 | 0.319005E+09 | 0.303146E+10 | 0.00 | 1.61 |
March | 0.337973E+10 | 424297.99 | 0.00 | 7318402.68 | 4157429.40 | 0.395295E+09 | 0.269578E+10 | 0.00 | 1.54 |
April | 0.261009E+10 | 1313969.61 | 0.00 | 7678417.73 | 2292475.32 | 0.105160E+09 | 0.276288E+10 | 0.00 | 1.67 |
May | 0.313289E+10 | 633916.38 | 0.00 | 4471190.87 | 0.00 | 63245206.44 | 0.193509E+10 | 0.00 | 1.52 |
June | 0.200652E+10 | 34799711.10 | 0.00 | 4756255.26 | 1046852.86 | 5870257.51 | 0.144719E+10 | 0.00 | 1.64 |
July | 0.927300E+09 | 0.360653E+09 | 0.00 | 3132100.24 | 85006504.94 | 0.00 | 0.596140E+09 | 0.00 | 1.45 |
August | 0.727446E+09 | 0.550334E+09 | 0.00 | 3763827.49 | 0.137202E+09 | 0.00 | 0.497272E+09 | 0.00 | 1.70 |
September | 0.139627E+10 | 0.185810E+09 | 0.00 | 8269748.75 | 66211288.67 | 5577732.14 | 0.168237E+10 | 0.00 | 1.96 |
October | 0.134593E+10 | 0.466845E+09 | 0.00 | 8253033.78 | 0.122615E+09 | 43507477.54 | 0.142597E+10 | 0.00 | 1.67 |
November | 0.225049E+10 | 184755.94 | 0.00 | 14140307.01 | 1750935.78 | 87275471.29 | 0.387733E+10 | 0.00 | 1.85 |
December | 0.212852E+10 | 1405034.99 | 0.00 | 16221336.79 | 0.00 | 0.212084E+09 | 0.351056E+10 | 0.00 | 1.77 |
Annual Sum or Average | 0.243748E+11 | 0.162413E+10 | 0.00 | 0.101263E+09 | 0.421984E+09 | 0.150946E+10 | 0.276544E+11 | 0.00 | 1.68 |
Minimum of Months | 0.727446E+09 | 184755.94 | 0.00 | 3132100.24 | 0.00 | 0.00 | 0.497272E+09 | 0.00 | 1.45 |
Maximum of Months | 0.337973E+10 | 0.550334E+09 | 0.00 | 16221336.79 | 0.137202E+09 | 0.395295E+09 | 0.419239E+10 | 0.00 | 1.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.271296E+10 | 3772578.43 | 0.00 | 1643642.92 | 6421881.62 | 0.518819E+09 | 0.737824E+09 | 0.00 | 1.61 |
February | 0.296950E+10 | 106561.02 | 0.00 | 1709367.48 | 144192.11 | 0.414169E+09 | 0.843624E+09 | 0.00 | 1.75 |
March | 0.347898E+10 | 0.00 | 0.00 | 2694740.71 | 3918962.06 | 0.441155E+09 | 0.124557E+10 | 0.00 | 1.84 |
April | 0.271791E+10 | 272015.69 | 0.00 | 4916269.44 | 2557257.87 | 0.108123E+09 | 0.191916E+10 | 0.00 | 2.22 |
May | 0.285756E+10 | 411175.71 | 0.00 | 4715044.08 | 0.00 | 59716015.64 | 0.199462E+10 | 0.00 | 2.27 |
June | 0.170655E+10 | 29886138.79 | 0.00 | 5940238.82 | 1130420.59 | 7811079.08 | 0.172941E+10 | 0.00 | 2.59 |
July | 0.754935E+09 | 0.354573E+09 | 0.00 | 4339908.13 | 85248734.24 | 741732.47 | 0.754897E+09 | 0.00 | 2.25 |
August | 0.651036E+09 | 0.404632E+09 | 0.00 | 3176038.76 | 0.168908E+09 | 1777598.01 | 0.449324E+09 | 0.00 | 2.36 |
September | 0.144001E+10 | 83101470.71 | 0.00 | 4152963.26 | 87111614.73 | 11314134.24 | 0.104072E+10 | 0.00 | 2.30 |
