Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:20:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2906.09 | 583.30 | 583.30 |
Net Site Energy | 2906.09 | 583.30 | 583.30 |
Total Source Energy | 9203.57 | 1847.30 | 1847.30 |
Net Source Energy | 9203.57 | 1847.30 | 1847.30 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1033.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 236.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 276.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2906.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 1033.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 236.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 276.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 35.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1033.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 236.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 276.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 35.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 270.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 583.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 161.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 270.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 583.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2906.085 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2906.085 | 100.00 |
Total On-Site and Utility Electric Sources | 2906.085 | 100.00 |
Total Electricity End Uses | 2906.085 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 387.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1047.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| CORE_BOTTOM PIU FAN | PERIMETER_BOT_ZN_1 PIU FAN | PERIMETER_BOT_ZN_2 PIU FAN | PERIMETER_BOT_ZN_3 PIU FAN | PERIMETER_BOT_ZN_4 PIU FAN | CORE_MID PIU FAN | PERIMETER_MID_ZN_1 PIU FAN | PERIMETER_MID_ZN_2 PIU FAN | PERIMETER_MID_ZN_3 PIU FAN | PERIMETER_MID_ZN_4 PIU FAN | CORE_TOP PIU FAN | PERIMETER_TOP_ZN_1 PIU FAN | PERIMETER_TOP_ZN_2 PIU FAN | PERIMETER_TOP_ZN_3 PIU FAN | PERIMETER_TOP_ZN_4 PIU FAN | PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:39 | - | - | - | - | - | - | - | - | - | - | - | 27-MAR-11:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 142334.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 34315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2543.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 271991.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 142334.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 34315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 2543.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 3.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3272.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 748.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 876.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 112.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9203.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 656.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 175.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1847.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 656.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 150.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 175.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1847.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
AirTerminal:SingleDuct:ParallelPIU:ReheatDesign Size Maximum Primary Air Flow Rate [m3/s] | Design Size Maximum Secondary Air Flow Rate [m3/s] | Design Size Minimum Primary Air Flow Fraction | User-Specified Minimum Primary Air Flow Fraction | |
CORE_BOTTOM VAV BOX COMPONENT | 3.39 | 3.39 | 0.125256 | 0.300000 |
CORE_MID VAV BOX COMPONENT | 2.84 | 2.84 | 0.149662 | 0.300000 |
CORE_TOP VAV BOX COMPONENT | 3.49 | 3.49 | 0.121606 | 0.300000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.34 | 1.34 | 0.066732 | 0.300000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.03 | 1.03 | 0.054809 | 0.300000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.48 | 1.48 | 0.060481 | 0.300000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.20 | 1.20 | 0.047127 | 0.300000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.13 | 1.13 | 0.079556 | 0.300000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.956234 | 0.956234 | 0.059273 | 0.300000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.27 | 1.27 | 0.070566 | 0.300000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.03 | 1.03 | 0.054776 | 0.300000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 1.13 | 1.13 | 0.079416 | 0.300000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.971613 | 0.971613 | 0.058335 | 0.300000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.27 | 1.27 | 0.070292 | 0.300000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.07 | 1.07 | 0.053110 | 0.300000 |
Design Size Maximum Flow Rate [m3/s] | |
CORE_BOTTOM PIU FAN | 3.39 |
CORE_MID PIU FAN | 2.84 |
CORE_TOP PIU FAN | 3.49 |
PERIMETER_TOP_ZN_3 PIU FAN | 1.34 |
PERIMETER_TOP_ZN_2 PIU FAN | 1.03 |
PERIMETER_TOP_ZN_1 PIU FAN | 1.48 |
PERIMETER_TOP_ZN_4 PIU FAN | 1.20 |
PERIMETER_BOT_ZN_3 PIU FAN | 1.13 |
PERIMETER_BOT_ZN_2 PIU FAN | 0.956234 |
PERIMETER_BOT_ZN_1 PIU FAN | 1.27 |
PERIMETER_BOT_ZN_4 PIU FAN | 1.03 |
PERIMETER_MID_ZN_3 PIU FAN | 1.13 |
PERIMETER_MID_ZN_2 PIU FAN | 0.971613 |
PERIMETER_MID_ZN_1 PIU FAN | 1.27 |
PERIMETER_MID_ZN_4 PIU FAN | 1.07 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 73271.70 |
CORE_MID VAV BOX REHEAT COIL | 62686.04 |
CORE_TOP VAV BOX REHEAT COIL | 76000.64 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 29131.27 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22407.72 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32142.10 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 26058.86 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 24488.95 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 20810.41 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 27609.15 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 22517.27 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 24470.49 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 21091.05 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 27646.88 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 23164.44 |
PACU_VAV_BOT HEATING COIL | 1181.30 |
PACU_VAV_MID HEATING COIL | 0.000000 |
PACU_VAV_TOP HEATING COIL | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.33 | 2.33 | 7.78 | 2.33 | 7.25 | 7.25 | 0.300000 | 0.321828 | 7.25 |
PACU_VAV_MID | 2.18 | 2.18 | 7.28 | 2.18 | 6.69 | 6.69 | 0.300000 | 0.326156 | 6.69 |
PACU_VAV_TOP | 2.57 | 2.57 | 8.55 | 3.08 | 8.33 | 8.33 | 0.300000 | 0.370315 | 8.33 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 7.25 |
PACU_VAV_MID_OA_CONTROLLER | 6.69 |
PACU_VAV_TOP_OA_CONTROLLER | 8.33 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 7.25 | 157240.84 | 0.745541 | 2.42 | 52408.37 | 0.745541 |
PACU_VAV_MID COOLING COIL | 6.69 | 147575.55 | 0.740052 | 2.23 | 49186.93 | 0.740052 |
PACU_VAV_TOP COOLING COIL | 8.33 | 176711.79 | 0.753809 | 2.78 | 58898.04 | 0.753809 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 7.25 |
PACU_VAV_MID FAN | 6.69 |
PACU_VAV_TOP FAN | 8.33 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
43 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
44 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
45 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
46 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
47 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
48 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
49 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
50 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
51 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
52 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
53 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
54 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
55 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
56 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
57 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
58 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
59 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
60 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
61 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
62 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
63 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
64 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
65 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_1.22_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
2 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
3 | WINDOW_U_1.22_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
4 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40575.39652 | 46661.70600 | 2.94833 | 3.39058 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42469 | 00:10:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 | |
3 | CORE_MID | Cooling | 33982.42604 | 39079.78994 | 2.46753 | 2.83766 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 6720.39950 | 8400.49938 | 0.47277 | 0.59097 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 41446.01218 | 47662.91400 | 3.03682 | 3.49234 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 13949.09584 | 17436.36980 | 1.00049 | 1.25061 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 15921.50274 | 18309.72815 | 1.16662 | 1.34161 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 6099.15037 | 7623.93797 | 0.44154 | 0.55193 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 12272.32775 | 14113.17691 | 0.89923 | 1.03412 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 4024.00227 | 5030.00284 | 0.29140 | 0.36425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 17566.98822 | 20202.03645 | 1.28719 | 1.48026 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 6134.14392 | 7667.67989 | 0.44410 | 0.55512 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 14272.02309 | 16412.82656 | 1.04575 | 1.20262 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 42.21800 | 1.07808E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 3999.09496 | 4998.86870 | 0.28958 | 0.36198 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 13355.26461 | 15358.55430 | 0.97857 | 1.12535 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 3140.14897 | 3925.18621 | 0.22558 | 0.28198 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 11348.24279 | 13050.47921 | 0.83151 | 0.95623 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 2126.03837 | 2657.54796 | 0.15289 | 0.19111 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 15056.68613 | 17315.18905 | 1.10323 | 1.26872 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 3185.91407 | 3982.39259 | 0.22892 | 0.28616 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 12279.21399 | 14121.09609 | 0.89972 | 1.03468 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 2095.89620 | 2619.87025 | 0.15069 | 0.18836 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 13378.72102 | 15385.52917 | 0.98030 | 1.12734 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 4288.09930 | 5360.12412 | 0.30938 | 0.38672 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11530.62702 | 13260.22107 | 0.84488 | 0.97161 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 2875.01397 | 3593.76746 | 0.20758 | 0.25948 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 15115.27344 | 17382.56446 | 1.10754 | 1.27367 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 4329.11466 | 5411.39332 | 0.31238 | 0.39047 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 12664.26261 | 14563.90200 | 0.92794 | 1.06714 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 2846.37238 | 3557.96547 | 0.20549 | 0.25686 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 119132.94 | 7.24820 | 7.24820 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 315.63 | 1.37468 | 1.37468 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 111648.19 | 6.69380 | 6.69380 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 201.06 | 1.88449 | 1.88449 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 133579.85 | 8.32772 | 8.32772 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 187.77 | 3.08388 | 3.08388 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 3.39058 |
2 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 3.39058 |
3 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.12526 |
4 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
5 | Fan:ConstantVolume | CORE_BOTTOM PIU FAN | Design Size Maximum Flow Rate [m3/s] | 3.39058 |
6 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 73271.69582 |
7 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 2.83766 |
8 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 2.83766 |
9 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.14966 |
10 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
11 | Fan:ConstantVolume | CORE_MID PIU FAN | Design Size Maximum Flow Rate [m3/s] | 2.83766 |
12 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 62686.04415 |
13 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 3.49234 |
14 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 3.49234 |
15 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.12161 |
16 | AirTerminal:SingleDuct:ParallelPIU:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
17 | Fan:ConstantVolume | CORE_TOP PIU FAN | Design Size Maximum Flow Rate [m3/s] | 3.49234 |
18 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 76000.64341 |
19 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.34161 |
20 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.34161 |
21 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.67322E-002 |
22 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
23 | Fan:ConstantVolume | PERIMETER_TOP_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.34161 |
24 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29131.26742 |
25 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.03412 |
26 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.03412 |
27 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.48092E-002 |
28 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
29 | Fan:ConstantVolume | PERIMETER_TOP_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.03412 |
30 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22407.72435 |
31 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.48026 |
32 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.48026 |
33 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 6.04815E-002 |
34 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
35 | Fan:ConstantVolume | PERIMETER_TOP_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.48026 |
36 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 32142.09903 |
37 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.20262 |
38 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.20262 |
39 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 4.71267E-002 |
40 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
41 | Fan:ConstantVolume | PERIMETER_TOP_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.20262 |
42 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26058.86110 |
43 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.12535 |
44 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.12535 |
45 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 7.95559E-002 |
46 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
47 | Fan:ConstantVolume | PERIMETER_BOT_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.12535 |
48 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24488.95017 |
49 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.95623 |
50 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.95623 |
51 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.92732E-002 |
52 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
53 | Fan:ConstantVolume | PERIMETER_BOT_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.95623 |
54 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20810.40771 |
55 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.26872 |
56 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.26872 |
57 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 7.05661E-002 |
58 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
59 | Fan:ConstantVolume | PERIMETER_BOT_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.26872 |
60 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27609.15416 |
61 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.03468 |
62 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.03468 |
63 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.47757E-002 |
64 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
65 | Fan:ConstantVolume | PERIMETER_BOT_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.03468 |
66 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22517.26961 |
67 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.12734 |
68 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.12734 |
69 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 7.94156E-002 |
70 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
71 | Fan:ConstantVolume | PERIMETER_MID_ZN_3 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.12734 |
72 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24470.48880 |
73 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.97161 |
74 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.97161 |
75 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.83350E-002 |
76 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
77 | Fan:ConstantVolume | PERIMETER_MID_ZN_2 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.97161 |
78 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21091.04557 |
79 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.27367 |
80 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.27367 |
81 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 7.02919E-002 |
82 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
83 | Fan:ConstantVolume | PERIMETER_MID_ZN_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.27367 |
84 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27646.88378 |
85 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 1.06714 |
86 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 1.06714 |
87 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 5.31097E-002 |
88 | AirTerminal:SingleDuct:ParallelPIU:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
89 | Fan:ConstantVolume | PERIMETER_MID_ZN_4 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 1.06714 |
90 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23164.44301 |
91 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.33267 |
92 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.33267 |
93 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.77557 |
94 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.33267 |
95 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.24820 |
96 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 7.24820 |
97 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
98 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.32183 |
99 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.18323 |
100 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.18323 |
101 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.27742 |
102 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.18323 |
103 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.69380 |
104 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 6.69380 |
105 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
106 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.32616 |
107 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.56529 |
108 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.56529 |
109 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.55095 |
110 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.08388 |
111 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.32772 |
112 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 8.32772 |
113 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
114 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.37032 |
115 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 7.24820 |
116 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 6.69380 |
117 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 8.32772 |
118 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.24820 |
119 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 7.24820 |
120 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 157240.83733 |
121 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74554 |
122 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.41582 |
123 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 52408.37108 |
124 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74554 |
125 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 1181.29825 |
126 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 7.24820 |
127 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.69380 |
128 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.69380 |
129 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 147575.55274 |
130 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74005 |
131 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.23104 |
132 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 49186.93173 |
133 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74005 |
134 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
135 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 6.69380 |
136 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.32772 |
137 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 8.32772 |
138 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 176711.78531 |
139 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75381 |
140 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.77563 |
141 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 58898.03804 |
142 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75381 |
143 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
144 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 8.32772 |
145 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
146 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
147 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
148 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
149 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 156275.60 | 533234.47 | 11.67 | 3.00 | 3.34 | 3.52 | 3.68 | 10.23 | 11.40 | 12.01 | 12.56 | 8.3794 | 6.6722 | 4.4928 | 1.8507 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 146753.83 | 500744.84 | 11.70 | 3.00 | 3.35 | 3.53 | 3.69 | 10.25 | 11.44 | 12.05 | 12.59 | 7.7385 | 6.1580 | 4.1466 | 1.7157 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 175486.29 | 598784.07 | 11.62 | 2.99 | 3.33 | 3.50 | 3.67 | 10.19 | 11.35 | 11.95 | 12.53 | 9.6274 | 7.6660 | 5.1697 | 2.1105 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_NORTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_EAST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_SOUTH_0.25 | N/A | 6.926 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_1.22_SHGC_WEST_0.25 | N/A | 6.926 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1005677440 | 0.2252878262 | Pass | Pass | 4.5052294023E-002 | 0.2073605877 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1019801628 | 7.2915545170E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.8106653375E-002 | 2.9738901644E-002 | Pass | Pass | 6.7571579883E-002 | 0.5322071056 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.5726766593E-002 | 4.5037658687E-002 | Pass | Pass | 6.5892423057E-002 | 0.2815932665 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.4106257295E-002 | 0.1262015156 | Pass | Pass | 1.4348174211E-002 | 0.1189218797 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.0957342476E-002 | 1.8375043089E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.4658529215E-002 | 3.7806047020E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.8302412564E-002 | 3.5915003679E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.7386622017E-002 | 6.9637282743E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.8311504213E-002 | 5.7602703246E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1214628349 | 0.2352071261 | Pass | Pass | 4.5182522004E-002 | 0.2068565368 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1483371685 | 0.3012946150 | Pass | Pass | 4.6699156406E-002 | 0.2092468529 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1677653278 | 0.3178387715 | Pass | Pass | 4.8808788553E-002 | 0.2183596563 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1673025956 | 0.3401556079 | Pass | Pass | 4.6738440375E-002 | 0.2114218918 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 8.5516924922E-002 | 0.1763007321 | Pass | Pass | 1.5290397290E-002 | 0.1224418457 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1012743629 | 0.2247853181 | Pass | Pass | 1.6168574196E-002 | 0.1255601592 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1289447089 | 0.2336991730 | Pass | Pass | 1.6778504464E-002 | 0.1301414381 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1231782829 | 0.2558369632 | Pass | Pass | 1.6565411271E-002 | 0.1290706903 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3230.18 | -132.2 | 0.00 | -1131.1 | 4827.01 | 6793.97 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_1.22_SHGC_NORTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_1.22_SHGC_EAST_0.25 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_1.22_SHGC_EAST_0.25 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_1.22_SHGC_WEST_0.25 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_1.22_SHGC_WEST_0.25 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 6.926 | 0.251 | 0.277 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_1.22_SHGC_NORTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_1.22_SHGC_EAST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_1.22_SHGC_SOUTH_0.25 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_1.22_SHGC_WEST_0.25 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 6.926 | 0.251 | 0.277 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
North Total or Average | 183.92 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
Non-North Total or Average | 429.15 | 6.926 | 0.251 | 0.277 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.85 | 83.85 | 236.30 | |
Exterior Lighting Total | 15013.15 | 236.30 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 157240.84 | 117229.52 | 40011.31 | 0.75 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 147575.55 | 109213.54 | 38362.02 | 0.74 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 176711.79 | 133206.92 | 43504.87 | 0.75 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 156275.6 | 3.00 | 10.23 | N/A | N/A | 11.67 | |
PACU_VAV_MID COOLING COIL | 146753.8 | 3.00 | 10.25 | N/A | N/A | 11.70 | |
PACU_VAV_TOP COOLING COIL | 175486.3 | 2.99 | 10.19 | N/A | N/A | 11.62 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 73271.70 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 62686.04 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 76000.64 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 29131.27 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22407.72 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 32142.10 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 26058.86 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 24488.95 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20810.41 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 27609.15 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22517.27 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 24470.49 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21091.05 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 27646.88 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23164.44 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 1181.30 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CORE_BOTTOM PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 3.39 | 2513.28 | 741.25 | 1.00 | 1.23 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
CORE_MID PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 2.84 | 2103.43 | 741.25 | 1.00 | 1.25 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
CORE_TOP PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 3.49 | 2588.71 | 741.25 | 1.00 | 1.22 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PERIMETER_TOP_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.34 | 994.47 | 741.25 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
PERIMETER_TOP_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.03 | 766.54 | 741.25 | 1.00 | 1.44 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 |
PERIMETER_TOP_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.48 | 1097.25 | 741.25 | 1.00 | 1.35 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
PERIMETER_TOP_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.20 | 891.44 | 741.25 | 1.00 | 1.40 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 |
PERIMETER_BOT_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.13 | 834.17 | 741.25 | 1.00 | 1.41 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
PERIMETER_BOT_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.96 | 708.81 | 741.25 | 1.00 | 1.46 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PERIMETER_BOT_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.27 | 940.44 | 741.25 | 1.00 | 1.38 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PERIMETER_BOT_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.03 | 766.96 | 741.25 | 1.00 | 1.44 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
PERIMETER_MID_ZN_3 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.13 | 835.65 | 741.25 | 1.00 | 1.41 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
PERIMETER_MID_ZN_2 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.97 | 720.21 | 741.25 | 1.00 | 1.45 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PERIMETER_MID_ZN_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.27 | 944.11 | 741.25 | 1.00 | 1.38 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
PERIMETER_MID_ZN_4 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 1.07 | 791.02 | 741.25 | 1.00 | 1.43 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.25 | 15929.95 | 2197.78 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.69 | 14711.51 | 2197.78 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 8.33 | 18302.51 | 2197.78 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 156275.60 | 3.00 | 10.23 | 11.67 | 8.3794 | 3.34 | 11.40 | 6.6722 | 3.52 | 12.01 | 4.4928 | 3.68 | 12.56 | 1.8507 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 146753.83 | 3.00 | 10.25 | 11.70 | 7.7385 | 3.35 | 11.44 | 6.1580 | 3.53 | 12.05 | 4.1466 | 3.69 | 12.59 | 1.7157 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 175486.29 | 2.99 | 10.19 | 11.62 | 9.6274 | 3.33 | 11.35 | 7.6660 | 3.50 | 11.95 | 5.1697 | 3.67 | 12.53 | 2.1105 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40575.40 | 46661.71 | 47.44 | 2.948 | 3.391 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_MID | 33982.43 | 39079.79 | 39.73 | 2.468 | 2.838 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_TOP | 41446.01 | 47662.91 | 48.46 | 3.037 | 3.492 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00879 | 42.80 | 0.01078 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15921.50 | 18309.73 | 88.31 | 1.167 | 1.342 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00872 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 12272.33 | 14113.18 | 107.52 | 0.899 | 1.034 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00868 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17566.99 | 20202.04 | 97.44 | 1.287 | 1.480 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00870 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 14272.02 | 16412.83 | 125.05 | 1.046 | 1.203 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 24.00 | 24.00 | 0.00866 | 42.22 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 13355.26 | 15358.55 | 74.07 | 0.979 | 1.125 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00873 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 11348.24 | 13050.48 | 99.42 | 0.832 | 0.956 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00867 | 39.60 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 15056.69 | 17315.19 | 83.51 | 1.103 | 1.269 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00870 | 42.64 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 12279.21 | 14121.10 | 107.59 | 0.900 | 1.035 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 24.00 | 24.00 | 0.00866 | 42.09 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 13378.72 | 15385.53 | 74.21 | 0.980 | 1.127 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00875 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11530.63 | 13260.22 | 101.02 | 0.845 | 0.972 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00869 | 39.60 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 15115.27 | 17382.56 | 83.84 | 1.108 | 1.274 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00872 | 42.64 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 12664.26 | 14563.90 | 110.96 | 0.928 | 1.067 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 24.00 | 24.00 | 0.00867 | 42.09 | 0.01078 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | 00:10:00 | 15.60 | 21.40 | 0.00915 | 12.70 | 0.00915 | 0.425 | 0.00 | |
CORE_MID | 6720.40 | 8400.50 | 8.54 | 0.473 | 0.591 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 13949.10 | 17436.37 | 17.73 | 1.000 | 1.251 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 6099.15 | 7623.94 | 36.77 | 0.442 | 0.552 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00809 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 4024.00 | 5030.00 | 38.32 | 0.291 | 0.364 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00809 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 6134.14 | 7667.68 | 36.98 | 0.444 | 0.555 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00809 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 3999.09 | 4998.87 | 38.09 | 0.290 | 0.362 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00809 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 3140.15 | 3925.19 | 18.93 | 0.226 | 0.282 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00816 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 2126.04 | 2657.55 | 20.25 | 0.153 | 0.191 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00815 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 3185.91 | 3982.39 | 19.21 | 0.229 | 0.286 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00815 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 2095.90 | 2619.87 | 19.96 | 0.151 | 0.188 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00815 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 4288.10 | 5360.12 | 25.85 | 0.309 | 0.387 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 2875.01 | 3593.77 | 27.38 | 0.208 | 0.259 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 4329.11 | 5411.39 | 26.10 | 0.312 | 0.390 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 2846.37 | 3557.97 | 27.11 | 0.205 | 0.257 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 7.25 | 7.25 | 1.37 | 1.37 | 7.2482 | 2.3327 | 7.2482 | 0.3218 | 0.3000 |
PACU_VAV_MID | 6.69 | 6.69 | 1.88 | 1.88 | 6.6938 | 2.1832 | 6.6938 | 0.3262 | 0.3000 |
PACU_VAV_TOP | 8.33 | 8.33 | 3.08 | 3.08 | 8.3277 | 3.0839 | 8.3277 | 0.3703 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 73271.696 | 73271.696 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 73271.70 | 7059.79 | 0.424691 | 18.57 | 5.11 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 62686.044 | 62686.044 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62686.04 | 10042.26 | 0.590968 | 18.27 | 4.96 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 8400.50 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 76000.643 | 76000.643 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76000.64 | 20935.30 | 1.250610 | 18.47 | 5.06 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 17436.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 29131.267 | 29131.267 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29131.27 | 9218.74 | 0.551928 | 18.50 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00808931 | 52.2616 | 7623.94 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 22407.724 | 22407.724 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22407.72 | 6071.34 | 0.364250 | 18.53 | 5.09 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00808695 | 52.2465 | 5030.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 32142.099 | 32142.099 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32142.10 | 9272.10 | 0.555120 | 18.50 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00808854 | 52.2567 | 7667.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 26058.861 | 26058.861 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26058.86 | 6033.43 | 0.361975 | 18.53 | 5.09 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00808777 | 52.2518 | 4998.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 24488.950 | 24488.950 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24488.95 | 4720.11 | 0.281977 | 18.47 | 5.06 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815548 | 52.6836 | 3925.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 20810.408 | 20810.408 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20810.41 | 3199.30 | 0.191109 | 18.47 | 5.06 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814990 | 52.6480 | 2657.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 27609.154 | 27609.154 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27609.15 | 4790.13 | 0.286156 | 18.47 | 5.06 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815270 | 52.6659 | 3982.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 22517.270 | 22517.270 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22517.27 | 3153.21 | 0.188359 | 18.47 | 5.06 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815269 | 52.6658 | 2619.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 24470.489 | 24470.489 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24470.49 | 6457.12 | 0.386719 | 18.51 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813944 | 52.5812 | 5360.12 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 21091.046 | 21091.046 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21091.05 | 4332.69 | 0.259475 | 18.51 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813352 | 52.5434 | 3593.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 27646.884 | 27646.884 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27646.88 | 6519.78 | 0.390470 | 18.51 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813755 | 52.5691 | 5411.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 23164.443 | 23164.443 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23164.44 | 4288.95 | 0.256857 | 18.51 | 5.08 | -999.0 | 32.11 | 18.73 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813549 | 52.5559 | 3557.97 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 157240.837 | 117229.524 | 7.248198 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 143811.46 | 132241.75 | 7.248198 | 26.48 | 17.68 | 0.00902129 | 11.10 | 11.10 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 13.1909 | 24.00 | 0.00875378 | 47.0845 | 86018.98 | 0.00 | 162136.41 | 119041.29 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 1181.298 | 1181.298 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 1181.30 | 1181.30 | 2.174459 | 12.44 | 12.28 | 0.00883239 | 12.89 | 11.63 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 43.9695 | 21.13 | 0.00865382 | 55.4120 | 7587.79 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 147575.553 | 109213.537 | 6.693802 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 135362.07 | 123651.96 | 6.693802 | 26.69 | 17.79 | 0.00907201 | 11.10 | 11.10 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 14.2834 | 24.00 | 0.00878696 | 47.2607 | 79408.19 | 0.00 | 152170.20 | 110946.25 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 2.008141 | 17.05 | 13.87 | 0.00857272 | 12.89 | 11.63 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 47.6112 | 19.59 | 0.00806382 | 56.8590 | 6763.38 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 176711.785 | 133206.920 | 8.327722 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 161002.85 | 148958.56 | 8.327722 | 26.16 | 17.53 | 0.00897151 | 11.10 | 11.10 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 11.4809 | 24.00 | 0.00873658 | 46.9935 | 98778.73 | 0.00 | 182213.57 | 135247.98 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 2.498317 | 17.82 | 14.07 | 0.00847020 | 12.89 | 11.63 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 38.2698 | 19.05 | 0.00806058 | 58.7626 | 6900.06 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 73271.696 | 73271.696 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 73271.70 | 7059.79 | 1.0000 | 0.51115607 | 0.424691 | 18.57 | 5.11 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73271.70 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 62686.044 | 62686.044 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 62686.04 | 10042.26 | 1.0000 | 0.71128647 | 0.590968 | 18.27 | 4.96 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62686.04 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.57 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 8400.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 76000.643 | 76000.643 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76000.64 | 20935.30 | 1.0000 | 1.50522847 | 1.250610 | 18.47 | 5.06 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76000.64 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 17436.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 29131.267 | 29131.267 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29131.27 | 9218.74 | 1.0000 | 0.66429719 | 0.551928 | 18.50 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29131.27 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00808931 | 21.00 | 0.00808931 | 52.2616 | 7623.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 22407.724 | 22407.724 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22407.72 | 6071.34 | 1.0000 | 0.43840928 | 0.364250 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22407.72 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.95 | 0.00808695 | 21.00 | 0.00808695 | 52.2465 | 5030.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 32142.099 | 32142.099 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32142.10 | 9272.10 | 1.0000 | 0.66813942 | 0.555120 | 18.50 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32142.10 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00808854 | 21.00 | 0.00808854 | 52.2567 | 7667.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 26058.861 | 26058.861 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26058.86 | 6033.43 | 1.0000 | 0.43567176 | 0.361975 | 18.53 | 5.09 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26058.86 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.95 | 0.00808777 | 21.00 | 0.00808777 | 52.2518 | 4998.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 24488.950 | 24488.950 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24488.95 | 4720.11 | 1.0000 | 0.33938659 | 0.281977 | 18.47 | 5.06 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24488.95 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00815548 | 21.00 | 0.00815548 | 52.6836 | 3925.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 20810.408 | 20810.408 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20810.41 | 3199.30 | 1.0000 | 0.23001830 | 0.191109 | 18.47 | 5.06 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20810.41 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00814990 | 21.00 | 0.00814990 | 52.6480 | 2657.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 27609.154 | 27609.154 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27609.15 | 4790.13 | 1.0000 | 0.34441589 | 0.286156 | 18.47 | 5.06 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27609.15 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00815270 | 21.00 | 0.00815270 | 52.6659 | 3982.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 22517.270 | 22517.270 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22517.27 | 3153.21 | 1.0000 | 0.22670821 | 0.188359 | 18.47 | 5.06 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22517.27 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00815269 | 21.00 | 0.00815269 | 52.6658 | 2619.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 24470.489 | 24470.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24470.49 | 6457.12 | 1.0000 | 0.46545316 | 0.386719 | 18.51 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24470.49 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813944 | 21.00 | 0.00813944 | 52.5812 | 5360.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 21091.046 | 21091.046 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21091.05 | 4332.69 | 1.0000 | 0.31230310 | 0.259475 | 18.51 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21091.05 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813352 | 21.00 | 0.00813352 | 52.5434 | 3593.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 27646.884 | 27646.884 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27646.88 | 6519.78 | 1.0000 | 0.46996717 | 0.390470 | 18.51 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27646.88 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813755 | 21.00 | 0.00813755 | 52.5691 | 5411.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 23164.443 | 23164.443 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23164.44 | 4288.95 | 1.0000 | 0.30915222 | 0.256857 | 18.51 | 5.08 | -999.0 | -999.0 | 32.11 | 18.73 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23164.44 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813549 | 21.00 | 0.00813549 | 52.5559 | 3557.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 157240.837 | 117229.524 | 7.248198 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6101 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 7.248198 | 8.72389499 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 143811.46 | 132241.75 | 0.9146 | 8.72389499 | 7.248198 | 26.48 | 17.68 | 0.00902129 | 49612.7 | 11.10 | 11.10 | 0.00850000 | 32588.6 | -999.0 | -999.00 | -999.00 | -999.00 | 15929.953 | 127881.51 | 42.80 | 0.01078182 | 23.86 | 0.95610000 | 13.1909 | 24.00 | 0.00875378 | 24.00 | 0.00875378 | 47.0845 | 86018.98 | 0.00 | 162136.41 | 119041.29 | 8.37936709 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.76 | 12.75 | 0.00916820 | 35972.9 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1181.298 | 1181.298 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 7.248198 | 8.72389499 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 1181.30 | 1181.30 | 1.0000 | 2.61716850 | 2.174459 | 12.44 | 12.28 | 0.00883239 | 34793.4 | 12.89 | 11.63 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1181.30 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 43.9695 | 12.24 | 0.00858044 | 21.13 | 0.00865382 | 55.4120 | 7587.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 147575.553 | 109213.537 | 6.693802 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7044 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.693802 | 8.05662685 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 135362.07 | 123651.96 | 0.9172 | 8.05662685 | 6.693802 | 26.69 | 17.79 | 0.00907201 | 49952.9 | 11.10 | 11.10 | 0.00850000 | 32588.8 | -999.0 | -999.00 | -999.00 | -999.00 | 14711.512 | 120650.55 | 42.80 | 0.01078182 | 23.86 | 0.95610000 | 14.2834 | 24.00 | 0.00878696 | 24.00 | 0.00878696 | 47.2607 | 79408.19 | 0.00 | 152170.20 | 110946.25 | 7.73845099 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.63 | 12.62 | 0.00909600 | 35658.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.693802 | 8.05662685 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.41698805 | 2.008141 | 17.05 | 13.87 | 0.00857272 | 38842.4 | 12.89 | 11.63 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 47.6112 | 21.00 | 0.00804496 | 19.59 | 0.00806382 | 56.8590 | 6763.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 176711.785 | 133206.920 | 8.327722 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5176 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 8.327722 | 10.02320438 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 161002.85 | 148958.56 | 0.9111 | 10.02320438 | 8.327722 | 26.16 | 17.53 | 0.00897151 | 49158.4 | 11.10 | 11.10 | 0.00850000 | 32588.5 | -999.0 | -999.00 | -999.00 | -999.00 | 18302.510 | 142700.34 | 42.80 | 0.01078182 | 23.86 | 0.95610000 | 11.4809 | 24.00 | 0.00873658 | 24.00 | 0.00873658 | 46.9935 | 98778.73 | 0.00 | 182213.57 | 135247.98 | 9.62736358 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.92 | 12.91 | 0.00927197 | 36395.8 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 8.327722 | 10.02320438 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 22:40:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 3.00696132 | 2.498317 | 17.82 | 14.07 | 0.00847020 | 39374.0 | 12.89 | 11.63 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 38.2698 | 21.00 | 0.00804662 | 19.05 | 0.00806058 | 58.7626 | 6900.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5631.17 | 0.00 | 0.00 |
