Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:22:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3182.82 | 638.84 | 638.84 |
Net Site Energy | 3182.82 | 638.84 | 638.84 |
Total Source Energy | 7586.52 | 1522.73 | 1522.73 |
Net Source Energy | 7586.52 | 1522.73 | 1522.73 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1197.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 173.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 235.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 59.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1985.77 | 1197.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1197.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 173.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 235.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 187.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 59.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1197.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 173.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 235.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 187.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 6.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 59.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 85.72 | 240.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 398.57 | 240.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 85.72 | 240.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 398.57 | 240.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1985.765 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1985.765 | 100.00 |
Total On-Site and Utility Electric Sources | 1985.765 | 100.00 |
Total Electricity End Uses | 1985.765 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 544.33 |
Time Setpoint Not Met During Occupied Cooling | 31.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3213.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-15:30 | 30-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 419663.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87265.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29290.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4281.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 213634.67 | 419663.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 419663.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 87265.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 29290.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4281.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 549.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 746.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 593.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 189.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6288.92 | 1297.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 260.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 110.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 119.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1262.28 | 260.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 260.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 110.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 119.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1262.28 | 260.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.51 | 0.213824 | 0.300000 | 1.05 | 0.570199 | 0.500000 | 0.001782 | 0.000197 | 1.05 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.87 | 0.260893 | 0.300000 | 0.861794 | 0.695716 | 0.500000 | 0.001460 | 0.000379 | 1.91 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 3.79 | 0.197991 | 0.300000 | 1.14 | 0.527975 | 0.500000 | 0.001924 | 0.000750 | 3.79 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.87 | 0.084404 | 0.300000 | 0.561557 | 0.300000 | 0.500000 | 0.004514 | 0.000370 | 1.87 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.21 | 0.082851 | 0.300000 | 0.362176 | 0.300000 | 0.500000 | 0.004599 | 0.000239 | 1.21 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.84 | 0.085690 | 0.300000 | 0.553124 | 0.300000 | 0.500000 | 0.004446 | 0.000365 | 1.84 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.23 | 0.081611 | 0.300000 | 0.367652 | 0.300000 | 0.500000 | 0.004668 | 0.000242 | 1.23 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.42 | 0.111287 | 0.300000 | 0.425904 | 0.300000 | 0.500000 | 0.003424 | 0.000281 | 1.42 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.916818 | 0.109097 | 0.300000 | 0.275045 | 0.300000 | 0.500000 | 0.003492 | 0.000181 | 0.916818 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.39 | 0.113430 | 0.300000 | 0.417857 | 0.302480 | 0.500000 | 0.003359 | 0.000276 | 1.39 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.934360 | 0.107041 | 0.300000 | 0.280308 | 0.300000 | 0.500000 | 0.003559 | 0.000185 | 0.934360 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 1.46 | 0.108532 | 0.300000 | 0.436714 | 0.300000 | 0.500000 | 0.003510 | 0.000288 | 1.46 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.992996 | 0.300000 | 0.500000 | 0.003782 | 0.000186 | 0.942753 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.43 | 0.110629 | 0.300000 | 0.428435 | 0.300000 | 0.500000 | 0.003444 | 0.000282 | 1.43 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.03 | 0.097050 | 0.300000 | 0.309165 | 0.300000 | 0.500000 | 0.003926 | 0.000190 | 0.960400 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 22556.89 | 0.000197 | 519.41 |
CORE_MID VAV BOX REHEAT COIL | 43366.52 | 0.000379 | 1014.12 |
CORE_TOP VAV BOX REHEAT COIL | 85733.91 | 0.000750 | 2003.10 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 42308.54 | 0.000370 | 987.94 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 27286.08 | 0.000239 | 637.15 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 41673.92 | 0.000365 | 973.12 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 27698.25 | 0.000242 | 646.77 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 32101.11 | 0.000281 | 749.67 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 20729.90 | 0.000181 | 484.11 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 31495.58 | 0.000276 | 735.53 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 21125.93 | 0.000185 | 493.35 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 32913.52 | 0.000288 | 768.63 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 21314.60 | 0.000186 | 497.75 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 32290.47 | 0.000282 | 754.08 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 21713.00 | 0.000190 | 507.05 |
PACU_VAV_BOT HEATING COIL | 38201.01 | 0.000334 | 621.68 |
PACU_VAV_MID HEATING COIL | 36344.73 | 0.000318 | 600.28 |
PACU_VAV_TOP HEATING COIL | 31977.88 | 0.000280 | 549.46 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 4.08 | 2.45 | 8.17 | 5.60 | 6.03 | 6.03 | 0.300000 | 0.928463 | 6.03 |
PACU_VAV_MID | 3.89 | 2.33 | 7.78 | 6.70 | 5.77 | 6.70 | 0.300000 | 1.00 | 6.70 |
PACU_VAV_TOP | 4.97 | 2.98 | 9.93 | 9.93 | 7.06 | 9.93 | 0.300000 | 1.00 | 9.93 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.03 |
PACU_VAV_MID_OA_CONTROLLER | 6.70 |
PACU_VAV_TOP_OA_CONTROLLER | 9.93 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.03 | 120329.27 | 0.777211 | 2.01 | 40105.75 | 0.777211 |
PACU_VAV_MID COOLING COIL | 6.70 | 135637.68 | 0.771430 | 2.23 | 45208.04 | 0.771430 |
PACU_VAV_TOP COOLING COIL | 9.93 | 193058.66 | 0.788150 | 3.31 | 64346.45 | 0.788150 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.03 |
PACU_VAV_MID FAN | 6.70 |
PACU_VAV_TOP FAN | 9.93 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000334 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000318 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000280 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.005344 | 0.641259 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.005344 | 1609.32 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 610831.85 | 610831.85 | 0.005344 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
43 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
44 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
45 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
46 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
47 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
48 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
49 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40024.30615 | 46027.95207 | 3.04783 | 3.50500 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10054.37919 | 12567.97399 | 0.75126 | 0.93907 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32828.42558 | 37752.68941 | 2.49795 | 2.87265 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 20187.94292 | 25234.92865 | 1.52692 | 1.90865 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 36906.31971 | 42442.26767 | 2.83379 | 3.25885 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 39819.74808 | 49774.68509 | 3.02825 | 3.78531 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10785.42379 | 12403.23736 | 0.82826 | 0.95249 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 19631.32218 | 24539.15272 | 1.49748 | 1.87186 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11366.86344 | 13071.89296 | 0.87290 | 1.00384 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53554E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 12660.81224 | 15826.01530 | 0.96580 | 1.20725 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14851.64801 | 17079.39521 | 1.14051 | 1.31158 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 19337.18530 | 24171.48162 | 1.47500 | 1.84375 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12810.20988 | 14731.74136 | 0.98374 | 1.13130 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 12851.84915 | 16064.81144 | 0.98041 | 1.22551 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7687.10103 | 8840.16618 | 0.59029 | 0.67883 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 14896.71586 | 18620.89483 | 1.13574 | 1.41968 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9169.77848 | 10545.24526 | 0.70413 | 0.80975 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 26.27100 | 1.53560E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 9619.69289 | 12024.61611 | 0.73345 | 0.91682 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11218.30565 | 12901.05150 | 0.86144 | 0.99066 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 14616.10854 | 18270.13567 | 1.11429 | 1.39286 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9789.92341 | 11258.41192 | 0.75175 | 0.86452 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.65600 | 1.53604E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 9803.21770 | 12254.02212 | 0.74749 | 0.93436 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8895.83887 | 10230.21470 | 0.68313 | 0.78560 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 15275.59726 | 19094.49657 | 1.16457 | 1.45571 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11244.38371 | 12931.04127 | 0.86347 | 0.99300 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53537E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 9892.24616 | 12365.30770 | 0.75420 | 0.94275 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 13078.97525 | 15040.82154 | 1.00436 | 1.15501 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 14986.85450 | 18733.56812 | 1.14249 | 1.42812 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11669.63596 | 13420.08136 | 0.89613 | 1.03055 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 10076.87978 | 12596.09973 | 0.76832 | 0.96040 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 85317.12 | 6.03447 | 6.03447 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 42707.13 | 5.60278 | 5.60278 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 81799.06 | 5.76551 | 5.76551 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 42901.50 | 6.69564 | 6.69564 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 98367.60 | 7.06107 | 7.06107 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 40249.52 | 9.93367 | 9.93367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.50500 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21382 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.05150 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57020 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78184E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97338E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.05150 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22556.89428 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97338E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 519.41007 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.87265 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26089 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.86179 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69572 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46037E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.79389E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.90865 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 43366.51967 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.79389E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1014.11603 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.78531 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19799 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.13559 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52797 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92433E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.50038E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.78531 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 85733.90531 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.50038E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2003.09918 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.87186 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.44038E-002 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.56156 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.51402E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.70134E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.87186 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 42308.54082 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.70134E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 987.93720 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20725 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.28508E-002 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36218 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.59863E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.38711E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20725 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27286.08292 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.38711E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 637.14608 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.84375 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.56905E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55312 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.44623E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.64582E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.84375 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 41673.92140 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.64582E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 973.12274 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.22551 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.16113E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36765 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.66847E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.42316E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22551 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27698.25077 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.42316E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 646.76770 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41968 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11129 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42590 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.42358E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.80835E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.41968 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32101.11305 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.80835E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 749.66914 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91682 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10910 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27505 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49232E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.81354E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.91682 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20729.89904 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.81354E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 484.10810 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39286 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11343 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41786 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30248 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35890E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.75537E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.39286 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31495.58090 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.75537E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 735.53421 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93436 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10704 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28031 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.55937E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.84819E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.93436 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21125.92930 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84819E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 493.35265 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45571 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10853 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43671 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.51049E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.87942E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.45571 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32913.51742 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.87942E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 768.62586 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99300 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.78249E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86469E-004 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.94275 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21314.60471 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86469E-004 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 497.75180 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.42812 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11063 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42844 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44393E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.82491E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.42812 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32290.47195 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.82491E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 754.08207 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03055 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.70504E-002 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30916 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.92580E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.89955E-004 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.96040 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21713.00114 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89955E-004 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 507.05160 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.08436 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.45061 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.16871 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.60278 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.03447 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.03447 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.92846 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.89001 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.33401 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.78002 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 6.69564 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.76551 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 6.69564 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.96683 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.98010 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.93367 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 9.93367 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.06107 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 9.93367 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.03447 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 6.69564 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 9.93367 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.03447 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.03447 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 120329.26863 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77721 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.01129 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 40105.74523 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77721 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 38201.00570 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.34199E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 621.67531 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.03447 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.34199E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.69564 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.69564 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 135637.67794 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77143 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.23166 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 45208.03806 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77143 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 36344.73302 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.17960E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 600.27656 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 6.69564 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.17960E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.93367 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 9.93367 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 193058.65914 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78815 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 3.31089 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 64346.45109 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78815 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 31977.88133 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.79756E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 549.46167 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 9.93367 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.79756E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.34382E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.64126 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.34382E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1609.32497 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 610831.85274 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 610831.85000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.34382E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 21401.86 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 41143.17 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 81338.73 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 40139.68 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 25887.32 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 39537.59 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 26278.36 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 30455.50 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 19667.21 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 29881.01 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 20042.94 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 31226.26 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 20221.95 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 30635.15 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 20599.92 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 28690.89 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 28135.95 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 26767.21 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 119213.43 | 406773.12 | 11.58 | 2.96 | 3.32 | 3.49 | 3.67 | 10.10 | 11.31 | 11.91 | 12.52 | 6.6572 | 5.3180 | 3.5813 | 1.4397 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 134462.28 | 458804.33 | 11.61 | 2.97 | 3.33 | 3.50 | 3.68 | 10.12 | 11.35 | 11.94 | 12.55 | 7.3866 | 5.9013 | 3.9751 | 1.6042 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 191073.64 | 651970.32 | 11.52 | 2.95 | 3.30 | 3.47 | 3.66 | 10.06 | 11.25 | 11.84 | 12.49 | 10.9588 | 8.7699 | 5.9094 | 2.3483 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.3631237449E-002 | 4.6060456528E-002 | Pass | Pass | 0.4899414694 | 0.4910099912 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2714732900 | 0.1890414141 | Pass | Pass | 0.4981076352 | 0.4821572951 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.0306421082E-002 | 5.4296991725E-002 | Pass | Pass | 0.5013113837 | 0.4731067820 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7433043233E-002 | 4.8619281189E-002 | Pass | Pass | 0.5061453416 | 0.4714410721 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 9.8550738376E-003 | 7.6368389651E-003 | Pass | Pass | 0.4948073157 | 0.4905051303 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1071097502 | 0.1142704900 | Pass | Pass | 3.4251908556 | 18.2789480603 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5111388920 | 0.5144306030 | Pass | Pass | 1.0142728337 | 2.5691366912 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5188552191 | 0.5280108816 | Pass | Pass | 1.2651722112 | 6.2051355536 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4716563007 | 0.4933967240 | Pass | Pass | 1.4276725029 | 8.1555314095 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5184837227 | 0.5226186932 | Pass | Pass | 0.9444772884 | 2.3163292759 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3939016589 | 0.3925645808 | Pass | Pass | 2.4598109969 | 11.9798821599 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4010377968 | 0.4038495128 | Pass | Pass | 1.9588017235 | 8.6436863219 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3485320931 | 0.3632534920 | Pass | Pass | 1.9988522305 | 9.0733180183 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4025140042 | 0.4016308161 | Pass | Pass | 2.5277881097 | 12.5459528747 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3767877478 | 0.3813296263 | Pass | Pass | 1.4985364225 | 8.0604948867 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3855477577 | 0.3958376029 | Pass | Pass | 1.2497316922 | 5.8019094589 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3384653457 | 0.3625524245 | Pass | Pass | 1.0621061484 | 3.5152150037 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3849238609 | 0.3900948841 | Pass | Pass | 1.4813469477 | 8.3721108116 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3742.28 | 221.29 | 0.00 | 2184.77 | 1297.09 | 7445.42 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 183.92 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 429.15 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.63 | 83.63 | 235.68 | |
Exterior Lighting Total | 15013.15 | 235.68 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 610831.85 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 120329.27 | 93521.20 | 26808.07 | 0.78 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 135637.68 | 104634.99 | 31002.69 | 0.77 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 193058.66 | 152159.17 | 40899.49 | 0.79 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 119213.4 | 2.96 | 10.10 | N/A | N/A | 11.58 | |
PACU_VAV_MID COOLING COIL | 134462.3 | 2.97 | 10.12 | N/A | N/A | 11.61 | |
PACU_VAV_TOP COOLING COIL | 191073.6 | 2.95 | 10.06 | N/A | N/A | 11.52 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 22556.89 | 21401.86 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 43366.52 | 41143.17 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 85733.91 | 81338.73 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 42308.54 | 40139.68 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 27286.08 | 25887.32 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 41673.92 | 39537.59 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 27698.25 | 26278.36 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 32101.11 | 30455.50 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 20729.90 | 19667.21 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31495.58 | 29881.01 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 21125.93 | 20042.94 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 32913.52 | 31226.26 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 21314.60 | 20221.95 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 32290.47 | 30635.15 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 21713.00 | 20599.92 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 38201.01 | 28690.89 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 36344.73 | 28135.95 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 31977.88 | 26767.21 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1337.13 | 6.03 | 13348.01 | 2211.96 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.70 | 14715.54 | 2197.78 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 9.93 | 21716.02 | 2186.10 | 1.00 | 1.12 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.005344 | 1609.32 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 119213.43 | 2.96 | 10.10 | 11.58 | 6.6572 | 3.32 | 11.31 | 5.3180 | 3.49 | 11.91 | 3.5813 | 3.67 | 12.52 | 1.4397 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 134462.28 | 2.97 | 10.12 | 11.61 | 7.3866 | 3.33 | 11.35 | 5.9013 | 3.50 | 11.94 | 3.9751 | 3.68 | 12.55 | 1.6042 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 191073.64 | 2.95 | 10.06 | 11.52 | 10.9588 | 3.30 | 11.25 | 8.7699 | 3.47 | 11.84 | 5.9094 | 3.66 | 12.49 | 2.3483 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40024.31 | 46027.95 | 46.80 | 3.048 | 3.505 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_MID | 32828.43 | 37752.69 | 38.38 | 2.498 | 2.873 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_TOP | 36906.32 | 42442.27 | 43.15 | 2.834 | 3.259 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00882 | 31.20 | 0.01537 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10785.42 | 12403.24 | 59.82 | 0.828 | 0.952 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00910 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11366.86 | 13071.89 | 99.59 | 0.873 | 1.004 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00888 | 25.97 | 0.01536 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14851.65 | 17079.40 | 82.37 | 1.141 | 1.312 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00894 | 31.02 | 0.01536 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12810.21 | 14731.74 | 112.24 | 0.984 | 1.131 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00884 | 29.54 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7687.10 | 8840.17 | 42.64 | 0.590 | 0.679 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00910 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9169.78 | 10545.25 | 80.34 | 0.704 | 0.810 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00883 | 26.27 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11218.31 | 12901.05 | 62.22 | 0.861 | 0.991 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00892 | 31.02 | 0.01536 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9789.92 | 11258.41 | 85.78 | 0.752 | 0.865 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00881 | 28.66 | 0.01536 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8895.84 | 10230.21 | 49.34 | 0.683 | 0.786 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00915 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11244.38 | 12931.04 | 98.51 | 0.863 | 0.993 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00885 | 25.03 | 0.01535 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13078.98 | 15040.82 | 72.54 | 1.004 | 1.155 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00895 | 30.85 | 0.01536 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11669.64 | 13420.08 | 102.25 | 0.896 | 1.031 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00883 | 29.54 | 0.01536 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10054.38 | 12567.97 | 12.78 | 0.751 | 0.939 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_MID | 20187.94 | 25234.93 | 25.66 | 1.527 | 1.909 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_TOP | 39819.75 | 49774.69 | 50.61 | 3.028 | 3.785 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 19631.32 | 24539.15 | 118.35 | 1.497 | 1.872 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 12660.81 | 15826.02 | 120.57 | 0.966 | 1.207 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 19337.19 | 24171.48 | 116.58 | 1.475 | 1.844 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12851.85 | 16064.81 | 122.40 | 0.980 | 1.226 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 14896.72 | 18620.89 | 89.81 | 1.136 | 1.420 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9619.69 | 12024.62 | 91.61 | 0.733 | 0.917 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 14616.11 | 18270.14 | 88.12 | 1.114 | 1.393 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9803.22 | 12254.02 | 93.36 | 0.747 | 0.934 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 15275.60 | 19094.50 | 92.09 | 1.165 | 1.456 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9892.25 | 12365.31 | 94.20 | 0.754 | 0.943 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14986.85 | 18733.57 | 90.35 | 1.142 | 1.428 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10076.88 | 12596.10 | 95.97 | 0.768 | 0.960 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -26.20 | 0.00036 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.03 | 6.03 | 5.60 | 5.60 | 6.0345 | 5.6028 | 6.0345 | 0.9285 | 0.3000 |
PACU_VAV_MID | 5.77 | 5.77 | 6.70 | 6.70 | 5.7655 | 6.6956 | 6.6956 | 1.0000 | 0.3000 |
PACU_VAV_TOP | 7.06 | 7.06 | 9.93 | 9.93 | 7.0611 | 9.9337 | 9.9337 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 22556.894 | 22556.894 | 1.051500 | 0.00019734 | 519.410 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22556.89 | 22556.89 | 1.051500 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 12567.97 | 0.00 | 22660.94 | 22660.94 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 43366.520 | 43366.520 | 1.908652 | 0.00037939 | 1014.116 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 43366.52 | 43366.52 | 1.908652 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 25234.93 | 0.00 | 43565.25 | 43565.25 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 85733.905 | 85733.905 | 3.785306 | 0.00075004 | 2003.099 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 85733.91 | 85218.44 | 3.785306 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3290 | 49774.69 | 0.00 | 86126.93 | 86126.93 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 42308.541 | 42308.541 | 1.871855 | 0.00037013 | 987.937 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 42308.54 | 42141.00 | 1.871855 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00773939 | 47.7474 | 24539.15 | 0.00 | 42502.54 | 42502.54 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 27286.083 | 27286.083 | 1.207252 | 0.00023871 | 637.146 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27286.08 | 27178.81 | 1.207252 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00773080 | 47.6952 | 15826.02 | 0.00 | 27411.20 | 27411.20 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 41673.921 | 41673.921 | 1.843748 | 0.00036458 | 973.123 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 41673.92 | 41508.22 | 1.843748 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00773555 | 47.7239 | 24171.48 | 0.00 | 41865.01 | 41865.01 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 27698.251 | 27698.251 | 1.225507 | 0.00024232 | 646.768 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27698.25 | 27589.78 | 1.225507 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00773468 | 47.7189 | 16064.81 | 0.00 | 27825.26 | 27825.26 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 32101.113 | 32101.113 | 1.419679 | 0.00028083 | 749.669 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32101.11 | 31961.18 | 1.419679 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00781734 | 48.2198 | 18620.89 | 0.00 | 32248.30 | 32248.30 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 20729.899 | 20729.899 | 0.916818 | 0.00018135 | 484.108 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20729.90 | 20640.29 | 0.916818 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00781146 | 48.1841 | 12024.62 | 0.00 | 20824.95 | 20824.95 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 31495.581 | 31495.581 | 1.392857 | 0.00027554 | 735.534 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31495.58 | 31357.32 | 1.392857 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00781394 | 48.1991 | 18270.14 | 0.00 | 31639.99 | 31639.99 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 21125.929 | 21125.929 | 0.934360 | 0.00018482 | 493.353 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21125.93 | 21035.22 | 0.934360 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00781488 | 48.2050 | 12254.02 | 0.00 | 21222.80 | 21222.80 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 32913.517 | 32913.517 | 1.455715 | 0.00028794 | 768.626 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32913.52 | 32772.45 | 1.455715 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00772310 | 47.6474 | 19094.50 | 0.00 | 33064.43 | 33064.43 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 21314.605 | 21314.605 | 0.942753 | 0.00018647 | 497.752 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21314.60 | 21314.60 | 0.942753 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00771507 | 47.5986 | 12365.31 | 0.00 | 21412.34 | 21412.34 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 32290.472 | 32290.472 | 1.428117 | 0.00028249 | 754.082 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32290.47 | 32151.13 | 1.428117 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00771798 | 47.6161 | 18733.57 | 0.00 | 32438.53 | 32438.53 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 21713.001 | 21713.001 | 0.960400 | 0.00018995 | 507.052 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21713.00 | 21713.00 | 0.960400 | 12.89 | 11.21 | 0.00800000 | 32.11 | 18.22 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00772009 | 47.6292 | 12596.10 | 0.00 | 21812.56 | 21812.56 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 120329.269 | 93521.200 | 6.034470 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 121471.90 | 97250.69 | 6.034470 | 25.14 | 17.47 | 0.00992220 | 11.01 | 10.94 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 15.8440 | 24.00 | 0.00889743 | 45.6594 | 68335.23 | 0.00 | 124075.63 | 92716.41 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 38201.006 | 38201.006 | 1.810341 | 0.00033420 | 621.675 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38201.01 | 38201.01 | 1.810341 | -5.39 | -5.39 | 0.00375507 | 12.89 | 11.21 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 52.8133 | 18.52 | 0.00777073 | 55.9143 | 9344.12 | 0.00 | 34714.44 | 34714.44 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 135637.678 | 104634.990 | 6.695636 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 137220.03 | 108211.17 | 6.695636 | 25.19 | 17.57 | 0.01003653 | 11.02 | 10.94 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 14.2794 | 24.00 | 0.00897602 | 46.0579 | 65227.66 | 0.00 | 139860.65 | 103798.75 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 36344.733 | 36344.733 | 2.008691 | 0.00031796 | 600.277 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36344.73 | 36344.73 | 2.008691 | -2.79 | -2.79 | 0.00405647 | 12.89 | 11.21 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 47.5982 | 17.90 | 0.00774011 | 57.9117 | 8758.42 | 0.00 | 34047.93 | 34047.93 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 193058.659 | 152159.170 | 9.933669 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 194293.60 | 158119.89 | 9.933669 | 24.97 | 17.31 | 0.00979139 | 11.03 | 10.95 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 9.6248 | 24.00 | 0.00891724 | 45.7608 | 79861.30 | 0.00 | 199069.39 | 150743.72 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 31977.881 | 31977.881 | 2.980101 | 0.00027976 | 549.462 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31977.88 | 31977.88 | 2.980101 | 3.59 | 3.56 | 0.00510733 | 12.89 | 11.21 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 32.0828 | 16.17 | 0.00772791 | 64.5030 | 16303.73 | 0.00 | 32401.84 | 32401.84 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 22556.894 | 22556.894 | 1.051500 | 0.00019734 | 519.410 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 3.6200 | 3.692816 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22556.89 | 22556.89 | 1.0000 | 1.20770658 | 1.051500 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.19731742 | 60.00 | 32.22 | 27.78 | 0.000 | 22556.89 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 12567.97 | 0.00 | 22660.94 | 22660.94 | 1.20770658 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.20 | 18.44 | 0.00800000 | 51823.4 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 43366.520 | 43366.520 | 1.908652 | 0.00037939 | 1014.116 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 6.9595 | 7.099584 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 43366.52 | 43366.52 | 1.0000 | 2.19219306 | 1.908652 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.37935053 | 60.00 | 32.22 | 27.78 | 0.000 | 43366.52 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 25234.93 | 0.00 | 43565.25 | 43565.25 | 2.19219306 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.29 | 18.79 | 0.00800000 | 52932.7 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 85733.905 | 85733.905 | 3.785306 | 0.00075004 | 2003.099 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 13.7587 | 14.035598 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 85733.91 | 85218.44 | 1.0000 | 4.34763574 | 3.785306 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.74996109 | 60.00 | 32.22 | 27.78 | 0.000 | 85733.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.3290 | 49774.69 | 0.00 | 86126.93 | 86126.93 | 4.34763574 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52869.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 42308.541 | 42308.541 | 1.871855 | 0.00037013 | 987.937 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 6.7897 | 6.926381 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 42308.54 | 42141.00 | 1.0000 | 2.14993040 | 1.871855 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.37009581 | 60.00 | 32.22 | 27.78 | 0.000 | 42308.54 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00773939 | 21.00 | 0.00773939 | 47.7474 | 24539.15 | 0.00 | 42502.54 | 42502.54 | 2.14993040 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.1 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27286.083 | 27286.083 | 1.207252 | 0.00023871 | 637.146 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 4.3789 | 4.467037 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27286.08 | 27178.81 | 1.0000 | 1.38659636 | 1.207252 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.23868621 | 60.00 | 32.22 | 27.78 | 0.000 | 27286.08 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00773080 | 21.00 | 0.00773080 | 47.6952 | 15826.02 | 0.00 | 27411.20 | 27411.20 | 1.38659636 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52828.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 41673.921 | 41673.921 | 1.843748 | 0.00036458 | 973.123 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 6.6879 | 6.822487 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 41673.92 | 41508.22 | 1.0000 | 2.11764733 | 1.843748 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.36454445 | 60.00 | 32.22 | 27.78 | 0.000 | 41673.92 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00773555 | 21.00 | 0.00773555 | 47.7239 | 24171.48 | 0.00 | 41865.01 | 41865.01 | 2.11764733 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52829.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27698.251 | 27698.251 | 1.225507 | 0.00024232 | 646.768 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 4.4451 | 4.534513 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27698.25 | 27589.78 | 1.0000 | 1.40756307 | 1.225507 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.24229166 | 60.00 | 32.22 | 27.78 | 0.000 | 27698.25 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00773468 | 21.00 | 0.00773468 | 47.7189 | 16064.81 | 0.00 | 27825.26 | 27825.26 | 1.40756307 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52828.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32101.113 | 32101.113 | 1.419679 | 0.00028083 | 749.669 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 5.1516 | 5.255311 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32101.11 | 31961.18 | 1.0000 | 1.63058085 | 1.419679 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.28080589 | 60.00 | 32.22 | 27.78 | 0.000 | 32101.11 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00781734 | 21.00 | 0.00781734 | 48.2198 | 18620.89 | 0.00 | 32248.30 | 32248.30 | 1.63058085 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52837.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20729.899 | 20729.899 | 0.916818 | 0.00018135 | 484.108 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 3.3268 | 3.393716 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20729.90 | 20640.29 | 1.0000 | 1.05301666 | 0.916818 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.18133570 | 60.00 | 32.22 | 27.78 | 0.000 | 20729.90 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00781146 | 21.00 | 0.00781146 | 48.1841 | 12024.62 | 0.00 | 20824.95 | 20824.95 | 1.05301666 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52836.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31495.581 | 31495.581 | 1.392857 | 0.00027554 | 735.534 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 5.0545 | 5.156179 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31495.58 | 31357.32 | 1.0000 | 1.59977345 | 1.392857 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.27550897 | 60.00 | 32.22 | 27.78 | 0.000 | 31495.58 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00781394 | 21.00 | 0.00781394 | 48.1991 | 18270.14 | 0.00 | 31639.99 | 31639.99 | 1.59977345 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21125.929 | 21125.929 | 0.934360 | 0.00018482 | 493.353 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 3.3903 | 3.458551 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21125.93 | 21035.22 | 1.0000 | 1.07316514 | 0.934360 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.18479999 | 60.00 | 32.22 | 27.78 | 0.000 | 21125.93 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00781488 | 21.00 | 0.00781488 | 48.2050 | 12254.02 | 0.00 | 21222.80 | 21222.80 | 1.07316514 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32913.517 | 32913.517 | 1.455715 | 0.00028794 | 768.626 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 5.2820 | 5.388311 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32913.52 | 32772.45 | 1.0000 | 1.67196994 | 1.455715 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.28791244 | 60.00 | 32.22 | 27.78 | 0.000 | 32913.52 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00772310 | 21.00 | 0.00772310 | 47.6474 | 19094.50 | 0.00 | 33064.43 | 33064.43 | 1.67196994 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52835.6 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21314.605 | 21314.605 | 0.942753 | 0.00018647 | 497.752 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 3.4206 | 3.489439 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21314.60 | 21314.60 | 1.0000 | 1.08280434 | 0.942753 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.18645044 | 60.00 | 32.22 | 27.78 | 0.000 | 21314.60 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00771507 | 21.00 | 0.00771507 | 47.5986 | 12365.31 | 0.00 | 21412.34 | 21412.34 | 1.08280434 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32290.472 | 32290.472 | 1.428117 | 0.00028249 | 754.082 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 5.1820 | 5.286311 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32290.47 | 32151.13 | 1.0000 | 1.64027188 | 1.428117 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.28246232 | 60.00 | 32.22 | 27.78 | 0.000 | 32290.47 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00771798 | 21.00 | 0.00771798 | 47.6161 | 18733.57 | 0.00 | 32438.53 | 32438.53 | 1.64027188 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52836.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21713.001 | 21713.001 | 0.960400 | 0.00018995 | 507.052 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 3.4845 | 3.554661 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21713.00 | 21713.00 | 1.0000 | 1.10307309 | 0.960400 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 32.11 | 18.22 | 0.00800000 | 52751.6 | 0.18993543 | 60.00 | 32.22 | 27.78 | 0.000 | 21713.00 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00772009 | 21.00 | 0.00772009 | 47.6292 | 12596.10 | 0.00 | 21812.56 | 21812.56 | 1.10307309 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52834.2 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 120329.269 | 93521.200 | 6.034470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2849 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.034470 | 6.93092582 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 121471.90 | 97250.69 | 1.0095 | 6.93092582 | 6.034470 | 25.14 | 17.47 | 0.00992220 | 50539.6 | 11.01 | 10.94 | 0.00850000 | 32492.0 | -999.0 | -999.00 | -999.00 | -999.00 | 13348.008 | 108123.89 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 15.8440 | 24.00 | 0.00889743 | 24.00 | 0.00889743 | 45.6594 | 68335.23 | 0.00 | 124075.63 | 92716.41 | 6.65720664 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.04 | 13.02 | 0.00933775 | 36684.6 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 38201.006 | 38201.006 | 1.810341 | 0.00033420 | 621.675 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.034470 | 6.93092582 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 6.1306 | 6.253932 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38201.01 | 38201.01 | 1.0000 | 2.07927775 | 1.810341 | -5.39 | -5.39 | 0.00375507 | 3932.9 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 0.33416497 | 60.00 | 32.22 | 27.78 | 0.000 | 38201.01 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 52.8133 | 17.89 | 0.00755346 | 18.52 | 0.00777073 | 55.9143 | 9344.12 | 0.00 | 34714.44 | 34714.44 | 2.07927775 | 2.80 | 1.60 | 0.00375507 | 12224.3 | 19.30 | 9.92 | 0.00375507 | 28919.7 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 135637.678 | 104634.990 | 6.695636 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4974 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.695636 | 7.69031231 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 137220.03 | 108211.17 | 1.0117 | 7.69031231 | 6.695636 | 25.19 | 17.57 | 0.01003653 | 50886.2 | 11.02 | 10.94 | 0.00850000 | 32504.8 | -999.0 | -999.00 | -999.00 | -999.00 | 14715.543 | 122504.48 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 14.2794 | 24.00 | 0.00897602 | 24.00 | 0.00897602 | 46.0579 | 65227.66 | 0.00 | 139860.65 | 103798.75 | 7.38660311 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.92 | 12.91 | 0.00927051 | 36388.0 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 36344.733 | 36344.733 | 2.008691 | 0.00031796 | 600.277 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.695636 | 7.69031231 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 5.8327 | 5.950039 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36344.73 | 36344.73 | 1.0000 | 2.30709369 | 2.008691 | -2.79 | -2.79 | 0.00405647 | 7322.1 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 0.31792714 | 60.00 | 32.22 | 27.78 | 0.000 | 36344.73 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 47.5982 | 18.48 | 0.00741286 | 17.90 | 0.00774011 | 57.9117 | 8758.42 | 0.00 | 34047.93 | 34047.93 | 2.30709369 | 2.80 | 2.02 | 0.00405647 | 12979.7 | 17.38 | 9.39 | 0.00405647 | 27737.6 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 193058.659 | 152159.170 | 9.933669 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0417 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 9.933669 | 11.40937290 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 194293.60 | 158119.89 | 1.0064 | 11.40937290 | 9.933669 | 24.97 | 17.31 | 0.00979139 | 50037.4 | 11.03 | 10.95 | 0.00850000 | 32514.0 | -999.0 | -999.00 | -999.00 | -999.00 | 21716.024 | 172577.57 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 9.6248 | 24.00 | 0.00891724 | 24.00 | 0.00891724 | 45.7608 | 79861.30 | 0.00 | 199069.39 | 150743.72 | 10.95878891 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.21 | 13.20 | 0.00945569 | 37157.1 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 31977.881 | 31977.881 | 2.980101 | 0.00027976 | 549.462 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 9.933669 | 11.40937290 | 4197.9300 | 999.8980 | 5.34327839 | 54.44 | 82.22 | 27.78 | 623125.09 | 5.1319 | 5.235137 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31977.88 | 31977.88 | 1.0000 | 3.42281187 | 2.980101 | 3.59 | 3.56 | 0.00510733 | 16416.1 | 12.89 | 11.21 | 0.00800000 | 33150.5 | 0.27972792 | 60.00 | 32.22 | 27.78 | 0.000 | 31977.88 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 32.0828 | 17.66 | 0.00734925 | 16.17 | 0.00772791 | 64.5030 | 16303.73 | 0.00 | 32401.84 | 32401.84 | 3.42281187 | 2.80 | 2.80 | 0.00510733 | 15613.3 | 12.13 | 8.16 | 0.00510733 | 25079.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.03 | - | |||
