Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2024-07-03 12:22:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2656.78 | 533.26 | 533.26 |
Net Site Energy | 2656.78 | 533.26 | 533.26 |
Total Source Energy | 7274.83 | 1460.17 | 1460.17 |
Net Source Energy | 7274.83 | 1460.17 | 1460.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 546.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 318.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 235.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 177.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 52.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2109.88 | 546.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 546.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 318.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 235.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 177.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 2.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 52.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 546.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 318.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 235.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 177.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 2.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 52.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.62 | 109.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 423.48 | 109.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.62 | 109.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 423.48 | 109.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2109.878 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2109.878 | 100.00 |
Total On-Site and Utility Electric Sources | 2109.878 | 100.00 |
Total Electricity End Uses | 2109.878 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 305.67 |
Time Setpoint Not Met During Occupied Cooling | 55.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2603.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 19-JUN-14:09 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 355511.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 83674.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 30944.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3190.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 210606.72 | 355511.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 355511.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 83674.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 30944.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 3190.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 592.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1008.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 746.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 561.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 8.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 167.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6681.98 | 592.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 118.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 202.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 112.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1341.18 | 118.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 118.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 202.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 112.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1341.18 | 118.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.30 | 0.227167 | 0.300000 | 0.989743 | 0.605778 | 0.500000 | 0.001677 | 0.000176 | 0.989743 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.71 | 0.276576 | 0.300000 | 0.812929 | 0.737535 | 0.500000 | 0.001378 | 0.000331 | 1.59 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 3.17 | 0.236266 | 0.300000 | 0.951624 | 0.630043 | 0.500000 | 0.001613 | 0.000618 | 2.97 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.43 | 0.110319 | 0.300000 | 0.429642 | 0.300000 | 0.500000 | 0.003454 | 0.000297 | 1.43 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.955656 | 0.104663 | 0.300000 | 0.286697 | 0.300000 | 0.500000 | 0.003640 | 0.000192 | 0.926082 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.41 | 0.111673 | 0.300000 | 0.424431 | 0.300000 | 0.500000 | 0.003412 | 0.000293 | 1.41 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.06 | 0.094150 | 0.300000 | 0.318687 | 0.300000 | 0.500000 | 0.004047 | 0.000194 | 0.937177 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.06 | 0.149090 | 0.300000 | 0.317911 | 0.397575 | 0.500000 | 0.002555 | 0.000220 | 1.06 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.786542 | 0.127167 | 0.300000 | 0.235963 | 0.339111 | 0.500000 | 0.002996 | 0.000142 | 0.686645 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.04 | 0.151490 | 0.300000 | 0.312875 | 0.403974 | 0.500000 | 0.002515 | 0.000216 | 1.04 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.814166 | 0.122844 | 0.300000 | 0.244250 | 0.327584 | 0.500000 | 0.003101 | 0.000145 | 0.697576 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 1.13 | 0.140261 | 0.300000 | 0.337923 | 0.374030 | 0.500000 | 0.002716 | 0.000234 | 1.13 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.926816 | 0.300000 | 0.500000 | 0.003530 | 0.000152 | 0.731483 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.11 | 0.142447 | 0.300000 | 0.332737 | 0.379859 | 0.500000 | 0.002675 | 0.000230 | 1.11 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.959733 | 0.104212 | 0.300000 | 0.287920 | 0.300000 | 0.500000 | 0.003656 | 0.000154 | 0.742360 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20122.01 | 0.000176 | 452.24 |
CORE_MID VAV BOX REHEAT COIL | 37833.79 | 0.000331 | 885.12 |
CORE_TOP VAV BOX REHEAT COIL | 70673.03 | 0.000618 | 1651.63 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 33931.89 | 0.000297 | 792.41 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21940.85 | 0.000192 | 512.37 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 33520.96 | 0.000293 | 782.81 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22203.31 | 0.000194 | 518.50 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 25123.35 | 0.000220 | 586.80 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 16277.97 | 0.000142 | 380.20 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 24726.29 | 0.000216 | 577.53 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 16536.52 | 0.000145 | 386.23 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 26699.91 | 0.000234 | 623.59 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 17337.67 | 0.000152 | 404.93 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 26291.05 | 0.000230 | 614.05 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 17594.95 | 0.000154 | 410.93 |
PACU_VAV_BOT HEATING COIL | 22205.28 | 0.000194 | 379.02 |
PACU_VAV_MID HEATING COIL | 22748.39 | 0.000199 | 386.30 |
PACU_VAV_TOP HEATING COIL | 19033.06 | 0.000167 | 332.64 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.50 | 2.10 | 7.00 | 4.22 | 5.92 | 5.92 | 0.300000 | 0.711929 | 5.92 |
PACU_VAV_MID | 3.42 | 2.05 | 6.83 | 5.30 | 5.63 | 5.63 | 0.300000 | 0.940639 | 5.63 |
PACU_VAV_TOP | 4.02 | 2.41 | 8.04 | 7.69 | 6.92 | 7.69 | 0.300000 | 1.00 | 7.69 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.92 |
PACU_VAV_MID_OA_CONTROLLER | 5.63 |
PACU_VAV_TOP_OA_CONTROLLER | 7.69 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.92 | 120319.66 | 0.769589 | 1.97 | 40102.54 | 0.769589 |
PACU_VAV_MID COOLING COIL | 5.63 | 116098.20 | 0.764138 | 1.88 | 38695.53 | 0.764138 |
PACU_VAV_TOP COOLING COIL | 7.69 | 152224.12 | 0.780255 | 2.56 | 50736.30 | 0.780255 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.92 |
PACU_VAV_MID FAN | 5.63 |
PACU_VAV_TOP FAN | 7.69 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000194 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000199 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000167 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004154 | 0.498451 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.004154 | 1250.93 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 474800.29 | 474800.29 | 0.004154 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
43 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
44 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
45 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
46 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
47 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
48 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
49 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39484.19222 | 45406.82105 | 2.86882 | 3.29914 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8215.34832 | 10269.18540 | 0.58385 | 0.72981 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32456.11966 | 37324.53760 | 2.35632 | 2.70976 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 17631.95230 | 22039.94038 | 1.26923 | 1.58654 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 37645.18500 | 43291.96275 | 2.75833 | 3.17208 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 32846.09819 | 41057.62274 | 2.37996 | 2.97495 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 11427.22806 | 13141.31227 | 0.83737 | 0.96298 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15750.22995 | 19687.78743 | 1.14571 | 1.43214 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11340.39523 | 13041.45451 | 0.83101 | 0.95566 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.65900 | 1.41134E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10184.21583 | 12730.26979 | 0.74087 | 0.92608 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14860.45485 | 17089.52307 | 1.08895 | 1.25229 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15559.78375 | 19449.72968 | 1.13181 | 1.41477 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12605.82444 | 14496.69810 | 0.92373 | 1.06229 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.41183E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10305.85378 | 12882.31723 | 0.74974 | 0.93718 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8436.54372 | 9702.02528 | 0.61819 | 0.71092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11664.41006 | 14580.51257 | 0.84776 | 1.05970 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9334.00375 | 10734.10431 | 0.68395 | 0.78654 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.65900 | 1.41134E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7557.40672 | 9446.75840 | 0.54932 | 0.68665 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11521.31788 | 13249.51557 | 0.84423 | 0.97086 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11480.42536 | 14350.53170 | 0.83433 | 1.04292 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9661.83477 | 11111.10999 | 0.70797 | 0.81417 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.41178E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7677.21292 | 9596.51615 | 0.55806 | 0.69758 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9443.27542 | 10859.76674 | 0.69198 | 0.79578 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12397.27475 | 15496.59344 | 0.90113 | 1.12641 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10998.34473 | 12648.09643 | 0.80593 | 0.92682 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8049.99366 | 10062.49207 | 0.58519 | 0.73148 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12988.55535 | 14936.83865 | 0.95177 | 1.09453 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12207.80566 | 15259.75707 | 0.88730 | 1.10912 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11388.97130 | 13097.31700 | 0.83455 | 0.95973 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8169.21555 | 10211.51944 | 0.59389 | 0.74236 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 88950.28 | 5.92286 | 5.92286 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 27269.54 | 4.21665 | 4.21665 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 85009.94 | 5.63013 | 5.63013 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 27276.40 | 5.29591 | 5.29591 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 102332.74 | 6.91899 | 6.91899 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 26927.99 | 7.68512 | 7.68512 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.29914 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22717 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.98974 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60578 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.67718E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76036E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.98974 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20122.00861 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76036E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 452.24292 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.70976 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27658 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81293 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73754 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37756E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.30987E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.58654 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37833.79323 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.30987E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 885.11765 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.17208 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23627 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.95162 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63004 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61259E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.18279E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.97495 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 70673.03493 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.18279E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1651.63099 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43214 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11032 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42964 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45363E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.96851E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.43214 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 33931.89472 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.96851E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 792.40618 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95566 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10466 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28670 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64026E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.91948E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.92608 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21940.84627 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.91948E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 512.37492 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41477 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11167 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42443 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.41174E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.93256E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.41477 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 33520.96050 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93256E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 782.81381 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06229 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.41505E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31869 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.04671E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94244E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.93718 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22203.30836 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94244E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 518.50151 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05970 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14909 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31791 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39757 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55550E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.19790E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.05970 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25123.35329 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.19790E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 586.80304 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78654 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12717 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23596 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33911 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99607E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42407E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68665 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16277.96841 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42407E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 380.19634 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04292 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15149 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31288 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40397 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.51502E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.16316E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.04292 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24726.28948 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.16316E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 577.53472 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81417 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12284 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24425 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32758 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10150E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.44669E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69758 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16536.52232 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44669E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 386.23155 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12641 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14026 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33792 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37403 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71636E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.33582E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.12641 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26699.91299 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.33582E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 623.59486 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92682 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.53040E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51678E-004 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73148 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17337.67476 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51678E-004 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 404.92629 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10912 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14245 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33274 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37986 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67468E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.30006E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.10912 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26291.05214 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.30006E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 614.05111 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95973 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10421 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28792 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.65603E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53928E-004 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74236 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17594.94580 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53928E-004 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 410.93158 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.50123 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.10074 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.00247 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.21665 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.92286 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.92286 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.71193 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.41592 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.04955 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.83185 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.29591 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.63013 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.63013 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.94064 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.01847 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.41108 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.03694 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 7.68512 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.91899 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 7.68512 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.92286 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.63013 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 7.68512 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.92286 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.92286 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 120319.65964 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76959 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.97409 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 40102.54256 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76959 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 22205.27747 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94261E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 379.01577 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.92286 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.94261E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.63013 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.63013 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 116098.20281 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76414 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.87652 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38695.53100 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76414 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 22748.38600 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99013E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 386.29721 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.63013 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.99013E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.68512 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 7.68512 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 152224.11975 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78026 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.56145 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 50736.29911 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78026 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 19033.06112 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66510E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 332.63834 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 7.68512 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.66510E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.15376E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.49845 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.15376E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1250.93012 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 474800.29040 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 474800.29000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.15376E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 19093.26 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 35890.72 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 67043.73 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32189.48 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20814.18 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 31799.65 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21063.16 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 23833.24 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 15442.08 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 23456.57 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 15687.36 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 25328.85 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 16447.37 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 24940.99 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 16691.43 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 18346.15 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 18607.28 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 16451.23 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 119289.85 | 407033.87 | 11.52 | 2.97 | 3.30 | 3.47 | 3.65 | 10.13 | 11.25 | 11.84 | 12.46 | 6.8472 | 5.4651 | 3.6772 | 1.4826 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 115170.20 | 392977.03 | 11.56 | 2.97 | 3.31 | 3.48 | 3.66 | 10.15 | 11.29 | 11.88 | 12.49 | 6.5088 | 5.1901 | 3.4914 | 1.4155 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 150772.97 | 514458.74 | 11.46 | 2.96 | 3.28 | 3.45 | 3.64 | 10.09 | 11.19 | 11.77 | 12.43 | 8.8845 | 7.0984 | 4.7848 | 1.9063 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 9.1392530123E-002 | 6.4807732933E-002 | Pass | Pass | 0.4864906375 | 0.4880522120 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.3077532216 | 0.2499403228 | Pass | Pass | 0.4899074487 | 0.4928047582 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1288604296 | 8.0751665101E-002 | Pass | Pass | 0.4878880926 | 0.4824314898 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1066114759 | 6.8769314433E-002 | Pass | Pass | 0.4857091378 | 0.4799121730 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.9161224766E-002 | 2.1194574597E-002 | Pass | Pass | 0.7980433640 | 1.3195333158 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1421561098 | 0.1682027490 | Pass | Pass | 0.7372207718 | 0.7427316142 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7625017252 | 0.7313932625 | Pass | Pass | 0.6581863797 | 0.5950959297 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6923587915 | 0.7188268876 | Pass | Pass | 0.6832097590 | 0.6352213179 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5773607447 | 0.6773637099 | Pass | Pass | 0.8073230048 | 0.9726433594 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7625367820 | 0.7530247888 | Pass | Pass | 0.6796300385 | 0.6335220240 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5270849716 | 0.5194809786 | Pass | Pass | 0.6883349813 | 0.6108185198 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4350714211 | 0.4890446559 | Pass | Pass | 0.7854711054 | 0.7904540344 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3252052840 | 0.4021110927 | Pass | Pass | 0.7060923729 | 0.7587195640 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5172289014 | 0.5253822956 | Pass | Pass | 0.7504900339 | 0.7414825686 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6016267305 | 0.5805163698 | Pass | Pass | 0.6994939981 | 0.6131826108 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5312550759 | 0.5803825412 | Pass | Pass | 0.7562213519 | 0.7858932851 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4425693537 | 0.5190430914 | Pass | Pass | 0.7124918463 | 0.7204635214 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6018139555 | 0.6045251843 | Pass | Pass | 0.7481628472 | 0.7265242827 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3683.93 | 123.87 | 0.00 | 732.47 | 1838.74 | 6379.03 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 183.92 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 429.15 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.64 | 83.64 | 235.72 | |
Exterior Lighting Total | 15013.15 | 235.72 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 474800.29 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 120319.66 | 92596.74 | 27722.92 | 0.77 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 116098.20 | 88715.01 | 27383.19 | 0.76 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 152224.12 | 118773.66 | 33450.46 | 0.78 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 119289.9 | 2.97 | 10.13 | N/A | N/A | 11.52 | |
PACU_VAV_MID COOLING COIL | 115170.2 | 2.97 | 10.15 | N/A | N/A | 11.56 | |
PACU_VAV_TOP COOLING COIL | 150773.0 | 2.96 | 10.09 | N/A | N/A | 11.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 20122.01 | 19093.26 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 37833.79 | 35890.72 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 70673.03 | 67043.73 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 33931.89 | 32189.48 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 21940.85 | 20814.18 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 33520.96 | 31799.65 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 22203.31 | 21063.16 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 25123.35 | 23833.24 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16277.97 | 15442.08 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24726.29 | 23456.57 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 16536.52 | 15687.36 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 26699.91 | 25328.85 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 17337.67 | 16447.37 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26291.05 | 24940.99 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 17594.95 | 16691.43 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 22205.28 | 18346.15 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 22748.39 | 18607.28 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 19033.06 | 16451.23 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.92 | 13101.12 | 2211.96 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.63 | 12453.62 | 2211.96 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.69 | 16890.22 | 2197.78 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004154 | 1250.93 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 119289.85 | 2.97 | 10.13 | 11.52 | 6.8472 | 3.30 | 11.25 | 5.4651 | 3.47 | 11.84 | 3.6772 | 3.65 | 12.46 | 1.4826 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 115170.20 | 2.97 | 10.15 | 11.56 | 6.5088 | 3.31 | 11.29 | 5.1901 | 3.48 | 11.88 | 3.4914 | 3.66 | 12.49 | 1.4155 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 150772.97 | 2.96 | 10.09 | 11.46 | 8.8845 | 3.28 | 11.19 | 7.0984 | 3.45 | 11.77 | 4.7848 | 3.64 | 12.43 | 1.9063 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39484.19 | 45406.82 | 46.17 | 2.869 | 3.299 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00881 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_MID | 32456.12 | 37324.54 | 37.95 | 2.356 | 2.710 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_TOP | 37645.19 | 43291.96 | 44.02 | 2.758 | 3.172 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00882 | 32.10 | 0.01412 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11427.23 | 13141.31 | 63.38 | 0.837 | 0.963 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00897 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11340.40 | 13041.45 | 99.35 | 0.831 | 0.956 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00881 | 28.66 | 0.01411 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14860.45 | 17089.52 | 82.42 | 1.089 | 1.252 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00886 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12605.82 | 14496.70 | 110.45 | 0.924 | 1.062 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00878 | 31.36 | 0.01412 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8436.54 | 9702.03 | 46.79 | 0.618 | 0.711 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00898 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9334.00 | 10734.10 | 81.78 | 0.684 | 0.787 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00878 | 28.66 | 0.01411 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11521.32 | 13249.52 | 63.90 | 0.844 | 0.971 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00885 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9661.83 | 11111.11 | 84.65 | 0.708 | 0.814 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00877 | 31.06 | 0.01412 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9443.28 | 10859.77 | 52.38 | 0.692 | 0.796 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00901 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10998.34 | 12648.10 | 96.36 | 0.806 | 0.927 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00879 | 28.24 | 0.01411 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12988.56 | 14936.84 | 72.04 | 0.952 | 1.095 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00888 | 31.79 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11388.97 | 13097.32 | 99.79 | 0.835 | 0.960 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00878 | 31.26 | 0.01412 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8215.35 | 10269.19 | 10.44 | 0.584 | 0.730 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_MID | 17631.95 | 22039.94 | 22.41 | 1.269 | 1.587 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_TOP | 32846.10 | 41057.62 | 41.74 | 2.380 | 2.975 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15750.23 | 19687.79 | 94.95 | 1.146 | 1.432 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10184.22 | 12730.27 | 96.98 | 0.741 | 0.926 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15559.78 | 19449.73 | 93.81 | 1.132 | 1.415 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10305.85 | 12882.32 | 98.15 | 0.750 | 0.937 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11664.41 | 14580.51 | 70.32 | 0.848 | 1.060 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7557.41 | 9446.76 | 71.97 | 0.549 | 0.687 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11480.43 | 14350.53 | 69.21 | 0.834 | 1.043 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7677.21 | 9596.52 | 73.11 | 0.558 | 0.698 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12397.27 | 15496.59 | 74.74 | 0.901 | 1.126 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8049.99 | 10062.49 | 76.66 | 0.585 | 0.731 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12207.81 | 15259.76 | 73.60 | 0.887 | 1.109 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8169.22 | 10211.52 | 77.80 | 0.594 | 0.742 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.92 | 5.92 | 4.22 | 4.22 | 5.9229 | 4.2167 | 5.9229 | 0.7119 | 0.3000 |
PACU_VAV_MID | 5.63 | 5.63 | 5.30 | 5.30 | 5.6301 | 5.2959 | 5.6301 | 0.9406 | 0.3000 |
PACU_VAV_TOP | 6.92 | 6.92 | 7.69 | 7.69 | 6.9190 | 7.6851 | 7.6851 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20122.009 | 20122.009 | 0.989743 | 0.00017604 | 452.243 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20122.01 | 20122.01 | 0.989743 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6927 | 10269.19 | 0.00 | 20216.90 | 20216.90 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 37833.793 | 37833.793 | 1.586538 | 0.00033099 | 885.118 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37833.79 | 37833.79 | 1.586538 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 22039.94 | 0.00 | 38007.14 | 38007.14 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 70673.035 | 70673.035 | 2.974954 | 0.00061828 | 1651.631 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 70673.03 | 70673.03 | 2.974954 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 41057.62 | 0.00 | 70996.99 | 70996.99 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 33931.895 | 33931.895 | 1.432140 | 0.00029685 | 792.406 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33931.89 | 33786.73 | 1.432140 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00765021 | 49.4663 | 19687.79 | 0.00 | 34087.48 | 34087.48 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 21940.846 | 21940.846 | 0.926082 | 0.00019195 | 512.375 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21940.85 | 21940.85 | 0.926082 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00763978 | 49.3999 | 12730.27 | 0.00 | 22041.45 | 22041.45 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 33520.960 | 33520.960 | 1.414769 | 0.00029326 | 782.814 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33520.96 | 33376.92 | 1.414769 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00764615 | 49.4404 | 19449.73 | 0.00 | 33674.66 | 33674.66 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 22203.308 | 22203.308 | 0.937177 | 0.00019424 | 518.502 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22203.31 | 22203.31 | 0.937177 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00764380 | 49.4257 | 12882.32 | 0.00 | 22305.11 | 22305.11 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 25123.353 | 25123.353 | 1.059703 | 0.00021979 | 586.803 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25123.35 | 25000.30 | 1.059703 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00774694 | 50.0814 | 14580.51 | 0.00 | 25238.54 | 25238.54 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 16277.968 | 16277.968 | 0.686645 | 0.00014241 | 380.196 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16277.97 | 16277.97 | 0.686645 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00773992 | 50.0367 | 9446.76 | 0.00 | 16352.60 | 16352.60 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 24726.289 | 24726.289 | 1.042917 | 0.00021632 | 577.535 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24726.29 | 24604.28 | 1.042917 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00774293 | 50.0558 | 14350.53 | 0.00 | 24839.66 | 24839.66 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 16536.522 | 16536.522 | 0.697576 | 0.00014467 | 386.232 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16536.52 | 16536.52 | 0.697576 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00774388 | 50.0620 | 9596.52 | 0.00 | 16612.34 | 16612.34 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 26699.913 | 26699.913 | 1.126409 | 0.00023358 | 623.595 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26699.91 | 26574.00 | 1.126409 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00763269 | 49.3536 | 15496.59 | 0.00 | 26822.33 | 26822.33 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 17337.675 | 17337.675 | 0.731483 | 0.00015168 | 404.926 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17337.67 | 17337.67 | 0.731483 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762333 | 49.2940 | 10062.49 | 0.00 | 17417.17 | 17417.17 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 26291.052 | 26291.052 | 1.109125 | 0.00023001 | 614.051 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26291.05 | 26166.23 | 1.109125 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762727 | 49.3190 | 15259.76 | 0.00 | 26411.59 | 26411.59 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 17594.946 | 17594.946 | 0.742360 | 0.00015393 | 410.932 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17594.95 | 17594.95 | 0.742360 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762854 | 49.3273 | 10211.52 | 0.00 | 17675.62 | 17675.62 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 120319.660 | 92596.739 | 5.922855 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 121687.73 | 99764.64 | 5.922855 | 25.31 | 17.84 | 0.00970725 | 11.09 | 11.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 16.1426 | 24.00 | 0.00885787 | 47.6372 | 70288.77 | 0.00 | 124065.72 | 93961.60 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 22205.277 | 22205.277 | 1.776857 | 0.00019426 | 379.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22205.28 | 22205.28 | 1.776857 | 2.56 | 2.00 | 0.00414055 | 12.89 | 11.63 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 53.8085 | 18.19 | 0.00752487 | 57.9286 | 8611.81 | 0.00 | 22205.54 | 22205.54 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 116098.203 | 88715.009 | 5.630127 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 117666.99 | 95215.86 | 5.630127 | 25.37 | 17.94 | 0.00980174 | 11.09 | 11.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 16.9819 | 24.00 | 0.00891841 | 47.9589 | 66808.32 | 0.00 | 119712.83 | 90027.58 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 22748.386 | 22748.386 | 1.689038 | 0.00019901 | 386.297 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22748.39 | 22748.39 | 1.689038 | 1.75 | 1.20 | 0.00389837 | 12.89 | 11.63 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 56.6062 | 17.63 | 0.00749598 | 59.8114 | 8615.64 | 0.00 | 22520.32 | 22520.32 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 152224.120 | 118773.661 | 7.685122 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 153437.29 | 127796.87 | 7.685122 | 25.12 | 17.68 | 0.00958724 | 11.10 | 11.10 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 12.4409 | 24.00 | 0.00886051 | 47.6520 | 82108.17 | 0.00 | 156963.50 | 120486.05 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 19033.061 | 19033.061 | 2.305537 | 0.00016651 | 332.638 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19033.06 | 19033.06 | 2.305537 | 6.06 | 4.88 | 0.00487518 | 12.89 | 11.63 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 41.4697 | 16.86 | 0.00770279 | 64.4850 | 9534.86 | 0.00 | 19915.10 | 19915.10 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 20122.009 | 20122.009 | 0.989743 | 0.00017604 | 452.243 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 4.1544 | 4.237994 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20122.01 | 20122.01 | 1.0000 | 1.19124913 | 0.989743 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.17601815 | 60.00 | 32.22 | 27.78 | 0.000 | 20122.01 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.89 | 0.00800000 | 21.00 | 0.00800000 | 51.6927 | 10269.19 | 0.00 | 20216.90 | 20216.90 | 1.19124913 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.44 | 17.85 | 0.00800000 | 50031.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 37833.793 | 37833.793 | 1.586538 | 0.00033099 | 885.118 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 7.8112 | 7.968359 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37833.79 | 37833.79 | 1.0000 | 1.90954972 | 1.586538 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.33095276 | 60.00 | 32.22 | 27.78 | 0.000 | 37833.79 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 22039.94 | 0.00 | 38007.14 | 38007.14 | 1.90954972 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.32 | 18.80 | 0.00800000 | 52963.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 70673.035 | 70673.035 | 2.974954 | 0.00061828 | 1651.631 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 14.5911 | 14.884792 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 70673.03 | 70673.03 | 1.0000 | 3.58064006 | 2.974954 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.61821547 | 60.00 | 32.22 | 27.78 | 0.000 | 70673.03 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 41057.62 | 0.00 | 70996.99 | 70996.99 | 3.58064006 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.24 | 18.78 | 0.00800000 | 52887.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33931.895 | 33931.895 | 1.432140 | 0.00029685 | 792.406 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 7.0056 | 7.146561 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 33931.89 | 33786.73 | 1.0000 | 1.72371603 | 1.432140 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.29682074 | 60.00 | 32.22 | 27.78 | 0.000 | 33931.89 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00765021 | 21.00 | 0.00765021 | 49.4663 | 19687.79 | 0.00 | 34087.48 | 34087.48 | 1.72371603 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21940.846 | 21940.846 | 0.926082 | 0.00019195 | 512.375 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 4.5299 | 4.621068 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21940.85 | 21940.85 | 1.0000 | 1.11462798 | 0.926082 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.19192851 | 60.00 | 32.22 | 27.78 | 0.000 | 21940.85 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00763978 | 21.00 | 0.00763978 | 49.3999 | 12730.27 | 0.00 | 22041.45 | 22041.45 | 1.11462798 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33520.960 | 33520.960 | 1.414769 | 0.00029326 | 782.814 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 6.9207 | 7.060013 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 33520.96 | 33376.92 | 1.0000 | 1.70280854 | 1.414769 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.29322607 | 60.00 | 32.22 | 27.78 | 0.000 | 33520.96 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00764615 | 21.00 | 0.00764615 | 49.4404 | 19449.73 | 0.00 | 33674.66 | 33674.66 | 1.70280854 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22203.308 | 22203.308 | 0.937177 | 0.00019424 | 518.502 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 4.5841 | 4.676347 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22203.31 | 22203.31 | 1.0000 | 1.12798158 | 0.937177 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.19422441 | 60.00 | 32.22 | 27.78 | 0.000 | 22203.31 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00764380 | 21.00 | 0.00764380 | 49.4257 | 12882.32 | 0.00 | 22305.11 | 22305.11 | 1.12798158 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25123.353 | 25123.353 | 1.059703 | 0.00021979 | 586.803 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 5.1870 | 5.291352 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25123.35 | 25000.30 | 1.0000 | 1.27545379 | 1.059703 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.21976763 | 60.00 | 32.22 | 27.78 | 0.000 | 25123.35 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00774694 | 21.00 | 0.00774694 | 50.0814 | 14580.51 | 0.00 | 25238.54 | 25238.54 | 1.27545379 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52847.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16277.968 | 16277.968 | 0.686645 | 0.00014241 | 380.196 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 3.3607 | 3.428382 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16277.97 | 16277.97 | 1.0000 | 0.82644250 | 0.686645 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.14239224 | 60.00 | 32.22 | 27.78 | 0.000 | 16277.97 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00773992 | 21.00 | 0.00773992 | 50.0367 | 9446.76 | 0.00 | 16352.60 | 16352.60 | 0.82644250 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52846.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24726.289 | 24726.289 | 1.042917 | 0.00021632 | 577.535 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 5.1050 | 5.207724 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24726.29 | 24604.28 | 1.0000 | 1.25524998 | 1.042917 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.21629430 | 60.00 | 32.22 | 27.78 | 0.000 | 24726.29 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00774293 | 21.00 | 0.00774293 | 50.0558 | 14350.53 | 0.00 | 24839.66 | 24839.66 | 1.25524998 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52848.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16536.522 | 16536.522 | 0.697576 | 0.00014467 | 386.232 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 3.4141 | 3.482837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16536.52 | 16536.52 | 1.0000 | 0.83959841 | 0.697576 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.14465395 | 60.00 | 32.22 | 27.78 | 0.000 | 16536.52 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00774388 | 21.00 | 0.00774388 | 50.0620 | 9596.52 | 0.00 | 16612.34 | 16612.34 | 0.83959841 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52845.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26699.913 | 26699.913 | 1.126409 | 0.00023358 | 623.595 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 5.5125 | 5.623399 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26699.91 | 26574.00 | 1.0000 | 1.35574038 | 1.126409 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.23355866 | 60.00 | 32.22 | 27.78 | 0.000 | 26699.91 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00763269 | 21.00 | 0.00763269 | 49.3536 | 15496.59 | 0.00 | 26822.33 | 26822.33 | 1.35574038 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52844.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17337.675 | 17337.675 | 0.731483 | 0.00015168 | 404.926 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 3.5795 | 3.651572 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17337.67 | 17337.67 | 1.0000 | 0.88040962 | 0.731483 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.15166207 | 60.00 | 32.22 | 27.78 | 0.000 | 17337.67 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00762333 | 21.00 | 0.00762333 | 49.2940 | 10062.49 | 0.00 | 17417.17 | 17417.17 | 0.88040962 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.9 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26291.052 | 26291.052 | 1.109125 | 0.00023001 | 614.051 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 5.4280 | 5.537286 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26291.05 | 26166.23 | 1.0000 | 1.33493670 | 1.109125 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.22998213 | 60.00 | 32.22 | 27.78 | 0.000 | 26291.05 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00762727 | 21.00 | 0.00762727 | 49.3190 | 15259.76 | 0.00 | 26411.59 | 26411.59 | 1.33493670 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52844.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17594.946 | 17594.946 | 0.742360 | 0.00015393 | 410.932 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 3.6326 | 3.705757 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17594.95 | 17594.95 | 1.0000 | 0.89350018 | 0.742360 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.15391256 | 60.00 | 32.22 | 27.78 | 0.000 | 17594.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00762854 | 21.00 | 0.00762854 | 49.3273 | 10211.52 | 0.00 | 17675.62 | 17675.62 | 0.89350018 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52842.3 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 120319.660 | 92596.739 | 5.922855 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8853 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.922855 | 7.12871915 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 121687.73 | 99764.64 | 1.0114 | 7.12871915 | 5.922855 | 25.31 | 17.84 | 0.00970725 | 50162.7 | 11.09 | 11.09 | 0.00850000 | 32579.2 | -999.0 | -999.00 | -999.00 | -999.00 | 13101.121 | 108586.61 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 16.1426 | 24.00 | 0.00885787 | 24.00 | 0.00885787 | 47.6372 | 70288.77 | 0.00 | 124065.72 | 93961.60 | 6.84718863 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.25 | 13.22 | 0.00946087 | 37203.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 22205.277 | 22205.277 | 1.776857 | 0.00019426 | 379.016 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.922855 | 7.12871915 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 4.5845 | 4.676762 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22205.28 | 22205.28 | 1.0000 | 2.13861575 | 1.776857 | 2.56 | 2.00 | 0.00414055 | 12943.4 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 0.19424164 | 60.00 | 32.22 | 27.78 | 0.000 | 22205.28 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 53.8085 | 18.00 | 0.00721198 | 18.19 | 0.00752487 | 57.9286 | 8611.81 | 0.00 | 22205.54 | 22205.54 | 2.13861575 | 2.80 | 2.14 | 0.00414055 | 13190.4 | 13.05 | 7.47 | 0.00414055 | 23573.5 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 116098.203 | 88715.009 | 5.630127 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0610 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.630127 | 6.77639230 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 117666.99 | 95215.86 | 1.0135 | 6.77639230 | 5.630127 | 25.37 | 17.94 | 0.00980174 | 50472.9 | 11.09 | 11.09 | 0.00850000 | 32579.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12453.617 | 105213.37 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 16.9819 | 24.00 | 0.00891841 | 24.00 | 0.00891841 | 47.9589 | 66808.32 | 0.00 | 119712.83 | 90027.58 | 6.50877603 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.14 | 13.12 | 0.00939647 | 36929.9 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 22748.386 | 22748.386 | 1.689038 | 0.00019901 | 386.297 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.630127 | 6.77639230 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 4.6966 | 4.791148 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22748.39 | 22748.39 | 1.0000 | 2.03291769 | 1.689038 | 1.75 | 1.20 | 0.00389837 | 11523.8 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 0.19899250 | 60.00 | 32.22 | 27.78 | 0.000 | 22748.39 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 56.6062 | 18.00 | 0.00702189 | 17.63 | 0.00749598 | 59.8114 | 8615.64 | 0.00 | 22520.32 | 22520.32 | 2.03291769 | 2.80 | 1.80 | 0.00389837 | 12583.4 | 13.75 | 7.52 | 0.00389837 | 23661.3 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 152224.120 | 118773.661 | 7.685122 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6622 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 7.685122 | 9.24977418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 153437.29 | 127796.87 | 1.0080 | 9.24977418 | 7.685122 | 25.12 | 17.68 | 0.00958724 | 49664.1 | 11.10 | 11.10 | 0.00850000 | 32590.5 | -999.0 | -999.00 | -999.00 | -999.00 | 16890.215 | 136547.07 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 12.4409 | 24.00 | 0.00886051 | 24.00 | 0.00886051 | 47.6520 | 82108.17 | 0.00 | 156963.50 | 120486.05 | 8.88447803 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.41 | 13.39 | 0.00957489 | 37655.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 19033.061 | 19033.061 | 2.305537 | 0.00016651 | 332.638 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 7.685122 | 9.24977418 | 4197.9300 | 999.8980 | 4.15333634 | 54.44 | 82.22 | 27.78 | 484355.83 | 3.9296 | 4.008646 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19033.06 | 19033.06 | 1.0000 | 2.77493225 | 2.305537 | 6.06 | 4.88 | 0.00487518 | 18340.0 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 0.16649254 | 60.00 | 32.22 | 27.78 | 0.000 | 19033.06 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 41.4697 | 17.94 | 0.00726379 | 16.86 | 0.00770279 | 64.4850 | 9534.86 | 0.00 | 19915.10 | 19915.10 | 2.77493225 | 2.80 | 2.80 | 0.00487518 | 15031.5 | 9.88 | 6.81 | 0.00487518 | 22208.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2687.33 | 2370.33 | 60.17 |