CORE_MID | 4753.67 | 388.00 | 0.00 |
CORE_TOP | 4199.33 | 1057.17 | 12.83 |
PERIMETER_TOP_ZN_3 | 3887.33 | 1901.00 | 312.83 |
PERIMETER_TOP_ZN_2 | 4090.17 | 1786.83 | 387.00 |
PERIMETER_TOP_ZN_1 | 4361.17 | 1583.00 | 358.17 |
PERIMETER_TOP_ZN_4 | 3783.50 | 2055.50 | 325.17 |
PERIMETER_BOT_ZN_3 | 4482.50 | 1165.83 | 195.50 |
PERIMETER_BOT_ZN_2 | 4620.83 | 1159.00 | 294.50 |
PERIMETER_BOT_ZN_1 | 4967.50 | 1355.67 | 758.50 |
PERIMETER_BOT_ZN_4 | 4389.17 | 1317.67 | 244.83 |
PERIMETER_MID_ZN_3 | 4244.83 | 1479.50 | 271.83 |
PERIMETER_MID_ZN_2 | 3520.17 | 1452.17 | 343.50 |
PERIMETER_MID_ZN_1 | 4682.67 | 1204.67 | 330.33 |
PERIMETER_MID_ZN_4 | 4067.00 | 1704.67 | 282.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5727.17 | 2834.33 | 1047.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 52.50 | 0.00 | 43.17 |
PERIMETER_TOP_ZN_2 | 0.00 | 72.83 | 0.00 | 65.83 |
PERIMETER_TOP_ZN_1 | 0.00 | 68.00 | 0.00 | 61.17 |
PERIMETER_TOP_ZN_4 | 0.00 | 58.33 | 0.00 | 44.83 |
PERIMETER_BOT_ZN_3 | 0.00 | 36.67 | 0.00 | 30.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 63.50 | 0.00 | 59.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 280.33 | 0.00 | 274.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 54.50 | 0.00 | 40.17 |
PERIMETER_MID_ZN_3 | 0.00 | 42.50 | 0.00 | 35.67 |
PERIMETER_MID_ZN_2 | 0.00 | 65.33 | 0.00 | 62.83 |
PERIMETER_MID_ZN_1 | 0.00 | 58.67 | 0.00 | 55.50 |
PERIMETER_MID_ZN_4 | 0.00 | 48.83 | 0.00 | 37.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 415.33 | 0.00 | 387.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.427 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.383 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.383 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.692 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.849 | 0.076 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.802 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.914 | 0.076 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.570 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.730 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.780 | 1.255 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.750 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.694 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.880 | 0.066 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.824 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.939 | 0.063 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.11 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 7279099.45 | 0.00 | 7279099.45 | 0.00 | 7279099.45 | 13393058.27 | 8067.82 | 99.11 | 593.07 | 517.02 |
CORE_MID | 6406497.23 | 0.00 | 6406497.23 | 0.00 | 6406497.23 | 13393058.27 | 8747.84 | 0.93 | 11.23 | 391.98 |
CORE_TOP | 6420770.30 | 0.00 | 6420770.30 | 0.00 | 6420770.30 | 13393058.27 | 8757.51 | 0.21 | 2.29 | 391.03 |
PERIMETER_TOP_ZN_3 | 2447070.70 | 0.00 | 2447070.70 | 413457.77 | 2860528.47 | 2823374.22 | 3334.72 | 31.43 | 5393.85 | 391.03 |
PERIMETER_TOP_ZN_2 | 1899224.27 | 0.00 | 1899224.27 | 275636.86 | 2174861.13 | 1787429.43 | 3305.80 | 0.72 | 5453.48 | 391.03 |
PERIMETER_TOP_ZN_1 | 2826338.85 | 0.00 | 2826338.85 | 413457.77 | 3239796.62 | 2823374.22 | 3308.28 | 1.20 | 5450.51 | 391.03 |
PERIMETER_TOP_ZN_4 | 2059405.19 | 0.00 | 2059405.19 | 275636.86 | 2335042.04 | 1787312.18 | 3300.87 | 1.20 | 5457.92 | 391.03 |
PERIMETER_BOT_ZN_3 | 2079054.51 | 0.00 | 2079054.51 | 219835.62 | 2298890.13 | 2823374.22 | 4542.05 | 133.27 | 4084.68 | 517.02 |
PERIMETER_BOT_ZN_2 | 1693046.73 | 0.00 | 1693046.73 | 146556.20 | 1839602.92 | 1787429.43 | 3273.43 | 59.94 | 5426.62 | 517.02 |
PERIMETER_BOT_ZN_1 | 2788505.86 | 0.00 | 2788505.86 | 4198137.27 | 6986643.13 | 2823374.22 | 3409.47 | 60.36 | 5290.17 | 517.02 |
PERIMETER_BOT_ZN_4 | 1749871.31 | 0.00 | 1749871.31 | 146556.20 | 1896427.51 | 1787312.18 | 3292.30 | 43.25 | 5424.45 | 517.02 |
PERIMETER_MID_ZN_3 | 2459857.21 | 0.00 | 2459857.21 | 344173.66 | 2804030.87 | 2823374.22 | 3608.58 | 85.05 | 5066.36 | 391.98 |
PERIMETER_MID_ZN_2 | 1974621.59 | 0.00 | 1974621.59 | 229447.73 | 2204069.31 | 1601953.02 | 3294.38 | 1.19 | 5464.43 | 1300.98 |
PERIMETER_MID_ZN_1 | 2908783.57 | 0.00 | 2908783.57 | 344173.66 | 3252957.22 | 2823374.22 | 3313.83 | 7.36 | 5438.81 | 391.98 |
PERIMETER_MID_ZN_4 | 2123625.47 | 0.00 | 2123625.47 | 229447.73 | 2353073.19 | 1787312.18 | 3290.26 | 0.68 | 5469.06 | 391.98 |
Total Facility | 47115772.22 | 0.00 | 47115772.22 | 7236517.31 | 54352289.53 | 67658168.57 | 8760.00 | 494.11 | 5910.53 | 1581.09 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3100 | 0.0000 | 0.3100 | 0.0000 | 0.3100 | 0.4247 | 5257.25 | 98.72 | 587.03 |
CORE_MID | 0.2776 | 0.0000 | 0.2776 | 0.0000 | 0.2776 | 0.4247 | 5932.00 | 0.93 | 10.07 |
CORE_TOP | 0.2784 | 0.0000 | 0.2784 | 0.0000 | 0.2784 | 0.4247 | 5941.17 | 0.13 | 1.70 |
PERIMETER_TOP_ZN_3 | 0.1059 | 0.0000 | 0.1059 | 0.0110 | 0.1169 | 0.0895 | 904.72 | 31.37 | 5006.91 |
PERIMETER_TOP_ZN_2 | 0.0823 | 0.0000 | 0.0823 | 0.0073 | 0.0897 | 0.0567 | 876.91 | 0.44 | 5065.65 |
PERIMETER_TOP_ZN_1 | 0.1229 | 0.0000 | 0.1229 | 0.0110 | 0.1339 | 0.0895 | 878.94 | 0.98 | 5063.08 |
PERIMETER_TOP_ZN_4 | 0.0888 | 0.0000 | 0.0888 | 0.0073 | 0.0961 | 0.0567 | 872.71 | 1.11 | 5069.18 |
PERIMETER_BOT_ZN_3 | 0.0872 | 0.0000 | 0.0872 | 0.0058 | 0.0930 | 0.0895 | 2227.19 | 131.55 | 3584.26 |
PERIMETER_BOT_ZN_2 | 0.0707 | 0.0000 | 0.0707 | 0.0039 | 0.0746 | 0.0567 | 968.93 | 59.04 | 4915.03 |
PERIMETER_BOT_ZN_1 | 0.1191 | 0.0000 | 0.1191 | 0.1918 | 0.3109 | 0.0895 | 1100.04 | 59.90 | 4783.06 |
PERIMETER_BOT_ZN_4 | 0.0726 | 0.0000 | 0.0726 | 0.0039 | 0.0765 | 0.0567 | 989.28 | 42.81 | 4910.90 |
PERIMETER_MID_ZN_3 | 0.1062 | 0.0000 | 0.1062 | 0.0091 | 0.1153 | 0.0895 | 1178.74 | 84.69 | 4679.56 |
PERIMETER_MID_ZN_2 | 0.0853 | 0.0000 | 0.0853 | 0.0064 | 0.0917 | 0.0567 | 866.62 | 0.88 | 4166.50 |
PERIMETER_MID_ZN_1 | 0.1261 | 0.0000 | 0.1261 | 0.0091 | 0.1353 | 0.0895 | 884.60 | 7.22 | 5051.18 |
PERIMETER_MID_ZN_4 | 0.0910 | 0.0000 | 0.0910 | 0.0061 | 0.0971 | 0.0567 | 863.33 | 0.53 | 5079.15 |
Total Facility | 2.0242 | 0.0000 | 2.0242 | 0.2728 | 2.2970 | 2.1513 | 5943.00 | 489.15 | 5239.41 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 22583710.27 | 0.00 | 22583710.27 | 22614548.33 | 3139.67 | 1.48 | 5618.86 | 517.02 |
PACU_VAV_MID | 22994847.64 | 0.00 | 22994847.64 | 22429071.92 | 3294.02 | 0.59 | 5465.38 | 391.98 |
PACU_VAV_TOP | 22675309.85 | 0.00 | 22675309.85 | 22614548.33 | 3305.17 | 0.50 | 5454.33 | 391.03 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9555 | 0.0000 | 0.9555 | 0.7171 | 837.12 | 1.20 | 5104.68 |
PACU_VAV_MID | 0.9936 | 0.0000 | 0.9936 | 0.7084 | 866.31 | 0.52 | 5076.17 |
PACU_VAV_TOP | 0.9826 | 0.0000 | 0.9826 | 0.7171 | 876.49 | 0.40 | 5066.11 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 80.90 | 0.00 | 0.00 | 0.00 | 0.00 | 5556.14 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 112.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5360.80 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 39.80 | 0.00 | 0.00 | 0.00 | 0.00 | 5423.02 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.9216 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1117 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1469 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1627 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.9981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1526 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 842 |
Defaulted Fields | 530 |
Fields with Defaults | 2032 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2906.09 | 15934.24 | 19-FEB-18:10 | 271991.78 | 10-AUG-15:40 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 1338.66 | 383.73 | 01-JAN-00:10 | 178172.15 | 10-AUG-15:30 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 28-APR-11:10 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 28-APR-11:10 |
ElectricityPurchased:Facility | 2906.09 | 15934.24 | 19-FEB-18:10 | 271991.78 | 10-AUG-15:40 |
ElectricityPurchased:Plant | 2906.09 | 15934.24 | 19-FEB-18:10 | 271991.78 | 10-AUG-15:40 |
Cogeneration:ElectricityPurchased | 2906.09 | 15934.24 | 19-FEB-18:10 | 271991.78 | 10-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 2906.09 | 15934.24 | 19-FEB-18:10 | 271991.78 | 10-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2906.09 | 15934.24 | 19-FEB-18:10 | 271991.78 | 10-AUG-15:40 |
ElectricityNet:Plant | 2906.09 | 15934.24 | 19-FEB-18:10 | 271991.78 | 10-AUG-15:40 |
Cogeneration:ElectricityNet | 2906.09 | 15934.24 | 19-FEB-18:10 | 271991.78 | 10-AUG-15:40 |
General:Cogeneration:ElectricityNet | 2906.09 | 15934.24 | 19-FEB-18:10 | 271991.78 | 10-AUG-15:40 |
Fans:Electricity | 276.71 | 0.00 | 01-JAN-00:10 | 35138.08 | 09-JUN-15:30 |
General:Fans:Electricity | 276.71 | 0.00 | 01-JAN-00:10 | 35138.08 | 09-JUN-15:30 |
Heating:Electricity | 0.98 | 0.00 | 01-JAN-00:10 | 23552.60 | 20-JAN-07:10 |
General:Heating:Electricity | 0.98 | 0.00 | 01-JAN-00:10 | 23552.60 | 20-JAN-07:10 |
ExteriorLights:Electricity | 236.30 | 0.00 | 01-JAN-07:10 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 236.30 | 0.00 | 01-JAN-07:10 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 1033.46 | 0.00 | 01-JAN-00:10 | 142390.76 | 10-AUG-15:30 |
General:Cooling:Electricity | 1033.46 | 0.00 | 01-JAN-00:10 | 142390.76 | 10-AUG-15:30 |
Electricity:Plant | 35.60 | 0.00 | 01-JAN-00:10 | 4623.65 | 13-JAN-12:20 |
WaterSystems:Electricity | 35.45 | 0.00 | 01-JAN-00:10 | 4616.80 | 13-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 35.45 | 0.00 | 01-JAN-00:10 | 4616.80 | 13-JAN-12:20 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 14-MAY-15:30 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 14-MAY-15:30 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-11:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-11:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-11:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-11:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-11:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-11:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-11:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 27-MAR-11:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 6296.69 | 0.00 | 01-JAN-00:10 | 647083.13 | 10-AUG-15:50 |
EnergyTransfer:Building | 2469.45 | 0.00 | 01-JAN-00:10 | 326212.04 | 09-JAN-08:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 370.78 | 0.00 | 01-JAN-00:10 | 27088.38 | 25-SEP-15:40 |
Heating:EnergyTransfer | 64.53 | 0.00 | 01-JAN-00:10 | 286465.48 | 09-JAN-08:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 64.53 | 0.00 | 01-JAN-00:10 | 286465.48 | 09-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 2404.92 | 0.00 | 01-JAN-00:10 | 234334.12 | 16-AUG-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 370.78 | 0.00 | 01-JAN-00:10 | 27088.38 | 25-SEP-15:40 |
General:Cooling:EnergyTransfer | 2404.92 | 0.00 | 01-JAN-00:10 | 234334.12 | 16-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 370.78 | 0.00 | 01-JAN-00:10 | 27088.38 | 25-SEP-15:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 191.37 | 0.00 | 01-JAN-00:10 | 132812.65 | 16-MAR-06:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.70 | 0.00 | 01-JAN-00:10 | 132812.65 | 16-MAR-06:50 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.70 | 0.00 | 01-JAN-00:10 | 132812.65 | 16-MAR-06:50 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 137.67 | 0.00 | 01-JAN-00:10 | 22355.48 | 21-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 137.67 | 0.00 | 01-JAN-00:10 | 22355.48 | 21-JUL-12:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 68.57 | 0.00 | 01-JAN-00:10 | 115875.88 | 09-JAN-08:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.13 | 0.00 | 01-JAN-00:10 | 115875.88 | 09-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.13 | 0.00 | 01-JAN-00:10 | 115875.88 | 09-JAN-08:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 64.44 | 0.00 | 01-JAN-00:10 | 7611.28 | 05-SEP-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 64.44 | 0.00 | 01-JAN-00:10 | 7611.28 | 05-SEP-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 79.93 | 0.00 | 01-JAN-00:10 | 45331.25 | 20-JAN-07:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.03 | 0.00 | 01-JAN-00:10 | 45331.25 | 20-JAN-07:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.03 | 0.00 | 01-JAN-00:10 | 45331.25 | 20-JAN-07:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 73.90 | 0.00 | 01-JAN-00:10 | 7674.85 | 31-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 73.90 | 0.00 | 01-JAN-00:10 | 7674.85 | 31-JUL-12:20 |
EnergyTransfer:Zone:CORE_MID | 262.56 | 0.00 | 01-JAN-00:10 | 21899.57 | 05-SEP-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 262.56 | 0.00 | 01-JAN-00:10 | 21899.57 | 05-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 262.56 | 0.00 | 01-JAN-00:10 | 21899.57 | 05-SEP-14:00 |
EnergyTransfer:Zone:CORE_TOP | 288.35 | 0.00 | 01-JAN-00:10 | 26162.53 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 288.35 | 0.00 | 01-JAN-00:10 | 26162.53 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 288.35 | 0.00 | 01-JAN-00:10 | 26162.53 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 108.00 | 0.00 | 01-JAN-00:10 | 12380.29 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2086.18 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2086.18 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 107.96 | 0.00 | 01-JAN-00:10 | 12380.29 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 107.96 | 0.00 | 01-JAN-00:10 | 12380.29 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 83.63 | 0.00 | 01-JAN-00:10 | 10272.17 | 21-JUL-10:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1030.83 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1030.83 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 83.61 | 0.00 | 01-JAN-00:10 | 10272.17 | 21-JUL-10:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 83.61 | 0.00 | 01-JAN-00:10 | 10272.17 | 21-JUL-10:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 126.42 | 0.00 | 01-JAN-00:10 | 14259.62 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 1787.80 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 1787.80 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 126.39 | 0.00 | 01-JAN-00:10 | 14259.62 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 126.39 | 0.00 | 01-JAN-00:10 | 14259.62 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 85.84 | 0.00 | 01-JAN-00:10 | 10712.81 | 09-JUN-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 1276.19 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 1276.19 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 85.82 | 0.00 | 01-JAN-00:10 | 10712.81 | 09-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 85.82 | 0.00 | 01-JAN-00:10 | 10712.81 | 09-JUN-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 105.34 | 0.00 | 01-JAN-00:10 | 11434.42 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 105.34 | 0.00 | 01-JAN-00:10 | 11434.42 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 105.34 | 0.00 | 01-JAN-00:10 | 11434.42 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 84.25 | 0.00 | 01-JAN-00:10 | 9715.14 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 265.79 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 265.79 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 84.25 | 0.00 | 01-JAN-00:10 | 9715.14 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 84.25 | 0.00 | 01-JAN-00:10 | 9715.14 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 150.75 | 0.00 | 01-JAN-00:10 | 24455.05 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.53 | 0.00 | 01-JAN-00:10 | 8230.06 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.53 | 0.00 | 01-JAN-00:10 | 8230.06 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 150.22 | 0.00 | 01-JAN-00:10 | 24455.05 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 150.22 | 0.00 | 01-JAN-00:10 | 24455.05 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 84.76 | 0.00 | 01-JAN-00:10 | 9698.77 | 10-AUG-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 381.96 | 21-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 381.96 | 21-JAN-07:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 84.76 | 0.00 | 01-JAN-00:10 | 9698.77 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 84.76 | 0.00 | 01-JAN-00:10 | 9698.77 | 10-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 99.99 | 0.00 | 01-JAN-00:10 | 11212.72 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 601.90 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 601.90 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 99.99 | 0.00 | 01-JAN-00:10 | 11212.72 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 99.99 | 0.00 | 01-JAN-00:10 | 11212.72 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 78.32 | 0.00 | 01-JAN-00:10 | 10127.06 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 746.79 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 746.79 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 78.31 | 0.00 | 01-JAN-00:10 | 10127.06 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 78.31 | 0.00 | 01-JAN-00:10 | 10127.06 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 119.37 | 0.00 | 01-JAN-00:10 | 13346.59 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 572.97 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 572.97 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 119.37 | 0.00 | 01-JAN-00:10 | 13346.59 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 119.37 | 0.00 | 01-JAN-00:10 | 13346.59 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 81.23 | 0.00 | 01-JAN-00:10 | 10029.09 | 09-JUN-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 813.70 | 21-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 813.70 | 21-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 81.21 | 0.00 | 01-JAN-00:10 | 10029.09 | 09-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 81.21 | 0.00 | 01-JAN-00:10 | 10029.09 | 09-JUN-15:30 |
PlantLoopHeatingDemand:Facility | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
EnergyTransfer:HVAC | 3794.52 | 0.00 | 01-JAN-00:10 | 419932.96 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.98 | 0.00 | 01-JAN-00:10 | 23552.60 | 20-JAN-07:10 |
CoolingCoils:EnergyTransfer | 3793.54 | 0.00 | 01-JAN-00:10 | 419932.96 | 10-AUG-16:00 |
EnergyTransfer:Plant | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
WaterSystems:EnergyTransfer | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -370.779 | 0.000 | 0.000 | 32.661 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -33.668 |
CORE_MID | 0.000 | 0.000 | 0.000 | -262.561 | 0.000 | 0.000 | 32.760 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 2.589 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -288.346 | 0.000 | 0.000 | 32.985 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 28.150 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.039 | -107.960 | 0.000 | 0.000 | 7.072 | 23.566 | 24.333 | 54.314 | 0.000 | 2.316 | 7.892 | 0.000 | -11.094 | 0.000 | -0.477 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.018 | -83.611 | 0.000 | 0.000 | 4.455 | 14.919 | 15.404 | 52.503 | 0.000 | 1.542 | 2.068 | 0.000 | -6.968 | 0.000 | -0.330 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.031 | -126.387 | 0.000 | 0.000 | 7.016 | 23.566 | 24.332 | 81.448 | 0.000 | 2.283 | 0.001 | 0.000 | -11.202 | 0.000 | -0.551 | -0.535 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.025 | -85.817 | 0.000 | 0.000 | 4.528 | 14.918 | 15.403 | 53.207 | 0.000 | 1.567 | 3.916 | 0.000 | -7.420 | 0.000 | -0.328 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -105.338 | 0.000 | 0.000 | 6.966 | 23.566 | 24.333 | 53.564 | 0.000 | 1.232 | 9.186 | 0.000 | -13.184 | 0.000 | -0.325 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -84.249 | 0.000 | 0.000 | 4.407 | 14.919 | 15.404 | 52.225 | 0.000 | 0.825 | 4.973 | 0.000 | -8.283 | 0.000 | -0.222 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.527 | -150.220 | 0.000 | 0.000 | 6.914 | 23.566 | 24.332 | 80.868 | 0.000 | 28.377 | 3.235 | 0.000 | -13.597 | 0.000 | -4.002 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.002 | -84.759 | 0.000 | 0.000 | 4.448 | 14.918 | 15.403 | 53.017 | 0.000 | 0.825 | 5.256 | 0.000 | -8.889 | 0.000 | -0.221 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.003 | -99.989 | 0.000 | 0.000 | 6.991 | 23.566 | 24.333 | 54.220 | 0.000 | 1.911 | 1.873 | 0.000 | -12.439 | 0.000 | -0.468 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.007 | -78.309 | 0.000 | 0.000 | 3.270 | 14.919 | 15.404 | 52.441 | 0.000 | 1.282 | 0.000 | 0.000 | -7.662 | 0.000 | -0.314 | -1.037 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.003 | -119.366 | 0.000 | 0.000 | 6.957 | 23.566 | 24.332 | 81.524 | 0.000 | 1.888 | 0.001 | 0.000 | -12.438 | 0.000 | -0.527 | -5.940 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.019 | -81.206 | 0.000 | 0.000 | 4.479 | 14.918 | 15.403 | 53.285 | 0.000 | 1.292 | 0.366 | 0.000 | -8.242 | 0.000 | -0.315 | -0.000 |
TOPFLOOR_PLENUM | 1.294 | -138.025 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.067 | 134.404 | 0.000 | 0.000 | 0.000 | -0.740 | -0.001 |
MIDFLOOR_PLENUM | 0.386 | -64.847 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.991 | 62.364 | 0.000 | 0.000 | 0.000 | -0.894 | 0.000 |
FIRSTFLOOR_PLENUM | 0.545 | -74.796 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.306 | 72.729 | 0.000 | 0.000 | 0.000 | -0.784 | 0.000 |
Total Facility | 2.224 | -277.667 | 0.675 | -2128.895 | 0.000 | 0.000 | 165.910 | 566.263 | 729.266 | 722.616 | 0.000 | 53.705 | 339.003 | 0.000 | -121.418 | 0.000 | -10.499 | -41.187 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 16-MAY-04:01 | 0.00 | 0.00 | 0.00 | -55353.75 | 0.00 | 0.00 | 0.00 | 1084.51 | 5966.06 | 0.00 | 0.00 | 0.00 | 48303.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 25-SEP-04:01 | 0.00 | 0.00 | 0.00 | -44611.04 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 41084.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-SEP-04:01 | 0.00 | 0.00 | 0.00 | -53978.90 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 50452.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-SEP-12:11 | 0.00 | 0.00 | 0.00 | -23715.89 | 0.00 | 0.00 | 23.77 | 114.31 | 478.42 | 5725.04 | 0.00 | 383.42 | 16990.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-10:11 | 0.00 | 0.00 | 0.00 | -19855.16 | 0.00 | 0.00 | 12.34 | 72.37 | 302.86 | 7200.77 | 0.00 | 302.12 | 11964.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 29-OCT-12:51 | 0.00 | 0.00 | 0.00 | -28042.02 | 0.00 | 0.00 | 20.89 | 114.31 | 478.41 | 11555.63 | 0.00 | 86.59 | 15786.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-SEP-16:11 | 0.00 | 0.00 | 0.00 | -21141.00 | 0.00 | 0.00 | 10.71 | 72.36 | 302.86 | 7102.06 | 0.00 | 389.75 | 13263.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-SEP-14:21 | 0.00 | 0.00 | 0.00 | -20603.51 | 0.00 | 0.00 | 24.07 | 114.31 | 478.42 | 5786.91 | 0.00 | 319.01 | 13880.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-09:41 | 0.00 | 0.00 | 0.00 | -17777.69 | 0.00 | 0.00 | 13.43 | 72.37 | 302.86 | 7140.68 | 0.00 | 130.23 | 10118.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | -24454.95 | 0.00 | 0.00 | 269.86 | 2057.62 | 1275.77 | 9290.80 | 0.00 | 20247.59 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8686.68 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:21 | 0.00 | 0.00 | 0.00 | -20048.09 | 0.00 | 0.00 | 12.18 | 72.36 | 302.86 | 7100.16 | 0.00 | 195.85 | 12364.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 30-JUL-13:32 | 0.00 | 0.00 | 0.00 | -19299.38 | 0.00 | 0.00 | 22.82 | 114.31 | 478.42 | 6960.66 | 0.00 | 713.71 | 11009.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 07-MAY-10:11 | 0.00 | 0.00 | 0.00 | -18179.91 | 0.00 | 0.00 | 13.66 | 72.37 | 302.86 | 7247.42 | 0.00 | 92.18 | 10451.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 08-OCT-11:52 | 0.00 | 0.00 | 0.00 | -23188.61 | 0.00 | 0.00 | 23.15 | 114.31 | 478.41 | 9407.07 | 0.00 | 139.07 | 13026.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14-MAY-16:01 | 0.00 | 0.00 | 0.00 | -19350.81 | 0.00 | 0.00 | 13.66 | 72.36 | 302.86 | 6362.87 | 0.00 | 187.57 | 12411.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-12:01 | 0.00 | -22507.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.80 | 22266.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 19-JAN-07:03 | 0.00 | -13014.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13148.28 | 0.00 | -0.00 | 0.00 | -134.23 | 0.00 |
FIRSTFLOOR_PLENUM | 04-AUG-12:06 | 0.00 | -10055.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.73 | 9778.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-04:01 | 0.00 | 13071.65 | 0.00 | -326580.79 | 0.00 | 0.00 | 0.00 | 5493.69 | 15894.33 | 0.00 | 0.00 | 657.69 | 293276.72 | 0.00 | -1813.28 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 20-JAN-07:03 | 0.00 | 0.00 | 7038.69 | 0.00 | 0.00 | 0.00 | 193.30 | 685.87 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2104.75 | 0.00 | -31.27 | -6419.73 |
PERIMETER_TOP_ZN_2 | 20-JAN-07:03 | 0.00 | 0.00 | 3897.71 | 0.00 | 0.00 | 0.00 | 122.37 | 434.22 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -136.61 | 0.00 | -20.77 | -4700.72 |
PERIMETER_TOP_ZN_1 | 20-JAN-07:03 | 0.00 | 0.00 | 6498.18 | 0.00 | 0.00 | 0.00 | 193.30 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1441.07 | 0.00 | -31.22 | -6542.94 |
PERIMETER_TOP_ZN_4 | 20-JAN-07:03 | 0.00 | 0.00 | 4153.19 | 0.00 | 0.00 | 0.00 | 122.37 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1401.56 | 0.00 | -20.71 | -3691.28 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 20-JAN-07:03 | 0.00 | 0.00 | 1063.29 | 0.00 | 0.00 | 0.00 | 117.73 | 434.22 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -349.40 | 0.00 | -11.72 | -1657.93 |
PERIMETER_BOT_ZN_1 | 20-JAN-07:03 | 0.00 | 0.00 | 10389.79 | 0.00 | 0.00 | 0.00 | 187.82 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 1350.95 | 0.00 | -1765.73 | 0.00 | -11486.59 | 0.00 |
PERIMETER_BOT_ZN_4 | 21-JAN-07:03 | 0.00 | 0.00 | 1359.31 | 0.00 | 0.00 | 0.00 | 59.13 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1485.29 | 0.00 | -8.37 | -473.32 |
PERIMETER_MID_ZN_3 | 20-JAN-07:03 | 0.00 | 0.00 | 2407.53 | 0.00 | 0.00 | 0.00 | 189.23 | 685.87 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2320.12 | 0.00 | -26.26 | -1574.14 |
PERIMETER_MID_ZN_2 | 20-JAN-07:03 | 0.00 | 0.00 | 2986.97 | 0.00 | 0.00 | 0.00 | 122.30 | 434.22 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -232.17 | 0.00 | -17.28 | -3697.84 |
PERIMETER_MID_ZN_1 | 20-JAN-07:03 | 0.00 | 0.00 | 2291.77 | 0.00 | 0.00 | 0.00 | 189.72 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1647.14 | 0.00 | -26.21 | -2131.90 |
PERIMETER_MID_ZN_4 | 21-JAN-07:03 | 0.00 | 0.00 | 3254.99 | 0.00 | 0.00 | 0.00 | 61.14 | 144.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1366.01 | 0.00 | -12.37 | -2486.28 |
TOPFLOOR_PLENUM | 25-APR-05:02 | 9590.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1.78 | -9588.41 |
MIDFLOOR_PLENUM | 30-JUL-13:32 | 6610.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.63 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7786.95 |
FIRSTFLOOR_PLENUM | 15-SEP-04:01 | 6513.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6567.25 |
Total Facility | 20-JAN-07:03 | -58815.26 | 39219.27 | 45172.03 | -39219.27 | 0.00 | 0.00 | 4223.27 | 16481.06 | 22777.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17032.64 | 0.00 | -11853.94 | -951.62 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 7.7756 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 7.2482 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 7.2774 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.6938 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 8.5510 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.3277 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.3327 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.3327 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.1832 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.1832 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.5653 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.5653 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 3.3906 | 3.3906 | 1.0172 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.8377 | 2.8377 | 0.8513 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 3.4923 | 3.4923 | 1.0477 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.3416 | 1.3416 | 0.4025 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0341 | 1.0341 | 0.3102 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.4803 | 1.4803 | 0.4441 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.2026 | 1.2026 | 0.3608 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.1254 | 1.1254 | 0.3376 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9562 | 0.9562 | 0.2869 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.2687 | 1.2687 | 0.3806 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0347 | 1.0347 | 0.3104 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.1273 | 1.1273 | 0.3382 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.9716 | 0.9716 | 0.2915 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.2737 | 1.2737 | 0.3821 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0671 | 1.0671 | 0.3201 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 7.7756 | 7.2482 | 7.7756 | 2.3327 | 0.0000 | 1.0000 |
PACU_VAV_MID | 7.2774 | 6.6938 | 7.2774 | 2.1832 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 8.5510 | 8.3277 | 8.5510 | 2.5653 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0172 | 4.4078 | 1.0172 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.8513 | 3.6890 | 0.8513 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.0477 | 4.5400 | 1.0477 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.4025 | 1.7441 | 0.4025 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3102 | 1.3444 | 0.3102 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.4441 | 1.9243 | 0.4441 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3608 | 1.5634 | 0.3608 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3376 | 1.4630 | 0.3376 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2869 | 1.2431 | 0.2869 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3806 | 1.6493 | 0.3806 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3104 | 1.3451 | 0.3104 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3382 | 1.4655 | 0.3382 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2915 | 1.2631 | 0.2915 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3821 | 1.6558 | 0.3821 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3201 | 1.3873 | 0.3201 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.3327 | 2.3327 | 10.1082 | 2.3327 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.1832 | 2.1832 | 9.4606 | 2.1832 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.5653 | 2.5653 | 11.1162 | 2.5653 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 387.50 |
Number of hours not met | 387.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.98 | 23552.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1033.46 | 142390.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 236.30 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 276.71 | 35138.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 35.45 | 4616.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 2906.09 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2906.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.20 |
Space Cooling | 207.43 |
Fans (All) | 55.54 |
Service Water Heating | 7.12 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 583.30 |
Subtotal | 583.30 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.49 |
Space Heating | 0.03 |
Space Cooling | 35.56 |
Fans (All) | 9.52 |
Service Water Heating | 1.22 |
Receptacle Equipment | 25.09 |
Miscellaneous | 9.08 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7703.67 | 1056.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8717.83 | 42.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8033.33 | 726.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7985.33 | 774.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7977.83 | 782.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7997.50 | 762.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8149.50 | 610.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8057.83 | 702.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7944.17 | 815.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8011.33 | 748.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7979.17 | 780.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7968.00 | 792.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7924.50 | 835.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7936.50 | 823.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8170.83 | 589.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8656.83 | 103.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8718.00 | 42.00 | 0.00 | 0.00 | 0.00 |
Min | 7703.67 | 25.00 | 0.00 | 0.00 | 0.00 |
Max | 8735.00 | 1056.33 | 0.00 | 0.00 | 0.00 |
Average | 8148.18 | 611.82 | 0.00 | 0.00 | 0.00 |
Sum | 146667.17 | 11012.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 127986.00 | 318.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128299.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24846.50 | 62.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128299.00 | 318.00 | 0.00 | 0.00 | 0.00 |
Average | 34121.55 | 21.79 | 0.00 | 0.00 | 0.00 |
Sum | 614187.83 | 392.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 6861.00 | 1899.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7441.33 | 1318.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7563.33 | 1196.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6753.17 | 2006.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6779.67 | 1980.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6725.67 | 2034.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6896.67 | 1863.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6732.67 | 2027.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6800.67 | 1959.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6048.00 | 2712.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6861.83 | 1898.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6592.50 | 2167.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6680.83 | 2079.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6528.83 | 2231.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6729.50 | 2030.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4908.17 | 3851.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 6433.67 | 2326.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6383.83 | 2376.17 | 0.00 | 0.00 | 0.00 |
Min | 4908.17 | 1196.67 | 0.00 | 0.00 | 0.00 |
Max | 7563.33 | 3851.83 | 0.00 | 0.00 | 0.00 |
Average | 6651.19 | 2108.81 | 0.00 | 0.00 | 0.00 |
Sum | 119721.33 | 37958.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127472.17 | 831.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127776.33 | 527.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127697.83 | 606.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24895.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24901.17 | 7.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24900.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 22611.67 | 2297.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24884.83 | 24.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24896.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127776.33 | 2297.33 | 0.00 | 0.00 | 0.00 |
Average | 33902.79 | 240.55 | 0.00 | 0.00 | 0.00 |
Sum | 610250.17 | 4329.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249325E+11 | 49699.56 | 02-JAN-06:12 | 13.00 | 10.85 | 0.199565E+10 | 2606.69 | 02-JAN-14:09 | 22.00 | 14.69 |
February | 0.234275E+11 | 49656.73 | 21-FEB-06:12 | 13.90 | 13.23 | 0.181081E+10 | 2606.69 | 02-FEB-10:30 | 13.90 | 13.23 |
March | 0.289966E+11 | 54495.22 | 28-MAR-04:02 | 26.08 | 14.62 | 0.216207E+10 | 2606.69 | 01-MAR-10:50 | 26.08 | 14.62 |
April | 0.287738E+11 | 55023.34 | 17-APR-04:02 | 24.33 | 19.27 | 0.191967E+10 | 2606.69 | 07-APR-09:30 | 24.33 | 19.27 |
May | 0.340775E+11 | 55364.69 | 16-MAY-04:01 | 25.00 | 22.44 | 0.207823E+10 | 2606.69 | 01-MAY-09:30 | 25.00 | 22.44 |
June | 0.344234E+11 | 54794.77 | 07-JUN-04:01 | 24.83 | 21.13 | 0.207049E+10 | 2606.69 | 19-JUN-09:00 | 34.80 | 25.73 |
July | 0.352167E+11 | 52027.14 | 03-JUL-04:01 | 29.00 | 16.97 | 0.192261E+10 | 2606.69 | 20-JUL-13:09 | 38.83 | 30.79 |
August | 0.375178E+11 | 46105.72 | 15-AUG-04:01 | 29.75 | 23.27 | 0.215767E+10 | 2606.69 | 09-AUG-13:30 | 29.75 | 23.27 |
September | 0.339241E+11 | 54263.45 | 30-SEP-04:01 | 24.52 | 21.72 | 0.191763E+10 | 2606.69 | 06-SEP-13:09 | 24.52 | 21.72 |
October | 0.333967E+11 | 54374.25 | 26-OCT-04:02 | 24.17 | 22.00 | 0.199536E+10 | 2606.69 | 13-OCT-13:50 | 24.17 | 22.00 |
November | 0.299635E+11 | 54553.82 | 03-NOV-04:02 | 24.08 | 22.27 | 0.197702E+10 | 2606.69 | 10-NOV-14:00 | 31.00 | 20.42 |
December | 0.261269E+11 | 49706.91 | 04-DEC-06:12 | 17.40 | 16.34 | 0.192604E+10 | 2606.69 | 27-DEC-10:30 | 22.55 | 15.82 |
Annual Sum or Average | 0.370777E+12 | 0.239333E+11 | ||||||||
Minimum of Months | 0.234275E+11 | 46105.72 | 13.00 | 10.85 | 0.181081E+10 | 2606.69 | 13.90 | 13.23 | ||
Maximum of Months | 0.375178E+11 | 55364.69 | 29.75 | 23.27 | 0.216207E+10 | 2606.69 | 38.83 | 30.79 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422347E+10 | 8607.34 | 31-JAN-13:50 | 23.15 | 16.15 | 0.00 | 0.00 | 01-JAN-00:10 | 23.15 | 16.15 |
February | 0.529130E+10 | 12706.26 | 07-FEB-14:05 | 30.50 | 20.52 | 0.00 | 0.00 | 01-FEB-00:10 | 30.50 | 20.52 |
March | 0.817487E+10 | 16836.35 | 27-MAR-13:05 | 35.83 | 19.71 | 0.00 | 0.00 | 01-MAR-00:10 | 35.83 | 19.71 |
April | 0.105538E+11 | 19279.02 | 28-APR-12:01 | 41.12 | 20.13 | 0.00 | 0.00 | 01-APR-00:10 | 41.12 | 20.13 |
May | 0.156762E+11 | 20628.30 | 29-MAY-12:52 | 33.40 | 29.11 | 0.00 | 0.00 | 01-MAY-00:10 | 33.40 | 29.11 |
June | 0.168192E+11 | 20373.78 | 12-JUN-13:00 | 40.90 | 27.13 | 0.00 | 0.00 | 01-JUN-00:10 | 40.90 | 27.13 |
July | 0.184026E+11 | 22507.43 | 21-JUL-12:01 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.189885E+11 | 22267.29 | 16-AUG-13:05 | 44.17 | 25.68 | 0.00 | 0.00 | 01-AUG-00:10 | 44.17 | 25.68 |
September | 0.148136E+11 | 20400.32 | 04-SEP-12:11 | 40.87 | 24.05 | 0.00 | 0.00 | 01-SEP-00:10 | 40.87 | 24.05 |
October | 0.118529E+11 | 17461.32 | 04-OCT-13:05 | 36.50 | 20.99 | 0.00 | 0.00 | 01-OCT-00:10 | 36.50 | 20.99 |
November | 0.792921E+10 | 13908.83 | 06-NOV-13:03 | 32.42 | 19.73 | 0.00 | 0.00 | 01-NOV-00:10 | 32.42 | 19.73 |
December | 0.494201E+10 | 10183.65 | 04-DEC-13:10 | 27.83 | 21.18 | 0.00 | 0.00 | 01-DEC-00:10 | 27.83 | 21.18 |
Annual Sum or Average | 0.137668E+12 | 0.00 | ||||||||
Minimum of Months | 0.422347E+10 | 8607.34 | 23.15 | 16.15 | 0.00 | 0.00 | 23.15 | 16.15 | ||
Maximum of Months | 0.189885E+11 | 22507.43 | 45.38 | 29.11 | 0.00 | 0.00 | 45.38 | 29.11 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216133E+10 | 3338.07 | 28-JAN-06:25 | 13.70 | 12.11 | 0.00 | 0.00 | 01-JAN-00:10 | 13.70 | 12.11 |
February | 0.250386E+10 | 3816.33 | 06-FEB-15:30 | 31.95 | 17.43 | 0.00 | 0.00 | 01-FEB-00:10 | 31.95 | 17.43 |
March | 0.380631E+10 | 5425.29 | 27-MAR-15:30 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.461857E+10 | 5884.90 | 28-APR-12:04 | 41.12 | 20.13 | 0.00 | 0.00 | 01-APR-00:10 | 41.12 | 20.13 |
May | 0.702391E+10 | 6801.86 | 30-MAY-15:30 | 38.75 | 25.65 | 0.00 | 0.00 | 01-MAY-00:10 | 38.75 | 25.65 |
June | 0.749053E+10 | 7268.57 | 12-JUN-12:04 | 42.65 | 25.06 | 0.00 | 0.00 | 01-JUN-00:10 | 42.65 | 25.06 |
July | 0.795326E+10 | 7522.38 | 31-JUL-12:04 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.849485E+10 | 7073.06 | 16-AUG-12:03 | 45.70 | 25.45 | 0.00 | 0.00 | 01-AUG-00:10 | 45.70 | 25.45 |
September | 0.708984E+10 | 7788.07 | 05-SEP-12:04 | 40.98 | 24.12 | 0.00 | 0.00 | 01-SEP-00:10 | 40.98 | 24.12 |
October | 0.617479E+10 | 6598.57 | 10-OCT-14:20 | 34.67 | 19.98 | 0.00 | 0.00 | 01-OCT-00:10 | 34.67 | 19.98 |
November | 0.436247E+10 | 5247.93 | 06-NOV-15:20 | 31.80 | 21.81 | 0.00 | 0.00 | 01-NOV-00:10 | 31.80 | 21.81 |
December | 0.276451E+10 | 3219.33 | 13-DEC-07:03 | 15.25 | 12.91 | 0.00 | 0.00 | 01-DEC-00:10 | 15.25 | 12.91 |
Annual Sum or Average | 0.644442E+11 | 0.00 | ||||||||
Minimum of Months | 0.216133E+10 | 3219.33 | 13.70 | 12.11 | 0.00 | 0.00 | 13.70 | 12.11 | ||
Maximum of Months | 0.849485E+10 | 7788.07 | 45.70 | 25.84 | 0.00 | 0.00 | 45.70 | 25.84 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312123E+10 | 4510.70 | 02-JAN-06:17 | 13.00 | 10.85 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 10.85 |
February | 0.330345E+10 | 4668.15 | 06-FEB-15:30 | 31.95 | 17.43 | 0.00 | 0.00 | 01-FEB-00:10 | 31.95 | 17.43 |
March | 0.463784E+10 | 7272.69 | 27-MAR-12:06 | 37.08 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 37.08 | 19.46 |
April | 0.535894E+10 | 8111.90 | 28-APR-12:06 | 41.12 | 20.13 | 0.00 | 0.00 | 01-APR-00:10 | 41.12 | 20.13 |
May | 0.760869E+10 | 8140.99 | 09-MAY-12:05 | 41.02 | 19.49 | 0.00 | 0.00 | 01-MAY-00:10 | 41.02 | 19.49 |
June | 0.801427E+10 | 9546.24 | 12-JUN-12:05 | 42.65 | 25.06 | 0.00 | 0.00 | 01-JUN-00:10 | 42.65 | 25.06 |
July | 0.841394E+10 | 9570.83 | 31-JUL-12:06 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.905264E+10 | 10055.94 | 04-AUG-12:06 | 44.92 | 24.74 | 0.00 | 0.00 | 01-AUG-00:10 | 44.92 | 24.74 |
September | 0.784700E+10 | 9362.61 | 05-SEP-12:08 | 40.98 | 24.12 | 0.00 | 0.00 | 01-SEP-00:10 | 40.98 | 24.12 |
October | 0.721952E+10 | 7963.75 | 04-OCT-12:07 | 37.77 | 20.04 | 0.00 | 0.00 | 01-OCT-00:10 | 37.77 | 20.04 |
November | 0.560575E+10 | 6564.92 | 06-NOV-13:07 | 32.42 | 19.73 | 0.00 | 0.00 | 01-NOV-00:10 | 32.42 | 19.73 |
December | 0.371836E+10 | 4419.32 | 04-DEC-15:10 | 26.87 | 21.39 | 0.00 | 0.00 | 01-DEC-00:10 | 26.87 | 21.39 |
Annual Sum or Average | 0.739016E+11 | 0.00 | ||||||||
Minimum of Months | 0.312123E+10 | 4419.32 | 13.00 | 10.85 | 0.00 | 0.00 | 13.00 | 10.85 | ||
Maximum of Months | 0.905264E+10 | 10055.94 | 44.92 | 25.84 | 0.00 | 0.00 | 44.92 | 25.84 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152450E+11 | 16310.58 | 30-JAN-17:00 | 22.00 | 19.30 | 0.197082E+10 | 2606.69 | 09-JAN-14:30 | 22.00 | 19.30 |
February | 0.150118E+11 | 18130.57 | 08-FEB-16:20 | 25.00 | 20.42 | 0.179351E+10 | 2606.69 | 07-FEB-14:20 | 25.00 | 20.42 |
March | 0.195233E+11 | 43349.20 | 28-MAR-04:02 | 26.08 | 14.62 | 0.215017E+10 | 2606.69 | 08-MAR-14:39 | 26.08 | 14.62 |
April | 0.203085E+11 | 43631.33 | 29-APR-04:01 | 25.83 | 16.41 | 0.191321E+10 | 2606.69 | 03-APR-09:20 | 25.83 | 16.41 |