PACU_VAV_MID_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.70 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | FixedDryBulb | 0.00 | 9.93 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2512.00 | 3073.33 | 423.83 |
CORE_MID | 2733.00 | 3900.17 | 1242.50 |
CORE_TOP | 3119.83 | 4454.50 | 2078.50 |
PERIMETER_TOP_ZN_3 | 3421.83 | 5102.17 | 2829.50 |
PERIMETER_TOP_ZN_2 | 3669.33 | 4660.33 | 2606.33 |
PERIMETER_TOP_ZN_1 | 3300.67 | 4661.33 | 2312.83 |
PERIMETER_TOP_ZN_4 | 3577.17 | 4809.33 | 2673.17 |
PERIMETER_BOT_ZN_3 | 3283.83 | 5130.67 | 2757.83 |
PERIMETER_BOT_ZN_2 | 3699.67 | 4488.67 | 2503.17 |
PERIMETER_BOT_ZN_1 | 3330.33 | 4688.33 | 2357.17 |
PERIMETER_BOT_ZN_4 | 3633.67 | 4580.67 | 2526.33 |
PERIMETER_MID_ZN_3 | 3354.50 | 4739.50 | 2477.00 |
PERIMETER_MID_ZN_2 | 3042.00 | 3738.17 | 2018.00 |
PERIMETER_MID_ZN_1 | 3245.17 | 4221.00 | 1950.50 |
PERIMETER_MID_ZN_4 | 3472.50 | 4498.00 | 2350.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5208.83 | 5386.83 | 3213.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.67 | 0.00 | 1.67 | 0.00 |
CORE_MID | 9.00 | 0.00 | 8.17 | 0.00 |
CORE_TOP | 17.67 | 0.00 | 11.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 244.33 | 0.00 | 78.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 242.83 | 4.17 | 71.33 | 4.17 |
PERIMETER_TOP_ZN_1 | 202.17 | 2.33 | 52.50 | 2.33 |
PERIMETER_TOP_ZN_4 | 243.50 | 11.67 | 75.17 | 7.50 |
PERIMETER_BOT_ZN_3 | 133.00 | 0.00 | 52.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 122.33 | 0.67 | 39.17 | 0.67 |
PERIMETER_BOT_ZN_1 | 526.67 | 0.83 | 468.67 | 0.83 |
PERIMETER_BOT_ZN_4 | 127.83 | 3.67 | 46.00 | 1.83 |
PERIMETER_MID_ZN_3 | 146.17 | 0.00 | 52.33 | 0.00 |
PERIMETER_MID_ZN_2 | 136.50 | 6.33 | 39.33 | 6.33 |
PERIMETER_MID_ZN_1 | 113.33 | 3.00 | 29.00 | 3.00 |
PERIMETER_MID_ZN_4 | 142.50 | 12.00 | 46.00 | 7.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 801.83 | 40.50 | 544.33 | 31.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.762 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.548 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.590 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 1.325 | 0.122 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.407 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 1.346 | 0.123 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.426 | 0.129 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 1.092 | 0.065 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 1.166 | 0.069 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 1.151 | 0.887 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 1.172 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 1.167 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 1.296 | 0.114 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 1.224 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.372 | 0.108 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.67 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 12110888.55 | 0.00 | 12110888.55 | 0.00 | 12110888.55 | 13393058.27 | 6494.30 | 95.12 | 2170.58 | 331.35 |
CORE_MID | 8718629.38 | 0.00 | 8718629.38 | 0.00 | 8718629.38 | 13393058.27 | 7063.20 | 32.02 | 1664.78 | 362.06 |
CORE_TOP | 9322430.01 | 0.00 | 9322430.01 | 0.00 | 9322430.01 | 13393058.27 | 6891.06 | 19.10 | 1849.84 | 49.89 |
PERIMETER_TOP_ZN_3 | 4433535.62 | 0.00 | 4433535.62 | 834711.09 | 5268246.72 | 2823374.22 | 4216.31 | 4.49 | 4539.20 | 49.89 |
PERIMETER_TOP_ZN_2 | 2974415.29 | 0.00 | 2974415.29 | 556470.72 | 3530886.01 | 1787429.43 | 4211.94 | 1.83 | 4546.24 | 49.89 |
PERIMETER_TOP_ZN_1 | 4494554.88 | 0.00 | 4494554.88 | 834711.09 | 5329265.98 | 2823374.22 | 4214.58 | 1.56 | 4543.87 | 49.89 |
PERIMETER_TOP_ZN_4 | 3015082.29 | 0.00 | 3015082.29 | 556470.72 | 3571553.00 | 1787312.18 | 4210.84 | 1.89 | 4547.26 | 49.89 |
PERIMETER_BOT_ZN_3 | 3703104.11 | 0.00 | 3703104.11 | 443809.51 | 4146913.62 | 2823374.22 | 4637.46 | 20.97 | 4101.56 | 331.35 |
PERIMETER_BOT_ZN_2 | 2496367.37 | 0.00 | 2496367.37 | 295871.23 | 2792238.60 | 1787429.43 | 4229.96 | 24.09 | 4505.95 | 331.35 |
PERIMETER_BOT_ZN_1 | 3899922.32 | 0.00 | 3899922.32 | 3202062.74 | 7101985.06 | 2823374.22 | 4262.14 | 19.89 | 4477.97 | 331.35 |
PERIMETER_BOT_ZN_4 | 2511234.55 | 0.00 | 2511234.55 | 295871.23 | 2807105.78 | 1787312.18 | 4314.17 | 31.90 | 4413.93 | 331.35 |
PERIMETER_MID_ZN_3 | 3938756.37 | 0.00 | 3938756.37 | 694831.36 | 4633587.72 | 2823374.22 | 4204.12 | 20.42 | 4535.46 | 362.06 |
PERIMETER_MID_ZN_2 | 2538864.86 | 0.00 | 2538864.86 | 463218.12 | 3002082.98 | 1601953.02 | 4143.56 | 4.43 | 4612.01 | 1271.06 |
PERIMETER_MID_ZN_1 | 4120654.09 | 0.00 | 4120654.09 | 694831.36 | 4815485.45 | 2823374.22 | 4161.82 | 4.60 | 4593.58 | 362.06 |
PERIMETER_MID_ZN_4 | 2927709.95 | 0.00 | 2927709.95 | 463218.12 | 3390928.07 | 1787312.18 | 4137.13 | 7.86 | 4615.02 | 362.06 |
Total Facility | 71206149.63 | 0.00 | 71206149.63 | 9336077.29 | 80542226.92 | 67658168.57 | 7102.56 | 265.98 | 4685.33 | 1372.34 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5590 | 0.0000 | 0.5590 | 0.0000 | 0.5590 | 0.4247 | 3680.54 | 95.12 | 2167.35 |
CORE_MID | 0.4029 | 0.0000 | 0.4029 | 0.0000 | 0.4029 | 0.4247 | 4253.08 | 32.02 | 1657.90 |
CORE_TOP | 0.4344 | 0.0000 | 0.4344 | 0.0000 | 0.4344 | 0.4247 | 4079.32 | 19.10 | 1844.57 |
PERIMETER_TOP_ZN_3 | 0.2066 | 0.0000 | 0.2066 | 0.0192 | 0.2257 | 0.0895 | 1405.08 | 4.49 | 4533.44 |
PERIMETER_TOP_ZN_2 | 0.1386 | 0.0000 | 0.1386 | 0.0128 | 0.1514 | 0.0567 | 1400.70 | 1.83 | 4540.47 |
PERIMETER_TOP_ZN_1 | 0.2094 | 0.0000 | 0.2094 | 0.0192 | 0.2286 | 0.0895 | 1403.34 | 1.56 | 4538.10 |
PERIMETER_TOP_ZN_4 | 0.1405 | 0.0000 | 0.1405 | 0.0128 | 0.1533 | 0.0567 | 1399.61 | 1.89 | 4541.50 |
PERIMETER_BOT_ZN_3 | 0.1702 | 0.0000 | 0.1702 | 0.0102 | 0.1804 | 0.0895 | 1847.88 | 17.48 | 4077.65 |
PERIMETER_BOT_ZN_2 | 0.1148 | 0.0000 | 0.1148 | 0.0068 | 0.1216 | 0.0567 | 1443.34 | 21.04 | 4478.63 |
PERIMETER_BOT_ZN_1 | 0.1794 | 0.0000 | 0.1794 | 0.1391 | 0.3186 | 0.0895 | 1468.47 | 17.37 | 4457.16 |
PERIMETER_BOT_ZN_4 | 0.1155 | 0.0000 | 0.1155 | 0.0068 | 0.1223 | 0.0567 | 1529.20 | 30.15 | 4383.64 |
PERIMETER_MID_ZN_3 | 0.1817 | 0.0000 | 0.1817 | 0.0160 | 0.1977 | 0.0895 | 1398.64 | 19.72 | 4524.64 |
PERIMETER_MID_ZN_2 | 0.1276 | 0.0000 | 0.1276 | 0.0113 | 0.1389 | 0.0567 | 1341.59 | 2.84 | 3689.57 |
PERIMETER_MID_ZN_1 | 0.1903 | 0.0000 | 0.1903 | 0.0160 | 0.2062 | 0.0895 | 1355.47 | 4.37 | 4583.16 |
PERIMETER_MID_ZN_4 | 0.1351 | 0.0000 | 0.1351 | 0.0106 | 0.1458 | 0.0567 | 1337.40 | 6.10 | 4599.50 |
Total Facility | 3.3059 | 0.0000 | 3.3059 | 0.2807 | 3.5866 | 2.1513 | 4286.82 | 251.57 | 4646.45 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 32612142.77 | 0.00 | 32612142.77 | 22614548.33 | 4150.70 | 5.82 | 4603.48 | 331.35 |
PACU_VAV_MID | 29344666.16 | 0.00 | 29344666.16 | 22429071.92 | 4168.71 | 2.45 | 4588.85 | 362.04 |
PACU_VAV_TOP | 31976959.47 | 0.00 | 31976959.47 | 22614548.33 | 4223.38 | 0.56 | 4536.06 | 49.76 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5025 | 0.0000 | 1.5025 | 0.7171 | 1352.98 | 3.09 | 4586.93 |
PACU_VAV_MID | 1.3548 | 0.0000 | 1.3548 | 0.7084 | 1360.60 | 2.14 | 4580.26 |
PACU_VAV_TOP | 1.4899 | 0.0000 | 1.4899 | 0.7171 | 1412.14 | 0.56 | 4530.30 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 25.03 | 2924.03 | 0.00 | 0.00 | 0.00 | 2148.26 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 68.56 | 2612.84 | 0.00 | 0.00 | 0.00 | 2485.39 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 30.61 | 2441.90 | 0.00 | 0.00 | 0.00 | 2270.91 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.1990 | 2.5643 | 0.0000 | 0.0000 | 0.0000 | 1.0486 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1887 | 2.3111 | 0.0000 | 0.0000 | 0.0000 | 1.1146 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1758 | 2.6657 | 0.0000 | 0.0000 | 0.0000 | 1.0762 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1985.77 | 15934.24 | 12-MAR-17:40 | 213634.67 | 04-AUG-15:30 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 388.63 | 385.65 | 04-FEB-20:00 | 117966.32 | 04-AUG-15:30 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 1985.77 | 15934.24 | 19-MAR-17:10 | 213634.67 | 04-AUG-15:30 |
ElectricityPurchased:Plant | 1985.77 | 15934.24 | 19-MAR-17:10 | 213634.67 | 04-AUG-15:30 |
Cogeneration:ElectricityPurchased | 1985.77 | 15934.24 | 19-MAR-17:10 | 213634.67 | 04-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 1985.77 | 15934.24 | 19-MAR-17:10 | 213634.67 | 04-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1985.77 | 15934.24 | 19-MAR-17:10 | 213634.67 | 04-AUG-15:30 |
ElectricityNet:Plant | 1985.77 | 15934.24 | 19-MAR-17:10 | 213634.67 | 04-AUG-15:30 |
Cogeneration:ElectricityNet | 1985.77 | 15934.24 | 19-MAR-17:10 | 213634.67 | 04-AUG-15:30 |
General:Cogeneration:ElectricityNet | 1985.77 | 15934.24 | 19-MAR-17:10 | 213634.67 | 04-AUG-15:30 |
Fans:Electricity | 187.51 | 0.00 | 01-JAN-00:40 | 29292.04 | 04-AUG-15:20 |
General:Fans:Electricity | 187.51 | 0.00 | 01-JAN-00:40 | 29292.04 | 04-AUG-15:20 |
ExteriorLights:Electricity | 235.68 | 0.00 | 01-JAN-08:00 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 235.68 | 0.00 | 01-JAN-08:00 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 173.62 | 0.00 | 01-JAN-00:10 | 87265.10 | 04-AUG-15:30 |
General:Cooling:Electricity | 173.62 | 0.00 | 01-JAN-00:10 | 87265.10 | 04-AUG-15:30 |
Electricity:Plant | 65.92 | 0.00 | 01-JAN-00:40 | 8751.22 | 03-FEB-12:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 59.83 | 0.00 | 01-JAN-00:10 | 7596.40 | 15-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 59.83 | 0.00 | 01-JAN-00:10 | 7596.40 | 15-FEB-12:40 |
Pumps:Electricity | 6.10 | 0.00 | 01-JAN-00:40 | 1657.42 | 30-JAN-07:30 |
General:Pumps:Electricity | 6.10 | 0.00 | 01-JAN-00:40 | 1657.42 | 30-JAN-07:30 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1197.05 | 0.00 | 01-JAN-00:40 | 419663.45 | 30-JAN-07:20 |
NaturalGas:Plant | 1197.05 | 0.00 | 01-JAN-00:40 | 419663.45 | 30-JAN-07:20 |
Heating:NaturalGas | 1197.05 | 0.00 | 01-JAN-00:40 | 419663.45 | 30-JAN-07:20 |
Boiler:Heating:NaturalGas | 1197.05 | 0.00 | 01-JAN-00:40 | 419663.45 | 30-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3826.40 | 0.00 | 01-JAN-00:40 | 824501.96 | 30-JAN-07:10 |
EnergyTransfer:Building | 1462.49 | 0.00 | 01-JAN-00:40 | 226768.09 | 30-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 228.13 | 0.00 | 01-JAN-00:40 | 26433.16 | 11-SEP-11:00 |
Heating:EnergyTransfer | 447.94 | 0.00 | 01-JAN-00:40 | 225851.40 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.29 | 0.00 | 01-JAN-00:10 | 11271.15 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 447.94 | 0.00 | 01-JAN-00:40 | 225851.40 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.29 | 0.00 | 01-JAN-00:10 | 11271.15 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 1014.55 | 0.00 | 01-JAN-00:40 | 189807.46 | 04-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 227.84 | 0.00 | 01-JAN-00:40 | 26433.16 | 11-SEP-11:00 |
General:Cooling:EnergyTransfer | 1014.55 | 0.00 | 01-JAN-00:40 | 189807.46 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 227.84 | 0.00 | 01-JAN-00:40 | 26433.16 | 11-SEP-11:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 124.52 | 0.00 | 01-JAN-00:40 | 30829.67 | 02-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 81.09 | 0.00 | 01-JAN-00:40 | 30829.67 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 81.09 | 0.00 | 01-JAN-00:40 | 30829.67 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.43 | 0.00 | 01-JAN-00:10 | 16692.42 | 26-JUN-13:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.43 | 0.00 | 01-JAN-00:10 | 16692.42 | 26-JUN-13:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 39.06 | 0.00 | 01-JAN-00:40 | 12432.55 | 02-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 20.98 | 0.00 | 01-JAN-00:40 | 12432.55 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 20.98 | 0.00 | 01-JAN-00:40 | 12432.55 | 02-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.08 | 0.00 | 01-JAN-00:10 | 5184.47 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.08 | 0.00 | 01-JAN-00:10 | 5184.47 | 04-AUG-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 38.42 | 0.00 | 01-JAN-00:40 | 11237.43 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.49 | 0.00 | 01-JAN-00:40 | 11237.43 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.49 | 0.00 | 01-JAN-00:40 | 11237.43 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 25.93 | 0.00 | 01-JAN-00:10 | 5543.97 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 25.93 | 0.00 | 01-JAN-00:10 | 5543.97 | 04-AUG-15:30 |
EnergyTransfer:Zone:CORE_MID | 147.00 | 0.00 | 01-JAN-00:40 | 19759.65 | 04-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 3.94 | 0.00 | 01-JAN-00:20 | 18625.44 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 3.94 | 0.00 | 01-JAN-00:20 | 18625.44 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 143.05 | 0.00 | 01-JAN-00:40 | 19759.65 | 04-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 143.05 | 0.00 | 01-JAN-00:40 | 19759.65 | 04-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 160.43 | 0.00 | 01-JAN-00:40 | 30808.79 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 21.65 | 0.00 | 01-JAN-00:40 | 30808.79 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 21.65 | 0.00 | 01-JAN-00:40 | 30808.79 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 138.77 | 0.00 | 01-JAN-00:20 | 23539.17 | 30-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 138.77 | 0.00 | 01-JAN-00:20 | 23539.17 | 30-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 79.38 | 0.00 | 01-JAN-00:40 | 17814.39 | 09-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.08 | 0.00 | 01-JAN-00:40 | 17814.39 | 09-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.08 | 0.00 | 01-JAN-00:40 | 17814.39 | 09-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.30 | 0.00 | 01-JAN-00:20 | 8149.53 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.30 | 0.00 | 01-JAN-00:20 | 8149.53 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.83 | 0.00 | 01-JAN-00:40 | 11518.33 | 09-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.84 | 0.00 | 01-JAN-00:40 | 11518.33 | 09-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.84 | 0.00 | 01-JAN-00:40 | 11518.33 | 09-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.98 | 0.00 | 01-JAN-00:20 | 8882.80 | 26-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.98 | 0.00 | 01-JAN-00:20 | 8882.80 | 26-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 83.49 | 0.00 | 01-JAN-00:40 | 17478.94 | 09-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 31.58 | 0.00 | 01-JAN-00:40 | 17478.94 | 09-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 31.58 | 0.00 | 01-JAN-00:40 | 17478.94 | 09-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.90 | 0.00 | 01-JAN-00:20 | 14372.78 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.90 | 0.00 | 01-JAN-00:20 | 14372.78 | 07-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.35 | 0.00 | 01-JAN-00:40 | 11735.41 | 09-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.93 | 0.00 | 01-JAN-00:40 | 11735.41 | 09-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.93 | 0.00 | 01-JAN-00:40 | 11735.41 | 09-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.42 | 0.00 | 01-JAN-00:20 | 10043.33 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.42 | 0.00 | 01-JAN-00:20 | 10043.33 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.23 | 0.00 | 01-JAN-00:40 | 13586.78 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.90 | 0.00 | 01-JAN-00:40 | 13586.78 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.90 | 0.00 | 01-JAN-00:40 | 13586.78 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.33 | 0.00 | 01-JAN-00:20 | 6261.82 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.33 | 0.00 | 01-JAN-00:20 | 6261.82 | 04-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 42.31 | 0.00 | 01-JAN-00:40 | 8720.55 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 16.65 | 0.00 | 01-JAN-00:40 | 8720.55 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 16.65 | 0.00 | 01-JAN-00:40 | 8720.55 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.66 | 0.00 | 01-JAN-00:20 | 6878.36 | 02-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.66 | 0.00 | 01-JAN-00:20 | 6878.36 | 02-AUG-09:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 81.74 | 0.00 | 01-JAN-00:40 | 20765.85 | 02-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 44.78 | 0.00 | 01-JAN-00:40 | 20765.85 | 02-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 44.78 | 0.00 | 01-JAN-00:40 | 20765.85 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 36.95 | 0.00 | 01-JAN-00:20 | 16380.91 | 07-SEP-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 36.95 | 0.00 | 01-JAN-00:20 | 16380.91 | 07-SEP-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 42.98 | 0.00 | 01-JAN-00:40 | 8868.23 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 17.33 | 0.00 | 01-JAN-00:40 | 8868.23 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 17.33 | 0.00 | 01-JAN-00:40 | 8868.23 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.65 | 0.00 | 01-JAN-00:20 | 7630.06 | 07-SEP-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.65 | 0.00 | 01-JAN-00:20 | 7630.06 | 07-SEP-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 61.97 | 0.00 | 01-JAN-00:40 | 13517.77 | 19-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.83 | 0.00 | 01-JAN-00:40 | 13517.77 | 19-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.83 | 0.00 | 01-JAN-00:40 | 13517.77 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 36.14 | 0.00 | 01-JAN-00:20 | 7233.35 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 36.14 | 0.00 | 01-JAN-00:20 | 7233.35 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.89 | 0.00 | 01-JAN-00:40 | 8962.97 | 19-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 15.01 | 0.00 | 01-JAN-00:40 | 8962.97 | 19-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 15.01 | 0.00 | 01-JAN-00:40 | 8962.97 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.87 | 0.00 | 01-JAN-00:20 | 8916.07 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.87 | 0.00 | 01-JAN-00:20 | 8916.07 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 69.28 | 0.00 | 01-JAN-00:40 | 13846.22 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 17.74 | 0.00 | 01-JAN-00:40 | 13210.88 | 19-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 17.74 | 0.00 | 01-JAN-00:40 | 13210.88 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 51.54 | 0.00 | 01-JAN-00:20 | 13846.22 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 51.54 | 0.00 | 01-JAN-00:20 | 13846.22 | 07-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.49 | 0.00 | 01-JAN-00:40 | 9510.98 | 05-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 15.80 | 0.00 | 01-JAN-00:40 | 9223.05 | 19-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 15.80 | 0.00 | 01-JAN-00:40 | 9223.05 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.70 | 0.00 | 01-JAN-00:20 | 9510.98 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.70 | 0.00 | 01-JAN-00:20 | 9510.98 | 05-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 854.68 | 0.00 | 01-JAN-00:40 | 314633.66 | 30-JAN-07:30 |
PlantLoopHeatingDemand:Plant | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:50 |
EnergyTransfer:HVAC | 1515.53 | 0.00 | 01-JAN-00:40 | 313801.95 | 04-AUG-15:30 |
HeatingCoils:EnergyTransfer | 797.71 | 0.00 | 01-JAN-00:40 | 312227.50 | 30-JAN-07:30 |
PlantLoopHeatingDemand:HVAC | 797.71 | 0.00 | 01-JAN-00:40 | 312227.50 | 30-JAN-07:30 |
HeatingCoils:PlantLoopHeatingDemand | 797.71 | 0.00 | 01-JAN-00:40 | 312227.50 | 30-JAN-07:30 |
CoolingCoils:EnergyTransfer | 717.83 | 0.00 | 01-JAN-00:10 | 313786.88 | 04-AUG-15:30 |
EnergyTransfer:Plant | 848.38 | 0.00 | 01-JAN-00:40 | 312794.34 | 30-JAN-07:30 |
WaterSystems:EnergyTransfer | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:50 |
Boilers:EnergyTransfer | 791.41 | 0.00 | 01-JAN-00:40 | 310388.18 | 30-JAN-07:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.288 | -227.838 | 0.000 | 0.000 | 33.811 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -178.047 |
CORE_MID | 0.000 | 0.000 | 3.942 | -143.053 | 0.000 | 0.000 | 35.065 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -123.166 |
CORE_TOP | 0.000 | 0.000 | 21.654 | -138.774 | 0.000 | 0.000 | 36.295 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -146.388 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 42.082 | -37.296 | 0.000 | 0.000 | 7.949 | 23.566 | 24.333 | 15.160 | 0.000 | 0.186 | 0.000 | 0.000 | -60.130 | 0.000 | -14.699 | -1.149 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 24.844 | -30.984 | 0.000 | 0.000 | 4.944 | 14.919 | 15.404 | 29.243 | 0.000 | 0.103 | 0.001 | 0.000 | -36.792 | 0.000 | -9.914 | -11.768 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 31.584 | -51.900 | 0.000 | 0.000 | 7.781 | 23.566 | 24.332 | 60.141 | 0.000 | 0.144 | 0.001 | 0.000 | -52.805 | 0.000 | -15.080 | -27.763 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 25.927 | -31.418 | 0.000 | 0.000 | 4.997 | 14.918 | 15.403 | 30.892 | 0.000 | 0.092 | 0.001 | 0.000 | -38.374 | 0.000 | -9.954 | -12.483 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 29.903 | -29.328 | 0.000 | 0.000 | 7.928 | 23.566 | 24.333 | 15.764 | 0.000 | 0.104 | 0.001 | 0.000 | -60.651 | 0.000 | -8.045 | -3.573 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 16.652 | -25.658 | 0.000 | 0.000 | 4.917 | 14.919 | 15.404 | 29.654 | 0.000 | 0.053 | 0.000 | 0.000 | -37.625 | 0.000 | -5.473 | -12.842 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 44.783 | -36.953 | 0.000 | 0.000 | 7.913 | 23.566 | 24.332 | 61.494 | 0.000 | 1.159 | 0.000 | 0.000 | -53.997 | 0.000 | -52.435 | -19.862 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 17.329 | -25.651 | 0.000 | 0.000 | 4.957 | 14.918 | 15.403 | 31.450 | 0.000 | 0.047 | 0.000 | 0.000 | -39.239 | 0.000 | -5.497 | -13.719 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 25.833 | -36.137 | 0.000 | 0.000 | 7.826 | 23.566 | 24.333 | 14.726 | 0.000 | 0.144 | 15.153 | 0.000 | -62.718 | 0.000 | -12.724 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 15.013 | -28.873 | 0.000 | 0.000 | 3.597 | 14.919 | 15.404 | 28.760 | 0.000 | 0.081 | 0.002 | 0.000 | -38.421 | 0.000 | -8.598 | -1.881 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 17.744 | -51.541 | 0.000 | 0.000 | 7.627 | 23.566 | 24.332 | 59.569 | 0.000 | 0.111 | 0.002 | 0.000 | -55.483 | 0.000 | -13.117 | -12.808 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 15.797 | -31.695 | 0.000 | 0.000 | 4.934 | 14.918 | 15.403 | 30.699 | 0.000 | 0.072 | 0.000 | 0.000 | -40.073 | 0.000 | -8.607 | -1.449 |
TOPFLOOR_PLENUM | 81.092 | -43.431 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.101 | 0.006 | 0.000 | 0.000 | 0.000 | -21.864 | -15.898 |
MIDFLOOR_PLENUM | 20.983 | -18.081 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.170 | 18.997 | 0.000 | 0.000 | 0.000 | -22.069 | -0.000 |
FIRSTFLOOR_PLENUM | 12.488 | -25.932 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.126 | 31.239 | 0.000 | 0.000 | 0.000 | -17.921 | -0.000 |
Total Facility | 114.563 | -87.444 | 333.375 | -927.099 | 0.000 | 0.000 | 180.542 | 566.263 | 729.266 | 407.552 | 0.000 | 2.694 | 65.404 | 0.000 | -576.306 | 0.000 | -225.998 | -582.798 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 11-SEP-05:12 | 0.00 | 0.00 | 0.00 | -48535.24 | 0.00 | 0.00 | 328.12 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 39388.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 27-JUN-05:12 | 0.00 | 0.00 | 0.00 | -30411.32 | 0.00 | 0.00 | 339.49 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 25961.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 30-JUN-15:00 | 0.00 | 0.00 | 0.00 | -23539.05 | 0.00 | 0.00 | 3497.11 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 3473.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 18-JUN-16:21 | 0.00 | 0.00 | 0.00 | -8649.61 | 0.00 | 0.00 | 32.05 | 114.31 | 478.42 | 3291.39 | 0.00 | 573.21 | 4160.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-09:02 | 0.00 | 0.00 | 0.00 | -11053.17 | 0.00 | 0.00 | 14.69 | 72.37 | 302.86 | 10029.73 | 0.00 | 0.00 | 663.75 | 0.00 | -0.00 | 0.00 | -30.23 | 0.00 |
PERIMETER_TOP_ZN_1 | 17-SEP-14:22 | 0.00 | 0.00 | 0.00 | -24060.29 | 0.00 | 0.00 | 25.56 | 114.31 | 478.41 | 10915.92 | 0.00 | 30.20 | 12495.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 18-JUN-16:21 | 0.00 | 0.00 | 0.00 | -21725.37 | 0.00 | 0.00 | 13.03 | 72.36 | 302.86 | 9778.77 | 0.00 | 258.85 | 11299.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | -6261.92 | 0.00 | 0.00 | 737.23 | 2057.62 | 1435.25 | 3966.50 | 0.00 | 50.78 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1985.45 |
PERIMETER_BOT_ZN_2 | 30-JUL-09:22 | 0.00 | 0.00 | 0.00 | -10553.53 | 0.00 | 0.00 | 17.60 | 72.37 | 302.86 | 9684.73 | 0.00 | 0.00 | 506.05 | 0.00 | -0.00 | 0.00 | -30.07 | 0.00 |
PERIMETER_BOT_ZN_1 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | -16377.74 | 0.00 | 0.00 | 398.51 | 2057.62 | 1275.77 | 17018.22 | 0.00 | 5025.12 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9397.50 |
PERIMETER_BOT_ZN_4 | 25-JUN-16:51 | 0.00 | 0.00 | 0.00 | -12924.80 | 0.00 | 0.00 | 15.92 | 72.36 | 302.86 | 12046.96 | 0.00 | 160.57 | 326.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 26-JUN-14:30 | 0.00 | 0.00 | 0.00 | -7233.24 | 0.00 | 0.00 | 737.22 | 2057.62 | 1435.25 | 4616.91 | 0.00 | 68.71 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1682.47 |
PERIMETER_MID_ZN_2 | 30-JUL-09:22 | 0.00 | 0.00 | 0.00 | -16943.40 | 0.00 | 0.00 | 14.74 | 72.37 | 302.86 | 9500.83 | 0.00 | 0.00 | 7109.90 | 0.00 | -0.00 | 0.00 | -57.30 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-14:42 | 0.00 | 0.00 | 0.00 | -22966.20 | 0.00 | 0.00 | 25.97 | 114.31 | 478.41 | 9614.61 | 0.00 | 0.00 | 12858.79 | 0.00 | -0.00 | 0.00 | -125.89 | 0.00 |
PERIMETER_MID_ZN_4 | 30-JUL-16:42 | 0.00 | 0.00 | 0.00 | -17616.62 | 0.00 | 0.00 | 14.40 | 72.36 | 302.86 | 8807.97 | 0.00 | 0.00 | 8444.17 | 0.00 | -0.00 | 0.00 | -25.15 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:05 | 0.00 | -16703.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.32 | 16622.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 18-FEB-05:01 | 0.00 | -6736.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8162.38 | 0.00 | -0.00 | 0.00 | -1425.50 | 0.00 |
FIRSTFLOOR_PLENUM | 16-FEB-05:01 | 0.00 | -7545.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9146.56 | 0.00 | -0.00 | 0.00 | -1600.64 | 0.00 |
Total Facility | 04-AUG-15:20 | 0.00 | -26658.69 | 0.00 | -163150.68 | 0.00 | 0.00 | 17715.01 | 49443.18 | 41937.01 | 74053.75 | 0.00 | 2041.49 | 4618.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 14412.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21463.51 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 22547.52 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26074.09 |
CORE_TOP | 23-JAN-05:11 | 0.00 | 0.00 | 37159.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -40686.16 |
PERIMETER_TOP_ZN_3 | 09-DEC-05:31 | 0.00 | 0.00 | 21240.49 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6151.81 | 0.00 | -5154.06 | -10435.03 |
PERIMETER_TOP_ZN_2 | 09-DEC-05:31 | 0.00 | 0.00 | 13746.06 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3862.19 | 0.00 | -3429.47 | -6771.18 |
PERIMETER_TOP_ZN_1 | 09-DEC-05:31 | 0.00 | 0.00 | 20811.78 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5813.17 | 0.00 | -5168.97 | -10330.05 |
PERIMETER_TOP_ZN_4 | 09-DEC-05:31 | 0.00 | 0.00 | 14028.46 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4088.72 | 0.00 | -3419.32 | -6837.21 |
PERIMETER_BOT_ZN_3 | 30-JAN-05:11 | 0.00 | 0.00 | 15821.96 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6585.04 | 0.00 | -1409.39 | -8570.95 |
PERIMETER_BOT_ZN_2 | 30-JAN-05:11 | 0.00 | 0.00 | 10176.76 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4231.55 | 0.00 | -941.34 | -5474.50 |
PERIMETER_BOT_ZN_1 | 02-FEB-07:10 | 0.00 | 0.00 | 21508.26 | 0.00 | 0.00 | 0.00 | 217.06 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 25120.58 | 0.00 | -7993.33 | 0.00 | -40176.34 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JAN-05:11 | 0.00 | 0.00 | 10376.12 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4408.81 | 0.00 | -941.13 | -5496.79 |
PERIMETER_MID_ZN_3 | 01-FEB-05:11 | 0.00 | 0.00 | 15545.11 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7117.45 | 0.00 | -1487.34 | -7683.75 |
PERIMETER_MID_ZN_2 | 01-FEB-05:11 | 0.00 | 0.00 | 10395.86 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4555.32 | 0.00 | -991.24 | -5319.93 |
PERIMETER_MID_ZN_1 | 01-FEB-05:11 | 0.00 | 0.00 | 15064.45 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6886.37 | 0.00 | -1494.92 | -7426.58 |
PERIMETER_MID_ZN_4 | 01-FEB-05:11 | 0.00 | 0.00 | 10739.63 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4741.71 | 0.00 | -990.08 | -5478.47 |
TOPFLOOR_PLENUM | 02-FEB-05:12 | 34192.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3151.73 | -31040.58 |
MIDFLOOR_PLENUM | 30-JAN-08:08 | 13300.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -914.20 | -12386.19 |
FIRSTFLOOR_PLENUM | 02-JAN-08:16 | 11531.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -499.63 | -11031.63 |
Total Facility | 11-DEC-06:01 | 28846.54 | 0.00 | 212918.64 | 0.00 | 0.00 | 0.00 | 2667.85 | 5493.69 | 20036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -57111.04 | 0.00 | -9529.82 | -203322.21 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 8.1687 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.0345 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 7.7800 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7655 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 9.9337 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 7.0611 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.0844 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.4506 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.8900 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.3340 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.9668 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9801 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5050 | 3.5050 | 1.0515 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8726 | 2.8726 | 0.8618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7853 | 3.7853 | 1.1356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8719 | 1.8719 | 0.5616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2073 | 1.2073 | 0.3622 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8437 | 1.8437 | 0.5531 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2255 | 1.2255 | 0.3677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4197 | 1.4197 | 0.4259 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9168 | 0.9168 | 0.2750 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3929 | 1.3929 | 0.4179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9344 | 0.9344 | 0.2803 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4557 | 1.4557 | 0.4367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9930 | 0.9930 | 0.2979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4281 | 1.4281 | 0.4284 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0305 | 1.0305 | 0.3092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 8.1687 | 6.0345 | 8.1687 | 2.4506 | 0.0000 | 1.0000 |
PACU_VAV_MID | 7.7800 | 5.7655 | 7.7800 | 2.3340 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 9.9337 | 7.0611 | 9.9337 | 2.9801 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7525 | 1.7525 | 1.0515 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4363 | 1.4363 | 0.8618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8927 | 1.8927 | 1.1356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9359 | 0.9359 | 0.5616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6036 | 0.6036 | 0.3622 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9219 | 0.9219 | 0.5531 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6128 | 0.6128 | 0.3677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7098 | 0.7098 | 0.4259 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4584 | 0.4584 | 0.2750 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6964 | 0.6964 | 0.4179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4672 | 0.4672 | 0.2803 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7279 | 0.7279 | 0.4367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4965 | 0.4965 | 0.2979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7141 | 0.7141 | 0.4284 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5153 | 0.5153 | 0.3092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.0844 | 2.4506 | 2.4506 | 2.4506 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.8900 | 2.3340 | 2.3340 | 2.3340 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.9668 | 2.9801 | 2.9801 | 2.9801 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 544.33 |
Number of hours cooling loads not met | 31.17 |
Number of hours not met | 575.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1197.05 | 419663.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 173.62 | 87265.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 235.68 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 187.51 | 29292.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 6.10 | 1657.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 59.83 | 7596.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 1985.77 |
Natural Gas | 0.00 | 1197.05 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 3182.82 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 34.85 |
Fans (All) | 37.64 |
Service Water Heating | 12.01 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 398.57 |
Subtotal | 398.57 |
Natural Gas [MJ/m2] | |
Space Heating | 240.27 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 240.27 |
Subtotal | 240.27 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.79 |
Space Heating | 37.61 |
Space Cooling | 5.45 |
Fans (All) | 5.89 |
Service Water Heating | 1.88 |
Receptacle Equipment | 22.91 |
Miscellaneous | 8.46 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8474.00 | 286.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8736.33 | 23.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8728.50 | 31.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8725.67 | 34.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8677.67 | 82.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8474.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 286.00 | 0.00 | 0.00 | 0.00 |
Average | 8727.88 | 32.12 | 0.00 | 0.00 | 0.00 |
Sum | 157101.83 | 578.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128203.67 | 100.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 100.33 | 0.00 | 0.00 | 0.00 |
Average | 34137.76 | 5.57 | 0.00 | 0.00 | 0.00 |
Sum | 614479.67 | 100.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8090.17 | 669.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8568.00 | 192.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8587.50 | 172.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8542.00 | 218.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8562.00 | 198.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8518.67 | 241.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8599.17 | 160.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8455.83 | 304.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8475.67 | 284.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8408.33 | 351.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8523.17 | 236.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8448.50 | 311.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8476.00 | 284.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8418.83 | 341.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8318.83 | 441.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8578.67 | 181.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8447.67 | 312.33 | 0.00 | 0.00 | 0.00 |
Min | 8090.17 | 17.00 | 0.00 | 0.00 | 0.00 |
Max | 8743.00 | 669.83 | 0.00 | 0.00 | 0.00 |
Average | 8486.78 | 273.22 | 0.00 | 0.00 | 0.00 |
Sum | 152762.00 | 4918.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127964.67 | 339.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128232.17 | 71.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128295.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24908.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24734.83 | 174.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128295.00 | 339.33 | 0.00 | 0.00 | 0.00 |
Average | 34109.92 | 33.42 | 0.00 | 0.00 | 0.00 |
Sum | 613978.50 | 601.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:22:02
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129209E+11 | 11020.27 | 13-JAN-17:00 | 2.20 | 0.77 | 0.163292E+10 | 2537.88 | 13-JAN-16:10 | 2.20 | 0.77 |
February | 0.120050E+11 | 11391.20 | 24-FEB-17:00 | 7.20 | 5.13 | 0.156933E+10 | 2540.94 | 10-FEB-14:00 | 7.20 | 5.13 |
March | 0.151271E+11 | 16443.93 | 24-MAR-16:00 | 10.60 | 5.50 | 0.202412E+10 | 2606.66 | 23-MAR-09:20 | 10.60 | 5.50 |
April | 0.160195E+11 | 27782.42 | 21-APR-05:01 | 0.60 | 0.31 | 0.186823E+10 | 2606.70 | 11-APR-13:00 | 0.60 | 0.31 |
May | 0.206084E+11 | 33176.15 | 30-MAY-05:13 | 14.60 | 14.60 | 0.207320E+10 | 2606.70 | 09-MAY-13:09 | 14.60 | 14.60 |
June | 0.259539E+11 | 47634.49 | 29-JUN-05:12 | 17.77 | 16.57 | 0.207014E+10 | 2606.69 | 21-JUN-13:20 | 17.77 | 16.57 |
July | 0.273728E+11 | 48532.47 | 06-JUL-05:12 | 18.90 | 18.23 | 0.192669E+10 | 2606.68 | 24-JUL-09:39 | 21.33 | 16.55 |
August | 0.291135E+11 | 47300.73 | 14-AUG-05:12 | 15.77 | 15.05 | 0.216215E+10 | 2606.80 | 08-AUG-09:09 | 15.77 | 15.05 |
September | 0.239015E+11 | 48540.60 | 11-SEP-05:12 | 19.80 | 17.33 | 0.191691E+10 | 2606.68 | 18-SEP-09:20 | 21.30 | 16.23 |
October | 0.172646E+11 | 25447.99 | 13-OCT-05:01 | 0.43 | -0.6 | 0.198031E+10 | 2606.66 | 20-OCT-13:20 | 22.07 | 12.75 |
November | 0.146016E+11 | 24961.04 | 04-NOV-05:01 | 1.10 | -0.6 | 0.186558E+10 | 2606.67 | 01-NOV-09:20 | 1.10 | -0.6 |
December | 0.129491E+11 | 11734.41 | 07-DEC-16:20 | -5.7 | -8.8 | 0.169326E+10 | 2578.58 | 07-DEC-14:00 | -5.7 | -8.8 |
Annual Sum or Average | 0.227838E+12 | 0.227828E+11 | ||||||||
Minimum of Months | 0.120050E+11 | 11020.27 | -5.7 | -8.8 | 0.156933E+10 | 2537.88 | -5.7 | -8.8 | ||
Maximum of Months | 0.291135E+11 | 48540.60 | 19.80 | 18.23 | 0.216215E+10 | 2606.80 | 22.07 | 16.57 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 852923.78 | 158.80 | 13-JAN-13:03 | 3.90 | 1.72 | 0.00 | 0.00 | 01-JAN-00:10 | 3.90 | 1.72 |
February | 82992500.39 | 2878.64 | 24-FEB-14:00 | 7.80 | 5.17 | 0.00 | 0.00 | 01-FEB-00:10 | 7.80 | 5.17 |
March | 0.780182E+09 | 5221.61 | 28-MAR-14:00 | 16.70 | 10.30 | 0.00 | 0.00 | 01-MAR-00:10 | 16.70 | 10.30 |
April | 0.278603E+10 | 12466.14 | 18-APR-13:50 | 28.12 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 28.12 | 20.65 |
May | 0.575595E+10 | 14790.09 | 31-MAY-13:50 | 29.50 | 19.49 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 19.49 |
June | 0.889385E+10 | 16703.42 | 26-JUN-13:05 | 31.20 | 21.54 | 0.00 | 0.00 | 01-JUN-00:10 | 31.20 | 21.54 |
July | 0.966720E+10 | 16125.30 | 05-JUL-13:50 | 27.12 | 19.90 | 0.00 | 0.00 | 01-JUL-00:10 | 27.12 | 19.90 |
August | 0.881796E+10 | 16462.16 | 04-AUG-14:30 | 33.60 | 25.57 | 0.00 | 0.00 | 01-AUG-00:10 | 33.60 | 25.57 |
September | 0.503118E+10 | 15533.17 | 07-SEP-13:40 | 32.03 | 18.28 | 0.00 | 0.00 | 01-SEP-00:10 | 32.03 | 18.28 |
October | 0.135153E+10 | 7123.21 | 01-OCT-13:55 | 19.00 | 12.30 | 0.00 | 0.00 | 01-OCT-00:10 | 19.00 | 12.30 |
November | 0.263507E+09 | 4057.54 | 03-NOV-13:13 | 15.77 | 10.85 | 0.00 | 0.00 | 01-NOV-00:10 | 15.77 | 10.85 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.434312E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -0.7 | -1.3 | 0.00 | 0.00 | -0.7 | -1.3 | ||
Maximum of Months | 0.966720E+10 | 16703.42 | 33.60 | 25.57 | 0.00 | 0.00 | 33.60 | 25.57 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334489E+09 | 5673.54 | 07-JAN-05:11 | -25.8 | -26.0 | 0.00 | 0.00 | 01-JAN-00:10 | -25.8 | -26.0 |
February | 0.174641E+09 | 6736.87 | 18-FEB-05:01 | -15.6 | -15.9 | 0.00 | 0.00 | 01-FEB-00:10 | -15.6 | -15.9 |
March | 0.230454E+09 | 5970.59 | 08-MAR-05:01 | -14.7 | -15.0 | 0.00 | 0.00 | 01-MAR-00:10 | -14.7 | -15.0 |
April | 0.881915E+09 | 4828.59 | 01-APR-05:01 | -6.6 | -7.0 | 0.00 | 0.00 | 01-APR-00:10 | -6.6 | -7.0 |
May | 0.198365E+10 | 4364.04 | 02-MAY-05:11 | 2.20 | 0.27 | 0.00 | 0.00 | 01-MAY-00:10 | 2.20 | 0.27 |
June | 0.354443E+10 | 5037.69 | 26-JUN-16:00 | 31.70 | 22.11 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 22.11 |
July | 0.392964E+10 | 4811.73 | 05-JUL-16:00 | 27.80 | 20.26 | 0.00 | 0.00 | 01-JUL-00:10 | 27.80 | 20.26 |
August | 0.375872E+10 | 5184.47 | 04-AUG-15:30 | 33.90 | 25.83 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.83 |
September | 0.228762E+10 | 4371.10 | 08-SEP-15:50 | 29.50 | 18.55 | 0.00 | 0.00 | 01-SEP-00:10 | 29.50 | 18.55 |
October | 0.556982E+09 | 3851.89 | 07-OCT-05:11 | 3.90 | 2.45 | 0.00 | 0.00 | 01-OCT-00:10 | 3.90 | 2.45 |
November | 0.279922E+09 | 4673.71 | 22-NOV-05:02 | -8.3 | -9.3 | 0.00 | 0.00 | 01-NOV-00:10 | -8.3 | -9.3 |
December | 0.118897E+09 | 6234.47 | 16-DEC-05:01 | -14.4 | -14.9 | 0.00 | 0.00 | 01-DEC-00:10 | -14.4 | -14.9 |
Annual Sum or Average | 0.180814E+11 | 0.00 | ||||||||
Minimum of Months | 0.118897E+09 | 3851.89 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.392964E+10 | 6736.87 | 33.90 | 25.83 | 0.00 | 0.00 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450000E+09 | 6181.40 | 07-JAN-05:01 | -25.7 | -26.0 | 0.00 | 0.00 | 01-JAN-00:10 | -25.7 | -26.0 |
February | 0.373387E+09 | 7545.89 | 16-FEB-05:01 | -17.3 | -17.7 | 0.00 | 0.00 | 01-FEB-00:10 | -17.3 | -17.7 |
March | 0.612505E+09 | 7488.26 | 08-MAR-05:01 | -14.7 | -15.0 | 0.00 | 0.00 | 01-MAR-00:10 | -14.7 | -15.0 |
April | 0.146350E+10 | 7279.66 | 01-APR-05:01 | -6.6 | -7.0 | 0.00 | 0.00 | 01-APR-00:10 | -6.6 | -7.0 |
May | 0.307967E+10 | 6739.68 | 02-MAY-05:11 | 2.20 | 0.27 | 0.00 | 0.00 | 01-MAY-00:10 | 2.20 | 0.27 |
June | 0.445612E+10 | 4971.79 | 30-JUN-15:50 | 28.98 | 20.94 | 0.00 | 0.00 | 01-JUN-00:10 | 28.98 | 20.94 |
July | 0.483545E+10 | 5027.66 | 05-JUL-16:00 | 27.80 | 20.26 | 0.00 | 0.00 | 01-JUL-00:10 | 27.80 | 20.26 |
August | 0.486681E+10 | 5543.97 | 04-AUG-15:30 | 33.90 | 25.83 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.83 |
September | 0.349652E+10 | 5192.90 | 08-SEP-15:40 | 29.60 | 18.66 | 0.00 | 0.00 | 01-SEP-00:10 | 29.60 | 18.66 |
October | 0.139728E+10 | 4124.68 | 24-OCT-05:11 | 2.07 | 0.17 | 0.00 | 0.00 | 01-OCT-00:10 | 2.07 | 0.17 |
November | 0.690568E+09 | 4897.96 | 25-NOV-05:01 | -15.3 | -15.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.3 | -15.7 |
December | 0.210791E+09 | 6099.49 | 28-DEC-05:01 | -17.2 | -17.5 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.5 |
Annual Sum or Average | 0.259326E+11 | 0.00 | ||||||||
Minimum of Months | 0.210791E+09 | 4124.68 | -25.7 | -26.0 | 0.00 | 0.00 | -25.7 | -26.0 | ||
Maximum of Months | 0.486681E+10 | 7545.89 | 33.90 | 25.83 | 0.00 | 0.00 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613875E+10 | 7580.18 | 19-JAN-17:00 | -23.3 | -23.7 | 0.150542E+10 | 2353.31 | 13-JAN-14:00 | -23.3 | -23.7 |
February | 0.646004E+10 | 8545.64 | 01-FEB-17:00 | -26.7 | -27.0 | 0.141430E+10 | 2365.86 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.918184E+10 | 9131.93 | 24-MAR-16:00 | 10.60 | 5.50 | 0.182335E+10 | 2582.69 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.104999E+11 | 16659.08 | 18-APR-16:00 | 25.00 | 19.37 | 0.174088E+10 | 2606.64 | 19-APR-13:20 | 10.60 | 7.03 |
May | 0.139511E+11 | 18284.71 | 31-MAY-16:00 | 28.30 | 18.78 | 0.203037E+10 | 2606.69 | 09-MAY-13:09 | 28.30 | 18.78 |
June | 0.182089E+11 | 30410.06 | 27-JUN-05:12 | 20.57 | 19.04 | 0.205126E+10 | 2606.67 | 21-JUN-13:20 | 20.57 | 19.04 |
July | 0.191135E+11 | 29364.14 | 05-JUL-05:12 | 18.33 | 17.79 | 0.191755E+10 | 2606.65 | 18-JUL-09:30 | 21.40 | 14.62 |
August | 0.196712E+11 | 28637.99 | 04-AUG-05:12 | 22.80 | 22.80 | 0.215143E+10 | 2606.74 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.149697E+11 | 25560.95 | 11-SEP-05:12 | 19.80 | 17.33 | 0.188078E+10 | 2606.67 | 12-SEP-13:20 | 21.67 | 16.01 |
