Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2024-07-03 12:20:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2459.02 | 493.56 | 493.56 |
Net Site Energy | 2459.02 | 493.56 | 493.56 |
Total Source Energy | 6900.16 | 1384.97 | 1384.97 |
Net Source Energy | 6900.16 | 1384.97 | 1384.97 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 426.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 201.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 235.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 215.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 55.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2032.92 | 426.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 426.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 201.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 235.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 215.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 2.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 55.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 426.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 201.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 235.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 215.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 2.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 55.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 95.16 | 85.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 408.04 | 85.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 95.16 | 85.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 408.04 | 85.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2032.923 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2032.923 | 100.00 |
Total On-Site and Utility Electric Sources | 2032.923 | 100.00 |
Total Electricity End Uses | 2032.923 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 273.67 |
Time Setpoint Not Met During Occupied Cooling | 74.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2614.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-15:09 | 23-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 284245.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89678.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 37569.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4249.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 224294.16 | 284245.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 284245.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 89678.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 37569.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4249.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 461.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 636.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 746.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 681.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 7.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 176.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6438.27 | 461.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 136.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1292.26 | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 136.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1292.26 | 92.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 4.10 | 0.182774 | 0.300000 | 1.23 | 0.487398 | 0.500000 | 0.002085 | 0.000167 | 1.23 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 3.36 | 0.223277 | 0.300000 | 1.01 | 0.595406 | 0.500000 | 0.001706 | 0.000307 | 1.82 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 3.91 | 0.191476 | 0.300000 | 1.17 | 0.510603 | 0.500000 | 0.001990 | 0.000640 | 3.80 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.64 | 0.096111 | 0.300000 | 0.493153 | 0.300000 | 0.500000 | 0.003964 | 0.000277 | 1.64 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.15 | 0.087267 | 0.300000 | 0.343847 | 0.300000 | 0.500000 | 0.004366 | 0.000183 | 1.09 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.66 | 0.095120 | 0.300000 | 0.498293 | 0.300000 | 0.500000 | 0.004005 | 0.000280 | 1.66 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.37 | 0.072928 | 0.300000 | 0.411426 | 0.300000 | 0.500000 | 0.005224 | 0.000183 | 1.09 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.21 | 0.130250 | 0.300000 | 0.363896 | 0.347333 | 0.500000 | 0.002925 | 0.000204 | 1.21 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.923726 | 0.108281 | 0.300000 | 0.277118 | 0.300000 | 0.500000 | 0.003519 | 0.000136 | 0.808827 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.23 | 0.128402 | 0.300000 | 0.369135 | 0.342404 | 0.500000 | 0.002967 | 0.000207 | 1.23 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.03 | 0.097160 | 0.300000 | 0.308815 | 0.300000 | 0.500000 | 0.003921 | 0.000136 | 0.808820 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 1.25 | 0.126806 | 0.300000 | 0.373781 | 0.338148 | 0.500000 | 0.003005 | 0.000210 | 1.25 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 1.14 | 0.300000 | 0.500000 | 0.004334 | 0.000140 | 0.832703 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.29 | 0.122191 | 0.300000 | 0.387897 | 0.325843 | 0.500000 | 0.003118 | 0.000213 | 1.26 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.24 | 0.080781 | 0.300000 | 0.371431 | 0.300000 | 0.500000 | 0.004716 | 0.000140 | 0.832696 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19063.22 | 0.000167 | 422.57 |
CORE_MID VAV BOX REHEAT COIL | 35140.16 | 0.000307 | 821.82 |
CORE_TOP VAV BOX REHEAT COIL | 73179.20 | 0.000640 | 1709.76 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 31628.77 | 0.000277 | 738.62 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20886.10 | 0.000183 | 487.74 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 31957.99 | 0.000280 | 746.30 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 20885.71 | 0.000183 | 487.73 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 23349.75 | 0.000204 | 545.35 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 15568.17 | 0.000136 | 363.60 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 23685.22 | 0.000207 | 553.18 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 15568.03 | 0.000136 | 363.59 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 23983.29 | 0.000210 | 560.14 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 16027.19 | 0.000140 | 374.31 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 24291.11 | 0.000213 | 567.33 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 16027.05 | 0.000140 | 374.31 |
PACU_VAV_BOT HEATING COIL | 19783.82 | 0.000173 | 339.60 |
PACU_VAV_MID HEATING COIL | 23478.70 | 0.000205 | 397.23 |
PACU_VAV_TOP HEATING COIL | 19785.69 | 0.000173 | 344.76 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 4.25 | 2.55 | 8.50 | 4.86 | 7.10 | 7.10 | 0.300000 | 0.684584 | 7.10 |
PACU_VAV_MID | 4.14 | 2.48 | 8.27 | 5.99 | 6.81 | 6.81 | 0.300000 | 0.879427 | 6.81 |
PACU_VAV_TOP | 4.87 | 2.92 | 9.74 | 9.27 | 8.47 | 9.27 | 0.300000 | 1.00 | 9.27 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 7.10 |
PACU_VAV_MID_OA_CONTROLLER | 6.81 |
PACU_VAV_TOP_OA_CONTROLLER | 9.27 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 7.10 | 117524.93 | 0.800655 | 2.37 | 39171.06 | 0.800655 |
PACU_VAV_MID COOLING COIL | 6.81 | 112750.70 | 0.800655 | 2.27 | 37579.81 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 9.27 | 153495.09 | 0.800655 | 3.09 | 51159.91 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 7.10 |
PACU_VAV_MID FAN | 6.81 |
PACU_VAV_TOP FAN | 9.27 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000173 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000205 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000173 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003974 | 0.476918 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.003974 | 1196.89 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 454289.16 | 454289.16 | 0.003974 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
43 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
44 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
45 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
46 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
47 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
48 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
49 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39831.60045 | 45806.34052 | 3.56560 | 4.10044 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7294.69412 | 9118.36764 | 0.63939 | 0.79924 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32627.64083 | 37521.78696 | 2.91879 | 3.35661 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 16362.49208 | 20453.11510 | 1.45338 | 1.81672 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 37722.41410 | 43380.77621 | 3.40356 | 3.91409 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 33988.34637 | 42485.43296 | 3.03734 | 3.79668 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 11174.81722 | 12851.03980 | 1.00821 | 1.15944 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 14674.70125 | 18343.37656 | 1.31507 | 1.64384 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11046.89097 | 12703.92462 | 0.99666 | 1.14616 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9690.06641 | 12112.58302 | 0.86846 | 1.08558 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14378.33344 | 16535.08346 | 1.29723 | 1.49182 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 14827.26402 | 18534.08002 | 1.32878 | 1.66098 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 13218.01300 | 15200.71495 | 1.19254 | 1.37142 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9689.88485 | 12112.35606 | 0.86845 | 1.08556 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7847.66496 | 9024.81471 | 0.70804 | 0.81425 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 10836.41148 | 13545.51435 | 0.97039 | 1.21299 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8902.86658 | 10238.29657 | 0.80324 | 0.92373 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7224.52242 | 9030.65302 | 0.64706 | 0.80883 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10716.54562 | 12324.02746 | 0.96688 | 1.11191 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53000 | 5.47470E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 10991.85243 | 13739.81554 | 0.98436 | 1.23045 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9921.20356 | 11409.38410 | 0.89512 | 1.02938 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.08800 | 5.47095E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7224.45889 | 9030.57361 | 0.64706 | 0.80882 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9114.88910 | 10482.12247 | 0.82237 | 0.94572 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11131.05818 | 13913.82273 | 0.99675 | 1.24594 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10964.86494 | 12609.59468 | 0.98926 | 1.13765 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.29133 | 5.46218E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7437.93878 | 9297.42347 | 0.66616 | 0.83270 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12461.92055 | 14331.20863 | 1.12434 | 1.29299 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11273.68991 | 14092.11239 | 1.00957 | 1.26196 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11932.97381 | 13722.91988 | 1.07661 | 1.23810 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7437.87385 | 9297.34232 | 0.66616 | 0.83270 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 86763.93 | 7.09968 | 7.09968 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 28907.34 | 4.86033 | 4.86033 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 83536.43 | 6.81127 | 6.81127 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 28871.62 | 5.99001 | 5.99001 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 101643.67 | 8.47250 | 8.47250 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 28696.37 | 9.27264 | 9.27264 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.10044 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18277 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.23013 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48740 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08454E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66773E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23013 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19063.21595 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66773E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 422.57305 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.35661 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22328 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.00698 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59541 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70640E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.07421E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.81672 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35140.16339 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.07421E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 821.82413 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.91409 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19148 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.17423 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51060 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98980E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.40204E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.79668 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 73179.19687 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.40204E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1709.76387 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.64384 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.61112E-002 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.49315 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.96416E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.76702E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.64384 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31628.76924 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.76702E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 738.61731 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14616 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.72670E-002 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34385 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.36591E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82721E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.08558 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20886.09985 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82721E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 487.73861 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.66098 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.51197E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.49829 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.00548E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.79582E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.66098 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31957.98590 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.79582E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 746.30235 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37142 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.29282E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41143 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.22432E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82717E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.08556 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20885.70941 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82717E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 487.72949 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21299 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13025 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36390 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34733 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.92514E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.04274E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21299 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23349.75395 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.04274E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 545.35085 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92373 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10828 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27712 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.51863E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36197E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80883 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15568.16631 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36197E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 363.59580 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23045 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12840 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36913 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34240 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96725E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07209E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23045 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23685.21884 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07209E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 553.18149 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02938 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.71602E-002 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30882 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.92136E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36196E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80882 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15568.03062 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36196E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 363.59262 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24594 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12681 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37378 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33815 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00460E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.09816E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.24594 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23983.29477 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09816E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 560.14307 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13765 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.33352E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40213E-004 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83270 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16027.19073 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40213E-004 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 374.31291 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29299 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12219 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38790 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32584 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11807E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.12509E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.26196 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24291.10659 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.12509E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 567.32823 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23810 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.07811E-002 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37143 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.71645E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40212E-004 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83270 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16027.05204 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40212E-004 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 374.30966 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.24849 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.54910 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.49699 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.86033 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.09968 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 7.09968 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.68458 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.13565 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.48139 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.27129 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.99001 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.81127 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 6.81127 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.87943 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.86824 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.92095 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.73649 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 9.27264 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.47250 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 9.27264 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 7.09968 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 6.81127 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 9.27264 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.09968 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 7.09968 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 117524.93268 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.36632 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39171.06006 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 19783.81586 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73077E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 339.59659 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 7.09968 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.73077E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.81127 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.81127 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 112750.69999 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.27020 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37579.80831 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 23478.70058 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05402E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 397.22532 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 6.81127 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.05402E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.27264 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 9.27264 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 153495.09113 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 3.09057 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 51159.91387 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 19785.69278 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73094E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 344.76120 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 9.27264 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.73094E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.97432E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.47692 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.97432E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1196.89059 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 454289.16369 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 454289.16000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.97432E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18096.02 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 33350.32 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 69452.04 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 30017.90 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 19822.36 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 30330.35 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19821.99 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 22160.53 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 14775.27 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 22478.91 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 14775.14 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 22761.80 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 15210.91 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 23053.94 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 15210.78 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 16529.61 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 19073.40 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 17009.96 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 115502.62 | 394111.30 | 11.51 | 2.87 | 3.30 | 3.48 | 3.63 | 9.79 | 11.25 | 11.86 | 12.38 | 6.6654 | 5.2697 | 3.5327 | 1.4961 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 110810.54 | 378101.26 | 11.51 | 2.87 | 3.30 | 3.48 | 3.63 | 9.79 | 11.25 | 11.86 | 12.38 | 6.3947 | 5.0557 | 3.3892 | 1.4353 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 150853.82 | 514734.61 | 11.51 | 2.87 | 3.30 | 3.48 | 3.63 | 9.79 | 11.25 | 11.86 | 12.38 | 8.7055 | 6.8826 | 4.6139 | 1.9539 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 9.0725040547E-003 | 6.6493525693E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2397277246 | 0.1733702583 | Pass | Pass | 0.2946239351 | 0.4423178071 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.0165383900E-002 | 1.2890553965E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6173105949E-002 | 9.9803629492E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.3664954859E-002 | 8.3116313496E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.3504752690E-002 | 3.8460415058E-002 | Pass | Pass | 0.2979765386 | 0.4630931205 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1894721893 | 0.2611644190 | Pass | Pass | 25.2121890961 | 112.9596115234 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1802960318 | 0.2209778096 | Pass | Pass | 13.1776889865 | 66.0918425664 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1918145843 | 0.1720956210 | Pass | Pass | 0.8211674361 | 5.5109202463 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2038719337 | 0.2209408105 | Pass | Pass | 10.3580400230 | 61.3044769981 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.6822572837E-002 | 3.2559516924E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.5096573007E-002 | 0.1136124423 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.7204172383E-002 | 0.1085647607 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.2898144458E-002 | 8.8039228239E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.9994462542E-002 | 3.3888451912E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.4036317917E-002 | 0.1354298757 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1395569568 | 0.1486397182 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.8824143287E-002 | 0.1024881681 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4247.82 | 120.22 | 0.00 | 2380.92 | 1147.76 | 7896.72 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 183.92 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 429.15 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.67 | 83.67 | 235.80 | |
Exterior Lighting Total | 15013.15 | 235.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 454289.16 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 117524.93 | 94096.96 | 23427.98 | 0.80 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 112750.70 | 90274.44 | 22476.26 | 0.80 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 153495.09 | 122896.65 | 30598.44 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 115502.6 | 2.87 | 9.79 | N/A | N/A | 11.51 | |
PACU_VAV_MID COOLING COIL | 110810.5 | 2.87 | 9.79 | N/A | N/A | 11.51 | |
PACU_VAV_TOP COOLING COIL | 150853.8 | 2.87 | 9.79 | N/A | N/A | 11.51 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19063.22 | 18096.02 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 35140.16 | 33350.32 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 73179.20 | 69452.04 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 31628.77 | 30017.90 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 20886.10 | 19822.36 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31957.99 | 30330.35 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 20885.71 | 19821.99 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 23349.75 | 22160.53 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 15568.17 | 14775.27 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23685.22 | 22478.91 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15568.03 | 14775.14 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 23983.29 | 22761.80 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16027.19 | 15210.91 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24291.11 | 23053.94 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 16027.05 | 15210.78 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 19783.82 | 16529.61 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 23478.70 | 19073.40 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 19785.69 | 17009.96 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.10 | 15603.54 | 2197.78 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.81 | 14969.68 | 2197.78 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 9.27 | 20379.23 | 2197.78 | 1.00 | 1.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003974 | 1196.89 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 115502.62 | 2.87 | 9.79 | 11.51 | 6.6654 | 3.30 | 11.25 | 5.2697 | 3.48 | 11.86 | 3.5327 | 3.63 | 12.38 | 1.4961 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 110810.54 | 2.87 | 9.79 | 11.51 | 6.3947 | 3.30 | 11.25 | 5.0557 | 3.48 | 11.86 | 3.3892 | 3.63 | 12.38 | 1.4353 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 150853.82 | 2.87 | 9.79 | 11.51 | 8.7055 | 3.30 | 11.25 | 6.8826 | 3.48 | 11.86 | 4.6139 | 3.63 | 12.38 | 1.9539 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39831.60 | 45806.34 | 46.57 | 3.566 | 4.100 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_MID | 32627.64 | 37521.79 | 38.15 | 2.919 | 3.357 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_TOP | 37722.41 | 43380.78 | 44.11 | 3.404 | 3.914 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00882 | 33.90 | 0.00548 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11174.82 | 12851.04 | 61.98 | 1.008 | 1.159 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00864 | 33.90 | 0.00548 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11046.89 | 12703.92 | 96.78 | 0.997 | 1.146 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00859 | 26.60 | 0.00546 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14378.33 | 16535.08 | 79.75 | 1.297 | 1.492 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00861 | 33.53 | 0.00547 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 13218.01 | 15200.71 | 115.81 | 1.193 | 1.371 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00857 | 32.03 | 0.00547 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7847.66 | 9024.81 | 43.53 | 0.708 | 0.814 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00876 | 33.90 | 0.00548 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8902.87 | 10238.30 | 78.00 | 0.803 | 0.924 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00864 | 26.60 | 0.00546 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10716.55 | 12324.03 | 59.44 | 0.967 | 1.112 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00869 | 33.53 | 0.00547 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9921.20 | 11409.38 | 86.93 | 0.895 | 1.029 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00863 | 31.09 | 0.00547 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9114.89 | 10482.12 | 50.56 | 0.822 | 0.946 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00869 | 33.90 | 0.00548 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10964.86 | 12609.59 | 96.06 | 0.989 | 1.138 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00860 | 25.29 | 0.00546 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12461.92 | 14331.21 | 69.12 | 1.124 | 1.293 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00864 | 33.41 | 0.00547 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11932.97 | 13722.92 | 104.55 | 1.077 | 1.238 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00859 | 32.03 | 0.00547 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7294.69 | 9118.37 | 9.27 | 0.639 | 0.799 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_MID | 16362.49 | 20453.12 | 20.80 | 1.453 | 1.817 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_TOP | 33988.35 | 42485.43 | 43.20 | 3.037 | 3.797 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 14674.70 | 18343.38 | 88.47 | 1.315 | 1.644 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9690.07 | 12112.58 | 92.28 | 0.868 | 1.086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14827.26 | 18534.08 | 89.39 | 1.329 | 1.661 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9689.88 | 12112.36 | 92.28 | 0.868 | 1.086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10836.41 | 13545.51 | 65.33 | 0.970 | 1.213 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7224.52 | 9030.65 | 68.80 | 0.647 | 0.809 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10991.85 | 13739.82 | 66.27 | 0.984 | 1.230 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7224.46 | 9030.57 | 68.80 | 0.647 | 0.809 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11131.06 | 13913.82 | 67.11 | 0.997 | 1.246 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7437.94 | 9297.42 | 70.83 | 0.666 | 0.833 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11273.69 | 14092.11 | 67.97 | 1.010 | 1.262 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7437.87 | 9297.34 | 70.83 | 0.666 | 0.833 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -17.90 | 0.00096 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 7.10 | 7.10 | 4.86 | 4.86 | 7.0997 | 4.8603 | 7.0997 | 0.6846 | 0.3000 |
PACU_VAV_MID | 6.81 | 6.81 | 5.99 | 5.99 | 6.8113 | 5.9900 | 6.8113 | 0.8794 | 0.3000 |
PACU_VAV_TOP | 8.47 | 8.47 | 9.27 | 9.27 | 8.4725 | 9.2726 | 9.2726 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19063.216 | 19063.216 | 1.230131 | 0.00016677 | 422.573 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19063.22 | 19063.22 | 1.230131 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 9118.37 | 0.00 | 19153.54 | 19153.54 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 35140.163 | 35140.163 | 1.816722 | 0.00030742 | 821.824 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 35140.16 | 35140.16 | 1.816722 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 20453.12 | 0.00 | 35301.19 | 35301.19 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 73179.197 | 73179.197 | 3.796680 | 0.00064020 | 1709.764 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 73179.20 | 73179.20 | 3.796680 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 42485.43 | 0.00 | 73514.67 | 73514.67 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 31628.769 | 31628.769 | 1.643842 | 0.00027670 | 738.617 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31628.77 | 31494.13 | 1.643842 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00788172 | 41.3686 | 18343.38 | 0.00 | 31773.79 | 31773.79 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 20886.100 | 20886.100 | 1.085580 | 0.00018272 | 487.739 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20886.10 | 20886.10 | 1.085580 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00788053 | 41.3625 | 12112.58 | 0.00 | 20981.87 | 20981.87 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 31957.986 | 31957.986 | 1.660977 | 0.00027958 | 746.302 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31957.99 | 31822.41 | 1.660977 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00788291 | 41.3747 | 18534.08 | 0.00 | 32104.52 | 32104.52 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 20885.709 | 20885.709 | 1.085560 | 0.00018272 | 487.729 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20885.71 | 20885.71 | 1.085560 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00788053 | 41.3624 | 12112.36 | 0.00 | 20981.47 | 20981.47 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 23349.754 | 23349.754 | 1.212988 | 0.00020427 | 545.351 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23349.75 | 23239.45 | 1.212988 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00791554 | 41.5431 | 13545.51 | 0.00 | 23456.81 | 23456.81 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 15568.166 | 15568.166 | 0.808827 | 0.00013620 | 363.596 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15568.17 | 15568.17 | 0.808827 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00791549 | 41.5428 | 9030.65 | 0.00 | 15639.55 | 15639.55 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 23685.219 | 23685.219 | 1.230450 | 0.00020721 | 553.181 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23685.22 | 23574.00 | 1.230450 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00791672 | 41.5492 | 13739.82 | 0.00 | 23793.81 | 23793.81 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 15568.031 | 15568.031 | 0.808820 | 0.00013620 | 363.593 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15568.03 | 15568.03 | 0.808820 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00791549 | 41.5428 | 9030.57 | 0.00 | 15639.41 | 15639.41 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 23983.295 | 23983.295 | 1.245936 | 0.00020982 | 560.143 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23983.29 | 23870.70 | 1.245936 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787129 | 41.3143 | 13913.82 | 0.00 | 24093.26 | 24093.26 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 16027.191 | 16027.191 | 0.832703 | 0.00014021 | 374.313 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16027.19 | 16027.19 | 0.832703 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787147 | 41.3153 | 9297.42 | 0.00 | 16100.68 | 16100.68 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 24291.107 | 24291.107 | 1.261959 | 0.00021251 | 567.328 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24291.11 | 24291.11 | 1.261959 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787288 | 41.3225 | 14092.11 | 0.00 | 24402.48 | 24402.48 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 16027.052 | 16027.052 | 0.832696 | 0.00014021 | 374.310 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16027.05 | 16027.05 | 0.832696 | 12.89 | 9.77 | 0.00800000 | 32.11 | 16.46 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00787147 | 41.3153 | 9297.34 | 0.00 | 16100.54 | 16100.54 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 117524.933 | 94096.956 | 7.099681 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 114429.95 | 114429.95 | 7.099681 | 25.33 | 14.55 | 0.00832572 | 10.69 | 9.21 | 0.00832572 | 33.90 | 0.00547527 | 15.07 | 13.4668 | 24.00 | 0.00876936 | 38.3043 | 68419.77 | 0.00 | 121183.98 | 86321.14 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 19783.816 | 19783.816 | 2.129904 | 0.00017308 | 339.597 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19783.82 | 19783.82 | 2.129904 | 3.43 | 1.94 | 0.00475489 | 12.89 | 9.77 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 44.8893 | 16.57 | 0.00776460 | 53.7813 | 5406.27 | 0.00 | 20005.25 | 20005.25 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 112750.700 | 90274.441 | 6.811270 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 109781.45 | 109781.45 | 6.811270 | 25.39 | 14.55 | 0.00830469 | 10.69 | 9.19 | 0.00830469 | 33.90 | 0.00547527 | 15.07 | 14.0370 | 24.00 | 0.00876734 | 38.2953 | 65569.26 | 0.00 | 116261.11 | 82814.50 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 23478.701 | 23478.701 | 2.043381 | 0.00020540 | 397.225 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23478.70 | 23478.70 | 2.043381 | 1.19 | 0.37 | 0.00445015 | 12.89 | 9.77 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 46.7901 | 17.69 | 0.00777439 | 50.1612 | 7105.34 | 0.00 | 23081.02 | 23081.02 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 153495.091 | 122896.652 | 9.272638 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 149452.85 | 149452.85 | 9.272638 | 25.12 | 14.50 | 0.00834370 | 10.69 | 9.23 | 0.00834370 | 33.90 | 0.00547527 | 15.07 | 10.3110 | 24.00 | 0.00870905 | 38.0440 | 81562.04 | 0.00 | 158274.04 | 112740.94 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 19785.693 | 19785.693 | 2.781792 | 0.00017309 | 344.761 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19785.69 | 19785.69 | 2.781792 | 5.65 | 3.82 | 0.00538644 | 12.89 | 9.77 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 34.3699 | 16.68 | 0.00789879 | 54.3046 | 7561.44 | 0.00 | 20589.52 | 20589.52 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19063.216 | 19063.216 | 1.230131 | 0.00016677 | 422.573 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 4.1135 | 4.196274 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19063.22 | 19063.22 | 1.0000 | 1.20237647 | 1.230131 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.16675632 | 60.00 | 32.22 | 27.78 | 0.000 | 19063.22 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 9118.37 | 0.00 | 19153.54 | 19153.54 | 1.20237647 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.42 | 17.51 | 0.00800000 | 48989.6 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 35140.163 | 35140.163 | 1.816722 | 0.00030742 | 821.824 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 7.5826 | 7.735197 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 35140.16 | 35140.16 | 1.0000 | 1.77573194 | 1.816722 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.30739012 | 60.00 | 32.22 | 27.78 | 0.000 | 35140.16 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 20453.12 | 0.00 | 35301.19 | 35301.19 | 1.77573194 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.30 | 18.79 | 0.00800000 | 52939.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 73179.197 | 73179.197 | 3.796680 | 0.00064020 | 1709.764 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 15.7907 | 16.108506 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 73179.20 | 73179.20 | 1.0000 | 3.71101776 | 3.796680 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.64013823 | 60.00 | 32.22 | 27.78 | 0.000 | 73179.20 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 42485.43 | 0.00 | 73514.67 | 73514.67 | 3.71101776 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52869.7 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31628.769 | 31628.769 | 1.643842 | 0.00027670 | 738.617 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 6.8249 | 6.962255 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 31628.77 | 31494.13 | 1.0000 | 1.60675294 | 1.643842 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.27667404 | 60.00 | 32.22 | 27.78 | 0.000 | 31628.77 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00788172 | 21.00 | 0.00788172 | 41.3686 | 18343.38 | 0.00 | 31773.79 | 31773.79 | 1.60675294 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20886.100 | 20886.100 | 1.085580 | 0.00018272 | 487.739 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 4.5068 | 4.597534 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20886.10 | 20886.10 | 1.0000 | 1.06108667 | 1.085580 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.18270207 | 60.00 | 32.22 | 27.78 | 0.000 | 20886.10 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00788053 | 21.00 | 0.00788053 | 41.3625 | 12112.58 | 0.00 | 20981.87 | 20981.87 | 1.06108667 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52833.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31957.986 | 31957.986 | 1.660977 | 0.00027958 | 746.302 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 6.8959 | 7.034723 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 31957.99 | 31822.41 | 1.0000 | 1.62350131 | 1.660977 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.27955388 | 60.00 | 32.22 | 27.78 | 0.000 | 31957.99 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00788291 | 21.00 | 0.00788291 | 41.3747 | 18534.08 | 0.00 | 32104.52 | 32104.52 | 1.62350131 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20885.709 | 20885.709 | 1.085560 | 0.00018272 | 487.729 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 4.5067 | 4.597448 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20885.71 | 20885.71 | 1.0000 | 1.06106691 | 1.085560 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.18269866 | 60.00 | 32.22 | 27.78 | 0.000 | 20885.71 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.94 | 0.00788053 | 21.00 | 0.00788053 | 41.3624 | 12112.36 | 0.00 | 20981.47 | 20981.47 | 1.06106691 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52833.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23349.754 | 23349.754 | 1.212988 | 0.00020427 | 545.351 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 5.0384 | 5.139844 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23349.75 | 23239.45 | 1.0000 | 1.18561963 | 1.212988 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.20425300 | 60.00 | 32.22 | 27.78 | 0.000 | 23349.75 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00791554 | 21.00 | 0.00791554 | 41.5431 | 13545.51 | 0.00 | 23456.81 | 23456.81 | 1.18561963 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52844.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15568.166 | 15568.166 | 0.808827 | 0.00013620 | 363.596 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 3.3593 | 3.426929 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15568.17 | 15568.17 | 1.0000 | 0.79057823 | 0.808827 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.13618322 | 60.00 | 32.22 | 27.78 | 0.000 | 15568.17 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00791549 | 21.00 | 0.00791549 | 41.5428 | 9030.65 | 0.00 | 15639.55 | 15639.55 | 0.79057823 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.2 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23685.219 | 23685.219 | 1.230450 | 0.00020721 | 553.181 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 5.1108 | 5.213688 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23685.22 | 23574.00 | 1.0000 | 1.20268778 | 1.230450 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.20718749 | 60.00 | 32.22 | 27.78 | 0.000 | 23685.22 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00791672 | 21.00 | 0.00791672 | 41.5492 | 13739.82 | 0.00 | 23793.81 | 23793.81 | 1.20268778 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.7 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15568.031 | 15568.031 | 0.808820 | 0.00013620 | 363.593 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 3.3593 | 3.426899 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15568.03 | 15568.03 | 1.0000 | 0.79057142 | 0.808820 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.13618203 | 60.00 | 32.22 | 27.78 | 0.000 | 15568.03 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00791549 | 21.00 | 0.00791549 | 41.5428 | 9030.57 | 0.00 | 15639.41 | 15639.41 | 0.79057142 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23983.295 | 23983.295 | 1.245936 | 0.00020982 | 560.143 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 5.1751 | 5.279302 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23983.29 | 23870.70 | 1.0000 | 1.21782465 | 1.245936 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.20979492 | 60.00 | 32.22 | 27.78 | 0.000 | 23983.29 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787129 | 21.00 | 0.00787129 | 41.3143 | 13913.82 | 0.00 | 24093.26 | 24093.26 | 1.21782465 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16027.191 | 16027.191 | 0.832703 | 0.00014021 | 374.313 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 3.4584 | 3.527971 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16027.19 | 16027.19 | 1.0000 | 0.81391525 | 0.832703 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.14019855 | 60.00 | 32.22 | 27.78 | 0.000 | 16027.19 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787147 | 21.00 | 0.00787147 | 41.3153 | 9297.42 | 0.00 | 16100.68 | 16100.68 | 0.81391525 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52841.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24291.107 | 24291.107 | 1.261959 | 0.00021251 | 567.328 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 5.2416 | 5.347058 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24291.11 | 24291.11 | 1.0000 | 1.23348571 | 1.261959 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.21248752 | 60.00 | 32.22 | 27.78 | 0.000 | 24291.11 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787288 | 21.00 | 0.00787288 | 41.3225 | 14092.11 | 0.00 | 24402.48 | 24402.48 | 1.23348571 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52843.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16027.052 | 16027.052 | 0.832696 | 0.00014021 | 374.310 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 3.4583 | 3.527941 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16027.05 | 16027.05 | 1.0000 | 0.81390830 | 0.832696 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 32.11 | 16.46 | 0.00800000 | 52751.6 | 0.14019734 | 60.00 | 32.22 | 27.78 | 0.000 | 16027.05 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787147 | 21.00 | 0.00787147 | 41.3153 | 9297.34 | 0.00 | 16100.54 | 16100.54 | 0.81390830 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52841.6 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 117524.933 | 94096.956 | 7.099681 | -999.0 | -999.000 | -999.0000 | 1.13305 | 1.00000 | 1020.3171 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 7.099681 | 6.93949542 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 114429.95 | 114429.95 | 0.9737 | 6.93949542 | 7.099681 | 25.33 | 14.55 | 0.00832572 | 46669.1 | 10.69 | 9.21 | 0.00832572 | 31724.4 | -999.0 | -999.00 | -999.00 | -999.00 | 15603.545 | 98826.41 | 33.90 | 0.00547527 | 15.07 | 0.95610000 | 13.4668 | 24.00 | 0.00876936 | 24.00 | 0.00876936 | 38.3043 | 68419.77 | 0.00 | 121183.98 | 86321.14 | 6.66543781 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 19783.816 | 19783.816 | 2.129904 | 0.00017308 | 339.597 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 7.099681 | 6.93949542 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 4.2690 | 4.354895 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 22:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19783.82 | 19783.82 | 1.0000 | 2.08184863 | 2.129904 | 3.43 | 1.94 | 0.00475489 | 15370.5 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 0.17305980 | 60.00 | 32.22 | 27.78 | 0.000 | 19783.82 | -17.90 | 0.00095524 | -17.90 | 0.95610000 | 44.8893 | 20.81 | 0.00784982 | 16.57 | 0.00776460 | 53.7813 | 5406.27 | 0.00 | 20005.25 | 20005.25 | 2.08184863 | 2.80 | 2.80 | 0.00475489 | 14730.0 | 12.28 | 7.82 | 0.00475489 | 24339.4 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 112750.700 | 90274.441 | 6.811270 | -999.0 | -999.000 | -999.0000 | 1.12878 | 1.00000 | 1020.2780 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.811270 | 6.65759128 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 109781.45 | 109781.45 | 0.9737 | 6.65759128 | 6.811270 | 25.39 | 14.55 | 0.00830469 | 46674.8 | 10.69 | 9.19 | 0.00830469 | 31671.3 | -999.0 | -999.00 | -999.00 | -999.00 | 14969.680 | 94811.77 | 33.90 | 0.00547527 | 15.07 | 0.95610000 | 14.0370 | 24.00 | 0.00876734 | 24.00 | 0.00876734 | 38.2953 | 65569.26 | 0.00 | 116261.11 | 82814.50 | 6.39466675 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 23478.701 | 23478.701 | 2.043381 | 0.00020540 | 397.225 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.811270 | 6.65759128 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 5.0663 | 5.168228 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:50:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23478.70 | 23478.70 | 1.0000 | 1.99727738 | 2.043381 | 1.19 | 0.37 | 0.00445015 | 12335.6 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 0.20538096 | 60.00 | 32.22 | 27.78 | 0.000 | 23478.70 | -17.90 | 0.00095524 | -17.90 | 0.95610000 | 46.7901 | 17.98 | 0.00752341 | 17.69 | 0.00777439 | 50.1612 | 7105.34 | 0.00 | 23081.02 | 23081.02 | 1.99727738 | 2.80 | 2.57 | 0.00445015 | 13966.3 | 14.21 | 8.38 | 0.00445015 | 25522.5 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 153495.091 | 122896.652 | 9.272638 | -999.0 | -999.000 | -999.0000 | 1.14912 | 1.00000 | 1020.3505 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 9.272638 | 9.06342559 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 149452.85 | 149452.85 | 0.9737 | 9.06342559 | 9.272638 | 25.12 | 14.50 | 0.00834370 | 46495.8 | 10.69 | 9.23 | 0.00834370 | 31769.8 | -999.0 | -999.00 | -999.00 | -999.00 | 20379.229 | 129073.62 | 33.90 | 0.00547527 | 15.07 | 0.95610000 | 10.3110 | 24.00 | 0.00870905 | 24.00 | 0.00870905 | 38.0440 | 81562.04 | 0.00 | 158274.04 | 112740.94 | 8.70548879 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 19785.693 | 19785.693 | 2.781792 | 0.00017309 | 344.761 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 9.272638 | 9.06342559 | 4197.9300 | 999.8980 | 3.97391436 | 54.44 | 82.22 | 27.78 | 463431.91 | 4.2694 | 4.355308 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19785.69 | 19785.69 | 1.0000 | 2.71902768 | 2.781792 | 5.65 | 3.82 | 0.00538644 | 19202.4 | 12.89 | 9.77 | 0.00800000 | 33150.5 | 0.17307621 | 60.00 | 32.22 | 27.78 | 0.000 | 19785.69 | -17.90 | 0.00095524 | -17.90 | 0.95610000 | 34.3699 | 17.98 | 0.00770703 | 16.68 | 0.00789879 | 54.3046 | 7561.44 | 0.00 | 20589.52 | 20589.52 | 2.71902768 | 2.80 | 2.80 | 0.00538644 | 16312.8 | 10.26 | 7.60 | 0.00538644 | 23885.1 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | FixedDryBulb | 0.00 | 7.10 | - | |||
