Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2024-07-03 12:20:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2134.64 | 428.45 | 428.45 |
Net Site Energy | 2134.64 | 428.45 | 428.45 |
Total Source Energy | 6078.84 | 1220.12 | 1220.12 |
Net Source Energy | 6078.84 | 1220.12 | 1220.12 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 327.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 49.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 235.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 56.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1807.44 | 327.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 327.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 49.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 235.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 141.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 56.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 327.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 49.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 235.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 141.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 56.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 49.97 | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 362.78 | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 49.97 | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 362.78 | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1807.438 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1807.438 | 100.00 |
Total On-Site and Utility Electric Sources | 1807.438 | 100.00 |
Total Electricity End Uses | 1807.438 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 362.33 |
Time Setpoint Not Met During Occupied Cooling | 12.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1999.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-15:00 | 02-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:20 |
Heating | 0.00 | 211549.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48505.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25114.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4629.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 171046.57 | 211549.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 211549.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 48505.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 25114.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4629.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 354.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 156.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 745.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 448.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 179.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5724.16 | 354.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 71.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 31.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1148.92 | 71.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 71.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 31.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1148.92 | 71.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.36 | 0.223322 | 0.300000 | 1.01 | 0.595526 | 0.500000 | 0.001706 | 0.000138 | 1.01 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.72 | 0.275884 | 0.300000 | 0.814967 | 0.735691 | 0.500000 | 0.001381 | 0.000231 | 1.11 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.95 | 0.254239 | 0.300000 | 0.884352 | 0.677970 | 0.500000 | 0.001499 | 0.000485 | 2.36 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.966406 | 0.163484 | 0.300000 | 0.289922 | 0.435957 | 0.500000 | 0.002331 | 0.000198 | 0.966406 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.889827 | 0.112406 | 0.300000 | 0.266948 | 0.300000 | 0.500000 | 0.003390 | 0.000130 | 0.634625 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.39 | 0.113425 | 0.300000 | 0.417873 | 0.302468 | 0.500000 | 0.003359 | 0.000200 | 0.972054 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.01 | 0.098581 | 0.300000 | 0.304363 | 0.300000 | 0.500000 | 0.003865 | 0.000129 | 0.630523 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.752497 | 0.209957 | 0.312000 | 0.234779 | 0.559884 | 0.500000 | 0.001815 | 0.000155 | 0.752497 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.726549 | 0.137667 | 0.300000 | 0.217965 | 0.367112 | 0.500000 | 0.002768 | 0.000103 | 0.501406 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.10 | 0.143513 | 0.300000 | 0.330265 | 0.382702 | 0.500000 | 0.002655 | 0.000156 | 0.759352 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.821838 | 0.121697 | 0.300000 | 0.246552 | 0.324525 | 0.500000 | 0.003131 | 0.000102 | 0.497137 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.719102 | 0.219707 | 0.300000 | 0.215731 | 0.585885 | 0.500000 | 0.001734 | 0.000148 | 0.719102 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.909474 | 0.300000 | 0.500000 | 0.003464 | 0.000098 | 0.478262 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.28 | 0.123618 | 0.300000 | 0.383418 | 0.329649 | 0.500000 | 0.003082 | 0.000149 | 0.724567 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.938977 | 0.106515 | 0.300000 | 0.281693 | 0.300000 | 0.500000 | 0.003577 | 0.000097 | 0.474147 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15746.30 | 0.000138 | 336.98 |
CORE_MID VAV BOX REHEAT COIL | 26362.81 | 0.000231 | 617.32 |
CORE_TOP VAV BOX REHEAT COIL | 55486.72 | 0.000485 | 1297.10 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22689.63 | 0.000198 | 530.03 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14898.51 | 0.000130 | 348.02 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22821.88 | 0.000200 | 533.12 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14802.46 | 0.000129 | 345.78 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17679.39 | 0.000155 | 413.07 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11778.18 | 0.000103 | 275.18 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17839.89 | 0.000156 | 416.81 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11678.23 | 0.000102 | 272.84 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16898.33 | 0.000148 | 394.84 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11236.83 | 0.000098 | 262.54 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 17026.27 | 0.000149 | 397.83 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11140.48 | 0.000097 | 260.30 |
PACU_VAV_BOT HEATING COIL | 14383.75 | 0.000126 | 251.07 |
PACU_VAV_MID HEATING COIL | 15121.00 | 0.000132 | 262.48 |
PACU_VAV_TOP HEATING COIL | 13758.39 | 0.000120 | 241.84 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.38 | 2.04 | 6.76 | 2.94 | 5.72 | 5.72 | 0.300000 | 0.513404 | 5.72 |
PACU_VAV_MID | 3.28 | 1.97 | 6.56 | 3.51 | 5.40 | 5.40 | 0.300000 | 0.650366 | 5.40 |
PACU_VAV_TOP | 3.61 | 2.16 | 7.21 | 5.56 | 6.37 | 6.37 | 0.300000 | 0.872918 | 6.37 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.72 |
PACU_VAV_MID_OA_CONTROLLER | 5.40 |
PACU_VAV_TOP_OA_CONTROLLER | 6.37 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.72 | 94635.17 | 0.800655 | 1.91 | 31541.90 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.40 | 89319.98 | 0.800655 | 1.80 | 29770.35 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 6.37 | 105452.92 | 0.800655 | 2.12 | 35147.46 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.72 |
PACU_VAV_MID FAN | 5.40 |
PACU_VAV_TOP FAN | 6.37 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000126 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000132 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000120 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002899 | 0.347854 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.002899 | 872.99 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 331349.06 | 331349.06 | 0.002899 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
43 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
44 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
45 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
46 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
47 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
48 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
49 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39755.14088 | 45718.41201 | 2.91820 | 3.35593 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 4660.53435 | 5825.66794 | 0.33663 | 0.42469 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32207.87746 | 37039.05908 | 2.36222 | 2.71656 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 12315.00211 | 15393.75264 | 0.89054 | 1.11318 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 34628.64893 | 39822.94627 | 2.56334 | 2.94784 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 25807.15173 | 32258.93967 | 1.88579 | 2.35724 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8911.42564 | 10248.13949 | 0.65965 | 0.75859 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10534.71005 | 13168.38756 | 0.77312 | 0.96641 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10453.13519 | 12021.10547 | 0.77376 | 0.88983 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6916.84740 | 8646.05925 | 0.50770 | 0.63463 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 16363.04790 | 18817.50508 | 1.21123 | 1.39291 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10595.98515 | 13244.98143 | 0.77764 | 0.97205 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11918.25588 | 13705.99426 | 0.88221 | 1.01454 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6872.34363 | 8590.42954 | 0.50442 | 0.63052 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6424.33577 | 7387.98614 | 0.47555 | 0.54688 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 8212.24824 | 10265.31030 | 0.60200 | 0.75250 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8596.93331 | 9886.47331 | 0.63178 | 0.72655 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5470.39736 | 6837.99670 | 0.40112 | 0.50141 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12932.44262 | 14872.30901 | 0.95729 | 1.10088 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 26.32417 | 8.40696E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 8286.60669 | 10358.25836 | 0.60748 | 0.75935 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9654.42102 | 11102.58417 | 0.71464 | 0.82184 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.21600 | 8.40365E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5424.09126 | 6780.11408 | 0.39771 | 0.49714 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7474.51142 | 8595.68814 | 0.55328 | 0.63628 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7851.01411 | 9813.76764 | 0.57528 | 0.71910 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10683.93488 | 12286.52511 | 0.79085 | 0.90947 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 21.10683 | 8.39884E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5219.99372 | 6524.99215 | 0.38261 | 0.47826 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 15013.81049 | 17265.88206 | 1.11136 | 1.27806 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 26.09667 | 8.40660E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7910.28787 | 9887.85983 | 0.57965 | 0.72457 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11030.51875 | 12685.09656 | 0.81650 | 0.93898 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5175.35713 | 6469.19641 | 0.37932 | 0.47415 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 78785.45 | 5.71691 | 5.71691 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 19296.20 | 2.93508 | 2.93508 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 74514.93 | 5.39582 | 5.39582 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 19665.59 | 3.50926 | 3.50926 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 87443.54 | 6.37041 | 6.37041 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 19154.46 | 5.56084 | 5.56084 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.35593 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22332 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.00678 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59553 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70605E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37756E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.00678 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15746.30174 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37756E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 336.97883 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.71656 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27588 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81497 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73569 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38101E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.30633E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.11318 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26362.81111 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.30633E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 617.32485 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.94784 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25424 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.88435 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67797 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49859E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.85422E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.35724 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 55486.72057 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.85422E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1297.09661 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96641 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16348 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28992 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43596 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33051E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.98499E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.96641 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22689.63070 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.98499E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 530.02922 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88983 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11241 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26695 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38950E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30339E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63463 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14898.50716 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30339E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 348.01932 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39291 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11343 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41787 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30247 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35903E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99656E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.97205 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22821.88228 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99656E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 533.11624 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01454 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.85814E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30436 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.86483E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29498E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63052 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14802.45594 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29498E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 345.77727 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75250 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20996 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23478 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55988 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81466E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54667E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75250 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17679.39417 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54667E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 413.06804 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72655 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13767 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21796 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36711 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76755E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03041E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50141 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11778.18093 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03041E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 275.17690 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10088 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14351 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33027 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38270 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65480E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.56071E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75935 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17839.89323 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56071E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 416.81440 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82184 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12170 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24655 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32453 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13073E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02166E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.49714 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11678.23177 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02166E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 272.84388 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71910 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21971 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21573 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58589 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73413E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47834E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71910 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16898.32526 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47834E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 394.84176 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90947 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46434E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.83047E-005 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47826 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11236.82862 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.83047E-005 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 262.54402 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27806 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12362 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38342 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32965 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.08206E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48953E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72457 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17026.27163 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48953E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 397.82826 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93898 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10652 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28169 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.57696E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.74618E-005 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47415 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11140.48162 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.74618E-005 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.29508 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.37885 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.03634 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.75770 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.93508 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.71691 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.71691 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.51340 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.28108 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.96865 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.56217 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 3.50926 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.39582 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.39582 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.65037 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.60576 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.16346 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.21153 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 5.56084 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.37041 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.37041 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.87292 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.71691 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.39582 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.37041 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.71691 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.71691 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 94635.17230 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.90545 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31541.90293 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 14383.74633 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25835E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 251.06551 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.71691 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.25835E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.39582 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.39582 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 89319.97921 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.79843 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29770.34907 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 15121.00208 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32285E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 262.48388 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.39582 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.32285E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.37041 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.37041 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105452.92009 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.12326 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35147.45827 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 13758.38987 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20364E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 241.83592 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.37041 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.20364E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.89879E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.34785 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.89879E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 872.98707 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 331349.05503 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 331349.06000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.89879E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 14944.88 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 25009.26 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 52638.25 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21524.91 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14133.72 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21650.37 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14042.60 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16771.84 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11173.57 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16924.11 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11078.75 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16030.87 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10660.00 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16152.25 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10568.60 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 12403.25 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 12903.87 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 12020.65 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 93006.74 | 317352.16 | 11.06 | 2.87 | 3.16 | 3.33 | 3.51 | 9.79 | 10.80 | 11.36 | 11.98 | 6.5420 | 5.1743 | 3.4683 | 1.4446 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 87783.00 | 299528.04 | 11.06 | 2.87 | 3.16 | 3.33 | 3.51 | 9.79 | 10.80 | 11.36 | 11.98 | 6.1746 | 4.8837 | 3.2735 | 1.3635 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 103638.34 | 353628.69 | 11.06 | 2.87 | 3.16 | 3.33 | 3.51 | 9.79 | 10.80 | 11.36 | 11.98 | 7.2898 | 5.7658 | 3.8647 | 1.6097 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.8035451427E-002 | 5.9943456577E-002 | Pass | Pass | 8.3784305016E-003 | 9.1858517104E-002 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1493479431 | 0.1171315897 | Pass | Pass | 0.5252046292 | 0.7651391101 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.1027261780E-002 | 9.1012782406E-003 | Pass | Pass | 1.9036515345E-002 | 0.2276436141 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.9971767084E-003 | 1.0839498343E-002 | Pass | Pass | 2.2300240559E-002 | 0.2016272773 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 9.2406831740E-003 | 1.4322216769E-002 | Pass | Pass | 7.6107202887E-003 | 9.1010977655E-002 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.3598104765E-002 | 3.2842909261E-002 | Pass | Pass | 0.4737021433 | 0.6118696563 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2073339665 | 0.2114886636 | Pass | Pass | 11.1700239824 | 25.0095502499 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1698809821 | 0.1863217566 | Pass | Pass | 10.5269541444 | 27.3346806512 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1809446829 | 0.1721798516 | Pass | Pass | 8.2342506553 | 23.6756448181 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1849148093 | 0.1921765272 | Pass | Pass | 10.8098494021 | 24.7187214273 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3345443625E-002 | 4.9271108642E-002 | Pass | Pass | 1.2259516801E-002 | 0.1440130136 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.9948913721E-002 | 6.4349000719E-002 | Pass | Pass | 9.4678914635E-003 | 9.8041807827E-002 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.3121143603E-002 | 8.3113274554E-002 | Pass | Pass | 8.1699802751E-003 | 9.0585222456E-002 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.7351876871E-002 | 4.6933869076E-002 | Pass | Pass | 8.5894554987E-003 | 0.1006268340 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.2526181142E-002 | 4.6291187268E-002 | Pass | Pass | 1.8697619635E-004 | 2.2359101087E-003 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.1307710483E-002 | 7.4977574078E-002 | Pass | Pass | 2.6016894873E-004 | 3.1111681261E-003 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.5552937321E-002 | 9.5195791943E-002 | Pass | Pass | 7.9193621184E-003 | 9.4701797131E-002 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.3523996945E-002 | 5.7280856748E-002 | Pass | Pass | 2.4766366648E-004 | 2.9616267003E-003 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3184.19 | 98.46 | 0.00 | 2964.06 | 373.14 | 6619.87 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 183.92 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 429.15 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.54 | 83.54 | 235.43 | |
Exterior Lighting Total | 15013.15 | 235.43 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 331349.06 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 94635.17 | 75770.15 | 18865.02 | 0.80 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 89319.98 | 71514.51 | 17805.47 | 0.80 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105452.92 | 84431.44 | 21021.48 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 93006.7 | 2.87 | 9.79 | N/A | N/A | 11.06 | |
PACU_VAV_MID COOLING COIL | 87783.0 | 2.87 | 9.79 | N/A | N/A | 11.06 | |
PACU_VAV_TOP COOLING COIL | 103638.3 | 2.87 | 9.79 | N/A | N/A | 11.06 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15746.30 | 14944.88 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 26362.81 | 25009.26 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 55486.72 | 52638.25 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22689.63 | 21524.91 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14898.51 | 14133.72 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22821.88 | 21650.37 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14802.46 | 14042.60 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17679.39 | 16771.84 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11778.18 | 11173.57 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17839.89 | 16924.11 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11678.23 | 11078.75 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16898.33 | 16030.87 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11236.83 | 10660.00 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17026.27 | 16152.25 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11140.48 | 10568.60 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 14383.75 | 12403.25 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 15121.00 | 12903.87 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 13758.39 | 12020.65 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.72 | 12645.58 | 2211.96 | 1.00 | 1.13 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.40 | 11935.34 | 2211.96 | 1.00 | 1.13 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1337.13 | 6.37 | 14091.10 | 2211.96 | 1.00 | 1.13 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002899 | 872.99 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93006.74 | 2.87 | 9.79 | 11.06 | 6.5420 | 3.16 | 10.80 | 5.1743 | 3.33 | 11.36 | 3.4683 | 3.51 | 11.98 | 1.4446 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 87783.00 | 2.87 | 9.79 | 11.06 | 6.1746 | 3.16 | 10.80 | 4.8837 | 3.33 | 11.36 | 3.2735 | 3.51 | 11.98 | 1.3635 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 103638.34 | 2.87 | 9.79 | 11.06 | 7.2898 | 3.16 | 10.80 | 5.7658 | 3.33 | 11.36 | 3.8647 | 3.51 | 11.98 | 1.6097 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39755.14 | 45718.41 | 46.48 | 2.918 | 3.356 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 19.67 | 0.00840 | 0.425 | 0.00 |
CORE_MID | 32207.88 | 37039.06 | 37.66 | 2.362 | 2.717 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 19.67 | 0.00840 | 0.425 | 0.00 |
CORE_TOP | 34628.65 | 39822.95 | 40.49 | 2.563 | 2.948 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00884 | 26.40 | 0.00841 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8911.43 | 10248.14 | 49.43 | 0.660 | 0.759 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00877 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10453.14 | 12021.11 | 91.58 | 0.774 | 0.890 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00865 | 21.65 | 0.00840 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16363.05 | 18817.51 | 90.76 | 1.211 | 1.393 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00865 | 26.17 | 0.00841 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11918.26 | 13705.99 | 104.42 | 0.882 | 1.015 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00863 | 25.13 | 0.00841 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6424.34 | 7387.99 | 35.63 | 0.476 | 0.547 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00888 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8596.93 | 9886.47 | 75.32 | 0.632 | 0.727 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00868 | 19.67 | 0.00840 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12932.44 | 14872.31 | 71.73 | 0.957 | 1.101 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00869 | 26.32 | 0.00841 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9654.42 | 11102.58 | 84.59 | 0.715 | 0.822 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00866 | 24.22 | 0.00840 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7474.51 | 8595.69 | 41.46 | 0.553 | 0.636 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00883 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10683.93 | 12286.53 | 93.60 | 0.791 | 0.909 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00865 | 21.11 | 0.00840 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 15013.81 | 17265.88 | 83.27 | 1.111 | 1.278 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00866 | 26.10 | 0.00841 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11030.52 | 12685.10 | 96.65 | 0.817 | 0.939 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 25.13 | 0.00841 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 4660.53 | 5825.67 | 5.92 | 0.337 | 0.425 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
CORE_MID | 12315.00 | 15393.75 | 15.65 | 0.891 | 1.113 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
CORE_TOP | 25807.15 | 32258.94 | 32.80 | 1.886 | 2.357 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10534.71 | 13168.39 | 63.51 | 0.773 | 0.966 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6916.85 | 8646.06 | 65.87 | 0.508 | 0.635 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10595.99 | 13244.98 | 63.88 | 0.778 | 0.972 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6872.34 | 8590.43 | 65.45 | 0.504 | 0.631 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8212.25 | 10265.31 | 49.51 | 0.602 | 0.752 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5470.40 | 6838.00 | 52.09 | 0.401 | 0.501 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8286.61 | 10358.26 | 49.96 | 0.607 | 0.759 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5424.09 | 6780.11 | 51.66 | 0.398 | 0.497 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7851.01 | 9813.77 | 47.33 | 0.575 | 0.719 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5219.99 | 6524.99 | 49.71 | 0.383 | 0.478 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7910.29 | 9887.86 | 47.69 | 0.580 | 0.725 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5175.36 | 6469.20 | 49.29 | 0.379 | 0.474 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.72 | 5.72 | 2.94 | 2.94 | 5.7169 | 2.9351 | 5.7169 | 0.5134 | 0.3000 |
PACU_VAV_MID | 5.40 | 5.40 | 3.51 | 3.51 | 5.3958 | 3.5093 | 5.3958 | 0.6504 | 0.3000 |
PACU_VAV_TOP | 6.37 | 6.37 | 5.56 | 5.56 | 6.3704 | 5.5608 | 6.3704 | 0.8729 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15746.302 | 15746.302 | 1.006780 | 0.00013776 | 336.979 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15746.30 | 15746.30 | 1.006780 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 5825.67 | 0.00 | 15821.99 | 15821.99 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 26362.811 | 26362.811 | 1.113179 | 0.00023063 | 617.325 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26362.81 | 26362.81 | 1.113179 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 15393.75 | 0.00 | 26483.56 | 26483.56 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 55486.721 | 55486.721 | 2.357237 | 0.00048542 | 1297.097 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 55486.72 | 55486.72 | 2.357237 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 32258.94 | 0.00 | 55741.03 | 55741.03 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22689.631 | 22689.631 | 0.966406 | 0.00019850 | 530.029 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22689.63 | 22567.70 | 0.966406 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00793068 | 50.7309 | 13168.39 | 0.00 | 22793.65 | 22793.65 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14898.507 | 14898.507 | 0.634625 | 0.00013034 | 348.019 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14898.51 | 14898.51 | 0.634625 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00792969 | 50.7247 | 8646.06 | 0.00 | 14966.81 | 14966.81 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22821.882 | 22821.882 | 0.972054 | 0.00019966 | 533.116 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22821.88 | 22821.88 | 0.972054 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00793109 | 50.7335 | 13244.98 | 0.00 | 22926.51 | 22926.51 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14802.456 | 14802.456 | 0.630523 | 0.00012950 | 345.777 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14802.46 | 14802.46 | 0.630523 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00792923 | 50.7218 | 8590.43 | 0.00 | 14870.32 | 14870.32 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17679.394 | 17679.394 | 0.752497 | 0.00015467 | 413.068 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17679.39 | 17572.46 | 0.752497 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00794817 | 50.8411 | 10265.31 | 0.00 | 17760.44 | 17760.44 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11778.181 | 11778.181 | 0.501406 | 0.00010304 | 275.177 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11778.18 | 11778.18 | 0.501406 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00794950 | 50.8495 | 6838.00 | 0.00 | 11832.18 | 11832.18 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17839.893 | 17839.893 | 0.759352 | 0.00015607 | 416.814 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17839.89 | 17839.89 | 0.759352 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00794887 | 50.8456 | 10358.26 | 0.00 | 17921.68 | 17921.68 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11678.232 | 11678.232 | 0.497137 | 0.00010217 | 272.844 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11678.23 | 11678.23 | 0.497137 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00794882 | 50.8452 | 6780.11 | 0.00 | 11731.77 | 11731.77 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16898.325 | 16898.325 | 0.719102 | 0.00014783 | 394.842 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16898.33 | 16792.61 | 0.719102 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791642 | 50.6409 | 9813.77 | 0.00 | 16975.79 | 16975.79 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11236.829 | 11236.829 | 0.478262 | 0.00009830 | 262.544 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11236.83 | 11236.83 | 0.478262 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791834 | 50.6530 | 6524.99 | 0.00 | 11288.34 | 11288.34 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 17026.272 | 17026.272 | 0.724567 | 0.00014895 | 397.828 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17026.27 | 17026.27 | 0.724567 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791744 | 50.6473 | 9887.86 | 0.00 | 17104.32 | 17104.32 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 11140.482 | 11140.482 | 0.474147 | 0.00009746 | 260.295 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11140.48 | 11140.48 | 0.474147 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791728 | 50.6463 | 6469.20 | 0.00 | 11191.55 | 11191.55 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 94635.172 | 75770.148 | 5.716911 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 96698.75 | 92569.07 | 5.716911 | 24.40 | 16.62 | 0.00873181 | 11.07 | 11.07 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 16.7241 | 24.00 | 0.00879702 | 46.8332 | 67157.67 | 0.00 | 97581.57 | 76389.74 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 14383.746 | 14383.746 | 1.715073 | 0.00012584 | 251.066 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14383.75 | 14383.75 | 1.715073 | 5.88 | 4.72 | 0.00487911 | 12.89 | 11.54 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 55.7469 | 18.95 | 0.00775315 | 56.3301 | 8577.37 | 0.00 | 15014.68 | 15014.68 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 89319.979 | 71514.511 | 5.395820 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 91290.51 | 87241.31 | 5.395820 | 24.42 | 16.63 | 0.00874161 | 11.07 | 11.07 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 17.7193 | 24.00 | 0.00881366 | 46.9204 | 63385.87 | 0.00 | 92100.89 | 72099.30 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 15121.002 | 15121.002 | 1.618746 | 0.00013229 | 262.484 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15121.00 | 15121.00 | 1.618746 | 5.09 | 4.01 | 0.00465744 | 12.89 | 11.54 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 59.0642 | 18.16 | 0.00768965 | 58.7217 | 7891.00 | 0.00 | 15620.14 | 15620.14 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 105452.920 | 84431.435 | 6.370411 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 107701.96 | 103471.49 | 6.370411 | 24.36 | 16.59 | 0.00871178 | 11.07 | 11.07 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 15.0085 | 24.00 | 0.00876561 | 46.6681 | 74804.73 | 0.00 | 108736.12 | 85121.85 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 13758.390 | 13758.390 | 1.911123 | 0.00012036 | 241.836 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13758.39 | 13758.39 | 1.911123 | 6.88 | 5.64 | 0.00520426 | 12.89 | 11.54 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 50.0282 | 16.02 | 0.00787915 | 68.8830 | 8122.22 | 0.00 | 14552.15 | 14552.15 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15746.302 | 15746.302 | 1.006780 | 0.00013776 | 336.979 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 4.6584 | 4.752179 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15746.30 | 15746.30 | 1.0000 | 1.19944977 | 1.006780 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.13774146 | 60.00 | 32.22 | 27.78 | 0.000 | 15746.30 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.73 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 5825.67 | 0.00 | 15821.99 | 15821.99 | 1.19944977 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.74 | 16.57 | 0.00800000 | 46250.9 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 26362.811 | 26362.811 | 1.113179 | 0.00023063 | 617.325 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 7.7992 | 7.956205 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26362.81 | 26362.81 | 1.0000 | 1.32620981 | 1.113179 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.23060985 | 60.00 | 32.22 | 27.78 | 0.000 | 26362.81 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 15393.75 | 0.00 | 26483.56 | 26483.56 | 1.32620981 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.38 | 18.82 | 0.00800000 | 53029.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 55486.721 | 55486.721 | 2.357237 | 0.00048542 | 1297.097 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 16.4153 | 16.745701 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 55486.72 | 55486.72 | 1.0000 | 2.80834595 | 2.357237 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.48537252 | 60.00 | 32.22 | 27.78 | 0.000 | 55486.72 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 32258.94 | 0.00 | 55741.03 | 55741.03 | 2.80834595 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.26 | 18.78 | 0.00800000 | 52908.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22689.631 | 22689.631 | 0.966406 | 0.00019850 | 530.029 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 6.7126 | 6.847652 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22689.63 | 22567.70 | 1.0000 | 1.15134870 | 0.966406 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.19847854 | 60.00 | 32.22 | 27.78 | 0.000 | 22689.63 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00793068 | 21.00 | 0.00793068 | 50.7309 | 13168.39 | 0.00 | 22793.65 | 22793.65 | 1.15134870 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52857.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14898.507 | 14898.507 | 0.634625 | 0.00013034 | 348.019 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 4.4076 | 4.496318 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14898.51 | 14898.51 | 1.0000 | 0.75607459 | 0.634625 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.13032534 | 60.00 | 32.22 | 27.78 | 0.000 | 14898.51 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00792969 | 21.00 | 0.00792969 | 50.7247 | 8646.06 | 0.00 | 14966.81 | 14966.81 | 0.75607459 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52855.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22821.882 | 22821.882 | 0.972054 | 0.00019966 | 533.116 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 6.7517 | 6.887565 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22821.88 | 22821.88 | 1.0000 | 1.15807816 | 0.972054 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.19963542 | 60.00 | 32.22 | 27.78 | 0.000 | 22821.88 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00793109 | 21.00 | 0.00793109 | 50.7335 | 13244.98 | 0.00 | 22926.51 | 22926.51 | 1.15807816 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52856.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14802.456 | 14802.456 | 0.630523 | 0.00012950 | 345.777 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 4.3792 | 4.467330 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14802.46 | 14802.46 | 1.0000 | 0.75118730 | 0.630523 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.12948513 | 60.00 | 32.22 | 27.78 | 0.000 | 14802.46 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00792923 | 21.00 | 0.00792923 | 50.7218 | 8590.43 | 0.00 | 14870.32 | 14870.32 | 0.75118730 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.77 | 0.00800000 | 52855.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17679.394 | 17679.394 | 0.752497 | 0.00015467 | 413.068 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 5.2303 | 5.335580 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17679.39 | 17572.46 | 1.0000 | 0.89650395 | 0.752497 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.15465128 | 60.00 | 32.22 | 27.78 | 0.000 | 17679.39 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794817 | 21.00 | 0.00794817 | 50.8411 | 10265.31 | 0.00 | 17760.44 | 17760.44 | 0.89650395 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52870.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11778.181 | 11778.181 | 0.501406 | 0.00010304 | 275.177 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 3.4845 | 3.554614 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11778.18 | 11778.18 | 1.0000 | 0.59736074 | 0.501406 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.10303015 | 60.00 | 32.22 | 27.78 | 0.000 | 11778.18 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794950 | 21.00 | 0.00794950 | 50.8495 | 6838.00 | 0.00 | 11832.18 | 11832.18 | 0.59736074 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52867.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17839.893 | 17839.893 | 0.759352 | 0.00015607 | 416.814 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 5.2778 | 5.384018 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17839.89 | 17839.89 | 1.0000 | 0.90467078 | 0.759352 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.15605525 | 60.00 | 32.22 | 27.78 | 0.000 | 17839.89 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794887 | 21.00 | 0.00794887 | 50.8456 | 10358.26 | 0.00 | 17921.68 | 17921.68 | 0.90467078 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52870.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11678.232 | 11678.232 | 0.497137 | 0.00010217 | 272.844 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 3.4549 | 3.524450 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11678.23 | 11678.23 | 1.0000 | 0.59227499 | 0.497137 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.10215584 | 60.00 | 32.22 | 27.78 | 0.000 | 11678.23 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794882 | 21.00 | 0.00794882 | 50.8452 | 6780.11 | 0.00 | 11731.77 | 11731.77 | 0.59227499 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52867.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16898.325 | 16898.325 | 0.719102 | 0.00014783 | 394.842 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 4.9992 | 5.099856 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16898.33 | 16792.61 | 1.0000 | 0.85671783 | 0.719102 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.14781884 | 60.00 | 32.22 | 27.78 | 0.000 | 16898.33 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00791642 | 21.00 | 0.00791642 | 50.6409 | 9813.77 | 0.00 | 16975.79 | 16975.79 | 0.85671783 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52874.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11236.829 | 11236.829 | 0.478262 | 0.00009830 | 262.544 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 3.3243 | 3.391236 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11236.83 | 11236.83 | 1.0000 | 0.56978840 | 0.478262 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.09829465 | 60.00 | 32.22 | 27.78 | 0.000 | 11236.83 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00791834 | 21.00 | 0.00791834 | 50.6530 | 6524.99 | 0.00 | 11288.34 | 11288.34 | 0.56978840 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52871.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17026.272 | 17026.272 | 0.724567 | 0.00014895 | 397.828 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 5.0371 | 5.138470 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17026.27 | 17026.27 | 1.0000 | 0.86322841 | 0.724567 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.14893806 | 60.00 | 32.22 | 27.78 | 0.000 | 17026.27 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00791744 | 21.00 | 0.00791744 | 50.6473 | 9887.86 | 0.00 | 17104.32 | 17104.32 | 0.86322841 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52874.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11140.482 | 11140.482 | 0.474147 | 0.00009746 | 260.295 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 3.2958 | 3.362159 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11140.48 | 11140.48 | 1.0000 | 0.56488594 | 0.474147 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.09745185 | 60.00 | 32.22 | 27.78 | 0.000 | 11140.48 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00791728 | 21.00 | 0.00791728 | 50.6463 | 6469.20 | 0.00 | 11191.55 | 11191.55 | 0.56488594 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52871.9 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 94635.172 | 75770.148 | 5.716911 | -999.0 | -999.000 | -999.0000 | 1.02543 | 1.00000 | 1021.0720 | 1004.8586 | 1.1914 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.716911 | 6.81096747 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 96698.75 | 92569.07 | 1.0218 | 6.81096747 | 5.716911 | 24.40 | 16.62 | 0.00873181 | 46752.3 | 11.07 | 11.07 | 0.00850000 | 32557.1 | -999.0 | -999.00 | -999.00 | -999.00 | 12645.580 | 84053.17 | 26.40 | 0.00840708 | 17.04 | 0.95610000 | 16.7241 | 24.00 | 0.00879702 | 24.00 | 0.00879702 | 46.8332 | 67157.67 | 0.00 | 97581.57 | 76389.74 | 6.54198574 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14383.746 | 14383.746 | 1.715073 | 0.00012584 | 251.066 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.716911 | 6.81096747 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 4.2553 | 4.340965 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14383.75 | 14383.75 | 1.0000 | 2.04329024 | 1.715073 | 5.88 | 4.72 | 0.00487911 | 18167.6 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 0.12582245 | 60.00 | 32.22 | 27.78 | 0.000 | 14383.75 | -4.30 | 0.00265759 | -4.30 | 0.95610000 | 55.7469 | 18.71 | 0.00767763 | 18.95 | 0.00775315 | 56.3301 | 8577.37 | 0.00 | 15014.68 | 15014.68 | 2.04329024 | 2.80 | 2.80 | 0.00487911 | 15041.3 | 10.05 | 6.89 | 0.00487911 | 22389.6 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 89319.979 | 71514.511 | 5.395820 | -999.0 | -999.000 | -999.0000 | 1.02223 | 1.00000 | 1021.0902 | 1004.8586 | 1.1914 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.395820 | 6.42842886 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 91290.51 | 87241.31 | 1.0221 | 6.42842886 | 5.395820 | 24.42 | 16.63 | 0.00874161 | 46801.7 | 11.07 | 11.07 | 0.00850000 | 32557.1 | -999.0 | -999.00 | -999.00 | -999.00 | 11935.339 | 79355.17 | 26.40 | 0.00840708 | 17.04 | 0.95610000 | 17.7193 | 24.00 | 0.00881366 | 24.00 | 0.00881366 | 46.9204 | 63385.87 | 0.00 | 92100.89 | 72099.30 | 6.17455451 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15121.002 | 15121.002 | 1.618746 | 0.00013229 | 262.484 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.395820 | 6.42842886 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 4.4734 | 4.563466 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15121.00 | 15121.00 | 1.0000 | 1.92852866 | 1.618746 | 5.09 | 4.01 | 0.00465744 | 16802.7 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 0.13227163 | 60.00 | 32.22 | 27.78 | 0.000 | 15121.00 | -4.30 | 0.00265759 | -4.30 | 0.95610000 | 59.0642 | 18.63 | 0.00754292 | 18.16 | 0.00768965 | 58.7217 | 7891.00 | 0.00 | 15620.14 | 15620.14 | 1.92852866 | 2.80 | 2.80 | 0.00465744 | 14485.8 | 10.79 | 6.99 | 0.00465744 | 22585.3 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105452.920 | 84431.435 | 6.370411 | -999.0 | -999.000 | -999.0000 | 1.03152 | 1.00000 | 1021.0348 | 1004.8586 | 1.1914 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.370411 | 7.58952925 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 107701.96 | 103471.49 | 1.0213 | 7.58952925 | 6.370411 | 24.36 | 16.59 | 0.00871178 | 46659.4 | 11.07 | 11.07 | 0.00850000 | 32557.0 | -999.0 | -999.00 | -999.00 | -999.00 | 14091.096 | 93610.87 | 26.40 | 0.00840708 | 17.04 | 0.95610000 | 15.0085 | 24.00 | 0.00876561 | 24.00 | 0.00876561 | 46.6681 | 74804.73 | 0.00 | 108736.12 | 85121.85 | 7.28980022 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 13758.390 | 13758.390 | 1.911123 | 0.00012036 | 241.836 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.370411 | 7.58952925 | 4197.9300 | 999.8980 | 2.89849037 | 54.44 | 82.22 | 27.78 | 338017.59 | 4.0703 | 4.152235 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13758.39 | 13758.39 | 1.0000 | 2.27685877 | 1.911123 | 6.88 | 5.64 | 0.00520426 | 19990.7 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 0.12035212 | 60.00 | 32.22 | 27.78 | 0.000 | 13758.39 | -4.30 | 0.00265759 | -4.30 | 0.95610000 | 50.0282 | 18.06 | 0.00775380 | 16.02 | 0.00787915 | 68.8830 | 8122.22 | 0.00 | 14552.15 | 14552.15 | 2.27685877 | 2.80 | 2.80 | 0.00520426 | 15856.2 | 9.10 | 6.82 | 0.00520426 | 22247.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | FixedDryBulb | 0.00 | 5.72 | - | |||