October | 0.101010E+11 | 11273.11 | 20-OCT-16:00 | 21.30 | 12.72 | 0.183688E+10 | 2606.66 | 20-OCT-13:20 | 21.30 | 12.72 |
November | 0.807798E+10 | 10848.18 | 03-NOV-16:00 | 15.00 | 9.33 | 0.167158E+10 | 2606.61 | 03-NOV-13:20 | 15.00 | 9.33 |
December | 0.667958E+10 | 7390.14 | 01-DEC-16:20 | -2.4 | -4.5 | 0.150509E+10 | 2323.07 | 01-DEC-14:00 | -2.4 | -4.5 |
Annual Sum or Average | 0.143053E+12 | 0.215289E+11 | ||||||||
Minimum of Months | 0.613875E+10 | 7390.14 | -26.7 | -27.0 | 0.141430E+10 | 2323.07 | -23.3 | -23.7 | ||
Maximum of Months | 0.196712E+11 | 30410.06 | 28.30 | 22.80 | 0.215143E+10 | 2606.74 | 28.30 | 19.04 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326274E+10 | 8799.34 | 07-JAN-17:01 | -20.1 | -20.6 | 0.145482E+10 | 2114.72 | 13-JAN-14:00 | 3.90 | 1.72 |
February | 0.445480E+10 | 9158.07 | 24-FEB-17:00 | 7.20 | 5.13 | 0.133671E+10 | 2200.00 | 24-FEB-14:00 | 7.20 | 5.13 |
March | 0.800500E+10 | 10364.48 | 24-MAR-15:50 | 10.97 | 5.67 | 0.166749E+10 | 2414.62 | 24-MAR-13:00 | 10.97 | 5.67 |
April | 0.106416E+11 | 19331.40 | 18-APR-15:40 | 26.10 | 19.83 | 0.160419E+10 | 2606.64 | 19-APR-13:20 | 10.60 | 7.03 |
May | 0.154521E+11 | 21842.48 | 31-MAY-15:20 | 29.43 | 19.40 | 0.192431E+10 | 2606.64 | 04-MAY-13:20 | 29.43 | 19.40 |
June | 0.200066E+11 | 23539.17 | 30-JUN-15:00 | 29.40 | 21.59 | 0.200194E+10 | 2606.68 | 30-JUN-09:50 | 29.40 | 21.59 |
July | 0.207163E+11 | 23407.45 | 05-JUL-14:50 | 27.70 | 20.18 | 0.189336E+10 | 2606.71 | 11-JUL-13:00 | 17.80 | 16.71 |
August | 0.205782E+11 | 23484.13 | 04-AUG-15:20 | 33.90 | 25.66 | 0.211467E+10 | 2606.68 | 21-AUG-13:20 | 29.07 | 21.18 |
September | 0.150717E+11 | 21177.96 | 08-SEP-15:20 | 29.80 | 18.88 | 0.176390E+10 | 2606.65 | 12-SEP-09:20 | 15.00 | 14.60 |
October | 0.969591E+10 | 10901.69 | 20-OCT-16:00 | 21.30 | 12.72 | 0.161674E+10 | 2485.92 | 20-OCT-15:00 | 21.30 | 12.72 |
November | 0.681104E+10 | 10518.66 | 03-NOV-16:00 | 15.00 | 9.33 | 0.151145E+10 | 2426.28 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.407789E+10 | 9158.92 | 09-DEC-17:01 | -19.4 | -19.8 | 0.140911E+10 | 2089.26 | 01-DEC-14:00 | -19.4 | -19.8 |
Annual Sum or Average | 0.138774E+12 | 0.202987E+11 | ||||||||
Minimum of Months | 0.326274E+10 | 8799.34 | -20.1 | -20.6 | 0.133671E+10 | 2089.26 | -19.4 | -19.8 | ||
Maximum of Months | 0.207163E+11 | 23539.17 | 33.90 | 25.66 | 0.211467E+10 | 2606.71 | 29.43 | 21.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31945111.97 | 4086.17 | 07-JAN-17:01 | -20.1 | -20.6 | 0.303683E+09 | 406.89 | 02-JAN-10:39 | -20.1 | -20.6 |
February | 77871867.92 | 3970.89 | 04-FEB-17:01 | -20.1 | -20.6 | 0.275719E+09 | 406.88 | 02-FEB-14:00 | -20.1 | -20.6 |
March | 0.700414E+09 | 3862.33 | 28-MAR-15:20 | 16.67 | 10.57 | 0.332821E+09 | 419.37 | 28-MAR-13:00 | 16.67 | 10.57 |
April | 0.223929E+10 | 6121.38 | 18-APR-15:00 | 28.30 | 20.65 | 0.304908E+09 | 549.47 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.530610E+10 | 7035.26 | 31-MAY-15:00 | 30.00 | 19.70 | 0.356118E+09 | 549.49 | 31-MAY-13:20 | 30.00 | 19.70 |
June | 0.711004E+10 | 8648.60 | 18-JUN-16:21 | 32.20 | 22.56 | 0.390417E+09 | 549.50 | 09-JUN-13:20 | 32.20 | 22.56 |
July | 0.751090E+10 | 8238.18 | 04-JUL-15:51 | 27.80 | 21.82 | 0.373601E+09 | 549.50 | 13-JUL-13:20 | 25.60 | 19.28 |
August | 0.732885E+10 | 7987.91 | 04-AUG-15:30 | 33.90 | 25.83 | 0.410482E+09 | 549.50 | 21-AUG-13:30 | 29.15 | 21.37 |
September | 0.468478E+10 | 6595.79 | 11-SEP-14:30 | 28.60 | 20.18 | 0.329814E+09 | 549.49 | 11-SEP-13:20 | 28.60 | 20.18 |
October | 0.162067E+10 | 4213.50 | 20-OCT-15:40 | 21.97 | 12.95 | 0.308363E+09 | 441.96 | 20-OCT-13:00 | 21.97 | 12.95 |
November | 0.661073E+09 | 4036.54 | 25-NOV-17:01 | -19.6 | -20.1 | 0.302392E+09 | 422.20 | 03-NOV-13:00 | -19.6 | -20.1 |
December | 25269729.43 | 4243.41 | 09-DEC-17:01 | -19.4 | -19.8 | 0.293453E+09 | 406.85 | 05-DEC-14:30 | -19.4 | -19.8 |
Annual Sum or Average | 0.372972E+11 | 0.398177E+10 | ||||||||
Minimum of Months | 25269729.43 | 3862.33 | -20.1 | -20.6 | 0.275719E+09 | 406.85 | -20.1 | -20.6 | ||
Maximum of Months | 0.751090E+10 | 8648.60 | 33.90 | 25.83 | 0.410482E+09 | 549.50 | 32.20 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46062838.27 | 2636.61 | 07-JAN-17:01 | -20.1 | -20.6 | 0.192438E+09 | 257.59 | 19-JAN-14:39 | -23.0 | -23.3 |
February | 0.170672E+09 | 2555.47 | 04-FEB-17:01 | -20.1 | -20.6 | 0.174994E+09 | 276.21 | 24-FEB-10:09 | 4.60 | 1.53 |
March | 0.902398E+09 | 3071.72 | 28-MAR-09:50 | 9.53 | 5.99 | 0.213445E+09 | 312.60 | 28-MAR-09:00 | 10.00 | 6.30 |
April | 0.202115E+10 | 7279.19 | 18-APR-09:30 | 24.20 | 19.59 | 0.201965E+09 | 347.88 | 18-APR-09:00 | 25.60 | 20.52 |
May | 0.419987E+10 | 8418.18 | 31-MAY-09:10 | 26.28 | 19.65 | 0.243290E+09 | 347.88 | 31-MAY-09:20 | 26.47 | 19.61 |
June | 0.576393E+10 | 11054.75 | 25-JUN-09:02 | 26.38 | 21.26 | 0.259794E+09 | 347.89 | 01-JUN-09:00 | 26.38 | 21.26 |
July | 0.613302E+10 | 9401.68 | 02-JUL-09:02 | 25.78 | 21.09 | 0.248526E+09 | 347.90 | 18-JUL-09:30 | 21.40 | 14.62 |
August | 0.579269E+10 | 8395.38 | 02-AUG-09:10 | 24.18 | 20.22 | 0.275638E+09 | 347.89 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.388732E+10 | 7330.49 | 08-SEP-09:40 | 26.47 | 17.94 | 0.222957E+09 | 347.89 | 07-SEP-09:00 | 26.47 | 17.94 |
October | 0.152037E+10 | 3224.06 | 20-OCT-09:50 | 14.70 | 9.97 | 0.198026E+09 | 323.17 | 20-OCT-09:00 | 15.20 | 10.20 |
November | 0.517375E+09 | 2605.67 | 25-NOV-17:01 | -19.6 | -20.1 | 0.191772E+09 | 276.70 | 03-NOV-13:00 | -19.6 | -20.1 |
December | 29233470.31 | 2734.15 | 09-DEC-17:01 | -19.4 | -19.8 | 0.185831E+09 | 257.58 | 11-DEC-10:30 | -20.6 | -21.2 |
Annual Sum or Average | 0.309841E+11 | 0.260868E+10 | ||||||||
Minimum of Months | 29233470.31 | 2555.47 | -20.1 | -20.6 | 0.174994E+09 | 257.58 | -23.0 | -23.3 | ||
Maximum of Months | 0.613302E+10 | 11054.75 | 26.47 | 21.26 | 0.275638E+09 | 347.90 | 26.47 | 21.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.875712E+09 | 4971.44 | 12-JAN-12:40 | 2.03 | 0.42 | 0.308806E+09 | 507.47 | 12-JAN-14:50 | 2.70 | 1.03 |
February | 0.121055E+10 | 7472.54 | 24-FEB-13:50 | 7.62 | 4.99 | 0.284843E+09 | 549.50 | 24-FEB-14:20 | 7.97 | 5.32 |
March | 0.219584E+10 | 7679.73 | 24-MAR-13:40 | 12.93 | 6.50 | 0.351094E+09 | 549.50 | 28-MAR-13:20 | 15.97 | 9.97 |
April | 0.351567E+10 | 11472.82 | 18-APR-12:40 | 27.40 | 20.72 | 0.326647E+09 | 549.50 | 13-APR-13:20 | 27.40 | 20.72 |
May | 0.599470E+10 | 10451.80 | 30-MAY-13:30 | 26.70 | 19.86 | 0.372948E+09 | 549.50 | 22-MAY-13:00 | 26.70 | 19.86 |
June | 0.781765E+10 | 11230.07 | 30-JUN-13:10 | 29.40 | 21.96 | 0.396869E+09 | 549.51 | 09-JUN-13:20 | 29.40 | 21.96 |
July | 0.850603E+10 | 10678.83 | 05-JUL-13:10 | 26.78 | 20.42 | 0.379629E+09 | 549.51 | 31-JUL-13:09 | 26.60 | 20.97 |
August | 0.895369E+10 | 12917.96 | 29-AUG-13:30 | 23.60 | 16.39 | 0.423775E+09 | 549.52 | 07-AUG-13:09 | 23.60 | 16.39 |
September | 0.675903E+10 | 24058.96 | 17-SEP-14:22 | 27.20 | 18.12 | 0.351221E+09 | 549.51 | 07-SEP-09:00 | 27.20 | 18.12 |
October | 0.351715E+10 | 10874.20 | 20-OCT-13:30 | 22.20 | 12.82 | 0.342121E+09 | 549.51 | 20-OCT-13:20 | 22.20 | 12.82 |
November | 0.157675E+10 | 9603.13 | 03-NOV-13:25 | 15.85 | 10.76 | 0.309090E+09 | 549.49 | 03-NOV-13:20 | 15.85 | 10.76 |
December | 0.978213E+09 | 5283.91 | 01-DEC-13:40 | -0.8 | -3.2 | 0.301994E+09 | 538.71 | 01-DEC-14:09 | -0.7 | -3.2 |
Annual Sum or Average | 0.519010E+11 | 0.414904E+10 | ||||||||
Minimum of Months | 0.875712E+09 | 4971.44 | -0.8 | -3.2 | 0.284843E+09 | 507.47 | -0.7 | -3.2 | ||
Maximum of Months | 0.895369E+10 | 24058.96 | 29.40 | 21.96 | 0.423775E+09 | 549.52 | 29.40 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80401696.02 | 2670.28 | 07-JAN-17:01 | -20.1 | -20.6 | 0.192268E+09 | 258.59 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.255017E+09 | 3265.46 | 24-FEB-16:40 | 7.57 | 5.38 | 0.175551E+09 | 314.42 | 24-FEB-16:49 | 7.38 | 5.26 |
March | 0.851266E+09 | 3359.56 | 23-MAR-16:00 | 17.20 | 10.15 | 0.213754E+09 | 317.06 | 23-MAR-15:00 | 17.20 | 10.15 |
April | 0.217271E+10 | 13262.99 | 15-APR-17:06 | 29.72 | 18.80 | 0.200240E+09 | 347.85 | 18-APR-13:20 | 27.57 | 20.63 |
May | 0.409326E+10 | 9095.75 | 30-MAY-16:00 | 27.80 | 19.90 | 0.230923E+09 | 347.85 | 30-MAY-13:20 | 27.80 | 19.90 |
June | 0.573314E+10 | 21725.52 | 18-JUN-16:21 | 32.20 | 22.56 | 0.248803E+09 | 347.85 | 09-JUN-13:20 | 32.20 | 22.56 |
July | 0.619333E+10 | 21510.37 | 04-JUL-15:51 | 27.80 | 21.82 | 0.238151E+09 | 347.86 | 31-JUL-13:20 | 26.50 | 21.07 |
August | 0.600864E+10 | 10292.86 | 05-AUG-17:05 | 25.32 | 17.94 | 0.263216E+09 | 347.86 | 21-AUG-13:20 | 29.07 | 21.18 |
September | 0.384865E+10 | 9254.56 | 07-SEP-16:00 | 31.70 | 18.53 | 0.212813E+09 | 347.85 | 11-SEP-13:20 | 28.50 | 20.29 |
October | 0.150443E+10 | 5384.94 | 20-OCT-15:30 | 22.30 | 13.06 | 0.202065E+09 | 338.69 | 20-OCT-15:39 | 21.97 | 12.95 |
November | 0.561582E+09 | 3484.30 | 03-NOV-15:40 | 15.37 | 9.43 | 0.192245E+09 | 329.94 | 03-NOV-15:50 | 15.18 | 9.38 |
December | 0.116151E+09 | 2771.05 | 09-DEC-17:01 | -19.4 | -19.8 | 0.185820E+09 | 257.60 | 08-DEC-14:39 | -19.4 | -19.8 |
Annual Sum or Average | 0.314186E+11 | 0.255585E+10 | ||||||||
Minimum of Months | 80401696.02 | 2670.28 | -20.1 | -20.6 | 0.175551E+09 | 257.60 | -19.4 | -19.8 | ||
Maximum of Months | 0.619333E+10 | 21725.52 | 32.20 | 22.56 | 0.263216E+09 | 347.86 | 32.20 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19715815.72 | 2465.69 | 14-JAN-17:01 | -7.4 | -8.6 | 0.303510E+09 | 406.86 | 18-JAN-10:09 | -13.4 | -13.8 |
February | 29421051.37 | 2487.63 | 25-FEB-17:02 | 4.63 | 1.87 | 0.275774E+09 | 406.83 | 27-FEB-10:50 | -5.0 | -5.6 |
March | 0.300827E+09 | 2508.73 | 25-MAR-16:03 | 17.62 | 10.44 | 0.332598E+09 | 406.82 | 06-MAR-10:30 | 17.62 | 10.44 |
April | 0.106664E+10 | 4095.32 | 16-APR-13:12 | 27.07 | 20.09 | 0.299197E+09 | 493.83 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.332971E+10 | 4045.61 | 31-MAY-15:10 | 29.72 | 19.55 | 0.341898E+09 | 528.18 | 31-MAY-13:00 | 29.72 | 19.55 |
June | 0.513629E+10 | 5233.42 | 27-JUN-15:30 | 30.30 | 21.78 | 0.384896E+09 | 549.49 | 28-JUN-13:20 | 28.90 | 20.51 |
July | 0.565469E+10 | 5096.00 | 03-JUL-15:00 | 30.00 | 24.25 | 0.377298E+09 | 549.49 | 05-JUL-13:20 | 26.87 | 20.29 |
August | 0.590645E+10 | 6261.82 | 04-AUG-15:30 | 33.90 | 25.83 | 0.425342E+09 | 549.49 | 11-AUG-13:20 | 27.23 | 18.31 |
September | 0.453406E+10 | 5583.14 | 11-SEP-14:30 | 28.60 | 20.18 | 0.346974E+09 | 549.49 | 08-SEP-13:20 | 28.60 | 20.18 |
October | 0.229565E+10 | 3270.70 | 02-OCT-15:00 | 18.30 | 14.84 | 0.315076E+09 | 453.36 | 02-OCT-13:00 | 18.30 | 14.84 |
November | 0.102964E+10 | 3089.50 | 03-NOV-15:10 | 15.92 | 9.56 | 0.306124E+09 | 441.10 | 03-NOV-13:00 | 15.92 | 9.56 |
December | 25229704.16 | 2500.74 | 02-DEC-17:02 | 1.70 | 0.90 | 0.294123E+09 | 406.85 | 08-DEC-14:50 | -14.9 | -15.3 |
Annual Sum or Average | 0.293283E+11 | 0.400281E+10 | ||||||||
Minimum of Months | 19715815.72 | 2465.69 | -7.4 | -8.6 | 0.275774E+09 | 406.82 | -14.9 | -15.3 | ||
Maximum of Months | 0.590645E+10 | 6261.82 | 33.90 | 25.83 | 0.425342E+09 | 549.49 | 29.72 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35185339.26 | 1593.26 | 14-JAN-17:01 | -7.4 | -8.6 | 0.192483E+09 | 257.59 | 18-JAN-14:30 | -16.9 | -17.2 |
February | 86805036.76 | 1808.21 | 24-FEB-09:20 | 3.33 | 0.76 | 0.175077E+09 | 264.48 | 24-FEB-10:09 | 4.60 | 1.53 |
March | 0.538598E+09 | 2096.24 | 28-MAR-10:00 | 10.00 | 6.30 | 0.212157E+09 | 290.33 | 28-MAR-09:00 | 10.00 | 6.30 |
April | 0.120939E+10 | 4401.52 | 18-APR-09:40 | 24.67 | 19.90 | 0.197467E+09 | 347.87 | 17-APR-09:20 | 24.67 | 19.90 |
May | 0.285984E+10 | 5566.84 | 31-MAY-09:30 | 26.65 | 19.56 | 0.237640E+09 | 347.88 | 04-MAY-09:00 | 26.65 | 19.56 |
June | 0.436677E+10 | 8546.98 | 25-JUN-10:32 | 28.87 | 21.94 | 0.260586E+09 | 347.88 | 01-JUN-09:50 | 28.87 | 21.94 |
July | 0.492274E+10 | 10552.18 | 30-JUL-09:22 | 23.35 | 19.20 | 0.251706E+09 | 347.89 | 18-JUL-09:30 | 23.35 | 19.20 |
August | 0.501469E+10 | 6878.36 | 02-AUG-09:20 | 24.47 | 20.38 | 0.282573E+09 | 347.90 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.383653E+10 | 6546.44 | 08-SEP-09:40 | 26.47 | 17.94 | 0.235709E+09 | 347.88 | 06-SEP-09:20 | 26.47 | 17.94 |
October | 0.197274E+10 | 2578.71 | 20-OCT-10:00 | 15.20 | 10.20 | 0.209634E+09 | 336.00 | 20-OCT-09:00 | 15.20 | 10.20 |
November | 0.775320E+09 | 2164.25 | 03-NOV-10:40 | 13.87 | 11.30 | 0.195005E+09 | 290.35 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 39795010.01 | 1619.99 | 02-DEC-17:02 | 1.70 | 0.90 | 0.186327E+09 | 257.56 | 12-DEC-14:39 | -15.8 | -16.3 |
Annual Sum or Average | 0.256584E+11 | 0.263636E+10 | ||||||||
Minimum of Months | 35185339.26 | 1593.26 | -7.4 | -8.6 | 0.175077E+09 | 257.56 | -16.9 | -17.2 | ||
Maximum of Months | 0.501469E+10 | 10552.18 | 28.87 | 21.94 | 0.282573E+09 | 347.90 | 28.87 | 21.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155452E+09 | 2902.67 | 13-JAN-14:30 | 3.90 | 1.72 | 0.274260E+09 | 432.09 | 13-JAN-14:39 | 3.90 | 1.72 |
February | 0.296956E+09 | 3397.74 | 24-FEB-14:30 | 8.05 | 5.40 | 0.259478E+09 | 479.16 | 24-FEB-14:39 | 8.13 | 5.47 |
March | 0.738182E+09 | 3798.13 | 24-MAR-14:00 | 13.30 | 6.51 | 0.326774E+09 | 518.64 | 24-MAR-13:00 | 13.30 | 6.51 |
April | 0.158037E+10 | 8621.79 | 18-APR-12:00 | 27.80 | 20.94 | 0.306973E+09 | 549.49 | 17-APR-13:20 | 27.80 | 20.94 |
May | 0.339724E+10 | 9575.61 | 31-MAY-12:00 | 29.40 | 19.85 | 0.353390E+09 | 549.49 | 05-MAY-13:20 | 29.40 | 19.85 |
June | 0.553379E+10 | 12003.86 | 26-JUN-12:00 | 30.60 | 21.63 | 0.391482E+09 | 549.51 | 20-JUN-13:20 | 30.60 | 21.63 |
July | 0.657486E+10 | 9650.43 | 26-JUL-16:10 | 29.82 | 25.48 | 0.384212E+09 | 549.50 | 18-JUL-13:20 | 29.82 | 25.48 |
August | 0.762511E+10 | 14278.40 | 04-AUG-12:00 | 31.10 | 26.10 | 0.436308E+09 | 549.51 | 07-AUG-13:09 | 21.20 | 12.89 |
September | 0.624372E+10 | 16380.91 | 07-SEP-12:00 | 30.60 | 18.67 | 0.361742E+09 | 549.51 | 12-SEP-13:20 | 21.67 | 16.01 |
October | 0.318353E+10 | 8744.65 | 20-OCT-13:50 | 22.47 | 12.96 | 0.342853E+09 | 549.51 | 20-OCT-13:20 | 22.47 | 12.96 |
November | 0.122971E+10 | 6136.19 | 04-NOV-13:25 | 14.15 | 6.81 | 0.303289E+09 | 549.50 | 03-NOV-13:20 | 14.15 | 6.81 |
December | 0.394324E+09 | 3127.33 | 01-DEC-14:20 | -0.8 | -3.3 | 0.276646E+09 | 454.00 | 01-DEC-14:30 | -0.9 | -3.4 |
Annual Sum or Average | 0.369532E+11 | 0.401741E+10 | ||||||||
Minimum of Months | 0.155452E+09 | 2902.67 | -0.8 | -3.3 | 0.259478E+09 | 432.09 | -0.9 | -3.4 | ||
Maximum of Months | 0.762511E+10 | 16380.91 | 31.10 | 26.10 | 0.436308E+09 | 549.51 | 30.60 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47070447.89 | 1834.10 | 12-JAN-16:00 | 2.80 | 1.13 | 0.192247E+09 | 257.56 | 19-JAN-14:39 | -23.0 | -23.3 |
February | 0.134264E+09 | 2323.51 | 24-FEB-16:40 | 7.57 | 5.38 | 0.175237E+09 | 299.22 | 24-FEB-16:49 | 7.38 | 5.26 |
March | 0.483673E+09 | 2266.85 | 23-MAR-16:00 | 17.20 | 10.15 | 0.212000E+09 | 290.49 | 23-MAR-15:00 | 17.20 | 10.15 |
April | 0.133689E+10 | 6903.55 | 16-APR-15:59 | 28.90 | 20.59 | 0.196067E+09 | 347.82 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.269815E+10 | 5364.21 | 31-MAY-16:00 | 28.30 | 18.78 | 0.225767E+09 | 347.84 | 31-MAY-13:20 | 28.30 | 18.78 |
June | 0.425783E+10 | 12924.86 | 25-JUN-16:51 | 31.70 | 21.68 | 0.251743E+09 | 347.85 | 27-JUN-09:20 | 26.87 | 21.57 |
July | 0.489668E+10 | 8812.92 | 02-JUL-18:02 | 28.12 | 21.02 | 0.246794E+09 | 347.85 | 05-JUL-09:20 | 23.33 | 20.37 |
August | 0.510972E+10 | 8028.23 | 05-AUG-17:07 | 25.32 | 17.94 | 0.277789E+09 | 347.85 | 30-AUG-13:20 | 22.77 | 17.06 |
September | 0.377071E+10 | 12009.63 | 04-SEP-17:12 | 21.67 | 14.30 | 0.227353E+09 | 347.86 | 12-SEP-13:20 | 21.67 | 16.01 |
October | 0.198235E+10 | 4226.43 | 11-OCT-16:00 | 17.80 | 11.96 | 0.208574E+09 | 338.68 | 20-OCT-15:30 | 22.30 | 13.06 |
November | 0.825358E+09 | 2731.97 | 03-NOV-15:40 | 15.37 | 9.43 | 0.195309E+09 | 337.13 | 03-NOV-15:50 | 15.18 | 9.38 |
December | 0.108360E+09 | 1933.45 | 01-DEC-15:40 | -1.5 | -3.9 | 0.186321E+09 | 265.66 | 01-DEC-15:50 | -1.6 | -4.0 |
Annual Sum or Average | 0.256511E+11 | 0.259520E+10 | ||||||||
Minimum of Months | 47070447.89 | 1834.10 | -1.5 | -3.9 | 0.175237E+09 | 257.56 | -23.0 | -23.3 | ||
Maximum of Months | 0.510972E+10 | 12924.86 | 31.70 | 21.68 | 0.277789E+09 | 347.86 | 28.30 | 21.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49003675.69 | 3054.13 | 07-JAN-17:01 | -20.1 | -20.6 | 0.303788E+09 | 406.84 | 18-JAN-10:39 | -13.7 | -14.1 |
February | 0.118214E+09 | 3072.31 | 04-FEB-17:01 | -20.1 | -20.6 | 0.276144E+09 | 406.84 | 03-FEB-14:09 | -20.1 | -20.6 |
March | 0.962757E+09 | 3236.64 | 28-MAR-15:30 | 16.40 | 10.50 | 0.334973E+09 | 441.45 | 24-MAR-13:00 | 16.40 | 10.50 |
April | 0.243566E+10 | 5568.58 | 18-APR-15:00 | 28.30 | 20.65 | 0.311297E+09 | 549.49 | 18-APR-13:20 | 28.30 | 20.65 |
May | 0.496756E+10 | 6256.81 | 31-MAY-15:00 | 30.00 | 19.70 | 0.376868E+09 | 549.49 | 31-MAY-13:20 | 30.00 | 19.70 |
June | 0.635901E+10 | 7233.35 | 26-JUN-14:30 | 31.40 | 21.97 | 0.409231E+09 | 549.51 | 21-JUN-13:20 | 31.40 | 21.97 |
July | 0.661765E+10 | 6716.90 | 03-JUL-13:40 | 29.23 | 24.20 | 0.391416E+09 | 549.50 | 18-JUL-13:20 | 24.07 | 16.16 |
August | 0.654988E+10 | 7171.46 | 04-AUG-15:30 | 33.90 | 25.83 | 0.433981E+09 | 549.50 | 30-AUG-13:20 | 22.77 | 17.06 |
September | 0.471198E+10 | 6407.92 | 11-SEP-14:00 | 28.90 | 20.23 | 0.350539E+09 | 549.49 | 08-SEP-13:20 | 28.90 | 20.23 |
October | 0.230080E+10 | 3556.97 | 20-OCT-15:40 | 21.97 | 12.95 | 0.316463E+09 | 468.89 | 20-OCT-13:00 | 21.97 | 12.95 |
November | 0.103756E+10 | 3311.56 | 03-NOV-15:20 | 15.73 | 9.52 | 0.306281E+09 | 452.42 | 03-NOV-13:00 | 15.73 | 9.52 |
December | 27431997.13 | 3021.05 | 09-DEC-17:01 | -19.4 | -19.8 | 0.293929E+09 | 406.83 | 11-DEC-10:50 | -20.2 | -20.9 |
Annual Sum or Average | 0.361375E+11 | 0.410491E+10 | ||||||||
Minimum of Months | 27431997.13 | 3021.05 | -20.1 | -20.6 | 0.276144E+09 | 406.83 | -20.2 | -20.9 | ||
Maximum of Months | 0.661765E+10 | 7233.35 | 33.90 | 25.83 | 0.433981E+09 | 549.51 | 31.40 | 21.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58340088.40 | 2238.10 | 13-JAN-11:03 | 2.48 | 0.68 | 0.141059E+09 | 291.90 | 13-JAN-11:09 | 2.48 | 0.68 |
February | 0.186744E+09 | 3283.23 | 24-FEB-11:02 | 5.68 | 2.52 | 0.129141E+09 | 356.08 | 24-FEB-11:09 | 5.68 | 2.52 |
March | 0.863211E+09 | 3856.38 | 28-MAR-10:05 | 10.47 | 6.54 | 0.161845E+09 | 356.45 | 28-MAR-10:09 | 10.47 | 6.54 |
April | 0.188485E+10 | 8102.52 | 18-APR-10:05 | 25.78 | 20.58 | 0.155135E+09 | 356.45 | 18-APR-10:09 | 25.78 | 20.58 |
May | 0.372786E+10 | 8766.18 | 31-MAY-10:05 | 27.38 | 19.40 | 0.189503E+09 | 356.46 | 04-MAY-10:09 | 27.38 | 19.40 |
June | 0.527765E+10 | 12489.20 | 11-JUN-10:52 | 30.60 | 22.57 | 0.196104E+09 | 356.47 | 01-JUN-10:09 | 30.60 | 22.57 |
July | 0.563015E+10 | 16943.09 | 30-JUL-09:22 | 23.35 | 19.20 | 0.187465E+09 | 356.46 | 18-JUL-10:09 | 23.35 | 19.20 |
August | 0.532951E+10 | 9069.30 | 27-AUG-08:52 | 22.80 | 19.47 | 0.208019E+09 | 356.46 | 08-AUG-10:09 | 22.80 | 19.47 |
September | 0.372801E+10 | 11374.28 | 04-SEP-08:42 | 15.63 | 12.89 | 0.173795E+09 | 356.47 | 06-SEP-10:09 | 25.97 | 18.78 |
October | 0.152783E+10 | 4446.31 | 20-OCT-10:05 | 15.68 | 10.42 | 0.157236E+09 | 356.46 | 19-OCT-12:09 | 15.68 | 10.42 |
November | 0.603663E+09 | 3590.18 | 03-NOV-14:02 | 16.10 | 10.33 | 0.144386E+09 | 356.44 | 03-NOV-14:09 | 16.10 | 10.33 |
December | 55772574.30 | 2056.28 | 09-DEC-17:01 | -19.4 | -19.8 | 0.136459E+09 | 274.30 | 01-DEC-11:09 | -19.4 | -19.8 |
Annual Sum or Average | 0.288736E+11 | 0.198015E+10 | ||||||||
Minimum of Months | 55772574.30 | 2056.28 | -19.4 | -19.8 | 0.129141E+09 | 274.30 | -19.4 | -19.8 | ||
Maximum of Months | 0.563015E+10 | 16943.09 | 30.60 | 22.57 | 0.208019E+09 | 356.47 | 30.60 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101616E+10 | 5073.71 | 12-JAN-12:30 | 1.95 | 0.38 | 0.314538E+09 | 549.49 | 12-JAN-14:00 | 2.80 | 1.13 |
February | 0.138071E+10 | 7951.90 | 24-FEB-13:40 | 7.43 | 4.81 | 0.290734E+09 | 549.50 | 24-FEB-14:20 | 7.97 | 5.32 |
March | 0.244344E+10 | 8063.22 | 24-MAR-13:07 | 12.38 | 6.48 | 0.361716E+09 | 549.50 | 22-MAR-13:20 | 12.38 | 6.48 |
April | 0.367933E+10 | 11047.43 | 18-APR-12:40 | 27.40 | 20.72 | 0.336126E+09 | 549.50 | 13-APR-13:20 | 27.40 | 20.72 |
May | 0.561818E+10 | 9673.12 | 30-MAY-13:20 | 26.70 | 19.86 | 0.393855E+09 | 549.50 | 22-MAY-13:00 | 26.70 | 19.86 |
June | 0.716810E+10 | 14482.87 | 25-JUN-13:22 | 31.95 | 22.61 | 0.412164E+09 | 549.51 | 21-JUN-13:20 | 31.95 | 22.61 |
July | 0.773468E+10 | 13408.11 | 30-JUL-15:22 | 27.50 | 19.21 | 0.393754E+09 | 549.50 | 11-JUL-13:00 | 27.50 | 19.21 |
August | 0.838545E+10 | 12542.51 | 29-AUG-13:30 | 23.60 | 16.39 | 0.440223E+09 | 549.52 | 07-AUG-13:09 | 23.60 | 16.39 |
September | 0.688020E+10 | 22966.06 | 04-SEP-14:42 | 22.12 | 14.37 | 0.370305E+09 | 549.52 | 12-SEP-13:20 | 21.67 | 16.01 |
October | 0.418837E+10 | 11275.93 | 20-OCT-13:05 | 21.93 | 12.68 | 0.359735E+09 | 549.51 | 20-OCT-13:20 | 22.07 | 12.75 |
November | 0.197613E+10 | 10160.11 | 03-NOV-13:07 | 15.68 | 10.94 | 0.319474E+09 | 549.49 | 03-NOV-13:20 | 15.77 | 10.85 |
December | 0.107060E+10 | 6161.34 | 01-DEC-13:30 | -0.9 | -3.3 | 0.310488E+09 | 549.49 | 15-DEC-14:20 | -7.6 | -9.3 |
Annual Sum or Average | 0.515413E+11 | 0.430311E+10 | ||||||||
Minimum of Months | 0.101616E+10 | 5073.71 | -0.9 | -3.3 | 0.290734E+09 | 549.49 | -7.6 | -9.3 | ||
Maximum of Months | 0.838545E+10 | 22966.06 | 31.95 | 22.61 | 0.440223E+09 | 549.52 | 31.95 | 22.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105894E+09 | 2261.29 | 12-JAN-15:50 | 2.80 | 1.13 | 0.192580E+09 | 275.17 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.299396E+09 | 2941.71 | 24-FEB-16:40 | 7.57 | 5.38 | 0.176438E+09 | 331.05 | 24-FEB-16:49 | 7.38 | 5.26 |
March | 0.101923E+10 | 3012.97 | 23-MAR-16:00 | 17.20 | 10.15 | 0.216006E+09 | 333.98 | 22-MAR-15:00 | 17.20 | 10.15 |
April | 0.233111E+10 | 12354.41 | 15-APR-17:06 | 29.72 | 18.80 | 0.203827E+09 | 347.84 | 18-APR-13:20 | 27.57 | 20.63 |
May | 0.400862E+10 | 12917.69 | 14-MAY-17:12 | 21.13 | 15.93 | 0.240538E+09 | 347.85 | 05-MAY-13:20 | 21.13 | 15.93 |
June | 0.543730E+10 | 17308.50 | 25-JUN-16:42 | 31.78 | 21.74 | 0.257180E+09 | 347.86 | 21-JUN-13:20 | 31.78 | 21.74 |
July | 0.581093E+10 | 17615.16 | 30-JUL-16:42 | 26.38 | 18.69 | 0.246625E+09 | 347.85 | 18-JUL-13:20 | 26.38 | 18.69 |
August | 0.573559E+10 | 17239.35 | 13-AUG-16:32 | 25.20 | 20.49 | 0.273990E+09 | 347.85 | 30-AUG-13:20 | 22.77 | 17.06 |
September | 0.400585E+10 | 16729.27 | 04-SEP-16:02 | 22.20 | 14.41 | 0.222512E+09 | 347.86 | 12-SEP-13:20 | 21.67 | 16.01 |
October | 0.194596E+10 | 5480.30 | 20-OCT-15:30 | 22.30 | 13.06 | 0.208048E+09 | 343.81 | 20-OCT-13:00 | 22.30 | 13.06 |
November | 0.824607E+09 | 3568.53 | 03-NOV-15:30 | 15.55 | 9.47 | 0.194602E+09 | 338.68 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.170928E+09 | 2256.31 | 01-DEC-15:40 | -1.5 | -3.9 | 0.186361E+09 | 275.19 | 01-DEC-15:50 | -1.6 | -4.0 |
Annual Sum or Average | 0.316954E+11 | 0.261871E+10 | ||||||||
Minimum of Months | 0.105894E+09 | 2256.31 | -1.5 | -3.9 | 0.176438E+09 | 275.17 | -1.6 | -4.0 | ||
Maximum of Months | 0.581093E+10 | 17615.16 | 31.78 | 21.74 | 0.273990E+09 | 347.86 | 31.78 | 21.74 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226781E+09 | 14412.99 | 02-JAN-05:01 | -4.5 |
February | 28616814.89 | 10388.19 | 06-FEB-06:01 | -15.0 |
March | 3160899.65 | 8529.79 | 06-MAR-07:01 | -12.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 8273888.76 | 9644.00 | 27-NOV-06:01 | -9.4 |
December | 21269425.05 | 9897.98 | 26-DEC-06:01 | -5.8 |
Annual Sum or Average | 0.288102E+09 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.226781E+09 | 14412.99 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218537E+11 | 32070.21 | 06-JAN-06:07 | -26.8 |
February | 0.145293E+11 | 34192.30 | 02-FEB-05:12 | -36.3 |
March | 0.779379E+10 | 28896.74 | 06-MAR-06:08 | -14.1 |
April | 0.346212E+10 | 22215.99 | 03-APR-05:13 | -7.2 |
May | 0.608198E+09 | 12805.81 | 03-MAY-05:02 | 1.38 |
June | 0.244039E+09 | 8912.98 | 01-JUN-05:03 | 5.65 |
July | 89701776.31 | 8050.35 | 24-JUL-05:03 | 10.28 |
August | 0.171303E+09 | 8064.44 | 07-AUG-05:02 | 8.80 |
September | 0.117342E+10 | 12255.97 | 30-SEP-06:03 | 0.60 |
October | 0.321617E+10 | 17569.04 | 16-OCT-05:03 | 0.48 |
November | 0.100664E+11 | 30413.55 | 28-NOV-06:06 | -18.2 |
December | 0.178834E+11 | 30349.40 | 11-DEC-06:09 | -22.1 |
Annual Sum or Average | 0.810915E+11 | |||
Minimum of Months | 89701776.31 | 8050.35 | -36.3 | |
Maximum of Months | 0.218537E+11 | 34192.30 | 10.28 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.607086E+10 | 13300.29 | 30-JAN-08:08 | -29.3 |
February | 0.372804E+10 | 12748.31 | 06-FEB-08:03 | -14.8 |
March | 0.224492E+10 | 11339.20 | 06-MAR-06:08 | -14.1 |
April | 0.744582E+09 | 10440.87 | 03-APR-06:11 | -7.0 |
May | 65498377.90 | 5276.49 | 21-MAY-14:37 | 17.60 |
June | 17115608.83 | 3132.33 | 18-JUN-12:32 | 26.70 |
July | 19008702.84 | 3756.35 | 23-JUL-14:20 | 22.40 |
August | 18519912.71 | 3723.26 | 27-AUG-14:17 | 26.70 |
September | 86895287.10 | 4986.43 | 04-SEP-15:22 | 22.20 |
October | 0.775963E+09 | 5693.20 | 01-OCT-12:13 | 18.43 |
November | 0.257379E+10 | 12877.31 | 27-NOV-06:07 | -9.4 |
December | 0.463789E+10 | 13264.12 | 11-DEC-08:05 | -21.7 |
Annual Sum or Average | 0.209831E+11 | |||
Minimum of Months | 17115608.83 | 3132.33 | -29.3 | |
Maximum of Months | 0.607086E+10 | 13300.29 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416891E+10 | 11531.24 | 02-JAN-08:16 | -7.6 |
February | 0.240187E+10 | 8586.09 | 06-FEB-06:12 | -15.0 |
March | 0.124613E+10 | 6638.24 | 06-MAR-08:14 | -11.5 |
April | 0.322720E+09 | 4863.03 | 03-APR-07:50 | -6.2 |
May | 3364664.03 | 2901.88 | 14-MAY-16:36 | 21.70 |
June | 5138389.66 | 3408.86 | 18-JUN-13:38 | 28.90 |
July | 9328623.24 | 3610.37 | 23-JUL-14:27 | 22.50 |
August | 17238710.37 | 3705.06 | 27-AUG-12:48 | 26.60 |
September | 13112795.40 | 4005.24 | 10-SEP-10:02 | 24.50 |
October | 82710964.12 | 4585.57 | 01-OCT-12:42 | 18.63 |
November | 0.138378E+10 | 7935.19 | 27-NOV-07:01 | -9.4 |
December | 0.283325E+10 | 7810.21 | 11-DEC-08:23 | -21.7 |
Annual Sum or Average | 0.124876E+11 | |||
Minimum of Months | 3364664.03 | 2901.88 | -21.7 | |
Maximum of Months | 0.416891E+10 | 11531.24 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165605E+10 | 22547.59 | 02-JAN-05:01 | -4.5 |
February | 0.752677E+09 | 21216.06 | 06-FEB-05:01 | -14.5 |
March | 0.220575E+09 | 19871.50 | 06-MAR-05:01 | -15.4 |
April | 65976006.27 | 18478.44 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 2942261.62 | 15266.87 | 16-OCT-06:02 | -0.4 |
November | 0.416820E+09 | 21214.87 | 27-NOV-05:01 | -9.4 |
December | 0.827385E+09 | 21389.67 | 11-DEC-05:01 | -22.2 |
Annual Sum or Average | 0.394243E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.165605E+10 | 22547.59 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.726540E+10 | 37158.66 | 23-JAN-05:11 | -18.0 |
February | 0.413672E+10 | 36491.37 | 13-FEB-05:11 | -5.0 |
March | 0.174295E+10 | 35956.57 | 06-MAR-05:01 | -15.4 |
April | 0.491328E+09 | 35413.80 | 03-APR-04:01 | -6.8 |
May | 14943223.05 | 25877.74 | 02-MAY-06:03 | 2.30 |
June | 1050820.10 | 3380.27 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 43944272.81 | 28663.08 | 30-SEP-05:01 | 0.10 |
October | 0.354430E+09 | 31398.61 | 16-OCT-05:01 | 0.48 |
November | 0.253805E+10 | 36008.09 | 27-NOV-05:01 | -9.4 |
December | 0.506563E+10 | 36780.08 | 26-DEC-05:11 | -4.5 |
Annual Sum or Average | 0.216544E+11 | |||
Minimum of Months | 0.00 | 0.00 | -18.0 | |
Maximum of Months | 0.726540E+10 | 37158.66 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128827E+11 | 20832.10 | 23-JAN-05:11 | -18.0 |
February | 0.801484E+10 | 19721.27 | 02-FEB-01:31 | -34.2 |
March | 0.388165E+10 | 19372.36 | 13-MAR-01:02 | -7.9 |
April | 0.130377E+10 | 18512.43 | 02-APR-22:33 | -4.6 |
May | 85620508.32 | 15508.28 | 02-MAY-05:11 | 2.20 |
June | 14829547.89 | 6702.66 | 05-JUN-05:13 | 9.23 |
July | 348697.32 | 1715.92 | 24-JUL-06:03 | 12.35 |
August | 4707655.32 | 4335.51 | 07-AUG-06:03 | 8.87 |
September | 0.216522E+09 | 15048.80 | 30-SEP-05:01 | 0.10 |
October | 0.102631E+10 | 17642.67 | 16-OCT-04:21 | 1.35 |
November | 0.496746E+10 | 19655.55 | 26-NOV-02:41 | -24.9 |
December | 0.968314E+10 | 21240.71 | 09-DEC-05:31 | -22.8 |
Annual Sum or Average | 0.420819E+11 | |||
Minimum of Months | 348697.32 | 1715.92 | -34.2 | |
Maximum of Months | 0.128827E+11 | 21240.71 | 12.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.778138E+10 | 13491.45 | 23-JAN-05:11 | -18.0 |
February | 0.456889E+10 | 12716.33 | 02-FEB-01:31 | -34.2 |
March | 0.212492E+10 | 12512.92 | 13-MAR-01:02 | -7.9 |
April | 0.730626E+09 | 11945.86 | 02-APR-22:33 | -4.6 |
May | 28666502.22 | 9972.87 | 02-MAY-05:11 | 2.20 |
June | 7738580.19 | 4078.14 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 692386.52 | 1848.29 | 25-AUG-06:03 | 13.40 |
September | 0.106164E+09 | 9697.06 | 30-SEP-05:01 | 0.10 |
October | 0.543959E+09 | 11353.83 | 23-OCT-04:01 | -1.9 |
November | 0.302247E+10 | 12681.70 | 26-NOV-02:41 | -24.9 |
December | 0.592882E+10 | 13746.22 | 09-DEC-05:31 | -22.8 |
Annual Sum or Average | 0.248443E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.2 | |
Maximum of Months | 0.778138E+10 | 13746.22 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.955363E+10 | 20358.56 | 23-JAN-05:11 | -18.0 |
February | 0.558327E+10 | 19225.16 | 06-FEB-02:61 | -17.9 |
March | 0.298113E+10 | 19021.85 | 13-MAR-03:42 | -9.2 |
April | 0.112089E+10 | 18183.24 | 02-APR-22:33 | -4.6 |
May | 86943105.20 | 15136.66 | 02-MAY-05:11 | 2.20 |
June | 16788046.66 | 7642.68 | 03-JUN-05:12 | 5.97 |
July | 1673652.59 | 3409.04 | 24-JUL-06:03 | 12.35 |
August | 4508873.37 | 4473.52 | 07-AUG-06:03 | 8.87 |
September | 0.169559E+09 | 14832.04 | 30-SEP-05:01 | 0.10 |
October | 0.707903E+09 | 17124.19 | 23-OCT-04:01 | -1.9 |
November | 0.379051E+10 | 19259.11 | 26-NOV-02:41 | -24.9 |
December | 0.756770E+10 | 20812.00 | 09-DEC-05:31 | -22.8 |
Annual Sum or Average | 0.315845E+11 | |||
Minimum of Months | 1673652.59 | 3409.04 | -24.9 | |
Maximum of Months | 0.955363E+10 | 20812.00 | 12.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.797436E+10 | 13632.41 | 23-JAN-05:11 | -18.0 |
February | 0.480899E+10 | 12935.94 | 02-FEB-01:31 | -34.2 |
March | 0.233588E+10 | 12714.55 | 13-MAR-01:02 | -7.9 |
April | 0.774778E+09 | 12149.86 | 02-APR-22:33 | -4.6 |
May | 59095944.15 | 10168.24 | 02-MAY-05:11 | 2.20 |
June | 11491592.88 | 5169.15 | 03-JUN-05:12 | 5.97 |
July | 738017.28 | 2052.15 | 12-JUL-06:03 | 14.18 |
August | 2595553.69 | 2815.59 | 07-AUG-06:03 | 8.87 |
September | 0.141359E+09 | 9846.15 | 30-SEP-05:01 | 0.10 |
October | 0.614239E+09 | 11570.59 | 16-OCT-04:21 | 1.35 |
November | 0.312034E+10 | 12892.33 | 26-NOV-02:41 | -24.9 |
December | 0.608283E+10 | 14028.62 | 09-DEC-05:31 | -22.8 |
Annual Sum or Average | 0.259267E+11 | |||
Minimum of Months | 738017.28 | 2052.15 | -34.2 | |
Maximum of Months | 0.797436E+10 | 14028.62 | 14.18 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.985742E+10 | 15822.10 | 30-JAN-05:11 | -28.0 |
February | 0.647752E+10 | 15019.58 | 03-FEB-04:42 | -33.9 |
March | 0.358768E+10 | 14336.73 | 06-MAR-05:11 | -15.2 |
April | 0.134104E+10 | 13870.07 | 03-APR-04:11 | -6.9 |
May | 77948051.09 | 11314.68 | 02-MAY-05:11 | 2.20 |
June | 5782193.08 | 6053.11 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 20894437.39 | 9563.64 | 29-SEP-06:02 | 0.10 |
October | 0.148438E+09 | 10718.49 | 16-OCT-05:01 | 0.48 |
November | 0.238800E+10 | 14176.32 | 26-NOV-04:31 | -25.0 |
December | 0.599802E+10 | 14518.78 | 11-DEC-02:61 | -21.7 |
Annual Sum or Average | 0.299027E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.985742E+10 | 15822.10 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.577515E+10 | 10176.85 | 30-JAN-05:11 | -28.0 |
February | 0.348424E+10 | 9606.81 | 03-FEB-04:02 | -33.9 |
March | 0.175664E+10 | 9241.53 | 06-MAR-05:11 | -15.2 |
April | 0.647223E+09 | 8968.57 | 03-APR-04:11 | -6.9 |
May | 14297635.58 | 7090.20 | 02-MAY-05:11 | 2.20 |
June | 2187231.68 | 3636.66 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 7099079.15 | 6159.17 | 29-SEP-06:02 | 0.10 |
October | 54279726.35 | 6763.53 | 24-OCT-05:11 | 2.07 |
November | 0.137622E+10 | 9123.55 | 26-NOV-04:31 | -25.0 |
December | 0.353470E+10 | 9353.67 | 11-DEC-02:61 | -21.7 |
Annual Sum or Average | 0.166520E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.577515E+10 | 10176.85 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120300E+11 | 20093.44 | 31-JAN-07:11 | -30.4 |
February | 0.791738E+10 | 21508.57 | 02-FEB-07:10 | -36.7 |
March | 0.590136E+10 | 16484.03 | 06-MAR-07:50 | -12.3 |
April | 0.302255E+10 | 15089.85 | 03-APR-06:50 | -6.8 |
May | 0.782741E+09 | 11490.03 | 02-MAY-06:10 | 2.30 |
June | 0.263300E+09 | 9846.15 | 02-JUN-06:03 | 7.30 |
July | 16009651.84 | 3423.94 | 24-JUL-06:03 | 12.35 |
August | 45815972.91 | 6086.25 | 07-AUG-06:07 | 8.87 |
September | 0.489535E+09 | 11512.09 | 29-SEP-06:10 | 0.10 |
October | 0.130259E+10 | 12382.24 | 23-OCT-06:10 | -3.0 |
November | 0.440088E+10 | 17146.99 | 28-NOV-07:50 | -16.9 |
December | 0.861102E+10 | 18773.52 | 11-DEC-08:00 | -21.7 |
Annual Sum or Average | 0.447832E+11 | |||
Minimum of Months | 16009651.84 | 3423.94 | -36.7 | |
Maximum of Months | 0.120300E+11 | 21508.57 | 12.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594535E+10 | 10376.22 | 30-JAN-05:11 | -28.0 |
February | 0.361966E+10 | 9787.98 | 03-FEB-04:02 | -33.9 |
March | 0.195643E+10 | 9397.38 | 06-MAR-05:11 | -15.2 |
April | 0.606275E+09 | 9158.86 | 03-APR-04:11 | -6.9 |
May | 35444000.37 | 7358.73 | 02-MAY-05:11 | 2.20 |
June | 3835671.29 | 3852.37 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 13674701.70 | 6283.62 | 29-SEP-06:02 | 0.10 |
October | 62213019.16 | 7030.69 | 16-OCT-05:01 | 0.48 |
November | 0.143645E+10 | 9313.95 | 26-NOV-04:31 | -25.0 |
December | 0.364963E+10 | 9573.06 | 09-DEC-05:31 | -22.8 |
Annual Sum or Average | 0.173290E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.594535E+10 | 10376.22 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.904845E+10 | 15418.65 | 30-JAN-04:51 | -27.8 |
February | 0.509453E+10 | 15545.28 | 01-FEB-05:11 | -30.4 |
March | 0.210284E+10 | 14692.99 | 06-MAR-04:42 | -15.7 |
April | 0.536682E+09 | 14243.98 | 03-APR-04:11 | -6.9 |
May | 14879673.66 | 10968.56 | 02-MAY-05:11 | 2.20 |
June | 2957840.86 | 5384.58 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 39602691.35 | 10984.32 | 30-SEP-05:01 | 0.10 |
October | 0.248800E+09 | 11990.78 | 16-OCT-05:01 | 0.48 |
November | 0.270503E+10 | 14906.68 | 26-NOV-04:41 | -25.0 |
December | 0.603884E+10 | 15210.59 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.258326E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.4 | |
Maximum of Months | 0.904845E+10 | 15545.28 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535906E+10 | 10290.70 | 30-JAN-04:51 | -27.8 |
February | 0.280316E+10 | 10395.99 | 01-FEB-05:11 | -30.4 |
March | 0.111284E+10 | 9806.61 | 06-MAR-04:42 | -15.7 |
April | 0.291858E+09 | 9495.69 | 03-APR-04:11 | -6.9 |
May | 2778535.72 | 7227.31 | 02-MAY-05:11 | 2.20 |
June | 1529175.39 | 3372.01 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 18993748.84 | 7256.90 | 30-SEP-05:01 | 0.10 |
October | 0.130833E+09 | 7920.05 | 16-OCT-05:01 | 0.48 |
November | 0.163258E+10 | 9947.42 | 26-NOV-04:41 | -25.0 |
December | 0.365929E+10 | 10152.58 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.150129E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.4 | |
Maximum of Months | 0.535906E+10 | 10395.99 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.610375E+10 | 14987.96 | 30-JAN-04:51 | -27.8 |
February | 0.314799E+10 | 15064.60 | 01-FEB-05:11 | -30.4 |
March | 0.146699E+10 | 14303.00 | 06-MAR-04:42 | -15.7 |
April | 0.428399E+09 | 13935.60 | 03-APR-04:11 | -6.9 |
May | 14376280.16 | 10628.53 | 02-MAY-05:11 | 2.20 |
June | 2957022.72 | 5336.69 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 29001131.39 | 10699.13 | 30-SEP-05:01 | 0.10 |
October | 0.155899E+09 | 11541.78 | 16-OCT-05:01 | 0.48 |
November | 0.191799E+10 | 14533.94 | 26-NOV-04:01 | -25.0 |
December | 0.447621E+10 | 14802.46 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.177436E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.4 | |
Maximum of Months | 0.610375E+10 | 15064.60 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.554041E+10 | 10610.28 | 30-JAN-04:51 | -27.8 |
February | 0.299862E+10 | 10739.76 | 01-FEB-05:11 | -30.4 |
March | 0.124036E+10 | 10053.69 | 06-MAR-04:42 | -15.7 |
April | 0.306483E+09 | 9783.52 | 03-APR-04:11 | -6.9 |
May | 11937863.22 | 7490.42 | 02-MAY-05:11 | 2.20 |
June | 2472404.63 | 3436.10 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 29222721.63 | 7570.30 | 30-SEP-05:01 | 0.10 |
October | 0.150891E+09 | 8203.56 | 16-OCT-05:01 | 0.48 |
November | 0.170760E+10 | 10254.23 | 26-NOV-04:41 | -25.0 |
December | 0.380925E+10 | 10477.27 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.157972E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.4 | |
Maximum of Months | 0.554041E+10 | 10739.76 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285402E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207344E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173637E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21139184.41 | 0.104997E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4914429.91 | 0.550257E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70870681.69 | 0.321716E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30829554.73 | 0.224144E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29016579.08 | 0.307884E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29385596.21 | 0.497052E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 106852.22 | 0.970136E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173792E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237644E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186263E+09 | 0.146993E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224144E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70870681.69 | 0.285402E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190237E+10 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138317E+10 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116361E+10 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11986603.73 | 0.720268E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2602767.38 | 0.386450E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40553336.92 | 0.223705E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16326801.34 | 0.160578E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16277164.73 | 0.214349E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15226670.79 | 0.347778E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15837.21 | 0.664582E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116135E+10 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158543E+10 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102989E+09 | 0.991364E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160578E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40553336.92 | 0.190237E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286616E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210183E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178120E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13588650.61 | 0.109804E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3992165.93 | 0.574394E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63744689.46 | 0.326199E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24823023.26 | 0.231296E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22009157.02 | 0.325860E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16300968.98 | 0.539091E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.94 | 0.105491E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177407E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240668E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144459E+09 | 0.150797E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231296E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63744689.46 | 0.286616E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190220E+10 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138773E+10 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116744E+10 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8328202.13 | 0.731357E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2754220.53 | 0.389015E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37744648.79 | 0.224181E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14217186.89 | 0.165173E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15047694.57 | 0.222464E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13464414.77 | 0.351328E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.57 | 0.664436E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116338E+10 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158541E+10 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91556561.26 | 0.995411E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165173E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37744648.79 | 0.190220E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152805E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111793E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937075E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13605581.96 | 0.551680E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3693521.60 | 0.280788E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40787866.83 | 0.166106E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17416304.33 | 0.120460E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14001706.13 | 0.178414E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14762905.10 | 0.293382E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45052.28 | 0.589484E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983957E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129779E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104313E+09 | 0.804510E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120460E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40787866.83 | 0.152805E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101895E+10 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748355E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629985E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7109588.46 | 0.381660E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1591585.44 | 0.204603E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21377130.12 | 0.121795E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8215013.29 | 91034173.70 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7601541.67 | 0.129245E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7017406.55 | 0.211955E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1479.83 | 0.408922E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659598E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867072E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52913745.36 | 0.547318E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91034173.70 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21377130.12 | 0.101895E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100981E+11 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761846E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653100E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26968102.52 | 0.398612E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71770454.46 | 0.204098E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293002E+09 | 0.107365E+10 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241562E+09 | 0.496817E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335636E+09 | 0.824464E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189756E+09 | 0.195507E+10 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395973E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577512E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.807514E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115869E+10 | 0.524347E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496817E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335636E+09 | 0.100981E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101915E+10 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750208E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632033E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4646153.26 | 0.389179E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1541304.58 | 0.204823E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20093415.85 | 0.121812E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7360750.49 | 95938563.59 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7061931.03 | 0.135269E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6359906.82 | 0.213213E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407624E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660652E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867038E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47063462.05 | 0.549694E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95938563.59 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20093415.85 | 0.101915E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239235E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175755E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150258E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17139782.49 | 0.923444E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3622147.00 | 0.493953E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56913678.30 | 0.292861E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22988818.83 | 0.208779E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21022695.72 | 0.287187E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22125491.70 | 0.456819E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29462.15 | 0.893204E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150213E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201362E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143842E+09 | 0.127245E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208779E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56913678.30 | 0.239235E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159291E+10 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117344E+10 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101250E+10 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9637996.56 | 0.637025E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2031965.44 | 0.349054E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32900430.91 | 0.202506E+09 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12485938.52 | 0.147179E+09 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12012707.97 | 0.198101E+09 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11563505.54 | 0.320451E+09 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.87 | 0.617179E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100549E+10 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134227E+10 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80632558.82 | 0.859811E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147179E+09 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32900430.91 | 0.159291E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241221E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179596E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155060E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10728867.84 | 0.967724E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3125874.18 | 0.515599E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50718675.07 | 0.295848E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18490086.94 | 0.214352E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16294965.56 | 0.301250E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12028593.53 | 0.493797E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968797E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154557E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205569E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111387E+09 | 0.131174E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214352E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50718675.07 | 0.241221E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159452E+10 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117783E+10 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101121E+10 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6631848.14 | 0.641676E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2215893.88 | 0.346207E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30556617.08 | 0.201700E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10968601.85 | 0.150968E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11527767.72 | 0.203840E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10398894.52 | 0.319948E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610056E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100543E+10 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134340E+10 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72299623.19 | 0.860680E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150968E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30556617.08 | 0.159452E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320851E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242282E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211663E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15525258.18 | 0.133518E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3207041.09 | 0.718180E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58698671.85 | 0.418246E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17799018.17 | 0.305823E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15561613.19 | 0.430013E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15049212.34 | 0.689991E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134669E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214764E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278120E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125841E+09 | 0.179209E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305823E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58698671.85 | 0.320851E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401598E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301156E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261660E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20645967.01 | 0.164544E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3934398.66 | 0.899820E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76736808.03 | 0.522662E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23359004.91 | 0.378325E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22346971.65 | 0.524684E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23092630.85 | 0.828645E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158822E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260191E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343565E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170116E+09 | 0.220695E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378325E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76736808.03 | 0.401598E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414210E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305273E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260303E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11191528.94 | 0.161180E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1980610.17 | 0.884353E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53261744.12 | 0.489331E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10292244.18 | 0.352502E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12647581.09 | 0.482822E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12122096.62 | 0.757523E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146581E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255912E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346311E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101496E+09 | 0.218642E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352502E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53261744.12 | 0.414210E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5618.99 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3918.92 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2973.31 | 20-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 765.49 | 15-APR-17:01 | 2238.46 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.64 | 29-MAY-10:40 | 1380.02 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 805.76 | 18-JUN-15:50 | 1135.15 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.98 | 02-JUL-15:50 | 519.53 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.83 | 13-AUG-14:10 | 687.86 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 562.93 | 17-SEP-15:10 | 1018.62 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 | 20-OCT-15:00 | 1403.47 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4291.05 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6590.64 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.53 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 805.76 | 6590.