PACU_VAV_MID_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.81 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | FixedDryBulb | 0.00 | 9.27 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1621.67 | 2686.50 | 39.00 |
CORE_MID | 1341.50 | 3746.50 | 326.33 |
CORE_TOP | 2083.50 | 4149.17 | 1169.33 |
PERIMETER_TOP_ZN_3 | 3135.00 | 4633.83 | 2276.33 |
PERIMETER_TOP_ZN_2 | 3151.67 | 4099.00 | 1825.17 |
PERIMETER_TOP_ZN_1 | 2939.00 | 3685.67 | 1487.50 |
PERIMETER_TOP_ZN_4 | 3052.83 | 4419.00 | 1990.00 |
PERIMETER_BOT_ZN_3 | 2828.50 | 4633.83 | 2146.83 |
PERIMETER_BOT_ZN_2 | 2843.17 | 3923.33 | 1473.83 |
PERIMETER_BOT_ZN_1 | 2358.83 | 3684.17 | 1078.67 |
PERIMETER_BOT_ZN_4 | 2632.00 | 4270.33 | 1563.17 |
PERIMETER_MID_ZN_3 | 2716.33 | 4275.83 | 1692.33 |
PERIMETER_MID_ZN_2 | 2350.00 | 3412.17 | 1253.00 |
PERIMETER_MID_ZN_1 | 2693.83 | 3229.00 | 1016.67 |
PERIMETER_MID_ZN_4 | 2608.83 | 4224.17 | 1457.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4914.17 | 4972.83 | 2614.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.50 | 0.00 | 0.50 | 0.00 |
CORE_TOP | 4.67 | 0.00 | 3.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 92.17 | 0.17 | 26.17 | 0.17 |
PERIMETER_TOP_ZN_2 | 85.50 | 13.00 | 18.00 | 13.00 |
PERIMETER_TOP_ZN_1 | 70.00 | 13.83 | 17.00 | 13.83 |
PERIMETER_TOP_ZN_4 | 84.17 | 14.83 | 21.50 | 9.67 |
PERIMETER_BOT_ZN_3 | 11.33 | 0.00 | 4.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 8.00 | 5.33 | 2.67 | 5.33 |
PERIMETER_BOT_ZN_1 | 253.17 | 12.33 | 250.67 | 12.33 |
PERIMETER_BOT_ZN_4 | 7.17 | 9.17 | 2.50 | 5.50 |
PERIMETER_MID_ZN_3 | 20.17 | 0.00 | 7.67 | 0.00 |
PERIMETER_MID_ZN_2 | 16.67 | 12.83 | 3.83 | 12.83 |
PERIMETER_MID_ZN_1 | 12.33 | 19.17 | 4.50 | 19.17 |
PERIMETER_MID_ZN_4 | 15.00 | 12.83 | 3.67 | 8.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 359.33 | 84.17 | 273.67 | 74.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 1.106 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.755 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.768 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 1.399 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.744 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.735 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.926 | 0.088 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 1.091 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.498 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.378 | 0.857 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 1.521 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 1.169 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.775 | 0.078 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.650 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 1.874 | 0.073 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 17597574.53 | 0.00 | 17597574.53 | 0.00 | 17597574.53 | 13393058.27 | 5323.72 | 80.09 | 3356.19 | 66.23 |
CORE_MID | 12043678.71 | 0.00 | 12043678.71 | 0.00 | 12043678.71 | 13393058.27 | 6140.18 | 42.15 | 2577.66 | 95.09 |
CORE_TOP | 12249131.45 | 0.00 | 12249131.45 | 0.00 | 12249131.45 | 13393058.27 | 6130.21 | 29.24 | 2600.55 | 52.70 |
PERIMETER_TOP_ZN_3 | 4719502.25 | 0.00 | 4719502.25 | 579019.07 | 5298521.32 | 2823374.22 | 4186.05 | 15.43 | 4558.52 | 52.70 |
PERIMETER_TOP_ZN_2 | 3716039.34 | 0.00 | 3716039.34 | 386010.39 | 4102049.73 | 1787429.43 | 4120.53 | 1.75 | 4637.72 | 52.70 |
PERIMETER_TOP_ZN_1 | 5831614.28 | 0.00 | 5831614.28 | 579019.07 | 6410633.34 | 2823374.22 | 4135.09 | 4.97 | 4619.94 | 52.70 |
PERIMETER_TOP_ZN_4 | 4111604.08 | 0.00 | 4111604.08 | 386010.39 | 4497614.48 | 1787312.18 | 4099.54 | 2.91 | 4657.54 | 52.70 |
PERIMETER_BOT_ZN_3 | 3688678.06 | 0.00 | 3688678.06 | 307860.96 | 3996539.02 | 2823374.22 | 4793.55 | 25.38 | 3941.07 | 66.23 |
PERIMETER_BOT_ZN_2 | 3198058.09 | 0.00 | 3198058.09 | 205239.41 | 3403297.50 | 1787429.43 | 4034.85 | 12.32 | 4712.82 | 66.23 |
PERIMETER_BOT_ZN_1 | 4644636.92 | 0.00 | 4644636.92 | 3038318.74 | 7682955.65 | 2823374.22 | 4170.04 | 26.61 | 4563.35 | 66.23 |
PERIMETER_BOT_ZN_4 | 3252413.52 | 0.00 | 3252413.52 | 205239.41 | 3457652.93 | 1787312.18 | 4193.84 | 21.78 | 4544.38 | 66.23 |
PERIMETER_MID_ZN_3 | 3944963.35 | 0.00 | 3944963.35 | 481988.59 | 4426951.94 | 2823374.22 | 4100.16 | 19.73 | 4640.11 | 95.09 |
PERIMETER_MID_ZN_2 | 3576710.35 | 0.00 | 3576710.35 | 321323.80 | 3898034.14 | 1601953.02 | 3982.74 | 2.47 | 4774.80 | 1004.09 |
PERIMETER_MID_ZN_1 | 5546097.33 | 0.00 | 5546097.33 | 481988.59 | 6028085.92 | 2823374.22 | 4042.09 | 5.36 | 4712.55 | 95.09 |
PERIMETER_MID_ZN_4 | 4005035.12 | 0.00 | 4005035.12 | 321323.80 | 4326358.92 | 1787312.18 | 3982.59 | 9.41 | 4768.01 | 95.09 |
Total Facility | 92125737.38 | 0.00 | 92125737.38 | 7293342.22 | 99419079.60 | 67658168.57 | 6303.08 | 277.27 | 4844.12 | 1062.46 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.8182 | 0.0000 | 0.8182 | 0.0000 | 0.8182 | 0.4247 | 2518.96 | 80.09 | 3343.95 |
CORE_MID | 0.5598 | 0.0000 | 0.5598 | 0.0000 | 0.5598 | 0.4247 | 3331.79 | 42.15 | 2569.05 |
CORE_TOP | 0.5702 | 0.0000 | 0.5702 | 0.0000 | 0.5702 | 0.4247 | 3322.93 | 29.24 | 2590.83 |
PERIMETER_TOP_ZN_3 | 0.2196 | 0.0000 | 0.2196 | 0.0131 | 0.2327 | 0.0895 | 1378.94 | 15.43 | 4548.63 |
PERIMETER_TOP_ZN_2 | 0.1730 | 0.0000 | 0.1730 | 0.0087 | 0.1817 | 0.0567 | 1313.42 | 1.75 | 4627.83 |
PERIMETER_TOP_ZN_1 | 0.2716 | 0.0000 | 0.2716 | 0.0131 | 0.2847 | 0.0895 | 1327.98 | 4.97 | 4610.05 |
PERIMETER_TOP_ZN_4 | 0.1913 | 0.0000 | 0.1913 | 0.0087 | 0.2001 | 0.0567 | 1292.68 | 2.91 | 4647.40 |
PERIMETER_BOT_ZN_3 | 0.1711 | 0.0000 | 0.1711 | 0.0070 | 0.1781 | 0.0895 | 1995.33 | 24.94 | 3922.72 |
PERIMETER_BOT_ZN_2 | 0.1485 | 0.0000 | 0.1485 | 0.0046 | 0.1532 | 0.0567 | 1244.65 | 10.42 | 4687.93 |
PERIMETER_BOT_ZN_1 | 0.2158 | 0.0000 | 0.2158 | 0.1346 | 0.3504 | 0.0895 | 1371.69 | 26.32 | 4544.99 |
PERIMETER_BOT_ZN_4 | 0.1509 | 0.0000 | 0.1509 | 0.0046 | 0.1556 | 0.0567 | 1408.52 | 20.81 | 4513.67 |
PERIMETER_MID_ZN_3 | 0.1832 | 0.0000 | 0.1832 | 0.0109 | 0.1941 | 0.0895 | 1292.98 | 19.71 | 4630.32 |
PERIMETER_MID_ZN_2 | 0.1760 | 0.0000 | 0.1760 | 0.0078 | 0.1838 | 0.0567 | 1188.66 | 2.23 | 3843.12 |
PERIMETER_MID_ZN_1 | 0.2580 | 0.0000 | 0.2580 | 0.0109 | 0.2689 | 0.0895 | 1234.86 | 5.24 | 4702.90 |
PERIMETER_MID_ZN_4 | 0.1860 | 0.0000 | 0.1860 | 0.0073 | 0.1933 | 0.0567 | 1193.36 | 8.55 | 4741.09 |
Total Facility | 4.2935 | 0.0000 | 4.2935 | 0.2312 | 4.5247 | 2.1513 | 3489.70 | 272.57 | 4801.02 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 30936643.58 | 0.00 | 30936643.58 | 22614548.33 | 4399.23 | 270.71 | 4090.07 | 66.23 |
PACU_VAV_MID | 27817432.09 | 0.00 | 27817432.09 | 22429071.92 | 4086.40 | 105.10 | 4568.49 | 95.09 |
PACU_VAV_TOP | 29261406.15 | 0.00 | 29261406.15 | 22614548.33 | 4171.48 | 351.68 | 4236.84 | 52.70 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4375 | 0.0000 | 1.4375 | 0.7171 | 1594.61 | 270.71 | 4077.68 |
PACU_VAV_MID | 1.2928 | 0.0000 | 1.2928 | 0.7084 | 1278.68 | 105.10 | 4559.21 |
PACU_VAV_TOP | 1.3622 | 0.0000 | 1.3622 | 0.7171 | 1364.37 | 351.68 | 4226.95 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 34.36 | 3587.68 | 0.00 | 0.00 | 0.00 | 1191.30 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 43.33 | 3263.39 | 0.00 | 0.00 | 0.00 | 1567.42 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 37.45 | 3212.59 | 0.00 | 0.00 | 0.00 | 1562.77 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.8563 | 2.1728 | 0.0000 | 0.0000 | 0.0000 | 0.7251 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.8521 | 2.0389 | 0.0000 | 0.0000 | 0.0000 | 0.7581 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.8526 | 2.1778 | 0.0000 | 0.0000 | 0.0000 | 0.7566 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2032.92 | 15934.24 | 12-MAR-17:20 | 224294.16 | 26-JUN-15:10 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 443.62 | 383.73 | 01-JAN-00:10 | 129198.86 | 26-JUN-15:00 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 05-JAN-12:20 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 05-JAN-12:20 |
ElectricityPurchased:Facility | 2032.92 | 15934.24 | 12-MAR-17:20 | 224294.16 | 26-JUN-15:10 |
ElectricityPurchased:Plant | 2032.92 | 15934.24 | 12-MAR-17:20 | 224294.16 | 26-JUN-15:10 |
Cogeneration:ElectricityPurchased | 2032.92 | 15934.24 | 12-MAR-17:20 | 224294.16 | 26-JUN-15:10 |
General:Cogeneration:ElectricityPurchased | 2032.92 | 15934.24 | 12-MAR-17:20 | 224294.16 | 26-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2032.92 | 15934.24 | 12-MAR-17:20 | 224294.16 | 26-JUN-15:10 |
ElectricityNet:Plant | 2032.92 | 15934.24 | 12-MAR-17:20 | 224294.16 | 26-JUN-15:10 |
Cogeneration:ElectricityNet | 2032.92 | 15934.24 | 12-MAR-17:20 | 224294.16 | 26-JUN-15:10 |
General:Cogeneration:ElectricityNet | 2032.92 | 15934.24 | 12-MAR-17:20 | 224294.16 | 26-JUN-15:10 |
Fans:Electricity | 215.07 | 0.00 | 01-JAN-00:10 | 38571.16 | 16-AUG-15:20 |
General:Fans:Electricity | 215.07 | 0.00 | 01-JAN-00:10 | 38571.16 | 16-AUG-15:20 |
ExteriorLights:Electricity | 235.80 | 0.00 | 01-JAN-07:30 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 235.80 | 0.00 | 01-JAN-07:30 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 201.05 | 0.00 | 01-JAN-00:10 | 90148.06 | 26-JUN-15:00 |
General:Cooling:Electricity | 201.05 | 0.00 | 01-JAN-00:10 | 90148.06 | 26-JUN-15:00 |
Electricity:Plant | 57.97 | 0.00 | 01-JAN-00:10 | 7461.96 | 20-DEC-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 55.71 | 0.00 | 01-JAN-00:10 | 6807.63 | 13-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 55.71 | 0.00 | 01-JAN-00:10 | 6807.63 | 13-FEB-13:00 |
Pumps:Electricity | 2.26 | 0.00 | 01-JAN-00:10 | 1141.29 | 23-DEC-07:10 |
General:Pumps:Electricity | 2.26 | 0.00 | 01-JAN-00:10 | 1141.29 | 23-DEC-07:10 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 426.10 | 0.00 | 01-JAN-00:10 | 284245.59 | 23-DEC-07:20 |
NaturalGas:Plant | 426.10 | 0.00 | 01-JAN-00:10 | 284245.59 | 23-DEC-07:20 |
Heating:NaturalGas | 426.10 | 0.00 | 01-JAN-00:10 | 284245.59 | 23-DEC-07:20 |
Boiler:Heating:NaturalGas | 426.10 | 0.00 | 01-JAN-00:10 | 284245.59 | 23-DEC-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2791.29 | 0.00 | 01-JAN-00:10 | 567511.50 | 23-DEC-07:10 |
EnergyTransfer:Building | 1398.02 | 0.00 | 01-JAN-00:10 | 193427.52 | 16-AUG-14:40 |
EnergyTransfer:Zone:CORE_BOTTOM | 255.87 | 0.00 | 01-JAN-00:10 | 26595.04 | 05-SEP-15:50 |
Heating:EnergyTransfer | 159.77 | 0.00 | 01-JAN-00:10 | 162609.67 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 1852.85 | 26-DEC-07:10 |
General:Heating:EnergyTransfer | 159.77 | 0.00 | 01-JAN-00:10 | 162609.67 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 1852.85 | 26-DEC-07:10 |
Cooling:EnergyTransfer | 1238.25 | 0.00 | 01-JAN-00:10 | 193427.52 | 16-AUG-14:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 255.87 | 0.00 | 01-JAN-00:10 | 26595.04 | 05-SEP-15:50 |
General:Cooling:EnergyTransfer | 1238.25 | 0.00 | 01-JAN-00:10 | 193427.52 | 16-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 255.87 | 0.00 | 01-JAN-00:10 | 26595.04 | 05-SEP-15:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 98.36 | 0.00 | 01-JAN-00:10 | 22824.57 | 22-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 39.90 | 0.00 | 01-JAN-00:10 | 22824.57 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 39.90 | 0.00 | 01-JAN-00:10 | 22824.57 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.46 | 0.00 | 01-JAN-00:10 | 19281.23 | 26-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.46 | 0.00 | 01-JAN-00:10 | 19281.23 | 26-JUN-13:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 32.14 | 0.00 | 01-JAN-00:10 | 9340.74 | 26-DEC-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.14 | 0.00 | 01-JAN-00:10 | 9340.74 | 26-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.14 | 0.00 | 01-JAN-00:10 | 9340.74 | 26-DEC-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.00 | 0.00 | 01-JAN-00:10 | 5692.31 | 17-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.00 | 0.00 | 01-JAN-00:10 | 5692.31 | 17-JUL-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.53 | 0.00 | 01-JAN-00:10 | 5784.50 | 17-JUL-14:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.01 | 0.00 | 01-JAN-00:10 | 5099.18 | 06-FEB-08:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.01 | 0.00 | 01-JAN-00:10 | 5099.18 | 06-FEB-08:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 29.52 | 0.00 | 01-JAN-00:10 | 5784.50 | 17-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 29.52 | 0.00 | 01-JAN-00:10 | 5784.50 | 17-JUL-14:10 |
EnergyTransfer:Zone:CORE_MID | 167.81 | 0.00 | 01-JAN-00:10 | 20600.27 | 17-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.55 | 0.00 | 01-JAN-00:10 | 15355.17 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.55 | 0.00 | 01-JAN-00:10 | 15355.17 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 167.26 | 0.00 | 01-JAN-00:10 | 20600.27 | 17-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 167.26 | 0.00 | 01-JAN-00:10 | 20600.27 | 17-JUL-14:00 |
EnergyTransfer:Zone:CORE_TOP | 168.89 | 0.00 | 01-JAN-00:10 | 27250.75 | 26-DEC-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 7.31 | 0.00 | 01-JAN-00:10 | 27250.75 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 7.31 | 0.00 | 01-JAN-00:10 | 27250.75 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 161.58 | 0.00 | 01-JAN-00:10 | 24423.35 | 26-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 161.58 | 0.00 | 01-JAN-00:10 | 24423.35 | 26-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 59.34 | 0.00 | 01-JAN-00:10 | 11535.07 | 23-DEC-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 16.69 | 0.00 | 01-JAN-00:10 | 11535.07 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 16.69 | 0.00 | 01-JAN-00:10 | 11535.07 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.65 | 0.00 | 01-JAN-00:10 | 8971.72 | 17-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.65 | 0.00 | 01-JAN-00:10 | 8971.72 | 17-JUL-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.99 | 0.00 | 01-JAN-00:10 | 9909.59 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.25 | 0.00 | 01-JAN-00:10 | 7816.70 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.25 | 0.00 | 01-JAN-00:10 | 7816.70 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.75 | 0.00 | 01-JAN-00:10 | 9909.59 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.75 | 0.00 | 01-JAN-00:10 | 9909.59 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.10 | 0.00 | 01-JAN-00:10 | 15809.48 | 28-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 11.69 | 0.00 | 01-JAN-00:10 | 11606.74 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 11.69 | 0.00 | 01-JAN-00:10 | 11606.74 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 69.41 | 0.00 | 01-JAN-00:10 | 15809.48 | 28-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 69.41 | 0.00 | 01-JAN-00:10 | 15809.48 | 28-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.66 | 0.00 | 01-JAN-00:10 | 11468.73 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 10.02 | 0.00 | 01-JAN-00:10 | 8230.60 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 10.02 | 0.00 | 01-JAN-00:10 | 8230.60 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.64 | 0.00 | 01-JAN-00:10 | 11468.73 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.64 | 0.00 | 01-JAN-00:10 | 11468.73 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 41.65 | 0.00 | 01-JAN-00:10 | 7986.09 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 8.38 | 0.00 | 01-JAN-00:10 | 7986.09 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 8.38 | 0.00 | 01-JAN-00:10 | 7986.09 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 33.26 | 0.00 | 01-JAN-00:10 | 6671.48 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 33.26 | 0.00 | 01-JAN-00:10 | 6671.48 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 39.64 | 0.00 | 01-JAN-00:10 | 7826.68 | 17-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.91 | 0.00 | 01-JAN-00:10 | 5563.20 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.91 | 0.00 | 01-JAN-00:10 | 5563.20 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 35.72 | 0.00 | 01-JAN-00:10 | 7826.68 | 17-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 35.72 | 0.00 | 01-JAN-00:10 | 7826.68 | 17-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 69.26 | 0.00 | 01-JAN-00:10 | 14515.79 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 14.99 | 0.00 | 01-JAN-00:10 | 13352.93 | 21-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 14.99 | 0.00 | 01-JAN-00:10 | 13352.93 | 21-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 54.27 | 0.00 | 01-JAN-00:10 | 14515.79 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 54.27 | 0.00 | 01-JAN-00:10 | 14515.79 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 37.91 | 0.00 | 01-JAN-00:10 | 8925.49 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 4.13 | 0.00 | 01-JAN-00:10 | 5764.55 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 4.13 | 0.00 | 01-JAN-00:10 | 5764.55 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 33.79 | 0.00 | 01-JAN-00:10 | 8925.49 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 33.79 | 0.00 | 01-JAN-00:10 | 8925.49 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 47.90 | 0.00 | 01-JAN-00:10 | 8500.36 | 22-DEC-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.74 | 0.00 | 01-JAN-00:10 | 8500.36 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 6.74 | 0.00 | 01-JAN-00:10 | 8500.36 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 41.17 | 0.00 | 01-JAN-00:10 | 8168.26 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 41.17 | 0.00 | 01-JAN-00:10 | 8168.26 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.93 | 0.00 | 01-JAN-00:10 | 9884.53 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.77 | 0.00 | 01-JAN-00:10 | 6307.04 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.77 | 0.00 | 01-JAN-00:10 | 6307.04 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.15 | 0.00 | 01-JAN-00:10 | 9884.53 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.15 | 0.00 | 01-JAN-00:10 | 9884.53 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 74.41 | 0.00 | 01-JAN-00:10 | 14761.83 | 28-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 4.28 | 0.00 | 01-JAN-00:10 | 8661.92 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 4.28 | 0.00 | 01-JAN-00:10 | 8661.92 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 70.14 | 0.00 | 01-JAN-00:10 | 14761.83 | 28-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 70.14 | 0.00 | 01-JAN-00:10 | 14761.83 | 28-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 45.64 | 0.00 | 01-JAN-00:10 | 10844.39 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 4.02 | 0.00 | 01-JAN-00:10 | 6457.24 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 4.02 | 0.00 | 01-JAN-00:10 | 6457.24 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 41.62 | 0.00 | 01-JAN-00:10 | 10844.39 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 41.62 | 0.00 | 01-JAN-00:10 | 10844.39 | 16-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 327.66 | 0.00 | 01-JAN-00:10 | 213317.94 | 23-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
EnergyTransfer:HVAC | 1067.85 | 0.00 | 01-JAN-00:10 | 260805.45 | 26-JUN-15:00 |
HeatingCoils:EnergyTransfer | 274.74 | 0.00 | 01-JAN-00:10 | 212082.46 | 23-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 274.74 | 0.00 | 01-JAN-00:10 | 212082.46 | 23-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 274.74 | 0.00 | 01-JAN-00:10 | 212082.46 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 793.11 | 0.00 | 01-JAN-00:10 | 260805.45 | 26-JUN-15:00 |
EnergyTransfer:Plant | 325.42 | 0.00 | 01-JAN-00:10 | 209848.40 | 23-DEC-07:20 |
WaterSystems:EnergyTransfer | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 52.92 | 0.00 | 01-JAN-00:10 | 6664.15 | 13-FEB-12:10 |
Boilers:EnergyTransfer | 272.50 | 0.00 | 01-JAN-00:10 | 208612.92 | 23-DEC-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.001 | -255.866 | 0.000 | 0.000 | 32.976 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -148.897 |
CORE_MID | 0.000 | 0.000 | 0.552 | -167.259 | 0.000 | 0.000 | 34.104 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -94.609 |
CORE_TOP | 0.000 | 0.000 | 7.311 | -161.576 | 0.000 | 0.000 | 35.224 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -108.171 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 16.689 | -42.651 | 0.000 | 0.000 | 7.733 | 23.566 | 24.333 | 18.698 | 0.000 | 0.195 | 6.853 | 0.000 | -48.504 | 0.000 | -6.911 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 9.246 | -40.747 | 0.000 | 0.000 | 4.770 | 14.919 | 15.404 | 43.269 | 0.000 | 0.118 | 0.000 | 0.000 | -30.852 | 0.000 | -4.715 | -11.411 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 11.693 | -69.406 | 0.000 | 0.000 | 7.400 | 23.566 | 24.332 | 89.909 | 0.000 | 0.178 | 0.004 | 0.000 | -46.245 | 0.000 | -7.268 | -34.159 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 10.017 | -40.640 | 0.000 | 0.000 | 4.871 | 14.918 | 15.403 | 40.108 | 0.000 | 0.123 | 0.001 | 0.000 | -31.756 | 0.000 | -4.716 | -8.328 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 8.383 | -33.262 | 0.000 | 0.000 | 7.697 | 23.566 | 24.333 | 19.229 | 0.000 | 0.106 | 3.999 | 0.000 | -50.191 | 0.000 | -3.858 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 3.915 | -35.721 | 0.000 | 0.000 | 4.740 | 14.919 | 15.404 | 43.606 | 0.000 | 0.063 | 0.005 | 0.000 | -32.543 | 0.000 | -2.682 | -11.700 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 14.986 | -54.272 | 0.000 | 0.000 | 7.469 | 23.566 | 24.332 | 90.943 | 0.000 | 2.418 | 0.002 | 0.000 | -49.545 | 0.000 | -32.896 | -27.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 4.129 | -33.785 | 0.000 | 0.000 | 4.821 | 14.918 | 15.403 | 40.562 | 0.000 | 0.064 | 0.000 | 0.000 | -33.576 | 0.000 | -2.680 | -9.855 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 6.736 | -41.165 | 0.000 | 0.000 | 7.601 | 23.566 | 24.333 | 18.324 | 0.000 | 0.156 | 18.311 | 0.000 | -51.722 | 0.000 | -6.139 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 3.773 | -40.153 | 0.000 | 0.000 | 3.481 | 14.919 | 15.404 | 42.854 | 0.000 | 0.100 | 0.002 | 0.000 | -32.758 | 0.000 | -4.175 | -3.446 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 4.277 | -70.138 | 0.000 | 0.000 | 7.261 | 23.566 | 24.332 | 89.386 | 0.000 | 0.144 | 0.000 | 0.000 | -49.395 | 0.000 | -6.459 | -22.972 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 4.017 | -41.618 | 0.000 | 0.000 | 4.817 | 14.918 | 15.403 | 39.969 | 0.000 | 0.101 | 0.366 | 0.000 | -33.808 | 0.000 | -4.167 | -0.000 |
TOPFLOOR_PLENUM | 39.903 | -58.461 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.157 | 28.727 | 0.000 | 0.000 | 0.000 | -10.325 | -0.000 |
MIDFLOOR_PLENUM | 10.135 | -22.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.217 | 22.550 | 0.000 | 0.000 | 0.000 | -10.902 | -0.000 |
FIRSTFLOOR_PLENUM | 4.006 | -29.524 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.164 | 34.248 | 0.000 | 0.000 | 0.000 | -8.895 | -0.000 |
Total Facility | 54.044 | -109.985 | 105.724 | -1128.260 | 0.000 | 0.000 | 174.965 | 566.263 | 729.266 | 576.856 | 0.000 | 4.303 | 115.068 | 0.000 | -490.894 | 0.000 | -116.788 | -480.551 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | -48057.50 | 0.00 | 0.00 | 314.43 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 38924.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-JUL-05:12 | 0.00 | 0.00 | 0.00 | -31846.76 | 0.00 | 0.00 | 336.64 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 27399.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | -24421.13 | 0.00 | 0.00 | 3497.16 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 4355.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 17-JUL-13:40 | 0.00 | 0.00 | 0.00 | -8971.94 | 0.00 | 0.00 | 757.17 | 2057.62 | 1435.25 | 5476.22 | 0.00 | 112.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -867.06 |
PERIMETER_TOP_ZN_2 | 09-JUL-09:12 | 0.00 | 0.00 | 0.00 | -16291.60 | 0.00 | 0.00 | 14.81 | 72.37 | 302.86 | 9926.79 | 0.00 | 0.00 | 5996.55 | 0.00 | -0.00 | 0.00 | -21.77 | 0.00 |
PERIMETER_TOP_ZN_1 | 17-SEP-13:22 | 0.00 | 0.00 | 0.00 | -23328.96 | 0.00 | 0.00 | 24.12 | 114.31 | 478.41 | 12513.10 | 0.00 | 0.00 | 10228.53 | 0.00 | -0.00 | 0.00 | -29.51 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:41 | 0.00 | 0.00 | 0.00 | -21059.31 | 0.00 | 0.00 | 12.20 | 72.36 | 302.86 | 11851.22 | 0.00 | 0.00 | 8856.36 | 0.00 | -0.00 | 0.00 | -35.68 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-13:30 | 0.00 | 0.00 | 0.00 | -6671.59 | 0.00 | 0.00 | 757.17 | 2057.62 | 1435.25 | 5843.79 | 0.00 | 51.64 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3473.88 |
PERIMETER_BOT_ZN_2 | 20-AUG-09:41 | 0.00 | 0.00 | 0.00 | -13292.46 | 0.00 | 0.00 | 15.66 | 72.37 | 302.86 | 8762.82 | 0.00 | 4.16 | 4134.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-13:52 | 0.00 | 0.00 | 0.00 | -18384.28 | 0.00 | 0.00 | 22.61 | 114.31 | 478.41 | 14648.50 | 0.00 | 0.00 | 3171.33 | 0.00 | -0.00 | 0.00 | -50.89 | 0.00 |
PERIMETER_BOT_ZN_4 | 10-SEP-17:11 | 0.00 | 0.00 | 0.00 | -15342.24 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 8475.50 | 0.00 | 18.07 | 6531.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-13:52 | 0.00 | 0.00 | 0.00 | -12143.32 | 0.00 | 0.00 | 28.45 | 114.31 | 478.42 | 5845.49 | 0.00 | 335.35 | 5341.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 20-AUG-09:01 | 0.00 | 0.00 | 0.00 | -17101.57 | 0.00 | 0.00 | 13.52 | 72.37 | 302.86 | 10592.96 | 0.00 | 0.00 | 6147.75 | 0.00 | -0.00 | 0.00 | -27.88 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-12:41 | 0.00 | 0.00 | 0.00 | -19886.06 | 0.00 | 0.00 | 21.88 | 114.31 | 478.41 | 13795.95 | 0.00 | 76.09 | 5399.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 10-SEP-16:41 | 0.00 | 0.00 | 0.00 | -18832.50 | 0.00 | 0.00 | 12.53 | 72.36 | 302.86 | 10614.83 | 0.00 | 25.84 | 7804.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:05 | 0.00 | -19293.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 | 19234.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-14:20 | 0.00 | -5692.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.43 | 5519.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-14:05 | 0.00 | -5791.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.15 | 5653.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-AUG-14:40 | 0.00 | -29016.87 | 0.00 | -164435.16 | 0.00 | 0.00 | 17713.73 | 49443.18 | 41937.01 | 79078.86 | 0.00 | 1590.34 | 3688.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 26-DEC-07:03 | 0.00 | 0.00 | 5005.33 | 0.00 | 0.00 | 0.00 | 908.43 | 3253.54 | 10475.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19642.39 |
CORE_MID | 26-DEC-06:11 | 0.00 | 0.00 | 17660.51 | 0.00 | 0.00 | 0.00 | 506.65 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22277.58 |
CORE_TOP | 06-FEB-05:01 | 0.00 | 0.00 | 31715.93 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35242.49 |
PERIMETER_TOP_ZN_3 | 24-DEC-00:32 | 0.00 | 0.00 | 15018.36 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5456.08 | 0.00 | -1472.88 | -8589.82 |
PERIMETER_TOP_ZN_2 | 24-DEC-00:32 | 0.00 | 0.00 | 10290.15 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3787.26 | 0.00 | -979.93 | -5839.75 |
PERIMETER_TOP_ZN_1 | 24-DEC-00:32 | 0.00 | 0.00 | 14969.77 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5747.07 | 0.00 | -1483.34 | -8239.77 |
PERIMETER_TOP_ZN_4 | 24-DEC-00:32 | 0.00 | 0.00 | 11293.96 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3796.48 | 0.00 | -985.74 | -6828.53 |
PERIMETER_BOT_ZN_3 | 24-DEC-07:01 | 0.00 | 0.00 | 10223.85 | 0.00 | 0.00 | 0.00 | 58.69 | 114.31 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5309.03 | 0.00 | -910.55 | -4655.69 |
PERIMETER_BOT_ZN_2 | 24-DEC-07:01 | 0.00 | 0.00 | 7333.63 | 0.00 | 0.00 | 0.00 | 37.23 | 72.37 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3677.57 | 0.00 | -607.61 | -3460.90 |
PERIMETER_BOT_ZN_1 | 21-DEC-08:00 | 0.00 | 0.00 | 13352.67 | 0.00 | 0.00 | 0.00 | 253.10 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 15479.55 | 0.00 | -6932.59 | 0.00 | -23476.48 | 0.00 |
PERIMETER_BOT_ZN_4 | 24-DEC-07:01 | 0.00 | 0.00 | 7722.26 | 0.00 | 0.00 | 0.00 | 37.15 | 72.36 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3551.37 | 0.00 | -609.42 | -3973.83 |
PERIMETER_MID_ZN_3 | 24-DEC-07:01 | 0.00 | 0.00 | 10810.97 | 0.00 | 0.00 | 0.00 | 59.63 | 114.31 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5266.64 | 0.00 | -1408.69 | -4787.99 |
PERIMETER_MID_ZN_2 | 24-DEC-07:01 | 0.00 | 0.00 | 8595.53 | 0.00 | 0.00 | 0.00 | 37.92 | 72.37 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3648.35 | 0.00 | -939.77 | -4420.56 |
PERIMETER_MID_ZN_1 | 24-DEC-07:01 | 0.00 | 0.00 | 11077.43 | 0.00 | 0.00 | 0.00 | 59.61 | 114.31 | 478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5514.93 | 0.00 | -1410.66 | -4804.17 |
PERIMETER_MID_ZN_4 | 24-DEC-07:01 | 0.00 | 0.00 | 8942.06 | 0.00 | 0.00 | 0.00 | 37.83 | 72.36 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3507.13 | 0.00 | -942.83 | -4905.16 |
TOPFLOOR_PLENUM | 22-DEC-06:12 | 25692.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -364.40 | -25328.08 |
MIDFLOOR_PLENUM | 26-DEC-07:15 | 10193.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -121.43 | -10071.86 |
FIRSTFLOOR_PLENUM | 16-OCT-05:01 | 6896.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -108.83 | -6787.33 |
Total Facility | 26-DEC-06:11 | 3718.96 | 6054.48 | 162720.03 | -6054.48 | 0.00 | 0.00 | 2592.54 | 5493.69 | 20036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15070.56 | 0.00 | -2395.24 | -177095.76 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 8.4970 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 7.0997 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 8.2713 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.8113 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 9.7365 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.4725 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.2485 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.5491 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.1356 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.4814 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.8682 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9209 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.1004 | 4.1004 | 1.2301 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3566 | 3.3566 | 1.0070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9141 | 3.9141 | 1.1742 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6438 | 1.6438 | 0.4932 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1462 | 1.1462 | 0.3438 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6610 | 1.6610 | 0.4983 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3714 | 1.3714 | 0.4114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2130 | 1.2130 | 0.3639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9237 | 0.9237 | 0.2771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2304 | 1.2304 | 0.3691 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0294 | 1.0294 | 0.3088 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2459 | 1.2459 | 0.3738 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1377 | 1.1377 | 0.3413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2930 | 1.2930 | 0.3879 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2381 | 1.2381 | 0.3714 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 8.4970 | 7.0997 | 8.4970 | 2.5491 | 0.0000 | 1.0000 |
PACU_VAV_MID | 8.2713 | 6.8113 | 8.2713 | 2.4814 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 9.7365 | 8.4725 | 9.7365 | 2.9209 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0502 | 2.0502 | 1.2301 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6783 | 1.6783 | 1.0070 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9570 | 1.9570 | 1.1742 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8219 | 0.8219 | 0.4932 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5731 | 0.5731 | 0.3438 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8305 | 0.8305 | 0.4983 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6857 | 0.6857 | 0.4114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6065 | 0.6065 | 0.3639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4619 | 0.4619 | 0.2771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6152 | 0.6152 | 0.3691 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5147 | 0.5147 | 0.3088 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6230 | 0.6230 | 0.3738 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5688 | 0.5688 | 0.3413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6465 | 0.6465 | 0.3879 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6191 | 0.6191 | 0.3714 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.2485 | 2.5491 | 2.5491 | 2.5491 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.1356 | 2.4814 | 2.4814 | 2.4814 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.8682 | 2.9209 | 2.9209 | 2.9209 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 273.67 |
Number of hours cooling loads not met | 74.33 |
Number of hours not met | 348.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 426.10 | 284245.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 201.05 | 90148.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 235.80 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 215.07 | 38571.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 2.26 | 1141.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 55.71 | 6807.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 2032.92 |
Natural Gas | 0.00 | 426.10 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2459.02 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 40.35 |
Fans (All) | 43.17 |
Service Water Heating | 11.18 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 408.04 |
Subtotal | 408.04 |
Natural Gas [MJ/m2] | |
Space Heating | 85.52 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 85.52 |
Subtotal | 85.52 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 23.03 |
Space Heating | 17.33 |
Space Cooling | 8.18 |
Fans (All) | 8.75 |
Service Water Heating | 2.27 |
Receptacle Equipment | 29.66 |
Miscellaneous | 10.80 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8715.50 | 44.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.83 | 7.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8688.00 | 72.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8688.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 72.00 | 0.00 | 0.00 | 0.00 |
Average | 8749.31 | 10.69 | 0.00 | 0.00 | 0.00 |
Sum | 157487.50 | 192.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 4.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.11 | 0.22 | 0.00 | 0.00 | 0.00 |
Sum | 614576.00 | 4.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8668.50 | 91.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8668.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 91.50 | 0.00 | 0.00 | 0.00 |
Average | 8751.37 | 8.63 | 0.00 | 0.00 | 0.00 |
Sum | 157524.67 | 155.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128274.17 | 29.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128300.33 | 3.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 29.83 | 0.00 | 0.00 | 0.00 |
Average | 34141.47 | 1.86 | 0.00 | 0.00 | 0.00 |
Sum | 614546.50 | 33.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151967E+11 | 25261.10 | 26-JAN-06:01 | -2.0 | -2.5 | 0.193296E+10 | 2606.66 | 27-JAN-10:20 | 2.33 | 2.17 |
February | 0.140799E+11 | 18773.76 | 24-FEB-17:00 | 6.00 | 1.47 | 0.173607E+10 | 2606.65 | 28-FEB-10:20 | 2.67 | 1.45 |
March | 0.183858E+11 | 22602.68 | 15-MAR-16:00 | 19.00 | 5.38 | 0.211479E+10 | 2606.65 | 02-MAR-10:20 | 19.00 | 5.38 |
April | 0.163188E+11 | 25784.62 | 22-APR-05:02 | 0.00 | -0.0 | 0.188717E+10 | 2606.77 | 13-APR-13:00 | 0.00 | -0.0 |
May | 0.222031E+11 | 25834.18 | 12-MAY-05:03 | 1.50 | 0.50 | 0.207544E+10 | 2606.74 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.291502E+11 | 41606.29 | 28-JUN-05:12 | 15.53 | 7.02 | 0.207215E+10 | 2606.67 | 20-JUN-09:30 | 15.53 | 7.02 |
July | 0.286967E+11 | 42293.94 | 10-JUL-05:12 | 17.33 | 9.81 | 0.192579E+10 | 2606.68 | 14-JUL-09:09 | 24.33 | 11.85 |
August | 0.308515E+11 | 44627.44 | 17-AUG-06:02 | 12.33 | 5.30 | 0.216214E+10 | 2606.68 | 29-AUG-09:00 | 22.00 | 14.30 |
September | 0.272424E+11 | 48062.84 | 22-SEP-05:01 | -1.7 | -2.9 | 0.191914E+10 | 2606.89 | 05-SEP-09:09 | -1.7 | -2.9 |
October | 0.213208E+11 | 44536.65 | 17-OCT-05:01 | 1.00 | -2.1 | 0.198444E+10 | 2606.76 | 03-OCT-13:09 | 1.00 | -2.1 |
November | 0.172778E+11 | 21743.32 | 08-NOV-16:30 | 15.50 | 6.83 | 0.195655E+10 | 2606.65 | 16-NOV-14:20 | 16.00 | 6.70 |
December | 0.151438E+11 | 18487.37 | 15-DEC-16:00 | 6.00 | 2.22 | 0.185140E+10 | 2606.64 | 15-DEC-14:30 | 6.00 | 2.22 |
Annual Sum or Average | 0.255867E+12 | 0.236180E+11 | ||||||||
Minimum of Months | 0.140799E+11 | 18487.37 | -2.0 | -2.9 | 0.173607E+10 | 2606.64 | -1.7 | -2.9 | ||
Maximum of Months | 0.308515E+11 | 48062.84 | 19.00 | 9.81 | 0.216214E+10 | 2606.89 | 24.33 | 14.30 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.795797E+09 | 5987.65 | 20-JAN-13:40 | 21.00 | 6.96 | 0.00 | 0.00 | 01-JAN-00:10 | 21.00 | 6.96 |
February | 0.111950E+10 | 6588.61 | 18-FEB-13:40 | 20.00 | 7.73 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.73 |
March | 0.271715E+10 | 10995.96 | 14-MAR-13:30 | 23.50 | 7.75 | 0.00 | 0.00 | 01-MAR-00:10 | 23.50 | 7.75 |
April | 0.302244E+10 | 10180.10 | 21-APR-13:30 | 15.50 | 6.04 | 0.00 | 0.00 | 01-APR-00:10 | 15.50 | 6.04 |
May | 0.570720E+10 | 14443.42 | 31-MAY-14:05 | 28.00 | 14.83 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.83 |
June | 0.116735E+11 | 19293.37 | 26-JUN-13:05 | 36.78 | 15.39 | 0.00 | 0.00 | 01-JUN-00:10 | 36.78 | 15.39 |
July | 0.106894E+11 | 16750.34 | 07-JUL-14:30 | 31.50 | 14.08 | 0.00 | 0.00 | 01-JUL-00:10 | 31.50 | 14.08 |
August | 0.107537E+11 | 19000.15 | 16-AUG-14:00 | 37.00 | 16.36 | 0.00 | 0.00 | 01-AUG-00:10 | 37.00 | 16.36 |
September | 0.711186E+10 | 14652.04 | 12-SEP-13:40 | 29.40 | 13.70 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.70 |
October | 0.302565E+10 | 11129.74 | 11-OCT-14:00 | 27.00 | 9.73 | 0.00 | 0.00 | 01-OCT-00:10 | 27.00 | 9.73 |
November | 0.129929E+10 | 6635.35 | 09-NOV-12:30 | 20.00 | 9.14 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 9.14 |
December | 0.546645E+09 | 4633.10 | 01-DEC-13:40 | 21.67 | 7.88 | 0.00 | 0.00 | 01-DEC-00:10 | 21.67 | 7.88 |
Annual Sum or Average | 0.584621E+11 | 0.00 | ||||||||
Minimum of Months | 0.546645E+09 | 4633.10 | 15.50 | 6.04 | 0.00 | 0.00 | 15.50 | 6.04 | ||
Maximum of Months | 0.116735E+11 | 19293.37 | 37.00 | 16.36 | 0.00 | 0.00 | 37.00 | 16.36 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344327E+09 | 5202.05 | 05-JAN-05:02 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 0.320777E+09 | 5395.07 | 12-FEB-05:31 | -19.3 | -19.3 | 0.00 | 0.00 | 01-FEB-00:10 | -19.3 | -19.3 |
March | 0.795646E+09 | 4517.08 | 18-MAR-05:01 | -0.2 | -0.3 | 0.00 | 0.00 | 01-MAR-00:10 | -0.2 | -0.3 |
April | 0.800417E+09 | 4299.79 | 15-APR-05:01 | -5.0 | -5.1 | 0.00 | 0.00 | 01-APR-00:10 | -5.0 | -5.1 |
May | 0.182326E+10 | 2988.23 | 18-MAY-21:00 | 7.00 | 4.43 | 0.00 | 0.00 | 01-MAY-00:10 | 7.00 | 4.43 |
June | 0.436932E+10 | 5437.16 | 26-JUN-15:40 | 39.00 | 15.72 | 0.00 | 0.00 | 01-JUN-00:10 | 39.00 | 15.72 |
July | 0.435352E+10 | 5692.31 | 17-JUL-14:20 | 34.67 | 14.75 | 0.00 | 0.00 | 01-JUL-00:10 | 34.67 | 14.75 |
August | 0.436315E+10 | 5056.60 | 11-AUG-15:50 | 33.00 | 11.84 | 0.00 | 0.00 | 01-AUG-00:10 | 33.00 | 11.84 |
September | 0.306705E+10 | 4404.83 | 12-SEP-16:00 | 31.10 | 14.26 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 14.26 |
October | 0.102871E+10 | 3299.06 | 28-OCT-05:11 | 2.67 | 1.57 | 0.00 | 0.00 | 01-OCT-00:10 | 2.67 | 1.57 |
November | 0.475324E+09 | 4761.28 | 29-NOV-05:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.0 |
December | 0.258829E+09 | 5328.03 | 21-DEC-05:11 | -18.3 | -18.5 | 0.00 | 0.00 | 01-DEC-00:10 | -18.3 | -18.5 |
Annual Sum or Average | 0.220003E+11 | 0.00 | ||||||||
Minimum of Months | 0.258829E+09 | 2988.23 | -19.3 | -19.3 | 0.00 | 0.00 | -19.3 | -19.3 | ||
Maximum of Months | 0.436932E+10 | 5692.31 | 39.00 | 15.72 | 0.00 | 0.00 | 39.00 | 15.72 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.742944E+09 | 5075.86 | 06-JAN-05:01 | -7.8 | -7.9 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -7.9 |
February | 0.680616E+09 | 4245.62 | 04-FEB-06:01 | -5.0 | -5.0 | 0.00 | 0.00 | 01-FEB-00:10 | -5.0 | -5.0 |
March | 0.135971E+10 | 4571.62 | 02-MAR-06:01 | -8.2 | -8.2 | 0.00 | 0.00 | 01-MAR-00:10 | -8.2 | -8.2 |
April | 0.124402E+10 | 5371.28 | 26-APR-05:11 | 2.33 | 0.28 | 0.00 | 0.00 | 01-APR-00:10 | 2.33 | 0.28 |
May | 0.265334E+10 | 4344.03 | 02-MAY-05:11 | 1.33 | -0.4 | 0.00 | 0.00 | 01-MAY-00:10 | 1.33 | -0.4 |
June | 0.495233E+10 | 5449.36 | 26-JUN-16:00 | 38.80 | 15.76 | 0.00 | 0.00 | 01-JUN-00:10 | 38.80 | 15.76 |
July | 0.492573E+10 | 5790.93 | 17-JUL-14:05 | 34.83 | 14.84 | 0.00 | 0.00 | 01-JUL-00:10 | 34.83 | 14.84 |
August | 0.524302E+10 | 5569.89 | 16-AUG-15:40 | 36.67 | 16.29 | 0.00 | 0.00 | 01-AUG-00:10 | 36.67 | 16.29 |
September | 0.415673E+10 | 5323.39 | 12-SEP-15:50 | 30.82 | 14.19 | 0.00 | 0.00 | 01-SEP-00:10 | 30.82 | 14.19 |
October | 0.196447E+10 | 4068.10 | 11-OCT-16:00 | 24.00 | 8.61 | 0.00 | 0.00 | 01-OCT-00:10 | 24.00 | 8.61 |
November | 0.105665E+10 | 3550.60 | 02-NOV-05:01 | -9.0 | -9.0 | 0.00 | 0.00 | 01-NOV-00:10 | -9.0 | -9.0 |
December | 0.544287E+09 | 5408.56 | 21-DEC-05:11 | -18.3 | -18.5 | 0.00 | 0.00 | 01-DEC-00:10 | -18.3 | -18.5 |
Annual Sum or Average | 0.295238E+11 | 0.00 | ||||||||
Minimum of Months | 0.544287E+09 | 3550.60 | -18.3 | -18.5 | 0.00 | 0.00 | -18.3 | -18.5 | ||
Maximum of Months | 0.524302E+10 | 5790.93 | 38.80 | 16.29 | 0.00 | 0.00 | 38.80 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.940946E+10 | 11473.94 | 20-JAN-16:50 | 13.00 | 5.63 | 0.175482E+10 | 2606.63 | 25-JAN-14:20 | 14.67 | 4.64 |
February | 0.853753E+10 | 10745.49 | 24-FEB-17:00 | 6.00 | 1.47 | 0.158181E+10 | 2606.63 | 28-FEB-14:30 | 4.50 | 2.83 |
March | 0.117001E+11 | 15991.75 | 15-MAR-16:00 | 19.00 | 5.38 | 0.197792E+10 | 2606.65 | 17-MAR-09:20 | 6.67 | 6.28 |
April | 0.103442E+11 | 14584.22 | 21-APR-16:00 | 13.00 | 5.24 | 0.175778E+10 | 2606.73 | 13-APR-13:00 | 13.00 | 5.24 |
May | 0.147379E+11 | 17331.04 | 18-MAY-16:00 | 19.00 | 11.41 | 0.202963E+10 | 2606.69 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.209502E+11 | 27868.46 | 27-JUN-05:12 | 18.63 | 8.20 | 0.206501E+10 | 2606.66 | 08-JUN-13:20 | 18.63 | 8.20 |
July | 0.205206E+11 | 31846.87 | 17-JUL-05:12 | 20.00 | 10.12 | 0.191893E+10 | 2606.66 | 14-JUL-09:20 | 20.00 | 10.12 |
August | 0.213915E+11 | 26224.45 | 21-AUG-05:12 | 19.83 | 12.23 | 0.215605E+10 | 2606.65 | 15-AUG-13:20 | 19.83 | 12.23 |
September | 0.178602E+11 | 21595.23 | 11-SEP-05:13 | 18.07 | 8.67 | 0.190582E+10 | 2606.86 | 05-SEP-09:09 | 18.07 | 8.67 |
October | 0.124487E+11 | 17060.92 | 11-OCT-16:00 | 24.00 | 8.61 | 0.188588E+10 | 2606.67 | 03-OCT-13:20 | 24.00 | 8.61 |
November | 0.103135E+11 | 13880.01 | 08-NOV-16:40 | 14.67 | 6.46 | 0.180033E+10 | 2606.64 | 08-NOV-14:20 | 14.67 | 6.46 |
December | 0.904575E+10 | 10039.77 | 15-DEC-16:00 | 6.00 | 2.22 | 0.165583E+10 | 2606.63 | 15-DEC-14:30 | 6.00 | 2.22 |
Annual Sum or Average | 0.167260E+12 | 0.224898E+11 | ||||||||
Minimum of Months | 0.853753E+10 | 10039.77 | 6.00 | 1.47 | 0.158181E+10 | 2606.63 | 4.50 | 2.22 | ||
Maximum of Months | 0.213915E+11 | 31846.87 | 24.00 | 12.23 | 0.215605E+10 | 2606.86 | 24.00 | 12.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761621E+10 | 10505.76 | 20-JAN-16:20 | 16.00 | 6.84 | 0.159745E+10 | 2579.00 | 20-JAN-14:00 | 16.00 | 6.84 |
February | 0.699230E+10 | 9573.32 | 17-FEB-17:00 | 13.00 | 6.46 | 0.145723E+10 | 2497.61 | 17-FEB-14:00 | 13.00 | 6.46 |
March | 0.107067E+11 | 17469.48 | 15-MAR-15:40 | 19.33 | 5.50 | 0.184934E+10 | 2606.63 | 10-MAR-14:20 | 19.33 | 5.50 |
April | 0.102037E+11 | 16936.34 | 21-APR-14:00 | 15.00 | 5.55 | 0.166244E+10 | 2606.74 | 13-APR-13:00 | 15.00 | 5.55 |
May | 0.151065E+11 | 19884.21 | 18-MAY-15:20 | 21.67 | 11.66 | 0.196817E+10 | 2606.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.228605E+11 | 24423.35 | 26-JUN-15:00 | 39.40 | 15.63 | 0.205233E+10 | 2606.67 | 08-JUN-13:20 | 39.40 | 15.63 |