October | 0.153725E+10 | 0.199231E+09 | 0.00 | 2168966.44 | 0.146385E+09 | 0.103477E+09 | 0.475688E+09 | 0.00 | 1.83 |
November | 0.291948E+10 | 0.00 | 0.00 | 2553971.16 | 1703877.32 | 0.279101E+09 | 0.934178E+09 | 0.00 | 1.81 |
December | 0.276160E+10 | 0.00 | 0.00 | 1807357.34 | 476047.86 | 0.447759E+09 | 0.602086E+09 | 0.00 | 1.65 |
Annual Sum or Average | 0.265078E+11 | 0.107599E+10 | 0.00 | 39818508.52 | 0.504006E+09 | 0.239397E+10 | 0.127271E+11 | 0.00 | 2.04 |
Minimum of Months | 0.651036E+09 | 0.00 | 0.00 | 1643642.92 | 0.00 | 741732.47 | 0.449324E+09 | 0.00 | 1.61 |
Maximum of Months | 0.347898E+10 | 0.404632E+09 | 0.00 | 5940238.82 | 0.168908E+09 | 0.518819E+09 | 0.199462E+10 | 0.00 | 2.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254809E+10 | 322080.50 | 0.00 | 247665.24 | 6209380.98 | 0.327253E+09 | 74132590.12 | 0.00 | 0.67 |
February | 0.272195E+10 | 1598835.00 | 0.00 | 38601.58 | 150698.92 | 0.182235E+09 | 37360440.69 | 0.00 | 0.71 |
March | 0.299858E+10 | 74367.41 | 0.00 | 145258.36 | 4749873.28 | 0.288339E+09 | 0.102654E+09 | 0.00 | 0.72 |
April | 0.211484E+10 | 1343289.68 | 0.00 | 1072288.33 | 11482129.30 | 22828445.86 | 0.489973E+09 | 0.00 | 0.78 |
May | 0.193364E+10 | 2061608.13 | 0.00 | 2300356.88 | 7792.53 | 315156.81 | 0.848609E+09 | 0.00 | 0.84 |
June | 0.103514E+10 | 84953464.15 | 0.00 | 3427039.15 | 9196778.17 | 0.00 | 0.850606E+09 | 0.00 | 0.97 |
July | 0.519841E+09 | 0.431765E+09 | 0.00 | 1970316.84 | 40227015.20 | 0.00 | 0.323121E+09 | 0.00 | 0.87 |
August | 0.538316E+09 | 0.527120E+09 | 0.00 | 1133027.59 | 60487467.85 | 0.00 | 0.185940E+09 | 0.00 | 0.89 |
September | 0.109407E+10 | 0.161557E+09 | 0.00 | 1853294.16 | 21563364.68 | 0.00 | 0.383946E+09 | 0.00 | 0.86 |
October | 0.125803E+10 | 0.264245E+09 | 0.00 | 1325075.57 | 46520861.45 | 1485838.99 | 0.284870E+09 | 0.00 | 0.76 |
November | 0.274888E+10 | 447312.91 | 0.00 | 186003.71 | 3711182.50 | 24764222.21 | 0.155443E+09 | 0.00 | 0.73 |
December | 0.267157E+10 | 32896.32 | 0.00 | 54234.28 | 967047.87 | 0.174276E+09 | 41234264.70 | 0.00 | 0.68 |
Annual Sum or Average | 0.221829E+11 | 0.147552E+10 | 0.00 | 13753161.70 | 0.205274E+09 | 0.102150E+10 | 0.377789E+10 | 0.00 | 0.79 |
Minimum of Months | 0.519841E+09 | 32896.32 | 0.00 | 38601.58 | 7792.53 | 0.00 | 37360440.69 | 0.00 | 0.67 |
Maximum of Months | 0.299858E+10 | 0.527120E+09 | 0.00 | 3427039.15 | 60487467.85 | 0.327253E+09 | 0.850606E+09 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.300552E+10 | 956673.73 | 0.00 | 726570.28 | 6955645.54 | 0.144190E+09 | 0.432445E+09 | 0.00 | 1.29 |
February | 0.299030E+10 | 2136204.65 | 0.00 | 713892.75 | 0.00 | 0.123587E+09 | 0.464930E+09 | 0.00 | 1.36 |
