Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:22

Tabular Output Report in Format: HTML

Building: OfficeMedium

Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930

Simulation Timestamp: 2024-07-03 12:22:07


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2201.72 441.92 441.92
Net Site Energy 2201.72 441.92 441.92
Total Source Energy 6255.99 1255.67 1255.67
Net Source Energy 6255.99 1255.67 1255.67


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4982.19
Net Conditioned Building Area 4982.19
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 344.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 91.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 566.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 235.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 729.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 27.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 151.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 54.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1857.57 344.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 344.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 91.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 566.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 235.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 134.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 10.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 584.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 27.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 151.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
  Water Heater 54.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 344.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 91.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 566.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 235.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 729.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 27.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 151.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 54.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 160.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 60.03 69.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 151.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 372.84 69.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 160.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 60.03 69.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 151.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 372.84 69.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1857.572 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1857.572 100.00
     
Total On-Site and Utility Electric Sources 1857.572 100.00
Total Electricity End Uses 1857.572 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 271.06 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 271.06 100.00
Total Water End Uses 271.06 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 282.33
Time Setpoint Not Met During Occupied Cooling 22.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 1921.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneHeatingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneElectricSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

SpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ComfortReportSimple55Monthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

OccupantComfortDataSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

WindowEnergyZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

FanReportMonthly

| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |

PumpReportMonthly

| HEATSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AirLoopSystemEnergyAndWaterUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentLoadsMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentEnergyUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

MechanicalVentilationLoadsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:22
RunPeriod RUNPERIOD 1
Weather File Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Latitude [deg] 47.47
Longitude [deg] -122.3
Elevation [m] 122.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 613.07 183.92 122.61 183.92 122.61
Gross Window-Wall Ratio [%] 31.00 31.00 31.00 31.00 31.00
Above Ground Window-Wall Ratio [%] 31.00 31.00 31.00 31.00 31.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 613.07 183.92 122.61 183.92 122.61
Gross Window-Wall Ratio [%] 31.00 31.00 31.00 31.00 31.00
Above Ground Window-Wall Ratio [%] 31.00 31.00 31.00 31.00 31.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1660.73
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_BOTTOM 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 11.0267 18.58 89.6613
TOPFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
FIRSTFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
CORE_MID 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 11.0267 18.58 8.0700
CORE_TOP 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 11.0267 18.58 8.0700
PERIMETER_TOP_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 61.31 61.31 11.0267 18.58 8.0700
PERIMETER_TOP_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 40.87 40.87 11.0267 18.58 8.0695
PERIMETER_TOP_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 61.31 61.31 11.0267 18.58 8.0699
PERIMETER_TOP_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 40.87 40.87 11.0267 18.58 8.0700
PERIMETER_BOT_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 61.31 61.31 11.0267 18.58 8.0700
PERIMETER_BOT_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 40.87 40.87 11.0267 18.58 8.0695
PERIMETER_BOT_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 61.31 61.31 11.0267 18.58 8.0699
PERIMETER_BOT_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 40.87 40.87 11.0267 18.58 8.0700
PERIMETER_MID_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 61.31 61.31 11.0267 18.58 8.0700
PERIMETER_MID_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 40.87 40.87 11.0267 18.58 8.0695
PERIMETER_MID_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 61.31 61.31 11.0267 18.58 8.0699
PERIMETER_MID_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 40.87 40.87 11.0267 18.58 8.0700
Total 4982.19     13667.13   1369.16 0.00 613.07 613.07 11.0267 18.58 24.1769
Conditioned Total 4982.19     13667.13   1369.16 0.00 613.07 613.07 11.0267 18.58 24.1769
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 4982.19     6074.28   608.51 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_BOTTOM 983.54 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 11.0267 18.58 89.6613  
TOPFLOOR_PLENUM 1660.73 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 1660.73 Yes No 1.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
FIRSTFLOOR_PLENUM 1660.73 Yes No 1.00 FIRSTFLOOR_PLENUM GENERAL FIRSTFLOOR_PLENUM 0.0000 0.00 0.0000  
CORE_MID 983.54 Yes Yes 1.00 CORE_MID GENERAL CORE_MID 11.0267 18.58 8.0700  
CORE_TOP 983.54 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 11.0267 18.58 8.0700  
PERIMETER_TOP_ZN_3 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 11.0267 18.58 8.0700  
PERIMETER_TOP_ZN_2 131.26 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 11.0267 18.58 8.0695  
PERIMETER_TOP_ZN_1 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 11.0267 18.58 8.0699  
PERIMETER_TOP_ZN_4 131.25 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 11.0267 18.58 8.0700  
PERIMETER_BOT_ZN_3 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 11.0267 18.58 8.0700  
PERIMETER_BOT_ZN_2 131.26 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 11.0267 18.58 8.0695  
PERIMETER_BOT_ZN_1 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 11.0267 18.58 8.0699  
PERIMETER_BOT_ZN_4 131.25 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 11.0267 18.58 8.0700  
PERIMETER_MID_ZN_3 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 11.0267 18.58 8.0700  
PERIMETER_MID_ZN_2 131.26 Yes Yes 1.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 11.0267 18.58 8.0695  
PERIMETER_MID_ZN_1 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 11.0267 18.58 8.0699  
PERIMETER_MID_ZN_4 131.25 Yes Yes 1.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 11.0267 18.58 8.0700  
Total 4982.19             11.0267 9.29 24.1769  
Conditioned Total 4982.19             11.0267 9.29 24.1769  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 4982.19             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4982.19 4982.19 0.00 4982.19 11.0267 18.58 24.1769
Total 4982.19 4982.19 0.00 4982.19      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 10-AUG-15:50 02-JAN-06:19 - - - - - - - - - - 20-JAN-12:09
Heating 0.00 266214.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 64650.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49443.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41937.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 30391.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4248.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 192087.47 266214.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 266214.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 64650.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 49443.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 324.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 30391.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4248.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 373.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 290.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1793.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 745.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2309.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 87.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 479.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 5.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 171.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 5882.93 373.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 74.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 58.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 359.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 149.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 463.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 96.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 34.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1180.79 74.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 74.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 58.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 359.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 149.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 463.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 96.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 34.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1180.79 74.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 3.39 0.220837 0.300000 1.02 0.588900 0.500000 0.001725 0.000152 1.02 12.89 0.008000
CORE_MID VAV BOX COMPONENT 2.76 0.271657 0.300000 0.827647 0.724420 0.500000 0.001403 0.000268 1.30 12.89 0.008000
CORE_TOP VAV BOX COMPONENT 3.05 0.245639 0.300000 0.915314 0.655036 0.500000 0.001551 0.000517 2.52 12.89 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.11 0.141861 0.300000 0.334112 0.378296 0.500000 0.002686 0.000228 1.11 12.89 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.951934 0.105072 0.300000 0.285580 0.300000 0.500000 0.003626 0.000149 0.727698 12.89 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.50 0.105621 0.300000 0.448750 0.300000 0.500000 0.003607 0.000226 1.10 12.89 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.08 0.092696 0.300000 0.323689 0.300000 0.500000 0.004110 0.000147 0.721108 12.89 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.835923 0.189003 0.300000 0.250777 0.504007 0.500000 0.002016 0.000171 0.835923 12.89 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.793053 0.126122 0.300000 0.237916 0.336326 0.500000 0.003021 0.000113 0.550628 12.89 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.20 0.131456 0.300000 0.360559 0.350549 0.500000 0.002898 0.000169 0.825577 12.89 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 0.888883 0.112518 0.300000 0.266665 0.300048 0.500000 0.003386 0.000111 0.544013 12.89 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 0.862322 0.183217 0.300000 0.258697 0.488578 0.500000 0.002080 0.000176 0.862322 12.89 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 0.965336       0.300000 0.500000 0.003677 0.000116 0.567858 12.89 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 1.37 0.115568 0.300000 0.410125 0.308182 0.500000 0.003297 0.000174 0.851866 12.89 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 0.997353 0.100281 0.300000 0.299206 0.300000 0.500000 0.003799 0.000115 0.561440 12.89 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 17388.78 0.000152 378.16
CORE_MID VAV BOX REHEAT COIL 30627.95 0.000268 716.87
CORE_TOP VAV BOX REHEAT COIL 59105.80 0.000517 1381.58
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 26039.53 0.000228 608.20
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 17013.01 0.000149 397.36
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 25795.05 0.000226 602.50
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 16859.28 0.000147 393.77
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 19558.91 0.000171 456.93
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 12882.04 0.000113 300.94
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 19317.57 0.000169 451.29
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 12727.73 0.000111 297.33
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 20174.75 0.000176 471.30
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 13283.94 0.000116 310.32
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 19930.86 0.000174 465.61
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 13134.24 0.000115 306.82
PACU_VAV_BOT HEATING COIL 13739.17 0.000120 240.93
PACU_VAV_MID HEATING COIL 14623.05 0.000128 254.96
PACU_VAV_TOP HEATING COIL 12938.69 0.000113 228.53
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PACU_VAV_BOT 3.56 2.13 7.11 3.29 6.05 6.05 0.300000 0.544199 6.05
PACU_VAV_MID 3.48 2.09 6.95 4.14 5.70 5.70 0.300000 0.726748 5.70
PACU_VAV_TOP 3.85 2.31 7.69 6.19 6.76 6.76 0.300000 0.914592 6.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PACU_VAV_BOT_OA_CONTROLLER 6.05
PACU_VAV_MID_OA_CONTROLLER 5.70
PACU_VAV_TOP_OA_CONTROLLER 6.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
PACU_VAV_BOT COOLING COIL 6.05 102669.89 0.800359 2.01 34219.87 0.800359
PACU_VAV_MID COOLING COIL 5.70 97360.23 0.800414 1.90 32450.17 0.800414
PACU_VAV_TOP COOLING COIL 6.76 113706.52 0.800062 2.25 37898.38 0.800062
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
PACU_VAV_BOT FAN 6.05
PACU_VAV_MID FAN 5.70
PACU_VAV_TOP FAN 6.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s]
PACU_VAV_BOT_HEATC_CONTROLLER 0.000120
PACU_VAV_MID_HEATC_CONTROLLER 0.000128
PACU_VAV_TOP_HEATC_CONTROLLER 0.000113
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.003194 0.383329
SWHSYS1 0.000054 0.006435
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
HEATSYS1 PUMP 0.003194 962.02 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 365140.36 365140.36 0.003194
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000054 6.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000054
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 11.40 8.10 5.40 4.50 5.80 8.30 10.90 13.00 15.60 17.70 18.80 15.10


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 47.47 -122.32 -8.00 122.00 99868 1.1870


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 11.22 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeMedium 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 18 167 24


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_BOTTOM 0.0 0.00 0.00 0.00 24.96 16.64 1.37 1 1 1 4.57 45.34 4.57 28.70 0.00 2.74 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
2 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 11.28 1 1 1 0.00 49.91 0.00 33.27 10.67 11.89 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 10 0 0 No
3 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 7.32 1 1 1 0.00 49.91 0.00 33.27 6.71 7.92 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
4 FIRSTFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 3.35 1 1 1 0.00 49.91 0.00 33.27 2.74 3.96 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
5 CORE_MID 0.0 0.00 0.00 0.00 24.96 16.64 5.33 1 1 1 4.57 45.34 4.57 28.70 3.96 6.71 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
6 CORE_TOP 0.0 0.00 0.00 0.00 24.96 16.64 9.30 1 1 1 4.57 45.34 4.57 28.70 7.92 10.67 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
7 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 9.30 1 1 1 0.00 49.91 28.70 33.27 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 75.61 61.31 6 1 0 Yes
8 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 9.30 1 1 1 45.34 49.91 0.00 33.27 7.92 10.67 2.74 360.08 TARP TARP 131.26 91.28 50.41 40.87 6 1 0 Yes
9 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 9.30 1 1 1 0.00 49.91 0.00 4.57 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 75.61 61.31 6 1 0 Yes
10 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 9.30 1 1 1 0.00 4.57 0.00 33.27 7.92 10.67 2.74 360.05 TARP TARP 131.25 91.28 50.41 40.87 6 1 0 Yes
11 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 1.37 1 1 1 0.00 49.91 28.70 33.27 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 71.71 61.31 6 5 0 Yes
12 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 1.37 1 1 1 45.34 49.91 0.00 33.27 0.00 2.74 2.74 360.08 TARP TARP 131.26 91.28 48.45 40.87 6 3 0 Yes
13 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 1.37 1 1 1 0.00 49.91 0.00 4.57 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 71.71 61.31 6 5 0 Yes
14 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 1.37 1 1 1 0.00 4.57 0.00 33.27 0.00 2.74 2.74 360.05 TARP TARP 131.25 91.28 48.45 40.87 6 3 0 Yes
15 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 5.33 1 1 1 0.00 49.91 28.70 33.27 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 75.61 61.31 6 1 0 Yes
16 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 5.33 1 1 1 45.34 49.91 0.00 33.27 3.96 6.71 2.74 360.08 TARP TARP 131.26 91.28 50.41 40.87 6 1 0 Yes
17 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 5.33 1 1 1 0.00 49.91 0.00 4.57 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 75.61 61.31 6 1 0 Yes
18 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 5.33 1 1 1 0.00 4.57 0.00 33.27 3.96 6.71 2.74 360.05 TARP TARP 131.25 91.28 50.41 40.87 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_BOTTOM 983.54 52.9 18.579 5.382E-002 11.027 89.661 0.000 0.000 0.000 0.000 100.688 No
2 TOPFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 MIDFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 FIRSTFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
5 CORE_MID 983.54 52.9 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
6 CORE_TOP 983.54 52.9 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
7 PERIMETER_TOP_ZN_3 207.34 11.2 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
8 PERIMETER_TOP_ZN_2 131.26 7.1 18.579 5.382E-002 11.027 8.069 0.000 0.000 0.000 0.000 19.096 No
9 PERIMETER_TOP_ZN_1 207.34 11.2 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
10 PERIMETER_TOP_ZN_4 131.25 7.1 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
11 PERIMETER_BOT_ZN_3 207.34 11.2 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
12 PERIMETER_BOT_ZN_2 131.26 7.1 18.579 5.382E-002 11.027 8.069 0.000 0.000 0.000 0.000 19.096 No
13 PERIMETER_BOT_ZN_1 207.34 11.2 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
14 PERIMETER_BOT_ZN_4 131.25 7.1 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
15 PERIMETER_MID_ZN_3 207.34 11.2 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
16 PERIMETER_MID_ZN_2 131.26 7.1 18.579 5.382E-002 11.027 8.069 0.000 0.000 0.000 0.000 19.096 No
17 PERIMETER_MID_ZN_1 207.34 11.2 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No
18 PERIMETER_MID_ZN_4 131.25 7.1 18.579 5.382E-002 11.027 8.070 0.000 0.000 0.000 0.000 19.097 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 983.54 52.9 10845.123 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10845.123
2 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 983.54 52.9 10845.123 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10845.123
3 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 983.54 52.9 10845.123 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10845.123
4 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 207.34 11.2 2286.247 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2286.247
5 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 131.26 7.1 1447.384 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1447.384
6 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 207.34 11.2 2286.247 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2286.247
7 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 131.25 7.1 1447.289 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1447.289
8 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 207.34 11.2 2286.247 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2286.247
9 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 131.26 7.1 1447.384 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1447.384
10 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 207.34 11.2 2286.247 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2286.247
11 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 131.25 7.1 1447.289 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1447.289
12 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 207.34 11.2 2286.247 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2286.247
13 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 131.26 7.1 1447.384 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1447.384
14 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 207.34 11.2 2286.247 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2286.247
15 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 131.25 7.1 1447.289 11.027 204.862 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1447.289


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH CORE_BOTTOM 983.54 52.9 76724.000 78.008 1449.300 0.000 0.500 0.000 0.500 ElevatorLift 0.000 4561.242
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH CORE_BOTTOM 983.54 52.9 3200.000 3.254 60.447 0.000 0.500 0.000 0.500 ElevatorLift 2563.936 3200.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_24_7 CORE_BOTTOM 983.54 52.9 324.000 0.329 6.120 0.000 0.500 0.000 0.500 ElevatorLightsFan 324.000 324.000
4 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
5 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
6 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
7 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
8 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
9 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
10 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
11 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
12 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
13 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
14 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
15 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
16 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
17 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
18 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 9.815 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 17 3 3 0.167 0.3762 0.900 0.900 0.700 0.700 Rough
8 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.7871 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 21 4 7 0.167 0.7871 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 22 4 7 0.167 0.7871 0.900 0.900 0.700 0.700 Smooth
11 PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 39 2 7 0.167 0.3192 0.000 0.900 0.000 0.700 MediumRough
12 PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 40 2 7 0.167 0.3371 0.000 0.900 0.000 0.700 MediumRough
13 PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 41 2 7 0.167 0.3192 0.000 0.900 0.000 0.700 MediumRough
14 PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 42 2 7 0.167 0.3371 0.000 0.900 0.000 0.700 MediumRough
15 CORE_BOT_ZN_5_FLOOR_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.1019
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 2.599
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.037
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.037
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 1.037
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.056
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.890
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.056
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.890
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 9.8148919 9.8148919 9.8148919  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
23 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
24 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
25 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
26 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
27 2 51.553741 0.22121684 1.2284947 -0.25833933
28 1 -128.86110 0.21944682 -5.1479470 1.1228340
29 0 81.526494 0.16043334E-01 4.4519351  
30 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
31 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
32 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
33 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
34 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
35 2 1.2284947 0.22121684 51.553741 -0.25833933
36 1 -5.1479470 0.21944682 -128.86110 1.1228340
37 0 4.4519351 0.16043334E-01 81.526494  
38 3 -0.61039648E-06 0.16815647E-08 -0.37447326E-05 0.10149002E-16
39 2 0.76989337 0.22941655E-02 1.0458372 -0.71793422E-06
40 1 -21.843031 0.15409339 -6.3407615 0.20050303
41 0 21.373924 0.14439780 5.5957134  
42 7 -0.29735092E-12 0.24575595E-14 -0.94456721E-13 0.15324278E-15
43 6 0.28546880E-07 0.22114619E-09 0.65405332E-08 -0.13451374E-12
44 5 -0.18947583E-03 0.18937623E-05 -0.97466953E-04 0.64660656E-08
45 4 0.29140875 0.92215111E-03 0.99417931E-01 -0.33466744E-04
46 3 -7.2517161 0.28579858E-01 -2.3345767 0.28937395E-01
47 2 40.822959 0.10163225 15.247323 -0.33280368
48 1 -80.508872 0.45869584E-01 -29.125752 1.0778326
49 0 46.824339 0.92288667E-03 16.291614  
50 7 -0.29735092E-12 0.24575595E-14 -0.94456721E-13 0.15324278E-15
51 6 0.28546880E-07 0.22114619E-09 0.65405332E-08 -0.13451374E-12
52 5 -0.18947583E-03 0.18937623E-05 -0.97466953E-04 0.64660656E-08
53 4 0.29140875 0.92215111E-03 0.99417931E-01 -0.33466744E-04
54 3 -7.2517161 0.28579858E-01 -2.3345767 0.28937395E-01
55 2 40.822959 0.10163225 15.247323 -0.33280368
56 1 -80.508872 0.45869584E-01 -29.125752 1.0778326
57 0 46.824339 0.92288667E-03 16.291614  
58 7 -0.29735092E-12 0.24575595E-14 -0.94456721E-13 0.15324278E-15
59 6 0.28546880E-07 0.22114619E-09 0.65405332E-08 -0.13451374E-12
60 5 -0.18947583E-03 0.18937623E-05 -0.97466953E-04 0.64660656E-08
61 4 0.29140875 0.92215111E-03 0.99417931E-01 -0.33466744E-04
62 3 -7.2517161 0.28579858E-01 -2.3345767 0.28937395E-01
63 2 40.822959 0.10163225 15.247323 -0.33280368
64 1 -80.508872 0.45869584E-01 -29.125752 1.0778326
65 0 46.824339 0.92288667E-03 16.291614  
66 7 -0.13059908E-08 -0.16504735E-15 0.90649122E-14 -0.12541312E-15
67 6 0.89164571E-05 0.61445766E-08 0.31804070E-02 -0.26679919E-04
68 5 -0.64531733E-03 0.36428408E-05 -0.22318667 0.19514025E-02
69 4 0.14868215E-01 0.16589759E-03 4.8205855 -0.45178851E-01
70 3 -0.13063200 0.13198961E-02 -37.970795 0.39809422
71 2 0.46393162 0.21965806E-02 116.38542 -1.4166214
72 1 -0.66966470 0.66967549E-03 -143.84930 2.0480865
73 0 0.32650513 0.16166393E-04 60.838472  
74 7 -0.12346633E-08 -0.14425327E-15 0.91357699E-14 -0.10087110E-15
75 6 0.94177090E-05 0.64929528E-08 0.31789869E-02 -0.26668006E-04
76 5 -0.68205191E-03 0.38502154E-05 -0.22310594 0.19506899E-02
77 4 0.15716902E-01 0.17535208E-03 4.8192406 -0.45165923E-01
78 3 -0.13809356 0.13952366E-02 -37.963195 0.39801023
79 2 0.49043520 0.23220647E-02 116.37063 -1.4164235
80 1 -0.70792287 0.70803996E-03 -143.84059 2.0479434
81 0 0.34515858 0.17069463E-04 60.838472  
82 7 -0.13059908E-08 -0.16504702E-15 0.90649122E-14 -0.12541312E-15
83 6 0.89164571E-05 0.61445766E-08 0.31804070E-02 -0.26679919E-04
84 5 -0.64531733E-03 0.36428408E-05 -0.22318667 0.19514025E-02
85 4 0.14868215E-01 0.16589759E-03 4.8205855 -0.45178851E-01
86 3 -0.13063200 0.13198961E-02 -37.970795 0.39809422
87 2 0.46393162 0.21965806E-02 116.38542 -1.4166214
88 1 -0.66966470 0.66967549E-03 -143.84930 2.0480865
89 0 0.32650513 0.16166393E-04 60.838472  
90 7 -0.12345751E-08 -0.14398051E-15 0.92894684E-14 -0.10085648E-15
91 6 0.94183649E-05 0.64934092E-08 0.31789851E-02 -0.26667991E-04
92 5 -0.68209995E-03 0.38504865E-05 -0.22310583 0.19506890E-02
93 4 0.15718012E-01 0.17536444E-03 4.8192388 -0.45165906E-01
94 3 -0.13810332 0.13953351E-02 -37.963185 0.39801012
95 2 0.49046985 0.23222288E-02 116.37061 -1.4164232
96 1 -0.70797289 0.70809005E-03 -143.84058 2.0479432
97 0 0.34518296 0.17070678E-04 60.838472  
98 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
99 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
100 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
101 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
102 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
103 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
104 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
105 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
106 0 0.84795330E-02 0.69040512E-07 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.57_SHGC_EAST_0.39 35 1 VerySmooth 3.241 3.241 1.000 0.391    
2 WINDOW_U_0.57_SHGC_SOUTH_0.39 36 1 VerySmooth 3.241 3.241 1.000 0.391    
3 WINDOW_U_0.57_SHGC_WEST_0.39 37 1 VerySmooth 3.241 3.241 1.000 0.391    
4 WINDOW_U_0.57_SHGC_NORTH_0.39 38 1 VerySmooth 3.241 3.241 1.000 0.391    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.00000E-003 0.30403 0.46623 0.46623 0.42900 0.13485 0.17261 0.00000 0.84000 0.84000 1.43763E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 27.185 0.8451


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
2 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
3 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
4 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
5 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
6 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
7 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
8 PERIMETER_TOP_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
9 PERIMETER_TOP_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
10 PERIMETER_TOP_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
11 PERIMETER_TOP_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
12 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
13 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
14 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
15 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
16 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
17 BUILDING_ROOF 0 1660.73 183.01 0.00 0 1.22 166.37 39.93 0.00 0 No No
18 PERIMETER_MID_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
19 PERIMETER_MID_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
20 PERIMETER_MID_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
21 PERIMETER_MID_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
22 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
23 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
24 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
25 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
26 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
27 iz-PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
28 iz-PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
29 iz-PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
30 iz-PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
31 iz-CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
32 PERIMETER_BOT_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
33 PERIMETER_BOT_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
34 PERIMETER_BOT_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
35 PERIMETER_BOT_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
36 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
37 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
38 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
39 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
40 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
41 iz-PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
42 iz-PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
43 iz-PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
44 iz-PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
45 iz-CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
46 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
47 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
48 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
49 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
50 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
51 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
52 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
53 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
54 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
55 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
56 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
57 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
58 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
59 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
60 PERIMETER_TOP_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 3 No No
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 2 No No
62 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
64 iz-CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
65 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
66 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
68 PERIMETER_TOP_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.45 3 No No
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.45 2 No No
70 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
72 iz-CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
73 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
74 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
76 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 3 No No
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 2 No No
78 PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
80 iz-CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
81 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
82 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
84 PERIMETER_TOP_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.45 3 No No
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.45 2 No No
86 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
88 iz-CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
89 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
90 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
92 PERIMETER_BOT_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 3 No No
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 2 No No
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 2 No No
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 2 No No
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 0 No No
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 0 No No
98 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
100 iz-CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
101 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
102 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
104 PERIMETER_BOT_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.45 3 No No
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.45 2 No No
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.45 2 No No
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.45 0 No No
108 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
110 iz-CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
111 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
112 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
114 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 3 No No
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 2 No No
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 2 No No
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 2 No No
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 0 No No
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 0 No No
120 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
122 iz-CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
123 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
124 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
126 PERIMETER_BOT_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.45 3 No No
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.45 2 No No
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.45 2 No No
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.45 0 No No
130 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
132 iz-CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
133 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
134 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
136 PERIMETER_MID_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 3 No No
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.45 2 No No
138 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
140 iz-CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
141 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
142 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
144 PERIMETER_MID_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.45 3 No No
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.45 2 No No
146 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
147 iz-PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
148 iz-CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
149 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
150 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
152 PERIMETER_MID_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 3 No No
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.45 2 No No
154 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
156 iz-CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
157 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
158 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.45 0 No No
160 PERIMETER_MID_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.45 3 No No
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.45 2 No No
162 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
163 iz-PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
164 iz-CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
165 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
166 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.45 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 207.34 11.2 7.798E-002 3.761E-004 5.696E-004 0.494 0.000 0.000 0.224 0.000
2 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 131.26 7.1 5.199E-002 3.961E-004 5.696E-004 0.520 0.000 0.000 0.224 0.000
3 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 207.34 11.2 7.798E-002 3.761E-004 5.696E-004 0.494 0.000 0.000 0.224 0.000
4 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 131.25 7.1 5.199E-002 3.961E-004 5.696E-004 0.520 0.000 0.000 0.224 0.000
5 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 207.34 11.2 7.798E-002 3.761E-004 5.538E-004 0.494 0.000 0.000 0.224 0.000
6 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 131.26 7.1 5.199E-002 3.961E-004 5.577E-004 0.520 0.000 0.000 0.224 0.000
7 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 207.34 11.2 7.798E-002 3.761E-004 5.538E-004 0.494 0.000 0.000 0.224 0.000
8 PERIMETER_BOT_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_BOT_ZN_1 207.34 11.2 0.679 3.273E-003 4.819E-003 4.296 1.000 0.000 0.000 0.000
9 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 131.25 7.1 5.199E-002 3.961E-004 5.577E-004 0.520 0.000 0.000 0.224 0.000
10 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 207.34 11.2 7.798E-002 3.761E-004 5.696E-004 0.494 0.000 0.000 0.224 0.000
11 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 131.26 7.1 5.199E-002 3.961E-004 5.696E-004 0.520 0.000 0.000 0.224 0.000
12 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 207.34 11.2 7.798E-002 3.761E-004 5.696E-004 0.494 0.000 0.000 0.224 0.000
13 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 131.25 7.1 5.199E-002 3.961E-004 5.696E-004 0.520 0.000 0.000 0.224 0.000
14 FIRSTFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL FIRSTFLOOR_PLENUM 1660.73 0.0 0.116 6.957E-005 5.696E-004 0.205 0.000 0.000 0.224 0.000
15 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 1660.73 0.0 0.116 6.957E-005 5.696E-004 0.205 0.000 0.000 0.224 0.000
16 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 1660.73 0.0 0.116 6.957E-005 6.199E-005 0.205 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_BOTTOM Mixing/Well-Stirred
2 TOPFLOOR_PLENUM Mixing/Well-Stirred
3 MIDFLOOR_PLENUM Mixing/Well-Stirred
4 FIRSTFLOOR_PLENUM Mixing/Well-Stirred
5 CORE_MID Mixing/Well-Stirred
6 CORE_TOP Mixing/Well-Stirred
7 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
8 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
9 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
10 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
11 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
12 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
13 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
14 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
15 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
16 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
17 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
18 PERIMETER_MID_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2500
2 Zone CORE_BOTTOM 1.2500
3 Zone CORE_MID 1.2500
4 Zone CORE_TOP 1.2500
5 Zone PERIMETER_TOP_ZN_3 1.2500
6 Zone PERIMETER_TOP_ZN_2 1.2500
7 Zone PERIMETER_TOP_ZN_1 1.2500
8 Zone PERIMETER_TOP_ZN_4 1.2500
9 Zone PERIMETER_BOT_ZN_3 1.2500
10 Zone PERIMETER_BOT_ZN_2 1.2500
11 Zone PERIMETER_BOT_ZN_1 1.2500
12 Zone PERIMETER_BOT_ZN_4 1.2500
13 Zone PERIMETER_MID_ZN_3 1.2500
14 Zone PERIMETER_MID_ZN_2 1.2500
15 Zone PERIMETER_MID_ZN_1 1.2500
16 Zone PERIMETER_MID_ZN_4 1.2500


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.1500
2 Zone CORE_BOTTOM 1.1500
3 Zone CORE_MID 1.1500
4 Zone CORE_TOP 1.1500
5 Zone PERIMETER_TOP_ZN_3 1.1500
6 Zone PERIMETER_TOP_ZN_2 1.1500
7 Zone PERIMETER_TOP_ZN_1 1.1500
8 Zone PERIMETER_TOP_ZN_4 1.1500
9 Zone PERIMETER_BOT_ZN_3 1.1500
10 Zone PERIMETER_BOT_ZN_2 1.1500
11 Zone PERIMETER_BOT_ZN_1 1.1500
12 Zone PERIMETER_BOT_ZN_4 1.1500
13 Zone PERIMETER_MID_ZN_3 1.1500
14 Zone PERIMETER_MID_ZN_2 1.1500
15 Zone PERIMETER_MID_ZN_1 1.1500
16 Zone PERIMETER_MID_ZN_4 1.1500


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_BOTTOM Cooling 40053.54104 46061.57220 2.95104 3.39370 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 983.53657 52.93867 0.42469 0.00000
2 CORE_BOTTOM Heating 5914.71781 7393.39726 0.42704 0.53379 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 983.53657 52.93867 0.42469 0.00000
3 CORE_MID Cooling 32587.05603 37475.11443 2.39898 2.75882 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 983.53657 52.93867 0.42469 0.00000
4 CORE_MID Heating 14290.44763 17863.05954 1.04017 1.30021 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 983.53657 52.93867 0.42469 0.00000
5 CORE_TOP Cooling 35709.22781 41065.61198 2.65308 3.05105 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 29.29600 8.82133E-003 983.53657 52.93867 0.42469 0.00000
6 CORE_TOP Heating 27484.32922 34355.41152 2.01682 2.52103 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 983.53657 52.93867 0.42469 0.00000
7 PERIMETER_TOP_ZN_3 Cooling 9739.07867 11199.94047 0.72357 0.83211 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 29.40000 8.82150E-003 207.33814 11.15994 8.95286E-002 0.00000
8 PERIMETER_TOP_ZN_3 Heating 12088.86881 15111.08601 0.89097 1.11371 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
9 PERIMETER_TOP_ZN_2 Cooling 11141.57811 12812.81482 0.82777 0.95193 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 23.97467 8.81286E-003 131.26219 7.06516 5.66790E-002 0.00000
10 PERIMETER_TOP_ZN_2 Heating 7897.94702 9872.43378 0.58216 0.72770 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.26219 7.06516 5.66790E-002 0.00000
11 PERIMETER_TOP_ZN_1 Cooling 17507.42785 20133.54203 1.30072 1.49583 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 29.14000 8.82108E-003 207.33814 11.15994 8.95286E-002 0.00000
12 PERIMETER_TOP_ZN_1 Heating 11975.58838 14969.48547 0.88258 1.10323 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
13 PERIMETER_TOP_ZN_4 Cooling 12628.36057 14522.61465 0.93823 1.07896 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 28.08267 8.81938E-003 131.25358 7.06470 5.66753E-002 0.00000
14 PERIMETER_TOP_ZN_4 Heating 7826.70925 9783.38656 0.57689 0.72111 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.25358 7.06470 5.66753E-002 0.00000
15 PERIMETER_BOT_ZN_3 Cooling 7226.09447 8310.00864 0.53687 0.61740 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 29.40000 8.82150E-003 207.33814 11.15994 8.95286E-002 0.00000
16 PERIMETER_BOT_ZN_3 Heating 9084.04651 11355.05814 0.66874 0.83592 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
17 PERIMETER_BOT_ZN_2 Cooling 9282.05935 10674.36826 0.68961 0.79305 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 22.36267 8.81033E-003 131.26219 7.06516 5.66790E-002 0.00000
18 PERIMETER_BOT_ZN_2 Heating 5982.49731 7478.12164 0.44050 0.55063 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.26219 7.06516 5.66790E-002 0.00000
19 PERIMETER_BOT_ZN_1 Cooling 14066.72597 16176.73487 1.04510 1.20186 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 29.31333 8.82136E-003 207.33814 11.15994 8.95286E-002 0.00000
20 PERIMETER_BOT_ZN_1 Heating 8972.23787 11215.29734 0.66046 0.82558 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
21 PERIMETER_BOT_ZN_4 Cooling 10403.60477 11964.14549 0.77294 0.88888 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 26.90400 8.81750E-003 131.25358 7.06470 5.66753E-002 0.00000
22 PERIMETER_BOT_ZN_4 Heating 5911.00416 7388.75520 0.43521 0.54401 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.25358 7.06470 5.66753E-002 0.00000
23 PERIMETER_MID_ZN_3 Cooling 8156.34325 9379.79473 0.60598 0.69688 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 29.40000 8.82150E-003 207.33814 11.15994 8.95286E-002 0.00000
24 PERIMETER_MID_ZN_3 Heating 9370.56436 11713.20544 0.68986 0.86232 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
25 PERIMETER_MID_ZN_2 Cooling 11298.43687 12993.20240 0.83942 0.96534 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 23.35067 8.81188E-003 131.26219 7.06516 5.66790E-002 0.00000
26 PERIMETER_MID_ZN_2 Heating 6169.49889 7711.87361 0.45429 0.56786 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.26219 7.06516 5.66790E-002 0.00000
27 PERIMETER_MID_ZN_1 Cooling 16000.50878 18400.58510 1.18877 1.36708 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 29.05333 8.82094E-003 207.33814 11.15994 8.95286E-002 0.00000
28 PERIMETER_MID_ZN_1 Heating 9257.56404 11571.95504 0.68149 0.85187 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
29 PERIMETER_MID_ZN_4 Cooling 11673.16308 13424.13755 0.86726 0.99735 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 27.94400 8.81916E-003 131.25358 7.06470 5.66753E-002 0.00000
30 PERIMETER_MID_ZN_4 Heating 6100.13617 7625.17021 0.44915 0.56144 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.25358 7.06470 5.66753E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PACU_VAV_BOT Cooling Sensible 86270.73 6.04547 6.04547 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 PACU_VAV_BOT Heating Sensible 19092.03 3.28993 3.28993 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:30:00
3 PACU_VAV_MID Cooling Sensible 81715.32 5.70169 5.70169 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 PACU_VAV_MID Heating Sensible 19357.81 4.14369 4.14369 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:20:00
5 PACU_VAV_TOP Cooling Sensible 95775.20 6.76451 6.76451 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 PACU_VAV_TOP Heating Sensible 19428.26 6.18677 6.18677 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 01:20:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.39370
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22084
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.01811
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58890
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.72525E-003
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.52125E-004
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.01811
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17388.77531
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.52125E-004
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 378.16014
15 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.75882
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27166
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.82765
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.72442
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.40250E-003
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.67947E-004
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.30021
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30627.95178
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.67947E-004
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 716.86528
29 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.05105
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24564
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.91531
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65504
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.55106E-003
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.17083E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.52103
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 59105.80222
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.17083E-004
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1381.58071
43 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.11371
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14186
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.33411
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37830
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.68572E-003
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.27805E-004
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.11371
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 26039.52696
55 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.27805E-004
56 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 608.20282
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.95193
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10507
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28558
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.62608E-003
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.48837E-004
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.72770
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17013.01499
69 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.48837E-004
70 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 397.36318
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.49583
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10562
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.44875
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.60723E-003
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.25666E-004
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.10323
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 25795.05407
83 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.25666E-004
84 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 602.49628
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.07896
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.26956E-002
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.32369
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.11023E-003
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.47492E-004
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.72111
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16859.27759
97 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.47492E-004
98 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 393.77459
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.83592
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18900
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.25078
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50401
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.01584E-003
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.71110E-004
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.83592
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19558.90894
111 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.71110E-004
112 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 456.92793
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.79305
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12612
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23792
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33633
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.02087E-003
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.12698E-004
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.55063
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
124 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12882.04200
125 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.12698E-004
126 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 300.93546
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.20186
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13146
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.36056
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35055
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.89831E-003
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.68999E-004
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.82558
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
138 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19317.57061
139 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.68999E-004
140 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 451.29465
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.88888
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11252
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26666
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30005
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.38613E-003
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.11348E-004
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.54401
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
152 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12727.72984
153 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.11348E-004
154 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 297.33351
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.86232
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18322
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.25870
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.48858
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.07951E-003
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.76497E-004
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.86232
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
166 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20174.74786
167 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.76497E-004
168 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 471.30298
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.96534
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.67713E-003
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.16214E-004
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.56786
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
177 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13283.94416
178 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.16214E-004
179 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 310.31652
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.36708
181 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11557
182 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41012
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30818
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.29675E-003
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.74364E-004
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.85187
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
191 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19930.85721
192 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.74364E-004
193 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 465.61013
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.99735
195 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10028
196 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30000
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.29921
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.79934E-003
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.14904E-004
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.56144
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.88890
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
205 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13134.24081
206 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.14904E-004
207 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 306.82216
208 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.55671
209 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.13403
210 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 7.11342
211 AirLoopHVAC PACU_VAV_BOT Adjusted Heating Design Air Flow Rate [m3/s] 3.28993
212 AirLoopHVAC PACU_VAV_BOT Adjusted Cooling Design Air Flow Rate [m3/s] 6.04547
213 AirLoopHVAC PACU_VAV_BOT Adjusted Main Design Air Flow Rate [m3/s] 6.04547
214 AirLoopHVAC PACU_VAV_BOT User Heating Air Flow Ratio [] 0.30000
215 AirLoopHVAC PACU_VAV_BOT Calculated Heating Air Flow Ratio [] 0.54420
216 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.47546
217 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.08528
218 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Flow Rates [m3/s] 6.95092
219 AirLoopHVAC PACU_VAV_MID Adjusted Heating Design Air Flow Rate [m3/s] 4.14369
220 AirLoopHVAC PACU_VAV_MID Adjusted Cooling Design Air Flow Rate [m3/s] 5.70169
221 AirLoopHVAC PACU_VAV_MID Adjusted Main Design Air Flow Rate [m3/s] 5.70169
222 AirLoopHVAC PACU_VAV_MID User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC PACU_VAV_MID Calculated Heating Air Flow Ratio [] 0.72675
224 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.84574
225 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.30745
226 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 7.69149
227 AirLoopHVAC PACU_VAV_TOP Adjusted Heating Design Air Flow Rate [m3/s] 6.18677
228 AirLoopHVAC PACU_VAV_TOP Adjusted Cooling Design Air Flow Rate [m3/s] 6.76451
229 AirLoopHVAC PACU_VAV_TOP Adjusted Main Design Air Flow Rate [m3/s] 6.76451
230 AirLoopHVAC PACU_VAV_TOP User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC PACU_VAV_TOP Calculated Heating Air Flow Ratio [] 0.91459
232 AirLoopHVAC PACU_VAV_BOT Design Supply Air Flow Rate [m3/s] 6.04547
233 AirLoopHVAC PACU_VAV_MID Design Supply Air Flow Rate [m3/s] 5.70169
234 AirLoopHVAC PACU_VAV_TOP Design Supply Air Flow Rate [m3/s] 6.76451
235 Controller:OutdoorAir PACU_VAV_BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.04547
236 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 6.04547
237 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 102669.88656
238 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80036
239 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 2.01495
240 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 34219.87319
241 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80036
242 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Rated Capacity [W] 13739.17347
243 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.20196E-004
244 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size U-Factor Times Area Value [W/K] 240.92685
245 Fan:VariableVolume PACU_VAV_BOT FAN Design Size Maximum Flow Rate [m3/s] 6.04547
246 Controller:WaterCoil PACU_VAV_BOT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.20196E-004
247 Controller:OutdoorAir PACU_VAV_MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.70169
248 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.70169
249 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 97360.23322
250 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80041
251 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.90037
252 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 32450.16573
253 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80041
254 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Rated Capacity [W] 14623.05047
255 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.27929E-004
256 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size U-Factor Times Area Value [W/K] 254.95874
257 Fan:VariableVolume PACU_VAV_MID FAN Design Size Maximum Flow Rate [m3/s] 5.70169
258 Controller:WaterCoil PACU_VAV_MID_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.27929E-004
259 Controller:OutdoorAir PACU_VAV_TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.76451
260 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 6.76451
261 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 113706.52209
262 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80006
263 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 2.25461
264 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 37898.38381
265 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80006
266 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Rated Capacity [W] 12938.69268
267 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.13193E-004
268 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size U-Factor Times Area Value [W/K] 228.53011
269 Fan:VariableVolume PACU_VAV_TOP FAN Design Size Maximum Flow Rate [m3/s] 6.76451
270 Controller:WaterCoil PACU_VAV_TOP_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.13193E-004
271 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.19441E-003
272 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.38333
273 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.19441E-003
274 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 962.01516
275 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
276 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 365140.36098
277 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 365140.36000
278 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.19441E-003
279 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 5.36267E-005
280 PlantLoop SWHSYS1 Plant Loop Volume [m3] 6.43520E-003
281 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 5.36267E-005
282 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 6.85023
283 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 5.36267E-005


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 16502.56
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 29055.68
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 56071.97
4 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 24703.03
5 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 16139.81
6 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 24471.11
7 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 15993.97
8 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 18555.02
9 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 12220.85
10 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 18326.07
11 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 12074.46
12 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 19139.25
13 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 12602.13
14 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 18907.88
15 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 12460.11
16 Coil:Heating:Water PACU_VAV_BOT HEATING COIL 11950.44
17 Coil:Heating:Water PACU_VAV_MID HEATING COIL 12583.01
18 Coil:Heating:Water PACU_VAV_TOP HEATING COIL 11406.24


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL N/A N/A 101024.46 344709.78 11.13 2.88 3.19 3.35 3.54 9.83 10.87 11.44 12.06 6.8925 5.4568 3.6590 1.5119
2 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL N/A N/A 95823.97 326964.97 11.15 2.88 3.19 3.36 3.54 9.84 10.88 11.45 12.08 6.5006 5.1479 3.4516 1.4234
3 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL N/A N/A 111830.72 381582.27 11.11 2.88 3.18 3.34 3.53 9.81 10.84 11.41 12.03 7.7123 6.1031 4.0911 1.6970


Zone Surfaces

Zone Name # Surfaces
1 CORE_BOTTOM 7
2 TOPFLOOR_PLENUM 10
3 MIDFLOOR_PLENUM 14
4 FIRSTFLOOR_PLENUM 14
5 CORE_MID 7
6 CORE_TOP 7
7 PERIMETER_TOP_ZN_3 8
8 PERIMETER_TOP_ZN_2 8
9 PERIMETER_TOP_ZN_1 8
10 PERIMETER_TOP_ZN_4 8
11 PERIMETER_BOT_ZN_3 12
12 PERIMETER_BOT_ZN_2 10
13 PERIMETER_BOT_ZN_1 12
14 PERIMETER_BOT_ZN_4 10
15 PERIMETER_MID_ZN_3 8
16 PERIMETER_MID_ZN_2 8
17 PERIMETER_MID_ZN_1 8
18 PERIMETER_MID_ZN_4 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction CORE_BOT_ZN_5_FLOOR_FFACTOR 5.650E-003 5.642E-003   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
8 PERIMETER_TOP_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 PERIMETER_TOP_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 PERIMETER_TOP_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 PERIMETER_TOP_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 225.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 135.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
14 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 45.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 315.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
16 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 180.00 180.00 40.76 24.13 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.376 0.351   1660.73 1660.73 1660.73 0.00 0.00 49.91 33.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
18 PERIMETER_MID_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 PERIMETER_MID_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
20 PERIMETER_MID_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 PERIMETER_MID_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
23 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
25 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
26 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
27 iz-PERIMETER_TOP_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
28 iz-PERIMETER_TOP_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
29 iz-PERIMETER_TOP_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 iz-PERIMETER_TOP_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
31 iz-CORE_TOP_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 PERIMETER_BOT_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 PERIMETER_BOT_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
37 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
38 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
39 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
40 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 iz-PERIMETER_MID_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 iz-PERIMETER_MID_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 iz-PERIMETER_MID_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 iz-PERIMETER_MID_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 iz-CORE_MID_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
46 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
51 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
53 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
57 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
58 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 0.00 0.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
60 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   75.61 136.92 75.61 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 61.31 61.31 61.31 0.00 90.00 49.91 1.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 iz-CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
65 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 225.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   50.41 91.28 50.41 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 40.87 40.87 40.87 90.00 90.00 33.27 1.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 iz-CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
74 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 315.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
76 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   75.61 136.92 75.61 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 61.31 61.31 61.31 180.00 90.00 49.91 1.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
78 PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 iz-CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
82 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 45.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
84 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 0.787 0.704   50.41 91.28 50.41 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 40.87 40.87 40.87 270.00 90.00 33.27 1.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 iz-CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
90 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 135.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
92 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   71.71 136.92 71.71 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 20.43 20.43 20.43 0.00 90.00 15.82 1.29 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 20.44 20.44 20.44 0.00 90.00 15.82 1.29 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 20.44 20.44 20.44 0.00 90.00 15.82 1.29 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 iz-CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 0.319 0.296   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   48.45 91.28 48.45 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 39.32 39.32 39.32 90.00 90.00 30.84 1.28 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 1.55 1.55 1.55 90.00 90.00 1.22 1.28 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 iz-CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 0.337 0.312   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
112 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
114 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   71.71 136.92 71.71 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 20.44 20.44 20.44 180.00 90.00 15.82 1.29 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 20.44 20.44 20.44 180.00 90.00 15.82 1.29 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 20.43 20.43 20.43 180.00 90.00 15.82 1.29 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
123 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 0.319 0.296   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
124 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
126 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.787 0.704   48.45 91.28 48.45 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 39.32 39.32 39.32 270.00 90.00 30.84 1.28 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 1.55 1.55 1.55 270.00 90.00 1.22 1.28 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 9.815 9.815   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 iz-CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 0.337 0.312   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   75.61 136.92 75.61 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_NORTH_0.39 N/A 3.241 No 61.31 61.31 61.31 0.00 90.00 49.91 1.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 iz-CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   50.41 91.28 50.41 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_EAST_0.39 N/A 3.241 No 40.87 40.87 40.87 90.00 90.00 33.27 1.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 iz-PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 iz-CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
150 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
152 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   75.61 136.92 75.61 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_SOUTH_0.39 N/A 3.241 No 61.31 61.31 61.31 180.00 90.00 49.91 1.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 iz-CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
160 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.787 0.704   50.41 91.28 50.41 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.57_SHGC_WEST_0.39 N/A 3.241 No 40.87 40.87 40.87 270.00 90.00 33.27 1.23 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 iz-PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 iz-CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.1063374208 7.0096304363E-002 Pass Pass 0.4129740144 0.4836819903 Pass Pass
2 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1691319063 0.1037541449 Pass Pass 0.5059813107 0.4736505448 Pass Pass
3 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.9317457776E-002 4.4778630137E-002 Pass Pass 0.4282709349 0.4864976324 Pass Pass
4 FIRSTFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.2729073668E-002 4.5150339109E-002 Pass Pass 0.4168171845 0.4628380747 Pass Pass
5 CORE_MID RunPeriod: RUNPERIOD 1 2.7516067141E-002 1.8976806907E-002 Pass Pass 0.6257239893 1.3645653728 Pass Pass
6 CORE_TOP RunPeriod: RUNPERIOD 1 3.1338806561E-002 3.6695120552E-002 Pass Pass 8.8829060194 54.6554252786 Pass Pass
7 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.2778773320 0.2741133851 Pass Pass 4.5743168169 13.2071507551 Pass Pass
8 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2862642085 0.2843083835 Pass Pass 4.2134645738 12.1873551381 Pass Pass
9 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.2727351591 0.2734557002 Pass Pass 4.0947044863 11.7222463263 Pass Pass
10 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.2908037306 0.2867351162 Pass Pass 4.1309170699 11.9593016852 Pass Pass
11 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.1526281903 0.1598361072 Pass Pass 1.6121542412 3.5324921045 Pass Pass
12 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1647488307 0.1725299586 Pass Pass 1.2704455761 2.3203803626 Pass Pass
13 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1465965886 0.1561327641 Pass Pass 1.3515497868 2.5217064917 Pass Pass
14 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.1695390902 0.1770425393 Pass Pass 1.2449452576 2.3372089463 Pass Pass
15 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.1810452265 0.1848302785 Pass Pass 4.9377069062 13.6884986867 Pass Pass
16 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.1877958895 0.1947588710 Pass Pass 4.1783812847 11.6810106324 Pass Pass
17 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1732375430 0.1817605782 Pass Pass 4.2167679406 11.5543286099 Pass Pass
18 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.1924841816 0.1992782980 Pass Pass 4.0862540135 11.3487433274 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3132.08 118.77 0.00 2801.66 599.26 6651.77



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB -4.20 0.00 -4.20 Wetbulb [C] 4.30 20.00
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 29.40 10.40 18.30 Wetbulb [C] 4.20 350.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 22.00 23      
Apr 0.00 0      
May 0.00 0      
Jun 16.00 20      
Jul 0.00 0      
Aug 24.00 18      
Sep 12.00 15      
Oct 61.00 41      
Nov 0.00 0      
Dec 45.00 41      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.704 0.787 60.85 60.85 0.00 90.00 N
PERIMETER_TOP_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.704 0.787 40.57 40.57 90.00 90.00 E
PERIMETER_TOP_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.704 0.787 60.85 60.85 180.00 90.00 S
PERIMETER_TOP_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.704 0.787 40.57 40.57 270.00 90.00 W
BUILDING_ROOF NONRES_ROOF 0.30 0.358 0.376 1660.73 1660.73 0.00 0.00  
PERIMETER_MID_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.704 0.787 60.85 60.85 0.00 90.00 N
PERIMETER_MID_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.704 0.787 40.57 40.57 90.00 90.00 E
PERIMETER_MID_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.704 0.787 60.85 60.85 180.00 90.00 S
PERIMETER_MID_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.704 0.787 40.57 40.57 270.00 90.00 W
PERIMETER_BOT_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 60.85 60.85 0.00 90.00 N
PERIMETER_BOT_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 40.57 40.57 90.00 90.00 E
PERIMETER_BOT_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 60.85 60.85 180.00 90.00 S
PERIMETER_BOT_PLENUM_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 40.57 40.57 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.704 0.787 136.92 75.61 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.704 0.787 91.28 50.41 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.704 0.787 136.92 75.61 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.704 0.787 91.28 50.41 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 136.92 71.71 0.00 90.00 N
PERIMETER_BOT_ZN_3_FLOOR PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 1.00 0.304 0.319 207.34 207.34 0.00 180.00  
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 91.28 48.45 90.00 90.00 E
PERIMETER_BOT_ZN_2_FLOOR PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 1.00 0.320 0.337 131.26 131.26 90.00 180.00  
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.704 0.787 136.92 71.71 180.00 90.00 S
PERIMETER_BOT_ZN_1_FLOOR PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 1.00 0.304 0.319 207.34 207.34 180.00 180.00  
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.704 0.787 91.28 48.45 270.00 90.00 W
PERIMETER_BOT_ZN_4_FLOOR PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 1.00 0.320 0.337 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.704 0.787 136.92 75.61 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.704 0.787 91.28 50.41 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.704 0.787 136.92 75.61 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.704 0.787 91.28 50.41 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_BOT_ZN_5_FLOOR CORE_BOT_ZN_5_FLOOR_FFACTOR 1.00 0.006 0.006 983.54 983.54 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 135.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 315.00 180.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_TOP_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_MID_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_MID_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_MID_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_MID_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_MID_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 315.00 0.00  
PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 135.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.57_SHGC_NORTH_0.39   61.31 0.00 0.00 61.31 61.31 3.241 0.391 0.431             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.57_SHGC_EAST_0.39   40.87 0.00 0.00 40.87 40.87 3.241 0.391 0.431             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.57_SHGC_SOUTH_0.39   61.31 0.00 0.00 61.31 61.31 3.241 0.391 0.431             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.57_SHGC_WEST_0.39   40.87 0.00 0.00 40.87 40.87 3.241 0.391 0.431             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.57_SHGC_NORTH_0.39   20.43 0.00 0.00 20.43 20.43 3.241 0.391 0.431             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.57_SHGC_NORTH_0.39   20.44 0.00 0.00 20.44 20.44 3.241 0.391 0.431             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.57_SHGC_NORTH_0.39   20.44 0.00 0.00 20.44 20.44 3.241 0.391 0.431             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.57_SHGC_EAST_0.39   39.32 0.00 0.00 39.32 39.32 3.241 0.391 0.431             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.57_SHGC_EAST_0.39   1.55 0.00 0.00 1.55 1.55 3.241 0.391 0.431             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.57_SHGC_SOUTH_0.39   20.44 0.00 0.00 20.44 20.44 3.241 0.391 0.431             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.57_SHGC_SOUTH_0.39   20.44 0.00 0.00 20.44 20.44 3.241 0.391 0.431             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.57_SHGC_SOUTH_0.39   20.43 0.00 0.00 20.43 20.43 3.241 0.391 0.431             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.57_SHGC_WEST_0.39   39.32 0.00 0.00 39.32 39.32 3.241 0.391 0.431             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.57_SHGC_WEST_0.39   1.55 0.00 0.00 1.55 1.55 3.241 0.391 0.431             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.57_SHGC_NORTH_0.39   61.31 0.00 0.00 61.31 61.31 3.241 0.391 0.431             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.57_SHGC_EAST_0.39   40.87 0.00 0.00 40.87 40.87 3.241 0.391 0.431             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.57_SHGC_SOUTH_0.39   61.31 0.00 0.00 61.31 61.31 3.241 0.391 0.431             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.57_SHGC_WEST_0.39   40.87 0.00 0.00 40.87 40.87 3.241 0.391 0.431             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             613.07 3.241 0.391 0.431                      
North Total or Average             183.92 3.241 0.391 0.431                      
Non-North Total or Average             429.15 3.241 0.391 0.431                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR SWINGING DOOR_CON 3.975 9.815 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 11.0267 983.54 10845.12 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 111.79
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 11.0267 983.54 10845.12 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 111.79
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 11.0267 983.54 10845.12 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 111.79
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 11.0267 207.34 2286.25 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 23.57
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 11.0267 131.26 1447.38 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 14.92
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 11.0267 207.34 2286.25 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 23.57
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 11.0267 131.25 1447.29 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 14.92
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 11.0267 207.34 2286.25 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 23.57
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 11.0267 131.26 1447.38 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 14.92
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 11.0267 207.34 2286.25 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 23.57
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 11.0267 131.25 1447.29 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 14.92
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 11.0267 207.34 2286.25 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 23.57
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 11.0267 131.26 1447.38 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 14.92
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 11.0267 207.34 2286.25 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 23.57
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 11.0267 131.25 1447.29 LightsWired LTG_SCH_OFFICE 56.37 168.00 54.91 0.0000 Y 14.92
Interior Lighting Total       11.0267 4982.19 54936.87               566.26


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS 15013.15 AstronomicalClock -   83.55 83.55 235.45
Exterior Lighting Total 15013.15           235.45



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 365140.36 0.75        


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed   102669.89 82172.79 20497.09 0.80 3.50    
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed   97360.23 77928.46 19431.78 0.80 3.50    
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed   113706.52 90972.28 22734.24 0.80 3.50    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PACU_VAV_BOT COOLING COIL   101024.5 2.88 9.83 N/A N/A 11.13
PACU_VAV_MID COOLING COIL   95824.0 2.88 9.84 N/A N/A 11.15
PACU_VAV_TOP COOLING COIL   111830.7 2.88 9.81 N/A N/A 11.11
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 17388.78 16502.56 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 30627.95 29055.68 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 59105.80 56071.97 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 26039.53 24703.03 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 17013.01 16139.81 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 25795.05 24471.11 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 16859.28 15993.97 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 19558.91 18555.02 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 12882.04 12220.85 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 19317.57 18326.07 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 12727.73 12074.46 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 20174.75 19139.25 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 13283.94 12602.13 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 19930.86 18907.88 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 13134.24 12460.11 -
PACU_VAV_BOT HEATING COIL Coil:Heating:Water 13739.17 11950.44 -
PACU_VAV_MID HEATING COIL Coil:Heating:Water 14623.05 12583.01 -
PACU_VAV_TOP HEATING COIL Coil:Heating:Water 12938.69 11406.24 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PACU_VAV_BOT FAN Fan:VariableVolume 0.60 1337.13 6.05 13372.33 2211.96 1.00 1.13 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
PACU_VAV_MID FAN Fan:VariableVolume 0.60 1337.13 5.70 12611.92 2211.96 1.00 1.13 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
PACU_VAV_TOP FAN Fan:VariableVolume 0.61 1337.13 6.76 14866.92 2197.78 1.00 1.13 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.003194 962.02 301156.09 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000054 6.85 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 1.00 27.19 0.85