July | 0.220942E+11 | 24330.56 | 17-JUL-14:00 | 35.00 | 14.93 | 0.190858E+10 | 2606.65 | 14-JUL-09:20 | 35.00 | 14.93 |
August | 0.225039E+11 | 23740.08 | 16-AUG-15:20 | 36.33 | 16.22 | 0.214079E+10 | 2606.65 | 15-AUG-13:20 | 36.33 | 16.22 |
September | 0.175549E+11 | 21290.98 | 12-SEP-15:20 | 29.97 | 13.95 | 0.186492E+10 | 2606.84 | 05-SEP-09:09 | 29.97 | 13.95 |
October | 0.108957E+11 | 17708.19 | 11-OCT-16:00 | 24.00 | 8.61 | 0.173571E+10 | 2606.65 | 10-OCT-13:20 | 24.00 | 8.61 |
November | 0.840460E+10 | 12154.28 | 08-NOV-16:00 | 18.00 | 7.82 | 0.163116E+10 | 2606.64 | 08-NOV-14:20 | 18.00 | 7.82 |
December | 0.663748E+10 | 9106.78 | 14-DEC-16:10 | 12.17 | 4.27 | 0.150172E+10 | 2433.35 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.161577E+12 | 0.213698E+11 | ||||||||
Minimum of Months | 0.663748E+10 | 9106.78 | 12.17 | 4.27 | 0.145723E+10 | 2433.35 | 9.00 | 3.00 | ||
Maximum of Months | 0.228605E+11 | 24423.35 | 39.40 | 16.22 | 0.214079E+10 | 2606.84 | 39.40 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.839628E+09 | 3285.02 | 20-JAN-15:50 | 18.33 | 7.40 | 0.308345E+09 | 465.78 | 20-JAN-14:00 | 18.33 | 7.40 |
February | 0.798103E+09 | 3101.98 | 27-FEB-15:40 | 13.33 | 4.47 | 0.279214E+09 | 444.41 | 27-FEB-14:00 | 13.33 | 4.47 |
March | 0.208375E+10 | 4039.62 | 14-MAR-14:50 | 23.00 | 7.59 | 0.349934E+09 | 538.96 | 14-MAR-13:00 | 23.00 | 7.59 |
April | 0.232971E+10 | 4080.48 | 20-APR-13:40 | 21.33 | 8.72 | 0.317334E+09 | 547.17 | 20-APR-13:50 | 21.17 | 8.62 |
May | 0.465241E+10 | 6492.78 | 17-MAY-13:30 | 29.00 | 11.78 | 0.383671E+09 | 549.50 | 18-MAY-13:09 | 24.00 | 11.61 |
June | 0.768643E+10 | 8696.45 | 26-JUN-15:00 | 39.40 | 15.63 | 0.424906E+09 | 549.50 | 27-JUN-09:20 | 25.53 | 11.25 |
July | 0.752539E+10 | 8971.72 | 17-JUL-13:40 | 35.33 | 14.88 | 0.394331E+09 | 549.50 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.714512E+10 | 7981.59 | 16-AUG-14:00 | 37.00 | 16.36 | 0.436868E+09 | 549.50 | 15-AUG-13:20 | 37.00 | 16.36 |
September | 0.537529E+10 | 7116.35 | 11-SEP-14:30 | 28.85 | 13.58 | 0.369094E+09 | 549.51 | 01-SEP-13:00 | 28.85 | 13.58 |
October | 0.243977E+10 | 4422.53 | 11-OCT-14:50 | 26.17 | 9.50 | 0.327570E+09 | 549.44 | 11-OCT-13:00 | 26.17 | 9.50 |
November | 0.119071E+10 | 3627.26 | 09-NOV-14:00 | 20.00 | 8.60 | 0.311028E+09 | 500.28 | 09-NOV-14:09 | 19.67 | 8.52 |
December | 0.585306E+09 | 3020.35 | 01-DEC-15:30 | 19.50 | 7.14 | 0.295080E+09 | 441.31 | 01-DEC-14:00 | 19.50 | 7.14 |
Annual Sum or Average | 0.426516E+11 | 0.419737E+10 | ||||||||
Minimum of Months | 0.585306E+09 | 3020.35 | 13.33 | 4.47 | 0.279214E+09 | 441.31 | 13.33 | 4.47 | ||
Maximum of Months | 0.768643E+10 | 8971.72 | 39.40 | 16.36 | 0.436868E+09 | 549.51 | 37.00 | 16.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107277E+10 | 2715.77 | 20-JAN-10:10 | 14.67 | 5.12 | 0.201175E+09 | 334.75 | 20-JAN-10:20 | 15.33 | 5.45 |
February | 0.117937E+10 | 2809.30 | 27-FEB-09:30 | 9.50 | 2.73 | 0.185931E+09 | 338.12 | 27-FEB-10:09 | 10.33 | 2.98 |
March | 0.225340E+10 | 6081.45 | 15-MAR-09:10 | 14.17 | 4.19 | 0.241645E+09 | 347.88 | 27-MAR-09:20 | 1.33 | -0.7 |
April | 0.236118E+10 | 6569.14 | 21-APR-09:00 | 12.00 | 5.98 | 0.218671E+09 | 347.89 | 13-APR-09:00 | 12.00 | 5.98 |
May | 0.407945E+10 | 7457.23 | 16-MAY-08:50 | 22.50 | 11.55 | 0.259073E+09 | 347.90 | 31-MAY-09:39 | 24.33 | 13.31 |
June | 0.703285E+10 | 13466.69 | 11-JUN-08:52 | 20.00 | 10.75 | 0.273914E+09 | 347.90 | 20-JUN-09:30 | 25.00 | 15.04 |
July | 0.666350E+10 | 16291.36 | 09-JUL-09:12 | 25.33 | 12.97 | 0.253633E+09 | 348.21 | 17-JUL-09:09 | 31.50 | 14.04 |
August | 0.684315E+10 | 11865.46 | 20-AUG-09:12 | 26.67 | 14.00 | 0.284328E+09 | 347.91 | 30-AUG-09:50 | 24.50 | 12.38 |
September | 0.491508E+10 | 7684.22 | 08-SEP-09:30 | 25.25 | 11.81 | 0.246070E+09 | 347.92 | 05-SEP-09:09 | 25.25 | 11.81 |
October | 0.225950E+10 | 5179.28 | 11-OCT-09:40 | 22.07 | 8.25 | 0.223528E+09 | 347.88 | 10-OCT-13:20 | 22.07 | 8.25 |
November | 0.129116E+10 | 2931.98 | 07-NOV-09:20 | 14.00 | 4.09 | 0.205608E+09 | 346.36 | 07-NOV-10:09 | 14.33 | 4.34 |
December | 0.796266E+09 | 2275.12 | 01-DEC-09:50 | 13.00 | 4.57 | 0.189473E+09 | 294.64 | 01-DEC-10:09 | 14.83 | 5.40 |
Annual Sum or Average | 0.407477E+11 | 0.278305E+10 | ||||||||
Minimum of Months | 0.796266E+09 | 2275.12 | 9.50 | 2.73 | 0.185931E+09 | 294.64 | 1.33 | -0.7 | ||
Maximum of Months | 0.703285E+10 | 16291.36 | 26.67 | 14.00 | 0.284328E+09 | 348.21 | 31.50 | 15.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406277E+10 | 13356.95 | 20-JAN-13:30 | 21.00 | 6.97 | 0.363445E+09 | 549.50 | 24-JAN-14:20 | 17.67 | 6.59 |
February | 0.368222E+10 | 11132.53 | 17-FEB-13:40 | 14.67 | 6.08 | 0.330091E+09 | 549.51 | 17-FEB-14:00 | 15.00 | 6.93 |
March | 0.463462E+10 | 13102.55 | 15-MAR-13:07 | 20.17 | 5.84 | 0.391134E+09 | 549.53 | 14-MAR-13:09 | 20.17 | 5.84 |
April | 0.347436E+10 | 9512.66 | 21-APR-13:10 | 15.83 | 6.37 | 0.342709E+09 | 549.53 | 13-APR-13:39 | 15.83 | 6.37 |
May | 0.538758E+10 | 8844.19 | 16-MAY-13:30 | 27.50 | 12.26 | 0.395039E+09 | 549.51 | 10-MAY-13:09 | 27.50 | 12.26 |
June | 0.847019E+10 | 10820.36 | 30-JUN-12:50 | 34.30 | 13.59 | 0.423141E+09 | 549.51 | 16-JUN-13:20 | 34.30 | 13.59 |
July | 0.848749E+10 | 17670.26 | 09-JUL-13:52 | 35.00 | 13.89 | 0.394018E+09 | 549.50 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.957810E+10 | 14127.22 | 31-AUG-12:50 | 30.00 | 12.10 | 0.440908E+09 | 549.77 | 31-AUG-13:39 | 30.00 | 11.76 |
September | 0.835627E+10 | 23328.48 | 17-SEP-13:22 | 26.35 | 10.86 | 0.384189E+09 | 549.92 | 28-SEP-13:00 | 30.50 | 11.31 |
October | 0.560466E+10 | 17204.37 | 08-OCT-12:52 | 21.00 | 8.56 | 0.364824E+09 | 549.88 | 11-OCT-13:00 | 27.00 | 9.73 |
November | 0.438218E+10 | 16393.47 | 05-NOV-13:12 | 21.00 | 6.50 | 0.363281E+09 | 549.50 | 16-NOV-14:09 | 16.00 | 6.65 |
December | 0.328597E+10 | 11912.88 | 03-DEC-13:42 | 17.87 | 6.56 | 0.337617E+09 | 549.51 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.694064E+11 | 0.453040E+10 | ||||||||
Minimum of Months | 0.328597E+10 | 8844.19 | 14.67 | 5.84 | 0.330091E+09 | 549.50 | 9.00 | 3.00 | ||
Maximum of Months | 0.957810E+10 | 23328.48 | 35.00 | 13.89 | 0.440908E+09 | 549.92 | 34.30 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117998E+10 | 4915.39 | 20-JAN-15:40 | 18.67 | 7.30 | 0.203785E+09 | 347.83 | 20-JAN-14:00 | 18.67 | 7.30 |
February | 0.118104E+10 | 5216.85 | 17-FEB-16:30 | 13.50 | 6.66 | 0.186370E+09 | 346.95 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.233262E+10 | 8239.16 | 13-MAR-16:00 | 23.00 | 6.97 | 0.228335E+09 | 347.85 | 10-MAR-14:20 | 23.00 | 6.97 |
April | 0.231150E+10 | 8565.72 | 07-APR-16:00 | 21.00 | 8.12 | 0.204317E+09 | 347.83 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.416194E+10 | 9393.40 | 31-MAY-16:00 | 28.00 | 14.86 | 0.240261E+09 | 347.86 | 18-MAY-13:20 | 28.00 | 14.86 |
June | 0.689656E+10 | 19916.28 | 04-JUN-15:31 | 30.00 | 12.76 | 0.263220E+09 | 347.86 | 16-JUN-13:20 | 24.57 | 15.19 |
July | 0.629895E+10 | 21059.00 | 02-JUL-16:41 | 28.00 | 12.40 | 0.244407E+09 | 347.86 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.648021E+10 | 14498.69 | 26-AUG-17:42 | 30.17 | 11.61 | 0.271003E+09 | 347.86 | 15-AUG-13:20 | 30.17 | 11.61 |
September | 0.491916E+10 | 18811.91 | 17-SEP-16:42 | 26.18 | 10.81 | 0.229987E+09 | 347.87 | 01-SEP-13:00 | 26.18 | 10.81 |
October | 0.257935E+10 | 8213.08 | 11-OCT-15:30 | 25.00 | 9.04 | 0.212929E+09 | 347.86 | 10-OCT-13:20 | 25.00 | 9.04 |
November | 0.144998E+10 | 5890.02 | 07-NOV-15:30 | 21.50 | 7.27 | 0.205038E+09 | 347.85 | 08-NOV-14:20 | 19.00 | 7.64 |
December | 0.848759E+09 | 3837.58 | 01-DEC-15:30 | 19.50 | 7.14 | 0.192355E+09 | 345.66 | 01-DEC-14:00 | 19.50 | 7.14 |
Annual Sum or Average | 0.406401E+11 | 0.268201E+10 | ||||||||
Minimum of Months | 0.848759E+09 | 3837.58 | 13.50 | 6.66 | 0.186370E+09 | 345.66 | 13.50 | 5.55 | ||
Maximum of Months | 0.689656E+10 | 21059.00 | 30.17 | 14.86 | 0.271003E+09 | 347.87 | 31.00 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.632701E+09 | 2248.60 | 20-JAN-15:50 | 18.33 | 7.40 | 0.308569E+09 | 444.34 | 20-JAN-14:00 | 18.33 | 7.40 |
February | 0.453429E+09 | 2131.80 | 27-FEB-15:40 | 13.33 | 4.47 | 0.278576E+09 | 426.66 | 27-FEB-14:00 | 13.33 | 4.47 |
March | 0.127887E+10 | 2641.12 | 14-MAR-15:20 | 22.67 | 7.41 | 0.343212E+09 | 492.40 | 14-MAR-13:00 | 22.67 | 7.41 |
April | 0.153817E+10 | 2643.01 | 20-APR-13:40 | 21.33 | 8.72 | 0.308918E+09 | 496.05 | 20-APR-13:50 | 21.17 | 8.62 |
May | 0.322469E+10 | 3876.63 | 17-MAY-13:30 | 29.00 | 11.78 | 0.376104E+09 | 549.50 | 18-MAY-13:20 | 24.00 | 11.54 |
June | 0.542762E+10 | 6011.37 | 14-JUN-13:30 | 34.95 | 13.21 | 0.427896E+09 | 549.50 | 27-JUN-09:20 | 25.53 | 11.25 |
July | 0.544303E+10 | 6671.48 | 17-JUL-13:30 | 35.50 | 14.85 | 0.398235E+09 | 549.50 | 14-JUL-09:20 | 35.50 | 14.85 |
August | 0.555377E+10 | 6159.59 | 18-AUG-14:20 | 35.00 | 13.50 | 0.446295E+09 | 549.50 | 17-AUG-13:20 | 35.00 | 13.50 |
September | 0.480188E+10 | 6233.88 | 11-SEP-14:30 | 28.85 | 13.58 | 0.387295E+09 | 549.52 | 05-SEP-09:20 | 28.85 | 13.58 |
October | 0.270829E+10 | 3780.10 | 11-OCT-13:50 | 26.83 | 9.68 | 0.343040E+09 | 535.00 | 11-OCT-15:00 | 24.00 | 8.61 |
November | 0.148224E+10 | 3073.90 | 05-NOV-14:22 | 21.00 | 6.57 | 0.318182E+09 | 514.69 | 09-NOV-14:09 | 19.67 | 8.52 |
December | 0.717746E+09 | 2295.58 | 04-DEC-15:02 | 18.67 | 6.02 | 0.297568E+09 | 451.18 | 04-DEC-14:00 | 18.67 | 6.02 |
Annual Sum or Average | 0.332624E+11 | 0.423389E+10 | ||||||||
Minimum of Months | 0.453429E+09 | 2131.80 | 13.33 | 4.47 | 0.278576E+09 | 426.66 | 13.33 | 4.47 | ||
Maximum of Months | 0.555377E+10 | 6671.48 | 35.50 | 14.85 | 0.446295E+09 | 549.52 | 35.50 | 14.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.954523E+09 | 2124.56 | 20-JAN-10:05 | 14.67 | 5.12 | 0.202946E+09 | 327.28 | 20-JAN-10:09 | 14.67 | 5.12 |
February | 0.946222E+09 | 2268.35 | 27-FEB-09:10 | 9.17 | 2.67 | 0.185858E+09 | 336.48 | 27-FEB-10:09 | 10.33 | 2.98 |
March | 0.172388E+10 | 4019.89 | 15-MAR-09:10 | 14.17 | 4.19 | 0.239331E+09 | 347.87 | 10-MAR-10:20 | 14.17 | 4.19 |
April | 0.182912E+10 | 4249.14 | 21-APR-09:00 | 12.00 | 5.98 | 0.215776E+09 | 347.88 | 13-APR-09:00 | 12.00 | 5.98 |
May | 0.303486E+10 | 5007.98 | 16-MAY-09:00 | 23.00 | 11.65 | 0.257465E+09 | 347.88 | 31-MAY-09:39 | 24.33 | 13.31 |
June | 0.568555E+10 | 7553.73 | 25-JUN-10:22 | 30.50 | 12.35 | 0.274783E+09 | 347.89 | 20-JUN-09:30 | 30.50 | 12.35 |
July | 0.544852E+10 | 13140.18 | 16-JUL-08:31 | 32.00 | 14.64 | 0.254993E+09 | 348.09 | 17-JUL-09:39 | 33.00 | 14.28 |
August | 0.607874E+10 | 13292.08 | 20-AUG-09:41 | 27.67 | 14.10 | 0.286710E+09 | 347.96 | 07-AUG-09:09 | 27.67 | 14.10 |
September | 0.491164E+10 | 6913.78 | 08-SEP-09:30 | 25.25 | 11.81 | 0.251904E+09 | 347.91 | 05-SEP-09:09 | 25.25 | 11.81 |
October | 0.256676E+10 | 4977.20 | 11-OCT-09:40 | 22.07 | 8.25 | 0.234654E+09 | 347.88 | 03-OCT-09:20 | 22.07 | 8.25 |
November | 0.160917E+10 | 3157.28 | 07-NOV-08:15 | 11.33 | 3.17 | 0.214523E+09 | 347.87 | 07-NOV-10:20 | 14.67 | 4.58 |
December | 0.931871E+09 | 2156.16 | 03-DEC-10:32 | 13.47 | 4.35 | 0.194006E+09 | 306.63 | 01-DEC-10:09 | 13.47 | 4.35 |
Annual Sum or Average | 0.357209E+11 | 0.281295E+10 | ||||||||
Minimum of Months | 0.931871E+09 | 2124.56 | 9.17 | 2.67 | 0.185858E+09 | 306.63 | 10.33 | 2.98 | ||
Maximum of Months | 0.607874E+10 | 13292.08 | 32.00 | 14.64 | 0.286710E+09 | 348.09 | 33.00 | 14.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269447E+10 | 9720.76 | 20-JAN-14:00 | 21.00 | 6.96 | 0.350401E+09 | 549.51 | 11-JAN-14:20 | 21.00 | 6.96 |
February | 0.209052E+10 | 9809.92 | 27-FEB-13:05 | 14.00 | 4.75 | 0.309497E+09 | 549.51 | 15-FEB-14:20 | 14.00 | 4.75 |
March | 0.268921E+10 | 9560.46 | 14-MAR-13:05 | 23.83 | 7.85 | 0.375963E+09 | 549.52 | 14-MAR-13:09 | 23.83 | 7.85 |
April | 0.195726E+10 | 5383.02 | 20-APR-12:10 | 20.33 | 9.03 | 0.325111E+09 | 549.50 | 27-APR-13:20 | 20.00 | 9.36 |
May | 0.330904E+10 | 6608.35 | 16-MAY-12:00 | 27.00 | 11.84 | 0.380752E+09 | 549.51 | 18-MAY-13:09 | 24.00 | 11.61 |
June | 0.670969E+10 | 14390.70 | 26-JUN-16:10 | 38.62 | 15.67 | 0.424582E+09 | 549.51 | 29-JUN-13:20 | 33.10 | 14.03 |
July | 0.679645E+10 | 14044.56 | 17-JUL-12:00 | 36.00 | 14.76 | 0.396404E+09 | 550.56 | 17-JUL-12:09 | 36.00 | 14.76 |
August | 0.848605E+10 | 14515.79 | 16-AUG-12:00 | 35.00 | 12.77 | 0.446967E+09 | 570.90 | 16-AUG-12:09 | 35.17 | 12.78 |
September | 0.812165E+10 | 17470.42 | 17-SEP-13:22 | 26.35 | 10.86 | 0.394382E+09 | 566.76 | 28-SEP-12:09 | 30.08 | 11.35 |
October | 0.513664E+10 | 18380.24 | 09-OCT-13:52 | 22.00 | 8.58 | 0.370639E+09 | 549.64 | 10-OCT-13:00 | 25.00 | 8.71 |
November | 0.375415E+10 | 17847.47 | 05-NOV-13:42 | 21.00 | 6.39 | 0.359060E+09 | 549.81 | 06-NOV-14:50 | 20.33 | 6.68 |
December | 0.252730E+10 | 8959.13 | 15-DEC-13:06 | 11.17 | 2.99 | 0.328087E+09 | 549.51 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.542724E+11 | 0.446185E+10 | ||||||||
Minimum of Months | 0.195726E+10 | 5383.02 | 11.17 | 2.99 | 0.309497E+09 | 549.50 | 9.00 | 3.00 | ||
Maximum of Months | 0.848605E+10 | 18380.24 | 38.62 | 15.67 | 0.446967E+09 | 570.90 | 36.00 | 14.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101354E+10 | 3452.90 | 20-JAN-16:00 | 18.00 | 7.49 | 0.203631E+09 | 338.71 | 20-JAN-15:00 | 18.00 | 7.49 |
February | 0.898630E+09 | 3646.20 | 17-FEB-16:30 | 13.50 | 6.66 | 0.184326E+09 | 338.68 | 17-FEB-16:00 | 13.00 | 6.46 |
March | 0.165276E+10 | 5138.29 | 13-MAR-16:50 | 22.17 | 6.72 | 0.226853E+09 | 347.16 | 10-MAR-14:00 | 22.17 | 6.72 |
April | 0.169123E+10 | 4859.46 | 07-APR-16:00 | 21.00 | 8.12 | 0.201279E+09 | 338.68 | 07-APR-15:00 | 21.00 | 8.12 |
May | 0.297847E+10 | 5780.95 | 31-MAY-16:00 | 28.00 | 14.86 | 0.240152E+09 | 347.85 | 18-MAY-13:20 | 28.00 | 14.86 |
June | 0.527979E+10 | 14580.32 | 25-JUN-16:21 | 32.70 | 13.84 | 0.269021E+09 | 347.86 | 27-JUN-09:20 | 25.53 | 11.25 |
July | 0.479471E+10 | 14262.48 | 02-JUL-17:11 | 28.00 | 12.39 | 0.249787E+09 | 347.85 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.537562E+10 | 14332.19 | 20-AUG-15:41 | 28.00 | 14.08 | 0.281076E+09 | 347.86 | 15-AUG-13:20 | 28.00 | 14.08 |
September | 0.459719E+10 | 15342.09 | 10-SEP-17:11 | 30.13 | 12.08 | 0.245480E+09 | 347.86 | 01-SEP-13:00 | 30.13 | 12.08 |
October | 0.283751E+10 | 14191.55 | 09-OCT-16:32 | 21.33 | 8.70 | 0.223927E+09 | 347.85 | 10-OCT-13:20 | 24.33 | 8.20 |
November | 0.171790E+10 | 5145.40 | 07-NOV-15:40 | 21.33 | 7.24 | 0.210689E+09 | 347.85 | 08-NOV-14:20 | 19.00 | 7.64 |
December | 0.948412E+09 | 3026.99 | 01-DEC-15:30 | 19.50 | 7.14 | 0.194839E+09 | 338.70 | 14-DEC-15:50 | 13.50 | 4.67 |
Annual Sum or Average | 0.337858E+11 | 0.273106E+10 | ||||||||
Minimum of Months | 0.898630E+09 | 3026.99 | 13.50 | 6.66 | 0.184326E+09 | 338.68 | 13.00 | 4.67 | ||
Maximum of Months | 0.537562E+10 | 15342.09 | 32.70 | 14.86 | 0.281076E+09 | 347.86 | 31.00 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119176E+10 | 3203.88 | 20-JAN-13:30 | 21.00 | 6.97 | 0.314284E+09 | 476.85 | 20-JAN-14:00 | 20.00 | 6.78 |
February | 0.101798E+10 | 3035.33 | 26-FEB-13:12 | 17.67 | 4.65 | 0.284040E+09 | 475.03 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.218797E+10 | 3691.73 | 14-MAR-15:20 | 22.67 | 7.41 | 0.361857E+09 | 549.48 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.230764E+10 | 3551.96 | 20-APR-13:30 | 21.50 | 8.83 | 0.329315E+09 | 549.48 | 20-APR-13:20 | 21.50 | 8.83 |
May | 0.418058E+10 | 6060.24 | 17-MAY-13:30 | 29.00 | 11.78 | 0.404377E+09 | 549.50 | 18-MAY-13:09 | 24.00 | 11.61 |
June | 0.688331E+10 | 7638.99 | 26-JUN-15:00 | 39.40 | 15.63 | 0.432525E+09 | 549.50 | 27-JUN-09:20 | 25.53 | 11.25 |
July | 0.675852E+10 | 12143.22 | 16-JUL-13:52 | 35.00 | 14.25 | 0.401878E+09 | 549.51 | 14-JUL-09:09 | 35.00 | 14.25 |
August | 0.643028E+10 | 7185.28 | 18-AUG-14:00 | 35.00 | 13.50 | 0.448856E+09 | 549.50 | 15-AUG-13:20 | 35.00 | 13.50 |
September | 0.499774E+10 | 6796.18 | 11-SEP-14:30 | 28.85 | 13.58 | 0.386868E+09 | 549.54 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.271546E+10 | 4278.18 | 11-OCT-14:50 | 26.17 | 9.50 | 0.345355E+09 | 549.48 | 11-OCT-13:00 | 26.17 | 9.50 |
November | 0.160477E+10 | 3401.29 | 07-NOV-13:30 | 21.00 | 7.19 | 0.320878E+09 | 534.03 | 09-NOV-14:20 | 19.33 | 8.45 |
December | 0.889693E+09 | 2897.67 | 03-DEC-13:42 | 17.87 | 6.56 | 0.299055E+09 | 467.39 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.411657E+11 | 0.432929E+10 | ||||||||
Minimum of Months | 0.889693E+09 | 2897.67 | 17.67 | 4.65 | 0.284040E+09 | 467.39 | 14.00 | 4.75 | ||
Maximum of Months | 0.688331E+10 | 12143.22 | 39.40 | 15.63 | 0.448856E+09 | 549.54 | 35.00 | 14.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112864E+10 | 4297.48 | 20-JAN-13:02 | 21.00 | 6.97 | 0.154297E+09 | 356.46 | 11-JAN-11:09 | 21.00 | 6.97 |
February | 0.116775E+10 | 4724.15 | 23-FEB-13:01 | 9.00 | 4.54 | 0.142851E+09 | 356.45 | 14-FEB-11:09 | 9.00 | 4.54 |
March | 0.229257E+10 | 6854.52 | 14-MAR-10:05 | 21.00 | 7.12 | 0.182312E+09 | 356.46 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.233017E+10 | 7130.52 | 21-APR-08:30 | 11.50 | 5.93 | 0.164618E+09 | 356.47 | 13-APR-10:09 | 11.50 | 5.93 |
May | 0.395494E+10 | 7877.08 | 16-MAY-08:30 | 21.50 | 11.33 | 0.194544E+09 | 356.49 | 16-MAY-10:09 | 24.17 | 11.32 |
June | 0.666590E+10 | 12443.58 | 25-JUN-09:52 | 30.50 | 12.20 | 0.202971E+09 | 356.47 | 22-JUN-12:09 | 30.50 | 12.20 |
July | 0.632166E+10 | 16941.04 | 16-JUL-08:31 | 32.00 | 14.64 | 0.188795E+09 | 356.47 | 13-JUL-10:09 | 32.00 | 14.64 |
August | 0.657193E+10 | 17101.02 | 20-AUG-09:01 | 26.33 | 13.95 | 0.210819E+09 | 356.47 | 29-AUG-10:09 | 22.62 | 14.51 |
September | 0.492741E+10 | 9046.68 | 10-SEP-09:22 | 26.90 | 13.43 | 0.183707E+09 | 356.47 | 14-SEP-10:09 | 24.58 | 12.19 |
October | 0.248406E+10 | 6374.63 | 11-OCT-10:05 | 23.17 | 8.56 | 0.169323E+09 | 356.46 | 10-OCT-14:09 | 23.17 | 8.56 |
November | 0.146583E+10 | 4195.01 | 07-NOV-09:10 | 14.00 | 4.09 | 0.157451E+09 | 356.46 | 07-NOV-11:09 | 16.67 | 5.90 |
December | 0.842858E+09 | 3596.09 | 15-DEC-11:02 | 8.50 | 1.88 | 0.144352E+09 | 356.46 | 15-DEC-11:09 | 8.50 | 1.88 |
Annual Sum or Average | 0.401537E+11 | 0.209604E+10 | ||||||||
Minimum of Months | 0.842858E+09 | 3596.09 | 8.50 | 1.88 | 0.142851E+09 | 356.45 | 0.33 | -0.4 | ||
Maximum of Months | 0.666590E+10 | 17101.02 | 32.00 | 14.64 | 0.210819E+09 | 356.49 | 32.00 | 14.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.468078E+10 | 13569.69 | 20-JAN-13:04 | 21.00 | 6.97 | 0.376439E+09 | 549.93 | 20-JAN-14:00 | 20.00 | 6.78 |
February | 0.414124E+10 | 18357.36 | 26-FEB-13:12 | 17.67 | 4.65 | 0.341275E+09 | 549.56 | 17-FEB-14:39 | 17.67 | 4.65 |
March | 0.489051E+10 | 12845.66 | 15-MAR-13:10 | 20.17 | 5.84 | 0.403971E+09 | 550.26 | 14-MAR-13:00 | 20.17 | 5.84 |
April | 0.354676E+10 | 8967.59 | 21-APR-13:10 | 15.83 | 6.37 | 0.354073E+09 | 549.53 | 13-APR-13:00 | 15.83 | 6.37 |
May | 0.507253E+10 | 8130.18 | 16-MAY-13:10 | 27.17 | 12.14 | 0.410790E+09 | 549.52 | 10-MAY-13:09 | 27.17 | 12.14 |
June | 0.769701E+10 | 13651.32 | 25-JUN-14:31 | 33.43 | 13.43 | 0.431030E+09 | 549.51 | 09-JUN-13:50 | 33.43 | 13.43 |
July | 0.774805E+10 | 17941.26 | 23-JUL-12:52 | 34.00 | 16.01 | 0.401354E+09 | 549.50 | 14-JUL-09:20 | 34.00 | 16.01 |
August | 0.897746E+10 | 18112.34 | 27-AUG-13:12 | 26.00 | 15.04 | 0.449944E+09 | 550.10 | 29-AUG-13:09 | 28.83 | 16.25 |
September | 0.825994E+10 | 19885.90 | 10-SEP-12:41 | 32.25 | 13.24 | 0.395110E+09 | 567.01 | 28-SEP-13:09 | 30.50 | 11.31 |
October | 0.618570E+10 | 18034.51 | 09-OCT-13:22 | 22.00 | 8.88 | 0.376990E+09 | 549.98 | 11-OCT-13:30 | 26.50 | 9.59 |
November | 0.515210E+10 | 19360.32 | 05-NOV-13:42 | 21.00 | 6.39 | 0.376515E+09 | 550.03 | 06-NOV-14:30 | 21.00 | 6.86 |
December | 0.378618E+10 | 18194.21 | 03-DEC-13:02 | 17.33 | 6.34 | 0.352236E+09 | 549.62 | 01-DEC-14:39 | 17.33 | 6.34 |
Annual Sum or Average | 0.701383E+11 | 0.466973E+10 | ||||||||
Minimum of Months | 0.354676E+10 | 8130.18 | 15.83 | 4.65 | 0.341275E+09 | 549.50 | 15.83 | 4.65 | ||
Maximum of Months | 0.897746E+10 | 19885.90 | 34.00 | 16.01 | 0.449944E+09 | 567.01 | 34.00 | 16.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149791E+10 | 4872.91 | 20-JAN-16:00 | 18.00 | 7.49 | 0.207315E+09 | 347.70 | 20-JAN-14:00 | 18.00 | 7.49 |
February | 0.140641E+10 | 5304.56 | 17-FEB-16:30 | 13.50 | 6.66 | 0.188963E+09 | 347.71 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.258088E+10 | 7964.72 | 13-MAR-16:00 | 23.00 | 6.97 | 0.231640E+09 | 347.85 | 10-MAR-14:20 | 23.00 | 6.97 |
April | 0.247497E+10 | 8146.56 | 07-APR-16:00 | 21.00 | 8.12 | 0.207145E+09 | 347.83 | 21-APR-13:00 | 15.00 | 5.55 |
May | 0.415163E+10 | 8820.89 | 31-MAY-16:00 | 28.00 | 14.86 | 0.246680E+09 | 347.86 | 18-MAY-13:20 | 28.00 | 14.86 |
June | 0.649688E+10 | 18432.49 | 25-JUN-16:31 | 32.70 | 13.89 | 0.267942E+09 | 347.86 | 27-JUN-09:20 | 25.53 | 11.25 |
July | 0.593075E+10 | 16320.10 | 02-JUL-16:52 | 28.00 | 12.40 | 0.249079E+09 | 347.86 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.617988E+10 | 18093.97 | 20-AUG-15:41 | 28.00 | 14.08 | 0.277220E+09 | 347.86 | 15-AUG-13:20 | 28.00 | 14.08 |
September | 0.492795E+10 | 18832.57 | 10-SEP-16:41 | 30.78 | 12.29 | 0.237301E+09 | 347.86 | 01-SEP-13:00 | 30.78 | 12.29 |
October | 0.301920E+10 | 8056.64 | 11-OCT-15:30 | 25.00 | 9.04 | 0.217684E+09 | 347.84 | 10-OCT-13:00 | 25.00 | 9.04 |
November | 0.185154E+10 | 5931.01 | 07-NOV-15:30 | 21.50 | 7.27 | 0.209090E+09 | 347.85 | 06-NOV-14:20 | 21.50 | 7.27 |
December | 0.109997E+10 | 3957.48 | 01-DEC-15:30 | 19.50 | 7.14 | 0.195544E+09 | 347.81 | 01-DEC-14:00 | 19.50 | 7.14 |
Annual Sum or Average | 0.416180E+11 | 0.273560E+10 | ||||||||
Minimum of Months | 0.109997E+10 | 3957.48 | 13.50 | 6.66 | 0.188963E+09 | 347.70 | 14.00 | 4.75 | ||
Maximum of Months | 0.649688E+10 | 18832.57 | 32.70 | 14.86 | 0.277220E+09 | 347.86 | 31.00 | 15.59 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 257614.94 | 4293.58 | 06-FEB-07:01 | -9.7 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 1111711.23 | 5005.28 | 26-DEC-07:03 | 6.83 |
Annual Sum or Average | 1369326.16 | |||
Minimum of Months | 0.00 | 0.00 | -9.7 | |
Maximum of Months | 1111711.23 | 5005.28 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.653588E+10 | 22298.56 | 05-JAN-06:13 | -17.0 |
February | 0.639961E+10 | 21839.70 | 13-FEB-05:22 | -11.0 |
March | 0.459793E+10 | 16736.40 | 06-MAR-06:15 | 1.33 |
April | 0.316785E+10 | 20402.75 | 17-APR-05:09 | -8.0 |
May | 0.733668E+09 | 12807.48 | 01-MAY-05:13 | 6.00 |
June | 0.141180E+09 | 7682.60 | 09-JUN-05:03 | 6.97 |
July | 92026790.60 | 7002.65 | 02-JUL-06:42 | 14.67 |
August | 0.117986E+09 | 6037.89 | 19-AUG-05:03 | 13.00 |
September | 0.553169E+09 | 11672.98 | 22-SEP-05:03 | -1.7 |
October | 0.365855E+10 | 19627.84 | 30-OCT-05:07 | -10.0 |
November | 0.478205E+10 | 22603.18 | 30-NOV-06:12 | -12.0 |
December | 0.912291E+10 | 25692.47 | 22-DEC-06:12 | -20.7 |
Annual Sum or Average | 0.399028E+11 | |||
Minimum of Months | 92026790.60 | 6037.89 | -20.7 | |
Maximum of Months | 0.912291E+10 | 25692.47 | 14.67 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171711E+10 | 7034.02 | 02-JAN-07:13 | -2.7 |
February | 0.176973E+10 | 9383.76 | 06-FEB-07:19 | -9.3 |
March | 0.109515E+10 | 9241.72 | 20-MAR-06:12 | 0.00 |
April | 0.944870E+09 | 7907.85 | 03-APR-06:11 | -7.3 |
May | 0.177930E+09 | 4314.75 | 28-MAY-14:02 | 20.00 |
June | 18413083.63 | 3952.35 | 11-JUN-16:12 | 28.53 |
July | 18421429.11 | 3392.15 | 02-JUL-16:52 | 28.00 |
August | 13067455.89 | 4040.80 | 20-AUG-15:01 | 28.00 |
September | 40125504.82 | 5201.79 | 10-SEP-15:21 | 31.90 |
October | 0.770239E+09 | 6559.71 | 30-OCT-06:12 | -10.0 |
November | 0.133017E+10 | 7870.97 | 05-NOV-11:42 | 19.67 |
December | 0.223996E+10 | 10193.13 | 26-DEC-07:15 | 6.67 |
Annual Sum or Average | 0.101352E+11 | |||
Minimum of Months | 13067455.89 | 3392.15 | -10.0 | |
Maximum of Months | 0.223996E+10 | 10193.13 | 31.90 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.653335E+09 | 3455.99 | 02-JAN-08:06 | -3.5 |
February | 0.775680E+09 | 5366.56 | 06-FEB-08:20 | -7.0 |
March | 0.468324E+09 | 4608.17 | 20-MAR-07:10 | 0.17 |
April | 0.383801E+09 | 3626.71 | 17-APR-07:50 | -3.5 |
May | 36528954.01 | 2644.74 | 07-MAY-15:28 | 22.50 |
June | 12710843.17 | 3129.88 | 11-JUN-13:37 | 27.93 |
July | 15120266.88 | 2946.20 | 30-JUL-15:11 | 23.33 |
August | 11045761.97 | 2890.82 | 27-AUG-10:10 | 21.33 |
September | 24036380.92 | 6219.84 | 22-SEP-05:01 | -1.7 |
October | 0.260406E+09 | 6896.41 | 16-OCT-05:01 | 1.00 |
November | 0.369741E+09 | 5070.69 | 05-NOV-13:02 | 21.00 |
December | 0.995285E+09 | 5173.91 | 26-DEC-07:03 | 6.83 |
Annual Sum or Average | 0.400602E+10 | |||
Minimum of Months | 11045761.97 | 2644.74 | -7.0 | |
Maximum of Months | 0.995285E+09 | 6896.41 | 27.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72681903.53 | 15780.93 | 02-JAN-06:01 | -2.8 |
February | 0.160879E+09 | 16907.25 | 06-FEB-06:01 | -10.0 |
March | 74381441.73 | 16255.18 | 20-MAR-05:02 | 0.00 |
April | 53185303.78 | 15240.66 | 17-APR-05:01 | -8.0 |
May | 1740201.05 | 11601.34 | 01-MAY-06:03 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 13250327.73 | 14267.38 | 30-OCT-05:01 | -10.0 |
November | 12452780.61 | 13827.41 | 01-NOV-06:01 | -2.8 |
December | 0.163619E+09 | 17660.44 | 26-DEC-06:11 | 7.00 |
Annual Sum or Average | 0.552190E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.163619E+09 | 17660.44 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125063E+10 | 30158.25 | 02-JAN-05:01 | -2.2 |
February | 0.143584E+10 | 31716.01 | 06-FEB-05:01 | -10.0 |
March | 0.686220E+09 | 31013.45 | 20-MAR-04:01 | 0.83 |
April | 0.633087E+09 | 30349.80 | 17-APR-04:11 | -8.0 |
May | 63616607.95 | 26417.77 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 2770350.45 | 15041.56 | 22-SEP-06:03 | -1.4 |
October | 0.510789E+09 | 29841.60 | 30-OCT-04:01 | -10.0 |
November | 0.751432E+09 | 27161.54 | 27-NOV-06:01 | -6.8 |
December | 0.197671E+10 | 31272.09 | 26-DEC-06:11 | 7.00 |
Annual Sum or Average | 0.731109E+10 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.197671E+10 | 31716.01 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278721E+10 | 13759.73 | 05-JAN-05:11 | -17.0 |
February | 0.303734E+10 | 14593.04 | 13-FEB-04:32 | -11.3 |
March | 0.184122E+10 | 14564.55 | 19-MAR-01:52 | -8.8 |
April | 0.116951E+10 | 14135.80 | 17-APR-04:11 | -8.0 |
May | 0.106087E+09 | 12566.26 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 314531.98 | 1572.66 | 23-AUG-06:03 | 12.50 |
September | 43992990.70 | 11139.45 | 22-SEP-05:01 | -1.7 |
October | 0.126320E+10 | 14026.20 | 30-OCT-04:01 | -10.0 |
November | 0.192006E+10 | 13540.38 | 27-NOV-05:11 | -7.0 |
December | 0.452007E+10 | 15018.39 | 24-DEC-00:32 | -21.3 |
Annual Sum or Average | 0.166890E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.3 | |
Maximum of Months | 0.452007E+10 | 15018.39 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145904E+10 | 9384.21 | 05-JAN-05:11 | -17.0 |
February | 0.164569E+10 | 9926.41 | 13-FEB-03:12 | -12.0 |
March | 0.101648E+10 | 9949.83 | 19-MAR-01:52 | -8.8 |
April | 0.647717E+09 | 9627.30 | 17-APR-04:11 | -8.0 |
May | 38739490.29 | 8548.44 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 18162215.46 | 7549.29 | 22-SEP-05:01 | -1.7 |
October | 0.789327E+09 | 9562.66 | 30-OCT-04:01 | -10.0 |
November | 0.106500E+10 | 9221.13 | 27-NOV-05:11 | -7.0 |
December | 0.256539E+10 | 10290.18 | 24-DEC-00:32 | -21.3 |
Annual Sum or Average | 0.924556E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.3 | |
Maximum of Months | 0.256539E+10 | 10290.18 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158137E+10 | 13861.09 | 05-JAN-05:11 | -17.0 |
February | 0.208744E+10 | 14713.38 | 06-FEB-04:22 | -10.0 |
March | 0.149890E+10 | 14691.24 | 19-MAR-01:52 | -8.8 |
April | 0.106239E+10 | 14297.47 | 17-APR-04:11 | -8.0 |
May | 0.114647E+09 | 12728.00 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 352384.45 | 1761.92 | 23-AUG-06:03 | 12.50 |
September | 35946783.07 | 11202.29 | 22-SEP-05:01 | -1.7 |
October | 0.110685E+10 | 14118.01 | 30-OCT-04:01 | -10.0 |
November | 0.127439E+10 | 13570.11 | 27-NOV-05:11 | -7.0 |
December | 0.293084E+10 | 14969.80 | 24-DEC-00:32 | -21.3 |
Annual Sum or Average | 0.116931E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.3 | |
Maximum of Months | 0.293084E+10 | 14969.80 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158461E+10 | 10271.20 | 05-JAN-05:11 | -17.0 |
February | 0.178946E+10 | 10913.66 | 06-FEB-04:22 | -10.0 |
March | 0.113665E+10 | 10936.13 | 19-MAR-01:52 | -8.8 |
April | 0.748680E+09 | 10625.57 | 17-APR-04:11 | -8.0 |
May | 76946195.77 | 9359.31 | 01-MAY-05:11 | 6.00 |
June | 12598.66 | 42.00 | 10-JUN-06:05 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 639014.84 | 2097.06 | 23-AUG-06:03 | 12.50 |
September | 30241495.88 | 8214.93 | 22-SEP-05:01 | -1.7 |
October | 0.807253E+09 | 10490.86 | 30-OCT-04:01 | -10.0 |
November | 0.115438E+10 | 10048.30 | 27-NOV-05:11 | -7.0 |
December | 0.268762E+10 | 11293.99 | 24-DEC-00:32 | -21.3 |
Annual Sum or Average | 0.100165E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.3 | |
Maximum of Months | 0.268762E+10 | 11293.99 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166307E+10 | 9718.96 | 02-JAN-05:01 | -2.2 |
February | 0.204425E+10 | 10198.67 | 12-FEB-05:31 | -19.3 |
March | 0.114766E+10 | 9786.79 | 20-MAR-04:01 | 0.83 |
April | 0.614737E+09 | 9728.51 | 03-APR-04:01 | -8.0 |
May | 43172484.83 | 8182.77 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 686750.99 | 4144.32 | 22-SEP-06:03 | -1.4 |
October | 0.313444E+09 | 8772.30 | 30-OCT-04:01 | -10.0 |
November | 0.539653E+09 | 8796.64 | 30-NOV-05:01 | -12.8 |
December | 0.201625E+10 | 10223.86 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.838292E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.204425E+10 | 10223.86 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.694540E+09 | 6813.58 | 06-JAN-05:01 | -7.8 |
February | 0.936995E+09 | 7066.97 | 07-FEB-05:01 | -7.0 |
March | 0.524597E+09 | 7064.17 | 20-MAR-04:01 | 0.83 |
April | 0.272326E+09 | 7006.24 | 03-APR-04:01 | -8.0 |
May | 12200990.13 | 5780.53 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 233509.77 | 1556.73 | 22-SEP-06:03 | -1.4 |
October | 0.193904E+09 | 6127.47 | 31-OCT-05:01 | -8.2 |
November | 0.272070E+09 | 6298.16 | 30-NOV-05:01 | -12.8 |
December | 0.100774E+10 | 7333.64 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.391460E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.100774E+10 | 7333.64 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210654E+10 | 12403.18 | 05-JAN-07:10 | -17.0 |
February | 0.252563E+10 | 11814.71 | 06-FEB-07:50 | -8.3 |
March | 0.223340E+10 | 10827.20 | 02-MAR-07:10 | -8.7 |
April | 0.161761E+10 | 10982.09 | 17-APR-06:50 | -6.3 |
May | 0.580136E+09 | 9229.73 | 02-MAY-06:10 | 0.17 |
June | 11829727.35 | 4751.84 | 09-JUN-06:10 | 9.37 |
July | 8617542.78 | 4504.25 | 03-JUL-06:07 | 11.00 |
August | 3121587.49 | 3041.52 | 23-AUG-06:07 | 12.50 |
September | 90081873.76 | 8532.67 | 22-SEP-06:10 | -1.4 |
October | 0.143407E+10 | 11154.67 | 30-OCT-06:10 | -10.0 |
November | 0.157777E+10 | 11353.24 | 30-NOV-07:10 | -11.3 |
December | 0.279728E+10 | 13352.93 | 21-DEC-08:00 | -20.0 |
Annual Sum or Average | 0.149861E+11 | |||
Minimum of Months | 3121587.49 | 3041.52 | -20.0 | |
Maximum of Months | 0.279728E+10 | 13352.93 | 12.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.740773E+09 | 7080.19 | 06-JAN-05:01 | -7.8 |
February | 0.963448E+09 | 7467.46 | 07-FEB-05:01 | -7.0 |
March | 0.577767E+09 | 7466.24 | 20-MAR-04:01 | 0.83 |
April | 0.329753E+09 | 7339.92 | 17-APR-04:01 | -8.0 |
May | 23780317.90 | 6132.56 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 678206.00 | 3810.82 | 22-SEP-06:03 | -1.4 |
October | 0.194083E+09 | 6396.36 | 31-OCT-05:01 | -8.2 |
November | 0.264220E+09 | 6374.93 | 02-NOV-05:01 | -9.0 |
December | 0.103446E+10 | 7722.27 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.412896E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.103446E+10 | 7722.27 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107334E+10 | 9847.95 | 06-JAN-05:01 | -7.8 |
February | 0.134489E+10 | 10601.58 | 12-FEB-05:31 | -19.3 |
March | 0.648077E+09 | 10124.47 | 20-MAR-04:01 | 0.83 |
April | 0.374143E+09 | 10219.70 | 17-APR-04:11 | -8.0 |
May | 20828232.68 | 8344.92 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 3492217.32 | 6959.12 | 22-SEP-06:03 | -1.4 |
October | 0.443372E+09 | 10128.98 | 30-OCT-04:01 | -10.0 |
November | 0.673337E+09 | 9705.04 | 30-NOV-05:01 | -12.8 |
December | 0.215464E+10 | 10810.97 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.673613E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.215464E+10 | 10810.97 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548804E+09 | 7755.35 | 06-JAN-05:01 | -7.8 |
February | 0.735419E+09 | 8382.10 | 12-FEB-05:31 | -19.3 |
March | 0.357623E+09 | 7972.77 | 20-MAR-04:01 | 0.83 |
April | 0.204596E+09 | 8085.33 | 03-APR-04:01 | -8.0 |
May | 7221443.41 | 6410.50 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 956091.80 | 4128.50 | 22-SEP-06:03 | -1.4 |
October | 0.304157E+09 | 7997.38 | 30-OCT-04:01 | -10.0 |
November | 0.395399E+09 | 7664.73 | 30-NOV-05:01 | -12.8 |
December | 0.121928E+10 | 8595.54 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.377345E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.121928E+10 | 8595.54 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.529516E+09 | 9964.55 | 06-JAN-05:01 | -7.8 |
February | 0.847270E+09 | 10499.83 | 13-FEB-05:01 | -11.0 |
March | 0.499021E+09 | 10388.11 | 20-MAR-04:01 | 0.83 |
April | 0.339832E+09 | 10495.52 | 17-APR-04:11 | -8.0 |
May | 23635954.68 | 8580.74 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 2845076.51 | 6965.55 | 22-SEP-06:03 | -1.4 |
October | 0.401351E+09 | 10273.67 | 30-OCT-04:01 | -10.0 |
November | 0.415613E+09 | 9806.96 | 30-NOV-05:01 | -12.8 |
December | 0.121749E+10 | 11077.43 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.427657E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.121749E+10 | 11077.43 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.592958E+09 | 8001.83 | 06-JAN-05:01 | -7.8 |
February | 0.777003E+09 | 8663.00 | 12-FEB-05:31 | -19.3 |
March | 0.406621E+09 | 8311.03 | 20-MAR-04:01 | 0.83 |
April | 0.250336E+09 | 8422.43 | 17-APR-04:11 | -8.0 |
May | 18095089.63 | 6680.67 | 01-MAY-05:11 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 3171364.91 | 4612.01 | 22-SEP-06:03 | -1.4 |
October | 0.296440E+09 | 8327.86 | 30-OCT-04:01 | -10.0 |
November | 0.409995E+09 | 7914.02 | 30-NOV-05:01 | -12.8 |
December | 0.126287E+10 | 8942.07 | 24-DEC-07:01 | -19.3 |
Annual Sum or Average | 0.401749E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.3 | |
Maximum of Months | 0.126287E+10 | 8942.07 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512955E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827485E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.24 | 0.886890E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923517E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2858239.49 | 0.481492E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54719545.81 | 0.207861E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74078200.81 | 0.206490E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37662810.27 | 0.203865E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24951857.49 | 0.295771E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 583192.18 | 0.658623E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63575.03 | 0.585230E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21530.71 | 0.112120E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194942E+09 | 0.691138E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203865E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74078200.81 | 0.112120E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348234E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560487E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605544E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630003E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1653673.99 | 0.329850E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34387992.61 | 0.143297E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45216571.66 | 0.145532E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22819381.17 | 0.142419E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14091450.43 | 0.207775E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 225207.39 | 0.453537E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 933.80 | 0.396028E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12989.92 | 0.752223E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118408E+09 | 0.471493E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142419E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45216571.66 | 0.752223E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556895E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875365E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932539E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948661E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2498587.94 | 0.491407E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53048872.15 | 0.207244E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70539159.87 | 0.208023E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33554516.23 | 0.214103E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17559366.28 | 0.319637E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 308954.78 | 0.708464E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627999E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117736E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177509E+09 | 0.726769E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207244E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70539159.87 | 0.117736E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349763E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562971E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1886.17 | 0.605946E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626354E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1989542.34 | 0.331202E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34874211.82 | 0.144095E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46728964.00 | 0.141420E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24716535.69 | 0.143239E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14378768.35 | 0.206868E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 329128.87 | 0.451363E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4144.75 | 0.398034E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754969E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123023E+09 | 0.471622E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141420E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46728964.00 | 0.754969E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287073E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453135E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30849.15 | 0.481776E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510652E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1909280.53 | 0.254557E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30146840.19 | 0.110716E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40840182.57 | 0.109848E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20182543.81 | 0.114037E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12571068.08 | 0.177014E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259865.18 | 0.389942E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4913.82 | 0.339013E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11931.78 | 0.630287E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105957E+09 | 0.385805E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109848E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40840182.57 | 0.630287E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197452E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310685E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 0.333924E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354607E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 963907.01 | 0.180214E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18541333.54 | 80017147.07 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23997556.68 | 80903214.68 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12008060.25 | 83608052.39 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7147014.42 | 0.128109E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115088.34 | 0.272786E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231843E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3087.61 | 0.427684E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62776049.52 | 0.268183E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80017147.07 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23997556.68 | 0.427684E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438835E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443537E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.62 | 0.388701E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299507E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55790416.73 | 0.181166E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765420E+09 | 0.446179E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621950E+09 | 0.422167E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674699E+09 | 0.628758E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293099E+09 | 0.103532E+10 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7048037.90 | 0.349126E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423168E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512334E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241801E+10 | 0.328961E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422167E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765420E+09 | 0.512334E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198333E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311528E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2863.17 | 0.333275E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351976E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1166902.58 | 0.179446E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18179525.21 | 81400682.72 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24249528.07 | 78637477.99 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12811375.31 | 84553290.46 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6986548.75 | 0.127899E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129993.25 | 0.271445E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232883E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428859E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63526736.33 | 0.268024E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78637477.99 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24249528.07 | 0.428859E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456084E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722448E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 954.57 | 0.776649E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824016E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2113366.53 | 0.431161E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44492669.57 | 0.187778E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60045803.80 | 0.186210E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30145387.36 | 0.185851E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19331224.76 | 0.273711E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 338409.88 | 0.596074E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5801.32 | 0.522257E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16988.51 | 0.976366E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156491E+09 | 0.613860E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185851E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60045803.80 | 0.976366E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311065E+09 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491004E+09 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530382E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561365E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1281664.48 | 0.292383E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29045923.14 | 0.126475E+09 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38603657.34 | 0.128148E+09 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18942112.67 | 0.126548E+09 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12001064.17 | 0.188032E+09 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167072.68 | 0.407643E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353420E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658043E+09 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100041E+09 | 0.417451E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126475E+09 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38603657.34 | 0.658043E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498076E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766823E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817664E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845711E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1918836.04 | 0.438418E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43168604.38 | 0.186863E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57030995.01 | 0.187286E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27084837.81 | 0.194015E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14047170.37 | 0.292429E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261356.74 | 0.637149E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559436E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103556E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143512E+09 | 0.645943E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186863E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57030995.01 | 0.103556E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310742E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490604E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4030.98 | 0.528264E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555756E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1561187.72 | 0.293171E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28625520.89 | 0.128656E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38533039.25 | 0.125928E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20220914.47 | 0.128607E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11671404.36 | 0.188122E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 266693.76 | 0.404868E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 | 0.353765E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658107E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100883E+09 | 0.416659E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125928E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38533039.25 | 0.658107E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664844E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103853E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112829E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119707E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1932654.42 | 0.607897E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48344698.40 | 0.263902E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65943127.79 | 0.261545E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30768980.03 | 0.268040E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16967715.90 | 0.407494E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184237.68 | 0.885103E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762376E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140947E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164141E+09 | 0.889457E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261545E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65943127.79 | 0.140947E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808137E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127845E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138902E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146773E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2597274.68 | 0.757687E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63375238.80 | 0.332606E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86567876.10 | 0.329465E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40670306.63 | 0.332947E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23926912.51 | 0.496045E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294606.05 | 0.107062E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924893E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171489E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217432E+09 | 0.109025E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329465E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86567876.10 | 0.171489E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764516E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123279E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134383E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140302E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945327.75 | 0.741129E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48426110.97 | 0.297313E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63384455.40 | 0.296806E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29221327.65 | 0.301030E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14762757.22 | 0.438459E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39244.67 | 0.994569E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871620E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163977E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156779E+09 | 0.103248E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296806E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63384455.40 | 0.163977E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1008.50 | 12-JAN-22:02 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1266.06 | 05-FEB-22:52 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 14-MAR-13:00 | 2881.79 | 19-MAR-06:53 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1857.35 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 17-MAY-14:50 | 967.83 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.57 | 25-JUN-17:32 | 631.70 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.00 | 16-JUL-11:52 | 585.58 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.90 | 06-AUG-16:00 | 749.86 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.25 | 10-SEP-15:00 | 668.54 | 21-SEP-23:30 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 11-OCT-14:00 | 1469.08 | 29-OCT-19:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.80 | 05-NOV-14:40 | 1599.38 | 01-NOV-04:09 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 02-DEC-15:00 | 2395.42 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.58 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 538.00 | 2881.