PACU_VAV_MID_OA_CONTROLLER | FixedDryBulb | 0.00 | 5.40 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.37 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1836.00 | 2211.33 | 15.00 |
CORE_MID | 875.83 | 3906.83 | 88.50 |
CORE_TOP | 1363.33 | 4564.00 | 760.33 |
PERIMETER_TOP_ZN_3 | 2254.17 | 5131.00 | 1806.00 |
PERIMETER_TOP_ZN_2 | 2543.33 | 4653.17 | 1649.50 |
PERIMETER_TOP_ZN_1 | 2421.33 | 4639.83 | 1473.50 |
PERIMETER_TOP_ZN_4 | 2416.17 | 5038.83 | 1771.83 |
PERIMETER_BOT_ZN_3 | 1535.00 | 5388.50 | 1359.50 |
PERIMETER_BOT_ZN_2 | 2024.50 | 4622.83 | 1210.67 |
PERIMETER_BOT_ZN_1 | 1792.50 | 4878.17 | 1123.00 |
PERIMETER_BOT_ZN_4 | 1842.17 | 4990.67 | 1286.83 |
PERIMETER_MID_ZN_3 | 1565.00 | 4772.33 | 1017.50 |
PERIMETER_MID_ZN_2 | 1629.00 | 3971.67 | 927.83 |
PERIMETER_MID_ZN_1 | 1826.33 | 4373.50 | 769.50 |
PERIMETER_MID_ZN_4 | 1733.00 | 4873.00 | 1041.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4215.33 | 5595.67 | 1999.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.83 | 0.00 | 0.83 | 0.00 |
CORE_TOP | 3.33 | 0.00 | 3.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 15.17 | 0.00 | 12.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 9.33 | 0.83 | 6.00 | 0.83 |
PERIMETER_TOP_ZN_1 | 7.00 | 2.00 | 4.83 | 2.00 |
PERIMETER_TOP_ZN_4 | 8.33 | 6.83 | 5.00 | 3.83 |
PERIMETER_BOT_ZN_3 | 3.17 | 0.00 | 2.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 1.33 | 0.50 | 1.17 | 0.50 |
PERIMETER_BOT_ZN_1 | 354.33 | 0.00 | 354.33 | 0.00 |
PERIMETER_BOT_ZN_4 | 1.00 | 0.33 | 0.83 | 0.17 |
PERIMETER_MID_ZN_3 | 4.00 | 0.00 | 3.67 | 0.00 |
PERIMETER_MID_ZN_2 | 0.83 | 2.67 | 0.67 | 2.67 |
PERIMETER_MID_ZN_1 | 0.83 | 2.83 | 0.67 | 2.83 |
PERIMETER_MID_ZN_4 | 0.83 | 5.83 | 0.67 | 3.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 366.33 | 16.33 | 362.33 | 12.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.66 | 52.94 | 2698.04 | 1.082 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.66 | 52.94 | 2698.04 | 0.729 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.66 | 52.94 | 2698.04 | 0.714 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 1.012 | 0.048 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.89 | 7.07 | 360.08 | 1.548 | 0.051 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 1.617 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.89 | 7.06 | 360.05 | 1.756 | 0.051 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.832 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.89 | 7.07 | 360.08 | 1.318 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 1.301 | 0.840 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.89 | 7.06 | 360.05 | 1.448 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.851 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.53 | 7.07 | 360.08 | 1.553 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 1.605 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.89 | 7.06 | 360.05 | 1.722 | 0.043 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.66 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.66 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.66 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.89 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.89 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.53 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.66 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.66 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.66 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.89 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.89 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.53 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.38 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 17062485.72 | 0.00 | 17062485.72 | 0.00 | 17062485.72 | 13393058.27 | 4636.55 | 48.85 | 4074.60 | 16.09 |
CORE_MID | 11540779.70 | 0.00 | 11540779.70 | 0.00 | 11540779.70 | 13393058.27 | 5704.67 | 87.81 | 2967.52 | 22.90 |
CORE_TOP | 11328191.90 | 0.00 | 11328191.90 | 0.00 | 11328191.90 | 13393058.27 | 5721.86 | 74.24 | 2963.90 | 28.26 |
PERIMETER_TOP_ZN_3 | 3391569.84 | 0.00 | 3391569.84 | 327463.48 | 3719033.32 | 2823374.22 | 4150.54 | 7.36 | 4602.10 | 28.26 |
PERIMETER_TOP_ZN_2 | 3282728.26 | 0.00 | 3282728.26 | 218307.67 | 3501035.94 | 1787429.43 | 4090.32 | 3.26 | 4666.42 | 28.26 |
PERIMETER_TOP_ZN_1 | 5413729.17 | 0.00 | 5413729.17 | 327463.48 | 5741192.65 | 2823374.22 | 4092.62 | 3.27 | 4664.12 | 28.26 |
PERIMETER_TOP_ZN_4 | 3728383.02 | 0.00 | 3728383.02 | 218307.67 | 3946690.70 | 1787312.18 | 4071.93 | 3.34 | 4684.74 | 28.26 |
PERIMETER_BOT_ZN_3 | 2784679.15 | 0.00 | 2784679.15 | 174110.49 | 2958789.64 | 2823374.22 | 4242.15 | 213.85 | 4304.00 | 16.09 |
PERIMETER_BOT_ZN_2 | 2789609.65 | 0.00 | 2789609.65 | 116072.96 | 2905682.61 | 1787429.43 | 4046.39 | 0.72 | 4712.89 | 16.09 |
PERIMETER_BOT_ZN_1 | 4358730.48 | 0.00 | 4358730.48 | 2905154.06 | 7263884.54 | 2823374.22 | 4047.02 | 1.91 | 4711.07 | 16.09 |
PERIMETER_BOT_ZN_4 | 3069843.58 | 0.00 | 3069843.58 | 116072.96 | 3185916.54 | 1787312.18 | 4047.58 | 0.83 | 4711.59 | 16.09 |
PERIMETER_MID_ZN_3 | 2848457.66 | 0.00 | 2848457.66 | 272588.12 | 3121045.77 | 2823374.22 | 4104.53 | 7.48 | 4647.99 | 22.90 |
PERIMETER_MID_ZN_2 | 3123019.21 | 0.00 | 3123019.21 | 181724.32 | 3304743.53 | 1601953.02 | 3991.12 | 0.26 | 4768.62 | 931.90 |
PERIMETER_MID_ZN_1 | 5370490.14 | 0.00 | 5370490.14 | 272588.12 | 5643078.26 | 2823374.22 | 3994.41 | 1.52 | 4764.06 | 22.90 |
PERIMETER_MID_ZN_4 | 3653845.51 | 0.00 | 3653845.51 | 181724.32 | 3835569.83 | 1787312.18 | 3989.94 | 0.46 | 4769.60 | 22.90 |
Total Facility | 83746542.99 | 0.00 | 83746542.99 | 5311577.65 | 89058120.64 | 67658168.57 | 5900.62 | 439.67 | 4806.05 | 947.71 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7952 | 0.0000 | 0.7952 | 0.0000 | 0.7952 | 0.4247 | 1832.72 | 48.85 | 4061.43 |
CORE_MID | 0.5368 | 0.0000 | 0.5368 | 0.0000 | 0.5368 | 0.4247 | 2906.79 | 87.81 | 2948.40 |
CORE_TOP | 0.5268 | 0.0000 | 0.5268 | 0.0000 | 0.5268 | 0.4247 | 2922.86 | 74.24 | 2945.90 |
PERIMETER_TOP_ZN_3 | 0.1576 | 0.0000 | 0.1576 | 0.0076 | 0.1652 | 0.0895 | 1351.87 | 7.36 | 4583.77 |
PERIMETER_TOP_ZN_2 | 0.1526 | 0.0000 | 0.1526 | 0.0051 | 0.1577 | 0.0567 | 1291.65 | 3.26 | 4648.09 |
PERIMETER_TOP_ZN_1 | 0.2518 | 0.0000 | 0.2518 | 0.0076 | 0.2593 | 0.0895 | 1293.95 | 3.27 | 4645.78 |
PERIMETER_TOP_ZN_4 | 0.1733 | 0.0000 | 0.1733 | 0.0051 | 0.1784 | 0.0567 | 1273.26 | 3.34 | 4666.40 |
PERIMETER_BOT_ZN_3 | 0.1296 | 0.0000 | 0.1296 | 0.0040 | 0.1336 | 0.0895 | 1438.38 | 213.85 | 4290.77 |
PERIMETER_BOT_ZN_2 | 0.1299 | 0.0000 | 0.1299 | 0.0027 | 0.1326 | 0.0567 | 1242.68 | 0.72 | 4699.60 |
PERIMETER_BOT_ZN_1 | 0.2030 | 0.0000 | 0.2030 | 0.1317 | 0.3347 | 0.0895 | 1243.21 | 1.91 | 4697.88 |
PERIMETER_BOT_ZN_4 | 0.1429 | 0.0000 | 0.1429 | 0.0027 | 0.1456 | 0.0567 | 1244.87 | 0.83 | 4697.30 |
PERIMETER_MID_ZN_3 | 0.1324 | 0.0000 | 0.1324 | 0.0063 | 0.1387 | 0.0895 | 1306.82 | 7.48 | 4628.70 |
PERIMETER_MID_ZN_2 | 0.1531 | 0.0000 | 0.1531 | 0.0044 | 0.1576 | 0.0567 | 1193.57 | 0.19 | 3840.24 |
PERIMETER_MID_ZN_1 | 0.2498 | 0.0000 | 0.2498 | 0.0063 | 0.2561 | 0.0895 | 1196.73 | 1.52 | 4744.75 |
PERIMETER_MID_ZN_4 | 0.1698 | 0.0000 | 0.1698 | 0.0042 | 0.1740 | 0.0567 | 1192.77 | 0.42 | 4749.81 |
Total Facility | 3.9047 | 0.0000 | 3.9047 | 0.1876 | 4.0923 | 2.1513 | 3091.62 | 439.55 | 4779.98 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 42673771.70 | 0.00 | 42673771.70 | 22614548.33 | 4044.08 | 1.00 | 4714.92 | 16.09 |
PACU_VAV_MID | 37665170.43 | 0.00 | 37665170.43 | 22429071.92 | 3999.53 | 1.07 | 4759.41 | 22.90 |
PACU_VAV_TOP | 38528159.88 | 0.00 | 38528159.88 | 22614548.33 | 4105.52 | 3.58 | 4650.90 | 28.21 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.9880 | 0.0000 | 1.9880 | 0.7171 | 1241.26 | 0.58 | 4701.16 |
PACU_VAV_MID | 1.7514 | 0.0000 | 1.7514 | 0.7084 | 1201.84 | 1.07 | 4740.09 |
PACU_VAV_TOP | 1.7914 | 0.0000 | 1.7914 | 0.7171 | 1306.86 | 3.58 | 4632.56 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 3.57 | 4419.91 | 0.00 | 0.00 | 0.00 | 294.42 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 8.71 | 3886.50 | 0.00 | 0.00 | 0.00 | 879.08 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 9.25 | 3816.34 | 0.00 | 0.00 | 0.00 | 941.92 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.4771 | 2.6077 | 0.0000 | 0.0000 | 0.0000 | 1.1164 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.3044 | 2.4197 | 0.0000 | 0.0000 | 0.0000 | 1.1954 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2715 | 2.5103 | 0.0000 | 0.0000 | 0.0000 | 1.1978 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1807.44 | 15934.24 | 12-MAR-17:10 | 171046.57 | 13-JUN-16:00 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 218.29 | 385.65 | 01-JAN-00:40 | 75030.22 | 13-JUN-16:00 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:10 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:10 |
ElectricityPurchased:Facility | 1807.44 | 15934.24 | 12-MAR-17:10 | 171046.57 | 13-JUN-16:00 |
ElectricityPurchased:Plant | 1807.44 | 15934.24 | 12-MAR-17:10 | 171046.57 | 13-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1807.44 | 15934.24 | 12-MAR-17:10 | 171046.57 | 13-JUN-16:00 |
General:Cogeneration:ElectricityPurchased | 1807.44 | 15934.24 | 12-MAR-17:10 | 171046.57 | 13-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1807.44 | 15934.24 | 12-MAR-17:10 | 171046.57 | 13-JUN-16:00 |
ElectricityNet:Plant | 1807.44 | 15934.24 | 12-MAR-17:10 | 171046.57 | 13-JUN-16:00 |
Cogeneration:ElectricityNet | 1807.44 | 15934.24 | 12-MAR-17:10 | 171046.57 | 13-JUN-16:00 |
General:Cogeneration:ElectricityNet | 1807.44 | 15934.24 | 12-MAR-17:10 | 171046.57 | 13-JUN-16:00 |
Fans:Electricity | 141.51 | 0.00 | 01-JAN-00:40 | 25114.50 | 13-JUN-16:00 |
General:Fans:Electricity | 141.51 | 0.00 | 01-JAN-00:40 | 25114.50 | 13-JUN-16:00 |
ExteriorLights:Electricity | 235.43 | 0.00 | 01-JAN-08:20 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 235.43 | 0.00 | 01-JAN-08:20 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 49.27 | 0.00 | 01-JAN-00:10 | 48505.43 | 13-JUN-16:00 |
General:Cooling:Electricity | 49.27 | 0.00 | 01-JAN-00:10 | 48505.43 | 13-JUN-16:00 |
Electricity:Plant | 58.19 | 0.00 | 01-JAN-00:40 | 7079.82 | 02-JAN-12:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 56.54 | 0.00 | 01-JAN-00:10 | 6667.74 | 13-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 56.54 | 0.00 | 01-JAN-00:10 | 6667.74 | 13-FEB-13:00 |
Pumps:Electricity | 1.65 | 0.00 | 01-JAN-00:40 | 802.59 | 02-JAN-07:10 |
General:Pumps:Electricity | 1.65 | 0.00 | 01-JAN-00:40 | 802.59 | 02-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 327.20 | 0.00 | 01-JAN-00:40 | 211549.49 | 02-JAN-07:20 |
NaturalGas:Plant | 327.20 | 0.00 | 01-JAN-00:40 | 211549.49 | 02-JAN-07:20 |
Heating:NaturalGas | 327.20 | 0.00 | 01-JAN-00:40 | 211549.49 | 02-JAN-07:20 |
Boiler:Heating:NaturalGas | 327.20 | 0.00 | 01-JAN-00:40 | 211549.49 | 02-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1739.47 | 0.00 | 01-JAN-00:40 | 438563.73 | 02-JAN-07:10 |
EnergyTransfer:Building | 1066.68 | 0.00 | 01-JAN-00:40 | 160373.28 | 13-JUN-15:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 234.07 | 0.00 | 01-JAN-00:10 | 24809.45 | 24-JUL-16:00 |
Heating:EnergyTransfer | 94.47 | 0.00 | 01-JAN-00:40 | 131169.42 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 1981.79 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 94.47 | 0.00 | 01-JAN-00:40 | 131169.42 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 1981.79 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 972.21 | 0.00 | 01-JAN-00:40 | 160373.28 | 13-JUN-15:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 234.07 | 0.00 | 01-JAN-00:10 | 24809.45 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer | 972.21 | 0.00 | 01-JAN-00:40 | 160373.28 | 13-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 234.07 | 0.00 | 01-JAN-00:10 | 24809.45 | 24-JUL-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 59.01 | 0.00 | 01-JAN-00:40 | 14717.42 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.34 | 0.00 | 01-JAN-00:40 | 14717.42 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.34 | 0.00 | 01-JAN-00:40 | 14717.42 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.66 | 0.00 | 01-JAN-00:10 | 13968.27 | 21-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.66 | 0.00 | 01-JAN-00:10 | 13968.27 | 21-JUL-14:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 20.25 | 0.00 | 01-JAN-00:10 | 8500.06 | 02-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.42 | 0.00 | 01-JAN-00:10 | 8500.06 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.42 | 0.00 | 01-JAN-00:10 | 8500.06 | 02-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.83 | 0.00 | 01-JAN-00:10 | 3769.63 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.83 | 0.00 | 01-JAN-00:10 | 3769.63 | 13-JUN-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.11 | 0.00 | 01-JAN-00:10 | 5029.84 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.27 | 0.00 | 01-JAN-00:10 | 5029.84 | 02-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.27 | 0.00 | 01-JAN-00:10 | 5029.84 | 02-JAN-08:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.84 | 0.00 | 01-JAN-00:10 | 4077.01 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.84 | 0.00 | 01-JAN-00:10 | 4077.01 | 13-JUN-16:00 |
EnergyTransfer:Zone:CORE_MID | 148.95 | 0.00 | 01-JAN-00:10 | 18162.60 | 24-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.22 | 0.00 | 01-JAN-00:10 | 12750.40 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.22 | 0.00 | 01-JAN-00:10 | 12750.40 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 148.74 | 0.00 | 01-JAN-00:10 | 18162.60 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 148.74 | 0.00 | 01-JAN-00:10 | 18162.60 | 24-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 136.66 | 0.00 | 01-JAN-00:40 | 22144.59 | 26-DEC-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.57 | 0.00 | 01-JAN-00:10 | 22144.59 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.57 | 0.00 | 01-JAN-00:10 | 22144.59 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 133.09 | 0.00 | 01-JAN-00:40 | 21285.45 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 133.09 | 0.00 | 01-JAN-00:40 | 21285.45 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.17 | 0.00 | 01-JAN-00:40 | 8411.98 | 26-DEC-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.01 | 0.00 | 01-JAN-00:40 | 8411.98 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.01 | 0.00 | 01-JAN-00:40 | 8411.98 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.16 | 0.00 | 01-JAN-00:20 | 6384.45 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.16 | 0.00 | 01-JAN-00:20 | 6384.45 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.19 | 0.00 | 01-JAN-00:40 | 7873.13 | 13-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.72 | 0.00 | 01-JAN-00:40 | 6198.01 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.72 | 0.00 | 01-JAN-00:40 | 6198.01 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.47 | 0.00 | 01-JAN-00:20 | 7873.13 | 13-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.47 | 0.00 | 01-JAN-00:20 | 7873.13 | 13-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 56.07 | 0.00 | 01-JAN-00:40 | 12490.02 | 12-SEP-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 6.26 | 0.00 | 01-JAN-00:40 | 9520.58 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 6.26 | 0.00 | 01-JAN-00:40 | 9520.58 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 49.81 | 0.00 | 01-JAN-00:20 | 12490.02 | 12-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 49.81 | 0.00 | 01-JAN-00:20 | 12490.02 | 12-SEP-12:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 34.76 | 0.00 | 01-JAN-00:40 | 9592.03 | 13-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.19 | 0.00 | 01-JAN-00:40 | 6462.40 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.19 | 0.00 | 01-JAN-00:40 | 6462.40 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 29.57 | 0.00 | 01-JAN-00:20 | 9592.03 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 29.57 | 0.00 | 01-JAN-00:20 | 9592.03 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.15 | 0.00 | 01-JAN-00:10 | 6211.33 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.40 | 0.00 | 01-JAN-00:10 | 6211.33 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.40 | 0.00 | 01-JAN-00:10 | 6211.33 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.75 | 0.00 | 01-JAN-00:10 | 4165.90 | 21-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.75 | 0.00 | 01-JAN-00:10 | 4165.90 | 21-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.11 | 0.00 | 01-JAN-00:10 | 5910.50 | 13-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.95 | 0.00 | 01-JAN-00:10 | 4607.92 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.95 | 0.00 | 01-JAN-00:10 | 4607.92 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.15 | 0.00 | 01-JAN-00:10 | 5910.50 | 13-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.15 | 0.00 | 01-JAN-00:10 | 5910.50 | 13-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 48.67 | 0.00 | 01-JAN-00:10 | 10349.82 | 10-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.95 | 0.00 | 01-JAN-00:10 | 10349.82 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 15.95 | 0.00 | 01-JAN-00:10 | 10349.82 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 32.72 | 0.00 | 01-JAN-00:10 | 9990.68 | 11-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 32.72 | 0.00 | 01-JAN-00:10 | 9990.68 | 11-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.67 | 0.00 | 01-JAN-00:10 | 6914.15 | 13-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.09 | 0.00 | 01-JAN-00:10 | 4808.49 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.09 | 0.00 | 01-JAN-00:10 | 4808.49 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.59 | 0.00 | 01-JAN-00:10 | 6914.15 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.59 | 0.00 | 01-JAN-00:10 | 6914.15 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 30.92 | 0.00 | 01-JAN-00:10 | 6056.98 | 26-DEC-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.29 | 0.00 | 01-JAN-00:10 | 6056.98 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.29 | 0.00 | 01-JAN-00:10 | 6056.98 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.63 | 0.00 | 01-JAN-00:10 | 5672.60 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.63 | 0.00 | 01-JAN-00:10 | 5672.60 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.12 | 0.00 | 01-JAN-00:10 | 8066.97 | 13-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.46 | 0.00 | 01-JAN-00:10 | 4844.09 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.46 | 0.00 | 01-JAN-00:10 | 4844.09 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.66 | 0.00 | 01-JAN-00:10 | 8066.97 | 13-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.66 | 0.00 | 01-JAN-00:10 | 8066.97 | 13-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 56.55 | 0.00 | 01-JAN-00:10 | 12374.62 | 12-SEP-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.72 | 0.00 | 01-JAN-00:10 | 7003.12 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.72 | 0.00 | 01-JAN-00:10 | 7003.12 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.82 | 0.00 | 01-JAN-00:10 | 12374.62 | 12-SEP-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.82 | 0.00 | 01-JAN-00:10 | 12374.62 | 12-SEP-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.24 | 0.00 | 01-JAN-00:10 | 9108.26 | 13-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.59 | 0.00 | 01-JAN-00:10 | 4861.52 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.59 | 0.00 | 01-JAN-00:10 | 4861.52 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.65 | 0.00 | 01-JAN-00:10 | 9108.26 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.65 | 0.00 | 01-JAN-00:10 | 9108.26 | 13-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 262.28 | 0.00 | 01-JAN-00:40 | 159879.60 | 02-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 53.74 | 0.00 | 01-JAN-00:10 | 6391.26 | 14-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 53.74 | 0.00 | 01-JAN-00:10 | 6391.26 | 14-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 53.74 | 0.00 | 01-JAN-00:10 | 6391.26 | 14-FEB-12:40 |
EnergyTransfer:HVAC | 412.12 | 0.00 | 01-JAN-00:40 | 205042.72 | 13-JUN-16:00 |
HeatingCoils:EnergyTransfer | 208.54 | 0.00 | 01-JAN-00:40 | 157778.49 | 02-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 208.54 | 0.00 | 01-JAN-00:40 | 157778.49 | 02-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 208.54 | 0.00 | 01-JAN-00:40 | 157778.49 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 203.58 | 0.00 | 01-JAN-00:10 | 205033.70 | 13-JUN-16:00 |
EnergyTransfer:Plant | 260.66 | 0.00 | 01-JAN-00:40 | 158245.45 | 02-JAN-07:20 |
WaterSystems:EnergyTransfer | 53.74 | 0.00 | 01-JAN-00:10 | 6391.26 | 14-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 53.74 | 0.00 | 01-JAN-00:10 | 6391.26 | 14-FEB-12:40 |
Boilers:EnergyTransfer | 206.92 | 0.00 | 01-JAN-00:40 | 156144.34 | 02-JAN-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.005 | -234.067 | 0.000 | 0.000 | 32.911 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -170.635 |
CORE_MID | 0.000 | 0.000 | 0.216 | -148.735 | 0.000 | 0.000 | 34.142 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -112.835 |
CORE_TOP | 0.000 | 0.000 | 3.575 | -133.089 | 0.000 | 0.000 | 35.437 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -133.134 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 8.014 | -28.157 | 0.000 | 0.000 | 7.781 | 23.566 | 24.333 | 10.430 | 0.000 | 0.002 | 1.518 | 0.000 | -43.049 | 0.000 | -4.438 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.720 | -28.471 | 0.000 | 0.000 | 4.875 | 14.919 | 15.404 | 27.128 | 0.000 | 0.002 | 0.000 | 0.000 | -27.443 | 0.000 | -3.005 | -8.128 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 6.258 | -49.814 | 0.000 | 0.000 | 7.685 | 23.566 | 24.332 | 55.506 | 0.000 | 0.002 | 0.001 | 0.000 | -42.221 | 0.000 | -4.596 | -20.719 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.190 | -29.573 | 0.000 | 0.000 | 4.985 | 14.918 | 15.403 | 26.645 | 0.000 | 0.001 | 0.000 | 0.000 | -28.561 | 0.000 | -3.008 | -6.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 3.403 | -23.749 | 0.000 | 0.000 | 7.746 | 23.566 | 24.333 | 10.985 | 0.000 | 0.001 | 1.285 | 0.000 | -45.073 | 0.000 | -2.496 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.954 | -25.153 | 0.000 | 0.000 | 4.842 | 14.919 | 15.404 | 27.301 | 0.000 | 0.001 | 0.000 | 0.000 | -29.108 | 0.000 | -1.720 | -8.440 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 15.949 | -32.718 | 0.000 | 0.000 | 7.808 | 23.566 | 24.332 | 56.318 | 0.000 | 0.044 | 0.001 | 0.000 | -44.733 | 0.000 | -37.582 | -12.983 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.087 | -25.585 | 0.000 | 0.000 | 4.943 | 14.918 | 15.403 | 27.041 | 0.000 | 0.001 | 0.000 | 0.000 | -30.290 | 0.000 | -1.717 | -6.801 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.290 | -28.628 | 0.000 | 0.000 | 7.575 | 23.566 | 24.333 | 9.870 | 0.000 | 0.002 | 11.775 | 0.000 | -46.780 | 0.000 | -4.003 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.460 | -29.665 | 0.000 | 0.000 | 3.556 | 14.919 | 15.404 | 26.621 | 0.000 | 0.001 | 0.001 | 0.000 | -29.583 | 0.000 | -2.689 | -0.023 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.724 | -54.821 | 0.000 | 0.000 | 7.552 | 23.566 | 24.332 | 54.906 | 0.000 | 0.002 | 0.000 | 0.000 | -45.534 | 0.000 | -4.111 | -7.617 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.590 | -32.651 | 0.000 | 0.000 | 4.921 | 14.918 | 15.403 | 26.408 | 0.000 | 0.001 | 2.906 | 0.000 | -30.810 | 0.000 | -2.687 | -0.001 |
TOPFLOOR_PLENUM | 27.343 | -31.663 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 11.061 | 0.000 | 0.000 | 0.000 | -6.742 | -0.002 |
MIDFLOOR_PLENUM | 6.424 | -13.831 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 14.440 | 0.000 | 0.000 | 0.000 | -7.035 | -0.000 |
FIRSTFLOOR_PLENUM | 2.270 | -21.839 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 25.320 | 0.000 | 0.000 | 0.000 | -5.752 | -0.000 |
Total Facility | 36.036 | -67.333 | 58.435 | -904.876 | 0.000 | 0.000 | 176.759 | 566.263 | 729.266 | 359.159 | 0.000 | 0.066 | 68.309 | 0.000 | -443.184 | 0.000 | -91.582 | -487.319 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -39642.43 | 0.00 | 0.00 | 702.64 | 3253.54 | 10475.10 | 0.00 | 0.00 | 0.00 | 25211.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-16:00 | 0.00 | 0.00 | 0.00 | -18162.20 | 0.00 | 0.00 | 3497.12 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1903.85 |
CORE_TOP | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -21285.44 | 0.00 | 0.00 | 3497.10 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 1219.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -6384.44 | 0.00 | 0.00 | 737.22 | 2057.62 | 1435.25 | 2615.72 | 0.00 | 22.56 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -483.93 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:22 | 0.00 | 0.00 | 0.00 | -15463.90 | 0.00 | 0.00 | 15.09 | 72.37 | 302.86 | 8893.87 | 0.00 | 0.00 | 6287.29 | 0.00 | -0.00 | 0.00 | -107.58 | 0.00 |
PERIMETER_TOP_ZN_1 | 23-JUL-13:22 | 0.00 | 0.00 | 0.00 | -15952.38 | 0.00 | 0.00 | 27.29 | 114.31 | 478.41 | 9028.24 | 0.00 | 0.00 | 6491.37 | 0.00 | -0.00 | 0.00 | -187.24 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-JUL-16:02 | 0.00 | 0.00 | 0.00 | -17337.47 | 0.00 | 0.00 | 15.65 | 72.36 | 302.86 | 9360.00 | 0.00 | 0.00 | 7698.51 | 0.00 | -0.00 | 0.00 | -111.90 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 | -4165.90 | 0.00 | 0.00 | 737.23 | 2057.62 | 1435.25 | 2626.77 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2690.96 |
PERIMETER_BOT_ZN_2 | 13-JUN-09:10 | 0.00 | 0.00 | 0.00 | -5910.69 | 0.00 | 0.00 | 479.36 | 1302.65 | 908.57 | 10207.94 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.29 | -6980.54 |
PERIMETER_BOT_ZN_1 | 11-SEP-13:40 | 0.00 | 0.00 | 0.00 | -9990.55 | 0.00 | 0.00 | 757.17 | 2057.62 | 1435.24 | 14891.35 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -366.23 | -8784.60 |
PERIMETER_BOT_ZN_4 | 23-JUL-17:22 | 0.00 | 0.00 | 0.00 | -8541.49 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 8325.70 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -67.07 | -33.93 |
PERIMETER_MID_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -5672.59 | 0.00 | 0.00 | 737.22 | 2057.62 | 1435.25 | 2655.08 | 0.00 | 18.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1231.55 |
PERIMETER_MID_ZN_2 | 20-AUG-09:02 | 0.00 | 0.00 | 0.00 | -11927.88 | 0.00 | 0.00 | 16.93 | 72.37 | 302.86 | 9500.05 | 0.00 | 0.00 | 2174.74 | 0.00 | -0.00 | 0.00 | -139.07 | 0.00 |
PERIMETER_MID_ZN_1 | 24-SEP-13:32 | 0.00 | 0.00 | 0.00 | -19367.31 | 0.00 | 0.00 | 26.46 | 114.31 | 478.41 | 13303.82 | 0.00 | 0.00 | 5599.16 | 0.00 | -0.00 | 0.00 | -154.85 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-16:32 | 0.00 | 0.00 | 0.00 | -16282.04 | 0.00 | 0.00 | 15.48 | 72.36 | 302.86 | 10456.67 | 0.00 | 0.00 | 5482.24 | 0.00 | -0.00 | 0.00 | -47.58 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:20 | 0.00 | -13968.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 13963.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 04-OCT-06:03 | 0.00 | -3840.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4001.50 | 0.00 | -0.00 | 0.00 | -160.87 | 0.00 |
FIRSTFLOOR_PLENUM | 25-MAR-05:12 | 0.00 | -4458.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4458.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-JUN-15:50 | 0.00 | -20764.32 | 0.00 | -139609.10 | 0.00 | 0.00 | 17714.91 | 49443.18 | 41937.01 | 61139.22 | 0.00 | 474.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10335.05 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:01 | 0.00 | 0.00 | 4326.90 | 0.00 | 0.00 | 0.00 | 470.99 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13616.75 |
CORE_MID | 02-JAN-06:01 | 0.00 | 0.00 | 14191.72 | 0.00 | 0.00 | 0.00 | 500.41 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18802.56 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 26333.09 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29859.66 |
PERIMETER_TOP_ZN_3 | 20-NOV-05:01 | 0.00 | 0.00 | 9797.42 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2417.09 | 0.00 | -425.68 | -7698.08 |
PERIMETER_TOP_ZN_2 | 09-JAN-05:01 | 0.00 | 0.00 | 7664.85 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1730.72 | 0.00 | 0.00 | -6404.76 |
PERIMETER_TOP_ZN_1 | 09-JAN-05:01 | 0.00 | 0.00 | 11801.01 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2625.65 | 0.00 | 0.00 | -9918.78 |
PERIMETER_TOP_ZN_4 | 13-FEB-05:01 | 0.00 | 0.00 | 8189.39 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1771.12 | 0.00 | -231.53 | -6657.37 |
PERIMETER_BOT_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 7661.07 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2119.81 | 0.00 | 0.00 | -6284.69 |
PERIMETER_BOT_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 6013.32 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1457.17 | 0.00 | 0.00 | -5026.78 |
PERIMETER_BOT_ZN_1 | 10-JAN-08:00 | 0.00 | 0.00 | 10349.09 | 0.00 | 0.00 | 0.00 | 235.22 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 9338.70 | 0.00 | -3405.55 | 0.00 | -17841.21 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 6471.08 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1440.33 | 0.00 | 0.00 | -5501.37 |
PERIMETER_MID_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 7315.67 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2129.78 | 0.00 | 0.00 | -5929.32 |
PERIMETER_MID_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 6759.36 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1428.78 | 0.00 | 0.00 | -5801.21 |
PERIMETER_MID_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 9477.84 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2225.78 | 0.00 | 0.00 | -7995.49 |
PERIMETER_MID_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 6851.02 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1425.90 | 0.00 | 0.00 | -5895.74 |
TOPFLOOR_PLENUM | 10-JAN-06:06 | 16896.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -226.82 | -16669.68 |
MIDFLOOR_PLENUM | 02-JAN-07:12 | 8579.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8579.90 |
FIRSTFLOOR_PLENUM | 02-JAN-08:08 | 5342.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5342.75 |
Total Facility | 02-JAN-06:01 | 16313.31 | 0.00 | 125934.86 | 0.00 | 0.00 | 0.00 | 2543.71 | 5493.69 | 20036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22997.74 | 0.00 | -1948.12 | -145376.05 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.7577 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7169 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.5622 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.3958 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 7.2115 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.3704 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.3789 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0363 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.2811 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.9687 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.6058 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.1635 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3559 | 3.3559 | 1.0068 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7166 | 2.7166 | 0.8150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9478 | 2.9478 | 0.8844 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9664 | 0.9664 | 0.2899 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8898 | 0.8898 | 0.2669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3929 | 1.3929 | 0.4179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0145 | 1.0145 | 0.3044 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7525 | 0.7525 | 0.2348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7265 | 0.7265 | 0.2180 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1009 | 1.1009 | 0.3303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8218 | 0.8218 | 0.2466 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7191 | 0.7191 | 0.2157 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9095 | 0.9095 | 0.2728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2781 | 1.2781 | 0.3834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9390 | 0.9390 | 0.2817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.7577 | 5.7169 | 6.7577 | 2.0363 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.5622 | 5.3958 | 6.5622 | 1.9687 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 7.2115 | 6.3704 | 7.2115 | 2.1635 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6780 | 1.6780 | 1.0068 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3583 | 1.3583 | 0.8150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4739 | 1.4739 | 0.8844 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4832 | 0.4832 | 0.2899 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4449 | 0.4449 | 0.2669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6965 | 0.6965 | 0.4179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5073 | 0.5073 | 0.3044 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3762 | 0.3762 | 0.2348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3633 | 0.3633 | 0.2180 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5504 | 0.5504 | 0.3303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4109 | 0.4109 | 0.2466 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3596 | 0.3596 | 0.2157 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4547 | 0.4547 | 0.2728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6390 | 0.6390 | 0.3834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4695 | 0.4695 | 0.2817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.3789 | 2.0363 | 2.0363 | 2.0363 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.2811 | 1.9687 | 1.9687 | 1.9687 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.6058 | 2.1635 | 2.1635 | 2.1635 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 362.33 |
Number of hours cooling loads not met | 12.33 |
Number of hours not met | 374.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 327.20 | 211549.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 49.27 | 48505.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 235.43 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 141.51 | 25114.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1.65 | 802.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 56.54 | 6667.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 1807.44 |
Natural Gas | 0.00 | 327.20 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2134.64 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 9.89 |
Fans (All) | 28.40 |
Service Water Heating | 11.35 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 362.78 |
Subtotal | 362.78 |
Natural Gas [MJ/m2] | |
Space Heating | 65.67 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 65.67 |
Subtotal | 65.67 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.53 |
Space Heating | 15.33 |
Space Cooling | 2.31 |
Fans (All) | 6.63 |
Service Water Heating | 2.65 |
Receptacle Equipment | 34.16 |
Miscellaneous | 12.39 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8728.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 32.00 | 0.00 | 0.00 | 0.00 |
Average | 8754.47 | 5.53 | 0.00 | 0.00 | 0.00 |
Sum | 157580.50 | 99.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8672.83 | 87.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8728.50 | 31.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8672.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 87.17 | 0.00 | 0.00 | 0.00 |
Average | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
Sum | 157515.00 | 165.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128257.83 | 46.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128302.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 46.17 | 0.00 | 0.00 | 0.00 |
Average | 34140.66 | 2.68 | 0.00 | 0.00 | 0.00 |
Sum | 614531.83 | 48.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137427E+11 | 16500.19 | 20-JAN-16:40 | 5.67 | 5.02 | 0.190445E+10 | 2606.66 | 20-JAN-10:20 | 5.67 | 5.02 |
February | 0.134558E+11 | 16755.64 | 10-FEB-17:00 | 6.00 | 4.60 | 0.177735E+10 | 2606.66 | 17-FEB-10:20 | 4.00 | 2.99 |
March | 0.165423E+11 | 17039.61 | 31-MAR-16:00 | 9.00 | 4.96 | 0.213231E+10 | 2606.67 | 28-MAR-13:09 | 9.00 | 4.96 |
April | 0.197039E+11 | 36181.49 | 20-APR-05:03 | 1.17 | -0.2 | 0.191292E+10 | 2606.77 | 14-APR-13:00 | 1.17 | -0.2 |
May | 0.220594E+11 | 28011.65 | 24-MAY-05:13 | 8.53 | 8.48 | 0.207586E+10 | 2606.66 | 04-MAY-09:30 | 8.53 | 8.48 |
June | 0.248825E+11 | 35861.60 | 27-JUN-05:13 | 14.33 | 14.33 | 0.207185E+10 | 2606.75 | 08-JUN-13:09 | 14.33 | 14.33 |
July | 0.251398E+11 | 39642.53 | 24-JUL-06:03 | 13.17 | 13.07 | 0.192639E+10 | 2606.68 | 03-JUL-09:09 | 13.17 | 13.07 |
August | 0.275147E+11 | 36212.65 | 07-AUG-05:13 | 10.33 | 9.22 | 0.216088E+10 | 2606.69 | 08-AUG-13:09 | 17.83 | 16.43 |
September | 0.234994E+11 | 33155.31 | 14-SEP-05:13 | 11.33 | 10.21 | 0.191835E+10 | 2606.80 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.186173E+11 | 22024.23 | 03-OCT-16:00 | 14.00 | 8.96 | 0.198561E+10 | 2606.72 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.153125E+11 | 18044.11 | 10-NOV-16:20 | 9.67 | 7.83 | 0.195232E+10 | 2606.66 | 03-NOV-09:30 | 9.67 | 7.83 |
December | 0.135971E+11 | 15078.64 | 22-DEC-17:00 | 5.00 | 4.08 | 0.186471E+10 | 2606.65 | 08-DEC-10:20 | 5.00 | 4.08 |
Annual Sum or Average | 0.234067E+12 | 0.236830E+11 | ||||||||
Minimum of Months | 0.134558E+11 | 15078.64 | 1.17 | -0.2 | 0.177735E+10 | 2606.65 | 1.17 | -0.2 | ||
Maximum of Months | 0.275147E+11 | 39642.53 | 14.33 | 14.33 | 0.216088E+10 | 2606.80 | 17.83 | 16.43 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65862534.83 | 1277.50 | 20-JAN-13:00 | 8.00 | 6.08 | 0.00 | 0.00 | 01-JAN-00:10 | 8.00 | 6.08 |
February | 0.191563E+09 | 1967.23 | 22-FEB-12:40 | 9.33 | 7.76 | 0.00 | 0.00 | 01-FEB-00:10 | 9.33 | 7.76 |
March | 0.550912E+09 | 3934.64 | 25-MAR-12:40 | 13.33 | 10.44 | 0.00 | 0.00 | 01-MAR-00:10 | 13.33 | 10.44 |
April | 0.351165E+10 | 11216.79 | 28-APR-14:30 | 20.05 | 13.23 | 0.00 | 0.00 | 01-APR-00:10 | 20.05 | 13.23 |
May | 0.411792E+10 | 12336.66 | 22-MAY-14:20 | 23.33 | 15.87 | 0.00 | 0.00 | 01-MAY-00:10 | 23.33 | 15.87 |
June | 0.573214E+10 | 13896.98 | 13-JUN-14:05 | 25.25 | 17.52 | 0.00 | 0.00 | 01-JUN-00:10 | 25.25 | 17.52 |
July | 0.653087E+10 | 13968.27 | 21-JUL-14:20 | 27.00 | 16.08 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 16.08 |
August | 0.610646E+10 | 11862.55 | 14-AUG-14:50 | 24.83 | 16.12 | 0.00 | 0.00 | 01-AUG-00:10 | 24.83 | 16.12 |
September | 0.376456E+10 | 9863.33 | 13-SEP-14:05 | 23.00 | 16.22 | 0.00 | 0.00 | 01-SEP-00:10 | 23.00 | 16.22 |
October | 0.100277E+10 | 4685.84 | 07-OCT-13:13 | 17.00 | 9.43 | 0.00 | 0.00 | 01-OCT-00:10 | 17.00 | 9.43 |
November | 87190419.98 | 1508.62 | 10-NOV-13:50 | 12.00 | 8.98 | 0.00 | 0.00 | 01-NOV-00:10 | 12.00 | 8.98 |
December | 1450244.80 | 379.42 | 06-DEC-13:03 | 7.00 | 5.20 | 0.00 | 0.00 | 01-DEC-00:10 | 7.00 | 5.20 |
Annual Sum or Average | 0.316633E+11 | 0.00 | ||||||||
Minimum of Months | 1450244.80 | 379.42 | 7.00 | 5.20 | 0.00 | 0.00 | 7.00 | 5.20 | ||
Maximum of Months | 0.653087E+10 | 13968.27 | 27.00 | 17.52 | 0.00 | 0.00 | 27.00 | 17.52 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153522E+09 | 3026.92 | 07-JAN-06:11 | 3.00 | 2.13 | 0.00 | 0.00 | 01-JAN-00:10 | 3.00 | 2.13 |
February | 0.197457E+09 | 3225.04 | 11-FEB-06:11 | 2.00 | 2.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2.00 | 2.00 |
March | 0.410281E+09 | 3011.04 | 04-MAR-06:11 | 3.00 | 0.90 | 0.00 | 0.00 | 01-MAR-00:10 | 3.00 | 0.90 |
April | 0.117796E+10 | 3453.29 | 08-APR-06:03 | 0.33 | -1.0 | 0.00 | 0.00 | 01-APR-00:10 | 0.33 | -1.0 |
May | 0.151400E+10 | 3332.42 | 17-MAY-06:03 | 6.17 | 5.29 | 0.00 | 0.00 | 01-MAY-00:10 | 6.17 | 5.29 |
June | 0.229630E+10 | 3769.63 | 13-JUN-16:00 | 26.50 | 17.70 | 0.00 | 0.00 | 01-JUN-00:10 | 26.50 | 17.70 |
July | 0.259266E+10 | 3496.75 | 21-JUL-16:00 | 28.00 | 16.11 | 0.00 | 0.00 | 01-JUL-00:10 | 28.00 | 16.11 |
August | 0.265457E+10 | 3180.09 | 18-AUG-16:00 | 21.00 | 16.54 | 0.00 | 0.00 | 01-AUG-00:10 | 21.00 | 16.54 |
September | 0.185321E+10 | 2962.36 | 13-SEP-16:00 | 23.00 | 16.22 | 0.00 | 0.00 | 01-SEP-00:10 | 23.00 | 16.22 |
October | 0.663822E+09 | 3840.68 | 04-OCT-06:03 | 3.17 | 3.17 | 0.00 | 0.00 | 01-OCT-00:10 | 3.17 | 3.17 |
November | 0.248527E+09 | 3155.18 | 17-NOV-06:11 | 2.33 | 1.25 | 0.00 | 0.00 | 01-NOV-00:10 | 2.33 | 1.25 |
December | 68832708.68 | 3002.70 | 23-DEC-06:11 | 3.00 | 2.55 | 0.00 | 0.00 | 01-DEC-00:10 | 3.00 | 2.55 |
Annual Sum or Average | 0.138311E+11 | 0.00 | ||||||||
Minimum of Months | 68832708.68 | 2962.36 | 0.33 | -1.0 | 0.00 | 0.00 | 0.33 | -1.0 | ||
Maximum of Months | 0.265457E+10 | 3840.68 | 28.00 | 17.70 | 0.00 | 0.00 | 28.00 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.441440E+09 | 4215.07 | 20-JAN-06:11 | 2.00 | 1.57 | 0.00 | 0.00 | 01-JAN-00:10 | 2.00 | 1.57 |
February | 0.540517E+09 | 4239.62 | 09-FEB-06:11 | 2.33 | 2.19 | 0.00 | 0.00 | 01-FEB-00:10 | 2.33 | 2.19 |
March | 0.890205E+09 | 4458.21 | 25-MAR-05:12 | 1.67 | 1.24 | 0.00 | 0.00 | 01-MAR-00:10 | 1.67 | 1.24 |
