Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2024-07-03 12:21:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2777.46 | 557.48 | 557.48 |
Net Site Energy | 2777.46 | 557.48 | 557.48 |
Total Source Energy | 7056.11 | 1416.27 | 1416.27 |
Net Source Energy | 7056.11 | 1416.27 | 1416.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 835.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 235.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 192.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 59.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1942.08 | 835.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 835.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 127.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 235.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 192.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 59.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 835.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 127.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 566.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 235.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 729.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 27.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 192.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 59.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 76.98 | 167.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 389.80 | 167.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 76.98 | 167.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 151.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 389.80 | 167.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1942.080 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1942.080 | 100.00 |
Total On-Site and Utility Electric Sources | 1942.080 | 100.00 |
Total Electricity End Uses | 1942.080 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 441.33 |
Time Setpoint Not Met During Occupied Cooling | 35.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3177.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 613.07 | 183.92 | 122.61 | 183.92 | 122.61 |
Gross Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Above Ground Window-Wall Ratio [%] | 31.00 | 31.00 | 31.00 | 31.00 | 31.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 89.6613 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 61.31 | 61.31 | 11.0267 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 40.87 | 40.87 | 11.0267 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 613.07 | 613.07 | 11.0267 | 18.58 | 24.1769 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 11.0267 | 18.58 | 89.6613 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 11.0267 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 11.0267 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 11.0267 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 11.0267 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 11.0267 | 18.58 | 8.0700 | |
Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Conditioned Total | 4982.19 | 11.0267 | 9.29 | 24.1769 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 11.0267 | 18.58 | 24.1769 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-15:00 | 09-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 04-JAN-12:09 |
Heating | 0.00 | 385302.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 84924.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41937.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 35214.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4353.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 217289.80 | 385302.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 385302.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 84924.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 35214.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4353.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 905.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 404.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 745.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2309.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 87.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 609.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 13.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 187.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6150.57 | 905.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 181.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 81.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1234.51 | 181.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 181.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 81.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 359.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 149.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1234.51 | 181.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.82 | 0.196320 | 0.300000 | 1.15 | 0.523520 | 0.500000 | 0.001941 | 0.000187 | 1.15 | 12.89 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 3.12 | 0.240063 | 0.300000 | 0.936572 | 0.640168 | 0.500000 | 0.001587 | 0.000355 | 1.95 | 12.89 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.05 | 0.185118 | 0.300000 | 1.21 | 0.493647 | 0.500000 | 0.002058 | 0.000735 | 4.05 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.84 | 0.085989 | 0.300000 | 0.551205 | 0.300000 | 0.500000 | 0.004431 | 0.000333 | 1.84 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.20 | 0.083284 | 0.300000 | 0.360292 | 0.300000 | 0.500000 | 0.004575 | 0.000218 | 1.20 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.86 | 0.084937 | 0.300000 | 0.558033 | 0.300000 | 0.500000 | 0.004486 | 0.000337 | 1.86 | 12.89 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.27 | 0.079039 | 0.300000 | 0.379620 | 0.300000 | 0.500000 | 0.004820 | 0.000221 | 1.22 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.42 | 0.111342 | 0.300000 | 0.425692 | 0.300000 | 0.500000 | 0.003422 | 0.000257 | 1.42 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.933606 | 0.107135 | 0.300000 | 0.280082 | 0.300000 | 0.500000 | 0.003556 | 0.000169 | 0.933606 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.44 | 0.109592 | 0.300000 | 0.432492 | 0.300000 | 0.500000 | 0.003477 | 0.000262 | 1.44 | 12.89 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.963854 | 0.103766 | 0.300000 | 0.289156 | 0.300000 | 0.500000 | 0.003672 | 0.000172 | 0.948442 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 1.40 | 0.112516 | 0.300000 | 0.421250 | 0.300043 | 0.500000 | 0.003386 | 0.000255 | 1.40 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 1.08 | 0.300000 | 0.500000 | 0.004115 | 0.000168 | 0.925905 | 12.89 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.43 | 0.110842 | 0.300000 | 0.427615 | 0.300000 | 0.500000 | 0.003437 | 0.000259 | 1.43 | 12.89 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.15 | 0.086870 | 0.300000 | 0.345396 | 0.300000 | 0.500000 | 0.004386 | 0.000171 | 0.941041 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21329.55 | 0.000187 | 484.55 |
CORE_MID VAV BOX REHEAT COIL | 40595.28 | 0.000355 | 949.27 |
CORE_TOP VAV BOX REHEAT COIL | 84060.05 | 0.000735 | 1963.87 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 38083.90 | 0.000333 | 889.32 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24892.33 | 0.000218 | 581.27 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 38555.10 | 0.000337 | 900.32 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 25220.11 | 0.000221 | 588.92 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 29421.92 | 0.000257 | 687.12 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 19356.76 | 0.000169 | 452.05 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 29891.15 | 0.000262 | 698.07 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 19663.87 | 0.000172 | 459.22 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 29115.77 | 0.000255 | 679.97 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 19197.52 | 0.000168 | 448.33 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 29554.93 | 0.000259 | 690.22 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 19510.85 | 0.000171 | 455.65 |
PACU_VAV_BOT HEATING COIL | 35351.32 | 0.000309 | 580.81 |
PACU_VAV_MID HEATING COIL | 35565.76 | 0.000311 | 583.42 |
PACU_VAV_TOP HEATING COIL | 29615.74 | 0.000259 | 509.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 4.29 | 2.57 | 8.58 | 5.66 | 6.72 | 6.72 | 0.300000 | 0.842853 | 6.72 |
PACU_VAV_MID | 4.09 | 2.45 | 8.18 | 6.65 | 6.44 | 6.65 | 0.300000 | 1.00 | 6.65 |
PACU_VAV_TOP | 5.11 | 3.06 | 10.21 | 10.16 | 7.89 | 10.16 | 0.300000 | 1.00 | 10.16 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.72 |
PACU_VAV_MID_OA_CONTROLLER | 6.65 |
PACU_VAV_TOP_OA_CONTROLLER | 10.16 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.72 | 111203.06 | 0.800655 | 2.24 | 37063.98 | 0.800655 |
PACU_VAV_MID COOLING COIL | 6.65 | 110004.49 | 0.800655 | 2.21 | 36664.50 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 10.16 | 168246.51 | 0.800655 | 3.39 | 56076.56 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.72 |
PACU_VAV_MID FAN | 6.65 |
PACU_VAV_TOP FAN | 10.16 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000309 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000311 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000259 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004978 | 0.597324 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.004978 | 1499.07 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 568981.92 | 568981.92 | 0.004978 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.71 | 61.31 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 48.45 | 40.87 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 75.61 | 61.31 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 50.41 | 40.87 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 89.661 | 0.000 | 0.000 | 0.000 | 0.000 | 100.688 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 19.096 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 11.027 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.097 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 10845.123 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10845.123 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1447.384 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.384 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2286.247 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2286.247 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1447.289 | 11.027 | 204.862 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1447.289 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 324.000 | 0.329 | 6.120 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
39 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
40 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
41 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
42 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
43 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
44 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
45 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
46 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
47 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
48 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
49 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
50 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
51 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
52 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
53 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
54 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
55 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
56 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
57 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
58 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
59 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
60 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
61 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
62 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
63 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
64 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
65 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.45 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.45 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone CORE_BOTTOM | 1.2500 |
3 | Zone CORE_MID | 1.2500 |
4 | Zone CORE_TOP | 1.2500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.2500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.2500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.2500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.2500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.2500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.2500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.2500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.2500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.2500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.2500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.2500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone CORE_BOTTOM | 1.1500 |
3 | Zone CORE_MID | 1.1500 |
4 | Zone CORE_TOP | 1.1500 |
5 | Zone PERIMETER_TOP_ZN_3 | 1.1500 |
6 | Zone PERIMETER_TOP_ZN_2 | 1.1500 |
7 | Zone PERIMETER_TOP_ZN_1 | 1.1500 |
8 | Zone PERIMETER_TOP_ZN_4 | 1.1500 |
9 | Zone PERIMETER_BOT_ZN_3 | 1.1500 |
10 | Zone PERIMETER_BOT_ZN_2 | 1.1500 |
11 | Zone PERIMETER_BOT_ZN_1 | 1.1500 |
12 | Zone PERIMETER_BOT_ZN_4 | 1.1500 |
13 | Zone PERIMETER_MID_ZN_3 | 1.1500 |
14 | Zone PERIMETER_MID_ZN_2 | 1.1500 |
15 | Zone PERIMETER_MID_ZN_1 | 1.1500 |
16 | Zone PERIMETER_MID_ZN_4 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 39962.32006 | 45956.66807 | 3.31958 | 3.81752 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9083.04467 | 11353.80584 | 0.76122 | 0.95153 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 32703.80397 | 37609.37457 | 2.71470 | 3.12191 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18895.68612 | 23619.60765 | 1.55910 | 1.94887 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 37165.91765 | 42740.80530 | 3.11229 | 3.57913 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 32.92000 | 6.30608E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 39036.24986 | 48795.31233 | 3.23883 | 4.04853 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10952.76634 | 12595.68129 | 0.91714 | 1.05471 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 17668.16038 | 22085.20048 | 1.46988 | 1.83735 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11271.67268 | 12962.42359 | 0.94383 | 1.08541 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.41333 | 6.29608E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 11547.95966 | 14434.94958 | 0.96078 | 1.20097 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 16069.88707 | 18480.37013 | 1.34562 | 1.54746 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 17886.53165 | 22358.16456 | 1.48809 | 1.86011 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 13140.79873 | 15111.91854 | 1.10035 | 1.26540 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 30.62667 | 6.30253E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 11699.87204 | 14624.84005 | 0.97345 | 1.21681 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7759.52352 | 8923.45204 | 0.64976 | 0.74723 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 13651.76419 | 17064.70523 | 1.13518 | 1.41897 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9161.67709 | 10535.92866 | 0.76717 | 0.88225 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.86667 | 6.29676E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8981.14862 | 11226.43578 | 0.74688 | 0.93361 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12203.38154 | 14033.88877 | 1.02188 | 1.17516 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 13869.19941 | 17336.49926 | 1.15331 | 1.44164 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10009.14473 | 11510.51644 | 0.83813 | 0.96385 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 28.76000 | 6.29966E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 9123.45855 | 11404.32318 | 0.75875 | 0.94844 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9013.74828 | 10365.81053 | 0.75478 | 0.86800 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 13511.23845 | 16889.04807 | 1.12333 | 1.40417 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11219.45509 | 12902.37336 | 0.93947 | 1.08039 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.50667 | 6.29470E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8908.24170 | 11135.30213 | 0.74072 | 0.92590 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14253.83014 | 16391.90467 | 1.19356 | 1.37259 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 13714.74785 | 17143.43481 | 1.14031 | 1.42538 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11956.02557 | 13749.42941 | 1.00115 | 1.15132 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 9053.44278 | 11316.80348 | 0.75283 | 0.94104 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 88451.79 | 6.71778 | 6.71778 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 40723.72 | 5.66210 | 5.66210 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 85091.68 | 6.43934 | 6.43934 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 40510.84 | 6.64537 | 6.64537 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 101996.88 | 7.89306 | 7.89306 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 39292.98 | 10.16377 | 10.16377 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.81752 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19632 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.14526 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52352 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94071E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86600E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.14526 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21329.55446 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86600E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 484.55063 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.12191 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24006 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.93657 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64017 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58708E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55145E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.94887 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40595.28172 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55145E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 949.26850 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.04853 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18512 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.21456 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49365 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05815E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.35394E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.04853 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 84060.05446 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.35394E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1963.87377 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.83735 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.59889E-002 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55120 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.43080E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.33175E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.83735 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38083.90252 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.33175E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 889.32265 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20097 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.32839E-002 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36029 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.57471E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.17769E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20097 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24892.32504 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17769E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 581.27068 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.86011 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.49368E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55803 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.48569E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.37297E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.86011 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38555.09686 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.37297E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 900.32215 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.26540 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.90385E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37962 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.82043E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.20637E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.21681 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25220.11222 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20637E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 588.92252 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41897 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11134 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42569 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.42188E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.57396E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.41897 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29421.91979 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.57396E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 687.11539 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93361 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10713 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28008 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.55626E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69341E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.93361 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19356.76141 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69341E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 452.04711 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44164 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10959 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43249 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.47655E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.61501E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.44164 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29891.15128 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.61501E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 698.06870 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96385 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10377 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28916 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67172E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72028E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.94844 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19663.86794 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72028E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 459.21594 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.40417 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11252 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42125 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30004 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38618E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.54717E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.40417 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29115.76664 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.54717E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 679.97098 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08039 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.11538E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67948E-004 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.92590 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19197.51582 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67948E-004 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 448.33096 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.42538 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11084 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42761 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.43734E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.58559E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.42538 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29554.93456 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.58559E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 690.22250 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15132 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.68702E-002 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34540 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.38586E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70689E-004 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.94104 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19510.85197 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70689E-004 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 455.64522 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.28780 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.57268 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.57559 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.66210 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.71778 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.71778 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.84285 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.09158 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.45495 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.18317 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 6.64537 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.43934 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 6.64537 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.10618 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.06371 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.21236 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 10.16377 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.89306 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 10.16377 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.71778 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 6.64537 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 10.16377 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.71778 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.71778 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 111203.05776 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.23903 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37063.97915 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 35351.31758 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.09269E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 580.81440 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.71778 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.09269E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.64537 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.64537 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 110004.49122 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.21490 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36664.49692 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 35565.76345 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.11145E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 583.41674 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 6.64537 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.11145E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.16377 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 10.16377 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 168246.51358 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 3.38759 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 56076.56297 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 29615.74394 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.59091E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 509.25440 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 10.16377 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.59091E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.97770E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.59732 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.97770E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1499.06527 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 568981.92168 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 568981.92000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.97770E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20243.07 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 38521.04 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 79765.21 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 36138.16 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23620.55 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 36585.28 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23931.59 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 27918.72 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 18367.80 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 28363.98 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 18659.22 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 27628.20 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 18216.69 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 28044.94 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 18514.02 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 27082.22 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 27157.72 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 24828.70 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 109289.53 | 372911.36 | 11.35 | 2.87 | 3.25 | 3.42 | 3.59 | 9.79 | 11.09 | 11.68 | 12.23 | 6.7954 | 5.3731 | 3.6014 | 1.5164 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 108111.59 | 368892.05 | 11.35 | 2.87 | 3.25 | 3.42 | 3.59 | 9.79 | 11.09 | 11.68 | 12.23 | 6.7221 | 5.3152 | 3.5626 | 1.5000 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 165351.41 | 564202.43 | 11.35 | 2.87 | 3.25 | 3.42 | 3.59 | 9.79 | 11.09 | 11.68 | 12.23 | 10.2812 | 8.1293 | 5.4488 | 2.2942 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 90.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 90.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 71.71 | 136.92 | 71.71 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.44 | 20.44 | 20.44 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 20.43 | 20.43 | 20.43 | 180.00 | 90.00 | 15.82 | 1.29 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 48.45 | 91.28 | 48.45 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 39.32 | 39.32 | 39.32 | 270.00 | 90.00 | 30.84 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 1.55 | 1.55 | 1.55 | 270.00 | 90.00 | 1.22 | 1.28 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 0.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 90.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 75.61 | 136.92 | 75.61 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 61.31 | 61.31 | 61.31 | 180.00 | 90.00 | 49.91 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 50.41 | 91.28 | 50.41 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 40.87 | 40.87 | 40.87 | 270.00 | 90.00 | 33.27 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1407769476 | 0.1114215524 | Pass | Pass | 0.3553061557 | 0.4636450834 | Pass | Fail |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2145093740 | 0.1706625618 | Pass | Pass | 0.5120173513 | 0.6045977946 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.1820740989E-002 | 3.2827547779E-002 | Pass | Pass | 0.3583014550 | 0.6902916302 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.6310473070E-002 | 2.5893912181E-002 | Pass | Pass | 0.8422402146 | 2.0805675066 | Pass | Fail |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.9786156136E-002 | 4.1105890053E-002 | Pass | Pass | 0.2732995390 | 0.4599516608 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.5264203288E-002 | 3.6885137022E-002 | Pass | Pass | 4.5108889839 | 28.2118620457 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3150741463 | 0.3577008360 | Pass | Pass | 6.3040451487 | 19.9124731562 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2587096524 | 0.3395940342 | Pass | Pass | 9.2539668750 | 33.5367161734 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2785639201 | 0.2996742090 | Pass | Pass | 13.3326421889 | 88.2490027842 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3113020893 | 0.3519621741 | Pass | Pass | 11.7782291660 | 40.3660962484 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1841827350 | 0.2052423915 | Pass | Pass | 2.4113649194 | 8.8594299390 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1241066300 | 0.1547869384 | Pass | Pass | 2.3113012978 | 10.1047440223 | Fail | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1521613449 | 0.1251498263 | Pass | Pass | 0.4371294779 | 0.6838037643 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1574723973 | 0.1728856379 | Pass | Pass | 1.3384697122 | 3.0334830508 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1560085276 | 0.2033260780 | Pass | Pass | 0.4626092246 | 1.3985545708 | Fail | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1379821211 | 0.1772412268 | Pass | Pass | 1.1944832157 | 9.8547678161 | Fail | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1595838903 | 0.1521885566 | Pass | Pass | 1.0818325696 | 9.6504548036 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1682714674 | 0.1895514762 | Pass | Pass | 0.3949018734 | 1.0539613941 | Fail | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3710.05 | 182.18 | 0.00 | 2586.64 | 928.49 | 7407.36 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 136.92 | 71.71 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 91.28 | 48.45 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 136.92 | 75.61 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 91.28 | 50.41 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.44 | 0.00 | 0.00 | 20.44 | 20.44 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 20.43 | 0.00 | 0.00 | 20.43 | 20.43 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.39 | 39.32 | 0.00 | 0.00 | 39.32 | 39.32 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.39 | 1.55 | 0.00 | 0.00 | 1.55 | 1.55 | 3.241 | 0.391 | 0.431 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.39 | 61.31 | 0.00 | 0.00 | 61.31 | 61.31 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.39 | 40.87 | 0.00 | 0.00 | 40.87 | 40.87 | 3.241 | 0.391 | 0.431 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 613.07 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 183.92 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 429.15 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 11.0267 | 983.54 | 10845.12 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 111.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 11.0267 | 131.26 | 1447.38 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 11.0267 | 207.34 | 2286.25 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 23.57 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 11.0267 | 131.25 | 1447.29 | LightsWired | LTG_SCH_OFFICE | 56.37 | 168.00 | 54.91 | 0.0000 | Y | 14.92 |
Interior Lighting Total | 11.0267 | 4982.19 | 54936.87 | 566.26 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 15013.15 | AstronomicalClock | - | 83.57 | 83.57 | 235.51 | |
Exterior Lighting Total | 15013.15 | 235.51 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 568981.92 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 111203.06 | 89035.31 | 22167.74 | 0.80 | 3.50 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 110004.49 | 88075.67 | 21928.82 | 0.80 | 3.50 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 168246.51 | 134707.46 | 33539.06 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 109289.5 | 2.87 | 9.79 | N/A | N/A | 11.35 | |
PACU_VAV_MID COOLING COIL | 108111.6 | 2.87 | 9.79 | N/A | N/A | 11.35 | |
PACU_VAV_TOP COOLING COIL | 165351.4 | 2.87 | 9.79 | N/A | N/A | 11.35 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 21329.55 | 20243.07 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 40595.28 | 38521.04 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 84060.05 | 79765.21 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 38083.90 | 36138.16 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 24892.33 | 23620.55 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 38555.10 | 36585.28 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 25220.11 | 23931.59 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 29421.92 | 27918.72 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19356.76 | 18367.80 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29891.15 | 28363.98 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 19663.87 | 18659.22 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 29115.77 | 27628.20 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19197.52 | 18216.69 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29554.93 | 28044.94 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 19510.85 | 18514.02 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 35351.32 | 27082.22 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 35565.76 | 27157.72 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 29615.74 | 24828.70 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.72 | 14764.20 | 2197.78 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.65 | 14605.07 | 2197.78 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.61 | 1337.13 | 10.16 | 22219.05 | 2186.10 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004978 | 1499.07 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 109289.53 | 2.87 | 9.79 | 11.35 | 6.7954 | 3.25 | 11.09 | 5.3731 | 3.42 | 11.68 | 3.6014 | 3.59 | 12.23 | 1.5164 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 108111.59 | 2.87 | 9.79 | 11.35 | 6.7221 | 3.25 | 11.09 | 5.3152 | 3.42 | 11.68 | 3.5626 | 3.59 | 12.23 | 1.5000 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 165351.41 | 2.87 | 9.79 | 11.35 | 10.2812 | 3.25 | 11.09 | 8.1293 | 3.42 | 11.68 | 5.4488 | 3.59 | 12.23 | 2.2942 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 39962.32 | 45956.67 | 46.73 | 3.320 | 3.818 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_MID | 32703.80 | 37609.37 | 38.24 | 2.715 | 3.122 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00887 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_TOP | 37165.92 | 42740.81 | 43.46 | 3.112 | 3.579 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00882 | 32.92 | 0.00631 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10952.77 | 12595.68 | 60.75 | 0.917 | 1.055 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00864 | 33.08 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11271.67 | 12962.42 | 98.75 | 0.944 | 1.085 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00858 | 26.41 | 0.00630 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16069.89 | 18480.37 | 89.13 | 1.346 | 1.547 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00860 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 13140.80 | 15111.92 | 115.14 | 1.100 | 1.265 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00857 | 30.63 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7759.52 | 8923.45 | 43.04 | 0.650 | 0.747 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00875 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9161.68 | 10535.93 | 80.27 | 0.767 | 0.882 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00863 | 26.87 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12203.38 | 14033.89 | 67.69 | 1.022 | 1.175 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00866 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10009.14 | 11510.52 | 87.70 | 0.838 | 0.964 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00862 | 28.76 | 0.00630 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9013.75 | 10365.81 | 49.99 | 0.755 | 0.868 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00869 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11219.46 | 12902.37 | 98.29 | 0.939 | 1.080 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00859 | 25.51 | 0.00629 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14253.83 | 16391.90 | 79.06 | 1.194 | 1.373 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00862 | 33.13 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11956.03 | 13749.43 | 104.75 | 1.001 | 1.151 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00859 | 30.36 | 0.00630 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9083.04 | 11353.81 | 11.54 | 0.761 | 0.952 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_MID | 18895.69 | 23619.61 | 24.01 | 1.559 | 1.949 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_TOP | 39036.25 | 48795.31 | 49.61 | 3.239 | 4.049 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 17668.16 | 22085.20 | 106.52 | 1.470 | 1.837 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11547.96 | 14434.95 | 109.97 | 0.961 | 1.201 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17886.53 | 22358.16 | 107.83 | 1.488 | 1.860 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11699.87 | 14624.84 | 111.42 | 0.973 | 1.217 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 13651.76 | 17064.71 | 82.30 | 1.135 | 1.419 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8981.15 | 11226.44 | 85.53 | 0.747 | 0.934 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 13869.20 | 17336.50 | 83.61 | 1.153 | 1.442 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9123.46 | 11404.32 | 86.89 | 0.759 | 0.948 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 13511.24 | 16889.05 | 81.46 | 1.123 | 1.404 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8908.24 | 11135.30 | 84.83 | 0.741 | 0.926 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13714.75 | 17143.43 | 82.68 | 1.140 | 1.425 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9053.44 | 11316.80 | 86.22 | 0.753 | 0.941 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.72 | 6.72 | 5.66 | 5.66 | 6.7178 | 5.6621 | 6.7178 | 0.8429 | 0.3000 |