May | 0.254453E+11 | 44318.57 | 16-MAY-04:01 | 25.00 | 22.44 | 0.207521E+10 | 2606.69 | 03-MAY-13:20 | 25.00 | 22.44 |
June | 0.260551E+11 | 44169.50 | 07-JUN-04:01 | 24.83 | 21.13 | 0.206824E+10 | 2606.69 | 01-JUN-09:39 | 24.83 | 21.13 |
July | 0.270132E+11 | 41900.09 | 03-JUL-04:01 | 29.00 | 16.97 | 0.192042E+10 | 2606.69 | 03-JUL-13:39 | 40.63 | 20.74 |
August | 0.286342E+11 | 35900.92 | 28-AUG-04:02 | 31.33 | 27.40 | 0.215592E+10 | 2606.69 | 07-AUG-09:50 | 31.33 | 27.40 |
September | 0.248596E+11 | 44618.16 | 25-SEP-04:01 | 24.17 | 23.10 | 0.191591E+10 | 2606.69 | 01-SEP-13:50 | 24.17 | 23.10 |
October | 0.237352E+11 | 44474.42 | 23-OCT-04:01 | 25.42 | 23.19 | 0.199249E+10 | 2606.69 | 04-OCT-13:39 | 25.42 | 23.19 |
November | 0.202101E+11 | 43544.48 | 03-NOV-04:02 | 24.08 | 22.27 | 0.197080E+10 | 2606.69 | 08-NOV-14:00 | 31.00 | 20.84 |
December | 0.165182E+11 | 18101.61 | 12-DEC-17:00 | 23.80 | 16.27 | 0.190740E+10 | 2606.69 | 04-DEC-14:30 | 23.80 | 16.27 |
Annual Sum or Average | 0.262560E+12 | 0.238341E+11 | ||||||||
Minimum of Months | 0.150118E+11 | 16310.58 | 22.00 | 14.62 | 0.179351E+10 | 2606.69 | 22.00 | 14.62 | ||
Maximum of Months | 0.286342E+11 | 44618.16 | 31.33 | 27.40 | 0.215592E+10 | 2606.69 | 40.63 | 27.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151022E+11 | 17053.28 | 31-JAN-15:40 | 22.73 | 16.59 | 0.190171E+10 | 2606.69 | 23-JAN-14:39 | 22.73 | 16.59 |
February | 0.154149E+11 | 20326.26 | 08-FEB-14:50 | 28.50 | 20.28 | 0.175070E+10 | 2606.69 | 15-FEB-14:39 | 24.67 | 17.94 |
March | 0.205228E+11 | 50984.85 | 28-MAR-05:01 | 25.67 | 14.74 | 0.212221E+10 | 2606.69 | 22-MAR-13:00 | 25.67 | 14.74 |
April | 0.221448E+11 | 51688.30 | 17-APR-05:01 | 24.00 | 19.24 | 0.190124E+10 | 2606.69 | 03-APR-13:09 | 24.00 | 19.24 |
May | 0.290238E+11 | 53322.84 | 08-MAY-04:01 | 26.67 | 16.98 | 0.207347E+10 | 2606.69 | 01-MAY-09:00 | 26.67 | 16.98 |
June | 0.300877E+11 | 53542.52 | 07-JUN-04:01 | 24.83 | 21.13 | 0.206767E+10 | 2606.69 | 01-JUN-13:09 | 24.83 | 21.13 |
July | 0.319818E+11 | 52819.49 | 03-JUL-04:01 | 29.00 | 16.97 | 0.192050E+10 | 2606.69 | 20-JUL-13:09 | 38.83 | 30.79 |
August | 0.335235E+11 | 45784.55 | 15-AUG-04:01 | 29.75 | 23.27 | 0.215552E+10 | 2606.69 | 02-AUG-13:39 | 29.75 | 23.27 |
September | 0.280211E+11 | 53989.34 | 25-SEP-04:01 | 24.17 | 23.10 | 0.191475E+10 | 2606.69 | 12-SEP-13:50 | 24.17 | 23.10 |
October | 0.255000E+11 | 53605.73 | 16-OCT-04:01 | 25.83 | 23.26 | 0.198754E+10 | 2606.69 | 02-OCT-13:09 | 25.83 | 23.26 |
November | 0.206318E+11 | 51378.05 | 03-NOV-05:02 | 23.83 | 22.46 | 0.195403E+10 | 2606.69 | 15-NOV-14:00 | 29.00 | 20.82 |
December | 0.163907E+11 | 19185.26 | 12-DEC-15:00 | 24.00 | 16.60 | 0.185971E+10 | 2606.69 | 27-DEC-14:39 | 22.33 | 15.41 |
Annual Sum or Average | 0.288345E+12 | 0.236091E+11 | ||||||||
Minimum of Months | 0.151022E+11 | 17053.28 | 22.73 | 14.74 | 0.175070E+10 | 2606.69 | 22.33 | 14.74 | ||
Maximum of Months | 0.335235E+11 | 53989.34 | 29.75 | 23.27 | 0.215552E+10 | 2606.69 | 38.83 | 30.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437150E+10 | 4894.84 | 23-JAN-14:10 | 27.50 | 16.66 | 0.366416E+09 | 549.51 | 23-JAN-14:00 | 25.00 | 16.89 |
February | 0.464726E+10 | 7255.56 | 06-FEB-15:00 | 32.50 | 17.28 | 0.347725E+09 | 549.51 | 09-FEB-14:00 | 23.00 | 20.24 |
March | 0.658703E+10 | 10974.75 | 02-MAR-06:02 | 28.80 | 15.43 | 0.429613E+09 | 549.51 | 01-MAR-14:30 | 28.80 | 15.43 |
April | 0.782690E+10 | 11241.15 | 29-APR-05:01 | 25.00 | 16.37 | 0.393003E+09 | 549.51 | 06-APR-13:09 | 25.00 | 16.37 |
May | 0.115469E+11 | 21963.81 | 29-MAY-12:52 | 33.40 | 29.11 | 0.436398E+09 | 549.51 | 18-MAY-13:50 | 33.40 | 29.11 |
June | 0.126131E+11 | 20804.97 | 11-JUN-15:22 | 36.70 | 27.29 | 0.436175E+09 | 549.51 | 08-JUN-13:20 | 36.70 | 27.29 |
July | 0.140188E+11 | 23316.42 | 23-JUL-10:11 | 40.07 | 23.79 | 0.406116E+09 | 549.51 | 13-JUL-13:09 | 40.07 | 23.79 |
August | 0.144675E+11 | 21864.53 | 06-AUG-16:42 | 40.02 | 26.09 | 0.455279E+09 | 549.51 | 04-AUG-13:09 | 40.02 | 26.09 |
September | 0.111275E+11 | 23727.09 | 04-SEP-12:11 | 40.87 | 24.05 | 0.403135E+09 | 549.51 | 07-SEP-09:00 | 35.90 | 27.72 |
October | 0.915468E+10 | 18876.86 | 08-OCT-13:52 | 32.90 | 26.14 | 0.415446E+09 | 549.51 | 06-OCT-13:39 | 32.90 | 26.14 |
November | 0.668433E+10 | 7990.39 | 01-NOV-14:00 | 33.00 | 26.24 | 0.402141E+09 | 549.51 | 21-NOV-14:39 | 26.00 | 18.89 |
December | 0.491656E+10 | 5681.25 | 03-DEC-12:22 | 28.90 | 18.13 | 0.366762E+09 | 549.51 | 05-DEC-14:30 | 26.00 | 22.83 |
Annual Sum or Average | 0.107962E+12 | 0.485821E+10 | ||||||||
Minimum of Months | 0.437150E+10 | 4894.84 | 25.00 | 15.43 | 0.347725E+09 | 549.51 | 23.00 | 15.43 | ||
Maximum of Months | 0.144675E+11 | 23727.09 | 40.87 | 29.11 | 0.455279E+09 | 549.51 | 40.07 | 29.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344164E+10 | 4081.43 | 29-JAN-10:52 | 26.00 | 18.88 | 0.237182E+09 | 347.89 | 23-JAN-14:39 | 26.00 | 18.88 |
February | 0.361846E+10 | 5015.18 | 05-FEB-14:42 | 31.93 | 19.38 | 0.225211E+09 | 347.89 | 06-FEB-14:09 | 32.08 | 17.23 |
March | 0.513908E+10 | 7944.88 | 27-MAR-10:50 | 37.50 | 18.71 | 0.275394E+09 | 347.89 | 13-MAR-13:50 | 37.50 | 18.71 |
April | 0.629053E+10 | 10004.82 | 23-APR-10:32 | 32.90 | 16.63 | 0.250471E+09 | 347.89 | 10-APR-13:20 | 32.90 | 16.63 |
May | 0.903556E+10 | 18204.91 | 21-MAY-10:12 | 38.00 | 20.42 | 0.276618E+09 | 347.89 | 05-MAY-13:00 | 38.00 | 20.42 |
June | 0.954052E+10 | 15589.55 | 11-JUN-10:02 | 38.17 | 26.68 | 0.276047E+09 | 347.89 | 01-JUN-13:00 | 38.17 | 26.68 |
July | 0.105381E+11 | 19869.24 | 23-JUL-10:11 | 40.07 | 23.79 | 0.256980E+09 | 347.89 | 13-JUL-13:09 | 40.07 | 23.79 |
August | 0.110699E+11 | 18476.28 | 27-AUG-09:02 | 35.25 | 26.71 | 0.288093E+09 | 347.89 | 18-AUG-13:50 | 35.25 | 26.71 |
September | 0.868178E+10 | 19376.06 | 04-SEP-09:31 | 37.27 | 22.65 | 0.255391E+09 | 347.89 | 06-SEP-13:30 | 37.85 | 27.56 |
October | 0.723554E+10 | 17839.78 | 08-OCT-09:52 | 32.00 | 26.27 | 0.264023E+09 | 347.89 | 20-OCT-13:50 | 34.00 | 18.68 |
November | 0.523112E+10 | 6681.41 | 05-NOV-09:07 | 27.40 | 18.90 | 0.257583E+09 | 347.89 | 16-NOV-14:09 | 30.83 | 19.30 |
December | 0.378935E+10 | 4599.79 | 03-DEC-12:22 | 28.90 | 18.13 | 0.235404E+09 | 347.89 | 04-DEC-14:20 | 27.00 | 21.10 |
Annual Sum or Average | 0.836116E+11 | 0.309840E+10 | ||||||||
Minimum of Months | 0.344164E+10 | 4081.43 | 26.00 | 16.63 | 0.225211E+09 | 347.89 | 26.00 | 16.63 | ||
Maximum of Months | 0.110699E+11 | 19869.24 | 40.07 | 26.71 | 0.288093E+09 | 347.89 | 40.07 | 27.56 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.634815E+10 | 10581.82 | 22-JAN-14:12 | 26.00 | 16.21 | 0.390556E+09 | 549.51 | 03-JAN-14:20 | 26.00 | 16.21 |
February | 0.659524E+10 | 25572.52 | 05-FEB-14:42 | 31.93 | 19.38 | 0.359038E+09 | 549.51 | 01-FEB-14:30 | 31.93 | 19.38 |
March | 0.842921E+10 | 14672.58 | 26-MAR-13:23 | 34.00 | 18.36 | 0.432948E+09 | 549.51 | 13-MAR-13:50 | 34.00 | 18.36 |
April | 0.887556E+10 | 15026.40 | 30-APR-13:13 | 36.07 | 21.81 | 0.391616E+09 | 549.51 | 06-APR-13:50 | 36.07 | 21.81 |
May | 0.117743E+11 | 24060.48 | 29-MAY-12:52 | 33.40 | 29.11 | 0.434741E+09 | 549.51 | 02-MAY-13:09 | 33.40 | 29.11 |
June | 0.123611E+11 | 19460.53 | 26-JUN-04:01 | 29.33 | 25.25 | 0.434975E+09 | 549.51 | 06-JUN-13:39 | 29.33 | 25.25 |
July | 0.140748E+11 | 25343.42 | 30-JUL-12:12 | 43.50 | 23.79 | 0.405424E+09 | 549.51 | 13-JUL-13:09 | 43.50 | 23.79 |
August | 0.153317E+11 | 23746.99 | 27-AUG-14:21 | 37.00 | 28.96 | 0.454783E+09 | 549.51 | 04-AUG-13:09 | 37.00 | 28.96 |
September | 0.131855E+11 | 27772.64 | 04-SEP-12:11 | 40.87 | 24.05 | 0.402904E+09 | 549.51 | 01-SEP-13:20 | 40.87 | 24.05 |
October | 0.123410E+11 | 28035.62 | 29-OCT-12:51 | 35.10 | 15.03 | 0.416737E+09 | 549.51 | 16-OCT-13:39 | 35.10 | 15.03 |
November | 0.983309E+10 | 26253.66 | 12-NOV-13:22 | 29.65 | 18.98 | 0.408164E+09 | 549.51 | 14-NOV-14:20 | 29.00 | 22.43 |
December | 0.723924E+10 | 25666.58 | 03-DEC-12:22 | 28.90 | 18.13 | 0.383033E+09 | 549.51 | 13-DEC-14:50 | 24.17 | 18.04 |
Annual Sum or Average | 0.126389E+12 | 0.491492E+10 | ||||||||
Minimum of Months | 0.634815E+10 | 10581.82 | 26.00 | 15.03 | 0.359038E+09 | 549.51 | 24.17 | 15.03 | ||
Maximum of Months | 0.153317E+11 | 28035.62 | 43.50 | 29.11 | 0.454783E+09 | 549.51 | 43.50 | 29.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358394E+10 | 4675.75 | 29-JAN-16:52 | 25.00 | 20.23 | 0.227170E+09 | 347.86 | 23-JAN-14:30 | 25.00 | 20.23 |
February | 0.391747E+10 | 10267.59 | 05-FEB-16:02 | 31.83 | 18.84 | 0.214377E+09 | 347.86 | 06-FEB-14:00 | 32.50 | 17.28 |
March | 0.553637E+10 | 8563.55 | 27-MAR-15:40 | 35.00 | 18.85 | 0.264416E+09 | 347.86 | 01-MAR-14:30 | 35.00 | 18.85 |
April | 0.637624E+10 | 12526.99 | 23-APR-15:52 | 32.50 | 18.27 | 0.243261E+09 | 347.86 | 07-APR-13:20 | 32.50 | 18.27 |
May | 0.901441E+10 | 20851.81 | 29-MAY-16:11 | 35.40 | 24.28 | 0.273195E+09 | 347.86 | 18-MAY-13:39 | 35.40 | 24.28 |
June | 0.964993E+10 | 19382.83 | 18-JUN-16:02 | 35.98 | 27.42 | 0.273920E+09 | 347.86 | 01-JUN-13:39 | 35.98 | 27.42 |
July | 0.106716E+11 | 20760.61 | 02-JUL-16:02 | 38.17 | 23.16 | 0.255606E+09 | 347.86 | 13-JUL-13:09 | 39.25 | 25.56 |
August | 0.111502E+11 | 20240.18 | 06-AUG-16:42 | 40.02 | 26.09 | 0.286655E+09 | 347.86 | 04-AUG-13:09 | 40.02 | 26.09 |
September | 0.882474E+10 | 21148.66 | 04-SEP-16:11 | 40.47 | 23.66 | 0.252670E+09 | 347.86 | 06-SEP-13:00 | 37.90 | 27.37 |
October | 0.741594E+10 | 20761.57 | 08-OCT-15:52 | 32.80 | 26.05 | 0.258567E+09 | 347.86 | 06-OCT-13:20 | 32.80 | 26.05 |
November | 0.557057E+10 | 7764.73 | 12-NOV-14:02 | 29.83 | 18.49 | 0.248464E+09 | 347.86 | 14-NOV-14:39 | 29.00 | 22.26 |
December | 0.410695E+10 | 5301.96 | 01-DEC-15:00 | 28.00 | 17.95 | 0.225868E+09 | 347.86 | 04-DEC-14:00 | 27.00 | 21.53 |
Annual Sum or Average | 0.858184E+11 | 0.302417E+10 | ||||||||
Minimum of Months | 0.358394E+10 | 4675.75 | 25.00 | 17.95 | 0.214377E+09 | 347.86 | 25.00 | 17.28 | ||
Maximum of Months | 0.111502E+11 | 21148.66 | 40.47 | 27.42 | 0.286655E+09 | 347.86 | 40.02 | 27.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448703E+10 | 4665.79 | 23-JAN-14:00 | 28.00 | 16.55 | 0.393196E+09 | 549.51 | 24-JAN-14:00 | 23.00 | 18.45 |
February | 0.443093E+10 | 6348.23 | 06-FEB-14:40 | 32.33 | 17.26 | 0.363781E+09 | 549.51 | 08-FEB-14:39 | 29.00 | 19.99 |
March | 0.594186E+10 | 7661.43 | 27-MAR-13:10 | 35.83 | 19.71 | 0.441659E+09 | 549.51 | 27-MAR-13:09 | 35.83 | 19.71 |
April | 0.689651E+10 | 8763.22 | 28-APR-12:20 | 40.23 | 20.93 | 0.399100E+09 | 549.51 | 06-APR-13:50 | 40.23 | 20.93 |
May | 0.105124E+11 | 18548.78 | 07-MAY-14:51 | 37.00 | 20.10 | 0.437585E+09 | 549.51 | 05-MAY-13:09 | 37.00 | 20.10 |
June | 0.117797E+11 | 16640.71 | 01-JUN-04:01 | 28.75 | 21.75 | 0.436650E+09 | 549.51 | 01-JUN-13:20 | 40.73 | 21.63 |
July | 0.132539E+11 | 19847.53 | 04-JUL-14:31 | 40.00 | 26.72 | 0.406504E+09 | 549.51 | 20-JUL-13:09 | 38.83 | 30.79 |
August | 0.143042E+11 | 19308.80 | 20-AUG-12:42 | 38.75 | 26.74 | 0.455866E+09 | 549.51 | 04-AUG-13:09 | 38.75 | 26.74 |
September | 0.114938E+11 | 20614.51 | 04-SEP-14:21 | 41.00 | 24.70 | 0.404634E+09 | 549.51 | 05-SEP-09:00 | 37.60 | 24.92 |
October | 0.987248E+10 | 15754.70 | 04-OCT-04:01 | 26.92 | 20.11 | 0.420092E+09 | 549.51 | 30-OCT-13:09 | 31.50 | 22.82 |
November | 0.724165E+10 | 7885.58 | 01-NOV-14:00 | 33.00 | 26.24 | 0.413747E+09 | 549.51 | 08-NOV-14:30 | 31.50 | 20.59 |
December | 0.512387E+10 | 5874.70 | 11-DEC-14:10 | 26.77 | 18.23 | 0.392078E+09 | 549.51 | 13-DEC-14:39 | 24.33 | 17.93 |
Annual Sum or Average | 0.105338E+12 | 0.496489E+10 | ||||||||
Minimum of Months | 0.443093E+10 | 4665.79 | 26.77 | 16.55 | 0.363781E+09 | 549.51 | 23.00 | 17.93 | ||
Maximum of Months | 0.143042E+11 | 20614.51 | 41.00 | 26.74 | 0.455866E+09 | 549.51 | 40.73 | 30.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377705E+10 | 3866.74 | 29-JAN-10:02 | 24.58 | 19.01 | 0.250308E+09 | 347.89 | 17-JAN-14:09 | 24.58 | 19.01 |
February | 0.368399E+10 | 5908.56 | 05-FEB-10:12 | 27.87 | 18.62 | 0.232091E+09 | 347.89 | 07-FEB-14:09 | 30.50 | 20.52 |
March | 0.491446E+10 | 7272.93 | 27-MAR-10:40 | 37.00 | 18.58 | 0.279769E+09 | 347.89 | 16-MAR-13:39 | 37.00 | 18.58 |
April | 0.583656E+10 | 14708.89 | 02-APR-10:02 | 32.67 | 17.46 | 0.252724E+09 | 347.89 | 11-APR-13:20 | 30.07 | 18.59 |
May | 0.849962E+10 | 17717.63 | 07-MAY-10:11 | 37.33 | 18.24 | 0.277024E+09 | 347.89 | 05-MAY-13:50 | 37.33 | 18.24 |
June | 0.910110E+10 | 13290.82 | 11-JUN-10:02 | 38.17 | 26.68 | 0.276274E+09 | 347.89 | 20-JUN-13:09 | 38.42 | 26.34 |
July | 0.101870E+11 | 17135.45 | 04-JUL-11:12 | 38.67 | 23.79 | 0.257216E+09 | 347.89 | 20-JUL-13:09 | 38.83 | 30.79 |
August | 0.111645E+11 | 16866.82 | 13-AUG-10:11 | 38.40 | 24.99 | 0.288438E+09 | 347.89 | 04-AUG-13:09 | 38.40 | 24.99 |
September | 0.913179E+10 | 17788.65 | 04-SEP-09:41 | 37.63 | 22.86 | 0.256097E+09 | 347.89 | 01-SEP-13:00 | 37.63 | 22.86 |
October | 0.793065E+10 | 15653.45 | 22-OCT-08:52 | 31.90 | 22.98 | 0.265897E+09 | 347.89 | 03-OCT-13:39 | 31.90 | 22.98 |
November | 0.585509E+10 | 8030.28 | 05-NOV-09:02 | 27.40 | 18.90 | 0.261877E+09 | 347.89 | 01-NOV-13:50 | 27.40 | 18.90 |
December | 0.416770E+10 | 4653.52 | 01-DEC-10:30 | 26.20 | 16.33 | 0.247847E+09 | 347.89 | 04-DEC-14:00 | 27.00 | 21.53 |
Annual Sum or Average | 0.842495E+11 | 0.314556E+10 | ||||||||
Minimum of Months | 0.368399E+10 | 3866.74 | 24.58 | 16.33 | 0.232091E+09 | 347.89 | 24.58 | 18.24 | ||
Maximum of Months | 0.111645E+11 | 17788.65 | 38.67 | 26.68 | 0.288438E+09 | 347.89 | 38.83 | 30.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639426E+10 | 12616.24 | 23-JAN-13:00 | 27.40 | 16.52 | 0.402258E+09 | 549.51 | 05-JAN-14:09 | 27.40 | 16.52 |
February | 0.656790E+10 | 17816.25 | 07-FEB-13:00 | 31.00 | 20.84 | 0.368310E+09 | 549.51 | 07-FEB-14:09 | 30.50 | 20.52 |
March | 0.860564E+10 | 20580.83 | 27-MAR-12:00 | 37.30 | 19.38 | 0.442298E+09 | 641.54 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.955591E+10 | 22188.87 | 28-APR-12:00 | 42.00 | 19.18 | 0.398469E+09 | 701.13 | 28-APR-12:09 | 41.12 | 20.13 |
May | 0.139679E+11 | 21478.95 | 09-MAY-12:00 | 41.00 | 19.42 | 0.440508E+09 | 673.59 | 09-MAY-12:09 | 41.02 | 19.49 |
June | 0.152372E+11 | 22515.82 | 12-JUN-12:00 | 43.00 | 24.56 | 0.441317E+09 | 705.86 | 12-JUN-12:09 | 42.65 | 25.06 |
July | 0.171764E+11 | 23976.51 | 21-JUL-12:00 | 46.00 | 22.01 | 0.412341E+09 | 764.10 | 21-JUL-12:09 | 45.38 | 23.17 |
August | 0.197512E+11 | 24455.05 | 16-AUG-12:00 | 46.00 | 25.38 | 0.464287E+09 | 778.78 | 16-AUG-12:09 | 45.70 | 25.45 |
September | 0.169519E+11 | 24370.42 | 04-SEP-14:21 | 41.00 | 24.70 | 0.410743E+09 | 709.98 | 05-SEP-12:09 | 40.98 | 24.12 |
October | 0.159115E+11 | 24115.70 | 29-OCT-12:51 | 35.10 | 15.03 | 0.424495E+09 | 669.79 | 04-OCT-12:09 | 35.10 | 15.03 |
November | 0.122074E+11 | 22457.48 | 11-NOV-12:32 | 30.27 | 19.08 | 0.415668E+09 | 594.93 | 06-NOV-13:09 | 30.27 | 19.08 |
December | 0.789290E+10 | 22482.62 | 25-DEC-13:42 | 27.08 | 18.31 | 0.395378E+09 | 549.51 | 01-DEC-14:09 | 27.08 | 18.31 |
Annual Sum or Average | 0.150220E+12 | 0.501607E+10 | ||||||||
Minimum of Months | 0.639426E+10 | 12616.24 | 27.08 | 15.03 | 0.368310E+09 | 549.51 | 27.08 | 15.03 | ||
Maximum of Months | 0.197512E+11 | 24455.05 | 46.00 | 25.38 | 0.464287E+09 | 778.78 | 45.70 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393262E+10 | 4093.79 | 29-JAN-17:22 | 24.50 | 19.78 | 0.241106E+09 | 347.86 | 23-JAN-14:00 | 24.50 | 19.78 |
February | 0.389219E+10 | 6101.23 | 06-FEB-15:30 | 31.95 | 17.43 | 0.223850E+09 | 347.86 | 08-FEB-14:00 | 28.00 | 20.53 |
March | 0.515865E+10 | 7600.10 | 27-MAR-15:50 | 35.00 | 18.85 | 0.273120E+09 | 347.86 | 27-MAR-13:09 | 35.00 | 18.85 |
April | 0.576271E+10 | 8452.39 | 29-APR-17:08 | 33.67 | 22.47 | 0.248996E+09 | 347.86 | 03-APR-13:30 | 33.67 | 22.47 |
May | 0.830931E+10 | 18478.80 | 07-MAY-15:31 | 35.07 | 21.55 | 0.275842E+09 | 347.86 | 04-MAY-13:09 | 35.07 | 21.55 |
June | 0.907941E+10 | 16097.58 | 18-JUN-16:02 | 35.98 | 27.42 | 0.275740E+09 | 347.86 | 06-JUN-13:20 | 35.98 | 27.42 |
July | 0.101513E+11 | 19048.16 | 04-JUL-14:31 | 40.00 | 26.72 | 0.256823E+09 | 347.86 | 20-JUL-13:09 | 38.83 | 30.79 |
August | 0.110790E+11 | 18302.32 | 13-AUG-14:51 | 40.00 | 25.61 | 0.288126E+09 | 347.86 | 04-AUG-13:09 | 40.00 | 25.61 |
September | 0.911646E+10 | 20057.22 | 04-SEP-16:21 | 40.35 | 23.48 | 0.255640E+09 | 347.86 | 13-SEP-13:09 | 40.00 | 23.31 |
October | 0.791086E+10 | 17499.04 | 22-OCT-15:32 | 31.60 | 23.78 | 0.264951E+09 | 347.86 | 02-OCT-13:00 | 31.60 | 23.78 |
November | 0.595541E+10 | 9093.16 | 11-NOV-15:52 | 29.20 | 20.21 | 0.259629E+09 | 347.86 | 08-NOV-14:20 | 29.20 | 20.21 |
December | 0.441210E+10 | 5273.67 | 01-DEC-15:00 | 28.00 | 17.95 | 0.241149E+09 | 347.86 | 11-DEC-14:20 | 26.83 | 18.23 |
Annual Sum or Average | 0.847601E+11 | 0.310497E+10 | ||||||||
Minimum of Months | 0.389219E+10 | 4093.79 | 24.50 | 17.43 | 0.223850E+09 | 347.86 | 24.50 | 18.23 | ||
Maximum of Months | 0.110790E+11 | 20057.22 | 40.35 | 27.42 | 0.288126E+09 | 347.86 | 40.00 | 30.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423053E+10 | 4726.96 | 23-JAN-14:00 | 28.00 | 16.55 | 0.385964E+09 | 549.51 | 30-JAN-14:20 | 22.67 | 20.79 |
February | 0.439001E+10 | 6735.39 | 06-FEB-14:40 | 32.33 | 17.26 | 0.360780E+09 | 549.51 | 06-FEB-14:30 | 32.33 | 17.26 |
March | 0.615820E+10 | 11363.77 | 02-MAR-06:02 | 28.80 | 15.43 | 0.440958E+09 | 549.51 | 01-MAR-14:09 | 28.80 | 15.43 |
April | 0.723674E+10 | 9342.48 | 28-APR-12:20 | 40.23 | 20.93 | 0.398876E+09 | 549.51 | 05-APR-13:09 | 40.23 | 20.93 |
May | 0.105942E+11 | 19075.89 | 07-MAY-14:51 | 37.00 | 20.10 | 0.437724E+09 | 549.51 | 01-MAY-13:30 | 37.00 | 20.10 |
June | 0.115756E+11 | 17001.22 | 11-JUN-15:22 | 36.70 | 27.29 | 0.436758E+09 | 549.51 | 01-JUN-13:30 | 36.70 | 27.29 |
July | 0.127063E+11 | 19303.05 | 30-JUL-13:32 | 44.17 | 24.21 | 0.406481E+09 | 549.51 | 13-JUL-13:09 | 44.17 | 24.21 |
August | 0.131919E+11 | 18609.81 | 06-AUG-15:42 | 40.25 | 25.55 | 0.455703E+09 | 549.51 | 03-AUG-13:00 | 40.25 | 25.55 |
September | 0.102589E+11 | 19001.13 | 04-SEP-15:52 | 40.70 | 24.03 | 0.404332E+09 | 549.51 | 01-SEP-09:39 | 40.70 | 24.03 |
October | 0.857586E+10 | 15177.71 | 10-OCT-04:01 | 27.00 | 23.50 | 0.418762E+09 | 549.51 | 11-OCT-13:00 | 35.00 | 22.01 |
November | 0.636382E+10 | 7420.44 | 01-NOV-14:00 | 33.00 | 26.24 | 0.409850E+09 | 549.51 | 02-NOV-13:09 | 32.50 | 23.94 |
December | 0.470811E+10 | 5449.87 | 11-DEC-14:10 | 26.77 | 18.23 | 0.383345E+09 | 549.51 | 01-DEC-14:30 | 26.77 | 18.23 |
Annual Sum or Average | 0.999901E+11 | 0.493953E+10 | ||||||||
Minimum of Months | 0.423053E+10 | 4726.96 | 26.77 | 15.43 | 0.360780E+09 | 549.51 | 22.67 | 15.43 | ||
Maximum of Months | 0.131919E+11 | 19303.05 | 44.17 | 27.29 | 0.455703E+09 | 549.51 | 44.17 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355584E+10 | 3930.70 | 29-JAN-10:32 | 25.43 | 18.95 | 0.178262E+09 | 346.31 | 24-JAN-11:09 | 25.43 | 18.95 |
February | 0.357074E+10 | 5688.04 | 06-FEB-15:05 | 32.32 | 17.34 | 0.167826E+09 | 356.46 | 06-FEB-15:09 | 32.32 | 17.34 |
March | 0.489960E+10 | 9599.75 | 27-MAR-12:02 | 37.08 | 19.46 | 0.204522E+09 | 356.46 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.586671E+10 | 16651.26 | 02-APR-10:02 | 32.67 | 17.46 | 0.186375E+09 | 356.46 | 28-APR-12:09 | 41.12 | 20.13 |
May | 0.830112E+10 | 18177.12 | 07-MAY-10:11 | 37.33 | 18.24 | 0.205434E+09 | 356.46 | 18-MAY-12:09 | 39.90 | 20.61 |
June | 0.873832E+10 | 14726.61 | 11-JUN-10:02 | 38.17 | 26.68 | 0.204699E+09 | 356.46 | 12-JUN-12:09 | 42.65 | 25.06 |
July | 0.959886E+10 | 18157.36 | 23-JUL-09:41 | 40.17 | 22.97 | 0.191189E+09 | 356.46 | 13-JUL-12:09 | 40.17 | 22.97 |
August | 0.101267E+11 | 17409.37 | 27-AUG-09:02 | 35.25 | 26.71 | 0.213581E+09 | 356.46 | 16-AUG-12:09 | 35.25 | 26.71 |
September | 0.801783E+10 | 17953.57 | 03-SEP-09:51 | 37.00 | 23.44 | 0.189817E+09 | 356.46 | 14-SEP-12:09 | 38.98 | 24.29 |
October | 0.678954E+10 | 16789.04 | 08-OCT-09:52 | 32.00 | 26.27 | 0.196477E+09 | 356.46 | 04-OCT-12:09 | 32.00 | 26.27 |
November | 0.502920E+10 | 7201.16 | 02-NOV-10:05 | 30.25 | 24.15 | 0.191925E+09 | 356.46 | 13-NOV-13:09 | 32.08 | 17.82 |
December | 0.381583E+10 | 5348.90 | 01-DEC-11:05 | 27.17 | 16.31 | 0.176802E+09 | 356.46 | 01-DEC-11:09 | 27.17 | 16.31 |
Annual Sum or Average | 0.783103E+11 | 0.230691E+10 | ||||||||
Minimum of Months | 0.355584E+10 | 3930.70 | 25.43 | 16.31 | 0.167826E+09 | 346.31 | 25.43 | 16.31 | ||
Maximum of Months | 0.101267E+11 | 18177.12 | 40.17 | 26.71 | 0.213581E+09 | 356.46 | 42.65 | 26.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.647646E+10 | 9395.34 | 23-JAN-13:30 | 27.70 | 16.54 | 0.402086E+09 | 549.51 | 05-JAN-14:50 | 27.70 | 16.54 |
February | 0.649139E+10 | 12934.15 | 05-FEB-13:32 | 31.43 | 19.44 | 0.367758E+09 | 549.51 | 02-FEB-14:50 | 31.43 | 19.44 |
March | 0.809964E+10 | 13857.15 | 26-MAR-13:43 | 33.33 | 18.37 | 0.442166E+09 | 549.51 | 07-MAR-14:09 | 33.33 | 18.37 |
April | 0.830123E+10 | 12878.19 | 30-APR-13:13 | 36.07 | 21.81 | 0.397583E+09 | 549.51 | 10-APR-13:39 | 36.07 | 21.81 |
May | 0.107937E+11 | 21415.41 | 07-MAY-14:51 | 37.00 | 20.10 | 0.436722E+09 | 549.51 | 02-MAY-13:00 | 37.00 | 20.10 |
June | 0.113016E+11 | 17561.51 | 16-JUN-04:01 | 28.83 | 20.58 | 0.436019E+09 | 549.51 | 01-JUN-13:30 | 28.83 | 20.58 |
July | 0.127588E+11 | 21841.99 | 30-JUL-13:32 | 44.17 | 24.21 | 0.406006E+09 | 549.51 | 13-JUL-13:09 | 44.17 | 24.21 |
August | 0.140454E+11 | 20726.65 | 06-AUG-15:02 | 40.85 | 24.99 | 0.455459E+09 | 549.51 | 04-AUG-13:09 | 40.85 | 24.99 |
September | 0.123282E+11 | 22955.15 | 24-SEP-12:32 | 34.73 | 25.63 | 0.404261E+09 | 549.88 | 05-SEP-13:20 | 34.73 | 25.63 |
October | 0.118160E+11 | 23200.72 | 08-OCT-11:52 | 34.00 | 27.29 | 0.419457E+09 | 549.92 | 02-OCT-13:20 | 34.00 | 27.29 |
November | 0.967128E+10 | 22502.45 | 19-NOV-12:42 | 30.92 | 16.54 | 0.412756E+09 | 549.51 | 09-NOV-14:39 | 30.92 | 16.54 |
December | 0.728351E+10 | 23097.68 | 03-DEC-12:32 | 29.20 | 17.98 | 0.392993E+09 | 549.51 | 07-DEC-14:09 | 25.83 | 17.79 |
Annual Sum or Average | 0.119367E+12 | 0.497327E+10 | ||||||||
Minimum of Months | 0.647646E+10 | 9395.34 | 27.70 | 16.54 | 0.367758E+09 | 549.51 | 25.83 | 16.54 | ||
Maximum of Months | 0.140454E+11 | 23200.72 | 44.17 | 27.29 | 0.455459E+09 | 549.92 | 44.17 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372303E+10 | 4156.75 | 31-JAN-16:20 | 22.73 | 16.79 | 0.235420E+09 | 347.86 | 23-JAN-14:00 | 22.73 | 16.79 |
February | 0.388049E+10 | 6482.68 | 06-FEB-15:30 | 31.95 | 17.43 | 0.220640E+09 | 347.86 | 07-FEB-14:39 | 29.00 | 21.78 |
March | 0.532271E+10 | 8135.80 | 27-MAR-15:40 | 35.00 | 18.85 | 0.271196E+09 | 347.86 | 22-MAR-13:39 | 35.00 | 18.85 |
April | 0.600601E+10 | 10775.43 | 23-APR-16:32 | 31.50 | 19.01 | 0.247785E+09 | 347.86 | 20-APR-13:09 | 31.50 | 19.01 |
May | 0.837489E+10 | 19355.85 | 14-MAY-16:01 | 34.00 | 20.66 | 0.275124E+09 | 347.86 | 15-MAY-13:30 | 32.00 | 24.71 |
June | 0.895945E+10 | 17677.51 | 18-JUN-16:02 | 35.98 | 27.42 | 0.275154E+09 | 347.86 | 06-JUN-13:39 | 35.98 | 27.42 |
July | 0.981496E+10 | 18572.92 | 04-JUL-16:01 | 38.17 | 27.77 | 0.256349E+09 | 347.86 | 13-JUL-13:09 | 39.25 | 25.56 |
August | 0.103135E+11 | 18606.59 | 06-AUG-16:22 | 40.05 | 25.93 | 0.287502E+09 | 347.86 | 04-AUG-13:20 | 40.05 | 25.93 |
September | 0.824969E+10 | 18674.18 | 04-SEP-15:52 | 40.70 | 24.03 | 0.254404E+09 | 347.86 | 01-SEP-13:30 | 40.70 | 24.03 |
October | 0.703338E+10 | 18435.99 | 08-OCT-15:52 | 32.80 | 26.05 | 0.261979E+09 | 347.86 | 02-OCT-13:50 | 32.80 | 26.05 |
November | 0.538723E+10 | 8418.85 | 11-NOV-15:02 | 29.87 | 20.58 | 0.254203E+09 | 347.86 | 08-NOV-14:50 | 29.87 | 20.58 |
December | 0.414193E+10 | 5182.68 | 06-DEC-15:30 | 26.85 | 20.67 | 0.233657E+09 | 347.86 | 04-DEC-14:00 | 26.85 | 20.67 |
Annual Sum or Average | 0.812073E+11 | 0.307341E+10 | ||||||||
Minimum of Months | 0.372303E+10 | 4156.75 | 22.73 | 16.79 | 0.220640E+09 | 347.86 | 22.73 | 16.79 | ||
Maximum of Months | 0.103135E+11 | 19355.85 | 40.70 | 27.77 | 0.287502E+09 | 347.86 | 40.70 | 27.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237404E+11 | 133086.78 | 03-JAN-07:08 | 12.67 |
February | 0.113250E+11 | 133174.42 | 21-FEB-07:08 | 13.92 |
March | 0.553487E+10 | 132812.65 | 16-MAR-06:50 | 15.00 |
April | 0.680207E+09 | 132754.25 | 01-APR-06:40 | 17.27 |
May | 33689288.18 | 8564.39 | 08-MAY-04:01 | 26.67 |
June | 39183859.10 | 8108.15 | 19-JUN-04:01 | 28.08 |
July | 36115249.61 | 8229.31 | 03-JUL-04:01 | 29.00 |
August | 33062462.67 | 6893.19 | 31-AUG-04:01 | 28.83 |
September | 34947405.68 | 7739.87 | 18-SEP-04:01 | 28.58 |
October | 35687354.21 | 7994.94 | 02-OCT-04:01 | 27.05 |
November | 0.362567E+09 | 129235.38 | 22-NOV-07:03 | 17.08 |
December | 0.118450E+11 | 132865.79 | 18-DEC-07:08 | 14.00 |
Annual Sum or Average | 0.537008E+11 | |||
Minimum of Months | 33062462.67 | 6893.19 | 12.67 | |
Maximum of Months | 0.237404E+11 | 133174.42 | 29.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249626E+10 | 115875.88 | 09-JAN-08:00 | 12.00 |
February | 0.660590E+09 | 110884.67 | 14-FEB-07:03 | 13.33 |
March | 0.103452E+09 | 49140.71 | 08-MAR-07:03 | 14.83 |
April | 12830474.06 | 2637.50 | 16-APR-14:04 | 29.00 |
May | 27209958.13 | 4715.31 | 11-MAY-04:01 | 29.58 |
June | 35792902.17 | 4294.49 | 28-JUN-04:01 | 29.00 |
July | 65017034.28 | 6609.97 | 30-JUL-13:32 | 44.17 |
August | 61861979.33 | 5646.54 | 06-AUG-15:02 | 40.85 |
September | 41176393.54 | 6072.25 | 03-SEP-13:51 | 40.00 |
October | 29759356.60 | 3979.33 | 05-OCT-04:01 | 27.83 |
November | 24061661.85 | 3524.31 | 05-NOV-12:02 | 33.90 |
December | 0.570447E+09 | 109968.30 | 30-DEC-07:03 | 13.33 |
Annual Sum or Average | 0.412846E+10 | |||
Minimum of Months | 12830474.06 | 2637.50 | 12.00 | |
Maximum of Months | 0.249626E+10 | 115875.88 | 44.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191841E+10 | 82117.23 | 20-JAN-07:03 | 12.17 |
February | 0.130608E+10 | 56689.23 | 13-FEB-07:05 | 13.33 |
March | 0.112815E+10 | 32684.57 | 06-MAR-07:03 | 16.00 |
April | 0.116988E+09 | 31773.72 | 05-APR-06:40 | 17.07 |
May | 35268661.02 | 6132.84 | 23-MAY-04:01 | 31.17 |
June | 46703692.08 | 6075.37 | 28-JUN-04:01 | 29.00 |
July | 91914745.99 | 6366.16 | 30-JUL-14:12 | 43.00 |
August | 99130288.76 | 6204.12 | 13-AUG-14:11 | 40.00 |
September | 72238188.04 | 6513.65 | 15-SEP-04:01 | 28.92 |
October | 54018233.75 | 6253.39 | 06-OCT-04:01 | 27.17 |
November | 40341426.38 | 29134.99 | 22-NOV-07:10 | 17.08 |
December | 0.111746E+10 | 32737.65 | 18-DEC-07:03 | 14.00 |
Annual Sum or Average | 0.602671E+10 | |||
Minimum of Months | 35268661.02 | 6075.37 | 12.17 | |
Maximum of Months | 0.191841E+10 | 82117.23 | 43.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19708141.12 | 7038.56 | 20-JAN-07:03 | 12.17 |
February | 9986913.05 | 5684.32 | 14-FEB-07:03 | 13.33 |
March | 1901816.60 | 4264.75 | 08-MAR-07:03 | 14.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 7674232.19 | 5550.12 | 28-DEC-07:03 | 14.75 |
Annual Sum or Average | 39271102.96 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 19708141.12 | 7038.56 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8837362.25 | 3897.64 | 20-JAN-07:03 | 12.17 |
February | 4012171.18 | 2913.14 | 03-FEB-07:03 | 14.42 |
March | 1230606.56 | 2804.47 | 08-MAR-07:03 | 14.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 3894304.58 | 3177.59 | 18-DEC-07:03 | 14.00 |
Annual Sum or Average | 17974444.56 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 8837362.25 | 3897.64 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14860151.13 | 6498.07 | 20-JAN-07:03 | 12.17 |
February | 8594791.19 | 5104.96 | 22-FEB-07:03 | 13.83 |
March | 2062475.65 | 4323.17 | 08-MAR-07:03 | 14.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 5776011.93 | 5104.85 | 30-DEC-07:03 | 13.33 |
Annual Sum or Average | 31293429.89 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 14860151.13 | 6498.07 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13151791.27 | 4153.13 | 20-JAN-07:03 | 12.17 |
February | 5219029.93 | 3669.39 | 13-FEB-07:03 | 13.33 |
March | 1791050.97 | 2905.66 | 11-MAR-07:03 | 15.75 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 146463.79 | 976.43 | 22-NOV-07:03 | 17.08 |
December | 5017884.52 | 3511.29 | 18-DEC-07:03 | 14.00 |
Annual Sum or Average | 25326220.48 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 13151791.27 | 4153.13 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 312158.54 | 1063.17 | 20-JAN-07:03 | 12.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 312158.54 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 312158.54 | 1063.17 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240101E+09 | 10390.53 | 20-JAN-07:03 | 12.17 |
February | 0.139438E+09 | 6001.11 | 01-FEB-07:05 | 13.25 |
March | 73663415.22 | 4603.03 | 07-MAR-07:05 | 14.58 |
April | 5581318.94 | 2926.35 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 431960.62 | 2879.74 | 22-NOV-07:10 | 17.08 |
December | 67278411.65 | 3968.34 | 18-DEC-07:08 | 14.00 |
Annual Sum or Average | 0.526494E+09 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 0.240101E+09 | 10390.53 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1767015.63 | 1359.18 | 21-JAN-07:03 | 13.33 |
February | 143256.00 | 955.04 | 13-FEB-07:05 | 13.33 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 1910271.63 | |||
Minimum of Months | 0.00 | 0.00 | 13.33 | |
Maximum of Months | 1767015.63 | 1359.18 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2361553.69 | 2407.62 | 20-JAN-07:03 | 12.17 |
February | 480917.73 | 805.66 | 13-FEB-07:03 | 13.33 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 295261.92 | 770.54 | 30-DEC-07:03 | 13.33 |
Annual Sum or Average | 3137733.34 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 2361553.69 | 2407.62 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3768654.41 | 2987.17 | 20-JAN-07:03 | 12.17 |
February | 1750463.27 | 1060.92 | 01-FEB-07:03 | 13.25 |
March | 454243.40 | 906.84 | 08-MAR-07:03 | 14.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 1259380.79 | 1008.84 | 30-DEC-07:03 | 13.33 |
Annual Sum or Average | 7232741.87 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 3768654.41 | 2987.17 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2157215.41 | 2291.89 | 20-JAN-07:03 | 12.17 |
February | 482037.84 | 898.23 | 01-FEB-07:03 | 13.25 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 199007.15 | 784.46 | 30-DEC-07:03 | 13.33 |
Annual Sum or Average | 2838260.40 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 2157215.41 | 2291.89 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8247676.11 | 3254.82 | 21-JAN-07:03 | 13.33 |
February | 4910790.84 | 1851.01 | 13-FEB-07:03 | 13.33 |
March | 1653906.99 | 1114.30 | 07-MAR-07:03 | 14.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 4340687.97 | 1392.74 | 30-DEC-07:03 | 13.33 |
Annual Sum or Average | 19153061.91 | |||
Minimum of Months | 0.00 | 0.00 | 13.33 | |
Maximum of Months | 8247676.11 | 3254.82 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5403379.13 | 0.122511E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22091486.53 | 0.124806E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50717786.81 | 69217855.24 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114845E+09 | 32714241.99 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263675E+09 | 3757849.97 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327172E+09 | 313381.94 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470634E+09 | 0.00 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450400E+09 | 0.00 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317281E+09 | 477150.33 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186485E+09 | 4907038.58 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88267114.23 | 31916077.44 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18689499.01 | 86729905.97 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231566E+10 | 0.477350E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5403379.13 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470634E+09 | 0.124806E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2942103.02 | 85620734.88 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13654854.90 | 85930228.85 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33322074.01 | 47511405.02 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74605045.20 | 22180206.62 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175688E+09 | 2573634.46 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219696E+09 | 221279.37 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316315E+09 | 0.00 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302004E+09 | 0.00 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211260E+09 | 332101.01 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123336E+09 | 3547328.29 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57431800.08 | 22688758.44 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12009324.61 | 59102422.73 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154226E+10 | 0.329708E+09 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2942103.02 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316315E+09 | 85930228.85 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1513450.69 | 0.148964E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16888581.80 | 0.141809E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45965927.57 | 75428301.71 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111908E+09 | 33169782.11 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267664E+09 | 3674433.10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332782E+09 | 297854.58 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477708E+09 | 0.00 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453844E+09 | 0.00 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314983E+09 | 518324.81 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176380E+09 | 5895464.95 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71677750.25 | 36879727.12 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11227466.05 | 0.104472E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228254E+10 | 0.551109E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1513450.69 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477708E+09 | 0.148964E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3821377.55 | 85083947.15 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15255986.58 | 84811723.70 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34229550.72 | 48050459.55 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76109898.44 | 22342830.59 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178150E+09 | 2566814.09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221813E+09 | 217419.51 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321447E+09 | 0.00 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306353E+09 | 0.00 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213890E+09 | 325573.66 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124873E+09 | 3447004.80 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58344914.14 | 21565128.34 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12944811.11 | 59441070.94 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156723E+10 | 0.327852E+09 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3821377.55 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321447E+09 | 85083947.15 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2456173.13 | 83843505.72 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11526884.74 | 82216005.96 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26456469.81 | 43373489.31 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62020160.34 | 19672181.37 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142624E+09 | 1772756.15 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176094E+09 | 134319.23 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251116E+09 | 0.00 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239871E+09 | 0.00 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170189E+09 | 287002.66 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98521799.17 | 3625140.23 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43473793.41 | 25098739.64 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8076780.61 | 64506785.77 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123243E+10 | 0.324530E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2456173.13 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251116E+09 | 83843505.72 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1404841.26 | 57618112.17 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7309114.85 | 56247704.05 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17730689.52 | 29680046.42 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40447349.35 | 13584126.45 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95026891.26 | 1268840.33 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118474E+09 | 101808.55 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169515E+09 | 0.00 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161570E+09 | 0.00 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113902E+09 | 205569.34 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65651263.64 | 2662647.21 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28849683.27 | 17542275.54 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5526880.42 | 43338599.13 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825407E+09 | 0.222250E+09 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1404841.26 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169515E+09 | 57618112.17 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22168631.96 | 0.139429E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264604E+09 | 0.843525E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928454E+09 | 0.531389E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172411E+10 | 0.153026E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362253E+10 | 19043031.89 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425969E+10 | 820133.10 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451522E+10 | 0.00 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519710E+10 | 0.00 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361306E+10 | 2018250.24 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263808E+10 | 15659613.31 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138517E+10 | 0.247268E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206942E+09 | 0.794966E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283771E+11 | 0.400200E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22168631.96 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519710E+10 | 0.139429E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1727560.33 | 56866285.91 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7737699.58 | 55804734.26 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17440227.74 | 30408658.57 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40202859.96 | 13761683.73 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95013646.66 | 1289706.44 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118022E+09 | 109841.42 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170094E+09 | 0.00 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162012E+09 | 0.00 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113863E+09 | 208723.99 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65359121.22 | 2672898.54 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28505294.31 | 17268462.68 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5439624.30 | 43098924.85 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825417E+09 | 0.221490E+09 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1727560.33 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170094E+09 | 56866285.91 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3832701.39 | 0.120147E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18051054.43 | 0.120531E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40396486.35 | 66790835.00 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94958478.49 | 31392756.77 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219053E+09 | 3597474.96 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271952E+09 | 300501.79 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389822E+09 | 0.00 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373165E+09 | 0.00 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263020E+09 | 437892.32 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153288E+09 | 4900243.59 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70026255.31 | 33001893.55 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13818062.66 | 87216717.06 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191138E+10 | 0.468316E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3832701.39 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389822E+09 | 0.120531E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2389433.18 | 80976174.40 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11536757.56 | 80819457.75 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27007546.80 | 44840711.01 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62137672.11 | 20904577.54 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146553E+09 | 2414580.55 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183300E+09 | 207984.51 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263584E+09 | 0.00 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251273E+09 | 0.00 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175978E+09 | 289662.46 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102265E+09 | 3432009.12 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46431630.05 | 22661325.32 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9578720.18 | 57674258.79 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128204E+10 | 0.314221E+09 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2389433.18 | 0.00 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263584E+09 | 80976174.40 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1121785.89 | 0.140582E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13605988.21 | 0.133992E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36871379.80 | 71865498.87 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92471613.02 | 31665497.81 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222546E+09 | 3520506.26 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277126E+09 | 288906.66 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396336E+09 | 0.00 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376126E+09 | 0.00 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260990E+09 | 469624.40 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144727E+09 | 5770467.15 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57340049.51 | 37179440.07 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8543284.87 | 0.101257E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188781E+10 | 0.526591E+09 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1121785.89 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396336E+09 | 0.140582E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2773181.88 | 81007444.81 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12327200.39 | 80561387.87 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27098164.97 | 45725289.18 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62599838.11 | 21224603.14 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147561E+09 | 2457863.86 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184186E+09 | 213451.81 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266062E+09 | 0.00 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253607E+09 | 0.00 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177072E+09 | 290026.90 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102439E+09 | 3393511.95 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46407572.96 | 22032040.70 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9581517.75 | 58144041.02 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129171E+10 | 0.315050E+09 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2773181.88 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266062E+09 | 81007444.81 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2055653.92 | 0.205083E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17825874.55 | 0.200749E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41764619.85 | 0.109268E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107600E+09 | 48628094.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269458E+09 | 4598384.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337456E+09 | 379628.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486276E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460465E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322377E+09 | 667336.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179564E+09 | 8131362.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70386694.74 | 55195676.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10408287.18 | 0.151350E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230564E+10 | 0.784051E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2055653.92 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486276E+09 | 0.205083E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4583459.33 | 0.230172E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25675408.06 | 0.231755E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56669897.09 | 0.126975E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141625E+09 | 58496591.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345904E+09 | 6013360.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433433E+09 | 498346.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624863E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593316E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415885E+09 | 826547.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234123E+09 | 9105000.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97987167.49 | 62189185.