CORE_MID | 2458.33 | 3292.33 | 449.17 |
CORE_TOP | 2943.50 | 3726.50 | 1242.83 |
PERIMETER_TOP_ZN_3 | 3463.33 | 4363.67 | 2227.50 |
PERIMETER_TOP_ZN_2 | 3625.83 | 4024.67 | 2007.50 |
PERIMETER_TOP_ZN_1 | 3339.50 | 3859.67 | 1688.83 |
PERIMETER_TOP_ZN_4 | 3505.83 | 4212.33 | 2068.17 |
PERIMETER_BOT_ZN_3 | 3384.83 | 4205.83 | 1993.00 |
PERIMETER_BOT_ZN_2 | 3472.50 | 3768.83 | 1661.50 |
PERIMETER_BOT_ZN_1 | 3283.00 | 3812.17 | 1535.00 |
PERIMETER_BOT_ZN_4 | 3465.17 | 3862.67 | 1737.17 |
PERIMETER_MID_ZN_3 | 3380.83 | 4029.50 | 1824.00 |
PERIMETER_MID_ZN_2 | 2854.83 | 3344.50 | 1462.50 |
PERIMETER_MID_ZN_1 | 3267.67 | 3411.17 | 1278.17 |
PERIMETER_MID_ZN_4 | 3296.17 | 3954.67 | 1671.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5107.00 | 4767.83 | 2603.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 3.00 | 0.00 | 2.67 | 0.00 |
CORE_MID | 3.83 | 0.00 | 3.33 | 0.00 |
CORE_TOP | 11.67 | 0.00 | 9.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 82.00 | 0.00 | 30.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 77.33 | 11.50 | 23.17 | 11.50 |
PERIMETER_TOP_ZN_1 | 60.67 | 11.50 | 17.83 | 11.50 |
PERIMETER_TOP_ZN_4 | 77.83 | 13.00 | 25.67 | 10.67 |
PERIMETER_BOT_ZN_3 | 21.50 | 0.00 | 10.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 14.50 | 4.83 | 5.33 | 4.83 |
PERIMETER_BOT_ZN_1 | 286.17 | 8.83 | 280.17 | 8.83 |
PERIMETER_BOT_ZN_4 | 18.00 | 5.50 | 8.50 | 4.00 |
PERIMETER_MID_ZN_3 | 26.50 | 0.00 | 10.33 | 0.00 |
PERIMETER_MID_ZN_2 | 23.00 | 10.33 | 6.67 | 10.33 |
PERIMETER_MID_ZN_1 | 18.00 | 12.67 | 6.00 | 12.67 |
PERIMETER_MID_ZN_4 | 24.67 | 10.67 | 9.33 | 8.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 370.00 | 59.83 | 305.67 | 55.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.435 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.378 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.370 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.730 | 0.106 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.819 | 0.112 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.786 | 0.106 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.897 | 0.112 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.514 | 0.056 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.638 | 0.060 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.594 | 0.863 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.658 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.677 | 0.088 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.878 | 0.099 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.764 | 0.089 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.942 | 0.093 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 6973474.46 | 0.00 | 6973474.46 | 0.00 | 6973474.46 | 13393058.27 | 7721.68 | 112.70 | 925.63 | 101.80 |
CORE_MID | 6118382.34 | 0.00 | 6118382.34 | 0.00 | 6118382.34 | 13393058.27 | 8751.48 | 1.15 | 7.36 | 124.00 |
CORE_TOP | 6186734.45 | 0.00 | 6186734.45 | 0.00 | 6186734.45 | 13393058.27 | 8759.06 | 0.06 | 0.89 | 285.82 |
PERIMETER_TOP_ZN_3 | 2595726.42 | 0.00 | 2595726.42 | 696839.46 | 3292565.88 | 2823374.22 | 3667.27 | 30.50 | 5062.23 | 285.82 |
PERIMETER_TOP_ZN_2 | 1834606.50 | 0.00 | 1834606.50 | 464556.85 | 2299163.35 | 1787429.43 | 3599.13 | 0.47 | 5160.40 | 285.82 |
PERIMETER_TOP_ZN_1 | 2773825.03 | 0.00 | 2773825.03 | 696839.46 | 3470664.49 | 2823374.22 | 3603.74 | 2.12 | 5154.15 | 285.82 |
PERIMETER_TOP_ZN_4 | 2010394.37 | 0.00 | 2010394.37 | 464556.85 | 2474951.22 | 1787312.18 | 3600.43 | 2.51 | 5157.06 | 285.82 |
PERIMETER_BOT_ZN_3 | 1758933.97 | 0.00 | 1758933.97 | 370505.73 | 2129439.70 | 2823374.22 | 5639.09 | 127.02 | 2993.89 | 101.80 |
PERIMETER_BOT_ZN_2 | 1378969.24 | 0.00 | 1378969.24 | 247002.33 | 1625971.57 | 1787429.43 | 4136.04 | 66.53 | 4557.42 | 101.80 |
PERIMETER_BOT_ZN_1 | 2022724.61 | 0.00 | 2022724.61 | 3064686.73 | 5087411.34 | 2823374.22 | 4788.57 | 105.03 | 3866.39 | 101.80 |
PERIMETER_BOT_ZN_4 | 1422365.97 | 0.00 | 1422365.97 | 247002.33 | 1669368.30 | 1787312.18 | 4210.65 | 75.08 | 4474.27 | 101.80 |
PERIMETER_MID_ZN_3 | 2323705.22 | 0.00 | 2323705.22 | 580065.25 | 2903770.47 | 2823374.22 | 4044.88 | 51.78 | 4663.34 | 124.00 |
PERIMETER_MID_ZN_2 | 1748694.48 | 0.00 | 1748694.48 | 386707.84 | 2135402.32 | 1601953.02 | 3803.79 | 0.82 | 4955.39 | 1033.00 |
PERIMETER_MID_ZN_1 | 2604735.65 | 0.00 | 2604735.65 | 580065.25 | 3184800.90 | 2823374.22 | 3854.59 | 16.91 | 4888.50 | 124.00 |
PERIMETER_MID_ZN_4 | 2043802.35 | 0.00 | 2043802.35 | 386707.84 | 2430510.19 | 1787312.18 | 3817.02 | 7.79 | 4935.18 | 124.00 |
Total Facility | 43797075.07 | 0.00 | 43797075.07 | 8185535.92 | 51982610.99 | 67658168.57 | 8760.00 | 546.03 | 5282.22 | 1244.56 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3196 | 0.0000 | 0.3196 | 0.0000 | 0.3196 | 0.4247 | 4907.05 | 112.58 | 923.36 |
CORE_MID | 0.2788 | 0.0000 | 0.2788 | 0.0000 | 0.2788 | 0.4247 | 5934.80 | 1.11 | 7.09 |
CORE_TOP | 0.2732 | 0.0000 | 0.2732 | 0.0000 | 0.2732 | 0.4247 | 5942.32 | 0.06 | 0.63 |
PERIMETER_TOP_ZN_3 | 0.1140 | 0.0000 | 0.1140 | 0.0166 | 0.1306 | 0.0895 | 1135.67 | 30.44 | 4776.89 |
PERIMETER_TOP_ZN_2 | 0.0809 | 0.0000 | 0.0809 | 0.0111 | 0.0919 | 0.0567 | 1067.60 | 0.43 | 4874.97 |
PERIMETER_TOP_ZN_1 | 0.1224 | 0.0000 | 0.1224 | 0.0166 | 0.1390 | 0.0895 | 1072.14 | 2.09 | 4868.77 |
PERIMETER_TOP_ZN_4 | 0.0885 | 0.0000 | 0.0885 | 0.0111 | 0.0996 | 0.0567 | 1069.15 | 2.49 | 4871.37 |
PERIMETER_BOT_ZN_3 | 0.0802 | 0.0000 | 0.0802 | 0.0088 | 0.0890 | 0.0895 | 2920.74 | 126.92 | 2895.33 |
PERIMETER_BOT_ZN_2 | 0.0629 | 0.0000 | 0.0629 | 0.0059 | 0.0688 | 0.0567 | 1419.48 | 66.53 | 4456.98 |
PERIMETER_BOT_ZN_1 | 0.0925 | 0.0000 | 0.0925 | 0.1348 | 0.2273 | 0.0895 | 2070.18 | 104.98 | 3767.85 |
PERIMETER_BOT_ZN_4 | 0.0649 | 0.0000 | 0.0649 | 0.0059 | 0.0708 | 0.0567 | 1494.39 | 75.00 | 4373.60 |
PERIMETER_MID_ZN_3 | 0.1056 | 0.0000 | 0.1056 | 0.0138 | 0.1194 | 0.0895 | 1351.07 | 51.71 | 4540.22 |
PERIMETER_MID_ZN_2 | 0.0866 | 0.0000 | 0.0866 | 0.0098 | 0.0964 | 0.0567 | 1110.38 | 0.72 | 3922.90 |
PERIMETER_MID_ZN_1 | 0.1188 | 0.0000 | 0.1188 | 0.0138 | 0.1326 | 0.0895 | 1160.86 | 16.88 | 4765.26 |
PERIMETER_MID_ZN_4 | 0.0930 | 0.0000 | 0.0930 | 0.0092 | 0.1022 | 0.0567 | 1123.94 | 7.76 | 4811.29 |
Total Facility | 1.9820 | 0.0000 | 1.9820 | 0.2573 | 2.2393 | 2.1513 | 5943.00 | 545.38 | 4946.66 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 19638452.20 | 0.00 | 19638452.20 | 22614548.33 | 3873.73 | 0.20 | 4886.06 | 101.80 |
PACU_VAV_MID | 21496881.82 | 0.00 | 21496881.82 | 22429071.92 | 3801.79 | 1.76 | 4956.45 | 124.00 |
PACU_VAV_TOP | 22310933.62 | 0.00 | 22310933.62 | 22614548.33 | 3598.43 | 0.21 | 5161.36 | 285.82 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.8984 | 0.0000 | 0.8984 | 0.7171 | 1158.31 | 0.15 | 4784.54 |
PACU_VAV_MID | 0.9784 | 0.0000 | 0.9784 | 0.7084 | 1108.52 | 1.65 | 4832.83 |
PACU_VAV_TOP | 0.9837 | 0.0000 | 0.9837 | 0.7171 | 1067.10 | 0.18 | 4875.72 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 35.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4859.01 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 69.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4889.59 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 43.23 | 0.00 | 0.00 | 0.00 | 0.00 | 5118.66 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.9482 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1152 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1406 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2037 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0623 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2001 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2109.88 | 15934.24 | 12-MAR-17:10 | 210606.72 | 19-JUN-14:10 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 523.02 | 385.65 | 01-JAN-00:40 | 116029.27 | 19-JUN-14:10 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:20 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:20 |
ElectricityPurchased:Facility | 2109.88 | 15934.24 | 12-MAR-17:10 | 210606.72 | 19-JUN-14:10 |
ElectricityPurchased:Plant | 2109.88 | 15934.24 | 12-MAR-17:10 | 210606.72 | 19-JUN-14:10 |
Cogeneration:ElectricityPurchased | 2109.88 | 15934.24 | 12-MAR-17:10 | 210606.72 | 19-JUN-14:10 |
General:Cogeneration:ElectricityPurchased | 2109.88 | 15934.24 | 12-MAR-17:10 | 210606.72 | 19-JUN-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2109.88 | 15934.24 | 12-MAR-17:10 | 210606.72 | 19-JUN-14:10 |
ElectricityNet:Plant | 2109.88 | 15934.24 | 12-MAR-17:10 | 210606.72 | 19-JUN-14:10 |
Cogeneration:ElectricityNet | 2109.88 | 15934.24 | 12-MAR-17:10 | 210606.72 | 19-JUN-14:10 |
General:Cogeneration:ElectricityNet | 2109.88 | 15934.24 | 12-MAR-17:10 | 210606.72 | 19-JUN-14:10 |
Fans:Electricity | 177.19 | 0.00 | 01-JAN-00:40 | 31743.94 | 14-AUG-14:20 |
General:Fans:Electricity | 177.19 | 0.00 | 01-JAN-00:40 | 31743.94 | 14-AUG-14:20 |
ExteriorLights:Electricity | 235.72 | 0.00 | 01-JAN-07:30 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 235.72 | 0.00 | 01-JAN-07:30 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 318.33 | 0.00 | 01-JAN-00:10 | 84116.79 | 19-JUN-12:00 |
General:Cooling:Electricity | 318.33 | 0.00 | 01-JAN-00:10 | 84116.79 | 19-JUN-12:00 |
Electricity:Plant | 55.61 | 0.00 | 01-JAN-00:40 | 7550.67 | 06-FEB-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 52.86 | 0.00 | 01-JAN-00:10 | 6688.63 | 06-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 52.86 | 0.00 | 01-JAN-00:10 | 6688.63 | 06-FEB-12:40 |
Pumps:Electricity | 2.75 | 0.00 | 01-JAN-00:40 | 1299.94 | 02-JAN-06:10 |
General:Pumps:Electricity | 2.75 | 0.00 | 01-JAN-00:40 | 1299.94 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 546.90 | 0.00 | 01-JAN-00:40 | 355511.19 | 02-JAN-05:10 |
NaturalGas:Plant | 546.90 | 0.00 | 01-JAN-00:40 | 355511.19 | 02-JAN-05:10 |
Heating:NaturalGas | 546.90 | 0.00 | 01-JAN-00:40 | 355511.19 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 546.90 | 0.00 | 01-JAN-00:40 | 355511.19 | 02-JAN-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3469.55 | 0.00 | 01-JAN-00:40 | 703836.06 | 02-JAN-05:10 |
EnergyTransfer:Building | 1394.52 | 0.00 | 01-JAN-00:40 | 198766.48 | 10-JUL-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 255.82 | 0.00 | 01-JAN-00:40 | 27029.67 | 14-AUG-15:20 |
Heating:EnergyTransfer | 165.54 | 0.00 | 01-JAN-00:40 | 187993.51 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.25 | 0.00 | 01-JAN-00:10 | 10506.71 | 02-JAN-05:10 |
General:Heating:EnergyTransfer | 165.54 | 0.00 | 01-JAN-00:40 | 187993.51 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.25 | 0.00 | 01-JAN-00:10 | 10506.71 | 02-JAN-05:10 |
Cooling:EnergyTransfer | 1228.98 | 0.00 | 01-JAN-00:40 | 198766.48 | 10-JUL-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 255.57 | 0.00 | 01-JAN-00:40 | 27029.67 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer | 1228.98 | 0.00 | 01-JAN-00:40 | 198766.48 | 10-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 255.57 | 0.00 | 01-JAN-00:40 | 27029.67 | 14-AUG-15:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 91.04 | 0.00 | 01-JAN-00:40 | 20850.22 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.68 | 0.00 | 01-JAN-00:40 | 20850.22 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.68 | 0.00 | 01-JAN-00:40 | 20850.22 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 55.37 | 0.00 | 01-JAN-00:10 | 19680.40 | 19-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 55.37 | 0.00 | 01-JAN-00:10 | 19680.40 | 19-JUN-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.61 | 0.00 | 01-JAN-00:40 | 12207.25 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.02 | 0.00 | 01-JAN-00:40 | 12207.25 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.02 | 0.00 | 01-JAN-00:40 | 12207.25 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 24.59 | 0.00 | 01-JAN-00:10 | 6424.62 | 10-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 24.59 | 0.00 | 01-JAN-00:10 | 6424.62 | 10-JUL-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 36.50 | 0.00 | 01-JAN-00:40 | 10416.76 | 02-JAN-08:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.50 | 0.00 | 01-JAN-00:40 | 10416.76 | 02-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.50 | 0.00 | 01-JAN-00:40 | 10416.76 | 02-JAN-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 31.00 | 0.00 | 01-JAN-00:10 | 6478.73 | 14-AUG-14:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 31.00 | 0.00 | 01-JAN-00:10 | 6478.73 | 14-AUG-14:20 |
EnergyTransfer:Zone:CORE_MID | 169.90 | 0.00 | 01-JAN-00:40 | 21350.04 | 14-AUG-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.23 | 0.00 | 01-JAN-00:40 | 17831.84 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.23 | 0.00 | 01-JAN-00:40 | 17831.84 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 168.67 | 0.00 | 01-JAN-00:20 | 21350.04 | 14-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 168.67 | 0.00 | 01-JAN-00:20 | 21350.04 | 14-AUG-14:00 |
EnergyTransfer:Zone:CORE_TOP | 173.85 | 0.00 | 01-JAN-00:40 | 25529.60 | 10-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 8.27 | 0.00 | 01-JAN-00:40 | 25509.73 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 8.27 | 0.00 | 01-JAN-00:40 | 25509.73 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 165.58 | 0.00 | 01-JAN-00:20 | 25529.60 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 165.58 | 0.00 | 01-JAN-00:20 | 25529.60 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 61.92 | 0.00 | 01-JAN-00:40 | 11810.76 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 16.70 | 0.00 | 01-JAN-00:40 | 11810.76 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 16.70 | 0.00 | 01-JAN-00:40 | 11810.76 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.22 | 0.00 | 01-JAN-00:10 | 9294.23 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.22 | 0.00 | 01-JAN-00:10 | 9294.23 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.26 | 0.00 | 01-JAN-00:40 | 9894.31 | 02-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.04 | 0.00 | 01-JAN-00:40 | 7712.79 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.04 | 0.00 | 01-JAN-00:40 | 7712.79 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.22 | 0.00 | 01-JAN-00:10 | 9894.31 | 02-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.22 | 0.00 | 01-JAN-00:10 | 9894.31 | 02-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 75.90 | 0.00 | 01-JAN-00:40 | 14498.24 | 01-SEP-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 11.63 | 0.00 | 01-JAN-00:40 | 11568.12 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 11.63 | 0.00 | 01-JAN-00:40 | 11568.12 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 64.27 | 0.00 | 01-JAN-00:10 | 14498.24 | 01-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 64.27 | 0.00 | 01-JAN-00:10 | 14498.24 | 01-SEP-12:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.79 | 0.00 | 01-JAN-00:40 | 10767.55 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 10.19 | 0.00 | 01-JAN-00:40 | 8044.80 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 10.19 | 0.00 | 01-JAN-00:40 | 8044.80 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 39.60 | 0.00 | 01-JAN-00:10 | 10767.55 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 39.60 | 0.00 | 01-JAN-00:10 | 10767.55 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 45.63 | 0.00 | 01-JAN-00:40 | 9529.16 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 8.51 | 0.00 | 01-JAN-00:40 | 9529.16 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 8.51 | 0.00 | 01-JAN-00:40 | 9529.16 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.11 | 0.00 | 01-JAN-00:10 | 6924.64 | 17-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.11 | 0.00 | 01-JAN-00:10 | 6924.64 | 17-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 38.32 | 0.00 | 01-JAN-00:40 | 8002.97 | 02-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 4.02 | 0.00 | 01-JAN-00:40 | 6310.77 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 4.02 | 0.00 | 01-JAN-00:40 | 6310.77 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.30 | 0.00 | 01-JAN-00:10 | 8002.97 | 02-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.30 | 0.00 | 01-JAN-00:10 | 8002.97 | 02-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 68.21 | 0.00 | 01-JAN-00:40 | 15558.11 | 19-JUN-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 16.98 | 0.00 | 01-JAN-00:40 | 13819.75 | 02-JAN-07:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 16.98 | 0.00 | 01-JAN-00:40 | 13819.75 | 02-JAN-07:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 51.23 | 0.00 | 01-JAN-00:10 | 15558.11 | 19-JUN-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 51.23 | 0.00 | 01-JAN-00:10 | 15558.11 | 19-JUN-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 38.82 | 0.00 | 01-JAN-00:40 | 8474.10 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 4.59 | 0.00 | 01-JAN-00:40 | 6540.87 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 4.59 | 0.00 | 01-JAN-00:40 | 6540.87 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 34.23 | 0.00 | 01-JAN-00:10 | 8474.10 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 34.23 | 0.00 | 01-JAN-00:10 | 8474.10 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 51.43 | 0.00 | 01-JAN-00:40 | 9928.58 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 7.97 | 0.00 | 01-JAN-00:40 | 9928.58 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 7.97 | 0.00 | 01-JAN-00:40 | 9928.58 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.46 | 0.00 | 01-JAN-00:10 | 8216.20 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.46 | 0.00 | 01-JAN-00:10 | 8216.20 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 41.25 | 0.00 | 01-JAN-00:40 | 9816.17 | 02-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 4.19 | 0.00 | 01-JAN-00:40 | 6836.97 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 4.19 | 0.00 | 01-JAN-00:40 | 6836.97 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.07 | 0.00 | 01-JAN-00:10 | 9816.17 | 02-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.07 | 0.00 | 01-JAN-00:10 | 9816.17 | 02-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 68.38 | 0.00 | 01-JAN-00:40 | 14121.21 | 28-SEP-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 4.92 | 0.00 | 01-JAN-00:40 | 9734.32 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 4.92 | 0.00 | 01-JAN-00:40 | 9734.32 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.47 | 0.00 | 01-JAN-00:10 | 14121.21 | 28-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.47 | 0.00 | 01-JAN-00:10 | 14121.21 | 28-SEP-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 44.89 | 0.00 | 01-JAN-00:40 | 10272.69 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 4.86 | 0.00 | 01-JAN-00:40 | 6991.64 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 4.86 | 0.00 | 01-JAN-00:40 | 6991.64 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 40.03 | 0.00 | 01-JAN-00:10 | 10272.69 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 40.03 | 0.00 | 01-JAN-00:10 | 10272.69 | 15-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 402.40 | 0.00 | 01-JAN-00:40 | 253673.14 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
EnergyTransfer:HVAC | 1675.41 | 0.00 | 01-JAN-00:40 | 320553.59 | 04-AUG-14:10 |
HeatingCoils:EnergyTransfer | 352.34 | 0.00 | 01-JAN-00:40 | 252899.98 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 352.34 | 0.00 | 01-JAN-00:40 | 252899.98 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 352.34 | 0.00 | 01-JAN-00:40 | 252899.98 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 1323.07 | 0.00 | 01-JAN-00:10 | 320538.07 | 04-AUG-14:10 |
EnergyTransfer:Plant | 399.62 | 0.00 | 01-JAN-00:40 | 263418.88 | 02-JAN-05:10 |
WaterSystems:EnergyTransfer | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
Boilers:EnergyTransfer | 349.56 | 0.00 | 01-JAN-00:40 | 263418.88 | 02-JAN-05:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.249 | -255.566 | 0.000 | 0.000 | 33.100 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -149.569 |
CORE_MID | 0.000 | 0.000 | 1.226 | -168.674 | 0.000 | 0.000 | 34.276 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -94.039 |
CORE_TOP | 0.000 | 0.000 | 8.269 | -165.579 | 0.000 | 0.000 | 35.273 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -105.175 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 16.703 | -45.219 | 0.000 | 0.000 | 7.719 | 23.566 | 24.333 | 18.102 | 0.000 | 0.178 | 1.222 | 0.000 | -37.936 | 0.000 | -8.668 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 9.040 | -38.224 | 0.000 | 0.000 | 4.809 | 14.919 | 15.404 | 32.758 | 0.000 | 0.104 | 0.000 | 0.000 | -23.631 | 0.000 | -5.878 | -9.300 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 11.629 | -64.272 | 0.000 | 0.000 | 7.508 | 23.566 | 24.332 | 66.769 | 0.000 | 0.155 | 0.000 | 0.000 | -35.072 | 0.000 | -9.067 | -25.548 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 10.188 | -39.596 | 0.000 | 0.000 | 4.870 | 14.918 | 15.403 | 33.563 | 0.000 | 0.110 | 0.000 | 0.000 | -24.507 | 0.000 | -5.908 | -9.040 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 8.512 | -37.113 | 0.000 | 0.000 | 7.658 | 23.566 | 24.333 | 18.495 | 0.000 | 0.096 | 0.001 | 0.000 | -39.865 | 0.000 | -4.945 | -0.736 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 4.023 | -34.301 | 0.000 | 0.000 | 4.775 | 14.919 | 15.404 | 33.042 | 0.000 | 0.056 | 0.001 | 0.000 | -25.255 | 0.000 | -3.390 | -9.271 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 16.981 | -51.230 | 0.000 | 0.000 | 7.575 | 23.566 | 24.332 | 67.704 | 0.000 | 2.093 | 0.000 | 0.000 | -37.882 | 0.000 | -34.110 | -19.029 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 4.594 | -34.226 | 0.000 | 0.000 | 4.816 | 14.918 | 15.403 | 33.934 | 0.000 | 0.056 | 0.000 | 0.000 | -26.245 | 0.000 | -3.410 | -9.839 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 7.969 | -43.457 | 0.000 | 0.000 | 7.605 | 23.566 | 24.333 | 17.758 | 0.000 | 0.141 | 10.496 | 0.000 | -40.691 | 0.000 | -7.719 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 4.186 | -37.065 | 0.000 | 0.000 | 3.515 | 14.919 | 15.404 | 32.404 | 0.000 | 0.087 | 0.003 | 0.000 | -25.286 | 0.000 | -5.229 | -2.933 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 4.915 | -63.468 | 0.000 | 0.000 | 7.363 | 23.566 | 24.332 | 66.284 | 0.000 | 0.123 | 0.000 | 0.000 | -37.787 | 0.000 | -8.109 | -17.218 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 4.858 | -40.031 | 0.000 | 0.000 | 4.820 | 14.918 | 15.403 | 33.433 | 0.000 | 0.090 | 0.001 | 0.000 | -26.251 | 0.000 | -5.240 | -2.001 |
TOPFLOOR_PLENUM | 35.679 | -55.366 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.128 | 32.575 | 0.000 | 0.000 | 0.000 | -13.016 | -0.000 |
MIDFLOOR_PLENUM | 11.022 | -24.587 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.168 | 27.060 | 0.000 | 0.000 | 0.000 | -13.663 | -0.001 |
FIRSTFLOOR_PLENUM | 5.501 | -30.996 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.128 | 36.671 | 0.000 | 0.000 | 0.000 | -11.305 | -0.000 |
Total Facility | 52.202 | -110.948 | 113.342 | -1118.022 | 0.000 | 0.000 | 175.681 | 566.263 | 729.266 | 454.246 | 0.000 | 3.711 | 108.031 | 0.000 | -380.410 | 0.000 | -139.657 | -453.701 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 18-JUL-04:02 | 0.00 | 0.00 | 0.00 | -53312.29 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 46261.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 10-JUL-04:03 | 0.00 | 0.00 | 0.00 | -42753.05 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 39226.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 20-JUL-05:02 | 0.00 | 0.00 | 0.00 | -46692.48 | 0.00 | 0.00 | 318.23 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 42263.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 10-JUL-04:01 | 0.00 | 0.00 | 0.00 | -15596.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 14.76 | 14998.30 | 0.00 | -160.48 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-08:42 | 0.00 | 0.00 | 0.00 | -13585.65 | 0.00 | 0.00 | 13.87 | 72.37 | 302.86 | 10742.46 | 0.00 | 0.00 | 2488.28 | 0.00 | -0.00 | 0.00 | -34.19 | 0.00 |
PERIMETER_TOP_ZN_1 | 30-JUL-12:52 | 0.00 | 0.00 | 0.00 | -22454.71 | 0.00 | 0.00 | 25.31 | 114.31 | 478.41 | 8932.06 | 0.00 | 15.37 | 12889.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-16:02 | 0.00 | 0.00 | 0.00 | -18404.72 | 0.00 | 0.00 | 15.44 | 72.36 | 302.86 | 8202.27 | 0.00 | 0.00 | 9864.79 | 0.00 | -0.00 | 0.00 | -53.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-AUG-13:40 | 0.00 | 0.00 | 0.00 | -6924.48 | 0.00 | 0.00 | 757.18 | 2057.62 | 1435.25 | 4886.04 | 0.00 | 46.62 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2258.22 |
PERIMETER_BOT_ZN_2 | 09-JUL-09:32 | 0.00 | 0.00 | 0.00 | -9322.13 | 0.00 | 0.00 | 15.63 | 72.37 | 302.86 | 8728.63 | 0.00 | 28.54 | 174.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-13:52 | 0.00 | 0.00 | 0.00 | -18037.12 | 0.00 | 0.00 | 25.92 | 114.31 | 478.41 | 11010.29 | 0.00 | 0.00 | 6482.23 | 0.00 | -0.00 | 0.00 | -74.05 | 0.00 |
PERIMETER_BOT_ZN_4 | 10-SEP-17:12 | 0.00 | 0.00 | 0.00 | -13988.27 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 7182.91 | 0.00 | 0.00 | 6585.58 | 0.00 | -0.00 | 0.00 | -97.00 | 0.00 |
PERIMETER_MID_ZN_3 | 10-JUL-04:01 | 0.00 | 0.00 | 0.00 | -11099.05 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 10523.51 | 0.00 | -166.28 | 0.00 | -1.60 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-08:31 | 0.00 | 0.00 | 0.00 | -17517.72 | 0.00 | 0.00 | 13.70 | 72.37 | 302.86 | 11035.21 | 0.00 | 0.00 | 6144.77 | 0.00 | -0.00 | 0.00 | -51.17 | 0.00 |
PERIMETER_MID_ZN_1 | 09-JUL-13:22 | 0.00 | 0.00 | 0.00 | -19449.22 | 0.00 | 0.00 | 25.45 | 114.31 | 478.41 | 7951.16 | 0.00 | 158.46 | 10721.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-16:11 | 0.00 | 0.00 | 0.00 | -17950.57 | 0.00 | 0.00 | 13.82 | 72.36 | 302.86 | 9548.15 | 0.00 | 0.00 | 8079.41 | 0.00 | -0.00 | 0.00 | -66.04 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:30 | 0.00 | -19680.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.66 | 19545.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-JUL-14:20 | 0.00 | -6424.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.89 | 6259.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 14-AUG-14:05 | 0.00 | -6497.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.32 | 6436.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-04:01 | 0.00 | 10454.53 | 0.00 | -225822.68 | 0.00 | 0.00 | 0.00 | 5493.69 | 15894.33 | 0.00 | 0.00 | 106.66 | 195337.38 | 0.00 | -1407.44 | 0.00 | -56.47 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:02 | 0.00 | 0.00 | 12331.16 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19381.73 |
CORE_MID | 02-JAN-05:02 | 0.00 | 0.00 | 19205.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22732.34 |
CORE_TOP | 17-JAN-05:01 | 0.00 | 0.00 | 30611.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34138.06 |
PERIMETER_TOP_ZN_3 | 09-JAN-05:41 | 0.00 | 0.00 | 14718.42 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2038.33 | 0.00 | -209.06 | -13214.46 |
PERIMETER_TOP_ZN_2 | 09-JAN-05:41 | 0.00 | 0.00 | 9698.12 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1356.24 | 0.00 | -139.21 | -8673.30 |
PERIMETER_TOP_ZN_1 | 09-JAN-05:41 | 0.00 | 0.00 | 14548.99 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2098.25 | 0.00 | -208.91 | -12985.26 |
PERIMETER_TOP_ZN_4 | 09-JAN-05:41 | 0.00 | 0.00 | 10317.96 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1393.58 | 0.00 | -139.53 | -9255.47 |
PERIMETER_BOT_ZN_3 | 01-JAN-08:42 | 0.00 | 0.00 | 11129.39 | 0.00 | 0.00 | 0.00 | 58.99 | 114.31 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1631.84 | 0.00 | -874.82 | -9274.44 |
PERIMETER_BOT_ZN_2 | 01-JAN-16:03 | 0.00 | 0.00 | 7540.18 | 0.00 | 0.00 | 0.00 | 36.96 | 72.37 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1790.26 | 0.00 | -534.42 | -5627.69 |
PERIMETER_BOT_ZN_1 | 02-JAN-07:40 | 0.00 | 0.00 | 13832.38 | 0.00 | 0.00 | 0.00 | 251.82 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 6769.35 | 0.00 | -1557.82 | 0.00 | -20619.49 | 0.00 |
PERIMETER_BOT_ZN_4 | 01-JAN-08:42 | 0.00 | 0.00 | 7966.51 | 0.00 | 0.00 | 0.00 | 37.40 | 72.36 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1169.05 | 0.00 | -584.91 | -6625.16 |
PERIMETER_MID_ZN_3 | 01-JAN-08:42 | 0.00 | 0.00 | 11612.82 | 0.00 | 0.00 | 0.00 | 59.31 | 114.31 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1653.97 | 0.00 | -1354.02 | -9256.86 |
PERIMETER_MID_ZN_2 | 17-JAN-05:01 | 0.00 | 0.00 | 8529.99 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1570.14 | 0.00 | -193.45 | -7237.04 |
PERIMETER_MID_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 11222.06 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2485.04 | 0.00 | -294.10 | -9186.34 |
PERIMETER_MID_ZN_4 | 01-JAN-08:42 | 0.00 | 0.00 | 8740.98 | 0.00 | 0.00 | 0.00 | 37.63 | 72.36 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1187.88 | 0.00 | -906.32 | -7059.62 |
TOPFLOOR_PLENUM | 06-FEB-05:09 | 22087.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3348.98 | -18738.99 |
MIDFLOOR_PLENUM | 02-JAN-08:14 | 12486.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -334.55 | -12151.47 |
FIRSTFLOOR_PLENUM | 02-JAN-08:23 | 10626.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -263.96 | -10362.32 |
Total Facility | 02-JAN-05:33 | 39304.33 | 0.00 | 156073.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5493.69 | 15894.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43764.71 | 0.00 | -11490.82 | -161510.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 7.0025 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9229 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.8318 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6301 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 8.0369 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.9190 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.5012 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.1007 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.4159 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0496 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.0185 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.4111 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2991 | 3.2991 | 0.9897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7098 | 2.7098 | 0.8129 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1721 | 3.1721 | 0.9516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4321 | 1.4321 | 0.4296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9557 | 0.9557 | 0.2867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4148 | 1.4148 | 0.4244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0623 | 1.0623 | 0.3187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0597 | 1.0597 | 0.3179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7865 | 0.7865 | 0.2360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0429 | 1.0429 | 0.3129 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8142 | 0.8142 | 0.2442 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1264 | 1.1264 | 0.3379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9268 | 0.9268 | 0.2780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1091 | 1.1091 | 0.3327 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9597 | 0.9597 | 0.2879 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 7.0025 | 5.9229 | 7.0025 | 2.1007 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.8318 | 5.6301 | 6.8318 | 2.0496 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 8.0369 | 6.9190 | 8.0369 | 2.4111 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6496 | 1.6496 | 0.9897 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3549 | 1.3549 | 0.8129 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5860 | 1.5860 | 0.9516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7161 | 0.7161 | 0.4296 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4778 | 0.4778 | 0.2867 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7074 | 0.7074 | 0.4244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5311 | 0.5311 | 0.3187 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5299 | 0.5299 | 0.3179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3933 | 0.3933 | 0.2360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5215 | 0.5215 | 0.3129 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4071 | 0.4071 | 0.2442 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5632 | 0.5632 | 0.3379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4634 | 0.4634 | 0.2780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5546 | 0.5546 | 0.3327 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4799 | 0.4799 | 0.2879 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.5012 | 2.1007 | 2.1007 | 2.1007 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.4159 | 2.0496 | 2.0496 | 2.0496 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.0185 | 2.4111 | 2.4111 | 2.4111 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 305.67 |
Number of hours cooling loads not met | 55.67 |
Number of hours not met | 361.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 546.90 | 355511.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 318.33 | 84116.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 235.72 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 177.19 | 31743.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 2.75 | 1299.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 52.86 | 6688.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 2109.88 |
Natural Gas | 0.00 | 546.90 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2656.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 63.89 |
Fans (All) | 35.56 |
Service Water Heating | 10.61 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 423.48 |
Subtotal | 423.48 |
Natural Gas [MJ/m2] | |
Space Heating | 109.77 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 109.77 |
Subtotal | 109.77 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 21.31 |
Space Heating | 20.59 |
Space Cooling | 11.98 |
Fans (All) | 6.67 |
Service Water Heating | 1.99 |
Receptacle Equipment | 27.45 |
Miscellaneous | 10.01 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8097.33 | 662.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8730.33 | 29.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8720.83 | 39.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8677.67 | 82.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8687.17 | 72.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8652.83 | 107.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8711.33 | 48.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8699.83 | 60.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8663.83 | 96.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8711.33 | 48.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8670.67 | 89.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8656.17 | 103.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8604.67 | 155.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8594.83 | 165.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8097.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 662.67 | 0.00 | 0.00 | 0.00 |
Average | 8661.35 | 98.65 | 0.00 | 0.00 | 0.00 |
Sum | 155904.33 | 1775.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128087.33 | 216.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.00 | 7.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128293.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.00 | 216.67 | 0.00 | 0.00 | 0.00 |
Average | 34130.30 | 13.04 | 0.00 | 0.00 | 0.00 |
Sum | 614345.33 | 234.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7855.00 | 905.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8179.00 | 581.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8403.67 | 356.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8128.67 | 631.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8054.33 | 705.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8064.00 | 696.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8043.83 | 716.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8133.67 | 626.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8046.50 | 713.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7839.67 | 920.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7969.67 | 790.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8017.50 | 742.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7986.83 | 773.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7949.83 | 810.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7956.00 | 804.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7524.00 | 1236.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7975.83 | 784.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7930.17 | 829.83 | 0.00 | 0.00 | 0.00 |
Min | 7524.00 | 356.33 | 0.00 | 0.00 | 0.00 |
Max | 8403.67 | 1236.00 | 0.00 | 0.00 | 0.00 |
Average | 8003.23 | 756.77 | 0.00 | 0.00 | 0.00 |
Sum | 144058.17 | 13621.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127866.67 | 437.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128056.67 | 247.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128157.83 | 146.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24898.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24898.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24901.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24106.17 | 802.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24889.67 | 19.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24888.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128157.83 | 802.83 | 0.00 | 0.00 | 0.00 |
Average | 34048.71 | 94.62 | 0.00 | 0.00 | 0.00 |
Sum | 612876.83 | 1703.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120833E+11 | 14005.51 | 27-JAN-16:30 | 5.00 | 2.53 | 0.180193E+10 | 2606.64 | 27-JAN-10:20 | 5.00 | 2.53 |
February | 0.122531E+11 | 14547.33 | 24-FEB-17:00 | 6.70 | 1.42 | 0.169061E+10 | 2606.65 | 03-FEB-10:30 | 6.70 | 1.42 |
March | 0.163973E+11 | 18406.74 | 29-MAR-16:00 | 7.20 | 4.88 | 0.212533E+10 | 2607.08 | 17-MAR-13:39 | 7.20 | 4.88 |
April | 0.178783E+11 | 25182.25 | 10-APR-06:03 | 15.78 | 13.94 | 0.190479E+10 | 2606.66 | 27-APR-09:20 | 15.77 | 12.54 |
May | 0.232857E+11 | 48229.25 | 30-MAY-05:12 | 18.53 | 14.51 | 0.207583E+10 | 2606.66 | 17-MAY-09:20 | 18.53 | 14.51 |
June | 0.288456E+11 | 48815.66 | 19-JUN-05:02 | 24.08 | 22.05 | 0.207351E+10 | 2606.70 | 05-JUN-09:09 | 24.08 | 22.05 |
July | 0.301329E+11 | 53324.56 | 18-JUL-04:02 | 24.40 | 22.88 | 0.192701E+10 | 2606.68 | 10-JUL-13:20 | 24.40 | 22.88 |
August | 0.327739E+11 | 53092.23 | 18-AUG-04:02 | 25.00 | 19.10 | 0.216275E+10 | 2606.66 | 08-AUG-09:20 | 25.00 | 19.10 |
September | 0.272536E+11 | 51776.14 | 01-SEP-05:03 | 24.08 | 21.83 | 0.192030E+10 | 2606.69 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.244480E+11 | 40151.79 | 05-OCT-06:03 | 15.68 | 14.98 | 0.199475E+10 | 2606.70 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.164037E+11 | 21560.38 | 03-NOV-16:00 | 15.00 | 10.26 | 0.194853E+10 | 2606.66 | 03-NOV-13:20 | 15.00 | 10.26 |
December | 0.138106E+11 | 16312.14 | 21-DEC-16:10 | 2.62 | -2.3 | 0.186869E+10 | 2606.65 | 15-DEC-10:20 | 2.62 | -2.3 |
Annual Sum or Average | 0.255566E+12 | 0.234940E+11 | ||||||||
Minimum of Months | 0.120833E+11 | 14005.51 | 2.62 | -2.3 | 0.169061E+10 | 2606.64 | 2.62 | -2.3 | ||
Maximum of Months | 0.327739E+11 | 53324.56 | 25.00 | 22.88 | 0.216275E+10 | 2607.08 | 25.00 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42135152.70 | 1715.18 | 17-JAN-14:00 | 11.10 | 5.15 | 0.00 | 0.00 | 01-JAN-00:10 | 11.10 | 5.15 |
February | 0.172432E+09 | 2664.68 | 17-FEB-13:00 | 6.70 | 1.56 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 1.56 |
March | 0.153747E+10 | 5986.51 | 03-MAR-13:00 | 14.40 | 8.04 | 0.00 | 0.00 | 01-MAR-00:10 | 14.40 | 8.04 |
April | 0.303771E+10 | 11854.42 | 07-APR-13:05 | 26.60 | 16.32 | 0.00 | 0.00 | 01-APR-00:10 | 26.60 | 16.32 |
May | 0.626220E+10 | 17210.81 | 30-MAY-13:05 | 29.90 | 17.82 | 0.00 | 0.00 | 01-MAY-00:10 | 29.90 | 17.82 |
June | 0.969171E+10 | 19680.40 | 19-JUN-13:30 | 34.70 | 23.81 | 0.00 | 0.00 | 01-JUN-00:10 | 34.70 | 23.81 |
July | 0.116398E+11 | 18264.49 | 07-JUL-13:05 | 32.80 | 23.37 | 0.00 | 0.00 | 01-JUL-00:10 | 32.80 | 23.37 |
August | 0.122508E+11 | 17843.36 | 18-AUG-13:05 | 33.30 | 20.35 | 0.00 | 0.00 | 01-AUG-00:10 | 33.30 | 20.35 |
September | 0.643653E+10 | 15754.76 | 01-SEP-13:30 | 30.85 | 17.87 | 0.00 | 0.00 | 01-SEP-00:10 | 30.85 | 17.87 |
October | 0.364897E+10 | 10888.97 | 04-OCT-13:40 | 24.60 | 18.82 | 0.00 | 0.00 | 01-OCT-00:10 | 24.60 | 18.82 |
November | 0.617726E+09 | 4840.36 | 04-NOV-13:00 | 17.80 | 12.74 | 0.00 | 0.00 | 01-NOV-00:10 | 17.80 | 12.74 |
December | 28307286.54 | 1236.20 | 20-DEC-12:10 | 8.98 | 5.23 | 0.00 | 0.00 | 01-DEC-00:10 | 8.98 | 5.23 |
Annual Sum or Average | 0.553658E+11 | 0.00 | ||||||||
Minimum of Months | 28307286.54 | 1236.20 | 6.70 | 1.56 | 0.00 | 0.00 | 6.70 | 1.56 | ||
Maximum of Months | 0.122508E+11 | 19680.40 | 34.70 | 23.81 | 0.00 | 0.00 | 34.70 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47810854.68 | 4661.46 | 05-JAN-05:01 | -7.8 | -9.6 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -9.6 |
February | 83503543.91 | 4555.07 | 09-FEB-05:01 | -8.3 | -9.9 | 0.00 | 0.00 | 01-FEB-00:10 | -8.3 | -9.9 |
March | 0.378054E+09 | 3847.26 | 08-MAR-06:11 | 1.83 | 1.83 | 0.00 | 0.00 | 01-MAR-00:10 | 1.83 | 1.83 |
April | 0.105149E+10 | 3825.44 | 21-APR-05:11 | 5.60 | 5.31 | 0.00 | 0.00 | 01-APR-00:10 | 5.60 | 5.31 |
May | 0.225356E+10 | 5071.02 | 30-MAY-15:50 | 28.30 | 17.54 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 17.54 |
June | 0.422426E+10 | 5777.85 | 19-JUN-14:30 | 33.85 | 23.48 | 0.00 | 0.00 | 01-JUN-00:10 | 33.85 | 23.48 |
July | 0.526032E+10 | 6424.62 | 10-JUL-14:20 | 32.97 | 20.94 | 0.00 | 0.00 | 01-JUL-00:10 | 32.97 | 20.94 |
August | 0.572071E+10 | 6341.56 | 14-AUG-14:20 | 29.43 | 23.03 | 0.00 | 0.00 | 01-AUG-00:10 | 29.43 | 23.03 |
September | 0.335423E+10 | 5566.13 | 01-SEP-14:50 | 30.68 | 17.45 | 0.00 | 0.00 | 01-SEP-00:10 | 30.68 | 17.45 |
October | 0.180331E+10 | 3359.73 | 04-OCT-15:30 | 23.35 | 19.12 | 0.00 | 0.00 | 01-OCT-00:10 | 23.35 | 19.12 |
November | 0.360953E+09 | 3428.84 | 18-NOV-06:11 | 2.80 | 1.71 | 0.00 | 0.00 | 01-NOV-00:10 | 2.80 | 1.71 |
December | 49513848.02 | 3550.71 | 23-DEC-06:11 | 2.93 | 2.42 | 0.00 | 0.00 | 01-DEC-00:10 | 2.93 | 2.42 |
Annual Sum or Average | 0.245877E+11 | 0.00 | ||||||||
Minimum of Months | 47810854.68 | 3359.73 | -8.3 | -9.9 | 0.00 | 0.00 | -8.3 | -9.9 | ||
Maximum of Months | 0.572071E+10 | 6424.62 | 33.85 | 23.48 | 0.00 | 0.00 | 33.85 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111946E+09 | 3509.14 | 28-JAN-06:11 | 3.30 | 2.32 | 0.00 | 0.00 | 01-JAN-00:10 | 3.30 | 2.32 |
February | 0.162667E+09 | 4404.84 | 24-FEB-06:11 | 4.80 | 4.55 | 0.00 | 0.00 | 01-FEB-00:10 | 4.80 | 4.55 |
March | 0.756446E+09 | 4860.86 | 31-MAR-05:11 | 5.20 | 5.20 | 0.00 | 0.00 | 01-MAR-00:10 | 5.20 | 5.20 |