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed None 101024.46 2.88 9.83 11.13 6.8925 3.19 10.87 5.4568 3.35 11.44 3.6590 3.54 12.06 1.5119
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed None 95823.97 2.88 9.84 11.15 6.5006 3.19 10.88 5.1479 3.36 11.45 3.4516 3.54 12.08 1.4234
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed None 111830.72 2.88 9.81 11.11 7.7123 3.18 10.84 6.1031 3.34 11.41 4.0911 3.53 12.03 1.6970
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 40053.54 46061.57 46.83 2.951 3.394 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00880 21.70 0.00881 0.425 0.00
CORE_MID 32587.06 37475.11 38.10 2.399 2.759 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00887 21.70 0.00881 0.425 0.00
CORE_TOP 35709.23 41065.61 41.75 2.653 3.051 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00883 29.30 0.00882 0.425 0.00
PERIMETER_TOP_ZN_3 9739.08 11199.94 54.02 0.724 0.832 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 24.00 24.00 0.00876 29.40 0.00882 0.090 0.00
PERIMETER_TOP_ZN_2 11141.58 12812.81 97.61 0.828 0.952 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 24.00 24.00 0.00865 23.97 0.00881 0.057 0.00
PERIMETER_TOP_ZN_1 17507.43 20133.54 97.10 1.301 1.496 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00865 29.14 0.00882 0.090 0.00
PERIMETER_TOP_ZN_4 12628.36 14522.61 110.65 0.938 1.079 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 24.00 24.00 0.00863 28.08 0.00882 0.057 0.00
PERIMETER_BOT_ZN_3 7226.09 8310.01 40.08 0.537 0.617 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00885 29.40 0.00882 0.090 0.00
PERIMETER_BOT_ZN_2 9282.06 10674.37 81.32 0.690 0.793 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 24.00 24.00 0.00867 22.36 0.00881 0.057 0.00
PERIMETER_BOT_ZN_1 14066.73 16176.73 78.02 1.045 1.202 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00868 29.31 0.00882 0.090 0.00
PERIMETER_BOT_ZN_4 10403.60 11964.15 91.15 0.773 0.889 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 24.00 24.00 0.00865 26.90 0.00882 0.057 0.00
PERIMETER_MID_ZN_3 8156.34 9379.79 45.24 0.606 0.697 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00881 29.40 0.00882 0.090 0.00
PERIMETER_MID_ZN_2 11298.44 12993.20 98.99 0.839 0.965 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 24.00 24.00 0.00864 23.35 0.00881 0.057 0.00
PERIMETER_MID_ZN_1 16000.51 18400.59 88.75 1.189 1.367 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 24.00 24.00 0.00866 29.05 0.00882 0.090 0.00
PERIMETER_MID_ZN_4 11673.16 13424.14 102.28 0.867 0.997 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00864 27.94 0.00882 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 5914.72 7393.40 7.52 0.427 0.534 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 0.425 0.00
CORE_MID 14290.45 17863.06 18.16 1.040 1.300 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 0.425 0.00
CORE_TOP 27484.33 34355.41 34.93 2.017 2.521 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 0.425 0.00
PERIMETER_TOP_ZN_3 12088.87 15111.09 72.88 0.891 1.114 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00779 -4.20 0.00269 0.090 0.00
PERIMETER_TOP_ZN_2 7897.95 9872.43 75.21 0.582 0.728 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00779 -4.20 0.00269 0.057 0.00
PERIMETER_TOP_ZN_1 11975.59 14969.49 72.20 0.883 1.103 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00779 -4.20 0.00269 0.090 0.00
PERIMETER_TOP_ZN_4 7826.71 9783.39 74.54 0.577 0.721 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00779 -4.20 0.00269 0.057 0.00
PERIMETER_BOT_ZN_3 9084.05 11355.06 54.77 0.669 0.836 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00785 -4.20 0.00269 0.090 0.00
PERIMETER_BOT_ZN_2 5982.50 7478.12 56.97 0.441 0.551 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00785 -4.20 0.00269 0.057 0.00
PERIMETER_BOT_ZN_1 8972.24 11215.30 54.09 0.660 0.826 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00785 -4.20 0.00269 0.090 0.00
PERIMETER_BOT_ZN_4 5911.00 7388.76 56.29 0.435 0.544 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00785 -4.20 0.00269 0.057 0.00
PERIMETER_MID_ZN_3 9370.56 11713.21 56.49 0.690 0.862 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00778 -4.20 0.00269 0.090 0.00
PERIMETER_MID_ZN_2 6169.50 7711.87 58.75 0.454 0.568 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.057 0.00
PERIMETER_MID_ZN_1 9257.56 11571.96 55.81 0.681 0.852 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.090 0.00
PERIMETER_MID_ZN_4 6100.14 7625.17 58.09 0.449 0.561 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PACU_VAV_BOT 6.05 6.05 3.29 3.29 6.0455 3.2899 6.0455 0.5442 0.3000
PACU_VAV_MID 5.70 5.70 4.14 4.14 5.7017 4.1437 5.7017 0.7267 0.3000
PACU_VAV_TOP 6.76 6.76 6.19 6.19 6.7645 6.1868 6.7645 0.9146 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 17388.775 17388.775 1.018109 0.00015212 378.160 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 17388.78 17388.78 1.018109 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9796 7393.40 0.00 17471.78 17471.78
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 30627.952 30627.952 1.300208 0.00026795 716.865 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 30627.95 30627.95 1.300208 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 17863.06 0.00 30768.26 30768.26
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 59105.802 59105.802 2.521028 0.00051708 1381.581 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 59105.80 59105.80 2.521028 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 34355.41 0.00 59376.71 59376.71
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 26039.527 26039.527 1.113706 0.00022781 608.203 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 26039.53 25911.86 1.113706 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00779193 49.6731 15111.09 0.00 26158.91 26158.91
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 17013.015 17013.015 0.727698 0.00014884 397.363 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 17013.01 17013.01 0.727698 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00778780 49.6472 9872.43 0.00 17091.02 17091.02
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 25795.054 25795.054 1.103227 0.00022567 602.496 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 25795.05 25795.05 1.103227 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00779003 49.6612 14969.49 0.00 25913.32 25913.32
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 16859.278 16859.278 0.721108 0.00014749 393.775 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 16859.28 16859.28 0.721108 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00778594 49.6355 9783.39 0.00 16936.58 16936.58
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 19558.909 19558.909 0.835923 0.00017111 456.928 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 19558.91 19448.85 0.835923 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00784780 50.0237 11355.06 0.00 19648.58 19648.58
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 12882.042 12882.042 0.550628 0.00011270 300.935 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 12882.04 12882.04 0.550628 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00784737 50.0210 7478.12 0.00 12941.10 12941.10
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 19317.571 19317.571 0.825577 0.00016900 451.295 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 19317.57 19317.57 0.825577 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00784536 50.0084 11215.30 0.00 19406.13 19406.13
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 12727.730 12727.730 0.544013 0.00011135 297.334 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 12727.73 12727.73 0.544013 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00784515 50.0071 7388.76 0.00 12786.08 12786.08
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 20174.748 20174.748 0.862322 0.00017650 471.303 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20174.75 20063.06 0.862322 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00777578 49.5711 11713.21 0.00 20267.24 20267.24
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 13283.944 13283.944 0.567858 0.00011621 310.317 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13283.94 13283.94 0.567858 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00777374 49.5584 7711.87 0.00 13344.85 13344.85
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 19930.857 19930.857 0.851866 0.00017436 465.610 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 19930.86 19930.86 0.851866 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00777288 49.5529 11571.96 0.00 20022.23 20022.23
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 13134.241 13134.241 0.561440 0.00011490 306.822 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13134.24 13134.24 0.561440 12.89 11.51 0.00800000 32.11 18.58 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00777109 49.5417 7625.17 0.00 13194.46 13194.46
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_BOT 102669.887 82172.792 6.045465 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 103519.72 98235.21 6.045465 24.85 16.79 0.00879039 11.06 11.06 0.00850000 29.40 0.00882150 18.34 15.8152 24.00 0.00878454 46.5957 70756.09 0.00 105866.43 82701.79
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_BOT 13739.173 13739.173 1.813640 0.00012020 240.927 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:30:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13739.17 13739.17 1.813640 6.54 4.97 0.00483182 12.89 11.51 0.00800000 -4.20 0.00269032 -4.20 52.7172 18.97 0.00745213 53.8873 7650.07 0.00 14466.57 14466.57
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_MID 97360.233 77928.458 5.701695 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 98216.19 92972.44 5.701695 24.90 16.82 0.00880561 11.06 11.06 0.00850000 29.40 0.00882150 18.34 16.7687 24.00 0.00880241 46.6891 66732.66 0.00 100391.47 78429.78
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_MID 14623.050 14623.050 1.710508 0.00012793 254.959 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:20:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 14623.05 14623.05 1.710508 5.72 4.41 0.00472587 12.89 11.51 0.00800000 -4.20 0.00269032 -4.20 55.8957 17.98 0.00757753 58.2889 8106.82 0.00 15231.98 15231.98
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_TOP 113706.522 90972.282 6.764513 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 114547.95 109152.35 6.764513 24.76 16.73 0.00876506 11.08 11.08 0.00850000 29.40 0.00882150 18.34 14.1341 24.00 0.00875577 46.4451 79150.69 0.00 117246.69 91558.64
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_TOP 12938.693 12938.693 2.029354 0.00011319 228.530 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 01:20:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 12938.69 12938.69 2.029354 7.54 5.87 0.00514225 12.89 11.51 0.00800000 -4.20 0.00269032 -4.20 47.1135 16.46 0.00769066 65.1562 8450.00 0.00 13808.36 13808.36



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 17388.775 17388.775 1.018109 0.00015212 378.160 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 4.6683 4.762217 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 17388.78 17388.78 1.0000 1.20848592 1.018109 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.15210907 60.00 32.22 27.78 0.000 17388.78 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.66 0.00800000 21.00 0.00800000 50.9796 7393.40 0.00 17471.78 17471.78 1.20848592 12.80 11.60 0.00800000 33059.8 26.98 17.01 0.00800000 47517.4
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 30627.952 30627.952 1.300208 0.00026795 716.865 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 8.2225 8.387994 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 30627.95 30627.95 1.0000 1.54333440 1.300208 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.26791935 60.00 32.22 27.78 0.000 30627.95 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 50.9797 17863.06 0.00 30768.26 30768.26 1.54333440 12.80 11.60 0.00800000 33059.8 32.35 18.81 0.00800000 52996.1
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 59105.802 59105.802 2.521028 0.00051708 1381.581 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 15.8678 16.187146 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 59105.80 59105.80 1.0000 2.99243650 2.521028 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.51703059 60.00 32.22 27.78 0.000 59105.80 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 50.9797 34355.41 0.00 59376.71 59376.71 2.99243650 12.80 11.60 0.00800000 33059.8 32.26 18.78 0.00800000 52902.1
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 26039.527 26039.527 1.113706 0.00022781 608.203 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 6.9907 7.131375 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 26039.53 25911.86 1.0000 1.32195929 1.113706 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.22778190 60.00 32.22 27.78 0.000 26039.53 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00779193 21.00 0.00779193 49.6731 15111.09 0.00 26158.91 26158.91 1.32195929 12.80 11.60 0.00800000 33059.8 32.21 18.76 0.00800000 52847.8
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 17013.015 17013.015 0.727698 0.00014884 397.363 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 4.5674 4.659308 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 17013.01 17013.01 1.0000 0.86377121 0.727698 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.14882209 60.00 32.22 27.78 0.000 17013.01 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00778780 21.00 0.00778780 49.6472 9872.43 0.00 17091.02 17091.02 0.86377121 12.80 11.60 0.00800000 33059.8 32.20 18.76 0.00800000 52846.3
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 25795.054 25795.054 1.103227 0.00022567 602.496 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 6.9251 7.064421 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 25795.05 25795.05 1.0000 1.30951995 1.103227 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.22564337 60.00 32.22 27.78 0.000 25795.05 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00779003 21.00 0.00779003 49.6612 14969.49 0.00 25913.32 25913.32 1.30951995 12.80 11.60 0.00800000 33059.8 32.21 18.76 0.00800000 52848.2
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 16859.278 16859.278 0.721108 0.00014749 393.775 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 4.5261 4.617205 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 16859.28 16859.28 1.0000 0.85594882 0.721108 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.14747727 60.00 32.22 27.78 0.000 16859.28 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00778594 21.00 0.00778594 49.6355 9783.39 0.00 16936.58 16936.58 0.85594882 12.80 11.60 0.00800000 33059.8 32.20 18.76 0.00800000 52846.7
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 19558.909 19558.909 0.835923 0.00017111 456.928 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 5.2509 5.356545 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 19558.91 19448.85 1.0000 0.99223263 0.835923 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.17109241 60.00 32.22 27.78 0.000 19558.91 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00784780 21.00 0.00784780 50.0237 11355.06 0.00 19648.58 19648.58 0.99223263 12.80 11.60 0.00800000 33059.8 32.22 18.77 0.00800000 52862.2
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 12882.042 12882.042 0.550628 0.00011270 300.935 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 3.4584 3.527970 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 12882.04 12882.04 1.0000 0.65359024 0.550628 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.11268623 60.00 32.22 27.78 0.000 12882.04 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00784737 21.00 0.00784737 50.0210 7478.12 0.00 12941.10 12941.10 0.65359024 12.80 11.60 0.00800000 33059.8 32.22 18.77 0.00800000 52859.8
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 19317.571 19317.571 0.825577 0.00016900 451.295 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 5.1861 5.290451 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 19317.57 19317.57 1.0000 0.97995215 0.825577 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.16898130 60.00 32.22 27.78 0.000 19317.57 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00784536 21.00 0.00784536 50.0084 11215.30 0.00 19406.13 19406.13 0.97995215 12.80 11.60 0.00800000 33059.8 32.22 18.77 0.00800000 52863.0
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 12727.730 12727.730 0.544013 0.00011135 297.334 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 3.4169 3.485709 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 12727.73 12727.73 1.0000 0.64573819 0.544013 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.11133637 60.00 32.22 27.78 0.000 12727.73 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00784515 21.00 0.00784515 50.0071 7388.76 0.00 12786.08 12786.08 0.64573819 12.80 11.60 0.00800000 33059.8 32.22 18.77 0.00800000 52860.5
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 20174.748 20174.748 0.862322 0.00017650 471.303 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 5.4162 5.525203 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 20174.75 20063.06 1.0000 1.02356788 0.862322 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.17647949 60.00 32.22 27.78 0.000 20174.75 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00777578 21.00 0.00777578 49.5711 11713.21 0.00 20267.24 20267.24 1.02356788 12.80 11.60 0.00800000 33059.8 32.22 18.77 0.00800000 52860.4
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 13283.944 13283.944 0.567858 0.00011621 310.317 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 3.5663 3.638038 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13283.94 13283.94 1.0000 0.67404171 0.567858 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.11620188 60.00 32.22 27.78 0.000 13283.94 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00777374 21.00 0.00777374 49.5584 7711.87 0.00 13344.85 13344.85 0.67404171 12.80 11.60 0.00800000 33059.8 32.22 18.77 0.00800000 52858.1
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 19930.857 19930.857 0.851866 0.00017436 465.610 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 5.3507 5.458410 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 19930.86 19930.86 1.0000 1.01115746 0.851866 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.17434605 60.00 32.22 27.78 0.000 19930.86 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00777288 21.00 0.00777288 49.5529 11571.96 0.00 20022.23 20022.23 1.01115746 12.80 11.60 0.00800000 33059.8 32.22 18.77 0.00800000 52861.1
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 13134.241 13134.241 0.561440 0.00011490 306.822 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 3.5261 3.597039 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13134.24 13134.24 1.0000 0.66642411 0.561440 12.89 11.51 0.00800000 33150.5 32.11 18.58 0.00800000 52751.6 0.11489235 60.00 32.22 27.78 0.000 13134.24 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00777109 21.00 0.00777109 49.5417 7625.17 0.00 13194.46 13194.46 0.66642411 12.80 11.60 0.00800000 33059.8 32.22 18.77 0.00800000 52858.7
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 102669.887 82172.792 6.045465 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.1809 1004.8586 1.1870 PACU_VAV_BOT FAN Fan:VariableVolume 6.045465 7.17591167   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 Sensible 103519.72 98235.21 1.0083 7.17591167 6.045465 24.85 16.79 0.00879039 47363.7 11.06 11.06 0.00850000 32550.4 -999.0 -999.00 -999.00 -999.00 13372.329 90147.39 29.40 0.00882150 18.34 0.95610000 15.8152 24.00 0.00878454 24.00 0.00878454 46.5957 70756.09 0.00 105866.43 82701.79 6.89251740 26.67 19.44 0.01118466 55322.4 14.94 14.27 0.00986695 39962.8
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 13739.173 13739.173 1.813640 0.00012020 240.927 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PACU_VAV_BOT FAN Fan:VariableVolume 6.045465 7.17591167   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 3.6885 3.762710 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:30:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13739.17 13739.17 1.0000 2.15277350 1.813640 6.54 4.97 0.00483182 18712.1 12.89 11.51 0.00800000 33150.5 0.12018402 60.00 32.22 27.78 0.000 13739.17 -4.20 0.00269032 -4.20 0.95610000 52.7172 18.51 0.00721946 18.97 0.00745213 53.8873 7650.07 0.00 14466.57 14466.57 2.15277350 2.80 2.80 0.00483182 14922.8 9.43 6.53 0.00483182 21642.8
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 97360.233 77928.458 5.701695 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.2092 1004.8586 1.1870 PACU_VAV_MID FAN Fan:VariableVolume 5.701695 6.76785918   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 Sensible 98216.19 92972.44 1.0088 6.76785918 5.701695 24.90 16.82 0.00880561 47455.1 11.06 11.06 0.00850000 32550.5 -999.0 -999.00 -999.00 -999.00 12611.923 85604.27 29.40 0.00882150 18.34 0.95610000 16.7687 24.00 0.00880241 24.00 0.00880241 46.6891 66732.66 0.00 100391.47 78429.78 6.50057991 26.67 19.44 0.01118466 55322.4 14.87 14.23 0.00986006 39878.9
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 14623.050 14623.050 1.710508 0.00012793 254.959 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PACU_VAV_MID FAN Fan:VariableVolume 5.701695 6.76785918   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 3.9258 4.004775 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:20:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 14623.05 14623.05 1.0000 2.03035776 1.710508 5.72 4.41 0.00472587 17618.6 12.89 11.51 0.00800000 33150.5 0.12791577 60.00 32.22 27.78 0.000 14623.05 -4.20 0.00269032 -4.20 0.95610000 55.8957 18.30 0.00730563 17.98 0.00757753 58.2889 8106.82 0.00 15231.98 15231.98 2.03035776 2.80 2.80 0.00472587 14657.3 10.20 6.79 0.00472587 22159.4
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 113706.522 90972.282 6.764513 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.1338 1004.8586 1.1870 PACU_VAV_TOP FAN Fan:VariableVolume 6.764513 8.02941446   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 Sensible 114547.95 109152.35 1.0074 8.02941446 6.764513 24.76 16.73 0.00876506 47206.7 11.08 11.08 0.00850000 32562.3 -999.0 -999.00 -999.00 -999.00 14866.918 99681.03 29.40 0.00882150 18.34 0.95610000 14.1341 24.00 0.00875577 24.00 0.00875577 46.4451 79150.69 0.00 117246.69 91558.64 7.71231328 26.67 19.44 0.01118466 55322.4 15.06 14.32 0.00987874 40119.9
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 12938.693 12938.693 2.029354 0.00011319 228.530 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PACU_VAV_TOP FAN Fan:VariableVolume 6.764513 8.02941446   4197.9300 999.8980 3.19408130 54.44 82.22 27.78 372488.96 3.4736 3.543485 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 01:20:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 12938.69 12938.69 1.0000 2.40882434 2.029354 7.54 5.87 0.00514225 20512.6 12.89 11.51 0.00800000 33150.5 0.11318178 60.00 32.22 27.78 0.000 12938.69 -4.20 0.00269032 -4.20 0.95610000 47.1135 18.01 0.00732654 16.46 0.00769066 65.1562 8450.00 0.00 13808.36 13808.36 2.40882434 2.80 2.80 0.00514225 15700.8 8.45 6.43 0.00514225 21433.2



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PACU_VAV_BOT_OA_CONTROLLER FixedDryBulb 0.00 6.05 -      
PACU_VAV_MID_OA_CONTROLLER FixedDryBulb 0.00 5.70 -      
PACU_VAV_TOP_OA_CONTROLLER FixedDryBulb 0.00 6.76 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area PERIMETER_MID_ZN_2_OA_MULT 1.00 1.00  
PERIMETER_MID_ZN_1 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_BOTTOM 1972.17 2204.50 32.67
CORE_MID 1166.33 3699.00 187.83
CORE_TOP 1527.67 4396.00 798.00
PERIMETER_TOP_ZN_3 2322.33 4996.50 1763.67
PERIMETER_TOP_ZN_2 2530.00 4670.50 1620.17
PERIMETER_TOP_ZN_1 2422.17 4516.50 1406.50
PERIMETER_TOP_ZN_4 2451.33 4907.50 1712.17
PERIMETER_BOT_ZN_3 1753.33 5064.33 1349.67
PERIMETER_BOT_ZN_2 2125.33 4612.00 1225.67
PERIMETER_BOT_ZN_1 1941.83 4650.83 1069.17
PERIMETER_BOT_ZN_4 2024.33 4821.33 1276.50
PERIMETER_MID_ZN_3 1831.50 4626.33 1141.50
PERIMETER_MID_ZN_2 1752.33 3919.83 1038.00
PERIMETER_MID_ZN_1 2031.00 4242.50 882.83
PERIMETER_MID_ZN_4 1953.83 4746.67 1145.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00
Facility 4261.67 5383.17 1921.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_BOTTOM 2.00 0.00 2.00 0.00
CORE_MID 2.67 0.00 2.67 0.00
CORE_TOP 5.67 0.00 5.17 0.00
PERIMETER_TOP_ZN_3 32.17 0.00 14.17 0.00
PERIMETER_TOP_ZN_2 30.17 2.67 10.50 2.67
PERIMETER_TOP_ZN_1 20.83 4.00 7.83 4.00
PERIMETER_TOP_ZN_4 27.67 9.00 10.00 4.83
PERIMETER_BOT_ZN_3 4.17 0.00 4.00 0.00
PERIMETER_BOT_ZN_2 2.33 0.67 2.17 0.67
PERIMETER_BOT_ZN_1 270.83 1.50 270.83 1.50
PERIMETER_BOT_ZN_4 2.17 4.00 2.00 1.17
PERIMETER_MID_ZN_3 4.50 0.00 4.00 0.00
PERIMETER_MID_ZN_2 2.33 4.50 1.83 4.50
PERIMETER_MID_ZN_1 2.17 4.17 1.83 4.17
PERIMETER_MID_ZN_4 2.33 8.17 1.83 4.17
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 303.33 31.00 282.33 22.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.52 52.94 2698.04 1.117 0.000 0.000 0.000
CORE_MID 21.52 52.94 2698.04 0.749 0.000 0.000 0.000
CORE_TOP 21.52 52.94 2698.04 0.747 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.54 11.16 568.77 1.180 0.078 0.000 0.000
PERIMETER_TOP_ZN_2 2.87 7.07 360.08 1.688 0.083 0.000 0.000
PERIMETER_TOP_ZN_1 4.54 11.16 568.77 1.733 0.079 0.000 0.000
PERIMETER_TOP_ZN_4 2.87 7.06 360.05 1.877 0.083 0.000 0.000
PERIMETER_BOT_ZN_3 4.54 11.16 568.77 0.924 0.042 0.000 0.000
PERIMETER_BOT_ZN_2 2.87 7.07 360.08 1.468 0.044 0.000 0.000
PERIMETER_BOT_ZN_1 4.54 11.16 568.77 1.440 0.852 0.000 0.000
PERIMETER_BOT_ZN_4 2.87 7.06 360.05 1.594 0.044 0.000 0.000
PERIMETER_MID_ZN_3 4.54 11.16 568.77 1.000 0.065 0.000 0.000
PERIMETER_MID_ZN_2 2.51 7.07 360.08 1.671 0.073 0.000 0.000
PERIMETER_MID_ZN_1 4.54 11.16 568.77 1.700 0.066 0.000 0.000
PERIMETER_MID_ZN_4 2.87 7.06 360.05 1.827 0.069 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.52 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_MID 21.52 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_TOP 21.52 52.94 2698.04 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.54 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 2.87 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 4.54 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 2.87 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 4.54 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 2.87 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 4.54 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 2.87 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 4.54 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 2.51 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 4.54 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 2.87 7.06 360.05 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_BOTTOM PACU_VAV_BOT 21.52 52.94 2698.04 983.54 0.0000 0.425
CORE_MID PACU_VAV_MID 21.52 52.94 2698.04 983.54 0.0000 0.425
CORE_TOP PACU_VAV_TOP 21.52 52.94 2698.04 983.54 0.0000 0.425
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 4.54 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 2.87 7.07 360.08 131.26 0.0000 0.057
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 4.54 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 2.87 7.06 360.05 131.25 0.0000 0.057
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 4.54 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 2.87 7.07 360.08 131.26 0.0000 0.057
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 4.54 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 2.87 7.06 360.05 131.25 0.0000 0.057
PERIMETER_MID_ZN_3 PACU_VAV_MID 4.54 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_2 PACU_VAV_MID 2.51 7.07 360.08 131.26 0.0000 0.057
PERIMETER_MID_ZN_1 PACU_VAV_MID 4.54 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_4 PACU_VAV_MID 2.87 7.06 360.05 131.25 0.0000 0.057
Total Facility   108.66 268.17 13667.13 4982.19 0.0000 2.151


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_BOTTOM 17590936.27 0.00 17590936.27 0.00 17590936.27 13393058.27 4646.05 72.24 4041.72 30.62
CORE_MID 11840314.13 0.00 11840314.13 0.00 11840314.13 13393058.27 5513.36 53.57 3193.07 37.31
CORE_TOP 11834322.65 0.00 11834322.65 0.00 11834322.65 13393058.27 5524.53 45.16 3190.30 34.00
PERIMETER_TOP_ZN_3 3951838.58 0.00 3951838.58 539250.78 4491089.36 2823374.22 4156.32 19.64 4584.04 34.00
PERIMETER_TOP_ZN_2 3575026.33 0.00 3575026.33 359498.36 3934524.69 1787429.43 4087.16 2.43 4670.41 34.00
PERIMETER_TOP_ZN_1 5795095.03 0.00 5795095.03 539250.78 6334345.81 2823374.22 4087.86 2.40 4669.74 34.00
PERIMETER_TOP_ZN_4 3980474.99 0.00 3980474.99 359498.36 4339973.35 1787312.18 4077.58 2.92 4679.50 34.00
PERIMETER_BOT_ZN_3 3088724.35 0.00 3088724.35 286716.78 3375441.12 2823374.22 4327.16 14.26 4418.58 30.62
PERIMETER_BOT_ZN_2 3105900.57 0.00 3105900.57 191143.37 3297043.94 1787429.43 4064.17 3.68 4692.15 30.62
PERIMETER_BOT_ZN_1 4817141.91 0.00 4817141.91 2993637.78 7810779.69 2823374.22 4054.64 1.76 4703.60 30.62
PERIMETER_BOT_ZN_4 3375104.77 0.00 3375104.77 191143.37 3566248.14 1787312.18 4073.41 2.77 4683.82 30.62
PERIMETER_MID_ZN_3 3342295.46 0.00 3342295.46 448884.86 3791180.32 2823374.22 4107.86 15.78 4636.36 37.31
PERIMETER_MID_ZN_2 3323617.53 0.00 3323617.53 299254.78 3622872.31 1601953.02 4021.71 0.18 4738.11 946.31
PERIMETER_MID_ZN_1 5681357.77 0.00 5681357.77 448884.86 6130242.63 2823374.22 4023.02 0.25 4736.73 37.31
PERIMETER_MID_ZN_4 3872190.18 0.00 3872190.18 299254.78 4171444.96 1787312.18 4023.21 3.54 4733.25 37.31
Total Facility 89174340.51 0.00 89174340.51 6956418.86 96130759.38 67658168.57 5655.54 226.13 4775.25 968.55


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_BOTTOM 0.8194 0.0000 0.8194 0.0000 0.8194 0.4247 1843.08 72.24 4027.68
CORE_MID 0.5506 0.0000 0.5506 0.0000 0.5506 0.4247 2714.95 53.57 3174.49
CORE_TOP 0.5500 0.0000 0.5500 0.0000 0.5500 0.4247 2727.04 45.16 3170.80
PERIMETER_TOP_ZN_3 0.1836 0.0000 0.1836 0.0123 0.1958 0.0895 1358.83 19.64 4564.53
PERIMETER_TOP_ZN_2 0.1661 0.0000 0.1661 0.0082 0.1743 0.0567 1289.67 2.43 4650.90
PERIMETER_TOP_ZN_1 0.2693 0.0000 0.2693 0.0123 0.2816 0.0895 1290.36 2.40 4650.23
PERIMETER_TOP_ZN_4 0.1849 0.0000 0.1849 0.0082 0.1931 0.0567 1280.09 2.92 4659.99
PERIMETER_BOT_ZN_3 0.1437 0.0000 0.1437 0.0065 0.1502 0.0895 1524.44 14.19 4404.37
PERIMETER_BOT_ZN_2 0.1445 0.0000 0.1445 0.0043 0.1489 0.0567 1262.50 3.68 4676.82
PERIMETER_BOT_ZN_1 0.2242 0.0000 0.2242 0.1330 0.3572 0.0895 1252.69 1.50 4688.81
PERIMETER_BOT_ZN_4 0.1570 0.0000 0.1570 0.0043 0.1613 0.0567 1273.61 2.75 4666.64
PERIMETER_MID_ZN_3 0.1553 0.0000 0.1553 0.0102 0.1655 0.0895 1309.98 15.78 4617.24
PERIMETER_MID_ZN_2 0.1645 0.0000 0.1645 0.0072 0.1717 0.0567 1224.45 0.18 3809.37
PERIMETER_MID_ZN_1 0.2642 0.0000 0.2642 0.0102 0.2744 0.0895 1225.68 0.17 4717.15
PERIMETER_MID_ZN_4 0.1799 0.0000 0.1799 0.0068 0.1867 0.0567 1225.93 3.50 4713.57
Total Facility 4.1572 0.0000 4.1572 0.2235 4.3807 2.1513 2847.49 225.65 4746.93


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PACU_VAV_BOT 45055040.29 0.00 45055040.29 22614548.33 4053.38 0.02 4706.59 30.62
PACU_VAV_MID 39534739.26 0.00 39534739.26 22429071.92 4025.74 2.19 4732.08 37.31
PACU_VAV_TOP 41052150.67 0.00 41052150.67 22614548.33 4099.91 1.88 4658.22 34.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PACU_VAV_BOT 2.0975 0.0000 2.0975 0.7171 1251.75 0.02 4691.23
PACU_VAV_MID 1.8378 0.0000 1.8378 0.7084 1227.86 2.14 4712.99
PACU_VAV_TOP 1.9078 0.0000 1.9078 0.7171 1302.41 1.88 4638.71


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PACU_VAV_BOT 0.00 19.69 4351.31 0.00 0.00 0.00 356.25 0.00 0.00 0.00
PACU_VAV_MID 0.00 23.21 3890.67 0.00 0.00 0.00 849.32 0.00 0.00 0.00
PACU_VAV_TOP 0.00 22.09 3876.82 0.00 0.00 0.00 857.19 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PACU_VAV_BOT 0.0000 1.2810 2.7882 0.0000 0.0000 0.0000 1.1131 0.0000 0.0000 0.0000
PACU_VAV_MID 0.0000 1.2648 2.5669 0.0000 0.0000 0.0000 1.1826 0.0000 0.0000 0.0000
PACU_VAV_TOP 0.0000 1.2168 2.6821 0.0000 0.0000 0.0000 1.1742 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Surfaces by Class

Total Outdoors
Wall 72 24
Floor 30 4
Roof 26 1
Internal Mass 15 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 18 18
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 18
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 873
Defaulted Fields 578
Fields with Defaults 2253
Autosized Fields 194
Autosizable Fields 250
Autocalculated Fields 156
Autocalculatable Fields 277



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1857.57 15934.24 12-MAR-17:10 192087.47 10-AUG-15:50
Electricity:Building 1295.53 15548.59 01-JAN-00:10 91380.19 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 371.79 5897.80 01-JAN-00:10 24018.11 02-JAN-08:10
Electricity:SpaceType:GENERAL 1295.53 15548.59 01-JAN-00:10 91380.19 02-JAN-08:10
InteriorLights:Electricity 566.26 2746.84 01-JAN-00:10 49443.18 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 111.79 542.26 01-JAN-00:10 9760.61 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 566.26 2746.84 01-JAN-00:10 49443.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity 566.26 2746.84 01-JAN-00:10 49443.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 111.79 542.26 01-JAN-00:10 9760.61 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 566.26 2746.84 01-JAN-00:10 49443.18 02-JAN-08:10
Electricity:Zone:CORE_MID 227.21 2373.80 01-JAN-00:10 16568.93 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 111.79 542.26 01-JAN-00:10 9760.61 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 111.79 542.26 01-JAN-00:10 9760.61 02-JAN-08:10
Electricity:Zone:CORE_TOP 227.21 2373.80 01-JAN-00:10 16568.93 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 111.79 542.26 01-JAN-00:10 9760.61 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 111.79 542.26 01-JAN-00:10 9760.61 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 47.90 500.42 01-JAN-00:10 3492.87 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 30.32 316.79 01-JAN-00:10 2211.22 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 14.92 72.37 01-JAN-00:10 1302.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 14.92 72.37 01-JAN-00:10 1302.65 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 47.90 500.41 01-JAN-00:10 3492.86 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 30.32 316.78 01-JAN-00:10 2211.13 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 14.92 72.36 01-JAN-00:10 1302.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 14.92 72.36 01-JAN-00:10 1302.56 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 47.90 500.42 01-JAN-00:10 3492.87 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 30.32 316.79 01-JAN-00:10 2211.22 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 14.92 72.37 01-JAN-00:10 1302.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 14.92 72.37 01-JAN-00:10 1302.65 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 47.90 500.41 01-JAN-00:10 3492.86 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 30.32 316.78 01-JAN-00:10 2211.13 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 14.92 72.36 01-JAN-00:10 1302.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 14.92 72.36 01-JAN-00:10 1302.56 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 47.90 500.42 01-JAN-00:10 3492.87 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 30.32 316.79 01-JAN-00:10 2211.22 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 14.92 72.37 01-JAN-00:10 1302.65 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 14.92 72.37 01-JAN-00:10 1302.65 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 47.90 500.41 01-JAN-00:10 3492.86 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 23.57 114.31 01-JAN-00:10 2057.62 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 30.32 316.78 01-JAN-00:10 2211.13 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 14.92 72.36 01-JAN-00:10 1302.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 14.92 72.36 01-JAN-00:10 1302.56 02-JAN-08:10
InteriorEquipment:Electricity 729.27 12801.75 01-JAN-00:10 41937.01 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 260.00 5355.54 01-JAN-00:10 14257.50 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 729.27 12801.75 01-JAN-00:10 41937.01 02-JAN-08:10
ElevatorLift:InteriorEquipment:Electricity 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 10.22 324.00 01-JAN-00:10 324.00 01-JAN-00:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 10.22 324.00 01-JAN-00:10 324.00 01-JAN-00:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 10.22 324.00 01-JAN-00:10 324.00 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
Electricity:HVAC 270.58 385.65 01-JAN-18:20 96452.10 10-AUG-15:50
ExteriorEquipment:Electricity 27.50 383.73 01-JAN-00:10 1410.29 03-JAN-08:10
Transformer:ExteriorEquipment:Electricity 27.50 383.73 01-JAN-00:10 1410.29 03-JAN-08:10
ElectricityPurchased:Facility 1857.57 15934.24 12-MAR-17:10 192087.47 10-AUG-15:50
ElectricityPurchased:Plant 1857.57 15934.24 12-MAR-17:10 192087.47 10-AUG-15:50
Cogeneration:ElectricityPurchased 1857.57 15934.24 12-MAR-17:10 192087.47 10-AUG-15:50
General:Cogeneration:ElectricityPurchased 1857.57 15934.24 12-MAR-17:10 192087.47 10-AUG-15:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1857.57 15934.24 12-MAR-17:10 192087.47 10-AUG-15:50
ElectricityNet:Plant 1857.57 15934.24 12-MAR-17:10 192087.47 10-AUG-15:50
Cogeneration:ElectricityNet 1857.57 15934.24 12-MAR-17:10 192087.47 10-AUG-15:50
General:Cogeneration:ElectricityNet 1857.57 15934.24 12-MAR-17:10 192087.47 10-AUG-15:50
Fans:Electricity 151.47 0.00 01-JAN-10:40 30475.76 10-AUG-15:30
General:Fans:Electricity 151.47 0.00 01-JAN-10:40 30475.76 10-AUG-15:30
ExteriorLights:Electricity 235.45 0.00 01-JAN-08:10 15013.15 01-JAN-00:10
General:ExteriorLights:Electricity 235.45 0.00 01-JAN-08:10 15013.15 01-JAN-00:10
Cooling:Electricity 91.62 0.00 01-JAN-00:10 64742.39 10-AUG-16:00
General:Cooling:Electricity 91.62 0.00 01-JAN-00:10 64742.39 10-AUG-16:00
Electricity:Plant 56.01 0.00 01-JAN-18:20 6887.32 13-FEB-12:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 54.29 0.00 01-JAN-00:10 6518.00 13-FEB-12:30
Water Heater:WaterSystems:Electricity 54.29 0.00 01-JAN-00:10 6518.00 13-FEB-12:30
Pumps:Electricity 1.72 0.00 01-JAN-18:20 893.29 02-JAN-07:00
General:Pumps:Electricity 1.72 0.00 01-JAN-18:20 893.29 02-JAN-07:00
WIRED_LTG_ELECTRICITY 15.91 0.00 01-JAN-00:10 1389.35 02-JAN-08:20
WIRED_INT_EQUIP1 690.40 12801.75 01-JAN-00:10 37819.83 02-JAN-09:10
WIRED_INT_EQUIP2 633.77 9601.75 01-JAN-00:10 39373.07 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 344.15 0.00 01-JAN-10:40 266214.58 02-JAN-06:20
NaturalGas:Plant 344.15 0.00 01-JAN-10:40 266214.58 02-JAN-06:20
Heating:NaturalGas 344.15 0.00 01-JAN-10:40 266214.58 02-JAN-06:20
Boiler:Heating:NaturalGas 344.15 0.00 01-JAN-10:40 266214.58 02-JAN-06:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 271.06 0.00 01-JAN-00:10 0.00 20-JAN-12:10
Water:Plant 271.06 0.00 01-JAN-00:10 0.00 20-JAN-12:10
WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 20-JAN-12:10
WaterUse:WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 20-JAN-12:10
MainsWater:Facility 271.06 0.00 01-JAN-00:10 0.00 20-JAN-12:10
MainsWater:Plant 271.06 0.00 01-JAN-00:10 0.00 20-JAN-12:10
WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 20-JAN-12:10
WaterUse:WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 20-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 2004.17 0.00 01-JAN-18:20 531384.56 02-JAN-06:20
EnergyTransfer:Building 1133.28 0.00 01-JAN-10:40 185435.14 10-AUG-15:30
EnergyTransfer:Zone:CORE_BOTTOM 237.29 0.00 01-JAN-00:40 25930.12 10-AUG-16:00
Heating:EnergyTransfer 105.92 0.00 01-JAN-10:40 163214.63 02-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.08 0.00 01-JAN-00:10 7434.08 02-JAN-06:20
General:Heating:EnergyTransfer 105.92 0.00 01-JAN-10:40 163214.63 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.08 0.00 01-JAN-00:10 7434.08 02-JAN-06:20
Cooling:EnergyTransfer 1027.36 0.00 01-JAN-10:30 185435.14 10-AUG-15:30
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 237.21 0.00 01-JAN-00:40 25930.12 10-AUG-16:00
General:Cooling:EnergyTransfer 1027.36 0.00 01-JAN-10:30 185435.14 10-AUG-15:30
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 237.21 0.00 01-JAN-00:40 25930.12 10-AUG-16:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 64.24 0.00 01-JAN-00:40 16440.45 09-JAN-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 27.67 0.00 01-JAN-00:40 16440.45 09-JAN-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 27.67 0.00 01-JAN-00:40 16440.45 09-JAN-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 36.57 0.00 01-JAN-00:10 15907.87 10-AUG-14:30
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 36.57 0.00 01-JAN-00:10 15907.87 10-AUG-14:30
EnergyTransfer:Zone:MIDFLOOR_PLENUM 24.27 0.00 01-JAN-00:10 9939.40 02-JAN-08:00
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 7.81 0.00 01-JAN-00:10 9939.40 02-JAN-08:00
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 7.81 0.00 01-JAN-00:10 9939.40 02-JAN-08:00
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 16.46 0.00 01-JAN-00:10 5119.79 10-AUG-15:50
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 16.46 0.00 01-JAN-00:10 5119.79 10-AUG-15:50
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 27.06 0.00 01-JAN-00:40 9119.84 02-JAN-08:40
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 3.55 0.00 01-JAN-00:40 9119.84 02-JAN-08:40
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 3.55 0.00 01-JAN-00:40 9119.84 02-JAN-08:40
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 23.51 0.00 01-JAN-00:10 5604.25 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 23.51 0.00 01-JAN-00:10 5604.25 10-AUG-16:00
EnergyTransfer:Zone:CORE_MID 150.83 0.00 01-JAN-00:10 19573.07 10-AUG-16:00
Heating:EnergyTransfer:Zone:CORE_MID 0.62 0.00 01-JAN-00:10 16260.05 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_MID 0.62 0.00 01-JAN-00:10 16260.05 02-JAN-06:20
Cooling:EnergyTransfer:Zone:CORE_MID 150.22 0.00 01-JAN-00:10 19573.07 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 150.22 0.00 01-JAN-00:10 19573.07 10-AUG-16:00
EnergyTransfer:Zone:CORE_TOP 143.27 0.00 01-JAN-00:40 24786.22 02-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_TOP 4.34 0.00 01-JAN-00:40 24786.22 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 4.34 0.00 01-JAN-00:40 24786.22 02-JAN-06:20
Cooling:EnergyTransfer:Zone:CORE_TOP 138.93 0.00 01-JAN-00:10 22853.27 10-AUG-15:30
General:Cooling:EnergyTransfer:Zone:CORE_TOP 138.93 0.00 01-JAN-00:10 22853.27 10-AUG-15:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 41.22 0.00 01-JAN-00:40 9528.58 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 9.17 0.00 01-JAN-00:40 9528.58 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 9.17 0.00 01-JAN-00:40 9528.58 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 32.05 0.00 01-JAN-00:10 7326.13 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 32.05 0.00 01-JAN-00:10 7326.13 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 35.78 0.00 01-JAN-00:40 9149.10 10-AUG-09:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 5.53 0.00 01-JAN-00:40 6826.90 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 5.53 0.00 01-JAN-00:40 6826.90 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 30.25 0.00 01-JAN-00:10 9149.10 10-AUG-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 30.25 0.00 01-JAN-00:10 9149.10 10-AUG-09:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 60.70 0.00 01-JAN-00:40 14505.91 29-AUG-12:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 7.23 0.00 01-JAN-00:40 10518.09 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 7.23 0.00 01-JAN-00:40 10518.09 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 53.46 0.00 01-JAN-00:10 14505.91 29-AUG-12:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 53.46 0.00 01-JAN-00:10 14505.91 29-AUG-12:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 37.83 0.00 01-JAN-00:40 10698.90 10-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 5.88 0.00 01-JAN-00:40 7019.12 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 5.88 0.00 01-JAN-00:40 7019.12 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 31.95 0.00 01-JAN-00:10 10698.90 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 31.95 0.00 01-JAN-00:10 10698.90 10-AUG-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 30.70 0.00 01-JAN-00:40 7306.12 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 3.97 0.00 01-JAN-00:40 7306.12 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 3.97 0.00 01-JAN-00:40 7306.12 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 26.73 0.00 01-JAN-00:10 5201.72 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 26.73 0.00 01-JAN-00:10 5201.72 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 29.94 0.00 01-JAN-00:40 7360.21 10-AUG-09:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.40 0.00 01-JAN-00:40 5480.84 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.40 0.00 01-JAN-00:40 5480.84 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 27.54 0.00 01-JAN-00:10 7360.21 10-AUG-09:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 27.54 0.00 01-JAN-00:10 7360.21 10-AUG-09:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 54.10 0.00 01-JAN-00:40 13683.62 10-AUG-16:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 14.92 0.00 01-JAN-00:40 10596.92 26-DEC-08:00
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 14.92 0.00 01-JAN-00:40 10596.92 26-DEC-08:00
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 39.19 0.00 01-JAN-00:10 13683.62 10-AUG-16:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 39.19 0.00 01-JAN-00:10 13683.62 10-AUG-16:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 31.12 0.00 01-JAN-00:40 8428.37 10-AUG-17:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 2.45 0.00 01-JAN-00:40 5671.59 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 2.45 0.00 01-JAN-00:40 5671.59 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 28.67 0.00 01-JAN-00:10 8428.37 10-AUG-17:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 28.67 0.00 01-JAN-00:10 8428.37 10-AUG-17:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 35.66 0.00 01-JAN-00:10 7502.57 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 3.34 0.00 01-JAN-00:10 7502.57 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 3.34 0.00 01-JAN-00:10 7502.57 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 32.33 0.00 01-JAN-00:10 6561.43 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 32.33 0.00 01-JAN-00:10 6561.43 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 32.69 0.00 01-JAN-00:10 9366.11 10-AUG-08:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.14 0.00 01-JAN-00:10 5932.68 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.14 0.00 01-JAN-00:10 5932.68 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 30.56 0.00 01-JAN-00:10 9366.11 10-AUG-08:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 30.56 0.00 01-JAN-00:10 9366.11 10-AUG-08:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 59.97 0.00 01-JAN-00:10 14153.37 04-OCT-13:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.61 0.00 01-JAN-00:10 8805.79 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.61 0.00 01-JAN-00:10 8805.79 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 57.37 0.00 01-JAN-00:10 14153.37 04-OCT-13:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 57.37 0.00 01-JAN-00:10 14153.37 04-OCT-13:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 36.59 0.00 01-JAN-00:10 10225.06 10-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 2.22 0.00 01-JAN-00:10 5917.61 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 2.22 0.00 01-JAN-00:10 5917.61 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 34.37 0.00 01-JAN-00:10 10225.06 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 34.37 0.00 01-JAN-00:10 10225.06 10-AUG-16:00
PlantLoopHeatingDemand:Facility 271.25 0.00 01-JAN-18:20 172495.40 02-JAN-07:40
PlantLoopHeatingDemand:Plant 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
EnergyTransfer:HVAC 601.33 0.00 01-JAN-10:40 245115.04 10-AUG-15:20
HeatingCoils:EnergyTransfer 219.76 0.00 01-JAN-10:40 170446.09 02-JAN-06:30
PlantLoopHeatingDemand:HVAC 219.76 0.00 01-JAN-10:40 170446.09 02-JAN-06:30
HeatingCoils:PlantLoopHeatingDemand 219.76 0.00 01-JAN-10:40 170446.09 02-JAN-06:30
CoolingCoils:EnergyTransfer 381.56 0.00 01-JAN-00:10 245105.34 10-AUG-15:20
EnergyTransfer:Plant 269.56 0.00 01-JAN-18:20 197858.06 02-JAN-06:20
WaterSystems:EnergyTransfer 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
Boilers:EnergyTransfer 218.07 0.00 01-JAN-10:40 197103.03 02-JAN-06:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_BOTTOM 0.000 0.000 0.078 -237.210 0.000 0.000 33.012 111.786 259.999 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -167.667
CORE_MID 0.000 0.000 0.616 -150.218 0.000 0.000 34.219 111.786 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -111.828
CORE_TOP 0.000 0.000 4.339 -138.934 0.000 0.000 35.392 111.786 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -128.009
PERIMETER_TOP_ZN_3 0.000 0.000 9.169 -32.054 0.000 0.000 7.789 23.566 24.333 12.281 0.000 0.026 0.002 0.000 -37.663 0.000 -6.501 -0.946
PERIMETER_TOP_ZN_2 0.000 0.000 5.534 -30.249 0.000 0.000 4.891 14.919 15.404 25.245 0.000 0.016 0.000 0.000 -24.091 0.000 -4.365 -7.303
PERIMETER_TOP_ZN_1 0.000 0.000 7.234 -53.463 0.000 0.000 7.685 23.566 24.332 55.331 0.000 0.020 0.000 0.000 -36.724 0.000 -6.724 -21.257
PERIMETER_TOP_ZN_4 0.000 0.000 5.882 -31.950 0.000 0.000 4.979 14.918 15.403 27.630 0.000 0.014 0.000 0.000 -24.906 0.000 -4.407 -7.562
PERIMETER_BOT_ZN_3 0.000 0.000 3.972 -26.730 0.000 0.000 7.710 23.566 24.333 12.624 0.000 0.015 0.001 0.000 -39.746 0.000 -3.703 -2.039
PERIMETER_BOT_ZN_2 0.000 0.000 2.399 -27.542 0.000 0.000 4.859 14.919 15.404 25.456 0.000 0.008 0.000 0.000 -25.633 0.000 -2.509 -7.361
PERIMETER_BOT_ZN_1 0.000 0.000 14.915 -39.189 0.000 0.000 7.766 23.566 24.332 56.154 0.000 0.391 0.001 0.000 -39.242 0.000 -34.008 -14.685
PERIMETER_BOT_ZN_4 0.000 0.000 2.450 -28.668 0.000 0.000 4.931 14.918 15.403 28.014 0.000 0.008 0.001 0.000 -26.579 0.000 -2.532 -7.945
PERIMETER_MID_ZN_3 0.000 0.000 3.336 -32.328 0.000 0.000 7.617 23.566 24.333 11.812 0.000 0.022 8.356 0.000 -40.850 0.000 -5.863 -0.001
PERIMETER_MID_ZN_2 0.000 0.000 2.137 -30.555 0.000 0.000 3.570 14.919 15.404 24.801 0.000 0.014 0.002 0.000 -25.963 0.000 -3.923 -0.403
PERIMETER_MID_ZN_1 0.000 0.000 2.607 -57.365 0.000 0.000 7.566 23.566 24.332 54.851 0.000 0.017 0.001 0.000 -39.603 0.000 -6.033 -9.937
PERIMETER_MID_ZN_4 0.000 0.000 2.218 -34.369 0.000 0.000 4.922 14.918 15.403 27.454 0.000 0.012 0.237 0.000 -26.849 0.000 -3.945 -0.000
TOPFLOOR_PLENUM 27.671 -36.565 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.009 18.651 0.000 0.000 0.000 -9.767 -0.002
MIDFLOOR_PLENUM 7.812 -16.460 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.024 18.940 0.000 0.000 0.000 -10.316 -0.000
FIRSTFLOOR_PLENUM 3.550 -23.508 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.018 28.462 0.000 0.000 0.000 -8.521 -0.000
Total Facility 39.034 -76.534 66.885 -950.824 0.000 0.000 176.906 566.263 729.266 361.653 0.000 0.614 74.652 0.000 -387.849 0.000 -113.117 -486.945


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 25-AUG-05:12 0.00 0.00 0.00 -48693.04 0.00 0.00 328.17 1084.51 7734.35 0.00 0.00 0.00 39546.01 0.00 -0.00 0.00 0.00 0.00
CORE_MID 10-AUG-05:12 0.00 0.00 0.00 -25431.66 0.00 0.00 342.95 1084.51 3025.92 0.00 0.00 0.00 20978.28 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 10-AUG-15:30 0.00 0.00 0.00 -22853.03 0.00 0.00 3497.11 9760.61 6808.32 0.00 0.00 0.00 2786.98 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24-JUL-15:00 0.00 0.00 0.00 -7326.17 0.00 0.00 737.22 2057.62 1435.25 3810.76 0.00 44.75 0.00 0.00 -0.00 0.00 0.00 -759.44
PERIMETER_TOP_ZN_2 06-AUG-09:22 0.00 0.00 0.00 -11062.24 0.00 0.00 17.23 72.37 302.86 9286.94 0.00 0.00 1571.03 0.00 -0.00 0.00 -188.18 0.00
PERIMETER_TOP_ZN_1 10-SEP-13:42 0.00 0.00 0.00 -26153.09 0.00 0.00 23.50 114.31 478.41 13816.08 0.00 0.00 11856.96 0.00 -0.00 0.00 -136.18 0.00
PERIMETER_TOP_ZN_4 30-JUL-16:42 0.00 0.00 0.00 -18501.73 0.00 0.00 12.67 72.36 302.86 12533.48 0.00 0.00 5587.84 0.00 -0.00 0.00 -7.49 0.00
PERIMETER_BOT_ZN_3 24-JUL-15:00 0.00 0.00 0.00 -5201.69 0.00 0.00 737.22 2057.62 1435.25 3906.08 0.00 23.98 0.00 0.00 -0.00 0.00 0.00 -2958.46
PERIMETER_BOT_ZN_2 10-AUG-09:10 0.00 0.00 0.00 -7360.33 0.00 0.00 479.35 1302.65 908.57 11161.76 0.00 0.00 0.00 0.00 -0.00 0.00 -2.42 -6489.59
PERIMETER_BOT_ZN_1 10-AUG-16:10 0.00 0.00 0.00 -13677.51 0.00 0.00 232.81 1143.12 797.35 4504.43 0.00 5689.70 1310.09 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 06-AUG-18:02 0.00 0.00 0.00 -15409.34 0.00 0.00 0.00 72.36 244.42 9122.24 0.00 0.00 6026.62 0.00 -0.00 0.00 -56.31 0.00
PERIMETER_MID_ZN_3 24-JUL-15:00 0.00 0.00 0.00 -6561.47 0.00 0.00 737.22 2057.62 1435.25 3849.64 0.00 37.40 0.00 0.00 -0.00 0.00 0.00 -1555.66
PERIMETER_MID_ZN_2 06-AUG-09:22 0.00 0.00 0.00 -14235.84 0.00 0.00 16.18 72.37 302.86 9245.31 0.00 0.00 4756.85 0.00 -0.00 0.00 -157.74 0.00
PERIMETER_MID_ZN_1 06-AUG-13:22 0.00 0.00 0.00 -16624.87 0.00 0.00 27.40 114.31 478.41 12032.35 0.00 0.00 4099.40 0.00 -0.00 0.00 -127.01 0.00
PERIMETER_MID_ZN_4 06-AUG-16:42 0.00 0.00 0.00 -17793.77 0.00 0.00 14.30 72.36 302.86 12166.40 0.00 0.00 5338.35 0.00 -0.00 0.00 -100.49 0.00
TOPFLOOR_PLENUM 10-AUG-14:30 0.00 -15907.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.54 15881.01 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 10-AUG-15:50 0.00 -5119.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.53 5087.23 0.00 -0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 10-AUG-16:00 0.00 -5604.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.94 5582.24 0.00 -0.00 0.00 0.00 0.00
Total Facility 10-AUG-15:30 0.00 -25875.24 0.00 -159558.52 0.00 0.00 17714.92 49443.18 41937.01 71314.97 0.00 1055.04 3968.64 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 02-JAN-06:11 0.00 0.00 9002.83 0.00 0.00 0.00 503.92 1084.51 7734.35 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -18325.61
CORE_MID 02-JAN-06:11 0.00 0.00 18238.54 0.00 0.00 0.00 526.60 1084.51 3025.92 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -22875.58
CORE_TOP 17-JAN-05:01 0.00 0.00 27836.82 0.00 0.00 0.00 0.00 1084.51 2442.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -31363.39
PERIMETER_TOP_ZN_3 17-JAN-05:01 0.00 0.00 11368.79 0.00 0.00 0.00 0.00 228.62 514.80 0.00 0.00 0.00 0.00 0.00 -2074.47 0.00 -300.52 -9737.23
PERIMETER_TOP_ZN_2 17-JAN-05:01 0.00 0.00 8564.61 0.00 0.00 0.00 0.00 144.74 325.89 0.00 0.00 0.00 0.00 0.00 -1380.70 0.00 -201.46 -7453.08
PERIMETER_TOP_ZN_1 17-JAN-05:01 0.00 0.00 13188.24 0.00 0.00 0.00 0.00 228.62 514.80 0.00 0.00 0.00 0.00 0.00 -2019.00 0.00 -303.13 -11609.54
PERIMETER_TOP_ZN_4 17-JAN-05:01 0.00 0.00 9085.48 0.00 0.00 0.00 0.00 144.73 325.89 0.00 0.00 0.00 0.00 0.00 -1339.37 0.00 -202.16 -8014.57
PERIMETER_BOT_ZN_3 02-JAN-06:11 0.00 0.00 8244.33 0.00 0.00 0.00 113.18 228.62 637.89 0.00 0.00 0.00 0.00 0.00 -1438.91 0.00 -77.79 -7707.32
PERIMETER_BOT_ZN_2 02-JAN-06:11 0.00 0.00 6526.50 0.00 0.00 0.00 71.65 144.74 403.81 0.00 0.00 0.00 0.00 0.00 -991.35 0.00 -52.31 -6103.04
PERIMETER_BOT_ZN_1 26-DEC-08:00 0.00 0.00 10596.22 0.00 0.00 0.00 230.15 685.87 637.88 0.00 0.00 0.00 4857.09 0.00 -2727.82 0.00 -14279.40 0.00
PERIMETER_BOT_ZN_4 02-JAN-06:11 0.00 0.00 6893.50 0.00 0.00 0.00 71.65 144.73 403.81 0.00 0.00 0.00 0.00 0.00 -956.68 0.00 -52.44 -6504.57
PERIMETER_MID_ZN_3 26-DEC-05:01 0.00 0.00 8591.88 0.00 0.00 0.00 0.00 228.62 514.80 0.00 0.00 0.00 0.00 0.00 -2398.87 0.00 0.00 -6936.44
PERIMETER_MID_ZN_2 26-DEC-05:01 0.00 0.00 7484.79 0.00 0.00 0.00 0.00 144.74 325.89 0.00 0.00 0.00 0.00 0.00 -1589.09 0.00 0.00 -6366.34
PERIMETER_MID_ZN_1 17-JAN-05:01 0.00 0.00 10767.08 0.00 0.00 0.00 0.00 228.62 514.80 0.00 0.00 0.00 0.00 0.00 -2181.91 0.00 -261.49 -9067.10
PERIMETER_MID_ZN_4 26-DEC-05:01 0.00 0.00 7546.62 0.00 0.00 0.00 0.00 144.73 325.89 0.00 0.00 0.00 0.00 0.00 -1591.08 0.00 0.00 -6426.16
TOPFLOOR_PLENUM 11-DEC-06:16 17573.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -42.28 -17531.58
MIDFLOOR_PLENUM 02-JAN-06:19 10377.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -211.31 -10166.31
FIRSTFLOOR_PLENUM 02-JAN-08:10 9500.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -112.39 -9388.13
Total Facility 02-JAN-06:11 9258.96 0.00 160856.59 0.00 0.00 0.00 2676.37 5493.69 20036.35 0.00 0.00 0.00 0.00 0.00 -14655.91 0.00 -2812.71 -180853.33



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 7.1134 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 6.0455 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 6.9509 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.7017 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 7.6915 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 6.7645 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 3.5567 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.1340 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 3.4755 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0853 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 3.8457 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.3074 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_BOTTOM PACU_VAV_BOT 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID PACU_VAV_MID 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP PACU_VAV_TOP 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PACU_VAV_BOT   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_MID   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_TOP   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.3937 3.3937 1.0181 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7588 2.7588 0.8276 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.0510 3.0510 0.9153 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1137 1.1137 0.3341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9519 0.9519 0.2856 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4958 1.4958 0.4487 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0790 1.0790 0.3237 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8359 0.8359 0.2508 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7931 0.7931 0.2379 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2019 1.2019 0.3606 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8889 0.8889 0.2667 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8623 0.8623 0.2587 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9653 0.9653 0.2896 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3671 1.3671 0.4101 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9974 0.9974 0.2992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 7.1134 6.0455 7.1134 2.1340 0.0000 1.0000
PACU_VAV_MID 6.9509 5.7017 6.9509 2.0853 0.0000 1.0000
PACU_VAV_TOP 7.6915 6.7645 7.6915 2.3074 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6968 1.6968 1.0181 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3794 1.3794 0.8276 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5255 1.5255 0.9153 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5569 0.5569 0.3341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4760 0.4760 0.2856 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7479 0.7479 0.4487 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5395 0.5395 0.3237 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4180 0.4180 0.2508 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3965 0.3965 0.2379 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6009 0.6009 0.3606 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4444 0.4444 0.2667 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4312 0.4312 0.2587 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4827 0.4827 0.2896 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6835 0.6835 0.4101 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4987 0.4987 0.2992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 3.5567 2.1340 2.1340 2.1340 0.0000 1.0000
PACU_VAV_MID 3.4755 2.0853 2.0853 2.0853 0.0000 1.0000
PACU_VAV_TOP 3.8457 2.3074 2.3074 2.3074 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Total gross floor area [m2] 4982.19
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_BOTTOM 983.54 983.54 0.00 113.98
CORE_MID 983.54 983.54 0.00 113.98
CORE_TOP 983.54 983.54 0.00 113.98
PERIMETER_TOP_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_TOP_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_BOT_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_BOT_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_MID_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_2 131.26 131.26 0.00 96.54
PERIMETER_MID_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_4 131.25 131.25 0.00 113.98
TOPFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
MIDFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
FIRSTFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
Totals 4982.19 4982.19 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 282.33
Number of hours cooling loads not met 22.83
Number of hours not met 305.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 344.15 266214.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 91.62 64742.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 566.26 49443.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 235.45 15013.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 134.36 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 10.22 324.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 584.69 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 27.50 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 151.47 30475.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1.72 893.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 54.29 6518.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 729.27 1857.57
Natural Gas 0.00 344.15
Additional 0.00 0.00
Total 729.27 2201.72