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 672.10 | 12-JAN-22:02 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 843.47 | 05-FEB-22:52 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1921.23 | 19-MAR-06:57 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1238.18 | 15-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 | 17-MAY-14:50 | 641.75 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.02 | 25-JUN-18:10 | 419.74 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.47 | 16-JUL-12:10 | 418.11 | 02-JUL-08:40 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.48 | 06-AUG-16:00 | 510.90 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.74 | 10-SEP-15:00 | 446.07 | 21-SEP-23:30 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-OCT-14:00 | 979.37 | 29-OCT-19:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 05-NOV-14:40 | 1066.21 | 01-NOV-04:10 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 02-DEC-15:00 | 1596.89 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.11 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 336.47 | 1921.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1013.05 | 12-JAN-22:02 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1286.34 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2881.88 | 19-MAR-07:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1857.49 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 | 17-MAY-14:50 | 976.24 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 402.56 | 25-JUN-18:10 | 627.67 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 519.25 | 16-JUL-11:52 | 589.44 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.94 | 06-AUG-16:00 | 823.55 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.32 | 10-SEP-14:58 | 674.38 | 21-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 | 11-OCT-14:00 | 1469.29 | 29-OCT-19:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1599.39 | 01-NOV-04:10 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2395.47 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.44 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 519.25 | 2881.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 673.11 | 12-JAN-22:02 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 843.11 | 05-FEB-22:52 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 14-MAR-13:00 | 1921.27 | 19-MAR-06:53 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1238.15 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 | 17-MAY-14:50 | 656.32 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.12 | 25-JUN-17:25 | 442.63 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.00 | 16-JUL-11:52 | 407.82 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.22 | 20-AUG-10:00 | 543.85 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.04 | 10-SEP-13:00 | 441.69 | 21-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 11-OCT-14:00 | 979.52 | 29-OCT-19:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 | 05-NOV-12:00 | 1066.28 | 01-NOV-04:09 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1596.91 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.82 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 378.00 | 1921.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 571.81 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 685.89 | 05-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 14-MAR-13:00 | 1517.22 | 19-MAR-06:53 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 994.78 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 06-MAY-17:02 | 556.52 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.34 | 25-JUN-17:50 | 344.14 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.82 | 16-JUL-12:00 | 319.23 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.25 | 06-AUG-16:10 | 386.95 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.04 | 10-SEP-14:41 | 403.93 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 11-OCT-14:00 | 896.60 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 05-NOV-14:30 | 866.42 | 01-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 02-DEC-15:00 | 1308.51 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.23 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 313.82 | 1517.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 387.52 | 13-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 470.37 | 23-FEB-24:00 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 1010.98 | 19-MAR-06:53 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 671.76 | 15-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 | 17-MAY-14:50 | 375.70 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.97 | 25-JUN-17:50 | 240.47 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.90 | 16-JUL-12:00 | 226.27 | 03-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.11 | 06-AUG-16:10 | 276.48 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.14 | 10-SEP-14:41 | 272.08 | 22-SEP-02:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 11-OCT-14:00 | 609.69 | 29-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 574.88 | 01-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 02-DEC-15:00 | 867.16 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.27 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 197.90 | 1010.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 27265.06 | 05-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 21478.59 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 14-MAR-13:00 | 20659.34 | 02-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 19871.12 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2552.43 | 31-MAY-16:10 | 13837.28 | 02-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9250.47 | 26-JUN-16:10 | 8190.97 | 09-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7572.40 | 17-JUL-12:00 | 7024.51 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8100.96 | 16-AUG-16:10 | 6711.64 | 17-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4478.54 | 12-SEP-16:10 | 15277.36 | 22-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 666.70 | 10-OCT-17:00 | 21824.41 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 23522.87 | 29-NOV-17:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 32564.11 | 21-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6711.64 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9250.47 | 32564.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 390.23 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 473.86 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 | 14-MAR-13:00 | 1009.66 | 19-MAR-06:53 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 662.02 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 | 17-MAY-14:50 | 385.45 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.65 | 25-JUN-17:44 | 252.08 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.67 | 16-JUL-12:00 | 236.13 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.32 | 06-AUG-16:10 | 302.97 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.18 | 10-SEP-12:52 | 268.04 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 11-OCT-14:00 | 601.20 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 573.54 | 01-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 874.01 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.13 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 218.67 | 1009.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 899.35 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1100.66 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 14-MAR-13:00 | 2396.94 | 19-MAR-07:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1546.89 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 17-MAY-14:50 | 893.96 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.57 | 25-JUN-18:00 | 556.52 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.86 | 16-JUL-12:00 | 518.02 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.65 | 06-AUG-11:52 | 637.18 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.78 | 10-SEP-14:50 | 607.96 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | 11-OCT-14:00 | 1327.49 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 05-NOV-14:30 | 1333.85 | 01-NOV-04:04 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 02-DEC-15:00 | 2016.68 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.02 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 456.86 | 2396.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 599.11 | 13-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 738.31 | 23-FEB-24:00 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1597.98 | 19-MAR-06:57 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1027.13 | 15-APR-05:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 17-MAY-14:50 | 593.35 | 03-MAY-03:00 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.88 | 25-JUN-18:00 | 367.66 | 08-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.31 | 16-JUL-12:00 | 369.21 | 02-JUL-08:50 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.53 | 06-AUG-12:00 | 429.78 | 27-AUG-18:00 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.96 | 10-SEP-14:50 | 403.71 | 22-SEP-02:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 | 11-OCT-14:10 | 887.85 | 29-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 886.44 | 01-NOV-04:07 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1332.75 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.66 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 315.31 | 1597.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 929.57 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1150.52 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2396.93 | 19-MAR-06:57 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1557.27 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 17-MAY-14:50 | 902.01 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.74 | 25-JUN-18:00 | 553.64 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.38 | 16-JUL-12:00 | 521.52 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.22 | 02-AUG-16:00 | 700.60 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.67 | 10-SEP-14:46 | 609.98 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 | 11-OCT-14:00 | 1358.55 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1330.41 | 01-NOV-04:04 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2037.33 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.52 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 445.38 | 2396.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 601.21 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 747.35 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 14-MAR-13:00 | 1597.94 | 19-MAR-07:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1023.00 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 17-MAY-14:50 | 604.33 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.04 | 25-JUN-17:54 | 388.41 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.66 | 16-JUL-12:00 | 359.45 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.72 | 06-AUG-11:52 | 460.66 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.59 | 04-SEP-12:00 | 399.89 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 11-OCT-14:00 | 880.01 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 05-NOV-12:30 | 886.48 | 01-NOV-04:07 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1343.48 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.45 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 343.66 | 1597.94 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1362.82 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1613.57 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3390.03 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2313.92 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.31 | 17-MAY-14:40 | 1320.74 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.40 | 25-JUN-18:00 | 772.18 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.92 | 16-JUL-12:00 | 728.54 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.19 | 06-AUG-12:00 | 879.79 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.65 | 10-SEP-14:56 | 887.72 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 11-OCT-14:00 | 1997.27 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1953.60 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2864.98 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.54 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.92 | 3390.03 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1662.33 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2006.83 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4140.89 | 19-MAR-06:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2852.70 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.61 | 17-MAY-14:40 | 1629.93 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.32 | 25-JUN-18:00 | 979.52 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.51 | 16-JUL-12:00 | 923.26 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.97 | 06-AUG-12:00 | 1082.49 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.34 | 10-SEP-15:00 | 1104.14 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 | 11-OCT-14:00 | 2377.56 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2341.07 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3578.34 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 923.26 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.51 | 4140.89 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1450.34 | 12-JAN-22:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1922.27 | 19-FEB-17:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4150.40 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2689.12 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.14 | 17-MAY-13:00 | 1333.72 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.02 | 25-JUN-17:50 | 869.06 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.92 | 16-JUL-11:52 | 816.49 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.45 | 02-AUG-16:00 | 1236.61 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.51 | 10-SEP-15:00 | 974.20 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 11-OCT-14:00 | 2160.54 | 29-OCT-19:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2215.11 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3603.67 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.49 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.92 | 4150.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25261.10 | 26-JAN-06:01 | 4446.85 | 7591.59 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18773.76 | 24-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22602.68 | 15-MAR-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25784.62 | 22-APR-05:02 | 3176.32 | 5422.56 | 38671.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25834.18 | 12-MAY-05:03 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41606.29 | 28-JUN-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42293.94 | 10-JUL-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44627.44 | 17-AUG-06:02 | 6352.64 | 16267.69 | 52375.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48062.84 | 22-SEP-05:01 | 4446.85 | 7591.59 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44536.65 | 17-OCT-05:01 | 4446.85 | 7591.59 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21743.32 | 08-NOV-16:30 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18487.37 | 15-DEC-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18487.37 | 1905.79 | 3253.54 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48062.84 | 6352.64 | 16267.69 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5987.65 | 20-JAN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 |
February | 6588.61 | 18-FEB-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 |
March | 10995.96 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.46 |
April | 10180.10 | 21-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.60 |
May | 14443.42 | 31-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.57 | 0.00 |
June | 19293.37 | 26-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 | 0.00 |
July | 16750.34 | 07-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 0.00 |
August | 19000.15 | 16-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.39 | 0.00 |
September | 14652.04 | 12-SEP-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 0.00 |
October | 11129.74 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 | 0.00 |
November | 6635.35 | 09-NOV-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 |
December | 4633.10 | 01-DEC-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4633.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19293.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.39 | 156.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5202.05 | 05-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.26 |
February | 5395.07 | 12-FEB-05:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1744.26 |
March | 4517.08 | 18-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.64 |
April | 4299.79 | 15-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.30 |
May | 2988.23 | 18-MAY-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.40 |
June | 5437.16 | 26-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.94 | 0.00 |
July | 5692.31 | 17-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.43 | 0.00 |
August | 5056.60 | 11-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.88 | 0.00 |
September | 4404.83 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.61 | 0.00 |
October | 3299.06 | 28-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.35 |
November | 4761.28 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1035.09 |
December | 5328.03 | 21-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1528.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2988.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5692.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.43 | 1744.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5075.86 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.76 |
February | 4245.62 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.09 |
March | 4571.62 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.02 |
April | 5371.28 | 26-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.42 |
May | 4344.03 | 02-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.14 |
June | 5449.36 | 26-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.41 | 0.00 |
July | 5790.93 | 17-JUL-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.15 | 0.00 |
August | 5569.89 | 16-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.80 | 0.00 |
September | 5323.39 | 12-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.33 | 0.00 |
October | 4068.10 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
November | 3550.60 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.94 |
December | 5408.56 | 21-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3550.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5790.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.15 | 1240.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11473.94 | 20-JAN-16:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10745.49 | 24-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15991.75 | 15-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14584.22 | 21-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17331.04 | 18-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27868.46 | 27-JUN-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31846.87 | 17-JUL-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26224.45 | 21-AUG-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21595.23 | 11-SEP-05:13 | 1905.79 | 3253.54 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17060.92 | 11-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13880.01 | 08-NOV-16:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10039.77 | 15-DEC-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10039.77 | 1905.79 | 3253.54 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31846.87 | 6035.01 | 9760.61 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 10505.76 | 20-JAN-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9573.32 | 17-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17469.48 | 15-MAR-15:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16936.34 | 21-APR-14:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19884.21 | 18-MAY-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24423.35 | 26-JUN-15:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24330.56 | 17-JUL-14:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23740.08 | 16-AUG-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21290.98 | 12-SEP-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17708.19 | 11-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12154.28 | 08-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9106.78 | 14-DEC-16:10 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9106.78 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24423.35 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3285.02 | 20-JAN-15:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 |
February | 3101.98 | 27-FEB-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.71 |
March | 4039.62 | 14-MAR-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 |
April | 4080.48 | 20-APR-13:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 |
May | 6492.78 | 17-MAY-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 0.00 |
June | 8696.45 | 26-JUN-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.39 | 0.00 |
July | 8971.72 | 17-JUL-13:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 112.75 | 0.00 |
August | 7981.59 | 16-AUG-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 84.03 | 0.00 |
September | 7116.35 | 11-SEP-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 0.00 |
October | 4422.53 | 11-OCT-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.63 | 0.00 |
November | 3627.26 | 09-NOV-14:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.75 |
December | 3020.35 | 01-DEC-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3020.35 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8971.72 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.39 | 153.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2715.77 | 20-JAN-10:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.66 |
February | 2809.30 | 27-FEB-09:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.45 |
March | 6081.45 | 15-MAR-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 |
April | 6569.14 | 21-APR-09:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.32 |
May | 7457.23 | 16-MAY-08:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 |
June | 13466.69 | 11-JUN-08:52 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.19 |
July | 16291.36 | 09-JUL-09:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 |
August | 11865.46 | 20-AUG-09:12 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 |
September | 7684.22 | 08-SEP-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
October | 5179.28 | 11-OCT-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 |
November | 2931.98 | 07-NOV-09:20 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.03 |
December | 2275.12 | 01-DEC-09:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2275.12 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16291.36 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 126.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13356.95 | 20-JAN-13:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 |
February | 11132.53 | 17-FEB-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.96 |
March | 13102.55 | 15-MAR-13:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 |
April | 9512.66 | 21-APR-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.16 |
May | 8844.19 | 16-MAY-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.57 | 0.00 |
June | 10820.36 | 30-JUN-12:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 107.81 | 0.00 |
July | 17670.26 | 09-JUL-13:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 213.13 | 0.00 |
August | 14127.22 | 31-AUG-12:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 | 0.00 |
September | 23328.48 | 17-SEP-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 |
October | 17204.37 | 08-OCT-12:52 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.26 |
November | 16393.47 | 05-NOV-13:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 |
December | 11912.88 | 03-DEC-13:42 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8844.19 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23328.48 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 213.13 | 351.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4915.39 | 20-JAN-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 |
February | 5216.85 | 17-FEB-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.59 |
March | 8239.16 | 13-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 |
April | 8565.72 | 07-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.03 |
May | 9393.40 | 31-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 0.00 |
June | 19916.28 | 04-JUN-15:31 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 61.75 | 0.00 |
July | 21059.00 | 02-JUL-16:41 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.68 |
August | 14498.69 | 26-AUG-17:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 32.98 | 0.00 |
September | 18811.91 | 17-SEP-16:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 |
October | 8213.08 | 11-OCT-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.36 | 0.00 |
November | 5890.02 | 07-NOV-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 |
December | 3837.58 | 01-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3837.58 | 254.33 | 434.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21059.00 | 805.38 | 1302.56 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 61.75 | 45.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2248.60 | 20-JAN-15:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 |
February | 2131.80 | 27-FEB-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.22 |
March | 2641.12 | 14-MAR-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
April | 2643.01 | 20-APR-13:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 |
May | 3876.63 | 17-MAY-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 | 0.00 |
June | 6011.37 | 14-JUN-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 66.89 | 0.00 |
July | 6671.48 | 17-JUL-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.64 | 0.00 |
August | 6159.59 | 18-AUG-14:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 | 0.00 |
September | 6233.88 | 11-SEP-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.81 | 0.00 |
October | 3780.10 | 11-OCT-13:50 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 0.00 |
November | 3073.90 | 05-NOV-14:22 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
December | 2295.58 | 04-DEC-15:02 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2131.80 | 401.76 | 685.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6671.48 | 5088.93 | 8230.49 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 66.89 | 77.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2124.56 | 20-JAN-10:05 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 |
February | 2268.35 | 27-FEB-09:10 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.04 |
March | 4019.89 | 15-MAR-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 |
April | 4249.14 | 21-APR-09:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 |
May | 5007.98 | 16-MAY-09:00 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
June | 7553.73 | 25-JUN-10:22 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 50.24 | 0.00 |
July | 13140.18 | 16-JUL-08:31 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.22 | 0.00 |
August | 13292.08 | 20-AUG-09:41 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 | 0.00 |
September | 6913.78 | 08-SEP-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 | 0.00 |
October | 4977.20 | 11-OCT-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 |
November | 3157.28 | 07-NOV-08:15 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 |
December | 2156.16 | 03-DEC-10:32 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2124.56 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13292.08 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 59.22 | 104.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9720.76 | 20-JAN-14:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.33 |
February | 9809.92 | 27-FEB-13:05 | 5088.93 | 8230.49 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014.64 |
March | 9560.46 | 14-MAR-13:05 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.88 |
April | 5383.02 | 20-APR-12:10 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.70 |
May | 6608.35 | 16-MAY-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1992.91 | 0.00 |
June | 14390.70 | 26-JUN-16:10 | 401.76 | 1143.12 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9250.47 | 0.00 |
July | 14044.56 | 17-JUL-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7572.40 | 0.00 |
August | 14515.79 | 16-AUG-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6655.80 | 0.00 |
September | 17470.42 | 17-SEP-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 |
October | 18380.24 | 09-OCT-13:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.89 |
November | 17847.47 | 05-NOV-13:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 |
December | 8959.13 | 15-DEC-13:06 | 6361.16 | 10288.11 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5383.02 | 401.76 | 685.87 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18380.24 | 6361.16 | 10288.11 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9250.47 | 1196.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3452.90 | 20-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
February | 3646.20 | 17-FEB-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 |
March | 5138.29 | 13-MAR-16:50 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 |
April | 4859.46 | 07-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.54 |
May | 5780.95 | 31-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 0.00 |
June | 14580.32 | 25-JUN-16:21 | 381.49 | 651.28 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 | 0.00 |
July | 14262.48 | 02-JUL-17:11 | 0.00 | 578.92 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 | 0.00 |
August | 14332.19 | 20-AUG-15:41 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 | 0.00 |
September | 15342.09 | 10-SEP-17:11 | 0.00 | 506.55 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 18.07 | 0.00 |
October | 14191.55 | 09-OCT-16:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.35 |
November | 5145.40 | 07-NOV-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
December | 3026.99 | 01-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3026.99 | 0.00 | 434.19 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15342.09 | 805.38 | 1302.56 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 | 40.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3203.88 | 20-JAN-13:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
February | 3035.33 | 26-FEB-13:12 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.03 |
March | 3691.73 | 14-MAR-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 |
April | 3551.96 | 20-APR-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
May | 6060.24 | 17-MAY-13:30 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.04 | 0.00 |
June | 7638.99 | 26-JUN-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 105.39 | 0.00 |
July | 12143.22 | 16-JUL-13:52 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 335.35 | 0.00 |
August | 7185.28 | 18-AUG-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 | 0.00 |
September | 6796.18 | 11-SEP-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 57.32 | 0.00 |
October | 4278.18 | 11-OCT-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 0.00 |
November | 3401.29 | 07-NOV-13:30 | 2544.47 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
December | 2897.67 | 03-DEC-13:42 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2897.67 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12143.22 | 2544.47 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 335.35 | 119.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4297.48 | 20-JAN-13:02 | 4027.14 | 6513.23 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 |
February | 4724.15 | 23-FEB-13:01 | 5638.00 | 9118.52 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.18 |
March | 6854.52 | 14-MAR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 |
April | 7130.52 | 21-APR-08:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.54 |
May | 7877.08 | 16-MAY-08:30 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 |
June | 12443.58 | 25-JUN-09:52 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 | 0.00 |
July | 16941.04 | 16-JUL-08:31 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.84 | 0.00 |
August | 17101.02 | 20-AUG-09:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.88 |
September | 9046.68 | 10-SEP-09:22 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 0.00 |
October | 6374.63 | 11-OCT-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 |
November | 4195.01 | 07-NOV-09:10 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 |
December | 3596.09 | 15-DEC-11:02 | 4027.14 | 6513.23 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3596.09 | 254.35 | 434.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17101.02 | 5638.00 | 9118.52 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 | 109.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13569.69 | 20-JAN-13:04 | 6361.16 | 10288.11 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
February | 18357.36 | 26-FEB-13:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.62 |
March | 12845.66 | 15-MAR-13:10 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 |
April | 8967.59 | 21-APR-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.86 |
May | 8130.18 | 16-MAY-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 24.07 | 0.00 |
June | 13651.32 | 25-JUN-14:31 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 0.00 |
July | 17941.26 | 23-JUL-12:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 110.49 | 0.00 |
August | 18112.34 | 27-AUG-13:12 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.80 |
September | 19885.90 | 10-SEP-12:41 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 76.09 | 0.00 |
October | 18034.51 | 09-OCT-13:22 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.94 |
November | 19360.32 | 05-NOV-13:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 |
December | 18194.21 | 03-DEC-13:02 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8130.18 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19885.90 | 6361.16 | 10288.11 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 110.49 | 346.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4872.91 | 20-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.57 |
February | 5304.56 | 17-FEB-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 |
March | 7964.72 | 13-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
April | 8146.56 | 07-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 |
May | 8820.89 | 31-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 0.00 |
June | 18432.49 | 25-JUN-16:31 | 423.88 | 723.64 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 94.60 | 0.00 |
July | 16320.10 | 02-JUL-16:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 55.18 | 0.00 |
August | 18093.97 | 20-AUG-15:41 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 |
September | 18832.57 | 10-SEP-16:41 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 | 0.00 |
October | 8056.64 | 11-OCT-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 0.00 |
November | 5931.01 | 07-NOV-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
December | 3957.48 | 01-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3957.48 | 254.33 | 434.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18832.57 | 805.38 | 1302.56 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 94.60 | 37.17 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.154834E+12 | 131174.52 | 20-JAN-13:09 | 0.708094E+11 | 251366.60 | 05-JAN-07:10 |
February | 0.139093E+12 | 112411.73 | 17-FEB-13:00 | 0.730903E+11 | 259409.98 | 06-FEB-07:19 |
March | 0.161247E+12 | 146624.89 | 13-MAR-15:20 | 0.516855E+11 | 241860.21 | 20-MAR-05:10 |
April | 0.145618E+12 | 134355.93 | 07-APR-15:50 | 0.354975E+11 | 237156.71 | 17-APR-06:10 |
May | 0.163980E+12 | 163005.77 | 31-MAY-15:50 | 0.600152E+10 | 154288.09 | 01-MAY-05:19 |
June | 0.206400E+12 | 224294.16 | 26-JUN-15:09 | 75036694.43 | 22209.47 | 09-JUN-06:10 |
July | 0.202119E+12 | 206763.47 | 17-JUL-14:09 | 41925196.09 | 10983.82 | 03-JUL-06:10 |
August | 0.212907E+12 | 216561.63 | 16-AUG-15:30 | 63348914.40 | 16167.86 | 23-AUG-06:10 |
September | 0.182565E+12 | 191378.84 | 12-SEP-15:00 | 0.180369E+10 | 117839.14 | 22-SEP-06:10 |
October | 0.158547E+12 | 164814.52 | 11-OCT-15:30 | 0.344111E+11 | 236019.25 | 30-OCT-06:10 |
November | 0.151797E+12 | 139008.90 | 07-NOV-15:09 | 0.502165E+11 | 225187.73 | 30-NOV-07:10 |
December | 0.153815E+12 | 129589.00 | 01-DEC-13:00 | 0.102405E+12 | 284245.59 | 23-DEC-07:19 |
Annual Sum or Average | 0.203292E+13 | 0.426101E+12 | ||||
Minimum of Months | 0.139093E+12 | 112411.73 | 41925196.09 | 10983.82 | ||
Maximum of Months | 0.212907E+12 | 224294.16 | 0.102405E+12 | 284245.59 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.242222E+11 | 0.613996E+11 | 0.230900E+10 | 0.133327E+11 | 0.361050E+09 | 0.00 | 0.857917E+09 | 0.00 | 0.00 | 0.00 | 0.510359E+10 | 0.00 |
February | 0.428574E+11 | 0.203939E+11 | 0.556056E+11 | 0.209511E+10 | 0.127472E+11 | 0.380922E+09 | 0.00 | 0.321979E+09 | 0.00 | 0.00 | 0.00 | 0.469131E+10 | 0.00 |
March | 0.509265E+11 | 0.204839E+11 | 0.635880E+11 | 0.240664E+10 | 0.152813E+11 | 0.268445E+09 | 0.00 | 0.283419E+10 | 0.00 | 0.00 | 0.00 | 0.545784E+10 | 0.00 |
April | 0.454877E+11 | 0.177005E+11 | 0.594055E+11 | 0.224272E+10 | 0.130019E+11 | 0.183405E+09 | 0.00 | 0.285101E+10 | 0.00 | 0.00 | 0.00 | 0.474553E+10 | 0.00 |
May | 0.490872E+11 | 0.164484E+11 | 0.624938E+11 | 0.235782E+10 | 0.160476E+11 | 44679208.60 | 0.00 | 0.126851E+11 | 0.00 | 0.00 | 0.00 | 0.481549E+10 | 0.00 |
June | 0.488499E+11 | 0.149441E+11 | 0.612808E+11 | 0.231841E+10 | 0.264315E+11 | 12648678.15 | 0.00 | 0.480501E+11 | 0.00 | 0.00 | 0.00 | 0.451256E+10 | 0.00 |
July | 0.457251E+11 | 0.158809E+11 | 0.606074E+11 | 0.228147E+10 | 0.251952E+11 | 12479700.62 | 0.00 | 0.483246E+11 | 0.00 | 0.00 | 0.00 | 0.409150E+10 | 0.00 |
August | 0.509265E+11 | 0.174753E+11 | 0.635880E+11 | 0.240664E+10 | 0.273506E+11 | 12960379.13 | 0.00 | 0.467131E+11 | 0.00 | 0.00 | 0.00 | 0.443420E+10 | 0.00 |
September | 0.454877E+11 | 0.188986E+11 | 0.593832E+11 | 0.224140E+10 | 0.221421E+11 | 20279187.11 | 0.00 | 0.303122E+11 | 0.00 | 0.00 | 0.00 | 0.407968E+10 | 0.00 |
October | 0.472479E+11 | 0.217180E+11 | 0.614108E+11 | 0.230966E+10 | 0.159038E+11 | 0.182609E+09 | 0.00 | 0.536737E+10 | 0.00 | 0.00 | 0.00 | 0.440702E+10 | 0.00 |
November | 0.466941E+11 | 0.228890E+11 | 0.599069E+11 | 0.224962E+10 | 0.135073E+11 | 0.252235E+09 | 0.00 | 0.171566E+10 | 0.00 | 0.00 | 0.00 | 0.458242E+10 | 0.00 |
December | 0.457251E+11 | 0.247447E+11 | 0.605962E+11 | 0.228081E+10 | 0.141330E+11 | 0.524804E+09 | 0.00 | 0.101794E+10 | 0.00 | 0.00 | 0.00 | 0.479262E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.235800E+12 | 0.729266E+12 | 0.274993E+11 | 0.215074E+12 | 0.225652E+10 | 0.00 | 0.201051E+12 | 0.00 | 0.00 | 0.00 | 0.557138E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.149441E+11 | 0.556056E+11 | 0.209511E+10 | 0.127472E+11 | 12479700.62 | 0.00 | 0.321979E+09 | 0.00 | 0.00 | 0.00 | 0.407968E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.247447E+11 | 0.635880E+11 | 0.240664E+10 | 0.273506E+11 | 0.524804E+09 | 0.00 | 0.483246E+11 | 0.00 | 0.00 | 0.00 | 0.545784E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.708094E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.730903E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.516855E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.354975E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.600152E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 75036694.43 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 41925196.09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 63348914.40 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.180369E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.344111E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.502165E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.102405E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.426101E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 41925196.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.102405E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 05-JAN-12:20 | 16276.35 | 20-JAN-15:30 | 1064.81 | 05-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 01-FEB-17:10 | 17519.37 | 06-FEB-07:10 | 1088.57 | 06-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 03-MAR-12:09 | 23552.67 | 15-MAR-15:20 | 1048.04 | 20-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 03-APR-07:19 | 16667.71 | 07-APR-15:39 | 1047.36 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 03-MAY-07:10 | 23909.81 | 18-MAY-14:30 | 725.43 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 01-JUN-07:10 | 37640.51 | 26-JUN-14:00 | 118.63 | 09-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 36892.53 | 17-JUL-14:09 | 62.22 | 03-JUL-06:19 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:19 | 38571.16 | 16-AUG-15:20 | 78.88 | 23-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 22-SEP-07:10 | 34566.23 | 12-SEP-15:50 | 553.23 | 22-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 12-OCT-11:09 | 26571.32 | 11-OCT-15:00 | 1036.40 | 30-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 01-NOV-07:19 | 19576.65 | 07-NOV-15:39 | 1014.34 | 30-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 06-DEC-13:09 | 16748.90 | 26-DEC-07:10 | 1141.29 | 23-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 16276.35 | 62.22 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 38571.16 | 1141.29 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 19917.24 | 20-JAN-13:30 | 0.00 | 0.00 | 0.00 | 6742.33 | 30-JAN-12:00 | 0.00 |
February | 14192.20 | 18-FEB-13:30 | 0.00 | 0.00 | 0.00 | 6807.63 | 13-FEB-12:00 | 0.00 |
March | 31263.98 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 6740.49 | 01-MAR-12:30 | 0.00 |
April | 20624.23 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 6680.06 | 03-APR-11:50 | 0.00 |
May | 42376.97 | 31-MAY-15:30 | 0.00 | 0.00 | 0.00 | 6264.87 | 01-MAY-11:30 | 0.00 |
June | 90148.06 | 26-JUN-14:00 | 0.00 | 0.00 | 0.00 | 5842.24 | 01-JUN-11:00 | 0.00 |
July | 75130.64 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 5757.87 | 06-JUL-11:39 | 0.00 |
August | 81485.57 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 5408.69 | 31-AUG-11:30 | 0.00 |
September | 59974.88 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 5766.90 | 28-SEP-11:39 | 0.00 |
October | 43404.11 | 11-OCT-14:09 | 0.00 | 0.00 | 0.00 | 6081.99 | 31-OCT-11:00 | 0.00 |
November | 23715.95 | 07-NOV-15:09 | 0.00 | 0.00 | 0.00 | 6270.27 | 30-NOV-12:39 | 0.00 |
December | 20085.63 | 01-DEC-13:00 | 0.00 | 0.00 | 0.00 | 6686.70 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14192.20 | 0.00 | 0.00 | 0.00 | 5408.69 | 0.00 | ||
Maximum of Months | 90148.06 | 0.00 | 0.00 | 0.00 | 6807.63 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 131174.52 | 20-JAN-13:09 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 14703.85 | 6.85 | 0.00 | 19882.90 | 0.00 |
February | 112411.73 | 17-FEB-13:00 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 13319.24 | 6.85 | 0.00 | 2424.03 | 0.00 |
March | 146624.89 | 13-MAR-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 20957.49 | 6.85 | 0.00 | 27510.18 | 0.00 |
April | 134355.93 | 07-APR-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 16658.48 | 6.85 | 0.00 | 19793.78 | 0.00 |
May | 163005.77 | 31-MAY-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 23241.00 | 6.85 | 0.00 | 42356.50 | 0.00 |
June | 224294.16 | 26-JUN-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 37569.22 | 6.85 | 0.00 | 89678.40 | 0.00 |
July | 206763.47 | 17-JUL-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 36892.53 | 6.85 | 0.00 | 73906.05 | 0.00 |
August | 216561.63 | 16-AUG-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 38527.96 | 6.85 | 0.00 | 81000.22 | 0.00 |
September | 191378.84 | 12-SEP-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 34359.98 | 6.85 | 0.00 | 59974.88 | 0.00 |
October | 164814.52 | 11-OCT-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 26476.07 | 6.85 | 0.00 | 40958.50 | 0.00 |
November | 139008.90 | 07-NOV-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 18956.74 | 6.85 | 0.00 | 23715.95 | 0.00 |
December | 129589.00 | 01-DEC-13:00 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 13586.40 | 6.85 | 0.00 | 20085.63 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 112411.73 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 13319.24 | 6.85 | 0.00 | 2424.03 | 0.00 | |
Maximum of Months | 224294.16 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 38527.96 | 6.85 | 0.00 | 89678.40 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 251366.60 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 259409.98 | 06-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 241860.21 | 20-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 237156.71 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 154288.09 | 01-MAY-05:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 22209.47 | 09-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 10983.82 | 03-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 16167.86 | 23-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 117839.14 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 236019.25 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 225187.73 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 284245.59 | 23-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 10983.82 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 284245.59 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.27 | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.68 | 0.33 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
Annual Sum or Average | 0.50 | 19.54 | 0.50 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.68 | 0.33 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.67 | 0.50 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
February | 1.17 | 18.18 | 0.67 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 0.50 | 17.85 | 0.17 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