April | 0.164866E+10 | 4904.27 | 19-APR-05:11 | 3.50 | 1.23 | 0.00 | 0.00 | 01-APR-00:10 | 3.50 | 1.23 |
May | 0.305694E+10 | 5167.87 | 30-MAY-15:50 | 28.30 | 17.54 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 17.54 |
June | 0.480588E+10 | 5970.16 | 19-JUN-12:07 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.575685E+10 | 6396.30 | 10-JUL-15:00 | 33.30 | 21.03 | 0.00 | 0.00 | 01-JUL-00:10 | 33.30 | 21.03 |
August | 0.652225E+10 | 6497.19 | 14-AUG-14:05 | 29.72 | 22.98 | 0.00 | 0.00 | 01-AUG-00:10 | 29.72 | 22.98 |
September | 0.428097E+10 | 6085.17 | 05-SEP-15:10 | 26.02 | 21.55 | 0.00 | 0.00 | 01-SEP-00:10 | 26.02 | 21.55 |
October | 0.288502E+10 | 4557.96 | 04-OCT-15:30 | 23.35 | 19.12 | 0.00 | 0.00 | 01-OCT-00:10 | 23.35 | 19.12 |
November | 0.800802E+09 | 3072.79 | 16-NOV-06:11 | 3.90 | 2.28 | 0.00 | 0.00 | 01-NOV-00:10 | 3.90 | 2.28 |
December | 0.207585E+09 | 3601.98 | 23-DEC-06:11 | 2.93 | 2.42 | 0.00 | 0.00 | 01-DEC-00:10 | 2.93 | 2.42 |
Annual Sum or Average | 0.309960E+11 | 0.00 | ||||||||
Minimum of Months | 0.111946E+09 | 3072.79 | 2.93 | 1.23 | 0.00 | 0.00 | 2.93 | 1.23 | ||
Maximum of Months | 0.652225E+10 | 6497.19 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.725617E+10 | 7879.20 | 20-JAN-17:00 | 5.60 | 3.19 | 0.160491E+10 | 2429.90 | 20-JAN-16:00 | 5.60 | 3.19 |
February | 0.749830E+10 | 7896.64 | 24-FEB-17:00 | 6.70 | 1.42 | 0.147931E+10 | 2447.54 | 24-FEB-14:00 | 6.70 | 1.42 |
March | 0.102927E+11 | 11005.32 | 29-MAR-16:00 | 7.20 | 4.88 | 0.193802E+10 | 2606.65 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.113764E+11 | 15903.22 | 10-APR-16:00 | 20.00 | 11.13 | 0.182073E+10 | 2606.66 | 27-APR-09:20 | 15.77 | 12.54 |
May | 0.157658E+11 | 25097.41 | 31-MAY-05:12 | 16.67 | 15.21 | 0.204505E+10 | 2606.66 | 17-MAY-09:20 | 16.67 | 15.21 |
June | 0.204945E+11 | 39464.45 | 20-JUN-05:12 | 20.97 | 18.26 | 0.206664E+10 | 2606.69 | 05-JUN-09:09 | 20.97 | 18.26 |
July | 0.219312E+11 | 42760.59 | 10-JUL-04:03 | 26.10 | 21.38 | 0.192209E+10 | 2606.64 | 11-JUL-09:20 | 24.27 | 16.60 |
August | 0.235223E+11 | 41587.05 | 04-AUG-04:02 | 23.90 | 23.16 | 0.215886E+10 | 2606.66 | 08-AUG-09:20 | 23.87 | 16.88 |
September | 0.180229E+11 | 39527.01 | 05-SEP-05:12 | 20.60 | 18.00 | 0.190826E+10 | 2606.69 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.147212E+11 | 18031.57 | 05-OCT-16:00 | 21.70 | 19.15 | 0.196389E+10 | 2606.69 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.935918E+10 | 13155.33 | 03-NOV-16:00 | 15.00 | 10.26 | 0.178107E+10 | 2606.66 | 03-NOV-13:20 | 15.00 | 10.26 |
December | 0.843339E+10 | 8055.99 | 21-DEC-16:20 | 2.43 | -2.4 | 0.162953E+10 | 2508.01 | 21-DEC-14:00 | 2.43 | -2.4 |
Annual Sum or Average | 0.168674E+12 | 0.223183E+11 | ||||||||
Minimum of Months | 0.725617E+10 | 7879.20 | 2.43 | -2.4 | 0.147931E+10 | 2429.90 | 2.43 | -2.4 | ||
Maximum of Months | 0.235223E+11 | 42760.59 | 26.10 | 23.16 | 0.215886E+10 | 2606.69 | 24.27 | 18.26 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573882E+10 | 8540.65 | 05-JAN-00:13 | -6.1 | -8.5 | 0.149886E+10 | 2247.75 | 19-JAN-14:00 | 8.90 | 3.60 |
February | 0.592699E+10 | 9289.94 | 09-FEB-00:13 | -7.8 | -9.9 | 0.137623E+10 | 2301.20 | 17-FEB-14:00 | 6.10 | 1.74 |
March | 0.950397E+10 | 10510.83 | 29-MAR-16:00 | 7.20 | 4.88 | 0.178270E+10 | 2597.21 | 03-MAR-14:00 | 7.20 | 4.88 |
April | 0.112008E+11 | 17720.79 | 07-APR-15:50 | 25.60 | 16.10 | 0.171407E+10 | 2606.66 | 06-APR-13:20 | 25.60 | 16.10 |
May | 0.165049E+11 | 23357.38 | 30-MAY-14:00 | 29.40 | 16.93 | 0.199053E+10 | 2606.71 | 31-MAY-09:09 | 25.10 | 19.47 |
June | 0.219246E+11 | 46524.97 | 19-JUN-05:02 | 24.08 | 22.05 | 0.205670E+10 | 2606.69 | 28-JUN-09:39 | 23.90 | 20.98 |
July | 0.239825E+11 | 46701.25 | 20-JUL-05:02 | 23.98 | 23.45 | 0.191884E+10 | 2606.66 | 05-JUL-09:20 | 23.98 | 23.45 |
August | 0.252105E+11 | 46682.79 | 01-AUG-05:02 | 23.90 | 20.76 | 0.215258E+10 | 2606.71 | 29-AUG-09:39 | 25.17 | 18.68 |
September | 0.178623E+11 | 46403.66 | 01-SEP-05:02 | 24.08 | 21.83 | 0.187727E+10 | 2606.69 | 05-SEP-09:09 | 23.98 | 19.44 |
October | 0.135991E+11 | 18646.01 | 04-OCT-15:50 | 22.98 | 19.12 | 0.186986E+10 | 2606.66 | 02-OCT-13:20 | 22.98 | 19.12 |
November | 0.809730E+10 | 10948.43 | 03-NOV-16:00 | 15.00 | 10.26 | 0.161085E+10 | 2584.95 | 03-NOV-13:00 | 15.00 | 10.26 |
December | 0.602693E+10 | 8142.91 | 21-DEC-16:00 | 2.80 | -2.2 | 0.147247E+10 | 2263.37 | 21-DEC-14:00 | 2.80 | -2.2 |
Annual Sum or Average | 0.165579E+12 | 0.213209E+11 | ||||||||
Minimum of Months | 0.573882E+10 | 8142.91 | -7.8 | -9.9 | 0.137623E+10 | 2247.75 | 2.80 | -2.2 | ||
Maximum of Months | 0.252105E+11 | 46701.25 | 29.40 | 23.45 | 0.215258E+10 | 2606.71 | 25.60 | 23.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199243E+09 | 3054.70 | 14-JAN-17:01 | -6.0 | -6.6 | 0.304692E+09 | 406.80 | 10-JAN-14:30 | -6.0 | -6.6 |
February | 0.224959E+09 | 2618.08 | 11-FEB-17:02 | 4.40 | 1.46 | 0.276809E+09 | 406.80 | 09-FEB-10:09 | 4.40 | 1.46 |
March | 0.138672E+10 | 3617.98 | 27-MAR-16:00 | 22.20 | 16.34 | 0.337437E+09 | 472.56 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.287117E+10 | 4857.93 | 07-APR-15:20 | 25.60 | 16.01 | 0.320164E+09 | 549.49 | 07-APR-13:00 | 25.60 | 16.01 |
May | 0.548438E+10 | 7613.05 | 30-MAY-13:50 | 29.50 | 17.11 | 0.384777E+09 | 549.51 | 31-MAY-09:20 | 25.20 | 19.45 |
June | 0.733269E+10 | 9793.93 | 19-JUN-05:02 | 24.08 | 22.05 | 0.421593E+09 | 549.51 | 23-JUN-09:20 | 27.80 | 18.74 |
July | 0.834111E+10 | 15605.40 | 10-JUL-04:01 | 26.10 | 21.38 | 0.400059E+09 | 549.50 | 12-JUL-09:20 | 27.40 | 18.56 |
August | 0.835798E+10 | 11811.14 | 05-AUG-04:01 | 25.68 | 23.87 | 0.445600E+09 | 549.51 | 24-AUG-09:39 | 26.67 | 19.60 |
September | 0.572962E+10 | 7359.94 | 01-SEP-14:30 | 30.85 | 17.41 | 0.370492E+09 | 549.50 | 12-SEP-13:20 | 22.40 | 15.58 |
October | 0.392267E+10 | 4759.03 | 04-OCT-15:00 | 23.90 | 19.11 | 0.348629E+09 | 549.49 | 04-OCT-13:20 | 23.90 | 19.11 |
November | 0.119543E+10 | 3558.88 | 03-NOV-14:50 | 17.30 | 10.93 | 0.306878E+09 | 465.96 | 03-NOV-13:00 | 17.30 | 10.93 |
December | 0.174017E+09 | 2615.59 | 23-DEC-17:02 | 3.40 | 2.18 | 0.294318E+09 | 406.80 | 28-DEC-14:50 | 2.98 | -1.0 |
Annual Sum or Average | 0.452200E+11 | 0.421145E+10 | ||||||||
Minimum of Months | 0.174017E+09 | 2615.59 | -6.0 | -6.6 | 0.276809E+09 | 406.80 | -6.0 | -6.6 | ||
Maximum of Months | 0.835798E+10 | 15605.40 | 30.85 | 23.87 | 0.445600E+09 | 549.51 | 27.80 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269935E+09 | 2030.88 | 14-JAN-17:01 | -6.0 | -6.6 | 0.193027E+09 | 267.74 | 19-JAN-10:20 | 7.80 | 4.36 |
February | 0.376541E+09 | 2058.79 | 22-FEB-09:50 | 0.50 | -3.2 | 0.175697E+09 | 271.78 | 22-FEB-10:09 | 0.87 | -3.0 |
March | 0.148857E+10 | 3105.13 | 29-MAR-09:30 | 6.15 | 3.19 | 0.223287E+09 | 347.87 | 29-MAR-09:00 | 6.70 | 3.39 |
April | 0.246942E+10 | 6001.22 | 07-APR-09:30 | 20.55 | 13.59 | 0.218916E+09 | 347.88 | 06-APR-13:20 | 20.55 | 13.59 |
May | 0.453195E+10 | 12588.13 | 28-MAY-09:02 | 20.87 | 12.95 | 0.256267E+09 | 347.90 | 31-MAY-09:09 | 25.10 | 19.47 |
June | 0.584222E+10 | 12462.20 | 04-JUN-09:22 | 23.85 | 12.91 | 0.270156E+09 | 347.89 | 05-JUN-09:09 | 19.60 | 15.98 |
July | 0.667279E+10 | 13584.57 | 02-JUL-08:42 | 25.40 | 21.60 | 0.254790E+09 | 347.89 | 14-JUL-09:09 | 29.18 | 20.91 |
August | 0.725990E+10 | 11995.15 | 13-AUG-09:52 | 28.90 | 19.41 | 0.286114E+09 | 347.91 | 02-AUG-09:09 | 28.90 | 19.41 |
September | 0.464033E+10 | 12038.75 | 04-SEP-09:32 | 25.03 | 18.26 | 0.242900E+09 | 347.89 | 05-SEP-09:09 | 23.98 | 19.44 |
October | 0.323149E+10 | 5508.43 | 25-OCT-09:30 | 22.20 | 19.22 | 0.238321E+09 | 347.88 | 05-OCT-09:39 | 22.20 | 19.22 |
November | 0.110794E+10 | 2582.78 | 03-NOV-09:40 | 13.13 | 8.29 | 0.198406E+09 | 315.46 | 03-NOV-09:50 | 13.22 | 8.34 |
December | 0.333465E+09 | 2073.79 | 20-DEC-09:40 | 7.57 | 4.72 | 0.186589E+09 | 271.96 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.382246E+11 | 0.274447E+10 | ||||||||
Minimum of Months | 0.269935E+09 | 2030.88 | -6.0 | -6.6 | 0.175697E+09 | 267.74 | 0.87 | -3.0 | ||
Maximum of Months | 0.725990E+10 | 13584.57 | 28.90 | 21.60 | 0.286114E+09 | 347.91 | 29.18 | 20.91 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133391E+10 | 6076.51 | 19-JAN-13:30 | 9.40 | 3.94 | 0.321837E+09 | 549.50 | 19-JAN-14:39 | 9.07 | 3.63 |
February | 0.165799E+10 | 6510.40 | 02-FEB-13:50 | 5.78 | -0.8 | 0.297357E+09 | 549.50 | 17-FEB-14:20 | 6.50 | 2.07 |
March | 0.318612E+10 | 9362.16 | 01-MAR-13:25 | 13.90 | 6.36 | 0.375106E+09 | 549.50 | 29-MAR-13:30 | 7.80 | 5.38 |
April | 0.398501E+10 | 10852.44 | 07-APR-12:30 | 26.15 | 15.90 | 0.343320E+09 | 549.51 | 06-APR-13:20 | 26.15 | 15.90 |
May | 0.620620E+10 | 11516.35 | 30-MAY-12:50 | 29.90 | 17.93 | 0.393525E+09 | 549.51 | 31-MAY-09:20 | 25.20 | 19.45 |
June | 0.805854E+10 | 14456.93 | 25-JUN-13:22 | 26.70 | 23.10 | 0.421926E+09 | 549.51 | 28-JUN-09:39 | 23.90 | 20.98 |
July | 0.931848E+10 | 22465.53 | 30-JUL-12:52 | 27.20 | 24.02 | 0.400437E+09 | 549.50 | 12-JUL-09:20 | 27.20 | 24.02 |
August | 0.109355E+11 | 19681.73 | 13-AUG-13:12 | 31.30 | 19.70 | 0.448201E+09 | 549.52 | 29-AUG-09:39 | 25.17 | 18.68 |
September | 0.817973E+10 | 20250.47 | 04-SEP-12:52 | 26.10 | 18.31 | 0.383137E+09 | 549.51 | 05-SEP-09:09 | 23.98 | 19.44 |
October | 0.700210E+10 | 13869.00 | 04-OCT-13:10 | 24.90 | 18.61 | 0.387124E+09 | 549.51 | 11-OCT-13:50 | 20.60 | 17.27 |
November | 0.278956E+10 | 10784.87 | 02-NOV-13:07 | 15.68 | 8.29 | 0.336896E+09 | 549.50 | 03-NOV-13:20 | 17.40 | 10.62 |
December | 0.161938E+10 | 5894.92 | 21-DEC-13:25 | 3.05 | -1.7 | 0.313944E+09 | 549.50 | 15-DEC-14:20 | 3.05 | -1.7 |
Annual Sum or Average | 0.642725E+11 | 0.442281E+10 | ||||||||
Minimum of Months | 0.133391E+10 | 5894.92 | 3.05 | -1.7 | 0.297357E+09 | 549.50 | 3.05 | -1.7 | ||
Maximum of Months | 0.109355E+11 | 22465.53 | 31.30 | 24.02 | 0.448201E+09 | 549.52 | 27.20 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334728E+09 | 2609.56 | 19-JAN-15:40 | 8.50 | 3.16 | 0.193925E+09 | 287.71 | 19-JAN-15:50 | 8.40 | 3.05 |
February | 0.445831E+09 | 2886.14 | 24-FEB-15:40 | 7.97 | 1.96 | 0.177639E+09 | 308.92 | 24-FEB-15:50 | 7.88 | 1.88 |
March | 0.153480E+10 | 5307.55 | 29-MAR-16:00 | 7.20 | 4.88 | 0.221944E+09 | 347.83 | 03-MAR-14:00 | 7.20 | 4.88 |
April | 0.260914E+10 | 8571.47 | 07-APR-15:30 | 25.60 | 16.04 | 0.206890E+09 | 347.85 | 07-APR-13:20 | 25.60 | 16.04 |
May | 0.463599E+10 | 10085.61 | 30-MAY-15:50 | 28.30 | 17.54 | 0.241985E+09 | 347.85 | 15-MAY-13:00 | 28.30 | 17.54 |
June | 0.619122E+10 | 18413.27 | 25-JUN-16:02 | 26.02 | 22.88 | 0.264018E+09 | 347.86 | 23-JUN-09:20 | 26.02 | 22.88 |
July | 0.677241E+10 | 14447.86 | 04-JUL-16:22 | 25.55 | 18.12 | 0.251901E+09 | 347.85 | 12-JUL-09:20 | 27.40 | 18.56 |
August | 0.741545E+10 | 17871.48 | 13-AUG-15:52 | 30.00 | 20.46 | 0.280876E+09 | 347.86 | 22-AUG-09:20 | 27.97 | 18.50 |
September | 0.482884E+10 | 12173.96 | 10-SEP-15:42 | 23.48 | 13.06 | 0.233243E+09 | 347.85 | 12-SEP-13:20 | 22.40 | 15.58 |
October | 0.347698E+10 | 7861.67 | 04-OCT-15:20 | 23.53 | 19.12 | 0.225899E+09 | 347.85 | 11-OCT-13:00 | 20.60 | 17.38 |
November | 0.101074E+10 | 3557.67 | 03-NOV-15:30 | 16.10 | 10.65 | 0.197133E+09 | 338.68 | 03-NOV-15:39 | 15.73 | 10.52 |
December | 0.341116E+09 | 2517.20 | 08-DEC-15:40 | 6.30 | 2.04 | 0.187109E+09 | 280.90 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.395972E+11 | 0.268256E+10 | ||||||||
Minimum of Months | 0.334728E+09 | 2517.20 | 6.30 | 1.96 | 0.177639E+09 | 280.90 | 6.20 | 1.88 | ||
Maximum of Months | 0.741545E+10 | 18413.27 | 30.00 | 22.88 | 0.280876E+09 | 347.86 | 28.30 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214232E+09 | 1995.65 | 21-JAN-17:02 | 7.70 | 6.90 | 0.305305E+09 | 406.83 | 02-JAN-14:50 | 7.70 | 6.90 |
February | 0.165163E+09 | 1963.39 | 18-FEB-17:03 | 5.32 | 2.41 | 0.277491E+09 | 406.81 | 06-FEB-14:09 | 5.32 | 2.41 |
March | 0.979479E+09 | 2493.13 | 27-MAR-16:00 | 22.20 | 16.34 | 0.335879E+09 | 450.27 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.205790E+10 | 2976.81 | 07-APR-16:00 | 25.60 | 16.13 | 0.314450E+09 | 507.57 | 10-APR-13:00 | 20.60 | 10.45 |
May | 0.376618E+10 | 4633.20 | 30-MAY-14:00 | 29.40 | 16.93 | 0.377870E+09 | 549.49 | 30-MAY-13:20 | 29.40 | 16.93 |
June | 0.527801E+10 | 6465.61 | 19-JUN-14:30 | 33.85 | 23.48 | 0.425175E+09 | 549.50 | 22-JUN-09:20 | 25.77 | 16.91 |
July | 0.649200E+10 | 6774.75 | 10-JUL-15:00 | 33.30 | 21.03 | 0.402320E+09 | 549.51 | 10-JUL-13:20 | 33.30 | 21.03 |
August | 0.692324E+10 | 6924.64 | 17-AUG-13:40 | 31.10 | 24.70 | 0.451465E+09 | 549.50 | 08-AUG-09:20 | 31.10 | 24.70 |
September | 0.500275E+10 | 5984.91 | 01-SEP-14:30 | 30.85 | 17.41 | 0.389589E+09 | 549.50 | 19-SEP-13:20 | 21.70 | 16.49 |
October | 0.394036E+10 | 4307.67 | 05-OCT-14:00 | 23.30 | 18.86 | 0.378160E+09 | 549.49 | 13-OCT-13:20 | 21.70 | 17.63 |
November | 0.184021E+10 | 2828.80 | 03-NOV-14:03 | 17.70 | 10.72 | 0.319216E+09 | 492.51 | 03-NOV-13:00 | 17.70 | 10.72 |
December | 0.454289E+09 | 2123.29 | 20-DEC-13:50 | 9.90 | 5.86 | 0.296026E+09 | 409.28 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.371138E+11 | 0.427295E+10 | ||||||||
Minimum of Months | 0.165163E+09 | 1963.39 | 5.32 | 2.41 | 0.277491E+09 | 406.81 | 5.32 | 2.41 | ||
Maximum of Months | 0.692324E+10 | 6924.64 | 33.85 | 24.70 | 0.451465E+09 | 549.51 | 33.30 | 24.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286170E+09 | 1707.62 | 27-JAN-10:20 | 4.60 | 1.51 | 0.193889E+09 | 272.70 | 27-JAN-10:30 | 4.70 | 1.53 |
February | 0.341571E+09 | 1663.75 | 02-FEB-10:40 | 5.40 | 0.82 | 0.176341E+09 | 268.43 | 02-FEB-10:50 | 5.50 | 0.85 |
March | 0.126001E+10 | 2268.61 | 29-MAR-09:40 | 6.33 | 3.26 | 0.220947E+09 | 331.35 | 29-MAR-09:50 | 6.52 | 3.33 |
April | 0.198379E+10 | 3861.56 | 28-APR-09:20 | 16.47 | 9.08 | 0.216634E+09 | 347.88 | 06-APR-09:20 | 16.47 | 9.08 |
May | 0.336272E+10 | 6816.27 | 30-MAY-09:20 | 26.67 | 17.22 | 0.254178E+09 | 347.88 | 17-MAY-09:20 | 26.67 | 17.22 |
June | 0.460242E+10 | 7273.09 | 26-JUN-08:40 | 24.63 | 19.00 | 0.271494E+09 | 347.89 | 05-JUN-09:09 | 24.63 | 19.00 |
July | 0.560371E+10 | 9322.91 | 09-JUL-09:32 | 29.43 | 25.37 | 0.255605E+09 | 347.88 | 10-JUL-13:20 | 32.40 | 20.60 |
August | 0.658382E+10 | 8736.12 | 13-AUG-09:52 | 28.90 | 19.41 | 0.287352E+09 | 347.88 | 08-AUG-09:20 | 28.90 | 19.41 |
September | 0.447981E+10 | 9271.05 | 04-SEP-09:12 | 24.47 | 18.42 | 0.250357E+09 | 347.88 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.350664E+10 | 5286.23 | 05-OCT-09:30 | 19.45 | 17.11 | 0.253576E+09 | 347.88 | 16-OCT-09:20 | 17.07 | 14.18 |
November | 0.164416E+10 | 2343.32 | 03-NOV-09:40 | 13.13 | 8.29 | 0.209072E+09 | 339.05 | 03-NOV-09:50 | 13.22 | 8.34 |
December | 0.646842E+09 | 1891.98 | 20-DEC-09:50 | 7.93 | 4.87 | 0.188678E+09 | 291.15 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.343017E+11 | 0.277812E+10 | ||||||||
Minimum of Months | 0.286170E+09 | 1663.75 | 4.60 | 0.82 | 0.176341E+09 | 268.43 | 4.70 | 0.85 | ||
Maximum of Months | 0.658382E+10 | 9322.91 | 29.43 | 25.37 | 0.287352E+09 | 347.89 | 32.40 | 20.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.549367E+09 | 2877.21 | 19-JAN-14:30 | 9.15 | 3.65 | 0.300150E+09 | 506.65 | 19-JAN-14:39 | 9.07 | 3.63 |
February | 0.671312E+09 | 2849.37 | 02-FEB-14:30 | 5.30 | -1.4 | 0.274060E+09 | 504.12 | 02-FEB-14:39 | 5.20 | -1.5 |
March | 0.157922E+10 | 4412.42 | 03-MAR-14:03 | 15.00 | 8.59 | 0.350754E+09 | 549.51 | 03-MAR-14:09 | 15.00 | 8.59 |
April | 0.225996E+10 | 7173.46 | 07-APR-12:00 | 25.60 | 15.40 | 0.329955E+09 | 549.52 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.377677E+10 | 11849.40 | 30-MAY-12:00 | 29.40 | 17.58 | 0.381404E+09 | 549.51 | 15-MAY-13:39 | 29.40 | 17.58 |
June | 0.605710E+10 | 15558.11 | 19-JUN-12:00 | 36.70 | 24.28 | 0.422672E+09 | 580.79 | 19-JUN-12:09 | 36.42 | 24.23 |
July | 0.816145E+10 | 15051.36 | 07-JUL-12:00 | 33.90 | 23.31 | 0.403403E+09 | 560.59 | 07-JUL-12:09 | 33.72 | 23.31 |
August | 0.104943E+11 | 15211.42 | 18-AUG-12:00 | 32.80 | 20.19 | 0.453187E+09 | 568.47 | 18-AUG-12:09 | 32.88 | 20.21 |
September | 0.759033E+10 | 18036.42 | 10-SEP-13:52 | 24.40 | 14.19 | 0.395070E+09 | 556.60 | 01-SEP-12:09 | 24.40 | 14.19 |
October | 0.658181E+10 | 16180.72 | 22-OCT-12:43 | 22.02 | 16.80 | 0.402818E+09 | 549.69 | 13-OCT-13:09 | 22.02 | 16.80 |
November | 0.239117E+10 | 10437.68 | 02-NOV-12:07 | 15.10 | 8.04 | 0.338221E+09 | 549.51 | 08-NOV-14:30 | 14.45 | 11.27 |
December | 0.111715E+10 | 3141.71 | 02-DEC-14:10 | 6.70 | 1.42 | 0.303889E+09 | 539.22 | 18-DEC-14:50 | 6.38 | 2.66 |
Annual Sum or Average | 0.512300E+11 | 0.435558E+10 | ||||||||
Minimum of Months | 0.549367E+09 | 2849.37 | 5.30 | -1.4 | 0.274060E+09 | 504.12 | 5.20 | -1.5 | ||
Maximum of Months | 0.104943E+11 | 18036.42 | 36.70 | 24.28 | 0.453187E+09 | 580.79 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300854E+09 | 2058.36 | 20-JAN-16:00 | 7.20 | 3.80 | 0.194360E+09 | 293.38 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.335004E+09 | 2117.78 | 02-FEB-16:30 | 3.60 | -2.6 | 0.177471E+09 | 299.91 | 02-FEB-16:40 | 3.33 | -2.8 |
March | 0.124584E+10 | 3264.94 | 27-MAR-16:50 | 21.28 | 15.57 | 0.219588E+09 | 338.63 | 29-MAR-15:00 | 7.20 | 4.88 |
April | 0.199285E+10 | 5365.09 | 10-APR-16:00 | 20.00 | 11.13 | 0.206691E+09 | 347.83 | 10-APR-13:00 | 20.00 | 11.13 |
May | 0.329340E+10 | 7061.89 | 30-MAY-16:00 | 28.30 | 17.60 | 0.242413E+09 | 347.85 | 22-MAY-13:20 | 28.30 | 17.60 |
June | 0.478832E+10 | 10125.29 | 18-JUN-16:31 | 25.20 | 22.01 | 0.269098E+09 | 347.85 | 22-JUN-09:20 | 25.77 | 16.91 |
July | 0.559169E+10 | 8082.59 | 01-JUL-17:08 | 22.70 | 20.09 | 0.254878E+09 | 347.86 | 10-JUL-13:20 | 32.40 | 20.60 |
August | 0.657196E+10 | 11938.19 | 13-AUG-15:52 | 30.00 | 20.46 | 0.286635E+09 | 347.86 | 23-AUG-09:20 | 23.17 | 15.83 |
September | 0.446562E+10 | 13987.26 | 10-SEP-17:12 | 22.43 | 12.33 | 0.246932E+09 | 347.86 | 13-SEP-09:20 | 22.40 | 20.83 |
October | 0.364238E+10 | 6987.09 | 04-OCT-15:50 | 22.98 | 19.12 | 0.245069E+09 | 347.86 | 16-OCT-13:20 | 19.07 | 15.97 |
November | 0.147250E+10 | 3342.70 | 03-NOV-15:30 | 16.10 | 10.65 | 0.204386E+09 | 338.68 | 03-NOV-15:00 | 15.00 | 10.26 |
December | 0.526509E+09 | 2080.26 | 08-DEC-15:40 | 6.30 | 2.04 | 0.189140E+09 | 295.66 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.342269E+11 | 0.273666E+10 | ||||||||
Minimum of Months | 0.300854E+09 | 2058.36 | 3.60 | -2.6 | 0.177471E+09 | 293.38 | 3.33 | -2.8 | ||
Maximum of Months | 0.657196E+10 | 13987.26 | 30.00 | 22.01 | 0.286635E+09 | 347.86 | 32.40 | 20.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336732E+09 | 2245.10 | 20-JAN-15:03 | 7.70 | 3.95 | 0.305319E+09 | 408.59 | 20-JAN-14:00 | 7.70 | 3.95 |
February | 0.370541E+09 | 2278.42 | 24-FEB-15:40 | 7.97 | 1.96 | 0.277555E+09 | 410.67 | 24-FEB-14:20 | 7.97 | 1.96 |
March | 0.173136E+10 | 3019.33 | 27-MAR-16:00 | 22.20 | 16.34 | 0.343405E+09 | 491.27 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.292001E+10 | 4195.85 | 07-APR-16:00 | 25.60 | 16.13 | 0.334589E+09 | 549.50 | 07-APR-13:20 | 25.60 | 16.13 |
May | 0.492188E+10 | 6734.78 | 30-MAY-14:00 | 29.40 | 16.93 | 0.404584E+09 | 549.50 | 30-MAY-09:20 | 29.40 | 16.93 |
June | 0.660834E+10 | 10818.80 | 19-JUN-05:02 | 24.08 | 22.05 | 0.431008E+09 | 549.51 | 05-JUN-09:20 | 24.08 | 22.05 |
July | 0.753083E+10 | 11104.10 | 10-JUL-04:01 | 26.10 | 21.38 | 0.403650E+09 | 549.50 | 11-JUL-09:20 | 24.27 | 16.60 |
August | 0.760010E+10 | 10374.71 | 05-AUG-04:01 | 25.68 | 23.87 | 0.452063E+09 | 549.50 | 08-AUG-09:20 | 23.87 | 16.88 |
September | 0.529127E+10 | 7997.32 | 01-SEP-05:02 | 24.08 | 21.83 | 0.387506E+09 | 549.50 | 19-SEP-13:20 | 21.70 | 16.49 |
October | 0.398580E+10 | 4678.32 | 05-OCT-14:00 | 23.30 | 18.86 | 0.373546E+09 | 549.50 | 13-OCT-13:20 | 21.70 | 17.63 |
November | 0.168030E+10 | 3087.07 | 03-NOV-14:07 | 17.70 | 10.72 | 0.316546E+09 | 500.45 | 03-NOV-13:00 | 17.70 | 10.72 |
December | 0.480624E+09 | 2311.15 | 20-DEC-13:50 | 9.90 | 5.86 | 0.295484E+09 | 415.27 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.434578E+11 | 0.432526E+10 | ||||||||
Minimum of Months | 0.336732E+09 | 2245.10 | 7.70 | 1.96 | 0.277555E+09 | 408.59 | 7.70 | 1.96 | ||
Maximum of Months | 0.760010E+10 | 11104.10 | 29.40 | 23.87 | 0.452063E+09 | 549.51 | 29.40 | 22.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323695E+09 | 2611.77 | 19-JAN-11:02 | 7.70 | 4.65 | 0.143153E+09 | 328.61 | 19-JAN-11:09 | 7.70 | 4.65 |
February | 0.443959E+09 | 2689.10 | 17-FEB-11:02 | 6.28 | 1.53 | 0.131050E+09 | 336.03 | 17-FEB-11:09 | 6.28 | 1.53 |
March | 0.146917E+10 | 4823.14 | 29-MAR-10:05 | 7.07 | 3.67 | 0.170241E+09 | 356.46 | 29-MAR-14:09 | 7.70 | 5.46 |
April | 0.245456E+10 | 6919.01 | 07-APR-10:05 | 21.97 | 14.06 | 0.165789E+09 | 356.46 | 26-APR-10:09 | 16.57 | 12.62 |
May | 0.429454E+10 | 12833.16 | 29-MAY-08:52 | 26.10 | 16.72 | 0.193068E+09 | 356.46 | 17-MAY-10:09 | 26.10 | 16.72 |
June | 0.545657E+10 | 11233.04 | 25-JUN-09:22 | 25.85 | 23.45 | 0.200952E+09 | 356.46 | 05-JUN-10:09 | 25.85 | 23.45 |
July | 0.621556E+10 | 17525.98 | 02-JUL-08:31 | 25.20 | 21.54 | 0.189503E+09 | 356.46 | 11-JUL-10:09 | 25.18 | 17.11 |
August | 0.683337E+10 | 13317.64 | 27-AUG-09:52 | 26.10 | 21.81 | 0.212112E+09 | 356.46 | 08-AUG-10:09 | 26.10 | 21.81 |
September | 0.450331E+10 | 12817.87 | 04-SEP-09:12 | 24.47 | 18.42 | 0.182446E+09 | 356.46 | 19-SEP-10:09 | 20.00 | 15.38 |
October | 0.333056E+10 | 6726.34 | 04-OCT-10:05 | 21.38 | 18.15 | 0.181678E+09 | 356.46 | 02-OCT-10:09 | 21.38 | 18.15 |
November | 0.124092E+10 | 5151.56 | 01-NOV-12:02 | 12.88 | 7.12 | 0.152851E+09 | 356.46 | 07-NOV-11:09 | 11.20 | 7.76 |
December | 0.499366E+09 | 2744.14 | 20-DEC-11:02 | 8.90 | 5.16 | 0.139401E+09 | 341.33 | 20-DEC-11:09 | 8.90 | 5.16 |
Annual Sum or Average | 0.370656E+11 | 0.206224E+10 | ||||||||
Minimum of Months | 0.323695E+09 | 2611.77 | 6.28 | 1.53 | 0.131050E+09 | 328.61 | 6.28 | 1.53 | ||
Maximum of Months | 0.683337E+10 | 17525.98 | 26.10 | 23.45 | 0.212112E+09 | 356.46 | 26.10 | 23.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149153E+10 | 6674.64 | 19-JAN-13:30 | 9.40 | 3.94 | 0.333047E+09 | 549.49 | 19-JAN-14:39 | 9.07 | 3.63 |
February | 0.183162E+10 | 7198.60 | 02-FEB-13:40 | 5.97 | -0.5 | 0.307794E+09 | 549.50 | 17-FEB-14:20 | 6.50 | 2.07 |
March | 0.357034E+10 | 9299.26 | 03-MAR-13:25 | 14.70 | 8.33 | 0.387746E+09 | 549.50 | 29-MAR-13:30 | 7.80 | 5.38 |
April | 0.409527E+10 | 10210.47 | 07-APR-12:30 | 26.15 | 15.90 | 0.356912E+09 | 549.50 | 07-APR-13:20 | 26.50 | 16.25 |
May | 0.571201E+10 | 14263.67 | 29-MAY-12:13 | 28.33 | 17.95 | 0.410869E+09 | 549.50 | 15-MAY-13:00 | 28.33 | 17.95 |
June | 0.735747E+10 | 10702.37 | 19-JUN-12:50 | 35.28 | 24.00 | 0.430915E+09 | 549.51 | 05-JUN-09:20 | 35.28 | 24.00 |
July | 0.851639E+10 | 19457.80 | 09-JUL-13:22 | 31.70 | 25.11 | 0.404034E+09 | 549.50 | 11-JUL-09:20 | 24.27 | 16.60 |
August | 0.102431E+11 | 19400.41 | 20-AUG-13:12 | 28.17 | 15.57 | 0.453284E+09 | 549.99 | 21-AUG-13:20 | 32.03 | 22.26 |
September | 0.795575E+10 | 19231.91 | 04-SEP-12:32 | 26.10 | 18.14 | 0.394789E+09 | 550.05 | 29-SEP-13:20 | 20.40 | 13.86 |
October | 0.741810E+10 | 18549.78 | 22-OCT-12:43 | 22.02 | 16.80 | 0.401926E+09 | 550.15 | 02-OCT-13:20 | 22.02 | 16.80 |
November | 0.329151E+10 | 11486.65 | 02-NOV-12:50 | 15.50 | 8.17 | 0.356543E+09 | 549.52 | 02-NOV-13:30 | 15.85 | 8.46 |
December | 0.198542E+10 | 7330.87 | 21-DEC-13:30 | 3.05 | -1.7 | 0.329496E+09 | 549.50 | 20-DEC-10:30 | 3.05 | -1.7 |
Annual Sum or Average | 0.634685E+11 | 0.456736E+10 | ||||||||
Minimum of Months | 0.149153E+10 | 6674.64 | 3.05 | -1.7 | 0.307794E+09 | 549.49 | 3.05 | -1.7 | ||
Maximum of Months | 0.102431E+11 | 19457.80 | 35.28 | 25.11 | 0.453284E+09 | 550.15 | 35.28 | 24.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444261E+09 | 2538.81 | 20-JAN-16:00 | 7.20 | 3.80 | 0.195092E+09 | 302.82 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.561572E+09 | 2780.98 | 24-FEB-15:40 | 7.97 | 1.96 | 0.179148E+09 | 323.61 | 24-FEB-15:50 | 7.88 | 1.88 |
March | 0.183194E+10 | 5347.19 | 29-MAR-16:00 | 7.20 | 4.88 | 0.224752E+09 | 347.84 | 03-MAR-14:00 | 7.20 | 4.88 |
April | 0.280991E+10 | 8071.27 | 07-APR-15:40 | 25.60 | 16.07 | 0.211569E+09 | 347.85 | 07-APR-13:20 | 25.60 | 16.07 |
May | 0.453212E+10 | 9581.71 | 30-MAY-16:00 | 28.30 | 17.60 | 0.249103E+09 | 347.86 | 30-MAY-09:20 | 28.30 | 17.60 |
June | 0.586690E+10 | 13330.14 | 18-JUN-16:02 | 25.50 | 22.07 | 0.268861E+09 | 347.85 | 22-JUN-09:20 | 25.77 | 16.91 |
July | 0.637897E+10 | 17953.08 | 04-JUL-16:11 | 25.73 | 18.07 | 0.254092E+09 | 347.85 | 11-JUL-09:20 | 24.27 | 16.60 |
August | 0.705059E+10 | 16518.51 | 20-AUG-16:32 | 25.20 | 17.51 | 0.284453E+09 | 347.86 | 23-AUG-09:20 | 23.17 | 15.83 |
September | 0.478385E+10 | 12287.76 | 10-SEP-16:02 | 23.22 | 12.85 | 0.240458E+09 | 347.86 | 19-SEP-13:20 | 21.70 | 16.49 |
October | 0.380415E+10 | 7738.07 | 04-OCT-15:30 | 23.35 | 19.12 | 0.234445E+09 | 347.85 | 13-OCT-13:20 | 21.70 | 17.63 |
November | 0.140419E+10 | 3852.97 | 03-NOV-15:30 | 16.10 | 10.65 | 0.201388E+09 | 339.59 | 02-NOV-13:00 | 16.10 | 10.65 |
December | 0.563352E+09 | 2488.11 | 08-DEC-15:40 | 6.30 | 2.04 | 0.188970E+09 | 298.43 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.400318E+11 | 0.273233E+10 | ||||||||
Minimum of Months | 0.444261E+09 | 2488.11 | 6.30 | 1.96 | 0.179148E+09 | 298.43 | 6.20 | 1.88 | ||
Maximum of Months | 0.705059E+10 | 17953.08 | 28.30 | 22.07 | 0.284453E+09 | 347.86 | 28.30 | 17.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248231E+09 | 12331.16 | 02-JAN-05:02 | -12.1 |
February | 925169.60 | 5883.99 | 06-FEB-07:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.249156E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.248231E+09 | 12331.16 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.966965E+10 | 21999.98 | 02-JAN-06:10 | -11.7 |
February | 0.812383E+10 | 22087.94 | 06-FEB-05:09 | -13.2 |
March | 0.366047E+10 | 18268.46 | 20-MAR-05:13 | -1.3 |
April | 0.163891E+10 | 18845.31 | 03-APR-05:15 | 2.60 |
May | 0.304190E+09 | 7250.99 | 02-MAY-05:03 | 8.40 |
June | 54698280.55 | 7084.26 | 19-JUN-05:02 | 24.08 |
July | 23679241.75 | 7678.15 | 25-JUL-05:02 | 23.90 |
August | 47724118.10 | 7533.30 | 01-AUG-05:02 | 23.90 |
September | 0.210064E+09 | 6701.12 | 29-SEP-05:03 | 11.78 |
October | 0.978921E+09 | 9141.80 | 19-OCT-05:03 | 5.37 |
November | 0.405229E+10 | 19743.00 | 24-NOV-06:08 | -4.4 |
December | 0.691439E+10 | 18061.29 | 15-DEC-06:04 | -3.4 |
Annual Sum or Average | 0.356788E+11 | |||
Minimum of Months | 23679241.75 | 6701.12 | -13.2 | |
Maximum of Months | 0.966965E+10 | 22087.94 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339292E+10 | 12485.84 | 02-JAN-08:14 | -10.9 |
February | 0.255964E+10 | 10039.60 | 06-FEB-07:40 | -13.0 |
March | 0.117218E+10 | 5588.80 | 20-MAR-06:12 | -0.6 |
April | 0.337528E+09 | 5205.29 | 16-APR-15:22 | 21.40 |
May | 82135390.08 | 3893.18 | 14-MAY-14:18 | 14.23 |
June | 11557253.91 | 3434.19 | 19-JUN-05:02 | 24.08 |
July | 17296409.92 | 2920.75 | 10-JUL-04:01 | 26.10 |
August | 14713755.24 | 3071.57 | 13-AUG-15:12 | 30.40 |
September | 21002996.71 | 5006.15 | 24-SEP-11:22 | 17.50 |
October | 0.142191E+09 | 5662.35 | 09-OCT-11:42 | 13.72 |
November | 0.126384E+10 | 7215.84 | 24-NOV-07:12 | -4.2 |
December | 0.200665E+10 | 7558.17 | 11-DEC-07:12 | 1.70 |
Annual Sum or Average | 0.110217E+11 | |||
Minimum of Months | 11557253.91 | 2920.75 | -13.0 | |
Maximum of Months | 0.339292E+10 | 12485.84 | 30.40 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220402E+10 | 10626.22 | 02-JAN-08:23 | -10.8 |
February | 0.142053E+10 | 6014.58 | 06-FEB-09:00 | -12.2 |
March | 0.396240E+09 | 3076.22 | 20-MAR-07:17 | 0.33 |
April | 73993807.26 | 2425.40 | 03-APR-07:08 | 3.68 |
May | 9455842.38 | 3422.72 | 28-MAY-14:08 | 25.78 |
June | 11723081.96 | 4695.52 | 19-JUN-05:02 | 24.08 |
July | 20718408.06 | 4282.27 | 07-JUL-04:02 | 26.02 |
August | 18935726.58 | 4710.18 | 03-AUG-04:02 | 26.02 |
September | 18370000.80 | 4847.57 | 01-SEP-05:02 | 24.08 |
October | 31983700.73 | 4387.73 | 09-OCT-11:42 | 13.72 |
November | 0.412357E+09 | 3457.81 | 24-NOV-08:08 | -3.5 |
December | 0.882838E+09 | 3564.73 | 11-DEC-08:09 | 1.60 |
Annual Sum or Average | 0.550116E+10 | |||
Minimum of Months | 9455842.38 | 2425.40 | -12.2 | |
Maximum of Months | 0.220402E+10 | 10626.22 | 26.02 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.760677E+09 | 19205.77 | 02-JAN-05:02 | -12.1 |
February | 0.315852E+09 | 17875.05 | 06-FEB-05:01 | -13.2 |
March | 20900543.39 | 15149.76 | 20-MAR-05:01 | -1.5 |
April | 3325184.20 | 14200.72 | 03-APR-06:01 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 44553411.27 | 15334.70 | 24-NOV-06:01 | -4.4 |
December | 80646948.87 | 15859.53 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.122595E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.760677E+09 | 19205.77 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311761E+10 | 30611.49 | 17-JAN-05:01 | 0.92 |
February | 0.226877E+10 | 29265.68 | 27-FEB-05:01 | -0.8 |
March | 0.583284E+09 | 26890.86 | 20-MAR-04:01 | -0.8 |
April | 0.122658E+09 | 26174.81 | 03-APR-05:11 | 2.60 |
May | 4147212.67 | 22044.12 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 15731733.15 | 21535.32 | 30-OCT-06:03 | 10.50 |
November | 0.849865E+09 | 28058.19 | 20-NOV-05:11 | 0.40 |
December | 0.130647E+10 | 29046.41 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.826854E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.311761E+10 | 30611.49 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.523005E+10 | 14718.25 | 09-JAN-05:41 | 1.28 |
February | 0.453990E+10 | 14115.07 | 01-FEB-06:01 | 1.78 |
March | 0.147315E+10 | 13790.47 | 20-MAR-04:01 | -0.8 |
April | 0.417014E+09 | 14044.06 | 03-APR-05:11 | 2.60 |
May | 25450827.29 | 11362.90 | 01-MAY-05:12 | 6.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 6758583.56 | 6923.55 | 29-SEP-06:03 | 12.38 |
October | 0.123398E+09 | 11816.96 | 28-OCT-05:12 | 3.90 |
November | 0.161589E+10 | 14158.43 | 20-NOV-05:11 | 0.40 |
December | 0.327168E+10 | 14432.37 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.167033E+11 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.523005E+10 | 14718.25 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298317E+10 | 9698.00 | 09-JAN-05:41 | 1.28 |
February | 0.235695E+10 | 9309.38 | 01-FEB-06:01 | 1.78 |
March | 0.744243E+09 | 9077.82 | 20-MAR-04:01 | -0.8 |
April | 0.222539E+09 | 9188.45 | 03-APR-05:11 | 2.60 |
May | 9681299.38 | 7424.75 | 01-MAY-05:12 | 6.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 2752054.13 | 3799.84 | 29-SEP-06:03 | 12.38 |
October | 62337645.37 | 7720.97 | 28-OCT-05:12 | 3.90 |
November | 0.851467E+09 | 9304.93 | 20-NOV-05:11 | 0.40 |
December | 0.180666E+10 | 9504.74 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.903980E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.298317E+10 | 9698.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.378921E+10 | 14548.82 | 09-JAN-05:41 | 1.28 |
February | 0.298315E+10 | 13808.34 | 21-FEB-06:11 | 2.40 |
March | 0.104643E+10 | 13520.43 | 20-MAR-04:01 | -0.8 |
April | 0.366722E+09 | 13614.30 | 03-APR-05:11 | 2.60 |
May | 29284339.29 | 11253.13 | 01-MAY-05:12 | 6.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 4189298.71 | 5192.27 | 30-SEP-06:03 | 11.20 |
October | 76514806.43 | 11355.26 | 28-OCT-05:12 | 3.90 |
November | 0.106716E+10 | 13936.11 | 20-NOV-05:11 | 0.40 |
December | 0.226680E+10 | 14241.19 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.116295E+11 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.378921E+10 | 14548.82 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323208E+10 | 10317.83 | 09-JAN-05:41 | 1.28 |
February | 0.272166E+10 | 9826.90 | 01-FEB-06:01 | 1.78 |
March | 0.837179E+09 | 9499.14 | 11-MAR-06:01 | 1.78 |
April | 0.257747E+09 | 9635.77 | 03-APR-05:11 | 2.60 |
May | 20313724.00 | 7810.58 | 01-MAY-05:12 | 6.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 4679638.09 | 4273.25 | 29-SEP-06:03 | 12.38 |
October | 74478348.32 | 8114.02 | 28-OCT-05:12 | 3.90 |
November | 0.101635E+10 | 9886.81 | 20-NOV-05:11 | 0.40 |
December | 0.202372E+10 | 10084.00 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.101882E+11 | |||
Minimum of Months | 0.00 | 0.00 | 0.40 | |
Maximum of Months | 0.323208E+10 | 10317.83 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315796E+10 | 11129.29 | 01-JAN-08:42 | -2.9 |
February | 0.288300E+10 | 10817.12 | 13-FEB-05:01 | -9.0 |
March | 0.864961E+09 | 9629.37 | 13-MAR-04:01 | -0.1 |
April | 0.209583E+09 | 9309.88 | 03-APR-05:11 | 2.60 |
May | 9197650.20 | 7457.12 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 3213459.31 | 6182.45 | 28-OCT-06:03 | 3.90 |
November | 0.354336E+09 | 9530.77 | 24-NOV-05:01 | -4.0 |
December | 0.103007E+10 | 9259.76 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.851233E+10 | |||
Minimum of Months | 0.00 | 0.00 | -9.0 | |
Maximum of Months | 0.315796E+10 | 11129.29 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164479E+10 | 7540.13 | 01-JAN-16:03 | -3.2 |
February | 0.128267E+10 | 7465.27 | 13-FEB-05:01 | -9.0 |
March | 0.334025E+09 | 6619.66 | 20-MAR-04:01 | -0.8 |
April | 86961769.30 | 6330.55 | 03-APR-05:11 | 2.60 |
May | 4005324.99 | 4317.98 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 648337.84 | 2411.35 | 28-OCT-06:03 | 3.90 |
November | 0.158683E+09 | 6377.43 | 24-NOV-06:01 | -4.4 |
December | 0.511081E+09 | 6402.65 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.402286E+10 | |||
Minimum of Months | 0.00 | 0.00 | -9.0 | |
Maximum of Months | 0.164479E+10 | 7540.13 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456848E+10 | 13832.25 | 02-JAN-07:40 | -11.3 |
February | 0.391993E+10 | 12979.66 | 06-FEB-07:40 | -13.0 |
March | 0.243573E+10 | 11131.91 | 23-MAR-06:10 | -4.7 |
April | 0.120891E+10 | 9691.58 | 03-APR-06:10 | 2.38 |
May | 0.393753E+09 | 8254.09 | 01-MAY-06:10 | 7.67 |
June | 2450405.86 | 1662.19 | 02-JUN-06:07 | 13.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 14274570.97 | 3957.99 | 20-SEP-06:07 | 12.48 |
October | 0.231424E+09 | 7747.21 | 27-OCT-06:10 | 5.68 |
November | 0.147719E+10 | 10859.53 | 24-NOV-07:10 | -4.3 |
December | 0.272883E+10 | 10836.45 | 22-DEC-07:10 | -4.9 |
Annual Sum or Average | 0.169810E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.0 | |
Maximum of Months | 0.456848E+10 | 13832.25 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183455E+10 | 7966.41 | 01-JAN-08:42 | -2.9 |
February | 0.152622E+10 | 7665.51 | 13-FEB-05:01 | -9.0 |
March | 0.342341E+09 | 6433.14 | 01-MAR-06:11 | 4.07 |
April | 96566018.83 | 6366.91 | 03-APR-05:11 | 2.60 |
May | 6015936.54 | 5146.35 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 601307.98 | 2709.12 | 28-OCT-06:03 | 3.90 |
November | 0.203814E+09 | 6516.73 | 24-NOV-06:01 | -4.4 |
December | 0.583697E+09 | 6541.45 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.459381E+10 | |||
Minimum of Months | 0.00 | 0.00 | -9.0 | |
Maximum of Months | 0.183455E+10 | 7966.41 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296833E+10 | 11612.67 | 01-JAN-08:42 | -2.9 |
February | 0.242514E+10 | 11312.41 | 27-FEB-05:01 | -0.8 |
March | 0.532778E+09 | 10548.71 | 13-MAR-04:01 | -0.1 |
April | 98932490.64 | 9873.07 | 03-APR-05:11 | 2.60 |
May | 2949838.22 | 7687.25 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 12147743.26 | 7967.28 | 28-OCT-06:03 | 3.90 |
November | 0.589647E+09 | 11270.24 | 24-NOV-05:01 | -4.0 |
December | 0.133911E+10 | 10747.35 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.796904E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.296833E+10 | 11612.67 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163791E+10 | 8530.03 | 17-JAN-05:01 | 0.92 |
February | 0.119430E+10 | 8395.21 | 27-FEB-05:01 | -0.8 |
March | 0.258313E+09 | 7654.82 | 13-MAR-04:01 | -0.1 |
April | 48788406.99 | 7121.97 | 03-APR-05:11 | 2.60 |
May | 1456558.04 | 3223.56 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 8472593.70 | 5434.09 | 28-OCT-06:03 | 3.90 |
November | 0.306072E+09 | 8243.86 | 24-NOV-05:01 | -4.0 |
December | 0.730365E+09 | 7912.90 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.418568E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.163791E+10 | 8530.03 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195399E+10 | 11222.10 | 17-JAN-05:01 | 0.92 |
February | 0.136958E+10 | 11070.99 | 27-FEB-05:01 | -0.8 |
March | 0.328453E+09 | 10161.67 | 13-MAR-04:01 | -0.1 |
April | 83786317.23 | 9497.90 | 03-APR-05:11 | 2.60 |
May | 3374716.09 | 7773.83 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 6882166.56 | 7822.25 | 28-OCT-06:03 | 3.90 |
November | 0.338741E+09 | 10582.89 | 24-NOV-05:01 | -4.0 |
December | 0.830363E+09 | 10514.73 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.491517E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.195399E+10 | 11222.10 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183483E+10 | 8740.83 | 01-JAN-08:42 | -2.9 |
February | 0.143577E+10 | 8537.45 | 27-FEB-05:01 | -0.8 |
March | 0.291925E+09 | 7851.01 | 13-MAR-04:01 | -0.1 |
April | 66145604.54 | 7178.93 | 03-APR-05:11 | 2.60 |
May | 3491411.59 | 5047.22 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 8558856.59 | 5439.25 | 28-OCT-06:03 | 3.90 |
November | 0.382565E+09 | 8426.69 | 24-NOV-05:01 | -4.0 |
December | 0.835062E+09 | 8064.24 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.485835E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.183483E+10 | 8740.83 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157225E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139901E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109332E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 947429.42 | 0.708545E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6452880.18 | 0.410446E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27372367.07 | 0.220154E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63358482.00 | 76610783.10 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68212748.85 | 98550329.53 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11660148.10 | 0.212876E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 221732.57 | 0.545103E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103957E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129133E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178226E+09 | 0.866777E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76610783.10 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68212748.85 | 0.157225E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104779E+10 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936698E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736328E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 462854.77 | 0.494005E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2201712.93 | 0.287429E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16222937.84 | 0.150947E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37183012.40 | 53218603.42 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41641559.37 | 70060006.73 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5853122.92 | 0.153245E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72298.43 | 0.381984E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701906E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864011E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103637E+09 | 0.587763E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53218603.42 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41641559.37 | 0.104779E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159952E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144157E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114256E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 677363.61 | 0.748514E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3672294.75 | 0.424709E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24588653.35 | 0.222175E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56694907.69 | 79449869.56 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61366911.67 | 0.105517E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7708663.46 | 0.241760E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108431.52 | 0.625732E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109329E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134207E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154817E+09 | 0.906687E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79449869.56 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61366911.67 | 0.159952E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105052E+10 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938916E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748223E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 593976.12 | 0.493381E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3656853.44 | 0.287326E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16606741.24 | 0.157431E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39173240.96 | 59995442.88 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43185242.42 | 72786463.43 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6446132.90 | 0.152341E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161831.11 | 0.385397E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695990E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865600E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109824E+09 | 0.590791E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59995442.88 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43185242.42 | 0.105052E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878276E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772898E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5647.73 | 0.610626E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 763996.10 | 0.388396E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3683046.33 | 0.216332E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14901127.01 | 0.115340E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35313992.12 | 37831799.89 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36131456.33 | 53473556.19 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5418101.92 | 0.133144E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67644.20 | 0.341273E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637261E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759879E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96285011.74 | 0.494473E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37831799.89 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36131456.33 | 0.878276E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586728E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523372E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4185.36 | 0.415011E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281490.34 | 0.274302E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1209605.59 | 0.156285E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8869162.90 | 81991069.09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20526471.47 | 27889025.47 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21901747.20 | 40064026.95 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2772875.97 | 96590687.64 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43380.50 | 0.241951E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434720E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511589E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55608919.33 | 0.339049E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27889025.47 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21901747.20 | 0.586728E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570306E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560796E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497065E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11175251.78 | 0.291351E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46797560.66 | 0.165532E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329228E+09 | 0.532025E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702635E+09 | 71959876.12 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857763E+09 | 0.186023E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142751E+09 | 0.829421E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2201746.68 | 0.229497E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421918E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512552E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209255E+10 | 0.341096E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71959876.12 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857763E+09 | 0.570306E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588670E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522454E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422112E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 357255.46 | 0.274854E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1902452.34 | 0.157229E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8336592.72 | 87664310.34 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20550597.98 | 32476098.84 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22030151.95 | 42688980.35 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2928790.06 | 96965378.72 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46566.29 | 0.244679E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428728E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511709E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56152406.79 | 0.341023E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32476098.84 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22030151.95 | 0.588670E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135564E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120657E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972372E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 692554.51 | 0.638364E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5083791.07 | 0.372661E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21791409.43 | 0.199796E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50142847.80 | 71060057.18 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54326003.35 | 91943556.25 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8503419.94 | 0.202296E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99539.12 | 0.510371E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949545E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114854E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140640E+09 | 0.771916E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71060057.18 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54326003.35 | 0.135564E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903036E+09 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811887E+09 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659039E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 366403.59 | 0.443300E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2035375.75 | 0.257188E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13577797.27 | 0.133906E+09 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31502356.37 | 47639334.70 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34218194.75 | 63351327.46 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4776082.74 | 0.141445E+09 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36603.16 | 0.353861E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644014E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770027E+09 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86512813.63 | 0.522869E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47639334.70 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34218194.75 | 0.903036E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139110E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126263E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101879E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 538099.23 | 0.672076E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2801068.55 | 0.384196E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19307054.37 | 0.201397E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44369977.90 | 73507653.17 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49245479.93 | 97887369.45 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6146704.77 | 0.225607E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95567.70 | 0.573238E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100350E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120549E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122504E+09 | 0.810942E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73507653.17 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49245479.93 | 0.139110E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906570E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811599E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664324E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 477668.00 | 0.440949E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3079673.18 | 0.256603E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13465260.16 | 0.140302E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32095844.00 | 54047416.05 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35277324.22 | 66494803.84 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5080295.72 | 0.140939E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109630.85 | 0.353830E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634358E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770072E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89585696.13 | 0.524009E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54047416.05 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35277324.22 | 0.906570E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192024E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172885E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141677E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543268.88 | 0.938032E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3648919.60 | 0.542177E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18815481.54 | 0.287757E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46686149.50 | 97286859.