Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2024-07-03 12:20:08
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2689.47 | 539.82 | 539.82 |
Net Site Energy | 2689.47 | 539.82 | 539.82 |
Total Source Energy | 6957.32 | 1396.44 | 1396.44 |
Net Source Energy | 6957.32 | 1396.44 | 1396.44 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 749.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 154.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 235.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 165.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 56.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1940.44 | 749.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 749.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 154.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 235.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 165.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 3.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 56.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 749.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 154.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 235.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 165.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 3.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 56.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 76.60 | 150.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 389.47 | 150.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 76.60 | 150.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 389.47 | 150.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1940.436 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1940.436 | 100.00 |
Total On-Site and Utility Electric Sources | 1940.436 | 100.00 |
Total Electricity End Uses | 1940.436 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 441.17 |
Time Setpoint Not Met During Occupied Cooling | 19.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2750.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 19-JUL-15:09 | 11-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 323034.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 68139.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27175.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4240.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 192352.22 | 323034.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 323034.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 68139.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 27175.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4240.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 811.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 490.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 746.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 525.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 12.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 180.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6145.36 | 811.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 162.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 105.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 36.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1233.47 | 162.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 162.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 105.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 36.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1233.47 | 162.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.42 | 0.219100 | 0.300000 | 1.03 | 0.584267 | 0.500000 | 0.001739 | 0.000175 | 1.03 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.80 | 0.267795 | 0.300000 | 0.839583 | 0.714121 | 0.500000 | 0.001423 | 0.000323 | 1.59 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 3.18 | 0.235784 | 0.300000 | 0.953571 | 0.628756 | 0.500000 | 0.001616 | 0.000644 | 3.18 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.49 | 0.105988 | 0.300000 | 0.447198 | 0.300000 | 0.500000 | 0.003595 | 0.000301 | 1.49 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.962701 | 0.103897 | 0.300000 | 0.288810 | 0.300000 | 0.500000 | 0.003667 | 0.000195 | 0.962701 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.49 | 0.106036 | 0.300000 | 0.446993 | 0.300000 | 0.500000 | 0.003593 | 0.000301 | 1.49 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.07 | 0.093822 | 0.300000 | 0.319803 | 0.300000 | 0.500000 | 0.004061 | 0.000197 | 0.975220 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.13 | 0.139799 | 0.300000 | 0.339041 | 0.372796 | 0.500000 | 0.002725 | 0.000229 | 1.13 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.772409 | 0.129493 | 0.300000 | 0.231723 | 0.345315 | 0.500000 | 0.002942 | 0.000148 | 0.731856 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.13 | 0.139799 | 0.300000 | 0.339041 | 0.372797 | 0.500000 | 0.002725 | 0.000229 | 1.13 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.807464 | 0.123863 | 0.300000 | 0.242239 | 0.330302 | 0.500000 | 0.003076 | 0.000150 | 0.743904 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 1.15 | 0.137290 | 0.300000 | 0.345236 | 0.366107 | 0.500000 | 0.002775 | 0.000233 | 1.15 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.938872 | 0.300000 | 0.500000 | 0.003576 | 0.000151 | 0.746844 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.15 | 0.137412 | 0.300000 | 0.344931 | 0.366431 | 0.500000 | 0.002773 | 0.000233 | 1.15 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.969278 | 0.103185 | 0.300000 | 0.290783 | 0.300000 | 0.500000 | 0.003692 | 0.000153 | 0.758964 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19963.23 | 0.000175 | 446.76 |
CORE_MID VAV BOX REHEAT COIL | 36895.10 | 0.000323 | 863.16 |
CORE_TOP VAV BOX REHEAT COIL | 73628.78 | 0.000644 | 1720.58 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 34448.15 | 0.000301 | 804.46 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22246.53 | 0.000195 | 519.52 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34432.41 | 0.000301 | 804.10 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22535.40 | 0.000197 | 526.26 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 26130.33 | 0.000229 | 610.31 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 16920.64 | 0.000148 | 395.20 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 26130.29 | 0.000229 | 610.31 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 17198.62 | 0.000150 | 401.69 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 26606.02 | 0.000233 | 621.41 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 17265.92 | 0.000151 | 403.25 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 26582.57 | 0.000233 | 620.86 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 17545.57 | 0.000153 | 409.78 |
PACU_VAV_BOT HEATING COIL | 28102.38 | 0.000246 | 470.02 |
PACU_VAV_MID HEATING COIL | 28628.40 | 0.000250 | 476.09 |
PACU_VAV_TOP HEATING COIL | 24400.27 | 0.000213 | 421.49 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.63 | 2.18 | 7.26 | 4.46 | 5.85 | 5.85 | 0.300000 | 0.763074 | 5.85 |
PACU_VAV_MID | 3.50 | 2.10 | 7.01 | 5.39 | 5.57 | 5.57 | 0.300000 | 0.968704 | 5.57 |
PACU_VAV_TOP | 4.09 | 2.46 | 8.19 | 8.10 | 6.81 | 8.10 | 0.300000 | 1.00 | 8.10 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.85 |
PACU_VAV_MID_OA_CONTROLLER | 5.57 |
PACU_VAV_TOP_OA_CONTROLLER | 8.10 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.85 | 112364.91 | 0.792896 | 1.95 | 37451.22 | 0.792896 |
PACU_VAV_MID COOLING COIL | 5.57 | 108383.58 | 0.786593 | 1.86 | 36124.25 | 0.786593 |
PACU_VAV_TOP COOLING COIL | 8.10 | 152103.52 | 0.800984 | 2.70 | 50696.10 | 0.800984 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.85 |
PACU_VAV_MID FAN | 5.57 |
PACU_VAV_TOP FAN | 8.10 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000246 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000250 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000213 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004371 | 0.524550 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.004371 | 1316.43 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 499660.60 | 499660.60 | 0.004371 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
43 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
44 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
45 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
46 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
47 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
48 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
49 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39925.86983 | 45914.75030 | 2.97444 | 3.42060 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7999.58357 | 9999.47946 | 0.58284 | 0.72855 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32691.56855 | 37595.30383 | 2.43357 | 2.79861 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 17194.49904 | 21493.12381 | 1.26902 | 1.58628 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 36663.60904 | 42163.15040 | 2.75431 | 3.16746 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 34213.12524 | 42766.40655 | 2.54286 | 3.17857 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10633.58441 | 12228.62207 | 0.79890 | 0.91873 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15987.36885 | 19984.21106 | 1.19253 | 1.49066 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11036.23138 | 12691.66608 | 0.82915 | 0.95352 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10324.48921 | 12905.61151 | 0.77016 | 0.96270 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14507.38615 | 16683.49408 | 1.08993 | 1.25342 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15980.07023 | 19975.08778 | 1.19198 | 1.48998 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12338.26317 | 14189.00265 | 0.92696 | 1.06601 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.99800 | 1.33646E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10458.35923 | 13072.94904 | 0.78018 | 0.97522 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7619.47920 | 8762.40108 | 0.57243 | 0.65829 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12129.67605 | 15162.09507 | 0.90411 | 1.13014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8940.39284 | 10281.45177 | 0.67166 | 0.77241 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.23900 | 1.33598E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7854.33023 | 9817.91279 | 0.58549 | 0.73186 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11018.68925 | 12671.49264 | 0.82780 | 0.95197 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12129.65911 | 15162.07389 | 0.90411 | 1.13014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9346.15192 | 10748.07471 | 0.70214 | 0.80746 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 28.37800 | 1.33635E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7983.13574 | 9978.91967 | 0.59512 | 0.74390 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8781.70082 | 10098.95594 | 0.65976 | 0.75872 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12351.98643 | 15439.98304 | 0.92063 | 1.15079 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10866.87666 | 12496.90816 | 0.81641 | 0.93887 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.44850 | 1.33584E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8015.57328 | 10019.46660 | 0.59747 | 0.74684 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12772.58308 | 14688.47054 | 0.95959 | 1.10352 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12341.12020 | 15426.40025 | 0.91982 | 1.14977 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11218.81464 | 12901.63684 | 0.84285 | 0.96928 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8145.16096 | 10181.45121 | 0.60717 | 0.75896 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 83783.23 | 5.85079 | 5.85079 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 32890.81 | 4.46459 | 4.46459 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 80011.77 | 5.56686 | 5.56686 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 32889.90 | 5.39264 | 5.39264 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 96244.10 | 6.80932 | 6.80932 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 32195.56 | 8.09713 | 8.09713 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.42060 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21910 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.02618 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58427 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73893E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74647E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.02618 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19963.22640 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74647E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 446.75631 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.79861 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26780 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.83958 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71412 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42273E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.22774E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.58628 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36895.09543 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.22774E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 863.15720 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.17857 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23578 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.95357 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62876 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61589E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.44137E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.17857 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 73628.78116 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.44137E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1720.57718 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49066 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10599 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44720 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.59476E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.01367E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.49066 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34448.15277 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01367E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 804.46455 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96270 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10390 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28881 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.66709E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94622E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.96270 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22246.53190 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94622E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 519.51575 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48998 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10604 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44699 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.59311E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.01230E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.48998 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34432.40521 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01230E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 804.09694 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06601 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.38221E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31980 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.06088E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97149E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.97522 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22535.39554 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97149E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 526.25871 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13014 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13980 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33904 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37280 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72535E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28600E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13014 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26130.32750 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28600E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 610.30727 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77241 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12949 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23172 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34532 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94224E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48029E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73186 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16920.63912 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48029E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 395.19752 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13014 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13980 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33904 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37280 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72535E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28599E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.13014 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26130.29093 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28599E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 610.30641 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80746 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12386 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24224 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33030 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.07597E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50461E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74390 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17198.61517 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50461E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 401.68615 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15079 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13729 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34524 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36611 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77514E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.32761E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15079 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26606.02097 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32761E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 621.40655 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93887 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.57632E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51050E-004 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74684 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17265.92071 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51050E-004 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 403.25394 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14977 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13741 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34493 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36643 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77269E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.32556E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.14977 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26582.57319 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32556E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 620.85920 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96928 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10319 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29078 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.69239E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53496E-004 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75896 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17545.56956 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53496E-004 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 409.78162 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.63038 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.17823 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.26075 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.46459 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.85079 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.85079 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.76307 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.50366 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.10219 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.00732 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.39264 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.56686 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.56686 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.96870 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.09396 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.45638 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.18792 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 8.09713 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.80932 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 8.09713 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.85079 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.56686 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 8.09713 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.85079 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.85079 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 112364.90532 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.79290 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.95007 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37451.22294 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.79290 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 28102.38016 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.45852E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 470.02049 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.85079 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.45852E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.56686 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.56686 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108383.58149 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78659 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.85544 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36124.24771 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78659 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 28628.40263 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.50454E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 476.09325 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.56686 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.50454E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.09713 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 8.09713 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 152103.51960 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80098 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.69877 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 50696.10308 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80098 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 24400.27026 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13464E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 421.49017 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 8.09713 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.13464E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.37125E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.52455 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.37125E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1316.42820 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 499660.59860 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 499660.60000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.37125E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18943.71 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 35001.94 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 69851.10 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32680.81 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21105.19 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32665.87 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21379.23 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 24789.71 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 16052.53 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 24789.68 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 16316.24 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 25241.00 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 16380.09 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 25218.76 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 16645.40 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 22309.51 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 22467.44 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 20630.83 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 111156.10 | 379280.35 | 11.45 | 2.94 | 3.28 | 3.44 | 3.64 | 10.04 | 11.18 | 11.75 | 12.43 | 6.5971 | 5.2821 | 3.5594 | 1.4043 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 107276.86 | 366043.84 | 11.48 | 2.95 | 3.29 | 3.46 | 3.65 | 10.06 | 11.21 | 11.79 | 12.45 | 6.2770 | 5.0191 | 3.3805 | 1.3438 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 150330.21 | 512947.97 | 11.40 | 2.93 | 3.26 | 3.43 | 3.63 | 10.00 | 11.12 | 11.70 | 12.39 | 9.1300 | 7.3065 | 4.9212 | 1.9332 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 8.7046654072E-002 | 5.1915070998E-002 | Pass | Pass | 0.4954753973 | 0.4922388793 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2192185599 | 0.1521132236 | Pass | Pass | 0.4990087369 | 0.4736292186 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.8866848962E-002 | 4.3973731439E-002 | Pass | Pass | 0.5118394120 | 0.4699232072 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.7864216395E-002 | 4.2565882768E-002 | Pass | Pass | 0.5135901200 | 0.4637962642 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.6678186053E-002 | 1.0471725869E-002 | Pass | Pass | 0.4942989605 | 0.4872535349 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 7.9554432633E-002 | 8.9026703682E-002 | Pass | Pass | 11.2030026669 | 32.4093323428 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4157782556 | 0.4173070563 | Pass | Pass | 5.7773958186 | 23.7238201130 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4231384599 | 0.4247796023 | Pass | Pass | 6.7307938957 | 28.5939957147 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3921675882 | 0.4010635818 | Pass | Pass | 7.7706791379 | 33.5022096215 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4273504720 | 0.4304168180 | Pass | Pass | 3.6102866822 | 10.4498778931 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2961203160 | 0.2908017578 | Pass | Pass | 8.8966984409 | 26.9889018150 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3036679411 | 0.2983013433 | Pass | Pass | 9.0872235794 | 28.5599329113 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2672533542 | 0.2704612264 | Pass | Pass | 9.1601130059 | 29.6896400217 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3075117933 | 0.3033097813 | Pass | Pass | 10.0459320090 | 33.3625236777 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2937566518 | 0.2919132016 | Pass | Pass | 9.5262723932 | 32.6158419887 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3000411946 | 0.2987438019 | Pass | Pass | 8.7400365076 | 31.5425685942 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2705870961 | 0.2764920239 | Pass | Pass | 8.2629378713 | 27.0066150617 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3043068979 | 0.3046943275 | Pass | Pass | 10.2009123410 | 37.7699035466 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3613.87 | 177.98 | 0.00 | 2175.33 | 1069.27 | 7036.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 183.92 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 429.15 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.67 | 83.67 | 235.79 | |
Exterior Lighting Total | 15013.15 | 235.79 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 499660.60 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 112364.91 | 89093.63 | 23271.28 | 0.79 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108383.58 | 85253.74 | 23129.84 | 0.79 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 152103.52 | 121832.51 | 30271.01 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 111156.1 | 2.94 | 10.04 | N/A | N/A | 11.45 | |
PACU_VAV_MID COOLING COIL | 107276.9 | 2.95 | 10.06 | N/A | N/A | 11.48 | |
PACU_VAV_TOP COOLING COIL | 150330.2 | 2.93 | 10.00 | N/A | N/A | 11.40 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19963.23 | 18943.71 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 36895.10 | 35001.94 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 73628.78 | 69851.10 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 34448.15 | 32680.81 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 22246.53 | 21105.19 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 34432.41 | 32665.87 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 22535.40 | 21379.23 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 26130.33 | 24789.71 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16920.64 | 16052.53 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26130.29 | 24789.68 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 17198.62 | 16316.24 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 26606.02 | 25241.00 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 17265.92 | 16380.09 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26582.57 | 25218.76 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 17545.57 | 16645.40 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 28102.38 | 22309.51 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 28628.40 | 22467.44 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 24400.27 | 20630.83 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.85 | 12941.72 | 2211.96 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.57 | 12313.68 | 2211.96 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 8.10 | 17795.72 | 2197.78 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004371 | 1316.43 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 111156.10 | 2.94 | 10.04 | 11.45 | 6.5971 | 3.28 | 11.18 | 5.2821 | 3.44 | 11.75 | 3.5594 | 3.64 | 12.43 | 1.4043 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107276.86 | 2.95 | 10.06 | 11.48 | 6.2770 | 3.29 | 11.21 | 5.0191 | 3.46 | 11.79 | 3.3805 | 3.65 | 12.45 | 1.3438 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 150330.21 | 2.93 | 10.00 | 11.40 | 9.1300 | 3.26 | 11.12 | 7.3065 | 3.43 | 11.70 | 4.9212 | 3.63 | 12.39 | 1.9332 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39925.87 | 45914.75 | 46.68 | 2.974 | 3.421 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_MID | 32691.57 | 37595.30 | 38.22 | 2.434 | 2.799 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_TOP | 36663.61 | 42163.15 | 42.87 | 2.754 | 3.167 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00882 | 30.30 | 0.01337 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10633.58 | 12228.62 | 58.98 | 0.799 | 0.919 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00896 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11036.23 | 12691.67 | 96.69 | 0.829 | 0.954 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00880 | 25.98 | 0.01336 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14507.39 | 16683.49 | 80.47 | 1.090 | 1.253 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00884 | 30.14 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12338.26 | 14189.00 | 108.10 | 0.927 | 1.066 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00876 | 29.00 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7619.48 | 8762.40 | 42.26 | 0.572 | 0.658 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00900 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8940.39 | 10281.45 | 78.33 | 0.672 | 0.772 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00878 | 26.24 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11018.69 | 12671.49 | 61.12 | 0.828 | 0.952 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00885 | 30.14 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9346.15 | 10748.07 | 81.89 | 0.702 | 0.807 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00877 | 28.38 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8781.70 | 10098.96 | 48.71 | 0.660 | 0.759 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00901 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10866.88 | 12496.91 | 95.21 | 0.816 | 0.939 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00878 | 25.45 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12772.58 | 14688.47 | 70.84 | 0.960 | 1.104 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00886 | 30.07 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11218.81 | 12901.64 | 98.30 | 0.843 | 0.969 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00877 | 28.84 | 0.01336 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7999.58 | 9999.48 | 10.17 | 0.583 | 0.729 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_MID | 17194.50 | 21493.12 | 21.85 | 1.269 | 1.586 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_TOP | 34213.13 | 42766.41 | 43.48 | 2.543 | 3.179 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15987.37 | 19984.21 | 96.38 | 1.193 | 1.491 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10324.49 | 12905.61 | 98.32 | 0.770 | 0.963 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15980.07 | 19975.09 | 96.34 | 1.192 | 1.490 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10458.36 | 13072.95 | 99.60 | 0.780 | 0.975 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12129.68 | 15162.10 | 73.13 | 0.904 | 1.130 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7854.33 | 9817.91 | 74.80 | 0.585 | 0.732 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12129.66 | 15162.07 | 73.13 | 0.904 | 1.130 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7983.14 | 9978.92 | 76.03 | 0.595 | 0.744 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12351.99 | 15439.98 | 74.47 | 0.921 | 1.151 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8015.57 | 10019.47 | 76.33 | 0.597 | 0.747 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12341.12 | 15426.40 | 74.40 | 0.920 | 1.150 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8145.16 | 10181.45 | 77.57 | 0.607 | 0.759 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -16.30 | 0.00092 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.85 | 5.85 | 4.46 | 4.46 | 5.8508 | 4.4646 | 5.8508 | 0.7631 | 0.3000 |
PACU_VAV_MID | 5.57 | 5.57 | 5.39 | 5.39 | 5.5669 | 5.3926 | 5.5669 | 0.9687 | 0.3000 |
PACU_VAV_TOP | 6.81 | 6.81 | 8.10 | 8.10 | 6.8093 | 8.0971 | 8.0971 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19963.226 | 19963.226 | 1.026181 | 0.00017465 | 446.756 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19963.23 | 19963.23 | 1.026181 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 9999.48 | 0.00 | 20057.50 | 20057.50 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 36895.095 | 36895.095 | 1.586276 | 0.00032277 | 863.157 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36895.10 | 36895.10 | 1.586276 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 21493.12 | 0.00 | 37064.14 | 37064.14 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 73628.781 | 73628.781 | 3.178570 | 0.00064414 | 1720.577 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 73628.78 | 73139.62 | 3.178570 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 42766.41 | 0.00 | 73966.29 | 73966.29 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 34448.153 | 34448.153 | 1.490660 | 0.00030137 | 804.465 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34448.15 | 34300.43 | 1.490660 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00774057 | 48.8083 | 19984.21 | 0.00 | 34606.10 | 34606.10 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 22246.532 | 22246.532 | 0.962701 | 0.00019462 | 519.516 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22246.53 | 22151.97 | 0.962701 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00773237 | 48.7574 | 12905.61 | 0.00 | 22348.54 | 22348.54 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 34432.405 | 34432.405 | 1.489978 | 0.00030123 | 804.097 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34432.41 | 34284.73 | 1.489978 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00774045 | 48.8076 | 19975.09 | 0.00 | 34590.28 | 34590.28 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 22535.396 | 22535.396 | 0.975220 | 0.00019715 | 526.259 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22535.40 | 22535.40 | 0.975220 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00773566 | 48.7779 | 13072.95 | 0.00 | 22638.72 | 22638.72 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 26130.327 | 26130.327 | 1.130138 | 0.00022860 | 610.307 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26130.33 | 26004.73 | 1.130138 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00781779 | 49.2871 | 15162.10 | 0.00 | 26250.13 | 26250.13 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 16920.639 | 16920.639 | 0.731856 | 0.00014803 | 395.198 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16920.64 | 16920.64 | 0.731856 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00781252 | 49.2545 | 9817.91 | 0.00 | 16998.22 | 16998.22 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 26130.291 | 26130.291 | 1.130136 | 0.00022860 | 610.306 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26130.29 | 26004.69 | 1.130136 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00781779 | 49.2871 | 15162.07 | 0.00 | 26250.10 | 26250.10 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 17198.615 | 17198.615 | 0.743904 | 0.00015046 | 401.686 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17198.62 | 17198.62 | 0.743904 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00781549 | 49.2730 | 9978.92 | 0.00 | 17277.47 | 17277.47 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 26606.021 | 26606.021 | 1.150786 | 0.00023276 | 621.407 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26606.02 | 26479.85 | 1.150786 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00772251 | 48.6952 | 15439.98 | 0.00 | 26728.01 | 26728.01 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 17265.921 | 17265.921 | 0.746844 | 0.00015105 | 403.254 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17265.92 | 17265.92 | 0.746844 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00771513 | 48.6494 | 10019.47 | 0.00 | 17345.08 | 17345.08 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 26582.573 | 26582.573 | 1.149770 | 0.00023256 | 620.859 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26582.57 | 26456.46 | 1.149770 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00772228 | 48.6938 | 15426.40 | 0.00 | 26704.45 | 26704.45 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 17545.570 | 17545.570 | 0.758964 | 0.00015350 | 409.782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17545.57 | 17545.57 | 0.758964 | 12.89 | 11.41 | 0.00800000 | 32.11 | 18.46 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00771950 | 48.6767 | 10181.45 | 0.00 | 17626.02 | 17626.02 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 112364.905 | 89093.629 | 5.850794 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 113918.90 | 95074.92 | 5.850794 | 25.03 | 17.40 | 0.00959694 | 11.05 | 11.05 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 16.3414 | 24.00 | 0.00886053 | 46.4766 | 67722.15 | 0.00 | 115863.30 | 89206.33 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 28102.380 | 28102.380 | 1.755238 | 0.00024585 | 470.020 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28102.38 | 28102.38 | 1.755238 | -0.68 | -0.68 | 0.00386342 | 12.89 | 11.41 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 54.4712 | 18.39 | 0.00764038 | 56.6713 | 8389.72 | 0.00 | 26998.45 | 26998.45 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 108383.581 | 85253.742 | 5.566862 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 110063.94 | 90763.81 | 5.566862 | 25.08 | 17.48 | 0.00968133 | 11.05 | 11.05 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 17.1748 | 24.00 | 0.00891645 | 46.7663 | 64390.90 | 0.00 | 111758.02 | 85380.86 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 28628.403 | 28628.403 | 1.670059 | 0.00025045 | 476.093 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28628.40 | 28628.40 | 1.670059 | -1.64 | -1.64 | 0.00362251 | 12.89 | 11.41 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 57.2495 | 17.71 | 0.00761041 | 58.9044 | 8483.80 | 0.00 | 27187.51 | 27187.51 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 152103.520 | 121832.506 | 8.097129 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 153820.37 | 130227.19 | 8.097129 | 24.88 | 17.26 | 0.00949231 | 11.06 | 11.06 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 11.8079 | 24.00 | 0.00885859 | 46.4672 | 78727.63 | 0.00 | 156839.15 | 121944.04 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 24400.270 | 24400.270 | 2.429139 | 0.00021346 | 421.490 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24400.27 | 24400.27 | 2.429139 | 4.37 | 3.80 | 0.00485990 | 12.89 | 11.41 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 39.3596 | 16.70 | 0.00776383 | 64.0580 | 10372.67 | 0.00 | 24973.65 | 24973.65 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19963.226 | 19963.226 | 1.026181 | 0.00017465 | 446.756 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 3.9165 | 3.995357 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19963.23 | 19963.23 | 1.0000 | 1.20466038 | 1.026181 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.17462920 | 60.00 | 32.22 | 27.78 | 0.000 | 19963.23 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.89 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 9999.48 | 0.00 | 20057.50 | 20057.50 | 1.20466038 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.13 | 17.74 | 0.00800000 | 49709.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 36895.095 | 36895.095 | 1.586276 | 0.00032277 | 863.157 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 7.2384 | 7.384031 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36895.10 | 36895.10 | 1.0000 | 1.86216947 | 1.586276 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.32274146 | 60.00 | 32.22 | 27.78 | 0.000 | 36895.10 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 21493.12 | 0.00 | 37064.14 | 37064.14 | 1.86216947 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.32 | 18.80 | 0.00800000 | 52963.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 73628.781 | 73628.781 | 3.178570 | 0.00064414 | 1720.577 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 14.4450 | 14.735759 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 73628.78 | 73139.62 | 1.0000 | 3.73140357 | 3.178570 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.64407099 | 60.00 | 32.22 | 27.78 | 0.000 | 73628.78 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 42766.41 | 0.00 | 73966.29 | 73966.29 | 3.73140357 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.24 | 18.78 | 0.00800000 | 52882.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34448.153 | 34448.153 | 1.490660 | 0.00030137 | 804.465 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 6.7583 | 6.894310 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34448.15 | 34300.43 | 1.0000 | 1.74992366 | 1.490660 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.30133673 | 60.00 | 32.22 | 27.78 | 0.000 | 34448.15 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00774057 | 21.00 | 0.00774057 | 48.8083 | 19984.21 | 0.00 | 34606.10 | 34606.10 | 1.74992366 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22246.532 | 22246.532 | 0.962701 | 0.00019462 | 519.516 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 4.3645 | 4.452329 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22246.53 | 22151.97 | 1.0000 | 1.13013930 | 0.962701 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.19460251 | 60.00 | 32.22 | 27.78 | 0.000 | 22246.53 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00773237 | 21.00 | 0.00773237 | 48.7574 | 12905.61 | 0.00 | 22348.54 | 22348.54 | 1.13013930 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34432.405 | 34432.405 | 1.489978 | 0.00030123 | 804.097 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 6.7552 | 6.891159 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34432.41 | 34284.73 | 1.0000 | 1.74912260 | 1.489978 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.30119897 | 60.00 | 32.22 | 27.78 | 0.000 | 34432.41 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00774045 | 21.00 | 0.00774045 | 48.8076 | 19975.09 | 0.00 | 34590.28 | 34590.28 | 1.74912260 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22535.396 | 22535.396 | 0.975220 | 0.00019715 | 526.259 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 4.4212 | 4.510141 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22535.40 | 22535.40 | 1.0000 | 1.14483554 | 0.975220 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.19712936 | 60.00 | 32.22 | 27.78 | 0.000 | 22535.40 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00773566 | 21.00 | 0.00773566 | 48.7779 | 13072.95 | 0.00 | 22638.72 | 22638.72 | 1.14483554 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26130.327 | 26130.327 | 1.130138 | 0.00022860 | 610.307 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 5.1264 | 5.229615 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26130.33 | 26004.73 | 1.0000 | 1.32669733 | 1.130138 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.22857618 | 60.00 | 32.22 | 27.78 | 0.000 | 26130.33 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781779 | 21.00 | 0.00781779 | 49.2871 | 15162.10 | 0.00 | 26250.13 | 26250.13 | 1.32669733 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52845.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16920.639 | 16920.639 | 0.731856 | 0.00014803 | 395.198 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 3.3196 | 3.386427 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16920.64 | 16920.64 | 1.0000 | 0.85914462 | 0.731856 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.14801403 | 60.00 | 32.22 | 27.78 | 0.000 | 16920.64 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781252 | 21.00 | 0.00781252 | 49.2545 | 9817.91 | 0.00 | 16998.22 | 16998.22 | 0.85914462 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52844.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26130.291 | 26130.291 | 1.130136 | 0.00022860 | 610.306 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 5.1264 | 5.229608 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26130.29 | 26004.69 | 1.0000 | 1.32669547 | 1.130136 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.22857586 | 60.00 | 32.22 | 27.78 | 0.000 | 26130.29 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781779 | 21.00 | 0.00781779 | 49.2871 | 15162.07 | 0.00 | 26250.10 | 26250.10 | 1.32669547 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52845.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17198.615 | 17198.615 | 0.743904 | 0.00015046 | 401.686 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 3.3742 | 3.442060 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17198.62 | 17198.62 | 1.0000 | 0.87328828 | 0.743904 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.15044564 | 60.00 | 32.22 | 27.78 | 0.000 | 17198.62 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781549 | 21.00 | 0.00781549 | 49.2730 | 9978.92 | 0.00 | 17277.47 | 17277.47 | 0.87328828 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52844.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26606.021 | 26606.021 | 1.150786 | 0.00023276 | 621.407 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 5.2198 | 5.324819 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26606.02 | 26479.85 | 1.0000 | 1.35093677 | 1.150786 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.23273733 | 60.00 | 32.22 | 27.78 | 0.000 | 26606.02 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00772251 | 21.00 | 0.00772251 | 48.6952 | 15439.98 | 0.00 | 26728.01 | 26728.01 | 1.35093677 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52844.6 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17265.921 | 17265.921 | 0.746844 | 0.00015105 | 403.254 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 3.3874 | 3.455530 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17265.92 | 17265.92 | 1.0000 | 0.87673860 | 0.746844 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.15103440 | 60.00 | 32.22 | 27.78 | 0.000 | 17265.92 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00771513 | 21.00 | 0.00771513 | 48.6494 | 10019.47 | 0.00 | 17345.08 | 17345.08 | 0.87673860 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26582.573 | 26582.573 | 1.149770 | 0.00023256 | 620.859 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 5.2152 | 5.320126 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26582.57 | 26456.46 | 1.0000 | 1.34974385 | 1.149770 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.23253222 | 60.00 | 32.22 | 27.78 | 0.000 | 26582.57 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00772228 | 21.00 | 0.00772228 | 48.6938 | 15426.40 | 0.00 | 26704.45 | 26704.45 | 1.34974385 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52844.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17545.570 | 17545.570 | 0.758964 | 0.00015350 | 409.782 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 3.4422 | 3.511498 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17545.57 | 17545.57 | 1.0000 | 0.89096740 | 0.758964 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 32.11 | 18.46 | 0.00800000 | 52751.6 | 0.15348064 | 60.00 | 32.22 | 27.78 | 0.000 | 17545.57 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00771950 | 21.00 | 0.00771950 | 48.6767 | 10181.45 | 0.00 | 17626.02 | 17626.02 | 0.89096740 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.8 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 112364.905 | 89093.629 | 5.850794 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6802 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.850794 | 6.86839555 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 113918.90 | 95074.92 | 1.0138 | 6.86839555 | 5.850794 | 25.03 | 17.40 | 0.00959694 | 49597.3 | 11.05 | 11.05 | 0.00850000 | 32532.4 | -999.0 | -999.00 | -999.00 | -999.00 | 12941.725 | 100977.17 | 30.30 | 0.01336696 | 21.83 | 0.95610000 | 16.3414 | 24.00 | 0.00886053 | 24.00 | 0.00886053 | 46.4766 | 67722.15 | 0.00 | 115863.30 | 89206.33 | 6.59714585 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.44 | 13.43 | 0.00960040 | 37759.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 28102.380 | 28102.380 | 1.755238 | 0.00024585 | 470.020 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.850794 | 6.86839555 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 5.5133 | 5.624294 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28102.38 | 28102.38 | 1.0000 | 2.06051867 | 1.755238 | -0.68 | -0.68 | 0.00386342 | 8970.3 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 0.24582680 | 60.00 | 32.22 | 27.78 | 0.000 | 28102.38 | -16.30 | 0.00092409 | -16.30 | 0.95610000 | 54.4712 | 18.00 | 0.00738007 | 18.39 | 0.00764038 | 56.6713 | 8389.72 | 0.00 | 26998.45 | 26998.45 | 2.06051867 | 2.80 | 1.75 | 0.00386342 | 12495.8 | 15.75 | 8.42 | 0.00386342 | 25598.6 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108383.581 | 85253.742 | 5.566862 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8371 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.566862 | 6.53508060 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 110063.94 | 90763.81 | 1.0155 | 6.53508060 | 5.566862 | 25.08 | 17.48 | 0.00968133 | 49866.6 | 11.05 | 11.05 | 0.00850000 | 32532.7 | -999.0 | -999.00 | -999.00 | -999.00 | 12313.678 | 97750.26 | 30.30 | 0.01336696 | 21.83 | 0.95610000 | 17.1748 | 24.00 | 0.00891645 | 24.00 | 0.00891645 | 46.7663 | 64390.90 | 0.00 | 111758.02 | 85380.86 | 6.27699432 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.36 | 13.34 | 0.00953707 | 37518.0 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 28628.403 | 28628.403 | 1.670059 | 0.00025045 | 476.093 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.566862 | 6.53508060 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 5.6165 | 5.729570 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28628.40 | 28628.40 | 1.0000 | 1.96052418 | 1.670059 | -1.64 | -1.64 | 0.00362251 | 7397.7 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 0.25042821 | 60.00 | 32.22 | 27.78 | 0.000 | 28628.40 | -16.30 | 0.00092409 | -16.30 | 0.95610000 | 57.2495 | 17.99 | 0.00723611 | 17.71 | 0.00761041 | 58.9044 | 8483.80 | 0.00 | 27187.51 | 27187.51 | 1.96052418 | 2.80 | 1.42 | 0.00362251 | 11892.1 | 16.51 | 8.50 | 0.00362251 | 25759.6 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 152103.520 | 121832.506 | 8.097129 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.4857 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 8.097129 | 9.50542467 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 153820.37 | 130227.19 | 1.0113 | 9.50542467 | 8.097129 | 24.88 | 17.26 | 0.00949231 | 49183.4 | 11.06 | 11.06 | 0.00850000 | 32544.1 | -999.0 | -999.00 | -999.00 | -999.00 | 17795.717 | 136024.65 | 30.30 | 0.01336696 | 21.83 | 0.95610000 | 11.8079 | 24.00 | 0.00885859 | 24.00 | 0.00885859 | 46.4672 | 78727.63 | 0.00 | 156839.15 | 121944.04 | 9.13003225 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.61 | 13.58 | 0.00968614 | 38144.0 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24400.270 | 24400.270 | 2.429139 | 0.00021346 | 421.490 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 8.097129 | 9.50542467 | 4197.9300 | 999.8980 | 4.37080298 | 54.44 | 82.22 | 27.78 | 509716.47 | 4.7870 | 4.883369 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24400.27 | 24400.27 | 1.0000 | 2.85162740 | 2.429139 | 4.37 | 3.80 | 0.00485990 | 16588.7 | 12.89 | 11.41 | 0.00800000 | 33150.5 | 0.21344243 | 60.00 | 32.22 | 27.78 | 0.000 | 24400.27 | -16.30 | 0.00092409 | -16.30 | 0.95610000 | 39.3596 | 17.79 | 0.00741450 | 16.70 | 0.00776383 | 64.0580 | 10372.67 | 0.00 | 24973.65 | 24973.65 | 2.85162740 | 2.80 | 2.80 | 0.00485990 | 14993.2 | 11.44 | 7.55 | 0.00485990 | 23750.8 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | FixedDryBulb | 0.00 | 5.85 | - | |||