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 113.66
Space Heating 0.00
Space Cooling 18.39
Fans (All) 30.40
Service Water Heating 10.90
Receptacle Equipment 146.37
Miscellaneous (All) 372.84
Subtotal 372.84


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 69.08
Service Water Heating 0.00
Miscellaneous (All) 69.08
Subtotal 69.08


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 25.72
Space Heating 15.63
Space Cooling 4.16
Fans (All) 6.88
Service Water Heating 2.47
Receptacle Equipment 33.12
Miscellaneous 12.02


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 145. 3744.
ELEVATOR_STANDBY_SCH 8276. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2939. 8760.
BLDG_EQUIP_SCH 4095. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2545. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 1470. 4212.
BLDG_SWH_SCH 1441. 5992.
WORK_EFF_SCH 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
INFIL_SCH_PNNL 5172. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
PERIMETER_MID_ZN_2_OA_MULT 7824. 7824.
PERIMETER_MID_ZN_2_MDP_SCH 2357. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 8646.67 113.33 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8755.67 4.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8750.33 9.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8747.33 12.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8757.33 2.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8752.83 7.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8752.67 7.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8754.17 5.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8749.67 10.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8747.33 12.67 0.00 0.00 0.00
TOPFLOOR_PLENUM 8715.17 44.83 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8646.67 0.00 0.00 0.00 0.00
Max 8760.00 113.33 0.00 0.00 0.00
Average 8747.18 12.82 0.00 0.00 0.00
Sum 157449.17 230.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 128259.00 45.00 0.00 0.00 0.00
CORE_MID 128304.00 0.00 0.00 0.00 0.00
CORE_TOP 128304.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128304.00 45.00 0.00 0.00 0.00
Average 34140.83 2.50 0.00 0.00 0.00
Sum 614535.00 45.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 8572.00 188.00 0.00 0.00 0.00
CORE_MID 8744.17 15.83 0.00 0.00 0.00
CORE_TOP 8757.00 3.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8754.83 5.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8747.50 12.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8744.17 15.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8755.17 4.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8745.00 15.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8742.00 18.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8750.67 9.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8744.67 15.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8737.33 22.67 0.00 0.00 0.00
TOPFLOOR_PLENUM 8688.17 71.83 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8572.00 0.00 0.00 0.00 0.00
Max 8760.00 188.00 0.00 0.00 0.00
Average 8737.93 22.07 0.00 0.00 0.00
Sum 157282.67 397.33 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 128194.33 109.67 0.00 0.00 0.00
CORE_MID 128297.00 7.00 0.00 0.00 0.00
CORE_TOP 128298.67 5.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128298.67 109.67 0.00 0.00 0.00
Average 34136.56 6.78 0.00 0.00 0.00
Sum 614458.00 122.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:22:07

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.123896E+11 13771.22 13-JAN-17:00 2.20 1.77 0.183386E+10 2606.64 27-JAN-14:20 9.43 7.91
February 0.129621E+11 16330.48 28-FEB-17:00 14.40 10.82 0.175132E+10 2606.66 08-FEB-10:20 14.40 10.82
March 0.178277E+11 18650.78 02-MAR-17:00 12.80 8.57 0.213916E+10 2606.67 09-MAR-14:09 14.90 12.35
April 0.183637E+11 27911.20 28-APR-05:13 11.10 9.98 0.191034E+10 2606.66 14-APR-09:20 11.10 9.98
May 0.230198E+11 31428.87 08-MAY-05:13 9.60 9.49 0.207612E+10 2606.67 05-MAY-09:09 9.60 9.49
June 0.252806E+11 36156.75 12-JUN-06:03 14.60 13.50 0.207223E+10 2606.70 05-JUN-13:00 14.60 13.50
July 0.263571E+11 41089.90 25-JUL-06:03 13.98 13.26 0.192746E+10 2606.65 21-JUL-13:20 13.98 13.26
August 0.288955E+11 48702.19 25-AUG-05:12 17.67 15.13 0.216182E+10 2606.89 09-AUG-09:00 17.67 15.13
September 0.236407E+11 44586.95 14-SEP-05:12 12.43 12.07 0.191972E+10 2606.67 22-SEP-09:20 14.83 14.31
October 0.194317E+11 26706.27 10-OCT-05:13 12.20 11.16 0.198763E+10 2606.67 05-OCT-09:00 12.20 11.16
November 0.153082E+11 18225.29 06-NOV-17:00 11.70 10.80 0.194737E+10 2606.66 03-NOV-09:20 11.70 10.80
December 0.137344E+11 15651.01 06-DEC-15:50 3.58 3.15 0.185457E+10 2606.67 13-DEC-14:20 6.90 5.05
                     
Annual Sum or Average 0.237211E+12         0.235816E+11        
Minimum of Months 0.123896E+11 13771.22   2.20 1.77 0.175132E+10 2606.64   6.90 5.05
Maximum of Months 0.288955E+11 48702.19   17.67 15.13 0.216182E+10 2606.89   17.67 15.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 7883528.83 650.73 20-JAN-14:15 6.87 4.79 0.00 0.00 01-JAN-00:10 6.87 4.79
February 0.261191E+09 3755.99 27-FEB-14:50 19.72 12.05 0.00 0.00 01-FEB-00:10 19.72 12.05
March 0.127494E+10 5861.47 14-MAR-13:40 15.20 10.17 0.00 0.00 01-MAR-00:10 15.20 10.17
April 0.297210E+10 13125.64 27-APR-14:05 26.28 16.91 0.00 0.00 01-APR-00:10 26.28 16.91
May 0.503907E+10 13717.98 04-MAY-14:05 23.98 15.25 0.00 0.00 01-MAY-00:10 23.98 15.25
June 0.618314E+10 14105.10 28-JUN-14:05 25.18 15.64 0.00 0.00 01-JUN-00:10 25.18 15.64
July 0.782530E+10 15437.24 24-JUL-13:50 29.22 18.16 0.00 0.00 01-JUL-00:10 29.22 18.16
August 0.745246E+10 15907.87 10-AUG-14:30 29.80 19.03 0.00 0.00 01-AUG-00:10 29.80 19.03
September 0.404225E+10 11736.94 14-SEP-14:20 23.90 17.07 0.00 0.00 01-SEP-00:10 23.90 17.07
October 0.131892E+10 7678.59 04-OCT-14:00 21.10 11.41 0.00 0.00 01-OCT-00:10 21.10 11.41
November 0.179620E+09 4429.48 04-NOV-13:50 21.02 15.96 0.00 0.00 01-NOV-00:10 21.02 15.96
December 8832485.98 736.72 05-DEC-13:40 10.60 6.32 0.00 0.00 01-DEC-00:10 10.60 6.32
                     
Annual Sum or Average 0.365657E+11         0.00        
Minimum of Months 7883528.83 650.73   6.87 4.79 0.00 0.00   6.87 4.79
Maximum of Months 0.782530E+10 15907.87   29.80 19.03 0.00 0.00   29.80 19.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 40707257.36 3196.98 14-JAN-06:11 2.20 1.14 0.00 0.00 01-JAN-00:10 2.20 1.14
February 0.208331E+09 3230.48 11-FEB-06:11 3.30 1.84 0.00 0.00 01-FEB-00:10 3.30 1.84
March 0.603314E+09 3895.33 25-MAR-05:11 2.20 -2.6 0.00 0.00 01-MAR-00:10 2.20 -2.6
April 0.111158E+10 3467.90 08-APR-06:03 6.60 5.59 0.00 0.00 01-APR-00:10 6.60 5.59
May 0.182335E+10 2838.51 06-MAY-06:05 14.60 12.60 0.00 0.00 01-MAY-00:10 14.60 12.60
June 0.254219E+10 3785.75 28-JUN-16:00 26.10 16.29 0.00 0.00 01-JUN-00:10 26.10 16.29
July 0.317803E+10 4483.60 31-JUL-16:00 28.90 19.18 0.00 0.00 01-JUL-00:10 28.90 19.18
August 0.360047E+10 5119.79 10-AUG-15:50 31.03 18.78 0.00 0.00 01-AUG-00:10 31.03 18.78
September 0.214452E+10 3821.74 14-SEP-15:50 24.32 17.03 0.00 0.00 01-SEP-00:10 24.32 17.03
October 0.903747E+09 2949.29 31-OCT-05:11 8.87 8.29 0.00 0.00 01-OCT-00:10 8.87 8.29
November 0.249302E+09 3012.96 22-NOV-06:11 3.13 2.35 0.00 0.00 01-NOV-00:10 3.13 2.35
December 54836870.35 3068.10 02-DEC-06:11 4.97 2.41 0.00 0.00 01-DEC-00:10 4.97 2.41
                     
Annual Sum or Average 0.164604E+11         0.00        
Minimum of Months 40707257.36 2838.51   2.20 -2.6 0.00 0.00   2.20 -2.6
Maximum of Months 0.360047E+10 5119.79   31.03 19.18 0.00 0.00   31.03 19.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141500E+09 3792.76 13-JAN-06:11 3.13 2.22 0.00 0.00 01-JAN-00:10 3.13 2.22
February 0.421470E+09 4206.74 10-FEB-06:11 2.07 1.09 0.00 0.00 01-FEB-00:10 2.07 1.09
March 0.114842E+10 4536.42 23-MAR-05:11 3.70 3.32 0.00 0.00 01-MAR-00:10 3.70 3.32
April 0.178490E+10 4364.45 18-APR-05:11 3.30 2.58 0.00 0.00 01-APR-00:10 3.30 2.58
May 0.272025E+10 3541.88 08-MAY-06:07 9.90 9.62 0.00 0.00 01-MAY-00:10 9.90 9.62
June 0.335627E+10 4178.77 28-JUN-16:00 26.10 16.29 0.00 0.00 01-JUN-00:10 26.10 16.29
July 0.392081E+10 4892.56 24-JUL-15:40 29.47 18.66 0.00 0.00 01-JUL-00:10 29.47 18.66
August 0.444148E+10 5604.25 10-AUG-16:00 31.20 18.74 0.00 0.00 01-AUG-00:10 31.20 18.74
September 0.304906E+10 4617.70 14-SEP-15:50 24.32 17.03 0.00 0.00 01-SEP-00:10 24.32 17.03
October 0.166307E+10 3842.83 27-OCT-06:03 9.40 8.87 0.00 0.00 01-OCT-00:10 9.40 8.87
November 0.617940E+09 3504.55 09-NOV-07:03 6.70 5.68 0.00 0.00 01-NOV-00:10 6.70 5.68
December 0.243243E+09 3751.26 07-DEC-06:11 4.63 2.88 0.00 0.00 01-DEC-00:10 4.63 2.88
                     
Annual Sum or Average 0.235084E+11         0.00        
Minimum of Months 0.141500E+09 3504.55   2.07 1.09 0.00 0.00   2.07 1.09
Maximum of Months 0.444148E+10 5604.25   31.20 18.74 0.00 0.00   31.20 18.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.755224E+10 7778.18 12-JAN-17:00 7.20 5.41 0.163349E+10 2428.52 12-JAN-14:00 7.20 5.41
February 0.804810E+10 8996.37 28-FEB-17:00 14.40 10.82 0.156105E+10 2585.92 28-FEB-14:00 14.40 10.82
March 0.108240E+11 10857.97 02-MAR-17:00 12.80 8.57 0.199452E+10 2606.64 02-MAR-14:30 12.80 8.57
April 0.114752E+11 16492.01 27-APR-16:00 27.20 16.90 0.183775E+10 2606.67 14-APR-09:20 27.20 16.90
May 0.147677E+11 16693.43 05-MAY-16:00 25.00 17.36 0.204567E+10 2606.67 26-MAY-13:20 12.77 11.65
June 0.167645E+11 18058.84 21-JUN-16:00 25.00 16.17 0.205553E+10 2606.68 09-JUN-13:09 25.00 16.17
July 0.176819E+11 18711.43 24-JUL-16:00 28.90 18.57 0.191604E+10 2606.65 11-JUL-09:20 28.90 18.57
August 0.195187E+11 25431.79 10-AUG-05:12 17.27 14.45 0.215064E+10 2606.82 09-AUG-09:00 17.27 14.45
September 0.148143E+11 18275.82 14-SEP-16:00 24.40 17.04 0.189568E+10 2606.67 22-SEP-09:20 14.83 14.31
October 0.114362E+11 15746.04 04-OCT-16:00 21.10 11.40 0.189947E+10 2606.67 12-OCT-09:20 9.47 7.95
November 0.906021E+10 8877.61 03-NOV-16:00 13.30 12.93 0.175760E+10 2594.97 06-NOV-14:00 11.10 10.22
December 0.827515E+10 8070.85 06-DEC-16:10 2.93 2.59 0.162802E+10 2510.77 06-DEC-14:00 2.93 2.59
                     
Annual Sum or Average 0.150218E+12         0.223755E+11        
Minimum of Months 0.755224E+10 7778.18   2.93 2.59 0.156105E+10 2428.52   2.93 2.59
Maximum of Months 0.195187E+11 25431.79   28.90 18.57 0.215064E+10 2606.82   28.90 18.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.541920E+10 7709.42 11-JAN-17:00 12.20 9.27 0.152096E+10 2252.99 11-JAN-14:00 12.20 9.27
February 0.652179E+10 8808.70 28-FEB-17:00 14.40 10.82 0.143618E+10 2460.25 28-FEB-14:00 14.40 10.82
March 0.984436E+10 9456.81 02-MAR-16:50 12.88 8.54 0.182882E+10 2553.77 02-MAR-14:00 12.88 8.54
April 0.110929E+11 18961.19 27-APR-15:30 27.20 17.10 0.173540E+10 2606.66 27-APR-13:20 27.20 17.10
May 0.145975E+11 19391.56 04-MAY-15:40 24.07 14.71 0.198087E+10 2606.67 26-MAY-13:20 12.77 11.65
June 0.168123E+11 21192.71 28-JUN-15:50 26.10 16.17 0.202365E+10 2606.69 09-JUN-13:09 26.10 16.17
July 0.181468E+11 22012.83 24-JUL-15:20 30.03 18.73 0.189615E+10 2606.65 11-JUL-09:20 30.03 18.73
August 0.194170E+11 22853.27 10-AUG-15:30 30.70 18.83 0.212760E+10 2606.80 09-AUG-09:00 30.70 18.83
September 0.138706E+11 19838.13 14-SEP-15:30 24.15 17.00 0.182753E+10 2606.65 28-SEP-13:20 17.20 11.88
October 0.102449E+11 15534.73 04-OCT-16:00 21.10 11.40 0.175160E+10 2606.65 03-OCT-13:20 21.10 11.40
November 0.727581E+10 8687.92 02-NOV-15:40 13.30 10.98 0.158972E+10 2425.37 02-NOV-13:00 13.30 10.98
December 0.569132E+10 7881.00 05-DEC-15:50 6.75 4.97 0.148407E+10 2288.93 06-DEC-14:00 5.00 4.36
                     
Annual Sum or Average 0.138934E+12         0.212026E+11        
Minimum of Months 0.541920E+10 7709.42   6.75 4.97 0.143618E+10 2252.99   5.00 4.36
Maximum of Months 0.194170E+11 22853.27   30.70 18.83 0.212760E+10 2606.80   30.70 18.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.252924E+09 2180.81 11-JAN-15:00 14.40 10.49 0.305141E+09 406.78 09-JAN-10:50 14.40 10.49
February 0.681652E+09 2685.47 27-FEB-16:20 19.23 12.34 0.279755E+09 460.83 28-FEB-14:00 13.90 10.81
March 0.171507E+10 2894.00 10-MAR-14:50 16.20 11.59 0.344116E+09 488.15 10-MAR-14:00 16.10 11.51
April 0.267939E+10 5378.94 27-APR-15:20 27.20 17.16 0.328952E+09 549.50 27-APR-13:20 27.20 17.16
May 0.409813E+10 5347.05 15-MAY-14:40 23.30 12.92 0.385571E+09 549.50 22-MAY-13:20 16.10 10.37
June 0.480882E+10 6173.63 21-JUN-15:40 24.80 15.84 0.403872E+09 549.51 09-JUN-13:09 24.80 15.84
July 0.529523E+10 7326.13 24-JUL-15:00 30.60 18.78 0.384839E+09 549.50 21-JUL-13:20 30.60 18.78
August 0.555848E+10 6877.05 09-AUG-15:30 28.70 18.83 0.430230E+09 549.54 09-AUG-09:00 28.70 18.83
September 0.374501E+10 5059.26 14-SEP-15:50 24.32 17.03 0.352476E+09 549.50 12-SEP-13:00 24.32 17.03
October 0.209620E+10 3287.92 04-OCT-15:40 21.30 11.43 0.326438E+09 526.64 04-OCT-13:00 21.30 11.43
November 0.849230E+09 2575.36 02-NOV-14:40 13.67 11.26 0.305340E+09 447.35 02-NOV-13:00 13.67 11.26
December 0.274113E+09 2042.22 30-DEC-17:02 5.60 4.81 0.294661E+09 406.77 13-DEC-10:30 5.60 4.81
                     
Annual Sum or Average 0.320542E+11         0.414139E+10        
Minimum of Months 0.252924E+09 2042.22   5.60 4.81 0.279755E+09 406.77   5.60 4.81
Maximum of Months 0.555848E+10 7326.13   30.60 18.83 0.430230E+09 549.54   30.60 18.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.223080E+09 1719.69 28-JAN-17:02 6.70 5.64 0.193221E+09 257.54 12-JAN-10:39 6.70 5.64
February 0.677445E+09 2233.37 27-FEB-15:50 19.50 12.39 0.177179E+09 284.59 27-FEB-14:00 19.50 12.39
March 0.166905E+10 2798.94 14-MAR-10:00 10.00 7.75 0.221894E+09 338.26 14-MAR-09:00 10.00 7.75
April 0.266483E+10 6663.21 27-APR-09:30 18.35 12.60 0.219597E+09 347.88 27-APR-13:20 26.10 16.46
May 0.371609E+10 6597.80 15-MAY-09:20 17.77 12.22 0.248796E+09 347.89 15-MAY-09:00 18.90 13.25
June 0.459510E+10 9487.63 25-JUN-09:12 17.07 12.34 0.260732E+09 347.88 09-JUN-13:09 17.07 12.34
July 0.495943E+10 8767.71 24-JUL-09:00 23.90 16.63 0.246059E+09 347.88 24-JUL-09:20 24.07 16.77
August 0.535253E+10 11062.88 06-AUG-09:22 16.20 13.22 0.275642E+09 347.93 09-AUG-09:00 23.80 15.92
September 0.350734E+10 7940.65 10-SEP-09:02 16.28 13.48 0.227817E+09 347.88 12-SEP-13:00 24.40 16.54
October 0.190222E+10 4441.91 04-OCT-09:30 16.40 10.73 0.212071E+09 347.88 05-OCT-09:00 13.90 9.28
November 0.704069E+09 2182.21 02-NOV-10:40 12.43 10.47 0.192879E+09 280.48 02-NOV-13:00 14.40 11.37
December 0.277607E+09 1728.26 30-DEC-17:02 5.60 4.81 0.186586E+09 257.56 26-DEC-10:39 5.60 4.81
                     
Annual Sum or Average 0.302488E+11         0.266247E+10        
Minimum of Months 0.223080E+09 1719.69   5.60 4.81 0.177179E+09 257.54   5.60 4.81
Maximum of Months 0.535253E+10 11062.88   23.90 16.63 0.275642E+09 347.93   26.10 16.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101054E+10 7106.42 20-JAN-13:25 6.70 4.72 0.311302E+09 549.50 20-JAN-14:30 6.95 4.83
February 0.180480E+10 9048.46 27-FEB-14:25 19.15 11.80 0.299261E+09 549.50 09-FEB-14:30 19.15 11.80
March 0.351035E+10 10413.76 14-MAR-13:40 15.20 10.17 0.370167E+09 549.50 02-MAR-14:30 15.20 10.17
April 0.456212E+10 12926.94 27-APR-13:10 26.10 16.37 0.346701E+09 549.51 27-APR-13:20 26.10 16.46
May 0.591093E+10 11052.60 04-MAY-13:40 23.33 15.33 0.386345E+09 549.51 15-MAY-13:09 22.88 13.76
June 0.653431E+10 10301.88 28-JUN-13:05 24.50 15.71 0.396867E+09 549.52 09-JUN-13:09 24.50 15.71
July 0.759809E+10 19265.47 30-JUL-12:02 26.10 17.31 0.378944E+09 549.50 20-JUL-13:20 26.10 17.31
August 0.859316E+10 14505.91 29-AUG-12:30 28.65 19.74 0.426187E+09 549.56 09-AUG-09:00 28.65 19.74
September 0.680416E+10 26152.46 10-SEP-13:42 21.93 14.56 0.359899E+09 549.52 12-SEP-13:00 24.40 16.54
October 0.422414E+10 14093.29 04-OCT-13:07 20.68 11.25 0.349410E+09 549.50 03-OCT-13:20 20.68 11.25
November 0.169734E+10 8730.31 04-NOV-13:25 20.85 16.00 0.314438E+09 549.50 15-NOV-14:30 9.45 6.68
December 0.121342E+10 6791.74 05-DEC-12:25 10.30 6.13 0.305975E+09 549.50 05-DEC-14:30 10.30 6.71
                     
Annual Sum or Average 0.534634E+11         0.424550E+10        
Minimum of Months 0.101054E+10 6791.74   6.70 4.72 0.299261E+09 549.50   6.95 4.83
Maximum of Months 0.859316E+10 26152.46   28.65 19.74 0.426187E+09 549.56   28.65 19.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.263301E+09 2309.60 05-JAN-15:50 6.20 4.71 0.193348E+09 264.88 05-JAN-15:00 6.10 4.61
February 0.674278E+09 3726.07 27-FEB-15:30 19.70 12.30 0.178978E+09 338.69 27-FEB-15:00 19.40 12.42
March 0.161615E+10 5521.03 14-MAR-16:00 17.20 10.94 0.219234E+09 338.69 02-MAR-15:20 17.20 10.94
April 0.264417E+10 8683.63 26-APR-16:00 24.40 14.49 0.205766E+09 347.85 27-APR-13:00 26.10 16.83
May 0.408609E+10 12907.02 07-MAY-16:42 21.78 16.19 0.234624E+09 347.85 05-MAY-13:00 21.78 16.19
June 0.466936E+10 18130.66 18-JUN-16:52 17.20 12.22 0.243498E+09 347.85 28-JUN-13:20 24.60 15.70
July 0.559881E+10 18504.66 30-JUL-16:42 26.88 17.94 0.234656E+09 347.85 20-JUL-13:20 26.88 17.94
August 0.563518E+10 13523.43 12-AUG-17:05 24.38 16.49 0.261469E+09 347.86 15-AUG-13:20 24.50 15.97
September 0.385696E+10 18312.43 10-SEP-16:22 22.20 14.33 0.216220E+09 347.85 12-SEP-13:00 24.40 16.54
October 0.191565E+10 6856.70 04-OCT-16:00 21.10 11.40 0.205958E+09 347.80 04-OCT-13:00 21.10 11.40
November 0.673181E+09 2979.08 04-NOV-15:40 20.37 15.93 0.193293E+09 291.39 15-NOV-14:00 8.90 6.49
December 0.316835E+09 2463.96 05-DEC-15:30 8.05 5.82 0.186928E+09 276.69 05-DEC-14:00 8.05 5.82
                     
Annual Sum or Average 0.319499E+11         0.257397E+10        
Minimum of Months 0.263301E+09 2309.60   6.20 4.71 0.178978E+09 264.88   6.10 4.61
Maximum of Months 0.563518E+10 18504.66   26.88 17.94 0.261469E+09 347.86   26.88 17.94



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.305891E+09 1691.71 11-JAN-15:00 14.40 10.49 0.306153E+09 414.69 11-JAN-14:00 14.40 10.49
February 0.627544E+09 1972.82 28-FEB-15:00 13.90 10.81 0.280877E+09 456.17 28-FEB-14:00 13.90 10.81
March 0.146882E+10 2073.61 10-MAR-14:40 16.30 11.68 0.344712E+09 472.53 10-MAR-14:50 16.20 11.59
April 0.208530E+10 2821.08 27-APR-16:00 27.20 16.90 0.326157E+09 544.07 27-APR-13:00 27.20 16.90
May 0.306235E+10 3468.39 05-MAY-15:30 24.70 17.20 0.388312E+09 549.49 15-MAY-13:20 22.97 13.71
June 0.350379E+10 4287.48 21-JUN-15:40 24.80 15.84 0.411599E+09 549.50 09-JUN-13:20 24.80 15.84
July 0.394771E+10 5201.72 24-JUL-15:00 30.60 18.78 0.393728E+09 549.50 12-JUL-13:20 30.60 18.78
August 0.435348E+10 5167.72 09-AUG-15:30 28.70 18.83 0.441860E+09 549.53 09-AUG-09:00 28.70 18.83
September 0.315983E+10 3821.73 14-SEP-15:50 24.32 17.03 0.370957E+09 549.49 05-SEP-13:20 24.32 17.03
October 0.235170E+10 2463.23 04-OCT-15:40 21.30 11.43 0.345067E+09 529.17 04-OCT-13:00 21.30 11.43
November 0.135194E+10 2069.29 02-NOV-14:02 14.22 11.35 0.315280E+09 470.74 02-NOV-13:00 14.22 11.35
December 0.512197E+09 1675.67 29-DEC-13:50 11.10 9.04 0.296296E+09 411.97 29-DEC-14:20 10.93 8.95
                     
Annual Sum or Average 0.267306E+11         0.422100E+10        
Minimum of Months 0.305891E+09 1675.67   11.10 9.04 0.280877E+09 411.97   10.93 8.95
Maximum of Months 0.435348E+10 5201.72   30.60 18.83 0.441860E+09 549.53   30.60 18.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.264373E+09 1460.96 28-JAN-17:02 6.70 5.64 0.193828E+09 257.53 03-JAN-14:09 6.70 5.64
February 0.644274E+09 1782.72 27-FEB-15:50 19.50 12.39 0.177922E+09 279.11 27-FEB-14:00 19.50 12.39
March 0.153089E+10 2144.89 14-MAR-10:05 10.28 7.92 0.221528E+09 317.90 14-MAR-09:00 10.28 7.92
April 0.228718E+10 4806.26 27-APR-09:30 18.35 12.60 0.218011E+09 347.88 27-APR-13:20 26.10 16.46
May 0.303541E+10 5241.66 15-MAY-09:40 18.33 12.73 0.248792E+09 347.88 15-MAY-09:00 18.90 13.25
June 0.377585E+10 5979.20 28-JUN-09:30 20.00 13.97 0.263547E+09 347.88 09-JUN-13:09 20.00 13.97
July 0.415230E+10 7119.80 24-JUL-09:10 23.98 16.70 0.249304E+09 347.88 24-JUL-09:20 24.07 16.77
August 0.475177E+10 7360.49 10-AUG-09:10 22.62 17.13 0.280444E+09 347.93 09-AUG-09:00 22.62 17.13
September 0.330872E+10 5675.97 14-SEP-09:30 17.75 15.56 0.235044E+09 347.88 12-SEP-13:00 17.75 15.56
October 0.220873E+10 3763.45 04-OCT-09:30 16.40 10.73 0.220898E+09 347.88 05-OCT-09:00 13.90 9.28
November 0.110548E+10 1949.45 02-NOV-10:40 12.43 10.47 0.196741E+09 289.79 02-NOV-09:00 12.43 10.47
December 0.477393E+09 1653.11 05-DEC-10:20 7.23 5.22 0.187681E+09 267.76 05-DEC-10:30 7.50 5.28
                     
Annual Sum or Average 0.275424E+11         0.269374E+10        
Minimum of Months 0.264373E+09 1460.96   6.70 5.22 0.177922E+09 257.53   6.70 5.28
Maximum of Months 0.475177E+10 7360.49   23.98 17.13 0.280444E+09 347.93   26.10 17.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.422871E+09 3283.66 20-JAN-13:50 6.70 4.72 0.299948E+09 504.37 20-JAN-14:09 6.78 4.76
February 0.104189E+10 5373.64 27-FEB-15:00 20.00 12.17 0.286451E+09 549.50 27-FEB-14:30 20.00 12.17
March 0.211255E+10 5004.86 01-MAR-14:40 12.77 7.03 0.353288E+09 549.50 02-MAR-14:30 13.30 8.35
April 0.296054E+10 9564.99 27-APR-13:40 26.10 16.65 0.329959E+09 549.51 27-APR-13:20 26.10 16.65
May 0.393122E+10 7963.84 14-MAY-14:30 23.05 12.36 0.371387E+09 549.51 15-MAY-13:09 22.88 13.76
June 0.450202E+10 7511.07 28-JUN-13:40 24.80 15.68 0.387807E+09 549.51 09-JUN-13:09 24.80 15.68
July 0.566652E+10 11042.92 31-JUL-16:10 28.80 19.11 0.380364E+09 549.50 20-JUL-13:20 28.80 19.11
August 0.722029E+10 13683.62 10-AUG-16:10 31.30 18.74 0.430754E+09 549.56 09-AUG-09:00 31.30 18.74
September 0.552997E+10 11508.57 14-SEP-13:50 23.72 17.23 0.365301E+09 549.51 12-SEP-13:00 23.72 17.23
October 0.364406E+10 11766.94 04-OCT-13:30 20.85 11.31 0.351583E+09 549.51 05-OCT-09:00 13.90 9.28
November 0.137785E+10 6567.90 04-NOV-13:40 20.93 15.98 0.310562E+09 537.57 15-NOV-14:09 9.82 6.80
December 0.779284E+09 4178.87 05-DEC-12:00 10.00 6.07 0.297336E+09 543.74 05-DEC-14:50 10.10 6.91
                     
Annual Sum or Average 0.391891E+11         0.416474E+10        
Minimum of Months 0.422871E+09 3283.66   6.70 4.72 0.286451E+09 504.37   6.78 4.76
Maximum of Months 0.722029E+10 13683.62   31.30 19.11 0.430754E+09 549.56   31.30 19.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.280343E+09 1884.76 05-JAN-15:50 6.20 4.71 0.193924E+09 263.30 05-JAN-15:00 6.10 4.61
February 0.636006E+09 2555.69 27-FEB-15:50 19.50 12.39 0.178917E+09 324.27 27-FEB-15:00 19.40 12.42
March 0.148246E+10 2894.98 02-MAR-16:30 13.05 8.47 0.217642E+09 338.68 02-MAR-16:00 12.80 8.57
April 0.221928E+10 5570.97 26-APR-17:00 24.40 13.95 0.204363E+09 347.85 27-APR-13:00 26.10 16.83
May 0.333132E+10 11295.02 14-MAY-17:42 22.30 11.98 0.237826E+09 347.85 15-MAY-13:20 22.97 13.71
June 0.378898E+10 6786.82 28-JUN-16:00 26.10 16.29 0.248826E+09 347.85 28-JUN-13:20 26.10 16.29
July 0.462902E+10 14769.34 23-JUL-18:01 25.82 15.89 0.243736E+09 347.85 21-JUL-13:20 25.82 15.89
August 0.486219E+10 15409.08 06-AUG-18:02 23.47 15.22 0.272178E+09 347.88 09-AUG-09:00 23.80 15.92
September 0.357872E+10 7034.65 11-SEP-16:00 23.30 16.14 0.227582E+09 347.85 12-SEP-13:00 24.40 16.54
October 0.229795E+10 5909.90 04-OCT-16:00 21.10 11.40 0.212360E+09 347.79 04-OCT-13:00 21.10 11.40
November 0.109251E+10 2483.38 04-NOV-15:40 20.37 15.93 0.195736E+09 293.76 10-NOV-14:00 10.00 6.84
December 0.469534E+09 2110.17 05-DEC-15:30 8.05 5.82 0.188170E+09 283.45 05-DEC-15:39 7.40 5.40
                     
Annual Sum or Average 0.286683E+11         0.262126E+10        
Minimum of Months 0.280343E+09 1884.76   6.20 4.71 0.178917E+09 263.30   6.10 4.61
Maximum of Months 0.486219E+10 15409.08   26.10 16.29 0.272178E+09 347.88   26.10 16.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.523844E+09 1894.75 11-JAN-16:00 14.40 10.49 0.306766E+09 435.67 11-JAN-14:00 14.40 10.49
February 0.984955E+09 2281.90 28-FEB-15:00 13.90 10.81 0.285405E+09 493.03 28-FEB-14:00 13.90 10.81
March 0.212311E+10 2404.45 10-MAR-14:40 16.30 11.68 0.360780E+09 513.29 10-MAR-14:00 16.10 11.51
April 0.268547E+10 4858.32 27-APR-16:00 27.20 16.90 0.347653E+09 549.50 27-APR-13:20 27.20 16.90
May 0.373937E+10 5102.72 05-MAY-15:30 24.70 17.20 0.408275E+09 549.51 05-MAY-09:20 24.70 17.20
June 0.433651E+10 5641.99 21-JUN-15:40 24.80 15.84 0.422182E+09 549.51 09-JUN-13:09 24.80 15.84
July 0.480962E+10 6561.43 24-JUL-15:00 30.60 18.78 0.397590E+09 549.50 14-JUL-09:20 30.60 18.78
August 0.513740E+10 6244.59 09-AUG-15:30 28.70 18.83 0.445307E+09 549.54 09-AUG-09:00 28.70 18.83
September 0.354112E+10 4783.36 14-SEP-15:50 24.32 17.03 0.376939E+09 549.50 06-SEP-13:20 24.32 17.03
October 0.244334E+10 3113.27 04-OCT-15:30 21.40 11.45 0.350321E+09 549.47 04-OCT-13:00 21.40 11.45
November 0.134689E+10 2218.47 02-NOV-14:30 13.85 11.29 0.315923E+09 482.09 02-NOV-13:00 13.85 11.29
December 0.656474E+09 1805.86 29-DEC-14:10 11.02 9.00 0.296473E+09 423.22 29-DEC-14:20 10.93 8.95
                     
Annual Sum or Average 0.323281E+11         0.431361E+10        
Minimum of Months 0.523844E+09 1805.86   11.02 9.00 0.285405E+09 423.22   10.93 8.95
Maximum of Months 0.513740E+10 6561.43   30.60 18.83 0.445307E+09 549.54   30.60 18.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.335023E+09 2405.13 20-JAN-11:03 5.60 3.32 0.143056E+09 305.69 20-JAN-11:09 5.60 3.32
February 0.741192E+09 3324.81 27-FEB-15:02 19.90 12.22 0.134022E+09 355.32 27-FEB-15:09 19.90 12.22
March 0.173777E+10 5034.32 02-MAR-13:02 12.38 7.47 0.170534E+09 356.46 14-MAR-10:09 10.28 7.92
April 0.267806E+10 7649.11 27-APR-10:05 19.27 13.13 0.166461E+09 356.46 20-APR-10:09 19.27 13.13
May 0.364692E+10 8698.76 14-MAY-09:42 18.53 12.07 0.187279E+09 356.47 15-MAY-10:09 19.18 13.24
June 0.446575E+10 8220.17 28-JUN-10:05 21.20 14.55 0.194724E+09 356.46 27-JUN-14:09 21.20 14.55
July 0.476209E+10 9956.11 30-JUL-09:02 20.87 15.88 0.183860E+09 356.46 07-JUL-12:09 20.87 15.88
August 0.519402E+10 14237.59 06-AUG-09:22 16.20 13.22 0.205910E+09 356.51 09-AUG-10:09 23.92 16.01
September 0.356103E+10 11244.80 10-SEP-09:52 17.20 13.54 0.173153E+09 356.46 11-SEP-10:09 19.08 14.37
October 0.209147E+10 5953.69 04-OCT-10:05 17.48 10.97 0.163422E+09 356.46 05-OCT-10:09 14.08 9.36
November 0.897395E+09 3490.41 04-NOV-10:02 16.38 13.96 0.146256E+09 356.44 02-NOV-10:09 16.38 13.96
December 0.444446E+09 2568.94 05-DEC-11:02 8.58 5.53 0.138914E+09 317.93 05-DEC-11:09 8.58 5.53
                     
Annual Sum or Average 0.305552E+11         0.200759E+10        
Minimum of Months 0.335023E+09 2405.13   5.60 3.32 0.134022E+09 305.69   5.60 3.32
Maximum of Months 0.519402E+10 14237.59   21.20 15.88 0.205910E+09 356.51   23.92 16.01



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.139821E+10 7917.54 20-JAN-13:13 6.70 4.72 0.315955E+09 549.50 20-JAN-14:20 6.87 4.79
February 0.233051E+10 9384.35 27-FEB-14:25 19.15 11.80 0.306241E+09 549.50 09-FEB-14:30 19.15 11.80
March 0.422825E+10 10633.57 01-MAR-13:40 11.33 6.09 0.380968E+09 549.50 02-MAR-14:30 13.30 8.35
April 0.493445E+10 12338.55 27-APR-13:10 26.10 16.37 0.356773E+09 549.51 27-APR-13:20 26.10 16.46
May 0.601166E+10 10580.58 14-MAY-12:32 21.83 12.33 0.398747E+09 549.51 15-MAY-13:09 22.88 13.76
June 0.637713E+10 9630.24 28-JUN-13:05 24.50 15.71 0.408926E+09 549.51 09-JUN-13:09 24.50 15.71
July 0.733886E+10 12227.53 31-JUL-13:10 27.38 18.36 0.388170E+09 549.50 21-JUL-13:20 27.38 18.36
August 0.844398E+10 16624.11 06-AUG-13:22 22.15 15.53 0.436826E+09 549.56 09-AUG-09:00 23.80 15.92
September 0.712305E+10 15033.07 10-SEP-13:13 21.13 14.29 0.372924E+09 549.51 12-SEP-13:00 24.40 16.54
October 0.501208E+10 14230.55 04-OCT-13:10 20.68 11.25 0.362145E+09 549.81 04-OCT-13:50 21.02 11.37
November 0.240788E+10 9091.38 04-NOV-13:25 20.85 16.00 0.324411E+09 549.50 15-NOV-14:30 9.45 6.68
December 0.175960E+10 8087.54 05-DEC-12:25 10.30 6.13 0.312860E+09 549.50 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.573657E+11         0.436495E+10        
Minimum of Months 0.139821E+10 7917.54   6.70 4.72 0.306241E+09 549.50   6.87 4.79
Maximum of Months 0.844398E+10 16624.11   27.38 18.36 0.436826E+09 549.81   27.38 18.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.460721E+09 2295.23 05-JAN-15:50 6.20 4.71 0.194160E+09 277.41 05-JAN-15:00 6.10 4.61
February 0.935326E+09 3727.10 27-FEB-15:30 19.70 12.30 0.181107E+09 339.02 27-FEB-14:00 19.70 12.30
March 0.208749E+10 5353.31 14-MAR-16:00 17.20 10.94 0.222552E+09 346.47 02-MAR-14:00 17.20 10.94
April 0.292522E+10 8306.29 26-APR-16:00 24.40 14.49 0.210213E+09 347.85 27-APR-13:00 26.10 16.83
May 0.418013E+10 17707.41 07-MAY-16:32 21.87 16.22 0.241774E+09 347.85 15-MAY-13:20 22.97 13.71
June 0.459455E+10 8953.79 28-JUN-16:00 26.10 16.29 0.250762E+09 347.85 28-JUN-13:20 26.10 16.29
July 0.542681E+10 15262.58 23-JUL-16:52 26.70 15.58 0.241033E+09 347.85 21-JUL-13:20 26.70 15.58
August 0.552841E+10 17792.59 06-AUG-16:42 23.47 15.19 0.269252E+09 347.86 15-AUG-13:20 24.50 15.97
September 0.407202E+10 8837.44 11-SEP-16:00 23.30 16.14 0.224583E+09 347.85 12-SEP-13:00 24.40 16.54
October 0.245338E+10 6893.39 04-OCT-16:00 21.10 11.40 0.211508E+09 347.82 04-OCT-13:00 21.10 11.40
November 0.111971E+10 2857.90 04-NOV-15:40 20.37 15.93 0.195537E+09 304.99 10-NOV-14:00 10.00 6.84
December 0.585870E+09 2471.86 05-DEC-15:30 8.05 5.82 0.188340E+09 291.46 05-DEC-15:39 7.40 5.40
                     
Annual Sum or Average 0.343696E+11         0.263082E+10        
Minimum of Months 0.460721E+09 2295.23   6.20 4.71 0.181107E+09 277.41   6.10 4.61
Maximum of Months 0.552841E+10 17792.59   26.70 16.29 0.269252E+09 347.86   26.70 16.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 78441654.81 9002.83 02-JAN-06:11 6.10
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 78441654.81      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 78441654.81 9002.83   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.674609E+10 17467.60 09-JAN-06:09 -1.5
February 0.426527E+10 17011.95 13-FEB-06:16 2.40
March 0.251734E+10 15040.75 06-MAR-06:16 6.70
April 0.131913E+10 10516.48 19-APR-05:03 1.78
May 0.646063E+09 7992.07 11-MAY-05:03 5.10
June 0.300130E+09 6826.76 19-JUN-05:03 11.20
July 0.183117E+09 6445.50 07-JUL-05:03 11.47
August 0.252667E+09 6030.46 21-AUG-05:03 11.20
September 0.627035E+09 7920.60 10-SEP-07:48 14.03
October 0.171466E+10 8728.20 16-OCT-05:13 7.03
November 0.337331E+10 17301.78 24-NOV-06:16 1.83
December 0.572645E+10 17573.80 11-DEC-06:16 4.60
         
Annual Sum or Average 0.276713E+11      
Minimum of Months 0.183117E+09 6030.46   -1.5
Maximum of Months 0.674609E+10 17573.80   14.03



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235235E+10 10377.62 02-JAN-06:19 6.10
February 0.129300E+10 8873.88 21-FEB-07:08 1.60
March 0.703060E+09 3896.61 06-MAR-07:08 6.70
April 0.295432E+09 4437.46 02-APR-11:52 17.20
May 59545745.36 5046.59 29-MAY-15:46 16.02
June 15198487.99 3515.86 18-JUN-15:06 18.80
July 18490807.95 4336.03 02-JUL-13:25 19.45
August 10835883.08 3784.49 06-AUG-15:22 23.75
September 46631448.10 3955.42 10-SEP-13:53 22.20
October 0.328859E+09 4525.55 29-OCT-12:32 10.93
November 0.994386E+09 4322.07 13-NOV-07:03 1.52
December 0.169401E+10 9160.75 26-DEC-07:18 -1.5
         
Annual Sum or Average 0.781180E+10      
Minimum of Months 10835883.08 3515.86   -1.5
Maximum of Months 0.235235E+10 10377.62   23.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.152748E+10 9500.38 02-JAN-08:10 6.70
February 0.593128E+09 4409.21 21-FEB-08:20 1.47
March 0.146878E+09 2586.09 06-MAR-08:08 6.78
April 24123694.12 1986.78 19-APR-07:08 4.18
May 11160992.82 3456.90 29-MAY-16:55 16.70
June 11073114.75 3473.79 25-JUN-14:42 21.60
July 11794221.47 3166.79 09-JUL-14:42 20.13
August 9948855.74 3044.12 06-AUG-15:25 23.75
September 9708180.23 4148.49 04-SEP-16:12 17.60
October 40739475.99 3401.98 08-OCT-11:32 16.87
November 0.334339E+09 2509.28 24-NOV-08:08 1.97
December 0.829864E+09 4443.56 26-DEC-09:10 -0.9
         
Annual Sum or Average 0.355023E+10      
Minimum of Months 9708180.23 1986.78   -0.9
Maximum of Months 0.152748E+10 9500.38   23.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.418725E+09 18238.54 02-JAN-06:11 6.10
February 73846423.95 14655.47 21-FEB-06:01 1.70
March 7665796.03 12166.78 06-MAR-07:03 6.70
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 16952726.18 12258.69 13-NOV-07:01 1.52
December 98329585.00 14950.55 26-DEC-06:02 -0.8
         
Annual Sum or Average 0.615520E+09      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.418725E+09 18238.54   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.166959E+10 27836.82 17-JAN-05:01 1.60
February 0.747899E+09 26782.80 21-FEB-05:51 1.70
March 0.241552E+09 23704.54 06-MAR-06:11 6.70
April 44637477.91 19934.90 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 67873053.46 21176.26 16-OCT-05:11 7.03
November 0.471494E+09 24898.37 13-NOV-05:11 1.30
December 0.109638E+10 27399.41 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.433943E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.166959E+10 27836.82   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.291526E+10 11368.79 17-JAN-05:01 1.60
February 0.168731E+10 11278.25 19-FEB-07:23 -5.0
March 0.649536E+09 10746.59 06-MAR-06:11 6.70
April 0.241477E+09 9633.62 18-APR-05:11 3.30
May 38138682.87 8658.16 18-MAY-05:12 5.60
June 4532930.76 5770.69 14-JUN-06:03 10.10
July 0.00 0.00 01-JUL-00:10 15.43
August 459008.99 964.72 03-AUG-06:03 11.82
September 23337692.07 6822.67 28-SEP-06:03 8.40
October 0.282478E+09 9827.74 16-OCT-05:11 7.03
November 0.105905E+10 11125.58 13-NOV-05:11 1.30
December 0.226769E+10 11029.04 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.916927E+10      
Minimum of Months 0.00 0.00   -5.0
Maximum of Months 0.291526E+10 11368.79   15.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.180124E+10 8564.61 17-JAN-05:01 1.60
February 0.979893E+09 8427.55 13-FEB-05:11 1.47
March 0.352688E+09 8075.75 06-MAR-06:11 6.70
April 0.116332E+09 7162.04 18-APR-05:11 3.30
May 25502681.46 6357.65 18-MAY-05:12 5.60
June 4412006.64 3689.59 14-JUN-06:03 10.10
July 0.00 0.00 01-JUL-00:10 15.43
August 1015348.41 2234.29 18-AUG-06:03 11.63
September 14174920.38 4358.89 28-SEP-06:03 8.40
October 0.173302E+09 7332.23 16-OCT-05:11 7.03
November 0.661171E+09 8368.75 13-NOV-05:11 1.30
December 0.140444E+10 8267.71 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.553417E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.180124E+10 8564.61   15.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.228562E+10 13188.24 17-JAN-05:01 1.60
February 0.118684E+10 12742.27 13-FEB-05:11 1.47
March 0.520233E+09 12389.32 06-MAR-06:11 6.70
April 0.226133E+09 10972.70 18-APR-05:11 3.30
May 49164365.91 9738.22 18-MAY-05:12 5.60
June 11105641.96 5724.41 14-JUN-06:03 10.10
July 255286.91 1152.50 18-JUL-06:03 13.17
August 3908559.08 3333.94 03-AUG-06:03 11.82
September 23398064.10 6778.94 28-SEP-06:03 8.40
October 0.229339E+09 11143.43 16-OCT-05:11 7.03
November 0.866182E+09 12785.07 13-NOV-05:11 1.30
December 0.183158E+10 12752.70 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.723377E+10      
Minimum of Months 255286.91 1152.50   -0.6
Maximum of Months 0.228562E+10 13188.24   13.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.185737E+10 9085.48 17-JAN-05:01 1.60
February 0.103109E+10 8898.66 13-FEB-05:11 1.47
March 0.419555E+09 8552.45 06-MAR-06:11 6.70
April 0.166451E+09 7546.41 18-APR-05:11 3.30
May 34795164.45 6661.23 18-MAY-05:12 5.60
June 8045823.00 3587.35 14-JUN-06:03 10.10
July 359732.74 1617.36 18-JUL-06:03 13.17
August 3507025.66 2737.48 18-AUG-06:03 11.63
September 18820157.69 4318.39 28-SEP-06:03 8.40
October 0.190534E+09 7659.54 16-OCT-05:11 7.03
November 0.693839E+09 8824.00 13-NOV-05:11 1.30
December 0.145774E+10 8756.49 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.588210E+10      
Minimum of Months 359732.74 1617.36   -0.6
Maximum of Months 0.185737E+10 9085.48   13.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.173579E+10 8244.32 02-JAN-06:11 6.10
February 0.825699E+09 7919.26 21-FEB-05:51 1.70
March 0.231180E+09 7047.76 06-MAR-06:11 6.70
April 64841388.81 6508.82 18-APR-05:11 3.30
May 3945976.04 4951.26 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 377320.94 1342.46 28-SEP-06:03 8.40
October 22348304.99 5915.18 30-OCT-06:03 7.20
November 0.216530E+09 6792.36 24-NOV-06:11 1.83
December 0.870940E+09 7813.81 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.397165E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.173579E+10 8244.32   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107213E+10 6526.50 02-JAN-06:11 6.10
February 0.446253E+09 6125.81 21-FEB-05:51 1.70
March 0.111352E+09 5469.32 06-MAR-06:11 6.70
April 30003316.37 4993.51 18-APR-05:11 3.30
May 4781395.82 3689.50 18-MAY-06:03 5.68
June 93427.95 350.15 14-JUN-06:03 10.10
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 1037416.61 2798.28 28-SEP-06:03 8.40
October 17786884.59 4318.42 28-OCT-06:03 7.80
November 0.142770E+09 5272.90 24-NOV-06:11 1.83
December 0.572706E+09 6162.95 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.239892E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.107213E+10 6526.50   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.364409E+10 10379.58 06-JAN-08:00 -2.8
February 0.213540E+10 9803.88 21-FEB-08:00 1.10
March 0.155049E+10 9286.55 01-MAR-07:10 -0.1
April 0.913008E+09 8957.97 18-APR-06:10 3.40
May 0.589741E+09 7832.20 18-MAY-06:10 5.68
June 0.309341E+09 6900.41 15-JUN-06:03 9.60
July 79325699.14 4492.96 10-JUL-06:07 12.88
August 84877114.41 5287.54 18-AUG-06:03 11.63
September 0.266005E+09 7080.91 28-SEP-06:10 8.40
October 0.768143E+09 7694.89 16-OCT-06:50 6.20
November 0.179729E+10 9494.79 24-NOV-07:10 1.20
December 0.277741E+10 10596.92 26-DEC-08:00 -1.1
         
Annual Sum or Average 0.149151E+11      
Minimum of Months 79325699.14 4492.96   -2.8
Maximum of Months 0.364409E+10 10596.92   12.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109141E+10 6893.49 02-JAN-06:11 6.10
February 0.452082E+09 6381.74 21-FEB-05:51 1.70
March 0.134615E+09 5766.80 06-MAR-06:11 6.70
April 41348107.32 5217.59 18-APR-05:11 3.30
May 6192813.34 3719.24 18-MAY-06:03 5.68
June 200063.28 499.46 07-JUN-06:03 10.10
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 991210.75 2617.55 28-SEP-06:03 8.40
October 18424550.48 4429.50 28-OCT-06:03 7.80
November 0.142431E+09 5490.89 24-NOV-06:11 1.83
December 0.562266E+09 6476.51 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.244996E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.109141E+10 6893.49   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.136604E+10 8541.71 17-JAN-05:01 1.60
February 0.573131E+09 8386.22 21-FEB-05:51 1.70
March 0.145288E+09 7407.13 06-MAR-06:11 6.70
April 38227591.59 6677.92 18-APR-05:11 3.30
May 1619790.49 4926.18 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 1024561.75 2750.57 28-SEP-06:03 8.40
October 39294594.06 6662.92 30-OCT-05:11 7.20
November 0.308782E+09 7485.81 13-NOV-06:01 1.70
December 0.862690E+09 8591.90 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.333610E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.136604E+10 8591.90   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.861419E+09 7387.97 17-JAN-05:01 1.60
February 0.345301E+09 7213.54 21-FEB-05:51 1.70
March 85248915.65 6260.63 06-MAR-06:11 6.70
April 24151444.48 5488.68 18-APR-05:11 3.30
May 4497185.65 3639.05 18-MAY-06:03 5.68
June 403840.05 1595.32 14-JUN-06:03 10.10
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 2604026.83 3368.10 28-SEP-06:03 8.40
October 33853003.80 5442.33 16-OCT-05:11 7.03
November 0.207698E+09 6319.35 24-NOV-06:11 1.83
December 0.571605E+09 7484.88 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.213678E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.861419E+09 7484.88   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.105046E+10 10767.04 17-JAN-05:01 1.60
February 0.400654E+09 10192.53 21-FEB-05:51 1.70
March 0.116989E+09 9077.40 06-MAR-06:11 6.70
April 43467253.72 8001.94 18-APR-05:11 3.30
May 7160658.23 5762.55 18-MAY-06:03 5.68
June 456832.38 1294.95 14-JUN-06:03 10.10
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 2664510.26 5097.93 28-SEP-06:03 8.40
October 38933699.49 7822.65 16-OCT-05:11 7.03
November 0.242792E+09 9095.53 24-NOV-06:11 1.83
December 0.703242E+09 10675.93 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.260682E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.105046E+10 10767.04   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.884776E+09 7467.45 17-JAN-05:01 1.60
February 0.356606E+09 7218.76 21-FEB-05:51 1.70
March 0.106415E+09 6325.24 06-MAR-06:11 6.70
April 34563638.43 5554.59 18-APR-05:11 3.30
May 6633207.36 3714.29 18-MAY-06:03 5.68
June 567667.04 1435.67 14-JUN-06:03 10.10
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 2747385.14 3310.39 28-SEP-06:03 8.40
October 34831867.83 5410.54 16-OCT-05:11 7.03
November 0.215552E+09 6343.20 24-NOV-06:11 1.83
December 0.574845E+09 7546.71 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.221754E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.884776E+09 7546.71   17.17



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.932724E+10 9760.61 02-JAN-08:09 0.219109E+11 14257.50 02-JAN-08:09
February 0.846050E+10 9760.61 01-FEB-08:09 0.198568E+11 14257.50 01-FEB-08:09
March 0.100534E+11 9760.61 01-MAR-08:09 0.225201E+11 14257.50 01-MAR-08:09
April 0.897976E+10 9760.61 03-APR-07:10 0.212729E+11 14257.50 03-APR-07:10
May 0.969033E+10 9760.61 01-MAY-07:10 0.222155E+11 14257.50 01-MAY-07:10
June 0.964348E+10 9760.61 01-JUN-07:10 0.217316E+11 14257.50 01-JUN-07:10
July 0.902661E+10 9760.61 03-JUL-07:10 0.217545E+11 14257.50 03-JUL-07:10
August 0.100534E+11 9760.61 01-AUG-07:10 0.225201E+11 14257.50 01-AUG-07:10
September 0.897976E+10 9760.61 01-SEP-07:10 0.212685E+11 14257.50 01-SEP-07:10
October 0.932724E+10 9760.61 02-OCT-07:10 0.219131E+11 14257.50 02-OCT-07:10
November 0.921792E+10 9760.61 01-NOV-07:10 0.212833E+11 14257.50 01-NOV-07:10
December 0.902661E+10 9760.61 01-DEC-08:09 0.217523E+11 14257.50 01-DEC-08:09
             