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17111855.34 | 0.167962E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299118E+10 | 0.893993E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4583459.33 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624863E+09 | 0.231755E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036135.53 | 0.209121E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19292189.66 | 0.204399E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53009003.59 | 0.112469E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120155E+09 | 37605279.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346905E+09 | 2831465.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454384E+09 | 196273.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653059E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627520E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436121E+09 | 334495.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247647E+09 | 2958861.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97305835.54 | 34179997.13 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10524439.63 | 0.136102E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306696E+10 | 0.740197E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036135.53 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653059E+09 | 0.209121E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 250.46 | 29-JAN-11:43 | 332.72 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 484.41 | 05-FEB-15:10 | 296.51 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 390.93 | 26-MAR-14:10 | 329.28 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.01 | 30-APR-13:00 | 207.35 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.19 | 21-MAY-12:56 | 76.63 | 01-MAY-04:53 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 682.79 | 11-JUN-14:46 | 46.66 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1003.58 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 933.68 | 13-AUG-14:25 | 0.00 | 01-AUG-00:02 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 752.16 | 03-SEP-15:54 | 45.42 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.83 | 09-OCT-15:28 | 102.98 | 20-OCT-04:35 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 525.60 | 19-NOV-14:00 | 165.33 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 240.04 | 10-DEC-12:43 | 229.38 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 240.04 | 0.00 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2759.19 | 332.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.96 | 29-JAN-12:00 | 222.20 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.56 | 05-FEB-14:50 | 196.97 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 261.31 | 26-MAR-14:10 | 228.16 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.58 | 30-APR-13:20 | 136.55 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1846.46 | 21-MAY-12:54 | 51.18 | 01-MAY-04:53 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.24 | 11-JUN-14:48 | 29.80 | 07-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.40 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.42 | 13-AUG-14:25 | 0.00 | 01-AUG-00:02 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 520.14 | 03-SEP-15:56 | 29.65 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 442.45 | 09-OCT-15:30 | 68.42 | 20-OCT-04:35 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.58 | 19-NOV-14:00 | 108.14 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.89 | 10-DEC-12:43 | 149.98 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 142.96 | 0.00 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1846.46 | 228.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 143.16 | 29-JAN-12:00 | 393.11 | 01-JAN-14:53 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 408.73 | 05-FEB-15:27 | 307.90 | 19-FEB-19:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.51 | 26-MAR-14:08 | 386.11 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.41 | 30-APR-13:18 | 208.15 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2768.01 | 21-MAY-12:54 | 77.13 | 01-MAY-04:53 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 690.13 | 11-JUN-14:48 | 45.21 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.38 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 934.63 | 13-AUG-14:25 | 0.00 | 01-AUG-00:02 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 751.61 | 04-SEP-16:54 | 46.26 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 634.86 | 09-OCT-15:26 | 106.74 | 20-OCT-04:42 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.85 | 19-NOV-13:56 | 167.44 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.32 | 10-DEC-13:23 | 228.51 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 143.16 | 0.00 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2768.01 | 393.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.36 | 29-JAN-11:43 | 220.97 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 310.67 | 05-FEB-13:30 | 199.04 | 13-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 253.74 | 26-MAR-14:10 | 244.80 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.18 | 30-APR-13:00 | 139.74 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1855.95 | 21-MAY-12:56 | 51.94 | 01-MAY-04:53 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 469.93 | 11-JUN-12:50 | 29.49 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 666.85 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 622.66 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.32 | 04-SEP-16:54 | 28.92 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.45 | 09-OCT-15:26 | 69.03 | 20-OCT-04:35 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.78 | 19-NOV-14:00 | 109.09 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.57 | 10-DEC-12:43 | 148.69 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 177.57 | 0.00 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1855.95 | 244.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.35 | 29-JAN-11:43 | 231.75 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 265.86 | 05-FEB-15:07 | 189.87 | 10-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 220.85 | 26-MAR-14:00 | 168.71 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.53 | 30-APR-13:00 | 124.01 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.33 | 21-MAY-12:56 | 34.32 | 02-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.84 | 11-JUN-14:48 | 21.93 | 07-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 547.25 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.66 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 394.86 | 03-SEP-16:08 | 31.86 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.74 | 09-OCT-15:30 | 69.70 | 20-OCT-04:10 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.69 | 19-NOV-14:00 | 116.19 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 117.70 | 10-DEC-12:43 | 157.27 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 117.70 | 0.00 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1469.33 | 231.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.78 | 29-JAN-11:43 | 158.91 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.10 | 05-FEB-15:00 | 128.08 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 145.31 | 26-MAR-14:00 | 115.38 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.78 | 30-APR-13:00 | 83.05 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 994.75 | 21-MAY-12:56 | 23.35 | 02-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.68 | 11-JUN-14:50 | 15.22 | 07-JUN-04:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.39 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.53 | 13-AUG-14:14 | 0.00 | 01-AUG-00:02 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.80 | 03-SEP-16:10 | 21.71 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.24 | 09-OCT-15:30 | 48.16 | 20-OCT-04:10 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.84 | 19-NOV-14:00 | 76.77 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.09 | 10-DEC-13:20 | 101.74 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 72.78 | 0.00 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 994.75 | 158.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4218.41 | 23-JAN-13:00 | 11805.20 | 19-JAN-07:10 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8347.07 | 07-FEB-13:00 | 10132.34 | 01-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15834.18 | 27-MAR-11:02 | 8291.38 | 07-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18467.93 | 28-APR-11:02 | 5817.55 | 05-APR-06:15 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18255.06 | 09-MAY-11:02 | 2721.92 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20338.93 | 12-JUN-11:01 | 541.76 | 22-JUN-08:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23404.94 | 21-JUL-11:01 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22725.97 | 16-AUG-11:01 | 0.00 | 01-AUG-00:02 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17781.08 | 12-SEP-11:02 | 729.53 | 25-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14179.35 | 04-OCT-11:02 | 2062.37 | 30-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9758.94 | 01-NOV-17:00 | 6289.23 | 22-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5206.11 | 01-DEC-13:00 | 9558.87 | 26-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4218.41 | 0.00 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23404.94 | 11805.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.70 | 29-JAN-11:43 | 156.60 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 166.96 | 05-FEB-14:32 | 128.73 | 13-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.41 | 26-MAR-14:00 | 125.75 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.35 | 30-APR-13:00 | 85.34 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 992.90 | 21-MAY-12:58 | 23.90 | 02-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.12 | 11-JUN-12:50 | 16.03 | 07-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.31 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.20 | 13-AUG-13:55 | 0.00 | 01-AUG-00:02 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.51 | 03-SEP-16:06 | 21.75 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.04 | 09-OCT-15:26 | 48.88 | 20-OCT-04:10 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.03 | 19-NOV-14:00 | 77.91 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.52 | 10-DEC-12:43 | 100.55 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 88.52 | 0.00 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 992.90 | 156.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 178.06 | 29-JAN-11:40 | 326.96 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 405.74 | 05-FEB-15:07 | 279.34 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.73 | 26-MAR-14:00 | 265.18 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.23 | 30-APR-13:00 | 190.28 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2284.67 | 21-MAY-12:54 | 66.09 | 01-MAY-04:53 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.06 | 11-JUN-14:46 | 43.54 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 833.27 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.01 | 13-AUG-14:00 | 0.00 | 01-AUG-00:02 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.70 | 03-SEP-15:54 | 41.78 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.70 | 09-OCT-15:28 | 98.85 | 20-OCT-04:53 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.41 | 19-NOV-13:50 | 159.97 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.03 | 10-DEC-13:10 | 217.78 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 178.06 | 0.00 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2284.67 | 326.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.86 | 29-JAN-11:40 | 216.59 | 18-JAN-04:00 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 280.06 | 05-FEB-15:00 | 185.11 | 13-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 221.29 | 26-MAR-14:00 | 183.72 | 05-MAR-15:00 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.13 | 30-APR-13:00 | 124.91 | 05-APR-01:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1539.58 | 21-MAY-12:54 | 43.96 | 01-MAY-04:53 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.32 | 11-JUN-14:48 | 27.36 | 07-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 578.62 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 530.69 | 13-AUG-14:25 | 0.00 | 01-AUG-00:02 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 429.78 | 03-SEP-15:56 | 26.65 | 25-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.81 | 09-OCT-15:30 | 65.51 | 20-OCT-04:53 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.04 | 19-NOV-14:10 | 104.34 | 22-NOV-06:00 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.08 | 10-DEC-13:10 | 140.69 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 97.86 | 0.00 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1539.58 | 216.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 29-JAN-11:40 | 341.53 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 309.40 | 05-FEB-15:00 | 287.90 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.53 | 26-MAR-14:28 | 312.08 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.49 | 30-APR-13:00 | 190.72 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2298.10 | 21-MAY-12:54 | 66.54 | 01-MAY-04:53 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 566.64 | 11-JUN-14:48 | 42.41 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 844.22 | 30-JUL-14:55 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 777.05 | 13-AUG-14:00 | 0.00 | 01-AUG-00:02 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 620.16 | 03-SEP-15:54 | 42.52 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.77 | 09-OCT-15:26 | 102.31 | 20-OCT-04:53 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.68 | 19-NOV-14:06 | 161.42 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 143.93 | 10-DEC-14:00 | 216.17 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 0.00 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2298.10 | 341.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.81 | 29-JAN-11:40 | 215.55 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 256.76 | 05-FEB-14:32 | 187.08 | 13-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 215.94 | 26-MAR-14:00 | 198.42 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.54 | 30-APR-13:00 | 128.07 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1535.78 | 21-MAY-12:56 | 44.86 | 01-MAY-04:53 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.12 | 11-JUN-12:50 | 27.56 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.83 | 30-JUL-14:13 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.52 | 13-AUG-14:00 | 0.00 | 01-AUG-00:02 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.49 | 03-SEP-15:54 | 26.62 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.94 | 09-OCT-15:26 | 66.21 | 20-OCT-04:53 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.70 | 19-NOV-13:50 | 105.49 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 140.62 | 10-DEC-13:10 | 140.03 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 140.62 | 0.00 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1535.78 | 215.55 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.47 | 29-JAN-11:55 | 541.46 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.16 | 05-FEB-15:10 | 448.40 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.70 | 26-MAR-14:00 | 404.67 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.05 | 30-APR-13:00 | 290.15 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2799.59 | 21-MAY-13:00 | 83.10 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.28 | 11-JUN-13:10 | 55.99 | 07-JUN-04:42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.36 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 997.16 | 13-AUG-14:00 | 0.00 | 01-AUG-00:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.22 | 03-SEP-15:51 | 65.82 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.61 | 09-OCT-15:10 | 146.67 | 20-OCT-04:13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.78 | 19-NOV-14:00 | 254.81 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.70 | 10-DEC-13:00 | 347.75 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.47 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2799.59 | 541.46 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.44 | 29-JAN-11:53 | 619.64 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.92 | 05-FEB-14:42 | 533.27 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.29 | 26-MAR-14:00 | 481.17 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.97 | 30-APR-13:00 | 359.34 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3556.93 | 21-MAY-13:00 | 116.89 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.46 | 11-JUN-13:10 | 82.60 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.57 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1273.46 | 13-AUG-14:00 | 0.00 | 01-AUG-00:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 963.05 | 02-SEP-17:02 | 80.43 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814.75 | 09-OCT-15:10 | 176.15 | 20-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.16 | 19-NOV-13:52 | 304.86 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.77 | 10-DEC-12:50 | 412.29 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.44 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3556.93 | 619.64 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.85 | 29-JAN-12:00 | 601.39 | 01-JAN-15:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.64 | 05-FEB-15:10 | 499.97 | 19-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.86 | 02-MAR-04:00 | 724.59 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.51 | 30-APR-13:00 | 273.56 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3014.87 | 21-MAY-13:00 | 102.09 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 877.76 | 09-JUN-03:00 | 44.12 | 07-JUN-04:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.82 | 30-JUL-14:20 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.72 | 16-AUG-21:02 | 0.00 | 01-AUG-00:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 934.21 | 02-SEP-17:02 | 51.65 | 25-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.89 | 09-OCT-16:10 | 116.33 | 20-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.05 | 19-NOV-14:00 | 215.39 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.95 | 10-DEC-13:00 | 342.32 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.85 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3014.87 | 724.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 49699.56 | 02-JAN-06:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49656.73 | 21-FEB-06:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54495.22 | 28-MAR-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55023.34 | 17-APR-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55364.69 | 16-MAY-04:01 | 0.00 | 7591.59 | 41762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54794.77 | 07-JUN-04:01 | 0.00 | 7591.59 | 41762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 52027.14 | 03-JUL-04:01 | 0.00 | 7591.59 | 41762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46105.72 | 15-AUG-04:01 | 0.00 | 7591.59 | 41762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54263.45 | 30-SEP-04:01 | 0.00 | 3795.79 | 37488.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54374.25 | 26-OCT-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 54553.82 | 03-NOV-04:02 | 0.00 | 6507.07 | 35796.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49706.91 | 04-DEC-06:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 46105.72 | 0.00 | 3795.79 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55364.69 | 2541.06 | 7591.59 | 41762.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8607.34 | 31-JAN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 |
February | 12706.26 | 07-FEB-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.62 | 0.00 |
March | 16836.35 | 27-MAR-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.84 | 0.00 |
April | 19279.02 | 28-APR-12:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.63 | 0.00 |
May | 20628.30 | 29-MAY-12:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.92 | 0.00 |
June | 20373.78 | 12-JUN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.60 | 0.00 |
July | 22507.43 | 21-JUL-12:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.80 | 0.00 |
August | 22267.29 | 16-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.81 | 0.00 |
September | 20400.32 | 04-SEP-12:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.68 | 0.00 |
October | 17461.32 | 04-OCT-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.79 | 0.00 |
November | 13908.83 | 06-NOV-13:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 0.00 |
December | 10183.65 | 04-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8607.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22507.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.68 | 29.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3338.07 | 28-JAN-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.55 |
February | 3816.33 | 06-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.02 | 0.00 |
March | 5425.29 | 27-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.76 | 0.00 |
April | 5884.90 | 28-APR-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.91 | 0.00 |
May | 6801.86 | 30-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.68 | 0.00 |
June | 7268.57 | 12-JUN-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.56 | 0.00 |
July | 7522.38 | 31-JUL-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.31 | 0.00 |
August | 7073.06 | 16-AUG-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.12 | 0.00 |
September | 7788.07 | 05-SEP-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.07 | 0.00 |
October | 6598.57 | 10-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.55 | 0.00 |
November | 5247.93 | 06-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.49 | 0.00 |
December | 3219.33 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3219.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7788.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.12 | 94.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4510.70 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 |
February | 4668.15 | 06-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.98 | 0.00 |
March | 7272.69 | 27-MAR-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.96 | 0.00 |
April | 8111.90 | 28-APR-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.12 | 0.00 |
May | 8140.99 | 09-MAY-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.98 | 0.00 |
June | 9546.24 | 12-JUN-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.37 | 0.00 |
July | 9570.83 | 31-JUL-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.71 | 0.00 |
August | 10055.94 | 04-AUG-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.73 | 0.00 |
September | 9362.61 | 05-SEP-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.74 | 0.00 |
October | 7963.75 | 04-OCT-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 | 0.00 |
November | 6564.92 | 06-NOV-13:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 0.00 |
December | 4419.32 | 04-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4419.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10055.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.73 | 29.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16310.58 | 30-JAN-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18130.57 | 08-FEB-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43349.20 | 28-MAR-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43631.33 | 29-APR-04:01 | 0.00 | 3795.79 | 12820.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44318.57 | 16-MAY-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44169.50 | 07-JUN-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41900.09 | 03-JUL-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35900.92 | 28-AUG-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44618.16 | 25-SEP-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44474.42 | 23-OCT-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 43544.48 | 03-NOV-04:02 | 0.00 | 6507.07 | 14652.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18101.61 | 12-DEC-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16310.58 | 0.00 | 3795.79 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44618.16 | 6035.01 | 9760.61 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17053.28 | 31-JAN-15:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20326.26 | 08-FEB-14:50 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50984.85 | 28-MAR-05:01 | 4446.85 | 7591.59 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51688.30 | 17-APR-05:01 | 4446.85 | 7591.59 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53322.84 | 08-MAY-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 53542.52 | 07-JUN-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 52819.49 | 03-JUL-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45784.55 | 15-AUG-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53989.34 | 25-SEP-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 53605.73 | 16-OCT-04:01 | 0.00 | 7591.59 | 17094.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 51378.05 | 03-NOV-05:02 | 3811.58 | 6507.07 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19185.26 | 12-DEC-15:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17053.28 | 0.00 | 6507.07 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53989.34 | 6198.29 | 9760.61 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4894.84 | 23-JAN-14:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 0.00 |
February | 7255.56 | 06-FEB-15:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.28 | 0.00 |
March | 10974.75 | 02-MAR-06:02 | 803.52 | 1371.75 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 59.11 | 0.00 |
April | 11241.15 | 29-APR-05:01 | 937.43 | 1600.37 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
May | 21963.81 | 29-MAY-12:52 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 413.42 | 0.00 |
June | 20804.97 | 11-JUN-15:22 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 586.80 | 0.00 |
July | 23316.42 | 23-JUL-10:11 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 513.79 | 0.00 |
August | 21864.53 | 06-AUG-16:42 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 514.04 | 0.00 |
September | 23727.09 | 04-SEP-12:11 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 383.42 | 0.00 |
October | 18876.86 | 08-OCT-13:52 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 280.82 | 0.00 |
November | 7990.39 | 01-NOV-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 123.32 | 0.00 |
December | 5681.25 | 03-DEC-12:22 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 51.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4894.84 | 401.76 | 685.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23727.09 | 1306.65 | 2057.62 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 586.80 | 0.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4081.43 | 29-JAN-10:52 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 |
February | 5015.18 | 05-FEB-14:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 244.52 | 0.00 |
March | 7944.88 | 27-MAR-10:50 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 145.44 | 0.00 |
April | 10004.82 | 23-APR-10:32 | 169.56 | 289.48 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 119.90 | 0.00 |
May | 18204.91 | 21-MAY-10:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 384.55 | 0.00 |
June | 15589.55 | 11-JUN-10:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 297.39 | 0.00 |
July | 19869.24 | 23-JUL-10:11 | 339.13 | 578.95 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 302.12 | 0.00 |
August | 18476.28 | 27-AUG-09:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 129.54 | 0.00 |
September | 19376.06 | 04-SEP-09:31 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.65 | 0.00 |
October | 17839.78 | 08-OCT-09:52 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.21 | 0.00 |
November | 6681.41 | 05-NOV-09:07 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 0.00 |
December | 4599.79 | 03-DEC-12:22 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 29.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4081.43 | 169.56 | 289.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19869.24 | 805.43 | 1302.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 384.55 | 15.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10581.82 | 22-JAN-14:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 |
February | 25572.52 | 05-FEB-14:42 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 309.12 | 0.00 |
March | 14672.58 | 26-MAR-13:23 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 242.67 | 0.00 |
April | 15026.40 | 30-APR-13:13 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 421.11 | 0.00 |
May | 24060.48 | 29-MAY-12:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 419.83 | 0.00 |
June | 19460.53 | 26-JUN-04:01 | 0.00 | 1600.37 | 3603.61 | 0.00 | 0.00 | 0.00 | 0.00 | 74.79 | 0.00 |
July | 25343.42 | 30-JUL-12:12 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 736.49 | 0.00 |
August | 23746.99 | 27-AUG-14:21 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 450.89 | 0.00 |
September | 27772.64 | 04-SEP-12:11 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 357.70 | 0.00 |
October | 28035.62 | 29-OCT-12:51 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 86.59 | 0.00 |
November | 26253.66 | 12-NOV-13:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 106.90 | 0.00 |
December | 25666.58 | 03-DEC-12:22 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10581.82 | 0.00 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28035.62 | 468.72 | 1600.37 | 3603.61 | 0.00 | 0.00 | 0.00 | 0.00 | 736.49 | 14.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4675.75 | 29-JAN-16:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 |
February | 10267.59 | 05-FEB-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 196.89 | 0.00 |
March | 8563.55 | 27-MAR-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 112.72 | 0.00 |
April | 12526.99 | 23-APR-15:52 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 217.50 | 0.00 |
May | 20851.81 | 29-MAY-16:11 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 201.74 | 0.00 |
June | 19382.83 | 18-JUN-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 308.84 | 0.00 |
July | 20760.61 | 02-JUL-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 345.91 | 0.00 |
August | 20240.18 | 06-AUG-16:42 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 331.33 | 0.00 |
September | 21148.66 | 04-SEP-16:11 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 389.75 | 0.00 |
October | 20761.57 | 08-OCT-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 184.79 | 0.00 |
November | 7764.73 | 12-NOV-14:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 101.99 | 0.00 |
December | 5301.96 | 01-DEC-15:00 | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4675.75 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21148.66 | 827.17 | 1302.56 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 389.75 | 18.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4665.79 | 23-JAN-14:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 | 0.00 |
February | 6348.23 | 06-FEB-14:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 61.04 | 0.00 |
March | 7661.43 | 27-MAR-13:10 | 2613.31 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 114.15 | 0.00 |
April | 8763.22 | 28-APR-12:20 | 2544.47 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 99.37 | 0.00 |
May | 18548.78 | 07-MAY-14:51 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 240.88 | 0.00 |
June | 16640.71 | 01-JUN-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 0.00 |
July | 19847.53 | 04-JUL-14:31 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 250.46 | 0.00 |
August | 19308.80 | 20-AUG-12:42 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 314.50 | 0.00 |
September | 20614.51 | 04-SEP-14:21 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 319.01 | 0.00 |
October | 15754.70 | 04-OCT-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 7.34 | 0.00 |
November | 7885.58 | 01-NOV-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.95 | 0.00 |
December | 5874.70 | 11-DEC-14:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4665.79 | 0.00 | 685.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.34 | 0.00 | |
Maximum of Months | 20614.51 | 2613.31 | 4115.24 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 319.01 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3866.74 | 29-JAN-10:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.96 |
February | 5908.56 | 05-FEB-10:12 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 | 0.00 |
March | 7272.93 | 27-MAR-10:40 | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 0.00 |
April | 14708.89 | 02-APR-10:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 54.13 | 0.00 |
May | 17717.63 | 07-MAY-10:11 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.43 | 0.00 |
June | 13290.82 | 11-JUN-10:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 159.96 | 0.00 |
July | 17135.45 | 04-JUL-11:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 73.91 | 0.00 |
August | 16866.82 | 13-AUG-10:11 | 339.13 | 578.95 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 243.76 | 0.00 |
September | 17788.65 | 04-SEP-09:41 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.23 | 0.00 |
October | 15653.45 | 22-OCT-08:52 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 57.99 | 0.00 |
November | 8030.28 | 05-NOV-09:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 0.00 |
December | 4653.52 | 01-DEC-10:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3866.74 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17788.65 | 827.22 | 1302.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 243.76 | 57.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12616.24 | 23-JAN-13:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4218.41 | 0.00 |
February | 17816.25 | 07-FEB-13:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8347.07 | 0.00 |
March | 20580.83 | 27-MAR-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 13476.32 | 0.00 |
April | 22188.87 | 28-APR-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 17468.28 | 0.00 |
May | 21478.95 | 09-MAY-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 16899.54 | 0.00 |
June | 22515.82 | 12-JUN-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18334.18 | 0.00 |
July | 23976.51 | 21-JUL-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 20353.28 | 0.00 |
August | 24455.05 | 16-AUG-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 20247.59 | 0.00 |
September | 24370.42 | 04-SEP-14:21 | 535.68 | 914.50 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 301.29 | 0.00 |
October | 24115.70 | 29-OCT-12:51 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 45.61 | 0.00 |
November | 22457.48 | 11-NOV-12:32 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 61.72 | 0.00 |
December | 22482.62 | 25-DEC-13:42 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12616.24 | 334.80 | 571.56 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24455.05 | 687.71 | 2057.62 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 20353.28 | 3.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4093.79 | 29-JAN-17:22 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 |
February | 6101.23 | 06-FEB-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 | 0.00 |
March | 7600.10 | 27-MAR-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 60.93 | 0.00 |
April | 8452.39 | 29-APR-17:08 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 66.90 | 0.00 |
May | 18478.80 | 07-MAY-15:31 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 145.72 | 0.00 |
June | 16097.58 | 18-JUN-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 167.97 | 0.00 |
July | 19048.16 | 04-JUL-14:31 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 158.59 | 0.00 |
August | 18302.32 | 13-AUG-14:51 | 381.49 | 651.28 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 288.49 | 0.00 |
September | 20057.22 | 04-SEP-16:21 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 195.85 | 0.00 |
October | 17499.04 | 22-OCT-15:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 85.52 | 0.00 |
November | 9093.16 | 11-NOV-15:52 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 | 0.00 |
December | 5273.67 | 01-DEC-15:00 | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4093.79 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20057.22 | 827.17 | 1302.56 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 288.49 | 16.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4726.96 | 23-JAN-14:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 0.00 |
February | 6735.39 | 06-FEB-14:40 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 95.26 | 0.00 |
March | 11363.77 | 02-MAR-06:02 | 803.52 | 1371.75 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 49.64 | 0.00 |
April | 9342.48 | 28-APR-12:20 | 2544.47 | 4115.24 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 155.33 | 0.00 |
May | 19075.89 | 07-MAY-14:51 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 362.92 | 0.00 |
June | 17001.22 | 11-JUN-15:22 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 493.21 | 0.00 |
July | 19303.05 | 30-JUL-13:32 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 713.71 | 0.00 |
August | 18609.81 | 06-AUG-15:42 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 444.91 | 0.00 |
September | 19001.13 | 04-SEP-15:52 | 401.76 | 685.87 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 500.98 | 0.00 |
October | 15177.71 | 10-OCT-04:01 | 0.00 | 1600.37 | 3603.63 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 0.00 |
November | 7420.44 | 01-NOV-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 102.95 | 0.00 |
December | 5449.87 | 11-DEC-14:10 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4726.96 | 0.00 | 685.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 0.00 | |
Maximum of Months | 19303.05 | 2544.47 | 4115.24 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 713.71 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3930.70 | 29-JAN-10:32 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.80 |
February | 5688.04 | 06-FEB-15:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 62.73 | 0.00 |
March | 9599.75 | 27-MAR-12:02 | 4027.14 | 6513.23 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 117.11 | 0.00 |
April | 16651.26 | 02-APR-10:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 82.29 | 0.00 |
May | 18177.12 | 07-MAY-10:11 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.18 | 0.00 |
June | 14726.61 | 11-JUN-10:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 249.03 | 0.00 |
July | 18157.36 | 23-JUL-09:41 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.55 | 0.00 |
August | 17409.37 | 27-AUG-09:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 107.06 | 0.00 |
September | 17953.57 | 03-SEP-09:51 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.45 | 0.00 |
October | 16789.04 | 08-OCT-09:52 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 0.00 |
November | 7201.16 | 02-NOV-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 | 0.00 |
December | 5348.90 | 01-DEC-11:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3930.70 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18177.12 | 4027.14 | 6513.23 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 259.55 | 48.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9395.34 | 23-JAN-13:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 37.30 | 0.00 |
February | 12934.15 | 05-FEB-13:32 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 234.32 | 0.00 |
March | 13857.15 | 26-MAR-13:43 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 241.83 | 0.00 |
April | 12878.19 | 30-APR-13:13 | 267.84 | 457.25 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 353.93 | 0.00 |
May | 21415.41 | 07-MAY-14:51 | 468.72 | 800.19 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 366.14 | 0.00 |
June | 17561.51 | 16-JUN-04:01 | 0.00 | 1600.37 | 3603.61 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 0.00 |
July | 21841.99 | 30-JUL-13:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 712.83 | 0.00 |
August | 20726.65 | 06-AUG-15:02 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 496.83 | 0.00 |
September | 22955.15 | 24-SEP-12:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 304.08 | 0.00 |
October | 23200.72 | 08-OCT-11:52 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 139.07 | 0.00 |
November | 22502.45 | 19-NOV-12:42 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 169.39 | 0.00 |
December | 23097.68 | 03-DEC-12:32 | 401.76 | 685.87 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9395.34 | 0.00 | 457.25 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | 0.00 | |
Maximum of Months | 23200.72 | 1272.23 | 2057.62 | 3603.61 | 0.00 | 0.00 | 0.00 | 0.00 | 712.83 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4156.75 | 31-JAN-16:20 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
February | 6482.68 | 06-FEB-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 | 0.00 |
March | 8135.80 | 27-MAR-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 94.06 | 0.00 |
April | 10775.43 | 23-APR-16:32 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 136.61 | 0.00 |
May | 19355.85 | 14-MAY-16:01 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 187.57 | 0.00 |
June | 17677.51 | 18-JUN-16:02 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 260.86 | 0.00 |
July | 18572.92 | 04-JUL-16:01 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 250.74 | 0.00 |
August | 18606.59 | 06-AUG-16:22 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 277.90 | 0.00 |
September | 18674.18 | 04-SEP-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 321.31 | 0.00 |
October | 18435.99 | 08-OCT-15:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 155.78 | 0.00 |
November | 8418.85 | 11-NOV-15:02 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 83.58 | 0.00 |
December | 5182.68 | 06-DEC-15:30 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4156.75 | 211.94 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19355.85 | 805.38 | 1302.56 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 321.31 | 9.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.185681E+12 | 146211.77 | 23-JAN-13:00 | 0.00 | 0.00 |
February | 0.173727E+12 | 176744.39 | 06-FEB-15:09 | 0.00 | 0.00 |
March | 0.209378E+12 | 205947.89 | 27-MAR-10:00 | 0.00 | 0.00 |
April | 0.211414E+12 | 223220.92 | 28-APR-12:09 | 0.00 | 0.00 |
May | 0.263730E+12 | 239022.97 | 30-MAY-14:00 | 0.00 | 0.00 |
June | 0.283846E+12 | 251109.48 | 09-JUN-14:30 | 0.00 | 0.00 |
July | 0.308562E+12 | 261214.89 | 21-JUL-14:09 | 0.00 | 0.00 |
August | 0.333687E+12 | 271991.78 | 10-AUG-15:39 | 0.00 | 0.00 |
September | 0.277845E+12 | 245737.65 | 05-SEP-14:09 | 0.00 | 0.00 |
October | 0.251911E+12 | 219114.86 | 06-OCT-15:20 | 0.00 | 0.00 |
November | 0.215279E+12 | 207382.67 | 01-NOV-14:09 | 0.00 | 0.00 |
December | 0.191024E+12 | 165497.97 | 05-DEC-15:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290609E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.173727E+12 | 146211.77 | 0.00 | 0.00 | |
Maximum of Months | 0.333687E+12 | 271991.78 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.223846E+11 | 0.613996E+11 | 0.230900E+10 | 0.138840E+11 | 12379742.02 | 0.568912E+09 | 0.343281E+11 | 0.00 | 0.00 | 0.00 | 0.354678E+10 | 0.00 |
February | 0.428574E+11 | 0.194210E+11 | 0.556056E+11 | 0.209511E+10 | 0.135043E+11 | 11196021.66 | 0.233846E+09 | 0.368585E+11 | 0.00 | 0.00 | 0.00 | 0.314038E+10 | 0.00 |
March | 0.509265E+11 | 0.203398E+11 | 0.635880E+11 | 0.240664E+10 | 0.178454E+11 | 12675672.10 | 33544611.68 | 0.507622E+11 | 0.00 | 0.00 | 0.00 | 0.346321E+10 | 0.00 |
April | 0.454877E+11 | 0.184482E+11 | 0.594055E+11 | 0.224272E+10 | 0.196038E+11 | 11960507.72 | 0.00 | 0.633682E+11 | 0.00 | 0.00 | 0.00 | 0.284634E+10 | 0.00 |
May | 0.490872E+11 | 0.180698E+11 | 0.624938E+11 | 0.235782E+10 | 0.278807E+11 | 12527707.06 | 0.00 | 0.101079E+12 | 0.00 | 0.00 | 0.00 | 0.274846E+10 | 0.00 |
June | 0.488499E+11 | 0.170249E+11 | 0.612808E+11 | 0.231841E+10 | 0.299001E+11 | 12231776.97 | 0.00 | 0.121952E+12 | 0.00 | 0.00 | 0.00 | 0.250793E+10 | 0.00 |
July | 0.457251E+11 | 0.177636E+11 | 0.606074E+11 | 0.228147E+10 | 0.315345E+11 | 12256437.81 | 0.00 | 0.148318E+12 | 0.00 | 0.00 | 0.00 | 0.232064E+10 | 0.00 |
August | 0.509265E+11 | 0.186193E+11 | 0.635880E+11 | 0.240664E+10 | 0.344571E+11 | 12675672.10 | 0.00 | 0.161033E+12 | 0.00 | 0.00 | 0.00 | 0.264353E+10 | 0.00 |
September | 0.454877E+11 | 0.191418E+11 | 0.593832E+11 | 0.224140E+10 | 0.282878E+11 | 11960507.72 | 0.00 | 0.120674E+12 | 0.00 | 0.00 | 0.00 | 0.261693E+10 | 0.00 |
October | 0.472479E+11 | 0.210064E+11 | 0.614108E+11 | 0.230966E+10 | 0.252231E+11 | 12379742.02 | 0.00 | 0.917043E+11 | 0.00 | 0.00 | 0.00 | 0.299662E+10 | 0.00 |
November | 0.466941E+11 | 0.213847E+11 | 0.599069E+11 | 0.224962E+10 | 0.197302E+11 | 12059151.09 | 220620.10 | 0.620778E+11 | 0.00 | 0.00 | 0.00 | 0.322354E+10 | 0.00 |