April | 0.208148E+10 | 4449.23 | 13-APR-06:03 | 6.17 | 4.70 | 0.00 | 0.00 | 01-APR-00:10 | 6.17 | 4.70 |
May | 0.248428E+10 | 4074.94 | 17-MAY-06:03 | 6.17 | 5.29 | 0.00 | 0.00 | 01-MAY-00:10 | 6.17 | 5.29 |
June | 0.318055E+10 | 4077.01 | 13-JUN-16:00 | 26.50 | 17.70 | 0.00 | 0.00 | 01-JUN-00:10 | 26.50 | 17.70 |
July | 0.336021E+10 | 3994.47 | 21-JUL-16:00 | 28.00 | 16.11 | 0.00 | 0.00 | 01-JUL-00:10 | 28.00 | 16.11 |
August | 0.359260E+10 | 3815.48 | 30-AUG-06:07 | 9.50 | 8.94 | 0.00 | 0.00 | 01-AUG-00:10 | 9.50 | 8.94 |
September | 0.285458E+10 | 3960.03 | 13-SEP-06:07 | 11.17 | 10.64 | 0.00 | 0.00 | 01-SEP-00:10 | 11.17 | 10.64 |
October | 0.144235E+10 | 4325.89 | 12-OCT-06:03 | 3.83 | 3.83 | 0.00 | 0.00 | 01-OCT-00:10 | 3.83 | 3.83 |
November | 0.681069E+09 | 3773.85 | 17-NOV-06:11 | 2.33 | 1.25 | 0.00 | 0.00 | 01-NOV-00:10 | 2.33 | 1.25 |
December | 0.289911E+09 | 3771.79 | 08-DEC-06:11 | 1.67 | 1.24 | 0.00 | 0.00 | 01-DEC-00:10 | 1.67 | 1.24 |
Annual Sum or Average | 0.218392E+11 | 0.00 | ||||||||
Minimum of Months | 0.289911E+09 | 3771.79 | 1.67 | 1.24 | 0.00 | 0.00 | 1.67 | 1.24 | ||
Maximum of Months | 0.359260E+10 | 4458.21 | 28.00 | 17.70 | 0.00 | 0.00 | 28.00 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.851604E+10 | 8582.78 | 20-JAN-16:50 | 5.33 | 4.77 | 0.170845E+10 | 2580.43 | 20-JAN-14:00 | 5.33 | 4.77 |
February | 0.837710E+10 | 8484.51 | 10-FEB-17:00 | 6.00 | 4.60 | 0.159394E+10 | 2543.10 | 10-FEB-14:00 | 6.00 | 4.60 |
March | 0.102887E+11 | 9120.63 | 31-MAR-16:00 | 9.00 | 4.96 | 0.195088E+10 | 2581.45 | 31-MAR-13:00 | 9.00 | 4.96 |
April | 0.123346E+11 | 16168.48 | 28-APR-16:00 | 20.00 | 12.32 | 0.186494E+10 | 2606.73 | 14-APR-13:00 | 20.00 | 12.32 |
May | 0.140995E+11 | 16817.37 | 23-MAY-16:00 | 18.00 | 14.38 | 0.204032E+10 | 2606.66 | 04-MAY-09:20 | 18.00 | 14.38 |
June | 0.165662E+11 | 18060.99 | 13-JUN-16:00 | 26.50 | 17.70 | 0.205429E+10 | 2606.70 | 08-JUN-13:09 | 26.50 | 17.70 |
July | 0.169128E+11 | 18162.60 | 24-JUL-16:00 | 20.00 | 16.18 | 0.191020E+10 | 2606.65 | 03-JUL-09:20 | 20.00 | 16.18 |
August | 0.183148E+11 | 17714.27 | 18-AUG-16:00 | 21.00 | 16.54 | 0.214664E+10 | 2606.67 | 08-AUG-13:09 | 21.00 | 16.54 |
September | 0.149930E+11 | 17321.85 | 13-SEP-16:00 | 23.00 | 16.22 | 0.189500E+10 | 2606.76 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.108928E+11 | 13976.05 | 05-OCT-16:00 | 16.00 | 9.13 | 0.188416E+10 | 2606.67 | 12-OCT-09:30 | 9.00 | 9.00 |
November | 0.913934E+10 | 9719.33 | 10-NOV-16:30 | 9.00 | 7.52 | 0.176941E+10 | 2606.62 | 10-NOV-14:20 | 9.00 | 7.52 |
December | 0.830016E+10 | 7890.00 | 21-DEC-17:00 | 6.00 | 5.49 | 0.163367E+10 | 2496.58 | 21-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.148735E+12 | 0.224519E+11 | ||||||||
Minimum of Months | 0.830016E+10 | 7890.00 | 5.33 | 4.60 | 0.159394E+10 | 2496.58 | 5.33 | 4.60 | ||
Maximum of Months | 0.183148E+11 | 18162.60 | 26.50 | 17.70 | 0.214664E+10 | 2606.76 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.620227E+10 | 8231.48 | 19-JAN-16:30 | 7.00 | 6.74 | 0.155866E+10 | 2386.44 | 20-JAN-14:00 | 8.00 | 6.49 |
February | 0.645891E+10 | 8257.99 | 09-FEB-17:00 | 6.00 | 4.60 | 0.144750E+10 | 2378.22 | 03-FEB-14:00 | 6.00 | 4.60 |
March | 0.869279E+10 | 8571.98 | 31-MAR-16:00 | 9.00 | 4.96 | 0.177656E+10 | 2441.71 | 31-MAR-15:00 | 9.00 | 4.96 |
April | 0.117217E+11 | 18224.59 | 28-APR-16:00 | 20.00 | 12.32 | 0.176962E+10 | 2606.72 | 14-APR-13:00 | 20.00 | 12.32 |
May | 0.135732E+11 | 19326.76 | 23-MAY-15:40 | 18.00 | 14.38 | 0.196093E+10 | 2606.65 | 09-MAY-13:20 | 18.00 | 14.38 |
June | 0.163421E+11 | 21285.45 | 13-JUN-16:00 | 26.50 | 17.70 | 0.202119E+10 | 2606.69 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.169357E+11 | 20841.83 | 21-JUL-16:00 | 28.00 | 16.11 | 0.188487E+10 | 2606.65 | 07-JUL-09:20 | 28.00 | 16.11 |
August | 0.175559E+11 | 19708.26 | 18-AUG-15:20 | 19.67 | 16.13 | 0.211341E+10 | 2606.67 | 15-AUG-09:20 | 19.67 | 16.13 |
September | 0.135978E+11 | 18478.51 | 13-SEP-16:00 | 23.00 | 16.22 | 0.183367E+10 | 2606.75 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.941722E+10 | 12385.42 | 05-OCT-16:00 | 16.00 | 9.13 | 0.171630E+10 | 2606.63 | 04-OCT-13:20 | 16.00 | 9.13 |
November | 0.716496E+10 | 8564.77 | 10-NOV-16:20 | 9.67 | 7.83 | 0.159144E+10 | 2476.89 | 10-NOV-14:00 | 9.67 | 7.83 |
December | 0.542692E+10 | 7692.02 | 21-DEC-15:20 | 7.67 | 6.81 | 0.148338E+10 | 2308.97 | 21-DEC-14:00 | 7.67 | 6.81 |
Annual Sum or Average | 0.133089E+12 | 0.211575E+11 | ||||||||
Minimum of Months | 0.542692E+10 | 7692.02 | 6.00 | 4.60 | 0.144750E+10 | 2308.97 | 6.00 | 4.60 | ||
Maximum of Months | 0.175559E+11 | 21285.45 | 28.00 | 17.70 | 0.211341E+10 | 2606.75 | 28.00 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489235E+09 | 2098.85 | 19-JAN-15:40 | 8.33 | 7.46 | 0.306600E+09 | 428.90 | 19-JAN-14:00 | 8.33 | 7.46 |
February | 0.664046E+09 | 2057.16 | 09-FEB-15:50 | 8.00 | 5.73 | 0.278720E+09 | 425.68 | 03-FEB-14:00 | 8.00 | 5.73 |
March | 0.129306E+10 | 2361.14 | 30-MAR-15:40 | 12.00 | 6.06 | 0.340510E+09 | 462.91 | 30-MAR-13:00 | 12.00 | 6.06 |
April | 0.275270E+10 | 4521.17 | 28-APR-15:30 | 20.05 | 13.01 | 0.341141E+09 | 549.50 | 21-APR-13:20 | 20.05 | 13.01 |
May | 0.334921E+10 | 4974.63 | 22-MAY-15:30 | 23.50 | 15.68 | 0.380435E+09 | 549.50 | 22-MAY-13:00 | 23.50 | 15.68 |
June | 0.435817E+10 | 6384.45 | 13-JUN-16:00 | 26.50 | 17.70 | 0.407435E+09 | 549.51 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.458933E+10 | 6146.62 | 21-JUL-16:00 | 28.00 | 16.11 | 0.384463E+09 | 549.50 | 12-JUL-13:00 | 28.00 | 16.11 |
August | 0.461072E+10 | 5372.68 | 14-AUG-16:00 | 26.00 | 15.86 | 0.426112E+09 | 549.50 | 11-AUG-13:20 | 26.00 | 15.86 |
September | 0.334160E+10 | 4727.25 | 13-SEP-15:30 | 23.00 | 16.22 | 0.358815E+09 | 549.50 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.169297E+10 | 2756.75 | 06-OCT-16:00 | 17.00 | 9.21 | 0.324584E+09 | 508.41 | 06-OCT-15:00 | 17.00 | 9.21 |
November | 0.757070E+09 | 2247.34 | 10-NOV-15:30 | 11.50 | 8.42 | 0.305740E+09 | 450.24 | 10-NOV-14:00 | 11.50 | 8.42 |
December | 0.258502E+09 | 1786.06 | 23-DEC-17:02 | 8.00 | 6.06 | 0.294496E+09 | 406.80 | 04-DEC-10:30 | 8.00 | 6.06 |
Annual Sum or Average | 0.281566E+11 | 0.414905E+10 | ||||||||
Minimum of Months | 0.258502E+09 | 1786.06 | 8.00 | 5.73 | 0.278720E+09 | 406.80 | 8.00 | 5.73 | ||
Maximum of Months | 0.461072E+10 | 6384.45 | 28.00 | 17.70 | 0.426112E+09 | 549.51 | 28.00 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475023E+09 | 1988.87 | 20-JAN-10:30 | 5.00 | 4.55 | 0.194130E+09 | 279.09 | 20-JAN-10:39 | 5.33 | 4.86 |
February | 0.668411E+09 | 2118.22 | 24-FEB-10:35 | 5.67 | 4.28 | 0.177286E+09 | 290.94 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.113893E+10 | 2105.49 | 30-MAR-10:30 | 9.50 | 6.81 | 0.213973E+09 | 284.61 | 31-MAR-09:50 | 8.33 | 5.01 |
April | 0.305425E+10 | 6149.91 | 28-APR-09:40 | 17.33 | 11.52 | 0.231084E+09 | 347.88 | 19-APR-09:09 | 17.33 | 11.52 |
May | 0.349456E+10 | 7156.94 | 23-MAY-09:10 | 19.17 | 14.75 | 0.250386E+09 | 347.88 | 22-MAY-13:50 | 19.17 | 14.75 |
June | 0.432057E+10 | 8057.37 | 25-JUN-09:32 | 17.33 | 12.62 | 0.261151E+09 | 347.89 | 20-JUN-09:09 | 17.33 | 12.62 |
July | 0.451523E+10 | 15466.65 | 23-JUL-09:22 | 20.50 | 15.83 | 0.247484E+09 | 347.88 | 03-JUL-09:09 | 20.50 | 15.83 |
August | 0.475376E+10 | 6989.55 | 17-AUG-09:30 | 19.50 | 16.05 | 0.275112E+09 | 347.88 | 14-AUG-09:50 | 19.50 | 16.05 |
September | 0.351526E+10 | 6128.55 | 12-SEP-09:20 | 17.67 | 14.44 | 0.239197E+09 | 347.89 | 06-SEP-09:09 | 17.67 | 14.44 |
October | 0.162069E+10 | 2947.95 | 04-OCT-10:00 | 13.00 | 9.81 | 0.208992E+09 | 347.87 | 04-OCT-09:00 | 13.00 | 9.81 |
November | 0.649219E+09 | 1967.45 | 03-NOV-09:50 | 6.83 | 5.00 | 0.193101E+09 | 277.21 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.264989E+09 | 1673.22 | 06-DEC-10:00 | 4.00 | 3.12 | 0.186544E+09 | 257.57 | 04-DEC-10:09 | 4.00 | 3.12 |
Annual Sum or Average | 0.284709E+11 | 0.267844E+10 | ||||||||
Minimum of Months | 0.264989E+09 | 1673.22 | 4.00 | 3.12 | 0.177286E+09 | 257.57 | 4.00 | 3.12 | ||
Maximum of Months | 0.475376E+10 | 15466.65 | 20.50 | 16.05 | 0.275112E+09 | 347.89 | 20.50 | 16.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155337E+10 | 5992.71 | 20-JAN-12:00 | 8.00 | 6.08 | 0.321838E+09 | 549.49 | 20-JAN-14:09 | 8.83 | 6.56 |
February | 0.183787E+10 | 7479.95 | 17-FEB-14:07 | 6.00 | 3.06 | 0.300154E+09 | 549.50 | 09-FEB-14:30 | 6.00 | 3.06 |
March | 0.211408E+10 | 4135.40 | 28-MAR-12:20 | 11.33 | 7.17 | 0.347779E+09 | 532.28 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.517936E+10 | 13734.65 | 30-APR-13:32 | 22.67 | 12.88 | 0.356132E+09 | 549.53 | 14-APR-13:00 | 22.67 | 12.88 |
May | 0.522585E+10 | 10194.89 | 22-MAY-13:30 | 22.50 | 15.28 | 0.382153E+09 | 549.51 | 22-MAY-13:50 | 22.83 | 15.60 |
June | 0.619394E+10 | 10380.09 | 13-JUN-13:20 | 24.37 | 17.19 | 0.398664E+09 | 549.53 | 08-JUN-13:09 | 24.37 | 17.19 |
July | 0.684619E+10 | 15951.96 | 23-JUL-13:22 | 21.50 | 16.21 | 0.377593E+09 | 549.51 | 12-JUL-13:00 | 21.50 | 16.21 |
August | 0.785101E+10 | 14731.42 | 20-AUG-13:32 | 23.00 | 14.82 | 0.423952E+09 | 549.51 | 21-AUG-13:50 | 21.00 | 14.91 |
September | 0.681947E+10 | 12490.02 | 12-SEP-12:40 | 20.33 | 16.13 | 0.371800E+09 | 549.52 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.355111E+10 | 10725.04 | 03-OCT-13:30 | 13.50 | 9.36 | 0.344227E+09 | 549.51 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.169382E+10 | 6423.35 | 03-NOV-12:40 | 9.00 | 5.48 | 0.318694E+09 | 549.50 | 03-NOV-13:30 | 9.00 | 5.54 |
December | 0.947924E+09 | 4671.72 | 18-DEC-13:30 | 8.00 | 5.46 | 0.302905E+09 | 549.49 | 18-DEC-14:09 | 8.00 | 5.67 |
Annual Sum or Average | 0.498140E+11 | 0.424589E+10 | ||||||||
Minimum of Months | 0.947924E+09 | 4135.40 | 6.00 | 3.06 | 0.300154E+09 | 532.28 | 6.00 | 3.06 | ||
Maximum of Months | 0.785101E+10 | 15951.96 | 24.37 | 17.19 | 0.423952E+09 | 549.53 | 24.37 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.502609E+09 | 2616.36 | 19-JAN-15:50 | 8.17 | 7.46 | 0.194794E+09 | 298.73 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.755627E+09 | 2905.87 | 27-FEB-16:40 | 8.00 | 6.81 | 0.180118E+09 | 322.39 | 27-FEB-16:49 | 8.00 | 6.89 |
March | 0.114876E+10 | 2963.99 | 23-MAR-16:50 | 10.00 | 6.65 | 0.213815E+09 | 321.47 | 23-MAR-15:00 | 10.00 | 6.65 |
April | 0.305102E+10 | 9592.76 | 30-APR-16:12 | 24.00 | 12.95 | 0.210176E+09 | 347.85 | 28-APR-13:00 | 24.00 | 12.95 |
May | 0.363419E+10 | 8843.09 | 22-MAY-16:00 | 23.00 | 15.28 | 0.231494E+09 | 347.85 | 22-MAY-13:00 | 23.00 | 15.28 |
June | 0.466189E+10 | 11584.22 | 25-JUN-17:22 | 21.50 | 17.05 | 0.244885E+09 | 347.86 | 09-JUN-13:00 | 21.50 | 17.05 |
July | 0.493485E+10 | 17341.71 | 23-JUL-16:02 | 21.83 | 16.81 | 0.232531E+09 | 347.85 | 12-JUL-13:00 | 21.83 | 16.81 |
August | 0.483396E+10 | 17278.85 | 20-AUG-16:12 | 23.33 | 14.80 | 0.257239E+09 | 347.85 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.355228E+10 | 8029.00 | 12-SEP-16:00 | 21.00 | 15.99 | 0.217904E+09 | 347.85 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.160837E+10 | 4987.20 | 03-OCT-15:40 | 14.00 | 8.96 | 0.203858E+09 | 338.70 | 11-OCT-15:50 | 13.67 | 10.49 |
November | 0.655233E+09 | 2664.20 | 10-NOV-15:40 | 11.33 | 8.41 | 0.193886E+09 | 302.71 | 10-NOV-15:50 | 11.17 | 8.40 |
December | 0.234828E+09 | 2160.09 | 21-DEC-14:40 | 8.00 | 6.98 | 0.186530E+09 | 270.32 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.295736E+11 | 0.256723E+10 | ||||||||
Minimum of Months | 0.234828E+09 | 2160.09 | 8.00 | 6.65 | 0.180118E+09 | 270.32 | 8.00 | 6.65 | ||
Maximum of Months | 0.493485E+10 | 17341.71 | 24.00 | 17.05 | 0.257239E+09 | 347.86 | 24.00 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530115E+09 | 1673.54 | 19-JAN-15:20 | 8.67 | 7.45 | 0.308279E+09 | 427.75 | 19-JAN-14:00 | 8.67 | 7.45 |
February | 0.645350E+09 | 1618.05 | 10-FEB-15:50 | 7.00 | 5.15 | 0.279596E+09 | 419.18 | 03-FEB-14:00 | 7.00 | 5.15 |
March | 0.114077E+10 | 1824.80 | 30-MAR-14:00 | 13.00 | 7.37 | 0.340018E+09 | 452.75 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.217395E+10 | 2353.27 | 28-APR-16:00 | 20.00 | 12.32 | 0.332891E+09 | 534.81 | 28-APR-13:00 | 20.00 | 12.32 |
May | 0.261234E+10 | 2561.47 | 23-MAY-15:20 | 18.00 | 14.38 | 0.376286E+09 | 549.48 | 23-MAY-13:00 | 18.00 | 14.38 |
June | 0.321228E+10 | 4095.62 | 13-JUN-16:00 | 26.50 | 17.70 | 0.408768E+09 | 549.50 | 23-JUN-13:20 | 14.33 | 13.16 |
July | 0.342582E+10 | 4165.90 | 21-JUL-16:00 | 28.00 | 16.11 | 0.389643E+09 | 549.50 | 07-JUL-13:20 | 28.00 | 16.11 |
August | 0.353962E+10 | 3476.46 | 17-AUG-15:20 | 21.67 | 16.58 | 0.433834E+09 | 549.50 | 09-AUG-13:20 | 21.67 | 16.58 |
September | 0.287248E+10 | 3263.08 | 13-SEP-15:30 | 23.00 | 16.22 | 0.368716E+09 | 549.50 | 12-SEP-13:20 | 23.00 | 16.22 |
October | 0.199513E+10 | 2190.54 | 06-OCT-15:50 | 17.00 | 9.21 | 0.337589E+09 | 505.44 | 06-OCT-13:00 | 17.00 | 9.21 |
November | 0.114603E+10 | 1883.19 | 10-NOV-15:10 | 11.83 | 8.42 | 0.312867E+09 | 461.55 | 10-NOV-14:00 | 11.83 | 8.42 |
December | 0.454990E+09 | 1588.82 | 22-DEC-13:50 | 7.00 | 5.54 | 0.296255E+09 | 414.93 | 22-DEC-14:09 | 7.00 | 5.54 |
Annual Sum or Average | 0.237489E+11 | 0.418474E+10 | ||||||||
Minimum of Months | 0.454990E+09 | 1588.82 | 7.00 | 5.15 | 0.279596E+09 | 414.93 | 7.00 | 5.15 | ||
Maximum of Months | 0.353962E+10 | 4165.90 | 28.00 | 17.70 | 0.433834E+09 | 549.50 | 28.00 | 16.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.518840E+09 | 1692.24 | 20-JAN-10:13 | 4.67 | 4.23 | 0.195127E+09 | 286.73 | 20-JAN-10:20 | 4.67 | 4.23 |
February | 0.650531E+09 | 1736.76 | 24-FEB-10:30 | 5.50 | 4.13 | 0.178315E+09 | 291.79 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.996147E+09 | 1675.23 | 30-MAR-10:30 | 9.50 | 6.81 | 0.213861E+09 | 283.32 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.251958E+10 | 5345.45 | 30-APR-08:10 | 17.50 | 12.51 | 0.229881E+09 | 347.88 | 19-APR-09:20 | 17.50 | 12.51 |
May | 0.284546E+10 | 5383.15 | 23-MAY-09:20 | 19.33 | 14.73 | 0.251936E+09 | 347.88 | 02-MAY-09:20 | 19.33 | 14.73 |
June | 0.344694E+10 | 5910.86 | 13-JUN-09:10 | 21.67 | 15.93 | 0.263059E+09 | 347.88 | 20-JUN-09:09 | 16.33 | 13.20 |
July | 0.366904E+10 | 5627.13 | 10-JUL-09:30 | 23.50 | 16.17 | 0.251024E+09 | 347.88 | 03-JUL-09:09 | 23.50 | 16.17 |
August | 0.401295E+10 | 5493.86 | 18-AUG-09:20 | 19.03 | 15.27 | 0.280152E+09 | 347.88 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.323954E+10 | 5053.07 | 12-SEP-09:10 | 17.83 | 14.41 | 0.246187E+09 | 347.89 | 06-SEP-09:09 | 17.83 | 14.41 |
October | 0.185408E+10 | 2707.35 | 04-OCT-10:00 | 13.00 | 9.81 | 0.217062E+09 | 347.88 | 03-OCT-09:20 | 13.00 | 9.81 |
November | 0.971826E+09 | 1744.37 | 03-NOV-09:35 | 6.67 | 4.83 | 0.196417E+09 | 292.52 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.428256E+09 | 1535.91 | 08-DEC-10:30 | 5.00 | 3.66 | 0.187711E+09 | 269.54 | 08-DEC-10:39 | 5.33 | 3.83 |
Annual Sum or Average | 0.251532E+11 | 0.271073E+10 | ||||||||
Minimum of Months | 0.428256E+09 | 1535.91 | 4.67 | 3.66 | 0.178315E+09 | 269.54 | 4.67 | 3.83 | ||
Maximum of Months | 0.401295E+10 | 5910.86 | 23.50 | 16.17 | 0.280152E+09 | 347.89 | 23.50 | 16.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.768288E+09 | 3208.00 | 21-JAN-11:40 | 6.33 | 5.22 | 0.306081E+09 | 510.60 | 20-JAN-11:00 | 6.33 | 5.22 |
February | 0.921262E+09 | 3264.35 | 04-FEB-14:00 | 9.00 | 6.13 | 0.282345E+09 | 506.75 | 17-FEB-14:50 | 6.00 | 3.32 |
March | 0.846556E+09 | 2684.95 | 25-MAR-11:50 | 11.92 | 8.82 | 0.329886E+09 | 456.20 | 10-MAR-14:00 | 11.92 | 8.82 |
April | 0.306384E+10 | 7845.94 | 28-APR-12:10 | 18.00 | 11.89 | 0.336172E+09 | 549.50 | 17-APR-13:00 | 18.00 | 11.89 |
May | 0.309663E+10 | 6731.06 | 22-MAY-13:50 | 22.83 | 15.60 | 0.362798E+09 | 549.51 | 22-MAY-13:50 | 22.83 | 15.60 |
June | 0.394785E+10 | 7454.91 | 13-JUN-13:50 | 24.92 | 17.39 | 0.382835E+09 | 549.51 | 09-JUN-13:00 | 24.92 | 17.39 |
July | 0.466932E+10 | 8617.42 | 21-JUL-16:10 | 28.17 | 16.20 | 0.373454E+09 | 549.50 | 21-JUL-13:20 | 28.17 | 16.20 |
August | 0.562504E+10 | 8725.15 | 20-AUG-14:14 | 23.00 | 14.82 | 0.427317E+09 | 549.50 | 21-AUG-13:39 | 21.00 | 14.82 |
September | 0.529025E+10 | 9990.68 | 11-SEP-13:40 | 20.67 | 15.89 | 0.377593E+09 | 549.52 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.283349E+10 | 9008.19 | 02-OCT-12:08 | 14.00 | 10.70 | 0.341769E+09 | 549.50 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.122994E+10 | 3191.46 | 03-NOV-14:30 | 9.00 | 5.72 | 0.310481E+09 | 527.59 | 15-NOV-14:39 | 12.00 | 8.90 |
December | 0.424951E+09 | 2997.37 | 18-DEC-14:00 | 8.00 | 5.67 | 0.291674E+09 | 504.77 | 18-DEC-14:09 | 8.00 | 5.67 |
Annual Sum or Average | 0.327174E+11 | 0.412240E+10 | ||||||||
Minimum of Months | 0.424951E+09 | 2684.95 | 6.33 | 5.22 | 0.282345E+09 | 456.20 | 6.00 | 3.32 | ||
Maximum of Months | 0.562504E+10 | 9990.68 | 28.17 | 17.39 | 0.427317E+09 | 549.52 | 28.17 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514751E+09 | 2077.70 | 19-JAN-15:50 | 8.17 | 7.46 | 0.195549E+09 | 294.74 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.704607E+09 | 2246.19 | 27-FEB-16:40 | 8.00 | 6.81 | 0.179990E+09 | 311.46 | 27-FEB-16:49 | 8.00 | 6.89 |
March | 0.993796E+09 | 2270.27 | 23-MAR-17:10 | 9.67 | 6.57 | 0.213207E+09 | 299.29 | 23-MAR-15:00 | 9.67 | 6.57 |
April | 0.244068E+10 | 5329.00 | 28-APR-16:00 | 20.00 | 12.32 | 0.208541E+09 | 347.76 | 28-APR-13:00 | 20.00 | 12.32 |
May | 0.292865E+10 | 5953.61 | 22-MAY-16:00 | 23.00 | 15.28 | 0.234488E+09 | 347.85 | 22-MAY-13:00 | 23.00 | 15.28 |
June | 0.368025E+10 | 6914.15 | 13-JUN-16:00 | 26.50 | 17.70 | 0.251013E+09 | 347.85 | 26-JUN-13:20 | 22.00 | 16.85 |
July | 0.397586E+10 | 8541.71 | 23-JUL-17:22 | 21.00 | 16.54 | 0.240594E+09 | 347.85 | 18-JUL-13:20 | 21.00 | 16.54 |
August | 0.396002E+10 | 7296.03 | 20-AUG-16:12 | 23.33 | 14.80 | 0.267184E+09 | 347.85 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.319351E+10 | 5873.08 | 12-SEP-16:00 | 21.00 | 15.99 | 0.227475E+09 | 347.85 | 13-SEP-13:20 | 22.33 | 15.98 |
October | 0.188840E+10 | 4014.88 | 03-OCT-16:00 | 14.00 | 8.96 | 0.208620E+09 | 338.69 | 11-OCT-15:00 | 13.00 | 10.30 |
November | 0.965438E+09 | 2177.91 | 10-NOV-15:40 | 11.33 | 8.41 | 0.195749E+09 | 304.80 | 10-NOV-15:50 | 11.17 | 8.40 |
December | 0.339603E+09 | 1788.35 | 21-DEC-14:50 | 8.00 | 6.98 | 0.187536E+09 | 274.09 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.255856E+11 | 0.260995E+10 | ||||||||
Minimum of Months | 0.339603E+09 | 1788.35 | 8.00 | 6.57 | 0.179990E+09 | 274.09 | 8.00 | 6.57 | ||
Maximum of Months | 0.397586E+10 | 8541.71 | 26.50 | 17.70 | 0.267184E+09 | 347.85 | 23.00 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.800476E+09 | 1766.21 | 19-JAN-15:40 | 8.33 | 7.46 | 0.314684E+09 | 465.91 | 19-JAN-14:00 | 8.33 | 7.46 |
February | 0.971080E+09 | 1728.79 | 10-FEB-16:00 | 7.00 | 5.15 | 0.288972E+09 | 458.56 | 10-FEB-14:00 | 7.00 | 5.15 |
March | 0.167678E+10 | 1960.88 | 30-MAR-15:40 | 12.00 | 6.06 | 0.359864E+09 | 503.11 | 30-MAR-13:00 | 12.00 | 6.06 |
April | 0.260517E+10 | 4113.72 | 28-APR-15:30 | 20.05 | 13.01 | 0.364712E+09 | 549.51 | 14-APR-13:00 | 20.05 | 13.01 |
May | 0.306838E+10 | 4331.97 | 22-MAY-15:40 | 23.33 | 15.55 | 0.406649E+09 | 549.50 | 02-MAY-13:20 | 23.33 | 15.55 |
June | 0.394912E+10 | 5672.60 | 13-JUN-16:00 | 26.50 | 17.70 | 0.425630E+09 | 549.51 | 08-JUN-13:09 | 26.50 | 17.70 |
July | 0.419886E+10 | 5483.71 | 21-JUL-16:00 | 28.00 | 16.11 | 0.397607E+09 | 549.50 | 07-JUL-09:20 | 28.00 | 16.11 |
August | 0.427739E+10 | 4896.14 | 14-AUG-16:00 | 26.00 | 15.86 | 0.444864E+09 | 549.50 | 15-AUG-09:20 | 16.00 | 13.59 |
September | 0.316685E+10 | 4519.92 | 13-SEP-15:30 | 23.00 | 16.22 | 0.383305E+09 | 549.52 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.203815E+10 | 2491.20 | 06-OCT-15:50 | 17.00 | 9.21 | 0.351789E+09 | 545.56 | 06-OCT-13:00 | 17.00 | 9.21 |
November | 0.124718E+10 | 1886.29 | 10-NOV-15:30 | 11.50 | 8.42 | 0.319752E+09 | 488.60 | 10-NOV-14:00 | 11.50 | 8.42 |
December | 0.628564E+09 | 1600.11 | 21-DEC-14:40 | 8.00 | 6.98 | 0.297997E+09 | 438.80 | 22-DEC-14:09 | 7.00 | 5.54 |
Annual Sum or Average | 0.286280E+11 | 0.435582E+10 | ||||||||
Minimum of Months | 0.628564E+09 | 1600.11 | 7.00 | 5.15 | 0.288972E+09 | 438.80 | 7.00 | 5.15 | ||
Maximum of Months | 0.427739E+10 | 5672.60 | 28.00 | 17.70 | 0.444864E+09 | 549.52 | 28.00 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.626003E+09 | 3613.64 | 20-JAN-11:02 | 6.33 | 5.61 | 0.145928E+09 | 356.46 | 20-JAN-11:09 | 6.33 | 5.61 |
February | 0.783560E+09 | 3806.26 | 24-FEB-11:02 | 6.00 | 4.60 | 0.134990E+09 | 356.46 | 17-FEB-11:09 | 6.00 | 4.60 |
March | 0.126458E+10 | 3614.03 | 31-MAR-10:02 | 8.83 | 5.31 | 0.164210E+09 | 356.45 | 31-MAR-10:09 | 8.83 | 5.31 |
April | 0.317179E+10 | 7347.86 | 28-APR-10:05 | 17.67 | 11.40 | 0.173934E+09 | 356.47 | 14-APR-14:09 | 17.67 | 11.40 |
May | 0.351778E+10 | 7808.92 | 23-MAY-10:05 | 20.00 | 14.59 | 0.189168E+09 | 356.46 | 22-MAY-14:09 | 20.00 | 14.59 |
June | 0.420649E+10 | 8282.42 | 13-JUN-10:05 | 22.00 | 15.85 | 0.195493E+09 | 356.46 | 09-JUN-14:09 | 22.00 | 15.85 |
July | 0.442069E+10 | 9625.05 | 23-JUL-08:53 | 20.00 | 15.65 | 0.184761E+09 | 356.46 | 10-JUL-10:09 | 20.00 | 15.65 |
August | 0.476866E+10 | 11928.63 | 20-AUG-09:02 | 16.83 | 13.42 | 0.205079E+09 | 356.46 | 14-AUG-10:09 | 16.83 | 13.42 |
September | 0.370851E+10 | 7245.62 | 12-SEP-10:05 | 17.17 | 14.50 | 0.179295E+09 | 356.47 | 07-SEP-10:09 | 17.17 | 14.50 |
October | 0.185093E+10 | 5352.84 | 04-OCT-12:02 | 13.17 | 9.89 | 0.161764E+09 | 356.46 | 13-OCT-10:09 | 12.00 | 10.91 |
November | 0.904591E+09 | 3706.94 | 03-NOV-10:02 | 7.33 | 5.22 | 0.146988E+09 | 356.46 | 03-NOV-10:09 | 7.33 | 5.22 |
December | 0.441246E+09 | 2442.61 | 08-DEC-11:03 | 6.17 | 4.24 | 0.139126E+09 | 321.13 | 08-DEC-11:09 | 6.17 | 4.24 |
Annual Sum or Average | 0.296648E+11 | 0.202073E+10 | ||||||||
Minimum of Months | 0.441246E+09 | 2442.61 | 6.00 | 4.24 | 0.134990E+09 | 321.13 | 6.00 | 4.24 | ||
Maximum of Months | 0.476866E+10 | 11928.63 | 22.00 | 15.85 | 0.205079E+09 | 356.47 | 22.00 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211576E+10 | 7398.65 | 20-JAN-12:00 | 8.00 | 6.08 | 0.331355E+09 | 549.50 | 20-JAN-14:30 | 8.50 | 6.54 |
February | 0.245476E+10 | 8359.83 | 17-FEB-13:25 | 6.00 | 3.38 | 0.309790E+09 | 549.50 | 09-FEB-14:30 | 6.00 | 3.38 |
March | 0.280143E+10 | 4615.38 | 28-MAR-12:05 | 11.67 | 7.18 | 0.360090E+09 | 549.50 | 10-MAR-14:30 | 11.67 | 7.18 |
April | 0.554834E+10 | 13665.53 | 30-APR-12:53 | 22.00 | 13.06 | 0.367090E+09 | 549.53 | 14-APR-13:00 | 22.00 | 13.06 |
May | 0.547598E+10 | 9574.53 | 23-MAY-13:10 | 18.17 | 14.45 | 0.395426E+09 | 549.51 | 22-MAY-13:50 | 18.17 | 14.45 |
June | 0.612190E+10 | 9679.82 | 13-JUN-13:10 | 24.18 | 17.12 | 0.410667E+09 | 549.53 | 08-JUN-13:09 | 24.18 | 17.12 |
July | 0.671473E+10 | 9861.54 | 21-JUL-13:10 | 26.17 | 16.40 | 0.387581E+09 | 549.51 | 12-JUL-13:00 | 26.17 | 16.40 |
August | 0.790077E+10 | 11194.29 | 30-AUG-12:50 | 21.00 | 15.45 | 0.435931E+09 | 549.51 | 21-AUG-13:50 | 21.00 | 15.45 |
September | 0.728281E+10 | 19367.73 | 24-SEP-13:32 | 20.33 | 15.24 | 0.382868E+09 | 549.52 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.444521E+10 | 11196.43 | 03-OCT-13:07 | 13.17 | 9.32 | 0.357350E+09 | 549.51 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.251093E+10 | 7627.88 | 03-NOV-12:25 | 9.00 | 5.54 | 0.329712E+09 | 549.50 | 03-NOV-13:30 | 9.00 | 5.54 |
December | 0.144842E+10 | 5731.08 | 18-DEC-13:25 | 8.00 | 5.46 | 0.310444E+09 | 549.50 | 21-DEC-14:39 | 8.00 | 6.98 |
Annual Sum or Average | 0.548210E+11 | 0.437830E+10 | ||||||||
Minimum of Months | 0.144842E+10 | 4615.38 | 6.00 | 3.38 | 0.309790E+09 | 549.50 | 6.00 | 3.38 | ||
Maximum of Months | 0.790077E+10 | 19367.73 | 26.17 | 17.12 | 0.435931E+09 | 549.53 | 26.17 | 17.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.817172E+09 | 2572.63 | 19-JAN-15:50 | 8.17 | 7.46 | 0.196920E+09 | 311.68 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.109129E+10 | 2824.85 | 27-FEB-16:40 | 8.00 | 6.81 | 0.183027E+09 | 334.61 | 27-FEB-16:49 | 8.00 | 6.89 |
March | 0.163464E+10 | 3003.56 | 23-MAR-16:40 | 10.00 | 6.65 | 0.217394E+09 | 334.90 | 23-MAR-15:00 | 10.00 | 6.65 |
April | 0.330321E+10 | 8959.83 | 30-APR-16:12 | 24.00 | 12.95 | 0.215981E+09 | 347.85 | 28-APR-13:00 | 24.00 | 12.95 |
May | 0.382467E+10 | 14640.97 | 21-MAY-16:52 | 20.00 | 12.79 | 0.239223E+09 | 347.85 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.462807E+10 | 16280.68 | 25-JUN-16:32 | 22.33 | 14.34 | 0.252790E+09 | 347.86 | 09-JUN-13:00 | 22.33 | 14.34 |
July | 0.485549E+10 | 11896.66 | 22-JUL-17:05 | 29.17 | 16.61 | 0.239438E+09 | 347.85 | 12-JUL-13:00 | 29.17 | 16.61 |
August | 0.484639E+10 | 11242.09 | 13-AUG-17:32 | 18.33 | 14.20 | 0.266170E+09 | 347.85 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.381634E+10 | 7893.62 | 12-SEP-16:00 | 21.00 | 15.99 | 0.226450E+09 | 347.86 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.218382E+10 | 5184.23 | 03-OCT-15:40 | 14.00 | 8.96 | 0.209599E+09 | 344.00 | 05-OCT-13:00 | 16.00 | 8.75 |
November | 0.114862E+10 | 2623.51 | 10-NOV-15:40 | 11.33 | 8.41 | 0.196594E+09 | 316.54 | 10-NOV-15:50 | 11.17 | 8.40 |
December | 0.501677E+09 | 2186.21 | 21-DEC-14:40 | 8.00 | 6.98 | 0.187621E+09 | 285.87 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.326514E+11 | 0.263121E+10 | ||||||||
Minimum of Months | 0.501677E+09 | 2186.21 | 8.00 | 6.65 | 0.183027E+09 | 285.87 | 8.00 | 6.65 | ||
Maximum of Months | 0.485549E+10 | 16280.68 | 29.17 | 16.61 | 0.266170E+09 | 347.86 | 29.17 | 16.61 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4714241.97 | 4327.11 | 02-JAN-06:01 | 1.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 4714241.97 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 4714241.97 | 4327.11 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517507E+10 | 16896.43 | 10-JAN-06:06 | -4.0 |
February | 0.349697E+10 | 15438.47 | 13-FEB-06:13 | -1.0 |
March | 0.297419E+10 | 14527.54 | 06-MAR-06:16 | 4.00 |
April | 0.125859E+10 | 9173.67 | 08-APR-05:03 | 0.00 |
May | 0.846444E+09 | 7742.39 | 03-MAY-05:03 | 3.50 |
June | 0.353182E+09 | 7751.07 | 01-JUN-05:03 | 6.50 |
July | 0.286298E+09 | 7007.18 | 06-JUL-05:03 | 9.50 |
August | 0.476421E+09 | 6733.87 | 14-AUG-05:03 | 11.17 |
September | 0.851333E+09 | 7420.56 | 20-SEP-05:03 | 6.00 |
October | 0.221051E+10 | 11697.32 | 23-OCT-05:23 | 3.50 |
November | 0.353344E+10 | 15262.83 | 27-NOV-06:17 | 4.00 |
December | 0.588042E+10 | 16219.33 | 26-DEC-06:20 | 1.93 |
Annual Sum or Average | 0.273429E+11 | |||
Minimum of Months | 0.286298E+09 | 6733.87 | -4.0 | |
Maximum of Months | 0.588042E+10 | 16896.43 | 11.17 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149231E+10 | 8580.02 | 02-JAN-07:12 | 1.67 |
February | 0.965356E+09 | 3661.90 | 13-FEB-07:03 | -0.7 |
March | 0.710709E+09 | 3166.20 | 06-MAR-07:03 | 4.33 |
April | 0.200482E+09 | 3617.49 | 30-APR-13:32 | 22.67 |
May | 92853129.77 | 4486.64 | 07-MAY-15:17 | 14.00 |
June | 15634577.72 | 3762.24 | 11-JUN-11:57 | 17.00 |
July | 28349344.37 | 4517.55 | 09-JUL-12:03 | 19.00 |
August | 19331566.22 | 3731.83 | 27-AUG-11:40 | 17.00 |
September | 55587658.40 | 5436.49 | 17-SEP-11:02 | 15.17 |
October | 0.431997E+09 | 5388.11 | 01-OCT-10:42 | 13.83 |
November | 0.893396E+09 | 5105.67 | 27-NOV-07:13 | 4.00 |
December | 0.151760E+10 | 7421.61 | 26-DEC-07:12 | 1.67 |
Annual Sum or Average | 0.642360E+10 | |||
Minimum of Months | 15634577.72 | 3166.20 | -0.7 | |
Maximum of Months | 0.151760E+10 | 8580.02 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.719870E+09 | 5342.91 | 02-JAN-08:08 | 1.00 |
February | 0.300364E+09 | 2279.48 | 27-FEB-08:09 | 6.00 |
March | 0.185358E+09 | 2314.50 | 06-MAR-08:09 | 6.17 |
April | 8538692.81 | 4172.20 | 20-APR-05:03 | 1.17 |
May | 3040198.07 | 3599.22 | 21-MAY-15:28 | 18.50 |
June | 6171949.29 | 3357.60 | 25-JUN-14:52 | 24.00 |
July | 15397168.14 | 3444.99 | 09-JUL-15:13 | 21.00 |
August | 18777696.61 | 3117.02 | 27-AUG-16:20 | 18.67 |
September | 19536122.91 | 3398.99 | 17-SEP-12:15 | 16.00 |
October | 41510652.90 | 3251.21 | 01-OCT-11:00 | 14.00 |
November | 0.240825E+09 | 2548.17 | 27-NOV-08:09 | 4.00 |
December | 0.710136E+09 | 3487.55 | 26-DEC-08:19 | 1.33 |
Annual Sum or Average | 0.226953E+10 | |||
Minimum of Months | 3040198.07 | 2279.48 | 1.00 | |
Maximum of Months | 0.719870E+09 | 5342.91 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127981E+09 | 14192.60 | 02-JAN-06:01 | 1.17 |
February | 13358345.65 | 10820.28 | 21-FEB-07:02 | 4.00 |
March | 5654540.49 | 10700.28 | 06-MAR-07:02 | 4.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 10515242.64 | 10822.62 | 27-NOV-07:02 | 4.00 |
December | 58569151.60 | 11812.78 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.216078E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 0.127981E+09 | 14192.60 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105401E+10 | 26333.10 | 02-JAN-05:01 | 1.00 |
February | 0.511174E+09 | 22483.55 | 13-FEB-06:01 | -1.0 |
March | 0.339304E+09 | 22197.00 | 06-MAR-06:11 | 4.00 |
April | 25434056.12 | 18819.57 | 03-APR-06:02 | 3.17 |
May | 3813917.06 | 12520.77 | 15-MAY-06:03 | 7.92 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.115337E+09 | 20581.28 | 23-OCT-05:11 | 3.33 |
November | 0.456741E+09 | 23073.97 | 27-NOV-06:11 | 4.00 |
December | 0.106885E+10 | 24805.94 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.357466E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.106885E+10 | 26333.10 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199269E+10 | 9796.69 | 09-JAN-05:01 | -2.1 |
February | 0.125947E+10 | 9769.51 | 13-FEB-05:01 | -1.0 |
March | 0.819861E+09 | 9149.36 | 06-MAR-06:11 | 4.00 |
April | 0.161296E+09 | 7882.92 | 01-APR-05:12 | 2.33 |
May | 47255312.05 | 7561.98 | 05-MAY-05:12 | 6.00 |
June | 2110520.48 | 5055.44 | 07-JUN-06:03 | 8.33 |
July | 1057100.22 | 4220.60 | 31-JUL-06:03 | 10.50 |
August | 2330186.05 | 4351.71 | 28-AUG-06:03 | 10.67 |
September | 29120173.33 | 6844.23 | 21-SEP-06:03 | 5.33 |
October | 0.389537E+09 | 8780.33 | 23-OCT-05:11 | 3.33 |
November | 0.106058E+10 | 9797.18 | 20-NOV-05:01 | 0.67 |
December | 0.224908E+10 | 9583.60 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.801439E+10 | |||
Minimum of Months | 1057100.22 | 4220.60 | -2.1 | |
Maximum of Months | 0.224908E+10 | 9797.18 | 10.67 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115894E+10 | 7664.85 | 09-JAN-05:01 | -2.1 |
February | 0.723151E+09 | 7596.91 | 13-FEB-05:01 | -1.0 |
March | 0.496569E+09 | 7115.48 | 06-MAR-06:11 | 4.00 |
April | 60375388.34 | 5974.14 | 01-APR-05:12 | 2.33 |
May | 20967678.32 | 5576.15 | 05-MAY-05:12 | 6.00 |
June | 1777024.54 | 2376.97 | 07-JUN-06:03 | 8.33 |
July | 299618.30 | 1321.61 | 08-JUL-06:03 | 12.17 |
August | 1053709.03 | 1918.29 | 30-AUG-06:03 | 9.50 |
September | 14357392.01 | 4898.37 | 20-SEP-06:03 | 6.17 |
October | 0.234150E+09 | 6765.15 | 23-OCT-05:11 | 3.33 |
November | 0.624075E+09 | 7659.68 | 20-NOV-05:01 | 0.67 |
December | 0.138453E+10 | 7450.36 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.472024E+10 | |||
Minimum of Months | 299618.30 | 1321.61 | -2.1 | |
Maximum of Months | 0.138453E+10 | 7664.85 | 12.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142061E+10 | 11801.01 | 09-JAN-05:01 | -2.1 |
February | 0.894637E+09 | 11464.56 | 13-FEB-05:01 | -1.0 |
March | 0.711076E+09 | 10936.85 | 06-MAR-06:11 | 4.00 |
April | 0.148180E+09 | 9060.05 | 01-APR-05:12 | 2.33 |
May | 76419782.27 | 8909.66 | 05-MAY-05:12 | 6.00 |
June | 13890801.09 | 6088.42 | 08-JUN-06:03 | 7.50 |
July | 5882600.17 | 5311.38 | 31-JUL-06:03 | 10.50 |
August | 6258632.93 | 5139.00 | 24-AUG-06:03 | 8.83 |
September | 27911530.10 | 7614.77 | 20-SEP-06:03 | 6.17 |
October | 0.311157E+09 | 10192.10 | 23-OCT-05:11 | 3.33 |
November | 0.791024E+09 | 11604.50 | 20-NOV-05:01 | 0.67 |
December | 0.185134E+10 | 11520.43 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.625838E+10 | |||
Minimum of Months | 5882600.17 | 5139.00 | -2.1 | |
Maximum of Months | 0.185134E+10 | 11801.01 | 10.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123312E+10 | 8177.93 | 09-JAN-05:01 | -2.1 |
February | 0.757138E+09 | 8189.51 | 13-FEB-05:01 | -1.0 |
March | 0.534576E+09 | 7579.58 | 06-MAR-06:11 | 4.00 |
April | 0.112035E+09 | 6238.03 | 01-APR-05:12 | 2.33 |
May | 52759841.19 | 6113.30 | 05-MAY-05:12 | 6.00 |
June | 9246676.62 | 3772.99 | 08-JUN-06:03 | 7.50 |
July | 4229521.96 | 3415.64 | 01-JUL-06:03 | 11.33 |
August | 5416883.12 | 3283.61 | 24-AUG-06:03 | 8.83 |
September | 23537302.34 | 5102.42 | 20-SEP-06:03 | 6.17 |
October | 0.264969E+09 | 7142.68 | 23-OCT-05:11 | 3.33 |
November | 0.688638E+09 | 8164.38 | 20-NOV-05:01 | 0.67 |
December | 0.150424E+10 | 7947.52 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.518991E+10 | |||
Minimum of Months | 4229521.96 | 3283.61 | -2.1 | |
Maximum of Months | 0.150424E+10 | 8189.51 | 11.33 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116747E+10 | 7660.63 | 02-JAN-05:01 | 1.00 |
February | 0.622116E+09 | 6467.26 | 13-FEB-06:01 | -1.0 |
March | 0.379883E+09 | 6325.29 | 06-MAR-06:11 | 4.00 |
April | 40067698.39 | 5655.22 | 01-APR-05:12 | 2.33 |
May | 9436928.57 | 5311.38 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 321941.56 | 1468.37 | 21-SEP-06:03 | 5.33 |
October | 40565821.07 | 5763.38 | 23-OCT-05:11 | 3.33 |
November | 0.236635E+09 | 6242.69 | 27-NOV-06:11 | 4.00 |
December | 0.906380E+09 | 6734.86 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.340287E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.116747E+10 | 7660.63 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.645405E+09 | 6012.95 | 02-JAN-05:01 | 1.00 |
February | 0.327197E+09 | 4959.16 | 13-FEB-06:01 | -1.0 |
March | 0.230684E+09 | 5006.82 | 06-MAR-06:11 | 4.00 |
April | 9530759.45 | 4302.89 | 01-APR-05:12 | 2.33 |
May | 2570654.56 | 3937.39 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 26654340.95 | 4371.33 | 23-OCT-05:11 | 3.33 |
November | 0.140443E+09 | 4862.16 | 27-NOV-06:11 | 4.00 |
December | 0.571578E+09 | 5320.95 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.195406E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.645405E+09 | 6012.95 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291011E+10 | 10349.82 | 10-JAN-08:00 | -6.0 |
February | 0.205709E+10 | 10006.43 | 17-FEB-07:10 | -3.8 |
March | 0.244150E+10 | 9176.21 | 08-MAR-07:10 | -0.5 |
April | 0.875068E+09 | 7984.14 | 03-APR-06:10 | 3.17 |
May | 0.907631E+09 | 7377.53 | 05-MAY-06:10 | 6.17 |
June | 0.384298E+09 | 6796.98 | 08-JUN-06:10 | 7.50 |
July | 0.162306E+09 | 6261.07 | 05-JUL-06:03 | 9.50 |
August | 0.140545E+09 | 6102.08 | 24-AUG-06:10 | 8.83 |
September | 0.324727E+09 | 6776.67 | 21-SEP-06:10 | 5.33 |
October | 0.101990E+10 | 7669.28 | 23-OCT-06:10 | 4.00 |
November | 0.183605E+10 | 9312.13 | 29-NOV-07:10 | -1.0 |
December | 0.288985E+10 | 9524.16 | 27-DEC-07:10 | -1.8 |
Annual Sum or Average | 0.159491E+11 | |||
Minimum of Months | 0.140545E+09 | 6102.08 | -6.0 | |
Maximum of Months | 0.291011E+10 | 10349.82 | 9.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.681609E+09 | 6470.68 | 02-JAN-05:01 | 1.00 |
February | 0.307180E+09 | 5300.92 | 13-FEB-06:01 | -1.0 |
March | 0.239990E+09 | 5271.80 | 06-MAR-06:11 | 4.00 |
April | 25037065.00 | 4219.29 | 01-APR-05:12 | 2.33 |
May | 8771914.79 | 4067.96 | 06-MAY-06:03 | 3.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 198836.28 | 994.18 | 01-JUL-06:03 | 11.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 1293450.34 | 2304.34 | 07-SEP-06:03 | 8.33 |
October | 30275360.99 | 4520.16 | 23-OCT-05:11 | 3.33 |
November | 0.159006E+09 | 5190.66 | 27-NOV-06:11 | 4.00 |
December | 0.633417E+09 | 5650.99 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.208678E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.681609E+09 | 6470.68 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.713509E+09 | 7315.14 | 02-JAN-05:01 | 1.00 |
February | 0.311602E+09 | 6229.26 | 13-FEB-06:01 | -1.0 |
March | 0.160406E+09 | 6009.70 | 06-MAR-06:11 | 4.00 |
April | 12904082.03 | 5206.82 | 03-APR-06:02 | 3.17 |
May | 1019390.82 | 2627.78 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 43980330.12 | 5640.58 | 23-OCT-05:11 | 3.33 |
November | 0.251013E+09 | 6261.95 | 20-NOV-06:01 | -0.7 |
December | 0.796054E+09 | 6843.62 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.229049E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.796054E+09 | 7315.14 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434196E+09 | 6758.61 | 02-JAN-05:01 | 1.00 |
February | 0.192518E+09 | 5429.15 | 13-FEB-06:01 | -1.0 |
March | 0.106601E+09 | 5327.48 | 06-MAR-06:11 | 4.00 |
April | 7293635.35 | 4118.30 | 03-APR-06:02 | 3.17 |
May | 2571730.53 | 4019.46 | 17-MAY-06:03 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 1672468.98 | 3170.76 | 20-SEP-06:03 | 6.17 |
October | 37579065.54 | 4861.05 | 23-OCT-05:11 | 3.33 |
November | 0.161416E+09 | 5590.47 | 27-NOV-06:11 | 4.00 |
December | 0.516075E+09 | 6261.87 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.145992E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.516075E+09 | 6758.61 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479777E+09 | 9476.85 | 02-JAN-05:01 | 1.00 |
February | 0.205456E+09 | 7730.45 | 27-FEB-06:11 | 6.00 |
March | 0.142110E+09 | 7742.81 | 06-MAR-06:11 | 4.00 |
April | 20085905.21 | 6209.79 | 03-APR-06:02 | 3.17 |
May | 11253480.37 | 6029.72 | 06-MAY-06:03 | 3.50 |
June | 267068.63 | 1335.34 | 08-JUN-06:03 | 7.50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 1676756.07 | 3703.17 | 20-SEP-06:03 | 6.17 |
October | 44461730.16 | 6890.86 | 23-OCT-05:11 | 3.33 |
November | 0.183661E+09 | 8111.84 | 27-NOV-06:11 | 4.00 |
December | 0.635323E+09 | 8907.87 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.172407E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.635323E+09 | 9476.85 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456918E+09 | 6850.24 | 02-JAN-05:01 | 1.00 |
February | 0.198882E+09 | 5535.83 | 13-FEB-06:01 | -1.0 |
March | 0.120516E+09 | 5367.67 | 06-MAR-06:11 | 4.00 |
April | 15938958.74 | 4153.81 | 03-APR-06:02 | 3.17 |
May | 8471901.97 | 4018.92 | 05-MAY-06:03 | 6.17 |
June | 182766.20 | 913.83 | 08-JUN-06:03 | 7.50 |
July | 50598.90 | 252.99 | 01-JUL-06:03 | 11.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 3675588.93 | 3843.83 | 20-SEP-06:03 | 6.17 |
October | 39657614.77 | 4843.83 | 23-OCT-05:11 | 3.33 |
November | 0.182139E+09 | 5679.91 | 27-NOV-06:11 | 4.00 |
December | 0.563767E+09 | 6344.54 | 26-DEC-06:11 | 1.93 |
Annual Sum or Average | 0.159020E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.563767E+09 | 6850.24 | 11.43 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222640E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316468E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189933E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35124.08 | 0.244549E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602095E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 315916.66 | 0.475044E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1652259.86 | 0.448284E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 211864.90 | 0.318744E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324870E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335745E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405534E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554322E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2215165.51 | 0.443823E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189933E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1652259.86 | 0.602095E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149255E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212720E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127158E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24446.30 | 0.169119E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409718E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 214682.32 | 0.319176E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146920.08 | 0.305787E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 143831.64 | 0.217716E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227201E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226687E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271353E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369380E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1529880.34 | 0.300527E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127158E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146920.08 | 0.409718E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232916E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332425E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194057E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1401.63 | 0.259147E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616434E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 316353.03 | 0.476440E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1800248.12 | 0.455936E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206519.83 | 0.331862E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351198E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357279E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421716E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566396E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2324522.61 | 0.459581E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194057E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1800248.12 | 0.616434E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149112E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213564E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126474E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.46 | 0.166423E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412830E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 215730.29 | 0.323165E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1068405.69 | 0.309178E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 145113.58 | 0.218402E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221740E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227275E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270919E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368457E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1429349.03 | 0.300754E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126474E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1068405.69 | 0.412830E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125599E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180354E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104804E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121021.99 | 0.131415E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.08 | 0.326181E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 185528.55 | 0.256679E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 961763.79 | 0.246132E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 136272.30 | 0.176078E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186118E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196461E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241173E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325335E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1404676.70 | 0.249633E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104804E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 961763.79 | 0.326181E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84661668.98 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121572E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70222537.66 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20450.88 | 93293589.82 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | 0.228690E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119311.67 | 0.176862E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 620243.77 | 0.173172E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76194.66 | 0.125208E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133578E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133858E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161597E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216785E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 836202.52 | 0.171950E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70222537.66 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 620243.77 | 0.228690E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431791E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377503E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413300E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.32 | 0.301148E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.14 | 0.322599E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12706142.13 | 0.227867E+10 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21768818.17 | 0.175109E+10 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9492361.24 | 0.177933E+10 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213496E+10 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313375E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382992E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421132E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43967570.99 | 0.375825E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175109E+10 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21768818.17 | 0.431791E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84365500.40 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122226E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69754686.42 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91536049.32 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.229608E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113629.92 | 0.180118E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 556977.51 | 0.174593E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74472.95 | 0.125019E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129268E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133330E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161089E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215946E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 745081.92 | 0.171685E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69754686.42 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 556977.51 | 0.229608E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198621E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287118E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169877E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14960.78 | 0.219328E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537700E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 263901.84 | 0.420547E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1335519.28 | 0.398241E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 176320.78 | 0.287470E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299107E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309931E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372874E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502328E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1790702.69 | 0.400314E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169877E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1335519.28 | 0.537700E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133634E+09 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193254E+09 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114045E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43320.11 | 0.150145E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362031E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 183277.94 | 0.279652E+09 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 954151.79 | 0.267483E+09 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135068.21 | 0.192186E+09 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204422E+09 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208494E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249433E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334670E+09 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1315818.05 | 0.268945E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114045E+09 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 954151.79 | 0.362031E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209420E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300627E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172525E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 976.45 | 0.229073E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544047E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 269227.89 | 0.418051E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1495082.88 | 0.401075E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173688.46 | 0.294580E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315529E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325025E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385992E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514725E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1938975.68 | 0.411067E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172525E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1495082.88 | 0.544047E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132950E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193002E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111987E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147243E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364022E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 182926.10 | 0.283410E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 865133.92 | 0.271705E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116655.97 | 0.194134E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200176E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207048E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247796E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333411E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1164715.99 | 0.268688E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111987E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 865133.92 | 0.364022E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285067E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415807E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239404E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309187E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758035E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192722.48 | 0.584780E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1399879.25 | 0.563535E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139086.01 | 0.414767E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437435E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455593E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551512E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737355E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1731687.74 | 0.575248E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239404E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1399879.25 | 0.758035E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343798E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502353E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292500E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383332E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944601E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253538.72 | 0.734164E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1874033.53 | 0.700598E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190176.43 | 0.514627E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533498E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547078E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657990E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880304E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2317748.68 | 0.703485E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292500E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1874033.53 | 0.944601E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326412E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467675E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286918E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391910E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935031E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27827.41 | 0.739382E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814239.39 | 0.706082E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58630.66 | 0.498217E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502736E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498822E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587554E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801562E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 900697.46 | 0.674230E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286918E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814239.39 | 0.935031E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 672.92 | 10-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 778.04 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 776.60 | 27-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | 30-APR-15:00 | 708.08 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1141.94 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 13-JUN-15:30 | 859.85 | 18-JUN-16:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.79 | 22-JUL-19:10 | 785.27 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 14-AUG-16:50 | 543.87 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 672.37 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 856.18 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 797.98 | 16-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1335.20 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.87 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 96.79 | 1335.