PACU_VAV_MID | 6.44 | 6.44 | 6.65 | 6.65 | 6.4393 | 6.6454 | 6.6454 | 1.0000 | 0.3000 |
PACU_VAV_TOP | 7.89 | 7.89 | 10.16 | 10.16 | 7.8931 | 10.1638 | 10.1638 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21329.554 | 21329.554 | 1.145255 | 0.00018660 | 484.551 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21329.55 | 21329.55 | 1.145255 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 11353.81 | 0.00 | 21429.82 | 21429.82 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 40595.282 | 40595.282 | 1.948874 | 0.00035515 | 949.269 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40595.28 | 40595.28 | 1.948874 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 23619.61 | 0.00 | 40781.32 | 40781.32 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 84060.054 | 84060.054 | 4.048532 | 0.00073539 | 1963.874 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 84060.05 | 83572.63 | 4.048532 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 48795.31 | 0.00 | 84445.42 | 84445.42 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 38083.903 | 38083.903 | 1.837349 | 0.00033317 | 889.323 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38083.90 | 37927.85 | 1.837349 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00787074 | 44.5117 | 22085.20 | 0.00 | 38258.53 | 38258.53 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 24892.325 | 24892.325 | 1.200974 | 0.00021777 | 581.271 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24892.33 | 24791.35 | 1.200974 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00786814 | 44.4973 | 14434.95 | 0.00 | 25006.46 | 25006.46 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 38555.097 | 38555.097 | 1.860110 | 0.00033730 | 900.322 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38555.10 | 38397.68 | 1.860110 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00787230 | 44.5204 | 22358.16 | 0.00 | 38731.88 | 38731.88 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 25220.112 | 25220.112 | 1.216807 | 0.00022064 | 588.923 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25220.11 | 25220.11 | 1.216807 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00786983 | 44.5067 | 14624.84 | 0.00 | 25335.75 | 25335.75 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 29421.920 | 29421.920 | 1.418973 | 0.00025740 | 687.115 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29421.92 | 29291.44 | 1.418973 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00791158 | 44.7387 | 17064.71 | 0.00 | 29556.82 | 29556.82 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 19356.761 | 19356.761 | 0.933606 | 0.00016934 | 452.047 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19356.76 | 19272.15 | 0.933606 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00791034 | 44.7318 | 11226.44 | 0.00 | 19445.51 | 19445.51 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 29891.151 | 29891.151 | 1.441641 | 0.00026150 | 698.069 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29891.15 | 29759.37 | 1.441641 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00791294 | 44.7463 | 17336.50 | 0.00 | 30028.21 | 30028.21 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 19663.868 | 19663.868 | 0.948442 | 0.00017203 | 459.216 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19663.87 | 19663.87 | 0.948442 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00791171 | 44.7395 | 11404.32 | 0.00 | 19754.03 | 19754.03 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 29115.767 | 29115.767 | 1.404168 | 0.00025472 | 679.971 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29115.77 | 28985.81 | 1.404168 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00786028 | 44.4530 | 16889.05 | 0.00 | 29249.26 | 29249.26 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 19197.516 | 19197.516 | 0.925905 | 0.00016795 | 448.331 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19197.52 | 19197.52 | 0.925905 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785864 | 44.4439 | 11135.30 | 0.00 | 19285.54 | 19285.54 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 29554.935 | 29554.935 | 1.425383 | 0.00025856 | 690.223 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29554.93 | 29423.76 | 1.425383 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00786230 | 44.4643 | 17143.43 | 0.00 | 29690.45 | 29690.45 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 19510.852 | 19510.852 | 0.941041 | 0.00017069 | 455.645 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19510.85 | 19510.85 | 0.941041 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00786085 | 44.4563 | 11316.80 | 0.00 | 19600.31 | 19600.31 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 111203.058 | 89035.313 | 6.717777 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 108697.14 | 108697.14 | 6.717777 | 25.34 | 15.40 | 0.00841264 | 10.84 | 10.02 | 0.00841264 | 33.40 | 0.00630683 | 16.37 | 14.2324 | 24.00 | 0.00876230 | 41.2380 | 69721.38 | 0.00 | 114665.28 | 84485.58 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 35351.318 | 35351.318 | 2.015333 | 0.00030927 | 580.814 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:20:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35351.32 | 35351.32 | 2.015333 | -3.69 | -3.69 | 0.00424687 | 12.89 | 10.44 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 47.4413 | 18.60 | 0.00788518 | 51.7624 | 8184.66 | 0.00 | 32769.23 | 32769.23 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 110004.491 | 88075.675 | 6.645371 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 107525.58 | 107525.58 | 6.645371 | 25.40 | 15.41 | 0.00839475 | 10.84 | 10.00 | 0.00839475 | 33.40 | 0.00630683 | 16.37 | 14.3875 | 24.00 | 0.00875955 | 41.2249 | 66753.76 | 0.00 | 113429.40 | 83574.97 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 35565.763 | 35565.763 | 1.993611 | 0.00031114 | 583.417 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:20:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35565.76 | 35565.76 | 1.993611 | -3.97 | -3.97 | 0.00414317 | 12.89 | 10.44 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 47.9582 | 17.79 | 0.00783806 | 54.1378 | 8776.25 | 0.00 | 32859.49 | 32859.49 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 168246.514 | 134707.456 | 10.163772 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 164656.41 | 164656.41 | 10.163772 | 25.12 | 15.33 | 0.00841448 | 10.85 | 10.03 | 0.00841448 | 33.24 | 0.00630658 | 16.31 | 9.4069 | 24.00 | 0.00870555 | 40.9742 | 81827.84 | 0.00 | 173484.74 | 127823.86 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 29615.744 | 29615.744 | 3.049132 | 0.00025909 | 509.254 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29615.74 | 29615.74 | 3.049132 | 3.71 | 3.40 | 0.00539330 | 12.89 | 10.44 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 31.3565 | 16.54 | 0.00788807 | 58.9526 | 11912.99 | 0.00 | 30054.24 | 30054.24 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 21329.554 | 21329.554 | 1.145255 | 0.00018660 | 484.551 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 3.6748 | 3.748723 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 21329.55 | 21329.55 | 1.0000 | 1.20611406 | 1.145255 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.18658121 | 60.00 | 32.22 | 27.78 | 0.000 | 21329.55 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 11353.81 | 0.00 | 21429.82 | 21429.82 | 1.20611406 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.22 | 18.11 | 0.00800000 | 50827.5 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 40595.282 | 40595.282 | 1.948874 | 0.00035515 | 949.269 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 6.9940 | 7.134723 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40595.28 | 40595.28 | 1.0000 | 2.05243737 | 1.948874 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.35510901 | 60.00 | 32.22 | 27.78 | 0.000 | 40595.28 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 23619.61 | 0.00 | 40781.32 | 40781.32 | 2.05243737 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.29 | 18.79 | 0.00800000 | 52929.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 84060.054 | 84060.054 | 4.048532 | 0.00073539 | 1963.874 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 14.4823 | 14.773765 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 84060.05 | 83572.63 | 1.0000 | 4.26367013 | 4.048532 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.73531901 | 60.00 | 32.22 | 27.78 | 0.000 | 84060.05 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 48795.31 | 0.00 | 84445.42 | 84445.42 | 4.26367013 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.22 | 18.77 | 0.00800000 | 52865.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38083.903 | 38083.903 | 1.837349 | 0.00033317 | 889.323 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 6.5613 | 6.693341 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38083.90 | 37927.85 | 1.0000 | 1.93498597 | 1.837349 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.33314061 | 60.00 | 32.22 | 27.78 | 0.000 | 38083.90 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00787074 | 21.00 | 0.00787074 | 44.5117 | 22085.20 | 0.00 | 38258.53 | 38258.53 | 1.93498597 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52831.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24892.325 | 24892.325 | 1.200974 | 0.00021777 | 581.271 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 4.2886 | 4.374889 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24892.33 | 24791.35 | 1.0000 | 1.26479382 | 1.200974 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.21774670 | 60.00 | 32.22 | 27.78 | 0.000 | 24892.33 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00786814 | 21.00 | 0.00786814 | 44.4973 | 14434.95 | 0.00 | 25006.46 | 25006.46 | 1.26479382 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52831.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38555.097 | 38555.097 | 1.860110 | 0.00033730 | 900.322 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 6.6425 | 6.776155 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38555.10 | 38397.68 | 1.0000 | 1.95895553 | 1.860110 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.33726240 | 60.00 | 32.22 | 27.78 | 0.000 | 38555.10 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00787230 | 21.00 | 0.00787230 | 44.5204 | 22358.16 | 0.00 | 38731.88 | 38731.88 | 1.95895553 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52831.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25220.112 | 25220.112 | 1.216807 | 0.00022064 | 588.923 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 4.3451 | 4.432498 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25220.11 | 25220.11 | 1.0000 | 1.28146805 | 1.216807 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.22061404 | 60.00 | 32.22 | 27.78 | 0.000 | 25220.11 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00786983 | 21.00 | 0.00786983 | 44.5067 | 14624.84 | 0.00 | 25335.75 | 25335.75 | 1.28146805 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52830.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29421.920 | 29421.920 | 1.418973 | 0.00025740 | 687.115 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 5.0690 | 5.170976 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29421.92 | 29291.44 | 1.0000 | 1.49437758 | 1.418973 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.25736953 | 60.00 | 32.22 | 27.78 | 0.000 | 29421.92 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791158 | 21.00 | 0.00791158 | 44.7387 | 17064.71 | 0.00 | 29556.82 | 29556.82 | 1.49437758 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19356.761 | 19356.761 | 0.933606 | 0.00016934 | 452.047 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 3.3349 | 3.401999 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19356.76 | 19272.15 | 1.0000 | 0.98321771 | 0.933606 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.16932412 | 60.00 | 32.22 | 27.78 | 0.000 | 19356.76 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00791034 | 21.00 | 0.00791034 | 44.7318 | 11226.44 | 0.00 | 19445.51 | 19445.51 | 0.98321771 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29891.151 | 29891.151 | 1.441641 | 0.00026150 | 698.069 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 5.1498 | 5.253445 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29891.15 | 29759.37 | 1.0000 | 1.51825012 | 1.441641 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.26147416 | 60.00 | 32.22 | 27.78 | 0.000 | 29891.15 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00791294 | 21.00 | 0.00791294 | 44.7463 | 17336.50 | 0.00 | 30028.21 | 30028.21 | 1.51825012 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19663.868 | 19663.868 | 0.948442 | 0.00017203 | 459.216 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 3.3878 | 3.455974 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19663.87 | 19663.87 | 1.0000 | 0.99884188 | 0.948442 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.17201055 | 60.00 | 32.22 | 27.78 | 0.000 | 19663.87 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00791171 | 21.00 | 0.00791171 | 44.7395 | 11404.32 | 0.00 | 19754.03 | 19754.03 | 0.99884188 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.19 | 18.76 | 0.00800000 | 52836.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29115.767 | 29115.767 | 1.404168 | 0.00025472 | 679.971 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 5.0162 | 5.117169 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29115.77 | 28985.81 | 1.0000 | 1.47878495 | 1.404168 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.25469144 | 60.00 | 32.22 | 27.78 | 0.000 | 29115.77 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00786028 | 21.00 | 0.00786028 | 44.4530 | 16889.05 | 0.00 | 29249.26 | 29249.26 | 1.47878495 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52839.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19197.516 | 19197.516 | 0.925905 | 0.00016795 | 448.331 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 3.3074 | 3.374012 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19197.52 | 19197.52 | 1.0000 | 0.97510708 | 0.925905 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.16793111 | 60.00 | 32.22 | 27.78 | 0.000 | 19197.52 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00785864 | 21.00 | 0.00785864 | 44.4439 | 11135.30 | 0.00 | 19285.54 | 19285.54 | 0.97510708 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29554.935 | 29554.935 | 1.425383 | 0.00025856 | 690.223 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 5.0919 | 5.194354 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29554.93 | 29423.76 | 1.0000 | 1.50112803 | 1.425383 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.25853308 | 60.00 | 32.22 | 27.78 | 0.000 | 29554.93 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00786230 | 21.00 | 0.00786230 | 44.4643 | 17143.43 | 0.00 | 29690.45 | 29690.45 | 1.50112803 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52838.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19510.852 | 19510.852 | 0.941041 | 0.00017069 | 455.645 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 3.3614 | 3.429081 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19510.85 | 19510.85 | 1.0000 | 0.99104812 | 0.941041 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.17067203 | 60.00 | 32.22 | 27.78 | 0.000 | 19510.85 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.94 | 0.00786085 | 21.00 | 0.00786085 | 44.4563 | 11316.80 | 0.00 | 19600.31 | 19600.31 | 0.99104812 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.20 | 18.76 | 0.00800000 | 52837.2 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 111203.058 | 89035.313 | 6.717777 | -999.0 | -999.000 | -999.0000 | 1.06717 | 1.00000 | 1020.4787 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.717777 | 7.07475857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 108697.14 | 108697.14 | 0.9775 | 7.07475857 | 6.717777 | 25.34 | 15.40 | 0.00841264 | 46896.0 | 10.84 | 10.02 | 0.00841264 | 32105.5 | -999.0 | -999.00 | -999.00 | -999.00 | 14764.202 | 93932.93 | 33.40 | 0.00630683 | 16.37 | 0.95610000 | 14.2324 | 24.00 | 0.00876230 | 24.00 | 0.00876230 | 41.2380 | 69721.38 | 0.00 | 114665.28 | 84485.58 | 6.79535909 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 35351.318 | 35351.318 | 2.015333 | 0.00030927 | 580.814 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.717777 | 7.07475857 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 6.0905 | 6.213083 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:20:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35351.32 | 35351.32 | 1.0000 | 2.12242757 | 2.015333 | -3.69 | -3.69 | 0.00424687 | 6887.6 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 0.30923720 | 60.00 | 32.22 | 27.78 | 0.000 | 35351.32 | -27.60 | 0.00034190 | -27.60 | 0.95610000 | 47.4413 | 17.90 | 0.00777164 | 18.60 | 0.00788518 | 51.7624 | 8184.66 | 0.00 | 32769.23 | 32769.23 | 2.12242757 | 2.80 | 2.29 | 0.00424687 | 13456.8 | 18.05 | 9.90 | 0.00424687 | 28896.3 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 110004.491 | 88075.675 | 6.645371 | -999.0 | -999.000 | -999.0000 | 1.06300 | 1.00000 | 1020.4454 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.645371 | 6.99850555 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 107525.58 | 107525.58 | 0.9775 | 6.99850555 | 6.645371 | 25.40 | 15.41 | 0.00839475 | 46911.3 | 10.84 | 10.00 | 0.00839475 | 32060.3 | -999.0 | -999.00 | -999.00 | -999.00 | 14605.071 | 92920.51 | 33.40 | 0.00630683 | 16.37 | 0.95610000 | 14.3875 | 24.00 | 0.00875955 | 24.00 | 0.00875955 | 41.2249 | 66753.76 | 0.00 | 113429.40 | 83574.97 | 6.72211748 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 35565.763 | 35565.763 | 1.993611 | 0.00031114 | 583.417 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 6.645371 | 6.99850555 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 6.1275 | 6.250772 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:20:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35565.76 | 35565.76 | 1.0000 | 2.09955166 | 1.993611 | -3.97 | -3.97 | 0.00414317 | 6343.2 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 0.31111307 | 60.00 | 32.22 | 27.78 | 0.000 | 35565.76 | -27.60 | 0.00034190 | -27.60 | 0.95610000 | 47.9582 | 17.81 | 0.00764617 | 17.79 | 0.00783806 | 54.1378 | 8776.25 | 0.00 | 32859.49 | 32859.49 | 2.09955166 | 2.80 | 2.14 | 0.00414317 | 13196.9 | 18.26 | 9.88 | 0.00414317 | 28847.7 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 168246.514 | 134707.456 | 10.163772 | -999.0 | -999.000 | -999.0000 | 1.08484 | 1.00000 | 1020.4821 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 10.163772 | 10.70387350 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 164656.41 | 164656.41 | 0.9787 | 10.70387350 | 10.163772 | 25.12 | 15.33 | 0.00841448 | 46678.9 | 10.85 | 10.03 | 0.00841448 | 32121.2 | -999.0 | -999.00 | -999.00 | -999.00 | 22219.054 | 142437.35 | 33.24 | 0.00630658 | 16.31 | 0.95610000 | 9.4069 | 24.00 | 0.00870555 | 24.00 | 0.00870555 | 40.9742 | 81827.84 | 0.00 | 173484.74 | 127823.86 | 10.28115142 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 29615.744 | 29615.744 | 3.049132 | 0.00025909 | 509.254 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 10.163772 | 10.70387350 | 4197.9300 | 999.8980 | 4.97719429 | 54.44 | 82.22 | 27.78 | 580432.91 | 5.1024 | 5.205041 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29615.74 | 29615.74 | 1.0000 | 3.21116205 | 3.049132 | 3.71 | 3.40 | 0.00539330 | 17254.2 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 0.25906502 | 60.00 | 32.22 | 27.78 | 0.000 | 29615.74 | -27.60 | 0.00034190 | -27.60 | 0.95610000 | 31.3565 | 18.01 | 0.00770078 | 16.54 | 0.00788807 | 58.9526 | 11912.99 | 0.00 | 30054.24 | 30054.24 | 3.21116205 | 2.80 | 2.80 | 0.00539330 | 16329.9 | 12.02 | 8.44 | 0.00539330 | 25689.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.72 | - | |||
PACU_VAV_MID_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.65 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | FixedDryBulb | 0.00 | 10.16 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1361.67 | 3254.00 | 176.83 |
CORE_MID | 1467.17 | 4275.67 | 793.17 |
CORE_TOP | 2428.00 | 4776.00 | 1894.17 |
PERIMETER_TOP_ZN_3 | 3271.67 | 5234.33 | 2854.33 |
PERIMETER_TOP_ZN_2 | 3438.50 | 4674.00 | 2523.33 |
PERIMETER_TOP_ZN_1 | 3082.33 | 4580.67 | 2162.17 |
PERIMETER_TOP_ZN_4 | 3351.50 | 4901.67 | 2623.17 |
PERIMETER_BOT_ZN_3 | 3018.50 | 5439.67 | 2808.67 |
PERIMETER_BOT_ZN_2 | 3268.50 | 4620.17 | 2350.17 |
PERIMETER_BOT_ZN_1 | 2726.17 | 4669.50 | 1924.33 |
PERIMETER_BOT_ZN_4 | 3095.17 | 4841.50 | 2407.83 |
PERIMETER_MID_ZN_3 | 2888.83 | 4967.67 | 2354.67 |
PERIMETER_MID_ZN_2 | 2640.67 | 3882.17 | 1859.17 |
PERIMETER_MID_ZN_1 | 2724.00 | 4185.50 | 1655.67 |
PERIMETER_MID_ZN_4 | 2933.00 | 4757.17 | 2151.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4900.33 | 5510.50 | 3177.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 4.17 | 0.00 | 3.83 | 0.00 |
CORE_TOP | 12.83 | 0.00 | 7.17 | 0.00 |
PERIMETER_TOP_ZN_3 | 162.00 | 0.00 | 52.67 | 0.00 |
PERIMETER_TOP_ZN_2 | 156.67 | 4.83 | 45.67 | 4.83 |
PERIMETER_TOP_ZN_1 | 125.50 | 6.00 | 33.33 | 6.00 |
PERIMETER_TOP_ZN_4 | 158.67 | 11.83 | 47.17 | 6.17 |
PERIMETER_BOT_ZN_3 | 63.83 | 0.00 | 28.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 59.33 | 3.50 | 23.00 | 3.50 |
PERIMETER_BOT_ZN_1 | 413.00 | 4.50 | 384.33 | 4.33 |
PERIMETER_BOT_ZN_4 | 60.83 | 6.17 | 24.00 | 3.17 |
PERIMETER_MID_ZN_3 | 73.33 | 0.00 | 26.67 | 0.00 |
PERIMETER_MID_ZN_2 | 69.83 | 7.83 | 19.67 | 7.83 |
PERIMETER_MID_ZN_1 | 53.83 | 7.83 | 15.83 | 7.67 |
PERIMETER_MID_ZN_4 | 69.83 | 10.83 | 20.00 | 5.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 616.33 | 45.17 | 441.33 | 35.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.963 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.668 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.722 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 1.470 | 0.113 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.659 | 0.119 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 1.626 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.688 | 0.119 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 1.222 | 0.060 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 1.400 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 1.371 | 0.881 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 1.367 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 1.240 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 1.578 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 1.493 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.691 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15305235.51 | 0.00 | 15305235.51 | 0.00 | 15305235.51 | 13393058.27 | 5640.28 | 69.61 | 3050.10 | 192.86 |
CORE_MID | 10662384.88 | 0.00 | 10662384.88 | 0.00 | 10662384.88 | 13393058.27 | 6406.40 | 39.43 | 2314.17 | 237.98 |
CORE_TOP | 11492770.96 | 0.00 | 11492770.96 | 0.00 | 11492770.96 | 13393058.27 | 6165.98 | 32.09 | 2561.93 | 55.65 |
PERIMETER_TOP_ZN_3 | 4953345.92 | 0.00 | 4953345.92 | 759318.16 | 5712664.09 | 2823374.22 | 4195.55 | 17.83 | 4546.62 | 55.65 |
PERIMETER_TOP_ZN_2 | 3529554.19 | 0.00 | 3529554.19 | 506209.06 | 4035763.25 | 1787429.43 | 4162.50 | 3.04 | 4594.46 | 55.65 |
PERIMETER_TOP_ZN_1 | 5463887.90 | 0.00 | 5463887.90 | 759318.16 | 6223206.06 | 2823374.22 | 4164.75 | 2.31 | 4592.93 | 55.65 |
PERIMETER_TOP_ZN_4 | 3596743.40 | 0.00 | 3596743.40 | 506209.06 | 4102952.46 | 1787312.18 | 4156.25 | 4.32 | 4599.43 | 55.65 |
PERIMETER_BOT_ZN_3 | 4140319.07 | 0.00 | 4140319.07 | 403724.27 | 4544043.34 | 2823374.22 | 4438.41 | 14.55 | 4307.04 | 192.86 |
PERIMETER_BOT_ZN_2 | 2991313.97 | 0.00 | 2991313.97 | 269147.90 | 3260461.86 | 1787429.43 | 4119.38 | 13.89 | 4626.74 | 192.86 |
PERIMETER_BOT_ZN_1 | 4632854.76 | 0.00 | 4632854.76 | 3161469.32 | 7794324.09 | 2823374.22 | 4095.89 | 8.16 | 4655.94 | 192.86 |
PERIMETER_BOT_ZN_4 | 2924978.89 | 0.00 | 2924978.89 | 269147.90 | 3194126.78 | 1787312.18 | 4185.24 | 12.55 | 4562.21 | 192.86 |
PERIMETER_MID_ZN_3 | 4196784.17 | 0.00 | 4196784.17 | 632073.14 | 4828857.31 | 2823374.22 | 4145.28 | 17.31 | 4597.41 | 237.98 |
PERIMETER_MID_ZN_2 | 3200195.37 | 0.00 | 3200195.37 | 421379.56 | 3621574.94 | 1601953.02 | 4053.49 | 2.21 | 4704.30 | 1146.98 |
PERIMETER_MID_ZN_1 | 5031184.49 | 0.00 | 5031184.49 | 632073.14 | 5663257.63 | 2823374.22 | 4080.60 | 4.65 | 4674.75 | 237.98 |
PERIMETER_MID_ZN_4 | 3619419.26 | 0.00 | 3619419.26 | 421379.56 | 4040798.82 | 1787312.18 | 4048.42 | 9.38 | 4702.21 | 237.98 |
Total Facility | 85740972.74 | 0.00 | 85740972.74 | 8741449.25 | 94482421.99 | 67658168.57 | 6488.03 | 228.98 | 4766.15 | 1219.59 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7089 | 0.0000 | 0.7089 | 0.0000 | 0.7089 | 0.4247 | 2835.83 | 69.28 | 3037.90 |
CORE_MID | 0.4927 | 0.0000 | 0.4927 | 0.0000 | 0.4927 | 0.4247 | 3607.16 | 39.43 | 2296.40 |
CORE_TOP | 0.5334 | 0.0000 | 0.5334 | 0.0000 | 0.5334 | 0.4247 | 3365.92 | 32.09 | 2544.99 |
PERIMETER_TOP_ZN_3 | 0.2298 | 0.0000 | 0.2298 | 0.0178 | 0.2476 | 0.0895 | 1395.82 | 17.83 | 4529.34 |
PERIMETER_TOP_ZN_2 | 0.1638 | 0.0000 | 0.1638 | 0.0119 | 0.1757 | 0.0567 | 1362.78 | 3.04 | 4577.18 |
PERIMETER_TOP_ZN_1 | 0.2536 | 0.0000 | 0.2536 | 0.0178 | 0.2714 | 0.0895 | 1365.03 | 2.31 | 4575.66 |
PERIMETER_TOP_ZN_4 | 0.1669 | 0.0000 | 0.1669 | 0.0119 | 0.1788 | 0.0567 | 1356.53 | 4.32 | 4582.15 |
PERIMETER_BOT_ZN_3 | 0.1911 | 0.0000 | 0.1911 | 0.0095 | 0.2006 | 0.0895 | 1648.43 | 13.52 | 4281.05 |
PERIMETER_BOT_ZN_2 | 0.1382 | 0.0000 | 0.1382 | 0.0063 | 0.1445 | 0.0567 | 1331.32 | 12.66 | 4599.02 |
PERIMETER_BOT_ZN_1 | 0.2141 | 0.0000 | 0.2141 | 0.1384 | 0.3525 | 0.0895 | 1306.09 | 7.25 | 4629.66 |
PERIMETER_BOT_ZN_4 | 0.1351 | 0.0000 | 0.1351 | 0.0063 | 0.1414 | 0.0567 | 1400.45 | 10.13 | 4532.42 |
PERIMETER_MID_ZN_3 | 0.1936 | 0.0000 | 0.1936 | 0.0148 | 0.2084 | 0.0895 | 1350.75 | 16.99 | 4575.27 |
PERIMETER_MID_ZN_2 | 0.1558 | 0.0000 | 0.1558 | 0.0105 | 0.1663 | 0.0567 | 1266.93 | 1.65 | 3765.41 |
PERIMETER_MID_ZN_1 | 0.2326 | 0.0000 | 0.2326 | 0.0148 | 0.2474 | 0.0895 | 1286.08 | 4.16 | 4652.76 |
PERIMETER_MID_ZN_4 | 0.1671 | 0.0000 | 0.1671 | 0.0099 | 0.1769 | 0.0567 | 1267.18 | 7.28 | 4668.54 |
Total Facility | 3.9768 | 0.0000 | 3.9768 | 0.2698 | 4.2465 | 2.1513 | 3676.63 | 221.50 | 4716.35 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 33267232.40 | 0.00 | 33267232.40 | 22614548.33 | 4111.85 | 2.32 | 4645.83 | 192.86 |
PACU_VAV_MID | 29624122.04 | 0.00 | 29624122.04 | 22429071.92 | 4110.65 | 2.86 | 4646.49 | 237.98 |
PACU_VAV_TOP | 32204267.69 | 0.00 | 32204267.69 | 22614548.33 | 4197.55 | 3.05 | 4559.40 | 55.65 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5388 | 0.0000 | 1.5388 | 0.7171 | 1312.98 | 2.02 | 4628.00 |
PACU_VAV_MID | 1.3681 | 0.0000 | 1.3681 | 0.7084 | 1311.62 | 2.86 | 4628.52 |
PACU_VAV_TOP | 1.4946 | 0.0000 | 1.4946 | 0.7171 | 1397.83 | 3.05 | 4542.12 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 20.38 | 3710.01 | 0.00 | 0.00 | 0.00 | 1194.67 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 34.12 | 3331.14 | 0.00 | 0.00 | 0.00 | 1653.19 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 24.17 | 3284.78 | 0.00 | 0.00 | 0.00 | 1464.61 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.9876 | 2.2989 | 0.0000 | 0.0000 | 0.0000 | 0.8713 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.9882 | 2.1261 | 0.0000 | 0.0000 | 0.0000 | 0.9208 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0041 | 2.3399 | 0.0000 | 0.0000 | 0.0000 | 0.8904 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 873 |
Defaulted Fields | 578 |
Fields with Defaults | 2253 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1942.08 | 15934.24 | 12-MAR-17:10 | 217289.80 | 17-JUL-16:00 |
Electricity:Building | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 371.79 | 5897.80 | 01-JAN-00:10 | 24018.11 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1295.53 | 15548.59 | 01-JAN-00:10 | 91380.19 | 02-JAN-08:10 |
InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 566.26 | 2746.84 | 01-JAN-00:10 | 49443.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 227.21 | 2373.80 | 01-JAN-00:10 | 16568.93 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 111.79 | 542.26 | 01-JAN-00:10 | 9760.61 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 47.90 | 500.42 | 01-JAN-00:10 | 3492.87 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 30.32 | 316.79 | 01-JAN-00:10 | 2211.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.92 | 72.37 | 01-JAN-00:10 | 1302.65 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 47.90 | 500.41 | 01-JAN-00:10 | 3492.86 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.57 | 114.31 | 01-JAN-00:10 | 2057.62 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 30.32 | 316.78 | 01-JAN-00:10 | 2211.13 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.92 | 72.36 | 01-JAN-00:10 | 1302.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 260.00 | 5355.54 | 01-JAN-00:10 | 14257.50 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 729.27 | 12801.75 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 347.69 | 385.65 | 04-MAR-05:40 | 121549.55 | 17-JUL-16:00 |
ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 27.50 | 383.73 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 1942.08 | 15934.24 | 12-MAR-17:10 | 217289.80 | 17-JUL-16:00 |
ElectricityPurchased:Plant | 1942.08 | 15934.24 | 12-MAR-17:10 | 217289.80 | 17-JUL-16:00 |
Cogeneration:ElectricityPurchased | 1942.08 | 15934.24 | 12-MAR-17:10 | 217289.80 | 17-JUL-16:00 |
General:Cogeneration:ElectricityPurchased | 1942.08 | 15934.24 | 12-MAR-17:10 | 217289.80 | 17-JUL-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1942.08 | 15934.24 | 12-MAR-17:10 | 217289.80 | 17-JUL-16:00 |
ElectricityNet:Plant | 1942.08 | 15934.24 | 12-MAR-17:10 | 217289.80 | 17-JUL-16:00 |
Cogeneration:ElectricityNet | 1942.08 | 15934.24 | 12-MAR-17:10 | 217289.80 | 17-JUL-16:00 |
General:Cogeneration:ElectricityNet | 1942.08 | 15934.24 | 12-MAR-17:10 | 217289.80 | 17-JUL-16:00 |
Fans:Electricity | 192.57 | 0.00 | 01-JAN-10:10 | 35214.68 | 17-JUL-16:00 |
General:Fans:Electricity | 192.57 | 0.00 | 01-JAN-10:10 | 35214.68 | 17-JUL-16:00 |
ExteriorLights:Electricity | 235.51 | 0.00 | 01-JAN-08:20 | 15013.15 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 235.51 | 0.00 | 01-JAN-08:20 | 15013.15 | 01-JAN-00:10 |
Cooling:Electricity | 127.62 | 0.00 | 01-JAN-00:10 | 84924.58 | 17-JUL-16:00 |
General:Cooling:Electricity | 127.62 | 0.00 | 01-JAN-00:10 | 84924.58 | 17-JUL-16:00 |
Electricity:Plant | 63.35 | 0.00 | 01-JAN-18:30 | 8432.48 | 09-JAN-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 59.06 | 0.00 | 01-JAN-00:10 | 7227.62 | 21-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 59.06 | 0.00 | 01-JAN-00:10 | 7227.62 | 21-FEB-13:00 |
Pumps:Electricity | 4.29 | 0.00 | 01-JAN-18:30 | 1517.68 | 09-JAN-07:30 |
General:Pumps:Electricity | 4.29 | 0.00 | 01-JAN-18:30 | 1517.68 | 09-JAN-07:30 |
WIRED_LTG_ELECTRICITY | 15.91 | 0.00 | 01-JAN-00:10 | 1389.35 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 690.40 | 12801.75 | 01-JAN-00:10 | 37819.83 | 02-JAN-09:10 |
WIRED_INT_EQUIP2 | 633.77 | 9601.75 | 01-JAN-00:10 | 39373.07 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 835.38 | 0.00 | 01-JAN-10:10 | 385302.60 | 09-JAN-07:20 |
NaturalGas:Plant | 835.38 | 0.00 | 01-JAN-10:10 | 385302.60 | 09-JAN-07:20 |
Heating:NaturalGas | 835.38 | 0.00 | 01-JAN-10:10 | 385302.60 | 09-JAN-07:20 |
Boiler:Heating:NaturalGas | 835.38 | 0.00 | 01-JAN-10:10 | 385302.60 | 09-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2991.09 | 0.00 | 01-JAN-18:30 | 767375.72 | 09-JAN-07:20 |
EnergyTransfer:Building | 1339.57 | 0.00 | 01-JAN-10:10 | 215112.53 | 09-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 230.11 | 0.00 | 01-JAN-00:10 | 26367.76 | 05-SEP-15:00 |
Heating:EnergyTransfer | 309.25 | 0.00 | 01-JAN-10:10 | 214653.82 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.07 | 0.00 | 01-JAN-00:10 | 6504.49 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 309.25 | 0.00 | 01-JAN-10:10 | 214653.82 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.07 | 0.00 | 01-JAN-00:10 | 6504.49 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 1030.32 | 0.00 | 01-JAN-10:10 | 199411.90 | 17-JUL-16:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 230.03 | 0.00 | 01-JAN-00:10 | 26367.76 | 05-SEP-15:00 |
General:Cooling:EnergyTransfer | 1030.32 | 0.00 | 01-JAN-10:10 | 199411.90 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 230.03 | 0.00 | 01-JAN-00:10 | 26367.76 | 05-SEP-15:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 108.49 | 0.00 | 01-JAN-00:10 | 28120.67 | 11-JAN-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.32 | 0.00 | 01-JAN-00:10 | 28120.67 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.32 | 0.00 | 01-JAN-00:10 | 28120.67 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.17 | 0.00 | 01-JAN-00:10 | 19041.67 | 17-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.17 | 0.00 | 01-JAN-00:10 | 19041.67 | 17-JUL-14:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 32.37 | 0.00 | 01-JAN-00:40 | 11606.32 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.66 | 0.00 | 01-JAN-00:10 | 11606.32 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.66 | 0.00 | 01-JAN-00:10 | 11606.32 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.70 | 0.00 | 01-JAN-00:20 | 5834.34 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.70 | 0.00 | 01-JAN-00:20 | 5834.34 | 17-JUL-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 32.69 | 0.00 | 01-JAN-00:10 | 7004.87 | 30-JAN-08:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.87 | 0.00 | 01-JAN-00:10 | 7004.87 | 30-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.87 | 0.00 | 01-JAN-00:10 | 7004.87 | 30-JAN-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.82 | 0.00 | 01-JAN-00:10 | 5936.51 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.82 | 0.00 | 01-JAN-00:10 | 5936.51 | 17-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 147.42 | 0.00 | 01-JAN-00:40 | 20171.87 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.94 | 0.00 | 01-JAN-00:10 | 17341.21 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.94 | 0.00 | 01-JAN-00:10 | 17341.21 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 145.49 | 0.00 | 01-JAN-00:40 | 20171.87 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 145.49 | 0.00 | 01-JAN-00:40 | 20171.87 | 17-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 154.84 | 0.00 | 01-JAN-00:10 | 30211.83 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 15.15 | 0.00 | 01-JAN-00:10 | 30211.83 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 15.15 | 0.00 | 01-JAN-00:10 | 30211.83 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 139.69 | 0.00 | 01-JAN-00:10 | 24681.56 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 139.69 | 0.00 | 01-JAN-00:10 | 24681.56 | 17-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 64.20 | 0.00 | 01-JAN-00:10 | 14945.27 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.45 | 0.00 | 01-JAN-00:10 | 14945.27 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.45 | 0.00 | 01-JAN-00:10 | 14945.27 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 34.75 | 0.00 | 01-JAN-00:10 | 8383.22 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 34.75 | 0.00 | 01-JAN-00:10 | 8383.22 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.01 | 0.00 | 01-JAN-00:10 | 9879.73 | 17-JUL-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 17.08 | 0.00 | 01-JAN-00:10 | 9775.44 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 17.08 | 0.00 | 01-JAN-00:10 | 9775.44 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.93 | 0.00 | 01-JAN-00:10 | 9879.73 | 17-JUL-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.93 | 0.00 | 01-JAN-00:10 | 9879.73 | 17-JUL-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.69 | 0.00 | 01-JAN-00:10 | 15009.70 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.04 | 0.00 | 01-JAN-00:10 | 15009.70 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.04 | 0.00 | 01-JAN-00:10 | 15009.70 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 55.65 | 0.00 | 01-JAN-00:10 | 14508.73 | 07-AUG-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 55.65 | 0.00 | 01-JAN-00:10 | 14508.73 | 07-AUG-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.67 | 0.00 | 01-JAN-00:10 | 11118.66 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 18.44 | 0.00 | 01-JAN-00:10 | 9994.73 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 18.44 | 0.00 | 01-JAN-00:10 | 9994.73 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.23 | 0.00 | 01-JAN-00:10 | 11118.66 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.23 | 0.00 | 01-JAN-00:10 | 11118.66 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 46.36 | 0.00 | 01-JAN-00:10 | 11442.64 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.66 | 0.00 | 01-JAN-00:10 | 11442.64 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.66 | 0.00 | 01-JAN-00:10 | 11442.64 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.70 | 0.00 | 01-JAN-00:10 | 5864.28 | 09-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.70 | 0.00 | 01-JAN-00:10 | 5864.28 | 09-AUG-14:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 37.36 | 0.00 | 01-JAN-00:10 | 7989.60 | 07-AUG-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 10.09 | 0.00 | 01-JAN-00:10 | 7524.86 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 10.09 | 0.00 | 01-JAN-00:10 | 7524.86 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.27 | 0.00 | 01-JAN-00:10 | 7989.60 | 07-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.27 | 0.00 | 01-JAN-00:10 | 7989.60 | 07-AUG-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 72.38 | 0.00 | 01-JAN-00:10 | 18722.17 | 09-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.52 | 0.00 | 01-JAN-00:10 | 18722.17 | 09-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.52 | 0.00 | 01-JAN-00:10 | 18722.17 | 09-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 40.86 | 0.00 | 01-JAN-00:10 | 16602.95 | 07-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 40.86 | 0.00 | 01-JAN-00:10 | 16602.95 | 07-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 36.59 | 0.00 | 01-JAN-00:10 | 8387.09 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 10.89 | 0.00 | 01-JAN-00:10 | 7487.32 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 10.89 | 0.00 | 01-JAN-00:10 | 7487.32 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.70 | 0.00 | 01-JAN-00:10 | 8387.09 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.70 | 0.00 | 01-JAN-00:10 | 8387.09 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 50.06 | 0.00 | 01-JAN-00:40 | 11883.85 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 15.51 | 0.00 | 01-JAN-00:40 | 11883.85 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 15.51 | 0.00 | 01-JAN-00:40 | 11883.85 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 34.54 | 0.00 | 01-JAN-00:10 | 7386.16 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 34.54 | 0.00 | 01-JAN-00:10 | 7386.16 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.25 | 0.00 | 01-JAN-00:40 | 9972.75 | 07-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 9.04 | 0.00 | 01-JAN-00:40 | 8158.22 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 9.04 | 0.00 | 01-JAN-00:40 | 8158.22 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.21 | 0.00 | 01-JAN-00:10 | 9972.75 | 07-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.21 | 0.00 | 01-JAN-00:10 | 9972.75 | 07-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 67.27 | 0.00 | 01-JAN-00:40 | 14123.21 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 10.70 | 0.00 | 01-JAN-00:20 | 11832.81 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 10.70 | 0.00 | 01-JAN-00:20 | 11832.81 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 56.56 | 0.00 | 01-JAN-00:10 | 14123.21 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 56.56 | 0.00 | 01-JAN-00:10 | 14123.21 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 42.80 | 0.00 | 01-JAN-00:40 | 10427.18 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 9.81 | 0.00 | 01-JAN-00:40 | 8137.69 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 9.81 | 0.00 | 01-JAN-00:40 | 8137.69 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.99 | 0.00 | 01-JAN-00:10 | 10427.18 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.99 | 0.00 | 01-JAN-00:10 | 10427.18 | 17-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 602.41 | 0.00 | 01-JAN-18:30 | 288971.82 | 09-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