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53409375.78 | 0.132094E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5234850.56 | 0.315617E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11622.15 | 0.791869E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143143E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170318E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128350E+09 | 0.113053E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97286859.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53409375.78 | 0.192024E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233719E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210454E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172844E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696004.07 | 0.114349E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5287415.61 | 0.673146E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25132186.00 | 0.360284E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60424123.36 | 0.121636E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69778069.84 | 0.163690E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7025361.80 | 0.374859E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33809.07 | 0.941817E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168815E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202564E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168377E+09 | 0.136629E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121636E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69778069.84 | 0.233719E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226938E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204767E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165680E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59611.57 | 0.111122E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1100907.25 | 0.673857E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17047878.37 | 0.356177E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44480305.86 | 0.118987E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60523829.94 | 0.140074E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5159440.59 | 0.346020E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869815E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154052E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188553E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128372E+09 | 0.130161E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118987E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60523829.94 | 0.226938E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2699.30 | 01-JAN-21:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2913.67 | 06-FEB-00:48 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2208.47 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 08-APR-10:00 | 1539.80 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.52 | 29-MAY-12:00 | 881.49 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.57 | 25-JUN-18:53 | 562.78 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.08 | 09-JUL-13:40 | 274.44 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 402.03 | 12-AUG-18:53 | 356.27 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.23 | 04-SEP-13:40 | 466.08 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.22 | 25-OCT-11:00 | 1273.45 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2165.28 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2919.06 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.44 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 402.03 | 2919.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1799.52 | 01-JAN-21:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1942.48 | 06-FEB-00:50 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1472.61 | 21-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 07-APR-13:00 | 1026.64 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.58 | 29-MAY-12:00 | 591.14 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.10 | 25-JUN-18:53 | 374.56 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.93 | 09-JUL-13:40 | 188.13 | 11-JUL-05:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.94 | 12-AUG-18:53 | 251.59 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 14-SEP-14:00 | 335.45 | 10-SEP-08:20 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 25-OCT-11:00 | 927.79 | 08-OCT-08:30 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1443.52 | 22-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1945.98 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.13 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 266.94 | 1945.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2699.18 | 01-JAN-21:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2913.77 | 06-FEB-00:48 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2215.81 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 07-APR-13:00 | 1572.17 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.20 | 29-MAY-12:00 | 901.31 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.37 | 25-JUN-18:53 | 564.12 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.07 | 09-JUL-13:40 | 269.46 | 11-JUL-04:52 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.27 | 12-AUG-18:53 | 359.76 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.07 | 14-SEP-14:00 | 489.80 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 25-OCT-11:00 | 1343.14 | 17-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2170.84 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2918.98 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.46 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 394.27 | 2918.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1799.67 | 01-JAN-21:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1942.55 | 06-FEB-00:48 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1475.27 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 08-APR-10:00 | 1042.15 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.98 | 29-MAY-12:00 | 605.64 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.58 | 19-JUN-21:02 | 457.19 | 03-JUN-18:55 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.52 | 09-JUL-13:40 | 249.73 | 01-JUL-17:40 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.34 | 12-AUG-18:53 | 243.20 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.07 | 04-SEP-12:20 | 324.19 | 10-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.47 | 25-OCT-11:00 | 869.62 | 17-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1443.10 | 22-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1946.09 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.20 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 257.34 | 1946.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1498.26 | 31-JAN-00:53 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1549.50 | 06-FEB-00:51 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 | 27-MAR-16:10 | 1178.77 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.40 | 07-APR-17:00 | 891.00 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.99 | 29-MAY-12:20 | 486.33 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.79 | 19-JUN-21:02 | 309.31 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.16 | 09-JUL-14:00 | 142.34 | 11-JUL-04:50 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.74 | 04-AUG-21:02 | 214.45 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.21 | 04-SEP-14:00 | 290.62 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 25-OCT-11:00 | 817.34 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1266.82 | 23-NOV-01:55 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1526.52 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.34 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 191.16 | 1549.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1006.60 | 31-JAN-00:53 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1033.71 | 06-FEB-00:51 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 27-MAR-16:10 | 787.23 | 21-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 | 07-APR-17:00 | 612.08 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.08 | 29-MAY-12:20 | 342.74 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 19-JUN-21:02 | 216.22 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.43 | 09-JUL-14:00 | 99.91 | 11-JUL-04:50 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.08 | 04-AUG-21:02 | 155.54 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 192.95 | 30-SEP-24:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 611.87 | 08-OCT-08:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 855.88 | 23-NOV-01:55 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1027.33 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.91 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 124.08 | 1033.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 26564.96 | 02-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 28428.60 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 21980.59 | 23-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1704.36 | 07-APR-17:00 | 15291.56 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4365.53 | 30-MAY-12:00 | 10615.22 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9337.62 | 19-JUN-11:05 | 6175.41 | 02-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7441.95 | 07-JUL-12:00 | 1814.82 | 11-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7728.12 | 24-AUG-16:10 | 3994.33 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4438.85 | 14-SEP-16:10 | 8544.97 | 11-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 662.26 | 25-OCT-11:10 | 13278.51 | 31-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21624.97 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 22209.11 | 22-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1814.82 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9337.62 | 28428.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1010.42 | 31-JAN-00:53 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1032.93 | 06-FEB-00:51 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 789.11 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 07-APR-13:00 | 633.47 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.11 | 29-MAY-12:20 | 347.56 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.04 | 19-JUN-21:02 | 232.93 | 03-JUN-19:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.71 | 09-JUL-13:52 | 115.50 | 02-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.61 | 04-AUG-21:02 | 154.66 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 201.52 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 560.33 | 08-OCT-08:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 847.36 | 23-NOV-01:55 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1028.28 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.50 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 123.61 | 1032.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2273.75 | 31-JAN-00:53 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2444.06 | 06-FEB-00:59 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1848.60 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 07-APR-13:00 | 1424.95 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.25 | 29-MAY-12:00 | 818.70 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.99 | 19-JUN-21:02 | 505.33 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.47 | 09-JUL-14:10 | 247.95 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.25 | 12-AUG-19:00 | 335.17 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.37 | 04-SEP-14:00 | 433.15 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 25-OCT-11:00 | 1181.37 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1867.76 | 23-NOV-01:55 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2427.10 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.95 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 340.25 | 2444.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1512.39 | 31-JAN-00:53 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.35 | 06-FEB-00:55 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1250.05 | 12-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 07-APR-17:00 | 946.83 | 11-APR-04:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.41 | 29-MAY-12:20 | 546.40 | 03-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.22 | 19-JUN-21:02 | 332.15 | 02-JUN-22:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.05 | 09-JUL-14:10 | 169.31 | 11-JUL-05:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.66 | 12-AUG-19:00 | 234.75 | 20-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.08 | 14-SEP-14:10 | 316.61 | 10-SEP-08:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 25-OCT-11:00 | 895.34 | 08-OCT-08:00 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1245.28 | 23-NOV-01:55 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1618.17 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.31 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 237.66 | 1629.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2352.38 | 31-JAN-00:53 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2444.06 | 06-FEB-00:56 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1878.03 | 12-MAR-10:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 07-APR-13:00 | 1450.62 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.88 | 29-MAY-12:20 | 835.44 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.92 | 19-JUN-21:02 | 505.73 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.71 | 09-JUL-14:10 | 243.44 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.27 | 12-AUG-19:00 | 338.01 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.88 | 14-SEP-14:00 | 452.84 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 25-OCT-11:00 | 1286.28 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1913.63 | 23-NOV-01:55 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2427.21 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.44 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 333.27 | 2444.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1518.38 | 31-JAN-00:53 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.39 | 06-FEB-00:58 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1235.89 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.52 | 08-APR-10:00 | 960.38 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.49 | 29-MAY-12:00 | 559.51 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.87 | 19-JUN-21:02 | 385.71 | 03-JUN-18:55 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.43 | 09-JUL-13:30 | 202.60 | 01-JUL-17:40 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.26 | 12-AUG-19:00 | 227.92 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 04-SEP-12:00 | 294.59 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.32 | 25-OCT-11:00 | 798.03 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1239.67 | 23-NOV-01:55 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1618.08 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.60 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 228.26 | 1629.39 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3424.19 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3337.60 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2508.79 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.54 | 07-APR-13:00 | 2136.21 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.65 | 29-MAY-11:53 | 1222.76 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.48 | 19-JUN-21:02 | 717.06 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.11 | 09-JUL-14:00 | 336.12 | 11-JUL-04:54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.39 | 12-AUG-18:53 | 481.03 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.12 | 14-SEP-14:00 | 639.74 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 25-OCT-11:00 | 1819.78 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2862.20 | 23-NOV-01:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3474.35 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.12 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.39 | 3474.35 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4176.00 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4006.42 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3141.95 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 | 07-APR-13:00 | 2657.13 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.12 | 29-MAY-12:00 | 1508.81 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.37 | 19-JUN-21:02 | 910.25 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.78 | 09-JUL-13:52 | 422.31 | 11-JUL-04:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.18 | 12-AUG-19:00 | 594.00 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.92 | 14-SEP-14:00 | 777.40 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 25-OCT-11:00 | 2203.18 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3465.38 | 23-NOV-01:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4082.74 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.18 | 4176.00 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3896.86 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3963.82 | 06-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3207.02 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.56 | 08-APR-10:00 | 2218.15 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 29-MAY-12:00 | 1588.37 | 14-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.66 | 19-JUN-21:02 | 847.69 | 03-JUN-17:08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.46 | 07-JUL-22:00 | 429.59 | 02-JUL-18:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.61 | 04-AUG-21:02 | 465.04 | 06-AUG-12:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.16 | 14-SEP-14:00 | 671.04 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1859.48 | 17-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3130.36 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3934.58 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.59 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.61 | 3963.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14005.51 | 27-JAN-16:30 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14547.33 | 24-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18406.74 | 29-MAR-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25182.25 | 10-APR-06:03 | 3811.58 | 9760.61 | 31425.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48229.25 | 30-MAY-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48815.66 | 19-JUN-05:02 | 3811.58 | 6507.07 | 46406.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 53324.56 | 18-JUL-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 53092.23 | 18-AUG-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51776.14 | 01-SEP-05:03 | 3811.58 | 6507.07 | 46406.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40151.79 | 05-OCT-06:03 | 5082.11 | 13014.15 | 41900.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21560.38 | 03-NOV-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16312.14 | 21-DEC-16:10 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14005.51 | 0.00 | 4338.05 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53324.56 | 6035.01 | 13014.15 | 46406.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1715.18 | 17-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.54 |
February | 2664.68 | 17-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.96 |
March | 5986.51 | 03-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.76 |
April | 11854.42 | 07-APR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
May | 17210.81 | 30-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.98 | 0.00 |
June | 19680.40 | 19-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.66 | 0.00 |
July | 18264.49 | 07-JUL-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.07 | 0.00 |
August | 17843.36 | 18-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 | 0.00 |
September | 15754.76 | 01-SEP-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.62 | 0.00 |
October | 10888.97 | 04-OCT-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 |
November | 4840.36 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.43 |
December | 1236.20 | 20-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1236.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19680.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.33 | 401.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4661.46 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1947.50 |
February | 4555.07 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2320.75 |
March | 3847.26 | 08-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.68 |
April | 3825.44 | 21-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.48 |
May | 5071.02 | 30-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.32 | 0.00 |
June | 5777.85 | 19-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.75 | 0.00 |
July | 6424.62 | 10-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.89 | 0.00 |
August | 6341.56 | 14-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.70 | 0.00 |
September | 5566.13 | 01-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.20 | 0.00 |
October | 3359.73 | 04-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 |
November | 3428.84 | 18-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.08 |
December | 3550.71 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3359.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6424.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.89 | 2320.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3509.14 | 28-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.07 |
February | 4404.84 | 24-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.13 |
March | 4860.86 | 31-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.10 |
April | 4904.27 | 19-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.89 |
May | 5167.87 | 30-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 0.00 |
June | 5970.16 | 19-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.41 | 0.00 |
July | 6396.30 | 10-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.03 | 0.00 |
August | 6497.19 | 14-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.32 | 0.00 |
September | 6085.17 | 05-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 0.00 |
October | 4557.96 | 04-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 |
November | 3072.79 | 16-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.99 |
December | 3601.98 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3072.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6497.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.41 | 451.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7879.20 | 20-JAN-17:00 | 12070.02 | 19521.22 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7896.64 | 24-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11005.32 | 29-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15903.22 | 10-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25097.41 | 31-MAY-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39464.45 | 20-JUN-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42760.59 | 10-JUL-04:03 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41587.05 | 04-AUG-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39527.01 | 05-SEP-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18031.57 | 05-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13155.33 | 03-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8055.99 | 21-DEC-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7879.20 | 0.00 | 4338.05 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42760.59 | 12070.02 | 19521.22 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8540.65 | 05-JAN-00:13 | 0.00 | 1626.77 | 7326.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9289.94 | 09-FEB-00:13 | 0.00 | 1626.77 | 7326.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10510.83 | 29-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17720.79 | 07-APR-15:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23357.38 | 30-MAY-14:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46524.97 | 19-JUN-05:02 | 3811.58 | 6507.07 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 46701.25 | 20-JUL-05:02 | 3811.58 | 6507.07 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46682.79 | 01-AUG-05:02 | 3811.58 | 6507.07 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46403.66 | 01-SEP-05:02 | 3811.58 | 6507.07 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18646.01 | 04-OCT-15:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10948.43 | 03-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8142.91 | 21-DEC-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8142.91 | 0.00 | 1626.77 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46701.25 | 6198.29 | 9760.61 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3054.70 | 14-JAN-17:01 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.78 |
February | 2618.08 | 11-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.95 |
March | 3617.98 | 27-MAR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 |
April | 4857.93 | 07-APR-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 0.00 |
May | 7613.05 | 30-MAY-13:50 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 57.94 | 0.00 |
June | 9793.93 | 19-JUN-05:02 | 803.52 | 1371.75 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 |
July | 15605.40 | 10-JUL-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 | 0.00 |
August | 11811.14 | 05-AUG-04:01 | 0.00 | 800.19 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 |
September | 7359.94 | 01-SEP-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 77.78 | 0.00 |
October | 4759.03 | 04-OCT-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
November | 3558.88 | 03-NOV-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.22 |
December | 2615.59 | 23-DEC-17:02 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2615.59 | 0.00 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15605.40 | 1306.65 | 2057.62 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 77.78 | 747.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2030.88 | 14-JAN-17:01 | 339.13 | 578.95 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.11 |
February | 2058.79 | 22-FEB-09:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.45 |
March | 3105.13 | 29-MAR-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.12 |
April | 6001.22 | 07-APR-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 |
May | 12588.13 | 28-MAY-09:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.41 |
June | 12462.20 | 04-JUN-09:22 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.46 |
July | 13584.57 | 02-JUL-08:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 |
August | 11995.15 | 13-AUG-09:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 0.00 |
September | 12038.75 | 04-SEP-09:32 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.99 |
October | 5508.43 | 25-OCT-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 |
November | 2582.78 | 03-NOV-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.31 |
December | 2073.79 | 20-DEC-09:40 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2030.88 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13584.57 | 1610.86 | 2605.29 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 498.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6076.51 | 19-JAN-13:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.56 |
February | 6510.40 | 02-FEB-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.88 |
March | 9362.16 | 01-MAR-13:25 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.63 |
April | 10852.44 | 07-APR-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | 0.00 |
May | 11516.35 | 30-MAY-12:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 65.22 | 0.00 |
June | 14456.93 | 25-JUN-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 |
July | 22465.53 | 30-JUL-12:52 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 | 0.00 |
August | 19681.73 | 13-AUG-13:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 142.98 | 0.00 |
September | 20250.47 | 04-SEP-12:52 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 |
October | 13869.00 | 04-OCT-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 | 0.00 |
November | 10784.87 | 02-NOV-13:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.03 |
December | 5894.92 | 21-DEC-13:25 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5894.92 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22465.53 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 142.98 | 307.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2609.56 | 19-JAN-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.37 |
February | 2886.14 | 24-FEB-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.24 |
March | 5307.55 | 29-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.31 |
April | 8571.47 | 07-APR-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 |
May | 10085.61 | 30-MAY-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 0.00 |
June | 18413.27 | 25-JUN-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 |
July | 14447.86 | 04-JUL-16:22 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 |
August | 17871.48 | 13-AUG-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 | 0.00 |
September | 12173.96 | 10-SEP-15:42 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.36 |
October | 7861.67 | 04-OCT-15:20 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
November | 3557.67 | 03-NOV-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 |
December | 2517.20 | 08-DEC-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2517.20 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18413.27 | 805.38 | 1302.56 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 | 225.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1995.65 | 21-JAN-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.28 |
February | 1963.39 | 18-FEB-17:03 | 267.84 | 457.25 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.97 |
March | 2493.13 | 27-MAR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 0.00 |
April | 2976.81 | 07-APR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 | 0.00 |
May | 4633.20 | 30-MAY-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 0.00 |
June | 6465.61 | 19-JUN-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 59.78 | 0.00 |
July | 6774.75 | 10-JUL-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.02 | 0.00 |
August | 6924.64 | 17-AUG-13:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.62 | 0.00 |
September | 5984.91 | 01-SEP-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 0.00 |
October | 4307.67 | 05-OCT-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
November | 2828.80 | 03-NOV-14:03 | 3816.70 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 |
December | 2123.29 | 20-DEC-13:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1963.39 | 267.84 | 457.25 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6924.64 | 3816.70 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 68.02 | 70.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1707.62 | 27-JAN-10:20 | 2481.66 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 |
February | 1663.75 | 02-FEB-10:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.20 |
March | 2268.61 | 29-MAR-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.66 |
April | 3861.56 | 28-APR-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 |
May | 6816.27 | 30-MAY-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 | 0.00 |
June | 7273.09 | 26-JUN-08:40 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 0.00 |
July | 9322.91 | 09-JUL-09:32 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 0.00 |
August | 8736.12 | 13-AUG-09:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 27.13 | 0.00 |
September | 9271.05 | 04-SEP-09:12 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 |
October | 5286.23 | 05-OCT-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 |
November | 2343.32 | 03-NOV-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.77 |
December | 1891.98 | 20-DEC-09:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1663.75 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9322.91 | 2481.66 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 87.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2877.21 | 19-JAN-14:30 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1714.44 |
February | 2849.37 | 02-FEB-14:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2136.52 |
March | 4412.42 | 03-MAR-14:03 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1088.02 |
April | 7173.46 | 07-APR-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.12 | 0.00 |
May | 11849.40 | 30-MAY-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4365.53 | 0.00 |
June | 15558.11 | 19-JUN-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9268.87 | 0.00 |
July | 15051.36 | 07-JUL-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7441.95 | 0.00 |
August | 15211.42 | 18-AUG-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6471.47 | 0.00 |
September | 18036.42 | 10-SEP-13:52 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.05 |
October | 16180.72 | 22-OCT-12:43 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.22 |
November | 10437.68 | 02-NOV-12:07 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.20 |
December | 3141.71 | 02-DEC-14:10 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2849.37 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18036.42 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 9268.87 | 2136.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2058.36 | 20-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.93 |
February | 2117.78 | 02-FEB-16:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.18 |
March | 3264.94 | 27-MAR-16:50 | 254.33 | 723.64 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 |
April | 5365.09 | 10-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.54 |
May | 7061.89 | 30-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 |
June | 10125.29 | 18-JUN-16:31 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.53 |
July | 8082.59 | 01-JUL-17:08 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.07 |
August | 11938.19 | 13-AUG-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 40.60 | 0.00 |
September | 13987.26 | 10-SEP-17:12 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.00 |
October | 6987.09 | 04-OCT-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 |
November | 3342.70 | 03-NOV-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 |
December | 2080.26 | 08-DEC-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2058.36 | 0.00 | 361.82 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13987.26 | 805.38 | 1302.56 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 40.60 | 97.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2245.10 | 20-JAN-15:03 | 3816.70 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.59 |
February | 2278.42 | 24-FEB-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.19 |
March | 3019.33 | 27-MAR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 |
April | 4195.85 | 07-APR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 0.00 |
May | 6734.78 | 30-MAY-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.58 | 0.00 |
June | 10818.80 | 19-JUN-05:02 | 803.52 | 1371.75 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 |
July | 11104.10 | 10-JUL-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
August | 10374.71 | 05-AUG-04:01 | 0.00 | 800.19 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
September | 7997.32 | 01-SEP-05:02 | 803.52 | 1371.75 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
October | 4678.32 | 05-OCT-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 |
November | 3087.07 | 03-NOV-14:07 | 3816.70 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.71 |
December | 2311.15 | 20-DEC-13:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2245.10 | 0.00 | 800.19 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11104.10 | 3816.70 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 46.58 | 245.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2611.77 | 19-JAN-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.76 |
February | 2689.10 | 17-FEB-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.33 |
March | 4823.14 | 29-MAR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 |
April | 6919.01 | 07-APR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 |
May | 12833.16 | 29-MAY-08:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.48 |
June | 11233.04 | 25-JUN-09:22 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.32 |
July | 17525.98 | 02-JUL-08:31 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 |
August | 13317.64 | 27-AUG-09:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 |
September | 12817.87 | 04-SEP-09:12 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.43 |
October | 6726.34 | 04-OCT-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.63 |
November | 5151.56 | 01-NOV-12:02 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.12 |
December | 2744.14 | 20-DEC-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2611.77 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 | |
Maximum of Months | 17525.98 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6674.64 | 19-JAN-13:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.57 |
February | 7198.60 | 02-FEB-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.63 |
March | 9299.26 | 03-MAR-13:25 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.74 |
April | 10210.47 | 07-APR-12:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 | 0.00 |
May | 14263.67 | 29-MAY-12:13 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 71.49 | 0.00 |
June | 10702.37 | 19-JUN-12:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 116.13 | 0.00 |
July | 19457.80 | 09-JUL-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 158.46 | 0.00 |
August | 19400.41 | 20-AUG-13:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | 0.00 |
September | 19231.91 | 04-SEP-12:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.92 |
October | 18549.78 | 22-OCT-12:43 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 |
November | 11486.65 | 02-NOV-12:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.67 |
December | 7330.87 | 21-DEC-13:30 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6674.64 | 267.84 | 457.25 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19457.80 | 2544.47 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 158.46 | 255.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2538.81 | 20-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 |
February | 2780.98 | 24-FEB-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.16 |
March | 5347.19 | 29-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.38 |
April | 8071.27 | 07-APR-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 0.00 |
May | 9581.71 | 30-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 24.77 | 0.00 |
June | 13330.14 | 18-JUN-16:02 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.09 |
July | 17953.08 | 04-JUL-16:11 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.04 |
August | 16518.51 | 20-AUG-16:32 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.71 |
September | 12287.76 | 10-SEP-16:02 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.82 |
October | 7738.07 | 04-OCT-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
November | 3852.97 | 03-NOV-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 |
December | 2488.11 | 08-DEC-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2488.11 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17953.08 | 805.38 | 1302.56 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 24.77 | 193.16 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.154502E+12 | 128680.22 | 18-JAN-16:49 | 0.163572E+12 | 355511.19 | 02-JAN-05:10 |
February | 0.137335E+12 | 111537.17 | 24-FEB-16:10 | 0.139554E+12 | 316493.37 | 06-FEB-06:10 |
March | 0.160206E+12 | 129442.80 | 27-MAR-15:00 | 0.612116E+11 | 226819.58 | 20-MAR-05:10 |
April | 0.154790E+12 | 150300.67 | 07-APR-15:30 | 0.234003E+11 | 196525.13 | 03-APR-05:19 |
May | 0.178309E+12 | 177950.10 | 30-MAY-14:09 | 0.324114E+10 | 122919.49 | 01-MAY-06:10 |
June | 0.201600E+12 | 210606.72 | 19-JUN-14:09 | 35439077.98 | 4999.46 | 02-JUN-06:19 |
July | 0.218115E+12 | 205144.03 | 07-JUL-14:30 | 8581525.86 | 26.26 | 05-JUL-15:50 |
August | 0.233205E+12 | 209968.50 | 04-AUG-14:09 | 10034041.30 | 25.32 | 09-AUG-13:20 |
September | 0.188390E+12 | 187603.07 | 07-SEP-15:09 | 0.487178E+09 | 32406.62 | 29-SEP-06:10 |
October | 0.178294E+12 | 164032.53 | 04-OCT-15:30 | 0.515589E+10 | 120573.74 | 31-OCT-06:10 |
November | 0.154891E+12 | 137717.74 | 09-NOV-16:00 | 0.519327E+11 | 254831.26 | 24-NOV-06:10 |
December | 0.150241E+12 | 127177.49 | 19-DEC-16:30 | 0.982949E+11 | 227967.18 | 11-DEC-06:10 |
Annual Sum or Average | 0.210988E+13 | 0.546904E+12 | ||||
Minimum of Months | 0.137335E+12 | 111537.17 | 8581525.86 | 25.32 | ||
Maximum of Months | 0.233205E+12 | 210606.72 | 0.163572E+12 | 355511.19 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.243934E+11 | 0.613996E+11 | 0.230900E+10 | 0.115561E+11 | 0.800283E+09 | 0.00 | 0.182568E+10 | 0.00 | 0.00 | 0.00 | 0.496951E+10 | 0.00 |
February | 0.428574E+11 | 0.204569E+11 | 0.556056E+11 | 0.209511E+10 | 0.101918E+11 | 0.688655E+09 | 0.00 | 0.885834E+09 | 0.00 | 0.00 | 0.00 | 0.455367E+10 | 0.00 |
March | 0.509265E+11 | 0.204839E+11 | 0.635880E+11 | 0.240664E+10 | 0.107570E+11 | 0.293641E+09 | 0.00 | 0.649654E+10 | 0.00 | 0.00 | 0.00 | 0.525397E+10 | 0.00 |
April | 0.454877E+11 | 0.176555E+11 | 0.594055E+11 | 0.224272E+10 | 0.108759E+11 | 0.120066E+09 | 0.00 | 0.144884E+11 | 0.00 | 0.00 | 0.00 | 0.451461E+10 | 0.00 |
May | 0.490872E+11 | 0.163223E+11 | 0.624938E+11 | 0.235782E+10 | 0.141275E+11 | 30277424.19 | 0.00 | 0.293695E+11 | 0.00 | 0.00 | 0.00 | 0.452056E+10 | 0.00 |
June | 0.488499E+11 | 0.147819E+11 | 0.612808E+11 | 0.231841E+10 | 0.194141E+11 | 12403918.69 | 0.00 | 0.507614E+11 | 0.00 | 0.00 | 0.00 | 0.418075E+10 | 0.00 |
July | 0.457251E+11 | 0.157278E+11 | 0.606074E+11 | 0.228147E+10 | 0.225058E+11 | 12295634.37 | 0.00 | 0.674884E+11 | 0.00 | 0.00 | 0.00 | 0.376651E+10 | 0.00 |
August | 0.509265E+11 | 0.173672E+11 | 0.635880E+11 | 0.240664E+10 | 0.258474E+11 | 12722425.91 | 0.00 | 0.689677E+11 | 0.00 | 0.00 | 0.00 | 0.408911E+10 | 0.00 |
September | 0.454877E+11 | 0.188715E+11 | 0.593832E+11 | 0.224140E+10 | 0.174375E+11 | 13919859.69 | 0.00 | 0.411508E+11 | 0.00 | 0.00 | 0.00 | 0.380400E+10 | 0.00 |
October | 0.472479E+11 | 0.217541E+11 | 0.614108E+11 | 0.230966E+10 | 0.143213E+11 | 36232540.35 | 0.00 | 0.270461E+11 | 0.00 | 0.00 | 0.00 | 0.416837E+10 | 0.00 |
November | 0.466941E+11 | 0.230332E+11 | 0.599069E+11 | 0.224962E+10 | 0.101119E+11 | 0.255931E+09 | 0.00 | 0.824239E+10 | 0.00 | 0.00 | 0.00 | 0.439653E+10 | 0.00 |
December | 0.457251E+11 | 0.248708E+11 | 0.605962E+11 | 0.228081E+10 | 0.100408E+11 | 0.477624E+09 | 0.00 | 0.160892E+10 | 0.00 | 0.00 | 0.00 | 0.464088E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.235718E+12 | 0.729266E+12 | 0.274993E+11 | 0.177187E+12 | 0.275405E+10 | 0.00 | 0.318332E+12 | 0.00 | 0.00 | 0.00 | 0.528585E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.147819E+11 | 0.556056E+11 | 0.209511E+10 | 0.100408E+11 | 12295634.37 | 0.00 | 0.885834E+09 | 0.00 | 0.00 | 0.00 | 0.376651E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.248708E+11 | 0.635880E+11 | 0.240664E+10 | 0.258474E+11 | 0.800283E+09 | 0.00 | 0.689677E+11 | 0.00 | 0.00 | 0.00 | 0.525397E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.163572E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.139554E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.612116E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.234003E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.324114E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 35439077.98 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8581525.86 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 10034041.30 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.487178E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.515589E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.519327E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.982949E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.546904E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 8581525.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.163572E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 02-JAN-12:20 | 15913.66 | 02-JAN-06:10 | 1299.94 | 02-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 03-FEB-12:09 | 14654.01 | 06-FEB-07:10 | 1251.37 | 06-FEB-07:49 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 01-MAR-08:09 | 10455.00 | 29-MAR-15:30 | 1038.62 | 20-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 06-APR-16:10 | 17273.81 | 07-APR-15:20 | 902.91 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 11-MAY-16:10 | 27003.10 | 30-MAY-14:30 | 513.57 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 01-JUN-07:10 | 31084.47 | 19-JUN-14:30 | 32.80 | 02-JUN-06:19 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 15-JUL-10:09 | 31696.56 | 10-JUL-14:09 | 6.97 | 05-JUL-15:50 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 07-AUG-07:10 | 31743.94 | 14-AUG-14:20 | 6.97 | 09-AUG-13:20 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 12-SEP-07:19 | 28574.94 | 01-SEP-14:50 | 142.70 | 29-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 06-OCT-12:09 | 23163.59 | 04-OCT-15:30 | 559.18 | 31-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:09 | 12776.55 | 02-NOV-14:09 | 1068.41 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 06-DEC-13:09 | 10983.89 | 11-DEC-06:10 | 1040.71 | 11-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 10455.00 | 6.97 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 31743.94 | 1299.94 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 9456.32 | 24-JAN-11:00 | 0.00 | 0.00 | 0.00 | 6685.36 | 31-JAN-12:50 | 0.00 |
February | 6648.29 | 24-FEB-15:20 | 0.00 | 0.00 | 0.00 | 6688.63 | 06-FEB-12:39 | 0.00 |
March | 22710.97 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 6673.25 | 01-MAR-12:50 | 0.00 |
April | 35336.54 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 6265.12 | 03-APR-11:20 | 0.00 |
May | 55024.09 | 30-MAY-14:09 | 0.00 | 0.00 | 0.00 | 5952.89 | 02-MAY-11:20 | 0.00 |
June | 84116.79 | 19-JUN-11:00 | 0.00 | 0.00 | 0.00 | 5584.09 | 01-JUN-11:50 | 0.00 |
July | 79252.27 | 07-JUL-14:09 | 0.00 | 0.00 | 0.00 | 5274.27 | 03-JUL-11:39 | 0.00 |
August | 83721.75 | 04-AUG-14:09 | 0.00 | 0.00 | 0.00 | 5003.88 | 31-AUG-11:39 | 0.00 |
September | 65735.89 | 07-SEP-14:09 | 0.00 | 0.00 | 0.00 | 5367.27 | 29-SEP-11:20 | 0.00 |
October | 46125.46 | 04-OCT-14:09 | 0.00 | 0.00 | 0.00 | 5779.06 | 31-OCT-11:50 | 0.00 |
November | 21305.13 | 03-NOV-14:09 | 0.00 | 0.00 | 0.00 | 6208.39 | 30-NOV-12:50 | 0.00 |
December | 7584.93 | 20-DEC-13:00 | 0.00 | 0.00 | 0.00 | 6510.13 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6648.29 | 0.00 | 0.00 | 0.00 | 5003.88 | 0.00 | ||
Maximum of Months | 84116.79 | 0.00 | 0.00 | 0.00 | 6688.63 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 128680.22 | 18-JAN-16:49 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 6729.18 | 113.57 | 0.00 | 9018.19 | 0.00 |
February | 111537.17 | 24-FEB-16:10 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 7496.61 | 22.30 | 0.00 | 6233.68 | 0.00 |
March | 129442.80 | 27-MAR-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 8949.27 | 6.85 | 0.00 | 22710.97 | 0.00 |
April | 150300.67 | 07-APR-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 17261.13 | 6.85 | 0.00 | 35275.77 | 0.00 |
May | 177950.10 | 30-MAY-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 26920.87 | 6.85 | 0.00 | 55024.09 | 0.00 |
June | 210606.72 | 19-JUN-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 30944.72 | 6.94 | 0.00 | 83674.26 | 0.00 |