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 448.59 | 10-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 518.06 | 08-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 517.40 | 27-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.88 | 30-APR-19:00 | 470.14 | 23-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 752.98 | 04-MAY-23:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 13-JUN-15:30 | 633.02 | 18-JUN-11:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.51 | 22-JUL-19:10 | 524.34 | 30-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 14-AUG-18:00 | 348.10 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 449.27 | 06-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 565.43 | 20-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 531.60 | 16-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 878.42 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.10 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 82.51 | 878.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 688.38 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 779.56 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 776.49 | 27-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | 30-APR-19:00 | 805.93 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1139.98 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 13-JUN-15:30 | 976.27 | 18-JUN-16:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.51 | 22-JUL-19:10 | 833.12 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 14-AUG-16:50 | 544.84 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 680.17 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 869.13 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 799.63 | 16-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1339.62 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.84 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 120.51 | 1339.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 448.59 | 10-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 518.89 | 08-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 517.21 | 27-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 30-APR-12:20 | 492.89 | 15-APR-17:25 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 754.63 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 | 13-JUN-15:30 | 714.88 | 18-JUN-16:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 | 22-JUL-19:10 | 683.81 | 30-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 20-AUG-13:00 | 369.59 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 445.22 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 572.15 | 20-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 531.75 | 16-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 873.87 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.59 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 | 873.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 421.07 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 415.22 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 413.95 | 27-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 30-APR-19:00 | 408.74 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 22-MAY-15:00 | 645.36 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 13-JUN-15:30 | 448.60 | 05-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.85 | 22-JUL-19:10 | 422.56 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.55 | 20-AUG-16:00 | 301.90 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 406.83 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 496.92 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 491.21 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 760.74 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.90 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 57.85 | 760.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 282.00 | 08-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 276.58 | 08-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 275.88 | 27-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 | 30-APR-19:00 | 279.04 | 23-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 427.46 | 04-MAY-23:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 13-JUN-15:30 | 335.67 | 18-JUN-09:53 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.55 | 22-JUL-19:10 | 292.90 | 30-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 14-AUG-18:00 | 203.27 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 286.25 | 06-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 326.74 | 20-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 323.66 | 25-NOV-05:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 502.23 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.27 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 42.55 | 502.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 20907.13 | 10-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 20671.46 | 17-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 17513.21 | 08-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 | 30-APR-19:00 | 14368.20 | 20-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 22-MAY-15:00 | 12779.67 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2398.95 | 13-JUN-17:00 | 10635.58 | 08-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.46 | 21-JUL-17:00 | 9379.06 | 05-JUL-06:10 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2401.38 | 14-AUG-17:00 | 10097.12 | 24-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 12830.66 | 21-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 14667.03 | 04-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 18268.83 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 19769.97 | 29-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9379.06 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3978.46 | 20907.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 280.33 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 277.08 | 08-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 275.74 | 27-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 274.38 | 23-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 429.79 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 | 13-JUN-15:30 | 337.71 | 18-JUN-16:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.43 | 22-JUL-19:10 | 367.91 | 30-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 | 14-AUG-16:50 | 219.25 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 275.22 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 331.00 | 20-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 323.35 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 500.37 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.25 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28.43 | 500.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 655.12 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 653.39 | 08-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 651.21 | 27-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 30-APR-17:42 | 662.25 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1031.67 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 13-JUN-15:30 | 731.79 | 05-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.67 | 22-JUL-19:10 | 669.42 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 14-AUG-16:50 | 492.98 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 638.58 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 776.88 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 745.55 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1181.32 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.98 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 76.67 | 1181.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 434.81 | 08-JAN-08:00 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 434.90 | 08-FEB-22:03 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 433.65 | 27-MAR-21:03 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.36 | 30-APR-19:00 | 439.47 | 23-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 677.03 | 04-MAY-23:00 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 13-JUN-15:30 | 548.50 | 18-JUN-10:25 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.45 | 22-JUL-19:10 | 439.81 | 30-JUL-19:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 | 14-AUG-18:00 | 308.25 | 22-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 423.69 | 06-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 511.79 | 20-OCT-22:00 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 492.29 | 25-NOV-05:00 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 771.20 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.25 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 72.45 | 771.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 669.44 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 656.50 | 05-FEB-14:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 650.78 | 27-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | 30-APR-19:00 | 709.03 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1022.63 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 13-JUN-15:30 | 790.76 | 18-JUN-16:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 | 22-JUL-19:10 | 704.21 | 30-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 14-AUG-16:50 | 485.22 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 641.81 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 783.85 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 745.52 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1180.57 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.22 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 | 1180.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 434.86 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 435.55 | 08-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 433.42 | 27-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 436.77 | 23-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 676.92 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 13-JUN-15:30 | 584.24 | 18-JUN-16:10 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 22-JUL-19:10 | 579.05 | 30-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 14-AUG-16:50 | 328.67 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 420.91 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 515.51 | 20-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 490.53 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 769.90 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.67 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 769.90 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 990.76 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 914.27 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 893.14 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 979.83 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1520.85 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 13-JUN-16:00 | 1025.66 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.75 | 22-JUL-18:52 | 947.07 | 30-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 14-AUG-17:00 | 708.45 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 951.34 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1141.61 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1155.17 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1775.59 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.45 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.75 | 1775.59 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1182.95 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1130.06 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1094.60 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1182.86 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1885.02 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 13-JUN-16:00 | 1290.66 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.64 | 22-JUL-18:52 | 1162.04 | 11-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 14-AUG-17:00 | 889.65 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1156.52 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1381.91 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1356.32 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2133.59 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.64 | 2133.59 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 975.01 | 09-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1117.03 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1133.89 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1176.42 | 16-APR-12:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1718.34 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 | 13-JUN-17:00 | 1717.69 | 18-JUN-16:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.51 | 22-JUL-18:52 | 1343.34 | 30-JUL-17:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 | 14-AUG-18:00 | 806.94 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 917.47 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1212.24 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1136.05 | 16-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2175.29 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806.94 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.51 | 2175.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16500.19 | 20-JAN-16:40 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16755.64 | 10-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17039.61 | 31-MAR-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36181.49 | 20-APR-05:03 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28011.65 | 24-MAY-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35861.60 | 27-JUN-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39642.53 | 24-JUL-06:03 | 5082.11 | 13014.15 | 41900.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36212.65 | 07-AUG-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33155.31 | 14-SEP-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22024.23 | 03-OCT-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18044.11 | 10-NOV-16:20 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15078.64 | 22-DEC-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15078.64 | 1905.79 | 3253.54 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39642.53 | 6035.01 | 13014.15 | 41900.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1277.50 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.87 |
February | 1967.23 | 22-FEB-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.68 |
March | 3934.64 | 25-MAR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.34 |
April | 11216.79 | 28-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.72 |
May | 12336.66 | 22-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 |
June | 13896.98 | 13-JUN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 |
July | 13968.27 | 21-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
August | 11862.55 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.98 |
September | 9863.33 | 13-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 |
October | 4685.84 | 07-OCT-13:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 |
November | 1508.62 | 10-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.50 |
December | 379.42 | 06-DEC-13:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 379.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13968.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 161.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3026.92 | 07-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.43 |
February | 3225.04 | 11-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.03 |
March | 3011.04 | 04-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.83 |
April | 3453.29 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3332.42 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.46 |
June | 3769.63 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 0.00 |
July | 3496.75 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3180.09 | 18-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.19 |
September | 2962.36 | 13-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 |
October | 3840.68 | 04-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.87 |
November | 3155.18 | 17-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.93 |
December | 3002.70 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2962.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3840.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 203.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4215.07 | 20-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4239.62 | 09-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.53 |
March | 4458.21 | 25-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4449.23 | 13-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 |
May | 4074.94 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.93 |
June | 4077.01 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 0.00 |
July | 3994.47 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3815.48 | 30-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 |
September | 3960.03 | 13-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.56 |
October | 4325.89 | 12-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 |
November | 3773.85 | 17-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.71 |
December | 3771.79 | 08-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3771.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4458.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 168.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8582.78 | 20-JAN-16:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8484.51 | 10-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9120.63 | 31-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16168.48 | 28-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16817.37 | 23-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18060.99 | 13-JUN-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18162.60 | 24-JUL-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17714.27 | 18-AUG-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17321.85 | 13-SEP-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13976.05 | 05-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9719.33 | 10-NOV-16:30 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7890.00 | 21-DEC-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7890.00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18162.60 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8231.48 | 19-JAN-16:30 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8257.99 | 09-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8571.98 | 31-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18224.59 | 28-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19326.76 | 23-MAY-15:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21285.45 | 13-JUN-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20841.83 | 21-JUL-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19708.26 | 18-AUG-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18478.51 | 13-SEP-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12385.42 | 05-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8564.77 | 10-NOV-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7692.02 | 21-DEC-15:20 | 18105.02 | 29281.83 | 20424.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7692.02 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21285.45 | 18105.02 | 29281.83 | 20424.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2098.85 | 19-JAN-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2057.16 | 09-FEB-15:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 |
March | 2361.14 | 30-MAR-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.26 |
April | 4521.17 | 28-APR-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
May | 4974.63 | 22-MAY-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
June | 6384.45 | 13-JUN-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 0.00 |
July | 6146.62 | 21-JUL-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5372.68 | 14-AUG-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 0.00 |
September | 4727.25 | 13-SEP-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
October | 2756.75 | 06-OCT-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 |
November | 2247.34 | 10-NOV-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 |
December | 1786.06 | 23-DEC-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1786.06 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6384.45 | 1272.23 | 2057.62 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 139.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1988.87 | 20-JAN-10:30 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2118.22 | 24-FEB-10:35 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.62 |
March | 2105.49 | 30-MAR-10:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.64 |
April | 6149.91 | 28-APR-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 |
May | 7156.94 | 23-MAY-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 |
June | 8057.37 | 25-JUN-09:32 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.97 |
July | 15466.65 | 23-JUL-09:22 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.58 |
August | 6989.55 | 17-AUG-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 |
September | 6128.55 | 12-SEP-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 |
October | 2947.95 | 04-OCT-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1967.45 | 03-NOV-09:50 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.02 |
December | 1673.22 | 06-DEC-10:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1673.22 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15466.65 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5992.71 | 20-JAN-12:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7479.95 | 17-FEB-14:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.71 |
March | 4135.40 | 28-MAR-12:20 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.90 |
April | 13734.65 | 30-APR-13:32 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.63 |
May | 10194.89 | 22-MAY-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 |
June | 10380.09 | 13-JUN-13:20 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 0.00 |
July | 15951.96 | 23-JUL-13:22 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.24 |
August | 14731.42 | 20-AUG-13:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.26 |
September | 12490.02 | 12-SEP-12:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 |
October | 10725.04 | 03-OCT-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.30 |
November | 6423.35 | 03-NOV-12:40 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.42 |
December | 4671.72 | 18-DEC-13:30 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4135.40 | 267.84 | 457.25 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15951.96 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 | 187.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2616.36 | 19-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2905.87 | 27-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2963.99 | 23-MAR-16:50 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.95 |
April | 9592.76 | 30-APR-16:12 | 169.55 | 289.46 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 |
May | 8843.09 | 22-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 |
June | 11584.22 | 25-JUN-17:22 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.13 |
July | 17341.71 | 23-JUL-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.90 |
August | 17278.85 | 20-AUG-16:12 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.22 |
September | 8029.00 | 12-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 |
October | 4987.20 | 03-OCT-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.48 |
November | 2664.20 | 10-NOV-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.61 |
December | 2160.09 | 21-DEC-14:40 | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2160.09 | 0.00 | 289.46 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17341.71 | 827.17 | 1302.56 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1673.54 | 19-JAN-15:20 | 3816.70 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1618.05 | 10-FEB-15:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 |
March | 1824.80 | 30-MAR-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 |
April | 2353.27 | 28-APR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 |
May | 2561.47 | 23-MAY-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.88 |
June | 4095.62 | 13-JUN-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 0.00 |
July | 4165.90 | 21-JUL-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3476.46 | 17-AUG-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 |
September | 3263.08 | 13-SEP-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
October | 2190.54 | 06-OCT-15:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.81 |
November | 1883.19 | 10-NOV-15:10 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 |
December | 1588.82 | 22-DEC-13:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1588.82 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4165.90 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 39.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1692.24 | 20-JAN-10:13 | 2481.66 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1736.76 | 24-FEB-10:30 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 |
March | 1675.23 | 30-MAR-10:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 |
April | 5345.45 | 30-APR-08:10 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 |
May | 5383.15 | 23-MAY-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 |
June | 5910.86 | 13-JUN-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 |
July | 5627.13 | 10-JUL-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
August | 5493.86 | 18-AUG-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 |
September | 5053.07 | 12-SEP-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 |
October | 2707.35 | 04-OCT-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1744.37 | 03-NOV-09:35 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 |
December | 1535.91 | 08-DEC-10:30 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1535.91 | 254.35 | 434.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5910.86 | 2481.66 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3208.00 | 21-JAN-11:40 | 803.52 | 1371.75 | 1594.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3264.35 | 04-FEB-14:00 | 133.92 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.44 |
March | 2684.95 | 25-MAR-11:50 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7845.94 | 28-APR-12:10 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.10 |
May | 6731.06 | 22-MAY-13:50 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.89 |
June | 7454.91 | 13-JUN-13:50 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 100.56 | 0.00 |
July | 8617.42 | 21-JUL-16:10 | 401.76 | 1143.12 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3316.61 | 0.00 |
August | 8725.15 | 20-AUG-14:14 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.40 |
September | 9990.68 | 11-SEP-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.23 |
October | 9008.19 | 02-OCT-12:08 | 5088.93 | 8230.49 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1139.35 |
November | 3191.46 | 03-NOV-14:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.25 |
December | 2997.37 | 18-DEC-14:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1751.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2684.95 | 133.92 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9990.68 | 5088.93 | 8230.49 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 3316.61 | 1751.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2077.70 | 19-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2246.19 | 27-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2270.27 | 23-MAR-17:10 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 |
April | 5329.00 | 28-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 |
May | 5953.61 | 22-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
June | 6914.15 | 13-JUN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 0.00 |
July | 8541.71 | 23-JUL-17:22 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.07 |
August | 7296.03 | 20-AUG-16:12 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 |
September | 5873.08 | 12-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 |
October | 4014.88 | 03-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 |
November | 2177.91 | 10-NOV-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 |
December | 1788.35 | 21-DEC-14:50 | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1788.35 | 0.00 | 361.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8541.71 | 827.17 | 1302.56 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 67.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1766.21 | 19-JAN-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1728.79 | 10-FEB-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.92 |
March | 1960.88 | 30-MAR-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.30 |
April | 4113.72 | 28-APR-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 |
May | 4331.97 | 22-MAY-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
June | 5672.60 | 13-JUN-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 0.00 |
July | 5483.71 | 21-JUL-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4896.14 | 14-AUG-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | 0.00 |
September | 4519.92 | 13-SEP-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 |
October | 2491.20 | 06-OCT-15:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.20 |
November | 1886.29 | 10-NOV-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.81 |
December | 1600.11 | 21-DEC-14:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1600.11 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5672.60 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 124.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3613.64 | 20-JAN-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3806.26 | 24-FEB-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 |
March | 3614.03 | 31-MAR-10:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.20 |
April | 7347.86 | 28-APR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 |
May | 7808.92 | 23-MAY-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 |
June | 8282.42 | 13-JUN-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 |
July | 9625.05 | 23-JUL-08:53 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.67 |
August | 11928.63 | 20-AUG-09:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.07 |
September | 7245.62 | 12-SEP-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 |
October | 5352.84 | 04-OCT-12:02 | 4027.14 | 6513.23 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.53 |
November | 3706.94 | 03-NOV-10:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.96 |
December | 2442.61 | 08-DEC-11:03 | 2416.29 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2442.61 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11928.63 | 4027.14 | 6513.23 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7398.65 | 20-JAN-12:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8359.83 | 17-FEB-13:25 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.97 |
March | 4615.38 | 28-MAR-12:05 | 5088.93 | 8230.49 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.22 |
April | 13665.53 | 30-APR-12:53 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.28 |
May | 9574.53 | 23-MAY-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 |
June | 9679.82 | 13-JUN-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
July | 9861.54 | 21-JUL-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 0.00 |
August | 11194.29 | 30-AUG-12:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
September | 19367.73 | 24-SEP-13:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.85 |
October | 11196.43 | 03-OCT-13:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 |
November | 7627.88 | 03-NOV-12:25 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.44 |
December | 5731.08 | 18-DEC-13:25 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4615.38 | 267.84 | 457.25 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19367.73 | 5088.93 | 8230.49 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 154.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2572.63 | 19-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2824.85 | 27-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3003.56 | 23-MAR-16:40 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 |
April | 8959.83 | 30-APR-16:12 | 169.55 | 289.46 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 |
May | 14640.97 | 21-MAY-16:52 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.76 |
June | 16280.68 | 25-JUN-16:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.58 |
July | 11896.66 | 22-JUL-17:05 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 0.00 |
August | 11242.09 | 13-AUG-17:32 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.56 |
September | 7893.62 | 12-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 |
October | 5184.23 | 03-OCT-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.60 |
November | 2623.51 | 10-NOV-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 |
December | 2186.21 | 21-DEC-14:40 | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2186.21 | 0.00 | 289.46 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16280.68 | 827.17 | 1302.56 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 157.56 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.151493E+12 | 121378.45 | 02-JAN-08:09 | 0.733845E+11 | 211549.49 | 02-JAN-07:19 |
February | 0.134999E+12 | 106019.95 | 17-FEB-11:50 | 0.488696E+11 | 179946.86 | 13-FEB-07:10 |
March | 0.153071E+12 | 105698.94 | 31-MAR-15:50 | 0.437758E+11 | 164611.41 | 06-MAR-07:10 |
April | 0.141916E+12 | 137877.36 | 28-APR-15:30 | 0.945748E+10 | 115159.25 | 03-APR-06:10 |
May | 0.148916E+12 | 150721.00 | 22-MAY-15:20 | 0.631953E+10 | 80915.56 | 17-MAY-06:10 |
June | 0.152701E+12 | 171046.57 | 13-JUN-15:00 | 0.165343E+10 | 44335.15 | 07-JUN-06:10 |
July | 0.155828E+12 | 169537.08 | 21-JUL-15:00 | 0.799344E+09 | 44279.55 | 03-JUL-06:10 |
August | 0.171440E+12 | 162046.27 | 14-AUG-15:50 | 0.832881E+09 | 37314.68 | 28-AUG-06:10 |
September | 0.152070E+12 | 153039.40 | 13-SEP-15:20 | 0.252753E+10 | 68654.60 | 21-SEP-06:10 |
October | 0.148651E+12 | 119068.26 | 06-OCT-15:30 | 0.201423E+11 | 132412.72 | 23-OCT-06:10 |
November | 0.146949E+12 | 120991.85 | 10-NOV-16:49 | 0.437130E+11 | 174393.89 | 20-NOV-07:10 |
December | 0.149403E+12 | 120237.04 | 22-DEC-16:00 | 0.757279E+11 | 192928.10 | 26-DEC-07:10 |
Annual Sum or Average | 0.180744E+13 | 0.327203E+12 | ||||
Minimum of Months | 0.134999E+12 | 105698.94 | 0.799344E+09 | 37314.68 | ||
Maximum of Months | 0.171440E+12 | 171046.57 | 0.757279E+11 | 211549.49 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.257355E+11 | 0.613996E+11 | 0.230900E+10 | 0.951561E+10 | 0.349788E+09 | 0.00 | 588860.87 | 0.00 | 0.00 | 0.00 | 0.493472E+10 | 0.00 |
February | 0.428574E+11 | 0.211775E+11 | 0.556056E+11 | 0.209511E+10 | 0.852123E+10 | 0.233768E+09 | 0.00 | 97060.67 | 0.00 | 0.00 | 0.00 | 0.450862E+10 | 0.00 |
March | 0.509265E+11 | 0.206101E+11 | 0.635880E+11 | 0.240664E+10 | 0.100427E+11 | 0.209752E+09 | 0.00 | 58331.46 | 0.00 | 0.00 | 0.00 | 0.528712E+10 | 0.00 |
April | 0.454877E+11 | 0.170790E+11 | 0.594055E+11 | 0.224272E+10 | 0.113390E+11 | 58426453.63 | 0.00 | 0.161819E+10 | 0.00 | 0.00 | 0.00 | 0.468514E+10 | 0.00 |
May | 0.490872E+11 | 0.151333E+11 | 0.624938E+11 | 0.235782E+10 | 0.125742E+11 | 47733760.15 | 0.00 | 0.233114E+10 | 0.00 | 0.00 | 0.00 | 0.489107E+10 | 0.00 |
June | 0.488499E+11 | 0.133047E+11 | 0.612808E+11 | 0.231841E+10 | 0.147136E+11 | 23592741.42 | 0.00 | 0.748003E+10 | 0.00 | 0.00 | 0.00 | 0.472997E+10 | 0.00 |
July | 0.457251E+11 | 0.143406E+11 | 0.606074E+11 | 0.228147E+10 | 0.155237E+11 | 17098981.57 | 0.00 | 0.129437E+11 | 0.00 | 0.00 | 0.00 | 0.438866E+10 | 0.00 |
August | 0.509265E+11 | 0.165295E+11 | 0.635880E+11 | 0.240664E+10 | 0.167375E+11 | 17214717.74 | 0.00 | 0.164408E+11 | 0.00 | 0.00 | 0.00 | 0.479442E+10 | 0.00 |
September | 0.454877E+11 | 0.187004E+11 | 0.593832E+11 | 0.224140E+10 | 0.137984E+11 | 25813225.96 | 0.00 | 0.807097E+10 | 0.00 | 0.00 | 0.00 | 0.436211E+10 | 0.00 |
October | 0.472479E+11 | 0.222675E+11 | 0.614108E+11 | 0.230966E+10 | 0.103345E+11 | 0.102697E+09 | 0.00 | 0.381166E+09 | 0.00 | 0.00 | 0.00 | 0.459697E+10 | 0.00 |
November | 0.466941E+11 | 0.241231E+11 | 0.599069E+11 | 0.224962E+10 | 0.912254E+10 | 0.207454E+09 | 0.00 | 7127524.06 | 0.00 | 0.00 | 0.00 | 0.463849E+10 | 0.00 |
December | 0.457251E+11 | 0.264291E+11 | 0.605962E+11 | 0.228081E+10 | 0.929176E+10 | 0.360678E+09 | 0.00 | 240519.13 | 0.00 | 0.00 | 0.00 | 0.471942E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.235430E+12 | 0.729266E+12 | 0.274993E+11 | 0.141515E+12 | 0.165402E+10 | 0.00 | 0.492741E+11 | 0.00 | 0.00 | 0.00 | 0.565367E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.133047E+11 | 0.556056E+11 | 0.209511E+10 | 0.852123E+10 | 17098981.57 | 0.00 | 58331.46 | 0.00 | 0.00 | 0.00 | 0.436211E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.264291E+11 | 0.635880E+11 | 0.240664E+10 | 0.167375E+11 | 0.360678E+09 | 0.00 | 0.164408E+11 | 0.00 | 0.00 | 0.00 | 0.528712E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.733845E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.488696E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.437758E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.945748E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.631953E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.165343E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.799344E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.832881E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.252753E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.201423E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.437130E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.757279E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.327203E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.799344E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.757279E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 02-JAN-12:09 | 15290.55 | 02-JAN-07:10 | 802.59 | 02-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 01-FEB-08:09 | 10414.92 | 13-FEB-07:10 | 731.75 | 13-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 06-MAR-08:09 | 9830.33 | 06-MAR-07:10 | 711.91 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 04-APR-07:10 | 20442.39 | 28-APR-15:20 | 509.82 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 02-MAY-07:10 | 19734.07 | 23-MAY-15:20 | 359.58 | 17-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 02-JUN-11:09 | 25114.50 | 13-JUN-15:00 | 258.13 | 07-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 03-JUL-11:09 | 24886.88 | 21-JUL-15:00 | 231.39 | 31-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:10 | 22797.89 | 14-AUG-15:30 | 217.84 | 24-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 05-SEP-16:10 | 22165.50 | 13-SEP-15:20 | 322.13 | 20-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 04-OCT-07:10 | 14402.35 | 03-OCT-14:00 | 613.70 | 23-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 01-NOV-07:10 | 11172.70 | 27-NOV-07:10 | 727.56 | 27-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 01-DEC-17:10 | 12836.65 | 26-DEC-07:10 | 768.66 | 26-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 9830.33 | 217.84 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 25114.50 | 802.59 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 230.80 | 11-JAN-05:30 | 0.00 | 0.00 | 0.00 | 6664.77 | 31-JAN-12:00 | 0.00 |
February | 49.57 | 18-FEB-05:10 | 0.00 | 0.00 | 0.00 | 6667.74 | 13-FEB-12:00 | 0.00 |
March | 45.13 | 06-MAR-06:10 | 0.00 | 0.00 | 0.00 | 6664.47 | 01-MAR-12:39 | 0.00 |
April | 19859.21 | 30-APR-14:00 | 0.00 | 0.00 | 0.00 | 6584.74 | 06-APR-11:20 | 0.00 |
May | 34359.54 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 6267.36 | 01-MAY-11:20 | 0.00 |
June | 48505.43 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 6220.38 | 01-JUN-11:50 | 0.00 |
July | 47244.95 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 6085.82 | 05-JUL-11:39 | 0.00 |
August | 41890.63 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 5838.25 | 31-AUG-11:00 | 0.00 |
September | 33468.01 | 13-SEP-15:20 | 0.00 | 0.00 | 0.00 | 6071.47 | 28-SEP-11:39 | 0.00 |
October | 9565.38 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 | 6220.57 | 31-OCT-11:50 | 0.00 |
November | 3888.75 | 24-NOV-11:00 | 0.00 | 0.00 | 0.00 | 6266.10 | 30-NOV-12:20 | 0.00 |
December | 107.47 | 30-DEC-05:30 | 0.00 | 0.00 | 0.00 | 6635.63 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 45.13 | 0.00 | 0.00 | 0.00 | 5838.25 | 0.00 | ||
Maximum of Months | 48505.43 | 0.00 | 0.00 | 0.00 | 6667.74 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 121378.45 | 02-JAN-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 9032.47 | 737.70 | 0.00 | 0.00 | 0.00 |
February | 106019.95 | 17-FEB-11:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 7797.67 | 30.29 | 0.00 | 0.00 | 0.00 |
March | 105698.94 | 31-MAR-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 7903.05 | 6.85 | 0.00 | 0.00 | 0.00 |
April | 137877.36 | 28-APR-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 20440.80 | 6.85 | 0.00 | 19661.69 | 0.00 |
May | 150721.00 | 22-MAY-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 19255.31 | 6.90 | 0.00 | 34021.64 | 0.00 |
June | 171046.57 | 13-JUN-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 25114.50 | 6.93 | 0.00 | 48505.43 | 0.00 |
July | 169537.08 | 21-JUL-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 24886.88 | 6.94 | 0.00 | 47244.95 | 0.00 |
August | 162046.27 | 14-AUG-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 22763.69 | 6.91 | 0.00 | 41881.99 | 0.00 |
September | 153039.40 | 13-SEP-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 22165.50 | 6.88 | 0.00 | 33468.01 | 0.00 |