EnergyTransfer:HVAC | 1053.49 | 0.00 | 01-JAN-10:10 | 295771.78 | 07-SEP-14:50 |
HeatingCoils:EnergyTransfer | 546.18 | 0.00 | 01-JAN-10:10 | 286662.28 | 09-JAN-07:20 |
PlantLoopHeatingDemand:HVAC | 546.18 | 0.00 | 01-JAN-10:10 | 286662.28 | 09-JAN-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 546.18 | 0.00 | 01-JAN-10:10 | 286662.28 | 09-JAN-07:20 |
CoolingCoils:EnergyTransfer | 507.30 | 0.00 | 01-JAN-00:10 | 295766.92 | 07-SEP-14:50 |
EnergyTransfer:Plant | 598.03 | 0.00 | 01-JAN-18:30 | 287287.60 | 09-JAN-07:20 |
WaterSystems:EnergyTransfer | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
Boilers:EnergyTransfer | 541.81 | 0.00 | 01-JAN-10:10 | 284978.05 | 09-JAN-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.071 | -230.034 | 0.000 | 0.000 | 33.387 | 111.786 | 259.999 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -175.210 |
CORE_MID | 0.000 | 0.000 | 1.937 | -145.486 | 0.000 | 0.000 | 34.734 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -118.396 |
CORE_TOP | 0.000 | 0.000 | 15.148 | -139.688 | 0.000 | 0.000 | 36.238 | 111.786 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -138.909 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 29.451 | -34.753 | 0.000 | 0.000 | 7.950 | 23.566 | 24.333 | 14.376 | 0.000 | 0.151 | 1.783 | 0.000 | -56.120 | 0.000 | -10.736 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 17.084 | -31.927 | 0.000 | 0.000 | 4.917 | 14.919 | 15.404 | 34.124 | 0.000 | 0.086 | 0.001 | 0.000 | -34.859 | 0.000 | -7.287 | -12.459 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 22.044 | -55.648 | 0.000 | 0.000 | 7.707 | 23.566 | 24.332 | 73.830 | 0.000 | 0.123 | 0.002 | 0.000 | -51.731 | 0.000 | -11.216 | -33.006 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 18.440 | -31.233 | 0.000 | 0.000 | 4.997 | 14.918 | 15.403 | 32.822 | 0.000 | 0.085 | 0.000 | 0.000 | -36.996 | 0.000 | -7.308 | -11.129 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 18.662 | -27.698 | 0.000 | 0.000 | 7.935 | 23.566 | 24.333 | 15.000 | 0.000 | 0.084 | 1.476 | 0.000 | -57.377 | 0.000 | -5.979 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 10.092 | -27.269 | 0.000 | 0.000 | 4.886 | 14.919 | 15.404 | 34.428 | 0.000 | 0.044 | 0.002 | 0.000 | -36.213 | 0.000 | -4.118 | -12.173 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 31.516 | -40.863 | 0.000 | 0.000 | 7.814 | 23.566 | 24.332 | 75.061 | 0.000 | 1.268 | 0.000 | 0.000 | -53.974 | 0.000 | -44.984 | -23.736 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 10.889 | -25.702 | 0.000 | 0.000 | 4.955 | 14.918 | 15.403 | 33.348 | 0.000 | 0.044 | 0.000 | 0.000 | -38.355 | 0.000 | -4.121 | -11.379 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 15.512 | -34.544 | 0.000 | 0.000 | 7.816 | 23.566 | 24.333 | 13.899 | 0.000 | 0.118 | 18.038 | 0.000 | -59.250 | 0.000 | -9.488 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 9.038 | -31.212 | 0.000 | 0.000 | 3.581 | 14.919 | 15.404 | 33.595 | 0.000 | 0.070 | 0.001 | 0.000 | -36.773 | 0.000 | -6.449 | -2.173 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 10.704 | -56.563 | 0.000 | 0.000 | 7.540 | 23.566 | 24.332 | 73.160 | 0.000 | 0.097 | 0.006 | 0.000 | -54.876 | 0.000 | -9.959 | -18.001 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 9.812 | -32.991 | 0.000 | 0.000 | 4.946 | 14.918 | 15.403 | 32.646 | 0.000 | 0.070 | 0.640 | 0.000 | -39.012 | 0.000 | -6.433 | -0.001 |
TOPFLOOR_PLENUM | 65.320 | -43.174 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.118 | 0.003 | 0.000 | 0.000 | 0.000 | -16.039 | -6.225 |
MIDFLOOR_PLENUM | 15.662 | -16.704 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.153 | 17.584 | 0.000 | 0.000 | 0.000 | -16.695 | -0.000 |
FIRSTFLOOR_PLENUM | 7.870 | -24.822 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.115 | 30.514 | 0.000 | 0.000 | 0.000 | -13.677 | -0.000 |
Total Facility | 88.852 | -84.699 | 220.400 | -945.611 | 0.000 | 0.000 | 179.402 | 566.263 | 729.266 | 466.290 | 0.000 | 2.624 | 70.050 | 0.000 | -555.537 | 0.000 | -174.490 | -562.796 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 08-AUG-05:12 | 0.00 | 0.00 | 0.00 | -45181.03 | 0.00 | 0.00 | 329.39 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 36032.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | -35094.45 | 0.00 | 0.00 | 335.27 | 1084.51 | 3025.92 | 0.00 | 0.00 | 0.00 | 30648.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 | -24681.05 | 0.00 | 0.00 | 3497.12 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 4615.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 | -8382.95 | 0.00 | 0.00 | 737.23 | 2057.62 | 1435.25 | 3925.20 | 0.00 | 116.94 | 110.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-09:12 | 0.00 | 0.00 | 0.00 | -16773.81 | 0.00 | 0.00 | 12.89 | 72.37 | 302.86 | 11820.44 | 0.00 | 23.49 | 4541.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-13:21 | 0.00 | 0.00 | 0.00 | -31193.54 | 0.00 | 0.00 | 19.53 | 114.31 | 478.41 | 15667.01 | 0.00 | 266.78 | 14647.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-JUL-16:51 | 0.00 | 0.00 | 0.00 | -20158.76 | 0.00 | 0.00 | 10.52 | 72.36 | 302.86 | 13285.25 | 0.00 | 75.37 | 6412.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 09-AUG-14:50 | 0.00 | 0.00 | 0.00 | -5863.97 | 0.00 | 0.00 | 737.23 | 2057.62 | 1435.25 | 4696.45 | 0.00 | 38.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3100.81 |
PERIMETER_BOT_ZN_2 | 06-AUG-09:41 | 0.00 | 0.00 | 0.00 | -13940.19 | 0.00 | 0.00 | 15.25 | 72.37 | 302.86 | 10765.03 | 0.00 | 33.79 | 2750.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-15:51 | 0.00 | 0.00 | 0.00 | -22487.59 | 0.00 | 0.00 | 24.16 | 114.31 | 478.41 | 7854.18 | 0.00 | 65.48 | 13951.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-SEP-17:11 | 0.00 | 0.00 | 0.00 | -15643.47 | 0.00 | 0.00 | 0.00 | 72.36 | 244.42 | 9266.13 | 0.00 | 27.68 | 6032.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 | -7385.90 | 0.00 | 0.00 | 737.23 | 2057.62 | 1435.25 | 3966.34 | 0.00 | 97.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -908.06 |
PERIMETER_MID_ZN_2 | 04-SEP-08:31 | 0.00 | 0.00 | 0.00 | -16786.63 | 0.00 | 0.00 | 14.99 | 72.37 | 302.86 | 9917.65 | 0.00 | 0.00 | 6504.74 | 0.00 | -0.00 | 0.00 | -25.98 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-15:51 | 0.00 | 0.00 | 0.00 | -22651.69 | 0.00 | 0.00 | 23.28 | 114.31 | 478.41 | 7785.12 | 0.00 | 96.76 | 14153.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-15:51 | 0.00 | 0.00 | 0.00 | -19057.31 | 0.00 | 0.00 | 12.71 | 72.36 | 302.86 | 11992.59 | 0.00 | 56.27 | 6620.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-14:20 | 0.00 | -19041.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 19011.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-05:01 | 0.00 | -7207.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8520.62 | 0.00 | -0.00 | 0.00 | -1313.36 | 0.00 |
FIRSTFLOOR_PLENUM | 04-MAR-05:01 | 0.00 | -8061.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9116.74 | 0.00 | -0.00 | 0.00 | -1055.72 | 0.00 |
Total Facility | 17-JUL-16:00 | 0.00 | -29856.12 | 0.00 | -169550.99 | 0.00 | 0.00 | 17714.96 | 49443.18 | 41937.01 | 76679.88 | 0.00 | 2523.68 | 11108.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:01 | 0.00 | 0.00 | 10196.07 | 0.00 | 0.00 | 0.00 | 488.29 | 1084.51 | 7734.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19503.22 |
CORE_MID | 09-JAN-05:11 | 0.00 | 0.00 | 21118.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24644.58 |
CORE_TOP | 27-NOV-05:11 | 0.00 | 0.00 | 35833.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.51 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39359.74 |
PERIMETER_TOP_ZN_3 | 06-MAR-05:21 | 0.00 | 0.00 | 17901.73 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4853.34 | 0.00 | -1256.51 | -12535.31 |
PERIMETER_TOP_ZN_2 | 06-MAR-05:21 | 0.00 | 0.00 | 11736.32 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3232.05 | 0.00 | -836.18 | -8138.72 |
PERIMETER_TOP_ZN_1 | 06-MAR-05:21 | 0.00 | 0.00 | 18081.40 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5059.39 | 0.00 | -1258.21 | -12507.22 |
PERIMETER_TOP_ZN_4 | 06-MAR-05:21 | 0.00 | 0.00 | 12183.85 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3358.91 | 0.00 | -835.86 | -8459.69 |
PERIMETER_BOT_ZN_3 | 09-JAN-03:11 | 0.00 | 0.00 | 13609.82 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6247.88 | 0.00 | -696.42 | -7294.64 |
PERIMETER_BOT_ZN_2 | 09-JAN-03:11 | 0.00 | 0.00 | 8982.48 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4161.28 | 0.00 | -463.63 | -4755.84 |
PERIMETER_BOT_ZN_1 | 09-JAN-08:00 | 0.00 | 0.00 | 18722.08 | 0.00 | 0.00 | 0.00 | 263.13 | 685.87 | 637.88 | 0.00 | 0.00 | 0.00 | 14698.52 | 0.00 | -5594.77 | 0.00 | -29412.72 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-03:11 | 0.00 | 0.00 | 9177.45 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4028.59 | 0.00 | -464.43 | -5082.68 |
PERIMETER_MID_ZN_3 | 09-JAN-05:11 | 0.00 | 0.00 | 13655.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6261.60 | 0.00 | -862.37 | -7274.47 |
PERIMETER_MID_ZN_2 | 09-JAN-05:11 | 0.00 | 0.00 | 9874.01 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4166.86 | 0.00 | -574.80 | -5602.98 |
PERIMETER_MID_ZN_1 | 09-JAN-05:11 | 0.00 | 0.00 | 13790.95 | 0.00 | 0.00 | 0.00 | 0.00 | 228.62 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6060.33 | 0.00 | -864.30 | -7609.75 |
PERIMETER_MID_ZN_4 | 09-JAN-05:11 | 0.00 | 0.00 | 10259.23 | 0.00 | 0.00 | 0.00 | 0.00 | 144.73 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4026.01 | 0.00 | -576.02 | -6127.81 |
TOPFLOOR_PLENUM | 11-JAN-05:11 | 31085.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -645.20 | -30439.93 |
MIDFLOOR_PLENUM | 09-JAN-08:08 | 12267.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -182.80 | -12084.73 |
FIRSTFLOOR_PLENUM | 02-JAN-06:13 | 7486.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -94.65 | -7391.81 |
Total Facility | 09-JAN-06:01 | 36221.96 | 0.00 | 194444.74 | 0.00 | 0.00 | 0.00 | 2598.71 | 5493.69 | 20036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63828.29 | 0.00 | -8224.85 | -186742.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 8.5756 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.7178 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 8.1832 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.4393 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 10.2124 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 7.8931 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.2878 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.5727 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.0916 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.4549 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.1062 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0637 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8175 | 3.8175 | 1.1453 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1219 | 3.1219 | 0.9366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0485 | 4.0485 | 1.2146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8373 | 1.8373 | 0.5512 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2010 | 1.2010 | 0.3603 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8601 | 1.8601 | 0.5580 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2654 | 1.2654 | 0.3796 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4190 | 1.4190 | 0.4257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9336 | 0.9336 | 0.2801 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4416 | 1.4416 | 0.4325 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9639 | 0.9639 | 0.2892 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4042 | 1.4042 | 0.4213 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0804 | 1.0804 | 0.3241 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4254 | 1.4254 | 0.4276 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1513 | 1.1513 | 0.3454 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 8.5756 | 6.7178 | 8.5756 | 2.5727 | 0.0000 | 1.0000 |
PACU_VAV_MID | 8.1832 | 6.4393 | 8.1832 | 2.4549 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 10.2124 | 7.8931 | 10.2124 | 3.0637 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9088 | 1.9088 | 1.1453 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5610 | 1.5610 | 0.9366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0243 | 2.0243 | 1.2146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9187 | 0.9187 | 0.5512 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6005 | 0.6005 | 0.3603 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9301 | 0.9301 | 0.5580 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6327 | 0.6327 | 0.3796 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7095 | 0.7095 | 0.4257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4668 | 0.4668 | 0.2801 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7208 | 0.7208 | 0.4325 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4819 | 0.4819 | 0.2892 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7021 | 0.7021 | 0.4213 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5402 | 0.5402 | 0.3241 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7127 | 0.7127 | 0.4276 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5757 | 0.5757 | 0.3454 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.2878 | 2.5727 | 2.5727 | 2.5727 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.0916 | 2.4549 | 2.4549 | 2.4549 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.1062 | 3.0637 | 3.0637 | 3.0637 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 441.33 |
Number of hours cooling loads not met | 35.33 |
Number of hours not met | 476.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 835.38 | 385302.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 127.62 | 84924.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 566.26 | 49443.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 235.51 | 15013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 27.50 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 192.57 | 35214.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 4.29 | 1517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 59.06 | 7227.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 729.27 | 1942.08 |
Natural Gas | 0.00 | 835.38 |
Additional | 0.00 | 0.00 |
Total | 729.27 | 2777.46 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 113.66 |
Space Heating | 0.00 |
Space Cooling | 25.62 |
Fans (All) | 38.65 |
Service Water Heating | 11.85 |
Receptacle Equipment | 146.37 |
Miscellaneous (All) | 389.80 |
Subtotal | 389.80 |
Natural Gas [MJ/m2] | |
Space Heating | 167.67 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 167.67 |
Subtotal | 167.67 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.39 |
Space Heating | 30.08 |
Space Cooling | 4.60 |
Fans (All) | 6.93 |
Service Water Heating | 2.13 |
Receptacle Equipment | 26.26 |
Miscellaneous | 9.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2939. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8727.83 | 32.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8729.00 | 31.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8727.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 32.17 | 0.00 | 0.00 | 0.00 |
Average | 8753.70 | 6.30 | 0.00 | 0.00 | 0.00 |
Sum | 157566.67 | 113.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128287.33 | 16.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 16.67 | 0.00 | 0.00 | 0.00 |
Average | 34142.41 | 0.93 | 0.00 | 0.00 | 0.00 |
Sum | 614563.33 | 16.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8711.67 | 48.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8711.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 48.33 | 0.00 | 0.00 | 0.00 |
Average | 8755.43 | 4.57 | 0.00 | 0.00 | 0.00 |
Sum | 157597.67 | 82.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128272.67 | 31.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128296.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128301.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128301.00 | 31.33 | 0.00 | 0.00 | 0.00 |
Average | 34141.00 | 2.33 | 0.00 | 0.00 | 0.00 |
Sum | 614538.00 | 42.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128616E+11 | 10335.86 | 19-JAN-16:50 | -6.4 | -8.0 | 0.172011E+10 | 2537.94 | 19-JAN-16:00 | -6.7 | -8.2 |
February | 0.123409E+11 | 16962.35 | 28-FEB-17:00 | 10.00 | 4.31 | 0.166888E+10 | 2606.66 | 28-FEB-10:20 | 10.00 | 4.31 |
March | 0.160642E+11 | 17625.38 | 01-MAR-17:00 | 7.80 | 3.22 | 0.207861E+10 | 2606.66 | 01-MAR-10:20 | 7.80 | 3.22 |
April | 0.162077E+11 | 24180.32 | 27-APR-05:01 | -1.2 | -3.0 | 0.189788E+10 | 2606.66 | 04-APR-09:20 | -1.2 | -3.0 |
May | 0.191110E+11 | 44672.72 | 22-MAY-05:01 | -0.6 | -0.6 | 0.205980E+10 | 2606.83 | 02-MAY-13:09 | -0.6 | -0.6 |
June | 0.252934E+11 | 34311.69 | 23-JUN-05:13 | 17.97 | 11.79 | 0.207088E+10 | 2606.67 | 20-JUN-09:00 | 17.97 | 11.79 |
July | 0.276816E+11 | 44796.55 | 18-JUL-05:12 | 17.93 | 11.91 | 0.192618E+10 | 2606.71 | 13-JUL-09:00 | 17.93 | 11.91 |
August | 0.289292E+11 | 45180.55 | 08-AUG-05:12 | 18.13 | 11.59 | 0.216229E+10 | 2606.66 | 24-AUG-09:00 | 20.00 | 12.25 |
September | 0.234959E+11 | 44069.95 | 11-SEP-05:12 | 10.93 | 10.10 | 0.191743E+10 | 2606.74 | 07-SEP-09:50 | 10.93 | 10.10 |
October | 0.192105E+11 | 39995.01 | 21-OCT-05:02 | -0.5 | -1.6 | 0.198599E+10 | 2606.66 | 27-OCT-09:20 | 8.13 | 3.61 |
November | 0.152995E+11 | 23912.03 | 02-NOV-05:01 | -0.8 | -2.6 | 0.192489E+10 | 2606.67 | 03-NOV-09:20 | 7.10 | 4.34 |
December | 0.135390E+11 | 14883.56 | 07-DEC-16:20 | 5.93 | 1.89 | 0.179453E+10 | 2606.65 | 07-DEC-10:30 | 5.93 | 1.89 |
Annual Sum or Average | 0.230034E+12 | 0.232075E+11 | ||||||||
Minimum of Months | 0.123409E+11 | 10335.86 | -6.4 | -8.0 | 0.166888E+10 | 2537.94 | -6.7 | -8.2 | ||
Maximum of Months | 0.289292E+11 | 45180.55 | 18.13 | 11.91 | 0.216229E+10 | 2606.83 | 20.00 | 12.25 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2756341.38 | 968.50 | 14-JAN-17:10 | 8.90 | 4.06 | 0.00 | 0.00 | 01-JAN-00:10 | 8.90 | 4.06 |
February | 0.254962E+09 | 4566.23 | 26-FEB-14:24 | 16.15 | 6.12 | 0.00 | 0.00 | 01-FEB-00:10 | 16.15 | 6.12 |
March | 0.114590E+10 | 5288.51 | 22-MAR-14:35 | 11.10 | 4.12 | 0.00 | 0.00 | 01-MAR-00:10 | 11.10 | 4.12 |
April | 0.257011E+10 | 9757.66 | 16-APR-13:13 | 18.67 | 7.93 | 0.00 | 0.00 | 01-APR-00:10 | 18.67 | 7.93 |
May | 0.480990E+10 | 13641.60 | 19-MAY-14:50 | 28.12 | 14.91 | 0.00 | 0.00 | 01-MAY-00:10 | 28.12 | 14.91 |
June | 0.826618E+10 | 16149.29 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.106125E+11 | 19041.67 | 17-JUL-14:20 | 36.50 | 17.01 | 0.00 | 0.00 | 01-JUL-00:10 | 36.50 | 17.01 |
August | 0.891787E+10 | 17440.75 | 07-AUG-14:00 | 32.80 | 15.97 | 0.00 | 0.00 | 01-AUG-00:10 | 32.80 | 15.97 |
September | 0.466186E+10 | 12853.44 | 01-SEP-14:05 | 27.88 | 14.54 | 0.00 | 0.00 | 01-SEP-00:10 | 27.88 | 14.54 |
October | 0.166386E+10 | 7578.09 | 18-OCT-14:30 | 25.00 | 11.51 | 0.00 | 0.00 | 01-OCT-00:10 | 25.00 | 11.51 |
November | 0.265349E+09 | 3046.45 | 03-NOV-13:50 | 14.78 | 7.82 | 0.00 | 0.00 | 01-NOV-00:10 | 14.78 | 7.82 |
December | 2816013.50 | 358.14 | 06-DEC-14:13 | 11.50 | 5.51 | 0.00 | 0.00 | 01-DEC-00:10 | 11.50 | 5.51 |
Annual Sum or Average | 0.431741E+11 | 0.00 | ||||||||
Minimum of Months | 2756341.38 | 358.14 | 8.90 | 4.06 | 0.00 | 0.00 | 8.90 | 4.06 | ||
Maximum of Months | 0.106125E+11 | 19041.67 | 36.50 | 17.01 | 0.00 | 0.00 | 36.50 | 17.01 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246686E+09 | 5614.45 | 28-JAN-02:13 | -29.2 | -29.6 | 0.00 | 0.00 | 01-JAN-00:10 | -29.2 | -29.6 |
February | 0.160729E+09 | 6569.16 | 09-FEB-05:01 | -17.3 | -17.7 | 0.00 | 0.00 | 01-FEB-00:10 | -17.3 | -17.7 |
March | 0.292928E+09 | 7207.28 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.682179E+09 | 4869.06 | 29-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.118728E+10 | 5007.72 | 22-MAY-05:01 | -0.6 | -0.6 | 0.00 | 0.00 | 01-MAY-00:10 | -0.6 | -0.6 |
June | 0.298838E+10 | 4482.07 | 23-JUN-15:30 | 27.50 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 27.50 | 14.33 |
July | 0.404837E+10 | 5834.34 | 17-JUL-16:00 | 37.20 | 17.28 | 0.00 | 0.00 | 01-JUL-00:10 | 37.20 | 17.28 |
August | 0.382035E+10 | 5487.96 | 07-AUG-16:00 | 32.20 | 16.16 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 16.16 |
September | 0.210912E+10 | 4668.68 | 05-SEP-14:20 | 24.40 | 15.02 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 15.02 |
October | 0.760438E+09 | 2812.41 | 05-OCT-05:01 | -1.9 | -2.5 | 0.00 | 0.00 | 01-OCT-00:10 | -1.9 | -2.5 |
November | 0.258743E+09 | 3509.77 | 10-NOV-06:01 | -4.0 | -4.9 | 0.00 | 0.00 | 01-NOV-00:10 | -4.0 | -4.9 |
December | 0.148466E+09 | 5553.47 | 23-DEC-05:01 | -11.6 | -12.4 | 0.00 | 0.00 | 01-DEC-00:10 | -11.6 | -12.4 |
Annual Sum or Average | 0.167037E+11 | 0.00 | ||||||||
Minimum of Months | 0.148466E+09 | 2812.41 | -29.2 | -29.6 | 0.00 | 0.00 | -29.2 | -29.6 | ||
Maximum of Months | 0.404837E+10 | 7207.28 | 37.20 | 17.28 | 0.00 | 0.00 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358958E+09 | 5962.43 | 19-JAN-05:01 | -14.3 | -15.0 | 0.00 | 0.00 | 01-JAN-00:10 | -14.3 | -15.0 |
February | 0.378848E+09 | 6590.17 | 03-FEB-05:01 | -16.7 | -17.0 | 0.00 | 0.00 | 01-FEB-00:10 | -16.7 | -17.0 |
March | 0.781511E+09 | 8060.99 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.140815E+10 | 6503.66 | 20-APR-05:11 | 2.13 | 0.99 | 0.00 | 0.00 | 01-APR-00:10 | 2.13 | 0.99 |
May | 0.209870E+10 | 5496.06 | 06-MAY-05:01 | -1.4 | -3.1 | 0.00 | 0.00 | 01-MAY-00:10 | -1.4 | -3.1 |
June | 0.397131E+10 | 4546.67 | 23-JUN-15:30 | 27.50 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 27.50 | 14.33 |
July | 0.489869E+10 | 5936.51 | 17-JUL-16:00 | 37.20 | 17.28 | 0.00 | 0.00 | 01-JUL-00:10 | 37.20 | 17.28 |
August | 0.491632E+10 | 5798.49 | 07-AUG-16:00 | 32.20 | 16.16 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 16.16 |
September | 0.320891E+10 | 5257.76 | 05-SEP-14:05 | 24.40 | 15.08 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 15.08 |
October | 0.176677E+10 | 3381.37 | 21-OCT-05:07 | -0.5 | -1.6 | 0.00 | 0.00 | 01-OCT-00:10 | -0.5 | -1.6 |
November | 0.724997E+09 | 4141.00 | 22-NOV-06:11 | 2.30 | -0.8 | 0.00 | 0.00 | 01-NOV-00:10 | 2.30 | -0.8 |
December | 0.308585E+09 | 5441.37 | 30-DEC-05:01 | -20.6 | -21.1 | 0.00 | 0.00 | 01-DEC-00:10 | -20.6 | -21.1 |
Annual Sum or Average | 0.248218E+11 | 0.00 | ||||||||
Minimum of Months | 0.308585E+09 | 3381.37 | -20.6 | -21.1 | 0.00 | 0.00 | -20.6 | -21.1 | ||
Maximum of Months | 0.491632E+10 | 8060.99 | 37.20 | 17.28 | 0.00 | 0.00 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.657230E+10 | 7373.43 | 13-JAN-16:40 | 8.17 | 4.18 | 0.154464E+10 | 2298.77 | 13-JAN-16:49 | 7.98 | 4.06 |
February | 0.731571E+10 | 9053.86 | 28-FEB-17:00 | 10.00 | 4.31 | 0.149089E+10 | 2548.82 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.981336E+10 | 9427.85 | 01-MAR-17:00 | 7.80 | 3.22 | 0.188827E+10 | 2579.58 | 23-MAR-13:00 | 10.00 | 2.51 |
April | 0.102957E+11 | 12987.18 | 25-APR-16:00 | 17.80 | 7.70 | 0.178418E+10 | 2606.66 | 13-APR-13:20 | 17.80 | 7.70 |
May | 0.121971E+11 | 16128.19 | 30-MAY-16:00 | 19.40 | 11.02 | 0.196521E+10 | 2606.66 | 17-MAY-09:20 | 19.40 | 11.02 |
June | 0.175627E+11 | 19098.58 | 23-JUN-16:00 | 26.70 | 13.80 | 0.205285E+10 | 2606.66 | 01-JUN-09:20 | 26.70 | 13.80 |
July | 0.194966E+11 | 29842.28 | 18-JUL-05:12 | 17.93 | 11.91 | 0.191656E+10 | 2606.68 | 13-JUL-09:00 | 17.93 | 11.91 |
August | 0.196722E+11 | 28414.06 | 08-AUG-05:12 | 18.13 | 11.59 | 0.215072E+10 | 2606.65 | 09-AUG-09:20 | 27.60 | 15.89 |
September | 0.147037E+11 | 35094.01 | 05-SEP-05:12 | 18.50 | 11.75 | 0.187974E+10 | 2606.71 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.111198E+11 | 14222.02 | 19-OCT-16:00 | 21.10 | 10.04 | 0.188786E+10 | 2606.66 | 13-OCT-09:30 | 21.10 | 10.04 |
November | 0.892498E+10 | 10414.83 | 03-NOV-16:00 | 14.30 | 7.69 | 0.172922E+10 | 2606.49 | 03-NOV-13:50 | 14.30 | 7.69 |
December | 0.781259E+10 | 8047.99 | 07-DEC-16:20 | 5.93 | 1.89 | 0.156986E+10 | 2487.37 | 07-DEC-14:00 | 5.93 | 1.89 |
Annual Sum or Average | 0.145487E+12 | 0.218600E+11 | ||||||||
Minimum of Months | 0.657230E+10 | 7373.43 | 5.93 | 1.89 | 0.149089E+10 | 2298.77 | 5.93 | 1.89 | ||
Maximum of Months | 0.196722E+11 | 35094.01 | 26.70 | 13.80 | 0.215072E+10 | 2606.71 | 27.60 | 15.89 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387673E+10 | 8869.36 | 07-JAN-17:01 | -21.8 | -22.3 | 0.145919E+10 | 2089.47 | 13-JAN-16:40 | 8.17 | 4.18 |
February | 0.540150E+10 | 9725.30 | 28-FEB-17:00 | 10.00 | 4.31 | 0.136132E+10 | 2325.29 | 28-FEB-16:00 | 10.00 | 4.31 |
March | 0.871057E+10 | 9940.87 | 23-MAR-14:50 | 8.17 | 1.37 | 0.169564E+10 | 2414.48 | 23-MAR-13:00 | 8.17 | 1.37 |
April | 0.103528E+11 | 14475.71 | 25-APR-16:00 | 17.80 | 7.70 | 0.161390E+10 | 2606.63 | 25-APR-13:20 | 17.80 | 7.70 |
May | 0.131580E+11 | 19220.25 | 19-MAY-16:00 | 27.80 | 14.54 | 0.182988E+10 | 2606.64 | 17-MAY-13:20 | 27.80 | 14.54 |
June | 0.188304E+11 | 22695.09 | 23-JUN-14:00 | 31.70 | 15.26 | 0.200178E+10 | 2606.68 | 20-JUN-13:09 | 31.70 | 15.26 |
July | 0.211244E+11 | 24681.56 | 17-JUL-15:30 | 36.65 | 17.14 | 0.189095E+10 | 2606.67 | 13-JUL-09:00 | 36.65 | 17.14 |
August | 0.204545E+11 | 23652.79 | 07-AUG-15:20 | 32.60 | 16.04 | 0.210497E+10 | 2606.65 | 09-AUG-09:20 | 27.60 | 15.89 |
September | 0.147950E+11 | 21864.26 | 05-SEP-14:00 | 24.40 | 15.14 | 0.176089E+10 | 2606.69 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.106297E+11 | 13175.29 | 18-OCT-16:00 | 24.40 | 11.02 | 0.167399E+10 | 2606.39 | 18-OCT-13:00 | 24.40 | 11.02 |
November | 0.735535E+10 | 9950.13 | 03-NOV-16:00 | 14.30 | 7.69 | 0.153225E+10 | 2361.05 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.499960E+10 | 8892.75 | 06-DEC-16:10 | 8.95 | 4.16 | 0.143177E+10 | 2208.23 | 07-DEC-14:00 | 8.30 | 2.55 |
Annual Sum or Average | 0.139689E+12 | 0.203565E+11 | ||||||||
Minimum of Months | 0.387673E+10 | 8869.36 | -21.8 | -22.3 | 0.136132E+10 | 2089.47 | 8.17 | 1.37 | ||
Maximum of Months | 0.211244E+11 | 24681.56 | 36.65 | 17.14 | 0.210497E+10 | 2606.69 | 36.65 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40327876.94 | 3792.54 | 07-JAN-17:01 | -21.8 | -22.3 | 0.303930E+09 | 406.88 | 26-JAN-10:00 | -21.7 | -22.3 |
February | 0.274698E+09 | 3317.06 | 27-FEB-16:10 | 17.78 | 6.92 | 0.277124E+09 | 408.35 | 27-FEB-14:00 | 17.78 | 6.92 |
March | 0.973426E+09 | 3520.20 | 29-MAR-16:00 | 12.20 | 4.07 | 0.332952E+09 | 423.24 | 29-MAR-13:00 | 12.20 | 4.07 |
April | 0.216892E+10 | 4393.15 | 07-APR-14:40 | 22.23 | 9.16 | 0.304136E+09 | 497.65 | 07-APR-13:00 | 22.23 | 9.16 |
May | 0.378391E+10 | 6083.47 | 28-MAY-17:32 | 20.37 | 10.36 | 0.346003E+09 | 549.49 | 19-MAY-13:00 | 20.37 | 10.36 |
June | 0.631701E+10 | 7376.59 | 23-JUN-13:50 | 31.60 | 15.24 | 0.388682E+09 | 549.50 | 20-JUN-13:20 | 31.60 | 15.24 |
July | 0.731146E+10 | 8383.22 | 17-JUL-16:00 | 37.20 | 17.28 | 0.378274E+09 | 549.50 | 06-JUL-13:20 | 37.20 | 17.28 |
August | 0.667542E+10 | 7945.84 | 09-AUG-14:50 | 33.40 | 16.01 | 0.409739E+09 | 549.50 | 01-AUG-13:20 | 33.40 | 16.01 |
September | 0.432473E+10 | 7594.25 | 03-SEP-15:21 | 33.30 | 15.93 | 0.329066E+09 | 549.50 | 05-SEP-13:50 | 24.22 | 15.03 |
October | 0.208578E+10 | 4230.53 | 18-OCT-16:00 | 24.40 | 11.02 | 0.314099E+09 | 477.63 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.670479E+09 | 3244.79 | 03-NOV-15:40 | 14.40 | 7.69 | 0.302781E+09 | 408.04 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.127339E+09 | 2904.88 | 09-DEC-17:02 | 11.52 | 4.10 | 0.293823E+09 | 406.86 | 28-DEC-14:00 | -20.6 | -21.0 |
Annual Sum or Average | 0.347535E+11 | 0.398061E+10 | ||||||||
Minimum of Months | 40327876.94 | 2904.88 | -21.8 | -22.3 | 0.277124E+09 | 406.86 | -21.7 | -22.3 | ||
Maximum of Months | 0.731146E+10 | 8383.22 | 37.20 | 17.28 | 0.409739E+09 | 549.50 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67340887.44 | 2473.92 | 07-JAN-17:01 | -21.8 | -22.3 | 0.192517E+09 | 257.59 | 10-JAN-14:50 | -24.2 | -24.7 |
February | 0.477521E+09 | 2568.30 | 27-FEB-10:40 | 13.50 | 5.02 | 0.176741E+09 | 294.82 | 27-FEB-10:50 | 13.95 | 5.20 |
March | 0.121145E+10 | 3160.17 | 23-MAR-10:30 | 8.60 | 1.66 | 0.217253E+09 | 340.51 | 23-MAR-09:00 | 8.60 | 1.66 |
April | 0.213435E+10 | 5377.39 | 25-APR-09:30 | 10.80 | 5.26 | 0.208211E+09 | 347.88 | 25-APR-09:20 | 10.80 | 5.26 |
May | 0.327572E+10 | 6961.16 | 19-MAY-09:10 | 18.17 | 11.56 | 0.238024E+09 | 347.88 | 02-MAY-09:00 | 18.17 | 11.56 |
June | 0.553455E+10 | 13474.46 | 25-JUN-08:42 | 16.52 | 11.73 | 0.263039E+09 | 347.90 | 28-JUN-09:00 | 24.40 | 12.69 |
July | 0.671219E+10 | 12631.59 | 02-JUL-08:52 | 22.20 | 15.44 | 0.250766E+09 | 347.90 | 13-JUL-09:00 | 23.30 | 13.98 |
August | 0.607117E+10 | 16773.83 | 06-AUG-09:12 | 28.13 | 14.48 | 0.278058E+09 | 347.89 | 04-AUG-09:30 | 28.13 | 14.48 |
September | 0.357552E+10 | 11126.88 | 03-SEP-10:02 | 28.07 | 14.84 | 0.224409E+09 | 347.88 | 05-SEP-13:50 | 24.22 | 15.03 |
October | 0.196411E+10 | 3874.98 | 18-OCT-09:50 | 19.53 | 8.61 | 0.208708E+09 | 347.87 | 18-OCT-09:39 | 19.53 | 8.61 |
November | 0.739158E+09 | 2588.32 | 03-NOV-10:00 | 8.70 | 5.33 | 0.192617E+09 | 295.61 | 03-NOV-09:00 | 8.70 | 5.33 |
December | 0.164029E+09 | 1898.21 | 09-DEC-17:02 | 11.52 | 4.10 | 0.186066E+09 | 257.60 | 27-DEC-14:09 | -15.2 | -15.8 |
Annual Sum or Average | 0.319271E+11 | 0.263641E+10 | ||||||||
Minimum of Months | 67340887.44 | 1898.21 | -21.8 | -22.3 | 0.176741E+09 | 257.59 | -24.2 | -24.7 | ||
Maximum of Months | 0.671219E+10 | 16773.83 | 28.13 | 15.44 | 0.278058E+09 | 347.90 | 28.13 | 15.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103548E+10 | 4736.94 | 19-JAN-14:00 | -5.6 | -7.5 | 0.311554E+09 | 528.28 | 19-JAN-14:09 | -5.5 | -7.4 |
February | 0.203106E+10 | 10006.48 | 27-FEB-13:30 | 17.75 | 6.76 | 0.297237E+09 | 549.50 | 27-FEB-14:30 | 18.60 | 7.13 |
March | 0.290159E+10 | 9805.93 | 01-MAR-14:07 | 6.97 | 2.89 | 0.364197E+09 | 549.50 | 14-MAR-13:30 | 15.00 | 6.74 |
April | 0.356108E+10 | 10374.42 | 25-APR-13:40 | 16.30 | 6.98 | 0.329120E+09 | 549.50 | 13-APR-13:20 | 16.30 | 6.98 |
May | 0.480281E+10 | 10705.84 | 19-MAY-13:40 | 26.83 | 14.98 | 0.368942E+09 | 549.53 | 02-MAY-13:09 | 26.83 | 14.98 |
June | 0.739467E+10 | 11205.42 | 23-JUN-13:10 | 31.20 | 15.18 | 0.397234E+09 | 549.51 | 27-JUN-13:50 | 24.53 | 13.02 |
July | 0.910402E+10 | 13183.17 | 17-JUL-13:10 | 36.20 | 17.01 | 0.383022E+09 | 549.52 | 28-JUL-13:00 | 24.40 | 13.30 |
August | 0.952815E+10 | 18297.21 | 06-AUG-13:52 | 34.40 | 15.37 | 0.424401E+09 | 549.51 | 22-AUG-13:00 | 24.40 | 15.66 |
September | 0.690333E+10 | 31193.54 | 03-SEP-13:21 | 33.60 | 16.11 | 0.355574E+09 | 549.53 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.452497E+10 | 13327.60 | 18-OCT-13:30 | 24.70 | 11.11 | 0.354781E+09 | 549.51 | 20-OCT-13:00 | 13.30 | 6.77 |
November | 0.248706E+10 | 10273.02 | 03-NOV-13:25 | 14.35 | 7.74 | 0.331163E+09 | 549.50 | 06-NOV-14:30 | 8.05 | 3.12 |
December | 0.137433E+10 | 4952.92 | 06-DEC-14:40 | 11.30 | 5.42 | 0.306707E+09 | 545.12 | 06-DEC-14:50 | 11.20 | 5.38 |
Annual Sum or Average | 0.556486E+11 | 0.422393E+10 | ||||||||
Minimum of Months | 0.103548E+10 | 4736.94 | -5.6 | -7.5 | 0.297237E+09 | 528.28 | -5.5 | -7.4 | ||
Maximum of Months | 0.952815E+10 | 31193.54 | 36.20 | 17.01 | 0.424401E+09 | 549.53 | 26.83 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121545E+09 | 2607.75 | 07-JAN-17:01 | -21.8 | -22.3 | 0.192588E+09 | 268.11 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.496192E+09 | 3639.38 | 28-FEB-16:40 | 10.37 | 4.49 | 0.178123E+09 | 338.67 | 28-FEB-16:00 | 10.00 | 4.31 |
March | 0.106384E+10 | 4771.97 | 28-MAR-16:00 | 10.60 | 3.09 | 0.216188E+09 | 338.68 | 02-MAR-16:40 | 10.60 | 3.09 |
April | 0.207672E+10 | 9190.13 | 16-APR-16:52 | 20.00 | 8.97 | 0.197889E+09 | 338.68 | 25-APR-15:09 | 17.13 | 7.50 |
May | 0.338423E+10 | 18231.30 | 28-MAY-17:32 | 20.37 | 10.36 | 0.225288E+09 | 347.85 | 19-MAY-13:00 | 20.37 | 10.36 |
June | 0.533073E+10 | 12204.05 | 24-JUN-17:42 | 26.38 | 11.78 | 0.246399E+09 | 347.85 | 27-JUN-13:00 | 25.00 | 13.11 |
July | 0.636547E+10 | 20159.14 | 16-JUL-16:51 | 33.30 | 17.43 | 0.238722E+09 | 347.86 | 28-JUL-13:00 | 24.40 | 13.30 |
August | 0.582600E+10 | 19263.56 | 06-AUG-16:32 | 35.20 | 15.91 | 0.260269E+09 | 347.85 | 22-AUG-13:00 | 24.40 | 15.66 |
September | 0.364677E+10 | 19178.14 | 03-SEP-15:21 | 33.30 | 15.93 | 0.212958E+09 | 347.85 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.189326E+10 | 6458.80 | 18-OCT-16:00 | 24.40 | 11.02 | 0.205276E+09 | 341.25 | 18-OCT-13:00 | 24.40 | 11.02 |
November | 0.785654E+09 | 3231.12 | 03-NOV-15:50 | 14.35 | 7.69 | 0.195141E+09 | 324.92 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.243375E+09 | 2633.19 | 06-DEC-15:40 | 9.97 | 4.80 | 0.186322E+09 | 281.35 | 06-DEC-15:50 | 9.68 | 4.65 |
Annual Sum or Average | 0.312338E+11 | 0.255516E+10 | ||||||||
Minimum of Months | 0.121545E+09 | 2607.75 | -21.8 | -22.3 | 0.178123E+09 | 268.11 | 8.90 | 3.09 | ||
Maximum of Months | 0.636547E+10 | 20159.14 | 35.20 | 17.43 | 0.260269E+09 | 347.86 | 25.00 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25105222.11 | 2291.87 | 14-JAN-17:02 | 8.90 | 4.06 | 0.304201E+09 | 406.86 | 10-JAN-14:39 | 8.90 | 4.06 |
February | 0.162582E+09 | 2291.36 | 25-FEB-17:03 | 12.33 | 4.03 | 0.277684E+09 | 406.83 | 01-FEB-10:50 | 12.33 | 4.03 |
March | 0.467996E+09 | 2460.42 | 29-MAR-16:00 | 12.20 | 4.07 | 0.332577E+09 | 406.79 | 17-MAR-09:00 | 12.20 | 4.07 |
April | 0.113791E+10 | 2935.81 | 07-APR-14:40 | 22.23 | 9.16 | 0.297521E+09 | 452.27 | 07-APR-13:00 | 22.23 | 9.16 |
May | 0.255024E+10 | 3643.86 | 29-MAY-18:26 | 22.50 | 12.11 | 0.336652E+09 | 505.01 | 19-MAY-13:00 | 22.50 | 12.11 |
June | 0.452685E+10 | 4633.12 | 23-JUN-14:00 | 31.70 | 15.26 | 0.382436E+09 | 549.49 | 29-JUN-13:20 | 32.03 | 14.50 |
July | 0.545224E+10 | 5790.29 | 17-JUL-16:00 | 37.20 | 17.28 | 0.381163E+09 | 549.50 | 26-JUL-09:20 | 27.80 | 14.33 |
August | 0.529311E+10 | 5864.28 | 09-AUG-14:50 | 33.40 | 16.01 | 0.416296E+09 | 549.50 | 01-AUG-13:20 | 33.40 | 16.01 |
September | 0.410955E+10 | 5562.81 | 04-SEP-15:51 | 32.80 | 16.49 | 0.340852E+09 | 549.50 | 05-SEP-13:50 | 24.22 | 15.03 |
October | 0.270217E+10 | 3375.78 | 19-OCT-14:50 | 21.60 | 10.25 | 0.325421E+09 | 496.78 | 19-OCT-13:00 | 21.60 | 10.25 |
November | 0.109119E+10 | 2738.45 | 08-NOV-14:10 | 13.78 | 7.92 | 0.306082E+09 | 434.33 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.179016E+09 | 2344.74 | 06-DEC-07:05 | 6.10 | 3.30 | 0.294713E+09 | 406.85 | 29-DEC-14:39 | -19.6 | -20.2 |
Annual Sum or Average | 0.276980E+11 | 0.399560E+10 | ||||||||
Minimum of Months | 25105222.11 | 2291.36 | 6.10 | 3.30 | 0.277684E+09 | 406.79 | -19.6 | -20.2 | ||
Maximum of Months | 0.545224E+10 | 5864.28 | 37.20 | 17.28 | 0.416296E+09 | 549.50 | 33.40 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46741303.60 | 1513.12 | 14-JAN-17:02 | 8.90 | 4.06 | 0.192792E+09 | 257.58 | 05-JAN-14:09 | 8.90 | 4.06 |
February | 0.388223E+09 | 2041.55 | 27-FEB-10:30 | 13.05 | 4.83 | 0.177653E+09 | 299.40 | 27-FEB-10:50 | 13.95 | 5.20 |
March | 0.846589E+09 | 2257.27 | 23-MAR-10:30 | 8.60 | 1.66 | 0.215761E+09 | 319.33 | 23-MAR-09:00 | 8.60 | 1.66 |
April | 0.148264E+10 | 3020.10 | 25-APR-09:30 | 10.80 | 5.26 | 0.203236E+09 | 347.87 | 25-APR-09:20 | 10.80 | 5.26 |
May | 0.238750E+10 | 4198.06 | 19-MAY-09:30 | 18.90 | 11.91 | 0.233283E+09 | 347.87 | 19-MAY-13:20 | 26.47 | 14.93 |
June | 0.420566E+10 | 6953.12 | 23-JUN-09:20 | 26.33 | 15.51 | 0.264027E+09 | 347.89 | 28-JUN-09:00 | 24.40 | 12.69 |
July | 0.555712E+10 | 9359.45 | 16-JUL-09:21 | 22.75 | 16.30 | 0.253281E+09 | 347.90 | 13-JUL-09:00 | 22.75 | 16.30 |
August | 0.526114E+10 | 13940.23 | 06-AUG-09:41 | 29.53 | 14.91 | 0.282538E+09 | 347.89 | 04-AUG-09:30 | 29.53 | 14.91 |
September | 0.346149E+10 | 13935.95 | 04-SEP-08:31 | 26.33 | 14.69 | 0.235066E+09 | 347.88 | 05-SEP-13:50 | 24.22 | 15.03 |
October | 0.232205E+10 | 3458.55 | 18-OCT-10:00 | 20.00 | 8.80 | 0.224122E+09 | 347.87 | 18-OCT-09:20 | 20.00 | 8.80 |
November | 0.106644E+10 | 2238.21 | 03-NOV-09:30 | 7.50 | 4.59 | 0.198585E+09 | 318.77 | 03-NOV-09:39 | 7.90 | 4.84 |
December | 0.243587E+09 | 1644.18 | 06-DEC-10:40 | 9.07 | 5.19 | 0.186761E+09 | 260.10 | 07-DEC-10:50 | 5.55 | 2.29 |
Annual Sum or Average | 0.272692E+11 | 0.266711E+10 | ||||||||
Minimum of Months | 46741303.60 | 1513.12 | 7.50 | 1.66 | 0.177653E+09 | 257.58 | 5.55 | 1.66 | ||
Maximum of Months | 0.555712E+10 | 13940.23 | 29.53 | 16.30 | 0.282538E+09 | 347.90 | 29.53 | 16.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414781E+09 | 3270.75 | 14-JAN-12:40 | 10.40 | 5.04 | 0.282520E+09 | 448.55 | 13-JAN-14:00 | 10.40 | 5.04 |
February | 0.988597E+09 | 7365.98 | 27-FEB-13:17 | 17.57 | 6.67 | 0.278681E+09 | 549.50 | 28-FEB-14:30 | 10.30 | 4.65 |
March | 0.128452E+10 | 4719.52 | 01-MAR-14:40 | 7.77 | 3.23 | 0.342217E+09 | 549.50 | 01-MAR-14:20 | 7.77 | 3.23 |
April | 0.181502E+10 | 4939.17 | 06-APR-14:30 | 20.85 | 10.20 | 0.311884E+09 | 549.50 | 06-APR-13:20 | 20.85 | 10.20 |
May | 0.271642E+10 | 6844.97 | 19-MAY-14:00 | 27.20 | 15.02 | 0.348369E+09 | 549.50 | 19-MAY-13:20 | 27.20 | 15.02 |
June | 0.509508E+10 | 10868.98 | 23-JUN-12:00 | 30.00 | 15.51 | 0.388877E+09 | 549.51 | 29-JUN-13:00 | 31.70 | 14.68 |
July | 0.740620E+10 | 16595.02 | 17-JUL-16:10 | 37.02 | 17.24 | 0.387526E+09 | 549.51 | 28-JUL-13:00 | 24.40 | 13.30 |
August | 0.799024E+10 | 16602.95 | 07-AUG-12:00 | 32.80 | 15.97 | 0.431837E+09 | 549.51 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.602570E+10 | 22487.49 | 04-SEP-15:51 | 32.80 | 16.49 | 0.364149E+09 | 549.53 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.423156E+10 | 11398.60 | 18-OCT-13:50 | 24.90 | 11.31 | 0.361782E+09 | 549.51 | 18-OCT-13:20 | 24.90 | 11.31 |
November | 0.211126E+10 | 7402.94 | 03-NOV-13:50 | 14.78 | 7.82 | 0.327648E+09 | 549.50 | 10-NOV-14:30 | 5.80 | 0.98 |
December | 0.783639E+09 | 3639.00 | 06-DEC-14:50 | 11.20 | 5.38 | 0.290780E+09 | 523.58 | 06-DEC-14:00 | 11.10 | 5.34 |
Annual Sum or Average | 0.408630E+11 | 0.411627E+10 | ||||||||
Minimum of Months | 0.414781E+09 | 3270.75 | 7.77 | 3.23 | 0.278681E+09 | 448.55 | 5.80 | 0.98 | ||
Maximum of Months | 0.799024E+10 | 22487.49 | 37.02 | 17.24 | 0.431837E+09 | 549.53 | 32.80 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70167960.90 | 1852.67 | 13-JAN-15:50 | 9.08 | 4.76 | 0.192827E+09 | 267.14 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.354623E+09 | 2580.33 | 28-FEB-16:50 | 10.18 | 4.40 | 0.177985E+09 | 337.51 | 28-FEB-16:00 | 10.00 | 4.31 |
March | 0.687409E+09 | 2561.41 | 01-MAR-16:50 | 8.07 | 3.33 | 0.213926E+09 | 335.74 | 01-MAR-16:00 | 7.80 | 3.22 |
April | 0.133394E+10 | 4458.61 | 25-APR-17:30 | 17.50 | 7.72 | 0.194451E+09 | 338.67 | 25-APR-15:00 | 17.50 | 7.72 |
May | 0.241269E+10 | 5597.37 | 19-MAY-17:50 | 25.68 | 14.33 | 0.223105E+09 | 347.72 | 19-MAY-13:00 | 25.68 | 14.33 |
June | 0.390637E+10 | 8793.89 | 24-JUN-17:07 | 27.52 | 12.47 | 0.250599E+09 | 347.85 | 29-JUN-13:20 | 32.03 | 14.50 |
July | 0.501191E+10 | 15275.09 | 16-JUL-18:01 | 32.70 | 16.90 | 0.247034E+09 | 347.85 | 26-JUL-09:20 | 27.80 | 14.33 |
August | 0.481073E+10 | 14674.90 | 06-AUG-16:21 | 35.30 | 16.02 | 0.271296E+09 | 347.85 | 09-AUG-09:20 | 27.60 | 15.89 |
September | 0.348085E+10 | 15643.19 | 04-SEP-17:11 | 32.43 | 16.63 | 0.224581E+09 | 347.85 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.230045E+10 | 5307.61 | 18-OCT-16:00 | 24.40 | 11.02 | 0.215440E+09 | 346.43 | 18-OCT-13:00 | 24.40 | 11.02 |
November | 0.105786E+10 | 2578.32 | 03-NOV-15:50 | 14.35 | 7.69 | 0.199235E+09 | 336.77 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.274991E+09 | 2099.73 | 06-DEC-15:50 | 9.68 | 4.65 | 0.187226E+09 | 290.26 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.257020E+11 | 0.259770E+10 | ||||||||