March | 0.338399E+10 | 152629.07 | 0.00 | 1363042.24 | 5691535.00 | 0.171946E+09 | 0.597370E+09 | 0.00 | 1.41 |
April | 0.199346E+10 | 7119701.31 | 0.00 | 3790124.76 | 9725601.19 | 9788498.79 | 0.143594E+10 | 0.00 | 1.64 |
May | 0.219720E+10 | 2966024.76 | 0.00 | 3609660.46 | 9440.00 | 1970236.74 | 0.133762E+10 | 0.00 | 1.70 |
June | 0.142106E+10 | 91993432.84 | 0.00 | 4136194.83 | 11232259.34 | 661615.99 | 0.932078E+09 | 0.00 | 1.90 |
July | 0.581099E+09 | 0.508312E+09 | 0.00 | 3638082.44 | 46735580.13 | 0.00 | 0.539281E+09 | 0.00 | 1.80 |
August | 0.584379E+09 | 0.739225E+09 | 0.00 | 2667302.77 | 51122807.28 | 0.00 | 0.393325E+09 | 0.00 | 1.90 |
September | 0.123633E+10 | 0.159739E+09 | 0.00 | 3276212.67 | 40546379.51 | 624686.67 | 0.650228E+09 | 0.00 | 1.71 |
October | 0.135948E+10 | 0.227533E+09 | 0.00 | 2247865.80 | 70103362.53 | 3811821.01 | 0.586396E+09 | 0.00 | 1.43 |
November | 0.298036E+10 | 754973.18 | 0.00 | 869193.64 | 4282696.16 | 5726284.88 | 0.574938E+09 | 0.00 | 1.40 |
December | 0.316257E+10 | 844818.02 | 0.00 | 544182.81 | 433556.62 | 68991874.39 | 0.266572E+09 | 0.00 | 1.31 |
Annual Sum or Average | 0.248957E+11 | 0.174173E+10 | 0.00 | 27582325.46 | 0.246839E+09 | 0.531298E+09 | 0.821112E+10 | 0.00 | 1.57 |
Minimum of Months | 0.581099E+09 | 152629.07 | 0.00 | 544182.81 | 0.00 | 0.00 | 0.266572E+09 | 0.00 | 1.29 |
Maximum of Months | 0.338399E+10 | 0.739225E+09 | 0.00 | 4136194.83 | 70103362.53 | 0.171946E+09 | 0.143594E+10 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210535E+10 | 26714864.85 | 0.00 | 12723303.73 | 483616.58 | 0.466405E+09 | 0.330295E+10 | 0.00 | 1.49 |
February | 0.265308E+10 | 7439446.49 | 0.00 | 6148928.16 | 0.00 | 0.489976E+09 | 0.190147E+10 | 0.00 | 1.33 |
March | 0.327009E+10 | 2135746.90 | 0.00 | 4257200.25 | 5115947.81 | 0.936528E+09 | 0.116789E+10 | 0.00 | 1.24 |
April | 0.262264E+10 | 11555032.49 | 0.00 | 4009389.18 | 10387234.85 | 0.331948E+09 | 0.108449E+10 | 0.00 | 1.26 |
May | 0.310310E+10 | 2387934.09 | 0.00 | 1741890.76 | 144542.79 | 0.294828E+09 | 0.575458E+09 | 0.00 | 1.19 |
June | 0.205858E+10 | 91969586.17 | 0.00 | 1443168.99 | 16703353.43 | 0.150936E+09 | 0.357967E+09 | 0.00 | 1.25 |
July | 0.968043E+09 | 0.505989E+09 | 0.00 | 1086294.00 | 83447666.41 | 14801415.50 | 0.166748E+09 | 0.00 | 1.12 |
August | 0.851292E+09 | 0.854112E+09 | 0.00 | 1247151.95 | 91995101.19 | 17318170.92 | 0.181902E+09 | 0.00 | 1.36 |
September | 0.144756E+10 | 0.340558E+09 | 0.00 | 5361053.24 | 36163662.86 | 66792153.83 | 0.862650E+09 | 0.00 | 1.60 |
October | 0.123720E+10 | 0.577370E+09 | 0.00 | 7045636.15 | 48613017.19 | 0.140716E+09 | 0.123358E+10 | 0.00 | 1.47 |