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3745.94 | 29-JAN-10:58 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2611.15 | 10-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1983.04 | 20-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.91 | 15-APR-17:01 | 1492.26 | 02-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 31-MAY-13:00 | 924.83 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 532.88 | 18-JUN-15:50 | 761.16 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.13 | 02-JUL-15:50 | 342.70 | 09-JUL-21:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.88 | 13-AUG-14:10 | 471.00 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.22 | 17-SEP-15:10 | 681.23 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 20-OCT-15:00 | 932.27 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2859.38 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.20 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.70 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 532.88 | 4393.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5641.21 | 29-JAN-10:53 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3921.33 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3036.12 | 05-MAR-14:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 630.06 | 15-APR-17:01 | 2238.47 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 31-MAY-13:00 | 1400.47 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 751.58 | 18-JUN-15:50 | 1144.77 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.32 | 02-JUL-15:50 | 525.01 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.75 | 05-AUG-17:10 | 726.98 | 06-AUG-13:50 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.38 | 17-SEP-15:10 | 1032.36 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 21-OCT-15:00 | 1443.73 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4293.55 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6589.64 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.01 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 751.58 | 6589.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3745.93 | 29-JAN-10:56 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2610.08 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1981.05 | 20-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.44 | 16-APR-12:50 | 1492.30 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 | 29-MAY-10:40 | 921.87 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 436.37 | 11-JUN-15:20 | 750.10 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.38 | 02-JUL-11:10 | 363.19 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.29 | 13-AUG-13:32 | 474.52 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.98 | 17-SEP-11:50 | 758.24 | 24-SEP-16:02 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 | 21-OCT-15:00 | 935.07 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2858.60 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.15 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.19 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 436.37 | 4393.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2983.48 | 29-JAN-10:51 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2090.71 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1598.61 | 06-MAR-05:56 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.11 | 15-APR-17:01 | 1187.29 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.07 | 05-MAY-15:00 | 749.57 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.05 | 18-JUN-16:20 | 652.40 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.32 | 02-JUL-15:30 | 263.45 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.84 | 13-AUG-14:00 | 393.00 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 301.90 | 17-SEP-15:00 | 606.75 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 20-OCT-15:00 | 913.93 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2293.61 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3499.25 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.45 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 482.11 | 3499.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1988.97 | 29-JAN-10:55 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1393.91 | 10-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1065.73 | 06-MAR-05:59 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 301.51 | 15-APR-17:01 | 791.51 | 02-APR-23:53 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 | 05-MAY-15:00 | 517.06 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.29 | 18-JUN-16:20 | 455.32 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.00 | 02-JUL-16:10 | 184.04 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.63 | 13-AUG-14:00 | 273.18 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.63 | 17-SEP-15:00 | 419.11 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 20-OCT-15:00 | 619.37 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1528.54 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2332.75 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.04 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 301.51 | 2332.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 44532.93 | 31-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 51429.02 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 27591.98 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2940.19 | 18-APR-12:00 | 22999.60 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4128.82 | 31-MAY-12:00 | 14709.69 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5846.61 | 26-JUN-16:10 | 10896.40 | 02-JUN-06:10 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4479.13 | 26-JUL-16:10 | 7051.86 | 24-JUL-06:07 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6881.20 | 04-AUG-16:10 | 10034.43 | 07-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5708.27 | 07-SEP-16:10 | 16564.83 | 29-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19514.11 | 23-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32337.98 | 28-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 36436.63 | 11-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7051.86 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6881.20 | 51429.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1988.95 | 29-JAN-10:58 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1393.41 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1065.75 | 06-MAR-05:57 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.72 | 15-APR-17:01 | 791.52 | 02-APR-23:57 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.70 | 29-MAY-10:00 | 508.08 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.40 | 11-JUN-15:00 | 438.47 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.19 | 02-JUL-11:00 | 196.77 | 09-JUL-10:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.47 | 13-AUG-13:53 | 282.64 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.30 | 17-SEP-15:00 | 417.66 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 619.54 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1528.40 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2332.62 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.77 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 240.40 | 2332.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4674.13 | 29-JAN-10:56 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3274.75 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2483.82 | 20-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 628.53 | 15-APR-17:01 | 1861.06 | 02-APR-23:53 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1240.01 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 693.53 | 18-JUN-16:00 | 1052.22 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.37 | 02-JUL-15:30 | 448.09 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.22 | 13-AUG-14:00 | 617.30 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.95 | 17-SEP-14:40 | 921.44 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 20-OCT-15:00 | 1350.49 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3583.24 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5481.46 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.09 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 693.53 | 5481.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3116.10 | 29-JAN-10:55 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2182.22 | 10-FEB-22:01 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1680.40 | 05-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 393.97 | 15-APR-17:01 | 1240.71 | 02-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 834.28 | 01-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.31 | 18-JUN-16:00 | 704.96 | 02-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.68 | 02-JUL-16:10 | 314.80 | 09-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.49 | 13-AUG-14:00 | 421.89 | 06-AUG-09:00 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.65 | 17-SEP-14:40 | 615.48 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 20-OCT-15:00 | 899.66 | 24-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2387.53 | 20-NOV-22:01 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3654.78 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.80 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 462.31 | 3654.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4680.74 | 29-JAN-10:54 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3277.17 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2637.60 | 05-MAR-14:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.06 | 15-APR-17:01 | 1861.09 | 02-APR-23:53 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1259.24 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.22 | 18-JUN-16:00 | 1060.64 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.36 | 02-JUL-16:10 | 452.89 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.61 | 04-AUG-16:40 | 631.99 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.68 | 17-SEP-15:20 | 933.60 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1384.82 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3585.31 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5481.68 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.89 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 645.22 | 5481.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3116.11 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2181.48 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1654.57 | 20-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.14 | 16-APR-13:10 | 1240.69 | 02-APR-23:55 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 827.89 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.04 | 11-JUN-15:00 | 694.48 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.20 | 02-JUL-11:30 | 312.70 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.08 | 13-AUG-13:20 | 424.25 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.90 | 17-SEP-12:00 | 658.10 | 24-SEP-16:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 899.51 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2387.30 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3654.32 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.70 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 354.04 | 3654.32 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6134.43 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4299.67 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3468.02 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.90 | 15-APR-17:01 | 2667.08 | 02-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.46 | 31-MAY-13:00 | 1814.88 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.42 | 18-JUN-16:00 | 1559.55 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.48 | 02-JUL-15:50 | 617.43 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.48 | 04-AUG-16:40 | 862.85 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.85 | 17-SEP-15:00 | 1363.17 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2095.27 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4609.69 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7462.22 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.43 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.42 | 7462.22 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 7616.58 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5396.71 | 04-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4333.77 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.23 | 15-APR-17:01 | 3199.17 | 02-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.32 | 31-MAY-13:00 | 2269.64 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 940.52 | 11-JUN-15:10 | 1933.19 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.60 | 02-JUL-15:10 | 756.35 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.65 | 13-AUG-14:00 | 1059.26 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.64 | 17-SEP-15:00 | 1686.31 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2481.85 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5751.33 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9274.15 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.35 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 940.52 | 9274.15 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 8076.85 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5710.77 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4397.64 | 20-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728.73 | 15-APR-17:01 | 3191.76 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.18 | 31-MAY-13:00 | 2024.62 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.73 | 11-JUN-15:00 | 1681.37 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.87 | 25-JUL-21:03 | 835.70 | 09-JUL-12:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.37 | 03-AUG-16:00 | 1163.66 | 06-AUG-13:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.95 | 10-SEP-15:00 | 1531.84 | 24-SEP-16:02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1975.85 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6207.65 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9306.57 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.70 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.73 | 9306.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11020.27 | 13-JAN-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11391.20 | 24-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16443.93 | 24-MAR-16:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27782.42 | 21-APR-05:01 | 4446.85 | 7591.59 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33176.15 | 30-MAY-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47634.49 | 29-JUN-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 48532.47 | 06-JUL-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 47300.73 | 14-AUG-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48540.60 | 11-SEP-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25447.99 | 13-OCT-05:01 | 4446.85 | 7591.59 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24961.04 | 04-NOV-05:01 | 4446.85 | 7591.59 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11734.41 | 07-DEC-16:20 | 12070.02 | 19521.22 | 28515.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11020.27 | 1905.79 | 3253.54 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48540.60 | 12070.02 | 19521.22 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 158.80 | 13-JAN-13:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.41 |
February | 2878.64 | 24-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.06 |
March | 5221.61 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.48 |
April | 12466.14 | 18-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.13 | 0.00 |
May | 14790.09 | 31-MAY-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.66 | 0.00 |
June | 16703.42 | 26-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.32 | 0.00 |
July | 16125.30 | 05-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 0.00 |
August | 16462.16 | 04-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.72 | 0.00 |
September | 15533.17 | 07-SEP-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.23 | 0.00 |
October | 7123.21 | 01-OCT-13:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.45 |
November | 4057.54 | 03-NOV-13:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.35 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1680.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16703.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.72 | 1680.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5673.54 | 07-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1842.71 |
February | 6736.87 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1425.50 |
March | 5970.59 | 08-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.24 |
April | 4828.59 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.08 |
May | 4364.04 | 02-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.13 |
June | 5037.69 | 26-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.89 | 0.00 |
July | 4811.73 | 05-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 0.00 |
August | 5184.47 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.93 | 0.00 |
September | 4371.10 | 08-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.49 | 0.00 |
October | 3851.89 | 07-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.72 |
November | 4673.71 | 22-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1563.30 |
December | 6234.47 | 16-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1275.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3851.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6736.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.93 | 1842.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6181.40 | 07-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1497.41 |
February | 7545.89 | 16-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1600.64 |
March | 7488.26 | 08-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.89 |
April | 7279.66 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.81 |
May | 6739.68 | 02-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.29 |
June | 4971.79 | 30-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.76 | 0.00 |
July | 5027.66 | 05-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 0.00 |
August | 5543.97 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.24 | 0.00 |
September | 5192.90 | 08-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.47 | 0.00 |
October | 4124.68 | 24-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.83 |
November | 4897.96 | 25-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2570.27 |
December | 6099.49 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4124.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7545.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.24 | 2570.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7580.18 | 19-JAN-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8545.64 | 01-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9131.93 | 24-MAR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16659.08 | 18-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18284.71 | 31-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30410.06 | 27-JUN-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29364.14 | 05-JUL-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28637.99 | 04-AUG-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25560.95 | 11-SEP-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11273.11 | 20-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10848.18 | 03-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7390.14 | 01-DEC-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7390.14 | 2541.06 | 4338.05 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30410.06 | 6035.01 | 9760.61 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8799.34 | 07-JAN-17:01 | 2858.69 | 4880.31 | 20424.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9158.07 | 24-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10364.48 | 24-MAR-15:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19331.40 | 18-APR-15:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21842.48 | 31-MAY-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23539.17 | 30-JUN-15:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23407.45 | 05-JUL-14:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23484.13 | 04-AUG-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21177.96 | 08-SEP-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10901.69 | 20-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10518.66 | 03-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9158.92 | 09-DEC-17:01 | 3176.32 | 5422.56 | 22694.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8799.34 | 2858.69 | 4880.31 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23539.17 | 6035.01 | 9760.61 | 22694.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4086.17 | 07-JAN-17:01 | 602.64 | 1028.81 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.63 |
February | 3970.89 | 04-FEB-17:01 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.10 |
March | 3862.33 | 28-MAR-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.01 |
April | 6121.38 | 18-APR-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.87 | 0.00 |
May | 7035.26 | 31-MAY-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 72.23 | 0.00 |
June | 8648.60 | 18-JUN-16:21 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 573.21 | 0.00 |
July | 8238.18 | 04-JUL-15:51 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 105.15 | 0.00 |
August | 7987.91 | 04-AUG-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 0.00 |
September | 6595.79 | 11-SEP-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 103.17 | 0.00 |
October | 4213.50 | 20-OCT-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
November | 4036.54 | 25-NOV-17:01 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.23 |
December | 4243.41 | 09-DEC-17:01 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3862.33 | 468.72 | 800.19 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8648.60 | 1272.23 | 2057.62 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 573.21 | 1244.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2636.61 | 07-JAN-17:01 | 381.52 | 651.32 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.77 |
February | 2555.47 | 04-FEB-17:01 | 423.91 | 723.69 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.21 |
March | 3071.72 | 28-MAR-09:50 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.47 |
April | 7279.19 | 18-APR-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 | 0.00 |
May | 8418.18 | 31-MAY-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 0.00 |
June | 11054.75 | 25-JUN-09:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.23 |
July | 9401.68 | 02-JUL-09:02 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.60 |
August | 8395.38 | 02-AUG-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 0.00 |
September | 7330.49 | 08-SEP-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 0.00 |
October | 3224.06 | 20-OCT-09:50 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.45 |
November | 2605.67 | 25-NOV-17:01 | 423.91 | 723.69 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.56 |
December | 2734.15 | 09-DEC-17:01 | 423.91 | 723.69 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2555.47 | 169.56 | 289.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11054.75 | 1654.44 | 2605.29 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 829.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4971.44 | 12-JAN-12:40 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.32 |
February | 7472.54 | 24-FEB-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.43 |
March | 7679.73 | 24-MAR-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.78 |
April | 11472.82 | 18-APR-12:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 92.43 | 0.00 |
May | 10451.80 | 30-MAY-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 | 0.00 |
June | 11230.07 | 30-JUN-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 | 0.00 |
July | 10678.83 | 05-JUL-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 |
August | 12917.96 | 29-AUG-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
September | 24058.96 | 17-SEP-14:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 | 0.00 |
October | 10874.20 | 20-OCT-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.14 |
November | 9603.13 | 03-NOV-13:25 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.38 |
December | 5283.91 | 01-DEC-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4971.44 | 401.76 | 685.87 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24058.96 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 92.43 | 314.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2670.28 | 07-JAN-17:01 | 381.49 | 651.28 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.67 |
February | 3265.46 | 24-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.60 |
March | 3359.56 | 23-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.08 |
April | 13262.99 | 15-APR-17:06 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 202.10 | 0.00 |
May | 9095.75 | 30-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 0.00 |
June | 21725.52 | 18-JUN-16:21 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 258.85 | 0.00 |
July | 21510.37 | 04-JUL-15:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
August | 10292.86 | 05-AUG-17:05 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.69 |
September | 9254.56 | 07-SEP-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5384.94 | 20-OCT-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
November | 3484.30 | 03-NOV-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.39 |
December | 2771.05 | 09-DEC-17:01 | 423.88 | 723.64 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2670.28 | 254.33 | 434.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21725.52 | 805.38 | 1302.56 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 258.85 | 829.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2465.69 | 14-JAN-17:01 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.03 |
February | 2487.63 | 25-FEB-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.73 |
March | 2508.73 | 25-MAR-16:03 | 200.88 | 342.94 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.53 |
April | 4095.32 | 16-APR-13:12 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 205.79 | 0.00 |
May | 4045.61 | 31-MAY-15:10 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 0.00 |
June | 5233.42 | 27-JUN-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 | 0.00 |
July | 5096.00 | 03-JUL-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 0.00 |
August | 6261.82 | 04-AUG-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 0.00 |
September | 5583.14 | 11-SEP-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 55.47 | 0.00 |
October | 3270.70 | 02-OCT-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 |
November | 3089.50 | 03-NOV-15:10 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.19 |
December | 2500.74 | 02-DEC-17:02 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2465.69 | 200.88 | 342.94 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6261.82 | 1272.23 | 2057.62 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 205.79 | 235.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1593.26 | 14-JAN-17:01 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.70 |
February | 1808.21 | 24-FEB-09:20 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.14 |
March | 2096.24 | 28-MAR-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.98 |
April | 4401.52 | 18-APR-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 0.00 |
May | 5566.84 | 31-MAY-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 0.00 |
June | 8546.98 | 25-JUN-10:32 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 59.79 | 0.00 |
July | 10552.18 | 30-JUL-09:22 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 |
August | 6878.36 | 02-AUG-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 0.00 |
September | 6546.44 | 08-SEP-09:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | 0.00 |
October | 2578.71 | 20-OCT-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.23 |
November | 2164.25 | 03-NOV-10:40 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 |
December | 1619.99 | 02-DEC-17:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1593.26 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10552.18 | 1610.86 | 2605.29 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.79 | 156.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2902.67 | 13-JAN-14:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2041.58 |
February | 3397.74 | 24-FEB-14:30 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1646.95 |
March | 3798.13 | 24-MAR-14:00 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1202.12 |
April | 8621.79 | 18-APR-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2940.19 | 0.00 |
May | 9575.61 | 31-MAY-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4128.82 | 0.00 |
June | 12003.86 | 26-JUN-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5103.06 | 0.00 |
July | 9650.43 | 26-JUL-16:10 | 401.76 | 1143.12 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 4479.13 | 0.00 |
August | 14278.40 | 04-AUG-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5398.79 | 0.00 |
September | 16380.91 | 07-SEP-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5025.12 | 0.00 |
October | 8744.65 | 20-OCT-13:50 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.44 |
November | 6136.19 | 04-NOV-13:25 | 275.09 | 685.87 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.35 |
December | 3127.33 | 01-DEC-14:20 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2902.67 | 275.09 | 685.87 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16380.91 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 5398.79 | 2658.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1834.10 | 12-JAN-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.18 |
February | 2323.51 | 24-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.33 |
March | 2266.85 | 23-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 |
April | 6903.55 | 16-APR-15:59 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 93.82 | 0.00 |
May | 5364.21 | 31-MAY-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 | 0.00 |
June | 12924.86 | 25-JUN-16:51 | 381.49 | 651.28 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 160.57 | 0.00 |
July | 8812.92 | 02-JUL-18:02 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 | 0.00 |
August | 8028.23 | 05-AUG-17:07 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.13 |
September | 12009.63 | 04-SEP-17:12 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 |
October | 4226.43 | 11-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 |
November | 2731.97 | 03-NOV-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 |
December | 1933.45 | 01-DEC-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1834.10 | 0.00 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12924.86 | 805.38 | 1302.56 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 160.57 | 117.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3054.13 | 07-JAN-17:01 | 602.64 | 1028.81 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.12 |
February | 3072.31 | 04-FEB-17:01 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.15 |
March | 3236.64 | 28-MAR-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.81 |
April | 5568.58 | 18-APR-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 | 0.00 |
May | 6256.81 | 31-MAY-15:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 | 0.00 |
June | 7233.35 | 26-JUN-14:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 68.71 | 0.00 |
July | 6716.90 | 03-JUL-13:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 0.00 |
August | 7171.46 | 04-AUG-15:30 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 79.29 | 0.00 |
September | 6407.92 | 11-SEP-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 81.04 | 0.00 |
October | 3556.97 | 20-OCT-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 |
November | 3311.56 | 03-NOV-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.42 |
December | 3021.05 | 09-DEC-17:01 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3021.05 | 602.64 | 1028.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7233.35 | 1306.65 | 2057.62 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 | 1038.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2238.10 | 13-JAN-11:03 | 2416.29 | 3907.94 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.44 |
February | 3283.23 | 24-FEB-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.61 |
March | 3856.38 | 28-MAR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.72 |
April | 8102.52 | 18-APR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 | 0.00 |
May | 8766.18 | 31-MAY-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 0.00 |
June | 12489.20 | 11-JUN-10:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 135.85 | 0.00 |
July | 16943.09 | 30-JUL-09:22 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.30 |
August | 9069.30 | 27-AUG-08:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.97 |
September | 11374.28 | 04-SEP-08:42 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.70 |
October | 4446.31 | 20-OCT-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.30 |
November | 3590.18 | 03-NOV-14:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.64 |
December | 2056.28 | 09-DEC-17:01 | 423.91 | 723.69 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2056.28 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16943.09 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 135.85 | 692.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5073.71 | 12-JAN-12:30 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.95 |
February | 7951.90 | 24-FEB-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.48 |
March | 8063.22 | 24-MAR-13:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.05 |
April | 11047.43 | 18-APR-12:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 77.55 | 0.00 |
May | 9673.12 | 30-MAY-13:20 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 0.00 |
June | 14482.87 | 25-JUN-13:22 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 313.97 | 0.00 |
July | 13408.11 | 30-JUL-15:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 0.00 |
August | 12542.51 | 29-AUG-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 |
September | 22966.06 | 04-SEP-14:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.89 |
October | 11275.93 | 20-OCT-13:05 | 5226.62 | 8230.49 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 |
November | 10160.11 | 03-NOV-13:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.38 |
December | 6161.34 | 01-DEC-13:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5073.71 | 334.80 | 571.56 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22966.06 | 5226.62 | 8230.49 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 313.97 | 268.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2261.29 | 12-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.07 |
February | 2941.71 | 24-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.82 |
March | 3012.97 | 23-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.30 |
April | 12354.41 | 15-APR-17:06 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 166.61 | 0.00 |
May | 12917.69 | 14-MAY-17:12 | 0.00 | 361.82 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.68 |
June | 17308.50 | 25-JUN-16:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 232.48 | 0.00 |
July | 17615.16 | 30-JUL-16:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.15 |
August | 17239.35 | 13-AUG-16:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.71 |
September | 16729.27 | 04-SEP-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.44 |
October | 5480.30 | 20-OCT-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 |
November | 3568.53 | 03-NOV-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 |
December | 2256.31 | 01-DEC-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2256.31 | 0.00 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17615.16 | 805.38 | 1302.56 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 232.48 | 182.07 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.161375E+12 | 123309.88 | 19-JAN-16:00 | 0.332130E+12 | 419663.45 | 30-JAN-07:19 |
February | 0.141750E+12 | 112943.51 | 02-FEB-08:30 | 0.218291E+12 | 416613.29 | 02-FEB-07:19 |
March | 0.158061E+12 | 114727.55 | 23-MAR-15:00 | 0.134159E+12 | 347205.30 | 06-MAR-07:30 |
April | 0.147830E+12 | 167469.24 | 18-APR-14:00 | 0.613825E+11 | 301626.34 | 03-APR-06:10 |
May | 0.162900E+12 | 172125.61 | 31-MAY-15:09 | 0.103259E+11 | 158215.02 | 02-MAY-06:10 |
June | 0.186550E+12 | 190576.47 | 26-JUN-15:50 | 0.342113E+10 | 129139.47 | 05-JUN-06:10 |
July | 0.195608E+12 | 191801.01 | 03-JUL-15:09 | 0.204632E+09 | 27965.19 | 24-JUL-06:10 |
August | 0.206027E+12 | 213634.67 | 04-AUG-15:30 | 0.558314E+09 | 46281.87 | 07-AUG-06:10 |
September | 0.167130E+12 | 187614.63 | 06-SEP-14:30 | 0.116234E+11 | 169126.45 | 29-SEP-06:10 |
October | 0.151437E+12 | 138854.01 | 20-OCT-15:20 | 0.409439E+11 | 205364.15 | 16-OCT-06:10 |
November | 0.151169E+12 | 122481.40 | 09-NOV-16:00 | 0.134962E+12 | 353115.80 | 28-NOV-07:10 |
December | 0.155927E+12 | 122983.81 | 11-DEC-16:40 | 0.249048E+12 | 396773.81 | 11-DEC-07:19 |
Annual Sum or Average | 0.198577E+13 | 0.119705E+13 | ||||
Minimum of Months | 0.141750E+12 | 112943.51 | 0.204632E+09 | 27965.19 | ||
Maximum of Months | 0.206027E+12 | 213634.67 | 0.332130E+12 | 419663.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.248978E+11 | 0.613996E+11 | 0.230900E+10 | 0.182781E+11 | 0.172116E+10 | 0.00 | 886629.36 | 0.00 | 0.00 | 0.00 | 0.552085E+10 | 0.00 |
February | 0.428574E+11 | 0.207452E+11 | 0.556056E+11 | 0.209511E+10 | 0.142493E+11 | 0.109080E+10 | 0.00 | 1136976.28 | 0.00 | 0.00 | 0.00 | 0.510522E+10 | 0.00 |
March | 0.509265E+11 | 0.205560E+11 | 0.635880E+11 | 0.240664E+10 | 0.137331E+11 | 0.664219E+09 | 0.00 | 0.224550E+09 | 0.00 | 0.00 | 0.00 | 0.596253E+10 | 0.00 |
April | 0.454877E+11 | 0.174213E+11 | 0.594055E+11 | 0.224272E+10 | 0.125998E+11 | 0.297725E+09 | 0.00 | 0.519243E+10 | 0.00 | 0.00 | 0.00 | 0.518248E+10 | 0.00 |
May | 0.490872E+11 | 0.158449E+11 | 0.624938E+11 | 0.235782E+10 | 0.141064E+11 | 62145370.02 | 0.00 | 0.137100E+11 | 0.00 | 0.00 | 0.00 | 0.523826E+10 | 0.00 |
June | 0.488499E+11 | 0.142505E+11 | 0.612808E+11 | 0.231841E+10 | 0.183107E+11 | 27875542.19 | 0.00 | 0.366457E+11 | 0.00 | 0.00 | 0.00 | 0.486661E+10 | 0.00 |
July | 0.457251E+11 | 0.151873E+11 | 0.606074E+11 | 0.228147E+10 | 0.191549E+11 | 13118069.05 | 0.00 | 0.482764E+11 | 0.00 | 0.00 | 0.00 | 0.436234E+10 | 0.00 |
August | 0.509265E+11 | 0.170519E+11 | 0.635880E+11 | 0.240664E+10 | 0.201854E+11 | 15045690.85 | 0.00 | 0.471703E+11 | 0.00 | 0.00 | 0.00 | 0.468290E+10 | 0.00 |
September | 0.454877E+11 | 0.187905E+11 | 0.593832E+11 | 0.224140E+10 | 0.162025E+11 | 63472696.66 | 0.00 | 0.206759E+11 | 0.00 | 0.00 | 0.00 | 0.428578E+10 | 0.00 |
October | 0.472479E+11 | 0.219702E+11 | 0.614108E+11 | 0.230966E+10 | 0.120196E+11 | 0.191659E+09 | 0.00 | 0.165049E+10 | 0.00 | 0.00 | 0.00 | 0.463695E+10 | 0.00 |
November | 0.466941E+11 | 0.234656E+11 | 0.599069E+11 | 0.224962E+10 | 0.132500E+11 | 0.678648E+09 | 0.00 | 67744012.03 | 0.00 | 0.00 | 0.00 | 0.485660E+10 | 0.00 |
December | 0.457251E+11 | 0.255013E+11 | 0.605962E+11 | 0.228081E+10 | 0.154242E+11 | 0.127145E+10 | 0.00 | 995756.04 | 0.00 | 0.00 | 0.00 | 0.512675E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.235682E+12 | 0.729266E+12 | 0.274993E+11 | 0.187514E+12 | 0.609731E+10 | 0.00 | 0.173617E+12 | 0.00 | 0.00 | 0.00 | 0.598273E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.142505E+11 | 0.556056E+11 | 0.209511E+10 | 0.120196E+11 | 13118069.05 | 0.00 | 886629.36 | 0.00 | 0.00 | 0.00 | 0.428578E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.255013E+11 | 0.635880E+11 | 0.240664E+10 | 0.201854E+11 | 0.172116E+10 | 0.00 | 0.482764E+11 | 0.00 | 0.00 | 0.00 | 0.596253E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.332130E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.218291E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.134159E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.613825E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.103259E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.342113E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204632E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.558314E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.116234E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.409439E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.134962E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.249048E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119705E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.204632E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.332130E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:20 | 18751.61 | 02-JAN-06:19 | 1657.42 | 30-JAN-07:30 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 06-FEB-12:20 | 18406.81 | 06-FEB-07:10 | 1609.37 | 02-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 01-MAR-08:20 | 17844.69 | 06-MAR-07:10 | 1469.79 | 06-MAR-07:00 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 04-APR-07:19 | 19816.12 | 18-APR-14:00 | 1403.36 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 02-MAY-07:10 | 21756.35 | 31-MAY-14:00 | 732.51 | 02-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 01-JUN-13:09 | 26049.88 | 26-JUN-15:30 | 581.03 | 05-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 25156.47 | 03-JUL-15:20 | 113.03 | 24-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:10 | 29292.04 | 04-AUG-15:20 | 202.72 | 07-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 25-SEP-11:09 | 27450.66 | 07-SEP-14:30 | 770.96 | 29-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 23-OCT-16:10 | 14059.78 | 20-OCT-14:00 | 1046.41 | 16-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 03-NOV-16:10 | 18032.06 | 27-NOV-07:10 | 1489.47 | 28-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 01-DEC-17:10 | 18219.44 | 11-DEC-07:10 | 1594.27 | 11-DEC-07:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 14059.78 | 113.03 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 29292.04 | 1657.42 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 119.90 | 05-JAN-06:19 | 0.00 | 0.00 | 0.00 | 7496.44 | 31-JAN-12:50 | 0.00 |
February | 194.71 | 11-FEB-01:19 | 0.00 | 0.00 | 0.00 | 7596.40 | 15-FEB-12:39 | 0.00 |
March | 10489.88 | 25-MAR-14:00 | 0.00 | 0.00 | 0.00 | 7527.80 | 08-MAR-12:30 | 0.00 |
April | 50665.24 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 7211.96 | 03-APR-11:00 | 0.00 |
May | 53432.06 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 6984.19 | 01-MAY-11:00 | 0.00 |
June | 67353.34 | 26-JUN-14:09 | 0.00 | 0.00 | 0.00 | 6574.45 | 02-JUN-11:39 | 0.00 |
July | 70615.97 | 26-JUL-14:00 | 0.00 | 0.00 | 0.00 | 6191.20 | 03-JUL-11:39 | 0.00 |
August | 87265.10 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 5807.08 | 01-AUG-11:30 | 0.00 |
September | 65335.55 | 06-SEP-14:30 | 0.00 | 0.00 | 0.00 | 5839.95 | 29-SEP-11:00 | 0.00 |
October | 27713.74 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 6263.90 | 31-OCT-11:20 | 0.00 |
November | 5402.93 | 03-NOV-14:09 | 0.00 | 0.00 | 0.00 | 6719.61 | 30-NOV-12:30 | 0.00 |
December | 229.23 | 11-DEC-06:40 | 0.00 | 0.00 | 0.00 | 7176.92 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 119.90 | 0.00 | 0.00 | 0.00 | 5807.08 | 0.00 | ||
Maximum of Months | 87265.10 | 0.00 | 0.00 | 0.00 | 7596.40 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 123309.88 | 19-JAN-16:00 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 8572.98 | 1153.01 | 0.00 | 0.00 | 0.00 |
February | 112943.51 | 02-FEB-08:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 14136.86 | 1408.33 | 0.00 | 0.00 | 0.00 |
March | 114727.55 | 23-MAR-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 9047.11 | 9.27 | 0.00 | 7262.41 | 0.00 |
April | 167469.24 | 18-APR-14:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 19816.12 | 6.97 | 0.00 | 50665.24 | 0.00 |
May | 172125.61 | 31-MAY-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 21708.78 | 6.95 | 0.00 | 52646.49 | 0.00 |
June | 190576.47 | 26-JUN-15:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 25839.64 | 6.95 | 0.00 | 67111.27 | 0.00 |
July | 191801.01 | 03-JUL-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 25141.96 | 6.95 | 0.00 | 69260.15 | 0.00 |
August | 213634.67 | 04-AUG-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 29290.93 | 6.95 | 0.00 | 87265.10 | 0.00 |
September | 187614.63 | 06-SEP-14:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 25965.75 | 6.95 | 0.00 | 65335.55 | 0.00 |
October | 138854.01 | 20-OCT-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 13949.08 | 6.85 | 0.00 | 27203.62 | 0.00 |
November | 122481.40 | 09-NOV-16:00 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 9579.06 | 105.90 | 0.00 | 0.00 | 0.00 |