Minimum of Months | 70167960.90 | 1852.67 | 8.07 | 3.33 | 0.177985E+09 | 267.14 | 7.80 | 3.22 | ||
Maximum of Months | 0.501191E+10 | 15643.19 | 35.30 | 16.90 | 0.271296E+09 | 347.85 | 32.03 | 15.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61657135.69 | 2289.87 | 14-JAN-17:02 | 8.90 | 4.06 | 0.304517E+09 | 406.84 | 10-JAN-14:30 | 8.90 | 4.06 |
February | 0.455531E+09 | 2830.94 | 27-FEB-16:10 | 17.78 | 6.92 | 0.278488E+09 | 436.46 | 27-FEB-14:00 | 17.78 | 6.92 |
March | 0.134061E+10 | 2973.88 | 29-MAR-16:00 | 12.20 | 4.07 | 0.336778E+09 | 453.14 | 29-MAR-13:00 | 12.20 | 4.07 |
April | 0.245917E+10 | 3630.69 | 07-APR-14:40 | 22.23 | 9.16 | 0.314512E+09 | 528.82 | 07-APR-13:00 | 22.23 | 9.16 |
May | 0.364647E+10 | 5157.02 | 19-MAY-16:00 | 27.80 | 14.54 | 0.361383E+09 | 549.50 | 19-MAY-13:20 | 27.80 | 14.54 |
June | 0.563627E+10 | 6580.36 | 29-JUN-15:20 | 31.83 | 14.57 | 0.410162E+09 | 549.51 | 27-JUN-13:50 | 31.83 | 14.57 |
July | 0.647625E+10 | 7386.16 | 17-JUL-16:00 | 37.20 | 17.28 | 0.394091E+09 | 549.51 | 13-JUL-09:00 | 37.20 | 17.28 |
August | 0.600402E+10 | 7194.62 | 09-AUG-14:50 | 33.40 | 16.01 | 0.432266E+09 | 549.50 | 09-AUG-09:20 | 33.40 | 16.01 |
September | 0.431190E+10 | 5794.29 | 04-SEP-15:51 | 32.80 | 16.49 | 0.350431E+09 | 549.50 | 05-SEP-13:50 | 24.22 | 15.03 |
October | 0.270057E+10 | 3883.37 | 15-OCT-14:32 | 22.97 | 11.08 | 0.330099E+09 | 520.75 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.117877E+10 | 2846.07 | 08-NOV-14:10 | 13.78 | 7.92 | 0.307249E+09 | 447.73 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.273285E+09 | 2282.77 | 09-DEC-17:02 | 11.52 | 4.10 | 0.294458E+09 | 406.83 | 28-DEC-14:09 | -20.1 | -20.6 |
Annual Sum or Average | 0.345445E+11 | 0.411443E+10 | ||||||||
Minimum of Months | 61657135.69 | 2282.77 | 8.90 | 4.06 | 0.278488E+09 | 406.83 | -20.1 | -20.6 | ||
Maximum of Months | 0.647625E+10 | 7386.16 | 37.20 | 17.28 | 0.432266E+09 | 549.51 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103334E+09 | 2250.36 | 14-JAN-11:02 | 8.58 | 4.13 | 0.141588E+09 | 287.33 | 20-JAN-11:09 | -1.9 | -4.9 |
February | 0.513263E+09 | 3815.75 | 28-FEB-11:02 | 4.37 | 1.41 | 0.132736E+09 | 356.45 | 28-FEB-11:09 | 4.37 | 1.41 |
March | 0.117076E+10 | 4961.46 | 23-MAR-10:05 | 8.40 | 1.62 | 0.165760E+09 | 356.46 | 01-MAR-11:09 | 8.40 | 1.62 |
April | 0.212443E+10 | 6665.45 | 25-APR-10:05 | 12.57 | 5.85 | 0.159359E+09 | 356.46 | 13-APR-14:09 | 12.57 | 5.85 |
May | 0.309512E+10 | 7676.88 | 19-MAY-10:05 | 20.37 | 12.65 | 0.181700E+09 | 356.48 | 02-MAY-12:09 | 20.37 | 12.65 |
June | 0.525295E+10 | 12731.70 | 25-JUN-09:32 | 18.50 | 12.34 | 0.197634E+09 | 356.47 | 28-JUN-10:09 | 24.78 | 12.68 |
July | 0.638059E+10 | 13606.48 | 16-JUL-11:12 | 26.33 | 17.11 | 0.187657E+09 | 356.48 | 13-JUL-10:09 | 26.33 | 17.11 |
August | 0.585425E+10 | 16541.22 | 06-AUG-08:52 | 27.20 | 14.17 | 0.207812E+09 | 356.47 | 08-AUG-10:09 | 24.18 | 14.57 |
September | 0.357260E+10 | 16786.55 | 04-SEP-08:31 | 26.33 | 14.69 | 0.172107E+09 | 356.46 | 07-SEP-10:09 | 16.88 | 15.79 |
October | 0.202977E+10 | 5711.52 | 18-OCT-10:05 | 20.28 | 8.90 | 0.164691E+09 | 356.46 | 18-OCT-14:09 | 25.00 | 11.44 |
November | 0.870240E+09 | 4517.86 | 03-NOV-12:02 | 12.62 | 7.22 | 0.147603E+09 | 356.46 | 02-NOV-10:09 | 12.62 | 7.22 |
December | 0.244373E+09 | 2511.28 | 07-DEC-11:02 | 6.38 | 2.62 | 0.137616E+09 | 315.01 | 07-DEC-11:09 | 6.38 | 2.62 |
Annual Sum or Average | 0.312117E+11 | 0.199626E+10 | ||||||||
Minimum of Months | 0.103334E+09 | 2250.36 | 4.37 | 1.41 | 0.132736E+09 | 287.33 | -1.9 | -4.9 | ||
Maximum of Months | 0.638059E+10 | 16786.55 | 27.20 | 17.11 | 0.207812E+09 | 356.48 | 26.33 | 17.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111135E+10 | 5412.44 | 19-JAN-13:40 | -6.0 | -7.8 | 0.319190E+09 | 549.49 | 19-JAN-14:00 | -5.0 | -6.9 |
February | 0.229509E+10 | 10910.80 | 27-FEB-13:30 | 17.75 | 6.76 | 0.309097E+09 | 549.50 | 27-FEB-14:30 | 18.60 | 7.13 |
March | 0.332236E+10 | 10862.12 | 01-MAR-13:50 | 6.52 | 2.64 | 0.375257E+09 | 549.50 | 14-MAR-13:30 | 15.00 | 6.74 |
April | 0.379345E+10 | 10093.90 | 25-APR-13:30 | 16.40 | 7.12 | 0.341984E+09 | 549.50 | 13-APR-13:20 | 16.40 | 7.12 |
May | 0.469530E+10 | 10043.79 | 19-MAY-13:30 | 26.65 | 14.96 | 0.383834E+09 | 549.53 | 02-MAY-13:09 | 26.65 | 14.96 |
June | 0.686594E+10 | 10402.35 | 23-JUN-13:10 | 31.20 | 15.18 | 0.413143E+09 | 549.51 | 27-JUN-13:50 | 24.53 | 13.02 |
July | 0.841143E+10 | 20719.84 | 16-JUL-13:12 | 30.17 | 18.28 | 0.395045E+09 | 549.52 | 28-JUL-13:00 | 24.40 | 13.30 |
August | 0.911929E+10 | 21149.98 | 06-AUG-12:12 | 33.17 | 14.59 | 0.439083E+09 | 550.10 | 30-AUG-13:20 | 25.97 | 14.23 |
September | 0.708161E+10 | 22651.57 | 04-SEP-15:51 | 32.80 | 16.49 | 0.372536E+09 | 550.08 | 05-SEP-13:20 | 23.67 | 14.70 |
October | 0.522755E+10 | 21723.19 | 15-OCT-13:52 | 23.30 | 11.17 | 0.374234E+09 | 549.61 | 18-OCT-13:20 | 24.60 | 11.01 |
November | 0.304630E+10 | 11309.40 | 03-NOV-13:25 | 14.35 | 7.74 | 0.348266E+09 | 549.50 | 06-NOV-14:30 | 8.05 | 3.12 |
December | 0.159381E+10 | 6169.11 | 07-DEC-13:40 | 8.67 | 3.00 | 0.318559E+09 | 549.50 | 06-DEC-14:30 | 8.67 | 3.00 |
Annual Sum or Average | 0.565635E+11 | 0.439023E+10 | ||||||||
Minimum of Months | 0.111135E+10 | 5412.44 | -6.0 | -7.8 | 0.309097E+09 | 549.49 | -5.0 | -6.9 | ||
Maximum of Months | 0.911929E+10 | 22651.57 | 33.17 | 18.28 | 0.439083E+09 | 550.10 | 26.65 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161159E+09 | 2397.51 | 13-JAN-15:50 | 9.08 | 4.76 | 0.193260E+09 | 281.35 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.652903E+09 | 4085.84 | 28-FEB-16:40 | 10.37 | 4.49 | 0.179686E+09 | 338.68 | 28-FEB-16:00 | 10.00 | 4.31 |
March | 0.134601E+10 | 4810.50 | 28-MAR-16:00 | 10.60 | 3.09 | 0.218251E+09 | 341.28 | 02-MAR-14:00 | 10.60 | 3.09 |
April | 0.237792E+10 | 7294.73 | 25-APR-16:00 | 17.80 | 7.70 | 0.201337E+09 | 338.68 | 06-APR-15:09 | 17.80 | 7.70 |
May | 0.351097E+10 | 17402.07 | 28-MAY-17:32 | 20.37 | 10.36 | 0.229817E+09 | 347.85 | 19-MAY-13:00 | 20.37 | 10.36 |
June | 0.522513E+10 | 13783.30 | 24-JUN-17:04 | 27.52 | 12.47 | 0.253171E+09 | 347.86 | 27-JUN-13:50 | 24.53 | 13.02 |
July | 0.612497E+10 | 18385.27 | 09-JUL-16:51 | 28.30 | 12.98 | 0.244546E+09 | 347.86 | 28-JUL-13:00 | 24.40 | 13.30 |
August | 0.572937E+10 | 17311.47 | 06-AUG-16:12 | 35.40 | 16.13 | 0.268075E+09 | 347.85 | 01-AUG-13:20 | 35.40 | 16.13 |
September | 0.393502E+10 | 19057.08 | 04-SEP-15:51 | 32.80 | 16.49 | 0.219951E+09 | 347.85 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.241475E+10 | 6476.54 | 18-OCT-16:00 | 24.40 | 11.02 | 0.211628E+09 | 346.56 | 18-OCT-13:00 | 24.40 | 11.02 |
November | 0.113745E+10 | 3274.08 | 03-NOV-15:40 | 14.40 | 7.69 | 0.199054E+09 | 338.67 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.375467E+09 | 2595.07 | 06-DEC-15:50 | 9.68 | 4.65 | 0.187390E+09 | 296.67 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.329911E+11 | 0.260617E+10 | ||||||||
Minimum of Months | 0.161159E+09 | 2397.51 | 9.08 | 3.09 | 0.179686E+09 | 281.35 | 8.90 | 3.09 | ||
Maximum of Months | 0.612497E+10 | 19057.08 | 35.40 | 16.49 | 0.268075E+09 | 347.86 | 35.40 | 16.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61788447.58 | 10196.08 | 02-JAN-06:01 | -1.3 |
February | 5290304.79 | 8681.53 | 06-FEB-06:01 | 0.60 |
March | 2208367.97 | 7361.34 | 06-MAR-07:01 | -19.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 1988545.16 | 7209.62 | 26-DEC-07:01 | -8.5 |
Annual Sum or Average | 71275665.50 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 61788447.58 | 10196.08 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179491E+11 | 31085.12 | 11-JAN-05:11 | -30.2 |
February | 0.941500E+10 | 27327.43 | 04-FEB-06:06 | -19.5 |
March | 0.697509E+10 | 28480.41 | 06-MAR-06:09 | -16.3 |
April | 0.276809E+10 | 18328.94 | 29-APR-05:02 | -7.7 |
May | 0.195688E+10 | 19344.76 | 08-MAY-05:13 | -2.8 |
June | 0.474459E+09 | 11885.87 | 17-JUN-05:02 | 2.35 |
July | 0.222063E+09 | 8655.01 | 12-JUL-05:03 | 6.85 |
August | 0.407569E+09 | 8461.96 | 03-AUG-05:03 | 8.12 |
September | 0.113090E+10 | 10049.15 | 20-SEP-05:15 | 3.30 |
October | 0.290698E+10 | 18631.66 | 10-OCT-06:03 | -6.1 |
November | 0.720924E+10 | 25767.58 | 27-NOV-05:23 | -15.1 |
December | 0.139046E+11 | 29412.64 | 29-DEC-06:06 | -25.1 |
Annual Sum or Average | 0.653200E+11 | |||
Minimum of Months | 0.222063E+09 | 8461.96 | -30.2 | |
Maximum of Months | 0.179491E+11 | 31085.12 | 8.12 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466433E+10 | 12267.41 | 09-JAN-08:08 | -27.1 |
February | 0.249186E+10 | 11613.24 | 06-FEB-07:12 | 0.40 |
March | 0.169507E+10 | 10573.36 | 06-MAR-07:11 | -19.4 |
April | 0.468511E+09 | 5466.19 | 16-APR-12:42 | 18.12 |
May | 0.548987E+09 | 5489.45 | 08-MAY-06:02 | -2.7 |
June | 21872313.18 | 4138.29 | 18-JUN-12:52 | 22.20 |
July | 27480105.48 | 4642.53 | 09-JUL-16:51 | 28.30 |
August | 25466498.43 | 5588.81 | 06-AUG-15:32 | 35.20 |
September | 0.149523E+09 | 5553.11 | 04-SEP-15:11 | 32.40 |
October | 0.621638E+09 | 8185.05 | 15-OCT-13:52 | 23.30 |
November | 0.180620E+10 | 10548.39 | 27-NOV-07:15 | -13.4 |
December | 0.314089E+10 | 11304.87 | 26-DEC-07:11 | -8.7 |
Annual Sum or Average | 0.156618E+11 | |||
Minimum of Months | 21872313.18 | 4138.29 | -27.1 | |
Maximum of Months | 0.466433E+10 | 12267.41 | 35.20 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304875E+10 | 7486.50 | 02-JAN-06:13 | -1.5 |
February | 0.135969E+10 | 6893.93 | 06-FEB-07:01 | 0.50 |
March | 0.728580E+09 | 6490.86 | 06-MAR-08:50 | -11.4 |
April | 74865333.46 | 2456.06 | 28-APR-07:07 | -3.2 |
May | 0.176114E+09 | 3401.98 | 22-MAY-05:01 | -0.6 |
June | 5489658.98 | 3566.94 | 18-JUN-15:32 | 24.80 |
July | 13960183.03 | 3953.02 | 09-JUL-14:48 | 28.12 |
August | 8989399.54 | 3544.27 | 13-AUG-16:08 | 16.88 |
September | 17424435.66 | 3357.13 | 04-SEP-16:31 | 32.80 |
October | 90877596.41 | 6981.46 | 31-OCT-05:01 | 1.60 |
November | 0.664403E+09 | 5338.86 | 27-NOV-08:40 | -12.2 |
December | 0.168064E+10 | 6435.86 | 26-DEC-07:01 | -8.5 |
Annual Sum or Average | 0.786979E+10 | |||
Minimum of Months | 5489658.98 | 2456.06 | -12.2 | |
Maximum of Months | 0.304875E+10 | 7486.50 | 32.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102598E+10 | 21118.02 | 09-JAN-05:11 | -27.2 |
February | 0.243808E+09 | 20013.72 | 06-FEB-05:01 | -0.4 |
March | 0.146874E+09 | 19400.24 | 06-MAR-05:01 | -18.4 |
April | 781259.42 | 4422.65 | 10-APR-06:03 | 3.90 |
May | 16594138.36 | 15748.46 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 5677770.04 | 15364.28 | 10-OCT-06:01 | -6.1 |
November | 0.125007E+09 | 18310.89 | 27-NOV-06:01 | -14.5 |
December | 0.372304E+09 | 19796.37 | 26-DEC-05:11 | -7.4 |
Annual Sum or Average | 0.193703E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.102598E+10 | 21118.02 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.574685E+10 | 35617.89 | 02-JAN-05:11 | -0.4 |
February | 0.232972E+10 | 35652.66 | 06-FEB-05:01 | -0.4 |
March | 0.139602E+10 | 35454.25 | 06-MAR-05:01 | -18.4 |
April | 0.231828E+09 | 29522.36 | 29-APR-05:01 | -7.7 |
May | 0.308906E+09 | 32504.58 | 08-MAY-04:01 | -2.3 |
June | 3607932.60 | 18039.66 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 765778.25 | 3828.89 | 18-AUG-06:03 | 8.17 |
September | 23055784.81 | 25454.32 | 19-SEP-06:03 | 2.20 |
October | 0.258517E+09 | 32353.91 | 10-OCT-04:01 | -5.2 |
November | 0.135670E+10 | 35833.29 | 27-NOV-05:11 | -15.3 |
December | 0.349181E+10 | 35404.80 | 18-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.151478E+11 | |||
Minimum of Months | 0.00 | 0.00 | -18.4 | |
Maximum of Months | 0.574685E+10 | 35833.29 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.954562E+10 | 17734.10 | 29-JAN-20:01 | -26.1 |
February | 0.471291E+10 | 17469.67 | 06-FEB-00:02 | -4.8 |
March | 0.302084E+10 | 17901.83 | 06-MAR-05:21 | -17.2 |
April | 0.793938E+09 | 15828.96 | 29-APR-04:01 | -7.8 |
May | 0.559561E+09 | 15712.60 | 08-MAY-04:01 | -2.3 |
June | 21966043.73 | 11845.69 | 17-JUN-05:02 | 2.35 |
July | 1592248.43 | 3989.64 | 05-JUL-06:03 | 9.40 |
August | 12544479.67 | 11934.63 | 18-AUG-05:12 | 7.40 |
September | 0.174157E+09 | 13939.67 | 20-SEP-05:11 | 3.30 |
October | 0.791759E+09 | 16292.89 | 10-OCT-04:01 | -5.2 |
November | 0.302561E+10 | 17598.89 | 27-NOV-05:11 | -15.3 |
December | 0.679071E+10 | 17703.35 | 31-DEC-20:51 | -24.4 |
Annual Sum or Average | 0.294512E+11 | |||
Minimum of Months | 1592248.43 | 3989.64 | -26.1 | |
Maximum of Months | 0.954562E+10 | 17901.83 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.570341E+10 | 11610.35 | 08-JAN-18:41 | -27.2 |
February | 0.267932E+10 | 11446.53 | 05-FEB-01:22 | -19.7 |
March | 0.169775E+10 | 11736.39 | 06-MAR-05:21 | -17.2 |
April | 0.386346E+09 | 10413.38 | 29-APR-04:01 | -7.8 |
May | 0.288051E+09 | 10350.39 | 09-MAY-04:01 | -1.8 |
June | 7752573.65 | 7228.48 | 17-JUN-05:02 | 2.35 |
July | 496924.33 | 2484.62 | 05-JUL-06:03 | 9.40 |
August | 3908517.26 | 8054.48 | 18-AUG-05:12 | 7.40 |
September | 87475162.91 | 9132.06 | 20-SEP-05:11 | 3.30 |
October | 0.423782E+09 | 10656.62 | 10-OCT-04:01 | -5.2 |
November | 0.174301E+10 | 11529.90 | 27-NOV-05:11 | -15.3 |
December | 0.406244E+10 | 11592.64 | 31-DEC-20:51 | -24.4 |
Annual Sum or Average | 0.170837E+11 | |||
Minimum of Months | 496924.33 | 2484.62 | -27.2 | |
Maximum of Months | 0.570341E+10 | 11736.39 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.723861E+10 | 17803.11 | 08-JAN-06:01 | -26.8 |
February | 0.330298E+10 | 17565.38 | 05-FEB-01:22 | -19.7 |
March | 0.234664E+10 | 18081.50 | 06-MAR-05:21 | -17.2 |
April | 0.698631E+09 | 16024.31 | 29-APR-04:01 | -7.8 |
May | 0.573488E+09 | 15935.43 | 09-MAY-04:01 | -1.8 |
June | 36003940.87 | 12596.72 | 17-JUN-05:02 | 2.35 |
July | 3254926.71 | 4798.29 | 08-JUL-06:03 | 9.78 |
August | 14805295.88 | 12085.76 | 18-AUG-05:12 | 7.40 |
September | 0.138694E+09 | 14018.54 | 19-SEP-05:11 | 2.20 |
October | 0.559009E+09 | 16461.84 | 10-OCT-04:01 | -5.2 |
November | 0.211907E+10 | 17779.49 | 27-NOV-05:11 | -15.3 |
December | 0.501277E+10 | 17832.25 | 31-DEC-06:51 | -28.3 |
Annual Sum or Average | 0.220440E+11 | |||
Minimum of Months | 3254926.71 | 4798.29 | -28.3 | |
Maximum of Months | 0.723861E+10 | 18081.50 | 9.78 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.603941E+10 | 12003.77 | 08-JAN-06:01 | -26.8 |
February | 0.285958E+10 | 11792.37 | 06-FEB-00:42 | -4.1 |
March | 0.188981E+10 | 12183.92 | 06-MAR-05:21 | -17.2 |
April | 0.490622E+09 | 10676.99 | 29-APR-04:01 | -7.8 |
May | 0.371291E+09 | 10594.86 | 08-MAY-04:01 | -2.3 |
June | 22732560.78 | 8396.61 | 17-JUN-05:02 | 2.35 |
July | 1782611.19 | 2846.63 | 08-JUL-06:03 | 9.78 |
August | 10665590.00 | 8308.01 | 18-AUG-05:12 | 7.40 |
September | 0.108592E+09 | 9436.60 | 19-SEP-05:11 | 2.20 |
October | 0.489262E+09 | 11032.33 | 10-OCT-04:01 | -5.2 |
November | 0.187037E+10 | 11964.19 | 27-NOV-05:11 | -15.3 |
December | 0.428602E+10 | 11981.85 | 31-DEC-06:51 | -28.3 |
Annual Sum or Average | 0.184401E+11 | |||
Minimum of Months | 1782611.19 | 2846.63 | -28.3 | |
Maximum of Months | 0.603941E+10 | 12183.92 | 9.78 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.705148E+10 | 13609.82 | 09-JAN-03:11 | -27.2 |
February | 0.359239E+10 | 13038.24 | 06-FEB-05:11 | -0.2 |
March | 0.233448E+10 | 13505.07 | 06-MAR-04:22 | -18.6 |
April | 0.652501E+09 | 10643.35 | 29-APR-05:01 | -7.7 |
May | 0.319233E+09 | 11494.79 | 08-MAY-04:01 | -2.3 |
June | 4772122.93 | 5732.24 | 16-JUN-06:03 | 2.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 519590.71 | 2597.95 | 18-AUG-06:03 | 8.17 |
September | 16730338.94 | 7850.34 | 19-SEP-06:03 | 2.20 |
October | 0.106934E+09 | 10389.58 | 10-OCT-05:01 | -6.1 |
November | 0.104623E+10 | 12795.13 | 27-NOV-05:11 | -15.3 |
December | 0.353658E+10 | 13249.20 | 31-DEC-21:21 | -24.1 |
Annual Sum or Average | 0.186618E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.705148E+10 | 13609.82 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405784E+10 | 8982.48 | 09-JAN-03:11 | -27.2 |
February | 0.190150E+10 | 8549.37 | 06-FEB-05:11 | -0.2 |
March | 0.110930E+10 | 8892.71 | 06-MAR-04:22 | -18.6 |
April | 0.232799E+09 | 6993.68 | 29-APR-05:01 | -7.7 |
May | 0.134915E+09 | 7505.68 | 08-MAY-04:01 | -2.3 |
June | 1216542.98 | 3306.64 | 16-JUN-06:03 | 2.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 4479721.97 | 4792.32 | 20-SEP-06:03 | 3.48 |
October | 43562471.08 | 6787.76 | 10-OCT-05:01 | -6.1 |
November | 0.571203E+09 | 8410.87 | 27-NOV-05:11 | -15.3 |
December | 0.203550E+10 | 8726.37 | 31-DEC-21:21 | -24.1 |
Annual Sum or Average | 0.100923E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.405784E+10 | 8982.48 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.895002E+10 | 18722.17 | 09-JAN-08:00 | -27.2 |
February | 0.483089E+10 | 17229.23 | 01-FEB-07:10 | -24.9 |
March | 0.387475E+10 | 16643.97 | 06-MAR-07:50 | -18.6 |
April | 0.209217E+10 | 12502.34 | 28-APR-06:10 | -5.2 |
May | 0.171241E+10 | 12391.59 | 08-MAY-07:00 | -2.2 |
June | 0.357177E+09 | 10241.39 | 16-JUN-07:00 | 2.20 |
July | 44253648.05 | 6309.96 | 05-JUL-06:03 | 9.40 |
August | 0.210463E+09 | 9233.26 | 18-AUG-06:03 | 8.17 |
September | 0.541853E+09 | 10167.63 | 19-SEP-06:10 | 2.20 |
October | 0.954530E+09 | 12679.77 | 10-OCT-06:10 | -6.1 |
November | 0.250047E+10 | 15001.64 | 27-NOV-07:50 | -13.0 |
December | 0.544732E+10 | 18319.62 | 29-DEC-08:00 | -27.8 |
Annual Sum or Average | 0.315163E+11 | |||
Minimum of Months | 44253648.05 | 6309.96 | -27.8 | |
Maximum of Months | 0.895002E+10 | 18722.17 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434968E+10 | 9177.45 | 09-JAN-03:11 | -27.2 |
February | 0.199080E+10 | 8785.83 | 06-FEB-05:11 | -0.2 |
March | 0.125709E+10 | 9136.74 | 06-MAR-04:22 | -18.6 |
April | 0.300535E+09 | 7157.15 | 10-APR-05:11 | 3.90 |
May | 0.158599E+09 | 7706.18 | 08-MAY-04:01 | -2.3 |
June | 2670245.15 | 3582.13 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 630702.67 | 2933.32 | 18-AUG-06:03 | 8.17 |
September | 6206443.72 | 4832.82 | 19-SEP-06:03 | 2.20 |
October | 52487220.14 | 7009.43 | 10-OCT-05:01 | -6.1 |
November | 0.598694E+09 | 8640.42 | 27-NOV-05:11 | -15.3 |
December | 0.217123E+10 | 8960.85 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.108886E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.434968E+10 | 9177.45 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613516E+10 | 13654.99 | 09-JAN-05:11 | -27.2 |
February | 0.264689E+10 | 13024.73 | 05-FEB-21:03 | -17.7 |
March | 0.134847E+10 | 13554.56 | 06-MAR-03:42 | -18.4 |
April | 0.200178E+09 | 10775.08 | 29-APR-05:01 | -7.7 |
May | 0.168146E+09 | 11576.48 | 08-MAY-04:01 | -2.3 |
June | 1745528.15 | 4981.70 | 16-JUN-06:03 | 2.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 609471.95 | 3047.36 | 18-AUG-06:03 | 8.17 |
September | 22290386.80 | 9478.22 | 19-SEP-05:11 | 2.20 |
October | 0.175628E+09 | 11345.97 | 10-OCT-04:01 | -5.2 |
November | 0.124950E+10 | 12946.13 | 27-NOV-05:01 | -15.4 |
December | 0.356370E+10 | 13089.52 | 31-DEC-21:02 | -24.3 |
Annual Sum or Average | 0.155123E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.613516E+10 | 13654.99 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363936E+10 | 9874.00 | 09-JAN-05:11 | -27.2 |
February | 0.148908E+10 | 9316.02 | 05-FEB-07:42 | -20.0 |
March | 0.745060E+09 | 9752.14 | 06-MAR-03:42 | -18.4 |
April | 92110581.21 | 7694.81 | 29-APR-05:01 | -7.7 |
May | 92264394.19 | 8252.30 | 08-MAY-04:01 | -2.3 |
June | 800901.85 | 3194.94 | 16-JUN-06:03 | 2.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 11881074.66 | 6677.98 | 20-SEP-05:11 | 3.30 |
October | 95833683.14 | 8109.17 | 10-OCT-04:01 | -5.2 |
November | 0.741762E+09 | 9311.00 | 27-NOV-05:01 | -15.4 |
December | 0.213004E+10 | 9405.92 | 31-DEC-07:42 | -27.9 |
Annual Sum or Average | 0.903818E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.363936E+10 | 9874.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431624E+10 | 13790.94 | 09-JAN-05:11 | -27.2 |
February | 0.166229E+10 | 13105.58 | 05-FEB-05:42 | -20.0 |
March | 0.964337E+09 | 13693.81 | 06-MAR-04:22 | -18.6 |
April | 0.172628E+09 | 10941.27 | 29-APR-05:01 | -7.7 |
May | 0.180442E+09 | 11642.89 | 08-MAY-04:01 | -2.3 |
June | 2974743.26 | 5272.67 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 991745.62 | 4711.12 | 18-AUG-06:03 | 8.17 |
September | 16681304.83 | 9546.07 | 19-SEP-05:11 | 2.20 |
October | 0.113754E+09 | 11431.07 | 10-OCT-04:01 | -5.2 |
November | 0.850989E+09 | 13084.37 | 27-NOV-05:01 | -15.4 |
December | 0.242225E+10 | 13256.55 | 31-DEC-07:42 | -27.9 |
Annual Sum or Average | 0.107036E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.431624E+10 | 13790.94 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389393E+10 | 10259.22 | 09-JAN-05:11 | -27.2 |
February | 0.158742E+10 | 9628.28 | 05-FEB-07:42 | -20.0 |
March | 0.859544E+09 | 10181.30 | 06-MAR-03:42 | -18.4 |
April | 0.134405E+09 | 7913.14 | 29-APR-05:01 | -7.7 |
May | 0.119257E+09 | 8595.47 | 08-MAY-04:01 | -2.3 |
June | 2614020.21 | 3374.03 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 921629.98 | 3028.89 | 18-AUG-06:03 | 8.17 |
September | 16202082.07 | 6963.40 | 19-SEP-05:11 | 2.20 |
October | 0.115996E+09 | 8447.51 | 10-OCT-04:01 | -5.2 |
November | 0.797159E+09 | 9718.31 | 27-NOV-05:01 | -15.4 |
December | 0.228465E+10 | 9815.61 | 31-DEC-07:42 | -27.9 |
Annual Sum or Average | 0.981210E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.389393E+10 | 10259.22 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.219109E+11 | 14257.50 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.198568E+11 | 14257.50 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.225201E+11 | 14257.50 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.212729E+11 | 14257.50 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.222155E+11 | 14257.50 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.217316E+11 | 14257.50 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.217545E+11 | 14257.50 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.225201E+11 | 14257.50 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.212685E+11 | 14257.50 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.219131E+11 | 14257.50 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.212833E+11 | 14257.50 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.217523E+11 | 14257.50 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.259999E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.198568E+11 | 14257.50 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.225201E+11 | 14257.50 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.932724E+10 | 9760.61 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.846050E+10 | 9760.61 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.100534E+11 | 9760.61 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.897976E+10 | 9760.61 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.969033E+10 | 9760.61 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.964348E+10 | 9760.61 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.902661E+10 | 9760.61 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.100534E+11 | 9760.61 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.897976E+10 | 9760.61 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.932724E+10 | 9760.61 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.921792E+10 | 9760.61 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.902661E+10 | 9760.61 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.111786E+12 | 0.115425E+12 | ||||
Minimum of Months | 0.846050E+10 | 9760.61 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.100534E+11 | 9760.61 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124481E+10 | 1302.65 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112913E+10 | 1302.65 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134172E+10 | 1302.65 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119843E+10 | 1302.65 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129327E+10 | 1302.65 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128701E+10 | 1302.65 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120469E+10 | 1302.65 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134172E+10 | 1302.65 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119843E+10 | 1302.65 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124481E+10 | 1302.65 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123022E+10 | 1302.65 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120469E+10 | 1302.65 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149189E+11 | 0.154036E+11 | ||||
Minimum of Months | 0.112913E+10 | 1302.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134172E+10 | 1302.65 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.196626E+10 | 2057.62 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.178355E+10 | 2057.62 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.211935E+10 | 2057.62 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.189301E+10 | 2057.62 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.204281E+10 | 2057.62 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.203293E+10 | 2057.62 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.190289E+10 | 2057.62 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.211935E+10 | 2057.62 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.189301E+10 | 2057.62 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.196626E+10 | 2057.62 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.194322E+10 | 2057.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.190289E+10 | 2057.62 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.235655E+11 | 0.243324E+11 | ||||
Minimum of Months | 0.178355E+10 | 2057.62 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.211935E+10 | 2057.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124473E+10 | 1302.56 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.112906E+10 | 1302.56 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.134164E+10 | 1302.56 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.119835E+10 | 1302.56 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.129318E+10 | 1302.56 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.128693E+10 | 1302.56 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.120461E+10 | 1302.56 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.134164E+10 | 1302.56 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.119835E+10 | 1302.56 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.124473E+10 | 1302.56 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.123014E+10 | 1302.56 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.120461E+10 | 1302.56 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.149180E+11 | 0.154035E+11 | ||||
Minimum of Months | 0.112906E+10 | 1302.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.134164E+10 | 1302.56 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.219109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.212729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.222155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.217316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.212685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.219131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.212833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.217523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.259999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.198568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.225201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.932724E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.897976E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.969033E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.964348E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.902661E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.897976E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.932724E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.921792E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.902661E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111786E+12 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.846050E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.100534E+11 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172490E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127827E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118484E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3890.25 | 0.811763E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3599353.88 | 0.820219E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15078558.27 | 0.418085E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55323858.12 | 0.276954E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41183943.31 | 0.302851E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32598529.69 | 0.533862E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3321486.16 | 0.754658E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113294E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149683E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151110E+09 | 0.107362E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276954E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55323858.12 | 0.172490E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115282E+10 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864511E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800574E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559932E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2020624.15 | 0.555849E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9091728.54 | 0.291765E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31354105.63 | 0.197403E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24568433.09 | 0.212873E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17373188.62 | 0.372000E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1094527.41 | 0.519601E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759602E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999697E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85502607.45 | 0.728663E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197403E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31354105.63 | 0.115282E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175924E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135675E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123819E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856229E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2599210.27 | 0.844406E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13315567.28 | 0.427383E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46996955.74 | 0.285601E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36754821.15 | 0.319637E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22764163.84 | 0.572065E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129186.02 | 0.833167E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118484E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153837E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122560E+09 | 0.112159E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285601E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46996955.74 | 0.175924E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115087E+10 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864857E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802860E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562787E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1802294.48 | 0.572453E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8278176.67 | 0.293118E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31134533.94 | 0.199601E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24804106.08 | 0.211830E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18095717.61 | 0.369951E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 889862.14 | 0.518524E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761679E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999678E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85004690.91 | 0.730821E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199601E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31134533.94 | 0.115087E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941158E+09 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713361E+09 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647805E+09 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59922.88 | 0.436275E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2681304.75 | 0.440557E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9006774.67 | 0.220556E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30330545.42 | 0.149535E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22717584.17 | 0.167287E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17738912.56 | 0.308574E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1230285.38 | 0.456144E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659343E+09 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838718E+09 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83765329.82 | 0.597931E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149535E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30330545.42 | 0.941158E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631064E+09 |
February | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485509E+09 |
March | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439909E+09 |
April | 0.605444E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5247.86 | 0.304904E+09 |
May | 0.655854E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208858.02 | 0.306075E+09 |
June | 0.654023E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4790418.70 | 0.162125E+09 |
July | 0.607275E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15927452.16 | 0.113072E+09 |
August | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12978134.67 | 0.123419E+09 |
September | 0.605444E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8944549.47 | 0.221918E+09 |
October | 0.629407E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 230166.06 | 0.320508E+09 |
November | 0.623262E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446057E+09 |
December | 0.607275E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563561E+09 |
Annual Sum or Average | 0.755301E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44084826.95 | 0.411812E+10 |
Minimum of Months | 0.571020E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113072E+09 |
Maximum of Months | 0.682301E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15927452.16 | 0.631064E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765165E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568588E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542799E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342164E+10 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16855329.72 | 0.318056E+10 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225874E+09 | 0.147316E+10 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554951E+09 | 0.644333E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398643E+09 | 0.120055E+10 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70510714.79 | 0.213733E+10 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 913034.46 | 0.331576E+10 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468693E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615797E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126775E+10 | 0.449838E+11 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644333E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554951E+09 | 0.765165E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628852E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484427E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440320E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7980.37 | 0.305940E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1054196.06 | 0.316327E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4377665.41 | 0.161426E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15881473.45 | 0.114105E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12913329.53 | 0.122222E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9247550.76 | 0.220111E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191509.54 | 0.318327E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446921E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562036E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43673705.11 | 0.412101E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114105E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15881473.45 | 0.628852E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147048E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112741E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103761E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726563E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2594104.30 | 0.731840E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11922871.89 | 0.375521E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43785891.01 | 0.251506E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32648350.79 | 0.276757E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25126984.08 | 0.487718E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1814585.90 | 0.698542E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101121E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129264E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117893E+09 | 0.948779E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251506E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43785891.01 | 0.147048E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.124481E+10 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983295E+09 |
February | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764946E+09 |
March | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705917E+09 |
April | 0.447140E+09 | 0.119843E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502799E+09 |
May | 0.484071E+09 | 0.129327E+10 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1523224.79 | 0.496203E+09 |
June | 0.482240E+09 | 0.128701E+10 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7465958.06 | 0.258278E+09 |
July | 0.448971E+09 | 0.120469E+10 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25819400.54 | 0.175647E+09 |
August | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20198128.01 | 0.191089E+09 |
September | 0.447140E+09 | 0.119843E+10 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14158166.22 | 0.339332E+09 |
October | 0.465148E+09 | 0.124481E+10 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 505886.29 | 0.483991E+09 |
November | 0.460569E+09 | 0.123022E+10 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681542E+09 |
December | 0.448971E+09 | 0.120469E+10 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866280E+09 |
Annual Sum or Average | 0.557719E+10 | 0.149189E+11 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69670763.91 | 0.644932E+10 |
Minimum of Months | 0.421807E+09 | 0.112913E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175647E+09 |
Maximum of Months | 0.502994E+09 | 0.134172E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25819400.54 | 0.983295E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.196626E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151296E+10 |
February | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120368E+10 |
March | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108862E+10 |
April | 0.956342E+09 | 0.189301E+10 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766848E+09 |
May | 0.103597E+10 | 0.204281E+10 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2014006.59 | 0.753068E+09 |
June | 0.103308E+10 | 0.203293E+10 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10739715.98 | 0.381778E+09 |
July | 0.959235E+09 | 0.190289E+10 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37025797.47 | 0.258316E+09 |
August | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29693723.83 | 0.289389E+09 |
September | 0.956342E+09 | 0.189301E+10 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17774706.75 | 0.519879E+09 |
October | 0.994195E+09 | 0.196626E+10 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111378.35 | 0.766981E+09 |
November | 0.984487E+09 | 0.194322E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106623E+10 |
December | 0.959235E+09 | 0.190289E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135102E+10 |
Annual Sum or Average | 0.119305E+11 | 0.235655E+11 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97359328.99 | 0.995877E+10 |
Minimum of Months | 0.901968E+09 | 0.178355E+10 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258316E+09 |