April | 0.50 | 18.30 | 0.33 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.39 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 19.03 | 1.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Annual Sum or Average | 4.67 | 18.57 | 3.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.39 | 1.50 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.00 | 15.36 | 3.17 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
February | 19.50 | 15.30 | 6.33 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
March | 10.50 | 15.06 | 2.83 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
April | 6.33 | 15.39 | 0.50 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
May | 0.17 | 19.43 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.33 | 15.24 | 0.33 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
November | 3.83 | 16.21 | 0.33 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 |
December | 33.50 | 15.73 | 12.50 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
Annual Sum or Average | 92.17 | 15.49 | 26.17 | 15.77 | 0.17 | 15.79 | 0.17 | 15.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.50 | 19.43 | 12.50 | 19.43 | 0.17 | 27.40 | 0.17 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.83 | 15.30 | 1.67 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
February | 18.33 | 15.16 | 4.83 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
March | 10.67 | 14.99 | 2.50 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
April | 6.83 | 15.22 | 0.50 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.59 | 2.00 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.92 | 7.33 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.02 | 3.00 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.79 | 0.67 | 27.79 |
October | 4.33 | 15.21 | 0.33 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
November | 4.33 | 16.02 | 0.33 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
December | 29.17 | 15.48 | 7.83 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
Annual Sum or Average | 85.50 | 15.32 | 18.00 | 15.56 | 13.00 | 16.93 | 13.00 | 18.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.17 | 16.02 | 7.83 | 16.24 | 7.33 | 28.02 | 7.33 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 15.97 | 1.33 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
February | 16.33 | 15.35 | 5.00 | 15.53 | 0.17 | 15.62 | 0.17 | 15.71 |
March | 10.00 | 15.07 | 2.50 | 14.98 | 0.67 | 15.61 | 0.67 | 16.19 |
April | 6.33 | 15.39 | 0.50 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
May | 0.17 | 19.42 | 0.17 | 19.42 | 0.17 | 22.05 | 0.17 | 23.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.56 | 0.67 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.67 | 1.83 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.64 | 2.17 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.21 | 3.67 | 28.21 |
October | 4.00 | 15.32 | 0.17 | 15.48 | 3.50 | 21.19 | 3.50 | 23.33 |
November | 3.17 | 16.21 | 0.33 | 16.49 | 1.00 | 19.06 | 1.00 | 20.69 |
December | 24.67 | 15.76 | 7.00 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
Annual Sum or Average | 70.00 | 15.55 | 17.00 | 15.84 | 13.83 | 17.50 | 13.83 | 18.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 | 0.00 | 15.67 |
Maximum of Months | 24.67 | 19.42 | 7.00 | 19.42 | 3.67 | 28.21 | 3.67 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.33 | 15.33 | 2.67 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
February | 17.33 | 14.95 | 5.00 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
March | 10.83 | 14.93 | 2.83 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
April | 6.67 | 15.10 | 0.33 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.42 | 3.00 | 28.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.19 | 3.00 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.18 | 1.67 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.47 | 1.50 | 28.53 |
October | 4.17 | 15.03 | 0.17 | 15.03 | 0.33 | 15.90 | 0.33 | 16.66 |
November | 4.00 | 16.14 | 0.33 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
December | 29.83 | 15.57 | 10.17 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
Annual Sum or Average | 84.17 | 15.29 | 21.50 | 15.50 | 14.83 | 17.07 | 9.67 | 17.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 | 14.80 |
Maximum of Months | 29.83 | 16.14 | 10.17 | 16.38 | 5.50 | 28.47 | 3.00 | 28.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
February | 6.00 | 17.29 | 2.50 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
March | 0.50 | 17.74 | 0.17 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
April | 0.33 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 17.01 | 1.83 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
Annual Sum or Average | 11.33 | 17.19 | 4.50 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 17.74 | 2.50 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
February | 3.83 | 17.47 | 1.67 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
March | 0.33 | 15.81 | 0.17 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
April | 0.33 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.58 | 2.50 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.81 | 2.00 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.45 | 0.83 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
December | 2.83 | 16.33 | 0.83 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
Annual Sum or Average | 8.00 | 16.94 | 2.67 | 17.44 | 5.33 | 20.84 | 5.33 | 22.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 17.47 | 1.67 | 18.18 | 2.50 | 27.81 | 2.50 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.17 | 18.08 | 39.83 | 18.08 | 0.17 | 18.10 | 0.17 | 18.12 |
February | 43.67 | 17.99 | 42.83 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 |
March | 31.83 | 18.41 | 31.67 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
April | 27.17 | 18.68 | 26.83 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
May | 6.67 | 19.40 | 6.67 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.63 | 0.83 | 24.63 |
September | 1.67 | 19.27 | 1.67 | 19.27 | 4.17 | 23.99 | 4.17 | 25.34 |
October | 22.83 | 18.16 | 22.83 | 18.16 | 4.67 | 19.07 | 4.67 | 19.83 |
November | 29.33 | 18.15 | 29.33 | 18.15 | 1.17 | 18.35 | 1.17 | 18.53 |
December | 49.83 | 17.47 | 49.00 | 17.48 | 1.33 | 17.61 | 1.33 | 17.74 |
Annual Sum or Average | 253.17 | 18.11 | 250.67 | 18.12 | 12.33 | 18.34 | 12.33 | 18.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.83 | 19.40 | 49.00 | 19.40 | 4.67 | 24.63 | 4.67 | 25.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
February | 3.17 | 17.57 | 1.33 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
March | 0.67 | 15.39 | 0.50 | 15.22 | 0.17 | 16.73 | 0.17 | 17.92 |
April | 0.33 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.91 | 1.83 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.19 | 0.83 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.85 | 1.00 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.16 | 1.17 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.62 | 0.50 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 15.82 | 0.67 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
Annual Sum or Average | 7.17 | 16.68 | 2.50 | 17.00 | 9.17 | 22.34 | 5.50 | 23.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 17.57 | 1.33 | 18.28 | 3.17 | 28.19 | 1.83 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
February | 5.67 | 16.27 | 1.83 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
March | 1.67 | 15.44 | 1.33 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
April | 0.67 | 17.03 | 0.17 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
November | 0.50 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
December | 10.67 | 16.53 | 4.33 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
Annual Sum or Average | 20.17 | 16.42 | 7.67 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.67 | 17.04 | 4.33 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
February | 4.33 | 15.56 | 0.83 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
March | 1.67 | 14.91 | 1.17 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
April | 0.50 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.67 | 2.17 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.98 | 6.33 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.15 | 3.17 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.88 | 1.17 | 27.88 |
October | 0.33 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
November | 0.67 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
December | 8.50 | 15.54 | 1.83 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
Annual Sum or Average | 16.67 | 15.65 | 3.83 | 15.79 | 12.83 | 20.47 | 12.83 | 22.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.50 | 17.03 | 1.83 | 17.03 | 6.33 | 28.15 | 6.33 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.05 | 0.00 | 17.05 | 0.67 | 23.88 | 0.67 | 25.24 |
February | 3.17 | 16.85 | 1.00 | 17.58 | 0.67 | 19.02 | 0.67 | 20.11 |
March | 1.50 | 15.53 | 1.17 | 15.49 | 1.00 | 18.85 | 1.00 | 20.77 |
April | 0.67 | 17.02 | 0.17 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.58 | 1.33 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.72 | 2.00 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.09 | 4.50 | 28.09 |
October | 0.33 | 17.03 | 0.00 | 17.03 | 4.83 | 27.43 | 4.83 | 27.77 |
November | 0.50 | 17.08 | 0.00 | 17.08 | 2.17 | 26.00 | 2.17 | 26.92 |
December | 5.83 | 16.57 | 2.17 | 17.10 | 1.67 | 18.96 | 1.67 | 20.28 |
Annual Sum or Average | 12.33 | 16.59 | 4.50 | 16.98 | 19.17 | 22.82 | 19.17 | 24.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.83 | 17.08 | 2.17 | 17.58 | 4.83 | 28.09 | 4.83 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
February | 4.00 | 15.56 | 0.83 | 15.79 | 0.00 | 15.79 | 0.00 | 15.79 |
March | 1.67 | 14.86 | 1.17 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
April | 0.50 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.38 | 2.67 | 28.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.37 | 1.67 | 28.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.16 | 1.50 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.48 | 1.33 | 28.52 |
October | 0.33 | 16.91 | 0.00 | 16.91 | 0.83 | 24.46 | 0.83 | 25.71 |
November | 0.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
December | 7.50 | 15.26 | 1.67 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
Annual Sum or Average | 15.00 | 15.47 | 3.67 | 15.53 | 12.83 | 20.72 | 8.17 | 22.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 | 0.00 | 14.76 |
Maximum of Months | 7.50 | 16.98 | 1.67 | 16.98 | 4.67 | 28.48 | 2.67 | 28.52 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 430.50 | 23.47 | 13.17 | 23.45 | 12.00 | 23.42 |
February | 384.17 | 23.34 | 3.50 | 23.32 | 3.50 | 23.30 |
March | 441.83 | 23.64 | 11.83 | 23.67 | 0.00 | 23.67 |
April | 334.50 | 23.71 | 14.00 | 23.77 | 0.00 | 23.77 |
May | 99.83 | 23.88 | 158.83 | 24.70 | 0.00 | 24.70 |
June | 0.00 | 0.00 | 342.67 | 24.57 | 0.00 | 24.57 |
July | 5.00 | 24.35 | 398.50 | 24.53 | 5.00 | 24.53 |
August | 0.00 | 0.00 | 385.17 | 24.55 | 0.00 | 24.55 |
September | 22.50 | 24.00 | 205.00 | 24.84 | 0.00 | 24.84 |
October | 188.33 | 23.87 | 51.00 | 24.30 | 0.00 | 24.30 |
November | 297.67 | 23.76 | 19.50 | 23.88 | 0.00 | 23.88 |
December | 482.17 | 23.40 | 18.50 | 23.32 | 18.50 | 23.24 |
Annual Sum or Average | 2686.50 | 23.58 | 1621.67 | 23.99 | 39.00 | 23.97 |
Minimum of Months | 0.00 | 0.00 | 3.50 | 23.32 | 0.00 | 23.24 |
Maximum of Months | 482.17 | 24.35 | 398.50 | 24.84 | 18.50 | 24.84 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.50 | 22.22 | 68.17 | 22.02 | 68.17 | 21.87 |
February | 452.67 | 22.23 | 67.67 | 22.01 | 67.67 | 21.84 |
March | 500.17 | 22.66 | 33.83 | 22.51 | 33.83 | 22.38 |
April | 445.00 | 22.67 | 24.50 | 22.58 | 24.33 | 22.50 |
May | 256.50 | 23.38 | 36.67 | 23.52 | 0.00 | 23.52 |
June | 26.83 | 23.67 | 253.33 | 24.29 | 0.00 | 24.29 |
July | 22.33 | 24.05 | 303.83 | 24.30 | 7.33 | 24.30 |
August | 8.17 | 23.86 | 310.00 | 24.36 | 0.00 | 24.36 |
September | 137.83 | 23.58 | 115.67 | 24.08 | 0.00 | 24.08 |
October | 432.67 | 23.13 | 9.83 | 23.10 | 7.00 | 23.06 |
November | 467.83 | 22.67 | 9.50 | 22.63 | 9.50 | 22.59 |
December | 497.00 | 21.94 | 108.50 | 21.66 | 108.50 | 21.46 |
Annual Sum or Average | 3746.50 | 22.61 | 1341.50 | 22.84 | 326.33 | 22.70 |
Minimum of Months | 8.17 | 21.94 | 9.50 | 21.66 | 0.00 | 21.46 |
Maximum of Months | 500.17 | 24.05 | 310.00 | 24.36 | 108.50 | 24.36 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.10 | 215.33 | 20.80 | 215.33 | 20.63 |
February | 454.00 | 21.23 | 195.33 | 20.94 | 195.33 | 20.78 |
March | 512.17 | 21.85 | 114.17 | 21.52 | 114.17 | 21.29 |
April | 457.50 | 21.79 | 109.50 | 21.45 | 109.00 | 21.21 |
May | 325.33 | 22.86 | 40.17 | 22.91 | 9.17 | 22.86 |
June | 77.67 | 23.33 | 256.33 | 24.02 | 0.00 | 24.02 |
July | 64.83 | 23.48 | 288.33 | 24.09 | 9.67 | 24.09 |
August | 71.00 | 23.31 | 260.50 | 24.03 | 0.00 | 24.03 |
September | 220.83 | 23.04 | 88.17 | 23.39 | 1.00 | 23.38 |
October | 480.00 | 22.13 | 84.67 | 21.88 | 84.67 | 21.70 |
November | 486.83 | 21.55 | 138.67 | 21.32 | 138.67 | 21.17 |
December | 497.00 | 20.82 | 292.33 | 20.57 | 292.33 | 20.46 |
Annual Sum or Average | 4149.17 | 21.78 | 2083.50 | 21.85 | 1169.33 | 21.59 |
Minimum of Months | 64.83 | 20.82 | 40.17 | 20.57 | 0.00 | 20.46 |
Maximum of Months | 512.17 | 23.48 | 292.33 | 24.09 | 292.33 | 24.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 378.33 | 20.00 | 378.33 | 19.94 |
February | 454.00 | 20.25 | 357.00 | 20.15 | 357.00 | 20.11 |
March | 514.00 | 20.79 | 273.33 | 20.54 | 273.33 | 20.42 |
April | 481.00 | 20.76 | 206.83 | 20.39 | 206.83 | 20.20 |
May | 406.00 | 21.99 | 76.33 | 22.05 | 37.67 | 21.92 |
June | 138.50 | 22.64 | 255.67 | 23.59 | 0.17 | 23.59 |
July | 139.83 | 22.76 | 284.00 | 23.67 | 18.33 | 23.66 |
August | 189.50 | 22.56 | 222.67 | 23.37 | 2.50 | 23.37 |
September | 325.83 | 22.18 | 100.17 | 22.47 | 21.50 | 22.36 |
October | 497.17 | 20.95 | 205.00 | 20.68 | 205.00 | 20.54 |
November | 489.00 | 20.48 | 330.50 | 20.32 | 330.50 | 20.25 |
December | 497.00 | 19.99 | 445.17 | 19.93 | 445.17 | 19.91 |
Annual Sum or Average | 4633.83 | 20.95 | 3135.00 | 21.02 | 2276.33 | 20.78 |
Minimum of Months | 138.50 | 19.99 | 76.33 | 19.93 | 0.17 | 19.91 |
Maximum of Months | 514.00 | 22.76 | 445.17 | 23.67 | 445.17 | 23.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.44 | 304.00 | 20.20 | 304.00 | 20.10 |
February | 453.67 | 20.63 | 262.50 | 20.35 | 262.50 | 20.22 |
March | 463.33 | 21.07 | 208.83 | 20.74 | 205.17 | 20.55 |
April | 411.33 | 20.80 | 184.17 | 20.47 | 169.00 | 20.22 |
May | 300.33 | 22.11 | 142.33 | 22.62 | 22.67 | 22.51 |
June | 76.33 | 23.04 | 350.67 | 24.02 | 6.17 | 24.05 |
July | 108.50 | 23.58 | 373.17 | 24.19 | 40.17 | 24.26 |
August | 125.00 | 22.99 | 334.00 | 23.89 | 13.33 | 23.95 |
September | 221.83 | 22.33 | 196.17 | 23.14 | 16.00 | 23.06 |
October | 451.67 | 21.30 | 168.50 | 21.03 | 158.83 | 20.81 |
November | 488.00 | 20.85 | 247.33 | 20.60 | 247.33 | 20.48 |
December | 497.00 | 20.16 | 380.00 | 20.01 | 380.00 | 19.95 |
Annual Sum or Average | 4099.00 | 21.11 | 3151.67 | 21.42 | 1825.17 | 21.14 |
Minimum of Months | 76.33 | 20.16 | 142.33 | 20.01 | 6.17 | 19.95 |
Maximum of Months | 502.00 | 23.58 | 380.00 | 24.19 | 380.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 391.50 | 20.88 | 257.17 | 20.85 | 208.67 | 20.63 |
February | 349.50 | 20.77 | 244.67 | 20.75 | 198.83 | 20.53 |
March | 400.17 | 20.99 | 237.33 | 20.91 | 198.33 | 20.71 |
April | 400.67 | 20.69 | 206.17 | 20.45 | 180.83 | 20.21 |
May | 341.17 | 21.95 | 128.50 | 22.30 | 37.17 | 22.15 |
June | 144.00 | 22.51 | 266.00 | 23.59 | 1.17 | 23.60 |
July | 147.83 | 22.79 | 303.17 | 23.77 | 23.17 | 23.79 |
August | 157.67 | 22.68 | 292.00 | 23.69 | 10.83 | 23.73 |
September | 228.17 | 22.54 | 216.33 | 23.31 | 28.83 | 23.30 |
October | 351.50 | 21.21 | 250.00 | 21.49 | 158.67 | 21.26 |
November | 357.00 | 21.07 | 235.17 | 21.24 | 165.17 | 21.01 |
December | 416.50 | 20.55 | 302.50 | 20.43 | 275.83 | 20.26 |
Annual Sum or Average | 3685.67 | 21.29 | 2939.00 | 21.69 | 1487.50 | 21.40 |
Minimum of Months | 144.00 | 20.55 | 128.50 | 20.43 | 1.17 | 20.21 |
Maximum of Months | 416.50 | 22.79 | 303.17 | 23.77 | 275.83 | 23.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.33 | 20.43 | 327.00 | 20.21 | 327.00 | 20.12 |
February | 434.50 | 20.52 | 286.17 | 20.31 | 282.67 | 20.21 |
March | 459.33 | 20.78 | 252.83 | 20.62 | 237.17 | 20.48 |
April | 430.83 | 20.62 | 213.00 | 20.40 | 191.50 | 20.18 |
May | 356.83 | 21.77 | 138.00 | 22.21 | 37.00 | 22.08 |
June | 168.33 | 22.55 | 268.67 | 23.61 | 13.00 | 23.70 |
July | 179.33 | 22.64 | 284.00 | 23.60 | 27.17 | 23.65 |
August | 195.67 | 22.38 | 255.67 | 23.41 | 10.67 | 23.46 |
September | 304.67 | 22.13 | 157.83 | 22.72 | 27.83 | 22.68 |
October | 435.50 | 20.89 | 218.17 | 20.82 | 185.00 | 20.64 |
November | 468.33 | 20.71 | 266.67 | 20.49 | 266.17 | 20.39 |
December | 494.33 | 20.21 | 384.83 | 20.04 | 384.83 | 19.97 |
Annual Sum or Average | 4419.00 | 21.03 | 3052.83 | 21.23 | 1990.00 | 20.98 |
Minimum of Months | 168.33 | 20.21 | 138.00 | 20.04 | 10.67 | 19.97 |
Maximum of Months | 494.33 | 22.64 | 384.83 | 23.61 | 384.83 | 23.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 390.67 | 20.27 | 390.67 | 20.24 |
February | 454.00 | 20.38 | 391.67 | 20.33 | 391.67 | 20.31 |
March | 514.00 | 20.73 | 348.00 | 20.59 | 348.00 | 20.53 |
April | 485.00 | 20.82 | 231.50 | 20.60 | 231.50 | 20.49 |
May | 486.67 | 22.15 | 33.67 | 22.06 | 32.50 | 21.97 |
June | 158.83 | 23.08 | 168.17 | 23.61 | 0.00 | 23.61 |
July | 139.50 | 23.19 | 232.50 | 23.77 | 18.50 | 23.76 |
August | 146.83 | 23.10 | 209.50 | 23.69 | 1.17 | 23.69 |
September | 260.17 | 22.84 | 90.83 | 23.20 | 0.83 | 23.20 |
October | 500.83 | 21.65 | 88.50 | 21.46 | 88.50 | 21.33 |
November | 489.00 | 21.00 | 223.83 | 20.86 | 223.83 | 20.79 |
December | 497.00 | 20.36 | 419.67 | 20.29 | 419.67 | 20.26 |
Annual Sum or Average | 4633.83 | 21.25 | 2828.50 | 21.25 | 2146.83 | 21.04 |
Minimum of Months | 139.50 | 20.36 | 33.67 | 20.27 | 0.00 | 20.24 |
Maximum of Months | 514.00 | 23.19 | 419.67 | 23.77 | 419.67 | 23.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.77 | 287.17 | 20.59 | 287.17 | 20.51 |
February | 454.00 | 20.83 | 256.67 | 20.59 | 256.67 | 20.48 |
March | 497.33 | 21.33 | 214.50 | 21.02 | 211.17 | 20.83 |
April | 450.33 | 21.27 | 153.33 | 20.94 | 150.83 | 20.74 |
May | 352.67 | 22.44 | 72.83 | 22.66 | 16.17 | 22.58 |
June | 41.33 | 23.14 | 354.67 | 24.17 | 0.83 | 24.18 |
July | 59.83 | 23.59 | 379.17 | 24.30 | 24.00 | 24.31 |
August | 50.83 | 23.72 | 379.17 | 24.24 | 10.00 | 24.29 |
September | 131.67 | 23.01 | 215.33 | 23.91 | 1.50 | 23.92 |
October | 409.00 | 21.99 | 87.00 | 21.86 | 72.17 | 21.68 |
November | 477.33 | 21.46 | 133.33 | 21.26 | 133.33 | 21.14 |
December | 497.00 | 20.67 | 310.00 | 20.48 | 310.00 | 20.40 |
Annual Sum or Average | 3923.33 | 21.43 | 2843.17 | 21.79 | 1473.83 | 21.53 |
Minimum of Months | 41.33 | 20.67 | 72.83 | 20.48 | 0.83 | 20.40 |
Maximum of Months | 502.00 | 23.72 | 379.17 | 24.30 | 310.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 406.50 | 21.14 | 168.00 | 21.02 | 137.00 | 20.76 |
February | 383.00 | 20.83 | 184.00 | 20.57 | 167.33 | 20.32 |
March | 441.83 | 21.08 | 190.67 | 20.77 | 183.83 | 20.56 |
April | 463.00 | 21.01 | 164.17 | 20.65 | 164.17 | 20.45 |
May | 429.50 | 22.04 | 45.00 | 22.02 | 30.00 | 21.92 |
June | 150.83 | 22.77 | 205.17 | 23.59 | 0.17 | 23.59 |
July | 134.33 | 22.95 | 276.67 | 23.81 | 27.50 | 23.78 |
August | 80.67 | 22.69 | 326.83 | 24.00 | 4.17 | 24.00 |
September | 118.83 | 22.94 | 255.33 | 24.03 | 12.67 | 24.09 |
October | 317.67 | 21.90 | 168.17 | 22.22 | 78.50 | 22.02 |
November | 342.67 | 21.48 | 157.83 | 21.78 | 74.33 | 21.51 |
December | 415.33 | 20.76 | 217.00 | 20.53 | 199.00 | 20.29 |
Annual Sum or Average | 3684.17 | 21.47 | 2358.83 | 21.83 | 1078.67 | 21.54 |
Minimum of Months | 80.67 | 20.76 | 45.00 | 20.53 | 0.17 | 20.29 |
Maximum of Months | 463.00 | 22.95 | 326.83 | 24.03 | 199.00 | 24.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.17 | 20.76 | 292.67 | 20.57 | 292.67 | 20.48 |
February | 448.83 | 20.76 | 272.50 | 20.55 | 272.50 | 20.46 |
March | 489.67 | 21.05 | 240.50 | 20.81 | 238.67 | 20.67 |
April | 464.67 | 21.04 | 166.50 | 20.75 | 165.67 | 20.58 |
May | 409.67 | 22.10 | 59.67 | 22.24 | 21.33 | 22.17 |
June | 123.83 | 22.92 | 272.67 | 23.89 | 4.00 | 23.93 |
July | 133.33 | 23.04 | 286.17 | 23.89 | 20.00 | 23.90 |
August | 105.50 | 22.98 | 306.67 | 23.96 | 4.83 | 23.98 |
September | 200.67 | 22.89 | 174.67 | 23.63 | 5.67 | 23.66 |
October | 429.83 | 21.80 | 93.83 | 21.74 | 71.67 | 21.58 |
November | 469.50 | 21.35 | 138.83 | 21.18 | 138.83 | 21.07 |
December | 496.67 | 20.67 | 327.33 | 20.48 | 327.33 | 20.40 |
Annual Sum or Average | 4270.33 | 21.40 | 2632.00 | 21.62 | 1563.17 | 21.38 |
Minimum of Months | 105.50 | 20.67 | 59.67 | 20.48 | 4.00 | 20.40 |
Maximum of Months | 498.17 | 23.04 | 327.33 | 23.96 | 327.33 | 23.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.52 | 293.33 | 20.32 | 293.33 | 20.23 |
February | 454.00 | 20.55 | 288.83 | 20.40 | 288.83 | 20.33 |
March | 514.00 | 21.15 | 194.67 | 20.85 | 194.67 | 20.68 |
April | 476.33 | 21.23 | 148.50 | 20.90 | 148.50 | 20.69 |
May | 361.00 | 22.53 | 61.67 | 22.65 | 15.33 | 22.58 |
June | 60.50 | 23.21 | 300.67 | 24.01 | 0.17 | 24.01 |
July | 66.67 | 23.33 | 328.83 | 24.06 | 17.67 | 24.05 |
August | 105.00 | 23.06 | 273.50 | 23.85 | 1.83 | 23.85 |
September | 254.00 | 22.68 | 97.67 | 23.10 | 3.33 | 23.07 |
October | 496.33 | 21.56 | 113.50 | 21.32 | 113.50 | 21.15 |
November | 489.00 | 20.96 | 231.50 | 20.77 | 231.50 | 20.68 |
December | 497.00 | 20.30 | 383.67 | 20.19 | 383.67 | 20.14 |
Annual Sum or Average | 4275.83 | 21.27 | 2716.33 | 21.42 | 1692.33 | 21.17 |
Minimum of Months | 60.50 | 20.30 | 61.67 | 20.19 | 0.17 | 20.14 |
Maximum of Months | 514.00 | 23.33 | 383.67 | 24.06 | 383.67 | 24.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 424.33 | 20.78 | 214.50 | 20.54 | 214.50 | 20.42 |
February | 369.83 | 20.78 | 186.00 | 20.50 | 184.50 | 20.35 |
March | 386.83 | 21.19 | 149.50 | 20.93 | 140.17 | 20.71 |
April | 352.67 | 21.10 | 140.00 | 20.88 | 120.50 | 20.64 |
May | 248.67 | 22.34 | 106.50 | 22.88 | 10.67 | 22.81 |
June | 61.83 | 23.35 | 290.00 | 24.16 | 7.33 | 24.21 |
July | 87.17 | 23.94 | 311.67 | 24.36 | 37.50 | 24.46 |
August | 99.33 | 23.26 | 268.00 | 24.05 | 13.67 | 24.13 |
September | 186.00 | 22.62 | 143.50 | 23.40 | 6.17 | 23.41 |
October | 370.00 | 21.53 | 111.00 | 21.42 | 90.17 | 21.21 |
November | 403.50 | 21.14 | 152.00 | 20.94 | 150.50 | 20.81 |
December | 422.00 | 20.46 | 277.33 | 20.24 | 277.33 | 20.14 |
Annual Sum or Average | 3412.17 | 21.36 | 2350.00 | 21.69 | 1253.00 | 21.44 |
Minimum of Months | 61.83 | 20.46 | 106.50 | 20.24 | 6.17 | 20.14 |
Maximum of Months | 424.33 | 23.94 | 311.67 | 24.36 | 277.33 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 354.17 | 21.30 | 210.67 | 21.48 | 136.00 | 21.24 |
February | 323.00 | 21.12 | 205.50 | 21.17 | 147.83 | 20.92 |
March | 380.67 | 21.38 | 169.17 | 21.28 | 131.17 | 21.04 |
April | 388.33 | 21.21 | 144.00 | 20.98 | 123.83 | 20.74 |
May | 301.83 | 22.45 | 113.33 | 22.86 | 14.50 | 22.79 |
June | 90.00 | 23.04 | 300.33 | 23.97 | 0.50 | 23.97 |
July | 85.50 | 23.37 | 337.67 | 24.14 | 21.00 | 24.15 |
August | 89.33 | 23.31 | 338.33 | 24.11 | 10.00 | 24.15 |
September | 169.00 | 23.12 | 226.33 | 23.88 | 17.00 | 23.97 |
October | 329.83 | 21.86 | 200.00 | 22.21 | 100.17 | 22.05 |
November | 322.83 | 21.55 | 197.33 | 21.92 | 104.17 | 21.70 |
December | 394.50 | 21.07 | 251.17 | 21.01 | 210.50 | 20.80 |
Annual Sum or Average | 3229.00 | 21.70 | 2693.83 | 22.24 | 1016.67 | 21.98 |
Minimum of Months | 85.50 | 21.07 | 113.33 | 20.98 | 0.50 | 20.74 |
Maximum of Months | 394.50 | 23.37 | 338.33 | 24.14 | 210.50 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.50 | 20.78 | 243.17 | 20.54 | 243.17 | 20.43 |
February | 428.33 | 20.77 | 232.00 | 20.56 | 228.33 | 20.44 |
March | 457.50 | 21.04 | 181.67 | 20.85 | 167.83 | 20.68 |
April | 431.17 | 21.02 | 153.67 | 20.83 | 134.67 | 20.62 |
May | 344.17 | 22.14 | 116.83 | 22.61 | 14.50 | 22.55 |
June | 136.83 | 22.96 | 288.00 | 23.88 | 11.83 | 23.97 |
July | 140.17 | 22.98 | 307.67 | 23.86 | 22.50 | 23.90 |
August | 152.83 | 22.77 | 285.00 | 23.74 | 10.00 | 23.78 |
September | 266.33 | 22.47 | 150.83 | 23.15 | 10.33 | 23.18 |
October | 429.00 | 21.32 | 143.67 | 21.31 | 109.50 | 21.14 |
November | 461.00 | 21.10 | 182.33 | 20.90 | 181.00 | 20.79 |
December | 490.33 | 20.52 | 324.00 | 20.32 | 324.00 | 20.23 |
Annual Sum or Average | 4224.17 | 21.32 | 2608.83 | 21.60 | 1457.67 | 21.37 |
Minimum of Months | 136.83 | 20.52 | 116.83 | 20.32 | 10.00 | 20.23 |
Maximum of Months | 490.33 | 22.98 | 324.00 | 23.88 | 324.00 | 23.97 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62412 | 20.38486 | 0.08332 | 5.68642 |
February | 454.00000 | 23.54427 | 17.45076 | 0.04440 | 5.93344 |
March | 514.00000 | 23.78979 | 17.03679 | 0.12122 | 5.78124 |
April | 485.00000 | 23.93635 | 21.20531 | 0.17962 | 6.08373 |
May | 508.00000 | 24.39520 | 24.64905 | -0.5144 | 11.35509 |
June | 496.00000 | 24.40651 | 32.69765 | -0.3784 | 8.58764 |
July | 497.00000 | 24.44580 | 34.83700 | -0.3499 | 8.13596 |
August | 514.00000 | 24.42187 | 33.27515 | -0.3625 | 8.35734 |
September | 485.00000 | 24.42887 | 24.74002 | -0.4378 | 9.73607 |
October | 502.00000 | 24.25652 | 18.59173 | 0.27144 | 6.92725 |
November | 489.00000 | 24.07110 | 19.91707 | 0.20899 | 6.26821 |
December | 497.00000 | 23.44902 | 14.07750 | 0.00024 | 5.96282 |
Annual Sum or Average | 5943.00000 | 24.06798 | 23.29168 | -0.0962 | 7.41474 |
Minimum of Months | 454.00000 | 23.44902 | 14.07750 | -0.5144 | 5.68642 |
Maximum of Months | 514.00000 | 24.44580 | 34.83700 | 0.27144 | 11.35509 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.22673 | 22.18037 | -0.2451 | 7.63608 |
February | 454.00000 | 22.23995 | 19.26131 | -0.2618 | 8.07044 |
March | 514.00000 | 22.70720 | 18.86055 | -0.1360 | 6.98512 |
April | 485.00000 | 22.79336 | 23.32693 | -0.0889 | 6.59035 |
May | 508.00000 | 23.79059 | 25.92142 | -0.7299 | 17.33102 |
June | 496.00000 | 24.17654 | 33.59846 | -0.4780 | 10.15278 |
July | 497.00000 | 24.21275 | 35.63482 | -0.4520 | 9.62227 |
August | 514.00000 | 24.23284 | 34.13233 | -0.4581 | 9.72438 |
September | 485.00000 | 24.08746 | 25.68352 | -0.5880 | 13.08707 |
October | 502.00000 | 23.27569 | 20.45376 | 0.02293 | 6.09318 |
November | 489.00000 | 22.73373 | 22.33181 | -0.1115 | 6.24223 |
December | 497.00000 | 21.93922 | 15.83734 | -0.3567 | 9.55396 |
Annual Sum or Average | 5943.00000 | 23.20966 | 24.81747 | -0.3245 | 9.27331 |
Minimum of Months | 454.00000 | 21.93922 | 15.83734 | -0.7299 | 6.09318 |
Maximum of Months | 514.00000 | 24.23284 | 35.63482 | 0.02293 | 17.33102 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.10093 | 22.08088 | -0.5382 | 13.46583 |
February | 454.00000 | 21.23434 | 19.89356 | -0.5192 | 13.00727 |
March | 514.00000 | 21.85620 | 19.39294 | -0.3470 | 10.27083 |
April | 485.00000 | 21.91733 | 23.98565 | -0.2977 | 9.94154 |
May | 508.00000 | 23.30229 | 26.35292 | -0.8832 | 23.63970 |
June | 496.00000 | 24.00658 | 33.70487 | -0.5117 | 11.09498 |
July | 497.00000 | 24.06143 | 35.66502 | -0.4832 | 10.40873 |
August | 514.00000 | 24.02659 | 34.34737 | -0.5112 | 11.03576 |
September | 485.00000 | 23.64944 | 26.15625 | -0.7306 | 18.07515 |
October | 502.00000 | 22.20693 | 21.62160 | -0.2396 | 8.32887 |
November | 489.00000 | 21.56339 | 23.76431 | -0.4055 | 10.07228 |
December | 497.00000 | 20.82222 | 16.44745 | -0.6492 | 16.28310 |
Annual Sum or Average | 5943.00000 | 22.49050 | 25.33017 | -0.5098 | 12.97142 |
Minimum of Months | 454.00000 | 20.82222 | 16.44745 | -0.8832 | 8.32887 |
Maximum of Months | 514.00000 | 24.06143 | 35.66502 | -0.2396 | 23.63970 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13850 | 22.84615 | -0.8200 | 21.69878 |
February | 454.00000 | 20.25354 | 20.49787 | -0.8059 | 20.92130 |
March | 514.00000 | 20.78684 | 19.70970 | -0.6237 | 15.91147 |
April | 485.00000 | 20.77969 | 24.87639 | -0.5656 | 15.59951 |
May | 508.00000 | 22.40731 | 27.77188 | -1.1287 | 34.71829 |
June | 496.00000 | 23.65280 | 34.39690 | -0.5570 | 13.17642 |
July | 497.00000 | 23.70557 | 36.52213 | -0.5279 | 12.60363 |
August | 514.00000 | 23.47009 | 35.97669 | -0.6327 | 15.47391 |
September | 485.00000 | 22.79596 | 27.44593 | -0.9638 | 28.17416 |
October | 502.00000 | 20.97499 | 22.82279 | -0.5391 | 13.62312 |
November | 489.00000 | 20.47960 | 24.28553 | -0.7041 | 17.31355 |
December | 497.00000 | 19.99083 | 16.43175 | -0.9185 | 25.30810 |
Annual Sum or Average | 5943.00000 | 21.63262 | 26.18099 | -0.7317 | 19.53105 |
Minimum of Months | 454.00000 | 19.99083 | 16.43175 | -1.1287 | 12.60363 |
Maximum of Months | 514.00000 | 23.70557 | 36.52213 | -0.5279 | 34.71829 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.43536 | 22.68162 | -0.7124 | 18.34592 |
February | 454.00000 | 20.63183 | 20.24459 | -0.6691 | 17.95107 |
March | 514.00000 | 21.37447 | 19.30238 | -0.4438 | 13.85172 |
April | 485.00000 | 21.28303 | 24.38688 | -0.4079 | 14.43594 |
May | 508.00000 | 22.94763 | 26.95668 | -0.8956 | 26.31881 |
June | 496.00000 | 23.97482 | 33.61407 | -0.3578 | 9.60540 |
July | 497.00000 | 24.05935 | 35.77167 | -0.3285 | 9.91264 |
August | 514.00000 | 23.83806 | 34.98707 | -0.4132 | 11.39067 |
September | 485.00000 | 23.33916 | 26.53849 | -0.7132 | 20.33747 |
October | 502.00000 | 21.59782 | 22.17967 | -0.3661 | 12.28591 |
November | 489.00000 | 20.85625 | 23.98510 | -0.5841 | 14.65111 |
December | 497.00000 | 20.16153 | 16.44082 | -0.8421 | 22.85612 |
Annual Sum or Average | 5943.00000 | 22.05517 | 25.63686 | -0.5602 | 15.97701 |
Minimum of Months | 454.00000 | 20.16153 | 16.44082 | -0.8956 | 9.60540 |
Maximum of Months | 514.00000 | 24.05935 | 35.77167 | -0.3285 | 26.31881 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.61616 | 20.94518 | -0.3732 | 14.45168 |
February | 454.00000 | 21.56052 | 19.00225 | -0.4014 | 15.73817 |
March | 514.00000 | 21.70478 | 18.73837 | -0.3461 | 13.73398 |
April | 485.00000 | 21.27848 | 24.20846 | -0.4180 | 14.93636 |
May | 508.00000 | 22.67964 | 27.29992 | -1.0169 | 31.17636 |
June | 496.00000 | 23.64334 | 34.35132 | -0.5380 | 13.71772 |
July | 497.00000 | 23.75538 | 36.32068 | -0.4839 | 12.67937 |
August | 514.00000 | 23.67849 | 35.35246 | -0.4972 | 13.45807 |
September | 485.00000 | 23.40398 | 26.29528 | -0.6744 | 20.57384 |
October | 502.00000 | 22.12438 | 21.26509 | -0.2008 | 13.06931 |
November | 489.00000 | 21.96093 | 22.20913 | -0.2676 | 12.87560 |
December | 497.00000 | 21.15977 | 15.31454 | -0.5420 | 18.31483 |
Annual Sum or Average | 5943.00000 | 22.38841 | 25.16291 | -0.4809 | 16.23787 |
Minimum of Months | 454.00000 | 21.15977 | 15.31454 | -1.0169 | 12.67937 |
Maximum of Months | 514.00000 | 23.75538 | 36.32068 | -0.2008 | 31.17636 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.50456 | 22.37627 | -0.7008 | 18.94189 |
February | 454.00000 | 20.67266 | 20.03447 | -0.6709 | 18.64225 |
March | 514.00000 | 21.13685 | 19.33215 | -0.5050 | 14.99623 |
April | 485.00000 | 21.00622 | 24.61483 | -0.4806 | 15.41426 |
May | 508.00000 | 22.49210 | 27.58175 | -1.0445 | 32.95262 |
June | 496.00000 | 23.53848 | 34.63334 | -0.5087 | 14.76539 |
July | 497.00000 | 23.54606 | 36.87570 | -0.5137 | 14.17728 |
August | 514.00000 | 23.40248 | 36.08457 | -0.5728 | 15.90431 |
September | 485.00000 | 22.86846 | 27.27316 | -0.8687 | 26.70045 |
October | 502.00000 | 21.33278 | 22.34266 | -0.4198 | 13.42792 |
November | 489.00000 | 20.85133 | 23.78502 | -0.5857 | 15.41793 |
December | 497.00000 | 20.23005 | 16.20247 | -0.8325 | 23.16793 |
Annual Sum or Average | 5943.00000 | 21.80957 | 25.97927 | -0.6418 | 18.70861 |
Minimum of Months | 454.00000 | 20.23005 | 16.20247 | -1.0445 | 13.42792 |
Maximum of Months | 514.00000 | 23.54606 | 36.87570 | -0.4198 | 32.95262 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36693 | 22.91141 | -0.7626 | 18.77126 |
February | 454.00000 | 20.37670 | 20.72190 | -0.7867 | 19.49703 |
March | 514.00000 | 20.73170 | 20.13703 | -0.6615 | 15.70967 |
April | 485.00000 | 20.81600 | 25.15885 | -0.5822 | 13.67982 |
May | 508.00000 | 22.21887 | 28.65680 | -1.2491 | 38.95778 |
June | 496.00000 | 23.73435 | 34.63557 | -0.6100 | 13.59349 |
July | 497.00000 | 23.82151 | 36.71996 | -0.5623 | 12.37542 |
August | 514.00000 | 23.76550 | 35.57930 | -0.5919 | 13.09604 |
September | 485.00000 | 23.43090 | 26.76573 | -0.7769 | 19.84060 |
October | 502.00000 | 21.65192 | 22.20487 | -0.3526 | 8.97038 |
November | 489.00000 | 21.00075 | 23.78558 | -0.5423 | 11.96829 |
December | 497.00000 | 20.35755 | 16.41568 | -0.7917 | 19.87603 |
Annual Sum or Average | 5943.00000 | 21.86801 | 26.19118 | -0.6892 | 17.20610 |
Minimum of Months | 454.00000 | 20.35755 | 16.41568 | -1.2491 | 8.97038 |
Maximum of Months | 514.00000 | 23.82151 | 36.71996 | -0.3526 | 38.95778 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.76882 | 22.61347 | -0.6263 | 14.72963 |
February | 454.00000 | 20.83219 | 20.31876 | -0.6262 | 15.83390 |
March | 514.00000 | 21.43260 | 19.58558 | -0.4467 | 12.49309 |
April | 485.00000 | 21.47050 | 24.42381 | -0.3834 | 11.38751 |
May | 508.00000 | 22.96945 | 27.47087 | -0.9457 | 26.72947 |
June | 496.00000 | 24.10691 | 33.54881 | -0.3808 | 9.04265 |
July | 497.00000 | 24.20215 | 35.74623 | -0.3424 | 8.83585 |
August | 514.00000 | 24.13407 | 34.36749 | -0.3551 | 8.85275 |
September | 485.00000 | 23.92800 | 25.75909 | -0.5236 | 13.01318 |
October | 502.00000 | 22.41600 | 21.29341 | -0.1450 | 8.42265 |
November | 489.00000 | 21.52528 | 23.20507 | -0.3873 | 9.90318 |
December | 497.00000 | 20.67135 | 16.24649 | -0.6838 | 16.79413 |
Annual Sum or Average | 5943.00000 | 22.38426 | 25.42817 | -0.4867 | 13.00044 |
Minimum of Months | 454.00000 | 20.67135 | 16.24649 | -0.9457 | 8.42265 |
Maximum of Months | 514.00000 | 24.20215 | 35.74623 | -0.1450 | 26.72947 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.76928 | 20.37981 | -0.2877 | 11.43205 |
February | 454.00000 | 21.38362 | 18.67644 | -0.4024 | 14.34321 |
March | 514.00000 | 21.53479 | 18.74408 | -0.3768 | 12.65258 |
April | 485.00000 | 21.15188 | 24.17384 | -0.4484 | 12.45437 |
May | 508.00000 | 22.38087 | 27.88986 | -1.1592 | 35.55221 |
June | 496.00000 | 23.70366 | 34.04869 | -0.5963 | 13.94630 |
July | 497.00000 | 23.85669 | 36.27672 | -0.5190 | 12.09845 |
August | 514.00000 | 23.96681 | 34.36918 | -0.4467 | 10.72448 |
September | 485.00000 | 23.98627 | 25.13511 | -0.4800 | 13.08450 |
October | 502.00000 | 22.79915 | 20.09337 | 0.00688 | 10.27719 |
November | 489.00000 | 22.39541 | 21.05656 | -0.0967 | 10.10774 |
December | 497.00000 | 21.37764 | 14.56922 | -0.4195 | 14.77283 |
Annual Sum or Average | 5943.00000 | 22.53418 | 24.67356 | -0.4367 | 14.31728 |
Minimum of Months | 454.00000 | 21.15188 | 14.56922 | -1.1592 | 10.10774 |
Maximum of Months | 514.00000 | 23.98627 | 36.27672 | 0.00688 | 35.55221 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78245 | 22.39485 | -0.6236 | 15.19473 |
February | 454.00000 | 20.80006 | 20.20293 | -0.6400 | 16.23823 |
March | 514.00000 | 21.20306 | 19.64796 | -0.5084 | 13.44639 |
April | 485.00000 | 21.16725 | 24.71985 | -0.4634 | 12.29456 |
May | 508.00000 | 22.51653 | 28.07822 | -1.0980 | 33.32325 |
June | 496.00000 | 23.85158 | 34.27100 | -0.4855 | 11.91714 |
July | 497.00000 | 23.84001 | 36.66260 | -0.4918 | 11.64156 |
August | 514.00000 | 23.88811 | 35.19287 | -0.4682 | 11.16589 |
September | 485.00000 | 23.67923 | 26.22782 | -0.6205 | 16.12349 |
October | 502.00000 | 22.15255 | 21.48180 | -0.1972 | 8.61831 |
November | 489.00000 | 21.46060 | 23.11328 | -0.3992 | 10.08092 |
December | 497.00000 | 20.66872 | 16.08945 | -0.6864 | 17.26366 |
Annual Sum or Average | 5943.00000 | 22.17867 | 25.72410 | -0.5569 | 14.78956 |
Minimum of Months | 454.00000 | 20.66872 | 16.08945 | -1.0980 | 8.61831 |
Maximum of Months | 514.00000 | 23.88811 | 36.66260 | -0.1972 | 33.32325 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.51543 | 22.68513 | -0.6841 | 16.73753 |
February | 454.00000 | 20.55472 | 20.42843 | -0.6909 | 16.98317 |
March | 514.00000 | 21.14502 | 19.80912 | -0.5103 | 12.91929 |
April | 485.00000 | 21.27403 | 24.49362 | -0.4331 | 11.66590 |
May | 508.00000 | 22.98582 | 27.25855 | -0.9530 | 26.68019 |
June | 496.00000 | 23.97794 | 33.93380 | -0.4799 | 10.41436 |
July | 497.00000 | 24.03517 | 36.07620 | -0.4478 | 9.90656 |
August | 514.00000 | 23.87598 | 35.36416 | -0.5263 | 11.63043 |
September | 485.00000 | 23.37057 | 26.86111 | -0.7879 | 20.69217 |
October | 502.00000 | 21.58979 | 22.35839 | -0.3676 | 9.73552 |
November | 489.00000 | 20.96001 | 23.93208 | -0.5477 | 12.48132 |
December | 497.00000 | 20.30427 | 16.43649 | -0.7899 | 20.31132 |
Annual Sum or Average | 5943.00000 | 22.06261 | 25.85101 | -0.6010 | 15.00131 |
Minimum of Months | 454.00000 | 20.30427 | 16.43649 | -0.9530 | 9.73552 |
Maximum of Months | 514.00000 | 24.03517 | 36.07620 | -0.3676 | 26.68019 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.79737 | 22.25392 | -0.5923 | 14.51520 |
February | 385.00000 | 20.92265 | 19.91608 | -0.5687 | 15.48877 |
March | 433.00000 | 21.52498 | 19.09976 | -0.3829 | 12.31293 |
April | 410.00000 | 21.51874 | 24.06544 | -0.3361 | 11.75056 |
May | 430.00000 | 23.15817 | 26.87262 | -0.8299 | 23.36183 |
June | 418.00000 | 24.04961 | 33.44533 | -0.3622 | 9.42505 |
July | 422.00000 | 24.16700 | 35.53553 | -0.3224 | 9.53137 |
August | 433.00000 | 23.93902 | 34.89420 | -0.4082 | 10.84758 |
September | 410.00000 | 23.50418 | 26.28208 | -0.6640 | 18.10795 |
October | 427.00000 | 21.91498 | 21.65588 | -0.2617 | 10.07719 |
November | 417.00000 | 21.24012 | 23.41563 | -0.4571 | 11.44993 |
December | 422.00000 | 20.45912 | 16.13849 | -0.7298 | 18.92732 |
Annual Sum or Average | 5034.00000 | 22.27628 | 25.33674 | -0.4925 | 13.80693 |
Minimum of Months | 385.00000 | 20.45912 | 16.13849 | -0.8299 | 9.42505 |
Maximum of Months | 433.00000 | 24.16700 | 35.53553 | -0.2617 | 23.36183 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.19521 | 20.40693 | -0.2004 | 11.28332 |
February | 454.00000 | 22.02858 | 18.58949 | -0.2562 | 13.01952 |
March | 514.00000 | 22.11071 | 18.56413 | -0.2245 | 11.39711 |
April | 485.00000 | 21.77984 | 23.66817 | -0.2846 | 11.17952 |
May | 508.00000 | 23.17162 | 26.80647 | -0.8640 | 24.18960 |
June | 496.00000 | 23.95476 | 33.88888 | -0.4642 | 10.74789 |
July | 497.00000 | 24.07269 | 35.87953 | -0.4068 | 9.87110 |
August | 514.00000 | 24.02545 | 34.77978 | -0.4057 | 10.14287 |
September | 485.00000 | 23.84682 | 25.76707 | -0.5328 | 14.97028 |
October | 502.00000 | 22.67687 | 20.61988 | -0.0424 | 10.58202 |
November | 489.00000 | 22.51845 | 21.55071 | -0.0984 | 10.37312 |
December | 497.00000 | 21.75237 | 14.96657 | -0.3634 | 14.10725 |
Annual Sum or Average | 5943.00000 | 22.85193 | 24.67867 | -0.3464 | 12.66203 |
Minimum of Months | 454.00000 | 21.75237 | 14.96657 | -0.8640 | 9.87110 |
Maximum of Months | 514.00000 | 24.07269 | 35.87953 | -0.0424 | 24.18960 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87427 | 21.99265 | -0.5683 | 14.58235 |
February | 454.00000 | 20.96053 | 19.75552 | -0.5604 | 15.23029 |
March | 514.00000 | 21.38123 | 19.27729 | -0.4142 | 12.48590 |
April | 485.00000 | 21.36102 | 24.18623 | -0.3751 | 11.80915 |
May | 508.00000 | 22.82468 | 27.25067 | -0.9322 | 27.58260 |
June | 496.00000 | 23.77565 | 34.29793 | -0.4529 | 12.13174 |
July | 497.00000 | 23.77854 | 36.59757 | -0.4572 | 11.64530 |
August | 514.00000 | 23.68468 | 35.65122 | -0.4971 | 12.71721 |
September | 485.00000 | 23.23613 | 26.85869 | -0.7459 | 21.19660 |
October | 502.00000 | 21.74361 | 21.84499 | -0.2879 | 10.22808 |
November | 489.00000 | 21.26323 | 23.24152 | -0.4446 | 11.40811 |
December | 497.00000 | 20.57147 | 15.97330 | -0.7015 | 18.42383 |
Annual Sum or Average | 5943.00000 | 22.13210 | 25.62906 | -0.5364 | 14.95605 |
Minimum of Months | 454.00000 | 20.57147 | 15.97330 | -0.9322 | 10.22808 |
Maximum of Months | 514.00000 | 23.77854 | 36.59757 | -0.2879 | 27.58260 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.452259E+11 | 0.00 | 416.47 | 352652.10 | 23-JAN-06:11 | 0.00 | 31.69 | 46.99 | 0.19 | 0.00 | 0.04 | 0.78 | 23-JAN-06:11 |
February | 0.470797E+11 | 0.00 | 410.57 | 282924.70 | 22-FEB-06:01 | 0.00 | 31.08 | 47.42 | 0.23 | 0.00 | 0.04 | 0.62 | 22-FEB-06:01 |
March | 0.323950E+11 | 0.00 | 381.07 | 306185.45 | 30-MAR-05:01 | 0.00 | 31.69 | 45.55 | 0.13 | 0.00 | 0.03 | 0.67 | 30-MAR-05:01 |
April | 0.221245E+11 | 0.00 | 313.57 | 320433.38 | 26-APR-05:11 | 0.00 | 30.09 | 42.26 | 0.09 | 0.00 | 0.02 | 0.71 | 26-APR-05:11 |
May | 0.358781E+10 | 0.00 | 109.64 | 379731.22 | 01-MAY-05:11 | 0.00 | 35.20 | 38.82 | 0.01 | 0.00 | 0.00 | 0.84 | 01-MAY-05:11 |
June | 42576890.23 | 0.00 | 45.08 | 15216.28 | 09-JUN-06:10 | 0.00 | 34.69 | 36.26 | 0.00 | 0.00 | 0.00 | 0.03 | 09-JUN-06:10 |
July | 23823667.74 | 0.00 | 71.07 | 14259.29 | 03-JUL-06:07 | 0.00 | 35.16 | 37.59 | 0.00 | 0.00 | 0.00 | 0.03 | 03-JUL-06:07 |
August | 36016003.56 | 0.00 | 54.11 | 14877.14 | 23-AUG-06:03 | 0.00 | 31.90 | 33.95 | 0.00 | 0.00 | 0.00 | 0.03 | 23-AUG-06:03 |
September | 0.106027E+10 | 0.00 | 53.29 | 216523.08 | 22-SEP-06:03 | 0.00 | 26.93 | 29.27 | 0.00 | 0.00 | 0.00 | 0.48 | 22-SEP-06:03 |
October | 0.220339E+11 | 0.00 | 266.75 | 259258.06 | 24-OCT-05:01 | 0.00 | 28.82 | 38.92 | 0.09 | 0.00 | 0.02 | 0.57 | 24-OCT-05:01 |
November | 0.314993E+11 | 0.00 | 336.89 | 287640.33 | 25-NOV-06:11 | 0.00 | 28.56 | 42.21 | 0.13 | 0.00 | 0.03 | 0.63 | 25-NOV-06:11 |
December | 0.673920E+11 | 0.00 | 469.29 | 312554.67 | 29-DEC-06:01 | 0.00 | 32.34 | 48.54 | 0.32 | 0.00 | 0.06 | 0.69 | 29-DEC-06:01 |
Annual Sum or Average | 0.272501E+12 | 0.00 | 2927.81 | 0.00 | 31.53 | 40.63 | 0.10 | 0.00 | 0.02 | ||||
Minimum of Months | 23823667.74 | 0.00 | 45.08 | 14259.29 | 0.00 | 26.93 | 29.27 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.673920E+11 | 0.00 | 469.29 | 379731.22 | 0.00 | 35.20 | 48.54 | 0.32 | 0.00 | 0.06 | 0.84 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.111256E+10 | 0.286833E+09 | 29.50 | 0.111184E+10 | 720677.39 | 0.00 | 0.71 | 20-JAN-14:00 | 0.00 | 01-JAN-00:05 | 26572.77 | 20-JAN-14:00 | 26572.77 | 20-JAN-14:00 | 127.48 | 19-JAN-12:20 | 6396.17 | 20-JAN-14:00 | 0.00 |
February | 0.377573E+09 | 0.100679E+09 | 13.24 | 0.377566E+09 | 7389.16 | 0.00 | 0.48 | 18-FEB-13:30 | 0.00 | 01-FEB-00:10 | 16970.70 | 18-FEB-13:30 | 16970.70 | 18-FEB-13:30 | 8.69 | 17-FEB-15:30 | 4341.03 | 18-FEB-13:30 | 0.00 |
March | 0.382367E+10 | 0.945465E+09 | 78.98 | 0.382321E+10 | 461095.65 | 0.00 | 1.00 | 13-MAR-14:30 | 0.00 | 01-MAR-00:10 | 44918.75 | 14-MAR-13:00 | 44918.75 | 14-MAR-13:00 | 319.35 | 31-MAR-17:50 | 10011.57 | 14-MAR-13:00 | 0.00 |
April | 0.368004E+10 | 0.949613E+09 | 91.08 | 0.362747E+10 | 52571682.60 | 0.00 | 0.72 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 27060.95 | 20-APR-13:00 | 27060.95 | 20-APR-13:00 | 4207.54 | 28-APR-14:00 | 6494.20 | 20-APR-13:00 | 0.00 |
May | 0.168145E+11 | 0.411212E+10 | 223.36 | 0.163974E+11 | 0.417089E+09 | 0.00 | 1.00 | 10-MAY-14:00 | 0.00 | 01-MAY-00:10 | 52025.47 | 17-MAY-14:10 | 52025.47 | 17-MAY-14:10 | 4448.01 | 31-MAY-07:35 | 13044.99 | 17-MAY-14:10 | 0.00 |
June | 0.609273E+11 | 0.156048E+11 | 423.10 | 0.579136E+11 | 0.301378E+10 | 0.00 | 1.00 | 01-JUN-10:30 | 0.00 | 01-JUN-00:10 | 80892.46 | 26-JUN-15:00 | 80892.46 | 26-JUN-15:00 | 19464.26 | 22-JUN-13:20 | 27959.55 | 26-JUN-15:00 | 0.00 |
July | 0.628736E+11 | 0.158527E+11 | 423.61 | 0.578928E+11 | 0.498074E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 78511.63 | 17-JUL-14:10 | 78511.63 | 17-JUL-14:10 | 35408.10 | 31-JUL-15:50 | 23836.15 | 17-JUL-13:30 | 0.00 |
August | 0.629287E+11 | 0.158411E+11 | 429.92 | 0.596531E+11 | 0.327560E+10 | 0.00 | 1.00 | 02-AUG-09:40 | 0.00 | 01-AUG-00:10 | 82967.15 | 16-AUG-15:40 | 82967.15 | 16-AUG-15:40 | 29352.12 | 04-AUG-05:12 | 26348.15 | 16-AUG-15:50 | 0.00 |
September | 0.441745E+11 | 0.107931E+11 | 358.79 | 0.436530E+11 | 0.521517E+09 | 0.00 | 1.00 | 01-SEP-10:05 | 0.00 | 01-SEP-00:10 | 77330.69 | 12-SEP-16:00 | 77330.69 | 12-SEP-16:00 | 9345.29 | 01-SEP-14:00 | 20746.16 | 12-SEP-16:00 | 0.00 |
October | 0.802706E+10 | 0.194948E+10 | 117.71 | 0.801297E+10 | 14094627.57 | 0.00 | 1.00 | 09-OCT-15:52 | 0.00 | 01-OCT-00:10 | 62700.04 | 11-OCT-15:40 | 62700.04 | 11-OCT-15:40 | 944.11 | 09-OCT-10:34 | 14771.28 | 11-OCT-14:10 | 0.00 |
November | 0.254425E+10 | 0.630142E+09 | 45.67 | 0.254414E+10 | 109569.58 | 0.00 | 0.97 | 07-NOV-15:03 | 0.00 | 01-NOV-00:10 | 38807.42 | 07-NOV-15:03 | 38807.42 | 07-NOV-15:03 | 96.55 | 09-NOV-08:50 | 8688.00 | 07-NOV-15:03 | 0.00 |
December | 0.134827E+10 | 0.347493E+09 | 33.63 | 0.134826E+10 | 2081.69 | 0.00 | 0.74 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 27797.62 | 01-DEC-14:00 | 27797.62 | 01-DEC-14:00 | 3.47 | 03-DEC-16:03 | 6641.02 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.268632E+12 | 0.674135E+11 | 2268.59 | 0.256355E+12 | 0.122767E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.377573E+09 | 0.100679E+09 | 13.24 | 0.377566E+09 | 2081.69 | 0.00 | 0.48 | 0.00 | 16970.70 | 16970.70 | 3.47 | 4341.03 | 0.00 | ||||||
Maximum of Months | 0.629287E+11 | 0.158527E+11 | 429.92 | 0.596531E+11 | 0.498074E+10 | 0.00 | 1.00 | 0.00 | 82967.15 | 82967.15 | 35408.10 | 27959.55 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.112677E+10 | 0.288799E+09 | 29.27 | 0.112627E+10 | 494933.91 | 0.00 | 0.83 | 20-JAN-13:02 | 0.00 | 01-JAN-00:05 | 30481.56 | 20-JAN-13:02 | 30481.56 | 20-JAN-13:02 | 472.36 | 11-JAN-13:01 | 7109.90 | 20-JAN-13:02 | 0.00 |
February | 0.408776E+09 | 0.108539E+09 | 14.27 | 0.408761E+09 | 14535.70 | 0.00 | 0.58 | 26-FEB-13:12 | 0.00 | 01-FEB-00:10 | 20161.68 | 26-FEB-13:12 | 20161.68 | 26-FEB-13:12 | 10.67 | 17-FEB-15:30 | 5024.57 | 26-FEB-13:12 | 0.00 |
March | 0.370992E+10 | 0.919014E+09 | 81.17 | 0.370942E+10 | 497035.22 | 0.00 | 1.00 | 13-MAR-15:20 | 0.00 | 01-MAR-00:10 | 42533.81 | 14-MAR-13:00 | 42533.81 | 14-MAR-13:00 | 278.74 | 31-MAR-17:50 | 9480.22 | 14-MAR-13:00 | 0.00 |
April | 0.343911E+10 | 0.889202E+09 | 90.69 | 0.339022E+10 | 48882758.93 | 0.00 | 0.76 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 27543.01 | 20-APR-13:00 | 27543.01 | 20-APR-13:00 | 3830.06 | 28-APR-14:00 | 6543.81 | 20-APR-13:00 | 0.00 |
May | 0.159029E+11 | 0.390339E+10 | 229.23 | 0.154703E+11 | 0.432624E+09 | 0.00 | 1.00 | 10-MAY-13:00 | 0.00 | 01-MAY-00:10 | 53411.47 | 17-MAY-14:05 | 53411.47 | 17-MAY-14:05 | 4152.94 | 31-MAY-07:50 | 13390.56 | 17-MAY-14:05 | 0.00 |
June | 0.573313E+11 | 0.147399E+11 | 429.88 | 0.544348E+11 | 0.289657E+10 | 0.00 | 1.00 | 01-JUN-10:30 | 0.00 | 01-JUN-00:10 | 79835.03 | 26-JUN-15:00 | 79835.03 | 26-JUN-15:00 | 19403.86 | 22-JUN-13:20 | 27591.26 | 26-JUN-15:00 | 0.00 |
July | 0.586128E+11 | 0.148576E+11 | 431.30 | 0.539643E+11 | 0.464845E+10 | 0.00 | 1.00 | 01-JUL-08:00 | 0.00 | 01-JUL-00:10 | 77411.80 | 17-JUL-14:05 | 77411.80 | 17-JUL-14:05 | 33949.53 | 31-JUL-15:50 | 23444.14 | 17-JUL-13:00 | 0.00 |
August | 0.560198E+11 | 0.141799E+11 | 429.38 | 0.529814E+11 | 0.303839E+10 | 0.00 | 1.00 | 02-AUG-09:50 | 0.00 | 01-AUG-00:10 | 77523.88 | 16-AUG-14:05 | 77523.88 | 16-AUG-14:05 | 20028.12 | 21-AUG-16:00 | 24725.77 | 16-AUG-14:05 | 0.00 |
September | 0.372350E+11 | 0.917874E+10 | 354.05 | 0.367132E+11 | 0.521839E+09 | 0.00 | 1.00 | 01-SEP-10:05 | 0.00 | 01-SEP-00:10 | 68296.01 | 12-SEP-16:00 | 68296.01 | 12-SEP-16:00 | 8468.12 | 01-SEP-14:00 | 18326.93 | 12-SEP-16:00 | 0.00 |
October | 0.682988E+10 | 0.167741E+10 | 116.04 | 0.681600E+10 | 13880703.15 | 0.00 | 1.00 | 10-OCT-12:05 | 0.00 | 01-OCT-00:10 | 55605.75 | 11-OCT-15:10 | 55605.75 | 11-OCT-15:10 | 802.90 | 09-OCT-10:26 | 13243.54 | 11-OCT-14:05 | 0.00 |
November | 0.220932E+10 | 0.554401E+09 | 44.96 | 0.220870E+10 | 618772.44 | 0.00 | 0.89 | 07-NOV-14:00 | 0.00 | 01-NOV-00:10 | 33537.34 | 07-NOV-14:00 | 33537.34 | 07-NOV-14:00 | 267.01 | 09-NOV-08:55 | 7677.07 | 07-NOV-14:00 | 0.00 |
December | 0.125302E+10 | 0.323910E+09 | 33.02 | 0.125302E+10 | -0.0 | 0.00 | 0.76 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 27316.62 | 01-DEC-14:00 | 27316.62 | 01-DEC-14:00 | 0.00 | 01-DEC-13:40 | 6499.33 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.244079E+12 | 0.616208E+11 | 2283.26 | 0.232476E+12 | 0.116023E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.408776E+09 | 0.108539E+09 | 14.27 | 0.408761E+09 | -0.0 | 0.00 | 0.58 | 0.00 | 20161.68 | 20161.68 | 0.00 | 5024.57 | 0.00 | ||||||
Maximum of Months | 0.586128E+11 | 0.148576E+11 | 431.30 | 0.544348E+11 | 0.464845E+10 | 0.00 | 1.00 | 0.00 | 79835.03 | 79835.03 | 33949.53 | 27591.26 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.106717E+10 | 0.282285E+09 | 28.25 | 0.106616E+10 | 1009314.19 | 0.00 | 0.56 | 20-JAN-13:30 | 0.00 | 01-JAN-00:05 | 26308.23 | 20-JAN-13:30 | 26308.23 | 20-JAN-13:30 | 128.06 | 18-JAN-14:40 | 6592.95 | 20-JAN-13:30 | 0.00 |
February | 0.419302E+09 | 0.112760E+09 | 13.86 | 0.418757E+09 | 545834.24 | 0.00 | 0.44 | 18-FEB-13:30 | 0.00 | 01-FEB-00:10 | 19783.61 | 18-FEB-13:30 | 19783.61 | 18-FEB-13:30 | 92.85 | 17-FEB-15:00 | 5121.52 | 18-FEB-13:30 | 0.00 |
March | 0.379475E+10 | 0.969710E+09 | 79.31 | 0.379321E+10 | 1537161.86 | 0.00 | 1.00 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 52808.80 | 14-MAR-13:00 | 52808.80 | 14-MAR-13:00 | 458.04 | 31-MAR-17:50 | 11772.18 | 14-MAR-13:00 | 0.00 |