July | 205144.03 | 07-JUL-14:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 30373.17 | 6.94 | 0.00 | 79084.97 | 0.00 |
August | 209968.50 | 04-AUG-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 30568.26 | 6.94 | 0.00 | 83721.75 | 0.00 |
September | 187603.07 | 07-SEP-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 28102.05 | 6.93 | 0.00 | 62826.10 | 0.00 |
October | 164032.53 | 04-OCT-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 23163.59 | 6.95 | 0.00 | 43848.71 | 0.00 |
November | 137717.74 | 09-NOV-16:00 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 8960.64 | 6.85 | 0.00 | 16356.05 | 0.00 |
December | 127177.49 | 19-DEC-16:30 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 7513.72 | 35.29 | 0.00 | 6848.20 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 111537.17 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 6729.18 | 6.85 | 0.00 | 6233.68 | 0.00 | |
Maximum of Months | 210606.72 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 30944.72 | 113.57 | 0.00 | 83721.75 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 355511.19 | 02-JAN-05:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 316493.37 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 226819.58 | 20-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 196525.13 | 03-APR-05:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 122919.49 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4999.46 | 02-JUN-06:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 26.26 | 05-JUL-15:50 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 25.32 | 09-AUG-13:20 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 32406.62 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 120573.74 | 31-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 254831.26 | 24-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 227967.18 | 11-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 25.32 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 355511.19 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 19.07 | 2.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.00 | 19.07 | 2.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.07 | 2.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 18.81 | 2.83 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 0.50 | 19.53 | 0.50 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 18.90 | 3.33 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.53 | 2.83 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.83 | 18.66 | 4.67 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 4.33 | 19.04 | 3.67 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
March | 0.33 | 19.38 | 0.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 18.10 | 0.50 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
December | 0.33 | 18.94 | 0.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Annual Sum or Average | 11.67 | 18.79 | 9.50 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.83 | 19.38 | 4.67 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.17 | 15.29 | 12.83 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
February | 28.33 | 15.59 | 11.50 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
March | 1.50 | 16.88 | 0.17 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
April | 0.17 | 18.95 | 0.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.67 | 15.78 | 1.00 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
December | 9.17 | 15.92 | 4.50 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
Annual Sum or Average | 82.00 | 15.53 | 30.17 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.17 | 18.95 | 12.83 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.33 | 15.26 | 11.67 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
February | 24.17 | 15.50 | 7.17 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
March | 1.67 | 16.67 | 0.33 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
April | 0.17 | 19.02 | 0.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.91 | 1.50 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.95 | 0.83 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.98 | 4.17 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.75 | 3.00 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.86 | 2.00 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.50 | 15.81 | 0.83 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
December | 8.50 | 16.05 | 3.00 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
Annual Sum or Average | 77.33 | 15.49 | 23.17 | 15.77 | 11.50 | 17.01 | 11.50 | 18.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.33 | 19.02 | 11.67 | 19.02 | 4.17 | 27.98 | 4.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.50 | 15.46 | 9.67 | 15.75 | 0.00 | 15.75 | 0.00 | 15.75 |
February | 20.33 | 15.77 | 5.33 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
March | 1.17 | 17.23 | 0.17 | 17.49 | 0.00 | 17.49 | 0.00 | 17.49 |
April | 0.17 | 19.08 | 0.17 | 19.08 | 0.17 | 21.82 | 0.17 | 23.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.65 | 2.83 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.99 | 3.17 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.05 | 4.00 | 28.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
November | 3.00 | 16.17 | 0.50 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
December | 6.50 | 16.31 | 2.00 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
Annual Sum or Average | 60.67 | 15.73 | 17.83 | 16.08 | 11.50 | 17.58 | 11.50 | 18.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.50 | 19.08 | 9.67 | 19.08 | 4.00 | 28.05 | 4.00 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.33 | 15.22 | 12.50 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
February | 25.83 | 15.49 | 8.67 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
March | 1.50 | 16.92 | 0.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
April | 0.17 | 19.16 | 0.17 | 19.16 | 0.50 | 24.05 | 0.50 | 25.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.50 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.11 | 1.83 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.16 | 3.83 | 28.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.24 | 1.83 | 28.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.82 | 2.17 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.83 | 15.77 | 1.00 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
December | 8.17 | 15.89 | 3.17 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
Annual Sum or Average | 77.83 | 15.45 | 25.67 | 15.69 | 13.00 | 17.07 | 10.67 | 17.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.33 | 19.16 | 12.50 | 19.16 | 4.67 | 28.24 | 3.83 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.00 | 16.21 | 7.00 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
February | 8.50 | 17.34 | 3.83 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.50 | 16.66 | 10.83 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.00 | 17.34 | 7.00 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.00 | 15.92 | 4.17 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
February | 4.50 | 16.67 | 1.17 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.50 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.68 | 1.83 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 1.00 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.65 | 1.50 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.50 | 16.15 | 5.33 | 16.56 | 4.83 | 18.73 | 4.83 | 20.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.00 | 16.67 | 4.17 | 17.26 | 1.83 | 27.68 | 1.83 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.67 | 17.71 | 69.50 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
February | 64.17 | 17.73 | 63.33 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 |
March | 45.17 | 18.64 | 45.17 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
April | 17.50 | 19.23 | 17.50 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
May | 1.67 | 19.94 | 1.67 | 19.94 | 0.00 | 19.94 | 0.00 | 19.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.80 | 0.83 | 24.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.22 | 2.50 | 27.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.79 | 4.00 | 27.79 |
October | 3.00 | 20.26 | 3.00 | 20.26 | 1.50 | 21.72 | 1.50 | 22.70 |
November | 28.67 | 19.15 | 28.67 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
December | 51.33 | 18.63 | 51.33 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
Annual Sum or Average | 286.17 | 18.30 | 280.17 | 18.34 | 8.83 | 18.47 | 8.83 | 18.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.67 | 20.26 | 69.50 | 20.26 | 4.00 | 27.79 | 4.00 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.00 | 16.10 | 6.17 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
February | 6.00 | 17.04 | 2.33 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.66 | 0.33 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.56 | 1.17 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.77 | 1.17 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.62 | 1.17 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.00 | 16.41 | 8.50 | 16.86 | 5.50 | 18.72 | 4.00 | 19.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.00 | 17.04 | 6.17 | 17.76 | 1.67 | 27.77 | 1.17 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.50 | 15.78 | 6.67 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
February | 10.17 | 16.50 | 3.50 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
March | 0.17 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
December | 1.50 | 15.25 | 0.17 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
Annual Sum or Average | 26.50 | 16.04 | 10.33 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.50 | 17.13 | 6.67 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.67 | 15.56 | 4.83 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 7.67 | 15.98 | 1.67 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
March | 0.17 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.01 | 1.67 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.89 | 1.00 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.13 | 3.17 | 28.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.82 | 2.17 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.04 | 2.33 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
December | 1.33 | 15.30 | 0.17 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
Annual Sum or Average | 23.00 | 15.70 | 6.67 | 16.04 | 10.33 | 19.13 | 10.33 | 20.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.67 | 17.11 | 4.83 | 17.11 | 3.17 | 28.13 | 3.17 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.17 | 15.83 | 3.83 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
February | 6.00 | 16.73 | 2.00 | 17.37 | 0.00 | 17.37 | 0.00 | 17.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.57 | 2.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.89 | 3.17 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.00 | 4.67 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.70 | 1.67 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 15.85 | 0.17 | 16.43 | 0.17 | 17.99 | 0.17 | 19.16 |
Annual Sum or Average | 18.00 | 16.13 | 6.00 | 16.63 | 12.67 | 20.50 | 12.67 | 22.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.17 | 16.73 | 3.83 | 17.37 | 4.67 | 28.00 | 4.67 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.33 | 15.60 | 6.33 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
February | 8.67 | 16.24 | 2.83 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
March | 0.17 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.42 | 0.17 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.90 | 1.83 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.98 | 3.33 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.11 | 1.50 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.90 | 1.83 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
December | 1.17 | 15.36 | 0.17 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
Annual Sum or Average | 24.67 | 15.84 | 9.33 | 16.17 | 10.67 | 18.99 | 8.67 | 20.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.33 | 17.10 | 6.33 | 17.10 | 4.17 | 28.11 | 3.33 | 28.14 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.83 | 22.60 | 53.83 | 22.35 | 53.83 | 22.14 |
February | 454.00 | 23.13 | 6.33 | 23.10 | 6.33 | 23.07 |
March | 426.00 | 23.70 | 0.83 | 23.70 | 0.00 | 23.70 |
April | 193.00 | 23.74 | 70.67 | 24.07 | 0.00 | 24.07 |
May | 14.67 | 23.80 | 277.83 | 24.61 | 0.00 | 24.61 |
June | 0.00 | 0.00 | 464.67 | 24.49 | 0.00 | 24.49 |
July | 0.00 | 0.00 | 497.00 | 24.50 | 0.00 | 24.50 |
August | 0.00 | 0.00 | 508.33 | 24.46 | 0.00 | 24.46 |
September | 0.00 | 0.00 | 435.67 | 24.52 | 0.00 | 24.52 |
October | 26.17 | 24.01 | 306.00 | 24.52 | 0.00 | 24.52 |
November | 262.33 | 23.63 | 66.17 | 23.97 | 0.00 | 23.97 |
December | 493.33 | 23.55 | 0.00 | 23.55 | 0.00 | 23.55 |
Annual Sum or Average | 2370.33 | 23.33 | 2687.33 | 23.92 | 60.17 | 23.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.35 | 0.00 | 22.14 |
Maximum of Months | 500.83 | 24.01 | 508.33 | 24.61 | 53.83 | 24.61 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.20 | 170.33 | 20.90 | 170.33 | 20.73 |
February | 454.00 | 21.53 | 138.33 | 21.32 | 138.33 | 21.20 |
March | 509.50 | 22.50 | 16.17 | 22.45 | 16.17 | 22.40 |
April | 388.33 | 22.92 | 18.67 | 22.97 | 1.83 | 22.96 |
May | 204.50 | 23.39 | 118.17 | 23.71 | 0.00 | 23.71 |
June | 14.00 | 23.65 | 420.67 | 24.27 | 0.00 | 24.27 |
July | 0.00 | 0.00 | 496.33 | 24.32 | 0.00 | 24.32 |
August | 0.00 | 0.00 | 485.17 | 24.33 | 0.00 | 24.33 |
September | 56.17 | 23.52 | 322.00 | 24.19 | 0.00 | 24.19 |
October | 208.83 | 23.36 | 150.00 | 23.70 | 0.00 | 23.70 |
November | 458.00 | 22.50 | 41.33 | 22.35 | 41.33 | 22.23 |
December | 497.00 | 21.78 | 81.17 | 21.60 | 81.17 | 21.47 |
Annual Sum or Average | 3292.33 | 22.24 | 2458.33 | 22.82 | 449.17 | 22.64 |
Minimum of Months | 0.00 | 0.00 | 16.17 | 20.90 | 0.00 | 20.73 |
Maximum of Months | 509.50 | 23.65 | 496.33 | 24.33 | 170.33 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.43 | 319.50 | 20.23 | 319.50 | 20.14 |
February | 454.00 | 20.64 | 312.17 | 20.47 | 312.17 | 20.40 |
March | 508.83 | 21.54 | 117.83 | 21.33 | 117.83 | 21.17 |
April | 420.67 | 22.17 | 51.33 | 22.09 | 35.67 | 21.95 |
May | 286.00 | 22.91 | 102.67 | 23.21 | 0.83 | 23.21 |
June | 41.50 | 23.28 | 363.83 | 24.14 | 0.00 | 24.14 |
July | 2.50 | 23.21 | 472.50 | 24.30 | 0.00 | 24.30 |
August | 16.33 | 23.33 | 444.50 | 24.26 | 0.00 | 24.26 |
September | 156.33 | 23.08 | 221.33 | 23.72 | 0.00 | 23.72 |
October | 354.50 | 22.56 | 102.00 | 22.72 | 21.00 | 22.62 |
November | 486.83 | 21.43 | 129.83 | 21.16 | 129.83 | 20.98 |
December | 497.00 | 20.71 | 306.00 | 20.51 | 306.00 | 20.43 |
Annual Sum or Average | 3726.50 | 21.52 | 2943.50 | 21.96 | 1242.83 | 21.67 |
Minimum of Months | 2.50 | 20.43 | 51.33 | 20.23 | 0.00 | 20.14 |
Maximum of Months | 508.83 | 23.33 | 472.50 | 24.30 | 319.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 454.50 | 19.78 | 454.50 | 19.76 |
February | 454.00 | 19.98 | 425.33 | 19.94 | 425.33 | 19.93 |
March | 514.00 | 20.53 | 291.67 | 20.36 | 291.67 | 20.27 |
April | 459.17 | 21.13 | 135.00 | 20.94 | 128.00 | 20.78 |
May | 384.33 | 21.95 | 73.50 | 22.21 | 9.17 | 22.17 |
June | 146.50 | 22.72 | 292.67 | 23.64 | 12.00 | 23.66 |
July | 73.17 | 23.89 | 414.83 | 24.16 | 36.50 | 24.23 |
August | 104.00 | 23.25 | 369.33 | 23.98 | 23.67 | 24.06 |
September | 292.67 | 22.20 | 141.67 | 22.75 | 12.50 | 22.75 |
October | 447.83 | 21.38 | 109.83 | 21.31 | 79.17 | 21.14 |
November | 489.00 | 20.36 | 282.33 | 20.17 | 282.33 | 20.07 |
December | 497.00 | 19.95 | 472.67 | 19.92 | 472.67 | 19.92 |
Annual Sum or Average | 4363.67 | 20.89 | 3463.33 | 21.16 | 2227.50 | 20.92 |
Minimum of Months | 73.17 | 19.84 | 73.50 | 19.78 | 9.17 | 19.76 |
Maximum of Months | 514.00 | 23.89 | 472.67 | 24.16 | 472.67 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.85 | 430.17 | 19.76 | 430.17 | 19.73 |
February | 454.00 | 20.07 | 392.83 | 20.00 | 392.83 | 19.98 |
March | 509.67 | 20.75 | 218.83 | 20.47 | 218.83 | 20.32 |
April | 385.00 | 21.25 | 173.00 | 21.44 | 103.83 | 21.24 |
May | 290.50 | 22.00 | 175.83 | 22.86 | 10.17 | 22.89 |
June | 120.67 | 23.08 | 338.50 | 23.92 | 19.33 | 24.00 |
July | 87.33 | 24.90 | 438.17 | 24.46 | 61.50 | 24.60 |
August | 84.33 | 24.10 | 426.00 | 24.25 | 36.00 | 24.37 |
September | 219.83 | 22.38 | 227.50 | 23.32 | 20.17 | 23.38 |
October | 385.33 | 21.67 | 134.00 | 21.94 | 43.67 | 21.78 |
November | 489.00 | 20.54 | 237.00 | 20.27 | 237.00 | 20.14 |
December | 497.00 | 20.03 | 434.00 | 19.96 | 434.00 | 19.94 |
Annual Sum or Average | 4024.67 | 20.99 | 3625.83 | 21.47 | 2007.50 | 21.21 |
Minimum of Months | 84.33 | 19.85 | 134.00 | 19.76 | 10.17 | 19.73 |
Maximum of Months | 509.67 | 24.90 | 438.17 | 24.46 | 434.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.83 | 20.18 | 357.33 | 19.92 | 357.33 | 19.82 |
February | 438.00 | 20.48 | 311.67 | 20.22 | 311.67 | 20.12 |
March | 445.67 | 20.80 | 233.00 | 20.67 | 205.67 | 20.50 |
April | 379.33 | 21.17 | 169.00 | 21.37 | 102.17 | 21.17 |
May | 328.17 | 21.91 | 136.17 | 22.53 | 11.50 | 22.51 |
June | 147.50 | 22.74 | 303.83 | 23.71 | 14.33 | 23.74 |
July | 92.17 | 24.32 | 416.50 | 24.31 | 53.50 | 24.43 |
August | 101.33 | 23.86 | 407.00 | 24.21 | 37.17 | 24.34 |
September | 219.17 | 22.61 | 248.17 | 23.50 | 26.67 | 23.60 |
October | 289.67 | 21.75 | 204.17 | 22.51 | 39.33 | 22.37 |
November | 444.17 | 20.79 | 215.50 | 20.59 | 195.00 | 20.41 |
December | 479.67 | 20.43 | 337.17 | 20.20 | 334.50 | 20.09 |
Annual Sum or Average | 3859.67 | 21.18 | 3339.50 | 21.66 | 1688.83 | 21.39 |
Minimum of Months | 92.17 | 20.18 | 136.17 | 19.92 | 11.50 | 19.82 |
Maximum of Months | 494.83 | 24.32 | 416.50 | 24.31 | 357.33 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.90 | 429.83 | 19.81 | 429.83 | 19.77 |
February | 454.00 | 20.11 | 383.17 | 20.01 | 383.17 | 19.97 |
March | 491.00 | 20.72 | 252.50 | 20.53 | 243.17 | 20.40 |
April | 407.83 | 21.08 | 166.33 | 21.18 | 112.83 | 21.00 |
May | 345.83 | 21.85 | 133.83 | 22.46 | 10.67 | 22.44 |
June | 154.67 | 22.82 | 310.17 | 23.76 | 21.67 | 23.84 |
July | 104.00 | 24.14 | 409.83 | 24.27 | 54.50 | 24.40 |
August | 105.00 | 23.49 | 396.67 | 24.11 | 30.83 | 24.22 |
September | 274.50 | 22.24 | 181.17 | 22.99 | 19.83 | 23.04 |
October | 391.33 | 21.43 | 139.83 | 21.65 | 60.33 | 21.47 |
November | 485.17 | 20.44 | 267.83 | 20.22 | 266.67 | 20.11 |
December | 497.00 | 20.04 | 434.67 | 19.97 | 434.67 | 19.94 |
Annual Sum or Average | 4212.33 | 20.97 | 3505.83 | 21.36 | 2068.17 | 21.11 |
Minimum of Months | 104.00 | 19.90 | 133.83 | 19.81 | 10.67 | 19.77 |
Maximum of Months | 502.00 | 24.14 | 434.67 | 24.27 | 434.67 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 449.50 | 20.06 | 449.50 | 20.04 |
February | 454.00 | 20.20 | 438.83 | 20.18 | 438.83 | 20.18 |
March | 514.00 | 20.67 | 311.17 | 20.57 | 311.17 | 20.52 |
April | 484.17 | 21.22 | 121.33 | 21.06 | 121.33 | 20.94 |
May | 462.50 | 22.11 | 28.17 | 22.20 | 3.17 | 22.18 |
June | 145.50 | 23.09 | 282.00 | 23.76 | 14.83 | 23.78 |
July | 37.67 | 24.87 | 444.00 | 24.24 | 32.67 | 24.30 |
August | 45.17 | 23.78 | 428.67 | 24.15 | 14.83 | 24.18 |
September | 178.33 | 22.89 | 217.17 | 23.54 | 6.83 | 23.56 |
October | 396.50 | 22.27 | 72.33 | 22.46 | 8.17 | 22.43 |
November | 489.00 | 21.07 | 154.50 | 20.87 | 154.50 | 20.75 |
December | 497.00 | 20.44 | 437.17 | 20.41 | 437.17 | 20.39 |
Annual Sum or Average | 4205.83 | 21.19 | 3384.83 | 21.52 | 1993.00 | 21.28 |
Minimum of Months | 37.67 | 20.10 | 28.17 | 20.06 | 3.17 | 20.04 |
Maximum of Months | 514.00 | 24.87 | 449.50 | 24.24 | 449.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 419.17 | 20.07 | 419.17 | 20.04 |
February | 454.00 | 20.38 | 394.33 | 20.33 | 394.33 | 20.31 |
March | 514.00 | 20.92 | 207.00 | 20.72 | 207.00 | 20.61 |
April | 419.33 | 21.54 | 101.17 | 21.55 | 71.00 | 21.41 |
May | 319.33 | 22.08 | 123.67 | 22.77 | 3.33 | 22.77 |
June | 98.00 | 23.21 | 346.33 | 24.00 | 15.83 | 24.05 |
July | 48.17 | 25.70 | 470.00 | 24.47 | 45.50 | 24.58 |
August | 27.83 | 25.31 | 479.17 | 24.36 | 21.83 | 24.43 |
September | 123.33 | 23.08 | 322.17 | 23.97 | 14.17 | 24.03 |
October | 279.83 | 22.56 | 143.00 | 23.06 | 2.83 | 23.04 |
November | 486.00 | 21.33 | 126.17 | 21.12 | 126.17 | 20.97 |
December | 497.00 | 20.57 | 340.33 | 20.47 | 340.33 | 20.42 |
Annual Sum or Average | 3768.83 | 21.27 | 3472.50 | 21.84 | 1661.50 | 21.60 |
Minimum of Months | 27.83 | 20.15 | 101.17 | 20.07 | 2.83 | 20.04 |
Maximum of Months | 514.00 | 25.70 | 479.17 | 24.47 | 419.17 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 349.50 | 19.78 | 349.50 | 19.68 |
February | 452.33 | 20.36 | 306.83 | 20.12 | 306.83 | 20.02 |
March | 496.17 | 20.86 | 182.00 | 20.60 | 181.67 | 20.45 |
April | 423.50 | 21.30 | 112.50 | 21.31 | 78.83 | 21.14 |
May | 398.83 | 21.96 | 59.67 | 22.27 | 4.83 | 22.24 |
June | 164.33 | 23.06 | 309.33 | 23.75 | 49.00 | 23.77 |
July | 104.83 | 24.35 | 471.50 | 24.30 | 100.00 | 24.32 |
August | 68.33 | 24.42 | 476.83 | 24.36 | 55.00 | 24.40 |
September | 122.67 | 23.40 | 356.67 | 24.13 | 42.83 | 24.21 |
October | 164.67 | 22.59 | 263.33 | 23.73 | 7.00 | 23.77 |
November | 430.83 | 21.35 | 118.17 | 21.25 | 91.33 | 21.06 |
December | 483.67 | 20.71 | 276.67 | 20.53 | 268.17 | 20.40 |
Annual Sum or Average | 3812.17 | 21.30 | 3283.00 | 21.88 | 1535.00 | 21.65 |
Minimum of Months | 68.33 | 20.01 | 59.67 | 19.78 | 4.83 | 19.68 |
Maximum of Months | 502.00 | 24.42 | 476.83 | 24.36 | 349.50 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.18 | 419.17 | 20.10 | 419.17 | 20.07 |
February | 454.00 | 20.37 | 395.33 | 20.30 | 395.33 | 20.28 |
March | 506.50 | 20.96 | 226.00 | 20.80 | 224.00 | 20.71 |
April | 432.67 | 21.37 | 109.17 | 21.36 | 81.67 | 21.22 |
May | 374.67 | 22.09 | 92.67 | 22.55 | 3.17 | 22.53 |
June | 100.00 | 23.23 | 347.67 | 24.03 | 18.17 | 24.08 |
July | 51.00 | 25.29 | 456.17 | 24.43 | 42.17 | 24.54 |
August | 31.33 | 24.76 | 473.50 | 24.35 | 19.50 | 24.41 |
September | 140.33 | 22.91 | 282.83 | 23.80 | 12.00 | 23.86 |
October | 290.33 | 22.41 | 142.50 | 22.94 | 2.83 | 22.93 |
November | 482.83 | 21.14 | 147.17 | 20.95 | 146.17 | 20.82 |
December | 497.00 | 20.57 | 373.00 | 20.48 | 373.00 | 20.44 |
Annual Sum or Average | 3862.67 | 21.25 | 3465.17 | 21.77 | 1737.17 | 21.53 |
Minimum of Months | 31.33 | 20.18 | 92.67 | 20.10 | 2.83 | 20.07 |
Maximum of Months | 506.50 | 25.29 | 473.50 | 24.43 | 419.17 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.03 | 409.17 | 19.94 | 409.17 | 19.90 |
February | 454.00 | 20.19 | 399.17 | 20.14 | 399.17 | 20.12 |
March | 514.00 | 20.84 | 220.83 | 20.67 | 220.83 | 20.58 |
April | 450.50 | 21.54 | 76.50 | 21.44 | 63.83 | 21.30 |
May | 342.83 | 22.47 | 93.83 | 22.80 | 2.00 | 22.79 |
June | 80.33 | 23.26 | 357.00 | 23.99 | 12.67 | 24.01 |
July | 39.67 | 25.37 | 474.33 | 24.35 | 39.00 | 24.43 |
August | 52.33 | 24.28 | 441.50 | 24.24 | 24.17 | 24.31 |
September | 201.33 | 22.69 | 204.50 | 23.39 | 9.17 | 23.42 |
October | 406.50 | 22.01 | 87.83 | 22.14 | 27.83 | 22.05 |
November | 489.00 | 20.84 | 188.50 | 20.62 | 188.50 | 20.49 |
December | 497.00 | 20.27 | 427.67 | 20.22 | 427.67 | 20.20 |
Annual Sum or Average | 4029.50 | 21.16 | 3380.83 | 21.57 | 1824.00 | 21.32 |
Minimum of Months | 39.67 | 20.03 | 76.50 | 19.94 | 2.00 | 19.90 |
Maximum of Months | 514.00 | 25.37 | 474.33 | 24.35 | 427.67 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.90 | 350.00 | 19.78 | 350.00 | 19.74 |
February | 385.00 | 20.23 | 304.17 | 20.12 | 304.17 | 20.08 |
March | 424.83 | 20.98 | 149.50 | 20.73 | 149.00 | 20.58 |
April | 331.00 | 21.55 | 95.00 | 21.80 | 42.50 | 21.65 |
May | 253.00 | 22.36 | 140.83 | 23.13 | 7.17 | 23.19 |
June | 87.00 | 23.22 | 292.00 | 24.05 | 15.50 | 24.11 |
July | 62.83 | 25.52 | 385.00 | 24.57 | 54.33 | 24.72 |
August | 61.00 | 24.70 | 370.67 | 24.40 | 34.50 | 24.53 |
September | 169.00 | 22.79 | 205.67 | 23.64 | 20.17 | 23.75 |
October | 306.50 | 22.05 | 94.33 | 22.37 | 17.50 | 22.29 |
November | 415.33 | 20.94 | 150.83 | 20.67 | 150.83 | 20.52 |
December | 422.00 | 20.27 | 316.83 | 20.15 | 316.83 | 20.10 |
Annual Sum or Average | 3344.50 | 21.22 | 2854.83 | 21.71 | 1462.50 | 21.47 |
Minimum of Months | 61.00 | 19.90 | 94.33 | 19.78 | 7.17 | 19.74 |
Maximum of Months | 427.00 | 25.52 | 385.00 | 24.57 | 350.00 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.33 | 20.48 | 302.00 | 20.18 | 302.00 | 20.04 |
February | 420.33 | 20.85 | 260.67 | 20.60 | 258.17 | 20.47 |
March | 428.17 | 21.19 | 161.50 | 21.12 | 130.17 | 20.94 |
April | 362.00 | 21.62 | 118.00 | 21.90 | 47.50 | 21.74 |
May | 289.33 | 22.45 | 156.00 | 23.08 | 3.33 | 23.08 |
June | 79.00 | 23.32 | 368.17 | 24.06 | 15.33 | 24.09 |
July | 57.17 | 25.62 | 473.33 | 24.49 | 54.50 | 24.61 |
August | 55.83 | 25.17 | 462.67 | 24.44 | 38.00 | 24.56 |
September | 142.83 | 23.27 | 306.67 | 24.00 | 26.17 | 24.12 |
October | 226.50 | 22.40 | 230.83 | 23.31 | 18.67 | 23.28 |
November | 414.00 | 21.32 | 153.50 | 21.22 | 118.67 | 21.01 |
December | 452.67 | 20.83 | 274.33 | 20.64 | 265.67 | 20.51 |
Annual Sum or Average | 3411.17 | 21.52 | 3267.67 | 22.16 | 1278.17 | 21.92 |
Minimum of Months | 55.83 | 20.48 | 118.00 | 20.18 | 3.33 | 20.04 |
Maximum of Months | 483.33 | 25.62 | 473.33 | 24.49 | 302.00 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.12 | 382.50 | 19.98 | 382.50 | 19.93 |
February | 454.00 | 20.38 | 347.00 | 20.24 | 347.00 | 20.18 |
March | 487.00 | 21.00 | 185.33 | 20.85 | 176.83 | 20.72 |
April | 400.67 | 21.40 | 111.50 | 21.58 | 57.67 | 21.44 |
May | 318.67 | 22.18 | 135.67 | 22.79 | 2.50 | 22.79 |
June | 103.00 | 23.16 | 351.33 | 23.99 | 19.33 | 24.06 |
July | 72.00 | 25.00 | 445.17 | 24.41 | 52.83 | 24.54 |
August | 66.00 | 24.33 | 439.00 | 24.30 | 32.00 | 24.41 |
September | 216.50 | 22.60 | 215.17 | 23.40 | 16.50 | 23.48 |
October | 356.50 | 21.90 | 121.17 | 22.27 | 23.83 | 22.18 |
November | 481.33 | 20.84 | 184.17 | 20.63 | 182.33 | 20.50 |
December | 497.00 | 20.39 | 378.17 | 20.28 | 378.17 | 20.24 |
Annual Sum or Average | 3954.67 | 21.21 | 3296.17 | 21.70 | 1671.50 | 21.47 |
Minimum of Months | 66.00 | 20.12 | 111.50 | 19.98 | 2.50 | 19.93 |
Maximum of Months | 502.00 | 25.00 | 445.17 | 24.41 | 382.50 | 24.54 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60662 | 22.82462 | -0.1742 | 8.07673 |
February | 454.00000 | 23.13094 | 19.56678 | -0.0590 | 5.74183 |
March | 514.00000 | 23.79351 | 27.06430 | 0.17694 | 5.99038 |
April | 485.00000 | 24.11435 | 32.72257 | 0.31556 | 7.49093 |
May | 508.00000 | 24.36691 | 39.80561 | -0.4043 | 8.93834 |
June | 496.00000 | 24.46060 | 49.84467 | -0.2421 | 6.86799 |
July | 497.00000 | 24.49797 | 53.70339 | -0.1892 | 6.42673 |
August | 514.00000 | 24.45030 | 51.02776 | -0.2127 | 6.60659 |
September | 485.00000 | 24.47038 | 46.41415 | -0.2703 | 7.15874 |
October | 502.00000 | 24.43779 | 38.70289 | 0.47996 | 10.23669 |
November | 489.00000 | 24.00688 | 29.76251 | 0.25432 | 7.09975 |
December | 497.00000 | 23.55984 | 22.73839 | 0.07543 | 5.41235 |
Annual Sum or Average | 5943.00000 | 23.99690 | 36.30833 | -0.0214 | 7.18207 |
Minimum of Months | 454.00000 | 22.60662 | 19.56678 | -0.4043 | 5.41235 |
Maximum of Months | 514.00000 | 24.49797 | 53.70339 | 0.47996 | 10.23669 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.19843 | 25.25217 | -0.4975 | 12.55720 |
February | 454.00000 | 21.53215 | 20.69883 | -0.4364 | 10.14005 |
March | 514.00000 | 22.51106 | 29.52878 | -0.1242 | 6.27754 |
April | 485.00000 | 23.16851 | 34.95495 | 0.08842 | 6.33631 |
May | 508.00000 | 23.82515 | 41.00516 | -0.6022 | 13.44971 |
June | 496.00000 | 24.23098 | 50.57407 | -0.3447 | 7.86794 |
July | 497.00000 | 24.31949 | 54.70053 | -0.2706 | 6.92293 |
August | 514.00000 | 24.31629 | 51.93103 | -0.2852 | 7.14926 |
September | 485.00000 | 24.13744 | 46.80746 | -0.4221 | 9.33330 |
October | 502.00000 | 23.80780 | 39.74148 | 0.30187 | 7.69424 |
November | 489.00000 | 22.59498 | 32.21423 | -0.0898 | 6.84333 |
December | 497.00000 | 21.77881 | 24.91643 | -0.3426 | 8.43491 |
Annual Sum or Average | 5943.00000 | 23.13022 | 37.82382 | -0.2514 | 8.57902 |
Minimum of Months | 454.00000 | 21.19843 | 20.69883 | -0.6022 | 6.27754 |
Maximum of Months | 514.00000 | 24.31949 | 54.70053 | 0.30187 | 13.44971 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.43471 | 25.92766 | -0.7102 | 18.30855 |
February | 454.00000 | 20.64428 | 20.78125 | -0.6778 | 16.83926 |
March | 514.00000 | 21.56942 | 30.37794 | -0.3559 | 9.25865 |
April | 485.00000 | 22.41935 | 35.40215 | -0.0916 | 7.34669 |
May | 508.00000 | 23.41137 | 40.62206 | -0.7346 | 18.27183 |
June | 496.00000 | 24.09417 | 49.62556 | -0.3810 | 8.70480 |
July | 497.00000 | 24.27008 | 54.10479 | -0.2676 | 6.92197 |
August | 514.00000 | 24.22107 | 51.31749 | -0.3033 | 7.52789 |
September | 485.00000 | 23.76530 | 46.04663 | -0.5536 | 12.93268 |
October | 502.00000 | 22.97754 | 40.06195 | 0.09461 | 7.26323 |
November | 489.00000 | 21.43982 | 33.24096 | -0.3821 | 10.30224 |
December | 497.00000 | 20.70794 | 25.85798 | -0.6273 | 15.01262 |
Annual Sum or Average | 5943.00000 | 22.51105 | 37.91051 | -0.4143 | 11.52360 |
Minimum of Months | 454.00000 | 20.43471 | 20.78125 | -0.7346 | 6.92197 |
Maximum of Months | 514.00000 | 24.27008 | 54.10479 | 0.09461 | 18.30855 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83742 | 25.78794 | -0.9270 | 26.00816 |
February | 454.00000 | 19.97610 | 20.61268 | -0.9137 | 25.05012 |
March | 514.00000 | 20.52874 | 31.10228 | -0.6295 | 15.23194 |
April | 485.00000 | 21.27296 | 37.06818 | -0.3494 | 10.26260 |
May | 508.00000 | 22.41107 | 42.90907 | -0.9975 | 29.21727 |
June | 496.00000 | 23.60283 | 52.32568 | -0.4622 | 11.56097 |
July | 497.00000 | 23.99994 | 57.22510 | -0.2621 | 7.69828 |
August | 514.00000 | 23.84210 | 53.69544 | -0.3502 | 9.48778 |
September | 485.00000 | 22.84407 | 49.44870 | -0.7906 | 21.56267 |
October | 502.00000 | 21.61574 | 42.89119 | -0.1947 | 8.82512 |
November | 489.00000 | 20.36432 | 34.39118 | -0.6602 | 16.59432 |
December | 497.00000 | 19.95081 | 26.22678 | -0.8736 | 23.44249 |
Annual Sum or Average | 5943.00000 | 21.70209 | 39.61400 | -0.6154 | 17.02313 |
Minimum of Months | 454.00000 | 19.83742 | 20.61268 | -0.9975 | 7.69828 |
Maximum of Months | 514.00000 | 23.99994 | 57.22510 | -0.1947 | 29.21727 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.85023 | 26.01458 | -0.8987 | 25.09439 |
February | 454.00000 | 20.07031 | 20.73231 | -0.8522 | 22.82682 |
March | 514.00000 | 20.77683 | 30.96021 | -0.5352 | 13.75320 |
April | 485.00000 | 21.86002 | 36.08294 | -0.1867 | 9.86016 |
May | 508.00000 | 22.91744 | 41.95234 | -0.7842 | 23.61583 |
June | 496.00000 | 23.80335 | 51.83256 | -0.3460 | 10.09338 |
July | 497.00000 | 24.19686 | 56.53980 | -0.1401 | 7.55133 |
August | 514.00000 | 24.07107 | 52.92410 | -0.1952 | 7.90897 |
September | 485.00000 | 23.27788 | 48.42536 | -0.6023 | 17.36895 |
October | 502.00000 | 22.19978 | 41.72415 | -0.0321 | 8.69010 |
November | 489.00000 | 20.53943 | 34.31764 | -0.5937 | 15.18351 |
December | 497.00000 | 20.03025 | 26.38967 | -0.8287 | 21.82645 |
Annual Sum or Average | 5943.00000 | 21.98181 | 39.12811 | -0.4971 | 15.26036 |
Minimum of Months | 454.00000 | 19.85023 | 20.73231 | -0.8987 | 7.55133 |
Maximum of Months | 514.00000 | 24.19686 | 56.53980 | -0.0321 | 25.09439 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.22920 | 25.31843 | -0.7688 | 22.03182 |
February | 454.00000 | 20.60197 | 19.95506 | -0.6844 | 19.48322 |
March | 514.00000 | 21.22442 | 29.95625 | -0.4121 | 13.03609 |
April | 485.00000 | 21.83869 | 35.90856 | -0.1909 | 10.41631 |
May | 508.00000 | 22.67365 | 42.30990 | -0.8911 | 26.69821 |
June | 496.00000 | 23.65221 | 52.12162 | -0.4258 | 11.49976 |
July | 497.00000 | 24.08518 | 56.86439 | -0.2072 | 7.86167 |
August | 514.00000 | 24.01738 | 52.96755 | -0.2243 | 8.67570 |
September | 485.00000 | 23.39254 | 47.85055 | -0.5393 | 16.68651 |
October | 502.00000 | 22.79554 | 40.15194 | 0.14330 | 10.34093 |
November | 489.00000 | 21.07793 | 33.07315 | -0.4377 | 13.40358 |
December | 497.00000 | 20.57622 | 25.41454 | -0.6602 | 18.48541 |
Annual Sum or Average | 5943.00000 | 22.19362 | 38.63081 | -0.4400 | 14.86062 |
Minimum of Months | 454.00000 | 20.22920 | 19.95506 | -0.8911 | 7.86167 |
Maximum of Months | 514.00000 | 24.08518 | 56.86439 | 0.14330 | 26.69821 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.90167 | 25.79824 | -0.8942 | 24.93843 |
February | 454.00000 | 20.11303 | 20.55702 | -0.8554 | 23.42763 |
March | 514.00000 | 20.86281 | 30.64296 | -0.5210 | 14.00583 |
April | 485.00000 | 21.56822 | 36.56908 | -0.2520 | 10.74109 |
May | 508.00000 | 22.56408 | 42.61935 | -0.8966 | 27.51696 |
June | 496.00000 | 23.63887 | 52.13418 | -0.3851 | 11.75360 |
July | 497.00000 | 24.02526 | 57.06477 | -0.1930 | 8.41670 |
August | 514.00000 | 23.92484 | 53.33278 | -0.2388 | 9.18107 |
September | 485.00000 | 22.96802 | 49.07815 | -0.6958 | 20.42077 |
October | 502.00000 | 21.98642 | 42.07067 | -0.0756 | 9.32919 |
November | 489.00000 | 20.46541 | 34.33214 | -0.6235 | 16.01197 |
December | 497.00000 | 20.04204 | 26.21066 | -0.8356 | 22.17313 |
Annual Sum or Average | 5943.00000 | 21.85370 | 39.33889 | -0.5364 | 16.44144 |
Minimum of Months | 454.00000 | 19.90167 | 20.55702 | -0.8966 | 8.41670 |
Maximum of Months | 514.00000 | 24.02526 | 57.06477 | -0.0756 | 27.51696 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10454 | 25.86787 | -0.8421 | 22.06716 |
February | 454.00000 | 20.19787 | 21.40649 | -0.8480 | 21.79091 |
March | 514.00000 | 20.66875 | 31.92908 | -0.6055 | 13.55045 |
April | 485.00000 | 21.22836 | 38.70104 | -0.3780 | 9.34767 |
May | 508.00000 | 22.28239 | 45.44343 | -1.0975 | 32.26639 |
June | 496.00000 | 23.69519 | 53.84722 | -0.4964 | 11.27279 |
July | 497.00000 | 24.09276 | 57.14051 | -0.2975 | 7.45453 |
August | 514.00000 | 24.05146 | 53.43600 | -0.3309 | 7.96122 |
September | 485.00000 | 23.54177 | 50.06012 | -0.5761 | 13.52589 |
October | 502.00000 | 22.58182 | 43.11048 | 0.04763 | 6.86697 |
November | 489.00000 | 21.06747 | 34.51802 | -0.4403 | 10.49304 |
December | 497.00000 | 20.44108 | 26.27196 | -0.7035 | 16.27744 |
Annual Sum or Average | 5943.00000 | 22.01004 | 40.28290 | -0.5459 | 14.38284 |
Minimum of Months | 454.00000 | 20.10454 | 21.40649 | -1.0975 | 6.86697 |
Maximum of Months | 514.00000 | 24.09276 | 57.14051 | 0.04763 | 32.26639 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14785 | 26.00514 | -0.8076 | 20.90771 |
February | 454.00000 | 20.37648 | 21.39144 | -0.7683 | 18.86906 |
March | 514.00000 | 20.91662 | 31.66932 | -0.5043 | 11.61535 |
April | 485.00000 | 21.89106 | 37.40169 | -0.1912 | 8.42731 |
May | 508.00000 | 22.92105 | 44.03566 | -0.8377 | 24.26879 |
June | 496.00000 | 23.89220 | 53.15014 | -0.3728 | 9.47454 |
July | 497.00000 | 24.27675 | 56.29687 | -0.1723 | 6.83752 |
August | 514.00000 | 24.24456 | 52.51650 | -0.1741 | 6.55397 |
September | 485.00000 | 23.86961 | 49.05515 | -0.4069 | 10.81459 |
October | 502.00000 | 23.18259 | 41.72666 | 0.22069 | 7.88275 |
November | 489.00000 | 21.35095 | 34.15183 | -0.3498 | 9.43107 |
December | 497.00000 | 20.56762 | 26.30058 | -0.6469 | 14.69300 |
Annual Sum or Average | 5943.00000 | 22.31739 | 39.60961 | -0.4158 | 12.45686 |
Minimum of Months | 454.00000 | 20.14785 | 21.39144 | -0.8377 | 6.55397 |
Maximum of Months | 514.00000 | 24.27675 | 56.29687 | 0.22069 | 24.26879 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.00678 | 24.88411 | -0.7659 | 20.37149 |
February | 454.00000 | 20.37165 | 20.03615 | -0.6857 | 17.64684 |
March | 514.00000 | 20.96145 | 30.24629 | -0.4448 | 11.38191 |
April | 485.00000 | 21.67379 | 36.70671 | -0.2310 | 9.01507 |
May | 508.00000 | 22.46413 | 44.95036 | -1.0036 | 29.58266 |
June | 496.00000 | 23.71230 | 55.38120 | -0.4520 | 10.97548 |
July | 497.00000 | 24.23113 | 59.48470 | -0.2026 | 6.76562 |
August | 514.00000 | 24.26589 | 54.14836 | -0.1691 | 6.67456 |
September | 485.00000 | 24.00614 | 49.37950 | -0.3232 | 9.88034 |
October | 502.00000 | 23.71605 | 40.34404 | 0.40011 | 10.55379 |
November | 489.00000 | 21.66992 | 32.29856 | -0.2295 | 9.04801 |
December | 497.00000 | 20.84691 | 24.57628 | -0.5214 | 13.28930 |
Annual Sum or Average | 5943.00000 | 22.34102 | 39.51670 | -0.3845 | 12.93035 |
Minimum of Months | 454.00000 | 20.00678 | 20.03615 | -1.0036 | 6.67456 |
Maximum of Months | 514.00000 | 24.26589 | 59.48470 | 0.40011 | 29.58266 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.18254 | 25.87498 | -0.8066 | 20.92128 |
February | 454.00000 | 20.37026 | 21.32147 | -0.7801 | 19.61134 |
March | 514.00000 | 21.00790 | 31.39915 | -0.4863 | 11.48241 |
April | 485.00000 | 21.67107 | 37.81280 | -0.2426 | 8.88824 |
May | 508.00000 | 22.66443 | 44.56526 | -0.9251 | 26.96018 |
June | 496.00000 | 23.90675 | 53.01826 | -0.3595 | 9.46737 |
July | 497.00000 | 24.22999 | 56.51310 | -0.1884 | 7.07104 |
August | 514.00000 | 24.24009 | 52.62989 | -0.1777 | 6.74754 |
September | 485.00000 | 23.73460 | 49.39337 | -0.4521 | 11.73379 |
October | 502.00000 | 23.05957 | 41.87808 | 0.19647 | 7.91617 |
November | 489.00000 | 21.17870 | 34.40869 | -0.4003 | 10.08738 |
December | 497.00000 | 20.56741 | 26.21629 | -0.6574 | 15.07060 |
Annual Sum or Average | 5943.00000 | 22.24917 | 39.72009 | -0.4380 | 12.96997 |
Minimum of Months | 454.00000 | 20.18254 | 21.32147 | -0.9251 | 6.74754 |
Maximum of Months | 514.00000 | 24.24009 | 56.51310 | 0.19647 | 26.96018 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03373 | 25.82911 | -0.8347 | 22.23525 |
February | 454.00000 | 20.18909 | 20.71999 | -0.8146 | 20.96934 |
March | 514.00000 | 20.83532 | 31.06265 | -0.5215 | 11.90108 |
April | 485.00000 | 21.71289 | 36.99146 | -0.2300 | 8.25945 |
May | 508.00000 | 22.94386 | 42.96605 | -0.8353 | 22.12819 |
June | 496.00000 | 23.92626 | 52.57427 | -0.3760 | 8.96078 |
July | 497.00000 | 24.22051 | 57.09933 | -0.2176 | 6.73742 |
August | 514.00000 | 24.10907 | 53.73532 | -0.2853 | 7.67318 |
September | 485.00000 | 23.40550 | 49.56391 | -0.6140 | 15.08050 |
October | 502.00000 | 22.34843 | 42.61836 | -0.0103 | 7.32821 |
November | 489.00000 | 20.83950 | 34.10217 | -0.5056 | 12.22599 |
December | 497.00000 | 20.27475 | 25.86794 | -0.7432 | 18.09085 |
Annual Sum or Average | 5943.00000 | 22.08532 | 39.56710 | -0.4970 | 13.41844 |
Minimum of Months | 454.00000 | 20.03373 | 20.71999 | -0.8353 | 6.73742 |
Maximum of Months | 514.00000 | 24.22051 | 57.09933 | -0.0103 | 22.23525 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.90093 | 25.63452 | -0.8475 | 23.00975 |
February | 385.00000 | 20.23499 | 20.40602 | -0.7749 | 19.85026 |
March | 433.00000 | 21.03780 | 30.63320 | -0.4485 | 11.29528 |
April | 410.00000 | 22.09312 | 36.03743 | -0.1166 | 8.61049 |
May | 430.00000 | 23.13113 | 42.19623 | -0.7177 | 20.53074 |
June | 418.00000 | 23.90687 | 52.28636 | -0.3332 | 9.40364 |
July | 422.00000 | 24.28656 | 56.85550 | -0.1439 | 7.43950 |
August | 433.00000 | 24.17324 | 53.25338 | -0.1944 | 7.60915 |
September | 410.00000 | 23.52126 | 48.99824 | -0.5236 | 14.51199 |
October | 427.00000 | 22.58655 | 41.43535 | 0.07032 | 7.75594 |
November | 417.00000 | 20.95506 | 33.78478 | -0.4607 | 11.80093 |
December | 422.00000 | 20.27398 | 25.75244 | -0.7243 | 17.68418 |
Annual Sum or Average | 5034.00000 | 22.18776 | 39.06070 | -0.4326 | 13.25531 |
Minimum of Months | 385.00000 | 19.90093 | 20.40602 | -0.8475 | 7.43950 |
Maximum of Months | 433.00000 | 24.28656 | 56.85550 | 0.07032 | 23.00975 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.61468 | 25.16519 | -0.6404 | 18.16554 |
February | 454.00000 | 21.10472 | 19.81888 | -0.5318 | 15.08539 |
March | 514.00000 | 21.66493 | 29.66360 | -0.2797 | 10.08639 |
April | 485.00000 | 22.28608 | 35.74793 | -0.0702 | 8.66680 |
May | 508.00000 | 23.17458 | 42.37542 | -0.7369 | 19.96439 |
June | 496.00000 | 23.96724 | 52.36114 | -0.3415 | 8.84263 |
July | 497.00000 | 24.30443 | 56.71208 | -0.1626 | 6.82256 |
August | 514.00000 | 24.25334 | 53.02013 | -0.1668 | 7.08507 |
September | 485.00000 | 23.85308 | 48.10201 | -0.3888 | 11.64491 |
October | 502.00000 | 23.40129 | 40.03510 | 0.30299 | 10.11666 |
November | 489.00000 | 21.73409 | 32.46444 | -0.2503 | 10.06549 |
December | 497.00000 | 21.16408 | 24.76654 | -0.4818 | 13.73404 |
Annual Sum or Average | 5943.00000 | 22.63895 | 38.49282 | -0.3112 | 11.67596 |
Minimum of Months | 454.00000 | 20.61468 | 19.81888 | -0.7369 | 6.82256 |
Maximum of Months | 514.00000 | 24.30443 | 56.71208 | 0.30299 | 19.96439 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.12213 | 25.64763 | -0.7992 | 21.18749 |
February | 454.00000 | 20.37918 | 20.47043 | -0.7485 | 19.29463 |
March | 514.00000 | 21.16081 | 30.45127 | -0.4163 | 10.99770 |
April | 485.00000 | 21.88032 | 36.55092 | -0.1574 | 8.88706 |
May | 508.00000 | 22.89151 | 42.99883 | -0.7872 | 22.34224 |
June | 496.00000 | 23.86003 | 52.55743 | -0.3245 | 9.55557 |
July | 497.00000 | 24.16404 | 57.05429 | -0.1690 | 7.49621 |
August | 514.00000 | 24.10631 | 53.53967 | -0.1948 | 7.69802 |
September | 485.00000 | 23.33841 | 49.56470 | -0.5685 | 15.56349 |
October | 502.00000 | 22.49174 | 42.14704 | 0.06553 | 8.07494 |
November | 489.00000 | 20.88694 | 33.98017 | -0.4809 | 11.97323 |
December | 497.00000 | 20.39264 | 25.66279 | -0.7028 | 17.00978 |
Annual Sum or Average | 5943.00000 | 22.15456 | 39.35765 | -0.4381 | 13.29992 |
Minimum of Months | 454.00000 | 20.12213 | 20.47043 | -0.7992 | 7.49621 |
Maximum of Months | 514.00000 | 24.16404 | 57.05429 | 0.06553 | 22.34224 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.107641E+12 | 0.00 | 520.75 | 315234.19 | 20-JAN-06:11 | 0.00 | 34.64 | 51.92 | 0.48 | 0.00 | 0.08 | 0.66 | 20-JAN-06:11 |
February | 0.912032E+11 | 0.00 | 460.21 | 318857.28 | 02-FEB-06:11 | 0.00 | 34.77 | 51.74 | 0.44 | 0.00 | 0.08 | 0.67 | 02-FEB-06:11 |
March | 0.374857E+11 | 0.00 | 390.28 | 361400.90 | 06-MAR-06:11 | 0.00 | 29.19 | 44.44 | 0.14 | 0.00 | 0.03 | 0.76 | 06-MAR-06:11 |
April | 0.139552E+11 | 0.00 | 234.39 | 322867.37 | 03-APR-05:11 | 0.00 | 30.22 | 39.33 | 0.05 | 0.00 | 0.01 | 0.68 | 03-APR-05:11 |
May | 0.189612E+10 | 0.00 | 98.13 | 265543.48 | 01-MAY-06:03 | 0.00 | 35.09 | 38.48 | 0.01 | 0.00 | 0.00 | 0.56 | 01-MAY-06:03 |
June | 20063284.84 | 0.00 | 82.43 | 3720.25 | 02-JUN-06:07 | 0.00 | 31.12 | 34.44 | 0.00 | 0.00 | 0.00 | 0.01 | 02-JUN-06:07 |
July | 4833468.98 | 0.00 | 136.10 | 14.79 | 05-JUL-15:50 | 0.00 | 31.01 | 36.32 | 0.00 | 0.00 | 0.00 | 0.00 | 05-JUL-15:50 |
August | 5655949.09 | 0.00 | 171.46 | 14.26 | 09-AUG-13:20 | 0.00 | 31.54 | 38.10 | 0.00 | 0.00 | 0.00 | 0.00 | 09-AUG-13:20 |
September | 0.280531E+09 | 0.00 | 87.18 | 64867.27 | 29-SEP-06:03 | 0.00 | 28.76 | 32.48 | 0.00 | 0.00 | 0.00 | 0.14 | 29-SEP-06:03 |
October | 0.304696E+10 | 0.00 | 180.78 | 234139.51 | 28-OCT-06:03 | 0.00 | 27.50 | 34.94 | 0.01 | 0.00 | 0.00 | 0.49 | 28-OCT-06:03 |
November | 0.322799E+11 | 0.00 | 352.76 | 341733.14 | 27-NOV-06:11 | 0.00 | 28.83 | 43.10 | 0.13 | 0.00 | 0.03 | 0.72 | 27-NOV-06:11 |
December | 0.617415E+11 | 0.00 | 443.29 | 319271.44 | 20-DEC-06:11 | 0.00 | 32.16 | 48.58 | 0.23 | 0.00 | 0.05 | 0.67 | 20-DEC-06:11 |
Annual Sum or Average | 0.349561E+12 | 0.00 | 3157.76 | 0.00 | 31.22 | 41.11 | 0.12 | 0.00 | 0.02 | ||||
Minimum of Months | 4833468.98 | 0.00 | 82.43 | 14.26 | 0.00 | 27.50 | 32.48 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107641E+12 | 0.00 | 520.75 | 361400.90 | 0.00 | 35.09 | 51.92 | 0.48 | 0.00 | 0.08 | 0.76 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.306278E+10 | 0.839373E+09 | 177.46 | 0.254912E+10 | 0.513660E+09 | 0.00 | 0.41 | 24-JAN-12:20 | 0.00 | 01-JAN-00:01 | 14428.25 | 24-JAN-12:20 | 11384.85 | 24-JAN-07:03 | 4319.36 | 24-JAN-12:20 | 3761.35 | 24-JAN-12:20 | 0.00 |
February | 0.172253E+10 | 0.478297E+09 | 138.44 | 0.166015E+10 | 62381498.14 | 0.00 | 0.34 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 | 11799.65 | 24-FEB-16:00 | 11799.65 | 24-FEB-16:00 | 1141.53 | 28-FEB-17:02 | 3129.56 | 24-FEB-16:00 | 0.00 |
March | 0.103204E+11 | 0.272919E+10 | 336.57 | 0.947390E+10 | 0.846548E+09 | 0.00 | 0.81 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 31960.15 | 27-MAR-16:00 | 28195.65 | 27-MAR-16:00 | 6765.21 | 27-MAR-12:00 | 7497.46 | 27-MAR-16:00 | 0.00 |
April | 0.214996E+11 | 0.540208E+10 | 376.51 | 0.200927E+11 | 0.140688E+10 | 0.00 | 1.00 | 07-APR-12:50 | 0.00 | 01-APR-00:10 | 45732.08 | 07-APR-15:30 | 45732.08 | 07-APR-15:30 | 6152.03 | 27-APR-17:15 | 10588.92 | 07-APR-15:30 | 0.00 |
May | 0.409253E+11 | 0.982217E+10 | 412.96 | 0.369808E+11 | 0.394457E+10 | 0.00 | 1.00 | 18-MAY-14:50 | 0.00 | 01-MAY-00:10 | 71276.31 | 31-MAY-14:05 | 66649.48 | 30-MAY-05:12 | 11319.09 | 19-MAY-17:10 | 16976.28 | 31-MAY-14:05 | 0.00 |
June | 0.720812E+11 | 0.168316E+11 | 421.58 | 0.589205E+11 | 0.131608E+11 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 135452.84 | 19-JUN-05:02 | 78473.04 | 19-JUN-14:20 | 61051.49 | 19-JUN-05:03 | 30488.51 | 19-JUN-11:20 | 0.00 |
July | 0.958218E+11 | 0.227209E+11 | 439.01 | 0.717845E+11 | 0.240373E+11 | 0.00 | 1.00 | 01-JUL-05:13 | 0.00 | 01-JUL-00:10 | 140479.16 | 22-JUL-04:02 | 81494.48 | 07-JUL-04:02 | 74168.33 | 22-JUL-04:02 | 30701.57 | 22-JUL-04:02 | 0.00 |
August | 0.991217E+11 | 0.238765E+11 | 459.87 | 0.813504E+11 | 0.177713E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 136637.17 | 04-AUG-04:02 | 89295.35 | 22-AUG-04:02 | 62109.02 | 04-AUG-04:02 | 30746.82 | 03-AUG-04:02 | 0.00 |
September | 0.637150E+11 | 0.147718E+11 | 410.98 | 0.552642E+11 | 0.845085E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 132828.58 | 01-SEP-05:03 | 87835.52 | 01-SEP-05:02 | 61466.95 | 14-SEP-05:12 | 29628.09 | 01-SEP-05:03 | 0.00 |
October | 0.444382E+11 | 0.104136E+11 | 402.11 | 0.395346E+11 | 0.490360E+10 | 0.00 | 1.00 | 02-OCT-10:20 | 0.00 | 01-OCT-00:10 | 71103.36 | 04-OCT-14:10 | 62823.13 | 04-OCT-15:30 | 14466.34 | 06-OCT-05:03 | 16041.08 | 04-OCT-14:10 | 0.00 |
November | 0.145894E+11 | 0.372512E+10 | 320.93 | 0.135768E+11 | 0.101255E+10 | 0.00 | 0.89 | 03-NOV-14:10 | 0.00 | 01-NOV-00:10 | 35937.46 | 03-NOV-14:10 | 35937.46 | 03-NOV-14:10 | 7503.22 | 10-NOV-08:00 | 8219.51 | 03-NOV-14:10 | 0.00 |
December | 0.370060E+10 | 0.101731E+10 | 234.65 | 0.356986E+10 | 0.130739E+09 | 0.00 | 0.38 | 19-DEC-15:20 | 0.00 | 01-DEC-00:10 | 13354.96 | 19-DEC-15:20 | 13354.96 | 19-DEC-15:20 | 1926.31 | 04-DEC-15:00 | 3506.01 | 19-DEC-15:20 | 0.00 |
Annual Sum or Average | 0.470999E+12 | 0.112628E+12 | 4131.07 | 0.394757E+12 | 0.762411E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.172253E+10 | 0.478297E+09 | 138.44 | 0.166015E+10 | 62381498.14 | 0.00 | 0.34 | 0.00 | 11799.65 | 11384.85 | 1141.53 | 3129.56 | 0.00 | ||||||
Maximum of Months | 0.991217E+11 | 0.238765E+11 | 459.87 | 0.813504E+11 | 0.240373E+11 | 0.00 | 1.00 | 0.00 | 140479.16 | 89295.35 | 74168.33 | 30746.82 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.113544E+10 | 0.314999E+09 | 87.90 | 0.843178E+09 | 0.292263E+09 | 0.00 | 0.45 | 24-JAN-07:03 | 0.00 | 01-JAN-00:01 | 15270.57 | 24-JAN-07:03 | 13215.43 | 24-JAN-07:03 | 3526.98 | 24-JAN-12:00 | 3945.10 | 24-JAN-07:03 | 0.00 |
February | 0.296874E+09 | 83797366.17 | 42.34 | 0.289635E+09 | 7239233.85 | 0.00 | 0.17 | 24-FEB-14:00 | 0.00 | 01-FEB-00:10 | 5331.47 | 24-FEB-14:00 | 5331.47 | 24-FEB-14:00 | 399.71 | 24-FEB-07:05 | 1475.25 | 24-FEB-14:00 | 0.00 |
March | 0.546333E+10 | 0.145300E+10 | 225.98 | 0.480649E+10 | 0.656842E+09 | 0.00 | 0.76 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 28420.97 | 27-MAR-16:00 | 24104.87 | 27-MAR-16:00 | 7015.59 | 27-MAR-13:10 | 6749.91 | 27-MAR-16:00 | 0.00 |
April | 0.157552E+11 | 0.397932E+10 | 351.53 | 0.142474E+11 | 0.150777E+10 | 0.00 | 1.00 | 07-APR-12:05 | 0.00 | 01-APR-00:10 | 46927.25 | 07-APR-14:05 | 46927.25 | 07-APR-14:05 | 6281.67 | 27-APR-16:30 | 10977.30 | 07-APR-14:05 | 0.00 |
May | 0.362746E+11 | 0.882942E+10 | 429.09 | 0.319489E+11 | 0.432569E+10 | 0.00 | 1.00 | 10-MAY-14:40 | 0.00 | 01-MAY-00:10 | 72367.16 | 31-MAY-14:05 | 68465.46 | 30-MAY-14:05 | 11044.61 | 18-MAY-16:15 | 17336.67 | 30-MAY-14:05 | 0.00 |
June | 0.672075E+11 | 0.157723E+11 | 428.67 | 0.537476E+11 | 0.134599E+11 | 0.00 | 1.00 | 01-JUN-09:30 | 0.00 | 01-JUN-00:10 | 131309.66 | 19-JUN-05:02 | 78319.28 | 19-JUN-14:05 | 55637.85 | 19-JUN-05:02 | 29045.80 | 19-JUN-05:02 | 0.00 |
July | 0.888143E+11 | 0.210605E+11 | 436.32 | 0.651235E+11 | 0.236908E+11 | 0.00 | 1.00 | 01-JUL-09:00 | 0.00 | 01-JUL-00:10 | 135434.19 | 22-JUL-05:02 | 81472.17 | 07-JUL-04:02 | 72841.33 | 22-JUL-05:02 | 29824.19 | 10-JUL-04:01 | 0.00 |
August | 0.881192E+11 | 0.212587E+11 | 448.67 | 0.713780E+11 | 0.167412E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 133140.60 | 04-AUG-04:02 | 81786.70 | 22-AUG-04:02 | 66277.03 | 04-AUG-04:02 | 29798.29 | 05-AUG-05:02 | 0.00 |
September | 0.533275E+11 | 0.125100E+11 | 409.56 | 0.446213E+11 | 0.870627E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 128246.15 | 01-SEP-05:02 | 77622.72 | 01-SEP-05:02 | 50623.43 | 01-SEP-05:02 | 28601.15 | 01-SEP-05:02 | 0.00 |
October | 0.334496E+11 | 0.799158E+10 | 394.97 | 0.281166E+11 | 0.533295E+10 | 0.00 | 1.00 | 02-OCT-14:05 | 0.00 | 01-OCT-00:10 | 64066.59 | 04-OCT-14:05 | 55626.26 | 04-OCT-14:05 | 14947.03 | 06-OCT-05:03 | 14456.28 | 04-OCT-14:05 | 0.00 |