Maximum of Months | 0.107774E+10 | 0.211935E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37025797.47 | 0.151296E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.124473E+10 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980719E+09 |
February | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762042E+09 |
March | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702574E+09 |
April | 0.605404E+09 | 0.119835E+10 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501402E+09 |
May | 0.655811E+09 | 0.129318E+10 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1476760.40 | 0.506954E+09 |
June | 0.653980E+09 | 0.128693E+10 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6846366.08 | 0.258447E+09 |
July | 0.607235E+09 | 0.120461E+10 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25765960.16 | 0.177426E+09 |
August | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20422951.13 | 0.189674E+09 |
September | 0.605404E+09 | 0.119835E+10 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14898751.22 | 0.333487E+09 |
October | 0.629366E+09 | 0.124473E+10 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 448465.71 | 0.476359E+09 |
November | 0.623221E+09 | 0.123014E+10 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679685E+09 |
December | 0.607235E+09 | 0.120461E+10 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864271E+09 |
Annual Sum or Average | 0.755252E+10 | 0.149180E+11 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69859254.70 | 0.643304E+10 |
Minimum of Months | 0.570983E+09 | 0.112906E+10 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177426E+09 |
Maximum of Months | 0.682256E+09 | 0.134164E+10 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25765960.16 | 0.980719E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203219E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161797E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147684E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105346E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2349054.25 | 0.105193E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10967060.02 | 0.535494E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42387183.49 | 0.364435E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34990810.43 | 0.403993E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23870880.63 | 0.730182E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86368.30 | 0.105938E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148658E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186459E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114651E+09 | 0.136770E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364435E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42387183.49 | 0.203219E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251209E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197017E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182242E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129661E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3124822.26 | 0.130085E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14485814.18 | 0.673545E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57127904.35 | 0.454084E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45460945.37 | 0.501247E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32483585.33 | 0.887793E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450384.52 | 0.125034E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177586E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225043E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153133E+09 | 0.166954E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454084E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57127904.35 | 0.251209E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251218E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189369E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177720E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124647E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1242133.09 | 0.126916E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9013613.85 | 0.657807E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42521480.45 | 0.425074E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38571326.08 | 0.466078E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26222754.46 | 0.817321E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113874E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165624E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217942E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117571E+09 | 0.160394E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425074E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42521480.45 | 0.251218E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 14257.50 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 14257.50 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 14257.50 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 14257.50 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 14257.50 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 14257.50 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 14257.50 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 14257.50 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 14257.50 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 14257.50 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 14257.50 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 14257.50 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9760.61 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9760.61 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9760.61 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9760.61 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9760.61 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9760.61 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9760.61 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9760.61 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9760.61 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9760.61 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9760.61 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9760.61 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3203.48 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1763.23 | 08-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2158.85 | 02-MAR-22:02 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 07-APR-14:00 | 1423.35 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.19 | 20-MAY-17:02 | 2775.31 | 22-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.70 | 24-JUN-17:10 | 1135.03 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 556.93 | 30-JUL-11:52 | 681.48 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.84 | 06-AUG-18:00 | 818.23 | 22-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 637.23 | 03-SEP-13:00 | 1461.14 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.83 | 15-OCT-14:10 | 1380.13 | 30-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1781.53 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2430.56 | 01-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 681.48 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 637.23 | 3203.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2135.26 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1174.82 | 08-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1439.17 | 02-MAR-22:02 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 950.84 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.86 | 20-MAY-17:02 | 1851.22 | 22-MAY-04:05 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.60 | 24-JUN-17:10 | 795.43 | 04-JUN-13:55 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.35 | 30-JUL-11:52 | 454.51 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.55 | 06-AUG-18:00 | 548.67 | 22-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.13 | 03-SEP-16:50 | 970.19 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.05 | 15-OCT-14:10 | 919.98 | 30-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1186.58 | 29-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.38 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.51 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 385.13 | 2135.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3204.86 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1766.62 | 08-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2183.45 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1438.82 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.32 | 20-MAY-17:02 | 2774.97 | 22-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.32 | 24-JUN-17:10 | 1162.61 | 04-JUN-13:55 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.85 | 30-JUL-11:52 | 689.74 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.21 | 06-AUG-18:00 | 837.64 | 22-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.97 | 03-SEP-16:50 | 1470.19 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 18-OCT-14:00 | 1391.67 | 30-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1781.49 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2430.63 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.74 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 527.21 | 3204.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2134.45 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1175.86 | 08-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1441.06 | 02-MAR-22:02 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 950.63 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.68 | 20-MAY-17:02 | 1850.95 | 22-MAY-04:05 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 758.58 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.62 | 30-JUL-11:52 | 469.40 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.10 | 06-AUG-12:00 | 554.38 | 22-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.47 | 03-SEP-13:00 | 963.80 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.70 | 15-OCT-13:02 | 920.50 | 30-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1186.03 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.38 | 01-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.40 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 408.47 | 2134.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1706.66 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 938.27 | 08-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1162.78 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | 07-APR-14:00 | 781.75 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.25 | 20-MAY-17:02 | 1550.68 | 22-MAY-04:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.57 | 24-JUN-17:01 | 637.53 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.68 | 30-JUL-12:00 | 383.55 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.88 | 06-AUG-17:50 | 483.21 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.68 | 03-SEP-13:00 | 908.80 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.43 | 15-OCT-14:10 | 758.37 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 952.23 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1361.19 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.55 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 370.68 | 1706.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1137.64 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 625.27 | 08-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 781.28 | 02-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 07-APR-14:00 | 539.10 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.53 | 20-MAY-17:02 | 1039.78 | 22-MAY-04:03 |
June | 827.22 | 01-JUN-09:09 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.14 | 24-JUN-17:01 | 434.36 | 14-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.67 | 30-JUL-11:54 | 265.28 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.39 | 06-AUG-17:50 | 337.75 | 23-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.05 | 03-SEP-13:00 | 609.55 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 | 15-OCT-14:10 | 515.10 | 30-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 634.48 | 29-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 900.19 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.28 | |||||
Maximum of Months | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 214.05 | 1137.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 38015.19 | 10-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 36567.40 | 01-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 30500.24 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 19411.70 | 28-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2521.91 | 19-MAY-16:10 | 17471.15 | 08-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4922.96 | 28-JUN-16:10 | 13133.80 | 16-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8995.70 | 17-JUL-16:10 | 8815.36 | 05-JUL-06:10 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6156.22 | 07-AUG-12:00 | 10562.55 | 28-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2979.54 | 01-SEP-16:10 | 13698.71 | 19-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.06 | 18-OCT-14:00 | 20492.28 | 10-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 26686.18 | 27-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 36650.71 | 29-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8815.36 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8995.70 | 38015.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1137.26 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 625.93 | 08-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 798.26 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | 07-APR-14:00 | 536.02 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.13 | 20-MAY-17:02 | 1038.55 | 22-MAY-04:03 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 29-JUN-15:00 | 436.88 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 30-JUL-11:54 | 270.08 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.70 | 06-AUG-11:53 | 336.99 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.96 | 03-SEP-13:00 | 607.70 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 15-OCT-13:42 | 517.31 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 634.11 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 902.48 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.08 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 226.96 | 1137.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2672.40 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1471.81 | 08-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1857.33 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1283.97 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.80 | 20-MAY-17:02 | 2409.80 | 22-MAY-04:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.26 | 24-JUN-17:10 | 1040.32 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 406.32 | 30-JUL-12:00 | 613.10 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.95 | 06-AUG-17:40 | 768.15 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.95 | 03-SEP-13:00 | 1362.05 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.33 | 15-OCT-14:00 | 1163.55 | 30-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1490.40 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2020.09 | 01-DEC-05:08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.10 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 543.95 | 2672.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1302.65 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1781.04 | 05-JAN-22:01 |
February | 805.43 | 01-FEB-08:09 | 1302.65 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 980.55 | 08-FEB-22:01 |
March | 805.43 | 01-MAR-08:09 | 1302.65 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1240.57 | 02-MAR-23:00 |
April | 805.43 | 03-APR-07:10 | 1302.65 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 857.50 | 27-APR-02:00 |
May | 805.43 | 01-MAY-07:10 | 1302.65 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.10 | 20-MAY-17:02 | 1596.33 | 22-MAY-04:03 |
June | 805.43 | 01-JUN-07:10 | 1302.65 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.73 | 24-JUN-17:10 | 684.63 | 14-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 1302.65 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.33 | 30-JUL-12:00 | 408.02 | 05-JUL-01:00 |
August | 805.43 | 01-AUG-07:10 | 1302.65 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.35 | 06-AUG-17:40 | 510.05 | 23-AUG-03:00 |
September | 805.43 | 01-SEP-07:10 | 1302.65 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.52 | 03-SEP-13:00 | 904.96 | 12-SEP-03:00 |
October | 805.43 | 02-OCT-07:10 | 1302.65 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.01 | 15-OCT-14:00 | 776.62 | 30-OCT-21:03 |
November | 805.43 | 01-NOV-07:10 | 1302.65 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 992.52 | 29-NOV-22:02 |
December | 805.43 | 01-DEC-08:09 | 1302.65 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1346.73 | 01-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.02 | |||||
Maximum of Months | 805.43 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 343.52 | 1781.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2057.62 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2673.25 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 2057.62 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1474.48 | 08-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 2057.62 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1908.95 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 2057.62 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1298.38 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 2057.62 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.64 | 20-MAY-17:02 | 2422.57 | 22-MAY-04:03 |
June | 1306.65 | 01-JUN-09:09 | 2057.62 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.54 | 24-JUN-17:10 | 1036.25 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 2057.62 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.91 | 30-JUL-12:00 | 619.78 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 2057.62 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.37 | 06-AUG-18:00 | 778.80 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 2057.62 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.38 | 03-SEP-16:20 | 1370.26 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 2057.62 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 18-OCT-14:50 | 1205.09 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 2057.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1490.53 | 29-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 2057.62 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2023.55 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.78 | |||||
Maximum of Months | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 397.37 | 2673.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1302.56 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1780.71 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 1302.56 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 981.39 | 08-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 1302.56 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1251.85 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 1302.56 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 856.19 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 1302.56 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.35 | 20-MAY-17:02 | 1589.92 | 22-MAY-04:03 |
June | 827.17 | 01-JUN-09:09 | 1302.56 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 | 29-JUN-15:00 | 691.14 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 1302.56 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.25 | 30-JUL-12:00 | 420.24 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 1302.56 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.83 | 06-AUG-12:00 | 513.19 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 1302.56 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.03 | 03-SEP-13:00 | 896.21 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 1302.56 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.85 | 15-OCT-12:40 | 776.68 | 30-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1302.56 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 992.17 | 29-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 1302.56 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1346.76 | 01-DEC-05:08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.24 | |||||
Maximum of Months | 827.17 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 365.03 | 1780.71 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3402.84 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2157.07 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2667.16 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1867.10 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.24 | 20-MAY-17:02 | 3686.64 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.70 | 29-JUN-15:00 | 1507.16 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.08 | 30-JUL-12:00 | 887.62 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.98 | 06-AUG-18:00 | 1143.58 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.59 | 03-SEP-13:00 | 2056.51 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 | 18-OCT-14:00 | 1713.06 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2012.98 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3125.68 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.62 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.59 | 3686.64 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4342.66 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2627.41 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3339.45 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2341.88 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.40 | 20-MAY-17:02 | 4525.12 | 22-MAY-04:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.90 | 29-JUN-15:00 | 1894.37 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.44 | 30-JUL-11:52 | 1093.52 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.88 | 06-AUG-18:00 | 1412.42 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.38 | 03-SEP-13:00 | 2500.17 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.92 | 15-OCT-13:50 | 2069.83 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2423.77 | 29-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3738.48 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.38 | 4525.12 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4621.41 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2567.70 | 08-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3232.82 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2115.78 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.49 | 20-MAY-17:02 | 4179.38 | 22-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.85 | 29-JUN-15:00 | 2143.18 | 04-JUN-13:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.10 | 30-JUL-11:58 | 994.86 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.99 | 06-AUG-18:00 | 1261.89 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.69 | 03-SEP-13:00 | 2171.94 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2021.79 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2548.08 | 29-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3385.53 | 31-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994.86 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.69 | 4621.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 10335.86 | 19-JAN-16:50 | 12070.02 | 19521.22 | 28515.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16962.35 | 28-FEB-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17625.38 | 01-MAR-17:00 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24180.32 | 27-APR-05:01 | 4446.85 | 7591.59 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44672.72 | 22-MAY-05:01 | 4446.85 | 7591.59 | 54140.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34311.69 | 23-JUN-05:13 | 1905.79 | 3253.54 | 23203.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 44796.55 | 18-JUL-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45180.55 | 08-AUG-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44069.95 | 11-SEP-05:12 | 2541.06 | 4338.05 | 30937.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39995.01 | 21-OCT-05:02 | 3811.58 | 6507.07 | 46406.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23912.03 | 02-NOV-05:01 | 5082.11 | 8676.10 | 61874.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14883.56 | 07-DEC-16:20 | 6035.01 | 9760.61 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10335.86 | 1905.79 | 3253.54 | 14257.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45180.55 | 12070.02 | 19521.22 | 61874.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 968.50 | 14-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.47 |
February | 4566.23 | 26-FEB-14:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.02 |
March | 5288.51 | 22-MAR-14:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.75 |
April | 9757.66 | 16-APR-13:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.56 |
May | 13641.60 | 19-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.24 | 0.00 |
June | 16149.29 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 | 0.00 |
July | 19041.67 | 17-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 0.00 |
August | 17440.75 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.43 | 0.00 |
September | 12853.44 | 01-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.65 | 0.00 |
October | 7578.09 | 18-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 |
November | 3046.45 | 03-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.31 |
December | 358.14 | 06-DEC-14:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 358.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19041.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.43 | 616.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5614.45 | 28-JAN-02:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2365.62 |
February | 6569.16 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1656.67 |
March | 7207.28 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.36 |
April | 4869.06 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.90 |
May | 5007.72 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.95 |
June | 4482.07 | 23-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 | 0.00 |
July | 5834.34 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.96 | 0.00 |
August | 5487.96 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.55 | 0.00 |
September | 4668.68 | 05-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
October | 2812.41 | 05-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.28 |
November | 3509.77 | 10-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.55 |
December | 5553.47 | 23-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2014.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2812.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7207.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.96 | 2365.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5962.43 | 19-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.37 |
February | 6590.17 | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.80 |
March | 8060.99 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1055.72 |
April | 6503.66 | 20-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 |
May | 5496.06 | 06-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.02 |
June | 4546.67 | 23-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.71 | 0.00 |
July | 5936.51 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.62 | 0.00 |
August | 5798.49 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.95 | 0.00 |
September | 5257.76 | 05-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 |
October | 3381.37 | 21-OCT-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.35 |
November | 4141.00 | 22-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.50 |
December | 5441.37 | 30-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3381.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8060.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.62 | 1055.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7373.43 | 13-JAN-16:40 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9053.86 | 28-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9427.85 | 01-MAR-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12987.18 | 25-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16128.19 | 30-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19098.58 | 23-JUN-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29842.28 | 18-JUL-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28414.06 | 08-AUG-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35094.01 | 05-SEP-05:12 | 2541.06 | 4338.05 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14222.02 | 19-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10414.83 | 03-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8047.99 | 07-DEC-16:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7373.43 | 2541.06 | 4338.05 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35094.01 | 6035.01 | 9760.61 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8869.36 | 07-JAN-17:01 | 3176.32 | 5422.56 | 22694.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9725.30 | 28-FEB-17:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9940.87 | 23-MAR-14:50 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14475.71 | 25-APR-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19220.25 | 19-MAY-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22695.09 | 23-JUN-14:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24681.56 | 17-JUL-15:30 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23652.79 | 07-AUG-15:20 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21864.26 | 05-SEP-14:00 | 6198.29 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13175.29 | 18-OCT-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9950.13 | 03-NOV-16:00 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8892.75 | 06-DEC-16:10 | 6035.01 | 9760.61 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8869.36 | 3176.32 | 5422.56 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24681.56 | 6198.29 | 9760.61 | 22694.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3792.54 | 07-JAN-17:01 | 669.60 | 1143.12 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.48 |
February | 3317.06 | 27-FEB-16:10 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.82 |
March | 3520.20 | 29-MAR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.74 |
April | 4393.15 | 07-APR-14:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 |
May | 6083.47 | 28-MAY-17:32 | 0.00 | 685.87 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.55 |
June | 7376.59 | 23-JUN-13:50 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 0.00 |
July | 8383.22 | 17-JUL-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.94 | 0.00 |
August | 7945.84 | 09-AUG-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 71.51 | 0.00 |
September | 7594.25 | 03-SEP-15:21 | 468.72 | 800.19 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 404.12 | 0.00 |
October | 4230.53 | 18-OCT-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.19 | 0.00 |
November | 3244.79 | 03-NOV-15:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.90 |
December | 2904.88 | 09-DEC-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2904.88 | 0.00 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8383.22 | 1306.65 | 2057.62 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 404.12 | 326.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2473.92 | 07-JAN-17:01 | 423.91 | 723.69 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.59 |
February | 2568.30 | 27-FEB-10:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.54 |
March | 3160.17 | 23-MAR-10:30 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.34 |
April | 5377.39 | 25-APR-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.74 |
May | 6961.16 | 19-MAY-09:10 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.08 |
June | 13474.46 | 25-JUN-08:42 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.48 |
July | 12631.59 | 02-JUL-08:52 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.42 |
August | 16773.83 | 06-AUG-09:12 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 23.49 | 0.00 |
September | 11126.88 | 03-SEP-10:02 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
October | 3874.98 | 18-OCT-09:50 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.09 |
November | 2588.32 | 03-NOV-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.45 |
December | 1898.21 | 09-DEC-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1898.21 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16773.83 | 1654.44 | 2605.29 | 3028.58 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 291.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4736.94 | 19-JAN-14:00 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.29 |
February | 10006.48 | 27-FEB-13:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.42 |
March | 9805.93 | 01-MAR-14:07 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.28 |
April | 10374.42 | 25-APR-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.61 |
May | 10705.84 | 19-MAY-13:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 47.58 | 0.00 |
June | 11205.42 | 23-JUN-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 | 0.00 |
July | 13183.17 | 17-JUL-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 57.01 | 0.00 |
August | 18297.21 | 06-AUG-13:52 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 298.00 | 0.00 |
September | 31193.54 | 03-SEP-13:21 | 535.68 | 914.50 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 266.78 | 0.00 |
October | 13327.60 | 18-OCT-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 0.00 |
November | 10273.02 | 03-NOV-13:25 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 |
December | 4952.92 | 06-DEC-14:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4736.94 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31193.54 | 3919.96 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 298.00 | 440.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2607.75 | 07-JAN-17:01 | 423.88 | 723.64 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.60 |
February | 3639.38 | 28-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.43 |
March | 4771.97 | 28-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.39 |
April | 9190.13 | 16-APR-16:52 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.01 |
May | 18231.30 | 28-MAY-17:32 | 0.00 | 434.19 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.99 |
June | 12204.05 | 24-JUN-17:42 | 211.94 | 361.82 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.32 |
July | 20159.14 | 16-JUL-16:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 75.37 | 0.00 |
August | 19263.56 | 06-AUG-16:32 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 227.90 | 0.00 |
September | 19178.14 | 03-SEP-15:21 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 221.53 | 0.00 |
October | 6458.80 | 18-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 | 0.00 |
November | 3231.12 | 03-NOV-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.46 |
December | 2633.19 | 06-DEC-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2607.75 | 0.00 | 361.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20159.14 | 805.38 | 1302.56 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 227.90 | 339.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2291.87 | 14-JAN-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.55 |
February | 2291.36 | 25-FEB-17:03 | 267.84 | 457.25 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 |
March | 2460.42 | 29-MAR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.59 |
April | 2935.81 | 07-APR-14:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 0.00 |
May | 3643.86 | 29-MAY-18:26 | 0.00 | 571.56 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 |
June | 4633.12 | 23-JUN-14:00 | 1306.65 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.73 | 0.00 |
July | 5790.29 | 17-JUL-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.42 | 0.00 |
August | 5864.28 | 09-AUG-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.23 | 0.00 |
September | 5562.81 | 04-SEP-15:51 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 95.70 | 0.00 |
October | 3375.78 | 19-OCT-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 |
November | 2738.45 | 08-NOV-14:10 | 3919.96 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.61 |
December | 2344.74 | 06-DEC-07:05 | 1071.35 | 2743.50 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2291.36 | 0.00 | 457.25 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5864.28 | 3919.96 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 95.70 | 125.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1513.12 | 14-JAN-17:02 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.13 |
February | 2041.55 | 27-FEB-10:30 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.29 |
March | 2257.27 | 23-MAR-10:30 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.62 |
April | 3020.10 | 25-APR-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 |
May | 4198.06 | 19-MAY-09:30 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.70 |
June | 6953.12 | 23-JUN-09:20 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | 0.00 |
July | 9359.45 | 16-JUL-09:21 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 |
August | 13940.23 | 06-AUG-09:41 | 339.13 | 578.95 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 33.79 | 0.00 |
September | 13935.95 | 04-SEP-08:31 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
October | 3458.55 | 18-OCT-10:00 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 |
November | 2238.21 | 03-NOV-09:30 | 1654.44 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.24 |
December | 1644.18 | 06-DEC-10:40 | 827.22 | 1302.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1513.12 | 211.95 | 361.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13940.23 | 1654.44 | 2605.29 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 33.79 | 147.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3270.75 | 14-JAN-12:40 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.04 |
February | 7365.98 | 27-FEB-13:17 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.41 |
March | 4719.52 | 01-MAR-14:40 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1683.98 |
April | 4939.17 | 06-APR-14:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.13 |
May | 6844.97 | 19-MAY-14:00 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 326.84 | 0.00 |
June | 10868.98 | 23-JUN-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4197.35 | 0.00 |
July | 16595.02 | 17-JUL-16:10 | 401.76 | 1143.12 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8995.70 | 0.00 |
August | 16602.95 | 07-AUG-12:00 | 687.71 | 2057.62 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6156.22 | 0.00 |
September | 22487.49 | 04-SEP-15:51 | 535.68 | 914.50 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 | 0.00 |
October | 11398.60 | 18-OCT-13:50 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 91.00 | 0.00 |
November | 7402.94 | 03-NOV-13:50 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.31 |
December | 3639.00 | 06-DEC-14:50 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1405.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3270.75 | 137.54 | 342.94 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22487.49 | 3816.70 | 6172.87 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 8995.70 | 1683.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1852.67 | 13-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.91 |
February | 2580.33 | 28-FEB-16:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 |
March | 2561.41 | 01-MAR-16:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 |
April | 4458.61 | 25-APR-17:30 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.66 |
May | 5597.37 | 19-MAY-17:50 | 84.78 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
June | 8793.89 | 24-JUN-17:07 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 0.00 |
July | 15275.09 | 16-JUL-18:01 | 0.00 | 723.64 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 0.00 |
August | 14674.90 | 06-AUG-16:21 | 381.49 | 651.28 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 121.37 | 0.00 |
September | 15643.19 | 04-SEP-17:11 | 0.00 | 578.92 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 | 0.00 |
October | 5307.61 | 18-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 | 0.00 |
November | 2578.32 | 03-NOV-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.10 |
December | 2099.73 | 06-DEC-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1852.67 | 0.00 | 434.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15643.19 | 805.38 | 1302.56 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 121.37 | 122.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2289.87 | 14-JAN-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.14 |