PACU_VAV_MID_OA_CONTROLLER | FixedDryBulb | 0.00 | 5.57 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | FixedDryBulb | 0.00 | 8.10 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2181.00 | 2745.00 | 91.17 |
CORE_MID | 2289.67 | 3689.33 | 804.00 |
CORE_TOP | 2834.83 | 4152.50 | 1634.83 |
PERIMETER_TOP_ZN_3 | 3264.00 | 4832.33 | 2468.67 |
PERIMETER_TOP_ZN_2 | 3545.50 | 4361.17 | 2311.83 |
PERIMETER_TOP_ZN_1 | 3239.17 | 4415.50 | 2082.33 |
PERIMETER_TOP_ZN_4 | 3405.50 | 4612.00 | 2364.33 |
PERIMETER_BOT_ZN_3 | 3053.17 | 4867.67 | 2304.17 |
PERIMETER_BOT_ZN_2 | 3373.83 | 4279.50 | 2098.83 |
PERIMETER_BOT_ZN_1 | 3138.00 | 4488.83 | 2048.00 |
PERIMETER_BOT_ZN_4 | 3292.50 | 4442.17 | 2134.33 |
PERIMETER_MID_ZN_3 | 3150.50 | 4473.33 | 2078.67 |
PERIMETER_MID_ZN_2 | 2795.67 | 3637.00 | 1732.33 |
PERIMETER_MID_ZN_1 | 3056.83 | 4001.50 | 1635.17 |
PERIMETER_MID_ZN_4 | 3186.50 | 4406.50 | 1990.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4947.33 | 5140.83 | 2750.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.00 | 0.00 | 2.00 | 0.00 |
CORE_MID | 4.33 | 0.00 | 4.17 | 0.00 |
CORE_TOP | 15.67 | 0.00 | 11.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 135.67 | 0.00 | 40.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 135.83 | 3.17 | 36.33 | 3.17 |
PERIMETER_TOP_ZN_1 | 111.67 | 2.50 | 27.67 | 2.50 |
PERIMETER_TOP_ZN_4 | 134.83 | 8.83 | 39.17 | 5.67 |
PERIMETER_BOT_ZN_3 | 39.50 | 0.00 | 14.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 34.33 | 0.67 | 11.17 | 0.67 |
PERIMETER_BOT_ZN_1 | 426.00 | 0.00 | 409.33 | 0.00 |
PERIMETER_BOT_ZN_4 | 38.67 | 2.83 | 12.33 | 1.50 |
PERIMETER_MID_ZN_3 | 52.67 | 0.00 | 16.17 | 0.00 |
PERIMETER_MID_ZN_2 | 46.67 | 3.50 | 9.67 | 3.50 |
PERIMETER_MID_ZN_1 | 42.00 | 3.33 | 12.00 | 3.33 |
PERIMETER_MID_ZN_4 | 49.33 | 9.00 | 11.83 | 5.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 574.67 | 24.67 | 441.17 | 19.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.842 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.600 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.590 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 1.191 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.315 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.269 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.416 | 0.120 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.945 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.104 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.035 | 0.876 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 1.114 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 1.014 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.329 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.138 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 1.406 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13321543.72 | 0.00 | 13321543.72 | 0.00 | 13321543.72 | 13393058.27 | 6003.46 | 63.31 | 2693.23 | 134.57 |
CORE_MID | 9510649.50 | 0.00 | 9510649.50 | 0.00 | 9510649.50 | 13393058.27 | 6848.26 | 29.67 | 1882.08 | 184.28 |
CORE_TOP | 9323620.84 | 0.00 | 9323620.84 | 0.00 | 9323620.84 | 13393058.27 | 6814.72 | 22.59 | 1922.69 | 30.41 |
PERIMETER_TOP_ZN_3 | 3985330.96 | 0.00 | 3985330.96 | 750436.27 | 4735767.24 | 2823374.22 | 4227.26 | 19.71 | 4513.03 | 30.41 |
PERIMETER_TOP_ZN_2 | 2779037.36 | 0.00 | 2779037.36 | 500287.84 | 3279325.20 | 1787429.43 | 4198.67 | 1.64 | 4559.69 | 30.41 |
PERIMETER_TOP_ZN_1 | 4238064.45 | 0.00 | 4238064.45 | 750436.27 | 4988500.72 | 2823374.22 | 4201.38 | 1.62 | 4557.00 | 30.41 |
PERIMETER_TOP_ZN_4 | 2994903.64 | 0.00 | 2994903.64 | 500287.84 | 3495191.48 | 1787312.18 | 4193.09 | 1.77 | 4565.14 | 30.41 |
PERIMETER_BOT_ZN_3 | 3182051.21 | 0.00 | 3182051.21 | 399002.08 | 3581053.28 | 2823374.22 | 4758.04 | 26.00 | 3975.96 | 134.57 |
PERIMETER_BOT_ZN_2 | 2348222.63 | 0.00 | 2348222.63 | 265999.79 | 2614222.41 | 1787429.43 | 4227.38 | 37.90 | 4494.71 | 134.57 |
PERIMETER_BOT_ZN_1 | 3484456.18 | 0.00 | 3484456.18 | 3134132.70 | 6618588.87 | 2823374.22 | 4316.12 | 30.24 | 4413.63 | 134.57 |
PERIMETER_BOT_ZN_4 | 2372134.11 | 0.00 | 2372134.11 | 265999.79 | 2638133.90 | 1787312.18 | 4303.12 | 32.08 | 4424.80 | 134.57 |
PERIMETER_MID_ZN_3 | 3405588.16 | 0.00 | 3405588.16 | 624679.86 | 4030268.02 | 2823374.22 | 4213.93 | 21.12 | 4524.95 | 184.28 |
PERIMETER_MID_ZN_2 | 2632263.97 | 0.00 | 2632263.97 | 416450.74 | 3048714.71 | 1601953.02 | 4118.09 | 2.12 | 4639.79 | 1093.28 |
PERIMETER_MID_ZN_1 | 3813623.04 | 0.00 | 3813623.04 | 624679.86 | 4438302.90 | 2823374.22 | 4160.14 | 5.51 | 4594.35 | 184.28 |
PERIMETER_MID_ZN_4 | 2988752.23 | 0.00 | 2988752.23 | 416450.74 | 3405202.97 | 1787312.18 | 4121.71 | 9.61 | 4628.68 | 184.28 |
Total Facility | 70380242.00 | 0.00 | 70380242.00 | 8648843.76 | 79029085.76 | 67658168.57 | 6932.30 | 265.08 | 4684.42 | 1131.51 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6183 | 0.0000 | 0.6183 | 0.0000 | 0.6183 | 0.4247 | 3194.39 | 63.31 | 2685.30 |
CORE_MID | 0.4414 | 0.0000 | 0.4414 | 0.0000 | 0.4414 | 0.4247 | 4037.76 | 29.67 | 1875.58 |
CORE_TOP | 0.4347 | 0.0000 | 0.4347 | 0.0000 | 0.4347 | 0.4247 | 4003.48 | 22.59 | 1916.93 |
PERIMETER_TOP_ZN_3 | 0.1858 | 0.0000 | 0.1858 | 0.0178 | 0.2036 | 0.0895 | 1416.35 | 19.71 | 4506.94 |
PERIMETER_TOP_ZN_2 | 0.1296 | 0.0000 | 0.1296 | 0.0119 | 0.1414 | 0.0567 | 1387.76 | 1.64 | 4553.60 |
PERIMETER_TOP_ZN_1 | 0.1976 | 0.0000 | 0.1976 | 0.0178 | 0.2154 | 0.0895 | 1390.47 | 1.62 | 4550.91 |
PERIMETER_TOP_ZN_4 | 0.1396 | 0.0000 | 0.1396 | 0.0119 | 0.1515 | 0.0567 | 1382.18 | 1.77 | 4559.05 |
PERIMETER_BOT_ZN_3 | 0.1473 | 0.0000 | 0.1473 | 0.0095 | 0.1568 | 0.0895 | 1952.40 | 25.83 | 3964.78 |
PERIMETER_BOT_ZN_2 | 0.1088 | 0.0000 | 0.1088 | 0.0063 | 0.1151 | 0.0567 | 1424.59 | 36.71 | 4481.70 |
PERIMETER_BOT_ZN_1 | 0.1614 | 0.0000 | 0.1614 | 0.1373 | 0.2987 | 0.0895 | 1510.14 | 30.03 | 4402.83 |
PERIMETER_BOT_ZN_4 | 0.1098 | 0.0000 | 0.1098 | 0.0063 | 0.1162 | 0.0567 | 1501.87 | 30.52 | 4410.61 |
PERIMETER_MID_ZN_3 | 0.1578 | 0.0000 | 0.1578 | 0.0148 | 0.1727 | 0.0895 | 1405.22 | 20.49 | 4517.30 |
PERIMETER_MID_ZN_2 | 0.1309 | 0.0000 | 0.1309 | 0.0105 | 0.1414 | 0.0567 | 1316.48 | 0.87 | 3716.65 |
PERIMETER_MID_ZN_1 | 0.1769 | 0.0000 | 0.1769 | 0.0148 | 0.1917 | 0.0895 | 1351.26 | 4.84 | 4586.90 |
PERIMETER_MID_ZN_4 | 0.1386 | 0.0000 | 0.1386 | 0.0099 | 0.1484 | 0.0567 | 1320.50 | 9.32 | 4613.18 |
Total Facility | 3.2786 | 0.0000 | 3.2786 | 0.2687 | 3.5473 | 2.1513 | 4116.77 | 260.58 | 4661.29 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 34050672.70 | 0.00 | 34050672.70 | 22614548.33 | 4134.95 | 1.66 | 4623.39 | 134.57 |
PACU_VAV_MID | 30801757.81 | 0.00 | 30801757.81 | 22429071.92 | 4144.27 | 1.95 | 4613.78 | 184.28 |
PACU_VAV_TOP | 32138626.16 | 0.00 | 32138626.16 | 22614548.33 | 4204.46 | 1.28 | 4554.26 | 30.41 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5789 | 0.0000 | 1.5789 | 0.7171 | 1331.45 | 1.52 | 4610.03 |
PACU_VAV_MID | 1.4286 | 0.0000 | 1.4286 | 0.7084 | 1335.17 | 1.90 | 4605.92 |
PACU_VAV_TOP | 1.4983 | 0.0000 | 1.4983 | 0.7171 | 1393.55 | 1.28 | 4548.17 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 22.40 | 2937.69 | 0.00 | 0.00 | 0.00 | 1844.02 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 40.69 | 2604.16 | 0.00 | 0.00 | 0.00 | 2256.90 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 32.61 | 2500.65 | 0.00 | 0.00 | 0.00 | 2192.95 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2393 | 2.6329 | 0.0000 | 0.0000 | 0.0000 | 1.0716 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1929 | 2.4281 | 0.0000 | 0.0000 | 0.0000 | 1.1376 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2013 | 2.5774 | 0.0000 | 0.0000 | 0.0000 | 1.1406 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1940.44 | 15934.24 | 12-MAR-17:20 | 192352.22 | 19-JUL-15:10 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 348.44 | 385.65 | 01-JAN-00:40 | 97525.69 | 19-JUL-15:00 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 03-JAN-13:20 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 03-JAN-13:20 |
ElectricityPurchased:Facility | 1940.44 | 15934.24 | 12-MAR-17:20 | 192352.22 | 19-JUL-15:10 |
ElectricityPurchased:Plant | 1940.44 | 15934.24 | 12-MAR-17:20 | 192352.22 | 19-JUL-15:10 |
Cogeneration:ElectricityPurchased | 1940.44 | 15934.24 | 12-MAR-17:20 | 192352.22 | 19-JUL-15:10 |
General:Cogeneration:ElectricityPurchased | 1940.44 | 15934.24 | 12-MAR-17:20 | 192352.22 | 19-JUL-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1940.44 | 15934.24 | 12-MAR-17:20 | 192352.22 | 19-JUL-15:10 |
ElectricityNet:Plant | 1940.44 | 15934.24 | 12-MAR-17:20 | 192352.22 | 19-JUL-15:10 |
Cogeneration:ElectricityNet | 1940.44 | 15934.24 | 12-MAR-17:20 | 192352.22 | 19-JUL-15:10 |
General:Cogeneration:ElectricityNet | 1940.44 | 15934.24 | 12-MAR-17:20 | 192352.22 | 19-JUL-15:10 |
Fans:Electricity | 165.99 | 0.00 | 01-JAN-00:40 | 28798.89 | 09-AUG-15:20 |
General:Fans:Electricity | 165.99 | 0.00 | 01-JAN-00:40 | 28798.89 | 09-AUG-15:20 |
ExteriorLights:Electricity | 235.79 | 0.00 | 01-JAN-08:00 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 235.79 | 0.00 | 01-JAN-08:00 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 154.95 | 0.00 | 01-JAN-00:10 | 68816.87 | 19-JUL-15:00 |
General:Cooling:Electricity | 154.95 | 0.00 | 01-JAN-00:10 | 68816.87 | 19-JUL-15:00 |
Electricity:Plant | 60.68 | 0.00 | 01-JAN-00:40 | 8174.24 | 06-FEB-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 56.86 | 0.00 | 01-JAN-00:10 | 7140.61 | 13-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 56.86 | 0.00 | 01-JAN-00:10 | 7140.61 | 13-FEB-12:20 |
Pumps:Electricity | 3.83 | 0.00 | 01-JAN-00:40 | 1313.86 | 11-DEC-08:00 |
General:Pumps:Electricity | 3.83 | 0.00 | 01-JAN-00:40 | 1313.86 | 11-DEC-08:00 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 749.04 | 0.00 | 01-JAN-00:40 | 323034.70 | 11-DEC-07:20 |
NaturalGas:Plant | 749.04 | 0.00 | 01-JAN-00:40 | 323034.70 | 11-DEC-07:20 |
Heating:NaturalGas | 749.04 | 0.00 | 01-JAN-00:40 | 323034.70 | 11-DEC-07:20 |
Boiler:Heating:NaturalGas | 749.04 | 0.00 | 01-JAN-00:40 | 323034.70 | 11-DEC-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2966.10 | 0.00 | 01-JAN-00:40 | 648530.23 | 11-DEC-07:10 |
EnergyTransfer:Building | 1285.38 | 0.00 | 01-JAN-00:40 | 187074.84 | 06-FEB-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 235.63 | 0.00 | 01-JAN-00:40 | 26440.97 | 17-JUL-11:00 |
Heating:EnergyTransfer | 255.52 | 0.00 | 01-JAN-00:40 | 184848.74 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.15 | 0.00 | 01-JAN-00:10 | 9261.99 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 255.52 | 0.00 | 01-JAN-00:40 | 184848.74 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.15 | 0.00 | 01-JAN-00:10 | 9261.99 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 1029.86 | 0.00 | 01-JAN-00:40 | 179786.68 | 09-AUG-15:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 235.49 | 0.00 | 01-JAN-00:40 | 26440.97 | 17-JUL-11:00 |
General:Cooling:EnergyTransfer | 1029.86 | 0.00 | 01-JAN-00:40 | 179786.68 | 09-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 235.49 | 0.00 | 01-JAN-00:40 | 26440.97 | 17-JUL-11:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 91.77 | 0.00 | 01-JAN-00:40 | 22153.98 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.26 | 0.00 | 01-JAN-00:40 | 22153.98 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.26 | 0.00 | 01-JAN-00:40 | 22153.98 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 41.51 | 0.00 | 01-JAN-00:10 | 15817.61 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 41.51 | 0.00 | 01-JAN-00:10 | 15817.61 | 21-JUL-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 32.40 | 0.00 | 01-JAN-00:40 | 10800.83 | 02-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.07 | 0.00 | 01-JAN-00:40 | 10800.83 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.07 | 0.00 | 01-JAN-00:40 | 10800.83 | 02-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.33 | 0.00 | 01-JAN-00:10 | 5109.60 | 17-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.33 | 0.00 | 01-JAN-00:10 | 5109.60 | 17-JUL-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 32.57 | 0.00 | 01-JAN-00:40 | 9865.91 | 02-JAN-08:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.72 | 0.00 | 01-JAN-00:40 | 9865.91 | 02-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.72 | 0.00 | 01-JAN-00:40 | 9865.91 | 02-JAN-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.85 | 0.00 | 01-JAN-00:10 | 5187.96 | 09-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.85 | 0.00 | 01-JAN-00:10 | 5187.96 | 09-AUG-15:30 |
EnergyTransfer:Zone:CORE_MID | 153.60 | 0.00 | 01-JAN-00:40 | 20328.48 | 17-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.81 | 0.00 | 01-JAN-00:20 | 17007.24 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.81 | 0.00 | 01-JAN-00:20 | 17007.24 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 151.80 | 0.00 | 01-JAN-00:40 | 20328.48 | 17-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 151.80 | 0.00 | 01-JAN-00:40 | 20328.48 | 17-JUL-14:00 |
EnergyTransfer:Zone:CORE_TOP | 153.82 | 0.00 | 01-JAN-00:40 | 26278.77 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 12.19 | 0.00 | 01-JAN-00:40 | 26278.77 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 12.19 | 0.00 | 01-JAN-00:40 | 26278.77 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 141.63 | 0.00 | 01-JAN-00:20 | 24094.49 | 17-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 141.63 | 0.00 | 01-JAN-00:20 | 24094.49 | 17-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 61.33 | 0.00 | 01-JAN-00:40 | 14053.61 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.19 | 0.00 | 01-JAN-00:40 | 14053.61 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.19 | 0.00 | 01-JAN-00:40 | 14053.61 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.14 | 0.00 | 01-JAN-00:20 | 8200.76 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.14 | 0.00 | 01-JAN-00:20 | 8200.76 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.02 | 0.00 | 01-JAN-00:40 | 9073.76 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 14.13 | 0.00 | 01-JAN-00:40 | 9073.76 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 14.13 | 0.00 | 01-JAN-00:40 | 9073.76 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.90 | 0.00 | 01-JAN-00:20 | 8596.59 | 17-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.90 | 0.00 | 01-JAN-00:20 | 8596.59 | 17-JUL-07:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 68.78 | 0.00 | 01-JAN-00:40 | 13955.50 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.66 | 0.00 | 01-JAN-00:40 | 13955.50 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.66 | 0.00 | 01-JAN-00:40 | 13955.50 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.12 | 0.00 | 01-JAN-00:20 | 12519.70 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.12 | 0.00 | 01-JAN-00:20 | 12519.70 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 46.92 | 0.00 | 01-JAN-00:40 | 9615.26 | 18-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 15.25 | 0.00 | 01-JAN-00:40 | 9297.79 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 15.25 | 0.00 | 01-JAN-00:40 | 9297.79 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.67 | 0.00 | 01-JAN-00:20 | 9615.26 | 18-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.67 | 0.00 | 01-JAN-00:20 | 9615.26 | 18-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 44.23 | 0.00 | 01-JAN-00:40 | 9772.62 | 21-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 14.57 | 0.00 | 01-JAN-00:40 | 9772.62 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 14.57 | 0.00 | 01-JAN-00:40 | 9772.62 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.67 | 0.00 | 01-JAN-00:20 | 6021.66 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.67 | 0.00 | 01-JAN-00:20 | 6021.66 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.27 | 0.00 | 01-JAN-00:40 | 6876.18 | 10-AUG-10:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 7.88 | 0.00 | 01-JAN-00:40 | 6451.90 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 7.88 | 0.00 | 01-JAN-00:40 | 6451.90 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.40 | 0.00 | 01-JAN-00:20 | 6876.18 | 10-AUG-10:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.40 | 0.00 | 01-JAN-00:20 | 6876.18 | 10-AUG-10:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 64.56 | 0.00 | 01-JAN-00:40 | 14832.40 | 07-FEB-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.12 | 0.00 | 01-JAN-00:40 | 14832.40 | 07-FEB-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.12 | 0.00 | 01-JAN-00:40 | 14832.40 | 07-FEB-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 35.44 | 0.00 | 01-JAN-00:20 | 12828.54 | 10-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 35.44 | 0.00 | 01-JAN-00:20 | 12828.54 | 10-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 34.77 | 0.00 | 01-JAN-00:40 | 7369.37 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 8.64 | 0.00 | 01-JAN-00:40 | 6618.39 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 8.64 | 0.00 | 01-JAN-00:40 | 6618.39 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.13 | 0.00 | 01-JAN-00:20 | 7369.37 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.13 | 0.00 | 01-JAN-00:20 | 7369.37 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 48.59 | 0.00 | 01-JAN-00:40 | 10403.84 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.65 | 0.00 | 01-JAN-00:40 | 10403.84 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 12.65 | 0.00 | 01-JAN-00:40 | 10403.84 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 35.94 | 0.00 | 01-JAN-00:20 | 7298.53 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 35.94 | 0.00 | 01-JAN-00:20 | 7298.53 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.68 | 0.00 | 01-JAN-00:40 | 8640.86 | 17-JUL-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.28 | 0.00 | 01-JAN-00:40 | 7230.38 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 7.28 | 0.00 | 01-JAN-00:40 | 7230.38 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.40 | 0.00 | 01-JAN-00:20 | 8640.86 | 17-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.40 | 0.00 | 01-JAN-00:20 | 8640.86 | 17-JUL-07:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 58.70 | 0.00 | 01-JAN-00:40 | 12231.48 | 21-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.96 | 0.00 | 01-JAN-00:40 | 10575.99 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.96 | 0.00 | 01-JAN-00:40 | 10575.99 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 49.75 | 0.00 | 01-JAN-00:20 | 12231.48 | 21-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 49.75 | 0.00 | 01-JAN-00:20 | 12231.48 | 21-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 40.71 | 0.00 | 01-JAN-00:40 | 9123.44 | 18-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.00 | 0.00 | 01-JAN-00:40 | 7389.86 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.00 | 0.00 | 01-JAN-00:40 | 7389.86 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.71 | 0.00 | 01-JAN-00:20 | 9123.44 | 18-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.71 | 0.00 | 01-JAN-00:20 | 9123.44 | 18-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 543.76 | 0.00 | 01-JAN-00:40 | 243317.45 | 11-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:30 |
EnergyTransfer:HVAC | 1140.85 | 0.00 | 01-JAN-00:40 | 264694.70 | 20-JUL-13:40 |
HeatingCoils:EnergyTransfer | 489.73 | 0.00 | 01-JAN-00:40 | 241182.00 | 11-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 489.73 | 0.00 | 01-JAN-00:40 | 241182.00 | 11-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 489.73 | 0.00 | 01-JAN-00:40 | 241182.00 | 11-DEC-07:10 |
CoolingCoils:EnergyTransfer | 651.12 | 0.00 | 01-JAN-00:10 | 264684.24 | 20-JUL-13:40 |
EnergyTransfer:Plant | 539.87 | 0.00 | 01-JAN-00:40 | 240790.47 | 11-DEC-07:20 |
WaterSystems:EnergyTransfer | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:30 |
Boilers:EnergyTransfer | 485.84 | 0.00 | 01-JAN-00:40 | 238655.02 | 11-DEC-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.147 | -235.486 | 0.000 | 0.000 | 33.374 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -169.820 |
CORE_MID | 0.000 | 0.000 | 1.805 | -151.796 | 0.000 | 0.000 | 34.658 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -111.879 |
CORE_TOP | 0.000 | 0.000 | 12.192 | -141.626 | 0.000 | 0.000 | 35.687 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -133.465 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 24.195 | -37.138 | 0.000 | 0.000 | 7.838 | 23.566 | 24.333 | 14.519 | 0.000 | 0.096 | 1.287 | 0.000 | -47.424 | 0.000 | -11.271 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 14.129 | -30.895 | 0.000 | 0.000 | 4.874 | 14.919 | 15.404 | 27.968 | 0.000 | 0.052 | 0.000 | 0.000 | -29.542 | 0.000 | -7.607 | -9.302 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 18.664 | -50.117 | 0.000 | 0.000 | 7.686 | 23.566 | 24.332 | 51.713 | 0.000 | 0.077 | 0.000 | 0.000 | -43.776 | 0.000 | -11.580 | -20.565 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 15.247 | -31.668 | 0.000 | 0.000 | 4.949 | 14.918 | 15.403 | 28.298 | 0.000 | 0.054 | 0.000 | 0.000 | -30.868 | 0.000 | -7.634 | -8.698 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 14.566 | -29.668 | 0.000 | 0.000 | 7.805 | 23.566 | 24.333 | 15.113 | 0.000 | 0.054 | 0.002 | 0.000 | -48.736 | 0.000 | -6.269 | -0.762 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 7.879 | -26.395 | 0.000 | 0.000 | 4.850 | 14.919 | 15.404 | 28.356 | 0.000 | 0.028 | 0.000 | 0.000 | -30.752 | 0.000 | -4.271 | -10.019 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 29.116 | -35.439 | 0.000 | 0.000 | 7.806 | 23.566 | 24.332 | 52.930 | 0.000 | 0.811 | 0.000 | 0.000 | -45.386 | 0.000 | -43.701 | -14.035 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 8.641 | -26.130 | 0.000 | 0.000 | 4.902 | 14.918 | 15.403 | 28.819 | 0.000 | 0.027 | 0.000 | 0.000 | -32.122 | 0.000 | -4.283 | -10.176 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 12.650 | -35.944 | 0.000 | 0.000 | 7.704 | 23.566 | 24.333 | 14.135 | 0.000 | 0.073 | 13.634 | 0.000 | -50.259 | 0.000 | -9.891 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 7.276 | -30.404 | 0.000 | 0.000 | 3.565 | 14.919 | 15.404 | 27.616 | 0.000 | 0.045 | 0.002 | 0.000 | -31.231 | 0.000 | -6.663 | -0.526 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 8.958 | -49.746 | 0.000 | 0.000 | 7.532 | 23.566 | 24.332 | 51.199 | 0.000 | 0.059 | 0.002 | 0.000 | -46.602 | 0.000 | -10.203 | -9.096 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 8.000 | -32.710 | 0.000 | 0.000 | 4.896 | 14.918 | 15.403 | 28.181 | 0.000 | 0.044 | 0.597 | 0.000 | -32.658 | 0.000 | -6.672 | -0.000 |
TOPFLOOR_PLENUM | 50.260 | -41.512 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.042 | 8.157 | 0.000 | 0.000 | 0.000 | -16.946 | -0.002 |
MIDFLOOR_PLENUM | 14.068 | -18.329 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.086 | 21.467 | 0.000 | 0.000 | 0.000 | -17.292 | -0.000 |
FIRSTFLOOR_PLENUM | 7.722 | -24.849 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.063 | 31.240 | 0.000 | 0.000 | 0.000 | -14.175 | -0.000 |
Total Facility | 72.050 | -84.691 | 183.467 | -945.162 | 0.000 | 0.000 | 178.125 | 566.263 | 729.266 | 368.847 | 0.000 | 1.610 | 76.388 | 0.000 | -469.356 | 0.000 | -178.458 | -498.346 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 20-JUL-04:02 | 0.00 | 0.00 | 0.00 | -51534.19 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 44483.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-JUL-05:12 | 0.00 | 0.00 | 0.00 | -39733.40 | 0.00 | 0.00 | 332.64 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 35290.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 | -42938.41 | 0.00 | 0.00 | 316.50 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 38511.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 21-JUL-04:02 | 0.00 | 0.00 | 0.00 | -12650.29 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 54.86 | 11884.09 | 0.00 | -32.09 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:12 | 0.00 | 0.00 | 0.00 | -11935.71 | 0.00 | 0.00 | 14.57 | 72.37 | 302.86 | 10116.78 | 0.00 | 0.00 | 1581.90 | 0.00 | -0.00 | 0.00 | -152.77 | 0.00 |
PERIMETER_TOP_ZN_1 | 21-JUL-04:02 | 0.00 | 0.00 | 0.00 | -13262.62 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 53.97 | 12500.72 | 0.00 | -35.49 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:52 | 0.00 | 0.00 | 0.00 | -18163.92 | 0.00 | 0.00 | 12.49 | 72.36 | 302.86 | 11678.13 | 0.00 | 0.00 | 6177.53 | 0.00 | -0.00 | 0.00 | -79.46 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | -6021.54 | 0.00 | 0.00 | 757.17 | 2057.62 | 1435.25 | 4496.67 | 0.00 | 46.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2771.98 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:42 | 0.00 | 0.00 | 0.00 | -10556.48 | 0.00 | 0.00 | 17.10 | 72.37 | 302.86 | 8499.29 | 0.00 | 0.00 | 1735.24 | 0.00 | -0.00 | 0.00 | -70.38 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-AUG-12:00 | 0.00 | 0.00 | 0.00 | -12830.49 | 0.00 | 0.00 | 398.60 | 2057.62 | 1275.77 | 10007.50 | 0.00 | 4712.01 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5621.01 |
PERIMETER_BOT_ZN_4 | 02-JUL-17:21 | 0.00 | 0.00 | 0.00 | -13539.84 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 11464.51 | 0.00 | 0.00 | 1798.36 | 0.00 | -0.00 | 0.00 | -39.81 | 0.00 |
PERIMETER_MID_ZN_3 | 21-JUL-04:02 | 0.00 | 0.00 | 0.00 | -9265.62 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 36.11 | 8504.87 | 0.00 | -18.79 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-08:32 | 0.00 | 0.00 | 0.00 | -14202.72 | 0.00 | 0.00 | 16.89 | 72.37 | 302.86 | 10199.87 | 0.00 | 0.00 | 3735.61 | 0.00 | -0.00 | 0.00 | -124.88 | 0.00 |
PERIMETER_MID_ZN_1 | 13-AUG-14:32 | 0.00 | 0.00 | 0.00 | -19254.58 | 0.00 | 0.00 | 26.21 | 114.31 | 478.41 | 8279.11 | 0.00 | 212.55 | 10143.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-16:32 | 0.00 | 0.00 | 0.00 | -16898.46 | 0.00 | 0.00 | 14.72 | 72.36 | 302.86 | 9454.42 | 0.00 | 8.36 | 7045.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-13:30 | 0.00 | -15817.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.30 | 15725.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 04-JAN-05:01 | 0.00 | -5174.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6254.43 | 0.00 | -0.00 | 0.00 | -1079.90 | 0.00 |
FIRSTFLOOR_PLENUM | 13-APR-05:11 | 0.00 | -5381.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5636.99 | 0.00 | -0.00 | 0.00 | -255.71 | 0.00 |
Total Facility | 21-JUL-04:02 | 0.00 | 8593.64 | 0.00 | -187630.67 | 0.00 | 0.00 | 0.00 | 5493.69 | 15894.33 | 222.89 | 0.00 | 493.74 | 157131.00 | 0.00 | -187.28 | 0.00 | -11.35 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 12075.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19125.69 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 20643.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24169.85 |
CORE_TOP | 30-JAN-05:11 | 0.00 | 0.00 | 31343.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34869.98 |
PERIMETER_TOP_ZN_3 | 05-FEB-21:12 | 0.00 | 0.00 | 16583.08 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4140.10 | 0.00 | -2324.30 | -10619.09 |
PERIMETER_TOP_ZN_2 | 26-DEC-00:52 | 0.00 | 0.00 | 10725.92 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2630.46 | 0.00 | -1276.98 | -7216.74 |
PERIMETER_TOP_ZN_1 | 26-DEC-00:52 | 0.00 | 0.00 | 16538.36 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4139.93 | 0.00 | -1920.99 | -11106.56 |
PERIMETER_TOP_ZN_4 | 05-FEB-21:12 | 0.00 | 0.00 | 11467.66 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2891.91 | 0.00 | -1548.20 | -7344.32 |
PERIMETER_BOT_ZN_3 | 06-FEB-04:42 | 0.00 | 0.00 | 12091.95 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4841.53 | 0.00 | -1234.59 | -6644.95 |
PERIMETER_BOT_ZN_2 | 06-FEB-04:42 | 0.00 | 0.00 | 8074.92 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3110.40 | 0.00 | -823.77 | -4539.01 |
PERIMETER_BOT_ZN_1 | 07-FEB-07:50 | 0.00 | 0.00 | 14832.10 | 0.00 | 0.00 | 0.00 | 254.10 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 10523.29 | 0.00 | -2619.92 | 0.00 | -24313.32 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-04:42 | 0.00 | 0.00 | 8357.67 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3227.84 | 0.00 | -822.99 | -4705.09 |
PERIMETER_MID_ZN_3 | 06-FEB-02:52 | 0.00 | 0.00 | 12557.47 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4726.38 | 0.00 | -2236.06 | -6224.15 |
PERIMETER_MID_ZN_2 | 06-FEB-02:52 | 0.00 | 0.00 | 9241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3009.04 | 0.00 | -1498.90 | -5131.67 |
PERIMETER_MID_ZN_1 | 06-FEB-02:52 | 0.00 | 0.00 | 12442.68 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4758.64 | 0.00 | -2248.24 | -6064.91 |
PERIMETER_MID_ZN_4 | 06-FEB-03:32 | 0.00 | 0.00 | 9526.56 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3205.45 | 0.00 | -1306.19 | -5413.18 |
TOPFLOOR_PLENUM | 06-FEB-05:16 | 23386.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3358.28 | -20027.83 |
MIDFLOOR_PLENUM | 02-JAN-06:06 | 11191.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -241.61 | -10950.02 |
FIRSTFLOOR_PLENUM | 02-JAN-08:10 | 10110.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -198.07 | -9912.49 |
Total Facility | 02-JAN-05:01 | 15308.75 | 0.00 | 187044.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5493.69 | 15894.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24826.07 | 0.00 | -8554.34 | -190360.51 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 7.2608 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.8508 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 7.0073 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5669 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 8.1879 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.8093 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.6304 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.1782 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.5037 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.1022 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.0940 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.4564 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4206 | 3.4206 | 1.0262 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7986 | 2.7986 | 0.8396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1786 | 3.1786 | 0.9536 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4907 | 1.4907 | 0.4472 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9627 | 0.9627 | 0.2888 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4900 | 1.4900 | 0.4470 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0660 | 1.0660 | 0.3198 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1301 | 1.1301 | 0.3390 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7724 | 0.7724 | 0.2317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1301 | 1.1301 | 0.3390 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8075 | 0.8075 | 0.2422 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1508 | 1.1508 | 0.3452 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9389 | 0.9389 | 0.2817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1498 | 1.1498 | 0.3449 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9693 | 0.9693 | 0.2908 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 7.2608 | 5.8508 | 7.2608 | 2.1782 | 0.0000 | 1.0000 |
PACU_VAV_MID | 7.0073 | 5.5669 | 7.0073 | 2.1022 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 8.1879 | 6.8093 | 8.1879 | 2.4564 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7103 | 1.7103 | 1.0262 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3993 | 1.3993 | 0.8396 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5893 | 1.5893 | 0.9536 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7453 | 0.7453 | 0.4472 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4814 | 0.4814 | 0.2888 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7450 | 0.7450 | 0.4470 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5330 | 0.5330 | 0.3198 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5651 | 0.5651 | 0.3390 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3862 | 0.3862 | 0.2317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5651 | 0.5651 | 0.3390 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4037 | 0.4037 | 0.2422 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5754 | 0.5754 | 0.3452 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4694 | 0.4694 | 0.2817 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5749 | 0.5749 | 0.3449 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4846 | 0.4846 | 0.2908 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.6304 | 2.1782 | 2.1782 | 2.1782 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.5037 | 2.1022 | 2.1022 | 2.1022 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.0940 | 2.4564 | 2.4564 | 2.4564 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 441.17 |
Number of hours cooling loads not met | 19.50 |
Number of hours not met | 460.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 749.04 | 323034.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 154.95 | 68816.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 235.79 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 165.99 | 28798.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 3.83 | 1313.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 56.86 | 7140.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 1940.44 |
Natural Gas | 0.00 | 749.04 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2689.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 31.10 |
Fans (All) | 33.32 |
Service Water Heating | 11.41 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 389.47 |
Subtotal | 389.47 |
Natural Gas [MJ/m2] | |
Space Heating | 150.34 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 150.34 |
Subtotal | 150.34 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 21.05 |
Space Heating | 27.85 |
Space Cooling | 5.76 |
Fans (All) | 6.17 |
Service Water Heating | 2.11 |
Receptacle Equipment | 27.12 |
Miscellaneous | 9.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8384.50 | 375.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8734.00 | 26.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8719.33 | 40.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8735.33 | 24.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8722.17 | 37.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8731.67 | 28.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8708.33 | 51.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8662.50 | 97.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8384.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 375.50 | 0.00 | 0.00 | 0.00 |
Average | 8718.09 | 41.91 | 0.00 | 0.00 | 0.00 |
Sum | 156925.67 | 754.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128150.33 | 153.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 153.67 | 0.00 | 0.00 | 0.00 |
Average | 34134.80 | 8.54 | 0.00 | 0.00 | 0.00 |
Sum | 614426.33 | 153.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8092.67 | 667.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8454.50 | 305.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8694.83 | 65.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8534.67 | 225.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8490.33 | 269.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8495.67 | 264.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8458.33 | 301.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8531.33 | 228.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8420.83 | 339.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8381.00 | 379.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8349.50 | 410.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8423.83 | 336.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8397.67 | 362.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8368.33 | 391.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8357.17 | 402.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8202.33 | 557.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8437.17 | 322.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8357.50 | 402.50 | 0.00 | 0.00 | 0.00 |
Min | 8092.67 | 65.17 | 0.00 | 0.00 | 0.00 |
Max | 8694.83 | 667.33 | 0.00 | 0.00 | 0.00 |
Average | 8413.76 | 346.24 | 0.00 | 0.00 | 0.00 |
Sum | 151447.67 | 6232.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127939.17 | 364.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128163.67 | 140.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128271.00 | 33.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24755.00 | 154.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24904.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24904.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128271.00 | 364.83 | 0.00 | 0.00 | 0.00 |
Average | 34104.06 | 39.28 | 0.00 | 0.00 | 0.00 |
Sum | 613873.00 | 707.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119931E+11 | 11381.27 | 20-JAN-17:00 | -1.1 | -3.7 | 0.175363E+10 | 2554.46 | 20-JAN-14:00 | -1.1 | -3.7 |
February | 0.116692E+11 | 11564.43 | 17-FEB-17:00 | 1.10 | 0.20 | 0.161343E+10 | 2565.70 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.158515E+11 | 19492.60 | 16-MAR-16:00 | 15.60 | 13.95 | 0.208503E+10 | 2606.65 | 16-MAR-09:30 | 15.60 | 13.95 |
April | 0.164254E+11 | 19343.07 | 26-APR-16:00 | 14.40 | 8.88 | 0.189626E+10 | 2606.67 | 21-APR-13:00 | 14.40 | 8.88 |
May | 0.214164E+11 | 26907.80 | 24-MAY-05:13 | 18.70 | 15.72 | 0.207544E+10 | 2606.67 | 31-MAY-13:20 | 21.30 | 14.21 |
June | 0.269676E+11 | 48513.70 | 19-JUN-05:12 | 16.70 | 15.97 | 0.207239E+10 | 2606.82 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.284688E+11 | 51545.37 | 20-JUL-04:02 | 24.82 | 22.53 | 0.192803E+10 | 2606.69 | 12-JUL-09:00 | 24.82 | 22.53 |
August | 0.303335E+11 | 48565.86 | 07-AUG-05:12 | 20.20 | 18.58 | 0.216304E+10 | 2606.69 | 04-AUG-09:09 | 20.20 | 18.58 |
September | 0.250819E+11 | 45102.75 | 19-SEP-05:12 | 10.60 | 9.56 | 0.191960E+10 | 2606.79 | 12-SEP-13:09 | 10.60 | 9.56 |
October | 0.191163E+11 | 40234.72 | 24-OCT-05:01 | 0.78 | -0.5 | 0.198762E+10 | 2606.69 | 03-OCT-09:00 | 0.78 | -0.5 |
November | 0.153294E+11 | 18492.17 | 01-NOV-16:00 | 9.40 | 6.91 | 0.194991E+10 | 2606.71 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.128336E+11 | 14993.95 | 01-DEC-17:00 | 7.20 | 4.89 | 0.177592E+10 | 2606.64 | 01-DEC-10:20 | 7.20 | 4.89 |
Annual Sum or Average | 0.235487E+12 | 0.232203E+11 | ||||||||
Minimum of Months | 0.116692E+11 | 11381.27 | -1.1 | -3.7 | 0.161343E+10 | 2554.46 | -1.1 | -3.7 | ||
Maximum of Months | 0.303335E+11 | 51545.37 | 24.82 | 22.53 | 0.216304E+10 | 2606.82 | 24.82 | 22.53 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 24318020.96 | 898.62 | 22-FEB-15:10 | 10.60 | 4.93 | 0.00 | 0.00 | 01-FEB-00:10 | 10.60 | 4.93 |
March | 0.975001E+09 | 8307.55 | 15-MAR-14:00 | 26.10 | 16.06 | 0.00 | 0.00 | 01-MAR-00:10 | 26.10 | 16.06 |
April | 0.230750E+10 | 8767.34 | 23-APR-13:13 | 16.67 | 9.22 | 0.00 | 0.00 | 01-APR-00:10 | 16.67 | 9.22 |
May | 0.497102E+10 | 11481.92 | 31-MAY-14:20 | 21.70 | 14.12 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.12 |
June | 0.841942E+10 | 15399.34 | 27-JUN-13:30 | 28.90 | 23.32 | 0.00 | 0.00 | 01-JUN-00:10 | 28.90 | 23.32 |
July | 0.992497E+10 | 15817.61 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.861615E+10 | 15449.86 | 09-AUG-13:50 | 29.32 | 18.11 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 18.11 |
September | 0.467261E+10 | 12012.00 | 21-SEP-14:05 | 25.68 | 16.62 | 0.00 | 0.00 | 01-SEP-00:10 | 25.68 | 16.62 |
October | 0.139030E+10 | 6727.19 | 11-OCT-12:50 | 22.12 | 14.02 | 0.00 | 0.00 | 01-OCT-00:10 | 22.12 | 14.02 |
November | 0.209596E+09 | 2683.54 | 16-NOV-13:02 | 18.62 | 13.01 | 0.00 | 0.00 | 01-NOV-00:10 | 18.62 | 13.01 |
December | 1863072.73 | 333.12 | 01-DEC-13:13 | 12.03 | 10.45 | 0.00 | 0.00 | 01-DEC-00:10 | 12.03 | 10.45 |
Annual Sum or Average | 0.415128E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.00 | 0.00 | -1.0 | -1.6 | ||
Maximum of Months | 0.992497E+10 | 15817.61 | 31.15 | 23.32 | 0.00 | 0.00 | 31.15 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76751472.21 | 5174.55 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 77740786.48 | 4950.03 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 0.422362E+09 | 4913.84 | 04-MAR-05:01 | -10.1 | -11.1 | 0.00 | 0.00 | 01-MAR-00:10 | -10.1 | -11.1 |
April | 0.745336E+09 | 3652.42 | 11-APR-05:11 | 3.30 | 2.10 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.10 |
May | 0.176439E+10 | 2881.56 | 23-MAY-05:25 | 7.75 | 5.55 | 0.00 | 0.00 | 01-MAY-00:10 | 7.75 | 5.55 |
June | 0.335947E+10 | 4286.97 | 27-JUN-16:00 | 26.10 | 22.53 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 22.53 |
July | 0.428605E+10 | 5109.60 | 17-JUL-14:20 | 26.87 | 20.71 | 0.00 | 0.00 | 01-JUL-00:10 | 26.87 | 20.71 |
August | 0.408787E+10 | 4672.22 | 09-AUG-15:30 | 29.40 | 18.31 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.31 |
September | 0.235903E+10 | 3384.56 | 18-SEP-06:15 | 10.57 | 9.34 | 0.00 | 0.00 | 01-SEP-00:10 | 10.57 | 9.34 |
October | 0.863916E+09 | 2527.63 | 24-OCT-06:03 | 1.70 | 0.40 | 0.00 | 0.00 | 01-OCT-00:10 | 1.70 | 0.40 |
November | 0.212190E+09 | 3039.27 | 17-NOV-06:11 | 5.20 | 2.43 | 0.00 | 0.00 | 01-NOV-00:10 | 5.20 | 2.43 |
December | 74574506.28 | 4311.76 | 29-DEC-05:01 | -8.3 | -8.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.3 | -8.9 |
Annual Sum or Average | 0.183297E+11 | 0.00 | ||||||||
Minimum of Months | 74574506.28 | 2527.63 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.428605E+10 | 5174.55 | 29.40 | 22.53 | 0.00 | 0.00 | 29.40 | 22.53 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124281E+09 | 4778.15 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 0.142022E+09 | 4668.59 | 11-FEB-05:01 | -9.4 | -9.9 | 0.00 | 0.00 | 01-FEB-00:10 | -9.4 | -9.9 |
March | 0.789326E+09 | 5248.55 | 18-MAR-05:11 | 2.60 | 1.59 | 0.00 | 0.00 | 01-MAR-00:10 | 2.60 | 1.59 |
April | 0.136608E+10 | 5381.34 | 13-APR-05:11 | 2.60 | 1.57 | 0.00 | 0.00 | 01-APR-00:10 | 2.60 | 1.57 |
May | 0.273411E+10 | 3501.65 | 11-MAY-06:03 | 13.90 | 13.27 | 0.00 | 0.00 | 01-MAY-00:10 | 13.90 | 13.27 |
June | 0.409735E+10 | 4493.11 | 19-JUN-06:15 | 16.70 | 15.97 | 0.00 | 0.00 | 01-JUN-00:10 | 16.70 | 15.97 |
July | 0.487756E+10 | 5176.87 | 17-JUL-14:05 | 27.33 | 20.86 | 0.00 | 0.00 | 01-JUL-00:10 | 27.33 | 20.86 |