November | 0.759182E+10 | 0.199547E+10 | 247.80 | 0.651582E+10 | 0.107600E+10 | 0.00 | 0.75 | 03-NOV-14:03 | 0.00 | 01-NOV-00:10 | 28079.52 | 03-NOV-14:03 | 28079.52 | 03-NOV-14:03 | 8090.95 | 10-NOV-10:00 | 6682.82 | 03-NOV-14:03 | 0.00 |
December | 0.584574E+09 | 0.164044E+09 | 64.50 | 0.535379E+09 | 49195030.21 | 0.00 | 0.21 | 04-DEC-07:03 | 0.00 | 01-DEC-00:10 | 6722.14 | 04-DEC-07:03 | 6722.14 | 04-DEC-07:03 | 1216.47 | 04-DEC-15:10 | 1841.74 | 04-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.398020E+12 | 0.954132E+11 | 3567.32 | 0.322174E+12 | 0.758461E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.296874E+09 | 83797366.17 | 42.34 | 0.289635E+09 | 7239233.85 | 0.00 | 0.17 | 0.00 | 5331.47 | 5331.47 | 399.71 | 1475.25 | 0.00 | ||||||
Maximum of Months | 0.888143E+11 | 0.212587E+11 | 448.67 | 0.713780E+11 | 0.236908E+11 | 0.00 | 1.00 | 0.00 | 135434.19 | 81786.70 | 72841.33 | 29824.19 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.242909E+10 | 0.671311E+09 | 125.70 | 0.191477E+10 | 0.514326E+09 | 0.00 | 0.34 | 24-JAN-07:03 | 0.00 | 01-JAN-00:01 | 15036.06 | 24-JAN-07:03 | 12161.44 | 24-JAN-07:03 | 4387.67 | 24-JAN-12:20 | 3985.70 | 24-JAN-07:03 | 0.00 |
February | 0.115878E+10 | 0.323740E+09 | 86.23 | 0.111722E+10 | 41559419.41 | 0.00 | 0.21 | 24-FEB-14:00 | 0.00 | 01-FEB-00:10 | 8963.14 | 24-FEB-14:00 | 8907.51 | 24-FEB-14:00 | 653.24 | 16-FEB-11:50 | 2453.76 | 24-FEB-14:00 | 0.00 |
March | 0.870248E+10 | 0.231435E+10 | 258.07 | 0.773900E+10 | 0.963480E+09 | 0.00 | 0.73 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 35265.43 | 27-MAR-16:00 | 29630.14 | 27-MAR-16:00 | 8267.45 | 27-MAR-12:40 | 8463.60 | 27-MAR-16:00 | 0.00 |
April | 0.200957E+11 | 0.510703E+10 | 348.99 | 0.180393E+11 | 0.205639E+10 | 0.00 | 1.00 | 07-APR-12:20 | 0.00 | 01-APR-00:10 | 60119.42 | 07-APR-14:40 | 60119.42 | 07-APR-14:40 | 7491.91 | 27-APR-16:40 | 14001.84 | 07-APR-14:30 | 0.00 |
May | 0.435869E+11 | 0.107179E+11 | 428.46 | 0.381490E+11 | 0.543787E+10 | 0.00 | 1.00 | 10-MAY-14:20 | 0.00 | 01-MAY-00:10 | 86686.57 | 31-MAY-14:00 | 84161.49 | 30-MAY-13:50 | 12680.83 | 19-MAY-11:10 | 21447.44 | 30-MAY-13:30 | 0.00 |
June | 0.763809E+11 | 0.181575E+11 | 428.61 | 0.616228E+11 | 0.147581E+11 | 0.00 | 1.00 | 01-JUN-10:50 | 0.00 | 01-JUN-00:10 | 167186.82 | 19-JUN-05:02 | 97601.22 | 19-JUN-13:50 | 82218.80 | 19-JUN-05:02 | 37039.38 | 19-JUN-05:02 | 0.00 |
July | 0.992078E+11 | 0.237070E+11 | 435.50 | 0.746039E+11 | 0.246039E+11 | 0.00 | 1.00 | 03-JUL-08:70 | 0.00 | 01-JUL-00:10 | 178623.30 | 22-JUL-05:02 | 106926.36 | 10-JUL-04:01 | 98485.20 | 22-JUL-05:02 | 39051.00 | 10-JUL-04:01 | 0.00 |
August | 0.980366E+11 | 0.238326E+11 | 448.46 | 0.803546E+11 | 0.176821E+11 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 172572.58 | 05-AUG-04:01 | 97640.85 | 05-AUG-04:01 | 74931.73 | 05-AUG-04:01 | 38949.14 | 05-AUG-04:01 | 0.00 |
September | 0.580655E+11 | 0.138689E+11 | 406.55 | 0.479791E+11 | 0.100863E+11 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 121804.14 | 01-SEP-05:02 | 87440.65 | 01-SEP-14:00 | 51037.75 | 01-SEP-05:02 | 27252.08 | 01-SEP-05:02 | 0.00 |
October | 0.353779E+11 | 0.864091E+10 | 381.33 | 0.290064E+11 | 0.637150E+10 | 0.00 | 1.00 | 03-OCT-12:50 | 0.00 | 01-OCT-00:10 | 70779.57 | 04-OCT-14:30 | 62702.13 | 04-OCT-14:20 | 18242.17 | 06-OCT-05:03 | 15920.39 | 04-OCT-14:30 | 0.00 |
November | 0.947793E+10 | 0.252180E+10 | 260.32 | 0.801081E+10 | 0.146712E+10 | 0.00 | 0.57 | 02-NOV-13:30 | 0.00 | 01-NOV-00:10 | 26379.99 | 02-NOV-13:30 | 26379.99 | 02-NOV-13:30 | 9278.79 | 10-NOV-10:00 | 6601.49 | 02-NOV-13:30 | 0.00 |
December | 0.153122E+10 | 0.427567E+09 | 116.59 | 0.140991E+10 | 0.121305E+09 | 0.00 | 0.23 | 20-DEC-14:00 | 0.00 | 01-DEC-00:10 | 9624.50 | 20-DEC-14:00 | 9135.73 | 19-DEC-14:00 | 2135.86 | 04-DEC-14:40 | 2625.45 | 20-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.454051E+12 | 0.110291E+12 | 3724.80 | 0.369947E+12 | 0.841039E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.115878E+10 | 0.323740E+09 | 86.23 | 0.111722E+10 | 41559419.41 | 0.00 | 0.21 | 0.00 | 8963.14 | 8907.51 | 653.24 | 2453.76 | 0.00 | ||||||
Maximum of Months | 0.992078E+11 | 0.238326E+11 | 448.46 | 0.803546E+11 | 0.246039E+11 | 0.00 | 1.00 | 0.00 | 178623.30 | 106926.36 | 98485.20 | 39051.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 343.90 | 0.00 | 343.90 | 4.13 | 2394.36 | 0.00 | 0.00 | 0.00 |
February | 470.61 | 0.00 | 470.61 | 21.85 | 2517.34 | 0.00 | 0.00 | 0.00 |
March | 652.62 | 0.00 | 652.62 | 154.50 | 1630.19 | 0.00 | 0.00 | 0.00 |
April | 783.89 | 2.23 | 781.66 | 416.32 | 1126.85 | 0.00 | 0.00 | 0.00 |
May | 1039.97 | 34.65 | 1005.32 | 891.71 | 663.08 | 0.00 | 0.00 | 0.00 |
June | 1102.87 | 59.26 | 1043.61 | 1306.09 | 370.65 | 0.00 | 0.00 | 0.00 |
July | 1065.82 | 38.54 | 1027.28 | 1504.55 | 207.88 | 0.00 | 0.00 | 0.00 |
August | 944.27 | 11.24 | 933.03 | 1316.59 | 282.46 | 0.00 | 0.00 | 0.00 |
September | 711.82 | 0.13 | 711.69 | 730.14 | 541.70 | 0.00 | 0.00 | 0.00 |
October | 616.03 | 0.00 | 616.03 | 407.61 | 994.71 | 0.00 | 0.00 | 0.00 |
November | 432.08 | 0.00 | 432.08 | 83.44 | 1611.82 | 0.00 | 0.00 | 0.00 |
December | 299.97 | 0.00 | 299.97 | 5.49 | 2184.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 706.68 | 12.24 | 694.44 | 574.01 | 1202.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.97 | 0.00 | 299.97 | 4.13 | 207.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1102.87 | 59.26 | 1043.61 | 1504.55 | 2517.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 478.91 | 192.00 | 286.90 | 243.39 | 1460.73 | 0.00 | 0.00 | 0.00 |
February | 742.68 | 346.46 | 396.22 | 445.83 | 1474.52 | 0.00 | 0.00 | 0.00 |
March | 947.43 | 402.95 | 544.48 | 739.52 | 1033.59 | 0.00 | 0.00 | 0.00 |
April | 1136.98 | 498.03 | 638.95 | 1060.50 | 728.22 | 0.00 | 0.00 | 0.00 |
May | 1378.92 | 551.10 | 827.82 | 1504.41 | 455.17 | 0.00 | 0.00 | 0.00 |
June | 1277.97 | 462.61 | 815.35 | 1610.06 | 253.84 | 0.00 | 0.00 | 0.00 |
July | 1283.56 | 463.20 | 820.36 | 1791.12 | 141.34 | 0.00 | 0.00 | 0.00 |
August | 1445.32 | 651.69 | 793.63 | 2001.72 | 190.77 | 0.00 | 0.00 | 0.00 |
September | 1077.93 | 483.62 | 594.31 | 1291.94 | 353.88 | 0.00 | 0.00 | 0.00 |
October | 977.22 | 442.91 | 534.31 | 1020.20 | 643.00 | 0.00 | 0.00 | 0.00 |
November | 604.33 | 232.07 | 372.27 | 431.03 | 986.77 | 0.00 | 0.00 | 0.00 |
December | 470.81 | 221.06 | 249.75 | 275.75 | 1318.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 986.74 | 412.77 | 573.96 | 1038.76 | 749.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.81 | 192.00 | 249.75 | 243.39 | 141.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1445.32 | 651.69 | 827.82 | 2001.72 | 1474.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1779.03 | 1164.92 | 614.11 | 1585.19 | 2065.75 | 0.00 | 0.00 | 0.00 |
February | 2346.48 | 1553.17 | 793.30 | 2137.66 | 2096.19 | 0.00 | 0.00 | 0.00 |
March | 2116.97 | 1174.95 | 942.02 | 2057.40 | 1546.01 | 0.00 | 0.00 | 0.00 |
April | 1642.70 | 649.57 | 993.13 | 1660.27 | 1161.35 | 0.00 | 0.00 | 0.00 |
May | 1439.58 | 300.27 | 1139.31 | 1567.19 | 719.50 | 0.00 | 0.00 | 0.00 |
June | 1351.01 | 206.51 | 1144.49 | 1746.70 | 402.37 | 0.00 | 0.00 | 0.00 |
July | 1416.13 | 245.98 | 1170.15 | 2087.29 | 217.54 | 0.00 | 0.00 | 0.00 |
August | 1891.07 | 701.43 | 1189.65 | 2807.93 | 303.46 | 0.00 | 0.00 | 0.00 |
September | 2051.85 | 1061.30 | 990.55 | 2650.41 | 565.17 | 0.00 | 0.00 | 0.00 |
October | 2810.86 | 1762.60 | 1048.25 | 3332.60 | 1006.35 | 0.00 | 0.00 | 0.00 |
November | 1949.09 | 1170.52 | 778.57 | 1931.83 | 1460.96 | 0.00 | 0.00 | 0.00 |
December | 1928.20 | 1368.89 | 559.31 | 1828.68 | 1868.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1891.44 | 943.60 | 947.84 | 2117.22 | 1112.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1351.01 | 206.51 | 559.31 | 1567.19 | 217.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2810.86 | 1762.60 | 1189.65 | 3332.60 | 2096.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 472.79 | 193.65 | 279.13 | 244.81 | 1504.91 | 0.00 | 0.00 | 0.00 |
February | 697.19 | 306.21 | 390.98 | 408.58 | 1553.76 | 0.00 | 0.00 | 0.00 |
March | 1029.49 | 475.29 | 554.21 | 828.49 | 1027.57 | 0.00 | 0.00 | 0.00 |
April | 1125.19 | 481.44 | 643.75 | 1064.48 | 750.98 | 0.00 | 0.00 | 0.00 |
May | 1310.73 | 497.76 | 812.97 | 1449.62 | 469.21 | 0.00 | 0.00 | 0.00 |
June | 1434.55 | 578.59 | 855.96 | 1828.49 | 272.19 | 0.00 | 0.00 | 0.00 |
July | 1343.54 | 505.93 | 837.61 | 1876.12 | 153.00 | 0.00 | 0.00 | 0.00 |
August | 1486.32 | 688.06 | 798.25 | 2080.78 | 207.06 | 0.00 | 0.00 | 0.00 |
September | 1055.17 | 461.10 | 594.06 | 1294.31 | 370.37 | 0.00 | 0.00 | 0.00 |
October | 1046.12 | 508.70 | 537.42 | 1118.53 | 668.69 | 0.00 | 0.00 | 0.00 |
November | 491.25 | 141.97 | 349.28 | 284.91 | 1032.56 | 0.00 | 0.00 | 0.00 |
December | 436.96 | 189.07 | 247.89 | 235.53 | 1368.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 996.19 | 419.94 | 576.25 | 1064.26 | 777.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 436.96 | 141.97 | 247.89 | 235.53 | 153.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1486.32 | 688.06 | 855.96 | 2080.78 | 1553.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.63 | 0.00 | 114.63 | 1.39 | 823.54 | 0.00 | 0.00 | 0.00 |
February | 156.87 | 0.00 | 156.87 | 6.91 | 856.33 | 0.00 | 0.00 | 0.00 |
March | 217.53 | 0.00 | 217.53 | 57.55 | 554.16 | 0.00 | 0.00 | 0.00 |
April | 261.29 | 0.74 | 260.54 | 151.47 | 378.42 | 0.00 | 0.00 | 0.00 |
May | 346.64 | 11.55 | 335.09 | 318.47 | 214.35 | 0.00 | 0.00 | 0.00 |
June | 367.61 | 19.75 | 347.86 | 449.50 | 120.28 | 0.00 | 0.00 | 0.00 |
July | 355.26 | 12.85 | 342.41 | 512.85 | 66.41 | 0.00 | 0.00 | 0.00 |
August | 314.74 | 3.75 | 311.00 | 443.80 | 97.43 | 0.00 | 0.00 | 0.00 |
September | 237.26 | 0.04 | 237.22 | 237.68 | 205.08 | 0.00 | 0.00 | 0.00 |
October | 205.34 | 0.00 | 205.34 | 125.90 | 379.93 | 0.00 | 0.00 | 0.00 |
November | 144.02 | 0.00 | 144.02 | 23.63 | 603.14 | 0.00 | 0.00 | 0.00 |
December | 99.99 | 0.00 | 99.99 | 1.05 | 787.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.55 | 4.08 | 231.47 | 195.49 | 421.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.99 | 0.00 | 99.99 | 1.05 | 66.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.61 | 19.75 | 347.86 | 512.85 | 856.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.63 | 0.00 | 114.63 | 1.39 | 823.60 | 0.00 | 0.00 | 0.00 |
February | 156.87 | 0.00 | 156.87 | 6.91 | 856.39 | 0.00 | 0.00 | 0.00 |
March | 217.54 | 0.00 | 217.54 | 57.56 | 554.20 | 0.00 | 0.00 | 0.00 |
April | 261.30 | 0.74 | 260.56 | 151.48 | 378.44 | 0.00 | 0.00 | 0.00 |
May | 346.66 | 11.55 | 335.11 | 318.49 | 214.36 | 0.00 | 0.00 | 0.00 |
June | 367.63 | 19.75 | 347.87 | 449.52 | 120.28 | 0.00 | 0.00 | 0.00 |
July | 355.28 | 12.85 | 342.43 | 512.87 | 66.41 | 0.00 | 0.00 | 0.00 |
August | 314.76 | 3.75 | 311.01 | 443.82 | 97.43 | 0.00 | 0.00 | 0.00 |
September | 237.28 | 0.04 | 237.23 | 237.69 | 205.10 | 0.00 | 0.00 | 0.00 |
October | 205.35 | 0.00 | 205.35 | 125.90 | 379.95 | 0.00 | 0.00 | 0.00 |
November | 144.03 | 0.00 | 144.03 | 23.63 | 603.18 | 0.00 | 0.00 | 0.00 |
December | 99.99 | 0.00 | 99.99 | 1.05 | 787.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.56 | 4.08 | 231.48 | 195.50 | 421.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.99 | 0.00 | 99.99 | 1.05 | 66.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.63 | 19.75 | 347.87 | 512.87 | 856.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.63 | 0.00 | 114.63 | 1.39 | 823.60 | 0.00 | 0.00 | 0.00 |
February | 156.87 | 0.00 | 156.87 | 6.91 | 856.39 | 0.00 | 0.00 | 0.00 |
March | 217.54 | 0.00 | 217.54 | 57.56 | 554.20 | 0.00 | 0.00 | 0.00 |
April | 261.30 | 0.74 | 260.56 | 151.48 | 378.44 | 0.00 | 0.00 | 0.00 |
May | 346.66 | 11.55 | 335.11 | 318.49 | 214.36 | 0.00 | 0.00 | 0.00 |
June | 367.63 | 19.75 | 347.87 | 449.52 | 120.28 | 0.00 | 0.00 | 0.00 |
July | 355.28 | 12.85 | 342.43 | 512.87 | 66.41 | 0.00 | 0.00 | 0.00 |
August | 314.76 | 3.75 | 311.01 | 443.82 | 97.43 | 0.00 | 0.00 | 0.00 |
September | 237.28 | 0.04 | 237.23 | 237.69 | 205.10 | 0.00 | 0.00 | 0.00 |
October | 205.35 | 0.00 | 205.35 | 125.90 | 379.95 | 0.00 | 0.00 | 0.00 |
November | 144.03 | 0.00 | 144.03 | 23.63 | 603.18 | 0.00 | 0.00 | 0.00 |
December | 99.99 | 0.00 | 99.99 | 1.05 | 787.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.56 | 4.08 | 231.48 | 195.50 | 421.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 99.99 | 0.00 | 99.99 | 1.05 | 66.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.63 | 19.75 | 347.87 | 512.87 | 856.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 460.71 | 184.71 | 276.00 | 235.87 | 1462.42 | 0.00 | 0.00 | 0.00 |
February | 714.46 | 333.29 | 381.16 | 430.35 | 1470.30 | 0.00 | 0.00 | 0.00 |
March | 911.42 | 387.64 | 523.79 | 729.02 | 1028.98 | 0.00 | 0.00 | 0.00 |
April | 1093.77 | 479.11 | 614.67 | 1046.40 | 721.12 | 0.00 | 0.00 | 0.00 |
May | 1326.52 | 530.16 | 796.36 | 1485.76 | 438.36 | 0.00 | 0.00 | 0.00 |
June | 1229.40 | 445.03 | 784.37 | 1577.59 | 245.77 | 0.00 | 0.00 | 0.00 |
July | 1234.78 | 445.60 | 789.18 | 1747.51 | 137.85 | 0.00 | 0.00 | 0.00 |
August | 1390.39 | 626.93 | 763.47 | 1941.16 | 199.97 | 0.00 | 0.00 | 0.00 |
September | 1036.96 | 465.24 | 571.72 | 1237.58 | 394.83 | 0.00 | 0.00 | 0.00 |
October | 940.08 | 426.08 | 514.01 | 960.92 | 724.73 | 0.00 | 0.00 | 0.00 |
November | 581.37 | 223.25 | 358.12 | 396.20 | 1080.03 | 0.00 | 0.00 | 0.00 |
December | 452.92 | 212.66 | 240.26 | 257.97 | 1387.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 949.24 | 397.09 | 552.15 | 1007.91 | 770.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 452.92 | 184.71 | 240.26 | 235.87 | 137.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1390.39 | 626.93 | 796.36 | 1941.16 | 1470.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.22 | 7.30 | 10.91 | 9.33 | 57.82 | 0.00 | 0.00 | 0.00 |
February | 28.25 | 13.18 | 15.07 | 17.02 | 58.13 | 0.00 | 0.00 | 0.00 |
March | 36.04 | 15.33 | 20.71 | 28.82 | 40.68 | 0.00 | 0.00 | 0.00 |
April | 43.25 | 18.94 | 24.30 | 41.37 | 28.51 | 0.00 | 0.00 | 0.00 |
May | 52.45 | 20.96 | 31.49 | 58.75 | 17.33 | 0.00 | 0.00 | 0.00 |
June | 48.61 | 17.60 | 31.01 | 62.38 | 9.72 | 0.00 | 0.00 | 0.00 |
July | 48.82 | 17.62 | 31.20 | 69.10 | 5.45 | 0.00 | 0.00 | 0.00 |
August | 54.97 | 24.79 | 30.19 | 76.75 | 7.91 | 0.00 | 0.00 | 0.00 |
September | 41.00 | 18.40 | 22.61 | 48.93 | 15.61 | 0.00 | 0.00 | 0.00 |
October | 37.17 | 16.85 | 20.32 | 37.99 | 28.66 | 0.00 | 0.00 | 0.00 |
November | 22.99 | 8.83 | 14.16 | 15.67 | 42.70 | 0.00 | 0.00 | 0.00 |
December | 17.91 | 8.41 | 9.50 | 10.20 | 54.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.53 | 15.70 | 21.83 | 39.85 | 30.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.91 | 7.30 | 9.50 | 9.33 | 5.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.97 | 24.79 | 31.49 | 76.75 | 58.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 593.02 | 388.32 | 204.71 | 541.16 | 722.62 | 0.00 | 0.00 | 0.00 |
February | 782.18 | 517.74 | 264.44 | 727.00 | 736.57 | 0.00 | 0.00 | 0.00 |
March | 705.67 | 391.66 | 314.01 | 706.11 | 540.34 | 0.00 | 0.00 | 0.00 |
April | 547.58 | 216.53 | 331.05 | 572.02 | 397.74 | 0.00 | 0.00 | 0.00 |
May | 479.87 | 100.09 | 379.78 | 545.82 | 235.88 | 0.00 | 0.00 | 0.00 |
June | 450.35 | 68.84 | 381.51 | 598.71 | 132.53 | 0.00 | 0.00 | 0.00 |
July | 472.05 | 81.99 | 390.06 | 707.89 | 72.45 | 0.00 | 0.00 | 0.00 |
August | 630.37 | 233.82 | 396.56 | 943.58 | 111.41 | 0.00 | 0.00 | 0.00 |
September | 683.97 | 353.77 | 330.19 | 883.19 | 222.76 | 0.00 | 0.00 | 0.00 |
October | 936.98 | 587.55 | 349.43 | 1107.69 | 404.61 | 0.00 | 0.00 | 0.00 |
November | 649.71 | 390.18 | 259.53 | 640.20 | 561.60 | 0.00 | 0.00 | 0.00 |
December | 642.75 | 456.31 | 186.44 | 610.00 | 689.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 630.50 | 314.54 | 315.95 | 715.64 | 400.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.35 | 68.84 | 186.44 | 541.16 | 72.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 936.98 | 587.55 | 396.56 | 1107.69 | 736.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 593.02 | 388.32 | 204.71 | 541.16 | 722.62 | 0.00 | 0.00 | 0.00 |
February | 782.18 | 517.74 | 264.44 | 727.00 | 736.57 | 0.00 | 0.00 | 0.00 |
March | 705.67 | 391.66 | 314.01 | 706.11 | 540.34 | 0.00 | 0.00 | 0.00 |
April | 547.58 | 216.53 | 331.05 | 572.02 | 397.74 | 0.00 | 0.00 | 0.00 |
May | 479.87 | 100.09 | 379.78 | 545.82 | 235.88 | 0.00 | 0.00 | 0.00 |
June | 450.35 | 68.84 | 381.51 | 598.71 | 132.53 | 0.00 | 0.00 | 0.00 |
July | 472.05 | 81.99 | 390.06 | 707.89 | 72.45 | 0.00 | 0.00 | 0.00 |
August | 630.37 | 233.82 | 396.56 | 943.58 | 111.41 | 0.00 | 0.00 | 0.00 |
September | 683.97 | 353.77 | 330.19 | 883.19 | 222.76 | 0.00 | 0.00 | 0.00 |
October | 936.98 | 587.55 | 349.43 | 1107.69 | 404.61 | 0.00 | 0.00 | 0.00 |
November | 649.71 | 390.18 | 259.53 | 640.20 | 561.60 | 0.00 | 0.00 | 0.00 |
December | 642.75 | 456.31 | 186.44 | 610.00 | 689.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 630.50 | 314.54 | 315.95 | 715.64 | 400.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.35 | 68.84 | 186.44 | 541.16 | 72.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 936.98 | 587.55 | 396.56 | 1107.69 | 736.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 592.99 | 388.29 | 204.70 | 541.13 | 722.58 | 0.00 | 0.00 | 0.00 |
February | 782.13 | 517.71 | 264.42 | 726.95 | 736.52 | 0.00 | 0.00 | 0.00 |
March | 705.63 | 391.64 | 313.99 | 706.06 | 540.31 | 0.00 | 0.00 | 0.00 |
April | 547.54 | 216.51 | 331.03 | 571.98 | 397.71 | 0.00 | 0.00 | 0.00 |
May | 479.84 | 100.09 | 379.76 | 545.79 | 235.87 | 0.00 | 0.00 | 0.00 |
June | 450.32 | 68.84 | 381.48 | 598.67 | 132.53 | 0.00 | 0.00 | 0.00 |
July | 472.02 | 81.99 | 390.03 | 707.85 | 72.44 | 0.00 | 0.00 | 0.00 |
August | 630.33 | 233.80 | 396.53 | 943.52 | 111.40 | 0.00 | 0.00 | 0.00 |
September | 683.92 | 353.75 | 330.17 | 883.14 | 222.75 | 0.00 | 0.00 | 0.00 |
October | 936.92 | 587.51 | 349.40 | 1107.62 | 404.58 | 0.00 | 0.00 | 0.00 |
November | 649.67 | 390.16 | 259.51 | 640.16 | 561.57 | 0.00 | 0.00 | 0.00 |
December | 642.71 | 456.28 | 186.43 | 609.96 | 689.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 630.46 | 314.52 | 315.93 | 715.60 | 400.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.32 | 68.84 | 186.43 | 541.13 | 72.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 936.92 | 587.51 | 396.53 | 1107.62 | 736.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 454.82 | 186.30 | 268.52 | 241.43 | 1503.70 | 0.00 | 0.00 | 0.00 |
February | 670.70 | 294.57 | 376.12 | 404.26 | 1545.87 | 0.00 | 0.00 | 0.00 |
March | 990.37 | 457.23 | 533.14 | 822.31 | 1032.16 | 0.00 | 0.00 | 0.00 |
April | 1082.42 | 463.14 | 619.28 | 1055.22 | 748.69 | 0.00 | 0.00 | 0.00 |
May | 1260.91 | 478.85 | 782.07 | 1431.36 | 456.33 | 0.00 | 0.00 | 0.00 |
June | 1380.03 | 556.61 | 823.43 | 1785.74 | 270.32 | 0.00 | 0.00 | 0.00 |
July | 1292.48 | 486.71 | 805.77 | 1827.27 | 152.11 | 0.00 | 0.00 | 0.00 |
August | 1429.83 | 661.92 | 767.91 | 2012.99 | 219.82 | 0.00 | 0.00 | 0.00 |
September | 1015.07 | 443.58 | 571.48 | 1235.68 | 414.76 | 0.00 | 0.00 | 0.00 |
October | 1006.36 | 489.37 | 516.99 | 1060.03 | 756.82 | 0.00 | 0.00 | 0.00 |
November | 472.58 | 136.58 | 336.00 | 265.61 | 1122.66 | 0.00 | 0.00 | 0.00 |
December | 420.35 | 181.89 | 238.47 | 224.76 | 1435.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 958.33 | 403.99 | 554.35 | 1035.10 | 800.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 420.35 | 136.58 | 238.47 | 224.76 | 152.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1429.83 | 661.92 | 823.43 | 2012.99 | 1545.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.98 | 7.37 | 10.62 | 9.55 | 59.45 | 0.00 | 0.00 | 0.00 |
February | 26.52 | 11.65 | 14.87 | 15.98 | 61.12 | 0.00 | 0.00 | 0.00 |
March | 39.16 | 18.08 | 21.08 | 32.51 | 40.81 | 0.00 | 0.00 | 0.00 |
April | 42.80 | 18.31 | 24.49 | 41.72 | 29.60 | 0.00 | 0.00 | 0.00 |
May | 49.86 | 18.93 | 30.92 | 56.59 | 18.04 | 0.00 | 0.00 | 0.00 |
June | 54.57 | 22.01 | 32.56 | 70.61 | 10.69 | 0.00 | 0.00 | 0.00 |
July | 51.10 | 19.24 | 31.86 | 72.25 | 6.01 | 0.00 | 0.00 | 0.00 |
August | 56.53 | 26.17 | 30.36 | 79.59 | 8.69 | 0.00 | 0.00 | 0.00 |
September | 40.13 | 17.54 | 22.60 | 48.86 | 16.40 | 0.00 | 0.00 | 0.00 |
October | 39.79 | 19.35 | 20.44 | 41.91 | 29.92 | 0.00 | 0.00 | 0.00 |
November | 18.69 | 5.40 | 13.29 | 10.50 | 44.39 | 0.00 | 0.00 | 0.00 |
December | 16.62 | 7.19 | 9.43 | 8.89 | 56.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.89 | 15.97 | 21.92 | 40.93 | 31.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.62 | 5.40 | 9.43 | 8.89 | 6.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.53 | 26.17 | 32.56 | 79.59 | 61.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 343.90 | 0.00 | 343.90 | 3.26 | 2501.36 | 0.00 | 0.00 | 0.00 |
February | 470.61 | 0.00 | 470.61 | 17.22 | 2637.90 | 0.00 | 0.00 | 0.00 |
March | 652.62 | 0.00 | 652.62 | 146.28 | 1746.85 | 0.00 | 0.00 | 0.00 |
April | 783.89 | 2.23 | 781.66 | 400.11 | 1221.63 | 0.00 | 0.00 | 0.00 |
May | 1039.97 | 34.65 | 1005.32 | 868.24 | 720.21 | 0.00 | 0.00 | 0.00 |
June | 1102.87 | 59.26 | 1043.61 | 1297.81 | 398.72 | 0.00 | 0.00 | 0.00 |
July | 1065.82 | 38.54 | 1027.28 | 1504.98 | 224.38 | 0.00 | 0.00 | 0.00 |
August | 944.27 | 11.24 | 933.03 | 1313.21 | 307.63 | 0.00 | 0.00 | 0.00 |
September | 711.82 | 0.13 | 711.69 | 709.13 | 605.16 | 0.00 | 0.00 | 0.00 |
October | 616.03 | 0.00 | 616.03 | 377.68 | 1109.18 | 0.00 | 0.00 | 0.00 |
November | 432.08 | 0.00 | 432.08 | 70.65 | 1762.16 | 0.00 | 0.00 | 0.00 |
December | 299.97 | 0.00 | 299.97 | 3.08 | 2341.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 706.68 | 12.24 | 694.44 | 563.10 | 1290.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 299.97 | 0.00 | 299.97 | 3.08 | 224.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1102.87 | 59.26 | 1043.61 | 1504.98 | 2637.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 478.91 | 192.00 | 286.90 | 237.69 | 1527.94 | 0.00 | 0.00 | 0.00 |
February | 742.68 | 346.46 | 396.22 | 432.49 | 1550.59 | 0.00 | 0.00 | 0.00 |
March | 947.43 | 402.95 | 544.48 | 721.84 | 1110.11 | 0.00 | 0.00 | 0.00 |
April | 1136.98 | 498.03 | 638.95 | 1042.89 | 783.66 | 0.00 | 0.00 | 0.00 |
May | 1378.92 | 551.10 | 827.82 | 1492.01 | 486.93 | 0.00 | 0.00 | 0.00 |
June | 1277.97 | 462.61 | 815.35 | 1608.06 | 268.35 | 0.00 | 0.00 | 0.00 |
July | 1283.56 | 463.20 | 820.36 | 1794.60 | 149.22 | 0.00 | 0.00 | 0.00 |
August | 1445.32 | 651.69 | 793.63 | 2002.63 | 203.16 | 0.00 | 0.00 | 0.00 |
September | 1077.93 | 483.62 | 594.31 | 1279.50 | 386.74 | 0.00 | 0.00 | 0.00 |
October | 977.22 | 442.91 | 534.31 | 995.54 | 708.62 | 0.00 | 0.00 | 0.00 |
November | 604.33 | 232.07 | 372.27 | 408.42 | 1080.36 | 0.00 | 0.00 | 0.00 |
December | 470.81 | 221.06 | 249.75 | 264.25 | 1416.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 986.74 | 412.77 | 573.96 | 1027.51 | 801.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.81 | 192.00 | 249.75 | 237.69 | 149.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1445.32 | 651.69 | 827.82 | 2002.63 | 1550.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1779.03 | 1164.92 | 614.11 | 1568.34 | 2175.80 | 0.00 | 0.00 | 0.00 |
February | 2346.48 | 1553.17 | 793.30 | 2110.96 | 2220.00 | 0.00 | 0.00 | 0.00 |
March | 2116.97 | 1174.95 | 942.02 | 2042.18 | 1663.33 | 0.00 | 0.00 | 0.00 |
April | 1642.70 | 649.57 | 993.13 | 1646.30 | 1255.79 | 0.00 | 0.00 | 0.00 |
May | 1439.58 | 300.27 | 1139.31 | 1553.15 | 781.45 | 0.00 | 0.00 | 0.00 |
June | 1351.01 | 206.51 | 1144.49 | 1744.11 | 433.51 | 0.00 | 0.00 | 0.00 |
July | 1416.13 | 245.98 | 1170.15 | 2091.24 | 235.61 | 0.00 | 0.00 | 0.00 |
August | 1891.07 | 701.43 | 1189.65 | 2811.22 | 329.44 | 0.00 | 0.00 | 0.00 |
September | 2051.85 | 1061.30 | 990.55 | 2637.82 | 624.96 | 0.00 | 0.00 | 0.00 |
October | 2810.86 | 1762.60 | 1048.25 | 3309.77 | 1112.64 | 0.00 | 0.00 | 0.00 |
November | 1949.09 | 1170.52 | 778.57 | 1896.61 | 1601.26 | 0.00 | 0.00 | 0.00 |
December | 1928.20 | 1368.89 | 559.31 | 1795.82 | 2015.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1891.44 | 943.60 | 947.84 | 2101.85 | 1198.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1351.01 | 206.51 | 559.31 | 1553.15 | 235.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2810.86 | 1762.60 | 1189.65 | 3309.77 | 2220.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 472.79 | 193.65 | 279.13 | 242.61 | 1574.48 | 0.00 | 0.00 | 0.00 |
February | 697.19 | 306.21 | 390.98 | 403.82 | 1633.21 | 0.00 | 0.00 | 0.00 |
March | 1029.49 | 475.29 | 554.21 | 823.28 | 1102.96 | 0.00 | 0.00 | 0.00 |
April | 1125.19 | 481.44 | 643.75 | 1059.28 | 810.95 | 0.00 | 0.00 | 0.00 |
May | 1310.73 | 497.76 | 812.97 | 1444.69 | 505.79 | 0.00 | 0.00 | 0.00 |
June | 1434.55 | 578.59 | 855.96 | 1830.22 | 290.75 | 0.00 | 0.00 | 0.00 |
July | 1343.54 | 505.93 | 837.61 | 1881.94 | 163.28 | 0.00 | 0.00 | 0.00 |
August | 1486.32 | 688.06 | 798.25 | 2083.81 | 222.54 | 0.00 | 0.00 | 0.00 |
September | 1055.17 | 461.10 | 594.06 | 1286.52 | 406.97 | 0.00 | 0.00 | 0.00 |
October | 1046.12 | 508.70 | 537.42 | 1105.16 | 738.12 | 0.00 | 0.00 | 0.00 |
November | 491.25 | 141.97 | 349.28 | 274.59 | 1126.65 | 0.00 | 0.00 | 0.00 |
December | 436.96 | 189.07 | 247.89 | 229.31 | 1468.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 996.19 | 419.94 | 576.25 | 1060.17 | 832.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 436.96 | 141.97 | 247.89 | 229.31 | 163.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1486.32 | 688.06 | 855.96 | 2083.81 | 1633.21 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921101E+09 | 0.00 | 0.921101E+09 | 11059118.29 | 0.641306E+10 |
February | 0.113851E+10 | 0.00 | 0.113851E+10 | 52857887.61 | 0.608996E+10 |
March | 0.174798E+10 | 0.00 | 0.174798E+10 | 0.413809E+09 | 0.436629E+10 |
April | 0.203184E+10 | 5779133.69 | 0.202606E+10 | 0.107911E+10 | 0.292079E+10 |
May | 0.278545E+10 | 92812301.28 | 0.269264E+10 | 0.238834E+10 | 0.177599E+10 |
June | 0.285865E+10 | 0.153606E+09 | 0.270504E+10 | 0.338539E+10 | 0.960737E+09 |
July | 0.285469E+10 | 0.103235E+09 | 0.275146E+10 | 0.402978E+10 | 0.556781E+09 |
August | 0.252912E+10 | 30099956.33 | 0.249902E+10 | 0.352635E+10 | 0.756536E+09 |
September | 0.184504E+10 | 345498.63 | 0.184469E+10 | 0.189252E+10 | 0.140407E+10 |
October | 0.164997E+10 | 0.00 | 0.164997E+10 | 0.109173E+10 | 0.266424E+10 |
November | 0.111996E+10 | 0.00 | 0.111996E+10 | 0.216274E+09 | 0.417784E+10 |
December | 0.803445E+09 | 0.00 | 0.803445E+09 | 14696833.42 | 0.584967E+10 |
Annual Sum or Average | 0.222858E+11 | 0.385878E+09 | 0.218999E+11 | 0.181019E+11 | 0.379360E+11 |
Minimum of Months | 0.803445E+09 | 0.00 | 0.803445E+09 | 11059118.29 | 0.556781E+09 |
Maximum of Months | 0.285865E+10 | 0.153606E+09 | 0.275146E+10 | 0.402978E+10 | 0.641306E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128270E+10 | 0.514257E+09 | 0.768444E+09 | 0.651890E+09 | 0.391243E+10 |
February | 0.179669E+10 | 0.838153E+09 | 0.958538E+09 | 0.107854E+10 | 0.356716E+10 |
March | 0.253759E+10 | 0.107925E+10 | 0.145834E+10 | 0.198073E+10 | 0.276838E+10 |
April | 0.294705E+10 | 0.129089E+10 | 0.165616E+10 | 0.274883E+10 | 0.188754E+10 |
May | 0.369329E+10 | 0.147605E+10 | 0.221724E+10 | 0.402941E+10 | 0.121914E+10 |
June | 0.331249E+10 | 0.119909E+10 | 0.211340E+10 | 0.417328E+10 | 0.657950E+09 |
July | 0.343789E+10 | 0.124064E+10 | 0.219725E+10 | 0.479733E+10 | 0.378569E+09 |
August | 0.387115E+10 | 0.174549E+10 | 0.212566E+10 | 0.536139E+10 | 0.510970E+09 |
September | 0.279399E+10 | 0.125354E+10 | 0.154044E+10 | 0.334872E+10 | 0.917251E+09 |
October | 0.261739E+10 | 0.118628E+10 | 0.143111E+10 | 0.273250E+10 | 0.172222E+10 |
November | 0.156644E+10 | 0.601524E+09 | 0.964912E+09 | 0.111723E+10 | 0.255770E+10 |
December | 0.126102E+10 | 0.592095E+09 | 0.668925E+09 | 0.738575E+09 | 0.353192E+10 |
Annual Sum or Average | 0.311177E+11 | 0.130173E+11 | 0.181004E+11 | 0.327584E+11 | 0.236312E+11 |
Minimum of Months | 0.126102E+10 | 0.514257E+09 | 0.668925E+09 | 0.651890E+09 | 0.378569E+09 |
Maximum of Months | 0.387115E+10 | 0.174549E+10 | 0.221724E+10 | 0.536139E+10 | 0.391243E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.476494E+10 | 0.312011E+10 | 0.164483E+10 | 0.424577E+10 | 0.553291E+10 |
February | 0.567659E+10 | 0.375743E+10 | 0.191916E+10 | 0.517142E+10 | 0.507111E+10 |
March | 0.567009E+10 | 0.314698E+10 | 0.252310E+10 | 0.551054E+10 | 0.414083E+10 |
April | 0.425787E+10 | 0.168368E+10 | 0.257419E+10 | 0.430343E+10 | 0.301021E+10 |
May | 0.385578E+10 | 0.804248E+09 | 0.305153E+10 | 0.419755E+10 | 0.192711E+10 |
June | 0.350181E+10 | 0.535283E+09 | 0.296653E+10 | 0.452744E+10 | 0.104295E+10 |
July | 0.379295E+10 | 0.658828E+09 | 0.313412E+10 | 0.559060E+10 | 0.582668E+09 |
August | 0.506505E+10 | 0.187870E+10 | 0.318636E+10 | 0.752077E+10 | 0.812782E+09 |
September | 0.531839E+10 | 0.275088E+10 | 0.256752E+10 | 0.686986E+10 | 0.146492E+10 |
October | 0.752859E+10 | 0.472096E+10 | 0.280764E+10 | 0.892603E+10 | 0.269541E+10 |
November | 0.505203E+10 | 0.303398E+10 | 0.201805E+10 | 0.500729E+10 | 0.378681E+10 |
December | 0.516448E+10 | 0.366643E+10 | 0.149805E+10 | 0.489793E+10 | 0.500390E+10 |
Annual Sum or Average | 0.596486E+11 | 0.297575E+11 | 0.298911E+11 | 0.667686E+11 | 0.350716E+11 |
Minimum of Months | 0.350181E+10 | 0.535283E+09 | 0.149805E+10 | 0.419755E+10 | 0.582668E+09 |
Maximum of Months | 0.752859E+10 | 0.472096E+10 | 0.318636E+10 | 0.892603E+10 | 0.553291E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126631E+10 | 0.518684E+09 | 0.747631E+09 | 0.655692E+09 | 0.403075E+10 |
February | 0.168665E+10 | 0.740780E+09 | 0.945871E+09 | 0.988448E+09 | 0.375886E+10 |
March | 0.275739E+10 | 0.127301E+10 | 0.148438E+10 | 0.221903E+10 | 0.275224E+10 |
April | 0.291648E+10 | 0.124788E+10 | 0.166860E+10 | 0.275913E+10 | 0.194655E+10 |
May | 0.351066E+10 | 0.133320E+10 | 0.217745E+10 | 0.388266E+10 | 0.125674E+10 |
June | 0.371836E+10 | 0.149971E+10 | 0.221865E+10 | 0.473943E+10 | 0.705523E+09 |
July | 0.359853E+10 | 0.135509E+10 | 0.224344E+10 | 0.502500E+10 | 0.409796E+09 |
August | 0.398095E+10 | 0.184291E+10 | 0.213804E+10 | 0.557317E+10 | 0.554588E+09 |
September | 0.273499E+10 | 0.119518E+10 | 0.153981E+10 | 0.335485E+10 | 0.960012E+09 |
October | 0.280192E+10 | 0.136250E+10 | 0.143942E+10 | 0.299586E+10 | 0.179102E+10 |
November | 0.127333E+10 | 0.367999E+09 | 0.905330E+09 | 0.738499E+09 | 0.267640E+10 |
December | 0.117035E+10 | 0.506413E+09 | 0.663940E+09 | 0.630831E+09 | 0.366496E+10 |
Annual Sum or Average | 0.314159E+11 | 0.132434E+11 | 0.181726E+11 | 0.335626E+11 | 0.245074E+11 |
Minimum of Months | 0.117035E+10 | 0.367999E+09 | 0.663940E+09 | 0.630831E+09 | 0.409796E+09 |
Maximum of Months | 0.398095E+10 | 0.184291E+10 | 0.224344E+10 | 0.557317E+10 | 0.403075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307022E+09 | 0.00 | 0.307022E+09 | 3722652.61 | 0.220578E+10 |
February | 0.379488E+09 | 0.00 | 0.379488E+09 | 16709580.49 | 0.207164E+10 |
March | 0.582638E+09 | 0.00 | 0.582638E+09 | 0.154155E+09 | 0.148427E+10 |
April | 0.677253E+09 | 1926317.16 | 0.675327E+09 | 0.392613E+09 | 0.980853E+09 |
May | 0.928449E+09 | 30936458.39 | 0.897513E+09 | 0.852999E+09 | 0.574114E+09 |
June | 0.952847E+09 | 51200485.87 | 0.901647E+09 | 0.116511E+10 | 0.311756E+09 |
July | 0.951529E+09 | 34410484.92 | 0.917119E+09 | 0.137362E+10 | 0.177863E+09 |
August | 0.843010E+09 | 10033002.45 | 0.832977E+09 | 0.118867E+10 | 0.260946E+09 |
September | 0.614990E+09 | 115162.58 | 0.614874E+09 | 0.616067E+09 | 0.531577E+09 |
October | 0.549970E+09 | 0.00 | 0.549970E+09 | 0.337198E+09 | 0.101760E+10 |
November | 0.373308E+09 | 0.00 | 0.373308E+09 | 61256046.44 | 0.156335E+10 |
December | 0.267805E+09 | 0.00 | 0.267805E+09 | 2813468.28 | 0.210814E+10 |
Annual Sum or Average | 0.742831E+10 | 0.128622E+09 | 0.729969E+10 | 0.616492E+10 | 0.132879E+11 |
Minimum of Months | 0.267805E+09 | 0.00 | 0.267805E+09 | 2813468.28 | 0.177863E+09 |
Maximum of Months | 0.952847E+09 | 51200485.87 | 0.917119E+09 | 0.137362E+10 | 0.220578E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307037E+09 | 0.00 | 0.307037E+09 | 3722277.64 | 0.220592E+10 |
February | 0.379506E+09 | 0.00 | 0.379506E+09 | 16709433.62 | 0.207178E+10 |
March | 0.582666E+09 | 0.00 | 0.582666E+09 | 0.154159E+09 | 0.148437E+10 |
April | 0.677285E+09 | 1926391.55 | 0.675359E+09 | 0.392629E+09 | 0.980915E+09 |
May | 0.928493E+09 | 30937652.95 | 0.897555E+09 | 0.853034E+09 | 0.574149E+09 |
June | 0.952892E+09 | 51202462.89 | 0.901690E+09 | 0.116516E+10 | 0.311774E+09 |
July | 0.951574E+09 | 34411813.62 | 0.917162E+09 | 0.137368E+10 | 0.177872E+09 |
August | 0.843051E+09 | 10033389.86 | 0.833017E+09 | 0.118873E+10 | 0.260960E+09 |
September | 0.615019E+09 | 115167.02 | 0.614904E+09 | 0.616095E+09 | 0.531609E+09 |
October | 0.549997E+09 | 0.00 | 0.549997E+09 | 0.337211E+09 | 0.101766E+10 |
November | 0.373325E+09 | 0.00 | 0.373325E+09 | 61256915.00 | 0.156345E+10 |
December | 0.267818E+09 | 0.00 | 0.267818E+09 | 2813277.35 | 0.210827E+10 |
Annual Sum or Average | 0.742866E+10 | 0.128627E+09 | 0.730003E+10 | 0.616520E+10 | 0.132887E+11 |
Minimum of Months | 0.267818E+09 | 0.00 | 0.267818E+09 | 2813277.35 | 0.177872E+09 |
Maximum of Months | 0.952892E+09 | 51202462.89 | 0.917162E+09 | 0.137368E+10 | 0.220592E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307037E+09 | 0.00 | 0.307037E+09 | 3722277.64 | 0.220592E+10 |
February | 0.379506E+09 | 0.00 | 0.379506E+09 | 16709433.62 | 0.207178E+10 |
March | 0.582666E+09 | 0.00 | 0.582666E+09 | 0.154159E+09 | 0.148437E+10 |
April | 0.677285E+09 | 1926391.55 | 0.675359E+09 | 0.392629E+09 | 0.980915E+09 |
May | 0.928493E+09 | 30937652.95 | 0.897555E+09 | 0.853034E+09 | 0.574149E+09 |
June | 0.952892E+09 | 51202462.89 | 0.901690E+09 | 0.116516E+10 | 0.311774E+09 |
July | 0.951574E+09 | 34411813.62 | 0.917162E+09 | 0.137368E+10 | 0.177872E+09 |
August | 0.843051E+09 | 10033389.86 | 0.833017E+09 | 0.118873E+10 | 0.260960E+09 |
September | 0.615019E+09 | 115167.02 | 0.614904E+09 | 0.616095E+09 | 0.531609E+09 |
October | 0.549997E+09 | 0.00 | 0.549997E+09 | 0.337211E+09 | 0.101766E+10 |
November | 0.373325E+09 | 0.00 | 0.373325E+09 | 61256915.00 | 0.156345E+10 |
December | 0.267818E+09 | 0.00 | 0.267818E+09 | 2813277.35 | 0.210827E+10 |
Annual Sum or Average | 0.742866E+10 | 0.128627E+09 | 0.730003E+10 | 0.616520E+10 | 0.132887E+11 |
Minimum of Months | 0.267818E+09 | 0.00 | 0.267818E+09 | 2813277.35 | 0.177872E+09 |
Maximum of Months | 0.952892E+09 | 51202462.89 | 0.917162E+09 | 0.137368E+10 | 0.220592E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123396E+10 | 0.494717E+09 | 0.739240E+09 | 0.631766E+09 | 0.391696E+10 |
February | 0.172841E+10 | 0.806306E+09 | 0.922108E+09 | 0.104110E+10 | 0.355695E+10 |
March | 0.244116E+10 | 0.103824E+10 | 0.140292E+10 | 0.195260E+10 | 0.275602E+10 |
April | 0.283506E+10 | 0.124184E+10 | 0.159321E+10 | 0.271228E+10 | 0.186915E+10 |
May | 0.355294E+10 | 0.141997E+10 | 0.213297E+10 | 0.397947E+10 | 0.117411E+10 |
June | 0.318660E+10 | 0.115353E+10 | 0.203308E+10 | 0.408911E+10 | 0.637024E+09 |
July | 0.330724E+10 | 0.119350E+10 | 0.211374E+10 | 0.468054E+10 | 0.369206E+09 |
August | 0.372403E+10 | 0.167917E+10 | 0.204487E+10 | 0.519920E+10 | 0.535593E+09 |
September | 0.268781E+10 | 0.120591E+10 | 0.148189E+10 | 0.320780E+10 | 0.102340E+10 |
October | 0.251792E+10 | 0.114121E+10 | 0.137671E+10 | 0.257373E+10 | 0.194112E+10 |
November | 0.150691E+10 | 0.578669E+09 | 0.928241E+09 | 0.102694E+10 | 0.279945E+10 |
December | 0.121310E+10 | 0.569598E+09 | 0.643503E+09 | 0.690953E+09 | 0.371556E+10 |
Annual Sum or Average | 0.299351E+11 | 0.125227E+11 | 0.174125E+11 | 0.317855E+11 | 0.242945E+11 |
Minimum of Months | 0.121310E+10 | 0.494717E+09 | 0.643503E+09 | 0.631766E+09 | 0.369206E+09 |
Maximum of Months | 0.372403E+10 | 0.167917E+10 | 0.213297E+10 | 0.519920E+10 | 0.391696E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48789536.05 | 19560666.34 | 29228869.71 | 24979444.00 | 0.154873E+09 |
February | 68339915.84 | 31880613.26 | 36459302.58 | 41164140.50 | 0.140639E+09 |
March | 96521219.46 | 41051147.96 | 55470071.51 | 77204175.78 | 0.108970E+09 |
April | 0.112096E+09 | 49101353.26 | 62994279.60 | 0.107241E+09 | 73904432.39 |
May | 0.140480E+09 | 56144309.51 | 84335799.93 | 0.157345E+09 | 46423276.55 |
June | 0.125995E+09 | 45609457.30 | 80385987.32 | 0.161680E+09 | 25187351.03 |
July | 0.130765E+09 | 47189953.42 | 83575326.18 | 0.185064E+09 | 14598090.90 |
August | 0.147245E+09 | 66392729.50 | 80852158.74 | 0.205572E+09 | 21176862.47 |
September | 0.106274E+09 | 47680786.21 | 58592781.41 | 0.126833E+09 | 40464193.33 |
October | 99556375.12 | 45122333.27 | 54434041.85 | 0.101763E+09 | 76750235.96 |
November | 59581840.27 | 22880038.17 | 36701802.10 | 40604289.61 | 0.110688E+09 |
December | 47964906.78 | 22521383.53 | 25443523.25 | 27319665.31 | 0.146910E+09 |
Annual Sum or Average | 0.118361E+10 | 0.495135E+09 | 0.688474E+09 | 0.125677E+10 | 0.960584E+09 |
Minimum of Months | 47964906.78 | 19560666.34 | 25443523.25 | 24979444.00 | 14598090.90 |
Maximum of Months | 0.147245E+09 | 66392729.50 | 84335799.93 | 0.205572E+09 | 0.154873E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158836E+10 | 0.104007E+10 | 0.548292E+09 | 0.144946E+10 | 0.193547E+10 |
February | 0.189225E+10 | 0.125251E+10 | 0.639736E+09 | 0.175876E+10 | 0.178190E+10 |
March | 0.189008E+10 | 0.104902E+10 | 0.841054E+09 | 0.189124E+10 | 0.144726E+10 |
April | 0.141932E+10 | 0.561241E+09 | 0.858083E+09 | 0.148267E+10 | 0.103093E+10 |
May | 0.128529E+10 | 0.268090E+09 | 0.101720E+10 | 0.146194E+10 | 0.631782E+09 |
June | 0.116730E+10 | 0.178432E+09 | 0.988866E+09 | 0.155186E+10 | 0.343527E+09 |
July | 0.126435E+10 | 0.219615E+09 | 0.104473E+10 | 0.189602E+10 | 0.194046E+09 |
August | 0.168839E+10 | 0.626250E+09 | 0.106214E+10 | 0.252729E+10 | 0.298399E+09 |
September | 0.177284E+10 | 0.916984E+09 | 0.855859E+09 | 0.228923E+10 | 0.577406E+09 |
October | 0.250960E+10 | 0.157369E+10 | 0.935902E+09 | 0.296683E+10 | 0.108370E+10 |
November | 0.168405E+10 | 0.101135E+10 | 0.672701E+09 | 0.165940E+10 | 0.145568E+10 |
December | 0.172154E+10 | 0.122218E+10 | 0.499363E+09 | 0.163382E+10 | 0.184739E+10 |
Annual Sum or Average | 0.198834E+11 | 0.991944E+10 | 0.996393E+10 | 0.225685E+11 | 0.126275E+11 |
Minimum of Months | 0.116730E+10 | 0.178432E+09 | 0.499363E+09 | 0.144946E+10 | 0.194046E+09 |
Maximum of Months | 0.250960E+10 | 0.157369E+10 | 0.106214E+10 | 0.296683E+10 | 0.193547E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158836E+10 | 0.104007E+10 | 0.548292E+09 | 0.144946E+10 | 0.193547E+10 |
February | 0.189225E+10 | 0.125251E+10 | 0.639736E+09 | 0.175876E+10 | 0.178190E+10 |
March | 0.189008E+10 | 0.104902E+10 | 0.841054E+09 | 0.189124E+10 | 0.144726E+10 |
April | 0.141932E+10 | 0.561241E+09 | 0.858083E+09 | 0.148267E+10 | 0.103093E+10 |
May | 0.128529E+10 | 0.268090E+09 | 0.101720E+10 | 0.146194E+10 | 0.631782E+09 |
June | 0.116730E+10 | 0.178432E+09 | 0.988866E+09 | 0.155186E+10 | 0.343527E+09 |
July | 0.126435E+10 | 0.219615E+09 | 0.104473E+10 | 0.189602E+10 | 0.194046E+09 |
August | 0.168839E+10 | 0.626250E+09 | 0.106214E+10 | 0.252729E+10 | 0.298399E+09 |
September | 0.177284E+10 | 0.916984E+09 | 0.855859E+09 | 0.228923E+10 | 0.577406E+09 |
October | 0.250960E+10 | 0.157369E+10 | 0.935902E+09 | 0.296683E+10 | 0.108370E+10 |
November | 0.168405E+10 | 0.101135E+10 | 0.672701E+09 | 0.165940E+10 | 0.145568E+10 |
December | 0.172154E+10 | 0.122218E+10 | 0.499363E+09 | 0.163382E+10 | 0.184739E+10 |
Annual Sum or Average | 0.198834E+11 | 0.991944E+10 | 0.996393E+10 | 0.225685E+11 | 0.126275E+11 |
Minimum of Months | 0.116730E+10 | 0.178432E+09 | 0.499363E+09 | 0.144946E+10 | 0.194046E+09 |
Maximum of Months | 0.250960E+10 | 0.157369E+10 | 0.106214E+10 | 0.296683E+10 | 0.193547E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158826E+10 | 0.104000E+10 | 0.548257E+09 | 0.144936E+10 | 0.193535E+10 |
February | 0.189213E+10 | 0.125243E+10 | 0.639695E+09 | 0.175864E+10 | 0.178179E+10 |
March | 0.188996E+10 | 0.104896E+10 | 0.841001E+09 | 0.189112E+10 | 0.144716E+10 |
April | 0.141923E+10 | 0.561206E+09 | 0.858029E+09 | 0.148257E+10 | 0.103086E+10 |
May | 0.128521E+10 | 0.268073E+09 | 0.101714E+10 | 0.146184E+10 | 0.631742E+09 |
June | 0.116722E+10 | 0.178421E+09 | 0.988803E+09 | 0.155176E+10 | 0.343505E+09 |
July | 0.126427E+10 | 0.219601E+09 | 0.104467E+10 | 0.189590E+10 | 0.194034E+09 |
August | 0.168829E+10 | 0.626211E+09 | 0.106208E+10 | 0.252713E+10 | 0.298380E+09 |
September | 0.177273E+10 | 0.916926E+09 | 0.855805E+09 | 0.228909E+10 | 0.577369E+09 |
October | 0.250944E+10 | 0.157360E+10 | 0.935843E+09 | 0.296664E+10 | 0.108363E+10 |
November | 0.168395E+10 | 0.101129E+10 | 0.672659E+09 | 0.165929E+10 | 0.145559E+10 |
December | 0.172143E+10 | 0.122210E+10 | 0.499332E+09 | 0.163372E+10 | 0.184727E+10 |
Annual Sum or Average | 0.198821E+11 | 0.991881E+10 | 0.996330E+10 | 0.225671E+11 | 0.126267E+11 |
Minimum of Months | 0.116722E+10 | 0.178421E+09 | 0.499332E+09 | 0.144936E+10 | 0.194034E+09 |
Maximum of Months | 0.250944E+10 | 0.157360E+10 | 0.106208E+10 | 0.296664E+10 | 0.193535E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121819E+10 | 0.498974E+09 | 0.719216E+09 | 0.646650E+09 | 0.402750E+10 |
February | 0.162255E+10 | 0.712631E+09 | 0.909920E+09 | 0.977983E+09 | 0.373976E+10 |
March | 0.265260E+10 | 0.122463E+10 | 0.142797E+10 | 0.220247E+10 | 0.276453E+10 |
April | 0.280565E+10 | 0.120046E+10 | 0.160518E+10 | 0.273513E+10 | 0.194061E+10 |
May | 0.337723E+10 | 0.128254E+10 | 0.209469E+10 | 0.383376E+10 | 0.122224E+10 |
June | 0.357705E+10 | 0.144273E+10 | 0.213432E+10 | 0.462865E+10 | 0.700680E+09 |
July | 0.346177E+10 | 0.130359E+10 | 0.215817E+10 | 0.489416E+10 | 0.407404E+09 |
August | 0.382966E+10 | 0.177288E+10 | 0.205678E+10 | 0.539160E+10 | 0.588760E+09 |
September | 0.263105E+10 | 0.114976E+10 | 0.148129E+10 | 0.320289E+10 | 0.107507E+10 |
October | 0.269544E+10 | 0.131073E+10 | 0.138471E+10 | 0.283918E+10 | 0.202706E+10 |
November | 0.122494E+10 | 0.354015E+09 | 0.870921E+09 | 0.688471E+09 | 0.290994E+10 |
December | 0.112588E+10 | 0.487169E+09 | 0.638706E+09 | 0.601995E+09 | 0.384360E+10 |
Annual Sum or Average | 0.302220E+11 | 0.127401E+11 | 0.174819E+11 | 0.326429E+11 | 0.252472E+11 |
Minimum of Months | 0.112588E+10 | 0.354015E+09 | 0.638706E+09 | 0.601995E+09 | 0.407404E+09 |
Maximum of Months | 0.382966E+10 | 0.177288E+10 | 0.215817E+10 | 0.539160E+10 | 0.402750E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48166139.39 | 19729001.55 | 28437137.84 | 25567965.69 | 0.159244E+09 |
February | 64154199.56 | 28176776.42 | 35977423.14 | 38668549.95 | 0.147867E+09 |
March | 0.104881E+09 | 48420850.92 | 56460502.63 | 87083653.80 | 0.109307E+09 |
April | 0.110933E+09 | 47465253.55 | 63467428.14 | 0.108145E+09 | 76729863.73 |
May | 0.133533E+09 | 50710587.64 | 82822223.37 | 0.151583E+09 | 48326133.19 |
June | 0.141433E+09 | 57044083.69 | 84389150.75 | 0.183013E+09 | 27704262.54 |
July | 0.136875E+09 | 51542969.10 | 85332167.44 | 0.193511E+09 | 16108383.71 |
August | 0.151421E+09 | 70098035.80 | 81323096.87 | 0.213179E+09 | 23279020.94 |
September | 0.104029E+09 | 45460580.57 | 58568751.36 | 0.126639E+09 | 42507279.13 |
October | 0.106575E+09 | 51824924.43 | 54750283.91 | 0.112259E+09 | 80148113.32 |
November | 48432893.25 | 13997450.41 | 34435442.83 | 27221512.91 | 0.115057E+09 |
December | 44516084.92 | 19262241.83 | 25253843.09 | 23802343.78 | 0.151972E+09 |
Annual Sum or Average | 0.119495E+10 | 0.503733E+09 | 0.691217E+09 | 0.129067E+10 | 0.998250E+09 |
Minimum of Months | 44516084.92 | 13997450.41 | 25253843.09 | 23802343.78 | 16108383.71 |
Maximum of Months | 0.151421E+09 | 70098035.80 | 85332167.44 | 0.213179E+09 | 0.159244E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921101E+09 | 0.00 | 0.921101E+09 | 8718507.41 | 0.669965E+10 |
February | 0.113851E+10 | 0.00 | 0.113851E+10 | 41660141.81 | 0.638161E+10 |
March | 0.174798E+10 | 0.00 | 0.174798E+10 | 0.391807E+09 | 0.467876E+10 |
April | 0.203184E+10 | 5779133.69 | 0.202606E+10 | 0.103709E+10 | 0.316646E+10 |
May | 0.278545E+10 | 92812301.28 | 0.269264E+10 | 0.232549E+10 | 0.192902E+10 |
June | 0.285865E+10 | 0.153606E+09 | 0.270504E+10 | 0.336393E+10 | 0.103349E+10 |
July | 0.285469E+10 | 0.103235E+09 | 0.275146E+10 | 0.403095E+10 | 0.600980E+09 |
August | 0.252912E+10 | 30099956.33 | 0.249902E+10 | 0.351731E+10 | 0.823968E+09 |
September | 0.184504E+10 | 345498.63 | 0.184469E+10 | 0.183806E+10 | 0.156858E+10 |
October | 0.164997E+10 | 0.00 | 0.164997E+10 | 0.101159E+10 | 0.297082E+10 |
November | 0.111996E+10 | 0.00 | 0.111996E+10 | 0.183120E+09 | 0.456753E+10 |
December | 0.803445E+09 | 0.00 | 0.803445E+09 | 8244489.04 | 0.627022E+10 |
Annual Sum or Average | 0.222858E+11 | 0.385878E+09 | 0.218999E+11 | 0.177580E+11 | 0.406911E+11 |
Minimum of Months | 0.803445E+09 | 0.00 | 0.803445E+09 | 8244489.04 | 0.600980E+09 |
Maximum of Months | 0.285865E+10 | 0.153606E+09 | 0.275146E+10 | 0.403095E+10 | 0.669965E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128270E+10 | 0.514257E+09 | 0.768444E+09 | 0.636636E+09 | 0.409245E+10 |
February | 0.179669E+10 | 0.838153E+09 | 0.958538E+09 | 0.104629E+10 | 0.375120E+10 |
March | 0.253759E+10 | 0.107925E+10 | 0.145834E+10 | 0.193338E+10 | 0.297331E+10 |
April | 0.294705E+10 | 0.129089E+10 | 0.165616E+10 | 0.270316E+10 | 0.203125E+10 |
May | 0.369329E+10 | 0.147605E+10 | 0.221724E+10 | 0.399619E+10 | 0.130419E+10 |
June | 0.331249E+10 | 0.119909E+10 | 0.211340E+10 | 0.416810E+10 | 0.695563E+09 |
July | 0.343789E+10 | 0.124064E+10 | 0.219725E+10 | 0.480666E+10 | 0.399667E+09 |
August | 0.387115E+10 | 0.174549E+10 | 0.212566E+10 | 0.536385E+10 | 0.544147E+09 |
September | 0.279399E+10 | 0.125354E+10 | 0.154044E+10 | 0.331647E+10 | 0.100243E+10 |
October | 0.261739E+10 | 0.118628E+10 | 0.143111E+10 | 0.266646E+10 | 0.189798E+10 |
November | 0.156644E+10 | 0.601524E+09 | 0.964912E+09 | 0.105862E+10 | 0.280031E+10 |
December | 0.126102E+10 | 0.592095E+09 | 0.668925E+09 | 0.707755E+09 | 0.379398E+10 |
Annual Sum or Average | 0.311177E+11 | 0.130173E+11 | 0.181004E+11 | 0.324036E+11 | 0.252865E+11 |
Minimum of Months | 0.126102E+10 | 0.514257E+09 | 0.668925E+09 | 0.636636E+09 | 0.399667E+09 |
Maximum of Months | 0.387115E+10 | 0.174549E+10 | 0.221724E+10 | 0.536385E+10 | 0.409245E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.476494E+10 | 0.312011E+10 | 0.164483E+10 | 0.420065E+10 | 0.582767E+10 |
February | 0.567659E+10 | 0.375743E+10 | 0.191916E+10 | 0.510684E+10 | 0.537063E+10 |
March | 0.567009E+10 | 0.314698E+10 | 0.252310E+10 | 0.546978E+10 | 0.445508E+10 |
April | 0.425787E+10 | 0.168368E+10 | 0.257419E+10 | 0.426720E+10 | 0.325501E+10 |
May | 0.385578E+10 | 0.804248E+09 | 0.305153E+10 | 0.415996E+10 | 0.209305E+10 |
June | 0.350181E+10 | 0.535283E+09 | 0.296653E+10 | 0.452073E+10 | 0.112365E+10 |
July | 0.379295E+10 | 0.658828E+09 | 0.313412E+10 | 0.560119E+10 | 0.631054E+09 |
August | 0.506505E+10 | 0.187870E+10 | 0.318636E+10 | 0.752958E+10 | 0.882366E+09 |
September | 0.531839E+10 | 0.275088E+10 | 0.256752E+10 | 0.683722E+10 | 0.161990E+10 |
October | 0.752859E+10 | 0.472096E+10 | 0.280764E+10 | 0.886489E+10 | 0.298009E+10 |
November | 0.505203E+10 | 0.303398E+10 | 0.201805E+10 | 0.491601E+10 | 0.415046E+10 |
December | 0.516448E+10 | 0.366643E+10 | 0.149805E+10 | 0.480992E+10 | 0.539849E+10 |
Annual Sum or Average | 0.596486E+11 | 0.297575E+11 | 0.298911E+11 | 0.662840E+11 | 0.377874E+11 |
Minimum of Months | 0.350181E+10 | 0.535283E+09 | 0.149805E+10 | 0.415996E+10 | 0.631054E+09 |
Maximum of Months | 0.752859E+10 | 0.472096E+10 | 0.318636E+10 | 0.886489E+10 | 0.582767E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126631E+10 | 0.518684E+09 | 0.747631E+09 | 0.649820E+09 | 0.421708E+10 |
February | 0.168665E+10 | 0.740780E+09 | 0.945871E+09 | 0.976926E+09 | 0.395106E+10 |
March | 0.275739E+10 | 0.127301E+10 | 0.148438E+10 | 0.220508E+10 | 0.295416E+10 |
April | 0.291648E+10 | 0.124788E+10 | 0.166860E+10 | 0.274566E+10 | 0.210199E+10 |
May | 0.351066E+10 | 0.133320E+10 | 0.217745E+10 | 0.386946E+10 | 0.135471E+10 |
June | 0.371836E+10 | 0.149971E+10 | 0.221865E+10 | 0.474393E+10 | 0.753615E+09 |
July | 0.359853E+10 | 0.135509E+10 | 0.224344E+10 | 0.504060E+10 | 0.437338E+09 |
August | 0.398095E+10 | 0.184291E+10 | 0.213804E+10 | 0.558129E+10 | 0.596039E+09 |
September | 0.273499E+10 | 0.119518E+10 | 0.153981E+10 | 0.333467E+10 | 0.105485E+10 |
October | 0.280192E+10 | 0.136250E+10 | 0.143942E+10 | 0.296005E+10 | 0.197699E+10 |
November | 0.127333E+10 | 0.367999E+09 | 0.905330E+09 | 0.711746E+09 | 0.292028E+10 |
December | 0.117035E+10 | 0.506413E+09 | 0.663940E+09 | 0.614192E+09 | 0.393301E+10 |
Annual Sum or Average | 0.314159E+11 | 0.132434E+11 | 0.181726E+11 | 0.334334E+11 | 0.262511E+11 |
Minimum of Months | 0.117035E+10 | 0.367999E+09 | 0.663940E+09 | 0.614192E+09 | 0.437338E+09 |
Maximum of Months | 0.398095E+10 | 0.184291E+10 | 0.224344E+10 | 0.558129E+10 | 0.421708E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.13 | 2394.36 | 343.90 | 0.00 | 343.90 | 0.00 | 0.00 |
February | 21.85 | 2517.34 | 470.61 | 0.00 | 470.61 | 0.00 | 0.00 |
March | 154.50 | 1630.19 | 652.62 | 0.00 | 652.62 | 0.00 | 0.00 |
April | 416.32 | 1126.85 | 783.89 | 2.23 | 781.66 | 0.00 | 0.00 |
May | 891.71 | 663.08 | 1039.97 | 34.65 | 1005.32 | 0.00 | 0.00 |
June | 1306.09 | 370.65 | 1102.87 | 59.26 | 1043.61 | 0.00 | 0.00 |