February | 2830.94 | 27-FEB-16:10 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 |
March | 2973.88 | 29-MAR-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.88 |
April | 3630.69 | 07-APR-14:40 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 |
May | 5157.02 | 19-MAY-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 83.32 | 0.00 |
June | 6580.36 | 29-JUN-15:20 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 127.96 | 0.00 |
July | 7386.16 | 17-JUL-16:00 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.53 | 0.00 |
August | 7194.62 | 09-AUG-14:50 | 1272.23 | 2057.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 59.69 | 0.00 |
September | 5794.29 | 04-SEP-15:51 | 535.68 | 914.50 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 136.70 | 0.00 |
October | 3883.37 | 15-OCT-14:32 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 81.55 | 0.00 |
November | 2846.07 | 08-NOV-14:10 | 3919.96 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.69 |
December | 2282.77 | 09-DEC-17:02 | 334.80 | 571.56 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2282.77 | 334.80 | 571.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7386.16 | 3919.96 | 6172.87 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 136.70 | 223.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2250.36 | 14-JAN-11:02 | 1017.38 | 1736.86 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.07 |
February | 3815.75 | 28-FEB-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.33 |
March | 4961.46 | 23-MAR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.38 |
April | 6665.45 | 25-APR-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.29 |
May | 7676.88 | 19-MAY-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 |
June | 12731.70 | 25-JUN-09:32 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.07 |
July | 13606.48 | 16-JUL-11:12 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
August | 16541.22 | 06-AUG-08:52 | 254.35 | 434.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 16786.55 | 04-SEP-08:31 | 296.74 | 506.58 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.98 |
October | 5711.52 | 18-OCT-10:05 | 1610.86 | 2605.29 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.73 |
November | 4517.86 | 03-NOV-12:02 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.19 |
December | 2511.28 | 07-DEC-11:02 | 3221.71 | 5210.58 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2250.36 | 211.95 | 361.85 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | |
Maximum of Months | 16786.55 | 4832.57 | 7815.87 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5412.44 | 19-JAN-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.64 |
February | 10910.80 | 27-FEB-13:30 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.42 |
March | 10862.12 | 01-MAR-13:50 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.14 |
April | 10093.90 | 25-APR-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 |
May | 10043.79 | 19-MAY-13:30 | 1306.65 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 35.87 | 0.00 |
June | 10402.35 | 23-JUN-13:10 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 | 0.00 |
July | 20719.84 | 16-JUL-13:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 48.94 | 0.00 |
August | 21149.98 | 06-AUG-12:12 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 262.48 | 0.00 |
September | 22651.57 | 04-SEP-15:51 | 535.68 | 914.50 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 96.76 | 0.00 |
October | 21723.19 | 15-OCT-13:52 | 334.80 | 571.56 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.25 |
November | 11309.40 | 03-NOV-13:25 | 2613.31 | 4115.24 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.69 |
December | 6169.11 | 07-DEC-13:40 | 1272.23 | 2057.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5412.44 | 334.80 | 571.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22651.57 | 2613.31 | 4115.24 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 262.48 | 255.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2397.51 | 13-JAN-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.46 |
February | 4085.84 | 28-FEB-16:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 |
March | 4810.50 | 28-MAR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.72 |
April | 7294.73 | 25-APR-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60 |
May | 17402.07 | 28-MAY-17:32 | 0.00 | 434.19 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.62 |
June | 13783.30 | 24-JUN-17:04 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 16.10 | 0.00 |
July | 18385.27 | 09-JUL-16:51 | 296.72 | 506.55 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 0.00 |
August | 17311.47 | 06-AUG-16:12 | 254.33 | 434.19 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 191.26 | 0.00 |
September | 19057.08 | 04-SEP-15:51 | 339.11 | 578.92 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 56.27 | 0.00 |
October | 6476.54 | 18-OCT-16:00 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 0.00 |
November | 3274.08 | 03-NOV-15:40 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.34 |
December | 2595.07 | 06-DEC-15:50 | 805.38 | 1302.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2397.51 | 0.00 | 434.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19057.08 | 805.38 | 1302.56 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 191.26 | 289.62 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.159795E+12 | 131121.62 | 09-JAN-08:09 | 0.243982E+12 | 385302.60 | 09-JAN-07:19 |
February | 0.140194E+12 | 120307.73 | 27-FEB-15:30 | 0.134775E+12 | 328590.50 | 01-FEB-07:19 |
March | 0.157997E+12 | 109737.46 | 01-MAR-16:30 | 0.975120E+11 | 343197.35 | 06-MAR-07:10 |
April | 0.143951E+12 | 134949.87 | 06-APR-15:00 | 0.401882E+11 | 185429.39 | 29-APR-06:10 |
May | 0.155744E+12 | 163132.27 | 19-MAY-15:30 | 0.259452E+11 | 226469.69 | 08-MAY-06:10 |
June | 0.173249E+12 | 183598.82 | 29-JUN-15:09 | 0.335304E+10 | 104984.06 | 16-JUN-06:10 |
July | 0.191064E+12 | 217289.80 | 17-JUL-15:00 | 0.413533E+09 | 46811.82 | 05-JUL-06:10 |
August | 0.195389E+12 | 202159.73 | 10-AUG-14:00 | 0.169397E+10 | 97170.92 | 18-AUG-06:10 |
September | 0.163072E+12 | 184155.75 | 07-SEP-14:50 | 0.958939E+10 | 152204.75 | 19-SEP-06:10 |
October | 0.155042E+12 | 150995.55 | 18-OCT-15:09 | 0.287498E+11 | 235867.36 | 10-OCT-06:10 |
November | 0.151145E+12 | 129430.18 | 17-NOV-16:00 | 0.804530E+11 | 315333.12 | 27-NOV-07:19 |
December | 0.155439E+12 | 125589.35 | 29-DEC-08:09 | 0.168720E+12 | 345938.18 | 29-DEC-07:19 |
Annual Sum or Average | 0.194208E+13 | 0.835375E+12 | ||||
Minimum of Months | 0.140194E+12 | 109737.46 | 0.413533E+09 | 46811.82 | ||
Maximum of Months | 0.195389E+12 | 217289.80 | 0.243982E+12 | 385302.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.472479E+11 | 0.255464E+11 | 0.613996E+11 | 0.230900E+10 | 0.166215E+11 | 0.125906E+10 | 0.00 | 1088862.33 | 0.00 | 0.00 | 0.00 | 0.541056E+10 | 0.00 |
February | 0.428574E+11 | 0.211055E+11 | 0.556056E+11 | 0.209511E+10 | 0.126703E+11 | 0.686200E+09 | 0.00 | 0.183317E+09 | 0.00 | 0.00 | 0.00 | 0.499078E+10 | 0.00 |
March | 0.509265E+11 | 0.206101E+11 | 0.635880E+11 | 0.240664E+10 | 0.141441E+11 | 0.485477E+09 | 0.00 | 6239727.83 | 0.00 | 0.00 | 0.00 | 0.582975E+10 | 0.00 |
April | 0.454877E+11 | 0.171600E+11 | 0.594055E+11 | 0.224272E+10 | 0.124377E+11 | 0.194111E+09 | 0.00 | 0.194485E+10 | 0.00 | 0.00 | 0.00 | 0.507790E+10 | 0.00 |
May | 0.490872E+11 | 0.152594E+11 | 0.624938E+11 | 0.235782E+10 | 0.142308E+11 | 0.139182E+09 | 0.00 | 0.701953E+10 | 0.00 | 0.00 | 0.00 | 0.515612E+10 | 0.00 |
June | 0.488499E+11 | 0.134758E+11 | 0.612808E+11 | 0.231841E+10 | 0.190353E+11 | 30092925.33 | 0.00 | 0.234413E+11 | 0.00 | 0.00 | 0.00 | 0.481727E+10 | 0.00 |
July | 0.457251E+11 | 0.145207E+11 | 0.606074E+11 | 0.228147E+10 | 0.227117E+11 | 14196191.95 | 0.00 | 0.408607E+11 | 0.00 | 0.00 | 0.00 | 0.434284E+10 | 0.00 |
August | 0.509265E+11 | 0.166196E+11 | 0.635880E+11 | 0.240664E+10 | 0.229602E+11 | 21597777.98 | 0.00 | 0.341885E+11 | 0.00 | 0.00 | 0.00 | 0.467853E+10 | 0.00 |
September | 0.454877E+11 | 0.187274E+11 | 0.593832E+11 | 0.224140E+10 | 0.167032E+11 | 56956980.34 | 0.00 | 0.161893E+11 | 0.00 | 0.00 | 0.00 | 0.428232E+10 | 0.00 |
October | 0.472479E+11 | 0.222135E+11 | 0.614108E+11 | 0.230966E+10 | 0.135523E+11 | 0.140386E+09 | 0.00 | 0.355108E+10 | 0.00 | 0.00 | 0.00 | 0.461641E+10 | 0.00 |
November | 0.466941E+11 | 0.240150E+11 | 0.599069E+11 | 0.224962E+10 | 0.128348E+11 | 0.399125E+09 | 0.00 | 0.237394E+09 | 0.00 | 0.00 | 0.00 | 0.480777E+10 | 0.00 |
December | 0.457251E+11 | 0.262580E+11 | 0.605962E+11 | 0.228081E+10 | 0.146659E+11 | 0.864724E+09 | 0.00 | 1149089.73 | 0.00 | 0.00 | 0.00 | 0.504702E+10 | 0.00 |
Annual Sum or Average | 0.566263E+12 | 0.235511E+12 | 0.729266E+12 | 0.274993E+11 | 0.192568E+12 | 0.429110E+10 | 0.00 | 0.127624E+12 | 0.00 | 0.00 | 0.00 | 0.590573E+11 | 0.00 |
Minimum of Months | 0.428574E+11 | 0.134758E+11 | 0.556056E+11 | 0.209511E+10 | 0.124377E+11 | 14196191.95 | 0.00 | 1088862.33 | 0.00 | 0.00 | 0.00 | 0.428232E+10 | 0.00 |
Maximum of Months | 0.509265E+11 | 0.262580E+11 | 0.635880E+11 | 0.240664E+10 | 0.229602E+11 | 0.125906E+10 | 0.00 | 0.408607E+11 | 0.00 | 0.00 | 0.00 | 0.582975E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.243982E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.134775E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.975120E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.401882E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.259452E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.335304E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.413533E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.169397E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.958939E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.287498E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.804530E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.168720E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.835375E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.413533E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.243982E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49443.18 | 02-JAN-08:09 | 15013.15 | 01-JAN-00:10 | 41937.01 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:20 | 19143.09 | 09-JAN-07:10 | 1517.68 | 09-JAN-07:30 | 0.00 | 01-JAN-00:10 |
February | 49443.18 | 01-FEB-08:09 | 15013.15 | 01-FEB-00:10 | 41937.01 | 01-FEB-08:09 | 1410.29 | 06-FEB-17:10 | 17865.95 | 06-FEB-07:10 | 1358.36 | 01-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 49443.18 | 01-MAR-08:09 | 15013.15 | 01-MAR-00:10 | 41937.01 | 01-MAR-08:09 | 1410.29 | 01-MAR-13:09 | 18370.59 | 06-MAR-07:10 | 1406.42 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 49443.18 | 03-APR-07:10 | 15013.15 | 01-APR-00:10 | 41937.01 | 03-APR-07:10 | 1410.29 | 05-APR-07:10 | 15853.15 | 25-APR-15:00 | 885.98 | 29-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 49443.18 | 01-MAY-07:10 | 15013.15 | 01-MAY-00:10 | 41937.01 | 01-MAY-07:10 | 1410.29 | 03-MAY-12:09 | 21849.14 | 19-MAY-15:39 | 1177.68 | 08-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 49443.18 | 01-JUN-07:10 | 15013.15 | 01-JUN-00:10 | 41937.01 | 01-JUN-07:10 | 1410.29 | 16-JUN-07:10 | 27583.67 | 29-JUN-14:50 | 542.14 | 16-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 49443.18 | 03-JUL-07:10 | 15013.15 | 01-JUL-00:10 | 41937.01 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 35214.68 | 17-JUL-15:00 | 226.67 | 05-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 49443.18 | 01-AUG-07:10 | 15013.15 | 01-AUG-00:10 | 41937.01 | 01-AUG-07:10 | 1410.29 | 16-AUG-16:10 | 34088.73 | 10-AUG-14:00 | 476.02 | 18-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 49443.18 | 01-SEP-07:10 | 15013.15 | 01-SEP-00:10 | 41937.01 | 01-SEP-07:10 | 1410.29 | 19-SEP-07:10 | 28715.46 | 01-SEP-15:20 | 705.93 | 19-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 49443.18 | 02-OCT-07:10 | 15013.15 | 01-OCT-00:10 | 41937.01 | 02-OCT-07:10 | 1410.29 | 04-OCT-07:10 | 19648.76 | 18-OCT-15:20 | 1186.93 | 10-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 49443.18 | 01-NOV-07:10 | 15013.15 | 01-NOV-00:10 | 41937.01 | 01-NOV-07:10 | 1410.29 | 02-NOV-16:10 | 17635.99 | 27-NOV-07:10 | 1339.04 | 27-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 49443.18 | 01-DEC-08:09 | 15013.15 | 01-DEC-00:10 | 41937.01 | 01-DEC-08:09 | 1410.29 | 07-DEC-12:09 | 18370.59 | 26-DEC-07:10 | 1402.20 | 29-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 15853.15 | 226.67 | 0.00 | |||||||
Maximum of Months | 49443.18 | 15013.15 | 41937.01 | 1410.29 | 35214.68 | 1517.68 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 194.83 | 07-JAN-06:19 | 0.00 | 0.00 | 0.00 | 7216.52 | 31-JAN-12:50 | 0.00 |
February | 11843.06 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 7227.62 | 21-FEB-12:00 | 0.00 |
March | 1138.96 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 7223.15 | 01-MAR-12:30 | 0.00 |
April | 22208.85 | 06-APR-15:00 | 0.00 | 0.00 | 0.00 | 7160.84 | 03-APR-11:39 | 0.00 |
May | 43493.09 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 | 6728.02 | 01-MAY-11:30 | 0.00 |
June | 59517.96 | 29-JUN-14:00 | 0.00 | 0.00 | 0.00 | 6279.55 | 01-JUN-11:00 | 0.00 |
July | 84924.58 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 6147.88 | 03-JUL-11:39 | 0.00 |
August | 72052.58 | 10-AUG-14:00 | 0.00 | 0.00 | 0.00 | 5803.89 | 01-AUG-11:50 | 0.00 |
September | 65811.15 | 07-SEP-14:50 | 0.00 | 0.00 | 0.00 | 5886.29 | 29-SEP-11:50 | 0.00 |
October | 34060.93 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 | 6252.70 | 31-OCT-11:00 | 0.00 |
November | 7024.17 | 17-NOV-16:00 | 0.00 | 0.00 | 0.00 | 6695.02 | 30-NOV-12:00 | 0.00 |
December | 225.39 | 24-DEC-12:20 | 0.00 | 0.00 | 0.00 | 7097.30 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 194.83 | 0.00 | 0.00 | 0.00 | 5803.89 | 0.00 | ||
Maximum of Months | 84924.58 | 0.00 | 0.00 | 0.00 | 7227.62 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 131121.62 | 09-JAN-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 17595.30 | 1483.27 | 0.00 | 0.00 | 0.00 |
February | 120307.73 | 27-FEB-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 11423.42 | 8.33 | 0.00 | 11843.06 | 0.00 |
March | 109737.46 | 01-MAR-16:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 11165.03 | 13.06 | 0.00 | 0.00 | 0.00 |
April | 134949.87 | 06-APR-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 14534.26 | 6.85 | 0.00 | 22208.85 | 0.00 |
May | 163132.27 | 19-MAY-15:30 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 21847.59 | 6.85 | 0.00 | 43478.56 | 0.00 |
June | 183598.82 | 29-JUN-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 27416.63 | 6.85 | 0.00 | 58903.19 | 0.00 |
July | 217289.80 | 17-JUL-15:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 35214.68 | 6.85 | 0.00 | 84924.58 | 0.00 |
August | 202159.73 | 10-AUG-14:00 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 34088.73 | 6.85 | 0.00 | 72052.58 | 0.00 |
September | 184155.75 | 07-SEP-14:50 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 22031.18 | 6.88 | 0.00 | 65811.15 | 0.00 |
October | 150995.55 | 18-OCT-15:09 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 19613.01 | 6.85 | 0.00 | 33973.17 | 0.00 |
November | 129430.18 | 17-NOV-16:00 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 9796.34 | 8.54 | 0.00 | 7024.17 | 0.00 |
December | 125589.35 | 29-DEC-08:09 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 12266.86 | 1288.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 109737.46 | 49443.18 | 41937.01 | 0.00 | 1410.29 | 9796.34 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 217289.80 | 49443.18 | 41937.01 | 15013.15 | 1410.29 | 35214.68 | 1483.27 | 0.00 | 84924.58 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 385302.60 | 09-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 328590.50 | 01-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 343197.35 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 185429.39 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 226469.69 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 104984.06 | 16-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 46811.82 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 97170.92 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 152204.75 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 235867.36 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 315333.12 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 345938.18 | 29-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 46811.82 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 385302.60 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 19.57 | 2.50 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
February | 0.33 | 19.72 | 0.33 | 19.72 | 0.00 | 19.72 | 0.00 | 19.72 |
March | 0.33 | 19.82 | 0.33 | 19.82 | 0.00 | 19.82 | 0.00 | 19.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 0.67 | 19.03 | 0.50 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 4.17 | 19.50 | 3.83 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.82 | 2.50 | 19.82 | 0.00 | 19.82 | 0.00 | 19.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 17.89 | 4.17 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
February | 1.17 | 18.24 | 0.67 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 0.83 | 18.23 | 0.50 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 18.15 | 0.67 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
December | 2.00 | 18.33 | 1.17 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
Annual Sum or Average | 12.83 | 18.04 | 7.17 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.67 | 18.33 | 4.17 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.83 | 15.37 | 24.17 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 20.50 | 15.04 | 4.83 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
March | 13.67 | 15.18 | 4.17 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
April | 0.33 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
May | 1.83 | 16.19 | 0.17 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
November | 16.00 | 14.94 | 4.83 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
December | 44.33 | 14.91 | 14.50 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
Annual Sum or Average | 162.00 | 15.16 | 52.67 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.83 | 16.83 | 24.17 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.33 | 15.36 | 22.83 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
February | 20.83 | 15.06 | 4.33 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
March | 12.50 | 14.98 | 2.67 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
April | 0.50 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
May | 2.00 | 16.06 | 0.17 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.26 | 2.50 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.34 | 1.50 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.73 | 0.33 | 27.73 |
October | 0.50 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
November | 15.33 | 14.97 | 4.00 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
December | 42.67 | 14.93 | 11.67 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
Annual Sum or Average | 156.67 | 15.15 | 45.67 | 15.45 | 4.83 | 15.74 | 4.83 | 16.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 | 0.00 | 15.07 |
Maximum of Months | 62.33 | 16.92 | 22.83 | 16.92 | 2.50 | 28.34 | 2.50 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.17 | 15.45 | 17.83 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
February | 15.83 | 15.18 | 2.67 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
March | 11.00 | 15.19 | 2.00 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
April | 0.33 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
May | 1.33 | 16.67 | 0.17 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.79 | 1.17 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.14 | 1.50 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.24 | 3.00 | 28.24 |
October | 0.50 | 16.12 | 0.00 | 16.12 | 0.33 | 20.61 | 0.33 | 22.53 |
November | 11.50 | 15.18 | 2.50 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
December | 33.83 | 14.87 | 8.17 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
Annual Sum or Average | 125.50 | 15.23 | 33.33 | 15.56 | 6.00 | 16.01 | 6.00 | 16.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.17 | 16.84 | 17.83 | 16.97 | 3.00 | 28.24 | 3.00 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.83 | 15.27 | 22.50 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
February | 20.83 | 15.00 | 4.50 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
March | 13.00 | 15.18 | 3.17 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
April | 0.33 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
May | 2.00 | 16.08 | 0.17 | 16.34 | 0.83 | 19.54 | 0.17 | 19.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.83 | 1.17 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.49 | 2.50 | 28.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.43 | 0.83 | 28.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.26 | 1.50 | 28.27 |
October | 0.67 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
November | 15.17 | 14.95 | 4.33 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
December | 43.83 | 14.76 | 12.50 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
Annual Sum or Average | 158.67 | 15.07 | 47.17 | 15.32 | 11.83 | 16.02 | 6.17 | 16.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 | 0.00 | 14.80 |
Maximum of Months | 62.83 | 16.82 | 22.50 | 16.82 | 5.00 | 28.49 | 2.50 | 28.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.17 | 16.24 | 18.33 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
February | 10.00 | 15.33 | 3.50 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
March | 7.83 | 16.15 | 2.83 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 15.95 | 0.17 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
December | 8.00 | 15.22 | 3.50 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
Annual Sum or Average | 63.83 | 15.96 | 28.33 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.17 | 17.19 | 18.33 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.17 | 16.25 | 16.67 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
February | 8.17 | 15.31 | 1.50 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
March | 6.67 | 15.50 | 1.50 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.60 | 1.83 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.82 | 1.33 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.46 | 0.33 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
December | 8.00 | 15.22 | 3.33 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
Annual Sum or Average | 59.33 | 15.88 | 23.00 | 16.30 | 3.50 | 16.76 | 3.50 | 17.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.17 | 17.21 | 16.67 | 17.21 | 1.83 | 27.82 | 1.83 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 130.17 | 16.71 | 113.67 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
February | 59.33 | 17.36 | 56.50 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
March | 53.33 | 17.90 | 49.00 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
April | 27.00 | 18.84 | 27.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
May | 20.83 | 18.92 | 20.83 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
June | 1.33 | 19.42 | 1.33 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 |
September | 4.83 | 19.87 | 4.83 | 19.87 | 3.17 | 21.88 | 3.00 | 23.05 |
October | 13.00 | 19.17 | 13.00 | 19.17 | 0.50 | 19.33 | 0.50 | 19.48 |
November | 33.67 | 18.22 | 33.17 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
December | 69.50 | 17.21 | 65.00 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
Annual Sum or Average | 413.00 | 17.54 | 384.33 | 17.63 | 4.50 | 17.68 | 4.33 | 17.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.17 | 19.87 | 113.67 | 19.87 | 3.17 | 27.63 | 3.00 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.67 | 16.15 | 15.83 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
February | 8.67 | 15.25 | 2.17 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
March | 7.67 | 15.95 | 2.50 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.17 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.01 | 1.17 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.01 | 0.67 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.93 | 1.17 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
December | 8.33 | 15.17 | 3.50 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
Annual Sum or Average | 60.83 | 15.85 | 24.00 | 16.25 | 6.17 | 17.05 | 3.17 | 17.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.67 | 17.18 | 15.83 | 17.18 | 2.67 | 28.01 | 1.17 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.33 | 15.82 | 16.00 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
February | 10.17 | 15.13 | 3.33 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
March | 7.33 | 15.83 | 2.17 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
November | 4.50 | 15.48 | 1.00 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
December | 13.67 | 15.14 | 4.17 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
Annual Sum or Average | 73.33 | 15.58 | 26.67 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.33 | 17.24 | 16.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.17 | 15.61 | 13.00 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
February | 9.00 | 15.11 | 1.50 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
March | 6.17 | 15.12 | 1.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.83 | 0.83 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.10 | 4.00 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.34 | 1.67 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.68 | 1.33 | 27.68 |
October | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
November | 3.83 | 15.12 | 0.33 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
December | 15.33 | 15.00 | 3.83 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Annual Sum or Average | 69.83 | 15.35 | 19.67 | 15.62 | 7.83 | 16.62 | 7.83 | 17.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.17 | 17.18 | 13.00 | 17.18 | 4.00 | 28.34 | 4.00 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.50 | 15.98 | 10.83 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
February | 6.67 | 15.35 | 0.83 | 15.38 | 0.33 | 15.89 | 0.33 | 16.36 |
March | 6.00 | 15.56 | 1.50 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.17 | 17.13 | 0.00 | 17.13 | 0.17 | 22.25 | 0.17 | 23.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.69 | 1.17 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.96 | 1.83 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.31 | 3.00 | 28.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.97 | 1.00 | 27.97 |
November | 3.17 | 15.66 | 0.33 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
December | 8.33 | 14.93 | 2.33 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 53.83 | 15.68 | 15.83 | 16.08 | 7.83 | 17.29 | 7.67 | 18.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.50 | 17.13 | 10.83 | 17.13 | 3.17 | 28.31 | 3.00 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.67 | 15.44 | 11.83 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 9.33 | 15.11 | 2.00 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 |
March | 6.67 | 15.38 | 1.50 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 17.01 | 0.00 | 17.01 | 0.83 | 26.13 | 0.17 | 26.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.80 | 0.83 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.39 | 2.00 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.31 | 0.83 | 28.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.27 | 1.33 | 28.27 |
October | 0.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
November | 4.00 | 15.20 | 0.33 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
December | 15.83 | 14.92 | 4.33 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
Annual Sum or Average | 69.83 | 15.26 | 20.00 | 15.49 | 10.83 | 16.86 | 5.17 | 17.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.67 | 17.16 | 11.83 | 17.16 | 4.83 | 28.39 | 2.00 | 28.39 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.12 | 114.33 | 21.85 | 114.33 | 21.66 |
February | 452.67 | 22.91 | 21.17 | 22.80 | 21.17 | 22.70 |
March | 506.00 | 23.42 | 12.17 | 23.36 | 12.17 | 23.31 |
April | 399.67 | 23.83 | 0.00 | 23.83 | 0.00 | 23.83 |
May | 228.67 | 23.73 | 71.33 | 24.20 | 0.00 | 24.20 |
June | 10.83 | 23.80 | 233.00 | 24.71 | 0.00 | 24.71 |
July | 0.00 | 0.00 | 376.83 | 24.60 | 0.00 | 24.60 |
August | 0.00 | 0.00 | 280.00 | 24.78 | 0.00 | 24.78 |
September | 36.17 | 23.91 | 191.67 | 24.69 | 0.00 | 24.69 |
October | 217.83 | 23.90 | 32.00 | 24.15 | 0.00 | 24.15 |
November | 403.17 | 23.64 | 1.17 | 23.63 | 1.17 | 23.62 |
December | 497.00 | 22.96 | 28.00 | 22.84 | 28.00 | 22.73 |
Annual Sum or Average | 3254.00 | 23.22 | 1361.67 | 23.53 | 176.83 | 23.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.85 | 0.00 | 21.66 |
Maximum of Months | 506.00 | 23.91 | 376.83 | 24.78 | 114.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.93 | 304.17 | 20.75 | 304.17 | 20.66 |
February | 454.00 | 21.56 | 144.83 | 21.32 | 144.83 | 21.18 |
March | 514.00 | 22.15 | 65.83 | 21.96 | 65.83 | 21.81 |
April | 480.67 | 22.84 | 8.83 | 22.81 | 8.83 | 22.79 |
May | 394.17 | 23.06 | 28.33 | 23.12 | 6.67 | 23.08 |
June | 141.83 | 23.39 | 127.67 | 23.85 | 0.00 | 23.85 |
July | 39.50 | 23.47 | 253.00 | 24.28 | 0.00 | 24.28 |
August | 65.17 | 23.54 | 156.50 | 24.28 | 0.00 | 24.28 |
September | 226.17 | 23.30 | 115.17 | 23.69 | 0.00 | 23.69 |
October | 472.17 | 23.07 | 2.17 | 23.06 | 2.17 | 23.05 |
November | 489.00 | 22.26 | 56.00 | 22.08 | 56.00 | 21.94 |
December | 497.00 | 21.33 | 204.67 | 21.05 | 204.67 | 20.89 |
Annual Sum or Average | 4275.67 | 22.26 | 1467.17 | 22.27 | 793.17 | 22.05 |
Minimum of Months | 39.50 | 20.93 | 2.17 | 20.75 | 0.00 | 20.66 |
Maximum of Months | 514.00 | 23.54 | 304.17 | 24.28 | 304.17 | 24.28 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.23 | 452.00 | 20.18 | 452.00 | 20.16 |
February | 454.00 | 20.66 | 335.00 | 20.53 | 335.00 | 20.48 |
March | 514.00 | 21.08 | 222.17 | 20.85 | 222.17 | 20.72 |
April | 479.17 | 21.76 | 102.67 | 21.52 | 102.67 | 21.35 |
May | 440.17 | 22.32 | 60.00 | 22.17 | 48.33 | 22.01 |
June | 237.50 | 22.91 | 112.67 | 23.32 | 0.67 | 23.31 |
July | 131.33 | 23.09 | 212.17 | 23.79 | 0.00 | 23.79 |
August | 197.17 | 23.06 | 130.50 | 23.54 | 0.00 | 23.54 |
September | 336.33 | 22.46 | 80.83 | 22.71 | 13.33 | 22.65 |
October | 498.33 | 21.76 | 77.83 | 21.56 | 77.83 | 21.40 |
November | 489.00 | 20.95 | 249.50 | 20.72 | 249.50 | 20.61 |
December | 497.00 | 20.37 | 392.67 | 20.24 | 392.67 | 20.20 |
Annual Sum or Average | 4776.00 | 21.44 | 2428.00 | 21.33 | 1894.17 | 21.10 |
Minimum of Months | 131.33 | 20.23 | 60.00 | 20.18 | 0.00 | 20.16 |
Maximum of Months | 514.00 | 23.09 | 452.00 | 23.79 | 452.00 | 23.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 497.67 | 19.70 | 497.67 | 19.70 |
February | 454.00 | 20.02 | 436.00 | 20.00 | 436.00 | 19.99 |
March | 514.00 | 20.29 | 389.67 | 20.19 | 389.67 | 20.15 |
April | 485.00 | 20.72 | 226.83 | 20.50 | 226.83 | 20.39 |
May | 476.83 | 21.33 | 135.33 | 21.17 | 121.00 | 20.99 |
June | 334.00 | 22.02 | 102.33 | 22.41 | 10.50 | 22.36 |
July | 241.00 | 22.34 | 169.50 | 23.06 | 1.50 | 23.05 |
August | 324.50 | 22.15 | 111.33 | 22.61 | 6.33 | 22.57 |
September | 415.00 | 21.44 | 97.17 | 21.50 | 59.00 | 21.36 |
October | 502.00 | 20.67 | 229.33 | 20.48 | 229.33 | 20.37 |
November | 489.00 | 20.10 | 392.67 | 20.00 | 392.67 | 19.96 |
December | 497.00 | 19.80 | 483.83 | 19.79 | 483.83 | 19.78 |
Annual Sum or Average | 5234.33 | 20.73 | 3271.67 | 20.62 | 2854.33 | 20.44 |
Minimum of Months | 241.00 | 19.70 | 97.17 | 19.70 | 1.50 | 19.70 |
Maximum of Months | 514.00 | 22.34 | 497.67 | 23.06 | 497.67 | 23.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 487.33 | 19.74 | 487.33 | 19.73 |
February | 454.00 | 20.18 | 382.00 | 20.09 | 382.00 | 20.06 |
March | 512.83 | 20.50 | 328.17 | 20.31 | 328.17 | 20.23 |
April | 445.33 | 21.05 | 167.00 | 20.78 | 160.33 | 20.60 |
May | 405.00 | 21.50 | 130.33 | 21.43 | 93.00 | 21.19 |
June | 204.83 | 22.12 | 220.17 | 23.19 | 8.00 | 23.15 |
July | 134.17 | 22.86 | 317.83 | 23.89 | 12.50 | 23.96 |
August | 201.17 | 22.34 | 262.67 | 23.40 | 10.00 | 23.42 |
September | 331.83 | 21.67 | 142.33 | 22.15 | 41.33 | 22.01 |
October | 496.83 | 21.00 | 169.00 | 20.73 | 169.00 | 20.58 |
November | 489.00 | 20.22 | 358.33 | 20.09 | 358.33 | 20.03 |
December | 497.00 | 19.83 | 473.33 | 19.80 | 473.33 | 19.79 |
Annual Sum or Average | 4674.00 | 20.78 | 3438.50 | 20.91 | 2523.33 | 20.68 |
Minimum of Months | 134.17 | 19.76 | 130.33 | 19.74 | 8.00 | 19.73 |
Maximum of Months | 512.83 | 22.86 | 487.33 | 23.89 | 487.33 | 23.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.50 | 20.10 | 417.17 | 19.96 | 417.17 | 19.90 |
February | 424.00 | 20.54 | 297.50 | 20.37 | 287.67 | 20.25 |
March | 464.83 | 20.64 | 297.83 | 20.45 | 287.83 | 20.33 |
April | 421.83 | 20.98 | 197.33 | 20.85 | 171.17 | 20.66 |
May | 403.50 | 21.39 | 163.33 | 21.43 | 110.00 | 21.21 |
June | 275.50 | 21.90 | 169.00 | 22.67 | 14.33 | 22.59 |
July | 198.33 | 22.33 | 250.67 | 23.39 | 8.33 | 23.40 |
August | 238.00 | 22.18 | 233.33 | 23.17 | 10.83 | 23.17 |
September | 305.50 | 21.74 | 192.50 | 22.43 | 50.83 | 22.33 |
October | 401.00 | 21.07 | 195.50 | 21.10 | 144.67 | 20.88 |
November | 452.83 | 20.67 | 280.00 | 20.46 | 271.17 | 20.34 |
December | 493.83 | 20.17 | 388.17 | 19.98 | 388.17 | 19.91 |
Annual Sum or Average | 4580.67 | 20.96 | 3082.33 | 21.08 | 2162.17 | 20.84 |
Minimum of Months | 198.33 | 20.10 | 163.33 | 19.96 | 8.33 | 19.90 |
Maximum of Months | 501.50 | 22.33 | 417.17 | 23.39 | 417.17 | 23.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 482.00 | 19.71 | 482.00 | 19.71 |
February | 450.83 | 20.18 | 380.83 | 20.07 | 380.83 | 20.03 |
March | 502.17 | 20.44 | 350.83 | 20.27 | 350.83 | 20.20 |
April | 447.67 | 20.85 | 210.67 | 20.69 | 192.50 | 20.53 |
May | 406.00 | 21.38 | 162.17 | 21.47 | 102.67 | 21.26 |
June | 274.67 | 21.90 | 177.00 | 22.73 | 16.00 | 22.70 |
July | 217.67 | 22.39 | 230.67 | 23.37 | 12.67 | 23.44 |
August | 273.33 | 22.13 | 188.17 | 22.95 | 10.50 | 22.96 |
September | 362.50 | 21.53 | 144.33 | 21.90 | 58.50 | 21.78 |
October | 479.50 | 20.85 | 206.17 | 20.64 | 198.00 | 20.50 |
November | 488.33 | 20.27 | 356.00 | 20.12 | 356.00 | 20.05 |
December | 497.00 | 19.83 | 462.67 | 19.79 | 462.67 | 19.77 |
Annual Sum or Average | 4901.67 | 20.76 | 3351.50 | 20.81 | 2623.17 | 20.60 |
Minimum of Months | 217.67 | 19.74 | 144.33 | 19.71 | 10.50 | 19.71 |
Maximum of Months | 502.17 | 22.39 | 482.00 | 23.37 | 482.00 | 23.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.88 | 502.00 | 19.88 | 502.00 | 19.88 |
February | 454.00 | 20.22 | 447.33 | 20.21 | 447.33 | 20.21 |
March | 514.00 | 20.40 | 488.00 | 20.38 | 488.00 | 20.37 |
April | 485.00 | 20.65 | 312.50 | 20.55 | 312.50 | 20.51 |
May | 506.17 | 21.30 | 148.33 | 21.11 | 148.33 | 21.00 |
June | 422.83 | 22.26 | 23.83 | 22.33 | 2.00 | 22.32 |
July | 285.00 | 22.74 | 98.33 | 23.10 | 0.00 | 23.10 |
August | 367.83 | 22.61 | 54.33 | 22.82 | 0.17 | 22.81 |
September | 414.83 | 21.88 | 51.33 | 22.00 | 15.83 | 21.95 |
October | 502.00 | 21.24 | 95.67 | 21.12 | 95.67 | 21.03 |
November | 489.00 | 20.57 | 316.00 | 20.46 | 316.00 | 20.41 |
December | 497.00 | 20.06 | 480.83 | 20.04 | 480.83 | 20.04 |
Annual Sum or Average | 5439.67 | 21.03 | 3018.50 | 20.83 | 2808.67 | 20.68 |
Minimum of Months | 285.00 | 19.88 | 23.83 | 19.88 | 0.00 | 19.88 |
Maximum of Months | 514.00 | 22.74 | 502.00 | 23.10 | 502.00 | 23.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 499.50 | 19.97 | 499.50 | 19.96 |
February | 454.00 | 20.42 | 405.17 | 20.36 | 405.17 | 20.33 |
March | 514.00 | 20.61 | 360.33 | 20.48 | 360.33 | 20.43 |
April | 478.50 | 21.18 | 189.33 | 20.94 | 189.33 | 20.81 |
May | 460.00 | 21.75 | 98.00 | 21.57 | 86.00 | 21.39 |
June | 227.50 | 22.50 | 187.67 | 23.37 | 1.67 | 23.36 |
July | 86.17 | 23.20 | 337.83 | 24.16 | 7.33 | 24.20 |
August | 147.17 | 22.81 | 265.33 | 23.81 | 3.83 | 23.84 |
September | 287.17 | 22.23 | 135.67 | 22.92 | 7.33 | 22.90 |
October | 477.67 | 21.76 | 55.83 | 21.62 | 55.83 | 21.51 |
November | 489.00 | 20.83 | 263.83 | 20.67 | 263.83 | 20.60 |
December | 497.00 | 20.14 | 470.00 | 20.12 | 470.00 | 20.11 |
Annual Sum or Average | 4620.17 | 21.10 | 3268.50 | 21.22 | 2350.17 | 21.00 |
Minimum of Months | 86.17 | 19.97 | 55.83 | 19.97 | 1.67 | 19.96 |
Maximum of Months | 514.00 | 23.20 | 499.50 | 24.16 | 499.50 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 19.45 | 438.83 | 19.32 | 438.83 | 19.28 |
February | 435.17 | 20.30 | 301.17 | 20.09 | 295.17 | 19.96 |
March | 508.50 | 20.59 | 293.50 | 20.34 | 293.50 | 20.22 |
April | 467.83 | 20.98 | 197.00 | 20.72 | 197.00 | 20.59 |
May | 464.67 | 21.36 | 133.33 | 21.20 | 117.00 | 21.01 |
June | 337.17 | 22.05 | 104.17 | 22.54 | 6.67 | 22.50 |
July | 174.00 | 22.54 | 235.50 | 23.57 | 0.33 | 23.57 |
August | 193.67 | 22.41 | 231.67 | 23.48 | 2.17 | 23.49 |
September | 254.83 | 22.12 | 181.67 | 23.10 | 19.33 | 23.14 |
October | 385.50 | 21.79 | 74.00 | 21.97 | 30.00 | 21.85 |
November | 450.67 | 21.05 | 181.17 | 20.82 | 170.17 | 20.63 |
December | 497.00 | 20.09 | 354.17 | 19.84 | 354.17 | 19.74 |
Annual Sum or Average | 4669.50 | 20.99 | 2726.17 | 21.03 | 1924.33 | 20.76 |
Minimum of Months | 174.00 | 19.45 | 74.00 | 19.32 | 0.33 | 19.28 |
Maximum of Months | 508.50 | 22.54 | 438.83 | 23.57 | 438.83 | 23.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.94 | 493.33 | 19.93 | 493.33 | 19.92 |
February | 453.67 | 20.40 | 400.17 | 20.32 | 400.17 | 20.29 |
March | 514.00 | 20.58 | 408.17 | 20.48 | 408.17 | 20.44 |
April | 471.83 | 20.98 | 218.50 | 20.80 | 217.17 | 20.69 |
May | 445.50 | 21.62 | 117.50 | 21.55 | 94.67 | 21.38 |
June | 292.33 | 22.33 | 123.33 | 22.92 | 1.83 | 22.91 |
July | 156.67 | 22.88 | 248.33 | 23.80 | 4.33 | 23.83 |
August | 222.00 | 22.67 | 190.17 | 23.45 | 3.50 | 23.46 |
September | 319.33 | 22.06 | 118.00 | 22.65 | 11.00 | 22.65 |
October | 478.67 | 21.61 | 66.33 | 21.49 | 62.33 | 21.39 |
November | 488.50 | 20.83 | 256.00 | 20.65 | 256.00 | 20.56 |
December | 497.00 | 20.12 | 455.33 | 20.07 | 455.33 | 20.06 |
Annual Sum or Average | 4841.50 | 21.08 | 3095.17 | 21.10 | 2407.83 | 20.90 |
Minimum of Months | 156.67 | 19.94 | 66.33 | 19.93 | 1.83 | 19.92 |
Maximum of Months | 514.00 | 22.88 | 493.33 | 23.80 | 493.33 | 23.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.88 | 492.67 | 19.87 | 492.67 | 19.87 |
February | 454.00 | 20.28 | 406.17 | 20.23 | 406.17 | 20.21 |
March | 514.00 | 20.55 | 323.50 | 20.41 | 323.50 | 20.36 |
April | 485.00 | 21.13 | 146.67 | 20.93 | 146.67 | 20.81 |
May | 463.17 | 21.75 | 93.33 | 21.64 | 75.83 | 21.46 |
June | 277.17 | 22.55 | 112.17 | 22.98 | 1.67 | 22.97 |
July | 153.50 | 22.86 | 212.33 | 23.62 | 0.00 | 23.62 |
August | 252.50 | 22.70 | 131.17 | 23.22 | 0.83 | 23.21 |
September | 378.33 | 21.92 | 83.83 | 22.18 | 20.33 | 22.10 |
October | 502.00 | 21.23 | 112.67 | 21.06 | 112.67 | 20.93 |
November | 489.00 | 20.48 | 312.67 | 20.33 | 312.67 | 20.26 |
December | 497.00 | 19.98 | 461.67 | 19.94 | 461.67 | 19.93 |
Annual Sum or Average | 4967.67 | 21.03 | 2888.83 | 20.95 | 2354.67 | 20.75 |
Minimum of Months | 153.50 | 19.88 | 83.83 | 19.87 | 0.00 | 19.87 |
Maximum of Months | 514.00 | 22.86 | 492.67 | 23.62 | 492.67 | 23.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.78 | 409.17 | 19.75 | 409.17 | 19.75 |
February | 385.00 | 20.39 | 298.67 | 20.25 | 298.67 | 20.20 |
March | 428.83 | 20.73 | 243.33 | 20.51 | 243.33 | 20.41 |
April | 371.50 | 21.35 | 110.00 | 21.18 | 100.00 | 20.99 |
May | 336.00 | 21.79 | 95.00 | 21.82 | 54.33 | 21.61 |
June | 166.83 | 22.53 | 180.33 | 23.50 | 4.67 | 23.52 |
July | 96.83 | 23.33 | 268.83 | 24.17 | 12.83 | 24.26 |
August | 158.00 | 22.69 | 202.67 | 23.67 | 5.50 | 23.71 |
September | 264.00 | 22.00 | 116.67 | 22.66 | 16.83 | 22.61 |
October | 409.33 | 21.45 | 84.50 | 21.26 | 82.33 | 21.10 |
November | 416.83 | 20.60 | 252.00 | 20.42 | 252.00 | 20.34 |
December | 422.00 | 19.88 | 379.50 | 19.82 | 379.50 | 19.79 |
Annual Sum or Average | 3882.17 | 21.02 | 2640.67 | 21.15 | 1859.17 | 20.90 |
Minimum of Months | 96.83 | 19.78 | 84.50 | 19.75 | 4.67 | 19.75 |
Maximum of Months | 428.83 | 23.33 | 409.17 | 24.17 | 409.17 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.67 | 20.41 | 394.00 | 20.24 | 392.33 | 20.16 |
February | 412.00 | 20.94 | 257.67 | 20.74 | 245.17 | 20.58 |
March | 447.50 | 20.98 | 236.50 | 20.82 | 219.83 | 20.68 |
April | 402.67 | 21.43 | 132.83 | 21.35 | 107.50 | 21.17 |
May | 376.00 | 21.80 | 122.00 | 21.89 | 66.83 | 21.69 |
June | 230.83 | 22.41 | 171.83 | 23.19 | 1.83 | 23.18 |