April | 0.385083E+10 | 0.101220E+10 | 89.63 | 0.377490E+10 | 75931239.79 | 0.00 | 0.65 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 30961.67 | 20-APR-13:00 | 30961.67 | 20-APR-13:00 | 4759.30 | 28-APR-14:00 | 7586.22 | 20-APR-13:00 | 0.00 |
May | 0.187273E+11 | 0.466959E+10 | 226.57 | 0.180068E+11 | 0.720478E+09 | 0.00 | 1.00 | 10-MAY-15:20 | 0.00 | 01-MAY-00:10 | 68995.09 | 31-MAY-15:00 | 68995.09 | 31-MAY-15:00 | 5750.86 | 30-MAY-17:00 | 16989.58 | 31-MAY-15:00 | 0.00 |
June | 0.679317E+11 | 0.177054E+11 | 429.35 | 0.643135E+11 | 0.361820E+10 | 0.00 | 1.00 | 01-JUN-10:50 | 0.00 | 01-JUN-00:10 | 100077.96 | 26-JUN-15:00 | 100077.96 | 26-JUN-15:00 | 21951.16 | 22-JUN-13:05 | 34597.25 | 26-JUN-15:00 | 0.00 |
July | 0.683267E+11 | 0.176143E+11 | 431.46 | 0.629342E+11 | 0.539247E+10 | 0.00 | 1.00 | 01-JUL-13:10 | 0.00 | 01-JUL-00:10 | 92773.68 | 17-JUL-13:40 | 92773.68 | 17-JUL-13:40 | 35798.43 | 31-JUL-15:40 | 28366.62 | 17-JUL-13:30 | 0.00 |
August | 0.649130E+11 | 0.166922E+11 | 427.04 | 0.612135E+11 | 0.369952E+10 | 0.00 | 1.00 | 02-AUG-10:05 | 0.00 | 01-AUG-00:10 | 97227.22 | 16-AUG-14:30 | 97227.22 | 16-AUG-14:30 | 22322.09 | 05-AUG-14:50 | 31132.20 | 16-AUG-14:00 | 0.00 |
September | 0.410990E+11 | 0.103403E+11 | 349.87 | 0.402265E+11 | 0.872527E+09 | 0.00 | 1.00 | 01-SEP-11:50 | 0.00 | 01-SEP-00:10 | 78801.75 | 12-SEP-14:00 | 78801.75 | 12-SEP-14:00 | 10683.68 | 01-SEP-14:00 | 20901.79 | 12-SEP-16:00 | 0.00 |
October | 0.691184E+10 | 0.174047E+10 | 111.12 | 0.688019E+10 | 31653547.31 | 0.00 | 1.00 | 10-OCT-13:03 | 0.00 | 01-OCT-00:10 | 65320.80 | 11-OCT-14:30 | 65320.80 | 11-OCT-14:30 | 1244.80 | 09-OCT-10:50 | 15600.98 | 11-OCT-14:00 | 0.00 |
November | 0.203913E+10 | 0.531117E+09 | 42.68 | 0.203440E+10 | 4728558.69 | 0.00 | 0.67 | 07-NOV-14:40 | 0.00 | 01-NOV-00:10 | 31984.79 | 07-NOV-14:40 | 31984.79 | 07-NOV-14:40 | 678.60 | 09-NOV-09:25 | 7798.69 | 07-NOV-14:40 | 0.00 |
December | 0.131558E+10 | 0.346535E+09 | 31.76 | 0.131546E+10 | 121015.58 | 0.00 | 0.59 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 27934.97 | 01-DEC-14:00 | 27934.97 | 01-DEC-14:00 | 55.24 | 31-DEC-24:00 | 6945.28 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.280396E+12 | 0.720168E+11 | 2260.92 | 0.265978E+12 | 0.144187E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.419302E+09 | 0.112760E+09 | 13.86 | 0.418757E+09 | 121015.58 | 0.00 | 0.44 | 0.00 | 19783.61 | 19783.61 | 55.24 | 5121.52 | 0.00 | ||||||
Maximum of Months | 0.683267E+11 | 0.177054E+11 | 431.46 | 0.643135E+11 | 0.539247E+10 | 0.00 | 1.00 | 0.00 | 100077.96 | 100077.96 | 35798.43 | 34597.25 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.46 | 0.00 | 376.46 | 43.42 | 2429.01 | 0.00 | 0.00 | 0.00 |
February | 473.17 | 0.00 | 473.17 | 52.54 | 2519.03 | 0.00 | 0.00 | 0.00 |
March | 643.82 | 0.00 | 643.82 | 211.15 | 1895.16 | 0.00 | 0.00 | 0.00 |
April | 808.55 | 4.49 | 804.06 | 342.15 | 1608.35 | 0.00 | 0.00 | 0.00 |
May | 1104.52 | 36.51 | 1068.01 | 887.80 | 920.18 | 0.00 | 0.00 | 0.00 |
June | 1211.19 | 134.28 | 1076.91 | 1600.14 | 511.75 | 0.00 | 0.00 | 0.00 |
July | 1145.45 | 74.15 | 1071.31 | 1546.24 | 486.99 | 0.00 | 0.00 | 0.00 |
August | 911.70 | 21.57 | 890.13 | 1165.52 | 555.51 | 0.00 | 0.00 | 0.00 |
September | 765.82 | 0.18 | 765.64 | 852.56 | 837.02 | 0.00 | 0.00 | 0.00 |
October | 548.51 | 0.00 | 548.51 | 248.78 | 1794.52 | 0.00 | 0.00 | 0.00 |
November | 416.39 | 0.00 | 416.39 | 84.03 | 2189.85 | 0.00 | 0.00 | 0.00 |
December | 352.23 | 0.00 | 352.23 | 44.61 | 2771.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 731.15 | 22.65 | 708.50 | 592.91 | 1538.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 352.23 | 0.00 | 352.23 | 43.42 | 486.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1211.19 | 134.28 | 1076.91 | 1600.14 | 2771.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 785.86 | 481.60 | 304.26 | 629.56 | 1490.57 | 0.00 | 0.00 | 0.00 |
February | 1043.93 | 659.03 | 384.90 | 898.92 | 1575.99 | 0.00 | 0.00 | 0.00 |
March | 1260.00 | 734.94 | 525.05 | 1177.25 | 1197.52 | 0.00 | 0.00 | 0.00 |
April | 1292.19 | 629.45 | 662.75 | 1176.61 | 1033.25 | 0.00 | 0.00 | 0.00 |
May | 1510.55 | 630.96 | 879.59 | 1611.87 | 616.86 | 0.00 | 0.00 | 0.00 |
June | 1843.03 | 967.54 | 875.49 | 2455.75 | 343.98 | 0.00 | 0.00 | 0.00 |
July | 1675.46 | 797.81 | 877.65 | 2262.44 | 329.02 | 0.00 | 0.00 | 0.00 |
August | 1689.93 | 930.75 | 759.18 | 2257.82 | 372.34 | 0.00 | 0.00 | 0.00 |
September | 1406.11 | 763.83 | 642.28 | 1760.83 | 538.38 | 0.00 | 0.00 | 0.00 |
October | 1018.30 | 557.97 | 460.34 | 1003.44 | 1164.18 | 0.00 | 0.00 | 0.00 |
November | 792.62 | 447.52 | 345.10 | 681.46 | 1387.57 | 0.00 | 0.00 | 0.00 |
December | 686.20 | 395.30 | 290.90 | 521.91 | 1728.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1251.13 | 666.06 | 585.08 | 1372.06 | 978.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.20 | 395.30 | 290.90 | 521.91 | 329.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1843.03 | 967.54 | 879.59 | 2455.75 | 1728.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3607.85 | 2967.84 | 640.01 | 3907.24 | 2117.16 | 0.00 | 0.00 | 0.00 |
February | 3460.60 | 2759.00 | 701.60 | 3667.78 | 2254.64 | 0.00 | 0.00 | 0.00 |
March | 2551.43 | 1678.69 | 872.74 | 2756.28 | 1825.88 | 0.00 | 0.00 | 0.00 |
April | 1652.50 | 664.47 | 988.03 | 1590.51 | 1641.98 | 0.00 | 0.00 | 0.00 |
May | 1514.33 | 277.56 | 1236.77 | 1620.82 | 1018.12 | 0.00 | 0.00 | 0.00 |
June | 1396.17 | 255.18 | 1140.99 | 2018.68 | 568.55 | 0.00 | 0.00 | 0.00 |
July | 1453.38 | 260.26 | 1193.12 | 2118.03 | 531.86 | 0.00 | 0.00 | 0.00 |
August | 1850.44 | 773.55 | 1076.89 | 2684.96 | 593.06 | 0.00 | 0.00 | 0.00 |
September | 2380.77 | 1328.45 | 1052.32 | 3205.76 | 874.88 | 0.00 | 0.00 | 0.00 |
October | 2846.70 | 2019.79 | 826.91 | 3328.05 | 1769.59 | 0.00 | 0.00 | 0.00 |
November | 3468.30 | 2764.73 | 703.57 | 3863.91 | 2026.65 | 0.00 | 0.00 | 0.00 |
December | 3316.60 | 2684.41 | 632.19 | 3505.48 | 2426.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2452.58 | 1529.21 | 923.37 | 2850.99 | 1466.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1396.17 | 255.18 | 632.19 | 1590.51 | 531.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3607.85 | 2967.84 | 1236.77 | 3907.24 | 2426.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.98 | 529.72 | 306.26 | 735.03 | 1530.13 | 0.00 | 0.00 | 0.00 |
February | 1008.08 | 624.71 | 383.37 | 870.96 | 1597.31 | 0.00 | 0.00 | 0.00 |
March | 1180.39 | 651.25 | 529.15 | 1101.81 | 1229.40 | 0.00 | 0.00 | 0.00 |
April | 1111.40 | 470.54 | 640.85 | 978.57 | 1061.43 | 0.00 | 0.00 | 0.00 |
May | 1358.41 | 478.89 | 879.52 | 1468.42 | 656.77 | 0.00 | 0.00 | 0.00 |
June | 1661.42 | 799.37 | 862.05 | 2273.79 | 388.35 | 0.00 | 0.00 | 0.00 |
July | 1353.66 | 495.82 | 857.85 | 1864.26 | 355.39 | 0.00 | 0.00 | 0.00 |
August | 1412.84 | 697.96 | 714.88 | 1907.97 | 393.54 | 0.00 | 0.00 | 0.00 |
September | 1252.77 | 600.78 | 651.98 | 1602.85 | 577.22 | 0.00 | 0.00 | 0.00 |
October | 1053.91 | 602.38 | 451.52 | 1093.93 | 1187.12 | 0.00 | 0.00 | 0.00 |
November | 864.79 | 525.03 | 339.76 | 789.81 | 1407.38 | 0.00 | 0.00 | 0.00 |
December | 698.51 | 412.63 | 285.88 | 553.57 | 1737.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1149.71 | 573.40 | 576.30 | 1271.81 | 1006.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 698.51 | 412.63 | 285.88 | 553.57 | 355.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1661.42 | 799.37 | 879.52 | 2273.79 | 1737.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.48 | 0.00 | 125.48 | 15.35 | 831.94 | 0.00 | 0.00 | 0.00 |
February | 157.72 | 0.00 | 157.72 | 19.05 | 848.07 | 0.00 | 0.00 | 0.00 |
March | 214.60 | 0.00 | 214.60 | 80.50 | 631.63 | 0.00 | 0.00 | 0.00 |
April | 269.51 | 1.50 | 268.01 | 128.40 | 548.44 | 0.00 | 0.00 | 0.00 |
May | 368.16 | 12.17 | 355.99 | 317.59 | 301.57 | 0.00 | 0.00 | 0.00 |
June | 403.71 | 44.76 | 358.96 | 547.24 | 168.20 | 0.00 | 0.00 | 0.00 |
July | 381.80 | 24.71 | 357.09 | 527.16 | 159.87 | 0.00 | 0.00 | 0.00 |
August | 303.89 | 7.19 | 296.70 | 393.08 | 191.98 | 0.00 | 0.00 | 0.00 |
September | 255.26 | 0.06 | 255.20 | 279.91 | 306.45 | 0.00 | 0.00 | 0.00 |
October | 182.83 | 0.00 | 182.83 | 78.91 | 649.95 | 0.00 | 0.00 | 0.00 |
November | 138.79 | 0.00 | 138.79 | 25.76 | 784.09 | 0.00 | 0.00 | 0.00 |
December | 117.40 | 0.00 | 117.40 | 13.60 | 964.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.71 | 7.55 | 236.16 | 203.24 | 530.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 117.40 | 0.00 | 117.40 | 13.60 | 159.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.71 | 44.76 | 358.96 | 547.24 | 964.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.49 | 0.00 | 125.49 | 15.35 | 831.99 | 0.00 | 0.00 | 0.00 |
February | 157.72 | 0.00 | 157.72 | 19.05 | 848.12 | 0.00 | 0.00 | 0.00 |
March | 214.61 | 0.00 | 214.61 | 80.50 | 631.67 | 0.00 | 0.00 | 0.00 |
April | 269.52 | 1.50 | 268.02 | 128.40 | 548.47 | 0.00 | 0.00 | 0.00 |
May | 368.18 | 12.17 | 356.01 | 317.60 | 301.58 | 0.00 | 0.00 | 0.00 |
June | 403.73 | 44.76 | 358.97 | 547.27 | 168.21 | 0.00 | 0.00 | 0.00 |
July | 381.82 | 24.72 | 357.11 | 527.19 | 159.88 | 0.00 | 0.00 | 0.00 |
August | 303.90 | 7.19 | 296.71 | 393.10 | 191.99 | 0.00 | 0.00 | 0.00 |
September | 255.28 | 0.06 | 255.22 | 279.92 | 306.46 | 0.00 | 0.00 | 0.00 |
October | 182.84 | 0.00 | 182.84 | 78.91 | 649.99 | 0.00 | 0.00 | 0.00 |
November | 138.80 | 0.00 | 138.80 | 25.76 | 784.14 | 0.00 | 0.00 | 0.00 |
December | 117.41 | 0.00 | 117.41 | 13.60 | 964.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.72 | 7.55 | 236.17 | 203.25 | 530.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 117.41 | 0.00 | 117.41 | 13.60 | 159.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.73 | 44.76 | 358.97 | 547.27 | 964.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.49 | 0.00 | 125.49 | 15.35 | 831.99 | 0.00 | 0.00 | 0.00 |
February | 157.72 | 0.00 | 157.72 | 19.05 | 848.12 | 0.00 | 0.00 | 0.00 |
March | 214.61 | 0.00 | 214.61 | 80.50 | 631.67 | 0.00 | 0.00 | 0.00 |
April | 269.52 | 1.50 | 268.02 | 128.40 | 548.47 | 0.00 | 0.00 | 0.00 |
May | 368.18 | 12.17 | 356.01 | 317.60 | 301.58 | 0.00 | 0.00 | 0.00 |
June | 403.73 | 44.76 | 358.97 | 547.27 | 168.21 | 0.00 | 0.00 | 0.00 |
July | 381.82 | 24.72 | 357.11 | 527.19 | 159.88 | 0.00 | 0.00 | 0.00 |
August | 303.90 | 7.19 | 296.71 | 393.10 | 191.99 | 0.00 | 0.00 | 0.00 |
September | 255.28 | 0.06 | 255.22 | 279.92 | 306.46 | 0.00 | 0.00 | 0.00 |
October | 182.84 | 0.00 | 182.84 | 78.91 | 649.99 | 0.00 | 0.00 | 0.00 |
November | 138.80 | 0.00 | 138.80 | 25.76 | 784.14 | 0.00 | 0.00 | 0.00 |
December | 117.41 | 0.00 | 117.41 | 13.60 | 964.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.72 | 7.55 | 236.17 | 203.25 | 530.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 117.41 | 0.00 | 117.41 | 13.60 | 159.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.73 | 44.76 | 358.97 | 547.27 | 964.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 756.00 | 463.30 | 292.70 | 605.52 | 1493.19 | 0.00 | 0.00 | 0.00 |
February | 1004.26 | 633.99 | 370.27 | 873.99 | 1551.92 | 0.00 | 0.00 | 0.00 |
March | 1212.11 | 707.02 | 505.10 | 1156.34 | 1176.96 | 0.00 | 0.00 | 0.00 |
April | 1243.09 | 605.53 | 637.56 | 1160.52 | 1041.11 | 0.00 | 0.00 | 0.00 |
May | 1453.15 | 606.99 | 846.16 | 1585.23 | 601.01 | 0.00 | 0.00 | 0.00 |
June | 1772.99 | 930.77 | 842.22 | 2389.31 | 342.03 | 0.00 | 0.00 | 0.00 |
July | 1611.79 | 767.50 | 844.30 | 2200.11 | 326.47 | 0.00 | 0.00 | 0.00 |
August | 1625.71 | 895.38 | 730.33 | 2184.28 | 390.18 | 0.00 | 0.00 | 0.00 |
September | 1352.68 | 734.81 | 617.86 | 1687.43 | 585.26 | 0.00 | 0.00 | 0.00 |
October | 979.61 | 536.77 | 442.84 | 954.14 | 1239.65 | 0.00 | 0.00 | 0.00 |
November | 762.50 | 430.51 | 331.98 | 642.83 | 1448.89 | 0.00 | 0.00 | 0.00 |
December | 660.12 | 380.28 | 279.84 | 495.96 | 1751.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1203.59 | 640.75 | 562.84 | 1330.15 | 992.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 660.12 | 380.28 | 279.84 | 495.96 | 326.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1772.99 | 930.77 | 846.16 | 2389.31 | 1751.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.89 | 18.32 | 11.57 | 23.94 | 59.04 | 0.00 | 0.00 | 0.00 |
February | 39.71 | 25.07 | 14.64 | 34.56 | 61.36 | 0.00 | 0.00 | 0.00 |
March | 47.93 | 27.95 | 19.97 | 45.72 | 46.54 | 0.00 | 0.00 | 0.00 |
April | 49.15 | 23.94 | 25.21 | 45.89 | 41.16 | 0.00 | 0.00 | 0.00 |
May | 57.46 | 24.00 | 33.46 | 62.68 | 23.76 | 0.00 | 0.00 | 0.00 |
June | 70.10 | 36.80 | 33.30 | 94.47 | 13.52 | 0.00 | 0.00 | 0.00 |
July | 63.73 | 30.35 | 33.38 | 86.99 | 12.91 | 0.00 | 0.00 | 0.00 |
August | 64.28 | 35.40 | 28.88 | 86.36 | 15.43 | 0.00 | 0.00 | 0.00 |
September | 53.48 | 29.05 | 24.43 | 66.72 | 23.14 | 0.00 | 0.00 | 0.00 |
October | 38.73 | 21.22 | 17.51 | 37.73 | 49.01 | 0.00 | 0.00 | 0.00 |
November | 30.15 | 17.02 | 13.13 | 25.42 | 57.29 | 0.00 | 0.00 | 0.00 |
December | 26.10 | 15.04 | 11.06 | 19.61 | 69.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.59 | 25.33 | 22.25 | 52.59 | 39.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.10 | 15.04 | 11.06 | 19.61 | 12.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.10 | 36.80 | 33.46 | 94.47 | 69.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1202.65 | 989.31 | 213.34 | 1309.81 | 765.57 | 0.00 | 0.00 | 0.00 |
February | 1153.56 | 919.69 | 233.87 | 1241.81 | 792.61 | 0.00 | 0.00 | 0.00 |
March | 850.50 | 559.58 | 290.92 | 938.21 | 631.43 | 0.00 | 0.00 | 0.00 |
April | 550.85 | 221.50 | 329.35 | 549.39 | 569.95 | 0.00 | 0.00 | 0.00 |
May | 504.79 | 92.52 | 412.27 | 563.35 | 336.35 | 0.00 | 0.00 | 0.00 |
June | 465.40 | 85.06 | 380.34 | 688.03 | 189.38 | 0.00 | 0.00 | 0.00 |
July | 484.47 | 86.75 | 397.72 | 718.87 | 177.53 | 0.00 | 0.00 | 0.00 |
August | 616.83 | 257.86 | 358.97 | 902.75 | 213.26 | 0.00 | 0.00 | 0.00 |
September | 793.61 | 442.83 | 350.78 | 1068.90 | 333.40 | 0.00 | 0.00 | 0.00 |
October | 948.92 | 673.28 | 275.64 | 1108.89 | 666.16 | 0.00 | 0.00 | 0.00 |
November | 1156.13 | 921.60 | 234.53 | 1290.21 | 753.34 | 0.00 | 0.00 | 0.00 |
December | 1105.56 | 894.83 | 210.74 | 1174.27 | 873.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 817.55 | 509.75 | 307.80 | 961.28 | 523.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 465.40 | 85.06 | 210.74 | 549.39 | 177.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1202.65 | 989.31 | 412.27 | 1309.81 | 873.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1202.65 | 989.31 | 213.34 | 1309.81 | 765.57 | 0.00 | 0.00 | 0.00 |
February | 1153.56 | 919.69 | 233.87 | 1241.81 | 792.61 | 0.00 | 0.00 | 0.00 |
March | 850.50 | 559.58 | 290.92 | 938.21 | 631.43 | 0.00 | 0.00 | 0.00 |
April | 550.85 | 221.50 | 329.35 | 549.39 | 569.95 | 0.00 | 0.00 | 0.00 |
May | 504.79 | 92.52 | 412.27 | 563.35 | 336.35 | 0.00 | 0.00 | 0.00 |
June | 465.40 | 85.06 | 380.34 | 688.03 | 189.38 | 0.00 | 0.00 | 0.00 |
July | 484.47 | 86.75 | 397.72 | 718.87 | 177.53 | 0.00 | 0.00 | 0.00 |
August | 616.83 | 257.86 | 358.97 | 902.75 | 213.26 | 0.00 | 0.00 | 0.00 |
September | 793.61 | 442.83 | 350.78 | 1068.90 | 333.40 | 0.00 | 0.00 | 0.00 |
October | 948.92 | 673.28 | 275.64 | 1108.89 | 666.16 | 0.00 | 0.00 | 0.00 |
November | 1156.13 | 921.60 | 234.53 | 1290.21 | 753.34 | 0.00 | 0.00 | 0.00 |
December | 1105.56 | 894.83 | 210.74 | 1174.27 | 873.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 817.55 | 509.75 | 307.80 | 961.28 | 523.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 465.40 | 85.06 | 210.74 | 549.39 | 177.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1202.65 | 989.31 | 412.27 | 1309.81 | 873.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1202.57 | 989.24 | 213.33 | 1309.72 | 765.52 | 0.00 | 0.00 | 0.00 |
February | 1153.49 | 919.63 | 233.86 | 1241.73 | 792.56 | 0.00 | 0.00 | 0.00 |
March | 850.44 | 559.54 | 290.90 | 938.15 | 631.39 | 0.00 | 0.00 | 0.00 |
April | 550.81 | 221.48 | 329.33 | 549.36 | 569.92 | 0.00 | 0.00 | 0.00 |
May | 504.76 | 92.52 | 412.24 | 563.31 | 336.33 | 0.00 | 0.00 | 0.00 |
June | 465.37 | 85.06 | 380.32 | 687.99 | 189.37 | 0.00 | 0.00 | 0.00 |
July | 484.44 | 86.75 | 397.69 | 718.83 | 177.52 | 0.00 | 0.00 | 0.00 |
August | 616.79 | 257.84 | 358.95 | 902.69 | 213.25 | 0.00 | 0.00 | 0.00 |
September | 793.56 | 442.80 | 350.76 | 1068.83 | 333.38 | 0.00 | 0.00 | 0.00 |
October | 948.86 | 673.24 | 275.62 | 1108.82 | 666.12 | 0.00 | 0.00 | 0.00 |
November | 1156.06 | 921.54 | 234.51 | 1290.13 | 753.30 | 0.00 | 0.00 | 0.00 |
December | 1105.49 | 894.77 | 210.72 | 1174.19 | 873.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 817.50 | 509.72 | 307.78 | 961.22 | 523.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 465.37 | 85.06 | 210.72 | 549.36 | 177.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1202.57 | 989.24 | 412.24 | 1309.72 | 873.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 804.21 | 509.59 | 294.62 | 717.36 | 1540.68 | 0.00 | 0.00 | 0.00 |
February | 969.77 | 600.97 | 368.80 | 857.17 | 1581.18 | 0.00 | 0.00 | 0.00 |
March | 1135.53 | 626.50 | 509.03 | 1089.76 | 1209.84 | 0.00 | 0.00 | 0.00 |
April | 1069.16 | 452.66 | 616.49 | 973.22 | 1066.97 | 0.00 | 0.00 | 0.00 |
May | 1306.78 | 460.69 | 846.09 | 1452.90 | 640.23 | 0.00 | 0.00 | 0.00 |
June | 1598.28 | 768.99 | 829.28 | 2209.95 | 388.69 | 0.00 | 0.00 | 0.00 |
July | 1302.22 | 476.98 | 825.24 | 1813.41 | 350.69 | 0.00 | 0.00 | 0.00 |
August | 1359.15 | 671.44 | 687.71 | 1842.93 | 410.01 | 0.00 | 0.00 | 0.00 |
September | 1205.16 | 577.95 | 627.20 | 1532.63 | 627.55 | 0.00 | 0.00 | 0.00 |
October | 1013.86 | 579.49 | 434.36 | 1046.60 | 1267.29 | 0.00 | 0.00 | 0.00 |
November | 831.92 | 505.08 | 326.84 | 757.43 | 1476.08 | 0.00 | 0.00 | 0.00 |
December | 671.97 | 396.95 | 275.02 | 534.09 | 1767.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1106.01 | 551.61 | 554.40 | 1237.28 | 1024.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 671.97 | 396.95 | 275.02 | 534.09 | 350.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1598.28 | 768.99 | 846.09 | 2209.95 | 1767.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.80 | 20.15 | 11.65 | 28.36 | 60.92 | 0.00 | 0.00 | 0.00 |
February | 38.34 | 23.76 | 14.58 | 33.89 | 62.52 | 0.00 | 0.00 | 0.00 |
March | 44.90 | 24.77 | 20.13 | 43.09 | 47.84 | 0.00 | 0.00 | 0.00 |
April | 42.27 | 17.90 | 24.38 | 38.48 | 42.19 | 0.00 | 0.00 | 0.00 |
May | 51.67 | 18.22 | 33.45 | 57.45 | 25.31 | 0.00 | 0.00 | 0.00 |
June | 63.19 | 30.41 | 32.79 | 87.38 | 15.37 | 0.00 | 0.00 | 0.00 |
July | 51.49 | 18.86 | 32.63 | 71.70 | 13.87 | 0.00 | 0.00 | 0.00 |
August | 53.74 | 26.55 | 27.19 | 72.87 | 16.21 | 0.00 | 0.00 | 0.00 |
September | 47.65 | 22.85 | 24.80 | 60.60 | 24.81 | 0.00 | 0.00 | 0.00 |
October | 40.09 | 22.91 | 17.17 | 41.38 | 50.11 | 0.00 | 0.00 | 0.00 |
November | 32.89 | 19.97 | 12.92 | 29.95 | 58.36 | 0.00 | 0.00 | 0.00 |
December | 26.57 | 15.69 | 10.87 | 21.12 | 69.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.73 | 21.81 | 21.92 | 48.92 | 40.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.57 | 15.69 | 10.87 | 21.12 | 13.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.19 | 30.41 | 33.45 | 87.38 | 69.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.46 | 0.00 | 376.46 | 36.97 | 2581.68 | 0.00 | 0.00 | 0.00 |
February | 473.17 | 0.00 | 473.17 | 46.01 | 2652.46 | 0.00 | 0.00 | 0.00 |
March | 643.82 | 0.00 | 643.82 | 201.47 | 2009.14 | 0.00 | 0.00 | 0.00 |
April | 808.55 | 4.49 | 804.06 | 333.82 | 1738.17 | 0.00 | 0.00 | 0.00 |
May | 1104.52 | 36.51 | 1068.01 | 861.73 | 989.48 | 0.00 | 0.00 | 0.00 |
June | 1211.19 | 134.28 | 1076.91 | 1590.22 | 543.06 | 0.00 | 0.00 | 0.00 |
July | 1145.45 | 74.15 | 1071.31 | 1537.08 | 516.47 | 0.00 | 0.00 | 0.00 |
August | 911.70 | 21.57 | 890.13 | 1154.49 | 598.38 | 0.00 | 0.00 | 0.00 |
September | 765.82 | 0.18 | 765.64 | 833.08 | 912.75 | 0.00 | 0.00 | 0.00 |
October | 548.51 | 0.00 | 548.51 | 229.74 | 1938.88 | 0.00 | 0.00 | 0.00 |
November | 416.39 | 0.00 | 416.39 | 73.63 | 2352.38 | 0.00 | 0.00 | 0.00 |
December | 352.23 | 0.00 | 352.23 | 38.78 | 2913.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 731.15 | 22.65 | 708.50 | 581.04 | 1640.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 352.23 | 0.00 | 352.23 | 36.97 | 516.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1211.19 | 134.28 | 1076.91 | 1590.22 | 2913.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 785.86 | 481.60 | 304.26 | 607.59 | 1586.26 | 0.00 | 0.00 | 0.00 |
February | 1043.93 | 659.03 | 384.90 | 879.90 | 1661.24 | 0.00 | 0.00 | 0.00 |
March | 1260.00 | 734.94 | 525.05 | 1162.56 | 1266.52 | 0.00 | 0.00 | 0.00 |
April | 1292.19 | 629.45 | 662.75 | 1163.31 | 1110.99 | 0.00 | 0.00 | 0.00 |
May | 1510.55 | 630.96 | 879.59 | 1594.77 | 652.66 | 0.00 | 0.00 | 0.00 |
June | 1843.03 | 967.54 | 875.49 | 2455.72 | 359.89 | 0.00 | 0.00 | 0.00 |
July | 1675.46 | 797.81 | 877.65 | 2262.02 | 343.87 | 0.00 | 0.00 | 0.00 |
August | 1689.93 | 930.75 | 759.18 | 2255.89 | 393.74 | 0.00 | 0.00 | 0.00 |
September | 1406.11 | 763.83 | 642.28 | 1750.30 | 576.26 | 0.00 | 0.00 | 0.00 |
October | 1018.30 | 557.97 | 460.34 | 983.65 | 1248.20 | 0.00 | 0.00 | 0.00 |
November | 792.62 | 447.52 | 345.10 | 659.33 | 1485.91 | 0.00 | 0.00 | 0.00 |
December | 686.20 | 395.30 | 290.90 | 504.60 | 1819.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1251.13 | 666.06 | 585.08 | 1358.90 | 1038.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.20 | 395.30 | 290.90 | 504.60 | 343.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1843.03 | 967.54 | 879.59 | 2455.72 | 1819.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3607.85 | 2967.84 | 640.01 | 3870.99 | 2261.60 | 0.00 | 0.00 | 0.00 |
February | 3460.60 | 2759.00 | 701.60 | 3643.61 | 2381.96 | 0.00 | 0.00 | 0.00 |
March | 2551.43 | 1678.69 | 872.74 | 2741.89 | 1938.11 | 0.00 | 0.00 | 0.00 |
April | 1652.50 | 664.47 | 988.03 | 1581.87 | 1771.14 | 0.00 | 0.00 | 0.00 |
May | 1514.33 | 277.56 | 1236.77 | 1605.20 | 1092.00 | 0.00 | 0.00 | 0.00 |
June | 1396.17 | 255.18 | 1140.99 | 2017.64 | 607.57 | 0.00 | 0.00 | 0.00 |
July | 1453.38 | 260.26 | 1193.12 | 2115.48 | 567.17 | 0.00 | 0.00 | 0.00 |
August | 1850.44 | 773.55 | 1076.89 | 2682.06 | 638.38 | 0.00 | 0.00 | 0.00 |
September | 2380.77 | 1328.45 | 1052.32 | 3194.49 | 947.45 | 0.00 | 0.00 | 0.00 |
October | 2846.70 | 2019.79 | 826.91 | 3308.32 | 1906.10 | 0.00 | 0.00 | 0.00 |
November | 3468.30 | 2764.73 | 703.57 | 3833.33 | 2172.35 | 0.00 | 0.00 | 0.00 |
December | 3316.60 | 2684.41 | 632.19 | 3473.32 | 2566.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2452.58 | 1529.21 | 923.37 | 2834.40 | 1566.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1396.17 | 255.18 | 632.19 | 1581.87 | 567.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3607.85 | 2967.84 | 1236.77 | 3870.99 | 2566.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.98 | 529.72 | 306.26 | 726.75 | 1627.94 | 0.00 | 0.00 | 0.00 |
February | 1008.08 | 624.71 | 383.37 | 865.95 | 1683.85 | 0.00 | 0.00 | 0.00 |
March | 1180.39 | 651.25 | 529.15 | 1099.28 | 1301.56 | 0.00 | 0.00 | 0.00 |
April | 1111.40 | 470.54 | 640.85 | 977.20 | 1142.98 | 0.00 | 0.00 | 0.00 |
May | 1358.41 | 478.89 | 879.52 | 1462.53 | 701.40 | 0.00 | 0.00 | 0.00 |
June | 1661.42 | 799.37 | 862.05 | 2275.44 | 412.18 | 0.00 | 0.00 | 0.00 |
July | 1353.66 | 495.82 | 857.85 | 1865.12 | 376.40 | 0.00 | 0.00 | 0.00 |
August | 1412.84 | 697.96 | 714.88 | 1906.44 | 420.65 | 0.00 | 0.00 | 0.00 |
September | 1252.77 | 600.78 | 651.98 | 1596.17 | 622.68 | 0.00 | 0.00 | 0.00 |
October | 1053.91 | 602.38 | 451.52 | 1086.30 | 1276.29 | 0.00 | 0.00 | 0.00 |
November | 864.79 | 525.03 | 339.76 | 781.04 | 1508.72 | 0.00 | 0.00 | 0.00 |
December | 698.51 | 412.63 | 285.88 | 546.04 | 1829.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1149.71 | 573.40 | 576.30 | 1267.42 | 1072.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 698.51 | 412.63 | 285.88 | 546.04 | 376.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1661.42 | 799.37 | 879.52 | 2275.44 | 1829.63 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100831E+10 | 0.00 | 0.100831E+10 | 0.116284E+09 | 0.650586E+10 |
February | 0.114468E+10 | 0.00 | 0.114468E+10 | 0.127103E+09 | 0.609404E+10 |
March | 0.172441E+10 | 0.00 | 0.172441E+10 | 0.565539E+09 | 0.507600E+10 |
April | 0.209575E+10 | 11626277.54 | 0.208413E+10 | 0.886850E+09 | 0.416884E+10 |
May | 0.295836E+10 | 97790864.98 | 0.286057E+10 | 0.237789E+10 | 0.246461E+10 |
June | 0.313940E+10 | 0.348051E+09 | 0.279135E+10 | 0.414757E+10 | 0.132647E+10 |
July | 0.306798E+10 | 0.198595E+09 | 0.286939E+10 | 0.414144E+10 | 0.130436E+10 |
August | 0.244188E+10 | 57766378.76 | 0.238412E+10 | 0.312173E+10 | 0.148789E+10 |
September | 0.198502E+10 | 466241.98 | 0.198455E+10 | 0.220985E+10 | 0.216956E+10 |
October | 0.146914E+10 | 0.00 | 0.146914E+10 | 0.666324E+09 | 0.480643E+10 |
November | 0.107929E+10 | 0.00 | 0.107929E+10 | 0.217799E+09 | 0.567609E+10 |
December | 0.943401E+09 | 0.00 | 0.943401E+09 | 0.119484E+09 | 0.742339E+10 |
Annual Sum or Average | 0.230576E+11 | 0.714296E+09 | 0.223433E+11 | 0.186979E+11 | 0.485036E+11 |
Minimum of Months | 0.943401E+09 | 0.00 | 0.943401E+09 | 0.116284E+09 | 0.130436E+10 |
Maximum of Months | 0.313940E+10 | 0.348051E+09 | 0.286939E+10 | 0.414757E+10 | 0.742339E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210485E+10 | 0.128991E+10 | 0.814941E+09 | 0.168622E+10 | 0.399234E+10 |
February | 0.252548E+10 | 0.159432E+10 | 0.931161E+09 | 0.217467E+10 | 0.381263E+10 |
March | 0.337477E+10 | 0.196846E+10 | 0.140631E+10 | 0.315313E+10 | 0.320743E+10 |
April | 0.334937E+10 | 0.163153E+10 | 0.171784E+10 | 0.304977E+10 | 0.267820E+10 |
May | 0.404587E+10 | 0.168997E+10 | 0.235590E+10 | 0.431722E+10 | 0.165219E+10 |
June | 0.477714E+10 | 0.250786E+10 | 0.226928E+10 | 0.636529E+10 | 0.891588E+09 |
July | 0.448756E+10 | 0.213685E+10 | 0.235071E+10 | 0.605973E+10 | 0.881251E+09 |
August | 0.452632E+10 | 0.249292E+10 | 0.203340E+10 | 0.604734E+10 | 0.997277E+09 |
September | 0.364464E+10 | 0.197986E+10 | 0.166478E+10 | 0.456408E+10 | 0.139548E+10 |
October | 0.272743E+10 | 0.149446E+10 | 0.123296E+10 | 0.268761E+10 | 0.311814E+10 |
November | 0.205447E+10 | 0.115997E+10 | 0.894502E+09 | 0.176634E+10 | 0.359658E+10 |
December | 0.183791E+10 | 0.105876E+10 | 0.779147E+09 | 0.139789E+10 | 0.462939E+10 |
Annual Sum or Average | 0.394558E+11 | 0.210049E+11 | 0.184509E+11 | 0.432693E+11 | 0.308525E+11 |
Minimum of Months | 0.183791E+10 | 0.105876E+10 | 0.779147E+09 | 0.139789E+10 | 0.881251E+09 |
Maximum of Months | 0.477714E+10 | 0.250786E+10 | 0.235590E+10 | 0.636529E+10 | 0.462939E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.966327E+10 | 0.794907E+10 | 0.171420E+10 | 0.104652E+11 | 0.567061E+10 |
February | 0.837189E+10 | 0.667458E+10 | 0.169731E+10 | 0.887309E+10 | 0.545444E+10 |
March | 0.683374E+10 | 0.449620E+10 | 0.233754E+10 | 0.738242E+10 | 0.489045E+10 |
April | 0.428327E+10 | 0.172231E+10 | 0.256096E+10 | 0.412260E+10 | 0.425601E+10 |
May | 0.405599E+10 | 0.743428E+09 | 0.331257E+10 | 0.434120E+10 | 0.272693E+10 |
June | 0.361887E+10 | 0.661421E+09 | 0.295745E+10 | 0.523241E+10 | 0.147367E+10 |
July | 0.389273E+10 | 0.697072E+09 | 0.319566E+10 | 0.567294E+10 | 0.142452E+10 |
August | 0.495623E+10 | 0.207187E+10 | 0.288435E+10 | 0.719139E+10 | 0.158845E+10 |
September | 0.617095E+10 | 0.344334E+10 | 0.272761E+10 | 0.830932E+10 | 0.226769E+10 |
October | 0.762460E+10 | 0.540981E+10 | 0.221479E+10 | 0.891385E+10 | 0.473966E+10 |
November | 0.898984E+10 | 0.716619E+10 | 0.182365E+10 | 0.100152E+11 | 0.525309E+10 |
December | 0.888318E+10 | 0.718991E+10 | 0.169327E+10 | 0.938907E+10 | 0.649928E+10 |
Annual Sum or Average | 0.773446E+11 | 0.482252E+11 | 0.291194E+11 | 0.899087E+11 | 0.462448E+11 |
Minimum of Months | 0.361887E+10 | 0.661421E+09 | 0.169327E+10 | 0.412260E+10 | 0.142452E+10 |
Maximum of Months | 0.966327E+10 | 0.794907E+10 | 0.331257E+10 | 0.104652E+11 | 0.649928E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223910E+10 | 0.141881E+10 | 0.820289E+09 | 0.196870E+10 | 0.409829E+10 |
February | 0.243874E+10 | 0.151129E+10 | 0.927451E+09 | 0.210702E+10 | 0.386422E+10 |
March | 0.316157E+10 | 0.174430E+10 | 0.141727E+10 | 0.295109E+10 | 0.329282E+10 |
April | 0.288074E+10 | 0.121965E+10 | 0.166109E+10 | 0.253644E+10 | 0.275123E+10 |
May | 0.363837E+10 | 0.128265E+10 | 0.235572E+10 | 0.393300E+10 | 0.175909E+10 |
June | 0.430640E+10 | 0.207196E+10 | 0.223444E+10 | 0.589365E+10 | 0.100662E+10 |
July | 0.362566E+10 | 0.132800E+10 | 0.229765E+10 | 0.499322E+10 | 0.951879E+09 |
August | 0.378415E+10 | 0.186941E+10 | 0.191474E+10 | 0.511030E+10 | 0.105406E+10 |
September | 0.324717E+10 | 0.155723E+10 | 0.168994E+10 | 0.415459E+10 | 0.149615E+10 |
October | 0.282279E+10 | 0.161343E+10 | 0.120936E+10 | 0.292999E+10 | 0.317957E+10 |
November | 0.224153E+10 | 0.136088E+10 | 0.880649E+09 | 0.204718E+10 | 0.364793E+10 |
December | 0.187089E+10 | 0.110518E+10 | 0.765711E+09 | 0.148268E+10 | 0.465392E+10 |
Annual Sum or Average | 0.362571E+11 | 0.180828E+11 | 0.181743E+11 | 0.401079E+11 | 0.317558E+11 |
Minimum of Months | 0.187089E+10 | 0.110518E+10 | 0.765711E+09 | 0.148268E+10 | 0.951879E+09 |
Maximum of Months | 0.430640E+10 | 0.207196E+10 | 0.235572E+10 | 0.589365E+10 | 0.465392E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.336091E+09 | 0.00 | 0.336091E+09 | 41101481.08 | 0.222827E+10 |
February | 0.381546E+09 | 0.00 | 0.381546E+09 | 46091441.62 | 0.205164E+10 |
March | 0.574782E+09 | 0.00 | 0.574782E+09 | 0.215601E+09 | 0.169175E+10 |
April | 0.698559E+09 | 3875303.66 | 0.694683E+09 | 0.332808E+09 | 0.142155E+10 |
May | 0.986083E+09 | 32595927.30 | 0.953487E+09 | 0.850635E+09 | 0.807712E+09 |
June | 0.104643E+10 | 0.116013E+09 | 0.930413E+09 | 0.141845E+10 | 0.435987E+09 |
July | 0.102262E+10 | 66196197.70 | 0.956427E+09 | 0.141195E+10 | 0.428206E+09 |
August | 0.813930E+09 | 19254852.51 | 0.794676E+09 | 0.105283E+10 | 0.514208E+09 |
September | 0.661647E+09 | 155409.09 | 0.661491E+09 | 0.725520E+09 | 0.794308E+09 |
October | 0.489695E+09 | 0.00 | 0.489695E+09 | 0.211354E+09 | 0.174083E+10 |
November | 0.359749E+09 | 0.00 | 0.359749E+09 | 66767871.30 | 0.203236E+10 |
December | 0.314455E+09 | 0.00 | 0.314455E+09 | 36427168.74 | 0.258283E+10 |
Annual Sum or Average | 0.768559E+10 | 0.238091E+09 | 0.744750E+10 | 0.640953E+10 | 0.167297E+11 |
Minimum of Months | 0.314455E+09 | 0.00 | 0.314455E+09 | 36427168.74 | 0.428206E+09 |
Maximum of Months | 0.104643E+10 | 0.116013E+09 | 0.956427E+09 | 0.141845E+10 | 0.258283E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.336107E+09 | 0.00 | 0.336107E+09 | 41102723.15 | 0.222841E+10 |
February | 0.381565E+09 | 0.00 | 0.381565E+09 | 46093076.36 | 0.205177E+10 |
March | 0.574811E+09 | 0.00 | 0.574811E+09 | 0.215610E+09 | 0.169186E+10 |
April | 0.698592E+09 | 3875453.30 | 0.694717E+09 | 0.332821E+09 | 0.142164E+10 |
May | 0.986129E+09 | 32597185.94 | 0.953532E+09 | 0.850671E+09 | 0.807763E+09 |
June | 0.104648E+10 | 0.116018E+09 | 0.930459E+09 | 0.141852E+10 | 0.436012E+09 |
July | 0.102267E+10 | 66198753.76 | 0.956472E+09 | 0.141202E+10 | 0.428231E+09 |
August | 0.813971E+09 | 19255596.01 | 0.794715E+09 | 0.105289E+10 | 0.514238E+09 |
September | 0.661679E+09 | 155415.09 | 0.661524E+09 | 0.725556E+09 | 0.794355E+09 |
October | 0.489719E+09 | 0.00 | 0.489719E+09 | 0.211363E+09 | 0.174094E+10 |
November | 0.359767E+09 | 0.00 | 0.359767E+09 | 66770572.12 | 0.203249E+10 |
December | 0.314470E+09 | 0.00 | 0.314470E+09 | 36428702.70 | 0.258299E+10 |
Annual Sum or Average | 0.768596E+10 | 0.238100E+09 | 0.744786E+10 | 0.640984E+10 | 0.167307E+11 |
Minimum of Months | 0.314470E+09 | 0.00 | 0.314470E+09 | 36428702.70 | 0.428231E+09 |
Maximum of Months | 0.104648E+10 | 0.116018E+09 | 0.956472E+09 | 0.141852E+10 | 0.258299E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.336107E+09 | 0.00 | 0.336107E+09 | 41102723.15 | 0.222841E+10 |
February | 0.381565E+09 | 0.00 | 0.381565E+09 | 46093076.36 | 0.205177E+10 |
March | 0.574811E+09 | 0.00 | 0.574811E+09 | 0.215610E+09 | 0.169186E+10 |
April | 0.698592E+09 | 3875453.30 | 0.694717E+09 | 0.332821E+09 | 0.142164E+10 |
May | 0.986129E+09 | 32597185.94 | 0.953532E+09 | 0.850671E+09 | 0.807763E+09 |
June | 0.104648E+10 | 0.116018E+09 | 0.930459E+09 | 0.141852E+10 | 0.436012E+09 |
July | 0.102267E+10 | 66198753.76 | 0.956472E+09 | 0.141202E+10 | 0.428231E+09 |
August | 0.813971E+09 | 19255596.01 | 0.794715E+09 | 0.105289E+10 | 0.514238E+09 |
September | 0.661679E+09 | 155415.09 | 0.661524E+09 | 0.725556E+09 | 0.794355E+09 |
October | 0.489719E+09 | 0.00 | 0.489719E+09 | 0.211363E+09 | 0.174094E+10 |
November | 0.359767E+09 | 0.00 | 0.359767E+09 | 66770572.12 | 0.203249E+10 |
December | 0.314470E+09 | 0.00 | 0.314470E+09 | 36428702.70 | 0.258299E+10 |
Annual Sum or Average | 0.768596E+10 | 0.238100E+09 | 0.744786E+10 | 0.640984E+10 | 0.167307E+11 |
Minimum of Months | 0.314470E+09 | 0.00 | 0.314470E+09 | 36428702.70 | 0.428231E+09 |
Maximum of Months | 0.104648E+10 | 0.116018E+09 | 0.956472E+09 | 0.141852E+10 | 0.258299E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202487E+10 | 0.124090E+10 | 0.783967E+09 | 0.162184E+10 | 0.399937E+10 |
February | 0.242950E+10 | 0.153374E+10 | 0.895768E+09 | 0.211435E+10 | 0.375439E+10 |
March | 0.324653E+10 | 0.189367E+10 | 0.135286E+10 | 0.309715E+10 | 0.315238E+10 |
April | 0.322209E+10 | 0.156953E+10 | 0.165255E+10 | 0.300807E+10 | 0.269855E+10 |
May | 0.389212E+10 | 0.162575E+10 | 0.226637E+10 | 0.424589E+10 | 0.160976E+10 |
June | 0.459560E+10 | 0.241257E+10 | 0.218303E+10 | 0.619308E+10 | 0.886548E+09 |
July | 0.431702E+10 | 0.205566E+10 | 0.226136E+10 | 0.589278E+10 | 0.874419E+09 |
August | 0.435431E+10 | 0.239820E+10 | 0.195611E+10 | 0.585037E+10 | 0.104506E+10 |
September | 0.350614E+10 | 0.190463E+10 | 0.160150E+10 | 0.437381E+10 | 0.151699E+10 |
October | 0.262378E+10 | 0.143768E+10 | 0.118610E+10 | 0.255556E+10 | 0.332029E+10 |
November | 0.197640E+10 | 0.111589E+10 | 0.860503E+09 | 0.166621E+10 | 0.375551E+10 |
December | 0.176807E+10 | 0.101853E+10 | 0.749534E+09 | 0.132837E+10 | 0.469206E+10 |
Annual Sum or Average | 0.379564E+11 | 0.202068E+11 | 0.177497E+11 | 0.419475E+11 | 0.313053E+11 |
Minimum of Months | 0.176807E+10 | 0.101853E+10 | 0.749534E+09 | 0.132837E+10 | 0.874419E+09 |
Maximum of Months | 0.459560E+10 | 0.241257E+10 | 0.226637E+10 | 0.619308E+10 | 0.469206E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80061350.71 | 49064018.85 | 30997331.85 | 64125955.84 | 0.158131E+09 |
February | 96060425.61 | 60642583.31 | 35417842.30 | 83599464.86 | 0.148445E+09 |
March | 0.128365E+09 | 74873987.39 | 53490688.22 | 0.122458E+09 | 0.124642E+09 |
April | 0.127398E+09 | 62057973.17 | 65340376.57 | 0.118936E+09 | 0.106698E+09 |
May | 0.153891E+09 | 64280811.85 | 89610059.47 | 0.167879E+09 | 63648390.07 |
June | 0.181706E+09 | 95390741.82 | 86315057.19 | 0.244869E+09 | 35053305.44 |
July | 0.170691E+09 | 81278946.80 | 89412244.83 | 0.232995E+09 | 34573732.64 |
August | 0.172165E+09 | 94822569.74 | 77342911.12 | 0.231318E+09 | 41320796.13 |
September | 0.138629E+09 | 75307432.17 | 63322019.94 | 0.172936E+09 | 59980392.39 |
October | 0.103742E+09 | 56844551.05 | 46897329.34 | 0.101045E+09 | 0.131281E+09 |
November | 78144935.66 | 44121414.24 | 34023521.43 | 65880500.64 | 0.148489E+09 |
December | 69907719.49 | 40271823.05 | 29635896.43 | 52522432.75 | 0.185520E+09 |
Annual Sum or Average | 0.150076E+10 | 0.798957E+09 | 0.701805E+09 | 0.165857E+10 | 0.123778E+10 |
Minimum of Months | 69907719.49 | 40271823.05 | 29635896.43 | 52522432.75 | 34573732.64 |
Maximum of Months | 0.181706E+09 | 95390741.82 | 89610059.47 | 0.244869E+09 | 0.185520E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322118E+10 | 0.264976E+10 | 0.571414E+09 | 0.350818E+10 | 0.205051E+10 |
February | 0.279070E+10 | 0.222492E+10 | 0.565782E+09 | 0.300418E+10 | 0.191749E+10 |
March | 0.227797E+10 | 0.149877E+10 | 0.779199E+09 | 0.251291E+10 | 0.169122E+10 |
April | 0.142779E+10 | 0.574119E+09 | 0.853675E+09 | 0.142403E+10 | 0.147732E+10 |
May | 0.135203E+10 | 0.247816E+09 | 0.110422E+10 | 0.150886E+10 | 0.900892E+09 |
June | 0.120632E+10 | 0.220480E+09 | 0.985840E+09 | 0.178338E+10 | 0.490881E+09 |
July | 0.129761E+10 | 0.232364E+09 | 0.106524E+10 | 0.192542E+10 | 0.475505E+09 |
August | 0.165212E+10 | 0.690643E+09 | 0.961473E+09 | 0.241793E+10 | 0.571205E+09 |
September | 0.205704E+10 | 0.114781E+10 | 0.909225E+09 | 0.277060E+10 | 0.864172E+09 |
October | 0.254160E+10 | 0.180332E+10 | 0.738280E+09 | 0.297004E+10 | 0.178424E+10 |
November | 0.299669E+10 | 0.238879E+10 | 0.607897E+09 | 0.334423E+10 | 0.195267E+10 |
December | 0.296114E+10 | 0.239670E+10 | 0.564436E+09 | 0.314516E+10 | 0.233914E+10 |
Annual Sum or Average | 0.257822E+11 | 0.160755E+11 | 0.970668E+10 | 0.303149E+11 | 0.165152E+11 |
Minimum of Months | 0.120632E+10 | 0.220480E+09 | 0.564436E+09 | 0.142403E+10 | 0.475505E+09 |
Maximum of Months | 0.322118E+10 | 0.264976E+10 | 0.110422E+10 | 0.350818E+10 | 0.233914E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322118E+10 | 0.264976E+10 | 0.571414E+09 | 0.350818E+10 | 0.205051E+10 |
February | 0.279070E+10 | 0.222492E+10 | 0.565782E+09 | 0.300418E+10 | 0.191749E+10 |
March | 0.227797E+10 | 0.149877E+10 | 0.779199E+09 | 0.251291E+10 | 0.169122E+10 |
April | 0.142779E+10 | 0.574119E+09 | 0.853675E+09 | 0.142403E+10 | 0.147732E+10 |
May | 0.135203E+10 | 0.247816E+09 | 0.110422E+10 | 0.150886E+10 | 0.900892E+09 |
June | 0.120632E+10 | 0.220480E+09 | 0.985840E+09 | 0.178338E+10 | 0.490881E+09 |
July | 0.129761E+10 | 0.232364E+09 | 0.106524E+10 | 0.192542E+10 | 0.475505E+09 |
August | 0.165212E+10 | 0.690643E+09 | 0.961473E+09 | 0.241793E+10 | 0.571205E+09 |
September | 0.205704E+10 | 0.114781E+10 | 0.909225E+09 | 0.277060E+10 | 0.864172E+09 |
October | 0.254160E+10 | 0.180332E+10 | 0.738280E+09 | 0.297004E+10 | 0.178424E+10 |
November | 0.299669E+10 | 0.238879E+10 | 0.607897E+09 | 0.334423E+10 | 0.195267E+10 |
December | 0.296114E+10 | 0.239670E+10 | 0.564436E+09 | 0.314516E+10 | 0.233914E+10 |
Annual Sum or Average | 0.257822E+11 | 0.160755E+11 | 0.970668E+10 | 0.303149E+11 | 0.165152E+11 |
Minimum of Months | 0.120632E+10 | 0.220480E+09 | 0.564436E+09 | 0.142403E+10 | 0.475505E+09 |
Maximum of Months | 0.322118E+10 | 0.264976E+10 | 0.110422E+10 | 0.350818E+10 | 0.233914E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322097E+10 | 0.264959E+10 | 0.571378E+09 | 0.350796E+10 | 0.205038E+10 |
February | 0.279053E+10 | 0.222478E+10 | 0.565746E+09 | 0.300399E+10 | 0.191737E+10 |
March | 0.227783E+10 | 0.149868E+10 | 0.779150E+09 | 0.251275E+10 | 0.169111E+10 |
April | 0.142770E+10 | 0.574082E+09 | 0.853621E+09 | 0.142394E+10 | 0.147722E+10 |
May | 0.135195E+10 | 0.247801E+09 | 0.110415E+10 | 0.150877E+10 | 0.900835E+09 |
June | 0.120624E+10 | 0.220466E+09 | 0.985778E+09 | 0.178326E+10 | 0.490850E+09 |
July | 0.129753E+10 | 0.232349E+09 | 0.106518E+10 | 0.192530E+10 | 0.475475E+09 |
August | 0.165201E+10 | 0.690599E+09 | 0.961412E+09 | 0.241778E+10 | 0.571169E+09 |
September | 0.205691E+10 | 0.114774E+10 | 0.909168E+09 | 0.277042E+10 | 0.864118E+09 |
October | 0.254144E+10 | 0.180320E+10 | 0.738233E+09 | 0.296985E+10 | 0.178412E+10 |
November | 0.299650E+10 | 0.238864E+10 | 0.607858E+09 | 0.334401E+10 | 0.195255E+10 |
December | 0.296095E+10 | 0.239655E+10 | 0.564400E+09 | 0.314496E+10 | 0.233900E+10 |
Annual Sum or Average | 0.257806E+11 | 0.160745E+11 | 0.970607E+10 | 0.303130E+11 | 0.165142E+11 |
Minimum of Months | 0.120624E+10 | 0.220466E+09 | 0.564400E+09 | 0.142394E+10 | 0.475475E+09 |
Maximum of Months | 0.322097E+10 | 0.264959E+10 | 0.110415E+10 | 0.350796E+10 | 0.233900E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.215400E+10 | 0.136489E+10 | 0.789110E+09 | 0.192139E+10 | 0.412655E+10 |
February | 0.234606E+10 | 0.145386E+10 | 0.892197E+09 | 0.207368E+10 | 0.382520E+10 |
March | 0.304141E+10 | 0.167802E+10 | 0.136340E+10 | 0.291882E+10 | 0.324045E+10 |
April | 0.277126E+10 | 0.117330E+10 | 0.159795E+10 | 0.252258E+10 | 0.276558E+10 |
May | 0.350009E+10 | 0.123391E+10 | 0.226618E+10 | 0.389143E+10 | 0.171480E+10 |
June | 0.414274E+10 | 0.199323E+10 | 0.214951E+10 | 0.572818E+10 | 0.100749E+10 |
July | 0.348786E+10 | 0.127754E+10 | 0.221032E+10 | 0.485704E+10 | 0.939280E+09 |
August | 0.364034E+10 | 0.179838E+10 | 0.184196E+10 | 0.493611E+10 | 0.109816E+10 |
September | 0.312376E+10 | 0.149805E+10 | 0.162571E+10 | 0.397257E+10 | 0.162661E+10 |
October | 0.271551E+10 | 0.155212E+10 | 0.116339E+10 | 0.280322E+10 | 0.339432E+10 |
November | 0.215634E+10 | 0.130917E+10 | 0.847175E+09 | 0.196327E+10 | 0.382600E+10 |
December | 0.179979E+10 | 0.106319E+10 | 0.736607E+09 | 0.143051E+10 | 0.473431E+10 |
Annual Sum or Average | 0.348792E+11 | 0.173957E+11 | 0.174835E+11 | 0.390188E+11 | 0.322987E+11 |
Minimum of Months | 0.179979E+10 | 0.106319E+10 | 0.736607E+09 | 0.143051E+10 | 0.939280E+09 |
Maximum of Months | 0.414274E+10 | 0.199323E+10 | 0.226618E+10 | 0.572818E+10 | 0.473431E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 85167368.11 | 53966680.88 | 31200687.23 | 75969842.46 | 0.163160E+09 |
February | 92761093.16 | 57484420.89 | 35276672.27 | 81991331.47 | 0.151245E+09 |
March | 0.120255E+09 | 66347254.30 | 53907534.19 | 0.115408E+09 | 0.128124E+09 |
April | 0.109573E+09 | 46391352.98 | 63181680.32 | 99740548.83 | 0.109349E+09 |
May | 0.138391E+09 | 48787813.25 | 89602709.95 | 0.153864E+09 | 67801493.49 |
June | 0.163800E+09 | 78810546.06 | 84989499.30 | 0.226487E+09 | 39835423.75 |
July | 0.137907E+09 | 50512745.75 | 87394140.84 | 0.192043E+09 | 37138301.19 |
August | 0.143936E+09 | 71106263.47 | 72829397.13 | 0.195169E+09 | 43420322.27 |
September | 0.123511E+09 | 59231687.90 | 64279117.88 | 0.157072E+09 | 64314834.22 |
October | 0.107369E+09 | 61369304.49 | 45999544.39 | 0.110837E+09 | 0.134208E+09 |
November | 85259811.73 | 51763277.30 | 33496534.43 | 77625965.07 | 0.151276E+09 |
December | 71162160.67 | 42037390.29 | 29124770.38 | 56560945.80 | 0.187190E+09 |
Annual Sum or Average | 0.137909E+10 | 0.687809E+09 | 0.691282E+09 | 0.154277E+10 | 0.127706E+10 |
Minimum of Months | 71162160.67 | 42037390.29 | 29124770.38 | 56560945.80 | 37138301.19 |
Maximum of Months | 0.163800E+09 | 78810546.06 | 89602709.95 | 0.226487E+09 | 0.187190E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100831E+10 | 0.00 | 0.100831E+10 | 99031926.07 | 0.691478E+10 |
February | 0.114468E+10 | 0.00 | 0.114468E+10 | 0.111315E+09 | 0.641684E+10 |
March | 0.172441E+10 | 0.00 | 0.172441E+10 | 0.539621E+09 | 0.538129E+10 |
April | 0.209575E+10 | 11626277.54 | 0.208413E+10 | 0.865270E+09 | 0.450533E+10 |
May | 0.295836E+10 | 97790864.98 | 0.286057E+10 | 0.230806E+10 | 0.265022E+10 |
June | 0.313940E+10 | 0.348051E+09 | 0.279135E+10 | 0.412185E+10 | 0.140760E+10 |
July | 0.306798E+10 | 0.198595E+09 | 0.286939E+10 | 0.411691E+10 | 0.138331E+10 |
August | 0.244188E+10 | 57766378.76 | 0.238412E+10 | 0.309219E+10 | 0.160271E+10 |
September | 0.198502E+10 | 466241.98 | 0.198455E+10 | 0.215933E+10 | 0.236585E+10 |
October | 0.146914E+10 | 0.00 | 0.146914E+10 | 0.615338E+09 | 0.519310E+10 |
November | 0.107929E+10 | 0.00 | 0.107929E+10 | 0.190860E+09 | 0.609738E+10 |
December | 0.943401E+09 | 0.00 | 0.943401E+09 | 0.103867E+09 | 0.780402E+10 |
Annual Sum or Average | 0.230576E+11 | 0.714296E+09 | 0.223433E+11 | 0.183237E+11 | 0.517224E+11 |
Minimum of Months | 0.943401E+09 | 0.00 | 0.943401E+09 | 99031926.07 | 0.138331E+10 |
Maximum of Months | 0.313940E+10 | 0.348051E+09 | 0.286939E+10 | 0.412185E+10 | 0.780402E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210485E+10 | 0.128991E+10 | 0.814941E+09 | 0.162736E+10 | 0.424863E+10 |
February | 0.252548E+10 | 0.159432E+10 | 0.931161E+09 | 0.212865E+10 | 0.401888E+10 |
March | 0.337477E+10 | 0.196846E+10 | 0.140631E+10 | 0.311380E+10 | 0.339225E+10 |
April | 0.334937E+10 | 0.163153E+10 | 0.171784E+10 | 0.301530E+10 | 0.287970E+10 |
May | 0.404587E+10 | 0.168997E+10 | 0.235590E+10 | 0.427143E+10 | 0.174809E+10 |
June | 0.477714E+10 | 0.250786E+10 | 0.226928E+10 | 0.636522E+10 | 0.932844E+09 |
July | 0.448756E+10 | 0.213685E+10 | 0.235071E+10 | 0.605860E+10 | 0.921023E+09 |
August | 0.452632E+10 | 0.249292E+10 | 0.203340E+10 | 0.604217E+10 | 0.105459E+10 |
September | 0.364464E+10 | 0.197986E+10 | 0.166478E+10 | 0.453678E+10 | 0.149368E+10 |
October | 0.272743E+10 | 0.149446E+10 | 0.123296E+10 | 0.263461E+10 | 0.334317E+10 |
November | 0.205447E+10 | 0.115997E+10 | 0.894502E+09 | 0.170899E+10 | 0.385147E+10 |
December | 0.183791E+10 | 0.105876E+10 | 0.779147E+09 | 0.135152E+10 | 0.487335E+10 |
Annual Sum or Average | 0.394558E+11 | 0.210049E+11 | 0.184509E+11 | 0.428544E+11 | 0.327577E+11 |
Minimum of Months | 0.183791E+10 | 0.105876E+10 | 0.779147E+09 | 0.135152E+10 | 0.921023E+09 |
Maximum of Months | 0.477714E+10 | 0.250786E+10 | 0.235590E+10 | 0.636522E+10 | 0.487335E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.966327E+10 | 0.794907E+10 | 0.171420E+10 | 0.103681E+11 | 0.605747E+10 |
February | 0.837189E+10 | 0.667458E+10 | 0.169731E+10 | 0.881463E+10 | 0.576244E+10 |
March | 0.683374E+10 | 0.449620E+10 | 0.233754E+10 | 0.734389E+10 | 0.519105E+10 |
April | 0.428327E+10 | 0.172231E+10 | 0.256096E+10 | 0.410021E+10 | 0.459079E+10 |
May | 0.405599E+10 | 0.743428E+09 | 0.331257E+10 | 0.429936E+10 | 0.292482E+10 |
June | 0.361887E+10 | 0.661421E+09 | 0.295745E+10 | 0.522973E+10 | 0.157481E+10 |
July | 0.389273E+10 | 0.697072E+09 | 0.319566E+10 | 0.566609E+10 | 0.151912E+10 |
August | 0.495623E+10 | 0.207187E+10 | 0.288435E+10 | 0.718363E+10 | 0.170984E+10 |
September | 0.617095E+10 | 0.344334E+10 | 0.272761E+10 | 0.828011E+10 | 0.245579E+10 |
October | 0.762460E+10 | 0.540981E+10 | 0.221479E+10 | 0.886100E+10 | 0.510531E+10 |
November | 0.898984E+10 | 0.716619E+10 | 0.182365E+10 | 0.993599E+10 | 0.563074E+10 |
December | 0.888318E+10 | 0.718991E+10 | 0.169327E+10 | 0.930294E+10 | 0.687306E+10 |
Annual Sum or Average | 0.773446E+11 | 0.482252E+11 | 0.291194E+11 | 0.893856E+11 | 0.493953E+11 |
Minimum of Months | 0.361887E+10 | 0.661421E+09 | 0.169327E+10 | 0.410021E+10 | 0.151912E+10 |
Maximum of Months | 0.966327E+10 | 0.794907E+10 | 0.331257E+10 | 0.103681E+11 | 0.687306E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223910E+10 | 0.141881E+10 | 0.820289E+09 | 0.194653E+10 | 0.436028E+10 |
February | 0.243874E+10 | 0.151129E+10 | 0.927451E+09 | 0.209491E+10 | 0.407357E+10 |
March | 0.316157E+10 | 0.174430E+10 | 0.141727E+10 | 0.294431E+10 | 0.348609E+10 |
April | 0.288074E+10 | 0.121965E+10 | 0.166109E+10 | 0.253289E+10 | 0.296261E+10 |
May | 0.363837E+10 | 0.128265E+10 | 0.235572E+10 | 0.391724E+10 | 0.187862E+10 |
June | 0.430640E+10 | 0.207196E+10 | 0.223444E+10 | 0.589795E+10 | 0.106838E+10 |
July | 0.362566E+10 | 0.132800E+10 | 0.229765E+10 | 0.499554E+10 | 0.100814E+10 |
August | 0.378415E+10 | 0.186941E+10 | 0.191474E+10 | 0.510621E+10 | 0.112668E+10 |
September | 0.324717E+10 | 0.155723E+10 | 0.168994E+10 | 0.413728E+10 | 0.161399E+10 |
October | 0.282279E+10 | 0.161343E+10 | 0.120936E+10 | 0.290956E+10 | 0.341842E+10 |
November | 0.224153E+10 | 0.136088E+10 | 0.880649E+09 | 0.202447E+10 | 0.391059E+10 |
December | 0.187089E+10 | 0.110518E+10 | 0.765711E+09 | 0.146251E+10 | 0.490047E+10 |
Annual Sum or Average | 0.362571E+11 | 0.180828E+11 | 0.181743E+11 | 0.399694E+11 | 0.338079E+11 |
Minimum of Months | 0.187089E+10 | 0.110518E+10 | 0.765711E+09 | 0.146251E+10 | 0.100814E+10 |
Maximum of Months | 0.430640E+10 | 0.207196E+10 | 0.235572E+10 | 0.589795E+10 | 0.490047E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 43.42 | 2429.01 | 376.46 | 0.00 | 376.46 | 0.00 | 0.00 |
February | 52.54 | 2519.03 | 473.17 | 0.00 | 473.17 | 0.00 | 0.00 |
March | 211.15 | 1895.16 | 643.82 | 0.00 | 643.82 | 0.00 | 0.00 |
April | 342.15 | 1608.35 | 808.55 | 4.49 | 804.06 | 0.00 | 0.00 |
May | 887.80 | 920.18 | 1104.52 | 36.51 | 1068.01 | 0.00 | 0.00 |
June | 1600.14 | 511.75 | 1211.19 | 134.28 | 1076.91 | 0.00 | 0.00 |
July | 1546.24 | 486.99 | 1145.45 | 74.15 | 1071.31 | 0.00 | 0.00 |
August | 1165.52 | 555.51 | 911.70 | 21.57 | 890.13 | 0.00 | 0.00 |
September | 852.56 | 837.02 | 765.82 | 0.18 | 765.64 | 0.00 | 0.00 |
October | 248.78 | 1794.52 | 548.51 | 0.00 | 548.51 | 0.00 | 0.00 |
November | 84.03 | 2189.85 | 416.39 | 0.00 | 416.39 | 0.00 | 0.00 |
December | 44.61 | 2771.58 | 352.23 | 0.00 | 352.23 | 0.00 | 0.00 |
Annual Sum or Average | 592.91 | 1538.04 | 731.15 | 22.65 | 708.50 | 0.00 | 0.00 |
Minimum of Months | 43.42 | 486.99 | 352.23 | 0.00 | 352.23 | 0.00 | 0.00 |
Maximum of Months | 1600.14 | 2771.58 | 1211.19 | 134.28 | 1076.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 629.56 | 1490.57 | 785.86 | 481.60 | 304.26 | 0.00 | 0.00 |
February | 898.92 | 1575.99 | 1043.93 | 659.03 | 384.90 | 0.00 | 0.00 |
March | 1177.25 | 1197.52 | 1260.00 | 734.94 | 525.05 | 0.00 | 0.00 |
April | 1176.61 | 1033.25 | 1292.19 | 629.45 | 662.75 | 0.00 | 0.00 |
May | 1611.87 | 616.86 | 1510.55 | 630.96 | 879.59 | 0.00 | 0.00 |
June | 2455.75 | 343.98 | 1843.03 | 967.54 | 875.49 | 0.00 | 0.00 |
July | 2262.44 | 329.02 | 1675.46 | 797.81 | 877.65 | 0.00 | 0.00 |
August | 2257.82 | 372.34 | 1689.93 | 930.75 | 759.18 | 0.00 | 0.00 |
September | 1760.83 | 538.38 | 1406.11 | 763.83 | 642.28 | 0.00 | 0.00 |
October | 1003.44 | 1164.18 | 1018.30 | 557.97 | 460.34 | 0.00 | 0.00 |
November | 681.46 | 1387.57 | 792.62 | 447.52 | 345.10 | 0.00 | 0.00 |
December | 521.91 | 1728.42 | 686.20 | 395.30 | 290.90 | 0.00 | 0.00 |