August | 0.497851E+10 | 5187.96 | 09-AUG-15:30 | 29.40 | 18.31 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.31 |
September | 0.335638E+10 | 4887.52 | 18-SEP-06:15 | 10.57 | 9.34 | 0.00 | 0.00 | 01-SEP-00:10 | 10.57 | 9.34 |
October | 0.161152E+10 | 3811.42 | 24-OCT-06:03 | 1.70 | 0.40 | 0.00 | 0.00 | 01-OCT-00:10 | 1.70 | 0.40 |
November | 0.643628E+09 | 3261.41 | 30-NOV-06:11 | 5.00 | 0.79 | 0.00 | 0.00 | 01-NOV-00:10 | 5.00 | 0.79 |
December | 0.128696E+09 | 3718.21 | 28-DEC-05:01 | -11.8 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.248495E+11 | 0.00 | ||||||||
Minimum of Months | 0.124281E+09 | 3261.41 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.497851E+10 | 5381.34 | 29.40 | 20.86 | 0.00 | 0.00 | 29.40 | 20.86 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.673329E+10 | 7244.89 | 12-JAN-16:50 | -6.6 | -8.3 | 0.156073E+10 | 2294.07 | 20-JAN-14:00 | 0.60 | -3.3 |
February | 0.648328E+10 | 7400.06 | 17-FEB-17:00 | 1.10 | 0.20 | 0.143073E+10 | 2336.09 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.101471E+11 | 13674.77 | 16-MAR-16:00 | 15.60 | 13.95 | 0.189041E+10 | 2606.65 | 16-MAR-09:30 | 15.60 | 13.95 |
April | 0.103148E+11 | 12762.36 | 21-APR-16:00 | 13.30 | 8.77 | 0.178838E+10 | 2606.65 | 20-APR-13:20 | 13.30 | 8.77 |
May | 0.142138E+11 | 15922.54 | 31-MAY-16:00 | 22.20 | 14.47 | 0.204145E+10 | 2606.66 | 31-MAY-13:20 | 22.20 | 14.47 |
June | 0.189729E+11 | 22858.77 | 21-JUN-05:12 | 18.30 | 16.18 | 0.206119E+10 | 2606.81 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.203966E+11 | 39738.47 | 17-JUL-05:12 | 22.80 | 21.19 | 0.192048E+10 | 2606.67 | 12-JUL-09:00 | 22.80 | 21.19 |
August | 0.209607E+11 | 39626.88 | 07-AUG-05:12 | 20.20 | 18.58 | 0.215584E+10 | 2606.69 | 04-AUG-09:09 | 20.20 | 18.58 |
September | 0.160063E+11 | 23560.17 | 18-SEP-05:13 | 9.60 | 8.73 | 0.190147E+10 | 2606.77 | 12-SEP-13:09 | 9.60 | 8.73 |
October | 0.111748E+11 | 14282.34 | 12-OCT-16:00 | 18.30 | 14.87 | 0.189038E+10 | 2606.65 | 27-OCT-13:20 | 10.17 | 7.43 |
November | 0.906745E+10 | 9925.12 | 01-NOV-16:00 | 9.40 | 6.91 | 0.175641E+10 | 2606.64 | 01-NOV-13:30 | 9.40 | 6.91 |
December | 0.732486E+10 | 7788.57 | 01-DEC-17:00 | 7.20 | 4.89 | 0.153907E+10 | 2426.66 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.151796E+12 | 0.219365E+11 | ||||||||
Minimum of Months | 0.648328E+10 | 7244.89 | -6.6 | -8.3 | 0.143073E+10 | 2294.07 | 0.60 | -3.3 | ||
Maximum of Months | 0.209607E+11 | 39738.47 | 22.80 | 21.19 | 0.215584E+10 | 2606.81 | 22.80 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411102E+10 | 7189.95 | 11-JAN-17:00 | 11.10 | 9.84 | 0.147293E+10 | 2091.26 | 06-JAN-14:00 | 11.10 | 9.84 |
February | 0.439751E+10 | 7477.64 | 28-FEB-17:00 | -0.6 | -3.0 | 0.135271E+10 | 2152.84 | 17-FEB-14:00 | -0.6 | -3.0 |
March | 0.868372E+10 | 14494.51 | 15-MAR-16:00 | 25.00 | 15.96 | 0.176082E+10 | 2606.64 | 16-MAR-13:20 | 15.90 | 13.22 |
April | 0.993841E+10 | 13966.67 | 21-APR-16:00 | 13.30 | 8.77 | 0.166429E+10 | 2606.64 | 20-APR-13:20 | 13.30 | 8.77 |
May | 0.143993E+11 | 19002.50 | 31-MAY-16:00 | 22.20 | 14.47 | 0.197578E+10 | 2606.66 | 10-MAY-13:20 | 22.20 | 14.47 |
June | 0.199380E+11 | 22473.74 | 27-JUN-14:40 | 26.13 | 22.80 | 0.204282E+10 | 2606.80 | 22-JUN-13:09 | 26.13 | 22.80 |
July | 0.217376E+11 | 42945.19 | 21-JUL-05:02 | 25.60 | 23.14 | 0.191186E+10 | 2606.69 | 26-JUL-09:00 | 25.00 | 20.49 |
August | 0.213398E+11 | 26003.29 | 07-AUG-05:12 | 20.20 | 18.58 | 0.214023E+10 | 2606.71 | 10-AUG-09:39 | 26.87 | 20.17 |
September | 0.151283E+11 | 19252.97 | 18-SEP-14:00 | 17.80 | 12.70 | 0.185201E+10 | 2606.75 | 12-SEP-13:09 | 17.80 | 12.70 |
October | 0.101179E+11 | 13550.96 | 12-OCT-16:00 | 18.30 | 14.87 | 0.173208E+10 | 2606.65 | 05-OCT-13:20 | 18.30 | 14.87 |
November | 0.723196E+10 | 8795.66 | 01-NOV-16:00 | 9.40 | 6.91 | 0.157379E+10 | 2437.58 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.460247E+10 | 7686.50 | 01-DEC-16:50 | 7.20 | 4.98 | 0.142822E+10 | 2213.25 | 01-DEC-14:00 | 7.20 | 4.98 |
Annual Sum or Average | 0.141626E+12 | 0.209075E+11 | ||||||||
Minimum of Months | 0.411102E+10 | 7189.95 | -0.6 | -3.0 | 0.135271E+10 | 2091.26 | -0.6 | -3.0 | ||
Maximum of Months | 0.217376E+11 | 42945.19 | 26.13 | 23.14 | 0.214023E+10 | 2606.80 | 26.87 | 22.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34636623.23 | 2639.91 | 14-JAN-17:02 | 3.22 | 2.72 | 0.304558E+09 | 406.83 | 24-JAN-10:30 | -9.8 | -11.3 |
February | 64286443.25 | 2649.59 | 18-FEB-17:02 | 0.82 | -0.6 | 0.276390E+09 | 406.87 | 06-FEB-10:09 | 0.82 | -0.6 |
March | 0.128627E+10 | 4421.89 | 15-MAR-15:30 | 25.30 | 16.10 | 0.339637E+09 | 533.98 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.228724E+10 | 3979.31 | 21-APR-15:20 | 14.43 | 8.49 | 0.306982E+09 | 498.71 | 07-APR-13:00 | 14.43 | 8.49 |
May | 0.463651E+10 | 5196.51 | 23-MAY-14:50 | 23.90 | 13.35 | 0.368973E+09 | 549.49 | 23-MAY-13:00 | 23.90 | 13.35 |
June | 0.661488E+10 | 7476.72 | 27-JUN-13:30 | 28.90 | 23.32 | 0.407230E+09 | 549.52 | 22-JUN-13:09 | 28.90 | 23.32 |
July | 0.733096E+10 | 12665.88 | 21-JUL-04:02 | 26.52 | 23.72 | 0.391603E+09 | 549.51 | 26-JUL-09:00 | 25.00 | 20.49 |
August | 0.698046E+10 | 7475.11 | 09-AUG-14:50 | 29.40 | 18.10 | 0.429688E+09 | 549.50 | 02-AUG-13:20 | 29.40 | 18.10 |
September | 0.482430E+10 | 5841.24 | 17-SEP-15:11 | 22.60 | 18.29 | 0.351094E+09 | 549.50 | 18-SEP-13:00 | 17.80 | 12.70 |
October | 0.231695E+10 | 4264.43 | 22-OCT-14:12 | 21.70 | 14.31 | 0.318364E+09 | 489.90 | 05-OCT-13:00 | 21.70 | 14.31 |
November | 0.676297E+09 | 3129.83 | 16-NOV-15:00 | 17.20 | 13.27 | 0.303818E+09 | 426.38 | 16-NOV-14:00 | 17.20 | 13.27 |
December | 86088744.68 | 2653.30 | 02-DEC-17:02 | 2.62 | 1.32 | 0.293722E+09 | 406.83 | 26-DEC-10:50 | -10.9 | -12.2 |
Annual Sum or Average | 0.371389E+11 | 0.409206E+10 | ||||||||
Minimum of Months | 34636623.23 | 2639.91 | 0.82 | -0.6 | 0.276390E+09 | 406.83 | -10.9 | -12.2 | ||
Maximum of Months | 0.733096E+10 | 12665.88 | 29.40 | 23.72 | 0.429688E+09 | 549.52 | 29.40 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24013332.83 | 1703.25 | 14-JAN-17:02 | 3.22 | 2.72 | 0.192848E+09 | 257.56 | 31-JAN-14:00 | -11.1 | -12.5 |
February | 0.144325E+09 | 1968.78 | 28-FEB-09:50 | -4.5 | -6.0 | 0.175060E+09 | 266.95 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.124973E+10 | 3237.37 | 15-MAR-14:30 | 25.85 | 16.15 | 0.219644E+09 | 347.87 | 15-MAR-13:20 | 25.85 | 16.15 |
April | 0.208828E+10 | 4586.75 | 24-APR-09:20 | 6.47 | 3.13 | 0.209744E+09 | 347.88 | 19-APR-09:20 | 6.47 | 3.13 |
May | 0.376699E+10 | 7030.09 | 31-MAY-09:00 | 17.80 | 13.21 | 0.251970E+09 | 347.88 | 31-MAY-13:20 | 21.30 | 14.21 |
June | 0.542783E+10 | 11331.62 | 11-JUN-09:42 | 24.22 | 16.74 | 0.268224E+09 | 347.89 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.610869E+10 | 11937.07 | 04-JUL-09:12 | 21.47 | 17.29 | 0.253480E+09 | 347.90 | 03-JUL-09:50 | 21.47 | 17.29 |
August | 0.572547E+10 | 8222.49 | 10-AUG-09:40 | 26.87 | 20.17 | 0.280347E+09 | 347.90 | 16-AUG-09:50 | 21.42 | 16.29 |
September | 0.381601E+10 | 6068.46 | 18-SEP-09:30 | 16.15 | 11.54 | 0.237588E+09 | 347.89 | 12-SEP-13:09 | 16.15 | 11.54 |
October | 0.190016E+10 | 3684.04 | 11-OCT-09:40 | 16.13 | 11.96 | 0.210647E+09 | 347.87 | 11-OCT-09:50 | 16.42 | 12.11 |
November | 0.584937E+09 | 2235.67 | 03-NOV-09:40 | 5.03 | 2.61 | 0.193356E+09 | 289.28 | 03-NOV-09:30 | 5.03 | 2.61 |
December | 59225346.32 | 1709.75 | 02-DEC-17:02 | 2.62 | 1.32 | 0.185980E+09 | 257.54 | 08-DEC-14:39 | -4.1 | -5.5 |
Annual Sum or Average | 0.308957E+11 | 0.267889E+10 | ||||||||
Minimum of Months | 24013332.83 | 1703.25 | -4.5 | -6.0 | 0.175060E+09 | 257.54 | -11.1 | -12.5 | ||
Maximum of Months | 0.610869E+10 | 11937.07 | 26.87 | 20.17 | 0.280347E+09 | 347.90 | 25.85 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.621880E+09 | 4047.13 | 12-JAN-13:50 | -6.3 | -8.9 | 0.309085E+09 | 510.83 | 12-JAN-14:09 | -6.0 | -8.6 |
February | 0.799148E+09 | 5550.69 | 28-FEB-13:50 | 0.00 | -3.0 | 0.283236E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.270633E+10 | 10366.97 | 15-MAR-13:30 | 25.55 | 15.84 | 0.364362E+09 | 549.50 | 14-MAR-13:20 | 25.55 | 15.84 |
April | 0.327957E+10 | 8011.83 | 21-APR-13:07 | 15.40 | 7.97 | 0.330945E+09 | 549.52 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.540282E+10 | 8344.17 | 26-MAY-13:30 | 20.85 | 13.56 | 0.385036E+09 | 549.52 | 16-MAY-13:39 | 20.85 | 13.56 |
June | 0.740786E+10 | 10363.25 | 27-JUN-13:00 | 30.60 | 23.75 | 0.410771E+09 | 549.53 | 22-JUN-13:09 | 30.60 | 23.75 |
July | 0.847846E+10 | 13279.63 | 21-JUL-04:02 | 26.52 | 23.72 | 0.392196E+09 | 549.53 | 06-JUL-13:30 | 26.52 | 23.72 |
August | 0.872783E+10 | 11970.15 | 08-AUG-13:10 | 27.30 | 16.59 | 0.434819E+09 | 549.52 | 10-AUG-09:39 | 26.87 | 20.17 |
September | 0.674467E+10 | 12520.01 | 21-SEP-13:10 | 25.10 | 16.52 | 0.370394E+09 | 549.52 | 12-SEP-13:09 | 25.10 | 16.52 |
October | 0.385382E+10 | 11662.08 | 11-OCT-12:30 | 21.95 | 13.79 | 0.350051E+09 | 549.51 | 30-OCT-13:00 | 15.00 | 8.94 |
November | 0.161736E+10 | 7059.36 | 03-NOV-12:35 | 8.53 | 4.68 | 0.318189E+09 | 549.50 | 03-NOV-13:30 | 9.15 | 4.96 |
December | 0.478143E+09 | 3989.86 | 16-DEC-13:30 | 5.60 | 3.03 | 0.295736E+09 | 477.27 | 04-DEC-14:50 | 5.60 | 3.03 |
Annual Sum or Average | 0.501179E+11 | 0.424482E+10 | ||||||||
Minimum of Months | 0.478143E+09 | 3989.86 | -6.3 | -8.9 | 0.283236E+09 | 477.27 | -6.0 | -8.6 | ||
Maximum of Months | 0.872783E+10 | 13279.63 | 30.60 | 23.75 | 0.434819E+09 | 549.53 | 30.60 | 23.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66588981.00 | 1876.35 | 14-JAN-17:02 | 3.22 | 2.72 | 0.192855E+09 | 257.56 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 0.171306E+09 | 2693.33 | 28-FEB-16:40 | -0.2 | -2.7 | 0.175435E+09 | 298.77 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.127760E+10 | 3995.87 | 15-MAR-14:20 | 25.93 | 16.12 | 0.218208E+09 | 347.81 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.201075E+10 | 6220.37 | 24-APR-16:00 | 13.30 | 7.63 | 0.200380E+09 | 338.94 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.392192E+10 | 10851.35 | 07-MAY-16:42 | 15.00 | 5.89 | 0.235200E+09 | 347.85 | 26-MAY-13:00 | 21.70 | 13.77 |
June | 0.571403E+10 | 14406.25 | 11-JUN-18:42 | 24.08 | 17.29 | 0.256413E+09 | 347.86 | 22-JUN-13:20 | 20.60 | 15.30 |
July | 0.613096E+10 | 18164.99 | 02-JUL-16:52 | 25.00 | 17.00 | 0.245960E+09 | 347.86 | 06-JUL-13:30 | 21.40 | 12.35 |
August | 0.590786E+10 | 12570.39 | 12-AUG-17:05 | 24.72 | 16.93 | 0.270284E+09 | 347.86 | 02-AUG-13:20 | 24.72 | 16.93 |
September | 0.392752E+10 | 8693.55 | 21-SEP-16:00 | 26.10 | 17.18 | 0.222954E+09 | 347.85 | 18-SEP-13:00 | 26.10 | 17.18 |
October | 0.186030E+10 | 6038.44 | 11-OCT-16:00 | 21.70 | 14.52 | 0.206245E+09 | 339.43 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.602097E+09 | 2721.84 | 03-NOV-15:00 | 10.00 | 5.48 | 0.193687E+09 | 303.04 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 78045310.61 | 1902.55 | 16-DEC-17:02 | 3.30 | 1.70 | 0.185964E+09 | 257.55 | 04-DEC-10:39 | 3.30 | 1.70 |
Annual Sum or Average | 0.316690E+11 | 0.260359E+10 | ||||||||
Minimum of Months | 66588981.00 | 1876.35 | -0.2 | -2.7 | 0.175435E+09 | 257.55 | -7.0 | -8.8 | ||
Maximum of Months | 0.613096E+10 | 18164.99 | 26.10 | 17.29 | 0.270284E+09 | 347.86 | 26.10 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31253353.97 | 2036.34 | 14-JAN-17:02 | 3.22 | 2.72 | 0.305186E+09 | 406.81 | 03-JAN-10:39 | 3.22 | 2.72 |
February | 30505880.75 | 2031.99 | 18-FEB-17:02 | 0.82 | -0.6 | 0.276957E+09 | 406.82 | 13-FEB-14:39 | 0.82 | -0.6 |
March | 0.784091E+09 | 2928.12 | 15-MAR-15:30 | 25.30 | 16.10 | 0.337204E+09 | 485.62 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.144031E+10 | 2633.49 | 07-APR-14:00 | 20.00 | 10.13 | 0.300868E+09 | 457.95 | 07-APR-13:00 | 20.00 | 10.13 |
May | 0.314361E+10 | 3138.87 | 23-MAY-14:50 | 23.90 | 13.35 | 0.353545E+09 | 509.31 | 23-MAY-13:00 | 23.90 | 13.35 |
June | 0.464711E+10 | 4888.37 | 27-JUN-13:20 | 29.47 | 23.48 | 0.404995E+09 | 549.49 | 02-JUN-13:20 | 29.47 | 23.48 |
July | 0.535747E+10 | 6021.66 | 21-JUL-13:50 | 31.52 | 21.79 | 0.395673E+09 | 549.50 | 07-JUL-13:20 | 31.52 | 21.79 |
August | 0.556500E+10 | 5825.43 | 09-AUG-15:20 | 29.40 | 18.24 | 0.441332E+09 | 549.51 | 09-AUG-09:20 | 29.40 | 18.24 |
September | 0.424319E+10 | 4483.64 | 15-SEP-14:00 | 25.60 | 21.03 | 0.370632E+09 | 549.50 | 18-SEP-13:00 | 17.80 | 12.70 |
October | 0.287725E+10 | 3223.14 | 22-OCT-14:12 | 21.70 | 14.31 | 0.336219E+09 | 509.57 | 05-OCT-13:00 | 21.70 | 14.31 |
November | 0.138435E+10 | 2587.15 | 16-NOV-15:02 | 17.20 | 13.33 | 0.308297E+09 | 450.56 | 16-NOV-14:20 | 17.20 | 13.33 |
December | 0.163813E+09 | 2294.90 | 01-DEC-07:05 | 10.68 | 9.22 | 0.295009E+09 | 406.96 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.296680E+11 | 0.412592E+10 | ||||||||
Minimum of Months | 30505880.75 | 2031.99 | 0.82 | -0.6 | 0.276957E+09 | 406.81 | 0.82 | -0.6 | ||
Maximum of Months | 0.556500E+10 | 6021.66 | 31.52 | 23.48 | 0.441332E+09 | 549.51 | 31.52 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24293956.26 | 1387.51 | 14-JAN-17:02 | 3.22 | 2.72 | 0.193339E+09 | 257.55 | 03-JAN-10:09 | 3.22 | 2.72 |
February | 86064833.28 | 1416.37 | 28-FEB-09:20 | -6.5 | -7.6 | 0.175474E+09 | 257.55 | 21-FEB-14:50 | -6.5 | -7.6 |
March | 0.873446E+09 | 2118.35 | 15-MAR-14:30 | 25.85 | 16.15 | 0.216993E+09 | 322.62 | 15-MAR-13:00 | 25.85 | 16.15 |
April | 0.159232E+10 | 2849.11 | 24-APR-09:10 | 6.28 | 2.92 | 0.205056E+09 | 347.87 | 24-APR-09:20 | 6.47 | 3.13 |
May | 0.267712E+10 | 4230.60 | 31-MAY-09:20 | 17.97 | 13.39 | 0.245777E+09 | 347.88 | 31-MAY-13:20 | 21.30 | 14.21 |
June | 0.409384E+10 | 6155.30 | 12-JUN-09:30 | 27.25 | 19.42 | 0.269008E+09 | 347.90 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.492194E+10 | 10555.23 | 04-JUL-09:42 | 22.02 | 17.51 | 0.254889E+09 | 347.89 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.501135E+10 | 6876.18 | 10-AUG-10:00 | 27.80 | 20.31 | 0.284314E+09 | 347.89 | 16-AUG-09:50 | 21.42 | 16.29 |
September | 0.363977E+10 | 5308.33 | 21-SEP-09:40 | 20.77 | 15.55 | 0.246065E+09 | 347.89 | 12-SEP-13:09 | 20.77 | 15.55 |
October | 0.226633E+10 | 3380.14 | 11-OCT-09:30 | 15.85 | 11.81 | 0.226809E+09 | 347.87 | 11-OCT-09:50 | 16.42 | 12.11 |
November | 0.109928E+10 | 2030.21 | 03-NOV-08:50 | 3.72 | 1.73 | 0.198444E+09 | 314.36 | 03-NOV-09:09 | 4.18 | 2.03 |
December | 0.109543E+09 | 1563.83 | 01-DEC-07:05 | 10.68 | 9.22 | 0.186841E+09 | 257.56 | 11-DEC-14:30 | -8.1 | -9.1 |
Annual Sum or Average | 0.263953E+11 | 0.270301E+10 | ||||||||
Minimum of Months | 24293956.26 | 1387.51 | -6.5 | -7.6 | 0.175474E+09 | 257.55 | -8.1 | -9.1 | ||
Maximum of Months | 0.501135E+10 | 10555.23 | 27.80 | 20.31 | 0.284314E+09 | 347.90 | 25.85 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92218794.67 | 2317.84 | 12-JAN-13:17 | -6.8 | -9.3 | 0.286273E+09 | 406.79 | 31-JAN-10:30 | -11.4 | -12.5 |
February | 0.147563E+09 | 2461.88 | 18-FEB-14:30 | 2.80 | 0.63 | 0.259162E+09 | 424.71 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.108872E+10 | 6210.65 | 15-MAR-13:30 | 25.55 | 15.84 | 0.336790E+09 | 549.51 | 15-MAR-13:20 | 25.55 | 15.84 |
April | 0.156023E+10 | 3319.98 | 26-APR-14:30 | 15.85 | 8.74 | 0.309316E+09 | 538.51 | 21-APR-13:00 | 15.85 | 8.74 |
May | 0.304399E+10 | 4577.28 | 23-MAY-14:30 | 23.90 | 13.29 | 0.362372E+09 | 549.51 | 23-MAY-13:20 | 23.90 | 13.29 |
June | 0.498772E+10 | 11026.57 | 27-JUN-12:00 | 30.00 | 22.87 | 0.403370E+09 | 549.53 | 22-JUN-13:09 | 30.00 | 22.87 |
July | 0.660626E+10 | 12549.81 | 21-JUL-12:00 | 30.00 | 21.57 | 0.394934E+09 | 549.52 | 06-JUL-13:30 | 30.00 | 21.57 |
August | 0.732561E+10 | 12828.54 | 10-AUG-12:00 | 30.00 | 22.51 | 0.440866E+09 | 549.51 | 04-AUG-13:00 | 30.00 | 22.51 |
September | 0.565795E+10 | 10648.45 | 21-SEP-13:50 | 25.50 | 16.60 | 0.381330E+09 | 549.53 | 12-SEP-13:09 | 25.50 | 16.60 |
October | 0.334714E+10 | 9828.86 | 11-OCT-12:30 | 21.95 | 13.79 | 0.355042E+09 | 549.51 | 11-OCT-13:20 | 22.20 | 14.14 |
November | 0.138087E+10 | 3669.56 | 03-NOV-14:30 | 9.70 | 5.23 | 0.314985E+09 | 548.14 | 03-NOV-13:00 | 9.70 | 5.23 |
December | 0.200651E+09 | 2945.29 | 16-DEC-13:30 | 5.60 | 3.03 | 0.279843E+09 | 420.23 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.354389E+11 | 0.412428E+10 | ||||||||
Minimum of Months | 92218794.67 | 2317.84 | -6.8 | -9.3 | 0.259162E+09 | 406.79 | -11.4 | -12.5 | ||
Maximum of Months | 0.732561E+10 | 12828.54 | 30.00 | 22.87 | 0.440866E+09 | 549.53 | 30.00 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50498655.15 | 1469.55 | 12-JAN-16:00 | -6.1 | -8.3 | 0.193264E+09 | 257.53 | 30-JAN-10:39 | -9.6 | -10.7 |
February | 96048122.16 | 1912.18 | 28-FEB-16:40 | -0.2 | -2.7 | 0.175533E+09 | 285.68 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.861181E+09 | 2266.80 | 15-MAR-14:30 | 25.85 | 16.15 | 0.215228E+09 | 325.32 | 15-MAR-13:00 | 25.85 | 16.15 |
April | 0.145642E+10 | 3057.17 | 24-APR-17:30 | 11.70 | 7.64 | 0.197251E+09 | 338.69 | 21-APR-15:00 | 11.70 | 7.64 |
May | 0.267833E+10 | 4758.99 | 31-MAY-16:00 | 22.20 | 14.47 | 0.232544E+09 | 347.64 | 23-MAY-13:00 | 22.20 | 14.47 |
June | 0.423799E+10 | 6385.72 | 20-JUN-16:00 | 27.80 | 17.33 | 0.262428E+09 | 347.86 | 22-JUN-13:20 | 20.60 | 15.30 |
July | 0.477130E+10 | 13541.51 | 02-JUL-17:21 | 24.45 | 16.81 | 0.252029E+09 | 347.85 | 03-JUL-09:50 | 21.42 | 16.28 |
August | 0.499575E+10 | 9493.12 | 12-AUG-17:07 | 24.72 | 16.93 | 0.281187E+09 | 347.86 | 18-AUG-09:20 | 24.97 | 18.30 |
September | 0.354899E+10 | 8672.16 | 04-SEP-16:52 | 18.30 | 12.88 | 0.238808E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.224377E+10 | 4991.57 | 11-OCT-16:00 | 21.70 | 14.52 | 0.218242E+09 | 347.82 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.106582E+10 | 2158.47 | 03-NOV-15:50 | 9.08 | 5.02 | 0.197300E+09 | 310.66 | 03-NOV-15:00 | 8.90 | 4.93 |
December | 0.123893E+09 | 1631.86 | 01-DEC-07:05 | 10.68 | 9.22 | 0.186791E+09 | 257.55 | 27-DEC-10:09 | -10.4 | -11.6 |
Annual Sum or Average | 0.261300E+11 | 0.265061E+10 | ||||||||
Minimum of Months | 50498655.15 | 1469.55 | -6.1 | -8.3 | 0.175533E+09 | 257.53 | -10.4 | -11.6 | ||
Maximum of Months | 0.499575E+10 | 13541.51 | 27.80 | 17.33 | 0.281187E+09 | 347.87 | 25.85 | 18.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84977675.54 | 2087.21 | 14-JAN-17:02 | 3.22 | 2.72 | 0.305144E+09 | 406.81 | 30-JAN-10:30 | -9.7 | -10.8 |
February | 0.143948E+09 | 2085.28 | 18-FEB-17:02 | 0.82 | -0.6 | 0.276971E+09 | 406.81 | 21-FEB-10:09 | -11.5 | -12.7 |
March | 0.150868E+10 | 3797.74 | 15-MAR-15:30 | 25.30 | 16.10 | 0.346534E+09 | 549.48 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.252281E+10 | 3232.67 | 07-APR-14:10 | 19.72 | 10.09 | 0.319573E+09 | 521.63 | 07-APR-13:00 | 19.72 | 10.09 |
May | 0.421898E+10 | 4833.64 | 23-MAY-14:40 | 23.90 | 13.32 | 0.391941E+09 | 549.50 | 31-MAY-13:20 | 21.30 | 14.21 |
June | 0.582151E+10 | 6671.07 | 27-JUN-13:20 | 29.47 | 23.48 | 0.423864E+09 | 549.53 | 22-JUN-13:09 | 29.47 | 23.48 |
July | 0.653130E+10 | 9273.74 | 21-JUL-04:02 | 26.52 | 23.72 | 0.400936E+09 | 549.51 | 06-JUL-13:30 | 26.52 | 23.72 |
August | 0.630308E+10 | 6792.58 | 09-AUG-14:50 | 29.40 | 18.10 | 0.445450E+09 | 549.51 | 09-AUG-09:20 | 29.40 | 18.10 |
September | 0.450507E+10 | 5175.68 | 15-SEP-14:00 | 25.60 | 21.03 | 0.375634E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.279388E+10 | 3334.85 | 12-OCT-15:30 | 18.30 | 15.05 | 0.337781E+09 | 526.63 | 12-OCT-13:00 | 18.30 | 15.05 |
November | 0.130860E+10 | 2763.15 | 16-NOV-15:40 | 17.20 | 13.51 | 0.308591E+09 | 464.62 | 16-NOV-14:00 | 17.20 | 13.51 |
December | 0.201872E+09 | 2339.30 | 01-DEC-07:05 | 10.68 | 9.22 | 0.294535E+09 | 409.85 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.359447E+11 | 0.422695E+10 | ||||||||
Minimum of Months | 84977675.54 | 2085.28 | 0.82 | -0.6 | 0.276971E+09 | 406.81 | -11.5 | -12.7 | ||
Maximum of Months | 0.653130E+10 | 9273.74 | 29.47 | 23.72 | 0.445450E+09 | 549.53 | 29.47 | 23.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74039077.76 | 1957.78 | 06-JAN-11:03 | -5.3 | -7.0 | 0.141729E+09 | 273.35 | 06-JAN-11:09 | -5.3 | -7.0 |
February | 0.187245E+09 | 2502.73 | 28-FEB-11:02 | -2.0 | -4.1 | 0.129226E+09 | 321.66 | 28-FEB-11:09 | -2.0 | -4.1 |
March | 0.124719E+10 | 4168.27 | 14-MAR-10:05 | 19.87 | 16.80 | 0.166329E+09 | 356.46 | 16-MAR-10:09 | 13.80 | 12.29 |
April | 0.210505E+10 | 5878.89 | 21-APR-10:05 | 12.48 | 6.58 | 0.160376E+09 | 356.46 | 21-APR-14:09 | 14.50 | 8.41 |
May | 0.363644E+10 | 7580.34 | 31-MAY-10:05 | 18.48 | 13.84 | 0.189980E+09 | 356.47 | 26-MAY-10:09 | 18.48 | 13.84 |
June | 0.515120E+10 | 8662.47 | 12-JUN-10:05 | 27.98 | 19.46 | 0.199524E+09 | 356.47 | 22-JUN-12:09 | 19.18 | 13.72 |
July | 0.575949E+10 | 12670.58 | 04-JUL-08:52 | 21.10 | 17.14 | 0.188625E+09 | 356.47 | 12-JUL-10:09 | 20.87 | 14.79 |
August | 0.549502E+10 | 14201.92 | 06-AUG-08:32 | 23.17 | 16.90 | 0.208796E+09 | 356.46 | 16-AUG-10:09 | 21.97 | 16.33 |
September | 0.384370E+10 | 7287.06 | 21-SEP-10:05 | 21.88 | 15.91 | 0.178810E+09 | 356.47 | 12-SEP-12:09 | 21.88 | 15.91 |
October | 0.198850E+10 | 5401.39 | 11-OCT-10:05 | 17.15 | 12.50 | 0.165052E+09 | 356.46 | 03-OCT-10:09 | 17.15 | 12.50 |
November | 0.803486E+09 | 4108.78 | 01-NOV-12:02 | 11.20 | 6.39 | 0.146716E+09 | 356.45 | 03-NOV-10:09 | 5.78 | 3.09 |
December | 0.113055E+09 | 2275.60 | 01-DEC-13:03 | 12.97 | 11.34 | 0.136939E+09 | 299.92 | 01-DEC-13:09 | 12.97 | 11.34 |
Annual Sum or Average | 0.304044E+11 | 0.201210E+10 | ||||||||
Minimum of Months | 74039077.76 | 1957.78 | -5.3 | -7.0 | 0.129226E+09 | 273.35 | -5.3 | -7.0 | ||
Maximum of Months | 0.575949E+10 | 14201.92 | 27.98 | 19.46 | 0.208796E+09 | 356.47 | 21.97 | 16.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.786907E+09 | 4308.11 | 12-JAN-13:40 | -6.5 | -9.0 | 0.315356E+09 | 549.50 | 12-JAN-14:20 | -5.9 | -8.5 |
February | 0.952797E+09 | 6100.08 | 28-FEB-13:40 | 0.00 | -2.9 | 0.289120E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.292514E+10 | 10010.65 | 15-MAR-13:30 | 25.55 | 15.84 | 0.380200E+09 | 549.50 | 29-MAR-13:30 | 9.70 | 3.75 |
April | 0.347312E+10 | 7840.16 | 21-APR-13:07 | 15.40 | 7.97 | 0.346538E+09 | 549.52 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.506657E+10 | 7711.60 | 26-MAY-13:30 | 20.85 | 13.56 | 0.404659E+09 | 549.52 | 16-MAY-13:39 | 20.85 | 13.56 |
June | 0.670411E+10 | 9594.10 | 27-JUN-13:00 | 30.60 | 23.75 | 0.424636E+09 | 549.54 | 22-JUN-13:09 | 30.60 | 23.75 |
July | 0.771115E+10 | 10245.83 | 21-JUL-13:30 | 31.15 | 21.91 | 0.400766E+09 | 549.53 | 06-JUL-13:30 | 31.15 | 21.91 |
August | 0.818486E+10 | 19256.42 | 13-AUG-14:32 | 30.00 | 23.12 | 0.447345E+09 | 549.51 | 02-AUG-13:09 | 30.00 | 23.12 |
September | 0.668248E+10 | 15220.15 | 04-SEP-13:42 | 18.07 | 13.01 | 0.386817E+09 | 550.10 | 20-SEP-13:20 | 23.67 | 14.28 |
October | 0.432912E+10 | 11977.98 | 11-OCT-12:30 | 21.95 | 13.79 | 0.372548E+09 | 549.51 | 30-OCT-13:00 | 15.00 | 8.94 |
November | 0.223067E+10 | 8282.95 | 03-NOV-12:25 | 8.35 | 4.56 | 0.331548E+09 | 549.50 | 01-NOV-13:30 | 8.35 | 4.56 |
December | 0.699161E+09 | 3751.94 | 16-DEC-13:30 | 5.60 | 3.03 | 0.299311E+09 | 530.25 | 04-DEC-11:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.497461E+11 | 0.439885E+10 | ||||||||
Minimum of Months | 0.699161E+09 | 3751.94 | -6.5 | -9.0 | 0.289120E+09 | 530.25 | -5.9 | -8.5 | ||
Maximum of Months | 0.818486E+10 | 19256.42 | 31.15 | 23.75 | 0.447345E+09 | 550.10 | 31.15 | 23.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126465E+09 | 1936.86 | 12-JAN-15:50 | -6.0 | -8.3 | 0.193281E+09 | 257.54 | 30-JAN-10:39 | -9.6 | -10.7 |
February | 0.240606E+09 | 2569.39 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176101E+09 | 309.20 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.149874E+10 | 3660.56 | 15-MAR-14:20 | 25.93 | 16.12 | 0.221414E+09 | 347.83 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.230738E+10 | 6065.21 | 24-APR-16:00 | 13.30 | 7.63 | 0.204378E+09 | 341.69 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.396208E+10 | 9839.61 | 27-MAY-17:42 | 19.18 | 10.48 | 0.242405E+09 | 347.85 | 16-MAY-13:50 | 19.18 | 10.48 |
June | 0.548259E+10 | 16495.71 | 25-JUN-16:32 | 27.40 | 18.24 | 0.262602E+09 | 347.86 | 22-JUN-13:20 | 27.40 | 18.24 |
July | 0.580857E+10 | 16576.34 | 02-JUL-16:52 | 25.00 | 17.00 | 0.250322E+09 | 347.86 | 06-JUL-13:30 | 21.40 | 12.35 |
August | 0.570455E+10 | 16899.70 | 06-AUG-16:32 | 27.80 | 18.98 | 0.277242E+09 | 347.86 | 02-AUG-13:20 | 27.80 | 18.98 |
September | 0.404273E+10 | 11218.59 | 04-SEP-16:22 | 18.30 | 13.01 | 0.231989E+09 | 347.86 | 12-SEP-13:20 | 21.10 | 16.62 |
October | 0.232711E+10 | 6013.54 | 11-OCT-16:00 | 21.70 | 14.52 | 0.213565E+09 | 347.71 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.103679E+10 | 2660.18 | 03-NOV-15:00 | 10.00 | 5.48 | 0.196347E+09 | 318.99 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 0.172619E+09 | 1951.85 | 01-DEC-07:05 | 10.68 | 9.22 | 0.186485E+09 | 257.54 | 11-DEC-10:50 | -12.4 | -12.6 |
Annual Sum or Average | 0.327102E+11 | 0.265613E+10 | ||||||||
Minimum of Months | 0.126465E+09 | 1936.86 | -6.0 | -8.3 | 0.176101E+09 | 257.54 | -12.4 | -12.6 | ||
Maximum of Months | 0.580857E+10 | 16899.70 | 27.80 | 18.98 | 0.277242E+09 | 347.86 | 27.80 | 18.98 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141246E+09 | 12075.15 | 02-JAN-05:01 | -0.7 |
February | 3998510.68 | 5970.34 | 06-FEB-07:01 | -14.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 1676568.69 | 5650.53 | 11-DEC-07:01 | -16.4 |
Annual Sum or Average | 0.146921E+09 | |||
Minimum of Months | 0.00 | 0.00 | -16.4 | |
Maximum of Months | 0.141246E+09 | 12075.15 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125782E+11 | 22484.84 | 10-JAN-06:07 | -13.0 |
February | 0.107731E+11 | 23386.16 | 06-FEB-05:16 | -14.6 |
March | 0.544028E+10 | 23113.99 | 07-MAR-06:12 | -13.3 |
April | 0.219060E+10 | 19606.07 | 17-APR-05:13 | -4.1 |
May | 0.647338E+09 | 8468.24 | 08-MAY-05:03 | 3.40 |
June | 0.177300E+09 | 7878.29 | 06-JUN-05:03 | 6.78 |
July | 0.101278E+09 | 6695.92 | 03-JUL-05:03 | 11.78 |
August | 0.146352E+09 | 6734.22 | 03-AUG-05:03 | 11.10 |
September | 0.490297E+09 | 7749.64 | 05-SEP-05:02 | 6.60 |
October | 0.202311E+10 | 15999.39 | 30-OCT-05:04 | -0.1 |
November | 0.418435E+10 | 18108.01 | 24-NOV-06:13 | -3.7 |
December | 0.115080E+11 | 23349.28 | 11-DEC-05:12 | -17.8 |
Annual Sum or Average | 0.502602E+11 | |||
Minimum of Months | 0.101278E+09 | 6695.92 | -17.8 | |
Maximum of Months | 0.125782E+11 | 23386.16 | 11.78 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383972E+10 | 11191.63 | 02-JAN-06:06 | -1.1 |
February | 0.326017E+10 | 9929.50 | 21-FEB-06:09 | -13.4 |
March | 0.150728E+10 | 8747.99 | 06-MAR-07:11 | -10.5 |
April | 0.510193E+09 | 6081.09 | 17-APR-06:11 | -4.0 |
May | 64256179.11 | 4288.56 | 14-MAY-12:05 | 22.48 |
June | 17129178.73 | 3648.52 | 04-JUN-14:18 | 19.80 |
July | 17865533.95 | 3380.87 | 21-JUL-04:02 | 26.52 |
August | 12403800.83 | 4100.36 | 13-AUG-15:12 | 29.80 |
September | 21793544.20 | 3829.16 | 04-SEP-13:42 | 18.07 |
October | 0.543414E+09 | 4919.54 | 22-OCT-14:12 | 21.70 |
November | 0.108426E+10 | 5645.81 | 24-NOV-07:03 | -3.2 |
December | 0.318945E+10 | 10439.13 | 26-DEC-06:10 | -12.2 |
Annual Sum or Average | 0.140679E+11 | |||
Minimum of Months | 12403800.83 | 3380.87 | -13.4 | |
Maximum of Months | 0.383972E+10 | 11191.63 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255619E+10 | 10110.45 | 02-JAN-08:10 | -1.1 |
February | 0.203781E+10 | 5733.45 | 06-FEB-09:00 | -15.0 |
March | 0.687557E+09 | 4683.16 | 06-MAR-08:23 | -8.9 |
April | 0.133824E+09 | 3148.66 | 17-APR-07:20 | -2.6 |
May | 1623356.57 | 1874.47 | 07-MAY-17:18 | 14.63 |
June | 10646719.86 | 3288.52 | 25-JUN-13:54 | 26.10 |
July | 18904613.19 | 4154.32 | 21-JUL-04:02 | 26.52 |
August | 13898258.06 | 4405.66 | 20-AUG-16:08 | 20.60 |
September | 19235210.04 | 3660.38 | 03-SEP-11:12 | 19.03 |
October | 79401094.51 | 6441.49 | 24-OCT-05:01 | 0.78 |
November | 0.310238E+09 | 2843.96 | 24-NOV-08:17 | -2.4 |
December | 0.185215E+10 | 5803.03 | 11-DEC-08:23 | -14.4 |
Annual Sum or Average | 0.772148E+10 | |||
Minimum of Months | 1623356.57 | 1874.47 | -15.0 | |
Maximum of Months | 0.255619E+10 | 10110.45 | 26.52 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.771178E+09 | 20643.33 | 02-JAN-05:01 | -0.7 |
February | 0.521487E+09 | 18322.41 | 06-FEB-05:01 | -14.8 |
March | 92030813.69 | 16539.69 | 06-MAR-06:02 | -11.1 |
April | 11611174.20 | 14940.68 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 2156032.94 | 13662.61 | 30-OCT-06:01 | -0.4 |
November | 21121285.85 | 14384.12 | 24-NOV-07:01 | -3.2 |
December | 0.385756E+09 | 18309.71 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.180534E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.771178E+09 | 20643.33 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375779E+10 | 31343.46 | 30-JAN-05:11 | -9.6 |
February | 0.315687E+10 | 31334.06 | 06-FEB-05:11 | -14.6 |
March | 0.118453E+10 | 30740.79 | 06-MAR-05:01 | -11.1 |
April | 0.242332E+09 | 28720.10 | 17-APR-04:01 | -3.4 |
May | 4530538.07 | 22479.40 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 505195.80 | 2525.98 | 30-SEP-06:03 | 7.30 |
October | 0.213981E+09 | 27027.01 | 30-OCT-05:01 | -0.1 |
November | 0.618085E+09 | 28616.97 | 24-NOV-05:01 | -3.0 |
December | 0.301369E+10 | 31109.13 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.121923E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.375779E+10 | 31343.46 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.681957E+10 | 15992.92 | 29-JAN-21:52 | -9.4 |
February | 0.599669E+10 | 16583.19 | 05-FEB-21:12 | -12.1 |
March | 0.264366E+10 | 15516.64 | 06-MAR-05:01 | -11.1 |
April | 0.643843E+09 | 14295.52 | 17-APR-04:01 | -3.4 |
May | 51233495.20 | 10452.74 | 08-MAY-05:12 | 3.50 |
June | 1097435.21 | 3025.52 | 14-JUN-06:03 | 7.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 636119.85 | 3180.60 | 31-AUG-06:03 | 11.78 |
September | 28141862.95 | 8938.54 | 30-SEP-05:12 | 7.20 |
October | 0.514312E+09 | 14470.47 | 30-OCT-04:01 | -0.5 |
November | 0.145159E+10 | 14366.59 | 25-NOV-05:01 | -1.7 |
December | 0.604375E+10 | 16547.30 | 26-DEC-00:52 | -11.1 |
Annual Sum or Average | 0.241945E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 0.681957E+10 | 16583.19 | 16.82 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.402817E+10 | 10323.86 | 29-JAN-21:52 | -9.4 |
February | 0.353756E+10 | 10725.85 | 05-FEB-21:12 | -12.1 |
March | 0.131821E+10 | 10023.48 | 06-MAR-05:01 | -11.1 |
April | 0.290684E+09 | 9225.24 | 17-APR-04:01 | -3.4 |
May | 19205895.55 | 6560.89 | 01-MAY-05:03 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 142051.50 | 710.26 | 31-AUG-06:03 | 11.78 |
September | 13667470.81 | 6011.06 | 30-SEP-05:12 | 7.20 |
October | 0.283711E+09 | 9376.89 | 30-OCT-04:01 | -0.5 |
November | 0.855856E+09 | 9360.88 | 25-NOV-05:01 | -1.7 |
December | 0.378194E+10 | 10726.09 | 26-DEC-00:52 | -11.1 |
Annual Sum or Average | 0.141291E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 0.402817E+10 | 10726.09 | 17.05 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.519344E+10 | 15897.65 | 24-JAN-04:22 | -11.7 |
February | 0.476027E+10 | 16490.22 | 05-FEB-21:12 | -12.1 |
March | 0.176113E+10 | 15367.98 | 06-MAR-05:01 | -11.1 |
April | 0.551557E+09 | 14268.74 | 17-APR-04:01 | -3.4 |
May | 59234063.80 | 10335.96 | 01-MAY-06:02 | 2.35 |
June | 4788999.28 | 5699.55 | 14-JUN-06:03 | 7.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 609508.51 | 3047.54 | 31-AUG-06:03 | 11.78 |
September | 20898346.33 | 7597.52 | 30-SEP-05:12 | 7.20 |
October | 0.378305E+09 | 14396.38 | 30-OCT-04:01 | -0.5 |
November | 0.114526E+10 | 14347.20 | 24-NOV-05:01 | -3.0 |
December | 0.478880E+10 | 16538.57 | 26-DEC-00:52 | -11.1 |
Annual Sum or Average | 0.186643E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 0.519344E+10 | 16538.57 | 16.82 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435445E+10 | 11019.02 | 29-JAN-21:52 | -9.4 |
February | 0.380930E+10 | 11467.74 | 05-FEB-21:12 | -12.1 |
March | 0.149769E+10 | 10633.04 | 06-MAR-05:01 | -11.1 |
April | 0.391351E+09 | 9758.07 | 17-APR-04:01 | -3.4 |
May | 36330701.09 | 6940.01 | 01-MAY-06:02 | 2.35 |
June | 2928157.63 | 3528.70 | 14-JUN-06:03 | 7.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 562692.95 | 2813.46 | 31-AUG-06:03 | 11.78 |
September | 17429175.28 | 5658.98 | 30-SEP-05:12 | 7.20 |
October | 0.318729E+09 | 9895.92 | 30-OCT-04:01 | -0.5 |
November | 0.938237E+09 | 9826.35 | 24-NOV-05:01 | -3.0 |
December | 0.388037E+10 | 11457.36 | 26-DEC-00:52 | -11.1 |
Annual Sum or Average | 0.152474E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 0.435445E+10 | 11467.74 | 16.82 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463411E+10 | 11459.72 | 02-JAN-02:62 | -1.7 |
February | 0.405910E+10 | 12091.99 | 06-FEB-04:42 | -15.0 |
March | 0.206891E+10 | 11070.40 | 06-MAR-05:01 | -11.1 |
April | 0.430729E+09 | 10328.73 | 17-APR-04:01 | -3.4 |
May | 28639444.18 | 7852.31 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 659810.19 | 3299.05 | 30-SEP-06:03 | 7.30 |
October | 53604151.02 | 8777.66 | 30-OCT-05:01 | -0.1 |
November | 0.281517E+09 | 9382.92 | 24-NOV-06:01 | -3.8 |
December | 0.300838E+10 | 11370.81 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.145656E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.463411E+10 | 12091.99 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264123E+10 | 7638.63 | 02-JAN-02:62 | -1.7 |
February | 0.224968E+10 | 8074.95 | 06-FEB-04:42 | -15.0 |
March | 0.822443E+09 | 7366.59 | 06-MAR-05:01 | -11.1 |
April | 0.140124E+09 | 6836.42 | 17-APR-04:01 | -3.4 |
May | 7992598.03 | 4622.09 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 511414.42 | 2557.07 | 30-SEP-06:03 | 7.30 |
October | 24882138.92 | 5863.86 | 30-OCT-05:01 | -0.1 |
November | 0.159140E+09 | 6313.22 | 24-NOV-06:01 | -3.8 |
December | 0.183328E+10 | 7605.47 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.787928E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.264123E+10 | 8074.95 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.724385E+10 | 14012.88 | 04-JAN-08:00 | -13.3 |
February | 0.644428E+10 | 14832.40 | 07-FEB-07:50 | -15.8 |
March | 0.352035E+10 | 13386.37 | 07-MAR-07:10 | -12.9 |
April | 0.182904E+10 | 11705.65 | 17-APR-06:50 | -3.5 |
May | 0.716154E+09 | 9861.78 | 01-MAY-06:10 | 2.35 |
June | 0.163126E+09 | 8266.69 | 14-JUN-06:03 | 7.67 |
July | 12553178.13 | 4465.31 | 03-JUL-06:07 | 12.77 |
August | 33223009.57 | 5453.72 | 03-AUG-06:07 | 11.57 |
September | 0.199571E+09 | 7871.37 | 29-SEP-06:03 | 10.00 |
October | 0.918110E+09 | 10663.51 | 17-OCT-06:10 | -2.8 |
November | 0.211163E+10 | 11226.97 | 24-NOV-07:10 | -3.2 |
December | 0.592455E+10 | 14505.04 | 11-DEC-07:50 | -15.3 |
Annual Sum or Average | 0.291164E+11 | |||
Minimum of Months | 12553178.13 | 4465.31 | -15.8 | |
Maximum of Months | 0.724385E+10 | 14832.40 | 12.77 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291976E+10 | 7886.14 | 02-JAN-02:62 | -1.7 |
February | 0.248377E+10 | 8357.70 | 06-FEB-04:42 | -15.0 |
March | 0.926916E+09 | 7595.99 | 06-MAR-05:01 | -11.1 |
April | 0.189021E+09 | 6848.24 | 17-APR-04:01 | -3.4 |
May | 12856099.74 | 5313.39 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 417461.81 | 1750.41 | 30-SEP-06:03 | 7.30 |
October | 27740306.55 | 5917.20 | 30-OCT-05:01 | -0.1 |
November | 0.175934E+09 | 6409.02 | 24-NOV-06:01 | -3.8 |
December | 0.190482E+10 | 7865.98 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.864124E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.291976E+10 | 8357.70 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400646E+10 | 11905.32 | 30-JAN-03:52 | -10.0 |
February | 0.345390E+10 | 12557.57 | 06-FEB-02:52 | -13.9 |
March | 0.121208E+10 | 11283.88 | 06-MAR-05:01 | -11.1 |
April | 0.174659E+09 | 10446.51 | 17-APR-04:01 | -3.4 |
May | 4799901.66 | 7956.83 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1756503.27 | 5734.08 | 30-SEP-06:03 | 7.30 |
October | 0.106280E+09 | 9852.20 | 30-OCT-05:01 | -0.1 |
November | 0.441173E+09 | 10337.30 | 24-NOV-05:01 | -3.0 |
December | 0.324893E+10 | 12019.70 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.126500E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.400646E+10 | 12557.57 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230655E+10 | 8727.16 | 30-JAN-03:52 | -10.0 |
February | 0.200554E+10 | 9241.41 | 06-FEB-02:52 | -13.9 |
March | 0.545757E+09 | 8279.05 | 07-MAR-05:01 | -13.3 |
April | 73181717.50 | 7570.56 | 17-APR-04:01 | -3.4 |
May | 1933347.10 | 3282.88 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1357233.74 | 3630.41 | 30-SEP-06:03 | 7.30 |
October | 62643402.70 | 7190.35 | 30-OCT-05:01 | -0.1 |
November | 0.266034E+09 | 7587.59 | 24-NOV-05:01 | -3.0 |
December | 0.201338E+10 | 8866.52 | 26-DEC-04:41 | -12.1 |
Annual Sum or Average | 0.727639E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.230655E+10 | 9241.41 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284221E+10 | 11800.26 | 30-JAN-03:52 | -10.0 |
February | 0.254461E+10 | 12442.76 | 06-FEB-02:52 | -13.9 |
March | 0.653882E+09 | 11247.72 | 06-MAR-05:01 | -11.1 |
April | 0.146712E+09 | 10190.21 | 17-APR-04:01 | -3.4 |
May | 6532367.40 | 7982.02 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1417370.37 | 5072.85 | 30-SEP-06:03 | 7.30 |
October | 74672342.18 | 9731.53 | 30-OCT-05:01 | -0.1 |
November | 0.328949E+09 | 10285.94 | 24-NOV-05:01 | -3.0 |
December | 0.235954E+10 | 12001.27 | 26-DEC-04:41 | -12.1 |
Annual Sum or Average | 0.895852E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.284221E+10 | 12442.76 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257672E+10 | 8973.65 | 30-JAN-03:52 | -10.0 |
February | 0.219522E+10 | 9526.65 | 06-FEB-03:32 | -14.6 |
March | 0.643996E+09 | 8434.22 | 06-MAR-05:01 | -11.1 |
April | 0.110453E+09 | 7529.07 | 17-APR-04:01 | -3.4 |
May | 5840598.37 | 5655.18 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1455582.73 | 3572.33 | 30-SEP-06:03 | 7.30 |
October | 68620885.20 | 7235.33 | 30-OCT-05:01 | -0.1 |
November | 0.300000E+09 | 7684.70 | 24-NOV-05:01 | -3.0 |
December | 0.209778E+10 | 9103.62 | 26-DEC-04:41 | -12.1 |
Annual Sum or Average | 0.800009E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.6 | |
Maximum of Months | 0.257672E+10 | 9526.65 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187372E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199891E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 987346.63 | 0.120146E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949220E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1496672.37 | 0.556513E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21864105.66 | 0.317306E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36643581.88 | 0.183083E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31950251.84 | 0.215568E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2689512.45 | 0.312712E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706170E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981052E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197496E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95631470.83 | 0.112707E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183083E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36643581.88 | 0.199891E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124917E+10 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133202E+10 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387877.83 | 0.805744E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646250E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 741982.60 | 0.392802E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10588104.69 | 0.222085E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21093765.50 | 0.130068E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18258949.84 | 0.152121E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1342548.27 | 0.220584E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483198E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657184E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131589E+10 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52413228.74 | 0.760712E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130068E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21093765.50 | 0.133202E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189624E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201121E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 456687.54 | 0.124785E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985549E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509451.32 | 0.583399E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17451047.16 | 0.323454E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31253044.56 | 0.189762E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25281421.45 | 0.229374E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1833700.47 | 0.343049E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759094E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101305E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199756E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76785352.50 | 0.115796E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189762E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31253044.56 | 0.201121E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124913E+10 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133287E+10 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 599569.30 | 0.816531E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654025E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 344067.33 | 0.394473E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11652934.27 | 0.227450E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21483681.46 | 0.134681E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18319541.65 | 0.156018E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1370348.11 | 0.220059E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479676E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654158E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131535E+10 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53770142.12 | 0.763443E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134681E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21483681.46 | 0.133287E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103151E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109120E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 848251.76 | 0.659053E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513190E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1014651.65 | 0.278253E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11936698.59 | 0.164460E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21107808.90 | 96296579.42 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17480325.86 | 0.119870E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1153976.24 | 0.184188E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428111E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587588E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111489E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53541713.01 | 0.626861E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96296579.42 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21107808.90 | 0.111489E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689880E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728539E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 412562.37 | 0.444569E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354295E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 294924.20 | 0.204452E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5566488.48 | 0.121333E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11771406.24 | 71813158.03 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9691553.58 | 87460131.27 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 626412.34 | 0.132159E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297018E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395601E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743673E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28363347.22 | 0.427079E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71813158.03 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11771406.24 | 0.743673E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718118E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666129E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10219715.36 | 0.546554E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369239E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4389432.25 | 0.224547E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136872E+09 | 0.116141E+10 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364052E+09 | 0.473827E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281799E+09 | 0.843364E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13856998.71 | 0.150240E+10 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336366E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444703E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666380E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811190E+09 | 0.437014E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473827E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364052E+09 | 0.718118E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687571E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728177E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 502675.03 | 0.450013E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355937E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117334.23 | 0.206967E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5115107.57 | 0.125560E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11318780.73 | 75823643.31 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9331144.46 | 91143170.37 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 610412.20 | 0.132666E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292903E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393650E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742584E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26995454.22 | 0.428299E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75823643.31 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11318780.73 | 0.742584E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160370E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170284E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 639324.88 | 0.105398E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843009E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1071970.18 | 0.495804E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16302582.86 | 0.286975E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29085590.64 | 0.166331E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24576642.24 | 0.197152E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1754757.68 | 0.290477E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651501E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892383E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170715E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73430868.49 | 0.989130E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166331E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29085590.64 | 0.170715E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106844E+10 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113440E+10 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 270294.24 | 0.710717E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575775E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 643289.96 | 0.345796E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9109758.57 | 0.195877E+09 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18191328.33 | 0.114237E+09 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15308493.35 | 0.134832E+09 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1037017.77 | 0.199931E+09 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447353E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600129E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113572E+10 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44560182.23 | 0.666321E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114237E+09 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18191328.33 | 0.113572E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163595E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172258E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 379587.92 | 0.110272E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876183E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 320425.62 | 0.518130E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12594683.36 | 0.291425E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24950402.91 | 0.172456E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19685030.87 | 0.208183E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1370885.53 | 0.313717E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698395E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923486E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173948E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59301016.21 | 0.102027E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172456E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24950402.91 | 0.173948E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106820E+10 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113479E+10 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 482448.75 | 0.716475E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577688E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 270374.82 | 0.346543E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9309978.04 | 0.201174E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18024174.12 | 0.119393E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15069286.02 | 0.139500E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1016232.23 | 0.199265E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439286E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594016E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113581E+10 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44172493.98 | 0.667215E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119393E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18024174.12 | 0.113581E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225560E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237550E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643704.69 | 0.150789E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121772E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 822243.47 | 0.704847E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11937357.73 | 0.409980E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25691593.71 | 0.240151E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22501823.25 | 0.288781E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1165622.73 | 0.438955E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976938E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132012E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243841E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62762345.58 | 0.141749E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240151E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25691593.71 | 0.243841E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276442E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291581E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844336.72 | 0.185434E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150138E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300542.38 | 0.883497E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17715655.74 | 0.516603E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33867458.59 | 0.298789E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30444791.27 | 0.357097E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1724246.13 | 0.530585E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115423E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156203E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295317E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85897030.84 | 0.172920E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298789E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33867458.59 | 0.295317E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273301E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291949E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 936.06 | 0.180977E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147121E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912801E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6137207.28 | 0.524190E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20514630.47 | 0.308968E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14368695.38 | 0.347240E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642357.84 | 0.510920E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107674E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144559E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288650E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41663827.02 | 0.169464E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308968E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20514630.47 | 0.291949E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3568.29 | 12-JAN-05:47 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3697.26 | 13-FEB-05:45 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.57 | 14-MAR-14:00 | 2007.94 | 01-MAR-22:02 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1817.31 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.33 | 14-MAY-14:50 | 1136.17 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.74 | 17-JUN-17:20 | 994.82 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.18 | 16-JUL-11:50 | 706.17 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 584.29 | 13-AUG-12:55 | 435.93 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.38 | 16-SEP-17:02 | 771.88 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 918.78 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1730.69 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3277.77 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.93 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 584.29 | 3697.