Annual Sum or Average 0.111786E+12     0.259999E+12    
Minimum of Months 0.846050E+10 9760.61   0.198568E+11 14257.50  
Maximum of Months 0.100534E+11 9760.61   0.225201E+11 14257.50  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.932724E+10 9760.61 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.846050E+10 9760.61 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.100534E+11 9760.61 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.897976E+10 9760.61 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.969033E+10 9760.61 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.964348E+10 9760.61 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.902661E+10 9760.61 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.100534E+11 9760.61 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.897976E+10 9760.61 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.932724E+10 9760.61 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.921792E+10 9760.61 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.902661E+10 9760.61 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.111786E+12     0.115425E+12    
Minimum of Months 0.846050E+10 9760.61   0.879311E+10 6808.32  
Maximum of Months 0.100534E+11 9760.61   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.932724E+10 9760.61 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.846050E+10 9760.61 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.100534E+11 9760.61 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.897976E+10 9760.61 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.969033E+10 9760.61 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.964348E+10 9760.61 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.902661E+10 9760.61 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.100534E+11 9760.61 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.897976E+10 9760.61 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.932724E+10 9760.61 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.921792E+10 9760.61 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.902661E+10 9760.61 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.111786E+12     0.115425E+12    
Minimum of Months 0.846050E+10 9760.61   0.879311E+10 6808.32  
Maximum of Months 0.100534E+11 9760.61   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196626E+10 2057.62 02-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.178355E+10 2057.62 01-FEB-08:09 0.185366E+10 1435.25 01-FEB-08:09
March 0.211935E+10 2057.62 01-MAR-08:09 0.212947E+10 1435.25 01-MAR-08:09
April 0.189301E+10 2057.62 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.204281E+10 2057.62 01-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.203293E+10 2057.62 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.190289E+10 2057.62 03-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.211935E+10 2057.62 01-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.189301E+10 2057.62 01-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.196626E+10 2057.62 02-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.194322E+10 2057.62 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.190289E+10 2057.62 01-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.235655E+11     0.243325E+11    
Minimum of Months 0.178355E+10 2057.62   0.185366E+10 1435.25  
Maximum of Months 0.211935E+10 2057.62   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124481E+10 1302.65 02-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.112913E+10 1302.65 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.134172E+10 1302.65 01-MAR-08:09 0.134804E+10 908.57 01-MAR-08:09
April 0.119843E+10 1302.65 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.129327E+10 1302.65 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.128701E+10 1302.65 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.120469E+10 1302.65 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.134172E+10 1302.65 01-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.119843E+10 1302.65 01-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.124481E+10 1302.65 02-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.123022E+10 1302.65 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.120469E+10 1302.65 01-DEC-08:09 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.149189E+11     0.154036E+11    
Minimum of Months 0.112913E+10 1302.65   0.117344E+10 908.57  
Maximum of Months 0.134172E+10 1302.65   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196626E+10 2057.62 02-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.178355E+10 2057.62 01-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.211935E+10 2057.62 01-MAR-08:09 0.212945E+10 1435.24 01-MAR-08:09
April 0.189301E+10 2057.62 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.204281E+10 2057.62 01-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.203293E+10 2057.62 01-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.190289E+10 2057.62 03-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.211935E+10 2057.62 01-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.189301E+10 2057.62 01-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.196626E+10 2057.62 02-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.194322E+10 2057.62 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.190289E+10 2057.62 01-DEC-08:09 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.235655E+11     0.243324E+11    
Minimum of Months 0.178355E+10 2057.62   0.185364E+10 1435.24  
Maximum of Months 0.211935E+10 2057.62   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124473E+10 1302.56 02-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.112906E+10 1302.56 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.134164E+10 1302.56 01-MAR-08:09 0.134804E+10 908.57 01-MAR-08:09
April 0.119835E+10 1302.56 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.129318E+10 1302.56 01-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.128693E+10 1302.56 01-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.120461E+10 1302.56 03-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.134164E+10 1302.56 01-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.119835E+10 1302.56 01-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.124473E+10 1302.56 02-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.123014E+10 1302.56 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.120461E+10 1302.56 01-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.149180E+11     0.154035E+11    
Minimum of Months 0.112906E+10 1302.56   0.117344E+10 908.57  
Maximum of Months 0.134164E+10 1302.56   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196626E+10 2057.62 02-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.178355E+10 2057.62 01-FEB-08:09 0.185366E+10 1435.25 01-FEB-08:09
March 0.211935E+10 2057.62 01-MAR-08:09 0.212947E+10 1435.25 01-MAR-08:09
April 0.189301E+10 2057.62 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.204281E+10 2057.62 01-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.203293E+10 2057.62 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.190289E+10 2057.62 03-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.211935E+10 2057.62 01-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.189301E+10 2057.62 01-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.196626E+10 2057.62 02-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.194322E+10 2057.62 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.190289E+10 2057.62 01-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.235655E+11     0.243325E+11    
Minimum of Months 0.178355E+10 2057.62   0.185366E+10 1435.25  
Maximum of Months 0.211935E+10 2057.62   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124481E+10 1302.65 02-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.112913E+10 1302.65 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.134172E+10 1302.65 01-MAR-08:09 0.134804E+10 908.57 01-MAR-08:09
April 0.119843E+10 1302.65 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.129327E+10 1302.65 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.128701E+10 1302.65 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.120469E+10 1302.65 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.134172E+10 1302.65 01-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.119843E+10 1302.65 01-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.124481E+10 1302.65 02-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.123022E+10 1302.65 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.120469E+10 1302.65 01-DEC-08:09 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.149189E+11     0.154036E+11    
Minimum of Months 0.112913E+10 1302.65   0.117344E+10 908.57  
Maximum of Months 0.134172E+10 1302.65   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196626E+10 2057.62 02-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.178355E+10 2057.62 01-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.211935E+10 2057.62 01-MAR-08:09 0.212945E+10 1435.24 01-MAR-08:09
April 0.189301E+10 2057.62 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.204281E+10 2057.62 01-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.203293E+10 2057.62 01-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.190289E+10 2057.62 03-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.211935E+10 2057.62 01-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.189301E+10 2057.62 01-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.196626E+10 2057.62 02-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.194322E+10 2057.62 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.190289E+10 2057.62 01-DEC-08:09 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.235655E+11     0.243324E+11    
Minimum of Months 0.178355E+10 2057.62   0.185364E+10 1435.24  
Maximum of Months 0.211935E+10 2057.62   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124473E+10 1302.56 02-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.112906E+10 1302.56 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.134164E+10 1302.56 01-MAR-08:09 0.134804E+10 908.57 01-MAR-08:09
April 0.119835E+10 1302.56 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.129318E+10 1302.56 01-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.128693E+10 1302.56 01-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.120461E+10 1302.56 03-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.134164E+10 1302.56 01-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.119835E+10 1302.56 01-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.124473E+10 1302.56 02-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.123014E+10 1302.56 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.120461E+10 1302.56 01-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.149180E+11     0.154035E+11    
Minimum of Months 0.112906E+10 1302.56   0.117344E+10 908.57  
Maximum of Months 0.134164E+10 1302.56   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196626E+10 2057.62 02-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.178355E+10 2057.62 01-FEB-08:09 0.185366E+10 1435.25 01-FEB-08:09
March 0.211935E+10 2057.62 01-MAR-08:09 0.212947E+10 1435.25 01-MAR-08:09
April 0.189301E+10 2057.62 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.204281E+10 2057.62 01-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.203293E+10 2057.62 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.190289E+10 2057.62 03-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.211935E+10 2057.62 01-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.189301E+10 2057.62 01-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.196626E+10 2057.62 02-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.194322E+10 2057.62 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.190289E+10 2057.62 01-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.235655E+11     0.243325E+11    
Minimum of Months 0.178355E+10 2057.62   0.185366E+10 1435.25  
Maximum of Months 0.211935E+10 2057.62   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124481E+10 1302.65 02-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.112913E+10 1302.65 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.134172E+10 1302.65 01-MAR-08:09 0.134804E+10 908.57 01-MAR-08:09
April 0.119843E+10 1302.65 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.129327E+10 1302.65 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.128701E+10 1302.65 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.120469E+10 1302.65 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.134172E+10 1302.65 01-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.119843E+10 1302.65 01-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.124481E+10 1302.65 02-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.123022E+10 1302.65 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.120469E+10 1302.65 01-DEC-08:09 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.149189E+11     0.154036E+11    
Minimum of Months 0.112913E+10 1302.65   0.117344E+10 908.57  
Maximum of Months 0.134172E+10 1302.65   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.196626E+10 2057.62 02-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.178355E+10 2057.62 01-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.211935E+10 2057.62 01-MAR-08:09 0.212945E+10 1435.24 01-MAR-08:09
April 0.189301E+10 2057.62 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.204281E+10 2057.62 01-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.203293E+10 2057.62 01-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.190289E+10 2057.62 03-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.211935E+10 2057.62 01-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.189301E+10 2057.62 01-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.196626E+10 2057.62 02-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.194322E+10 2057.62 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.190289E+10 2057.62 01-DEC-08:09 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.235655E+11     0.243324E+11    
Minimum of Months 0.178355E+10 2057.62   0.185364E+10 1435.24  
Maximum of Months 0.211935E+10 2057.62   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124473E+10 1302.56 02-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.112906E+10 1302.56 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.134164E+10 1302.56 01-MAR-08:09 0.134804E+10 908.57 01-MAR-08:09
April 0.119835E+10 1302.56 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.129318E+10 1302.56 01-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.128693E+10 1302.56 01-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.120461E+10 1302.56 03-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.134164E+10 1302.56 01-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.119835E+10 1302.56 01-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.124473E+10 1302.56 02-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.123014E+10 1302.56 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.120461E+10 1302.56 01-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.149180E+11     0.154035E+11    
Minimum of Months 0.112906E+10 1302.56   0.117344E+10 908.57  
Maximum of Months 0.134164E+10 1302.56   0.134804E+10 908.57  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.932724E+10 0.219109E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.846050E+10 0.198568E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.100534E+11 0.225201E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.897976E+10 0.212729E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.969033E+10 0.222155E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.964348E+10 0.217316E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.902661E+10 0.217545E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.100534E+11 0.225201E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.897976E+10 0.212685E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.932724E+10 0.219131E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.921792E+10 0.212833E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.902661E+10 0.217523E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.111786E+12 0.259999E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.846050E+10 0.198568E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.100534E+11 0.225201E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.932724E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.846050E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.100534E+11 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.897976E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.969033E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.964348E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.902661E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.100534E+11 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.897976E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.932724E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.921792E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.902661E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.111786E+12 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.846050E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.100534E+11 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.932724E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.846050E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.100534E+11 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.897976E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.969033E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.964348E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.902661E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.100534E+11 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.897976E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.932724E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.921792E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.902661E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.111786E+12 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.846050E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.100534E+11 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.196626E+10 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.789407E+09
February 0.901968E+09 0.178355E+10 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.702729E+09
March 0.107774E+10 0.211935E+10 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.675848E+09
April 0.956342E+09 0.189301E+10 0.197726E+10 0.00 0.00 0.00 0.00 2136672.83 0.651639E+09
May 0.103597E+10 0.204281E+10 0.208852E+10 0.00 0.00 0.00 0.00 69525.64 0.526384E+09
June 0.103308E+10 0.203293E+10 0.205071E+10 0.00 0.00 0.00 0.00 470253.49 0.445912E+09
July 0.959235E+09 0.190289E+10 0.201461E+10 0.00 0.00 0.00 0.00 10505611.35 0.376848E+09
August 0.107774E+10 0.211935E+10 0.212947E+10 0.00 0.00 0.00 0.00 12886913.91 0.299502E+09
September 0.956342E+09 0.189301E+10 0.197634E+10 0.00 0.00 0.00 0.00 63637.36 0.238758E+09
October 0.994195E+09 0.196626E+10 0.204804E+10 0.00 0.00 0.00 0.00 0.00 0.528918E+09
November 0.984487E+09 0.194322E+10 0.200273E+10 0.00 0.00 0.00 0.00 91.63 0.602925E+09
December 0.959235E+09 0.190289E+10 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.661837E+09
                   
Annual Sum or Average 0.119305E+11 0.235655E+11 0.243325E+11 0.00 0.00 0.00 0.00 26132706.19 0.650071E+10
Minimum of Months 0.901968E+09 0.178355E+10 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.238758E+09
Maximum of Months 0.107774E+10 0.211935E+10 0.212947E+10 0.00 0.00 0.00 0.00 12886913.91 0.789407E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.124481E+10 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.524839E+09
February 0.571020E+09 0.112913E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.472148E+09
March 0.682301E+09 0.134172E+10 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.452394E+09
April 0.605444E+09 0.119843E+10 0.125169E+10 0.00 0.00 0.00 0.00 1371496.20 0.441236E+09
May 0.655854E+09 0.129327E+10 0.132213E+10 0.00 0.00 0.00 0.00 35685.43 0.355213E+09
June 0.654023E+09 0.128701E+10 0.129819E+10 0.00 0.00 0.00 0.00 342362.45 0.302908E+09
July 0.607275E+09 0.120469E+10 0.127534E+10 0.00 0.00 0.00 0.00 6019942.68 0.253783E+09
August 0.682301E+09 0.134172E+10 0.134804E+10 0.00 0.00 0.00 0.00 8023878.03 0.203327E+09
September 0.605444E+09 0.119843E+10 0.125111E+10 0.00 0.00 0.00 0.00 37516.02 0.161802E+09
October 0.629407E+09 0.124481E+10 0.129650E+10 0.00 0.00 0.00 0.00 0.00 0.356247E+09
November 0.623262E+09 0.123022E+10 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.400997E+09
December 0.607275E+09 0.120469E+10 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.440510E+09
                   
Annual Sum or Average 0.755301E+10 0.149189E+11 0.154036E+11 0.00 0.00 0.00 0.00 15830880.81 0.436540E+10
Minimum of Months 0.571020E+09 0.112913E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.161802E+09
Maximum of Months 0.682301E+09 0.134172E+10 0.134804E+10 0.00 0.00 0.00 0.00 8023878.03 0.524839E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.196626E+10 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.802643E+09
February 0.901968E+09 0.178355E+10 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.743847E+09
March 0.107774E+10 0.211935E+10 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.704641E+09
April 0.956342E+09 0.189301E+10 0.197725E+10 0.00 0.00 0.00 0.00 1351242.83 0.677219E+09
May 0.103597E+10 0.204281E+10 0.208851E+10 0.00 0.00 0.00 0.00 42717.87 0.539194E+09
June 0.103308E+10 0.203293E+10 0.205070E+10 0.00 0.00 0.00 0.00 493555.09 0.449592E+09
July 0.959235E+09 0.190289E+10 0.201460E+10 0.00 0.00 0.00 0.00 6762846.62 0.381427E+09
August 0.107774E+10 0.211935E+10 0.212945E+10 0.00 0.00 0.00 0.00 10855503.55 0.306826E+09
September 0.956342E+09 0.189301E+10 0.197632E+10 0.00 0.00 0.00 0.00 43154.43 0.254057E+09
October 0.994195E+09 0.196626E+10 0.204803E+10 0.00 0.00 0.00 0.00 0.00 0.563845E+09
November 0.984487E+09 0.194322E+10 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.619752E+09
December 0.959235E+09 0.190289E+10 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.680779E+09
                   
Annual Sum or Average 0.119305E+11 0.235655E+11 0.243324E+11 0.00 0.00 0.00 0.00 19549020.40 0.672382E+10
Minimum of Months 0.901968E+09 0.178355E+10 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.254057E+09
Maximum of Months 0.107774E+10 0.211935E+10 0.212945E+10 0.00 0.00 0.00 0.00 10855503.55 0.802643E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.124473E+10 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.525926E+09
February 0.570983E+09 0.112906E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.475675E+09
March 0.682256E+09 0.134164E+10 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.457127E+09
April 0.605404E+09 0.119835E+10 0.125169E+10 0.00 0.00 0.00 0.00 693417.62 0.443950E+09
May 0.655811E+09 0.129318E+10 0.132212E+10 0.00 0.00 0.00 0.00 66413.89 0.363113E+09
June 0.653980E+09 0.128693E+10 0.129818E+10 0.00 0.00 0.00 0.00 327805.45 0.301279E+09
July 0.607235E+09 0.120461E+10 0.127533E+10 0.00 0.00 0.00 0.00 4630777.04 0.262630E+09
August 0.682256E+09 0.134164E+10 0.134804E+10 0.00 0.00 0.00 0.00 7981153.29 0.206504E+09
September 0.605404E+09 0.119835E+10 0.125110E+10 0.00 0.00 0.00 0.00 28778.17 0.166487E+09
October 0.629366E+09 0.124473E+10 0.129649E+10 0.00 0.00 0.00 0.00 0.00 0.359840E+09
November 0.623221E+09 0.123014E+10 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.402899E+09
December 0.607235E+09 0.120461E+10 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.441801E+09
                   
Annual Sum or Average 0.755252E+10 0.149180E+11 0.154035E+11 0.00 0.00 0.00 0.00 13728345.46 0.440723E+10
Minimum of Months 0.570983E+09 0.112906E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.166487E+09
Maximum of Months 0.682256E+09 0.134164E+10 0.134804E+10 0.00 0.00 0.00 0.00 7981153.29 0.525926E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.196626E+10 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.448825E+09
February 0.901968E+09 0.178355E+10 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.400127E+09
March 0.107774E+10 0.211935E+10 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.380337E+09
April 0.956342E+09 0.189301E+10 0.197726E+10 0.00 0.00 0.00 0.00 1381198.77 0.357507E+09
May 0.103597E+10 0.204281E+10 0.208852E+10 0.00 0.00 0.00 0.00 142009.95 0.288134E+09
June 0.103308E+10 0.203293E+10 0.205071E+10 0.00 0.00 0.00 0.00 280873.24 0.245157E+09
July 0.959235E+09 0.190289E+10 0.201461E+10 0.00 0.00 0.00 0.00 6243116.59 0.208104E+09
August 0.107774E+10 0.211935E+10 0.212947E+10 0.00 0.00 0.00 0.00 7235893.24 0.168959E+09
September 0.956342E+09 0.189301E+10 0.197634E+10 0.00 0.00 0.00 0.00 37553.33 0.138138E+09
October 0.994195E+09 0.196626E+10 0.204804E+10 0.00 0.00 0.00 0.00 0.00 0.314973E+09
November 0.984487E+09 0.194322E+10 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.361706E+09
December 0.959235E+09 0.190289E+10 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.390576E+09
                   
Annual Sum or Average 0.119305E+11 0.235655E+11 0.243325E+11 0.00 0.00 0.00 0.00 15320645.11 0.370254E+10
Minimum of Months 0.901968E+09 0.178355E+10 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.138138E+09
Maximum of Months 0.107774E+10 0.211935E+10 0.212947E+10 0.00 0.00 0.00 0.00 7235893.24 0.448825E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.124481E+10 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.298613E+09
February 0.571020E+09 0.112913E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.270255E+09
March 0.682301E+09 0.134172E+10 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.256841E+09
April 0.605444E+09 0.119843E+10 0.125169E+10 0.00 0.00 0.00 0.00 772003.14 0.246302E+09
May 0.655854E+09 0.129327E+10 0.132213E+10 0.00 0.00 0.00 0.00 36170.88 0.197822E+09
June 0.654023E+09 0.128701E+10 0.129819E+10 0.00 0.00 0.00 0.00 190843.34 0.171230E+09
July 0.607275E+09 0.120469E+10 0.127534E+10 0.00 0.00 0.00 0.00 3259089.69 0.142394E+09
August 0.682301E+09 0.134172E+10 0.134804E+10 0.00 0.00 0.00 0.00 4203199.36 0.117671E+09
September 0.605444E+09 0.119843E+10 0.125111E+10 0.00 0.00 0.00 0.00 20893.27 94415320.01
October 0.629407E+09 0.124481E+10 0.129650E+10 0.00 0.00 0.00 0.00 0.00 0.213022E+09
November 0.623262E+09 0.123022E+10 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.240359E+09
December 0.607275E+09 0.120469E+10 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.260081E+09
                   
Annual Sum or Average 0.755301E+10 0.149189E+11 0.154036E+11 0.00 0.00 0.00 0.00 8482199.67 0.250900E+10
Minimum of Months 0.571020E+09 0.112913E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 94415320.01
Maximum of Months 0.682301E+09 0.134172E+10 0.134804E+10 0.00 0.00 0.00 0.00 4203199.36 0.298613E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.196626E+10 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.429974E+10
February 0.901968E+09 0.178355E+10 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.372460E+10
March 0.107774E+10 0.211935E+10 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.386179E+10
April 0.956342E+09 0.189301E+10 0.197725E+10 0.00 0.00 0.00 0.00 14672581.27 0.288528E+10
May 0.103597E+10 0.204281E+10 0.208851E+10 0.00 0.00 0.00 0.00 1739960.18 0.246727E+10
June 0.103308E+10 0.203293E+10 0.205070E+10 0.00 0.00 0.00 0.00 16102133.96 0.187703E+10
July 0.959235E+09 0.190289E+10 0.201460E+10 0.00 0.00 0.00 0.00 96464296.00 0.123785E+10
August 0.107774E+10 0.211935E+10 0.212945E+10 0.00 0.00 0.00 0.00 0.258864E+09 0.116261E+10
September 0.956342E+09 0.189301E+10 0.197632E+10 0.00 0.00 0.00 0.00 3517984.60 0.176100E+10
October 0.994195E+09 0.196626E+10 0.204803E+10 0.00 0.00 0.00 0.00 0.00 0.289698E+10
November 0.984487E+09 0.194322E+10 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.371741E+10
December 0.959235E+09 0.190289E+10 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.411671E+10
                   
Annual Sum or Average 0.119305E+11 0.235655E+11 0.243324E+11 0.00 0.00 0.00 0.00 0.391361E+09 0.340083E+11
Minimum of Months 0.901968E+09 0.178355E+10 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.116261E+10
Maximum of Months 0.107774E+10 0.211935E+10 0.212945E+10 0.00 0.00 0.00 0.00 0.258864E+09 0.429974E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.124473E+10 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.299345E+09
February 0.570983E+09 0.112906E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.271259E+09
March 0.682256E+09 0.134164E+10 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.258708E+09
April 0.605404E+09 0.119835E+10 0.125169E+10 0.00 0.00 0.00 0.00 422155.52 0.246105E+09
May 0.655811E+09 0.129318E+10 0.132212E+10 0.00 0.00 0.00 0.00 58281.97 0.202932E+09
June 0.653980E+09 0.128693E+10 0.129818E+10 0.00 0.00 0.00 0.00 195044.41 0.168581E+09
July 0.607235E+09 0.120461E+10 0.127533E+10 0.00 0.00 0.00 0.00 2546443.69 0.150999E+09
August 0.682256E+09 0.134164E+10 0.134804E+10 0.00 0.00 0.00 0.00 4304346.02 0.120324E+09
September 0.605404E+09 0.119835E+10 0.125110E+10 0.00 0.00 0.00 0.00 17440.06 97751435.04
October 0.629366E+09 0.124473E+10 0.129649E+10 0.00 0.00 0.00 0.00 0.00 0.214160E+09
November 0.623221E+09 0.123014E+10 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.241128E+09
December 0.607235E+09 0.120461E+10 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.260806E+09
                   
Annual Sum or Average 0.755252E+10 0.149180E+11 0.154035E+11 0.00 0.00 0.00 0.00 7543711.67 0.253210E+10
Minimum of Months 0.570983E+09 0.112906E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 97751435.04
Maximum of Months 0.682256E+09 0.134164E+10 0.134804E+10 0.00 0.00 0.00 0.00 4304346.02 0.299345E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.196626E+10 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.697811E+09
February 0.901968E+09 0.178355E+10 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.627490E+09
March 0.107774E+10 0.211935E+10 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.611700E+09
April 0.956342E+09 0.189301E+10 0.197726E+10 0.00 0.00 0.00 0.00 1770809.92 0.585830E+09
May 0.103597E+10 0.204281E+10 0.208852E+10 0.00 0.00 0.00 0.00 43675.25 0.472217E+09
June 0.103308E+10 0.203293E+10 0.205071E+10 0.00 0.00 0.00 0.00 400558.67 0.397833E+09
July 0.959235E+09 0.190289E+10 0.201461E+10 0.00 0.00 0.00 0.00 8809130.32 0.336385E+09
August 0.107774E+10 0.211935E+10 0.212947E+10 0.00 0.00 0.00 0.00 10460437.97 0.272243E+09
September 0.956342E+09 0.189301E+10 0.197634E+10 0.00 0.00 0.00 0.00 43084.09 0.219285E+09
October 0.994195E+09 0.196626E+10 0.204804E+10 0.00 0.00 0.00 0.00 0.00 0.488913E+09
November 0.984487E+09 0.194322E+10 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.552747E+09
December 0.959235E+09 0.190289E+10 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.600216E+09
                   
Annual Sum or Average 0.119305E+11 0.235655E+11 0.243325E+11 0.00 0.00 0.00 0.00 21527696.21 0.586267E+10
Minimum of Months 0.901968E+09 0.178355E+10 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.219285E+09
Maximum of Months 0.107774E+10 0.211935E+10 0.212947E+10 0.00 0.00 0.00 0.00 10460437.97 0.697811E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.465148E+09 0.124481E+10 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.463942E+09
February 0.421807E+09 0.112913E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.423565E+09
March 0.502994E+09 0.134172E+10 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.411010E+09
April 0.447140E+09 0.119843E+10 0.125169E+10 0.00 0.00 0.00 0.00 1157365.81 0.395780E+09
May 0.484071E+09 0.129327E+10 0.132213E+10 0.00 0.00 0.00 0.00 48003.91 0.314641E+09
June 0.482240E+09 0.128701E+10 0.129819E+10 0.00 0.00 0.00 0.00 319174.19 0.266323E+09
July 0.448971E+09 0.120469E+10 0.127534E+10 0.00 0.00 0.00 0.00 5888196.90 0.223828E+09
August 0.502994E+09 0.134172E+10 0.134804E+10 0.00 0.00 0.00 0.00 6963508.66 0.181737E+09
September 0.447140E+09 0.119843E+10 0.125111E+10 0.00 0.00 0.00 0.00 36345.99 0.146340E+09
October 0.465148E+09 0.124481E+10 0.129650E+10 0.00 0.00 0.00 0.00 0.00 0.328387E+09
November 0.460569E+09 0.123022E+10 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.367785E+09
December 0.448971E+09 0.120469E+10 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.399562E+09
                   
Annual Sum or Average 0.557719E+10 0.149189E+11 0.154036E+11 0.00 0.00 0.00 0.00 14412595.45 0.392290E+10
Minimum of Months 0.421807E+09 0.112913E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.146340E+09
Maximum of Months 0.502994E+09 0.134172E+10 0.134804E+10 0.00 0.00 0.00 0.00 6963508.66 0.463942E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.196626E+10 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.713848E+09
February 0.901968E+09 0.178355E+10 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.667806E+09
March 0.107774E+10 0.211935E+10 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.634344E+09
April 0.956342E+09 0.189301E+10 0.197725E+10 0.00 0.00 0.00 0.00 1188069.55 0.603524E+09
May 0.103597E+10 0.204281E+10 0.208851E+10 0.00 0.00 0.00 0.00 38092.66 0.477351E+09
June 0.103308E+10 0.203293E+10 0.205070E+10 0.00 0.00 0.00 0.00 426303.36 0.396984E+09
July 0.959235E+09 0.190289E+10 0.201460E+10 0.00 0.00 0.00 0.00 6052850.76 0.337678E+09
August 0.107774E+10 0.211935E+10 0.212945E+10 0.00 0.00 0.00 0.00 9105683.67 0.275289E+09
September 0.956342E+09 0.189301E+10 0.197632E+10 0.00 0.00 0.00 0.00 38401.13 0.228513E+09
October 0.994195E+09 0.196626E+10 0.204803E+10 0.00 0.00 0.00 0.00 0.00 0.514197E+09
November 0.984487E+09 0.194322E+10 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.565835E+09
December 0.959235E+09 0.190289E+10 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.617845E+09
                   
Annual Sum or Average 0.119305E+11 0.235655E+11 0.243324E+11 0.00 0.00 0.00 0.00 16849401.13 0.603321E+10
Minimum of Months 0.901968E+09 0.178355E+10 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.228513E+09
Maximum of Months 0.107774E+10 0.211935E+10 0.212945E+10 0.00 0.00 0.00 0.00 9105683.67 0.713848E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.124473E+10 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.464773E+09
February 0.570983E+09 0.112906E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.424579E+09
March 0.682256E+09 0.134164E+10 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.410918E+09
April 0.605404E+09 0.119835E+10 0.125169E+10 0.00 0.00 0.00 0.00 594155.80 0.394859E+09
May 0.655811E+09 0.129318E+10 0.132212E+10 0.00 0.00 0.00 0.00 56659.43 0.321167E+09
June 0.653980E+09 0.128693E+10 0.129818E+10 0.00 0.00 0.00 0.00 284459.89 0.265761E+09
July 0.607235E+09 0.120461E+10 0.127533E+10 0.00 0.00 0.00 0.00 3987363.94 0.232350E+09
August 0.682256E+09 0.134164E+10 0.134804E+10 0.00 0.00 0.00 0.00 6659690.70 0.185320E+09
September 0.605404E+09 0.119835E+10 0.125110E+10 0.00 0.00 0.00 0.00 25608.02 0.149724E+09
October 0.629366E+09 0.124473E+10 0.129649E+10 0.00 0.00 0.00 0.00 0.00 0.327930E+09
November 0.623221E+09 0.123014E+10 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.367363E+09
December 0.607235E+09 0.120461E+10 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.400100E+09
                   
Annual Sum or Average 0.755252E+10 0.149180E+11 0.154035E+11 0.00 0.00 0.00 0.00 11607937.77 0.394484E+10
Minimum of Months 0.570983E+09 0.112906E+10 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.149724E+09
Maximum of Months 0.682256E+09 0.134164E+10 0.134804E+10 0.00 0.00 0.00 0.00 6659690.70 0.464773E+09



Table of Contents

Report: SpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.100436E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.921464E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.893704E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1514884.26 0.843268E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3029.99 0.673219E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 186158.88 0.562200E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6621188.96 0.476078E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9262093.21 0.393167E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 765.49 0.321953E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.729040E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.817898E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.885041E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17588120.79 0.852140E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.321953E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9262093.21 0.100436E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.120855E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110362E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.108442E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2399784.86 0.103398E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4620.20 0.834639E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 247279.87 0.700465E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9463536.00 0.590928E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12381894.62 0.485430E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1443.33 0.391762E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.865704E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.965904E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.105099E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24498558.88 0.103164E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.391762E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12381894.62 0.120855E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.113794E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.104405E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.100704E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 980316.45 0.997472E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.828920E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12376.70 0.703344E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1791967.41 0.593353E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6356654.36 0.459715E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.367766E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.794998E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.876318E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.955831E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9141314.92 0.976674E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.367766E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6356654.36 0.113794E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 9760.61 02-JAN-08:09 14257.50 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 9760.61 01-FEB-08:09 14257.50 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 9760.61 01-MAR-08:09 14257.50 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 9760.61 03-APR-07:10 14257.50 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 9760.61 01-MAY-07:10 14257.50 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 9760.61 01-JUN-07:10 14257.50 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 9760.61 03-JUL-07:10 14257.50 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 9760.61 01-AUG-07:10 14257.50 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 9760.61 01-SEP-07:10 14257.50 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 9760.61 02-OCT-07:10 14257.50 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 9760.61 01-NOV-07:10 14257.50 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 9760.61 01-DEC-08:09 14257.50 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   9760.61   14257.50   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   9760.61   14257.50   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 9760.61 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 9760.61 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 9760.61 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 9760.61 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 9760.61 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 9760.61 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 9760.61 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 9760.61 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 9760.61 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 9760.61 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 9760.61 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 9760.61 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   9760.61   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   9760.61   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 9760.61 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 9760.61 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 9760.61 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 9760.61 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 9760.61 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 9760.61 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 9760.61 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 9760.61 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 9760.61 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 9760.61 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 9760.61 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 9760.61 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   9760.61   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   9760.61   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 2057.62 02-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1349.34 12-JAN-22:03
February 1306.65 01-FEB-10:09 2057.62 01-FEB-08:09 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1270.04 16-FEB-22:03
March 1306.65 01-MAR-10:09 2057.62 01-MAR-08:09 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1112.37 28-MAR-24:00
April 1306.65 03-APR-09:09 2057.62 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 276.62 01-APR-17:02 1266.00 10-APR-21:03
May 1306.65 01-MAY-09:09 2057.62 01-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 22.56 14-MAY-15:00 892.24 22-MAY-24:00
June 1306.65 01-JUN-09:09 2057.62 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 21.17 28-JUN-16:00 1164.46 13-JUN-03:00
July 1306.65 03-JUL-09:09 2057.62 03-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 288.36 23-JUL-16:00 576.93 02-JUL-04:00
August 1306.65 01-AUG-09:09 2057.62 01-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 156.31 13-AUG-14:50 869.78 11-AUG-04:00
September 1306.65 01-SEP-09:09 2057.62 01-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 6.64 14-SEP-17:00 546.16 18-SEP-23:00
October 1306.65 02-OCT-09:09 2057.62 02-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1166.80 31-OCT-21:03
November 1306.65 01-NOV-09:09 2057.62 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.06 04-NOV-14:13 1268.46 29-NOV-22:03
December 1306.65 01-DEC-10:09 2057.62 01-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1048.17 22-DEC-22:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   2057.62   1435.25   0.00 0.00 0.00 0.00 0.00   546.16  
Maximum of Months 1306.65   2057.62   1435.25   0.00 0.00 0.00 0.00 288.36   1349.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 1302.65 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 898.24 12-JAN-22:03
February 827.22 01-FEB-10:09 1302.65 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 845.89 16-FEB-22:03
March 827.22 01-MAR-10:09 1302.65 01-MAR-08:09 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 746.84 28-MAR-24:00
April 827.22 03-APR-09:09 1302.65 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 183.74 01-APR-17:02 842.47 10-APR-21:03
May 827.22 01-MAY-09:09 1302.65 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 3.71 05-MAY-16:00 588.85 22-MAY-24:00
June 827.22 01-JUN-09:09 1302.65 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 14.12 28-JUN-16:00 767.82 13-JUN-03:00
July 827.22 03-JUL-09:09 1302.65 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 183.39 23-JUL-16:00 396.66 02-JUL-10:00
August 827.22 01-AUG-09:09 1302.65 01-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 93.47 13-AUG-17:30 578.89 11-AUG-04:00
September 827.22 01-SEP-09:09 1302.65 01-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 4.88 14-SEP-17:00 359.49 18-SEP-23:00
October 827.22 02-OCT-09:09 1302.65 02-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 776.90 31-OCT-21:03
November 827.22 01-NOV-09:09 1302.65 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 844.61 29-NOV-22:03
December 827.22 01-DEC-10:09 1302.65 01-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 698.01 22-DEC-22:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   1302.65   908.57   0.00 0.00 0.00 0.00 0.00   359.49  
Maximum of Months 827.22   1302.65   908.57   0.00 0.00 0.00 0.00 183.74   898.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 2057.62 02-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1349.09 12-JAN-22:03
February 1306.65 01-FEB-10:09 2057.62 01-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1270.13 16-FEB-22:03
March 1306.65 01-MAR-10:09 2057.62 01-MAR-08:09 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1156.38 28-MAR-24:00
April 1306.65 03-APR-09:09 2057.62 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 199.07 01-APR-17:30 1267.16 10-APR-21:03
May 1306.65 01-MAY-09:09 2057.62 01-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 5.56 05-MAY-16:00 889.08 22-MAY-24:00
June 1306.65 01-JUN-09:09 2057.62 01-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 21.17 28-JUN-16:00 1150.63 13-JUN-03:00
July 1306.65 03-JUL-09:09 2057.62 03-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 247.64 23-JUL-16:00 582.23 02-JUL-04:00
August 1306.65 01-AUG-09:09 2057.62 01-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 120.06 13-AUG-17:30 879.66 11-AUG-04:00
September 1306.65 01-SEP-09:09 2057.62 01-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 6.64 14-SEP-17:00 546.66 18-SEP-23:00
October 1306.65 02-OCT-09:09 2057.62 02-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1166.33 31-OCT-21:03
November 1306.65 01-NOV-09:09 2057.62 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1267.90 29-NOV-22:03
December 1306.65 01-DEC-10:09 2057.62 01-DEC-08:09 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1048.85 22-DEC-22:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   2057.62   1435.24   0.00 0.00 0.00 0.00 0.00   546.66  
Maximum of Months 1306.65   2057.62   1435.24   0.00 0.00 0.00 0.00 247.64   1349.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 1302.56 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 897.84 12-JAN-22:03
February 827.17 01-FEB-10:09 1302.56 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 845.47 16-FEB-22:03
March 827.17 01-MAR-10:09 1302.56 01-MAR-08:09 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 742.89 28-MAR-24:00
April 827.17 03-APR-09:09 1302.56 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 74.51 01-APR-17:30 844.97 10-APR-21:03
May 827.17 01-MAY-09:09 1302.56 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 6.67 06-MAY-13:00 589.04 22-MAY-24:00
June 827.17 01-JUN-09:09 1302.56 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 14.12 28-JUN-16:00 756.04 13-JUN-03:00
July 827.17 03-JUL-09:09 1302.56 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 157.20 23-JUL-14:00 389.08 02-JUL-04:00
August 827.17 01-AUG-09:09 1302.56 01-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 104.81 13-AUG-12:10 593.75 11-AUG-04:00
September 827.17 01-SEP-09:09 1302.56 01-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 4.42 14-SEP-17:00 359.44 18-SEP-23:00
October 827.17 02-OCT-09:09 1302.56 02-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 776.21 31-OCT-21:03
November 827.17 01-NOV-09:09 1302.56 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 844.35 29-NOV-22:03
December 827.17 01-DEC-10:09 1302.56 01-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 698.17 22-DEC-22:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   1302.56   908.57   0.00 0.00 0.00 0.00 0.00   359.44  
Maximum of Months 827.17   1302.56   908.57   0.00 0.00 0.00 0.00 157.20   897.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 2057.62 02-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 757.67 12-JAN-24:00
February 1306.65 01-FEB-10:09 2057.62 01-FEB-08:09 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 689.96 16-FEB-04:00
March 1306.65 01-MAR-10:09 2057.62 01-MAR-08:09 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 632.65 28-MAR-24:00
April 1306.65 03-APR-09:09 2057.62 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 168.83 01-APR-17:02 676.35 10-APR-21:03
May 1306.65 01-MAY-09:09 2057.62 01-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 22.60 14-MAY-15:50 515.07 18-MAY-05:00
June 1306.65 01-JUN-09:09 2057.62 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 11.54 28-JUN-16:00 688.10 13-JUN-03:00
July 1306.65 03-JUL-09:09 2057.62 03-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 157.34 23-JUL-15:50 341.72 02-JUL-04:00
August 1306.65 01-AUG-09:09 2057.62 01-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 91.57 13-AUG-15:10 496.47 11-AUG-04:00
September 1306.65 01-SEP-09:09 2057.62 01-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 3.72 14-SEP-17:00 325.97 18-SEP-23:00
October 1306.65 02-OCT-09:09 2057.62 02-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 627.51 31-OCT-21:03
November 1306.65 01-NOV-09:09 2057.62 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 732.02 29-NOV-23:00
December 1306.65 01-DEC-10:09 2057.62 01-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 575.09 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   2057.62   1435.25   0.00 0.00 0.00 0.00 0.00   325.97  
Maximum of Months 1306.65   2057.62   1435.25   0.00 0.00 0.00 0.00 168.83   757.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 1302.65 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 501.44 12-JAN-24:00
February 827.22 01-FEB-10:09 1302.65 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 456.54 16-FEB-04:00
March 827.22 01-MAR-10:09 1302.65 01-MAR-08:09 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 436.27 28-MAR-24:00
April 827.22 03-APR-09:09 1302.65 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 110.00 01-APR-17:02 465.73 07-APR-24:00
May 827.22 01-MAY-09:09 1302.65 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 2.47 06-MAY-15:00 339.22 18-MAY-05:00
June 827.22 01-JUN-09:09 1302.65 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 7.69 28-JUN-16:00 466.92 13-JUN-03:00
July 827.22 03-JUL-09:09 1302.65 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 94.01 23-JUL-16:10 225.73 02-JUL-04:00
August 827.22 01-AUG-09:09 1302.65 01-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 51.79 13-AUG-15:10 344.15 11-AUG-04:00
September 827.22 01-SEP-09:09 1302.65 01-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 2.48 14-SEP-17:00 212.84 18-SEP-23:00
October 827.22 02-OCT-09:09 1302.65 02-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 417.74 31-OCT-21:03
November 827.22 01-NOV-09:09 1302.65 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 484.83 29-NOV-23:00
December 827.22 01-DEC-10:09 1302.65 01-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 381.60 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   1302.65   908.57   0.00 0.00 0.00 0.00 0.00   212.84  
Maximum of Months 827.22   1302.65   908.57   0.00 0.00 0.00 0.00 110.00   501.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 2057.62 02-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 19187.29 06-JAN-07:01
February 1306.65 01-FEB-10:09 2057.62 01-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 17681.20 09-FEB-07:01
March 1306.65 01-MAR-10:09 2057.62 01-MAR-08:09 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 17266.13 01-MAR-07:01
April 1306.65 03-APR-09:09 2057.62 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 2399.67 27-APR-16:10 14905.50 19-APR-06:02
May 1306.65 01-MAY-09:09 2057.62 01-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 509.46 05-MAY-16:10 11914.07 18-MAY-06:03
June 1306.65 01-JUN-09:09 2057.62 01-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 2158.27 28-JUN-17:00 9124.76 01-JUN-06:10
July 1306.65 03-JUL-09:09 2057.62 03-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 3822.96 31-JUL-16:10 7636.94 03-JUL-06:05
August 1306.65 01-AUG-09:09 2057.62 01-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 6068.92 10-AUG-17:00 8435.16 01-AUG-06:03
September 1306.65 01-SEP-09:09 2057.62 01-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 804.65 14-SEP-17:00 9824.12 27-SEP-06:03
October 1306.65 02-OCT-09:09 2057.62 02-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 11751.50 13-OCT-07:00
November 1306.65 01-NOV-09:09 2057.62 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 16166.86 24-NOV-07:01
December 1306.65 01-DEC-10:09 2057.62 01-DEC-08:09 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 18648.13 26-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   2057.62   1435.24   0.00 0.00 0.00 0.00 0.00   7636.94  
Maximum of Months 1306.65   2057.62   1435.24   0.00 0.00 0.00 0.00 6068.92   19187.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 1302.56 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 500.43 12-JAN-24:00
February 827.17 01-FEB-10:09 1302.56 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 454.28 16-FEB-04:00
March 827.17 01-MAR-10:09 1302.56 01-MAR-08:09 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 427.73 28-MAR-24:00
April 827.17 03-APR-09:09 1302.56 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 57.06 01-APR-17:02 452.28 10-APR-21:03
May 827.17 01-MAY-09:09 1302.56 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 4.83 06-MAY-13:00 338.37 18-MAY-05:00
June 827.17 01-JUN-09:09 1302.56 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 7.69 28-JUN-16:00 446.60 13-JUN-03:00
July 827.17 03-JUL-09:09 1302.56 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 81.88 23-JUL-13:50 234.66 02-JUL-04:00
August 827.17 01-AUG-09:09 1302.56 01-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 48.80 13-AUG-12:30 355.78 11-AUG-04:00
September 827.17 01-SEP-09:09 1302.56 01-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 2.48 14-SEP-17:00 216.23 30-SEP-05:00
October 827.17 02-OCT-09:09 1302.56 02-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 417.70 31-OCT-21:03
November 827.17 01-NOV-09:09 1302.56 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 483.23 29-NOV-23:00
December 827.17 01-DEC-10:09 1302.56 01-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 382.19 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   1302.56   908.57   0.00 0.00 0.00 0.00 0.00   216.23  
Maximum of Months 827.17   1302.56   908.57   0.00 0.00 0.00 0.00 81.88   500.43  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 2057.62 02-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1176.05 12-JAN-24:00
February 1306.65 01-FEB-10:09 2057.62 01-FEB-08:09 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1074.94 16-FEB-04:00
March 1306.65 01-MAR-10:09 2057.62 01-MAR-08:09 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1019.99 28-MAR-24:00
April 1306.65 03-APR-09:09 2057.62 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 226.62 01-APR-17:02 1083.88 07-APR-24:00
May 1306.65 01-MAY-09:09 2057.62 01-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 10.92 14-MAY-15:20 802.90 18-MAY-05:00
June 1306.65 01-JUN-09:09 2057.62 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 17.85 28-JUN-16:00 1074.71 13-JUN-03:00
July 1306.65 03-JUL-09:09 2057.62 03-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 227.17 23-JUL-16:00 535.10 02-JUL-04:00
August 1306.65 01-AUG-09:09 2057.62 01-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 130.63 13-AUG-15:10 778.02 11-AUG-04:00
September 1306.65 01-SEP-09:09 2057.62 01-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 5.67 14-SEP-17:00 505.49 18-SEP-23:00
October 1306.65 02-OCT-09:09 2057.62 02-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 981.01 31-OCT-21:03
November 1306.65 01-NOV-09:09 2057.62 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1116.94 29-NOV-23:00
December 1306.65 01-DEC-10:09 2057.62 01-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 892.92 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   2057.62   1435.25   0.00 0.00 0.00 0.00 0.00   505.49  
Maximum of Months 1306.65   2057.62   1435.25   0.00 0.00 0.00 0.00 227.17   1176.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 805.43 02-JAN-08:09 1302.65 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 777.62 12-JAN-24:00
February 805.43 01-FEB-08:09 1302.65 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 710.34 16-FEB-04:00
March 805.43 01-MAR-08:09 1302.65 01-MAR-08:09 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 684.45 28-MAR-24:00
April 805.43 03-APR-07:10 1302.65 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 157.45 01-APR-17:02 725.08 07-APR-24:00
May 805.43 01-MAY-07:10 1302.65 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 14.05 14-MAY-16:00 527.85 18-MAY-05:00
June 805.43 01-JUN-07:10 1302.65 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 11.90 28-JUN-16:00 706.29 13-JUN-03:00
July 805.43 03-JUL-07:10 1302.65 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 161.02 23-JUL-15:40 354.85 02-JUL-10:00
August 805.43 01-AUG-07:10 1302.65 01-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 91.12 13-AUG-15:10 516.99 11-AUG-04:00
September 805.43 01-SEP-07:10 1302.65 01-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 4.68 14-SEP-17:00 329.24 18-SEP-23:00
October 805.43 02-OCT-07:10 1302.65 02-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 652.86 31-OCT-21:03
November 805.43 01-NOV-07:10 1302.65 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 739.01 29-NOV-23:00
December 805.43 01-DEC-08:09 1302.65 01-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 591.25 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 805.43   1302.65   908.57   0.00 0.00 0.00 0.00 0.00   329.24  
Maximum of Months 805.43   1302.65   908.57   0.00 0.00 0.00 0.00 161.02   777.62  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 2057.62 02-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1174.66 12-JAN-24:00
February 1306.65 01-FEB-10:09 2057.62 01-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1156.53 19-FEB-12:00
March 1306.65 01-MAR-10:09 2057.62 01-MAR-08:09 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1053.88 28-MAR-24:00
April 1306.65 03-APR-09:09 2057.62 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 165.86 01-APR-17:02 1094.66 07-APR-24:00
May 1306.65 01-MAY-09:09 2057.62 01-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 4.75 05-MAY-16:00 795.51 22-MAY-24:00
June 1306.65 01-JUN-09:09 2057.62 01-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 17.85 28-JUN-16:00 1061.92 13-JUN-03:00
July 1306.65 03-JUL-09:09 2057.62 03-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 191.79 23-JUL-16:00 537.75 02-JUL-04:00
August 1306.65 01-AUG-09:09 2057.62 01-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 106.02 13-AUG-17:50 785.82 11-AUG-04:00
September 1306.65 01-SEP-09:09 2057.62 01-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 5.67 14-SEP-17:00 501.66 30-SEP-05:00
October 1306.65 02-OCT-09:09 2057.62 02-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 979.93 31-OCT-21:03
November 1306.65 01-NOV-09:09 2057.62 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1114.67 29-NOV-23:00
December 1306.65 01-DEC-10:09 2057.62 01-DEC-08:09 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 897.84 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   2057.62   1435.24   0.00 0.00 0.00 0.00 0.00   501.66  
Maximum of Months 1306.65   2057.62   1435.24   0.00 0.00 0.00 0.00 191.79   1174.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 1302.56 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 774.78 12-JAN-24:00
February 827.17 01-FEB-10:09 1302.56 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 708.05 16-FEB-22:03
March 827.17 01-MAR-10:09 1302.56 01-MAR-08:09 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 678.65 28-MAR-24:00
April 827.17 03-APR-09:09 1302.56 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 53.28 01-APR-17:50 711.31 07-APR-24:00
May 827.17 01-MAY-09:09 1302.56 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 5.47 06-MAY-13:00 527.17 22-MAY-24:00
June 827.17 01-JUN-09:09 1302.56 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 11.90 28-JUN-16:00 698.30 13-JUN-03:00
July 827.17 03-JUL-09:09 1302.56 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 137.84 23-JUL-13:52 358.91 02-JUL-04:00
August 827.17 01-AUG-09:09 1302.56 01-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 83.00 13-AUG-12:30 530.03 11-AUG-04:00
September 827.17 01-SEP-09:09 1302.56 01-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 3.78 14-SEP-17:00 330.05 30-SEP-05:00
October 827.17 02-OCT-09:09 1302.56 02-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 652.00 31-OCT-21:03
November 827.17 01-NOV-09:09 1302.56 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 736.18 29-NOV-23:00
December 827.17 01-DEC-10:09 1302.56 01-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 592.34 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   1302.56   908.57   0.00 0.00 0.00 0.00 0.00   330.05  
Maximum of Months 827.17   1302.56   908.57   0.00 0.00 0.00 0.00 137.84   774.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1740.15 12-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1607.38 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1517.56 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 210.44 01-APR-17:02 1581.50 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.12 05-MAY-16:00 1186.75 18-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.65 28-JUN-15:00 1585.02 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 187.89 23-JUL-15:52 789.80 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.62 13-AUG-14:52 1112.26 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.89 14-SEP-17:00 733.51 30-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1380.31 31-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1637.33 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1314.85 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   733.51  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 210.44   1740.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2124.39 12-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1942.06 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1858.56 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 316.70 01-APR-17:02 1970.68 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.00 05-MAY-16:00 1453.36 18-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.33 28-JUN-15:00 1964.28 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 277.58 23-JUL-14:00 964.07 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.41 13-AUG-14:52 1402.10 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.41 14-SEP-17:00 891.33 30-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1679.77 31-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1981.71 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1608.84 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   891.33  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 316.70   2124.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1943.94 12-JAN-22:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1804.44 16-FEB-22:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1578.53 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 191.55 01-APR-17:02 1858.61 10-APR-21:03
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1284.15 17-MAY-21:03
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.63 28-JUN-17:00 1646.93 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.39 24-JUL-14:30 929.14 04-JUL-15:10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.02 08-AUG-17:00 1235.03 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 788.06 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1695.05 31-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1843.95 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1572.20 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   788.06  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 191.55   1943.94  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 13771.22 13-JAN-17:00 6035.01 9760.61 14257.50 0.00 0.00 0.00 0.00 0.00 0.00
February 16330.48 28-FEB-17:00 6035.01 9760.61 14257.50 0.00 0.00 0.00 0.00 0.00 0.00
March 18650.78 02-MAR-17:00 6035.01 9760.61 14257.50 0.00 0.00 0.00 0.00 0.00 0.00
April 27911.20 28-APR-05:13 1905.79 3253.54 23203.05 0.00 0.00 0.00 0.00 0.00 0.00
May 31428.87 08-MAY-05:13 1905.79 3253.54 23203.05 0.00 0.00 0.00 0.00 0.00 0.00
June 36156.75 12-JUN-06:03 3811.58 9760.61 31425.29 0.00 0.00 0.00 0.00 0.00 0.00
July 41089.90 25-JUL-06:03 5082.11 13014.15 41900.39 0.00 0.00 0.00 0.00 0.00 0.00
August 48702.19 25-AUG-05:12 2541.06 4338.05 30937.39 0.00 0.00 0.00 0.00 0.00 0.00
September 44586.95 14-SEP-05:12 2541.06 4338.05 30937.39 0.00 0.00 0.00 0.00 0.00 0.00
October 26706.27 10-OCT-05:13 1905.79 3253.54 23203.05 0.00 0.00 0.00 0.00 0.00 0.00
November 18225.29 06-NOV-17:00 6035.01 9760.61 14257.50 0.00 0.00 0.00 0.00 0.00 0.00
December 15651.01 06-DEC-15:50 6035.01 9760.61 14257.50 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 13771.22   1905.79 3253.54 14257.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 48702.19   6035.01 13014.15 41900.39 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 650.73 20-JAN-14:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.16
February 3755.99 27-FEB-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.03
March 5861.47 14-MAR-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.61
April 13125.64 27-APR-14:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.48
May 13717.98 04-MAY-14:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.45
June 14105.10 28-JUN-14:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.22
July 15437.24 24-JUL-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.18 0.00
August 15907.87 10-AUG-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.54 0.00
September 11736.94 14-SEP-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.24
October 7678.59 04-OCT-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.06
November 4429.48 04-NOV-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 736.72 05-DEC-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.63
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 650.73   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15907.87   0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.18 111.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3196.98 14-JAN-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 161.94
February 3230.48 11-FEB-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 129.41
March 3895.33 25-MAR-05:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 262.60
April 3467.90 08-APR-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 362.56
May 2838.51 06-MAY-06:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.43
June 3785.75 28-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.85 0.00
July 4483.60 31-JUL-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.78 0.00
August 5119.79 10-AUG-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.53 0.00
September 3821.74 14-SEP-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.53
October 2949.29 31-OCT-05:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 185.54
November 3012.96 22-NOV-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 217.73
December 3068.10 02-DEC-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70.89
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2838.51   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5119.79   0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.78 362.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3792.76 13-JAN-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 279.04
February 4206.74 10-FEB-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 125.29
March 4536.42 23-MAR-05:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.82
April 4364.45 18-APR-05:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 187.53
May 3541.88 08-MAY-06:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.09
June 4178.77 28-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.38 0.00
July 4892.56 24-JUL-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.37 0.00
August 5604.25 10-AUG-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.94 0.00
September 4617.70 14-SEP-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.05
October 3842.83 27-OCT-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 164.67
November 3504.55 09-NOV-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 151.45
December 3751.26 07-DEC-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 102.82
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3504.55   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5604.25   0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.37 279.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 7778.18 12-JAN-17:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 8996.37 28-FEB-17:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 10857.97 02-MAR-17:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 16492.01 27-APR-16:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 16693.43 05-MAY-16:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
June 18058.84 21-JUN-16:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
July 18711.43 24-JUL-16:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
August 25431.79 10-AUG-05:12 2541.06 4338.05 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
September 18275.82 14-SEP-16:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
October 15746.04 04-OCT-16:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 8877.61 03-NOV-16:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 8070.85 06-DEC-16:10 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 7778.18   2541.06 4338.05 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25431.79   6035.01 9760.61 12103.68 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 7709.42 11-JAN-17:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 8808.70 28-FEB-17:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 9456.81 02-MAR-16:50 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 18961.19 27-APR-15:30 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 19391.56 04-MAY-15:40 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
June 21192.71 28-JUN-15:50 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
July 22012.83 24-JUL-15:20 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
August 22853.27 10-AUG-15:30 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
September 19838.13 14-SEP-15:30 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
October 15534.73 04-OCT-16:00 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 8687.92 02-NOV-15:40 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 7881.00 05-DEC-15:50 6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 7709.42   6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22853.27   6035.01 9760.61 6808.32 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2180.81 11-JAN-15:00 1306.65 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 136.26
February 2685.47 27-FEB-16:20 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 18.27
March 2894.00 10-MAR-14:50 1306.65 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 65.54
April 5378.94 27-APR-15:20 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 28.75 0.00
May 5347.05 15-MAY-14:40 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 5.24
June 6173.63 21-JUN-15:40 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 6.08 0.00
July 7326.13 24-JUL-15:00 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 44.75 0.00
August 6877.05 09-AUG-15:30 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 53.26 0.00
September 5059.26 14-SEP-15:50 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 1.56 0.00
October 3287.92 04-OCT-15:40 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 29.63
November 2575.36 02-NOV-14:40 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 54.40
December 2042.22 30-DEC-17:02 334.80 571.56 2392.08 0.00 0.00 0.00 0.00 0.00 94.72
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2042.22   334.80 571.56 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7326.13   1306.65 2057.62 2392.08 0.00 0.00 0.00 0.00 53.26 136.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1719.69 28-JAN-17:02 211.95 361.85 1514.29 0.00 0.00 0.00 0.00 0.00 142.82
February 2233.37 27-FEB-15:50 805.43 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 10.38
March 2798.94 14-MAR-10:00 1654.44 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 45.98
April 6663.21 27-APR-09:30 827.22 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 22.74
May 6597.80 15-MAY-09:20 827.22 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 26.73
June 9487.63 25-JUN-09:12 211.95 361.85 1514.29 0.00 0.00 0.00 0.00 0.00 145.90
July 8767.71 24-JUL-09:00 805.43 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 0.70
August 11062.88 06-AUG-09:22 211.95 361.85 1514.29 0.00 0.00 0.00 0.00 0.00 188.18
September 7940.65 10-SEP-09:02 211.95 361.85 1514.29 0.00 0.00 0.00 0.00 0.00 129.61
October 4441.91 04-OCT-09:30 827.22 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 42.51
November 2182.21 02-NOV-10:40 1610.86 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 51.59
December 1728.26 30-DEC-17:02 211.95 361.85 1514.29 0.00 0.00 0.00 0.00 0.00 62.94
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1719.69   211.95 361.85 908.57 0.00 0.00 0.00 0.00 0.00 0.70
Maximum of Months 11062.88   1654.44 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 188.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7106.42 20-JAN-13:25 2544.47 4115.24 2870.47 0.00 0.00 0.00 0.00 0.00 31.52
February 9048.46 27-FEB-14:25 2613.31 4115.24 2870.47 0.00 0.00 0.00 0.00 0.00 29.25
March 10413.76 14-MAR-13:40 1306.65 2057.62 1435.24 0.00 0.00 0.00 0.00 0.00 42.75
April 12926.94 27-APR-13:10 2613.31 4115.24 2870.47 0.00 0.00 0.00 0.00 15.74 0.00
May 11052.60 04-MAY-13:40 1306.65 2057.62 1435.24 0.00 0.00 0.00 0.00 0.00 6.94
June 10301.88 28-JUN-13:05 2613.31 4115.24 2870.47 0.00 0.00 0.00 0.00 4.50 0.00
July 19265.47 30-JUL-12:02 334.80 571.56 2392.06 0.00 0.00 0.00 0.00 0.00 26.65
August 14505.91 29-AUG-12:30 1272.23 2057.62 1435.24 0.00 0.00 0.00 0.00 31.66 0.00
September 26152.46 10-SEP-13:42 401.76 685.87 2870.47 0.00 0.00 0.00 0.00 0.00 136.18
October 14093.29 04-OCT-13:07 3919.96 6172.87 4305.71 0.00 0.00 0.00 0.00 0.00 31.35
November 8730.31 04-NOV-13:25 275.09 685.87 1116.30 0.00 0.00 0.00 0.00 0.00 0.00
December 6791.74 05-DEC-12:25 1375.43 4115.24 2551.53 0.00 0.00 0.00 0.00 0.00 84.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6791.74   275.09 571.56 1116.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26152.46   3919.96 6172.87 4305.71 0.00 0.00 0.00 0.00 31.66 136.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2309.60 05-JAN-15:50 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 74.08
February 3726.07 27-FEB-15:30 1610.75 2605.12 1817.13 0.00 0.00 0.00 0.00 0.00 17.28
March 5521.03 14-MAR-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 22.21
April 8683.63 26-APR-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 1.63 0.00
May 12907.02 07-MAY-16:42 211.94 361.82 1514.28 0.00 0.00 0.00 0.00 0.00 130.47
June 18130.66 18-JUN-16:52 254.33 434.19 1817.13 0.00 0.00 0.00 0.00 0.00 313.24
July 18504.66 30-JUL-16:42 254.33 434.19 1817.13 0.00 0.00 0.00 0.00 0.00 7.49
August 13523.43 12-AUG-17:05 254.33 434.19 1817.13 0.00 0.00 0.00 0.00 0.00 90.43
September 18312.43 10-SEP-16:22 254.33 434.19 1817.13 0.00 0.00 0.00 0.00 0.00 77.58
October 6856.70 04-OCT-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 23.15
November 2979.08 04-NOV-15:40 84.78 217.09 353.33 0.00 0.00 0.00 0.00 0.00 3.07
December 2463.96 05-DEC-15:30 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 62.65
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2309.60   84.78 217.09 353.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18504.66   1610.75 2605.12 1817.13 0.00 0.00 0.00 0.00 1.63 313.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1691.71 11-JAN-15:00 1306.65 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 73.86
February 1972.82 28-FEB-15:00 1306.65 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
March 2073.61 10-MAR-14:40 1306.65 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 33.70
April 2821.08 27-APR-16:00 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 15.54 0.00
May 3468.39 05-MAY-15:30 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 2.39 0.00
June 4287.48 21-JUN-15:40 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 3.46 0.00
July 5201.72 24-JUL-15:00 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 23.98 0.00
August 5167.72 09-AUG-15:30 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 28.63 0.00
September 3821.73 14-SEP-15:50 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.99 0.00
October 2463.23 04-OCT-15:40 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 15.36
November 2069.29 02-NOV-14:02 5088.93 8230.49 5740.99 0.00 0.00 0.00 0.00 0.00 30.87
December 1675.67 29-DEC-13:50 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 77.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1675.67   1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5201.72   5088.93 8230.49 5740.99 0.00 0.00 0.00 0.00 28.63 77.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1460.96 28-JAN-17:02 211.95 361.85 1514.29 0.00 0.00 0.00 0.00 0.00 76.19
February 1782.72 27-FEB-15:50 805.43 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 4.87
March 2144.89 14-MAR-10:05 1610.86 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 18.89
April 4806.26 27-APR-09:30 827.22 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 11.98
May 5241.66 15-MAY-09:40 827.22 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 13.56
June 5979.20 28-JUN-09:30 827.22 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 8.46
July 7119.80 24-JUL-09:10 1654.44 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 0.04
August 7360.49 10-AUG-09:10 1654.44 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 2.42
September 5675.97 14-SEP-09:30 827.22 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 10.51
October 3763.45 04-OCT-09:30 827.22 1302.65 908.57 0.00 0.00 0.00 0.00 0.00 22.45
November 1949.45 02-NOV-10:40 1610.86 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 28.60
December 1653.11 05-DEC-10:20 2481.66 3907.94 2725.72 0.00 0.00 0.00 0.00 0.00 44.91
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1460.96   211.95 361.85 908.57 0.00 0.00 0.00 0.00 0.00 0.04
Maximum of Months 7360.49   2481.66 3907.94 2725.72 0.00 0.00 0.00 0.00 0.00 76.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3283.66 20-JAN-13:50 1272.23 2057.62 1435.24 0.00 0.00 0.00 0.00 0.00 1880.20
February 5373.64 27-FEB-15:00 1306.65 2057.62 1435.24 0.00 0.00 0.00 0.00 0.00 438.25
March 5004.86 01-MAR-14:40 1306.65 2057.62 1435.24 0.00 0.00 0.00 0.00 0.00 1261.89
April 9564.99 27-APR-13:40 1306.65 2057.62 1435.24 0.00 0.00 0.00 0.00 225.85 0.00
May 7963.84 14-MAY-14:30 401.76 685.87 2870.47 0.00 0.00 0.00 0.00 0.00 131.66
June 7511.07 28-JUN-13:40 1306.65 2057.62 1435.24 0.00 0.00 0.00 0.00 87.87 0.00
July 11042.92 31-JUL-16:10 401.76 1143.12 797.35 0.00 0.00 0.00 0.00 3822.96 0.00
August 13683.62 10-AUG-16:10 401.76 1143.12 797.35 0.00 0.00 0.00 0.00 5689.70 0.00
September 11508.57 14-SEP-13:50 1306.65 2057.62 1435.24 0.00 0.00 0.00 0.00 0.00 30.73
October 11766.94 04-OCT-13:30 1306.65 2057.62 1435.24 0.00 0.00 0.00 0.00 0.00 347.80
November 6567.90 04-NOV-13:40 137.54 342.94 558.15 0.00 0.00 0.00 0.00 0.00 0.00
December 4178.87 05-DEC-12:00 1272.23 2057.62 1435.24 0.00 0.00 0.00 0.00 0.00 1586.90
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3283.66   137.54 342.94 558.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13683.62   1306.65 2057.62 2870.47 0.00 0.00 0.00 0.00 5689.70 1880.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1884.76 05-JAN-15:50 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 39.11
February 2555.69 27-FEB-15:50 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 8.53
March 2894.98 02-MAR-16:30 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 13.63
April 5570.97 26-APR-17:00 254.33 723.64 504.76 0.00 0.00 0.00 0.00 1.48 0.00
May 11295.02 14-MAY-17:42 0.00 361.82 1222.09 0.00 0.00 0.00 0.00 0.00 66.32
June 6786.82 28-JUN-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 7.69 0.00
July 14769.34 23-JUL-18:01 0.00 506.55 1710.93 0.00 0.00 0.00 0.00 0.00 16.00
August 15409.08 06-AUG-18:02 0.00 434.19 1466.51 0.00 0.00 0.00 0.00 0.00 56.31
September 7034.65 11-SEP-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 1.45
October 5909.90 04-OCT-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 12.10
November 2483.38 04-NOV-15:40 84.78 217.09 353.33 0.00 0.00 0.00 0.00 0.00 1.65
December 2110.17 05-DEC-15:30 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 33.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1884.76   0.00 217.09 353.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15409.08   805.38 1302.56 1710.93 0.00 0.00 0.00 0.00 7.69 66.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1894.75 11-JAN-16:00 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 87.50
February 2281.90 28-FEB-15:00 1306.65 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
March 2404.45 10-MAR-14:40 1306.65 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 60.20
April 4858.32 27-APR-16:00 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 24.13 0.00
May 5102.72 05-MAY-15:30 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 3.61 0.00
June 5641.99 21-JUN-15:40 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 5.24 0.00
July 6561.43 24-JUL-15:00 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 37.40 0.00
August 6244.59 09-AUG-15:30 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 44.58 0.00
September 4783.36 14-SEP-15:50 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 1.43 0.00
October 3113.27 04-OCT-15:30 1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 25.70
November 2218.47 02-NOV-14:30 2544.47 4115.24 2870.49 0.00 0.00 0.00 0.00 0.00 49.43
December 1805.86 29-DEC-14:10 2613.31 4115.24 2870.49 0.00 0.00 0.00 0.00 0.00 118.63
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1805.86   1272.23 2057.62 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6561.43   2613.31 4115.24 2870.49 0.00 0.00 0.00 0.00 44.58 118.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2405.13 20-JAN-11:03 2416.29 3907.94 2725.72 0.00 0.00 0.00 0.00 0.00 38.49
February 3324.81 27-FEB-15:02 3221.71 5210.58 3634.29 0.00 0.00 0.00 0.00 0.00 13.73
March 5034.32 02-MAR-13:02 4832.57 7815.87 5451.44 0.00 0.00 0.00 0.00 0.00 33.30
April 7649.11 27-APR-10:05 1610.86 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 14.95
May 8698.76 14-MAY-09:42 211.95 361.85 1514.29 0.00 0.00 0.00 0.00 0.00 189.30
June 8220.17 28-JUN-10:05 1610.86 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 9.68
July 9956.11 30-JUL-09:02 169.56 289.48 1211.43 0.00 0.00 0.00 0.00 0.00 80.53
August 14237.59 06-AUG-09:22 211.95 361.85 1514.29 0.00 0.00 0.00 0.00 0.00 157.74
September 11244.80 10-SEP-09:52 211.95 361.85 1514.29 0.00 0.00 0.00 0.00 0.00 73.81
October 5953.69 04-OCT-10:05 1610.86 2605.29 1817.15 0.00 0.00 0.00 0.00 0.00 29.12
November 3490.41 04-NOV-10:02 1017.38 1736.86 2019.05 0.00 0.00 0.00 0.00 0.00 21.48
December 2568.94 05-DEC-11:02 3221.71 5210.58 3634.29 0.00 0.00 0.00 0.00 0.00 42.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2405.13   169.56 289.48 1211.43 0.00 0.00 0.00 0.00 0.00 9.68
Maximum of Months 14237.59   4832.57 7815.87 5451.44 0.00 0.00 0.00 0.00 0.00 189.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7917.54 20-JAN-13:13 3816.70 6172.87 4305.71 0.00 0.00 0.00 0.00 0.00 17.47
February 9384.35 27-FEB-14:25 2613.31 4115.24 2870.47 0.00 0.00 0.00 0.00 0.00 24.22
March 10633.57 01-MAR-13:40 1272.23 2057.62 1435.24 0.00 0.00 0.00 0.00 0.00 57.08
April 12338.55 27-APR-13:10 2613.31 4115.24 2870.47 0.00 0.00 0.00 0.00 13.27 0.00
May 10580.58 14-MAY-12:32 334.80 571.56 2392.06 0.00 0.00 0.00 0.00 0.00 272.11
June 9630.24 28-JUN-13:05 2613.31 4115.24 2870.47 0.00 0.00 0.00 0.00 3.96 0.00
July 12227.53 31-JUL-13:10 2613.31 4115.24 2870.47 0.00 0.00 0.00 0.00 25.17 0.00
August 16624.11 06-AUG-13:22 334.80 571.56 2392.06 0.00 0.00 0.00 0.00 0.00 127.01
September 15033.07 10-SEP-13:13 267.84 457.25 1913.65 0.00 0.00 0.00 0.00 0.00 129.11
October 14230.55 04-OCT-13:10 3919.96 6172.87 4305.71 0.00 0.00 0.00 0.00 0.00 25.91
November 9091.38 04-NOV-13:25 275.09 685.87 1116.30 0.00 0.00 0.00 0.00 0.00 0.00
December 8087.54 05-DEC-12:25 1375.43 4115.24 2551.53 0.00 0.00 0.00 0.00 0.00 69.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7917.54   267.84 457.25 1116.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16624.11   3919.96 6172.87 4305.71 0.00 0.00 0.00 0.00 25.17 272.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2295.23 05-JAN-15:50 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 63.34
February 3727.10 27-FEB-15:30 1610.75 2605.12 1817.13 0.00 0.00 0.00 0.00 0.00 14.30
March 5353.31 14-MAR-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 18.42
April 8306.29 26-APR-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 1.46 0.00
May 17707.41 07-MAY-16:32 254.33 434.19 1817.13 0.00 0.00 0.00 0.00 0.00 119.44
June 8953.79 28-JUN-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 11.90 0.00
July 15262.58 23-JUL-16:52 211.94 361.82 1514.28 0.00 0.00 0.00 0.00 0.00 11.61
August 17792.59 06-AUG-16:42 254.33 434.19 1817.13 0.00 0.00 0.00 0.00 0.00 100.49
September 8837.44 11-SEP-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 2.36
October 6893.39 04-OCT-16:00 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 19.11
November 2857.90 04-NOV-15:40 84.78 217.09 353.33 0.00 0.00 0.00 0.00 0.00 2.78
December 2471.86 05-DEC-15:30 805.38 1302.56 908.57 0.00 0.00 0.00 0.00 0.00 54.04
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2295.23   84.78 217.09 353.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17792.59   1610.75 2605.12 1817.13 0.00 0.00 0.00 0.00 11.90 119.44