Annual Sum or Average | 1372.06 | 978.33 | 1251.13 | 666.06 | 585.08 | 0.00 | 0.00 |
Minimum of Months | 521.91 | 329.02 | 686.20 | 395.30 | 290.90 | 0.00 | 0.00 |
Maximum of Months | 2455.75 | 1728.42 | 1843.03 | 967.54 | 879.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3907.24 | 2117.16 | 3607.85 | 2967.84 | 640.01 | 0.00 | 0.00 |
February | 3667.78 | 2254.64 | 3460.60 | 2759.00 | 701.60 | 0.00 | 0.00 |
March | 2756.28 | 1825.88 | 2551.43 | 1678.69 | 872.74 | 0.00 | 0.00 |
April | 1590.51 | 1641.98 | 1652.50 | 664.47 | 988.03 | 0.00 | 0.00 |
May | 1620.82 | 1018.12 | 1514.33 | 277.56 | 1236.77 | 0.00 | 0.00 |
June | 2018.68 | 568.55 | 1396.17 | 255.18 | 1140.99 | 0.00 | 0.00 |
July | 2118.03 | 531.86 | 1453.38 | 260.26 | 1193.12 | 0.00 | 0.00 |
August | 2684.96 | 593.06 | 1850.44 | 773.55 | 1076.89 | 0.00 | 0.00 |
September | 3205.76 | 874.88 | 2380.77 | 1328.45 | 1052.32 | 0.00 | 0.00 |
October | 3328.05 | 1769.59 | 2846.70 | 2019.79 | 826.91 | 0.00 | 0.00 |
November | 3863.91 | 2026.65 | 3468.30 | 2764.73 | 703.57 | 0.00 | 0.00 |
December | 3505.48 | 2426.55 | 3316.60 | 2684.41 | 632.19 | 0.00 | 0.00 |
Annual Sum or Average | 2850.99 | 1466.41 | 2452.58 | 1529.21 | 923.37 | 0.00 | 0.00 |
Minimum of Months | 1590.51 | 531.86 | 1396.17 | 255.18 | 632.19 | 0.00 | 0.00 |
Maximum of Months | 3907.24 | 2426.55 | 3607.85 | 2967.84 | 1236.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 735.03 | 1530.13 | 835.98 | 529.72 | 306.26 | 0.00 | 0.00 |
February | 870.96 | 1597.31 | 1008.08 | 624.71 | 383.37 | 0.00 | 0.00 |
March | 1101.81 | 1229.40 | 1180.39 | 651.25 | 529.15 | 0.00 | 0.00 |
April | 978.57 | 1061.43 | 1111.40 | 470.54 | 640.85 | 0.00 | 0.00 |
May | 1468.42 | 656.77 | 1358.41 | 478.89 | 879.52 | 0.00 | 0.00 |
June | 2273.79 | 388.35 | 1661.42 | 799.37 | 862.05 | 0.00 | 0.00 |
July | 1864.26 | 355.39 | 1353.66 | 495.82 | 857.85 | 0.00 | 0.00 |
August | 1907.97 | 393.54 | 1412.84 | 697.96 | 714.88 | 0.00 | 0.00 |
September | 1602.85 | 577.22 | 1252.77 | 600.78 | 651.98 | 0.00 | 0.00 |
October | 1093.93 | 1187.12 | 1053.91 | 602.38 | 451.52 | 0.00 | 0.00 |
November | 789.81 | 1407.38 | 864.79 | 525.03 | 339.76 | 0.00 | 0.00 |
December | 553.57 | 1737.57 | 698.51 | 412.63 | 285.88 | 0.00 | 0.00 |
Annual Sum or Average | 1271.81 | 1006.97 | 1149.71 | 573.40 | 576.30 | 0.00 | 0.00 |
Minimum of Months | 553.57 | 355.39 | 698.51 | 412.63 | 285.88 | 0.00 | 0.00 |
Maximum of Months | 2273.79 | 1737.57 | 1661.42 | 799.37 | 879.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 46.04 | 2495.93 | 376.46 | 0.00 | 376.46 | 0.00 | 0.00 |
February | 57.16 | 2544.31 | 473.16 | 0.00 | 473.16 | 0.00 | 0.00 |
March | 241.50 | 1894.97 | 643.82 | 0.00 | 643.82 | 0.00 | 0.00 |
April | 385.20 | 1645.38 | 808.54 | 4.49 | 804.06 | 0.00 | 0.00 |
May | 952.80 | 904.73 | 1104.52 | 36.51 | 1068.01 | 0.00 | 0.00 |
June | 1641.77 | 504.63 | 1211.18 | 134.28 | 1076.90 | 0.00 | 0.00 |
July | 1581.54 | 479.64 | 1145.45 | 74.15 | 1071.30 | 0.00 | 0.00 |
August | 1179.29 | 575.97 | 911.69 | 21.57 | 890.12 | 0.00 | 0.00 |
September | 839.75 | 919.37 | 765.82 | 0.18 | 765.64 | 0.00 | 0.00 |
October | 236.74 | 1949.94 | 548.51 | 0.00 | 548.51 | 0.00 | 0.00 |
November | 77.28 | 2352.37 | 416.39 | 0.00 | 416.39 | 0.00 | 0.00 |
December | 40.80 | 2893.07 | 352.22 | 0.00 | 352.22 | 0.00 | 0.00 |
Annual Sum or Average | 609.75 | 1591.55 | 731.15 | 22.65 | 708.50 | 0.00 | 0.00 |
Minimum of Months | 40.80 | 479.64 | 352.22 | 0.00 | 352.22 | 0.00 | 0.00 |
Maximum of Months | 1641.77 | 2893.07 | 1211.18 | 134.28 | 1076.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 629.47 | 1552.23 | 785.89 | 481.62 | 304.27 | 0.00 | 0.00 |
February | 908.54 | 1613.28 | 1043.97 | 659.05 | 384.91 | 0.00 | 0.00 |
March | 1202.06 | 1223.50 | 1260.04 | 734.97 | 525.07 | 0.00 | 0.00 |
April | 1206.41 | 1082.27 | 1292.24 | 629.47 | 662.77 | 0.00 | 0.00 |
May | 1647.91 | 624.78 | 1510.61 | 630.99 | 879.62 | 0.00 | 0.00 |
June | 2483.78 | 355.56 | 1843.10 | 967.58 | 875.52 | 0.00 | 0.00 |
July | 2287.10 | 339.38 | 1675.52 | 797.84 | 877.68 | 0.00 | 0.00 |
August | 2270.64 | 405.61 | 1689.99 | 930.79 | 759.21 | 0.00 | 0.00 |
September | 1754.15 | 608.40 | 1406.16 | 763.87 | 642.29 | 0.00 | 0.00 |
October | 991.86 | 1288.67 | 1018.34 | 557.99 | 460.35 | 0.00 | 0.00 |
November | 668.25 | 1506.17 | 792.65 | 447.54 | 345.11 | 0.00 | 0.00 |
December | 515.57 | 1821.08 | 686.22 | 395.31 | 290.91 | 0.00 | 0.00 |
Annual Sum or Average | 1382.74 | 1031.94 | 1251.18 | 666.09 | 585.09 | 0.00 | 0.00 |
Minimum of Months | 515.57 | 339.38 | 686.22 | 395.31 | 290.91 | 0.00 | 0.00 |
Maximum of Months | 2483.78 | 1821.08 | 1843.10 | 967.58 | 879.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3929.34 | 2296.67 | 3607.87 | 2967.86 | 640.01 | 0.00 | 0.00 |
February | 3725.34 | 2377.79 | 3460.62 | 2759.02 | 701.60 | 0.00 | 0.00 |
March | 2814.58 | 1894.24 | 2551.44 | 1678.70 | 872.74 | 0.00 | 0.00 |
April | 1648.14 | 1709.82 | 1652.50 | 664.48 | 988.03 | 0.00 | 0.00 |
May | 1690.00 | 1009.04 | 1514.34 | 277.57 | 1236.77 | 0.00 | 0.00 |
June | 2064.05 | 568.14 | 1396.17 | 255.18 | 1140.99 | 0.00 | 0.00 |
July | 2156.57 | 532.59 | 1453.38 | 260.26 | 1193.12 | 0.00 | 0.00 |
August | 2708.20 | 639.78 | 1850.45 | 773.55 | 1076.90 | 0.00 | 0.00 |
September | 3206.64 | 1000.18 | 2380.78 | 1328.46 | 1052.32 | 0.00 | 0.00 |
October | 3326.59 | 1998.43 | 2846.71 | 2019.80 | 826.91 | 0.00 | 0.00 |
November | 3870.55 | 2259.99 | 3468.32 | 2764.75 | 703.57 | 0.00 | 0.00 |
December | 3522.73 | 2619.95 | 3316.62 | 2684.42 | 632.20 | 0.00 | 0.00 |
Annual Sum or Average | 2883.78 | 1571.05 | 2452.59 | 1529.22 | 923.37 | 0.00 | 0.00 |
Minimum of Months | 1648.14 | 532.59 | 1396.17 | 255.18 | 632.20 | 0.00 | 0.00 |
Maximum of Months | 3929.34 | 2619.95 | 3607.87 | 2967.86 | 1236.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 745.73 | 1601.59 | 836.01 | 529.74 | 306.27 | 0.00 | 0.00 |
February | 891.07 | 1643.70 | 1008.11 | 624.73 | 383.38 | 0.00 | 0.00 |
March | 1132.85 | 1257.68 | 1180.43 | 651.27 | 529.16 | 0.00 | 0.00 |
April | 1011.70 | 1109.15 | 1111.43 | 470.56 | 640.87 | 0.00 | 0.00 |
May | 1510.34 | 665.55 | 1358.45 | 478.91 | 879.55 | 0.00 | 0.00 |
June | 2297.33 | 404.06 | 1661.47 | 799.40 | 862.07 | 0.00 | 0.00 |
July | 1885.11 | 364.55 | 1353.71 | 495.84 | 857.87 | 0.00 | 0.00 |
August | 1915.80 | 426.22 | 1412.89 | 697.99 | 714.90 | 0.00 | 0.00 |
September | 1593.23 | 652.36 | 1252.81 | 600.80 | 652.00 | 0.00 | 0.00 |
October | 1087.98 | 1317.40 | 1053.94 | 602.41 | 451.54 | 0.00 | 0.00 |
November | 787.38 | 1534.44 | 864.82 | 525.05 | 339.77 | 0.00 | 0.00 |
December | 555.21 | 1837.48 | 698.53 | 412.64 | 285.89 | 0.00 | 0.00 |
Annual Sum or Average | 1286.20 | 1064.68 | 1149.74 | 573.42 | 576.32 | 0.00 | 0.00 |
Minimum of Months | 555.21 | 364.55 | 698.53 | 412.64 | 285.89 | 0.00 | 0.00 |
Maximum of Months | 2297.33 | 1837.48 | 1661.47 | 799.40 | 879.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 36.97 | 2581.68 | 376.46 | 0.00 | 376.46 | 0.00 | 0.00 |
February | 46.01 | 2652.46 | 473.17 | 0.00 | 473.17 | 0.00 | 0.00 |
March | 201.47 | 2009.14 | 643.82 | 0.00 | 643.82 | 0.00 | 0.00 |
April | 333.82 | 1738.17 | 808.55 | 4.49 | 804.06 | 0.00 | 0.00 |
May | 861.73 | 989.48 | 1104.52 | 36.51 | 1068.01 | 0.00 | 0.00 |
June | 1590.22 | 543.06 | 1211.19 | 134.28 | 1076.91 | 0.00 | 0.00 |
July | 1537.08 | 516.47 | 1145.45 | 74.15 | 1071.31 | 0.00 | 0.00 |
August | 1154.49 | 598.38 | 911.70 | 21.57 | 890.13 | 0.00 | 0.00 |
September | 833.08 | 912.75 | 765.82 | 0.18 | 765.64 | 0.00 | 0.00 |
October | 229.74 | 1938.88 | 548.51 | 0.00 | 548.51 | 0.00 | 0.00 |
November | 73.63 | 2352.38 | 416.39 | 0.00 | 416.39 | 0.00 | 0.00 |
December | 38.78 | 2913.69 | 352.23 | 0.00 | 352.23 | 0.00 | 0.00 |
Annual Sum or Average | 581.04 | 1640.11 | 731.15 | 22.65 | 708.50 | 0.00 | 0.00 |
Minimum of Months | 36.97 | 516.47 | 352.23 | 0.00 | 352.23 | 0.00 | 0.00 |
Maximum of Months | 1590.22 | 2913.69 | 1211.19 | 134.28 | 1076.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 607.59 | 1586.26 | 785.86 | 481.60 | 304.26 | 0.00 | 0.00 |
February | 879.90 | 1661.24 | 1043.93 | 659.03 | 384.90 | 0.00 | 0.00 |
March | 1162.56 | 1266.52 | 1260.00 | 734.94 | 525.05 | 0.00 | 0.00 |
April | 1163.31 | 1110.99 | 1292.19 | 629.45 | 662.75 | 0.00 | 0.00 |
May | 1594.77 | 652.66 | 1510.55 | 630.96 | 879.59 | 0.00 | 0.00 |
June | 2455.72 | 359.89 | 1843.03 | 967.54 | 875.49 | 0.00 | 0.00 |
July | 2262.02 | 343.87 | 1675.46 | 797.81 | 877.65 | 0.00 | 0.00 |
August | 2255.89 | 393.74 | 1689.93 | 930.75 | 759.18 | 0.00 | 0.00 |
September | 1750.30 | 576.26 | 1406.11 | 763.83 | 642.28 | 0.00 | 0.00 |
October | 983.65 | 1248.20 | 1018.30 | 557.97 | 460.34 | 0.00 | 0.00 |
November | 659.33 | 1485.91 | 792.62 | 447.52 | 345.10 | 0.00 | 0.00 |
December | 504.60 | 1819.50 | 686.20 | 395.30 | 290.90 | 0.00 | 0.00 |
Annual Sum or Average | 1358.90 | 1038.74 | 1251.13 | 666.06 | 585.08 | 0.00 | 0.00 |
Minimum of Months | 504.60 | 343.87 | 686.20 | 395.30 | 290.90 | 0.00 | 0.00 |
Maximum of Months | 2455.72 | 1819.50 | 1843.03 | 967.54 | 879.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3870.99 | 2261.60 | 3607.85 | 2967.84 | 640.01 | 0.00 | 0.00 |
February | 3643.61 | 2381.96 | 3460.60 | 2759.00 | 701.60 | 0.00 | 0.00 |
March | 2741.89 | 1938.11 | 2551.43 | 1678.69 | 872.74 | 0.00 | 0.00 |
April | 1581.87 | 1771.14 | 1652.50 | 664.47 | 988.03 | 0.00 | 0.00 |
May | 1605.20 | 1092.00 | 1514.33 | 277.56 | 1236.77 | 0.00 | 0.00 |
June | 2017.64 | 607.57 | 1396.17 | 255.18 | 1140.99 | 0.00 | 0.00 |
July | 2115.48 | 567.17 | 1453.38 | 260.26 | 1193.12 | 0.00 | 0.00 |
August | 2682.06 | 638.38 | 1850.44 | 773.55 | 1076.89 | 0.00 | 0.00 |
September | 3194.49 | 947.45 | 2380.77 | 1328.45 | 1052.32 | 0.00 | 0.00 |
October | 3308.32 | 1906.10 | 2846.70 | 2019.79 | 826.91 | 0.00 | 0.00 |
November | 3833.33 | 2172.35 | 3468.30 | 2764.73 | 703.57 | 0.00 | 0.00 |
December | 3473.32 | 2566.11 | 3316.60 | 2684.41 | 632.19 | 0.00 | 0.00 |
Annual Sum or Average | 2834.40 | 1566.31 | 2452.58 | 1529.21 | 923.37 | 0.00 | 0.00 |
Minimum of Months | 1581.87 | 567.17 | 1396.17 | 255.18 | 632.19 | 0.00 | 0.00 |
Maximum of Months | 3870.99 | 2566.11 | 3607.85 | 2967.84 | 1236.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 726.75 | 1627.94 | 835.98 | 529.72 | 306.26 | 0.00 | 0.00 |
February | 865.95 | 1683.85 | 1008.08 | 624.71 | 383.37 | 0.00 | 0.00 |
March | 1099.28 | 1301.56 | 1180.39 | 651.25 | 529.15 | 0.00 | 0.00 |
April | 977.20 | 1142.98 | 1111.40 | 470.54 | 640.85 | 0.00 | 0.00 |
May | 1462.53 | 701.40 | 1358.41 | 478.89 | 879.52 | 0.00 | 0.00 |
June | 2275.44 | 412.18 | 1661.42 | 799.37 | 862.05 | 0.00 | 0.00 |
July | 1865.12 | 376.40 | 1353.66 | 495.82 | 857.85 | 0.00 | 0.00 |
August | 1906.44 | 420.65 | 1412.84 | 697.96 | 714.88 | 0.00 | 0.00 |
September | 1596.17 | 622.68 | 1252.77 | 600.78 | 651.98 | 0.00 | 0.00 |
October | 1086.30 | 1276.29 | 1053.91 | 602.38 | 451.52 | 0.00 | 0.00 |
November | 781.04 | 1508.72 | 864.79 | 525.03 | 339.76 | 0.00 | 0.00 |
December | 546.04 | 1829.63 | 698.51 | 412.63 | 285.88 | 0.00 | 0.00 |
Annual Sum or Average | 1267.42 | 1072.04 | 1149.71 | 573.40 | 576.30 | 0.00 | 0.00 |
Minimum of Months | 546.04 | 376.40 | 698.51 | 412.63 | 285.88 | 0.00 | 0.00 |
Maximum of Months | 2275.44 | 1829.63 | 1661.42 | 799.37 | 879.52 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116284E+09 | 0.650586E+10 | 0.100831E+10 | 0.00 | 0.100831E+10 | 0.00 | 0.00 |
February | 0.127103E+09 | 0.609404E+10 | 0.114468E+10 | 0.00 | 0.114468E+10 | 0.00 | 0.00 |
March | 0.565539E+09 | 0.507600E+10 | 0.172441E+10 | 0.00 | 0.172441E+10 | 0.00 | 0.00 |
April | 0.886850E+09 | 0.416884E+10 | 0.209575E+10 | 11626277.54 | 0.208413E+10 | 0.00 | 0.00 |
May | 0.237789E+10 | 0.246461E+10 | 0.295836E+10 | 97790864.98 | 0.286057E+10 | 0.00 | 0.00 |
June | 0.414757E+10 | 0.132647E+10 | 0.313940E+10 | 0.348051E+09 | 0.279135E+10 | 0.00 | 0.00 |
July | 0.414144E+10 | 0.130436E+10 | 0.306798E+10 | 0.198595E+09 | 0.286939E+10 | 0.00 | 0.00 |
August | 0.312173E+10 | 0.148789E+10 | 0.244188E+10 | 57766378.76 | 0.238412E+10 | 0.00 | 0.00 |
September | 0.220985E+10 | 0.216956E+10 | 0.198502E+10 | 466241.98 | 0.198455E+10 | 0.00 | 0.00 |
October | 0.666324E+09 | 0.480643E+10 | 0.146914E+10 | 0.00 | 0.146914E+10 | 0.00 | 0.00 |
November | 0.217799E+09 | 0.567609E+10 | 0.107929E+10 | 0.00 | 0.107929E+10 | 0.00 | 0.00 |
December | 0.119484E+09 | 0.742339E+10 | 0.943401E+09 | 0.00 | 0.943401E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186979E+11 | 0.485036E+11 | 0.230576E+11 | 0.714296E+09 | 0.223433E+11 | 0.00 | 0.00 |
Minimum of Months | 0.116284E+09 | 0.130436E+10 | 0.943401E+09 | 0.00 | 0.943401E+09 | 0.00 | 0.00 |
Maximum of Months | 0.414757E+10 | 0.742339E+10 | 0.313940E+10 | 0.348051E+09 | 0.286939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168622E+10 | 0.399234E+10 | 0.210485E+10 | 0.128991E+10 | 0.814941E+09 | 0.00 | 0.00 |
February | 0.217467E+10 | 0.381263E+10 | 0.252548E+10 | 0.159432E+10 | 0.931161E+09 | 0.00 | 0.00 |
March | 0.315313E+10 | 0.320743E+10 | 0.337477E+10 | 0.196846E+10 | 0.140631E+10 | 0.00 | 0.00 |
April | 0.304977E+10 | 0.267820E+10 | 0.334937E+10 | 0.163153E+10 | 0.171784E+10 | 0.00 | 0.00 |
May | 0.431722E+10 | 0.165219E+10 | 0.404587E+10 | 0.168997E+10 | 0.235590E+10 | 0.00 | 0.00 |
June | 0.636529E+10 | 0.891588E+09 | 0.477714E+10 | 0.250786E+10 | 0.226928E+10 | 0.00 | 0.00 |
July | 0.605973E+10 | 0.881251E+09 | 0.448756E+10 | 0.213685E+10 | 0.235071E+10 | 0.00 | 0.00 |
August | 0.604734E+10 | 0.997277E+09 | 0.452632E+10 | 0.249292E+10 | 0.203340E+10 | 0.00 | 0.00 |
September | 0.456408E+10 | 0.139548E+10 | 0.364464E+10 | 0.197986E+10 | 0.166478E+10 | 0.00 | 0.00 |
October | 0.268761E+10 | 0.311814E+10 | 0.272743E+10 | 0.149446E+10 | 0.123296E+10 | 0.00 | 0.00 |
November | 0.176634E+10 | 0.359658E+10 | 0.205447E+10 | 0.115997E+10 | 0.894502E+09 | 0.00 | 0.00 |
December | 0.139789E+10 | 0.462939E+10 | 0.183791E+10 | 0.105876E+10 | 0.779147E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.432693E+11 | 0.308525E+11 | 0.394558E+11 | 0.210049E+11 | 0.184509E+11 | 0.00 | 0.00 |
Minimum of Months | 0.139789E+10 | 0.881251E+09 | 0.183791E+10 | 0.105876E+10 | 0.779147E+09 | 0.00 | 0.00 |
Maximum of Months | 0.636529E+10 | 0.462939E+10 | 0.477714E+10 | 0.250786E+10 | 0.235590E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104652E+11 | 0.567061E+10 | 0.966327E+10 | 0.794907E+10 | 0.171420E+10 | 0.00 | 0.00 |
February | 0.887309E+10 | 0.545444E+10 | 0.837189E+10 | 0.667458E+10 | 0.169731E+10 | 0.00 | 0.00 |
March | 0.738242E+10 | 0.489045E+10 | 0.683374E+10 | 0.449620E+10 | 0.233754E+10 | 0.00 | 0.00 |
April | 0.412260E+10 | 0.425601E+10 | 0.428327E+10 | 0.172231E+10 | 0.256096E+10 | 0.00 | 0.00 |
May | 0.434120E+10 | 0.272693E+10 | 0.405599E+10 | 0.743428E+09 | 0.331257E+10 | 0.00 | 0.00 |
June | 0.523241E+10 | 0.147367E+10 | 0.361887E+10 | 0.661421E+09 | 0.295745E+10 | 0.00 | 0.00 |
July | 0.567294E+10 | 0.142452E+10 | 0.389273E+10 | 0.697072E+09 | 0.319566E+10 | 0.00 | 0.00 |
August | 0.719139E+10 | 0.158845E+10 | 0.495623E+10 | 0.207187E+10 | 0.288435E+10 | 0.00 | 0.00 |
September | 0.830932E+10 | 0.226769E+10 | 0.617095E+10 | 0.344334E+10 | 0.272761E+10 | 0.00 | 0.00 |
October | 0.891385E+10 | 0.473966E+10 | 0.762460E+10 | 0.540981E+10 | 0.221479E+10 | 0.00 | 0.00 |
November | 0.100152E+11 | 0.525309E+10 | 0.898984E+10 | 0.716619E+10 | 0.182365E+10 | 0.00 | 0.00 |
December | 0.938907E+10 | 0.649928E+10 | 0.888318E+10 | 0.718991E+10 | 0.169327E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.899087E+11 | 0.462448E+11 | 0.773446E+11 | 0.482252E+11 | 0.291194E+11 | 0.00 | 0.00 |
Minimum of Months | 0.412260E+10 | 0.142452E+10 | 0.361887E+10 | 0.661421E+09 | 0.169327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104652E+11 | 0.649928E+10 | 0.966327E+10 | 0.794907E+10 | 0.331257E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196870E+10 | 0.409829E+10 | 0.223910E+10 | 0.141881E+10 | 0.820289E+09 | 0.00 | 0.00 |
February | 0.210702E+10 | 0.386422E+10 | 0.243874E+10 | 0.151129E+10 | 0.927451E+09 | 0.00 | 0.00 |
March | 0.295109E+10 | 0.329282E+10 | 0.316157E+10 | 0.174430E+10 | 0.141727E+10 | 0.00 | 0.00 |
April | 0.253644E+10 | 0.275123E+10 | 0.288074E+10 | 0.121965E+10 | 0.166109E+10 | 0.00 | 0.00 |
May | 0.393300E+10 | 0.175909E+10 | 0.363837E+10 | 0.128265E+10 | 0.235572E+10 | 0.00 | 0.00 |
June | 0.589365E+10 | 0.100662E+10 | 0.430640E+10 | 0.207196E+10 | 0.223444E+10 | 0.00 | 0.00 |
July | 0.499322E+10 | 0.951879E+09 | 0.362566E+10 | 0.132800E+10 | 0.229765E+10 | 0.00 | 0.00 |
August | 0.511030E+10 | 0.105406E+10 | 0.378415E+10 | 0.186941E+10 | 0.191474E+10 | 0.00 | 0.00 |
September | 0.415459E+10 | 0.149615E+10 | 0.324717E+10 | 0.155723E+10 | 0.168994E+10 | 0.00 | 0.00 |
October | 0.292999E+10 | 0.317957E+10 | 0.282279E+10 | 0.161343E+10 | 0.120936E+10 | 0.00 | 0.00 |
November | 0.204718E+10 | 0.364793E+10 | 0.224153E+10 | 0.136088E+10 | 0.880649E+09 | 0.00 | 0.00 |
December | 0.148268E+10 | 0.465392E+10 | 0.187089E+10 | 0.110518E+10 | 0.765711E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.401079E+11 | 0.317558E+11 | 0.362571E+11 | 0.180828E+11 | 0.181743E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148268E+10 | 0.951879E+09 | 0.187089E+10 | 0.110518E+10 | 0.765711E+09 | 0.00 | 0.00 |
Maximum of Months | 0.589365E+10 | 0.465392E+10 | 0.430640E+10 | 0.207196E+10 | 0.235572E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123307E+09 | 0.668510E+10 | 0.100831E+10 | 0.00 | 0.100831E+10 | 0.00 | 0.00 |
February | 0.138278E+09 | 0.615519E+10 | 0.114468E+10 | 0.00 | 0.114468E+10 | 0.00 | 0.00 |
March | 0.646822E+09 | 0.507548E+10 | 0.172440E+10 | 0.00 | 0.172440E+10 | 0.00 | 0.00 |
April | 0.998451E+09 | 0.426483E+10 | 0.209574E+10 | 11626210.27 | 0.208412E+10 | 0.00 | 0.00 |
May | 0.255198E+10 | 0.242324E+10 | 0.295834E+10 | 97790299.17 | 0.286055E+10 | 0.00 | 0.00 |
June | 0.425548E+10 | 0.130801E+10 | 0.313938E+10 | 0.348049E+09 | 0.279133E+10 | 0.00 | 0.00 |
July | 0.423599E+10 | 0.128467E+10 | 0.306797E+10 | 0.198594E+09 | 0.286937E+10 | 0.00 | 0.00 |
August | 0.315860E+10 | 0.154269E+10 | 0.244187E+10 | 57766044.53 | 0.238411E+10 | 0.00 | 0.00 |
September | 0.217663E+10 | 0.238302E+10 | 0.198500E+10 | 466239.28 | 0.198454E+10 | 0.00 | 0.00 |
October | 0.634079E+09 | 0.522271E+10 | 0.146913E+10 | 0.00 | 0.146913E+10 | 0.00 | 0.00 |
November | 0.200309E+09 | 0.609734E+10 | 0.107928E+10 | 0.00 | 0.107928E+10 | 0.00 | 0.00 |
December | 0.109285E+09 | 0.774880E+10 | 0.943395E+09 | 0.00 | 0.943395E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.192292E+11 | 0.501911E+11 | 0.230575E+11 | 0.714292E+09 | 0.223432E+11 | 0.00 | 0.00 |
Minimum of Months | 0.109285E+09 | 0.128467E+10 | 0.943395E+09 | 0.00 | 0.943395E+09 | 0.00 | 0.00 |
Maximum of Months | 0.425548E+10 | 0.774880E+10 | 0.313938E+10 | 0.348049E+09 | 0.286937E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168596E+10 | 0.415750E+10 | 0.210493E+10 | 0.128996E+10 | 0.814964E+09 | 0.00 | 0.00 |
February | 0.219795E+10 | 0.390284E+10 | 0.252557E+10 | 0.159438E+10 | 0.931185E+09 | 0.00 | 0.00 |
March | 0.321961E+10 | 0.327702E+10 | 0.337489E+10 | 0.196854E+10 | 0.140635E+10 | 0.00 | 0.00 |
April | 0.312701E+10 | 0.280525E+10 | 0.334948E+10 | 0.163159E+10 | 0.171789E+10 | 0.00 | 0.00 |
May | 0.441376E+10 | 0.167341E+10 | 0.404601E+10 | 0.169003E+10 | 0.235598E+10 | 0.00 | 0.00 |
June | 0.643795E+10 | 0.921601E+09 | 0.477730E+10 | 0.250796E+10 | 0.226935E+10 | 0.00 | 0.00 |
July | 0.612578E+10 | 0.908993E+09 | 0.448771E+10 | 0.213694E+10 | 0.235077E+10 | 0.00 | 0.00 |
August | 0.608169E+10 | 0.108638E+10 | 0.452648E+10 | 0.249302E+10 | 0.203346E+10 | 0.00 | 0.00 |
September | 0.454675E+10 | 0.157697E+10 | 0.364477E+10 | 0.197994E+10 | 0.166483E+10 | 0.00 | 0.00 |
October | 0.265661E+10 | 0.345157E+10 | 0.272752E+10 | 0.149452E+10 | 0.123300E+10 | 0.00 | 0.00 |
November | 0.173209E+10 | 0.390400E+10 | 0.205454E+10 | 0.116001E+10 | 0.894527E+09 | 0.00 | 0.00 |
December | 0.138089E+10 | 0.487758E+10 | 0.183797E+10 | 0.105880E+10 | 0.779170E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.436060E+11 | 0.325431E+11 | 0.394572E+11 | 0.210057E+11 | 0.184515E+11 | 0.00 | 0.00 |
Minimum of Months | 0.138089E+10 | 0.908993E+09 | 0.183797E+10 | 0.105880E+10 | 0.779170E+09 | 0.00 | 0.00 |
Maximum of Months | 0.643795E+10 | 0.487758E+10 | 0.477730E+10 | 0.250796E+10 | 0.235598E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105243E+11 | 0.615140E+10 | 0.966332E+10 | 0.794912E+10 | 0.171421E+10 | 0.00 | 0.00 |
February | 0.901234E+10 | 0.575235E+10 | 0.837193E+10 | 0.667462E+10 | 0.169731E+10 | 0.00 | 0.00 |
March | 0.753858E+10 | 0.507354E+10 | 0.683377E+10 | 0.449622E+10 | 0.233755E+10 | 0.00 | 0.00 |
April | 0.427199E+10 | 0.443186E+10 | 0.428329E+10 | 0.172232E+10 | 0.256097E+10 | 0.00 | 0.00 |
May | 0.452650E+10 | 0.270262E+10 | 0.405601E+10 | 0.743433E+09 | 0.331258E+10 | 0.00 | 0.00 |
June | 0.535002E+10 | 0.147261E+10 | 0.361888E+10 | 0.661425E+09 | 0.295746E+10 | 0.00 | 0.00 |
July | 0.577615E+10 | 0.142649E+10 | 0.389274E+10 | 0.697077E+09 | 0.319566E+10 | 0.00 | 0.00 |
August | 0.725364E+10 | 0.171358E+10 | 0.495624E+10 | 0.207189E+10 | 0.288436E+10 | 0.00 | 0.00 |
September | 0.831161E+10 | 0.259246E+10 | 0.617098E+10 | 0.344336E+10 | 0.272762E+10 | 0.00 | 0.00 |
October | 0.890993E+10 | 0.535260E+10 | 0.762463E+10 | 0.540984E+10 | 0.221479E+10 | 0.00 | 0.00 |
November | 0.100325E+11 | 0.585788E+10 | 0.898989E+10 | 0.716623E+10 | 0.182365E+10 | 0.00 | 0.00 |
December | 0.943528E+10 | 0.701728E+10 | 0.888323E+10 | 0.718996E+10 | 0.169327E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.909428E+11 | 0.495447E+11 | 0.773449E+11 | 0.482255E+11 | 0.291194E+11 | 0.00 | 0.00 |
Minimum of Months | 0.427199E+10 | 0.142649E+10 | 0.361888E+10 | 0.661425E+09 | 0.169327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105243E+11 | 0.701728E+10 | 0.966332E+10 | 0.794912E+10 | 0.331258E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199736E+10 | 0.428971E+10 | 0.223917E+10 | 0.141886E+10 | 0.820310E+09 | 0.00 | 0.00 |
February | 0.215567E+10 | 0.397644E+10 | 0.243882E+10 | 0.151135E+10 | 0.927474E+09 | 0.00 | 0.00 |
March | 0.303423E+10 | 0.336857E+10 | 0.316167E+10 | 0.174436E+10 | 0.141731E+10 | 0.00 | 0.00 |
April | 0.262232E+10 | 0.287493E+10 | 0.288083E+10 | 0.121969E+10 | 0.166114E+10 | 0.00 | 0.00 |
May | 0.404530E+10 | 0.178260E+10 | 0.363848E+10 | 0.128270E+10 | 0.235578E+10 | 0.00 | 0.00 |
June | 0.595467E+10 | 0.104733E+10 | 0.430654E+10 | 0.207204E+10 | 0.223449E+10 | 0.00 | 0.00 |
July | 0.504909E+10 | 0.976419E+09 | 0.362577E+10 | 0.132805E+10 | 0.229772E+10 | 0.00 | 0.00 |
August | 0.513128E+10 | 0.114158E+10 | 0.378427E+10 | 0.186948E+10 | 0.191479E+10 | 0.00 | 0.00 |
September | 0.412964E+10 | 0.169093E+10 | 0.324727E+10 | 0.155729E+10 | 0.168999E+10 | 0.00 | 0.00 |
October | 0.291406E+10 | 0.352853E+10 | 0.282288E+10 | 0.161349E+10 | 0.120939E+10 | 0.00 | 0.00 |
November | 0.204090E+10 | 0.397727E+10 | 0.224160E+10 | 0.136093E+10 | 0.880671E+09 | 0.00 | 0.00 |
December | 0.148707E+10 | 0.492150E+10 | 0.187095E+10 | 0.110522E+10 | 0.765732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.405616E+11 | 0.335758E+11 | 0.362583E+11 | 0.180835E+11 | 0.181748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148707E+10 | 0.976419E+09 | 0.187095E+10 | 0.110522E+10 | 0.765732E+09 | 0.00 | 0.00 |
Maximum of Months | 0.595467E+10 | 0.492150E+10 | 0.430654E+10 | 0.207204E+10 | 0.235578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 99031926.07 | 0.691478E+10 | 0.100831E+10 | 0.00 | 0.100831E+10 | 0.00 | 0.00 |
February | 0.111315E+09 | 0.641684E+10 | 0.114468E+10 | 0.00 | 0.114468E+10 | 0.00 | 0.00 |
March | 0.539621E+09 | 0.538129E+10 | 0.172441E+10 | 0.00 | 0.172441E+10 | 0.00 | 0.00 |
April | 0.865270E+09 | 0.450533E+10 | 0.209575E+10 | 11626277.54 | 0.208413E+10 | 0.00 | 0.00 |
May | 0.230806E+10 | 0.265022E+10 | 0.295836E+10 | 97790864.98 | 0.286057E+10 | 0.00 | 0.00 |
June | 0.412185E+10 | 0.140760E+10 | 0.313940E+10 | 0.348051E+09 | 0.279135E+10 | 0.00 | 0.00 |
July | 0.411691E+10 | 0.138331E+10 | 0.306798E+10 | 0.198595E+09 | 0.286939E+10 | 0.00 | 0.00 |
August | 0.309219E+10 | 0.160271E+10 | 0.244188E+10 | 57766378.76 | 0.238412E+10 | 0.00 | 0.00 |
September | 0.215933E+10 | 0.236585E+10 | 0.198502E+10 | 466241.98 | 0.198455E+10 | 0.00 | 0.00 |
October | 0.615338E+09 | 0.519310E+10 | 0.146914E+10 | 0.00 | 0.146914E+10 | 0.00 | 0.00 |
November | 0.190860E+09 | 0.609738E+10 | 0.107929E+10 | 0.00 | 0.107929E+10 | 0.00 | 0.00 |
December | 0.103867E+09 | 0.780402E+10 | 0.943401E+09 | 0.00 | 0.943401E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183237E+11 | 0.517224E+11 | 0.230576E+11 | 0.714296E+09 | 0.223433E+11 | 0.00 | 0.00 |
Minimum of Months | 99031926.07 | 0.138331E+10 | 0.943401E+09 | 0.00 | 0.943401E+09 | 0.00 | 0.00 |
Maximum of Months | 0.412185E+10 | 0.780402E+10 | 0.313940E+10 | 0.348051E+09 | 0.286939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162736E+10 | 0.424863E+10 | 0.210485E+10 | 0.128991E+10 | 0.814941E+09 | 0.00 | 0.00 |
February | 0.212865E+10 | 0.401888E+10 | 0.252548E+10 | 0.159432E+10 | 0.931161E+09 | 0.00 | 0.00 |
March | 0.311380E+10 | 0.339225E+10 | 0.337477E+10 | 0.196846E+10 | 0.140631E+10 | 0.00 | 0.00 |
April | 0.301530E+10 | 0.287970E+10 | 0.334937E+10 | 0.163153E+10 | 0.171784E+10 | 0.00 | 0.00 |
May | 0.427143E+10 | 0.174809E+10 | 0.404587E+10 | 0.168997E+10 | 0.235590E+10 | 0.00 | 0.00 |
June | 0.636522E+10 | 0.932844E+09 | 0.477714E+10 | 0.250786E+10 | 0.226928E+10 | 0.00 | 0.00 |
July | 0.605860E+10 | 0.921023E+09 | 0.448756E+10 | 0.213685E+10 | 0.235071E+10 | 0.00 | 0.00 |
August | 0.604217E+10 | 0.105459E+10 | 0.452632E+10 | 0.249292E+10 | 0.203340E+10 | 0.00 | 0.00 |
September | 0.453678E+10 | 0.149368E+10 | 0.364464E+10 | 0.197986E+10 | 0.166478E+10 | 0.00 | 0.00 |
October | 0.263461E+10 | 0.334317E+10 | 0.272743E+10 | 0.149446E+10 | 0.123296E+10 | 0.00 | 0.00 |
November | 0.170899E+10 | 0.385147E+10 | 0.205447E+10 | 0.115997E+10 | 0.894502E+09 | 0.00 | 0.00 |
December | 0.135152E+10 | 0.487335E+10 | 0.183791E+10 | 0.105876E+10 | 0.779147E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.428544E+11 | 0.327577E+11 | 0.394558E+11 | 0.210049E+11 | 0.184509E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135152E+10 | 0.921023E+09 | 0.183791E+10 | 0.105876E+10 | 0.779147E+09 | 0.00 | 0.00 |
Maximum of Months | 0.636522E+10 | 0.487335E+10 | 0.477714E+10 | 0.250786E+10 | 0.235590E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103681E+11 | 0.605747E+10 | 0.966327E+10 | 0.794907E+10 | 0.171420E+10 | 0.00 | 0.00 |
February | 0.881463E+10 | 0.576244E+10 | 0.837189E+10 | 0.667458E+10 | 0.169731E+10 | 0.00 | 0.00 |
March | 0.734389E+10 | 0.519105E+10 | 0.683374E+10 | 0.449620E+10 | 0.233754E+10 | 0.00 | 0.00 |
April | 0.410021E+10 | 0.459079E+10 | 0.428327E+10 | 0.172231E+10 | 0.256096E+10 | 0.00 | 0.00 |
May | 0.429936E+10 | 0.292482E+10 | 0.405599E+10 | 0.743428E+09 | 0.331257E+10 | 0.00 | 0.00 |
June | 0.522973E+10 | 0.157481E+10 | 0.361887E+10 | 0.661421E+09 | 0.295745E+10 | 0.00 | 0.00 |
July | 0.566609E+10 | 0.151912E+10 | 0.389273E+10 | 0.697072E+09 | 0.319566E+10 | 0.00 | 0.00 |
August | 0.718363E+10 | 0.170984E+10 | 0.495623E+10 | 0.207187E+10 | 0.288435E+10 | 0.00 | 0.00 |
September | 0.828011E+10 | 0.245579E+10 | 0.617095E+10 | 0.344334E+10 | 0.272761E+10 | 0.00 | 0.00 |
October | 0.886100E+10 | 0.510531E+10 | 0.762460E+10 | 0.540981E+10 | 0.221479E+10 | 0.00 | 0.00 |
November | 0.993599E+10 | 0.563074E+10 | 0.898984E+10 | 0.716619E+10 | 0.182365E+10 | 0.00 | 0.00 |
December | 0.930294E+10 | 0.687306E+10 | 0.888318E+10 | 0.718991E+10 | 0.169327E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.893856E+11 | 0.493953E+11 | 0.773446E+11 | 0.482252E+11 | 0.291194E+11 | 0.00 | 0.00 |
Minimum of Months | 0.410021E+10 | 0.151912E+10 | 0.361887E+10 | 0.661421E+09 | 0.169327E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103681E+11 | 0.687306E+10 | 0.966327E+10 | 0.794907E+10 | 0.331257E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.194653E+10 | 0.436028E+10 | 0.223910E+10 | 0.141881E+10 | 0.820289E+09 | 0.00 | 0.00 |
February | 0.209491E+10 | 0.407357E+10 | 0.243874E+10 | 0.151129E+10 | 0.927451E+09 | 0.00 | 0.00 |
March | 0.294431E+10 | 0.348609E+10 | 0.316157E+10 | 0.174430E+10 | 0.141727E+10 | 0.00 | 0.00 |
April | 0.253289E+10 | 0.296261E+10 | 0.288074E+10 | 0.121965E+10 | 0.166109E+10 | 0.00 | 0.00 |
May | 0.391724E+10 | 0.187862E+10 | 0.363837E+10 | 0.128265E+10 | 0.235572E+10 | 0.00 | 0.00 |
June | 0.589795E+10 | 0.106838E+10 | 0.430640E+10 | 0.207196E+10 | 0.223444E+10 | 0.00 | 0.00 |
July | 0.499554E+10 | 0.100814E+10 | 0.362566E+10 | 0.132800E+10 | 0.229765E+10 | 0.00 | 0.00 |
August | 0.510621E+10 | 0.112668E+10 | 0.378415E+10 | 0.186941E+10 | 0.191474E+10 | 0.00 | 0.00 |
September | 0.413728E+10 | 0.161399E+10 | 0.324717E+10 | 0.155723E+10 | 0.168994E+10 | 0.00 | 0.00 |
October | 0.290956E+10 | 0.341842E+10 | 0.282279E+10 | 0.161343E+10 | 0.120936E+10 | 0.00 | 0.00 |
November | 0.202447E+10 | 0.391059E+10 | 0.224153E+10 | 0.136088E+10 | 0.880649E+09 | 0.00 | 0.00 |
December | 0.146251E+10 | 0.490047E+10 | 0.187089E+10 | 0.110518E+10 | 0.765711E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.399694E+11 | 0.338079E+11 | 0.362571E+11 | 0.180828E+11 | 0.181743E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146251E+10 | 0.100814E+10 | 0.187089E+10 | 0.110518E+10 | 0.765711E+09 | 0.00 | 0.00 |
Maximum of Months | 0.589795E+10 | 0.490047E+10 | 0.430640E+10 | 0.207196E+10 | 0.235572E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.510373E+10 | -0.486322E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -240501540.6 | 60.05 | 0.00 | 0.00 |
February | 0.469126E+10 | -0.447350E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -217764636.0 | 60.05 | 0.00 | 0.00 |
March | 0.545782E+10 | -0.521901E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -238807116.9 | 60.05 | 0.00 | 0.00 |
April | 0.474560E+10 | -0.451551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -230088973.3 | 60.05 | 0.00 | 0.00 |
May | 0.481541E+10 | -0.458213E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233279458.9 | 60.05 | 0.00 | 0.00 |
June | 0.451259E+10 | -0.428800E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224590588.6 | 60.05 | 0.00 | 0.00 |
July | 0.409153E+10 | -0.386026E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231268888.7 | 60.05 | 0.00 | 0.00 |
August | 0.443417E+10 | -0.420254E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231627995.0 | 60.05 | 0.00 | 0.00 |
September | 0.407967E+10 | -0.385535E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224318484.4 | 60.05 | 0.00 | 0.00 |
October | 0.440699E+10 | -0.417274E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234255077.1 | 60.05 | 0.00 | 0.00 |
November | 0.458248E+10 | -0.435358E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -228899488.1 | 60.05 | 0.00 | 0.00 |
December | 0.479250E+10 | -0.455072E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241778071.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.557138E+11 | -0.529366E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.277718E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.407967E+10 | -0.521901E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -241778071.0 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.545782E+10 | -0.385535E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -217764636.0 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 394.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 354.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 262.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 257.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 251.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3902.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 430.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120040E+10 | 13316.29 | 05-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.868110E+09 | 8266.35 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229608E+09 | 6671.32 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93444448.47 | 5204.76 | 17-APR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 263185.06 | 5.83 | 19-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 593637.11 | 5.56 | 25-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410835.31 | 5.47 | 03-AUG-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28488.25 | 4.57 | 01-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.504140E+09 | 7473.57 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452857E+09 | 9603.14 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302701E+10 | 14889.95 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.637687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.302701E+10 | 14889.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 876414.24 | 14606.90 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10118200.95 | 14606.09 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10994615.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10118200.95 | 14606.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.311261E+10 | 10226.11 | 11-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363919E+10 | 10226.64 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355519E+10 | 10226.80 | 21-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.276573E+10 | 10228.04 | 25-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100067E+10 | 10269.17 | 30-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37650900.03 | 6901.62 | 09-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20571031.50 | 6722.62 | 03-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23645947.02 | 5238.66 | 23-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160095E+09 | 10221.53 | 22-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208609E+10 | 10267.12 | 12-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235237E+10 | 10223.56 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393331E+10 | 10354.50 | 21-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 20571031.50 | 5238.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.393331E+10 | 10354.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186601E+10 | 7228.58 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199267E+10 | 7236.78 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139645E+10 | 7222.45 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.867435E+09 | 7215.20 | 18-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80608556.87 | 7211.26 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1901748.24 | 3008.14 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.550743E+09 | 7206.92 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.949034E+09 | 7216.16 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221148E+10 | 7237.05 | 26-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.991634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221148E+10 | 7237.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373410E+10 | 10072.51 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408283E+10 | 10081.79 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.287373E+10 | 10075.45 | 28-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184615E+10 | 10067.57 | 26-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223421E+09 | 10060.68 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7743277.14 | 6048.65 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.885534E+09 | 10056.22 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.183838E+10 | 10063.66 | 21-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402856E+10 | 10140.85 | 23-DEC-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.408283E+10 | 10140.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212071E+10 | 7642.90 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228967E+10 | 7663.42 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174156E+10 | 7639.21 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116635E+10 | 7644.38 | 25-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165962E+09 | 7635.72 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8881097.04 | 5420.11 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.633252E+09 | 7631.55 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109648E+10 | 7631.98 | 01-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.248025E+10 | 7709.23 | 23-DEC-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.248025E+10 | 7709.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.266203E+10 | 16462.45 | 05-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237739E+10 | 12068.02 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.953281E+09 | 10897.91 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448527E+09 | 9912.00 | 17-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4388833.17 | 1879.75 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 257490.07 | 4.85 | 19-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 535902.66 | 5.10 | 25-JUL-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 343021.87 | 5.06 | 24-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1474094.51 | 1212.48 | 22-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130226E+10 | 12573.00 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177591E+10 | 14014.29 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.493877E+10 | 18113.81 | 23-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 257490.07 | 4.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.493877E+10 | 18113.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.334112E+09 | 21106.95 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.615376E+09 | 21064.35 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285201E+09 | 21106.61 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212514E+09 | 21124.86 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8142800.34 | 18119.30 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104992E+09 | 21015.84 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75311936.66 | 21078.75 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.824234E+09 | 21120.54 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.824234E+09 | 21124.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133242E+10 | 10643.75 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168598E+10 | 10656.32 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133776E+10 | 10659.99 | 20-MAR-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.984412E+09 | 10652.19 | 03-APR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105524E+09 | 10596.91 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20214006.07 | 9985.29 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.949163E+09 | 10629.61 | 30-OCT-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108771E+10 | 10650.91 | 29-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235255E+10 | 10732.65 | 23-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.985575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.235255E+10 | 10732.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164801E+10 | 8176.21 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171874E+10 | 8179.03 | 13-FEB-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113263E+10 | 8173.34 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.734996E+09 | 8186.99 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66422365.74 | 8148.84 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24126813.69 | 5889.54 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.851541E+09 | 8175.01 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128464E+10 | 8172.39 | 30-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256790E+10 | 8250.75 | 23-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256790E+10 | 8250.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.273782E+10 | 10387.20 | 30-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294821E+10 | 10377.28 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181078E+10 | 10380.93 | 20-MAR-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115850E+10 | 10373.31 | 03-APR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104079E+09 | 10319.62 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26897217.69 | 10028.92 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112387E+10 | 10354.96 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199524E+10 | 10385.41 | 02-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412650E+10 | 10545.98 | 22-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.412650E+10 | 10545.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208857E+10 | 8553.60 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217827E+10 | 8558.99 | 13-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155457E+10 | 8548.93 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107594E+10 | 8552.90 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143968E+09 | 8526.62 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 57720.49 | 288.60 | 23-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 56823283.00 | 6620.15 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104988E+10 | 8551.67 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163925E+10 | 8547.39 | 30-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309071E+10 | 8711.06 | 23-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309071E+10 | 8711.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344179E+10 | 15468.82 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343790E+10 | 14426.36 | 13-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149053E+10 | 13008.85 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.648609E+09 | 10137.00 | 17-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15818383.85 | 4686.62 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 187936.53 | 5.82 | 16-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 451108.29 | 6.05 | 24-JUL-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 214404.03 | 5.62 | 24-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21952818.30 | 5994.11 | 22-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159709E+10 | 13050.26 | 31-OCT-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226603E+10 | 14520.12 | 30-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.614265E+10 | 15802.52 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 187936.53 | 5.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.614265E+10 | 15802.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.378014E+10 | 32280.68 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380678E+10 | 32166.56 | 21-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232986E+10 | 32192.07 | 21-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172083E+10 | 32140.65 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185264E+09 | 32039.44 | 01-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20004100.62 | 21069.26 | 22-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154960E+10 | 32101.78 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.246855E+10 | 32129.55 | 24-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.562387E+10 | 32975.91 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.562387E+10 | 32975.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.315090E+10 | 14093.10 | 05-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356792E+10 | 13804.14 | 08-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304658E+10 | 13794.28 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.238200E+10 | 13807.14 | 17-APR-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.455876E+09 | 13823.77 | 01-MAY-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2470869.51 | 1730.75 | 10-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3561695.27 | 4420.78 | 23-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171281E+09 | 13679.73 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228025E+10 | 13794.25 | 30-OCT-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265825E+10 | 13802.23 | 01-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.499795E+10 | 14422.98 | 23-DEC-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.499795E+10 | 14422.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.306473E+10 | 9497.31 | 05-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297273E+10 | 9298.28 | 22-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213736E+10 | 9295.30 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145380E+10 | 9297.74 | 25-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157588E+09 | 9288.10 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 175934.08 | 879.67 | 23-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88695434.39 | 9218.11 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171085E+10 | 9295.52 | 30-OCT-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.245162E+10 | 9308.62 | 02-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.453870E+10 | 9720.01 | 23-DEC-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453870E+10 | 9720.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.567738E+10 | 13947.92 | 05-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.564773E+10 | 13686.35 | 09-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.399281E+10 | 13692.97 | 28-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274352E+10 | 13678.82 | 18-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.447084E+09 | 13681.36 | 01-MAY-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3821622.25 | 4204.73 | 23-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.236425E+09 | 13625.85 | 22-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290331E+10 | 13652.14 | 30-OCT-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.441024E+10 | 13675.80 | 02-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.786946E+10 | 14292.74 | 22-DEC-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.786946E+10 | 14292.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365334E+10 | 10461.80 | 05-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.364282E+10 | 10230.36 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279901E+10 | 10236.89 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200758E+10 | 10239.19 | 25-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.439084E+09 | 10230.13 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7323913.94 | 2211.81 | 10-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1612214.64 | 694.67 | 29-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10080957.98 | 4276.18 | 23-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.222092E+09 | 10151.84 | 22-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212115E+10 | 10231.36 | 30-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295821E+10 | 10232.91 | 25-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.516843E+10 | 10721.56 | 22-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1612214.64 | 694.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.516843E+10 | 10721.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.111256E+10 | 0.111184E+10 | 26572.77 | 20-JAN-14:00 | 26572.77 | 0.00 |
February | 0.00 | 0.00 | 0.377573E+09 | 0.377566E+09 | 16970.70 | 18-FEB-13:30 | 16970.70 | 0.00 |
March | 0.00 | 0.00 | 0.382367E+10 | 0.382321E+10 | 44918.75 | 14-MAR-13:00 | 44918.75 | 0.00 |
April | 0.00 | 0.00 | 0.368004E+10 | 0.362747E+10 | 27060.95 | 20-APR-13:00 | 27060.95 | 0.00 |
May | 0.00 | 0.00 | 0.168145E+11 | 0.163974E+11 | 52025.47 | 17-MAY-14:10 | 52025.47 | 0.00 |
June | 0.00 | 0.00 | 0.609273E+11 | 0.579136E+11 | 80892.46 | 26-JUN-15:00 | 80892.46 | 0.00 |
July | 0.00 | 0.00 | 0.628736E+11 | 0.578928E+11 | 78511.63 | 17-JUL-14:10 | 78511.63 | 0.00 |
August | 0.00 | 0.00 | 0.629287E+11 | 0.596531E+11 | 82967.15 | 16-AUG-15:40 | 82967.15 | 0.00 |
September | 0.00 | 0.00 | 0.441745E+11 | 0.436530E+11 | 77330.69 | 12-SEP-16:00 | 77330.69 | 0.00 |
October | 0.00 | 0.00 | 0.802706E+10 | 0.801297E+10 | 62700.04 | 11-OCT-15:40 | 62700.04 | 0.00 |
November | 0.00 | 0.00 | 0.254425E+10 | 0.254414E+10 | 38807.42 | 07-NOV-15:03 | 38807.42 | 0.00 |
December | 0.00 | 0.00 | 0.134827E+10 | 0.134826E+10 | 27797.62 | 01-DEC-14:00 | 27797.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.268632E+12 | 0.256355E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.377573E+09 | 0.377566E+09 | 16970.70 | 16970.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.629287E+11 | 0.596531E+11 | 82967.15 | 82967.15 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112677E+10 | 0.112627E+10 | 30481.56 | 20-JAN-13:02 | 30481.56 | 0.00 |
February | 0.00 | 0.00 | 0.408776E+09 | 0.408761E+09 | 20161.68 | 26-FEB-13:12 | 20161.68 | 0.00 |
March | 0.00 | 0.00 | 0.370992E+10 | 0.370942E+10 | 42533.81 | 14-MAR-13:00 | 42533.81 | 0.00 |
April | 0.00 | 0.00 | 0.343911E+10 | 0.339022E+10 | 27543.01 | 20-APR-13:00 | 27543.01 | 0.00 |
May | 0.00 | 0.00 | 0.159029E+11 | 0.154703E+11 | 53411.47 | 17-MAY-14:05 | 53411.47 | 0.00 |
June | 0.00 | 0.00 | 0.573313E+11 | 0.544348E+11 | 79835.03 | 26-JUN-15:00 | 79835.03 | 0.00 |
July | 0.00 | 0.00 | 0.586128E+11 | 0.539643E+11 | 77411.80 | 17-JUL-14:05 | 77411.80 | 0.00 |
August | 0.00 | 0.00 | 0.560198E+11 | 0.529814E+11 | 77523.88 | 16-AUG-14:05 | 77523.88 | 0.00 |
September | 0.00 | 0.00 | 0.372350E+11 | 0.367132E+11 | 68296.01 | 12-SEP-16:00 | 68296.01 | 0.00 |