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2378.76 | 12-JAN-05:43 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2464.82 | 13-FEB-05:45 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1338.77 | 01-MAR-22:02 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1210.33 | 04-APR-21:03 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.17 | 14-MAY-14:50 | 823.62 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.77 | 17-JUN-17:20 | 666.78 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.68 | 21-JUL-04:10 | 469.66 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.65 | 13-AUG-12:55 | 289.76 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.95 | 16-SEP-17:02 | 510.27 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 644.78 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1144.92 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2178.71 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.76 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 352.65 | 2464.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3568.26 | 12-JAN-05:47 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3697.23 | 13-FEB-05:46 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2052.65 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1816.49 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.41 | 14-MAY-14:50 | 1229.67 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.31 | 17-JUN-17:20 | 1004.49 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.32 | 16-JUL-10:30 | 710.68 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.52 | 13-AUG-12:55 | 458.67 | 20-AUG-15:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.15 | 16-SEP-17:02 | 775.01 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 966.29 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1745.65 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3291.30 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.67 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 428.52 | 3697.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2378.89 | 12-JAN-05:47 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2464.82 | 13-FEB-05:46 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | 15-MAR-12:00 | 1392.69 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1209.59 | 04-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.64 | 14-MAY-14:50 | 879.69 | 29-MAY-15:30 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.94 | 18-JUN-10:50 | 669.05 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.46 | 16-JUL-11:50 | 477.55 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.76 | 13-AUG-12:55 | 340.79 | 27-AUG-17:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 16-SEP-12:40 | 507.10 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 611.39 | 30-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1139.35 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2174.02 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.79 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 385.76 | 2464.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1904.60 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1992.60 | 13-FEB-05:58 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.70 | 14-MAR-14:00 | 1089.48 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1029.03 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.50 | 14-MAY-14:55 | 507.59 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.38 | 17-JUN-17:02 | 538.16 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.93 | 16-JUL-11:40 | 392.50 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.18 | 13-AUG-12:55 | 254.00 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.47 | 16-SEP-17:02 | 482.65 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 611.10 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1071.38 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1846.87 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.00 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 324.18 | 1992.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1269.71 | 12-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.37 | 13-FEB-05:57 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 | 14-MAR-14:00 | 743.18 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 691.74 | 16-APR-06:55 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.38 | 14-MAY-14:55 | 383.34 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.24 | 17-JUN-17:02 | 376.92 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.84 | 16-JUL-16:10 | 270.94 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.93 | 13-AUG-12:55 | 169.49 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.68 | 16-SEP-17:02 | 321.01 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 424.86 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 716.42 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1228.00 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.49 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 190.93 | 1328.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 29001.18 | 31-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 31472.18 | 07-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 940.67 | 15-MAR-17:00 | 29530.37 | 07-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20882.65 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.36 | 10-MAY-16:20 | 14657.37 | 01-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4719.57 | 27-JUN-12:00 | 10876.61 | 06-JUN-06:10 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4716.92 | 21-JUL-12:00 | 6850.95 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4712.01 | 10-AUG-12:00 | 7962.29 | 01-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.24 | 15-SEP-12:00 | 12498.06 | 05-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19684.19 | 17-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19903.12 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31646.50 | 11-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6850.95 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4719.57 | 31646.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1269.73 | 12-JAN-05:57 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.39 | 13-FEB-05:58 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.12 | 15-MAR-12:00 | 749.43 | 02-MAR-01:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 680.25 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 10-MAY-14:00 | 396.92 | 06-MAY-17:20 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.10 | 18-JUN-11:00 | 380.49 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.73 | 16-JUL-11:40 | 277.55 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.71 | 13-AUG-12:55 | 170.44 | 19-AUG-17:30 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 16-SEP-12:50 | 318.76 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 410.83 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 715.13 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1225.69 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.44 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 196.71 | 1328.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2967.10 | 12-JAN-05:47 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3122.60 | 13-FEB-05:58 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.38 | 14-MAR-14:00 | 1742.07 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1598.15 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.58 | 14-MAY-15:00 | 936.78 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.67 | 17-JUN-17:20 | 874.71 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.24 | 16-JUL-11:53 | 635.46 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.69 | 13-AUG-12:55 | 393.51 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.79 | 16-SEP-17:02 | 727.50 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 898.19 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1605.11 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2846.71 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.51 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 450.69 | 3122.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1978.06 | 12-JAN-05:50 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2081.71 | 13-FEB-05:57 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 | 15-MAR-14:10 | 1166.46 | 02-MAR-01:00 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1073.19 | 16-APR-06:55 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.07 | 14-MAY-15:00 | 680.50 | 29-MAY-14:00 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.83 | 17-JUN-17:20 | 584.78 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.84 | 16-JUL-15:50 | 420.74 | 06-JUL-02:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.73 | 13-AUG-13:20 | 255.86 | 30-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.82 | 16-SEP-17:02 | 480.63 | 29-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 626.26 | 08-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1063.41 | 17-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1883.84 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.86 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 295.73 | 2081.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2967.01 | 12-JAN-05:43 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3122.57 | 13-FEB-05:58 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1841.29 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1603.65 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.69 | 14-MAY-15:00 | 1017.36 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.47 | 17-JUN-17:20 | 882.96 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.53 | 16-JUL-10:30 | 639.45 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.01 | 13-AUG-15:20 | 396.40 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.04 | 16-SEP-17:02 | 730.30 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 940.76 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1619.88 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2861.05 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.40 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 327.01 | 3122.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1978.16 | 12-JAN-05:47 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2081.69 | 13-FEB-05:58 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 14-MAR-13:02 | 1193.42 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1053.31 | 16-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.99 | 14-MAY-15:00 | 726.98 | 29-MAY-15:30 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.82 | 18-JUN-12:50 | 587.17 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.80 | 16-JUL-11:53 | 427.85 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.86 | 13-AUG-12:55 | 279.54 | 27-AUG-16:30 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 | 16-SEP-12:40 | 476.47 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 597.32 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1054.76 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1884.10 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.54 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 310.86 | 2081.69 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4065.84 | 12-JAN-01:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3956.99 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 15-MAR-14:00 | 2634.35 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2428.66 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.09 | 14-MAY-14:55 | 1165.00 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.02 | 17-JUN-17:02 | 1237.53 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.86 | 21-JUL-03:00 | 907.51 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.43 | 13-AUG-13:00 | 568.64 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 | 16-SEP-17:02 | 1096.02 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1352.77 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2436.36 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4076.62 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 568.64 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.43 | 4076.62 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5033.42 | 12-JAN-01:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4792.09 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.68 | 15-MAR-14:00 | 3256.15 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2930.98 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.11 | 14-MAY-15:00 | 1434.42 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.30 | 17-JUN-17:02 | 1575.58 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.92 | 21-JUL-03:00 | 1138.17 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.83 | 13-AUG-13:00 | 716.97 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.94 | 16-SEP-17:02 | 1319.01 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1569.15 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2939.38 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5034.79 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.97 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.83 | 5034.79 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4864.56 | 12-JAN-05:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4956.92 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 15-MAR-14:00 | 2921.73 | 25-MAR-17:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2715.09 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2132.71 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.81 | 17-JUN-17:02 | 1481.76 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.25 | 21-JUL-02:00 | 1027.05 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.35 | 13-AUG-13:00 | 816.31 | 20-AUG-15:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 | 16-SEP-17:02 | 1132.56 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1349.11 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2557.58 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5228.92 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.35 | 5228.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11381.27 | 20-JAN-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11564.43 | 17-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19492.60 | 16-MAR-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19343.07 | 26-APR-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26907.80 | 24-MAY-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48513.70 | 19-JUN-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 51545.37 | 20-JUL-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 48565.86 | 07-AUG-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45102.75 | 19-SEP-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40234.72 | 24-OCT-05:01 | 4446.85 | 7591.59 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18492.17 | 01-NOV-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14993.95 | 01-DEC-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11381.27 | 0.00 | 3253.54 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51545.37 | 6035.01 | 9760.61 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.54 |
February | 898.62 | 22-FEB-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.53 |
March | 8307.55 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 0.00 |
April | 8767.34 | 23-APR-13:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 681.68 |
May | 11481.92 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.72 |
June | 15399.34 | 27-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.53 | 0.00 |
July | 15817.61 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.30 | 0.00 |
August | 15449.86 | 09-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.09 | 0.00 |
September | 12012.00 | 21-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 |
October | 6727.19 | 11-OCT-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.97 |
November | 2683.54 | 16-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.70 |
December | 333.12 | 01-DEC-13:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15817.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.30 | 966.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5174.55 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.90 |
February | 4950.03 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1492.75 |
March | 4913.84 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1249.55 |
April | 3652.42 | 11-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.33 |
May | 2881.56 | 23-MAY-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.91 |
June | 4286.97 | 27-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 | 0.00 |
July | 5109.60 | 17-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.99 | 0.00 |
August | 4672.22 | 09-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 | 0.00 |
September | 3384.56 | 18-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2527.63 | 24-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.39 |
November | 3039.27 | 17-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.82 |
December | 4311.76 | 29-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2344.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2527.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5174.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 | 2344.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4778.15 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 850.15 |
February | 4668.59 | 11-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.38 |
March | 5248.55 | 18-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.44 |
April | 5381.34 | 13-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.71 |
May | 3501.65 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.48 |
June | 4493.11 | 19-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 |
July | 5176.87 | 17-JUL-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.97 | 0.00 |
August | 5187.96 | 09-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.23 | 0.00 |
September | 4887.52 | 18-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3811.42 | 24-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.06 |
November | 3261.41 | 30-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.67 |
December | 3718.21 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1517.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3261.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5381.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.23 | 1517.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7244.89 | 12-JAN-16:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7400.06 | 17-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13674.77 | 16-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12762.36 | 21-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15922.54 | 31-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22858.77 | 21-JUN-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39738.47 | 17-JUL-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39626.88 | 07-AUG-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23560.17 | 18-SEP-05:13 | 1905.79 | 3253.54 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14282.34 | 12-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9925.12 | 01-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7788.57 | 01-DEC-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7244.89 | 1905.79 | 3253.54 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39738.47 | 6035.01 | 9760.61 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7189.95 | 11-JAN-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7477.64 | 28-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14494.51 | 15-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13966.67 | 21-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19002.50 | 31-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22473.74 | 27-JUN-14:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42945.19 | 21-JUL-05:02 | 3811.58 | 6507.07 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26003.29 | 07-AUG-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19252.97 | 18-SEP-14:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13550.96 | 12-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8795.66 | 01-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7686.50 | 01-DEC-16:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7189.95 | 2541.06 | 4338.05 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42945.19 | 6198.29 | 9760.61 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2639.91 | 14-JAN-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.25 |
February | 2649.59 | 18-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.45 |
March | 4421.89 | 15-MAR-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 | 0.00 |
April | 3979.31 | 21-APR-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.14 |
May | 5196.51 | 23-MAY-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
June | 7476.72 | 27-JUN-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 93.19 | 0.00 |
July | 12665.88 | 21-JUL-04:02 | 0.00 | 1371.75 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 54.86 | 0.00 |
August | 7475.11 | 09-AUG-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.22 | 0.00 |
September | 5841.24 | 17-SEP-15:11 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.68 |
October | 4264.43 | 22-OCT-14:12 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.77 |
November | 3129.83 | 16-NOV-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.04 |
December | 2653.30 | 02-DEC-17:02 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2639.91 | 0.00 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12665.88 | 1306.65 | 2057.62 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 93.19 | 517.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1703.25 | 14-JAN-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.48 |
February | 1968.78 | 28-FEB-09:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.10 |
March | 3237.37 | 15-MAR-14:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 0.00 |
April | 4586.75 | 24-APR-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.86 |
May | 7030.09 | 31-MAY-09:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.88 |
June | 11331.62 | 11-JUN-09:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.81 |
July | 11937.07 | 04-JUL-09:12 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.77 |
August | 8222.49 | 10-AUG-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 | 0.00 |
September | 6068.46 | 18-SEP-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 |
October | 3684.04 | 11-OCT-09:40 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.70 |
November | 2235.67 | 03-NOV-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 |
December | 1709.75 | 02-DEC-17:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1703.25 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11937.07 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 | 345.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4047.13 | 12-JAN-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.34 |
February | 5550.69 | 28-FEB-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.13 |
March | 10366.97 | 15-MAR-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 0.00 |
April | 8011.83 | 21-APR-13:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.17 |
May | 8344.17 | 26-MAY-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 |
June | 10363.25 | 27-JUN-13:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 133.01 | 0.00 |
July | 13279.63 | 21-JUL-04:02 | 0.00 | 1371.75 | 3088.80 | 0.00 | 0.00 | 0.00 | 0.00 | 53.97 | 0.00 |
August | 11970.15 | 08-AUG-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 0.00 |
September | 12520.01 | 21-SEP-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 9.64 | 0.00 |
October | 11662.08 | 11-OCT-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 |
November | 7059.36 | 03-NOV-12:35 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.78 |
December | 3989.86 | 16-DEC-13:30 | 133.92 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3989.86 | 0.00 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13279.63 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 133.01 | 858.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1876.35 | 14-JAN-17:02 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.41 |
February | 2693.33 | 28-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.86 |
March | 3995.87 | 15-MAR-14:20 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 0.00 |
April | 6220.37 | 24-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 |
May | 10851.35 | 07-MAY-16:42 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.94 |
June | 14406.25 | 11-JUN-18:42 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 |
July | 18164.99 | 02-JUL-16:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.46 |
August | 12570.39 | 12-AUG-17:05 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.99 |
September | 8693.55 | 21-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 | 0.00 |
October | 6038.44 | 11-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
November | 2721.84 | 03-NOV-15:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.70 |
December | 1902.55 | 16-DEC-17:02 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1876.35 | 0.00 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18164.99 | 805.38 | 1302.56 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 371.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2036.34 | 14-JAN-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.56 |
February | 2031.99 | 18-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.64 |
March | 2928.12 | 15-MAR-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 0.00 |
April | 2633.49 | 07-APR-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 |
May | 3138.87 | 23-MAY-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 0.00 |
June | 4888.37 | 27-JUN-13:20 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 0.00 |
July | 6021.66 | 21-JUL-13:50 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.81 | 0.00 |
August | 5825.43 | 09-AUG-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 | 0.00 |
September | 4483.64 | 15-SEP-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 | 0.00 |
October | 3223.14 | 22-OCT-14:12 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.70 |
November | 2587.15 | 16-NOV-15:02 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.29 |
December | 2294.90 | 01-DEC-07:05 | 1071.35 | 2743.50 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2031.99 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6021.66 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 56.93 | 165.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1387.51 | 14-JAN-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.35 |
February | 1416.37 | 28-FEB-09:20 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.65 |
March | 2118.35 | 15-MAR-14:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 | 0.00 |
April | 2849.11 | 24-APR-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.09 |
May | 4230.60 | 31-MAY-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.58 |
June | 6155.30 | 12-JUN-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 | 0.00 |
July | 10555.23 | 04-JUL-09:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.38 |
August | 6876.18 | 10-AUG-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 0.00 |
September | 5308.33 | 21-SEP-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 |
October | 3380.14 | 11-OCT-09:30 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 |
November | 2030.21 | 03-NOV-08:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.24 |
December | 1563.83 | 01-DEC-07:05 | 678.26 | 1736.86 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1387.51 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10555.23 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 | 116.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2317.84 | 12-JAN-13:17 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3758.06 |
February | 2461.88 | 18-FEB-14:30 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.00 |
March | 6210.65 | 15-MAR-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 173.50 | 0.00 |
April | 3319.98 | 26-APR-14:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.62 |
May | 4577.28 | 23-MAY-14:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 |
June | 11026.57 | 27-JUN-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4719.57 | 0.00 |
July | 12549.81 | 21-JUL-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4716.92 | 0.00 |
August | 12828.54 | 10-AUG-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4712.01 | 0.00 |
September | 10648.45 | 21-SEP-13:50 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 163.45 | 0.00 |
October | 9828.86 | 11-OCT-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.09 |
November | 3669.56 | 03-NOV-14:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1637.18 |
December | 2945.29 | 16-DEC-13:30 | 133.92 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2317.84 | 133.92 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12828.54 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 4719.57 | 3758.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1469.55 | 12-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.38 |
February | 1912.18 | 28-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.32 |
March | 2266.80 | 15-MAR-14:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 0.00 |
April | 3057.17 | 24-APR-17:30 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 |
May | 4758.99 | 31-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 |
June | 6385.72 | 20-JUN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 | 0.00 |
July | 13541.51 | 02-JUL-17:21 | 0.00 | 578.92 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 |
August | 9493.12 | 12-AUG-17:07 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 |
September | 8672.16 | 04-SEP-16:52 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.66 |
October | 4991.57 | 11-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 |
November | 2158.47 | 03-NOV-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.16 |
December | 1631.86 | 01-DEC-07:05 | 678.21 | 1736.75 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1469.55 | 0.00 | 361.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13541.51 | 805.38 | 1736.75 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 | 260.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2087.21 | 14-JAN-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.14 |
February | 2085.28 | 18-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.19 |
March | 3797.74 | 15-MAR-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
April | 3232.67 | 07-APR-14:10 | 2544.47 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 |
May | 4833.64 | 23-MAY-14:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
June | 6671.07 | 27-JUN-13:20 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 88.71 | 0.00 |
July | 9273.74 | 21-JUL-04:02 | 0.00 | 1371.75 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 36.11 | 0.00 |
August | 6792.58 | 09-AUG-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 52.04 | 0.00 |
September | 5175.68 | 15-SEP-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 0.00 |
October | 3334.85 | 12-OCT-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 |
November | 2763.15 | 16-NOV-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.67 |
December | 2339.30 | 01-DEC-07:05 | 1071.35 | 2743.50 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2085.28 | 0.00 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9273.74 | 2544.47 | 4115.24 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 88.71 | 260.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1957.78 | 06-JAN-11:03 | 2416.29 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 |
February | 2502.73 | 28-FEB-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.80 |
March | 4168.27 | 14-MAR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 |
April | 5878.89 | 21-APR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 |
May | 7580.34 | 31-MAY-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.06 |
June | 8662.47 | 12-JUN-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 0.00 |
July | 12670.58 | 04-JUL-08:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.05 |
August | 14201.92 | 06-AUG-08:32 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.88 |
September | 7287.06 | 21-SEP-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 |
October | 5401.39 | 11-OCT-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 |
November | 4108.78 | 01-NOV-12:02 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.64 |
December | 2275.60 | 01-DEC-13:03 | 2416.29 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1957.78 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14201.92 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 166.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4308.11 | 12-JAN-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.85 |
February | 6100.08 | 28-FEB-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.91 |
March | 10010.65 | 15-MAR-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 |
April | 7840.16 | 21-APR-13:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.18 |
May | 7711.60 | 26-MAY-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
June | 9594.10 | 27-JUN-13:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 111.16 | 0.00 |
July | 10245.83 | 21-JUL-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 73.86 | 0.00 |
August | 19256.42 | 13-AUG-14:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 212.55 | 0.00 |
September | 15220.15 | 04-SEP-13:42 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.12 |
October | 11977.98 | 11-OCT-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.07 |
November | 8282.95 | 03-NOV-12:25 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 |
December | 3751.94 | 16-DEC-13:30 | 133.92 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3751.94 | 133.92 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19256.42 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 212.55 | 753.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1936.86 | 12-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.20 |
February | 2569.39 | 28-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.91 |
March | 3660.56 | 15-MAR-14:20 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 0.00 |
April | 6065.21 | 24-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 |
May | 9839.61 | 27-MAY-17:42 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.87 |
June | 16495.71 | 25-JUN-16:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 | 0.00 |
July | 16576.34 | 02-JUL-16:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 |
August | 16899.70 | 06-AUG-16:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 | 0.00 |
September | 11218.59 | 04-SEP-16:22 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.95 |
October | 6013.54 | 11-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
November | 2660.18 | 03-NOV-15:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.69 |
December | 1951.85 | 01-DEC-07:05 | 678.21 | 1736.75 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1936.86 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16899.70 | 805.38 | 1736.75 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 413.20 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.154622E+12 | 120901.16 | 09-JAN-16:00 | 0.196502E+12 | 299314.58 | 30-JAN-07:19 |
February | 0.138393E+12 | 110864.94 | 06-FEB-08:09 | 0.174144E+12 | 321221.38 | 06-FEB-07:00 |
March | 0.157107E+12 | 138358.55 | 15-MAR-14:09 | 0.909446E+11 | 288454.95 | 06-MAR-07:10 |
April | 0.140936E+12 | 119056.10 | 07-APR-14:09 | 0.317365E+11 | 233070.14 | 17-APR-06:10 |
May | 0.155652E+12 | 145253.52 | 31-MAY-15:00 | 0.613204E+10 | 124449.79 | 01-MAY-06:10 |
June | 0.179685E+12 | 185106.57 | 27-JUN-12:00 | 0.680586E+09 | 48239.99 | 14-JUN-06:10 |
July | 0.197388E+12 | 192352.22 | 19-JUL-15:09 | 88933101.75 | 9413.83 | 13-JUL-06:10 |
August | 0.201633E+12 | 184970.04 | 18-AUG-14:30 | 0.239904E+09 | 35022.28 | 31-AUG-06:10 |
September | 0.164783E+12 | 163359.02 | 21-SEP-15:20 | 0.219579E+10 | 87579.05 | 29-SEP-06:10 |
October | 0.151260E+12 | 139989.43 | 11-OCT-15:20 | 0.209705E+11 | 196003.06 | 30-OCT-06:10 |
November | 0.147517E+12 | 132041.04 | 16-NOV-16:00 | 0.564676E+11 | 229495.05 | 24-NOV-07:10 |
December | 0.151459E+12 | 120963.13 | 26-DEC-16:40 | 0.168935E+12 | 323034.70 | 11-DEC-07:19 |
Annual Sum or Average | 0.194044E+13 | 0.749037E+12 | ||||
Minimum of Months | 0.138393E+12 | 110864.94 | 88933101.75 | 9413.83 | ||
Maximum of Months | 0.201633E+12 | 192352.22 | 0.196502E+12 | 323034.70 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.247627E+11 | 0.613996E+11 | 0.230900E+10 | 0.126789E+11 | 0.996144E+09 | 0.00 | 912656.45 | 0.00 | 0.00 | 0.00 | 0.522718E+10 | 0.00 |
February | 0.428574E+11 | 0.206641E+11 | 0.556056E+11 | 0.209511E+10 | 0.114803E+11 | 0.877886E+09 | 0.00 | 612315.88 | 0.00 | 0.00 | 0.00 | 0.481179E+10 | 0.00 |
March | 0.509265E+11 | 0.205290E+11 | 0.635880E+11 | 0.240664E+10 | 0.116209E+11 | 0.450659E+09 | 0.00 | 0.198678E+10 | 0.00 | 0.00 | 0.00 | 0.559885E+10 | 0.00 |
April | 0.454877E+11 | 0.174933E+11 | 0.594055E+11 | 0.224272E+10 | 0.104577E+11 | 0.162043E+09 | 0.00 | 0.823377E+09 | 0.00 | 0.00 | 0.00 | 0.486400E+10 | 0.00 |
May | 0.490872E+11 | 0.159890E+11 | 0.624938E+11 | 0.235782E+10 | 0.129019E+11 | 46218063.95 | 0.00 | 0.784671E+10 | 0.00 | 0.00 | 0.00 | 0.492938E+10 | 0.00 |
June | 0.488499E+11 | 0.144667E+11 | 0.612808E+11 | 0.231841E+10 | 0.177692E+11 | 17197979.95 | 0.00 | 0.303761E+11 | 0.00 | 0.00 | 0.00 | 0.460658E+10 | 0.00 |
July | 0.457251E+11 | 0.153494E+11 | 0.606074E+11 | 0.228147E+10 | 0.203608E+11 | 12689319.98 | 0.00 | 0.488888E+11 | 0.00 | 0.00 | 0.00 | 0.416223E+10 | 0.00 |
August | 0.509265E+11 | 0.171420E+11 | 0.635880E+11 | 0.240664E+10 | 0.208168E+11 | 13809386.66 | 0.00 | 0.422394E+11 | 0.00 | 0.00 | 0.00 | 0.449964E+10 | 0.00 |
September | 0.454877E+11 | 0.188445E+11 | 0.593832E+11 | 0.224140E+10 | 0.150873E+11 | 22960125.56 | 0.00 | 0.195806E+11 | 0.00 | 0.00 | 0.00 | 0.413523E+10 | 0.00 |
October | 0.472479E+11 | 0.219072E+11 | 0.614108E+11 | 0.230966E+10 | 0.111382E+11 | 0.110052E+09 | 0.00 | 0.266524E+10 | 0.00 | 0.00 | 0.00 | 0.447105E+10 | 0.00 |
November | 0.466941E+11 | 0.233124E+11 | 0.599069E+11 | 0.224962E+10 | 0.989006E+10 | 0.268688E+09 | 0.00 | 0.535600E+09 | 0.00 | 0.00 | 0.00 | 0.466002E+10 | 0.00 |
December | 0.457251E+11 | 0.253302E+11 | 0.605962E+11 | 0.228081E+10 | 0.117879E+11 | 0.847426E+09 | 0.00 | 2600182.15 | 0.00 | 0.00 | 0.00 | 0.488921E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.235791E+12 | 0.729266E+12 | 0.274993E+11 | 0.165990E+12 | 0.382577E+10 | 0.00 | 0.154947E+12 | 0.00 | 0.00 | 0.00 | 0.568552E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.144667E+11 | 0.556056E+11 | 0.209511E+10 | 0.989006E+10 | 12689319.98 | 0.00 | 612315.88 | 0.00 | 0.00 | 0.00 | 0.413523E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.253302E+11 | 0.635880E+11 | 0.240664E+10 | 0.208168E+11 | 0.996144E+09 | 0.00 | 0.488888E+11 | 0.00 | 0.00 | 0.00 | 0.559885E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.196502E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.174144E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.909446E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.317365E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.613204E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.680586E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 88933101.75 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.239904E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.219579E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.209705E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.564676E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.168935E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.749037E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 88933101.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.196502E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 03-JAN-13:20 | 16551.60 | 02-JAN-06:19 | 1226.36 | 30-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 01-FEB-12:09 | 15364.56 | 06-FEB-07:10 | 1300.92 | 06-FEB-07:00 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 03-MAR-12:09 | 13988.33 | 06-MAR-06:10 | 1209.75 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 03-APR-07:19 | 12301.17 | 21-APR-15:30 | 1086.47 | 17-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 08-MAY-07:10 | 16962.34 | 31-MAY-15:00 | 534.89 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 13-JUN-16:10 | 24511.07 | 27-JUN-14:30 | 299.28 | 14-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 27378.38 | 21-JUL-13:30 | 52.06 | 03-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:19 | 28798.89 | 09-AUG-15:20 | 155.73 | 31-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 29-SEP-16:10 | 23485.69 | 21-SEP-15:20 | 408.30 | 29-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 04-OCT-16:10 | 15315.89 | 11-OCT-15:20 | 1001.46 | 30-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 01-NOV-12:09 | 10407.00 | 24-NOV-07:10 | 1081.31 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 04-DEC-08:20 | 15364.56 | 11-DEC-07:10 | 1313.86 | 11-DEC-07:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 10407.00 | 52.06 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 28798.89 | 1313.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 191.06 | 09-JAN-06:19 | 0.00 | 0.00 | 0.00 | 7127.78 | 27-JAN-12:00 | 0.00 |
February | 162.10 | 12-FEB-09:39 | 0.00 | 0.00 | 0.00 | 7140.61 | 13-FEB-12:20 | 0.00 |
March | 28882.72 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 7130.60 | 03-MAR-12:39 | 0.00 |
April | 14226.82 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 6730.33 | 03-APR-11:39 | 0.00 |
May | 31889.36 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 | 6579.44 | 03-MAY-11:50 | 0.00 |
June | 65960.66 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 6202.62 | 01-JUN-11:50 | 0.00 |
July | 68816.87 | 19-JUL-14:00 | 0.00 | 0.00 | 0.00 | 5789.98 | 03-JUL-11:20 | 0.00 |
August | 61870.87 | 18-AUG-14:30 | 0.00 | 0.00 | 0.00 | 5672.01 | 02-AUG-11:20 | 0.00 |
September | 45933.12 | 15-SEP-12:09 | 0.00 | 0.00 | 0.00 | 5788.19 | 29-SEP-11:50 | 0.00 |
October | 27432.17 | 11-OCT-15:20 | 0.00 | 0.00 | 0.00 | 6199.90 | 31-OCT-11:30 | 0.00 |
November | 11575.19 | 16-NOV-17:00 | 0.00 | 0.00 | 0.00 | 6581.19 | 30-NOV-12:20 | 0.00 |
December | 962.69 | 01-DEC-10:00 | 0.00 | 0.00 | 0.00 | 6728.68 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 162.10 | 0.00 | 0.00 | 0.00 | 5672.01 | 0.00 | ||
Maximum of Months | 68816.87 | 0.00 | 0.00 | 0.00 | 7140.61 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 120901.16 | 09-JAN-16:00 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 6990.16 | 728.84 | 0.00 | 0.00 | 0.00 |
February | 110864.94 | 06-FEB-08:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 12603.28 | 1241.83 | 0.00 | 0.00 | 0.00 |
March | 138358.55 | 15-MAR-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 12768.62 | 6.85 | 0.00 | 28882.72 | 0.00 |
April | 119056.10 | 07-APR-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 9655.30 | 6.85 | 0.00 | 12709.96 | 0.00 |