October | 119068.26 | 06-OCT-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 13756.65 | 6.85 | 0.00 | 7893.86 | 0.00 |
November | 120991.85 | 10-NOV-16:49 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 8224.77 | 6.85 | 0.00 | 0.00 | 0.00 |
December | 120237.04 | 22-DEC-16:00 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 7368.86 | 72.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 105698.94 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 7368.86 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 171046.57 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 25114.50 | 737.70 | 0.00 | 48505.43 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 211549.49 | 02-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 179946.86 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 164611.41 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 115159.25 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 80915.56 | 17-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 44335.15 | 07-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 44279.55 | 03-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 37314.68 | 28-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 68654.60 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 132412.72 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 174393.89 | 20-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 192928.10 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 37314.68 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 211549.49 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.78 | 0.83 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.78 | 0.83 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.78 | 0.83 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 18.99 | 1.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
February | 0.33 | 19.37 | 0.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.22 | 0.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 1.00 | 19.08 | 1.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Annual Sum or Average | 3.33 | 19.08 | 3.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.37 | 1.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 18.81 | 3.50 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 1.50 | 18.16 | 1.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
March | 0.50 | 19.07 | 0.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.23 | 0.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
November | 1.50 | 18.73 | 1.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
December | 6.83 | 18.97 | 5.83 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Annual Sum or Average | 15.17 | 18.82 | 12.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 19.23 | 5.83 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 18.37 | 1.83 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
February | 1.17 | 17.61 | 0.50 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
March | 0.33 | 19.11 | 0.33 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.12 | 0.83 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
November | 0.83 | 18.21 | 0.50 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
December | 3.83 | 18.34 | 2.67 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
Annual Sum or Average | 9.33 | 18.29 | 6.00 | 18.67 | 0.83 | 19.16 | 0.83 | 19.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 19.35 | 2.67 | 19.35 | 0.83 | 28.12 | 0.83 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 18.34 | 1.33 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
February | 0.67 | 18.59 | 0.50 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
March | 0.33 | 19.17 | 0.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.00 | 1.00 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.48 | 0.83 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 18.01 | 0.33 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
December | 3.17 | 18.49 | 2.33 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
Annual Sum or Average | 7.00 | 18.44 | 4.83 | 18.76 | 2.00 | 20.06 | 2.00 | 21.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.17 | 2.33 | 19.17 | 1.00 | 28.00 | 1.00 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.14 | 1.33 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
February | 0.83 | 18.26 | 0.50 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
March | 0.33 | 19.15 | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.03 | 0.50 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.59 | 0.50 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.89 | 0.83 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.03 | 1.00 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.59 | 1.00 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.41 | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
November | 0.83 | 17.80 | 0.33 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
December | 3.67 | 18.10 | 2.33 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
Annual Sum or Average | 8.33 | 18.16 | 5.00 | 18.57 | 6.83 | 21.72 | 3.83 | 22.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.41 | 2.33 | 19.41 | 2.33 | 28.03 | 1.00 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.25 | 2.50 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.26 | 0.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 3.17 | 19.25 | 2.83 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.26 | 2.50 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.41 | 1.00 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.50 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.29 | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 1.33 | 19.40 | 1.17 | 19.56 | 0.50 | 20.86 | 0.50 | 21.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.41 | 1.00 | 19.60 | 0.50 | 27.40 | 0.50 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.17 | 18.38 | 64.17 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
February | 52.33 | 18.84 | 52.33 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
March | 60.17 | 18.91 | 60.17 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
April | 21.33 | 19.21 | 21.33 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
May | 17.67 | 19.66 | 17.67 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
June | 2.67 | 20.11 | 2.67 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3.33 | 19.98 | 3.33 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
October | 23.17 | 19.44 | 23.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
November | 48.00 | 19.10 | 48.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
December | 61.50 | 18.46 | 61.50 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
Annual Sum or Average | 354.33 | 18.86 | 354.33 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.17 | 20.11 | 64.17 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.41 | 0.67 | 19.69 | 0.00 | 19.69 | 0.00 | 19.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.72 | 0.17 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.29 | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 1.00 | 19.39 | 0.83 | 19.62 | 0.33 | 20.86 | 0.17 | 21.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.41 | 0.67 | 19.69 | 0.33 | 27.72 | 0.17 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.25 | 2.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.17 | 19.41 | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.38 | 0.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
December | 1.00 | 19.28 | 1.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Annual Sum or Average | 4.00 | 19.27 | 3.67 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.41 | 2.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.81 | 0.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.50 | 0.67 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.88 | 1.50 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.09 | 0.33 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Annual Sum or Average | 0.83 | 18.92 | 0.67 | 19.15 | 2.67 | 24.61 | 2.67 | 25.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.09 | 0.33 | 19.20 | 1.50 | 27.88 | 1.50 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.94 | 0.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.97 | 1.00 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.50 | 1.50 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
December | 0.33 | 19.22 | 0.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Annual Sum or Average | 0.83 | 19.06 | 0.67 | 19.27 | 2.83 | 24.75 | 2.83 | 25.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.22 | 0.33 | 19.31 | 1.50 | 27.97 | 1.50 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.81 | 0.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.03 | 0.50 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.54 | 0.33 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.77 | 0.50 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.94 | 0.83 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.53 | 1.00 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.07 | 0.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 0.83 | 18.91 | 0.67 | 19.14 | 5.83 | 26.03 | 3.17 | 26.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.07 | 0.33 | 19.19 | 2.00 | 28.03 | 1.00 | 28.04 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 441.17 | 23.29 | 15.00 | 23.19 | 15.00 | 23.11 |
February | 383.50 | 23.70 | 0.00 | 23.70 | 0.00 | 23.70 |
March | 402.67 | 23.71 | 0.00 | 23.71 | 0.00 | 23.71 |
April | 97.83 | 23.80 | 59.00 | 24.51 | 0.00 | 24.51 |
May | 31.83 | 23.83 | 160.83 | 24.89 | 0.00 | 24.89 |
June | 0.00 | 0.00 | 348.33 | 24.59 | 0.00 | 24.59 |
July | 0.00 | 0.00 | 409.33 | 24.59 | 0.00 | 24.59 |
August | 0.00 | 0.00 | 433.17 | 24.46 | 0.00 | 24.46 |
September | 0.00 | 0.00 | 314.00 | 24.63 | 0.00 | 24.63 |
October | 102.33 | 23.60 | 84.83 | 24.36 | 0.00 | 24.36 |
November | 275.33 | 23.67 | 11.50 | 23.73 | 0.00 | 23.73 |
December | 476.67 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
Annual Sum or Average | 2211.33 | 23.57 | 1836.00 | 24.06 | 15.00 | 24.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.19 | 0.00 | 23.11 |
Maximum of Months | 476.67 | 23.83 | 433.17 | 24.89 | 15.00 | 24.89 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.97 | 38.17 | 21.82 | 38.17 | 21.69 |
February | 454.00 | 22.29 | 3.00 | 22.28 | 3.00 | 22.26 |
March | 514.00 | 22.59 | 1.17 | 22.58 | 1.17 | 22.58 |
April | 368.50 | 23.39 | 2.83 | 23.41 | 0.00 | 23.41 |
May | 269.17 | 23.40 | 38.50 | 23.52 | 0.00 | 23.52 |
June | 105.33 | 23.41 | 170.17 | 23.95 | 0.00 | 23.95 |
July | 80.00 | 23.40 | 239.00 | 24.06 | 0.00 | 24.06 |
August | 65.33 | 23.45 | 233.67 | 24.10 | 0.00 | 24.10 |
September | 153.33 | 23.32 | 103.17 | 23.71 | 0.00 | 23.71 |
October | 416.50 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
November | 481.67 | 22.50 | 3.33 | 22.49 | 3.33 | 22.47 |
December | 497.00 | 21.84 | 42.83 | 21.75 | 42.83 | 21.66 |
Annual Sum or Average | 3906.83 | 22.62 | 875.83 | 22.85 | 88.50 | 22.81 |
Minimum of Months | 65.33 | 21.84 | 0.00 | 21.75 | 0.00 | 21.66 |
Maximum of Months | 514.00 | 23.45 | 239.00 | 24.10 | 42.83 | 24.10 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.94 | 195.50 | 20.68 | 195.50 | 20.54 |
February | 454.00 | 21.17 | 123.00 | 20.91 | 123.00 | 20.75 |
March | 514.00 | 21.56 | 78.50 | 21.39 | 78.50 | 21.26 |
April | 408.67 | 22.63 | 14.83 | 22.57 | 13.50 | 22.50 |
May | 364.33 | 22.78 | 36.67 | 22.90 | 0.00 | 22.90 |
June | 203.00 | 23.06 | 140.17 | 23.49 | 0.00 | 23.49 |
July | 161.67 | 22.97 | 207.67 | 23.64 | 0.00 | 23.64 |
August | 183.50 | 23.09 | 155.00 | 23.52 | 0.00 | 23.52 |
September | 302.67 | 22.81 | 62.17 | 23.01 | 0.00 | 23.01 |
October | 484.17 | 21.94 | 32.00 | 21.83 | 32.00 | 21.73 |
November | 489.00 | 21.32 | 105.17 | 21.11 | 105.17 | 20.96 |
December | 497.00 | 20.79 | 212.67 | 20.54 | 212.67 | 20.41 |
Annual Sum or Average | 4564.00 | 21.84 | 1363.33 | 21.84 | 760.33 | 21.63 |
Minimum of Months | 161.67 | 20.79 | 14.83 | 20.54 | 0.00 | 20.41 |
Maximum of Months | 514.00 | 23.09 | 212.67 | 23.64 | 212.67 | 23.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.20 | 358.50 | 20.06 | 358.50 | 20.01 |
February | 454.00 | 20.29 | 280.33 | 20.12 | 280.33 | 20.04 |
March | 514.00 | 20.72 | 239.17 | 20.56 | 239.17 | 20.48 |
April | 457.33 | 21.70 | 72.33 | 21.51 | 70.83 | 21.35 |
May | 442.83 | 21.88 | 66.50 | 21.89 | 34.50 | 21.78 |
June | 301.00 | 22.39 | 113.50 | 22.83 | 1.83 | 22.82 |
July | 260.17 | 22.48 | 161.33 | 23.08 | 1.00 | 23.07 |
August | 314.00 | 22.45 | 114.50 | 22.86 | 0.00 | 22.86 |
September | 397.67 | 21.94 | 48.83 | 21.98 | 20.67 | 21.89 |
October | 502.00 | 20.97 | 133.83 | 20.75 | 133.83 | 20.60 |
November | 489.00 | 20.41 | 264.00 | 20.21 | 264.00 | 20.12 |
December | 497.00 | 20.03 | 401.33 | 19.93 | 401.33 | 19.89 |
Annual Sum or Average | 5131.00 | 21.14 | 2254.17 | 21.01 | 1806.00 | 20.80 |
Minimum of Months | 260.17 | 20.03 | 48.83 | 19.93 | 0.00 | 19.89 |
Maximum of Months | 514.00 | 22.48 | 401.33 | 23.08 | 401.33 | 23.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.26 | 340.50 | 20.12 | 340.50 | 20.06 |
February | 454.00 | 20.41 | 259.00 | 20.23 | 259.00 | 20.14 |
March | 514.00 | 20.72 | 224.00 | 20.57 | 224.00 | 20.49 |
April | 371.00 | 21.79 | 81.50 | 21.84 | 43.67 | 21.68 |
May | 361.50 | 21.84 | 108.17 | 22.20 | 21.83 | 22.10 |
June | 257.00 | 22.15 | 185.00 | 23.00 | 1.33 | 23.00 |
July | 206.00 | 22.38 | 239.33 | 23.43 | 5.33 | 23.46 |
August | 232.33 | 22.24 | 219.83 | 23.17 | 0.17 | 23.17 |
September | 280.17 | 21.76 | 149.17 | 22.47 | 16.83 | 22.38 |
October | 489.17 | 21.05 | 114.83 | 20.83 | 114.83 | 20.67 |
November | 489.00 | 20.46 | 236.00 | 20.26 | 236.00 | 20.15 |
December | 497.00 | 20.07 | 386.00 | 19.96 | 386.00 | 19.91 |
Annual Sum or Average | 4653.17 | 21.04 | 2543.33 | 21.19 | 1649.50 | 20.96 |
Minimum of Months | 206.00 | 20.07 | 81.50 | 19.96 | 0.17 | 19.91 |
Maximum of Months | 514.00 | 22.38 | 386.00 | 23.43 | 386.00 | 23.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.50 | 20.58 | 283.83 | 20.37 | 280.67 | 20.27 |
February | 425.00 | 20.75 | 210.83 | 20.53 | 204.50 | 20.40 |
March | 512.83 | 20.88 | 211.67 | 20.70 | 211.67 | 20.60 |
April | 352.67 | 21.68 | 136.83 | 21.90 | 64.33 | 21.75 |
May | 377.67 | 21.62 | 130.83 | 22.00 | 39.17 | 21.86 |
June | 294.33 | 21.99 | 152.67 | 22.70 | 3.50 | 22.68 |
July | 260.83 | 22.17 | 191.50 | 23.04 | 4.50 | 23.04 |
August | 266.33 | 22.21 | 205.17 | 23.07 | 4.00 | 23.09 |
September | 273.67 | 21.78 | 199.67 | 22.70 | 21.50 | 22.64 |
October | 426.83 | 21.10 | 150.83 | 21.18 | 99.67 | 21.01 |
November | 470.67 | 20.71 | 204.17 | 20.52 | 196.67 | 20.37 |
December | 492.50 | 20.33 | 343.33 | 20.16 | 343.33 | 20.09 |
Annual Sum or Average | 4639.83 | 21.17 | 2421.33 | 21.35 | 1473.50 | 21.13 |
Minimum of Months | 260.83 | 20.33 | 130.83 | 20.16 | 3.50 | 20.09 |
Maximum of Months | 512.83 | 22.21 | 343.33 | 23.07 | 343.33 | 23.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.27 | 343.67 | 20.12 | 343.67 | 20.05 |
February | 453.50 | 20.47 | 258.17 | 20.26 | 258.17 | 20.16 |
March | 512.50 | 20.70 | 235.50 | 20.54 | 235.50 | 20.46 |
April | 407.67 | 21.44 | 118.67 | 21.53 | 71.67 | 21.39 |
May | 397.17 | 21.51 | 121.00 | 21.83 | 42.50 | 21.71 |
June | 311.83 | 22.01 | 139.00 | 22.66 | 6.83 | 22.68 |
July | 279.50 | 22.17 | 171.00 | 22.92 | 11.00 | 22.96 |
August | 331.00 | 22.14 | 139.33 | 22.73 | 5.67 | 22.76 |
September | 378.83 | 21.63 | 104.17 | 22.00 | 22.50 | 21.91 |
October | 478.83 | 20.88 | 138.33 | 20.74 | 127.00 | 20.61 |
November | 489.00 | 20.46 | 248.67 | 20.25 | 248.67 | 20.15 |
December | 497.00 | 20.05 | 398.67 | 19.94 | 398.67 | 19.90 |
Annual Sum or Average | 5038.83 | 21.02 | 2416.17 | 21.05 | 1771.83 | 20.85 |
Minimum of Months | 279.50 | 20.05 | 104.17 | 19.94 | 5.67 | 19.90 |
Maximum of Months | 512.50 | 22.17 | 398.67 | 22.92 | 398.67 | 22.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.50 | 327.00 | 20.38 | 327.00 | 20.33 |
February | 454.00 | 20.58 | 266.00 | 20.46 | 266.00 | 20.41 |
March | 514.00 | 20.85 | 210.00 | 20.74 | 210.00 | 20.68 |
April | 484.50 | 21.67 | 40.67 | 21.57 | 40.67 | 21.48 |
May | 490.67 | 22.03 | 4.33 | 22.02 | 4.33 | 22.00 |
June | 381.83 | 22.79 | 40.50 | 22.91 | 0.00 | 22.91 |
July | 289.67 | 22.97 | 81.67 | 23.20 | 0.00 | 23.20 |
August | 349.50 | 22.90 | 42.50 | 23.02 | 0.00 | 23.02 |
September | 434.33 | 22.54 | 10.83 | 22.58 | 0.00 | 22.58 |
October | 502.00 | 21.48 | 27.33 | 21.41 | 27.33 | 21.35 |
November | 489.00 | 20.90 | 140.50 | 20.77 | 140.50 | 20.69 |
December | 497.00 | 20.48 | 343.67 | 20.39 | 343.67 | 20.35 |
Annual Sum or Average | 5388.50 | 21.53 | 1535.00 | 21.35 | 1359.50 | 21.17 |
Minimum of Months | 289.67 | 20.48 | 4.33 | 20.38 | 0.00 | 20.33 |
Maximum of Months | 514.00 | 22.97 | 343.67 | 23.20 | 343.67 | 23.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.57 | 310.83 | 20.46 | 310.83 | 20.42 |
February | 454.00 | 20.71 | 221.50 | 20.58 | 221.50 | 20.52 |
March | 514.00 | 20.85 | 185.67 | 20.75 | 185.67 | 20.69 |
April | 409.00 | 22.11 | 37.33 | 22.14 | 17.67 | 22.06 |
May | 388.67 | 22.26 | 67.17 | 22.55 | 3.00 | 22.53 |
June | 261.33 | 22.54 | 146.33 | 23.18 | 0.00 | 23.18 |
July | 182.17 | 22.83 | 234.83 | 23.73 | 2.50 | 23.75 |
August | 198.67 | 22.81 | 219.50 | 23.58 | 0.00 | 23.58 |
September | 245.83 | 22.48 | 128.83 | 23.15 | 0.00 | 23.15 |
October | 481.17 | 21.56 | 25.67 | 21.52 | 22.67 | 21.46 |
November | 489.00 | 20.92 | 119.67 | 20.80 | 119.67 | 20.73 |
December | 497.00 | 20.51 | 327.17 | 20.41 | 327.17 | 20.36 |
Annual Sum or Average | 4622.83 | 21.43 | 2024.50 | 21.59 | 1210.67 | 21.39 |
Minimum of Months | 182.17 | 20.51 | 25.67 | 20.41 | 0.00 | 20.36 |
Maximum of Months | 514.00 | 22.83 | 327.17 | 23.73 | 327.17 | 23.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.00 | 20.57 | 250.67 | 20.34 | 249.50 | 20.22 |
February | 449.50 | 20.81 | 156.67 | 20.56 | 156.67 | 20.41 |
March | 514.00 | 20.63 | 204.67 | 20.45 | 204.67 | 20.35 |
April | 417.67 | 21.67 | 72.17 | 21.68 | 43.33 | 21.52 |
May | 439.00 | 21.64 | 64.67 | 21.78 | 25.00 | 21.68 |
June | 377.17 | 22.08 | 71.33 | 22.42 | 2.00 | 22.41 |
July | 295.67 | 22.42 | 129.17 | 23.02 | 0.00 | 23.02 |
August | 241.17 | 22.51 | 175.17 | 23.26 | 0.00 | 23.26 |
September | 233.33 | 22.28 | 182.50 | 23.23 | 0.83 | 23.23 |
October | 438.50 | 21.55 | 69.00 | 21.66 | 29.33 | 21.54 |
November | 477.17 | 20.93 | 113.00 | 20.77 | 108.17 | 20.63 |
December | 497.00 | 20.40 | 303.50 | 20.21 | 303.50 | 20.13 |
Annual Sum or Average | 4878.17 | 21.30 | 1792.50 | 21.37 | 1123.00 | 21.16 |
Minimum of Months | 233.33 | 20.40 | 64.67 | 20.21 | 0.00 | 20.13 |
Maximum of Months | 514.00 | 22.51 | 303.50 | 23.26 | 303.50 | 23.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.56 | 311.50 | 20.44 | 311.50 | 20.39 |
February | 454.00 | 20.76 | 219.33 | 20.61 | 219.33 | 20.53 |
March | 514.00 | 20.82 | 203.00 | 20.72 | 203.00 | 20.66 |
April | 439.33 | 21.68 | 49.17 | 21.69 | 31.00 | 21.60 |
May | 421.33 | 21.90 | 55.33 | 22.13 | 7.83 | 22.09 |
June | 308.00 | 22.45 | 120.83 | 22.96 | 0.00 | 22.96 |
July | 222.67 | 22.55 | 176.00 | 23.30 | 1.17 | 23.31 |
August | 293.50 | 22.66 | 120.50 | 23.11 | 0.00 | 23.11 |
September | 367.00 | 22.28 | 70.33 | 22.60 | 0.00 | 22.60 |
October | 482.83 | 21.37 | 31.83 | 21.32 | 28.67 | 21.26 |
November | 489.00 | 20.89 | 134.00 | 20.77 | 134.00 | 20.69 |
December | 497.00 | 20.48 | 350.33 | 20.38 | 350.33 | 20.35 |
Annual Sum or Average | 4990.67 | 21.37 | 1842.17 | 21.41 | 1286.83 | 21.23 |
Minimum of Months | 222.67 | 20.48 | 31.83 | 20.38 | 0.00 | 20.35 |
Maximum of Months | 514.00 | 22.66 | 350.33 | 23.30 | 350.33 | 23.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.63 | 267.33 | 20.45 | 267.33 | 20.36 |
February | 454.00 | 20.79 | 176.33 | 20.58 | 176.33 | 20.47 |
March | 514.00 | 21.24 | 107.00 | 21.08 | 107.00 | 20.97 |
April | 435.83 | 22.34 | 15.50 | 22.27 | 15.00 | 22.21 |
May | 410.50 | 22.57 | 27.17 | 22.66 | 0.33 | 22.66 |
June | 222.67 | 23.01 | 125.50 | 23.39 | 0.00 | 23.39 |
July | 186.17 | 23.07 | 192.50 | 23.58 | 0.00 | 23.58 |
August | 226.50 | 23.09 | 150.50 | 23.45 | 0.00 | 23.45 |
September | 335.83 | 22.64 | 51.67 | 22.82 | 0.00 | 22.82 |
October | 498.83 | 21.72 | 30.17 | 21.63 | 30.17 | 21.55 |
November | 489.00 | 20.96 | 135.83 | 20.79 | 135.83 | 20.68 |
December | 497.00 | 20.45 | 285.50 | 20.29 | 285.50 | 20.21 |
Annual Sum or Average | 4772.33 | 21.63 | 1565.00 | 21.59 | 1017.50 | 21.39 |
Minimum of Months | 186.17 | 20.45 | 15.50 | 20.29 | 0.00 | 20.21 |
Maximum of Months | 514.00 | 23.09 | 285.50 | 23.58 | 285.50 | 23.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.57 | 229.83 | 20.41 | 229.83 | 20.34 |
February | 385.00 | 20.79 | 155.67 | 20.62 | 155.67 | 20.52 |
March | 433.00 | 21.05 | 94.50 | 20.91 | 94.50 | 20.82 |
April | 318.67 | 22.09 | 49.83 | 22.22 | 16.50 | 22.15 |
May | 304.33 | 22.14 | 75.00 | 22.58 | 1.00 | 22.57 |
June | 215.00 | 22.44 | 142.67 | 23.19 | 0.50 | 23.20 |
July | 186.67 | 22.75 | 187.50 | 23.62 | 6.17 | 23.67 |
August | 208.33 | 22.61 | 158.50 | 23.32 | 1.50 | 23.33 |
September | 246.33 | 22.16 | 107.33 | 22.86 | 0.00 | 22.86 |
October | 408.33 | 21.45 | 39.67 | 21.39 | 33.67 | 21.30 |
November | 417.00 | 20.85 | 120.67 | 20.70 | 120.67 | 20.60 |
December | 422.00 | 20.37 | 267.83 | 20.22 | 267.83 | 20.16 |
Annual Sum or Average | 3971.67 | 21.39 | 1629.00 | 21.56 | 927.83 | 21.37 |
Minimum of Months | 186.67 | 20.37 | 39.67 | 20.22 | 0.00 | 20.16 |
Maximum of Months | 433.00 | 22.75 | 267.83 | 23.62 | 267.83 | 23.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 470.67 | 20.97 | 188.67 | 20.82 | 182.00 | 20.70 |
February | 408.00 | 21.14 | 123.83 | 21.06 | 107.67 | 20.92 |
March | 505.50 | 21.25 | 90.50 | 21.11 | 90.50 | 21.01 |
April | 332.50 | 22.10 | 97.50 | 22.43 | 22.50 | 22.37 |
May | 361.17 | 22.07 | 98.17 | 22.52 | 5.17 | 22.49 |
June | 267.33 | 22.42 | 160.83 | 23.08 | 0.00 | 23.08 |
July | 217.67 | 22.53 | 206.67 | 23.39 | 0.67 | 23.39 |
August | 220.17 | 22.65 | 223.17 | 23.43 | 2.50 | 23.45 |
September | 243.17 | 22.32 | 203.00 | 23.25 | 4.83 | 23.28 |
October | 405.50 | 21.58 | 88.17 | 21.86 | 24.17 | 21.78 |
November | 455.50 | 21.14 | 109.00 | 21.10 | 92.67 | 20.97 |
December | 486.33 | 20.76 | 236.83 | 20.56 | 236.83 | 20.46 |
Annual Sum or Average | 4373.50 | 21.57 | 1826.33 | 21.88 | 769.50 | 21.70 |
Minimum of Months | 217.67 | 20.76 | 88.17 | 20.56 | 0.00 | 20.46 |
Maximum of Months | 505.50 | 22.65 | 236.83 | 23.43 | 236.83 | 23.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.62 | 250.17 | 20.46 | 250.17 | 20.38 |
February | 449.83 | 20.86 | 156.17 | 20.66 | 156.17 | 20.55 |
March | 511.33 | 20.99 | 113.33 | 20.87 | 113.33 | 20.79 |
April | 403.33 | 21.84 | 71.17 | 22.00 | 25.33 | 21.93 |
May | 389.33 | 21.94 | 84.83 | 22.32 | 7.00 | 22.29 |
June | 281.83 | 22.40 | 148.00 | 23.03 | 3.00 | 23.06 |
July | 235.33 | 22.51 | 186.83 | 23.28 | 6.50 | 23.33 |
August | 284.00 | 22.52 | 144.67 | 23.07 | 3.83 | 23.10 |
September | 356.00 | 22.08 | 87.00 | 22.51 | 0.17 | 22.51 |
October | 474.00 | 21.31 | 55.00 | 21.30 | 40.00 | 21.21 |
November | 489.00 | 20.86 | 135.17 | 20.71 | 135.17 | 20.61 |
December | 497.00 | 20.43 | 300.67 | 20.29 | 300.67 | 20.22 |
Annual Sum or Average | 4873.00 | 21.37 | 1733.00 | 21.49 | 1041.33 | 21.31 |
Minimum of Months | 235.33 | 20.43 | 55.00 | 20.29 | 0.17 | 20.22 |
Maximum of Months | 511.33 | 22.52 | 300.67 | 23.28 | 300.67 | 23.33 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.39079 | 32.48536 | 0.09494 | 6.03513 |
February | 454.00000 | 23.76800 | 30.91346 | 0.18915 | 5.94574 |
March | 514.00000 | 23.84387 | 29.95333 | 0.21017 | 6.11915 |
April | 485.00000 | 24.27622 | 28.91733 | 0.34320 | 7.69128 |
May | 508.00000 | 24.37565 | 34.49968 | -0.4535 | 9.80709 |
June | 496.00000 | 24.42015 | 41.40200 | -0.3556 | 8.18321 |
July | 497.00000 | 24.49109 | 42.85773 | -0.3180 | 7.68291 |
August | 514.00000 | 24.39210 | 42.71009 | -0.3373 | 7.84131 |
September | 485.00000 | 24.41560 | 40.89765 | -0.3650 | 8.33057 |
October | 502.00000 | 24.22929 | 35.83357 | 0.36516 | 8.01116 |
November | 489.00000 | 23.96820 | 33.74870 | 0.26374 | 6.73973 |
December | 497.00000 | 23.52846 | 30.06080 | 0.11556 | 5.58439 |
Annual Sum or Average | 5943.00000 | 24.09325 | 35.39373 | -0.0231 | 7.34096 |
Minimum of Months | 454.00000 | 23.39079 | 28.91733 | -0.4535 | 5.58439 |
Maximum of Months | 514.00000 | 24.49109 | 42.85773 | 0.36516 | 9.80709 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.96736 | 35.60160 | -0.2343 | 7.28757 |
February | 454.00000 | 22.28993 | 34.56684 | -0.1516 | 6.21551 |
March | 514.00000 | 22.58558 | 33.43860 | -0.0815 | 5.76489 |
April | 485.00000 | 23.57329 | 31.08983 | 0.16958 | 6.09289 |
May | 508.00000 | 23.73267 | 36.47502 | -0.6847 | 15.62819 |
June | 496.00000 | 23.99461 | 43.00222 | -0.5198 | 11.06979 |
July | 497.00000 | 24.04674 | 44.33586 | -0.4879 | 10.44364 |
August | 514.00000 | 24.03290 | 44.09329 | -0.4866 | 10.26804 |
September | 485.00000 | 23.85433 | 42.69715 | -0.5799 | 12.56962 |
October | 502.00000 | 23.15923 | 39.22455 | 0.10526 | 5.86915 |
November | 489.00000 | 22.52094 | 37.71394 | -0.0749 | 5.92900 |
December | 497.00000 | 21.84312 | 33.71827 | -0.2735 | 7.42615 |
Annual Sum or Average | 5943.00000 | 23.13899 | 38.02584 | -0.2768 | 8.73785 |
Minimum of Months | 454.00000 | 21.84312 | 31.08983 | -0.6847 | 5.76489 |
Maximum of Months | 514.00000 | 24.04674 | 44.33586 | 0.16958 | 15.62819 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94119 | 35.74010 | -0.5089 | 12.23049 |
February | 454.00000 | 21.16815 | 36.23041 | -0.4371 | 10.49320 |
March | 514.00000 | 21.55588 | 35.02303 | -0.3376 | 8.42399 |
April | 485.00000 | 22.84628 | 32.29421 | -0.0013 | 6.40649 |
May | 508.00000 | 23.13747 | 37.56003 | -0.8820 | 23.44195 |
June | 496.00000 | 23.65569 | 43.87085 | -0.6288 | 14.52762 |
July | 497.00000 | 23.73429 | 45.14215 | -0.5857 | 13.42822 |
August | 514.00000 | 23.68515 | 44.98829 | -0.6039 | 13.58802 |
September | 485.00000 | 23.25157 | 44.49207 | -0.7873 | 19.71743 |
October | 502.00000 | 22.01205 | 41.70756 | -0.1730 | 6.92425 |
November | 489.00000 | 21.31875 | 40.06626 | -0.3765 | 9.24984 |
December | 497.00000 | 20.79234 | 35.33509 | -0.5550 | 13.02602 |
Annual Sum or Average | 5943.00000 | 22.34997 | 39.39501 | -0.4910 | 12.64496 |
Minimum of Months | 454.00000 | 20.79234 | 32.29421 | -0.8820 | 6.40649 |
Maximum of Months | 514.00000 | 23.73429 | 45.14215 | -0.0013 | 23.44195 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.20274 | 36.81741 | -0.7338 | 18.48070 |
February | 454.00000 | 20.29137 | 37.39448 | -0.6850 | 16.78877 |
March | 514.00000 | 20.72269 | 36.28979 | -0.5586 | 12.62907 |
April | 485.00000 | 21.82865 | 33.88359 | -0.2330 | 8.24367 |
May | 508.00000 | 22.14216 | 39.39133 | -1.1865 | 36.96930 |
June | 496.00000 | 23.00496 | 45.41396 | -0.8133 | 21.61706 |
July | 497.00000 | 23.19818 | 46.46912 | -0.7331 | 18.91375 |
August | 514.00000 | 23.01074 | 46.84261 | -0.8022 | 20.95782 |
September | 485.00000 | 22.28310 | 46.17765 | -1.0950 | 32.84633 |
October | 502.00000 | 20.96812 | 44.16525 | -0.4264 | 10.19863 |
November | 489.00000 | 20.40711 | 41.17048 | -0.6289 | 14.99461 |
December | 497.00000 | 20.03338 | 36.04045 | -0.7914 | 20.56264 |
Annual Sum or Average | 5943.00000 | 21.51726 | 40.86587 | -0.7249 | 19.46257 |
Minimum of Months | 454.00000 | 20.03338 | 33.88359 | -1.1865 | 8.24367 |
Maximum of Months | 514.00000 | 23.19818 | 46.84261 | -0.2330 | 36.96930 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26344 | 36.49409 | -0.7075 | 17.49103 |
February | 454.00000 | 20.40769 | 36.96192 | -0.6423 | 15.29929 |
March | 514.00000 | 20.71803 | 36.07784 | -0.5458 | 12.22138 |
April | 485.00000 | 22.31463 | 32.66737 | -0.0696 | 8.07315 |
May | 508.00000 | 22.50171 | 38.36144 | -1.0007 | 30.39936 |
June | 496.00000 | 23.07416 | 44.95492 | -0.7147 | 19.80349 |
July | 497.00000 | 23.41578 | 45.70382 | -0.5847 | 16.05537 |
August | 514.00000 | 23.21488 | 45.87709 | -0.6492 | 17.53673 |
September | 485.00000 | 22.73978 | 44.68585 | -0.8726 | 25.70541 |
October | 502.00000 | 21.12276 | 43.66945 | -0.3684 | 9.69448 |
November | 489.00000 | 20.45550 | 40.92821 | -0.6079 | 14.24821 |
December | 497.00000 | 20.07311 | 35.79264 | -0.7752 | 19.90465 |
Annual Sum or Average | 5943.00000 | 21.70053 | 40.20980 | -0.6291 | 17.22635 |
Minimum of Months | 454.00000 | 20.07311 | 32.66737 | -1.0007 | 8.07315 |
Maximum of Months | 514.00000 | 23.41578 | 45.87709 | -0.0696 | 30.39936 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.69247 | 35.20850 | -0.5784 | 15.07855 |
February | 454.00000 | 20.95828 | 35.48124 | -0.4875 | 13.33310 |
March | 514.00000 | 20.88791 | 35.33827 | -0.4978 | 11.67702 |
April | 485.00000 | 22.33022 | 32.25622 | -0.0622 | 8.93531 |
May | 508.00000 | 22.28624 | 38.52553 | -1.0822 | 34.49174 |
June | 496.00000 | 22.81261 | 45.40689 | -0.8176 | 23.44925 |
July | 497.00000 | 23.09361 | 46.30492 | -0.6973 | 19.96290 |
August | 514.00000 | 23.09052 | 45.96383 | -0.6793 | 19.55545 |
September | 485.00000 | 22.83115 | 44.04025 | -0.8057 | 25.42770 |
October | 502.00000 | 21.54911 | 42.21856 | -0.2481 | 9.65020 |
November | 489.00000 | 20.85140 | 39.68926 | -0.4938 | 12.75389 |
December | 497.00000 | 20.36159 | 34.81432 | -0.6879 | 17.55429 |
Annual Sum or Average | 5943.00000 | 21.81702 | 39.64109 | -0.5969 | 17.70519 |
Minimum of Months | 454.00000 | 20.36159 | 32.25622 | -1.0822 | 8.93531 |
Maximum of Months | 514.00000 | 23.09361 | 46.30492 | -0.0622 | 34.49174 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26728 | 36.28871 | -0.7099 | 17.78178 |
February | 454.00000 | 20.47623 | 36.62628 | -0.6256 | 15.61084 |
March | 514.00000 | 20.70365 | 35.90287 | -0.5521 | 12.61565 |
April | 485.00000 | 21.84980 | 33.37034 | -0.1823 | 8.92605 |
May | 508.00000 | 22.08541 | 39.15611 | -1.1341 | 36.89385 |
June | 496.00000 | 22.73251 | 45.76008 | -0.8122 | 23.88764 |
July | 497.00000 | 22.96186 | 46.82046 | -0.7162 | 21.00033 |
August | 514.00000 | 22.76626 | 47.09673 | -0.7928 | 22.71723 |
September | 485.00000 | 22.16556 | 46.01572 | -1.0600 | 33.19200 |
October | 502.00000 | 21.01888 | 43.71056 | -0.3965 | 10.17687 |
November | 489.00000 | 20.45907 | 40.71512 | -0.6109 | 14.60672 |
December | 497.00000 | 20.04827 | 35.66114 | -0.7881 | 20.40081 |
Annual Sum or Average | 5943.00000 | 21.46863 | 40.62651 | -0.6997 | 19.85871 |
Minimum of Months | 454.00000 | 20.04827 | 33.37034 | -1.1341 | 8.92605 |
Maximum of Months | 514.00000 | 22.96186 | 47.09673 | -0.1823 | 36.89385 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49620 | 36.77217 | -0.6479 | 15.00123 |
February | 454.00000 | 20.58059 | 37.14252 | -0.6063 | 13.39217 |
March | 514.00000 | 20.85200 | 36.17933 | -0.5279 | 11.26627 |
April | 485.00000 | 21.67708 | 34.54532 | -0.2853 | 7.59806 |
May | 508.00000 | 22.09339 | 40.02978 | -1.2367 | 38.18311 |
June | 496.00000 | 23.05742 | 45.93913 | -0.8452 | 21.39182 |
July | 497.00000 | 23.36893 | 46.70751 | -0.7233 | 17.15538 |
August | 514.00000 | 23.22273 | 47.00978 | -0.7733 | 18.62481 |
September | 485.00000 | 22.68131 | 45.80040 | -0.9825 | 26.70047 |
October | 502.00000 | 21.47563 | 43.07919 | -0.2878 | 7.37644 |
November | 489.00000 | 20.89890 | 40.32272 | -0.4764 | 10.32519 |
December | 497.00000 | 20.48218 | 35.48761 | -0.6501 | 14.63618 |
Annual Sum or Average | 5943.00000 | 21.74914 | 40.78154 | -0.6717 | 16.85499 |
Minimum of Months | 454.00000 | 20.48218 | 34.54532 | -1.2367 | 7.37644 |
Maximum of Months | 514.00000 | 23.36893 | 47.00978 | -0.2853 | 38.18311 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.57134 | 36.37596 | -0.6190 | 14.00968 |
February | 454.00000 | 20.71040 | 36.61986 | -0.5609 | 12.16643 |
March | 514.00000 | 20.84906 | 35.86226 | -0.5167 | 10.99866 |
April | 485.00000 | 22.42846 | 32.73575 | -0.0627 | 6.98824 |
May | 508.00000 | 22.71765 | 38.29508 | -0.9664 | 27.72570 |
June | 496.00000 | 23.28715 | 44.81740 | -0.6940 | 17.72849 |
July | 497.00000 | 23.72159 | 45.34995 | -0.5309 | 13.03911 |
August | 514.00000 | 23.60332 | 45.29333 | -0.5598 | 13.48461 |
September | 485.00000 | 23.30894 | 43.61636 | -0.7006 | 17.96981 |
October | 502.00000 | 21.67286 | 42.43742 | -0.2185 | 7.21653 |
November | 489.00000 | 20.91665 | 40.08184 | -0.4613 | 9.93937 |
December | 497.00000 | 20.51028 | 35.18374 | -0.6382 | 14.27660 |
Annual Sum or Average | 5943.00000 | 22.03310 | 39.75149 | -0.5452 | 13.82844 |
Minimum of Months | 454.00000 | 20.51028 | 32.73575 | -0.9664 | 6.98824 |
Maximum of Months | 514.00000 | 23.72159 | 45.34995 | -0.0627 | 27.72570 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.60606 | 34.62372 | -0.5552 | 13.50523 |
February | 454.00000 | 20.84968 | 34.98234 | -0.4705 | 11.26326 |
March | 514.00000 | 20.62624 | 34.80122 | -0.5380 | 11.87104 |
April | 485.00000 | 22.03328 | 32.42907 | -0.1287 | 7.75105 |
May | 508.00000 | 22.00452 | 39.02459 | -1.1789 | 36.91560 |
June | 496.00000 | 22.55888 | 46.22426 | -0.9246 | 25.81964 |
July | 497.00000 | 23.11483 | 46.64723 | -0.7207 | 18.72329 |
August | 514.00000 | 23.33476 | 45.83410 | -0.6224 | 15.85896 |
September | 485.00000 | 23.28171 | 43.07031 | -0.6529 | 17.80473 |
October | 502.00000 | 21.88000 | 40.89705 | -0.1305 | 7.58922 |
November | 489.00000 | 21.02914 | 38.57412 | -0.3942 | 9.74117 |
December | 497.00000 | 20.40473 | 33.89897 | -0.6220 | 14.44957 |
Annual Sum or Average | 5943.00000 | 21.81515 | 39.29044 | -0.5807 | 16.01224 |
Minimum of Months | 454.00000 | 20.40473 | 32.42907 | -1.1789 | 7.58922 |
Maximum of Months | 514.00000 | 23.33476 | 46.64723 | -0.1287 | 36.91560 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.55914 | 36.15358 | -0.6249 | 14.32524 |
February | 454.00000 | 20.76342 | 36.26172 | -0.5459 | 12.12715 |
March | 514.00000 | 20.82242 | 35.66261 | -0.5251 | 11.25580 |
April | 485.00000 | 21.90669 | 33.49591 | -0.1886 | 7.55366 |
May | 508.00000 | 22.29995 | 39.00906 | -1.0989 | 33.64730 |
June | 496.00000 | 23.06132 | 45.27901 | -0.7558 | 19.79888 |
July | 497.00000 | 23.37466 | 46.10916 | -0.6297 | 16.11968 |
August | 514.00000 | 23.22666 | 46.31173 | -0.6841 | 16.91711 |
September | 485.00000 | 22.70965 | 45.03059 | -0.8971 | 24.65157 |
October | 502.00000 | 21.46854 | 42.66516 | -0.2655 | 7.47652 |
November | 489.00000 | 20.88656 | 39.89224 | -0.4710 | 10.23661 |
December | 497.00000 | 20.47580 | 35.02271 | -0.6547 | 14.77408 |
Annual Sum or Average | 5943.00000 | 21.80357 | 40.10682 | -0.6133 | 15.78725 |
Minimum of Months | 454.00000 | 20.47580 | 33.49591 | -1.0989 | 7.47652 |
Maximum of Months | 514.00000 | 23.37466 | 46.31173 | -0.1886 | 33.64730 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.62713 | 36.63325 | -0.5858 | 13.70636 |
February | 454.00000 | 20.78590 | 37.08107 | -0.5225 | 11.71175 |
March | 514.00000 | 21.23532 | 36.03800 | -0.4013 | 9.18970 |
April | 485.00000 | 22.50772 | 33.21444 | -0.0714 | 6.53455 |
May | 508.00000 | 22.84351 | 38.41797 | -0.9636 | 26.57715 |
June | 496.00000 | 23.55904 | 44.27603 | -0.6486 | 15.02060 |
July | 497.00000 | 23.67595 | 45.35985 | -0.5928 | 13.41966 |
August | 514.00000 | 23.57190 | 45.61222 | -0.6314 | 14.33164 |
September | 485.00000 | 23.05020 | 44.56790 | -0.8480 | 21.95738 |
October | 502.00000 | 21.73209 | 42.90202 | -0.2220 | 7.17750 |
November | 489.00000 | 20.96430 | 40.55383 | -0.4517 | 10.26070 |
December | 497.00000 | 20.45174 | 35.70252 | -0.6387 | 14.76035 |
Annual Sum or Average | 5943.00000 | 22.09329 | 40.05556 | -0.5492 | 13.74453 |
Minimum of Months | 454.00000 | 20.45174 | 33.21444 | -0.9636 | 6.53455 |
Maximum of Months | 514.00000 | 23.67595 | 45.61222 | -0.0714 | 26.57715 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.56616 | 35.68971 | -0.5955 | 13.73933 |
February | 385.00000 | 20.78536 | 35.88686 | -0.5151 | 11.41126 |
March | 433.00000 | 21.04661 | 35.35373 | -0.4339 | 9.63512 |
April | 410.00000 | 22.53191 | 32.15052 | -0.0088 | 7.23702 |
May | 430.00000 | 22.75346 | 37.59618 | -0.9115 | 26.22470 |
June | 418.00000 | 23.25189 | 44.21121 | -0.6621 | 17.33086 |
July | 422.00000 | 23.57713 | 45.04428 | -0.5423 | 14.21323 |
August | 433.00000 | 23.34536 | 45.35816 | -0.6096 | 15.55451 |
September | 410.00000 | 22.97524 | 43.80439 | -0.7831 | 21.76282 |
October | 427.00000 | 21.56851 | 42.20777 | -0.2364 | 7.60913 |
November | 417.00000 | 20.85358 | 39.76948 | -0.4715 | 10.46481 |
December | 422.00000 | 20.37002 | 34.87751 | -0.6575 | 15.21470 |
Annual Sum or Average | 5034.00000 | 21.97426 | 39.35756 | -0.5367 | 14.22517 |
Minimum of Months | 385.00000 | 20.37002 | 32.15052 | -0.9115 | 7.23702 |
Maximum of Months | 433.00000 | 23.57713 | 45.35816 | -0.0088 | 26.22470 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.17486 | 34.39712 | -0.4230 | 11.24531 |
February | 454.00000 | 21.45541 | 34.66492 | -0.3281 | 9.86395 |
March | 514.00000 | 21.29481 | 34.71010 | -0.3633 | 8.89667 |
April | 485.00000 | 22.73606 | 31.56521 | 0.04645 | 7.81709 |
May | 508.00000 | 22.68852 | 37.76846 | -0.9386 | 27.59207 |
June | 496.00000 | 23.16726 | 44.52975 | -0.7055 | 18.37205 |
July | 497.00000 | 23.42676 | 45.43805 | -0.5945 | 15.39290 |
August | 514.00000 | 23.44947 | 45.07434 | -0.5616 | 14.61684 |
September | 485.00000 | 23.25587 | 42.93357 | -0.6492 | 18.67722 |
October | 502.00000 | 22.07632 | 40.96059 | -0.0912 | 7.80095 |
November | 489.00000 | 21.36347 | 38.70249 | -0.3285 | 9.31442 |
December | 497.00000 | 20.83339 | 33.90936 | -0.5280 | 12.65697 |
Annual Sum or Average | 5943.00000 | 22.24773 | 38.75869 | -0.4577 | 13.56217 |
Minimum of Months | 454.00000 | 20.83339 | 31.56521 | -0.9386 | 7.80095 |
Maximum of Months | 514.00000 | 23.44947 | 45.43805 | 0.04645 | 27.59207 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.62228 | 35.70902 | -0.5788 | 13.40066 |
February | 454.00000 | 20.88196 | 35.96961 | -0.4837 | 11.28974 |
March | 514.00000 | 21.00691 | 35.44935 | -0.4374 | 9.72835 |
April | 485.00000 | 22.21521 | 32.77094 | -0.0810 | 7.44274 |
May | 508.00000 | 22.46277 | 38.45070 | -0.9968 | 30.06377 |
June | 496.00000 | 23.08382 | 44.90036 | -0.7003 | 18.80330 |
July | 497.00000 | 23.29431 | 45.97483 | -0.6130 | 16.42584 |
August | 514.00000 | 23.14014 | 46.19964 | -0.6707 | 17.41346 |
September | 485.00000 | 22.60243 | 44.92132 | -0.8999 | 25.69481 |
October | 502.00000 | 21.45812 | 42.67861 | -0.2554 | 7.68219 |
November | 489.00000 | 20.85667 | 39.92815 | -0.4671 | 10.46522 |
December | 497.00000 | 20.42935 | 34.88403 | -0.6466 | 14.90807 |
Annual Sum or Average | 5943.00000 | 21.84471 | 39.85266 | -0.5707 | 15.31567 |
Minimum of Months | 454.00000 | 20.42935 | 32.77094 | -0.9968 | 7.44274 |
Maximum of Months | 514.00000 | 23.29431 | 46.19964 | -0.0810 | 30.06377 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.475592E+11 | 0.00 | 405.11 | 245598.77 | 23-JAN-06:11 | 0.00 | 31.72 | 46.51 | 0.18 | 0.00 | 0.05 | 0.74 | 23-JAN-06:11 |
February | 0.308973E+11 | 0.00 | 344.97 | 253493.38 | 06-FEB-06:11 | 0.00 | 31.03 | 45.63 | 0.12 | 0.00 | 0.04 | 0.77 | 06-FEB-06:11 |
March | 0.270215E+11 | 0.00 | 384.74 | 250296.97 | 20-MAR-05:11 | 0.00 | 29.63 | 44.52 | 0.09 | 0.00 | 0.03 | 0.76 | 20-MAR-05:11 |
April | 0.568577E+10 | 0.00 | 184.95 | 206637.79 | 12-APR-06:02 | 0.00 | 31.53 | 38.39 | 0.02 | 0.00 | 0.01 | 0.62 | 12-APR-06:02 |
May | 0.370818E+10 | 0.00 | 162.20 | 158516.32 | 19-MAY-06:03 | 0.00 | 33.84 | 39.17 | 0.02 | 0.00 | 0.00 | 0.48 | 19-MAY-06:03 |
June | 0.942131E+09 | 0.00 | 86.23 | 59982.08 | 07-JUN-06:03 | 0.00 | 38.12 | 40.77 | 0.00 | 0.00 | 0.00 | 0.18 | 07-JUN-06:03 |
July | 0.456678E+09 | 0.00 | 68.77 | 50958.49 | 31-JUL-06:03 | 0.00 | 36.38 | 38.57 | 0.00 | 0.00 | 0.00 | 0.15 | 31-JUL-06:03 |
August | 0.474578E+09 | 0.00 | 60.31 | 43669.10 | 28-AUG-06:03 | 0.00 | 32.57 | 34.85 | 0.00 | 0.00 | 0.00 | 0.13 | 28-AUG-06:03 |
September | 0.148247E+10 | 0.00 | 117.86 | 121204.76 | 21-SEP-06:03 | 0.00 | 33.01 | 37.25 | 0.01 | 0.00 | 0.00 | 0.37 | 21-SEP-06:03 |
October | 0.121271E+11 | 0.00 | 283.48 | 265998.03 | 23-OCT-05:11 | 0.00 | 27.36 | 38.87 | 0.04 | 0.00 | 0.01 | 0.80 | 23-OCT-05:11 |
November | 0.271910E+11 | 0.00 | 355.31 | 241741.62 | 13-NOV-06:11 | 0.00 | 29.07 | 43.56 | 0.10 | 0.00 | 0.03 | 0.73 | 13-NOV-06:11 |
December | 0.493787E+11 | 0.00 | 405.61 | 225589.38 | 08-DEC-06:11 | 0.00 | 32.36 | 47.42 | 0.18 | 0.00 | 0.06 | 0.68 | 08-DEC-06:11 |
Annual Sum or Average | 0.206924E+12 | 0.00 | 2859.54 | 0.00 | 32.22 | 41.27 | 0.06 | 0.00 | 0.02 | ||||
Minimum of Months | 0.456678E+09 | 0.00 | 60.31 | 43669.10 | 0.00 | 27.36 | 34.85 | 0.00 | 0.00 | 0.00 | 0.13 | ||
Maximum of Months | 0.493787E+11 | 0.00 | 405.61 | 265998.03 | 0.00 | 38.12 | 47.42 | 0.18 | 0.00 | 0.06 | 0.80 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.206650E+10 | 0.521256E+09 | 49.44 | 0.197043E+10 | 96070467.49 | 0.00 | 0.87 | 28-APR-15:00 | 0.00 | 01-APR-00:10 | 27385.33 | 28-APR-15:00 | 27372.14 | 28-APR-15:00 | 7715.12 | 28-APR-07:55 | 6303.74 | 28-APR-15:00 | 0.00 |
May | 0.314890E+10 | 0.767528E+09 | 63.37 | 0.262242E+10 | 0.526479E+09 | 0.00 | 1.00 | 22-MAY-13:30 | 0.00 | 01-MAY-00:10 | 47544.33 | 22-MAY-15:00 | 46313.14 | 22-MAY-15:00 | 6547.35 | 23-MAY-14:50 | 10590.90 | 22-MAY-15:00 | 0.00 |
June | 0.103307E+11 | 0.245625E+10 | 158.27 | 0.839015E+10 | 0.194058E+10 | 0.00 | 1.00 | 12-JUN-12:05 | 0.00 | 01-JUN-00:10 | 64695.69 | 13-JUN-16:00 | 59305.05 | 13-JUN-16:00 | 22100.00 | 25-JUN-17:52 | 15309.92 | 13-JUN-16:00 | 0.00 |
July | 0.180062E+11 | 0.434697E+10 | 276.29 | 0.143438E+11 | 0.366236E+10 | 0.00 | 1.00 | 10-JUL-07:05 | 0.00 | 01-JUL-00:10 | 61236.99 | 21-JUL-16:00 | 61236.99 | 21-JUL-16:00 | 13130.76 | 24-JUL-15:30 | 15063.60 | 21-JUL-16:00 | 0.00 |
August | 0.236780E+11 | 0.568705E+10 | 356.36 | 0.183587E+11 | 0.531927E+10 | 0.00 | 1.00 | 09-AUG-15:50 | 0.00 | 01-AUG-00:10 | 59165.27 | 14-AUG-15:30 | 57352.29 | 14-AUG-16:00 | 14843.73 | 08-AUG-13:00 | 13771.98 | 14-AUG-16:00 | 0.00 |
September | 0.118658E+11 | 0.285051E+10 | 203.40 | 0.960512E+10 | 0.226064E+10 | 0.00 | 1.00 | 11-SEP-12:50 | 0.00 | 01-SEP-00:10 | 52348.03 | 13-SEP-15:30 | 47182.54 | 13-SEP-15:30 | 12495.03 | 12-SEP-14:00 | 11599.38 | 13-SEP-15:30 | 0.00 |
October | 0.529298E+09 | 0.142679E+09 | 24.00 | 0.499050E+09 | 30248130.55 | 0.00 | 0.46 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 12820.26 | 07-OCT-15:00 | 12820.26 | 07-OCT-15:00 | 2996.18 | 17-OCT-15:00 | 3301.99 | 07-OCT-15:00 | 0.00 |
November | 9395631.83 | 2614783.77 | 0.83 | 6646229.50 | 2749402.33 | 0.00 | 0.20 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 5219.58 | 24-NOV-12:00 | 3828.82 | 24-NOV-12:00 | 1390.77 | 24-NOV-12:00 | 1433.31 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.696347E+11 | 0.167749E+11 | 1131.97 | 0.557963E+11 | 0.138384E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.236780E+11 | 0.568705E+10 | 356.36 | 0.183587E+11 | 0.531927E+10 | 0.00 | 1.00 | 0.00 | 64695.69 | 61236.99 | 22100.00 | 15309.92 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 599235.71 | 169043.35 | 0.11 | 504384.31 | 94851.40 | 0.00 | 0.11 | 17-JAN-07:05 | 0.00 | 01-JAN-00:05 | 2668.73 | 17-JAN-07:05 | 2224.07 | 17-JAN-07:05 | 444.66 | 17-JAN-07:05 | 748.42 | 17-JAN-07:05 | 0.00 |
February | 93089.53 | 26658.53 | 0.06 | 86203.43 | 6886.10 | 0.00 | 0.02 | 14-FEB-07:04 | 0.00 | 01-FEB-00:10 | 525.01 | 14-FEB-07:04 | 493.09 | 14-FEB-07:04 | 35.65 | 09-FEB-07:03 | 150.27 | 14-FEB-07:04 | 0.00 |
March | 109180.65 | 31253.87 | 0.07 | 105732.42 | 3448.23 | 0.00 | 0.03 | 03-MAR-07:03 | 0.00 | 01-MAR-00:10 | 660.83 | 03-MAR-07:03 | 621.83 | 03-MAR-07:03 | 39.00 | 03-MAR-07:03 | 188.90 | 03-MAR-07:03 | 0.00 |
April | 0.208260E+10 | 0.522364E+09 | 51.39 | 0.199079E+10 | 91805193.02 | 0.00 | 0.96 | 30-APR-14:53 | 0.00 | 01-APR-00:10 | 29056.51 | 30-APR-14:53 | 29056.51 | 30-APR-14:53 | 6005.64 | 28-APR-07:55 | 6558.39 | 30-APR-14:53 | 0.00 |
May | 0.305179E+10 | 0.742732E+09 | 66.07 | 0.254825E+10 | 0.503539E+09 | 0.00 | 1.00 | 22-MAY-13:10 | 0.00 | 01-MAY-00:10 | 46574.70 | 22-MAY-15:00 | 45190.88 | 22-MAY-15:00 | 6415.29 | 23-MAY-15:20 | 10374.00 | 22-MAY-15:00 | 0.00 |
June | 0.100016E+11 | 0.237770E+10 | 163.59 | 0.813834E+10 | 0.186325E+10 | 0.00 | 1.00 | 12-JUN-12:05 | 0.00 | 01-JUN-00:10 | 72319.64 | 25-JUN-17:52 | 57852.44 | 13-JUN-16:00 | 40721.46 | 25-JUN-17:52 | 16065.12 | 25-JUN-17:52 | 0.00 |
July | 0.169165E+11 | 0.408881E+10 | 284.82 | 0.134244E+11 | 0.349213E+10 | 0.00 | 1.00 | 06-JUL-14:05 | 0.00 | 01-JUL-00:10 | 58458.79 | 21-JUL-16:00 | 58390.56 | 21-JUL-16:00 | 12628.65 | 24-JUL-15:30 | 14379.55 | 21-JUL-16:00 | 0.00 |
August | 0.217435E+11 | 0.524420E+10 | 367.08 | 0.167654E+11 | 0.497810E+10 | 0.00 | 1.00 | 10-AUG-14:05 | 0.00 | 01-AUG-00:10 | 55486.49 | 14-AUG-14:05 | 52930.44 | 14-AUG-16:00 | 12998.43 | 08-AUG-13:00 | 12758.91 | 14-AUG-16:00 | 0.00 |
September | 0.108115E+11 | 0.260578E+10 | 208.07 | 0.871157E+10 | 0.209991E+10 | 0.00 | 1.00 | 11-SEP-12:50 | 0.00 | 01-SEP-00:10 | 49751.42 | 13-SEP-14:05 | 44875.81 | 13-SEP-14:05 | 11927.94 | 12-SEP-14:00 | 11023.83 | 13-SEP-14:05 | 0.00 |
October | 0.443895E+09 | 0.120258E+09 | 23.71 | 0.418318E+09 | 25577102.53 | 0.00 | 0.45 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 11844.17 | 07-OCT-15:00 | 11844.17 | 07-OCT-15:00 | 2157.87 | 17-OCT-15:00 | 3057.36 | 07-OCT-15:00 | 0.00 |
November | 7609906.42 | 2128732.55 | 0.94 | 5322539.20 | 2287367.23 | 0.00 | 0.17 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 4267.05 | 24-NOV-12:00 | 3062.38 | 24-NOV-12:00 | 1204.67 | 24-NOV-12:00 | 1178.91 | 24-NOV-12:00 | 0.00 |
December | 176862.65 | 50551.72 | 0.08 | 156413.68 | 20448.97 | 0.00 | 0.04 | 01-DEC-07:03 | 0.00 | 01-DEC-00:10 | 896.41 | 01-DEC-07:03 | 783.77 | 01-DEC-07:03 | 112.65 | 01-DEC-07:03 | 255.66 | 01-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.650599E+11 | 0.157043E+11 | 1165.98 | 0.520032E+11 | 0.130567E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 93089.53 | 26658.53 | 0.06 | 86203.43 | 3448.23 | 0.00 | 0.02 | 0.00 | 525.01 | 493.09 | 35.65 | 150.27 | 0.00 | ||||||
Maximum of Months | 0.217435E+11 | 0.524420E+10 | 367.08 | 0.167654E+11 | 0.497810E+10 | 0.00 | 1.00 | 0.00 | 72319.64 | 58390.56 | 40721.46 | 16065.12 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1468943.20 | 419817.52 | 0.52 | 1437794.07 | 31149.13 | 0.00 | 0.03 | 12-JAN-05:50 | 0.00 | 01-JAN-00:05 | 940.19 | 12-JAN-05:50 | 940.19 | 12-JAN-05:50 | 155.75 | 30-JAN-06:07 | 268.40 | 12-JAN-05:50 | 0.00 |
February | 245709.20 | 70402.13 | 0.16 | 235752.56 | 9956.64 | 0.00 | 0.02 | 18-FEB-05:08 | 0.00 | 01-FEB-00:10 | 693.17 | 18-FEB-05:08 | 678.84 | 18-FEB-05:08 | 20.42 | 17-FEB-05:08 | 198.28 | 18-FEB-05:08 | 0.00 |
March | 94490.48 | 27077.58 | 0.06 | 88359.15 | 6131.33 | 0.00 | 0.02 | 06-MAR-06:07 | 0.00 | 01-MAR-00:10 | 472.45 | 06-MAR-06:07 | 441.80 | 06-MAR-06:07 | 30.66 | 06-MAR-06:07 | 135.39 | 06-MAR-06:07 | 0.00 |
April | 0.228547E+10 | 0.574568E+09 | 50.67 | 0.216842E+10 | 0.117047E+09 | 0.00 | 1.00 | 30-APR-14:53 | 0.00 | 01-APR-00:10 | 41669.84 | 30-APR-14:53 | 41669.84 | 30-APR-14:53 | 4756.79 | 28-APR-07:55 | 9286.89 | 30-APR-14:53 | 0.00 |
May | 0.334734E+10 | 0.820881E+09 | 65.51 | 0.277235E+10 | 0.574990E+09 | 0.00 | 1.00 | 22-MAY-13:20 | 0.00 | 01-MAY-00:10 | 59971.54 | 22-MAY-15:00 | 59930.87 | 22-MAY-15:00 | 7330.14 | 23-MAY-14:50 | 13394.64 | 22-MAY-15:00 | 0.00 |
June | 0.110836E+11 | 0.264608E+10 | 161.56 | 0.904137E+10 | 0.204221E+10 | 0.00 | 1.00 | 12-JUN-12:20 | 0.00 | 01-JUN-00:10 | 77356.91 | 13-JUN-15:30 | 72032.43 | 13-JUN-15:40 | 22337.61 | 25-JUN-18:03 | 18249.85 | 13-JUN-16:00 | 0.00 |
July | 0.185007E+11 | 0.450788E+10 | 281.30 | 0.146785E+11 | 0.382218E+10 | 0.00 | 1.00 | 10-JUL-09:40 | 0.00 | 01-JUL-00:10 | 72479.77 | 21-JUL-16:00 | 72479.77 | 21-JUL-16:00 | 15980.89 | 23-JUL-16:02 | 17801.80 | 21-JUL-16:00 | 0.00 |
August | 0.225397E+11 | 0.550955E+10 | 361.78 | 0.171473E+11 | 0.539237E+10 | 0.00 | 1.00 | 14-AUG-10:40 | 0.00 | 01-AUG-00:10 | 66709.46 | 14-AUG-15:20 | 64449.70 | 14-AUG-15:40 | 13559.09 | 18-AUG-15:30 | 15410.43 | 14-AUG-15:40 | 0.00 |
September | 0.106884E+11 | 0.261468E+10 | 201.64 | 0.847491E+10 | 0.221349E+10 | 0.00 | 1.00 | 11-SEP-13:40 | 0.00 | 01-SEP-00:10 | 50070.40 | 13-SEP-15:20 | 45427.07 | 13-SEP-15:00 | 12424.21 | 12-SEP-14:00 | 11098.70 | 13-SEP-15:20 | 0.00 |