December | 122983.81 | 11-DEC-16:40 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 8572.98 | 1223.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 112943.51 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 8572.98 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 213634.67 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 29290.93 | 1408.33 | 0.00 | 87265.10 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 419663.45 | 30-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 416613.29 | 02-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 347205.30 | 06-MAR-07:30 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 301626.34 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 158215.02 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 129139.47 | 05-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 27965.19 | 24-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 46281.87 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 169126.45 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 205364.15 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 353115.80 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 396773.81 | 11-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 27965.19 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 419663.45 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.60 | 1.67 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 19.60 | 1.67 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.60 | 1.67 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 19.32 | 4.67 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
February | 0.83 | 19.80 | 0.83 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
March | 0.17 | 19.24 | 0.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.68 | 0.67 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
December | 2.00 | 19.55 | 1.83 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
Annual Sum or Average | 9.00 | 19.44 | 8.17 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 19.80 | 4.67 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 18.56 | 4.83 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
February | 3.50 | 18.45 | 2.33 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
March | 1.00 | 17.95 | 0.50 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
April | 0.33 | 18.26 | 0.17 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 18.30 | 1.17 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
December | 4.00 | 18.40 | 2.50 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Annual Sum or Average | 17.67 | 18.43 | 11.50 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 18.56 | 4.83 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 84.67 | 14.94 | 31.33 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
February | 52.50 | 15.43 | 19.17 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
March | 16.83 | 15.01 | 4.17 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
April | 3.67 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
November | 29.67 | 14.68 | 6.50 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
December | 56.33 | 14.92 | 17.00 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 |
Annual Sum or Average | 244.33 | 15.02 | 78.17 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.67 | 16.96 | 31.33 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 85.67 | 14.87 | 30.83 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
February | 49.83 | 15.25 | 15.83 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
March | 16.33 | 15.08 | 2.83 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
April | 4.00 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.81 | 2.00 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.91 | 2.17 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
October | 0.67 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
November | 30.00 | 14.69 | 5.67 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
December | 56.17 | 14.89 | 16.17 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
Annual Sum or Average | 242.83 | 14.96 | 71.33 | 15.20 | 4.17 | 15.36 | 4.17 | 15.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.67 | 17.22 | 30.83 | 17.22 | 2.17 | 27.91 | 2.17 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.83 | 14.99 | 22.50 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
February | 41.17 | 15.45 | 12.17 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
March | 13.00 | 15.20 | 1.17 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
April | 3.33 | 14.95 | 0.00 | 14.95 | 0.33 | 16.08 | 0.33 | 17.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.50 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 1.17 | 27.52 |
October | 0.67 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
November | 24.00 | 14.72 | 5.00 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
December | 46.17 | 15.02 | 11.67 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
Annual Sum or Average | 202.17 | 15.08 | 52.50 | 15.37 | 2.33 | 15.48 | 2.33 | 15.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.83 | 17.03 | 22.50 | 17.03 | 1.17 | 27.52 | 1.17 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 84.83 | 14.95 | 31.00 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
February | 51.67 | 15.47 | 18.50 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
March | 15.67 | 15.07 | 2.67 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
April | 4.00 | 15.07 | 0.00 | 15.07 | 1.17 | 17.97 | 0.83 | 19.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 0.67 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.49 | 2.17 | 28.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.15 | 2.83 | 28.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.69 | 0.67 | 27.72 |
September | 0.17 | 17.20 | 0.00 | 17.20 | 0.50 | 24.90 | 0.33 | 25.77 |
October | 0.67 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
November | 30.17 | 14.66 | 6.83 | 14.72 | 0.00 | 14.72 | 0.00 | 14.72 |
December | 56.33 | 14.90 | 16.17 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
Annual Sum or Average | 243.50 | 15.03 | 75.17 | 15.30 | 11.67 | 15.76 | 7.50 | 16.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 0.00 | 14.72 |
Maximum of Months | 84.83 | 17.20 | 31.00 | 17.20 | 4.67 | 28.49 | 2.83 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.17 | 15.90 | 21.83 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
February | 33.17 | 16.57 | 16.50 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
March | 9.00 | 16.17 | 2.50 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
April | 1.67 | 15.78 | 0.17 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.50 | 15.15 | 3.33 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
December | 22.50 | 15.43 | 7.67 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
Annual Sum or Average | 133.00 | 15.95 | 52.00 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.17 | 16.57 | 21.83 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.50 | 15.77 | 18.00 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
February | 29.00 | 16.32 | 12.50 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
March | 7.83 | 16.06 | 1.33 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
April | 1.83 | 15.68 | 0.17 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.83 | 15.14 | 2.33 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
December | 20.33 | 15.48 | 4.83 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
Annual Sum or Average | 122.33 | 15.82 | 39.17 | 16.26 | 0.67 | 16.31 | 0.67 | 16.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.50 | 16.32 | 18.00 | 16.91 | 0.67 | 27.38 | 0.67 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 152.83 | 16.12 | 128.17 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
February | 99.67 | 16.48 | 86.83 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
March | 66.17 | 17.62 | 62.83 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
April | 30.83 | 18.35 | 30.33 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
May | 4.83 | 19.50 | 4.83 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
June | 0.17 | 20.42 | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4.67 | 19.71 | 4.67 | 19.71 | 0.67 | 20.22 | 0.67 | 20.67 |
October | 12.17 | 18.96 | 12.17 | 18.96 | 0.17 | 19.02 | 0.17 | 19.07 |
November | 54.00 | 17.53 | 49.33 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
December | 101.33 | 16.77 | 89.33 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
Annual Sum or Average | 526.67 | 16.91 | 468.67 | 17.01 | 0.83 | 17.02 | 0.83 | 17.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.83 | 20.42 | 128.17 | 20.42 | 0.67 | 20.42 | 0.67 | 20.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.33 | 15.83 | 20.33 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
February | 30.50 | 16.53 | 14.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
March | 7.83 | 15.93 | 2.00 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
April | 1.83 | 15.66 | 0.17 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.59 | 0.83 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.66 | 0.83 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.53 | 0.17 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.44 | 0.00 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.83 | 15.00 | 3.17 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
December | 21.50 | 15.42 | 6.33 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
Annual Sum or Average | 127.83 | 15.87 | 46.00 | 16.29 | 3.67 | 16.53 | 1.83 | 16.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.33 | 16.53 | 20.33 | 17.15 | 1.83 | 27.66 | 0.83 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.83 | 15.50 | 22.50 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
February | 30.50 | 16.27 | 13.17 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
March | 8.67 | 15.35 | 2.67 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
April | 1.33 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14.17 | 15.13 | 4.17 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
December | 29.67 | 15.28 | 9.83 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
Annual Sum or Average | 146.17 | 15.57 | 52.33 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.83 | 16.27 | 22.50 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.17 | 15.34 | 18.17 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
February | 26.83 | 15.82 | 9.00 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
March | 7.00 | 15.34 | 0.67 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
April | 1.50 | 15.08 | 0.00 | 15.08 | 0.33 | 17.30 | 0.33 | 18.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.11 | 2.17 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.09 | 3.00 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.50 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14.33 | 15.17 | 4.00 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
December | 27.67 | 15.22 | 7.50 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
Annual Sum or Average | 136.50 | 15.39 | 39.33 | 15.71 | 6.33 | 16.13 | 6.33 | 16.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.17 | 15.82 | 18.17 | 16.35 | 3.00 | 28.11 | 3.00 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.00 | 15.55 | 13.17 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
February | 22.67 | 16.26 | 7.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
March | 5.67 | 15.72 | 0.50 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
April | 1.00 | 15.24 | 0.00 | 15.24 | 0.33 | 18.30 | 0.33 | 20.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.48 | 0.67 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.78 | 1.83 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
November | 12.50 | 15.32 | 3.83 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
December | 22.50 | 15.42 | 4.50 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
Annual Sum or Average | 113.33 | 15.65 | 29.00 | 16.06 | 3.00 | 16.30 | 3.00 | 16.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.00 | 16.26 | 13.17 | 16.97 | 1.83 | 27.78 | 1.83 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.33 | 15.38 | 20.50 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
February | 29.67 | 16.18 | 12.17 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
March | 7.33 | 15.36 | 1.33 | 15.44 | 0.00 | 15.44 | 0.00 | 15.44 |
April | 1.50 | 15.04 | 0.00 | 15.04 | 0.83 | 19.69 | 0.67 | 21.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.55 | 0.50 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.24 | 2.00 | 28.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.03 | 3.00 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.90 | 0.50 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.81 | 0.33 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14.67 | 15.03 | 4.00 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
December | 28.00 | 15.14 | 8.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
Annual Sum or Average | 142.50 | 15.46 | 46.00 | 15.79 | 12.00 | 16.52 | 7.00 | 16.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.33 | 16.18 | 20.50 | 16.79 | 5.33 | 28.24 | 3.00 | 28.25 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.49 | 227.67 | 21.22 | 227.67 | 21.07 |
February | 454.00 | 22.22 | 78.00 | 22.01 | 78.00 | 21.85 |
March | 490.17 | 23.05 | 18.17 | 22.97 | 18.17 | 22.90 |
April | 343.50 | 23.49 | 46.83 | 23.63 | 1.00 | 23.63 |
May | 68.50 | 23.80 | 276.67 | 24.42 | 0.00 | 24.42 |
June | 1.50 | 23.69 | 440.50 | 24.40 | 0.00 | 24.40 |
July | 0.00 | 0.00 | 493.00 | 24.49 | 0.00 | 24.49 |
August | 0.00 | 0.00 | 508.33 | 24.43 | 0.00 | 24.43 |
September | 45.33 | 23.78 | 281.50 | 24.53 | 0.00 | 24.53 |
October | 292.17 | 23.90 | 26.50 | 24.00 | 0.00 | 24.00 |
November | 379.17 | 23.04 | 45.83 | 22.94 | 30.00 | 22.79 |
December | 497.00 | 22.32 | 69.00 | 22.12 | 69.00 | 21.97 |
Annual Sum or Average | 3073.33 | 22.71 | 2512.00 | 23.23 | 423.83 | 23.05 |
Minimum of Months | 0.00 | 0.00 | 18.17 | 21.22 | 0.00 | 21.07 |
Maximum of Months | 502.00 | 23.90 | 508.33 | 24.53 | 227.67 | 24.53 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.58 | 405.67 | 20.46 | 405.67 | 20.41 |
February | 454.00 | 21.03 | 260.33 | 20.82 | 260.33 | 20.72 |
March | 514.00 | 21.87 | 107.67 | 21.65 | 107.67 | 21.49 |
April | 422.00 | 22.41 | 51.83 | 22.37 | 32.00 | 22.27 |
May | 252.17 | 23.22 | 134.83 | 23.55 | 0.00 | 23.55 |
June | 63.33 | 23.09 | 309.33 | 24.04 | 0.00 | 24.04 |
July | 15.83 | 23.43 | 439.33 | 24.24 | 0.00 | 24.24 |
August | 14.00 | 23.28 | 417.33 | 24.20 | 0.00 | 24.20 |
September | 198.83 | 23.21 | 169.83 | 23.73 | 0.00 | 23.73 |
October | 488.33 | 22.74 | 1.00 | 22.74 | 1.00 | 22.73 |
November | 478.67 | 21.78 | 141.67 | 21.49 | 141.67 | 21.31 |
December | 497.00 | 20.94 | 294.17 | 20.73 | 294.17 | 20.63 |
Annual Sum or Average | 3900.17 | 21.83 | 2733.00 | 22.11 | 1242.50 | 21.84 |
Minimum of Months | 14.00 | 20.58 | 1.00 | 20.46 | 0.00 | 20.41 |
Maximum of Months | 514.00 | 23.43 | 439.33 | 24.24 | 405.67 | 24.24 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 478.17 | 20.03 | 478.17 | 20.02 |
February | 454.00 | 20.35 | 359.17 | 20.24 | 359.17 | 20.20 |
March | 514.00 | 21.04 | 261.33 | 20.85 | 261.33 | 20.76 |
April | 442.83 | 21.56 | 123.33 | 21.35 | 110.00 | 21.16 |
May | 358.67 | 22.59 | 83.17 | 22.85 | 4.17 | 22.83 |
June | 155.83 | 22.61 | 243.50 | 23.55 | 0.00 | 23.55 |
July | 86.67 | 22.95 | 323.33 | 23.93 | 0.00 | 23.93 |
August | 127.33 | 22.86 | 285.00 | 23.73 | 0.00 | 23.73 |
September | 325.83 | 22.42 | 107.83 | 22.77 | 10.67 | 22.72 |
October | 501.33 | 21.43 | 109.50 | 21.22 | 109.50 | 21.08 |
November | 489.00 | 20.69 | 279.00 | 20.45 | 279.00 | 20.34 |
December | 497.00 | 20.21 | 466.50 | 20.17 | 466.50 | 20.15 |
Annual Sum or Average | 4454.50 | 21.19 | 3119.83 | 21.31 | 2078.50 | 21.06 |
Minimum of Months | 86.67 | 20.06 | 83.17 | 20.03 | 0.00 | 20.02 |
Maximum of Months | 514.00 | 22.95 | 478.17 | 23.93 | 478.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.63 | 500.83 | 19.63 | 500.83 | 19.63 |
February | 454.00 | 19.76 | 441.17 | 19.75 | 441.17 | 19.74 |
March | 514.00 | 20.34 | 404.33 | 20.26 | 404.33 | 20.22 |
April | 468.00 | 20.69 | 234.00 | 20.53 | 221.00 | 20.39 |
May | 450.33 | 21.50 | 69.67 | 21.62 | 31.33 | 21.53 |
June | 281.00 | 21.97 | 167.67 | 22.66 | 14.67 | 22.64 |
July | 233.67 | 22.32 | 205.67 | 23.10 | 16.00 | 23.16 |
August | 298.67 | 22.09 | 157.83 | 22.68 | 8.50 | 22.69 |
September | 412.50 | 21.44 | 106.17 | 21.57 | 57.17 | 21.46 |
October | 502.00 | 20.44 | 269.83 | 20.26 | 269.83 | 20.17 |
November | 489.00 | 19.91 | 367.67 | 19.76 | 367.67 | 19.70 |
December | 497.00 | 19.69 | 497.00 | 19.69 | 497.00 | 19.69 |
Annual Sum or Average | 5102.17 | 20.63 | 3421.83 | 20.60 | 2829.50 | 20.41 |
Minimum of Months | 233.67 | 19.63 | 69.67 | 19.63 | 8.50 | 19.63 |
Maximum of Months | 514.00 | 22.32 | 500.83 | 23.10 | 500.83 | 23.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.63 | 491.67 | 19.62 | 491.67 | 19.62 |
February | 454.00 | 19.79 | 417.33 | 19.74 | 417.33 | 19.72 |
March | 514.00 | 20.44 | 339.00 | 20.29 | 339.00 | 20.22 |
April | 434.17 | 20.92 | 212.33 | 20.87 | 177.17 | 20.69 |
May | 368.17 | 21.77 | 129.00 | 22.34 | 21.67 | 22.30 |
June | 210.00 | 22.22 | 270.67 | 23.27 | 24.17 | 23.33 |
July | 161.50 | 22.88 | 323.17 | 23.79 | 29.00 | 23.91 |
August | 207.50 | 22.22 | 271.83 | 23.23 | 10.17 | 23.25 |
September | 321.00 | 21.51 | 155.67 | 22.11 | 37.50 | 21.98 |
October | 502.00 | 20.66 | 206.33 | 20.46 | 206.33 | 20.35 |
November | 489.00 | 19.97 | 355.33 | 19.81 | 355.33 | 19.74 |
December | 497.00 | 19.71 | 497.00 | 19.71 | 497.00 | 19.71 |
Annual Sum or Average | 4660.33 | 20.65 | 3669.33 | 20.86 | 2606.33 | 20.64 |
Minimum of Months | 161.50 | 19.63 | 129.00 | 19.62 | 10.17 | 19.62 |
Maximum of Months | 514.00 | 22.88 | 497.00 | 23.79 | 497.00 | 23.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 442.33 | 19.65 | 442.33 | 19.61 |
February | 444.83 | 20.01 | 363.83 | 19.88 | 360.33 | 19.82 |
March | 492.50 | 20.60 | 316.67 | 20.44 | 308.17 | 20.34 |
April | 411.67 | 20.90 | 230.33 | 20.95 | 176.83 | 20.74 |
May | 390.00 | 21.60 | 112.50 | 21.99 | 30.33 | 21.89 |
June | 260.50 | 21.95 | 211.83 | 22.86 | 17.50 | 22.86 |
July | 204.00 | 22.39 | 257.17 | 23.39 | 18.67 | 23.47 |
August | 235.83 | 22.13 | 241.67 | 23.11 | 9.83 | 23.13 |
September | 310.50 | 21.60 | 178.33 | 22.31 | 41.83 | 22.22 |
October | 438.50 | 20.84 | 209.33 | 20.78 | 177.17 | 20.60 |
November | 475.67 | 20.21 | 309.83 | 20.02 | 303.00 | 19.91 |
December | 495.33 | 19.97 | 426.83 | 19.83 | 426.83 | 19.78 |
Annual Sum or Average | 4661.33 | 20.78 | 3300.67 | 20.93 | 2312.83 | 20.69 |
Minimum of Months | 204.00 | 19.76 | 112.50 | 19.65 | 9.83 | 19.61 |
Maximum of Months | 502.00 | 22.39 | 442.33 | 23.39 | 442.33 | 23.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.63 | 493.17 | 19.62 | 493.17 | 19.62 |
February | 454.00 | 19.86 | 415.33 | 19.80 | 415.33 | 19.77 |
March | 511.50 | 20.46 | 359.83 | 20.31 | 359.00 | 20.25 |
April | 422.83 | 20.82 | 228.17 | 20.80 | 188.83 | 20.63 |
May | 393.17 | 21.55 | 124.17 | 21.98 | 32.67 | 21.89 |
June | 251.67 | 22.07 | 223.83 | 23.00 | 25.17 | 23.05 |
July | 204.33 | 22.65 | 273.83 | 23.58 | 32.33 | 23.72 |
August | 243.17 | 22.18 | 233.17 | 23.09 | 13.33 | 23.13 |
September | 354.00 | 21.45 | 152.33 | 21.96 | 47.67 | 21.84 |
October | 488.33 | 20.63 | 241.50 | 20.43 | 233.83 | 20.29 |
November | 487.33 | 20.00 | 347.50 | 19.82 | 347.50 | 19.75 |
December | 497.00 | 19.71 | 484.33 | 19.69 | 484.33 | 19.69 |
Annual Sum or Average | 4809.33 | 20.67 | 3577.17 | 20.80 | 2673.17 | 20.59 |
Minimum of Months | 204.33 | 19.63 | 124.17 | 19.62 | 13.33 | 19.62 |
Maximum of Months | 511.50 | 22.65 | 493.17 | 23.58 | 493.17 | 23.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 502.00 | 19.68 | 502.00 | 19.68 |
February | 454.00 | 19.86 | 452.00 | 19.86 | 452.00 | 19.86 |
March | 514.00 | 20.38 | 452.67 | 20.34 | 452.67 | 20.33 |
April | 484.83 | 20.64 | 310.00 | 20.51 | 310.00 | 20.45 |
May | 489.33 | 21.37 | 46.17 | 21.34 | 37.83 | 21.28 |
June | 356.67 | 22.17 | 109.83 | 22.58 | 14.00 | 22.61 |
July | 232.33 | 22.61 | 184.00 | 23.20 | 11.33 | 23.23 |
August | 232.67 | 22.59 | 192.33 | 23.17 | 8.00 | 23.18 |
September | 376.83 | 21.90 | 81.50 | 22.14 | 16.67 | 22.08 |
October | 502.00 | 20.97 | 138.50 | 20.86 | 138.50 | 20.79 |
November | 489.00 | 20.38 | 317.83 | 20.22 | 317.83 | 20.15 |
December | 497.00 | 19.91 | 497.00 | 19.91 | 497.00 | 19.91 |
Annual Sum or Average | 5130.67 | 20.84 | 3283.83 | 20.77 | 2757.83 | 20.60 |
Minimum of Months | 232.33 | 19.68 | 46.17 | 19.68 | 8.00 | 19.68 |
Maximum of Months | 514.00 | 22.61 | 502.00 | 23.20 | 502.00 | 23.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 500.33 | 19.70 | 500.33 | 19.70 |
February | 454.00 | 19.93 | 439.83 | 19.92 | 439.83 | 19.91 |
March | 514.00 | 20.48 | 400.00 | 20.40 | 400.00 | 20.36 |
April | 462.33 | 20.94 | 241.00 | 20.83 | 222.17 | 20.71 |
May | 409.33 | 21.79 | 79.67 | 22.13 | 14.33 | 22.08 |
June | 205.33 | 22.38 | 257.83 | 23.39 | 16.50 | 23.46 |
July | 99.50 | 23.23 | 371.17 | 24.04 | 20.83 | 24.11 |
August | 105.17 | 22.87 | 350.67 | 23.82 | 10.33 | 23.85 |
September | 250.50 | 22.06 | 188.50 | 22.97 | 8.17 | 22.93 |
October | 500.50 | 21.38 | 72.00 | 21.26 | 72.00 | 21.17 |
November | 489.00 | 20.50 | 301.67 | 20.33 | 301.67 | 20.25 |
December | 497.00 | 19.95 | 497.00 | 19.95 | 497.00 | 19.95 |
Annual Sum or Average | 4488.67 | 20.84 | 3699.67 | 21.11 | 2503.17 | 20.87 |
Minimum of Months | 99.50 | 19.70 | 72.00 | 19.70 | 8.17 | 19.70 |
Maximum of Months | 514.00 | 23.23 | 500.33 | 24.04 | 500.33 | 24.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.71 | 484.67 | 18.67 | 484.67 | 18.65 |
February | 454.00 | 19.41 | 397.67 | 19.29 | 397.67 | 19.25 |
March | 514.00 | 20.25 | 351.17 | 20.06 | 351.17 | 19.97 |
April | 455.50 | 20.77 | 241.33 | 20.63 | 219.67 | 20.48 |
May | 440.67 | 21.44 | 72.83 | 21.64 | 25.83 | 21.57 |
June | 307.17 | 22.11 | 182.00 | 22.79 | 33.67 | 22.84 |
July | 187.00 | 22.73 | 295.50 | 23.55 | 50.67 | 23.57 |
August | 162.00 | 22.71 | 334.00 | 23.63 | 47.83 | 23.64 |
September | 255.83 | 21.93 | 203.00 | 22.96 | 15.17 | 22.93 |
October | 442.50 | 21.43 | 72.83 | 21.51 | 43.67 | 21.39 |
November | 472.33 | 20.38 | 263.00 | 20.13 | 254.83 | 19.97 |
December | 495.33 | 19.48 | 432.33 | 19.36 | 432.33 | 19.32 |
Annual Sum or Average | 4688.33 | 20.61 | 3330.33 | 20.74 | 2357.17 | 20.47 |
Minimum of Months | 162.00 | 18.71 | 72.83 | 18.67 | 15.17 | 18.65 |
Maximum of Months | 514.00 | 22.73 | 484.67 | 23.63 | 484.67 | 23.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 495.50 | 19.69 | 495.50 | 19.69 |
February | 454.00 | 19.97 | 433.00 | 19.94 | 433.00 | 19.93 |
March | 514.00 | 20.50 | 400.17 | 20.41 | 400.17 | 20.38 |
April | 458.67 | 20.91 | 245.67 | 20.79 | 225.33 | 20.66 |
May | 433.17 | 21.58 | 76.50 | 21.83 | 23.00 | 21.77 |
June | 240.83 | 22.25 | 218.67 | 23.17 | 19.67 | 23.23 |
July | 117.33 | 23.14 | 343.67 | 23.97 | 21.00 | 24.05 |
August | 108.00 | 22.82 | 354.50 | 23.83 | 11.00 | 23.85 |
September | 281.33 | 21.97 | 173.67 | 22.76 | 13.33 | 22.71 |
October | 488.33 | 21.29 | 104.83 | 21.19 | 97.50 | 21.09 |
November | 486.00 | 20.49 | 299.50 | 20.32 | 298.83 | 20.23 |
December | 497.00 | 19.94 | 488.00 | 19.93 | 488.00 | 19.93 |
Annual Sum or Average | 4580.67 | 20.83 | 3633.67 | 21.06 | 2526.33 | 20.84 |
Minimum of Months | 108.00 | 19.70 | 76.50 | 19.69 | 11.00 | 19.69 |
Maximum of Months | 514.00 | 23.14 | 495.50 | 23.97 | 495.50 | 24.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 495.00 | 19.69 | 495.00 | 19.69 |
February | 454.00 | 19.91 | 424.67 | 19.87 | 424.67 | 19.86 |
March | 514.00 | 20.54 | 349.17 | 20.44 | 349.17 | 20.39 |
April | 463.50 | 20.95 | 181.83 | 20.80 | 169.17 | 20.66 |
May | 422.33 | 21.96 | 59.50 | 22.16 | 9.67 | 22.12 |
June | 199.50 | 22.33 | 221.33 | 23.23 | 8.33 | 23.25 |
July | 132.17 | 22.88 | 302.50 | 23.70 | 15.17 | 23.74 |
August | 196.00 | 22.62 | 242.67 | 23.36 | 9.17 | 23.37 |
September | 368.00 | 21.87 | 101.00 | 22.19 | 19.83 | 22.12 |
October | 502.00 | 20.87 | 163.83 | 20.72 | 163.83 | 20.62 |
November | 489.00 | 20.24 | 316.00 | 20.04 | 316.00 | 19.96 |
December | 497.00 | 19.84 | 497.00 | 19.84 | 497.00 | 19.84 |
Annual Sum or Average | 4739.50 | 20.82 | 3354.50 | 20.91 | 2477.00 | 20.69 |
Minimum of Months | 132.17 | 19.70 | 59.50 | 19.69 | 8.33 | 19.69 |
Maximum of Months | 514.00 | 22.88 | 497.00 | 23.70 | 497.00 | 23.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.48 | 416.33 | 19.46 | 416.33 | 19.45 |
February | 385.00 | 19.79 | 344.83 | 19.71 | 344.83 | 19.69 |
March | 431.83 | 20.63 | 256.50 | 20.43 | 256.50 | 20.34 |
April | 351.17 | 21.13 | 147.00 | 21.09 | 114.67 | 20.89 |
May | 263.33 | 22.05 | 123.83 | 22.83 | 6.00 | 22.82 |
June | 151.33 | 22.67 | 240.00 | 23.66 | 19.33 | 23.77 |
July | 96.83 | 23.73 | 310.83 | 24.21 | 31.17 | 24.34 |
August | 130.83 | 22.81 | 261.50 | 23.68 | 13.67 | 23.72 |
September | 239.00 | 21.91 | 143.17 | 22.69 | 17.67 | 22.62 |
October | 422.83 | 21.18 | 106.50 | 20.99 | 106.33 | 20.87 |
November | 417.00 | 20.23 | 271.67 | 20.01 | 271.67 | 19.92 |
December | 422.00 | 19.68 | 419.83 | 19.67 | 419.83 | 19.67 |
Annual Sum or Average | 3738.17 | 20.79 | 3042.00 | 21.05 | 2018.00 | 20.80 |
Minimum of Months | 96.83 | 19.48 | 106.50 | 19.46 | 6.00 | 19.45 |
Maximum of Months | 431.83 | 23.73 | 419.83 | 24.21 | 419.83 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.83 | 19.92 | 426.17 | 19.78 | 426.17 | 19.73 |
February | 442.50 | 20.31 | 330.50 | 20.14 | 325.50 | 20.05 |
March | 476.17 | 20.87 | 268.50 | 20.71 | 257.33 | 20.59 |
April | 390.33 | 21.17 | 186.83 | 21.28 | 128.17 | 21.08 |
May | 344.83 | 22.05 | 117.33 | 22.58 | 10.00 | 22.53 |
June | 197.50 | 22.35 | 251.50 | 23.35 | 10.50 | 23.39 |
July | 117.50 | 23.06 | 340.83 | 23.91 | 19.83 | 23.98 |
August | 141.33 | 22.64 | 319.50 | 23.67 | 11.17 | 23.69 |
September | 259.50 | 22.09 | 198.83 | 22.99 | 20.33 | 22.98 |
October | 405.67 | 21.31 | 134.83 | 21.47 | 83.33 | 21.31 |
November | 465.33 | 20.62 | 262.33 | 20.42 | 250.17 | 20.27 |
December | 483.50 | 20.23 | 408.00 | 20.07 | 408.00 | 20.01 |
Annual Sum or Average | 4221.00 | 21.03 | 3245.17 | 21.32 | 1950.50 | 21.06 |
Minimum of Months | 117.50 | 19.92 | 117.33 | 19.78 | 10.00 | 19.73 |
Maximum of Months | 496.83 | 23.06 | 426.17 | 23.91 | 426.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 488.83 | 19.69 | 488.83 | 19.69 |
February | 452.83 | 20.03 | 395.83 | 19.94 | 395.83 | 19.91 |
March | 509.00 | 20.69 | 311.17 | 20.53 | 310.50 | 20.45 |
April | 414.00 | 21.09 | 182.67 | 21.09 | 142.50 | 20.92 |
May | 364.17 | 21.92 | 112.67 | 22.43 | 12.00 | 22.41 |
June | 199.83 | 22.43 | 260.67 | 23.44 | 18.50 | 23.53 |
July | 129.33 | 23.29 | 335.83 | 24.01 | 32.17 | 24.14 |
August | 154.67 | 22.58 | 307.00 | 23.59 | 14.33 | 23.64 |
September | 311.00 | 21.79 | 150.83 | 22.47 | 19.67 | 22.42 |
October | 479.83 | 21.05 | 147.50 | 20.91 | 137.33 | 20.78 |
November | 484.33 | 20.30 | 304.67 | 20.11 | 303.50 | 20.02 |
December | 497.00 | 19.87 | 474.83 | 19.84 | 474.83 | 19.83 |
Annual Sum or Average | 4498.00 | 20.85 | 3472.50 | 21.09 | 2350.00 | 20.85 |
Minimum of Months | 129.33 | 19.71 | 112.67 | 19.69 | 12.00 | 19.69 |
Maximum of Months | 509.00 | 23.29 | 488.83 | 24.01 | 488.83 | 24.14 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.48599 | 13.41088 | -0.5108 | 11.92176 |
February | 454.00000 | 22.22029 | 17.19562 | -0.3008 | 8.12425 |
March | 514.00000 | 23.10745 | 21.64032 | -0.0413 | 6.17464 |
April | 485.00000 | 23.73370 | 28.29095 | 0.17552 | 6.56360 |
May | 508.00000 | 24.31905 | 40.69511 | -0.4434 | 9.87009 |
June | 496.00000 | 24.35293 | 48.12581 | -0.3192 | 7.69519 |
July | 497.00000 | 24.48640 | 51.43902 | -0.2360 | 6.76126 |
August | 514.00000 | 24.42956 | 51.11609 | -0.2505 | 6.86102 |
September | 485.00000 | 24.38269 | 38.25021 | -0.3922 | 9.18777 |
October | 502.00000 | 24.09176 | 26.65386 | 0.25817 | 6.62214 |
November | 489.00000 | 23.31400 | 23.38315 | 0.02503 | 6.93446 |
December | 497.00000 | 22.31888 | 15.60586 | -0.2870 | 7.81680 |
Annual Sum or Average | 5943.00000 | 23.52926 | 31.44670 | -0.1935 | 7.87553 |
Minimum of Months | 454.00000 | 21.48599 | 13.41088 | -0.5108 | 6.17464 |
Maximum of Months | 514.00000 | 24.48640 | 51.43902 | 0.25817 | 11.92176 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.58054 | 14.26827 | -0.7368 | 18.37601 |
February | 454.00000 | 21.03476 | 18.44373 | -0.5845 | 13.82774 |
March | 514.00000 | 21.86832 | 23.56869 | -0.3305 | 8.79028 |
April | 485.00000 | 22.63102 | 30.54115 | -0.0794 | 7.08355 |
May | 508.00000 | 23.65500 | 42.44799 | -0.6711 | 15.61361 |
June | 496.00000 | 23.98958 | 48.73804 | -0.4654 | 10.40054 |
July | 497.00000 | 24.19930 | 51.61717 | -0.3631 | 8.13597 |
August | 514.00000 | 24.13362 | 51.47137 | -0.3878 | 8.50106 |
September | 485.00000 | 23.78999 | 39.54008 | -0.6249 | 14.89170 |
October | 502.00000 | 22.77469 | 29.75593 | -0.0560 | 5.93043 |
November | 489.00000 | 21.82715 | 25.80527 | -0.3315 | 9.99346 |
December | 497.00000 | 20.94298 | 16.83610 | -0.6187 | 14.62629 |
Annual Sum or Average | 5943.00000 | 22.63134 | 32.88092 | -0.4368 | 11.32684 |
Minimum of Months | 454.00000 | 20.58054 | 14.26827 | -0.7368 | 5.93043 |
Maximum of Months | 514.00000 | 24.19930 | 51.61717 | -0.0560 | 18.37601 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06366 | 14.69340 | -0.9051 | 24.69676 |
February | 454.00000 | 20.34911 | 19.04545 | -0.7837 | 20.20563 |
March | 514.00000 | 21.03716 | 24.21791 | -0.5453 | 12.82742 |
April | 485.00000 | 21.76644 | 30.93895 | -0.2851 | 9.77127 |
May | 508.00000 | 23.00167 | 43.25292 | -0.8687 | 23.24652 |
June | 496.00000 | 23.58282 | 48.44417 | -0.5857 | 14.29476 |
July | 497.00000 | 23.88190 | 50.82732 | -0.4585 | 10.32393 |
August | 514.00000 | 23.73773 | 51.04766 | -0.5153 | 11.57848 |
September | 485.00000 | 22.95951 | 40.14944 | -0.9005 | 25.33471 |
October | 502.00000 | 21.43103 | 31.04291 | -0.3764 | 9.37261 |
November | 489.00000 | 20.69261 | 26.54573 | -0.6238 | 16.27543 |
December | 497.00000 | 20.20505 | 17.27919 | -0.8403 | 22.02948 |
Annual Sum or Average | 5943.00000 | 21.90595 | 33.24941 | -0.6397 | 16.62207 |
Minimum of Months | 454.00000 | 20.06366 | 14.69340 | -0.9051 | 9.37261 |
Maximum of Months | 514.00000 | 23.88190 | 51.04766 | -0.2851 | 25.33471 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.62902 | 14.19006 | -1.1400 | 34.29365 |
February | 454.00000 | 19.76441 | 18.90839 | -1.0235 | 29.65667 |
March | 514.00000 | 20.33737 | 24.48147 | -0.7692 | 19.54160 |
April | 485.00000 | 20.79648 | 32.24110 | -0.5254 | 14.39246 |
May | 508.00000 | 21.77453 | 45.81732 | -1.2052 | 37.97924 |
June | 496.00000 | 22.73330 | 51.30803 | -0.7792 | 21.73923 |
July | 497.00000 | 23.05809 | 54.67489 | -0.6324 | 15.96848 |
August | 514.00000 | 22.72372 | 54.68281 | -0.7592 | 19.81170 |
September | 485.00000 | 21.79000 | 42.73815 | -1.2403 | 40.18184 |
October | 502.00000 | 20.44218 | 32.31144 | -0.6281 | 15.04436 |
November | 489.00000 | 19.91483 | 27.15236 | -0.8681 | 24.45028 |
December | 497.00000 | 19.68858 | 17.05209 | -1.0767 | 31.57531 |
Annual Sum or Average | 5943.00000 | 21.06634 | 34.76920 | -0.8862 | 25.33897 |
Minimum of Months | 454.00000 | 19.62902 | 14.19006 | -1.2403 | 14.39246 |
Maximum of Months | 514.00000 | 23.05809 | 54.68281 | -0.5254 | 40.18184 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.63418 | 14.39751 | -1.1153 | 33.39627 |
February | 454.00000 | 19.79152 | 19.10001 | -0.9836 | 28.26206 |
March | 514.00000 | 20.44310 | 24.51888 | -0.7063 | 18.02617 |
April | 485.00000 | 21.26167 | 31.53614 | -0.3886 | 13.13402 |
May | 508.00000 | 22.45655 | 44.41272 | -0.9422 | 28.95653 |
June | 496.00000 | 23.21123 | 49.96742 | -0.5691 | 17.52706 |
July | 497.00000 | 23.63074 | 52.96806 | -0.3873 | 11.64239 |
August | 514.00000 | 23.20817 | 53.24349 | -0.5529 | 14.88284 |
September | 485.00000 | 22.36748 | 41.43752 | -1.0035 | 32.33198 |
October | 502.00000 | 20.66315 | 32.14561 | -0.5483 | 12.94994 |
November | 489.00000 | 19.97488 | 27.30436 | -0.8402 | 23.37305 |
December | 497.00000 | 19.70899 | 17.22518 | -1.0556 | 30.76484 |
Annual Sum or Average | 5943.00000 | 21.37637 | 34.15472 | -0.7560 | 22.03806 |
Minimum of Months | 454.00000 | 19.63418 | 14.39751 | -1.1153 | 11.64239 |
Maximum of Months | 514.00000 | 23.63074 | 53.24349 | -0.3873 | 33.39627 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.75873 | 14.08737 | -1.0131 | 30.17749 |
February | 454.00000 | 20.08555 | 18.48276 | -0.8552 | 24.60461 |
March | 514.00000 | 20.74782 | 23.84552 | -0.6123 | 16.74165 |
April | 485.00000 | 21.40901 | 31.06501 | -0.3474 | 13.76286 |
May | 508.00000 | 22.20065 | 44.86501 | -1.0454 | 32.74785 |
June | 496.00000 | 22.88675 | 50.83761 | -0.7093 | 20.89597 |
July | 497.00000 | 23.30299 | 53.90559 | -0.5249 | 14.56395 |
August | 514.00000 | 23.09823 | 53.47253 | -0.5926 | 16.58565 |
September | 485.00000 | 22.50970 | 41.01188 | -0.9392 | 31.09806 |
October | 502.00000 | 21.27347 | 30.83742 | -0.3783 | 12.24478 |
November | 489.00000 | 20.32245 | 26.57616 | -0.7224 | 20.52292 |
December | 497.00000 | 19.98468 | 16.71813 | -0.9339 | 27.07196 |
Annual Sum or Average | 5943.00000 | 21.47667 | 33.94663 | -0.7221 | 21.72023 |
Minimum of Months | 454.00000 | 19.75873 | 14.08737 | -1.0454 | 12.24478 |
Maximum of Months | 514.00000 | 23.30299 | 53.90559 | -0.3474 | 32.74785 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.63194 | 14.37279 | -1.1186 | 33.58459 |
February | 454.00000 | 19.85719 | 18.95202 | -0.9732 | 27.98168 |
March | 514.00000 | 20.47782 | 24.46684 | -0.7104 | 18.43103 |
April | 485.00000 | 21.24516 | 31.61811 | -0.3891 | 14.16109 |
May | 508.00000 | 22.14550 | 45.17325 | -1.0528 | 33.51770 |
June | 496.00000 | 22.98554 | 50.66849 | -0.6472 | 20.19113 |
July | 497.00000 | 23.39423 | 53.77492 | -0.4659 | 14.28420 |
August | 514.00000 | 23.06962 | 53.71415 | -0.5916 | 16.75808 |
September | 485.00000 | 22.17418 | 41.96141 | -1.0752 | 35.65888 |
October | 502.00000 | 20.72115 | 32.01774 | -0.5405 | 14.08702 |
November | 489.00000 | 20.01603 | 27.22276 | -0.8325 | 23.41764 |
December | 497.00000 | 19.70788 | 17.21084 | -1.0555 | 30.84294 |
Annual Sum or Average | 5943.00000 | 21.29808 | 34.39926 | -0.7863 | 23.52447 |
Minimum of Months | 454.00000 | 19.63194 | 14.37279 | -1.1186 | 14.08702 |
Maximum of Months | 514.00000 | 23.39423 | 53.77492 | -0.3891 | 35.65888 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68227 | 14.11140 | -1.1206 | 33.23540 |
February | 454.00000 | 19.86345 | 18.92029 | -1.0121 | 28.63470 |
March | 514.00000 | 20.38407 | 24.71601 | -0.7968 | 19.78706 |
April | 485.00000 | 20.64398 | 33.25548 | -0.6170 | 15.10676 |
May | 508.00000 | 21.45336 | 47.95729 | -1.3899 | 45.87930 |
June | 496.00000 | 22.59778 | 53.98163 | -0.8808 | 24.00053 |
July | 497.00000 | 23.18362 | 56.71180 | -0.6407 | 14.85405 |
August | 514.00000 | 23.17745 | 55.67616 | -0.6445 | 14.98893 |
September | 485.00000 | 22.31903 | 42.95988 | -1.0532 | 31.48085 |
October | 502.00000 | 20.97033 | 31.44295 | -0.4632 | 10.09375 |
November | 489.00000 | 20.38240 | 26.64773 | -0.7154 | 18.29247 |
December | 497.00000 | 19.91221 | 16.94565 | -0.9904 | 27.45842 |
Annual Sum or Average | 5943.00000 | 21.22593 | 35.42315 | -0.8596 | 23.62553 |
Minimum of Months | 454.00000 | 19.68227 | 14.11140 | -1.3899 | 10.09375 |
Maximum of Months | 514.00000 | 23.18362 | 56.71180 | -0.4632 | 45.87930 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70037 | 14.39576 | -1.0939 | 32.18088 |
February | 454.00000 | 19.93387 | 19.18438 | -0.9638 | 26.72301 |
March | 514.00000 | 20.47978 | 24.85649 | -0.7336 | 17.96735 |
April | 485.00000 | 21.08485 | 32.59116 | -0.4780 | 13.09906 |
May | 508.00000 | 22.29314 | 46.14625 | -1.0683 | 32.64050 |
June | 496.00000 | 23.31476 | 51.82618 | -0.5932 | 16.82496 |
July | 497.00000 | 23.90551 | 54.37741 | -0.3436 | 9.40369 |
August | 514.00000 | 23.74055 | 53.84094 | -0.4042 | 9.97484 |
September | 485.00000 | 23.07188 | 41.24107 | -0.7599 | 22.52966 |
October | 502.00000 | 21.39031 | 31.03689 | -0.3417 | 8.36900 |
November | 489.00000 | 20.50271 | 26.83073 | -0.6743 | 17.06561 |
December | 497.00000 | 19.95053 | 17.21961 | -0.9654 | 26.48969 |
Annual Sum or Average | 5943.00000 | 21.62781 | 34.60004 | -0.7001 | 19.39107 |
Minimum of Months | 454.00000 | 19.70037 | 14.39576 | -1.0939 | 8.36900 |
Maximum of Months | 514.00000 | 23.90551 | 54.37741 | -0.3417 | 32.64050 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.71092 | 13.70512 | -1.1995 | 37.28663 |
February | 454.00000 | 19.41249 | 18.14683 | -0.9784 | 27.92574 |
March | 514.00000 | 20.25464 | 23.80835 | -0.7273 | 18.87161 |
April | 485.00000 | 20.97207 | 31.76208 | -0.4754 | 14.03700 |
May | 508.00000 | 21.81840 | 46.98920 | -1.2287 | 39.23228 |
June | 496.00000 | 22.78704 | 53.93132 | -0.7899 | 22.17484 |
July | 497.00000 | 23.49431 | 57.03893 | -0.4982 | 12.37357 |
August | 514.00000 | 23.59089 | 55.24871 | -0.4448 | 11.30987 |
September | 485.00000 | 23.03290 | 40.83175 | -0.7363 | 22.96428 |
October | 502.00000 | 21.79850 | 29.48483 | -0.1991 | 8.24186 |
November | 489.00000 | 20.52782 | 25.64015 | -0.6068 | 17.11866 |
December | 497.00000 | 19.50061 | 16.24109 | -0.9736 | 27.89943 |
Annual Sum or Average | 5943.00000 | 21.33951 | 34.55191 | -0.7371 | 21.58976 |
Minimum of Months | 454.00000 | 18.71092 | 13.70512 | -1.2287 | 8.24186 |
Maximum of Months | 514.00000 | 23.59089 | 57.03893 | -0.1991 | 39.23228 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69759 | 14.35040 | -1.0985 | 32.40318 |
February | 454.00000 | 19.96891 | 19.05856 | -0.9585 | 26.60791 |
March | 514.00000 | 20.49758 | 24.79567 | -0.7403 | 18.24808 |
April | 485.00000 | 21.08649 | 32.55962 | -0.4685 | 13.36762 |
May | 508.00000 | 21.97936 | 46.91096 | -1.1825 | 37.40278 |
June | 496.00000 | 23.13347 | 52.41824 | -0.6600 | 18.77029 |
July | 497.00000 | 23.81471 | 54.72309 | -0.3770 | 10.15018 |
August | 514.00000 | 23.73161 | 53.94822 | -0.4047 | 10.14500 |
September | 485.00000 | 22.88825 | 41.65434 | -0.8260 | 24.96373 |
October | 502.00000 | 21.36792 | 30.98949 | -0.3476 | 8.96346 |
November | 489.00000 | 20.51688 | 26.76264 | -0.6707 | 17.28578 |
December | 497.00000 | 19.94237 | 17.19985 | -0.9673 | 26.63958 |
Annual Sum or Average | 5943.00000 | 21.56521 | 34.75420 | -0.7238 | 20.37333 |
Minimum of Months | 454.00000 | 19.69759 | 14.35040 | -1.1825 | 8.96346 |
Maximum of Months | 514.00000 | 23.81471 | 54.72309 | -0.3476 | 37.40278 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69979 | 13.79515 | -1.0759 | 31.55542 |
February | 454.00000 | 19.90849 | 18.56548 | -0.9443 | 26.23628 |
March | 514.00000 | 20.53808 | 24.21546 | -0.6831 | 16.47024 |
April | 485.00000 | 21.07753 | 32.06815 | -0.4333 | 11.84279 |
May | 508.00000 | 22.27992 | 45.05891 | -1.0463 | 30.73918 |
June | 496.00000 | 23.23991 | 51.10771 | -0.6314 | 16.28875 |
July | 497.00000 | 23.59074 | 54.54465 | -0.4802 | 11.18702 |
August | 514.00000 | 23.34086 | 54.30620 | -0.5745 | 13.47676 |
September | 485.00000 | 22.35426 | 42.31800 | -1.0382 | 31.32364 |
October | 502.00000 | 20.87343 | 31.86061 | -0.4841 | 10.86926 |
November | 489.00000 | 20.23779 | 26.70838 | -0.7438 | 19.83217 |
December | 497.00000 | 19.84299 | 16.61423 | -0.9885 | 27.72330 |
Annual Sum or Average | 5943.00000 | 21.42898 | 34.40199 | -0.7589 | 20.57345 |
Minimum of Months | 454.00000 | 19.69979 | 13.79515 | -1.0759 | 10.86926 |
Maximum of Months | 514.00000 | 23.59074 | 54.54465 | -0.4333 | 31.55542 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.47882 | 13.98770 | -1.1047 | 33.08726 |
February | 385.00000 | 19.78707 | 18.71677 | -0.9431 | 26.49997 |
March | 433.00000 | 20.63979 | 24.21535 | -0.6327 | 15.87628 |
April | 410.00000 | 21.57182 | 31.04119 | -0.2995 | 11.59215 |
May | 430.00000 | 22.92242 | 43.58914 | -0.8046 | 23.55095 |
June | 418.00000 | 23.53712 | 50.03902 | -0.4837 | 14.45349 |
July | 422.00000 | 23.97206 | 53.16787 | -0.2996 | 9.48297 |
August | 433.00000 | 23.59012 | 53.24518 | -0.4479 | 11.43456 |
September | 410.00000 | 22.84398 | 41.05260 | -0.8406 | 25.85061 |
October | 427.00000 | 21.21133 | 31.24596 | -0.3937 | 9.68342 |
November | 417.00000 | 20.22598 | 26.45775 | -0.7412 | 19.91720 |
December | 422.00000 | 19.67792 | 16.78149 | -1.0115 | 28.82570 |
Annual Sum or Average | 5034.00000 | 21.63377 | 33.73674 | -0.6652 | 19.12652 |
Minimum of Months | 385.00000 | 19.47882 | 13.98770 | -1.1047 | 9.48297 |
Maximum of Months | 433.00000 | 23.97206 | 53.24518 | -0.2995 | 33.08726 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95871 | 13.61407 | -0.9226 | 26.78024 |
February | 454.00000 | 20.40000 | 17.95927 | -0.7424 | 20.58749 |
March | 514.00000 | 21.11168 | 23.37632 | -0.4958 | 13.68944 |
April | 485.00000 | 21.77280 | 30.76186 | -0.2398 | 11.44834 |
May | 508.00000 | 22.73496 | 44.03862 | -0.8786 | 25.48703 |
June | 496.00000 | 23.34250 | 50.71608 | -0.5748 | 15.69955 |
July | 497.00000 | 23.77403 | 53.88911 | -0.3888 | 10.24810 |
August | 514.00000 | 23.61273 | 53.29088 | -0.4350 | 11.34768 |
September | 485.00000 | 23.06822 | 40.58896 | -0.7390 | 23.10908 |
October | 502.00000 | 21.89452 | 30.05477 | -0.2003 | 9.36789 |
November | 489.00000 | 20.80994 | 25.96637 | -0.5666 | 16.28021 |
December | 497.00000 | 20.33200 | 16.13756 | -0.8080 | 22.73258 |
Annual Sum or Average | 5943.00000 | 21.91354 | 33.50411 | -0.5817 | 17.19827 |
Minimum of Months | 454.00000 | 19.95871 | 13.61407 | -0.9226 | 9.36789 |
Maximum of Months | 514.00000 | 23.77403 | 53.88911 | -0.2003 | 26.78024 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71178 | 13.92366 | -1.0535 | 30.81969 |
February | 454.00000 | 20.03476 | 18.54589 | -0.8883 | 24.49073 |
March | 514.00000 | 20.72142 | 24.10074 | -0.6176 | 15.38973 |
April | 485.00000 | 21.53075 | 31.39263 | -0.2969 | 11.77311 |
May | 508.00000 | 22.54979 | 44.61149 | -0.9200 | 27.47849 |
June | 496.00000 | 23.34825 | 50.77043 | -0.5364 | 15.85326 |
July | 497.00000 | 23.78356 | 53.97603 | -0.3501 | 10.58328 |
August | 514.00000 | 23.51821 | 53.73605 | -0.4503 | 11.97846 |
September | 485.00000 | 22.62573 | 41.74371 | -0.9031 | 28.26448 |
October | 502.00000 | 21.18407 | 31.47038 | -0.3924 | 10.31738 |
November | 489.00000 | 20.34249 | 26.76867 | -0.7086 | 19.00860 |
December | 497.00000 | 19.87258 | 16.74618 | -0.9662 | 26.99066 |
Annual Sum or Average | 5943.00000 | 21.61554 | 34.11921 | -0.6721 | 19.35837 |
Minimum of Months | 454.00000 | 19.71178 | 13.92366 | -1.0535 | 10.31738 |
Maximum of Months | 514.00000 | 23.78356 | 53.97603 | -0.2969 | 30.81969 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.228790E+12 | 0.00 | 662.99 | 376730.65 | 12-JAN-06:01 | 0.00 | 39.95 | 57.49 | 1.22 | 0.00 | 0.14 | 0.62 | 12-JAN-06:01 |
February | 0.146796E+12 | 0.00 | 531.51 | 395861.70 | 10-FEB-06:11 | 0.00 | 36.74 | 54.57 | 0.80 | 0.00 | 0.10 | 0.65 | 10-FEB-06:11 |
March | 0.850355E+11 | 0.00 | 491.75 | 416269.00 | 23-MAR-05:11 | 0.00 | 31.44 | 49.36 | 0.34 | 0.00 | 0.05 | 0.68 | 23-MAR-05:11 |
April | 0.374316E+11 | 0.00 | 362.12 | 408910.74 | 29-APR-05:11 | 0.00 | 29.57 | 44.03 | 0.14 | 0.00 | 0.02 | 0.67 | 29-APR-05:11 |
May | 0.603091E+10 | 0.00 | 231.37 | 347298.58 | 02-MAY-05:11 | 0.00 | 27.92 | 37.06 | 0.02 | 0.00 | 0.00 | 0.57 | 02-MAY-05:11 |
June | 0.197074E+10 | 0.00 | 123.28 | 187326.09 | 05-JUN-06:03 | 0.00 | 32.23 | 37.08 | 0.01 | 0.00 | 0.00 | 0.31 | 05-JUN-06:03 |
July | 0.117049E+09 | 0.00 | 96.57 | 27541.70 | 24-JUL-06:03 | 0.00 | 29.25 | 33.27 | 0.00 | 0.00 | 0.00 | 0.05 | 24-JUL-06:03 |
August | 0.317989E+09 | 0.00 | 104.76 | 38797.82 | 07-AUG-06:03 | 0.00 | 27.03 | 31.66 | 0.00 | 0.00 | 0.00 | 0.06 | 07-AUG-06:03 |
September | 0.681278E+10 | 0.00 | 203.62 | 346224.16 | 29-SEP-06:02 | 0.00 | 27.31 | 36.22 | 0.02 | 0.00 | 0.00 | 0.57 | 29-SEP-06:02 |
October | 0.242883E+11 | 0.00 | 352.89 | 428672.10 | 24-OCT-05:11 | 0.00 | 25.78 | 41.02 | 0.08 | 0.00 | 0.01 | 0.70 | 24-OCT-05:11 |
November | 0.872128E+11 | 0.00 | 497.65 | 420332.10 | 20-NOV-06:11 | 0.00 | 32.24 | 50.44 | 0.39 | 0.00 | 0.06 | 0.69 | 20-NOV-06:11 |
December | 0.166605E+12 | 0.00 | 608.73 | 374604.04 | 14-DEC-06:01 | 0.00 | 37.63 | 55.64 | 0.79 | 0.00 | 0.10 | 0.61 | 14-DEC-06:01 |
Annual Sum or Average | 0.791408E+12 | 0.00 | 4267.25 | 0.00 | 31.39 | 43.92 | 0.32 | 0.00 | 0.04 | ||||
Minimum of Months | 0.117049E+09 | 0.00 | 96.57 | 27541.70 | 0.00 | 25.78 | 31.66 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.228790E+12 | 0.00 | 662.99 | 428672.10 | 0.00 | 39.95 | 57.49 | 1.22 | 0.00 | 0.14 | 0.70 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 205757.40 | 58329.90 | 0.03 | 205757.40 | -0.0 | 0.00 | 0.06 | 07-FEB-07:12 | 0.00 | 01-FEB-00:03 | 2057.57 | 07-FEB-07:12 | 2057.57 | 07-FEB-07:12 | 0.00 | 01-FEB-00:03 | 583.30 | 07-FEB-07:12 | 0.00 |
March | 0.268532E+09 | 73326470.72 | 12.33 | 0.259237E+09 | 9294462.09 | 0.00 | 0.35 | 25-MAR-15:00 | 0.00 | 01-MAR-00:03 | 12234.94 | 25-MAR-15:00 | 12234.94 | 25-MAR-15:00 | 572.16 | 25-MAR-17:00 | 3235.72 | 25-MAR-15:00 | 0.00 |
April | 0.600465E+10 | 0.148303E+10 | 72.60 | 0.494024E+10 | 0.106441E+10 | 0.00 | 1.00 | 18-APR-08:30 | 0.00 | 01-APR-00:10 | 63777.22 | 18-APR-15:00 | 53489.77 | 18-APR-15:00 | 16245.21 | 18-APR-08:00 | 15651.80 | 18-APR-15:00 | 0.00 |
May | 0.170258E+11 | 0.416621E+10 | 216.65 | 0.133025E+11 | 0.372334E+10 | 0.00 | 1.00 | 05-MAY-14:00 | 0.00 | 01-MAY-00:10 | 64028.95 | 31-MAY-15:00 | 58848.56 | 31-MAY-15:00 | 27020.69 | 30-MAY-09:30 | 16417.56 | 31-MAY-15:00 | 0.00 |
June | 0.483997E+11 | 0.115710E+11 | 340.90 | 0.389064E+11 | 0.949337E+10 | 0.00 | 1.00 | 08-JUN-15:00 | 0.00 | 01-JUN-00:10 | 118172.03 | 30-JUN-05:12 | 70766.26 | 26-JUN-05:12 | 66378.34 | 27-JUN-05:12 | 26324.27 | 30-JUN-05:12 | 0.00 |
July | 0.676457E+11 | 0.157664E+11 | 414.49 | 0.514497E+11 | 0.161960E+11 | 0.00 | 1.00 | 01-JUL-10:05 | 0.00 | 01-JUL-00:10 | 113903.13 | 27-JUL-05:12 | 72290.10 | 26-JUL-05:12 | 71211.01 | 27-JUL-05:12 | 25376.02 | 27-JUL-05:12 | 0.00 |
August | 0.677312E+11 | 0.158780E+11 | 413.01 | 0.521680E+11 | 0.155632E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 135360.28 | 03-AUG-05:12 | 79732.43 | 04-AUG-15:30 | 60429.47 | 03-AUG-05:12 | 29887.20 | 03-AUG-05:12 | 0.00 |
September | 0.290506E+11 | 0.705789E+10 | 234.93 | 0.268151E+11 | 0.223550E+10 | 0.00 | 1.00 | 01-SEP-10:20 | 0.00 | 01-SEP-00:10 | 88371.65 | 11-SEP-05:12 | 76416.22 | 07-SEP-15:20 | 42194.63 | 11-SEP-05:12 | 22568.68 | 06-SEP-14:30 | 0.00 |
October | 0.220162E+10 | 0.556831E+09 | 50.74 | 0.196384E+10 | 0.237779E+09 | 0.00 | 1.00 | 20-OCT-14:15 | 0.00 | 01-OCT-00:10 | 43146.60 | 20-OCT-15:00 | 43146.60 | 20-OCT-15:00 | 6352.53 | 02-OCT-15:00 | 9569.07 | 20-OCT-15:00 | 0.00 |
November | 91096940.66 | 25183874.63 | 5.00 | 84653096.98 | 6443843.68 | 0.00 | 0.21 | 03-NOV-14:40 | 0.00 | 01-NOV-00:10 | 7135.92 | 03-NOV-14:40 | 7135.92 | 03-NOV-14:40 | 804.21 | 03-NOV-12:13 | 1952.86 | 03-NOV-14:40 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.238419E+12 | 0.565779E+11 | 1760.68 | 0.189890E+12 | 0.485294E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.677312E+11 | 0.158780E+11 | 414.49 | 0.521680E+11 | 0.161960E+11 | 0.00 | 1.00 | 0.00 | 135360.28 | 79732.43 | 71211.01 | 29887.20 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 277462.15 | 79652.13 | 0.25 | 275574.15 | 1888.00 | 0.00 | 0.01 | 29-JAN-20:11 | 0.00 | 01-JAN-00:02 | 514.45 | 29-JAN-20:11 | 514.45 | 29-JAN-20:11 | 5.07 | 01-JAN-20:43 | 147.51 | 29-JAN-20:11 | 0.00 |
February | 93301.63 | 26749.83 | 0.05 | 93301.63 | 0.00 | 0.00 | 0.02 | 06-FEB-02:61 | 0.00 | 01-FEB-00:03 | 633.06 | 06-FEB-02:61 | 633.06 | 06-FEB-02:61 | 0.00 | 06-FEB-02:42 | 181.38 | 06-FEB-02:61 | 0.00 |
March | 0.242525E+09 | 66775212.80 | 12.07 | 0.215675E+09 | 26850003.56 | 0.00 | 0.30 | 25-MAR-15:00 | 0.00 | 01-MAR-00:03 | 11694.56 | 25-MAR-15:00 | 11379.36 | 25-MAR-15:00 | 1115.30 | 28-MAR-15:10 | 3131.21 | 25-MAR-15:00 | 0.00 |
April | 0.650559E+10 | 0.163036E+10 | 77.83 | 0.519717E+10 | 0.130841E+10 | 0.00 | 1.00 | 18-APR-09:50 | 0.00 | 01-APR-00:10 | 66787.04 | 18-APR-14:05 | 56097.98 | 18-APR-14:05 | 17113.17 | 18-APR-08:30 | 16380.12 | 18-APR-14:05 | 0.00 |
May | 0.167611E+11 | 0.417418E+10 | 229.40 | 0.127218E+11 | 0.403937E+10 | 0.00 | 1.00 | 05-MAY-15:00 | 0.00 | 01-MAY-00:10 | 65931.59 | 31-MAY-14:05 | 60725.50 | 31-MAY-14:05 | 23277.75 | 30-MAY-09:30 | 16746.81 | 31-MAY-15:00 | 0.00 |
June | 0.461767E+11 | 0.112440E+11 | 345.41 | 0.362440E+11 | 0.993277E+10 | 0.00 | 1.00 | 09-JUN-10:30 | 0.00 | 01-JUN-00:10 | 81390.60 | 27-JUN-14:05 | 68969.29 | 26-JUN-14:05 | 36302.89 | 27-JUN-05:12 | 21411.99 | 26-JUN-14:05 | 0.00 |
July | 0.620158E+11 | 0.146966E+11 | 422.20 | 0.460530E+11 | 0.159628E+11 | 0.00 | 1.00 | 03-JUL-07:15 | 0.00 | 01-JUL-00:10 | 88936.11 | 26-JUL-15:00 | 64858.88 | 03-JUL-15:00 | 46115.87 | 20-JUL-08:00 | 22356.11 | 26-JUL-15:00 | 0.00 |
August | 0.596617E+11 | 0.142486E+11 | 416.89 | 0.445183E+11 | 0.151435E+11 | 0.00 | 1.00 | 01-AUG-07:15 | 0.00 | 01-AUG-00:10 | 98134.26 | 04-AUG-14:05 | 73711.65 | 04-AUG-15:30 | 45432.15 | 31-AUG-11:00 | 27139.92 | 04-AUG-15:30 | 0.00 |
September | 0.249119E+11 | 0.618374E+10 | 232.63 | 0.223033E+11 | 0.260864E+10 | 0.00 | 1.00 | 01-SEP-13:40 | 0.00 | 01-SEP-00:10 | 75597.73 | 06-SEP-14:05 | 69821.01 | 07-SEP-14:05 | 19734.32 | 11-SEP-07:30 | 20432.79 | 06-SEP-14:05 | 0.00 |
October | 0.187590E+10 | 0.489071E+09 | 49.44 | 0.158478E+10 | 0.291112E+09 | 0.00 | 0.80 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 35068.64 | 20-OCT-15:00 | 35068.64 | 20-OCT-15:00 | 6330.14 | 02-OCT-15:00 | 8247.94 | 20-OCT-15:00 | 0.00 |
November | 71645119.92 | 20021917.58 | 4.86 | 61330407.00 | 10314712.93 | 0.00 | 0.16 | 03-NOV-14:02 | 0.00 | 01-NOV-00:10 | 6042.91 | 03-NOV-14:02 | 5490.05 | 03-NOV-14:02 | 923.43 | 03-NOV-12:05 | 1674.01 | 03-NOV-14:02 | 0.00 |
December | 54527.91 | 15622.92 | 0.02 | 54527.91 | 0.00 | 0.00 | 0.02 | 10-DEC-22:01 | 0.00 | 01-DEC-00:10 | 636.16 | 10-DEC-22:01 | 636.16 | 10-DEC-22:01 | 0.00 | 10-DEC-22:01 | 182.27 | 10-DEC-22:01 | 0.00 |
Annual Sum or Average | 0.218223E+12 | 0.527534E+11 | 1791.05 | 0.168900E+12 | 0.493237E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 54527.91 | 15622.92 | 0.02 | 54527.91 | 0.00 | 0.00 | 0.01 | 0.00 | 514.45 | 514.45 | 0.00 | 147.51 | 0.00 | ||||||