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.152541E+12 120418.54 13-JAN-16:49 0.927193E+11 266214.58 02-JAN-06:19
February 0.135832E+12 118594.50 27-FEB-15:09 0.579542E+11 211061.21 21-FEB-07:10
March 0.154153E+12 115247.47 14-MAR-15:00 0.330253E+11 170563.31 06-MAR-07:10
April 0.143144E+12 161964.25 27-APR-15:09 0.140645E+11 128358.63 18-APR-06:10
May 0.154196E+12 154927.99 15-MAY-15:00 0.481119E+10 98913.18 18-MAY-06:10
June 0.158229E+12 164652.20 28-JUN-15:30 0.155332E+10 63530.45 14-JUN-06:10
July 0.167565E+12 182574.37 24-JUL-15:09 0.456189E+09 17544.71 03-JUL-06:10
August 0.188361E+12 192087.47 10-AUG-15:50 0.525823E+09 34030.23 18-AUG-06:10
September 0.155967E+12 167382.36 14-SEP-15:20 0.293407E+10 89001.44 28-SEP-06:10
October 0.150429E+12 140471.84 04-OCT-15:09 0.168494E+11 127905.21 16-OCT-06:10
November 0.147516E+12 120828.45 06-NOV-16:00 0.452511E+11 183291.16 13-NOV-07:10
December 0.149637E+12 120622.29 06-DEC-16:30 0.740084E+11 226065.47 26-DEC-07:19
             
Annual Sum or Average 0.185757E+13     0.344153E+12    
Minimum of Months 0.135832E+12 115247.47   0.456189E+09 17544.71  
Maximum of Months 0.188361E+12 192087.47   0.927193E+11 266214.58  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.472479E+11 0.256004E+11 0.613996E+11 0.230900E+10 0.107071E+11 0.445445E+09 0.00 535375.77 0.00 0.00 0.00 0.483069E+10 0.00
February 0.428574E+11 0.211055E+11 0.556056E+11 0.209511E+10 0.923941E+10 0.276155E+09 0.00 0.240826E+09 0.00 0.00 0.00 0.441236E+10 0.00
March 0.509265E+11 0.206010E+11 0.635880E+11 0.240664E+10 0.108981E+11 0.158647E+09 0.00 0.425743E+09 0.00 0.00 0.00 0.514817E+10 0.00
April 0.454877E+11 0.171600E+11 0.594055E+11 0.224272E+10 0.110017E+11 76347668.91 0.00 0.324321E+10 0.00 0.00 0.00 0.452717E+10 0.00
May 0.490872E+11 0.152413E+11 0.624938E+11 0.235782E+10 0.133396E+11 38069096.06 0.00 0.696045E+10 0.00 0.00 0.00 0.467785E+10 0.00
June 0.488499E+11 0.134127E+11 0.612808E+11 0.231841E+10 0.151138E+11 21927786.02 0.00 0.127541E+11 0.00 0.00 0.00 0.447743E+10 0.00
July 0.457251E+11 0.144757E+11 0.606074E+11 0.228147E+10 0.171112E+11 14494592.86 0.00 0.232214E+11 0.00 0.00 0.00 0.412871E+10 0.00
August 0.509265E+11 0.166196E+11 0.635880E+11 0.240664E+10 0.193134E+11 15420323.55 0.00 0.309845E+11 0.00 0.00 0.00 0.450676E+10 0.00
September 0.454877E+11 0.187274E+11 0.593832E+11 0.224140E+10 0.141810E+11 26167162.87 0.00 0.117963E+11 0.00 0.00 0.00 0.412374E+10 0.00
October 0.472479E+11 0.222225E+11 0.614108E+11 0.230966E+10 0.111592E+11 86165155.59 0.00 0.160632E+10 0.00 0.00 0.00 0.438697E+10 0.00
November 0.466941E+11 0.240240E+11 0.599069E+11 0.224962E+10 0.956867E+10 0.213615E+09 0.00 0.385422E+09 0.00 0.00 0.00 0.447388E+10 0.00
December 0.457251E+11 0.262580E+11 0.605962E+11 0.228081E+10 0.983230E+10 0.352112E+09 0.00 275137.45 0.00 0.00 0.00 0.459241E+10 0.00
                           
Annual Sum or Average 0.566263E+12 0.235448E+12 0.729266E+12 0.274993E+11 0.151466E+12 0.172457E+10 0.00 0.916191E+11 0.00 0.00 0.00 0.542861E+11 0.00
Minimum of Months 0.428574E+11 0.134127E+11 0.556056E+11 0.209511E+10 0.923941E+10 14494592.86 0.00 275137.45 0.00 0.00 0.00 0.412374E+10 0.00
Maximum of Months 0.509265E+11 0.262580E+11 0.635880E+11 0.240664E+10 0.193134E+11 0.445445E+09 0.00 0.309845E+11 0.00 0.00 0.00 0.514817E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.927193E+11 0.00 0.00 0.00 0.00
February 0.00 0.00 0.579542E+11 0.00 0.00 0.00 0.00
March 0.00 0.00 0.330253E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.140645E+11 0.00 0.00 0.00 0.00
May 0.00 0.00 0.481119E+10 0.00 0.00 0.00 0.00
June 0.00 0.00 0.155332E+10 0.00 0.00 0.00 0.00
July 0.00 0.00 0.456189E+09 0.00 0.00 0.00 0.00
August 0.00 0.00 0.525823E+09 0.00 0.00 0.00 0.00
September 0.00 0.00 0.293407E+10 0.00 0.00 0.00 0.00
October 0.00 0.00 0.168494E+11 0.00 0.00 0.00 0.00
November 0.00 0.00 0.452511E+11 0.00 0.00 0.00 0.00
December 0.00 0.00 0.740084E+11 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.344153E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.456189E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.927193E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 49443.18 02-JAN-08:09 15013.15 01-JAN-00:10 41937.01 02-JAN-08:09 1410.29 03-JAN-08:09 16174.82 02-JAN-06:30 893.29 02-JAN-06:00 0.00 01-JAN-00:10
February 49443.18 01-FEB-08:09 15013.15 01-FEB-00:10 41937.01 01-FEB-08:09 1410.29 02-FEB-08:09 14265.01 21-FEB-07:10 862.32 21-FEB-07:10 0.00 01-FEB-00:10
March 49443.18 01-MAR-08:09 15013.15 01-MAR-00:10 41937.01 01-MAR-08:09 1410.29 01-MAR-12:09 10299.57 02-MAR-15:30 771.01 06-MAR-07:10 0.00 01-MAR-00:10
April 49443.18 03-APR-07:10 15013.15 01-APR-00:10 41937.01 03-APR-07:10 1410.29 04-APR-16:10 22021.21 27-APR-14:30 581.58 18-APR-06:10 0.00 01-APR-00:10
May 49443.18 01-MAY-07:10 15013.15 01-MAY-00:10 41937.01 01-MAY-07:10 1410.29 10-MAY-16:10 21506.71 15-MAY-15:20 436.56 18-MAY-06:10 0.00 01-MAY-00:10
June 49443.18 01-JUN-07:10 15013.15 01-JUN-00:10 41937.01 01-JUN-07:10 1410.29 13-JUN-16:10 23808.09 28-JUN-15:30 315.17 14-JUN-06:10 0.00 01-JUN-00:10
July 49443.18 03-JUL-07:10 15013.15 01-JUL-00:10 41937.01 03-JUL-07:10 1410.29 01-JUL-10:20 27169.25 31-JUL-15:20 92.76 03-JUL-06:10 0.00 01-JUL-00:10
August 49443.18 01-AUG-07:10 15013.15 01-AUG-00:10 41937.01 01-AUG-07:10 1410.29 01-AUG-07:10 30475.76 10-AUG-15:30 183.64 18-AUG-06:10 0.00 01-AUG-00:10
September 49443.18 01-SEP-07:10 15013.15 01-SEP-00:10 41937.01 01-SEP-07:10 1410.29 01-SEP-07:10 25119.65 14-SEP-14:50 389.55 28-SEP-06:10 0.00 01-SEP-00:10
October 49443.18 02-OCT-07:10 15013.15 01-OCT-00:10 41937.01 02-OCT-07:10 1410.29 11-OCT-11:09 19587.20 04-OCT-14:00 591.10 16-OCT-06:10 0.00 01-OCT-00:10
November 49443.18 01-NOV-07:10 15013.15 01-NOV-00:10 41937.01 01-NOV-07:10 1410.29 02-NOV-11:09 10747.03 24-NOV-07:10 792.63 13-NOV-07:10 0.00 01-NOV-00:10
December 49443.18 01-DEC-08:09 15013.15 01-DEC-00:10 41937.01 01-DEC-08:09 1410.29 04-DEC-12:09 14562.84 26-DEC-07:10 878.87 26-DEC-07:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 49443.18   15013.15   41937.01   1410.29   10299.57   92.76   0.00  
Maximum of Months 49443.18   15013.15   41937.01   1410.29   30475.76   893.29   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 137.49 30-JAN-07:19 0.00 0.00 0.00 6491.58 31-JAN-12:50 0.00
February 12796.99 27-FEB-15:09 0.00 0.00 0.00 6518.00 13-FEB-12:30 0.00
March 11750.27 18-MAR-15:00 0.00 0.00 0.00 6437.96 01-MAR-12:30 0.00
April 42983.99 27-APR-14:00 0.00 0.00 0.00 6250.83 03-APR-11:39 0.00
May 37017.92 04-MAY-14:00 0.00 0.00 0.00 6180.23 10-MAY-11:50 0.00
June 43540.38 28-JUN-15:30 0.00 0.00 0.00 5815.83 01-JUN-11:30 0.00
July 59305.36 24-JUL-14:00 0.00 0.00 0.00 5767.44 03-JUL-11:00 0.00
August 64742.39 10-AUG-15:00 0.00 0.00 0.00 5660.72 25-AUG-11:39 0.00
September 45922.54 14-SEP-14:09 0.00 0.00 0.00 5776.64 29-SEP-11:39 0.00
October 24263.06 04-OCT-14:00 0.00 0.00 0.00 5828.94 31-OCT-11:20 0.00
November 18507.81 04-NOV-14:09 0.00 0.00 0.00 6210.47 29-NOV-12:50 0.00
December 139.71 17-DEC-21:10 0.00 0.00 0.00 6261.88 29-DEC-12:20 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 137.49   0.00 0.00 0.00 5660.72   0.00
Maximum of Months 64742.39   0.00 0.00 0.00 6518.00   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 120418.54 13-JAN-16:49 49443.18 41937.01 15013.15 1410.29 7443.89 188.85 0.00 0.00 0.00
February 118594.50 27-FEB-15:09 49443.18 41937.01 0.00 1410.29 9412.07 6.85 0.00 12796.99 0.00
March 115247.47 14-MAR-15:00 49443.18 41937.01 0.00 1410.29 10054.24 6.85 0.00 7415.11 0.00
April 161964.25 27-APR-15:09 49443.18 41937.01 0.00 1410.29 21719.45 6.85 0.00 42837.22 0.00
May 154927.99 15-MAY-15:00 49443.18 41937.01 0.00 1410.29 21124.59 6.85 0.00 36497.78 0.00
June 164652.20 28-JUN-15:30 49443.18 41937.01 0.00 1410.29 23808.09 6.85 0.00 43540.38 0.00
July 182574.37 24-JUL-15:09 49443.18 41937.01 0.00 1410.29 26943.64 6.93 0.00 58638.43 0.00
August 192087.47 10-AUG-15:50 49443.18 41937.01 0.00 1410.29 30391.31 6.93 0.00 64650.50 0.00
September 167382.36 14-SEP-15:20 49443.18 41937.01 0.00 1410.29 25089.42 6.90 0.00 45183.60 0.00
October 140471.84 04-OCT-15:09 49443.18 41937.01 0.00 1410.29 19510.06 6.85 0.00 23912.39 0.00
November 120828.45 06-NOV-16:00 49443.18 41937.01 15013.15 1410.29 8400.64 16.05 0.00 0.00 0.00
December 120622.29 06-DEC-16:30 49443.18 41937.01 15013.15 1410.29 7803.16 65.85 0.00 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 115247.47   49443.18 41937.01 0.00 1410.29 7443.89 6.85 0.00 0.00 0.00
Maximum of Months 192087.47   49443.18 41937.01 15013.15 1410.29 30391.31 188.85 0.00 64650.50 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 266214.58 02-JAN-06:19 0.00 0.00 0.00
February 0.00 0.00 211061.21 21-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 170563.31 06-MAR-07:10 0.00 0.00 0.00
April 0.00 0.00 128358.63 18-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 98913.18 18-MAY-06:10 0.00 0.00 0.00
June 0.00 0.00 63530.45 14-JUN-06:10 0.00 0.00 0.00
July 0.00 0.00 17544.71 03-JUL-06:10 0.00 0.00 0.00
August 0.00 0.00 34030.23 18-AUG-06:10 0.00 0.00 0.00
September 0.00 0.00 89001.44 28-SEP-06:10 0.00 0.00 0.00
October 0.00 0.00 127905.21 16-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 183291.16 13-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 226065.47 26-DEC-07:19 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 17544.71   0.00 0.00 0.00
Maximum of Months 0.00 0.00 266214.58   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 19.49 2.00 19.49 0.00 19.49 0.00 19.49
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.00 19.49 2.00 19.49 0.00 19.49 0.00 19.49
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 19.49 2.00 19.49 0.00 19.49 0.00 19.49



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.50 19.28 2.50 19.28 0.00 19.28 0.00 19.28
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.34 0.17 19.34 0.00 19.34 0.00 19.34
                 
Annual Sum or Average 2.67 19.28 2.67 19.28 0.00 19.28 0.00 19.28
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.50 19.34 2.50 19.34 0.00 19.34 0.00 19.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.33 19.11 3.00 19.23 0.00 19.23 0.00 19.23
February 0.67 19.37 0.67 19.37 0.00 19.37 0.00 19.37
March 0.17 19.38 0.17 19.38 0.00 19.38 0.00 19.38
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 19.37 0.50 19.37 0.00 19.37 0.00 19.37
December 1.00 18.92 0.83 19.08 0.00 19.08 0.00 19.08
                 
Annual Sum or Average 5.67 19.14 5.17 19.24 0.00 19.24 0.00 19.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.33 19.38 3.00 19.38 0.00 19.38 0.00 19.38



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 16.50 16.26 5.83 16.77 0.00 16.77 0.00 16.77
February 7.67 16.04 3.33 16.41 0.00 16.41 0.00 16.41
March 0.50 19.16 0.50 19.16 0.00 19.16 0.00 19.16
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.50 18.50 1.17 18.81 0.00 18.81 0.00 18.81
December 6.00 17.42 3.33 18.10 0.00 18.10 0.00 18.10
                 
Annual Sum or Average 32.17 16.57 14.17 17.12 0.00 17.12 0.00 17.12
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16.50 19.16 5.83 19.16 0.00 19.16 0.00 19.16



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 16.50 15.76 4.83 16.11 0.00 16.11 0.00 16.11
February 6.17 15.89 2.00 16.25 0.00 16.25 0.00 16.25
March 0.33 19.14 0.33 19.14 0.00 19.14 0.00 19.14
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.67 27.86 1.67 27.86
August 0.00 0.00 0.00 0.00 1.00 27.87 1.00 27.87
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.50 18.08 1.00 18.56 0.00 18.56 0.00 18.56
December 5.67 16.88 2.33 17.57 0.00 17.57 0.00 17.57
                 
Annual Sum or Average 30.17 16.15 10.50 16.63 2.67 17.32 2.67 17.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16.50 19.14 4.83 19.14 1.67 27.87 1.67 27.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.50 15.81 3.50 16.19 0.00 16.19 0.00 16.19
February 3.17 16.43 1.50 16.71 0.00 16.71 0.00 16.71
March 0.33 19.16 0.33 19.16 0.00 19.16 0.00 19.16
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 27.31 0.33 27.31
July 0.00 0.00 0.00 0.00 1.17 27.72 1.17 27.72
August 0.00 0.00 0.00 0.00 1.33 27.84 1.33 27.84
September 0.00 0.00 0.00 0.00 1.17 27.98 1.17 27.98
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.83 17.96 0.50 18.41 0.00 18.41 0.00 18.41
December 4.00 17.20 2.00 17.90 0.00 17.90 0.00 17.90
                 
Annual Sum or Average 20.83 16.31 7.83 16.81 4.00 18.15 4.00 19.21
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12.50 19.16 3.50 19.16 1.33 27.98 1.33 27.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 15.33 15.72 4.67 16.04 0.00 16.04 0.00 16.04
February 5.67 15.73 2.33 15.93 0.00 15.93 0.00 15.93
March 0.33 19.18 0.33 19.18 0.00 19.18 0.00 19.18
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.67 28.19 1.00 28.19
June 0.00 0.00 0.00 0.00 1.00 27.56 0.50 27.55
July 0.00 0.00 0.00 0.00 3.33 28.48 1.50 28.46
August 0.00 0.00 0.00 0.00 2.17 27.99 1.17 28.00
September 0.00 0.00 0.00 0.00 0.83 27.66 0.67 27.69
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.83 17.95 0.50 18.42 0.00 18.42 0.00 18.42
December 5.50 16.84 2.17 17.54 0.00 17.54 0.00 17.54
                 
Annual Sum or Average 27.67 16.06 10.00 16.46 9.00 18.71 4.83 19.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15.33 19.18 4.67 19.18 3.33 28.48 1.50 28.46



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.33 19.31 3.17 19.36 0.00 19.36 0.00 19.36
February 0.50 19.62 0.50 19.62 0.00 19.62 0.00 19.62
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.90 0.33 19.90 0.00 19.90 0.00 19.90
                 
Annual Sum or Average 4.17 19.39 4.00 19.44 0.00 19.44 0.00 19.44
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.33 19.90 3.17 19.90 0.00 19.90 0.00 19.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 19.33 2.17 19.41 0.00 19.41 0.00 19.41
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.67 27.39 0.67 27.39
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.33 19.33 2.17 19.41 0.67 20.44 0.67 21.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 19.33 2.17 19.41 0.67 27.39 0.67 27.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 65.83 18.61 65.83 18.61 0.00 18.61 0.00 18.61
February 37.83 18.63 37.83 18.63 0.00 18.63 0.00 18.63
March 30.50 19.09 30.50 19.09 0.00 19.09 0.00 19.09
April 17.33 19.18 17.33 19.18 0.00 19.18 0.00 19.18
May 9.50 19.91 9.50 19.91 0.00 19.91 0.00 19.91
June 0.50 20.36 0.50 20.36 0.00 20.36 0.00 20.36
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.50 27.41 0.50 27.41
September 2.00 19.99 2.00 19.99 1.00 21.53 1.00 22.55
October 14.00 19.89 14.00 19.89 0.00 19.89 0.00 19.89
November 37.33 19.25 37.33 19.25 0.00 19.25 0.00 19.25
December 56.00 18.77 56.00 18.77 0.00 18.77 0.00 18.77
                 
Annual Sum or Average 270.83 18.95 270.83 18.95 1.50 18.97 1.50 19.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 65.83 20.36 65.83 20.36 1.00 27.41 1.00 27.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.39 2.00 19.49 0.00 19.49 0.00 19.49
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 27.35 0.00 27.35
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.67 27.86 0.83 27.81
August 0.00 0.00 0.00 0.00 0.83 27.77 0.17 27.79
September 0.00 0.00 0.00 0.00 0.33 27.43 0.17 27.38
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.17 19.39 2.00 19.49 4.00 23.55 1.17 24.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.39 2.00 19.49 2.67 27.86 0.83 27.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.17 19.20 2.83 19.33 0.00 19.33 0.00 19.33
February 0.50 19.55 0.50 19.55 0.00 19.55 0.00 19.55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.83 19.16 0.67 19.40 0.00 19.40 0.00 19.40
                 
Annual Sum or Average 4.50 19.23 4.00 19.37 0.00 19.37 0.00 19.37
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.17 19.55 2.83 19.55 0.00 19.55 0.00 19.55



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.67 18.50 1.33 18.68 0.00 18.68 0.00 18.68
February 0.17 19.35 0.17 19.35 0.00 19.35 0.00 19.35
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 27.46 0.33 27.46
July 0.00 0.00 0.00 0.00 2.00 27.98 2.00 27.98
August 0.00 0.00 0.00 0.00 1.67 27.91 1.67 27.91
September 0.00 0.00 0.00 0.00 0.50 27.45 0.50 27.45
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 18.54 0.33 18.85 0.00 18.85 0.00 18.85
                 
Annual Sum or Average 2.33 18.57 1.83 18.77 4.50 23.49 4.50 24.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.67 19.35 1.33 19.35 2.00 27.98 2.00 27.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.67 19.24 1.50 19.37 0.00 19.37 0.00 19.37
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.27 0.17 27.27
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 27.64 1.00 27.64
August 0.00 0.00 0.00 0.00 1.17 27.77 1.17 27.77
September 0.00 0.00 0.00 0.00 1.33 27.96 1.33 27.96
October 0.00 0.00 0.00 0.00 0.33 27.33 0.33 27.33
November 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
December 0.50 18.57 0.33 18.88 0.00 18.88 0.00 18.88
                 
Annual Sum or Average 2.17 19.08 1.83 19.26 4.17 23.58 4.17 24.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.67 19.24 1.50 19.37 1.33 27.96 1.33 27.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.67 18.51 1.33 18.69 0.00 18.69 0.00 18.69
February 0.17 19.43 0.17 19.43 0.00 19.43 0.00 19.43
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.67 28.09 0.67 28.12
June 0.00 0.00 0.00 0.00 0.67 27.60 0.50 27.56
July 0.00 0.00 0.00 0.00 3.17 28.37 1.33 28.42
August 0.00 0.00 0.00 0.00 2.00 27.93 1.17 27.89
September 0.00 0.00 0.00 0.00 0.67 27.80 0.50 27.77
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 18.55 0.33 18.87 0.00 18.87 0.00 18.87
                 
Annual Sum or Average 2.33 18.59 1.83 18.79 8.17 24.95 4.17 25.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.67 19.43 1.33 19.43 3.17 28.37 1.33 28.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 496.67 22.84 32.67 22.64 32.67 22.47
February 402.17 23.45 0.00 23.45 0.00 23.45
March 319.83 23.76 6.17 23.79 0.00 23.79
April 141.67 23.74 76.33 24.21 0.00 24.21
May 12.00 23.86 205.00 24.80 0.00 24.80
June 0.00 0.00 279.67 24.75 0.00 24.75
July 0.00 0.00 425.33 24.61 0.00 24.61
August 0.00 0.00 473.00 24.45 0.00 24.45
September 0.00 0.00 353.17 24.65 0.00 24.65
October 78.50 23.61 90.33 24.58 0.00 24.58
November 283.33 23.64 30.50 23.78 0.00 23.78
December 470.33 23.44 0.00 23.44 0.00 23.44
             
Annual Sum or Average 2204.50 23.41 1972.17 23.97 32.67 23.94
Minimum of Months 0.00 0.00 0.00 22.64 0.00 22.47
Maximum of Months 496.67 23.86 473.00 24.80 32.67 24.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.41 113.00 21.15 113.00 20.97
February 451.17 22.02 41.67 21.87 41.67 21.75
March 505.67 22.82 1.17 22.81 1.17 22.81
April 375.67 23.12 25.00 23.21 0.00 23.21
May 221.83 23.36 53.67 23.56 0.00 23.56
June 104.83 23.45 130.17 23.98 0.00 23.98
July 25.83 23.50 268.33 24.33 0.00 24.33
August 46.00 23.39 341.33 24.18 0.00 24.18
September 119.83 23.28 159.50 23.92 0.00 23.92
October 375.17 22.99 0.50 22.99 0.00 22.99
November 474.00 22.39 2.67 22.38 2.67 22.37
December 497.00 21.82 29.33 21.73 29.33 21.65
             
Annual Sum or Average 3699.00 22.47 1166.33 22.76 187.83 22.66
Minimum of Months 25.83 21.41 0.50 21.15 0.00 20.97
Maximum of Months 505.67 23.50 341.33 24.33 113.00 24.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.59 240.83 20.31 240.83 20.17
February 454.00 21.07 155.00 20.79 155.00 20.62
March 514.00 21.84 66.17 21.65 66.17 21.51
April 416.00 22.39 26.67 22.37 13.83 22.31
May 319.33 22.85 40.00 22.99 0.00 22.99
June 195.17 23.14 99.33 23.51 0.00 23.51
July 119.83 23.21 224.17 23.88 0.00 23.88
August 133.50 23.12 265.17 23.82 0.00 23.82
September 286.83 22.87 88.17 23.17 0.00 23.17
October 469.33 22.14 23.00 22.05 23.00 21.98
November 489.00 21.33 97.83 21.10 97.83 20.93
December 497.00 20.82 201.33 20.57 201.33 20.44
             
Annual Sum or Average 4396.00 21.81 1527.67 21.85 798.00 21.62
Minimum of Months 119.83 20.59 23.00 20.31 0.00 20.17
Maximum of Months 514.00 23.21 265.17 23.88 240.83 23.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.96 406.50 19.85 406.50 19.81
February 454.00 20.24 287.17 20.05 287.17 19.96
March 514.00 20.78 200.50 20.57 200.50 20.46
April 466.67 21.47 91.33 21.32 81.50 21.17
May 407.00 21.97 60.67 22.01 26.83 21.90
June 308.17 22.44 85.67 22.77 2.00 22.76
July 219.83 22.59 187.67 23.28 0.00 23.28
August 243.00 22.43 196.33 23.18 0.00 23.18
September 393.83 21.98 51.50 22.18 4.17 22.16
October 502.00 21.12 104.33 20.90 104.33 20.76
November 489.00 20.40 255.33 20.19 255.33 20.09
December 497.00 20.07 395.33 19.97 395.33 19.93
             
Annual Sum or Average 4996.50 21.09 2322.33 21.02 1763.67 20.79
Minimum of Months 219.83 19.96 51.50 19.85 0.00 19.81
Maximum of Months 514.00 22.59 406.50 23.28 406.50 23.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.98 393.50 19.85 393.50 19.80
February 454.00 20.32 264.50 20.13 264.50 20.04
March 512.50 20.89 159.50 20.65 159.50 20.50
April 416.17 21.56 88.33 21.52 59.33 21.36
May 344.83 21.81 115.83 22.20 24.50 22.09
June 238.50 22.25 187.50 23.12 2.50 23.11
July 195.50 22.55 250.50 23.52 7.00 23.57
August 204.83 22.42 253.00 23.39 4.83 23.43
September 331.33 21.81 115.33 22.39 4.83 22.37
October 484.83 21.21 90.17 21.02 87.83 20.86
November 489.00 20.42 240.83 20.21 240.83 20.10
December 497.00 20.09 371.00 19.96 371.00 19.90
             
Annual Sum or Average 4670.50 21.03 2530.00 21.17 1620.17 20.92
Minimum of Months 195.50 19.98 88.33 19.85 2.50 19.80
Maximum of Months 512.50 22.55 393.50 23.52 393.50 23.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.50 20.18 337.17 19.98 336.33 19.89
February 423.83 20.65 222.00 20.46 212.83 20.32
March 457.33 21.00 170.00 20.86 146.67 20.68
April 373.83 21.40 131.00 21.58 68.00 21.41
May 350.33 21.71 131.33 22.16 29.67 22.05
June 293.17 22.09 139.00 22.77 3.83 22.76
July 224.67 22.32 224.00 23.30 4.83 23.33
August 235.67 22.27 232.00 23.24 6.67 23.29
September 303.50 21.84 160.00 22.64 7.83 22.66
October 406.00 21.18 141.67 21.43 71.17 21.25
November 464.50 20.60 217.50 20.45 202.83 20.31
December 485.17 20.34 316.50 20.12 315.83 20.02
             
Annual Sum or Average 4516.50 21.13 2422.17 21.33 1406.50 21.09
Minimum of Months 224.67 20.18 131.00 19.98 3.83 19.89
Maximum of Months 498.50 22.32 337.17 23.30 336.33 23.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.99 398.17 19.87 398.17 19.82
February 452.33 20.37 275.17 20.17 274.67 20.08
March 500.33 20.81 187.67 20.62 181.50 20.49
April 421.33 21.27 117.00 21.33 77.33 21.17
May 391.00 21.71 112.00 22.07 32.00 22.00
June 321.50 22.00 119.83 22.58 4.83 22.58
July 232.67 22.28 207.17 23.24 9.17 23.31
August 269.17 22.13 193.17 23.02 6.17 23.07
September 359.67 21.72 103.50 22.26 7.00 22.27
October 472.67 21.03 111.17 20.94 94.83 20.79
November 487.83 20.46 245.67 20.24 245.67 20.14
December 497.00 20.11 380.83 19.99 380.83 19.94
             
Annual Sum or Average 4907.50 21.00 2451.33 21.08 1712.17 20.86
Minimum of Months 232.67 19.99 103.50 19.87 4.83 19.82
Maximum of Months 502.00 22.28 398.17 23.24 398.17 23.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.25 389.67 20.15 389.67 20.12
February 454.00 20.51 267.00 20.37 267.00 20.30
March 514.00 20.94 167.83 20.81 167.83 20.73
April 477.67 21.53 50.17 21.42 49.67 21.33
May 475.33 22.34 7.00 22.36 1.00 22.35
June 357.00 22.91 35.50 23.02 0.00 23.02
July 211.00 23.10 131.33 23.48 0.00 23.48
August 204.50 22.97 188.67 23.51 0.00 23.51
September 380.83 22.62 41.67 22.77 0.00 22.77
October 502.00 21.74 12.83 21.70 12.83 21.66
November 489.00 20.97 139.50 20.81 139.50 20.70
December 497.00 20.50 322.17 20.40 322.17 20.35
             
Annual Sum or Average 5064.33 21.50 1753.33 21.39 1349.67 21.19
Minimum of Months 204.50 20.25 7.00 20.15 0.00 20.12
Maximum of Months 514.00 23.10 389.67 23.51 389.67 23.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.26 379.17 20.16 379.17 20.12
February 454.00 20.61 243.00 20.48 243.00 20.41
March 514.00 21.07 113.83 20.92 113.83 20.81
April 447.17 21.82 47.33 21.77 33.67 21.67
May 390.67 22.18 59.83 22.46 2.00 22.45
June 246.17 22.69 165.00 23.39 0.00 23.39
July 168.33 22.83 252.00 23.71 1.33 23.72
August 147.00 22.81 287.33 23.75 2.33 23.76
September 295.17 22.30 122.50 22.89 0.00 22.89
October 461.50 21.68 19.50 21.66 14.50 21.62
November 489.00 20.93 129.00 20.78 129.00 20.68
December 497.00 20.52 306.83 20.40 306.83 20.35
             
Annual Sum or Average 4612.00 21.37 2125.33 21.55 1225.67 21.34
Minimum of Months 147.00 20.26 19.50 20.16 0.00 20.12
Maximum of Months 514.00 22.83 379.17 23.75 379.17 23.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.18 346.00 20.00 346.00 19.92
February 444.67 20.76 171.67 20.51 171.17 20.36
March 494.00 21.11 96.00 20.90 95.17 20.74
April 420.67 21.46 74.17 21.49 45.17 21.35
May 414.00 21.81 56.33 22.07 7.67 22.03
June 352.17 22.22 76.00 22.66 0.00 22.66
July 212.50 22.53 202.33 23.41 0.17 23.41
August 195.67 22.48 251.67 23.50 2.00 23.51
September 262.00 22.18 179.50 23.08 3.50 23.11
October 396.00 21.62 82.83 22.05 10.33 22.00
November 468.17 20.91 129.67 20.83 114.50 20.68
December 489.00 20.51 275.67 20.31 273.50 20.20
             
Annual Sum or Average 4650.83 21.30 1941.83 21.48 1069.17 21.25
Minimum of Months 195.67 20.18 56.33 20.00 0.00 19.92
Maximum of Months 502.00 22.53 346.00 23.50 346.00 23.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.27 385.00 20.17 385.00 20.13
February 454.00 20.63 246.67 20.47 246.67 20.40
March 510.00 21.01 131.50 20.87 131.50 20.78
April 445.83 21.49 64.00 21.50 43.83 21.41
May 411.17 22.05 58.33 22.33 3.50 22.31
June 335.67 22.44 90.50 22.87 0.00 22.87
July 180.50 22.82 237.00 23.71 4.33 23.74
August 208.67 22.65 227.17 23.49 1.50 23.50
September 316.67 22.27 112.00 22.82 0.50 22.83
October 472.17 21.54 25.50 21.58 13.00 21.55
November 487.67 20.92 134.33 20.78 134.33 20.69
December 497.00 20.54 312.33 20.42 312.33 20.37
             
Annual Sum or Average 4821.33 21.35 2024.33 21.46 1276.50 21.27
Minimum of Months 180.50 20.27 25.50 20.17 0.00 20.13
Maximum of Months 510.00 22.82 385.00 23.71 385.00 23.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.21 330.17 20.05 330.17 19.97
February 454.00 20.58 214.67 20.36 214.67 20.25
March 514.00 21.25 100.50 21.08 100.50 20.96
April 447.17 21.95 38.50 21.90 27.17 21.82
May 358.17 22.53 45.17 22.69 1.00 22.68
June 235.67 22.97 92.17 23.29 0.00 23.29
July 145.50 23.14 215.00 23.74 0.00 23.74
August 166.00 22.99 261.83 23.69 0.00 23.69
September 325.67 22.59 65.50 22.85 0.00 22.85
October 492.17 21.74 29.83 21.65 29.83 21.57
November 489.00 20.89 148.00 20.68 148.00 20.55
December 497.00 20.43 290.17 20.27 290.17 20.20
             
Annual Sum or Average 4626.33 21.47 1831.50 21.48 1141.50 21.25
Minimum of Months 145.50 20.21 29.83 20.05 0.00 19.97
Maximum of Months 514.00 23.14 330.17 23.74 330.17 23.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.08 294.67 19.92 294.67 19.84
February 385.00 20.59 186.50 20.38 186.50 20.28
March 429.83 21.19 79.00 21.01 79.00 20.88
April 345.83 21.78 52.33 21.83 26.50 21.73
May 299.67 22.09 71.33 22.51 2.00 22.50
June 204.67 22.49 136.00 23.25 1.33 23.27
July 165.67 22.84 195.00 23.67 7.83 23.74
August 162.17 22.72 213.83 23.60 7.17 23.66
September 268.33 22.14 84.83 22.67 2.00 22.68
October 392.67 21.49 40.17 21.43 32.33 21.34
November 417.00 20.78 138.83 20.58 138.83 20.45
December 422.00 20.34 259.83 20.18 259.83 20.10
             
Annual Sum or Average 3919.83 21.29 1752.33 21.43 1038.00 21.21
Minimum of Months 162.17 20.08 40.17 19.92 1.33 19.84
Maximum of Months 429.83 22.84 294.67 23.67 294.67 23.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 494.67 20.49 264.00 20.26 262.33 20.14
February 411.17 20.96 162.17 20.86 144.17 20.71
March 437.50 21.32 100.17 21.31 71.17 21.17
April 350.00 21.70 95.00 22.01 27.50 21.91
May 332.00 22.12 109.83 22.65 2.83 22.64
June 261.33 22.44 140.17 23.10 0.00 23.10
July 188.33 22.72 240.00 23.61 4.00 23.64
August 189.83 22.67 263.17 23.60 5.33 23.64
September 267.33 22.29 178.67 23.10 4.67 23.14
October 382.33 21.60 111.33 22.06 22.67 21.98
November 456.50 21.01 135.17 20.97 112.67 20.82
December 471.50 20.68 231.33 20.49 225.50 20.37
             
Annual Sum or Average 4242.50 21.46 2031.00 21.79 882.83 21.58
Minimum of Months 188.33 20.49 95.00 20.26 0.00 20.14
Maximum of Months 494.67 22.72 264.00 23.61 262.33 23.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.23 326.67 20.06 326.67 19.99
February 452.00 20.67 202.83 20.46 202.17 20.34
March 498.00 21.11 101.67 20.99 95.50 20.88
April 409.17 21.53 73.33 21.67 34.83 21.57
May 381.17 22.09 87.00 22.50 6.50 22.51
June 303.33 22.38 119.67 22.92 1.33 22.93
July 197.50 22.67 229.33 23.58 8.33 23.64
August 227.83 22.51 219.50 23.38 5.67 23.42
September 328.00 22.09 112.33 22.67 2.33 22.68
October 464.83 21.40 54.00 21.43 34.17 21.34
November 485.83 20.81 146.67 20.63 146.67 20.52
December 497.00 20.46 280.83 20.29 280.83 20.21
             
Annual Sum or Average 4746.67 21.30 1953.83 21.45 1145.00 21.25
Minimum of Months 197.50 20.23 54.00 20.06 1.33 19.99
Maximum of Months 502.00 22.67 326.67 23.58 326.67 23.64



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.85063 30.70736 -0.0606 6.74623
February 454.00000 23.53663 30.66324 0.12625 5.83202
March 514.00000 23.96567 29.36567 0.24580 6.45606
April 485.00000 24.22706 32.44718 0.34523 7.80207
May 508.00000 24.37217 36.08557 -0.4338 9.37790
June 496.00000 24.43285 38.09341 -0.3704 8.44119
July 497.00000 24.52418 41.98806 -0.3001 7.58978
August 514.00000 24.41829 45.00197 -0.3007 7.45432
September 485.00000 24.47103 42.77934 -0.3332 8.04292
October 502.00000 24.27885 35.76416 0.38331 8.38676
November 489.00000 23.92305 35.24786 0.26274 6.83467
December 497.00000 23.48243 30.71237 0.10919 5.59855
           
Annual Sum or Average 5943.00000 24.04341 35.77213 -0.0292 7.39135
Minimum of Months 454.00000 22.85063 29.36567 -0.4338 5.59855
Maximum of Months 514.00000 24.52418 45.00197 0.38331 9.37790



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.41435 33.67069 -0.3897 10.05319
February 454.00000 22.02861 33.94290 -0.2222 7.38965
March 514.00000 22.83664 32.42908 -0.0220 5.75797
April 485.00000 23.35786 35.02633 0.13630 6.12081
May 508.00000 23.77999 38.05555 -0.6507 14.60957
June 496.00000 24.02638 39.53398 -0.5303 11.28931
July 497.00000 24.18219 43.20760 -0.4414 9.44272
August 514.00000 24.12937 46.22049 -0.4287 9.26236
September 485.00000 23.94897 44.74326 -0.5379 11.64634
October 502.00000 23.27054 38.92333 0.13533 6.09340
November 489.00000 22.43933 39.41295 -0.0851 6.17010
December 497.00000 21.82014 34.54271 -0.2753 7.46570
           
Annual Sum or Average 5943.00000 23.11130 38.33456 -0.2770 8.79015
Minimum of Months 454.00000 21.41435 32.42908 -0.6507 5.75797
Maximum of Months 514.00000 24.18219 46.22049 0.13630 14.60957



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.59299 34.49350 -0.6127 15.47280
February 454.00000 21.07215 34.87080 -0.4699 11.91009
March 514.00000 21.83925 33.88772 -0.2631 7.83914
April 485.00000 22.62860 36.23262 -0.0349 6.59389
May 508.00000 23.28485 39.02398 -0.8110 20.72862
June 496.00000 23.72425 40.13642 -0.6251 14.23900
July 497.00000 23.92591 43.60473 -0.5175 11.42049
August 514.00000 23.85449 46.75599 -0.5173 11.55030
September 485.00000 23.35786 46.28614 -0.7391 18.10485
October 502.00000 22.25992 41.12652 -0.1084 6.60287
November 489.00000 21.32791 41.60481 -0.3644 9.29099
December 497.00000 20.81987 35.99873 -0.5420 12.67768
           
Annual Sum or Average 5943.00000 22.40163 39.52626 -0.4675 12.20713
Minimum of Months 454.00000 20.59299 33.88772 -0.8110 6.59389
Maximum of Months 514.00000 23.92591 46.75599 -0.0349 20.72862



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.96266 34.98004 -0.8219 22.07788
February 454.00000 20.23620 35.50120 -0.7089 18.30298
March 514.00000 20.77861 35.42568 -0.5254 12.29770
April 485.00000 21.56091 37.81482 -0.2754 8.67618
May 508.00000 22.34401 41.01880 -1.0830 32.58459
June 496.00000 23.01234 41.90104 -0.8182 21.62488
July 497.00000 23.37074 44.88484 -0.6587 16.38161
August 514.00000 23.24885 48.72483 -0.6773 17.18388
September 485.00000 22.33939 49.05598 -1.0462 30.75440
October 502.00000 21.11608 43.44937 -0.3772 9.36949
November 489.00000 20.39600 42.49477 -0.6189 15.10730
December 497.00000 20.07397 36.76502 -0.7757 19.87029
           
Annual Sum or Average 5943.00000 21.54822 41.03234 -0.6991 18.68704
Minimum of Months 454.00000 19.96266 34.98004 -1.0830 8.67618
Maximum of Months 514.00000 23.37074 49.05598 -0.2754 32.58459



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.97525 34.89102 -0.8122 21.72271
February 454.00000 20.32090 35.31853 -0.6721 16.89614
March 514.00000 20.89494 35.18275 -0.4719 11.47093
April 485.00000 21.89187 37.06098 -0.1593 8.39155
May 508.00000 22.51445 40.51489 -0.9734 29.32192
June 496.00000 23.20621 41.18119 -0.6814 18.68101
July 497.00000 23.47445 44.45476 -0.5506 15.00933
August 514.00000 23.37844 48.11026 -0.5527 15.05214
September 485.00000 22.51523 48.41046 -0.9309 27.90156
October 502.00000 21.30199 42.93723 -0.3113 8.98508
November 489.00000 20.42116 42.41309 -0.6045 14.69780
December 497.00000 20.08980 36.70429 -0.7633 19.47588
           
Annual Sum or Average 5943.00000 21.67690 40.62832 -0.6235 17.29915
Minimum of Months 454.00000 19.97525 34.89102 -0.9734 8.39155
Maximum of Months 514.00000 23.47445 48.41046 -0.1593 29.32192



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.20319 34.16277 -0.7294 19.44843
February 454.00000 20.87762 34.03024 -0.5170 14.42160
March 514.00000 21.32793 34.05329 -0.3528 11.16236
April 485.00000 22.02193 36.46420 -0.1248 9.13011
May 508.00000 22.44792 40.36527 -0.9939 30.89993
June 496.00000 22.89320 41.79491 -0.8031 22.90168
July 497.00000 23.29869 44.70225 -0.6130 17.37969
August 514.00000 23.23263 48.31660 -0.5961 17.18380
September 485.00000 22.68590 47.55345 -0.8379 26.13037
October 502.00000 21.76749 41.45007 -0.1775 9.36582
November 489.00000 20.78205 41.19269 -0.5018 13.36452
December 497.00000 20.42454 35.70135 -0.6558 17.40312
           
Annual Sum or Average 5943.00000 21.83857 40.01913 -0.5761 17.42590
Minimum of Months 454.00000 20.20319 34.03024 -0.9939 9.13011
Maximum of Months 514.00000 23.29869 48.31660 -0.1248 30.89993



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.98824 34.70042 -0.8105 21.67115
February 454.00000 20.38055 35.03751 -0.6636 17.05912
March 514.00000 20.89522 34.99195 -0.4795 12.00945
April 485.00000 21.64744 37.44682 -0.2219 9.21716
May 508.00000 22.25219 40.99791 -1.0451 33.17264
June 496.00000 22.71226 42.37153 -0.8403 24.37499
July 497.00000 23.23124 45.02464 -0.6043 17.94412
August 514.00000 23.02145 49.14570 -0.6599 19.16910
September 485.00000 22.33041 48.80325 -0.9761 30.23513
October 502.00000 21.20997 42.98363 -0.3350 9.40831
November 489.00000 20.46164 42.14820 -0.5996 14.66653
December 497.00000 20.11141 36.48854 -0.7600 19.45231
           
Annual Sum or Average 5943.00000 21.53006 40.87972 -0.6666 19.04872
Minimum of Months 454.00000 19.98824 34.70042 -1.0451 9.21716
Maximum of Months 514.00000 23.23124 49.14570 -0.2219 33.17264



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.24705 35.00862 -0.7362 18.17905
February 454.00000 20.50938 35.60068 -0.6344 14.98982
March 514.00000 20.94309 35.49018 -0.4895 10.61945
April 485.00000 21.56081 38.31706 -0.2929 7.85758
May 508.00000 22.44459 41.41893 -1.0932 31.68260
June 496.00000 23.22508 42.14696 -0.8013 19.75786
July 497.00000 23.62996 44.95257 -0.6243 14.05430
August 514.00000 23.58345 48.39554 -0.6102 13.85208
September 485.00000 22.91369 48.02747 -0.8786 22.74953
October 502.00000 21.73587 42.37244 -0.2162 6.78769
November 489.00000 20.96956 41.53882 -0.4431 9.99333
December 497.00000 20.50449 36.10779 -0.6371 14.25169
           
Annual Sum or Average 5943.00000 21.86672 40.81231 -0.6219 15.41494
Minimum of Months 454.00000 20.24705 35.00862 -1.0932 6.78769
Maximum of Months 514.00000 23.62996 48.39554 -0.2162 31.68260



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.26101 34.72584 -0.7293 17.89193
February 454.00000 20.61191 35.19469 -0.5948 13.60820
March 514.00000 21.06794 34.99753 -0.4320 9.64210
April 485.00000 21.97994 37.13977 -0.1534 7.28139
May 508.00000 22.63471 40.63305 -0.9710 27.89002
June 496.00000 23.46153 41.03619 -0.6423 16.26559
July 497.00000 23.71403 44.33039 -0.5149 12.55956
August 514.00000 23.70925 47.53575 -0.4742 11.72719
September 485.00000 23.00738 47.32381 -0.7778 20.89418
October 502.00000 21.86934 41.75107 -0.1579 6.88414
November 489.00000 20.92905 41.38532 -0.4425 9.91656
December 497.00000 20.51893 35.83071 -0.6276 14.02063
           
Annual Sum or Average 5943.00000 21.99142 40.18673 -0.5433 14.06025
Minimum of Months 454.00000 20.26101 34.72584 -0.9710 6.88414
Maximum of Months 514.00000 23.71403 47.53575 -0.1534 27.89002



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.18180 33.67232 -0.6985 17.27480
February 454.00000 20.83262 33.70916 -0.4886 12.15154
March 514.00000 21.22115 33.71707 -0.3522 9.32369
April 485.00000 21.82398 36.58980 -0.1662 7.97267
May 508.00000 22.26452 40.81271 -1.0674 32.15154
June 496.00000 22.80834 42.17477 -0.8591 23.49766
July 497.00000 23.45406 44.74535 -0.5989 15.10799
August 514.00000 23.48854 48.03564 -0.5331 13.75923
September 485.00000 23.11579 46.50086 -0.6897 19.36764
October 502.00000 22.21499 40.10459 -0.0356 7.62452
November 489.00000 21.07681 39.88248 -0.3743 9.81287
December 497.00000 20.58024 34.52591 -0.5658 13.62028
           
Annual Sum or Average 5943.00000 21.93045 39.57795 -0.5369 15.17839
Minimum of Months 454.00000 20.18180 33.67232 -1.0674 7.62452
Maximum of Months 514.00000 23.48854 48.03564 -0.0356 32.15154



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.26882 34.51700 -0.7282 17.88025
February 454.00000 20.62769 34.94373 -0.5933 13.89376
March 514.00000 21.02980 34.83305 -0.4460 10.07812
April 485.00000 21.71185 37.52741 -0.2208 7.92233
May 508.00000 22.46295 40.83049 -1.0131 29.80670
June 496.00000 22.98976 42.13838 -0.7959 21.08705
July 497.00000 23.69110 44.28174 -0.5020 12.68882
August 514.00000 23.48981 48.18552 -0.5428 13.67627
September 485.00000 22.92417 47.41803 -0.7921 21.44766
October 502.00000 21.70606 41.95137 -0.1932 7.10814
November 489.00000 20.93052 41.20126 -0.4446 9.98299
December 497.00000 20.53794 35.59837 -0.6246 14.02576
           
Annual Sum or Average 5943.00000 21.87428 40.31836 -0.5752 14.98670
Minimum of Months 454.00000 20.26882 34.51700 -1.0131 7.10814
Maximum of Months 514.00000 23.69110 48.18552 -0.1932 29.80670



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.21332 34.88716 -0.7167 18.04508
February 454.00000 20.57734 35.25868 -0.5860 14.32981
March 514.00000 21.25302 35.01129 -0.3844 9.13091
April 485.00000 22.10195 37.12876 -0.1406 7.04359
May 508.00000 22.95136 39.99879 -0.8954 24.09586
June 496.00000 23.52419 41.00277 -0.6694 15.66084
July 497.00000 23.79332 44.11346 -0.5393 11.98218
August 514.00000 23.71142 47.74640 -0.5414 12.30442
September 485.00000 23.05388 47.43749 -0.8177 20.94631
October 502.00000 21.78231 42.26051 -0.2008 7.03904
November 489.00000 20.88748 41.80112 -0.4607 10.70572
December 497.00000 20.42613 36.30618 -0.6416 14.80357
           
Annual Sum or Average 5943.00000 22.03509 40.27490 -0.5496 13.83929
Minimum of Months 454.00000 20.21332 34.88716 -0.8954 7.03904
Maximum of Months 514.00000 23.79332 47.74640 -0.1406 24.09586



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.08474 34.29250 -0.7465 19.04127
February 385.00000 20.58846 34.42995 -0.5764 13.80849
March 433.00000 21.21280 34.42958 -0.3724 9.20609
April 410.00000 22.13106 36.28319 -0.0942 7.41374
May 430.00000 22.68790 39.83590 -0.9147 26.26301
June 418.00000 23.32785 40.86690 -0.6489 17.06132
July 422.00000 23.61533 43.98704 -0.5200 13.47524
August 433.00000 23.53900 47.58718 -0.5119 13.34789
September 410.00000 22.80391 47.41960 -0.8274 23.15567
October 427.00000 21.68860 41.87901 -0.1973 7.44109
November 417.00000 20.78246 41.31616 -0.4810 11.12112
December 422.00000 20.33823 35.79713 -0.6605 15.43205
           
Annual Sum or Average 5034.00000 21.90826 39.87321 -0.5461 14.73673
Minimum of Months 385.00000 20.08474 34.29250 -0.9147 7.41374
Maximum of Months 433.00000 23.61533 47.58718 -0.0942 26.26301



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.54173 33.62215 -0.6096 15.52811
February 454.00000 21.27476 33.42653 -0.3854 11.41139
March 514.00000 21.72342 33.42451 -0.2287 8.80187
April 485.00000 22.38642 35.80069 -0.0240 7.92954
May 508.00000 22.81342 39.59763 -0.8694 24.90964
June 496.00000 23.22695 41.11137 -0.7006 18.32013
July 497.00000 23.60224 44.09562 -0.5243 13.54411
August 514.00000 23.55469 47.58863 -0.4962 13.22788
September 485.00000 23.11788 46.40688 -0.6836 19.52569
October 502.00000 22.25206 40.32138 -0.0371 8.07470
November 489.00000 21.24866 40.28611 -0.3504 9.98252
December 497.00000 20.86487 34.76093 -0.5078 12.98409
           
Annual Sum or Average 5943.00000 22.22519 39.24031 -0.4524 13.70946
Minimum of Months 454.00000 20.54173 33.42451 -0.8694 7.92954
Maximum of Months 514.00000 23.60224 47.58863 -0.0240 24.90964



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.22864 34.31388 -0.7099 17.80175
February 454.00000 20.67957 34.58141 -0.5511 13.49239
March 514.00000 21.19683 34.55014 -0.3728 9.34639
April 485.00000 21.94445 36.94269 -0.1336 7.82201
May 508.00000 22.59068 40.30164 -0.9272 27.32637
June 496.00000 23.02735 41.73341 -0.7421 19.85179
July 497.00000 23.54026 44.41466 -0.5135 14.05345
August 514.00000 23.35458 48.41216 -0.5566 14.98302
September 485.00000 22.74453 47.72188 -0.8261 23.47774
October 502.00000 21.60354 42.07911 -0.2111 7.54742
November 489.00000 20.83221 41.41899 -0.4665 10.75524
December 497.00000 20.46085 35.70104 -0.6296 14.62486
           