December | 0.457251E+11 | 0.226999E+11 | 0.605962E+11 | 0.228081E+10 | 0.148620E+11 | 12256437.81 | 0.144219E+09 | 0.413074E+11 | 0.00 | 0.00 | 0.00 | 0.339602E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.236304E+12 | 0.729266E+12 | 0.274993E+11 | 0.276713E+12 | 0.146559E+09 | 0.980742E+09 | 0.103346E+13 | 0.00 | 0.00 | 0.00 | 0.354504E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.170249E+11 | 0.556056E+11 | 0.209511E+10 | 0.135043E+11 | 11196021.66 | 0.00 | 0.343281E+11 | 0.00 | 0.00 | 0.00 | 0.232064E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.226999E+11 | 0.635880E+11 | 0.240664E+10 | 0.344571E+11 | 12675672.10 | 0.568912E+09 | 0.161033E+12 | 0.00 | 0.00 | 0.00 | 0.354678E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:09 | 15595.80 | 09-JAN-07:40 | 6.85 | 01-JAN-06:10 | 23552.60 | 20-JAN-07:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 06-FEB-08:09 | 22920.57 | 06-FEB-15:09 | 6.85 | 01-FEB-06:10 | 15395.97 | 13-FEB-07:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 01-MAR-13:09 | 29353.64 | 27-MAR-14:50 | 6.85 | 01-MAR-06:10 | 9314.22 | 08-MAR-07:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 28-APR-11:09 | 29677.98 | 28-APR-12:50 | 6.85 | 01-APR-05:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 09-MAY-12:09 | 33301.09 | 10-MAY-14:00 | 6.85 | 14-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 01-JUN-11:09 | 35138.08 | 09-JUN-15:30 | 6.85 | 01-JUN-22:40 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 03-JUL-16:10 | 35136.01 | 31-JUL-15:39 | 6.85 | 02-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 01-AUG-11:09 | 34371.10 | 10-AUG-15:30 | 6.85 | 04-AUG-11:09 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 01-SEP-12:09 | 33641.69 | 05-SEP-14:30 | 6.85 | 03-SEP-10:30 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 03-OCT-16:10 | 30103.38 | 02-OCT-14:30 | 6.85 | 09-OCT-11:00 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 01-NOV-12:09 | 26581.13 | 02-NOV-14:00 | 6.85 | 01-NOV-05:10 | 367.70 | 22-NOV-07:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 01-DEC-08:20 | 19584.60 | 04-DEC-13:09 | 6.85 | 01-DEC-06:10 | 12590.98 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 15595.80 | 6.85 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 35138.08 | 6.85 | 23552.60 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 37380.31 | 23-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4616.80 | 13-JAN-12:20 | 0.00 |
February | 58456.24 | 06-FEB-15:09 | 0.00 | 0.00 | 0.00 | 4608.11 | 01-FEB-12:50 | 0.00 |
March | 82631.96 | 27-MAR-10:00 | 0.00 | 0.00 | 0.00 | 4569.17 | 01-MAR-12:00 | 0.00 |
April | 101765.73 | 28-APR-12:09 | 0.00 | 0.00 | 0.00 | 3954.40 | 05-APR-11:20 | 0.00 |
May | 111428.05 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 3543.86 | 01-MAY-11:00 | 0.00 |
June | 122407.82 | 09-JUN-14:09 | 0.00 | 0.00 | 0.00 | 3204.33 | 01-JUN-11:39 | 0.00 |
July | 132620.85 | 21-JUL-14:09 | 0.00 | 0.00 | 0.00 | 3183.52 | 31-JUL-11:39 | 0.00 |
August | 142390.76 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 3397.46 | 31-AUG-11:39 | 0.00 |
September | 118040.71 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | 3825.78 | 28-SEP-11:30 | 0.00 |
October | 95587.79 | 05-OCT-12:30 | 0.00 | 0.00 | 0.00 | 4214.20 | 31-OCT-11:50 | 0.00 |
November | 86024.28 | 01-NOV-14:09 | 0.00 | 0.00 | 0.00 | 4577.72 | 30-NOV-12:39 | 0.00 |
December | 52223.63 | 05-DEC-15:09 | 0.00 | 0.00 | 0.00 | 4612.44 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 37380.31 | 0.00 | 0.00 | 0.00 | 3183.52 | 0.00 | ||
Maximum of Months | 142390.76 | 0.00 | 0.00 | 0.00 | 4616.80 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 146211.77 | 23-JAN-13:00 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 14509.07 | 6.85 | 0.00 | 37380.31 | 0.00 |
February | 176744.39 | 06-FEB-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 22920.57 | 6.85 | 0.00 | 58456.24 | 0.00 |
March | 205947.89 | 27-MAR-10:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 27296.84 | 6.85 | 0.00 | 82631.96 | 0.00 |
April | 223220.92 | 28-APR-12:09 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 27871.58 | 6.85 | 0.00 | 101765.73 | 0.00 |
May | 239022.97 | 30-MAY-14:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 33158.41 | 6.85 | 0.00 | 111124.50 | 0.00 |
June | 251109.48 | 09-JUN-14:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 34145.56 | 6.85 | 0.00 | 122227.42 | 0.00 |
July | 261214.89 | 21-JUL-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 34138.89 | 6.85 | 0.00 | 132620.85 | 0.00 |
August | 271991.78 | 10-AUG-15:39 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 34315.97 | 6.85 | 0.00 | 142334.61 | 0.00 |
September | 245737.65 | 05-SEP-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 33462.59 | 6.85 | 0.00 | 117530.95 | 0.00 |
October | 219114.86 | 06-OCT-15:20 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 29251.01 | 6.85 | 0.00 | 94272.09 | 0.00 |
November | 207382.67 | 01-NOV-14:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 26300.26 | 6.85 | 0.00 | 86024.28 | 0.00 |
December | 165497.97 | 05-DEC-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 17912.77 | 6.85 | 0.00 | 52223.63 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 146211.77 | 49443.18 | 39196.26 | 0.00 | 1410.29 | 14509.07 | 6.85 | 0.00 | 37380.31 | 0.00 | |
Maximum of Months | 271991.78 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 34315.97 | 6.85 | 0.00 | 142334.61 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.50 | 0.67 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.83 | 7.50 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.99 | 6.67 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.10 | 11.17 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.08 | 7.17 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.88 | 7.33 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.60 | 2.67 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 52.50 | 27.96 | 43.17 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.10 | 11.17 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.75 | 3.67 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.18 | 11.67 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.26 | 9.17 | 28.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 28.42 | 14.17 | 28.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.41 | 9.33 | 28.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.26 | 10.50 | 28.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.78 | 7.33 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 72.83 | 28.23 | 65.83 | 28.26 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 28.42 | 14.17 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.70 | 1.00 | 27.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.99 | 1.17 | 27.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.68 | 2.67 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.80 | 7.33 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.84 | 6.00 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.06 | 10.00 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.28 | 7.17 | 28.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.40 | 8.83 | 28.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.39 | 10.17 | 28.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.93 | 5.50 | 27.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.71 | 1.33 | 27.71 |
Annual Sum or Average | 0.00 | 0.00 | 68.00 | 28.10 | 61.17 | 28.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.40 | 10.17 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.78 | 0.67 | 27.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.89 | 2.67 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.39 | 6.50 | 28.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.34 | 5.83 | 28.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 28.46 | 9.83 | 28.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.47 | 7.00 | 28.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.42 | 6.50 | 28.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.06 | 5.50 | 28.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.52 | 0.33 | 27.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 58.33 | 28.34 | 44.83 | 28.38 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 28.47 | 9.83 | 28.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.57 | 1.50 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.46 | 5.33 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.70 | 10.33 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.67 | 7.17 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.66 | 5.33 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 1.17 | 27.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 36.67 | 27.63 | 30.83 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.70 | 10.33 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.57 | 1.33 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.86 | 8.33 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.84 | 8.33 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 28.07 | 13.50 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.02 | 9.33 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.97 | 10.67 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.61 | 7.67 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.67 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 63.50 | 27.91 | 59.83 | 27.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 28.07 | 13.50 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.67 | 1.00 | 27.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.73 | 4.17 | 25.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 25.67 | 5.33 | 25.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 25.32 | 27.17 | 25.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 25.46 | 36.17 | 25.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 26.06 | 47.67 | 26.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 26.17 | 53.17 | 26.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 | 26.09 | 46.50 | 26.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 26.19 | 36.33 | 26.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 26.57 | 14.67 | 26.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.89 | 2.00 | 27.89 |
Annual Sum or Average | 0.00 | 0.00 | 280.33 | 25.99 | 274.33 | 25.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.32 | 0.17 | 25.32 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 27.89 | 53.17 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.42 | 1.17 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.06 | 5.17 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.95 | 5.33 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.03 | 8.33 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.15 | 6.33 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.07 | 7.50 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.87 | 5.33 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 54.50 | 28.00 | 40.17 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.15 | 8.33 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.59 | 5.33 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.68 | 6.17 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.81 | 10.67 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.81 | 7.17 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.75 | 5.17 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.17 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 42.50 | 27.74 | 35.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.81 | 10.67 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.62 | 3.50 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.96 | 10.33 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.97 | 9.33 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 28.17 | 13.67 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.15 | 9.33 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.03 | 10.00 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.64 | 6.17 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 65.33 | 28.00 | 62.83 | 28.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 28.17 | 13.67 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.85 | 1.17 | 27.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.58 | 1.50 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.59 | 4.33 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.47 | 4.33 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.76 | 9.33 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.03 | 7.00 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.20 | 8.67 | 28.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.24 | 10.33 | 28.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.92 | 6.17 | 27.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.87 | 1.67 | 27.87 |
Annual Sum or Average | 0.00 | 0.00 | 58.67 | 27.93 | 55.50 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.24 | 10.33 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.72 | 2.00 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.29 | 5.33 | 28.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.21 | 4.83 | 28.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.34 | 7.83 | 28.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.28 | 6.00 | 28.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.26 | 5.67 | 28.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.93 | 4.83 | 27.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.34 | 0.50 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 48.83 | 28.20 | 37.67 | 28.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.34 | 7.83 | 28.41 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 381.50 | 24.61 | 0.00 | 24.61 |
February | 0.00 | 0.00 | 389.17 | 24.55 | 0.00 | 24.55 |
March | 0.00 | 0.00 | 456.00 | 24.48 | 0.00 | 24.48 |
April | 0.00 | 0.00 | 478.00 | 24.45 | 0.00 | 24.45 |
May | 0.00 | 0.00 | 504.33 | 24.43 | 0.00 | 24.43 |
June | 0.00 | 0.00 | 496.00 | 24.36 | 0.00 | 24.36 |
July | 0.00 | 0.00 | 497.00 | 24.34 | 0.00 | 24.34 |
August | 0.00 | 0.00 | 514.00 | 24.27 | 0.00 | 24.27 |
September | 0.00 | 0.00 | 485.00 | 24.38 | 0.00 | 24.38 |
October | 0.00 | 0.00 | 496.33 | 24.46 | 0.00 | 24.46 |
November | 0.00 | 0.00 | 484.33 | 24.50 | 0.00 | 24.50 |
December | 0.00 | 0.00 | 449.50 | 24.51 | 0.00 | 24.51 |
Annual Sum or Average | 0.00 | 5631.17 | 24.44 | 0.00 | 24.44 | |
Minimum of Months | 0.00 | 0.00 | 381.50 | 24.27 | 0.00 | 24.27 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.61 | 0.00 | 24.61 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 155.17 | 23.36 | 144.50 | 23.79 | 0.00 | 23.79 |
February | 90.00 | 23.36 | 220.67 | 24.01 | 0.00 | 24.01 |
March | 46.33 | 23.44 | 311.83 | 24.20 | 0.00 | 24.20 |
April | 6.00 | 23.57 | 406.17 | 24.28 | 0.00 | 24.28 |
May | 0.00 | 0.00 | 495.00 | 24.32 | 0.00 | 24.32 |
June | 0.00 | 0.00 | 496.00 | 24.27 | 0.00 | 24.27 |
July | 0.00 | 0.00 | 497.00 | 24.26 | 0.00 | 24.26 |
August | 0.00 | 0.00 | 514.00 | 24.22 | 0.00 | 24.22 |
September | 0.00 | 0.00 | 485.00 | 24.31 | 0.00 | 24.31 |
October | 0.00 | 0.00 | 484.67 | 24.36 | 0.00 | 24.36 |
November | 2.67 | 23.71 | 442.33 | 24.31 | 0.00 | 24.31 |
December | 87.83 | 23.35 | 256.50 | 24.04 | 0.00 | 24.04 |
Annual Sum or Average | 388.00 | 23.37 | 4753.67 | 24.22 | 0.00 | 24.22 |
Minimum of Months | 0.00 | 0.00 | 144.50 | 23.79 | 0.00 | 23.79 |
Maximum of Months | 155.17 | 23.71 | 514.00 | 24.36 | 0.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 326.83 | 22.92 | 86.00 | 23.14 | 12.83 | 23.16 |
February | 218.67 | 22.99 | 143.00 | 23.44 | 0.00 | 23.44 |
March | 151.17 | 23.15 | 233.83 | 23.78 | 0.00 | 23.78 |
April | 41.33 | 23.17 | 346.17 | 24.15 | 0.00 | 24.15 |
May | 0.00 | 0.00 | 483.67 | 24.33 | 0.00 | 24.33 |
June | 0.00 | 0.00 | 494.33 | 24.29 | 0.00 | 24.29 |
July | 0.00 | 0.00 | 496.83 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 514.00 | 24.23 | 0.00 | 24.23 |
September | 0.00 | 0.00 | 482.50 | 24.32 | 0.00 | 24.32 |
October | 3.83 | 23.36 | 461.67 | 24.32 | 0.00 | 24.32 |
November | 56.00 | 23.23 | 315.33 | 24.07 | 0.00 | 24.07 |
December | 259.33 | 22.96 | 142.00 | 23.36 | 0.00 | 23.36 |
Annual Sum or Average | 1057.17 | 23.00 | 4199.33 | 24.01 | 12.83 | 24.01 |
Minimum of Months | 0.00 | 0.00 | 86.00 | 23.14 | 0.00 | 23.16 |
Maximum of Months | 326.83 | 23.36 | 514.00 | 24.33 | 12.83 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 410.50 | 21.97 | 31.67 | 22.08 | 3.33 | 22.07 |
February | 296.50 | 22.13 | 105.17 | 22.64 | 0.33 | 22.64 |
March | 243.67 | 22.40 | 200.83 | 23.18 | 0.00 | 23.18 |
April | 115.17 | 22.84 | 326.17 | 23.91 | 15.83 | 23.95 |
May | 48.67 | 25.64 | 469.67 | 24.59 | 36.50 | 24.72 |
June | 49.17 | 26.42 | 490.00 | 24.62 | 49.17 | 24.77 |
July | 66.17 | 26.69 | 496.50 | 24.80 | 66.17 | 25.00 |
August | 48.67 | 26.61 | 514.00 | 24.61 | 48.67 | 24.77 |
September | 56.50 | 26.05 | 468.67 | 24.63 | 52.17 | 24.78 |
October | 69.00 | 24.32 | 426.67 | 24.39 | 36.33 | 24.49 |
November | 145.67 | 22.58 | 269.67 | 23.61 | 1.17 | 23.61 |
December | 351.33 | 22.16 | 88.33 | 22.53 | 3.17 | 22.52 |
Annual Sum or Average | 1901.00 | 22.88 | 3887.33 | 23.89 | 312.83 | 24.01 |
Minimum of Months | 48.67 | 21.97 | 31.67 | 22.08 | 0.00 | 22.07 |
Maximum of Months | 410.50 | 26.69 | 514.00 | 24.80 | 66.17 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 368.00 | 21.98 | 55.67 | 22.23 | 4.33 | 22.21 |
February | 251.00 | 22.02 | 150.00 | 22.82 | 0.33 | 22.81 |
March | 215.33 | 22.29 | 239.83 | 23.30 | 0.33 | 23.30 |
April | 116.50 | 23.19 | 352.00 | 24.09 | 26.17 | 24.19 |
May | 60.67 | 26.17 | 473.33 | 24.70 | 52.00 | 24.88 |
June | 54.50 | 26.61 | 488.50 | 24.65 | 54.50 | 24.83 |
July | 72.33 | 26.86 | 496.00 | 24.84 | 72.33 | 25.07 |
August | 54.50 | 26.79 | 514.00 | 24.64 | 54.50 | 24.83 |
September | 68.00 | 26.37 | 470.17 | 24.72 | 64.00 | 24.92 |
October | 80.17 | 24.88 | 431.83 | 24.54 | 49.67 | 24.69 |
November | 129.33 | 22.47 | 306.17 | 23.72 | 1.17 | 23.72 |
December | 316.50 | 22.12 | 112.67 | 22.62 | 7.67 | 22.62 |
Annual Sum or Average | 1786.83 | 23.09 | 4090.17 | 24.00 | 387.00 | 24.15 |
Minimum of Months | 54.50 | 21.98 | 55.67 | 22.23 | 0.33 | 22.21 |
Maximum of Months | 368.00 | 26.86 | 514.00 | 24.84 | 72.33 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 283.00 | 21.96 | 188.00 | 22.94 | 3.00 | 22.93 |
February | 229.50 | 22.20 | 192.67 | 23.19 | 3.17 | 23.21 |
March | 208.50 | 22.42 | 252.33 | 23.43 | 4.50 | 23.46 |
April | 125.17 | 22.93 | 330.50 | 23.95 | 21.50 | 24.02 |
May | 57.67 | 25.02 | 456.17 | 24.51 | 35.00 | 24.63 |
June | 44.17 | 26.16 | 478.50 | 24.53 | 42.33 | 24.66 |
July | 55.83 | 26.65 | 495.50 | 24.70 | 55.83 | 24.88 |
August | 45.33 | 26.67 | 514.00 | 24.57 | 45.33 | 24.73 |
September | 62.33 | 26.24 | 466.33 | 24.69 | 56.50 | 24.87 |
October | 91.33 | 25.21 | 440.67 | 24.66 | 61.00 | 24.85 |
November | 128.67 | 23.25 | 334.67 | 24.13 | 22.17 | 24.25 |
December | 251.50 | 22.29 | 211.83 | 23.28 | 7.83 | 23.33 |
Annual Sum or Average | 1583.00 | 23.18 | 4361.17 | 24.09 | 358.17 | 24.23 |
Minimum of Months | 44.17 | 21.96 | 188.00 | 22.94 | 3.00 | 22.93 |
Maximum of Months | 283.00 | 26.67 | 514.00 | 24.70 | 61.00 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 392.33 | 21.74 | 73.33 | 22.11 | 4.17 | 22.09 |
February | 301.33 | 21.91 | 113.50 | 22.52 | 0.33 | 22.52 |
March | 257.50 | 22.13 | 197.67 | 23.01 | 2.17 | 23.03 |
April | 150.67 | 22.68 | 305.50 | 23.77 | 23.33 | 23.86 |
May | 75.00 | 24.46 | 438.83 | 24.44 | 34.83 | 24.58 |
June | 62.67 | 25.88 | 462.83 | 24.55 | 52.17 | 24.73 |
July | 60.67 | 26.72 | 490.67 | 24.67 | 60.67 | 24.87 |
August | 49.33 | 26.63 | 509.50 | 24.51 | 49.33 | 24.68 |
September | 69.17 | 25.43 | 440.33 | 24.55 | 50.83 | 24.72 |
October | 104.67 | 23.74 | 390.50 | 24.25 | 39.17 | 24.38 |
November | 180.00 | 22.28 | 251.50 | 23.39 | 3.00 | 23.41 |
December | 352.17 | 21.90 | 109.33 | 22.42 | 5.17 | 22.42 |
Annual Sum or Average | 2055.50 | 22.67 | 3783.50 | 23.75 | 325.17 | 23.88 |
Minimum of Months | 49.33 | 21.74 | 73.33 | 22.11 | 0.33 | 22.09 |
Maximum of Months | 392.33 | 26.72 | 509.50 | 24.67 | 60.67 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 325.83 | 22.73 | 82.33 | 22.98 | 0.00 | 22.98 |
February | 225.67 | 22.77 | 149.67 | 23.30 | 0.00 | 23.30 |
March | 175.50 | 22.85 | 241.17 | 23.61 | 0.00 | 23.61 |
April | 53.33 | 23.13 | 369.50 | 24.14 | 5.50 | 24.15 |
May | 13.83 | 26.64 | 499.33 | 24.50 | 13.83 | 24.56 |
June | 31.17 | 26.52 | 496.00 | 24.56 | 31.17 | 24.67 |
July | 54.17 | 26.73 | 497.00 | 24.79 | 54.17 | 24.96 |
August | 38.33 | 26.74 | 514.00 | 24.62 | 38.33 | 24.76 |
September | 37.33 | 26.53 | 485.00 | 24.63 | 37.33 | 24.76 |
October | 15.17 | 26.31 | 497.00 | 24.50 | 15.17 | 24.55 |
November | 9.67 | 23.06 | 435.33 | 24.25 | 0.00 | 24.25 |
December | 185.83 | 22.88 | 216.17 | 23.55 | 0.00 | 23.55 |
Annual Sum or Average | 1165.83 | 23.43 | 4482.50 | 24.19 | 195.50 | 24.27 |
Minimum of Months | 9.67 | 22.73 | 82.33 | 22.98 | 0.00 | 22.98 |
Maximum of Months | 325.83 | 26.74 | 514.00 | 24.79 | 54.17 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 271.67 | 22.54 | 130.00 | 23.05 | 0.00 | 23.05 |
February | 192.33 | 22.56 | 196.50 | 23.38 | 0.00 | 23.38 |
March | 161.83 | 22.60 | 273.50 | 23.62 | 0.00 | 23.62 |
April | 61.50 | 23.27 | 379.17 | 24.21 | 10.33 | 24.27 |
May | 34.67 | 26.75 | 495.67 | 24.62 | 34.67 | 24.75 |
June | 42.50 | 26.67 | 496.00 | 24.60 | 42.50 | 24.75 |
July | 65.00 | 26.81 | 497.00 | 24.82 | 65.00 | 25.02 |
August | 47.67 | 26.82 | 514.00 | 24.65 | 47.67 | 24.82 |
September | 56.17 | 26.69 | 485.00 | 24.72 | 56.17 | 24.90 |
October | 37.17 | 26.54 | 495.50 | 24.62 | 37.17 | 24.74 |
November | 14.17 | 23.16 | 429.50 | 24.28 | 1.00 | 24.28 |
December | 174.33 | 22.66 | 229.00 | 23.52 | 0.00 | 23.52 |
Annual Sum or Average | 1159.00 | 23.64 | 4620.83 | 24.25 | 294.50 | 24.37 |
Minimum of Months | 14.17 | 22.54 | 130.00 | 23.05 | 0.00 | 23.05 |
Maximum of Months | 271.67 | 26.82 | 514.00 | 24.82 | 65.00 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 188.67 | 22.52 | 237.83 | 23.60 | 0.33 | 23.61 |
February | 137.67 | 22.63 | 252.50 | 23.76 | 5.17 | 23.79 |
March | 129.83 | 22.67 | 314.33 | 23.82 | 7.00 | 23.83 |
April | 66.17 | 23.08 | 381.50 | 24.16 | 16.67 | 24.17 |
May | 35.33 | 24.75 | 493.33 | 24.49 | 34.50 | 24.51 |
June | 91.83 | 24.80 | 496.00 | 24.54 | 91.83 | 24.57 |
July | 144.83 | 25.25 | 497.00 | 24.80 | 144.83 | 24.88 |
August | 155.50 | 25.35 | 514.00 | 24.80 | 155.50 | 24.91 |
September | 135.67 | 25.56 | 485.00 | 24.86 | 135.67 | 24.99 |
October | 100.00 | 25.75 | 500.50 | 24.85 | 100.00 | 24.98 |
November | 57.83 | 25.31 | 469.00 | 24.62 | 51.50 | 24.71 |
December | 112.33 | 22.97 | 326.50 | 24.07 | 15.50 | 24.13 |
Annual Sum or Average | 1355.67 | 24.10 | 4967.50 | 24.44 | 758.50 | 24.53 |
Minimum of Months | 35.33 | 22.52 | 237.83 | 23.60 | 0.33 | 23.61 |
Maximum of Months | 188.67 | 25.75 | 514.00 | 24.86 | 155.50 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 334.17 | 22.41 | 100.17 | 22.82 | 0.00 | 22.82 |
February | 234.67 | 22.45 | 144.67 | 23.11 | 0.00 | 23.11 |
March | 186.33 | 22.52 | 241.83 | 23.48 | 0.33 | 23.48 |
April | 84.33 | 22.95 | 353.33 | 24.04 | 9.50 | 24.08 |
May | 25.83 | 26.35 | 475.17 | 24.53 | 22.50 | 24.63 |
June | 39.17 | 26.78 | 494.00 | 24.55 | 39.17 | 24.70 |
July | 53.50 | 26.83 | 497.00 | 24.72 | 53.50 | 24.91 |
August | 45.17 | 26.80 | 514.00 | 24.60 | 45.17 | 24.76 |
September | 45.33 | 26.76 | 484.67 | 24.63 | 45.33 | 24.80 |
October | 26.83 | 26.55 | 485.67 | 24.52 | 26.67 | 24.62 |
November | 29.50 | 23.12 | 402.00 | 24.20 | 2.67 | 24.22 |
December | 212.83 | 22.53 | 196.67 | 23.31 | 0.00 | 23.31 |
Annual Sum or Average | 1317.67 | 23.27 | 4389.17 | 24.11 | 244.83 | 24.22 |
Minimum of Months | 25.83 | 22.41 | 100.17 | 22.82 | 0.00 | 22.82 |
Maximum of Months | 334.17 | 26.83 | 514.00 | 24.72 | 53.50 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 363.17 | 22.45 | 61.67 | 22.68 | 0.00 | 22.68 |
February | 252.33 | 22.58 | 138.50 | 23.12 | 0.17 | 23.12 |
March | 186.67 | 22.77 | 240.17 | 23.56 | 0.00 | 23.56 |
April | 65.83 | 23.21 | 367.00 | 24.15 | 12.17 | 24.17 |
May | 27.83 | 26.52 | 497.17 | 24.58 | 27.83 | 24.68 |
June | 47.33 | 26.41 | 496.00 | 24.63 | 47.33 | 24.77 |
July | 63.67 | 26.68 | 497.00 | 24.82 | 63.67 | 25.01 |
August | 45.33 | 26.60 | 514.00 | 24.63 | 45.33 | 24.78 |
September | 47.50 | 26.34 | 482.33 | 24.65 | 47.50 | 24.79 |
October | 32.33 | 25.34 | 470.67 | 24.47 | 26.17 | 24.54 |
November | 69.83 | 22.91 | 341.83 | 24.00 | 0.83 | 24.00 |
December | 277.67 | 22.58 | 138.50 | 23.09 | 0.83 | 23.09 |
Annual Sum or Average | 1479.50 | 23.29 | 4244.83 | 24.11 | 271.83 | 24.21 |
Minimum of Months | 27.83 | 22.45 | 61.67 | 22.68 | 0.00 | 22.68 |
Maximum of Months | 363.17 | 26.68 | 514.00 | 24.82 | 63.67 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 304.33 | 22.20 | 53.83 | 22.53 | 0.00 | 22.53 |
February | 213.33 | 22.29 | 123.50 | 23.02 | 0.00 | 23.02 |
March | 178.50 | 22.49 | 194.50 | 23.44 | 0.33 | 23.44 |
April | 88.00 | 23.37 | 292.67 | 24.24 | 20.17 | 24.33 |
May | 47.50 | 26.59 | 412.17 | 24.78 | 46.17 | 24.95 |
June | 52.17 | 26.58 | 417.67 | 24.73 | 52.17 | 24.91 |
July | 69.00 | 26.77 | 421.50 | 24.95 | 69.00 | 25.17 |
August | 51.67 | 26.74 | 433.00 | 24.73 | 51.67 | 24.93 |
September | 60.17 | 26.57 | 404.33 | 24.82 | 59.67 | 25.02 |
October | 53.50 | 25.60 | 384.50 | 24.66 | 42.00 | 24.81 |
November | 83.00 | 22.66 | 273.50 | 23.96 | 0.83 | 23.96 |
December | 251.00 | 22.34 | 109.00 | 22.91 | 1.50 | 22.92 |
Annual Sum or Average | 1452.17 | 23.36 | 3520.17 | 24.16 | 343.50 | 24.32 |
Minimum of Months | 47.50 | 22.20 | 53.83 | 22.53 | 0.00 | 22.53 |
Maximum of Months | 304.33 | 26.77 | 433.00 | 24.95 | 69.00 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 243.00 | 22.45 | 215.50 | 23.40 | 0.17 | 23.41 |
February | 185.17 | 22.62 | 222.83 | 23.58 | 3.50 | 23.60 |
March | 154.67 | 22.75 | 291.00 | 23.75 | 3.67 | 23.78 |
April | 80.33 | 23.28 | 365.33 | 24.17 | 16.67 | 24.22 |
May | 29.00 | 26.02 | 482.17 | 24.53 | 25.17 | 24.62 |
June | 38.50 | 26.24 | 494.50 | 24.52 | 38.50 | 24.64 |
July | 53.17 | 26.56 | 497.00 | 24.71 | 53.17 | 24.88 |
August | 41.83 | 26.67 | 514.00 | 24.60 | 41.83 | 24.74 |
September | 55.50 | 26.62 | 481.50 | 24.73 | 55.50 | 24.90 |
October | 65.83 | 26.33 | 477.67 | 24.76 | 60.33 | 24.95 |
November | 68.00 | 24.22 | 384.83 | 24.45 | 23.83 | 24.56 |
December | 189.67 | 22.74 | 256.33 | 23.73 | 8.00 | 23.79 |
Annual Sum or Average | 1204.67 | 23.65 | 4682.67 | 24.28 | 330.33 | 24.40 |
Minimum of Months | 29.00 | 22.45 | 215.50 | 23.40 | 0.17 | 23.41 |
Maximum of Months | 243.00 | 26.67 | 514.00 | 24.76 | 60.33 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.17 | 22.11 | 86.00 | 22.52 | 0.00 | 22.52 |
February | 270.83 | 22.25 | 129.17 | 22.88 | 0.00 | 22.88 |
March | 213.33 | 22.40 | 227.50 | 23.33 | 1.17 | 23.34 |
April | 112.83 | 22.97 | 337.17 | 23.98 | 18.83 | 24.05 |
May | 44.33 | 25.47 | 462.67 | 24.53 | 30.00 | 24.65 |
June | 47.67 | 26.63 | 482.17 | 24.57 | 47.67 | 24.74 |
July | 54.50 | 26.78 | 495.33 | 24.68 | 54.50 | 24.87 |
August | 45.33 | 26.72 | 514.00 | 24.54 | 45.33 | 24.70 |
September | 50.17 | 26.34 | 466.17 | 24.60 | 47.00 | 24.76 |
October | 65.17 | 24.52 | 430.17 | 24.40 | 34.83 | 24.52 |
November | 120.00 | 22.54 | 302.83 | 23.76 | 2.00 | 23.77 |
December | 309.33 | 22.23 | 133.83 | 22.82 | 1.33 | 22.83 |
Annual Sum or Average | 1704.67 | 22.98 | 4067.00 | 23.95 | 282.67 | 24.07 |
Minimum of Months | 44.33 | 22.11 | 86.00 | 22.52 | 0.00 | 22.52 |
Maximum of Months | 371.17 | 26.78 | 514.00 | 24.68 | 54.50 | 24.87 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.46694 | 42.56889 | 0.51871 | 10.93520 |
February | 454.00000 | 24.47444 | 45.36678 | 0.54698 | 11.57268 |
March | 514.00000 | 24.42875 | 45.11064 | 0.54873 | 11.59855 |
April | 485.00000 | 24.44271 | 47.85066 | 0.58376 | 12.46368 |
May | 508.00000 | 24.42294 | 50.30382 | -0.2203 | 6.58286 |
June | 496.00000 | 24.35634 | 53.19678 | -0.2159 | 6.40976 |
July | 497.00000 | 24.33878 | 53.38432 | -0.2264 | 6.36869 |
August | 514.00000 | 24.27421 | 53.70164 | -0.2391 | 6.43066 |
September | 485.00000 | 24.38047 | 53.08360 | -0.2122 | 6.36845 |
October | 502.00000 | 24.45406 | 51.03914 | 0.62237 | 13.44173 |
November | 489.00000 | 24.49127 | 49.89210 | 0.61394 | 13.19407 |
December | 497.00000 | 24.46691 | 46.53417 | 0.55839 | 11.83249 |
Annual Sum or Average | 5943.00000 | 24.41571 | 49.35673 | 0.23669 | 9.74475 |
Minimum of Months | 454.00000 | 24.27421 | 42.56889 | -0.2391 | 6.36845 |
Maximum of Months | 514.00000 | 24.49127 | 53.70164 | 0.62237 | 13.44173 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.90462 | 43.15157 | 0.35303 | 7.90841 |
February | 454.00000 | 24.01809 | 45.86968 | 0.40982 | 8.79198 |
March | 514.00000 | 24.12894 | 45.32672 | 0.44993 | 9.46652 |
April | 485.00000 | 24.23029 | 48.55948 | 0.51321 | 10.73133 |
May | 508.00000 | 24.31304 | 51.73079 | -0.2734 | 6.94032 |
June | 496.00000 | 24.27417 | 54.69845 | -0.2585 | 6.69726 |
July | 497.00000 | 24.26152 | 54.95166 | -0.2620 | 6.63875 |
August | 514.00000 | 24.21653 | 55.59006 | -0.2671 | 6.66037 |
September | 485.00000 | 24.31322 | 55.01599 | -0.2475 | 6.63381 |
October | 502.00000 | 24.34466 | 52.44920 | 0.58389 | 12.38767 |
November | 489.00000 | 24.27677 | 50.65245 | 0.53707 | 11.21350 |
December | 497.00000 | 24.00633 | 46.87892 | 0.41563 | 8.91869 |
Annual Sum or Average | 5943.00000 | 24.19149 | 50.43081 | 0.16004 | 8.57387 |
Minimum of Months | 454.00000 | 23.90462 | 43.15157 | -0.2734 | 6.63381 |
Maximum of Months | 514.00000 | 24.34466 | 55.59006 | 0.58389 | 12.38767 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.29186 | 44.38315 | 0.21120 | 6.82434 |
February | 454.00000 | 23.55064 | 45.61131 | 0.29766 | 7.58336 |
March | 514.00000 | 23.82368 | 44.76239 | 0.37958 | 8.56086 |
April | 485.00000 | 24.07919 | 47.70594 | 0.48552 | 10.27810 |
May | 508.00000 | 24.30611 | 50.80262 | -0.2482 | 6.79773 |
June | 496.00000 | 24.28382 | 54.30766 | -0.2199 | 6.42584 |
July | 497.00000 | 24.29293 | 54.84072 | -0.2078 | 6.30070 |
August | 514.00000 | 24.23075 | 55.53972 | -0.2212 | 6.32456 |
September | 485.00000 | 24.31317 | 54.85274 | -0.2178 | 6.47513 |
October | 502.00000 | 24.27447 | 51.84104 | 0.57526 | 12.23362 |
November | 489.00000 | 24.00197 | 50.01771 | 0.46996 | 9.95438 |
December | 497.00000 | 23.47396 | 46.49947 | 0.28258 | 7.42829 |
Annual Sum or Average | 5943.00000 | 23.99629 | 50.12239 | 0.13007 | 7.92829 |
Minimum of Months | 454.00000 | 23.29186 | 44.38315 | -0.2482 | 6.30070 |
Maximum of Months | 514.00000 | 24.31317 | 55.53972 | 0.57526 | 12.23362 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.29692 | 46.31556 | -0.0007 | 6.56737 |
February | 454.00000 | 22.75432 | 48.95894 | 0.14854 | 7.21343 |
March | 514.00000 | 23.25137 | 46.82003 | 0.28567 | 8.28895 |
April | 485.00000 | 23.83952 | 49.37433 | 0.48376 | 11.06837 |
May | 508.00000 | 24.38562 | 51.00710 | -0.1180 | 6.90645 |
June | 496.00000 | 24.42118 | 54.83687 | -0.0477 | 6.47099 |
July | 497.00000 | 24.54988 | 54.83509 | 0.01349 | 6.68103 |
August | 514.00000 | 24.42277 | 55.74071 | -0.0225 | 6.28360 |
September | 485.00000 | 24.41153 | 55.91197 | -0.0773 | 6.79729 |
October | 502.00000 | 24.20531 | 53.46678 | 0.61917 | 13.93911 |
November | 489.00000 | 23.60535 | 52.12537 | 0.41915 | 9.70405 |
December | 497.00000 | 22.65534 | 49.95086 | 0.12679 | 6.96310 |
Annual Sum or Average | 5943.00000 | 23.73981 | 51.61985 | 0.15168 | 8.07148 |
Minimum of Months | 454.00000 | 22.29692 | 46.31556 | -0.1180 | 6.28360 |
Maximum of Months | 514.00000 | 24.54988 | 55.91197 | 0.61917 | 13.93911 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.47760 | 45.84727 | 0.06262 | 6.83682 |
February | 454.00000 | 22.90692 | 48.54877 | 0.20666 | 7.86039 |
March | 514.00000 | 23.32841 | 46.58099 | 0.33082 | 9.13705 |
April | 485.00000 | 23.92596 | 49.03849 | 0.54094 | 12.67138 |
May | 508.00000 | 24.41261 | 50.84198 | -0.0487 | 7.17619 |
June | 496.00000 | 24.40831 | 54.75426 | 0.00085 | 6.79818 |
July | 497.00000 | 24.54626 | 54.75397 | 0.06536 | 7.28859 |
August | 514.00000 | 24.41095 | 55.64051 | 0.03375 | 6.67511 |
September | 485.00000 | 24.42963 | 55.67754 | -0.0123 | 7.20316 |
October | 502.00000 | 24.25627 | 53.13156 | 0.66851 | 15.56673 |
November | 489.00000 | 23.69950 | 51.79798 | 0.47037 | 10.86563 |
December | 497.00000 | 22.74889 | 49.66080 | 0.16963 | 7.33699 |
Annual Sum or Average | 5943.00000 | 23.80170 | 51.36578 | 0.20648 | 8.78032 |
Minimum of Months | 454.00000 | 22.47760 | 45.84727 | -0.0487 | 6.67511 |
Maximum of Months | 514.00000 | 24.54626 | 55.67754 | 0.66851 | 15.56673 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.00700 | 44.18960 | 0.19881 | 8.81218 |
February | 454.00000 | 23.18934 | 47.47319 | 0.28817 | 9.34437 |
March | 514.00000 | 23.42853 | 46.11344 | 0.35934 | 9.78899 |
April | 485.00000 | 23.83662 | 49.22966 | 0.50279 | 11.79590 |
May | 508.00000 | 24.29975 | 51.18930 | -0.1411 | 7.21500 |
June | 496.00000 | 24.33540 | 55.07352 | -0.0835 | 6.57724 |
July | 497.00000 | 24.47923 | 55.01196 | -0.0106 | 6.63699 |
August | 514.00000 | 24.38755 | 55.75133 | -0.0158 | 6.42945 |
September | 485.00000 | 24.42670 | 55.62386 | -0.0210 | 7.27237 |
October | 502.00000 | 24.34676 | 52.72769 | 0.70695 | 16.93602 |
November | 489.00000 | 23.95124 | 50.81955 | 0.55644 | 13.25786 |
December | 497.00000 | 23.26695 | 47.90676 | 0.30945 | 9.73150 |
Annual Sum or Average | 5943.00000 | 23.91744 | 50.94056 | 0.21930 | 9.47301 |
Minimum of Months | 454.00000 | 23.00700 | 44.18960 | -0.1411 | 6.42945 |
Maximum of Months | 514.00000 | 24.47923 | 55.75133 | 0.70695 | 16.93602 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.22841 | 46.35527 | 0.00901 | 7.07135 |
February | 454.00000 | 22.59834 | 49.18813 | 0.14575 | 7.65577 |
March | 514.00000 | 23.05756 | 47.12994 | 0.28021 | 8.84856 |
April | 485.00000 | 23.63396 | 49.75093 | 0.47662 | 11.64610 |
May | 508.00000 | 24.20906 | 51.37588 | -0.1191 | 7.98336 |
June | 496.00000 | 24.26674 | 55.15799 | -0.0454 | 7.25959 |
July | 497.00000 | 24.39420 | 55.18426 | 0.01387 | 7.31545 |
August | 514.00000 | 24.29008 | 56.02922 | -0.0089 | 6.89681 |
September | 485.00000 | 24.25490 | 56.17255 | -0.0677 | 7.70199 |
October | 502.00000 | 24.00209 | 53.84711 | 0.61438 | 14.40156 |
November | 489.00000 | 23.37811 | 52.58429 | 0.40672 | 10.14376 |
December | 497.00000 | 22.49300 | 50.20106 | 0.12017 | 7.37973 |
Annual Sum or Average | 5943.00000 | 23.57386 | 51.92280 | 0.15133 | 8.69126 |
Minimum of Months | 454.00000 | 22.22841 | 46.35527 | -0.1191 | 6.89681 |
Maximum of Months | 514.00000 | 24.39420 | 56.17255 | 0.61438 | 14.40156 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.13221 | 46.75337 | 0.21359 | 6.72215 |
February | 454.00000 | 23.37729 | 49.54170 | 0.30135 | 7.70034 |
March | 514.00000 | 23.63487 | 47.95153 | 0.37199 | 8.60096 |
April | 485.00000 | 24.04604 | 49.90751 | 0.51465 | 11.02568 |
May | 508.00000 | 24.42851 | 50.64933 | -0.1398 | 6.33045 |
June | 496.00000 | 24.43809 | 53.54119 | -0.0766 | 6.02163 |
July | 497.00000 | 24.57734 | 53.11238 | -0.0115 | 6.16989 |
August | 514.00000 | 24.46637 | 53.47014 | -0.0300 | 5.93859 |
September | 485.00000 | 24.48793 | 53.45492 | -0.0663 | 6.12493 |
October | 502.00000 | 24.43879 | 51.75263 | 0.67232 | 14.94940 |
November | 489.00000 | 24.18570 | 51.36735 | 0.56772 | 12.04248 |
December | 497.00000 | 23.56324 | 50.00353 | 0.35912 | 8.38231 |
Annual Sum or Average | 5943.00000 | 24.06875 | 50.96029 | 0.22145 | 8.32749 |
Minimum of Months | 454.00000 | 23.13221 | 46.75337 | -0.1398 | 5.93859 |
Maximum of Months | 514.00000 | 24.57734 | 53.54119 | 0.67232 | 14.94940 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.17624 | 46.46179 | 0.25359 | 7.33051 |
February | 454.00000 | 23.41455 | 49.28992 | 0.34024 | 8.45882 |
March | 514.00000 | 23.60843 | 47.86512 | 0.39953 | 9.33378 |
April | 485.00000 | 24.06985 | 49.64534 | 0.56242 | 12.45301 |
May | 508.00000 | 24.44399 | 50.45719 | -0.0703 | 6.44672 |
June | 496.00000 | 24.41967 | 53.45161 | -0.0280 | 6.18077 |
July | 497.00000 | 24.55747 | 53.06317 | 0.03725 | 6.52038 |
August | 514.00000 | 24.44336 | 53.41166 | 0.02607 | 6.13737 |
September | 485.00000 | 24.49171 | 53.25013 | -0.0019 | 6.39706 |
October | 502.00000 | 24.45938 | 51.49892 | 0.71833 | 16.51187 |
November | 489.00000 | 24.17803 | 51.27486 | 0.60242 | 13.09738 |
December | 497.00000 | 23.51136 | 50.00095 | 0.37636 | 8.83064 |
Annual Sum or Average | 5943.00000 | 24.06819 | 50.80851 | 0.26645 | 8.96488 |
Minimum of Months | 454.00000 | 23.17624 | 46.46179 | -0.0703 | 6.13737 |
Maximum of Months | 514.00000 | 24.55747 | 53.45161 | 0.71833 | 16.51187 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62911 | 45.29346 | 0.38552 | 9.66423 |
February | 454.00000 | 23.72624 | 48.85000 | 0.43807 | 10.37396 |
March | 514.00000 | 23.79613 | 47.61395 | 0.45148 | 10.37388 |
April | 485.00000 | 24.06701 | 50.54708 | 0.54659 | 12.01903 |
May | 508.00000 | 24.44796 | 52.25783 | -0.1235 | 6.29546 |
June | 496.00000 | 24.49244 | 56.68552 | -0.0546 | 5.89357 |
July | 497.00000 | 24.66603 | 57.30661 | 0.03683 | 6.13387 |
August | 514.00000 | 24.64069 | 58.16070 | 0.07151 | 6.30989 |
September | 485.00000 | 24.66732 | 56.82060 | 0.06923 | 6.58057 |
October | 502.00000 | 24.66768 | 53.64007 | 0.80449 | 19.41069 |
November | 489.00000 | 24.46244 | 52.38658 | 0.71633 | 16.56100 |
December | 497.00000 | 23.95553 | 49.37578 | 0.51570 | 11.91115 |
Annual Sum or Average | 5943.00000 | 24.27128 | 52.42894 | 0.31951 | 10.11100 |
Minimum of Months | 454.00000 | 23.62911 | 45.29346 | -0.1235 | 5.89357 |
Maximum of Months | 514.00000 | 24.66768 | 58.16070 | 0.80449 | 19.41069 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.91930 | 47.02413 | 0.19889 | 6.99766 |
February | 454.00000 | 23.17958 | 49.80768 | 0.29289 | 7.99457 |
March | 514.00000 | 23.47771 | 48.12878 | 0.37633 | 9.09311 |
April | 485.00000 | 23.91846 | 50.09270 | 0.52545 | 11.69928 |
May | 508.00000 | 24.34930 | 50.78896 | -0.1113 | 6.73994 |
June | 496.00000 | 24.36854 | 53.65443 | -0.0486 | 6.31152 |
July | 497.00000 | 24.49212 | 53.27864 | 0.00991 | 6.40495 |
August | 514.00000 | 24.40517 | 53.58996 | 0.00595 | 6.14398 |
September | 485.00000 | 24.43510 | 53.46772 | -0.0251 | 6.41510 |
October | 502.00000 | 24.37141 | 51.82718 | 0.69592 | 15.85663 |
November | 489.00000 | 24.06504 | 51.58319 | 0.57850 | 12.61668 |
December | 497.00000 | 23.32341 | 50.40327 | 0.34017 | 8.46753 |
Annual Sum or Average | 5943.00000 | 23.94668 | 51.13810 | 0.23517 | 8.72208 |
Minimum of Months | 454.00000 | 22.91930 | 47.02413 | -0.1113 | 6.14398 |
Maximum of Months | 514.00000 | 24.49212 | 53.65443 | 0.69592 | 15.85663 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.84628 | 46.24437 | 0.13231 | 6.46297 |
February | 454.00000 | 23.20380 | 49.05871 | 0.25391 | 7.45097 |
March | 514.00000 | 23.59247 | 47.13841 | 0.36121 | 8.63437 |
April | 485.00000 | 24.05139 | 49.84335 | 0.52316 | 11.36753 |
May | 508.00000 | 24.45494 | 51.61378 | -0.1202 | 6.44068 |
June | 496.00000 | 24.46200 | 54.90670 | -0.0654 | 6.20485 |
July | 497.00000 | 24.58461 | 54.59421 | -0.0140 | 6.37209 |
August | 514.00000 | 24.45589 | 55.46594 | -0.0475 | 6.08969 |
September | 485.00000 | 24.47844 | 55.70737 | -0.0840 | 6.41413 |
October | 502.00000 | 24.34986 | 53.61853 | 0.64176 | 14.23560 |
November | 489.00000 | 23.92742 | 52.37102 | 0.49221 | 10.58234 |
December | 497.00000 | 23.17998 | 50.08370 | 0.25321 | 7.40562 |
Annual Sum or Average | 5943.00000 | 23.97048 | 51.72849 | 0.19253 | 8.13351 |
Minimum of Months | 454.00000 | 22.84628 | 46.24437 | -0.1202 | 6.08969 |
Maximum of Months | 514.00000 | 24.58461 | 55.70737 | 0.64176 | 14.23560 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.72722 | 45.97804 | 0.12458 | 6.72397 |
February | 385.00000 | 23.09680 | 48.94333 | 0.24908 | 7.76743 |
March | 433.00000 | 23.45863 | 46.97168 | 0.35092 | 8.95039 |
April | 410.00000 | 24.03905 | 49.70927 | 0.54815 | 12.54439 |
May | 430.00000 | 24.51529 | 51.39917 | -0.0614 | 7.01138 |
June | 418.00000 | 24.49850 | 54.87470 | -0.0233 | 6.70915 |
July | 422.00000 | 24.64564 | 54.34058 | 0.03656 | 7.10719 |
August | 433.00000 | 24.49414 | 55.35357 | 0.00149 | 6.57347 |
September | 410.00000 | 24.53888 | 55.50910 | -0.0265 | 7.10806 |
October | 427.00000 | 24.38037 | 53.36396 | 0.67457 | 15.61200 |
November | 417.00000 | 23.86965 | 51.84935 | 0.49956 | 11.12682 |
December | 422.00000 | 23.00896 | 50.03082 | 0.23275 | 7.46208 |
Annual Sum or Average | 5034.00000 | 23.94389 | 51.53233 | 0.21641 | 8.72362 |
Minimum of Months | 385.00000 | 22.72722 | 45.97804 | -0.0614 | 6.57347 |
Maximum of Months | 433.00000 | 24.64564 | 55.50910 | 0.67457 | 15.61200 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.43493 | 44.25876 | 0.30913 | 9.03486 |
February | 454.00000 | 23.56508 | 47.64294 | 0.37982 | 9.75777 |
March | 514.00000 | 23.72568 | 46.46744 | 0.42677 | 10.11018 |
April | 485.00000 | 24.04182 | 49.68512 | 0.54098 | 12.03669 |
May | 508.00000 | 24.38115 | 51.76160 | -0.1404 | 6.61092 |
June | 496.00000 | 24.38669 | 55.11428 | -0.0990 | 6.22258 |
July | 497.00000 | 24.51577 | 54.75919 | -0.0380 | 6.25839 |
August | 514.00000 | 24.42871 | 55.43992 | -0.0388 | 6.15092 |
September | 485.00000 | 24.49879 | 55.36557 | -0.0259 | 6.75222 |
October | 502.00000 | 24.47934 | 52.86113 | 0.72772 | 17.18926 |
November | 489.00000 | 24.20637 | 51.18345 | 0.61769 | 14.13297 |
December | 497.00000 | 23.67598 | 48.22460 | 0.41462 | 10.44421 |
Annual Sum or Average | 5943.00000 | 24.11487 | 51.07812 | 0.25426 | 9.54439 |
Minimum of Months | 454.00000 | 23.43493 | 44.25876 | -0.1404 | 6.15092 |
Maximum of Months | 514.00000 | 24.51577 | 55.43992 | 0.72772 | 17.18926 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60846 | 46.54418 | 0.11038 | 6.86084 |
February | 454.00000 | 22.94968 | 49.44352 | 0.23283 | 7.74869 |
March | 514.00000 | 23.35563 | 47.48702 | 0.34793 | 9.04550 |
April | 485.00000 | 23.84360 | 50.19505 | 0.51613 | 11.83191 |
May | 508.00000 | 24.30764 | 51.90255 | -0.1124 | 7.17238 |
June | 496.00000 | 24.33608 | 55.13073 | -0.0545 | 6.70337 |
July | 497.00000 | 24.45008 | 54.85112 | -0.0068 | 6.75154 |
August | 514.00000 | 24.34682 | 55.66279 | -0.0263 | 6.45290 |
September | 485.00000 | 24.35101 | 55.85410 | -0.0656 | 6.99935 |
October | 502.00000 | 24.16879 | 53.92104 | 0.64148 | 14.66323 |
November | 489.00000 | 23.68727 | 52.83722 | 0.47770 | 10.84192 |
December | 497.00000 | 22.89080 | 50.55105 | 0.22292 | 7.59449 |
Annual Sum or Average | 5943.00000 | 23.78012 | 52.03893 | 0.18910 | 8.55165 |
Minimum of Months | 454.00000 | 22.60846 | 46.54418 | -0.1124 | 6.45290 |
Maximum of Months | 514.00000 | 24.45008 | 55.85410 | 0.64148 | 14.66323 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.533644E+11 | 0.127565E+11 | 403.53 | 0.471237E+11 | 0.624063E+10 | 0.00 | 1.00 | 02-JAN-06:12 | 0.00 | 01-JAN-00:10 | 74096.11 | 30-JAN-06:12 | 65143.68 | 30-JAN-06:12 | 15123.57 | 30-JAN-14:40 | 16536.34 | 30-JAN-06:12 | 0.00 |
February | 0.554491E+11 | 0.132906E+11 | 367.24 | 0.481108E+11 | 0.733833E+10 | 0.00 | 1.00 | 06-FEB-06:12 | 0.00 | 01-FEB-00:10 | 113206.90 | 09-FEB-06:12 | 75343.52 | 09-FEB-06:12 | 37863.38 | 09-FEB-06:12 | 25256.56 | 09-FEB-06:12 | 0.00 |
March | 0.728245E+11 | 0.179797E+11 | 435.24 | 0.653346E+11 | 0.748987E+10 | 0.00 | 1.00 | 01-MAR-05:02 | 0.00 | 01-MAR-00:10 | 108240.03 | 29-MAR-05:12 | 92809.21 | 02-MAR-05:02 | 34557.94 | 29-MAR-05:12 | 28674.11 | 27-MAR-11:00 | 0.00 |
April | 0.848145E+11 | 0.220081E+11 | 425.24 | 0.744151E+11 | 0.103993E+11 | 0.00 | 1.00 | 02-APR-10:02 | 0.00 | 01-APR-00:10 | 116305.91 | 12-APR-05:12 | 93757.01 | 28-APR-12:01 | 41181.47 | 12-APR-05:12 | 34368.13 | 28-APR-12:00 | 0.00 |
May | 0.124637E+12 | 0.351909E+11 | 497.22 | 0.106022E+12 | 0.186152E+11 | 0.00 | 1.00 | 01-MAY-01:21 | 0.00 | 01-MAY-00:03 | 177421.00 | 24-MAY-04:01 | 130843.40 | 11-MAY-04:01 | 77961.16 | 24-MAY-04:01 | 43262.56 | 31-MAY-12:02 | 0.00 |
June | 0.149739E+12 | 0.426136E+11 | 508.59 | 0.114119E+12 | 0.356199E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:12 | 177529.50 | 08-JUN-04:01 | 128755.17 | 01-JUN-04:01 | 76108.32 | 20-JUN-04:01 | 45981.35 | 12-JUN-11:09 | 0.00 |
July | 0.178093E+12 | 0.517526E+11 | 562.98 | 0.126530E+12 | 0.515631E+11 | 0.00 | 1.00 | 01-JUL-02:12 | 0.00 | 01-JUL-00:10 | 175478.95 | 06-JUL-04:01 | 132502.30 | 22-JUL-04:01 | 73857.60 | 20-JUL-12:02 | 52717.56 | 30-JUL-14:12 | 0.00 |
August | 0.196360E+12 | 0.573017E+11 | 588.44 | 0.137434E+12 | 0.589264E+11 | 0.00 | 1.00 | 01-AUG-00:32 | 0.00 | 01-AUG-00:02 | 173531.14 | 26-AUG-04:01 | 121241.20 | 15-AUG-04:01 | 77298.16 | 22-AUG-17:00 | 51677.48 | 13-AUG-14:51 | 0.00 |
September | 0.158378E+12 | 0.438486E+11 | 517.06 | 0.113671E+12 | 0.447071E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:02 | 176971.68 | 23-SEP-04:01 | 122102.86 | 26-SEP-04:01 | 72791.39 | 23-SEP-04:01 | 51917.69 | 04-SEP-13:41 | 0.00 |
October | 0.128883E+12 | 0.339878E+11 | 495.23 | 0.101365E+12 | 0.275180E+11 | 0.00 | 1.00 | 01-OCT-00:11 | 0.00 | 01-OCT-00:10 | 176560.56 | 07-OCT-04:01 | 125339.61 | 04-OCT-04:01 | 69781.39 | 07-OCT-04:01 | 40901.02 | 05-OCT-04:01 | 0.00 |
November | 0.936053E+11 | 0.232276E+11 | 430.22 | 0.781208E+11 | 0.154845E+11 | 0.00 | 1.00 | 01-NOV-04:32 | 0.00 | 01-NOV-00:10 | 155755.08 | 03-NOV-04:02 | 92468.55 | 03-NOV-04:02 | 63286.52 | 03-NOV-04:02 | 34683.59 | 03-NOV-04:02 | 0.00 |
December | 0.643566E+11 | 0.152634E+11 | 406.06 | 0.550056E+11 | 0.935099E+10 | 0.00 | 1.00 | 01-DEC-06:12 | 0.00 | 01-DEC-00:10 | 110344.44 | 11-DEC-06:12 | 76202.60 | 12-DEC-06:12 | 35084.18 | 11-DEC-06:12 | 24629.26 | 11-DEC-06:12 | 0.00 |
Annual Sum or Average | 0.136051E+13 | 0.369221E+12 | 5637.04 | 0.106725E+13 | 0.293253E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.533644E+11 | 0.127565E+11 | 367.24 | 0.471237E+11 | 0.624063E+10 | 0.00 | 1.00 | 0.00 | 74096.11 | 65143.68 | 15123.57 | 16536.34 | 0.00 | ||||||
Maximum of Months | 0.196360E+12 | 0.573017E+11 | 588.44 | 0.137434E+12 | 0.589264E+11 | 0.00 | 1.00 | 0.00 | 177529.50 | 132502.30 | 77961.16 | 52717.56 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.419616E+11 | 0.102714E+11 | 398.23 | 0.347089E+11 | 0.725269E+10 | 0.00 | 0.94 | 30-JAN-14:30 | 0.00 | 01-JAN-00:10 | 48882.89 | 30-JAN-14:30 | 44031.42 | 23-JAN-14:00 | 14229.69 | 30-JAN-15:10 | 11146.73 | 23-JAN-14:00 | 0.00 |
February | 0.455293E+11 | 0.111233E+11 | 366.26 | 0.374694E+11 | 0.805993E+10 | 0.00 | 1.00 | 06-FEB-11:40 | 0.00 | 01-FEB-00:10 | 73572.13 | 07-FEB-15:05 | 65404.27 | 06-FEB-15:05 | 17893.00 | 07-FEB-16:00 | 17992.92 | 06-FEB-15:05 | 0.00 |
March | 0.615126E+11 | 0.153882E+11 | 434.20 | 0.534373E+11 | 0.807527E+10 | 0.00 | 1.00 | 01-MAR-10:50 | 0.00 | 01-MAR-00:10 | 90487.36 | 02-MAR-06:02 | 90487.36 | 02-MAR-06:02 | 17188.99 | 31-MAR-18:00 | 26266.07 | 27-MAR-12:02 | 0.00 |
April | 0.739490E+11 | 0.192933E+11 | 425.77 | 0.635465E+11 | 0.104026E+11 | 0.00 | 1.00 | 02-APR-10:02 | 0.00 | 01-APR-00:10 | 103926.32 | 18-APR-04:01 | 87311.51 | 28-APR-12:01 | 29719.86 | 18-APR-04:01 | 31873.80 | 28-APR-12:01 | 0.00 |