July | 1504.55 | 207.88 | 1065.82 | 38.54 | 1027.28 | 0.00 | 0.00 |
August | 1316.59 | 282.46 | 944.27 | 11.24 | 933.03 | 0.00 | 0.00 |
September | 730.14 | 541.70 | 711.82 | 0.13 | 711.69 | 0.00 | 0.00 |
October | 407.61 | 994.71 | 616.03 | 0.00 | 616.03 | 0.00 | 0.00 |
November | 83.44 | 1611.82 | 432.08 | 0.00 | 432.08 | 0.00 | 0.00 |
December | 5.49 | 2184.02 | 299.97 | 0.00 | 299.97 | 0.00 | 0.00 |
Annual Sum or Average | 574.01 | 1202.94 | 706.68 | 12.24 | 694.44 | 0.00 | 0.00 |
Minimum of Months | 4.13 | 207.88 | 299.97 | 0.00 | 299.97 | 0.00 | 0.00 |
Maximum of Months | 1504.55 | 2517.34 | 1102.87 | 59.26 | 1043.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 243.39 | 1460.73 | 478.91 | 192.00 | 286.90 | 0.00 | 0.00 |
February | 445.83 | 1474.52 | 742.68 | 346.46 | 396.22 | 0.00 | 0.00 |
March | 739.52 | 1033.59 | 947.43 | 402.95 | 544.48 | 0.00 | 0.00 |
April | 1060.50 | 728.22 | 1136.98 | 498.03 | 638.95 | 0.00 | 0.00 |
May | 1504.41 | 455.17 | 1378.92 | 551.10 | 827.82 | 0.00 | 0.00 |
June | 1610.06 | 253.84 | 1277.97 | 462.61 | 815.35 | 0.00 | 0.00 |
July | 1791.12 | 141.34 | 1283.56 | 463.20 | 820.36 | 0.00 | 0.00 |
August | 2001.72 | 190.77 | 1445.32 | 651.69 | 793.63 | 0.00 | 0.00 |
September | 1291.94 | 353.88 | 1077.93 | 483.62 | 594.31 | 0.00 | 0.00 |
October | 1020.20 | 643.00 | 977.22 | 442.91 | 534.31 | 0.00 | 0.00 |
November | 431.03 | 986.77 | 604.33 | 232.07 | 372.27 | 0.00 | 0.00 |
December | 275.75 | 1318.67 | 470.81 | 221.06 | 249.75 | 0.00 | 0.00 |
Annual Sum or Average | 1038.76 | 749.34 | 986.74 | 412.77 | 573.96 | 0.00 | 0.00 |
Minimum of Months | 243.39 | 141.34 | 470.81 | 192.00 | 249.75 | 0.00 | 0.00 |
Maximum of Months | 2001.72 | 1474.52 | 1445.32 | 651.69 | 827.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1585.19 | 2065.75 | 1779.03 | 1164.92 | 614.11 | 0.00 | 0.00 |
February | 2137.66 | 2096.19 | 2346.48 | 1553.17 | 793.30 | 0.00 | 0.00 |
March | 2057.40 | 1546.01 | 2116.97 | 1174.95 | 942.02 | 0.00 | 0.00 |
April | 1660.27 | 1161.35 | 1642.70 | 649.57 | 993.13 | 0.00 | 0.00 |
May | 1567.19 | 719.50 | 1439.58 | 300.27 | 1139.31 | 0.00 | 0.00 |
June | 1746.70 | 402.37 | 1351.01 | 206.51 | 1144.49 | 0.00 | 0.00 |
July | 2087.29 | 217.54 | 1416.13 | 245.98 | 1170.15 | 0.00 | 0.00 |
August | 2807.93 | 303.46 | 1891.07 | 701.43 | 1189.65 | 0.00 | 0.00 |
September | 2650.41 | 565.17 | 2051.85 | 1061.30 | 990.55 | 0.00 | 0.00 |
October | 3332.60 | 1006.35 | 2810.86 | 1762.60 | 1048.25 | 0.00 | 0.00 |
November | 1931.83 | 1460.96 | 1949.09 | 1170.52 | 778.57 | 0.00 | 0.00 |
December | 1828.68 | 1868.24 | 1928.20 | 1368.89 | 559.31 | 0.00 | 0.00 |
Annual Sum or Average | 2117.22 | 1112.11 | 1891.44 | 943.60 | 947.84 | 0.00 | 0.00 |
Minimum of Months | 1567.19 | 217.54 | 1351.01 | 206.51 | 559.31 | 0.00 | 0.00 |
Maximum of Months | 3332.60 | 2096.19 | 2810.86 | 1762.60 | 1189.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 244.81 | 1504.91 | 472.79 | 193.65 | 279.13 | 0.00 | 0.00 |
February | 408.58 | 1553.76 | 697.19 | 306.21 | 390.98 | 0.00 | 0.00 |
March | 828.49 | 1027.57 | 1029.49 | 475.29 | 554.21 | 0.00 | 0.00 |
April | 1064.48 | 750.98 | 1125.19 | 481.44 | 643.75 | 0.00 | 0.00 |
May | 1449.62 | 469.21 | 1310.73 | 497.76 | 812.97 | 0.00 | 0.00 |
June | 1828.49 | 272.19 | 1434.55 | 578.59 | 855.96 | 0.00 | 0.00 |
July | 1876.12 | 153.00 | 1343.54 | 505.93 | 837.61 | 0.00 | 0.00 |
August | 2080.78 | 207.06 | 1486.32 | 688.06 | 798.25 | 0.00 | 0.00 |
September | 1294.31 | 370.37 | 1055.17 | 461.10 | 594.06 | 0.00 | 0.00 |
October | 1118.53 | 668.69 | 1046.12 | 508.70 | 537.42 | 0.00 | 0.00 |
November | 284.91 | 1032.56 | 491.25 | 141.97 | 349.28 | 0.00 | 0.00 |
December | 235.53 | 1368.34 | 436.96 | 189.07 | 247.89 | 0.00 | 0.00 |
Annual Sum or Average | 1064.26 | 777.13 | 996.19 | 419.94 | 576.25 | 0.00 | 0.00 |
Minimum of Months | 235.53 | 153.00 | 436.96 | 141.97 | 247.89 | 0.00 | 0.00 |
Maximum of Months | 2080.78 | 1553.76 | 1486.32 | 688.06 | 855.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.17 | 2470.74 | 343.90 | 0.00 | 343.90 | 0.00 | 0.00 |
February | 20.72 | 2569.11 | 470.61 | 0.00 | 470.61 | 0.00 | 0.00 |
March | 172.67 | 1662.56 | 652.62 | 0.00 | 652.62 | 0.00 | 0.00 |
April | 454.43 | 1135.29 | 783.88 | 2.23 | 781.65 | 0.00 | 0.00 |
May | 955.45 | 643.08 | 1039.96 | 34.65 | 1005.31 | 0.00 | 0.00 |
June | 1348.55 | 360.84 | 1102.87 | 59.26 | 1043.61 | 0.00 | 0.00 |
July | 1538.60 | 199.23 | 1065.81 | 38.54 | 1027.27 | 0.00 | 0.00 |
August | 1331.44 | 292.29 | 944.26 | 11.24 | 933.02 | 0.00 | 0.00 |
September | 713.06 | 615.28 | 711.82 | 0.13 | 711.68 | 0.00 | 0.00 |
October | 377.70 | 1139.83 | 616.03 | 0.00 | 616.03 | 0.00 | 0.00 |
November | 70.90 | 1809.51 | 432.08 | 0.00 | 432.08 | 0.00 | 0.00 |
December | 3.15 | 2361.37 | 299.97 | 0.00 | 299.97 | 0.00 | 0.00 |
Annual Sum or Average | 586.48 | 1264.12 | 706.67 | 12.24 | 694.44 | 0.00 | 0.00 |
Minimum of Months | 3.15 | 199.23 | 299.97 | 0.00 | 299.97 | 0.00 | 0.00 |
Maximum of Months | 1538.60 | 2569.11 | 1102.87 | 59.26 | 1043.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 245.20 | 1520.25 | 478.92 | 192.01 | 286.91 | 0.00 | 0.00 |
February | 447.36 | 1528.44 | 742.71 | 346.47 | 396.23 | 0.00 | 0.00 |
March | 757.84 | 1069.66 | 947.46 | 402.96 | 544.50 | 0.00 | 0.00 |
April | 1087.78 | 749.63 | 1137.02 | 498.05 | 638.97 | 0.00 | 0.00 |
May | 1544.51 | 455.70 | 1378.97 | 551.12 | 827.85 | 0.00 | 0.00 |
June | 1639.97 | 255.48 | 1278.01 | 462.63 | 815.38 | 0.00 | 0.00 |
July | 1816.61 | 143.30 | 1283.60 | 463.22 | 820.38 | 0.00 | 0.00 |
August | 2017.91 | 207.87 | 1445.37 | 651.72 | 793.65 | 0.00 | 0.00 |
September | 1286.51 | 410.44 | 1077.96 | 483.64 | 594.32 | 0.00 | 0.00 |
October | 998.91 | 753.39 | 977.25 | 442.92 | 534.33 | 0.00 | 0.00 |
November | 411.86 | 1122.74 | 604.36 | 232.08 | 372.28 | 0.00 | 0.00 |
December | 268.17 | 1442.08 | 470.83 | 221.07 | 249.76 | 0.00 | 0.00 |
Annual Sum or Average | 1047.76 | 800.83 | 986.77 | 412.79 | 573.98 | 0.00 | 0.00 |
Minimum of Months | 245.20 | 143.30 | 470.83 | 192.01 | 249.76 | 0.00 | 0.00 |
Maximum of Months | 2017.91 | 1528.44 | 1445.37 | 651.72 | 827.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1623.46 | 2167.82 | 1779.04 | 1164.92 | 614.11 | 0.00 | 0.00 |
February | 2180.95 | 2209.65 | 2346.49 | 1553.18 | 793.31 | 0.00 | 0.00 |
March | 2118.27 | 1621.00 | 2116.98 | 1174.96 | 942.02 | 0.00 | 0.00 |
April | 1716.01 | 1193.18 | 1642.70 | 649.57 | 993.13 | 0.00 | 0.00 |
May | 1637.44 | 707.63 | 1439.59 | 300.27 | 1139.31 | 0.00 | 0.00 |
June | 1796.09 | 397.59 | 1351.01 | 206.51 | 1144.50 | 0.00 | 0.00 |
July | 2123.63 | 217.34 | 1416.13 | 245.98 | 1170.15 | 0.00 | 0.00 |
August | 2830.68 | 334.22 | 1891.08 | 701.43 | 1189.65 | 0.00 | 0.00 |
September | 2649.52 | 668.28 | 2051.86 | 1061.30 | 990.56 | 0.00 | 0.00 |
October | 3322.99 | 1213.79 | 2810.87 | 1762.61 | 1048.26 | 0.00 | 0.00 |
November | 1920.56 | 1684.78 | 1949.10 | 1170.52 | 778.57 | 0.00 | 0.00 |
December | 1829.96 | 2069.16 | 1928.21 | 1368.90 | 559.31 | 0.00 | 0.00 |
Annual Sum or Average | 2146.88 | 1201.22 | 1891.45 | 943.61 | 947.84 | 0.00 | 0.00 |
Minimum of Months | 1623.46 | 217.34 | 1351.01 | 206.51 | 559.31 | 0.00 | 0.00 |
Maximum of Months | 3322.99 | 2209.65 | 2810.87 | 1762.61 | 1189.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 250.98 | 1563.15 | 472.80 | 193.66 | 279.14 | 0.00 | 0.00 |
February | 420.24 | 1606.99 | 697.22 | 306.22 | 391.00 | 0.00 | 0.00 |
March | 854.82 | 1072.97 | 1029.53 | 475.30 | 554.22 | 0.00 | 0.00 |
April | 1096.94 | 778.29 | 1125.22 | 481.45 | 643.77 | 0.00 | 0.00 |
May | 1487.96 | 474.37 | 1310.77 | 497.78 | 812.99 | 0.00 | 0.00 |
June | 1856.35 | 281.01 | 1434.60 | 578.61 | 855.98 | 0.00 | 0.00 |
July | 1899.52 | 158.12 | 1343.58 | 505.95 | 837.63 | 0.00 | 0.00 |
August | 2092.58 | 228.51 | 1486.36 | 688.09 | 798.27 | 0.00 | 0.00 |
September | 1284.54 | 431.16 | 1055.20 | 461.12 | 594.08 | 0.00 | 0.00 |
October | 1101.94 | 786.74 | 1046.15 | 508.72 | 537.43 | 0.00 | 0.00 |
November | 276.12 | 1167.05 | 491.27 | 141.98 | 349.29 | 0.00 | 0.00 |
December | 233.65 | 1491.78 | 436.97 | 189.08 | 247.89 | 0.00 | 0.00 |
Annual Sum or Average | 1076.03 | 832.24 | 996.22 | 419.96 | 576.26 | 0.00 | 0.00 |
Minimum of Months | 233.65 | 158.12 | 436.97 | 141.98 | 247.89 | 0.00 | 0.00 |
Maximum of Months | 2092.58 | 1606.99 | 1486.36 | 688.09 | 855.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.26 | 2501.36 | 343.90 | 0.00 | 343.90 | 0.00 | 0.00 |
February | 17.22 | 2637.90 | 470.61 | 0.00 | 470.61 | 0.00 | 0.00 |
March | 146.28 | 1746.85 | 652.62 | 0.00 | 652.62 | 0.00 | 0.00 |
April | 400.11 | 1221.63 | 783.89 | 2.23 | 781.66 | 0.00 | 0.00 |
May | 868.24 | 720.21 | 1039.97 | 34.65 | 1005.32 | 0.00 | 0.00 |
June | 1297.81 | 398.72 | 1102.87 | 59.26 | 1043.61 | 0.00 | 0.00 |
July | 1504.98 | 224.38 | 1065.82 | 38.54 | 1027.28 | 0.00 | 0.00 |
August | 1313.21 | 307.63 | 944.27 | 11.24 | 933.03 | 0.00 | 0.00 |
September | 709.13 | 605.16 | 711.82 | 0.13 | 711.69 | 0.00 | 0.00 |
October | 377.68 | 1109.18 | 616.03 | 0.00 | 616.03 | 0.00 | 0.00 |
November | 70.65 | 1762.16 | 432.08 | 0.00 | 432.08 | 0.00 | 0.00 |
December | 3.08 | 2341.03 | 299.97 | 0.00 | 299.97 | 0.00 | 0.00 |
Annual Sum or Average | 563.10 | 1290.31 | 706.68 | 12.24 | 694.44 | 0.00 | 0.00 |
Minimum of Months | 3.08 | 224.38 | 299.97 | 0.00 | 299.97 | 0.00 | 0.00 |
Maximum of Months | 1504.98 | 2637.90 | 1102.87 | 59.26 | 1043.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.69 | 1527.94 | 478.91 | 192.00 | 286.90 | 0.00 | 0.00 |
February | 432.49 | 1550.59 | 742.68 | 346.46 | 396.22 | 0.00 | 0.00 |
March | 721.84 | 1110.11 | 947.43 | 402.95 | 544.48 | 0.00 | 0.00 |
April | 1042.89 | 783.66 | 1136.98 | 498.03 | 638.95 | 0.00 | 0.00 |
May | 1492.01 | 486.93 | 1378.92 | 551.10 | 827.82 | 0.00 | 0.00 |
June | 1608.06 | 268.35 | 1277.97 | 462.61 | 815.35 | 0.00 | 0.00 |
July | 1794.60 | 149.22 | 1283.56 | 463.20 | 820.36 | 0.00 | 0.00 |
August | 2002.63 | 203.16 | 1445.32 | 651.69 | 793.63 | 0.00 | 0.00 |
September | 1279.50 | 386.74 | 1077.93 | 483.62 | 594.31 | 0.00 | 0.00 |
October | 995.54 | 708.62 | 977.22 | 442.91 | 534.31 | 0.00 | 0.00 |
November | 408.42 | 1080.36 | 604.33 | 232.07 | 372.27 | 0.00 | 0.00 |
December | 264.25 | 1416.51 | 470.81 | 221.06 | 249.75 | 0.00 | 0.00 |
Annual Sum or Average | 1027.51 | 801.83 | 986.74 | 412.77 | 573.96 | 0.00 | 0.00 |
Minimum of Months | 237.69 | 149.22 | 470.81 | 192.00 | 249.75 | 0.00 | 0.00 |
Maximum of Months | 2002.63 | 1550.59 | 1445.32 | 651.69 | 827.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1568.34 | 2175.80 | 1779.03 | 1164.92 | 614.11 | 0.00 | 0.00 |
February | 2110.96 | 2220.00 | 2346.48 | 1553.17 | 793.30 | 0.00 | 0.00 |
March | 2042.18 | 1663.33 | 2116.97 | 1174.95 | 942.02 | 0.00 | 0.00 |
April | 1646.30 | 1255.79 | 1642.70 | 649.57 | 993.13 | 0.00 | 0.00 |
May | 1553.15 | 781.45 | 1439.58 | 300.27 | 1139.31 | 0.00 | 0.00 |
June | 1744.11 | 433.51 | 1351.01 | 206.51 | 1144.49 | 0.00 | 0.00 |
July | 2091.24 | 235.61 | 1416.13 | 245.98 | 1170.15 | 0.00 | 0.00 |
August | 2811.22 | 329.44 | 1891.07 | 701.43 | 1189.65 | 0.00 | 0.00 |
September | 2637.82 | 624.96 | 2051.85 | 1061.30 | 990.55 | 0.00 | 0.00 |
October | 3309.77 | 1112.64 | 2810.86 | 1762.60 | 1048.25 | 0.00 | 0.00 |
November | 1896.61 | 1601.26 | 1949.09 | 1170.52 | 778.57 | 0.00 | 0.00 |
December | 1795.82 | 2015.56 | 1928.20 | 1368.89 | 559.31 | 0.00 | 0.00 |
Annual Sum or Average | 2101.85 | 1198.23 | 1891.44 | 943.60 | 947.84 | 0.00 | 0.00 |
Minimum of Months | 1553.15 | 235.61 | 1351.01 | 206.51 | 559.31 | 0.00 | 0.00 |
Maximum of Months | 3309.77 | 2220.00 | 2810.86 | 1762.60 | 1189.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 242.61 | 1574.48 | 472.79 | 193.65 | 279.13 | 0.00 | 0.00 |
February | 403.82 | 1633.21 | 697.19 | 306.21 | 390.98 | 0.00 | 0.00 |
March | 823.28 | 1102.96 | 1029.49 | 475.29 | 554.21 | 0.00 | 0.00 |
April | 1059.28 | 810.95 | 1125.19 | 481.44 | 643.75 | 0.00 | 0.00 |
May | 1444.69 | 505.79 | 1310.73 | 497.76 | 812.97 | 0.00 | 0.00 |
June | 1830.22 | 290.75 | 1434.55 | 578.59 | 855.96 | 0.00 | 0.00 |
July | 1881.94 | 163.28 | 1343.54 | 505.93 | 837.61 | 0.00 | 0.00 |
August | 2083.81 | 222.54 | 1486.32 | 688.06 | 798.25 | 0.00 | 0.00 |
September | 1286.52 | 406.97 | 1055.17 | 461.10 | 594.06 | 0.00 | 0.00 |
October | 1105.16 | 738.12 | 1046.12 | 508.70 | 537.42 | 0.00 | 0.00 |
November | 274.59 | 1126.65 | 491.25 | 141.97 | 349.28 | 0.00 | 0.00 |
December | 229.31 | 1468.42 | 436.96 | 189.07 | 247.89 | 0.00 | 0.00 |
Annual Sum or Average | 1060.17 | 832.42 | 996.19 | 419.94 | 576.25 | 0.00 | 0.00 |
Minimum of Months | 229.31 | 163.28 | 436.96 | 141.97 | 247.89 | 0.00 | 0.00 |
Maximum of Months | 2083.81 | 1633.21 | 1486.32 | 688.06 | 855.96 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 11059118.29 | 0.641306E+10 | 0.921101E+09 | 0.00 | 0.921101E+09 | 0.00 | 0.00 |
February | 52857887.61 | 0.608996E+10 | 0.113851E+10 | 0.00 | 0.113851E+10 | 0.00 | 0.00 |
March | 0.413809E+09 | 0.436629E+10 | 0.174798E+10 | 0.00 | 0.174798E+10 | 0.00 | 0.00 |
April | 0.107911E+10 | 0.292079E+10 | 0.203184E+10 | 5779133.69 | 0.202606E+10 | 0.00 | 0.00 |
May | 0.238834E+10 | 0.177599E+10 | 0.278545E+10 | 92812301.28 | 0.269264E+10 | 0.00 | 0.00 |
June | 0.338539E+10 | 0.960737E+09 | 0.285865E+10 | 0.153606E+09 | 0.270504E+10 | 0.00 | 0.00 |
July | 0.402978E+10 | 0.556781E+09 | 0.285469E+10 | 0.103235E+09 | 0.275146E+10 | 0.00 | 0.00 |
August | 0.352635E+10 | 0.756536E+09 | 0.252912E+10 | 30099956.33 | 0.249902E+10 | 0.00 | 0.00 |
September | 0.189252E+10 | 0.140407E+10 | 0.184504E+10 | 345498.63 | 0.184469E+10 | 0.00 | 0.00 |
October | 0.109173E+10 | 0.266424E+10 | 0.164997E+10 | 0.00 | 0.164997E+10 | 0.00 | 0.00 |
November | 0.216274E+09 | 0.417784E+10 | 0.111996E+10 | 0.00 | 0.111996E+10 | 0.00 | 0.00 |
December | 14696833.42 | 0.584967E+10 | 0.803445E+09 | 0.00 | 0.803445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181019E+11 | 0.379360E+11 | 0.222858E+11 | 0.385878E+09 | 0.218999E+11 | 0.00 | 0.00 |
Minimum of Months | 11059118.29 | 0.556781E+09 | 0.803445E+09 | 0.00 | 0.803445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.402978E+10 | 0.641306E+10 | 0.285865E+10 | 0.153606E+09 | 0.275146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.651890E+09 | 0.391243E+10 | 0.128270E+10 | 0.514257E+09 | 0.768444E+09 | 0.00 | 0.00 |
February | 0.107854E+10 | 0.356716E+10 | 0.179669E+10 | 0.838153E+09 | 0.958538E+09 | 0.00 | 0.00 |
March | 0.198073E+10 | 0.276838E+10 | 0.253759E+10 | 0.107925E+10 | 0.145834E+10 | 0.00 | 0.00 |
April | 0.274883E+10 | 0.188754E+10 | 0.294705E+10 | 0.129089E+10 | 0.165616E+10 | 0.00 | 0.00 |
May | 0.402941E+10 | 0.121914E+10 | 0.369329E+10 | 0.147605E+10 | 0.221724E+10 | 0.00 | 0.00 |
June | 0.417328E+10 | 0.657950E+09 | 0.331249E+10 | 0.119909E+10 | 0.211340E+10 | 0.00 | 0.00 |
July | 0.479733E+10 | 0.378569E+09 | 0.343789E+10 | 0.124064E+10 | 0.219725E+10 | 0.00 | 0.00 |
August | 0.536139E+10 | 0.510970E+09 | 0.387115E+10 | 0.174549E+10 | 0.212566E+10 | 0.00 | 0.00 |
September | 0.334872E+10 | 0.917251E+09 | 0.279399E+10 | 0.125354E+10 | 0.154044E+10 | 0.00 | 0.00 |
October | 0.273250E+10 | 0.172222E+10 | 0.261739E+10 | 0.118628E+10 | 0.143111E+10 | 0.00 | 0.00 |
November | 0.111723E+10 | 0.255770E+10 | 0.156644E+10 | 0.601524E+09 | 0.964912E+09 | 0.00 | 0.00 |
December | 0.738575E+09 | 0.353192E+10 | 0.126102E+10 | 0.592095E+09 | 0.668925E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.327584E+11 | 0.236312E+11 | 0.311177E+11 | 0.130173E+11 | 0.181004E+11 | 0.00 | 0.00 |
Minimum of Months | 0.651890E+09 | 0.378569E+09 | 0.126102E+10 | 0.514257E+09 | 0.668925E+09 | 0.00 | 0.00 |
Maximum of Months | 0.536139E+10 | 0.391243E+10 | 0.387115E+10 | 0.174549E+10 | 0.221724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.424577E+10 | 0.553291E+10 | 0.476494E+10 | 0.312011E+10 | 0.164483E+10 | 0.00 | 0.00 |
February | 0.517142E+10 | 0.507111E+10 | 0.567659E+10 | 0.375743E+10 | 0.191916E+10 | 0.00 | 0.00 |
March | 0.551054E+10 | 0.414083E+10 | 0.567009E+10 | 0.314698E+10 | 0.252310E+10 | 0.00 | 0.00 |
April | 0.430343E+10 | 0.301021E+10 | 0.425787E+10 | 0.168368E+10 | 0.257419E+10 | 0.00 | 0.00 |
May | 0.419755E+10 | 0.192711E+10 | 0.385578E+10 | 0.804248E+09 | 0.305153E+10 | 0.00 | 0.00 |
June | 0.452744E+10 | 0.104295E+10 | 0.350181E+10 | 0.535283E+09 | 0.296653E+10 | 0.00 | 0.00 |
July | 0.559060E+10 | 0.582668E+09 | 0.379295E+10 | 0.658828E+09 | 0.313412E+10 | 0.00 | 0.00 |
August | 0.752077E+10 | 0.812782E+09 | 0.506505E+10 | 0.187870E+10 | 0.318636E+10 | 0.00 | 0.00 |
September | 0.686986E+10 | 0.146492E+10 | 0.531839E+10 | 0.275088E+10 | 0.256752E+10 | 0.00 | 0.00 |
October | 0.892603E+10 | 0.269541E+10 | 0.752859E+10 | 0.472096E+10 | 0.280764E+10 | 0.00 | 0.00 |
November | 0.500729E+10 | 0.378681E+10 | 0.505203E+10 | 0.303398E+10 | 0.201805E+10 | 0.00 | 0.00 |
December | 0.489793E+10 | 0.500390E+10 | 0.516448E+10 | 0.366643E+10 | 0.149805E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.667686E+11 | 0.350716E+11 | 0.596486E+11 | 0.297575E+11 | 0.298911E+11 | 0.00 | 0.00 |
Minimum of Months | 0.419755E+10 | 0.582668E+09 | 0.350181E+10 | 0.535283E+09 | 0.149805E+10 | 0.00 | 0.00 |
Maximum of Months | 0.892603E+10 | 0.553291E+10 | 0.752859E+10 | 0.472096E+10 | 0.318636E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.655692E+09 | 0.403075E+10 | 0.126631E+10 | 0.518684E+09 | 0.747631E+09 | 0.00 | 0.00 |
February | 0.988448E+09 | 0.375886E+10 | 0.168665E+10 | 0.740780E+09 | 0.945871E+09 | 0.00 | 0.00 |
March | 0.221903E+10 | 0.275224E+10 | 0.275739E+10 | 0.127301E+10 | 0.148438E+10 | 0.00 | 0.00 |
April | 0.275913E+10 | 0.194655E+10 | 0.291648E+10 | 0.124788E+10 | 0.166860E+10 | 0.00 | 0.00 |
May | 0.388266E+10 | 0.125674E+10 | 0.351066E+10 | 0.133320E+10 | 0.217745E+10 | 0.00 | 0.00 |
June | 0.473943E+10 | 0.705523E+09 | 0.371836E+10 | 0.149971E+10 | 0.221865E+10 | 0.00 | 0.00 |
July | 0.502500E+10 | 0.409796E+09 | 0.359853E+10 | 0.135509E+10 | 0.224344E+10 | 0.00 | 0.00 |
August | 0.557317E+10 | 0.554588E+09 | 0.398095E+10 | 0.184291E+10 | 0.213804E+10 | 0.00 | 0.00 |
September | 0.335485E+10 | 0.960012E+09 | 0.273499E+10 | 0.119518E+10 | 0.153981E+10 | 0.00 | 0.00 |
October | 0.299586E+10 | 0.179102E+10 | 0.280192E+10 | 0.136250E+10 | 0.143942E+10 | 0.00 | 0.00 |
November | 0.738499E+09 | 0.267640E+10 | 0.127333E+10 | 0.367999E+09 | 0.905330E+09 | 0.00 | 0.00 |
December | 0.630831E+09 | 0.366496E+10 | 0.117035E+10 | 0.506413E+09 | 0.663940E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335626E+11 | 0.245074E+11 | 0.314159E+11 | 0.132434E+11 | 0.181726E+11 | 0.00 | 0.00 |
Minimum of Months | 0.630831E+09 | 0.409796E+09 | 0.117035E+10 | 0.367999E+09 | 0.663940E+09 | 0.00 | 0.00 |
Maximum of Months | 0.557317E+10 | 0.403075E+10 | 0.398095E+10 | 0.184291E+10 | 0.224344E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 11167207.88 | 0.661762E+10 | 0.921096E+09 | 0.00 | 0.921096E+09 | 0.00 | 0.00 |
February | 50128447.73 | 0.621519E+10 | 0.113850E+10 | 0.00 | 0.113850E+10 | 0.00 | 0.00 |
March | 0.462473E+09 | 0.445300E+10 | 0.174797E+10 | 0.00 | 0.174797E+10 | 0.00 | 0.00 |
April | 0.117787E+10 | 0.294268E+10 | 0.203182E+10 | 5779100.26 | 0.202604E+10 | 0.00 | 0.00 |
May | 0.255907E+10 | 0.172241E+10 | 0.278544E+10 | 92811764.28 | 0.269262E+10 | 0.00 | 0.00 |
June | 0.349543E+10 | 0.935305E+09 | 0.285863E+10 | 0.153605E+09 | 0.270503E+10 | 0.00 | 0.00 |
July | 0.412098E+10 | 0.533606E+09 | 0.285468E+10 | 0.103234E+09 | 0.275144E+10 | 0.00 | 0.00 |
August | 0.356612E+10 | 0.782867E+09 | 0.252911E+10 | 30099782.18 | 0.249901E+10 | 0.00 | 0.00 |
September | 0.184826E+10 | 0.159479E+10 | 0.184503E+10 | 345496.63 | 0.184468E+10 | 0.00 | 0.00 |
October | 0.101162E+10 | 0.305293E+10 | 0.164996E+10 | 0.00 | 0.164996E+10 | 0.00 | 0.00 |
November | 0.183770E+09 | 0.469025E+10 | 0.111996E+10 | 0.00 | 0.111996E+10 | 0.00 | 0.00 |
December | 8440022.98 | 0.632468E+10 | 0.803440E+09 | 0.00 | 0.803440E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.184953E+11 | 0.398653E+11 | 0.222856E+11 | 0.385876E+09 | 0.218998E+11 | 0.00 | 0.00 |
Minimum of Months | 8440022.98 | 0.533606E+09 | 0.803440E+09 | 0.00 | 0.803440E+09 | 0.00 | 0.00 |
Maximum of Months | 0.412098E+10 | 0.661762E+10 | 0.285863E+10 | 0.153605E+09 | 0.275144E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.656745E+09 | 0.407183E+10 | 0.128275E+10 | 0.514278E+09 | 0.768469E+09 | 0.00 | 0.00 |
February | 0.108226E+10 | 0.369759E+10 | 0.179675E+10 | 0.838187E+09 | 0.958567E+09 | 0.00 | 0.00 |
March | 0.202981E+10 | 0.286499E+10 | 0.253768E+10 | 0.107929E+10 | 0.145839E+10 | 0.00 | 0.00 |
April | 0.281952E+10 | 0.194305E+10 | 0.294715E+10 | 0.129094E+10 | 0.165621E+10 | 0.00 | 0.00 |
May | 0.413682E+10 | 0.122053E+10 | 0.369342E+10 | 0.147611E+10 | 0.221731E+10 | 0.00 | 0.00 |
June | 0.425079E+10 | 0.662211E+09 | 0.331260E+10 | 0.119914E+10 | 0.211346E+10 | 0.00 | 0.00 |
July | 0.486560E+10 | 0.383805E+09 | 0.343800E+10 | 0.124069E+10 | 0.219731E+10 | 0.00 | 0.00 |
August | 0.540477E+10 | 0.556770E+09 | 0.387128E+10 | 0.174556E+10 | 0.212572E+10 | 0.00 | 0.00 |
September | 0.333463E+10 | 0.106386E+10 | 0.279408E+10 | 0.125360E+10 | 0.154049E+10 | 0.00 | 0.00 |
October | 0.267549E+10 | 0.201787E+10 | 0.261748E+10 | 0.118633E+10 | 0.143115E+10 | 0.00 | 0.00 |
November | 0.106754E+10 | 0.291014E+10 | 0.156649E+10 | 0.601549E+09 | 0.964943E+09 | 0.00 | 0.00 |
December | 0.718273E+09 | 0.386247E+10 | 0.126107E+10 | 0.592119E+09 | 0.668946E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330423E+11 | 0.252551E+11 | 0.311188E+11 | 0.130178E+11 | 0.181010E+11 | 0.00 | 0.00 |
Minimum of Months | 0.656745E+09 | 0.383805E+09 | 0.126107E+10 | 0.514278E+09 | 0.668946E+09 | 0.00 | 0.00 |
Maximum of Months | 0.540477E+10 | 0.407183E+10 | 0.387128E+10 | 0.174556E+10 | 0.221731E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434828E+10 | 0.580630E+10 | 0.476497E+10 | 0.312013E+10 | 0.164484E+10 | 0.00 | 0.00 |
February | 0.527616E+10 | 0.534559E+10 | 0.567662E+10 | 0.375746E+10 | 0.191917E+10 | 0.00 | 0.00 |
March | 0.567359E+10 | 0.434167E+10 | 0.567011E+10 | 0.314700E+10 | 0.252311E+10 | 0.00 | 0.00 |
April | 0.444791E+10 | 0.309272E+10 | 0.425788E+10 | 0.168369E+10 | 0.257420E+10 | 0.00 | 0.00 |
May | 0.438571E+10 | 0.189531E+10 | 0.385579E+10 | 0.804252E+09 | 0.305154E+10 | 0.00 | 0.00 |
June | 0.465547E+10 | 0.103056E+10 | 0.350182E+10 | 0.535286E+09 | 0.296654E+10 | 0.00 | 0.00 |
July | 0.568794E+10 | 0.582127E+09 | 0.379296E+10 | 0.658832E+09 | 0.313413E+10 | 0.00 | 0.00 |
August | 0.758170E+10 | 0.895179E+09 | 0.506507E+10 | 0.187871E+10 | 0.318636E+10 | 0.00 | 0.00 |
September | 0.686756E+10 | 0.173218E+10 | 0.531842E+10 | 0.275089E+10 | 0.256752E+10 | 0.00 | 0.00 |
October | 0.890031E+10 | 0.325102E+10 | 0.752863E+10 | 0.472098E+10 | 0.280765E+10 | 0.00 | 0.00 |
November | 0.497808E+10 | 0.436695E+10 | 0.505206E+10 | 0.303400E+10 | 0.201806E+10 | 0.00 | 0.00 |
December | 0.490135E+10 | 0.554205E+10 | 0.516451E+10 | 0.366645E+10 | 0.149806E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.677041E+11 | 0.378816E+11 | 0.596489E+11 | 0.297577E+11 | 0.298912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.434828E+10 | 0.582127E+09 | 0.350182E+10 | 0.535286E+09 | 0.149806E+10 | 0.00 | 0.00 |
Maximum of Months | 0.890031E+10 | 0.580630E+10 | 0.752863E+10 | 0.472098E+10 | 0.318636E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.672218E+09 | 0.418675E+10 | 0.126636E+10 | 0.518703E+09 | 0.747653E+09 | 0.00 | 0.00 |
February | 0.101665E+10 | 0.388762E+10 | 0.168671E+10 | 0.740807E+09 | 0.945898E+09 | 0.00 | 0.00 |
March | 0.228955E+10 | 0.287384E+10 | 0.275748E+10 | 0.127305E+10 | 0.148443E+10 | 0.00 | 0.00 |
April | 0.284328E+10 | 0.201734E+10 | 0.291658E+10 | 0.124793E+10 | 0.166865E+10 | 0.00 | 0.00 |
May | 0.398534E+10 | 0.127056E+10 | 0.351077E+10 | 0.133325E+10 | 0.217751E+10 | 0.00 | 0.00 |
June | 0.481166E+10 | 0.728384E+09 | 0.371848E+10 | 0.149977E+10 | 0.221871E+10 | 0.00 | 0.00 |
July | 0.508767E+10 | 0.423512E+09 | 0.359864E+10 | 0.135514E+10 | 0.224350E+10 | 0.00 | 0.00 |
August | 0.560478E+10 | 0.612039E+09 | 0.398108E+10 | 0.184298E+10 | 0.213810E+10 | 0.00 | 0.00 |
September | 0.332953E+10 | 0.111758E+10 | 0.273508E+10 | 0.119522E+10 | 0.153986E+10 | 0.00 | 0.00 |
October | 0.295144E+10 | 0.210721E+10 | 0.280201E+10 | 0.136255E+10 | 0.143946E+10 | 0.00 | 0.00 |
November | 0.715692E+09 | 0.302500E+10 | 0.127337E+10 | 0.368013E+09 | 0.905357E+09 | 0.00 | 0.00 |
December | 0.625797E+09 | 0.399557E+10 | 0.117039E+10 | 0.506432E+09 | 0.663959E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339336E+11 | 0.262454E+11 | 0.314169E+11 | 0.132438E+11 | 0.181731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.625797E+09 | 0.423512E+09 | 0.117039E+10 | 0.368013E+09 | 0.663959E+09 | 0.00 | 0.00 |
Maximum of Months | 0.560478E+10 | 0.418675E+10 | 0.398108E+10 | 0.184298E+10 | 0.224350E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8718507.41 | 0.669965E+10 | 0.921101E+09 | 0.00 | 0.921101E+09 | 0.00 | 0.00 |
February | 41660141.81 | 0.638161E+10 | 0.113851E+10 | 0.00 | 0.113851E+10 | 0.00 | 0.00 |
March | 0.391807E+09 | 0.467876E+10 | 0.174798E+10 | 0.00 | 0.174798E+10 | 0.00 | 0.00 |
April | 0.103709E+10 | 0.316646E+10 | 0.203184E+10 | 5779133.69 | 0.202606E+10 | 0.00 | 0.00 |
May | 0.232549E+10 | 0.192902E+10 | 0.278545E+10 | 92812301.28 | 0.269264E+10 | 0.00 | 0.00 |
June | 0.336393E+10 | 0.103349E+10 | 0.285865E+10 | 0.153606E+09 | 0.270504E+10 | 0.00 | 0.00 |
July | 0.403095E+10 | 0.600980E+09 | 0.285469E+10 | 0.103235E+09 | 0.275146E+10 | 0.00 | 0.00 |
August | 0.351731E+10 | 0.823968E+09 | 0.252912E+10 | 30099956.33 | 0.249902E+10 | 0.00 | 0.00 |
September | 0.183806E+10 | 0.156858E+10 | 0.184504E+10 | 345498.63 | 0.184469E+10 | 0.00 | 0.00 |
October | 0.101159E+10 | 0.297082E+10 | 0.164997E+10 | 0.00 | 0.164997E+10 | 0.00 | 0.00 |
November | 0.183120E+09 | 0.456753E+10 | 0.111996E+10 | 0.00 | 0.111996E+10 | 0.00 | 0.00 |
December | 8244489.04 | 0.627022E+10 | 0.803445E+09 | 0.00 | 0.803445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.177580E+11 | 0.406911E+11 | 0.222858E+11 | 0.385878E+09 | 0.218999E+11 | 0.00 | 0.00 |
Minimum of Months | 8244489.04 | 0.600980E+09 | 0.803445E+09 | 0.00 | 0.803445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.403095E+10 | 0.669965E+10 | 0.285865E+10 | 0.153606E+09 | 0.275146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.636636E+09 | 0.409245E+10 | 0.128270E+10 | 0.514257E+09 | 0.768444E+09 | 0.00 | 0.00 |
February | 0.104629E+10 | 0.375120E+10 | 0.179669E+10 | 0.838153E+09 | 0.958538E+09 | 0.00 | 0.00 |
March | 0.193338E+10 | 0.297331E+10 | 0.253759E+10 | 0.107925E+10 | 0.145834E+10 | 0.00 | 0.00 |
April | 0.270316E+10 | 0.203125E+10 | 0.294705E+10 | 0.129089E+10 | 0.165616E+10 | 0.00 | 0.00 |
May | 0.399619E+10 | 0.130419E+10 | 0.369329E+10 | 0.147605E+10 | 0.221724E+10 | 0.00 | 0.00 |
June | 0.416810E+10 | 0.695563E+09 | 0.331249E+10 | 0.119909E+10 | 0.211340E+10 | 0.00 | 0.00 |
July | 0.480666E+10 | 0.399667E+09 | 0.343789E+10 | 0.124064E+10 | 0.219725E+10 | 0.00 | 0.00 |
August | 0.536385E+10 | 0.544147E+09 | 0.387115E+10 | 0.174549E+10 | 0.212566E+10 | 0.00 | 0.00 |
September | 0.331647E+10 | 0.100243E+10 | 0.279399E+10 | 0.125354E+10 | 0.154044E+10 | 0.00 | 0.00 |
October | 0.266646E+10 | 0.189798E+10 | 0.261739E+10 | 0.118628E+10 | 0.143111E+10 | 0.00 | 0.00 |
November | 0.105862E+10 | 0.280031E+10 | 0.156644E+10 | 0.601524E+09 | 0.964912E+09 | 0.00 | 0.00 |
December | 0.707755E+09 | 0.379398E+10 | 0.126102E+10 | 0.592095E+09 | 0.668925E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.324036E+11 | 0.252865E+11 | 0.311177E+11 | 0.130173E+11 | 0.181004E+11 | 0.00 | 0.00 |
Minimum of Months | 0.636636E+09 | 0.399667E+09 | 0.126102E+10 | 0.514257E+09 | 0.668925E+09 | 0.00 | 0.00 |
Maximum of Months | 0.536385E+10 | 0.409245E+10 | 0.387115E+10 | 0.174549E+10 | 0.221724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.420065E+10 | 0.582767E+10 | 0.476494E+10 | 0.312011E+10 | 0.164483E+10 | 0.00 | 0.00 |
February | 0.510684E+10 | 0.537063E+10 | 0.567659E+10 | 0.375743E+10 | 0.191916E+10 | 0.00 | 0.00 |
March | 0.546978E+10 | 0.445508E+10 | 0.567009E+10 | 0.314698E+10 | 0.252310E+10 | 0.00 | 0.00 |
April | 0.426720E+10 | 0.325501E+10 | 0.425787E+10 | 0.168368E+10 | 0.257419E+10 | 0.00 | 0.00 |
May | 0.415996E+10 | 0.209305E+10 | 0.385578E+10 | 0.804248E+09 | 0.305153E+10 | 0.00 | 0.00 |
June | 0.452073E+10 | 0.112365E+10 | 0.350181E+10 | 0.535283E+09 | 0.296653E+10 | 0.00 | 0.00 |
July | 0.560119E+10 | 0.631054E+09 | 0.379295E+10 | 0.658828E+09 | 0.313412E+10 | 0.00 | 0.00 |
August | 0.752958E+10 | 0.882366E+09 | 0.506505E+10 | 0.187870E+10 | 0.318636E+10 | 0.00 | 0.00 |
September | 0.683722E+10 | 0.161990E+10 | 0.531839E+10 | 0.275088E+10 | 0.256752E+10 | 0.00 | 0.00 |
October | 0.886489E+10 | 0.298009E+10 | 0.752859E+10 | 0.472096E+10 | 0.280764E+10 | 0.00 | 0.00 |
November | 0.491601E+10 | 0.415046E+10 | 0.505203E+10 | 0.303398E+10 | 0.201805E+10 | 0.00 | 0.00 |
December | 0.480992E+10 | 0.539849E+10 | 0.516448E+10 | 0.366643E+10 | 0.149805E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.662840E+11 | 0.377874E+11 | 0.596486E+11 | 0.297575E+11 | 0.298911E+11 | 0.00 | 0.00 |
Minimum of Months | 0.415996E+10 | 0.631054E+09 | 0.350181E+10 | 0.535283E+09 | 0.149805E+10 | 0.00 | 0.00 |
Maximum of Months | 0.886489E+10 | 0.582767E+10 | 0.752859E+10 | 0.472096E+10 | 0.318636E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.649820E+09 | 0.421708E+10 | 0.126631E+10 | 0.518684E+09 | 0.747631E+09 | 0.00 | 0.00 |
February | 0.976926E+09 | 0.395106E+10 | 0.168665E+10 | 0.740780E+09 | 0.945871E+09 | 0.00 | 0.00 |
March | 0.220508E+10 | 0.295416E+10 | 0.275739E+10 | 0.127301E+10 | 0.148438E+10 | 0.00 | 0.00 |
April | 0.274566E+10 | 0.210199E+10 | 0.291648E+10 | 0.124788E+10 | 0.166860E+10 | 0.00 | 0.00 |
May | 0.386946E+10 | 0.135471E+10 | 0.351066E+10 | 0.133320E+10 | 0.217745E+10 | 0.00 | 0.00 |
June | 0.474393E+10 | 0.753615E+09 | 0.371836E+10 | 0.149971E+10 | 0.221865E+10 | 0.00 | 0.00 |
July | 0.504060E+10 | 0.437338E+09 | 0.359853E+10 | 0.135509E+10 | 0.224344E+10 | 0.00 | 0.00 |
August | 0.558129E+10 | 0.596039E+09 | 0.398095E+10 | 0.184291E+10 | 0.213804E+10 | 0.00 | 0.00 |
September | 0.333467E+10 | 0.105485E+10 | 0.273499E+10 | 0.119518E+10 | 0.153981E+10 | 0.00 | 0.00 |
October | 0.296005E+10 | 0.197699E+10 | 0.280192E+10 | 0.136250E+10 | 0.143942E+10 | 0.00 | 0.00 |
November | 0.711746E+09 | 0.292028E+10 | 0.127333E+10 | 0.367999E+09 | 0.905330E+09 | 0.00 | 0.00 |
December | 0.614192E+09 | 0.393301E+10 | 0.117035E+10 | 0.506413E+09 | 0.663940E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.334334E+11 | 0.262511E+11 | 0.314159E+11 | 0.132434E+11 | 0.181726E+11 | 0.00 | 0.00 |
Minimum of Months | 0.614192E+09 | 0.437338E+09 | 0.117035E+10 | 0.367999E+09 | 0.663940E+09 | 0.00 | 0.00 |
Maximum of Months | 0.558129E+10 | 0.421708E+10 | 0.398095E+10 | 0.184291E+10 | 0.224344E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.496961E+10 | -0.472086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -248744934.6 | 60.05 | 0.00 | 0.00 |
February | 0.455358E+10 | -0.433272E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -220868762.8 | 60.05 | 0.00 | 0.00 |
March | 0.525410E+10 | -0.501498E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -239118059.9 | 60.05 | 0.00 | 0.00 |
April | 0.451448E+10 | -0.428604E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -228441811.9 | 60.05 | 0.00 | 0.00 |
May | 0.452054E+10 | -0.428732E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233219471.6 | 60.05 | 0.00 | 0.00 |
June | 0.418076E+10 | -0.395667E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224091152.9 | 60.05 | 0.00 | 0.00 |
July | 0.376655E+10 | -0.353550E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231045756.5 | 60.05 | 0.00 | 0.00 |
August | 0.408907E+10 | -0.385767E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231403560.0 | 60.05 | 0.00 | 0.00 |
September | 0.380398E+10 | -0.358006E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223927892.8 | 60.05 | 0.00 | 0.00 |
October | 0.416836E+10 | -0.393596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232401241.0 | 60.05 | 0.00 | 0.00 |
November | 0.439666E+10 | -0.416705E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229611004.9 | 60.05 | 0.00 | 0.00 |
December | 0.464088E+10 | -0.439982E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241061765.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.528586E+11 | -0.500746E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.278394E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.376655E+10 | -0.501498E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -248744934.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.525410E+10 | -0.353550E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -220868762.8 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.648587E+10 | 18002.64 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.571297E+10 | 17147.04 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.719429E+09 | 8305.12 | 23-MAR-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10383059.87 | 2227.60 | 03-APR-05:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84288.12 | 5.37 | 31-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 884096.48 | 6.28 | 20-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1577349.15 | 6.40 | 10-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2093594.12 | 6.51 | 02-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 717599.99 | 6.27 | 06-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 412656.63 | 5.71 | 04-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.517854E+09 | 12272.19 | 24-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.980423E+09 | 15098.60 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 84288.12 | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648587E+10 | 18002.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.760372E+09 | 15862.38 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8364337.59 | 15525.98 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.768736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.760372E+09 | 15862.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.687412E+10 | 11278.81 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.584730E+10 | 11003.41 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415616E+10 | 10674.00 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.234303E+10 | 10689.19 | 11-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.728510E+09 | 10700.07 | 15-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19049441.03 | 3959.74 | 02-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60988134.59 | 6249.71 | 20-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374574E+09 | 10696.89 | 18-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251771E+10 | 10673.17 | 27-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.453454E+10 | 10670.08 | 05-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.687412E+10 | 11278.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354163E+10 | 8008.82 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293778E+10 | 7850.54 | 06-FEB-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147900E+10 | 7561.86 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.625083E+09 | 7555.50 | 22-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67014980.78 | 6032.96 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7171484.63 | 3938.91 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.771272E+09 | 7555.91 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196505E+10 | 7556.79 | 19-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.354163E+10 | 8008.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.590821E+10 | 11459.93 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542758E+10 | 11305.74 | 06-FEB-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300590E+10 | 10840.52 | 21-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119130E+10 | 10817.08 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105745E+09 | 10790.00 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35891736.19 | 8494.41 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144129E+10 | 10825.00 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.339124E+10 | 10834.35 | 23-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.590821E+10 | 11459.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.380337E+10 | 8218.75 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328302E+10 | 8069.53 | 06-FEB-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161439E+10 | 7752.39 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.694111E+09 | 7753.14 | 22-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82211751.57 | 7734.87 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13405486.80 | 4289.85 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101446E+10 | 7760.86 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223698E+10 | 7754.55 | 19-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.380337E+10 | 8218.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109800E+11 | 18759.01 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101564E+11 | 18632.54 | 06-FEB-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.287771E+10 | 13078.04 | 23-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182433E+09 | 6562.23 | 03-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92142.65 | 5.58 | 31-MAY-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 824454.32 | 5.77 | 19-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1440098.77 | 6.02 | 07-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1820280.65 | 6.46 | 18-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 460191.71 | 5.49 | 06-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11873279.18 | 1718.51 | 28-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197407E+10 | 16525.72 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.493590E+10 | 16410.32 | 31-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 92142.65 | 5.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109800E+11 | 18759.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237594E+10 | 22398.49 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125972E+10 | 22235.09 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96369603.47 | 21744.56 | 20-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15650941.17 | 21755.28 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285048E+09 | 21825.10 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.425528E+09 | 21804.76 | 26-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.445826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237594E+10 | 22398.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397113E+10 | 12228.97 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299743E+10 | 12196.06 | 06-FEB-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128760E+10 | 11338.42 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.576141E+09 | 11304.38 | 03-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23865903.60 | 11285.30 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42788027.99 | 11259.66 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113360E+10 | 11350.26 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237224E+10 | 11346.49 | 26-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.397113E+10 | 12228.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.347738E+10 | 9178.02 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277655E+10 | 9153.18 | 06-FEB-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123999E+10 | 8504.46 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.488304E+09 | 8478.87 | 03-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25528932.73 | 4997.71 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337757.03 | 541.53 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89662779.47 | 8105.56 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120358E+10 | 8511.67 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.225736E+10 | 8509.40 | 26-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.347738E+10 | 9178.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.583182E+10 | 12419.15 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.504545E+10 | 12385.72 | 06-FEB-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.220161E+10 | 11514.74 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.735720E+09 | 11518.60 | 03-APR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24247086.69 | 11042.79 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130412E+09 | 11434.76 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200149E+10 | 11526.78 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388032E+10 | 11523.29 | 23-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.583182E+10 | 12419.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.412662E+10 | 9411.87 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.345963E+10 | 9386.39 | 06-FEB-02:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156649E+10 | 8720.66 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642046E+09 | 8694.42 | 03-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45973642.71 | 7239.47 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2649553.08 | 949.03 | 26-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132752E+09 | 8038.89 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162616E+10 | 8727.91 | 27-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.286745E+10 | 8725.63 | 26-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.412662E+10 | 9411.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129469E+11 | 16071.43 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113284E+11 | 16215.77 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.318655E+10 | 14910.90 | 20-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350395E+09 | 12474.46 | 03-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8959187.78 | 4741.16 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 705193.69 | 6.96 | 19-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1294193.58 | 6.75 | 07-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1566186.92 | 6.96 | 18-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 370046.75 | 6.47 | 05-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97371802.51 | 7683.63 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295263E+10 | 15186.24 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.685356E+10 | 15252.83 | 31-DEC-23:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 370046.75 | 6.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129469E+11 | 16215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.833228E+10 | 34502.83 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666071E+10 | 34813.79 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198959E+10 | 32024.88 | 20-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.682107E+09 | 31637.47 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21423462.91 | 31394.19 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69955749.62 | 31431.56 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263095E+10 | 32601.36 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.485054E+10 | 31705.08 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.833228E+10 | 34813.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.726000E+10 | 15889.35 | 02-JAN-00:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.595800E+10 | 16370.58 | 06-FEB-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301666E+10 | 15225.47 | 23-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151418E+10 | 14441.79 | 04-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225094E+09 | 14372.41 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1337427.34 | 1428.50 | 03-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42036749.37 | 7965.65 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386030E+09 | 14357.59 | 27-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280914E+10 | 15021.33 | 25-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.485665E+10 | 15828.21 | 31-DEC-23:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.726000E+10 | 16370.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.580077E+10 | 10587.99 | 02-JAN-00:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.486877E+10 | 10908.93 | 06-FEB-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225423E+10 | 10145.24 | 23-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.982419E+09 | 9622.48 | 04-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106817E+09 | 9576.00 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27160477.57 | 5672.71 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.352763E+09 | 9583.29 | 10-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239923E+10 | 10008.98 | 25-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412094E+10 | 10547.19 | 31-DEC-23:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.580077E+10 | 10908.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.967461E+10 | 16084.13 | 02-JAN-00:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.867089E+10 | 16571.27 | 06-FEB-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.439023E+10 | 15412.12 | 23-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180408E+10 | 14656.87 | 03-APR-05:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.226376E+09 | 14548.60 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79550807.26 | 9732.40 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.799453E+09 | 14559.53 | 10-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.431830E+10 | 15205.47 | 25-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.706401E+10 | 16022.24 | 31-DEC-23:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.967461E+10 | 16571.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.633785E+10 | 11288.54 | 02-JAN-00:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552828E+10 | 11631.62 | 06-FEB-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270856E+10 | 10815.24 | 23-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123958E+10 | 10256.07 | 04-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207263E+09 | 10205.74 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1909462.38 | 1384.35 | 03-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74612908.32 | 6353.64 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.530034E+09 | 10213.80 | 10-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293663E+10 | 10669.22 | 25-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.463069E+10 | 11244.87 | 31-DEC-23:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.633785E+10 | 11631.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.306278E+10 | 0.254912E+10 | 14428.25 | 24-JAN-12:20 | 10108.89 | 0.00 |
February | 0.00 | 0.00 | 0.172253E+10 | 0.166015E+10 | 11799.65 | 24-FEB-16:00 | 11799.65 | 0.00 |
March | 0.00 | 0.00 | 0.103204E+11 | 0.947390E+10 | 31960.15 | 27-MAR-16:00 | 28195.65 | 0.00 |
April | 0.00 | 0.00 | 0.214996E+11 | 0.200927E+11 | 45732.08 | 07-APR-15:30 | 45732.08 | 0.00 |
May | 0.00 | 0.00 | 0.409253E+11 | 0.369808E+11 | 71276.31 | 31-MAY-14:05 | 60957.15 | 0.00 |
June | 0.00 | 0.00 | 0.720812E+11 | 0.589205E+11 | 135452.84 | 19-JUN-05:02 | 75643.46 | 0.00 |
July | 0.00 | 0.00 | 0.958218E+11 | 0.717845E+11 | 140479.16 | 22-JUL-04:02 | 66310.83 | 0.00 |
August | 0.00 | 0.00 | 0.991217E+11 | 0.813504E+11 | 136637.17 | 04-AUG-04:02 | 74528.15 | 0.00 |
September | 0.00 | 0.00 | 0.637150E+11 | 0.552642E+11 | 132828.58 | 01-SEP-05:03 | 78723.55 | 0.00 |
October | 0.00 | 0.00 | 0.444382E+11 | 0.395346E+11 | 71103.36 | 04-OCT-14:10 | 61222.18 | 0.00 |
November | 0.00 | 0.00 | 0.145894E+11 | 0.135768E+11 | 35937.46 | 03-NOV-14:10 | 35937.46 | 0.00 |
December | 0.00 | 0.00 | 0.370060E+10 | 0.356986E+10 | 13354.96 | 19-DEC-15:20 | 13354.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.470999E+12 | 0.394757E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.172253E+10 | 0.166015E+10 | 11799.65 | 10108.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.991217E+11 | 0.813504E+11 | 140479.16 | 78723.55 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.113544E+10 | 0.843178E+09 | 15270.57 | 24-JAN-07:03 | 13215.43 | 0.00 |
February | 0.00 | 0.00 | 0.296874E+09 | 0.289635E+09 | 5331.47 | 24-FEB-14:00 | 5331.47 | 0.00 |
March | 0.00 | 0.00 | 0.546333E+10 | 0.480649E+10 | 28420.97 | 27-MAR-16:00 | 24104.87 | 0.00 |
April | 0.00 | 0.00 | 0.157552E+11 | 0.142474E+11 | 46927.25 | 07-APR-14:05 | 46927.25 | 0.00 |
May | 0.00 | 0.00 | 0.362746E+11 | 0.319489E+11 | 72367.16 | 31-MAY-14:05 | 62299.95 | 0.00 |
June | 0.00 | 0.00 | 0.672075E+11 | 0.537476E+11 | 131309.66 | 19-JUN-05:02 | 75671.80 | 0.00 |
July | 0.00 | 0.00 | 0.888143E+11 | 0.651235E+11 | 135434.19 | 22-JUL-05:02 | 62592.86 | 0.00 |
August | 0.00 | 0.00 | 0.881192E+11 | 0.713780E+11 | 133140.60 | 04-AUG-04:02 | 66863.56 | 0.00 |
September | 0.00 | 0.00 | 0.533275E+11 | 0.446213E+11 | 128246.15 | 01-SEP-05:02 | 77622.72 | 0.00 |
October | 0.00 | 0.00 | 0.334496E+11 | 0.281166E+11 | 64066.59 | 04-OCT-14:05 | 55626.26 | 0.00 |
November | 0.00 | 0.00 | 0.759182E+10 | 0.651582E+10 | 28079.52 | 03-NOV-14:03 | 28079.52 | 0.00 |