October | 0.432265E+09 | 0.118230E+09 | 23.50 | 0.399360E+09 | 32904742.87 | 0.00 | 0.40 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 12263.23 | 07-OCT-15:00 | 12263.23 | 07-OCT-15:00 | 2345.46 | 17-OCT-15:00 | 3206.03 | 07-OCT-15:00 | 0.00 |
November | 8499421.28 | 2384007.74 | 1.07 | 5943032.22 | 2556389.06 | 0.00 | 0.16 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 4604.69 | 24-NOV-12:00 | 3260.37 | 24-NOV-12:00 | 1344.31 | 24-NOV-12:00 | 1276.54 | 24-NOV-12:00 | 0.00 |
December | 662793.40 | 189967.42 | 0.43 | 623124.53 | 39668.87 | 0.00 | 0.02 | 18-DEC-06:01 | 0.00 | 01-DEC-00:10 | 684.92 | 18-DEC-06:01 | 641.15 | 18-DEC-06:01 | 62.61 | 25-DEC-17:40 | 195.93 | 18-DEC-06:01 | 0.00 |
Annual Sum or Average | 0.688884E+11 | 0.167950E+11 | 1148.19 | 0.546906E+11 | 0.141978E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 94490.48 | 27077.58 | 0.06 | 88359.15 | 6131.33 | 0.00 | 0.02 | 0.00 | 472.45 | 441.80 | 20.42 | 135.39 | 0.00 | ||||||
Maximum of Months | 0.225397E+11 | 0.550955E+10 | 361.78 | 0.171473E+11 | 0.539237E+10 | 0.00 | 1.00 | 0.00 | 77356.91 | 72479.77 | 22337.61 | 18249.85 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.74 | 0.00 | 251.74 | 6.04 | 1976.96 | 0.00 | 0.00 | 0.00 |
February | 393.10 | 0.00 | 393.10 | 20.04 | 1884.70 | 0.00 | 0.00 | 0.00 |
March | 543.99 | 0.00 | 543.99 | 99.43 | 1543.00 | 0.00 | 0.00 | 0.00 |
April | 885.69 | 3.96 | 881.73 | 421.01 | 1258.38 | 0.00 | 0.00 | 0.00 |
May | 1107.34 | 53.42 | 1053.92 | 506.46 | 1026.86 | 0.00 | 0.00 | 0.00 |
June | 1224.10 | 76.76 | 1147.34 | 817.21 | 806.78 | 0.00 | 0.00 | 0.00 |
July | 1161.12 | 66.20 | 1094.92 | 862.08 | 740.45 | 0.00 | 0.00 | 0.00 |
August | 912.70 | 14.30 | 898.40 | 665.14 | 820.99 | 0.00 | 0.00 | 0.00 |
September | 694.69 | 0.15 | 694.54 | 422.51 | 1077.22 | 0.00 | 0.00 | 0.00 |
October | 445.15 | 0.00 | 445.15 | 121.42 | 1409.35 | 0.00 | 0.00 | 0.00 |
November | 267.47 | 0.00 | 267.47 | 8.44 | 1746.33 | 0.00 | 0.00 | 0.00 |
December | 182.15 | 0.00 | 182.15 | 0.05 | 2121.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 673.69 | 18.02 | 655.66 | 330.73 | 1365.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 182.15 | 0.00 | 182.15 | 0.05 | 740.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1224.10 | 76.76 | 1147.34 | 862.08 | 2121.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 343.03 | 137.79 | 205.23 | 167.55 | 1228.73 | 0.00 | 0.00 | 0.00 |
February | 511.51 | 188.96 | 322.56 | 284.48 | 1184.32 | 0.00 | 0.00 | 0.00 |
March | 534.54 | 105.34 | 429.21 | 255.44 | 966.69 | 0.00 | 0.00 | 0.00 |
April | 1435.29 | 674.45 | 760.84 | 1376.08 | 786.77 | 0.00 | 0.00 | 0.00 |
May | 1509.17 | 658.12 | 851.05 | 1389.25 | 694.77 | 0.00 | 0.00 | 0.00 |
June | 1493.80 | 596.60 | 897.19 | 1492.02 | 546.10 | 0.00 | 0.00 | 0.00 |
July | 1524.87 | 648.07 | 876.81 | 1611.59 | 501.81 | 0.00 | 0.00 | 0.00 |
August | 1444.48 | 690.16 | 754.33 | 1589.46 | 535.85 | 0.00 | 0.00 | 0.00 |
September | 1300.81 | 691.71 | 609.10 | 1375.13 | 675.82 | 0.00 | 0.00 | 0.00 |
October | 627.92 | 260.22 | 367.69 | 499.21 | 898.68 | 0.00 | 0.00 | 0.00 |
November | 327.35 | 111.57 | 215.79 | 156.99 | 1101.46 | 0.00 | 0.00 | 0.00 |
December | 242.61 | 90.20 | 152.41 | 100.74 | 1339.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 942.64 | 404.95 | 537.69 | 860.23 | 870.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 242.61 | 90.20 | 152.41 | 100.74 | 501.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1524.87 | 691.71 | 897.19 | 1611.59 | 1339.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1429.18 | 925.17 | 504.01 | 1312.57 | 1742.18 | 0.00 | 0.00 | 0.00 |
February | 1745.48 | 1065.11 | 680.37 | 1643.93 | 1740.27 | 0.00 | 0.00 | 0.00 |
March | 1079.17 | 314.21 | 764.97 | 757.72 | 1469.53 | 0.00 | 0.00 | 0.00 |
April | 2241.00 | 1012.90 | 1228.10 | 2388.19 | 1292.30 | 0.00 | 0.00 | 0.00 |
May | 1853.51 | 603.44 | 1250.08 | 1768.96 | 1155.48 | 0.00 | 0.00 | 0.00 |
June | 1707.49 | 413.31 | 1294.18 | 1709.65 | 893.38 | 0.00 | 0.00 | 0.00 |
July | 1850.03 | 579.35 | 1270.67 | 2047.43 | 824.74 | 0.00 | 0.00 | 0.00 |
August | 2167.82 | 975.16 | 1192.66 | 2594.36 | 878.88 | 0.00 | 0.00 | 0.00 |
September | 2561.79 | 1500.74 | 1061.06 | 3048.48 | 1098.28 | 0.00 | 0.00 | 0.00 |
October | 1760.06 | 1028.67 | 731.39 | 1841.96 | 1381.68 | 0.00 | 0.00 | 0.00 |
November | 1247.88 | 759.11 | 488.76 | 1156.33 | 1632.27 | 0.00 | 0.00 | 0.00 |
December | 989.06 | 633.69 | 355.36 | 880.83 | 1981.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1716.74 | 814.40 | 902.35 | 1760.08 | 1338.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 989.06 | 314.21 | 355.36 | 757.72 | 824.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2561.79 | 1500.74 | 1294.18 | 3048.48 | 1981.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 333.58 | 110.22 | 223.36 | 168.05 | 1246.76 | 0.00 | 0.00 | 0.00 |
February | 590.62 | 249.38 | 341.24 | 411.39 | 1207.33 | 0.00 | 0.00 | 0.00 |
March | 534.05 | 102.16 | 431.88 | 252.46 | 983.02 | 0.00 | 0.00 | 0.00 |
April | 1260.10 | 500.52 | 759.58 | 1185.12 | 834.64 | 0.00 | 0.00 | 0.00 |
May | 1478.39 | 601.16 | 877.23 | 1365.12 | 733.82 | 0.00 | 0.00 | 0.00 |
June | 1596.50 | 657.21 | 939.28 | 1634.37 | 582.34 | 0.00 | 0.00 | 0.00 |
July | 1625.96 | 716.89 | 909.08 | 1767.81 | 539.17 | 0.00 | 0.00 | 0.00 |
August | 1365.70 | 591.31 | 774.39 | 1507.04 | 576.92 | 0.00 | 0.00 | 0.00 |
September | 1095.65 | 491.31 | 604.34 | 1155.69 | 721.65 | 0.00 | 0.00 | 0.00 |
October | 584.49 | 210.18 | 374.31 | 461.13 | 930.07 | 0.00 | 0.00 | 0.00 |
November | 316.31 | 92.33 | 223.97 | 161.38 | 1134.91 | 0.00 | 0.00 | 0.00 |
December | 179.04 | 37.78 | 141.26 | 51.70 | 1395.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 914.33 | 363.52 | 550.81 | 844.90 | 905.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.04 | 37.78 | 141.26 | 51.70 | 539.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1625.96 | 716.89 | 939.28 | 1767.81 | 1395.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.91 | 0.00 | 83.91 | 1.83 | 688.31 | 0.00 | 0.00 | 0.00 |
February | 131.03 | 0.00 | 131.03 | 5.83 | 655.64 | 0.00 | 0.00 | 0.00 |
March | 181.32 | 0.00 | 181.32 | 35.93 | 529.83 | 0.00 | 0.00 | 0.00 |
April | 295.22 | 1.32 | 293.90 | 155.39 | 421.83 | 0.00 | 0.00 | 0.00 |
May | 369.10 | 17.81 | 351.29 | 185.85 | 345.62 | 0.00 | 0.00 | 0.00 |
June | 408.02 | 25.59 | 382.43 | 289.39 | 271.25 | 0.00 | 0.00 | 0.00 |
July | 387.03 | 22.07 | 364.96 | 298.66 | 252.21 | 0.00 | 0.00 | 0.00 |
August | 304.22 | 4.77 | 299.46 | 231.08 | 282.39 | 0.00 | 0.00 | 0.00 |
September | 231.56 | 0.05 | 231.50 | 143.29 | 380.16 | 0.00 | 0.00 | 0.00 |
October | 148.38 | 0.00 | 148.38 | 37.60 | 509.65 | 0.00 | 0.00 | 0.00 |
November | 89.15 | 0.00 | 89.15 | 1.85 | 633.47 | 0.00 | 0.00 | 0.00 |
December | 60.71 | 0.00 | 60.71 | 0.00 | 757.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.55 | 6.01 | 218.55 | 116.11 | 476.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.71 | 0.00 | 60.71 | 0.00 | 252.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.02 | 25.59 | 382.43 | 298.66 | 757.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.91 | 0.00 | 83.91 | 1.83 | 688.35 | 0.00 | 0.00 | 0.00 |
February | 131.04 | 0.00 | 131.04 | 5.83 | 655.69 | 0.00 | 0.00 | 0.00 |
March | 181.33 | 0.00 | 181.33 | 35.93 | 529.87 | 0.00 | 0.00 | 0.00 |
April | 295.23 | 1.32 | 293.91 | 155.39 | 421.86 | 0.00 | 0.00 | 0.00 |
May | 369.12 | 17.81 | 351.31 | 185.86 | 345.65 | 0.00 | 0.00 | 0.00 |
June | 408.04 | 25.59 | 382.45 | 289.40 | 271.27 | 0.00 | 0.00 | 0.00 |
July | 387.05 | 22.07 | 364.98 | 298.67 | 252.22 | 0.00 | 0.00 | 0.00 |
August | 304.24 | 4.77 | 299.47 | 231.09 | 282.41 | 0.00 | 0.00 | 0.00 |
September | 231.57 | 0.05 | 231.52 | 143.30 | 380.18 | 0.00 | 0.00 | 0.00 |
October | 148.39 | 0.00 | 148.39 | 37.60 | 509.68 | 0.00 | 0.00 | 0.00 |
November | 89.16 | 0.00 | 89.16 | 1.85 | 633.51 | 0.00 | 0.00 | 0.00 |
December | 60.72 | 0.00 | 60.72 | 0.00 | 757.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.56 | 6.01 | 218.56 | 116.12 | 476.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.72 | 0.00 | 60.72 | 0.00 | 252.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.04 | 25.59 | 382.45 | 298.67 | 757.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.91 | 0.00 | 83.91 | 1.83 | 688.35 | 0.00 | 0.00 | 0.00 |
February | 131.04 | 0.00 | 131.04 | 5.83 | 655.69 | 0.00 | 0.00 | 0.00 |
March | 181.33 | 0.00 | 181.33 | 35.93 | 529.87 | 0.00 | 0.00 | 0.00 |
April | 295.23 | 1.32 | 293.91 | 155.39 | 421.86 | 0.00 | 0.00 | 0.00 |
May | 369.12 | 17.81 | 351.31 | 185.86 | 345.65 | 0.00 | 0.00 | 0.00 |
June | 408.04 | 25.59 | 382.45 | 289.40 | 271.27 | 0.00 | 0.00 | 0.00 |
July | 387.05 | 22.07 | 364.98 | 298.67 | 252.22 | 0.00 | 0.00 | 0.00 |
August | 304.24 | 4.77 | 299.47 | 231.09 | 282.41 | 0.00 | 0.00 | 0.00 |
September | 231.57 | 0.05 | 231.52 | 143.30 | 380.18 | 0.00 | 0.00 | 0.00 |
October | 148.39 | 0.00 | 148.39 | 37.60 | 509.68 | 0.00 | 0.00 | 0.00 |
November | 89.16 | 0.00 | 89.16 | 1.85 | 633.51 | 0.00 | 0.00 | 0.00 |
December | 60.72 | 0.00 | 60.72 | 0.00 | 757.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.56 | 6.01 | 218.56 | 116.12 | 476.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.72 | 0.00 | 60.72 | 0.00 | 252.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.04 | 25.59 | 382.45 | 298.67 | 757.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 329.99 | 132.56 | 197.43 | 159.06 | 1240.25 | 0.00 | 0.00 | 0.00 |
February | 492.08 | 181.78 | 310.30 | 269.70 | 1193.23 | 0.00 | 0.00 | 0.00 |
March | 514.23 | 101.34 | 412.89 | 250.98 | 961.36 | 0.00 | 0.00 | 0.00 |
April | 1380.75 | 648.82 | 731.93 | 1343.68 | 785.33 | 0.00 | 0.00 | 0.00 |
May | 1451.81 | 633.11 | 818.70 | 1356.36 | 696.29 | 0.00 | 0.00 | 0.00 |
June | 1437.03 | 573.94 | 863.10 | 1457.00 | 544.44 | 0.00 | 0.00 | 0.00 |
July | 1466.92 | 623.44 | 843.48 | 1565.22 | 509.27 | 0.00 | 0.00 | 0.00 |
August | 1389.59 | 663.93 | 725.66 | 1538.45 | 551.87 | 0.00 | 0.00 | 0.00 |
September | 1251.37 | 665.42 | 585.95 | 1321.83 | 710.33 | 0.00 | 0.00 | 0.00 |
October | 604.05 | 250.34 | 353.72 | 470.19 | 946.44 | 0.00 | 0.00 | 0.00 |
November | 314.91 | 107.33 | 207.59 | 144.57 | 1154.60 | 0.00 | 0.00 | 0.00 |
December | 233.39 | 86.77 | 146.62 | 92.20 | 1379.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 906.82 | 389.56 | 517.26 | 832.80 | 887.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.39 | 86.77 | 146.62 | 92.20 | 509.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1466.92 | 665.42 | 863.10 | 1565.22 | 1379.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.05 | 5.24 | 7.81 | 6.29 | 49.04 | 0.00 | 0.00 | 0.00 |
February | 19.46 | 7.19 | 12.27 | 10.66 | 47.18 | 0.00 | 0.00 | 0.00 |
March | 20.33 | 4.01 | 16.33 | 9.92 | 38.01 | 0.00 | 0.00 | 0.00 |
April | 54.59 | 25.65 | 28.94 | 53.13 | 31.05 | 0.00 | 0.00 | 0.00 |
May | 57.40 | 25.03 | 32.37 | 53.63 | 27.53 | 0.00 | 0.00 | 0.00 |
June | 56.82 | 22.69 | 34.13 | 57.61 | 21.53 | 0.00 | 0.00 | 0.00 |
July | 58.00 | 24.65 | 33.35 | 61.89 | 20.14 | 0.00 | 0.00 | 0.00 |
August | 54.94 | 26.25 | 28.69 | 60.83 | 21.82 | 0.00 | 0.00 | 0.00 |
September | 49.48 | 26.31 | 23.17 | 52.26 | 28.09 | 0.00 | 0.00 | 0.00 |
October | 23.88 | 9.90 | 13.99 | 18.59 | 37.42 | 0.00 | 0.00 | 0.00 |
November | 12.45 | 4.24 | 8.21 | 5.72 | 45.65 | 0.00 | 0.00 | 0.00 |
December | 9.23 | 3.43 | 5.80 | 3.65 | 54.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.85 | 15.40 | 20.45 | 32.93 | 35.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.23 | 3.43 | 5.80 | 3.65 | 20.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.00 | 26.31 | 34.13 | 61.89 | 54.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 476.41 | 308.40 | 168.01 | 440.11 | 612.37 | 0.00 | 0.00 | 0.00 |
February | 581.84 | 355.05 | 226.79 | 553.83 | 614.88 | 0.00 | 0.00 | 0.00 |
March | 359.73 | 104.74 | 255.00 | 261.02 | 504.31 | 0.00 | 0.00 | 0.00 |
April | 747.02 | 337.64 | 409.38 | 814.75 | 446.08 | 0.00 | 0.00 | 0.00 |
May | 617.85 | 201.15 | 416.70 | 609.20 | 394.49 | 0.00 | 0.00 | 0.00 |
June | 569.18 | 137.77 | 431.40 | 590.22 | 300.85 | 0.00 | 0.00 | 0.00 |
July | 616.69 | 193.12 | 423.57 | 696.93 | 285.07 | 0.00 | 0.00 | 0.00 |
August | 722.63 | 325.06 | 397.56 | 874.48 | 314.25 | 0.00 | 0.00 | 0.00 |
September | 853.95 | 500.26 | 353.69 | 1020.48 | 404.73 | 0.00 | 0.00 | 0.00 |
October | 586.70 | 342.90 | 243.80 | 613.58 | 509.93 | 0.00 | 0.00 | 0.00 |
November | 415.97 | 253.05 | 162.93 | 385.24 | 594.74 | 0.00 | 0.00 | 0.00 |
December | 329.69 | 211.24 | 118.46 | 293.47 | 701.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 572.26 | 271.47 | 300.79 | 595.29 | 472.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.69 | 104.74 | 118.46 | 261.02 | 285.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 853.95 | 500.26 | 431.40 | 1020.48 | 701.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 476.41 | 308.40 | 168.01 | 440.11 | 612.37 | 0.00 | 0.00 | 0.00 |
February | 581.84 | 355.05 | 226.79 | 553.83 | 614.88 | 0.00 | 0.00 | 0.00 |
March | 359.73 | 104.74 | 255.00 | 261.02 | 504.31 | 0.00 | 0.00 | 0.00 |
April | 747.02 | 337.64 | 409.38 | 814.75 | 446.08 | 0.00 | 0.00 | 0.00 |
May | 617.85 | 201.15 | 416.70 | 609.20 | 394.49 | 0.00 | 0.00 | 0.00 |
June | 569.18 | 137.77 | 431.40 | 590.22 | 300.85 | 0.00 | 0.00 | 0.00 |
July | 616.69 | 193.12 | 423.57 | 696.93 | 285.07 | 0.00 | 0.00 | 0.00 |
August | 722.63 | 325.06 | 397.56 | 874.48 | 314.25 | 0.00 | 0.00 | 0.00 |
September | 853.95 | 500.26 | 353.69 | 1020.48 | 404.73 | 0.00 | 0.00 | 0.00 |
October | 586.70 | 342.90 | 243.80 | 613.58 | 509.93 | 0.00 | 0.00 | 0.00 |
November | 415.97 | 253.05 | 162.93 | 385.24 | 594.74 | 0.00 | 0.00 | 0.00 |
December | 329.69 | 211.24 | 118.46 | 293.47 | 701.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 572.26 | 271.47 | 300.79 | 595.29 | 472.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.69 | 104.74 | 118.46 | 261.02 | 285.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 853.95 | 500.26 | 431.40 | 1020.48 | 701.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 476.38 | 308.38 | 168.00 | 440.08 | 612.33 | 0.00 | 0.00 | 0.00 |
February | 581.81 | 355.03 | 226.78 | 553.80 | 614.84 | 0.00 | 0.00 | 0.00 |
March | 359.71 | 104.73 | 254.98 | 261.01 | 504.28 | 0.00 | 0.00 | 0.00 |
April | 746.97 | 337.62 | 409.35 | 814.70 | 446.05 | 0.00 | 0.00 | 0.00 |
May | 617.81 | 201.14 | 416.68 | 609.16 | 394.47 | 0.00 | 0.00 | 0.00 |
June | 569.14 | 137.76 | 431.38 | 590.19 | 300.83 | 0.00 | 0.00 | 0.00 |
July | 616.65 | 193.11 | 423.54 | 696.89 | 285.05 | 0.00 | 0.00 | 0.00 |
August | 722.58 | 325.04 | 397.54 | 874.42 | 314.23 | 0.00 | 0.00 | 0.00 |
September | 853.90 | 500.23 | 353.67 | 1020.42 | 404.70 | 0.00 | 0.00 | 0.00 |
October | 586.66 | 342.88 | 243.79 | 613.54 | 509.89 | 0.00 | 0.00 | 0.00 |
November | 415.94 | 253.03 | 162.92 | 385.22 | 594.71 | 0.00 | 0.00 | 0.00 |
December | 329.67 | 211.22 | 118.45 | 293.45 | 701.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 572.23 | 271.46 | 300.77 | 595.25 | 472.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.67 | 104.73 | 118.45 | 261.01 | 285.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 853.90 | 500.23 | 431.38 | 1020.42 | 701.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 320.90 | 106.03 | 214.87 | 162.74 | 1259.10 | 0.00 | 0.00 | 0.00 |
February | 568.17 | 239.90 | 328.27 | 399.55 | 1224.10 | 0.00 | 0.00 | 0.00 |
March | 513.75 | 98.28 | 415.47 | 254.03 | 979.45 | 0.00 | 0.00 | 0.00 |
April | 1212.21 | 481.50 | 730.71 | 1171.10 | 829.99 | 0.00 | 0.00 | 0.00 |
May | 1422.20 | 578.32 | 843.88 | 1344.41 | 736.46 | 0.00 | 0.00 | 0.00 |
June | 1535.82 | 632.24 | 903.58 | 1601.22 | 586.39 | 0.00 | 0.00 | 0.00 |
July | 1564.17 | 689.65 | 874.52 | 1722.41 | 549.54 | 0.00 | 0.00 | 0.00 |
August | 1313.80 | 568.84 | 744.96 | 1466.21 | 593.34 | 0.00 | 0.00 | 0.00 |
September | 1054.02 | 472.64 | 581.37 | 1116.96 | 751.30 | 0.00 | 0.00 | 0.00 |
October | 562.28 | 202.19 | 360.08 | 440.76 | 975.51 | 0.00 | 0.00 | 0.00 |
November | 304.28 | 88.82 | 215.46 | 153.47 | 1188.10 | 0.00 | 0.00 | 0.00 |
December | 172.23 | 36.35 | 135.89 | 48.30 | 1432.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 879.58 | 349.71 | 529.88 | 824.86 | 923.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 172.23 | 36.35 | 135.89 | 48.30 | 549.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1564.17 | 689.65 | 903.58 | 1722.41 | 1432.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.69 | 4.19 | 8.50 | 6.43 | 49.78 | 0.00 | 0.00 | 0.00 |
February | 22.47 | 9.49 | 12.98 | 15.80 | 48.40 | 0.00 | 0.00 | 0.00 |
March | 20.31 | 3.89 | 16.43 | 10.04 | 38.73 | 0.00 | 0.00 | 0.00 |
April | 47.93 | 19.04 | 28.89 | 46.30 | 32.82 | 0.00 | 0.00 | 0.00 |
May | 56.23 | 22.87 | 33.37 | 53.16 | 29.12 | 0.00 | 0.00 | 0.00 |
June | 60.73 | 25.00 | 35.73 | 63.31 | 23.19 | 0.00 | 0.00 | 0.00 |
July | 61.85 | 27.27 | 34.58 | 68.10 | 21.73 | 0.00 | 0.00 | 0.00 |
August | 51.95 | 22.49 | 29.46 | 57.97 | 23.46 | 0.00 | 0.00 | 0.00 |
September | 41.67 | 18.69 | 22.99 | 44.16 | 29.71 | 0.00 | 0.00 | 0.00 |
October | 22.23 | 7.99 | 14.24 | 17.43 | 38.57 | 0.00 | 0.00 | 0.00 |
November | 12.03 | 3.51 | 8.52 | 6.07 | 46.98 | 0.00 | 0.00 | 0.00 |
December | 6.81 | 1.44 | 5.37 | 1.91 | 56.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.78 | 13.83 | 20.95 | 32.61 | 36.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.81 | 1.44 | 5.37 | 1.91 | 21.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.85 | 27.27 | 35.73 | 68.10 | 56.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.74 | 0.00 | 251.74 | 3.42 | 2128.07 | 0.00 | 0.00 | 0.00 |
February | 393.10 | 0.00 | 393.10 | 12.17 | 2048.40 | 0.00 | 0.00 | 0.00 |
March | 543.99 | 0.00 | 543.99 | 81.01 | 1674.07 | 0.00 | 0.00 | 0.00 |
April | 885.69 | 3.96 | 881.73 | 395.45 | 1362.69 | 0.00 | 0.00 | 0.00 |
May | 1107.34 | 53.42 | 1053.92 | 473.53 | 1115.65 | 0.00 | 0.00 | 0.00 |
June | 1224.10 | 76.76 | 1147.34 | 791.16 | 865.56 | 0.00 | 0.00 | 0.00 |
July | 1161.12 | 66.20 | 1094.92 | 840.08 | 793.90 | 0.00 | 0.00 | 0.00 |
August | 912.70 | 14.30 | 898.40 | 645.30 | 891.80 | 0.00 | 0.00 | 0.00 |
September | 694.69 | 0.15 | 694.54 | 395.06 | 1183.35 | 0.00 | 0.00 | 0.00 |
October | 445.15 | 0.00 | 445.15 | 96.22 | 1561.00 | 0.00 | 0.00 | 0.00 |
November | 267.47 | 0.00 | 267.47 | 4.16 | 1920.17 | 0.00 | 0.00 | 0.00 |
December | 182.15 | 0.00 | 182.15 | 0.00 | 2291.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 673.69 | 18.02 | 655.66 | 312.99 | 1483.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 182.15 | 0.00 | 182.15 | 0.00 | 793.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1224.10 | 76.76 | 1147.34 | 840.08 | 2291.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 343.03 | 137.79 | 205.23 | 158.03 | 1323.14 | 0.00 | 0.00 | 0.00 |
February | 511.51 | 188.96 | 322.56 | 268.15 | 1285.13 | 0.00 | 0.00 | 0.00 |
March | 534.54 | 105.34 | 429.21 | 233.27 | 1045.59 | 0.00 | 0.00 | 0.00 |
April | 1435.29 | 674.45 | 760.84 | 1354.07 | 839.62 | 0.00 | 0.00 | 0.00 |
May | 1509.17 | 658.12 | 851.05 | 1366.58 | 739.78 | 0.00 | 0.00 | 0.00 |
June | 1493.80 | 596.60 | 897.19 | 1477.78 | 577.28 | 0.00 | 0.00 | 0.00 |
July | 1524.87 | 648.07 | 876.81 | 1600.84 | 530.08 | 0.00 | 0.00 | 0.00 |
August | 1444.48 | 690.16 | 754.33 | 1577.74 | 569.50 | 0.00 | 0.00 | 0.00 |
September | 1300.81 | 691.71 | 609.10 | 1355.96 | 726.92 | 0.00 | 0.00 | 0.00 |
October | 627.92 | 260.22 | 367.69 | 473.77 | 986.69 | 0.00 | 0.00 | 0.00 |
November | 327.35 | 111.57 | 215.79 | 145.46 | 1208.63 | 0.00 | 0.00 | 0.00 |
December | 242.61 | 90.20 | 152.41 | 93.09 | 1445.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 942.64 | 404.95 | 537.69 | 844.14 | 938.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 242.61 | 90.20 | 152.41 | 93.09 | 530.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1524.87 | 691.71 | 897.19 | 1600.84 | 1445.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1429.18 | 925.17 | 504.01 | 1287.10 | 1877.18 | 0.00 | 0.00 | 0.00 |
February | 1745.48 | 1065.11 | 680.37 | 1613.69 | 1880.53 | 0.00 | 0.00 | 0.00 |
March | 1079.17 | 314.21 | 764.97 | 732.95 | 1584.89 | 0.00 | 0.00 | 0.00 |
April | 2241.00 | 1012.90 | 1228.10 | 2371.17 | 1382.68 | 0.00 | 0.00 | 0.00 |
May | 1853.51 | 603.44 | 1250.08 | 1754.13 | 1237.61 | 0.00 | 0.00 | 0.00 |
June | 1707.49 | 413.31 | 1294.18 | 1699.40 | 952.32 | 0.00 | 0.00 | 0.00 |
July | 1850.03 | 579.35 | 1270.67 | 2039.45 | 880.38 | 0.00 | 0.00 | 0.00 |
August | 2167.82 | 975.16 | 1192.66 | 2585.67 | 943.24 | 0.00 | 0.00 | 0.00 |
September | 2561.79 | 1500.74 | 1061.06 | 3032.00 | 1185.94 | 0.00 | 0.00 | 0.00 |
October | 1760.06 | 1028.67 | 731.39 | 1814.33 | 1510.64 | 0.00 | 0.00 | 0.00 |
November | 1247.88 | 759.11 | 488.76 | 1131.73 | 1781.76 | 0.00 | 0.00 | 0.00 |
December | 989.06 | 633.69 | 355.36 | 859.70 | 2136.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1716.74 | 814.40 | 902.35 | 1741.06 | 1443.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 989.06 | 314.21 | 355.36 | 732.95 | 880.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2561.79 | 1500.74 | 1294.18 | 3032.00 | 2136.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 333.58 | 110.22 | 223.36 | 161.79 | 1338.74 | 0.00 | 0.00 | 0.00 |
February | 590.62 | 249.38 | 341.24 | 401.28 | 1305.78 | 0.00 | 0.00 | 0.00 |
March | 534.05 | 102.16 | 431.88 | 242.49 | 1060.46 | 0.00 | 0.00 | 0.00 |
April | 1260.10 | 500.52 | 759.58 | 1176.37 | 894.49 | 0.00 | 0.00 | 0.00 |
May | 1478.39 | 601.16 | 877.23 | 1356.78 | 787.29 | 0.00 | 0.00 | 0.00 |
June | 1596.50 | 657.21 | 939.28 | 1629.89 | 621.77 | 0.00 | 0.00 | 0.00 |
July | 1625.96 | 716.89 | 909.08 | 1764.15 | 576.39 | 0.00 | 0.00 | 0.00 |
August | 1365.70 | 591.31 | 774.39 | 1501.39 | 619.95 | 0.00 | 0.00 | 0.00 |
September | 1095.65 | 491.31 | 604.34 | 1144.88 | 781.28 | 0.00 | 0.00 | 0.00 |
October | 584.49 | 210.18 | 374.31 | 447.99 | 1016.91 | 0.00 | 0.00 | 0.00 |
November | 316.31 | 92.33 | 223.97 | 155.19 | 1238.39 | 0.00 | 0.00 | 0.00 |
December | 179.04 | 37.78 | 141.26 | 48.61 | 1502.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 914.33 | 363.52 | 550.81 | 837.38 | 976.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.04 | 37.78 | 141.26 | 48.61 | 576.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1625.96 | 716.89 | 939.28 | 1764.15 | 1502.04 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.674262E+09 | 0.00 | 0.674262E+09 | 16181992.48 | 0.529510E+10 |
February | 0.950996E+09 | 0.00 | 0.950996E+09 | 48472119.99 | 0.455946E+10 |
March | 0.145701E+10 | 0.00 | 0.145701E+10 | 0.266323E+09 | 0.413276E+10 |
April | 0.229572E+10 | 10274618.92 | 0.228544E+10 | 0.109125E+10 | 0.326172E+10 |
May | 0.296591E+10 | 0.143090E+09 | 0.282282E+10 | 0.135650E+10 | 0.275033E+10 |
June | 0.317286E+10 | 0.198958E+09 | 0.297390E+10 | 0.211820E+10 | 0.209118E+10 |
July | 0.310995E+10 | 0.177314E+09 | 0.293264E+10 | 0.230899E+10 | 0.198323E+10 |
August | 0.244458E+10 | 38300349.15 | 0.240628E+10 | 0.178150E+10 | 0.219895E+10 |
September | 0.180064E+10 | 398443.74 | 0.180024E+10 | 0.109516E+10 | 0.279215E+10 |
October | 0.119230E+10 | 0.00 | 0.119230E+10 | 0.325211E+09 | 0.377479E+10 |
November | 0.693285E+09 | 0.00 | 0.693285E+09 | 21880485.45 | 0.452650E+10 |
December | 0.487863E+09 | 0.00 | 0.487863E+09 | 136787.50 | 0.568314E+10 |
Annual Sum or Average | 0.212454E+11 | 0.568335E+09 | 0.206770E+11 | 0.104298E+11 | 0.430493E+11 |
Minimum of Months | 0.487863E+09 | 0.00 | 0.487863E+09 | 136787.50 | 0.198323E+10 |
Maximum of Months | 0.317286E+10 | 0.198958E+09 | 0.297390E+10 | 0.230899E+10 | 0.568314E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.918765E+09 | 0.369068E+09 | 0.549697E+09 | 0.448759E+09 | 0.329104E+10 |
February | 0.123745E+10 | 0.457123E+09 | 0.780332E+09 | 0.688220E+09 | 0.286510E+10 |
March | 0.143172E+10 | 0.282138E+09 | 0.114958E+10 | 0.684170E+09 | 0.258919E+10 |
April | 0.372028E+10 | 0.174817E+10 | 0.197210E+10 | 0.356680E+10 | 0.203931E+10 |
May | 0.404215E+10 | 0.176270E+10 | 0.227945E+10 | 0.372096E+10 | 0.186088E+10 |
June | 0.387193E+10 | 0.154640E+10 | 0.232553E+10 | 0.386732E+10 | 0.141548E+10 |
July | 0.408422E+10 | 0.173578E+10 | 0.234844E+10 | 0.431649E+10 | 0.134406E+10 |
August | 0.386891E+10 | 0.184852E+10 | 0.202039E+10 | 0.425721E+10 | 0.143521E+10 |
September | 0.337169E+10 | 0.179290E+10 | 0.157879E+10 | 0.356433E+10 | 0.175172E+10 |
October | 0.168181E+10 | 0.696982E+09 | 0.984829E+09 | 0.133709E+10 | 0.240702E+10 |
November | 0.848495E+09 | 0.289178E+09 | 0.559317E+09 | 0.406930E+09 | 0.285497E+10 |
December | 0.649799E+09 | 0.241585E+09 | 0.408214E+09 | 0.269824E+09 | 0.358876E+10 |
Annual Sum or Average | 0.297272E+11 | 0.127706E+11 | 0.169567E+11 | 0.271281E+11 | 0.274427E+11 |
Minimum of Months | 0.649799E+09 | 0.241585E+09 | 0.408214E+09 | 0.269824E+09 | 0.134406E+10 |
Maximum of Months | 0.408422E+10 | 0.184852E+10 | 0.234844E+10 | 0.431649E+10 | 0.358876E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382792E+10 | 0.247796E+10 | 0.134995E+10 | 0.351558E+10 | 0.466624E+10 |
February | 0.422267E+10 | 0.257673E+10 | 0.164595E+10 | 0.397700E+10 | 0.421007E+10 |
March | 0.289046E+10 | 0.841569E+09 | 0.204889E+10 | 0.202949E+10 | 0.393600E+10 |
April | 0.580866E+10 | 0.262543E+10 | 0.318323E+10 | 0.619018E+10 | 0.334964E+10 |
May | 0.496445E+10 | 0.161625E+10 | 0.334820E+10 | 0.473797E+10 | 0.309483E+10 |
June | 0.442580E+10 | 0.107129E+10 | 0.335451E+10 | 0.443141E+10 | 0.231564E+10 |
July | 0.495511E+10 | 0.155174E+10 | 0.340338E+10 | 0.548384E+10 | 0.220899E+10 |
August | 0.580629E+10 | 0.261187E+10 | 0.319442E+10 | 0.694872E+10 | 0.235399E+10 |
September | 0.664017E+10 | 0.388991E+10 | 0.275026E+10 | 0.790166E+10 | 0.284673E+10 |
October | 0.471414E+10 | 0.275519E+10 | 0.195894E+10 | 0.493350E+10 | 0.370068E+10 |
November | 0.323450E+10 | 0.196763E+10 | 0.126688E+10 | 0.299721E+10 | 0.423085E+10 |
December | 0.264909E+10 | 0.169728E+10 | 0.951809E+09 | 0.235921E+10 | 0.530696E+10 |
Annual Sum or Average | 0.541393E+11 | 0.256829E+11 | 0.284564E+11 | 0.555058E+11 | 0.422206E+11 |
Minimum of Months | 0.264909E+10 | 0.841569E+09 | 0.951809E+09 | 0.202949E+10 | 0.220899E+10 |
Maximum of Months | 0.664017E+10 | 0.388991E+10 | 0.340338E+10 | 0.790166E+10 | 0.530696E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.893457E+09 | 0.295200E+09 | 0.598257E+09 | 0.450118E+09 | 0.333931E+10 |
February | 0.142882E+10 | 0.603292E+09 | 0.825530E+09 | 0.995231E+09 | 0.292077E+10 |
March | 0.143039E+10 | 0.273631E+09 | 0.115676E+10 | 0.676178E+09 | 0.263292E+10 |
April | 0.326617E+10 | 0.129735E+10 | 0.196883E+10 | 0.307182E+10 | 0.216338E+10 |
May | 0.395971E+10 | 0.161015E+10 | 0.234956E+10 | 0.365634E+10 | 0.196546E+10 |
June | 0.413812E+10 | 0.170350E+10 | 0.243462E+10 | 0.423628E+10 | 0.150943E+10 |
July | 0.435498E+10 | 0.192011E+10 | 0.243487E+10 | 0.473491E+10 | 0.144410E+10 |
August | 0.365789E+10 | 0.158376E+10 | 0.207414E+10 | 0.403645E+10 | 0.154522E+10 |
September | 0.283994E+10 | 0.127349E+10 | 0.156645E+10 | 0.299554E+10 | 0.187051E+10 |
October | 0.156550E+10 | 0.562943E+09 | 0.100255E+10 | 0.123508E+10 | 0.249109E+10 |
November | 0.819864E+09 | 0.239327E+09 | 0.580536E+09 | 0.418307E+09 | 0.294168E+10 |
December | 0.479536E+09 | 0.101192E+09 | 0.378344E+09 | 0.138465E+09 | 0.373677E+10 |
Annual Sum or Average | 0.288344E+11 | 0.114639E+11 | 0.173704E+11 | 0.266447E+11 | 0.285606E+11 |
Minimum of Months | 0.479536E+09 | 0.101192E+09 | 0.378344E+09 | 0.138465E+09 | 0.144410E+10 |
Maximum of Months | 0.435498E+10 | 0.192011E+10 | 0.243487E+10 | 0.473491E+10 | 0.373677E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.224746E+09 | 0.00 | 0.224746E+09 | 4893519.41 | 0.184357E+10 |
February | 0.316987E+09 | 0.00 | 0.316987E+09 | 14105171.20 | 0.158613E+10 |
March | 0.485653E+09 | 0.00 | 0.485653E+09 | 96247125.60 | 0.141911E+10 |
April | 0.765211E+09 | 3424765.00 | 0.761786E+09 | 0.402766E+09 | 0.109339E+10 |
May | 0.988599E+09 | 47695157.25 | 0.940904E+09 | 0.497781E+09 | 0.925719E+09 |
June | 0.105758E+10 | 66317228.13 | 0.991265E+09 | 0.750109E+09 | 0.703075E+09 |
July | 0.103661E+10 | 59102788.71 | 0.977510E+09 | 0.799921E+09 | 0.675506E+09 |
August | 0.814831E+09 | 12766380.55 | 0.802064E+09 | 0.618934E+09 | 0.756349E+09 |
September | 0.600192E+09 | 132810.39 | 0.600059E+09 | 0.371418E+09 | 0.985379E+09 |
October | 0.397419E+09 | 0.00 | 0.397419E+09 | 0.100711E+09 | 0.136504E+10 |
November | 0.231087E+09 | 0.00 | 0.231087E+09 | 4800819.00 | 0.164195E+10 |
December | 0.162615E+09 | 0.00 | 0.162615E+09 | 0.00 | 0.202839E+10 |
Annual Sum or Average | 0.708153E+10 | 0.189439E+09 | 0.689210E+10 | 0.366169E+10 | 0.150236E+11 |
Minimum of Months | 0.162615E+09 | 0.00 | 0.162615E+09 | 0.00 | 0.675506E+09 |
Maximum of Months | 0.105758E+10 | 66317228.13 | 0.991265E+09 | 0.799921E+09 | 0.202839E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.224756E+09 | 0.00 | 0.224756E+09 | 4893235.54 | 0.184369E+10 |
February | 0.317002E+09 | 0.00 | 0.317002E+09 | 14104575.29 | 0.158623E+10 |
March | 0.485675E+09 | 0.00 | 0.485675E+09 | 96246500.13 | 0.141920E+10 |
April | 0.765247E+09 | 3424897.24 | 0.761822E+09 | 0.402779E+09 | 0.109346E+10 |
May | 0.988646E+09 | 47696998.92 | 0.940949E+09 | 0.497795E+09 | 0.925779E+09 |
June | 0.105763E+10 | 66319788.86 | 0.991311E+09 | 0.750135E+09 | 0.703119E+09 |
July | 0.103666E+10 | 59105070.87 | 0.977556E+09 | 0.799951E+09 | 0.675548E+09 |
August | 0.814870E+09 | 12766873.50 | 0.802103E+09 | 0.618960E+09 | 0.756394E+09 |
September | 0.600221E+09 | 132815.52 | 0.600088E+09 | 0.371432E+09 | 0.985438E+09 |
October | 0.397437E+09 | 0.00 | 0.397437E+09 | 0.100712E+09 | 0.136512E+10 |
November | 0.231097E+09 | 0.00 | 0.231097E+09 | 4800442.14 | 0.164206E+10 |
December | 0.162622E+09 | 0.00 | 0.162622E+09 | 0.00 | 0.202852E+10 |
Annual Sum or Average | 0.708187E+10 | 0.189446E+09 | 0.689242E+10 | 0.366181E+10 | 0.150246E+11 |
Minimum of Months | 0.162622E+09 | 0.00 | 0.162622E+09 | 0.00 | 0.675548E+09 |
Maximum of Months | 0.105763E+10 | 66319788.86 | 0.991311E+09 | 0.799951E+09 | 0.202852E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.224756E+09 | 0.00 | 0.224756E+09 | 4893235.54 | 0.184369E+10 |
February | 0.317002E+09 | 0.00 | 0.317002E+09 | 14104575.29 | 0.158623E+10 |
March | 0.485675E+09 | 0.00 | 0.485675E+09 | 96246500.13 | 0.141920E+10 |
April | 0.765247E+09 | 3424897.24 | 0.761822E+09 | 0.402779E+09 | 0.109346E+10 |
May | 0.988646E+09 | 47696998.92 | 0.940949E+09 | 0.497795E+09 | 0.925779E+09 |
June | 0.105763E+10 | 66319788.86 | 0.991311E+09 | 0.750135E+09 | 0.703119E+09 |
July | 0.103666E+10 | 59105070.87 | 0.977556E+09 | 0.799951E+09 | 0.675548E+09 |
August | 0.814870E+09 | 12766873.50 | 0.802103E+09 | 0.618960E+09 | 0.756394E+09 |
September | 0.600221E+09 | 132815.52 | 0.600088E+09 | 0.371432E+09 | 0.985438E+09 |
October | 0.397437E+09 | 0.00 | 0.397437E+09 | 0.100712E+09 | 0.136512E+10 |
November | 0.231097E+09 | 0.00 | 0.231097E+09 | 4800442.14 | 0.164206E+10 |
December | 0.162622E+09 | 0.00 | 0.162622E+09 | 0.00 | 0.202852E+10 |
Annual Sum or Average | 0.708187E+10 | 0.189446E+09 | 0.689242E+10 | 0.366181E+10 | 0.150246E+11 |
Minimum of Months | 0.162622E+09 | 0.00 | 0.162622E+09 | 0.00 | 0.675548E+09 |
Maximum of Months | 0.105763E+10 | 66319788.86 | 0.991311E+09 | 0.799951E+09 | 0.202852E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.883851E+09 | 0.355044E+09 | 0.528807E+09 | 0.426033E+09 | 0.332190E+10 |
February | 0.119043E+10 | 0.439754E+09 | 0.750676E+09 | 0.652465E+09 | 0.288666E+10 |
March | 0.137731E+10 | 0.271418E+09 | 0.110590E+10 | 0.672228E+09 | 0.257491E+10 |
April | 0.357890E+10 | 0.168175E+10 | 0.189715E+10 | 0.348281E+10 | 0.203557E+10 |
May | 0.388854E+10 | 0.169573E+10 | 0.219282E+10 | 0.363287E+10 | 0.186496E+10 |
June | 0.372479E+10 | 0.148764E+10 | 0.223714E+10 | 0.377655E+10 | 0.141118E+10 |
July | 0.392901E+10 | 0.166983E+10 | 0.225918E+10 | 0.419228E+10 | 0.136402E+10 |
August | 0.372188E+10 | 0.177828E+10 | 0.194360E+10 | 0.412058E+10 | 0.147813E+10 |
September | 0.324356E+10 | 0.172478E+10 | 0.151878E+10 | 0.342619E+10 | 0.184119E+10 |
October | 0.161790E+10 | 0.670499E+09 | 0.947400E+09 | 0.125935E+10 | 0.253495E+10 |
November | 0.816251E+09 | 0.278190E+09 | 0.538061E+09 | 0.374721E+09 | 0.299273E+10 |
December | 0.625106E+09 | 0.232406E+09 | 0.392700E+09 | 0.246941E+09 | 0.369479E+10 |
Annual Sum or Average | 0.285975E+11 | 0.122853E+11 | 0.163122E+11 | 0.262630E+11 | 0.280010E+11 |
Minimum of Months | 0.625106E+09 | 0.232406E+09 | 0.392700E+09 | 0.246941E+09 | 0.136402E+10 |
Maximum of Months | 0.392901E+10 | 0.177828E+10 | 0.225918E+10 | 0.419228E+10 | 0.369479E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34946682.54 | 14038137.51 | 20908545.03 | 16844948.96 | 0.131345E+09 |
February | 47068525.01 | 17387464.80 | 29681060.21 | 25797886.23 | 0.114136E+09 |
March | 54457747.75 | 10731630.45 | 43726117.30 | 26579281.43 | 0.101809E+09 |
April | 0.141507E+09 | 66494889.48 | 75011717.66 | 0.137707E+09 | 80484800.21 |
May | 0.153749E+09 | 67047480.96 | 86701937.45 | 0.143641E+09 | 73738656.90 |
June | 0.147275E+09 | 58820037.72 | 88454613.91 | 0.149321E+09 | 55796696.93 |
July | 0.155350E+09 | 66023534.91 | 89326041.79 | 0.165759E+09 | 53932084.66 |
August | 0.147160E+09 | 70311563.02 | 76848227.29 | 0.162924E+09 | 58444060.83 |
September | 0.128248E+09 | 68196169.01 | 60051333.09 | 0.135468E+09 | 72798840.27 |
October | 63970289.87 | 26510932.96 | 37459356.92 | 49793736.15 | 0.100230E+09 |
November | 32273825.36 | 10999386.47 | 21274438.89 | 14816120.58 | 0.118330E+09 |
December | 24716130.18 | 9189110.51 | 15527019.67 | 9763841.51 | 0.146089E+09 |
Annual Sum or Average | 0.113072E+10 | 0.485750E+09 | 0.644970E+09 | 0.103842E+10 | 0.110713E+10 |
Minimum of Months | 24716130.18 | 9189110.51 | 15527019.67 | 9763841.51 | 53932084.66 |
Maximum of Months | 0.155350E+09 | 70311563.02 | 89326041.79 | 0.165759E+09 | 0.146089E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127601E+10 | 0.826010E+09 | 0.449996E+09 | 0.117879E+10 | 0.164016E+10 |
February | 0.140759E+10 | 0.858932E+09 | 0.548662E+09 | 0.133983E+10 | 0.148751E+10 |
March | 0.963512E+09 | 0.280530E+09 | 0.682981E+09 | 0.699122E+09 | 0.135075E+10 |
April | 0.193627E+10 | 0.875168E+09 | 0.106110E+10 | 0.211184E+10 | 0.115624E+10 |
May | 0.165486E+10 | 0.538766E+09 | 0.111609E+10 | 0.163168E+10 | 0.105661E+10 |
June | 0.147530E+10 | 0.357107E+09 | 0.111820E+10 | 0.152986E+10 | 0.779806E+09 |
July | 0.165174E+10 | 0.517260E+09 | 0.113449E+10 | 0.186666E+10 | 0.763525E+09 |
August | 0.193548E+10 | 0.870647E+09 | 0.106483E+10 | 0.234220E+10 | 0.841679E+09 |
September | 0.221345E+10 | 0.129667E+10 | 0.916776E+09 | 0.264509E+10 | 0.104906E+10 |
October | 0.157142E+10 | 0.918422E+09 | 0.652997E+09 | 0.164341E+10 | 0.136578E+10 |
November | 0.107820E+10 | 0.655893E+09 | 0.422303E+09 | 0.998551E+09 | 0.154157E+10 |
December | 0.883054E+09 | 0.565777E+09 | 0.317278E+09 | 0.786031E+09 | 0.187876E+10 |
Annual Sum or Average | 0.180469E+11 | 0.856118E+10 | 0.948570E+10 | 0.187731E+11 | 0.149115E+11 |
Minimum of Months | 0.883054E+09 | 0.280530E+09 | 0.317278E+09 | 0.699122E+09 | 0.763525E+09 |
Maximum of Months | 0.221345E+10 | 0.129667E+10 | 0.113449E+10 | 0.264509E+10 | 0.187876E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127601E+10 | 0.826010E+09 | 0.449996E+09 | 0.117879E+10 | 0.164016E+10 |
February | 0.140759E+10 | 0.858932E+09 | 0.548662E+09 | 0.133983E+10 | 0.148751E+10 |
March | 0.963512E+09 | 0.280530E+09 | 0.682981E+09 | 0.699122E+09 | 0.135075E+10 |
April | 0.193627E+10 | 0.875168E+09 | 0.106110E+10 | 0.211184E+10 | 0.115624E+10 |
May | 0.165486E+10 | 0.538766E+09 | 0.111609E+10 | 0.163168E+10 | 0.105661E+10 |
June | 0.147530E+10 | 0.357107E+09 | 0.111820E+10 | 0.152986E+10 | 0.779806E+09 |
July | 0.165174E+10 | 0.517260E+09 | 0.113449E+10 | 0.186666E+10 | 0.763525E+09 |
August | 0.193548E+10 | 0.870647E+09 | 0.106483E+10 | 0.234220E+10 | 0.841679E+09 |
September | 0.221345E+10 | 0.129667E+10 | 0.916776E+09 | 0.264509E+10 | 0.104906E+10 |
October | 0.157142E+10 | 0.918422E+09 | 0.652997E+09 | 0.164341E+10 | 0.136578E+10 |
November | 0.107820E+10 | 0.655893E+09 | 0.422303E+09 | 0.998551E+09 | 0.154157E+10 |
December | 0.883054E+09 | 0.565777E+09 | 0.317278E+09 | 0.786031E+09 | 0.187876E+10 |
Annual Sum or Average | 0.180469E+11 | 0.856118E+10 | 0.948570E+10 | 0.187731E+11 | 0.149115E+11 |
Minimum of Months | 0.883054E+09 | 0.280530E+09 | 0.317278E+09 | 0.699122E+09 | 0.763525E+09 |
Maximum of Months | 0.221345E+10 | 0.129667E+10 | 0.113449E+10 | 0.264509E+10 | 0.187876E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127593E+10 | 0.825958E+09 | 0.449968E+09 | 0.117871E+10 | 0.164005E+10 |
February | 0.140751E+10 | 0.858878E+09 | 0.548628E+09 | 0.133975E+10 | 0.148742E+10 |
March | 0.963451E+09 | 0.280513E+09 | 0.682938E+09 | 0.699078E+09 | 0.135066E+10 |
April | 0.193615E+10 | 0.875113E+09 | 0.106103E+10 | 0.211170E+10 | 0.115617E+10 |
May | 0.165475E+10 | 0.538732E+09 | 0.111602E+10 | 0.163157E+10 | 0.105654E+10 |
June | 0.147521E+10 | 0.357085E+09 | 0.111813E+10 | 0.152976E+10 | 0.779757E+09 |
July | 0.165164E+10 | 0.517227E+09 | 0.113441E+10 | 0.186654E+10 | 0.763477E+09 |
August | 0.193536E+10 | 0.870592E+09 | 0.106477E+10 | 0.234205E+10 | 0.841625E+09 |
September | 0.221331E+10 | 0.129659E+10 | 0.916718E+09 | 0.264493E+10 | 0.104899E+10 |
October | 0.157132E+10 | 0.918364E+09 | 0.652956E+09 | 0.164331E+10 | 0.136570E+10 |
November | 0.107813E+10 | 0.655851E+09 | 0.422276E+09 | 0.998488E+09 | 0.154148E+10 |
December | 0.882999E+09 | 0.565741E+09 | 0.317258E+09 | 0.785982E+09 | 0.187864E+10 |
Annual Sum or Average | 0.180457E+11 | 0.856064E+10 | 0.948510E+10 | 0.187719E+11 | 0.149105E+11 |
Minimum of Months | 0.882999E+09 | 0.280513E+09 | 0.317258E+09 | 0.699078E+09 | 0.763477E+09 |
Maximum of Months | 0.221331E+10 | 0.129659E+10 | 0.113441E+10 | 0.264493E+10 | 0.187864E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.859502E+09 | 0.283983E+09 | 0.575519E+09 | 0.435870E+09 | 0.337237E+10 |
February | 0.137452E+10 | 0.580367E+09 | 0.794154E+09 | 0.966601E+09 | 0.296134E+10 |
March | 0.137603E+10 | 0.263234E+09 | 0.111279E+10 | 0.680382E+09 | 0.262337E+10 |
April | 0.314204E+10 | 0.124805E+10 | 0.189400E+10 | 0.303550E+10 | 0.215134E+10 |
May | 0.380922E+10 | 0.154896E+10 | 0.226026E+10 | 0.360087E+10 | 0.197254E+10 |
June | 0.398086E+10 | 0.163877E+10 | 0.234209E+10 | 0.415036E+10 | 0.151993E+10 |
July | 0.418947E+10 | 0.184715E+10 | 0.234232E+10 | 0.461331E+10 | 0.147190E+10 |
August | 0.351888E+10 | 0.152358E+10 | 0.199530E+10 | 0.392711E+10 | 0.158920E+10 |
September | 0.273201E+10 | 0.122509E+10 | 0.150691E+10 | 0.289516E+10 | 0.194738E+10 |
October | 0.150600E+10 | 0.541551E+09 | 0.964450E+09 | 0.118052E+10 | 0.261282E+10 |
November | 0.788705E+09 | 0.230233E+09 | 0.558472E+09 | 0.397792E+09 | 0.307956E+10 |
December | 0.461312E+09 | 97346819.68 | 0.363965E+09 | 0.129374E+09 | 0.383570E+10 |
Annual Sum or Average | 0.277385E+11 | 0.110283E+11 | 0.167102E+11 | 0.260129E+11 | 0.291374E+11 |
Minimum of Months | 0.461312E+09 | 97346819.68 | 0.363965E+09 | 0.129374E+09 | 0.147190E+10 |
Maximum of Months | 0.418947E+10 | 0.184715E+10 | 0.234232E+10 | 0.461331E+10 | 0.383570E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33983954.27 | 11228433.98 | 22755520.29 | 17233911.71 | 0.133340E+09 |
February | 54347331.36 | 22947186.01 | 31400145.35 | 38218524.12 | 0.117089E+09 |
March | 54406826.68 | 10408023.70 | 43998802.99 | 26901709.61 | 0.103726E+09 |
April | 0.124234E+09 | 49346665.15 | 74886950.33 | 0.120021E+09 | 85061945.22 |
May | 0.150613E+09 | 61244553.93 | 89368701.09 | 0.142375E+09 | 77992464.19 |
June | 0.157399E+09 | 64795383.61 | 92604101.62 | 0.164102E+09 | 60096659.26 |
July | 0.165648E+09 | 73034645.28 | 92613300.29 | 0.182406E+09 | 58197550.11 |
August | 0.139133E+09 | 60240799.54 | 78892442.15 | 0.155274E+09 | 62835706.06 |
September | 0.108021E+09 | 48439107.09 | 59582006.70 | 0.114472E+09 | 76997611.03 |
October | 59545926.79 | 21412457.73 | 38133469.06 | 46676878.42 | 0.103308E+09 |
November | 31184702.85 | 9103203.35 | 22081499.50 | 15728341.28 | 0.121763E+09 |
December | 18239845.78 | 3849005.61 | 14390840.17 | 5115320.08 | 0.151660E+09 |
Annual Sum or Average | 0.109676E+10 | 0.436049E+09 | 0.660708E+09 | 0.102853E+10 | 0.115207E+10 |
Minimum of Months | 18239845.78 | 3849005.61 | 14390840.17 | 5115320.08 | 58197550.11 |
Maximum of Months | 0.165648E+09 | 73034645.28 | 92613300.29 | 0.182406E+09 | 0.151660E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.674262E+09 | 0.00 | 0.674262E+09 | 9148592.19 | 0.569982E+10 |
February | 0.950996E+09 | 0.00 | 0.950996E+09 | 29432382.04 | 0.495548E+10 |
March | 0.145701E+10 | 0.00 | 0.145701E+10 | 0.216969E+09 | 0.448382E+10 |
April | 0.229572E+10 | 10274618.92 | 0.228544E+10 | 0.102501E+10 | 0.353208E+10 |
May | 0.296591E+10 | 0.143090E+09 | 0.282282E+10 | 0.126831E+10 | 0.298815E+10 |
June | 0.317286E+10 | 0.198958E+09 | 0.297390E+10 | 0.205068E+10 | 0.224353E+10 |
July | 0.310995E+10 | 0.177314E+09 | 0.293264E+10 | 0.225008E+10 | 0.212639E+10 |
August | 0.244458E+10 | 38300349.15 | 0.240628E+10 | 0.172836E+10 | 0.238859E+10 |
September | 0.180064E+10 | 398443.74 | 0.180024E+10 | 0.102400E+10 | 0.306725E+10 |
October | 0.119230E+10 | 0.00 | 0.119230E+10 | 0.257719E+09 | 0.418099E+10 |
November | 0.693285E+09 | 0.00 | 0.693285E+09 | 10789348.76 | 0.497708E+10 |
December | 0.487863E+09 | 0.00 | 0.487863E+09 | 0.00 | 0.613662E+10 |
Annual Sum or Average | 0.212454E+11 | 0.568335E+09 | 0.206770E+11 | 0.987049E+10 | 0.467798E+11 |
Minimum of Months | 0.487863E+09 | 0.00 | 0.487863E+09 | 0.00 | 0.212639E+10 |
Maximum of Months | 0.317286E+10 | 0.198958E+09 | 0.297390E+10 | 0.225008E+10 | 0.613662E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.918765E+09 | 0.369068E+09 | 0.549697E+09 | 0.423269E+09 | 0.354389E+10 |
February | 0.123745E+10 | 0.457123E+09 | 0.780332E+09 | 0.648714E+09 | 0.310900E+10 |
March | 0.143172E+10 | 0.282138E+09 | 0.114958E+10 | 0.624796E+09 | 0.280052E+10 |
April | 0.372028E+10 | 0.174817E+10 | 0.197210E+10 | 0.350975E+10 | 0.217629E+10 |
May | 0.404215E+10 | 0.176270E+10 | 0.227945E+10 | 0.366025E+10 | 0.198142E+10 |
June | 0.387193E+10 | 0.154640E+10 | 0.232553E+10 | 0.383040E+10 | 0.149631E+10 |
July | 0.408422E+10 | 0.173578E+10 | 0.234844E+10 | 0.428769E+10 | 0.141976E+10 |
August | 0.386891E+10 | 0.184852E+10 | 0.202039E+10 | 0.422581E+10 | 0.152534E+10 |
September | 0.337169E+10 | 0.179290E+10 | 0.157879E+10 | 0.351465E+10 | 0.188419E+10 |
October | 0.168181E+10 | 0.696982E+09 | 0.984829E+09 | 0.126896E+10 | 0.264274E+10 |
November | 0.848495E+09 | 0.289178E+09 | 0.559317E+09 | 0.377037E+09 | 0.313277E+10 |
December | 0.649799E+09 | 0.241585E+09 | 0.408214E+09 | 0.249320E+09 | 0.387113E+10 |
Annual Sum or Average | 0.297272E+11 | 0.127706E+11 | 0.169567E+11 | 0.266207E+11 | 0.295834E+11 |
Minimum of Months | 0.649799E+09 | 0.241585E+09 | 0.408214E+09 | 0.249320E+09 | 0.141976E+10 |
Maximum of Months | 0.408422E+10 | 0.184852E+10 | 0.234844E+10 | 0.428769E+10 | 0.387113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382792E+10 | 0.247796E+10 | 0.134995E+10 | 0.344737E+10 | 0.502784E+10 |
February | 0.422267E+10 | 0.257673E+10 | 0.164595E+10 | 0.390383E+10 | 0.454938E+10 |
March | 0.289046E+10 | 0.841569E+09 | 0.204889E+10 | 0.196313E+10 | 0.424498E+10 |
April | 0.580866E+10 | 0.262543E+10 | 0.318323E+10 | 0.614607E+10 | 0.358390E+10 |
May | 0.496445E+10 | 0.161625E+10 | 0.334820E+10 | 0.469827E+10 | 0.331482E+10 |
June | 0.442580E+10 | 0.107129E+10 | 0.335451E+10 | 0.440485E+10 | 0.246842E+10 |
July | 0.495511E+10 | 0.155174E+10 | 0.340338E+10 | 0.546247E+10 | 0.235802E+10 |
August | 0.580629E+10 | 0.261187E+10 | 0.319442E+10 | 0.692545E+10 | 0.252637E+10 |
September | 0.664017E+10 | 0.388991E+10 | 0.275026E+10 | 0.785893E+10 | 0.307397E+10 |
October | 0.471414E+10 | 0.275519E+10 | 0.195894E+10 | 0.485950E+10 | 0.404609E+10 |
November | 0.323450E+10 | 0.196763E+10 | 0.126688E+10 | 0.293344E+10 | 0.461832E+10 |
December | 0.264909E+10 | 0.169728E+10 | 0.951809E+09 | 0.230263E+10 | 0.572161E+10 |
Annual Sum or Average | 0.541393E+11 | 0.256829E+11 | 0.284564E+11 | 0.549059E+11 | 0.455337E+11 |
Minimum of Months | 0.264909E+10 | 0.841569E+09 | 0.951809E+09 | 0.196313E+10 | 0.235802E+10 |
Maximum of Months | 0.664017E+10 | 0.388991E+10 | 0.340338E+10 | 0.785893E+10 | 0.572161E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.893457E+09 | 0.295200E+09 | 0.598257E+09 | 0.433337E+09 | 0.358569E+10 |
February | 0.142882E+10 | 0.603292E+09 | 0.825530E+09 | 0.970767E+09 | 0.315895E+10 |
March | 0.143039E+10 | 0.273631E+09 | 0.115676E+10 | 0.649481E+09 | 0.284033E+10 |
April | 0.326617E+10 | 0.129735E+10 | 0.196883E+10 | 0.304915E+10 | 0.231851E+10 |
May | 0.395971E+10 | 0.161015E+10 | 0.234956E+10 | 0.363400E+10 | 0.210867E+10 |
June | 0.413812E+10 | 0.170350E+10 | 0.243462E+10 | 0.422468E+10 | 0.161164E+10 |
July | 0.435498E+10 | 0.192011E+10 | 0.243487E+10 | 0.472510E+10 | 0.154381E+10 |
August | 0.365789E+10 | 0.158376E+10 | 0.207414E+10 | 0.402132E+10 | 0.166048E+10 |
September | 0.283994E+10 | 0.127349E+10 | 0.156645E+10 | 0.296753E+10 | 0.202507E+10 |
October | 0.156550E+10 | 0.562943E+09 | 0.100255E+10 | 0.119991E+10 | 0.272368E+10 |
November | 0.819864E+09 | 0.239327E+09 | 0.580536E+09 | 0.402252E+09 | 0.320989E+10 |
December | 0.479536E+09 | 0.101192E+09 | 0.378344E+09 | 0.130188E+09 | 0.402306E+10 |
Annual Sum or Average | 0.288344E+11 | 0.114639E+11 | 0.173704E+11 | 0.264077E+11 | 0.308098E+11 |
Minimum of Months | 0.479536E+09 | 0.101192E+09 | 0.378344E+09 | 0.130188E+09 | 0.154381E+10 |
Maximum of Months | 0.435498E+10 | 0.192011E+10 | 0.243487E+10 | 0.472510E+10 | 0.402306E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.04 | 1976.96 | 251.74 | 0.00 | 251.74 | 0.00 | 0.00 |
February | 20.04 | 1884.70 | 393.10 | 0.00 | 393.10 | 0.00 | 0.00 |
March | 99.43 | 1543.00 | 543.99 | 0.00 | 543.99 | 0.00 | 0.00 |
April | 421.01 | 1258.38 | 885.69 | 3.96 | 881.73 | 0.00 | 0.00 |
May | 506.46 | 1026.86 | 1107.34 | 53.42 | 1053.92 | 0.00 | 0.00 |
June | 817.21 | 806.78 | 1224.10 | 76.76 | 1147.34 | 0.00 | 0.00 |
July | 862.08 | 740.45 | 1161.12 | 66.20 | 1094.92 | 0.00 | 0.00 |
August | 665.14 | 820.99 | 912.70 | 14.30 | 898.40 | 0.00 | 0.00 |
September | 422.51 | 1077.22 | 694.69 | 0.15 | 694.54 | 0.00 | 0.00 |
October | 121.42 | 1409.35 | 445.15 | 0.00 | 445.15 | 0.00 | 0.00 |
November | 8.44 | 1746.33 | 267.47 | 0.00 | 267.47 | 0.00 | 0.00 |
December | 0.05 | 2121.84 | 182.15 | 0.00 | 182.15 | 0.00 | 0.00 |
Annual Sum or Average | 330.73 | 1365.08 | 673.69 | 18.02 | 655.66 | 0.00 | 0.00 |
Minimum of Months | 0.05 | 740.45 | 182.15 | 0.00 | 182.15 | 0.00 | 0.00 |
Maximum of Months | 862.08 | 2121.84 | 1224.10 | 76.76 | 1147.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 167.55 | 1228.73 | 343.03 | 137.79 | 205.23 | 0.00 | 0.00 |
February | 284.48 | 1184.32 | 511.51 | 188.96 | 322.56 | 0.00 | 0.00 |
March | 255.44 | 966.69 | 534.54 | 105.34 | 429.21 | 0.00 | 0.00 |
April | 1376.08 | 786.77 | 1435.29 | 674.45 | 760.84 | 0.00 | 0.00 |
May | 1389.25 | 694.77 | 1509.17 | 658.12 | 851.05 | 0.00 | 0.00 |
June | 1492.02 | 546.10 | 1493.80 | 596.60 | 897.19 | 0.00 | 0.00 |
July | 1611.59 | 501.81 | 1524.87 | 648.07 | 876.81 | 0.00 | 0.00 |
August | 1589.46 | 535.85 | 1444.48 | 690.16 | 754.33 | 0.00 | 0.00 |
September | 1375.13 | 675.82 | 1300.81 | 691.71 | 609.10 | 0.00 | 0.00 |
October | 499.21 | 898.68 | 627.92 | 260.22 | 367.69 | 0.00 | 0.00 |
November | 156.99 | 1101.46 | 327.35 | 111.57 | 215.79 | 0.00 | 0.00 |
December | 100.74 | 1339.89 | 242.61 | 90.20 | 152.41 | 0.00 | 0.00 |
Annual Sum or Average | 860.23 | 870.20 | 942.64 | 404.95 | 537.69 | 0.00 | 0.00 |
Minimum of Months | 100.74 | 501.81 | 242.61 | 90.20 | 152.41 | 0.00 | 0.00 |
Maximum of Months | 1611.59 | 1339.89 | 1524.87 | 691.71 | 897.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1312.57 | 1742.18 | 1429.18 | 925.17 | 504.01 | 0.00 | 0.00 |
February | 1643.93 | 1740.27 | 1745.48 | 1065.11 | 680.37 | 0.00 | 0.00 |
March | 757.72 | 1469.53 | 1079.17 | 314.21 | 764.97 | 0.00 | 0.00 |
April | 2388.19 | 1292.30 | 2241.00 | 1012.90 | 1228.10 | 0.00 | 0.00 |
May | 1768.96 | 1155.48 | 1853.51 | 603.44 | 1250.08 | 0.00 | 0.00 |
June | 1709.65 | 893.38 | 1707.49 | 413.31 | 1294.18 | 0.00 | 0.00 |
July | 2047.43 | 824.74 | 1850.03 | 579.35 | 1270.67 | 0.00 | 0.00 |