May | 0.108944E+12 | 0.306754E+11 | 485.75 | 0.924900E+11 | 0.164545E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:03 | 168450.51 | 24-MAY-04:01 | 121259.17 | 11-MAY-04:01 | 79425.49 | 24-MAY-04:01 | 42739.36 | 29-MAY-12:52 | 0.00 |
June | 0.131814E+12 | 0.372544E+11 | 496.48 | 0.992599E+11 | 0.325543E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:12 | 169820.66 | 20-JUN-04:01 | 117599.31 | 01-JUN-04:01 | 82633.20 | 08-JUN-05:02 | 43693.19 | 12-JUN-12:01 | 0.00 |
July | 0.157573E+12 | 0.454488E+11 | 548.10 | 0.110613E+12 | 0.469596E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 167945.03 | 06-JUL-04:01 | 122783.55 | 03-JUL-04:01 | 79074.50 | 15-JUL-04:02 | 52515.86 | 30-JUL-13:32 | 0.00 |
August | 0.169285E+12 | 0.490447E+11 | 564.64 | 0.117490E+12 | 0.517956E+11 | 0.00 | 1.00 | 01-AUG-00:02 | 0.00 | 01-AUG-00:12 | 166357.06 | 09-AUG-04:01 | 111289.53 | 06-AUG-15:02 | 73614.30 | 23-AUG-04:02 | 51115.60 | 16-AUG-12:01 | 0.00 |
September | 0.132577E+12 | 0.365227E+11 | 481.79 | 0.941153E+11 | 0.384613E+11 | 0.00 | 1.00 | 01-SEP-00:02 | 0.00 | 01-SEP-00:23 | 167796.17 | 28-SEP-04:01 | 115808.07 | 04-SEP-15:12 | 82641.33 | 23-SEP-04:01 | 49469.51 | 04-SEP-14:32 | 0.00 |
October | 0.104338E+12 | 0.275229E+11 | 458.32 | 0.813984E+11 | 0.229392E+11 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 166984.99 | 02-OCT-04:01 | 113367.98 | 10-OCT-04:01 | 75300.67 | 07-OCT-04:01 | 38576.03 | 08-OCT-13:52 | 0.00 |
November | 0.746010E+11 | 0.186441E+11 | 412.71 | 0.605309E+11 | 0.140701E+11 | 0.00 | 1.00 | 01-NOV-04:42 | 0.00 | 01-NOV-00:10 | 122164.56 | 03-NOV-04:02 | 74074.64 | 06-NOV-13:03 | 53380.53 | 03-NOV-04:02 | 27171.77 | 03-NOV-04:02 | 0.00 |
December | 0.515061E+11 | 0.124653E+11 | 401.13 | 0.414276E+11 | 0.100786E+11 | 0.00 | 1.00 | 01-DEC-13:10 | 0.00 | 01-DEC-00:10 | 68391.45 | 05-DEC-15:10 | 53423.60 | 04-DEC-13:10 | 23940.94 | 25-DEC-11:00 | 15875.05 | 05-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.115359E+13 | 0.313655E+12 | 5473.37 | 0.886487E+12 | 0.267104E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.419616E+11 | 0.102714E+11 | 366.26 | 0.347089E+11 | 0.725269E+10 | 0.00 | 0.94 | 0.00 | 48882.89 | 44031.42 | 14229.69 | 11146.73 | 0.00 | ||||||
Maximum of Months | 0.169285E+12 | 0.490447E+11 | 564.64 | 0.117490E+12 | 0.517956E+11 | 0.00 | 1.00 | 0.00 | 169820.66 | 122783.55 | 82641.33 | 52515.86 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.456510E+11 | 0.113001E+11 | 395.79 | 0.371793E+11 | 0.847167E+10 | 0.00 | 0.88 | 24-JAN-14:30 | 0.00 | 01-JAN-00:10 | 53224.00 | 30-JAN-14:30 | 50483.76 | 23-JAN-14:00 | 15417.65 | 30-JAN-15:10 | 12897.01 | 23-JAN-14:00 | 0.00 |
February | 0.504073E+11 | 0.124446E+11 | 365.68 | 0.412928E+11 | 0.911453E+10 | 0.00 | 1.00 | 05-FEB-12:42 | 0.00 | 01-FEB-00:10 | 82045.53 | 07-FEB-15:20 | 78532.34 | 05-FEB-15:22 | 19609.18 | 06-FEB-06:02 | 21346.59 | 05-FEB-15:22 | 0.00 |
March | 0.688646E+11 | 0.173943E+11 | 433.13 | 0.597096E+11 | 0.915503E+10 | 0.00 | 1.00 | 01-MAR-11:20 | 0.00 | 01-MAR-00:10 | 92771.13 | 27-MAR-13:40 | 92771.13 | 27-MAR-13:40 | 18501.83 | 31-MAR-17:50 | 29223.57 | 27-MAR-12:02 | 0.00 |
April | 0.837846E+11 | 0.220668E+11 | 423.91 | 0.724640E+11 | 0.113207E+11 | 0.00 | 1.00 | 03-APR-05:02 | 0.00 | 01-APR-00:10 | 113901.55 | 17-APR-05:01 | 102989.56 | 28-APR-12:01 | 28086.06 | 30-APR-08:05 | 37600.28 | 28-APR-12:01 | 0.00 |
May | 0.124198E+12 | 0.352130E+11 | 486.73 | 0.106928E+12 | 0.172701E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:03 | 197873.74 | 29-MAY-12:52 | 139272.39 | 23-MAY-04:01 | 96446.99 | 24-MAY-04:01 | 51199.89 | 29-MAY-12:52 | 0.00 |
June | 0.148011E+12 | 0.420837E+11 | 496.13 | 0.115053E+12 | 0.329578E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:02 | 203592.10 | 20-JUN-04:01 | 132542.87 | 26-JUN-04:01 | 103017.13 | 08-JUN-04:01 | 53726.95 | 11-JUN-15:22 | 0.00 |
July | 0.176462E+12 | 0.511162E+11 | 552.13 | 0.129151E+12 | 0.473108E+11 | 0.00 | 1.00 | 01-JUL-02:47 | 0.00 | 01-JUL-00:10 | 200296.14 | 06-JUL-04:01 | 160148.37 | 30-JUL-13:32 | 84787.84 | 06-JUL-04:01 | 64011.46 | 30-JUL-13:32 | 0.00 |
August | 0.187965E+12 | 0.546870E+11 | 567.68 | 0.135949E+12 | 0.520157E+11 | 0.00 | 1.00 | 01-AUG-00:40 | 0.00 | 01-AUG-00:02 | 197109.06 | 26-AUG-04:01 | 146972.43 | 06-AUG-14:42 | 77499.73 | 26-AUG-04:01 | 59078.88 | 06-AUG-14:42 | 0.00 |
September | 0.145484E+12 | 0.403029E+11 | 480.40 | 0.106835E+12 | 0.386485E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:23 | 201065.68 | 28-SEP-04:01 | 150376.23 | 04-SEP-12:11 | 92449.11 | 28-SEP-05:02 | 59273.34 | 04-SEP-14:11 | 0.00 |
October | 0.113404E+12 | 0.301936E+11 | 453.60 | 0.897998E+11 | 0.236041E+11 | 0.00 | 1.00 | 01-OCT-07:05 | 0.00 | 01-OCT-00:10 | 198203.74 | 02-OCT-04:01 | 126076.21 | 08-OCT-13:52 | 86244.89 | 02-OCT-04:01 | 49223.82 | 08-OCT-13:52 | 0.00 |
November | 0.799153E+11 | 0.202061E+11 | 408.98 | 0.648288E+11 | 0.150865E+11 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 138831.66 | 03-NOV-05:02 | 84872.61 | 20-NOV-06:02 | 62529.76 | 03-NOV-05:02 | 30862.06 | 03-NOV-05:02 | 0.00 |
December | 0.553012E+11 | 0.135787E+11 | 398.68 | 0.439197E+11 | 0.113814E+11 | 0.00 | 1.00 | 03-DEC-12:22 | 0.00 | 01-DEC-00:10 | 74769.10 | 05-DEC-15:00 | 66813.93 | 03-DEC-12:22 | 21493.76 | 05-DEC-17:20 | 17287.32 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.127945E+13 | 0.350587E+12 | 5462.82 | 0.100311E+13 | 0.276337E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.456510E+11 | 0.113001E+11 | 365.68 | 0.371793E+11 | 0.847167E+10 | 0.00 | 0.88 | 0.00 | 53224.00 | 50483.76 | 15417.65 | 12897.01 | 0.00 | ||||||
Maximum of Months | 0.187965E+12 | 0.546870E+11 | 567.68 | 0.135949E+12 | 0.520157E+11 | 0.00 | 1.00 | 0.00 | 203592.10 | 160148.37 | 103017.13 | 64011.46 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 265.64 | 0.00 | 265.64 | 453.28 | 952.33 | 0.00 | 0.00 | 0.00 |
February | 304.50 | 0.00 | 304.50 | 636.94 | 800.52 | 0.00 | 0.00 | 0.00 |
March | 349.76 | 0.00 | 349.76 | 949.47 | 608.18 | 0.00 | 0.00 | 0.00 |
April | 394.63 | 1.38 | 393.25 | 1470.45 | 388.70 | 0.00 | 0.00 | 0.00 |
May | 448.80 | 18.26 | 430.54 | 2373.76 | 101.00 | 0.00 | 0.00 | 0.00 |
June | 484.31 | 35.77 | 448.54 | 2785.86 | 22.93 | 0.00 | 0.00 | 0.00 |
July | 441.15 | 17.93 | 423.22 | 3230.61 | 0.25 | 0.00 | 0.00 | 0.00 |
August | 407.48 | 5.17 | 402.31 | 3204.64 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 369.57 | 0.08 | 369.48 | 2336.88 | 34.40 | 0.00 | 0.00 | 0.00 |
October | 327.58 | 0.00 | 327.58 | 1620.41 | 156.72 | 0.00 | 0.00 | 0.00 |
November | 281.22 | 0.00 | 281.22 | 982.69 | 424.49 | 0.00 | 0.00 | 0.00 |
December | 247.94 | 0.00 | 247.94 | 539.51 | 757.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 360.43 | 6.57 | 353.85 | 1722.28 | 351.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.94 | 0.00 | 247.94 | 453.28 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 484.31 | 35.77 | 448.54 | 3230.61 | 952.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 320.87 | 97.44 | 223.43 | 650.22 | 592.14 | 0.00 | 0.00 | 0.00 |
February | 349.58 | 95.08 | 254.50 | 797.84 | 503.24 | 0.00 | 0.00 | 0.00 |
March | 385.70 | 95.11 | 290.59 | 1057.68 | 385.09 | 0.00 | 0.00 | 0.00 |
April | 469.46 | 136.74 | 332.72 | 1580.42 | 249.82 | 0.00 | 0.00 | 0.00 |
May | 523.85 | 166.32 | 357.53 | 2251.01 | 63.35 | 0.00 | 0.00 | 0.00 |
June | 514.12 | 157.41 | 356.72 | 2426.64 | 12.97 | 0.00 | 0.00 | 0.00 |
July | 480.66 | 139.32 | 341.34 | 2720.88 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 491.27 | 150.89 | 340.38 | 2810.82 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 461.33 | 142.33 | 319.00 | 2196.76 | 19.89 | 0.00 | 0.00 | 0.00 |
October | 418.77 | 136.69 | 282.08 | 1657.28 | 94.77 | 0.00 | 0.00 | 0.00 |
November | 351.77 | 111.89 | 239.88 | 1101.79 | 268.50 | 0.00 | 0.00 | 0.00 |
December | 285.04 | 78.84 | 206.20 | 663.78 | 478.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.31 | 125.80 | 295.52 | 1664.85 | 220.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.04 | 78.84 | 206.20 | 650.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 523.85 | 166.32 | 357.53 | 2810.82 | 592.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 851.63 | 396.75 | 454.88 | 1965.76 | 940.46 | 0.00 | 0.00 | 0.00 |
February | 810.48 | 334.07 | 476.41 | 2017.25 | 808.72 | 0.00 | 0.00 | 0.00 |
March | 683.82 | 200.45 | 483.37 | 1959.30 | 626.60 | 0.00 | 0.00 | 0.00 |
April | 541.18 | 74.91 | 466.27 | 1952.78 | 397.50 | 0.00 | 0.00 | 0.00 |
May | 447.06 | 12.01 | 435.05 | 2378.15 | 99.73 | 0.00 | 0.00 | 0.00 |
June | 416.67 | 1.09 | 415.58 | 2584.09 | 17.63 | 0.00 | 0.00 | 0.00 |
July | 418.78 | 6.24 | 412.54 | 3152.74 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 497.39 | 48.96 | 448.42 | 3512.27 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 663.26 | 172.75 | 490.50 | 3281.55 | 33.76 | 0.00 | 0.00 | 0.00 |
October | 848.44 | 346.55 | 501.89 | 3196.60 | 157.98 | 0.00 | 0.00 | 0.00 |
November | 915.68 | 439.68 | 476.01 | 2792.50 | 437.86 | 0.00 | 0.00 | 0.00 |
December | 843.08 | 411.35 | 431.73 | 2153.83 | 768.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 660.53 | 203.01 | 457.52 | 2582.71 | 355.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 416.67 | 1.09 | 412.54 | 1952.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 915.68 | 439.68 | 501.89 | 3512.27 | 940.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 314.90 | 90.97 | 223.93 | 665.19 | 633.75 | 0.00 | 0.00 | 0.00 |
February | 359.52 | 103.08 | 256.44 | 852.90 | 528.58 | 0.00 | 0.00 | 0.00 |
March | 424.62 | 125.49 | 299.14 | 1171.68 | 407.70 | 0.00 | 0.00 | 0.00 |
April | 463.47 | 129.55 | 333.92 | 1557.28 | 266.56 | 0.00 | 0.00 | 0.00 |
May | 505.43 | 151.26 | 354.17 | 2196.37 | 71.60 | 0.00 | 0.00 | 0.00 |
June | 522.41 | 164.70 | 357.71 | 2454.70 | 14.26 | 0.00 | 0.00 | 0.00 |
July | 480.15 | 138.02 | 342.13 | 2718.15 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 491.04 | 148.88 | 342.15 | 2793.04 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 467.19 | 146.45 | 320.74 | 2213.43 | 23.64 | 0.00 | 0.00 | 0.00 |
October | 415.63 | 134.26 | 281.36 | 1665.57 | 107.20 | 0.00 | 0.00 | 0.00 |
November | 357.68 | 117.32 | 240.37 | 1156.76 | 284.91 | 0.00 | 0.00 | 0.00 |
December | 300.09 | 91.47 | 208.62 | 740.95 | 502.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.42 | 128.54 | 296.88 | 1687.19 | 235.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 300.09 | 90.97 | 208.62 | 665.19 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 522.41 | 164.70 | 357.71 | 2793.04 | 633.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.54 | 0.00 | 88.54 | 140.26 | 380.69 | 0.00 | 0.00 | 0.00 |
February | 101.50 | 0.00 | 101.50 | 207.97 | 311.46 | 0.00 | 0.00 | 0.00 |
March | 116.58 | 0.00 | 116.58 | 320.12 | 227.02 | 0.00 | 0.00 | 0.00 |
April | 131.54 | 0.46 | 131.08 | 497.08 | 138.92 | 0.00 | 0.00 | 0.00 |
May | 149.60 | 6.09 | 143.51 | 794.87 | 33.71 | 0.00 | 0.00 | 0.00 |
June | 161.43 | 11.92 | 149.51 | 927.00 | 7.94 | 0.00 | 0.00 | 0.00 |
July | 147.04 | 5.98 | 141.07 | 1065.83 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 135.82 | 1.72 | 134.10 | 1048.70 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 123.18 | 0.03 | 123.16 | 764.46 | 14.71 | 0.00 | 0.00 | 0.00 |
October | 109.19 | 0.00 | 109.19 | 525.40 | 66.07 | 0.00 | 0.00 | 0.00 |
November | 93.74 | 0.00 | 93.74 | 310.83 | 182.73 | 0.00 | 0.00 | 0.00 |
December | 82.64 | 0.00 | 82.64 | 164.08 | 318.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.14 | 2.19 | 117.95 | 566.14 | 139.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.64 | 0.00 | 82.64 | 140.26 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.43 | 11.92 | 149.51 | 1065.83 | 380.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.55 | 0.00 | 88.55 | 140.27 | 380.71 | 0.00 | 0.00 | 0.00 |
February | 101.50 | 0.00 | 101.50 | 207.98 | 311.47 | 0.00 | 0.00 | 0.00 |
March | 116.59 | 0.00 | 116.59 | 320.14 | 227.03 | 0.00 | 0.00 | 0.00 |
April | 131.54 | 0.46 | 131.08 | 497.11 | 138.93 | 0.00 | 0.00 | 0.00 |
May | 149.60 | 6.09 | 143.52 | 794.92 | 33.71 | 0.00 | 0.00 | 0.00 |
June | 161.44 | 11.92 | 149.51 | 927.05 | 7.94 | 0.00 | 0.00 | 0.00 |
July | 147.05 | 5.98 | 141.07 | 1065.89 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 135.83 | 1.72 | 134.10 | 1048.77 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 123.19 | 0.03 | 123.16 | 764.51 | 14.71 | 0.00 | 0.00 | 0.00 |
October | 109.19 | 0.00 | 109.19 | 525.43 | 66.07 | 0.00 | 0.00 | 0.00 |
November | 93.74 | 0.00 | 93.74 | 310.85 | 182.74 | 0.00 | 0.00 | 0.00 |
December | 82.65 | 0.00 | 82.65 | 164.08 | 318.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.14 | 2.19 | 117.95 | 566.17 | 139.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.65 | 0.00 | 82.65 | 140.27 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.44 | 11.92 | 149.51 | 1065.89 | 380.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.55 | 0.00 | 88.55 | 140.27 | 380.71 | 0.00 | 0.00 | 0.00 |
February | 101.50 | 0.00 | 101.50 | 207.98 | 311.47 | 0.00 | 0.00 | 0.00 |
March | 116.59 | 0.00 | 116.59 | 320.14 | 227.03 | 0.00 | 0.00 | 0.00 |
April | 131.54 | 0.46 | 131.08 | 497.11 | 138.93 | 0.00 | 0.00 | 0.00 |
May | 149.60 | 6.09 | 143.52 | 794.92 | 33.71 | 0.00 | 0.00 | 0.00 |
June | 161.44 | 11.92 | 149.51 | 927.05 | 7.94 | 0.00 | 0.00 | 0.00 |
July | 147.05 | 5.98 | 141.07 | 1065.89 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 135.83 | 1.72 | 134.10 | 1048.77 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 123.19 | 0.03 | 123.16 | 764.51 | 14.71 | 0.00 | 0.00 | 0.00 |
October | 109.19 | 0.00 | 109.19 | 525.43 | 66.07 | 0.00 | 0.00 | 0.00 |
November | 93.74 | 0.00 | 93.74 | 310.85 | 182.74 | 0.00 | 0.00 | 0.00 |
December | 82.65 | 0.00 | 82.65 | 164.08 | 318.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 120.14 | 2.19 | 117.95 | 566.17 | 139.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.65 | 0.00 | 82.65 | 140.27 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.44 | 11.92 | 149.51 | 1065.89 | 380.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 308.68 | 93.74 | 214.94 | 599.51 | 679.12 | 0.00 | 0.00 | 0.00 |
February | 336.30 | 91.47 | 244.83 | 761.33 | 564.55 | 0.00 | 0.00 | 0.00 |
March | 371.04 | 91.50 | 279.54 | 1029.16 | 414.97 | 0.00 | 0.00 | 0.00 |
April | 451.62 | 131.55 | 320.07 | 1542.13 | 261.34 | 0.00 | 0.00 | 0.00 |
May | 503.94 | 160.00 | 343.94 | 2181.72 | 63.67 | 0.00 | 0.00 | 0.00 |
June | 494.59 | 151.42 | 343.16 | 2341.10 | 13.73 | 0.00 | 0.00 | 0.00 |
July | 462.40 | 134.03 | 328.37 | 2609.01 | 0.13 | 0.00 | 0.00 | 0.00 |
August | 472.60 | 145.15 | 327.45 | 2680.16 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 443.80 | 136.92 | 306.87 | 2098.29 | 25.87 | 0.00 | 0.00 | 0.00 |
October | 402.85 | 131.50 | 271.36 | 1576.26 | 119.25 | 0.00 | 0.00 | 0.00 |
November | 338.40 | 107.64 | 230.76 | 1033.13 | 333.53 | 0.00 | 0.00 | 0.00 |
December | 274.21 | 75.84 | 198.37 | 605.12 | 573.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 405.30 | 121.02 | 284.28 | 1593.06 | 252.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 274.21 | 75.84 | 198.37 | 599.51 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 503.94 | 160.00 | 343.94 | 2680.16 | 679.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.20 | 3.71 | 8.50 | 23.70 | 26.85 | 0.00 | 0.00 | 0.00 |
February | 13.30 | 3.62 | 9.68 | 30.10 | 22.32 | 0.00 | 0.00 | 0.00 |
March | 14.67 | 3.62 | 11.05 | 40.69 | 16.41 | 0.00 | 0.00 | 0.00 |
April | 17.86 | 5.20 | 12.66 | 60.97 | 10.33 | 0.00 | 0.00 | 0.00 |
May | 19.93 | 6.33 | 13.60 | 86.26 | 2.52 | 0.00 | 0.00 | 0.00 |
June | 19.56 | 5.99 | 13.57 | 92.57 | 0.54 | 0.00 | 0.00 | 0.00 |
July | 18.28 | 5.30 | 12.98 | 103.16 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 18.69 | 5.74 | 12.95 | 105.97 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17.55 | 5.41 | 12.13 | 82.96 | 1.02 | 0.00 | 0.00 | 0.00 |
October | 15.93 | 5.20 | 10.73 | 62.32 | 4.71 | 0.00 | 0.00 | 0.00 |
November | 13.38 | 4.26 | 9.12 | 40.85 | 13.19 | 0.00 | 0.00 | 0.00 |
December | 10.84 | 3.00 | 7.84 | 23.93 | 22.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.03 | 4.78 | 11.24 | 62.99 | 9.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.84 | 3.00 | 7.84 | 23.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.93 | 6.33 | 13.60 | 105.97 | 26.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.88 | 132.25 | 151.63 | 654.43 | 381.28 | 0.00 | 0.00 | 0.00 |
February | 270.17 | 111.36 | 158.81 | 678.11 | 321.23 | 0.00 | 0.00 | 0.00 |
March | 227.95 | 66.82 | 161.13 | 661.98 | 238.62 | 0.00 | 0.00 | 0.00 |
April | 180.40 | 24.97 | 155.43 | 659.99 | 144.56 | 0.00 | 0.00 | 0.00 |
May | 149.02 | 4.00 | 145.02 | 792.29 | 34.21 | 0.00 | 0.00 | 0.00 |
June | 138.89 | 0.36 | 138.53 | 851.56 | 6.44 | 0.00 | 0.00 | 0.00 |
July | 139.60 | 2.08 | 137.52 | 1032.89 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 165.80 | 16.32 | 149.48 | 1141.70 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 221.09 | 57.59 | 163.50 | 1076.81 | 16.11 | 0.00 | 0.00 | 0.00 |
October | 282.82 | 115.52 | 167.30 | 1055.77 | 72.55 | 0.00 | 0.00 | 0.00 |
November | 305.24 | 146.56 | 158.67 | 925.46 | 194.64 | 0.00 | 0.00 | 0.00 |
December | 281.03 | 137.12 | 143.91 | 712.35 | 325.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.18 | 67.67 | 152.51 | 854.78 | 143.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.89 | 0.36 | 137.52 | 654.43 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 305.24 | 146.56 | 167.30 | 1141.70 | 381.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.88 | 132.25 | 151.63 | 654.43 | 381.28 | 0.00 | 0.00 | 0.00 |
February | 270.17 | 111.36 | 158.81 | 678.11 | 321.23 | 0.00 | 0.00 | 0.00 |
March | 227.95 | 66.82 | 161.13 | 661.98 | 238.62 | 0.00 | 0.00 | 0.00 |
April | 180.40 | 24.97 | 155.43 | 659.99 | 144.56 | 0.00 | 0.00 | 0.00 |
May | 149.02 | 4.00 | 145.02 | 792.29 | 34.21 | 0.00 | 0.00 | 0.00 |
June | 138.89 | 0.36 | 138.53 | 851.56 | 6.44 | 0.00 | 0.00 | 0.00 |
July | 139.60 | 2.08 | 137.52 | 1032.89 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 165.80 | 16.32 | 149.48 | 1141.70 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 221.09 | 57.59 | 163.50 | 1076.81 | 16.11 | 0.00 | 0.00 | 0.00 |
October | 282.82 | 115.52 | 167.30 | 1055.77 | 72.55 | 0.00 | 0.00 | 0.00 |
November | 305.24 | 146.56 | 158.67 | 925.46 | 194.64 | 0.00 | 0.00 | 0.00 |
December | 281.03 | 137.12 | 143.91 | 712.35 | 325.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.18 | 67.67 | 152.51 | 854.78 | 143.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.89 | 0.36 | 137.52 | 654.43 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 305.24 | 146.56 | 167.30 | 1141.70 | 381.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.87 | 132.25 | 151.62 | 654.39 | 381.26 | 0.00 | 0.00 | 0.00 |
February | 270.15 | 111.35 | 158.80 | 678.06 | 321.21 | 0.00 | 0.00 | 0.00 |
March | 227.93 | 66.81 | 161.12 | 661.94 | 238.61 | 0.00 | 0.00 | 0.00 |
April | 180.39 | 24.97 | 155.42 | 659.95 | 144.55 | 0.00 | 0.00 | 0.00 |
May | 149.02 | 4.00 | 145.01 | 792.24 | 34.20 | 0.00 | 0.00 | 0.00 |
June | 138.88 | 0.36 | 138.52 | 851.50 | 6.44 | 0.00 | 0.00 | 0.00 |
July | 139.59 | 2.08 | 137.51 | 1032.83 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 165.79 | 16.32 | 149.47 | 1141.63 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 221.08 | 57.58 | 163.49 | 1076.74 | 16.10 | 0.00 | 0.00 | 0.00 |
October | 282.80 | 115.51 | 167.29 | 1055.70 | 72.55 | 0.00 | 0.00 | 0.00 |
November | 305.22 | 146.55 | 158.66 | 925.40 | 194.63 | 0.00 | 0.00 | 0.00 |
December | 281.02 | 137.11 | 143.90 | 712.31 | 325.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.17 | 67.67 | 152.50 | 854.73 | 143.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.88 | 0.36 | 137.51 | 654.39 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 305.22 | 146.55 | 167.29 | 1141.63 | 381.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 302.93 | 87.51 | 215.42 | 633.35 | 726.99 | 0.00 | 0.00 | 0.00 |
February | 345.86 | 99.16 | 246.70 | 826.26 | 596.66 | 0.00 | 0.00 | 0.00 |
March | 408.48 | 120.72 | 287.77 | 1148.35 | 445.76 | 0.00 | 0.00 | 0.00 |
April | 445.85 | 124.62 | 321.23 | 1525.21 | 281.97 | 0.00 | 0.00 | 0.00 |
May | 486.22 | 145.51 | 340.71 | 2127.56 | 73.22 | 0.00 | 0.00 | 0.00 |
June | 502.55 | 158.44 | 344.11 | 2362.06 | 15.91 | 0.00 | 0.00 | 0.00 |
July | 461.90 | 132.78 | 329.12 | 2598.12 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 472.37 | 143.22 | 329.15 | 2657.97 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 449.43 | 140.88 | 308.55 | 2110.13 | 30.73 | 0.00 | 0.00 | 0.00 |
October | 399.83 | 129.16 | 270.67 | 1580.91 | 133.88 | 0.00 | 0.00 | 0.00 |
November | 344.09 | 112.86 | 231.23 | 1086.59 | 359.28 | 0.00 | 0.00 | 0.00 |
December | 288.69 | 87.99 | 200.70 | 693.46 | 607.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 409.25 | 123.66 | 285.59 | 1617.22 | 271.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 288.69 | 87.51 | 200.70 | 633.35 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 502.55 | 158.44 | 344.11 | 2657.97 | 726.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.98 | 3.46 | 8.52 | 25.04 | 28.74 | 0.00 | 0.00 | 0.00 |
February | 13.68 | 3.92 | 9.75 | 32.67 | 23.59 | 0.00 | 0.00 | 0.00 |
March | 16.15 | 4.77 | 11.38 | 45.40 | 17.62 | 0.00 | 0.00 | 0.00 |
April | 17.63 | 4.93 | 12.70 | 60.31 | 11.15 | 0.00 | 0.00 | 0.00 |
May | 19.22 | 5.75 | 13.47 | 84.12 | 2.90 | 0.00 | 0.00 | 0.00 |
June | 19.87 | 6.26 | 13.61 | 93.39 | 0.63 | 0.00 | 0.00 | 0.00 |
July | 18.26 | 5.25 | 13.01 | 102.73 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18.68 | 5.66 | 13.01 | 105.09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17.77 | 5.57 | 12.20 | 83.43 | 1.22 | 0.00 | 0.00 | 0.00 |
October | 15.81 | 5.11 | 10.70 | 62.51 | 5.29 | 0.00 | 0.00 | 0.00 |
November | 13.61 | 4.46 | 9.14 | 42.96 | 14.21 | 0.00 | 0.00 | 0.00 |
December | 11.41 | 3.48 | 7.94 | 27.42 | 24.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.18 | 4.89 | 11.29 | 63.94 | 10.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.41 | 3.46 | 7.94 | 25.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.87 | 6.26 | 13.61 | 105.09 | 28.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 265.64 | 0.00 | 265.64 | 426.62 | 1072.86 | 0.00 | 0.00 | 0.00 |
February | 304.50 | 0.00 | 304.50 | 619.13 | 895.54 | 0.00 | 0.00 | 0.00 |
March | 349.76 | 0.00 | 349.76 | 942.43 | 674.98 | 0.00 | 0.00 | 0.00 |
April | 394.63 | 1.38 | 393.25 | 1475.88 | 422.71 | 0.00 | 0.00 | 0.00 |
May | 448.80 | 18.26 | 430.54 | 2387.06 | 107.86 | 0.00 | 0.00 | 0.00 |
June | 484.31 | 35.77 | 448.54 | 2800.62 | 24.63 | 0.00 | 0.00 | 0.00 |
July | 441.15 | 17.93 | 423.22 | 3243.27 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 407.48 | 5.17 | 402.31 | 3213.27 | 0.12 | 0.00 | 0.00 | 0.00 |
September | 369.57 | 0.08 | 369.48 | 2342.56 | 38.26 | 0.00 | 0.00 | 0.00 |
October | 327.58 | 0.00 | 327.58 | 1618.40 | 175.66 | 0.00 | 0.00 | 0.00 |
November | 281.22 | 0.00 | 281.22 | 966.10 | 484.58 | 0.00 | 0.00 | 0.00 |
December | 247.94 | 0.00 | 247.94 | 512.51 | 864.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 360.43 | 6.57 | 353.85 | 1719.29 | 394.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.94 | 0.00 | 247.94 | 426.62 | 0.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 484.31 | 35.77 | 448.54 | 3243.27 | 1072.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 320.87 | 97.44 | 223.43 | 631.63 | 652.29 | 0.00 | 0.00 | 0.00 |
February | 349.58 | 95.08 | 254.50 | 786.86 | 552.47 | 0.00 | 0.00 | 0.00 |
March | 385.70 | 95.11 | 290.59 | 1052.25 | 419.88 | 0.00 | 0.00 | 0.00 |
April | 469.46 | 136.74 | 332.72 | 1582.18 | 267.53 | 0.00 | 0.00 | 0.00 |
May | 523.85 | 166.32 | 357.53 | 2259.12 | 67.31 | 0.00 | 0.00 | 0.00 |
June | 514.12 | 157.41 | 356.72 | 2435.63 | 13.87 | 0.00 | 0.00 | 0.00 |
July | 480.66 | 139.32 | 341.34 | 2731.64 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 491.27 | 150.89 | 340.38 | 2818.10 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 461.33 | 142.33 | 319.00 | 2201.40 | 21.82 | 0.00 | 0.00 | 0.00 |
October | 418.77 | 136.69 | 282.08 | 1656.31 | 104.80 | 0.00 | 0.00 | 0.00 |
November | 351.77 | 111.89 | 239.88 | 1090.07 | 300.56 | 0.00 | 0.00 | 0.00 |
December | 285.04 | 78.84 | 206.20 | 646.03 | 533.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.31 | 125.80 | 295.52 | 1662.90 | 242.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.04 | 78.84 | 206.20 | 631.63 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 523.85 | 166.32 | 357.53 | 2818.10 | 652.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 851.63 | 396.75 | 454.88 | 1946.95 | 1046.68 | 0.00 | 0.00 | 0.00 |
February | 810.48 | 334.07 | 476.41 | 2009.21 | 896.00 | 0.00 | 0.00 | 0.00 |
March | 683.82 | 200.45 | 483.37 | 1960.13 | 690.93 | 0.00 | 0.00 | 0.00 |
April | 541.18 | 74.91 | 466.27 | 1961.62 | 432.10 | 0.00 | 0.00 | 0.00 |
May | 447.06 | 12.01 | 435.05 | 2391.04 | 108.03 | 0.00 | 0.00 | 0.00 |
June | 416.67 | 1.09 | 415.58 | 2595.94 | 19.53 | 0.00 | 0.00 | 0.00 |
July | 418.78 | 6.24 | 412.54 | 3165.56 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 497.39 | 48.96 | 448.42 | 3521.71 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 663.26 | 172.75 | 490.50 | 3294.05 | 37.58 | 0.00 | 0.00 | 0.00 |
October | 848.44 | 346.55 | 501.89 | 3205.26 | 175.93 | 0.00 | 0.00 | 0.00 |
November | 915.68 | 439.68 | 476.01 | 2788.71 | 492.65 | 0.00 | 0.00 | 0.00 |
December | 843.08 | 411.35 | 431.73 | 2135.21 | 862.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 660.53 | 203.01 | 457.52 | 2585.12 | 394.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 416.67 | 1.09 | 412.54 | 1946.95 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 915.68 | 439.68 | 501.89 | 3521.71 | 1046.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 314.90 | 90.97 | 223.93 | 655.20 | 703.84 | 0.00 | 0.00 | 0.00 |
February | 359.52 | 103.08 | 256.44 | 848.01 | 586.25 | 0.00 | 0.00 | 0.00 |
March | 424.62 | 125.49 | 299.14 | 1172.74 | 449.58 | 0.00 | 0.00 | 0.00 |
April | 463.47 | 129.55 | 333.92 | 1565.72 | 288.63 | 0.00 | 0.00 | 0.00 |
May | 505.43 | 151.26 | 354.17 | 2208.53 | 77.06 | 0.00 | 0.00 | 0.00 |
June | 522.41 | 164.70 | 357.71 | 2466.63 | 15.49 | 0.00 | 0.00 | 0.00 |
July | 480.15 | 138.02 | 342.13 | 2729.10 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 491.04 | 148.88 | 342.15 | 2802.60 | 0.12 | 0.00 | 0.00 | 0.00 |
September | 467.19 | 146.45 | 320.74 | 2220.61 | 26.06 | 0.00 | 0.00 | 0.00 |
October | 415.63 | 134.26 | 281.36 | 1667.18 | 119.07 | 0.00 | 0.00 | 0.00 |
November | 357.68 | 117.32 | 240.37 | 1149.32 | 322.89 | 0.00 | 0.00 | 0.00 |
December | 300.09 | 91.47 | 208.62 | 729.74 | 565.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.42 | 128.54 | 296.88 | 1689.67 | 261.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 300.09 | 90.97 | 208.62 | 655.20 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 522.41 | 164.70 | 357.71 | 2802.60 | 703.84 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.711484E+09 | 0.00 | 0.711484E+09 | 0.121406E+10 | 0.255073E+10 |
February | 0.736639E+09 | 0.00 | 0.736639E+09 | 0.154089E+10 | 0.193661E+10 |
March | 0.936786E+09 | 0.00 | 0.936786E+09 | 0.254307E+10 | 0.162894E+10 |
April | 0.102288E+10 | 3580422.73 | 0.101930E+10 | 0.381141E+10 | 0.100752E+10 |
May | 0.120208E+10 | 48913757.96 | 0.115316E+10 | 0.635787E+10 | 0.270522E+09 |
June | 0.125534E+10 | 92722543.66 | 0.116261E+10 | 0.722096E+10 | 59445636.54 |
July | 0.118158E+10 | 48035592.07 | 0.113354E+10 | 0.865286E+10 | 676121.65 |
August | 0.109139E+10 | 13836094.29 | 0.107755E+10 | 0.858330E+10 | 152449.75 |
September | 0.957916E+09 | 218304.56 | 0.957698E+09 | 0.605720E+10 | 89160241.43 |
October | 0.877378E+09 | 0.00 | 0.877378E+09 | 0.434012E+10 | 0.419761E+09 |
November | 0.728913E+09 | 0.00 | 0.728913E+09 | 0.254714E+10 | 0.110027E+10 |
December | 0.664078E+09 | 0.00 | 0.664078E+09 | 0.144502E+10 | 0.203002E+10 |
Annual Sum or Average | 0.113664E+11 | 0.207307E+09 | 0.111591E+11 | 0.543139E+11 | 0.110938E+11 |
Minimum of Months | 0.664078E+09 | 0.00 | 0.664078E+09 | 0.121406E+10 | 152449.75 |
Maximum of Months | 0.125534E+10 | 92722543.66 | 0.116261E+10 | 0.865286E+10 | 0.255073E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.859423E+09 | 0.260988E+09 | 0.598435E+09 | 0.174155E+10 | 0.158598E+10 |
February | 0.845711E+09 | 0.230025E+09 | 0.615686E+09 | 0.193015E+10 | 0.121744E+10 |
March | 0.103305E+10 | 0.254748E+09 | 0.778303E+09 | 0.283289E+10 | 0.103143E+10 |
April | 0.121684E+10 | 0.354435E+09 | 0.862401E+09 | 0.409644E+10 | 0.647536E+09 |
May | 0.140309E+10 | 0.445483E+09 | 0.957602E+09 | 0.602909E+10 | 0.169686E+09 |
June | 0.133261E+10 | 0.407995E+09 | 0.924613E+09 | 0.628984E+10 | 33613434.81 |
July | 0.128741E+10 | 0.373161E+09 | 0.914247E+09 | 0.728761E+10 | 398248.74 |
August | 0.131582E+10 | 0.404130E+09 | 0.911686E+09 | 0.752851E+10 | 7177.85 |
September | 0.119576E+10 | 0.368923E+09 | 0.826840E+09 | 0.569401E+10 | 51547565.98 |
October | 0.112163E+10 | 0.366109E+09 | 0.755521E+09 | 0.443885E+10 | 0.253827E+09 |
November | 0.911786E+09 | 0.290025E+09 | 0.621761E+09 | 0.285584E+10 | 0.695957E+09 |
December | 0.763447E+09 | 0.211154E+09 | 0.552294E+09 | 0.177787E+10 | 0.128051E+10 |
Annual Sum or Average | 0.132866E+11 | 0.396718E+10 | 0.931939E+10 | 0.525026E+11 | 0.696793E+10 |
Minimum of Months | 0.763447E+09 | 0.211154E+09 | 0.552294E+09 | 0.174155E+10 | 7177.85 |
Maximum of Months | 0.140309E+10 | 0.445483E+09 | 0.957602E+09 | 0.752851E+10 | 0.158598E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228100E+10 | 0.106265E+10 | 0.121835E+10 | 0.526508E+10 | 0.251894E+10 |
February | 0.196071E+10 | 0.808182E+09 | 0.115253E+10 | 0.488013E+10 | 0.195646E+10 |
March | 0.183154E+10 | 0.536880E+09 | 0.129466E+10 | 0.524780E+10 | 0.167827E+10 |
April | 0.140274E+10 | 0.194157E+09 | 0.120858E+10 | 0.506162E+10 | 0.103031E+10 |
May | 0.119742E+10 | 32175432.60 | 0.116524E+10 | 0.636965E+10 | 0.267107E+09 |
June | 0.108000E+10 | 2832297.93 | 0.107717E+10 | 0.669795E+10 | 45702223.01 |
July | 0.112166E+10 | 16708698.66 | 0.110496E+10 | 0.844429E+10 | 275615.77 |
August | 0.133220E+10 | 0.131143E+09 | 0.120105E+10 | 0.940726E+10 | 12189.58 |
September | 0.171916E+10 | 0.447780E+09 | 0.127138E+10 | 0.850579E+10 | 87517471.68 |
October | 0.227245E+10 | 0.928197E+09 | 0.134426E+10 | 0.856177E+10 | 0.423122E+09 |
November | 0.237345E+10 | 0.113964E+10 | 0.123381E+10 | 0.723815E+10 | 0.113495E+10 |
December | 0.225811E+10 | 0.110176E+10 | 0.115634E+10 | 0.576882E+10 | 0.205936E+10 |
Annual Sum or Average | 0.208304E+11 | 0.640212E+10 | 0.144283E+11 | 0.814483E+11 | 0.112020E+11 |
Minimum of Months | 0.108000E+10 | 2832297.93 | 0.107717E+10 | 0.488013E+10 | 12189.58 |
Maximum of Months | 0.237345E+10 | 0.113964E+10 | 0.134426E+10 | 0.940726E+10 | 0.251894E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.843432E+09 | 0.243649E+09 | 0.599784E+09 | 0.178164E+10 | 0.169742E+10 |
February | 0.869761E+09 | 0.249371E+09 | 0.620390E+09 | 0.206334E+10 | 0.127873E+10 |
March | 0.113731E+10 | 0.336100E+09 | 0.801209E+09 | 0.313824E+10 | 0.109199E+10 |
April | 0.120131E+10 | 0.335783E+09 | 0.865523E+09 | 0.403647E+10 | 0.690926E+09 |
May | 0.135375E+10 | 0.405127E+09 | 0.948619E+09 | 0.588276E+10 | 0.191776E+09 |
June | 0.135408E+10 | 0.426895E+09 | 0.927185E+09 | 0.636258E+10 | 36966127.11 |
July | 0.128604E+10 | 0.369681E+09 | 0.916357E+09 | 0.728029E+10 | 216363.08 |
August | 0.131519E+10 | 0.398766E+09 | 0.916428E+09 | 0.748087E+10 | 148366.68 |
September | 0.121095E+10 | 0.379595E+09 | 0.831359E+09 | 0.573722E+10 | 61266921.30 |
October | 0.111322E+10 | 0.359613E+09 | 0.753603E+09 | 0.446106E+10 | 0.287127E+09 |
November | 0.927116E+09 | 0.304086E+09 | 0.623030E+09 | 0.299833E+10 | 0.738491E+09 |
December | 0.803774E+09 | 0.244994E+09 | 0.558780E+09 | 0.198456E+10 | 0.134537E+10 |
Annual Sum or Average | 0.134159E+11 | 0.405366E+10 | 0.936227E+10 | 0.532073E+11 | 0.742044E+10 |
Minimum of Months | 0.803774E+09 | 0.243649E+09 | 0.558780E+09 | 0.178164E+10 | 148366.68 |
Maximum of Months | 0.135408E+10 | 0.426895E+09 | 0.948619E+09 | 0.748087E+10 | 0.169742E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237153E+09 | 0.00 | 0.237153E+09 | 0.375673E+09 | 0.101964E+10 |
February | 0.245537E+09 | 0.00 | 0.245537E+09 | 0.503113E+09 | 0.753474E+09 |
March | 0.312250E+09 | 0.00 | 0.312250E+09 | 0.857417E+09 | 0.608046E+09 |
April | 0.340948E+09 | 1193436.62 | 0.339754E+09 | 0.128844E+10 | 0.360082E+09 |
May | 0.400677E+09 | 16304071.95 | 0.384373E+09 | 0.212898E+10 | 90289103.36 |
June | 0.418430E+09 | 30906540.12 | 0.387524E+09 | 0.240277E+10 | 20582409.23 |
July | 0.393844E+09 | 16011359.21 | 0.377833E+09 | 0.285471E+10 | 286304.80 |
August | 0.363782E+09 | 4611886.02 | 0.359170E+09 | 0.280885E+10 | 57641.36 |
September | 0.319293E+09 | 72765.89 | 0.319221E+09 | 0.198149E+10 | 38121613.74 |
October | 0.292449E+09 | 0.00 | 0.292449E+09 | 0.140724E+10 | 0.176958E+09 |
November | 0.242962E+09 | 0.00 | 0.242962E+09 | 0.805677E+09 | 0.473630E+09 |
December | 0.221351E+09 | 0.00 | 0.221351E+09 | 0.439464E+09 | 0.853384E+09 |
Annual Sum or Average | 0.378868E+10 | 69100059.81 | 0.371958E+10 | 0.178538E+11 | 0.439455E+10 |
Minimum of Months | 0.221351E+09 | 0.00 | 0.221351E+09 | 0.375673E+09 | 57641.36 |
Maximum of Months | 0.418430E+09 | 30906540.12 | 0.387524E+09 | 0.285471E+10 | 0.101964E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237164E+09 | 0.00 | 0.237164E+09 | 0.375689E+09 | 0.101970E+10 |
February | 0.245549E+09 | 0.00 | 0.245549E+09 | 0.503137E+09 | 0.753517E+09 |
March | 0.312265E+09 | 0.00 | 0.312265E+09 | 0.857461E+09 | 0.608078E+09 |
April | 0.340964E+09 | 1193482.70 | 0.339770E+09 | 0.128851E+10 | 0.360100E+09 |
May | 0.400696E+09 | 16304701.50 | 0.384391E+09 | 0.212911E+10 | 90292191.92 |
June | 0.418450E+09 | 30907733.53 | 0.387542E+09 | 0.240291E+10 | 20582446.10 |
July | 0.393863E+09 | 16011977.46 | 0.377851E+09 | 0.285488E+10 | 286265.75 |
August | 0.363799E+09 | 4612064.10 | 0.359187E+09 | 0.280902E+10 | 57627.41 |
September | 0.319309E+09 | 72768.70 | 0.319236E+09 | 0.198161E+10 | 38122577.34 |
October | 0.292462E+09 | 0.00 | 0.292462E+09 | 0.140732E+10 | 0.176965E+09 |
November | 0.242973E+09 | 0.00 | 0.242973E+09 | 0.805721E+09 | 0.473654E+09 |
December | 0.221362E+09 | 0.00 | 0.221362E+09 | 0.439485E+09 | 0.853432E+09 |
Annual Sum or Average | 0.378885E+10 | 69102728.00 | 0.371975E+10 | 0.178549E+11 | 0.439478E+10 |
Minimum of Months | 0.221362E+09 | 0.00 | 0.221362E+09 | 0.375689E+09 | 57627.41 |
Maximum of Months | 0.418450E+09 | 30907733.53 | 0.387542E+09 | 0.285488E+10 | 0.101970E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237164E+09 | 0.00 | 0.237164E+09 | 0.375689E+09 | 0.101970E+10 |
February | 0.245549E+09 | 0.00 | 0.245549E+09 | 0.503137E+09 | 0.753517E+09 |
March | 0.312265E+09 | 0.00 | 0.312265E+09 | 0.857461E+09 | 0.608078E+09 |
April | 0.340964E+09 | 1193482.70 | 0.339770E+09 | 0.128851E+10 | 0.360100E+09 |
May | 0.400696E+09 | 16304701.50 | 0.384391E+09 | 0.212911E+10 | 90292191.92 |
June | 0.418450E+09 | 30907733.53 | 0.387542E+09 | 0.240291E+10 | 20582446.10 |
July | 0.393863E+09 | 16011977.46 | 0.377851E+09 | 0.285488E+10 | 286265.75 |
August | 0.363799E+09 | 4612064.10 | 0.359187E+09 | 0.280902E+10 | 57627.41 |
September | 0.319309E+09 | 72768.70 | 0.319236E+09 | 0.198161E+10 | 38122577.34 |
October | 0.292462E+09 | 0.00 | 0.292462E+09 | 0.140732E+10 | 0.176965E+09 |
November | 0.242973E+09 | 0.00 | 0.242973E+09 | 0.805721E+09 | 0.473654E+09 |
December | 0.221362E+09 | 0.00 | 0.221362E+09 | 0.439485E+09 | 0.853432E+09 |
Annual Sum or Average | 0.378885E+10 | 69102728.00 | 0.371975E+10 | 0.178549E+11 | 0.439478E+10 |
Minimum of Months | 0.221362E+09 | 0.00 | 0.221362E+09 | 0.375689E+09 | 57627.41 |
Maximum of Months | 0.418450E+09 | 30907733.53 | 0.387542E+09 | 0.285488E+10 | 0.101970E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.826763E+09 | 0.251072E+09 | 0.575692E+09 | 0.160572E+10 | 0.181896E+10 |
February | 0.813572E+09 | 0.221285E+09 | 0.592287E+09 | 0.184180E+10 | 0.136577E+10 |
March | 0.993793E+09 | 0.245069E+09 | 0.748724E+09 | 0.275651E+10 | 0.111145E+10 |
April | 0.117059E+10 | 0.340967E+09 | 0.829625E+09 | 0.399720E+10 | 0.677404E+09 |
May | 0.134976E+10 | 0.428556E+09 | 0.921208E+09 | 0.584351E+10 | 0.170540E+09 |
June | 0.128196E+10 | 0.392492E+09 | 0.889472E+09 | 0.606814E+10 | 35583064.42 |
July | 0.123848E+10 | 0.358982E+09 | 0.879499E+09 | 0.698797E+10 | 344793.44 |
August | 0.126581E+10 | 0.388775E+09 | 0.877036E+09 | 0.717854E+10 | 68544.62 |
September | 0.115032E+10 | 0.354905E+09 | 0.795416E+09 | 0.543877E+10 | 67050080.68 |
October | 0.107901E+10 | 0.352199E+09 | 0.726807E+09 | 0.422185E+10 | 0.319396E+09 |
November | 0.877136E+09 | 0.279005E+09 | 0.598131E+09 | 0.267787E+10 | 0.864504E+09 |
December | 0.734435E+09 | 0.203131E+09 | 0.531304E+09 | 0.162074E+10 | 0.153695E+10 |
Annual Sum or Average | 0.127816E+11 | 0.381644E+10 | 0.896520E+10 | 0.502386E+11 | 0.796801E+10 |
Minimum of Months | 0.734435E+09 | 0.203131E+09 | 0.531304E+09 | 0.160572E+10 | 68544.62 |
Maximum of Months | 0.134976E+10 | 0.428556E+09 | 0.921208E+09 | 0.717854E+10 | 0.181896E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32689480.83 | 9927146.71 | 22762334.12 | 63488721.01 | 71919915.81 |
February | 32167903.54 | 8749420.70 | 23418482.84 | 72823227.07 | 54001215.72 |
March | 39293663.66 | 9689802.01 | 29603861.65 | 0.108990E+09 | 43945573.44 |
April | 46284158.23 | 13481540.70 | 32802617.53 | 0.158046E+09 | 26783925.06 |
May | 53368444.97 | 16944717.65 | 36423727.32 | 0.231047E+09 | 6742994.35 |
June | 50687730.09 | 15518796.12 | 35168933.97 | 0.239929E+09 | 1406922.33 |
July | 48968453.90 | 14193840.93 | 34774612.97 | 0.276298E+09 | 13632.82 |
August | 50049041.67 | 15371811.90 | 34677229.77 | 0.283833E+09 | 2710.19 |
September | 45482642.44 | 14032628.51 | 31450013.93 | 0.215044E+09 | 2651099.82 |
October | 42662908.29 | 13925617.92 | 28737290.38 | 0.166928E+09 | 12628637.98 |
November | 34681168.45 | 11031608.42 | 23649560.03 | 0.105881E+09 | 34181726.09 |
December | 29038880.58 | 8031605.26 | 21007275.32 | 64082694.81 | 60769731.59 |
Annual Sum or Average | 0.505374E+09 | 0.150899E+09 | 0.354476E+09 | 0.198639E+10 | 0.315048E+09 |
Minimum of Months | 29038880.58 | 8031605.26 | 21007275.32 | 63488721.01 | 2710.19 |
Maximum of Months | 53368444.97 | 16944717.65 | 36423727.32 | 0.283833E+09 | 71919915.81 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.760354E+09 | 0.354227E+09 | 0.406126E+09 | 0.175283E+10 | 0.102123E+10 |
February | 0.653587E+09 | 0.269401E+09 | 0.384186E+09 | 0.164047E+10 | 0.777110E+09 |
March | 0.610530E+09 | 0.178965E+09 | 0.431565E+09 | 0.177305E+10 | 0.639124E+09 |
April | 0.467592E+09 | 64720664.86 | 0.402871E+09 | 0.171070E+10 | 0.374700E+09 |
May | 0.399148E+09 | 10725435.08 | 0.388422E+09 | 0.212208E+10 | 91617074.27 |
June | 0.360009E+09 | 944124.92 | 0.359065E+09 | 0.220724E+10 | 16700297.62 |
July | 0.373897E+09 | 5569717.27 | 0.368327E+09 | 0.276649E+10 | 79764.61 |
August | 0.444076E+09 | 43715576.76 | 0.400361E+09 | 0.305794E+10 | 62834.18 |
September | 0.573067E+09 | 0.149264E+09 | 0.423803E+09 | 0.279110E+10 | 41744315.49 |
October | 0.757504E+09 | 0.309407E+09 | 0.448096E+09 | 0.282777E+10 | 0.194318E+09 |
November | 0.791171E+09 | 0.379891E+09 | 0.411280E+09 | 0.239879E+10 | 0.504500E+09 |
December | 0.752722E+09 | 0.367265E+09 | 0.385457E+09 | 0.190796E+10 | 0.871193E+09 |
Annual Sum or Average | 0.694366E+10 | 0.213410E+10 | 0.480956E+10 | 0.269564E+11 | 0.453237E+10 |
Minimum of Months | 0.360009E+09 | 944124.92 | 0.359065E+09 | 0.164047E+10 | 62834.18 |
Maximum of Months | 0.791171E+09 | 0.379891E+09 | 0.448096E+09 | 0.305794E+10 | 0.102123E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.760354E+09 | 0.354227E+09 | 0.406126E+09 | 0.175283E+10 | 0.102123E+10 |
February | 0.653587E+09 | 0.269401E+09 | 0.384186E+09 | 0.164047E+10 | 0.777110E+09 |
March | 0.610530E+09 | 0.178965E+09 | 0.431565E+09 | 0.177305E+10 | 0.639124E+09 |
April | 0.467592E+09 | 64720664.86 | 0.402871E+09 | 0.171070E+10 | 0.374700E+09 |
May | 0.399148E+09 | 10725435.08 | 0.388422E+09 | 0.212208E+10 | 91617074.27 |
June | 0.360009E+09 | 944124.92 | 0.359065E+09 | 0.220724E+10 | 16700297.62 |
July | 0.373897E+09 | 5569717.27 | 0.368327E+09 | 0.276649E+10 | 79764.61 |
August | 0.444076E+09 | 43715576.76 | 0.400361E+09 | 0.305794E+10 | 62834.18 |
September | 0.573067E+09 | 0.149264E+09 | 0.423803E+09 | 0.279110E+10 | 41744315.49 |
October | 0.757504E+09 | 0.309407E+09 | 0.448096E+09 | 0.282777E+10 | 0.194318E+09 |
November | 0.791171E+09 | 0.379891E+09 | 0.411280E+09 | 0.239879E+10 | 0.504500E+09 |
December | 0.752722E+09 | 0.367265E+09 | 0.385457E+09 | 0.190796E+10 | 0.871193E+09 |
Annual Sum or Average | 0.694366E+10 | 0.213410E+10 | 0.480956E+10 | 0.269564E+11 | 0.453237E+10 |
Minimum of Months | 0.360009E+09 | 944124.92 | 0.359065E+09 | 0.164047E+10 | 62834.18 |
Maximum of Months | 0.791171E+09 | 0.379891E+09 | 0.448096E+09 | 0.305794E+10 | 0.102123E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.760305E+09 | 0.354205E+09 | 0.406100E+09 | 0.175272E+10 | 0.102116E+10 |
February | 0.653546E+09 | 0.269384E+09 | 0.384161E+09 | 0.164037E+10 | 0.777061E+09 |
March | 0.610491E+09 | 0.178953E+09 | 0.431538E+09 | 0.177293E+10 | 0.639083E+09 |
April | 0.467562E+09 | 64716574.88 | 0.402845E+09 | 0.171060E+10 | 0.374676E+09 |
May | 0.399122E+09 | 10724757.29 | 0.388398E+09 | 0.212194E+10 | 91611284.59 |
June | 0.359987E+09 | 944065.25 | 0.359042E+09 | 0.220710E+10 | 16699242.25 |
July | 0.373873E+09 | 5569365.30 | 0.368304E+09 | 0.276632E+10 | 79759.57 |
August | 0.444048E+09 | 43712814.19 | 0.400335E+09 | 0.305775E+10 | 62830.21 |
September | 0.573031E+09 | 0.149254E+09 | 0.423776E+09 | 0.279092E+10 | 41741677.48 |
October | 0.757456E+09 | 0.309388E+09 | 0.448068E+09 | 0.282759E+10 | 0.194306E+09 |
November | 0.791121E+09 | 0.379867E+09 | 0.411254E+09 | 0.239864E+10 | 0.504468E+09 |
December | 0.752675E+09 | 0.367242E+09 | 0.385433E+09 | 0.190784E+10 | 0.871138E+09 |
Annual Sum or Average | 0.694322E+10 | 0.213396E+10 | 0.480925E+10 | 0.269547E+11 | 0.453209E+10 |
Minimum of Months | 0.359987E+09 | 944065.25 | 0.359042E+09 | 0.164037E+10 | 62830.21 |
Maximum of Months | 0.791121E+09 | 0.379867E+09 | 0.448068E+09 | 0.305775E+10 | 0.102116E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.811378E+09 | 0.234390E+09 | 0.576988E+09 | 0.169637E+10 | 0.194717E+10 |
February | 0.836706E+09 | 0.239895E+09 | 0.596811E+09 | 0.199888E+10 | 0.144344E+10 |
March | 0.109409E+10 | 0.323328E+09 | 0.770758E+09 | 0.307575E+10 | 0.119391E+10 |
April | 0.115565E+10 | 0.323024E+09 | 0.832627E+09 | 0.395334E+10 | 0.730861E+09 |
May | 0.130230E+10 | 0.389732E+09 | 0.912564E+09 | 0.569845E+10 | 0.196110E+09 |
June | 0.130262E+10 | 0.410673E+09 | 0.891945E+09 | 0.612246E+10 | 41247596.11 |
July | 0.123716E+10 | 0.355634E+09 | 0.881528E+09 | 0.695881E+10 | 309627.55 |
August | 0.126521E+10 | 0.383613E+09 | 0.881596E+09 | 0.711912E+10 | 177495.33 |
September | 0.116493E+10 | 0.365170E+09 | 0.799761E+09 | 0.546945E+10 | 79661348.36 |
October | 0.107091E+10 | 0.345948E+09 | 0.724960E+09 | 0.423431E+10 | 0.358594E+09 |
November | 0.891881E+09 | 0.292531E+09 | 0.599350E+09 | 0.281644E+10 | 0.931253E+09 |
December | 0.773227E+09 | 0.235684E+09 | 0.537543E+09 | 0.185737E+10 | 0.162778E+10 |
Annual Sum or Average | 0.129061E+11 | 0.389962E+10 | 0.900643E+10 | 0.510007E+11 | 0.855051E+10 |
Minimum of Months | 0.773227E+09 | 0.234390E+09 | 0.537543E+09 | 0.169637E+10 | 177495.33 |
Maximum of Months | 0.130262E+10 | 0.410673E+09 | 0.912564E+09 | 0.711912E+10 | 0.194717E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32081158.98 | 9267573.99 | 22813584.99 | 67073125.81 | 76989360.22 |
February | 33082594.06 | 9485226.41 | 23597367.65 | 79034081.26 | 57072293.61 |
March | 43259169.14 | 12784104.97 | 30475064.17 | 0.121612E+09 | 47206256.81 |
April | 45693383.71 | 12772073.79 | 32921309.92 | 0.156312E+09 | 28897580.73 |
May | 51491620.13 | 15409666.54 | 36081953.59 | 0.225312E+09 | 7754024.13 |
June | 51504333.30 | 16237650.33 | 35266682.97 | 0.242076E+09 | 1630892.81 |
July | 48916249.69 | 14061437.74 | 34854811.95 | 0.275145E+09 | 12242.39 |
August | 50025226.63 | 15167717.93 | 34857508.70 | 0.281483E+09 | 7018.01 |
September | 46060336.29 | 14438503.65 | 31621832.64 | 0.216257E+09 | 3149737.99 |
October | 42342755.48 | 13678481.65 | 28664273.83 | 0.167421E+09 | 14178473.45 |
November | 35264188.21 | 11566420.21 | 23697768.00 | 0.111359E+09 | 36820904.48 |
December | 30572688.15 | 9318731.33 | 21253956.81 | 73438717.28 | 64360805.86 |
Annual Sum or Average | 0.510294E+09 | 0.154188E+09 | 0.356106E+09 | 0.201652E+10 | 0.338080E+09 |
Minimum of Months | 30572688.15 | 9267573.99 | 21253956.81 | 67073125.81 | 7018.01 |
Maximum of Months | 51504333.30 | 16237650.33 | 36081953.59 | 0.281483E+09 | 76989360.22 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.711484E+09 | 0.00 | 0.711484E+09 | 0.114267E+10 | 0.287354E+10 |
February | 0.736639E+09 | 0.00 | 0.736639E+09 | 0.149780E+10 | 0.216650E+10 |
March | 0.936786E+09 | 0.00 | 0.936786E+09 | 0.252421E+10 | 0.180786E+10 |
April | 0.102288E+10 | 3580422.73 | 0.101930E+10 | 0.382549E+10 | 0.109567E+10 |
May | 0.120208E+10 | 48913757.96 | 0.115316E+10 | 0.639351E+10 | 0.288887E+09 |
June | 0.125534E+10 | 92722543.66 | 0.116261E+10 | 0.725921E+10 | 63842094.17 |
July | 0.118158E+10 | 48035592.07 | 0.113354E+10 | 0.868676E+10 | 646346.31 |
August | 0.109139E+10 | 13836094.29 | 0.107755E+10 | 0.860641E+10 | 325870.56 |
September | 0.957916E+09 | 218304.56 | 0.957698E+09 | 0.607192E+10 | 99166416.08 |
October | 0.877378E+09 | 0.00 | 0.877378E+09 | 0.433473E+10 | 0.470495E+09 |
November | 0.728913E+09 | 0.00 | 0.728913E+09 | 0.250412E+10 | 0.125602E+10 |
December | 0.664078E+09 | 0.00 | 0.664078E+09 | 0.137270E+10 | 0.231582E+10 |
Annual Sum or Average | 0.113664E+11 | 0.207307E+09 | 0.111591E+11 | 0.542195E+11 | 0.124388E+11 |
Minimum of Months | 0.664078E+09 | 0.00 | 0.664078E+09 | 0.114267E+10 | 325870.56 |
Maximum of Months | 0.125534E+10 | 92722543.66 | 0.116261E+10 | 0.868676E+10 | 0.287354E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.859423E+09 | 0.260988E+09 | 0.598435E+09 | 0.169176E+10 | 0.174708E+10 |
February | 0.845711E+09 | 0.230025E+09 | 0.615686E+09 | 0.190357E+10 | 0.133653E+10 |