November | 0.227676E+10 | 6675123.07 | 0.00 | 12329594.10 | 2702189.03 | 0.240672E+09 | 0.306404E+10 | 0.00 | 1.60 |
December | 0.225489E+10 | 4052106.84 | 0.00 | 15491258.45 | 0.00 | 0.379547E+09 | 0.290951E+10 | 0.00 | 1.58 |
Annual Sum or Average | 0.248486E+11 | 0.243096E+10 | 0.00 | 72884868.95 | 0.295756E+09 | 0.353047E+10 | 0.168087E+11 | 0.00 | 1.37 |
Minimum of Months | 0.851292E+09 | 2135746.90 | 0.00 | 1086294.00 | 0.00 | 14801415.50 | 0.166748E+09 | 0.00 | 1.12 |
Maximum of Months | 0.327009E+10 | 0.854112E+09 | 0.00 | 15491258.45 | 91995101.19 | 0.936528E+09 | 0.330295E+10 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311731E+10 | 4630202.24 | 0.00 | 1148947.38 | 4090279.67 | 0.255536E+09 | 0.509875E+09 | 0.00 | 1.39 |
February | 0.323208E+10 | 1831971.37 | 0.00 | 1167850.85 | 457033.94 | 0.150149E+09 | 0.537009E+09 | 0.00 | 1.50 |
March | 0.361692E+10 | 96929.91 | 0.00 | 1776150.25 | 6190948.26 | 0.223474E+09 | 0.709974E+09 | 0.00 | 1.56 |
April | 0.258937E+10 | 1932808.87 | 0.00 | 3528921.44 | 14686599.82 | 32505438.21 | 0.111844E+10 | 0.00 | 1.80 |
May | 0.267578E+10 | 1917941.19 | 0.00 | 3539050.70 | 279195.18 | 5518499.34 | 0.118957E+10 | 0.00 | 1.86 |
June | 0.154306E+10 | 0.105752E+09 | 0.00 | 3938059.49 | 10419285.05 | 632364.47 | 0.104227E+10 | 0.00 | 2.11 |
July | 0.659310E+09 | 0.548595E+09 | 0.00 | 2817380.32 | 65647654.86 | 0.00 | 0.508044E+09 | 0.00 | 1.86 |
August | 0.659747E+09 | 0.692872E+09 | 0.00 | 1700330.94 | 0.100505E+09 | 0.00 | 0.325615E+09 | 0.00 | 1.97 |
September | 0.137538E+10 | 0.155076E+09 | 0.00 | 3100097.75 | 64304465.49 | 0.00 | 0.710119E+09 | 0.00 | 1.91 |
October | 0.165439E+10 | 0.239654E+09 | 0.00 | 1585833.74 | 78888214.21 | 4653131.79 | 0.394468E+09 | 0.00 | 1.55 |
November | 0.320799E+10 | 886366.22 | 0.00 | 2047767.70 | 4740383.34 | 25623327.87 | 0.688506E+09 | 0.00 | 1.56 |
December | 0.325736E+10 | 289103.20 | 0.00 | 1359912.52 | 1077692.38 | 0.133874E+09 | 0.420069E+09 | 0.00 | 1.44 |
Annual Sum or Average | 0.275887E+11 | 0.175353E+10 | 0.00 | 27710303.08 | 0.351287E+09 | 0.831966E+09 | 0.815396E+10 | 0.00 | 1.71 |
Minimum of Months | 0.659310E+09 | 96929.91 | 0.00 | 1148947.38 | 279195.18 | 0.00 | 0.325615E+09 | 0.00 | 1.39 |
Maximum of Months | 0.361692E+10 | 0.692872E+09 | 0.00 | 3938059.49 | 0.100505E+09 | 0.255536E+09 | 0.118957E+10 | 0.00 | 2.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245300E+10 | 2915492.94 | 0.00 | 509629.33 | 8138551.69 | 0.288845E+09 | 0.131764E+09 | 0.00 | 0.70 |
February | 0.244192E+10 | 2341342.83 | 0.00 | 424343.94 | 0.00 | 0.140818E+09 | 0.334482E+09 | 0.00 | 0.74 |