May | 145253.52 | 31-MAY-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 16962.34 | 6.85 | 0.00 | 30711.04 | 0.00 |
June | 185106.57 | 27-JUN-12:00 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 23676.06 | 6.93 | 0.00 | 65960.66 | 0.00 |
July | 192352.22 | 19-JUL-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 27175.26 | 6.94 | 0.00 | 68139.26 | 0.00 |
August | 184970.04 | 18-AUG-14:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 27097.19 | 6.94 | 0.00 | 61870.87 | 0.00 |
September | 163359.02 | 21-SEP-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 23485.69 | 6.85 | 0.00 | 42811.66 | 0.00 |
October | 139989.43 | 11-OCT-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 15315.89 | 6.85 | 0.00 | 27432.17 | 0.00 |
November | 132041.04 | 16-NOV-16:00 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 8403.67 | 6.85 | 0.00 | 11047.19 | 0.00 |
December | 120963.13 | 26-DEC-16:40 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 6990.16 | 812.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 110864.94 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 6990.16 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 192352.22 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 27175.26 | 1241.83 | 0.00 | 68139.26 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 299314.58 | 30-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 321221.38 | 06-FEB-07:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 288454.95 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 233070.14 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 124449.79 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 48239.99 | 14-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 9413.83 | 13-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 35022.28 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 87579.05 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 196003.06 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 229495.05 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 323034.70 | 11-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 9413.83 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 323034.70 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.58 | 2.00 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 19.58 | 2.00 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.58 | 2.00 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.29 | 2.67 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
February | 0.83 | 19.43 | 0.83 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.75 | 0.67 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
Annual Sum or Average | 4.33 | 19.39 | 4.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.75 | 2.67 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.59 | 3.67 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
February | 4.83 | 18.73 | 3.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
March | 1.17 | 18.69 | 0.83 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
April | 0.17 | 19.31 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.36 | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
December | 4.00 | 19.00 | 3.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 15.67 | 18.77 | 11.67 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 19.36 | 3.67 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.33 | 15.26 | 13.17 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
February | 42.33 | 15.61 | 13.67 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
March | 13.50 | 15.62 | 2.33 | 15.89 | 0.00 | 15.89 | 0.00 | 15.89 |
April | 0.50 | 17.38 | 0.17 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
November | 0.83 | 18.14 | 0.50 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
December | 35.67 | 15.37 | 10.67 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
Annual Sum or Average | 135.67 | 15.47 | 40.50 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.33 | 18.14 | 13.67 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.17 | 15.26 | 11.83 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
February | 41.50 | 15.49 | 11.33 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
March | 12.67 | 15.60 | 1.50 | 15.88 | 0.00 | 15.88 | 0.00 | 15.88 |
April | 0.83 | 17.75 | 0.33 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.01 | 2.17 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.52 | 0.67 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
November | 1.33 | 17.23 | 0.50 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
December | 36.83 | 15.35 | 10.83 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
Annual Sum or Average | 135.83 | 15.43 | 36.33 | 15.73 | 3.17 | 15.95 | 3.17 | 16.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.17 | 17.75 | 11.83 | 18.21 | 2.17 | 28.01 | 2.17 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.33 | 15.35 | 8.67 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
February | 37.50 | 15.59 | 10.17 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
March | 8.17 | 15.84 | 1.33 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
April | 0.50 | 17.45 | 0.17 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.43 | 0.50 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.45 | 1.00 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
October | 0.33 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
November | 0.83 | 18.19 | 0.50 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
December | 29.00 | 15.48 | 6.83 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
Annual Sum or Average | 111.67 | 15.54 | 27.67 | 15.89 | 2.50 | 16.09 | 2.50 | 16.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.50 | 18.19 | 10.17 | 18.58 | 1.00 | 27.45 | 1.00 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.67 | 15.16 | 13.33 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
February | 42.83 | 15.46 | 13.67 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
March | 10.83 | 15.57 | 1.83 | 15.75 | 0.00 | 15.75 | 0.00 | 15.75 |
April | 0.50 | 17.48 | 0.17 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.93 | 1.67 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.25 | 2.00 | 28.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.86 | 1.50 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.17 | 27.43 |
October | 0.50 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
November | 1.00 | 18.00 | 0.50 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
December | 35.50 | 15.27 | 9.67 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
Annual Sum or Average | 134.83 | 15.35 | 39.17 | 15.62 | 8.83 | 16.22 | 5.67 | 16.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 | 15.32 |
Maximum of Months | 43.67 | 18.00 | 13.67 | 18.41 | 3.83 | 28.25 | 2.00 | 28.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.17 | 16.66 | 5.00 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
February | 14.50 | 17.07 | 5.67 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 |
March | 3.00 | 17.68 | 1.17 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.83 | 17.23 | 2.83 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
Annual Sum or Average | 39.50 | 16.99 | 14.67 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.17 | 17.68 | 5.67 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.17 | 16.52 | 3.83 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
February | 14.00 | 16.84 | 4.67 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
March | 1.67 | 17.38 | 0.33 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.35 | 0.67 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.50 | 17.05 | 2.33 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
Annual Sum or Average | 34.33 | 16.80 | 11.17 | 17.42 | 0.67 | 17.56 | 0.67 | 17.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.00 | 17.38 | 4.67 | 17.78 | 0.67 | 27.35 | 0.67 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 102.83 | 17.04 | 95.83 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
February | 95.00 | 17.06 | 88.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
March | 56.17 | 18.15 | 55.67 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
April | 29.00 | 18.87 | 29.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
May | 7.17 | 19.54 | 7.17 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
June | 0.33 | 20.30 | 0.33 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10.67 | 18.93 | 10.67 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
November | 42.50 | 19.17 | 42.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
December | 82.33 | 17.29 | 80.17 | 17.30 | 0.00 | 17.30 | 0.00 | 17.30 |
Annual Sum or Average | 426.00 | 17.67 | 409.33 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.83 | 20.30 | 95.83 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.00 | 16.28 | 4.17 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
February | 15.00 | 16.89 | 5.17 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
March | 1.83 | 17.51 | 0.50 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.74 | 0.83 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.83 | 17.08 | 2.50 | 17.83 | 0.00 | 17.83 | 0.00 | 17.83 |
Annual Sum or Average | 38.67 | 16.72 | 12.33 | 17.36 | 2.83 | 17.91 | 1.50 | 18.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.00 | 17.51 | 5.17 | 17.97 | 2.17 | 27.74 | 0.83 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.00 | 16.10 | 4.50 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
February | 18.67 | 16.49 | 6.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
March | 2.17 | 16.63 | 0.33 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.83 | 16.26 | 5.33 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
Annual Sum or Average | 52.67 | 16.30 | 16.17 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 18.67 | 16.63 | 6.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.17 | 15.74 | 2.67 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
February | 16.33 | 15.95 | 3.50 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
March | 1.67 | 16.57 | 0.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.52 | 0.33 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.92 | 2.50 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.55 | 0.67 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.50 | 16.01 | 3.33 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
Annual Sum or Average | 46.67 | 15.91 | 9.67 | 16.38 | 3.50 | 17.05 | 3.50 | 17.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.33 | 16.57 | 3.50 | 16.82 | 2.50 | 27.92 | 2.50 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 16.26 | 3.33 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
February | 16.83 | 16.59 | 5.33 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
March | 0.67 | 17.50 | 0.17 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.47 | 1.33 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.52 | 1.33 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.83 | 16.65 | 3.17 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
Annual Sum or Average | 42.00 | 16.51 | 12.00 | 17.16 | 3.33 | 17.76 | 3.33 | 18.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.83 | 17.50 | 5.33 | 17.87 | 1.33 | 27.52 | 1.33 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.83 | 15.69 | 3.50 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
February | 16.83 | 16.04 | 4.33 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
March | 1.33 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.67 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.81 | 1.50 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.11 | 2.17 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.81 | 1.00 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.33 | 15.99 | 4.00 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
Annual Sum or Average | 49.33 | 15.91 | 11.83 | 16.34 | 9.00 | 17.82 | 5.67 | 18.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.83 | 16.47 | 4.33 | 16.64 | 3.67 | 28.11 | 2.17 | 28.08 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.36 | 60.17 | 22.13 | 60.17 | 21.95 |
February | 454.00 | 22.57 | 20.67 | 22.50 | 20.67 | 22.44 |
March | 436.17 | 23.41 | 23.83 | 23.44 | 1.83 | 23.43 |
April | 289.17 | 23.71 | 19.67 | 23.82 | 0.00 | 23.82 |
May | 86.17 | 23.89 | 175.17 | 24.62 | 0.00 | 24.62 |
June | 0.00 | 0.00 | 379.50 | 24.55 | 0.00 | 24.55 |
July | 0.00 | 0.00 | 492.33 | 24.55 | 0.00 | 24.55 |
August | 0.00 | 0.00 | 506.33 | 24.46 | 0.00 | 24.46 |
September | 2.33 | 23.83 | 377.83 | 24.58 | 0.00 | 24.58 |
October | 131.00 | 23.79 | 105.17 | 24.26 | 0.00 | 24.26 |
November | 357.33 | 23.75 | 11.83 | 23.79 | 0.00 | 23.79 |
December | 486.83 | 22.92 | 8.50 | 22.89 | 8.50 | 22.86 |
Annual Sum or Average | 2745.00 | 23.10 | 2181.00 | 23.69 | 91.17 | 23.63 |
Minimum of Months | 0.00 | 0.00 | 8.50 | 22.13 | 0.00 | 21.95 |
Maximum of Months | 502.00 | 23.89 | 506.33 | 24.62 | 60.17 | 24.62 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.00 | 279.83 | 20.79 | 279.83 | 20.69 |
February | 454.00 | 21.18 | 228.33 | 20.97 | 228.33 | 20.87 |
March | 477.67 | 22.10 | 78.50 | 21.97 | 70.33 | 21.84 |
April | 455.00 | 22.89 | 3.33 | 22.88 | 3.33 | 22.86 |
May | 265.17 | 23.44 | 54.67 | 23.59 | 0.00 | 23.59 |
June | 58.83 | 23.60 | 274.33 | 24.14 | 0.00 | 24.14 |
July | 0.00 | 0.00 | 466.00 | 24.29 | 0.00 | 24.29 |
August | 0.83 | 23.50 | 449.50 | 24.28 | 0.00 | 24.28 |
September | 93.17 | 23.32 | 223.67 | 24.03 | 0.00 | 24.03 |
October | 398.83 | 22.94 | 9.83 | 22.97 | 0.50 | 22.96 |
November | 486.83 | 22.40 | 8.33 | 22.37 | 8.33 | 22.34 |
December | 497.00 | 21.27 | 213.33 | 21.06 | 213.33 | 20.94 |
Annual Sum or Average | 3689.33 | 22.10 | 2289.67 | 22.43 | 804.00 | 22.21 |
Minimum of Months | 0.00 | 0.00 | 3.33 | 20.79 | 0.00 | 20.69 |
Maximum of Months | 502.00 | 23.60 | 466.00 | 24.29 | 279.83 | 24.29 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 429.67 | 20.25 | 429.67 | 20.22 |
February | 454.00 | 20.46 | 355.67 | 20.33 | 355.67 | 20.28 |
March | 492.33 | 21.29 | 207.50 | 21.06 | 199.50 | 20.91 |
April | 471.50 | 22.06 | 54.67 | 21.87 | 54.67 | 21.71 |
May | 344.00 | 22.98 | 49.00 | 23.12 | 1.83 | 23.11 |
June | 116.83 | 23.28 | 238.67 | 23.88 | 0.00 | 23.88 |
July | 22.00 | 23.21 | 410.50 | 24.22 | 0.00 | 24.22 |
August | 56.67 | 23.20 | 360.33 | 24.09 | 0.00 | 24.09 |
September | 234.83 | 22.90 | 132.33 | 23.38 | 0.00 | 23.38 |
October | 472.33 | 21.94 | 64.33 | 21.76 | 61.33 | 21.60 |
November | 489.00 | 21.21 | 153.50 | 20.98 | 153.50 | 20.83 |
December | 497.00 | 20.41 | 378.67 | 20.29 | 378.67 | 20.25 |
Annual Sum or Average | 4152.50 | 21.45 | 2834.83 | 21.64 | 1634.83 | 21.36 |
Minimum of Months | 22.00 | 20.33 | 49.00 | 20.25 | 0.00 | 20.22 |
Maximum of Months | 502.00 | 23.28 | 429.67 | 24.22 | 429.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 494.17 | 19.76 | 494.17 | 19.76 |
February | 454.00 | 19.83 | 445.00 | 19.82 | 445.00 | 19.82 |
March | 508.33 | 20.43 | 333.00 | 20.26 | 330.67 | 20.18 |
April | 482.67 | 20.89 | 163.33 | 20.65 | 163.33 | 20.51 |
May | 447.00 | 21.85 | 53.33 | 21.88 | 27.67 | 21.79 |
June | 250.50 | 22.44 | 182.00 | 23.09 | 4.33 | 23.10 |
July | 124.00 | 22.86 | 315.83 | 23.77 | 18.67 | 23.82 |
August | 192.00 | 22.35 | 242.00 | 23.30 | 2.00 | 23.30 |
September | 383.83 | 21.97 | 74.17 | 22.24 | 21.67 | 22.28 |
October | 502.00 | 20.82 | 154.00 | 20.57 | 154.00 | 20.41 |
November | 489.00 | 20.30 | 330.17 | 20.16 | 330.17 | 20.10 |
December | 497.00 | 19.78 | 477.00 | 19.75 | 477.00 | 19.75 |
Annual Sum or Average | 4832.33 | 20.81 | 3264.00 | 20.85 | 2468.67 | 20.63 |
Minimum of Months | 124.00 | 19.77 | 53.33 | 19.75 | 2.00 | 19.75 |
Maximum of Months | 508.33 | 22.86 | 494.17 | 23.77 | 494.17 | 23.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 494.17 | 19.78 | 494.17 | 19.77 |
February | 454.00 | 19.84 | 432.17 | 19.81 | 432.17 | 19.80 |
March | 498.67 | 20.51 | 288.17 | 20.33 | 278.50 | 20.21 |
April | 445.00 | 21.16 | 122.67 | 20.89 | 118.50 | 20.68 |
May | 335.83 | 22.00 | 126.67 | 22.49 | 17.33 | 22.42 |
June | 156.83 | 22.55 | 276.50 | 23.61 | 5.00 | 23.64 |
July | 92.83 | 23.78 | 388.17 | 24.21 | 33.00 | 24.31 |
August | 134.17 | 22.53 | 332.33 | 23.71 | 6.33 | 23.74 |
September | 268.83 | 22.04 | 173.83 | 22.84 | 18.50 | 22.87 |
October | 487.00 | 21.06 | 126.50 | 20.80 | 124.00 | 20.62 |
November | 489.00 | 20.38 | 307.83 | 20.21 | 307.83 | 20.14 |
December | 497.00 | 19.79 | 476.50 | 19.77 | 476.50 | 19.76 |
Annual Sum or Average | 4361.17 | 20.80 | 3545.50 | 21.08 | 2311.83 | 20.82 |
Minimum of Months | 92.83 | 19.79 | 122.67 | 19.77 | 5.00 | 19.76 |
Maximum of Months | 502.00 | 23.78 | 494.17 | 24.21 | 494.17 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.98 | 444.50 | 19.89 | 444.50 | 19.85 |
February | 450.83 | 19.98 | 378.17 | 19.85 | 378.17 | 19.79 |
March | 482.17 | 20.82 | 252.33 | 20.60 | 240.50 | 20.44 |
April | 423.50 | 21.09 | 155.17 | 20.99 | 130.33 | 20.79 |
May | 372.00 | 21.89 | 108.00 | 22.24 | 26.50 | 22.14 |
June | 215.17 | 22.34 | 220.50 | 23.21 | 7.00 | 23.21 |
July | 128.83 | 23.00 | 337.83 | 23.92 | 26.00 | 23.99 |
August | 164.00 | 22.47 | 301.50 | 23.59 | 8.33 | 23.63 |
September | 274.00 | 22.10 | 192.50 | 22.97 | 18.00 | 23.01 |
October | 429.33 | 21.14 | 151.67 | 21.13 | 106.33 | 20.92 |
November | 476.67 | 20.64 | 254.00 | 20.40 | 253.67 | 20.29 |
December | 497.00 | 19.96 | 443.00 | 19.88 | 443.00 | 19.85 |
Annual Sum or Average | 4415.50 | 20.95 | 3239.17 | 21.17 | 2082.33 | 20.91 |
Minimum of Months | 128.83 | 19.96 | 108.00 | 19.85 | 7.00 | 19.79 |
Maximum of Months | 502.00 | 23.00 | 444.50 | 23.92 | 444.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 491.00 | 19.78 | 491.00 | 19.77 |
February | 454.00 | 19.86 | 425.17 | 19.82 | 425.17 | 19.80 |
March | 504.67 | 20.59 | 288.50 | 20.39 | 283.00 | 20.27 |
April | 435.83 | 20.93 | 168.00 | 20.85 | 143.17 | 20.68 |
May | 384.67 | 21.79 | 118.17 | 22.19 | 26.83 | 22.10 |
June | 213.33 | 22.41 | 237.67 | 23.33 | 14.17 | 23.38 |
July | 138.00 | 23.03 | 336.67 | 23.92 | 31.67 | 24.03 |
August | 181.00 | 22.37 | 276.00 | 23.47 | 10.50 | 23.53 |
September | 336.33 | 21.93 | 131.33 | 22.53 | 17.83 | 22.58 |
October | 476.17 | 20.86 | 153.67 | 20.66 | 141.67 | 20.49 |
November | 489.00 | 20.35 | 307.83 | 20.18 | 307.83 | 20.10 |
December | 497.00 | 19.79 | 471.50 | 19.75 | 471.50 | 19.74 |
Annual Sum or Average | 4612.00 | 20.80 | 3405.50 | 21.00 | 2364.33 | 20.77 |
Minimum of Months | 138.00 | 19.79 | 118.17 | 19.75 | 10.50 | 19.74 |
Maximum of Months | 504.67 | 23.03 | 491.00 | 23.92 | 491.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.98 | 494.50 | 19.97 | 494.50 | 19.97 |
February | 454.00 | 20.04 | 454.00 | 20.04 | 454.00 | 20.04 |
March | 514.00 | 20.54 | 381.00 | 20.44 | 381.00 | 20.39 |
April | 485.00 | 20.84 | 189.83 | 20.69 | 189.83 | 20.61 |
May | 506.67 | 21.68 | 30.00 | 21.61 | 30.00 | 21.55 |
June | 326.50 | 22.72 | 116.83 | 23.07 | 9.17 | 23.10 |
July | 107.67 | 23.19 | 318.17 | 23.90 | 18.33 | 23.93 |
August | 137.33 | 22.90 | 269.67 | 23.70 | 7.17 | 23.71 |
September | 346.50 | 22.60 | 89.00 | 22.92 | 10.00 | 22.97 |
October | 502.00 | 21.53 | 50.17 | 21.44 | 50.17 | 21.36 |
November | 489.00 | 20.83 | 197.67 | 20.70 | 197.67 | 20.63 |
December | 497.00 | 20.16 | 462.33 | 20.13 | 462.33 | 20.12 |
Annual Sum or Average | 4867.67 | 21.09 | 3053.17 | 21.13 | 2304.17 | 20.93 |
Minimum of Months | 107.67 | 19.98 | 30.00 | 19.97 | 7.17 | 19.97 |
Maximum of Months | 514.00 | 23.19 | 494.50 | 23.90 | 494.50 | 23.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 494.50 | 20.03 | 494.50 | 20.03 |
February | 454.00 | 20.09 | 450.33 | 20.08 | 450.33 | 20.08 |
March | 514.00 | 20.70 | 318.17 | 20.54 | 318.17 | 20.47 |
April | 476.17 | 21.31 | 121.50 | 21.07 | 121.50 | 20.92 |
May | 405.50 | 22.10 | 44.67 | 22.25 | 9.67 | 22.20 |
June | 164.00 | 22.93 | 246.00 | 23.75 | 9.00 | 23.80 |
July | 44.50 | 24.55 | 427.83 | 24.34 | 25.33 | 24.41 |
August | 74.50 | 23.10 | 388.67 | 24.06 | 8.50 | 24.09 |
September | 194.50 | 22.69 | 221.50 | 23.54 | 10.17 | 23.59 |
October | 464.33 | 21.86 | 35.67 | 21.82 | 26.67 | 21.75 |
November | 489.00 | 20.96 | 163.33 | 20.82 | 163.33 | 20.73 |
December | 497.00 | 20.19 | 461.67 | 20.16 | 461.67 | 20.15 |
Annual Sum or Average | 4279.50 | 21.11 | 3373.83 | 21.40 | 2098.83 | 21.16 |
Minimum of Months | 44.50 | 20.04 | 35.67 | 20.03 | 8.50 | 20.03 |
Maximum of Months | 514.00 | 24.55 | 494.50 | 24.34 | 494.50 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.52 | 470.00 | 19.46 | 470.00 | 19.43 |
February | 454.00 | 19.48 | 421.67 | 19.43 | 421.67 | 19.41 |
March | 503.00 | 20.53 | 273.67 | 20.33 | 266.17 | 20.21 |
April | 474.67 | 21.02 | 142.33 | 20.80 | 138.83 | 20.64 |
May | 455.17 | 21.72 | 41.50 | 21.76 | 23.33 | 21.68 |
June | 289.17 | 22.53 | 158.83 | 23.11 | 21.33 | 23.15 |
July | 114.00 | 23.23 | 373.00 | 24.00 | 47.83 | 24.03 |
August | 118.17 | 22.74 | 360.17 | 23.87 | 24.67 | 23.89 |
September | 191.67 | 22.59 | 231.33 | 23.57 | 16.50 | 23.63 |
October | 411.00 | 21.68 | 75.33 | 21.85 | 27.50 | 21.74 |
November | 479.00 | 21.04 | 147.50 | 20.82 | 147.50 | 20.68 |
December | 497.00 | 19.82 | 442.67 | 19.73 | 442.67 | 19.70 |
Annual Sum or Average | 4488.83 | 20.91 | 3138.00 | 21.11 | 2048.00 | 20.85 |
Minimum of Months | 114.00 | 19.48 | 41.50 | 19.43 | 16.50 | 19.41 |
Maximum of Months | 503.00 | 23.23 | 470.00 | 24.00 | 470.00 | 24.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.00 | 494.00 | 19.99 | 494.00 | 19.99 |
February | 454.00 | 20.07 | 442.50 | 20.05 | 442.50 | 20.05 |
March | 514.00 | 20.71 | 313.17 | 20.56 | 313.17 | 20.49 |
April | 471.17 | 21.13 | 136.50 | 20.93 | 136.50 | 20.80 |
May | 431.00 | 21.93 | 53.00 | 22.13 | 11.00 | 22.09 |
June | 196.00 | 22.84 | 231.83 | 23.62 | 10.17 | 23.66 |
July | 69.83 | 23.74 | 392.50 | 24.25 | 26.00 | 24.32 |
August | 95.67 | 23.07 | 371.00 | 24.02 | 12.00 | 24.06 |
September | 250.00 | 22.68 | 168.33 | 23.33 | 10.33 | 23.39 |
October | 472.50 | 21.65 | 47.33 | 21.62 | 36.33 | 21.54 |
November | 489.00 | 20.91 | 182.50 | 20.77 | 182.50 | 20.69 |
December | 497.00 | 20.17 | 459.83 | 20.14 | 459.83 | 20.13 |
Annual Sum or Average | 4442.17 | 21.09 | 3292.50 | 21.34 | 2134.33 | 21.11 |
Minimum of Months | 69.83 | 20.00 | 47.33 | 19.99 | 10.17 | 19.99 |
Maximum of Months | 514.00 | 23.74 | 494.00 | 24.25 | 494.00 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.95 | 482.50 | 19.93 | 482.50 | 19.92 |
February | 454.00 | 20.02 | 429.17 | 19.99 | 429.17 | 19.98 |
March | 502.50 | 20.71 | 285.83 | 20.54 | 282.67 | 20.45 |
April | 484.17 | 21.31 | 91.50 | 21.11 | 91.50 | 20.96 |
May | 415.67 | 22.36 | 38.17 | 22.46 | 5.17 | 22.44 |
June | 168.00 | 22.94 | 224.33 | 23.60 | 4.17 | 23.62 |
July | 46.33 | 23.88 | 403.00 | 24.14 | 20.00 | 24.18 |
August | 101.83 | 22.81 | 337.17 | 23.82 | 3.00 | 23.82 |
September | 316.33 | 22.56 | 111.00 | 22.97 | 12.67 | 23.04 |
October | 496.50 | 21.41 | 87.00 | 21.23 | 87.00 | 21.10 |
November | 489.00 | 20.71 | 216.50 | 20.54 | 216.50 | 20.45 |
December | 497.00 | 20.02 | 444.33 | 19.97 | 444.33 | 19.95 |
Annual Sum or Average | 4473.33 | 21.07 | 3150.50 | 21.23 | 2078.67 | 20.99 |
Minimum of Months | 46.33 | 19.95 | 38.17 | 19.93 | 3.00 | 19.92 |
Maximum of Months | 502.50 | 23.88 | 482.50 | 24.14 | 482.50 | 24.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.81 | 413.17 | 19.79 | 413.17 | 19.78 |
February | 385.00 | 19.89 | 353.50 | 19.84 | 353.50 | 19.83 |
March | 420.17 | 20.77 | 214.17 | 20.58 | 206.83 | 20.46 |
April | 367.33 | 21.37 | 78.50 | 21.25 | 65.50 | 21.07 |
May | 289.67 | 22.25 | 90.33 | 22.77 | 3.67 | 22.76 |
June | 126.17 | 22.80 | 231.33 | 23.76 | 6.00 | 23.80 |
July | 61.50 | 24.41 | 345.17 | 24.36 | 31.67 | 24.48 |
August | 98.33 | 22.77 | 285.67 | 23.88 | 6.83 | 23.91 |
September | 226.50 | 22.44 | 144.50 | 23.17 | 12.50 | 23.25 |
October | 396.33 | 21.47 | 70.50 | 21.33 | 63.83 | 21.19 |
November | 417.00 | 20.75 | 183.17 | 20.56 | 183.17 | 20.45 |
December | 422.00 | 19.87 | 385.67 | 19.82 | 385.67 | 19.80 |
Annual Sum or Average | 3637.00 | 21.00 | 2795.67 | 21.29 | 1732.33 | 21.03 |
Minimum of Months | 61.50 | 19.81 | 70.50 | 19.79 | 3.67 | 19.78 |
Maximum of Months | 427.00 | 24.41 | 413.17 | 24.36 | 413.17 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.50 | 20.28 | 403.17 | 20.12 | 403.17 | 20.07 |
February | 449.67 | 20.31 | 342.67 | 20.12 | 342.67 | 20.05 |
March | 466.67 | 21.26 | 189.33 | 21.06 | 172.00 | 20.88 |
April | 404.00 | 21.52 | 90.50 | 21.48 | 68.50 | 21.31 |
May | 323.67 | 22.36 | 99.17 | 22.79 | 6.50 | 22.76 |
June | 150.33 | 22.85 | 259.83 | 23.70 | 5.17 | 23.72 |
July | 63.83 | 23.95 | 411.67 | 24.26 | 27.17 | 24.32 |
August | 93.67 | 23.09 | 372.33 | 24.03 | 10.00 | 24.07 |
September | 205.83 | 22.73 | 232.67 | 23.59 | 15.50 | 23.67 |
October | 388.17 | 21.72 | 108.67 | 21.93 | 43.17 | 21.78 |
November | 461.83 | 21.13 | 159.50 | 20.93 | 154.00 | 20.78 |
December | 495.33 | 20.30 | 387.33 | 20.17 | 387.33 | 20.11 |
Annual Sum or Average | 4001.50 | 21.28 | 3056.83 | 21.63 | 1635.17 | 21.36 |
Minimum of Months | 63.83 | 20.28 | 90.50 | 20.12 | 5.17 | 20.05 |
Maximum of Months | 498.50 | 23.95 | 411.67 | 24.26 | 403.17 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 476.00 | 19.95 | 476.00 | 19.94 |
February | 454.00 | 20.05 | 407.83 | 19.99 | 407.83 | 19.97 |
March | 502.50 | 20.89 | 239.33 | 20.69 | 234.33 | 20.57 |
April | 433.67 | 21.25 | 107.17 | 21.22 | 83.17 | 21.06 |
May | 364.67 | 22.12 | 94.83 | 22.56 | 5.50 | 22.53 |
June | 174.17 | 22.74 | 266.00 | 23.63 | 10.67 | 23.69 |
July | 93.17 | 23.58 | 378.83 | 24.15 | 30.00 | 24.25 |
August | 127.00 | 22.72 | 331.50 | 23.81 | 9.83 | 23.85 |
September | 299.33 | 22.35 | 150.33 | 22.99 | 13.00 | 23.07 |
October | 470.00 | 21.33 | 91.33 | 21.24 | 76.50 | 21.11 |
November | 489.00 | 20.75 | 203.83 | 20.57 | 203.83 | 20.47 |
December | 497.00 | 20.03 | 439.50 | 19.97 | 439.50 | 19.94 |
Annual Sum or Average | 4406.50 | 21.05 | 3186.50 | 21.32 | 1990.17 | 21.08 |
Minimum of Months | 93.17 | 19.97 | 91.33 | 19.95 | 5.50 | 19.94 |
Maximum of Months | 502.50 | 23.58 | 476.00 | 24.15 | 476.00 | 24.25 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35818 | 18.66074 | -0.2660 | 7.98050 |
February | 454.00000 | 22.57105 | 18.09920 | -0.2111 | 6.59940 |
March | 514.00000 | 23.51859 | 24.57000 | 0.08654 | 6.00689 |
April | 485.00000 | 23.99760 | 27.90746 | 0.24214 | 6.57511 |
May | 508.00000 | 24.37627 | 32.46576 | -0.4739 | 10.36249 |
June | 496.00000 | 24.42727 | 43.49032 | -0.3184 | 7.77032 |
July | 497.00000 | 24.54052 | 51.31774 | -0.2075 | 6.63005 |
August | 514.00000 | 24.45389 | 48.82388 | -0.2475 | 6.91912 |
September | 485.00000 | 24.45870 | 43.43869 | -0.3179 | 7.86550 |
October | 502.00000 | 24.26326 | 33.09573 | 0.35872 | 7.98174 |
November | 489.00000 | 23.92368 | 27.36482 | 0.20896 | 6.22646 |
December | 497.00000 | 22.94863 | 21.37762 | -0.0935 | 5.94784 |
Annual Sum or Average | 5943.00000 | 23.82807 | 32.66043 | -0.1035 | 7.24735 |
Minimum of Months | 454.00000 | 22.35818 | 18.09920 | -0.4739 | 5.94784 |
Maximum of Months | 514.00000 | 24.54052 | 51.31774 | 0.35872 | 10.36249 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.00178 | 19.92992 | -0.5854 | 13.70350 |
February | 454.00000 | 21.17688 | 19.40482 | -0.5423 | 12.30779 |
March | 514.00000 | 22.23455 | 26.66454 | -0.2107 | 7.74433 |
April | 485.00000 | 22.96043 | 30.53550 | -0.0005 | 6.01140 |
May | 508.00000 | 23.79888 | 34.21495 | -0.6761 | 15.46331 |
June | 496.00000 | 24.10850 | 44.44999 | -0.4454 | 9.66883 |
July | 497.00000 | 24.26703 | 51.92657 | -0.3227 | 7.51281 |
August | 514.00000 | 24.23727 | 49.51239 | -0.3534 | 7.92010 |
September | 485.00000 | 24.01119 | 44.87594 | -0.5012 | 11.05316 |
October | 502.00000 | 23.16709 | 36.21530 | 0.09093 | 6.09455 |
November | 489.00000 | 22.40261 | 30.85476 | -0.1481 | 6.39014 |
December | 497.00000 | 21.26594 | 23.27981 | -0.4910 | 11.26927 |
Annual Sum or Average | 5943.00000 | 22.89874 | 34.43011 | -0.3481 | 9.58519 |
Minimum of Months | 454.00000 | 21.00178 | 19.40482 | -0.6761 | 6.01140 |
Maximum of Months | 514.00000 | 24.26703 | 51.92657 | 0.09093 | 15.46331 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32644 | 20.16293 | -0.7881 | 20.16199 |
February | 454.00000 | 20.45557 | 19.98637 | -0.7486 | 18.89333 |
March | 514.00000 | 21.39912 | 27.42817 | -0.4262 | 11.58561 |
April | 485.00000 | 22.12218 | 31.41665 | -0.2004 | 7.70237 |
May | 508.00000 | 23.34003 | 34.70811 | -0.8224 | 21.15595 |
June | 496.00000 | 23.89755 | 44.16894 | -0.5063 | 11.39799 |
July | 497.00000 | 24.15685 | 50.85721 | -0.3515 | 8.11188 |
August | 514.00000 | 24.03863 | 48.89110 | -0.4193 | 9.27261 |
September | 485.00000 | 23.51246 | 45.35776 | -0.6760 | 16.45937 |
October | 502.00000 | 22.06010 | 38.14104 | -0.1761 | 7.66648 |
November | 489.00000 | 21.21113 | 32.46473 | -0.4483 | 10.62707 |
December | 497.00000 | 20.41494 | 24.01336 | -0.7338 | 18.36364 |
Annual Sum or Average | 5943.00000 | 22.25930 | 34.90351 | -0.5235 | 13.41791 |
Minimum of Months | 454.00000 | 20.32644 | 19.98637 | -0.8224 | 7.66648 |
Maximum of Months | 514.00000 | 24.15685 | 50.85721 | -0.1761 | 21.15595 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76847 | 19.76385 | -1.0076 | 28.83874 |
February | 454.00000 | 19.83426 | 19.88229 | -0.9730 | 27.48314 |
March | 514.00000 | 20.45997 | 28.10664 | -0.6819 | 18.12108 |
April | 485.00000 | 20.90802 | 32.56577 | -0.4799 | 11.89583 |
May | 508.00000 | 22.08275 | 37.49508 | -1.1711 | 36.06302 |
June | 496.00000 | 23.14554 | 46.44170 | -0.6812 | 17.63697 |
July | 497.00000 | 23.66711 | 53.69187 | -0.4317 | 10.62627 |
August | 514.00000 | 23.32372 | 51.41439 | -0.5858 | 14.61327 |
September | 485.00000 | 22.32409 | 48.82589 | -1.0076 | 29.68535 |
October | 502.00000 | 20.82275 | 39.62694 | -0.4636 | 11.71726 |
November | 489.00000 | 20.29978 | 32.50473 | -0.7028 | 17.45712 |
December | 497.00000 | 19.77927 | 23.96423 | -0.9638 | 27.28009 |
Annual Sum or Average | 5943.00000 | 21.38173 | 36.30523 | -0.7611 | 20.91077 |
Minimum of Months | 454.00000 | 19.76847 | 19.76385 | -1.1711 | 10.62627 |
Maximum of Months | 514.00000 | 23.66711 | 53.69187 | -0.4317 | 36.06302 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78651 | 19.99253 | -0.9862 | 28.01674 |
February | 454.00000 | 19.84391 | 20.14028 | -0.9459 | 26.58755 |
March | 514.00000 | 20.60717 | 28.16056 | -0.6114 | 16.48519 |
April | 485.00000 | 21.41391 | 32.03117 | -0.3297 | 10.73499 |
May | 508.00000 | 22.72457 | 36.39945 | -0.9213 | 27.37725 |
June | 496.00000 | 23.58524 | 45.41100 | -0.4837 | 13.21234 |
July | 497.00000 | 24.00951 | 52.61259 | -0.2572 | 8.65631 |
August | 514.00000 | 23.66752 | 50.43621 | -0.4185 | 11.54383 |
September | 485.00000 | 22.90925 | 47.48107 | -0.7796 | 22.50463 |
October | 502.00000 | 21.14173 | 39.20996 | -0.3685 | 10.52926 |
November | 489.00000 | 20.37861 | 32.67998 | -0.6711 | 16.54972 |
December | 497.00000 | 19.79191 | 24.20493 | -0.9522 | 26.81078 |
Annual Sum or Average | 5943.00000 | 21.67017 | 35.84033 | -0.6418 | 18.19450 |
Minimum of Months | 454.00000 | 19.78651 | 19.99253 | -0.9862 | 8.65631 |
Maximum of Months | 514.00000 | 24.00951 | 52.61259 | -0.2572 | 28.01674 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.98412 | 19.47865 | -0.9023 | 25.30340 |
February | 454.00000 | 20.00934 | 19.68047 | -0.8729 | 24.73055 |
March | 514.00000 | 21.00994 | 27.38859 | -0.4975 | 14.55174 |
April | 485.00000 | 21.49684 | 31.57574 | -0.3160 | 11.03293 |
May | 508.00000 | 22.49775 | 36.66361 | -1.0122 | 31.02194 |
June | 496.00000 | 23.26671 | 46.09821 | -0.6187 | 16.82706 |
July | 497.00000 | 23.77482 | 53.25464 | -0.3641 | 10.55229 |
August | 514.00000 | 23.54812 | 50.60887 | -0.4640 | 13.04679 |
September | 485.00000 | 22.96874 | 47.03181 | -0.7380 | 22.15800 |
October | 502.00000 | 21.57066 | 37.99586 | -0.2499 | 10.43474 |
November | 489.00000 | 20.72152 | 31.76213 | -0.5686 | 14.75413 |
December | 497.00000 | 19.95895 | 23.70621 | -0.8804 | 24.24178 |
Annual Sum or Average | 5943.00000 | 21.74845 | 35.54998 | -0.6222 | 18.18345 |
Minimum of Months | 454.00000 | 19.95895 | 19.47865 | -1.0122 | 10.43474 |
Maximum of Months | 514.00000 | 23.77482 | 53.25464 | -0.2499 | 31.02194 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.79157 | 19.85678 | -0.9942 | 28.34133 |
February | 454.00000 | 19.85889 | 19.98849 | -0.9519 | 26.87775 |
March | 514.00000 | 20.65045 | 28.04555 | -0.6102 | 16.48804 |
April | 485.00000 | 21.27674 | 32.08803 | -0.3716 | 11.59996 |
May | 508.00000 | 22.39056 | 37.00903 | -1.0261 | 32.18176 |
June | 496.00000 | 23.30651 | 46.07375 | -0.5639 | 16.44179 |
July | 497.00000 | 23.74816 | 53.44604 | -0.3441 | 10.83843 |
August | 514.00000 | 23.41976 | 51.15793 | -0.4931 | 14.08949 |
September | 485.00000 | 22.54747 | 48.35596 | -0.8934 | 26.89860 |
October | 502.00000 | 21.01179 | 39.37485 | -0.4035 | 11.39201 |
November | 489.00000 | 20.35031 | 32.61096 | -0.6808 | 16.98011 |
December | 497.00000 | 19.78592 | 24.09682 | -0.9556 | 26.98220 |
Annual Sum or Average | 5943.00000 | 21.52587 | 36.12211 | -0.6889 | 19.87900 |
Minimum of Months | 454.00000 | 19.78592 | 19.85678 | -1.0261 | 10.83843 |
Maximum of Months | 514.00000 | 23.74816 | 53.44604 | -0.3441 | 32.18176 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.98141 | 19.97984 | -0.9420 | 25.52653 |
February | 454.00000 | 20.03988 | 20.19517 | -0.9194 | 24.56547 |
March | 514.00000 | 20.53949 | 28.67141 | -0.6883 | 16.99430 |
April | 485.00000 | 20.83554 | 33.06109 | -0.5316 | 11.80823 |
May | 508.00000 | 21.68682 | 39.04555 | -1.3650 | 44.34170 |
June | 496.00000 | 23.09900 | 47.96688 | -0.7640 | 19.18301 |
July | 497.00000 | 23.77542 | 55.20325 | -0.4567 | 10.23068 |
August | 514.00000 | 23.65043 | 52.02159 | -0.5196 | 11.67359 |
September | 485.00000 | 22.93936 | 48.31334 | -0.8213 | 21.31778 |
October | 502.00000 | 21.53081 | 38.38313 | -0.2699 | 7.63640 |
November | 489.00000 | 20.82986 | 31.72603 | -0.5263 | 11.46743 |
December | 497.00000 | 20.16066 | 23.91418 | -0.8327 | 21.26906 |
Annual Sum or Average | 5943.00000 | 21.60150 | 36.66023 | -0.7191 | 18.82975 |
Minimum of Months | 454.00000 | 19.98141 | 19.97984 | -1.3650 | 7.63640 |
Maximum of Months | 514.00000 | 23.77542 | 55.20325 | -0.2699 | 44.34170 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03642 | 20.20206 | -0.9151 | 24.41224 |
February | 454.00000 | 20.08742 | 20.45364 | -0.8871 | 23.33290 |
March | 514.00000 | 20.69697 | 28.72973 | -0.6117 | 14.83309 |
April | 485.00000 | 21.36263 | 32.48735 | -0.3671 | 9.70832 |
May | 508.00000 | 22.51249 | 37.56359 | -1.0545 | 31.23628 |
June | 496.00000 | 23.69658 | 46.39258 | -0.5123 | 12.77144 |
July | 497.00000 | 24.16285 | 53.77628 | -0.2594 | 7.69237 |
August | 514.00000 | 23.97329 | 50.92663 | -0.3473 | 8.97507 |
September | 485.00000 | 23.52137 | 46.80398 | -0.5842 | 14.82380 |
October | 502.00000 | 22.01642 | 37.62629 | -0.1397 | 7.08045 |
November | 489.00000 | 20.96463 | 31.81369 | -0.4824 | 10.72408 |
December | 497.00000 | 20.19401 | 24.16367 | -0.8191 | 20.69841 |
Annual Sum or Average | 5943.00000 | 21.94958 | 36.02583 | -0.5802 | 15.49637 |
Minimum of Months | 454.00000 | 20.03642 | 20.20206 | -1.0545 | 7.08045 |
Maximum of Months | 514.00000 | 24.16285 | 53.77628 | -0.1397 | 31.23628 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.51646 | 19.10600 | -0.9625 | 27.02541 |
February | 454.00000 | 19.48488 | 19.54312 | -0.9558 | 26.58568 |
March | 514.00000 | 20.59996 | 27.41674 | -0.5779 | 14.67525 |
April | 485.00000 | 21.10557 | 31.92556 | -0.4125 | 10.59449 |
May | 508.00000 | 21.99101 | 37.88647 | -1.2234 | 38.51705 |
June | 496.00000 | 23.13726 | 48.05544 | -0.7146 | 18.66257 |
July | 497.00000 | 23.90723 | 55.55064 | -0.3685 | 9.60053 |
August | 514.00000 | 23.82386 | 51.59957 | -0.3957 | 10.36989 |
September | 485.00000 | 23.52853 | 46.61348 | -0.5480 | 14.68772 |
October | 502.00000 | 22.14633 | 36.38008 | -0.0717 | 7.63551 |
November | 489.00000 | 21.10337 | 30.34176 | -0.4122 | 10.23356 |
December | 497.00000 | 19.82060 | 23.18197 | -0.8473 | 22.35800 |
Annual Sum or Average | 5943.00000 | 21.69646 | 35.75323 | -0.6228 | 17.55269 |
Minimum of Months | 454.00000 | 19.48488 | 19.10600 | -1.2234 | 7.63551 |
Maximum of Months | 514.00000 | 23.90723 | 55.55064 | -0.0717 | 38.51705 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.00306 | 20.15381 | -0.9306 | 25.12224 |
February | 454.00000 | 20.06693 | 20.38645 | -0.9001 | 23.91276 |
March | 514.00000 | 20.70973 | 28.66896 | -0.6142 | 14.87096 |
April | 485.00000 | 21.21929 | 32.59939 | -0.4098 | 10.34208 |
May | 508.00000 | 22.29393 | 37.95200 | -1.1264 | 34.61616 |
June | 496.00000 | 23.59648 | 46.62236 | -0.5387 | 13.76789 |
July | 497.00000 | 24.06885 | 54.19616 | -0.2984 | 8.41803 |
August | 514.00000 | 23.92259 | 51.14785 | -0.3660 | 9.53267 |
September | 485.00000 | 23.32754 | 47.36401 | -0.6520 | 16.73944 |
October | 502.00000 | 21.78863 | 38.00113 | -0.1936 | 7.42259 |
November | 489.00000 | 20.91328 | 31.82303 | -0.4969 | 10.97072 |
December | 497.00000 | 20.17372 | 24.11551 | -0.8254 | 20.98229 |
Annual Sum or Average | 5943.00000 | 21.85434 | 36.20124 | -0.6113 | 16.36588 |
Minimum of Months | 454.00000 | 20.00306 | 20.15381 | -1.1264 | 7.42259 |
Maximum of Months | 514.00000 | 24.06885 | 54.19616 | -0.1936 | 34.61616 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95192 | 19.57409 | -0.9171 | 24.90152 |
February | 454.00000 | 20.01989 | 19.74867 | -0.8829 | 23.57463 |
March | 514.00000 | 20.78068 | 27.93600 | -0.5712 | 14.65379 |
April | 485.00000 | 21.31640 | 32.19766 | -0.3635 | 9.34434 |
May | 508.00000 | 22.64174 | 36.76972 | -1.0002 | 28.24787 |
June | 496.00000 | 23.62524 | 46.06196 | -0.5491 | 12.91599 |
July | 497.00000 | 24.01003 | 53.83609 | -0.3418 | 8.18401 |
August | 514.00000 | 23.78819 | 51.18365 | -0.4518 | 10.39375 |
September | 485.00000 | 23.01125 | 47.89776 | -0.7880 | 20.72774 |
October | 502.00000 | 21.43534 | 38.63248 | -0.2933 | 8.42465 |
November | 489.00000 | 20.71095 | 32.10720 | -0.5553 | 12.54483 |
December | 497.00000 | 20.02073 | 23.61780 | -0.8541 | 22.60700 |
Annual Sum or Average | 5943.00000 | 21.79098 | 35.91118 | -0.6292 | 16.33616 |
Minimum of Months | 454.00000 | 19.95192 | 19.57409 | -1.0002 | 8.18401 |
Maximum of Months | 514.00000 | 24.01003 | 53.83609 | -0.2933 | 28.24787 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.80969 | 19.50881 | -0.9386 | 25.82757 |
February | 385.00000 | 19.89460 | 19.73601 | -0.8947 | 24.19443 |
March | 433.00000 | 20.85224 | 27.75726 | -0.5276 | 13.62342 |
April | 410.00000 | 21.68172 | 31.54502 | -0.2512 | 9.12793 |
May | 430.00000 | 22.91980 | 36.03415 | -0.8602 | 24.59232 |
June | 418.00000 | 23.69600 | 45.60240 | -0.4629 | 12.16565 |
July | 422.00000 | 24.11299 | 53.20091 | -0.2456 | 8.22196 |
August | 433.00000 | 23.79786 | 50.68517 | -0.3908 | 10.40051 |
September | 410.00000 | 23.15905 | 47.37184 | -0.6907 | 18.77498 |
October | 427.00000 | 21.64290 | 38.09364 | -0.2295 | 8.20855 |
November | 417.00000 | 20.75245 | 31.73027 | -0.5414 | 12.46105 |
December | 422.00000 | 19.87023 | 23.53345 | -0.8850 | 23.78893 |
Annual Sum or Average | 5034.00000 | 21.86194 | 35.49583 | -0.5748 | 15.90299 |
Minimum of Months | 385.00000 | 19.80969 | 19.50881 | -0.9386 | 8.20855 |
Maximum of Months | 433.00000 | 24.11299 | 53.20091 | -0.2295 | 25.82757 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.30764 | 19.19135 | -0.7840 | 20.99148 |
February | 454.00000 | 20.34149 | 19.39819 | -0.7548 | 20.21809 |
March | 514.00000 | 21.50462 | 27.01390 | -0.3543 | 11.28128 |
April | 485.00000 | 21.98773 | 31.01060 | -0.1845 | 8.82243 |
May | 508.00000 | 23.01800 | 35.92587 | -0.8514 | 23.83415 |
June | 496.00000 | 23.69794 | 45.74804 | -0.4991 | 12.48699 |
July | 497.00000 | 24.10523 | 53.38202 | -0.2771 | 8.09913 |
August | 514.00000 | 23.94682 | 50.47066 | -0.3470 | 9.39864 |
September | 485.00000 | 23.52884 | 46.27645 | -0.5523 | 15.16243 |
October | 502.00000 | 22.28062 | 36.75692 | -0.0628 | 8.26614 |
November | 489.00000 | 21.28730 | 31.11466 | -0.3934 | 10.59993 |
December | 497.00000 | 20.31488 | 23.24986 | -0.7484 | 19.24135 |
Annual Sum or Average | 5943.00000 | 22.20857 | 35.07430 | -0.4825 | 13.99989 |
Minimum of Months | 454.00000 | 20.30764 | 19.19135 | -0.8514 | 8.09913 |
Maximum of Months | 514.00000 | 24.10523 | 53.38202 | -0.0628 | 23.83415 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97497 | 19.47593 | -0.9054 | 24.52810 |
February | 454.00000 | 20.05287 | 19.67182 | -0.8621 | 23.02827 |
March | 514.00000 | 20.95072 | 27.76440 | -0.5049 | 13.18480 |
April | 485.00000 | 21.57874 | 31.70673 | -0.2761 | 9.41356 |
May | 508.00000 | 22.71083 | 36.54058 | -0.9174 | 26.92774 |
June | 496.00000 | 23.57523 | 46.03045 | -0.4856 | 13.25491 |
July | 497.00000 | 23.95300 | 53.86649 | -0.2890 | 8.92672 |
August | 514.00000 | 23.71250 | 51.27826 | -0.4029 | 10.92450 |
September | 485.00000 | 22.97185 | 47.92782 | -0.7426 | 20.54094 |
October | 502.00000 | 21.49856 | 38.46700 | -0.2585 | 8.45933 |
November | 489.00000 | 20.74821 | 32.03744 | -0.5383 | 12.29229 |
December | 497.00000 | 20.02648 | 23.57887 | -0.8482 | 22.39060 |
Annual Sum or Average | 5943.00000 | 21.82765 | 35.81010 | -0.5842 | 16.11375 |
Minimum of Months | 454.00000 | 19.97497 | 19.47593 | -0.9174 | 8.45933 |
Maximum of Months | 514.00000 | 23.95300 | 53.86649 | -0.2585 | 26.92774 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.131054E+12 | 0.00 | 559.11 | 306226.56 | 14-JAN-06:11 | 0.00 | 37.32 | 53.95 | 0.61 | 0.00 | 0.10 | 0.61 | 14-JAN-06:11 |
February | 0.115482E+12 | 0.00 | 511.74 | 332547.60 | 23-FEB-06:11 | 0.00 | 37.18 | 54.28 | 0.60 | 0.00 | 0.10 | 0.67 | 23-FEB-06:11 |
March | 0.569956E+11 | 0.00 | 432.96 | 329315.61 | 10-MAR-06:11 | 0.00 | 32.14 | 47.41 | 0.23 | 0.00 | 0.04 | 0.66 | 10-MAR-06:11 |
April | 0.190562E+11 | 0.00 | 325.64 | 327645.64 | 18-APR-05:11 | 0.00 | 28.22 | 41.10 | 0.07 | 0.00 | 0.01 | 0.66 | 18-APR-05:11 |
May | 0.359226E+10 | 0.00 | 162.45 | 286042.22 | 01-MAY-06:02 | 0.00 | 34.10 | 39.69 | 0.01 | 0.00 | 0.00 | 0.57 | 01-MAY-06:02 |
June | 0.386551E+09 | 0.00 | 78.41 | 46637.19 | 14-JUN-06:03 | 0.00 | 37.66 | 40.18 | 0.00 | 0.00 | 0.00 | 0.09 | 14-JUN-06:03 |
July | 50170836.25 | 0.00 | 120.51 | 12531.56 | 03-JUL-06:07 | 0.00 | 32.07 | 36.65 | 0.00 | 0.00 | 0.00 | 0.03 | 03-JUL-06:07 |
August | 0.135804E+09 | 0.00 | 80.09 | 33773.25 | 31-AUG-06:03 | 0.00 | 31.17 | 34.24 | 0.00 | 0.00 | 0.00 | 0.07 | 31-AUG-06:03 |
September | 0.126682E+10 | 0.00 | 88.62 | 147649.87 | 30-SEP-06:03 | 0.00 | 32.15 | 35.62 | 0.00 | 0.00 | 0.00 | 0.30 | 30-SEP-06:03 |
October | 0.125313E+11 | 0.00 | 285.71 | 293158.02 | 17-OCT-06:01 | 0.00 | 27.30 | 38.78 | 0.04 | 0.00 | 0.01 | 0.59 | 17-OCT-06:01 |
November | 0.342228E+11 | 0.00 | 368.54 | 361812.98 | 13-NOV-06:11 | 0.00 | 28.48 | 43.71 | 0.12 | 0.00 | 0.03 | 0.72 | 13-NOV-06:11 |
December | 0.111064E+12 | 0.00 | 540.21 | 339317.96 | 02-DEC-06:11 | 0.00 | 35.65 | 52.74 | 0.49 | 0.00 | 0.08 | 0.68 | 02-DEC-06:11 |
Annual Sum or Average | 0.485837E+12 | 0.00 | 3553.99 | 0.00 | 32.76 | 43.14 | 0.18 | 0.00 | 0.03 | ||||
Minimum of Months | 50170836.25 | 0.00 | 78.41 | 12531.56 | 0.00 | 27.30 | 34.24 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.131054E+12 | 0.00 | 559.11 | 361812.98 | 0.00 | 37.66 | 54.28 | 0.61 | 0.00 | 0.10 | 0.72 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.261508E+10 | 0.634670E+09 | 35.33 | 0.227748E+10 | 0.337600E+09 | 0.00 | 0.98 | 15-MAR-14:10 | 0.00 | 01-MAR-00:10 | 37535.27 | 15-MAR-14:10 | 37535.27 | 15-MAR-14:10 | 10107.94 | 14-MAR-10:20 | 8823.71 | 15-MAR-14:10 | 0.00 |
April | 0.104518E+10 | 0.277591E+09 | 41.50 | 0.986610E+09 | 58573816.77 | 0.00 | 0.53 | 07-APR-14:10 | 0.00 | 01-APR-00:10 | 17902.33 | 07-APR-14:10 | 17902.33 | 07-APR-14:10 | 2240.07 | 08-APR-15:40 | 4527.49 | 07-APR-14:10 | 0.00 |
May | 0.101626E+11 | 0.251340E+10 | 192.78 | 0.936338E+10 | 0.799187E+09 | 0.00 | 1.00 | 10-MAY-14:05 | 0.00 | 01-MAY-00:10 | 43039.64 | 23-MAY-14:30 | 43039.64 | 23-MAY-14:30 | 11252.35 | 17-MAY-15:00 | 9808.57 | 10-MAY-15:00 | 0.00 |
June | 0.415866E+11 | 0.978881E+10 | 362.02 | 0.339940E+11 | 0.759261E+10 | 0.00 | 1.00 | 01-JUN-13:40 | 0.00 | 01-JUN-00:10 | 99139.95 | 27-JUN-05:12 | 69378.98 | 27-JUN-05:12 | 39832.04 | 29-JUN-05:12 | 22102.72 | 27-JUN-05:12 | 0.00 |
July | 0.688646E+11 | 0.160984E+11 | 408.43 | 0.557950E+11 | 0.130695E+11 | 0.00 | 1.00 | 02-JUL-16:41 | 0.00 | 01-JUL-00:10 | 128319.48 | 21-JUL-04:02 | 76331.41 | 19-JUL-05:12 | 78367.31 | 22-JUL-05:12 | 29172.31 | 21-JUL-04:02 | 0.00 |
August | 0.613694E+11 | 0.143799E+11 | 411.54 | 0.522851E+11 | 0.908433E+10 | 0.00 | 1.00 | 01-AUG-11:20 | 0.00 | 01-AUG-00:10 | 125202.97 | 14-AUG-05:12 | 76744.61 | 15-AUG-05:12 | 64312.23 | 08-AUG-05:12 | 27731.01 | 14-AUG-05:12 | 0.00 |
September | 0.290843E+11 | 0.683230E+10 | 306.77 | 0.241783E+11 | 0.490605E+10 | 0.00 | 1.00 | 08-SEP-09:10 | 0.00 | 01-SEP-00:10 | 73373.30 | 14-SEP-05:13 | 62174.96 | 21-SEP-15:30 | 41099.56 | 14-SEP-05:13 | 16367.38 | 14-SEP-05:13 | 0.00 |
October | 0.372744E+10 | 0.945755E+09 | 89.17 | 0.323528E+10 | 0.492158E+09 | 0.00 | 1.00 | 11-OCT-12:20 | 0.00 | 01-OCT-00:10 | 44747.52 | 11-OCT-16:00 | 44747.52 | 11-OCT-16:00 | 6636.38 | 12-OCT-15:00 | 9922.32 | 11-OCT-16:00 | 0.00 |
November | 0.686711E+09 | 0.182070E+09 | 21.00 | 0.534119E+09 | 0.152592E+09 | 0.00 | 0.46 | 16-NOV-17:00 | 0.00 | 01-NOV-00:10 | 15470.10 | 16-NOV-17:00 | 13006.89 | 16-NOV-17:00 | 3651.07 | 04-NOV-14:00 | 3977.70 | 16-NOV-17:00 | 0.00 |
December | 2599374.28 | 741046.01 | 0.67 | 1620621.46 | 978752.82 | 0.00 | 0.05 | 01-DEC-11:00 | 0.00 | 01-DEC-00:10 | 1574.29 | 01-DEC-11:00 | 980.18 | 01-DEC-11:00 | 594.11 | 01-DEC-11:00 | 447.47 | 01-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.219145E+12 | 0.516536E+11 | 1869.22 | 0.182651E+12 | 0.364936E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.688646E+11 | 0.160984E+11 | 411.54 | 0.557950E+11 | 0.130695E+11 | 0.00 | 1.00 | 0.00 | 128319.48 | 76744.61 | 78367.31 | 29172.31 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 185588.94 | 52867.93 | 0.04 | 183802.45 | 1786.49 | 0.00 | 0.04 | 01-FEB-07:05 | 0.00 | 01-FEB-00:10 | 1237.26 | 01-FEB-07:05 | 1225.35 | 01-FEB-07:05 | 11.91 | 01-FEB-07:05 | 352.45 | 01-FEB-07:05 | 0.00 |
March | 0.245167E+10 | 0.596291E+09 | 35.33 | 0.210811E+10 | 0.343562E+09 | 0.00 | 1.00 | 15-MAR-14:05 | 0.00 | 01-MAR-00:10 | 38717.33 | 15-MAR-14:05 | 38717.33 | 15-MAR-14:05 | 9768.96 | 14-MAR-10:25 | 9058.80 | 15-MAR-14:05 | 0.00 |
April | 0.953798E+09 | 0.254841E+09 | 42.51 | 0.890747E+09 | 63051336.48 | 0.00 | 0.52 | 08-APR-13:00 | 0.00 | 01-APR-00:10 | 17043.63 | 08-APR-13:00 | 16106.16 | 08-APR-13:00 | 2554.40 | 08-APR-14:00 | 4317.10 | 08-APR-13:00 | 0.00 |
May | 0.971151E+10 | 0.241009E+10 | 200.24 | 0.886512E+10 | 0.846389E+09 | 0.00 | 1.00 | 10-MAY-14:05 | 0.00 | 01-MAY-00:10 | 43677.66 | 23-MAY-14:30 | 43677.66 | 23-MAY-14:30 | 9503.08 | 17-MAY-14:03 | 9744.33 | 10-MAY-15:00 | 0.00 |
June | 0.398155E+11 | 0.942031E+10 | 373.01 | 0.323404E+11 | 0.747509E+10 | 0.00 | 1.00 | 01-JUN-13:00 | 0.00 | 01-JUN-00:10 | 81496.77 | 27-JUN-13:00 | 63106.23 | 12-JUN-14:05 | 35251.29 | 21-JUN-10:05 | 20916.44 | 27-JUN-13:00 | 0.00 |
July | 0.644245E+11 | 0.151189E+11 | 419.84 | 0.515595E+11 | 0.128650E+11 | 0.00 | 1.00 | 02-JUL-16:12 | 0.00 | 01-JUL-00:10 | 125607.11 | 21-JUL-04:02 | 70216.63 | 20-JUL-04:02 | 59008.25 | 21-JUL-04:02 | 28276.97 | 21-JUL-04:02 | 0.00 |
August | 0.548376E+11 | 0.129274E+11 | 412.06 | 0.461595E+11 | 0.867814E+10 | 0.00 | 1.00 | 01-AUG-11:20 | 0.00 | 01-AUG-00:10 | 91667.62 | 07-AUG-05:12 | 68048.48 | 10-AUG-14:05 | 51031.61 | 07-AUG-05:12 | 20453.18 | 07-AUG-05:12 | 0.00 |
September | 0.251994E+11 | 0.597853E+10 | 306.81 | 0.203974E+11 | 0.480201E+10 | 0.00 | 1.00 | 08-SEP-10:05 | 0.00 | 01-SEP-00:10 | 62731.68 | 15-SEP-12:05 | 55729.37 | 21-SEP-15:20 | 25095.52 | 14-SEP-09:30 | 14589.91 | 15-SEP-12:05 | 0.00 |
October | 0.315445E+10 | 0.811254E+09 | 88.04 | 0.265485E+10 | 0.499599E+09 | 0.00 | 0.98 | 11-OCT-15:20 | 0.00 | 01-OCT-00:10 | 36176.32 | 11-OCT-15:20 | 36176.32 | 11-OCT-15:20 | 6717.01 | 12-OCT-15:00 | 8079.57 | 11-OCT-15:20 | 0.00 |
November | 0.596451E+09 | 0.159220E+09 | 20.73 | 0.442436E+09 | 0.154015E+09 | 0.00 | 0.42 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 13408.50 | 16-NOV-18:00 | 10595.92 | 16-NOV-18:00 | 3536.02 | 04-NOV-14:10 | 3485.16 | 16-NOV-18:00 | 0.00 |
December | 1141951.03 | 326746.46 | 0.50 | 685753.49 | 456197.54 | 0.00 | 0.03 | 01-DEC-11:00 | 0.00 | 01-DEC-00:10 | 865.60 | 01-DEC-11:00 | 517.32 | 01-DEC-11:00 | 348.28 | 01-DEC-11:00 | 247.30 | 01-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.201146E+12 | 0.476772E+11 | 1899.12 | 0.165419E+12 | 0.357273E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.644245E+11 | 0.151189E+11 | 419.84 | 0.515595E+11 | 0.128650E+11 | 0.00 | 1.00 | 0.00 | 125607.11 | 70216.63 | 59008.25 | 28276.97 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3190351.59 | 912656.45 | 1.25 | 3146397.35 | 43954.24 | 0.00 | 0.05 | 09-JAN-06:20 | 0.00 | 01-JAN-00:03 | 2015.24 | 09-JAN-06:20 | 2015.24 | 09-JAN-06:20 | 75.82 | 18-JAN-06:10 | 573.17 | 09-JAN-06:20 | 0.00 |