October | 0.00 | 0.00 | 0.682988E+10 | 0.681600E+10 | 55605.75 | 11-OCT-15:10 | 55605.75 | 0.00 |
November | 0.00 | 0.00 | 0.220932E+10 | 0.220870E+10 | 33537.34 | 07-NOV-14:00 | 33537.34 | 0.00 |
December | 0.00 | 0.00 | 0.125302E+10 | 0.125302E+10 | 27316.62 | 01-DEC-14:00 | 27316.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.244079E+12 | 0.232476E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.408776E+09 | 0.408761E+09 | 20161.68 | 20161.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.586128E+11 | 0.544348E+11 | 79835.03 | 79835.03 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.106717E+10 | 0.106616E+10 | 26308.23 | 20-JAN-13:30 | 26308.23 | 0.00 |
February | 0.00 | 0.00 | 0.419302E+09 | 0.418757E+09 | 19783.61 | 18-FEB-13:30 | 19783.61 | 0.00 |
March | 0.00 | 0.00 | 0.379475E+10 | 0.379321E+10 | 52808.80 | 14-MAR-13:00 | 52808.80 | 0.00 |
April | 0.00 | 0.00 | 0.385083E+10 | 0.377490E+10 | 30961.67 | 20-APR-13:00 | 30961.67 | 0.00 |
May | 0.00 | 0.00 | 0.187273E+11 | 0.180068E+11 | 68995.09 | 31-MAY-15:00 | 68995.09 | 0.00 |
June | 0.00 | 0.00 | 0.679317E+11 | 0.643135E+11 | 100077.96 | 26-JUN-15:00 | 100077.96 | 0.00 |
July | 0.00 | 0.00 | 0.683267E+11 | 0.629342E+11 | 92773.68 | 17-JUL-13:40 | 92773.68 | 0.00 |
August | 0.00 | 0.00 | 0.649130E+11 | 0.612135E+11 | 97227.22 | 16-AUG-14:30 | 97227.22 | 0.00 |
September | 0.00 | 0.00 | 0.410990E+11 | 0.402265E+11 | 78801.75 | 12-SEP-14:00 | 78801.75 | 0.00 |
October | 0.00 | 0.00 | 0.691184E+10 | 0.688019E+10 | 65320.80 | 11-OCT-14:30 | 65320.80 | 0.00 |
November | 0.00 | 0.00 | 0.203913E+10 | 0.203440E+10 | 31984.79 | 07-NOV-14:40 | 31984.79 | 0.00 |
December | 0.00 | 0.00 | 0.131558E+10 | 0.131546E+10 | 27934.97 | 01-DEC-14:00 | 27934.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.280396E+12 | 0.265978E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.419302E+09 | 0.418757E+09 | 19783.61 | 19783.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.683267E+11 | 0.643135E+11 | 100077.96 | 100077.96 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 16885.43 | 352652.10 | 23-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 19460.84 | 282924.70 | 22-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 12094.91 | 306185.45 | 30-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 8535.68 | 320433.38 | 26-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1339.54 | 379731.22 | 01-MAY-05:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 16.43 | 15216.28 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 8.89 | 14259.29 | 03-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 13.45 | 14877.14 | 23-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 409.06 | 216523.08 | 22-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 8226.53 | 259258.06 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12152.51 | 287640.33 | 25-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25161.28 | 312554.67 | 29-DEC-06:01 |
Annual Sum or Average | 0.00 | 8640.94 | ||||
Minimum of Months | 0.00 | 0.00 | 8.89 | 14259.29 | ||
Maximum of Months | 0.00 | 0.00 | 25161.28 | 379731.22 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1806.24 | 6633.42 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1839.63 | 6650.91 | 13-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1938.73 | 6625.00 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1732.72 | 6419.08 | 03-APR-11:12 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1701.34 | 6126.07 | 01-MAY-11:17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1644.90 | 5759.55 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1432.33 | 5439.71 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1559.72 | 5288.02 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1478.36 | 5461.95 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1548.77 | 5790.88 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1670.26 | 6145.66 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1689.79 | 6442.60 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1669.26 | ||||
Minimum of Months | 0.00 | 0.00 | 1432.33 | 5288.02 | ||
Maximum of Months | 0.00 | 0.00 | 1938.73 | 6650.91 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.440069E+10 | 0.59 | 6831.66 | 26-JAN-06:01 | 1.56 |
February | 0.417882E+10 | 0.63 | 6370.62 | 06-FEB-07:01 | 1.52 |
March | 0.519878E+10 | 0.67 | 8027.56 | 15-MAR-15:30 | 1.68 |
April | 0.444721E+10 | 0.61 | 6258.73 | 22-APR-05:02 | 1.50 |
May | 0.586527E+10 | 0.67 | 7708.93 | 18-MAY-14:30 | 1.64 |
June | 0.944811E+10 | 0.87 | 12599.86 | 26-JUN-16:00 | 2.01 |
July | 0.916849E+10 | 0.82 | 12742.43 | 18-JUL-14:30 | 2.02 |
August | 0.103528E+11 | 0.89 | 13698.24 | 16-AUG-15:40 | 2.09 |
September | 0.890553E+10 | 0.83 | 13322.44 | 12-SEP-15:50 | 2.06 |
October | 0.614293E+10 | 0.69 | 10996.00 | 11-OCT-16:00 | 1.91 |
November | 0.490182E+10 | 0.63 | 8459.63 | 07-NOV-15:40 | 1.72 |
December | 0.452892E+10 | 0.62 | 6370.62 | 26-DEC-07:03 | 1.52 |
Annual Sum or Average | 0.775394E+11 | 0.71 | |||
Minimum of Months | 0.417882E+10 | 0.59 | 6258.73 | 1.50 | |
Maximum of Months | 0.103528E+11 | 0.89 | 13698.24 | 2.09 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.405615E+10 | 0.59 | 6267.32 | 02-JAN-06:01 | 1.53 |
February | 0.396636E+10 | 0.64 | 6267.32 | 02-FEB-07:01 | 1.54 |
March | 0.476214E+10 | 0.66 | 8099.39 | 15-MAR-15:30 | 1.72 |
April | 0.396151E+10 | 0.59 | 6267.32 | 03-APR-05:01 | 1.53 |
May | 0.511977E+10 | 0.65 | 8403.56 | 18-MAY-14:05 | 1.73 |
June | 0.867880E+10 | 0.86 | 12376.46 | 26-JUN-15:20 | 2.03 |
July | 0.824525E+10 | 0.81 | 12564.47 | 17-JUL-14:05 | 2.05 |
August | 0.878868E+10 | 0.84 | 12399.99 | 16-AUG-15:20 | 2.04 |
September | 0.696404E+10 | 0.76 | 11154.73 | 12-SEP-15:40 | 1.94 |
October | 0.485462E+10 | 0.64 | 9202.84 | 11-OCT-15:30 | 1.80 |
November | 0.415912E+10 | 0.61 | 6523.42 | 07-NOV-15:03 | 1.56 |
December | 0.433628E+10 | 0.64 | 6267.32 | 11-DEC-06:01 | 1.54 |
Annual Sum or Average | 0.678927E+11 | 0.69 | |||
Minimum of Months | 0.396151E+10 | 0.59 | 6267.32 | 1.53 | |
Maximum of Months | 0.878868E+10 | 0.86 | 12564.47 | 2.05 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.487587E+10 | 0.61 | 6644.75 | 02-JAN-05:01 | 1.38 |
February | 0.460200E+10 | 0.63 | 6644.75 | 01-FEB-06:01 | 1.38 |
March | 0.532037E+10 | 0.65 | 7451.08 | 15-MAR-15:20 | 1.45 |
April | 0.459320E+10 | 0.59 | 6644.75 | 03-APR-04:01 | 1.38 |
May | 0.506261E+10 | 0.57 | 8111.79 | 31-MAY-15:20 | 1.49 |
June | 0.830459E+10 | 0.74 | 12720.61 | 26-JUN-15:00 | 1.80 |
July | 0.778145E+10 | 0.70 | 12161.91 | 17-JUL-13:40 | 1.77 |
August | 0.820911E+10 | 0.72 | 12492.15 | 16-AUG-15:20 | 1.79 |
September | 0.627255E+10 | 0.64 | 10163.18 | 12-SEP-15:20 | 1.64 |
October | 0.490620E+10 | 0.58 | 8215.97 | 11-OCT-14:40 | 1.51 |
November | 0.444636E+10 | 0.57 | 6644.75 | 01-NOV-05:01 | 1.38 |
December | 0.526775E+10 | 0.65 | 6644.75 | 01-DEC-06:11 | 1.38 |
Annual Sum or Average | 0.696421E+11 | 0.64 | |||
Minimum of Months | 0.444636E+10 | 0.57 | 6644.75 | 1.38 | |
Maximum of Months | 0.830459E+10 | 0.74 | 12720.61 | 1.80 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.348670E+09 | 0.313803E+09 | 1122.46 | 05-JAN-07:03 | 1010.22 | 1010.22 | 46.61 | 3.60 |
February | 0.369726E+09 | 0.332753E+09 | 1111.35 | 06-FEB-07:01 | 1000.21 | 1000.21 | 47.56 | 3.55 |
March | 0.255769E+09 | 0.230193E+09 | 1046.56 | 20-MAR-06:25 | 941.90 | 941.90 | 48.26 | 3.26 |
April | 0.171444E+09 | 0.154300E+09 | 1068.02 | 17-APR-06:01 | 961.22 | 961.22 | 47.65 | 3.37 |
May | 32151501.54 | 28936351.39 | 1043.70 | 01-MAY-06:03 | 939.33 | 939.33 | 41.91 | 3.26 |
June | 416901.17 | 375211.06 | 137.96 | 09-JUN-06:10 | 124.16 | 124.16 | 35.42 | 0.15 |
July | 223262.80 | 200936.52 | 124.31 | 03-JUL-06:07 | 111.88 | 111.88 | 34.30 | 0.13 |
August | 284707.03 | 256236.32 | 115.64 | 23-AUG-06:03 | 104.07 | 104.07 | 31.10 | 0.12 |
September | 8318679.39 | 7486811.45 | 956.00 | 22-SEP-06:03 | 860.40 | 860.40 | 39.46 | 2.52 |
October | 0.170230E+09 | 0.153207E+09 | 1078.12 | 30-OCT-06:12 | 970.31 | 970.31 | 47.03 | 3.42 |
November | 0.240175E+09 | 0.216158E+09 | 1083.94 | 30-NOV-07:01 | 975.54 | 975.54 | 47.10 | 3.45 |
December | 0.512547E+09 | 0.461292E+09 | 1164.08 | 23-DEC-07:05 | 1047.67 | 1047.67 | 46.21 | 3.73 |
Annual Sum or Average | 0.210996E+10 | 0.189896E+10 | ||||||
Minimum of Months | 223262.80 | 200936.52 | 115.64 | 104.07 | 104.07 | 31.10 | 0.12 | |
Maximum of Months | 0.512547E+09 | 0.461292E+09 | 1164.08 | 1047.67 | 1047.67 | 48.26 | 3.73 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 58.04 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.97 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.97 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 56.82 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.11 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:02 | 2.06 | 2.06 | 57.29 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:02 | 2.06 | 2.06 | 57.43 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:02 | 2.06 | 2.06 | 57.51 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 57.51 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.21 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:01 | 2.06 | 2.06 | 57.45 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 56.96 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.82 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.21 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 42.53 | 42.53 | 16885.43 | 352652.10 | 23-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 32.08 | 32.08 | 19460.84 | 282924.70 | 22-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 28.02 | 28.02 | 12094.91 | 306185.45 | 30-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.81 | 25.81 | 8535.68 | 320433.38 | 26-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.41 | 21.41 | 1339.54 | 379731.22 | 01-MAY-05:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 38.74 | 38.74 | 16.43 | 15216.28 | 09-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 33.58 | 33.58 | 8.89 | 14259.29 | 03-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.87 | 33.87 | 13.45 | 14877.14 | 23-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.86 | 27.86 | 409.06 | 216523.08 | 22-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.33 | 28.33 | 8226.53 | 259258.06 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 38.54 | 38.54 | 12152.51 | 287640.33 | 25-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 32.43 | 32.43 | 25161.28 | 312554.67 | 29-DEC-06:01 |
Annual Sum or Average | 0.00 | 8640.94 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.41 | 21.41 | 8.89 | 14259.29 | ||
Maximum of Months | 0.00 | 0.00 | 42.53 | 42.53 | 25161.28 | 379731.22 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.03 | 58.03 | 1806.24 | 6633.42 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.46 | 57.46 | 1839.63 | 6650.91 | 13-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.46 | 57.46 | 1938.73 | 6625.00 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.54 | 57.54 | 1732.72 | 6419.08 | 03-APR-11:12 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.13 | 58.13 | 1701.34 | 6126.07 | 01-MAY-11:17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.80 | 57.80 | 1644.90 | 5759.55 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.91 | 57.91 | 1432.33 | 5439.71 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.98 | 57.98 | 1559.72 | 5288.02 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.98 | 57.98 | 1478.36 | 5461.95 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.05 | 57.05 | 1548.77 | 5790.88 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.79 | 57.79 | 1670.26 | 6145.66 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.65 | 57.65 | 1689.79 | 6442.60 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1669.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.05 | 57.05 | 1432.33 | 5288.02 | ||
Maximum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 1938.73 | 6650.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.120338E+11 | 0.00 | 0.00 | 0.468752E+10 | 0.00 | 0.00 |
February | 0.128734E+11 | 0.00 | 0.00 | 0.427950E+10 | 0.00 | 0.00 |
March | 0.979654E+10 | 0.00 | 0.00 | 0.614424E+10 | 0.00 | 0.00 |
April | 0.673911E+10 | 0.00 | 0.00 | 0.539682E+10 | 0.00 | 0.00 |
May | 0.147066E+10 | 0.00 | 0.00 | 0.997739E+10 | 0.00 | 0.00 |
June | 37914085.09 | 0.00 | 0.00 | 0.250529E+11 | 0.00 | 0.00 |
July | 21164668.61 | 0.00 | 0.00 | 0.250212E+11 | 0.00 | 0.00 |
August | 24056782.32 | 0.00 | 0.00 | 0.261939E+11 | 0.00 | 0.00 |
September | 0.178650E+09 | 0.00 | 0.00 | 0.196986E+11 | 0.00 | 0.00 |
October | 0.465975E+10 | 0.00 | 0.00 | 0.809242E+10 | 0.00 | 0.00 |
November | 0.668912E+10 | 0.00 | 0.00 | 0.553196E+10 | 0.00 | 0.00 |
December | 0.156907E+11 | 0.00 | 0.00 | 0.487642E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.702149E+11 | 0.00 | 0.00 | 0.144953E+12 | 0.00 | 0.00 |
Minimum of Months | 21164668.61 | 0.00 | 0.00 | 0.427950E+10 | 0.00 | 0.00 |
Maximum of Months | 0.156907E+11 | 0.00 | 0.00 | 0.261939E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.108030E+11 | 0.00 | 0.00 | 0.434495E+10 | 0.00 | 0.00 |
February | 0.115240E+11 | 0.00 | 0.00 | 0.407490E+10 | 0.00 | 0.00 |
March | 0.707422E+10 | 0.00 | 0.00 | 0.568116E+10 | 0.00 | 0.00 |
April | 0.461489E+10 | 0.00 | 0.00 | 0.485071E+10 | 0.00 | 0.00 |
May | 0.432526E+09 | 0.00 | 0.00 | 0.902316E+10 | 0.00 | 0.00 |
June | 257490.07 | 0.00 | 0.00 | 0.234187E+11 | 0.00 | 0.00 |
July | 535902.66 | 0.00 | 0.00 | 0.231029E+11 | 0.00 | 0.00 |
August | 400742.36 | 0.00 | 0.00 | 0.229686E+11 | 0.00 | 0.00 |
September | 0.129535E+09 | 0.00 | 0.00 | 0.161428E+11 | 0.00 | 0.00 |
October | 0.538171E+10 | 0.00 | 0.00 | 0.653203E+10 | 0.00 | 0.00 |
November | 0.785808E+10 | 0.00 | 0.00 | 0.471352E+10 | 0.00 | 0.00 |
December | 0.179007E+11 | 0.00 | 0.00 | 0.466019E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.657198E+11 | 0.00 | 0.00 | 0.129514E+12 | 0.00 | 0.00 |
Minimum of Months | 257490.07 | 0.00 | 0.00 | 0.407490E+10 | 0.00 | 0.00 |
Maximum of Months | 0.179007E+11 | 0.00 | 0.00 | 0.234187E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.227683E+11 | 0.00 | 0.00 | 0.515816E+10 | 0.00 | 0.00 |
February | 0.230759E+11 | 0.00 | 0.00 | 0.471476E+10 | 0.00 | 0.00 |
March | 0.157962E+11 | 0.00 | 0.00 | 0.629008E+10 | 0.00 | 0.00 |
April | 0.109563E+11 | 0.00 | 0.00 | 0.560540E+10 | 0.00 | 0.00 |
May | 0.170071E+10 | 0.00 | 0.00 | 0.973220E+10 | 0.00 | 0.00 |
June | 9982719.98 | 0.00 | 0.00 | 0.260100E+11 | 0.00 | 0.00 |
July | 2063322.92 | 0.00 | 0.00 | 0.253957E+11 | 0.00 | 0.00 |
August | 17854613.61 | 0.00 | 0.00 | 0.249013E+11 | 0.00 | 0.00 |
September | 0.760451E+09 | 0.00 | 0.00 | 0.166129E+11 | 0.00 | 0.00 |
October | 0.121623E+11 | 0.00 | 0.00 | 0.664668E+10 | 0.00 | 0.00 |
November | 0.172129E+11 | 0.00 | 0.00 | 0.497748E+10 | 0.00 | 0.00 |
December | 0.343410E+11 | 0.00 | 0.00 | 0.561429E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.138804E+12 | 0.00 | 0.00 | 0.141659E+12 | 0.00 | 0.00 |
Minimum of Months | 2063322.92 | 0.00 | 0.00 | 0.471476E+10 | 0.00 | 0.00 |
Maximum of Months | 0.343410E+11 | 0.00 | 0.00 | 0.260100E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.440069E+10 | 0.111256E+10 | 0.120338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417882E+10 | 0.377573E+09 | 0.128734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.519878E+10 | 0.382367E+10 | 0.979654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.444721E+10 | 0.368004E+10 | 0.673911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.586527E+10 | 0.168145E+11 | 0.147066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.944811E+10 | 0.609273E+11 | 37914085.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.916849E+10 | 0.628736E+11 | 21164668.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103528E+11 | 0.629287E+11 | 24056782.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.890553E+10 | 0.441745E+11 | 0.178650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614293E+10 | 0.802706E+10 | 0.465975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.490182E+10 | 0.254425E+10 | 0.668912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452892E+10 | 0.134827E+10 | 0.156907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775394E+11 | 0.268632E+12 | 0.702149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.417882E+10 | 0.377573E+09 | 21164668.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103528E+11 | 0.629287E+11 | 0.156907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.405615E+10 | 0.112677E+10 | 0.108030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396636E+10 | 0.408776E+09 | 0.115240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.476214E+10 | 0.370992E+10 | 0.707422E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396151E+10 | 0.343911E+10 | 0.461489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511977E+10 | 0.159029E+11 | 0.432526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.867880E+10 | 0.573313E+11 | 257490.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.824525E+10 | 0.586128E+11 | 535902.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.878868E+10 | 0.560198E+11 | 400742.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.696404E+10 | 0.372350E+11 | 0.129535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485462E+10 | 0.682988E+10 | 0.538171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.415912E+10 | 0.220932E+10 | 0.785808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.433628E+10 | 0.125302E+10 | 0.179007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.678927E+11 | 0.244079E+12 | 0.657198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.396151E+10 | 0.408776E+09 | 257490.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.878868E+10 | 0.586128E+11 | 0.179007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.487587E+10 | 0.106717E+10 | 0.227683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.460200E+10 | 0.419302E+09 | 0.230759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532037E+10 | 0.379475E+10 | 0.157962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459320E+10 | 0.385083E+10 | 0.109563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.506261E+10 | 0.187273E+11 | 0.170071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.830459E+10 | 0.679317E+11 | 9982719.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.778145E+10 | 0.683267E+11 | 2063322.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.820911E+10 | 0.649130E+11 | 17854613.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.627255E+10 | 0.410990E+11 | 0.760451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.490620E+10 | 0.691184E+10 | 0.121623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444636E+10 | 0.203913E+10 | 0.172129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.526775E+10 | 0.131558E+10 | 0.343410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.696421E+11 | 0.280396E+12 | 0.138804E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.444636E+10 | 0.419302E+09 | 2063322.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.830459E+10 | 0.683267E+11 | 0.343410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.440069E+10 | 0.120338E+11 | 0.00 | 0.00 | 0.286833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417882E+10 | 0.128734E+11 | 0.00 | 0.00 | 0.100679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.519878E+10 | 0.979654E+10 | 0.00 | 0.00 | 0.945465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.444721E+10 | 0.673911E+10 | 0.00 | 0.00 | 0.949613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.586527E+10 | 0.147066E+10 | 0.00 | 0.00 | 0.411212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.944811E+10 | 37914085.09 | 0.00 | 0.00 | 0.156048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.916849E+10 | 21164668.61 | 0.00 | 0.00 | 0.158527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103528E+11 | 24056782.32 | 0.00 | 0.00 | 0.158411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.890553E+10 | 0.178650E+09 | 0.00 | 0.00 | 0.107931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.614293E+10 | 0.465975E+10 | 0.00 | 0.00 | 0.194948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.490182E+10 | 0.668912E+10 | 0.00 | 0.00 | 0.630142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452892E+10 | 0.156907E+11 | 0.00 | 0.00 | 0.347493E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.775394E+11 | 0.702149E+11 | 0.00 | 0.00 | 0.674135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.417882E+10 | 21164668.61 | 0.00 | 0.00 | 0.100679E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103528E+11 | 0.156907E+11 | 0.00 | 0.00 | 0.158527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.405615E+10 | 0.108030E+11 | 0.00 | 0.00 | 0.288799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396636E+10 | 0.115240E+11 | 0.00 | 0.00 | 0.108539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.476214E+10 | 0.707422E+10 | 0.00 | 0.00 | 0.919014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396151E+10 | 0.461489E+10 | 0.00 | 0.00 | 0.889202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511977E+10 | 0.432526E+09 | 0.00 | 0.00 | 0.390339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.867880E+10 | 257490.07 | 0.00 | 0.00 | 0.147399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.824525E+10 | 535902.66 | 0.00 | 0.00 | 0.148576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.878868E+10 | 400742.36 | 0.00 | 0.00 | 0.141799E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.696404E+10 | 0.129535E+09 | 0.00 | 0.00 | 0.917874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485462E+10 | 0.538171E+10 | 0.00 | 0.00 | 0.167741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.415912E+10 | 0.785808E+10 | 0.00 | 0.00 | 0.554401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.433628E+10 | 0.179007E+11 | 0.00 | 0.00 | 0.323910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.678927E+11 | 0.657198E+11 | 0.00 | 0.00 | 0.616208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.396151E+10 | 257490.07 | 0.00 | 0.00 | 0.108539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.878868E+10 | 0.179007E+11 | 0.00 | 0.00 | 0.148576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.487587E+10 | 0.227683E+11 | 0.00 | 0.00 | 0.282285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.460200E+10 | 0.230759E+11 | 0.00 | 0.00 | 0.112760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532037E+10 | 0.157962E+11 | 0.00 | 0.00 | 0.969710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459320E+10 | 0.109563E+11 | 0.00 | 0.00 | 0.101220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.506261E+10 | 0.170071E+10 | 0.00 | 0.00 | 0.466959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.830459E+10 | 9982719.98 | 0.00 | 0.00 | 0.177054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.778145E+10 | 2063322.92 | 0.00 | 0.00 | 0.176143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.820911E+10 | 17854613.61 | 0.00 | 0.00 | 0.166922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.627255E+10 | 0.760451E+09 | 0.00 | 0.00 | 0.103403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.490620E+10 | 0.121623E+11 | 0.00 | 0.00 | 0.174047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444636E+10 | 0.172129E+11 | 0.00 | 0.00 | 0.531117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.526775E+10 | 0.343410E+11 | 0.00 | 0.00 | 0.346535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.696421E+11 | 0.138804E+12 | 0.00 | 0.00 | 0.720168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.444636E+10 | 2063322.92 | 0.00 | 0.00 | 0.112760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.830459E+10 | 0.343410E+11 | 0.00 | 0.00 | 0.177054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.534174E+10 | 0.00 | 0.00 | 23501298.93 | 0.00 | 0.00 | 0.117381E+11 | 0.00 | 0.49 |
February | 0.603726E+10 | 0.00 | 0.00 | 18994514.63 | 0.00 | 652845.69 | 0.964295E+10 | 0.00 | 0.44 |
March | 0.413934E+10 | 0.00 | 0.00 | 30635079.52 | 0.00 | 0.00 | 0.151807E+11 | 0.00 | 0.72 |
April | 0.296364E+10 | 0.00 | 0.00 | 26887996.06 | 0.00 | 0.00 | 0.137493E+11 | 0.00 | 0.71 |
May | 0.106287E+10 | 5791477.54 | 0.00 | 43573334.61 | 2153678.51 | 0.00 | 0.169021E+11 | 0.00 | 1.06 |
June | 0.401539E+09 | 0.512437E+09 | 0.00 | 34571204.91 | 60537074.67 | 0.00 | 0.593761E+10 | 0.00 | 0.85 |
July | 0.394016E+09 | 0.726162E+09 | 0.00 | 30079851.67 | 73263267.53 | 0.00 | 0.405455E+10 | 0.00 | 0.78 |
August | 0.539002E+09 | 0.479737E+09 | 0.00 | 45558133.63 | 11120119.47 | 0.00 | 0.799965E+10 | 0.00 | 0.93 |
September | 0.724682E+09 | 69000503.65 | 0.00 | 49798370.83 | 9870898.40 | 0.00 | 0.120608E+11 | 0.00 | 1.06 |
October | 0.242053E+10 | 0.00 | 0.00 | 43181665.53 | 0.00 | 0.00 | 0.196603E+11 | 0.00 | 0.89 |
November | 0.302547E+10 | 0.00 | 0.00 | 34835358.68 | 0.00 | 0.00 | 0.158446E+11 | 0.00 | 0.63 |
December | 0.632771E+10 | 0.00 | 0.00 | 20965838.48 | 0.00 | 2080419.83 | 0.108527E+11 | 0.00 | 0.46 |
Annual Sum or Average | 0.333778E+11 | 0.179313E+10 | 0.00 | 0.402583E+09 | 0.156945E+09 | 2733265.53 | 0.143623E+12 | 0.00 | 0.75 |
Minimum of Months | 0.394016E+09 | 0.00 | 0.00 | 18994514.63 | 0.00 | 0.00 | 0.405455E+10 | 0.00 | 0.44 |
Maximum of Months | 0.632771E+10 | 0.726162E+09 | 0.00 | 49798370.83 | 73263267.53 | 2080419.83 | 0.196603E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101013E+11 | 0.00 | 0.00 | 3002949.85 | 0.00 | 0.114450E+09 | 0.201171E+10 | 0.00 | 0.34 |
February | 0.910296E+10 | 0.00 | 0.00 | 2143391.25 | 0.00 | 0.322033E+09 | 0.193415E+10 | 0.00 | 0.32 |
March | 0.846633E+10 | 0.00 | 0.00 | 8564356.32 | 0.00 | 66872161.56 | 0.485744E+10 | 0.00 | 0.50 |
April | 0.721192E+10 | 0.00 | 0.00 | 7302556.51 | 0.00 | 95538069.70 | 0.420727E+10 | 0.00 | 0.49 |
May | 0.339088E+10 | 191902.80 | 0.00 | 20553566.80 | 9710930.02 | 1355842.75 | 0.875057E+10 | 0.00 | 0.72 |
June | 0.743748E+09 | 0.367914E+09 | 0.00 | 22795977.97 | 61795958.19 | 0.00 | 0.358714E+10 | 0.00 | 0.61 |
July | 0.600046E+09 | 0.510044E+09 | 0.00 | 20076808.64 | 0.113013E+09 | 0.00 | 0.239918E+10 | 0.00 | 0.55 |
August | 0.838350E+09 | 0.347063E+09 | 0.00 | 30346252.37 | 12795286.87 | 0.00 | 0.481640E+10 | 0.00 | 0.65 |
September | 0.147701E+10 | 53829768.52 | 0.00 | 27467882.07 | 7836117.96 | 0.00 | 0.633074E+10 | 0.00 | 0.70 |
October | 0.672139E+10 | 0.00 | 0.00 | 13512967.14 | 0.00 | 42478168.32 | 0.651163E+10 | 0.00 | 0.55 |
November | 0.889840E+10 | 0.00 | 0.00 | 6233570.43 | 0.00 | 16251866.68 | 0.333639E+10 | 0.00 | 0.41 |
December | 0.112036E+11 | 0.00 | 0.00 | 1351725.20 | 0.00 | 0.255575E+09 | 0.121799E+10 | 0.00 | 0.33 |
Annual Sum or Average | 0.687559E+11 | 0.127904E+10 | 0.00 | 0.163352E+09 | 0.205151E+09 | 0.914554E+09 | 0.499606E+11 | 0.00 | 0.52 |
Minimum of Months | 0.600046E+09 | 0.00 | 0.00 | 1351725.20 | 0.00 | 0.00 | 0.121799E+10 | 0.00 | 0.32 |
Maximum of Months | 0.112036E+11 | 0.510044E+09 | 0.00 | 30346252.37 | 0.113013E+09 | 0.322033E+09 | 0.875057E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.967500E+10 | 0.00 | 0.00 | 495635.15 | 0.00 | 0.134796E+10 | 0.607233E+09 | 0.00 | 0.35 |
February | 0.895999E+10 | 0.00 | 0.00 | 283733.94 | 0.00 | 0.145274E+10 | 0.556640E+09 | 0.00 | 0.33 |
March | 0.970961E+10 | 0.00 | 0.00 | 4653289.63 | 0.00 | 0.669645E+09 | 0.318229E+10 | 0.00 | 0.52 |
April | 0.849111E+10 | 0.00 | 0.00 | 4994281.89 | 0.00 | 0.480299E+09 | 0.338559E+10 | 0.00 | 0.53 |
May | 0.497466E+10 | 0.00 | 0.00 | 17215990.93 | 4538256.09 | 58093189.68 | 0.757812E+10 | 0.00 | 0.75 |
June | 0.136602E+10 | 0.228325E+09 | 0.00 | 24667892.53 | 78815787.02 | 0.00 | 0.287831E+10 | 0.00 | 0.62 |
July | 0.907396E+09 | 0.380902E+09 | 0.00 | 21068639.50 | 0.106919E+09 | 0.00 | 0.178714E+10 | 0.00 | 0.55 |
August | 0.158491E+10 | 0.293800E+09 | 0.00 | 27773670.13 | 9810502.91 | 0.00 | 0.358183E+10 | 0.00 | 0.64 |
September | 0.293594E+10 | 21489845.10 | 0.00 | 20974771.30 | 19182820.26 | 1814449.92 | 0.419108E+10 | 0.00 | 0.68 |
October | 0.862594E+10 | 0.00 | 0.00 | 5556978.49 | 0.00 | 0.681870E+09 | 0.319969E+10 | 0.00 | 0.54 |
November | 0.950758E+10 | 0.00 | 0.00 | 1817368.48 | 0.00 | 0.764233E+09 | 0.124999E+10 | 0.00 | 0.40 |
December | 0.910010E+10 | 0.00 | 0.00 | 35116.70 | 0.00 | 0.241264E+10 | 0.139342E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.758382E+11 | 0.924517E+09 | 0.00 | 0.129537E+09 | 0.219267E+09 | 0.786929E+10 | 0.323373E+11 | 0.00 | 0.52 |
Minimum of Months | 0.907396E+09 | 0.00 | 0.00 | 35116.70 | 0.00 | 0.00 | 0.139342E+09 | 0.00 | 0.33 |
Maximum of Months | 0.970961E+10 | 0.380902E+09 | 0.00 | 27773670.13 | 0.106919E+09 | 0.241264E+10 | 0.757812E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.233278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257147E+10 | 0.00 | 0.00 | 0.70 |
February | 0.233282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228633E+10 | 0.00 | 0.00 | 0.65 |
March | 0.363222E+10 | 0.00 | 0.00 | 225213.65 | 0.00 | 0.165967E+10 | 0.248849E+09 | 0.00 | 0.98 |
April | 0.349932E+10 | 0.00 | 0.00 | 338767.08 | 0.00 | 0.109734E+10 | 0.422364E+09 | 0.00 | 1.01 |
May | 0.331823E+10 | 0.00 | 0.00 | 2607304.90 | 1905979.36 | 0.122993E+09 | 0.130004E+10 | 0.00 | 1.33 |
June | 0.794507E+09 | 78962463.39 | 0.00 | 6615355.97 | 40307270.95 | 0.00 | 0.688037E+09 | 0.00 | 1.04 |
July | 0.555773E+09 | 0.119180E+09 | 0.00 | 5617659.23 | 64245995.35 | 0.00 | 0.413586E+09 | 0.00 | 0.94 |
August | 0.103818E+10 | 86711468.16 | 0.00 | 6468325.34 | 30425104.46 | 673005.61 | 0.759520E+09 | 0.00 | 1.07 |
September | 0.189473E+10 | 7720210.07 | 0.00 | 3995595.92 | 9340609.37 | 70836799.04 | 0.660014E+09 | 0.00 | 1.18 |
October | 0.376144E+10 | 0.00 | 0.00 | 249693.34 | 0.00 | 0.120256E+10 | 0.167294E+09 | 0.00 | 1.04 |
November | 0.279235E+10 | 0.00 | 0.00 | 2830.71 | 0.00 | 0.201764E+10 | 17425061.36 | 0.00 | 0.79 |
December | 0.171228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331494E+10 | 0.00 | 0.00 | 0.68 |
Annual Sum or Average | 0.276646E+11 | 0.292574E+09 | 0.00 | 26120746.14 | 0.146225E+09 | 0.143445E+11 | 0.467713E+10 | 0.00 | 0.95 |
Minimum of Months | 0.555773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.376144E+10 | 0.119180E+09 | 0.00 | 6615355.97 | 64245995.35 | 0.331494E+10 | 0.130004E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203007E+10 | 0.00 | 0.00 | 24833.54 | 0.00 | 0.133274E+10 | 50589361.56 | 0.00 | 0.77 |
February | 0.191927E+10 | 0.00 | 0.00 | 111013.91 | 0.00 | 0.112863E+10 | 0.166259E+09 | 0.00 | 0.72 |
March | 0.199619E+10 | 0.00 | 0.00 | 1651411.47 | 0.00 | 0.872795E+09 | 0.113118E+10 | 0.00 | 1.14 |
April | 0.184911E+10 | 0.00 | 0.00 | 1992692.99 | 0.00 | 0.602470E+09 | 0.126866E+10 | 0.00 | 1.20 |
May | 0.157712E+10 | 0.00 | 0.00 | 4547307.24 | 1328931.70 | 48264313.49 | 0.197493E+10 | 0.00 | 1.63 |
June | 0.346253E+09 | 67587540.06 | 0.00 | 8348579.33 | 19154687.19 | 0.00 | 0.108410E+10 | 0.00 | 1.56 |
July | 0.302529E+09 | 0.111042E+09 | 0.00 | 6531054.87 | 28739686.49 | 0.00 | 0.507917E+09 | 0.00 | 1.27 |
August | 0.453504E+09 | 73513006.39 | 0.00 | 9098835.32 | 19257793.50 | 0.00 | 0.131508E+10 | 0.00 | 1.60 |
September | 0.959405E+09 | 7709566.07 | 0.00 | 6104020.50 | 5876063.71 | 25520173.42 | 0.113425E+10 | 0.00 | 1.55 |
October | 0.195812E+10 | 0.00 | 0.00 | 1335822.40 | 0.00 | 0.752853E+09 | 0.907616E+09 | 0.00 | 1.17 |
November | 0.207167E+10 | 0.00 | 0.00 | 165572.54 | 0.00 | 0.105837E+10 | 0.232928E+09 | 0.00 | 0.87 |
December | 0.156815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191088E+10 | 0.00 | 0.00 | 0.74 |
Annual Sum or Average | 0.170314E+11 | 0.259852E+09 | 0.00 | 39911144.09 | 74357162.58 | 0.773253E+10 | 0.977350E+10 | 0.00 | 1.19 |
Minimum of Months | 0.302529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
Maximum of Months | 0.207167E+10 | 0.111042E+09 | 0.00 | 9098835.32 | 28739686.49 | 0.191088E+10 | 0.197493E+10 | 0.00 | 1.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176322E+10 | 0.00 | 0.00 | 7857562.23 | 0.00 | 0.135180E+10 | 0.293990E+10 | 0.00 | 0.96 |
February | 0.149060E+10 | 0.00 | 0.00 | 7266172.39 | 0.00 | 0.125619E+10 | 0.308338E+10 | 0.00 | 0.87 |
March | 0.228298E+10 | 0.00 | 0.00 | 7080357.88 | 0.00 | 0.119071E+10 | 0.345312E+10 | 0.00 | 1.34 |
April | 0.245502E+10 | 0.00 | 0.00 | 4047813.94 | 0.00 | 0.930185E+09 | 0.219444E+10 | 0.00 | 1.16 |
May | 0.267627E+10 | 0.00 | 0.00 | 5407364.10 | 1925846.79 | 0.130919E+09 | 0.225721E+10 | 0.00 | 1.44 |
June | 0.819486E+09 | 86461029.38 | 0.00 | 7825634.66 | 36366103.83 | 0.00 | 0.766450E+09 | 0.00 | 1.12 |
July | 0.567940E+09 | 0.140787E+09 | 0.00 | 6705839.45 | 55648196.20 | 0.00 | 0.472130E+09 | 0.00 | 1.01 |
August | 0.957936E+09 | 0.117672E+09 | 0.00 | 10771674.85 | 22696249.56 | 680020.85 | 0.116759E+10 | 0.00 | 1.26 |
September | 0.138042E+10 | 20355658.97 | 0.00 | 10875617.79 | 2323527.90 | 44598014.53 | 0.181704E+10 | 0.00 | 1.51 |
October | 0.190248E+10 | 0.00 | 0.00 | 9696855.58 | 0.00 | 0.103085E+10 | 0.395093E+10 | 0.00 | 1.51 |
November | 0.167531E+10 | 0.00 | 0.00 | 8540745.79 | 0.00 | 0.119660E+10 | 0.331874E+10 | 0.00 | 1.13 |
December | 0.179933E+10 | 0.00 | 0.00 | 5932124.43 | 0.00 | 0.196819E+10 | 0.193971E+10 | 0.00 | 0.85 |
Annual Sum or Average | 0.197710E+11 | 0.365276E+09 | 0.00 | 92007763.09 | 0.118960E+09 | 0.910072E+10 | 0.273606E+11 | 0.00 | 1.18 |
Minimum of Months | 0.567940E+09 | 0.00 | 0.00 | 4047813.94 | 0.00 | 0.00 | 0.472130E+09 | 0.00 | 0.85 |
Maximum of Months | 0.267627E+10 | 0.140787E+09 | 0.00 | 10875617.79 | 55648196.20 | 0.196819E+10 | 0.395093E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199189E+10 | 0.00 | 0.00 | 406571.45 | 0.00 | 0.177646E+10 | 0.325312E+09 | 0.00 | 0.93 |
February | 0.179762E+10 | 0.00 | 0.00 | 587523.17 | 0.00 | 0.159107E+10 | 0.484293E+09 | 0.00 | 0.87 |
March | 0.257614E+10 | 0.00 | 0.00 | 2048923.27 | 0.00 | 0.119284E+10 | 0.111620E+10 | 0.00 | 1.42 |
April | 0.246170E+10 | 0.00 | 0.00 | 1705395.39 | 0.00 | 0.820217E+09 | 0.109518E+10 | 0.00 | 1.41 |
May | 0.253628E+10 | 0.00 | 0.00 | 3550300.22 | 1590115.90 | 0.103344E+09 | 0.149887E+10 | 0.00 | 1.86 |
June | 0.702043E+09 | 82970451.09 | 0.00 | 5529035.64 | 30612547.65 | 1133753.53 | 0.541861E+09 | 0.00 | 1.42 |
July | 0.482362E+09 | 0.104194E+09 | 0.00 | 4218974.03 | 54427654.73 | 0.00 | 0.351561E+09 | 0.00 | 1.27 |
August | 0.933647E+09 | 90343339.93 | 0.00 | 5960778.63 | 20874012.18 | 1325811.62 | 0.589864E+09 | 0.00 | 1.46 |
September | 0.150682E+10 | 7917061.18 | 0.00 | 4217565.36 | 7604511.17 | 63607092.73 | 0.741545E+09 | 0.00 | 1.66 |
October | 0.254859E+10 | 0.00 | 0.00 | 1984041.22 | 0.00 | 0.943492E+09 | 0.101249E+10 | 0.00 | 1.47 |
November | 0.215579E+10 | 0.00 | 0.00 | 728788.32 | 0.00 | 0.144165E+10 | 0.455058E+09 | 0.00 | 1.06 |
December | 0.160072E+10 | 0.00 | 0.00 | 161776.75 | 0.00 | 0.239132E+10 | 0.133235E+09 | 0.00 | 0.89 |
Annual Sum or Average | 0.212936E+11 | 0.285425E+09 | 0.00 | 31099673.45 | 0.115109E+09 | 0.103265E+11 | 0.834547E+10 | 0.00 | 1.31 |
Minimum of Months | 0.482362E+09 | 0.00 | 0.00 | 161776.75 | 0.00 | 0.00 | 0.133235E+09 | 0.00 | 0.87 |
Maximum of Months | 0.257614E+10 | 0.104194E+09 | 0.00 | 5960778.63 | 54427654.73 | 0.239132E+10 | 0.149887E+10 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261500E+10 | 0.00 | 0.00 | 0.58 |
February | 0.158234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263804E+10 | 0.00 | 0.00 | 0.55 |
March | 0.280567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191742E+10 | 0.00 | 0.00 | 0.78 |
April | 0.292126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124382E+10 | 0.00 | 0.00 | 0.80 |
May | 0.324678E+10 | 50124.19 | 0.00 | 600343.72 | 2134140.09 | 0.124340E+09 | 0.235615E+09 | 0.00 | 0.98 |
June | 0.734195E+09 | 98371008.46 | 0.00 | 3224515.91 | 30216842.36 | 0.00 | 0.443726E+09 | 0.00 | 0.75 |
July | 0.556286E+09 | 0.121665E+09 | 0.00 | 2857815.70 | 46482869.29 | 0.00 | 0.293625E+09 | 0.00 | 0.69 |
August | 0.845100E+09 | 94092089.01 | 0.00 | 4423050.04 | 8650431.88 | 0.00 | 0.652552E+09 | 0.00 | 0.79 |
September | 0.156800E+10 | 14695432.27 | 0.00 | 4016672.56 | 2919999.97 | 1645057.77 | 0.813863E+09 | 0.00 | 0.93 |
October | 0.390718E+10 | 0.00 | 0.00 | 205432.26 | 0.00 | 0.621381E+09 | 0.148685E+09 | 0.00 | 0.86 |
November | 0.317964E+10 | 0.00 | 0.00 | 6962.98 | 0.00 | 0.129269E+10 | 18874030.09 | 0.00 | 0.66 |
December | 0.192523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277363E+10 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.251875E+11 | 0.328874E+09 | 0.00 | 15334793.17 | 90404283.60 | 0.132280E+11 | 0.260694E+10 | 0.00 | 0.75 |
Minimum of Months | 0.556286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.390718E+10 | 0.121665E+09 | 0.00 | 4423050.04 | 46482869.29 | 0.277363E+10 | 0.813863E+09 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208761E+10 | 0.00 | 0.00 | 7709.03 | 0.00 | 0.131654E+10 | 32119698.78 | 0.00 | 0.70 |
February | 0.179353E+10 | 0.00 | 0.00 | 48239.22 | 0.00 | 0.130260E+10 | 0.102292E+09 | 0.00 | 0.66 |
March | 0.204005E+10 | 0.00 | 0.00 | 885534.74 | 0.00 | 0.991317E+09 | 0.618410E+09 | 0.00 | 0.96 |
April | 0.199410E+10 | 0.00 | 0.00 | 1006346.99 | 0.00 | 0.619911E+09 | 0.640377E+09 | 0.00 | 0.99 |
May | 0.164656E+10 | 174178.59 | 0.00 | 2630501.49 | 1496719.31 | 54927387.16 | 0.117204E+10 | 0.00 | 1.26 |
June | 0.308511E+09 | 93283848.42 | 0.00 | 5755943.44 | 14110921.15 | 0.00 | 0.931727E+09 | 0.00 | 1.25 |
July | 0.280724E+09 | 0.122217E+09 | 0.00 | 4465056.33 | 22775945.68 | 0.00 | 0.507537E+09 | 0.00 | 1.03 |
August | 0.345263E+09 | 93629413.01 | 0.00 | 7819729.27 | 2505086.25 | 0.00 | 0.133072E+10 | 0.00 | 1.38 |
September | 0.697320E+09 | 14003109.45 | 0.00 | 6883243.59 | 2223667.82 | 385961.37 | 0.155141E+10 | 0.00 | 1.44 |
October | 0.214461E+10 | 0.00 | 0.00 | 2070792.06 | 0.00 | 0.425183E+09 | 0.111402E+10 | 0.00 | 1.09 |
November | 0.239195E+10 | 0.00 | 0.00 | 484337.81 | 0.00 | 0.668039E+09 | 0.367130E+09 | 0.00 | 0.80 |
December | 0.184001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171158E+10 | 0.00 | 0.00 | 0.69 |
Annual Sum or Average | 0.175702E+11 | 0.323307E+09 | 0.00 | 32057433.97 | 43112340.22 | 0.709048E+10 | 0.836778E+10 | 0.00 | 1.02 |
Minimum of Months | 0.280724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.239195E+10 | 0.122217E+09 | 0.00 | 7819729.27 | 22775945.68 | 0.171158E+10 | 0.155141E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206997E+10 | 0.00 | 0.00 | 3508509.98 | 0.00 | 0.187519E+10 | 0.144881E+10 | 0.00 | 0.76 |
February | 0.185431E+10 | 0.00 | 0.00 | 2351798.08 | 0.00 | 0.196937E+10 | 0.111250E+10 | 0.00 | 0.67 |
March | 0.210171E+10 | 0.00 | 0.00 | 2784635.66 | 0.00 | 0.211712E+10 | 0.124027E+10 | 0.00 | 0.97 |
April | 0.244822E+10 | 0.00 | 0.00 | 864045.91 | 0.00 | 0.158778E+10 | 0.478501E+09 | 0.00 | 0.86 |
May | 0.274751E+10 | 725985.63 | 0.00 | 1789937.53 | 1522609.51 | 0.579962E+09 | 0.437481E+09 | 0.00 | 1.03 |
June | 0.821026E+09 | 0.140641E+09 | 0.00 | 3971715.38 | 21172226.87 | 26966333.23 | 0.374572E+09 | 0.00 | 0.83 |
July | 0.609956E+09 | 0.182886E+09 | 0.00 | 3494586.52 | 27017608.01 | 11759332.19 | 0.262460E+09 | 0.00 | 0.76 |
August | 0.798527E+09 | 0.158524E+09 | 0.00 | 8425555.65 | 3261698.66 | 13140398.45 | 0.909903E+09 | 0.00 | 0.99 |
September | 0.101697E+10 | 28188268.27 | 0.00 | 10953205.14 | 2962036.22 | 0.107325E+09 | 0.183950E+10 | 0.00 | 1.32 |
October | 0.175811E+10 | 0.00 | 0.00 | 9051859.57 | 0.00 | 0.127515E+10 | 0.335655E+10 | 0.00 | 1.34 |
November | 0.204630E+10 | 0.00 | 0.00 | 6344840.93 | 0.00 | 0.136802E+10 | 0.248141E+10 | 0.00 | 1.00 |
December | 0.195431E+10 | 0.00 | 0.00 | 3748919.82 | 0.00 | 0.243368E+10 | 0.129090E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.202269E+11 | 0.510966E+09 | 0.00 | 57289610.16 | 55936179.27 | 0.133655E+11 | 0.152328E+11 | 0.00 | 0.94 |
Minimum of Months | 0.609956E+09 | 0.00 | 0.00 | 864045.91 | 0.00 | 11759332.19 | 0.262460E+09 | 0.00 | 0.67 |
Maximum of Months | 0.274751E+10 | 0.182886E+09 | 0.00 | 10953205.14 | 27017608.01 | 0.243368E+10 | 0.335655E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206913E+10 | 0.00 | 0.00 | 173780.43 | 0.00 | 0.160682E+10 | 0.155364E+09 | 0.00 | 0.79 |
February | 0.179740E+10 | 0.00 | 0.00 | 170600.21 | 0.00 | 0.157988E+10 | 0.193363E+09 | 0.00 | 0.73 |
March | 0.239797E+10 | 0.00 | 0.00 | 861226.55 | 0.00 | 0.121310E+10 | 0.458241E+09 | 0.00 | 1.08 |
April | 0.246014E+10 | 0.00 | 0.00 | 574588.33 | 0.00 | 0.724523E+09 | 0.377966E+09 | 0.00 | 1.09 |
May | 0.243245E+10 | 677159.12 | 0.00 | 1584041.93 | 1197616.91 | 71476679.39 | 0.595311E+09 | 0.00 | 1.35 |
June | 0.587819E+09 | 0.113594E+09 | 0.00 | 3177683.84 | 20884487.20 | 0.00 | 0.421115E+09 | 0.00 | 1.06 |
July | 0.452410E+09 | 0.127226E+09 | 0.00 | 2309148.52 | 27722031.31 | 0.00 | 0.291816E+09 | 0.00 | 0.96 |
August | 0.656326E+09 | 0.104821E+09 | 0.00 | 4390980.28 | 6123791.69 | 0.00 | 0.630072E+09 | 0.00 | 1.12 |
September | 0.107421E+10 | 14422102.47 | 0.00 | 4615682.87 | 2324805.60 | 2244731.51 | 0.104016E+10 | 0.00 | 1.34 |
October | 0.276475E+10 | 0.00 | 0.00 | 1993914.46 | 0.00 | 0.496419E+09 | 0.919863E+09 | 0.00 | 1.25 |
November | 0.267633E+10 | 0.00 | 0.00 | 640301.05 | 0.00 | 0.773518E+09 | 0.393129E+09 | 0.00 | 0.91 |
December | 0.195212E+10 | 0.00 | 0.00 | 136938.50 | 0.00 | 0.191171E+10 | 99467400.15 | 0.00 | 0.77 |
Annual Sum or Average | 0.213210E+11 | 0.360740E+09 | 0.00 | 20628886.95 | 58252732.70 | 0.837969E+10 | 0.557587E+10 | 0.00 | 1.04 |
Minimum of Months | 0.452410E+09 | 0.00 | 0.00 | 136938.50 | 0.00 | 0.00 | 99467400.15 | 0.00 | 0.73 |
Maximum of Months | 0.276475E+10 | 0.127226E+09 | 0.00 | 4615682.87 | 27722031.31 | 0.191171E+10 | 0.104016E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199228E+10 | 0.00 | 0.00 | 0.60 |
February | 0.236596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185486E+10 | 0.00 | 0.00 | 0.56 |
March | 0.325705E+10 | 0.00 | 0.00 | 359717.20 | 0.00 | 0.116952E+10 | 0.290844E+09 | 0.00 | 0.80 |
April | 0.307982E+10 | 0.00 | 0.00 | 449830.30 | 0.00 | 0.648492E+09 | 0.354748E+09 | 0.00 | 0.81 |
May | 0.231033E+10 | 1078195.24 | 0.00 | 3431392.76 | 2597019.68 | 44611638.56 | 0.143528E+10 | 0.00 | 1.07 |
June | 0.557651E+09 | 0.137252E+09 | 0.00 | 5694020.48 | 22437539.35 | 0.00 | 0.759652E+09 | 0.00 | 0.91 |
July | 0.415204E+09 | 0.192873E+09 | 0.00 | 4819907.28 | 32855197.38 | 0.00 | 0.505752E+09 | 0.00 | 0.82 |
August | 0.757624E+09 | 0.122133E+09 | 0.00 | 6408482.25 | 7013513.55 | 0.00 | 0.850090E+09 | 0.00 | 0.90 |
September | 0.146950E+10 | 16323065.02 | 0.00 | 4560852.76 | 7219772.83 | 11034059.89 | 0.849497E+09 | 0.00 | 0.97 |
October | 0.349586E+10 | 0.00 | 0.00 | 467867.24 | 0.00 | 0.739129E+09 | 0.286281E+09 | 0.00 | 0.86 |
November | 0.293377E+10 | 0.00 | 0.00 | 55184.67 | 0.00 | 0.140707E+10 | 80516577.83 | 0.00 | 0.67 |
December | 0.194802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282920E+10 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.251093E+11 | 0.469659E+09 | 0.00 | 26247254.94 | 72123042.79 | 0.106962E+11 | 0.541266E+10 | 0.00 | 0.80 |
Minimum of Months | 0.415204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.349586E+10 | 0.192873E+09 | 0.00 | 6408482.25 | 32855197.38 | 0.282920E+10 | 0.143528E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192014E+10 | 0.00 | 0.00 | 294716.80 | 0.00 | 0.130229E+10 | 0.166057E+09 | 0.00 | 0.68 |
February | 0.166340E+10 | 0.00 | 0.00 | 534927.71 | 0.00 | 0.121321E+10 | 0.324960E+09 | 0.00 | 0.66 |
March | 0.196364E+10 | 0.00 | 0.00 | 2247170.12 | 0.00 | 0.769926E+09 | 0.118268E+10 | 0.00 | 1.08 |
April | 0.181654E+10 | 0.00 | 0.00 | 2311347.44 | 0.00 | 0.421202E+09 | 0.122514E+10 | 0.00 | 1.11 |
May | 0.153361E+10 | 1108362.60 | 0.00 | 4910952.07 | 2087171.48 | 20392648.02 | 0.190697E+10 | 0.00 | 1.56 |
June | 0.389802E+09 | 0.104655E+09 | 0.00 | 7037769.39 | 19235203.96 | 0.00 | 0.116343E+10 | 0.00 | 1.56 |
July | 0.363058E+09 | 0.151526E+09 | 0.00 | 5497790.38 | 27697982.47 | 0.00 | 0.589735E+09 | 0.00 | 1.27 |
August | 0.503455E+09 | 0.100999E+09 | 0.00 | 8503723.99 | 10459133.31 | 0.00 | 0.143397E+10 | 0.00 | 1.62 |
September | 0.104998E+10 | 15893108.64 | 0.00 | 6206238.90 | 5579897.90 | 5105721.09 | 0.128817E+10 | 0.00 | 1.56 |
October | 0.206475E+10 | 0.00 | 0.00 | 2154785.08 | 0.00 | 0.576807E+09 | 0.106788E+10 | 0.00 | 1.14 |
November | 0.200102E+10 | 0.00 | 0.00 | 687087.19 | 0.00 | 0.981083E+09 | 0.392711E+09 | 0.00 | 0.80 |
December | 0.155535E+10 | 0.00 | 0.00 | 49381.69 | 0.00 | 0.200100E+10 | 22485112.96 | 0.00 | 0.67 |
Annual Sum or Average | 0.168247E+11 | 0.374182E+09 | 0.00 | 40435890.75 | 65059389.13 | 0.729102E+10 | 0.107642E+11 | 0.00 | 1.14 |
Minimum of Months | 0.363058E+09 | 0.00 | 0.00 | 49381.69 | 0.00 | 0.00 | 22485112.96 | 0.00 | 0.66 |
Maximum of Months | 0.206475E+10 | 0.151526E+09 | 0.00 | 8503723.99 | 27697982.47 | 0.200100E+10 | 0.190697E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.190753E+10 | 0.00 | 0.00 | 10209191.25 | 0.00 | 0.993017E+09 | 0.352418E+10 | 0.00 | 0.99 |
February | 0.160652E+10 | 0.00 | 0.00 | 9035388.32 | 0.00 | 0.106791E+10 | 0.342618E+10 | 0.00 | 0.90 |
March | 0.217759E+10 | 0.00 | 0.00 | 8248422.35 | 0.00 | 0.898226E+09 | 0.340579E+10 | 0.00 | 1.27 |
April | 0.242535E+10 | 0.00 | 0.00 | 4448937.32 | 0.00 | 0.513811E+09 | 0.190477E+10 | 0.00 | 1.04 |
May | 0.208351E+10 | 1689035.96 | 0.00 | 6118569.22 | 2293570.53 | 46398254.45 | 0.217291E+10 | 0.00 | 1.25 |
June | 0.677249E+09 | 0.151682E+09 | 0.00 | 6196284.06 | 22947703.88 | 0.00 | 0.731020E+09 | 0.00 | 0.99 |
July | 0.502575E+09 | 0.232739E+09 | 0.00 | 5293316.39 | 32041234.44 | 0.00 | 0.488510E+09 | 0.00 | 0.90 |
August | 0.751707E+09 | 0.177827E+09 | 0.00 | 10054680.63 | 4886602.89 | 0.00 | 0.120030E+10 | 0.00 | 1.14 |
September | 0.109336E+10 | 37694907.49 | 0.00 | 11079917.64 | 3007967.79 | 10830254.76 | 0.194036E+10 | 0.00 | 1.42 |
October | 0.199119E+10 | 0.00 | 0.00 | 11920416.46 | 0.00 | 0.703141E+09 | 0.419687E+10 | 0.00 | 1.52 |
November | 0.192207E+10 | 0.00 | 0.00 | 11172018.45 | 0.00 | 0.804758E+09 | 0.383289E+10 | 0.00 | 1.17 |
December | 0.194558E+10 | 0.00 | 0.00 | 7981605.61 | 0.00 | 0.168355E+10 | 0.250410E+10 | 0.00 | 0.89 |
Annual Sum or Average | 0.190842E+11 | 0.601633E+09 | 0.00 | 0.101759E+09 | 65177079.54 | 0.672164E+10 | 0.293279E+11 | 0.00 | 1.12 |
Minimum of Months | 0.502575E+09 | 0.00 | 0.00 | 4448937.32 | 0.00 | 0.00 | 0.488510E+09 | 0.00 | 0.89 |
Maximum of Months | 0.242535E+10 | 0.232739E+09 | 0.00 | 11920416.46 | 32041234.44 | 0.168355E+10 | 0.419687E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.250444E+10 | 0.00 | 0.00 | 552618.49 | 0.00 | 0.159099E+10 | 0.402909E+09 | 0.00 | 0.95 |
February | 0.220041E+10 | 0.00 | 0.00 | 784677.24 | 0.00 | 0.153318E+10 | 0.508569E+09 | 0.00 | 0.90 |
March | 0.294395E+10 | 0.00 | 0.00 | 2104019.32 | 0.00 | 0.102229E+10 | 0.971908E+09 | 0.00 | 1.39 |
April | 0.278954E+10 | 0.00 | 0.00 | 1638313.62 | 0.00 | 0.563795E+09 | 0.870543E+09 | 0.00 | 1.35 |
May | 0.244310E+10 | 1304362.38 | 0.00 | 3483681.00 | 2440672.86 | 50235595.36 | 0.137957E+10 | 0.00 | 1.75 |
June | 0.720688E+09 | 0.143982E+09 | 0.00 | 4207800.90 | 27057223.56 | 0.00 | 0.509890E+09 | 0.00 | 1.34 |
July | 0.550461E+09 | 0.174912E+09 | 0.00 | 3098584.29 | 39479639.21 | 0.00 | 0.342459E+09 | 0.00 | 1.21 |
August | 0.891665E+09 | 0.131937E+09 | 0.00 | 5213077.17 | 9743896.82 | 0.00 | 0.642081E+09 | 0.00 | 1.38 |
September | 0.155561E+10 | 21832219.07 | 0.00 | 4166173.61 | 3208627.87 | 13308542.74 | 0.794065E+09 | 0.00 | 1.57 |
October | 0.304529E+10 | 0.00 | 0.00 | 2189814.11 | 0.00 | 0.725599E+09 | 0.973379E+09 | 0.00 | 1.48 |
November | 0.273885E+10 | 0.00 | 0.00 | 949924.93 | 0.00 | 0.118624E+10 | 0.516751E+09 | 0.00 | 1.09 |
December | 0.207533E+10 | 0.00 | 0.00 | 297760.76 | 0.00 | 0.246496E+10 | 0.176443E+09 | 0.00 | 0.92 |
Annual Sum or Average | 0.244593E+11 | 0.473969E+09 | 0.00 | 28686445.44 | 81930060.31 | 0.915060E+10 | 0.808857E+10 | 0.00 | 1.28 |
Minimum of Months | 0.550461E+09 | 0.00 | 0.00 | 297760.76 | 0.00 | 0.00 | 0.176443E+09 | 0.00 | 0.90 |
Maximum of Months | 0.304529E+10 | 0.174912E+09 | 0.00 | 5213077.17 | 39479639.21 | 0.246496E+10 | 0.137957E+10 | 0.00 | 1.75 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.258233E+12 | 0.113929E+11 | 0.00 | 0.203169E+12 | 0.297479E+11 |
February | 0.315586E+12 | 0.153327E+11 | 0.00 | 0.183923E+12 | 0.275383E+11 |
March | 0.378172E+12 | 0.155222E+11 | 0.00 | 0.222127E+12 | 0.334530E+11 |
April | 0.388683E+12 | 0.150768E+11 | 0.00 | 0.220641E+12 | 0.271940E+11 |
May | 0.449278E+12 | 0.790737E+10 | 0.00 | 0.261501E+12 | 0.665435E+11 |
June | 0.465871E+12 | 0.232697E+10 | 0.00 | 0.156596E+12 | 0.234273E+12 |
July | 0.435685E+12 | 0.164404E+10 | 0.00 | 0.124528E+12 | 0.238156E+12 |
August | 0.434348E+12 | 0.221136E+10 | 0.00 | 0.135777E+12 | 0.230602E+12 |
September | 0.332468E+12 | 0.488299E+10 | 0.00 | 0.204506E+12 | 0.153564E+12 |
October | 0.299408E+12 | 0.121770E+11 | 0.00 | 0.253873E+12 | 0.395133E+11 |
November | 0.269549E+12 | 0.122006E+11 | 0.00 | 0.224941E+12 | 0.272256E+11 |
December | 0.220539E+12 | 0.195447E+11 | 0.00 | 0.189326E+12 | 0.399482E+11 |
Annual Sum or Average | 0.424782E+13 | 0.120220E+12 | 0.00 | 0.238091E+13 | 0.114776E+13 |
Minimum of Months | 0.220539E+12 | 0.164404E+10 | 0.00 | 0.124528E+12 | 0.271940E+11 |
Maximum of Months | 0.465871E+12 | 0.195447E+11 | 0.00 | 0.261501E+12 | 0.238156E+12 |