Maximum of Months | 0.620158E+11 | 0.146966E+11 | 422.20 | 0.460530E+11 | 0.159628E+11 | 0.00 | 1.00 | 0.00 | 98134.26 | 73711.65 | 46115.87 | 27139.92 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2815194.86 | 806977.23 | 1.12 | 2785239.32 | 29955.54 | 0.00 | 0.03 | 09-JAN-06:05 | 0.00 | 01-JAN-00:02 | 1700.84 | 09-JAN-06:05 | 1700.84 | 09-JAN-06:05 | 47.41 | 14-JAN-05:20 | 485.59 | 09-JAN-06:05 | 0.00 |
February | 3670264.06 | 1051896.55 | 1.43 | 3560872.13 | 109391.93 | 0.00 | 0.03 | 21-FEB-06:06 | 0.00 | 01-FEB-00:03 | 1668.15 | 21-FEB-06:06 | 1668.15 | 21-FEB-06:06 | 64.27 | 08-FEB-05:55 | 476.33 | 21-FEB-06:06 | 0.00 |
March | 0.305411E+09 | 84448215.41 | 12.63 | 0.260867E+09 | 44543840.17 | 0.00 | 0.28 | 25-MAR-15:00 | 0.00 | 01-MAR-00:03 | 15313.16 | 25-MAR-15:00 | 14234.86 | 25-MAR-15:00 | 1792.06 | 28-MAR-15:00 | 4122.94 | 25-MAR-15:00 | 0.00 |
April | 0.820231E+10 | 0.207905E+10 | 76.90 | 0.655101E+10 | 0.165131E+10 | 0.00 | 1.00 | 18-APR-13:00 | 0.00 | 01-APR-00:10 | 77117.56 | 18-APR-15:00 | 67562.95 | 18-APR-15:00 | 21309.96 | 18-APR-08:30 | 18837.10 | 18-APR-15:00 | 0.00 |
May | 0.213559E+11 | 0.536957E+10 | 228.51 | 0.161289E+11 | 0.522706E+10 | 0.00 | 1.00 | 30-MAY-13:05 | 0.00 | 01-MAY-00:10 | 79560.50 | 31-MAY-15:00 | 75126.27 | 31-MAY-15:00 | 27660.88 | 30-MAY-09:30 | 20267.69 | 31-MAY-15:00 | 0.00 |
June | 0.558510E+11 | 0.138308E+11 | 343.85 | 0.437688E+11 | 0.120821E+11 | 0.00 | 1.00 | 09-JUN-13:20 | 0.00 | 01-JUN-00:10 | 95644.29 | 26-JUN-14:00 | 84506.88 | 26-JUN-14:00 | 32364.53 | 13-JUN-09:20 | 25241.22 | 26-JUN-14:00 | 0.00 |
July | 0.737260E+11 | 0.178133E+11 | 420.62 | 0.551782E+11 | 0.185478E+11 | 0.00 | 1.00 | 03-JUL-10:00 | 0.00 | 01-JUL-00:10 | 100039.81 | 26-JUL-15:10 | 78594.48 | 03-JUL-15:20 | 43479.74 | 20-JUL-08:00 | 25040.31 | 26-JUL-15:20 | 0.00 |
August | 0.699623E+11 | 0.170438E+11 | 414.59 | 0.518672E+11 | 0.180951E+11 | 0.00 | 1.00 | 01-AUG-12:00 | 0.00 | 01-AUG-00:10 | 111830.39 | 04-AUG-15:30 | 89102.86 | 04-AUG-15:00 | 45290.62 | 31-AUG-11:00 | 30927.66 | 04-AUG-15:30 | 0.00 |
September | 0.293976E+11 | 0.743425E+10 | 229.68 | 0.256360E+11 | 0.376159E+10 | 0.00 | 1.00 | 06-SEP-12:40 | 0.00 | 01-SEP-00:10 | 84767.62 | 06-SEP-14:30 | 81341.32 | 07-SEP-14:00 | 22820.30 | 11-SEP-07:30 | 22723.28 | 06-SEP-14:30 | 0.00 |
October | 0.229435E+10 | 0.604593E+09 | 47.68 | 0.187148E+10 | 0.422861E+09 | 0.00 | 0.67 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 40654.97 | 20-OCT-15:00 | 40654.97 | 20-OCT-15:00 | 8403.51 | 02-OCT-15:00 | 9896.73 | 20-OCT-15:00 | 0.00 |
November | 80084354.52 | 22538219.82 | 5.97 | 64246416.75 | 15837937.77 | 0.00 | 0.13 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6606.00 | 03-NOV-14:00 | 5379.08 | 03-NOV-14:00 | 1256.07 | 03-NOV-13:25 | 1845.85 | 03-NOV-14:00 | 0.00 |
December | 3423798.72 | 980133.12 | 1.24 | 3364101.39 | 59697.33 | 0.00 | 0.05 | 11-DEC-06:37 | 0.00 | 01-DEC-00:10 | 2416.35 | 11-DEC-06:37 | 2416.35 | 11-DEC-06:37 | 57.90 | 31-DEC-11:30 | 687.69 | 11-DEC-06:37 | 0.00 |
Annual Sum or Average | 0.261185E+12 | 0.642852E+11 | 1784.22 | 0.201336E+12 | 0.598485E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2815194.86 | 806977.23 | 1.12 | 2785239.32 | 29955.54 | 0.00 | 0.03 | 0.00 | 1668.15 | 1668.15 | 47.41 | 476.33 | 0.00 | ||||||
Maximum of Months | 0.737260E+11 | 0.178133E+11 | 420.62 | 0.551782E+11 | 0.185478E+11 | 0.00 | 1.00 | 0.00 | 111830.39 | 89102.86 | 45290.62 | 30927.66 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.34 | 0.00 | 354.34 | 0.00 | 4400.68 | 0.00 | 0.00 | 0.00 |
February | 449.23 | 0.00 | 449.23 | 3.70 | 3557.95 | 0.00 | 0.00 | 0.00 |
March | 673.26 | 0.00 | 673.26 | 105.32 | 2268.84 | 0.00 | 0.00 | 0.00 |
April | 777.23 | 3.83 | 773.40 | 329.93 | 1520.93 | 0.00 | 0.00 | 0.00 |
May | 1013.53 | 38.10 | 975.43 | 786.67 | 790.55 | 0.00 | 0.00 | 0.00 |
June | 1184.58 | 107.52 | 1077.06 | 1300.92 | 549.90 | 0.00 | 0.00 | 0.00 |
July | 1110.95 | 74.31 | 1036.64 | 1292.44 | 463.67 | 0.00 | 0.00 | 0.00 |
August | 930.19 | 16.49 | 913.71 | 1094.54 | 542.90 | 0.00 | 0.00 | 0.00 |
September | 713.19 | 0.18 | 713.01 | 628.08 | 977.95 | 0.00 | 0.00 | 0.00 |
October | 530.27 | 0.00 | 530.27 | 163.02 | 1551.11 | 0.00 | 0.00 | 0.00 |
November | 370.93 | 0.00 | 370.93 | 29.56 | 2562.07 | 0.00 | 0.00 | 0.00 |
December | 240.61 | 0.00 | 240.61 | 0.00 | 3788.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.00 | 20.11 | 676.88 | 480.71 | 1906.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 240.61 | 0.00 | 240.61 | 0.00 | 463.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1184.58 | 107.52 | 1077.06 | 1300.92 | 4400.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.18 | 208.29 | 297.89 | 131.05 | 2628.87 | 0.00 | 0.00 | 0.00 |
February | 670.94 | 295.02 | 375.91 | 277.92 | 2068.72 | 0.00 | 0.00 | 0.00 |
March | 911.60 | 361.84 | 549.76 | 565.01 | 1348.91 | 0.00 | 0.00 | 0.00 |
April | 1119.36 | 490.20 | 629.16 | 961.38 | 951.81 | 0.00 | 0.00 | 0.00 |
May | 1405.82 | 614.28 | 791.54 | 1472.52 | 529.24 | 0.00 | 0.00 | 0.00 |
June | 1547.07 | 673.72 | 873.35 | 1875.74 | 372.18 | 0.00 | 0.00 | 0.00 |
July | 1563.69 | 721.52 | 842.17 | 1954.46 | 313.92 | 0.00 | 0.00 | 0.00 |
August | 1318.16 | 568.29 | 749.88 | 1659.54 | 364.57 | 0.00 | 0.00 | 0.00 |
September | 1175.68 | 555.57 | 620.11 | 1336.06 | 622.03 | 0.00 | 0.00 | 0.00 |
October | 749.22 | 312.94 | 436.28 | 575.21 | 946.01 | 0.00 | 0.00 | 0.00 |
November | 442.05 | 143.59 | 298.46 | 171.60 | 1580.16 | 0.00 | 0.00 | 0.00 |
December | 342.42 | 147.04 | 195.37 | 104.75 | 2324.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 980.88 | 424.97 | 555.91 | 927.30 | 1166.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.42 | 143.59 | 195.37 | 104.75 | 313.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1563.69 | 721.52 | 873.35 | 1954.46 | 2628.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2203.57 | 1507.95 | 695.62 | 1614.60 | 3473.72 | 0.00 | 0.00 | 0.00 |
February | 2361.09 | 1595.17 | 765.92 | 1846.05 | 2779.23 | 0.00 | 0.00 | 0.00 |
March | 2054.68 | 1081.92 | 972.76 | 1730.32 | 2006.57 | 0.00 | 0.00 | 0.00 |
April | 1851.13 | 865.44 | 985.70 | 1839.42 | 1502.79 | 0.00 | 0.00 | 0.00 |
May | 1533.60 | 415.78 | 1117.83 | 1648.59 | 867.42 | 0.00 | 0.00 | 0.00 |
June | 1488.90 | 303.15 | 1185.75 | 1860.32 | 600.76 | 0.00 | 0.00 | 0.00 |
July | 1576.10 | 397.13 | 1178.97 | 2072.17 | 504.15 | 0.00 | 0.00 | 0.00 |
August | 1775.74 | 636.82 | 1138.92 | 2392.34 | 593.66 | 0.00 | 0.00 | 0.00 |
September | 2151.82 | 1133.83 | 1017.99 | 2653.90 | 992.10 | 0.00 | 0.00 | 0.00 |
October | 2246.95 | 1409.64 | 837.31 | 2309.67 | 1445.45 | 0.00 | 0.00 | 0.00 |
November | 1695.32 | 1061.30 | 634.02 | 1401.50 | 2213.36 | 0.00 | 0.00 | 0.00 |
December | 1807.81 | 1369.39 | 438.42 | 1513.90 | 3176.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1892.81 | 977.95 | 914.86 | 1907.05 | 1674.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1488.90 | 303.15 | 438.42 | 1401.50 | 504.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2361.09 | 1595.17 | 1185.75 | 2653.90 | 3473.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.01 | 203.12 | 298.89 | 147.84 | 2704.02 | 0.00 | 0.00 | 0.00 |
February | 736.10 | 362.73 | 373.38 | 364.18 | 2159.88 | 0.00 | 0.00 | 0.00 |
March | 878.76 | 326.94 | 551.81 | 527.96 | 1406.34 | 0.00 | 0.00 | 0.00 |
April | 1281.84 | 633.85 | 648.00 | 1203.27 | 997.36 | 0.00 | 0.00 | 0.00 |
May | 1285.55 | 513.54 | 772.01 | 1366.34 | 566.98 | 0.00 | 0.00 | 0.00 |
June | 1508.44 | 653.72 | 854.72 | 1860.10 | 408.28 | 0.00 | 0.00 | 0.00 |
July | 1619.61 | 769.34 | 850.27 | 2066.72 | 352.52 | 0.00 | 0.00 | 0.00 |
August | 1415.94 | 649.82 | 766.12 | 1827.09 | 399.25 | 0.00 | 0.00 | 0.00 |
September | 1146.17 | 544.03 | 602.14 | 1322.11 | 665.79 | 0.00 | 0.00 | 0.00 |
October | 798.70 | 355.09 | 443.61 | 656.49 | 1005.31 | 0.00 | 0.00 | 0.00 |
November | 478.07 | 176.79 | 301.28 | 231.88 | 1616.77 | 0.00 | 0.00 | 0.00 |
December | 367.66 | 173.32 | 194.34 | 144.06 | 2372.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1002.63 | 446.94 | 555.69 | 979.59 | 1216.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.66 | 173.32 | 194.34 | 144.06 | 352.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1619.61 | 769.34 | 854.72 | 2066.72 | 2704.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.11 | 0.00 | 118.11 | 0.00 | 1452.77 | 0.00 | 0.00 | 0.00 |
February | 149.74 | 0.00 | 149.74 | 1.24 | 1172.92 | 0.00 | 0.00 | 0.00 |
March | 224.41 | 0.00 | 224.41 | 41.21 | 741.56 | 0.00 | 0.00 | 0.00 |
April | 259.07 | 1.28 | 257.79 | 127.26 | 487.20 | 0.00 | 0.00 | 0.00 |
May | 337.83 | 12.70 | 325.13 | 291.80 | 247.68 | 0.00 | 0.00 | 0.00 |
June | 394.85 | 35.84 | 359.01 | 454.78 | 175.93 | 0.00 | 0.00 | 0.00 |
July | 370.30 | 24.77 | 345.53 | 442.10 | 154.53 | 0.00 | 0.00 | 0.00 |
August | 310.05 | 5.49 | 304.56 | 365.32 | 192.15 | 0.00 | 0.00 | 0.00 |
September | 237.72 | 0.06 | 237.66 | 205.69 | 354.97 | 0.00 | 0.00 | 0.00 |
October | 176.75 | 0.00 | 176.75 | 49.56 | 567.59 | 0.00 | 0.00 | 0.00 |
November | 123.64 | 0.00 | 123.64 | 8.63 | 896.79 | 0.00 | 0.00 | 0.00 |
December | 80.20 | 0.00 | 80.20 | 0.00 | 1278.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.32 | 6.70 | 225.62 | 166.62 | 641.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.20 | 0.00 | 80.20 | 0.00 | 154.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.85 | 35.84 | 359.01 | 454.78 | 1452.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.11 | 0.00 | 118.11 | 0.00 | 1452.86 | 0.00 | 0.00 | 0.00 |
February | 149.75 | 0.00 | 149.75 | 1.24 | 1173.00 | 0.00 | 0.00 | 0.00 |
March | 224.42 | 0.00 | 224.42 | 41.21 | 741.61 | 0.00 | 0.00 | 0.00 |
April | 259.08 | 1.28 | 257.80 | 127.27 | 487.23 | 0.00 | 0.00 | 0.00 |
May | 337.85 | 12.70 | 325.15 | 291.82 | 247.69 | 0.00 | 0.00 | 0.00 |
June | 394.86 | 35.84 | 359.03 | 454.80 | 175.94 | 0.00 | 0.00 | 0.00 |
July | 370.32 | 24.77 | 345.55 | 442.12 | 154.54 | 0.00 | 0.00 | 0.00 |
August | 310.07 | 5.50 | 304.57 | 365.34 | 192.16 | 0.00 | 0.00 | 0.00 |
September | 237.73 | 0.06 | 237.67 | 205.70 | 355.00 | 0.00 | 0.00 | 0.00 |
October | 176.76 | 0.00 | 176.76 | 49.57 | 567.63 | 0.00 | 0.00 | 0.00 |
November | 123.64 | 0.00 | 123.64 | 8.63 | 896.85 | 0.00 | 0.00 | 0.00 |
December | 80.20 | 0.00 | 80.20 | 0.00 | 1279.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.33 | 6.70 | 225.63 | 166.63 | 641.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.20 | 0.00 | 80.20 | 0.00 | 154.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.86 | 35.84 | 359.03 | 454.80 | 1452.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.11 | 0.00 | 118.11 | 0.00 | 1452.86 | 0.00 | 0.00 | 0.00 |
February | 149.75 | 0.00 | 149.75 | 1.24 | 1173.00 | 0.00 | 0.00 | 0.00 |
March | 224.42 | 0.00 | 224.42 | 41.21 | 741.61 | 0.00 | 0.00 | 0.00 |
April | 259.08 | 1.28 | 257.80 | 127.27 | 487.23 | 0.00 | 0.00 | 0.00 |
May | 337.85 | 12.70 | 325.15 | 291.82 | 247.69 | 0.00 | 0.00 | 0.00 |
June | 394.86 | 35.84 | 359.03 | 454.80 | 175.94 | 0.00 | 0.00 | 0.00 |
July | 370.32 | 24.77 | 345.55 | 442.12 | 154.54 | 0.00 | 0.00 | 0.00 |
August | 310.07 | 5.50 | 304.57 | 365.34 | 192.16 | 0.00 | 0.00 | 0.00 |
September | 237.73 | 0.06 | 237.67 | 205.70 | 355.00 | 0.00 | 0.00 | 0.00 |
October | 176.76 | 0.00 | 176.76 | 49.57 | 567.63 | 0.00 | 0.00 | 0.00 |
November | 123.64 | 0.00 | 123.64 | 8.63 | 896.85 | 0.00 | 0.00 | 0.00 |
December | 80.20 | 0.00 | 80.20 | 0.00 | 1279.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.33 | 6.70 | 225.63 | 166.63 | 641.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.20 | 0.00 | 80.20 | 0.00 | 154.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 394.86 | 35.84 | 359.03 | 454.80 | 1452.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 486.94 | 200.38 | 286.56 | 132.18 | 2515.87 | 0.00 | 0.00 | 0.00 |
February | 645.44 | 283.81 | 361.63 | 276.56 | 1987.29 | 0.00 | 0.00 | 0.00 |
March | 876.96 | 348.09 | 528.87 | 567.55 | 1287.17 | 0.00 | 0.00 | 0.00 |
April | 1076.82 | 471.57 | 605.24 | 968.09 | 894.21 | 0.00 | 0.00 | 0.00 |
May | 1352.40 | 590.94 | 761.46 | 1470.61 | 496.89 | 0.00 | 0.00 | 0.00 |
June | 1488.28 | 648.12 | 840.16 | 1837.21 | 361.75 | 0.00 | 0.00 | 0.00 |
July | 1504.27 | 694.10 | 810.16 | 1898.21 | 318.85 | 0.00 | 0.00 | 0.00 |
August | 1268.07 | 546.69 | 721.38 | 1596.97 | 385.99 | 0.00 | 0.00 | 0.00 |
September | 1131.00 | 534.46 | 596.55 | 1273.49 | 672.85 | 0.00 | 0.00 | 0.00 |
October | 720.75 | 301.05 | 419.70 | 533.72 | 1017.62 | 0.00 | 0.00 | 0.00 |
November | 425.25 | 138.13 | 287.12 | 158.48 | 1606.04 | 0.00 | 0.00 | 0.00 |
December | 329.40 | 141.45 | 187.95 | 100.87 | 2274.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 943.60 | 408.82 | 534.78 | 904.56 | 1147.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.40 | 138.13 | 187.95 | 100.87 | 318.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1504.27 | 694.10 | 840.16 | 1898.21 | 2515.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.25 | 7.92 | 11.33 | 5.23 | 99.48 | 0.00 | 0.00 | 0.00 |
February | 25.52 | 11.22 | 14.30 | 10.94 | 78.58 | 0.00 | 0.00 | 0.00 |
March | 34.67 | 13.76 | 20.91 | 22.44 | 50.89 | 0.00 | 0.00 | 0.00 |
April | 42.58 | 18.65 | 23.93 | 38.28 | 35.36 | 0.00 | 0.00 | 0.00 |
May | 53.47 | 23.37 | 30.11 | 58.15 | 19.65 | 0.00 | 0.00 | 0.00 |
June | 58.85 | 25.63 | 33.22 | 72.64 | 14.30 | 0.00 | 0.00 | 0.00 |
July | 59.48 | 27.44 | 32.03 | 75.05 | 12.61 | 0.00 | 0.00 | 0.00 |
August | 50.14 | 21.62 | 28.52 | 63.14 | 15.26 | 0.00 | 0.00 | 0.00 |
September | 44.72 | 21.13 | 23.59 | 50.35 | 26.60 | 0.00 | 0.00 | 0.00 |
October | 28.50 | 11.90 | 16.59 | 21.10 | 40.24 | 0.00 | 0.00 | 0.00 |
November | 16.81 | 5.46 | 11.35 | 6.27 | 63.50 | 0.00 | 0.00 | 0.00 |
December | 13.02 | 5.59 | 7.43 | 3.99 | 89.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.31 | 16.16 | 21.14 | 35.77 | 45.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.02 | 5.46 | 7.43 | 3.99 | 12.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.48 | 27.44 | 33.22 | 75.05 | 99.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.54 | 502.66 | 231.88 | 559.84 | 1137.81 | 0.00 | 0.00 | 0.00 |
February | 787.05 | 531.74 | 255.31 | 639.14 | 926.57 | 0.00 | 0.00 | 0.00 |
March | 684.91 | 360.65 | 324.26 | 601.92 | 666.00 | 0.00 | 0.00 | 0.00 |
April | 617.06 | 288.49 | 328.57 | 640.90 | 492.75 | 0.00 | 0.00 | 0.00 |
May | 511.21 | 138.60 | 372.62 | 580.01 | 278.78 | 0.00 | 0.00 | 0.00 |
June | 496.31 | 101.05 | 395.26 | 640.71 | 196.18 | 0.00 | 0.00 | 0.00 |
July | 525.38 | 132.38 | 393.00 | 702.46 | 173.61 | 0.00 | 0.00 | 0.00 |
August | 591.93 | 212.28 | 379.65 | 801.09 | 218.46 | 0.00 | 0.00 | 0.00 |
September | 717.29 | 377.95 | 339.34 | 885.47 | 373.86 | 0.00 | 0.00 | 0.00 |
October | 749.00 | 469.89 | 279.11 | 768.35 | 547.15 | 0.00 | 0.00 | 0.00 |
November | 565.12 | 353.78 | 211.34 | 467.05 | 784.92 | 0.00 | 0.00 | 0.00 |
December | 602.62 | 456.48 | 146.14 | 513.06 | 1073.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 630.95 | 325.99 | 304.96 | 650.00 | 570.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.31 | 101.05 | 146.14 | 467.05 | 173.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.05 | 531.74 | 395.26 | 885.47 | 1137.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.54 | 502.66 | 231.88 | 559.84 | 1137.81 | 0.00 | 0.00 | 0.00 |
February | 787.05 | 531.74 | 255.31 | 639.14 | 926.57 | 0.00 | 0.00 | 0.00 |
March | 684.91 | 360.65 | 324.26 | 601.92 | 666.00 | 0.00 | 0.00 | 0.00 |
April | 617.06 | 288.49 | 328.57 | 640.90 | 492.75 | 0.00 | 0.00 | 0.00 |
May | 511.21 | 138.60 | 372.62 | 580.01 | 278.78 | 0.00 | 0.00 | 0.00 |
June | 496.31 | 101.05 | 395.26 | 640.71 | 196.18 | 0.00 | 0.00 | 0.00 |
July | 525.38 | 132.38 | 393.00 | 702.46 | 173.61 | 0.00 | 0.00 | 0.00 |
August | 591.93 | 212.28 | 379.65 | 801.09 | 218.46 | 0.00 | 0.00 | 0.00 |
September | 717.29 | 377.95 | 339.34 | 885.47 | 373.86 | 0.00 | 0.00 | 0.00 |
October | 749.00 | 469.89 | 279.11 | 768.35 | 547.15 | 0.00 | 0.00 | 0.00 |
November | 565.12 | 353.78 | 211.34 | 467.05 | 784.92 | 0.00 | 0.00 | 0.00 |
December | 602.62 | 456.48 | 146.14 | 513.06 | 1073.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 630.95 | 325.99 | 304.96 | 650.00 | 570.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.31 | 101.05 | 146.14 | 467.05 | 173.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.05 | 531.74 | 395.26 | 885.47 | 1137.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.50 | 502.63 | 231.87 | 559.81 | 1137.74 | 0.00 | 0.00 | 0.00 |
February | 787.00 | 531.70 | 255.30 | 639.10 | 926.51 | 0.00 | 0.00 | 0.00 |
March | 684.87 | 360.63 | 324.24 | 601.88 | 665.96 | 0.00 | 0.00 | 0.00 |
April | 617.02 | 288.47 | 328.55 | 640.86 | 492.72 | 0.00 | 0.00 | 0.00 |
May | 511.18 | 138.59 | 372.59 | 579.98 | 278.76 | 0.00 | 0.00 | 0.00 |
June | 496.28 | 101.04 | 395.24 | 640.67 | 196.17 | 0.00 | 0.00 | 0.00 |
July | 525.35 | 132.37 | 392.97 | 702.41 | 173.60 | 0.00 | 0.00 | 0.00 |
August | 591.89 | 212.27 | 379.63 | 801.04 | 218.45 | 0.00 | 0.00 | 0.00 |
September | 717.25 | 377.93 | 339.32 | 885.42 | 373.84 | 0.00 | 0.00 | 0.00 |
October | 748.95 | 469.86 | 279.09 | 768.31 | 547.12 | 0.00 | 0.00 | 0.00 |
November | 565.08 | 353.75 | 211.33 | 467.02 | 784.87 | 0.00 | 0.00 | 0.00 |
December | 602.58 | 456.45 | 146.13 | 513.03 | 1073.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 630.91 | 325.97 | 304.94 | 649.96 | 570.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.28 | 101.04 | 146.13 | 467.02 | 173.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.00 | 531.70 | 395.24 | 885.42 | 1137.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.93 | 195.40 | 287.53 | 151.15 | 2583.04 | 0.00 | 0.00 | 0.00 |
February | 708.13 | 348.94 | 359.18 | 367.83 | 2068.09 | 0.00 | 0.00 | 0.00 |
March | 845.36 | 314.52 | 530.84 | 538.76 | 1341.14 | 0.00 | 0.00 | 0.00 |
April | 1233.13 | 609.76 | 623.37 | 1208.14 | 945.98 | 0.00 | 0.00 | 0.00 |
May | 1236.69 | 494.03 | 742.66 | 1370.13 | 531.74 | 0.00 | 0.00 | 0.00 |
June | 1451.11 | 628.88 | 822.24 | 1822.92 | 396.61 | 0.00 | 0.00 | 0.00 |
July | 1558.06 | 740.10 | 817.95 | 2004.52 | 361.72 | 0.00 | 0.00 | 0.00 |
August | 1362.13 | 625.13 | 737.00 | 1758.52 | 426.43 | 0.00 | 0.00 | 0.00 |
September | 1102.61 | 523.35 | 579.25 | 1265.84 | 716.97 | 0.00 | 0.00 | 0.00 |
October | 768.34 | 341.60 | 426.75 | 625.28 | 1079.16 | 0.00 | 0.00 | 0.00 |
November | 459.90 | 170.07 | 289.83 | 221.26 | 1642.15 | 0.00 | 0.00 | 0.00 |
December | 353.69 | 166.73 | 186.96 | 142.64 | 2319.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 964.53 | 429.96 | 534.57 | 959.36 | 1196.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.69 | 166.73 | 186.96 | 142.64 | 361.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1558.06 | 740.10 | 822.24 | 2004.52 | 2583.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.09 | 7.73 | 11.37 | 5.98 | 102.13 | 0.00 | 0.00 | 0.00 |
February | 28.00 | 13.80 | 14.20 | 14.54 | 81.77 | 0.00 | 0.00 | 0.00 |
March | 33.42 | 12.44 | 20.99 | 21.30 | 53.03 | 0.00 | 0.00 | 0.00 |
April | 48.76 | 24.11 | 24.65 | 47.77 | 37.40 | 0.00 | 0.00 | 0.00 |
May | 48.90 | 19.53 | 29.36 | 54.17 | 21.02 | 0.00 | 0.00 | 0.00 |
June | 57.38 | 24.87 | 32.51 | 72.08 | 15.68 | 0.00 | 0.00 | 0.00 |
July | 61.60 | 29.26 | 32.34 | 79.26 | 14.30 | 0.00 | 0.00 | 0.00 |
August | 53.86 | 24.72 | 29.14 | 69.53 | 16.86 | 0.00 | 0.00 | 0.00 |
September | 43.60 | 20.69 | 22.90 | 50.05 | 28.35 | 0.00 | 0.00 | 0.00 |
October | 30.38 | 13.51 | 16.87 | 24.72 | 42.67 | 0.00 | 0.00 | 0.00 |
November | 18.18 | 6.72 | 11.46 | 8.75 | 64.93 | 0.00 | 0.00 | 0.00 |
December | 13.98 | 6.59 | 7.39 | 5.64 | 91.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.14 | 17.00 | 21.14 | 37.93 | 47.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.98 | 6.59 | 7.39 | 5.64 | 14.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.60 | 29.26 | 32.51 | 79.26 | 102.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.34 | 0.00 | 354.34 | 0.00 | 4463.92 | 0.00 | 0.00 | 0.00 |
February | 449.23 | 0.00 | 449.23 | 2.64 | 3643.28 | 0.00 | 0.00 | 0.00 |
March | 673.26 | 0.00 | 673.26 | 99.31 | 2364.67 | 0.00 | 0.00 | 0.00 |
April | 777.23 | 3.83 | 773.40 | 323.02 | 1612.80 | 0.00 | 0.00 | 0.00 |
May | 1013.53 | 38.10 | 975.43 | 763.90 | 851.64 | 0.00 | 0.00 | 0.00 |
June | 1184.58 | 107.52 | 1077.06 | 1277.04 | 593.88 | 0.00 | 0.00 | 0.00 |
July | 1110.95 | 74.31 | 1036.64 | 1266.62 | 503.44 | 0.00 | 0.00 | 0.00 |
August | 930.19 | 16.49 | 913.71 | 1065.61 | 596.53 | 0.00 | 0.00 | 0.00 |
September | 713.19 | 0.18 | 713.01 | 603.39 | 1070.23 | 0.00 | 0.00 | 0.00 |
October | 530.27 | 0.00 | 530.27 | 144.37 | 1689.57 | 0.00 | 0.00 | 0.00 |
November | 370.93 | 0.00 | 370.93 | 24.11 | 2686.52 | 0.00 | 0.00 | 0.00 |
December | 240.61 | 0.00 | 240.61 | 0.00 | 3884.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.00 | 20.11 | 676.88 | 466.95 | 1988.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 240.61 | 0.00 | 240.61 | 0.00 | 503.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1184.58 | 107.52 | 1077.06 | 1277.04 | 4463.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.18 | 208.29 | 297.89 | 129.55 | 2666.46 | 0.00 | 0.00 | 0.00 |
February | 670.94 | 295.02 | 375.91 | 272.87 | 2122.94 | 0.00 | 0.00 | 0.00 |
March | 911.60 | 361.84 | 549.76 | 549.23 | 1411.24 | 0.00 | 0.00 | 0.00 |
April | 1119.36 | 490.20 | 629.16 | 943.83 | 1010.90 | 0.00 | 0.00 | 0.00 |
May | 1405.82 | 614.28 | 791.54 | 1446.84 | 567.56 | 0.00 | 0.00 | 0.00 |
June | 1547.07 | 673.72 | 873.35 | 1862.38 | 400.45 | 0.00 | 0.00 | 0.00 |
July | 1563.69 | 721.52 | 842.17 | 1942.06 | 338.49 | 0.00 | 0.00 | 0.00 |
August | 1318.16 | 568.29 | 749.88 | 1641.52 | 396.04 | 0.00 | 0.00 | 0.00 |
September | 1175.68 | 555.57 | 620.11 | 1311.11 | 680.25 | 0.00 | 0.00 | 0.00 |
October | 749.22 | 312.94 | 436.28 | 541.75 | 1035.62 | 0.00 | 0.00 | 0.00 |
November | 442.05 | 143.59 | 298.46 | 159.34 | 1659.49 | 0.00 | 0.00 | 0.00 |
December | 342.42 | 147.04 | 195.37 | 101.55 | 2381.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 980.88 | 424.97 | 555.91 | 911.97 | 1218.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.42 | 143.59 | 195.37 | 101.55 | 338.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1563.69 | 721.52 | 873.35 | 1942.06 | 2666.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2203.57 | 1507.95 | 695.62 | 1604.80 | 3542.30 | 0.00 | 0.00 | 0.00 |
February | 2361.09 | 1595.17 | 765.92 | 1833.10 | 2872.91 | 0.00 | 0.00 | 0.00 |
March | 2054.68 | 1081.92 | 972.76 | 1713.99 | 2105.44 | 0.00 | 0.00 | 0.00 |
April | 1851.13 | 865.44 | 985.70 | 1830.18 | 1597.74 | 0.00 | 0.00 | 0.00 |
May | 1533.60 | 415.78 | 1117.83 | 1629.69 | 933.99 | 0.00 | 0.00 | 0.00 |
June | 1488.90 | 303.15 | 1185.75 | 1847.51 | 651.37 | 0.00 | 0.00 | 0.00 |
July | 1576.10 | 397.13 | 1178.97 | 2057.55 | 549.02 | 0.00 | 0.00 | 0.00 |
August | 1775.74 | 636.82 | 1138.92 | 2375.79 | 649.91 | 0.00 | 0.00 | 0.00 |
September | 2151.82 | 1133.83 | 1017.99 | 2631.55 | 1084.32 | 0.00 | 0.00 | 0.00 |
October | 2246.95 | 1409.64 | 837.31 | 2271.78 | 1576.83 | 0.00 | 0.00 | 0.00 |
November | 1695.32 | 1061.30 | 634.02 | 1374.19 | 2334.18 | 0.00 | 0.00 | 0.00 |
December | 1807.81 | 1369.39 | 438.42 | 1495.74 | 3277.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1892.81 | 977.95 | 914.86 | 1888.93 | 1759.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1488.90 | 303.15 | 438.42 | 1374.19 | 549.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2361.09 | 1595.17 | 1185.75 | 2631.55 | 3542.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.01 | 203.12 | 298.89 | 147.74 | 2745.63 | 0.00 | 0.00 | 0.00 |
February | 736.10 | 362.73 | 373.38 | 362.98 | 2216.33 | 0.00 | 0.00 | 0.00 |
March | 878.76 | 326.94 | 551.81 | 523.42 | 1469.99 | 0.00 | 0.00 | 0.00 |
April | 1281.84 | 633.85 | 648.00 | 1201.54 | 1059.33 | 0.00 | 0.00 | 0.00 |
May | 1285.55 | 513.54 | 772.01 | 1358.08 | 608.17 | 0.00 | 0.00 | 0.00 |
June | 1508.44 | 653.72 | 854.72 | 1854.84 | 439.22 | 0.00 | 0.00 | 0.00 |
July | 1619.61 | 769.34 | 850.27 | 2059.97 | 380.57 | 0.00 | 0.00 | 0.00 |
August | 1415.94 | 649.82 | 766.12 | 1817.11 | 433.57 | 0.00 | 0.00 | 0.00 |
September | 1146.17 | 544.03 | 602.14 | 1310.15 | 724.44 | 0.00 | 0.00 | 0.00 |
October | 798.70 | 355.09 | 443.61 | 641.84 | 1095.44 | 0.00 | 0.00 | 0.00 |
November | 478.07 | 176.79 | 301.28 | 225.19 | 1695.59 | 0.00 | 0.00 | 0.00 |
December | 367.66 | 173.32 | 194.34 | 142.23 | 2434.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1002.63 | 446.94 | 555.69 | 973.47 | 1270.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.66 | 173.32 | 194.34 | 142.23 | 380.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1619.61 | 769.34 | 854.72 | 2059.97 | 2745.63 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.949059E+09 | 0.00 | 0.949059E+09 | 0.00 | 0.117868E+11 |
February | 0.108678E+10 | 0.00 | 0.108678E+10 | 8950833.83 | 0.860740E+10 |
March | 0.180326E+10 | 0.00 | 0.180326E+10 | 0.282077E+09 | 0.607687E+10 |
April | 0.201459E+10 | 9925722.21 | 0.200466E+10 | 0.855185E+09 | 0.394226E+10 |
May | 0.271463E+10 | 0.102036E+09 | 0.261259E+10 | 0.210703E+10 | 0.211740E+10 |
June | 0.307043E+10 | 0.278680E+09 | 0.279175E+10 | 0.337198E+10 | 0.142535E+10 |
July | 0.297557E+10 | 0.199032E+09 | 0.277654E+10 | 0.346166E+10 | 0.124190E+10 |
August | 0.249142E+10 | 44154751.14 | 0.244727E+10 | 0.293162E+10 | 0.145410E+10 |
September | 0.184859E+10 | 458364.66 | 0.184813E+10 | 0.162798E+10 | 0.253485E+10 |
October | 0.142027E+10 | 0.00 | 0.142027E+10 | 0.436625E+09 | 0.415450E+10 |
November | 0.961448E+09 | 0.00 | 0.961448E+09 | 76624846.84 | 0.664090E+10 |
December | 0.644441E+09 | 0.00 | 0.644441E+09 | 0.00 | 0.101475E+11 |
Annual Sum or Average | 0.219805E+11 | 0.634287E+09 | 0.213462E+11 | 0.151597E+11 | 0.601298E+11 |
Minimum of Months | 0.644441E+09 | 0.00 | 0.644441E+09 | 0.00 | 0.124190E+10 |
Maximum of Months | 0.307043E+10 | 0.278680E+09 | 0.279175E+10 | 0.346166E+10 | 0.117868E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135575E+10 | 0.557892E+09 | 0.797857E+09 | 0.351004E+09 | 0.704116E+10 |
February | 0.162313E+10 | 0.713719E+09 | 0.909411E+09 | 0.672345E+09 | 0.500465E+10 |
March | 0.244163E+10 | 0.969148E+09 | 0.147248E+10 | 0.151332E+10 | 0.361292E+10 |
April | 0.290137E+10 | 0.127060E+10 | 0.163078E+10 | 0.249191E+10 | 0.246709E+10 |
May | 0.376535E+10 | 0.164528E+10 | 0.212007E+10 | 0.394399E+10 | 0.141753E+10 |
June | 0.401000E+10 | 0.174628E+10 | 0.226372E+10 | 0.486193E+10 | 0.964698E+09 |
July | 0.418819E+10 | 0.193251E+10 | 0.225567E+10 | 0.523482E+10 | 0.840813E+09 |
August | 0.353056E+10 | 0.152210E+10 | 0.200847E+10 | 0.444491E+10 | 0.976471E+09 |
September | 0.304736E+10 | 0.144003E+10 | 0.160733E+10 | 0.346306E+10 | 0.161230E+10 |
October | 0.200672E+10 | 0.838189E+09 | 0.116854E+10 | 0.154063E+10 | 0.253379E+10 |
November | 0.114579E+10 | 0.372173E+09 | 0.773620E+09 | 0.444775E+09 | 0.409579E+10 |
December | 0.917126E+09 | 0.393834E+09 | 0.523292E+09 | 0.280561E+09 | 0.622471E+10 |
Annual Sum or Average | 0.309330E+11 | 0.134018E+11 | 0.175312E+11 | 0.292433E+11 | 0.367919E+11 |
Minimum of Months | 0.917126E+09 | 0.372173E+09 | 0.523292E+09 | 0.280561E+09 | 0.840813E+09 |
Maximum of Months | 0.418819E+10 | 0.193251E+10 | 0.226372E+10 | 0.523482E+10 | 0.704116E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.590204E+10 | 0.403889E+10 | 0.186315E+10 | 0.432454E+10 | 0.930401E+10 |
February | 0.571194E+10 | 0.385902E+10 | 0.185292E+10 | 0.446596E+10 | 0.672350E+10 |
March | 0.550325E+10 | 0.289782E+10 | 0.260543E+10 | 0.463449E+10 | 0.537439E+10 |
April | 0.479813E+10 | 0.224321E+10 | 0.255492E+10 | 0.476778E+10 | 0.389524E+10 |
May | 0.410760E+10 | 0.111362E+10 | 0.299398E+10 | 0.441558E+10 | 0.232331E+10 |
June | 0.385922E+10 | 0.785752E+09 | 0.307347E+10 | 0.482195E+10 | 0.155717E+10 |
July | 0.422143E+10 | 0.106368E+10 | 0.315775E+10 | 0.555009E+10 | 0.135033E+10 |
August | 0.475614E+10 | 0.170566E+10 | 0.305049E+10 | 0.640766E+10 | 0.159005E+10 |
September | 0.557751E+10 | 0.293888E+10 | 0.263863E+10 | 0.687891E+10 | 0.257151E+10 |
October | 0.601822E+10 | 0.377558E+10 | 0.224264E+10 | 0.618623E+10 | 0.387148E+10 |
November | 0.439426E+10 | 0.275088E+10 | 0.164338E+10 | 0.363269E+10 | 0.573703E+10 |
December | 0.484203E+10 | 0.366778E+10 | 0.117426E+10 | 0.405483E+10 | 0.850742E+10 |
Annual Sum or Average | 0.596918E+11 | 0.308408E+11 | 0.288510E+11 | 0.601407E+11 | 0.528054E+11 |
Minimum of Months | 0.385922E+10 | 0.785752E+09 | 0.117426E+10 | 0.363269E+10 | 0.135033E+10 |
Maximum of Months | 0.601822E+10 | 0.403889E+10 | 0.315775E+10 | 0.687891E+10 | 0.930401E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134457E+10 | 0.544028E+09 | 0.800545E+09 | 0.395962E+09 | 0.724245E+10 |
February | 0.178078E+10 | 0.877511E+09 | 0.903269E+09 | 0.881022E+09 | 0.522518E+10 |
March | 0.235366E+10 | 0.875685E+09 | 0.147797E+10 | 0.141410E+10 | 0.376675E+10 |
April | 0.332253E+10 | 0.164293E+10 | 0.167961E+10 | 0.311887E+10 | 0.258517E+10 |
May | 0.344322E+10 | 0.137548E+10 | 0.206774E+10 | 0.365961E+10 | 0.151860E+10 |
June | 0.390988E+10 | 0.169444E+10 | 0.221544E+10 | 0.482139E+10 | 0.105827E+10 |
July | 0.433796E+10 | 0.206059E+10 | 0.227737E+10 | 0.553551E+10 | 0.944184E+09 |
August | 0.379247E+10 | 0.174049E+10 | 0.205198E+10 | 0.489368E+10 | 0.106935E+10 |
September | 0.297086E+10 | 0.141012E+10 | 0.156075E+10 | 0.342692E+10 | 0.172573E+10 |
October | 0.213923E+10 | 0.951072E+09 | 0.118816E+10 | 0.175835E+10 | 0.269262E+10 |
November | 0.123916E+10 | 0.458240E+09 | 0.780924E+09 | 0.601028E+09 | 0.419066E+10 |
December | 0.984747E+09 | 0.464222E+09 | 0.520525E+09 | 0.385856E+09 | 0.635532E+10 |
Annual Sum or Average | 0.316191E+11 | 0.140948E+11 | 0.175243E+11 | 0.308923E+11 | 0.383743E+11 |
Minimum of Months | 0.984747E+09 | 0.458240E+09 | 0.520525E+09 | 0.385856E+09 | 0.944184E+09 |
Maximum of Months | 0.433796E+10 | 0.206059E+10 | 0.227737E+10 | 0.553551E+10 | 0.724245E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316341E+09 | 0.00 | 0.316341E+09 | 0.00 | 0.389109E+10 |
February | 0.362247E+09 | 0.00 | 0.362247E+09 | 2989109.29 | 0.283754E+10 |
March | 0.601064E+09 | 0.00 | 0.601064E+09 | 0.110365E+09 | 0.198620E+10 |
April | 0.671504E+09 | 3308469.76 | 0.668196E+09 | 0.329862E+09 | 0.126282E+10 |
May | 0.904842E+09 | 34010938.33 | 0.870832E+09 | 0.781570E+09 | 0.663375E+09 |
June | 0.102344E+10 | 92890387.15 | 0.930549E+09 | 0.117880E+10 | 0.456007E+09 |
July | 0.991820E+09 | 66341860.84 | 0.925478E+09 | 0.118411E+10 | 0.413893E+09 |
August | 0.830444E+09 | 14717786.35 | 0.815726E+09 | 0.978481E+09 | 0.514657E+09 |
September | 0.616173E+09 | 152783.40 | 0.616020E+09 | 0.533154E+09 | 0.920093E+09 |
October | 0.473407E+09 | 0.00 | 0.473407E+09 | 0.132754E+09 | 0.152025E+10 |
November | 0.320471E+09 | 0.00 | 0.320471E+09 | 22381717.53 | 0.232449E+10 |
December | 0.214806E+09 | 0.00 | 0.214806E+09 | 0.00 | 0.342561E+10 |
Annual Sum or Average | 0.732656E+10 | 0.211422E+09 | 0.711514E+10 | 0.525446E+10 | 0.202160E+11 |
Minimum of Months | 0.214806E+09 | 0.00 | 0.214806E+09 | 0.00 | 0.413893E+09 |
Maximum of Months | 0.102344E+10 | 92890387.15 | 0.930549E+09 | 0.118411E+10 | 0.389109E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316356E+09 | 0.00 | 0.316356E+09 | 0.00 | 0.389134E+10 |
February | 0.362264E+09 | 0.00 | 0.362264E+09 | 2988825.51 | 0.283772E+10 |
March | 0.601092E+09 | 0.00 | 0.601092E+09 | 0.110367E+09 | 0.198633E+10 |
April | 0.671536E+09 | 3308597.51 | 0.668228E+09 | 0.329876E+09 | 0.126291E+10 |
May | 0.904885E+09 | 34012251.60 | 0.870873E+09 | 0.781602E+09 | 0.663417E+09 |
June | 0.102349E+10 | 92893973.96 | 0.930593E+09 | 0.117885E+10 | 0.456035E+09 |
July | 0.991867E+09 | 66344422.52 | 0.925522E+09 | 0.118416E+10 | 0.413916E+09 |
August | 0.830483E+09 | 14718354.66 | 0.815765E+09 | 0.978527E+09 | 0.514687E+09 |
September | 0.616202E+09 | 152789.30 | 0.616050E+09 | 0.533179E+09 | 0.920149E+09 |
October | 0.473430E+09 | 0.00 | 0.473430E+09 | 0.132757E+09 | 0.152034E+10 |
November | 0.320486E+09 | 0.00 | 0.320486E+09 | 22381748.45 | 0.232464E+10 |
December | 0.214816E+09 | 0.00 | 0.214816E+09 | 0.00 | 0.342582E+10 |
Annual Sum or Average | 0.732690E+10 | 0.211430E+09 | 0.711547E+10 | 0.525469E+10 | 0.202173E+11 |
Minimum of Months | 0.214816E+09 | 0.00 | 0.214816E+09 | 0.00 | 0.413916E+09 |
Maximum of Months | 0.102349E+10 | 92893973.96 | 0.930593E+09 | 0.118416E+10 | 0.389134E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316356E+09 | 0.00 | 0.316356E+09 | 0.00 | 0.389134E+10 |
February | 0.362264E+09 | 0.00 | 0.362264E+09 | 2988825.51 | 0.283772E+10 |
March | 0.601092E+09 | 0.00 | 0.601092E+09 | 0.110367E+09 | 0.198633E+10 |
April | 0.671536E+09 | 3308597.51 | 0.668228E+09 | 0.329876E+09 | 0.126291E+10 |
May | 0.904885E+09 | 34012251.60 | 0.870873E+09 | 0.781602E+09 | 0.663417E+09 |
June | 0.102349E+10 | 92893973.96 | 0.930593E+09 | 0.117885E+10 | 0.456035E+09 |
July | 0.991867E+09 | 66344422.52 | 0.925522E+09 | 0.118416E+10 | 0.413916E+09 |
August | 0.830483E+09 | 14718354.66 | 0.815765E+09 | 0.978527E+09 | 0.514687E+09 |
September | 0.616202E+09 | 152789.30 | 0.616050E+09 | 0.533179E+09 | 0.920149E+09 |
October | 0.473430E+09 | 0.00 | 0.473430E+09 | 0.132757E+09 | 0.152034E+10 |
November | 0.320486E+09 | 0.00 | 0.320486E+09 | 22381748.45 | 0.232464E+10 |
December | 0.214816E+09 | 0.00 | 0.214816E+09 | 0.00 | 0.342582E+10 |
Annual Sum or Average | 0.732690E+10 | 0.211430E+09 | 0.711547E+10 | 0.525469E+10 | 0.202173E+11 |
Minimum of Months | 0.214816E+09 | 0.00 | 0.214816E+09 | 0.00 | 0.413916E+09 |
Maximum of Months | 0.102349E+10 | 92893973.96 | 0.930593E+09 | 0.118416E+10 | 0.389134E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130423E+10 | 0.536694E+09 | 0.767534E+09 | 0.354041E+09 | 0.673851E+10 |
February | 0.156145E+10 | 0.686600E+09 | 0.874848E+09 | 0.669060E+09 | 0.480766E+10 |
March | 0.234884E+10 | 0.932324E+09 | 0.141651E+10 | 0.152013E+10 | 0.344755E+10 |
April | 0.279111E+10 | 0.122232E+10 | 0.156879E+10 | 0.250928E+10 | 0.231780E+10 |
May | 0.362226E+10 | 0.158276E+10 | 0.203950E+10 | 0.393889E+10 | 0.133087E+10 |
June | 0.385761E+10 | 0.167993E+10 | 0.217768E+10 | 0.476206E+10 | 0.937649E+09 |
July | 0.402903E+10 | 0.185909E+10 | 0.216994E+10 | 0.508416E+10 | 0.854013E+09 |
August | 0.339639E+10 | 0.146426E+10 | 0.193213E+10 | 0.427732E+10 | 0.103383E+10 |
September | 0.293156E+10 | 0.138532E+10 | 0.154625E+10 | 0.330088E+10 | 0.174403E+10 |
October | 0.193047E+10 | 0.806341E+09 | 0.112412E+10 | 0.142952E+10 | 0.272560E+10 |
November | 0.110225E+10 | 0.358031E+09 | 0.744219E+09 | 0.410783E+09 | 0.416285E+10 |
December | 0.882273E+09 | 0.378870E+09 | 0.503404E+09 | 0.270173E+09 | 0.609317E+10 |
Annual Sum or Average | 0.297575E+11 | 0.128925E+11 | 0.168649E+11 | 0.285263E+11 | 0.361935E+11 |
Minimum of Months | 0.882273E+09 | 0.358031E+09 | 0.503404E+09 | 0.270173E+09 | 0.854013E+09 |
Maximum of Months | 0.402903E+10 | 0.185909E+10 | 0.217768E+10 | 0.508416E+10 | 0.673851E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51568003.37 | 21220394.23 | 30347609.14 | 13998464.87 | 0.266435E+09 |
February | 61738278.45 | 27147561.86 | 34590716.59 | 26454016.04 | 0.190091E+09 |
March | 92870990.16 | 36863265.00 | 56007725.16 | 60104715.34 | 0.136313E+09 |
April | 0.110358E+09 | 48329344.80 | 62028716.91 | 99214608.41 | 91643537.28 |
May | 0.143221E+09 | 62581088.63 | 80639893.57 | 0.155740E+09 | 52621566.68 |
June | 0.152527E+09 | 66422973.79 | 86103621.67 | 0.188287E+09 | 37073799.08 |
July | 0.159304E+09 | 73506585.02 | 85797581.84 | 0.201023E+09 | 33766895.34 |
August | 0.134290E+09 | 57895566.49 | 76394816.09 | 0.169121E+09 | 40876819.93 |
September | 0.115911E+09 | 54774113.84 | 61137135.33 | 0.130514E+09 | 68957203.74 |
October | 76328856.60 | 31881982.42 | 44446874.18 | 56521792.37 | 0.107768E+09 |
November | 43581979.74 | 14156241.32 | 29425738.42 | 16241994.19 | 0.164595E+09 |
December | 34884292.51 | 14980165.84 | 19904126.67 | 10682409.39 | 0.240919E+09 |
Annual Sum or Average | 0.117658E+10 | 0.509759E+09 | 0.666825E+09 | 0.112790E+10 | 0.143106E+10 |
Minimum of Months | 34884292.51 | 14156241.32 | 19904126.67 | 10682409.39 | 33766895.34 |
Maximum of Months | 0.159304E+09 | 73506585.02 | 86103621.67 | 0.201023E+09 | 0.266435E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196740E+10 | 0.134633E+10 | 0.621067E+09 | 0.149948E+10 | 0.304752E+10 |
February | 0.190403E+10 | 0.128638E+10 | 0.617654E+09 | 0.154621E+10 | 0.224156E+10 |
March | 0.183446E+10 | 0.965966E+09 | 0.868498E+09 | 0.161219E+10 | 0.178381E+10 |
April | 0.159942E+10 | 0.747757E+09 | 0.851662E+09 | 0.166122E+10 | 0.127721E+10 |
May | 0.136923E+10 | 0.371216E+09 | 0.998019E+09 | 0.155351E+10 | 0.746672E+09 |
June | 0.128644E+10 | 0.261925E+09 | 0.102451E+10 | 0.166073E+10 | 0.508507E+09 |
July | 0.140718E+10 | 0.354570E+09 | 0.105261E+10 | 0.188146E+10 | 0.464995E+09 |
August | 0.158542E+10 | 0.568568E+09 | 0.101685E+10 | 0.214564E+10 | 0.585123E+09 |
September | 0.185922E+10 | 0.979653E+09 | 0.879566E+09 | 0.229515E+10 | 0.969047E+09 |
October | 0.200613E+10 | 0.125856E+10 | 0.747567E+09 | 0.205796E+10 | 0.146550E+10 |
November | 0.146479E+10 | 0.916986E+09 | 0.547806E+09 | 0.121059E+10 | 0.203450E+10 |
December | 0.161405E+10 | 0.122263E+10 | 0.391429E+09 | 0.137418E+10 | 0.287480E+10 |
Annual Sum or Average | 0.198978E+11 | 0.102805E+11 | 0.961724E+10 | 0.204983E+11 | 0.179992E+11 |
Minimum of Months | 0.128644E+10 | 0.261925E+09 | 0.391429E+09 | 0.121059E+10 | 0.464995E+09 |
Maximum of Months | 0.200613E+10 | 0.134633E+10 | 0.105261E+10 | 0.229515E+10 | 0.304752E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196740E+10 | 0.134633E+10 | 0.621067E+09 | 0.149948E+10 | 0.304752E+10 |
February | 0.190403E+10 | 0.128638E+10 | 0.617654E+09 | 0.154621E+10 | 0.224156E+10 |
March | 0.183446E+10 | 0.965966E+09 | 0.868498E+09 | 0.161219E+10 | 0.178381E+10 |
April | 0.159942E+10 | 0.747757E+09 | 0.851662E+09 | 0.166122E+10 | 0.127721E+10 |
May | 0.136923E+10 | 0.371216E+09 | 0.998019E+09 | 0.155351E+10 | 0.746672E+09 |
June | 0.128644E+10 | 0.261925E+09 | 0.102451E+10 | 0.166073E+10 | 0.508507E+09 |
July | 0.140718E+10 | 0.354570E+09 | 0.105261E+10 | 0.188146E+10 | 0.464995E+09 |
August | 0.158542E+10 | 0.568568E+09 | 0.101685E+10 | 0.214564E+10 | 0.585123E+09 |
September | 0.185922E+10 | 0.979653E+09 | 0.879566E+09 | 0.229515E+10 | 0.969047E+09 |
October | 0.200613E+10 | 0.125856E+10 | 0.747567E+09 | 0.205796E+10 | 0.146550E+10 |
November | 0.146479E+10 | 0.916986E+09 | 0.547806E+09 | 0.121059E+10 | 0.203450E+10 |
December | 0.161405E+10 | 0.122263E+10 | 0.391429E+09 | 0.137418E+10 | 0.287480E+10 |
Annual Sum or Average | 0.198978E+11 | 0.102805E+11 | 0.961724E+10 | 0.204983E+11 | 0.179992E+11 |
Minimum of Months | 0.128644E+10 | 0.261925E+09 | 0.391429E+09 | 0.121059E+10 | 0.464995E+09 |
Maximum of Months | 0.200613E+10 | 0.134633E+10 | 0.105261E+10 | 0.229515E+10 | 0.304752E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196728E+10 | 0.134625E+10 | 0.621028E+09 | 0.149939E+10 | 0.304732E+10 |
February | 0.190391E+10 | 0.128630E+10 | 0.617615E+09 | 0.154611E+10 | 0.224141E+10 |
March | 0.183435E+10 | 0.965905E+09 | 0.868443E+09 | 0.161208E+10 | 0.178370E+10 |
April | 0.159932E+10 | 0.747710E+09 | 0.851608E+09 | 0.166112E+10 | 0.127713E+10 |
May | 0.136915E+10 | 0.371193E+09 | 0.997956E+09 | 0.155341E+10 | 0.746624E+09 |
June | 0.128636E+10 | 0.261908E+09 | 0.102445E+10 | 0.166062E+10 | 0.508475E+09 |
July | 0.140709E+10 | 0.354548E+09 | 0.105254E+10 | 0.188134E+10 | 0.464965E+09 |
August | 0.158532E+10 | 0.568532E+09 | 0.101679E+10 | 0.214551E+10 | 0.585086E+09 |
September | 0.185910E+10 | 0.979591E+09 | 0.879510E+09 | 0.229500E+10 | 0.968986E+09 |
October | 0.200600E+10 | 0.125848E+10 | 0.747519E+09 | 0.205783E+10 | 0.146540E+10 |
November | 0.146470E+10 | 0.916928E+09 | 0.547771E+09 | 0.121051E+10 | 0.203438E+10 |
December | 0.161395E+10 | 0.122255E+10 | 0.391404E+09 | 0.137409E+10 | 0.287461E+10 |
Annual Sum or Average | 0.198965E+11 | 0.102799E+11 | 0.961664E+10 | 0.204970E+11 | 0.179981E+11 |
Minimum of Months | 0.128636E+10 | 0.261908E+09 | 0.391404E+09 | 0.121051E+10 | 0.464965E+09 |
Maximum of Months | 0.200600E+10 | 0.134625E+10 | 0.105254E+10 | 0.229500E+10 | 0.304732E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129347E+10 | 0.523355E+09 | 0.770118E+09 | 0.404837E+09 | 0.691841E+10 |
February | 0.171310E+10 | 0.844166E+09 | 0.868938E+09 | 0.889854E+09 | 0.500312E+10 |
March | 0.226421E+10 | 0.842410E+09 | 0.142180E+10 | 0.144302E+10 | 0.359211E+10 |
April | 0.319627E+10 | 0.158050E+10 | 0.161577E+10 | 0.313150E+10 | 0.245198E+10 |
May | 0.331236E+10 | 0.132321E+10 | 0.198915E+10 | 0.366975E+10 | 0.142422E+10 |
June | 0.376129E+10 | 0.163005E+10 | 0.213124E+10 | 0.472501E+10 | 0.102801E+10 |
July | 0.417310E+10 | 0.198229E+10 | 0.219081E+10 | 0.536890E+10 | 0.968820E+09 |
August | 0.364834E+10 | 0.167435E+10 | 0.197399E+10 | 0.471003E+10 | 0.114215E+10 |
September | 0.285796E+10 | 0.135653E+10 | 0.150143E+10 | 0.328105E+10 | 0.185840E+10 |
October | 0.205793E+10 | 0.914932E+09 | 0.114300E+10 | 0.167476E+10 | 0.289041E+10 |
November | 0.119207E+10 | 0.440827E+09 | 0.751244E+09 | 0.573515E+09 | 0.425646E+10 |
December | 0.947323E+09 | 0.446582E+09 | 0.500741E+09 | 0.382048E+09 | 0.621219E+10 |
Annual Sum or Average | 0.304174E+11 | 0.135592E+11 | 0.168582E+11 | 0.302543E+11 | 0.377463E+11 |
Minimum of Months | 0.947323E+09 | 0.440827E+09 | 0.500741E+09 | 0.382048E+09 | 0.968820E+09 |
Maximum of Months | 0.417310E+10 | 0.198229E+10 | 0.219081E+10 | 0.536890E+10 | 0.691841E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51142790.03 | 20693003.29 | 30449786.74 | 16006889.43 | 0.273548E+09 |
February | 67734582.16 | 33377571.38 | 34357010.79 | 35184044.12 | 0.197819E+09 |
March | 89524784.28 | 33308131.93 | 56216652.35 | 57055762.74 | 0.142029E+09 |
April | 0.126377E+09 | 62491444.40 | 63885996.84 | 0.123817E+09 | 96949276.99 |
May | 0.130968E+09 | 52318551.13 | 78649277.04 | 0.145099E+09 | 56312345.90 |
June | 0.148718E+09 | 64450714.96 | 84267187.81 | 0.186823E+09 | 40646667.69 |
July | 0.165000E+09 | 78377823.10 | 86622623.83 | 0.212281E+09 | 38306281.47 |
August | 0.144252E+09 | 66202221.74 | 78049691.88 | 0.186230E+09 | 45159388.40 |
September | 0.113001E+09 | 53636160.26 | 59364993.75 | 0.129730E+09 | 73479266.07 |
October | 81368649.91 | 36175595.75 | 45193054.15 | 66218329.72 | 0.114284E+09 |
November | 47133392.50 | 17429899.21 | 29703493.29 | 22676253.80 | 0.168297E+09 |
December | 37456291.35 | 17657440.02 | 19798851.34 | 15105819.07 | 0.245624E+09 |
Annual Sum or Average | 0.120268E+10 | 0.536119E+09 | 0.666559E+09 | 0.119623E+10 | 0.149245E+10 |
Minimum of Months | 37456291.35 | 17429899.21 | 19798851.34 | 15105819.07 | 38306281.47 |
Maximum of Months | 0.165000E+09 | 78377823.10 | 86622623.83 | 0.212281E+09 | 0.273548E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.949059E+09 | 0.00 | 0.949059E+09 | 0.00 | 0.119562E+11 |
February | 0.108678E+10 | 0.00 | 0.108678E+10 | 6393798.18 | 0.881381E+10 |
March | 0.180326E+10 | 0.00 | 0.180326E+10 | 0.265993E+09 | 0.633354E+10 |
April | 0.201459E+10 | 9925722.21 | 0.200466E+10 | 0.837261E+09 | 0.418037E+10 |
May | 0.271463E+10 | 0.102036E+09 | 0.261259E+10 | 0.204602E+10 | 0.228104E+10 |
June | 0.307043E+10 | 0.278680E+09 | 0.279175E+10 | 0.331008E+10 | 0.153935E+10 |
July | 0.297557E+10 | 0.199032E+09 | 0.277654E+10 | 0.339252E+10 | 0.134842E+10 |
August | 0.249142E+10 | 44154751.14 | 0.244727E+10 | 0.285413E+10 | 0.159775E+10 |
September | 0.184859E+10 | 458364.66 | 0.184813E+10 | 0.156399E+10 | 0.277403E+10 |
October | 0.142027E+10 | 0.00 | 0.142027E+10 | 0.386689E+09 | 0.452536E+10 |
November | 0.961448E+09 | 0.00 | 0.961448E+09 | 62504237.08 | 0.696346E+10 |
December | 0.644441E+09 | 0.00 | 0.644441E+09 | 0.00 | 0.104044E+11 |
Annual Sum or Average | 0.219805E+11 | 0.634287E+09 | 0.213462E+11 | 0.147256E+11 | 0.627177E+11 |
Minimum of Months | 0.644441E+09 | 0.00 | 0.644441E+09 | 0.00 | 0.134842E+10 |
Maximum of Months | 0.307043E+10 | 0.278680E+09 | 0.279175E+10 | 0.339252E+10 | 0.119562E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135575E+10 | 0.557892E+09 | 0.797857E+09 | 0.346977E+09 | 0.714183E+10 |
February | 0.162313E+10 | 0.713719E+09 | 0.909411E+09 | 0.660135E+09 | 0.513582E+10 |
March | 0.244163E+10 | 0.969148E+09 | 0.147248E+10 | 0.147105E+10 | 0.377986E+10 |
April | 0.290137E+10 | 0.127060E+10 | 0.163078E+10 | 0.244641E+10 | 0.262024E+10 |
May | 0.376535E+10 | 0.164528E+10 | 0.212007E+10 | 0.387522E+10 | 0.152015E+10 |
June | 0.401000E+10 | 0.174628E+10 | 0.226372E+10 | 0.482728E+10 | 0.103798E+10 |
July | 0.418819E+10 | 0.193251E+10 | 0.225567E+10 | 0.520162E+10 | 0.906620E+09 |
August | 0.353056E+10 | 0.152210E+10 | 0.200847E+10 | 0.439665E+10 | 0.106076E+10 |
September | 0.304736E+10 | 0.144003E+10 | 0.160733E+10 | 0.339840E+10 | 0.176320E+10 |
October | 0.200672E+10 | 0.838189E+09 | 0.116854E+10 | 0.145101E+10 | 0.277380E+10 |
November | 0.114579E+10 | 0.372173E+09 | 0.773620E+09 | 0.413018E+09 | 0.430139E+10 |
December | 0.917126E+09 | 0.393834E+09 | 0.523292E+09 | 0.271998E+09 | 0.637887E+10 |
Annual Sum or Average | 0.309330E+11 | 0.134018E+11 | 0.175312E+11 | 0.287598E+11 | 0.384205E+11 |
Minimum of Months | 0.917126E+09 | 0.372173E+09 | 0.523292E+09 | 0.271998E+09 | 0.906620E+09 |
Maximum of Months | 0.418819E+10 | 0.193251E+10 | 0.226372E+10 | 0.520162E+10 | 0.714183E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.590204E+10 | 0.403889E+10 | 0.186315E+10 | 0.429831E+10 | 0.948770E+10 |
February | 0.571194E+10 | 0.385902E+10 | 0.185292E+10 | 0.443463E+10 | 0.695015E+10 |
March | 0.550325E+10 | 0.289782E+10 | 0.260543E+10 | 0.459076E+10 | 0.563921E+10 |
April | 0.479813E+10 | 0.224321E+10 | 0.255492E+10 | 0.474382E+10 | 0.414134E+10 |
May | 0.410760E+10 | 0.111362E+10 | 0.299398E+10 | 0.436497E+10 | 0.250160E+10 |
June | 0.385922E+10 | 0.785752E+09 | 0.307347E+10 | 0.478875E+10 | 0.168834E+10 |
July | 0.422143E+10 | 0.106368E+10 | 0.315775E+10 | 0.551094E+10 | 0.147050E+10 |
August | 0.475614E+10 | 0.170566E+10 | 0.305049E+10 | 0.636332E+10 | 0.174071E+10 |
September | 0.557751E+10 | 0.293888E+10 | 0.263863E+10 | 0.682097E+10 | 0.281056E+10 |
October | 0.601822E+10 | 0.377558E+10 | 0.224264E+10 | 0.608473E+10 | 0.422338E+10 |
November | 0.439426E+10 | 0.275088E+10 | 0.164338E+10 | 0.356190E+10 | 0.605020E+10 |
December | 0.484203E+10 | 0.366778E+10 | 0.117426E+10 | 0.400620E+10 | 0.877944E+10 |
Annual Sum or Average | 0.596918E+11 | 0.308408E+11 | 0.288510E+11 | 0.595693E+11 | 0.554831E+11 |
Minimum of Months | 0.385922E+10 | 0.785752E+09 | 0.117426E+10 | 0.356190E+10 | 0.147050E+10 |
Maximum of Months | 0.601822E+10 | 0.403889E+10 | 0.315775E+10 | 0.682097E+10 | 0.948770E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134457E+10 | 0.544028E+09 | 0.800545E+09 | 0.395711E+09 | 0.735391E+10 |
February | 0.178078E+10 | 0.877511E+09 | 0.903269E+09 | 0.878121E+09 | 0.536176E+10 |
March | 0.235366E+10 | 0.875685E+09 | 0.147797E+10 | 0.140192E+10 | 0.393721E+10 |
April | 0.332253E+10 | 0.164293E+10 | 0.167961E+10 | 0.311439E+10 | 0.274579E+10 |
May | 0.344322E+10 | 0.137548E+10 | 0.206774E+10 | 0.363749E+10 | 0.162892E+10 |
June | 0.390988E+10 | 0.169444E+10 | 0.221544E+10 | 0.480774E+10 | 0.113845E+10 |
July | 0.433796E+10 | 0.206059E+10 | 0.227737E+10 | 0.551741E+10 | 0.101932E+10 |
August | 0.379247E+10 | 0.174049E+10 | 0.205198E+10 | 0.486695E+10 | 0.116128E+10 |
September | 0.297086E+10 | 0.141012E+10 | 0.156075E+10 | 0.339590E+10 | 0.187774E+10 |
October | 0.213923E+10 | 0.951072E+09 | 0.118816E+10 | 0.171909E+10 | 0.293403E+10 |
November | 0.123916E+10 | 0.458240E+09 | 0.780924E+09 | 0.583690E+09 | 0.439497E+10 |
December | 0.984747E+09 | 0.464222E+09 | 0.520525E+09 | 0.380952E+09 | 0.651983E+10 |
Annual Sum or Average | 0.316191E+11 | 0.140948E+11 | 0.175243E+11 | 0.306994E+11 | 0.400732E+11 |
Minimum of Months | 0.984747E+09 | 0.458240E+09 | 0.520525E+09 | 0.380952E+09 | 0.101932E+10 |
Maximum of Months | 0.433796E+10 | 0.206059E+10 | 0.227737E+10 | 0.551741E+10 | 0.735391E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4400.68 | 354.34 | 0.00 | 354.34 | 0.00 | 0.00 |
February | 3.70 | 3557.95 | 449.23 | 0.00 | 449.23 | 0.00 | 0.00 |
March | 105.32 | 2268.84 | 673.26 | 0.00 | 673.26 | 0.00 | 0.00 |
April | 329.93 | 1520.93 | 777.23 | 3.83 | 773.40 | 0.00 | 0.00 |
May | 786.67 | 790.55 | 1013.53 | 38.10 | 975.43 | 0.00 | 0.00 |
June | 1300.92 | 549.90 | 1184.58 | 107.52 | 1077.06 | 0.00 | 0.00 |
July | 1292.44 | 463.67 | 1110.95 | 74.31 | 1036.64 | 0.00 | 0.00 |
August | 1094.54 | 542.90 | 930.19 | 16.49 | 913.71 | 0.00 | 0.00 |
September | 628.08 | 977.95 | 713.19 | 0.18 | 713.01 | 0.00 | 0.00 |
October | 163.02 | 1551.11 | 530.27 | 0.00 | 530.27 | 0.00 | 0.00 |
November | 29.56 | 2562.07 | 370.93 | 0.00 | 370.93 | 0.00 | 0.00 |
December | 0.00 | 3788.64 | 240.61 | 0.00 | 240.61 | 0.00 | 0.00 |
Annual Sum or Average | 480.71 | 1906.70 | 697.00 | 20.11 | 676.88 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 463.67 | 240.61 | 0.00 | 240.61 | 0.00 | 0.00 |
Maximum of Months | 1300.92 | 4400.68 | 1184.58 | 107.52 | 1077.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 131.05 | 2628.87 | 506.18 | 208.29 | 297.89 | 0.00 | 0.00 |
February | 277.92 | 2068.72 | 670.94 | 295.02 | 375.91 | 0.00 | 0.00 |
March | 565.01 | 1348.91 | 911.60 | 361.84 | 549.76 | 0.00 | 0.00 |
April | 961.38 | 951.81 | 1119.36 | 490.20 | 629.16 | 0.00 | 0.00 |
May | 1472.52 | 529.24 | 1405.82 | 614.28 | 791.54 | 0.00 | 0.00 |
June | 1875.74 | 372.18 | 1547.07 | 673.72 | 873.35 | 0.00 | 0.00 |
July | 1954.46 | 313.92 | 1563.69 | 721.52 | 842.17 | 0.00 | 0.00 |
August | 1659.54 | 364.57 | 1318.16 | 568.29 | 749.88 | 0.00 | 0.00 |
September | 1336.06 | 622.03 | 1175.68 | 555.57 | 620.11 | 0.00 | 0.00 |
October | 575.21 | 946.01 | 749.22 | 312.94 | 436.28 | 0.00 | 0.00 |
November | 171.60 | 1580.16 | 442.05 | 143.59 | 298.46 | 0.00 | 0.00 |