February | 1952277.57 | 559447.95 | 1.00 | 1928879.09 | 23398.48 | 0.00 | 0.03 | 13-FEB-06:10 | 0.00 | 01-FEB-00:10 | 1415.43 | 13-FEB-06:10 | 1415.43 | 13-FEB-06:10 | 66.76 | 02-FEB-05:05 | 403.94 | 13-FEB-06:10 | 0.00 |
March | 0.305795E+10 | 0.755821E+09 | 35.85 | 0.255047E+10 | 0.507480E+09 | 0.00 | 0.92 | 15-MAR-14:00 | 0.00 | 01-MAR-00:10 | 46933.61 | 15-MAR-14:00 | 46933.61 | 15-MAR-14:00 | 12639.56 | 14-MAR-10:30 | 11256.04 | 15-MAR-14:00 | 0.00 |
April | 0.107897E+10 | 0.290945E+09 | 39.34 | 0.966416E+09 | 0.112556E+09 | 0.00 | 0.47 | 08-APR-13:00 | 0.00 | 01-APR-00:10 | 21223.76 | 08-APR-13:00 | 18446.34 | 08-APR-13:00 | 3847.53 | 08-APR-14:00 | 5449.28 | 08-APR-13:00 | 0.00 |
May | 0.116709E+11 | 0.292322E+10 | 197.94 | 0.104309E+11 | 0.123999E+10 | 0.00 | 1.00 | 23-MAY-14:30 | 0.00 | 01-MAY-00:10 | 54022.31 | 31-MAY-16:00 | 54022.31 | 31-MAY-16:00 | 9281.15 | 10-MAY-17:30 | 12336.46 | 10-MAY-15:00 | 0.00 |
June | 0.464329E+11 | 0.111670E+11 | 371.69 | 0.377279E+11 | 0.870509E+10 | 0.00 | 1.00 | 01-JUN-13:40 | 0.00 | 01-JUN-00:10 | 96400.15 | 27-JUN-13:05 | 78339.50 | 12-JUN-14:00 | 31984.18 | 21-JUN-11:00 | 24467.10 | 27-JUN-13:00 | 0.00 |
July | 0.743168E+11 | 0.176716E+11 | 419.51 | 0.597253E+11 | 0.145915E+11 | 0.00 | 1.00 | 02-JUL-16:52 | 0.00 | 01-JUL-00:10 | 177530.60 | 21-JUL-04:02 | 95368.15 | 21-JUL-04:02 | 86342.46 | 21-JUL-05:02 | 39766.37 | 21-JUL-04:02 | 0.00 |
August | 0.622261E+11 | 0.149321E+11 | 409.75 | 0.518779E+11 | 0.103482E+11 | 0.00 | 1.00 | 01-AUG-12:05 | 0.00 | 01-AUG-00:10 | 87823.53 | 18-AUG-14:30 | 80580.02 | 09-AUG-14:50 | 30251.49 | 25-AUG-19:10 | 22293.51 | 18-AUG-14:30 | 0.00 |
September | 0.278504E+11 | 0.676974E+10 | 301.40 | 0.216431E+11 | 0.620726E+10 | 0.00 | 1.00 | 08-SEP-13:50 | 0.00 | 01-SEP-00:10 | 68532.21 | 15-SEP-12:05 | 64884.22 | 21-SEP-15:00 | 26963.79 | 14-SEP-09:30 | 15896.27 | 15-SEP-12:05 | 0.00 |
October | 0.346700E+10 | 0.908232E+09 | 85.61 | 0.274660E+10 | 0.720399E+09 | 0.00 | 0.82 | 11-OCT-15:20 | 0.00 | 01-OCT-00:10 | 40444.32 | 11-OCT-15:20 | 40444.32 | 11-OCT-15:20 | 8505.41 | 12-OCT-15:00 | 9463.17 | 11-OCT-15:20 | 0.00 |
November | 0.721183E+09 | 0.194309E+09 | 19.72 | 0.509556E+09 | 0.211627E+09 | 0.00 | 0.37 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 16250.09 | 16-NOV-18:00 | 12387.91 | 27-NOV-07:03 | 4708.23 | 04-NOV-14:40 | 4280.08 | 16-NOV-18:00 | 0.00 |
December | 5343802.74 | 1532389.69 | 3.05 | 4925424.52 | 418378.23 | 0.00 | 0.03 | 09-DEC-06:01 | 0.00 | 01-DEC-00:10 | 1245.50 | 09-DEC-06:01 | 1245.50 | 09-DEC-06:01 | 380.38 | 01-DEC-11:00 | 355.78 | 09-DEC-06:01 | 0.00 |
Annual Sum or Average | 0.230833E+12 | 0.556160E+11 | 1886.12 | 0.188188E+12 | 0.426446E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1952277.57 | 559447.95 | 1.00 | 1928879.09 | 23398.48 | 0.00 | 0.03 | 0.00 | 1245.50 | 1245.50 | 66.76 | 355.78 | 0.00 | ||||||
Maximum of Months | 0.743168E+11 | 0.176716E+11 | 419.51 | 0.597253E+11 | 0.145915E+11 | 0.00 | 1.00 | 0.00 | 177530.60 | 95368.15 | 86342.46 | 39766.37 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.04 | 0.00 | 353.04 | 0.32 | 2980.24 | 0.00 | 0.00 | 0.00 |
February | 537.91 | 0.00 | 537.91 | 3.60 | 2843.76 | 0.00 | 0.00 | 0.00 |
March | 652.33 | 0.00 | 652.33 | 138.37 | 2005.70 | 0.00 | 0.00 | 0.00 |
April | 831.20 | 3.32 | 827.88 | 327.50 | 1356.08 | 0.00 | 0.00 | 0.00 |
May | 965.81 | 40.96 | 924.86 | 642.31 | 840.87 | 0.00 | 0.00 | 0.00 |
June | 1161.67 | 98.89 | 1062.78 | 1163.33 | 540.43 | 0.00 | 0.00 | 0.00 |
July | 1077.60 | 69.56 | 1008.04 | 1313.14 | 379.44 | 0.00 | 0.00 | 0.00 |
August | 932.43 | 14.18 | 918.24 | 1062.93 | 501.80 | 0.00 | 0.00 | 0.00 |
September | 709.60 | 0.15 | 709.45 | 590.78 | 803.64 | 0.00 | 0.00 | 0.00 |
October | 530.45 | 0.00 | 530.45 | 196.35 | 1300.84 | 0.00 | 0.00 | 0.00 |
November | 356.45 | 0.00 | 356.45 | 50.06 | 1762.04 | 0.00 | 0.00 | 0.00 |
December | 330.44 | 0.00 | 330.44 | 1.30 | 2810.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.93 | 19.00 | 684.93 | 460.40 | 1503.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.44 | 0.00 | 330.44 | 0.32 | 379.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1161.67 | 98.89 | 1062.78 | 1313.14 | 2980.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 430.71 | 138.88 | 291.82 | 115.99 | 1791.87 | 0.00 | 0.00 | 0.00 |
February | 631.98 | 189.64 | 442.34 | 216.29 | 1715.23 | 0.00 | 0.00 | 0.00 |
March | 906.87 | 379.79 | 527.08 | 606.81 | 1199.97 | 0.00 | 0.00 | 0.00 |
April | 1200.30 | 530.35 | 669.95 | 1008.04 | 842.36 | 0.00 | 0.00 | 0.00 |
May | 1344.77 | 594.86 | 749.91 | 1358.87 | 571.80 | 0.00 | 0.00 | 0.00 |
June | 1501.88 | 663.75 | 838.13 | 1751.90 | 370.15 | 0.00 | 0.00 | 0.00 |
July | 1442.20 | 634.98 | 807.22 | 1852.29 | 257.49 | 0.00 | 0.00 | 0.00 |
August | 1302.46 | 546.70 | 755.76 | 1625.22 | 336.04 | 0.00 | 0.00 | 0.00 |
September | 1083.88 | 480.76 | 603.11 | 1191.55 | 516.55 | 0.00 | 0.00 | 0.00 |
October | 735.50 | 304.22 | 431.28 | 594.94 | 811.45 | 0.00 | 0.00 | 0.00 |
November | 417.19 | 133.83 | 283.36 | 218.74 | 1111.16 | 0.00 | 0.00 | 0.00 |
December | 335.86 | 69.40 | 266.46 | 56.74 | 1763.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 945.87 | 389.88 | 555.99 | 886.85 | 936.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 335.86 | 69.40 | 266.46 | 56.74 | 257.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1501.88 | 663.75 | 838.13 | 1852.29 | 1791.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1518.06 | 886.13 | 631.92 | 1051.49 | 2485.33 | 0.00 | 0.00 | 0.00 |
February | 1733.24 | 835.75 | 897.49 | 1134.36 | 2446.58 | 0.00 | 0.00 | 0.00 |
March | 2115.54 | 1188.70 | 926.84 | 1847.34 | 1759.19 | 0.00 | 0.00 | 0.00 |
April | 1752.00 | 700.10 | 1051.90 | 1622.14 | 1384.02 | 0.00 | 0.00 | 0.00 |
May | 1533.16 | 445.29 | 1087.87 | 1573.56 | 940.81 | 0.00 | 0.00 | 0.00 |
June | 1489.74 | 315.68 | 1174.06 | 1763.05 | 605.52 | 0.00 | 0.00 | 0.00 |
July | 1520.78 | 368.99 | 1151.80 | 2059.05 | 419.94 | 0.00 | 0.00 | 0.00 |
August | 1707.33 | 553.55 | 1153.77 | 2269.09 | 538.40 | 0.00 | 0.00 | 0.00 |
September | 1985.11 | 966.89 | 1018.22 | 2396.87 | 830.10 | 0.00 | 0.00 | 0.00 |
October | 1899.45 | 1085.00 | 814.45 | 1924.16 | 1238.58 | 0.00 | 0.00 | 0.00 |
November | 1360.35 | 767.96 | 592.39 | 1178.77 | 1631.18 | 0.00 | 0.00 | 0.00 |
December | 1269.40 | 656.97 | 612.43 | 821.80 | 2444.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1656.50 | 730.53 | 925.97 | 1639.80 | 1388.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1269.40 | 315.68 | 592.39 | 821.80 | 419.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2115.54 | 1188.70 | 1174.06 | 2396.87 | 2485.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.54 | 86.75 | 282.79 | 69.23 | 1885.22 | 0.00 | 0.00 | 0.00 |
February | 598.92 | 153.93 | 445.00 | 175.70 | 1787.54 | 0.00 | 0.00 | 0.00 |
March | 938.70 | 401.93 | 536.77 | 638.54 | 1230.76 | 0.00 | 0.00 | 0.00 |
April | 1149.32 | 471.26 | 678.05 | 966.09 | 891.37 | 0.00 | 0.00 | 0.00 |
May | 1355.80 | 612.73 | 743.07 | 1391.05 | 609.33 | 0.00 | 0.00 | 0.00 |
June | 1635.82 | 769.42 | 866.40 | 1946.09 | 408.77 | 0.00 | 0.00 | 0.00 |
July | 1462.48 | 641.20 | 821.28 | 1897.15 | 289.04 | 0.00 | 0.00 | 0.00 |
August | 1322.73 | 562.43 | 760.29 | 1684.92 | 359.62 | 0.00 | 0.00 | 0.00 |
September | 1038.75 | 448.59 | 590.16 | 1156.45 | 545.28 | 0.00 | 0.00 | 0.00 |
October | 673.37 | 237.20 | 436.17 | 529.30 | 848.15 | 0.00 | 0.00 | 0.00 |
November | 399.04 | 114.99 | 284.05 | 198.92 | 1139.76 | 0.00 | 0.00 | 0.00 |
December | 345.93 | 75.37 | 270.56 | 66.33 | 1799.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 942.42 | 382.42 | 560.00 | 897.31 | 978.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 345.93 | 75.37 | 270.56 | 66.33 | 289.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1635.82 | 769.42 | 866.40 | 1946.09 | 1885.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.68 | 0.00 | 117.68 | 0.00 | 1005.54 | 0.00 | 0.00 | 0.00 |
February | 179.30 | 0.00 | 179.30 | 1.11 | 955.48 | 0.00 | 0.00 | 0.00 |
March | 217.43 | 0.00 | 217.43 | 52.09 | 667.14 | 0.00 | 0.00 | 0.00 |
April | 277.06 | 1.11 | 275.95 | 123.43 | 447.19 | 0.00 | 0.00 | 0.00 |
May | 321.93 | 13.65 | 308.27 | 241.57 | 265.61 | 0.00 | 0.00 | 0.00 |
June | 387.21 | 32.96 | 354.25 | 407.86 | 174.03 | 0.00 | 0.00 | 0.00 |
July | 359.19 | 23.19 | 336.00 | 450.47 | 123.09 | 0.00 | 0.00 | 0.00 |
August | 310.80 | 4.73 | 306.07 | 359.06 | 173.17 | 0.00 | 0.00 | 0.00 |
September | 236.52 | 0.05 | 236.47 | 194.81 | 293.07 | 0.00 | 0.00 | 0.00 |
October | 176.81 | 0.00 | 176.81 | 59.69 | 484.25 | 0.00 | 0.00 | 0.00 |
November | 118.81 | 0.00 | 118.81 | 14.41 | 644.54 | 0.00 | 0.00 | 0.00 |
December | 110.14 | 0.00 | 110.14 | 0.32 | 974.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.63 | 6.33 | 228.30 | 159.74 | 515.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.14 | 0.00 | 110.14 | 0.00 | 123.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.21 | 32.96 | 354.25 | 450.47 | 1005.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.68 | 0.00 | 117.68 | 0.00 | 1005.60 | 0.00 | 0.00 | 0.00 |
February | 179.30 | 0.00 | 179.30 | 1.11 | 955.54 | 0.00 | 0.00 | 0.00 |
March | 217.45 | 0.00 | 217.45 | 52.09 | 667.18 | 0.00 | 0.00 | 0.00 |
April | 277.07 | 1.11 | 275.96 | 123.43 | 447.22 | 0.00 | 0.00 | 0.00 |
May | 321.94 | 13.65 | 308.29 | 241.58 | 265.63 | 0.00 | 0.00 | 0.00 |
June | 387.23 | 32.96 | 354.27 | 407.87 | 174.04 | 0.00 | 0.00 | 0.00 |
July | 359.21 | 23.19 | 336.02 | 450.49 | 123.10 | 0.00 | 0.00 | 0.00 |
August | 310.81 | 4.73 | 306.08 | 359.08 | 173.18 | 0.00 | 0.00 | 0.00 |
September | 236.53 | 0.05 | 236.49 | 194.81 | 293.09 | 0.00 | 0.00 | 0.00 |
October | 176.82 | 0.00 | 176.82 | 59.69 | 484.28 | 0.00 | 0.00 | 0.00 |
November | 118.82 | 0.00 | 118.82 | 14.41 | 644.59 | 0.00 | 0.00 | 0.00 |
December | 110.15 | 0.00 | 110.15 | 0.32 | 974.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.65 | 6.33 | 228.31 | 159.75 | 515.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.15 | 0.00 | 110.15 | 0.00 | 123.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.23 | 32.96 | 354.27 | 450.49 | 1005.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.68 | 0.00 | 117.68 | 0.00 | 1005.60 | 0.00 | 0.00 | 0.00 |
February | 179.30 | 0.00 | 179.30 | 1.11 | 955.54 | 0.00 | 0.00 | 0.00 |
March | 217.45 | 0.00 | 217.45 | 52.09 | 667.18 | 0.00 | 0.00 | 0.00 |
April | 277.07 | 1.11 | 275.96 | 123.43 | 447.22 | 0.00 | 0.00 | 0.00 |
May | 321.94 | 13.65 | 308.29 | 241.58 | 265.63 | 0.00 | 0.00 | 0.00 |
June | 387.23 | 32.96 | 354.27 | 407.87 | 174.04 | 0.00 | 0.00 | 0.00 |
July | 359.21 | 23.19 | 336.02 | 450.49 | 123.10 | 0.00 | 0.00 | 0.00 |
August | 310.81 | 4.73 | 306.08 | 359.08 | 173.18 | 0.00 | 0.00 | 0.00 |
September | 236.53 | 0.05 | 236.49 | 194.81 | 293.09 | 0.00 | 0.00 | 0.00 |
October | 176.82 | 0.00 | 176.82 | 59.69 | 484.28 | 0.00 | 0.00 | 0.00 |
November | 118.82 | 0.00 | 118.82 | 14.41 | 644.59 | 0.00 | 0.00 | 0.00 |
December | 110.15 | 0.00 | 110.15 | 0.32 | 974.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.65 | 6.33 | 228.31 | 159.75 | 515.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.15 | 0.00 | 110.15 | 0.00 | 123.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.23 | 32.96 | 354.27 | 450.49 | 1005.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.34 | 133.61 | 280.73 | 112.69 | 1754.87 | 0.00 | 0.00 | 0.00 |
February | 607.96 | 182.43 | 425.53 | 211.67 | 1671.38 | 0.00 | 0.00 | 0.00 |
March | 872.41 | 365.36 | 507.05 | 604.56 | 1166.77 | 0.00 | 0.00 | 0.00 |
April | 1154.69 | 510.20 | 644.48 | 1002.62 | 818.78 | 0.00 | 0.00 | 0.00 |
May | 1293.66 | 572.26 | 721.41 | 1354.73 | 538.33 | 0.00 | 0.00 | 0.00 |
June | 1444.80 | 638.53 | 806.27 | 1717.70 | 359.16 | 0.00 | 0.00 | 0.00 |
July | 1387.39 | 610.85 | 776.54 | 1805.78 | 252.68 | 0.00 | 0.00 | 0.00 |
August | 1252.97 | 525.93 | 727.04 | 1575.84 | 345.26 | 0.00 | 0.00 | 0.00 |
September | 1042.69 | 462.50 | 580.19 | 1142.23 | 557.11 | 0.00 | 0.00 | 0.00 |
October | 707.55 | 292.66 | 414.89 | 553.87 | 887.05 | 0.00 | 0.00 | 0.00 |
November | 401.33 | 128.74 | 272.59 | 201.55 | 1181.82 | 0.00 | 0.00 | 0.00 |
December | 323.09 | 66.76 | 256.34 | 52.69 | 1767.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 909.92 | 375.06 | 534.86 | 864.97 | 938.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 323.09 | 66.76 | 256.34 | 52.69 | 252.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1444.80 | 638.53 | 806.27 | 1805.78 | 1767.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.38 | 5.28 | 11.10 | 4.46 | 69.39 | 0.00 | 0.00 | 0.00 |
February | 24.04 | 7.21 | 16.82 | 8.37 | 66.08 | 0.00 | 0.00 | 0.00 |
March | 34.49 | 14.45 | 20.05 | 23.90 | 46.13 | 0.00 | 0.00 | 0.00 |
April | 45.66 | 20.17 | 25.48 | 39.64 | 32.37 | 0.00 | 0.00 | 0.00 |
May | 51.15 | 22.63 | 28.52 | 53.56 | 21.29 | 0.00 | 0.00 | 0.00 |
June | 57.13 | 25.25 | 31.88 | 67.92 | 14.20 | 0.00 | 0.00 | 0.00 |
July | 54.86 | 24.15 | 30.70 | 71.40 | 9.99 | 0.00 | 0.00 | 0.00 |
August | 49.54 | 20.79 | 28.75 | 62.31 | 13.65 | 0.00 | 0.00 | 0.00 |
September | 41.23 | 18.29 | 22.94 | 45.16 | 22.03 | 0.00 | 0.00 | 0.00 |
October | 27.98 | 11.57 | 16.40 | 21.90 | 35.07 | 0.00 | 0.00 | 0.00 |
November | 15.87 | 5.09 | 10.78 | 7.97 | 46.73 | 0.00 | 0.00 | 0.00 |
December | 12.77 | 2.64 | 10.14 | 2.08 | 69.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.98 | 14.83 | 21.15 | 34.20 | 37.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.77 | 2.64 | 10.14 | 2.08 | 9.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.13 | 25.25 | 31.88 | 71.40 | 69.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.03 | 295.39 | 210.65 | 359.77 | 835.47 | 0.00 | 0.00 | 0.00 |
February | 577.76 | 278.59 | 299.17 | 395.17 | 817.76 | 0.00 | 0.00 | 0.00 |
March | 705.20 | 396.25 | 308.95 | 640.39 | 599.22 | 0.00 | 0.00 | 0.00 |
April | 584.02 | 233.37 | 350.64 | 564.60 | 463.17 | 0.00 | 0.00 | 0.00 |
May | 511.07 | 148.43 | 362.63 | 554.70 | 301.50 | 0.00 | 0.00 | 0.00 |
June | 496.59 | 105.23 | 391.36 | 611.09 | 197.94 | 0.00 | 0.00 | 0.00 |
July | 506.94 | 123.00 | 383.94 | 701.08 | 140.63 | 0.00 | 0.00 | 0.00 |
August | 569.12 | 184.52 | 384.60 | 764.98 | 192.15 | 0.00 | 0.00 | 0.00 |
September | 661.72 | 322.31 | 339.41 | 801.22 | 313.07 | 0.00 | 0.00 | 0.00 |
October | 633.17 | 361.68 | 271.49 | 640.07 | 471.51 | 0.00 | 0.00 | 0.00 |
November | 453.46 | 255.99 | 197.47 | 391.18 | 604.12 | 0.00 | 0.00 | 0.00 |
December | 423.14 | 219.00 | 204.15 | 277.80 | 842.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 552.18 | 243.52 | 308.66 | 559.48 | 479.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 423.14 | 105.23 | 197.47 | 277.80 | 140.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 705.20 | 396.25 | 391.36 | 801.22 | 842.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.03 | 295.39 | 210.65 | 359.77 | 835.47 | 0.00 | 0.00 | 0.00 |
February | 577.76 | 278.59 | 299.17 | 395.17 | 817.76 | 0.00 | 0.00 | 0.00 |
March | 705.20 | 396.25 | 308.95 | 640.39 | 599.22 | 0.00 | 0.00 | 0.00 |
April | 584.02 | 233.37 | 350.64 | 564.60 | 463.17 | 0.00 | 0.00 | 0.00 |
May | 511.07 | 148.43 | 362.63 | 554.70 | 301.50 | 0.00 | 0.00 | 0.00 |
June | 496.59 | 105.23 | 391.36 | 611.09 | 197.94 | 0.00 | 0.00 | 0.00 |
July | 506.94 | 123.00 | 383.94 | 701.08 | 140.63 | 0.00 | 0.00 | 0.00 |
August | 569.12 | 184.52 | 384.60 | 764.98 | 192.15 | 0.00 | 0.00 | 0.00 |
September | 661.72 | 322.31 | 339.41 | 801.22 | 313.07 | 0.00 | 0.00 | 0.00 |
October | 633.17 | 361.68 | 271.49 | 640.07 | 471.51 | 0.00 | 0.00 | 0.00 |
November | 453.46 | 255.99 | 197.47 | 391.18 | 604.12 | 0.00 | 0.00 | 0.00 |
December | 423.14 | 219.00 | 204.15 | 277.80 | 842.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 552.18 | 243.52 | 308.66 | 559.48 | 479.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 423.14 | 105.23 | 197.47 | 277.80 | 140.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 705.20 | 396.25 | 391.36 | 801.22 | 842.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.00 | 295.37 | 210.63 | 359.75 | 835.42 | 0.00 | 0.00 | 0.00 |
February | 577.73 | 278.57 | 299.15 | 395.14 | 817.71 | 0.00 | 0.00 | 0.00 |
March | 705.15 | 396.22 | 308.93 | 640.35 | 599.18 | 0.00 | 0.00 | 0.00 |
April | 583.98 | 233.36 | 350.62 | 564.56 | 463.14 | 0.00 | 0.00 | 0.00 |
May | 511.03 | 148.43 | 362.61 | 554.67 | 301.49 | 0.00 | 0.00 | 0.00 |
June | 496.56 | 105.22 | 391.34 | 611.05 | 197.93 | 0.00 | 0.00 | 0.00 |
July | 506.91 | 122.99 | 383.92 | 701.03 | 140.63 | 0.00 | 0.00 | 0.00 |
August | 569.09 | 184.51 | 384.58 | 764.93 | 192.13 | 0.00 | 0.00 | 0.00 |
September | 661.68 | 322.29 | 339.39 | 801.17 | 313.05 | 0.00 | 0.00 | 0.00 |
October | 633.13 | 361.65 | 271.47 | 640.03 | 471.48 | 0.00 | 0.00 | 0.00 |
November | 453.43 | 255.98 | 197.46 | 391.16 | 604.08 | 0.00 | 0.00 | 0.00 |
December | 423.12 | 218.98 | 204.14 | 277.78 | 841.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 552.15 | 243.50 | 308.64 | 559.44 | 479.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 423.12 | 105.22 | 197.46 | 277.78 | 140.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 705.15 | 396.22 | 391.34 | 801.17 | 841.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 355.50 | 83.46 | 272.04 | 69.31 | 1835.80 | 0.00 | 0.00 | 0.00 |
February | 576.16 | 148.08 | 428.08 | 178.56 | 1734.83 | 0.00 | 0.00 | 0.00 |
March | 903.03 | 386.66 | 516.37 | 644.77 | 1201.11 | 0.00 | 0.00 | 0.00 |
April | 1105.64 | 453.36 | 652.28 | 970.70 | 866.04 | 0.00 | 0.00 | 0.00 |
May | 1304.28 | 589.45 | 714.83 | 1389.98 | 579.34 | 0.00 | 0.00 | 0.00 |
June | 1573.65 | 740.18 | 833.47 | 1908.26 | 404.54 | 0.00 | 0.00 | 0.00 |
July | 1406.90 | 616.83 | 790.07 | 1849.55 | 287.96 | 0.00 | 0.00 | 0.00 |
August | 1272.46 | 541.06 | 731.40 | 1630.68 | 375.33 | 0.00 | 0.00 | 0.00 |
September | 999.27 | 431.54 | 567.73 | 1109.04 | 589.99 | 0.00 | 0.00 | 0.00 |
October | 647.78 | 228.18 | 419.59 | 499.67 | 921.35 | 0.00 | 0.00 | 0.00 |
November | 383.88 | 110.62 | 273.26 | 187.07 | 1208.95 | 0.00 | 0.00 | 0.00 |
December | 332.79 | 72.51 | 260.28 | 64.78 | 1798.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 906.60 | 367.89 | 538.71 | 879.07 | 979.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.79 | 72.51 | 260.28 | 64.78 | 287.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1573.65 | 740.18 | 833.47 | 1908.26 | 1835.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.06 | 3.30 | 10.76 | 2.74 | 72.59 | 0.00 | 0.00 | 0.00 |
February | 22.78 | 5.85 | 16.93 | 7.06 | 68.59 | 0.00 | 0.00 | 0.00 |
March | 35.70 | 15.29 | 20.42 | 25.49 | 47.49 | 0.00 | 0.00 | 0.00 |
April | 43.72 | 17.93 | 25.79 | 38.38 | 34.24 | 0.00 | 0.00 | 0.00 |
May | 51.57 | 23.31 | 28.26 | 54.96 | 22.91 | 0.00 | 0.00 | 0.00 |
June | 62.22 | 29.27 | 32.95 | 75.45 | 16.00 | 0.00 | 0.00 | 0.00 |
July | 55.63 | 24.39 | 31.24 | 73.13 | 11.39 | 0.00 | 0.00 | 0.00 |
August | 50.31 | 21.39 | 28.92 | 64.48 | 14.84 | 0.00 | 0.00 | 0.00 |
September | 39.51 | 17.06 | 22.45 | 43.85 | 23.33 | 0.00 | 0.00 | 0.00 |
October | 25.61 | 9.02 | 16.59 | 19.76 | 36.43 | 0.00 | 0.00 | 0.00 |
November | 15.18 | 4.37 | 10.80 | 7.40 | 47.80 | 0.00 | 0.00 | 0.00 |
December | 13.16 | 2.87 | 10.29 | 2.56 | 71.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.85 | 14.55 | 21.30 | 34.76 | 38.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.16 | 2.87 | 10.29 | 2.56 | 11.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.22 | 29.27 | 32.95 | 75.45 | 72.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.04 | 0.00 | 353.04 | 0.00 | 3080.20 | 0.00 | 0.00 | 0.00 |
February | 537.91 | 0.00 | 537.91 | 2.57 | 2944.29 | 0.00 | 0.00 | 0.00 |
March | 652.33 | 0.00 | 652.33 | 131.13 | 2117.90 | 0.00 | 0.00 | 0.00 |
April | 831.20 | 3.32 | 827.88 | 311.58 | 1454.20 | 0.00 | 0.00 | 0.00 |
May | 965.81 | 40.96 | 924.86 | 621.51 | 908.66 | 0.00 | 0.00 | 0.00 |
June | 1161.67 | 98.89 | 1062.78 | 1144.04 | 579.01 | 0.00 | 0.00 | 0.00 |
July | 1077.60 | 69.56 | 1008.04 | 1303.23 | 403.94 | 0.00 | 0.00 | 0.00 |
August | 932.43 | 14.18 | 918.24 | 1047.98 | 543.58 | 0.00 | 0.00 | 0.00 |
September | 709.60 | 0.15 | 709.45 | 565.31 | 888.77 | 0.00 | 0.00 | 0.00 |
October | 530.45 | 0.00 | 530.45 | 173.83 | 1434.63 | 0.00 | 0.00 | 0.00 |
November | 356.45 | 0.00 | 356.45 | 42.19 | 1916.24 | 0.00 | 0.00 | 0.00 |
December | 330.44 | 0.00 | 330.44 | 0.88 | 2934.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.93 | 19.00 | 684.93 | 448.22 | 1593.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.44 | 0.00 | 330.44 | 0.00 | 403.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1161.67 | 98.89 | 1062.78 | 1303.23 | 3080.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 430.71 | 138.88 | 291.82 | 112.05 | 1852.32 | 0.00 | 0.00 | 0.00 |
February | 631.98 | 189.64 | 442.34 | 210.31 | 1776.59 | 0.00 | 0.00 | 0.00 |
March | 906.87 | 379.79 | 527.08 | 590.72 | 1271.86 | 0.00 | 0.00 | 0.00 |
April | 1200.30 | 530.35 | 669.95 | 984.80 | 901.43 | 0.00 | 0.00 | 0.00 |
May | 1344.77 | 594.86 | 749.91 | 1345.27 | 608.40 | 0.00 | 0.00 | 0.00 |
June | 1501.88 | 663.75 | 838.13 | 1747.10 | 389.52 | 0.00 | 0.00 | 0.00 |
July | 1442.20 | 634.98 | 807.22 | 1851.87 | 269.39 | 0.00 | 0.00 | 0.00 |
August | 1302.46 | 546.70 | 755.76 | 1620.56 | 356.34 | 0.00 | 0.00 | 0.00 |
September | 1083.88 | 480.76 | 603.11 | 1176.03 | 560.20 | 0.00 | 0.00 | 0.00 |
October | 735.50 | 304.22 | 431.28 | 566.43 | 894.44 | 0.00 | 0.00 | 0.00 |
November | 417.19 | 133.83 | 283.36 | 205.15 | 1212.46 | 0.00 | 0.00 | 0.00 |
December | 335.86 | 69.40 | 266.46 | 53.35 | 1838.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 945.87 | 389.88 | 555.99 | 875.70 | 990.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 335.86 | 69.40 | 266.46 | 53.35 | 269.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1501.88 | 663.75 | 838.13 | 1851.87 | 1852.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1518.06 | 886.13 | 631.92 | 1035.34 | 2585.99 | 0.00 | 0.00 | 0.00 |
February | 1733.24 | 835.75 | 897.49 | 1118.92 | 2544.54 | 0.00 | 0.00 | 0.00 |
March | 2115.54 | 1188.70 | 926.84 | 1825.85 | 1872.88 | 0.00 | 0.00 | 0.00 |
April | 1752.00 | 700.10 | 1051.90 | 1602.08 | 1482.63 | 0.00 | 0.00 | 0.00 |
May | 1533.16 | 445.29 | 1087.87 | 1561.03 | 1012.91 | 0.00 | 0.00 | 0.00 |
June | 1489.74 | 315.68 | 1174.06 | 1756.02 | 651.15 | 0.00 | 0.00 | 0.00 |
July | 1520.78 | 368.99 | 1151.80 | 2057.06 | 449.65 | 0.00 | 0.00 | 0.00 |
August | 1707.33 | 553.55 | 1153.77 | 2263.48 | 582.25 | 0.00 | 0.00 | 0.00 |
September | 1985.11 | 966.89 | 1018.22 | 2379.25 | 911.02 | 0.00 | 0.00 | 0.00 |
October | 1899.45 | 1085.00 | 814.45 | 1889.76 | 1365.89 | 0.00 | 0.00 | 0.00 |
November | 1360.35 | 767.96 | 592.39 | 1150.55 | 1777.28 | 0.00 | 0.00 | 0.00 |
December | 1269.40 | 656.97 | 612.43 | 806.82 | 2564.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1656.50 | 730.53 | 925.97 | 1623.52 | 1477.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1269.40 | 315.68 | 592.39 | 806.82 | 449.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2115.54 | 1188.70 | 1174.06 | 2379.25 | 2585.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.54 | 86.75 | 282.79 | 67.67 | 1948.72 | 0.00 | 0.00 | 0.00 |
February | 598.92 | 153.93 | 445.00 | 174.42 | 1851.25 | 0.00 | 0.00 | 0.00 |
March | 938.70 | 401.93 | 536.77 | 633.65 | 1303.79 | 0.00 | 0.00 | 0.00 |
April | 1149.32 | 471.26 | 678.05 | 960.04 | 953.60 | 0.00 | 0.00 | 0.00 |
May | 1355.80 | 612.73 | 743.07 | 1388.84 | 651.59 | 0.00 | 0.00 | 0.00 |
June | 1635.82 | 769.42 | 866.40 | 1947.90 | 435.15 | 0.00 | 0.00 | 0.00 |
July | 1462.48 | 641.20 | 821.28 | 1900.83 | 306.13 | 0.00 | 0.00 | 0.00 |
August | 1322.73 | 562.43 | 760.29 | 1683.43 | 385.00 | 0.00 | 0.00 | 0.00 |
September | 1038.75 | 448.59 | 590.16 | 1147.53 | 594.72 | 0.00 | 0.00 | 0.00 |
October | 673.37 | 237.20 | 436.17 | 515.10 | 930.65 | 0.00 | 0.00 | 0.00 |
November | 399.04 | 114.99 | 284.05 | 191.36 | 1238.22 | 0.00 | 0.00 | 0.00 |
December | 345.93 | 75.37 | 270.56 | 64.58 | 1877.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 942.42 | 382.42 | 560.00 | 893.60 | 1035.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 345.93 | 75.37 | 270.56 | 64.58 | 306.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1635.82 | 769.42 | 866.40 | 1947.90 | 1948.72 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.945592E+09 | 0.00 | 0.945592E+09 | 847413.88 | 0.798229E+10 |
February | 0.130130E+10 | 0.00 | 0.130130E+10 | 8707757.73 | 0.687961E+10 |
March | 0.174720E+10 | 0.00 | 0.174720E+10 | 0.370601E+09 | 0.537208E+10 |
April | 0.215447E+10 | 8597147.97 | 0.214587E+10 | 0.848881E+09 | 0.351497E+10 |
May | 0.258684E+10 | 0.109696E+09 | 0.247714E+10 | 0.172035E+10 | 0.225218E+10 |
June | 0.301105E+10 | 0.256315E+09 | 0.275474E+10 | 0.301536E+10 | 0.140081E+10 |
July | 0.288626E+10 | 0.186313E+09 | 0.269994E+10 | 0.351712E+10 | 0.101630E+10 |
August | 0.249741E+10 | 37992498.94 | 0.245942E+10 | 0.284695E+10 | 0.134403E+10 |
September | 0.183928E+10 | 382119.68 | 0.183889E+10 | 0.153131E+10 | 0.208303E+10 |
October | 0.142077E+10 | 0.00 | 0.142077E+10 | 0.525893E+09 | 0.348418E+10 |
November | 0.923923E+09 | 0.00 | 0.923923E+09 | 0.129754E+09 | 0.456722E+10 |
December | 0.885045E+09 | 0.00 | 0.885045E+09 | 3494867.60 | 0.752776E+10 |
Annual Sum or Average | 0.221991E+11 | 0.599295E+09 | 0.215998E+11 | 0.145193E+11 | 0.474244E+11 |
Minimum of Months | 0.885045E+09 | 0.00 | 0.885045E+09 | 847413.88 | 0.101630E+10 |
Maximum of Months | 0.301105E+10 | 0.256315E+09 | 0.275474E+10 | 0.351712E+10 | 0.798229E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115360E+10 | 0.371985E+09 | 0.781620E+09 | 0.310668E+09 | 0.479934E+10 |
February | 0.152888E+10 | 0.458777E+09 | 0.107010E+10 | 0.523250E+09 | 0.414949E+10 |
March | 0.242896E+10 | 0.101723E+10 | 0.141173E+10 | 0.162529E+10 | 0.321401E+10 |
April | 0.311118E+10 | 0.137468E+10 | 0.173650E+10 | 0.261283E+10 | 0.218339E+10 |
May | 0.360183E+10 | 0.159327E+10 | 0.200856E+10 | 0.363960E+10 | 0.153151E+10 |
June | 0.389287E+10 | 0.172045E+10 | 0.217243E+10 | 0.454093E+10 | 0.959436E+09 |
July | 0.386279E+10 | 0.170072E+10 | 0.216207E+10 | 0.496116E+10 | 0.689668E+09 |
August | 0.348852E+10 | 0.146428E+10 | 0.202424E+10 | 0.435298E+10 | 0.900039E+09 |
September | 0.280940E+10 | 0.124614E+10 | 0.156327E+10 | 0.308849E+10 | 0.133889E+10 |
October | 0.196996E+10 | 0.814825E+09 | 0.115514E+10 | 0.159350E+10 | 0.217339E+10 |
November | 0.108135E+10 | 0.346883E+09 | 0.734469E+09 | 0.566971E+09 | 0.288012E+10 |
December | 0.899562E+09 | 0.185868E+09 | 0.713694E+09 | 0.151961E+09 | 0.472225E+10 |
Annual Sum or Average | 0.298289E+11 | 0.122951E+11 | 0.175338E+11 | 0.279676E+11 | 0.295415E+11 |
Minimum of Months | 0.899562E+09 | 0.185868E+09 | 0.713694E+09 | 0.151961E+09 | 0.689668E+09 |
Maximum of Months | 0.389287E+10 | 0.172045E+10 | 0.217243E+10 | 0.496116E+10 | 0.479934E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406597E+10 | 0.237342E+10 | 0.169255E+10 | 0.281630E+10 | 0.665671E+10 |
February | 0.419306E+10 | 0.202185E+10 | 0.217121E+10 | 0.274425E+10 | 0.591877E+10 |
March | 0.566626E+10 | 0.318383E+10 | 0.248244E+10 | 0.494793E+10 | 0.471181E+10 |
April | 0.454119E+10 | 0.181466E+10 | 0.272653E+10 | 0.420458E+10 | 0.358737E+10 |
May | 0.410642E+10 | 0.119267E+10 | 0.291375E+10 | 0.421462E+10 | 0.251985E+10 |
June | 0.386141E+10 | 0.818244E+09 | 0.304317E+10 | 0.456984E+10 | 0.156950E+10 |
July | 0.407327E+10 | 0.988299E+09 | 0.308497E+10 | 0.551496E+10 | 0.112478E+10 |
August | 0.457290E+10 | 0.148264E+10 | 0.309026E+10 | 0.607754E+10 | 0.144206E+10 |
September | 0.514540E+10 | 0.250618E+10 | 0.263922E+10 | 0.621268E+10 | 0.215162E+10 |
October | 0.508749E+10 | 0.290606E+10 | 0.218143E+10 | 0.515368E+10 | 0.331741E+10 |
November | 0.352602E+10 | 0.199055E+10 | 0.153547E+10 | 0.305537E+10 | 0.422803E+10 |
December | 0.339996E+10 | 0.175963E+10 | 0.164033E+10 | 0.220112E+10 | 0.654811E+10 |
Annual Sum or Average | 0.522394E+11 | 0.230380E+11 | 0.292013E+11 | 0.517129E+11 | 0.437760E+11 |
Minimum of Months | 0.339996E+10 | 0.818244E+09 | 0.153547E+10 | 0.220112E+10 | 0.112478E+10 |
Maximum of Months | 0.566626E+10 | 0.318383E+10 | 0.309026E+10 | 0.621268E+10 | 0.665671E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.989776E+09 | 0.232359E+09 | 0.757417E+09 | 0.185423E+09 | 0.504936E+10 |
February | 0.144891E+10 | 0.372379E+09 | 0.107653E+10 | 0.425055E+09 | 0.432441E+10 |
March | 0.251422E+10 | 0.107653E+10 | 0.143770E+10 | 0.171026E+10 | 0.329646E+10 |
April | 0.297903E+10 | 0.122151E+10 | 0.175751E+10 | 0.250410E+10 | 0.231044E+10 |
May | 0.363138E+10 | 0.164114E+10 | 0.199024E+10 | 0.372578E+10 | 0.163203E+10 |
June | 0.424003E+10 | 0.199433E+10 | 0.224571E+10 | 0.504426E+10 | 0.105954E+10 |
July | 0.391711E+10 | 0.171739E+10 | 0.219972E+10 | 0.508133E+10 | 0.774159E+09 |
August | 0.354279E+10 | 0.150642E+10 | 0.203637E+10 | 0.451289E+10 | 0.963196E+09 |
September | 0.269244E+10 | 0.116274E+10 | 0.152970E+10 | 0.299751E+10 | 0.141338E+10 |
October | 0.180355E+10 | 0.635310E+09 | 0.116824E+10 | 0.141769E+10 | 0.227168E+10 |
November | 0.103431E+10 | 0.298051E+09 | 0.736263E+09 | 0.515613E+09 | 0.295427E+10 |
December | 0.926546E+09 | 0.201883E+09 | 0.724663E+09 | 0.177655E+09 | 0.481925E+10 |
Annual Sum or Average | 0.297201E+11 | 0.120600E+11 | 0.176601E+11 | 0.282976E+11 | 0.308682E+11 |
Minimum of Months | 0.926546E+09 | 0.201883E+09 | 0.724663E+09 | 0.177655E+09 | 0.774159E+09 |
Maximum of Months | 0.424003E+10 | 0.199433E+10 | 0.224571E+10 | 0.508133E+10 | 0.504936E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315186E+09 | 0.00 | 0.315186E+09 | 0.00 | 0.269324E+10 |
February | 0.433752E+09 | 0.00 | 0.433752E+09 | 2693762.23 | 0.231149E+10 |
March | 0.582377E+09 | 0.00 | 0.582377E+09 | 0.139521E+09 | 0.178687E+10 |
April | 0.718131E+09 | 2865625.64 | 0.715265E+09 | 0.319920E+09 | 0.115911E+10 |
May | 0.862247E+09 | 36564166.26 | 0.825683E+09 | 0.647010E+09 | 0.711406E+09 |
June | 0.100365E+10 | 85435496.14 | 0.918211E+09 | 0.105716E+10 | 0.451084E+09 |
July | 0.962049E+09 | 62102441.67 | 0.899947E+09 | 0.120655E+10 | 0.329695E+09 |
August | 0.832440E+09 | 12663767.05 | 0.819776E+09 | 0.961705E+09 | 0.463819E+09 |
September | 0.613069E+09 | 127369.21 | 0.612942E+09 | 0.504937E+09 | 0.759644E+09 |
October | 0.473572E+09 | 0.00 | 0.473572E+09 | 0.159874E+09 | 0.129702E+10 |
November | 0.307963E+09 | 0.00 | 0.307963E+09 | 37362457.46 | 0.167066E+10 |
December | 0.295005E+09 | 0.00 | 0.295005E+09 | 862460.94 | 0.261074E+10 |
Annual Sum or Average | 0.739944E+10 | 0.199759E+09 | 0.719968E+10 | 0.503760E+10 | 0.162448E+11 |
Minimum of Months | 0.295005E+09 | 0.00 | 0.295005E+09 | 0.00 | 0.329695E+09 |
Maximum of Months | 0.100365E+10 | 85435496.14 | 0.918211E+09 | 0.120655E+10 | 0.269324E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315200E+09 | 0.00 | 0.315200E+09 | 0.00 | 0.269341E+10 |
February | 0.433771E+09 | 0.00 | 0.433771E+09 | 2693642.08 | 0.231165E+10 |
March | 0.582405E+09 | 0.00 | 0.582405E+09 | 0.139525E+09 | 0.178698E+10 |
April | 0.718164E+09 | 2865736.29 | 0.715299E+09 | 0.319930E+09 | 0.115918E+10 |
May | 0.862288E+09 | 36565578.12 | 0.825722E+09 | 0.647037E+09 | 0.711450E+09 |
June | 0.100369E+10 | 85438795.09 | 0.918255E+09 | 0.105721E+10 | 0.451111E+09 |
July | 0.962095E+09 | 62104839.66 | 0.899990E+09 | 0.120660E+10 | 0.329713E+09 |
August | 0.832479E+09 | 12664256.04 | 0.819815E+09 | 0.961751E+09 | 0.463847E+09 |
September | 0.613098E+09 | 127374.13 | 0.612971E+09 | 0.504958E+09 | 0.759690E+09 |
October | 0.473594E+09 | 0.00 | 0.473594E+09 | 0.159878E+09 | 0.129710E+10 |
November | 0.307977E+09 | 0.00 | 0.307977E+09 | 37363194.67 | 0.167077E+10 |
December | 0.295018E+09 | 0.00 | 0.295018E+09 | 862443.79 | 0.261091E+10 |
Annual Sum or Average | 0.739978E+10 | 0.199767E+09 | 0.720002E+10 | 0.503781E+10 | 0.162458E+11 |
Minimum of Months | 0.295018E+09 | 0.00 | 0.295018E+09 | 0.00 | 0.329713E+09 |
Maximum of Months | 0.100369E+10 | 85438795.09 | 0.918255E+09 | 0.120660E+10 | 0.269341E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315200E+09 | 0.00 | 0.315200E+09 | 0.00 | 0.269341E+10 |
February | 0.433771E+09 | 0.00 | 0.433771E+09 | 2693642.08 | 0.231165E+10 |
March | 0.582405E+09 | 0.00 | 0.582405E+09 | 0.139525E+09 | 0.178698E+10 |
April | 0.718164E+09 | 2865736.29 | 0.715299E+09 | 0.319930E+09 | 0.115918E+10 |
May | 0.862288E+09 | 36565578.12 | 0.825722E+09 | 0.647037E+09 | 0.711450E+09 |
June | 0.100369E+10 | 85438795.09 | 0.918255E+09 | 0.105721E+10 | 0.451111E+09 |
July | 0.962095E+09 | 62104839.66 | 0.899990E+09 | 0.120660E+10 | 0.329713E+09 |
August | 0.832479E+09 | 12664256.04 | 0.819815E+09 | 0.961751E+09 | 0.463847E+09 |
September | 0.613098E+09 | 127374.13 | 0.612971E+09 | 0.504958E+09 | 0.759690E+09 |
October | 0.473594E+09 | 0.00 | 0.473594E+09 | 0.159878E+09 | 0.129710E+10 |
November | 0.307977E+09 | 0.00 | 0.307977E+09 | 37363194.67 | 0.167077E+10 |
December | 0.295018E+09 | 0.00 | 0.295018E+09 | 862443.79 | 0.261091E+10 |
Annual Sum or Average | 0.739978E+10 | 0.199767E+09 | 0.720002E+10 | 0.503781E+10 | 0.162458E+11 |
Minimum of Months | 0.295018E+09 | 0.00 | 0.295018E+09 | 0.00 | 0.329713E+09 |
Maximum of Months | 0.100369E+10 | 85438795.09 | 0.918255E+09 | 0.120660E+10 | 0.269341E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110977E+10 | 0.357851E+09 | 0.751916E+09 | 0.301820E+09 | 0.470025E+10 |
February | 0.147078E+10 | 0.441345E+09 | 0.102944E+10 | 0.512078E+09 | 0.404341E+10 |
March | 0.233666E+10 | 0.978578E+09 | 0.135808E+10 | 0.161925E+10 | 0.312507E+10 |
April | 0.299295E+10 | 0.132245E+10 | 0.167050E+10 | 0.259880E+10 | 0.212228E+10 |
May | 0.346495E+10 | 0.153273E+10 | 0.193222E+10 | 0.362850E+10 | 0.144187E+10 |
June | 0.374493E+10 | 0.165508E+10 | 0.208986E+10 | 0.445228E+10 | 0.930943E+09 |
July | 0.371599E+10 | 0.163610E+10 | 0.207989E+10 | 0.483659E+10 | 0.676789E+09 |
August | 0.335595E+10 | 0.140864E+10 | 0.194730E+10 | 0.422072E+10 | 0.924753E+09 |
September | 0.270264E+10 | 0.119879E+10 | 0.150385E+10 | 0.296065E+10 | 0.144403E+10 |
October | 0.189510E+10 | 0.783864E+09 | 0.111124E+10 | 0.148350E+10 | 0.237588E+10 |
November | 0.104026E+10 | 0.333703E+09 | 0.706556E+09 | 0.522420E+09 | 0.306327E+10 |
December | 0.865377E+09 | 0.178805E+09 | 0.686571E+09 | 0.141118E+09 | 0.473350E+10 |
Annual Sum or Average | 0.286954E+11 | 0.118279E+11 | 0.168674E+11 | 0.272777E+11 | 0.295821E+11 |
Minimum of Months | 0.865377E+09 | 0.178805E+09 | 0.686571E+09 | 0.141118E+09 | 0.676789E+09 |
Maximum of Months | 0.374493E+10 | 0.165508E+10 | 0.208986E+10 | 0.483659E+10 | 0.473350E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43879161.13 | 14149094.21 | 29730066.92 | 11933681.78 | 0.185844E+09 |
February | 58153370.33 | 17450394.47 | 40702975.86 | 20247101.25 | 0.159873E+09 |
March | 92389391.59 | 38692104.70 | 53697286.89 | 64023761.29 | 0.123562E+09 |
April | 0.118339E+09 | 52288347.32 | 66050216.62 | 0.102754E+09 | 83913124.88 |
May | 0.137001E+09 | 60602879.90 | 76398102.47 | 0.143467E+09 | 57010163.01 |
June | 0.148071E+09 | 65440254.51 | 82631072.63 | 0.176039E+09 | 36808635.30 |
July | 0.146927E+09 | 64689881.98 | 82237012.77 | 0.191234E+09 | 26759645.34 |
August | 0.132691E+09 | 55696498.23 | 76994643.35 | 0.166884E+09 | 36563888.77 |
September | 0.106860E+09 | 47399024.44 | 59461042.73 | 0.117061E+09 | 57095526.52 |
October | 74930527.44 | 30993285.40 | 43937242.05 | 58656123.35 | 93940287.06 |
November | 41130900.35 | 13194318.65 | 27936581.71 | 20656017.34 | 0.121119E+09 |
December | 34216213.26 | 7069807.40 | 27146405.86 | 5579687.66 | 0.187158E+09 |
Annual Sum or Average | 0.113459E+10 | 0.467666E+09 | 0.666923E+09 | 0.107854E+10 | 0.116965E+10 |
Minimum of Months | 34216213.26 | 7069807.40 | 27146405.86 | 5579687.66 | 26759645.34 |
Maximum of Months | 0.148071E+09 | 65440254.51 | 82631072.63 | 0.191234E+09 | 0.187158E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135536E+10 | 0.791162E+09 | 0.564197E+09 | 0.963614E+09 | 0.223773E+10 |
February | 0.139772E+10 | 0.673969E+09 | 0.723755E+09 | 0.955992E+09 | 0.197833E+10 |
March | 0.188880E+10 | 0.106130E+10 | 0.827499E+09 | 0.171523E+10 | 0.160494E+10 |
April | 0.151377E+10 | 0.604904E+09 | 0.908865E+09 | 0.146344E+10 | 0.120054E+10 |
May | 0.136884E+10 | 0.397567E+09 | 0.971274E+09 | 0.148572E+10 | 0.807550E+09 |
June | 0.128717E+10 | 0.272756E+09 | 0.101441E+10 | 0.158394E+10 | 0.513057E+09 |
July | 0.135779E+10 | 0.329442E+09 | 0.102835E+10 | 0.187776E+10 | 0.376676E+09 |
August | 0.152434E+10 | 0.494227E+09 | 0.103011E+10 | 0.204892E+10 | 0.514644E+09 |
September | 0.171518E+10 | 0.835416E+09 | 0.879761E+09 | 0.207676E+10 | 0.811479E+09 |
October | 0.169588E+10 | 0.968714E+09 | 0.727161E+09 | 0.171437E+10 | 0.126290E+10 |
November | 0.117537E+10 | 0.663535E+09 | 0.511836E+09 | 0.101395E+10 | 0.156588E+10 |
December | 0.113335E+10 | 0.586558E+09 | 0.546790E+09 | 0.744058E+09 | 0.225532E+10 |
Annual Sum or Average | 0.174136E+11 | 0.767955E+10 | 0.973401E+10 | 0.176437E+11 | 0.151290E+11 |
Minimum of Months | 0.113335E+10 | 0.272756E+09 | 0.511836E+09 | 0.744058E+09 | 0.376676E+09 |
Maximum of Months | 0.188880E+10 | 0.106130E+10 | 0.103011E+10 | 0.207676E+10 | 0.225532E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135536E+10 | 0.791162E+09 | 0.564197E+09 | 0.963614E+09 | 0.223773E+10 |
February | 0.139772E+10 | 0.673969E+09 | 0.723755E+09 | 0.955992E+09 | 0.197833E+10 |
March | 0.188880E+10 | 0.106130E+10 | 0.827499E+09 | 0.171523E+10 | 0.160494E+10 |
April | 0.151377E+10 | 0.604904E+09 | 0.908865E+09 | 0.146344E+10 | 0.120054E+10 |
May | 0.136884E+10 | 0.397567E+09 | 0.971274E+09 | 0.148572E+10 | 0.807550E+09 |
June | 0.128717E+10 | 0.272756E+09 | 0.101441E+10 | 0.158394E+10 | 0.513057E+09 |
July | 0.135779E+10 | 0.329442E+09 | 0.102835E+10 | 0.187776E+10 | 0.376676E+09 |
August | 0.152434E+10 | 0.494227E+09 | 0.103011E+10 | 0.204892E+10 | 0.514644E+09 |
September | 0.171518E+10 | 0.835416E+09 | 0.879761E+09 | 0.207676E+10 | 0.811479E+09 |
October | 0.169588E+10 | 0.968714E+09 | 0.727161E+09 | 0.171437E+10 | 0.126290E+10 |
November | 0.117537E+10 | 0.663535E+09 | 0.511836E+09 | 0.101395E+10 | 0.156588E+10 |
December | 0.113335E+10 | 0.586558E+09 | 0.546790E+09 | 0.744058E+09 | 0.225532E+10 |
Annual Sum or Average | 0.174136E+11 | 0.767955E+10 | 0.973401E+10 | 0.176437E+11 | 0.151290E+11 |
Minimum of Months | 0.113335E+10 | 0.272756E+09 | 0.511836E+09 | 0.744058E+09 | 0.376676E+09 |
Maximum of Months | 0.188880E+10 | 0.106130E+10 | 0.103011E+10 | 0.207676E+10 | 0.225532E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135527E+10 | 0.791112E+09 | 0.564161E+09 | 0.963553E+09 | 0.223759E+10 |
February | 0.139764E+10 | 0.673926E+09 | 0.723709E+09 | 0.955932E+09 | 0.197820E+10 |
March | 0.188868E+10 | 0.106124E+10 | 0.827447E+09 | 0.171512E+10 | 0.160484E+10 |
April | 0.151367E+10 | 0.604866E+09 | 0.908808E+09 | 0.146334E+10 | 0.120047E+10 |
May | 0.136875E+10 | 0.397542E+09 | 0.971213E+09 | 0.148562E+10 | 0.807499E+09 |
June | 0.128709E+10 | 0.272738E+09 | 0.101435E+10 | 0.158384E+10 | 0.513025E+09 |
July | 0.135770E+10 | 0.329421E+09 | 0.102828E+10 | 0.187764E+10 | 0.376652E+09 |
August | 0.152424E+10 | 0.494196E+09 | 0.103005E+10 | 0.204879E+10 | 0.514611E+09 |
September | 0.171507E+10 | 0.835364E+09 | 0.879706E+09 | 0.207663E+10 | 0.811428E+09 |
October | 0.169577E+10 | 0.968653E+09 | 0.727115E+09 | 0.171427E+10 | 0.126282E+10 |
November | 0.117530E+10 | 0.663493E+09 | 0.511804E+09 | 0.101388E+10 | 0.156578E+10 |
December | 0.113328E+10 | 0.586521E+09 | 0.546756E+09 | 0.744011E+09 | 0.225518E+10 |
Annual Sum or Average | 0.174125E+11 | 0.767907E+10 | 0.973340E+10 | 0.176426E+11 | 0.151281E+11 |
Minimum of Months | 0.113328E+10 | 0.272738E+09 | 0.511804E+09 | 0.744011E+09 | 0.376652E+09 |
Maximum of Months | 0.188868E+10 | 0.106124E+10 | 0.103005E+10 | 0.207663E+10 | 0.225518E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.952160E+09 | 0.223530E+09 | 0.728630E+09 | 0.185628E+09 | 0.491701E+10 |
February | 0.139385E+10 | 0.358229E+09 | 0.103562E+10 | 0.431976E+09 | 0.419690E+10 |
March | 0.241867E+10 | 0.103562E+10 | 0.138305E+10 | 0.172695E+10 | 0.321704E+10 |
April | 0.286581E+10 | 0.117510E+10 | 0.169071E+10 | 0.251606E+10 | 0.224478E+10 |
May | 0.349337E+10 | 0.157878E+10 | 0.191459E+10 | 0.372293E+10 | 0.155172E+10 |
June | 0.407889E+10 | 0.191854E+10 | 0.216035E+10 | 0.494621E+10 | 0.104857E+10 |
July | 0.376824E+10 | 0.165213E+10 | 0.211612E+10 | 0.495383E+10 | 0.771267E+09 |
August | 0.340815E+10 | 0.144918E+10 | 0.195897E+10 | 0.436760E+10 | 0.100528E+10 |
September | 0.259012E+10 | 0.111856E+10 | 0.147156E+10 | 0.287463E+10 | 0.152926E+10 |
October | 0.173501E+10 | 0.611169E+09 | 0.112384E+10 | 0.133830E+10 | 0.246775E+10 |
November | 0.995005E+09 | 0.286725E+09 | 0.708280E+09 | 0.484876E+09 | 0.313359E+10 |
December | 0.891333E+09 | 0.194212E+09 | 0.697122E+09 | 0.173513E+09 | 0.481662E+10 |
Annual Sum or Average | 0.285906E+11 | 0.116018E+11 | 0.169888E+11 | 0.277225E+11 | 0.308998E+11 |
Minimum of Months | 0.891333E+09 | 0.194212E+09 | 0.697122E+09 | 0.173513E+09 | 0.771267E+09 |
Maximum of Months | 0.407889E+10 | 0.191854E+10 | 0.216035E+10 | 0.495383E+10 | 0.491701E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37647536.09 | 8838166.42 | 28809369.66 | 7339563.48 | 0.194414E+09 |
February | 55111504.45 | 14164060.65 | 40947443.80 | 17079926.34 | 0.165942E+09 |
March | 95632162.24 | 40947462.25 | 54684699.98 | 68281996.43 | 0.127199E+09 |
April | 0.113312E+09 | 46462320.34 | 66849262.95 | 99482707.66 | 88756515.76 |
May | 0.138125E+09 | 62423458.46 | 75701256.79 | 0.147201E+09 | 61353431.75 |
June | 0.161276E+09 | 75857480.60 | 85418329.45 | 0.195569E+09 | 41459468.48 |
July | 0.148993E+09 | 65323610.92 | 83669288.30 | 0.195870E+09 | 30495201.04 |
August | 0.134755E+09 | 57299240.71 | 77456033.23 | 0.172691E+09 | 39747844.23 |
September | 0.102411E+09 | 44226838.14 | 58184144.83 | 0.113660E+09 | 60465650.30 |
October | 68600629.05 | 24165069.12 | 44435559.93 | 52915334.18 | 97572603.29 |
November | 39341606.19 | 11336847.59 | 28004758.60 | 19171570.00 | 0.123899E+09 |
December | 35242515.49 | 7678951.01 | 27563564.48 | 6860546.02 | 0.190445E+09 |
Annual Sum or Average | 0.113045E+10 | 0.458724E+09 | 0.671724E+09 | 0.109612E+10 | 0.122175E+10 |
Minimum of Months | 35242515.49 | 7678951.01 | 27563564.48 | 6860546.02 | 30495201.04 |
Maximum of Months | 0.161276E+09 | 75857480.60 | 85418329.45 | 0.195870E+09 | 0.194414E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.945592E+09 | 0.00 | 0.945592E+09 | 0.00 | 0.825000E+10 |
February | 0.130130E+10 | 0.00 | 0.130130E+10 | 6225348.92 | 0.712283E+10 |
March | 0.174720E+10 | 0.00 | 0.174720E+10 | 0.351223E+09 | 0.567258E+10 |
April | 0.215447E+10 | 8597147.97 | 0.214587E+10 | 0.807606E+09 | 0.376929E+10 |
May | 0.258684E+10 | 0.109696E+09 | 0.247714E+10 | 0.166465E+10 | 0.243375E+10 |
June | 0.301105E+10 | 0.256315E+09 | 0.275474E+10 | 0.296536E+10 | 0.150080E+10 |
July | 0.288626E+10 | 0.186313E+09 | 0.269994E+10 | 0.349057E+10 | 0.108191E+10 |
August | 0.249741E+10 | 37992498.94 | 0.245942E+10 | 0.280691E+10 | 0.145592E+10 |
September | 0.183928E+10 | 382119.68 | 0.183889E+10 | 0.146530E+10 | 0.230368E+10 |
October | 0.142077E+10 | 0.00 | 0.142077E+10 | 0.465596E+09 | 0.384250E+10 |
November | 0.923923E+09 | 0.00 | 0.923923E+09 | 0.109350E+09 | 0.496691E+10 |
December | 0.885045E+09 | 0.00 | 0.885045E+09 | 2346833.01 | 0.785862E+10 |
Annual Sum or Average | 0.221991E+11 | 0.599295E+09 | 0.215998E+11 | 0.141351E+11 | 0.502588E+11 |
Minimum of Months | 0.885045E+09 | 0.00 | 0.885045E+09 | 0.00 | 0.108191E+10 |
Maximum of Months | 0.301105E+10 | 0.256315E+09 | 0.275474E+10 | 0.349057E+10 | 0.825000E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115360E+10 | 0.371985E+09 | 0.781620E+09 | 0.300113E+09 | 0.496126E+10 |
February | 0.152888E+10 | 0.458777E+09 | 0.107010E+10 | 0.508782E+09 | 0.429792E+10 |
March | 0.242896E+10 | 0.101723E+10 | 0.141173E+10 | 0.158217E+10 | 0.340656E+10 |
April | 0.311118E+10 | 0.137468E+10 | 0.173650E+10 | 0.255261E+10 | 0.233651E+10 |
May | 0.360183E+10 | 0.159327E+10 | 0.200856E+10 | 0.360316E+10 | 0.162955E+10 |
June | 0.389287E+10 | 0.172045E+10 | 0.217243E+10 | 0.452848E+10 | 0.100962E+10 |
July | 0.386279E+10 | 0.170072E+10 | 0.216207E+10 | 0.496006E+10 | 0.721542E+09 |
August | 0.348852E+10 | 0.146428E+10 | 0.202424E+10 | 0.434050E+10 | 0.954411E+09 |
September | 0.280940E+10 | 0.124614E+10 | 0.156327E+10 | 0.304826E+10 | 0.145203E+10 |
October | 0.196996E+10 | 0.814825E+09 | 0.115514E+10 | 0.151714E+10 | 0.239567E+10 |
November | 0.108135E+10 | 0.346883E+09 | 0.734469E+09 | 0.531743E+09 | 0.314270E+10 |
December | 0.899562E+09 | 0.185868E+09 | 0.713694E+09 | 0.142900E+09 | 0.492355E+10 |
Annual Sum or Average | 0.298289E+11 | 0.122951E+11 | 0.175338E+11 | 0.276159E+11 | 0.312313E+11 |
Minimum of Months | 0.899562E+09 | 0.185868E+09 | 0.713694E+09 | 0.142900E+09 | 0.721542E+09 |
Maximum of Months | 0.389287E+10 | 0.172045E+10 | 0.217243E+10 | 0.496006E+10 | 0.496126E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406597E+10 | 0.237342E+10 | 0.169255E+10 | 0.277305E+10 | 0.692633E+10 |
February | 0.419306E+10 | 0.202185E+10 | 0.217121E+10 | 0.270689E+10 | 0.615574E+10 |
March | 0.566626E+10 | 0.318383E+10 | 0.248244E+10 | 0.489036E+10 | 0.501632E+10 |
April | 0.454119E+10 | 0.181466E+10 | 0.272653E+10 | 0.415258E+10 | 0.384297E+10 |
May | 0.410642E+10 | 0.119267E+10 | 0.291375E+10 | 0.418107E+10 | 0.271298E+10 |
June | 0.386141E+10 | 0.818244E+09 | 0.304317E+10 | 0.455159E+10 | 0.168778E+10 |
July | 0.407327E+10 | 0.988299E+09 | 0.308497E+10 | 0.550964E+10 | 0.120434E+10 |
August | 0.457290E+10 | 0.148264E+10 | 0.309026E+10 | 0.606250E+10 | 0.155949E+10 |
September | 0.514540E+10 | 0.250618E+10 | 0.263922E+10 | 0.616701E+10 | 0.236137E+10 |
October | 0.508749E+10 | 0.290606E+10 | 0.218143E+10 | 0.506154E+10 | 0.365839E+10 |
November | 0.352602E+10 | 0.199055E+10 | 0.153547E+10 | 0.298222E+10 | 0.460670E+10 |
December | 0.339996E+10 | 0.175963E+10 | 0.164033E+10 | 0.216100E+10 | 0.687002E+10 |
Annual Sum or Average | 0.522394E+11 | 0.230380E+11 | 0.292013E+11 | 0.511995E+11 | 0.466024E+11 |
Minimum of Months | 0.339996E+10 | 0.818244E+09 | 0.153547E+10 | 0.216100E+10 | 0.120434E+10 |
Maximum of Months | 0.566626E+10 | 0.318383E+10 | 0.309026E+10 | 0.616701E+10 | 0.692633E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.989776E+09 | 0.232359E+09 | 0.757417E+09 | 0.181250E+09 | 0.521945E+10 |
February | 0.144891E+10 | 0.372379E+09 | 0.107653E+10 | 0.421945E+09 | 0.447854E+10 |
March | 0.251422E+10 | 0.107653E+10 | 0.143770E+10 | 0.169716E+10 | 0.349206E+10 |
April | 0.297903E+10 | 0.122151E+10 | 0.175751E+10 | 0.248841E+10 | 0.247173E+10 |
May | 0.363138E+10 | 0.164114E+10 | 0.199024E+10 | 0.371987E+10 | 0.174522E+10 |
June | 0.424003E+10 | 0.199433E+10 | 0.224571E+10 | 0.504895E+10 | 0.112791E+10 |
July | 0.391711E+10 | 0.171739E+10 | 0.219972E+10 | 0.509118E+10 | 0.819940E+09 |
August | 0.354279E+10 | 0.150642E+10 | 0.203637E+10 | 0.450890E+10 | 0.103118E+10 |
September | 0.269244E+10 | 0.116274E+10 | 0.152970E+10 | 0.297439E+10 | 0.154151E+10 |
October | 0.180355E+10 | 0.635310E+09 | 0.116824E+10 | 0.137964E+10 | 0.249265E+10 |
November | 0.103431E+10 | 0.298051E+09 | 0.736263E+09 | 0.496001E+09 | 0.320948E+10 |
December | 0.926546E+09 | 0.201883E+09 | 0.724663E+09 | 0.172979E+09 | 0.502817E+10 |
Annual Sum or Average | 0.297201E+11 | 0.120600E+11 | 0.176601E+11 | 0.281807E+11 | 0.326578E+11 |
Minimum of Months | 0.926546E+09 | 0.201883E+09 | 0.724663E+09 | 0.172979E+09 | 0.819940E+09 |
Maximum of Months | 0.424003E+10 | 0.199433E+10 | 0.224571E+10 | 0.509118E+10 | 0.521945E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.32 | 2980.24 | 353.04 | 0.00 | 353.04 | 0.00 | 0.00 |
February | 3.60 | 2843.76 | 537.91 | 0.00 | 537.91 | 0.00 | 0.00 |
March | 138.37 | 2005.70 | 652.33 | 0.00 | 652.33 | 0.00 | 0.00 |
April | 327.50 | 1356.08 | 831.20 | 3.32 | 827.88 | 0.00 | 0.00 |
May | 642.31 | 840.87 | 965.81 | 40.96 | 924.86 | 0.00 | 0.00 |
June | 1163.33 | 540.43 | 1161.67 | 98.89 | 1062.78 | 0.00 | 0.00 |
July | 1313.14 | 379.44 | 1077.60 | 69.56 | 1008.04 | 0.00 | 0.00 |
August | 1062.93 | 501.80 | 932.43 | 14.18 | 918.24 | 0.00 | 0.00 |
September | 590.78 | 803.64 | 709.60 | 0.15 | 709.45 | 0.00 | 0.00 |
October | 196.35 | 1300.84 | 530.45 | 0.00 | 530.45 | 0.00 | 0.00 |
November | 50.06 | 1762.04 | 356.45 | 0.00 | 356.45 | 0.00 | 0.00 |
December | 1.30 | 2810.54 | 330.44 | 0.00 | 330.44 | 0.00 | 0.00 |
Annual Sum or Average | 460.40 | 1503.82 | 703.93 | 19.00 | 684.93 | 0.00 | 0.00 |
Minimum of Months | 0.32 | 379.44 | 330.44 | 0.00 | 330.44 | 0.00 | 0.00 |
Maximum of Months | 1313.14 | 2980.24 | 1161.67 | 98.89 | 1062.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 115.99 | 1791.87 | 430.71 | 138.88 | 291.82 | 0.00 | 0.00 |
February | 216.29 | 1715.23 | 631.98 | 189.64 | 442.34 | 0.00 | 0.00 |
March | 606.81 | 1199.97 | 906.87 | 379.79 | 527.08 | 0.00 | 0.00 |
April | 1008.04 | 842.36 | 1200.30 | 530.35 | 669.95 | 0.00 | 0.00 |