Annual Sum or Average 5943.00000 21.86017 40.21514 -0.5538 15.10638
Minimum of Months 454.00000 20.22864 34.31388 -0.9272 7.54742
Maximum of Months 514.00000 23.54026 48.41216 -0.1336 27.32637



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.606805E+11 0.00 465.24 332425.65 02-JAN-06:11 0.00 33.07 49.90 0.24 0.00 0.06 0.91 02-JAN-06:11
February 0.368342E+11 0.00 374.46 288550.74 27-FEB-06:11 0.00 31.07 46.80 0.15 0.00 0.04 0.79 27-FEB-06:11
March 0.201067E+11 0.00 347.33 302977.88 27-MAR-05:11 0.00 27.43 41.70 0.07 0.00 0.02 0.83 27-MAR-05:11
April 0.848393E+10 0.00 225.74 248180.48 17-APR-05:11 0.00 27.89 37.24 0.03 0.00 0.01 0.68 17-APR-05:11
May 0.283015E+10 0.00 132.73 165876.87 18-MAY-06:03 0.00 32.52 37.13 0.01 0.00 0.00 0.45 18-MAY-06:03
June 0.891288E+09 0.00 55.33 90094.08 14-JUN-06:03 0.00 37.77 39.47 0.00 0.00 0.00 0.25 14-JUN-06:03
July 0.257888E+09 0.00 87.56 13547.27 10-JUL-06:07 0.00 31.89 35.33 0.00 0.00 0.00 0.04 10-JUL-06:07
August 0.298428E+09 0.00 139.12 37367.77 18-AUG-06:03 0.00 31.79 37.23 0.00 0.00 0.00 0.10 18-AUG-06:03
September 0.170713E+10 0.00 148.92 145778.85 28-SEP-06:03 0.00 30.14 36.31 0.01 0.00 0.00 0.40 28-SEP-06:03
October 0.100417E+11 0.00 273.79 257729.87 16-OCT-05:11 0.00 26.76 38.12 0.03 0.00 0.01 0.71 16-OCT-05:11
November 0.281707E+11 0.00 361.00 273019.61 20-NOV-06:11 0.00 28.65 43.70 0.10 0.00 0.03 0.75 20-NOV-06:11
December 0.477720E+11 0.00 406.79 267866.41 04-DEC-06:11 0.00 31.09 46.65 0.18 0.00 0.05 0.73 04-DEC-06:11
                           
Annual Sum or Average 0.218075E+12 0.00 3018.00     0.00 30.83 40.77 0.07 0.00 0.02    
Minimum of Months 0.257888E+09 0.00 55.33 13547.27   0.00 26.76 35.33 0.00 0.00 0.00 0.04  
Maximum of Months 0.606805E+11 0.00 465.24 332425.65   0.00 37.77 49.90 0.24 0.00 0.06 0.91  



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 0.304679E+09 79761204.23 9.67 0.277368E+09 27310300.04 0.00 0.54 27-FEB-15:05 0.00 01-FEB-00:10 16904.13 27-FEB-15:05 16904.13 27-FEB-15:05 1672.72 27-FEB-17:50 4257.85 27-FEB-15:05 0.00
March 0.541788E+09 0.145728E+09 26.50 0.470803E+09 70985080.28 0.00 0.49 18-MAR-16:00 0.00 01-MAR-00:10 15052.38 18-MAR-16:00 15052.38 18-MAR-16:00 2145.82 09-MAR-12:00 3843.81 18-MAR-16:00 0.00
April 0.425860E+10 0.104179E+10 74.00 0.404770E+10 0.210897E+09 0.00 1.00 26-APR-13:40 0.00 01-APR-00:10 55804.38 27-APR-16:00 55119.60 27-APR-15:10 5740.45 28-APR-13:00 13447.16 27-APR-16:00 0.00
May 0.944000E+10 0.228401E+10 163.28 0.827113E+10 0.116887E+10 0.00 1.00 04-MAY-13:20 0.00 01-MAY-00:10 51685.72 15-MAY-16:00 51685.72 15-MAY-16:00 7295.55 06-MAY-10:05 11487.10 15-MAY-16:00 0.00
June 0.176669E+11 0.427020E+10 269.29 0.162064E+11 0.146056E+10 0.00 1.00 09-JUN-14:20 0.00 01-JUN-00:10 58673.10 28-JUN-15:50 58673.10 28-JUN-15:50 8546.48 12-JUN-14:40 13747.37 28-JUN-15:50 0.00
July 0.330661E+11 0.783281E+10 352.97 0.287625E+11 0.430359E+10 0.00 1.00 06-JUL-14:50 0.00 01-JUL-00:10 74122.08 31-JUL-16:00 69304.88 24-JUL-15:00 15228.55 31-JUL-10:05 19274.72 24-JUL-15:00 0.00
August 0.447670E+11 0.106623E+11 381.46 0.385819E+11 0.618510E+10 0.00 1.00 06-AUG-17:22 0.00 01-AUG-00:10 79682.89 10-AUG-15:30 75379.53 10-AUG-16:00 24729.24 30-AUG-05:12 21229.20 10-AUG-16:00 0.00
September 0.173690E+11 0.412318E+10 234.84 0.140501E+11 0.331890E+10 0.00 1.00 08-SEP-14:05 0.00 01-SEP-00:10 68694.37 14-SEP-14:05 61854.74 14-SEP-15:30 17877.42 14-SEP-11:00 15337.63 14-SEP-14:05 0.00
October 0.230704E+10 0.584491E+09 66.75 0.214849E+10 0.158549E+09 0.00 1.00 04-OCT-14:05 0.00 01-OCT-00:10 38748.61 04-OCT-15:00 38748.61 04-OCT-15:00 3652.34 08-OCT-13:26 8592.94 04-OCT-15:00 0.00
November 0.509743E+09 0.125241E+09 8.50 0.350847E+09 0.158896E+09 0.00 0.76 04-NOV-14:00 0.00 01-NOV-00:10 25057.97 04-NOV-14:00 18847.75 04-NOV-14:00 7170.30 04-NOV-16:00 5954.33 04-NOV-14:00 0.00
December 30404.83 8713.22 0.02 27752.92 2651.91 0.00 0.02 19-DEC-08:09 0.00 01-DEC-00:10 456.07 19-DEC-08:09 416.29 19-DEC-08:09 39.78 19-DEC-08:09 130.70 19-DEC-08:09 0.00
                                       
Annual Sum or Average 0.130231E+12 0.311495E+11 1587.29 0.113167E+12 0.170637E+11 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.447670E+11 0.106623E+11 381.46 0.385819E+11 0.618510E+10 0.00 1.00   0.00   79682.89   75379.53   24729.24   21229.20   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 494542.11 140740.57 0.12 461781.32 32760.80 0.00 0.06 30-JAN-07:13 0.00 01-JAN-00:05 1452.24 30-JAN-07:13 1294.64 30-JAN-07:13 157.61 30-JAN-07:13 412.46 30-JAN-07:13 0.00
February 0.290266E+09 76025410.75 9.86 0.265042E+09 25223940.03 0.00 0.56 27-FEB-15:05 0.00 01-FEB-00:10 16578.08 27-FEB-15:05 16578.08 27-FEB-15:05 1569.19 27-FEB-18:20 4158.03 27-FEB-15:05 0.00
March 0.494761E+09 0.132650E+09 25.73 0.434195E+09 60565802.16 0.00 0.52 18-MAR-14:05 0.00 01-MAR-00:10 15336.21 18-MAR-14:05 15336.21 18-MAR-14:05 1969.32 09-MAR-12:00 3883.83 18-MAR-14:05 0.00
April 0.419030E+10 0.102525E+10 75.82 0.399187E+10 0.198426E+09 0.00 1.00 26-APR-13:40 0.00 01-APR-00:10 55048.19 27-APR-14:05 55048.19 27-APR-14:05 5783.10 28-APR-13:00 13243.62 27-APR-15:00 0.00
May 0.910081E+10 0.220524E+10 169.79 0.796482E+10 0.113599E+10 0.00 1.00 04-MAY-13:00 0.00 01-MAY-00:10 49925.87 04-MAY-14:05 49925.87 04-MAY-14:05 10753.53 07-MAY-16:32 11207.37 04-MAY-15:00 0.00
June 0.164835E+11 0.399438E+10 273.91 0.150917E+11 0.139180E+10 0.00 1.00 09-JUN-14:05 0.00 01-JUN-00:10 56349.55 28-JUN-15:40 56349.55 28-JUN-15:40 7563.87 12-JUN-14:05 13201.36 28-JUN-15:40 0.00
July 0.303865E+11 0.721859E+10 355.90 0.264247E+11 0.396179E+10 0.00 1.00 06-JUL-14:50 0.00 01-JUL-00:10 70879.70 31-JUL-14:05 65043.77 24-JUL-14:05 14666.25 31-JUL-10:05 18013.65 24-JUL-15:00 0.00
August 0.401225E+11 0.959616E+10 381.86 0.345398E+11 0.558275E+10 0.00 1.00 06-AUG-15:22 0.00 01-AUG-00:10 75710.78 10-AUG-14:05 70576.57 10-AUG-15:50 20265.71 30-AUG-13:00 19865.22 10-AUG-16:00 0.00
September 0.156551E+11 0.372973E+10 236.44 0.126104E+11 0.304469E+10 0.00 1.00 08-SEP-14:05 0.00 01-SEP-00:10 65634.11 14-SEP-14:05 57573.92 14-SEP-14:05 16699.87 14-SEP-12:05 14653.09 14-SEP-14:05 0.00
October 0.202249E+10 0.514796E+09 65.82 0.186810E+10 0.154394E+09 0.00 1.00 04-OCT-14:30 0.00 01-OCT-00:10 35105.91 04-OCT-15:00 35105.91 04-OCT-15:00 3443.62 08-OCT-13:35 7785.74 04-OCT-15:00 0.00
November 0.502037E+09 0.122544E+09 8.53 0.350552E+09 0.151485E+09 0.00 0.81 04-NOV-14:02 0.00 01-NOV-00:10 25511.88 04-NOV-14:02 19730.07 04-NOV-14:02 6889.09 04-NOV-13:00 5985.51 04-NOV-14:02 0.00
December 75233.73 21523.04 0.03 69823.21 5410.52 0.00 0.02 05-DEC-07:04 0.00 01-DEC-00:10 626.95 05-DEC-07:04 581.86 05-DEC-07:04 45.09 05-DEC-07:04 179.36 05-DEC-07:04 0.00
                                       
Annual Sum or Average 0.119249E+12 0.286155E+11 1603.81 0.103542E+12 0.157071E+11 0.00                         0.00
Minimum of Months 75233.73 21523.04 0.03 69823.21 5410.52 0.00 0.02   0.00   626.95   581.86   45.09   179.36   0.00
Maximum of Months 0.401225E+11 0.959616E+10 381.86 0.345398E+11 0.558275E+10 0.00 1.00   0.00   75710.78   70576.57   20265.71   19865.22   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1378417.43 394635.21 0.71 1270637.89 107779.54 0.00 0.04 08-JAN-10:37 0.00 01-JAN-00:05 1144.41 08-JAN-10:37 1137.79 08-JAN-10:37 114.99 26-JAN-07:04 326.38 08-JAN-10:37 0.00
February 0.323266E+09 85039283.80 9.97 0.288992E+09 34274138.01 0.00 0.51 27-FEB-15:00 0.00 01-FEB-00:10 17558.50 27-FEB-15:00 17514.61 27-FEB-15:00 1892.94 27-FEB-17:40 4457.11 27-FEB-15:00 0.00
March 0.547466E+09 0.147366E+09 25.75 0.475043E+09 72423615.32 0.00 0.48 18-MAR-14:00 0.00 01-MAR-00:10 16245.61 18-MAR-14:00 16245.61 18-MAR-14:00 2297.46 09-MAR-12:00 4160.43 18-MAR-14:00 0.00
April 0.480912E+10 0.117617E+10 74.42 0.455951E+10 0.249613E+09 0.00 1.00 26-APR-13:50 0.00 01-APR-00:10 68669.43 27-APR-14:40 68669.43 27-APR-14:40 5668.62 28-APR-13:00 16464.72 27-APR-15:00 0.00
May 0.101730E+11 0.247120E+10 167.59 0.883548E+10 0.133755E+10 0.00 1.00 04-MAY-13:05 0.00 01-MAY-00:10 65291.19 04-MAY-14:50 65291.19 04-MAY-14:50 8395.09 05-MAY-18:00 14684.14 04-MAY-15:00 0.00
June 0.184640E+11 0.448956E+10 271.78 0.167454E+11 0.171866E+10 0.00 1.00 09-JUN-14:05 0.00 01-JUN-00:10 70986.53 28-JUN-15:20 70986.53 28-JUN-15:20 7300.82 12-JUN-12:40 16641.06 28-JUN-15:20 0.00
July 0.342620E+11 0.817000E+10 353.49 0.296813E+11 0.458066E+10 0.00 1.00 06-JUL-15:10 0.00 01-JUL-00:10 85761.51 31-JUL-14:40 80289.77 24-JUL-15:00 14577.01 31-JUL-10:05 22017.00 24-JUL-15:00 0.00
August 0.445529E+11 0.107260E+11 378.89 0.383593E+11 0.619361E+10 0.00 1.00 07-AUG-10:20 0.00 01-AUG-00:10 90801.59 10-AUG-14:50 85634.58 10-AUG-15:20 20842.10 30-AUG-13:00 23680.26 10-AUG-15:40 0.00
September 0.164305E+11 0.394339E+10 231.52 0.130325E+11 0.339799E+10 0.00 1.00 08-SEP-14:30 0.00 01-SEP-00:10 73145.10 14-SEP-14:00 66000.23 14-SEP-14:40 17072.29 14-SEP-13:00 16358.38 14-SEP-14:00 0.00
October 0.195917E+10 0.507030E+09 63.07 0.177951E+10 0.179664E+09 0.00 0.91 04-OCT-15:00 0.00 01-OCT-00:10 34606.16 04-OCT-15:00 34606.16 04-OCT-15:00 4080.46 08-OCT-13:40 7884.38 04-OCT-15:00 0.00
November 0.559982E+09 0.137637E+09 8.50 0.383438E+09 0.176543E+09 0.00 0.76 04-NOV-13:40 0.00 01-NOV-00:10 27958.10 04-NOV-13:40 20895.06 04-NOV-14:00 8065.83 04-NOV-13:00 6634.88 04-NOV-13:40 0.00
December 854396.45 244901.20 0.53 717155.09 137241.36 0.00 0.02 11-DEC-06:13 0.00 01-DEC-00:10 685.13 11-DEC-06:13 634.02 11-DEC-06:13 125.60 17-DEC-20:20 196.07 11-DEC-06:13 0.00
                                       
Annual Sum or Average 0.132084E+12 0.318541E+11 1586.23 0.114142E+12 0.179412E+11 0.00                         0.00
Minimum of Months 854396.45 244901.20 0.53 717155.09 107779.54 0.00 0.02   0.00   685.13   634.02   114.99   196.07   0.00
Maximum of Months 0.445529E+11 0.107260E+11 378.89 0.383593E+11 0.619361E+10 0.00 1.00   0.00   90801.59   85634.58   20842.10   23680.26   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 252.09 0.00 252.09 3.18 1921.95 0.00 0.00 0.00
February 392.26 0.00 392.26 51.21 1708.11 0.00 0.00 0.00
March 577.93 0.00 577.93 170.00 1370.54 0.00 0.00 0.00
April 817.83 2.90 814.93 437.44 1088.56 0.00 0.00 0.00
May 1052.34 31.26 1021.08 732.11 879.48 0.00 0.00 0.00
June 1106.51 73.07 1033.44 858.23 690.71 0.00 0.00 0.00
July 1051.68 82.46 969.22 961.83 624.45 0.00 0.00 0.00
August 851.34 23.01 828.33 809.34 606.10 0.00 0.00 0.00
September 661.29 0.20 661.10 439.14 873.07 0.00 0.00 0.00
October 453.09 0.00 453.09 158.01 1177.19 0.00 0.00 0.00
November 285.40 0.00 285.40 24.53 1510.90 0.00 0.00 0.00
December 214.21 0.00 214.21 1.94 1910.33 0.00 0.00 0.00
                 
Annual Sum or Average 644.24 17.87 626.37 389.43 1194.29 0.00 0.00 0.00
Minimum of Months 214.21 0.00 214.21 1.94 606.10 0.00 0.00 0.00
Maximum of Months 1106.51 82.46 1033.44 961.83 1921.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 270.05 68.47 201.58 70.83 1214.76 0.00 0.00 0.00
February 495.51 175.86 319.64 272.11 1061.05 0.00 0.00 0.00
March 739.83 267.82 472.00 538.26 863.95 0.00 0.00 0.00
April 1146.86 476.53 670.32 1060.37 687.37 0.00 0.00 0.00
May 1220.36 424.29 796.07 1192.73 584.23 0.00 0.00 0.00
June 1461.52 635.91 825.60 1551.99 468.24 0.00 0.00 0.00
July 1361.01 610.90 750.12 1532.23 414.16 0.00 0.00 0.00
August 1337.68 669.18 668.50 1574.83 397.73 0.00 0.00 0.00
September 989.02 456.14 532.88 1014.07 556.15 0.00 0.00 0.00
October 644.64 273.91 370.73 529.80 750.35 0.00 0.00 0.00
November 315.97 89.20 226.77 138.42 966.98 0.00 0.00 0.00
December 259.16 83.43 175.73 97.66 1218.66 0.00 0.00 0.00
                 
Annual Sum or Average 855.04 353.41 501.63 800.52 763.92 0.00 0.00 0.00
Minimum of Months 259.16 68.47 175.73 70.83 397.73 0.00 0.00 0.00
Maximum of Months 1461.52 669.18 825.60 1574.83 1218.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1113.78 661.37 452.41 879.95 1707.69 0.00 0.00 0.00
February 1712.83 1060.26 652.57 1585.17 1532.63 0.00 0.00 0.00
March 1842.51 982.59 859.92 1800.12 1340.48 0.00 0.00 0.00
April 1945.34 844.65 1100.69 2022.91 1136.88 0.00 0.00 0.00
May 1778.77 529.91 1248.86 1861.78 951.55 0.00 0.00 0.00
June 1627.40 436.93 1190.47 1737.44 765.25 0.00 0.00 0.00
July 1774.75 650.00 1124.75 2147.86 692.72 0.00 0.00 0.00
August 1906.75 889.14 1017.60 2424.27 660.28 0.00 0.00 0.00
September 2112.59 1166.64 945.95 2500.84 889.16 0.00 0.00 0.00
October 1913.65 1181.53 732.11 2038.26 1160.78 0.00 0.00 0.00
November 1131.41 648.39 483.02 984.57 1407.33 0.00 0.00 0.00
December 1183.78 766.07 417.71 1062.23 1750.10 0.00 0.00 0.00
                 
Annual Sum or Average 1669.58 816.62 852.96 1754.54 1164.50 0.00 0.00 0.00
Minimum of Months 1113.78 436.93 417.71 879.95 660.28 0.00 0.00 0.00
Maximum of Months 2112.59 1181.53 1248.86 2500.84 1750.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 284.83 83.99 200.84 95.37 1223.20 0.00 0.00 0.00
February 510.68 191.93 318.75 310.47 1075.70 0.00 0.00 0.00
March 715.60 241.53 474.06 526.90 887.33 0.00 0.00 0.00
April 1088.70 416.25 672.45 1003.44 734.61 0.00 0.00 0.00
May 1400.91 569.11 831.80 1438.71 619.32 0.00 0.00 0.00
June 1347.29 523.10 824.19 1419.09 495.46 0.00 0.00 0.00
July 1664.39 874.88 789.51 1966.85 457.56 0.00 0.00 0.00
August 1376.85 703.06 673.79 1667.75 437.35 0.00 0.00 0.00
September 1121.23 537.99 583.24 1230.11 589.19 0.00 0.00 0.00
October 638.32 260.08 378.24 538.52 777.94 0.00 0.00 0.00
November 317.88 89.66 228.23 147.48 969.10 0.00 0.00 0.00
December 267.24 91.58 175.66 123.63 1226.19 0.00 0.00 0.00
                 
Annual Sum or Average 896.83 383.38 513.45 876.13 789.77 0.00 0.00 0.00
Minimum of Months 267.24 83.99 175.66 95.37 437.35 0.00 0.00 0.00
Maximum of Months 1664.39 874.88 831.80 1966.85 1226.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 84.03 0.00 84.03 0.70 668.31 0.00 0.00 0.00
February 130.75 0.00 130.75 16.76 592.84 0.00 0.00 0.00
March 192.64 0.00 192.64 60.92 472.38 0.00 0.00 0.00
April 272.60 0.97 271.63 156.72 367.35 0.00 0.00 0.00
May 350.77 10.42 340.35 257.03 298.62 0.00 0.00 0.00
June 368.82 24.36 344.47 296.90 234.92 0.00 0.00 0.00
July 350.55 27.48 323.06 328.56 213.84 0.00 0.00 0.00
August 283.77 7.67 276.10 273.94 211.84 0.00 0.00 0.00
September 220.42 0.06 220.36 145.58 315.20 0.00 0.00 0.00
October 151.03 0.00 151.03 48.22 433.05 0.00 0.00 0.00
November 95.13 0.00 95.13 6.58 557.38 0.00 0.00 0.00
December 71.40 0.00 71.40 0.24 685.50 0.00 0.00 0.00
                 
Annual Sum or Average 214.74 5.96 208.78 133.43 420.09 0.00 0.00 0.00
Minimum of Months 71.40 0.00 71.40 0.24 211.84 0.00 0.00 0.00
Maximum of Months 368.82 27.48 344.47 328.56 685.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 84.03 0.00 84.03 0.70 668.35 0.00 0.00 0.00
February 130.75 0.00 130.75 16.76 592.88 0.00 0.00 0.00
March 192.65 0.00 192.65 60.92 472.41 0.00 0.00 0.00
April 272.61 0.97 271.65 156.73 367.38 0.00 0.00 0.00
May 350.78 10.42 340.36 257.04 298.64 0.00 0.00 0.00
June 368.84 24.36 344.48 296.92 234.93 0.00 0.00 0.00
July 350.56 27.49 323.08 328.58 213.85 0.00 0.00 0.00
August 283.78 7.67 276.11 273.95 211.85 0.00 0.00 0.00
September 220.43 0.07 220.37 145.59 315.22 0.00 0.00 0.00
October 151.03 0.00 151.03 48.22 433.07 0.00 0.00 0.00
November 95.14 0.00 95.14 6.58 557.41 0.00 0.00 0.00
December 71.40 0.00 71.40 0.24 685.54 0.00 0.00 0.00
                 
Annual Sum or Average 214.75 5.96 208.79 133.43 420.12 0.00 0.00 0.00
Minimum of Months 71.40 0.00 71.40 0.24 211.85 0.00 0.00 0.00
Maximum of Months 368.84 27.49 344.48 328.58 685.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 84.03 0.00 84.03 0.70 668.35 0.00 0.00 0.00
February 130.75 0.00 130.75 16.76 592.88 0.00 0.00 0.00
March 192.65 0.00 192.65 60.92 472.41 0.00 0.00 0.00
April 272.61 0.97 271.65 156.73 367.38 0.00 0.00 0.00
May 350.78 10.42 340.36 257.04 298.64 0.00 0.00 0.00
June 368.84 24.36 344.48 296.92 234.93 0.00 0.00 0.00
July 350.56 27.49 323.08 328.58 213.85 0.00 0.00 0.00
August 283.78 7.67 276.11 273.95 211.85 0.00 0.00 0.00
September 220.43 0.07 220.37 145.59 315.22 0.00 0.00 0.00
October 151.03 0.00 151.03 48.22 433.07 0.00 0.00 0.00
November 95.14 0.00 95.14 6.58 557.41 0.00 0.00 0.00
December 71.40 0.00 71.40 0.24 685.54 0.00 0.00 0.00
                 
Annual Sum or Average 214.75 5.96 208.79 133.43 420.12 0.00 0.00 0.00
Minimum of Months 71.40 0.00 71.40 0.24 211.85 0.00 0.00 0.00
Maximum of Months 368.84 27.49 344.48 328.58 685.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 259.78 65.86 193.92 66.63 1218.92 0.00 0.00 0.00
February 476.68 169.18 307.49 260.43 1067.11 0.00 0.00 0.00
March 711.71 257.65 454.07 528.57 867.84 0.00 0.00 0.00
April 1103.27 458.43 644.85 1040.57 685.06 0.00 0.00 0.00
May 1173.98 408.17 765.82 1170.41 582.13 0.00 0.00 0.00
June 1405.98 611.75 794.23 1512.90 473.41 0.00 0.00 0.00
July 1309.29 587.68 721.61 1490.48 417.49 0.00 0.00 0.00
August 1286.85 643.76 643.09 1523.35 411.78 0.00 0.00 0.00
September 951.44 438.81 512.63 974.49 586.30 0.00 0.00 0.00
October 620.14 263.50 356.64 500.28 801.03 0.00 0.00 0.00
November 303.96 85.81 218.15 127.61 1027.09 0.00 0.00 0.00
December 249.32 80.26 169.05 90.22 1260.87 0.00 0.00 0.00
                 
Annual Sum or Average 822.55 339.98 482.56 776.51 781.91 0.00 0.00 0.00
Minimum of Months 249.32 65.86 169.05 66.63 411.78 0.00 0.00 0.00
Maximum of Months 1405.98 643.76 794.23 1523.35 1260.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.27 2.60 7.67 2.63 48.20 0.00 0.00 0.00
February 18.85 6.69 12.16 10.30 42.19 0.00 0.00 0.00
March 28.14 10.19 17.95 20.90 34.31 0.00 0.00 0.00
April 43.62 18.13 25.50 41.14 27.09 0.00 0.00 0.00
May 46.42 16.14 30.28 46.28 23.02 0.00 0.00 0.00
June 55.59 24.19 31.40 59.82 18.72 0.00 0.00 0.00
July 51.77 23.24 28.53 58.93 16.51 0.00 0.00 0.00
August 50.88 25.45 25.43 60.23 16.28 0.00 0.00 0.00
September 37.62 17.35 20.27 38.53 23.18 0.00 0.00 0.00
October 24.52 10.42 14.10 19.78 31.67 0.00 0.00 0.00
November 12.02 3.39 8.63 5.05 40.61 0.00 0.00 0.00
December 9.86 3.17 6.68 3.57 49.85 0.00 0.00 0.00
                 
Annual Sum or Average 32.52 13.44 19.08 30.70 30.92 0.00 0.00 0.00
Minimum of Months 9.86 2.60 6.68 2.63 16.28 0.00 0.00 0.00
Maximum of Months 55.59 25.45 31.40 60.23 49.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 371.27 220.46 150.81 296.20 595.48 0.00 0.00 0.00
February 570.96 353.43 217.53 534.85 542.65 0.00 0.00 0.00
March 614.19 327.54 286.65 613.21 473.29 0.00 0.00 0.00
April 648.46 281.56 366.91 692.71 391.94 0.00 0.00 0.00
May 592.94 176.64 416.30 640.94 325.89 0.00 0.00 0.00
June 542.48 145.65 396.83 598.32 261.18 0.00 0.00 0.00
July 591.60 216.67 374.93 729.37 241.57 0.00 0.00 0.00
August 635.60 296.39 339.21 817.11 237.66 0.00 0.00 0.00
September 704.22 388.89 315.33 836.95 330.84 0.00 0.00 0.00
October 637.90 393.85 244.04 680.11 437.48 0.00 0.00 0.00
November 377.15 216.14 161.01 326.23 519.58 0.00 0.00 0.00
December 394.60 255.36 139.24 353.60 627.30 0.00 0.00 0.00
                 
Annual Sum or Average 556.54 272.21 284.33 593.56 414.79 0.00 0.00 0.00
Minimum of Months 371.27 145.65 139.24 296.20 237.66 0.00 0.00 0.00
Maximum of Months 704.22 393.85 416.30 836.95 627.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 371.27 220.46 150.81 296.20 595.48 0.00 0.00 0.00
February 570.96 353.43 217.53 534.85 542.65 0.00 0.00 0.00
March 614.19 327.54 286.65 613.21 473.29 0.00 0.00 0.00
April 648.46 281.56 366.91 692.71 391.94 0.00 0.00 0.00
May 592.94 176.64 416.30 640.94 325.89 0.00 0.00 0.00
June 542.48 145.65 396.83 598.32 261.18 0.00 0.00 0.00
July 591.60 216.67 374.93 729.37 241.57 0.00 0.00 0.00
August 635.60 296.39 339.21 817.11 237.66 0.00 0.00 0.00
September 704.22 388.89 315.33 836.95 330.84 0.00 0.00 0.00
October 637.90 393.85 244.04 680.11 437.48 0.00 0.00 0.00
November 377.15 216.14 161.01 326.23 519.58 0.00 0.00 0.00
December 394.60 255.36 139.24 353.60 627.30 0.00 0.00 0.00
                 
Annual Sum or Average 556.54 272.21 284.33 593.56 414.79 0.00 0.00 0.00
Minimum of Months 371.27 145.65 139.24 296.20 237.66 0.00 0.00 0.00
Maximum of Months 704.22 393.85 416.30 836.95 627.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 371.25 220.45 150.80 296.18 595.45 0.00 0.00 0.00
February 570.92 353.41 217.51 534.82 542.62 0.00 0.00 0.00
March 614.15 327.52 286.63 613.17 473.26 0.00 0.00 0.00
April 648.42 281.54 366.88 692.67 391.91 0.00 0.00 0.00
May 592.90 176.63 416.27 640.90 325.87 0.00 0.00 0.00
June 542.45 145.64 396.81 598.28 261.16 0.00 0.00 0.00
July 591.56 216.66 374.90 729.33 241.55 0.00 0.00 0.00
August 635.56 296.37 339.19 817.05 237.65 0.00 0.00 0.00
September 704.17 388.87 315.31 836.90 330.82 0.00 0.00 0.00
October 637.86 393.83 244.03 680.07 437.45 0.00 0.00 0.00
November 377.12 216.12 161.00 326.21 519.55 0.00 0.00 0.00
December 394.58 255.35 139.23 353.58 627.26 0.00 0.00 0.00
                 
Annual Sum or Average 556.50 272.20 284.31 593.52 414.77 0.00 0.00 0.00
Minimum of Months 371.25 145.64 139.23 296.18 237.65 0.00 0.00 0.00
Maximum of Months 704.17 393.83 416.27 836.90 627.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 274.01 80.80 193.21 92.69 1228.73 0.00 0.00 0.00
February 491.27 184.63 306.64 303.74 1086.15 0.00 0.00 0.00
March 688.40 232.35 456.05 523.91 893.48 0.00 0.00 0.00
April 1047.33 400.43 646.89 995.97 729.07 0.00 0.00 0.00
May 1347.67 547.48 800.18 1415.20 623.09 0.00 0.00 0.00
June 1296.09 503.23 792.86 1393.04 498.40 0.00 0.00 0.00
July 1601.14 841.64 759.50 1911.73 473.10 0.00 0.00 0.00
August 1324.52 676.34 648.18 1616.60 456.39 0.00 0.00 0.00
September 1078.62 517.55 561.08 1185.72 626.01 0.00 0.00 0.00
October 614.06 250.20 363.86 515.31 828.00 0.00 0.00 0.00
November 305.80 86.25 219.55 138.72 1030.25 0.00 0.00 0.00
December 257.08 88.10 168.99 117.85 1271.44 0.00 0.00 0.00
                 
Annual Sum or Average 862.75 368.82 493.94 854.52 810.75 0.00 0.00 0.00
Minimum of Months 257.08 80.80 168.99 92.69 456.39 0.00 0.00 0.00
Maximum of Months 1601.14 841.64 800.18 1911.73 1271.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.83 3.19 7.64 3.66 48.58 0.00 0.00 0.00
February 19.42 7.30 12.12 12.01 42.95 0.00 0.00 0.00
March 27.22 9.19 18.03 20.71 35.33 0.00 0.00 0.00
April 41.41 15.83 25.58 39.38 28.83 0.00 0.00 0.00
May 53.29 21.65 31.64 55.96 24.64 0.00 0.00 0.00
June 51.25 19.90 31.35 55.08 19.71 0.00 0.00 0.00
July 63.31 33.28 30.03 75.59 18.71 0.00 0.00 0.00
August 52.37 26.74 25.63 63.92 18.05 0.00 0.00 0.00
September 42.65 20.46 22.18 46.88 24.75 0.00 0.00 0.00
October 24.28 9.89 14.39 20.37 32.74 0.00 0.00 0.00
November 12.09 3.41 8.68 5.48 40.74 0.00 0.00 0.00
December 10.16 3.48 6.68 4.66 50.27 0.00 0.00 0.00
                 
Annual Sum or Average 34.11 14.58 19.53 33.79 32.06 0.00 0.00 0.00
Minimum of Months 10.16 3.19 6.68 3.66 18.05 0.00 0.00 0.00
Maximum of Months 63.31 33.28 31.64 75.59 50.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 252.09 0.00 252.09 1.43 2041.17 0.00 0.00 0.00
February 392.26 0.00 392.26 43.73 1835.96 0.00 0.00 0.00
March 577.93 0.00 577.93 152.95 1491.32 0.00 0.00 0.00
April 817.83 2.90 814.93 416.06 1180.22 0.00 0.00 0.00
May 1052.34 31.26 1021.08 708.40 955.29 0.00 0.00 0.00
June 1106.51 73.07 1033.44 836.75 743.34 0.00 0.00 0.00
July 1051.68 82.46 969.22 947.52 670.21 0.00 0.00 0.00
August 851.34 23.01 828.33 793.10 659.46 0.00 0.00 0.00
September 661.29 0.20 661.10 414.66 966.62 0.00 0.00 0.00
October 453.09 0.00 453.09 134.94 1307.15 0.00 0.00 0.00
November 285.40 0.00 285.40 18.68 1663.07 0.00 0.00 0.00
December 214.21 0.00 214.21 0.66 2062.41 0.00 0.00 0.00
                 
Annual Sum or Average 644.24 17.87 626.37 374.57 1295.35 0.00 0.00 0.00
Minimum of Months 214.21 0.00 214.21 0.66 659.46 0.00 0.00 0.00
Maximum of Months 1106.51 82.46 1033.44 947.52 2062.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 270.05 68.47 201.58 65.57 1290.08 0.00 0.00 0.00
February 495.51 175.86 319.64 256.99 1141.39 0.00 0.00 0.00
March 739.83 267.82 472.00 514.82 938.80 0.00 0.00 0.00
April 1146.86 476.53 670.32 1038.68 738.16 0.00 0.00 0.00
May 1220.36 424.29 796.07 1176.84 623.39 0.00 0.00 0.00
June 1461.52 635.91 825.60 1542.49 495.69 0.00 0.00 0.00
July 1361.01 610.90 750.12 1524.51 437.36 0.00 0.00 0.00
August 1337.68 669.18 668.50 1564.00 423.41 0.00 0.00 0.00
September 989.02 456.14 532.88 995.99 604.19 0.00 0.00 0.00
October 644.64 273.91 370.73 505.54 825.75 0.00 0.00 0.00
November 315.97 89.20 226.77 127.75 1063.89 0.00 0.00 0.00
December 259.16 83.43 175.73 90.71 1315.47 0.00 0.00 0.00
                 
Annual Sum or Average 855.04 353.41 501.63 786.42 823.29 0.00 0.00 0.00
Minimum of Months 259.16 68.47 175.73 65.57 423.41 0.00 0.00 0.00
Maximum of Months 1461.52 669.18 825.60 1564.00 1315.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1113.78 661.37 452.41 862.52 1821.43 0.00 0.00 0.00
February 1712.83 1060.26 652.57 1558.85 1647.91 0.00 0.00 0.00
March 1842.51 982.59 859.92 1781.67 1450.37 0.00 0.00 0.00
April 1945.34 844.65 1100.69 2008.80 1219.09 0.00 0.00 0.00
May 1778.77 529.91 1248.86 1852.87 1020.43 0.00 0.00 0.00
June 1627.40 436.93 1190.47 1732.34 818.02 0.00 0.00 0.00
July 1774.75 650.00 1124.75 2146.04 738.85 0.00 0.00 0.00
August 1906.75 889.14 1017.60 2418.66 709.77 0.00 0.00 0.00
September 2112.59 1166.64 945.95 2485.20 966.92 0.00 0.00 0.00
October 1913.65 1181.53 732.11 2013.96 1272.15 0.00 0.00 0.00
November 1131.41 648.39 483.02 960.16 1538.51 0.00 0.00 0.00
December 1183.78 766.07 417.71 1040.80 1888.80 0.00 0.00 0.00
                 
Annual Sum or Average 1669.58 816.62 852.96 1739.33 1255.82 0.00 0.00 0.00
Minimum of Months 1113.78 436.93 417.71 862.52 709.77 0.00 0.00 0.00
Maximum of Months 2112.59 1181.53 1248.86 2485.20 1888.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 284.83 83.99 200.84 92.05 1299.05 0.00 0.00 0.00
February 510.68 191.93 318.75 302.54 1154.93 0.00 0.00 0.00
March 715.60 241.53 474.06 519.43 960.47 0.00 0.00 0.00
April 1088.70 416.25 672.45 997.29 788.82 0.00 0.00 0.00
May 1400.91 569.11 831.80 1434.14 664.76 0.00 0.00 0.00
June 1347.29 523.10 824.19 1416.93 530.16 0.00 0.00 0.00
July 1664.39 874.88 789.51 1966.60 488.72 0.00 0.00 0.00
August 1376.85 703.06 673.79 1663.73 470.29 0.00 0.00 0.00
September 1121.23 537.99 583.24 1221.15 641.16 0.00 0.00 0.00
October 638.32 260.08 378.24 526.97 852.13 0.00 0.00 0.00
November 317.88 89.66 228.23 141.09 1060.63 0.00 0.00 0.00
December 267.24 91.58 175.66 119.23 1322.21 0.00 0.00 0.00
                 
Annual Sum or Average 896.83 383.38 513.45 870.55 851.36 0.00 0.00 0.00
Minimum of Months 267.24 83.99 175.66 92.05 470.29 0.00 0.00 0.00
Maximum of Months 1664.39 874.88 831.80 1966.60 1322.21 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.675195E+09 0.00 0.675195E+09 8509742.19 0.514775E+10
February 0.948948E+09 0.00 0.948948E+09 0.123878E+09 0.413226E+10
March 0.154793E+10 0.00 0.154793E+10 0.455335E+09 0.367087E+10
April 0.211981E+10 7519582.16 0.211229E+10 0.113385E+10 0.282156E+10
May 0.281859E+10 83735716.19 0.273485E+10 0.196087E+10 0.235559E+10
June 0.286807E+10 0.189395E+09 0.267868E+10 0.222453E+10 0.179033E+10
July 0.281681E+10 0.220850E+09 0.259596E+10 0.257617E+10 0.167251E+10
August 0.228023E+10 61641115.79 0.221859E+10 0.216773E+10 0.162339E+10
September 0.171407E+10 505449.15 0.171356E+10 0.113824E+10 0.226299E+10
October 0.121357E+10 0.00 0.121357E+10 0.423220E+09 0.315299E+10
November 0.739768E+09 0.00 0.739768E+09 63571532.82 0.391624E+10
December 0.573741E+09 0.00 0.573741E+09 5208766.04 0.511662E+10
           
Annual Sum or Average 0.203167E+11 0.563647E+09 0.197531E+11 0.122811E+11 0.376631E+11
Minimum of Months 0.573741E+09 0.00 0.573741E+09 5208766.04 0.162339E+10
Maximum of Months 0.286807E+10 0.220850E+09 0.273485E+10 0.257617E+10 0.514775E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.723289E+09 0.183377E+09 0.539912E+09 0.189722E+09 0.325360E+10
February 0.119873E+10 0.425452E+09 0.773277E+09 0.658285E+09 0.256690E+10
March 0.198155E+10 0.717334E+09 0.126422E+10 0.144167E+10 0.231401E+10
April 0.297265E+10 0.123517E+10 0.173748E+10 0.274849E+10 0.178165E+10
May 0.326861E+10 0.113641E+10 0.213220E+10 0.319461E+10 0.156480E+10
June 0.378825E+10 0.164829E+10 0.213997E+10 0.402275E+10 0.121367E+10
July 0.364534E+10 0.163623E+10 0.200911E+10 0.410394E+10 0.110929E+10
August 0.358285E+10 0.179234E+10 0.179051E+10 0.421802E+10 0.106529E+10
September 0.256354E+10 0.118232E+10 0.138122E+10 0.262847E+10 0.144153E+10
October 0.172661E+10 0.733643E+09 0.992967E+09 0.141902E+10 0.200975E+10
November 0.818989E+09 0.231208E+09 0.587782E+09 0.358774E+09 0.250641E+10
December 0.694147E+09 0.223465E+09 0.470682E+09 0.261581E+09 0.326407E+10
           
Annual Sum or Average 0.269646E+11 0.111452E+11 0.158193E+11 0.252453E+11 0.240910E+11
Minimum of Months 0.694147E+09 0.183377E+09 0.470682E+09 0.189722E+09 0.106529E+10
Maximum of Months 0.378825E+10 0.179234E+10 0.213997E+10 0.421802E+10 0.326407E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298316E+10 0.177141E+10 0.121175E+10 0.235686E+10 0.457387E+10
February 0.414367E+10 0.256498E+10 0.157869E+10 0.383485E+10 0.370773E+10
March 0.493498E+10 0.263176E+10 0.230322E+10 0.482143E+10 0.359033E+10
April 0.504233E+10 0.218934E+10 0.285299E+10 0.524337E+10 0.294679E+10
May 0.476426E+10 0.141931E+10 0.334495E+10 0.498659E+10 0.254862E+10
June 0.421823E+10 0.113253E+10 0.308570E+10 0.450343E+10 0.198352E+10
July 0.475350E+10 0.174097E+10 0.301253E+10 0.575282E+10 0.185538E+10
August 0.510703E+10 0.238148E+10 0.272555E+10 0.649317E+10 0.176849E+10
September 0.547584E+10 0.302393E+10 0.245191E+10 0.648218E+10 0.230469E+10
October 0.512551E+10 0.316462E+10 0.196090E+10 0.545928E+10 0.310904E+10
November 0.293262E+10 0.168063E+10 0.125199E+10 0.255200E+10 0.364779E+10
December 0.317064E+10 0.205184E+10 0.111880E+10 0.284509E+10 0.468746E+10
           
Annual Sum or Average 0.526517E+11 0.257528E+11 0.268989E+11 0.553311E+11 0.367237E+11
Minimum of Months 0.293262E+10 0.113253E+10 0.111880E+10 0.235686E+10 0.176849E+10
Maximum of Months 0.547584E+10 0.316462E+10 0.334495E+10 0.649317E+10 0.468746E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.762895E+09 0.224963E+09 0.537932E+09 0.255434E+09 0.327621E+10
February 0.123544E+10 0.464312E+09 0.771130E+09 0.751086E+09 0.260232E+10
March 0.191665E+10 0.646918E+09 0.126974E+10 0.141125E+10 0.237661E+10
April 0.282192E+10 0.107892E+10 0.174300E+10 0.260092E+10 0.190412E+10
May 0.375219E+10 0.152430E+10 0.222789E+10 0.385344E+10 0.165879E+10
June 0.349218E+10 0.135589E+10 0.213629E+10 0.367828E+10 0.128424E+10
July 0.445791E+10 0.234329E+10 0.211461E+10 0.526801E+10 0.122552E+10
August 0.368776E+10 0.188306E+10 0.180469E+10 0.446691E+10 0.117139E+10
September 0.290624E+10 0.139447E+10 0.151177E+10 0.318844E+10 0.152718E+10
October 0.170968E+10 0.696610E+09 0.101307E+10 0.144237E+10 0.208363E+10
November 0.823946E+09 0.232386E+09 0.591560E+09 0.382258E+09 0.251190E+10
December 0.715776E+09 0.245277E+09 0.470499E+09 0.331130E+09 0.328423E+10
           
Annual Sum or Average 0.282826E+11 0.120904E+11 0.161922E+11 0.276295E+11 0.249062E+11
Minimum of Months 0.715776E+09 0.224963E+09 0.470499E+09 0.255434E+09 0.117139E+10
Maximum of Months 0.445791E+10 0.234329E+10 0.222789E+10 0.526801E+10 0.328423E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.225057E+09 0.00 0.225057E+09 1885297.13 0.179001E+10
February 0.316305E+09 0.00 0.316305E+09 40556511.72 0.143419E+10
March 0.515957E+09 0.00 0.515957E+09 0.163177E+09 0.126522E+10
April 0.706578E+09 2506448.36 0.704072E+09 0.406225E+09 0.952180E+09
May 0.939495E+09 27911025.41 0.911584E+09 0.688441E+09 0.799831E+09
June 0.955989E+09 63129536.60 0.892860E+09 0.769575E+09 0.608911E+09
July 0.938903E+09 73614410.82 0.865288E+09 0.880028E+09 0.572745E+09
August 0.760048E+09 20546390.80 0.739502E+09 0.733721E+09 0.567384E+09
September 0.571334E+09 168477.74 0.571166E+09 0.377349E+09 0.816988E+09
October 0.404507E+09 0.00 0.404507E+09 0.129161E+09 0.115987E+10
November 0.246581E+09 0.00 0.246581E+09 17065483.23 0.144472E+10
December 0.191240E+09 0.00 0.191240E+09 636195.60 0.183604E+10
           
Annual Sum or Average 0.677199E+10 0.187876E+09 0.658412E+10 0.420782E+10 0.132481E+11
Minimum of Months 0.191240E+09 0.00 0.191240E+09 636195.60 0.567384E+09
Maximum of Months 0.955989E+09 73614410.82 0.911584E+09 0.880028E+09 0.183604E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.225067E+09 0.00 0.225067E+09 1885087.30 0.179012E+10
February 0.316319E+09 0.00 0.316319E+09 40557020.40 0.143429E+10
March 0.515981E+09 0.00 0.515981E+09 0.163180E+09 0.126530E+10
April 0.706611E+09 2506545.14 0.704105E+09 0.406239E+09 0.952241E+09
May 0.939539E+09 27912103.15 0.911627E+09 0.688467E+09 0.799881E+09
June 0.956034E+09 63131974.25 0.892902E+09 0.769605E+09 0.608949E+09
July 0.938947E+09 73617253.32 0.865330E+09 0.880066E+09 0.572780E+09
August 0.760085E+09 20547184.17 0.739538E+09 0.733755E+09 0.567418E+09
September 0.571361E+09 168484.24 0.571193E+09 0.377363E+09 0.817037E+09
October 0.404526E+09 0.00 0.404526E+09 0.129164E+09 0.115994E+10
November 0.246592E+09 0.00 0.246592E+09 17065491.32 0.144481E+10
December 0.191249E+09 0.00 0.191249E+09 636129.48 0.183616E+10
           
Annual Sum or Average 0.677231E+10 0.187884E+09 0.658443E+10 0.420799E+10 0.132489E+11
Minimum of Months 0.191249E+09 0.00 0.191249E+09 636129.48 0.567418E+09
Maximum of Months 0.956034E+09 73617253.32 0.911627E+09 0.880066E+09 0.183616E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.225067E+09 0.00 0.225067E+09 1885087.30 0.179012E+10
February 0.316319E+09 0.00 0.316319E+09 40557020.40 0.143429E+10
March 0.515981E+09 0.00 0.515981E+09 0.163180E+09 0.126530E+10
April 0.706611E+09 2506545.14 0.704105E+09 0.406239E+09 0.952241E+09
May 0.939539E+09 27912103.15 0.911627E+09 0.688467E+09 0.799881E+09
June 0.956034E+09 63131974.25 0.892902E+09 0.769605E+09 0.608949E+09
July 0.938947E+09 73617253.32 0.865330E+09 0.880066E+09 0.572780E+09
August 0.760085E+09 20547184.17 0.739538E+09 0.733755E+09 0.567418E+09
September 0.571361E+09 168484.24 0.571193E+09 0.377363E+09 0.817037E+09
October 0.404526E+09 0.00 0.404526E+09 0.129164E+09 0.115994E+10
November 0.246592E+09 0.00 0.246592E+09 17065491.32 0.144481E+10
December 0.191249E+09 0.00 0.191249E+09 636129.48 0.183616E+10
           
Annual Sum or Average 0.677231E+10 0.187884E+09 0.658443E+10 0.420799E+10 0.132489E+11
Minimum of Months 0.191249E+09 0.00 0.191249E+09 636129.48 0.567418E+09
Maximum of Months 0.956034E+09 73617253.32 0.911627E+09 0.880066E+09 0.183616E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.695803E+09 0.176409E+09 0.519393E+09 0.178466E+09 0.326477E+10
February 0.115318E+10 0.409286E+09 0.743889E+09 0.630042E+09 0.258154E+10
March 0.190625E+10 0.690078E+09 0.121617E+10 0.141573E+10 0.232442E+10
April 0.285969E+10 0.118824E+10 0.167144E+10 0.269716E+10 0.177567E+10
May 0.314439E+10 0.109323E+10 0.205116E+10 0.313482E+10 0.155917E+10
June 0.364429E+10 0.158566E+10 0.205863E+10 0.392143E+10 0.122709E+10
July 0.350680E+10 0.157406E+10 0.193275E+10 0.399209E+10 0.111821E+10
August 0.344670E+10 0.172424E+10 0.172246E+10 0.408013E+10 0.110292E+10
September 0.246612E+10 0.113740E+10 0.132873E+10 0.252589E+10 0.151968E+10
October 0.166100E+10 0.705767E+09 0.955229E+09 0.133994E+10 0.214547E+10
November 0.787866E+09 0.222422E+09 0.565444E+09 0.330756E+09 0.266221E+10
December 0.667768E+09 0.214974E+09 0.452794E+09 0.241637E+09 0.337712E+10
           
Annual Sum or Average 0.259398E+11 0.107218E+11 0.152181E+11 0.244881E+11 0.246583E+11
Minimum of Months 0.667768E+09 0.176409E+09 0.452794E+09 0.178466E+09 0.110292E+10
Maximum of Months 0.364429E+10 0.172424E+10 0.205863E+10 0.408013E+10 0.337712E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27511406.14 6975055.52 20536350.63 7056403.83 0.129086E+09
February 45595516.94 16182811.94 29412705.00 24911277.58 0.102072E+09
March 75371288.78 27285051.50 48086237.28 55976568.65 91905283.84
April 0.113069E+09 46982009.39 66087428.66 0.106643E+09 70208330.59
May 0.124326E+09 43225475.32 81100993.92 0.123948E+09 61648153.05
June 0.144092E+09 62695431.61 81396504.59 0.155050E+09 48517881.07
July 0.138656E+09 62236719.63 76419098.64 0.157844E+09 44213038.69
August 0.136279E+09 68174718.27 68104583.89 0.161325E+09 43608628.44
September 97508291.40 44971671.77 52536619.63 99871379.43 60086774.99
October 65674294.15 27905404.48 37768889.66 52980216.73 84829999.45
November 31151520.61 8794384.52 22357136.09 13077788.41 0.105261E+09
December 26402954.98 8499892.46 17903062.52 9554115.71 0.133528E+09
           
Annual Sum or Average 0.102564E+10 0.423929E+09 0.601710E+09 0.968237E+09 0.974966E+09
Minimum of Months 26402954.98 6975055.52 17903062.52 7056403.83 43608628.44
Maximum of Months 0.144092E+09 68174718.27 81396504.59 0.161325E+09 0.133528E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.994411E+09 0.590485E+09 0.403926E+09 0.793333E+09 0.159494E+10
February 0.138126E+10 0.855017E+09 0.526243E+09 0.129392E+10 0.131278E+10
March 0.164503E+10 0.877277E+09 0.767758E+09 0.164241E+10 0.126765E+10
April 0.168082E+10 0.729800E+09 0.951019E+09 0.179551E+10 0.101590E+10
May 0.158813E+10 0.473116E+09 0.111501E+10 0.171670E+10 0.872871E+09
June 0.140611E+10 0.377521E+09 0.102859E+10 0.155085E+10 0.676970E+09
July 0.158454E+10 0.580339E+09 0.100420E+10 0.195355E+10 0.647010E+09
August 0.170238E+10 0.793847E+09 0.908538E+09 0.218854E+10 0.636554E+09
September 0.182533E+10 0.100800E+10 0.817323E+09 0.216938E+10 0.857540E+09
October 0.170855E+10 0.105490E+10 0.653648E+09 0.182160E+10 0.117174E+10
November 0.977565E+09 0.560226E+09 0.417339E+09 0.845584E+09 0.134675E+10
December 0.105691E+10 0.683965E+09 0.372941E+09 0.947075E+09 0.168017E+10
           
Annual Sum or Average 0.175510E+11 0.858450E+10 0.896653E+10 0.187184E+11 0.130809E+11
Minimum of Months 0.977565E+09 0.377521E+09 0.372941E+09 0.793333E+09 0.636554E+09
Maximum of Months 0.182533E+10 0.105490E+10 0.111501E+10 0.218854E+10 0.168017E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.994411E+09 0.590485E+09 0.403926E+09 0.793333E+09 0.159494E+10
February 0.138126E+10 0.855017E+09 0.526243E+09 0.129392E+10 0.131278E+10
March 0.164503E+10 0.877277E+09 0.767758E+09 0.164241E+10 0.126765E+10
April 0.168082E+10 0.729800E+09 0.951019E+09 0.179551E+10 0.101590E+10
May 0.158813E+10 0.473116E+09 0.111501E+10 0.171670E+10 0.872871E+09
June 0.140611E+10 0.377521E+09 0.102859E+10 0.155085E+10 0.676970E+09
July 0.158454E+10 0.580339E+09 0.100420E+10 0.195355E+10 0.647010E+09
August 0.170238E+10 0.793847E+09 0.908538E+09 0.218854E+10 0.636554E+09
September 0.182533E+10 0.100800E+10 0.817323E+09 0.216938E+10 0.857540E+09
October 0.170855E+10 0.105490E+10 0.653648E+09 0.182160E+10 0.117174E+10
November 0.977565E+09 0.560226E+09 0.417339E+09 0.845584E+09 0.134675E+10
December 0.105691E+10 0.683965E+09 0.372941E+09 0.947075E+09 0.168017E+10
           
Annual Sum or Average 0.175510E+11 0.858450E+10 0.896653E+10 0.187184E+11 0.130809E+11
Minimum of Months 0.977565E+09 0.377521E+09 0.372941E+09 0.793333E+09 0.636554E+09
Maximum of Months 0.182533E+10 0.105490E+10 0.111501E+10 0.218854E+10 0.168017E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.994349E+09 0.590448E+09 0.403901E+09 0.793282E+09 0.159484E+10
February 0.138117E+10 0.854963E+09 0.526209E+09 0.129384E+10 0.131270E+10
March 0.164493E+10 0.877221E+09 0.767709E+09 0.164231E+10 0.126757E+10
April 0.168071E+10 0.729754E+09 0.950959E+09 0.179540E+10 0.101584E+10
May 0.158802E+10 0.473086E+09 0.111494E+10 0.171659E+10 0.872816E+09
June 0.140602E+10 0.377497E+09 0.102852E+10 0.155075E+10 0.676927E+09
July 0.158444E+10 0.580303E+09 0.100414E+10 0.195343E+10 0.646969E+09
August 0.170228E+10 0.793797E+09 0.908480E+09 0.218840E+10 0.636514E+09
September 0.182521E+10 0.100794E+10 0.817272E+09 0.216924E+10 0.857486E+09
October 0.170844E+10 0.105483E+10 0.653607E+09 0.182149E+10 0.117167E+10
November 0.977504E+09 0.560191E+09 0.417313E+09 0.845530E+09 0.134667E+10
December 0.105684E+10 0.683922E+09 0.372918E+09 0.947015E+09 0.168006E+10
           
Annual Sum or Average 0.175499E+11 0.858396E+10 0.896597E+10 0.187173E+11 0.130801E+11
Minimum of Months 0.977504E+09 0.377497E+09 0.372918E+09 0.793282E+09 0.636514E+09
Maximum of Months 0.182521E+10 0.105483E+10 0.111494E+10 0.218840E+10 0.168006E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.733902E+09 0.216414E+09 0.517488E+09 0.248252E+09 0.329103E+10
February 0.118849E+10 0.446668E+09 0.741822E+09 0.734813E+09 0.262761E+10
March 0.184381E+10 0.622336E+09 0.122148E+10 0.140323E+10 0.239309E+10
April 0.271467E+10 0.103792E+10 0.167675E+10 0.258156E+10 0.188976E+10
May 0.360959E+10 0.146638E+10 0.214321E+10 0.379047E+10 0.166888E+10
June 0.335945E+10 0.130436E+10 0.205509E+10 0.361077E+10 0.129186E+10
July 0.428849E+10 0.225425E+10 0.203424E+10 0.512038E+10 0.126716E+10
August 0.354761E+10 0.181151E+10 0.173610E+10 0.432991E+10 0.122241E+10
September 0.279579E+10 0.134148E+10 0.145431E+10 0.307339E+10 0.162261E+10
October 0.164471E+10 0.670140E+09 0.974568E+09 0.138020E+10 0.221771E+10
November 0.792633E+09 0.223555E+09 0.569078E+09 0.359562E+09 0.267040E+10
December 0.688573E+09 0.235957E+09 0.452617E+09 0.315653E+09 0.340542E+10
           
Annual Sum or Average 0.272077E+11 0.116310E+11 0.155767E+11 0.269482E+11 0.255679E+11
Minimum of Months 0.688573E+09 0.216414E+09 0.452617E+09 0.248252E+09 0.122241E+10
Maximum of Months 0.428849E+10 0.225425E+10 0.214321E+10 0.512038E+10 0.340542E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29017830.29 8556830.13 20461000.16 9815644.96 0.130124E+09
February 46991849.05 17660860.22 29330988.83 29053862.47 0.103893E+09
March 72902677.81 24606606.33 48296071.48 55482640.18 94620557.63
April 0.107336E+09 41038575.68 66297148.76 0.102072E+09 74719334.77
May 0.142720E+09 57979403.98 84740578.40 0.149872E+09 65985853.44
June 0.132830E+09 51573417.70 81256400.73 0.142766E+09 51078957.50
July 0.169563E+09 89130945.21 80431978.00 0.202455E+09 50102404.09
August 0.140269E+09 71625467.90 68643659.86 0.171201E+09 48332865.38
September 0.110543E+09 53040965.04 57502084.26 0.121519E+09 64156386.07
October 65030251.66 26496725.49 38533526.17 54572047.50 87686106.16
November 31339996.48 8839182.66 22500813.82 14216775.21 0.105585E+09
December 27225573.32 9329511.87 17896061.45 12480630.01 0.134647E+09
           
Annual Sum or Average 0.107577E+10 0.459878E+09 0.615890E+09 0.106551E+10 0.101093E+10
Minimum of Months 27225573.32 8556830.13 17896061.45 9815644.96 48332865.38
Maximum of Months 0.169563E+09 89130945.21 84740578.40 0.202455E+09 0.134647E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.675195E+09 0.00 0.675195E+09 3827537.30 0.546707E+10
February 0.948948E+09 0.00 0.948948E+09 0.105796E+09 0.444155E+10
March 0.154793E+10 0.00 0.154793E+10 0.409652E+09 0.399434E+10
April 0.211981E+10 7519582.16 0.211229E+10 0.107842E+10 0.305913E+10
May 0.281859E+10 83735716.19 0.273485E+10 0.189739E+10 0.255864E+10
June 0.286807E+10 0.189395E+09 0.267868E+10 0.216886E+10 0.192675E+10
July 0.281681E+10 0.220850E+09 0.259596E+10 0.253784E+10 0.179509E+10
August 0.228023E+10 61641115.79 0.221859E+10 0.212424E+10 0.176630E+10
September 0.171407E+10 505449.15 0.171356E+10 0.107479E+10 0.250549E+10
October 0.121357E+10 0.00 0.121357E+10 0.361436E+09 0.350108E+10
November 0.739768E+09 0.00 0.739768E+09 48414290.65 0.431068E+10
December 0.573741E+09 0.00 0.573741E+09 1770411.31 0.552395E+10
           