March | 0.103305E+10 | 0.254748E+09 | 0.778303E+09 | 0.281834E+10 | 0.112462E+10 |
April | 0.121684E+10 | 0.354435E+09 | 0.862401E+09 | 0.410101E+10 | 0.693450E+09 |
May | 0.140309E+10 | 0.445483E+09 | 0.957602E+09 | 0.605084E+10 | 0.180283E+09 |
June | 0.133261E+10 | 0.407995E+09 | 0.924613E+09 | 0.631316E+10 | 35945381.25 |
July | 0.128741E+10 | 0.373161E+09 | 0.914247E+09 | 0.731642E+10 | 285545.45 |
August | 0.131582E+10 | 0.404130E+09 | 0.911686E+09 | 0.754801E+10 | 119012.49 |
September | 0.119576E+10 | 0.368923E+09 | 0.826840E+09 | 0.570603E+10 | 56546673.17 |
October | 0.112163E+10 | 0.366109E+09 | 0.755521E+09 | 0.443627E+10 | 0.280702E+09 |
November | 0.911786E+09 | 0.290025E+09 | 0.621761E+09 | 0.282545E+10 | 0.779056E+09 |
December | 0.763447E+09 | 0.211154E+09 | 0.552294E+09 | 0.173031E+10 | 0.142777E+10 |
Annual Sum or Average | 0.132866E+11 | 0.396718E+10 | 0.931939E+10 | 0.524412E+11 | 0.766238E+10 |
Minimum of Months | 0.763447E+09 | 0.211154E+09 | 0.552294E+09 | 0.169176E+10 | 119012.49 |
Maximum of Months | 0.140309E+10 | 0.445483E+09 | 0.957602E+09 | 0.754801E+10 | 0.174708E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228100E+10 | 0.106265E+10 | 0.121835E+10 | 0.521470E+10 | 0.280342E+10 |
February | 0.196071E+10 | 0.808182E+09 | 0.115253E+10 | 0.486068E+10 | 0.216760E+10 |
March | 0.183154E+10 | 0.536880E+09 | 0.129466E+10 | 0.525000E+10 | 0.185058E+10 |
April | 0.140274E+10 | 0.194157E+09 | 0.120858E+10 | 0.508451E+10 | 0.112001E+10 |
May | 0.119742E+10 | 32175432.60 | 0.116524E+10 | 0.640417E+10 | 0.289358E+09 |
June | 0.108000E+10 | 2832297.93 | 0.107717E+10 | 0.672867E+10 | 50632806.04 |
July | 0.112166E+10 | 16708698.66 | 0.110496E+10 | 0.847863E+10 | 217711.89 |
August | 0.133220E+10 | 0.131143E+09 | 0.120105E+10 | 0.943254E+10 | 166673.88 |
September | 0.171916E+10 | 0.447780E+09 | 0.127138E+10 | 0.853818E+10 | 97396747.27 |
October | 0.227245E+10 | 0.928197E+09 | 0.134426E+10 | 0.858498E+10 | 0.471224E+09 |
November | 0.237345E+10 | 0.113964E+10 | 0.123381E+10 | 0.722834E+10 | 0.127694E+10 |
December | 0.225811E+10 | 0.110176E+10 | 0.115634E+10 | 0.571894E+10 | 0.231029E+10 |
Annual Sum or Average | 0.208304E+11 | 0.640212E+10 | 0.144283E+11 | 0.815243E+11 | 0.124379E+11 |
Minimum of Months | 0.108000E+10 | 2832297.93 | 0.107717E+10 | 0.486068E+10 | 166673.88 |
Maximum of Months | 0.237345E+10 | 0.113964E+10 | 0.134426E+10 | 0.943254E+10 | 0.280342E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.843432E+09 | 0.243649E+09 | 0.599784E+09 | 0.175488E+10 | 0.188516E+10 |
February | 0.869761E+09 | 0.249371E+09 | 0.620390E+09 | 0.205151E+10 | 0.141826E+10 |
March | 0.113731E+10 | 0.336100E+09 | 0.801209E+09 | 0.314105E+10 | 0.120414E+10 |
April | 0.120131E+10 | 0.335783E+09 | 0.865523E+09 | 0.405835E+10 | 0.748134E+09 |
May | 0.135375E+10 | 0.405127E+09 | 0.948619E+09 | 0.591532E+10 | 0.206385E+09 |
June | 0.135408E+10 | 0.426895E+09 | 0.927185E+09 | 0.639352E+10 | 40141048.86 |
July | 0.128604E+10 | 0.369681E+09 | 0.916357E+09 | 0.730961E+10 | 172180.53 |
August | 0.131519E+10 | 0.398766E+09 | 0.916428E+09 | 0.750649E+10 | 310833.22 |
September | 0.121095E+10 | 0.379595E+09 | 0.831359E+09 | 0.575582E+10 | 67543569.06 |
October | 0.111322E+10 | 0.359613E+09 | 0.753603E+09 | 0.446538E+10 | 0.318924E+09 |
November | 0.927116E+09 | 0.304086E+09 | 0.623030E+09 | 0.297903E+10 | 0.836926E+09 |
December | 0.803774E+09 | 0.244994E+09 | 0.558780E+09 | 0.195454E+10 | 0.151576E+10 |
Annual Sum or Average | 0.134159E+11 | 0.405366E+10 | 0.936227E+10 | 0.532855E+11 | 0.824186E+10 |
Minimum of Months | 0.803774E+09 | 0.243649E+09 | 0.558780E+09 | 0.175488E+10 | 172180.53 |
Maximum of Months | 0.135408E+10 | 0.426895E+09 | 0.948619E+09 | 0.750649E+10 | 0.188516E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 453.28 | 952.33 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
February | 636.94 | 800.52 | 304.50 | 0.00 | 304.50 | 0.00 | 0.00 |
March | 949.47 | 608.18 | 349.76 | 0.00 | 349.76 | 0.00 | 0.00 |
April | 1470.45 | 388.70 | 394.63 | 1.38 | 393.25 | 0.00 | 0.00 |
May | 2373.76 | 101.00 | 448.80 | 18.26 | 430.54 | 0.00 | 0.00 |
June | 2785.86 | 22.93 | 484.31 | 35.77 | 448.54 | 0.00 | 0.00 |
July | 3230.61 | 0.25 | 441.15 | 17.93 | 423.22 | 0.00 | 0.00 |
August | 3204.64 | 0.06 | 407.48 | 5.17 | 402.31 | 0.00 | 0.00 |
September | 2336.88 | 34.40 | 369.57 | 0.08 | 369.48 | 0.00 | 0.00 |
October | 1620.41 | 156.72 | 327.58 | 0.00 | 327.58 | 0.00 | 0.00 |
November | 982.69 | 424.49 | 281.22 | 0.00 | 281.22 | 0.00 | 0.00 |
December | 539.51 | 757.92 | 247.94 | 0.00 | 247.94 | 0.00 | 0.00 |
Annual Sum or Average | 1722.28 | 351.78 | 360.43 | 6.57 | 353.85 | 0.00 | 0.00 |
Minimum of Months | 453.28 | 0.06 | 247.94 | 0.00 | 247.94 | 0.00 | 0.00 |
Maximum of Months | 3230.61 | 952.33 | 484.31 | 35.77 | 448.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 650.22 | 592.14 | 320.87 | 97.44 | 223.43 | 0.00 | 0.00 |
February | 797.84 | 503.24 | 349.58 | 95.08 | 254.50 | 0.00 | 0.00 |
March | 1057.68 | 385.09 | 385.70 | 95.11 | 290.59 | 0.00 | 0.00 |
April | 1580.42 | 249.82 | 469.46 | 136.74 | 332.72 | 0.00 | 0.00 |
May | 2251.01 | 63.35 | 523.85 | 166.32 | 357.53 | 0.00 | 0.00 |
June | 2426.64 | 12.97 | 514.12 | 157.41 | 356.72 | 0.00 | 0.00 |
July | 2720.88 | 0.15 | 480.66 | 139.32 | 341.34 | 0.00 | 0.00 |
August | 2810.82 | 0.00 | 491.27 | 150.89 | 340.38 | 0.00 | 0.00 |
September | 2196.76 | 19.89 | 461.33 | 142.33 | 319.00 | 0.00 | 0.00 |
October | 1657.28 | 94.77 | 418.77 | 136.69 | 282.08 | 0.00 | 0.00 |
November | 1101.79 | 268.50 | 351.77 | 111.89 | 239.88 | 0.00 | 0.00 |
December | 663.78 | 478.09 | 285.04 | 78.84 | 206.20 | 0.00 | 0.00 |
Annual Sum or Average | 1664.85 | 220.95 | 421.31 | 125.80 | 295.52 | 0.00 | 0.00 |
Minimum of Months | 650.22 | 0.00 | 285.04 | 78.84 | 206.20 | 0.00 | 0.00 |
Maximum of Months | 2810.82 | 592.14 | 523.85 | 166.32 | 357.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1965.76 | 940.46 | 851.63 | 396.75 | 454.88 | 0.00 | 0.00 |
February | 2017.25 | 808.72 | 810.48 | 334.07 | 476.41 | 0.00 | 0.00 |
March | 1959.30 | 626.60 | 683.82 | 200.45 | 483.37 | 0.00 | 0.00 |
April | 1952.78 | 397.50 | 541.18 | 74.91 | 466.27 | 0.00 | 0.00 |
May | 2378.15 | 99.73 | 447.06 | 12.01 | 435.05 | 0.00 | 0.00 |
June | 2584.09 | 17.63 | 416.67 | 1.09 | 415.58 | 0.00 | 0.00 |
July | 3152.74 | 0.10 | 418.78 | 6.24 | 412.54 | 0.00 | 0.00 |
August | 3512.27 | 0.00 | 497.39 | 48.96 | 448.42 | 0.00 | 0.00 |
September | 3281.55 | 33.76 | 663.26 | 172.75 | 490.50 | 0.00 | 0.00 |
October | 3196.60 | 157.98 | 848.44 | 346.55 | 501.89 | 0.00 | 0.00 |
November | 2792.50 | 437.86 | 915.68 | 439.68 | 476.01 | 0.00 | 0.00 |
December | 2153.83 | 768.88 | 843.08 | 411.35 | 431.73 | 0.00 | 0.00 |
Annual Sum or Average | 2582.71 | 355.21 | 660.53 | 203.01 | 457.52 | 0.00 | 0.00 |
Minimum of Months | 1952.78 | 0.00 | 416.67 | 1.09 | 412.54 | 0.00 | 0.00 |
Maximum of Months | 3512.27 | 940.46 | 915.68 | 439.68 | 501.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 665.19 | 633.75 | 314.90 | 90.97 | 223.93 | 0.00 | 0.00 |
February | 852.90 | 528.58 | 359.52 | 103.08 | 256.44 | 0.00 | 0.00 |
March | 1171.68 | 407.70 | 424.62 | 125.49 | 299.14 | 0.00 | 0.00 |
April | 1557.28 | 266.56 | 463.47 | 129.55 | 333.92 | 0.00 | 0.00 |
May | 2196.37 | 71.60 | 505.43 | 151.26 | 354.17 | 0.00 | 0.00 |
June | 2454.70 | 14.26 | 522.41 | 164.70 | 357.71 | 0.00 | 0.00 |
July | 2718.15 | 0.08 | 480.15 | 138.02 | 342.13 | 0.00 | 0.00 |
August | 2793.04 | 0.06 | 491.04 | 148.88 | 342.15 | 0.00 | 0.00 |
September | 2213.43 | 23.64 | 467.19 | 146.45 | 320.74 | 0.00 | 0.00 |
October | 1665.57 | 107.20 | 415.63 | 134.26 | 281.36 | 0.00 | 0.00 |
November | 1156.76 | 284.91 | 357.68 | 117.32 | 240.37 | 0.00 | 0.00 |
December | 740.95 | 502.30 | 300.09 | 91.47 | 208.62 | 0.00 | 0.00 |
Annual Sum or Average | 1687.19 | 235.30 | 425.42 | 128.54 | 296.88 | 0.00 | 0.00 |
Minimum of Months | 665.19 | 0.06 | 300.09 | 90.97 | 208.62 | 0.00 | 0.00 |
Maximum of Months | 2793.04 | 633.75 | 522.41 | 164.70 | 357.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 420.79 | 1142.11 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
February | 623.92 | 934.40 | 304.50 | 0.00 | 304.50 | 0.00 | 0.00 |
March | 960.40 | 681.08 | 349.75 | 0.00 | 349.75 | 0.00 | 0.00 |
April | 1491.30 | 416.78 | 394.63 | 1.38 | 393.25 | 0.00 | 0.00 |
May | 2384.71 | 101.13 | 448.80 | 18.26 | 430.54 | 0.00 | 0.00 |
June | 2781.10 | 23.82 | 484.31 | 35.77 | 448.54 | 0.00 | 0.00 |
July | 3197.61 | 0.32 | 441.15 | 17.93 | 423.21 | 0.00 | 0.00 |
August | 3146.24 | 0.06 | 407.47 | 5.17 | 402.31 | 0.00 | 0.00 |
September | 2293.48 | 44.12 | 369.56 | 0.08 | 369.48 | 0.00 | 0.00 |
October | 1576.27 | 198.21 | 327.57 | 0.00 | 327.57 | 0.00 | 0.00 |
November | 932.53 | 548.20 | 281.21 | 0.00 | 281.21 | 0.00 | 0.00 |
December | 492.25 | 955.89 | 247.94 | 0.00 | 247.94 | 0.00 | 0.00 |
Annual Sum or Average | 1698.49 | 418.07 | 360.43 | 6.57 | 353.85 | 0.00 | 0.00 |
Minimum of Months | 420.79 | 0.06 | 247.94 | 0.00 | 247.94 | 0.00 | 0.00 |
Maximum of Months | 3197.61 | 1142.11 | 484.31 | 35.77 | 448.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 623.21 | 705.97 | 320.88 | 97.45 | 223.44 | 0.00 | 0.00 |
February | 791.43 | 586.88 | 349.59 | 95.09 | 254.51 | 0.00 | 0.00 |
March | 1069.85 | 431.37 | 385.71 | 95.12 | 290.59 | 0.00 | 0.00 |
April | 1603.11 | 271.68 | 469.47 | 136.75 | 332.73 | 0.00 | 0.00 |
May | 2267.98 | 66.19 | 523.87 | 166.33 | 357.54 | 0.00 | 0.00 |
June | 2433.67 | 14.27 | 514.14 | 157.41 | 356.73 | 0.00 | 0.00 |
July | 2712.17 | 0.13 | 480.68 | 139.33 | 341.35 | 0.00 | 0.00 |
August | 2786.13 | 0.03 | 491.29 | 150.89 | 340.39 | 0.00 | 0.00 |
September | 2181.26 | 26.89 | 461.34 | 142.34 | 319.01 | 0.00 | 0.00 |
October | 1638.58 | 123.96 | 418.78 | 136.70 | 282.09 | 0.00 | 0.00 |
November | 1073.98 | 346.72 | 351.78 | 111.90 | 239.88 | 0.00 | 0.00 |
December | 629.04 | 596.52 | 285.05 | 78.84 | 206.21 | 0.00 | 0.00 |
Annual Sum or Average | 1656.04 | 262.65 | 421.33 | 125.80 | 295.52 | 0.00 | 0.00 |
Minimum of Months | 623.21 | 0.03 | 285.05 | 78.84 | 206.21 | 0.00 | 0.00 |
Maximum of Months | 2786.13 | 705.97 | 523.87 | 166.33 | 357.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1963.25 | 1143.82 | 851.63 | 396.75 | 454.88 | 0.00 | 0.00 |
February | 2034.28 | 963.66 | 810.48 | 334.07 | 476.41 | 0.00 | 0.00 |
March | 1985.90 | 715.85 | 683.82 | 200.45 | 483.37 | 0.00 | 0.00 |
April | 1979.94 | 433.67 | 541.18 | 74.91 | 466.28 | 0.00 | 0.00 |
May | 2376.83 | 102.62 | 447.06 | 12.01 | 435.05 | 0.00 | 0.00 |
June | 2554.62 | 19.33 | 416.67 | 1.09 | 415.58 | 0.00 | 0.00 |
July | 3098.61 | 0.09 | 418.78 | 6.24 | 412.54 | 0.00 | 0.00 |
August | 3425.04 | 0.07 | 497.39 | 48.96 | 448.42 | 0.00 | 0.00 |
September | 3230.37 | 48.31 | 663.26 | 172.76 | 490.50 | 0.00 | 0.00 |
October | 3167.24 | 217.65 | 848.44 | 346.55 | 501.89 | 0.00 | 0.00 |
November | 2776.32 | 583.90 | 915.69 | 439.68 | 476.01 | 0.00 | 0.00 |
December | 2137.01 | 975.78 | 843.08 | 411.35 | 431.73 | 0.00 | 0.00 |
Annual Sum or Average | 2564.29 | 431.15 | 660.53 | 203.01 | 457.52 | 0.00 | 0.00 |
Minimum of Months | 1963.25 | 0.07 | 416.67 | 1.09 | 412.54 | 0.00 | 0.00 |
Maximum of Months | 3425.04 | 1143.82 | 915.69 | 439.68 | 501.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 658.40 | 755.73 | 314.91 | 90.97 | 223.94 | 0.00 | 0.00 |
February | 858.93 | 620.25 | 359.54 | 103.08 | 256.45 | 0.00 | 0.00 |
March | 1193.76 | 463.38 | 424.64 | 125.49 | 299.15 | 0.00 | 0.00 |
April | 1585.52 | 293.12 | 463.48 | 129.55 | 333.93 | 0.00 | 0.00 |
May | 2211.68 | 76.11 | 505.45 | 151.26 | 354.18 | 0.00 | 0.00 |
June | 2455.45 | 16.54 | 522.42 | 164.70 | 357.72 | 0.00 | 0.00 |
July | 2700.85 | 0.12 | 480.17 | 138.03 | 342.14 | 0.00 | 0.00 |
August | 2763.07 | 0.07 | 491.05 | 148.89 | 342.16 | 0.00 | 0.00 |
September | 2193.56 | 31.95 | 467.20 | 146.45 | 320.75 | 0.00 | 0.00 |
October | 1643.42 | 139.18 | 415.64 | 134.27 | 281.37 | 0.00 | 0.00 |
November | 1129.55 | 373.49 | 357.70 | 117.32 | 240.37 | 0.00 | 0.00 |
December | 720.88 | 631.77 | 300.10 | 91.47 | 208.63 | 0.00 | 0.00 |
Annual Sum or Average | 1681.17 | 281.86 | 425.43 | 128.55 | 296.88 | 0.00 | 0.00 |
Minimum of Months | 658.40 | 0.07 | 300.10 | 90.97 | 208.63 | 0.00 | 0.00 |
Maximum of Months | 2763.07 | 755.73 | 522.42 | 164.70 | 357.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 426.62 | 1072.86 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
February | 619.13 | 895.54 | 304.50 | 0.00 | 304.50 | 0.00 | 0.00 |
March | 942.43 | 674.98 | 349.76 | 0.00 | 349.76 | 0.00 | 0.00 |
April | 1475.88 | 422.71 | 394.63 | 1.38 | 393.25 | 0.00 | 0.00 |
May | 2387.06 | 107.86 | 448.80 | 18.26 | 430.54 | 0.00 | 0.00 |
June | 2800.62 | 24.63 | 484.31 | 35.77 | 448.54 | 0.00 | 0.00 |
July | 3243.27 | 0.24 | 441.15 | 17.93 | 423.22 | 0.00 | 0.00 |
August | 3213.27 | 0.12 | 407.48 | 5.17 | 402.31 | 0.00 | 0.00 |
September | 2342.56 | 38.26 | 369.57 | 0.08 | 369.48 | 0.00 | 0.00 |
October | 1618.40 | 175.66 | 327.58 | 0.00 | 327.58 | 0.00 | 0.00 |
November | 966.10 | 484.58 | 281.22 | 0.00 | 281.22 | 0.00 | 0.00 |
December | 512.51 | 864.63 | 247.94 | 0.00 | 247.94 | 0.00 | 0.00 |
Annual Sum or Average | 1719.29 | 394.43 | 360.43 | 6.57 | 353.85 | 0.00 | 0.00 |
Minimum of Months | 426.62 | 0.12 | 247.94 | 0.00 | 247.94 | 0.00 | 0.00 |
Maximum of Months | 3243.27 | 1072.86 | 484.31 | 35.77 | 448.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 631.63 | 652.29 | 320.87 | 97.44 | 223.43 | 0.00 | 0.00 |
February | 786.86 | 552.47 | 349.58 | 95.08 | 254.50 | 0.00 | 0.00 |
March | 1052.25 | 419.88 | 385.70 | 95.11 | 290.59 | 0.00 | 0.00 |
April | 1582.18 | 267.53 | 469.46 | 136.74 | 332.72 | 0.00 | 0.00 |
May | 2259.12 | 67.31 | 523.85 | 166.32 | 357.53 | 0.00 | 0.00 |
June | 2435.63 | 13.87 | 514.12 | 157.41 | 356.72 | 0.00 | 0.00 |
July | 2731.64 | 0.11 | 480.66 | 139.32 | 341.34 | 0.00 | 0.00 |
August | 2818.10 | 0.04 | 491.27 | 150.89 | 340.38 | 0.00 | 0.00 |
September | 2201.40 | 21.82 | 461.33 | 142.33 | 319.00 | 0.00 | 0.00 |
October | 1656.31 | 104.80 | 418.77 | 136.69 | 282.08 | 0.00 | 0.00 |
November | 1090.07 | 300.56 | 351.77 | 111.89 | 239.88 | 0.00 | 0.00 |
December | 646.03 | 533.07 | 285.04 | 78.84 | 206.20 | 0.00 | 0.00 |
Annual Sum or Average | 1662.90 | 242.97 | 421.31 | 125.80 | 295.52 | 0.00 | 0.00 |
Minimum of Months | 631.63 | 0.04 | 285.04 | 78.84 | 206.20 | 0.00 | 0.00 |
Maximum of Months | 2818.10 | 652.29 | 523.85 | 166.32 | 357.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1946.95 | 1046.68 | 851.63 | 396.75 | 454.88 | 0.00 | 0.00 |
February | 2009.21 | 896.00 | 810.48 | 334.07 | 476.41 | 0.00 | 0.00 |
March | 1960.13 | 690.93 | 683.82 | 200.45 | 483.37 | 0.00 | 0.00 |
April | 1961.62 | 432.10 | 541.18 | 74.91 | 466.27 | 0.00 | 0.00 |
May | 2391.04 | 108.03 | 447.06 | 12.01 | 435.05 | 0.00 | 0.00 |
June | 2595.94 | 19.53 | 416.67 | 1.09 | 415.58 | 0.00 | 0.00 |
July | 3165.56 | 0.08 | 418.78 | 6.24 | 412.54 | 0.00 | 0.00 |
August | 3521.71 | 0.06 | 497.39 | 48.96 | 448.42 | 0.00 | 0.00 |
September | 3294.05 | 37.58 | 663.26 | 172.75 | 490.50 | 0.00 | 0.00 |
October | 3205.26 | 175.93 | 848.44 | 346.55 | 501.89 | 0.00 | 0.00 |
November | 2788.71 | 492.65 | 915.68 | 439.68 | 476.01 | 0.00 | 0.00 |
December | 2135.21 | 862.57 | 843.08 | 411.35 | 431.73 | 0.00 | 0.00 |
Annual Sum or Average | 2585.12 | 394.40 | 660.53 | 203.01 | 457.52 | 0.00 | 0.00 |
Minimum of Months | 1946.95 | 0.06 | 416.67 | 1.09 | 412.54 | 0.00 | 0.00 |
Maximum of Months | 3521.71 | 1046.68 | 915.68 | 439.68 | 501.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 655.20 | 703.84 | 314.90 | 90.97 | 223.93 | 0.00 | 0.00 |
February | 848.01 | 586.25 | 359.52 | 103.08 | 256.44 | 0.00 | 0.00 |
March | 1172.74 | 449.58 | 424.62 | 125.49 | 299.14 | 0.00 | 0.00 |
April | 1565.72 | 288.63 | 463.47 | 129.55 | 333.92 | 0.00 | 0.00 |
May | 2208.53 | 77.06 | 505.43 | 151.26 | 354.17 | 0.00 | 0.00 |
June | 2466.63 | 15.49 | 522.41 | 164.70 | 357.71 | 0.00 | 0.00 |
July | 2729.10 | 0.06 | 480.15 | 138.02 | 342.13 | 0.00 | 0.00 |
August | 2802.60 | 0.12 | 491.04 | 148.88 | 342.15 | 0.00 | 0.00 |
September | 2220.61 | 26.06 | 467.19 | 146.45 | 320.74 | 0.00 | 0.00 |
October | 1667.18 | 119.07 | 415.63 | 134.26 | 281.36 | 0.00 | 0.00 |
November | 1149.32 | 322.89 | 357.68 | 117.32 | 240.37 | 0.00 | 0.00 |
December | 729.74 | 565.92 | 300.09 | 91.47 | 208.62 | 0.00 | 0.00 |
Annual Sum or Average | 1689.67 | 261.35 | 425.42 | 128.54 | 296.88 | 0.00 | 0.00 |
Minimum of Months | 655.20 | 0.06 | 300.09 | 90.97 | 208.62 | 0.00 | 0.00 |
Maximum of Months | 2802.60 | 703.84 | 522.41 | 164.70 | 357.71 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121406E+10 | 0.255073E+10 | 0.711484E+09 | 0.00 | 0.711484E+09 | 0.00 | 0.00 |
February | 0.154089E+10 | 0.193661E+10 | 0.736639E+09 | 0.00 | 0.736639E+09 | 0.00 | 0.00 |
March | 0.254307E+10 | 0.162894E+10 | 0.936786E+09 | 0.00 | 0.936786E+09 | 0.00 | 0.00 |
April | 0.381141E+10 | 0.100752E+10 | 0.102288E+10 | 3580422.73 | 0.101930E+10 | 0.00 | 0.00 |
May | 0.635787E+10 | 0.270522E+09 | 0.120208E+10 | 48913757.96 | 0.115316E+10 | 0.00 | 0.00 |
June | 0.722096E+10 | 59445636.54 | 0.125534E+10 | 92722543.66 | 0.116261E+10 | 0.00 | 0.00 |
July | 0.865286E+10 | 676121.65 | 0.118158E+10 | 48035592.07 | 0.113354E+10 | 0.00 | 0.00 |
August | 0.858330E+10 | 152449.75 | 0.109139E+10 | 13836094.29 | 0.107755E+10 | 0.00 | 0.00 |
September | 0.605720E+10 | 89160241.43 | 0.957916E+09 | 218304.56 | 0.957698E+09 | 0.00 | 0.00 |
October | 0.434012E+10 | 0.419761E+09 | 0.877378E+09 | 0.00 | 0.877378E+09 | 0.00 | 0.00 |
November | 0.254714E+10 | 0.110027E+10 | 0.728913E+09 | 0.00 | 0.728913E+09 | 0.00 | 0.00 |
December | 0.144502E+10 | 0.203002E+10 | 0.664078E+09 | 0.00 | 0.664078E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.543139E+11 | 0.110938E+11 | 0.113664E+11 | 0.207307E+09 | 0.111591E+11 | 0.00 | 0.00 |
Minimum of Months | 0.121406E+10 | 152449.75 | 0.664078E+09 | 0.00 | 0.664078E+09 | 0.00 | 0.00 |
Maximum of Months | 0.865286E+10 | 0.255073E+10 | 0.125534E+10 | 92722543.66 | 0.116261E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174155E+10 | 0.158598E+10 | 0.859423E+09 | 0.260988E+09 | 0.598435E+09 | 0.00 | 0.00 |
February | 0.193015E+10 | 0.121744E+10 | 0.845711E+09 | 0.230025E+09 | 0.615686E+09 | 0.00 | 0.00 |
March | 0.283289E+10 | 0.103143E+10 | 0.103305E+10 | 0.254748E+09 | 0.778303E+09 | 0.00 | 0.00 |
April | 0.409644E+10 | 0.647536E+09 | 0.121684E+10 | 0.354435E+09 | 0.862401E+09 | 0.00 | 0.00 |
May | 0.602909E+10 | 0.169686E+09 | 0.140309E+10 | 0.445483E+09 | 0.957602E+09 | 0.00 | 0.00 |
June | 0.628984E+10 | 33613434.81 | 0.133261E+10 | 0.407995E+09 | 0.924613E+09 | 0.00 | 0.00 |
July | 0.728761E+10 | 398248.74 | 0.128741E+10 | 0.373161E+09 | 0.914247E+09 | 0.00 | 0.00 |
August | 0.752851E+10 | 7177.85 | 0.131582E+10 | 0.404130E+09 | 0.911686E+09 | 0.00 | 0.00 |
September | 0.569401E+10 | 51547565.98 | 0.119576E+10 | 0.368923E+09 | 0.826840E+09 | 0.00 | 0.00 |
October | 0.443885E+10 | 0.253827E+09 | 0.112163E+10 | 0.366109E+09 | 0.755521E+09 | 0.00 | 0.00 |
November | 0.285584E+10 | 0.695957E+09 | 0.911786E+09 | 0.290025E+09 | 0.621761E+09 | 0.00 | 0.00 |
December | 0.177787E+10 | 0.128051E+10 | 0.763447E+09 | 0.211154E+09 | 0.552294E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.525026E+11 | 0.696793E+10 | 0.132866E+11 | 0.396718E+10 | 0.931939E+10 | 0.00 | 0.00 |
Minimum of Months | 0.174155E+10 | 7177.85 | 0.763447E+09 | 0.211154E+09 | 0.552294E+09 | 0.00 | 0.00 |
Maximum of Months | 0.752851E+10 | 0.158598E+10 | 0.140309E+10 | 0.445483E+09 | 0.957602E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.526508E+10 | 0.251894E+10 | 0.228100E+10 | 0.106265E+10 | 0.121835E+10 | 0.00 | 0.00 |
February | 0.488013E+10 | 0.195646E+10 | 0.196071E+10 | 0.808182E+09 | 0.115253E+10 | 0.00 | 0.00 |
March | 0.524780E+10 | 0.167827E+10 | 0.183154E+10 | 0.536880E+09 | 0.129466E+10 | 0.00 | 0.00 |
April | 0.506162E+10 | 0.103031E+10 | 0.140274E+10 | 0.194157E+09 | 0.120858E+10 | 0.00 | 0.00 |
May | 0.636965E+10 | 0.267107E+09 | 0.119742E+10 | 32175432.60 | 0.116524E+10 | 0.00 | 0.00 |
June | 0.669795E+10 | 45702223.01 | 0.108000E+10 | 2832297.93 | 0.107717E+10 | 0.00 | 0.00 |
July | 0.844429E+10 | 275615.77 | 0.112166E+10 | 16708698.66 | 0.110496E+10 | 0.00 | 0.00 |
August | 0.940726E+10 | 12189.58 | 0.133220E+10 | 0.131143E+09 | 0.120105E+10 | 0.00 | 0.00 |
September | 0.850579E+10 | 87517471.68 | 0.171916E+10 | 0.447780E+09 | 0.127138E+10 | 0.00 | 0.00 |
October | 0.856177E+10 | 0.423122E+09 | 0.227245E+10 | 0.928197E+09 | 0.134426E+10 | 0.00 | 0.00 |
November | 0.723815E+10 | 0.113495E+10 | 0.237345E+10 | 0.113964E+10 | 0.123381E+10 | 0.00 | 0.00 |
December | 0.576882E+10 | 0.205936E+10 | 0.225811E+10 | 0.110176E+10 | 0.115634E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.814483E+11 | 0.112020E+11 | 0.208304E+11 | 0.640212E+10 | 0.144283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.488013E+10 | 12189.58 | 0.108000E+10 | 2832297.93 | 0.107717E+10 | 0.00 | 0.00 |
Maximum of Months | 0.940726E+10 | 0.251894E+10 | 0.237345E+10 | 0.113964E+10 | 0.134426E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.178164E+10 | 0.169742E+10 | 0.843432E+09 | 0.243649E+09 | 0.599784E+09 | 0.00 | 0.00 |
February | 0.206334E+10 | 0.127873E+10 | 0.869761E+09 | 0.249371E+09 | 0.620390E+09 | 0.00 | 0.00 |
March | 0.313824E+10 | 0.109199E+10 | 0.113731E+10 | 0.336100E+09 | 0.801209E+09 | 0.00 | 0.00 |
April | 0.403647E+10 | 0.690926E+09 | 0.120131E+10 | 0.335783E+09 | 0.865523E+09 | 0.00 | 0.00 |
May | 0.588276E+10 | 0.191776E+09 | 0.135375E+10 | 0.405127E+09 | 0.948619E+09 | 0.00 | 0.00 |
June | 0.636258E+10 | 36966127.11 | 0.135408E+10 | 0.426895E+09 | 0.927185E+09 | 0.00 | 0.00 |
July | 0.728029E+10 | 216363.08 | 0.128604E+10 | 0.369681E+09 | 0.916357E+09 | 0.00 | 0.00 |
August | 0.748087E+10 | 148366.68 | 0.131519E+10 | 0.398766E+09 | 0.916428E+09 | 0.00 | 0.00 |
September | 0.573722E+10 | 61266921.30 | 0.121095E+10 | 0.379595E+09 | 0.831359E+09 | 0.00 | 0.00 |
October | 0.446106E+10 | 0.287127E+09 | 0.111322E+10 | 0.359613E+09 | 0.753603E+09 | 0.00 | 0.00 |
November | 0.299833E+10 | 0.738491E+09 | 0.927116E+09 | 0.304086E+09 | 0.623030E+09 | 0.00 | 0.00 |
December | 0.198456E+10 | 0.134537E+10 | 0.803774E+09 | 0.244994E+09 | 0.558780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.532073E+11 | 0.742044E+10 | 0.134159E+11 | 0.405366E+10 | 0.936227E+10 | 0.00 | 0.00 |
Minimum of Months | 0.178164E+10 | 148366.68 | 0.803774E+09 | 0.243649E+09 | 0.558780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.748087E+10 | 0.169742E+10 | 0.135408E+10 | 0.426895E+09 | 0.948619E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112705E+10 | 0.305903E+10 | 0.711480E+09 | 0.00 | 0.711480E+09 | 0.00 | 0.00 |
February | 0.150939E+10 | 0.226051E+10 | 0.736635E+09 | 0.00 | 0.736635E+09 | 0.00 | 0.00 |
March | 0.257234E+10 | 0.182420E+10 | 0.936780E+09 | 0.00 | 0.936780E+09 | 0.00 | 0.00 |
April | 0.386545E+10 | 0.108028E+10 | 0.102288E+10 | 3580402.02 | 0.101930E+10 | 0.00 | 0.00 |
May | 0.638719E+10 | 0.270873E+09 | 0.120207E+10 | 48913474.95 | 0.115316E+10 | 0.00 | 0.00 |
June | 0.720860E+10 | 61747301.43 | 0.125533E+10 | 92722007.17 | 0.116261E+10 | 0.00 | 0.00 |
July | 0.856448E+10 | 858836.29 | 0.118157E+10 | 48035314.14 | 0.113353E+10 | 0.00 | 0.00 |
August | 0.842690E+10 | 172896.18 | 0.109138E+10 | 13836014.23 | 0.107754E+10 | 0.00 | 0.00 |
September | 0.594470E+10 | 0.114367E+09 | 0.957911E+09 | 218303.29 | 0.957692E+09 | 0.00 | 0.00 |
October | 0.422187E+10 | 0.530888E+09 | 0.877373E+09 | 0.00 | 0.877373E+09 | 0.00 | 0.00 |
November | 0.241712E+10 | 0.142094E+10 | 0.728909E+09 | 0.00 | 0.728909E+09 | 0.00 | 0.00 |
December | 0.131843E+10 | 0.256025E+10 | 0.664074E+09 | 0.00 | 0.664074E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.535635E+11 | 0.131841E+11 | 0.113664E+11 | 0.207306E+09 | 0.111591E+11 | 0.00 | 0.00 |
Minimum of Months | 0.112705E+10 | 172896.18 | 0.664074E+09 | 0.00 | 0.664074E+09 | 0.00 | 0.00 |
Maximum of Months | 0.856448E+10 | 0.305903E+10 | 0.125533E+10 | 92722007.17 | 0.116261E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166921E+10 | 0.189088E+10 | 0.859453E+09 | 0.260999E+09 | 0.598454E+09 | 0.00 | 0.00 |
February | 0.191463E+10 | 0.141977E+10 | 0.845740E+09 | 0.230035E+09 | 0.615705E+09 | 0.00 | 0.00 |
March | 0.286550E+10 | 0.115539E+10 | 0.103309E+10 | 0.254759E+09 | 0.778328E+09 | 0.00 | 0.00 |
April | 0.415525E+10 | 0.704187E+09 | 0.121688E+10 | 0.354449E+09 | 0.862427E+09 | 0.00 | 0.00 |
May | 0.607455E+10 | 0.177283E+09 | 0.140313E+10 | 0.445501E+09 | 0.957632E+09 | 0.00 | 0.00 |
June | 0.630806E+10 | 36989986.75 | 0.133265E+10 | 0.408011E+09 | 0.924641E+09 | 0.00 | 0.00 |
July | 0.726427E+10 | 358426.27 | 0.128745E+10 | 0.373176E+09 | 0.914274E+09 | 0.00 | 0.00 |
August | 0.746238E+10 | 71254.81 | 0.131586E+10 | 0.404147E+09 | 0.911714E+09 | 0.00 | 0.00 |
September | 0.565382E+10 | 69701180.50 | 0.119580E+10 | 0.368938E+09 | 0.826866E+09 | 0.00 | 0.00 |
October | 0.438878E+10 | 0.332025E+09 | 0.112167E+10 | 0.366124E+09 | 0.755544E+09 | 0.00 | 0.00 |
November | 0.278375E+10 | 0.898686E+09 | 0.911817E+09 | 0.290037E+09 | 0.621781E+09 | 0.00 | 0.00 |
December | 0.168483E+10 | 0.159772E+10 | 0.763473E+09 | 0.211162E+09 | 0.552311E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.522250E+11 | 0.828306E+10 | 0.132870E+11 | 0.396734E+10 | 0.931968E+10 | 0.00 | 0.00 |
Minimum of Months | 0.166921E+10 | 71254.81 | 0.763473E+09 | 0.211162E+09 | 0.552311E+09 | 0.00 | 0.00 |
Maximum of Months | 0.746238E+10 | 0.189088E+10 | 0.140313E+10 | 0.445501E+09 | 0.957632E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.525837E+10 | 0.306361E+10 | 0.228101E+10 | 0.106266E+10 | 0.121835E+10 | 0.00 | 0.00 |
February | 0.492132E+10 | 0.233128E+10 | 0.196072E+10 | 0.808187E+09 | 0.115253E+10 | 0.00 | 0.00 |
March | 0.531902E+10 | 0.191733E+10 | 0.183155E+10 | 0.536883E+09 | 0.129467E+10 | 0.00 | 0.00 |
April | 0.513200E+10 | 0.112408E+10 | 0.140275E+10 | 0.194158E+09 | 0.120859E+10 | 0.00 | 0.00 |
May | 0.636609E+10 | 0.274845E+09 | 0.119742E+10 | 32175627.44 | 0.116524E+10 | 0.00 | 0.00 |
June | 0.662157E+10 | 50099837.49 | 0.108001E+10 | 2832315.08 | 0.107717E+10 | 0.00 | 0.00 |
July | 0.829931E+10 | 239288.80 | 0.112167E+10 | 16708799.85 | 0.110496E+10 | 0.00 | 0.00 |
August | 0.917363E+10 | 188498.58 | 0.133220E+10 | 0.131144E+09 | 0.120106E+10 | 0.00 | 0.00 |
September | 0.837312E+10 | 0.125230E+09 | 0.171916E+10 | 0.447782E+09 | 0.127138E+10 | 0.00 | 0.00 |
October | 0.848314E+10 | 0.582942E+09 | 0.227246E+10 | 0.928202E+09 | 0.134426E+10 | 0.00 | 0.00 |
November | 0.719621E+10 | 0.151347E+10 | 0.237346E+10 | 0.113965E+10 | 0.123381E+10 | 0.00 | 0.00 |
December | 0.572377E+10 | 0.261352E+10 | 0.225812E+10 | 0.110177E+10 | 0.115635E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.808676E+11 | 0.135968E+11 | 0.208305E+11 | 0.640215E+10 | 0.144284E+11 | 0.00 | 0.00 |
Minimum of Months | 0.492132E+10 | 188498.58 | 0.108001E+10 | 2832315.08 | 0.107717E+10 | 0.00 | 0.00 |
Maximum of Months | 0.917363E+10 | 0.306361E+10 | 0.237346E+10 | 0.113965E+10 | 0.134426E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.176345E+10 | 0.202416E+10 | 0.843459E+09 | 0.243658E+09 | 0.599802E+09 | 0.00 | 0.00 |
February | 0.207792E+10 | 0.150051E+10 | 0.869788E+09 | 0.249380E+09 | 0.620408E+09 | 0.00 | 0.00 |
March | 0.319736E+10 | 0.124112E+10 | 0.113735E+10 | 0.336112E+09 | 0.801233E+09 | 0.00 | 0.00 |
April | 0.410966E+10 | 0.759758E+09 | 0.120134E+10 | 0.335796E+09 | 0.865548E+09 | 0.00 | 0.00 |
May | 0.592376E+10 | 0.203864E+09 | 0.135379E+10 | 0.405142E+09 | 0.948646E+09 | 0.00 | 0.00 |
June | 0.636453E+10 | 42878488.92 | 0.135412E+10 | 0.426911E+09 | 0.927211E+09 | 0.00 | 0.00 |
July | 0.723396E+10 | 321869.95 | 0.128608E+10 | 0.369695E+09 | 0.916383E+09 | 0.00 | 0.00 |
August | 0.740060E+10 | 184513.33 | 0.131523E+10 | 0.398781E+09 | 0.916453E+09 | 0.00 | 0.00 |
September | 0.568570E+10 | 82811086.35 | 0.121099E+10 | 0.379609E+09 | 0.831383E+09 | 0.00 | 0.00 |
October | 0.440173E+10 | 0.372772E+09 | 0.111325E+10 | 0.359627E+09 | 0.753624E+09 | 0.00 | 0.00 |
November | 0.292780E+10 | 0.968074E+09 | 0.927146E+09 | 0.304098E+09 | 0.623048E+09 | 0.00 | 0.00 |
December | 0.193081E+10 | 0.169214E+10 | 0.803799E+09 | 0.245003E+09 | 0.558797E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.530173E+11 | 0.888859E+10 | 0.134163E+11 | 0.405381E+10 | 0.936254E+10 | 0.00 | 0.00 |
Minimum of Months | 0.176345E+10 | 184513.33 | 0.803799E+09 | 0.243658E+09 | 0.558797E+09 | 0.00 | 0.00 |
Maximum of Months | 0.740060E+10 | 0.202416E+10 | 0.135412E+10 | 0.426911E+09 | 0.948646E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114267E+10 | 0.287354E+10 | 0.711484E+09 | 0.00 | 0.711484E+09 | 0.00 | 0.00 |
February | 0.149780E+10 | 0.216650E+10 | 0.736639E+09 | 0.00 | 0.736639E+09 | 0.00 | 0.00 |
March | 0.252421E+10 | 0.180786E+10 | 0.936786E+09 | 0.00 | 0.936786E+09 | 0.00 | 0.00 |
April | 0.382549E+10 | 0.109567E+10 | 0.102288E+10 | 3580422.73 | 0.101930E+10 | 0.00 | 0.00 |
May | 0.639351E+10 | 0.288887E+09 | 0.120208E+10 | 48913757.96 | 0.115316E+10 | 0.00 | 0.00 |
June | 0.725921E+10 | 63842094.17 | 0.125534E+10 | 92722543.66 | 0.116261E+10 | 0.00 | 0.00 |
July | 0.868676E+10 | 646346.31 | 0.118158E+10 | 48035592.07 | 0.113354E+10 | 0.00 | 0.00 |
August | 0.860641E+10 | 325870.56 | 0.109139E+10 | 13836094.29 | 0.107755E+10 | 0.00 | 0.00 |
September | 0.607192E+10 | 99166416.08 | 0.957916E+09 | 218304.56 | 0.957698E+09 | 0.00 | 0.00 |
October | 0.433473E+10 | 0.470495E+09 | 0.877378E+09 | 0.00 | 0.877378E+09 | 0.00 | 0.00 |
November | 0.250412E+10 | 0.125602E+10 | 0.728913E+09 | 0.00 | 0.728913E+09 | 0.00 | 0.00 |
December | 0.137270E+10 | 0.231582E+10 | 0.664078E+09 | 0.00 | 0.664078E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.542195E+11 | 0.124388E+11 | 0.113664E+11 | 0.207307E+09 | 0.111591E+11 | 0.00 | 0.00 |
Minimum of Months | 0.114267E+10 | 325870.56 | 0.664078E+09 | 0.00 | 0.664078E+09 | 0.00 | 0.00 |
Maximum of Months | 0.868676E+10 | 0.287354E+10 | 0.125534E+10 | 92722543.66 | 0.116261E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.169176E+10 | 0.174708E+10 | 0.859423E+09 | 0.260988E+09 | 0.598435E+09 | 0.00 | 0.00 |
February | 0.190357E+10 | 0.133653E+10 | 0.845711E+09 | 0.230025E+09 | 0.615686E+09 | 0.00 | 0.00 |
March | 0.281834E+10 | 0.112462E+10 | 0.103305E+10 | 0.254748E+09 | 0.778303E+09 | 0.00 | 0.00 |
April | 0.410101E+10 | 0.693450E+09 | 0.121684E+10 | 0.354435E+09 | 0.862401E+09 | 0.00 | 0.00 |
May | 0.605084E+10 | 0.180283E+09 | 0.140309E+10 | 0.445483E+09 | 0.957602E+09 | 0.00 | 0.00 |
June | 0.631316E+10 | 35945381.25 | 0.133261E+10 | 0.407995E+09 | 0.924613E+09 | 0.00 | 0.00 |
July | 0.731642E+10 | 285545.45 | 0.128741E+10 | 0.373161E+09 | 0.914247E+09 | 0.00 | 0.00 |
August | 0.754801E+10 | 119012.49 | 0.131582E+10 | 0.404130E+09 | 0.911686E+09 | 0.00 | 0.00 |
September | 0.570603E+10 | 56546673.17 | 0.119576E+10 | 0.368923E+09 | 0.826840E+09 | 0.00 | 0.00 |
October | 0.443627E+10 | 0.280702E+09 | 0.112163E+10 | 0.366109E+09 | 0.755521E+09 | 0.00 | 0.00 |
November | 0.282545E+10 | 0.779056E+09 | 0.911786E+09 | 0.290025E+09 | 0.621761E+09 | 0.00 | 0.00 |
December | 0.173031E+10 | 0.142777E+10 | 0.763447E+09 | 0.211154E+09 | 0.552294E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.524412E+11 | 0.766238E+10 | 0.132866E+11 | 0.396718E+10 | 0.931939E+10 | 0.00 | 0.00 |
Minimum of Months | 0.169176E+10 | 119012.49 | 0.763447E+09 | 0.211154E+09 | 0.552294E+09 | 0.00 | 0.00 |
Maximum of Months | 0.754801E+10 | 0.174708E+10 | 0.140309E+10 | 0.445483E+09 | 0.957602E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.521470E+10 | 0.280342E+10 | 0.228100E+10 | 0.106265E+10 | 0.121835E+10 | 0.00 | 0.00 |
February | 0.486068E+10 | 0.216760E+10 | 0.196071E+10 | 0.808182E+09 | 0.115253E+10 | 0.00 | 0.00 |
March | 0.525000E+10 | 0.185058E+10 | 0.183154E+10 | 0.536880E+09 | 0.129466E+10 | 0.00 | 0.00 |
April | 0.508451E+10 | 0.112001E+10 | 0.140274E+10 | 0.194157E+09 | 0.120858E+10 | 0.00 | 0.00 |
May | 0.640417E+10 | 0.289358E+09 | 0.119742E+10 | 32175432.60 | 0.116524E+10 | 0.00 | 0.00 |
June | 0.672867E+10 | 50632806.04 | 0.108000E+10 | 2832297.93 | 0.107717E+10 | 0.00 | 0.00 |
July | 0.847863E+10 | 217711.89 | 0.112166E+10 | 16708698.66 | 0.110496E+10 | 0.00 | 0.00 |
August | 0.943254E+10 | 166673.88 | 0.133220E+10 | 0.131143E+09 | 0.120105E+10 | 0.00 | 0.00 |
September | 0.853818E+10 | 97396747.27 | 0.171916E+10 | 0.447780E+09 | 0.127138E+10 | 0.00 | 0.00 |
October | 0.858498E+10 | 0.471224E+09 | 0.227245E+10 | 0.928197E+09 | 0.134426E+10 | 0.00 | 0.00 |
November | 0.722834E+10 | 0.127694E+10 | 0.237345E+10 | 0.113964E+10 | 0.123381E+10 | 0.00 | 0.00 |
December | 0.571894E+10 | 0.231029E+10 | 0.225811E+10 | 0.110176E+10 | 0.115634E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.815243E+11 | 0.124379E+11 | 0.208304E+11 | 0.640212E+10 | 0.144283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.486068E+10 | 166673.88 | 0.108000E+10 | 2832297.93 | 0.107717E+10 | 0.00 | 0.00 |
Maximum of Months | 0.943254E+10 | 0.280342E+10 | 0.237345E+10 | 0.113964E+10 | 0.134426E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.175488E+10 | 0.188516E+10 | 0.843432E+09 | 0.243649E+09 | 0.599784E+09 | 0.00 | 0.00 |
February | 0.205151E+10 | 0.141826E+10 | 0.869761E+09 | 0.249371E+09 | 0.620390E+09 | 0.00 | 0.00 |
March | 0.314105E+10 | 0.120414E+10 | 0.113731E+10 | 0.336100E+09 | 0.801209E+09 | 0.00 | 0.00 |
April | 0.405835E+10 | 0.748134E+09 | 0.120131E+10 | 0.335783E+09 | 0.865523E+09 | 0.00 | 0.00 |
May | 0.591532E+10 | 0.206385E+09 | 0.135375E+10 | 0.405127E+09 | 0.948619E+09 | 0.00 | 0.00 |
June | 0.639352E+10 | 40141048.86 | 0.135408E+10 | 0.426895E+09 | 0.927185E+09 | 0.00 | 0.00 |
July | 0.730961E+10 | 172180.53 | 0.128604E+10 | 0.369681E+09 | 0.916357E+09 | 0.00 | 0.00 |
August | 0.750649E+10 | 310833.22 | 0.131519E+10 | 0.398766E+09 | 0.916428E+09 | 0.00 | 0.00 |
September | 0.575582E+10 | 67543569.06 | 0.121095E+10 | 0.379595E+09 | 0.831359E+09 | 0.00 | 0.00 |
October | 0.446538E+10 | 0.318924E+09 | 0.111322E+10 | 0.359613E+09 | 0.753603E+09 | 0.00 | 0.00 |
November | 0.297903E+10 | 0.836926E+09 | 0.927116E+09 | 0.304086E+09 | 0.623030E+09 | 0.00 | 0.00 |
December | 0.195454E+10 | 0.151576E+10 | 0.803774E+09 | 0.244994E+09 | 0.558780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.532855E+11 | 0.824186E+10 | 0.134159E+11 | 0.405366E+10 | 0.936227E+10 | 0.00 | 0.00 |
Minimum of Months | 0.175488E+10 | 172180.53 | 0.803774E+09 | 0.243649E+09 | 0.558780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.750649E+10 | 0.188516E+10 | 0.135408E+10 | 0.426895E+09 | 0.948619E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.354693E+10 | -0.331502E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231914041.8 | 60.05 | 0.00 | 0.00 |
February | 0.314035E+10 | -0.293107E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -209278591.6 | 60.05 | 0.00 | 0.00 |
March | 0.346316E+10 | -0.323128E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231882463.1 | 60.05 | 0.00 | 0.00 |
April | 0.284635E+10 | -0.262248E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223863790.5 | 60.05 | 0.00 | 0.00 |
May | 0.274851E+10 | -0.251643E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232079533.5 | 60.05 | 0.00 | 0.00 |
June | 0.250783E+10 | -0.228242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225410566.0 | 60.05 | 0.00 | 0.00 |
July | 0.232060E+10 | -0.208655E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234043650.7 | 60.05 | 0.00 | 0.00 |
August | 0.264359E+10 | -0.240878E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234807103.7 | 60.05 | 0.00 | 0.00 |
September | 0.261698E+10 | -0.239148E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225495441.7 | 60.05 | 0.00 | 0.00 |
October | 0.299662E+10 | -0.276466E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231957507.8 | 60.05 | 0.00 | 0.00 |
November | 0.322352E+10 | -0.299995E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223569921.2 | 60.05 | 0.00 | 0.00 |
December | 0.339605E+10 | -0.316457E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231482633.6 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.354505E+11 | -0.327147E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273579E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.232060E+10 | -0.331502E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -234807103.7 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.354693E+10 | -0.208655E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -209278591.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134255E+09 | 8128.26 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61884600.55 | 3712.62 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8544139.66 | 2131.52 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4956546.72 | 1701.49 | 18-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134255E+09 | 8128.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 328838.31 | 1532.98 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 328838.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 328838.31 | 1532.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1018933.12 | 2264.56 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5204.43 | 34.70 | 18-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1024137.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1018933.12 | 2264.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 419595.55 | 1766.89 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419595.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 419595.55 | 1766.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1594973.71 | 2466.19 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 117242.55 | 781.62 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70177.57 | 359.10 | 18-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1782393.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1594973.71 | 2466.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 95366271.82 | 9679.79 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42329363.29 | 7815.97 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5720893.57 | 6419.53 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25226437.39 | 7995.06 | 30-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95366271.82 | 9679.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 57955833.30 | 6092.84 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21878129.13 | 4856.59 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4337712.08 | 4248.19 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17531444.23 | 5191.65 | 18-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57955833.30 | 6092.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135641E+09 | 9953.01 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50420220.65 | 8287.04 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5163108.60 | 6206.68 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44088577.01 | 8164.19 | 18-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135641E+09 | 9953.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142331E+09 | 6657.73 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57216607.26 | 5939.13 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9778757.76 | 3995.93 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 220620.10 | 1470.80 | 22-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52340475.41 | 5810.09 | 18-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142331E+09 | 6657.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.533644E+11 | 0.471237E+11 | 74096.11 | 30-JAN-06:12 | 65143.68 | 0.00 |
February | 0.00 | 0.00 | 0.554491E+11 | 0.481108E+11 | 113206.90 | 09-FEB-06:12 | 75343.52 | 0.00 |
March | 0.00 | 0.00 | 0.728245E+11 | 0.653346E+11 | 108240.03 | 29-MAR-05:12 | 73682.09 | 0.00 |
April | 0.00 | 0.00 | 0.848145E+11 | 0.744151E+11 | 116305.91 | 12-APR-05:12 | 75124.44 | 0.00 |
May | 0.00 | 0.00 | 0.124637E+12 | 0.106022E+12 | 177421.00 | 24-MAY-04:01 | 99459.84 | 0.00 |
June | 0.00 | 0.00 | 0.149739E+12 | 0.114119E+12 | 177529.50 | 08-JUN-04:01 | 103105.72 | 0.00 |
July | 0.00 | 0.00 | 0.178093E+12 | 0.126530E+12 | 175478.95 | 06-JUL-04:01 | 108638.74 | 0.00 |
August | 0.00 | 0.00 | 0.196360E+12 | 0.137434E+12 | 173531.14 | 26-AUG-04:01 | 104195.36 | 0.00 |
September | 0.00 | 0.00 | 0.158378E+12 | 0.113671E+12 | 176971.68 | 23-SEP-04:01 | 104180.29 | 0.00 |
October | 0.00 | 0.00 | 0.128883E+12 | 0.101365E+12 | 176560.56 | 07-OCT-04:01 | 106779.17 | 0.00 |
November | 0.00 | 0.00 | 0.936053E+11 | 0.781208E+11 | 155755.08 | 03-NOV-04:02 | 92468.55 | 0.00 |
December | 0.00 | 0.00 | 0.643566E+11 | 0.550056E+11 | 110344.44 | 11-DEC-06:12 | 75260.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136051E+13 | 0.106725E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.533644E+11 | 0.471237E+11 | 74096.11 | 65143.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.196360E+12 | 0.137434E+12 | 177529.50 | 108638.74 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.419616E+11 | 0.347089E+11 | 48882.89 | 30-JAN-14:30 | 35545.43 | 0.00 |
February | 0.00 | 0.00 | 0.455293E+11 | 0.374694E+11 | 73572.13 | 07-FEB-15:05 | 57816.34 | 0.00 |
March | 0.00 | 0.00 | 0.615126E+11 | 0.534373E+11 | 90487.36 | 02-MAR-06:02 | 90487.36 | 0.00 |
April | 0.00 | 0.00 | 0.739490E+11 | 0.635465E+11 | 103926.32 | 18-APR-04:01 | 74206.45 | 0.00 |
May | 0.00 | 0.00 | 0.108944E+12 | 0.924900E+11 | 168450.51 | 24-MAY-04:01 | 89025.02 | 0.00 |
June | 0.00 | 0.00 | 0.131814E+12 | 0.992599E+11 | 169820.66 | 20-JUN-04:01 | 92767.29 | 0.00 |
July | 0.00 | 0.00 | 0.157573E+12 | 0.110613E+12 | 167945.03 | 06-JUL-04:01 | 95686.13 | 0.00 |
August | 0.00 | 0.00 | 0.169285E+12 | 0.117490E+12 | 166357.06 | 09-AUG-04:01 | 97177.18 | 0.00 |
September | 0.00 | 0.00 | 0.132577E+12 | 0.941153E+11 | 167796.17 | 28-SEP-04:01 | 94873.02 | 0.00 |
October | 0.00 | 0.00 | 0.104338E+12 | 0.813984E+11 | 166984.99 | 02-OCT-04:01 | 99617.12 | 0.00 |
November | 0.00 | 0.00 | 0.746010E+11 | 0.605309E+11 | 122164.56 | 03-NOV-04:02 | 68784.03 | 0.00 |
December | 0.00 | 0.00 | 0.515061E+11 | 0.414276E+11 | 68391.45 | 05-DEC-15:10 | 48915.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115359E+13 | 0.886487E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.419616E+11 | 0.347089E+11 | 48882.89 | 35545.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169285E+12 | 0.117490E+12 | 169820.66 | 99617.12 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.456510E+11 | 0.371793E+11 | 53224.00 | 30-JAN-14:30 | 38567.54 | 0.00 |
February | 0.00 | 0.00 | 0.504073E+11 | 0.412928E+11 | 82045.53 | 07-FEB-15:20 | 66102.09 | 0.00 |
March | 0.00 | 0.00 | 0.688646E+11 | 0.597096E+11 | 92771.13 | 27-MAR-13:40 | 92771.13 | 0.00 |
April | 0.00 | 0.00 | 0.837846E+11 | 0.724640E+11 | 113901.55 | 17-APR-05:01 | 86507.19 | 0.00 |
May | 0.00 | 0.00 | 0.124198E+12 | 0.106928E+12 | 197873.74 | 29-MAY-12:52 | 132488.47 | 0.00 |
June | 0.00 | 0.00 | 0.148011E+12 | 0.115053E+12 | 203592.10 | 20-JUN-04:01 | 106025.80 | 0.00 |
July | 0.00 | 0.00 | 0.176462E+12 | 0.129151E+12 | 200296.14 | 06-JUL-04:01 | 115508.30 | 0.00 |
August | 0.00 | 0.00 | 0.187965E+12 | 0.135949E+12 | 197109.06 | 26-AUG-04:01 | 119609.33 | 0.00 |
September | 0.00 | 0.00 | 0.145484E+12 | 0.106835E+12 | 201065.68 | 28-SEP-04:01 | 109774.29 | 0.00 |
October | 0.00 | 0.00 | 0.113404E+12 | 0.897998E+11 | 198203.74 | 02-OCT-04:01 | 111958.85 | 0.00 |
November | 0.00 | 0.00 | 0.799153E+11 | 0.648288E+11 | 138831.66 | 03-NOV-05:02 | 76301.90 | 0.00 |
December | 0.00 | 0.00 | 0.553012E+11 | 0.439197E+11 | 74769.10 | 05-DEC-15:00 | 55022.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127945E+13 | 0.100311E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.456510E+11 | 0.371793E+11 | 53224.00 | 38567.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.187965E+12 | 0.135949E+12 | 203592.10 | 132488.47 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1228.96 | 4483.27 | 12-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1202.89 | 4436.51 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1197.58 | 4225.50 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1003.36 | 3823.22 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 931.13 | 3441.37 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 872.20 | 3086.27 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 771.01 | 2915.82 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 890.93 | 3142.35 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 914.36 | 3491.81 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1023.76 | 3927.50 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1148.72 | 4272.10 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1172.94 | 4459.61 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1028.89 | ||||
Minimum of Months | 0.00 | 0.00 | 771.01 | 2915.82 | ||
Maximum of Months | 0.00 | 0.00 | 1228.96 | 4483.27 |
Report: FanReportMonthly
For: CORE_BOTTOM PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 54498686.72 | 0.01 | 940.44 | 02-JAN-07:03 | 0.60 |
February | 38746262.17 | 0.01 | 940.44 | 01-FEB-07:03 | 0.60 |
March | 33573824.26 | 0.01 | 940.44 | 03-MAR-07:07 | 0.60 |
April | 3009418.42 | 0.00 | 940.44 | 05-APR-06:10 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 141066.49 | 0.00 | 940.44 | 22-NOV-07:10 | 0.60 |
December | 32680403.17 | 0.01 | 940.44 | 08-DEC-07:08 | 0.60 |
Annual Sum or Average | 0.162650E+09 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54498686.72 | 0.01 | 940.44 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 212643.69 | 0.00 | 708.81 | 20-JAN-07:03 | 0.61 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 212643.69 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 212643.69 | 0.00 | 708.81 | 0.61 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PERIMETER_BOT_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 2147489.14 | 0.00 | 766.96 | 19-JAN-07:03 | 0.61 |
February | 115044.06 | 0.00 | 766.96 | 13-FEB-07:05 | 0.60 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 2262533.20 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2147489.14 | 0.00 | 766.96 | 0.61 |
Report: FanReportMonthly
For: CORE_MID PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 6986433.25 | 0.00 | 944.11 | 02-JAN-07:03 | 0.60 |