December | 0.00 | 0.00 | 0.584574E+09 | 0.535379E+09 | 6722.14 | 04-DEC-07:03 | 6722.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.398020E+12 | 0.322174E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.296874E+09 | 0.289635E+09 | 5331.47 | 5331.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.888143E+11 | 0.713780E+11 | 135434.19 | 77622.72 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.242909E+10 | 0.191477E+10 | 15036.06 | 24-JAN-07:03 | 12161.44 | 0.00 |
February | 0.00 | 0.00 | 0.115878E+10 | 0.111722E+10 | 8963.14 | 24-FEB-14:00 | 8907.51 | 0.00 |
March | 0.00 | 0.00 | 0.870248E+10 | 0.773900E+10 | 35265.43 | 27-MAR-16:00 | 29630.14 | 0.00 |
April | 0.00 | 0.00 | 0.200957E+11 | 0.180393E+11 | 60119.42 | 07-APR-14:40 | 60119.42 | 0.00 |
May | 0.00 | 0.00 | 0.435869E+11 | 0.381490E+11 | 86686.57 | 31-MAY-14:00 | 76957.99 | 0.00 |
June | 0.00 | 0.00 | 0.763809E+11 | 0.616228E+11 | 167186.82 | 19-JUN-05:02 | 84968.01 | 0.00 |
July | 0.00 | 0.00 | 0.992078E+11 | 0.746039E+11 | 178623.30 | 22-JUL-05:02 | 80138.10 | 0.00 |
August | 0.00 | 0.00 | 0.980366E+11 | 0.803546E+11 | 172572.58 | 05-AUG-04:01 | 97640.85 | 0.00 |
September | 0.00 | 0.00 | 0.580655E+11 | 0.479791E+11 | 121804.14 | 01-SEP-05:02 | 70766.39 | 0.00 |
October | 0.00 | 0.00 | 0.353779E+11 | 0.290064E+11 | 70779.57 | 04-OCT-14:30 | 62696.46 | 0.00 |
November | 0.00 | 0.00 | 0.947793E+10 | 0.801081E+10 | 26379.99 | 02-NOV-13:30 | 26379.99 | 0.00 |
December | 0.00 | 0.00 | 0.153122E+10 | 0.140991E+10 | 9624.50 | 20-DEC-14:00 | 8844.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.454051E+12 | 0.369947E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.115878E+10 | 0.111722E+10 | 8963.14 | 8844.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.992078E+11 | 0.803546E+11 | 178623.30 | 97640.85 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 40188.67 | 315234.19 | 20-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 37699.72 | 318857.28 | 02-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13995.54 | 361400.90 | 06-MAR-06:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5383.95 | 322867.37 | 03-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 707.93 | 265543.48 | 01-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 7.74 | 3720.25 | 02-JUN-06:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1.80 | 14.79 | 05-JUL-15:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2.11 | 14.26 | 09-AUG-13:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 108.23 | 64867.27 | 29-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1137.61 | 234139.51 | 28-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12453.65 | 341733.14 | 27-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23051.65 | 319271.44 | 20-DEC-06:11 |
Annual Sum or Average | 0.00 | 11084.50 | ||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 14.26 | ||
Maximum of Months | 0.00 | 0.00 | 40188.67 | 361400.90 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1753.16 | 6437.59 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1781.51 | 6446.36 | 09-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1862.65 | 6396.56 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1644.30 | 6126.57 | 03-APR-11:17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1591.41 | 5771.04 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1517.24 | 5345.04 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1311.24 | 4990.77 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1431.13 | 4874.06 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1372.29 | 5103.53 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1460.48 | 5503.66 | 31-OCT-11:17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1598.39 | 6845.64 | 22-NOV-13:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1633.52 | 6246.38 | 29-DEC-12:17 |
Annual Sum or Average | 0.00 | 1578.63 | ||||
Minimum of Months | 0.00 | 0.00 | 1311.24 | 4874.06 | ||
Maximum of Months | 0.00 | 0.00 | 1862.65 | 6845.64 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.356334E+10 | 0.50 | 5237.37 | 02-JAN-05:02 | 1.24 |
February | 0.317862E+10 | 0.50 | 5237.37 | 06-FEB-07:01 | 1.24 |
March | 0.373367E+10 | 0.51 | 3889.04 | 29-MAR-16:00 | 1.08 |
April | 0.392780E+10 | 0.50 | 6041.60 | 10-APR-15:30 | 1.30 |
May | 0.510303E+10 | 0.56 | 8828.72 | 30-MAY-15:20 | 1.52 |
June | 0.703981E+10 | 0.66 | 10478.50 | 19-JUN-14:30 | 1.63 |
July | 0.825599E+10 | 0.70 | 10942.09 | 10-JUL-14:50 | 1.66 |
August | 0.972675E+10 | 0.77 | 13089.33 | 03-AUG-04:02 | 1.79 |
September | 0.693673E+10 | 0.65 | 13089.33 | 01-SEP-05:02 | 1.80 |
October | 0.586092E+10 | 0.58 | 9267.28 | 04-OCT-15:30 | 1.55 |
November | 0.367757E+10 | 0.48 | 5547.82 | 02-NOV-12:07 | 1.26 |
December | 0.326628E+10 | 0.45 | 3662.81 | 04-DEC-07:03 | 1.06 |
Annual Sum or Average | 0.642705E+11 | 0.57 | |||
Minimum of Months | 0.317862E+10 | 0.45 | 3662.81 | 1.06 | |
Maximum of Months | 0.972675E+10 | 0.77 | 13089.33 | 1.80 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.349834E+10 | 0.52 | 5207.18 | 02-JAN-05:02 | 1.26 |
February | 0.308936E+10 | 0.51 | 5207.18 | 01-FEB-07:02 | 1.25 |
March | 0.332663E+10 | 0.49 | 5207.18 | 01-MAR-07:02 | 1.25 |
April | 0.341634E+10 | 0.49 | 5924.08 | 10-APR-14:05 | 1.32 |
May | 0.454279E+10 | 0.56 | 9455.00 | 30-MAY-14:05 | 1.60 |
June | 0.638367E+10 | 0.65 | 12442.41 | 19-JUN-05:02 | 1.79 |
July | 0.734510E+10 | 0.67 | 12442.41 | 10-JUL-04:01 | 1.79 |
August | 0.838163E+10 | 0.72 | 12442.41 | 03-AUG-04:02 | 1.79 |
September | 0.550563E+10 | 0.60 | 9974.00 | 01-SEP-14:50 | 1.63 |
October | 0.445667E+10 | 0.53 | 7807.54 | 04-OCT-15:00 | 1.47 |
November | 0.301838E+10 | 0.46 | 5207.18 | 20-NOV-07:01 | 1.25 |
December | 0.302021E+10 | 0.46 | 5207.18 | 04-DEC-07:03 | 1.25 |
Annual Sum or Average | 0.559848E+11 | 0.56 | |||
Minimum of Months | 0.301838E+10 | 0.46 | 5207.18 | 1.25 | |
Maximum of Months | 0.838163E+10 | 0.72 | 12442.41 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.449446E+10 | 0.56 | 5469.11 | 01-JAN-00:04 | 1.12 |
February | 0.392382E+10 | 0.54 | 5469.11 | 01-FEB-06:01 | 1.12 |
March | 0.369675E+10 | 0.46 | 5469.11 | 01-MAR-06:11 | 1.12 |
April | 0.353171E+10 | 0.44 | 5904.10 | 07-APR-15:20 | 1.14 |
May | 0.448169E+10 | 0.49 | 9032.90 | 30-MAY-14:00 | 1.37 |
June | 0.599064E+10 | 0.56 | 10403.18 | 19-JUN-14:00 | 1.45 |
July | 0.690476E+10 | 0.58 | 16875.01 | 10-JUL-04:01 | 1.78 |
August | 0.773898E+10 | 0.61 | 12036.76 | 05-AUG-04:01 | 1.54 |
September | 0.499517E+10 | 0.51 | 9646.29 | 01-SEP-14:30 | 1.40 |
October | 0.400375E+10 | 0.45 | 6743.72 | 04-OCT-14:30 | 1.21 |
November | 0.341596E+10 | 0.44 | 5469.11 | 06-NOV-06:11 | 1.12 |
December | 0.375433E+10 | 0.47 | 5469.11 | 01-DEC-07:03 | 1.12 |
Annual Sum or Average | 0.569320E+11 | 0.51 | |||
Minimum of Months | 0.341596E+10 | 0.44 | 5469.11 | 1.12 | |
Maximum of Months | 0.773898E+10 | 0.61 | 16875.01 | 1.78 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.787904E+09 | 0.709113E+09 | 1293.09 | 02-JAN-05:02 | 1163.78 | 1163.78 | 42.62 | 4.15 |
February | 0.677459E+09 | 0.609713E+09 | 1266.37 | 06-FEB-07:01 | 1139.74 | 1139.74 | 46.03 | 4.04 |
March | 0.280965E+09 | 0.252869E+09 | 1135.58 | 20-MAR-05:01 | 1022.02 | 1022.02 | 40.22 | 3.62 |
April | 0.108106E+09 | 97295003.47 | 1097.53 | 03-APR-06:01 | 987.78 | 987.78 | 41.21 | 3.44 |
May | 17749717.13 | 15974745.42 | 1032.61 | 01-MAY-06:03 | 929.35 | 929.35 | 38.76 | 2.99 |
June | 172141.72 | 154927.55 | 34.49 | 02-JUN-06:07 | 31.04 | 31.04 | 34.92 | 0.04 |
July | 39196.55 | 35276.90 | 0.12 | 05-JUL-15:50 | 0.11 | 0.11 | 30.90 | 0.00 |
August | 46753.80 | 42078.42 | 0.12 | 09-AUG-13:20 | 0.11 | 0.11 | 31.48 | 0.00 |
September | 1959351.96 | 1763416.77 | 395.41 | 29-SEP-06:03 | 355.87 | 355.87 | 27.56 | 0.48 |
October | 23852798.33 | 21467518.50 | 1004.41 | 28-OCT-06:03 | 903.97 | 903.97 | 39.23 | 2.70 |
November | 0.243871E+09 | 0.219484E+09 | 1157.63 | 24-NOV-06:01 | 1041.87 | 1041.87 | 42.26 | 3.71 |
December | 0.465367E+09 | 0.418830E+09 | 1125.26 | 11-DEC-06:01 | 1012.73 | 1012.73 | 42.80 | 3.57 |
Annual Sum or Average | 0.260749E+10 | 0.234674E+10 | ||||||
Minimum of Months | 39196.55 | 35276.90 | 0.12 | 0.11 | 0.11 | 27.56 | 0.00 | |
Maximum of Months | 0.787904E+09 | 0.709113E+09 | 1293.09 | 1163.78 | 1163.78 | 46.03 | 4.15 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:02 | 2.06 | 2.06 | 58.09 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 57.17 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:05 | 2.06 | 2.06 | 56.74 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.88 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.28 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.43 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.59 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:02 | 2.06 | 2.06 | 57.78 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 57.74 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.33 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.28 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 56.99 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.74 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.33 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 44.78 | 44.78 | 40188.67 | 315234.19 | 20-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 36.28 | 36.28 | 37699.72 | 318857.28 | 02-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 31.97 | 31.97 | 13995.54 | 361400.90 | 06-MAR-06:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.92 | 26.92 | 5383.95 | 322867.37 | 03-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.47 | 20.47 | 707.93 | 265543.48 | 01-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 35.07 | 35.07 | 7.74 | 3720.25 | 02-JUN-06:07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.79 | 30.79 | 1.80 | 14.79 | 05-JUL-15:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 31.33 | 31.33 | 2.11 | 14.26 | 09-AUG-13:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.54 | 31.54 | 108.23 | 64867.27 | 29-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.58 | 25.58 | 1137.61 | 234139.51 | 28-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23.37 | 23.37 | 12453.65 | 341733.14 | 27-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 28.98 | 28.98 | 23051.65 | 319271.44 | 20-DEC-06:11 |
Annual Sum or Average | 0.00 | 11084.50 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.47 | 20.47 | 1.80 | 14.26 | ||
Maximum of Months | 0.00 | 0.00 | 44.78 | 44.78 | 40188.67 | 361400.90 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 58.09 | 58.09 | 1753.16 | 6437.59 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.54 | 57.54 | 1781.51 | 6446.36 | 09-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.55 | 57.55 | 1862.65 | 6396.56 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.64 | 57.64 | 1644.30 | 6126.57 | 03-APR-11:17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.24 | 58.24 | 1591.41 | 5771.04 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.96 | 57.96 | 1517.24 | 5345.04 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.09 | 58.09 | 1311.24 | 4990.77 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.16 | 58.16 | 1431.13 | 4874.06 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.15 | 58.15 | 1372.29 | 5103.53 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.25 | 57.25 | 1460.48 | 5503.66 | 31-OCT-11:17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.90 | 57.90 | 1598.39 | 6845.64 | 22-NOV-13:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.74 | 57.74 | 1633.52 | 6246.38 | 29-DEC-12:17 |
Annual Sum or Average | 0.00 | 1578.63 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.25 | 57.25 | 1311.24 | 4874.06 | ||
Maximum of Months | 0.00 | 0.00 | 58.24 | 58.24 | 1862.65 | 6845.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.273736E+11 | 0.00 | 0.00 | 0.440272E+10 | 0.00 | 0.00 |
February | 0.232170E+11 | 0.00 | 0.00 | 0.365691E+10 | 0.00 | 0.00 |
March | 0.109749E+11 | 0.00 | 0.00 | 0.646285E+10 | 0.00 | 0.00 |
April | 0.486391E+10 | 0.00 | 0.00 | 0.932988E+10 | 0.00 | 0.00 |
May | 0.983566E+09 | 0.00 | 0.00 | 0.149252E+11 | 0.00 | 0.00 |
June | 19933537.51 | 0.00 | 0.00 | 0.238714E+11 | 0.00 | 0.00 |
July | 1577349.15 | 0.00 | 0.00 | 0.309769E+11 | 0.00 | 0.00 |
August | 2093594.12 | 0.00 | 0.00 | 0.336032E+11 | 0.00 | 0.00 |
September | 61705734.58 | 0.00 | 0.00 | 0.217086E+11 | 0.00 | 0.00 |
October | 0.431455E+09 | 0.00 | 0.00 | 0.162745E+11 | 0.00 | 0.00 |
November | 0.626258E+10 | 0.00 | 0.00 | 0.740269E+10 | 0.00 | 0.00 |
December | 0.131082E+11 | 0.00 | 0.00 | 0.428359E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.873005E+11 | 0.00 | 0.00 | 0.176899E+12 | 0.00 | 0.00 |
Minimum of Months | 1577349.15 | 0.00 | 0.00 | 0.365691E+10 | 0.00 | 0.00 |
Maximum of Months | 0.273736E+11 | 0.00 | 0.00 | 0.336032E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.307629E+11 | 0.00 | 0.00 | 0.381334E+10 | 0.00 | 0.00 |
February | 0.256952E+11 | 0.00 | 0.00 | 0.317316E+10 | 0.00 | 0.00 |
March | 0.926978E+10 | 0.00 | 0.00 | 0.477964E+10 | 0.00 | 0.00 |
April | 0.264030E+10 | 0.00 | 0.00 | 0.739567E+10 | 0.00 | 0.00 |
May | 0.119708E+09 | 0.00 | 0.00 | 0.133722E+11 | 0.00 | 0.00 |
June | 824454.32 | 0.00 | 0.00 | 0.221560E+11 | 0.00 | 0.00 |
July | 1440098.77 | 0.00 | 0.00 | 0.284056E+11 | 0.00 | 0.00 |
August | 1820280.65 | 0.00 | 0.00 | 0.296403E+11 | 0.00 | 0.00 |
September | 3447501.82 | 0.00 | 0.00 | 0.180157E+11 | 0.00 | 0.00 |
October | 0.407488E+09 | 0.00 | 0.00 | 0.124483E+11 | 0.00 | 0.00 |
November | 0.822395E+10 | 0.00 | 0.00 | 0.501385E+10 | 0.00 | 0.00 |
December | 0.167388E+11 | 0.00 | 0.00 | 0.318426E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.938657E+11 | 0.00 | 0.00 | 0.151398E+12 | 0.00 | 0.00 |
Minimum of Months | 824454.32 | 0.00 | 0.00 | 0.317316E+10 | 0.00 | 0.00 |
Maximum of Months | 0.307629E+11 | 0.00 | 0.00 | 0.296403E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.503524E+11 | 0.00 | 0.00 | 0.516577E+10 | 0.00 | 0.00 |
February | 0.430151E+11 | 0.00 | 0.00 | 0.424756E+10 | 0.00 | 0.00 |
March | 0.175458E+11 | 0.00 | 0.00 | 0.601109E+10 | 0.00 | 0.00 |
April | 0.657276E+10 | 0.00 | 0.00 | 0.863875E+10 | 0.00 | 0.00 |
May | 0.795932E+09 | 0.00 | 0.00 | 0.151996E+11 | 0.00 | 0.00 |
June | 3952083.41 | 0.00 | 0.00 | 0.241481E+11 | 0.00 | 0.00 |
July | 1294193.58 | 0.00 | 0.00 | 0.306117E+11 | 0.00 | 0.00 |
August | 1566186.92 | 0.00 | 0.00 | 0.315716E+11 | 0.00 | 0.00 |
September | 0.223731E+09 | 0.00 | 0.00 | 0.188641E+11 | 0.00 | 0.00 |
October | 0.223561E+10 | 0.00 | 0.00 | 0.126447E+11 | 0.00 | 0.00 |
November | 0.180469E+11 | 0.00 | 0.00 | 0.593776E+10 | 0.00 | 0.00 |
December | 0.323764E+11 | 0.00 | 0.00 | 0.418190E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.171171E+12 | 0.00 | 0.00 | 0.167223E+12 | 0.00 | 0.00 |
Minimum of Months | 1294193.58 | 0.00 | 0.00 | 0.418190E+10 | 0.00 | 0.00 |
Maximum of Months | 0.503524E+11 | 0.00 | 0.00 | 0.315716E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.356334E+10 | 0.306278E+10 | 0.273736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317862E+10 | 0.172253E+10 | 0.232170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373367E+10 | 0.103204E+11 | 0.109749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.392780E+10 | 0.214996E+11 | 0.486391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.510303E+10 | 0.409253E+11 | 0.983566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.703981E+10 | 0.720812E+11 | 19933537.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.825599E+10 | 0.958218E+11 | 1577349.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.972675E+10 | 0.991217E+11 | 2093594.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.693673E+10 | 0.637150E+11 | 61705734.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.586092E+10 | 0.444382E+11 | 0.431455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367757E+10 | 0.145894E+11 | 0.626258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326628E+10 | 0.370060E+10 | 0.131082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.642705E+11 | 0.470999E+12 | 0.873005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.317862E+10 | 0.172253E+10 | 1577349.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.972675E+10 | 0.991217E+11 | 0.273736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.349834E+10 | 0.113544E+10 | 0.307629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308936E+10 | 0.296874E+09 | 0.256952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332663E+10 | 0.546333E+10 | 0.926978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341634E+10 | 0.157552E+11 | 0.264030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.454279E+10 | 0.362746E+11 | 0.119708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.638367E+10 | 0.672075E+11 | 824454.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.734510E+10 | 0.888143E+11 | 1440098.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.838163E+10 | 0.881192E+11 | 1820280.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550563E+10 | 0.533275E+11 | 3447501.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.445667E+10 | 0.334496E+11 | 0.407488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301838E+10 | 0.759182E+10 | 0.822395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302021E+10 | 0.584574E+09 | 0.167388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559848E+11 | 0.398020E+12 | 0.938657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301838E+10 | 0.296874E+09 | 824454.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.838163E+10 | 0.888143E+11 | 0.307629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.449446E+10 | 0.242909E+10 | 0.503524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392382E+10 | 0.115878E+10 | 0.430151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369675E+10 | 0.870248E+10 | 0.175458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353171E+10 | 0.200957E+11 | 0.657276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.448169E+10 | 0.435869E+11 | 0.795932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.599064E+10 | 0.763809E+11 | 3952083.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.690476E+10 | 0.992078E+11 | 1294193.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.773898E+10 | 0.980366E+11 | 1566186.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.499517E+10 | 0.580655E+11 | 0.223731E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.400375E+10 | 0.353779E+11 | 0.223561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341596E+10 | 0.947793E+10 | 0.180469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375433E+10 | 0.153122E+10 | 0.323764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569320E+11 | 0.454051E+12 | 0.171171E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.341596E+10 | 0.115878E+10 | 1294193.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.773898E+10 | 0.992078E+11 | 0.503524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.356334E+10 | 0.273736E+11 | 0.00 | 0.00 | 0.839373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317862E+10 | 0.232170E+11 | 0.00 | 0.00 | 0.478297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373367E+10 | 0.109749E+11 | 0.00 | 0.00 | 0.272919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.392780E+10 | 0.486391E+10 | 0.00 | 0.00 | 0.540208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.510303E+10 | 0.983566E+09 | 0.00 | 0.00 | 0.982217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.703981E+10 | 19933537.51 | 0.00 | 0.00 | 0.168316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.825599E+10 | 1577349.15 | 0.00 | 0.00 | 0.227209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.972675E+10 | 2093594.12 | 0.00 | 0.00 | 0.238765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.693673E+10 | 61705734.58 | 0.00 | 0.00 | 0.147718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.586092E+10 | 0.431455E+09 | 0.00 | 0.00 | 0.104136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367757E+10 | 0.626258E+10 | 0.00 | 0.00 | 0.372512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326628E+10 | 0.131082E+11 | 0.00 | 0.00 | 0.101731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.642705E+11 | 0.873005E+11 | 0.00 | 0.00 | 0.112628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.317862E+10 | 1577349.15 | 0.00 | 0.00 | 0.478297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.972675E+10 | 0.273736E+11 | 0.00 | 0.00 | 0.238765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.349834E+10 | 0.307629E+11 | 0.00 | 0.00 | 0.314999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308936E+10 | 0.256952E+11 | 0.00 | 0.00 | 83797366.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332663E+10 | 0.926978E+10 | 0.00 | 0.00 | 0.145300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341634E+10 | 0.264030E+10 | 0.00 | 0.00 | 0.397932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.454279E+10 | 0.119708E+09 | 0.00 | 0.00 | 0.882942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.638367E+10 | 824454.32 | 0.00 | 0.00 | 0.157723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.734510E+10 | 1440098.77 | 0.00 | 0.00 | 0.210605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.838163E+10 | 1820280.65 | 0.00 | 0.00 | 0.212587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550563E+10 | 3447501.82 | 0.00 | 0.00 | 0.125100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.445667E+10 | 0.407488E+09 | 0.00 | 0.00 | 0.799158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301838E+10 | 0.822395E+10 | 0.00 | 0.00 | 0.199547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302021E+10 | 0.167388E+11 | 0.00 | 0.00 | 0.164044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559848E+11 | 0.938657E+11 | 0.00 | 0.00 | 0.954132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301838E+10 | 824454.32 | 0.00 | 0.00 | 83797366.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.838163E+10 | 0.307629E+11 | 0.00 | 0.00 | 0.212587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.449446E+10 | 0.503524E+11 | 0.00 | 0.00 | 0.671311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392382E+10 | 0.430151E+11 | 0.00 | 0.00 | 0.323740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369675E+10 | 0.175458E+11 | 0.00 | 0.00 | 0.231435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353171E+10 | 0.657276E+10 | 0.00 | 0.00 | 0.510703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.448169E+10 | 0.795932E+09 | 0.00 | 0.00 | 0.107179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.599064E+10 | 3952083.41 | 0.00 | 0.00 | 0.181575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.690476E+10 | 1294193.58 | 0.00 | 0.00 | 0.237070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.773898E+10 | 1566186.92 | 0.00 | 0.00 | 0.238326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.499517E+10 | 0.223731E+09 | 0.00 | 0.00 | 0.138689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.400375E+10 | 0.223561E+10 | 0.00 | 0.00 | 0.864091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341596E+10 | 0.180469E+11 | 0.00 | 0.00 | 0.252180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375433E+10 | 0.323764E+11 | 0.00 | 0.00 | 0.427567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569320E+11 | 0.171171E+12 | 0.00 | 0.00 | 0.110291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.341596E+10 | 1294193.58 | 0.00 | 0.00 | 0.323740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.773898E+10 | 0.503524E+11 | 0.00 | 0.00 | 0.238326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103325E+11 | 0.00 | 0.00 | 5063801.64 | 0.00 | 0.603572E+09 | 0.332921E+10 | 0.00 | 0.28 |
February | 0.994265E+10 | 0.00 | 0.00 | 6828651.27 | 0.00 | 3790133.70 | 0.402661E+10 | 0.00 | 0.28 |
March | 0.435060E+10 | 2092495.79 | 0.00 | 24978390.50 | 0.00 | 0.00 | 0.816795E+10 | 0.00 | 0.29 |
April | 0.150182E+10 | 4784579.51 | 0.00 | 32650058.38 | 0.00 | 0.00 | 0.716470E+10 | 0.00 | 0.29 |
May | 0.407233E+09 | 0.105732E+09 | 0.00 | 42551053.60 | 34336284.37 | 0.00 | 0.491728E+10 | 0.00 | 0.32 |
June | 95233693.79 | 0.330025E+10 | 0.00 | 19237442.42 | 0.288349E+09 | 0.00 | 0.113653E+10 | 0.00 | 0.34 |
July | 4364525.38 | 0.826966E+10 | 0.00 | 2134841.90 | 0.110516E+10 | 0.00 | 60013448.34 | 0.00 | 0.32 |
August | 74397440.76 | 0.634057E+10 | 0.00 | 18881335.46 | 0.441191E+09 | 0.00 | 0.658228E+09 | 0.00 | 0.33 |
September | 0.243811E+09 | 0.195428E+10 | 0.00 | 30866877.73 | 81111729.65 | 0.00 | 0.267442E+10 | 0.00 | 0.32 |
October | 0.520445E+09 | 0.181040E+09 | 0.00 | 44881249.58 | 2002440.28 | 0.00 | 0.561920E+10 | 0.00 | 0.31 |
November | 0.268314E+10 | 20174.39 | 0.00 | 29940155.00 | 0.00 | 0.00 | 0.768516E+10 | 0.00 | 0.28 |
December | 0.595496E+10 | 0.00 | 0.00 | 14765938.88 | 0.00 | 0.00 | 0.683883E+10 | 0.00 | 0.26 |
Annual Sum or Average | 0.361111E+11 | 0.201584E+11 | 0.00 | 0.272780E+09 | 0.195215E+10 | 0.607362E+09 | 0.522781E+11 | 0.00 | 0.30 |
Minimum of Months | 4364525.38 | 0.00 | 0.00 | 2134841.90 | 0.00 | 0.00 | 60013448.34 | 0.00 | 0.26 |
Maximum of Months | 0.103325E+11 | 0.826966E+10 | 0.00 | 44881249.58 | 0.110516E+10 | 0.603572E+09 | 0.816795E+10 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120390E+11 | 0.00 | 0.00 | 7890.96 | 0.00 | 0.144426E+10 | 32110581.01 | 0.00 | 0.28 |
February | 0.122984E+11 | 0.00 | 0.00 | 27574.88 | 0.00 | 0.676638E+09 | 0.114889E+09 | 0.00 | 0.27 |
March | 0.938291E+10 | 74860.93 | 0.00 | 1968131.13 | 3040377.18 | 43151250.22 | 0.148738E+10 | 0.00 | 0.26 |
April | 0.450482E+10 | 3728329.93 | 0.00 | 10110624.00 | 1619052.36 | 3253098.43 | 0.276692E+10 | 0.00 | 0.25 |
May | 0.158837E+10 | 93186336.05 | 0.00 | 19564684.83 | 39547976.80 | 0.00 | 0.271331E+10 | 0.00 | 0.27 |
June | 0.162876E+09 | 0.267293E+10 | 0.00 | 11816632.28 | 0.372434E+09 | 0.00 | 0.783685E+09 | 0.00 | 0.28 |
July | 4214611.70 | 0.682373E+10 | 0.00 | 1877615.69 | 0.108817E+10 | 0.00 | 53432750.00 | 0.00 | 0.27 |
August | 88734348.19 | 0.537589E+10 | 0.00 | 12290965.49 | 0.430795E+09 | 0.00 | 0.521006E+09 | 0.00 | 0.27 |
September | 0.594897E+09 | 0.167719E+10 | 0.00 | 14866901.32 | 0.104765E+09 | 0.00 | 0.148204E+10 | 0.00 | 0.27 |
October | 0.185824E+10 | 0.178189E+09 | 0.00 | 17258520.21 | 21798048.68 | 0.00 | 0.263590E+10 | 0.00 | 0.25 |
November | 0.713803E+10 | 0.00 | 0.00 | 4589547.30 | 1066392.71 | 89669417.05 | 0.144470E+10 | 0.00 | 0.24 |
December | 0.111787E+11 | 0.00 | 0.00 | 94071.81 | 0.00 | 92840526.30 | 0.266473E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.608391E+11 | 0.168249E+11 | 0.00 | 94473159.88 | 0.206323E+10 | 0.234982E+10 | 0.143019E+11 | 0.00 | 0.26 |
Minimum of Months | 4214611.70 | 0.00 | 0.00 | 7890.96 | 0.00 | 0.00 | 32110581.01 | 0.00 | 0.24 |
Maximum of Months | 0.122984E+11 | 0.682373E+10 | 0.00 | 19564684.83 | 0.108817E+10 | 0.144426E+10 | 0.276692E+10 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.958549E+10 | 0.00 | 0.00 | 0.00 | 137324.08 | 0.415497E+10 | 0.00 | 0.00 | 0.31 |
February | 0.100691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323514E+10 | 0.00 | 0.00 | 0.30 |
March | 0.909838E+10 | 0.00 | 0.00 | 767438.92 | 3399865.26 | 0.720432E+09 | 0.384573E+09 | 0.00 | 0.26 |
April | 0.493494E+10 | 159371.23 | 0.00 | 6497360.13 | 9006279.75 | 0.119179E+09 | 0.148669E+10 | 0.00 | 0.24 |
May | 0.188258E+10 | 93737308.40 | 0.00 | 15049666.58 | 47988377.52 | 3001425.96 | 0.200282E+10 | 0.00 | 0.26 |
June | 0.222473E+09 | 0.264317E+10 | 0.00 | 10192767.84 | 0.445470E+09 | 0.00 | 0.710926E+09 | 0.00 | 0.28 |
July | 9561164.27 | 0.649579E+10 | 0.00 | 2334125.22 | 0.113022E+10 | 0.00 | 59311465.95 | 0.00 | 0.27 |
August | 89650465.71 | 0.511173E+10 | 0.00 | 11619702.05 | 0.564176E+09 | 0.00 | 0.474921E+09 | 0.00 | 0.27 |
September | 0.734623E+09 | 0.154254E+10 | 0.00 | 10591884.85 | 0.337324E+09 | 0.00 | 0.926577E+09 | 0.00 | 0.26 |
October | 0.238402E+10 | 0.141352E+09 | 0.00 | 7853868.94 | 0.138727E+09 | 4582132.95 | 0.126045E+10 | 0.00 | 0.23 |
November | 0.686857E+10 | 0.00 | 0.00 | 493255.85 | 5214635.00 | 0.957343E+09 | 0.239897E+09 | 0.00 | 0.25 |
December | 0.934335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183927E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.552227E+11 | 0.160285E+11 | 0.00 | 65400070.39 | 0.268166E+10 | 0.110339E+11 | 0.754617E+10 | 0.00 | 0.27 |
Minimum of Months | 9561164.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.100691E+11 | 0.649579E+10 | 0.00 | 15049666.58 | 0.113022E+10 | 0.415497E+10 | 0.200282E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.740187E+09 | 0.00 | 31217.38 | 0.00 | 25779.07 | 0.552707E+10 | 0.00 | 5003.02 | 0.66 |
February | 0.847136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524579E+10 | 0.00 | 0.00 | 0.64 |
March | 0.226009E+10 | 0.00 | 0.00 | 0.00 | 1534980.91 | 0.235294E+10 | 0.00 | 0.00 | 0.55 |
April | 0.203918E+10 | 0.00 | 0.00 | 416789.88 | 4138134.37 | 0.699567E+09 | 0.133559E+09 | 0.00 | 0.49 |
May | 0.117787E+10 | 21184991.06 | 0.00 | 2056923.46 | 32834951.09 | 31254922.67 | 0.374544E+09 | 0.00 | 0.51 |
June | 0.149154E+09 | 0.759605E+09 | 0.00 | 2581526.68 | 0.386928E+09 | 0.00 | 0.191245E+09 | 0.00 | 0.49 |
July | 5088948.63 | 0.206067E+10 | 0.00 | 670245.68 | 0.776105E+09 | 0.00 | 18361337.18 | 0.00 | 0.48 |
August | 51074696.92 | 0.163708E+10 | 0.00 | 3033711.31 | 0.424242E+09 | 0.00 | 0.136828E+09 | 0.00 | 0.47 |
September | 0.472778E+09 | 0.327506E+09 | 0.00 | 1555936.51 | 0.365133E+09 | 3131302.92 | 0.170036E+09 | 0.00 | 0.47 |
October | 0.132782E+10 | 12835103.70 | 0.00 | 408942.52 | 0.104565E+09 | 0.166075E+09 | 76529649.63 | 0.00 | 0.47 |
November | 0.158120E+10 | 0.00 | 386923.77 | 0.00 | 1960184.87 | 0.206783E+10 | 0.00 | 7209.71 | 0.53 |
December | 0.952242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410559E+10 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.116038E+11 | 0.481889E+10 | 418141.15 | 10724076.04 | 0.209747E+10 | 0.201992E+11 | 0.110110E+10 | 12212.73 | 0.53 |
Minimum of Months | 5088948.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.226009E+10 | 0.206067E+10 | 386923.77 | 3033711.31 | 0.776105E+09 | 0.552707E+10 | 0.374544E+09 | 7209.71 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.808223E+09 | 0.00 | 20766.59 | 0.00 | 17202.18 | 0.335770E+10 | 0.00 | 3403.00 | 0.70 |
February | 0.110869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292602E+10 | 0.00 | 0.00 | 0.67 |
March | 0.182061E+10 | 0.00 | 0.00 | 123963.75 | 1024281.14 | 0.117399E+10 | 82852081.69 | 0.00 | 0.58 |
April | 0.119874E+10 | 3298912.70 | 0.00 | 1752912.05 | 0.00 | 0.404682E+09 | 0.361274E+09 | 0.00 | 0.54 |
May | 0.583431E+09 | 31159742.75 | 0.00 | 4003876.72 | 14323351.05 | 8876526.69 | 0.576413E+09 | 0.00 | 0.59 |
June | 66520869.36 | 0.632081E+09 | 0.00 | 3038413.94 | 0.232568E+09 | 0.00 | 0.208437E+09 | 0.00 | 0.58 |
July | 3144012.43 | 0.174643E+10 | 0.00 | 676152.52 | 0.422188E+09 | 0.00 | 16639238.43 | 0.00 | 0.58 |
August | 28306548.67 | 0.145898E+10 | 0.00 | 2981901.22 | 0.219606E+09 | 0.00 | 0.126922E+09 | 0.00 | 0.61 |
September | 0.245729E+09 | 0.304989E+09 | 0.00 | 2476953.39 | 0.201462E+09 | 1163954.69 | 0.225243E+09 | 0.00 | 0.55 |
October | 0.755301E+09 | 32499981.47 | 0.00 | 1203479.76 | 54606212.09 | 72424919.87 | 0.224061E+09 | 0.00 | 0.51 |
November | 0.134401E+10 | 0.00 | 258202.95 | 492.30 | 1308016.52 | 0.108477E+10 | 3175353.60 | 4799.34 | 0.56 |
December | 0.113140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224259E+10 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.909410E+10 | 0.420943E+10 | 278969.55 | 16258145.66 | 0.114710E+10 | 0.112722E+11 | 0.182502E+10 | 8202.34 | 0.59 |
Minimum of Months | 3144012.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.182061E+10 | 0.174643E+10 | 258202.95 | 4003876.72 | 0.422188E+09 | 0.335770E+10 | 0.576413E+09 | 4799.34 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179744E+10 | 0.00 | 30847.30 | 462622.92 | 25466.39 | 0.407654E+10 | 0.289148E+09 | 4933.77 | 0.65 |
February | 0.205987E+10 | 0.00 | 0.00 | 1003442.17 | 0.00 | 0.342433E+10 | 0.532041E+09 | 0.00 | 0.63 |
March | 0.219122E+10 | 1337108.22 | 0.00 | 3981500.82 | 382774.12 | 0.154985E+10 | 0.103888E+10 | 0.00 | 0.57 |
April | 0.163032E+10 | 1931090.76 | 0.00 | 4156125.15 | 2255302.12 | 0.600029E+09 | 0.775898E+09 | 0.00 | 0.53 |
May | 0.956059E+09 | 25232073.53 | 0.00 | 4927971.13 | 31696304.63 | 32748872.88 | 0.692943E+09 | 0.00 | 0.53 |
June | 0.139885E+09 | 0.826839E+09 | 0.00 | 3438954.69 | 0.393234E+09 | 0.00 | 0.231297E+09 | 0.00 | 0.52 |
July | 5174044.19 | 0.234019E+10 | 0.00 | 874353.34 | 0.727503E+09 | 0.00 | 21737903.31 | 0.00 | 0.51 |
August | 43345726.42 | 0.208739E+10 | 0.00 | 5051982.00 | 0.359989E+09 | 0.00 | 0.209027E+09 | 0.00 | 0.57 |
September | 0.324965E+09 | 0.538750E+09 | 0.00 | 6407968.30 | 0.268287E+09 | 2004270.63 | 0.506155E+09 | 0.00 | 0.57 |
October | 0.781329E+09 | 71893106.21 | 0.00 | 7178517.05 | 69419365.53 | 0.100351E+09 | 0.996074E+09 | 0.00 | 0.58 |
November | 0.184395E+10 | 0.00 | 382534.08 | 2623939.43 | 1936409.17 | 0.134551E+10 | 0.522020E+09 | 6818.83 | 0.54 |
December | 0.182123E+10 | 0.00 | 0.00 | 707993.51 | 0.00 | 0.277765E+10 | 0.410327E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.135948E+11 | 0.589356E+10 | 413381.38 | 40815370.51 | 0.185473E+10 | 0.139090E+11 | 0.622554E+10 | 11752.60 | 0.56 |
Minimum of Months | 5174044.19 | 0.00 | 0.00 | 462622.92 | 0.00 | 0.00 | 21737903.31 | 0.00 | 0.51 |
Maximum of Months | 0.219122E+10 | 0.234019E+10 | 382534.08 | 7178517.05 | 0.727503E+09 | 0.407654E+10 | 0.103888E+10 | 6818.83 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.898802E+09 | 0.00 | 23442.99 | 0.00 | 19121.66 | 0.372343E+10 | 0.00 | 3423.53 | 0.77 |
February | 0.102521E+10 | 0.00 | 0.00 | 2702.84 | 0.00 | 0.344248E+10 | 28809575.33 | 0.00 | 0.75 |
March | 0.169270E+10 | 0.00 | 0.00 | 681568.76 | 1138573.94 | 0.146498E+10 | 0.282112E+09 | 0.00 | 0.65 |
April | 0.130971E+10 | 0.00 | 0.00 | 2116790.45 | 3069466.15 | 0.478662E+09 | 0.435462E+09 | 0.00 | 0.61 |
May | 0.740748E+09 | 18774720.50 | 0.00 | 3431861.62 | 23963980.10 | 25416391.78 | 0.531201E+09 | 0.00 | 0.64 |
June | 0.103374E+09 | 0.648961E+09 | 0.00 | 2630504.99 | 0.266652E+09 | 0.00 | 0.192149E+09 | 0.00 | 0.63 |
July | 3675982.57 | 0.169426E+10 | 0.00 | 745603.38 | 0.570950E+09 | 0.00 | 17487464.70 | 0.00 | 0.60 |
August | 35842737.03 | 0.144753E+10 | 0.00 | 3108923.14 | 0.293312E+09 | 0.00 | 0.141042E+09 | 0.00 | 0.63 |
September | 0.308369E+09 | 0.319925E+09 | 0.00 | 2285158.09 | 0.233727E+09 | 1954579.96 | 0.225280E+09 | 0.00 | 0.59 |
October | 0.819562E+09 | 18623299.69 | 0.00 | 1696550.56 | 72689173.33 | 0.110274E+09 | 0.277055E+09 | 0.00 | 0.58 |
November | 0.126193E+10 | 0.00 | 287455.32 | 91944.19 | 1453969.49 | 0.139591E+10 | 43847686.52 | 4893.67 | 0.62 |
December | 0.960834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278707E+10 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.916076E+10 | 0.414807E+10 | 310898.31 | 16791608.02 | 0.146697E+10 | 0.134302E+11 | 0.217445E+10 | 8317.20 | 0.64 |
Minimum of Months | 3675982.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.169270E+10 | 0.169426E+10 | 287455.32 | 3431861.62 | 0.570950E+09 | 0.372343E+10 | 0.531201E+09 | 4893.67 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.693492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393375E+10 | 0.00 | 0.00 | 0.43 |
February | 0.601094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394253E+10 | 0.00 | 0.00 | 0.42 |
March | 0.170471E+10 | 0.00 | 0.00 | 0.00 | 547034.11 | 0.197112E+10 | 0.00 | 0.00 | 0.40 |
April | 0.165413E+10 | 0.00 | 0.00 | 4969.71 | 1255654.25 | 0.608274E+09 | 8517424.04 | 0.00 | 0.35 |
May | 0.113514E+10 | 16305120.25 | 0.00 | 370600.33 | 13084351.37 | 7907391.55 | 79512696.35 | 0.00 | 0.33 |
June | 0.136821E+09 | 0.535001E+09 | 0.00 | 1575062.52 | 0.203455E+09 | 0.00 | 0.115211E+09 | 0.00 | 0.33 |
July | 4709749.95 | 0.163341E+10 | 0.00 | 387951.95 | 0.505488E+09 | 0.00 | 9453297.86 | 0.00 | 0.35 |
August | 58103539.20 | 0.134636E+10 | 0.00 | 2507893.10 | 0.231778E+09 | 0.00 | 94779002.80 | 0.00 | 0.35 |
September | 0.412113E+09 | 0.338823E+09 | 0.00 | 1825438.89 | 77372123.57 | 0.00 | 0.197015E+09 | 0.00 | 0.32 |
October | 0.118599E+10 | 22459792.82 | 0.00 | 860900.87 | 10811729.30 | 4143264.42 | 0.144705E+09 | 0.00 | 0.30 |
November | 0.204563E+10 | 0.00 | 0.00 | 0.00 | 5966.95 | 0.821544E+09 | 0.00 | 0.00 | 0.35 |
December | 0.148858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241994E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.111205E+11 | 0.389236E+10 | 0.00 | 7532817.38 | 0.104380E+10 | 0.137092E+11 | 0.649194E+09 | 0.00 | 0.36 |
Minimum of Months | 4709749.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.204563E+10 | 0.163341E+10 | 0.00 | 2507893.10 | 0.505488E+09 | 0.394253E+10 | 0.197015E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.895914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249725E+10 | 0.00 | 0.00 | 0.49 |
February | 0.977415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234944E+10 | 0.00 | 0.00 | 0.49 |
March | 0.180162E+10 | 0.00 | 0.00 | 19032.92 | 406024.09 | 0.889100E+09 | 35466113.10 | 0.00 | 0.47 |
April | 0.119663E+10 | 987256.61 | 0.00 | 875294.99 | 0.00 | 0.304517E+09 | 0.196857E+09 | 0.00 | 0.41 |
May | 0.631345E+09 | 20884046.26 | 0.00 | 2324682.49 | 8110797.80 | 3012713.39 | 0.311543E+09 | 0.00 | 0.42 |
June | 67404470.27 | 0.478346E+09 | 0.00 | 2439675.12 | 0.135795E+09 | 0.00 | 0.157413E+09 | 0.00 | 0.43 |
July | 2471288.67 | 0.144874E+10 | 0.00 | 423873.30 | 0.317284E+09 | 0.00 | 11716653.87 | 0.00 | 0.46 |
August | 33033140.98 | 0.125477E+10 | 0.00 | 2953145.67 | 0.149464E+09 | 0.00 | 0.113233E+09 | 0.00 | 0.50 |
September | 0.238280E+09 | 0.297832E+09 | 0.00 | 2944123.64 | 47055608.34 | 0.00 | 0.268982E+09 | 0.00 | 0.42 |
October | 0.668260E+09 | 24174103.25 | 0.00 | 2723133.08 | 6082928.44 | 652583.03 | 0.348021E+09 | 0.00 | 0.38 |
November | 0.161472E+10 | 0.00 | 0.00 | 69156.23 | 4428.84 | 0.462646E+09 | 48894731.99 | 0.00 | 0.41 |
December | 0.147172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142846E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.959881E+10 | 0.352573E+10 | 0.00 | 14772117.45 | 0.664202E+09 | 0.793508E+10 | 0.149213E+10 | 0.00 | 0.44 |
Minimum of Months | 2471288.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.180162E+10 | 0.144874E+10 | 0.00 | 2953145.67 | 0.317284E+09 | 0.249725E+10 | 0.348021E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394115E+10 | 0.00 | 0.00 | 0.46 |
February | 0.128648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364435E+10 | 0.00 | 0.00 | 0.46 |
March | 0.168593E+10 | 428746.92 | 0.00 | 417705.15 | 109621.90 | 0.214730E+10 | 0.135397E+09 | 0.00 | 0.42 |
April | 0.130793E+10 | 1274277.68 | 0.00 | 1187166.98 | 126965.22 | 0.910695E+09 | 0.169358E+09 | 0.00 | 0.37 |
May | 0.910002E+09 | 24233553.13 | 0.00 | 1393373.12 | 12889902.74 | 0.135690E+09 | 0.187559E+09 | 0.00 | 0.34 |
June | 0.146142E+09 | 0.680049E+09 | 0.00 | 2057693.59 | 0.195798E+09 | 6133567.05 | 0.111869E+09 | 0.00 | 0.36 |
July | 5770332.89 | 0.212013E+10 | 0.00 | 519165.23 | 0.470892E+09 | 0.00 | 10477645.80 | 0.00 | 0.41 |
August | 54253721.13 | 0.208938E+10 | 0.00 | 4478785.68 | 0.201346E+09 | 0.00 | 0.153943E+09 | 0.00 | 0.48 |
September | 0.270369E+09 | 0.550110E+09 | 0.00 | 5941565.56 | 59252500.23 | 16898857.85 | 0.494649E+09 | 0.00 | 0.43 |
October | 0.678340E+09 | 66218928.96 | 0.00 | 7882519.01 | 3553074.54 | 0.103087E+09 | 0.877472E+09 | 0.00 | 0.42 |
November | 0.172303E+10 | 0.00 | 4100.84 | 1756080.05 | 0.00 | 0.110912E+10 | 0.294760E+09 | 1771.59 | 0.38 |
December | 0.154332E+10 | 0.00 | 0.00 | 73515.40 | 0.00 | 0.260099E+10 | 91739655.70 | 0.00 | 0.40 |
Annual Sum or Average | 0.107200E+11 | 0.553182E+10 | 4100.84 | 25707569.77 | 0.943968E+09 | 0.146154E+11 | 0.252722E+10 | 1771.59 | 0.41 |
Minimum of Months | 5770332.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.172303E+10 | 0.212013E+10 | 4100.84 | 7882519.01 | 0.470892E+09 | 0.394115E+10 | 0.877472E+09 | 1771.59 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.850626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266961E+10 | 0.00 | 0.00 | 0.51 |
February | 0.880565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258216E+10 | 0.00 | 0.00 | 0.51 |
March | 0.177962E+10 | 0.00 | 0.00 | 179322.06 | 420284.01 | 0.960461E+09 | 81158149.29 | 0.00 | 0.48 |
April | 0.128227E+10 | 28536.71 | 0.00 | 964025.08 | 936177.18 | 0.293585E+09 | 0.192601E+09 | 0.00 | 0.43 |
May | 0.720548E+09 | 17659283.79 | 0.00 | 1675474.23 | 9716696.17 | 7988548.41 | 0.254772E+09 | 0.00 | 0.43 |
June | 85794197.63 | 0.541067E+09 | 0.00 | 1914829.54 | 0.109859E+09 | 0.00 | 0.133257E+09 | 0.00 | 0.45 |
July | 3618481.11 | 0.145292E+10 | 0.00 | 365679.58 | 0.366977E+09 | 0.00 | 8885593.03 | 0.00 | 0.46 |
August | 39465687.67 | 0.130130E+10 | 0.00 | 2730248.77 | 0.156791E+09 | 0.00 | 99768939.67 | 0.00 | 0.50 |
September | 0.267131E+09 | 0.319024E+09 | 0.00 | 2404356.35 | 46157769.36 | 0.00 | 0.246158E+09 | 0.00 | 0.42 |
October | 0.776911E+09 | 30362567.96 | 0.00 | 2305116.30 | 4734486.34 | 675502.31 | 0.303451E+09 | 0.00 | 0.40 |
November | 0.155816E+10 | 0.00 | 0.00 | 136987.90 | 4584.38 | 0.605101E+09 | 39277292.80 | 0.00 | 0.42 |
December | 0.131731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168442E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.956202E+10 | 0.366236E+10 | 0.00 | 12676039.82 | 0.695596E+09 | 0.880400E+10 | 0.135933E+10 | 0.00 | 0.46 |
Minimum of Months | 3618481.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.177962E+10 | 0.145292E+10 | 0.00 | 2730248.77 | 0.366977E+09 | 0.266961E+10 | 0.303451E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460423E+10 | 0.00 | 0.00 | 0.55 |
February | 0.126433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426015E+10 | 0.00 | 0.00 | 0.54 |
March | 0.309052E+10 | 0.00 | 0.00 | 0.00 | 1294959.15 | 0.144389E+10 | 0.00 | 0.00 | 0.51 |
April | 0.243595E+10 | 36200.97 | 0.00 | 572888.22 | 2170312.36 | 0.307082E+09 | 0.143528E+09 | 0.00 | 0.46 |
May | 0.115296E+10 | 28087850.02 | 0.00 | 2681821.76 | 18418089.78 | 2317392.74 | 0.429141E+09 | 0.00 | 0.47 |
June | 0.145763E+09 | 0.854237E+09 | 0.00 | 2843583.23 | 0.219484E+09 | 0.00 | 0.177125E+09 | 0.00 | 0.46 |
July | 4955006.07 | 0.229431E+10 | 0.00 | 539228.52 | 0.536821E+09 | 0.00 | 13952818.29 | 0.00 | 0.46 |
August | 68981366.59 | 0.178305E+10 | 0.00 | 2935830.25 | 0.247353E+09 | 0.00 | 0.125669E+09 | 0.00 | 0.44 |
September | 0.502525E+09 | 0.425933E+09 | 0.00 | 1946975.60 | 0.142046E+09 | 0.00 | 0.214821E+09 | 0.00 | 0.42 |
October | 0.146659E+10 | 32350033.25 | 0.00 | 911642.73 | 28820558.37 | 33223071.19 | 0.144025E+09 | 0.00 | 0.41 |
November | 0.227525E+10 | 0.00 | 4522.93 | 0.00 | 435861.20 | 0.130222E+10 | 0.00 | 2899.80 | 0.47 |
December | 0.184174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296782E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.153130E+11 | 0.541800E+10 | 4522.93 | 12431970.31 | 0.119684E+10 | 0.149209E+11 | 0.124826E+10 | 2899.80 | 0.47 |
Minimum of Months | 4955006.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.309052E+10 | 0.229431E+10 | 4522.93 | 2935830.25 | 0.536821E+09 | 0.460423E+10 | 0.429141E+09 | 2899.80 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286430E+10 | 0.00 | 0.00 | 0.59 |
February | 0.128905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248207E+10 | 0.00 | 0.00 | 0.58 |
March | 0.207214E+10 | 5683.87 | 0.00 | 440502.05 | 666606.05 | 0.814979E+09 | 0.211204E+09 | 0.00 | 0.55 |
April | 0.146308E+10 | 2089113.89 | 0.00 | 2030911.07 | 0.00 | 0.212550E+09 | 0.434489E+09 | 0.00 | 0.54 |
May | 0.714538E+09 | 30562989.39 | 0.00 | 4163366.58 | 11051867.14 | 1184748.90 | 0.594451E+09 | 0.00 | 0.61 |
June | 87592256.87 | 0.650955E+09 | 0.00 | 3003746.53 | 0.200654E+09 | 0.00 | 0.213688E+09 | 0.00 | 0.60 |
July | 2391144.55 | 0.184964E+10 | 0.00 | 508828.59 | 0.433294E+09 | 0.00 | 16052442.05 | 0.00 | 0.60 |
August | 47729134.68 | 0.150353E+10 | 0.00 | 2904965.53 | 0.204851E+09 | 0.00 | 0.130324E+09 | 0.00 | 0.61 |
September | 0.329670E+09 | 0.314622E+09 | 0.00 | 2839365.33 | 0.135317E+09 | 0.00 | 0.260412E+09 | 0.00 | 0.55 |
October | 0.881599E+09 | 30728229.04 | 0.00 | 2334177.00 | 20641617.00 | 20387114.69 | 0.333479E+09 | 0.00 | 0.51 |
November | 0.158279E+10 | 0.00 | 2969.07 | 222941.00 | 358629.14 | 0.773368E+09 | 72838024.74 | 3138.40 | 0.50 |
December | 0.132839E+10 | 0.00 | 0.00 | 835.30 | 0.00 | 0.190249E+10 | 333524.40 | 0.00 | 0.51 |
Annual Sum or Average | 0.108496E+11 | 0.438214E+10 | 2969.07 | 18449638.99 | 0.100684E+10 | 0.907133E+10 | 0.226727E+10 | 3138.40 | 0.56 |
Minimum of Months | 2391144.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.207214E+10 | 0.184964E+10 | 2969.07 | 4163366.58 | 0.433294E+09 | 0.286430E+10 | 0.594451E+09 | 3138.40 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213111E+10 | 0.00 | 0.00 | 1183665.77 | 0.00 | 0.287719E+10 | 0.627540E+09 | 0.00 | 0.55 |
February | 0.226581E+10 | 0.00 | 0.00 | 1842065.26 | 0.00 | 0.245417E+10 | 0.878166E+09 | 0.00 | 0.55 |
March | 0.271911E+10 | 2113289.89 | 0.00 | 4882848.51 | 15249.95 | 0.806047E+09 | 0.138682E+10 | 0.00 | 0.56 |
April | 0.204265E+10 | 3121100.98 | 0.00 | 4533881.12 | 25046.52 | 0.232875E+09 | 0.824262E+09 | 0.00 | 0.51 |
May | 0.979684E+09 | 35041029.57 | 0.00 | 5468748.52 | 17612103.32 | 4258280.78 | 0.728374E+09 | 0.00 | 0.50 |
June | 0.139321E+09 | 0.962581E+09 | 0.00 | 3542580.76 | 0.219406E+09 | 0.00 | 0.211396E+09 | 0.00 | 0.49 |
July | 5191070.23 | 0.267334E+10 | 0.00 | 651782.62 | 0.470633E+09 | 0.00 | 15011284.52 | 0.00 | 0.50 |
August | 62563791.65 | 0.233758E+10 | 0.00 | 4802799.88 | 0.201288E+09 | 0.00 | 0.190210E+09 | 0.00 | 0.55 |
September | 0.369691E+09 | 0.640085E+09 | 0.00 | 6900341.18 | 97307469.67 | 0.00 | 0.575061E+09 | 0.00 | 0.55 |
October | 0.914923E+09 | 98699803.36 | 0.00 | 9391960.71 | 12938579.87 | 10243415.39 | 0.124007E+10 | 0.00 | 0.58 |
November | 0.210781E+10 | 0.00 | 5192.35 | 4250801.53 | 429172.96 | 0.760555E+09 | 0.952526E+09 | 2116.48 | 0.52 |
December | 0.226788E+10 | 0.00 | 0.00 | 1815286.36 | 0.00 | 0.184293E+10 | 0.799096E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.160057E+11 | 0.675256E+10 | 5192.35 | 49266762.21 | 0.101965E+10 | 0.898827E+10 | 0.842852E+10 | 2116.48 | 0.53 |
Minimum of Months | 5191070.23 | 0.00 | 0.00 | 651782.62 | 0.00 | 0.00 | 15011284.52 | 0.00 | 0.49 |
Maximum of Months | 0.271911E+10 | 0.267334E+10 | 5192.35 | 9391960.71 | 0.470633E+09 | 0.287719E+10 | 0.138682E+10 | 2116.48 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349134E+10 | 0.00 | 0.00 | 0.73 |
February | 0.146954E+10 | 0.00 | 0.00 | 29928.87 | 0.00 | 0.313794E+10 | 72771725.79 | 0.00 | 0.72 |
March | 0.257493E+10 | 26513.93 | 0.00 | 805396.30 | 1076828.29 | 0.953914E+09 | 0.366903E+09 | 0.00 | 0.69 |
April | 0.184921E+10 | 54964.19 | 0.00 | 2078407.94 | 1826755.40 | 0.256747E+09 | 0.461432E+09 | 0.00 | 0.66 |
May | 0.904669E+09 | 26011832.01 | 0.00 | 3354150.23 | 16351766.73 | 4185807.13 | 0.557258E+09 | 0.00 | 0.67 |
June | 0.120523E+09 | 0.762477E+09 | 0.00 | 2537371.32 | 0.176121E+09 | 0.00 | 0.181488E+09 | 0.00 | 0.65 |
July | 4597956.43 | 0.195752E+10 | 0.00 | 456024.13 | 0.482772E+09 | 0.00 | 12881112.97 | 0.00 | 0.63 |
August | 59342043.73 | 0.164316E+10 | 0.00 | 2822471.78 | 0.210624E+09 | 0.00 | 0.127508E+09 | 0.00 | 0.65 |
September | 0.406052E+09 | 0.373504E+09 | 0.00 | 2265990.03 | 0.133886E+09 | 0.00 | 0.253236E+09 | 0.00 | 0.60 |
October | 0.112035E+10 | 40688323.12 | 0.00 | 2003188.36 | 21962936.53 | 25772845.65 | 0.315519E+09 | 0.00 | 0.59 |
November | 0.192266E+10 | 0.00 | 2998.63 | 183859.23 | 371366.20 | 0.106171E+10 | 62966444.28 | 3325.75 | 0.63 |
December | 0.172523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236988E+10 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 0.134689E+11 | 0.480345E+10 | 2998.63 | 16536788.20 | 0.104499E+10 | 0.113015E+11 | 0.241196E+10 | 3325.75 | 0.66 |
Minimum of Months | 4597956.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.257493E+10 | 0.195752E+10 | 2998.63 | 3354150.23 | 0.482772E+09 | 0.349134E+10 | 0.557258E+09 | 3325.75 | 0.73 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.150084E+12 | 0.252509E+11 | 0.00 | 0.147122E+12 | 0.643835E+11 |
February | 0.223437E+12 | 0.233885E+11 | 0.00 | 0.146353E+12 | 0.524151E+11 |
March | 0.348638E+12 | 0.196495E+11 | 0.00 | 0.127103E+12 | 0.547088E+11 |
April | 0.362809E+12 | 0.124332E+11 | 0.00 | 0.864809E+11 | 0.812841E+11 |
May | 0.453843E+12 | 0.651393E+10 | 0.00 | 0.517238E+11 | 0.151501E+12 |
June | 0.434908E+12 | -0.137289E+10 | 0.00 | -0.150037E+11 | 0.266446E+12 |
July | 0.425283E+12 | -0.818730E+10 | 0.00 | -0.766801E+11 | 0.351336E+12 |
August | 0.413494E+12 | -0.486380E+10 | 0.00 | -0.476061E+11 | 0.354250E+12 |
September | 0.297311E+12 | 0.150797E+10 | 0.00 | 0.100793E+11 | 0.216465E+12 |
October | 0.295546E+12 | 0.916253E+10 | 0.00 | 0.600495E+11 | 0.142421E+12 |
November | 0.155668E+12 | 0.183125E+11 | 0.00 | 0.107362E+12 | 0.595543E+11 |
December | 0.122905E+12 | 0.220758E+11 | 0.00 | 0.135480E+12 | 0.439786E+11 |
Annual Sum or Average | 0.368393E+13 | 0.123871E+12 | 0.00 | 0.732463E+12 | 0.183874E+13 |
Minimum of Months | 0.122905E+12 | -0.818730E+10 | 0.00 | -0.766801E+11 | 0.439786E+11 |
Maximum of Months | 0.453843E+12 | 0.252509E+11 | 0.00 | 0.147122E+12 | 0.354250E+12 |