August | 2594.36 | 878.88 | 2167.82 | 975.16 | 1192.66 | 0.00 | 0.00 |
September | 3048.48 | 1098.28 | 2561.79 | 1500.74 | 1061.06 | 0.00 | 0.00 |
October | 1841.96 | 1381.68 | 1760.06 | 1028.67 | 731.39 | 0.00 | 0.00 |
November | 1156.33 | 1632.27 | 1247.88 | 759.11 | 488.76 | 0.00 | 0.00 |
December | 880.83 | 1981.39 | 989.06 | 633.69 | 355.36 | 0.00 | 0.00 |
Annual Sum or Average | 1760.08 | 1338.81 | 1716.74 | 814.40 | 902.35 | 0.00 | 0.00 |
Minimum of Months | 757.72 | 824.74 | 989.06 | 314.21 | 355.36 | 0.00 | 0.00 |
Maximum of Months | 3048.48 | 1981.39 | 2561.79 | 1500.74 | 1294.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.05 | 1246.76 | 333.58 | 110.22 | 223.36 | 0.00 | 0.00 |
February | 411.39 | 1207.33 | 590.62 | 249.38 | 341.24 | 0.00 | 0.00 |
March | 252.46 | 983.02 | 534.05 | 102.16 | 431.88 | 0.00 | 0.00 |
April | 1185.12 | 834.64 | 1260.10 | 500.52 | 759.58 | 0.00 | 0.00 |
May | 1365.12 | 733.82 | 1478.39 | 601.16 | 877.23 | 0.00 | 0.00 |
June | 1634.37 | 582.34 | 1596.50 | 657.21 | 939.28 | 0.00 | 0.00 |
July | 1767.81 | 539.17 | 1625.96 | 716.89 | 909.08 | 0.00 | 0.00 |
August | 1507.04 | 576.92 | 1365.70 | 591.31 | 774.39 | 0.00 | 0.00 |
September | 1155.69 | 721.65 | 1095.65 | 491.31 | 604.34 | 0.00 | 0.00 |
October | 461.13 | 930.07 | 584.49 | 210.18 | 374.31 | 0.00 | 0.00 |
November | 161.38 | 1134.91 | 316.31 | 92.33 | 223.97 | 0.00 | 0.00 |
December | 51.70 | 1395.15 | 179.04 | 37.78 | 141.26 | 0.00 | 0.00 |
Annual Sum or Average | 844.90 | 905.65 | 914.33 | 363.52 | 550.81 | 0.00 | 0.00 |
Minimum of Months | 51.70 | 539.17 | 179.04 | 37.78 | 141.26 | 0.00 | 0.00 |
Maximum of Months | 1767.81 | 1395.15 | 1625.96 | 716.89 | 939.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.48 | 2065.02 | 251.74 | 0.00 | 251.74 | 0.00 | 0.00 |
February | 17.49 | 1967.01 | 393.10 | 0.00 | 393.10 | 0.00 | 0.00 |
March | 107.80 | 1589.57 | 543.98 | 0.00 | 543.98 | 0.00 | 0.00 |
April | 466.17 | 1265.55 | 885.69 | 3.96 | 881.72 | 0.00 | 0.00 |
May | 557.56 | 1036.92 | 1107.34 | 53.42 | 1053.91 | 0.00 | 0.00 |
June | 868.20 | 813.78 | 1224.09 | 76.76 | 1147.33 | 0.00 | 0.00 |
July | 895.99 | 756.65 | 1161.12 | 66.20 | 1094.92 | 0.00 | 0.00 |
August | 693.27 | 847.20 | 912.70 | 14.30 | 898.40 | 0.00 | 0.00 |
September | 429.89 | 1140.53 | 694.69 | 0.15 | 694.53 | 0.00 | 0.00 |
October | 112.80 | 1529.00 | 445.15 | 0.00 | 445.15 | 0.00 | 0.00 |
November | 5.56 | 1900.49 | 267.47 | 0.00 | 267.47 | 0.00 | 0.00 |
December | 0.00 | 2272.04 | 182.15 | 0.00 | 182.15 | 0.00 | 0.00 |
Annual Sum or Average | 348.34 | 1429.25 | 673.68 | 18.02 | 655.66 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 756.65 | 182.15 | 0.00 | 182.15 | 0.00 | 0.00 |
Maximum of Months | 895.99 | 2272.04 | 1224.09 | 76.76 | 1147.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 165.35 | 1289.29 | 343.04 | 137.80 | 205.24 | 0.00 | 0.00 |
February | 280.37 | 1240.41 | 511.53 | 188.96 | 322.57 | 0.00 | 0.00 |
March | 260.90 | 999.37 | 534.56 | 105.34 | 429.22 | 0.00 | 0.00 |
April | 1396.81 | 816.38 | 1435.34 | 674.48 | 760.87 | 0.00 | 0.00 |
May | 1409.99 | 723.83 | 1509.22 | 658.14 | 851.07 | 0.00 | 0.00 |
June | 1514.61 | 565.96 | 1493.85 | 596.63 | 897.22 | 0.00 | 0.00 |
July | 1627.11 | 529.40 | 1524.93 | 648.09 | 876.83 | 0.00 | 0.00 |
August | 1599.28 | 573.69 | 1444.53 | 690.18 | 754.35 | 0.00 | 0.00 |
September | 1374.10 | 738.42 | 1300.85 | 691.73 | 609.12 | 0.00 | 0.00 |
October | 488.78 | 983.86 | 627.94 | 260.23 | 367.70 | 0.00 | 0.00 |
November | 150.28 | 1200.25 | 327.36 | 111.57 | 215.79 | 0.00 | 0.00 |
December | 95.84 | 1434.02 | 242.62 | 90.20 | 152.41 | 0.00 | 0.00 |
Annual Sum or Average | 865.72 | 923.01 | 942.68 | 404.97 | 537.71 | 0.00 | 0.00 |
Minimum of Months | 95.84 | 529.40 | 242.62 | 90.20 | 152.41 | 0.00 | 0.00 |
Maximum of Months | 1627.11 | 1434.02 | 1524.93 | 691.73 | 897.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1320.30 | 1837.06 | 1429.19 | 925.17 | 504.02 | 0.00 | 0.00 |
February | 1661.46 | 1844.59 | 1745.49 | 1065.12 | 680.37 | 0.00 | 0.00 |
March | 783.05 | 1512.90 | 1079.18 | 314.21 | 764.97 | 0.00 | 0.00 |
April | 2444.20 | 1338.21 | 2241.01 | 1012.90 | 1228.10 | 0.00 | 0.00 |
May | 1827.56 | 1183.46 | 1853.52 | 603.44 | 1250.08 | 0.00 | 0.00 |
June | 1770.63 | 902.53 | 1707.49 | 413.31 | 1294.18 | 0.00 | 0.00 |
July | 2090.75 | 855.18 | 1850.03 | 579.36 | 1270.68 | 0.00 | 0.00 |
August | 2623.37 | 942.72 | 2167.83 | 975.17 | 1192.66 | 0.00 | 0.00 |
September | 3061.39 | 1214.16 | 2561.81 | 1500.75 | 1061.06 | 0.00 | 0.00 |
October | 1840.70 | 1529.74 | 1760.07 | 1028.68 | 731.39 | 0.00 | 0.00 |
November | 1155.71 | 1784.19 | 1247.89 | 759.12 | 488.77 | 0.00 | 0.00 |
December | 880.39 | 2104.30 | 989.06 | 633.70 | 355.37 | 0.00 | 0.00 |
Annual Sum or Average | 1785.83 | 1418.49 | 1716.75 | 814.40 | 902.35 | 0.00 | 0.00 |
Minimum of Months | 783.05 | 855.18 | 989.06 | 314.21 | 355.37 | 0.00 | 0.00 |
Maximum of Months | 3061.39 | 2104.30 | 2561.81 | 1500.75 | 1294.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 169.17 | 1308.88 | 333.59 | 110.22 | 223.37 | 0.00 | 0.00 |
February | 415.35 | 1272.50 | 590.64 | 249.39 | 341.25 | 0.00 | 0.00 |
March | 264.07 | 1018.18 | 534.06 | 102.17 | 431.90 | 0.00 | 0.00 |
April | 1217.41 | 862.81 | 1260.14 | 500.54 | 759.60 | 0.00 | 0.00 |
May | 1397.57 | 765.58 | 1478.43 | 601.18 | 877.25 | 0.00 | 0.00 |
June | 1664.53 | 609.58 | 1596.55 | 657.24 | 939.31 | 0.00 | 0.00 |
July | 1790.52 | 571.27 | 1626.02 | 716.91 | 909.10 | 0.00 | 0.00 |
August | 1524.19 | 616.80 | 1365.74 | 591.33 | 774.42 | 0.00 | 0.00 |
September | 1161.13 | 781.01 | 1095.69 | 491.33 | 604.36 | 0.00 | 0.00 |
October | 458.18 | 1014.08 | 584.51 | 210.19 | 374.32 | 0.00 | 0.00 |
November | 159.54 | 1235.08 | 316.32 | 92.34 | 223.98 | 0.00 | 0.00 |
December | 50.21 | 1488.71 | 179.04 | 37.78 | 141.26 | 0.00 | 0.00 |
Annual Sum or Average | 857.48 | 960.47 | 914.36 | 363.53 | 550.83 | 0.00 | 0.00 |
Minimum of Months | 50.21 | 571.27 | 179.04 | 37.78 | 141.26 | 0.00 | 0.00 |
Maximum of Months | 1790.52 | 1488.71 | 1626.02 | 716.91 | 939.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.42 | 2128.07 | 251.74 | 0.00 | 251.74 | 0.00 | 0.00 |
February | 12.17 | 2048.40 | 393.10 | 0.00 | 393.10 | 0.00 | 0.00 |
March | 81.01 | 1674.07 | 543.99 | 0.00 | 543.99 | 0.00 | 0.00 |
April | 395.45 | 1362.69 | 885.69 | 3.96 | 881.73 | 0.00 | 0.00 |
May | 473.53 | 1115.65 | 1107.34 | 53.42 | 1053.92 | 0.00 | 0.00 |
June | 791.16 | 865.56 | 1224.10 | 76.76 | 1147.34 | 0.00 | 0.00 |
July | 840.08 | 793.90 | 1161.12 | 66.20 | 1094.92 | 0.00 | 0.00 |
August | 645.30 | 891.80 | 912.70 | 14.30 | 898.40 | 0.00 | 0.00 |
September | 395.06 | 1183.35 | 694.69 | 0.15 | 694.54 | 0.00 | 0.00 |
October | 96.22 | 1561.00 | 445.15 | 0.00 | 445.15 | 0.00 | 0.00 |
November | 4.16 | 1920.17 | 267.47 | 0.00 | 267.47 | 0.00 | 0.00 |
December | 0.00 | 2291.15 | 182.15 | 0.00 | 182.15 | 0.00 | 0.00 |
Annual Sum or Average | 312.99 | 1483.38 | 673.69 | 18.02 | 655.66 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 793.90 | 182.15 | 0.00 | 182.15 | 0.00 | 0.00 |
Maximum of Months | 840.08 | 2291.15 | 1224.10 | 76.76 | 1147.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.03 | 1323.14 | 343.03 | 137.79 | 205.23 | 0.00 | 0.00 |
February | 268.15 | 1285.13 | 511.51 | 188.96 | 322.56 | 0.00 | 0.00 |
March | 233.27 | 1045.59 | 534.54 | 105.34 | 429.21 | 0.00 | 0.00 |
April | 1354.07 | 839.62 | 1435.29 | 674.45 | 760.84 | 0.00 | 0.00 |
May | 1366.58 | 739.78 | 1509.17 | 658.12 | 851.05 | 0.00 | 0.00 |
June | 1477.78 | 577.28 | 1493.80 | 596.60 | 897.19 | 0.00 | 0.00 |
July | 1600.84 | 530.08 | 1524.87 | 648.07 | 876.81 | 0.00 | 0.00 |
August | 1577.74 | 569.50 | 1444.48 | 690.16 | 754.33 | 0.00 | 0.00 |
September | 1355.96 | 726.92 | 1300.81 | 691.71 | 609.10 | 0.00 | 0.00 |
October | 473.77 | 986.69 | 627.92 | 260.22 | 367.69 | 0.00 | 0.00 |
November | 145.46 | 1208.63 | 327.35 | 111.57 | 215.79 | 0.00 | 0.00 |
December | 93.09 | 1445.32 | 242.61 | 90.20 | 152.41 | 0.00 | 0.00 |
Annual Sum or Average | 844.14 | 938.08 | 942.64 | 404.95 | 537.69 | 0.00 | 0.00 |
Minimum of Months | 93.09 | 530.08 | 242.61 | 90.20 | 152.41 | 0.00 | 0.00 |
Maximum of Months | 1600.84 | 1445.32 | 1524.87 | 691.71 | 897.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1287.10 | 1877.18 | 1429.18 | 925.17 | 504.01 | 0.00 | 0.00 |
February | 1613.69 | 1880.53 | 1745.48 | 1065.11 | 680.37 | 0.00 | 0.00 |
March | 732.95 | 1584.89 | 1079.17 | 314.21 | 764.97 | 0.00 | 0.00 |
April | 2371.17 | 1382.68 | 2241.00 | 1012.90 | 1228.10 | 0.00 | 0.00 |
May | 1754.13 | 1237.61 | 1853.51 | 603.44 | 1250.08 | 0.00 | 0.00 |
June | 1699.40 | 952.32 | 1707.49 | 413.31 | 1294.18 | 0.00 | 0.00 |
July | 2039.45 | 880.38 | 1850.03 | 579.35 | 1270.67 | 0.00 | 0.00 |
August | 2585.67 | 943.24 | 2167.82 | 975.16 | 1192.66 | 0.00 | 0.00 |
September | 3032.00 | 1185.94 | 2561.79 | 1500.74 | 1061.06 | 0.00 | 0.00 |
October | 1814.33 | 1510.64 | 1760.06 | 1028.67 | 731.39 | 0.00 | 0.00 |
November | 1131.73 | 1781.76 | 1247.88 | 759.11 | 488.76 | 0.00 | 0.00 |
December | 859.70 | 2136.20 | 989.06 | 633.69 | 355.36 | 0.00 | 0.00 |
Annual Sum or Average | 1741.06 | 1443.86 | 1716.74 | 814.40 | 902.35 | 0.00 | 0.00 |
Minimum of Months | 732.95 | 880.38 | 989.06 | 314.21 | 355.36 | 0.00 | 0.00 |
Maximum of Months | 3032.00 | 2136.20 | 2561.79 | 1500.74 | 1294.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.79 | 1338.74 | 333.58 | 110.22 | 223.36 | 0.00 | 0.00 |
February | 401.28 | 1305.78 | 590.62 | 249.38 | 341.24 | 0.00 | 0.00 |
March | 242.49 | 1060.46 | 534.05 | 102.16 | 431.88 | 0.00 | 0.00 |
April | 1176.37 | 894.49 | 1260.10 | 500.52 | 759.58 | 0.00 | 0.00 |
May | 1356.78 | 787.29 | 1478.39 | 601.16 | 877.23 | 0.00 | 0.00 |
June | 1629.89 | 621.77 | 1596.50 | 657.21 | 939.28 | 0.00 | 0.00 |
July | 1764.15 | 576.39 | 1625.96 | 716.89 | 909.08 | 0.00 | 0.00 |
August | 1501.39 | 619.95 | 1365.70 | 591.31 | 774.39 | 0.00 | 0.00 |
September | 1144.88 | 781.28 | 1095.65 | 491.31 | 604.34 | 0.00 | 0.00 |
October | 447.99 | 1016.91 | 584.49 | 210.18 | 374.31 | 0.00 | 0.00 |
November | 155.19 | 1238.39 | 316.31 | 92.33 | 223.97 | 0.00 | 0.00 |
December | 48.61 | 1502.04 | 179.04 | 37.78 | 141.26 | 0.00 | 0.00 |
Annual Sum or Average | 837.38 | 976.97 | 914.33 | 363.52 | 550.81 | 0.00 | 0.00 |
Minimum of Months | 48.61 | 576.39 | 179.04 | 37.78 | 141.26 | 0.00 | 0.00 |
Maximum of Months | 1764.15 | 1502.04 | 1625.96 | 716.89 | 939.28 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16181992.48 | 0.529510E+10 | 0.674262E+09 | 0.00 | 0.674262E+09 | 0.00 | 0.00 |
February | 48472119.99 | 0.455946E+10 | 0.950996E+09 | 0.00 | 0.950996E+09 | 0.00 | 0.00 |
March | 0.266323E+09 | 0.413276E+10 | 0.145701E+10 | 0.00 | 0.145701E+10 | 0.00 | 0.00 |
April | 0.109125E+10 | 0.326172E+10 | 0.229572E+10 | 10274618.92 | 0.228544E+10 | 0.00 | 0.00 |
May | 0.135650E+10 | 0.275033E+10 | 0.296591E+10 | 0.143090E+09 | 0.282282E+10 | 0.00 | 0.00 |
June | 0.211820E+10 | 0.209118E+10 | 0.317286E+10 | 0.198958E+09 | 0.297390E+10 | 0.00 | 0.00 |
July | 0.230899E+10 | 0.198323E+10 | 0.310995E+10 | 0.177314E+09 | 0.293264E+10 | 0.00 | 0.00 |
August | 0.178150E+10 | 0.219895E+10 | 0.244458E+10 | 38300349.15 | 0.240628E+10 | 0.00 | 0.00 |
September | 0.109516E+10 | 0.279215E+10 | 0.180064E+10 | 398443.74 | 0.180024E+10 | 0.00 | 0.00 |
October | 0.325211E+09 | 0.377479E+10 | 0.119230E+10 | 0.00 | 0.119230E+10 | 0.00 | 0.00 |
November | 21880485.45 | 0.452650E+10 | 0.693285E+09 | 0.00 | 0.693285E+09 | 0.00 | 0.00 |
December | 136787.50 | 0.568314E+10 | 0.487863E+09 | 0.00 | 0.487863E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104298E+11 | 0.430493E+11 | 0.212454E+11 | 0.568335E+09 | 0.206770E+11 | 0.00 | 0.00 |
Minimum of Months | 136787.50 | 0.198323E+10 | 0.487863E+09 | 0.00 | 0.487863E+09 | 0.00 | 0.00 |
Maximum of Months | 0.230899E+10 | 0.568314E+10 | 0.317286E+10 | 0.198958E+09 | 0.297390E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.448759E+09 | 0.329104E+10 | 0.918765E+09 | 0.369068E+09 | 0.549697E+09 | 0.00 | 0.00 |
February | 0.688220E+09 | 0.286510E+10 | 0.123745E+10 | 0.457123E+09 | 0.780332E+09 | 0.00 | 0.00 |
March | 0.684170E+09 | 0.258919E+10 | 0.143172E+10 | 0.282138E+09 | 0.114958E+10 | 0.00 | 0.00 |
April | 0.356680E+10 | 0.203931E+10 | 0.372028E+10 | 0.174817E+10 | 0.197210E+10 | 0.00 | 0.00 |
May | 0.372096E+10 | 0.186088E+10 | 0.404215E+10 | 0.176270E+10 | 0.227945E+10 | 0.00 | 0.00 |
June | 0.386732E+10 | 0.141548E+10 | 0.387193E+10 | 0.154640E+10 | 0.232553E+10 | 0.00 | 0.00 |
July | 0.431649E+10 | 0.134406E+10 | 0.408422E+10 | 0.173578E+10 | 0.234844E+10 | 0.00 | 0.00 |
August | 0.425721E+10 | 0.143521E+10 | 0.386891E+10 | 0.184852E+10 | 0.202039E+10 | 0.00 | 0.00 |
September | 0.356433E+10 | 0.175172E+10 | 0.337169E+10 | 0.179290E+10 | 0.157879E+10 | 0.00 | 0.00 |
October | 0.133709E+10 | 0.240702E+10 | 0.168181E+10 | 0.696982E+09 | 0.984829E+09 | 0.00 | 0.00 |
November | 0.406930E+09 | 0.285497E+10 | 0.848495E+09 | 0.289178E+09 | 0.559317E+09 | 0.00 | 0.00 |
December | 0.269824E+09 | 0.358876E+10 | 0.649799E+09 | 0.241585E+09 | 0.408214E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.271281E+11 | 0.274427E+11 | 0.297272E+11 | 0.127706E+11 | 0.169567E+11 | 0.00 | 0.00 |
Minimum of Months | 0.269824E+09 | 0.134406E+10 | 0.649799E+09 | 0.241585E+09 | 0.408214E+09 | 0.00 | 0.00 |
Maximum of Months | 0.431649E+10 | 0.358876E+10 | 0.408422E+10 | 0.184852E+10 | 0.234844E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.351558E+10 | 0.466624E+10 | 0.382792E+10 | 0.247796E+10 | 0.134995E+10 | 0.00 | 0.00 |
February | 0.397700E+10 | 0.421007E+10 | 0.422267E+10 | 0.257673E+10 | 0.164595E+10 | 0.00 | 0.00 |
March | 0.202949E+10 | 0.393600E+10 | 0.289046E+10 | 0.841569E+09 | 0.204889E+10 | 0.00 | 0.00 |
April | 0.619018E+10 | 0.334964E+10 | 0.580866E+10 | 0.262543E+10 | 0.318323E+10 | 0.00 | 0.00 |
May | 0.473797E+10 | 0.309483E+10 | 0.496445E+10 | 0.161625E+10 | 0.334820E+10 | 0.00 | 0.00 |
June | 0.443141E+10 | 0.231564E+10 | 0.442580E+10 | 0.107129E+10 | 0.335451E+10 | 0.00 | 0.00 |
July | 0.548384E+10 | 0.220899E+10 | 0.495511E+10 | 0.155174E+10 | 0.340338E+10 | 0.00 | 0.00 |
August | 0.694872E+10 | 0.235399E+10 | 0.580629E+10 | 0.261187E+10 | 0.319442E+10 | 0.00 | 0.00 |
September | 0.790166E+10 | 0.284673E+10 | 0.664017E+10 | 0.388991E+10 | 0.275026E+10 | 0.00 | 0.00 |
October | 0.493350E+10 | 0.370068E+10 | 0.471414E+10 | 0.275519E+10 | 0.195894E+10 | 0.00 | 0.00 |
November | 0.299721E+10 | 0.423085E+10 | 0.323450E+10 | 0.196763E+10 | 0.126688E+10 | 0.00 | 0.00 |
December | 0.235921E+10 | 0.530696E+10 | 0.264909E+10 | 0.169728E+10 | 0.951809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.555058E+11 | 0.422206E+11 | 0.541393E+11 | 0.256829E+11 | 0.284564E+11 | 0.00 | 0.00 |
Minimum of Months | 0.202949E+10 | 0.220899E+10 | 0.264909E+10 | 0.841569E+09 | 0.951809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.790166E+10 | 0.530696E+10 | 0.664017E+10 | 0.388991E+10 | 0.340338E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.450118E+09 | 0.333931E+10 | 0.893457E+09 | 0.295200E+09 | 0.598257E+09 | 0.00 | 0.00 |
February | 0.995231E+09 | 0.292077E+10 | 0.142882E+10 | 0.603292E+09 | 0.825530E+09 | 0.00 | 0.00 |
March | 0.676178E+09 | 0.263292E+10 | 0.143039E+10 | 0.273631E+09 | 0.115676E+10 | 0.00 | 0.00 |
April | 0.307182E+10 | 0.216338E+10 | 0.326617E+10 | 0.129735E+10 | 0.196883E+10 | 0.00 | 0.00 |
May | 0.365634E+10 | 0.196546E+10 | 0.395971E+10 | 0.161015E+10 | 0.234956E+10 | 0.00 | 0.00 |
June | 0.423628E+10 | 0.150943E+10 | 0.413812E+10 | 0.170350E+10 | 0.243462E+10 | 0.00 | 0.00 |
July | 0.473491E+10 | 0.144410E+10 | 0.435498E+10 | 0.192011E+10 | 0.243487E+10 | 0.00 | 0.00 |
August | 0.403645E+10 | 0.154522E+10 | 0.365789E+10 | 0.158376E+10 | 0.207414E+10 | 0.00 | 0.00 |
September | 0.299554E+10 | 0.187051E+10 | 0.283994E+10 | 0.127349E+10 | 0.156645E+10 | 0.00 | 0.00 |
October | 0.123508E+10 | 0.249109E+10 | 0.156550E+10 | 0.562943E+09 | 0.100255E+10 | 0.00 | 0.00 |
November | 0.418307E+09 | 0.294168E+10 | 0.819864E+09 | 0.239327E+09 | 0.580536E+09 | 0.00 | 0.00 |
December | 0.138465E+09 | 0.373677E+10 | 0.479536E+09 | 0.101192E+09 | 0.378344E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.266447E+11 | 0.285606E+11 | 0.288344E+11 | 0.114639E+11 | 0.173704E+11 | 0.00 | 0.00 |
Minimum of Months | 0.138465E+09 | 0.144410E+10 | 0.479536E+09 | 0.101192E+09 | 0.378344E+09 | 0.00 | 0.00 |
Maximum of Months | 0.473491E+10 | 0.373677E+10 | 0.435498E+10 | 0.192011E+10 | 0.243487E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14679990.43 | 0.553094E+10 | 0.674258E+09 | 0.00 | 0.674258E+09 | 0.00 | 0.00 |
February | 42314321.79 | 0.475860E+10 | 0.950991E+09 | 0.00 | 0.950991E+09 | 0.00 | 0.00 |
March | 0.288740E+09 | 0.425751E+10 | 0.145700E+10 | 0.00 | 0.145700E+10 | 0.00 | 0.00 |
April | 0.120833E+10 | 0.328030E+10 | 0.229571E+10 | 10274559.48 | 0.228543E+10 | 0.00 | 0.00 |
May | 0.149337E+10 | 0.277728E+10 | 0.296589E+10 | 0.143089E+09 | 0.282280E+10 | 0.00 | 0.00 |
June | 0.225038E+10 | 0.210931E+10 | 0.317284E+10 | 0.198957E+09 | 0.297389E+10 | 0.00 | 0.00 |
July | 0.239982E+10 | 0.202660E+10 | 0.310994E+10 | 0.177313E+09 | 0.293262E+10 | 0.00 | 0.00 |
August | 0.185685E+10 | 0.226914E+10 | 0.244457E+10 | 38300127.55 | 0.240627E+10 | 0.00 | 0.00 |
September | 0.111428E+10 | 0.295626E+10 | 0.180063E+10 | 398441.43 | 0.180023E+10 | 0.00 | 0.00 |
October | 0.302135E+09 | 0.409528E+10 | 0.119229E+10 | 0.00 | 0.119229E+10 | 0.00 | 0.00 |
November | 14401703.28 | 0.492607E+10 | 0.693281E+09 | 0.00 | 0.693281E+09 | 0.00 | 0.00 |
December | 0.00 | 0.608543E+10 | 0.487860E+09 | 0.00 | 0.487860E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109853E+11 | 0.450727E+11 | 0.212453E+11 | 0.568332E+09 | 0.206769E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.202660E+10 | 0.487860E+09 | 0.00 | 0.487860E+09 | 0.00 | 0.00 |
Maximum of Months | 0.239982E+10 | 0.608543E+10 | 0.317284E+10 | 0.198957E+09 | 0.297389E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.442878E+09 | 0.345324E+10 | 0.918798E+09 | 0.369083E+09 | 0.549715E+09 | 0.00 | 0.00 |
February | 0.678263E+09 | 0.300080E+10 | 0.123750E+10 | 0.457141E+09 | 0.780357E+09 | 0.00 | 0.00 |
March | 0.698807E+09 | 0.267672E+10 | 0.143177E+10 | 0.282150E+09 | 0.114962E+10 | 0.00 | 0.00 |
April | 0.362052E+10 | 0.211606E+10 | 0.372041E+10 | 0.174825E+10 | 0.197216E+10 | 0.00 | 0.00 |
May | 0.377651E+10 | 0.193869E+10 | 0.404229E+10 | 0.176277E+10 | 0.227952E+10 | 0.00 | 0.00 |
June | 0.392587E+10 | 0.146697E+10 | 0.387206E+10 | 0.154646E+10 | 0.232560E+10 | 0.00 | 0.00 |
July | 0.435804E+10 | 0.141795E+10 | 0.408436E+10 | 0.173585E+10 | 0.234851E+10 | 0.00 | 0.00 |
August | 0.428351E+10 | 0.153658E+10 | 0.386904E+10 | 0.184859E+10 | 0.202045E+10 | 0.00 | 0.00 |
September | 0.356166E+10 | 0.191398E+10 | 0.337181E+10 | 0.179297E+10 | 0.157883E+10 | 0.00 | 0.00 |
October | 0.130915E+10 | 0.263518E+10 | 0.168187E+10 | 0.697010E+09 | 0.984860E+09 | 0.00 | 0.00 |
November | 0.389537E+09 | 0.311105E+10 | 0.848525E+09 | 0.289189E+09 | 0.559335E+09 | 0.00 | 0.00 |
December | 0.256705E+09 | 0.384088E+10 | 0.649822E+09 | 0.241595E+09 | 0.408227E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.273014E+11 | 0.291081E+11 | 0.297283E+11 | 0.127711E+11 | 0.169572E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256705E+09 | 0.141795E+10 | 0.649822E+09 | 0.241595E+09 | 0.408227E+09 | 0.00 | 0.00 |
Maximum of Months | 0.435804E+10 | 0.384088E+10 | 0.408436E+10 | 0.184859E+10 | 0.234851E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.353629E+10 | 0.492037E+10 | 0.382794E+10 | 0.247798E+10 | 0.134996E+10 | 0.00 | 0.00 |
February | 0.401941E+10 | 0.446244E+10 | 0.422269E+10 | 0.257674E+10 | 0.164595E+10 | 0.00 | 0.00 |
March | 0.209732E+10 | 0.405215E+10 | 0.289047E+10 | 0.841574E+09 | 0.204890E+10 | 0.00 | 0.00 |
April | 0.633538E+10 | 0.346865E+10 | 0.580869E+10 | 0.262545E+10 | 0.318324E+10 | 0.00 | 0.00 |
May | 0.489493E+10 | 0.316977E+10 | 0.496447E+10 | 0.161626E+10 | 0.334821E+10 | 0.00 | 0.00 |
June | 0.458948E+10 | 0.233937E+10 | 0.442582E+10 | 0.107130E+10 | 0.335452E+10 | 0.00 | 0.00 |
July | 0.559985E+10 | 0.229053E+10 | 0.495513E+10 | 0.155175E+10 | 0.340338E+10 | 0.00 | 0.00 |
August | 0.702645E+10 | 0.252498E+10 | 0.580632E+10 | 0.261189E+10 | 0.319443E+10 | 0.00 | 0.00 |
September | 0.793511E+10 | 0.314710E+10 | 0.664020E+10 | 0.388993E+10 | 0.275027E+10 | 0.00 | 0.00 |
October | 0.493013E+10 | 0.409727E+10 | 0.471416E+10 | 0.275521E+10 | 0.195895E+10 | 0.00 | 0.00 |
November | 0.299559E+10 | 0.462462E+10 | 0.323452E+10 | 0.196764E+10 | 0.126688E+10 | 0.00 | 0.00 |
December | 0.235804E+10 | 0.563616E+10 | 0.264911E+10 | 0.169729E+10 | 0.951814E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.563180E+11 | 0.447334E+11 | 0.541395E+11 | 0.256830E+11 | 0.284565E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209732E+10 | 0.229053E+10 | 0.264911E+10 | 0.841574E+09 | 0.951814E+09 | 0.00 | 0.00 |
Maximum of Months | 0.793511E+10 | 0.563616E+10 | 0.664020E+10 | 0.388993E+10 | 0.340338E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.453104E+09 | 0.350571E+10 | 0.893486E+09 | 0.295211E+09 | 0.598275E+09 | 0.00 | 0.00 |
February | 0.100482E+10 | 0.307843E+10 | 0.142887E+10 | 0.603314E+09 | 0.825554E+09 | 0.00 | 0.00 |
March | 0.707284E+09 | 0.272709E+10 | 0.143043E+10 | 0.273642E+09 | 0.115679E+10 | 0.00 | 0.00 |
April | 0.315552E+10 | 0.223640E+10 | 0.326628E+10 | 0.129739E+10 | 0.196888E+10 | 0.00 | 0.00 |
May | 0.374325E+10 | 0.205053E+10 | 0.395984E+10 | 0.161021E+10 | 0.234963E+10 | 0.00 | 0.00 |
June | 0.431446E+10 | 0.158003E+10 | 0.413826E+10 | 0.170356E+10 | 0.243469E+10 | 0.00 | 0.00 |
July | 0.479572E+10 | 0.153010E+10 | 0.435512E+10 | 0.192018E+10 | 0.243494E+10 | 0.00 | 0.00 |
August | 0.408238E+10 | 0.165204E+10 | 0.365801E+10 | 0.158382E+10 | 0.207419E+10 | 0.00 | 0.00 |
September | 0.300964E+10 | 0.202438E+10 | 0.284003E+10 | 0.127353E+10 | 0.156650E+10 | 0.00 | 0.00 |
October | 0.122720E+10 | 0.271612E+10 | 0.156555E+10 | 0.562964E+09 | 0.100258E+10 | 0.00 | 0.00 |
November | 0.413520E+09 | 0.320132E+10 | 0.819890E+09 | 0.239336E+09 | 0.580554E+09 | 0.00 | 0.00 |
December | 0.134489E+09 | 0.398736E+10 | 0.479551E+09 | 0.101196E+09 | 0.378356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.270414E+11 | 0.302895E+11 | 0.288353E+11 | 0.114644E+11 | 0.173709E+11 | 0.00 | 0.00 |
Minimum of Months | 0.134489E+09 | 0.153010E+10 | 0.479551E+09 | 0.101196E+09 | 0.378356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.479572E+10 | 0.398736E+10 | 0.435512E+10 | 0.192018E+10 | 0.243494E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9148592.19 | 0.569982E+10 | 0.674262E+09 | 0.00 | 0.674262E+09 | 0.00 | 0.00 |
February | 29432382.04 | 0.495548E+10 | 0.950996E+09 | 0.00 | 0.950996E+09 | 0.00 | 0.00 |
March | 0.216969E+09 | 0.448382E+10 | 0.145701E+10 | 0.00 | 0.145701E+10 | 0.00 | 0.00 |
April | 0.102501E+10 | 0.353208E+10 | 0.229572E+10 | 10274618.92 | 0.228544E+10 | 0.00 | 0.00 |
May | 0.126831E+10 | 0.298815E+10 | 0.296591E+10 | 0.143090E+09 | 0.282282E+10 | 0.00 | 0.00 |
June | 0.205068E+10 | 0.224353E+10 | 0.317286E+10 | 0.198958E+09 | 0.297390E+10 | 0.00 | 0.00 |
July | 0.225008E+10 | 0.212639E+10 | 0.310995E+10 | 0.177314E+09 | 0.293264E+10 | 0.00 | 0.00 |
August | 0.172836E+10 | 0.238859E+10 | 0.244458E+10 | 38300349.15 | 0.240628E+10 | 0.00 | 0.00 |
September | 0.102400E+10 | 0.306725E+10 | 0.180064E+10 | 398443.74 | 0.180024E+10 | 0.00 | 0.00 |
October | 0.257719E+09 | 0.418099E+10 | 0.119230E+10 | 0.00 | 0.119230E+10 | 0.00 | 0.00 |
November | 10789348.76 | 0.497708E+10 | 0.693285E+09 | 0.00 | 0.693285E+09 | 0.00 | 0.00 |
December | 0.00 | 0.613662E+10 | 0.487863E+09 | 0.00 | 0.487863E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.987049E+10 | 0.467798E+11 | 0.212454E+11 | 0.568335E+09 | 0.206770E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.212639E+10 | 0.487863E+09 | 0.00 | 0.487863E+09 | 0.00 | 0.00 |
Maximum of Months | 0.225008E+10 | 0.613662E+10 | 0.317286E+10 | 0.198958E+09 | 0.297390E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.423269E+09 | 0.354389E+10 | 0.918765E+09 | 0.369068E+09 | 0.549697E+09 | 0.00 | 0.00 |
February | 0.648714E+09 | 0.310900E+10 | 0.123745E+10 | 0.457123E+09 | 0.780332E+09 | 0.00 | 0.00 |
March | 0.624796E+09 | 0.280052E+10 | 0.143172E+10 | 0.282138E+09 | 0.114958E+10 | 0.00 | 0.00 |
April | 0.350975E+10 | 0.217629E+10 | 0.372028E+10 | 0.174817E+10 | 0.197210E+10 | 0.00 | 0.00 |
May | 0.366025E+10 | 0.198142E+10 | 0.404215E+10 | 0.176270E+10 | 0.227945E+10 | 0.00 | 0.00 |
June | 0.383040E+10 | 0.149631E+10 | 0.387193E+10 | 0.154640E+10 | 0.232553E+10 | 0.00 | 0.00 |
July | 0.428769E+10 | 0.141976E+10 | 0.408422E+10 | 0.173578E+10 | 0.234844E+10 | 0.00 | 0.00 |
August | 0.422581E+10 | 0.152534E+10 | 0.386891E+10 | 0.184852E+10 | 0.202039E+10 | 0.00 | 0.00 |
September | 0.351465E+10 | 0.188419E+10 | 0.337169E+10 | 0.179290E+10 | 0.157879E+10 | 0.00 | 0.00 |
October | 0.126896E+10 | 0.264274E+10 | 0.168181E+10 | 0.696982E+09 | 0.984829E+09 | 0.00 | 0.00 |
November | 0.377037E+09 | 0.313277E+10 | 0.848495E+09 | 0.289178E+09 | 0.559317E+09 | 0.00 | 0.00 |
December | 0.249320E+09 | 0.387113E+10 | 0.649799E+09 | 0.241585E+09 | 0.408214E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.266207E+11 | 0.295834E+11 | 0.297272E+11 | 0.127706E+11 | 0.169567E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249320E+09 | 0.141976E+10 | 0.649799E+09 | 0.241585E+09 | 0.408214E+09 | 0.00 | 0.00 |
Maximum of Months | 0.428769E+10 | 0.387113E+10 | 0.408422E+10 | 0.184852E+10 | 0.234844E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.344737E+10 | 0.502784E+10 | 0.382792E+10 | 0.247796E+10 | 0.134995E+10 | 0.00 | 0.00 |
February | 0.390383E+10 | 0.454938E+10 | 0.422267E+10 | 0.257673E+10 | 0.164595E+10 | 0.00 | 0.00 |
March | 0.196313E+10 | 0.424498E+10 | 0.289046E+10 | 0.841569E+09 | 0.204889E+10 | 0.00 | 0.00 |
April | 0.614607E+10 | 0.358390E+10 | 0.580866E+10 | 0.262543E+10 | 0.318323E+10 | 0.00 | 0.00 |
May | 0.469827E+10 | 0.331482E+10 | 0.496445E+10 | 0.161625E+10 | 0.334820E+10 | 0.00 | 0.00 |
June | 0.440485E+10 | 0.246842E+10 | 0.442580E+10 | 0.107129E+10 | 0.335451E+10 | 0.00 | 0.00 |
July | 0.546247E+10 | 0.235802E+10 | 0.495511E+10 | 0.155174E+10 | 0.340338E+10 | 0.00 | 0.00 |
August | 0.692545E+10 | 0.252637E+10 | 0.580629E+10 | 0.261187E+10 | 0.319442E+10 | 0.00 | 0.00 |
September | 0.785893E+10 | 0.307397E+10 | 0.664017E+10 | 0.388991E+10 | 0.275026E+10 | 0.00 | 0.00 |
October | 0.485950E+10 | 0.404609E+10 | 0.471414E+10 | 0.275519E+10 | 0.195894E+10 | 0.00 | 0.00 |
November | 0.293344E+10 | 0.461832E+10 | 0.323450E+10 | 0.196763E+10 | 0.126688E+10 | 0.00 | 0.00 |
December | 0.230263E+10 | 0.572161E+10 | 0.264909E+10 | 0.169728E+10 | 0.951809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.549059E+11 | 0.455337E+11 | 0.541393E+11 | 0.256829E+11 | 0.284564E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196313E+10 | 0.235802E+10 | 0.264909E+10 | 0.841569E+09 | 0.951809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.785893E+10 | 0.572161E+10 | 0.664017E+10 | 0.388991E+10 | 0.340338E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.433337E+09 | 0.358569E+10 | 0.893457E+09 | 0.295200E+09 | 0.598257E+09 | 0.00 | 0.00 |
February | 0.970767E+09 | 0.315895E+10 | 0.142882E+10 | 0.603292E+09 | 0.825530E+09 | 0.00 | 0.00 |
March | 0.649481E+09 | 0.284033E+10 | 0.143039E+10 | 0.273631E+09 | 0.115676E+10 | 0.00 | 0.00 |
April | 0.304915E+10 | 0.231851E+10 | 0.326617E+10 | 0.129735E+10 | 0.196883E+10 | 0.00 | 0.00 |
May | 0.363400E+10 | 0.210867E+10 | 0.395971E+10 | 0.161015E+10 | 0.234956E+10 | 0.00 | 0.00 |
June | 0.422468E+10 | 0.161164E+10 | 0.413812E+10 | 0.170350E+10 | 0.243462E+10 | 0.00 | 0.00 |
July | 0.472510E+10 | 0.154381E+10 | 0.435498E+10 | 0.192011E+10 | 0.243487E+10 | 0.00 | 0.00 |
August | 0.402132E+10 | 0.166048E+10 | 0.365789E+10 | 0.158376E+10 | 0.207414E+10 | 0.00 | 0.00 |
September | 0.296753E+10 | 0.202507E+10 | 0.283994E+10 | 0.127349E+10 | 0.156645E+10 | 0.00 | 0.00 |
October | 0.119991E+10 | 0.272368E+10 | 0.156550E+10 | 0.562943E+09 | 0.100255E+10 | 0.00 | 0.00 |
November | 0.402252E+09 | 0.320989E+10 | 0.819864E+09 | 0.239327E+09 | 0.580536E+09 | 0.00 | 0.00 |
December | 0.130188E+09 | 0.402306E+10 | 0.479536E+09 | 0.101192E+09 | 0.378344E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.264077E+11 | 0.308098E+11 | 0.288344E+11 | 0.114639E+11 | 0.173704E+11 | 0.00 | 0.00 |
Minimum of Months | 0.130188E+09 | 0.154381E+10 | 0.479536E+09 | 0.101192E+09 | 0.378344E+09 | 0.00 | 0.00 |
Maximum of Months | 0.472510E+10 | 0.402306E+10 | 0.435498E+10 | 0.192011E+10 | 0.243487E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.493480E+10 | -0.469246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -242344314.1 | 60.05 | 0.00 | 0.00 |
February | 0.450868E+10 | -0.429250E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -216179565.2 | 60.05 | 0.00 | 0.00 |
March | 0.528699E+10 | -0.504838E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -238614534.9 | 60.05 | 0.00 | 0.00 |
April | 0.468525E+10 | -0.445840E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226847198.0 | 60.05 | 0.00 | 0.00 |
May | 0.489104E+10 | -0.465747E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233569050.1 | 60.05 | 0.00 | 0.00 |
June | 0.472996E+10 | -0.450480E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225158567.2 | 60.05 | 0.00 | 0.00 |
July | 0.438869E+10 | -0.415672E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231973248.9 | 60.05 | 0.00 | 0.00 |
August | 0.479438E+10 | -0.456189E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232490846.3 | 60.05 | 0.00 | 0.00 |
September | 0.436216E+10 | -0.413713E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225030762.7 | 60.05 | 0.00 | 0.00 |
October | 0.459693E+10 | -0.436185E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235084572.8 | 60.05 | 0.00 | 0.00 |
November | 0.463845E+10 | -0.440844E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -230017908.8 | 60.05 | 0.00 | 0.00 |
December | 0.471938E+10 | -0.447811E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241269623.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.565367E+11 | -0.537581E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.277858E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.436216E+10 | -0.504838E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -242344314.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.528699E+10 | -0.413713E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -216179565.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125261E+10 | 9833.98 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223677E+09 | 6156.50 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36119410.83 | 2729.66 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1326191.44 | 1310.20 | 08-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15277.26 | 4.33 | 22-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 161499.91 | 5.24 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 189671.83 | 5.15 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 150761.29 | 5.02 | 17-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69335.47 | 5.14 | 13-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121776E+09 | 3854.98 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.508914E+09 | 5570.77 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125261E+10 | 9833.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 74820366.34 | 12040.96 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 74820366.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74820366.34 | 12040.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.513142E+10 | 9394.97 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.395658E+10 | 9382.75 | 08-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486780E+10 | 9384.58 | 20-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159428E+10 | 9400.56 | 28-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164072E+10 | 9441.30 | 24-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.693323E+09 | 9435.71 | 19-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.316274E+09 | 9455.90 | 05-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.304480E+09 | 9442.03 | 30-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.539321E+09 | 9475.16 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201449E+10 | 9397.98 | 04-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.363653E+10 | 9388.14 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.536068E+10 | 9380.39 | 20-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.304480E+09 | 9380.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.536068E+10 | 9475.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208108E+10 | 6200.92 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146897E+10 | 6181.87 | 06-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136011E+10 | 6178.42 | 20-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132800E+09 | 6159.66 | 10-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60256250.53 | 6169.46 | 04-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 253167.25 | 177.86 | 05-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 291522.28 | 1086.39 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.401424E+09 | 6165.37 | 18-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108292E+10 | 6175.14 | 17-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205948E+10 | 6181.25 | 23-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.864759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208108E+10 | 6200.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275311E+10 | 7638.57 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189802E+10 | 7627.64 | 13-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154571E+10 | 7621.40 | 13-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.304383E+09 | 7601.15 | 14-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82864253.67 | 7596.02 | 16-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2275357.61 | 2957.23 | 21-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.391623E+09 | 7594.67 | 18-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117527E+10 | 7624.01 | 20-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251896E+10 | 7623.63 | 30-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275311E+10 | 7638.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.238224E+10 | 6616.17 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165391E+10 | 6596.14 | 06-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164876E+10 | 6592.06 | 20-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.300241E+09 | 6578.61 | 26-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145257E+09 | 6586.07 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1231753.36 | 1181.34 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4331465.92 | 2588.04 | 01-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15278948.10 | 3856.89 | 07-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.582651E+09 | 6584.65 | 30-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135116E+10 | 6593.90 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245923E+10 | 6595.53 | 23-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245923E+10 | 6616.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.343711E+10 | 10758.65 | 10-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159818E+10 | 10608.71 | 17-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926574E+09 | 7628.41 | 08-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57599709.91 | 5113.55 | 08-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2197911.79 | 1940.65 | 06-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 152145.37 | 5.12 | 13-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 151966.19 | 4.94 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 139224.25 | 4.65 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84081.04 | 4.87 | 12-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54402852.41 | 3414.93 | 23-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.927089E+09 | 8853.27 | 29-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.278828E+10 | 9991.94 | 27-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.979197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 84081.04 | 4.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.343711E+10 | 10758.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.532538E+09 | 18099.94 | 03-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65225058.83 | 18108.77 | 27-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28856694.79 | 18037.86 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53152477.69 | 18103.44 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344237E+09 | 18104.06 | 11-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.532538E+09 | 18108.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217971E+10 | 9970.78 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145405E+10 | 9949.02 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136066E+10 | 9972.51 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205185E+09 | 9915.97 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120111E+09 | 9922.47 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2809440.56 | 3822.88 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 335216.30 | 944.52 | 01-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18805750.06 | 6175.93 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.589299E+09 | 9916.35 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140373E+10 | 9969.96 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273809E+10 | 9972.64 | 19-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.273809E+10 | 9972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181388E+10 | 6858.89 | 09-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125668E+10 | 6853.05 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106611E+10 | 6842.50 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106625E+09 | 6796.79 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52832606.51 | 6802.00 | 19-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 171446.03 | 111.84 | 05-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7801431.98 | 4925.76 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.542284E+09 | 6836.50 | 23-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122052E+10 | 6840.84 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201718E+10 | 6842.58 | 19-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.808408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201718E+10 | 6858.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190551E+10 | 7381.08 | 10-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116874E+10 | 7318.28 | 13-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744896E+09 | 7298.02 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70899688.30 | 7241.64 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6540181.90 | 3985.37 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 323446.52 | 1153.72 | 21-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.282655E+09 | 7285.75 | 23-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.975489E+09 | 7317.99 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208893E+10 | 7322.16 | 05-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.724399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208893E+10 | 7381.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.219520E+10 | 6922.68 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149513E+10 | 6913.93 | 16-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129369E+10 | 6923.78 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223062E+09 | 6896.01 | 26-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113797E+09 | 6894.91 | 10-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3326914.63 | 2739.21 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2901626.92 | 2087.98 | 01-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395117.97 | 741.69 | 24-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43902229.51 | 6585.71 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.697639E+09 | 6888.40 | 03-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151973E+10 | 6922.15 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254266E+10 | 6923.87 | 19-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 395117.97 | 741.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.254266E+10 | 6923.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.391347E+10 | 10527.80 | 10-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213251E+10 | 10280.22 | 17-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139600E+10 | 9504.80 | 27-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217889E+09 | 9146.21 | 08-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31071281.63 | 5383.34 | 06-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 180033.51 | 5.62 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 145583.20 | 5.49 | 21-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 93513.28 | 5.29 | 17-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8970786.57 | 2722.46 | 21-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252223E+09 | 6227.30 | 23-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129722E+10 | 9562.93 | 29-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348070E+10 | 9949.02 | 27-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 93513.28 | 5.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.391347E+10 | 10527.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.358317E+10 | 27060.73 | 25-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210521E+10 | 27062.37 | 28-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142382E+10 | 27071.55 | 20-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129209E+09 | 26778.81 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12870950.09 | 18113.11 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.526951E+09 | 27051.92 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186502E+10 | 27055.87 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410991E+10 | 27071.13 | 20-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.410991E+10 | 27071.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.389969E+10 | 12141.37 | 10-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285640E+10 | 11922.37 | 06-FEB-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.281232E+10 | 11932.62 | 20-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.762335E+09 | 11850.91 | 27-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.556489E+09 | 11864.65 | 15-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119640E+09 | 8781.90 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 60921415.28 | 8008.27 | 31-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72307570.15 | 7842.87 | 28-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258981E+09 | 11858.75 | 09-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164018E+10 | 11928.33 | 16-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294154E+10 | 11932.41 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.470073E+10 | 11926.87 | 05-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 60921415.28 | 7842.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.470073E+10 | 12141.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.312070E+10 | 7862.97 | 10-JAN-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225651E+10 | 7702.18 | 27-FEB-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196668E+10 | 7699.62 | 20-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.347339E+09 | 7688.16 | 01-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197192E+09 | 7642.59 | 04-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21632201.36 | 4100.53 | 07-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4257888.96 | 3061.32 | 08-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9208726.77 | 3651.24 | 30-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116410E+09 | 7648.61 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119972E+10 | 7697.94 | 16-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229584E+10 | 7699.55 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348649E+10 | 7704.84 | 30-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4257888.96 | 3061.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348649E+10 | 7862.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.416317E+10 | 10027.98 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299044E+10 | 10070.76 | 17-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238950E+10 | 9824.86 | 27-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594263E+09 | 9780.63 | 01-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.268837E+09 | 9735.40 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13780364.08 | 6932.75 | 07-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5464462.39 | 6099.90 | 31-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14943595.89 | 6237.07 | 28-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175147E+09 | 9746.09 | 25-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145836E+10 | 9799.01 | 16-OCT-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.284239E+10 | 9847.47 | 29-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.457717E+10 | 9912.16 | 27-DEC-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5464462.39 | 6099.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457717E+10 | 10070.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.351053E+10 | 8408.99 | 10-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.255614E+10 | 8259.07 | 13-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.236749E+10 | 8259.36 | 20-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.681825E+09 | 8202.98 | 27-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.446834E+09 | 8212.35 | 15-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 99958611.25 | 5732.56 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 65001019.19 | 5381.55 | 01-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80067463.79 | 5249.96 | 28-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317119E+09 | 8203.98 | 07-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158914E+10 | 8256.62 | 16-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268889E+10 | 8259.23 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396415E+10 | 8255.69 | 05-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 65001019.19 | 5249.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396415E+10 | 8408.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.206650E+10 | 0.197043E+10 | 27385.33 | 28-APR-15:00 | 27372.14 | 0.00 |
May | 0.00 | 0.00 | 0.314890E+10 | 0.262242E+10 | 47544.33 | 22-MAY-15:00 | 46313.14 | 0.00 |
June | 0.00 | 0.00 | 0.103307E+11 | 0.839015E+10 | 64695.69 | 13-JUN-16:00 | 59305.05 | 0.00 |
July | 0.00 | 0.00 | 0.180062E+11 | 0.143438E+11 | 61236.99 | 21-JUL-16:00 | 61236.99 | 0.00 |
August | 0.00 | 0.00 | 0.236780E+11 | 0.183587E+11 | 59165.27 | 14-AUG-15:30 | 56714.86 | 0.00 |
September | 0.00 | 0.00 | 0.118658E+11 | 0.960512E+10 | 52348.03 | 13-SEP-15:30 | 47182.54 | 0.00 |
October | 0.00 | 0.00 | 0.529298E+09 | 0.499050E+09 | 12820.26 | 07-OCT-15:00 | 12820.26 | 0.00 |
November | 0.00 | 0.00 | 9395631.83 | 6646229.50 | 5219.58 | 24-NOV-12:00 | 3828.82 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.696347E+11 | 0.557963E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236780E+11 | 0.183587E+11 | 64695.69 | 61236.99 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 599235.71 | 504384.31 | 2668.73 | 17-JAN-07:05 | 2224.07 | 0.00 |
February | 0.00 | 0.00 | 93089.53 | 86203.43 | 525.01 | 14-FEB-07:04 | 493.09 | 0.00 |
March | 0.00 | 0.00 | 109180.65 | 105732.42 | 660.83 | 03-MAR-07:03 | 621.83 | 0.00 |
April | 0.00 | 0.00 | 0.208260E+10 | 0.199079E+10 | 29056.51 | 30-APR-14:53 | 29056.51 | 0.00 |
May | 0.00 | 0.00 | 0.305179E+10 | 0.254825E+10 | 46574.70 | 22-MAY-15:00 | 45190.88 | 0.00 |
June | 0.00 | 0.00 | 0.100016E+11 | 0.813834E+10 | 72319.64 | 25-JUN-17:52 | 31598.17 | 0.00 |
July | 0.00 | 0.00 | 0.169165E+11 | 0.134244E+11 | 58458.79 | 21-JUL-16:00 | 58390.56 | 0.00 |
August | 0.00 | 0.00 | 0.217435E+11 | 0.167654E+11 | 55486.49 | 14-AUG-14:05 | 50245.88 | 0.00 |