May | 1358.87 | 571.80 | 1344.77 | 594.86 | 749.91 | 0.00 | 0.00 |
June | 1751.90 | 370.15 | 1501.88 | 663.75 | 838.13 | 0.00 | 0.00 |
July | 1852.29 | 257.49 | 1442.20 | 634.98 | 807.22 | 0.00 | 0.00 |
August | 1625.22 | 336.04 | 1302.46 | 546.70 | 755.76 | 0.00 | 0.00 |
September | 1191.55 | 516.55 | 1083.88 | 480.76 | 603.11 | 0.00 | 0.00 |
October | 594.94 | 811.45 | 735.50 | 304.22 | 431.28 | 0.00 | 0.00 |
November | 218.74 | 1111.16 | 417.19 | 133.83 | 283.36 | 0.00 | 0.00 |
December | 56.74 | 1763.09 | 335.86 | 69.40 | 266.46 | 0.00 | 0.00 |
Annual Sum or Average | 886.85 | 936.76 | 945.87 | 389.88 | 555.99 | 0.00 | 0.00 |
Minimum of Months | 56.74 | 257.49 | 335.86 | 69.40 | 266.46 | 0.00 | 0.00 |
Maximum of Months | 1852.29 | 1791.87 | 1501.88 | 663.75 | 838.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1051.49 | 2485.33 | 1518.06 | 886.13 | 631.92 | 0.00 | 0.00 |
February | 1134.36 | 2446.58 | 1733.24 | 835.75 | 897.49 | 0.00 | 0.00 |
March | 1847.34 | 1759.19 | 2115.54 | 1188.70 | 926.84 | 0.00 | 0.00 |
April | 1622.14 | 1384.02 | 1752.00 | 700.10 | 1051.90 | 0.00 | 0.00 |
May | 1573.56 | 940.81 | 1533.16 | 445.29 | 1087.87 | 0.00 | 0.00 |
June | 1763.05 | 605.52 | 1489.74 | 315.68 | 1174.06 | 0.00 | 0.00 |
July | 2059.05 | 419.94 | 1520.78 | 368.99 | 1151.80 | 0.00 | 0.00 |
August | 2269.09 | 538.40 | 1707.33 | 553.55 | 1153.77 | 0.00 | 0.00 |
September | 2396.87 | 830.10 | 1985.11 | 966.89 | 1018.22 | 0.00 | 0.00 |
October | 1924.16 | 1238.58 | 1899.45 | 1085.00 | 814.45 | 0.00 | 0.00 |
November | 1178.77 | 1631.18 | 1360.35 | 767.96 | 592.39 | 0.00 | 0.00 |
December | 821.80 | 2444.79 | 1269.40 | 656.97 | 612.43 | 0.00 | 0.00 |
Annual Sum or Average | 1639.80 | 1388.13 | 1656.50 | 730.53 | 925.97 | 0.00 | 0.00 |
Minimum of Months | 821.80 | 419.94 | 1269.40 | 315.68 | 592.39 | 0.00 | 0.00 |
Maximum of Months | 2396.87 | 2485.33 | 2115.54 | 1188.70 | 1174.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 69.23 | 1885.22 | 369.54 | 86.75 | 282.79 | 0.00 | 0.00 |
February | 175.70 | 1787.54 | 598.92 | 153.93 | 445.00 | 0.00 | 0.00 |
March | 638.54 | 1230.76 | 938.70 | 401.93 | 536.77 | 0.00 | 0.00 |
April | 966.09 | 891.37 | 1149.32 | 471.26 | 678.05 | 0.00 | 0.00 |
May | 1391.05 | 609.33 | 1355.80 | 612.73 | 743.07 | 0.00 | 0.00 |
June | 1946.09 | 408.77 | 1635.82 | 769.42 | 866.40 | 0.00 | 0.00 |
July | 1897.15 | 289.04 | 1462.48 | 641.20 | 821.28 | 0.00 | 0.00 |
August | 1684.92 | 359.62 | 1322.73 | 562.43 | 760.29 | 0.00 | 0.00 |
September | 1156.45 | 545.28 | 1038.75 | 448.59 | 590.16 | 0.00 | 0.00 |
October | 529.30 | 848.15 | 673.37 | 237.20 | 436.17 | 0.00 | 0.00 |
November | 198.92 | 1139.76 | 399.04 | 114.99 | 284.05 | 0.00 | 0.00 |
December | 66.33 | 1799.30 | 345.93 | 75.37 | 270.56 | 0.00 | 0.00 |
Annual Sum or Average | 897.31 | 978.82 | 942.42 | 382.42 | 560.00 | 0.00 | 0.00 |
Minimum of Months | 66.33 | 289.04 | 345.93 | 75.37 | 270.56 | 0.00 | 0.00 |
Maximum of Months | 1946.09 | 1885.22 | 1635.82 | 769.42 | 866.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3016.75 | 353.04 | 0.00 | 353.04 | 0.00 | 0.00 |
February | 3.34 | 2866.56 | 537.90 | 0.00 | 537.90 | 0.00 | 0.00 |
March | 156.28 | 2001.50 | 652.32 | 0.00 | 652.32 | 0.00 | 0.00 |
April | 370.29 | 1341.62 | 831.20 | 3.32 | 827.88 | 0.00 | 0.00 |
May | 724.72 | 796.86 | 965.81 | 40.96 | 924.85 | 0.00 | 0.00 |
June | 1223.60 | 522.11 | 1161.66 | 98.89 | 1062.78 | 0.00 | 0.00 |
July | 1351.46 | 369.30 | 1077.60 | 69.56 | 1008.04 | 0.00 | 0.00 |
August | 1077.21 | 519.53 | 932.42 | 14.18 | 918.24 | 0.00 | 0.00 |
September | 584.43 | 879.25 | 709.59 | 0.15 | 709.45 | 0.00 | 0.00 |
October | 179.07 | 1452.82 | 530.45 | 0.00 | 530.45 | 0.00 | 0.00 |
November | 43.24 | 1933.72 | 356.45 | 0.00 | 356.45 | 0.00 | 0.00 |
December | 0.97 | 2924.34 | 330.44 | 0.00 | 330.44 | 0.00 | 0.00 |
Annual Sum or Average | 479.24 | 1545.42 | 703.93 | 19.00 | 684.92 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 369.30 | 330.44 | 0.00 | 330.44 | 0.00 | 0.00 |
Maximum of Months | 1351.46 | 3016.75 | 1161.66 | 98.89 | 1062.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 117.14 | 1824.26 | 430.72 | 138.89 | 291.83 | 0.00 | 0.00 |
February | 220.04 | 1737.47 | 632.00 | 189.65 | 442.35 | 0.00 | 0.00 |
March | 628.46 | 1212.90 | 906.90 | 379.81 | 527.10 | 0.00 | 0.00 |
April | 1042.27 | 851.16 | 1200.34 | 530.38 | 669.97 | 0.00 | 0.00 |
May | 1408.29 | 559.62 | 1344.81 | 594.88 | 749.93 | 0.00 | 0.00 |
June | 1785.62 | 373.36 | 1501.93 | 663.78 | 838.15 | 0.00 | 0.00 |
July | 1877.17 | 262.68 | 1442.25 | 635.00 | 807.25 | 0.00 | 0.00 |
August | 1638.14 | 358.91 | 1302.51 | 546.72 | 755.79 | 0.00 | 0.00 |
September | 1187.39 | 579.14 | 1083.91 | 480.78 | 603.13 | 0.00 | 0.00 |
October | 575.77 | 922.13 | 735.52 | 304.23 | 431.29 | 0.00 | 0.00 |
November | 209.52 | 1228.54 | 417.20 | 133.83 | 283.37 | 0.00 | 0.00 |
December | 54.77 | 1837.16 | 335.87 | 69.40 | 266.47 | 0.00 | 0.00 |
Annual Sum or Average | 899.17 | 975.13 | 945.90 | 389.89 | 556.01 | 0.00 | 0.00 |
Minimum of Months | 54.77 | 262.68 | 335.87 | 69.40 | 266.47 | 0.00 | 0.00 |
Maximum of Months | 1877.17 | 1837.16 | 1501.93 | 663.78 | 838.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1079.29 | 2506.37 | 1518.07 | 886.14 | 631.93 | 0.00 | 0.00 |
February | 1185.48 | 2453.23 | 1733.25 | 835.76 | 897.49 | 0.00 | 0.00 |
March | 1921.14 | 1797.62 | 2115.55 | 1188.71 | 926.84 | 0.00 | 0.00 |
April | 1693.76 | 1389.49 | 1752.01 | 700.11 | 1051.91 | 0.00 | 0.00 |
May | 1664.07 | 904.49 | 1533.17 | 445.29 | 1087.87 | 0.00 | 0.00 |
June | 1833.22 | 593.80 | 1489.75 | 315.68 | 1174.06 | 0.00 | 0.00 |
July | 2103.18 | 421.89 | 1520.79 | 368.99 | 1151.80 | 0.00 | 0.00 |
August | 2294.88 | 576.43 | 1707.33 | 553.56 | 1153.78 | 0.00 | 0.00 |
September | 2403.60 | 939.19 | 1985.12 | 966.90 | 1018.22 | 0.00 | 0.00 |
October | 1920.18 | 1414.51 | 1899.46 | 1085.01 | 814.45 | 0.00 | 0.00 |
November | 1173.53 | 1812.32 | 1360.35 | 767.96 | 592.39 | 0.00 | 0.00 |
December | 833.38 | 2526.07 | 1269.41 | 656.97 | 612.43 | 0.00 | 0.00 |
Annual Sum or Average | 1678.40 | 1439.19 | 1656.51 | 730.54 | 925.97 | 0.00 | 0.00 |
Minimum of Months | 833.38 | 421.89 | 1269.41 | 315.68 | 592.39 | 0.00 | 0.00 |
Maximum of Months | 2403.60 | 2526.07 | 2115.55 | 1188.71 | 1174.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 72.05 | 1908.39 | 369.55 | 86.76 | 282.80 | 0.00 | 0.00 |
February | 185.62 | 1803.42 | 598.94 | 153.93 | 445.01 | 0.00 | 0.00 |
March | 670.26 | 1248.60 | 938.73 | 401.94 | 536.79 | 0.00 | 0.00 |
April | 1009.08 | 900.28 | 1149.35 | 471.28 | 678.07 | 0.00 | 0.00 |
May | 1444.94 | 602.25 | 1355.84 | 612.75 | 743.09 | 0.00 | 0.00 |
June | 1983.71 | 420.54 | 1635.87 | 769.44 | 866.42 | 0.00 | 0.00 |
July | 1922.68 | 299.34 | 1462.53 | 641.22 | 821.31 | 0.00 | 0.00 |
August | 1695.15 | 390.17 | 1322.77 | 562.45 | 760.32 | 0.00 | 0.00 |
September | 1152.89 | 613.32 | 1038.78 | 448.61 | 590.18 | 0.00 | 0.00 |
October | 519.42 | 957.78 | 673.39 | 237.21 | 436.18 | 0.00 | 0.00 |
November | 194.46 | 1256.75 | 399.05 | 114.99 | 284.06 | 0.00 | 0.00 |
December | 67.34 | 1869.42 | 345.94 | 75.38 | 270.57 | 0.00 | 0.00 |
Annual Sum or Average | 913.83 | 1018.57 | 942.45 | 382.44 | 560.01 | 0.00 | 0.00 |
Minimum of Months | 67.34 | 299.34 | 345.94 | 75.38 | 270.57 | 0.00 | 0.00 |
Maximum of Months | 1983.71 | 1908.39 | 1635.87 | 769.44 | 866.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3080.20 | 353.04 | 0.00 | 353.04 | 0.00 | 0.00 |
February | 2.57 | 2944.29 | 537.91 | 0.00 | 537.91 | 0.00 | 0.00 |
March | 131.13 | 2117.90 | 652.33 | 0.00 | 652.33 | 0.00 | 0.00 |
April | 311.58 | 1454.20 | 831.20 | 3.32 | 827.88 | 0.00 | 0.00 |
May | 621.51 | 908.66 | 965.81 | 40.96 | 924.86 | 0.00 | 0.00 |
June | 1144.04 | 579.01 | 1161.67 | 98.89 | 1062.78 | 0.00 | 0.00 |
July | 1303.23 | 403.94 | 1077.60 | 69.56 | 1008.04 | 0.00 | 0.00 |
August | 1047.98 | 543.58 | 932.43 | 14.18 | 918.24 | 0.00 | 0.00 |
September | 565.31 | 888.77 | 709.60 | 0.15 | 709.45 | 0.00 | 0.00 |
October | 173.83 | 1434.63 | 530.45 | 0.00 | 530.45 | 0.00 | 0.00 |
November | 42.19 | 1916.24 | 356.45 | 0.00 | 356.45 | 0.00 | 0.00 |
December | 0.88 | 2934.07 | 330.44 | 0.00 | 330.44 | 0.00 | 0.00 |
Annual Sum or Average | 448.22 | 1593.70 | 703.93 | 19.00 | 684.93 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 403.94 | 330.44 | 0.00 | 330.44 | 0.00 | 0.00 |
Maximum of Months | 1303.23 | 3080.20 | 1161.67 | 98.89 | 1062.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 112.05 | 1852.32 | 430.71 | 138.88 | 291.82 | 0.00 | 0.00 |
February | 210.31 | 1776.59 | 631.98 | 189.64 | 442.34 | 0.00 | 0.00 |
March | 590.72 | 1271.86 | 906.87 | 379.79 | 527.08 | 0.00 | 0.00 |
April | 984.80 | 901.43 | 1200.30 | 530.35 | 669.95 | 0.00 | 0.00 |
May | 1345.27 | 608.40 | 1344.77 | 594.86 | 749.91 | 0.00 | 0.00 |
June | 1747.10 | 389.52 | 1501.88 | 663.75 | 838.13 | 0.00 | 0.00 |
July | 1851.87 | 269.39 | 1442.20 | 634.98 | 807.22 | 0.00 | 0.00 |
August | 1620.56 | 356.34 | 1302.46 | 546.70 | 755.76 | 0.00 | 0.00 |
September | 1176.03 | 560.20 | 1083.88 | 480.76 | 603.11 | 0.00 | 0.00 |
October | 566.43 | 894.44 | 735.50 | 304.22 | 431.28 | 0.00 | 0.00 |
November | 205.15 | 1212.46 | 417.19 | 133.83 | 283.36 | 0.00 | 0.00 |
December | 53.35 | 1838.24 | 335.86 | 69.40 | 266.46 | 0.00 | 0.00 |
Annual Sum or Average | 875.70 | 990.34 | 945.87 | 389.88 | 555.99 | 0.00 | 0.00 |
Minimum of Months | 53.35 | 269.39 | 335.86 | 69.40 | 266.46 | 0.00 | 0.00 |
Maximum of Months | 1851.87 | 1852.32 | 1501.88 | 663.75 | 838.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1035.34 | 2585.99 | 1518.06 | 886.13 | 631.92 | 0.00 | 0.00 |
February | 1118.92 | 2544.54 | 1733.24 | 835.75 | 897.49 | 0.00 | 0.00 |
March | 1825.85 | 1872.88 | 2115.54 | 1188.70 | 926.84 | 0.00 | 0.00 |
April | 1602.08 | 1482.63 | 1752.00 | 700.10 | 1051.90 | 0.00 | 0.00 |
May | 1561.03 | 1012.91 | 1533.16 | 445.29 | 1087.87 | 0.00 | 0.00 |
June | 1756.02 | 651.15 | 1489.74 | 315.68 | 1174.06 | 0.00 | 0.00 |
July | 2057.06 | 449.65 | 1520.78 | 368.99 | 1151.80 | 0.00 | 0.00 |
August | 2263.48 | 582.25 | 1707.33 | 553.55 | 1153.77 | 0.00 | 0.00 |
September | 2379.25 | 911.02 | 1985.11 | 966.89 | 1018.22 | 0.00 | 0.00 |
October | 1889.76 | 1365.89 | 1899.45 | 1085.00 | 814.45 | 0.00 | 0.00 |
November | 1150.55 | 1777.28 | 1360.35 | 767.96 | 592.39 | 0.00 | 0.00 |
December | 806.82 | 2564.97 | 1269.40 | 656.97 | 612.43 | 0.00 | 0.00 |
Annual Sum or Average | 1623.52 | 1477.75 | 1656.50 | 730.53 | 925.97 | 0.00 | 0.00 |
Minimum of Months | 806.82 | 449.65 | 1269.40 | 315.68 | 592.39 | 0.00 | 0.00 |
Maximum of Months | 2379.25 | 2585.99 | 2115.54 | 1188.70 | 1174.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 67.67 | 1948.72 | 369.54 | 86.75 | 282.79 | 0.00 | 0.00 |
February | 174.42 | 1851.25 | 598.92 | 153.93 | 445.00 | 0.00 | 0.00 |
March | 633.65 | 1303.79 | 938.70 | 401.93 | 536.77 | 0.00 | 0.00 |
April | 960.04 | 953.60 | 1149.32 | 471.26 | 678.05 | 0.00 | 0.00 |
May | 1388.84 | 651.59 | 1355.80 | 612.73 | 743.07 | 0.00 | 0.00 |
June | 1947.90 | 435.15 | 1635.82 | 769.42 | 866.40 | 0.00 | 0.00 |
July | 1900.83 | 306.13 | 1462.48 | 641.20 | 821.28 | 0.00 | 0.00 |
August | 1683.43 | 385.00 | 1322.73 | 562.43 | 760.29 | 0.00 | 0.00 |
September | 1147.53 | 594.72 | 1038.75 | 448.59 | 590.16 | 0.00 | 0.00 |
October | 515.10 | 930.65 | 673.37 | 237.20 | 436.17 | 0.00 | 0.00 |
November | 191.36 | 1238.22 | 399.04 | 114.99 | 284.05 | 0.00 | 0.00 |
December | 64.58 | 1877.31 | 345.93 | 75.37 | 270.56 | 0.00 | 0.00 |
Annual Sum or Average | 893.60 | 1035.57 | 942.42 | 382.42 | 560.00 | 0.00 | 0.00 |
Minimum of Months | 64.58 | 306.13 | 345.93 | 75.37 | 270.56 | 0.00 | 0.00 |
Maximum of Months | 1947.90 | 1948.72 | 1635.82 | 769.42 | 866.40 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 847413.88 | 0.798229E+10 | 0.945592E+09 | 0.00 | 0.945592E+09 | 0.00 | 0.00 |
February | 8707757.73 | 0.687961E+10 | 0.130130E+10 | 0.00 | 0.130130E+10 | 0.00 | 0.00 |
March | 0.370601E+09 | 0.537208E+10 | 0.174720E+10 | 0.00 | 0.174720E+10 | 0.00 | 0.00 |
April | 0.848881E+09 | 0.351497E+10 | 0.215447E+10 | 8597147.97 | 0.214587E+10 | 0.00 | 0.00 |
May | 0.172035E+10 | 0.225218E+10 | 0.258684E+10 | 0.109696E+09 | 0.247714E+10 | 0.00 | 0.00 |
June | 0.301536E+10 | 0.140081E+10 | 0.301105E+10 | 0.256315E+09 | 0.275474E+10 | 0.00 | 0.00 |
July | 0.351712E+10 | 0.101630E+10 | 0.288626E+10 | 0.186313E+09 | 0.269994E+10 | 0.00 | 0.00 |
August | 0.284695E+10 | 0.134403E+10 | 0.249741E+10 | 37992498.94 | 0.245942E+10 | 0.00 | 0.00 |
September | 0.153131E+10 | 0.208303E+10 | 0.183928E+10 | 382119.68 | 0.183889E+10 | 0.00 | 0.00 |
October | 0.525893E+09 | 0.348418E+10 | 0.142077E+10 | 0.00 | 0.142077E+10 | 0.00 | 0.00 |
November | 0.129754E+09 | 0.456722E+10 | 0.923923E+09 | 0.00 | 0.923923E+09 | 0.00 | 0.00 |
December | 3494867.60 | 0.752776E+10 | 0.885045E+09 | 0.00 | 0.885045E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.145193E+11 | 0.474244E+11 | 0.221991E+11 | 0.599295E+09 | 0.215998E+11 | 0.00 | 0.00 |
Minimum of Months | 847413.88 | 0.101630E+10 | 0.885045E+09 | 0.00 | 0.885045E+09 | 0.00 | 0.00 |
Maximum of Months | 0.351712E+10 | 0.798229E+10 | 0.301105E+10 | 0.256315E+09 | 0.275474E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.310668E+09 | 0.479934E+10 | 0.115360E+10 | 0.371985E+09 | 0.781620E+09 | 0.00 | 0.00 |
February | 0.523250E+09 | 0.414949E+10 | 0.152888E+10 | 0.458777E+09 | 0.107010E+10 | 0.00 | 0.00 |
March | 0.162529E+10 | 0.321401E+10 | 0.242896E+10 | 0.101723E+10 | 0.141173E+10 | 0.00 | 0.00 |
April | 0.261283E+10 | 0.218339E+10 | 0.311118E+10 | 0.137468E+10 | 0.173650E+10 | 0.00 | 0.00 |
May | 0.363960E+10 | 0.153151E+10 | 0.360183E+10 | 0.159327E+10 | 0.200856E+10 | 0.00 | 0.00 |
June | 0.454093E+10 | 0.959436E+09 | 0.389287E+10 | 0.172045E+10 | 0.217243E+10 | 0.00 | 0.00 |
July | 0.496116E+10 | 0.689668E+09 | 0.386279E+10 | 0.170072E+10 | 0.216207E+10 | 0.00 | 0.00 |
August | 0.435298E+10 | 0.900039E+09 | 0.348852E+10 | 0.146428E+10 | 0.202424E+10 | 0.00 | 0.00 |
September | 0.308849E+10 | 0.133889E+10 | 0.280940E+10 | 0.124614E+10 | 0.156327E+10 | 0.00 | 0.00 |
October | 0.159350E+10 | 0.217339E+10 | 0.196996E+10 | 0.814825E+09 | 0.115514E+10 | 0.00 | 0.00 |
November | 0.566971E+09 | 0.288012E+10 | 0.108135E+10 | 0.346883E+09 | 0.734469E+09 | 0.00 | 0.00 |
December | 0.151961E+09 | 0.472225E+10 | 0.899562E+09 | 0.185868E+09 | 0.713694E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.279676E+11 | 0.295415E+11 | 0.298289E+11 | 0.122951E+11 | 0.175338E+11 | 0.00 | 0.00 |
Minimum of Months | 0.151961E+09 | 0.689668E+09 | 0.899562E+09 | 0.185868E+09 | 0.713694E+09 | 0.00 | 0.00 |
Maximum of Months | 0.496116E+10 | 0.479934E+10 | 0.389287E+10 | 0.172045E+10 | 0.217243E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.281630E+10 | 0.665671E+10 | 0.406597E+10 | 0.237342E+10 | 0.169255E+10 | 0.00 | 0.00 |
February | 0.274425E+10 | 0.591877E+10 | 0.419306E+10 | 0.202185E+10 | 0.217121E+10 | 0.00 | 0.00 |
March | 0.494793E+10 | 0.471181E+10 | 0.566626E+10 | 0.318383E+10 | 0.248244E+10 | 0.00 | 0.00 |
April | 0.420458E+10 | 0.358737E+10 | 0.454119E+10 | 0.181466E+10 | 0.272653E+10 | 0.00 | 0.00 |
May | 0.421462E+10 | 0.251985E+10 | 0.410642E+10 | 0.119267E+10 | 0.291375E+10 | 0.00 | 0.00 |
June | 0.456984E+10 | 0.156950E+10 | 0.386141E+10 | 0.818244E+09 | 0.304317E+10 | 0.00 | 0.00 |
July | 0.551496E+10 | 0.112478E+10 | 0.407327E+10 | 0.988299E+09 | 0.308497E+10 | 0.00 | 0.00 |
August | 0.607754E+10 | 0.144206E+10 | 0.457290E+10 | 0.148264E+10 | 0.309026E+10 | 0.00 | 0.00 |
September | 0.621268E+10 | 0.215162E+10 | 0.514540E+10 | 0.250618E+10 | 0.263922E+10 | 0.00 | 0.00 |
October | 0.515368E+10 | 0.331741E+10 | 0.508749E+10 | 0.290606E+10 | 0.218143E+10 | 0.00 | 0.00 |
November | 0.305537E+10 | 0.422803E+10 | 0.352602E+10 | 0.199055E+10 | 0.153547E+10 | 0.00 | 0.00 |
December | 0.220112E+10 | 0.654811E+10 | 0.339996E+10 | 0.175963E+10 | 0.164033E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.517129E+11 | 0.437760E+11 | 0.522394E+11 | 0.230380E+11 | 0.292013E+11 | 0.00 | 0.00 |
Minimum of Months | 0.220112E+10 | 0.112478E+10 | 0.339996E+10 | 0.818244E+09 | 0.153547E+10 | 0.00 | 0.00 |
Maximum of Months | 0.621268E+10 | 0.665671E+10 | 0.566626E+10 | 0.318383E+10 | 0.309026E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.185423E+09 | 0.504936E+10 | 0.989776E+09 | 0.232359E+09 | 0.757417E+09 | 0.00 | 0.00 |
February | 0.425055E+09 | 0.432441E+10 | 0.144891E+10 | 0.372379E+09 | 0.107653E+10 | 0.00 | 0.00 |
March | 0.171026E+10 | 0.329646E+10 | 0.251422E+10 | 0.107653E+10 | 0.143770E+10 | 0.00 | 0.00 |
April | 0.250410E+10 | 0.231044E+10 | 0.297903E+10 | 0.122151E+10 | 0.175751E+10 | 0.00 | 0.00 |
May | 0.372578E+10 | 0.163203E+10 | 0.363138E+10 | 0.164114E+10 | 0.199024E+10 | 0.00 | 0.00 |
June | 0.504426E+10 | 0.105954E+10 | 0.424003E+10 | 0.199433E+10 | 0.224571E+10 | 0.00 | 0.00 |
July | 0.508133E+10 | 0.774159E+09 | 0.391711E+10 | 0.171739E+10 | 0.219972E+10 | 0.00 | 0.00 |
August | 0.451289E+10 | 0.963196E+09 | 0.354279E+10 | 0.150642E+10 | 0.203637E+10 | 0.00 | 0.00 |
September | 0.299751E+10 | 0.141338E+10 | 0.269244E+10 | 0.116274E+10 | 0.152970E+10 | 0.00 | 0.00 |
October | 0.141769E+10 | 0.227168E+10 | 0.180355E+10 | 0.635310E+09 | 0.116824E+10 | 0.00 | 0.00 |
November | 0.515613E+09 | 0.295427E+10 | 0.103431E+10 | 0.298051E+09 | 0.736263E+09 | 0.00 | 0.00 |
December | 0.177655E+09 | 0.481925E+10 | 0.926546E+09 | 0.201883E+09 | 0.724663E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.282976E+11 | 0.308682E+11 | 0.297201E+11 | 0.120600E+11 | 0.176601E+11 | 0.00 | 0.00 |
Minimum of Months | 0.177655E+09 | 0.774159E+09 | 0.926546E+09 | 0.201883E+09 | 0.724663E+09 | 0.00 | 0.00 |
Maximum of Months | 0.508133E+10 | 0.504936E+10 | 0.424003E+10 | 0.199433E+10 | 0.224571E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.808006E+10 | 0.945587E+09 | 0.00 | 0.945587E+09 | 0.00 | 0.00 |
February | 8081046.39 | 0.693479E+10 | 0.130129E+10 | 0.00 | 0.130129E+10 | 0.00 | 0.00 |
March | 0.418571E+09 | 0.536083E+10 | 0.174719E+10 | 0.00 | 0.174719E+10 | 0.00 | 0.00 |
April | 0.959779E+09 | 0.347747E+10 | 0.215446E+10 | 8597098.23 | 0.214586E+10 | 0.00 | 0.00 |
May | 0.194108E+10 | 0.213431E+10 | 0.258682E+10 | 0.109695E+09 | 0.247713E+10 | 0.00 | 0.00 |
June | 0.317158E+10 | 0.135330E+10 | 0.301103E+10 | 0.256313E+09 | 0.275472E+10 | 0.00 | 0.00 |
July | 0.361976E+10 | 0.989121E+09 | 0.288624E+10 | 0.186312E+09 | 0.269993E+10 | 0.00 | 0.00 |
August | 0.288521E+10 | 0.139151E+10 | 0.249740E+10 | 37992279.12 | 0.245941E+10 | 0.00 | 0.00 |
September | 0.151485E+10 | 0.227903E+10 | 0.183927E+10 | 382117.47 | 0.183888E+10 | 0.00 | 0.00 |
October | 0.479629E+09 | 0.389122E+10 | 0.142076E+10 | 0.00 | 0.142076E+10 | 0.00 | 0.00 |
November | 0.112089E+09 | 0.501219E+10 | 0.923917E+09 | 0.00 | 0.923917E+09 | 0.00 | 0.00 |
December | 2587348.51 | 0.783255E+10 | 0.885040E+09 | 0.00 | 0.885040E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.151132E+11 | 0.487364E+11 | 0.221990E+11 | 0.599292E+09 | 0.215997E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.989121E+09 | 0.885040E+09 | 0.00 | 0.885040E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361976E+10 | 0.808006E+10 | 0.301103E+10 | 0.256313E+09 | 0.275472E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.313753E+09 | 0.488610E+10 | 0.115365E+10 | 0.372000E+09 | 0.781646E+09 | 0.00 | 0.00 |
February | 0.532325E+09 | 0.420328E+10 | 0.152893E+10 | 0.458796E+09 | 0.107014E+10 | 0.00 | 0.00 |
March | 0.168328E+10 | 0.324863E+10 | 0.242905E+10 | 0.101727E+10 | 0.141178E+10 | 0.00 | 0.00 |
April | 0.270155E+10 | 0.220620E+10 | 0.311129E+10 | 0.137473E+10 | 0.173655E+10 | 0.00 | 0.00 |
May | 0.377196E+10 | 0.149888E+10 | 0.360195E+10 | 0.159334E+10 | 0.200861E+10 | 0.00 | 0.00 |
June | 0.462831E+10 | 0.967751E+09 | 0.389301E+10 | 0.172052E+10 | 0.217249E+10 | 0.00 | 0.00 |
July | 0.502782E+10 | 0.703549E+09 | 0.386292E+10 | 0.170079E+10 | 0.216213E+10 | 0.00 | 0.00 |
August | 0.438760E+10 | 0.961317E+09 | 0.348864E+10 | 0.146434E+10 | 0.202430E+10 | 0.00 | 0.00 |
September | 0.307771E+10 | 0.150112E+10 | 0.280950E+10 | 0.124619E+10 | 0.156332E+10 | 0.00 | 0.00 |
October | 0.154215E+10 | 0.246982E+10 | 0.197003E+10 | 0.814858E+09 | 0.115517E+10 | 0.00 | 0.00 |
November | 0.543076E+09 | 0.318439E+10 | 0.108139E+10 | 0.346897E+09 | 0.734492E+09 | 0.00 | 0.00 |
December | 0.146698E+09 | 0.492066E+10 | 0.899593E+09 | 0.185875E+09 | 0.713718E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.283562E+11 | 0.307517E+11 | 0.298299E+11 | 0.122956E+11 | 0.175343E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146698E+09 | 0.703549E+09 | 0.899593E+09 | 0.185875E+09 | 0.713718E+09 | 0.00 | 0.00 |
Maximum of Months | 0.502782E+10 | 0.492066E+10 | 0.389301E+10 | 0.172052E+10 | 0.217249E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289078E+10 | 0.671305E+10 | 0.406599E+10 | 0.237343E+10 | 0.169255E+10 | 0.00 | 0.00 |
February | 0.286792E+10 | 0.593486E+10 | 0.419308E+10 | 0.202186E+10 | 0.217122E+10 | 0.00 | 0.00 |
March | 0.514559E+10 | 0.481473E+10 | 0.566629E+10 | 0.318384E+10 | 0.248245E+10 | 0.00 | 0.00 |
April | 0.439022E+10 | 0.360155E+10 | 0.454121E+10 | 0.181468E+10 | 0.272654E+10 | 0.00 | 0.00 |
May | 0.445706E+10 | 0.242260E+10 | 0.410644E+10 | 0.119268E+10 | 0.291376E+10 | 0.00 | 0.00 |
June | 0.475171E+10 | 0.153914E+10 | 0.386142E+10 | 0.818249E+09 | 0.304317E+10 | 0.00 | 0.00 |
July | 0.563317E+10 | 0.113000E+10 | 0.407328E+10 | 0.988305E+09 | 0.308498E+10 | 0.00 | 0.00 |
August | 0.614662E+10 | 0.154390E+10 | 0.457292E+10 | 0.148265E+10 | 0.309027E+10 | 0.00 | 0.00 |
September | 0.623014E+10 | 0.243439E+10 | 0.514542E+10 | 0.250620E+10 | 0.263923E+10 | 0.00 | 0.00 |
October | 0.514301E+10 | 0.378862E+10 | 0.508752E+10 | 0.290608E+10 | 0.218144E+10 | 0.00 | 0.00 |
November | 0.304178E+10 | 0.469753E+10 | 0.352604E+10 | 0.199056E+10 | 0.153548E+10 | 0.00 | 0.00 |
December | 0.223213E+10 | 0.676582E+10 | 0.339997E+10 | 0.175964E+10 | 0.164034E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.529301E+11 | 0.453862E+11 | 0.522396E+11 | 0.230382E+11 | 0.292014E+11 | 0.00 | 0.00 |
Minimum of Months | 0.223213E+10 | 0.113000E+10 | 0.339997E+10 | 0.818249E+09 | 0.153548E+10 | 0.00 | 0.00 |
Maximum of Months | 0.623014E+10 | 0.676582E+10 | 0.566629E+10 | 0.318384E+10 | 0.309027E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.192968E+09 | 0.511143E+10 | 0.989807E+09 | 0.232368E+09 | 0.757439E+09 | 0.00 | 0.00 |
February | 0.449056E+09 | 0.436284E+10 | 0.144896E+10 | 0.372393E+09 | 0.107657E+10 | 0.00 | 0.00 |
March | 0.179523E+10 | 0.334424E+10 | 0.251431E+10 | 0.107657E+10 | 0.143774E+10 | 0.00 | 0.00 |
April | 0.261554E+10 | 0.233353E+10 | 0.297912E+10 | 0.122156E+10 | 0.175756E+10 | 0.00 | 0.00 |
May | 0.387014E+10 | 0.161307E+10 | 0.363149E+10 | 0.164120E+10 | 0.199029E+10 | 0.00 | 0.00 |
June | 0.514178E+10 | 0.109003E+10 | 0.424017E+10 | 0.199440E+10 | 0.224577E+10 | 0.00 | 0.00 |
July | 0.514970E+10 | 0.801762E+09 | 0.391723E+10 | 0.171745E+10 | 0.219978E+10 | 0.00 | 0.00 |
August | 0.454029E+10 | 0.104503E+10 | 0.354291E+10 | 0.150648E+10 | 0.203643E+10 | 0.00 | 0.00 |
September | 0.298829E+10 | 0.158973E+10 | 0.269253E+10 | 0.116279E+10 | 0.152974E+10 | 0.00 | 0.00 |
October | 0.139122E+10 | 0.256532E+10 | 0.180361E+10 | 0.635334E+09 | 0.116827E+10 | 0.00 | 0.00 |
November | 0.504048E+09 | 0.325749E+10 | 0.103435E+10 | 0.298062E+09 | 0.736285E+09 | 0.00 | 0.00 |
December | 0.180374E+09 | 0.500706E+10 | 0.926576E+09 | 0.201891E+09 | 0.724685E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.288186E+11 | 0.321215E+11 | 0.297211E+11 | 0.120605E+11 | 0.176606E+11 | 0.00 | 0.00 |
Minimum of Months | 0.180374E+09 | 0.801762E+09 | 0.926576E+09 | 0.201891E+09 | 0.724685E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514970E+10 | 0.511143E+10 | 0.424017E+10 | 0.199440E+10 | 0.224577E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.825000E+10 | 0.945592E+09 | 0.00 | 0.945592E+09 | 0.00 | 0.00 |
February | 6225348.92 | 0.712283E+10 | 0.130130E+10 | 0.00 | 0.130130E+10 | 0.00 | 0.00 |
March | 0.351223E+09 | 0.567258E+10 | 0.174720E+10 | 0.00 | 0.174720E+10 | 0.00 | 0.00 |
April | 0.807606E+09 | 0.376929E+10 | 0.215447E+10 | 8597147.97 | 0.214587E+10 | 0.00 | 0.00 |
May | 0.166465E+10 | 0.243375E+10 | 0.258684E+10 | 0.109696E+09 | 0.247714E+10 | 0.00 | 0.00 |
June | 0.296536E+10 | 0.150080E+10 | 0.301105E+10 | 0.256315E+09 | 0.275474E+10 | 0.00 | 0.00 |
July | 0.349057E+10 | 0.108191E+10 | 0.288626E+10 | 0.186313E+09 | 0.269994E+10 | 0.00 | 0.00 |
August | 0.280691E+10 | 0.145592E+10 | 0.249741E+10 | 37992498.94 | 0.245942E+10 | 0.00 | 0.00 |
September | 0.146530E+10 | 0.230368E+10 | 0.183928E+10 | 382119.68 | 0.183889E+10 | 0.00 | 0.00 |
October | 0.465596E+09 | 0.384250E+10 | 0.142077E+10 | 0.00 | 0.142077E+10 | 0.00 | 0.00 |
November | 0.109350E+09 | 0.496691E+10 | 0.923923E+09 | 0.00 | 0.923923E+09 | 0.00 | 0.00 |
December | 2346833.01 | 0.785862E+10 | 0.885045E+09 | 0.00 | 0.885045E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.141351E+11 | 0.502588E+11 | 0.221991E+11 | 0.599295E+09 | 0.215998E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.108191E+10 | 0.885045E+09 | 0.00 | 0.885045E+09 | 0.00 | 0.00 |
Maximum of Months | 0.349057E+10 | 0.825000E+10 | 0.301105E+10 | 0.256315E+09 | 0.275474E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.300113E+09 | 0.496126E+10 | 0.115360E+10 | 0.371985E+09 | 0.781620E+09 | 0.00 | 0.00 |
February | 0.508782E+09 | 0.429792E+10 | 0.152888E+10 | 0.458777E+09 | 0.107010E+10 | 0.00 | 0.00 |
March | 0.158217E+10 | 0.340656E+10 | 0.242896E+10 | 0.101723E+10 | 0.141173E+10 | 0.00 | 0.00 |
April | 0.255261E+10 | 0.233651E+10 | 0.311118E+10 | 0.137468E+10 | 0.173650E+10 | 0.00 | 0.00 |
May | 0.360316E+10 | 0.162955E+10 | 0.360183E+10 | 0.159327E+10 | 0.200856E+10 | 0.00 | 0.00 |
June | 0.452848E+10 | 0.100962E+10 | 0.389287E+10 | 0.172045E+10 | 0.217243E+10 | 0.00 | 0.00 |
July | 0.496006E+10 | 0.721542E+09 | 0.386279E+10 | 0.170072E+10 | 0.216207E+10 | 0.00 | 0.00 |
August | 0.434050E+10 | 0.954411E+09 | 0.348852E+10 | 0.146428E+10 | 0.202424E+10 | 0.00 | 0.00 |
September | 0.304826E+10 | 0.145203E+10 | 0.280940E+10 | 0.124614E+10 | 0.156327E+10 | 0.00 | 0.00 |
October | 0.151714E+10 | 0.239567E+10 | 0.196996E+10 | 0.814825E+09 | 0.115514E+10 | 0.00 | 0.00 |
November | 0.531743E+09 | 0.314270E+10 | 0.108135E+10 | 0.346883E+09 | 0.734469E+09 | 0.00 | 0.00 |
December | 0.142900E+09 | 0.492355E+10 | 0.899562E+09 | 0.185868E+09 | 0.713694E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.276159E+11 | 0.312313E+11 | 0.298289E+11 | 0.122951E+11 | 0.175338E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142900E+09 | 0.721542E+09 | 0.899562E+09 | 0.185868E+09 | 0.713694E+09 | 0.00 | 0.00 |
Maximum of Months | 0.496006E+10 | 0.496126E+10 | 0.389287E+10 | 0.172045E+10 | 0.217243E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.277305E+10 | 0.692633E+10 | 0.406597E+10 | 0.237342E+10 | 0.169255E+10 | 0.00 | 0.00 |
February | 0.270689E+10 | 0.615574E+10 | 0.419306E+10 | 0.202185E+10 | 0.217121E+10 | 0.00 | 0.00 |
March | 0.489036E+10 | 0.501632E+10 | 0.566626E+10 | 0.318383E+10 | 0.248244E+10 | 0.00 | 0.00 |
April | 0.415258E+10 | 0.384297E+10 | 0.454119E+10 | 0.181466E+10 | 0.272653E+10 | 0.00 | 0.00 |
May | 0.418107E+10 | 0.271298E+10 | 0.410642E+10 | 0.119267E+10 | 0.291375E+10 | 0.00 | 0.00 |
June | 0.455159E+10 | 0.168778E+10 | 0.386141E+10 | 0.818244E+09 | 0.304317E+10 | 0.00 | 0.00 |
July | 0.550964E+10 | 0.120434E+10 | 0.407327E+10 | 0.988299E+09 | 0.308497E+10 | 0.00 | 0.00 |
August | 0.606250E+10 | 0.155949E+10 | 0.457290E+10 | 0.148264E+10 | 0.309026E+10 | 0.00 | 0.00 |
September | 0.616701E+10 | 0.236137E+10 | 0.514540E+10 | 0.250618E+10 | 0.263922E+10 | 0.00 | 0.00 |
October | 0.506154E+10 | 0.365839E+10 | 0.508749E+10 | 0.290606E+10 | 0.218143E+10 | 0.00 | 0.00 |
November | 0.298222E+10 | 0.460670E+10 | 0.352602E+10 | 0.199055E+10 | 0.153547E+10 | 0.00 | 0.00 |
December | 0.216100E+10 | 0.687002E+10 | 0.339996E+10 | 0.175963E+10 | 0.164033E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.511995E+11 | 0.466024E+11 | 0.522394E+11 | 0.230380E+11 | 0.292013E+11 | 0.00 | 0.00 |
Minimum of Months | 0.216100E+10 | 0.120434E+10 | 0.339996E+10 | 0.818244E+09 | 0.153547E+10 | 0.00 | 0.00 |
Maximum of Months | 0.616701E+10 | 0.692633E+10 | 0.566626E+10 | 0.318383E+10 | 0.309026E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181250E+09 | 0.521945E+10 | 0.989776E+09 | 0.232359E+09 | 0.757417E+09 | 0.00 | 0.00 |
February | 0.421945E+09 | 0.447854E+10 | 0.144891E+10 | 0.372379E+09 | 0.107653E+10 | 0.00 | 0.00 |
March | 0.169716E+10 | 0.349206E+10 | 0.251422E+10 | 0.107653E+10 | 0.143770E+10 | 0.00 | 0.00 |
April | 0.248841E+10 | 0.247173E+10 | 0.297903E+10 | 0.122151E+10 | 0.175751E+10 | 0.00 | 0.00 |
May | 0.371987E+10 | 0.174522E+10 | 0.363138E+10 | 0.164114E+10 | 0.199024E+10 | 0.00 | 0.00 |
June | 0.504895E+10 | 0.112791E+10 | 0.424003E+10 | 0.199433E+10 | 0.224571E+10 | 0.00 | 0.00 |
July | 0.509118E+10 | 0.819940E+09 | 0.391711E+10 | 0.171739E+10 | 0.219972E+10 | 0.00 | 0.00 |
August | 0.450890E+10 | 0.103118E+10 | 0.354279E+10 | 0.150642E+10 | 0.203637E+10 | 0.00 | 0.00 |
September | 0.297439E+10 | 0.154151E+10 | 0.269244E+10 | 0.116274E+10 | 0.152970E+10 | 0.00 | 0.00 |
October | 0.137964E+10 | 0.249265E+10 | 0.180355E+10 | 0.635310E+09 | 0.116824E+10 | 0.00 | 0.00 |
November | 0.496001E+09 | 0.320948E+10 | 0.103431E+10 | 0.298051E+09 | 0.736263E+09 | 0.00 | 0.00 |
December | 0.172979E+09 | 0.502817E+10 | 0.926546E+09 | 0.201883E+09 | 0.724663E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.281807E+11 | 0.326578E+11 | 0.297201E+11 | 0.120600E+11 | 0.176601E+11 | 0.00 | 0.00 |
Minimum of Months | 0.172979E+09 | 0.819940E+09 | 0.926546E+09 | 0.201883E+09 | 0.724663E+09 | 0.00 | 0.00 |
Maximum of Months | 0.509118E+10 | 0.521945E+10 | 0.424003E+10 | 0.199433E+10 | 0.224571E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.522720E+10 | -0.497663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -250575673.3 | 60.05 | 0.00 | 0.00 |
February | 0.481188E+10 | -0.458711E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -224765638.6 | 60.05 | 0.00 | 0.00 |
March | 0.559880E+10 | -0.535740E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241401388.4 | 60.05 | 0.00 | 0.00 |
April | 0.486406E+10 | -0.463455E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229506664.3 | 60.05 | 0.00 | 0.00 |
May | 0.492935E+10 | -0.469578E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233574604.8 | 60.05 | 0.00 | 0.00 |
June | 0.460654E+10 | -0.438171E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224826527.3 | 60.05 | 0.00 | 0.00 |
July | 0.416221E+10 | -0.393131E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -230896130.4 | 60.05 | 0.00 | 0.00 |
August | 0.449966E+10 | -0.426810E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231563327.8 | 60.05 | 0.00 | 0.00 |
September | 0.413529E+10 | -0.391085E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224442678.5 | 60.05 | 0.00 | 0.00 |
October | 0.447104E+10 | -0.423621E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234827351.8 | 60.05 | 0.00 | 0.00 |
November | 0.466000E+10 | -0.442963E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -230376035.4 | 60.05 | 0.00 | 0.00 |
December | 0.488921E+10 | -0.464342E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -245787294.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.568552E+11 | -0.540527E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.280254E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.413529E+10 | -0.535740E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -250575673.3 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.559880E+10 | -0.391085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -224442678.5 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.892234E+10 | 18602.55 | 04-JAN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.820422E+10 | 21233.23 | 06-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265677E+10 | 16523.27 | 07-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97707716.76 | 7682.56 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3622.33 | 3.89 | 10-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 507943.24 | 5.37 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1407748.58 | 5.79 | 18-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 820693.56 | 6.29 | 11-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 137395.86 | 5.19 | 08-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24775922.19 | 4425.38 | 17-OCT-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162437E+09 | 5946.60 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.645181E+10 | 21287.85 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3622.33 | 3.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.892234E+10 | 21287.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.579870E+09 | 15424.21 | 02-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28777123.00 | 15393.27 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 195450.63 | 3257.51 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12078962.28 | 15392.87 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.620921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579870E+09 | 15424.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.987741E+10 | 11280.03 | 02-JAN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.878883E+10 | 11275.04 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.580721E+10 | 11283.28 | 13-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.344679E+10 | 11279.20 | 04-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135003E+10 | 11299.83 | 22-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.291702E+09 | 11347.19 | 06-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 49352013.67 | 6913.32 | 03-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103631E+09 | 7896.14 | 03-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.358473E+09 | 11338.93 | 05-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150826E+10 | 11279.27 | 05-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384076E+10 | 11276.76 | 13-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.845915E+10 | 11290.68 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 49352013.67 | 6913.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.987741E+10 | 11347.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.470432E+10 | 7528.60 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408097E+10 | 7526.69 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223545E+10 | 7509.43 | 22-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.771492E+09 | 7509.99 | 19-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102125E+09 | 6515.05 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4424253.49 | 4036.51 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207490E+09 | 7481.83 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108481E+10 | 7510.14 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376180E+10 | 7537.28 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.470432E+10 | 7537.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.766522E+10 | 11277.96 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.685083E+10 | 11275.06 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458895E+10 | 11265.69 | 29-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197844E+10 | 11272.80 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.365644E+09 | 11217.25 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10164554.06 | 5467.28 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.493913E+09 | 11222.68 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181015E+10 | 11269.36 | 13-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.583043E+10 | 11290.69 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.766522E+10 | 11290.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.505210E+10 | 7772.11 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.439787E+10 | 7770.46 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245231E+10 | 7748.41 | 10-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.997748E+09 | 7749.21 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155288E+09 | 7730.01 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7676993.37 | 3298.83 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.282159E+09 | 7723.99 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121622E+10 | 7753.32 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.391140E+10 | 7781.48 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.505210E+10 | 7781.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134569E+11 | 20683.30 | 04-JAN-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122480E+11 | 22170.21 | 06-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552179E+10 | 20500.94 | 07-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.548188E+09 | 12558.00 | 17-APR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3912478.40 | 2917.79 | 01-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 518109.37 | 5.35 | 27-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1256917.19 | 5.40 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 612717.35 | 5.95 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63539.51 | 4.48 | 08-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276313E+09 | 9561.08 | 17-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144567E+10 | 11464.49 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109502E+11 | 22123.57 | 11-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 63539.51 | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134569E+11 | 22170.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.273206E+10 | 21641.41 | 17-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220990E+10 | 21591.16 | 27-FEB-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.392485E+09 | 21622.07 | 20-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51182877.24 | 21597.91 | 17-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12597829.02 | 21541.29 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132815E+09 | 21628.73 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177889E+10 | 21642.08 | 18-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.730993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.273206E+10 | 21642.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.527293E+10 | 11490.04 | 23-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.462894E+10 | 11657.17 | 06-FEB-08:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183685E+10 | 11464.47 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.682194E+09 | 11493.08 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50302804.85 | 11397.33 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 104568.55 | 522.84 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10717016.10 | 7272.92 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402288E+09 | 11434.33 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147946E+10 | 11457.77 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.480547E+10 | 11593.29 | 11-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527293E+10 | 11657.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.430664E+10 | 8444.10 | 17-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.374193E+10 | 8538.07 | 06-FEB-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168725E+10 | 8435.12 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520012E+09 | 8435.69 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33407187.86 | 5067.69 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20651475.59 | 5420.60 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.483296E+09 | 8412.26 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145210E+10 | 8430.08 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393957E+10 | 8509.91 | 11-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.430664E+10 | 8538.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.702820E+10 | 11506.97 | 06-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.619487E+10 | 11755.46 | 07-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317568E+10 | 11515.22 | 07-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.937390E+09 | 11503.22 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41973678.18 | 11407.38 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21420739.00 | 7934.63 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.703459E+09 | 11478.97 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210920E+10 | 11467.87 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.611238E+10 | 11741.42 | 11-DEC-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.702820E+10 | 11755.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.505376E+10 | 8642.55 | 23-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438372E+10 | 8752.69 | 07-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211414E+10 | 8641.98 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.770694E+09 | 8642.58 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80051302.40 | 8589.57 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1364796.40 | 1844.35 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35539484.47 | 5419.95 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.654831E+09 | 8618.52 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178157E+10 | 8636.82 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.449841E+10 | 8787.11 | 11-DEC-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.505376E+10 | 8787.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143905E+11 | 18670.88 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128269E+11 | 18916.51 | 07-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.539134E+10 | 18735.98 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.671423E+09 | 14208.57 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20128851.16 | 5691.23 | 01-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 325644.60 | 5.97 | 27-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 857219.96 | 6.37 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 343470.14 | 6.48 | 09-AUG-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.420932E+09 | 12969.79 | 17-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154522E+10 | 12629.85 | 24-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118343E+11 | 18917.41 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143905E+11 | 18917.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.938822E+10 | 31819.07 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.789741E+10 | 32234.38 | 07-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340015E+10 | 31926.83 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.798419E+09 | 31797.42 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23367298.10 | 31508.51 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6805493.57 | 8653.60 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.663587E+09 | 31802.35 | 16-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242498E+10 | 31804.42 | 13-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.806098E+10 | 32240.31 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.938822E+10 | 32240.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.878498E+10 | 15231.22 | 04-JAN-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.789360E+10 | 15447.56 | 07-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.396278E+10 | 15337.57 | 07-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190943E+10 | 14843.28 | 18-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.432388E+09 | 14734.90 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46219653.16 | 8538.93 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 54929.69 | 147.04 | 07-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7812320.10 | 5909.76 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194701E+09 | 10055.44 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153778E+10 | 14813.76 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.358062E+10 | 14850.60 | 14-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.843700E+10 | 15231.68 | 11-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 54929.69 | 147.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.878498E+10 | 15447.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.668632E+10 | 9889.61 | 06-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.586731E+10 | 9946.93 | 07-FEB-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.299415E+10 | 9646.55 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109339E+10 | 9590.13 | 18-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158321E+09 | 8602.30 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1893763.24 | 877.79 | 09-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1808986.77 | 2562.89 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115379E+09 | 7756.38 | 30-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115886E+10 | 9571.06 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274782E+10 | 9594.87 | 14-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.635343E+10 | 9889.50 | 11-DEC-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.668632E+10 | 9946.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109376E+11 | 15238.19 | 04-JAN-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.977808E+10 | 15556.39 | 07-FEB-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.578910E+10 | 15367.93 | 07-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.240950E+10 | 14850.06 | 18-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.446005E+09 | 14741.64 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17125327.55 | 5874.32 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8418995.00 | 6042.74 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293072E+09 | 11455.51 | 30-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229276E+10 | 14859.12 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459174E+10 | 14857.39 | 14-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100302E+11 | 15375.67 | 11-DEC-08:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109376E+11 | 15556.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.724643E+10 | 10465.94 | 04-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.638659E+10 | 10714.87 | 07-FEB-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346118E+10 | 10552.50 | 07-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153767E+10 | 10211.27 | 18-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.343829E+09 | 10135.86 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36720873.31 | 5557.50 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 427209.02 | 685.31 | 13-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9334343.41 | 4852.85 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213827E+09 | 7303.55 | 30-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151027E+10 | 10190.56 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.308428E+10 | 10215.96 | 14-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670884E+10 | 10562.67 | 11-DEC-08:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 427209.02 | 685.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.724643E+10 | 10714.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.261508E+10 | 0.227748E+10 | 37535.27 | 15-MAR-14:10 | 37535.27 | 0.00 |
April | 0.00 | 0.00 | 0.104518E+10 | 0.986610E+09 | 17902.33 | 07-APR-14:10 | 17902.33 | 0.00 |
May | 0.00 | 0.00 | 0.101626E+11 | 0.936338E+10 | 43039.64 | 23-MAY-14:30 | 43039.64 | 0.00 |
June | 0.00 | 0.00 | 0.415866E+11 | 0.339940E+11 | 99139.95 | 27-JUN-05:12 | 69378.98 | 0.00 |
July | 0.00 | 0.00 | 0.688646E+11 | 0.557950E+11 | 128319.48 | 21-JUL-04:02 | 70257.65 | 0.00 |
August | 0.00 | 0.00 | 0.613694E+11 | 0.522851E+11 | 125202.97 | 14-AUG-05:12 | 74836.06 | 0.00 |
September | 0.00 | 0.00 | 0.290843E+11 | 0.241783E+11 | 73373.30 | 14-SEP-05:13 | 32273.74 | 0.00 |
October | 0.00 | 0.00 | 0.372744E+10 | 0.323528E+10 | 44747.52 | 11-OCT-16:00 | 44747.52 | 0.00 |
November | 0.00 | 0.00 | 0.686711E+09 | 0.534119E+09 | 15470.10 | 16-NOV-17:00 | 13006.89 | 0.00 |
December | 0.00 | 0.00 | 2599374.28 | 1620621.46 | 1574.29 | 01-DEC-11:00 | 980.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.219145E+12 | 0.182651E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.688646E+11 | 0.557950E+11 | 128319.48 | 74836.06 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 185588.94 | 183802.45 | 1237.26 | 01-FEB-07:05 | 1225.35 | 0.00 |
March | 0.00 | 0.00 | 0.245167E+10 | 0.210811E+10 | 38717.33 | 15-MAR-14:05 | 38717.33 | 0.00 |
April | 0.00 | 0.00 | 0.953798E+09 | 0.890747E+09 | 17043.63 | 08-APR-13:00 | 16106.16 | 0.00 |
May | 0.00 | 0.00 | 0.971151E+10 | 0.886512E+10 | 43677.66 | 23-MAY-14:30 | 43677.66 | 0.00 |
June | 0.00 | 0.00 | 0.398155E+11 | 0.323404E+11 | 81496.77 | 27-JUN-13:00 | 62246.55 | 0.00 |
July | 0.00 | 0.00 | 0.644245E+11 | 0.515595E+11 | 125607.11 | 21-JUL-04:02 | 66598.85 | 0.00 |