March | 0.284855E+10 | 261521.74 | 0.00 | 766111.43 | 7021382.64 | 0.188182E+09 | 0.372303E+09 | 0.00 | 0.76 |
April | 0.187734E+10 | 2474635.40 | 0.00 | 2635362.14 | 17005722.13 | 20666938.76 | 0.869788E+09 | 0.00 | 0.87 |
May | 0.168157E+10 | 3261499.21 | 0.00 | 4001765.20 | 307751.88 | 286488.71 | 0.131510E+10 | 0.00 | 0.96 |
June | 0.928604E+09 | 0.108357E+09 | 0.00 | 4933501.44 | 12123231.74 | 0.00 | 0.115917E+10 | 0.00 | 1.14 |
July | 0.497671E+09 | 0.532504E+09 | 0.00 | 2504276.70 | 41458768.79 | 0.00 | 0.392276E+09 | 0.00 | 1.00 |
August | 0.516507E+09 | 0.663531E+09 | 0.00 | 1532880.51 | 68337889.12 | 0.00 | 0.229496E+09 | 0.00 | 1.02 |
September | 0.102309E+10 | 0.211438E+09 | 0.00 | 2485389.33 | 28076335.09 | 0.00 | 0.502942E+09 | 0.00 | 0.97 |
October | 0.119839E+10 | 0.316286E+09 | 0.00 | 1723275.45 | 54975904.90 | 6732385.10 | 0.349522E+09 | 0.00 | 0.83 |
November | 0.246567E+10 | 589618.74 | 0.00 | 754891.98 | 5584579.30 | 38938977.22 | 0.393882E+09 | 0.00 | 0.76 |
December | 0.246890E+10 | 1388994.00 | 0.00 | 333619.90 | 1202230.73 | 0.183597E+09 | 0.139941E+09 | 0.00 | 0.71 |
Annual Sum or Average | 0.204012E+11 | 0.184535E+10 | 0.00 | 22605047.35 | 0.244232E+09 | 0.868067E+09 | 0.619066E+10 | 0.00 | 0.87 |
Minimum of Months | 0.497671E+09 | 261521.74 | 0.00 | 333619.90 | 0.00 | 0.00 | 0.131764E+09 | 0.00 | 0.70 |
Maximum of Months | 0.284855E+10 | 0.663531E+09 | 0.00 | 4933501.44 | 68337889.12 | 0.288845E+09 | 0.131510E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254901E+10 | 4297776.93 | 0.00 | 1427649.83 | 4943259.28 | 0.205437E+09 | 0.567492E+09 | 0.00 | 1.22 |
February | 0.249838E+10 | 2684557.05 | 0.00 | 1525595.46 | 781.97 | 0.134596E+09 | 0.736092E+09 | 0.00 | 1.30 |
March | 0.281620E+10 | 818096.95 | 0.00 | 2340680.93 | 8578024.07 | 0.173415E+09 | 0.933304E+09 | 0.00 | 1.37 |
April | 0.198472E+10 | 9749720.08 | 0.00 | 4866731.52 | 14251172.44 | 16280870.69 | 0.161728E+10 | 0.00 | 1.77 |
May | 0.210972E+10 | 4119692.76 | 0.00 | 4575663.15 | 334200.70 | 3345278.70 | 0.153881E+10 | 0.00 | 1.79 |
June | 0.139715E+10 | 0.100334E+09 | 0.00 | 5123339.27 | 12906501.91 | 1265214.01 | 0.110042E+10 | 0.00 | 2.05 |
July | 0.638186E+09 | 0.538930E+09 | 0.00 | 4129265.91 | 61799208.07 | 0.00 | 0.555417E+09 | 0.00 | 1.97 |
August | 0.642855E+09 | 0.806059E+09 | 0.00 | 2798566.68 | 65353850.20 | 0.00 | 0.406443E+09 | 0.00 | 2.08 |
September | 0.125577E+10 | 0.184097E+09 | 0.00 | 3702325.27 | 35451486.72 | 1771909.21 | 0.688726E+09 | 0.00 | 1.81 |
October | 0.136887E+10 | 0.245153E+09 | 0.00 | 2541646.99 | 90530277.29 | 8591048.38 | 0.600845E+09 | 0.00 | 1.50 |