December | 104.75 | 2324.04 | 342.42 | 147.04 | 195.37 | 0.00 | 0.00 |
Annual Sum or Average | 927.30 | 1166.66 | 980.88 | 424.97 | 555.91 | 0.00 | 0.00 |
Minimum of Months | 104.75 | 313.92 | 342.42 | 143.59 | 195.37 | 0.00 | 0.00 |
Maximum of Months | 1954.46 | 2628.87 | 1563.69 | 721.52 | 873.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1614.60 | 3473.72 | 2203.57 | 1507.95 | 695.62 | 0.00 | 0.00 |
February | 1846.05 | 2779.23 | 2361.09 | 1595.17 | 765.92 | 0.00 | 0.00 |
March | 1730.32 | 2006.57 | 2054.68 | 1081.92 | 972.76 | 0.00 | 0.00 |
April | 1839.42 | 1502.79 | 1851.13 | 865.44 | 985.70 | 0.00 | 0.00 |
May | 1648.59 | 867.42 | 1533.60 | 415.78 | 1117.83 | 0.00 | 0.00 |
June | 1860.32 | 600.76 | 1488.90 | 303.15 | 1185.75 | 0.00 | 0.00 |
July | 2072.17 | 504.15 | 1576.10 | 397.13 | 1178.97 | 0.00 | 0.00 |
August | 2392.34 | 593.66 | 1775.74 | 636.82 | 1138.92 | 0.00 | 0.00 |
September | 2653.90 | 992.10 | 2151.82 | 1133.83 | 1017.99 | 0.00 | 0.00 |
October | 2309.67 | 1445.45 | 2246.95 | 1409.64 | 837.31 | 0.00 | 0.00 |
November | 1401.50 | 2213.36 | 1695.32 | 1061.30 | 634.02 | 0.00 | 0.00 |
December | 1513.90 | 3176.31 | 1807.81 | 1369.39 | 438.42 | 0.00 | 0.00 |
Annual Sum or Average | 1907.05 | 1674.45 | 1892.81 | 977.95 | 914.86 | 0.00 | 0.00 |
Minimum of Months | 1401.50 | 504.15 | 1488.90 | 303.15 | 438.42 | 0.00 | 0.00 |
Maximum of Months | 2653.90 | 3473.72 | 2361.09 | 1595.17 | 1185.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 147.84 | 2704.02 | 502.01 | 203.12 | 298.89 | 0.00 | 0.00 |
February | 364.18 | 2159.88 | 736.10 | 362.73 | 373.38 | 0.00 | 0.00 |
March | 527.96 | 1406.34 | 878.76 | 326.94 | 551.81 | 0.00 | 0.00 |
April | 1203.27 | 997.36 | 1281.84 | 633.85 | 648.00 | 0.00 | 0.00 |
May | 1366.34 | 566.98 | 1285.55 | 513.54 | 772.01 | 0.00 | 0.00 |
June | 1860.10 | 408.28 | 1508.44 | 653.72 | 854.72 | 0.00 | 0.00 |
July | 2066.72 | 352.52 | 1619.61 | 769.34 | 850.27 | 0.00 | 0.00 |
August | 1827.09 | 399.25 | 1415.94 | 649.82 | 766.12 | 0.00 | 0.00 |
September | 1322.11 | 665.79 | 1146.17 | 544.03 | 602.14 | 0.00 | 0.00 |
October | 656.49 | 1005.31 | 798.70 | 355.09 | 443.61 | 0.00 | 0.00 |
November | 231.88 | 1616.77 | 478.07 | 176.79 | 301.28 | 0.00 | 0.00 |
December | 144.06 | 2372.81 | 367.66 | 173.32 | 194.34 | 0.00 | 0.00 |
Annual Sum or Average | 979.59 | 1216.84 | 1002.63 | 446.94 | 555.69 | 0.00 | 0.00 |
Minimum of Months | 144.06 | 352.52 | 367.66 | 173.32 | 194.34 | 0.00 | 0.00 |
Maximum of Months | 2066.72 | 2704.02 | 1619.61 | 769.34 | 854.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4358.48 | 354.34 | 0.00 | 354.34 | 0.00 | 0.00 |
February | 3.71 | 3518.92 | 449.23 | 0.00 | 449.23 | 0.00 | 0.00 |
March | 123.62 | 2224.79 | 673.26 | 0.00 | 673.26 | 0.00 | 0.00 |
April | 381.80 | 1461.67 | 777.23 | 3.83 | 773.40 | 0.00 | 0.00 |
May | 875.44 | 743.06 | 1013.52 | 38.10 | 975.42 | 0.00 | 0.00 |
June | 1364.39 | 527.81 | 1184.57 | 107.51 | 1077.06 | 0.00 | 0.00 |
July | 1326.33 | 463.61 | 1110.94 | 74.31 | 1036.63 | 0.00 | 0.00 |
August | 1096.00 | 576.48 | 930.19 | 16.49 | 913.70 | 0.00 | 0.00 |
September | 617.10 | 1064.97 | 713.19 | 0.18 | 713.01 | 0.00 | 0.00 |
October | 148.70 | 1702.86 | 530.27 | 0.00 | 530.27 | 0.00 | 0.00 |
November | 25.90 | 2690.49 | 370.93 | 0.00 | 370.93 | 0.00 | 0.00 |
December | 0.00 | 3837.09 | 240.61 | 0.00 | 240.61 | 0.00 | 0.00 |
Annual Sum or Average | 499.87 | 1923.22 | 696.99 | 20.11 | 676.88 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 463.61 | 240.61 | 0.00 | 240.61 | 0.00 | 0.00 |
Maximum of Months | 1364.39 | 4358.48 | 1184.57 | 107.51 | 1077.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 137.41 | 2615.35 | 506.20 | 208.30 | 297.89 | 0.00 | 0.00 |
February | 287.50 | 2065.87 | 670.96 | 295.03 | 375.93 | 0.00 | 0.00 |
March | 589.99 | 1338.06 | 911.63 | 361.85 | 549.78 | 0.00 | 0.00 |
April | 1006.36 | 929.57 | 1119.39 | 490.22 | 629.18 | 0.00 | 0.00 |
May | 1528.76 | 516.54 | 1405.87 | 614.30 | 791.57 | 0.00 | 0.00 |
June | 1909.86 | 376.05 | 1547.12 | 673.75 | 873.37 | 0.00 | 0.00 |
July | 1973.26 | 331.46 | 1563.74 | 721.55 | 842.20 | 0.00 | 0.00 |
August | 1660.11 | 401.25 | 1318.21 | 568.31 | 749.90 | 0.00 | 0.00 |
September | 1323.84 | 699.45 | 1175.72 | 555.59 | 620.13 | 0.00 | 0.00 |
October | 554.82 | 1057.86 | 749.25 | 312.96 | 436.29 | 0.00 | 0.00 |
November | 164.75 | 1669.54 | 442.06 | 143.59 | 298.47 | 0.00 | 0.00 |
December | 104.86 | 2364.88 | 342.43 | 147.05 | 195.38 | 0.00 | 0.00 |
Annual Sum or Average | 940.33 | 1193.07 | 980.91 | 424.98 | 555.93 | 0.00 | 0.00 |
Minimum of Months | 104.86 | 331.46 | 342.43 | 143.59 | 195.38 | 0.00 | 0.00 |
Maximum of Months | 1973.26 | 2615.35 | 1563.74 | 721.55 | 873.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1679.49 | 3413.36 | 2203.58 | 1507.96 | 695.62 | 0.00 | 0.00 |
February | 1917.38 | 2779.65 | 2361.10 | 1595.18 | 765.92 | 0.00 | 0.00 |
March | 1805.73 | 1997.96 | 2054.69 | 1081.93 | 972.76 | 0.00 | 0.00 |
April | 1922.67 | 1478.22 | 1851.14 | 865.44 | 985.70 | 0.00 | 0.00 |
May | 1740.01 | 836.31 | 1533.61 | 415.78 | 1117.83 | 0.00 | 0.00 |
June | 1922.10 | 588.54 | 1488.90 | 303.15 | 1185.76 | 0.00 | 0.00 |
July | 2107.32 | 520.82 | 1576.11 | 397.14 | 1178.97 | 0.00 | 0.00 |
August | 2403.22 | 655.37 | 1775.75 | 636.82 | 1138.92 | 0.00 | 0.00 |
September | 2656.36 | 1121.56 | 2151.83 | 1133.83 | 1017.99 | 0.00 | 0.00 |
October | 2305.02 | 1641.43 | 2246.96 | 1409.65 | 837.31 | 0.00 | 0.00 |
November | 1401.11 | 2354.70 | 1695.33 | 1061.30 | 634.02 | 0.00 | 0.00 |
December | 1539.14 | 3219.91 | 1807.82 | 1369.40 | 438.42 | 0.00 | 0.00 |
Annual Sum or Average | 1949.95 | 1712.22 | 1892.82 | 977.96 | 914.86 | 0.00 | 0.00 |
Minimum of Months | 1401.11 | 520.82 | 1488.90 | 303.15 | 438.42 | 0.00 | 0.00 |
Maximum of Months | 2656.36 | 3413.36 | 2361.10 | 1595.18 | 1185.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 157.13 | 2685.17 | 502.02 | 203.12 | 298.90 | 0.00 | 0.00 |
February | 382.37 | 2149.86 | 736.13 | 362.74 | 373.39 | 0.00 | 0.00 |
March | 560.06 | 1394.17 | 878.78 | 326.96 | 551.83 | 0.00 | 0.00 |
April | 1255.91 | 983.39 | 1281.88 | 633.87 | 648.01 | 0.00 | 0.00 |
May | 1424.30 | 552.77 | 1285.59 | 513.56 | 772.03 | 0.00 | 0.00 |
June | 1895.00 | 412.29 | 1508.49 | 653.74 | 854.75 | 0.00 | 0.00 |
July | 2083.77 | 376.02 | 1619.66 | 769.36 | 850.30 | 0.00 | 0.00 |
August | 1828.05 | 443.29 | 1415.99 | 649.85 | 766.14 | 0.00 | 0.00 |
September | 1315.89 | 745.32 | 1146.20 | 544.05 | 602.16 | 0.00 | 0.00 |
October | 650.01 | 1121.83 | 798.72 | 355.10 | 443.62 | 0.00 | 0.00 |
November | 230.01 | 1707.08 | 478.09 | 176.80 | 301.29 | 0.00 | 0.00 |
December | 148.28 | 2411.07 | 367.67 | 173.33 | 194.35 | 0.00 | 0.00 |
Annual Sum or Average | 997.29 | 1244.25 | 1002.67 | 446.96 | 555.71 | 0.00 | 0.00 |
Minimum of Months | 148.28 | 376.02 | 367.67 | 173.33 | 194.35 | 0.00 | 0.00 |
Maximum of Months | 2083.77 | 2685.17 | 1619.66 | 769.36 | 854.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4463.92 | 354.34 | 0.00 | 354.34 | 0.00 | 0.00 |
February | 2.64 | 3643.28 | 449.23 | 0.00 | 449.23 | 0.00 | 0.00 |
March | 99.31 | 2364.67 | 673.26 | 0.00 | 673.26 | 0.00 | 0.00 |
April | 323.02 | 1612.80 | 777.23 | 3.83 | 773.40 | 0.00 | 0.00 |
May | 763.90 | 851.64 | 1013.53 | 38.10 | 975.43 | 0.00 | 0.00 |
June | 1277.04 | 593.88 | 1184.58 | 107.52 | 1077.06 | 0.00 | 0.00 |
July | 1266.62 | 503.44 | 1110.95 | 74.31 | 1036.64 | 0.00 | 0.00 |
August | 1065.61 | 596.53 | 930.19 | 16.49 | 913.71 | 0.00 | 0.00 |
September | 603.39 | 1070.23 | 713.19 | 0.18 | 713.01 | 0.00 | 0.00 |
October | 144.37 | 1689.57 | 530.27 | 0.00 | 530.27 | 0.00 | 0.00 |
November | 24.11 | 2686.52 | 370.93 | 0.00 | 370.93 | 0.00 | 0.00 |
December | 0.00 | 3884.55 | 240.61 | 0.00 | 240.61 | 0.00 | 0.00 |
Annual Sum or Average | 466.95 | 1988.76 | 697.00 | 20.11 | 676.88 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 503.44 | 240.61 | 0.00 | 240.61 | 0.00 | 0.00 |
Maximum of Months | 1277.04 | 4463.92 | 1184.58 | 107.52 | 1077.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 129.55 | 2666.46 | 506.18 | 208.29 | 297.89 | 0.00 | 0.00 |
February | 272.87 | 2122.94 | 670.94 | 295.02 | 375.91 | 0.00 | 0.00 |
March | 549.23 | 1411.24 | 911.60 | 361.84 | 549.76 | 0.00 | 0.00 |
April | 943.83 | 1010.90 | 1119.36 | 490.20 | 629.16 | 0.00 | 0.00 |
May | 1446.84 | 567.56 | 1405.82 | 614.28 | 791.54 | 0.00 | 0.00 |
June | 1862.38 | 400.45 | 1547.07 | 673.72 | 873.35 | 0.00 | 0.00 |
July | 1942.06 | 338.49 | 1563.69 | 721.52 | 842.17 | 0.00 | 0.00 |
August | 1641.52 | 396.04 | 1318.16 | 568.29 | 749.88 | 0.00 | 0.00 |
September | 1311.11 | 680.25 | 1175.68 | 555.57 | 620.11 | 0.00 | 0.00 |
October | 541.75 | 1035.62 | 749.22 | 312.94 | 436.28 | 0.00 | 0.00 |
November | 159.34 | 1659.49 | 442.05 | 143.59 | 298.46 | 0.00 | 0.00 |
December | 101.55 | 2381.60 | 342.42 | 147.04 | 195.37 | 0.00 | 0.00 |
Annual Sum or Average | 911.97 | 1218.31 | 980.88 | 424.97 | 555.91 | 0.00 | 0.00 |
Minimum of Months | 101.55 | 338.49 | 342.42 | 143.59 | 195.37 | 0.00 | 0.00 |
Maximum of Months | 1942.06 | 2666.46 | 1563.69 | 721.52 | 873.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1604.80 | 3542.30 | 2203.57 | 1507.95 | 695.62 | 0.00 | 0.00 |
February | 1833.10 | 2872.91 | 2361.09 | 1595.17 | 765.92 | 0.00 | 0.00 |
March | 1713.99 | 2105.44 | 2054.68 | 1081.92 | 972.76 | 0.00 | 0.00 |
April | 1830.18 | 1597.74 | 1851.13 | 865.44 | 985.70 | 0.00 | 0.00 |
May | 1629.69 | 933.99 | 1533.60 | 415.78 | 1117.83 | 0.00 | 0.00 |
June | 1847.51 | 651.37 | 1488.90 | 303.15 | 1185.75 | 0.00 | 0.00 |
July | 2057.55 | 549.02 | 1576.10 | 397.13 | 1178.97 | 0.00 | 0.00 |
August | 2375.79 | 649.91 | 1775.74 | 636.82 | 1138.92 | 0.00 | 0.00 |
September | 2631.55 | 1084.32 | 2151.82 | 1133.83 | 1017.99 | 0.00 | 0.00 |
October | 2271.78 | 1576.83 | 2246.95 | 1409.64 | 837.31 | 0.00 | 0.00 |
November | 1374.19 | 2334.18 | 1695.32 | 1061.30 | 634.02 | 0.00 | 0.00 |
December | 1495.74 | 3277.87 | 1807.81 | 1369.39 | 438.42 | 0.00 | 0.00 |
Annual Sum or Average | 1888.93 | 1759.36 | 1892.81 | 977.95 | 914.86 | 0.00 | 0.00 |
Minimum of Months | 1374.19 | 549.02 | 1488.90 | 303.15 | 438.42 | 0.00 | 0.00 |
Maximum of Months | 2631.55 | 3542.30 | 2361.09 | 1595.17 | 1185.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 147.74 | 2745.63 | 502.01 | 203.12 | 298.89 | 0.00 | 0.00 |
February | 362.98 | 2216.33 | 736.10 | 362.73 | 373.38 | 0.00 | 0.00 |
March | 523.42 | 1469.99 | 878.76 | 326.94 | 551.81 | 0.00 | 0.00 |
April | 1201.54 | 1059.33 | 1281.84 | 633.85 | 648.00 | 0.00 | 0.00 |
May | 1358.08 | 608.17 | 1285.55 | 513.54 | 772.01 | 0.00 | 0.00 |
June | 1854.84 | 439.22 | 1508.44 | 653.72 | 854.72 | 0.00 | 0.00 |
July | 2059.97 | 380.57 | 1619.61 | 769.34 | 850.27 | 0.00 | 0.00 |
August | 1817.11 | 433.57 | 1415.94 | 649.82 | 766.12 | 0.00 | 0.00 |
September | 1310.15 | 724.44 | 1146.17 | 544.03 | 602.14 | 0.00 | 0.00 |
October | 641.84 | 1095.44 | 798.70 | 355.09 | 443.61 | 0.00 | 0.00 |
November | 225.19 | 1695.59 | 478.07 | 176.79 | 301.28 | 0.00 | 0.00 |
December | 142.23 | 2434.23 | 367.66 | 173.32 | 194.34 | 0.00 | 0.00 |
Annual Sum or Average | 973.47 | 1270.71 | 1002.63 | 446.94 | 555.69 | 0.00 | 0.00 |
Minimum of Months | 142.23 | 380.57 | 367.66 | 173.32 | 194.34 | 0.00 | 0.00 |
Maximum of Months | 2059.97 | 2745.63 | 1619.61 | 769.34 | 854.72 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.117868E+11 | 0.949059E+09 | 0.00 | 0.949059E+09 | 0.00 | 0.00 |
February | 8950833.83 | 0.860740E+10 | 0.108678E+10 | 0.00 | 0.108678E+10 | 0.00 | 0.00 |
March | 0.282077E+09 | 0.607687E+10 | 0.180326E+10 | 0.00 | 0.180326E+10 | 0.00 | 0.00 |
April | 0.855185E+09 | 0.394226E+10 | 0.201459E+10 | 9925722.21 | 0.200466E+10 | 0.00 | 0.00 |
May | 0.210703E+10 | 0.211740E+10 | 0.271463E+10 | 0.102036E+09 | 0.261259E+10 | 0.00 | 0.00 |
June | 0.337198E+10 | 0.142535E+10 | 0.307043E+10 | 0.278680E+09 | 0.279175E+10 | 0.00 | 0.00 |
July | 0.346166E+10 | 0.124190E+10 | 0.297557E+10 | 0.199032E+09 | 0.277654E+10 | 0.00 | 0.00 |
August | 0.293162E+10 | 0.145410E+10 | 0.249142E+10 | 44154751.14 | 0.244727E+10 | 0.00 | 0.00 |
September | 0.162798E+10 | 0.253485E+10 | 0.184859E+10 | 458364.66 | 0.184813E+10 | 0.00 | 0.00 |
October | 0.436625E+09 | 0.415450E+10 | 0.142027E+10 | 0.00 | 0.142027E+10 | 0.00 | 0.00 |
November | 76624846.84 | 0.664090E+10 | 0.961448E+09 | 0.00 | 0.961448E+09 | 0.00 | 0.00 |
December | 0.00 | 0.101475E+11 | 0.644441E+09 | 0.00 | 0.644441E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.151597E+11 | 0.601298E+11 | 0.219805E+11 | 0.634287E+09 | 0.213462E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.124190E+10 | 0.644441E+09 | 0.00 | 0.644441E+09 | 0.00 | 0.00 |
Maximum of Months | 0.346166E+10 | 0.117868E+11 | 0.307043E+10 | 0.278680E+09 | 0.279175E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.351004E+09 | 0.704116E+10 | 0.135575E+10 | 0.557892E+09 | 0.797857E+09 | 0.00 | 0.00 |
February | 0.672345E+09 | 0.500465E+10 | 0.162313E+10 | 0.713719E+09 | 0.909411E+09 | 0.00 | 0.00 |
March | 0.151332E+10 | 0.361292E+10 | 0.244163E+10 | 0.969148E+09 | 0.147248E+10 | 0.00 | 0.00 |
April | 0.249191E+10 | 0.246709E+10 | 0.290137E+10 | 0.127060E+10 | 0.163078E+10 | 0.00 | 0.00 |
May | 0.394399E+10 | 0.141753E+10 | 0.376535E+10 | 0.164528E+10 | 0.212007E+10 | 0.00 | 0.00 |
June | 0.486193E+10 | 0.964698E+09 | 0.401000E+10 | 0.174628E+10 | 0.226372E+10 | 0.00 | 0.00 |
July | 0.523482E+10 | 0.840813E+09 | 0.418819E+10 | 0.193251E+10 | 0.225567E+10 | 0.00 | 0.00 |
August | 0.444491E+10 | 0.976471E+09 | 0.353056E+10 | 0.152210E+10 | 0.200847E+10 | 0.00 | 0.00 |
September | 0.346306E+10 | 0.161230E+10 | 0.304736E+10 | 0.144003E+10 | 0.160733E+10 | 0.00 | 0.00 |
October | 0.154063E+10 | 0.253379E+10 | 0.200672E+10 | 0.838189E+09 | 0.116854E+10 | 0.00 | 0.00 |
November | 0.444775E+09 | 0.409579E+10 | 0.114579E+10 | 0.372173E+09 | 0.773620E+09 | 0.00 | 0.00 |
December | 0.280561E+09 | 0.622471E+10 | 0.917126E+09 | 0.393834E+09 | 0.523292E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292433E+11 | 0.367919E+11 | 0.309330E+11 | 0.134018E+11 | 0.175312E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280561E+09 | 0.840813E+09 | 0.917126E+09 | 0.372173E+09 | 0.523292E+09 | 0.00 | 0.00 |
Maximum of Months | 0.523482E+10 | 0.704116E+10 | 0.418819E+10 | 0.193251E+10 | 0.226372E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.432454E+10 | 0.930401E+10 | 0.590204E+10 | 0.403889E+10 | 0.186315E+10 | 0.00 | 0.00 |
February | 0.446596E+10 | 0.672350E+10 | 0.571194E+10 | 0.385902E+10 | 0.185292E+10 | 0.00 | 0.00 |
March | 0.463449E+10 | 0.537439E+10 | 0.550325E+10 | 0.289782E+10 | 0.260543E+10 | 0.00 | 0.00 |
April | 0.476778E+10 | 0.389524E+10 | 0.479813E+10 | 0.224321E+10 | 0.255492E+10 | 0.00 | 0.00 |
May | 0.441558E+10 | 0.232331E+10 | 0.410760E+10 | 0.111362E+10 | 0.299398E+10 | 0.00 | 0.00 |
June | 0.482195E+10 | 0.155717E+10 | 0.385922E+10 | 0.785752E+09 | 0.307347E+10 | 0.00 | 0.00 |
July | 0.555009E+10 | 0.135033E+10 | 0.422143E+10 | 0.106368E+10 | 0.315775E+10 | 0.00 | 0.00 |
August | 0.640766E+10 | 0.159005E+10 | 0.475614E+10 | 0.170566E+10 | 0.305049E+10 | 0.00 | 0.00 |
September | 0.687891E+10 | 0.257151E+10 | 0.557751E+10 | 0.293888E+10 | 0.263863E+10 | 0.00 | 0.00 |
October | 0.618623E+10 | 0.387148E+10 | 0.601822E+10 | 0.377558E+10 | 0.224264E+10 | 0.00 | 0.00 |
November | 0.363269E+10 | 0.573703E+10 | 0.439426E+10 | 0.275088E+10 | 0.164338E+10 | 0.00 | 0.00 |
December | 0.405483E+10 | 0.850742E+10 | 0.484203E+10 | 0.366778E+10 | 0.117426E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.601407E+11 | 0.528054E+11 | 0.596918E+11 | 0.308408E+11 | 0.288510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.363269E+10 | 0.135033E+10 | 0.385922E+10 | 0.785752E+09 | 0.117426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.687891E+10 | 0.930401E+10 | 0.601822E+10 | 0.403889E+10 | 0.315775E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.395962E+09 | 0.724245E+10 | 0.134457E+10 | 0.544028E+09 | 0.800545E+09 | 0.00 | 0.00 |
February | 0.881022E+09 | 0.522518E+10 | 0.178078E+10 | 0.877511E+09 | 0.903269E+09 | 0.00 | 0.00 |
March | 0.141410E+10 | 0.376675E+10 | 0.235366E+10 | 0.875685E+09 | 0.147797E+10 | 0.00 | 0.00 |
April | 0.311887E+10 | 0.258517E+10 | 0.332253E+10 | 0.164293E+10 | 0.167961E+10 | 0.00 | 0.00 |
May | 0.365961E+10 | 0.151860E+10 | 0.344322E+10 | 0.137548E+10 | 0.206774E+10 | 0.00 | 0.00 |
June | 0.482139E+10 | 0.105827E+10 | 0.390988E+10 | 0.169444E+10 | 0.221544E+10 | 0.00 | 0.00 |
July | 0.553551E+10 | 0.944184E+09 | 0.433796E+10 | 0.206059E+10 | 0.227737E+10 | 0.00 | 0.00 |
August | 0.489368E+10 | 0.106935E+10 | 0.379247E+10 | 0.174049E+10 | 0.205198E+10 | 0.00 | 0.00 |
September | 0.342692E+10 | 0.172573E+10 | 0.297086E+10 | 0.141012E+10 | 0.156075E+10 | 0.00 | 0.00 |
October | 0.175835E+10 | 0.269262E+10 | 0.213923E+10 | 0.951072E+09 | 0.118816E+10 | 0.00 | 0.00 |
November | 0.601028E+09 | 0.419066E+10 | 0.123916E+10 | 0.458240E+09 | 0.780924E+09 | 0.00 | 0.00 |
December | 0.385856E+09 | 0.635532E+10 | 0.984747E+09 | 0.464222E+09 | 0.520525E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.308923E+11 | 0.383743E+11 | 0.316191E+11 | 0.140948E+11 | 0.175243E+11 | 0.00 | 0.00 |
Minimum of Months | 0.385856E+09 | 0.944184E+09 | 0.984747E+09 | 0.458240E+09 | 0.520525E+09 | 0.00 | 0.00 |
Maximum of Months | 0.553551E+10 | 0.724245E+10 | 0.433796E+10 | 0.206059E+10 | 0.227737E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.116738E+11 | 0.949054E+09 | 0.00 | 0.949054E+09 | 0.00 | 0.00 |
February | 8966760.30 | 0.851298E+10 | 0.108677E+10 | 0.00 | 0.108677E+10 | 0.00 | 0.00 |
March | 0.331099E+09 | 0.595887E+10 | 0.180325E+10 | 0.00 | 0.180325E+10 | 0.00 | 0.00 |
April | 0.989614E+09 | 0.378864E+10 | 0.201458E+10 | 9925664.78 | 0.200465E+10 | 0.00 | 0.00 |
May | 0.234477E+10 | 0.199021E+10 | 0.271461E+10 | 0.102035E+09 | 0.261258E+10 | 0.00 | 0.00 |
June | 0.353650E+10 | 0.136808E+10 | 0.307041E+10 | 0.278678E+09 | 0.279173E+10 | 0.00 | 0.00 |
July | 0.355244E+10 | 0.124173E+10 | 0.297555E+10 | 0.199031E+09 | 0.277652E+10 | 0.00 | 0.00 |
August | 0.293553E+10 | 0.154403E+10 | 0.249141E+10 | 44154495.67 | 0.244726E+10 | 0.00 | 0.00 |
September | 0.159951E+10 | 0.276039E+10 | 0.184858E+10 | 458362.00 | 0.184812E+10 | 0.00 | 0.00 |
October | 0.398268E+09 | 0.456093E+10 | 0.142027E+10 | 0.00 | 0.142027E+10 | 0.00 | 0.00 |
November | 67145214.43 | 0.697376E+10 | 0.961442E+09 | 0.00 | 0.961442E+09 | 0.00 | 0.00 |
December | 0.00 | 0.102773E+11 | 0.644438E+09 | 0.00 | 0.644438E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157638E+11 | 0.606506E+11 | 0.219804E+11 | 0.634283E+09 | 0.213461E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.124173E+10 | 0.644438E+09 | 0.00 | 0.644438E+09 | 0.00 | 0.00 |
Maximum of Months | 0.355244E+10 | 0.116738E+11 | 0.307041E+10 | 0.278678E+09 | 0.279173E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.368040E+09 | 0.700494E+10 | 0.135580E+10 | 0.557914E+09 | 0.797882E+09 | 0.00 | 0.00 |
February | 0.695514E+09 | 0.499775E+10 | 0.162319E+10 | 0.713748E+09 | 0.909439E+09 | 0.00 | 0.00 |
March | 0.158024E+10 | 0.358387E+10 | 0.244171E+10 | 0.969188E+09 | 0.147252E+10 | 0.00 | 0.00 |
April | 0.260849E+10 | 0.240944E+10 | 0.290147E+10 | 0.127065E+10 | 0.163082E+10 | 0.00 | 0.00 |
May | 0.409463E+10 | 0.138350E+10 | 0.376548E+10 | 0.164535E+10 | 0.212014E+10 | 0.00 | 0.00 |
June | 0.495035E+10 | 0.974723E+09 | 0.401014E+10 | 0.174635E+10 | 0.226379E+10 | 0.00 | 0.00 |
July | 0.528518E+10 | 0.887780E+09 | 0.418833E+10 | 0.193259E+10 | 0.225574E+10 | 0.00 | 0.00 |
August | 0.444644E+10 | 0.107471E+10 | 0.353068E+10 | 0.152216E+10 | 0.200853E+10 | 0.00 | 0.00 |
September | 0.343139E+10 | 0.181298E+10 | 0.304747E+10 | 0.144009E+10 | 0.160738E+10 | 0.00 | 0.00 |
October | 0.148604E+10 | 0.283337E+10 | 0.200679E+10 | 0.838223E+09 | 0.116857E+10 | 0.00 | 0.00 |
November | 0.427025E+09 | 0.432745E+10 | 0.114583E+10 | 0.372188E+09 | 0.773644E+09 | 0.00 | 0.00 |
December | 0.280856E+09 | 0.633409E+10 | 0.917158E+09 | 0.393850E+09 | 0.523308E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.296542E+11 | 0.376246E+11 | 0.309341E+11 | 0.134023E+11 | 0.175318E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280856E+09 | 0.887780E+09 | 0.917158E+09 | 0.372188E+09 | 0.523308E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528518E+10 | 0.700494E+10 | 0.418833E+10 | 0.193259E+10 | 0.226379E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449835E+10 | 0.914235E+10 | 0.590208E+10 | 0.403891E+10 | 0.186316E+10 | 0.00 | 0.00 |
February | 0.463852E+10 | 0.672453E+10 | 0.571197E+10 | 0.385905E+10 | 0.185292E+10 | 0.00 | 0.00 |
March | 0.483646E+10 | 0.535133E+10 | 0.550328E+10 | 0.289784E+10 | 0.260544E+10 | 0.00 | 0.00 |
April | 0.498356E+10 | 0.383155E+10 | 0.479815E+10 | 0.224322E+10 | 0.255493E+10 | 0.00 | 0.00 |
May | 0.466043E+10 | 0.223997E+10 | 0.410762E+10 | 0.111362E+10 | 0.299399E+10 | 0.00 | 0.00 |
June | 0.498208E+10 | 0.152549E+10 | 0.385923E+10 | 0.785757E+09 | 0.307348E+10 | 0.00 | 0.00 |
July | 0.564425E+10 | 0.139495E+10 | 0.422145E+10 | 0.106369E+10 | 0.315776E+10 | 0.00 | 0.00 |
August | 0.643679E+10 | 0.175533E+10 | 0.475616E+10 | 0.170567E+10 | 0.305050E+10 | 0.00 | 0.00 |
September | 0.688529E+10 | 0.290708E+10 | 0.557754E+10 | 0.293890E+10 | 0.263864E+10 | 0.00 | 0.00 |
October | 0.617375E+10 | 0.439640E+10 | 0.601825E+10 | 0.377560E+10 | 0.224265E+10 | 0.00 | 0.00 |
November | 0.363168E+10 | 0.610338E+10 | 0.439428E+10 | 0.275090E+10 | 0.164338E+10 | 0.00 | 0.00 |
December | 0.412244E+10 | 0.862421E+10 | 0.484206E+10 | 0.366780E+10 | 0.117426E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.614936E+11 | 0.539966E+11 | 0.596921E+11 | 0.308410E+11 | 0.288511E+11 | 0.00 | 0.00 |
Minimum of Months | 0.363168E+10 | 0.139495E+10 | 0.385923E+10 | 0.785757E+09 | 0.117426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.688529E+10 | 0.914235E+10 | 0.601825E+10 | 0.403891E+10 | 0.315776E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.420844E+09 | 0.719195E+10 | 0.134462E+10 | 0.544048E+09 | 0.800568E+09 | 0.00 | 0.00 |
February | 0.925039E+09 | 0.520094E+10 | 0.178084E+10 | 0.877544E+09 | 0.903295E+09 | 0.00 | 0.00 |
March | 0.150008E+10 | 0.373414E+10 | 0.235373E+10 | 0.875718E+09 | 0.147802E+10 | 0.00 | 0.00 |
April | 0.325531E+10 | 0.254893E+10 | 0.332264E+10 | 0.164299E+10 | 0.167965E+10 | 0.00 | 0.00 |
May | 0.381485E+10 | 0.148053E+10 | 0.344333E+10 | 0.137553E+10 | 0.206780E+10 | 0.00 | 0.00 |
June | 0.491183E+10 | 0.106866E+10 | 0.391000E+10 | 0.169450E+10 | 0.221550E+10 | 0.00 | 0.00 |
July | 0.558118E+10 | 0.100713E+10 | 0.433810E+10 | 0.206066E+10 | 0.227743E+10 | 0.00 | 0.00 |
August | 0.489626E+10 | 0.118730E+10 | 0.379259E+10 | 0.174055E+10 | 0.205204E+10 | 0.00 | 0.00 |
September | 0.341078E+10 | 0.193187E+10 | 0.297096E+10 | 0.141017E+10 | 0.156079E+10 | 0.00 | 0.00 |
October | 0.174097E+10 | 0.300470E+10 | 0.213930E+10 | 0.951108E+09 | 0.118819E+10 | 0.00 | 0.00 |
November | 0.596191E+09 | 0.442476E+10 | 0.123920E+10 | 0.458257E+09 | 0.780947E+09 | 0.00 | 0.00 |
December | 0.397153E+09 | 0.645782E+10 | 0.984779E+09 | 0.464239E+09 | 0.520540E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.314505E+11 | 0.392387E+11 | 0.316201E+11 | 0.140953E+11 | 0.175248E+11 | 0.00 | 0.00 |
Minimum of Months | 0.397153E+09 | 0.100713E+10 | 0.984779E+09 | 0.458257E+09 | 0.520540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.558118E+10 | 0.719195E+10 | 0.433810E+10 | 0.206066E+10 | 0.227743E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.119562E+11 | 0.949059E+09 | 0.00 | 0.949059E+09 | 0.00 | 0.00 |
February | 6393798.18 | 0.881381E+10 | 0.108678E+10 | 0.00 | 0.108678E+10 | 0.00 | 0.00 |
March | 0.265993E+09 | 0.633354E+10 | 0.180326E+10 | 0.00 | 0.180326E+10 | 0.00 | 0.00 |
April | 0.837261E+09 | 0.418037E+10 | 0.201459E+10 | 9925722.21 | 0.200466E+10 | 0.00 | 0.00 |
May | 0.204602E+10 | 0.228104E+10 | 0.271463E+10 | 0.102036E+09 | 0.261259E+10 | 0.00 | 0.00 |
June | 0.331008E+10 | 0.153935E+10 | 0.307043E+10 | 0.278680E+09 | 0.279175E+10 | 0.00 | 0.00 |
July | 0.339252E+10 | 0.134842E+10 | 0.297557E+10 | 0.199032E+09 | 0.277654E+10 | 0.00 | 0.00 |
August | 0.285413E+10 | 0.159775E+10 | 0.249142E+10 | 44154751.14 | 0.244727E+10 | 0.00 | 0.00 |
September | 0.156399E+10 | 0.277403E+10 | 0.184859E+10 | 458364.66 | 0.184813E+10 | 0.00 | 0.00 |
October | 0.386689E+09 | 0.452536E+10 | 0.142027E+10 | 0.00 | 0.142027E+10 | 0.00 | 0.00 |
November | 62504237.08 | 0.696346E+10 | 0.961448E+09 | 0.00 | 0.961448E+09 | 0.00 | 0.00 |
December | 0.00 | 0.104044E+11 | 0.644441E+09 | 0.00 | 0.644441E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.147256E+11 | 0.627177E+11 | 0.219805E+11 | 0.634287E+09 | 0.213462E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.134842E+10 | 0.644441E+09 | 0.00 | 0.644441E+09 | 0.00 | 0.00 |
Maximum of Months | 0.339252E+10 | 0.119562E+11 | 0.307043E+10 | 0.278680E+09 | 0.279175E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.346977E+09 | 0.714183E+10 | 0.135575E+10 | 0.557892E+09 | 0.797857E+09 | 0.00 | 0.00 |
February | 0.660135E+09 | 0.513582E+10 | 0.162313E+10 | 0.713719E+09 | 0.909411E+09 | 0.00 | 0.00 |
March | 0.147105E+10 | 0.377986E+10 | 0.244163E+10 | 0.969148E+09 | 0.147248E+10 | 0.00 | 0.00 |
April | 0.244641E+10 | 0.262024E+10 | 0.290137E+10 | 0.127060E+10 | 0.163078E+10 | 0.00 | 0.00 |
May | 0.387522E+10 | 0.152015E+10 | 0.376535E+10 | 0.164528E+10 | 0.212007E+10 | 0.00 | 0.00 |
June | 0.482728E+10 | 0.103798E+10 | 0.401000E+10 | 0.174628E+10 | 0.226372E+10 | 0.00 | 0.00 |
July | 0.520162E+10 | 0.906620E+09 | 0.418819E+10 | 0.193251E+10 | 0.225567E+10 | 0.00 | 0.00 |
August | 0.439665E+10 | 0.106076E+10 | 0.353056E+10 | 0.152210E+10 | 0.200847E+10 | 0.00 | 0.00 |
September | 0.339840E+10 | 0.176320E+10 | 0.304736E+10 | 0.144003E+10 | 0.160733E+10 | 0.00 | 0.00 |
October | 0.145101E+10 | 0.277380E+10 | 0.200672E+10 | 0.838189E+09 | 0.116854E+10 | 0.00 | 0.00 |
November | 0.413018E+09 | 0.430139E+10 | 0.114579E+10 | 0.372173E+09 | 0.773620E+09 | 0.00 | 0.00 |
December | 0.271998E+09 | 0.637887E+10 | 0.917126E+09 | 0.393834E+09 | 0.523292E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.287598E+11 | 0.384205E+11 | 0.309330E+11 | 0.134018E+11 | 0.175312E+11 | 0.00 | 0.00 |
Minimum of Months | 0.271998E+09 | 0.906620E+09 | 0.917126E+09 | 0.372173E+09 | 0.523292E+09 | 0.00 | 0.00 |
Maximum of Months | 0.520162E+10 | 0.714183E+10 | 0.418819E+10 | 0.193251E+10 | 0.226372E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.429831E+10 | 0.948770E+10 | 0.590204E+10 | 0.403889E+10 | 0.186315E+10 | 0.00 | 0.00 |
February | 0.443463E+10 | 0.695015E+10 | 0.571194E+10 | 0.385902E+10 | 0.185292E+10 | 0.00 | 0.00 |
March | 0.459076E+10 | 0.563921E+10 | 0.550325E+10 | 0.289782E+10 | 0.260543E+10 | 0.00 | 0.00 |
April | 0.474382E+10 | 0.414134E+10 | 0.479813E+10 | 0.224321E+10 | 0.255492E+10 | 0.00 | 0.00 |
May | 0.436497E+10 | 0.250160E+10 | 0.410760E+10 | 0.111362E+10 | 0.299398E+10 | 0.00 | 0.00 |
June | 0.478875E+10 | 0.168834E+10 | 0.385922E+10 | 0.785752E+09 | 0.307347E+10 | 0.00 | 0.00 |
July | 0.551094E+10 | 0.147050E+10 | 0.422143E+10 | 0.106368E+10 | 0.315775E+10 | 0.00 | 0.00 |
August | 0.636332E+10 | 0.174071E+10 | 0.475614E+10 | 0.170566E+10 | 0.305049E+10 | 0.00 | 0.00 |
September | 0.682097E+10 | 0.281056E+10 | 0.557751E+10 | 0.293888E+10 | 0.263863E+10 | 0.00 | 0.00 |
October | 0.608473E+10 | 0.422338E+10 | 0.601822E+10 | 0.377558E+10 | 0.224264E+10 | 0.00 | 0.00 |
November | 0.356190E+10 | 0.605020E+10 | 0.439426E+10 | 0.275088E+10 | 0.164338E+10 | 0.00 | 0.00 |
December | 0.400620E+10 | 0.877944E+10 | 0.484203E+10 | 0.366778E+10 | 0.117426E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.595693E+11 | 0.554831E+11 | 0.596918E+11 | 0.308408E+11 | 0.288510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.356190E+10 | 0.147050E+10 | 0.385922E+10 | 0.785752E+09 | 0.117426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.682097E+10 | 0.948770E+10 | 0.601822E+10 | 0.403889E+10 | 0.315775E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.395711E+09 | 0.735391E+10 | 0.134457E+10 | 0.544028E+09 | 0.800545E+09 | 0.00 | 0.00 |
February | 0.878121E+09 | 0.536176E+10 | 0.178078E+10 | 0.877511E+09 | 0.903269E+09 | 0.00 | 0.00 |
March | 0.140192E+10 | 0.393721E+10 | 0.235366E+10 | 0.875685E+09 | 0.147797E+10 | 0.00 | 0.00 |
April | 0.311439E+10 | 0.274579E+10 | 0.332253E+10 | 0.164293E+10 | 0.167961E+10 | 0.00 | 0.00 |
May | 0.363749E+10 | 0.162892E+10 | 0.344322E+10 | 0.137548E+10 | 0.206774E+10 | 0.00 | 0.00 |
June | 0.480774E+10 | 0.113845E+10 | 0.390988E+10 | 0.169444E+10 | 0.221544E+10 | 0.00 | 0.00 |
July | 0.551741E+10 | 0.101932E+10 | 0.433796E+10 | 0.206059E+10 | 0.227737E+10 | 0.00 | 0.00 |
August | 0.486695E+10 | 0.116128E+10 | 0.379247E+10 | 0.174049E+10 | 0.205198E+10 | 0.00 | 0.00 |
September | 0.339590E+10 | 0.187774E+10 | 0.297086E+10 | 0.141012E+10 | 0.156075E+10 | 0.00 | 0.00 |
October | 0.171909E+10 | 0.293403E+10 | 0.213923E+10 | 0.951072E+09 | 0.118816E+10 | 0.00 | 0.00 |
November | 0.583690E+09 | 0.439497E+10 | 0.123916E+10 | 0.458240E+09 | 0.780924E+09 | 0.00 | 0.00 |
December | 0.380952E+09 | 0.651983E+10 | 0.984747E+09 | 0.464222E+09 | 0.520525E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.306994E+11 | 0.400732E+11 | 0.316191E+11 | 0.140948E+11 | 0.175243E+11 | 0.00 | 0.00 |
Minimum of Months | 0.380952E+09 | 0.101932E+10 | 0.984747E+09 | 0.458240E+09 | 0.520525E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551741E+10 | 0.735391E+10 | 0.433796E+10 | 0.206059E+10 | 0.227737E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.552086E+10 | -0.526311E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -257743467.2 | 60.05 | 0.00 | 0.00 |
February | 0.510530E+10 | -0.487798E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -227327270.1 | 60.05 | 0.00 | 0.00 |
March | 0.596254E+10 | -0.571793E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -244614069.2 | 60.05 | 0.00 | 0.00 |
April | 0.518247E+10 | -0.495087E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -231599495.0 | 60.05 | 0.00 | 0.00 |
May | 0.523819E+10 | -0.500407E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234121257.9 | 60.05 | 0.00 | 0.00 |
June | 0.486671E+10 | -0.464127E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225439224.9 | 60.05 | 0.00 | 0.00 |
July | 0.436227E+10 | -0.413070E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231571032.7 | 60.05 | 0.00 | 0.00 |
August | 0.468286E+10 | -0.445094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231922202.5 | 60.05 | 0.00 | 0.00 |
September | 0.428574E+10 | -0.406062E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225119119.6 | 60.05 | 0.00 | 0.00 |
October | 0.463706E+10 | -0.440059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -236469057.5 | 60.05 | 0.00 | 0.00 |
November | 0.485662E+10 | -0.462151E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -235107230.0 | 60.05 | 0.00 | 0.00 |
December | 0.512673E+10 | -0.487588E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -250843578.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.598274E+11 | -0.569955E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.283188E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.428574E+10 | -0.571793E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -257743467.2 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.596254E+10 | -0.406062E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -225119119.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194989E+11 | 30645.71 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106231E+11 | 31444.27 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330663E+10 | 16416.27 | 06-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.673683E+09 | 10794.22 | 03-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 151676.04 | 4.87 | 30-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 615190.53 | 5.76 | 30-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 815318.02 | 5.82 | 05-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 929225.71 | 6.35 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 466132.54 | 5.85 | 06-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5783293.93 | 1712.31 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.411564E+10 | 23551.87 | 25-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111256E+11 | 28922.72 | 11-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 151676.04 | 4.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.194989E+11 | 31444.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112173E+10 | 17548.32 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272165E+09 | 17495.56 | 07-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22261258.35 | 17488.91 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89981155.63 | 17489.14 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.238926E+09 | 17492.75 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112173E+10 | 17548.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149515E+11 | 14068.73 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107044E+11 | 14444.49 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.902734E+10 | 13599.31 | 30-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.537149E+10 | 13613.24 | 19-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175697E+10 | 13580.31 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.619522E+09 | 13608.61 | 02-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 61181420.38 | 6011.77 | 24-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142311E+09 | 9034.05 | 07-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.916824E+09 | 13640.78 | 19-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237682E+10 | 13595.45 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.672621E+10 | 13607.06 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115255E+11 | 13595.59 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.641801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 61181420.38 | 6011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149515E+11 | 14444.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.825286E+10 | 9259.82 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.571004E+10 | 9507.14 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.383193E+10 | 8944.60 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197499E+10 | 8923.43 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200143E+09 | 8870.07 | 02-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 61331662.33 | 5354.71 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96933560.08 | 8884.48 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.634868E+09 | 8885.73 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294695E+10 | 8943.58 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.589271E+10 | 8945.26 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.825286E+10 | 9507.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137882E+11 | 14339.22 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101412E+11 | 14722.20 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730329E+10 | 13854.55 | 23-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398497E+10 | 13850.32 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.871079E+09 | 13818.97 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147238E+09 | 8713.78 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.326279E+09 | 13757.98 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160305E+10 | 13786.68 | 18-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496695E+10 | 13849.50 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.969135E+10 | 13856.98 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.528236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137882E+11 | 14722.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.848233E+10 | 9436.72 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587655E+10 | 9688.77 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.414631E+10 | 9115.48 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189538E+10 | 9093.90 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.354335E+09 | 9094.35 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82329592.67 | 5602.75 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168171E+09 | 9054.21 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.716921E+09 | 9055.48 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301093E+10 | 9114.44 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.598850E+10 | 9116.15 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.848233E+10 | 9688.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.234211E+11 | 28803.01 | 30-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138748E+11 | 29386.58 | 02-FEB-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.718480E+10 | 20888.22 | 06-MAR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197799E+10 | 15287.65 | 03-APR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8382205.15 | 2311.05 | 02-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 307925.26 | 5.78 | 30-JUN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 167321.20 | 5.47 | 03-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 257874.45 | 5.62 | 04-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45509141.30 | 4563.98 | 29-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.492151E+09 | 9295.74 | 23-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728435E+10 | 25113.92 | 25-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166370E+11 | 27654.37 | 11-DEC-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.709269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 167321.20 | 5.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.234211E+11 | 29386.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.560231E+10 | 23369.20 | 30-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320990E+10 | 23546.40 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101270E+10 | 23321.98 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231936E+09 | 23313.15 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16006512.76 | 23039.06 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148435E+10 | 23351.52 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322588E+10 | 23317.44 | 05-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.560231E+10 | 23546.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.937650E+10 | 14815.04 | 30-JAN-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.583877E+10 | 15047.21 | 02-FEB-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360093E+10 | 13920.39 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161640E+10 | 13892.88 | 03-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135145E+09 | 13819.67 | 02-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41956838.03 | 8013.60 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.239171E+09 | 13821.27 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.932228E+09 | 13888.51 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.392032E+10 | 13927.63 | 27-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.746317E+10 | 14121.65 | 11-DEC-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.937650E+10 | 15047.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.775570E+10 | 10021.04 | 30-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.485983E+10 | 10229.09 | 02-FEB-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263567E+10 | 9461.90 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108677E+10 | 9456.76 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49809557.32 | 9393.23 | 02-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31012850.78 | 5231.04 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174113E+09 | 9394.28 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.878179E+09 | 9440.02 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312073E+10 | 9462.06 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.581490E+10 | 9656.27 | 11-DEC-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.775570E+10 | 10229.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133047E+11 | 15252.37 | 30-JAN-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.900710E+10 | 15655.45 | 02-FEB-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.526826E+10 | 14188.99 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219490E+10 | 14198.75 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168451E+09 | 14086.32 | 02-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46796806.65 | 8112.50 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.402698E+09 | 14087.95 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182623E+10 | 14156.48 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.538278E+10 | 14223.95 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.989335E+10 | 14637.28 | 11-DEC-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133047E+11 | 15655.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.844981E+10 | 10470.46 | 30-JAN-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552268E+10 | 10747.68 | 02-FEB-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323269E+10 | 9738.94 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128136E+10 | 9716.92 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129292E+09 | 9668.19 | 02-MAY-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42399576.57 | 5364.44 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.283740E+09 | 9699.47 | 29-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112490E+10 | 9716.35 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352844E+10 | 9738.96 | 20-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.638343E+10 | 10034.59 | 11-DEC-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.844981E+10 | 10747.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249071E+11 | 25149.86 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134212E+11 | 25782.52 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504940E+10 | 20265.23 | 06-MAR-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116953E+10 | 13634.73 | 03-APR-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7571562.34 | 2894.81 | 02-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 197518.30 | 6.51 | 30-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29117.63 | 5.01 | 05-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38169.20 | 6.65 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 52639283.73 | 6022.01 | 29-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.388186E+09 | 10187.08 | 23-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728478E+10 | 23728.42 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169501E+11 | 24483.12 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 29117.63 | 5.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.249071E+11 | 25782.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161111E+11 | 38257.01 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107468E+11 | 39231.80 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.557986E+10 | 37017.55 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211783E+10 | 37008.28 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75598038.89 | 36774.00 | 03-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15138645.42 | 10536.18 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.305592E+09 | 36796.17 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179633E+10 | 37029.67 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661053E+10 | 37053.90 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123224E+11 | 37228.38 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161111E+11 | 39231.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142089E+11 | 18976.90 | 31-JAN-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.946867E+10 | 19607.06 | 02-FEB-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.635904E+10 | 17968.25 | 18-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.336250E+10 | 17972.05 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.703636E+09 | 17922.27 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.269392E+09 | 10442.44 | 03-JUN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27188688.30 | 6860.56 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 61986628.25 | 7911.89 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.981069E+09 | 17862.61 | 27-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.273476E+10 | 17970.24 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.712427E+10 | 18076.87 | 28-NOV-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116985E+11 | 18502.52 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 27188688.30 | 6860.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142089E+11 | 19607.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113182E+11 | 12418.89 | 31-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.765616E+10 | 12837.76 | 02-FEB-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.468194E+10 | 11764.75 | 18-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226601E+10 | 11767.24 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293509E+09 | 11734.64 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151225E+09 | 6330.61 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3535220.70 | 679.18 | 08-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9459397.05 | 4116.03 | 25-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.629590E+09 | 11695.58 | 27-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220951E+10 | 11766.05 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.557546E+10 | 11770.58 | 15-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.913705E+10 | 12114.56 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3535220.70 | 679.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113182E+11 | 12837.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184774E+11 | 19465.77 | 30-JAN-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130937E+11 | 20011.67 | 02-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.847414E+10 | 18241.88 | 18-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.418322E+10 | 18245.73 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.832191E+09 | 18195.19 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.279213E+09 | 9957.35 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16561623.11 | 5230.83 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 67616133.66 | 7826.99 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140535E+10 | 18134.62 | 27-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.428162E+10 | 18251.97 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.905204E+10 | 18250.92 | 15-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146809E+11 | 18784.28 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.748439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16561623.11 | 5230.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184774E+11 | 20011.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115669E+11 | 12743.71 | 30-JAN-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.790967E+10 | 13101.09 | 02-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.502576E+10 | 11942.46 | 18-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235258E+10 | 11944.99 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.493775E+09 | 11911.90 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187035E+09 | 7028.12 | 03-JUN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16139171.18 | 4353.63 | 12-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42357763.18 | 5100.96 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.842588E+09 | 11872.25 | 27-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245660E+10 | 11943.78 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568683E+10 | 11966.52 | 28-NOV-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925707E+10 | 12297.55 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 16139171.18 | 4353.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115669E+11 | 13101.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 205757.40 | 205757.40 | 2057.57 | 07-FEB-07:12 | 2057.57 | 0.00 |
March | 0.00 | 0.00 | 0.268532E+09 | 0.259237E+09 | 12234.94 | 25-MAR-15:00 | 12234.94 | 0.00 |
April | 0.00 | 0.00 | 0.600465E+10 | 0.494024E+10 | 63777.22 | 18-APR-15:00 | 53489.77 | 0.00 |
May | 0.00 | 0.00 | 0.170258E+11 | 0.133025E+11 | 64028.95 | 31-MAY-15:00 | 58848.56 | 0.00 |
June | 0.00 | 0.00 | 0.483997E+11 | 0.389064E+11 | 118172.03 | 30-JUN-05:12 | 51969.24 | 0.00 |
July | 0.00 | 0.00 | 0.676457E+11 | 0.514497E+11 | 113903.13 | 27-JUL-05:12 | 42692.13 | 0.00 |
August | 0.00 | 0.00 | 0.677312E+11 | 0.521680E+11 | 135360.28 | 03-AUG-05:12 | 74930.81 | 0.00 |
September | 0.00 | 0.00 | 0.290506E+11 | 0.268151E+11 | 88371.65 | 11-SEP-05:12 | 46177.01 | 0.00 |
October | 0.00 | 0.00 | 0.220162E+10 | 0.196384E+10 | 43146.60 | 20-OCT-15:00 | 43146.60 | 0.00 |
November | 0.00 | 0.00 | 91096940.66 | 84653096.98 | 7135.92 | 03-NOV-14:40 | 7135.92 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.238419E+12 | 0.189890E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.677312E+11 | 0.521680E+11 | 135360.28 | 74930.81 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 277462.15 | 275574.15 | 514.45 | 29-JAN-20:11 | 514.45 | 0.00 |
February | 0.00 | 0.00 | 93301.63 | 93301.63 | 633.06 | 06-FEB-02:61 | 633.06 | 0.00 |
March | 0.00 | 0.00 | 0.242525E+09 | 0.215675E+09 | 11694.56 | 25-MAR-15:00 | 11379.36 | 0.00 |
April | 0.00 | 0.00 | 0.650559E+10 | 0.519717E+10 | 66787.04 | 18-APR-14:05 | 56097.98 | 0.00 |
May | 0.00 | 0.00 | 0.167611E+11 | 0.127218E+11 | 65931.59 | 31-MAY-14:05 | 60725.50 | 0.00 |
June | 0.00 | 0.00 | 0.461767E+11 | 0.362440E+11 | 81390.60 | 27-JUN-14:05 | 66948.69 | 0.00 |
July | 0.00 | 0.00 | 0.620158E+11 | 0.460530E+11 | 88936.11 | 26-JUL-15:00 | 61511.78 | 0.00 |