July | 135.83 | 22.89 | 278.83 | 23.86 | 5.00 | 23.90 |
August | 180.67 | 22.72 | 257.67 | 23.66 | 5.83 | 23.69 |
September | 249.67 | 22.21 | 192.00 | 23.10 | 23.17 | 23.12 |
October | 364.67 | 21.67 | 137.00 | 21.90 | 67.67 | 21.73 |
November | 421.67 | 21.13 | 212.50 | 20.99 | 189.33 | 20.81 |
December | 471.33 | 20.48 | 331.17 | 20.25 | 331.17 | 20.15 |
Annual Sum or Average | 4185.50 | 21.33 | 2724.00 | 21.53 | 1655.67 | 21.27 |
Minimum of Months | 135.83 | 20.41 | 122.00 | 20.24 | 1.83 | 20.15 |
Maximum of Months | 492.67 | 22.89 | 394.00 | 23.86 | 392.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.93 | 474.83 | 19.90 | 474.83 | 19.89 |
February | 449.33 | 20.44 | 349.33 | 20.31 | 349.33 | 20.26 |
March | 500.50 | 20.70 | 286.17 | 20.51 | 286.17 | 20.43 |
April | 445.83 | 21.21 | 143.50 | 21.09 | 126.17 | 20.94 |
May | 399.17 | 21.70 | 126.17 | 21.84 | 65.67 | 21.66 |
June | 255.83 | 22.26 | 170.67 | 23.06 | 5.67 | 23.07 |
July | 178.17 | 22.75 | 245.17 | 23.69 | 10.00 | 23.77 |
August | 234.17 | 22.47 | 196.83 | 23.31 | 5.17 | 23.34 |
September | 338.00 | 21.84 | 125.33 | 22.37 | 24.00 | 22.34 |
October | 469.83 | 21.29 | 111.33 | 21.16 | 100.33 | 21.02 |
November | 487.33 | 20.67 | 274.67 | 20.48 | 274.67 | 20.38 |
December | 497.00 | 20.04 | 429.00 | 19.96 | 429.00 | 19.93 |
Annual Sum or Average | 4757.17 | 21.04 | 2933.00 | 21.11 | 2151.00 | 20.89 |
Minimum of Months | 178.17 | 19.93 | 111.33 | 19.90 | 5.17 | 19.89 |
Maximum of Months | 502.00 | 22.75 | 474.83 | 23.69 | 474.83 | 23.77 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.12382 | 13.98213 | -0.3494 | 9.00171 |
February | 454.00000 | 22.91264 | 15.73085 | -0.1353 | 6.44729 |
March | 514.00000 | 23.43618 | 16.54622 | 0.01288 | 5.79440 |
April | 485.00000 | 23.94239 | 19.77984 | 0.17115 | 5.85475 |
May | 508.00000 | 24.19486 | 22.94906 | -0.6286 | 14.53237 |
June | 496.00000 | 24.38469 | 30.71697 | -0.4392 | 9.59714 |
July | 497.00000 | 24.46738 | 35.06713 | -0.3542 | 8.30701 |
August | 514.00000 | 24.43902 | 30.77033 | -0.3952 | 8.89074 |
September | 485.00000 | 24.39107 | 30.05461 | -0.4529 | 10.02349 |
October | 502.00000 | 24.22890 | 21.86862 | 0.27244 | 6.77382 |
November | 489.00000 | 23.80644 | 17.96076 | 0.11357 | 5.87514 |
December | 497.00000 | 22.96271 | 15.24110 | -0.1242 | 6.49103 |
Annual Sum or Average | 5943.00000 | 23.77938 | 22.59954 | -0.1940 | 8.15509 |
Minimum of Months | 454.00000 | 22.12382 | 13.98213 | -0.6286 | 5.79440 |
Maximum of Months | 514.00000 | 24.46738 | 35.06713 | 0.27244 | 14.53237 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.93228 | 15.20658 | -0.6364 | 15.03245 |
February | 454.00000 | 21.55863 | 17.32055 | -0.4503 | 10.59009 |
March | 514.00000 | 22.15407 | 18.47346 | -0.2861 | 8.17741 |
April | 485.00000 | 22.85032 | 21.89196 | -0.0829 | 6.12997 |
May | 508.00000 | 23.36400 | 24.69641 | -0.9131 | 24.67074 |
June | 496.00000 | 23.95338 | 32.06668 | -0.5992 | 13.34864 |
July | 497.00000 | 24.16675 | 35.97419 | -0.4785 | 10.33584 |
August | 514.00000 | 24.14872 | 31.74106 | -0.5218 | 11.24574 |
September | 485.00000 | 23.80572 | 31.69661 | -0.6778 | 16.02754 |
October | 502.00000 | 23.13224 | 24.29521 | 0.00253 | 5.77381 |
November | 489.00000 | 22.25904 | 20.08332 | -0.2536 | 7.77514 |
December | 497.00000 | 21.33185 | 16.90453 | -0.5090 | 12.32832 |
Annual Sum or Average | 5943.00000 | 22.81391 | 24.23800 | -0.4514 | 11.81261 |
Minimum of Months | 454.00000 | 20.93228 | 15.20658 | -0.9131 | 5.77381 |
Maximum of Months | 514.00000 | 24.16675 | 35.97419 | 0.00253 | 24.67074 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.23424 | 15.11355 | -0.8482 | 22.26134 |
February | 454.00000 | 20.66434 | 17.58992 | -0.6934 | 16.77666 |
March | 514.00000 | 21.08413 | 18.73103 | -0.5532 | 13.24571 |
April | 485.00000 | 21.78784 | 22.51647 | -0.3311 | 9.06964 |
May | 508.00000 | 22.56800 | 25.08478 | -1.1654 | 35.76083 |
June | 496.00000 | 23.53149 | 32.40934 | -0.7227 | 17.96661 |
July | 497.00000 | 23.84862 | 36.11116 | -0.5650 | 12.87690 |
August | 514.00000 | 23.73919 | 32.07660 | -0.6469 | 15.28904 |
September | 485.00000 | 22.96620 | 32.65218 | -0.9511 | 27.00889 |
October | 502.00000 | 21.77419 | 25.55655 | -0.3186 | 8.60219 |
November | 489.00000 | 20.94595 | 20.71695 | -0.5842 | 14.03503 |
December | 497.00000 | 20.36720 | 17.14360 | -0.7800 | 20.19417 |
Annual Sum or Average | 5943.00000 | 21.97017 | 24.68289 | -0.6804 | 17.77763 |
Minimum of Months | 454.00000 | 20.23424 | 15.11355 | -1.1654 | 8.60219 |
Maximum of Months | 514.00000 | 23.84862 | 36.11116 | -0.3186 | 35.76083 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70376 | 14.71098 | -1.0846 | 31.97107 |
February | 454.00000 | 20.02168 | 17.32702 | -0.9275 | 25.27552 |
March | 514.00000 | 20.29082 | 18.63642 | -0.7928 | 20.35965 |
April | 485.00000 | 20.72404 | 23.28135 | -0.5894 | 14.36460 |
May | 508.00000 | 21.50658 | 26.47440 | -1.4813 | 49.87187 |
June | 496.00000 | 22.63572 | 33.85948 | -0.9479 | 27.42611 |
July | 497.00000 | 23.16202 | 37.22744 | -0.7160 | 18.60058 |
August | 514.00000 | 22.81801 | 33.60770 | -0.8862 | 24.91726 |
September | 485.00000 | 21.79911 | 34.58571 | -1.3001 | 42.58099 |
October | 502.00000 | 20.67428 | 26.49678 | -0.5899 | 13.90785 |
November | 489.00000 | 20.10022 | 20.82939 | -0.8401 | 22.32431 |
December | 497.00000 | 19.80250 | 16.95493 | -1.0124 | 29.02482 |
Annual Sum or Average | 5943.00000 | 21.11329 | 25.37932 | -0.9311 | 26.74103 |
Minimum of Months | 454.00000 | 19.70376 | 14.71098 | -1.4813 | 13.90785 |
Maximum of Months | 514.00000 | 23.16202 | 37.22744 | -0.5894 | 49.87187 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.75703 | 14.85131 | -1.0503 | 30.58176 |
February | 454.00000 | 20.18232 | 17.35657 | -0.8555 | 22.76767 |
March | 514.00000 | 20.51245 | 18.63977 | -0.7033 | 18.13163 |
April | 485.00000 | 21.29249 | 22.77667 | -0.4207 | 12.45829 |
May | 508.00000 | 22.02311 | 25.91015 | -1.2624 | 40.68824 |
June | 496.00000 | 23.29998 | 32.60552 | -0.6625 | 19.21647 |
July | 497.00000 | 23.79957 | 35.82515 | -0.4185 | 12.29632 |
August | 514.00000 | 23.43929 | 32.40668 | -0.6037 | 17.40186 |
September | 485.00000 | 22.47081 | 33.57521 | -1.0366 | 32.98576 |
October | 502.00000 | 21.02399 | 26.23183 | -0.4769 | 12.05683 |
November | 489.00000 | 20.21611 | 20.92765 | -0.7880 | 20.42633 |
December | 497.00000 | 19.82802 | 17.12294 | -0.9864 | 28.04829 |
Annual Sum or Average | 5943.00000 | 21.49829 | 24.89579 | -0.7718 | 22.25920 |
Minimum of Months | 454.00000 | 19.75703 | 14.85131 | -1.2624 | 12.05683 |
Maximum of Months | 514.00000 | 23.79957 | 35.82515 | -0.4185 | 40.68824 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10758 | 14.31534 | -0.9132 | 26.09945 |
February | 454.00000 | 20.78943 | 16.54620 | -0.6601 | 19.20688 |
March | 514.00000 | 20.96370 | 17.93809 | -0.5715 | 16.76173 |
April | 485.00000 | 21.41131 | 22.41518 | -0.3932 | 12.87879 |
May | 508.00000 | 21.97162 | 25.76642 | -1.2969 | 42.94739 |
June | 496.00000 | 22.87480 | 33.34341 | -0.8397 | 25.09766 |
July | 497.00000 | 23.40639 | 36.60350 | -0.5862 | 16.76861 |
August | 514.00000 | 23.23931 | 32.61636 | -0.6701 | 20.18160 |
September | 485.00000 | 22.65030 | 32.95654 | -0.9409 | 31.23785 |
October | 502.00000 | 21.70568 | 24.98177 | -0.2864 | 11.68314 |
November | 489.00000 | 20.91937 | 19.88020 | -0.5794 | 16.55408 |
December | 497.00000 | 20.19347 | 16.54030 | -0.8423 | 23.99327 |
Annual Sum or Average | 5943.00000 | 21.69360 | 24.53996 | -0.7161 | 21.99084 |
Minimum of Months | 454.00000 | 20.10758 | 14.31534 | -1.2969 | 11.68314 |
Maximum of Months | 514.00000 | 23.40639 | 36.60350 | -0.2864 | 42.94739 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.74060 | 14.82301 | -1.0622 | 31.12966 |
February | 454.00000 | 20.20679 | 17.29597 | -0.8579 | 23.53127 |
March | 514.00000 | 20.51695 | 18.57879 | -0.7175 | 19.07734 |
April | 485.00000 | 21.10902 | 22.99898 | -0.4724 | 13.58749 |
May | 508.00000 | 21.94577 | 26.03317 | -1.2921 | 43.01772 |
June | 496.00000 | 22.87823 | 33.52880 | -0.8139 | 24.90349 |
July | 497.00000 | 23.34493 | 36.92986 | -0.5874 | 17.63111 |
August | 514.00000 | 23.05363 | 33.21000 | -0.7439 | 22.21993 |
September | 485.00000 | 22.18186 | 34.00683 | -1.1324 | 37.51942 |
October | 502.00000 | 20.99207 | 26.22088 | -0.4924 | 13.05076 |
November | 489.00000 | 20.27789 | 20.79441 | -0.7776 | 20.58358 |
December | 497.00000 | 19.83239 | 17.06722 | -0.9891 | 28.25361 |
Annual Sum or Average | 5943.00000 | 21.35018 | 25.16975 | -0.8284 | 24.55841 |
Minimum of Months | 454.00000 | 19.74060 | 14.82301 | -1.2921 | 13.05076 |
Maximum of Months | 514.00000 | 23.34493 | 36.92986 | -0.4724 | 43.01772 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.88283 | 14.57011 | -1.0329 | 29.30752 |
February | 454.00000 | 20.21830 | 17.34374 | -0.8880 | 23.01207 |
March | 514.00000 | 20.39600 | 18.81251 | -0.7951 | 19.61964 |
April | 485.00000 | 20.64908 | 23.58401 | -0.6517 | 14.73803 |
May | 508.00000 | 21.31280 | 27.26024 | -1.5986 | 55.91997 |
June | 496.00000 | 22.48990 | 34.67968 | -1.0611 | 30.67979 |
July | 497.00000 | 23.25343 | 37.81185 | -0.7475 | 18.22896 |
August | 514.00000 | 22.99918 | 33.84316 | -0.8722 | 22.87024 |
September | 485.00000 | 22.18247 | 34.25895 | -1.1731 | 36.32280 |
October | 502.00000 | 21.23944 | 25.77619 | -0.4220 | 9.37917 |
November | 489.00000 | 20.57171 | 20.46414 | -0.6818 | 16.09421 |
December | 497.00000 | 20.05940 | 16.85155 | -0.9098 | 24.38200 |
Annual Sum or Average | 5943.00000 | 21.28030 | 25.48725 | -0.9037 | 25.09587 |
Minimum of Months | 454.00000 | 19.88283 | 14.57011 | -1.5986 | 9.37917 |
Maximum of Months | 514.00000 | 23.25343 | 37.81185 | -0.4220 | 55.91997 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.96762 | 14.75606 | -0.9926 | 27.65481 |
February | 454.00000 | 20.41796 | 17.41058 | -0.8055 | 20.35469 |
March | 514.00000 | 20.60890 | 18.89650 | -0.6997 | 16.97778 |
April | 485.00000 | 21.21923 | 23.15452 | -0.4705 | 11.62341 |
May | 508.00000 | 21.98123 | 26.51808 | -1.3262 | 43.31618 |
June | 496.00000 | 23.46465 | 32.81160 | -0.6760 | 18.36846 |
July | 497.00000 | 24.07614 | 35.86535 | -0.3816 | 9.99343 |
August | 514.00000 | 23.81907 | 32.15168 | -0.5174 | 13.11659 |
September | 485.00000 | 23.07990 | 32.84852 | -0.8370 | 24.15385 |
October | 502.00000 | 21.87884 | 25.17889 | -0.2487 | 7.76023 |
November | 489.00000 | 20.82643 | 20.50727 | -0.6000 | 13.93514 |
December | 497.00000 | 20.14145 | 17.06081 | -0.8727 | 22.93694 |
Annual Sum or Average | 5943.00000 | 21.80093 | 24.80735 | -0.7024 | 19.20510 |
Minimum of Months | 454.00000 | 19.96762 | 14.75606 | -1.3262 | 7.76023 |
Maximum of Months | 514.00000 | 24.07614 | 35.86535 | -0.2487 | 43.31618 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.47197 | 13.69104 | -1.0073 | 29.34848 |
February | 454.00000 | 20.48379 | 16.14048 | -0.6938 | 19.49687 |
March | 514.00000 | 20.62805 | 17.78986 | -0.6282 | 16.20765 |
April | 485.00000 | 21.09731 | 22.47578 | -0.4796 | 12.11119 |
May | 508.00000 | 21.62642 | 26.23647 | -1.4380 | 48.68697 |
June | 496.00000 | 22.73663 | 33.70820 | -0.9410 | 27.38242 |
July | 497.00000 | 23.61191 | 36.41612 | -0.5764 | 14.55412 |
August | 514.00000 | 23.56529 | 32.09211 | -0.5973 | 15.99551 |
September | 485.00000 | 23.17152 | 32.12912 | -0.7504 | 22.89834 |
October | 502.00000 | 22.38544 | 23.65390 | -0.0778 | 8.11961 |
November | 489.00000 | 21.32337 | 19.00455 | -0.4163 | 12.24335 |
December | 497.00000 | 20.09163 | 15.86300 | -0.7973 | 21.88809 |
Annual Sum or Average | 5943.00000 | 21.69093 | 24.14958 | -0.7016 | 20.79859 |
Minimum of Months | 454.00000 | 19.47197 | 13.69104 | -1.4380 | 8.11961 |
Maximum of Months | 514.00000 | 23.61191 | 36.41612 | -0.0778 | 48.68697 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.93567 | 14.75401 | -1.0085 | 28.33031 |
February | 454.00000 | 20.39914 | 17.38791 | -0.8159 | 20.99846 |
March | 514.00000 | 20.58123 | 18.86540 | -0.7197 | 17.74716 |
April | 485.00000 | 21.06798 | 23.32593 | -0.5169 | 12.43523 |
May | 508.00000 | 21.95880 | 26.53173 | -1.3364 | 44.40040 |
June | 496.00000 | 23.08918 | 33.65917 | -0.8148 | 22.68181 |
July | 497.00000 | 23.76271 | 36.73214 | -0.5122 | 12.93419 |
August | 514.00000 | 23.53363 | 32.83954 | -0.6331 | 16.47876 |
September | 485.00000 | 22.80488 | 33.22841 | -0.9269 | 27.86159 |
October | 502.00000 | 21.72663 | 25.31778 | -0.2856 | 8.27293 |
November | 489.00000 | 20.83654 | 20.44360 | -0.5989 | 14.24018 |
December | 497.00000 | 20.11721 | 17.03324 | -0.8812 | 23.44940 |
Annual Sum or Average | 5943.00000 | 21.66141 | 25.05582 | -0.7545 | 20.84736 |
Minimum of Months | 454.00000 | 19.93567 | 14.75401 | -1.3364 | 8.27293 |
Maximum of Months | 514.00000 | 23.76271 | 36.73214 | -0.2856 | 44.40040 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.88013 | 14.43780 | -0.9948 | 28.03157 |
February | 454.00000 | 20.27578 | 17.24546 | -0.8206 | 20.83689 |
March | 514.00000 | 20.54890 | 18.77935 | -0.6863 | 16.45123 |
April | 485.00000 | 21.13492 | 23.15959 | -0.4658 | 10.84122 |
May | 508.00000 | 21.97425 | 26.24660 | -1.3179 | 42.88396 |
June | 496.00000 | 23.18712 | 33.30540 | -0.7895 | 20.56817 |
July | 497.00000 | 23.66331 | 36.71715 | -0.5796 | 13.44122 |
August | 514.00000 | 23.40329 | 32.95358 | -0.7159 | 17.87701 |
September | 485.00000 | 22.40015 | 33.88799 | -1.0922 | 33.40955 |
October | 502.00000 | 21.23385 | 25.99011 | -0.4223 | 9.83467 |
November | 489.00000 | 20.47736 | 20.57374 | -0.6971 | 17.07572 |
December | 497.00000 | 19.97615 | 16.85178 | -0.9098 | 24.81846 |
Annual Sum or Average | 5943.00000 | 21.52386 | 25.05807 | -0.7912 | 21.35741 |
Minimum of Months | 454.00000 | 19.88013 | 14.43780 | -1.3179 | 9.83467 |
Maximum of Months | 514.00000 | 23.66331 | 36.71715 | -0.4223 | 42.88396 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.78083 | 14.26934 | -1.0017 | 28.43083 |
February | 385.00000 | 20.38886 | 17.03366 | -0.7698 | 19.71393 |
March | 433.00000 | 20.75925 | 18.35334 | -0.6153 | 15.40287 |
April | 410.00000 | 21.63514 | 22.44554 | -0.3224 | 10.12328 |
May | 430.00000 | 22.32418 | 25.63742 | -1.1593 | 36.76914 |
June | 418.00000 | 23.53630 | 32.22069 | -0.6038 | 16.62505 |
July | 422.00000 | 24.01572 | 35.58159 | -0.3763 | 10.86715 |
August | 433.00000 | 23.67722 | 31.92638 | -0.5482 | 14.88761 |
September | 410.00000 | 22.83832 | 33.00340 | -0.9056 | 27.67581 |
October | 427.00000 | 21.56926 | 25.41857 | -0.3254 | 9.16164 |
November | 417.00000 | 20.60486 | 20.21627 | -0.6549 | 16.06220 |
December | 422.00000 | 19.87984 | 16.65737 | -0.9199 | 25.31069 |
Annual Sum or Average | 5034.00000 | 21.75905 | 24.42933 | -0.6836 | 19.26504 |
Minimum of Months | 385.00000 | 19.78083 | 14.26934 | -1.1593 | 9.16164 |
Maximum of Months | 433.00000 | 24.01572 | 35.58159 | -0.3224 | 36.76914 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48279 | 13.91310 | -0.7845 | 21.79252 |
February | 454.00000 | 21.26056 | 16.25111 | -0.5119 | 15.36074 |
March | 514.00000 | 21.38828 | 17.84415 | -0.4345 | 13.16935 |
April | 485.00000 | 21.92003 | 22.10738 | -0.2519 | 9.80115 |
May | 508.00000 | 22.43869 | 25.47925 | -1.1333 | 36.16274 |
June | 496.00000 | 23.33722 | 32.84199 | -0.7043 | 19.07372 |
July | 497.00000 | 23.83436 | 36.16282 | -0.4685 | 12.19259 |
August | 514.00000 | 23.69517 | 32.08492 | -0.5334 | 14.53942 |
September | 485.00000 | 23.19575 | 32.27586 | -0.7476 | 23.31307 |
October | 502.00000 | 22.37720 | 24.20698 | -0.0998 | 9.06369 |
November | 489.00000 | 21.56558 | 19.32362 | -0.3877 | 12.58063 |
December | 497.00000 | 20.66041 | 16.15668 | -0.6853 | 19.27322 |
Annual Sum or Average | 5943.00000 | 22.18671 | 24.10211 | -0.5631 | 17.22833 |
Minimum of Months | 454.00000 | 20.48279 | 13.91310 | -1.1333 | 9.06369 |
Maximum of Months | 514.00000 | 23.83436 | 36.16282 | -0.0998 | 36.16274 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.93245 | 14.38676 | -0.9710 | 27.16017 |
February | 454.00000 | 20.47538 | 17.02596 | -0.7500 | 19.40446 |
March | 514.00000 | 20.78169 | 18.52774 | -0.6117 | 15.41140 |
April | 485.00000 | 21.44935 | 22.77152 | -0.3633 | 10.41824 |
May | 508.00000 | 22.25200 | 25.85951 | -1.1711 | 37.92875 |
June | 496.00000 | 23.16097 | 33.30292 | -0.7246 | 20.54333 |
July | 497.00000 | 23.62339 | 36.77950 | -0.5076 | 14.00297 |
August | 514.00000 | 23.38141 | 32.87856 | -0.6399 | 17.54147 |
September | 485.00000 | 22.54805 | 33.59417 | -0.9861 | 30.99459 |
October | 502.00000 | 21.46642 | 25.64534 | -0.3428 | 9.54534 |
November | 489.00000 | 20.68561 | 20.34755 | -0.6315 | 15.71790 |
December | 497.00000 | 20.03701 | 16.77512 | -0.8831 | 23.99298 |
Annual Sum or Average | 5943.00000 | 21.65959 | 24.87087 | -0.7155 | 20.23997 |
Minimum of Months | 454.00000 | 19.93245 | 14.38676 | -1.1711 | 9.54534 |
Maximum of Months | 514.00000 | 23.62339 | 36.77950 | -0.3428 | 37.92875 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.165921E+12 | 0.00 | 600.99 | 375671.01 | 14-JAN-06:11 | 0.00 | 37.90 | 55.04 | 0.86 | 0.00 | 0.11 | 0.66 | 14-JAN-06:11 |
February | 0.878190E+11 | 0.00 | 444.94 | 411361.65 | 27-FEB-06:11 | 0.00 | 33.52 | 50.21 | 0.44 | 0.00 | 0.06 | 0.72 | 27-FEB-06:11 |
March | 0.611772E+11 | 0.00 | 475.39 | 389347.94 | 18-MAR-05:11 | 0.00 | 30.66 | 48.61 | 0.25 | 0.00 | 0.04 | 0.68 | 18-MAR-05:11 |
April | 0.239716E+11 | 0.00 | 342.71 | 465972.30 | 10-APR-05:11 | 0.00 | 26.85 | 41.46 | 0.08 | 0.00 | 0.02 | 0.82 | 10-APR-05:11 |
May | 0.156980E+11 | 0.00 | 252.65 | 386100.82 | 02-MAY-05:11 | 0.00 | 29.76 | 39.38 | 0.06 | 0.00 | 0.01 | 0.68 | 02-MAY-05:11 |
June | 0.193060E+10 | 0.00 | 101.00 | 181257.86 | 17-JUN-06:03 | 0.00 | 31.82 | 35.58 | 0.01 | 0.00 | 0.00 | 0.32 | 17-JUN-06:03 |
July | 0.235485E+09 | 0.00 | 48.67 | 50520.90 | 05-JUL-06:03 | 0.00 | 28.90 | 30.91 | 0.00 | 0.00 | 0.00 | 0.09 | 05-JUL-06:03 |
August | 0.972445E+09 | 0.00 | 51.24 | 145734.54 | 18-AUG-05:12 | 0.00 | 32.72 | 34.56 | 0.00 | 0.00 | 0.00 | 0.26 | 18-AUG-05:12 |
September | 0.562328E+10 | 0.00 | 172.62 | 296001.16 | 13-SEP-06:03 | 0.00 | 28.40 | 35.60 | 0.02 | 0.00 | 0.00 | 0.52 | 13-SEP-06:03 |
October | 0.171285E+11 | 0.00 | 308.67 | 324649.24 | 05-OCT-06:02 | 0.00 | 25.34 | 38.68 | 0.06 | 0.00 | 0.01 | 0.57 | 05-OCT-06:02 |
November | 0.504539E+11 | 0.00 | 437.93 | 371622.52 | 15-NOV-06:11 | 0.00 | 29.97 | 47.58 | 0.20 | 0.00 | 0.03 | 0.65 | 15-NOV-06:11 |
December | 0.110879E+12 | 0.00 | 559.91 | 379701.93 | 06-DEC-06:11 | 0.00 | 35.06 | 53.21 | 0.51 | 0.00 | 0.07 | 0.67 | 06-DEC-06:11 |
Annual Sum or Average | 0.541810E+12 | 0.00 | 3796.72 | 0.00 | 30.91 | 42.53 | 0.21 | 0.00 | 0.03 | ||||
Minimum of Months | 0.235485E+09 | 0.00 | 48.67 | 50520.90 | 0.00 | 25.34 | 30.91 | 0.00 | 0.00 | 0.00 | 0.09 | ||
Maximum of Months | 0.165921E+12 | 0.00 | 600.99 | 465972.30 | 0.00 | 37.90 | 55.04 | 0.86 | 0.00 | 0.11 | 0.82 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.223454E+09 | 59318073.16 | 9.73 | 0.223454E+09 | 0.00 | 0.00 | 0.48 | 27-FEB-15:30 | 0.00 | 01-FEB-00:10 | 16069.94 | 27-FEB-15:30 | 16069.94 | 27-FEB-15:30 | 0.00 | 26-FEB-13:04 | 4110.27 | 27-FEB-15:30 | 0.00 |
March | 6325454.30 | 1803691.99 | 1.67 | 6320037.50 | 5416.80 | 0.00 | 0.04 | 14-MAR-14:00 | 0.00 | 01-MAR-00:10 | 1273.16 | 14-MAR-14:00 | 1265.97 | 14-MAR-14:00 | 7.19 | 14-MAR-14:00 | 362.67 | 14-MAR-14:00 | 0.00 |
April | 0.242851E+10 | 0.622386E+09 | 62.33 | 0.241780E+10 | 10710530.30 | 0.00 | 0.88 | 07-APR-14:10 | 0.00 | 01-APR-00:10 | 32731.05 | 07-APR-14:10 | 32731.05 | 07-APR-14:10 | 544.76 | 24-APR-11:15 | 7508.54 | 07-APR-14:10 | 0.00 |
May | 0.893109E+10 | 0.222069E+10 | 147.09 | 0.873704E+10 | 0.194053E+09 | 0.00 | 1.00 | 19-MAY-12:05 | 0.00 | 01-MAY-00:10 | 52514.49 | 19-MAY-15:40 | 52514.49 | 19-MAY-15:40 | 6874.09 | 02-MAY-13:00 | 12941.45 | 19-MAY-15:30 | 0.00 |
June | 0.304348E+11 | 0.742234E+10 | 297.79 | 0.291879E+11 | 0.124694E+10 | 0.00 | 1.00 | 05-JUN-13:30 | 0.00 | 01-JUN-00:10 | 66876.25 | 29-JUN-15:00 | 66876.25 | 29-JUN-15:00 | 7919.57 | 20-JUN-15:50 | 18533.19 | 29-JUN-15:00 | 0.00 |
July | 0.532080E+11 | 0.133311E+11 | 390.86 | 0.515495E+11 | 0.165857E+10 | 0.00 | 1.00 | 01-JUL-10:05 | 0.00 | 01-JUL-00:10 | 83652.89 | 17-JUL-16:00 | 83652.89 | 17-JUL-16:00 | 27689.12 | 19-JUL-05:12 | 26978.18 | 17-JUL-16:00 | 0.00 |
August | 0.460610E+11 | 0.114553E+11 | 362.22 | 0.456761E+11 | 0.384911E+09 | 0.00 | 1.00 | 01-AUG-11:50 | 0.00 | 01-AUG-00:10 | 80478.45 | 10-AUG-15:00 | 80478.45 | 10-AUG-15:00 | 5702.56 | 22-AUG-15:30 | 23452.17 | 10-AUG-15:00 | 0.00 |
September | 0.225851E+11 | 0.554042E+10 | 237.48 | 0.209037E+11 | 0.168133E+10 | 0.00 | 1.00 | 01-SEP-09:30 | 0.00 | 01-SEP-00:10 | 105084.17 | 07-SEP-14:50 | 68892.57 | 01-SEP-15:40 | 52594.55 | 07-SEP-14:50 | 23367.69 | 07-SEP-14:50 | 0.00 |
October | 0.523879E+10 | 0.128600E+10 | 97.95 | 0.522901E+10 | 9783363.30 | 0.00 | 1.00 | 18-OCT-12:05 | 0.00 | 01-OCT-00:10 | 53276.74 | 18-OCT-15:30 | 53276.74 | 18-OCT-15:30 | 487.87 | 13-OCT-10:00 | 12106.63 | 18-OCT-15:00 | 0.00 |
November | 0.308908E+09 | 85152356.05 | 21.83 | 0.307370E+09 | 1537826.41 | 0.00 | 0.31 | 17-NOV-17:00 | 0.00 | 01-NOV-00:10 | 9923.34 | 17-NOV-17:00 | 9923.34 | 17-NOV-17:00 | 147.81 | 17-NOV-18:10 | 2650.55 | 17-NOV-17:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.169426E+12 | 0.420245E+11 | 1628.96 | 0.164238E+12 | 0.518784E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.532080E+11 | 0.133311E+11 | 390.86 | 0.515495E+11 | 0.168133E+10 | 0.00 | 1.00 | 0.00 | 105084.17 | 83652.89 | 52594.55 | 26978.18 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.223837E+09 | 60017831.35 | 11.17 | 0.223837E+09 | 0.00 | 0.00 | 0.44 | 27-FEB-15:02 | 0.00 | 01-FEB-00:10 | 14327.12 | 27-FEB-15:02 | 14327.12 | 27-FEB-15:02 | 0.00 | 27-FEB-11:50 | 3705.07 | 27-FEB-15:02 | 0.00 |
March | 7531202.98 | 2146125.04 | 1.89 | 7516521.76 | 14681.22 | 0.00 | 0.06 | 14-MAR-13:00 | 0.00 | 01-MAR-00:10 | 1626.33 | 14-MAR-13:00 | 1626.33 | 14-MAR-13:00 | 17.35 | 14-MAR-14:00 | 461.96 | 14-MAR-13:00 | 0.00 |
April | 0.237975E+10 | 0.615685E+09 | 66.07 | 0.236786E+10 | 11894526.79 | 0.00 | 0.84 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 30410.81 | 06-APR-16:00 | 30410.81 | 06-APR-16:00 | 563.14 | 24-APR-11:02 | 7063.21 | 06-APR-16:00 | 0.00 |
May | 0.854702E+10 | 0.213694E+10 | 150.60 | 0.832343E+10 | 0.223589E+09 | 0.00 | 1.00 | 19-MAY-12:05 | 0.00 | 01-MAY-00:10 | 54471.96 | 19-MAY-15:30 | 54471.96 | 19-MAY-15:30 | 6871.23 | 02-MAY-13:00 | 13428.51 | 19-MAY-15:30 | 0.00 |
June | 0.293611E+11 | 0.720555E+10 | 310.62 | 0.279879E+11 | 0.137323E+10 | 0.00 | 1.00 | 05-JUN-13:50 | 0.00 | 01-JUN-00:10 | 66919.31 | 21-JUN-14:05 | 66577.06 | 29-JUN-14:50 | 7733.95 | 20-JUN-16:00 | 18447.45 | 29-JUN-15:00 | 0.00 |
July | 0.492507E+11 | 0.124326E+11 | 398.36 | 0.475543E+11 | 0.169641E+10 | 0.00 | 1.00 | 02-JUL-17:12 | 0.00 | 01-JUL-00:10 | 80818.30 | 17-JUL-16:00 | 80818.30 | 17-JUL-16:00 | 13517.65 | 18-JUL-21:00 | 26066.33 | 17-JUL-16:00 | 0.00 |
August | 0.416227E+11 | 0.104331E+11 | 364.67 | 0.411428E+11 | 0.479876E+09 | 0.00 | 1.00 | 01-AUG-12:00 | 0.00 | 01-AUG-00:10 | 76713.92 | 09-AUG-14:05 | 76713.92 | 09-AUG-14:05 | 5336.74 | 22-AUG-15:30 | 22290.52 | 09-AUG-14:05 | 0.00 |
September | 0.197286E+11 | 0.489216E+10 | 233.63 | 0.181659E+11 | 0.156270E+10 | 0.00 | 1.00 | 01-SEP-09:50 | 0.00 | 01-SEP-00:10 | 96649.63 | 07-SEP-14:50 | 65983.93 | 04-SEP-16:31 | 48269.74 | 07-SEP-14:50 | 21498.27 | 07-SEP-14:50 | 0.00 |
October | 0.432026E+10 | 0.108117E+10 | 97.38 | 0.430142E+10 | 18836955.32 | 0.00 | 1.00 | 15-OCT-13:52 | 0.00 | 01-OCT-00:10 | 45156.16 | 18-OCT-15:00 | 45156.16 | 18-OCT-15:00 | 553.96 | 28-OCT-11:10 | 10302.22 | 18-OCT-15:00 | 0.00 |
November | 0.247631E+09 | 68643886.85 | 19.67 | 0.241880E+09 | 5750813.95 | 0.00 | 0.24 | 04-NOV-14:02 | 0.00 | 01-NOV-00:10 | 7458.30 | 04-NOV-14:02 | 7458.30 | 04-NOV-14:02 | 283.72 | 17-NOV-15:00 | 2026.95 | 04-NOV-14:02 | 0.00 |
December | 60900.91 | 17436.19 | 0.03 | 60900.91 | 0.00 | 0.00 | 0.02 | 08-DEC-07:03 | 0.00 | 01-DEC-00:10 | 609.01 | 08-DEC-07:03 | 609.01 | 08-DEC-07:03 | 0.00 | 08-DEC-07:03 | 174.36 | 08-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.155689E+12 | 0.389281E+11 | 1654.09 | 0.150317E+12 | 0.537231E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.492507E+11 | 0.124326E+11 | 398.36 | 0.475543E+11 | 0.169641E+10 | 0.00 | 1.00 | 0.00 | 96649.63 | 80818.30 | 48269.74 | 26066.33 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3800884.94 | 1088862.33 | 1.63 | 3783838.64 | 17046.30 | 0.00 | 0.04 | 31-JAN-06:06 | 0.00 | 01-JAN-00:05 | 1746.08 | 31-JAN-06:06 | 1746.08 | 31-JAN-06:06 | 35.74 | 13-JAN-05:05 | 497.84 | 31-JAN-06:06 | 0.00 |
February | 0.234801E+09 | 63980873.36 | 11.36 | 0.234722E+09 | 78390.55 | 0.00 | 0.32 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 15362.53 | 27-FEB-15:00 | 15362.53 | 27-FEB-15:00 | 57.70 | 08-FEB-05:43 | 4096.56 | 27-FEB-15:00 | 0.00 |
March | 8008314.61 | 2289910.80 | 2.15 | 7734315.43 | 273999.18 | 0.00 | 0.05 | 06-MAR-06:30 | 0.00 | 01-MAR-00:10 | 2271.85 | 06-MAR-06:30 | 2271.85 | 06-MAR-06:30 | 87.55 | 22-MAR-04:50 | 646.02 | 06-MAR-06:30 | 0.00 |
April | 0.265678E+10 | 0.706782E+09 | 63.57 | 0.262084E+10 | 35937853.15 | 0.00 | 0.63 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 32632.36 | 06-APR-16:00 | 32632.36 | 06-APR-16:00 | 1016.71 | 22-APR-15:00 | 8041.41 | 06-APR-16:00 | 0.00 |
May | 0.104091E+11 | 0.266189E+10 | 147.63 | 0.989188E+10 | 0.517232E+09 | 0.00 | 1.00 | 19-MAY-13:10 | 0.00 | 01-MAY-00:10 | 69373.04 | 19-MAY-15:30 | 69373.04 | 19-MAY-15:30 | 9059.55 | 02-MAY-13:00 | 17140.62 | 19-MAY-15:20 | 0.00 |
June | 0.351534E+11 | 0.881337E+10 | 306.48 | 0.330094E+11 | 0.214399E+10 | 0.00 | 1.00 | 06-JUN-14:30 | 0.00 | 01-JUN-00:10 | 81278.63 | 29-JUN-15:00 | 81278.63 | 29-JUN-15:00 | 11140.70 | 22-JUN-19:40 | 22537.32 | 29-JUN-15:00 | 0.00 |
July | 0.585319E+11 | 0.150970E+11 | 394.53 | 0.557526E+11 | 0.277929E+10 | 0.00 | 1.00 | 02-JUL-17:32 | 0.00 | 01-JUL-00:10 | 98770.45 | 17-JUL-16:00 | 98770.45 | 17-JUL-16:00 | 17328.30 | 18-JUL-20:40 | 31880.07 | 17-JUL-16:00 | 0.00 |
August | 0.478083E+11 | 0.123001E+11 | 360.21 | 0.465520E+11 | 0.125624E+10 | 0.00 | 1.00 | 03-AUG-14:00 | 0.00 | 01-AUG-00:10 | 90993.09 | 07-AUG-14:40 | 90993.09 | 07-AUG-14:40 | 7670.36 | 22-AUG-15:20 | 26374.15 | 10-AUG-15:00 | 0.00 |
September | 0.225122E+11 | 0.575674E+10 | 228.59 | 0.203780E+11 | 0.213425E+10 | 0.00 | 1.00 | 01-SEP-12:00 | 0.00 | 01-SEP-00:10 | 94684.76 | 03-SEP-15:21 | 94684.76 | 03-SEP-15:21 | 46397.32 | 07-SEP-14:50 | 27118.73 | 03-SEP-15:21 | 0.00 |
October | 0.456480E+10 | 0.118391E+10 | 91.41 | 0.448799E+10 | 76804917.70 | 0.00 | 0.89 | 18-OCT-15:00 | 0.00 | 01-OCT-00:10 | 49385.67 | 18-OCT-15:00 | 49385.67 | 18-OCT-15:00 | 1121.29 | 28-OCT-11:50 | 11652.08 | 18-OCT-15:00 | 0.00 |
November | 0.299608E+09 | 83597734.92 | 18.64 | 0.277889E+09 | 21719721.49 | 0.00 | 0.19 | 17-NOV-17:00 | 0.00 | 01-NOV-00:10 | 8901.28 | 17-NOV-17:00 | 8104.02 | 17-NOV-17:00 | 797.26 | 17-NOV-17:00 | 2448.84 | 17-NOV-17:00 | 0.00 |
December | 3948027.02 | 1131653.54 | 1.74 | 3921151.18 | 26875.84 | 0.00 | 0.02 | 23-DEC-06:06 | 0.00 | 01-DEC-00:10 | 1038.29 | 23-DEC-06:06 | 1038.29 | 23-DEC-06:06 | 66.45 | 20-DEC-05:55 | 297.10 | 23-DEC-06:06 | 0.00 |
Annual Sum or Average | 0.182187E+12 | 0.466719E+11 | 1627.93 | 0.173221E+12 | 0.896586E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 3800884.94 | 1088862.33 | 1.63 | 3783838.64 | 17046.30 | 0.00 | 0.02 | 0.00 | 1038.29 | 1038.29 | 35.74 | 297.10 | 0.00 | ||||||
Maximum of Months | 0.585319E+11 | 0.150970E+11 | 394.53 | 0.557526E+11 | 0.277929E+10 | 0.00 | 1.00 | 0.00 | 98770.45 | 98770.45 | 46397.32 | 31880.07 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 308.35 | 0.00 | 308.35 | 2.63 | 3794.67 | 0.00 | 0.00 | 0.00 |
February | 435.37 | 0.00 | 435.37 | 38.81 | 2796.34 | 0.00 | 0.00 | 0.00 |
March | 707.24 | 0.00 | 707.24 | 130.16 | 2219.08 | 0.00 | 0.00 | 0.00 |
April | 806.40 | 4.71 | 801.70 | 317.22 | 1519.84 | 0.00 | 0.00 | 0.00 |
May | 1059.00 | 62.75 | 996.25 | 665.08 | 1127.78 | 0.00 | 0.00 | 0.00 |
June | 1233.14 | 141.74 | 1091.41 | 1177.59 | 716.01 | 0.00 | 0.00 | 0.00 |
July | 1126.55 | 105.51 | 1021.03 | 1365.25 | 583.30 | 0.00 | 0.00 | 0.00 |
August | 902.71 | 24.20 | 878.51 | 982.14 | 670.81 | 0.00 | 0.00 | 0.00 |
September | 676.06 | 0.24 | 675.82 | 555.58 | 1016.93 | 0.00 | 0.00 | 0.00 |
October | 493.15 | 0.00 | 493.15 | 171.92 | 1507.60 | 0.00 | 0.00 | 0.00 |
November | 335.25 | 0.00 | 335.25 | 31.27 | 2259.36 | 0.00 | 0.00 | 0.00 |
December | 258.57 | 0.00 | 258.57 | 0.76 | 3189.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 696.54 | 28.40 | 668.14 | 455.87 | 1779.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.57 | 0.00 | 258.57 | 0.76 | 583.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1233.14 | 141.74 | 1091.41 | 1365.25 | 3794.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 472.03 | 216.40 | 255.62 | 193.02 | 2312.43 | 0.00 | 0.00 | 0.00 |
February | 738.29 | 366.54 | 371.75 | 480.03 | 1695.80 | 0.00 | 0.00 | 0.00 |
March | 992.70 | 410.75 | 581.95 | 696.53 | 1366.00 | 0.00 | 0.00 | 0.00 |
April | 1266.59 | 627.71 | 638.88 | 1126.01 | 955.58 | 0.00 | 0.00 | 0.00 |
May | 1399.11 | 622.51 | 776.60 | 1356.93 | 750.15 | 0.00 | 0.00 | 0.00 |
June | 1810.97 | 931.92 | 879.05 | 2104.07 | 495.48 | 0.00 | 0.00 | 0.00 |
July | 1900.66 | 1074.49 | 826.17 | 2446.28 | 394.52 | 0.00 | 0.00 | 0.00 |
August | 1651.76 | 920.30 | 731.45 | 2060.40 | 444.58 | 0.00 | 0.00 | 0.00 |
September | 1168.46 | 603.15 | 565.31 | 1291.10 | 638.50 | 0.00 | 0.00 | 0.00 |
October | 838.31 | 425.68 | 412.63 | 731.12 | 930.64 | 0.00 | 0.00 | 0.00 |
November | 531.30 | 248.05 | 283.26 | 312.67 | 1362.02 | 0.00 | 0.00 | 0.00 |
December | 391.87 | 168.31 | 223.56 | 144.47 | 1944.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1098.71 | 552.27 | 546.44 | 1082.05 | 1105.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.87 | 168.31 | 223.56 | 144.47 | 394.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1900.66 | 1074.49 | 879.05 | 2446.28 | 2312.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2173.46 | 1552.33 | 621.14 | 1795.54 | 3187.81 | 0.00 | 0.00 | 0.00 |
February | 2767.88 | 1990.76 | 777.12 | 2602.79 | 2353.00 | 0.00 | 0.00 | 0.00 |
March | 2474.12 | 1389.35 | 1084.77 | 2306.55 | 2098.96 | 0.00 | 0.00 | 0.00 |
April | 1988.78 | 951.24 | 1037.54 | 1970.06 | 1541.85 | 0.00 | 0.00 | 0.00 |
May | 1766.99 | 586.86 | 1180.13 | 1778.65 | 1226.23 | 0.00 | 0.00 | 0.00 |
June | 1755.68 | 512.04 | 1243.65 | 2104.33 | 847.20 | 0.00 | 0.00 | 0.00 |
July | 1892.80 | 699.19 | 1193.61 | 2625.24 | 654.86 | 0.00 | 0.00 | 0.00 |
August | 2249.46 | 1134.13 | 1115.33 | 3009.86 | 737.42 | 0.00 | 0.00 | 0.00 |
September | 2494.92 | 1528.71 | 966.21 | 3032.63 | 1039.74 | 0.00 | 0.00 | 0.00 |
October | 2608.30 | 1803.60 | 804.70 | 2835.97 | 1442.35 | 0.00 | 0.00 | 0.00 |
November | 2378.00 | 1722.52 | 655.47 | 2286.80 | 1916.61 | 0.00 | 0.00 | 0.00 |
December | 2066.84 | 1492.47 | 574.38 | 1771.54 | 2668.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2214.28 | 1275.54 | 938.74 | 2341.14 | 1640.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1755.68 | 512.04 | 574.38 | 1771.54 | 654.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2767.88 | 1990.76 | 1243.65 | 3032.63 | 3187.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 427.56 | 172.31 | 255.25 | 171.58 | 2433.20 | 0.00 | 0.00 | 0.00 |
February | 729.77 | 358.72 | 371.05 | 482.15 | 1746.25 | 0.00 | 0.00 | 0.00 |
March | 933.93 | 342.21 | 591.73 | 632.91 | 1451.64 | 0.00 | 0.00 | 0.00 |
April | 1219.26 | 540.18 | 679.07 | 1094.29 | 1017.47 | 0.00 | 0.00 | 0.00 |
May | 1508.13 | 687.79 | 820.35 | 1523.64 | 808.78 | 0.00 | 0.00 | 0.00 |
June | 1640.79 | 753.67 | 887.12 | 1922.95 | 556.01 | 0.00 | 0.00 | 0.00 |
July | 1680.81 | 849.33 | 831.48 | 2208.37 | 452.34 | 0.00 | 0.00 | 0.00 |
August | 1427.23 | 700.45 | 726.78 | 1810.67 | 489.38 | 0.00 | 0.00 | 0.00 |
September | 1148.12 | 580.44 | 567.68 | 1304.10 | 699.32 | 0.00 | 0.00 | 0.00 |
October | 820.59 | 407.70 | 412.88 | 741.71 | 998.61 | 0.00 | 0.00 | 0.00 |
November | 580.90 | 288.17 | 292.72 | 399.66 | 1429.53 | 0.00 | 0.00 | 0.00 |
December | 390.47 | 164.81 | 225.66 | 161.42 | 2018.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1043.71 | 487.62 | 556.10 | 1040.79 | 1173.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 390.47 | 164.81 | 225.66 | 161.42 | 452.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1680.81 | 849.33 | 887.12 | 2208.37 | 2433.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.78 | 0.00 | 102.78 | 0.47 | 1270.37 | 0.00 | 0.00 | 0.00 |
February | 145.12 | 0.00 | 145.12 | 12.53 | 939.02 | 0.00 | 0.00 | 0.00 |
March | 235.74 | 0.00 | 235.74 | 49.69 | 740.37 | 0.00 | 0.00 | 0.00 |
April | 268.79 | 1.57 | 267.22 | 121.74 | 499.52 | 0.00 | 0.00 | 0.00 |
May | 352.99 | 20.92 | 332.07 | 244.25 | 373.15 | 0.00 | 0.00 | 0.00 |
June | 411.03 | 47.24 | 363.79 | 414.03 | 233.15 | 0.00 | 0.00 | 0.00 |
July | 375.50 | 35.17 | 340.33 | 466.55 | 193.82 | 0.00 | 0.00 | 0.00 |
August | 300.89 | 8.07 | 292.83 | 335.41 | 228.62 | 0.00 | 0.00 | 0.00 |
September | 225.35 | 0.08 | 225.27 | 185.70 | 361.43 | 0.00 | 0.00 | 0.00 |
October | 164.38 | 0.00 | 164.38 | 52.28 | 551.53 | 0.00 | 0.00 | 0.00 |
November | 111.75 | 0.00 | 111.75 | 8.53 | 805.20 | 0.00 | 0.00 | 0.00 |
December | 86.19 | 0.00 | 86.19 | 0.28 | 1096.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.17 | 9.47 | 222.71 | 158.54 | 606.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.19 | 0.00 | 86.19 | 0.28 | 193.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.03 | 47.24 | 363.79 | 466.55 | 1270.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.78 | 0.00 | 102.78 | 0.47 | 1270.45 | 0.00 | 0.00 | 0.00 |
February | 145.12 | 0.00 | 145.12 | 12.53 | 939.08 | 0.00 | 0.00 | 0.00 |
March | 235.75 | 0.00 | 235.75 | 49.69 | 740.42 | 0.00 | 0.00 | 0.00 |
April | 268.80 | 1.57 | 267.23 | 121.74 | 499.55 | 0.00 | 0.00 | 0.00 |
May | 353.00 | 20.92 | 332.09 | 244.26 | 373.18 | 0.00 | 0.00 | 0.00 |
June | 411.05 | 47.25 | 363.81 | 414.05 | 233.16 | 0.00 | 0.00 | 0.00 |
July | 375.52 | 35.17 | 340.35 | 466.57 | 193.83 | 0.00 | 0.00 | 0.00 |
August | 300.91 | 8.07 | 292.84 | 335.43 | 228.63 | 0.00 | 0.00 | 0.00 |
September | 225.36 | 0.08 | 225.28 | 185.70 | 361.45 | 0.00 | 0.00 | 0.00 |
October | 164.38 | 0.00 | 164.38 | 52.28 | 551.56 | 0.00 | 0.00 | 0.00 |
November | 111.75 | 0.00 | 111.75 | 8.53 | 805.25 | 0.00 | 0.00 | 0.00 |
December | 86.19 | 0.00 | 86.19 | 0.28 | 1096.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.18 | 9.47 | 222.72 | 158.55 | 606.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.19 | 0.00 | 86.19 | 0.28 | 193.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.05 | 47.25 | 363.81 | 466.57 | 1270.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.78 | 0.00 | 102.78 | 0.47 | 1270.45 | 0.00 | 0.00 | 0.00 |
February | 145.12 | 0.00 | 145.12 | 12.53 | 939.08 | 0.00 | 0.00 | 0.00 |
March | 235.75 | 0.00 | 235.75 | 49.69 | 740.42 | 0.00 | 0.00 | 0.00 |
April | 268.80 | 1.57 | 267.23 | 121.74 | 499.55 | 0.00 | 0.00 | 0.00 |
May | 353.00 | 20.92 | 332.09 | 244.26 | 373.18 | 0.00 | 0.00 | 0.00 |
June | 411.05 | 47.25 | 363.81 | 414.05 | 233.16 | 0.00 | 0.00 | 0.00 |
July | 375.52 | 35.17 | 340.35 | 466.57 | 193.83 | 0.00 | 0.00 | 0.00 |
August | 300.91 | 8.07 | 292.84 | 335.43 | 228.63 | 0.00 | 0.00 | 0.00 |
September | 225.36 | 0.08 | 225.28 | 185.70 | 361.45 | 0.00 | 0.00 | 0.00 |
October | 164.38 | 0.00 | 164.38 | 52.28 | 551.56 | 0.00 | 0.00 | 0.00 |
November | 111.75 | 0.00 | 111.75 | 8.53 | 805.25 | 0.00 | 0.00 | 0.00 |
December | 86.19 | 0.00 | 86.19 | 0.28 | 1096.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.18 | 9.47 | 222.72 | 158.55 | 606.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.19 | 0.00 | 86.19 | 0.28 | 193.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 411.05 | 47.25 | 363.81 | 466.57 | 1270.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 454.09 | 208.18 | 245.91 | 186.67 | 2244.66 | 0.00 | 0.00 | 0.00 |
February | 710.23 | 352.61 | 357.62 | 464.83 | 1655.45 | 0.00 | 0.00 | 0.00 |
March | 954.97 | 395.14 | 559.83 | 689.21 | 1332.68 | 0.00 | 0.00 | 0.00 |
April | 1218.45 | 603.86 | 614.60 | 1119.25 | 925.98 | 0.00 | 0.00 | 0.00 |
May | 1345.94 | 598.86 | 747.08 | 1343.83 | 734.44 | 0.00 | 0.00 | 0.00 |
June | 1742.15 | 896.51 | 845.64 | 2051.92 | 487.55 | 0.00 | 0.00 | 0.00 |
July | 1828.43 | 1033.66 | 794.77 | 2369.89 | 402.15 | 0.00 | 0.00 | 0.00 |
August | 1588.99 | 885.33 | 703.65 | 1992.55 | 460.02 | 0.00 | 0.00 | 0.00 |
September | 1124.05 | 580.23 | 543.82 | 1236.78 | 678.94 | 0.00 | 0.00 | 0.00 |
October | 806.45 | 409.50 | 396.95 | 682.96 | 1004.28 | 0.00 | 0.00 | 0.00 |
November | 511.11 | 238.62 | 272.49 | 286.83 | 1414.89 | 0.00 | 0.00 | 0.00 |
December | 376.97 | 161.91 | 215.06 | 136.77 | 1938.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1056.96 | 531.29 | 525.67 | 1050.18 | 1104.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.97 | 161.91 | 215.06 | 136.77 | 402.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1828.43 | 1033.66 | 845.64 | 2369.89 | 2244.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.95 | 8.23 | 9.72 | 7.38 | 88.75 | 0.00 | 0.00 | 0.00 |
February | 28.08 | 13.94 | 14.14 | 18.38 | 65.45 | 0.00 | 0.00 | 0.00 |
March | 37.76 | 15.62 | 22.14 | 27.25 | 52.69 | 0.00 | 0.00 | 0.00 |
April | 48.18 | 23.88 | 24.30 | 44.25 | 36.61 | 0.00 | 0.00 | 0.00 |
May | 53.22 | 23.68 | 29.54 | 53.13 | 29.04 | 0.00 | 0.00 | 0.00 |
June | 68.88 | 35.45 | 33.44 | 81.13 | 19.28 | 0.00 | 0.00 | 0.00 |
July | 72.29 | 40.87 | 31.42 | 93.70 | 15.90 | 0.00 | 0.00 | 0.00 |
August | 62.83 | 35.01 | 27.82 | 78.78 | 18.19 | 0.00 | 0.00 | 0.00 |
September | 44.44 | 22.94 | 21.50 | 48.90 | 26.84 | 0.00 | 0.00 | 0.00 |
October | 31.89 | 16.19 | 15.69 | 27.00 | 39.71 | 0.00 | 0.00 | 0.00 |
November | 20.21 | 9.43 | 10.77 | 11.34 | 55.94 | 0.00 | 0.00 | 0.00 |
December | 14.91 | 6.40 | 8.50 | 5.41 | 76.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.79 | 21.01 | 20.78 | 41.52 | 43.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.91 | 6.40 | 8.50 | 5.41 | 15.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.29 | 40.87 | 33.44 | 93.70 | 88.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 724.51 | 517.46 | 207.05 | 612.25 | 1063.33 | 0.00 | 0.00 | 0.00 |
February | 922.65 | 663.60 | 259.05 | 886.10 | 808.30 | 0.00 | 0.00 | 0.00 |
March | 824.73 | 463.13 | 361.60 | 792.19 | 716.67 | 0.00 | 0.00 | 0.00 |
April | 662.94 | 317.09 | 345.86 | 680.88 | 519.04 | 0.00 | 0.00 | 0.00 |
May | 589.01 | 195.63 | 393.38 | 619.45 | 411.76 | 0.00 | 0.00 | 0.00 |
June | 585.24 | 170.68 | 414.56 | 724.18 | 281.33 | 0.00 | 0.00 | 0.00 |
July | 630.95 | 233.07 | 397.88 | 887.50 | 227.04 | 0.00 | 0.00 | 0.00 |
August | 749.84 | 378.05 | 371.79 | 1012.91 | 264.35 | 0.00 | 0.00 | 0.00 |
September | 831.66 | 509.58 | 322.08 | 1015.95 | 389.31 | 0.00 | 0.00 | 0.00 |
October | 869.46 | 601.22 | 268.24 | 944.21 | 550.86 | 0.00 | 0.00 | 0.00 |
November | 792.69 | 574.19 | 218.50 | 759.30 | 701.23 | 0.00 | 0.00 | 0.00 |
December | 688.97 | 497.50 | 191.46 | 595.12 | 923.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.11 | 425.19 | 312.92 | 793.40 | 570.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 585.24 | 170.68 | 191.46 | 595.12 | 227.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 922.65 | 663.60 | 414.56 | 1015.95 | 1063.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 724.51 | 517.46 | 207.05 | 612.25 | 1063.33 | 0.00 | 0.00 | 0.00 |
February | 922.65 | 663.60 | 259.05 | 886.10 | 808.30 | 0.00 | 0.00 | 0.00 |
March | 824.73 | 463.13 | 361.60 | 792.19 | 716.67 | 0.00 | 0.00 | 0.00 |
April | 662.94 | 317.09 | 345.86 | 680.88 | 519.04 | 0.00 | 0.00 | 0.00 |
May | 589.01 | 195.63 | 393.38 | 619.45 | 411.76 | 0.00 | 0.00 | 0.00 |
June | 585.24 | 170.68 | 414.56 | 724.18 | 281.33 | 0.00 | 0.00 | 0.00 |
July | 630.95 | 233.07 | 397.88 | 887.50 | 227.04 | 0.00 | 0.00 | 0.00 |
August | 749.84 | 378.05 | 371.79 | 1012.91 | 264.35 | 0.00 | 0.00 | 0.00 |
September | 831.66 | 509.58 | 322.08 | 1015.95 | 389.31 | 0.00 | 0.00 | 0.00 |
October | 869.46 | 601.22 | 268.24 | 944.21 | 550.86 | 0.00 | 0.00 | 0.00 |
November | 792.69 | 574.19 | 218.50 | 759.30 | 701.23 | 0.00 | 0.00 | 0.00 |
December | 688.97 | 497.50 | 191.46 | 595.12 | 923.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.11 | 425.19 | 312.92 | 793.40 | 570.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 585.24 | 170.68 | 191.46 | 595.12 | 227.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 922.65 | 663.60 | 414.56 | 1015.95 | 1063.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 724.46 | 517.42 | 207.04 | 612.21 | 1063.26 | 0.00 | 0.00 | 0.00 |
February | 922.59 | 663.56 | 259.03 | 886.04 | 808.25 | 0.00 | 0.00 | 0.00 |
March | 824.68 | 463.10 | 361.58 | 792.13 | 716.62 | 0.00 | 0.00 | 0.00 |
April | 662.90 | 317.07 | 345.83 | 680.84 | 519.01 | 0.00 | 0.00 | 0.00 |
May | 588.97 | 195.61 | 393.36 | 619.41 | 411.73 | 0.00 | 0.00 | 0.00 |
June | 585.20 | 170.67 | 414.53 | 724.13 | 281.31 | 0.00 | 0.00 | 0.00 |
July | 630.91 | 233.05 | 397.85 | 887.44 | 227.03 | 0.00 | 0.00 | 0.00 |
August | 749.79 | 378.03 | 371.76 | 1012.85 | 264.33 | 0.00 | 0.00 | 0.00 |