November | 0.258912E+10 | 902033.06 | 0.00 | 1745600.93 | 6331000.31 | 26085259.09 | 0.779509E+09 | 0.00 | 1.35 |
December | 0.268774E+10 | 1858848.03 | 0.00 | 1250613.35 | 1042980.23 | 0.116523E+09 | 0.400339E+09 | 0.00 | 1.23 |
Annual Sum or Average | 0.225377E+11 | 0.189900E+10 | 0.00 | 36027679.31 | 0.301523E+09 | 0.687311E+09 | 0.992467E+10 | 0.00 | 1.62 |
Minimum of Months | 0.638186E+09 | 818096.95 | 0.00 | 1250613.35 | 781.97 | 0.00 | 0.400339E+09 | 0.00 | 1.22 |
Maximum of Months | 0.281620E+10 | 0.806059E+09 | 0.00 | 5123339.27 | 90530277.29 | 0.205437E+09 | 0.161728E+10 | 0.00 | 2.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220080E+10 | 41530675.95 | 0.00 | 16178606.79 | 159277.62 | 0.142929E+09 | 0.406580E+10 | 0.00 | 1.76 |
February | 0.259464E+10 | 9989251.26 | 0.00 | 9313958.11 | 0.00 | 99801193.32 | 0.293527E+10 | 0.00 | 1.58 |
March | 0.337658E+10 | 5850172.06 | 0.00 | 7490080.20 | 6290664.07 | 0.208895E+09 | 0.231140E+10 | 0.00 | 1.47 |
April | 0.253712E+10 | 20098975.41 | 0.00 | 7168001.38 | 15469311.99 | 35790240.84 | 0.200304E+10 | 0.00 | 1.55 |
May | 0.292050E+10 | 4465768.71 | 0.00 | 4306368.20 | 458486.70 | 9843443.26 | 0.138984E+10 | 0.00 | 1.37 |
June | 0.185677E+10 | 0.127241E+09 | 0.00 | 3803849.54 | 18598256.64 | 0.00 | 0.958649E+09 | 0.00 | 1.46 |
July | 0.885552E+09 | 0.639091E+09 | 0.00 | 2095198.12 | 80764509.21 | 0.00 | 0.347127E+09 | 0.00 | 1.31 |
August | 0.817392E+09 | 0.105115E+10 | 0.00 | 1998519.30 | 0.111250E+09 | 0.00 | 0.299295E+09 | 0.00 | 1.58 |
September | 0.144823E+10 | 0.440702E+09 | 0.00 | 6807455.61 | 36553005.17 | 0.00 | 0.113080E+10 | 0.00 | 1.86 |
October | 0.146823E+10 | 0.671651E+09 | 0.00 | 8069024.32 | 63361200.62 | 7301982.23 | 0.124459E+10 | 0.00 | 1.63 |
November | 0.233535E+10 | 11645487.50 | 0.00 | 15368651.03 | 3887829.39 | 10910306.96 | 0.375052E+10 | 0.00 | 1.85 |
December | 0.232161E+10 | 11240788.25 | 0.00 | 17658943.08 | 0.00 | 53743562.90 | 0.349170E+10 | 0.00 | 1.79 |
Annual Sum or Average | 0.247628E+11 | 0.303465E+10 | 0.00 | 0.100259E+09 | 0.336792E+09 | 0.569215E+09 | 0.239280E+11 | 0.00 | 1.60 |
Minimum of Months | 0.817392E+09 | 4465768.71 | 0.00 | 1998519.30 | 0.00 | 0.00 | 0.299295E+09 | 0.00 | 1.31 |
Maximum of Months | 0.337658E+10 | 0.105115E+10 | 0.00 | 17658943.08 | 0.111250E+09 | 0.208895E+09 | 0.406580E+10 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301715E+10 | 7589709.74 | 0.00 | 1719751.26 | 8377839.01 | 0.358753E+09 | 0.667838E+09 | 0.00 | 1.55 |
February | 0.321853E+10 | 2222307.32 | 0.00 | 1805411.32 | 829298.59 | 0.212096E+09 | 0.748804E+09 | 0.00 | 1.69 |
March | 0.367231E+10 | 338582.59 | 0.00 | 2633746.61 | 9682252.73 | 0.261998E+09 | 0.996396E+09 | 0.00 | 1.77 |