August | 0.00 | 0.00 | 0.548376E+11 | 0.461595E+11 | 91667.62 | 07-AUG-05:12 | 40636.01 | 0.00 |
September | 0.00 | 0.00 | 0.251994E+11 | 0.203974E+11 | 62731.68 | 15-SEP-12:05 | 49877.10 | 0.00 |
October | 0.00 | 0.00 | 0.315445E+10 | 0.265485E+10 | 36176.32 | 11-OCT-15:20 | 36176.32 | 0.00 |
November | 0.00 | 0.00 | 0.596451E+09 | 0.442436E+09 | 13408.50 | 16-NOV-18:00 | 10595.92 | 0.00 |
December | 0.00 | 0.00 | 1141951.03 | 685753.49 | 865.60 | 01-DEC-11:00 | 517.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201146E+12 | 0.165419E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.644245E+11 | 0.515595E+11 | 125607.11 | 66598.85 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3190351.59 | 3146397.35 | 2015.24 | 09-JAN-06:20 | 2015.24 | 0.00 |
February | 0.00 | 0.00 | 1952277.57 | 1928879.09 | 1415.43 | 13-FEB-06:10 | 1415.43 | 0.00 |
March | 0.00 | 0.00 | 0.305795E+10 | 0.255047E+10 | 46933.61 | 15-MAR-14:00 | 46933.61 | 0.00 |
April | 0.00 | 0.00 | 0.107897E+10 | 0.966416E+09 | 21223.76 | 08-APR-13:00 | 18446.34 | 0.00 |
May | 0.00 | 0.00 | 0.116709E+11 | 0.104309E+11 | 54022.31 | 31-MAY-16:00 | 54022.31 | 0.00 |
June | 0.00 | 0.00 | 0.464329E+11 | 0.377279E+11 | 96400.15 | 27-JUN-13:05 | 77081.73 | 0.00 |
July | 0.00 | 0.00 | 0.743168E+11 | 0.597253E+11 | 177530.60 | 21-JUL-04:02 | 95368.15 | 0.00 |
August | 0.00 | 0.00 | 0.622261E+11 | 0.518779E+11 | 87823.53 | 18-AUG-14:30 | 78588.12 | 0.00 |
September | 0.00 | 0.00 | 0.278504E+11 | 0.216431E+11 | 68532.21 | 15-SEP-12:05 | 56606.40 | 0.00 |
October | 0.00 | 0.00 | 0.346700E+10 | 0.274660E+10 | 40444.32 | 11-OCT-15:20 | 40444.32 | 0.00 |
November | 0.00 | 0.00 | 0.721183E+09 | 0.509556E+09 | 16250.09 | 16-NOV-18:00 | 12012.24 | 0.00 |
December | 0.00 | 0.00 | 5343802.74 | 4925424.52 | 1245.50 | 09-DEC-06:01 | 1245.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.230833E+12 | 0.188188E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1952277.57 | 1928879.09 | 1245.50 | 1245.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.743168E+11 | 0.597253E+11 | 177530.60 | 95368.15 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 48929.94 | 306226.56 | 14-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 47735.54 | 332547.60 | 23-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 21279.74 | 329315.61 | 10-MAR-06:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7351.91 | 327645.64 | 18-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1341.20 | 286042.22 | 01-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 149.13 | 46637.19 | 14-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.73 | 12531.56 | 03-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 50.70 | 33773.25 | 31-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 488.74 | 147649.87 | 30-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4678.66 | 293158.02 | 17-OCT-06:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13203.23 | 361812.98 | 13-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 41466.55 | 339317.96 | 02-DEC-06:11 |
Annual Sum or Average | 0.00 | 15405.80 | ||||
Minimum of Months | 0.00 | 0.00 | 18.73 | 12531.56 | ||
Maximum of Months | 0.00 | 0.00 | 48929.94 | 361812.98 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1848.53 | 6796.19 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1886.54 | 6820.25 | 15-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1990.33 | 6798.42 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1778.59 | 6590.28 | 03-APR-11:17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1743.72 | 6284.03 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1681.00 | 5894.59 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1458.82 | 5548.22 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1584.16 | 5368.51 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1499.74 | 5540.97 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1572.44 | 5884.41 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1699.56 | 6261.56 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1724.36 | 6582.54 | 29-DEC-12:17 |
Annual Sum or Average | 0.00 | 1704.61 | ||||
Minimum of Months | 0.00 | 0.00 | 1458.82 | 5368.51 | ||
Maximum of Months | 0.00 | 0.00 | 1990.33 | 6820.25 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.401053E+10 | 0.55 | 5625.28 | 02-JAN-05:01 | 1.31 |
February | 0.361765E+10 | 0.55 | 5625.28 | 06-FEB-07:01 | 1.31 |
March | 0.403661E+10 | 0.55 | 4311.12 | 15-MAR-14:10 | 1.16 |
April | 0.385346E+10 | 0.52 | 4591.67 | 26-APR-07:03 | 1.20 |
May | 0.483084E+10 | 0.56 | 6694.65 | 30-MAY-06:03 | 1.39 |
June | 0.652842E+10 | 0.67 | 8401.52 | 19-JUN-05:12 | 1.53 |
July | 0.756995E+10 | 0.68 | 10563.90 | 21-JUL-04:02 | 1.68 |
August | 0.813188E+10 | 0.72 | 10547.89 | 09-AUG-15:30 | 1.69 |
September | 0.612445E+10 | 0.63 | 8965.72 | 21-SEP-15:30 | 1.57 |
October | 0.439028E+10 | 0.53 | 8401.52 | 24-OCT-05:01 | 1.55 |
November | 0.364855E+10 | 0.50 | 4051.78 | 01-NOV-16:00 | 1.13 |
December | 0.365065E+10 | 0.51 | 5625.28 | 11-DEC-07:01 | 1.31 |
Annual Sum or Average | 0.603933E+11 | 0.58 | |||
Minimum of Months | 0.361765E+10 | 0.50 | 4051.78 | 1.13 | |
Maximum of Months | 0.813188E+10 | 0.72 | 10563.90 | 1.69 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.387192E+10 | 0.58 | 5485.57 | 02-JAN-05:01 | 1.32 |
February | 0.347840E+10 | 0.57 | 5485.57 | 01-FEB-07:03 | 1.32 |
March | 0.356563E+10 | 0.53 | 5485.57 | 01-MAR-07:01 | 1.32 |
April | 0.323732E+10 | 0.49 | 5485.57 | 03-APR-06:01 | 1.32 |
May | 0.413905E+10 | 0.55 | 5884.06 | 23-MAY-14:30 | 1.35 |
June | 0.589545E+10 | 0.66 | 8714.98 | 27-JUN-14:05 | 1.59 |
July | 0.675862E+10 | 0.67 | 12302.60 | 21-JUL-04:02 | 1.83 |
August | 0.681092E+10 | 0.68 | 9784.10 | 09-AUG-14:05 | 1.67 |
September | 0.482736E+10 | 0.59 | 7854.05 | 21-SEP-15:20 | 1.52 |
October | 0.339226E+10 | 0.49 | 5485.57 | 30-OCT-06:01 | 1.32 |
November | 0.300797E+10 | 0.47 | 5485.57 | 13-NOV-07:03 | 1.32 |
December | 0.358200E+10 | 0.54 | 5485.57 | 04-DEC-06:01 | 1.32 |
Annual Sum or Average | 0.525669E+11 | 0.57 | |||
Minimum of Months | 0.300797E+10 | 0.47 | 5485.57 | 1.32 | |
Maximum of Months | 0.681092E+10 | 0.68 | 12302.60 | 1.83 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.479647E+10 | 0.60 | 5440.75 | 02-JAN-05:01 | 1.12 |
February | 0.438424E+10 | 0.60 | 5440.75 | 01-FEB-06:11 | 1.12 |
March | 0.401862E+10 | 0.51 | 5440.75 | 01-MAR-06:01 | 1.12 |
April | 0.336692E+10 | 0.44 | 5440.75 | 01-APR-06:03 | 1.12 |
May | 0.393203E+10 | 0.46 | 5514.98 | 31-MAY-16:00 | 1.12 |
June | 0.534530E+10 | 0.55 | 7975.67 | 12-JUN-15:00 | 1.30 |
July | 0.603223E+10 | 0.55 | 17060.93 | 21-JUL-04:02 | 1.79 |
August | 0.587396E+10 | 0.55 | 8660.75 | 09-AUG-15:20 | 1.34 |
September | 0.413551E+10 | 0.47 | 6666.58 | 21-SEP-15:20 | 1.20 |
October | 0.335562E+10 | 0.42 | 5440.75 | 16-OCT-05:01 | 1.12 |
November | 0.323354E+10 | 0.42 | 5440.75 | 03-NOV-05:01 | 1.12 |
December | 0.455524E+10 | 0.57 | 5440.75 | 02-DEC-06:11 | 1.12 |
Annual Sum or Average | 0.530297E+11 | 0.51 | |||
Minimum of Months | 0.323354E+10 | 0.42 | 5440.75 | 1.12 | |
Maximum of Months | 0.603223E+10 | 0.60 | 17060.93 | 1.79 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.983764E+09 | 0.885388E+09 | 1252.17 | 04-JAN-07:01 | 1126.95 | 1126.95 | 47.28 | 4.02 |
February | 0.866690E+09 | 0.780021E+09 | 1294.06 | 06-FEB-08:00 | 1164.66 | 1164.66 | 46.39 | 4.15 |
March | 0.437983E+09 | 0.394185E+09 | 1229.19 | 06-MAR-07:01 | 1106.27 | 1106.27 | 48.22 | 3.93 |
April | 0.150083E+09 | 0.135074E+09 | 1158.76 | 17-APR-06:01 | 1042.89 | 1042.89 | 44.93 | 3.63 |
May | 33690356.89 | 30321321.20 | 1074.77 | 01-MAY-06:02 | 967.29 | 967.29 | 37.44 | 3.03 |
June | 4966202.98 | 4469582.68 | 423.40 | 14-JUN-06:03 | 381.06 | 381.06 | 38.23 | 0.51 |
July | 432882.17 | 389593.95 | 111.45 | 03-JUL-06:07 | 100.31 | 100.31 | 34.56 | 0.12 |
August | 1133714.55 | 1020343.10 | 234.90 | 31-AUG-06:03 | 211.41 | 211.41 | 29.08 | 0.26 |
September | 10999617.83 | 9899656.05 | 869.01 | 30-SEP-06:03 | 782.11 | 782.11 | 36.44 | 1.50 |
October | 97671999.19 | 87904799.27 | 1138.29 | 30-OCT-06:01 | 1024.46 | 1024.46 | 42.18 | 3.52 |
November | 0.256629E+09 | 0.230966E+09 | 1150.53 | 24-NOV-07:01 | 1035.48 | 1035.48 | 44.49 | 3.59 |
December | 0.835170E+09 | 0.751653E+09 | 1309.72 | 11-DEC-07:11 | 1178.74 | 1178.74 | 46.07 | 4.19 |
Annual Sum or Average | 0.367921E+10 | 0.331129E+10 | ||||||
Minimum of Months | 432882.17 | 389593.95 | 111.45 | 100.31 | 100.31 | 29.08 | 0.12 | |
Maximum of Months | 0.983764E+09 | 0.885388E+09 | 1309.72 | 1178.74 | 1178.74 | 48.22 | 4.19 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.98 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 56.54 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.89 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 56.98 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.15 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.16 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.33 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.42 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.42 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.18 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.16 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 56.81 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.54 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.18 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 33.64 | 33.64 | 48929.94 | 306226.56 | 14-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 42.46 | 42.46 | 47735.54 | 332547.60 | 23-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33.86 | 33.86 | 21279.74 | 329315.61 | 10-MAR-06:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.14 | 26.14 | 7351.91 | 327645.64 | 18-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.16 | 20.16 | 1341.20 | 286042.22 | 01-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 38.59 | 38.59 | 149.13 | 46637.19 | 14-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 34.03 | 34.03 | 18.73 | 12531.56 | 03-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 31.54 | 31.54 | 50.70 | 33773.25 | 31-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 35.37 | 35.37 | 488.74 | 147649.87 | 30-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.93 | 21.93 | 4678.66 | 293158.02 | 17-OCT-06:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23.25 | 23.25 | 13203.23 | 361812.98 | 13-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.45 | 29.45 | 41466.55 | 339317.96 | 02-DEC-06:11 |
Annual Sum or Average | 0.00 | 15405.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.16 | 20.16 | 18.73 | 12531.56 | ||
Maximum of Months | 0.00 | 0.00 | 42.46 | 42.46 | 48929.94 | 361812.98 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.98 | 57.98 | 1848.53 | 6796.19 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.39 | 57.39 | 1886.54 | 6820.25 | 15-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.39 | 57.39 | 1990.33 | 6798.42 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.47 | 57.47 | 1778.59 | 6590.28 | 03-APR-11:17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.08 | 58.08 | 1743.72 | 6284.03 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.74 | 57.74 | 1681.00 | 5894.59 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.87 | 57.87 | 1458.82 | 5548.22 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.95 | 57.95 | 1584.16 | 5368.51 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 1499.74 | 5540.97 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.01 | 57.01 | 1572.44 | 5884.41 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.75 | 57.75 | 1699.56 | 6261.56 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.60 | 57.60 | 1724.36 | 6582.54 | 29-DEC-12:17 |
Annual Sum or Average | 0.00 | 1704.61 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.01 | 57.01 | 1458.82 | 5368.51 | ||
Maximum of Months | 0.00 | 0.00 | 58.08 | 58.08 | 1990.33 | 6820.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.368013E+11 | 0.00 | 0.00 | 0.401053E+10 | 0.00 | 0.00 |
February | 0.323515E+11 | 0.00 | 0.00 | 0.361765E+10 | 0.00 | 0.00 |
March | 0.177409E+11 | 0.00 | 0.00 | 0.467128E+10 | 0.00 | 0.00 |
April | 0.729218E+10 | 0.00 | 0.00 | 0.413105E+10 | 0.00 | 0.00 |
May | 0.197309E+10 | 0.00 | 0.00 | 0.734424E+10 | 0.00 | 0.00 |
June | 0.292210E+09 | 0.00 | 0.00 | 0.163172E+11 | 0.00 | 0.00 |
July | 50759762.25 | 0.00 | 0.00 | 0.236683E+11 | 0.00 | 0.00 |
August | 0.104452E+09 | 0.00 | 0.00 | 0.225117E+11 | 0.00 | 0.00 |
September | 0.380877E+09 | 0.00 | 0.00 | 0.129567E+11 | 0.00 | 0.00 |
October | 0.251660E+10 | 0.00 | 0.00 | 0.533604E+10 | 0.00 | 0.00 |
November | 0.811437E+10 | 0.00 | 0.00 | 0.383062E+10 | 0.00 | 0.00 |
December | 0.284267E+11 | 0.00 | 0.00 | 0.365139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136045E+12 | 0.00 | 0.00 | 0.112047E+12 | 0.00 | 0.00 |
Minimum of Months | 50759762.25 | 0.00 | 0.00 | 0.361765E+10 | 0.00 | 0.00 |
Maximum of Months | 0.368013E+11 | 0.00 | 0.00 | 0.236683E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.378505E+11 | 0.00 | 0.00 | 0.387192E+10 | 0.00 | 0.00 |
February | 0.334073E+11 | 0.00 | 0.00 | 0.347845E+10 | 0.00 | 0.00 |
March | 0.147282E+11 | 0.00 | 0.00 | 0.416192E+10 | 0.00 | 0.00 |
April | 0.350966E+10 | 0.00 | 0.00 | 0.349216E+10 | 0.00 | 0.00 |
May | 0.209647E+09 | 0.00 | 0.00 | 0.654914E+10 | 0.00 | 0.00 |
June | 1987474.32 | 0.00 | 0.00 | 0.153158E+11 | 0.00 | 0.00 |
July | 1256917.19 | 0.00 | 0.00 | 0.218775E+11 | 0.00 | 0.00 |
August | 612717.35 | 0.00 | 0.00 | 0.197383E+11 | 0.00 | 0.00 |
September | 88392254.67 | 0.00 | 0.00 | 0.108059E+11 | 0.00 | 0.00 |
October | 0.253279E+10 | 0.00 | 0.00 | 0.420351E+10 | 0.00 | 0.00 |
November | 0.840082E+10 | 0.00 | 0.00 | 0.316719E+10 | 0.00 | 0.00 |
December | 0.320850E+11 | 0.00 | 0.00 | 0.358233E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.132816E+12 | 0.00 | 0.00 | 0.100244E+12 | 0.00 | 0.00 |
Minimum of Months | 612717.35 | 0.00 | 0.00 | 0.316719E+10 | 0.00 | 0.00 |
Maximum of Months | 0.378505E+11 | 0.00 | 0.00 | 0.218775E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.574341E+11 | 0.00 | 0.00 | 0.479738E+10 | 0.00 | 0.00 |
February | 0.506499E+11 | 0.00 | 0.00 | 0.438480E+10 | 0.00 | 0.00 |
March | 0.249987E+11 | 0.00 | 0.00 | 0.477444E+10 | 0.00 | 0.00 |
April | 0.841984E+10 | 0.00 | 0.00 | 0.365787E+10 | 0.00 | 0.00 |
May | 0.142404E+10 | 0.00 | 0.00 | 0.685525E+10 | 0.00 | 0.00 |
June | 0.102285E+09 | 0.00 | 0.00 | 0.165123E+11 | 0.00 | 0.00 |
July | 1339358.67 | 0.00 | 0.00 | 0.237038E+11 | 0.00 | 0.00 |
August | 27718115.42 | 0.00 | 0.00 | 0.208061E+11 | 0.00 | 0.00 |
September | 0.823785E+09 | 0.00 | 0.00 | 0.109052E+11 | 0.00 | 0.00 |
October | 0.758418E+10 | 0.00 | 0.00 | 0.426385E+10 | 0.00 | 0.00 |
November | 0.179747E+11 | 0.00 | 0.00 | 0.342785E+10 | 0.00 | 0.00 |
December | 0.514247E+11 | 0.00 | 0.00 | 0.455677E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.220865E+12 | 0.00 | 0.00 | 0.108646E+12 | 0.00 | 0.00 |
Minimum of Months | 1339358.67 | 0.00 | 0.00 | 0.342785E+10 | 0.00 | 0.00 |
Maximum of Months | 0.574341E+11 | 0.00 | 0.00 | 0.237038E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.401053E+10 | 0.00 | 0.368013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361765E+10 | 0.00 | 0.323515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403661E+10 | 0.261508E+10 | 0.177409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.385346E+10 | 0.104518E+10 | 0.729218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.483084E+10 | 0.101626E+11 | 0.197309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.652842E+10 | 0.415866E+11 | 0.292210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.756995E+10 | 0.688646E+11 | 50759762.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.813188E+10 | 0.613694E+11 | 0.104452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.612445E+10 | 0.290843E+11 | 0.380877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439028E+10 | 0.372744E+10 | 0.251660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.364855E+10 | 0.686711E+09 | 0.811437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365065E+10 | 2599374.28 | 0.284267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.603933E+11 | 0.219145E+12 | 0.136045E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361765E+10 | 0.00 | 50759762.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.813188E+10 | 0.688646E+11 | 0.368013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.387192E+10 | 0.00 | 0.378505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347840E+10 | 185588.94 | 0.334073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356563E+10 | 0.245167E+10 | 0.147282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.323732E+10 | 0.953798E+09 | 0.350966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.413905E+10 | 0.971151E+10 | 0.209647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.589545E+10 | 0.398155E+11 | 1987474.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.675862E+10 | 0.644245E+11 | 1256917.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.681092E+10 | 0.548376E+11 | 612717.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482736E+10 | 0.251994E+11 | 88392254.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.339226E+10 | 0.315445E+10 | 0.253279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300797E+10 | 0.596451E+09 | 0.840082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358200E+10 | 1141951.03 | 0.320850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.525669E+11 | 0.201146E+12 | 0.132816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300797E+10 | 0.00 | 612717.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.681092E+10 | 0.644245E+11 | 0.378505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.479647E+10 | 3190351.59 | 0.574341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438424E+10 | 1952277.57 | 0.506499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401862E+10 | 0.305795E+10 | 0.249987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336692E+10 | 0.107897E+10 | 0.841984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393203E+10 | 0.116709E+11 | 0.142404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.534530E+10 | 0.464329E+11 | 0.102285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.603223E+10 | 0.743168E+11 | 1339358.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587396E+10 | 0.622261E+11 | 27718115.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.413551E+10 | 0.278504E+11 | 0.823785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335562E+10 | 0.346700E+10 | 0.758418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323354E+10 | 0.721183E+09 | 0.179747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455524E+10 | 5343802.74 | 0.514247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.530297E+11 | 0.230833E+12 | 0.220865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323354E+10 | 1952277.57 | 1339358.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.603223E+10 | 0.743168E+11 | 0.574341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.401053E+10 | 0.368013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361765E+10 | 0.323515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403661E+10 | 0.177409E+11 | 0.00 | 0.00 | 0.634670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.385346E+10 | 0.729218E+10 | 0.00 | 0.00 | 0.277591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.483084E+10 | 0.197309E+10 | 0.00 | 0.00 | 0.251340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.652842E+10 | 0.292210E+09 | 0.00 | 0.00 | 0.978881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.756995E+10 | 50759762.25 | 0.00 | 0.00 | 0.160984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.813188E+10 | 0.104452E+09 | 0.00 | 0.00 | 0.143799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.612445E+10 | 0.380877E+09 | 0.00 | 0.00 | 0.683230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439028E+10 | 0.251660E+10 | 0.00 | 0.00 | 0.945755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.364855E+10 | 0.811437E+10 | 0.00 | 0.00 | 0.182070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365065E+10 | 0.284267E+11 | 0.00 | 0.00 | 741046.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.603933E+11 | 0.136045E+12 | 0.00 | 0.00 | 0.516536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361765E+10 | 50759762.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.813188E+10 | 0.368013E+11 | 0.00 | 0.00 | 0.160984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.387192E+10 | 0.378505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347840E+10 | 0.334073E+11 | 0.00 | 0.00 | 52867.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356563E+10 | 0.147282E+11 | 0.00 | 0.00 | 0.596291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.323732E+10 | 0.350966E+10 | 0.00 | 0.00 | 0.254841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.413905E+10 | 0.209647E+09 | 0.00 | 0.00 | 0.241009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.589545E+10 | 1987474.32 | 0.00 | 0.00 | 0.942031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.675862E+10 | 1256917.19 | 0.00 | 0.00 | 0.151189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.681092E+10 | 612717.35 | 0.00 | 0.00 | 0.129274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482736E+10 | 88392254.67 | 0.00 | 0.00 | 0.597853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.339226E+10 | 0.253279E+10 | 0.00 | 0.00 | 0.811254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300797E+10 | 0.840082E+10 | 0.00 | 0.00 | 0.159220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358200E+10 | 0.320850E+11 | 0.00 | 0.00 | 326746.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.525669E+11 | 0.132816E+12 | 0.00 | 0.00 | 0.476772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300797E+10 | 612717.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.681092E+10 | 0.378505E+11 | 0.00 | 0.00 | 0.151189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.479647E+10 | 0.574341E+11 | 0.00 | 0.00 | 912656.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438424E+10 | 0.506499E+11 | 0.00 | 0.00 | 559447.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401862E+10 | 0.249987E+11 | 0.00 | 0.00 | 0.755821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336692E+10 | 0.841984E+10 | 0.00 | 0.00 | 0.290945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393203E+10 | 0.142404E+10 | 0.00 | 0.00 | 0.292322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.534530E+10 | 0.102285E+09 | 0.00 | 0.00 | 0.111670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.603223E+10 | 1339358.67 | 0.00 | 0.00 | 0.176716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587396E+10 | 27718115.42 | 0.00 | 0.00 | 0.149321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.413551E+10 | 0.823785E+09 | 0.00 | 0.00 | 0.676974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335562E+10 | 0.758418E+10 | 0.00 | 0.00 | 0.908232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323354E+10 | 0.179747E+11 | 0.00 | 0.00 | 0.194309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455524E+10 | 0.514247E+11 | 0.00 | 0.00 | 1532389.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.530297E+11 | 0.220865E+12 | 0.00 | 0.00 | 0.556160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.323354E+10 | 1339358.67 | 0.00 | 0.00 | 559447.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.603223E+10 | 0.574341E+11 | 0.00 | 0.00 | 0.176716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137198E+11 | 0.00 | 0.00 | 1530797.92 | 0.00 | 0.347689E+09 | 0.230176E+10 | 0.00 | 0.27 |
February | 0.129036E+11 | 0.00 | 0.00 | 1609956.29 | 0.00 | 13258613.91 | 0.226560E+10 | 0.00 | 0.27 |
March | 0.764421E+10 | 7544218.15 | 0.00 | 16383557.69 | 0.00 | 0.00 | 0.905260E+10 | 0.00 | 0.39 |
April | 0.282908E+10 | 0.00 | 0.00 | 27848531.68 | 0.00 | 0.00 | 0.148966E+11 | 0.00 | 0.56 |
May | 0.995895E+09 | 2626531.87 | 0.00 | 42800293.47 | 2252222.17 | 0.00 | 0.187829E+11 | 0.00 | 0.88 |
June | 0.348317E+09 | 0.112148E+10 | 0.00 | 37891398.65 | 25085599.34 | 0.00 | 0.120516E+11 | 0.00 | 0.89 |
July | 0.163612E+09 | 0.351874E+10 | 0.00 | 21062954.50 | 64316110.08 | 0.00 | 0.325174E+10 | 0.00 | 0.51 |
August | 0.279027E+09 | 0.160896E+10 | 0.00 | 38423198.84 | 23044025.88 | 0.00 | 0.763081E+10 | 0.00 | 0.73 |
September | 0.108765E+10 | 0.584373E+09 | 0.00 | 41697598.56 | 10126842.97 | 0.00 | 0.149103E+11 | 0.00 | 0.98 |
October | 0.122506E+10 | 0.00 | 0.00 | 40615281.84 | 0.00 | 0.00 | 0.189813E+11 | 0.00 | 0.70 |
November | 0.338016E+10 | 0.00 | 0.00 | 23987012.67 | 2284877.27 | 0.00 | 0.128276E+11 | 0.00 | 0.44 |
December | 0.110599E+11 | 0.00 | 0.00 | 4644688.36 | 0.00 | 5365797.04 | 0.459428E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.556364E+11 | 0.684371E+10 | 0.00 | 0.298495E+09 | 0.127110E+09 | 0.366313E+09 | 0.121547E+12 | 0.00 | 0.58 |
Minimum of Months | 0.163612E+09 | 0.00 | 0.00 | 1530797.92 | 0.00 | 0.00 | 0.226560E+10 | 0.00 | 0.27 |
Maximum of Months | 0.137198E+11 | 0.351874E+10 | 0.00 | 42800293.47 | 64316110.08 | 0.347689E+09 | 0.189813E+11 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131789E+10 | 0.00 | 0.00 | 0.24 |
February | 0.126097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105784E+10 | 0.00 | 0.00 | 0.25 |
March | 0.116748E+11 | 3045073.78 | 0.00 | 2711665.00 | 4617898.60 | 0.169754E+09 | 0.149709E+10 | 0.00 | 0.31 |
April | 0.752956E+10 | 0.00 | 0.00 | 6499923.00 | 0.00 | 39141680.16 | 0.441479E+10 | 0.00 | 0.38 |
May | 0.415126E+10 | 1673741.00 | 0.00 | 19620185.29 | 2461940.79 | 0.00 | 0.938720E+10 | 0.00 | 0.60 |
June | 0.101500E+10 | 0.916145E+09 | 0.00 | 21718758.73 | 47893357.97 | 0.00 | 0.743561E+10 | 0.00 | 0.63 |
July | 0.383831E+09 | 0.279048E+10 | 0.00 | 13092844.71 | 90673840.97 | 0.00 | 0.185661E+10 | 0.00 | 0.37 |
August | 0.673740E+09 | 0.133193E+10 | 0.00 | 23287454.30 | 28868750.73 | 0.00 | 0.449816E+10 | 0.00 | 0.51 |
September | 0.243901E+10 | 0.495978E+09 | 0.00 | 20060455.26 | 18712017.04 | 0.00 | 0.737556E+10 | 0.00 | 0.64 |
October | 0.662022E+10 | 0.00 | 0.00 | 9931125.68 | 0.00 | 3365006.66 | 0.542881E+10 | 0.00 | 0.43 |
November | 0.924008E+10 | 0.00 | 0.00 | 1280101.46 | 5676089.90 | 30692935.59 | 0.145142E+10 | 0.00 | 0.30 |
December | 0.129399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864552E+09 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.827520E+11 | 0.553925E+10 | 0.00 | 0.118203E+09 | 0.198904E+09 | 0.348323E+10 | 0.433453E+11 | 0.00 | 0.41 |
Minimum of Months | 0.383831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.134749E+11 | 0.279048E+10 | 0.00 | 23287454.30 | 90673840.97 | 0.131789E+10 | 0.938720E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.748959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522721E+10 | 0.00 | 0.00 | 0.22 |
February | 0.772264E+10 | 0.00 | 0.00 | 0.00 | 1945.43 | 0.416495E+10 | 0.00 | 0.00 | 0.22 |
March | 0.103452E+11 | 1195943.09 | 0.00 | 1485589.93 | 2344415.13 | 0.129280E+10 | 0.595452E+09 | 0.00 | 0.31 |
April | 0.958118E+10 | 0.00 | 0.00 | 2403349.34 | 0.00 | 0.224828E+09 | 0.230424E+10 | 0.00 | 0.40 |
May | 0.611206E+10 | 0.00 | 0.00 | 14773500.18 | 6517771.96 | 6822665.45 | 0.755047E+10 | 0.00 | 0.61 |
June | 0.197888E+10 | 0.860256E+09 | 0.00 | 20001361.59 | 0.130451E+09 | 0.00 | 0.645363E+10 | 0.00 | 0.63 |
July | 0.591595E+09 | 0.269191E+10 | 0.00 | 11487621.07 | 0.249672E+09 | 0.00 | 0.122926E+10 | 0.00 | 0.36 |
August | 0.125764E+10 | 0.133243E+10 | 0.00 | 19888674.19 | 0.148834E+09 | 0.00 | 0.296713E+10 | 0.00 | 0.49 |
September | 0.408049E+10 | 0.451993E+09 | 0.00 | 12477242.59 | 0.201149E+09 | 940376.01 | 0.447326E+10 | 0.00 | 0.61 |
October | 0.910115E+10 | 0.00 | 0.00 | 2373233.87 | 0.00 | 0.169116E+09 | 0.177030E+10 | 0.00 | 0.43 |
November | 0.919796E+10 | 0.00 | 959960.89 | 0.00 | 11581249.96 | 0.575856E+09 | 0.00 | 40736.33 | 0.30 |
December | 0.766334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419726E+10 | 0.00 | 0.00 | 0.22 |
Annual Sum or Average | 0.751217E+11 | 0.533778E+10 | 959960.89 | 84890572.75 | 0.750550E+09 | 0.158598E+11 | 0.273437E+11 | 40736.33 | 0.40 |
Minimum of Months | 0.591595E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.103452E+11 | 0.269191E+10 | 959960.89 | 20001361.59 | 0.249672E+09 | 0.522721E+10 | 0.755047E+10 | 40736.33 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586198E+10 | 0.00 | 0.00 | 0.49 |
February | 0.542702E+09 | 0.00 | 0.00 | 0.00 | 912.35 | 0.510708E+10 | 0.00 | 0.00 | 0.50 |
March | 0.265474E+10 | 0.00 | 0.00 | 93651.98 | 1660328.74 | 0.305337E+10 | 30412879.24 | 0.00 | 0.68 |
April | 0.449925E+10 | 0.00 | 0.00 | 8689.71 | 0.00 | 0.101677E+10 | 91611054.83 | 0.00 | 0.87 |
May | 0.491710E+10 | 0.00 | 0.00 | 942031.44 | 3056652.30 | 99066979.94 | 0.804495E+09 | 0.00 | 1.23 |
June | 0.199832E+10 | 0.259363E+09 | 0.00 | 3031268.92 | 0.123615E+09 | 1604652.45 | 0.112970E+10 | 0.00 | 1.10 |
July | 0.391342E+09 | 0.740143E+09 | 0.00 | 2557250.98 | 0.381513E+09 | 0.00 | 0.282669E+09 | 0.00 | 0.66 |
August | 0.108551E+10 | 0.314472E+09 | 0.00 | 3735175.85 | 0.249336E+09 | 821035.38 | 0.540089E+09 | 0.00 | 0.88 |
September | 0.303095E+10 | 75559666.01 | 0.00 | 1050761.54 | 0.197067E+09 | 57389071.71 | 0.505540E+09 | 0.00 | 1.20 |
October | 0.421631E+10 | 0.00 | 0.00 | 1758.81 | 0.00 | 0.893172E+09 | 31091660.11 | 0.00 | 0.94 |
November | 0.228073E+10 | 0.00 | 2069793.27 | 0.00 | 3734980.18 | 0.230298E+10 | 0.00 | 22332.94 | 0.66 |
December | 0.404407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519946E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.261689E+11 | 0.138954E+10 | 2069793.27 | 11420589.22 | 0.959985E+09 | 0.235937E+11 | 0.341561E+10 | 22332.94 | 0.81 |
Minimum of Months | 0.147480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.491710E+10 | 0.740143E+09 | 2069793.27 | 3735175.85 | 0.381513E+09 | 0.586198E+10 | 0.112970E+10 | 22332.94 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371515E+10 | 0.00 | 0.00 | 0.50 |
February | 0.744397E+09 | 0.00 | 0.00 | 0.00 | 589.22 | 0.288824E+10 | 0.00 | 0.00 | 0.51 |
March | 0.223150E+10 | 1072276.93 | 0.00 | 178488.70 | 0.00 | 0.142872E+10 | 34700741.15 | 0.00 | 0.69 |
April | 0.248224E+10 | 0.00 | 0.00 | 775076.40 | 0.00 | 0.419997E+09 | 0.761955E+09 | 0.00 | 0.89 |
May | 0.216246E+10 | 0.00 | 0.00 | 3371211.95 | 1974053.50 | 26102714.33 | 0.185987E+10 | 0.00 | 1.37 |
June | 0.760465E+09 | 0.228274E+09 | 0.00 | 4848205.47 | 58363477.88 | 0.00 | 0.174745E+10 | 0.00 | 1.35 |
July | 0.142893E+09 | 0.629018E+09 | 0.00 | 3855941.35 | 0.183560E+09 | 0.00 | 0.500531E+09 | 0.00 | 0.87 |
August | 0.530432E+09 | 0.284097E+09 | 0.00 | 4914701.88 | 0.119904E+09 | 530242.76 | 0.680520E+09 | 0.00 | 1.06 |
September | 0.139160E+10 | 77315667.31 | 0.00 | 2842479.53 | 0.106553E+09 | 20088490.48 | 0.108056E+10 | 0.00 | 1.32 |
October | 0.271566E+10 | 0.00 | 0.00 | 172493.00 | 0.00 | 0.445821E+09 | 0.162080E+09 | 0.00 | 0.97 |
November | 0.162687E+10 | 0.00 | 1334608.26 | 0.00 | 2412132.60 | 0.133359E+10 | 0.00 | 13839.27 | 0.68 |
December | 0.279576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333663E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.152331E+11 | 0.121978E+10 | 1334608.26 | 20958598.29 | 0.472767E+09 | 0.136149E+11 | 0.682767E+10 | 13839.27 | 0.89 |
Minimum of Months | 0.142893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.271566E+10 | 0.629018E+09 | 1334608.26 | 4914701.88 | 0.183560E+09 | 0.371515E+10 | 0.185987E+10 | 13839.27 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148879E+10 | 0.00 | 0.00 | 10432.90 | 0.00 | 0.445729E+10 | 46984218.14 | 0.00 | 0.49 |
February | 0.180869E+10 | 0.00 | 0.00 | 159772.64 | 911.94 | 0.370508E+10 | 0.108320E+09 | 0.00 | 0.50 |
March | 0.327148E+10 | 2797946.34 | 0.00 | 1223489.24 | 0.00 | 0.185316E+10 | 0.627607E+09 | 0.00 | 0.69 |
April | 0.350912E+10 | 0.00 | 0.00 | 2385161.83 | 0.00 | 0.763296E+09 | 0.160021E+10 | 0.00 | 0.91 |
May | 0.372117E+10 | 0.00 | 0.00 | 4368766.09 | 3055253.07 | 0.106687E+09 | 0.229667E+10 | 0.00 | 1.30 |
June | 0.167752E+10 | 0.285344E+09 | 0.00 | 5293208.39 | 0.121648E+09 | 5047613.40 | 0.168530E+10 | 0.00 | 1.18 |
July | 0.402711E+09 | 0.884234E+09 | 0.00 | 3633859.15 | 0.337872E+09 | 0.00 | 0.339814E+09 | 0.00 | 0.71 |
August | 0.999396E+09 | 0.407769E+09 | 0.00 | 6826698.71 | 0.211420E+09 | 820659.54 | 0.768466E+09 | 0.00 | 0.96 |
September | 0.216360E+10 | 0.130376E+09 | 0.00 | 5891799.37 | 0.173306E+09 | 37682351.99 | 0.196638E+10 | 0.00 | 1.40 |
October | 0.347842E+10 | 0.00 | 0.00 | 3441523.98 | 0.00 | 0.549319E+09 | 0.145655E+10 | 0.00 | 1.03 |
November | 0.263312E+10 | 0.00 | 1494893.20 | 715468.63 | 4303244.31 | 0.164077E+10 | 0.349847E+09 | 17642.50 | 0.67 |
December | 0.134416E+10 | 0.00 | 0.00 | 2599.99 | 0.00 | 0.422781E+10 | 14793266.05 | 0.00 | 0.50 |
Annual Sum or Average | 0.264982E+11 | 0.171052E+10 | 1494893.20 | 33952780.90 | 0.851605E+09 | 0.173470E+11 | 0.112609E+11 | 17642.50 | 0.86 |
Minimum of Months | 0.402711E+09 | 0.00 | 0.00 | 2599.99 | 0.00 | 0.00 | 14793266.05 | 0.00 | 0.49 |
Maximum of Months | 0.372117E+10 | 0.884234E+09 | 1494893.20 | 6826698.71 | 0.337872E+09 | 0.445729E+10 | 0.229667E+10 | 17642.50 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.349532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393571E+10 | 0.00 | 0.00 | 0.55 |
February | 0.681108E+09 | 0.00 | 0.00 | 0.00 | 652.45 | 0.334311E+10 | 0.00 | 0.00 | 0.57 |
March | 0.218145E+10 | 60034.41 | 0.00 | 185010.81 | 1127308.83 | 0.180935E+10 | 0.106441E+09 | 0.00 | 0.76 |
April | 0.270234E+10 | 0.00 | 0.00 | 1039678.68 | 0.00 | 0.637401E+09 | 0.792902E+09 | 0.00 | 1.01 |
May | 0.297297E+10 | 0.00 | 0.00 | 2961167.45 | 2185889.69 | 77802902.97 | 0.150035E+10 | 0.00 | 1.52 |
June | 0.123564E+10 | 0.225457E+09 | 0.00 | 4170452.96 | 76241526.41 | 2996493.97 | 0.134466E+10 | 0.00 | 1.42 |
July | 0.290671E+09 | 0.607510E+09 | 0.00 | 2433743.49 | 0.266878E+09 | 0.00 | 0.227235E+09 | 0.00 | 0.81 |
August | 0.757853E+09 | 0.264552E+09 | 0.00 | 4023050.41 | 0.165088E+09 | 587143.25 | 0.477663E+09 | 0.00 | 1.06 |
September | 0.197549E+10 | 59956614.57 | 0.00 | 2179789.29 | 0.139020E+09 | 34374551.81 | 0.727401E+09 | 0.00 | 1.45 |
October | 0.282579E+10 | 0.00 | 0.00 | 434565.58 | 0.00 | 0.578286E+09 | 0.282755E+09 | 0.00 | 1.07 |
November | 0.168457E+10 | 0.00 | 1475422.83 | 0.00 | 2670979.17 | 0.159277E+10 | 0.00 | 14514.71 | 0.75 |
December | 0.400367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359931E+10 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.180578E+11 | 0.115753E+10 | 1475422.83 | 17427458.68 | 0.653213E+09 | 0.156117E+11 | 0.545941E+10 | 14514.71 | 0.96 |
Minimum of Months | 0.290671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.297297E+10 | 0.607510E+09 | 1475422.83 | 4170452.96 | 0.266878E+09 | 0.393571E+10 | 0.150035E+10 | 14514.71 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535345E+10 | 0.00 | 0.00 | 0.42 |
February | 0.218639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496607E+10 | 0.00 | 0.00 | 0.43 |
March | 0.178626E+10 | 0.00 | 0.00 | 0.00 | 2168393.66 | 0.343086E+10 | 0.00 | 0.00 | 0.56 |
April | 0.359937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124843E+10 | 0.00 | 0.00 | 0.71 |
May | 0.449657E+10 | 0.00 | 0.00 | 10541.19 | 1402778.65 | 74845136.73 | 5263833.93 | 0.00 | 0.94 |
June | 0.200007E+10 | 0.139925E+09 | 0.00 | 1053051.91 | 93401009.30 | 0.00 | 0.445478E+09 | 0.00 | 0.82 |
July | 0.430662E+09 | 0.539135E+09 | 0.00 | 1587403.65 | 0.209275E+09 | 0.00 | 0.232576E+09 | 0.00 | 0.48 |
August | 0.100236E+10 | 0.251898E+09 | 0.00 | 2996760.49 | 89549015.51 | 0.00 | 0.531360E+09 | 0.00 | 0.66 |
September | 0.275055E+10 | 65245697.29 | 0.00 | 1112469.31 | 58198124.79 | 679120.33 | 0.552315E+09 | 0.00 | 0.94 |
October | 0.467949E+10 | 0.00 | 0.00 | 13989.96 | 0.00 | 0.187143E+09 | 48125404.85 | 0.00 | 0.79 |
November | 0.353531E+10 | 0.00 | 0.00 | 0.00 | 754903.36 | 0.107782E+10 | 0.00 | 0.00 | 0.58 |
December | 0.739917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446069E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.254002E+11 | 0.996203E+09 | 0.00 | 6774216.53 | 0.454749E+09 | 0.208000E+11 | 0.181512E+10 | 0.00 | 0.65 |
Minimum of Months | 0.160956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.467949E+10 | 0.539135E+09 | 0.00 | 2996760.49 | 0.209275E+09 | 0.535345E+10 | 0.552315E+09 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354637E+10 | 0.00 | 0.00 | 0.45 |
February | 0.489834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302540E+10 | 0.00 | 0.00 | 0.46 |
March | 0.184309E+10 | 0.00 | 0.00 | 6620.04 | 1482020.92 | 0.169923E+10 | 2933886.97 | 0.00 | 0.60 |
April | 0.264522E+10 | 0.00 | 0.00 | 191425.92 | 0.00 | 0.459286E+09 | 0.212441E+09 | 0.00 | 0.77 |
May | 0.240043E+10 | 73639.45 | 0.00 | 1333970.86 | 885110.50 | 15098958.21 | 0.786099E+09 | 0.00 | 1.05 |
June | 0.726224E+09 | 0.169119E+09 | 0.00 | 3355705.45 | 23042899.94 | 0.00 | 0.125690E+10 | 0.00 | 1.05 |
July | 0.156010E+09 | 0.518490E+09 | 0.00 | 3218680.36 | 75388431.32 | 0.00 | 0.507574E+09 | 0.00 | 0.70 |
August | 0.440554E+09 | 0.221757E+09 | 0.00 | 4823846.57 | 43480796.16 | 0.00 | 0.826979E+09 | 0.00 | 0.89 |
September | 0.133397E+10 | 64149333.33 | 0.00 | 3377980.93 | 27656066.25 | 464154.90 | 0.121561E+10 | 0.00 | 1.15 |
October | 0.292137E+10 | 0.00 | 0.00 | 438164.92 | 0.00 | 67765533.66 | 0.378645E+09 | 0.00 | 0.85 |
November | 0.256422E+10 | 0.00 | 0.00 | 0.00 | 515949.94 | 0.588571E+09 | 0.00 | 0.00 | 0.63 |
December | 0.526927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302190E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.162590E+11 | 0.973589E+09 | 0.00 | 16746395.04 | 0.172451E+09 | 0.124241E+11 | 0.518718E+10 | 0.00 | 0.76 |
Minimum of Months | 0.156010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.292137E+10 | 0.518490E+09 | 0.00 | 4823846.57 | 75388431.32 | 0.354637E+10 | 0.125690E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.368458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603793E+10 | 0.00 | 0.00 | 0.49 |
February | 0.354321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560923E+10 | 0.00 | 0.00 | 0.49 |
March | 0.192225E+10 | 2459783.02 | 0.00 | 199472.65 | 151154.55 | 0.381651E+10 | 7516492.39 | 0.00 | 0.61 |
April | 0.286764E+10 | 0.00 | 0.00 | 137647.88 | 0.00 | 0.210801E+10 | 0.202071E+09 | 0.00 | 0.75 |
May | 0.368979E+10 | 131421.42 | 0.00 | 618124.89 | 1295032.53 | 0.748510E+09 | 0.257021E+09 | 0.00 | 0.96 |
June | 0.182215E+10 | 0.210658E+09 | 0.00 | 1913858.29 | 70497710.71 | 0.203791E+09 | 0.469743E+09 | 0.00 | 0.85 |
July | 0.421446E+09 | 0.776687E+09 | 0.00 | 2314743.92 | 0.134442E+09 | 54530818.47 | 0.217554E+09 | 0.00 | 0.53 |
August | 0.934820E+09 | 0.374211E+09 | 0.00 | 5451787.51 | 61539475.41 | 86687125.65 | 0.613880E+09 | 0.00 | 0.75 |
September | 0.186383E+10 | 0.122378E+09 | 0.00 | 5183112.89 | 28508303.90 | 0.272912E+09 | 0.159400E+10 | 0.00 | 1.10 |
October | 0.358990E+10 | 0.00 | 0.00 | 2103486.82 | 0.00 | 0.821825E+09 | 0.868990E+09 | 0.00 | 0.86 |
November | 0.250852E+10 | 0.00 | 0.00 | 144019.64 | 754902.30 | 0.238199E+10 | 0.129418E+09 | 0.00 | 0.62 |
December | 0.455276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547822E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.207984E+11 | 0.148653E+10 | 0.00 | 18066254.48 | 0.297188E+09 | 0.276201E+11 | 0.436019E+10 | 0.00 | 0.71 |
Minimum of Months | 0.354321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54530818.47 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.368979E+10 | 0.776687E+09 | 0.00 | 5451787.51 | 0.134442E+09 | 0.603793E+10 | 0.159400E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293876E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363602E+10 | 0.00 | 0.00 | 0.48 |
February | 0.385489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329501E+10 | 0.00 | 0.00 | 0.48 |
March | 0.182189E+10 | 0.00 | 0.00 | 10236.37 | 1549280.44 | 0.188930E+10 | 1368082.75 | 0.00 | 0.63 |
April | 0.262545E+10 | 0.00 | 0.00 | 242077.63 | 0.00 | 0.602005E+09 | 0.240557E+09 | 0.00 | 0.80 |
May | 0.275601E+10 | 90925.96 | 0.00 | 1170853.87 | 914054.51 | 31496271.52 | 0.561673E+09 | 0.00 | 1.10 |
June | 0.988298E+09 | 0.156585E+09 | 0.00 | 2907916.53 | 46248135.64 | 0.00 | 0.940845E+09 | 0.00 | 1.05 |
July | 0.275435E+09 | 0.494723E+09 | 0.00 | 1997253.64 | 0.125662E+09 | 0.00 | 0.224805E+09 | 0.00 | 0.61 |
August | 0.621534E+09 | 0.239335E+09 | 0.00 | 3697318.51 | 48995502.65 | 0.00 | 0.531368E+09 | 0.00 | 0.82 |
September | 0.159537E+10 | 51745968.42 | 0.00 | 2413706.31 | 38635627.15 | 1009199.44 | 0.910197E+09 | 0.00 | 1.15 |
October | 0.313459E+10 | 0.00 | 0.00 | 448788.97 | 0.00 | 91180796.43 | 0.297471E+09 | 0.00 | 0.89 |
November | 0.259986E+10 | 0.00 | 0.00 | 1182.66 | 539365.63 | 0.679995E+09 | 15889395.83 | 0.00 | 0.66 |
December | 0.605406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310401E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.177032E+11 | 0.942480E+09 | 0.00 | 12889334.50 | 0.262543E+09 | 0.133300E+11 | 0.372417E+10 | 0.00 | 0.76 |
Minimum of Months | 0.275435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.313459E+10 | 0.494723E+09 | 0.00 | 3697318.51 | 0.125662E+09 | 0.363602E+10 | 0.940845E+09 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.589664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554734E+10 | 0.00 | 0.00 | 0.48 |
February | 0.109307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461575E+10 | 0.00 | 0.00 | 0.49 |
March | 0.299051E+10 | 350612.80 | 0.00 | 157854.36 | 2800394.80 | 0.240104E+10 | 40787560.79 | 0.00 | 0.59 |
April | 0.419581E+10 | 0.00 | 0.00 | 39090.71 | 0.00 | 0.476133E+09 | 0.127358E+09 | 0.00 | 0.71 |
May | 0.373662E+10 | 471867.07 | 0.00 | 1411413.12 | 1055936.95 | 7271133.78 | 0.102128E+10 | 0.00 | 0.99 |
June | 0.126208E+10 | 0.308684E+09 | 0.00 | 3867057.16 | 28855484.00 | 0.00 | 0.132989E+10 | 0.00 | 0.92 |
July | 0.330128E+09 | 0.900131E+09 | 0.00 | 2684957.24 | 98459059.29 | 0.00 | 0.359882E+09 | 0.00 | 0.57 |
August | 0.870149E+09 | 0.381650E+09 | 0.00 | 4244053.92 | 77159414.77 | 0.00 | 0.714965E+09 | 0.00 | 0.75 |
September | 0.241873E+10 | 0.101939E+09 | 0.00 | 1985918.90 | 74713737.24 | 3848817.69 | 0.786038E+09 | 0.00 | 0.98 |
October | 0.424884E+10 | 0.00 | 0.00 | 92070.58 | 0.00 | 0.266086E+09 | 0.153050E+09 | 0.00 | 0.78 |
November | 0.306356E+10 | 0.00 | 76724.29 | 0.00 | 2268644.89 | 0.134621E+10 | 0.00 | 9317.36 | 0.58 |
December | 0.866665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486225E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.256658E+11 | 0.169323E+10 | 76724.29 | 14482415.99 | 0.285313E+09 | 0.195259E+11 | 0.453325E+10 | 9317.36 | 0.69 |
Minimum of Months | 0.330128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.424884E+10 | 0.900131E+09 | 76724.29 | 4244053.92 | 98459059.29 | 0.554734E+10 | 0.132989E+10 | 9317.36 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.556278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354286E+10 | 0.00 | 0.00 | 0.50 |
February | 0.921613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286464E+10 | 0.00 | 0.00 | 0.51 |
March | 0.220494E+10 | 1985373.47 | 0.00 | 308198.75 | 2190.75 | 0.128177E+10 | 0.122881E+09 | 0.00 | 0.63 |
April | 0.233969E+10 | 0.00 | 0.00 | 1319864.35 | 0.00 | 0.218809E+09 | 0.850644E+09 | 0.00 | 0.80 |
May | 0.200903E+10 | 344300.87 | 0.00 | 3686977.91 | 851636.96 | 3617484.94 | 0.183538E+10 | 0.00 | 1.28 |
June | 0.772934E+09 | 0.238237E+09 | 0.00 | 4746754.26 | 30354949.68 | 0.00 | 0.171528E+10 | 0.00 | 1.31 |
July | 0.196468E+09 | 0.670834E+09 | 0.00 | 3747289.80 | 99219191.78 | 0.00 | 0.595371E+09 | 0.00 | 0.87 |
August | 0.558347E+09 | 0.280333E+09 | 0.00 | 4904212.78 | 71972892.28 | 0.00 | 0.854038E+09 | 0.00 | 1.05 |
September | 0.145511E+10 | 77194529.07 | 0.00 | 3329682.26 | 62462358.44 | 3633881.15 | 0.119624E+10 | 0.00 | 1.28 |
October | 0.256391E+10 | 0.00 | 0.00 | 721294.95 | 0.00 | 0.156282E+09 | 0.429509E+09 | 0.00 | 0.84 |
November | 0.196144E+10 | 0.00 | 160674.63 | 24379.35 | 1740648.56 | 0.931419E+09 | 14433207.54 | 6427.20 | 0.60 |
December | 0.556743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324977E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.160965E+11 | 0.126893E+10 | 160674.63 | 22788654.42 | 0.266604E+09 | 0.122528E+11 | 0.761378E+10 | 6427.20 | 0.85 |
Minimum of Months | 0.196468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.256391E+10 | 0.670834E+09 | 160674.63 | 4904212.78 | 99219191.78 | 0.354286E+10 | 0.183538E+10 | 6427.20 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195067E+10 | 0.00 | 0.00 | 204083.59 | 0.00 | 0.401181E+10 | 0.163467E+09 | 0.00 | 0.48 |
February | 0.211820E+10 | 0.00 | 0.00 | 342805.74 | 0.00 | 0.336990E+10 | 0.228018E+09 | 0.00 | 0.49 |
March | 0.333599E+10 | 6827513.60 | 0.00 | 2107812.89 | 0.00 | 0.124087E+10 | 0.985153E+09 | 0.00 | 0.62 |
April | 0.320471E+10 | 0.00 | 0.00 | 3157168.71 | 0.00 | 0.362486E+09 | 0.164879E+10 | 0.00 | 0.80 |
May | 0.288548E+10 | 986034.29 | 0.00 | 5101236.14 | 920518.86 | 10764579.33 | 0.231167E+10 | 0.00 | 1.11 |
June | 0.117837E+10 | 0.341312E+09 | 0.00 | 5725397.35 | 32618419.36 | 0.00 | 0.171405E+10 | 0.00 | 1.04 |
July | 0.379144E+09 | 0.105559E+10 | 0.00 | 3445482.40 | 96878904.51 | 0.00 | 0.376382E+09 | 0.00 | 0.63 |
August | 0.811681E+09 | 0.482326E+09 | 0.00 | 6875233.35 | 62946734.15 | 0.00 | 0.951575E+09 | 0.00 | 0.86 |
September | 0.178286E+10 | 0.165595E+09 | 0.00 | 7333602.41 | 54578046.08 | 3094807.04 | 0.222856E+10 | 0.00 | 1.28 |
October | 0.324432E+10 | 0.00 | 0.00 | 5096944.95 | 0.00 | 0.149151E+09 | 0.192827E+10 | 0.00 | 0.95 |
November | 0.298620E+10 | 0.00 | 72170.99 | 1503360.09 | 2266641.61 | 0.916577E+09 | 0.663939E+09 | 8393.59 | 0.60 |
December | 0.197659E+10 | 0.00 | 0.00 | 84819.37 | 0.00 | 0.363858E+10 | 94953499.96 | 0.00 | 0.48 |
Annual Sum or Average | 0.258542E+11 | 0.205263E+10 | 72170.99 | 40977946.99 | 0.250209E+09 | 0.137032E+11 | 0.132948E+11 | 8393.59 | 0.78 |
Minimum of Months | 0.379144E+09 | 0.00 | 0.00 | 84819.37 | 0.00 | 0.00 | 94953499.96 | 0.00 | 0.48 |
Maximum of Months | 0.333599E+10 | 0.105559E+10 | 72170.99 | 7333602.41 | 96878904.51 | 0.401181E+10 | 0.231167E+10 | 8393.59 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.769582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437302E+10 | 0.00 | 0.00 | 0.63 |
February | 0.109893E+10 | 0.00 | 0.00 | 1022.79 | 0.00 | 0.367066E+10 | 8460636.26 | 0.00 | 0.64 |
March | 0.278412E+10 | 418789.95 | 0.00 | 215950.53 | 2235223.18 | 0.161505E+10 | 0.166102E+09 | 0.00 | 0.79 |
April | 0.309906E+10 | 0.00 | 0.00 | 1063488.92 | 0.00 | 0.364892E+09 | 0.707118E+09 | 0.00 | 0.99 |
May | 0.294209E+10 | 615480.19 | 0.00 | 2819791.82 | 786225.93 | 10353911.84 | 0.142135E+10 | 0.00 | 1.45 |
June | 0.110661E+10 | 0.261110E+09 | 0.00 | 4161233.87 | 39115094.57 | 577704.44 | 0.136362E+10 | 0.00 | 1.37 |
July | 0.336755E+09 | 0.722146E+09 | 0.00 | 2286543.80 | 0.150801E+09 | 0.00 | 0.254422E+09 | 0.00 | 0.79 |
August | 0.786015E+09 | 0.316065E+09 | 0.00 | 3752922.98 | 79010138.54 | 0.00 | 0.573846E+09 | 0.00 | 1.02 |
September | 0.201744E+10 | 70725289.61 | 0.00 | 2409985.01 | 76749310.19 | 3807368.20 | 0.838165E+09 | 0.00 | 1.40 |
October | 0.343618E+10 | 0.00 | 0.00 | 604807.42 | 0.00 | 0.207956E+09 | 0.308288E+09 | 0.00 | 1.05 |
November | 0.260983E+10 | 0.00 | 163999.83 | 12513.62 | 1797020.13 | 0.106498E+10 | 38394072.03 | 6632.99 | 0.77 |
December | 0.918362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388580E+10 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.219050E+11 | 0.137108E+10 | 163999.83 | 17328260.75 | 0.350494E+09 | 0.151971E+11 | 0.567977E+10 | 6632.99 | 0.96 |
Minimum of Months | 0.336755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.343618E+10 | 0.722146E+09 | 163999.83 | 4161233.87 | 0.150801E+09 | 0.437302E+10 | 0.142135E+10 | 6632.99 | 1.45 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.149927E+12 | 0.305594E+11 | 0.00 | 0.160883E+12 | 0.654523E+11 |
February | 0.223657E+12 | 0.312830E+11 | 0.00 | 0.149198E+12 | 0.586650E+11 |
March | 0.322637E+12 | 0.209810E+11 | 0.00 | 0.195879E+12 | 0.440604E+11 |
April | 0.376048E+12 | 0.161976E+11 | 0.00 | 0.244197E+12 | 0.165817E+11 |
May | 0.453798E+12 | 0.929359E+10 | 0.00 | 0.272429E+12 | 0.419315E+11 |
June | 0.486546E+12 | 0.311734E+10 | 0.00 | 0.157582E+12 | 0.158505E+12 |
July | 0.451829E+12 | -0.179805E+10 | 0.00 | 0.438135E+11 | 0.256533E+12 |
August | 0.388414E+12 | 0.100376E+10 | 0.00 | 0.123414E+12 | 0.220777E+12 |
September | 0.301024E+12 | 0.509056E+10 | 0.00 | 0.213982E+12 | 0.102644E+12 |
October | 0.209810E+12 | 0.130141E+11 | 0.00 | 0.250053E+12 | 0.214533E+11 |
November | 0.115453E+12 | 0.177259E+11 | 0.00 | 0.196940E+12 | 0.247848E+11 |
December | 0.134730E+12 | 0.315124E+11 | 0.00 | 0.166958E+12 | 0.578822E+11 |
Annual Sum or Average | 0.361387E+13 | 0.177980E+12 | 0.00 | 0.217533E+13 | 0.106927E+13 |
Minimum of Months | 0.115453E+12 | -0.179805E+10 | 0.00 | 0.438135E+11 | 0.165817E+11 |
Maximum of Months | 0.486546E+12 | 0.315124E+11 | 0.00 | 0.272429E+12 | 0.256533E+12 |