September | 0.00 | 0.00 | 0.108115E+11 | 0.871157E+10 | 49751.42 | 13-SEP-14:05 | 44875.81 | 0.00 |
October | 0.00 | 0.00 | 0.443895E+09 | 0.418318E+09 | 11844.17 | 07-OCT-15:00 | 11844.17 | 0.00 |
November | 0.00 | 0.00 | 7609906.42 | 5322539.20 | 4267.05 | 24-NOV-12:00 | 3062.38 | 0.00 |
December | 0.00 | 0.00 | 176862.65 | 156413.68 | 896.41 | 01-DEC-07:03 | 783.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.650599E+11 | 0.520032E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 93089.53 | 86203.43 | 525.01 | 493.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217435E+11 | 0.167654E+11 | 72319.64 | 58390.56 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1468943.20 | 1437794.07 | 940.19 | 12-JAN-05:50 | 940.19 | 0.00 |
February | 0.00 | 0.00 | 245709.20 | 235752.56 | 693.17 | 18-FEB-05:08 | 678.84 | 0.00 |
March | 0.00 | 0.00 | 94490.48 | 88359.15 | 472.45 | 06-MAR-06:07 | 441.80 | 0.00 |
April | 0.00 | 0.00 | 0.228547E+10 | 0.216842E+10 | 41669.84 | 30-APR-14:53 | 41669.84 | 0.00 |
May | 0.00 | 0.00 | 0.334734E+10 | 0.277235E+10 | 59971.54 | 22-MAY-15:00 | 59930.87 | 0.00 |
June | 0.00 | 0.00 | 0.110836E+11 | 0.904137E+10 | 77356.91 | 13-JUN-15:30 | 72024.33 | 0.00 |
July | 0.00 | 0.00 | 0.185007E+11 | 0.146785E+11 | 72479.77 | 21-JUL-16:00 | 72479.77 | 0.00 |
August | 0.00 | 0.00 | 0.225397E+11 | 0.171473E+11 | 66709.46 | 14-AUG-15:20 | 64210.81 | 0.00 |
September | 0.00 | 0.00 | 0.106884E+11 | 0.847491E+10 | 50070.40 | 13-SEP-15:20 | 45419.22 | 0.00 |
October | 0.00 | 0.00 | 0.432265E+09 | 0.399360E+09 | 12263.23 | 07-OCT-15:00 | 12263.23 | 0.00 |
November | 0.00 | 0.00 | 8499421.28 | 5943032.22 | 4604.69 | 24-NOV-12:00 | 3260.37 | 0.00 |
December | 0.00 | 0.00 | 662793.40 | 623124.53 | 684.92 | 18-DEC-06:01 | 641.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.688884E+11 | 0.546906E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 94490.48 | 88359.15 | 472.45 | 441.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.225397E+11 | 0.171473E+11 | 77356.91 | 72479.77 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17756.58 | 245598.77 | 23-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12771.69 | 253493.38 | 06-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 10088.67 | 250296.97 | 20-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2193.59 | 206637.79 | 12-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1384.47 | 158516.32 | 19-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 363.48 | 59982.08 | 07-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 170.50 | 50958.49 | 31-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 177.19 | 43669.10 | 28-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 571.94 | 121204.76 | 21-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4527.72 | 265998.03 | 23-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10490.34 | 241741.62 | 13-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 18435.88 | 225589.38 | 08-DEC-06:11 |
Annual Sum or Average | 0.00 | 6561.53 | ||||
Minimum of Months | 0.00 | 0.00 | 170.50 | 43669.10 | ||
Maximum of Months | 0.00 | 0.00 | 18435.88 | 265998.03 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1742.57 | 6368.02 | 31-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1764.91 | 6378.09 | 14-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1875.11 | 6367.74 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1710.72 | 6273.12 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1729.43 | 6135.46 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1728.43 | 5961.13 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1542.87 | 5806.86 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1693.70 | 5727.73 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1586.93 | 5807.36 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1619.28 | 5961.93 | 31-OCT-11:25 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1691.40 | 6130.66 | 30-NOV-12:17 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1662.71 | 6273.73 | 29-DEC-12:35 |
Annual Sum or Average | 0.00 | 1695.28 | ||||
Minimum of Months | 0.00 | 0.00 | 1542.87 | 5727.73 | ||
Maximum of Months | 0.00 | 0.00 | 1875.11 | 6378.09 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.326230E+10 | 0.47 | 5053.61 | 02-JAN-06:01 | 1.23 |
February | 0.301393E+10 | 0.47 | 3459.30 | 01-FEB-06:11 | 1.06 |
March | 0.365871E+10 | 0.51 | 3462.95 | 31-MAR-16:00 | 1.06 |
April | 0.419312E+10 | 0.53 | 7946.50 | 20-APR-05:03 | 1.50 |
May | 0.470923E+10 | 0.55 | 6230.80 | 23-MAY-15:30 | 1.34 |
June | 0.543060E+10 | 0.61 | 8152.33 | 13-JUN-16:00 | 1.51 |
July | 0.566602E+10 | 0.59 | 8308.12 | 21-JUL-16:00 | 1.52 |
August | 0.624159E+10 | 0.64 | 7946.50 | 07-AUG-05:13 | 1.49 |
September | 0.530767E+10 | 0.59 | 8509.34 | 05-SEP-06:03 | 1.54 |
October | 0.398775E+10 | 0.50 | 5647.75 | 03-OCT-15:30 | 1.30 |
November | 0.334488E+10 | 0.48 | 3670.05 | 10-NOV-16:20 | 1.08 |
December | 0.315295E+10 | 0.46 | 3459.30 | 01-DEC-06:11 | 1.06 |
Annual Sum or Average | 0.519687E+11 | 0.53 | |||
Minimum of Months | 0.301393E+10 | 0.46 | 3459.30 | 1.06 | |
Maximum of Months | 0.624159E+10 | 0.64 | 8509.34 | 1.54 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.286660E+10 | 0.46 | 5009.76 | 02-JAN-06:01 | 1.26 |
February | 0.260780E+10 | 0.46 | 5009.76 | 06-FEB-07:02 | 1.26 |
March | 0.303738E+10 | 0.49 | 5009.76 | 06-MAR-07:02 | 1.26 |
April | 0.356210E+10 | 0.51 | 6913.50 | 28-APR-15:20 | 1.44 |
May | 0.392841E+10 | 0.53 | 6697.17 | 23-MAY-14:05 | 1.42 |
June | 0.468551E+10 | 0.59 | 8130.69 | 13-JUN-16:00 | 1.54 |
July | 0.498573E+10 | 0.58 | 7982.11 | 21-JUL-16:00 | 1.53 |
August | 0.541771E+10 | 0.63 | 7362.04 | 18-AUG-14:05 | 1.48 |
September | 0.442880E+10 | 0.56 | 7551.86 | 13-SEP-14:05 | 1.49 |
October | 0.312919E+10 | 0.47 | 4921.51 | 04-OCT-12:02 | 1.25 |
November | 0.274814E+10 | 0.45 | 5009.76 | 20-NOV-07:01 | 1.27 |
December | 0.279956E+10 | 0.45 | 5009.76 | 04-DEC-07:01 | 1.26 |
Annual Sum or Average | 0.441969E+11 | 0.52 | |||
Minimum of Months | 0.260780E+10 | 0.45 | 4921.51 | 1.25 | |
Maximum of Months | 0.541771E+10 | 0.63 | 8130.69 | 1.54 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.338671E+10 | 0.48 | 5227.18 | 02-JAN-05:01 | 1.20 |
February | 0.289950E+10 | 0.45 | 5227.18 | 01-FEB-07:03 | 1.20 |
March | 0.334660E+10 | 0.48 | 5227.18 | 01-MAR-07:02 | 1.20 |
April | 0.358382E+10 | 0.48 | 7126.18 | 28-APR-15:20 | 1.36 |
May | 0.393653E+10 | 0.50 | 6980.51 | 23-MAY-15:20 | 1.35 |
June | 0.459745E+10 | 0.55 | 8833.31 | 13-JUN-15:50 | 1.49 |
July | 0.487199E+10 | 0.54 | 8596.65 | 21-JUL-16:00 | 1.47 |
August | 0.507816E+10 | 0.57 | 7599.53 | 14-AUG-15:30 | 1.40 |
September | 0.406198E+10 | 0.51 | 7021.95 | 12-SEP-15:20 | 1.35 |
October | 0.321754E+10 | 0.44 | 5227.18 | 10-OCT-06:03 | 1.19 |
November | 0.302952E+10 | 0.44 | 5227.18 | 01-NOV-06:03 | 1.20 |
December | 0.333925E+10 | 0.47 | 5227.18 | 01-DEC-07:02 | 1.20 |
Annual Sum or Average | 0.453491E+11 | 0.49 | |||
Minimum of Months | 0.289950E+10 | 0.44 | 5227.18 | 1.19 | |
Maximum of Months | 0.507816E+10 | 0.57 | 8833.31 | 1.49 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.337409E+09 | 0.303668E+09 | 799.31 | 10-JAN-07:01 | 719.38 | 719.38 | 44.57 | 2.55 |
February | 0.222572E+09 | 0.200315E+09 | 772.82 | 13-FEB-07:01 | 695.54 | 695.54 | 43.57 | 2.43 |
March | 0.197077E+09 | 0.177369E+09 | 770.52 | 27-MAR-06:01 | 693.46 | 693.46 | 39.89 | 2.43 |
April | 46465945.90 | 41819351.31 | 728.01 | 01-APR-06:03 | 655.21 | 655.21 | 38.52 | 2.15 |
May | 35206053.09 | 31685447.78 | 673.58 | 17-MAY-06:03 | 606.22 | 606.22 | 36.71 | 1.58 |
June | 11360964.45 | 10224868.00 | 447.32 | 07-JUN-06:03 | 402.59 | 402.59 | 37.37 | 0.63 |
July | 4842543.76 | 4358289.38 | 372.80 | 31-JUL-06:03 | 335.52 | 335.52 | 35.07 | 0.49 |
August | 4539045.63 | 4085141.07 | 346.22 | 28-AUG-06:03 | 311.60 | 311.60 | 36.41 | 0.44 |
September | 13852718.24 | 12467446.42 | 611.64 | 20-SEP-06:03 | 550.47 | 550.47 | 35.06 | 1.15 |
October | 90317364.76 | 81285628.29 | 729.76 | 23-OCT-06:03 | 656.78 | 656.78 | 40.87 | 2.16 |
November | 0.195395E+09 | 0.175856E+09 | 768.50 | 20-NOV-07:01 | 691.65 | 691.65 | 43.65 | 2.41 |
December | 0.348422E+09 | 0.313580E+09 | 784.48 | 27-DEC-07:12 | 706.03 | 706.03 | 44.92 | 2.49 |
Annual Sum or Average | 0.150746E+10 | 0.135671E+10 | ||||||
Minimum of Months | 4539045.63 | 4085141.07 | 346.22 | 311.60 | 311.60 | 35.06 | 0.44 | |
Maximum of Months | 0.348422E+09 | 0.313580E+09 | 799.31 | 719.38 | 719.38 | 44.92 | 2.55 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 58.09 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 56.85 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.85 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.81 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.21 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.12 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.13 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.24 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.24 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.10 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.13 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.97 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.81 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.10 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 41.67 | 60.00 | 17756.58 | 245598.77 | 23-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 29.60 | 29.60 | 12771.69 | 253493.38 | 06-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 28.89 | 28.89 | 10088.67 | 250296.97 | 20-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.75 | 25.75 | 2193.59 | 206637.79 | 12-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 33.10 | 33.10 | 1384.47 | 158516.32 | 19-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 42.05 | 42.05 | 363.48 | 59982.08 | 07-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 37.76 | 37.76 | 170.50 | 50958.49 | 31-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 39.97 | 39.97 | 177.19 | 43669.10 | 28-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 36.48 | 36.48 | 571.94 | 121204.76 | 21-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.43 | 25.43 | 4527.72 | 265998.03 | 23-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26.32 | 26.32 | 10490.34 | 241741.62 | 13-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.99 | 29.99 | 18435.88 | 225589.38 | 08-DEC-06:11 |
Annual Sum or Average | 0.00 | 6561.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.43 | 25.43 | 170.50 | 43669.10 | ||
Maximum of Months | 0.00 | 0.00 | 42.05 | 60.00 | 18435.88 | 265998.03 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.09 | 58.09 | 1742.57 | 6368.02 | 31-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.56 | 57.56 | 1764.91 | 6378.09 | 14-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.56 | 57.56 | 1875.11 | 6367.74 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.59 | 57.59 | 1710.72 | 6273.12 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.13 | 58.13 | 1729.43 | 6135.46 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.72 | 57.72 | 1728.43 | 5961.13 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.78 | 57.78 | 1542.87 | 5806.86 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.81 | 57.81 | 1693.70 | 5727.73 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.81 | 57.81 | 1586.93 | 5807.36 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.87 | 56.87 | 1619.28 | 5961.93 | 31-OCT-11:25 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.72 | 57.72 | 1691.40 | 6130.66 | 30-NOV-12:17 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.66 | 57.66 | 1662.71 | 6273.73 | 29-DEC-12:35 |
Annual Sum or Average | 0.00 | 1695.28 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.87 | 56.87 | 1542.87 | 5727.73 | ||
Maximum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 1875.11 | 6378.09 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.136753E+11 | 0.00 | 0.00 | 0.326230E+10 | 0.00 | 0.00 |
February | 0.920117E+10 | 0.00 | 0.00 | 0.301393E+10 | 0.00 | 0.00 |
March | 0.945850E+10 | 0.00 | 0.00 | 0.365871E+10 | 0.00 | 0.00 |
April | 0.233303E+10 | 0.00 | 0.00 | 0.471437E+10 | 0.00 | 0.00 |
May | 0.192911E+10 | 0.00 | 0.00 | 0.547675E+10 | 0.00 | 0.00 |
June | 0.694969E+09 | 0.00 | 0.00 | 0.788684E+10 | 0.00 | 0.00 |
July | 0.320795E+09 | 0.00 | 0.00 | 0.100130E+11 | 0.00 | 0.00 |
August | 0.304631E+09 | 0.00 | 0.00 | 0.119286E+11 | 0.00 | 0.00 |
September | 0.557237E+09 | 0.00 | 0.00 | 0.815817E+10 | 0.00 | 0.00 |
October | 0.339019E+10 | 0.00 | 0.00 | 0.413043E+10 | 0.00 | 0.00 |
November | 0.736767E+10 | 0.00 | 0.00 | 0.334750E+10 | 0.00 | 0.00 |
December | 0.129073E+11 | 0.00 | 0.00 | 0.315295E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.621398E+11 | 0.00 | 0.00 | 0.687436E+11 | 0.00 | 0.00 |
Minimum of Months | 0.304631E+09 | 0.00 | 0.00 | 0.301393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.136753E+11 | 0.00 | 0.00 | 0.119286E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.120640E+11 | 0.00 | 0.00 | 0.286677E+10 | 0.00 | 0.00 |
February | 0.703801E+10 | 0.00 | 0.00 | 0.260782E+10 | 0.00 | 0.00 |
March | 0.542079E+10 | 0.00 | 0.00 | 0.303741E+10 | 0.00 | 0.00 |
April | 0.663371E+09 | 0.00 | 0.00 | 0.408446E+10 | 0.00 | 0.00 |
May | 0.295480E+09 | 0.00 | 0.00 | 0.467114E+10 | 0.00 | 0.00 |
June | 6459946.60 | 0.00 | 0.00 | 0.706321E+10 | 0.00 | 0.00 |
July | 3388809.41 | 0.00 | 0.00 | 0.907454E+10 | 0.00 | 0.00 |
August | 534342.22 | 0.00 | 0.00 | 0.106619E+11 | 0.00 | 0.00 |
September | 70916939.11 | 0.00 | 0.00 | 0.703458E+10 | 0.00 | 0.00 |
October | 0.216628E+10 | 0.00 | 0.00 | 0.324944E+10 | 0.00 | 0.00 |
November | 0.609971E+10 | 0.00 | 0.00 | 0.275027E+10 | 0.00 | 0.00 |
December | 0.125194E+11 | 0.00 | 0.00 | 0.279961E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.463483E+11 | 0.00 | 0.00 | 0.599012E+11 | 0.00 | 0.00 |
Minimum of Months | 534342.22 | 0.00 | 0.00 | 0.260782E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125194E+11 | 0.00 | 0.00 | 0.106619E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.221907E+11 | 0.00 | 0.00 | 0.338713E+10 | 0.00 | 0.00 |
February | 0.148972E+11 | 0.00 | 0.00 | 0.289957E+10 | 0.00 | 0.00 |
March | 0.123558E+11 | 0.00 | 0.00 | 0.334663E+10 | 0.00 | 0.00 |
April | 0.273286E+10 | 0.00 | 0.00 | 0.415839E+10 | 0.00 | 0.00 |
May | 0.151329E+10 | 0.00 | 0.00 | 0.475741E+10 | 0.00 | 0.00 |
June | 0.255191E+09 | 0.00 | 0.00 | 0.724354E+10 | 0.00 | 0.00 |
July | 0.135790E+09 | 0.00 | 0.00 | 0.937987E+10 | 0.00 | 0.00 |
August | 0.176621E+09 | 0.00 | 0.00 | 0.105877E+11 | 0.00 | 0.00 |
September | 0.876627E+09 | 0.00 | 0.00 | 0.667666E+10 | 0.00 | 0.00 |
October | 0.666657E+10 | 0.00 | 0.00 | 0.333577E+10 | 0.00 | 0.00 |
November | 0.139309E+11 | 0.00 | 0.00 | 0.303191E+10 | 0.00 | 0.00 |
December | 0.243191E+11 | 0.00 | 0.00 | 0.333944E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100051E+12 | 0.00 | 0.00 | 0.621440E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135790E+09 | 0.00 | 0.00 | 0.289957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.243191E+11 | 0.00 | 0.00 | 0.105877E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.326230E+10 | 0.00 | 0.136753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301393E+10 | 0.00 | 0.920117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365871E+10 | 0.00 | 0.945850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.419312E+10 | 0.206650E+10 | 0.233303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.470923E+10 | 0.314890E+10 | 0.192911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.543060E+10 | 0.103307E+11 | 0.694969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.566602E+10 | 0.180062E+11 | 0.320795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.624159E+10 | 0.236780E+11 | 0.304631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.530767E+10 | 0.118658E+11 | 0.557237E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398775E+10 | 0.529298E+09 | 0.339019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334488E+10 | 9395631.83 | 0.736767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315295E+10 | 0.00 | 0.129073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519687E+11 | 0.696347E+11 | 0.621398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301393E+10 | 0.00 | 0.304631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.624159E+10 | 0.236780E+11 | 0.136753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.286660E+10 | 599235.71 | 0.120640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260780E+10 | 93089.53 | 0.703801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303738E+10 | 109180.65 | 0.542079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356210E+10 | 0.208260E+10 | 0.663371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.392841E+10 | 0.305179E+10 | 0.295480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468551E+10 | 0.100016E+11 | 6459946.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.498573E+10 | 0.169165E+11 | 3388809.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.541771E+10 | 0.217435E+11 | 534342.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.442880E+10 | 0.108115E+11 | 70916939.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.312919E+10 | 0.443895E+09 | 0.216628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274814E+10 | 7609906.42 | 0.609971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279956E+10 | 176862.65 | 0.125194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441969E+11 | 0.650599E+11 | 0.463483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.260780E+10 | 93089.53 | 534342.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.541771E+10 | 0.217435E+11 | 0.125194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.338671E+10 | 1468943.20 | 0.221907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289950E+10 | 245709.20 | 0.148972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334660E+10 | 94490.48 | 0.123558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.358382E+10 | 0.228547E+10 | 0.273286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393653E+10 | 0.334734E+10 | 0.151329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.459745E+10 | 0.110836E+11 | 0.255191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.487199E+10 | 0.185007E+11 | 0.135790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.507816E+10 | 0.225397E+11 | 0.176621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.406198E+10 | 0.106884E+11 | 0.876627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.321754E+10 | 0.432265E+09 | 0.666657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.302952E+10 | 8499421.28 | 0.139309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333925E+10 | 662793.40 | 0.243191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453491E+11 | 0.688884E+11 | 0.100051E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.289950E+10 | 94490.48 | 0.135790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.507816E+10 | 0.225397E+11 | 0.243191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.326230E+10 | 0.136753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301393E+10 | 0.920117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365871E+10 | 0.945850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.419312E+10 | 0.233303E+10 | 0.00 | 0.00 | 0.521256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.470923E+10 | 0.192911E+10 | 0.00 | 0.00 | 0.767528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.543060E+10 | 0.694969E+09 | 0.00 | 0.00 | 0.245625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.566602E+10 | 0.320795E+09 | 0.00 | 0.00 | 0.434697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.624159E+10 | 0.304631E+09 | 0.00 | 0.00 | 0.568705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.530767E+10 | 0.557237E+09 | 0.00 | 0.00 | 0.285051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398775E+10 | 0.339019E+10 | 0.00 | 0.00 | 0.142679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334488E+10 | 0.736767E+10 | 0.00 | 0.00 | 2614783.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.315295E+10 | 0.129073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519687E+11 | 0.621398E+11 | 0.00 | 0.00 | 0.167749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301393E+10 | 0.304631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.624159E+10 | 0.136753E+11 | 0.00 | 0.00 | 0.568705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.286660E+10 | 0.120640E+11 | 0.00 | 0.00 | 169043.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260780E+10 | 0.703801E+10 | 0.00 | 0.00 | 26658.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303738E+10 | 0.542079E+10 | 0.00 | 0.00 | 31253.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356210E+10 | 0.663371E+09 | 0.00 | 0.00 | 0.522364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.392841E+10 | 0.295480E+09 | 0.00 | 0.00 | 0.742732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468551E+10 | 6459946.60 | 0.00 | 0.00 | 0.237770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.498573E+10 | 3388809.41 | 0.00 | 0.00 | 0.408881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.541771E+10 | 534342.22 | 0.00 | 0.00 | 0.524420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.442880E+10 | 70916939.11 | 0.00 | 0.00 | 0.260578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.312919E+10 | 0.216628E+10 | 0.00 | 0.00 | 0.120258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274814E+10 | 0.609971E+10 | 0.00 | 0.00 | 2128732.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279956E+10 | 0.125194E+11 | 0.00 | 0.00 | 50551.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.441969E+11 | 0.463483E+11 | 0.00 | 0.00 | 0.157043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.260780E+10 | 534342.22 | 0.00 | 0.00 | 26658.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.541771E+10 | 0.125194E+11 | 0.00 | 0.00 | 0.524420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.338671E+10 | 0.221907E+11 | 0.00 | 0.00 | 419817.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289950E+10 | 0.148972E+11 | 0.00 | 0.00 | 70402.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334660E+10 | 0.123558E+11 | 0.00 | 0.00 | 27077.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.358382E+10 | 0.273286E+10 | 0.00 | 0.00 | 0.574568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393653E+10 | 0.151329E+10 | 0.00 | 0.00 | 0.820881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.459745E+10 | 0.255191E+09 | 0.00 | 0.00 | 0.264608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.487199E+10 | 0.135790E+09 | 0.00 | 0.00 | 0.450788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.507816E+10 | 0.176621E+09 | 0.00 | 0.00 | 0.550955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.406198E+10 | 0.876627E+09 | 0.00 | 0.00 | 0.261468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.321754E+10 | 0.666657E+10 | 0.00 | 0.00 | 0.118230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.302952E+10 | 0.139309E+11 | 0.00 | 0.00 | 2384007.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333925E+10 | 0.243191E+11 | 0.00 | 0.00 | 189967.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453491E+11 | 0.100051E+12 | 0.00 | 0.00 | 0.167950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.289950E+10 | 0.135790E+09 | 0.00 | 0.00 | 27077.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.507816E+10 | 0.243191E+11 | 0.00 | 0.00 | 0.550955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.708762E+10 | 0.00 | 0.00 | 13924308.09 | 0.00 | 26995176.90 | 0.825460E+10 | 0.00 | 0.34 |
February | 0.499980E+10 | 0.00 | 0.00 | 18619932.51 | 0.00 | 0.00 | 0.953366E+10 | 0.00 | 0.36 |
March | 0.463919E+10 | 0.00 | 0.00 | 25794034.19 | 0.00 | 0.00 | 0.133342E+11 | 0.00 | 0.44 |
April | 0.143273E+10 | 0.00 | 0.00 | 41765228.04 | 0.00 | 0.00 | 0.208243E+11 | 0.00 | 0.73 |
May | 0.106183E+10 | 0.00 | 0.00 | 47982852.85 | 0.00 | 0.00 | 0.236087E+11 | 0.00 | 0.82 |
June | 0.791367E+09 | 20879199.02 | 0.00 | 51651124.67 | 37044187.22 | 0.00 | 0.244541E+11 | 0.00 | 1.12 |
July | 0.884972E+09 | 23918853.38 | 0.00 | 49200422.39 | 2339375.38 | 0.00 | 0.207046E+11 | 0.00 | 1.15 |
August | 0.895496E+09 | 0.00 | 0.00 | 54925745.10 | 0.00 | 0.00 | 0.201735E+11 | 0.00 | 1.31 |
September | 0.964532E+09 | 0.00 | 0.00 | 49337833.78 | 1414256.08 | 0.00 | 0.215216E+11 | 0.00 | 1.11 |
October | 0.172178E+10 | 0.00 | 0.00 | 38028097.63 | 0.00 | 0.00 | 0.194711E+11 | 0.00 | 0.67 |
November | 0.345420E+10 | 0.00 | 0.00 | 24473216.44 | 0.00 | 0.00 | 0.131998E+11 | 0.00 | 0.44 |
December | 0.669255E+10 | 0.00 | 0.00 | 12888859.39 | 0.00 | 0.00 | 0.775200E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.346261E+11 | 44798052.40 | 0.00 | 0.428592E+09 | 40797818.68 | 26995176.90 | 0.202832E+12 | 0.00 | 0.74 |
Minimum of Months | 0.791367E+09 | 0.00 | 0.00 | 12888859.39 | 0.00 | 0.00 | 0.775200E+10 | 0.00 | 0.32 |
Maximum of Months | 0.708762E+10 | 23918853.38 | 0.00 | 54925745.10 | 37044187.22 | 26995176.90 | 0.244541E+11 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109793E+11 | 0.00 | 0.00 | 433859.89 | 0.00 | 0.230741E+09 | 0.559680E+09 | 0.00 | 0.26 |
February | 0.964591E+10 | 0.00 | 0.00 | 468426.56 | 0.00 | 15323655.72 | 0.776789E+09 | 0.00 | 0.26 |
March | 0.105678E+11 | 0.00 | 0.00 | 1275001.38 | 0.00 | 6524414.47 | 0.184312E+10 | 0.00 | 0.30 |
April | 0.523561E+10 | 149074.41 | 0.00 | 15284335.31 | 0.00 | 0.00 | 0.906457E+10 | 0.00 | 0.47 |
May | 0.462514E+10 | 0.00 | 0.00 | 21090727.52 | 0.00 | 0.00 | 0.114355E+11 | 0.00 | 0.54 |
June | 0.291841E+10 | 16891377.50 | 0.00 | 26998248.32 | 33631283.16 | 0.00 | 0.138995E+11 | 0.00 | 0.75 |
July | 0.253426E+10 | 20030248.13 | 0.00 | 27338546.45 | 2951863.51 | 0.00 | 0.118672E+11 | 0.00 | 0.79 |
August | 0.212860E+10 | 0.00 | 0.00 | 30070736.17 | 0.00 | 0.00 | 0.116537E+11 | 0.00 | 0.89 |
September | 0.358160E+10 | 0.00 | 0.00 | 22503179.23 | 3580211.08 | 0.00 | 0.105599E+11 | 0.00 | 0.73 |
October | 0.729809E+10 | 0.00 | 0.00 | 8369109.28 | 0.00 | 0.00 | 0.542421E+10 | 0.00 | 0.41 |
November | 0.931241E+10 | 0.00 | 0.00 | 1342283.53 | 0.00 | 13720914.67 | 0.158005E+10 | 0.00 | 0.29 |
December | 0.105947E+11 | 0.00 | 0.00 | 62710.92 | 0.00 | 0.137042E+09 | 0.225087E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.794219E+11 | 37070700.04 | 0.00 | 0.155237E+09 | 40163357.75 | 0.403352E+09 | 0.788894E+11 | 0.00 | 0.50 |
Minimum of Months | 0.212860E+10 | 0.00 | 0.00 | 62710.92 | 0.00 | 0.00 | 0.225087E+09 | 0.00 | 0.25 |
Maximum of Months | 0.109793E+11 | 20030248.13 | 0.00 | 30070736.17 | 33631283.16 | 0.230741E+09 | 0.138995E+11 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.950033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111356E+10 | 0.00 | 0.00 | 0.26 |
February | 0.906499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556504E+09 | 0.00 | 0.00 | 0.26 |
March | 0.110199E+11 | 0.00 | 0.00 | 29608.06 | 0.00 | 0.431461E+09 | 0.159951E+09 | 0.00 | 0.30 |
April | 0.737043E+10 | 0.00 | 0.00 | 9661996.36 | 1963998.63 | 26088436.53 | 0.685668E+10 | 0.00 | 0.47 |
May | 0.679673E+10 | 0.00 | 0.00 | 14384422.48 | 0.00 | 3285025.83 | 0.925998E+10 | 0.00 | 0.54 |
June | 0.417413E+10 | 2109498.03 | 0.00 | 23574525.24 | 24542891.77 | 0.00 | 0.129365E+11 | 0.00 | 0.75 |
July | 0.362515E+10 | 3185325.52 | 0.00 | 24703913.81 | 18191683.79 | 0.00 | 0.114925E+11 | 0.00 | 0.79 |
August | 0.353807E+10 | 0.00 | 0.00 | 24244529.11 | 0.00 | 0.00 | 0.102516E+11 | 0.00 | 0.86 |
September | 0.543361E+10 | 0.00 | 0.00 | 14678001.27 | 0.00 | 0.00 | 0.757366E+10 | 0.00 | 0.68 |
October | 0.943071E+10 | 0.00 | 0.00 | 2044858.06 | 0.00 | 0.123149E+09 | 0.181578E+10 | 0.00 | 0.39 |
November | 0.921177E+10 | 0.00 | 0.00 | 29578.66 | 0.00 | 0.462092E+09 | 85450173.94 | 0.00 | 0.29 |
December | 0.816643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153056E+10 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.873322E+11 | 5294823.55 | 0.00 | 0.113351E+09 | 44698574.19 | 0.424670E+10 | 0.604322E+11 | 0.00 | 0.49 |
Minimum of Months | 0.353807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.110199E+11 | 3185325.52 | 0.00 | 24703913.81 | 24542891.77 | 0.153056E+10 | 0.129365E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233095E+10 | 0.00 | 0.00 | 0.40 |
February | 0.155801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161073E+10 | 0.00 | 0.00 | 0.40 |
March | 0.265709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115622E+10 | 0.00 | 0.00 | 0.47 |
April | 0.327339E+10 | 0.00 | 0.00 | 711014.48 | 643867.70 | 0.248173E+09 | 0.801542E+09 | 0.00 | 0.67 |
May | 0.339448E+10 | 0.00 | 0.00 | 1610335.23 | 0.00 | 84936342.42 | 0.123197E+10 | 0.00 | 0.74 |
June | 0.234547E+10 | 721628.38 | 0.00 | 4005679.18 | 8046021.58 | 2017464.13 | 0.243788E+10 | 0.00 | 1.01 |
July | 0.175554E+10 | 855121.50 | 0.00 | 5238378.45 | 6167203.36 | 957819.70 | 0.247138E+10 | 0.00 | 1.06 |
August | 0.191737E+10 | 0.00 | 0.00 | 4271943.30 | 0.00 | 3198175.71 | 0.197081E+10 | 0.00 | 1.16 |
September | 0.263980E+10 | 0.00 | 0.00 | 1577709.14 | 0.00 | 54987687.41 | 0.108357E+10 | 0.00 | 0.92 |
October | 0.303366E+10 | 0.00 | 0.00 | 6897.53 | 0.00 | 0.610813E+09 | 34253062.42 | 0.00 | 0.60 |
November | 0.177932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143366E+10 | 0.00 | 0.00 | 0.45 |
December | 0.916125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228995E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.264445E+11 | 1576749.87 | 0.00 | 17421957.32 | 14857092.64 | 0.982660E+10 | 0.100314E+11 | 0.00 | 0.69 |
Minimum of Months | 0.916125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 957819.70 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.339448E+10 | 855121.50 | 0.00 | 5238378.45 | 8046021.58 | 0.233095E+10 | 0.247138E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185152E+10 | 0.00 | 0.00 | 0.58 |
February | 0.162195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128603E+10 | 0.00 | 0.00 | 0.58 |
March | 0.253905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967755E+09 | 0.00 | 0.00 | 0.69 |
April | 0.214674E+10 | 984123.28 | 0.00 | 2653075.55 | 0.00 | 0.108424E+09 | 0.196084E+10 | 0.00 | 1.04 |
May | 0.251567E+10 | 0.00 | 0.00 | 3285411.49 | 0.00 | 43598525.73 | 0.207349E+10 | 0.00 | 1.17 |
June | 0.201126E+10 | 500441.48 | 0.00 | 4976038.44 | 7408446.37 | 2630910.22 | 0.271702E+10 | 0.00 | 1.59 |
July | 0.142383E+10 | 11656236.87 | 0.00 | 5708336.84 | 51254.73 | 1056635.52 | 0.269360E+10 | 0.00 | 1.63 |
August | 0.147765E+10 | 0.00 | 0.00 | 5787079.84 | 0.00 | 2576242.70 | 0.246943E+10 | 0.00 | 1.85 |
September | 0.185989E+10 | 0.00 | 0.00 | 3469237.80 | 0.00 | 20267495.13 | 0.182268E+10 | 0.00 | 1.45 |
October | 0.250723E+10 | 0.00 | 0.00 | 215142.66 | 0.00 | 0.488813E+09 | 0.390456E+09 | 0.00 | 0.87 |
November | 0.182164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112865E+10 | 0.00 | 0.00 | 0.65 |
December | 0.106018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187600E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.223480E+11 | 13140801.63 | 0.00 | 26094322.62 | 7459701.10 | 0.777732E+10 | 0.141275E+11 | 0.00 | 1.06 |
Minimum of Months | 0.106018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1056635.52 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.253905E+10 | 11656236.87 | 0.00 | 5787079.84 | 7408446.37 | 0.187600E+10 | 0.271702E+10 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243823E+10 | 0.00 | 0.00 | 614310.28 | 0.00 | 0.220220E+10 | 0.399204E+09 | 0.00 | 0.58 |
February | 0.237556E+10 | 0.00 | 0.00 | 1263977.32 | 0.00 | 0.158095E+10 | 0.690157E+09 | 0.00 | 0.59 |
March | 0.396429E+10 | 0.00 | 0.00 | 100104.55 | 0.00 | 0.133261E+10 | 0.191960E+09 | 0.00 | 0.68 |
April | 0.301730E+10 | 0.00 | 0.00 | 6835431.86 | 928027.04 | 0.333377E+09 | 0.407093E+10 | 0.00 | 1.16 |
May | 0.406700E+10 | 0.00 | 0.00 | 5324177.89 | 0.00 | 0.174657E+09 | 0.323472E+10 | 0.00 | 1.19 |
June | 0.355711E+10 | 861611.11 | 0.00 | 6264252.27 | 11596987.35 | 17331285.08 | 0.356291E+10 | 0.00 | 1.50 |
July | 0.266048E+10 | 977524.34 | 0.00 | 8132555.98 | 9206499.73 | 7522456.15 | 0.379378E+10 | 0.00 | 1.62 |
August | 0.251659E+10 | 0.00 | 0.00 | 9668671.27 | 0.00 | 8472841.41 | 0.400236E+10 | 0.00 | 1.95 |
September | 0.268405E+10 | 0.00 | 0.00 | 9231429.53 | 0.00 | 57726224.20 | 0.422301E+10 | 0.00 | 1.75 |
October | 0.325969E+10 | 0.00 | 0.00 | 3859438.69 | 0.00 | 0.643999E+09 | 0.213044E+10 | 0.00 | 0.99 |
November | 0.288288E+10 | 0.00 | 0.00 | 706509.45 | 0.00 | 0.140202E+10 | 0.372817E+09 | 0.00 | 0.65 |
December | 0.181598E+10 | 0.00 | 0.00 | 157539.06 | 0.00 | 0.262622E+10 | 0.148277E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.352392E+11 | 1839135.45 | 0.00 | 52158398.15 | 21731514.13 | 0.103871E+11 | 0.268206E+11 | 0.00 | 1.10 |
Minimum of Months | 0.181598E+10 | 0.00 | 0.00 | 100104.55 | 0.00 | 7522456.15 | 0.148277E+09 | 0.00 | 0.54 |
Maximum of Months | 0.406700E+10 | 977524.34 | 0.00 | 9668671.27 | 11596987.35 | 0.262622E+10 | 0.422301E+10 | 0.00 | 1.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214249E+10 | 0.00 | 0.00 | 0.66 |
February | 0.177425E+10 | 0.00 | 0.00 | 30004.30 | 0.00 | 0.146038E+10 | 79461213.79 | 0.00 | 0.67 |
March | 0.281926E+10 | 0.00 | 0.00 | 25082.56 | 0.00 | 0.112907E+10 | 49589676.65 | 0.00 | 0.78 |
April | 0.301748E+10 | 0.00 | 0.00 | 2426335.88 | 675940.13 | 0.260869E+09 | 0.163201E+10 | 0.00 | 1.21 |
May | 0.330518E+10 | 0.00 | 0.00 | 2965874.36 | 0.00 | 0.132879E+09 | 0.191971E+10 | 0.00 | 1.35 |
June | 0.278450E+10 | 7070321.48 | 0.00 | 4291527.38 | 3097142.71 | 13005712.82 | 0.254837E+10 | 0.00 | 1.78 |
July | 0.216265E+10 | 232328.63 | 0.00 | 5356875.53 | 7134696.41 | 7642656.92 | 0.255653E+10 | 0.00 | 1.89 |
August | 0.219467E+10 | 0.00 | 0.00 | 4364716.67 | 0.00 | 12331016.81 | 0.203775E+10 | 0.00 | 1.99 |
September | 0.287153E+10 | 0.00 | 0.00 | 2437972.21 | 0.00 | 60503637.61 | 0.127698E+10 | 0.00 | 1.65 |
October | 0.286841E+10 | 0.00 | 0.00 | 562225.63 | 0.00 | 0.625209E+09 | 0.418674E+09 | 0.00 | 1.01 |
November | 0.198130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138110E+10 | 0.00 | 0.00 | 0.74 |
December | 0.984937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235892E+10 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.282815E+11 | 7302650.11 | 0.00 | 22460614.52 | 10907779.25 | 0.958441E+10 | 0.125191E+11 | 0.00 | 1.20 |
Minimum of Months | 0.984937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7642656.92 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.330518E+10 | 7070321.48 | 0.00 | 5356875.53 | 7134696.41 | 0.235892E+10 | 0.255653E+10 | 0.00 | 1.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205937E+10 | 0.00 | 0.00 | 0.36 |
February | 0.163759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147915E+10 | 0.00 | 0.00 | 0.36 |
March | 0.263241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109369E+10 | 0.00 | 0.00 | 0.43 |
April | 0.351288E+10 | 0.00 | 0.00 | 41357.60 | 0.00 | 0.123732E+09 | 67191670.12 | 0.00 | 0.56 |
May | 0.359187E+10 | 0.00 | 0.00 | 273821.66 | 0.00 | 12246064.64 | 0.259977E+09 | 0.00 | 0.59 |
June | 0.253298E+10 | 3328929.11 | 0.00 | 1664066.99 | 8638628.69 | 0.00 | 0.113070E+10 | 0.00 | 0.76 |
July | 0.160678E+10 | 2063661.96 | 0.00 | 3173041.56 | 2146770.34 | 0.00 | 0.155395E+10 | 0.00 | 0.80 |
August | 0.186519E+10 | 0.00 | 0.00 | 2641369.57 | 0.00 | 0.00 | 0.117866E+10 | 0.00 | 0.88 |
September | 0.263251E+10 | 0.00 | 0.00 | 909649.73 | 329801.63 | 848194.69 | 0.700575E+09 | 0.00 | 0.76 |
October | 0.355668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148320E+09 | 0.00 | 0.00 | 0.54 |
November | 0.266257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688916E+09 | 0.00 | 0.00 | 0.41 |
December | 0.143381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180229E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.290218E+11 | 5392591.07 | 0.00 | 8703307.11 | 11115200.66 | 0.740855E+10 | 0.489105E+10 | 0.00 | 0.57 |
Minimum of Months | 0.135657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.359187E+10 | 3328929.11 | 0.00 | 3173041.56 | 8638628.69 | 0.205937E+10 | 0.155395E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164687E+10 | 0.00 | 0.00 | 0.52 |
February | 0.170034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119102E+10 | 0.00 | 0.00 | 0.53 |
March | 0.250030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.958248E+09 | 0.00 | 0.00 | 0.62 |
April | 0.237791E+10 | 0.00 | 0.00 | 1629927.74 | 0.00 | 26042742.76 | 0.117029E+10 | 0.00 | 0.86 |
May | 0.245711E+10 | 0.00 | 0.00 | 2210032.80 | 0.00 | 5448799.24 | 0.134530E+10 | 0.00 | 0.95 |
June | 0.185359E+10 | 3166671.68 | 0.00 | 3564585.96 | 8019951.88 | 0.00 | 0.188947E+10 | 0.00 | 1.28 |
July | 0.120083E+10 | 5920977.08 | 0.00 | 4590242.06 | 506467.53 | 0.00 | 0.205902E+10 | 0.00 | 1.31 |
August | 0.123319E+10 | 0.00 | 0.00 | 5192659.47 | 0.00 | 0.00 | 0.206491E+10 | 0.00 | 1.52 |
September | 0.170791E+10 | 0.00 | 0.00 | 3618820.43 | 306182.06 | 0.00 | 0.172009E+10 | 0.00 | 1.26 |
October | 0.288165E+10 | 0.00 | 0.00 | 381365.37 | 0.00 | 0.121849E+09 | 0.444129E+09 | 0.00 | 0.80 |
November | 0.255960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551454E+09 | 0.00 | 0.00 | 0.61 |
December | 0.147290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152722E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.234554E+11 | 9087648.76 | 0.00 | 21187633.84 | 8832601.47 | 0.602815E+10 | 0.106932E+11 | 0.00 | 0.90 |
Minimum of Months | 0.120083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.288165E+10 | 5920977.08 | 0.00 | 5192659.47 | 8019951.88 | 0.164687E+10 | 0.206491E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175817E+10 | 0.00 | 0.00 | 12150.31 | 0.00 | 0.355301E+10 | 28333341.96 | 0.00 | 0.55 |
February | 0.215596E+10 | 0.00 | 0.00 | 35395.92 | 0.00 | 0.266418E+10 | 38934440.57 | 0.00 | 0.56 |
March | 0.253893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330097E+10 | 0.00 | 0.00 | 0.66 |
April | 0.358061E+10 | 0.00 | 0.00 | 1575862.07 | 0.00 | 0.988706E+09 | 0.102177E+10 | 0.00 | 0.86 |
May | 0.402503E+10 | 0.00 | 0.00 | 1049357.60 | 0.00 | 0.105489E+10 | 0.699531E+09 | 0.00 | 0.89 |
June | 0.394151E+10 | 5382699.75 | 0.00 | 1583190.90 | 12274930.47 | 0.499111E+09 | 0.790050E+09 | 0.00 | 1.10 |
July | 0.294323E+10 | 4099917.78 | 0.00 | 3286321.84 | 3062791.31 | 0.257767E+09 | 0.134663E+10 | 0.00 | 1.16 |
August | 0.239286E+10 | 0.00 | 0.00 | 5619787.32 | 0.00 | 0.237364E+09 | 0.210444E+10 | 0.00 | 1.42 |
September | 0.256813E+10 | 87421.58 | 0.00 | 6036817.32 | 391288.18 | 0.399452E+09 | 0.262494E+10 | 0.00 | 1.37 |
October | 0.362289E+10 | 0.00 | 0.00 | 1965101.11 | 0.00 | 0.111565E+10 | 0.113490E+10 | 0.00 | 0.87 |
November | 0.290771E+10 | 0.00 | 0.00 | 26718.60 | 0.00 | 0.221781E+10 | 68131550.18 | 0.00 | 0.64 |
December | 0.108097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399483E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.335160E+11 | 9570039.11 | 0.00 | 21190702.99 | 15729009.96 | 0.202838E+11 | 0.985766E+10 | 0.00 | 0.89 |
Minimum of Months | 0.108097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237364E+09 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.402503E+10 | 5382699.75 | 0.00 | 6036817.32 | 12274930.47 | 0.399483E+10 | 0.262494E+10 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189246E+10 | 0.00 | 0.00 | 0.59 |
February | 0.197171E+10 | 0.00 | 0.00 | 861.79 | 0.00 | 0.128755E+10 | 10604558.06 | 0.00 | 0.60 |
March | 0.285529E+10 | 0.00 | 0.00 | 922.94 | 0.00 | 0.104987E+10 | 6852880.18 | 0.00 | 0.70 |
April | 0.316565E+10 | 0.00 | 0.00 | 1070385.15 | 0.00 | 0.109596E+09 | 0.711419E+09 | 0.00 | 0.96 |
May | 0.313208E+10 | 0.00 | 0.00 | 1666073.71 | 0.00 | 32971336.73 | 0.109037E+10 | 0.00 | 1.06 |
June | 0.243462E+10 | 7825806.12 | 0.00 | 2714692.30 | 7635709.63 | 0.00 | 0.163730E+10 | 0.00 | 1.38 |
July | 0.161711E+10 | 2977067.87 | 0.00 | 4102097.39 | 2095917.73 | 614974.95 | 0.198776E+10 | 0.00 | 1.47 |
August | 0.185601E+10 | 0.00 | 0.00 | 3276632.70 | 0.00 | 0.00 | 0.151730E+10 | 0.00 | 1.55 |
September | 0.271288E+10 | 0.00 | 0.00 | 1854255.16 | 346338.76 | 2240563.76 | 0.934136E+09 | 0.00 | 1.34 |
October | 0.344824E+10 | 0.00 | 0.00 | 396912.78 | 0.00 | 0.171769E+09 | 0.297510E+09 | 0.00 | 0.90 |
November | 0.280323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715761E+09 | 0.00 | 0.00 | 0.69 |
December | 0.147137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192192E+10 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.291460E+11 | 10802873.99 | 0.00 | 15082833.93 | 10077966.12 | 0.718476E+10 | 0.819326E+10 | 0.00 | 0.99 |
Minimum of Months | 0.147137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.344824E+10 | 7825806.12 | 0.00 | 4102097.39 | 7635709.63 | 0.192192E+10 | 0.198776E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132818E+10 | 0.00 | 0.00 | 0.33 |
February | 0.191503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856810E+09 | 0.00 | 0.00 | 0.33 |
March | 0.286707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426029E+09 | 0.00 | 0.00 | 0.38 |
April | 0.239165E+10 | 0.00 | 0.00 | 1290622.24 | 27632.39 | 26072917.88 | 0.102406E+10 | 0.00 | 0.53 |
May | 0.230133E+10 | 0.00 | 0.00 | 2372143.03 | 0.00 | 1562710.97 | 0.147259E+10 | 0.00 | 0.61 |
June | 0.127226E+10 | 5822699.65 | 0.00 | 5301528.49 | 8902565.97 | 0.00 | 0.269734E+10 | 0.00 | 0.87 |
July | 0.110007E+10 | 6598054.95 | 0.00 | 5943724.13 | 781390.34 | 0.00 | 0.241614E+10 | 0.00 | 0.94 |
August | 0.117185E+10 | 0.00 | 0.00 | 5752625.42 | 0.00 | 0.00 | 0.210102E+10 | 0.00 | 1.01 |
September | 0.184927E+10 | 0.00 | 0.00 | 2906910.93 | 947720.76 | 0.00 | 0.136265E+10 | 0.00 | 0.78 |
October | 0.287061E+10 | 0.00 | 0.00 | 197386.39 | 0.00 | 0.101617E+09 | 0.213312E+09 | 0.00 | 0.48 |
November | 0.233119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559233E+09 | 0.00 | 0.00 | 0.37 |
December | 0.144381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147857E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.233216E+11 | 12420754.61 | 0.00 | 23764940.63 | 10659309.46 | 0.477807E+10 | 0.112871E+11 | 0.00 | 0.58 |
Minimum of Months | 0.110007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.287061E+10 | 6598054.95 | 0.00 | 5943724.13 | 8902565.97 | 0.147857E+10 | 0.269734E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182918E+10 | 0.00 | 0.00 | 4359.28 | 0.00 | 0.138500E+10 | 784197.32 | 0.00 | 0.53 |
February | 0.189114E+10 | 0.00 | 0.00 | 19547.50 | 0.00 | 0.959936E+09 | 4950053.56 | 0.00 | 0.52 |
March | 0.281293E+10 | 0.00 | 0.00 | 28200.86 | 0.00 | 0.553349E+09 | 8627990.35 | 0.00 | 0.61 |
April | 0.205985E+10 | 75176.94 | 0.00 | 3360694.18 | 0.00 | 15605013.13 | 0.204438E+10 | 0.00 | 1.01 |
May | 0.235388E+10 | 0.00 | 0.00 | 3685084.55 | 0.00 | 5054420.13 | 0.205749E+10 | 0.00 | 1.12 |
June | 0.186414E+10 | 4354026.68 | 0.00 | 5154553.85 | 11259393.87 | 0.00 | 0.254323E+10 | 0.00 | 1.52 |
July | 0.145597E+10 | 11035821.37 | 0.00 | 5575196.24 | 988252.33 | 0.00 | 0.239522E+10 | 0.00 | 1.58 |
August | 0.155691E+10 | 0.00 | 0.00 | 6123670.81 | 0.00 | 0.00 | 0.231698E+10 | 0.00 | 1.81 |
September | 0.198774E+10 | 0.00 | 0.00 | 4067911.29 | 1198616.37 | 4408351.32 | 0.185998E+10 | 0.00 | 1.45 |
October | 0.269712E+10 | 0.00 | 0.00 | 731773.79 | 0.00 | 0.150604E+09 | 0.530875E+09 | 0.00 | 0.79 |
November | 0.231256E+10 | 0.00 | 0.00 | 8874.16 | 0.00 | 0.651953E+09 | 2791613.03 | 0.00 | 0.59 |
December | 0.139192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160540E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.242133E+11 | 15465024.99 | 0.00 | 28759866.52 | 13446262.57 | 0.533131E+10 | 0.137653E+11 | 0.00 | 1.00 |
Minimum of Months | 0.139192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.281293E+10 | 11035821.37 | 0.00 | 6123670.81 | 11259393.87 | 0.160540E+10 | 0.254323E+10 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.356278E+10 | 0.00 | 0.00 | 1290953.57 | 0.00 | 0.143432E+10 | 0.645903E+09 | 0.00 | 0.60 |
February | 0.336906E+10 | 0.00 | 0.00 | 1941906.46 | 0.00 | 0.822199E+09 | 0.943157E+09 | 0.00 | 0.61 |
March | 0.494896E+10 | 0.00 | 0.00 | 347964.59 | 0.00 | 0.619973E+09 | 0.283506E+09 | 0.00 | 0.68 |
April | 0.319104E+10 | 0.00 | 0.00 | 7529238.82 | 49111.01 | 56678953.68 | 0.395112E+10 | 0.00 | 1.15 |
May | 0.407389E+10 | 0.00 | 0.00 | 5576020.10 | 0.00 | 19936804.61 | 0.301835E+10 | 0.00 | 1.15 |
June | 0.322547E+10 | 7591006.78 | 0.00 | 6462099.97 | 15822519.25 | 850965.34 | 0.333595E+10 | 0.00 | 1.44 |
July | 0.239451E+10 | 7870359.51 | 0.00 | 8186502.82 | 5334651.81 | 0.00 | 0.343335E+10 | 0.00 | 1.55 |
August | 0.238199E+10 | 0.00 | 0.00 | 10286787.85 | 0.00 | 0.00 | 0.365584E+10 | 0.00 | 1.90 |
September | 0.285178E+10 | 881804.64 | 0.00 | 10288588.29 | 901537.66 | 3773108.91 | 0.411815E+10 | 0.00 | 1.79 |
October | 0.396640E+10 | 0.00 | 0.00 | 5084849.54 | 0.00 | 0.175618E+09 | 0.250572E+10 | 0.00 | 1.03 |
November | 0.394772E+10 | 0.00 | 0.00 | 1267419.64 | 0.00 | 0.697897E+09 | 0.600900E+09 | 0.00 | 0.67 |
December | 0.286013E+10 | 0.00 | 0.00 | 527949.60 | 0.00 | 0.208697E+10 | 0.245995E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.407737E+11 | 16343170.93 | 0.00 | 58790281.26 | 22107819.73 | 0.591822E+10 | 0.267379E+11 | 0.00 | 1.09 |
Minimum of Months | 0.238199E+10 | 0.00 | 0.00 | 347964.59 | 0.00 | 0.00 | 0.245995E+09 | 0.00 | 0.56 |
Maximum of Months | 0.494896E+10 | 7870359.51 | 0.00 | 10288588.29 | 15822519.25 | 0.208697E+10 | 0.411815E+10 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245274E+10 | 0.00 | 0.00 | 2429.32 | 0.00 | 0.161169E+10 | 11289110.77 | 0.00 | 0.68 |
February | 0.256306E+10 | 0.00 | 0.00 | 90053.34 | 0.00 | 0.915317E+09 | 0.137656E+09 | 0.00 | 0.68 |
March | 0.362620E+10 | 0.00 | 0.00 | 63965.13 | 0.00 | 0.588694E+09 | 83650329.16 | 0.00 | 0.78 |
April | 0.321690E+10 | 0.00 | 0.00 | 2462338.41 | 36081.38 | 59269542.72 | 0.147503E+10 | 0.00 | 1.17 |
May | 0.333340E+10 | 0.00 | 0.00 | 3005699.08 | 0.00 | 18940838.87 | 0.176981E+10 | 0.00 | 1.31 |
June | 0.253283E+10 | 17495733.76 | 0.00 | 4174034.21 | 5791696.37 | 625195.94 | 0.240341E+10 | 0.00 | 1.70 |
July | 0.184916E+10 | 5611296.70 | 0.00 | 5335159.34 | 3637367.04 | 648190.77 | 0.242602E+10 | 0.00 | 1.80 |
August | 0.200927E+10 | 0.00 | 0.00 | 4554214.31 | 0.00 | 0.00 | 0.195896E+10 | 0.00 | 1.90 |
September | 0.289129E+10 | 56775.61 | 0.00 | 2655877.51 | 1180724.10 | 7233525.82 | 0.128909E+10 | 0.00 | 1.61 |
October | 0.361222E+10 | 0.00 | 0.00 | 712046.71 | 0.00 | 0.176448E+09 | 0.449626E+09 | 0.00 | 1.01 |
November | 0.295786E+10 | 0.00 | 0.00 | 7900.65 | 0.00 | 0.773539E+09 | 40682721.29 | 0.00 | 0.76 |
December | 0.183086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196900E+10 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.328758E+11 | 23163806.06 | 0.00 | 23063718.02 | 10645868.89 | 0.612141E+10 | 0.120452E+11 | 0.00 | 1.17 |
Minimum of Months | 0.183086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.362620E+10 | 17495733.76 | 0.00 | 5335159.34 | 5791696.37 | 0.196900E+10 | 0.242602E+10 | 0.00 | 1.90 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:30
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.922734E+11 | 0.762924E+10 | 0.00 | 0.192071E+12 | 0.258241E+11 |
February | 0.138707E+12 | 0.828282E+10 | 0.00 | 0.181094E+12 | 0.179728E+11 |
March | 0.158921E+12 | 0.708776E+10 | 0.00 | 0.219188E+12 | 0.167546E+11 |
April | 0.400045E+12 | 0.649008E+10 | 0.00 | 0.274065E+12 | 0.118245E+11 |
May | 0.476652E+12 | 0.112039E+11 | 0.00 | 0.293679E+12 | 0.144905E+11 |
June | 0.476067E+12 | 0.846525E+10 | 0.00 | 0.300403E+12 | 0.396072E+11 |
July | 0.482148E+12 | 0.737884E+10 | 0.00 | 0.298932E+12 | 0.667097E+11 |
August | 0.399502E+12 | 0.575792E+10 | 0.00 | 0.276787E+12 | 0.847603E+11 |
September | 0.305358E+12 | 0.673973E+10 | 0.00 | 0.297559E+12 | 0.424817E+11 |
October | 0.146949E+12 | 0.785699E+10 | 0.00 | 0.244387E+12 | 0.980187E+10 |
November | 0.688469E+11 | 0.958693E+10 | 0.00 | 0.206167E+12 | 0.165547E+11 |
December | 0.387251E+11 | 0.119851E+11 | 0.00 | 0.179722E+12 | 0.263503E+11 |
Annual Sum or Average | 0.318419E+13 | 0.984645E+11 | 0.00 | 0.296405E+13 | 0.373132E+12 |
Minimum of Months | 0.387251E+11 | 0.575792E+10 | 0.00 | 0.179722E+12 | 0.980187E+10 |
Maximum of Months | 0.482148E+12 | 0.119851E+11 | 0.00 | 0.300403E+12 | 0.847603E+11 |