April | 0.271980E+10 | 4350737.41 | 0.00 | 4571635.53 | 21835084.23 | 44229395.73 | 0.139045E+10 | 0.00 | 2.10 |
May | 0.279140E+10 | 2549840.35 | 0.00 | 4422435.78 | 801998.29 | 15855853.10 | 0.146970E+10 | 0.00 | 2.13 |
June | 0.166536E+10 | 0.124370E+09 | 0.00 | 4769233.30 | 15632528.20 | 1938517.73 | 0.120337E+10 | 0.00 | 2.41 |
July | 0.769936E+09 | 0.626940E+09 | 0.00 | 3240327.92 | 88933077.30 | 0.00 | 0.478428E+09 | 0.00 | 2.09 |
August | 0.766617E+09 | 0.796127E+09 | 0.00 | 1746579.50 | 0.151665E+09 | 0.00 | 0.281735E+09 | 0.00 | 2.23 |
September | 0.150412E+10 | 0.191558E+09 | 0.00 | 3486862.07 | 86507136.88 | 1880479.36 | 0.720141E+09 | 0.00 | 2.16 |
October | 0.175542E+10 | 0.276764E+09 | 0.00 | 1856493.60 | 0.109266E+09 | 17426887.07 | 0.388235E+09 | 0.00 | 1.74 |
November | 0.323091E+10 | 1736956.45 | 0.00 | 2616673.69 | 7184073.53 | 75881036.36 | 0.841888E+09 | 0.00 | 1.74 |
December | 0.314884E+10 | 1493141.98 | 0.00 | 1833220.96 | 2279213.34 | 0.249654E+09 | 0.528373E+09 | 0.00 | 1.60 |
Annual Sum or Average | 0.282604E+11 | 0.203604E+10 | 0.00 | 34702371.56 | 0.502993E+09 | 0.123971E+10 | 0.971536E+10 | 0.00 | 1.93 |
Minimum of Months | 0.766617E+09 | 338582.59 | 0.00 | 1719751.26 | 801998.29 | 0.00 | 0.281735E+09 | 0.00 | 1.55 |
Maximum of Months | 0.367231E+10 | 0.796127E+09 | 0.00 | 4769233.30 | 0.151665E+09 | 0.358753E+09 | 0.146970E+10 | 0.00 | 2.41 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.278036E+12 | 0.605639E+10 | 0.00 | 0.256357E+12 | 0.482018E+11 |
February | 0.316478E+12 | 0.660362E+10 | 0.00 | 0.261186E+12 | 0.306112E+11 |
March | 0.419422E+12 | 0.723755E+10 | 0.00 | 0.274857E+12 | 0.382999E+11 |
April | 0.528592E+12 | 0.413120E+10 | 0.00 | 0.264294E+12 | 0.720621E+11 |
May | 0.547644E+12 | 0.463271E+10 | 0.00 | 0.276135E+12 | 0.734109E+11 |
June | 0.534713E+12 | 0.219605E+10 | 0.00 | 0.216284E+12 | 0.132445E+12 |
July | 0.574230E+12 | 0.225596E+09 | 0.00 | 0.122357E+12 | 0.209617E+12 |
August | 0.537069E+12 | 0.153040E+09 | 0.00 | 0.887904E+11 | 0.240571E+12 |
September | 0.430322E+12 | 0.158930E+10 | 0.00 | 0.175751E+12 | 0.153389E+12 |
October | 0.320740E+12 | 0.267032E+10 | 0.00 | 0.189975E+12 | 0.161828E+12 |
November | 0.294814E+12 | 0.575540E+10 | 0.00 | 0.286225E+12 | 0.499403E+11 |
December | 0.260323E+12 | 0.627976E+10 | 0.00 | 0.281553E+12 | 0.535729E+11 |
Annual Sum or Average | 0.504238E+13 | 0.475309E+11 | 0.00 | 0.269376E+13 | 0.126395E+13 |
Minimum of Months | 0.260323E+12 | 0.153040E+09 | 0.00 | 0.887904E+11 | 0.306112E+11 |
Maximum of Months | 0.574230E+12 | 0.723755E+10 | 0.00 | 0.286225E+12 | 0.240571E+12 |