August | 0.00 | 0.00 | 0.596617E+11 | 0.445183E+11 | 98134.26 | 04-AUG-14:05 | 73345.53 | 0.00 |
September | 0.00 | 0.00 | 0.249119E+11 | 0.223033E+11 | 75597.73 | 06-SEP-14:05 | 67176.24 | 0.00 |
October | 0.00 | 0.00 | 0.187590E+10 | 0.158478E+10 | 35068.64 | 20-OCT-15:00 | 35068.64 | 0.00 |
November | 0.00 | 0.00 | 71645119.92 | 61330407.00 | 6042.91 | 03-NOV-14:02 | 5490.05 | 0.00 |
December | 0.00 | 0.00 | 54527.91 | 54527.91 | 636.16 | 10-DEC-22:01 | 636.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.218223E+12 | 0.168900E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 54527.91 | 54527.91 | 514.45 | 514.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.620158E+11 | 0.460530E+11 | 98134.26 | 73345.53 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2815194.86 | 2785239.32 | 1700.84 | 09-JAN-06:05 | 1700.84 | 0.00 |
February | 0.00 | 0.00 | 3670264.06 | 3560872.13 | 1668.15 | 21-FEB-06:06 | 1668.15 | 0.00 |
March | 0.00 | 0.00 | 0.305411E+09 | 0.260867E+09 | 15313.16 | 25-MAR-15:00 | 14234.86 | 0.00 |
April | 0.00 | 0.00 | 0.820231E+10 | 0.655101E+10 | 77117.56 | 18-APR-15:00 | 67562.95 | 0.00 |
May | 0.00 | 0.00 | 0.213559E+11 | 0.161289E+11 | 79560.50 | 31-MAY-15:00 | 75126.27 | 0.00 |
June | 0.00 | 0.00 | 0.558510E+11 | 0.437688E+11 | 95644.29 | 26-JUN-14:00 | 84506.88 | 0.00 |
July | 0.00 | 0.00 | 0.737260E+11 | 0.551782E+11 | 100039.81 | 26-JUL-15:10 | 73518.89 | 0.00 |
August | 0.00 | 0.00 | 0.699623E+11 | 0.518672E+11 | 111830.39 | 04-AUG-15:30 | 88681.40 | 0.00 |
September | 0.00 | 0.00 | 0.293976E+11 | 0.256360E+11 | 84767.62 | 06-SEP-14:30 | 77602.96 | 0.00 |
October | 0.00 | 0.00 | 0.229435E+10 | 0.187148E+10 | 40654.97 | 20-OCT-15:00 | 40654.97 | 0.00 |
November | 0.00 | 0.00 | 80084354.52 | 64246416.75 | 6606.00 | 03-NOV-14:00 | 5379.08 | 0.00 |
December | 0.00 | 0.00 | 3423798.72 | 3364101.39 | 2416.35 | 11-DEC-06:37 | 2416.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.261185E+12 | 0.201336E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2815194.86 | 2785239.32 | 1668.15 | 1668.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.737260E+11 | 0.551782E+11 | 111830.39 | 88681.40 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 85420.30 | 376730.65 | 12-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 60679.42 | 395861.70 | 10-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 31748.62 | 416269.00 | 23-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14441.19 | 408910.74 | 29-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2251.68 | 347298.58 | 02-MAY-05:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 760.32 | 187326.09 | 05-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 43.70 | 27541.70 | 24-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 118.72 | 38797.82 | 07-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2628.39 | 346224.16 | 29-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 9068.22 | 428672.10 | 24-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 33646.90 | 420332.10 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 62203.17 | 374604.04 | 14-DEC-06:01 |
Annual Sum or Average | 0.00 | 25095.38 | ||||
Minimum of Months | 0.00 | 0.00 | 43.70 | 27541.70 | ||
Maximum of Months | 0.00 | 0.00 | 85420.30 | 428672.10 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 1955.34 | 7209.48 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 2006.59 | 7256.37 | 21-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2124.75 | 7245.55 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1900.47 | 7041.28 | 03-APR-11:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1858.67 | 6708.71 | 01-MAY-11:13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1781.01 | 6265.19 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1533.17 | 5851.63 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1652.33 | 5617.77 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1557.45 | 5750.26 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1633.73 | 6122.63 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1773.50 | 6552.15 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1811.04 | 6933.65 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1797.80 | ||||
Minimum of Months | 0.00 | 0.00 | 1533.17 | 5617.77 | ||
Maximum of Months | 0.00 | 0.00 | 2124.75 | 7256.37 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.639645E+10 | 0.79 | 6745.14 | 02-JAN-05:01 | 1.42 |
February | 0.484760E+10 | 0.67 | 6745.14 | 01-FEB-07:01 | 1.43 |
March | 0.492952E+10 | 0.62 | 6745.14 | 06-MAR-07:01 | 1.43 |
April | 0.461979E+10 | 0.57 | 9836.29 | 21-APR-05:01 | 1.67 |
May | 0.541482E+10 | 0.59 | 8152.69 | 30-MAY-05:13 | 1.52 |
June | 0.712122E+10 | 0.70 | 9414.13 | 27-JUN-15:30 | 1.62 |
July | 0.764495E+10 | 0.69 | 9582.51 | 05-JUL-06:03 | 1.63 |
August | 0.839659E+10 | 0.73 | 11486.14 | 04-AUG-15:30 | 1.76 |
September | 0.681721E+10 | 0.67 | 11234.65 | 07-SEP-15:20 | 1.75 |
October | 0.468473E+10 | 0.55 | 6062.19 | 20-OCT-15:30 | 1.35 |
November | 0.460559E+10 | 0.58 | 6745.14 | 27-NOV-06:01 | 1.43 |
December | 0.504310E+10 | 0.64 | 6745.14 | 11-DEC-06:01 | 1.43 |
Annual Sum or Average | 0.705216E+11 | 0.65 | |||
Minimum of Months | 0.460559E+10 | 0.55 | 6062.19 | 1.35 | |
Maximum of Months | 0.839659E+10 | 0.79 | 11486.14 | 1.76 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.527420E+10 | 0.71 | 5709.53 | 02-JAN-06:01 | 1.26 |
February | 0.394077E+10 | 0.59 | 5709.53 | 06-FEB-06:15 | 1.27 |
March | 0.386552E+10 | 0.54 | 5709.53 | 01-MAR-06:01 | 1.27 |
April | 0.363861E+10 | 0.50 | 6888.28 | 18-APR-14:05 | 1.35 |
May | 0.418141E+10 | 0.52 | 7477.05 | 31-MAY-14:05 | 1.40 |
June | 0.565886E+10 | 0.61 | 8707.10 | 26-JUN-14:05 | 1.49 |
July | 0.591034E+10 | 0.60 | 8206.06 | 03-JUL-15:00 | 1.45 |
August | 0.612050E+10 | 0.62 | 9325.27 | 04-AUG-14:05 | 1.54 |
September | 0.472822E+10 | 0.55 | 8973.84 | 07-SEP-14:05 | 1.51 |
October | 0.335250E+10 | 0.46 | 5709.53 | 16-OCT-06:02 | 1.26 |
November | 0.360627E+10 | 0.51 | 5709.53 | 24-NOV-06:13 | 1.27 |
December | 0.429865E+10 | 0.59 | 5709.53 | 12-DEC-06:13 | 1.27 |
Annual Sum or Average | 0.545758E+11 | 0.57 | |||
Minimum of Months | 0.335250E+10 | 0.46 | 5709.53 | 1.26 | |
Maximum of Months | 0.612050E+10 | 0.71 | 9325.27 | 1.54 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.660741E+10 | 0.69 | 6514.26 | 03-JAN-07:02 | 1.13 |
February | 0.546097E+10 | 0.63 | 6514.26 | 01-FEB-07:03 | 1.13 |
March | 0.493802E+10 | 0.53 | 6514.26 | 13-MAR-06:04 | 1.13 |
April | 0.434143E+10 | 0.47 | 6514.26 | 01-APR-05:01 | 1.13 |
May | 0.451016E+10 | 0.46 | 6891.75 | 31-MAY-15:00 | 1.14 |
June | 0.553059E+10 | 0.52 | 8046.31 | 26-JUN-15:30 | 1.22 |
July | 0.559962E+10 | 0.50 | 7549.10 | 05-JUL-15:20 | 1.18 |
August | 0.566827E+10 | 0.51 | 8520.06 | 04-AUG-15:20 | 1.25 |
September | 0.465707E+10 | 0.47 | 7527.12 | 07-SEP-14:30 | 1.18 |
October | 0.398242E+10 | 0.42 | 6514.26 | 27-OCT-06:02 | 1.13 |
November | 0.503813E+10 | 0.55 | 6514.26 | 13-NOV-07:03 | 1.13 |
December | 0.608247E+10 | 0.64 | 6514.26 | 08-DEC-07:01 | 1.13 |
Annual Sum or Average | 0.624166E+11 | 0.53 | |||
Minimum of Months | 0.398242E+10 | 0.42 | 6514.26 | 1.13 | |
Maximum of Months | 0.660741E+10 | 0.69 | 8520.06 | 1.25 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.170878E+10 | 0.153790E+10 | 1662.90 | 30-JAN-07:25 | 1496.61 | 1496.61 | 45.88 | 5.29 |
February | 0.107960E+10 | 0.971639E+09 | 1663.56 | 02-FEB-07:01 | 1497.20 | 1497.20 | 47.01 | 5.31 |
March | 0.651543E+09 | 0.586389E+09 | 1484.44 | 06-MAR-07:01 | 1336.00 | 1336.00 | 48.68 | 4.74 |
April | 0.285764E+09 | 0.257188E+09 | 1408.34 | 03-APR-06:01 | 1267.50 | 1267.50 | 47.52 | 4.39 |
May | 49617662.96 | 44655896.67 | 1325.49 | 02-MAY-06:03 | 1192.94 | 1192.94 | 40.53 | 3.82 |
June | 15643765.22 | 14079388.70 | 985.93 | 05-JUN-06:03 | 887.34 | 887.34 | 31.63 | 1.58 |
July | 861631.23 | 775468.11 | 180.99 | 24-JUL-06:03 | 162.89 | 162.89 | 26.13 | 0.19 |
August | 2370018.74 | 2133016.87 | 269.73 | 07-AUG-06:03 | 242.76 | 242.76 | 28.88 | 0.30 |
September | 51512188.93 | 46360970.04 | 1328.61 | 30-SEP-06:03 | 1195.75 | 1195.75 | 40.31 | 3.85 |
October | 0.179279E+09 | 0.161351E+09 | 1377.05 | 16-OCT-06:02 | 1239.35 | 1239.35 | 40.94 | 4.22 |
November | 0.666589E+09 | 0.599930E+09 | 1524.73 | 28-NOV-07:01 | 1372.26 | 1372.26 | 48.37 | 4.89 |
December | 0.125919E+10 | 0.113327E+10 | 1601.02 | 11-DEC-08:07 | 1440.92 | 1440.92 | 46.82 | 5.12 |
Annual Sum or Average | 0.595075E+10 | 0.535568E+10 | ||||||
Minimum of Months | 861631.23 | 775468.11 | 180.99 | 162.89 | 162.89 | 26.13 | 0.19 | |
Maximum of Months | 0.170878E+10 | 0.153790E+10 | 1663.56 | 1497.20 | 1497.20 | 48.68 | 5.31 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.87 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.73 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.80 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 56.77 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.83 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.98 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:02 | 2.06 | 2.06 | 57.22 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.30 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 57.38 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.11 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.04 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 57.04 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.73 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.11 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 34.78 | 34.78 | 85420.30 | 376730.65 | 12-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 39.75 | 60.00 | 60679.42 | 395861.70 | 10-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 41.12 | 60.00 | 31748.62 | 416269.00 | 23-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.33 | 27.33 | 14441.19 | 408910.74 | 29-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.59 | 22.59 | 2251.68 | 347298.58 | 02-MAY-05:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.90 | 24.90 | 760.32 | 187326.09 | 05-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 33.55 | 33.55 | 43.70 | 27541.70 | 24-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.85 | 27.85 | 118.72 | 38797.82 | 07-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.55 | 24.55 | 2628.39 | 346224.16 | 29-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.38 | 22.38 | 9068.22 | 428672.10 | 24-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.15 | 27.15 | 33646.90 | 420332.10 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 32.07 | 32.07 | 62203.17 | 374604.04 | 14-DEC-06:01 |
Annual Sum or Average | 0.00 | 25095.38 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.38 | 22.38 | 43.70 | 27541.70 | ||
Maximum of Months | 0.00 | 0.00 | 41.12 | 60.00 | 85420.30 | 428672.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.87 | 57.87 | 1955.34 | 7209.48 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 57.23 | 57.23 | 2006.59 | 7256.37 | 21-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 57.22 | 57.22 | 2124.75 | 7245.55 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.29 | 57.29 | 1900.47 | 7041.28 | 03-APR-11:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.95 | 57.95 | 1858.67 | 6708.71 | 01-MAY-11:13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.60 | 57.60 | 1781.01 | 6265.19 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.75 | 57.75 | 1533.17 | 5851.63 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.85 | 57.85 | 1652.33 | 5617.77 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.87 | 57.87 | 1557.45 | 5750.26 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.90 | 56.90 | 1633.73 | 6122.63 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.66 | 57.66 | 1773.50 | 6552.15 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.49 | 57.49 | 1811.04 | 6933.65 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1797.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.90 | 56.90 | 1533.17 | 5617.77 | ||
Maximum of Months | 0.00 | 0.00 | 57.95 | 57.95 | 2124.75 | 7256.37 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.660956E+11 | 0.00 | 0.00 | 0.639645E+10 | 0.00 | 0.00 |
February | 0.433275E+11 | 0.00 | 0.00 | 0.484766E+10 | 0.00 | 0.00 |
March | 0.276378E+11 | 0.00 | 0.00 | 0.500285E+10 | 0.00 | 0.00 |
April | 0.139005E+11 | 0.00 | 0.00 | 0.610282E+10 | 0.00 | 0.00 |
May | 0.318268E+10 | 0.00 | 0.00 | 0.958103E+10 | 0.00 | 0.00 |
June | 0.911036E+09 | 0.00 | 0.00 | 0.186922E+11 | 0.00 | 0.00 |
July | 61996738.41 | 0.00 | 0.00 | 0.234114E+11 | 0.00 | 0.00 |
August | 0.143241E+09 | 0.00 | 0.00 | 0.242746E+11 | 0.00 | 0.00 |
September | 0.150867E+10 | 0.00 | 0.00 | 0.138751E+11 | 0.00 | 0.00 |
October | 0.533743E+10 | 0.00 | 0.00 | 0.524156E+10 | 0.00 | 0.00 |
November | 0.218567E+11 | 0.00 | 0.00 | 0.463078E+10 | 0.00 | 0.00 |
December | 0.444626E+11 | 0.00 | 0.00 | 0.504310E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.228426E+12 | 0.00 | 0.00 | 0.127099E+12 | 0.00 | 0.00 |
Minimum of Months | 61996738.41 | 0.00 | 0.00 | 0.463078E+10 | 0.00 | 0.00 |
Maximum of Months | 0.660956E+11 | 0.00 | 0.00 | 0.242746E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.679101E+11 | 0.00 | 0.00 | 0.527428E+10 | 0.00 | 0.00 |
February | 0.423131E+11 | 0.00 | 0.00 | 0.394079E+10 | 0.00 | 0.00 |
March | 0.229350E+11 | 0.00 | 0.00 | 0.393229E+10 | 0.00 | 0.00 |
April | 0.838935E+10 | 0.00 | 0.00 | 0.526896E+10 | 0.00 | 0.00 |
May | 0.491079E+09 | 0.00 | 0.00 | 0.835560E+10 | 0.00 | 0.00 |
June | 0.162474E+09 | 0.00 | 0.00 | 0.169028E+11 | 0.00 | 0.00 |
July | 167321.20 | 0.00 | 0.00 | 0.206069E+11 | 0.00 | 0.00 |
August | 257874.45 | 0.00 | 0.00 | 0.203691E+11 | 0.00 | 0.00 |
September | 0.114523E+10 | 0.00 | 0.00 | 0.109120E+11 | 0.00 | 0.00 |
October | 0.526970E+10 | 0.00 | 0.00 | 0.384157E+10 | 0.00 | 0.00 |
November | 0.247210E+11 | 0.00 | 0.00 | 0.362629E+10 | 0.00 | 0.00 |
December | 0.494177E+11 | 0.00 | 0.00 | 0.429867E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.222755E+12 | 0.00 | 0.00 | 0.107329E+12 | 0.00 | 0.00 |
Minimum of Months | 167321.20 | 0.00 | 0.00 | 0.362629E+10 | 0.00 | 0.00 |
Maximum of Months | 0.679101E+11 | 0.00 | 0.00 | 0.206069E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.965896E+11 | 0.00 | 0.00 | 0.660821E+10 | 0.00 | 0.00 |
February | 0.622962E+11 | 0.00 | 0.00 | 0.546202E+10 | 0.00 | 0.00 |
March | 0.351701E+11 | 0.00 | 0.00 | 0.502247E+10 | 0.00 | 0.00 |
April | 0.154517E+11 | 0.00 | 0.00 | 0.642047E+10 | 0.00 | 0.00 |
May | 0.240628E+10 | 0.00 | 0.00 | 0.987973E+10 | 0.00 | 0.00 |
June | 0.902201E+09 | 0.00 | 0.00 | 0.193614E+11 | 0.00 | 0.00 |
July | 63453820.92 | 0.00 | 0.00 | 0.234130E+11 | 0.00 | 0.00 |
August | 0.181458E+09 | 0.00 | 0.00 | 0.227120E+11 | 0.00 | 0.00 |
September | 0.421683E+10 | 0.00 | 0.00 | 0.120913E+11 | 0.00 | 0.00 |
October | 0.138670E+11 | 0.00 | 0.00 | 0.458701E+10 | 0.00 | 0.00 |
November | 0.413339E+11 | 0.00 | 0.00 | 0.506067E+10 | 0.00 | 0.00 |
December | 0.740460E+11 | 0.00 | 0.00 | 0.608345E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.346525E+12 | 0.00 | 0.00 | 0.126702E+12 | 0.00 | 0.00 |
Minimum of Months | 63453820.92 | 0.00 | 0.00 | 0.458701E+10 | 0.00 | 0.00 |
Maximum of Months | 0.965896E+11 | 0.00 | 0.00 | 0.234130E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.639645E+10 | 0.00 | 0.660956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.484760E+10 | 205757.40 | 0.433275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.492952E+10 | 0.268532E+09 | 0.276378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.461979E+10 | 0.600465E+10 | 0.139005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541482E+10 | 0.170258E+11 | 0.318268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.712122E+10 | 0.483997E+11 | 0.911036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.764495E+10 | 0.676457E+11 | 61996738.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.839659E+10 | 0.677312E+11 | 0.143241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.681721E+10 | 0.290506E+11 | 0.150867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.468473E+10 | 0.220162E+10 | 0.533743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460559E+10 | 91096940.66 | 0.218567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.504310E+10 | 0.00 | 0.444626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.705216E+11 | 0.238419E+12 | 0.228426E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.460559E+10 | 0.00 | 61996738.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.839659E+10 | 0.677312E+11 | 0.660956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.527420E+10 | 277462.15 | 0.679101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394077E+10 | 93301.63 | 0.423131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386552E+10 | 0.242525E+09 | 0.229350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363861E+10 | 0.650559E+10 | 0.838935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.418141E+10 | 0.167611E+11 | 0.491079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.565886E+10 | 0.461767E+11 | 0.162474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.591034E+10 | 0.620158E+11 | 167321.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.612050E+10 | 0.596617E+11 | 257874.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.472822E+10 | 0.249119E+11 | 0.114523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335250E+10 | 0.187590E+10 | 0.526970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360627E+10 | 71645119.92 | 0.247210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429865E+10 | 54527.91 | 0.494177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545758E+11 | 0.218223E+12 | 0.222755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.335250E+10 | 54527.91 | 167321.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.612050E+10 | 0.620158E+11 | 0.679101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.660741E+10 | 2815194.86 | 0.965896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.546097E+10 | 3670264.06 | 0.622962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.493802E+10 | 0.305411E+09 | 0.351701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.434143E+10 | 0.820231E+10 | 0.154517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.451016E+10 | 0.213559E+11 | 0.240628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553059E+10 | 0.558510E+11 | 0.902201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.559962E+10 | 0.737260E+11 | 63453820.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.566827E+10 | 0.699623E+11 | 0.181458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.465707E+10 | 0.293976E+11 | 0.421683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398242E+10 | 0.229435E+10 | 0.138670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.503813E+10 | 80084354.52 | 0.413339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608247E+10 | 3423798.72 | 0.740460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624166E+11 | 0.261185E+12 | 0.346525E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.398242E+10 | 2815194.86 | 63453820.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.660741E+10 | 0.737260E+11 | 0.965896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.639645E+10 | 0.660956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.484760E+10 | 0.433275E+11 | 0.00 | 0.00 | 58329.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.492952E+10 | 0.276378E+11 | 0.00 | 0.00 | 73326470.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.461979E+10 | 0.139005E+11 | 0.00 | 0.00 | 0.148303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541482E+10 | 0.318268E+10 | 0.00 | 0.00 | 0.416621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.712122E+10 | 0.911036E+09 | 0.00 | 0.00 | 0.115710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.764495E+10 | 61996738.41 | 0.00 | 0.00 | 0.157664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.839659E+10 | 0.143241E+09 | 0.00 | 0.00 | 0.158780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.681721E+10 | 0.150867E+10 | 0.00 | 0.00 | 0.705789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.468473E+10 | 0.533743E+10 | 0.00 | 0.00 | 0.556831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460559E+10 | 0.218567E+11 | 0.00 | 0.00 | 25183874.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.504310E+10 | 0.444626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.705216E+11 | 0.228426E+12 | 0.00 | 0.00 | 0.565779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.460559E+10 | 61996738.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.839659E+10 | 0.660956E+11 | 0.00 | 0.00 | 0.158780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.527420E+10 | 0.679101E+11 | 0.00 | 0.00 | 79652.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394077E+10 | 0.423131E+11 | 0.00 | 0.00 | 26749.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386552E+10 | 0.229350E+11 | 0.00 | 0.00 | 66775212.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363861E+10 | 0.838935E+10 | 0.00 | 0.00 | 0.163036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.418141E+10 | 0.491079E+09 | 0.00 | 0.00 | 0.417418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.565886E+10 | 0.162474E+09 | 0.00 | 0.00 | 0.112440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.591034E+10 | 167321.20 | 0.00 | 0.00 | 0.146966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.612050E+10 | 257874.45 | 0.00 | 0.00 | 0.142486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.472822E+10 | 0.114523E+10 | 0.00 | 0.00 | 0.618374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335250E+10 | 0.526970E+10 | 0.00 | 0.00 | 0.489071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360627E+10 | 0.247210E+11 | 0.00 | 0.00 | 20021917.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429865E+10 | 0.494177E+11 | 0.00 | 0.00 | 15622.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545758E+11 | 0.222755E+12 | 0.00 | 0.00 | 0.527534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.335250E+10 | 167321.20 | 0.00 | 0.00 | 15622.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.612050E+10 | 0.679101E+11 | 0.00 | 0.00 | 0.146966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.660741E+10 | 0.965896E+11 | 0.00 | 0.00 | 806977.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.546097E+10 | 0.622962E+11 | 0.00 | 0.00 | 1051896.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.493802E+10 | 0.351701E+11 | 0.00 | 0.00 | 84448215.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.434143E+10 | 0.154517E+11 | 0.00 | 0.00 | 0.207905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.451016E+10 | 0.240628E+10 | 0.00 | 0.00 | 0.536957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.553059E+10 | 0.902201E+09 | 0.00 | 0.00 | 0.138308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.559962E+10 | 63453820.92 | 0.00 | 0.00 | 0.178133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.566827E+10 | 0.181458E+09 | 0.00 | 0.00 | 0.170438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.465707E+10 | 0.421683E+10 | 0.00 | 0.00 | 0.743425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398242E+10 | 0.138670E+11 | 0.00 | 0.00 | 0.604593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.503813E+10 | 0.413339E+11 | 0.00 | 0.00 | 22538219.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608247E+10 | 0.740460E+11 | 0.00 | 0.00 | 980133.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624166E+11 | 0.346525E+12 | 0.00 | 0.00 | 0.642852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.398242E+10 | 63453820.92 | 0.00 | 0.00 | 806977.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.660741E+10 | 0.965896E+11 | 0.00 | 0.00 | 0.178133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194586E+11 | 0.00 | 0.00 | 342226.18 | 0.00 | 0.632634E+09 | 0.397112E+09 | 0.00 | 0.26 |
February | 0.143329E+11 | 0.00 | 0.00 | 1152578.77 | 0.00 | 71680534.41 | 0.164496E+10 | 0.00 | 0.26 |
March | 0.988386E+10 | 0.00 | 0.00 | 10899143.27 | 0.00 | 4970174.57 | 0.681025E+10 | 0.00 | 0.36 |
April | 0.495608E+10 | 0.193762E+09 | 0.00 | 20234315.58 | 21154038.53 | 0.00 | 0.102061E+11 | 0.00 | 0.48 |
May | 0.132654E+10 | 0.218175E+09 | 0.00 | 34134475.43 | 1859619.12 | 0.00 | 0.140611E+11 | 0.00 | 0.83 |
June | 0.462982E+09 | 0.196327E+10 | 0.00 | 29517774.98 | 40465470.30 | 0.00 | 0.917879E+10 | 0.00 | 0.76 |
July | 0.270130E+09 | 0.352622E+10 | 0.00 | 19975413.42 | 32648835.36 | 0.00 | 0.340481E+10 | 0.00 | 0.61 |
August | 0.389178E+09 | 0.341574E+10 | 0.00 | 28148812.65 | 42570765.00 | 0.00 | 0.552206E+10 | 0.00 | 0.71 |
September | 0.907452E+09 | 0.354186E+09 | 0.00 | 39086785.21 | 11526335.22 | 0.00 | 0.145495E+11 | 0.00 | 0.76 |
October | 0.182299E+10 | 0.00 | 0.00 | 33771963.14 | 236672.38 | 0.00 | 0.162762E+11 | 0.00 | 0.57 |
November | 0.745215E+10 | 0.00 | 0.00 | 16170122.38 | 0.00 | 16909129.82 | 0.938611E+10 | 0.00 | 0.41 |
December | 0.143456E+11 | 0.00 | 0.00 | 1969392.92 | 0.00 | 69877823.56 | 0.267780E+10 | 0.00 | 0.25 |
Annual Sum or Average | 0.756084E+11 | 0.967136E+10 | 0.00 | 0.235403E+09 | 0.150462E+09 | 0.796072E+09 | 0.941148E+11 | 0.00 | 0.52 |
Minimum of Months | 0.270130E+09 | 0.00 | 0.00 | 342226.18 | 0.00 | 0.00 | 0.397112E+09 | 0.00 | 0.25 |
Maximum of Months | 0.194586E+11 | 0.352622E+10 | 0.00 | 39086785.21 | 42570765.00 | 0.632634E+09 | 0.162762E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419714E+10 | 0.00 | 0.00 | 0.23 |
February | 0.127211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157842E+10 | 0.00 | 0.00 | 0.23 |
March | 0.126763E+11 | 0.00 | 0.00 | 433904.05 | 0.00 | 0.289172E+09 | 0.615058E+09 | 0.00 | 0.29 |
April | 0.780520E+10 | 87813448.78 | 0.00 | 4851392.65 | 96287526.49 | 75517737.37 | 0.313447E+10 | 0.00 | 0.35 |
May | 0.467085E+10 | 0.177004E+09 | 0.00 | 13353188.38 | 30823121.75 | 0.00 | 0.573298E+10 | 0.00 | 0.58 |
June | 0.163098E+10 | 0.157061E+10 | 0.00 | 15520680.15 | 0.115843E+09 | 0.00 | 0.464577E+10 | 0.00 | 0.53 |
July | 0.639917E+09 | 0.289197E+10 | 0.00 | 9815061.23 | 70382884.33 | 0.00 | 0.159660E+10 | 0.00 | 0.43 |
August | 0.804604E+09 | 0.271199E+10 | 0.00 | 15328918.26 | 0.228867E+09 | 0.00 | 0.268377E+10 | 0.00 | 0.49 |
September | 0.325719E+10 | 0.272678E+09 | 0.00 | 15282167.25 | 73841133.77 | 0.00 | 0.579373E+10 | 0.00 | 0.49 |
October | 0.824335E+10 | 0.00 | 0.00 | 3296646.31 | 4657817.45 | 4093043.14 | 0.273287E+10 | 0.00 | 0.36 |
November | 0.103409E+11 | 0.00 | 0.00 | 1213467.92 | 0.00 | 0.889318E+09 | 0.127650E+10 | 0.00 | 0.30 |
December | 0.133581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204232E+10 | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.904103E+11 | 0.771207E+10 | 0.00 | 79095426.21 | 0.620703E+09 | 0.907599E+10 | 0.282117E+11 | 0.00 | 0.38 |
Minimum of Months | 0.639917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.142618E+11 | 0.289197E+10 | 0.00 | 15520680.15 | 0.228867E+09 | 0.419714E+10 | 0.579373E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.664983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927315E+10 | 0.00 | 0.00 | 0.21 |
February | 0.730484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555511E+10 | 0.00 | 0.00 | 0.22 |
March | 0.112890E+11 | 0.00 | 0.00 | 19684.23 | 0.00 | 0.200336E+10 | 82967139.66 | 0.00 | 0.31 |
April | 0.974489E+10 | 83949034.83 | 0.00 | 2208392.55 | 0.119064E+09 | 0.521815E+09 | 0.154184E+10 | 0.00 | 0.40 |
May | 0.809083E+10 | 0.161310E+09 | 0.00 | 5411534.46 | 45837231.08 | 15977136.54 | 0.336487E+10 | 0.00 | 0.67 |
June | 0.320030E+10 | 0.155256E+10 | 0.00 | 11197219.31 | 0.317716E+09 | 4059539.27 | 0.310549E+10 | 0.00 | 0.57 |
July | 0.103603E+10 | 0.281762E+10 | 0.00 | 6509633.36 | 0.480553E+09 | 0.00 | 0.804233E+09 | 0.00 | 0.45 |
August | 0.160087E+10 | 0.251225E+10 | 0.00 | 10289415.64 | 0.780585E+09 | 0.00 | 0.124412E+10 | 0.00 | 0.51 |
September | 0.647007E+10 | 0.312885E+09 | 0.00 | 6060097.98 | 0.135778E+09 | 53590227.35 | 0.206271E+10 | 0.00 | 0.52 |
October | 0.114860E+11 | 0.00 | 0.00 | 101980.66 | 6418757.23 | 0.393783E+09 | 92870112.25 | 0.00 | 0.43 |
November | 0.901345E+10 | 0.00 | 0.00 | 26309.80 | 3008.09 | 0.299759E+10 | 89345299.43 | 32181.03 | 0.32 |
December | 0.668837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667004E+10 | 0.00 | 0.00 | 0.21 |
Annual Sum or Average | 0.825745E+11 | 0.744057E+10 | 0.00 | 41824267.98 | 0.188596E+10 | 0.274885E+11 | 0.123884E+11 | 32181.03 | 0.40 |
Minimum of Months | 0.103603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
Maximum of Months | 0.114860E+11 | 0.281762E+10 | 0.00 | 11197219.31 | 0.780585E+09 | 0.927315E+10 | 0.336487E+10 | 32181.03 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793394E+10 | 0.00 | 0.00 | 0.49 |
February | 0.457330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623455E+10 | 0.00 | 0.00 | 0.53 |
March | 0.241481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419947E+10 | 0.00 | 0.00 | 0.72 |
April | 0.382963E+10 | 23683962.56 | 303911.35 | 36431.01 | 67223180.38 | 0.184024E+10 | 75725733.35 | 2669.57 | 0.92 |
May | 0.530654E+10 | 48633946.19 | 0.00 | 152080.35 | 36888249.22 | 0.161132E+09 | 0.157236E+09 | 0.00 | 1.52 |
June | 0.220747E+10 | 0.462212E+09 | 0.00 | 1317177.00 | 0.288999E+09 | 46233212.04 | 0.566007E+09 | 0.00 | 1.19 |
July | 0.764992E+09 | 0.729121E+09 | 0.00 | 814427.60 | 0.621794E+09 | 1314516.18 | 88635875.23 | 0.00 | 0.95 |
August | 0.114353E+10 | 0.645691E+09 | 0.00 | 1312063.72 | 0.728371E+09 | 6982381.66 | 0.166116E+09 | 0.00 | 1.08 |
September | 0.361785E+10 | 74666724.68 | 0.00 | 347075.56 | 0.116511E+09 | 0.436559E+09 | 0.104503E+09 | 0.00 | 1.16 |
October | 0.407712E+10 | 0.00 | 0.00 | 0.00 | 3174111.66 | 0.184337E+10 | 0.00 | 0.00 | 1.00 |
November | 0.200823E+10 | 0.00 | 1016.04 | 0.00 | 0.00 | 0.398613E+10 | 0.00 | 16385.18 | 0.76 |
December | 64820596.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661835E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.261061E+11 | 0.198401E+10 | 304927.39 | 3979255.25 | 0.186296E+10 | 0.333083E+11 | 0.115822E+10 | 19054.74 | 0.90 |
Minimum of Months | 64820596.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1314516.18 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.530654E+10 | 0.729121E+09 | 303911.35 | 1317177.00 | 0.728371E+09 | 0.793394E+10 | 0.566007E+09 | 16385.18 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.222573E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496221E+10 | 0.00 | 0.00 | 0.50 |
February | 0.526011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368338E+10 | 0.00 | 0.00 | 0.53 |
March | 0.217907E+10 | 0.00 | 0.00 | 2012.37 | 0.00 | 0.207392E+10 | 12278038.45 | 0.00 | 0.73 |
April | 0.238270E+10 | 51831501.53 | 0.00 | 450196.18 | 17209721.06 | 0.100707E+10 | 0.353898E+09 | 0.00 | 0.95 |
May | 0.274933E+10 | 48718035.77 | 0.00 | 1330785.70 | 18568383.89 | 42992419.79 | 0.875328E+09 | 0.00 | 1.59 |
June | 0.110357E+10 | 0.458428E+09 | 0.00 | 3062931.07 | 0.113883E+09 | 22970230.51 | 0.868640E+09 | 0.00 | 1.36 |
July | 0.336357E+09 | 0.679536E+09 | 0.00 | 1965614.52 | 0.306506E+09 | 0.00 | 0.274650E+09 | 0.00 | 1.10 |
August | 0.552450E+09 | 0.628701E+09 | 0.00 | 2615407.79 | 0.366585E+09 | 1974226.87 | 0.362538E+09 | 0.00 | 1.20 |
September | 0.212492E+10 | 0.103905E+09 | 0.00 | 1096574.57 | 39769647.74 | 0.185369E+09 | 0.383840E+09 | 0.00 | 1.22 |
October | 0.296476E+10 | 0.00 | 0.00 | 12755.60 | 2047141.47 | 0.829431E+09 | 24068769.78 | 0.00 | 1.02 |
November | 0.140492E+10 | 0.00 | 579.88 | 0.00 | 0.00 | 0.245658E+10 | 0.00 | 10643.03 | 0.77 |
December | 0.184632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411754E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.167313E+11 | 0.197112E+10 | 579.88 | 10536277.79 | 0.864570E+09 | 0.193834E+11 | 0.315524E+10 | 10643.03 | 0.96 |
Minimum of Months | 0.184632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.296476E+10 | 0.679536E+09 | 579.88 | 3062931.07 | 0.366585E+09 | 0.496221E+10 | 0.875328E+09 | 10643.03 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197916E+10 | 0.00 | 0.00 | 25226.09 | 0.00 | 0.582498E+10 | 63333435.82 | 0.00 | 0.48 |
February | 0.208616E+10 | 0.00 | 0.00 | 507244.17 | 0.00 | 0.399933E+10 | 0.274427E+09 | 0.00 | 0.52 |
March | 0.303854E+10 | 0.00 | 0.00 | 904423.75 | 0.00 | 0.282853E+10 | 0.679970E+09 | 0.00 | 0.72 |
April | 0.319100E+10 | 85681228.12 | 300548.02 | 1966232.94 | 28936901.02 | 0.142346E+10 | 0.119621E+10 | 1429.32 | 0.94 |
May | 0.443422E+10 | 60114125.65 | 0.00 | 1565469.78 | 34828760.41 | 0.155097E+09 | 0.972993E+09 | 0.00 | 1.52 |
June | 0.204465E+10 | 0.575621E+09 | 0.00 | 2942655.22 | 0.230462E+09 | 45181094.62 | 0.760542E+09 | 0.00 | 1.21 |
July | 0.680024E+09 | 0.894073E+09 | 0.00 | 1654246.32 | 0.556129E+09 | 3293132.44 | 0.167080E+09 | 0.00 | 0.97 |
August | 0.986493E+09 | 0.892676E+09 | 0.00 | 3885770.21 | 0.621078E+09 | 6877535.15 | 0.372911E+09 | 0.00 | 1.13 |
September | 0.301099E+10 | 0.185909E+09 | 0.00 | 3075511.97 | 58617684.85 | 0.302878E+09 | 0.881590E+09 | 0.00 | 1.21 |
October | 0.371010E+10 | 0.00 | 0.00 | 2947614.08 | 3126449.62 | 0.962018E+09 | 0.128699E+10 | 0.00 | 1.01 |
November | 0.273066E+10 | 0.00 | 991.56 | 734266.06 | 0.00 | 0.292982E+10 | 0.309737E+09 | 16148.37 | 0.76 |
December | 0.135989E+10 | 0.00 | 0.00 | 116672.23 | 0.00 | 0.500792E+10 | 0.188433E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.292519E+11 | 0.269407E+10 | 301539.58 | 20325332.83 | 0.153318E+10 | 0.234894E+11 | 0.715421E+10 | 17577.69 | 0.92 |
Minimum of Months | 0.680024E+09 | 0.00 | 0.00 | 25226.09 | 0.00 | 3293132.44 | 63333435.82 | 0.00 | 0.48 |
Maximum of Months | 0.443422E+10 | 0.894073E+09 | 300548.02 | 3885770.21 | 0.621078E+09 | 0.582498E+10 | 0.128699E+10 | 16148.37 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.318992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499887E+10 | 0.00 | 0.00 | 0.51 |
February | 0.604998E+09 | 0.00 | 0.00 | 10430.28 | 0.00 | 0.369664E+10 | 22550614.11 | 0.00 | 0.55 |
March | 0.184962E+10 | 0.00 | 0.00 | 37954.94 | 0.00 | 0.238064E+10 | 99852198.74 | 0.00 | 0.75 |
April | 0.223256E+10 | 32829154.84 | 199674.58 | 1008950.23 | 32930136.25 | 0.989085E+09 | 0.627775E+09 | 1044.47 | 0.99 |
May | 0.304202E+10 | 48281471.57 | 0.00 | 1243194.67 | 19049447.01 | 0.108221E+09 | 0.603770E+09 | 0.00 | 1.62 |
June | 0.137149E+10 | 0.420609E+09 | 0.00 | 2500663.30 | 0.152605E+09 | 34614432.17 | 0.586109E+09 | 0.00 | 1.37 |
July | 0.460930E+09 | 0.724440E+09 | 0.00 | 1344687.41 | 0.311503E+09 | 2188887.42 | 0.124865E+09 | 0.00 | 1.07 |
August | 0.698430E+09 | 0.615044E+09 | 0.00 | 2552203.19 | 0.392797E+09 | 4571377.09 | 0.213228E+09 | 0.00 | 1.21 |
September | 0.218149E+10 | 93379630.82 | 0.00 | 1307502.96 | 50956330.68 | 0.276671E+09 | 0.307914E+09 | 0.00 | 1.24 |
October | 0.267879E+10 | 0.00 | 0.00 | 275368.42 | 2078096.27 | 0.964701E+09 | 0.239775E+09 | 0.00 | 1.04 |
November | 0.147790E+10 | 0.00 | 631.59 | 24882.33 | 0.00 | 0.241853E+10 | 28909505.05 | 10761.02 | 0.79 |
December | 0.384665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399305E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.173019E+11 | 0.193458E+10 | 200306.17 | 10305837.74 | 0.961919E+09 | 0.198678E+11 | 0.285475E+10 | 11805.48 | 0.97 |
Minimum of Months | 0.318992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2188887.42 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.304202E+10 | 0.724440E+09 | 199674.58 | 2552203.19 | 0.392797E+09 | 0.499887E+10 | 0.627775E+09 | 10761.02 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867151E+10 | 0.00 | 0.00 | 0.52 |
February | 0.180691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693275E+10 | 0.00 | 0.00 | 0.53 |
March | 0.130200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526291E+10 | 0.00 | 0.00 | 0.65 |
April | 0.249602E+10 | 3316651.03 | 79560.94 | 0.00 | 62202615.91 | 0.284171E+10 | 0.00 | 4228.51 | 0.77 |
May | 0.448457E+10 | 15882542.44 | 0.00 | 0.00 | 34311601.75 | 0.230420E+09 | 0.00 | 0.00 | 1.16 |
June | 0.240070E+10 | 0.288131E+09 | 0.00 | 196093.38 | 0.172886E+09 | 11716449.13 | 0.151455E+09 | 0.00 | 0.92 |
July | 0.889612E+09 | 0.495420E+09 | 0.00 | 368617.07 | 0.298414E+09 | 0.00 | 72520241.17 | 0.00 | 0.71 |
August | 0.130625E+10 | 0.525297E+09 | 0.00 | 925875.06 | 0.274894E+09 | 0.00 | 0.198076E+09 | 0.00 | 0.81 |
September | 0.383849E+10 | 59516106.32 | 0.00 | 403320.03 | 23442524.22 | 93173757.32 | 0.283799E+09 | 0.00 | 0.94 |
October | 0.516826E+10 | 0.00 | 0.00 | 0.00 | 95862.72 | 0.761907E+09 | 0.00 | 0.00 | 0.86 |
November | 0.275314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343709E+10 | 0.00 | 0.00 | 0.68 |
December | 0.110969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695367E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.251248E+11 | 0.138756E+10 | 79560.94 | 1893905.53 | 0.866247E+09 | 0.351969E+11 | 0.705850E+09 | 4228.51 | 0.75 |
Minimum of Months | 0.110969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.516826E+10 | 0.525297E+09 | 79560.94 | 925875.06 | 0.298414E+09 | 0.867151E+10 | 0.283799E+09 | 4228.51 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537621E+10 | 0.00 | 0.00 | 0.52 |
February | 0.376481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402273E+10 | 0.00 | 0.00 | 0.52 |
March | 0.162054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261270E+10 | 0.00 | 0.00 | 0.66 |
April | 0.200193E+10 | 17179899.25 | 0.00 | 140330.64 | 28088859.49 | 0.135379E+10 | 97751924.14 | 0.00 | 0.79 |
May | 0.268287E+10 | 30714875.65 | 0.00 | 465863.29 | 7882596.53 | 47450732.06 | 0.315884E+09 | 0.00 | 1.19 |
June | 0.111034E+10 | 0.326184E+09 | 0.00 | 2249160.49 | 52071945.36 | 4842595.55 | 0.662401E+09 | 0.00 | 1.04 |
July | 0.369870E+09 | 0.545442E+09 | 0.00 | 2014141.98 | 74948328.83 | 0.00 | 0.322984E+09 | 0.00 | 0.85 |
August | 0.570736E+09 | 0.528315E+09 | 0.00 | 2972925.95 | 0.110540E+09 | 0.00 | 0.517015E+09 | 0.00 | 0.95 |
September | 0.204388E+10 | 68629681.72 | 0.00 | 2294478.62 | 3014993.03 | 18381525.95 | 0.720486E+09 | 0.00 | 1.02 |
October | 0.355485E+10 | 0.00 | 0.00 | 31826.62 | 61907.41 | 0.235657E+09 | 38221658.05 | 0.00 | 0.88 |
November | 0.184472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215124E+10 | 0.00 | 0.00 | 0.70 |
December | 0.274848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427440E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.166906E+11 | 0.151646E+10 | 0.00 | 10168727.59 | 0.276608E+09 | 0.200974E+11 | 0.267474E+10 | 0.00 | 0.80 |
Minimum of Months | 0.239565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.355485E+10 | 0.545442E+09 | 0.00 | 2972925.95 | 0.110540E+09 | 0.537621E+10 | 0.720486E+09 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.470951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972134E+10 | 0.00 | 0.00 | 0.59 |
February | 0.709327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696958E+10 | 0.00 | 0.00 | 0.57 |
March | 0.158886E+10 | 0.00 | 0.00 | 10914.95 | 0.00 | 0.547435E+10 | 40359291.93 | 0.00 | 0.69 |
April | 0.198598E+10 | 60279534.82 | 205327.00 | 204131.75 | 15134790.78 | 0.353315E+10 | 0.125608E+09 | 2212.81 | 0.81 |
May | 0.380236E+10 | 45013801.22 | 0.00 | 155025.26 | 14925475.62 | 0.849186E+09 | 60039909.99 | 0.00 | 1.15 |
June | 0.198083E+10 | 0.456273E+09 | 0.00 | 1073795.98 | 0.109513E+09 | 0.337132E+09 | 0.225472E+09 | 0.00 | 0.93 |
July | 0.799783E+09 | 0.757233E+09 | 0.00 | 1111156.88 | 0.196356E+09 | 42736421.55 | 0.106176E+09 | 0.00 | 0.73 |
August | 0.982591E+09 | 0.873269E+09 | 0.00 | 3272737.58 | 0.173932E+09 | 0.120863E+09 | 0.428558E+09 | 0.00 | 0.87 |
September | 0.300409E+10 | 0.156447E+09 | 0.00 | 3286179.72 | 5373935.13 | 0.503418E+09 | 0.761801E+09 | 0.00 | 1.00 |
October | 0.416241E+10 | 42079.10 | 0.00 | 1438257.51 | 57960.96 | 0.123119E+10 | 0.698630E+09 | 0.00 | 0.89 |
November | 0.227569E+10 | 0.00 | 0.00 | 482320.74 | 0.00 | 0.416061E+10 | 0.223505E+09 | 0.00 | 0.73 |
December | 0.940958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710075E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.227038E+11 | 0.234856E+10 | 205327.00 | 11034520.37 | 0.515294E+09 | 0.400443E+11 | 0.267015E+10 | 2212.81 | 0.79 |
Minimum of Months | 0.470951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42736421.55 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.416241E+10 | 0.873269E+09 | 205327.00 | 3286179.72 | 0.196356E+09 | 0.972134E+10 | 0.761801E+09 | 2212.81 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557810E+10 | 0.00 | 0.00 | 0.54 |
February | 0.424268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412826E+10 | 0.00 | 0.00 | 0.54 |
March | 0.141268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290304E+10 | 0.00 | 0.00 | 0.68 |
April | 0.211390E+10 | 17791869.13 | 0.00 | 226017.94 | 27018435.22 | 0.124550E+10 | 0.164387E+09 | 0.00 | 0.81 |
May | 0.282421E+10 | 29111517.25 | 0.00 | 374080.08 | 10624471.85 | 0.112815E+09 | 0.169910E+09 | 0.00 | 1.21 |
June | 0.136925E+10 | 0.311159E+09 | 0.00 | 1627357.97 | 68780668.67 | 9300000.16 | 0.386017E+09 | 0.00 | 1.04 |
July | 0.459738E+09 | 0.613051E+09 | 0.00 | 1239112.64 | 68429635.13 | 0.00 | 0.193352E+09 | 0.00 | 0.81 |
August | 0.587378E+09 | 0.547916E+09 | 0.00 | 2628437.71 | 95614136.16 | 0.00 | 0.458667E+09 | 0.00 | 0.93 |
September | 0.227653E+10 | 73956728.15 | 0.00 | 1548976.26 | 5591633.82 | 61423962.09 | 0.474298E+09 | 0.00 | 1.02 |
October | 0.342173E+10 | 0.00 | 0.00 | 249217.31 | 63091.95 | 0.253389E+09 | 0.234256E+09 | 0.00 | 0.90 |
November | 0.189888E+10 | 0.00 | 0.00 | 21123.33 | 0.00 | 0.214671E+10 | 28455494.39 | 0.00 | 0.71 |
December | 0.406052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423704E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.173989E+11 | 0.159299E+10 | 0.00 | 7914323.25 | 0.276122E+09 | 0.206756E+11 | 0.210934E+10 | 0.00 | 0.81 |
Minimum of Months | 0.204280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.342173E+10 | 0.613051E+09 | 0.00 | 2628437.71 | 95614136.16 | 0.557810E+10 | 0.474298E+09 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.284960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947933E+10 | 0.00 | 0.00 | 0.57 |
February | 0.727037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700380E+10 | 0.00 | 0.00 | 0.58 |
March | 0.278802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411188E+10 | 0.00 | 0.00 | 0.69 |
April | 0.387841E+10 | 27295511.13 | 0.00 | 56277.37 | 50843549.20 | 0.139734E+10 | 81543989.19 | 0.00 | 0.79 |
May | 0.446272E+10 | 57876094.08 | 0.00 | 344612.15 | 19938329.07 | 41211922.62 | 0.340520E+09 | 0.00 | 1.24 |
June | 0.178711E+10 | 0.523720E+09 | 0.00 | 2009340.68 | 0.117844E+09 | 5306842.14 | 0.735861E+09 | 0.00 | 0.99 |
July | 0.656787E+09 | 0.889959E+09 | 0.00 | 1272238.90 | 0.203641E+09 | 0.00 | 0.255607E+09 | 0.00 | 0.79 |
August | 0.110355E+10 | 0.791721E+09 | 0.00 | 1920844.85 | 0.312394E+09 | 0.00 | 0.304000E+09 | 0.00 | 0.89 |
September | 0.350861E+10 | 78565240.05 | 0.00 | 742592.09 | 52363758.12 | 0.138445E+09 | 0.357266E+09 | 0.00 | 0.97 |
October | 0.464928E+10 | 0.00 | 0.00 | 0.00 | 2360351.01 | 0.898728E+09 | 0.00 | 0.00 | 0.85 |
November | 0.254909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380552E+10 | 0.00 | 0.00 | 0.71 |
December | 0.179498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773562E+10 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.265751E+11 | 0.236914E+10 | 0.00 | 6345906.05 | 0.759385E+09 | 0.346172E+11 | 0.207480E+10 | 0.00 | 0.80 |
Minimum of Months | 0.179498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.464928E+10 | 0.889959E+09 | 0.00 | 2009340.68 | 0.312394E+09 | 0.947933E+10 | 0.735861E+09 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.235786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537595E+10 | 0.00 | 0.00 | 0.52 |
February | 0.645913E+09 | 0.00 | 0.00 | 4265.66 | 0.00 | 0.364570E+10 | 809052.74 | 0.00 | 0.51 |
March | 0.178713E+10 | 0.00 | 0.00 | 143579.91 | 0.00 | 0.197813E+10 | 86757303.70 | 0.00 | 0.60 |
April | 0.194512E+10 | 50912711.78 | 0.00 | 815034.66 | 4928308.61 | 0.686411E+09 | 0.483323E+09 | 0.00 | 0.75 |
May | 0.190300E+10 | 50561990.44 | 0.00 | 2414427.17 | 11019021.51 | 7593076.87 | 0.114886E+10 | 0.00 | 1.27 |
June | 0.866590E+09 | 0.455546E+09 | 0.00 | 3435429.71 | 41985287.10 | 4104713.42 | 0.976937E+09 | 0.00 | 1.20 |
July | 0.288138E+09 | 0.715123E+09 | 0.00 | 2523306.08 | 0.108843E+09 | 0.00 | 0.428464E+09 | 0.00 | 1.01 |
August | 0.574185E+09 | 0.673387E+09 | 0.00 | 3145470.18 | 0.130696E+09 | 0.00 | 0.521557E+09 | 0.00 | 1.08 |
September | 0.169089E+10 | 85868282.92 | 0.00 | 2396378.52 | 11578305.89 | 50792365.16 | 0.740374E+09 | 0.00 | 1.01 |
October | 0.256914E+10 | 0.00 | 0.00 | 196371.43 | 1538454.95 | 0.443606E+09 | 75531049.20 | 0.00 | 0.73 |
November | 0.134485E+10 | 0.00 | 0.00 | 16777.01 | 0.00 | 0.220060E+10 | 4715128.77 | 0.00 | 0.62 |
December | 0.345039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420464E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.141958E+11 | 0.203140E+10 | 0.00 | 15091040.33 | 0.310589E+09 | 0.185975E+11 | 0.446733E+10 | 0.00 | 0.82 |
Minimum of Months | 0.235786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.256914E+10 | 0.715123E+09 | 0.00 | 3435429.71 | 0.130696E+09 | 0.537595E+10 | 0.114886E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252124E+10 | 0.00 | 0.00 | 218658.27 | 0.00 | 0.663768E+10 | 0.187653E+09 | 0.00 | 0.55 |
February | 0.264564E+10 | 0.00 | 0.00 | 737087.42 | 0.00 | 0.428249E+10 | 0.385021E+09 | 0.00 | 0.56 |
March | 0.323569E+10 | 0.00 | 0.00 | 1717743.20 | 0.00 | 0.277423E+10 | 0.895334E+09 | 0.00 | 0.70 |
April | 0.323842E+10 | 0.107953E+09 | 0.00 | 2720131.84 | 11792882.90 | 0.102708E+10 | 0.125358E+10 | 0.00 | 0.85 |
May | 0.355534E+10 | 79059375.90 | 0.00 | 2271048.43 | 18977080.29 | 38787479.89 | 0.123023E+10 | 0.00 | 1.26 |
June | 0.172327E+10 | 0.658622E+09 | 0.00 | 3289578.23 | 72393865.39 | 5206232.31 | 0.873703E+09 | 0.00 | 1.04 |
July | 0.602867E+09 | 0.107027E+10 | 0.00 | 2072798.73 | 0.177718E+09 | 0.00 | 0.307167E+09 | 0.00 | 0.83 |
August | 0.989681E+09 | 0.109543E+10 | 0.00 | 4258739.10 | 0.210036E+09 | 0.00 | 0.510766E+09 | 0.00 | 0.99 |
September | 0.277152E+10 | 0.193433E+09 | 0.00 | 4550272.03 | 15869152.37 | 86593112.99 | 0.130371E+10 | 0.00 | 1.08 |
October | 0.373453E+10 | 180464.83 | 0.00 | 4707204.51 | 2169179.35 | 0.400159E+09 | 0.176335E+10 | 0.00 | 0.93 |
November | 0.322214E+10 | 0.00 | 0.00 | 1034570.90 | 0.00 | 0.268942E+10 | 0.477456E+09 | 0.00 | 0.73 |
December | 0.152088E+10 | 0.00 | 0.00 | 708547.00 | 0.00 | 0.568195E+10 | 0.558627E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.297612E+11 | 0.320495E+10 | 0.00 | 28286379.65 | 0.508956E+09 | 0.236236E+11 | 0.974660E+10 | 0.00 | 0.84 |
Minimum of Months | 0.602867E+09 | 0.00 | 0.00 | 218658.27 | 0.00 | 0.00 | 0.187653E+09 | 0.00 | 0.54 |
Maximum of Months | 0.373453E+10 | 0.109543E+10 | 0.00 | 4707204.51 | 0.210036E+09 | 0.663768E+10 | 0.176335E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.547858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628531E+10 | 0.00 | 0.00 | 0.63 |
February | 0.101959E+10 | 0.00 | 0.00 | 20115.98 | 0.00 | 0.430670E+10 | 28739297.64 | 0.00 | 0.64 |
March | 0.218001E+10 | 0.00 | 0.00 | 113711.29 | 0.00 | 0.253365E+10 | 0.167890E+09 | 0.00 | 0.77 |
April | 0.247203E+10 | 41061095.45 | 0.00 | 1120914.05 | 23434538.52 | 0.801779E+09 | 0.637845E+09 | 0.00 | 0.94 |
May | 0.280274E+10 | 62359340.63 | 0.00 | 1396904.04 | 10823453.00 | 34830987.18 | 0.683616E+09 | 0.00 | 1.45 |
June | 0.126468E+10 | 0.481474E+09 | 0.00 | 2700549.39 | 67680947.77 | 4259948.38 | 0.676017E+09 | 0.00 | 1.27 |
July | 0.448238E+09 | 0.850857E+09 | 0.00 | 1544550.25 | 0.111186E+09 | 0.00 | 0.234796E+09 | 0.00 | 0.99 |
August | 0.709634E+09 | 0.735436E+09 | 0.00 | 2767084.92 | 0.170878E+09 | 0.00 | 0.359413E+09 | 0.00 | 1.11 |
September | 0.236429E+10 | 0.102518E+09 | 0.00 | 1508679.62 | 17780382.05 | 99201294.07 | 0.434139E+09 | 0.00 | 1.14 |
October | 0.310632E+10 | 0.00 | 0.00 | 510442.79 | 1670972.36 | 0.504675E+09 | 0.333266E+09 | 0.00 | 0.96 |
November | 0.190431E+10 | 0.00 | 0.00 | 55039.28 | 0.00 | 0.253890E+10 | 53883589.94 | 0.00 | 0.79 |
December | 0.604028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498302E+10 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.194237E+11 | 0.227370E+10 | 0.00 | 11737991.61 | 0.403454E+09 | 0.220923E+11 | 0.360961E+10 | 0.00 | 0.94 |
Minimum of Months | 0.448238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.310632E+10 | 0.850857E+09 | 0.00 | 2767084.92 | 0.170878E+09 | 0.628531E+10 | 0.683616E+09 | 0.00 | 1.45 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:22:02
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.233730E+12 | 0.440645E+11 | 0.00 | 0.169346E+12 | 0.103344E+12 |
February | 0.245760E+12 | 0.329503E+11 | 0.00 | 0.160840E+12 | 0.715003E+11 |
March | 0.340403E+12 | 0.286999E+11 | 0.00 | 0.200753E+12 | 0.501645E+11 |
April | 0.388295E+12 | 0.168191E+11 | 0.00 | 0.226005E+12 | 0.498559E+11 |
May | 0.433724E+12 | 0.875147E+10 | 0.00 | 0.270273E+12 | 0.731478E+11 |
June | 0.446762E+12 | 0.110761E+10 | 0.00 | 0.147706E+12 | 0.188524E+12 |
July | 0.448771E+12 | -0.124908E+10 | 0.00 | 0.562949E+11 | 0.251752E+12 |
August | 0.393574E+12 | 0.100275E+10 | 0.00 | 0.127110E+12 | 0.244766E+12 |
September | 0.285628E+12 | 0.779764E+10 | 0.00 | 0.221654E+12 | 0.108847E+12 |
October | 0.230265E+12 | 0.169273E+11 | 0.00 | 0.245024E+12 | 0.246780E+11 |
November | 0.155755E+12 | 0.273909E+11 | 0.00 | 0.190328E+12 | 0.480600E+11 |
December | 0.139609E+12 | 0.370244E+11 | 0.00 | 0.169437E+12 | 0.824474E+11 |
Annual Sum or Average | 0.374228E+13 | 0.221287E+12 | 0.00 | 0.218477E+13 | 0.129709E+13 |
Minimum of Months | 0.139609E+12 | -0.124908E+10 | 0.00 | 0.562949E+11 | 0.246780E+11 |
Maximum of Months | 0.448771E+12 | 0.440645E+11 | 0.00 | 0.270273E+12 | 0.251752E+12 |