Annual Sum or Average 0.203167E+11 0.563647E+09 0.197531E+11 0.118124E+11 0.408501E+11
Minimum of Months 0.573741E+09 0.00 0.573741E+09 1770411.31 0.176630E+10
Maximum of Months 0.286807E+10 0.220850E+09 0.273485E+10 0.253784E+10 0.552395E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.723289E+09 0.183377E+09 0.539912E+09 0.175618E+09 0.345534E+10
February 0.119873E+10 0.425452E+09 0.773277E+09 0.621712E+09 0.276126E+10
March 0.198155E+10 0.717334E+09 0.126422E+10 0.137889E+10 0.251449E+10
April 0.297265E+10 0.123517E+10 0.173748E+10 0.269225E+10 0.191330E+10
May 0.326861E+10 0.113641E+10 0.213220E+10 0.315205E+10 0.166970E+10
June 0.378825E+10 0.164829E+10 0.213997E+10 0.399814E+10 0.128484E+10
July 0.364534E+10 0.163623E+10 0.200911E+10 0.408325E+10 0.117143E+10
August 0.358285E+10 0.179234E+10 0.179051E+10 0.418902E+10 0.113407E+10
September 0.256354E+10 0.118232E+10 0.138122E+10 0.258160E+10 0.156607E+10
October 0.172661E+10 0.733643E+09 0.992967E+09 0.135404E+10 0.221169E+10
November 0.818989E+09 0.231208E+09 0.587782E+09 0.331137E+09 0.275759E+10
December 0.694147E+09 0.223465E+09 0.470682E+09 0.242944E+09 0.352335E+10
           
Annual Sum or Average 0.269646E+11 0.111452E+11 0.158193E+11 0.248007E+11 0.259631E+11
Minimum of Months 0.694147E+09 0.183377E+09 0.470682E+09 0.175618E+09 0.113407E+10
Maximum of Months 0.378825E+10 0.179234E+10 0.213997E+10 0.418902E+10 0.352335E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298316E+10 0.177141E+10 0.121175E+10 0.231017E+10 0.487853E+10
February 0.414367E+10 0.256498E+10 0.157869E+10 0.377116E+10 0.398663E+10
March 0.493498E+10 0.263176E+10 0.230322E+10 0.477202E+10 0.388466E+10
April 0.504233E+10 0.218934E+10 0.285299E+10 0.520681E+10 0.315988E+10
May 0.476426E+10 0.141931E+10 0.334495E+10 0.496273E+10 0.273311E+10
June 0.421823E+10 0.113253E+10 0.308570E+10 0.449022E+10 0.212030E+10
July 0.475350E+10 0.174097E+10 0.301253E+10 0.574796E+10 0.197894E+10
August 0.510703E+10 0.238148E+10 0.272555E+10 0.647815E+10 0.190105E+10
September 0.547584E+10 0.302393E+10 0.245191E+10 0.644163E+10 0.250626E+10
October 0.512551E+10 0.316462E+10 0.196090E+10 0.539420E+10 0.340734E+10
November 0.293262E+10 0.168063E+10 0.125199E+10 0.248874E+10 0.398782E+10
December 0.317064E+10 0.205184E+10 0.111880E+10 0.278767E+10 0.505897E+10
           
Annual Sum or Average 0.526517E+11 0.257528E+11 0.268989E+11 0.548514E+11 0.396035E+11
Minimum of Months 0.293262E+10 0.113253E+10 0.111880E+10 0.231017E+10 0.190105E+10
Maximum of Months 0.547584E+10 0.316462E+10 0.334495E+10 0.647815E+10 0.505897E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.762895E+09 0.224963E+09 0.537932E+09 0.246560E+09 0.347939E+10
February 0.123544E+10 0.464312E+09 0.771130E+09 0.731914E+09 0.279402E+10
March 0.191665E+10 0.646918E+09 0.126974E+10 0.139124E+10 0.257251E+10
April 0.282192E+10 0.107892E+10 0.174300E+10 0.258497E+10 0.204463E+10
May 0.375219E+10 0.152430E+10 0.222789E+10 0.384120E+10 0.178051E+10
June 0.349218E+10 0.135589E+10 0.213629E+10 0.367268E+10 0.137417E+10
July 0.445791E+10 0.234329E+10 0.211461E+10 0.526734E+10 0.130898E+10
August 0.368776E+10 0.188306E+10 0.180469E+10 0.445614E+10 0.125964E+10
September 0.290624E+10 0.139447E+10 0.151177E+10 0.316523E+10 0.166188E+10
October 0.170968E+10 0.696610E+09 0.101307E+10 0.141144E+10 0.228234E+10
November 0.823946E+09 0.232386E+09 0.591560E+09 0.365713E+09 0.274916E+10
December 0.715776E+09 0.245277E+09 0.470499E+09 0.319347E+09 0.354140E+10
           
Annual Sum or Average 0.282826E+11 0.120904E+11 0.161922E+11 0.274538E+11 0.268486E+11
Minimum of Months 0.715776E+09 0.224963E+09 0.470499E+09 0.246560E+09 0.125964E+10
Maximum of Months 0.445791E+10 0.234329E+10 0.222789E+10 0.526734E+10 0.354140E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3.18 1921.95 252.09 0.00 252.09 0.00 0.00
February 51.21 1708.11 392.26 0.00 392.26 0.00 0.00
March 170.00 1370.54 577.93 0.00 577.93 0.00 0.00
April 437.44 1088.56 817.83 2.90 814.93 0.00 0.00
May 732.11 879.48 1052.34 31.26 1021.08 0.00 0.00
June 858.23 690.71 1106.51 73.07 1033.44 0.00 0.00
July 961.83 624.45 1051.68 82.46 969.22 0.00 0.00
August 809.34 606.10 851.34 23.01 828.33 0.00 0.00
September 439.14 873.07 661.29 0.20 661.10 0.00 0.00
October 158.01 1177.19 453.09 0.00 453.09 0.00 0.00
November 24.53 1510.90 285.40 0.00 285.40 0.00 0.00
December 1.94 1910.33 214.21 0.00 214.21 0.00 0.00
               
Annual Sum or Average 389.43 1194.29 644.24 17.87 626.37 0.00 0.00
Minimum of Months 1.94 606.10 214.21 0.00 214.21 0.00 0.00
Maximum of Months 961.83 1921.95 1106.51 82.46 1033.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 70.83 1214.76 270.05 68.47 201.58 0.00 0.00
February 272.11 1061.05 495.51 175.86 319.64 0.00 0.00
March 538.26 863.95 739.83 267.82 472.00 0.00 0.00
April 1060.37 687.37 1146.86 476.53 670.32 0.00 0.00
May 1192.73 584.23 1220.36 424.29 796.07 0.00 0.00
June 1551.99 468.24 1461.52 635.91 825.60 0.00 0.00
July 1532.23 414.16 1361.01 610.90 750.12 0.00 0.00
August 1574.83 397.73 1337.68 669.18 668.50 0.00 0.00
September 1014.07 556.15 989.02 456.14 532.88 0.00 0.00
October 529.80 750.35 644.64 273.91 370.73 0.00 0.00
November 138.42 966.98 315.97 89.20 226.77 0.00 0.00
December 97.66 1218.66 259.16 83.43 175.73 0.00 0.00
               
Annual Sum or Average 800.52 763.92 855.04 353.41 501.63 0.00 0.00
Minimum of Months 70.83 397.73 259.16 68.47 175.73 0.00 0.00
Maximum of Months 1574.83 1218.66 1461.52 669.18 825.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 879.95 1707.69 1113.78 661.37 452.41 0.00 0.00
February 1585.17 1532.63 1712.83 1060.26 652.57 0.00 0.00
March 1800.12 1340.48 1842.51 982.59 859.92 0.00 0.00
April 2022.91 1136.88 1945.34 844.65 1100.69 0.00 0.00
May 1861.78 951.55 1778.77 529.91 1248.86 0.00 0.00
June 1737.44 765.25 1627.40 436.93 1190.47 0.00 0.00
July 2147.86 692.72 1774.75 650.00 1124.75 0.00 0.00
August 2424.27 660.28 1906.75 889.14 1017.60 0.00 0.00
September 2500.84 889.16 2112.59 1166.64 945.95 0.00 0.00
October 2038.26 1160.78 1913.65 1181.53 732.11 0.00 0.00
November 984.57 1407.33 1131.41 648.39 483.02 0.00 0.00
December 1062.23 1750.10 1183.78 766.07 417.71 0.00 0.00
               
Annual Sum or Average 1754.54 1164.50 1669.58 816.62 852.96 0.00 0.00
Minimum of Months 879.95 660.28 1113.78 436.93 417.71 0.00 0.00
Maximum of Months 2500.84 1750.10 2112.59 1181.53 1248.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 95.37 1223.20 284.83 83.99 200.84 0.00 0.00
February 310.47 1075.70 510.68 191.93 318.75 0.00 0.00
March 526.90 887.33 715.60 241.53 474.06 0.00 0.00
April 1003.44 734.61 1088.70 416.25 672.45 0.00 0.00
May 1438.71 619.32 1400.91 569.11 831.80 0.00 0.00
June 1419.09 495.46 1347.29 523.10 824.19 0.00 0.00
July 1966.85 457.56 1664.39 874.88 789.51 0.00 0.00
August 1667.75 437.35 1376.85 703.06 673.79 0.00 0.00
September 1230.11 589.19 1121.23 537.99 583.24 0.00 0.00
October 538.52 777.94 638.32 260.08 378.24 0.00 0.00
November 147.48 969.10 317.88 89.66 228.23 0.00 0.00
December 123.63 1226.19 267.24 91.58 175.66 0.00 0.00
               
Annual Sum or Average 876.13 789.77 896.83 383.38 513.45 0.00 0.00
Minimum of Months 95.37 437.35 267.24 83.99 175.66 0.00 0.00
Maximum of Months 1966.85 1226.19 1664.39 874.88 831.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2.11 2005.02 252.09 0.00 252.09 0.00 0.00
February 50.29 1778.59 392.25 0.00 392.25 0.00 0.00
March 182.77 1417.20 577.93 0.00 577.93 0.00 0.00
April 470.18 1102.11 817.82 2.90 814.92 0.00 0.00
May 771.12 895.91 1052.33 31.26 1021.07 0.00 0.00
June 890.73 704.79 1106.50 73.07 1033.44 0.00 0.00
July 985.72 641.54 1051.67 82.46 969.22 0.00 0.00
August 821.85 635.54 851.34 23.01 828.32 0.00 0.00
September 436.76 945.63 661.29 0.20 661.09 0.00 0.00
October 144.67 1299.19 453.09 0.00 453.09 0.00 0.00
November 19.75 1672.20 285.40 0.00 285.40 0.00 0.00
December 0.71 2056.59 214.21 0.00 214.21 0.00 0.00
               
Annual Sum or Average 400.30 1260.34 644.24 17.87 626.36 0.00 0.00
Minimum of Months 0.71 635.54 214.21 0.00 214.21 0.00 0.00
Maximum of Months 985.72 2056.59 1106.50 82.46 1033.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 69.27 1267.12 270.05 68.47 201.59 0.00 0.00
February 270.73 1109.30 495.52 175.87 319.65 0.00 0.00
March 549.47 902.15 739.85 267.83 472.02 0.00 0.00
April 1081.71 712.14 1146.90 476.55 670.34 0.00 0.00
May 1216.68 605.14 1220.40 424.31 796.09 0.00 0.00
June 1572.72 492.13 1461.57 635.94 825.63 0.00 0.00
July 1549.41 434.00 1361.06 610.92 750.14 0.00 0.00
August 1583.58 428.07 1337.73 669.21 668.52 0.00 0.00
September 1013.02 609.48 989.06 456.16 532.89 0.00 0.00
October 520.06 832.70 644.66 273.92 370.74 0.00 0.00
November 132.65 1067.70 315.98 89.20 226.78 0.00 0.00
December 93.78 1310.73 259.17 83.44 175.74 0.00 0.00
               
Annual Sum or Average 807.21 812.82 855.07 353.43 501.64 0.00 0.00
Minimum of Months 69.27 428.07 259.17 68.47 175.74 0.00 0.00
Maximum of Months 1583.58 1310.73 1461.57 669.21 825.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 888.57 1786.41 1113.79 661.37 452.42 0.00 0.00
February 1604.53 1627.92 1712.84 1060.27 652.57 0.00 0.00
March 1839.58 1419.83 1842.52 982.59 859.93 0.00 0.00
April 2078.09 1175.79 1945.35 844.66 1100.69 0.00 0.00
May 1922.79 977.66 1778.78 529.91 1248.86 0.00 0.00
June 1794.92 783.51 1627.41 436.94 1190.47 0.00 0.00
July 2188.07 724.68 1774.76 650.01 1124.75 0.00 0.00
August 2451.27 712.97 1906.75 889.15 1017.61 0.00 0.00
September 2510.80 992.50 2112.60 1166.65 945.96 0.00 0.00
October 2040.28 1312.41 1913.66 1181.54 732.12 0.00 0.00
November 978.66 1558.71 1131.42 648.40 483.02 0.00 0.00
December 1060.77 1881.87 1183.79 766.07 417.71 0.00 0.00
               
Annual Sum or Average 1780.64 1244.35 1669.58 816.62 852.96 0.00 0.00
Minimum of Months 888.57 712.97 1113.79 436.94 417.71 0.00 0.00
Maximum of Months 2510.80 1881.87 2112.60 1181.54 1248.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 96.35 1277.31 284.84 83.99 200.85 0.00 0.00
February 315.75 1129.10 510.70 191.93 318.76 0.00 0.00
March 544.62 928.80 715.62 241.54 474.08 0.00 0.00
April 1035.35 757.90 1088.74 416.27 672.47 0.00 0.00
May 1471.16 647.72 1400.95 569.13 831.82 0.00 0.00
June 1448.12 518.11 1347.33 523.12 824.21 0.00 0.00
July 1987.32 491.81 1664.45 874.92 789.53 0.00 0.00
August 1680.52 474.44 1376.89 703.08 673.81 0.00 0.00
September 1232.60 650.76 1121.27 538.01 583.26 0.00 0.00
October 535.68 860.73 638.34 260.09 378.25 0.00 0.00
November 144.20 1070.98 317.89 89.66 228.23 0.00 0.00
December 122.51 1321.71 267.25 91.58 175.67 0.00 0.00
               
Annual Sum or Average 888.31 842.81 896.86 383.40 513.46 0.00 0.00
Minimum of Months 96.35 474.44 267.25 83.99 175.67 0.00 0.00
Maximum of Months 1987.32 1321.71 1664.45 874.92 831.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.43 2041.17 252.09 0.00 252.09 0.00 0.00
February 43.73 1835.96 392.26 0.00 392.26 0.00 0.00
March 152.95 1491.32 577.93 0.00 577.93 0.00 0.00
April 416.06 1180.22 817.83 2.90 814.93 0.00 0.00
May 708.40 955.29 1052.34 31.26 1021.08 0.00 0.00
June 836.75 743.34 1106.51 73.07 1033.44 0.00 0.00
July 947.52 670.21 1051.68 82.46 969.22 0.00 0.00
August 793.10 659.46 851.34 23.01 828.33 0.00 0.00
September 414.66 966.62 661.29 0.20 661.10 0.00 0.00
October 134.94 1307.15 453.09 0.00 453.09 0.00 0.00
November 18.68 1663.07 285.40 0.00 285.40 0.00 0.00
December 0.66 2062.41 214.21 0.00 214.21 0.00 0.00
               
Annual Sum or Average 374.57 1295.35 644.24 17.87 626.37 0.00 0.00
Minimum of Months 0.66 659.46 214.21 0.00 214.21 0.00 0.00
Maximum of Months 947.52 2062.41 1106.51 82.46 1033.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 65.57 1290.08 270.05 68.47 201.58 0.00 0.00
February 256.99 1141.39 495.51 175.86 319.64 0.00 0.00
March 514.82 938.80 739.83 267.82 472.00 0.00 0.00
April 1038.68 738.16 1146.86 476.53 670.32 0.00 0.00
May 1176.84 623.39 1220.36 424.29 796.07 0.00 0.00
June 1542.49 495.69 1461.52 635.91 825.60 0.00 0.00
July 1524.51 437.36 1361.01 610.90 750.12 0.00 0.00
August 1564.00 423.41 1337.68 669.18 668.50 0.00 0.00
September 995.99 604.19 989.02 456.14 532.88 0.00 0.00
October 505.54 825.75 644.64 273.91 370.73 0.00 0.00
November 127.75 1063.89 315.97 89.20 226.77 0.00 0.00
December 90.71 1315.47 259.16 83.43 175.73 0.00 0.00
               
Annual Sum or Average 786.42 823.29 855.04 353.41 501.63 0.00 0.00
Minimum of Months 65.57 423.41 259.16 68.47 175.73 0.00 0.00
Maximum of Months 1564.00 1315.47 1461.52 669.18 825.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 862.52 1821.43 1113.78 661.37 452.41 0.00 0.00
February 1558.85 1647.91 1712.83 1060.26 652.57 0.00 0.00
March 1781.67 1450.37 1842.51 982.59 859.92 0.00 0.00
April 2008.80 1219.09 1945.34 844.65 1100.69 0.00 0.00
May 1852.87 1020.43 1778.77 529.91 1248.86 0.00 0.00
June 1732.34 818.02 1627.40 436.93 1190.47 0.00 0.00
July 2146.04 738.85 1774.75 650.00 1124.75 0.00 0.00
August 2418.66 709.77 1906.75 889.14 1017.60 0.00 0.00
September 2485.20 966.92 2112.59 1166.64 945.95 0.00 0.00
October 2013.96 1272.15 1913.65 1181.53 732.11 0.00 0.00
November 960.16 1538.51 1131.41 648.39 483.02 0.00 0.00
December 1040.80 1888.80 1183.78 766.07 417.71 0.00 0.00
               
Annual Sum or Average 1739.33 1255.82 1669.58 816.62 852.96 0.00 0.00
Minimum of Months 862.52 709.77 1113.78 436.93 417.71 0.00 0.00
Maximum of Months 2485.20 1888.80 2112.59 1181.53 1248.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 92.05 1299.05 284.83 83.99 200.84 0.00 0.00
February 302.54 1154.93 510.68 191.93 318.75 0.00 0.00
March 519.43 960.47 715.60 241.53 474.06 0.00 0.00
April 997.29 788.82 1088.70 416.25 672.45 0.00 0.00
May 1434.14 664.76 1400.91 569.11 831.80 0.00 0.00
June 1416.93 530.16 1347.29 523.10 824.19 0.00 0.00
July 1966.60 488.72 1664.39 874.88 789.51 0.00 0.00
August 1663.73 470.29 1376.85 703.06 673.79 0.00 0.00
September 1221.15 641.16 1121.23 537.99 583.24 0.00 0.00
October 526.97 852.13 638.32 260.08 378.24 0.00 0.00
November 141.09 1060.63 317.88 89.66 228.23 0.00 0.00
December 119.23 1322.21 267.24 91.58 175.66 0.00 0.00
               
Annual Sum or Average 870.55 851.36 896.83 383.38 513.45 0.00 0.00
Minimum of Months 92.05 470.29 267.24 83.99 175.66 0.00 0.00
Maximum of Months 1966.60 1322.21 1664.39 874.88 831.80 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 8509742.19 0.514775E+10 0.675195E+09 0.00 0.675195E+09 0.00 0.00
February 0.123878E+09 0.413226E+10 0.948948E+09 0.00 0.948948E+09 0.00 0.00
March 0.455335E+09 0.367087E+10 0.154793E+10 0.00 0.154793E+10 0.00 0.00
April 0.113385E+10 0.282156E+10 0.211981E+10 7519582.16 0.211229E+10 0.00 0.00
May 0.196087E+10 0.235559E+10 0.281859E+10 83735716.19 0.273485E+10 0.00 0.00
June 0.222453E+10 0.179033E+10 0.286807E+10 0.189395E+09 0.267868E+10 0.00 0.00
July 0.257617E+10 0.167251E+10 0.281681E+10 0.220850E+09 0.259596E+10 0.00 0.00
August 0.216773E+10 0.162339E+10 0.228023E+10 61641115.79 0.221859E+10 0.00 0.00
September 0.113824E+10 0.226299E+10 0.171407E+10 505449.15 0.171356E+10 0.00 0.00
October 0.423220E+09 0.315299E+10 0.121357E+10 0.00 0.121357E+10 0.00 0.00
November 63571532.82 0.391624E+10 0.739768E+09 0.00 0.739768E+09 0.00 0.00
December 5208766.04 0.511662E+10 0.573741E+09 0.00 0.573741E+09 0.00 0.00
               
Annual Sum or Average 0.122811E+11 0.376631E+11 0.203167E+11 0.563647E+09 0.197531E+11 0.00 0.00
Minimum of Months 5208766.04 0.162339E+10 0.573741E+09 0.00 0.573741E+09 0.00 0.00
Maximum of Months 0.257617E+10 0.514775E+10 0.286807E+10 0.220850E+09 0.273485E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.189722E+09 0.325360E+10 0.723289E+09 0.183377E+09 0.539912E+09 0.00 0.00
February 0.658285E+09 0.256690E+10 0.119873E+10 0.425452E+09 0.773277E+09 0.00 0.00
March 0.144167E+10 0.231401E+10 0.198155E+10 0.717334E+09 0.126422E+10 0.00 0.00
April 0.274849E+10 0.178165E+10 0.297265E+10 0.123517E+10 0.173748E+10 0.00 0.00
May 0.319461E+10 0.156480E+10 0.326861E+10 0.113641E+10 0.213220E+10 0.00 0.00
June 0.402275E+10 0.121367E+10 0.378825E+10 0.164829E+10 0.213997E+10 0.00 0.00
July 0.410394E+10 0.110929E+10 0.364534E+10 0.163623E+10 0.200911E+10 0.00 0.00
August 0.421802E+10 0.106529E+10 0.358285E+10 0.179234E+10 0.179051E+10 0.00 0.00
September 0.262847E+10 0.144153E+10 0.256354E+10 0.118232E+10 0.138122E+10 0.00 0.00
October 0.141902E+10 0.200975E+10 0.172661E+10 0.733643E+09 0.992967E+09 0.00 0.00
November 0.358774E+09 0.250641E+10 0.818989E+09 0.231208E+09 0.587782E+09 0.00 0.00
December 0.261581E+09 0.326407E+10 0.694147E+09 0.223465E+09 0.470682E+09 0.00 0.00
               
Annual Sum or Average 0.252453E+11 0.240910E+11 0.269646E+11 0.111452E+11 0.158193E+11 0.00 0.00
Minimum of Months 0.189722E+09 0.106529E+10 0.694147E+09 0.183377E+09 0.470682E+09 0.00 0.00
Maximum of Months 0.421802E+10 0.326407E+10 0.378825E+10 0.179234E+10 0.213997E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.235686E+10 0.457387E+10 0.298316E+10 0.177141E+10 0.121175E+10 0.00 0.00
February 0.383485E+10 0.370773E+10 0.414367E+10 0.256498E+10 0.157869E+10 0.00 0.00
March 0.482143E+10 0.359033E+10 0.493498E+10 0.263176E+10 0.230322E+10 0.00 0.00
April 0.524337E+10 0.294679E+10 0.504233E+10 0.218934E+10 0.285299E+10 0.00 0.00
May 0.498659E+10 0.254862E+10 0.476426E+10 0.141931E+10 0.334495E+10 0.00 0.00
June 0.450343E+10 0.198352E+10 0.421823E+10 0.113253E+10 0.308570E+10 0.00 0.00
July 0.575282E+10 0.185538E+10 0.475350E+10 0.174097E+10 0.301253E+10 0.00 0.00
August 0.649317E+10 0.176849E+10 0.510703E+10 0.238148E+10 0.272555E+10 0.00 0.00
September 0.648218E+10 0.230469E+10 0.547584E+10 0.302393E+10 0.245191E+10 0.00 0.00
October 0.545928E+10 0.310904E+10 0.512551E+10 0.316462E+10 0.196090E+10 0.00 0.00
November 0.255200E+10 0.364779E+10 0.293262E+10 0.168063E+10 0.125199E+10 0.00 0.00
December 0.284509E+10 0.468746E+10 0.317064E+10 0.205184E+10 0.111880E+10 0.00 0.00
               
Annual Sum or Average 0.553311E+11 0.367237E+11 0.526517E+11 0.257528E+11 0.268989E+11 0.00 0.00
Minimum of Months 0.235686E+10 0.176849E+10 0.293262E+10 0.113253E+10 0.111880E+10 0.00 0.00
Maximum of Months 0.649317E+10 0.468746E+10 0.547584E+10 0.316462E+10 0.334495E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.255434E+09 0.327621E+10 0.762895E+09 0.224963E+09 0.537932E+09 0.00 0.00
February 0.751086E+09 0.260232E+10 0.123544E+10 0.464312E+09 0.771130E+09 0.00 0.00
March 0.141125E+10 0.237661E+10 0.191665E+10 0.646918E+09 0.126974E+10 0.00 0.00
April 0.260092E+10 0.190412E+10 0.282192E+10 0.107892E+10 0.174300E+10 0.00 0.00
May 0.385344E+10 0.165879E+10 0.375219E+10 0.152430E+10 0.222789E+10 0.00 0.00
June 0.367828E+10 0.128424E+10 0.349218E+10 0.135589E+10 0.213629E+10 0.00 0.00
July 0.526801E+10 0.122552E+10 0.445791E+10 0.234329E+10 0.211461E+10 0.00 0.00
August 0.446691E+10 0.117139E+10 0.368776E+10 0.188306E+10 0.180469E+10 0.00 0.00
September 0.318844E+10 0.152718E+10 0.290624E+10 0.139447E+10 0.151177E+10 0.00 0.00
October 0.144237E+10 0.208363E+10 0.170968E+10 0.696610E+09 0.101307E+10 0.00 0.00
November 0.382258E+09 0.251190E+10 0.823946E+09 0.232386E+09 0.591560E+09 0.00 0.00
December 0.331130E+09 0.328423E+10 0.715776E+09 0.245277E+09 0.470499E+09 0.00 0.00
               
Annual Sum or Average 0.276295E+11 0.249062E+11 0.282826E+11 0.120904E+11 0.161922E+11 0.00 0.00
Minimum of Months 0.255434E+09 0.117139E+10 0.715776E+09 0.224963E+09 0.470499E+09 0.00 0.00
Maximum of Months 0.526801E+10 0.328423E+10 0.445791E+10 0.234329E+10 0.222789E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 5655471.74 0.537024E+10 0.675191E+09 0.00 0.675191E+09 0.00 0.00
February 0.121671E+09 0.430276E+10 0.948943E+09 0.00 0.948943E+09 0.00 0.00
March 0.489538E+09 0.379582E+10 0.154792E+10 0.00 0.154792E+10 0.00 0.00
April 0.121870E+10 0.285666E+10 0.211980E+10 7519538.65 0.211228E+10 0.00 0.00
May 0.206538E+10 0.239959E+10 0.281857E+10 83735231.71 0.273484E+10 0.00 0.00
June 0.230878E+10 0.182681E+10 0.286806E+10 0.189393E+09 0.267866E+10 0.00 0.00
July 0.264016E+10 0.171830E+10 0.281680E+10 0.220849E+09 0.259595E+10 0.00 0.00
August 0.220123E+10 0.170222E+10 0.228022E+10 61640759.14 0.221858E+10 0.00 0.00
September 0.113208E+10 0.245106E+10 0.171406E+10 505446.22 0.171355E+10 0.00 0.00
October 0.387489E+09 0.347975E+10 0.121356E+10 0.00 0.121356E+10 0.00 0.00
November 51196465.87 0.433434E+10 0.739764E+09 0.00 0.739764E+09 0.00 0.00
December 1908454.56 0.550836E+10 0.573738E+09 0.00 0.573738E+09 0.00 0.00
               
Annual Sum or Average 0.126238E+11 0.397459E+11 0.203166E+11 0.563643E+09 0.197530E+11 0.00 0.00
Minimum of Months 1908454.56 0.170222E+10 0.573738E+09 0.00 0.573738E+09 0.00 0.00
Maximum of Months 0.264016E+10 0.550836E+10 0.286806E+10 0.220849E+09 0.273484E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.185523E+09 0.339385E+10 0.723314E+09 0.183384E+09 0.539930E+09 0.00 0.00
February 0.654953E+09 0.268361E+10 0.119877E+10 0.425469E+09 0.773302E+09 0.00 0.00
March 0.147170E+10 0.241632E+10 0.198162E+10 0.717363E+09 0.126426E+10 0.00 0.00
April 0.280381E+10 0.184588E+10 0.297276E+10 0.123522E+10 0.173753E+10 0.00 0.00
May 0.325877E+10 0.162082E+10 0.326872E+10 0.113646E+10 0.213226E+10 0.00 0.00
June 0.407648E+10 0.127560E+10 0.378838E+10 0.164835E+10 0.214003E+10 0.00 0.00
July 0.414993E+10 0.116242E+10 0.364546E+10 0.163629E+10 0.200917E+10 0.00 0.00
August 0.424145E+10 0.114653E+10 0.358298E+10 0.179241E+10 0.179057E+10 0.00 0.00
September 0.262576E+10 0.157977E+10 0.256363E+10 0.118237E+10 0.138126E+10 0.00 0.00
October 0.139293E+10 0.223030E+10 0.172667E+10 0.733673E+09 0.992998E+09 0.00 0.00
November 0.343834E+09 0.276747E+10 0.819018E+09 0.231217E+09 0.587801E+09 0.00 0.00
December 0.251191E+09 0.351065E+10 0.694171E+09 0.223474E+09 0.470697E+09 0.00 0.00
               
Annual Sum or Average 0.254563E+11 0.256332E+11 0.269655E+11 0.111457E+11 0.158198E+11 0.00 0.00
Minimum of Months 0.185523E+09 0.114653E+10 0.694171E+09 0.183384E+09 0.470697E+09 0.00 0.00
Maximum of Months 0.424145E+10 0.351065E+10 0.378838E+10 0.179241E+10 0.214003E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.237995E+10 0.478472E+10 0.298317E+10 0.177142E+10 0.121175E+10 0.00 0.00
February 0.388167E+10 0.393827E+10 0.414369E+10 0.256500E+10 0.157869E+10 0.00 0.00
March 0.492714E+10 0.380286E+10 0.493500E+10 0.263178E+10 0.230322E+10 0.00 0.00
April 0.538642E+10 0.304765E+10 0.504235E+10 0.218935E+10 0.285300E+10 0.00 0.00
May 0.514999E+10 0.261856E+10 0.476428E+10 0.141932E+10 0.334496E+10 0.00 0.00
June 0.465244E+10 0.203087E+10 0.421824E+10 0.113254E+10 0.308570E+10 0.00 0.00
July 0.586052E+10 0.194099E+10 0.475352E+10 0.174098E+10 0.301253E+10 0.00 0.00
August 0.656548E+10 0.190962E+10 0.510705E+10 0.238149E+10 0.272556E+10 0.00 0.00
September 0.650800E+10 0.257257E+10 0.547586E+10 0.302394E+10 0.245192E+10 0.00 0.00
October 0.546470E+10 0.351515E+10 0.512554E+10 0.316464E+10 0.196090E+10 0.00 0.00
November 0.253670E+10 0.404017E+10 0.293263E+10 0.168064E+10 0.125199E+10 0.00 0.00
December 0.284117E+10 0.504040E+10 0.317065E+10 0.205185E+10 0.111880E+10 0.00 0.00
               
Annual Sum or Average 0.561542E+11 0.392418E+11 0.526520E+11 0.257530E+11 0.268990E+11 0.00 0.00
Minimum of Months 0.237995E+10 0.190962E+10 0.293263E+10 0.113254E+10 0.111880E+10 0.00 0.00
Maximum of Months 0.656548E+10 0.504040E+10 0.547586E+10 0.316464E+10 0.334496E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.258067E+09 0.342115E+10 0.762920E+09 0.224971E+09 0.537949E+09 0.00 0.00
February 0.763867E+09 0.273151E+10 0.123548E+10 0.464329E+09 0.771153E+09 0.00 0.00
March 0.145872E+10 0.248771E+10 0.191671E+10 0.646943E+09 0.126977E+10 0.00 0.00
April 0.268363E+10 0.196448E+10 0.282201E+10 0.107896E+10 0.174305E+10 0.00 0.00
May 0.394035E+10 0.173486E+10 0.375231E+10 0.152436E+10 0.222795E+10 0.00 0.00
June 0.375353E+10 0.134294E+10 0.349228E+10 0.135594E+10 0.213635E+10 0.00 0.00
July 0.532283E+10 0.131726E+10 0.445805E+10 0.234338E+10 0.211467E+10 0.00 0.00
August 0.450111E+10 0.127074E+10 0.368787E+10 0.188314E+10 0.180474E+10 0.00 0.00
September 0.319491E+10 0.168676E+10 0.290633E+10 0.139452E+10 0.151181E+10 0.00 0.00
October 0.143478E+10 0.230539E+10 0.170974E+10 0.696637E+09 0.101310E+10 0.00 0.00
November 0.373779E+09 0.277599E+10 0.823973E+09 0.232395E+09 0.591578E+09 0.00 0.00
December 0.328133E+09 0.354006E+10 0.715799E+09 0.245286E+09 0.470513E+09 0.00 0.00
               
Annual Sum or Average 0.280137E+11 0.265789E+11 0.282835E+11 0.120909E+11 0.161926E+11 0.00 0.00
Minimum of Months 0.258067E+09 0.127074E+10 0.715799E+09 0.224971E+09 0.470513E+09 0.00 0.00
Maximum of Months 0.532283E+10 0.354006E+10 0.445805E+10 0.234338E+10 0.222795E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 3827537.30 0.546707E+10 0.675195E+09 0.00 0.675195E+09 0.00 0.00
February 0.105796E+09 0.444155E+10 0.948948E+09 0.00 0.948948E+09 0.00 0.00
March 0.409652E+09 0.399434E+10 0.154793E+10 0.00 0.154793E+10 0.00 0.00
April 0.107842E+10 0.305913E+10 0.211981E+10 7519582.16 0.211229E+10 0.00 0.00
May 0.189739E+10 0.255864E+10 0.281859E+10 83735716.19 0.273485E+10 0.00 0.00
June 0.216886E+10 0.192675E+10 0.286807E+10 0.189395E+09 0.267868E+10 0.00 0.00
July 0.253784E+10 0.179509E+10 0.281681E+10 0.220850E+09 0.259596E+10 0.00 0.00
August 0.212424E+10 0.176630E+10 0.228023E+10 61641115.79 0.221859E+10 0.00 0.00
September 0.107479E+10 0.250549E+10 0.171407E+10 505449.15 0.171356E+10 0.00 0.00
October 0.361436E+09 0.350108E+10 0.121357E+10 0.00 0.121357E+10 0.00 0.00
November 48414290.65 0.431068E+10 0.739768E+09 0.00 0.739768E+09 0.00 0.00
December 1770411.31 0.552395E+10 0.573741E+09 0.00 0.573741E+09 0.00 0.00
               
Annual Sum or Average 0.118124E+11 0.408501E+11 0.203167E+11 0.563647E+09 0.197531E+11 0.00 0.00
Minimum of Months 1770411.31 0.176630E+10 0.573741E+09 0.00 0.573741E+09 0.00 0.00
Maximum of Months 0.253784E+10 0.552395E+10 0.286807E+10 0.220850E+09 0.273485E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.175618E+09 0.345534E+10 0.723289E+09 0.183377E+09 0.539912E+09 0.00 0.00
February 0.621712E+09 0.276126E+10 0.119873E+10 0.425452E+09 0.773277E+09 0.00 0.00
March 0.137889E+10 0.251449E+10 0.198155E+10 0.717334E+09 0.126422E+10 0.00 0.00
April 0.269225E+10 0.191330E+10 0.297265E+10 0.123517E+10 0.173748E+10 0.00 0.00
May 0.315205E+10 0.166970E+10 0.326861E+10 0.113641E+10 0.213220E+10 0.00 0.00
June 0.399814E+10 0.128484E+10 0.378825E+10 0.164829E+10 0.213997E+10 0.00 0.00
July 0.408325E+10 0.117143E+10 0.364534E+10 0.163623E+10 0.200911E+10 0.00 0.00
August 0.418902E+10 0.113407E+10 0.358285E+10 0.179234E+10 0.179051E+10 0.00 0.00
September 0.258160E+10 0.156607E+10 0.256354E+10 0.118232E+10 0.138122E+10 0.00 0.00
October 0.135404E+10 0.221169E+10 0.172661E+10 0.733643E+09 0.992967E+09 0.00 0.00
November 0.331137E+09 0.275759E+10 0.818989E+09 0.231208E+09 0.587782E+09 0.00 0.00
December 0.242944E+09 0.352335E+10 0.694147E+09 0.223465E+09 0.470682E+09 0.00 0.00
               
Annual Sum or Average 0.248007E+11 0.259631E+11 0.269646E+11 0.111452E+11 0.158193E+11 0.00 0.00
Minimum of Months 0.175618E+09 0.113407E+10 0.694147E+09 0.183377E+09 0.470682E+09 0.00 0.00
Maximum of Months 0.418902E+10 0.352335E+10 0.378825E+10 0.179234E+10 0.213997E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.231017E+10 0.487853E+10 0.298316E+10 0.177141E+10 0.121175E+10 0.00 0.00
February 0.377116E+10 0.398663E+10 0.414367E+10 0.256498E+10 0.157869E+10 0.00 0.00
March 0.477202E+10 0.388466E+10 0.493498E+10 0.263176E+10 0.230322E+10 0.00 0.00
April 0.520681E+10 0.315988E+10 0.504233E+10 0.218934E+10 0.285299E+10 0.00 0.00
May 0.496273E+10 0.273311E+10 0.476426E+10 0.141931E+10 0.334495E+10 0.00 0.00
June 0.449022E+10 0.212030E+10 0.421823E+10 0.113253E+10 0.308570E+10 0.00 0.00
July 0.574796E+10 0.197894E+10 0.475350E+10 0.174097E+10 0.301253E+10 0.00 0.00
August 0.647815E+10 0.190105E+10 0.510703E+10 0.238148E+10 0.272555E+10 0.00 0.00
September 0.644163E+10 0.250626E+10 0.547584E+10 0.302393E+10 0.245191E+10 0.00 0.00
October 0.539420E+10 0.340734E+10 0.512551E+10 0.316462E+10 0.196090E+10 0.00 0.00
November 0.248874E+10 0.398782E+10 0.293262E+10 0.168063E+10 0.125199E+10 0.00 0.00
December 0.278767E+10 0.505897E+10 0.317064E+10 0.205184E+10 0.111880E+10 0.00 0.00
               
Annual Sum or Average 0.548514E+11 0.396035E+11 0.526517E+11 0.257528E+11 0.268989E+11 0.00 0.00
Minimum of Months 0.231017E+10 0.190105E+10 0.293262E+10 0.113253E+10 0.111880E+10 0.00 0.00
Maximum of Months 0.647815E+10 0.505897E+10 0.547584E+10 0.316462E+10 0.334495E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.246560E+09 0.347939E+10 0.762895E+09 0.224963E+09 0.537932E+09 0.00 0.00
February 0.731914E+09 0.279402E+10 0.123544E+10 0.464312E+09 0.771130E+09 0.00 0.00
March 0.139124E+10 0.257251E+10 0.191665E+10 0.646918E+09 0.126974E+10 0.00 0.00
April 0.258497E+10 0.204463E+10 0.282192E+10 0.107892E+10 0.174300E+10 0.00 0.00
May 0.384120E+10 0.178051E+10 0.375219E+10 0.152430E+10 0.222789E+10 0.00 0.00
June 0.367268E+10 0.137417E+10 0.349218E+10 0.135589E+10 0.213629E+10 0.00 0.00
July 0.526734E+10 0.130898E+10 0.445791E+10 0.234329E+10 0.211461E+10 0.00 0.00
August 0.445614E+10 0.125964E+10 0.368776E+10 0.188306E+10 0.180469E+10 0.00 0.00
September 0.316523E+10 0.166188E+10 0.290624E+10 0.139447E+10 0.151177E+10 0.00 0.00
October 0.141144E+10 0.228234E+10 0.170968E+10 0.696610E+09 0.101307E+10 0.00 0.00
November 0.365713E+09 0.274916E+10 0.823946E+09 0.232386E+09 0.591560E+09 0.00 0.00
December 0.319347E+09 0.354140E+10 0.715776E+09 0.245277E+09 0.470499E+09 0.00 0.00
               
Annual Sum or Average 0.274538E+11 0.268486E+11 0.282826E+11 0.120904E+11 0.161922E+11 0.00 0.00
Minimum of Months 0.246560E+09 0.125964E+10 0.715776E+09 0.224963E+09 0.470499E+09 0.00 0.00
Maximum of Months 0.526734E+10 0.354140E+10 0.445791E+10 0.234329E+10 0.222789E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.50 3.10 1.22 3.91 -4.2 29.50 44.23 0.00
February 5.82 4.07 1.77 3.94 -3.8 43.80 82.64 0.00
March 8.33 5.86 2.94 3.85 -1.4 65.55 100.60 0.02
April 10.85 8.04 5.25 4.23 1.22 89.73 150.02 0.00
May 12.97 10.02 7.49 3.85 3.75 114.98 168.60 0.00
June 15.59 11.80 8.88 4.02 5.93 107.53 199.74 0.01
July 17.66 13.41 10.38 3.76 8.02 92.25 247.81 0.00
August 18.80 14.57 11.86 3.84 8.90 79.20 215.47 0.01
September 15.09 12.55 10.74 2.23 5.47 68.06 162.11 0.01
October 11.43 9.19 7.19 4.02 2.10 48.18 106.36 0.04
November 8.07 6.72 5.29 3.86 0.13 33.26 46.10 0.00
December 5.42 4.09 2.46 3.51 -3.8 24.03 50.49 0.04
                 
Annual Sum or Average 11.24 8.64 6.31 3.75 1.89 66.43 131.49 0.01
Minimum of Months 4.50 3.10 1.22 2.23 -4.2 24.03 44.23 0.00
Maximum of Months 18.80 14.57 11.86 4.23 8.90 114.98 247.81 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.40 11-JAN-14:20 10.49 7.20 8.40 3.89 99.17 130.33
February 20.00 27-FEB-14:00 12.17 5.60 2.60 5.54 87.00 691.00
March 20.60 18-MAR-15:00 10.43 0.00 6.20 6.55 111.50 465.50
April 27.20 27-APR-15:09 17.22 11.02 4.10 12.63 151.33 598.33
May 25.00 05-MAY-15:00 17.36 12.80 2.60 18.99 208.50 29.50
June 26.70 28-JUN-16:00 16.74 10.60 3.10 11.84 131.50 527.00
July 30.60 24-JUL-14:00 18.78 12.20 3.10 20.75 267.00 383.50
August 31.80 10-AUG-16:00 18.70 11.10 2.60 16.85 50.50 750.50
September 25.00 14-SEP-16:00 16.69 11.70 3.10 13.54 100.50 235.00
October 21.70 04-OCT-14:00 11.49 1.70 5.20 4.92 56.50 783.50
November 21.10 04-NOV-13:00 15.94 12.80 0.00 6.95 52.50 729.00
December 13.30 14-DEC-11:00 8.44 3.60 13.90 5.33 127.50 85.00
                 
Annual Sum or Average                
Minimum of Months 13.30   8.44 0.00 0.00 3.89 50.50 29.50
Maximum of Months 31.80   18.78 12.80 13.90 20.75 267.00 783.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -3.9 07-JAN-07:00 -3.9 -3.9 2.10 -14.4 0.00 0.00
February -5.6 19-FEB-05:10 -6.1 -7.3 3.77 -22.8 0.00 0.00
March -0.6 01-MAR-06:00 -2.0 -3.9 1.50 -17.3 16.50 102.00
April 1.70 19-APR-04:00 1.21 0.60 3.10 -11.9 0.00 0.00
May 4.40 11-MAY-02:00 3.92 3.30 3.10 -10.9 0.00 0.00
June 8.30 15-JUN-02:00 7.50 6.70 3.10 -3.2 0.00 0.00
July 11.10 03-JUL-03:00 8.19 5.00 2.60 5.54 0.00 0.00
August 11.00 06-AUG-04:00 10.57 10.20 2.60 -3.2 11.00 135.50
September 7.20 27-SEP-04:49 6.72 6.20 0.25 -4.0 0.00 0.00
October 5.60 13-OCT-04:00 4.51 3.30 2.10 -8.5 0.00 0.00
November 0.00 11-NOV-06:00 -0.2 -0.6 2.10 -16.0 0.00 0.00
December -1.7 26-DEC-06:00 -1.7 -1.7 2.10 -15.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -6.1 -7.3 0.25 -22.8 0.00 0.00
Maximum of Months 11.10   10.57 10.20 3.77 5.54 16.50 135.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.49 11-JAN-13:00 14.40 7.20 8.20 2.85 105.50 249.00
February 12.42 27-FEB-15:00 19.40 6.70 2.60 6.35 88.00 342.50
March 12.45 09-MAR-11:00 17.20 8.90 2.10 12.41 178.00 40.00
April 17.29 27-APR-14:00 27.20 11.10 4.10 12.41 147.50 646.00
May 17.58 06-MAY-12:00 23.90 13.90 5.20 15.57 365.50 282.50
June 16.74 28-JUN-16:00 26.70 10.60 3.10 11.84 131.50 527.00
July 19.18 31-JUL-15:00 28.90 13.90 4.10 14.65 45.00 848.50
August 20.13 29-AUG-12:00 28.90 15.70 2.60 17.39 136.50 655.00
September 17.97 23-SEP-13:00 23.30 15.00 2.10 9.72 148.00 670.50
October 15.15 01-OCT-11:00 17.20 13.90 4.60 13.73 236.50 63.50
November 16.05 04-NOV-12:00 20.60 13.30 0.00 7.95 62.00 746.50
December 10.71 16-DEC-11:00 11.70 10.00 6.70 7.35 89.50 0.00
                 
Annual Sum or Average                
Minimum of Months 10.49   11.70 6.70 0.00 2.85 45.00 0.00
Maximum of Months 20.13   28.90 15.70 8.20 17.39 365.50 848.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.00 11-JAN-21:00 11.10 10.49 4.60 6.75 0.00 0.00
February 11.70 24-FEB-00:00 12.80 12.15 4.10 8.74 0.00 0.00
March 11.70 09-MAR-16:00 12.80 12.15 2.10 8.74 37.50 0.00
April 12.80 28-APR-12:00 16.70 14.35 4.10 8.35 265.50 596.00
May 13.90 05-MAY-16:00 22.80 17.10 2.60 19.17 111.50 27.50
June 13.90 12-JUN-12:00 16.70 15.00 3.60 13.16 263.50 0.00
July 15.00 11-JUL-09:20 16.13 15.49 4.60 12.91 204.17 28.17
August 16.40 30-AUG-07:00 17.40 16.77 5.20 12.41 168.50 34.50
September 15.00 14-SEP-11:20 20.37 16.93 2.10 6.89 152.83 748.17
October 13.90 01-OCT-10:00 16.70 15.01 4.10 13.16 184.50 0.00
November 13.90 03-NOV-19:00 15.00 14.31 4.60 11.46 0.00 0.00
December 10.00 16-DEC-10:00 11.10 10.48 7.70 6.75 81.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.00   11.10 10.48 2.10 6.75 0.00 0.00
Maximum of Months 16.40   22.80 17.10 7.70 19.17 265.50 748.17



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.48 8.35 0.00
February 18.00 13.00 16.00 11.14 14.81 0.00
March 18.00 13.00 16.00 11.69 23.26 0.00
April 18.00 13.00 16.00 12.99 36.00 0.00
May 18.00 13.00 16.00 14.72 45.46 0.00
June 18.00 13.00 16.00 16.40 49.26 0.00
July 18.00 13.00 16.00 17.58 51.50 0.00
August 18.00 13.00 16.00 17.95 42.11 0.00
September 18.00 13.00 16.00 17.39 30.76 0.00
October 18.00 13.00 16.00 16.06 18.91 0.00
November 18.00 13.00 16.00 14.32 9.65 0.00
December 18.00 13.00 16.00 12.65 7.39 0.00
             
Annual Sum or Average 18.00 13.00 16.00 14.55 28.19 0.00
Minimum of Months 18.00 13.00 16.00 11.14 7.39 0.00
Maximum of Months 18.00 13.00 16.00 17.95 51.50 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.483074E+10 -0.458408E+10 0.00 0.00 744.00 0.00 -246655947.1 60.05 0.00 0.00
February 0.441240E+10 -0.419457E+10 0.00 0.00 672.00 0.00 -217832976.4 60.05 0.00 0.00
March 0.514811E+10 -0.491064E+10 0.00 0.00 744.00 0.00 -237465150.2 60.05 0.00 0.00
April 0.452724E+10 -0.429981E+10 0.00 0.00 720.00 0.00 -227430763.6 60.05 0.00 0.00
May 0.467774E+10 -0.444432E+10 0.00 0.00 744.00 0.00 -233418914.7 60.05 0.00 0.00
June 0.447746E+10 -0.425257E+10 0.00 0.00 720.00 0.00 -224889697.3 60.05 0.00 0.00
July 0.412879E+10 -0.389744E+10 0.00 0.00 744.00 0.00 -231356236.2 60.05 0.00 0.00
August 0.450673E+10 -0.427461E+10 0.00 0.00 744.00 0.00 -232115902.9 60.05 0.00 0.00
September 0.412374E+10 -0.389919E+10 0.00 0.00 720.00 0.00 -224548544.0 60.05 0.00 0.00
October 0.438694E+10 -0.415238E+10 0.00 0.00 744.00 0.00 -234562126.3 60.05 0.00 0.00
November 0.447395E+10 -0.424363E+10 0.00 0.00 720.00 0.00 -230316246.0 60.05 0.00 0.00
December 0.459238E+10 -0.435083E+10 0.00 0.00 744.00 0.00 -241550088.3 60.05 0.00 0.00
                     
Annual Sum or Average 0.542862E+11 -0.515041E+11 0.00 0.00 8760.00 0.00 -0.278214E+10 60.05 0.00 0.00
Minimum of Months 0.412374E+10 -0.491064E+10 0.00 0.00 672.00 0.00 -246655947.1 60.05 0.00 0.00
Maximum of Months 0.514811E+10 -0.389744E+10 0.00 0.00 744.00 0.00 -217832976.4 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 237.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 259.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 247.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 379.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 427.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 375.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 471.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 366.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 301.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 245.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 242.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 160.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 3714.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 160.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 471.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT HEATING COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.567321E+09 7025.43 07-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.229779E+09 5148.86 18-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 1058253.83 945.84 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 17934.98 4.13 27-APR-17:00 0.00 0.00 0.00 0.00 0.00
May 26765.30 4.02 05-MAY-14:30 0.00 0.00 0.00 0.00 0.00
June 608.57 1.01 21-JUN-17:00 0.00 0.00 0.00 0.00 0.00
July 476620.53 5.80 24-JUL-16:00 0.00 0.00 0.00 0.00 0.00
August 1081292.01 6.16 10-AUG-14:50 0.00 0.00 0.00 0.00 0.00
September 271283.34 5.66 14-SEP-15:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 20487225.51 2671.28 13-NOV-08:08 0.00 0.00 0.00 0.00 0.00
December 0.201703E+09 6821.90 26-DEC-08:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102222E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.567321E+09 7025.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.436086E+09 13367.84 03-JAN-07:08 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.436086E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.436086E+09 13367.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.644224E+10 10217.20 03-JAN-07:17 0.00 0.00 0.00 0.00 0.00
February 0.418208E+10 10193.21 24-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.327865E+10 10193.25 10-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.184533E+10 10187.68 04-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.109096E+10 10207.34 17-MAY-06:07 0.00 0.00 0.00 0.00 0.00
June 0.570760E+09 10221.53 06-JUN-06:07 0.00 0.00 0.00 0.00 0.00
July 0.225404E+09 7112.16 10-JUL-06:07 0.00 0.00 0.00 0.00 0.00
August 0.189029E+09 7552.77 18-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 0.510969E+09 10193.01 20-SEP-06:07 0.00 0.00 0.00 0.00 0.00
October 0.149727E+10 10213.04 05-OCT-06:07 0.00 0.00 0.00 0.00 0.00
November 0.377693E+10 10191.37 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.527530E+10 10186.99 29-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.288849E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.189029E+09 7112.16   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.644224E+10 10221.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.292549E+10 6748.88 17-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.175140E+10 6738.13 10-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.983055E+09 6736.17 14-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.288926E+09 6716.28 04-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 59451848.89 5349.83 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 1473870.76 1865.17 14-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 14695177.69 4333.48 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.300930E+09 6717.66 27-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.112990E+10 6735.88 27-NOV-06:12 0.00 0.00 0.00 0.00 0.00
December 0.218310E+10 6737.92 26-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.963842E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.292549E+10 6748.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.367252E+10 8455.14 04-JAN-07:04 0.00 0.00 0.00 0.00 0.00
February 0.226102E+10 8439.73 07-FEB-06:13 0.00 0.00 0.00 0.00 0.00
March 0.125439E+10 8437.29 27-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.449394E+09 8402.72 07-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 29481258.90 6876.18 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 3617054.69 2971.74 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.240736E+09 8399.49 27-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.110943E+10 8422.09 13-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.256223E+10 8439.54 05-DEC-06:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.115828E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.367252E+10 8455.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.318512E+10 7155.64 17-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.201257E+10 7141.41 11-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.131514E+10 7136.11 13-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.549865E+09 7123.98 07-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 92028849.15 5445.63 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 7532290.01 2200.57 07-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 17123379.08 4337.54 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.433314E+09 7121.47 27-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.138189E+10 7140.84 27-NOV-06:12 0.00 0.00 0.00 0.00 0.00
December 0.243721E+10 7142.48 02-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114318E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.318512E+10 7155.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID HEATING COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.247350E+10 10095.44 07-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.163376E+10 9416.83 18-FEB-07:08 0.00 0.00 0.00 0.00 0.00
March 0.164511E+09 6164.43 01-MAR-07:06 0.00 0.00 0.00 0.00 0.00
April 34101002.05 3694.58 19-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 32534.02 4.13 31-MAY-15:20 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 418554.14 4.99 31-JUL-12:40 0.00 0.00 0.00 0.00 0.00
August 914460.27 5.74 09-AUG-15:40 0.00 0.00 0.00 0.00 0.00
September 238851.43 5.34 12-SEP-14:05 0.00 0.00 0.00 0.00 0.00
October 399690.75 229.01 16-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.448267E+09 7449.69 13-NOV-08:00 0.00 0.00 0.00 0.00 0.00
December 0.151654E+10 10303.97 26-DEC-08:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.627268E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.247350E+10 10303.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.137696E+10 19713.17 04-JAN-07:04 0.00 0.00 0.00 0.00 0.00
February 0.319167E+09 19728.56 22-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 35769641.83 19723.55 06-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.128343E+09 19740.28 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.484689E+09 19724.66 27-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.234493E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137696E+10 19740.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.345590E+10 11100.61 03-JAN-06:13 0.00 0.00 0.00 0.00 0.00
February 0.195797E+10 11091.27 17-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.102020E+10 11066.31 06-MAR-06:14 0.00 0.00 0.00 0.00 0.00
April 0.414893E+09 11036.79 21-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 89148069.75 8404.28 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 7236974.76 3954.72 14-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 40674384.11 7740.74 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.526793E+09 11020.28 27-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.176207E+10 11072.57 27-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.283659E+10 11102.07 21-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121115E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.345590E+10 11102.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.261574E+10 7632.88 03-JAN-06:13 0.00 0.00 0.00 0.00 0.00
February 0.154999E+10 7626.71 17-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.848424E+09 7616.98 27-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.267683E+09 7582.29 12-APR-05:11 0.00 0.00 0.00 0.00 0.00
May 64624123.20 5497.32 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 4688472.75 3468.35 14-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 34697.58 142.05 18-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 44519596.74 5232.05 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.489544E+09 7584.41 30-OCT-05:11 0.00 0.00 0.00 0.00 0.00
November 0.137752E+10 7621.30 20-NOV-06:12 0.00 0.00 0.00 0.00 0.00
December 0.218415E+10 7630.52 18-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.944692E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.261574E+10 7632.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.315784E+10 8737.50 05-JAN-07:04 0.00 0.00 0.00 0.00 0.00
February 0.175409E+10 8737.46 15-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.736095E+09 8714.00 13-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 0.217689E+09 8651.10 19-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 11725454.76 6782.19 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 6048243.03 4428.69 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.304293E+09 8654.58 30-OCT-05:11 0.00 0.00 0.00 0.00 0.00
November 0.128640E+10 8738.43 28-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.248561E+10 8738.73 18-DEC-07:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.995979E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.315784E+10 8738.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.308890E+10 7724.61 03-JAN-06:13 0.00 0.00 0.00 0.00 0.00
February 0.191823E+10 7718.56 17-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.112744E+10 7700.78 06-MAR-06:14 0.00 0.00 0.00 0.00 0.00
April 0.452688E+09 7678.69 22-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 98160543.11 5633.58 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 10511541.94 3370.61 14-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 118511.19 284.35 18-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 54244846.33 5235.02 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.638164E+09 7675.52 30-OCT-05:11 0.00 0.00 0.00 0.00 0.00
November 0.171430E+10 7712.88 20-NOV-06:12 0.00 0.00 0.00 0.00 0.00
December 0.262418E+10 7722.29 18-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.117269E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.308890E+10 7724.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP HEATING COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.289952E+10 9070.42 06-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.195341E+10 9060.40 08-FEB-07:12 0.00 0.00 0.00 0.00 0.00
March 0.429825E+09 8737.68 01-MAR-07:06 0.00 0.00 0.00 0.00 0.00
April 0.114515E+09 6867.21 19-APR-06:07 0.00 0.00 0.00 0.00 0.00
May 5139318.15 1734.90 18-MAY-06:07 0.00 0.00 0.00 0.00 0.00
June 1383.64 2.31 28-JUN-16:00 0.00 0.00 0.00 0.00 0.00
July 492965.70 6.04 31-JUL-13:30 0.00 0.00 0.00 0.00 0.00
August 942298.09 6.20 29-AUG-14:30 0.00 0.00 0.00 0.00 0.00
September 209737.88 5.61 14-SEP-14:20 0.00 0.00 0.00 0.00 0.00
October 21184878.51 2297.41 16-OCT-06:08 0.00 0.00 0.00 0.00 0.00
November 0.609324E+09 8011.41 13-NOV-08:00 0.00 0.00 0.00 0.00 0.00
December 0.195450E+10 8985.69 26-DEC-08:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.798905E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1383.64 2.31   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.289952E+10 9070.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.514611E+10 28363.23 03-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.267016E+10 28363.35 22-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.907067E+09 28350.10 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.220537E+09 28354.64 19-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 1980036.03 5642.68 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 1716770.27 3494.82 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.355773E+09 28057.89 16-OCT-05:11 0.00 0.00 0.00 0.00 0.00
November 0.202110E+10 28349.62 27-NOV-06:16 0.00 0.00 0.00 0.00 0.00
December 0.409172E+10 28335.76 26-DEC-05:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.154162E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.514611E+10 28363.35   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.539891E+10 13111.85 18-JAN-06:17 0.00 0.00 0.00 0.00 0.00
February 0.345812E+10 13109.69 22-FEB-06:14 0.00 0.00 0.00 0.00 0.00
March 0.223974E+10 13104.00 13-MAR-05:14 0.00 0.00 0.00 0.00 0.00
April 0.110798E+10 13067.89 17-APR-05:13 0.00 0.00 0.00 0.00 0.00
May 0.449513E+09 13009.45 18-MAY-05:12 0.00 0.00 0.00 0.00 0.00
June 0.123810E+09 8616.16 14-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 16944265.82 4056.82 18-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 44079437.16 6239.96 03-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 0.315710E+09 9656.81 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.142179E+10 13107.48 23-OCT-05:13 0.00 0.00 0.00 0.00 0.00
November 0.326650E+10 13111.13 24-NOV-07:08 0.00 0.00 0.00 0.00 0.00
December 0.473836E+10 13102.50 20-DEC-06:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.225815E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 16944265.82 4056.82   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.539891E+10 13111.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.413772E+10 8501.60 21-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.265804E+10 8506.49 06-FEB-06:17 0.00 0.00 0.00 0.00 0.00
March 0.157478E+10 8487.54 13-MAR-05:14 0.00 0.00 0.00 0.00 0.00
April 0.605033E+09 8464.20 17-APR-05:13 0.00 0.00 0.00 0.00 0.00
May 0.225026E+09 8426.35 18-MAY-05:12 0.00 0.00 0.00 0.00 0.00
June 43049894.89 5529.30 14-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 2203220.74 1103.25 13-JUL-06:05 0.00 0.00 0.00 0.00 0.00
August 10352270.90 4082.48 18-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 0.203690E+09 6188.64 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.108199E+10 8489.88 23-OCT-05:13 0.00 0.00 0.00 0.00 0.00
November 0.242241E+10 8496.06 24-NOV-07:15 0.00 0.00 0.00 0.00 0.00
December 0.363660E+10 8507.00 11-DEC-06:26 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.166009E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2203220.74 1103.25   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.413772E+10 8507.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.566998E+10 11343.54 06-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.376861E+10 11267.34 14-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.225368E+10 11273.64 06-MAR-06:26 0.00 0.00 0.00 0.00 0.00
April 0.963279E+09 11239.00 19-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 0.239671E+09 11156.92 18-MAY-05:12 0.00 0.00 0.00 0.00 0.00
June 30182346.62 7930.23 14-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 9314531.38 3141.49 03-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 0.197425E+09 9557.62 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.136946E+10 11244.58 16-OCT-05:14 0.00 0.00 0.00 0.00 0.00
November 0.310645E+10 11272.22 13-NOV-07:17 0.00 0.00 0.00 0.00 0.00
December 0.494041E+10 11272.15 27-DEC-06:25 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.225485E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.566998E+10 11343.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.449180E+10 9028.05 04-JAN-06:13 0.00 0.00 0.00 0.00 0.00
February 0.304423E+10 9029.40 27-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.209255E+10 9028.40 13-MAR-05:14 0.00 0.00 0.00 0.00 0.00
April 0.102028E+10 9003.73 17-APR-05:13 0.00 0.00 0.00 0.00 0.00
May 0.386053E+09 8962.98 18-MAY-05:12 0.00 0.00 0.00 0.00 0.00
June 0.108783E+09 5669.09 14-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 20105310.78 3704.35 18-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 44784455.92 4826.12 18-AUG-06:03 0.00 0.00 0.00 0.00 0.00
September 0.317131E+09 6389.97 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.143348E+10 9032.08 23-OCT-05:13 0.00 0.00 0.00 0.00 0.00
November 0.282366E+10 9029.87 20-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.398651E+10 9026.81 20-DEC-06:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.197694E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 20105310.78 3704.35   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.449180E+10 9032.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.304679E+09 0.277368E+09 16904.13 27-FEB-15:05 16904.13 0.00
March 0.00 0.00 0.541788E+09 0.470803E+09 15052.38 18-MAR-16:00 15052.38 0.00
April 0.00 0.00 0.425860E+10 0.404770E+10 55804.38 27-APR-16:00 54871.55 0.00
May 0.00 0.00 0.944000E+10 0.827113E+10 51685.72 15-MAY-16:00 51685.72 0.00
June 0.00 0.00 0.176669E+11 0.162064E+11 58673.10 28-JUN-15:50 58673.10 0.00
July 0.00 0.00 0.330661E+11 0.287625E+11 74122.08 31-JUL-16:00 67341.45 0.00
August 0.00 0.00 0.447670E+11 0.385819E+11 79682.89 10-AUG-15:30 74798.65 0.00
September 0.00 0.00 0.173690E+11 0.140501E+11 68694.37 14-SEP-14:05 60180.69 0.00
October 0.00 0.00 0.230704E+10 0.214849E+10 38748.61 04-OCT-15:00 38748.61 0.00
November 0.00 0.00 0.509743E+09 0.350847E+09 25057.97 04-NOV-14:00 18847.75 0.00
December 0.00 0.00 30404.83 27752.92 456.07 19-DEC-08:09 416.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.130231E+12 0.113167E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.447670E+11 0.385819E+11 79682.89   74798.65 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 494542.11 461781.32 1452.24 30-JAN-07:13 1294.64 0.00
February 0.00 0.00 0.290266E+09 0.265042E+09 16578.08 27-FEB-15:05 16578.08 0.00
March 0.00 0.00 0.494761E+09 0.434195E+09 15336.21 18-MAR-14:05 15336.21 0.00
April 0.00 0.00 0.419030E+10 0.399187E+10 55048.19 27-APR-14:05 55048.19 0.00
May 0.00 0.00 0.910081E+10 0.796482E+10 49925.87 04-MAY-14:05 49925.87 0.00
June 0.00 0.00 0.164835E+11 0.150917E+11 56349.55 28-JUN-15:40 56349.55 0.00
July 0.00 0.00 0.303865E+11 0.264247E+11 70879.70 31-JUL-14:05 63757.91 0.00
August 0.00 0.00 0.401225E+11 0.345398E+11 75710.78 10-AUG-14:05 69035.87 0.00
September 0.00 0.00 0.156551E+11 0.126104E+11 65634.11 14-SEP-14:05 57573.92 0.00
October 0.00 0.00 0.202249E+10 0.186810E+10 35105.91 04-OCT-15:00 35105.91 0.00
November 0.00 0.00 0.502037E+09 0.350552E+09 25511.88 04-NOV-14:02 19730.07 0.00
December 0.00 0.00 75233.73 69823.21 626.95 05-DEC-07:04 581.86 0.00
                 