February | 566467.56 | 0.00 | 944.11 | 01-FEB-07:03 | 0.60 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 283233.78 | 0.00 | 944.11 | 18-DEC-07:03 | 0.60 |
Annual Sum or Average | 7836134.60 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6986433.25 | 0.00 | 944.11 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 9362751.44 | 0.00 | 720.21 | 02-JAN-07:03 | 0.60 |
February | 2700793.68 | 0.00 | 720.21 | 01-FEB-07:03 | 0.60 |
March | 612179.90 | 0.00 | 720.21 | 04-MAR-07:23 | 0.60 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 1584465.63 | 0.00 | 720.21 | 16-DEC-07:03 | 0.60 |
Annual Sum or Average | 14260190.65 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9362751.44 | 0.00 | 720.21 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 13579265.24 | 0.00 | 835.65 | 02-JAN-07:03 | 0.60 |
February | 1545947.12 | 0.00 | 835.65 | 13-FEB-07:03 | 0.60 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 1504164.77 | 0.00 | 835.65 | 18-DEC-07:03 | 0.60 |
Annual Sum or Average | 16629377.13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13579265.24 | 0.00 | 835.65 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_MID_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 42794116.77 | 0.01 | 791.02 | 02-JAN-07:03 | 0.60 |
February | 14673398.63 | 0.00 | 791.02 | 01-FEB-07:03 | 0.60 |
March | 2135750.74 | 0.00 | 791.02 | 04-MAR-07:03 | 0.60 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 13130911.99 | 0.00 | 791.02 | 14-DEC-07:03 | 0.60 |
Annual Sum or Average | 72734178.14 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42794116.77 | 0.01 | 791.02 | 0.60 |
Report: FanReportMonthly
For: CORE_TOP PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_1 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122289E+09 | 0.03 | 1097.25 | 02-JAN-06:20 | 0.60 |
February | 64463555.33 | 0.01 | 1097.25 | 01-FEB-06:50 | 0.60 |
March | 37580881.19 | 0.01 | 1097.25 | 04-MAR-07:03 | 0.60 |
April | 3620931.62 | 0.00 | 1097.25 | 01-APR-06:15 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 164587.80 | 0.00 | 1097.25 | 22-NOV-07:03 | 0.60 |
December | 59855096.90 | 0.01 | 1097.25 | 02-DEC-07:05 | 0.60 |
Annual Sum or Average | 0.287974E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122289E+09 | 0.03 | 1097.25 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_2 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126671E+09 | 0.04 | 766.54 | 02-JAN-06:15 | 0.60 |
February | 54232874.59 | 0.02 | 766.54 | 01-FEB-06:20 | 0.60 |
March | 25334226.22 | 0.01 | 766.54 | 04-MAR-07:03 | 0.60 |
April | 3219478.07 | 0.00 | 766.54 | 01-APR-06:05 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 114981.36 | 0.00 | 766.54 | 22-NOV-07:03 | 0.60 |
December | 58027259.46 | 0.02 | 766.54 | 01-DEC-07:03 | 0.60 |
Annual Sum or Average | 0.267600E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126671E+09 | 0.04 | 766.54 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_3 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159663E+09 | 0.04 | 994.47 | 02-JAN-06:17 | 0.60 |
February | 68966802.42 | 0.02 | 994.47 | 01-FEB-06:50 | 0.60 |
March | 30182299.26 | 0.01 | 994.47 | 04-MAR-07:03 | 0.60 |
April | 596684.66 | 0.00 | 994.47 | 01-APR-06:40 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 1044198.16 | 0.00 | 994.47 | 22-NOV-07:03 | 0.60 |
December | 71850778.30 | 0.02 | 994.47 | 01-DEC-07:03 | 0.60 |
Annual Sum or Average | 0.332304E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159663E+09 | 0.04 | 994.47 | 0.60 |
Report: FanReportMonthly
For: PERIMETER_TOP_ZN_4 PIU FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.268057E+09 | 0.07 | 891.44 | 02-JAN-06:15 | 0.60 |
February | 0.133360E+09 | 0.04 | 891.44 | 01-FEB-06:17 | 0.60 |
March | 61420490.23 | 0.02 | 891.44 | 03-MAR-07:03 | 0.60 |
April | 10608183.36 | 0.00 | 891.44 | 01-APR-06:05 | 0.60 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 7800134.83 | 0.00 | 891.44 | 22-NOV-07:03 | 0.60 |
December | 0.145528E+09 | 0.04 | 891.44 | 01-DEC-07:03 | 0.60 |
Annual Sum or Average | 0.626774E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.268057E+09 | 0.07 | 891.44 | 0.60 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.533320E+10 | 0.52 | 7489.65 | 02-JAN-06:12 | 1.30 |
February | 0.523588E+10 | 0.54 | 8756.93 | 06-FEB-15:10 | 1.38 |
March | 0.687001E+10 | 0.60 | 10790.34 | 27-MAR-14:50 | 1.51 |
April | 0.741667E+10 | 0.62 | 10798.91 | 28-APR-11:00 | 1.52 |
May | 0.102322E+11 | 0.75 | 15915.62 | 23-MAY-04:01 | 1.79 |
June | 0.109826E+11 | 0.80 | 15915.62 | 10-JUN-04:01 | 1.78 |
July | 0.115355E+11 | 0.84 | 15915.62 | 01-JUL-04:01 | 1.78 |
August | 0.126489E+11 | 0.89 | 15915.62 | 01-AUG-04:01 | 1.78 |
September | 0.105919E+11 | 0.80 | 15915.62 | 06-SEP-04:01 | 1.78 |
October | 0.979695E+10 | 0.73 | 15915.62 | 02-OCT-04:01 | 1.78 |
November | 0.814649E+10 | 0.65 | 10514.35 | 02-NOV-15:00 | 1.49 |
December | 0.598442E+10 | 0.54 | 8188.27 | 04-DEC-13:10 | 1.34 |
Annual Sum or Average | 0.104775E+12 | 0.69 | |||
Minimum of Months | 0.523588E+10 | 0.52 | 7489.65 | 1.30 | |
Maximum of Months | 0.126489E+11 | 0.89 | 15915.62 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.390040E+10 | 0.47 | 4493.02 | 23-JAN-13:30 | 1.08 |
February | 0.396476E+10 | 0.49 | 7419.93 | 06-FEB-15:05 | 1.33 |
March | 0.541818E+10 | 0.56 | 10943.35 | 02-MAR-06:02 | 1.58 |
April | 0.605650E+10 | 0.59 | 9686.22 | 28-APR-12:04 | 1.50 |
May | 0.869527E+10 | 0.71 | 14698.27 | 11-MAY-04:01 | 1.79 |
June | 0.928147E+10 | 0.76 | 14698.27 | 05-JUN-04:01 | 1.78 |
July | 0.973191E+10 | 0.80 | 14698.27 | 01-JUL-04:01 | 1.78 |
August | 0.106801E+11 | 0.84 | 14698.27 | 09-AUG-04:01 | 1.78 |
September | 0.879554E+10 | 0.73 | 14698.27 | 01-SEP-04:01 | 1.78 |
October | 0.781551E+10 | 0.66 | 14698.27 | 02-OCT-04:01 | 1.78 |
November | 0.596584E+10 | 0.58 | 9021.46 | 06-NOV-13:03 | 1.45 |
December | 0.432886E+10 | 0.49 | 6095.84 | 04-DEC-13:10 | 1.22 |
Annual Sum or Average | 0.846344E+11 | 0.64 | |||
Minimum of Months | 0.390040E+10 | 0.47 | 4493.02 | 1.08 | |
Maximum of Months | 0.106801E+11 | 0.84 | 14698.27 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.384417E+10 | 0.43 | 4126.61 | 23-JAN-14:00 | 0.96 |
February | 0.392433E+10 | 0.45 | 7078.83 | 06-FEB-14:50 | 1.19 |
March | 0.536641E+10 | 0.51 | 10680.40 | 02-MAR-06:02 | 1.42 |
April | 0.610953E+10 | 0.54 | 10781.76 | 29-APR-05:01 | 1.43 |
May | 0.895324E+10 | 0.66 | 18242.35 | 30-MAY-04:01 | 1.78 |
June | 0.963604E+10 | 0.71 | 18286.04 | 10-JUN-04:01 | 1.78 |
July | 0.102670E+11 | 0.75 | 18286.04 | 06-JUL-04:01 | 1.78 |
August | 0.111280E+11 | 0.78 | 18286.04 | 11-AUG-04:01 | 1.78 |
September | 0.890034E+10 | 0.67 | 18286.04 | 08-SEP-04:01 | 1.78 |
October | 0.761067E+10 | 0.59 | 14811.03 | 02-OCT-04:01 | 1.63 |
November | 0.560862E+10 | 0.51 | 8689.91 | 20-NOV-06:02 | 1.30 |
December | 0.416430E+10 | 0.44 | 5556.25 | 01-DEC-14:30 | 1.08 |
Annual Sum or Average | 0.855127E+11 | 0.59 | |||
Minimum of Months | 0.384417E+10 | 0.43 | 4126.61 | 0.96 | |
Maximum of Months | 0.111280E+11 | 0.78 | 18286.04 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.65 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:02 | 2.06 | 2.06 | 57.91 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:02 | 2.06 | 2.06 | 58.02 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 58.18 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:02 | 2.06 | 2.06 | 58.56 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:02 | 2.06 | 2.06 | 58.58 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:01 | 2.06 | 2.06 | 58.71 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.61 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 58.52 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.87 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:02 | 2.06 | 2.06 | 58.20 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:02 | 2.06 | 2.06 | 58.01 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.91 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.87 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.65 | 58.65 | 1228.96 | 4483.27 | 12-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.31 | 58.31 | 1202.89 | 4436.51 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.40 | 58.40 | 1197.58 | 4225.50 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.55 | 58.55 | 1003.36 | 3823.22 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.97 | 58.97 | 931.13 | 3441.37 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 58.83 | 58.83 | 872.20 | 3086.27 | 01-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.93 | 58.93 | 771.01 | 2915.82 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 58.89 | 58.89 | 890.93 | 3142.35 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 58.83 | 58.83 | 914.36 | 3491.81 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.13 | 58.13 | 1023.76 | 3927.50 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.51 | 58.51 | 1148.72 | 4272.10 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.39 | 58.39 | 1172.94 | 4459.61 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1028.89 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 771.01 | 2915.82 | ||
Maximum of Months | 0.00 | 0.00 | 58.97 | 58.97 | 1228.96 | 4483.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.182808E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.186272E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.248918E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.294278E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.454231E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.535962E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.632881E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.699507E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.544405E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.437848E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.313742E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.212855E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.474371E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.182808E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.699507E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.142479E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.151076E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.208091E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.253498E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.393706E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.465359E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.551807E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.597249E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.453183E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.353384E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.246099E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168107E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.398404E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.142479E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.597249E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.162523E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.168618E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.229403E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.281943E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.441662E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.517197E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.613833E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.658150E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.492032E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.378042E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.258241E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.182174E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.438382E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162523E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.658150E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.539005E+10 | 0.533644E+11 | 0.134255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.527474E+10 | 0.554491E+11 | 61884600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.690358E+10 | 0.728245E+11 | 8544139.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.741968E+10 | 0.848145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102322E+11 | 0.124637E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109826E+11 | 0.149739E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115355E+11 | 0.178093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126489E+11 | 0.196360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105919E+11 | 0.158378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.979695E+10 | 0.128883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.814663E+10 | 0.936053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601710E+10 | 0.643566E+11 | 4956546.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104940E+12 | 0.136051E+13 | 0.209640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.527474E+10 | 0.533644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126489E+11 | 0.196360E+12 | 0.134255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.397312E+10 | 0.419616E+11 | 3362340.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398425E+10 | 0.455293E+11 | 117242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.542092E+10 | 0.615126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605650E+10 | 0.739490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.869527E+10 | 0.108944E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.928147E+10 | 0.131814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.973191E+10 | 0.157573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106801E+11 | 0.169285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.879554E+10 | 0.132577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.781551E+10 | 0.104338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.596584E+10 | 0.746010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434537E+10 | 0.515061E+11 | 75382.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.847458E+11 | 0.115359E+13 | 3554965.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.397312E+10 | 0.419616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106801E+11 | 0.169285E+12 | 3362340.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.452085E+10 | 0.456510E+11 | 0.431294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424536E+10 | 0.504073E+11 | 0.171844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552093E+10 | 0.688646E+11 | 25000472.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.612757E+10 | 0.837846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.895324E+10 | 0.124198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.963604E+10 | 0.148011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102670E+11 | 0.176462E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111280E+11 | 0.187965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.890034E+10 | 0.145484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.761067E+10 | 0.113404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.561775E+10 | 0.799153E+11 | 220620.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.449956E+10 | 0.553012E+11 | 0.139187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870274E+11 | 0.127945E+13 | 0.767547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.424536E+10 | 0.456510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111280E+11 | 0.187965E+12 | 0.431294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.539005E+10 | 0.00 | 0.00 | 0.00 | 0.127565E+11 | 0.134255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.527474E+10 | 0.00 | 0.00 | 0.00 | 0.132906E+11 | 61884600.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.690358E+10 | 0.00 | 0.00 | 0.00 | 0.179797E+11 | 8544139.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.741968E+10 | 0.00 | 0.00 | 0.00 | 0.220081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102322E+11 | 0.00 | 0.00 | 0.00 | 0.351909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109826E+11 | 0.00 | 0.00 | 0.00 | 0.426136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115355E+11 | 0.00 | 0.00 | 0.00 | 0.517526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126489E+11 | 0.00 | 0.00 | 0.00 | 0.573017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105919E+11 | 0.00 | 0.00 | 0.00 | 0.438486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.979695E+10 | 0.00 | 0.00 | 0.00 | 0.339878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.814663E+10 | 0.00 | 0.00 | 0.00 | 0.232276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.601710E+10 | 0.00 | 0.00 | 0.00 | 0.152634E+11 | 4956546.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104940E+12 | 0.00 | 0.00 | 0.00 | 0.369221E+12 | 0.209640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.527474E+10 | 0.00 | 0.00 | 0.00 | 0.127565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126489E+11 | 0.00 | 0.00 | 0.00 | 0.573017E+11 | 0.134255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.397312E+10 | 0.00 | 0.00 | 0.00 | 0.102714E+11 | 3362340.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398425E+10 | 0.00 | 0.00 | 0.00 | 0.111233E+11 | 117242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.542092E+10 | 0.00 | 0.00 | 0.00 | 0.153882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605650E+10 | 0.00 | 0.00 | 0.00 | 0.192933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.869527E+10 | 0.00 | 0.00 | 0.00 | 0.306754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.928147E+10 | 0.00 | 0.00 | 0.00 | 0.372544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.973191E+10 | 0.00 | 0.00 | 0.00 | 0.454488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106801E+11 | 0.00 | 0.00 | 0.00 | 0.490447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.879554E+10 | 0.00 | 0.00 | 0.00 | 0.365227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.781551E+10 | 0.00 | 0.00 | 0.00 | 0.275229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.596584E+10 | 0.00 | 0.00 | 0.00 | 0.186441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434537E+10 | 0.00 | 0.00 | 0.00 | 0.124653E+11 | 75382.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.847458E+11 | 0.00 | 0.00 | 0.00 | 0.313655E+12 | 3554965.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.397312E+10 | 0.00 | 0.00 | 0.00 | 0.102714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106801E+11 | 0.00 | 0.00 | 0.00 | 0.490447E+11 | 3362340.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.452085E+10 | 0.00 | 0.00 | 0.00 | 0.113001E+11 | 0.431294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424536E+10 | 0.00 | 0.00 | 0.00 | 0.124446E+11 | 0.171844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552093E+10 | 0.00 | 0.00 | 0.00 | 0.173943E+11 | 25000472.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.612757E+10 | 0.00 | 0.00 | 0.00 | 0.220668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.895324E+10 | 0.00 | 0.00 | 0.00 | 0.352130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.963604E+10 | 0.00 | 0.00 | 0.00 | 0.420837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102670E+11 | 0.00 | 0.00 | 0.00 | 0.511162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111280E+11 | 0.00 | 0.00 | 0.00 | 0.546870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.890034E+10 | 0.00 | 0.00 | 0.00 | 0.403029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.761067E+10 | 0.00 | 0.00 | 0.00 | 0.301936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.561775E+10 | 0.00 | 0.00 | 0.00 | 0.202061E+11 | 220620.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.449956E+10 | 0.00 | 0.00 | 0.00 | 0.135787E+11 | 0.139187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870274E+11 | 0.00 | 0.00 | 0.00 | 0.350587E+12 | 0.767547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.424536E+10 | 0.00 | 0.00 | 0.00 | 0.113001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111280E+11 | 0.00 | 0.00 | 0.00 | 0.546870E+11 | 0.431294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172657E+09 | 0.414768E+09 | 0.00 | 35510117.61 | 0.102925E+09 | 0.00 | 0.227358E+10 | 0.00 | 0.30 |
February | 94321827.41 | 0.106445E+10 | 0.00 | 23779609.48 | 0.110889E+09 | 0.00 | 0.114082E+10 | 0.00 | 0.30 |
March | 89458570.53 | 0.201103E+10 | 0.00 | 22468827.41 | 0.137231E+09 | 0.00 | 0.991289E+09 | 0.00 | 0.32 |
April | 43822618.78 | 0.417986E+10 | 0.00 | 8737450.36 | 0.786486E+09 | 0.00 | 0.303115E+09 | 0.00 | 0.31 |
May | 24491982.99 | 0.847736E+10 | 0.00 | 2507947.87 | 0.215174E+10 | 0.00 | 45480940.57 | 0.00 | 0.32 |
June | 2801755.34 | 0.133509E+11 | 0.00 | 321512.92 | 0.414636E+10 | 0.00 | 2711706.43 | 0.00 | 0.33 |
July | 6397640.74 | 0.167051E+11 | 0.00 | 296367.15 | 0.804332E+10 | 0.00 | 2449042.49 | 0.00 | 0.34 |
August | 0.00 | 0.191003E+11 | 0.00 | 0.00 | 0.791888E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.147357E+11 | 0.00 | 0.00 | 0.546026E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 34330578.29 | 0.937820E+10 | 0.00 | 1692889.55 | 0.301417E+10 | 0.00 | 47416833.35 | 0.00 | 0.32 |
November | 18684947.70 | 0.509604E+10 | 0.00 | 4361881.60 | 0.588778E+09 | 0.00 | 82645331.90 | 0.00 | 0.30 |
December | 71626383.93 | 0.153983E+10 | 0.00 | 25622774.80 | 0.268755E+09 | 0.00 | 0.106385E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.558594E+09 | 0.960536E+11 | 0.00 | 0.125299E+09 | 0.327298E+11 | 0.00 | 0.595335E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.414768E+09 | 0.00 | 0.00 | 0.102925E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.172657E+09 | 0.191003E+11 | 0.00 | 35510117.61 | 0.804332E+10 | 0.00 | 0.227358E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.689344E+09 | 0.417781E+09 | 0.00 | 12279441.19 | 0.244616E+09 | 0.00 | 0.896991E+09 | 0.00 | 0.25 |
February | 0.349921E+09 | 0.982257E+09 | 0.00 | 8225166.32 | 0.284393E+09 | 0.00 | 0.452279E+09 | 0.00 | 0.25 |
March | 0.247378E+09 | 0.184571E+10 | 0.00 | 9359975.15 | 0.230018E+09 | 0.00 | 0.483412E+09 | 0.00 | 0.27 |
April | 0.114477E+09 | 0.369806E+10 | 0.00 | 4220197.39 | 0.813710E+09 | 0.00 | 0.166558E+09 | 0.00 | 0.27 |
May | 36532896.24 | 0.741181E+10 | 0.00 | 1576285.49 | 0.196344E+10 | 0.00 | 42257209.79 | 0.00 | 0.29 |
June | 5795356.23 | 0.119300E+11 | 0.00 | 309138.48 | 0.374243E+10 | 0.00 | 3484010.34 | 0.00 | 0.30 |
July | 7610273.65 | 0.152473E+11 | 0.00 | 183057.91 | 0.733999E+10 | 0.00 | 3520886.38 | 0.00 | 0.32 |
August | 0.00 | 0.176441E+11 | 0.00 | 0.00 | 0.688480E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 285483.79 | 0.135466E+11 | 0.00 | 76328.71 | 0.400822E+10 | 0.00 | 569761.62 | 0.00 | 0.29 |
October | 30266641.49 | 0.840330E+10 | 0.00 | 1051380.35 | 0.209290E+10 | 0.00 | 24727819.54 | 0.00 | 0.27 |
November | 28884944.65 | 0.471836E+10 | 0.00 | 2056409.60 | 0.531500E+09 | 0.00 | 41188867.16 | 0.00 | 0.26 |
December | 0.304887E+09 | 0.137434E+10 | 0.00 | 8251778.54 | 0.507952E+09 | 0.00 | 0.357368E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.181538E+10 | 0.872197E+11 | 0.00 | 47589159.13 | 0.286440E+11 | 0.00 | 0.247236E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.417781E+09 | 0.00 | 0.00 | 0.230018E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.689344E+09 | 0.176441E+11 | 0.00 | 12279441.19 | 0.733999E+10 | 0.00 | 0.896991E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.654939E+09 | 0.353670E+09 | 0.00 | 7677787.31 | 0.484207E+09 | 0.00 | 0.541997E+09 | 0.00 | 0.24 |
February | 0.273037E+09 | 0.770704E+09 | 0.00 | 6947952.86 | 0.669264E+09 | 0.00 | 0.345124E+09 | 0.00 | 0.25 |
March | 0.224090E+09 | 0.170876E+10 | 0.00 | 6985652.37 | 0.455285E+09 | 0.00 | 0.325717E+09 | 0.00 | 0.27 |
April | 0.101097E+09 | 0.357682E+10 | 0.00 | 2382133.11 | 0.870668E+09 | 0.00 | 58879110.51 | 0.00 | 0.27 |
May | 31129872.65 | 0.727782E+10 | 0.00 | 1083902.89 | 0.204188E+10 | 0.00 | 11449252.17 | 0.00 | 0.29 |
June | 4142045.36 | 0.115728E+11 | 0.00 | 353961.63 | 0.398660E+10 | 0.00 | 1935450.35 | 0.00 | 0.31 |
July | 4205540.33 | 0.149165E+11 | 0.00 | 112646.08 | 0.773546E+10 | 0.00 | 754779.21 | 0.00 | 0.33 |
August | 0.00 | 0.172532E+11 | 0.00 | 0.00 | 0.737269E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 9854.36 | 0.131240E+11 | 0.00 | 13841.63 | 0.427559E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 35171372.07 | 0.816744E+10 | 0.00 | 615394.79 | 0.221547E+10 | 0.00 | 7218864.77 | 0.00 | 0.27 |
November | 10179017.76 | 0.445077E+10 | 0.00 | 1480742.93 | 0.971705E+09 | 0.00 | 30372210.96 | 0.00 | 0.26 |
December | 0.214153E+09 | 0.105987E+10 | 0.00 | 4651007.43 | 0.112635E+10 | 0.00 | 0.188116E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.155215E+10 | 0.842324E+11 | 0.00 | 32305023.02 | 0.322052E+11 | 0.00 | 0.151156E+10 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.353670E+09 | 0.00 | 0.00 | 0.455285E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.654939E+09 | 0.172532E+11 | 0.00 | 7677787.31 | 0.773546E+10 | 0.00 | 0.541997E+09 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.318112E+09 | 61141183.53 | 0.00 | 724312.34 | 0.244100E+09 | 15571333.62 | 98731002.21 | 0.00 | 0.42 |
February | 0.129030E+09 | 0.156591E+09 | 19647.93 | 1303682.39 | 0.362409E+09 | 3202948.59 | 76937835.79 | 5055.17 | 0.42 |
March | 0.102415E+09 | 0.442302E+09 | 0.00 | 1538292.68 | 0.328501E+09 | 456063.12 | 81173858.27 | 0.00 | 0.45 |
April | 49315313.55 | 0.117286E+10 | 0.00 | 661315.96 | 0.470623E+09 | 0.00 | 10861554.10 | 0.00 | 0.47 |
May | 13452167.85 | 0.303337E+10 | 0.00 | 237370.76 | 0.664521E+09 | 0.00 | 2837978.30 | 0.00 | 0.55 |
June | 1744305.66 | 0.530824E+10 | 0.00 | 116057.86 | 0.114633E+10 | 0.00 | 602108.89 | 0.00 | 0.60 |
July | 1657178.32 | 0.731343E+10 | 0.00 | 47854.93 | 0.227279E+10 | 0.00 | 239340.67 | 0.00 | 0.66 |
August | 0.00 | 0.813931E+10 | 0.00 | 0.00 | 0.222142E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 3785.63 | 0.538921E+10 | 0.00 | 2283.90 | 0.148187E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 13513468.13 | 0.279530E+10 | 0.00 | 228528.67 | 0.979133E+09 | 0.00 | 2805944.54 | 0.00 | 0.47 |
November | 3910351.07 | 0.118655E+10 | 0.00 | 402608.02 | 0.697008E+09 | 0.00 | 8986847.07 | 0.00 | 0.43 |
December | 95042861.42 | 0.198590E+09 | 4700.31 | 684094.01 | 0.584161E+09 | 2351802.50 | 42709980.57 | 5252.74 | 0.41 |
Annual Sum or Average | 0.728197E+09 | 0.351969E+11 | 24348.25 | 5946401.52 | 0.114529E+11 | 21582147.83 | 0.325886E+09 | 10307.90 | 0.51 |
Minimum of Months | 0.00 | 61141183.53 | 0.00 | 0.00 | 0.244100E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.318112E+09 | 0.813931E+10 | 19647.93 | 1538292.68 | 0.227279E+10 | 15571333.62 | 98731002.21 | 5252.74 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228302E+09 | 70060127.81 | 0.00 | 667083.55 | 0.165340E+09 | 4464272.34 | 0.100379E+09 | 0.00 | 0.51 |
February | 92650669.32 | 0.142291E+09 | 15832.09 | 1138846.71 | 0.255874E+09 | 1141258.28 | 66984445.23 | 3209.10 | 0.51 |
March | 76905558.76 | 0.384798E+09 | 0.00 | 1293634.73 | 0.222197E+09 | 351534.14 | 63559077.21 | 0.00 | 0.55 |
April | 35377639.12 | 0.958208E+09 | 0.00 | 662762.27 | 0.350064E+09 | 0.00 | 11421107.96 | 0.00 | 0.59 |
May | 9696895.31 | 0.236706E+10 | 0.00 | 213189.90 | 0.462288E+09 | 0.00 | 2775930.81 | 0.00 | 0.68 |
June | 1344513.43 | 0.396240E+10 | 0.00 | 98554.01 | 0.902129E+09 | 0.00 | 545622.79 | 0.00 | 0.72 |
July | 1336427.87 | 0.535814E+10 | 0.00 | 30899.72 | 0.181610E+10 | 0.00 | 124180.29 | 0.00 | 0.79 |
August | 0.00 | 0.606491E+10 | 0.00 | 0.00 | 0.179114E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
September | 2917.97 | 0.421822E+10 | 0.00 | 1301.52 | 0.108658E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 9565992.20 | 0.235100E+10 | 0.00 | 312888.59 | 0.658584E+09 | 0.00 | 3109482.71 | 0.00 | 0.59 |
November | 3007964.01 | 0.969454E+09 | 0.00 | 299790.23 | 0.516818E+09 | 0.00 | 6404557.80 | 0.00 | 0.53 |
December | 71210118.58 | 0.191769E+09 | 40954.08 | 539498.34 | 0.410629E+09 | 750594.83 | 35566106.15 | 4574.96 | 0.50 |
Annual Sum or Average | 0.529400E+09 | 0.270383E+11 | 56786.17 | 5258449.56 | 0.863775E+10 | 6707659.59 | 0.290870E+09 | 7784.06 | 0.62 |
Minimum of Months | 0.00 | 70060127.81 | 0.00 | 0.00 | 0.165340E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.228302E+09 | 0.606491E+10 | 40954.08 | 1293634.73 | 0.181610E+10 | 4464272.34 | 0.100379E+09 | 4574.96 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.281672E+09 | 0.189493E+09 | 0.00 | 3619523.57 | 0.182131E+09 | 7696877.87 | 0.236577E+09 | 0.00 | 0.52 |
February | 0.121226E+09 | 0.296068E+09 | 22760.09 | 3281955.44 | 0.327578E+09 | 2791361.24 | 0.151850E+09 | 4496.04 | 0.53 |
March | 0.106190E+09 | 0.627402E+09 | 0.00 | 2673416.54 | 0.294679E+09 | 503196.62 | 0.122203E+09 | 0.00 | 0.54 |
April | 54325862.19 | 0.133414E+10 | 0.00 | 774462.99 | 0.524315E+09 | 0.00 | 12564354.82 | 0.00 | 0.53 |
May | 15781056.72 | 0.300515E+10 | 0.00 | 226334.82 | 0.808234E+09 | 0.00 | 2105424.68 | 0.00 | 0.57 |
June | 1949928.67 | 0.502901E+10 | 0.00 | 111524.22 | 0.142016E+10 | 0.00 | 566952.04 | 0.00 | 0.60 |
July | 1913003.34 | 0.703899E+10 | 0.00 | 44713.15 | 0.273611E+10 | 0.00 | 176358.63 | 0.00 | 0.67 |
August | 0.00 | 0.841526E+10 | 0.00 | 0.00 | 0.258532E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 4176.87 | 0.639023E+10 | 0.00 | 2215.74 | 0.156322E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 10585277.10 | 0.386728E+10 | 0.00 | 934207.83 | 0.905295E+09 | 0.00 | 9335902.57 | 0.00 | 0.61 |
November | 4137971.94 | 0.193411E+10 | 0.00 | 798493.61 | 0.565239E+09 | 0.00 | 14898547.98 | 0.00 | 0.58 |
December | 84566222.56 | 0.550620E+09 | 5200.33 | 2407491.43 | 0.444665E+09 | 1354573.17 | 96883061.49 | 5781.36 | 0.53 |
Annual Sum or Average | 0.682351E+09 | 0.386778E+11 | 27960.42 | 14874339.36 | 0.123569E+11 | 12346008.90 | 0.647160E+09 | 10277.39 | 0.59 |
Minimum of Months | 0.00 | 0.189493E+09 | 0.00 | 0.00 | 0.182131E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.281672E+09 | 0.841526E+10 | 22760.09 | 3619523.57 | 0.273611E+10 | 7696877.87 | 0.236577E+09 | 5781.36 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285021E+09 | 54776414.85 | 0.00 | 841226.79 | 0.218815E+09 | 16703033.09 | 85864713.79 | 0.00 | 0.59 |
February | 0.111994E+09 | 0.117088E+09 | 19827.04 | 1219896.26 | 0.344072E+09 | 3122379.30 | 75507386.68 | 2316.75 | 0.59 |
March | 93105111.31 | 0.351603E+09 | 18860.17 | 1303123.28 | 0.318313E+09 | 605991.73 | 76906386.22 | 786.20 | 0.62 |
April | 44385732.53 | 0.946489E+09 | 0.00 | 462697.46 | 0.470453E+09 | 0.00 | 8261211.27 | 0.00 | 0.63 |
May | 12897517.19 | 0.238213E+10 | 0.00 | 157462.07 | 0.651175E+09 | 0.00 | 1678174.16 | 0.00 | 0.70 |
June | 1563590.49 | 0.400375E+10 | 0.00 | 73304.21 | 0.114426E+10 | 0.00 | 386714.00 | 0.00 | 0.75 |
July | 1610846.74 | 0.532248E+10 | 0.00 | 28455.57 | 0.227252E+10 | 0.00 | 85072.47 | 0.00 | 0.82 |
August | 0.00 | 0.609565E+10 | 0.00 | 0.00 | 0.221814E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
September | 3393.43 | 0.431396E+10 | 0.00 | 1429.94 | 0.139296E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
October | 12207916.26 | 0.220176E+10 | 0.00 | 153188.60 | 0.998452E+09 | 0.00 | 1903397.88 | 0.00 | 0.63 |
November | 3487966.00 | 0.874558E+09 | 0.00 | 362708.55 | 0.766310E+09 | 17261.27 | 8346104.35 | 0.00 | 0.59 |
December | 84399965.92 | 0.173323E+09 | 48434.09 | 707917.37 | 0.529625E+09 | 2399272.53 | 39467097.47 | 4513.52 | 0.58 |
Annual Sum or Average | 0.650677E+09 | 0.268376E+11 | 87121.29 | 5311410.11 | 0.113251E+11 | 22847937.91 | 0.298406E+09 | 7616.48 | 0.67 |
Minimum of Months | 0.00 | 54776414.85 | 0.00 | 0.00 | 0.218815E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.285021E+09 | 0.609565E+10 | 48434.09 | 1303123.28 | 0.227252E+10 | 16703033.09 | 85864713.79 | 4513.52 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.379447E+09 | 36303654.19 | 0.00 | 1616790.08 | 89464306.97 | 0.00 | 0.146617E+09 | 0.00 | 0.31 |
February | 0.179597E+09 | 0.150050E+09 | 0.00 | 1566599.55 | 0.132448E+09 | 0.00 | 88082131.58 | 0.00 | 0.31 |
March | 0.155185E+09 | 0.395464E+09 | 0.00 | 1594056.05 | 0.116549E+09 | 0.00 | 82312128.25 | 0.00 | 0.34 |
April | 63555809.21 | 0.997687E+09 | 0.00 | 573914.42 | 0.313049E+09 | 0.00 | 22408943.73 | 0.00 | 0.36 |
May | 18527509.81 | 0.268180E+10 | 0.00 | 175844.47 | 0.688760E+09 | 0.00 | 2804202.05 | 0.00 | 0.47 |
June | 1712393.88 | 0.484753E+10 | 0.00 | 17533.44 | 0.115524E+10 | 0.00 | 77656.75 | 0.00 | 0.53 |
July | 2304737.03 | 0.684636E+10 | 0.00 | 68791.20 | 0.219191E+10 | 0.00 | 625638.11 | 0.00 | 0.60 |
August | 0.00 | 0.780915E+10 | 0.00 | 0.00 | 0.222345E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.513763E+10 | 0.00 | 0.00 | 0.171122E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 15254908.05 | 0.267274E+10 | 0.00 | 235715.19 | 0.107020E+10 | 0.00 | 7147397.87 | 0.00 | 0.45 |
November | 16547341.53 | 0.120916E+10 | 0.00 | 406229.84 | 0.237494E+09 | 0.00 | 8624528.29 | 0.00 | 0.36 |
December | 0.162232E+09 | 0.262936E+09 | 0.00 | 1985886.48 | 0.168994E+09 | 0.00 | 89466422.69 | 0.00 | 0.31 |
Annual Sum or Average | 0.994363E+09 | 0.330468E+11 | 0.00 | 8241360.73 | 0.100988E+11 | 0.00 | 0.448166E+09 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 36303654.19 | 0.00 | 0.00 | 89464306.97 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.379447E+09 | 0.780915E+10 | 0.00 | 1985886.48 | 0.222345E+10 | 0.00 | 0.146617E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291807E+09 | 38415285.99 | 0.00 | 1557647.05 | 67251265.13 | 0.00 | 0.154565E+09 | 0.00 | 0.41 |
February | 0.138348E+09 | 0.107505E+09 | 0.00 | 1558949.07 | 0.125063E+09 | 0.00 | 87907757.32 | 0.00 | 0.41 |
March | 0.128391E+09 | 0.323866E+09 | 0.00 | 1463565.28 | 0.104039E+09 | 0.00 | 72900932.17 | 0.00 | 0.45 |
April | 52635760.26 | 0.830873E+09 | 0.00 | 685295.21 | 0.262091E+09 | 0.00 | 21944836.70 | 0.00 | 0.49 |
May | 15213475.64 | 0.212419E+10 | 0.00 | 185259.45 | 0.531923E+09 | 0.00 | 3058588.04 | 0.00 | 0.60 |
June | 1473387.75 | 0.365815E+10 | 0.00 | 11256.45 | 0.990199E+09 | 0.00 | 52776.96 | 0.00 | 0.66 |
July | 1958377.60 | 0.508655E+10 | 0.00 | 44781.74 | 0.191621E+10 | 0.00 | 518263.94 | 0.00 | 0.74 |
August | 0.00 | 0.594345E+10 | 0.00 | 0.00 | 0.190299E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.399286E+10 | 0.00 | 0.00 | 0.142162E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 12373347.03 | 0.217525E+10 | 0.00 | 297952.53 | 0.849017E+09 | 0.00 | 8249735.66 | 0.00 | 0.57 |
November | 12889317.65 | 0.966888E+09 | 0.00 | 384128.23 | 0.203893E+09 | 0.00 | 8178600.99 | 0.00 | 0.47 |
December | 0.125853E+09 | 0.206285E+09 | 0.00 | 1594124.98 | 0.153343E+09 | 0.00 | 84772613.77 | 0.00 | 0.41 |
Annual Sum or Average | 0.780943E+09 | 0.254543E+11 | 0.00 | 7782959.99 | 0.852764E+10 | 0.00 | 0.442149E+09 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 38415285.99 | 0.00 | 0.00 | 67251265.13 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.291807E+09 | 0.594345E+10 | 0.00 | 1594124.98 | 0.191621E+10 | 0.00 | 0.154565E+09 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.348299E+09 | 0.107796E+09 | 0.00 | 4376114.71 | 61693479.31 | 51974506.08 | 0.259759E+09 | 0.00 | 0.41 |
February | 0.165795E+09 | 0.287698E+09 | 0.00 | 3694786.36 | 0.100193E+09 | 28910426.44 | 0.156483E+09 | 0.00 | 0.43 |
March | 0.157297E+09 | 0.673517E+09 | 0.00 | 2811657.02 | 76121583.41 | 14801093.06 | 0.120359E+09 | 0.00 | 0.46 |
April | 76555822.38 | 0.142020E+10 | 0.00 | 815160.73 | 0.334376E+09 | 124729.00 | 22821579.52 | 0.00 | 0.48 |
May | 19739176.08 | 0.347277E+10 | 0.00 | 243665.70 | 0.814242E+09 | 0.00 | 5338013.51 | 0.00 | 0.59 |
June | 1943167.85 | 0.585540E+10 | 0.00 | 10868.59 | 0.145038E+10 | 0.00 | 83788.29 | 0.00 | 0.65 |
July | 2598350.79 | 0.842116E+10 | 0.00 | 78407.98 | 0.270881E+10 | 0.00 | 695349.38 | 0.00 | 0.73 |
August | 0.00 | 0.105303E+11 | 0.00 | 0.00 | 0.250730E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
September | 0.00 | 0.770435E+10 | 0.00 | 0.00 | 0.169621E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
October | 13545878.89 | 0.460255E+10 | 0.00 | 865412.26 | 0.908767E+09 | 0.00 | 13942216.27 | 0.00 | 0.67 |
November | 18651608.27 | 0.213818E+10 | 0.00 | 808072.77 | 0.194950E+09 | 0.00 | 14115466.01 | 0.00 | 0.56 |
December | 0.134494E+09 | 0.527095E+09 | 0.00 | 4455702.79 | 0.112378E+09 | 16178023.20 | 0.187411E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.938919E+09 | 0.457410E+11 | 0.00 | 18159848.90 | 0.109654E+11 | 0.111989E+09 | 0.781010E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.107796E+09 | 0.00 | 0.00 | 61693479.31 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.348299E+09 | 0.105303E+11 | 0.00 | 4455702.79 | 0.270881E+10 | 51974506.08 | 0.259759E+09 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.364771E+09 | 42362935.26 | 0.00 | 1257128.72 | 71340884.41 | 0.00 | 0.119774E+09 | 0.00 | 0.45 |
February | 0.169924E+09 | 0.116414E+09 | 0.00 | 1300835.57 | 0.136690E+09 | 0.00 | 78414144.18 | 0.00 | 0.45 |
March | 0.149892E+09 | 0.347010E+09 | 0.00 | 1181238.38 | 0.104685E+09 | 0.00 | 71654983.80 | 0.00 | 0.48 |
April | 66293281.62 | 0.877395E+09 | 0.00 | 304623.81 | 0.271984E+09 | 0.00 | 10958322.46 | 0.00 | 0.50 |
May | 17724775.44 | 0.217874E+10 | 0.00 | 73175.64 | 0.604331E+09 | 0.00 | 1885191.53 | 0.00 | 0.61 |
June | 1605489.17 | 0.370334E+10 | 0.00 | 7190.97 | 0.111431E+10 | 0.00 | 49228.62 | 0.00 | 0.67 |
July | 2119035.01 | 0.513592E+10 | 0.00 | 39541.57 | 0.207151E+10 | 0.00 | 563441.84 | 0.00 | 0.75 |
August | 0.00 | 0.600370E+10 | 0.00 | 0.00 | 0.208155E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
September | 0.00 | 0.414712E+10 | 0.00 | 0.00 | 0.149816E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 14206139.80 | 0.213845E+10 | 0.00 | 122847.41 | 0.958467E+09 | 0.00 | 5875320.90 | 0.00 | 0.58 |
November | 16656750.07 | 0.984930E+09 | 0.00 | 315336.92 | 0.228685E+09 | 0.00 | 6404702.40 | 0.00 | 0.48 |
December | 0.151912E+09 | 0.210938E+09 | 0.00 | 1390528.09 | 0.179339E+09 | 0.00 | 79394609.67 | 0.00 | 0.44 |
Annual Sum or Average | 0.955105E+09 | 0.258863E+11 | 0.00 | 5992447.08 | 0.932104E+10 | 0.00 | 0.374974E+09 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 42362935.26 | 0.00 | 0.00 | 71340884.41 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.364771E+09 | 0.600370E+10 | 0.00 | 1390528.09 | 0.208155E+10 | 0.00 | 0.119774E+09 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.430821E+09 | 71206093.12 | 0.00 | 1199752.10 | 0.152337E+09 | 1435407.48 | 0.112519E+09 | 0.00 | 0.39 |
February | 0.198188E+09 | 0.195989E+09 | 0.00 | 1336740.60 | 0.240923E+09 | 226747.99 | 75396332.62 | 0.00 | 0.40 |
March | 0.170649E+09 | 0.540409E+09 | 0.00 | 1516026.16 | 0.190505E+09 | 0.00 | 78061550.07 | 0.00 | 0.44 |
April | 74075796.92 | 0.134557E+10 | 0.00 | 634555.91 | 0.370373E+09 | 0.00 | 26036384.79 | 0.00 | 0.47 |
May | 23524986.78 | 0.329546E+10 | 0.00 | 304742.52 | 0.646618E+09 | 0.00 | 5857191.47 | 0.00 | 0.56 |
June | 3002084.86 | 0.578531E+10 | 0.00 | 67318.13 | 0.114064E+10 | 0.00 | 548814.39 | 0.00 | 0.62 |
July | 3143403.78 | 0.809364E+10 | 0.00 | 64574.98 | 0.215920E+10 | 0.00 | 1268751.26 | 0.00 | 0.68 |
August | 0.00 | 0.890335E+10 | 0.00 | 0.00 | 0.211746E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 342921.50 | 0.576435E+10 | 0.00 | 10277.36 | 0.146989E+10 | 0.00 | 5920.09 | 0.00 | 0.56 |
October | 16304073.30 | 0.294020E+10 | 0.00 | 189168.94 | 0.899916E+09 | 0.00 | 4061538.47 | 0.00 | 0.48 |
November | 17660064.56 | 0.136458E+10 | 0.00 | 356482.11 | 0.383759E+09 | 0.00 | 7287176.99 | 0.00 | 0.42 |
December | 0.176962E+09 | 0.265617E+09 | 0.00 | 1096467.85 | 0.376081E+09 | 0.00 | 52515657.57 | 0.00 | 0.39 |
Annual Sum or Average | 0.111467E+10 | 0.385657E+11 | 0.00 | 6776106.64 | 0.101477E+11 | 1662155.47 | 0.363559E+09 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 71206093.12 | 0.00 | 0.00 | 0.152337E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.430821E+09 | 0.890335E+10 | 0.00 | 1516026.16 | 0.215920E+10 | 1435407.48 | 0.112519E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.377279E+09 | 55903952.11 | 0.00 | 632015.31 | 0.134661E+09 | 2841456.05 | 89524734.71 | 0.00 | 0.53 |
February | 0.166987E+09 | 0.136412E+09 | 0.00 | 902211.59 | 0.224788E+09 | 503624.30 | 65215363.91 | 0.00 | 0.53 |
March | 0.146512E+09 | 0.395002E+09 | 0.00 | 1125355.57 | 0.198968E+09 | 0.00 | 63504872.58 | 0.00 | 0.57 |
April | 63666686.81 | 0.102264E+10 | 0.00 | 639688.23 | 0.365387E+09 | 0.00 | 23015161.38 | 0.00 | 0.61 |
May | 19954078.72 | 0.247826E+10 | 0.00 | 260090.17 | 0.531494E+09 | 0.00 | 5469615.69 | 0.00 | 0.70 |
June | 2814296.94 | 0.420311E+10 | 0.00 | 40240.37 | 0.101634E+10 | 0.00 | 225601.74 | 0.00 | 0.75 |
July | 3353539.08 | 0.564995E+10 | 0.00 | 37934.70 | 0.210037E+10 | 0.00 | 415291.89 | 0.00 | 0.83 |
August | 0.00 | 0.637272E+10 | 0.00 | 0.00 | 0.204625E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
September | 295550.67 | 0.433859E+10 | 0.00 | 5745.18 | 0.127833E+10 | 0.00 | 3385.35 | 0.00 | 0.70 |
October | 12036938.85 | 0.239136E+10 | 0.00 | 227055.24 | 0.702850E+09 | 0.00 | 5852240.65 | 0.00 | 0.61 |
November | 14335071.73 | 0.100974E+10 | 0.00 | 252381.72 | 0.407479E+09 | 0.00 | 6137843.31 | 0.00 | 0.54 |
December | 0.155010E+09 | 0.180019E+09 | 0.00 | 604097.34 | 0.357372E+09 | 665139.98 | 40302183.13 | 0.00 | 0.52 |
Annual Sum or Average | 0.962245E+09 | 0.282337E+11 | 0.00 | 4726815.41 | 0.936428E+10 | 4010220.34 | 0.299666E+09 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 55903952.11 | 0.00 | 0.00 | 0.134661E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.377279E+09 | 0.637272E+10 | 0.00 | 1125355.57 | 0.210037E+10 | 2841456.05 | 89524734.71 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.408029E+09 | 0.198664E+09 | 0.00 | 4232560.94 | 0.107111E+09 | 1344956.16 | 0.279442E+09 | 0.00 | 0.53 |
February | 0.205887E+09 | 0.362368E+09 | 0.00 | 3043197.11 | 0.203693E+09 | 0.00 | 0.148990E+09 | 0.00 | 0.54 |
March | 0.190537E+09 | 0.772170E+09 | 0.00 | 2450174.23 | 0.153130E+09 | 0.00 | 0.113106E+09 | 0.00 | 0.55 |
April | 95457002.87 | 0.156786E+10 | 0.00 | 656128.62 | 0.415230E+09 | 0.00 | 17379369.53 | 0.00 | 0.54 |
May | 27525802.21 | 0.325159E+10 | 0.00 | 241328.31 | 0.803891E+09 | 0.00 | 5535086.54 | 0.00 | 0.58 |
June | 3771353.99 | 0.544241E+10 | 0.00 | 54645.96 | 0.145121E+10 | 0.00 | 230043.06 | 0.00 | 0.62 |
July | 4216247.13 | 0.766248E+10 | 0.00 | 52133.84 | 0.280559E+10 | 0.00 | 732627.11 | 0.00 | 0.70 |
August | 0.00 | 0.922240E+10 | 0.00 | 0.00 | 0.254379E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 387432.10 | 0.700356E+10 | 0.00 | 10079.88 | 0.152006E+10 | 0.00 | 5832.87 | 0.00 | 0.67 |
October | 16440420.98 | 0.424915E+10 | 0.00 | 449860.41 | 0.778896E+09 | 0.00 | 7271397.73 | 0.00 | 0.63 |
November | 19456025.79 | 0.217930E+10 | 0.00 | 654028.24 | 0.284470E+09 | 0.00 | 12153321.75 | 0.00 | 0.59 |
December | 0.173807E+09 | 0.615704E+09 | 0.00 | 3047616.00 | 0.277231E+09 | 0.00 | 0.123125E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.114552E+10 | 0.425277E+11 | 0.00 | 14891753.56 | 0.113443E+11 | 1344956.16 | 0.707971E+09 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.198664E+09 | 0.00 | 0.00 | 0.107111E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.408029E+09 | 0.922240E+10 | 0.00 | 4232560.94 | 0.280559E+10 | 1344956.16 | 0.279442E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.420847E+09 | 71612313.65 | 0.00 | 1026844.63 | 0.137597E+09 | 3450809.37 | 92505145.84 | 0.00 | 0.59 |
February | 0.188683E+09 | 0.153459E+09 | 0.00 | 1095662.04 | 0.249679E+09 | 2137822.82 | 70294005.81 | 0.00 | 0.60 |
March | 0.168699E+09 | 0.438639E+09 | 0.00 | 1153124.10 | 0.216450E+09 | 0.00 | 69548200.18 | 0.00 | 0.63 |
April | 84054735.34 | 0.113792E+10 | 0.00 | 344080.10 | 0.384760E+09 | 0.00 | 8318156.11 | 0.00 | 0.65 |
May | 23591160.19 | 0.266564E+10 | 0.00 | 143233.06 | 0.629966E+09 | 0.00 | 4136495.76 | 0.00 | 0.73 |
June | 3159805.17 | 0.445038E+10 | 0.00 | 33774.59 | 0.116908E+10 | 0.00 | 183833.47 | 0.00 | 0.79 |
July | 3936979.21 | 0.589958E+10 | 0.00 | 26658.07 | 0.237750E+10 | 0.00 | 200471.71 | 0.00 | 0.87 |
August | 0.00 | 0.667620E+10 | 0.00 | 0.00 | 0.233618E+10 | 0.00 | 0.00 | 0.00 | 0.89 |
September | 324607.55 | 0.468733E+10 | 0.00 | 5455.43 | 0.142794E+10 | 0.00 | 3242.41 | 0.00 | 0.75 |
October | 18092956.14 | 0.240661E+10 | 0.00 | 102111.82 | 0.897518E+09 | 0.00 | 1027223.56 | 0.00 | 0.65 |
November | 16795865.49 | 0.102698E+10 | 0.00 | 320846.90 | 0.521827E+09 | 0.00 | 6873052.23 | 0.00 | 0.59 |
December | 0.168840E+09 | 0.222262E+09 | 0.00 | 864250.05 | 0.378176E+09 | 1155222.57 | 48429851.92 | 0.00 | 0.58 |
Annual Sum or Average | 0.109703E+10 | 0.298366E+11 | 0.00 | 5116040.80 | 0.107267E+11 | 6743854.76 | 0.301520E+09 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 71612313.65 | 0.00 | 0.00 | 0.137597E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.420847E+09 | 0.667620E+10 | 0.00 | 1153124.10 | 0.237750E+10 | 3450809.37 | 92505145.84 | 0.00 | 0.89 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.219341E+12 | 0.201583E+10 | 0.00 | 0.166397E+11 | 0.175305E+12 |
February | 0.238623E+12 | 0.314042E+09 | 0.00 | 0.104014E+10 | 0.188244E+12 |
March | 0.294683E+12 | -0.137136E+10 | 0.00 | -0.916134E+10 | 0.253964E+12 |
April | 0.312405E+12 | -0.540854E+10 | 0.00 | -0.433092E+11 | 0.305916E+12 |
May | 0.329634E+12 | -0.120554E+11 | 0.00 | -0.989368E+11 | 0.458858E+12 |
June | 0.318493E+12 | -0.200167E+11 | 0.00 | -0.163879E+12 | 0.551516E+12 |
July | 0.311591E+12 | -0.268272E+11 | 0.00 | -0.226502E+12 | 0.660446E+12 |
August | 0.302353E+12 | -0.288089E+11 | 0.00 | -0.242610E+12 | 0.714643E+12 |
September | 0.272362E+12 | -0.212258E+11 | 0.00 | -0.187765E+12 | 0.557113E+12 |
October | 0.240587E+12 | -0.124915E+11 | 0.00 | -0.116643E+12 | 0.438329E+12 |
November | 0.198316E+12 | -0.577296E+10 | 0.00 | -0.507627E+11 | 0.310199E+12 |
December | 0.191791E+12 | -508412089.2 | 0.00 | -0.919980E+10 | 0.212471E+12 |
Annual Sum or Average | 0.323018E+13 | -0.132157E+12 | 0.00 | -0.113109E+13 | 0.482701E+13 |
Minimum of Months | 0.191791E+12 | -0.288089E+11 | 0.00 | -0.242610E+12 | 0.175305E+12 |
Maximum of Months | 0.329634E+12 | 0.201583E+10 | 0.00 | 0.166397E+11 | 0.714643E+12 |