Annual Sum or Average 0.00 0.00 0.119249E+12 0.103542E+12       0.00
Minimum of Months 0.00 0.00 75233.73 69823.21 626.95   581.86 0.00
Maximum of Months 0.00 0.00 0.401225E+11 0.345398E+11 75710.78   69035.87 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1378417.43 1270637.89 1144.41 08-JAN-10:37 1137.79 0.00
February 0.00 0.00 0.323266E+09 0.288992E+09 17558.50 27-FEB-15:00 17514.61 0.00
March 0.00 0.00 0.547466E+09 0.475043E+09 16245.61 18-MAR-14:00 16245.61 0.00
April 0.00 0.00 0.480912E+10 0.455951E+10 68669.43 27-APR-14:40 68669.43 0.00
May 0.00 0.00 0.101730E+11 0.883548E+10 65291.19 04-MAY-14:50 65291.19 0.00
June 0.00 0.00 0.184640E+11 0.167454E+11 70986.53 28-JUN-15:20 70986.53 0.00
July 0.00 0.00 0.342620E+11 0.296813E+11 85761.51 31-JUL-14:40 78593.78 0.00
August 0.00 0.00 0.445529E+11 0.383593E+11 90801.59 10-AUG-14:50 85101.83 0.00
September 0.00 0.00 0.164305E+11 0.130325E+11 73145.10 14-SEP-14:00 64898.53 0.00
October 0.00 0.00 0.195917E+10 0.177951E+10 34606.16 04-OCT-15:00 34606.16 0.00
November 0.00 0.00 0.559982E+09 0.383438E+09 27958.10 04-NOV-13:40 20579.01 0.00
December 0.00 0.00 854396.45 717155.09 685.13 11-DEC-06:13 634.02 0.00
                 
Annual Sum or Average 0.00 0.00 0.132084E+12 0.114142E+12       0.00
Minimum of Months 0.00 0.00 854396.45 717155.09 685.13   634.02 0.00
Maximum of Months 0.00 0.00 0.445529E+11 0.383593E+11 90801.59   85101.83 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 22655.49 332425.65 02-JAN-06:11
February 0.00 0.00 01-FEB-00:10 15225.78 288550.74 27-FEB-06:11
March 0.00 0.00 01-MAR-00:10 7506.99 302977.88 27-MAR-05:11
April 0.00 0.00 01-APR-00:10 3273.12 248180.48 17-APR-05:11
May 0.00 0.00 01-MAY-00:10 1056.66 165876.87 18-MAY-06:03
June 0.00 0.00 01-JUN-00:10 343.86 90094.08 14-JUN-06:03
July 0.00 0.00 01-JUL-00:10 96.28 13547.27 10-JUL-06:07
August 0.00 0.00 01-AUG-00:10 111.42 37367.77 18-AUG-06:03
September 0.00 0.00 01-SEP-00:10 658.62 145778.85 28-SEP-06:03
October 0.00 0.00 01-OCT-00:10 3749.14 257729.87 16-OCT-05:11
November 0.00 0.00 01-NOV-00:10 10868.31 273019.61 20-NOV-06:11
December 0.00 0.00 01-DEC-00:10 17836.02 267866.41 04-DEC-06:11
             
Annual Sum or Average 0.00     6915.10    
Minimum of Months 0.00 0.00   96.28 13547.27  
Maximum of Months 0.00 0.00   22655.49 332425.65  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 1702.15 6226.66 31-JAN-12:15
February 0.00 0.00 01-FEB-00:10 1724.48 6234.19 10-FEB-12:40
March 0.00 0.00 01-MAR-00:10 1823.75 6212.90 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 1649.61 6074.31 03-APR-11:20
May 0.00 0.00 01-MAY-00:10 1649.95 5884.96 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 1631.24 5653.24 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 1446.19 5455.79 03-JUL-11:50
August 0.00 0.00 01-AUG-00:10 1586.59 5376.20 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 1495.25 5493.64 29-SEP-11:18
October 0.00 0.00 01-OCT-00:10 1541.18 5706.32 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 1627.90 5930.81 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 1615.25 6114.39 29-DEC-12:15
             
Annual Sum or Average 0.00     1623.90    
Minimum of Months 0.00 0.00   1446.19 5376.20  
Maximum of Months 0.00 0.00   1823.75 6234.19  



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_BOT FAN

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.345108E+10 0.48 5302.00 02-JAN-06:11 1.24
February 0.307111E+10 0.47 3690.03 01-FEB-06:11 1.06
March 0.394897E+10 0.52 3876.21 02-MAR-16:50 1.09
April 0.402382E+10 0.51 6934.00 27-APR-14:50 1.38
May 0.495684E+10 0.56 7022.22 15-MAY-15:20 1.39
June 0.560849E+10 0.60 8003.11 12-JUN-06:03 1.46
July 0.628605E+10 0.61 9286.72 24-JUL-15:00 1.56
August 0.724380E+10 0.67 10480.98 10-AUG-15:50 1.64
September 0.547190E+10 0.58 8952.30 14-SEP-15:20 1.54
October 0.427614E+10 0.51 7405.16 04-OCT-15:40 1.43
November 0.345754E+10 0.47 3754.87 06-NOV-17:00 1.07
December 0.330318E+10 0.46 3690.03 01-DEC-06:11 1.07
           
Annual Sum or Average 0.550989E+11 0.54      
Minimum of Months 0.307111E+10 0.46 3690.03   1.06
Maximum of Months 0.724380E+10 0.67 10480.98   1.64



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_MID FAN

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.321752E+10 0.48 5315.87 02-JAN-06:11 1.27
February 0.278273E+10 0.46 5315.87 06-FEB-07:02 1.27
March 0.334082E+10 0.50 5315.87 06-MAR-07:03 1.27
April 0.341998E+10 0.49 7505.95 27-APR-14:05 1.46
May 0.417279E+10 0.54 7010.86 15-MAY-14:05 1.43
June 0.478351E+10 0.59 7673.17 28-JUN-15:30 1.48
July 0.544843E+10 0.59 8809.32 31-JUL-14:05 1.56
August 0.615536E+10 0.64 9727.03 10-AUG-15:30 1.63
September 0.446334E+10 0.55 8457.26 14-SEP-14:05 1.54
October 0.341069E+10 0.48 6603.15 04-OCT-14:05 1.39
November 0.291057E+10 0.45 5315.87 13-NOV-07:01 1.27
December 0.298048E+10 0.45 5315.87 04-DEC-07:02 1.27
           
Annual Sum or Average 0.470862E+11 0.52      
Minimum of Months 0.278273E+10 0.45 5315.87   1.27
Maximum of Months 0.615536E+10 0.64 9727.03   1.63



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_TOP FAN

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.403854E+10 0.53 5556.94 09-JAN-06:12 1.20
February 0.338557E+10 0.50 5556.94 07-FEB-06:11 1.20
March 0.360828E+10 0.48 5556.94 01-MAR-07:01 1.20
April 0.355792E+10 0.46 7731.97 27-APR-14:30 1.37
May 0.420995E+10 0.51 7531.69 15-MAY-15:10 1.36
June 0.472183E+10 0.54 8270.48 28-JUN-15:20 1.41
July 0.537670E+10 0.54 9329.79 31-JUL-15:00 1.48
August 0.591428E+10 0.58 10294.93 10-AUG-15:20 1.55
September 0.424574E+10 0.50 7994.87 14-SEP-14:50 1.39
October 0.347235E+10 0.45 5776.37 04-OCT-14:50 1.22
November 0.320057E+10 0.44 5556.94 01-NOV-06:03 1.20
December 0.354865E+10 0.47 5556.94 09-DEC-06:02 1.20
           
Annual Sum or Average 0.492804E+11 0.50      
Minimum of Months 0.320057E+10 0.44 5556.94   1.20
Maximum of Months 0.591428E+10 0.58 10294.93   1.55



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.433065E+09 0.389759E+09 891.86 17-JAN-07:01 802.67 802.67 47.06 2.85
February 0.264959E+09 0.238463E+09 858.86 18-FEB-07:03 772.97 772.97 42.39 2.72
March 0.145971E+09 0.131374E+09 851.22 06-MAR-07:03 766.10 766.10 43.19 2.68
April 64387161.18 57948445.07 807.67 19-APR-06:02 726.90 726.90 37.37 2.42
May 25541389.00 22987250.10 758.50 18-MAY-06:03 682.65 682.65 39.25 1.91
June 9696009.05 8726408.15 546.71 14-JUN-06:03 492.04 492.04 33.90 0.83
July 2238155.05 2014339.55 117.60 10-JUL-06:07 105.84 105.84 34.43 0.13
August 2744651.45 2470186.30 290.88 18-AUG-06:03 261.79 261.79 34.32 0.35
September 14206655.15 12785989.63 698.87 28-SEP-06:03 628.98 628.98 35.05 1.40
October 73785413.57 66406872.21 807.56 16-OCT-06:03 726.80 726.80 39.79 2.41
November 0.201555E+09 0.181400E+09 856.99 24-NOV-07:01 771.29 771.29 43.77 2.71
December 0.339856E+09 0.305870E+09 876.70 26-DEC-07:01 789.03 789.03 47.06 2.79
                 
Annual Sum or Average 0.157801E+10 0.142021E+10            
Minimum of Months 2238155.05 2014339.55 117.60   105.84 105.84 33.90 0.13
Maximum of Months 0.433065E+09 0.389759E+09 891.86   802.67 802.67 47.06 2.85



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12379742.02 3713922.60 6.85 01-JAN-06:05 2.06 2.06 58.14 0.05
February 11196021.66 3358806.50 6.85 01-FEB-06:05 2.06 2.06 56.83 0.05
March 12675672.10 3802701.63 6.85 01-MAR-06:01 2.06 2.06 57.20 0.05
April 11960507.72 3588152.32 6.85 01-APR-05:05 2.06 2.06 56.91 0.05
May 12527707.06 3758312.12 6.85 01-MAY-05:03 2.06 2.06 57.23 0.05
June 12231776.97 3669533.09 6.85 01-JUN-05:03 2.06 2.06 57.28 0.05
July 12256437.81 3676931.34 6.85 01-JUL-05:03 2.06 2.06 57.38 0.05
August 12675672.10 3802701.63 6.85 01-AUG-05:02 2.06 2.06 57.47 0.05
September 11960507.72 3588152.32 6.85 01-SEP-05:03 2.06 2.06 57.41 0.05
October 12379742.02 3713922.60 6.85 01-OCT-05:10 2.06 2.06 58.20 0.05
November 12059151.09 3617745.33 6.85 01-NOV-05:03 2.06 2.06 57.18 0.05
December 12256437.81 3676931.34 6.85 01-DEC-06:03 2.06 2.06 57.07 0.05
                 
Annual Sum or Average 0.146559E+09 43967812.83            
Minimum of Months 11196021.66 3358806.50 6.85   2.06 2.06 56.83 0.05
Maximum of Months 12675672.10 3802701.63 6.85   2.06 2.06 58.20 0.05



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 28.61 60.00 22655.49 332425.65 02-JAN-06:11
February 0.00 0.00 01-FEB-00:10 30.92 30.92 15225.78 288550.74 27-FEB-06:11
March 0.00 0.00 01-MAR-00:10 25.30 25.30 7506.99 302977.88 27-MAR-05:11
April 0.00 0.00 01-APR-00:10 26.78 26.78 3273.12 248180.48 17-APR-05:11
May 0.00 0.00 01-MAY-00:10 27.14 27.14 1056.66 165876.87 18-MAY-06:03
June 0.00 0.00 01-JUN-00:10 44.08 44.08 343.86 90094.08 14-JUN-06:03
July 0.00 0.00 01-JUL-00:10 35.43 35.43 96.28 13547.27 10-JUL-06:07
August 0.00 0.00 01-AUG-00:10 28.16 28.16 111.42 37367.77 18-AUG-06:03
September 0.00 0.00 01-SEP-00:10 28.92 28.92 658.62 145778.85 28-SEP-06:03
October 0.00 0.00 01-OCT-00:10 21.13 21.13 3749.14 257729.87 16-OCT-05:11
November 0.00 0.00 01-NOV-00:10 28.26 28.26 10868.31 273019.61 20-NOV-06:11
December 0.00 0.00 01-DEC-00:10 31.24 31.24 17836.02 267866.41 04-DEC-06:11
                 
Annual Sum or Average 0.00         6915.10    
Minimum of Months 0.00 0.00   21.13 21.13 96.28 13547.27  
Maximum of Months 0.00 0.00   44.08 60.00 22655.49 332425.65  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 58.14 58.14 1702.15 6226.66 31-JAN-12:15
February 0.00 0.00 01-FEB-00:10 57.62 57.62 1724.48 6234.19 10-FEB-12:40
March 0.00 0.00 01-MAR-00:10 57.62 57.62 1823.75 6212.90 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 57.67 57.67 1649.61 6074.31 03-APR-11:20
May 0.00 0.00 01-MAY-00:10 58.21 58.21 1649.95 5884.96 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 57.84 57.84 1631.24 5653.24 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 57.91 57.91 1446.19 5455.79 03-JUL-11:50
August 0.00 0.00 01-AUG-00:10 57.95 57.95 1586.59 5376.20 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 57.95 57.95 1495.25 5493.64 29-SEP-11:18
October 0.00 0.00 01-OCT-00:10 57.04 57.04 1541.18 5706.32 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 57.82 57.82 1627.90 5930.81 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 57.73 57.73 1615.25 6114.39 29-DEC-12:15
                 
Annual Sum or Average 0.00         1623.90    
Minimum of Months 0.00 0.00   57.04 57.04 1446.19 5376.20  
Maximum of Months 0.00 0.00   58.21 58.21 1823.75 6234.19  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.172288E+11 0.00 0.00 0.345108E+10 0.00 0.00
February 0.104369E+11 0.00 0.00 0.315087E+10 0.00 0.00
March 0.683230E+10 0.00 0.00 0.409470E+10 0.00 0.00
April 0.313353E+10 0.00 0.00 0.506562E+10 0.00 0.00
May 0.127195E+10 0.00 0.00 0.724085E+10 0.00 0.00
June 0.579767E+09 0.00 0.00 0.987869E+10 0.00 0.00
July 0.225881E+09 0.00 0.00 0.141189E+11 0.00 0.00
August 0.190110E+09 0.00 0.00 0.179061E+11 0.00 0.00
September 0.546676E+09 0.00 0.00 0.959508E+10 0.00 0.00
October 0.247225E+10 0.00 0.00 0.486063E+10 0.00 0.00
November 0.741864E+10 0.00 0.00 0.358278E+10 0.00 0.00
December 0.126595E+11 0.00 0.00 0.330319E+10 0.00 0.00
             
Annual Sum or Average 0.629963E+11 0.00 0.00 0.862485E+11 0.00 0.00
Minimum of Months 0.190110E+09 0.00 0.00 0.315087E+10 0.00 0.00
Maximum of Months 0.172288E+11 0.00 0.00 0.179061E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.161688E+11 0.00 0.00 0.321766E+10 0.00 0.00
February 0.913321E+10 0.00 0.00 0.285876E+10 0.00 0.00
March 0.393245E+10 0.00 0.00 0.347347E+10 0.00 0.00
April 0.138705E+10 0.00 0.00 0.444523E+10 0.00 0.00
May 0.263691E+09 0.00 0.00 0.637803E+10 0.00 0.00
June 22436989.44 0.00 0.00 0.877789E+10 0.00 0.00
July 418554.14 0.00 0.00 0.126670E+11 0.00 0.00
August 1067669.04 0.00 0.00 0.157515E+11 0.00 0.00
September 0.145726E+09 0.00 0.00 0.819307E+10 0.00 0.00
October 0.195919E+10 0.00 0.00 0.392548E+10 0.00 0.00
November 0.671690E+10 0.00 0.00 0.303311E+10 0.00 0.00
December 0.121317E+11 0.00 0.00 0.298050E+10 0.00 0.00
             
Annual Sum or Average 0.518627E+11 0.00 0.00 0.757017E+11 0.00 0.00
Minimum of Months 418554.14 0.00 0.00 0.285876E+10 0.00 0.00
Maximum of Months 0.161688E+11 0.00 0.00 0.157515E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.277440E+11 0.00 0.00 0.403894E+10 0.00 0.00
February 0.175526E+11 0.00 0.00 0.347061E+10 0.00 0.00
March 0.949764E+10 0.00 0.00 0.375565E+10 0.00 0.00
April 0.403162E+10 0.00 0.00 0.473409E+10 0.00 0.00
May 0.130738E+10 0.00 0.00 0.668116E+10 0.00 0.00
June 0.305827E+09 0.00 0.00 0.921139E+10 0.00 0.00
July 39745763.03 0.00 0.00 0.135467E+11 0.00 0.00
August 0.109473E+09 0.00 0.00 0.166403E+11 0.00 0.00
September 0.103588E+10 0.00 0.00 0.818912E+10 0.00 0.00
October 0.568367E+10 0.00 0.00 0.397938E+10 0.00 0.00
November 0.142494E+11 0.00 0.00 0.333821E+10 0.00 0.00
December 0.233481E+11 0.00 0.00 0.354889E+10 0.00 0.00
             
Annual Sum or Average 0.104905E+12 0.00 0.00 0.811344E+11 0.00 0.00
Minimum of Months 39745763.03 0.00 0.00 0.333821E+10 0.00 0.00
Maximum of Months 0.277440E+11 0.00 0.00 0.166403E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.345108E+10 0.00 0.172288E+11 0.00 0.00 0.00 0.00 0.00
February 0.307111E+10 0.304679E+09 0.104369E+11 0.00 0.00 0.00 0.00 0.00
March 0.394897E+10 0.541788E+09 0.683230E+10 0.00 0.00 0.00 0.00 0.00
April 0.402382E+10 0.425860E+10 0.313353E+10 0.00 0.00 0.00 0.00 0.00
May 0.495684E+10 0.944000E+10 0.127195E+10 0.00 0.00 0.00 0.00 0.00
June 0.560849E+10 0.176669E+11 0.579767E+09 0.00 0.00 0.00 0.00 0.00
July 0.628605E+10 0.330661E+11 0.225881E+09 0.00 0.00 0.00 0.00 0.00
August 0.724380E+10 0.447670E+11 0.190110E+09 0.00 0.00 0.00 0.00 0.00
September 0.547190E+10 0.173690E+11 0.546676E+09 0.00 0.00 0.00 0.00 0.00
October 0.427614E+10 0.230704E+10 0.247225E+10 0.00 0.00 0.00 0.00 0.00
November 0.345754E+10 0.509743E+09 0.741864E+10 0.00 0.00 0.00 0.00 0.00
December 0.330318E+10 30404.83 0.126595E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.550989E+11 0.130231E+12 0.629963E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.307111E+10 0.00 0.190110E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.724380E+10 0.447670E+11 0.172288E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.321752E+10 494542.11 0.161688E+11 0.00 0.00 0.00 0.00 0.00
February 0.278273E+10 0.290266E+09 0.913321E+10 0.00 0.00 0.00 0.00 0.00
March 0.334082E+10 0.494761E+09 0.393245E+10 0.00 0.00 0.00 0.00 0.00
April 0.341998E+10 0.419030E+10 0.138705E+10 0.00 0.00 0.00 0.00 0.00
May 0.417279E+10 0.910081E+10 0.263691E+09 0.00 0.00 0.00 0.00 0.00
June 0.478351E+10 0.164835E+11 22436989.44 0.00 0.00 0.00 0.00 0.00
July 0.544843E+10 0.303865E+11 418554.14 0.00 0.00 0.00 0.00 0.00
August 0.615536E+10 0.401225E+11 1067669.04 0.00 0.00 0.00 0.00 0.00
September 0.446334E+10 0.156551E+11 0.145726E+09 0.00 0.00 0.00 0.00 0.00
October 0.341069E+10 0.202249E+10 0.195919E+10 0.00 0.00 0.00 0.00 0.00
November 0.291057E+10 0.502037E+09 0.671690E+10 0.00 0.00 0.00 0.00 0.00
December 0.298048E+10 75233.73 0.121317E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.470862E+11 0.119249E+12 0.518627E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.278273E+10 75233.73 418554.14 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.615536E+10 0.401225E+11 0.161688E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.403854E+10 1378417.43 0.277440E+11 0.00 0.00 0.00 0.00 0.00
February 0.338557E+10 0.323266E+09 0.175526E+11 0.00 0.00 0.00 0.00 0.00
March 0.360828E+10 0.547466E+09 0.949764E+10 0.00 0.00 0.00 0.00 0.00
April 0.355792E+10 0.480912E+10 0.403162E+10 0.00 0.00 0.00 0.00 0.00
May 0.420995E+10 0.101730E+11 0.130738E+10 0.00 0.00 0.00 0.00 0.00
June 0.472183E+10 0.184640E+11 0.305827E+09 0.00 0.00 0.00 0.00 0.00
July 0.537670E+10 0.342620E+11 39745763.03 0.00 0.00 0.00 0.00 0.00
August 0.591428E+10 0.445529E+11 0.109473E+09 0.00 0.00 0.00 0.00 0.00
September 0.424574E+10 0.164305E+11 0.103588E+10 0.00 0.00 0.00 0.00 0.00
October 0.347235E+10 0.195917E+10 0.568367E+10 0.00 0.00 0.00 0.00 0.00
November 0.320057E+10 0.559982E+09 0.142494E+11 0.00 0.00 0.00 0.00 0.00
December 0.354865E+10 854396.45 0.233481E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.492804E+11 0.132084E+12 0.104905E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.320057E+10 854396.45 39745763.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.591428E+10 0.445529E+11 0.277440E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.345108E+10 0.172288E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.307111E+10 0.104369E+11 0.00 0.00 79761204.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.394897E+10 0.683230E+10 0.00 0.00 0.145728E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.402382E+10 0.313353E+10 0.00 0.00 0.104179E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.495684E+10 0.127195E+10 0.00 0.00 0.228401E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.560849E+10 0.579767E+09 0.00 0.00 0.427020E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.628605E+10 0.225881E+09 0.00 0.00 0.783281E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.724380E+10 0.190110E+09 0.00 0.00 0.106623E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.547190E+10 0.546676E+09 0.00 0.00 0.412318E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.427614E+10 0.247225E+10 0.00 0.00 0.584491E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.345754E+10 0.741864E+10 0.00 0.00 0.125241E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.330318E+10 0.126595E+11 0.00 0.00 8713.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.550989E+11 0.629963E+11 0.00 0.00 0.311495E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.307111E+10 0.190110E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.724380E+10 0.172288E+11 0.00 0.00 0.106623E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.321752E+10 0.161688E+11 0.00 0.00 140740.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.278273E+10 0.913321E+10 0.00 0.00 76025410.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.334082E+10 0.393245E+10 0.00 0.00 0.132650E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.341998E+10 0.138705E+10 0.00 0.00 0.102525E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.417279E+10 0.263691E+09 0.00 0.00 0.220524E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.478351E+10 22436989.44 0.00 0.00 0.399438E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.544843E+10 418554.14 0.00 0.00 0.721859E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.615536E+10 1067669.04 0.00 0.00 0.959616E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.446334E+10 0.145726E+09 0.00 0.00 0.372973E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.341069E+10 0.195919E+10 0.00 0.00 0.514796E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.291057E+10 0.671690E+10 0.00 0.00 0.122544E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.298048E+10 0.121317E+11 0.00 0.00 21523.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.470862E+11 0.518627E+11 0.00 0.00 0.286155E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.278273E+10 418554.14 0.00 0.00 21523.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.615536E+10 0.161688E+11 0.00 0.00 0.959616E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.403854E+10 0.277440E+11 0.00 0.00 394635.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.338557E+10 0.175526E+11 0.00 0.00 85039283.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.360828E+10 0.949764E+10 0.00 0.00 0.147366E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.355792E+10 0.403162E+10 0.00 0.00 0.117617E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.420995E+10 0.130738E+10 0.00 0.00 0.247120E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.472183E+10 0.305827E+09 0.00 0.00 0.448956E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.537670E+10 39745763.03 0.00 0.00 0.817000E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.591428E+10 0.109473E+09 0.00 0.00 0.107260E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.424574E+10 0.103588E+10 0.00 0.00 0.394339E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.347235E+10 0.568367E+10 0.00 0.00 0.507030E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.320057E+10 0.142494E+11 0.00 0.00 0.137637E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.354865E+10 0.233481E+11 0.00 0.00 244901.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.492804E+11 0.104905E+12 0.00 0.00 0.318541E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.320057E+10 39745763.03 0.00 0.00 244901.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.591428E+10 0.277440E+11 0.00 0.00 0.107260E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.840066E+10 0.00 0.00 6216089.92 0.00 0.222687E+09 0.477576E+10 0.00 0.32
February 0.553010E+10 0.00 0.00 14625829.43 0.00 0.00 0.811935E+10 0.00 0.41
March 0.266953E+10 0.00 0.00 31979487.21 0.00 0.00 0.166861E+11 0.00 0.58
April 0.133445E+10 12268842.10 0.00 35534541.88 4363864.42 0.00 0.176254E+11 0.00 0.69
May 0.104984E+10 13397805.91 0.00 47457602.30 0.00 0.00 0.215310E+11 0.00 0.98
June 0.675700E+09 1746136.37 0.00 51141597.04 3727350.15 0.00 0.209588E+11 0.00 1.18
July 0.532712E+09 0.170838E+09 0.00 45594602.82 17087076.49 0.00 0.151097E+11 0.00 1.13
August 0.526619E+09 0.480192E+09 0.00 44856313.79 5373186.18 0.00 0.129386E+11 0.00 1.08
September 0.848241E+09 18405625.93 0.00 49929065.73 0.00 0.00 0.191235E+11 0.00 1.11
October 0.139082E+10 0.00 0.00 40039756.02 0.00 0.00 0.199539E+11 0.00 0.78
November 0.372202E+10 0.00 0.00 23462513.00 0.00 0.00 0.125135E+11 0.00 0.49
December 0.679544E+10 0.00 0.00 12930051.15 0.00 0.00 0.753862E+10 0.00 0.35
                   
Annual Sum or Average 0.334761E+11 0.696849E+09 0.00 0.403767E+09 30551477.24 0.222687E+09 0.176874E+12 0.00 0.76
Minimum of Months 0.526619E+09 0.00 0.00 6216089.92 0.00 0.00 0.477576E+10 0.00 0.32
Maximum of Months 0.840066E+10 0.480192E+09 0.00 51141597.04 17087076.49 0.222687E+09 0.215310E+11 0.00 1.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100804E+11 0.00 0.00 0.00 0.00 0.451258E+09 0.00 0.00 0.26
February 0.928101E+10 0.00 0.00 491166.69 0.00 60600927.83 0.692278E+09 0.00 0.31
March 0.905002E+10 0.00 0.00 3789661.57 0.00 6637235.14 0.339909E+10 0.00 0.38
April 0.590461E+10 6015632.83 0.00 10828722.74 11564996.19 0.00 0.624815E+10 0.00 0.45
May 0.388053E+10 1520643.00 0.00 21764084.64 10686089.34 0.00 0.106618E+11 0.00 0.65
June 0.225064E+10 964934.31 0.00 27321828.57 3327236.34 0.00 0.119869E+11 0.00 0.80
July 0.128634E+10 0.131428E+09 0.00 25929724.45 19503985.06 0.00 0.881805E+10 0.00 0.76
August 0.139603E+10 0.377321E+09 0.00 25225833.62 8052589.13 0.00 0.726362E+10 0.00 0.73
September 0.308772E+10 2865214.98 0.00 22801429.16 13428889.11 0.00 0.899718E+10 0.00 0.71
October 0.649886E+10 0.00 0.00 10946721.47 0.00 0.00 0.621478E+10 0.00 0.48
November 0.877801E+10 0.00 0.00 1559807.68 323917.42 25650795.93 0.160033E+10 0.00 0.32
December 0.100603E+11 0.00 0.00 70834.75 0.00 0.118172E+09 0.192197E+09 0.00 0.26
                   
Annual Sum or Average 0.715544E+11 0.520116E+09 0.00 0.150730E+09 66887702.59 0.662318E+09 0.660743E+11 0.00 0.51
Minimum of Months 0.128634E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.26
Maximum of Months 0.100804E+11 0.377321E+09 0.00 27321828.57 19503985.06 0.451258E+09 0.119869E+11 0.00 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.791649E+10 0.00 0.00 0.00 0.00 0.178596E+10 0.00 0.00 0.25
February 0.858644E+10 0.00 0.00 23854.93 0.00 0.807623E+09 99641401.99 0.00 0.31
March 0.107749E+11 0.00 0.00 654351.21 0.00 0.238673E+09 0.114183E+10 0.00 0.40
April 0.790273E+10 57683.93 0.00 6537765.76 56740.14 60345351.57 0.419085E+10 0.00 0.46
May 0.592921E+10 3063134.61 0.00 15926642.75 207916.26 0.00 0.888292E+10 0.00 0.65
June 0.400659E+10 0.00 0.00 23272127.31 2364790.99 0.00 0.105373E+11 0.00 0.80
July 0.253481E+10 80091544.27 0.00 23201213.22 4141995.14 0.00 0.795249E+10 0.00 0.78
August 0.239017E+10 0.266305E+09 0.00 20404344.98 10227206.49 0.00 0.547844E+10 0.00 0.71
September 0.549294E+10 0.00 0.00 13775997.66 3696127.02 0.00 0.561808E+10 0.00 0.69
October 0.922821E+10 0.00 0.00 3322820.09 0.00 82346437.20 0.232375E+10 0.00 0.47
November 0.914100E+10 0.00 0.00 6505.40 0.00 0.409087E+09 53039558.99 0.00 0.33
December 0.814355E+10 0.00 0.00 0.00 0.00 0.126057E+10 0.00 0.00 0.25
                   
Annual Sum or Average 0.820471E+11 0.349517E+09 0.00 0.107126E+09 20694776.03 0.464460E+10 0.462783E+11 0.00 0.51
Minimum of Months 0.239017E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 0.107749E+11 0.266305E+09 0.00 23272127.31 10227206.49 0.178596E+10 0.105373E+11 0.00 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103097E+10 0.00 0.00 0.00 0.00 0.252251E+10 0.00 0.00 0.44
February 0.171995E+10 0.00 0.00 0.00 0.00 0.175595E+10 0.00 0.00 0.55
March 0.355208E+10 0.00 0.00 0.00 0.00 0.889566E+09 0.00 0.00 0.68
April 0.360952E+10 16223.55 0.00 474085.93 20711.54 0.337610E+09 0.335218E+09 0.00 0.76
May 0.341394E+10 1193856.47 0.00 2025444.61 0.00 59792165.37 0.141168E+10 0.00 1.02
June 0.250379E+10 0.00 0.00 3952582.28 863206.46 5243133.90 0.199657E+10 0.00 1.18
July 0.149307E+10 23828467.09 0.00 4866802.94 3139582.68 0.00 0.171656E+10 0.00 1.13
August 0.145590E+10 78641104.43 0.00 3557744.93 6889568.68 1923951.57 0.989485E+09 0.00 1.04
September 0.292374E+10 0.00 0.00 1615115.38 1349176.62 37024282.13 0.726615E+09 0.00 1.06
October 0.356420E+10 0.00 0.00 57964.85 0.00 0.488605E+09 0.109498E+09 0.00 0.79
November 0.204828E+10 0.00 0.00 0.00 0.00 0.146568E+10 0.00 0.00 0.57
December 0.113903E+10 0.00 0.00 0.00 0.00 0.230489E+10 0.00 0.00 0.44
                   
Annual Sum or Average 0.284545E+11 0.103680E+09 0.00 16549740.91 12262245.98 0.986879E+10 0.728563E+10 0.00 0.81
Minimum of Months 0.103097E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.44
Maximum of Months 0.360952E+10 78641104.43 0.00 4866802.94 6889568.68 0.252251E+10 0.199657E+10 0.00 1.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.106628E+10 0.00 0.00 0.00 0.00 0.196124E+10 0.00 0.00 0.59
February 0.164399E+10 0.00 0.00 0.00 0.00 0.131981E+10 0.00 0.00 0.73
March 0.315420E+10 0.00 0.00 33729.63 0.00 0.586763E+09 54150412.27 0.00 0.92
April 0.247697E+10 13091.16 0.00 1387025.77 17703.07 0.189883E+09 0.107812E+10 0.00 1.06
May 0.248665E+10 1020442.24 0.00 2989943.28 0.00 42365360.98 0.183245E+10 0.00 1.44
June 0.167321E+10 0.00 0.00 5385242.84 737820.97 5212622.31 0.263362E+10 0.00 1.77
July 0.114683E+10 17163399.78 0.00 5723219.26 4541917.64 0.00 0.188783E+10 0.00 1.69
August 0.103565E+10 61944352.25 0.00 4931367.29 9197361.31 1672197.34 0.126604E+10 0.00 1.61
September 0.209189E+10 846100.59 0.00 2889391.34 307100.70 29479319.43 0.124096E+10 0.00 1.54
October 0.285643E+10 0.00 0.00 420455.48 0.00 0.340488E+09 0.380356E+09 0.00 1.08
November 0.184695E+10 0.00 0.00 0.00 0.00 0.115237E+10 0.00 0.00 0.77
December 0.115206E+10 0.00 0.00 0.00 0.00 0.178446E+10 0.00 0.00 0.60
                   
Annual Sum or Average 0.226311E+11 80987386.02 0.00 23760374.90 14801903.70 0.741374E+10 0.103735E+11 0.00 1.15
Minimum of Months 0.103565E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.59
Maximum of Months 0.315420E+10 61944352.25 0.00 5723219.26 9197361.31 0.196124E+10 0.263362E+10 0.00 1.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.213785E+10 0.00 0.00 213968.97 0.00 0.252383E+10 0.105058E+09 0.00 0.59
February 0.247718E+10 0.00 0.00 1539166.75 0.00 0.161725E+10 0.676988E+09 0.00 0.75
March 0.374226E+10 0.00 0.00 3633642.27 0.00 0.801886E+09 0.185071E+10 0.00 0.99
April 0.340910E+10 68859.72 0.00 4860965.66 0.00 0.373831E+09 0.245880E+10 0.00 1.13
May 0.394085E+10 1771811.99 0.00 5598766.81 0.00 98105393.04 0.301281E+10 0.00 1.48
June 0.331467E+10 0.00 0.00 6207558.09 1159383.46 15112406.32 0.298163E+10 0.00 1.66
July 0.215168E+10 32985067.61 0.00 7607822.05 6738902.11 1423956.50 0.245743E+10 0.00 1.63
August 0.195122E+10 0.129612E+09 0.00 6486425.51 11413238.92 5088657.45 0.153413E+10 0.00 1.52
September 0.314999E+10 3699938.71 0.00 8312306.97 0.00 44527776.08 0.269906E+10 0.00 1.79
October 0.360336E+10 0.00 0.00 4699105.94 0.00 0.481650E+09 0.230076E+10 0.00 1.24
November 0.290518E+10 0.00 0.00 908196.36 0.00 0.156195E+10 0.280620E+09 0.00 0.78
December 0.202688E+10 0.00 0.00 526239.46 0.00 0.229803E+10 0.303929E+09 0.00 0.59
                   
Annual Sum or Average 0.348102E+11 0.168137E+09 0.00 50594164.84 19311524.49 0.982268E+10 0.206619E+11 0.00 1.18
Minimum of Months 0.195122E+10 0.00 0.00 213968.97 0.00 1423956.50 0.105058E+09 0.00 0.59
Maximum of Months 0.394085E+10 0.129612E+09 0.00 8312306.97 11413238.92 0.252383E+10 0.301281E+10 0.00 1.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109107E+10 0.00 0.00 0.00 0.00 0.233686E+10 0.00 0.00 0.67
February 0.171919E+10 0.00 0.00 48428.10 0.00 0.160484E+10 33273037.32 0.00 0.83
March 0.323612E+10 0.00 0.00 387849.13 0.00 0.799407E+09 0.296038E+09 0.00 1.05
April 0.304847E+10 42851.69 0.00 1585829.83 0.00 0.322358E+09 0.903899E+09 0.00 1.21
May 0.335303E+10 957723.12 0.00 3153258.92 198891.37 74395021.33 0.158251E+10 0.00 1.67
June 0.279913E+10 0.00 0.00 3817115.55 836279.01 12299584.58 0.164437E+10 0.00 1.87
July 0.163568E+10 35917257.33 0.00 4913311.88 259202.34 1027119.13 0.164354E+10 0.00 1.88
August 0.158829E+10 92431302.78 0.00 3367261.81 6859266.29 4299935.41 0.836944E+09 0.00 1.64
September 0.273959E+10 1252915.16 0.00 2822457.22 54174.33 41322363.55 0.999031E+09 0.00 1.75
October 0.321498E+10 0.00 0.00 601488.92 0.00 0.461261E+09 0.412609E+09 0.00 1.24
November 0.200097E+10 0.00 0.00 5554.96 0.00 0.139638E+10 926704.17 0.00 0.87
December 0.119933E+10 0.00 0.00 0.00 0.00 0.212640E+10 0.00 0.00 0.67
                   
Annual Sum or Average 0.276259E+11 0.130602E+09 0.00 20702556.30 8207813.34 0.918086E+10 0.835315E+10 0.00 1.28
Minimum of Months 0.109107E+10 0.00 0.00 0.00 0.00 1027119.13 0.00 0.00 0.67
Maximum of Months 0.335303E+10 92431302.78 0.00 4913311.88 6859266.29 0.233686E+10 0.164437E+10 0.00 1.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.110277E+10 0.00 0.00 0.00 0.00 0.218111E+10 0.00 0.00 0.37
February 0.168131E+10 0.00 0.00 0.00 0.00 0.148932E+10 0.00 0.00 0.45
March 0.327748E+10 0.00 0.00 0.00 0.00 0.714269E+09 0.00 0.00 0.56
April 0.329316E+10 1113847.68 0.00 45403.23 1811954.34 0.225547E+09 31688448.88 0.00 0.60
May 0.320827E+10 248798.57 0.00 567044.08 2487698.34 8740750.00 0.476107E+09 0.00 0.75
June 0.207921E+10 297784.48 0.00 2360042.79 918107.13 0.00 0.118983E+10 0.00 0.86
July 0.113602E+10 28167150.09 0.00 3526120.26 6236041.01 0.00 0.121594E+10 0.00 0.83
August 0.118575E+10 85831912.11 0.00 2866776.61 1613846.05 0.00 0.870418E+09 0.00 0.80
September 0.248215E+10 518909.14 0.00 1371096.88 3158652.16 1069432.65 0.633016E+09 0.00 0.82
October 0.364755E+10 0.00 0.00 64532.79 0.00 66810142.84 0.109815E+09 0.00 0.65
November 0.273945E+10 0.00 0.00 0.00 0.00 0.712318E+09 0.00 0.00 0.49
December 0.154611E+10 0.00 0.00 0.00 0.00 0.181959E+10 0.00 0.00 0.38
                   
Annual Sum or Average 0.273792E+11 0.116178E+09 0.00 10801016.63 16226299.03 0.721878E+10 0.452682E+10 0.00 0.63
Minimum of Months 0.110277E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.37
Maximum of Months 0.364755E+10 85831912.11 0.00 3526120.26 6236041.01 0.218111E+10 0.121594E+10 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.121644E+10 0.00 0.00 0.00 0.00 0.188702E+10 0.00 0.00 0.55
February 0.174841E+10 0.00 0.00 0.00 0.00 0.125275E+10 0.00 0.00 0.67
March 0.329452E+10 0.00 0.00 328.10 0.00 0.485669E+09 6021748.32 0.00 0.84
April 0.272570E+10 1407048.59 0.00 664663.71 1704147.06 0.131976E+09 0.551707E+09 0.00 0.92
May 0.256884E+10 2282182.32 0.00 1669853.90 309474.29 9193243.36 0.102685E+10 0.00 1.18
June 0.151665E+10 282512.85 0.00 4183231.15 871022.75 1015614.56 0.194062E+10 0.00 1.44
July 0.100807E+10 29020123.32 0.00 4483470.56 6189717.84 0.00 0.146463E+10 0.00 1.38
August 0.910489E+09 87117095.20 0.00 4266123.94 1341709.51 0.00 0.124718E+10 0.00 1.38
September 0.202795E+10 2483402.96 0.00 2820089.63 1006447.21 1561375.24 0.115236E+10 0.00 1.34
October 0.316759E+10 0.00 0.00 552322.16 0.00 70148105.11 0.424058E+09 0.00 0.98
November 0.261308E+10 0.00 0.00 0.00 0.00 0.661731E+09 0.00 0.00 0.73
December 0.162155E+10 0.00 0.00 0.00 0.00 0.156875E+10 0.00 0.00 0.57
                   
Annual Sum or Average 0.244193E+11 0.122592E+09 0.00 18640083.15 11422518.66 0.606982E+10 0.781342E+10 0.00 1.00
Minimum of Months 0.910489E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.55
Maximum of Months 0.329452E+10 87117095.20 0.00 4483470.56 6189717.84 0.188702E+10 0.194062E+10 0.00 1.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.107720E+10 0.00 0.00 175.28 0.00 0.416338E+10 2193454.42 0.00 0.59
February 0.223499E+10 0.00 0.00 196265.79 0.00 0.260911E+10 0.108967E+09 0.00 0.69
March 0.376687E+10 0.00 0.00 647077.74 0.00 0.192071E+10 0.434021E+09 0.00 0.86
April 0.370736E+10 6617571.40 0.00 1092853.13 0.00 0.112165E+10 0.538133E+09 0.00 0.91
May 0.409409E+10 3781055.07 0.00 1608636.24 198684.86 0.682506E+09 0.739898E+09 0.00 1.13
June 0.341491E+10 261332.45 0.00 2501326.16 1490140.10 0.420588E+09 0.919366E+09 0.00 1.25
July 0.203635E+10 58099409.73 0.00 4238961.62 7282079.10 0.211406E+09 0.114028E+10 0.00 1.23
August 0.191132E+10 0.190732E+09 0.00 4145582.32 2281340.14 0.125985E+09 0.936157E+09 0.00 1.22
September 0.299040E+10 10688799.53 0.00 5825807.06 0.00 0.345207E+09 0.161667E+10 0.00 1.44
October 0.387597E+10 0.00 0.00 2808905.91 0.00 0.813781E+09 0.140578E+10 0.00 1.07
November 0.298831E+10 0.00 0.00 325950.31 0.00 0.237073E+10 56860522.21 0.00 0.76
December 0.164269E+10 0.00 0.00 122982.93 0.00 0.360042E+10 0.107209E+09 0.00 0.61
                   
Annual Sum or Average 0.337405E+11 0.270180E+09 0.00 23514524.50 11252244.21 0.183855E+11 0.800554E+10 0.00 0.98
Minimum of Months 0.107720E+10 0.00 0.00 175.28 0.00 0.125985E+09 2193454.42 0.00 0.59
Maximum of Months 0.409409E+10 0.190732E+09 0.00 5825807.06 7282079.10 0.416338E+10 0.161667E+10 0.00 1.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.124042E+10 0.00 0.00 0.00 0.00 0.223605E+10 0.00 0.00 0.62
February 0.194792E+10 0.00 0.00 6825.46 0.00 0.140693E+10 7224984.32 0.00 0.75
March 0.356446E+10 0.00 0.00 107678.82 0.00 0.575204E+09 0.103804E+09 0.00 0.94
April 0.326771E+10 1835050.86 0.00 630116.52 1711080.47 0.194311E+09 0.335180E+09 0.00 1.02
May 0.327150E+10 1248114.21 0.00 1576991.42 1658843.81 10360159.08 0.740777E+09 0.00 1.33
June 0.242499E+10 583872.55 0.00 2500319.43 976274.34 2392852.46 0.109769E+10 0.00 1.49
July 0.125536E+10 49793373.22 0.00 3856764.71 1568061.67 0.00 0.133031E+10 0.00 1.50
August 0.136337E+10 0.108854E+09 0.00 2715758.60 2497015.01 0.00 0.818813E+09 0.00 1.35
September 0.257765E+10 2926007.49 0.00 2256278.93 1170145.33 2335190.74 0.840940E+09 0.00 1.46
October 0.368258E+10 0.00 0.00 480063.83 0.00 88063699.17 0.335261E+09 0.00 1.11
November 0.295585E+10 0.00 0.00 3709.07 0.00 0.713711E+09 775676.80 0.00 0.82
December 0.174871E+10 0.00 0.00 0.00 0.00 0.182558E+10 0.00 0.00 0.64
                   
Annual Sum or Average 0.293005E+11 0.165241E+09 0.00 14134506.78 9581420.64 0.705494E+10 0.561078E+10 0.00 1.09
Minimum of Months 0.124042E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.62
Maximum of Months 0.368258E+10 0.108854E+09 0.00 3856764.71 2497015.01 0.223605E+10 0.133031E+10 0.00 1.50



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.137648E+10 0.00 0.00 0.00 0.00 0.193114E+10 0.00 0.00 0.38
February 0.201002E+10 0.00 0.00 0.00 0.00 0.113856E+10 0.00 0.00 0.46
March 0.356258E+10 0.00 0.00 0.00 0.00 0.314766E+09 0.00 0.00 0.56
April 0.299001E+10 1726990.92 0.00 658527.83 3614856.08 82371252.60 0.491219E+09 0.00 0.62
May 0.231997E+10 3813181.84 0.00 3032999.62 0.00 3549109.49 0.162510E+10 0.00 0.84
June 0.149054E+10 322515.63 0.00 5198721.83 1039990.01 0.00 0.219871E+10 0.00 1.01
July 0.918499E+09 42798147.92 0.00 5465184.40 5462809.98 0.00 0.174020E+10 0.00 0.99
August 0.100087E+10 0.116362E+09 0.00 4440958.49 2296034.98 0.00 0.120240E+10 0.00 0.91
September 0.215773E+10 737542.45 0.00 2553138.09 4197450.71 967623.93 0.102575E+10 0.00 0.88
October 0.335466E+10 0.00 0.00 267356.90 0.00 99795486.51 0.238409E+09 0.00 0.65
November 0.250889E+10 0.00 0.00 0.00 101246.46 0.748183E+09 0.00 0.00 0.48
December 0.155856E+10 0.00 0.00 0.00 0.00 0.169824E+10 0.00 0.00 0.39
                   
Annual Sum or Average 0.252488E+11 0.165760E+09 0.00 21616887.15 16712388.22 0.601757E+10 0.852179E+10 0.00 0.68
Minimum of Months 0.918499E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.38
Maximum of Months 0.356258E+10 0.116362E+09 0.00 5465184.40 5462809.98 0.193114E+10 0.219871E+10 0.00 1.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.117710E+10 0.00 0.00 0.00 0.00 0.181351E+10 0.00 0.00 0.54
February 0.178737E+10 0.00 0.00 15851.24 0.00 0.103940E+10 3539608.91 0.00 0.65
March 0.303777E+10 0.00 0.00 366241.99 0.00 0.300016E+09 0.209049E+09 0.00 0.81
April 0.229479E+10 1412119.63 0.00 1905807.84 2655736.31 69182457.91 0.116886E+10 0.00 0.98
May 0.223214E+10 3997666.44 0.00 3337418.78 20161.90 9461664.80 0.175410E+10 0.00 1.35
June 0.153009E+10 294472.81 0.00 5552618.79 1164229.08 1113833.42 0.247414E+10 0.00 1.69
July 0.111639E+10 33878186.87 0.00 5596300.05 8847087.74 0.00 0.170764E+10 0.00 1.60
August 0.100639E+10 94270467.96 0.00 5006541.80 4702599.24 0.00 0.135445E+10 0.00 1.56
September 0.197793E+10 3292421.86 0.00 3409237.45 215579.71 4499984.98 0.132576E+10 0.00 1.46
October 0.274989E+10 0.00 0.00 908821.23 0.00 0.127421E+09 0.602955E+09 0.00 0.98
November 0.215711E+10 0.00 0.00 13566.13 68291.74 0.788138E+09 2037436.50 0.00 0.68
December 0.135096E+10 0.00 0.00 0.00 0.00 0.159064E+10 0.00 0.00 0.54
                   
Annual Sum or Average 0.224179E+11 0.137145E+09 0.00 26112405.32 17673685.73 0.574338E+10 0.106025E+11 0.00 1.07
Minimum of Months 0.100639E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.54
Maximum of Months 0.303777E+10 94270467.96 0.00 5596300.05 8847087.74 0.181351E+10 0.247414E+10 0.00 1.69



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.281967E+10 0.00 0.00 311289.55 0.00 0.227508E+10 0.156122E+09 0.00 0.61
February 0.324303E+10 0.00 0.00 2197565.76 0.00 0.107496E+10 0.877585E+09 0.00 0.77
March 0.421913E+10 0.00 0.00 4640768.61 0.00 0.407291E+09 0.209187E+10 0.00 0.99
April 0.363873E+10 12150180.92 0.00 4945355.87 46212.96 0.138846E+09 0.238253E+10 0.00 1.11
May 0.370481E+10 6833619.84 0.00 5860438.58 0.00 15099435.68 0.281282E+10 0.00 1.41
June 0.296166E+10 419177.94 0.00 6552735.90 1648750.10 1577381.11 0.274333E+10 0.00 1.57
July 0.201106E+10 68318096.36 0.00 7311958.12 10413476.04 0.00 0.210795E+10 0.00 1.55
August 0.183471E+10 0.210294E+09 0.00 6117051.01 4841745.95 0.00 0.160047E+10 0.00 1.47
September 0.320636E+10 16008575.85 0.00 8643580.02 0.00 3993339.02 0.260862E+10 0.00 1.76
October 0.402481E+10 0.00 0.00 5728970.50 0.00 0.141025E+09 0.268021E+10 0.00 1.26
November 0.397180E+10 342727.88 0.00 1269561.12 0.00 0.869719E+09 0.394837E+09 0.00 0.79
December 0.282338E+10 0.00 0.00 1113036.60 0.00 0.189497E+10 0.507604E+09 0.00 0.62
                   
Annual Sum or Average 0.384591E+11 0.314366E+09 0.00 54692311.63 16950185.05 0.682255E+10 0.209640E+11 0.00 1.16
Minimum of Months 0.183471E+10 0.00 0.00 311289.55 0.00 0.00 0.156122E+09 0.00 0.61
Maximum of Months 0.421913E+10 0.210294E+09 0.00 8643580.02 10413476.04 0.227508E+10 0.281282E+10 0.00 1.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.168715E+10 0.00 0.00 0.00 0.00 0.212382E+10 0.00 0.00 0.69
February 0.241874E+10 0.00 0.00 74030.71 0.00 0.115915E+10 56379336.83 0.00 0.84
March 0.379717E+10 0.00 0.00 455692.55 0.00 0.386141E+09 0.339566E+09 0.00 1.04
April 0.328508E+10 3718311.50 0.00 1487868.62 2709413.53 0.124124E+09 0.817675E+09 0.00 1.17
May 0.321497E+10 3108238.11 0.00 3128786.82 1280232.76 12382881.29 0.143304E+10 0.00 1.60
June 0.250290E+10 647031.44 0.00 3761181.22 1202842.82 2375680.64 0.157382E+10 0.00 1.77
July 0.147023E+10 67492024.93 0.00 4600186.93 1614839.64 0.00 0.148554E+10 0.00 1.78
August 0.149756E+10 0.139779E+09 0.00 3258902.41 4382536.68 0.00 0.915664E+09 0.00 1.57
September 0.285054E+10 5020982.88 0.00 2831497.86 999245.44 4649235.03 0.919568E+09 0.00 1.68
October 0.372829E+10 0.00 0.00 747472.16 0.00 0.150894E+09 0.460468E+09 0.00 1.22
November 0.290345E+10 0.00 0.00 10682.34 117100.71 0.861936E+09 239276.88 0.00 0.88
December 0.195775E+10 0.00 0.00 0.00 0.00 0.180116E+10 0.00 0.00 0.70
                   
Annual Sum or Average 0.313138E+11 0.219766E+09 0.00 20356301.62 12306211.58 0.662664E+10 0.800196E+10 0.00 1.25
Minimum of Months 0.147023E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.69
Maximum of Months 0.379717E+10 0.139779E+09 0.00 4600186.93 4382536.68 0.212382E+10 0.157382E+10 0.00 1.78



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:22:07

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.757199E+11 0.147979E+11 0.00 0.164110E+12 0.320361E+11
February 0.136382E+12 0.131748E+11 0.00 0.178811E+12 0.222791E+11
March 0.230264E+12 0.127767E+11 0.00 0.229976E+12 0.149283E+11
April 0.347404E+12 0.114133E+11 0.00 0.257494E+12 0.220818E+11
May 0.448992E+12 0.922264E+10 0.00 0.284352E+12 0.376553E+11
June 0.449941E+12 0.745552E+10 0.00 0.273370E+12 0.660306E+11
July 0.475497E+12 0.562052E+10 0.00 0.268730E+12 0.121134E+12
August 0.375646E+12 0.415558E+10 0.00 0.205977E+12 0.160654E+12
September 0.270862E+12 0.483063E+10 0.00 0.274809E+12 0.624779E+11
October 0.178566E+12 0.101049E+11 0.00 0.268604E+12 0.147027E+11
November 0.810721E+11 0.120686E+11 0.00 0.213225E+12 0.190376E+11
December 0.617361E+11 0.131440E+11 0.00 0.182201E+12 0.262377E+11
           
Annual Sum or Average 0.313208E+13 0.118765E+12 0.00 0.280166E+13 0.599256E+12
Minimum of Months 0.617361E+11 0.415558E+10 0.00 0.164110E+12 0.147027E+11
Maximum of Months 0.475497E+12 0.147979E+11 0.00 0.284352E+12 0.160654E+12