September | 831.61 | 509.55 | 322.06 | 1015.89 | 389.28 | 0.00 | 0.00 | 0.00 |
October | 869.40 | 601.18 | 268.22 | 944.15 | 550.82 | 0.00 | 0.00 | 0.00 |
November | 792.64 | 574.15 | 218.48 | 759.25 | 701.19 | 0.00 | 0.00 | 0.00 |
December | 688.92 | 497.47 | 191.45 | 595.08 | 923.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 738.07 | 425.16 | 312.90 | 793.35 | 570.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 585.20 | 170.67 | 191.45 | 595.08 | 227.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 922.59 | 663.56 | 414.53 | 1015.89 | 1063.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.31 | 165.76 | 245.55 | 170.22 | 2351.00 | 0.00 | 0.00 | 0.00 |
February | 702.04 | 345.09 | 356.95 | 477.28 | 1707.81 | 0.00 | 0.00 | 0.00 |
March | 898.44 | 329.20 | 569.24 | 637.38 | 1410.29 | 0.00 | 0.00 | 0.00 |
April | 1172.92 | 519.66 | 653.26 | 1095.31 | 984.42 | 0.00 | 0.00 | 0.00 |
May | 1450.82 | 661.65 | 789.17 | 1510.77 | 795.23 | 0.00 | 0.00 | 0.00 |
June | 1578.43 | 725.03 | 853.40 | 1885.98 | 547.24 | 0.00 | 0.00 | 0.00 |
July | 1616.93 | 817.06 | 799.87 | 2142.31 | 459.91 | 0.00 | 0.00 | 0.00 |
August | 1372.99 | 673.83 | 699.16 | 1753.37 | 503.81 | 0.00 | 0.00 | 0.00 |
September | 1104.48 | 558.38 | 546.10 | 1257.45 | 740.39 | 0.00 | 0.00 | 0.00 |
October | 789.40 | 392.21 | 397.19 | 704.91 | 1073.04 | 0.00 | 0.00 | 0.00 |
November | 558.82 | 277.22 | 281.60 | 379.74 | 1482.38 | 0.00 | 0.00 | 0.00 |
December | 375.63 | 158.54 | 217.09 | 157.56 | 2006.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1004.05 | 469.09 | 534.96 | 1017.23 | 1169.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 375.63 | 158.54 | 217.09 | 157.56 | 459.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1616.93 | 817.06 | 853.40 | 2142.31 | 2351.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.26 | 6.55 | 9.71 | 6.73 | 92.96 | 0.00 | 0.00 | 0.00 |
February | 27.76 | 13.64 | 14.11 | 18.87 | 67.53 | 0.00 | 0.00 | 0.00 |
March | 35.52 | 13.02 | 22.51 | 25.20 | 55.76 | 0.00 | 0.00 | 0.00 |
April | 46.38 | 20.55 | 25.83 | 43.31 | 38.92 | 0.00 | 0.00 | 0.00 |
May | 57.36 | 26.16 | 31.20 | 59.73 | 31.44 | 0.00 | 0.00 | 0.00 |
June | 62.41 | 28.67 | 33.74 | 74.57 | 21.64 | 0.00 | 0.00 | 0.00 |
July | 63.93 | 32.31 | 31.63 | 84.70 | 18.18 | 0.00 | 0.00 | 0.00 |
August | 54.29 | 26.64 | 27.64 | 69.33 | 19.92 | 0.00 | 0.00 | 0.00 |
September | 43.67 | 22.08 | 21.59 | 49.72 | 29.27 | 0.00 | 0.00 | 0.00 |
October | 31.21 | 15.51 | 15.70 | 27.87 | 42.43 | 0.00 | 0.00 | 0.00 |
November | 22.10 | 10.96 | 11.13 | 15.01 | 58.61 | 0.00 | 0.00 | 0.00 |
December | 14.85 | 6.27 | 8.58 | 6.23 | 79.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.70 | 18.55 | 21.15 | 40.22 | 46.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.85 | 6.27 | 8.58 | 6.23 | 18.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.93 | 32.31 | 33.74 | 84.70 | 92.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 308.35 | 0.00 | 308.35 | 1.24 | 3889.66 | 0.00 | 0.00 | 0.00 |
February | 435.37 | 0.00 | 435.37 | 30.97 | 2913.88 | 0.00 | 0.00 | 0.00 |
March | 707.24 | 0.00 | 707.24 | 121.13 | 2338.68 | 0.00 | 0.00 | 0.00 |
April | 806.40 | 4.71 | 801.70 | 302.67 | 1632.35 | 0.00 | 0.00 | 0.00 |
May | 1059.00 | 62.75 | 996.25 | 646.09 | 1213.32 | 0.00 | 0.00 | 0.00 |
June | 1233.14 | 141.74 | 1091.41 | 1148.90 | 765.76 | 0.00 | 0.00 | 0.00 |
July | 1126.55 | 105.51 | 1021.03 | 1341.73 | 623.17 | 0.00 | 0.00 | 0.00 |
August | 902.71 | 24.20 | 878.51 | 959.27 | 730.16 | 0.00 | 0.00 | 0.00 |
September | 676.06 | 0.24 | 675.82 | 531.54 | 1110.76 | 0.00 | 0.00 | 0.00 |
October | 493.15 | 0.00 | 493.15 | 149.33 | 1649.44 | 0.00 | 0.00 | 0.00 |
November | 335.25 | 0.00 | 335.25 | 23.65 | 2412.71 | 0.00 | 0.00 | 0.00 |
December | 258.57 | 0.00 | 258.57 | 0.60 | 3314.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 696.54 | 28.40 | 668.14 | 440.74 | 1878.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.57 | 0.00 | 258.57 | 0.60 | 623.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1233.14 | 141.74 | 1091.41 | 1341.73 | 3889.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 472.03 | 216.40 | 255.62 | 187.28 | 2370.33 | 0.00 | 0.00 | 0.00 |
February | 738.29 | 366.54 | 371.75 | 463.39 | 1767.88 | 0.00 | 0.00 | 0.00 |
March | 992.70 | 410.75 | 581.95 | 674.94 | 1443.31 | 0.00 | 0.00 | 0.00 |
April | 1266.59 | 627.71 | 638.88 | 1102.33 | 1025.68 | 0.00 | 0.00 | 0.00 |
May | 1399.11 | 622.51 | 776.60 | 1337.50 | 803.45 | 0.00 | 0.00 | 0.00 |
June | 1810.97 | 931.92 | 879.05 | 2090.69 | 523.78 | 0.00 | 0.00 | 0.00 |
July | 1900.66 | 1074.49 | 826.17 | 2438.98 | 416.77 | 0.00 | 0.00 | 0.00 |
August | 1651.76 | 920.30 | 731.45 | 2049.99 | 475.62 | 0.00 | 0.00 | 0.00 |
September | 1168.46 | 603.15 | 565.31 | 1269.30 | 692.15 | 0.00 | 0.00 | 0.00 |
October | 838.31 | 425.68 | 412.63 | 697.12 | 1019.53 | 0.00 | 0.00 | 0.00 |
November | 531.30 | 248.05 | 283.26 | 291.85 | 1458.93 | 0.00 | 0.00 | 0.00 |
December | 391.87 | 168.31 | 223.56 | 137.94 | 2022.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1098.71 | 552.27 | 546.44 | 1065.31 | 1166.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.87 | 168.31 | 223.56 | 137.94 | 416.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1900.66 | 1074.49 | 879.05 | 2438.98 | 2370.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2173.46 | 1552.33 | 621.14 | 1775.77 | 3285.60 | 0.00 | 0.00 | 0.00 |
February | 2767.88 | 1990.76 | 777.12 | 2574.80 | 2469.53 | 0.00 | 0.00 | 0.00 |
March | 2474.12 | 1389.35 | 1084.77 | 2286.67 | 2218.93 | 0.00 | 0.00 | 0.00 |
April | 1988.78 | 951.24 | 1037.54 | 1949.63 | 1655.03 | 0.00 | 0.00 | 0.00 |
May | 1766.99 | 586.86 | 1180.13 | 1765.47 | 1316.78 | 0.00 | 0.00 | 0.00 |
June | 1755.68 | 512.04 | 1243.65 | 2093.59 | 907.14 | 0.00 | 0.00 | 0.00 |
July | 1892.80 | 699.19 | 1193.61 | 2616.96 | 703.23 | 0.00 | 0.00 | 0.00 |
August | 2249.46 | 1134.13 | 1115.33 | 3001.35 | 798.35 | 0.00 | 0.00 | 0.00 |
September | 2494.92 | 1528.71 | 966.21 | 3014.02 | 1131.31 | 0.00 | 0.00 | 0.00 |
October | 2608.30 | 1803.60 | 804.70 | 2800.16 | 1577.12 | 0.00 | 0.00 | 0.00 |
November | 2378.00 | 1722.52 | 655.47 | 2242.94 | 2057.96 | 0.00 | 0.00 | 0.00 |
December | 2066.84 | 1492.47 | 574.38 | 1742.60 | 2791.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2214.28 | 1275.54 | 938.74 | 2319.89 | 1740.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1755.68 | 512.04 | 574.38 | 1742.60 | 703.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2767.88 | 1990.76 | 1243.65 | 3014.02 | 3285.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 427.56 | 172.31 | 255.25 | 168.96 | 2493.72 | 0.00 | 0.00 | 0.00 |
February | 729.77 | 358.72 | 371.05 | 475.85 | 1824.02 | 0.00 | 0.00 | 0.00 |
March | 933.93 | 342.21 | 591.73 | 627.46 | 1529.89 | 0.00 | 0.00 | 0.00 |
April | 1219.26 | 540.18 | 679.07 | 1087.23 | 1089.54 | 0.00 | 0.00 | 0.00 |
May | 1508.13 | 687.79 | 820.35 | 1521.00 | 865.25 | 0.00 | 0.00 | 0.00 |
June | 1640.79 | 753.67 | 887.12 | 1921.74 | 591.03 | 0.00 | 0.00 | 0.00 |
July | 1680.81 | 849.33 | 831.48 | 2207.73 | 480.67 | 0.00 | 0.00 | 0.00 |
August | 1427.23 | 700.45 | 726.78 | 1806.82 | 525.19 | 0.00 | 0.00 | 0.00 |
September | 1148.12 | 580.44 | 567.68 | 1296.58 | 756.53 | 0.00 | 0.00 | 0.00 |
October | 820.59 | 407.70 | 412.88 | 727.01 | 1088.71 | 0.00 | 0.00 | 0.00 |
November | 580.90 | 288.17 | 292.72 | 388.19 | 1526.68 | 0.00 | 0.00 | 0.00 |
December | 390.47 | 164.81 | 225.66 | 157.59 | 2098.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1043.71 | 487.62 | 556.10 | 1035.21 | 1237.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 390.47 | 164.81 | 225.66 | 157.59 | 480.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1680.81 | 849.33 | 887.12 | 2207.73 | 2493.72 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.825882E+09 | 0.00 | 0.825882E+09 | 7057284.90 | 0.101636E+11 |
February | 0.105325E+10 | 0.00 | 0.105325E+10 | 93892908.39 | 0.676490E+10 |
March | 0.189427E+10 | 0.00 | 0.189427E+10 | 0.348612E+09 | 0.594360E+10 |
April | 0.209019E+10 | 12197831.14 | 0.207800E+10 | 0.822247E+09 | 0.393942E+10 |
May | 0.283642E+10 | 0.168075E+09 | 0.266835E+10 | 0.178136E+10 | 0.302065E+10 |
June | 0.319631E+10 | 0.367387E+09 | 0.282892E+10 | 0.305232E+10 | 0.185590E+10 |
July | 0.301734E+10 | 0.282608E+09 | 0.273473E+10 | 0.365669E+10 | 0.156230E+10 |
August | 0.241781E+10 | 64808205.07 | 0.235300E+10 | 0.263058E+10 | 0.179670E+10 |
September | 0.175236E+10 | 628838.05 | 0.175173E+10 | 0.144006E+10 | 0.263588E+10 |
October | 0.132085E+10 | 0.00 | 0.132085E+10 | 0.460461E+09 | 0.403796E+10 |
November | 0.868963E+09 | 0.00 | 0.868963E+09 | 81061136.07 | 0.585626E+10 |
December | 0.692548E+09 | 0.00 | 0.692548E+09 | 2025917.19 | 0.854285E+10 |
Annual Sum or Average | 0.219662E+11 | 0.895704E+09 | 0.210705E+11 | 0.143764E+11 | 0.561200E+11 |
Minimum of Months | 0.692548E+09 | 0.00 | 0.692548E+09 | 2025917.19 | 0.156230E+10 |
Maximum of Months | 0.319631E+10 | 0.367387E+09 | 0.282892E+10 | 0.365669E+10 | 0.101636E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126427E+10 | 0.579615E+09 | 0.684658E+09 | 0.516986E+09 | 0.619360E+10 |
February | 0.178607E+10 | 0.886738E+09 | 0.899334E+09 | 0.116128E+10 | 0.410248E+10 |
March | 0.265884E+10 | 0.110015E+10 | 0.155869E+10 | 0.186560E+10 | 0.365868E+10 |
April | 0.328299E+10 | 0.162702E+10 | 0.165597E+10 | 0.291862E+10 | 0.247686E+10 |
May | 0.374738E+10 | 0.166734E+10 | 0.208004E+10 | 0.363441E+10 | 0.200920E+10 |
June | 0.469402E+10 | 0.241553E+10 | 0.227850E+10 | 0.545375E+10 | 0.128428E+10 |
July | 0.509072E+10 | 0.287791E+10 | 0.221282E+10 | 0.655211E+10 | 0.105669E+10 |
August | 0.442407E+10 | 0.246494E+10 | 0.195913E+10 | 0.551858E+10 | 0.119077E+10 |
September | 0.302864E+10 | 0.156336E+10 | 0.146527E+10 | 0.334653E+10 | 0.165500E+10 |
October | 0.224532E+10 | 0.114013E+10 | 0.110519E+10 | 0.195822E+10 | 0.249263E+10 |
November | 0.137713E+10 | 0.642938E+09 | 0.734197E+09 | 0.810452E+09 | 0.353036E+10 |
December | 0.104957E+10 | 0.450792E+09 | 0.598782E+09 | 0.386957E+09 | 0.520847E+10 |
Annual Sum or Average | 0.346490E+11 | 0.174165E+11 | 0.172326E+11 | 0.341235E+11 | 0.348590E+11 |
Minimum of Months | 0.104957E+10 | 0.450792E+09 | 0.598782E+09 | 0.386957E+09 | 0.105669E+10 |
Maximum of Months | 0.509072E+10 | 0.287791E+10 | 0.227850E+10 | 0.655211E+10 | 0.619360E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.582141E+10 | 0.415776E+10 | 0.166365E+10 | 0.480919E+10 | 0.853822E+10 |
February | 0.669604E+10 | 0.481604E+10 | 0.188001E+10 | 0.629668E+10 | 0.569237E+10 |
March | 0.662669E+10 | 0.372123E+10 | 0.290546E+10 | 0.617787E+10 | 0.562187E+10 |
April | 0.515493E+10 | 0.246562E+10 | 0.268930E+10 | 0.510640E+10 | 0.399648E+10 |
May | 0.473270E+10 | 0.157185E+10 | 0.316085E+10 | 0.476394E+10 | 0.328433E+10 |
June | 0.455073E+10 | 0.132720E+10 | 0.322353E+10 | 0.545441E+10 | 0.219594E+10 |
July | 0.506968E+10 | 0.187271E+10 | 0.319697E+10 | 0.703143E+10 | 0.175397E+10 |
August | 0.602496E+10 | 0.303766E+10 | 0.298730E+10 | 0.806161E+10 | 0.197512E+10 |
September | 0.646683E+10 | 0.396242E+10 | 0.250441E+10 | 0.786058E+10 | 0.269501E+10 |
October | 0.698608E+10 | 0.483077E+10 | 0.215531E+10 | 0.759585E+10 | 0.386319E+10 |
November | 0.616377E+10 | 0.446478E+10 | 0.169899E+10 | 0.592738E+10 | 0.496785E+10 |
December | 0.553583E+10 | 0.399742E+10 | 0.153841E+10 | 0.474488E+10 | 0.714703E+10 |
Annual Sum or Average | 0.698296E+11 | 0.402255E+11 | 0.296042E+11 | 0.738302E+11 | 0.517314E+11 |
Minimum of Months | 0.455073E+10 | 0.132720E+10 | 0.153841E+10 | 0.474488E+10 | 0.175397E+10 |
Maximum of Months | 0.698608E+10 | 0.483077E+10 | 0.322353E+10 | 0.806161E+10 | 0.853822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114517E+10 | 0.461509E+09 | 0.683658E+09 | 0.459553E+09 | 0.651707E+10 |
February | 0.176547E+10 | 0.867814E+09 | 0.897655E+09 | 0.116641E+10 | 0.422454E+10 |
March | 0.250145E+10 | 0.916564E+09 | 0.158488E+10 | 0.169519E+10 | 0.388806E+10 |
April | 0.316031E+10 | 0.140016E+10 | 0.176015E+10 | 0.283641E+10 | 0.263729E+10 |
May | 0.403938E+10 | 0.184216E+10 | 0.219722E+10 | 0.408091E+10 | 0.216624E+10 |
June | 0.425293E+10 | 0.195352E+10 | 0.229941E+10 | 0.498428E+10 | 0.144118E+10 |
July | 0.450187E+10 | 0.227485E+10 | 0.222702E+10 | 0.591489E+10 | 0.121154E+10 |
August | 0.382270E+10 | 0.187609E+10 | 0.194661E+10 | 0.484971E+10 | 0.131075E+10 |
September | 0.297592E+10 | 0.150450E+10 | 0.147142E+10 | 0.338022E+10 | 0.181264E+10 |
October | 0.219786E+10 | 0.109200E+10 | 0.110587E+10 | 0.198658E+10 | 0.267467E+10 |
November | 0.150569E+10 | 0.746947E+09 | 0.758742E+09 | 0.103593E+10 | 0.370534E+10 |
December | 0.104583E+10 | 0.441415E+09 | 0.604419E+09 | 0.432343E+09 | 0.540707E+10 |
Annual Sum or Average | 0.329146E+11 | 0.153775E+11 | 0.175371E+11 | 0.328224E+11 | 0.369964E+11 |
Minimum of Months | 0.104583E+10 | 0.441415E+09 | 0.604419E+09 | 0.432343E+09 | 0.121154E+10 |
Maximum of Months | 0.450187E+10 | 0.227485E+10 | 0.229941E+10 | 0.591489E+10 | 0.651707E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275284E+09 | 0.00 | 0.275284E+09 | 1247501.12 | 0.340256E+10 |
February | 0.351069E+09 | 0.00 | 0.351069E+09 | 30306150.06 | 0.227168E+10 |
March | 0.631399E+09 | 0.00 | 0.631399E+09 | 0.133100E+09 | 0.198300E+10 |
April | 0.696705E+09 | 4065815.53 | 0.692639E+09 | 0.315545E+09 | 0.129475E+10 |
May | 0.945438E+09 | 56023081.11 | 0.889415E+09 | 0.654187E+09 | 0.999448E+09 |
June | 0.106540E+10 | 0.122458E+09 | 0.942939E+09 | 0.107317E+10 | 0.604313E+09 |
July | 0.100574E+10 | 94199815.79 | 0.911542E+09 | 0.124960E+10 | 0.519132E+09 |
August | 0.805906E+09 | 21602053.95 | 0.784304E+09 | 0.898360E+09 | 0.612327E+09 |
September | 0.584098E+09 | 209606.08 | 0.583889E+09 | 0.481324E+09 | 0.936825E+09 |
October | 0.440268E+09 | 0.00 | 0.440268E+09 | 0.140030E+09 | 0.147722E+10 |
November | 0.289644E+09 | 0.00 | 0.289644E+09 | 22103855.37 | 0.208708E+10 |
December | 0.230841E+09 | 0.00 | 0.230841E+09 | 756989.13 | 0.293661E+10 |
Annual Sum or Average | 0.732179E+10 | 0.298559E+09 | 0.702323E+10 | 0.499973E+10 | 0.191250E+11 |
Minimum of Months | 0.230841E+09 | 0.00 | 0.230841E+09 | 756989.13 | 0.519132E+09 |
Maximum of Months | 0.106540E+10 | 0.122458E+09 | 0.942939E+09 | 0.124960E+10 | 0.340256E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275297E+09 | 0.00 | 0.275297E+09 | 1247399.08 | 0.340277E+10 |
February | 0.351085E+09 | 0.00 | 0.351085E+09 | 30306901.60 | 0.227183E+10 |
March | 0.631429E+09 | 0.00 | 0.631429E+09 | 0.133102E+09 | 0.198313E+10 |
April | 0.696738E+09 | 4065972.52 | 0.692672E+09 | 0.315556E+09 | 0.129484E+10 |
May | 0.945483E+09 | 56025244.34 | 0.889458E+09 | 0.654213E+09 | 0.999512E+09 |
June | 0.106545E+10 | 0.122463E+09 | 0.942985E+09 | 0.107321E+10 | 0.604350E+09 |
July | 0.100579E+10 | 94203453.16 | 0.911587E+09 | 0.124966E+10 | 0.519162E+09 |
August | 0.805946E+09 | 21602888.07 | 0.784343E+09 | 0.898405E+09 | 0.612364E+09 |
September | 0.584126E+09 | 209614.17 | 0.583917E+09 | 0.481347E+09 | 0.936882E+09 |
October | 0.440289E+09 | 0.00 | 0.440289E+09 | 0.140035E+09 | 0.147731E+10 |
November | 0.289657E+09 | 0.00 | 0.289657E+09 | 22103891.14 | 0.208721E+10 |
December | 0.230852E+09 | 0.00 | 0.230852E+09 | 756945.42 | 0.293680E+10 |
Annual Sum or Average | 0.732214E+10 | 0.298570E+09 | 0.702357E+10 | 0.499995E+10 | 0.191262E+11 |
Minimum of Months | 0.230852E+09 | 0.00 | 0.230852E+09 | 756945.42 | 0.519162E+09 |
Maximum of Months | 0.106545E+10 | 0.122463E+09 | 0.942985E+09 | 0.124966E+10 | 0.340277E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275297E+09 | 0.00 | 0.275297E+09 | 1247399.08 | 0.340277E+10 |
February | 0.351085E+09 | 0.00 | 0.351085E+09 | 30306901.60 | 0.227183E+10 |
March | 0.631429E+09 | 0.00 | 0.631429E+09 | 0.133102E+09 | 0.198313E+10 |
April | 0.696738E+09 | 4065972.52 | 0.692672E+09 | 0.315556E+09 | 0.129484E+10 |
May | 0.945483E+09 | 56025244.34 | 0.889458E+09 | 0.654213E+09 | 0.999512E+09 |
June | 0.106545E+10 | 0.122463E+09 | 0.942985E+09 | 0.107321E+10 | 0.604350E+09 |
July | 0.100579E+10 | 94203453.16 | 0.911587E+09 | 0.124966E+10 | 0.519162E+09 |
August | 0.805946E+09 | 21602888.07 | 0.784343E+09 | 0.898405E+09 | 0.612364E+09 |
September | 0.584126E+09 | 209614.17 | 0.583917E+09 | 0.481347E+09 | 0.936882E+09 |
October | 0.440289E+09 | 0.00 | 0.440289E+09 | 0.140035E+09 | 0.147731E+10 |
November | 0.289657E+09 | 0.00 | 0.289657E+09 | 22103891.14 | 0.208721E+10 |
December | 0.230852E+09 | 0.00 | 0.230852E+09 | 756945.42 | 0.293680E+10 |
Annual Sum or Average | 0.732214E+10 | 0.298570E+09 | 0.702357E+10 | 0.499995E+10 | 0.191262E+11 |
Minimum of Months | 0.230852E+09 | 0.00 | 0.230852E+09 | 756945.42 | 0.519162E+09 |
Maximum of Months | 0.106545E+10 | 0.122463E+09 | 0.942985E+09 | 0.124966E+10 | 0.340277E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121623E+10 | 0.557592E+09 | 0.658638E+09 | 0.499980E+09 | 0.601209E+10 |
February | 0.171820E+10 | 0.853045E+09 | 0.865154E+09 | 0.112451E+10 | 0.400486E+10 |
March | 0.255780E+10 | 0.105835E+10 | 0.149946E+10 | 0.184598E+10 | 0.356944E+10 |
April | 0.315823E+10 | 0.156520E+10 | 0.159304E+10 | 0.290111E+10 | 0.240013E+10 |
May | 0.360497E+10 | 0.160398E+10 | 0.200098E+10 | 0.359931E+10 | 0.196712E+10 |
June | 0.451564E+10 | 0.232375E+10 | 0.219190E+10 | 0.531858E+10 | 0.126372E+10 |
July | 0.489727E+10 | 0.276856E+10 | 0.212871E+10 | 0.634752E+10 | 0.107711E+10 |
August | 0.425595E+10 | 0.237128E+10 | 0.188466E+10 | 0.533685E+10 | 0.123211E+10 |
September | 0.291354E+10 | 0.150396E+10 | 0.140958E+10 | 0.320573E+10 | 0.175980E+10 |
October | 0.215999E+10 | 0.109681E+10 | 0.106318E+10 | 0.182924E+10 | 0.268987E+10 |
November | 0.132480E+10 | 0.618508E+09 | 0.706294E+09 | 0.743455E+09 | 0.366740E+10 |
December | 0.100969E+10 | 0.433664E+09 | 0.576025E+09 | 0.366319E+09 | 0.519160E+10 |
Annual Sum or Average | 0.333323E+11 | 0.167547E+11 | 0.165776E+11 | 0.331186E+11 | 0.348353E+11 |
Minimum of Months | 0.100969E+10 | 0.433664E+09 | 0.576025E+09 | 0.366319E+09 | 0.107711E+10 |
Maximum of Months | 0.489727E+10 | 0.276856E+10 | 0.219190E+10 | 0.634752E+10 | 0.601209E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48088628.59 | 22046689.15 | 26041939.44 | 19768740.06 | 0.237713E+09 |
February | 67936035.91 | 33728627.02 | 34207408.89 | 44462101.71 | 0.158348E+09 |
March | 0.101133E+09 | 41846118.05 | 59287139.70 | 72988274.59 | 0.141132E+09 |
April | 0.124874E+09 | 61886465.77 | 62987178.24 | 0.114707E+09 | 94898938.50 |
May | 0.142537E+09 | 63420109.69 | 79117066.44 | 0.142314E+09 | 77778277.28 |
June | 0.178544E+09 | 91878828.34 | 86665576.58 | 0.210292E+09 | 49966396.54 |
July | 0.193634E+09 | 0.109466E+09 | 84167353.17 | 0.250975E+09 | 42588083.22 |
August | 0.168276E+09 | 93758296.89 | 74517941.66 | 0.211014E+09 | 48716393.16 |
September | 0.115199E+09 | 59465255.31 | 55733685.68 | 0.126752E+09 | 69581065.72 |
October | 85404191.57 | 43366919.67 | 42037271.90 | 72326605.89 | 0.106355E+09 |
November | 52381479.05 | 24455264.14 | 27926214.91 | 29395521.59 | 0.145006E+09 |
December | 39922190.97 | 17146671.25 | 22775519.71 | 14483942.13 | 0.205271E+09 |
Annual Sum or Average | 0.131793E+10 | 0.662466E+09 | 0.655464E+09 | 0.130948E+10 | 0.137735E+10 |
Minimum of Months | 39922190.97 | 17146671.25 | 22775519.71 | 14483942.13 | 42588083.22 |
Maximum of Months | 0.193634E+09 | 0.109466E+09 | 86665576.58 | 0.250975E+09 | 0.237713E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194052E+10 | 0.138596E+10 | 0.554563E+09 | 0.163984E+10 | 0.284801E+10 |
February | 0.223207E+10 | 0.160539E+10 | 0.626685E+09 | 0.214365E+10 | 0.195544E+10 |
March | 0.220895E+10 | 0.124044E+10 | 0.968510E+09 | 0.212179E+10 | 0.191952E+10 |
April | 0.171835E+10 | 0.821896E+09 | 0.896457E+09 | 0.176485E+10 | 0.134535E+10 |
May | 0.157761E+10 | 0.523963E+09 | 0.105364E+10 | 0.165914E+10 | 0.110285E+10 |
June | 0.151695E+10 | 0.442411E+09 | 0.107453E+10 | 0.187706E+10 | 0.729209E+09 |
July | 0.168993E+10 | 0.624253E+09 | 0.106568E+10 | 0.237707E+10 | 0.608108E+09 |
August | 0.200837E+10 | 0.101258E+10 | 0.995791E+09 | 0.271299E+10 | 0.708038E+09 |
September | 0.215567E+10 | 0.132084E+10 | 0.834824E+09 | 0.263334E+10 | 0.100908E+10 |
October | 0.232875E+10 | 0.161030E+10 | 0.718453E+09 | 0.252897E+10 | 0.147542E+10 |
November | 0.205464E+10 | 0.148830E+10 | 0.566344E+09 | 0.196810E+10 | 0.181759E+10 |
December | 0.184533E+10 | 0.133251E+10 | 0.512815E+09 | 0.159396E+10 | 0.247313E+10 |
Annual Sum or Average | 0.232772E+11 | 0.134089E+11 | 0.986830E+10 | 0.250208E+11 | 0.179917E+11 |
Minimum of Months | 0.151695E+10 | 0.442411E+09 | 0.512815E+09 | 0.159396E+10 | 0.608108E+09 |
Maximum of Months | 0.232875E+10 | 0.161030E+10 | 0.107453E+10 | 0.271299E+10 | 0.284801E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194052E+10 | 0.138596E+10 | 0.554563E+09 | 0.163984E+10 | 0.284801E+10 |
February | 0.223207E+10 | 0.160539E+10 | 0.626685E+09 | 0.214365E+10 | 0.195544E+10 |
March | 0.220895E+10 | 0.124044E+10 | 0.968510E+09 | 0.212179E+10 | 0.191952E+10 |
April | 0.171835E+10 | 0.821896E+09 | 0.896457E+09 | 0.176485E+10 | 0.134535E+10 |
May | 0.157761E+10 | 0.523963E+09 | 0.105364E+10 | 0.165914E+10 | 0.110285E+10 |
June | 0.151695E+10 | 0.442411E+09 | 0.107453E+10 | 0.187706E+10 | 0.729209E+09 |
July | 0.168993E+10 | 0.624253E+09 | 0.106568E+10 | 0.237707E+10 | 0.608108E+09 |
August | 0.200837E+10 | 0.101258E+10 | 0.995791E+09 | 0.271299E+10 | 0.708038E+09 |
September | 0.215567E+10 | 0.132084E+10 | 0.834824E+09 | 0.263334E+10 | 0.100908E+10 |
October | 0.232875E+10 | 0.161030E+10 | 0.718453E+09 | 0.252897E+10 | 0.147542E+10 |
November | 0.205464E+10 | 0.148830E+10 | 0.566344E+09 | 0.196810E+10 | 0.181759E+10 |
December | 0.184533E+10 | 0.133251E+10 | 0.512815E+09 | 0.159396E+10 | 0.247313E+10 |
Annual Sum or Average | 0.232772E+11 | 0.134089E+11 | 0.986830E+10 | 0.250208E+11 | 0.179917E+11 |
Minimum of Months | 0.151695E+10 | 0.442411E+09 | 0.512815E+09 | 0.159396E+10 | 0.608108E+09 |
Maximum of Months | 0.232875E+10 | 0.161030E+10 | 0.107453E+10 | 0.271299E+10 | 0.284801E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194040E+10 | 0.138587E+10 | 0.554528E+09 | 0.163973E+10 | 0.284783E+10 |
February | 0.223193E+10 | 0.160529E+10 | 0.626646E+09 | 0.214352E+10 | 0.195531E+10 |
March | 0.220881E+10 | 0.124037E+10 | 0.968449E+09 | 0.212165E+10 | 0.191940E+10 |
April | 0.171824E+10 | 0.821844E+09 | 0.896400E+09 | 0.176474E+10 | 0.134526E+10 |
May | 0.157751E+10 | 0.523930E+09 | 0.105358E+10 | 0.165903E+10 | 0.110278E+10 |
June | 0.151685E+10 | 0.442383E+09 | 0.107447E+10 | 0.187694E+10 | 0.729163E+09 |
July | 0.168983E+10 | 0.624213E+09 | 0.106561E+10 | 0.237692E+10 | 0.608070E+09 |
August | 0.200825E+10 | 0.101252E+10 | 0.995728E+09 | 0.271282E+10 | 0.707993E+09 |
September | 0.215553E+10 | 0.132076E+10 | 0.834771E+09 | 0.263318E+10 | 0.100902E+10 |
October | 0.232861E+10 | 0.161020E+10 | 0.718407E+09 | 0.252882E+10 | 0.147532E+10 |
November | 0.205451E+10 | 0.148821E+10 | 0.566309E+09 | 0.196797E+10 | 0.181748E+10 |
December | 0.184521E+10 | 0.133243E+10 | 0.512783E+09 | 0.159386E+10 | 0.247297E+10 |
Annual Sum or Average | 0.232757E+11 | 0.134080E+11 | 0.986768E+10 | 0.250192E+11 | 0.179906E+11 |
Minimum of Months | 0.151685E+10 | 0.442383E+09 | 0.512783E+09 | 0.159386E+10 | 0.608070E+09 |
Maximum of Months | 0.232861E+10 | 0.161020E+10 | 0.107447E+10 | 0.271282E+10 | 0.284783E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110165E+10 | 0.443972E+09 | 0.657674E+09 | 0.455914E+09 | 0.629692E+10 |
February | 0.169837E+10 | 0.834837E+09 | 0.863537E+09 | 0.115464E+10 | 0.413154E+10 |
March | 0.240638E+10 | 0.881735E+09 | 0.152465E+10 | 0.170716E+10 | 0.377731E+10 |
April | 0.304021E+10 | 0.134695E+10 | 0.169325E+10 | 0.283905E+10 | 0.255163E+10 |
May | 0.388587E+10 | 0.177216E+10 | 0.211370E+10 | 0.404645E+10 | 0.212996E+10 |
June | 0.409130E+10 | 0.187929E+10 | 0.221201E+10 | 0.488846E+10 | 0.141844E+10 |
July | 0.433078E+10 | 0.218841E+10 | 0.214237E+10 | 0.573796E+10 | 0.123181E+10 |
August | 0.367742E+10 | 0.180480E+10 | 0.187262E+10 | 0.469623E+10 | 0.134940E+10 |
September | 0.286282E+10 | 0.144733E+10 | 0.141550E+10 | 0.325931E+10 | 0.191908E+10 |
October | 0.211434E+10 | 0.105050E+10 | 0.106384E+10 | 0.188803E+10 | 0.287402E+10 |
November | 0.144847E+10 | 0.718563E+09 | 0.729904E+09 | 0.984278E+09 | 0.384233E+10 |
December | 0.100609E+10 | 0.424642E+09 | 0.581447E+09 | 0.422018E+09 | 0.537390E+10 |
Annual Sum or Average | 0.316637E+11 | 0.147932E+11 | 0.168705E+11 | 0.320795E+11 | 0.368964E+11 |
Minimum of Months | 0.100609E+10 | 0.424642E+09 | 0.581447E+09 | 0.422018E+09 | 0.123181E+10 |
Maximum of Months | 0.433078E+10 | 0.218841E+10 | 0.221201E+10 | 0.573796E+10 | 0.629692E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43558086.08 | 17554235.48 | 26003850.60 | 18026412.49 | 0.248975E+09 |
February | 67152206.57 | 33008722.16 | 34143484.40 | 45653373.65 | 0.163358E+09 |
March | 95146176.06 | 34863004.17 | 60283171.89 | 67499581.41 | 0.149351E+09 |
April | 0.120207E+09 | 53257251.03 | 66949718.69 | 0.112254E+09 | 0.100889E+09 |
May | 0.153644E+09 | 70069727.27 | 83573927.22 | 0.159993E+09 | 84216540.94 |
June | 0.161766E+09 | 74305261.51 | 87460933.56 | 0.193285E+09 | 56083984.05 |
July | 0.171235E+09 | 86527660.76 | 84707526.21 | 0.226874E+09 | 48704757.68 |
August | 0.145402E+09 | 71360117.07 | 74041640.40 | 0.185685E+09 | 53354124.64 |
September | 0.113194E+09 | 57226040.50 | 55967463.68 | 0.128870E+09 | 75878836.90 |
October | 83598998.33 | 41535833.66 | 42063164.67 | 74651150.55 | 0.113636E+09 |
November | 57271098.37 | 28411351.41 | 28859746.96 | 38917462.44 | 0.151922E+09 |
December | 39779864.03 | 16789957.23 | 22989906.80 | 16686223.69 | 0.212479E+09 |
Annual Sum or Average | 0.125195E+10 | 0.584909E+09 | 0.667045E+09 | 0.126839E+10 | 0.145885E+10 |
Minimum of Months | 39779864.03 | 16789957.23 | 22989906.80 | 16686223.69 | 48704757.68 |
Maximum of Months | 0.171235E+09 | 86527660.76 | 87460933.56 | 0.226874E+09 | 0.248975E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.825882E+09 | 0.00 | 0.825882E+09 | 3325507.06 | 0.104181E+11 |
February | 0.105325E+10 | 0.00 | 0.105325E+10 | 74913574.55 | 0.704926E+10 |
March | 0.189427E+10 | 0.00 | 0.189427E+10 | 0.324439E+09 | 0.626392E+10 |
April | 0.209019E+10 | 12197831.14 | 0.207800E+10 | 0.784521E+09 | 0.423106E+10 |
May | 0.283642E+10 | 0.168075E+09 | 0.266835E+10 | 0.173049E+10 | 0.324976E+10 |
June | 0.319631E+10 | 0.367387E+09 | 0.282892E+10 | 0.297794E+10 | 0.198484E+10 |
July | 0.301734E+10 | 0.282608E+09 | 0.273473E+10 | 0.359368E+10 | 0.166910E+10 |
August | 0.241781E+10 | 64808205.07 | 0.235300E+10 | 0.256931E+10 | 0.195567E+10 |
September | 0.175236E+10 | 628838.05 | 0.175173E+10 | 0.137775E+10 | 0.287910E+10 |
October | 0.132085E+10 | 0.00 | 0.132085E+10 | 0.399965E+09 | 0.441785E+10 |
November | 0.868963E+09 | 0.00 | 0.868963E+09 | 61301817.86 | 0.625374E+10 |
December | 0.692548E+09 | 0.00 | 0.692548E+09 | 1607520.10 | 0.887752E+10 |
Annual Sum or Average | 0.219662E+11 | 0.895704E+09 | 0.210705E+11 | 0.138992E+11 | 0.592499E+11 |
Minimum of Months | 0.692548E+09 | 0.00 | 0.692548E+09 | 1607520.10 | 0.166910E+10 |
Maximum of Months | 0.319631E+10 | 0.367387E+09 | 0.282892E+10 | 0.359368E+10 | 0.104181E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126427E+10 | 0.579615E+09 | 0.684658E+09 | 0.501599E+09 | 0.634869E+10 |
February | 0.178607E+10 | 0.886738E+09 | 0.899334E+09 | 0.112104E+10 | 0.427686E+10 |
March | 0.265884E+10 | 0.110015E+10 | 0.155869E+10 | 0.180777E+10 | 0.386577E+10 |
April | 0.328299E+10 | 0.162702E+10 | 0.165597E+10 | 0.285723E+10 | 0.265855E+10 |
May | 0.374738E+10 | 0.166734E+10 | 0.208004E+10 | 0.358237E+10 | 0.215197E+10 |
June | 0.469402E+10 | 0.241553E+10 | 0.227850E+10 | 0.541908E+10 | 0.135763E+10 |
July | 0.509072E+10 | 0.287791E+10 | 0.221282E+10 | 0.653256E+10 | 0.111629E+10 |
August | 0.442407E+10 | 0.246494E+10 | 0.195913E+10 | 0.549070E+10 | 0.127389E+10 |
September | 0.302864E+10 | 0.156336E+10 | 0.146527E+10 | 0.329003E+10 | 0.179405E+10 |
October | 0.224532E+10 | 0.114013E+10 | 0.110519E+10 | 0.186717E+10 | 0.273071E+10 |
November | 0.137713E+10 | 0.642938E+09 | 0.734197E+09 | 0.756465E+09 | 0.378155E+10 |
December | 0.104957E+10 | 0.450792E+09 | 0.598782E+09 | 0.369468E+09 | 0.541724E+10 |
Annual Sum or Average | 0.346490E+11 | 0.174165E+11 | 0.172326E+11 | 0.335955E+11 | 0.367732E+11 |
Minimum of Months | 0.104957E+10 | 0.450792E+09 | 0.598782E+09 | 0.369468E+09 | 0.111629E+10 |
Maximum of Months | 0.509072E+10 | 0.287791E+10 | 0.227850E+10 | 0.653256E+10 | 0.634869E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.582141E+10 | 0.415776E+10 | 0.166365E+10 | 0.475623E+10 | 0.880016E+10 |
February | 0.669604E+10 | 0.481604E+10 | 0.188001E+10 | 0.622897E+10 | 0.597430E+10 |
March | 0.662669E+10 | 0.372123E+10 | 0.290546E+10 | 0.612461E+10 | 0.594319E+10 |
April | 0.515493E+10 | 0.246562E+10 | 0.268930E+10 | 0.505345E+10 | 0.428983E+10 |
May | 0.473270E+10 | 0.157185E+10 | 0.316085E+10 | 0.472864E+10 | 0.352685E+10 |
June | 0.455073E+10 | 0.132720E+10 | 0.322353E+10 | 0.542658E+10 | 0.235130E+10 |
July | 0.506968E+10 | 0.187271E+10 | 0.319697E+10 | 0.700926E+10 | 0.188354E+10 |
August | 0.602496E+10 | 0.303766E+10 | 0.298730E+10 | 0.803880E+10 | 0.213830E+10 |
September | 0.646683E+10 | 0.396242E+10 | 0.250441E+10 | 0.781235E+10 | 0.293235E+10 |
October | 0.698608E+10 | 0.483077E+10 | 0.215531E+10 | 0.749995E+10 | 0.422417E+10 |
November | 0.616377E+10 | 0.446478E+10 | 0.169899E+10 | 0.581369E+10 | 0.533423E+10 |
December | 0.553583E+10 | 0.399742E+10 | 0.153841E+10 | 0.466737E+10 | 0.747804E+10 |
Annual Sum or Average | 0.698296E+11 | 0.402255E+11 | 0.296042E+11 | 0.731599E+11 | 0.548763E+11 |
Minimum of Months | 0.455073E+10 | 0.132720E+10 | 0.153841E+10 | 0.466737E+10 | 0.188354E+10 |
Maximum of Months | 0.698608E+10 | 0.483077E+10 | 0.322353E+10 | 0.803880E+10 | 0.880016E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114517E+10 | 0.461509E+09 | 0.683658E+09 | 0.452530E+09 | 0.667919E+10 |
February | 0.176547E+10 | 0.867814E+09 | 0.897655E+09 | 0.115119E+10 | 0.441268E+10 |
March | 0.250145E+10 | 0.916564E+09 | 0.158488E+10 | 0.168058E+10 | 0.409766E+10 |
April | 0.316031E+10 | 0.140016E+10 | 0.176015E+10 | 0.281811E+10 | 0.282408E+10 |
May | 0.403938E+10 | 0.184216E+10 | 0.219722E+10 | 0.407384E+10 | 0.231750E+10 |
June | 0.425293E+10 | 0.195352E+10 | 0.229941E+10 | 0.498116E+10 | 0.153194E+10 |
July | 0.450187E+10 | 0.227485E+10 | 0.222702E+10 | 0.591320E+10 | 0.128743E+10 |
August | 0.382270E+10 | 0.187609E+10 | 0.194661E+10 | 0.483938E+10 | 0.140668E+10 |
September | 0.297592E+10 | 0.150450E+10 | 0.147142E+10 | 0.336075E+10 | 0.196092E+10 |
October | 0.219786E+10 | 0.109200E+10 | 0.110587E+10 | 0.194722E+10 | 0.291599E+10 |
November | 0.150569E+10 | 0.746947E+09 | 0.758742E+09 | 0.100620E+10 | 0.395714E+10 |
December | 0.104583E+10 | 0.441415E+09 | 0.604419E+09 | 0.422101E+09 | 0.562089E+10 |
Annual Sum or Average | 0.329146E+11 | 0.153775E+11 | 0.175371E+11 | 0.326462E+11 | 0.390121E+11 |
Minimum of Months | 0.104583E+10 | 0.441415E+09 | 0.604419E+09 | 0.422101E+09 | 0.128743E+10 |
Maximum of Months | 0.450187E+10 | 0.227485E+10 | 0.229941E+10 | 0.591320E+10 | 0.667919E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.63 | 3794.67 | 308.35 | 0.00 | 308.35 | 0.00 | 0.00 |
February | 38.81 | 2796.34 | 435.37 | 0.00 | 435.37 | 0.00 | 0.00 |
March | 130.16 | 2219.08 | 707.24 | 0.00 | 707.24 | 0.00 | 0.00 |
April | 317.22 | 1519.84 | 806.40 | 4.71 | 801.70 | 0.00 | 0.00 |
May | 665.08 | 1127.78 | 1059.00 | 62.75 | 996.25 | 0.00 | 0.00 |
June | 1177.59 | 716.01 | 1233.14 | 141.74 | 1091.41 | 0.00 | 0.00 |
July | 1365.25 | 583.30 | 1126.55 | 105.51 | 1021.03 | 0.00 | 0.00 |
August | 982.14 | 670.81 | 902.71 | 24.20 | 878.51 | 0.00 | 0.00 |
September | 555.58 | 1016.93 | 676.06 | 0.24 | 675.82 | 0.00 | 0.00 |
October | 171.92 | 1507.60 | 493.15 | 0.00 | 493.15 | 0.00 | 0.00 |
November | 31.27 | 2259.36 | 335.25 | 0.00 | 335.25 | 0.00 | 0.00 |
December | 0.76 | 3189.54 | 258.57 | 0.00 | 258.57 | 0.00 | 0.00 |
Annual Sum or Average | 455.87 | 1779.56 | 696.54 | 28.40 | 668.14 | 0.00 | 0.00 |
Minimum of Months | 0.76 | 583.30 | 258.57 | 0.00 | 258.57 | 0.00 | 0.00 |
Maximum of Months | 1365.25 | 3794.67 | 1233.14 | 141.74 | 1091.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 193.02 | 2312.43 | 472.03 | 216.40 | 255.62 | 0.00 | 0.00 |
February | 480.03 | 1695.80 | 738.29 | 366.54 | 371.75 | 0.00 | 0.00 |
March | 696.53 | 1366.00 | 992.70 | 410.75 | 581.95 | 0.00 | 0.00 |
April | 1126.01 | 955.58 | 1266.59 | 627.71 | 638.88 | 0.00 | 0.00 |
May | 1356.93 | 750.15 | 1399.11 | 622.51 | 776.60 | 0.00 | 0.00 |
June | 2104.07 | 495.48 | 1810.97 | 931.92 | 879.05 | 0.00 | 0.00 |
July | 2446.28 | 394.52 | 1900.66 | 1074.49 | 826.17 | 0.00 | 0.00 |
August | 2060.40 | 444.58 | 1651.76 | 920.30 | 731.45 | 0.00 | 0.00 |
September | 1291.10 | 638.50 | 1168.46 | 603.15 | 565.31 | 0.00 | 0.00 |
October | 731.12 | 930.64 | 838.31 | 425.68 | 412.63 | 0.00 | 0.00 |
November | 312.67 | 1362.02 | 531.30 | 248.05 | 283.26 | 0.00 | 0.00 |
December | 144.47 | 1944.62 | 391.87 | 168.31 | 223.56 | 0.00 | 0.00 |
Annual Sum or Average | 1082.05 | 1105.37 | 1098.71 | 552.27 | 546.44 | 0.00 | 0.00 |
Minimum of Months | 144.47 | 394.52 | 391.87 | 168.31 | 223.56 | 0.00 | 0.00 |
Maximum of Months | 2446.28 | 2312.43 | 1900.66 | 1074.49 | 879.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1795.54 | 3187.81 | 2173.46 | 1552.33 | 621.14 | 0.00 | 0.00 |
February | 2602.79 | 2353.00 | 2767.88 | 1990.76 | 777.12 | 0.00 | 0.00 |
March | 2306.55 | 2098.96 | 2474.12 | 1389.35 | 1084.77 | 0.00 | 0.00 |
April | 1970.06 | 1541.85 | 1988.78 | 951.24 | 1037.54 | 0.00 | 0.00 |
May | 1778.65 | 1226.23 | 1766.99 | 586.86 | 1180.13 | 0.00 | 0.00 |
June | 2104.33 | 847.20 | 1755.68 | 512.04 | 1243.65 | 0.00 | 0.00 |
July | 2625.24 | 654.86 | 1892.80 | 699.19 | 1193.61 | 0.00 | 0.00 |
August | 3009.86 | 737.42 | 2249.46 | 1134.13 | 1115.33 | 0.00 | 0.00 |
September | 3032.63 | 1039.74 | 2494.92 | 1528.71 | 966.21 | 0.00 | 0.00 |
October | 2835.97 | 1442.35 | 2608.30 | 1803.60 | 804.70 | 0.00 | 0.00 |
November | 2286.80 | 1916.61 | 2378.00 | 1722.52 | 655.47 | 0.00 | 0.00 |
December | 1771.54 | 2668.39 | 2066.84 | 1492.47 | 574.38 | 0.00 | 0.00 |
Annual Sum or Average | 2341.14 | 1640.39 | 2214.28 | 1275.54 | 938.74 | 0.00 | 0.00 |
Minimum of Months | 1771.54 | 654.86 | 1755.68 | 512.04 | 574.38 | 0.00 | 0.00 |
Maximum of Months | 3032.63 | 3187.81 | 2767.88 | 1990.76 | 1243.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.58 | 2433.20 | 427.56 | 172.31 | 255.25 | 0.00 | 0.00 |
February | 482.15 | 1746.25 | 729.77 | 358.72 | 371.05 | 0.00 | 0.00 |
March | 632.91 | 1451.64 | 933.93 | 342.21 | 591.73 | 0.00 | 0.00 |
April | 1094.29 | 1017.47 | 1219.26 | 540.18 | 679.07 | 0.00 | 0.00 |
May | 1523.64 | 808.78 | 1508.13 | 687.79 | 820.35 | 0.00 | 0.00 |
June | 1922.95 | 556.01 | 1640.79 | 753.67 | 887.12 | 0.00 | 0.00 |
July | 2208.37 | 452.34 | 1680.81 | 849.33 | 831.48 | 0.00 | 0.00 |
August | 1810.67 | 489.38 | 1427.23 | 700.45 | 726.78 | 0.00 | 0.00 |
September | 1304.10 | 699.32 | 1148.12 | 580.44 | 567.68 | 0.00 | 0.00 |
October | 741.71 | 998.61 | 820.59 | 407.70 | 412.88 | 0.00 | 0.00 |
November | 399.66 | 1429.53 | 580.90 | 288.17 | 292.72 | 0.00 | 0.00 |
December | 161.42 | 2018.77 | 390.47 | 164.81 | 225.66 | 0.00 | 0.00 |
Annual Sum or Average | 1040.79 | 1173.15 | 1043.71 | 487.62 | 556.10 | 0.00 | 0.00 |
Minimum of Months | 161.42 | 452.34 | 390.47 | 164.81 | 225.66 | 0.00 | 0.00 |
Maximum of Months | 2208.37 | 2433.20 | 1680.81 | 849.33 | 887.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.40 | 3811.27 | 308.35 | 0.00 | 308.35 | 0.00 | 0.00 |
February | 37.58 | 2817.19 | 435.37 | 0.00 | 435.37 | 0.00 | 0.00 |
March | 149.08 | 2221.20 | 707.23 | 0.00 | 707.23 | 0.00 | 0.00 |
April | 365.22 | 1498.62 | 806.40 | 4.71 | 801.69 | 0.00 | 0.00 |
May | 732.76 | 1119.50 | 1058.99 | 62.75 | 996.24 | 0.00 | 0.00 |
June | 1242.13 | 699.46 | 1233.14 | 141.74 | 1091.40 | 0.00 | 0.00 |
July | 1399.69 | 581.49 | 1126.54 | 105.51 | 1021.03 | 0.00 | 0.00 |
August | 1006.26 | 685.88 | 902.70 | 24.20 | 878.51 | 0.00 | 0.00 |
September | 557.11 | 1084.33 | 676.06 | 0.24 | 675.82 | 0.00 | 0.00 |
October | 156.85 | 1654.66 | 493.15 | 0.00 | 493.15 | 0.00 | 0.00 |
November | 25.58 | 2415.71 | 335.25 | 0.00 | 335.25 | 0.00 | 0.00 |
December | 0.85 | 3289.36 | 258.57 | 0.00 | 258.57 | 0.00 | 0.00 |
Annual Sum or Average | 475.64 | 1819.42 | 696.54 | 28.40 | 668.14 | 0.00 | 0.00 |
Minimum of Months | 0.85 | 581.49 | 258.57 | 0.00 | 258.57 | 0.00 | 0.00 |
Maximum of Months | 1399.69 | 3811.27 | 1233.14 | 141.74 | 1091.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 194.05 | 2333.41 | 472.04 | 216.41 | 255.63 | 0.00 | 0.00 |
February | 483.21 | 1720.90 | 738.32 | 366.56 | 371.76 | 0.00 | 0.00 |
March | 716.46 | 1385.37 | 992.73 | 410.77 | 581.97 | 0.00 | 0.00 |
April | 1163.51 | 962.59 | 1266.63 | 627.73 | 638.90 | 0.00 | 0.00 |
May | 1396.96 | 763.48 | 1399.16 | 622.54 | 776.62 | 0.00 | 0.00 |
June | 2133.05 | 506.82 | 1811.03 | 931.95 | 879.07 | 0.00 | 0.00 |
July | 2463.60 | 418.05 | 1900.73 | 1074.53 | 826.19 | 0.00 | 0.00 |
August | 2071.34 | 478.20 | 1651.82 | 920.34 | 731.47 | 0.00 | 0.00 |
September | 1285.68 | 705.78 | 1168.50 | 603.17 | 565.32 | 0.00 | 0.00 |
October | 709.96 | 1043.99 | 838.34 | 425.69 | 412.64 | 0.00 | 0.00 |
November | 298.17 | 1470.84 | 531.32 | 248.06 | 283.26 | 0.00 | 0.00 |
December | 142.18 | 2014.96 | 391.88 | 168.31 | 223.57 | 0.00 | 0.00 |
Annual Sum or Average | 1091.71 | 1148.29 | 1098.75 | 552.29 | 546.46 | 0.00 | 0.00 |
Minimum of Months | 142.18 | 418.05 | 391.88 | 168.31 | 223.57 | 0.00 | 0.00 |
Maximum of Months | 2463.60 | 2333.41 | 1900.73 | 1074.53 | 879.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1836.70 | 3189.91 | 2173.48 | 1552.34 | 621.14 | 0.00 | 0.00 |
February | 2658.24 | 2424.85 | 2767.89 | 1990.77 | 777.12 | 0.00 | 0.00 |
March | 2376.50 | 2149.95 | 2474.14 | 1389.36 | 1084.78 | 0.00 | 0.00 |
April | 2042.60 | 1557.08 | 1988.79 | 951.25 | 1037.54 | 0.00 | 0.00 |
May | 1858.31 | 1235.25 | 1766.99 | 586.86 | 1180.13 | 0.00 | 0.00 |
June | 2172.48 | 843.97 | 1755.69 | 512.04 | 1243.65 | 0.00 | 0.00 |
July | 2662.43 | 681.11 | 1892.81 | 699.19 | 1193.61 | 0.00 | 0.00 |
August | 3038.68 | 793.04 | 2249.47 | 1134.14 | 1115.33 | 0.00 | 0.00 |
September | 3047.79 | 1167.89 | 2494.93 | 1528.72 | 966.21 | 0.00 | 0.00 |
October | 2832.57 | 1652.54 | 2608.32 | 1803.61 | 804.70 | 0.00 | 0.00 |
November | 2277.84 | 2103.65 | 2378.01 | 1722.53 | 655.48 | 0.00 | 0.00 |
December | 1785.31 | 2770.02 | 2066.85 | 1492.48 | 574.38 | 0.00 | 0.00 |
Annual Sum or Average | 2380.16 | 1711.51 | 2214.29 | 1275.55 | 938.75 | 0.00 | 0.00 |
Minimum of Months | 1785.31 | 681.11 | 1755.69 | 512.04 | 574.38 | 0.00 | 0.00 |
Maximum of Months | 3047.79 | 3189.91 | 2767.89 | 1990.77 | 1243.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.95 | 2443.96 | 427.57 | 172.31 | 255.26 | 0.00 | 0.00 |
February | 496.15 | 1775.34 | 729.80 | 358.73 | 371.07 | 0.00 | 0.00 |
March | 662.58 | 1466.05 | 933.96 | 342.22 | 591.75 | 0.00 | 0.00 |
April | 1138.62 | 1023.35 | 1219.29 | 540.20 | 679.09 | 0.00 | 0.00 |
May | 1570.50 | 826.68 | 1508.18 | 687.81 | 820.37 | 0.00 | 0.00 |
June | 1960.55 | 568.88 | 1640.84 | 753.70 | 887.14 | 0.00 | 0.00 |
July | 2227.01 | 478.09 | 1680.86 | 849.36 | 831.50 | 0.00 | 0.00 |
August | 1822.70 | 523.73 | 1427.28 | 700.48 | 726.80 | 0.00 | 0.00 |
September | 1307.17 | 769.66 | 1148.16 | 580.46 | 567.69 | 0.00 | 0.00 |
October | 732.78 | 1115.46 | 820.62 | 407.72 | 412.90 | 0.00 | 0.00 |
November | 394.75 | 1540.99 | 580.92 | 288.18 | 292.73 | 0.00 | 0.00 |
December | 163.79 | 2085.71 | 390.48 | 164.81 | 225.67 | 0.00 | 0.00 |
Annual Sum or Average | 1057.45 | 1216.24 | 1043.75 | 487.64 | 556.11 | 0.00 | 0.00 |
Minimum of Months | 163.79 | 478.09 | 390.48 | 164.81 | 225.67 | 0.00 | 0.00 |
Maximum of Months | 2227.01 | 2443.96 | 1680.86 | 849.36 | 887.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.24 | 3889.66 | 308.35 | 0.00 | 308.35 | 0.00 | 0.00 |
February | 30.97 | 2913.88 | 435.37 | 0.00 | 435.37 | 0.00 | 0.00 |
March | 121.13 | 2338.68 | 707.24 | 0.00 | 707.24 | 0.00 | 0.00 |
April | 302.67 | 1632.35 | 806.40 | 4.71 | 801.70 | 0.00 | 0.00 |
May | 646.09 | 1213.32 | 1059.00 | 62.75 | 996.25 | 0.00 | 0.00 |
June | 1148.90 | 765.76 | 1233.14 | 141.74 | 1091.41 | 0.00 | 0.00 |
July | 1341.73 | 623.17 | 1126.55 | 105.51 | 1021.03 | 0.00 | 0.00 |
August | 959.27 | 730.16 | 902.71 | 24.20 | 878.51 | 0.00 | 0.00 |
September | 531.54 | 1110.76 | 676.06 | 0.24 | 675.82 | 0.00 | 0.00 |
October | 149.33 | 1649.44 | 493.15 | 0.00 | 493.15 | 0.00 | 0.00 |
November | 23.65 | 2412.71 | 335.25 | 0.00 | 335.25 | 0.00 | 0.00 |
December | 0.60 | 3314.49 | 258.57 | 0.00 | 258.57 | 0.00 | 0.00 |
Annual Sum or Average | 440.74 | 1878.80 | 696.54 | 28.40 | 668.14 | 0.00 | 0.00 |
Minimum of Months | 0.60 | 623.17 | 258.57 | 0.00 | 258.57 | 0.00 | 0.00 |
Maximum of Months | 1341.73 | 3889.66 | 1233.14 | 141.74 | 1091.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 187.28 | 2370.33 | 472.03 | 216.40 | 255.62 | 0.00 | 0.00 |
February | 463.39 | 1767.88 | 738.29 | 366.54 | 371.75 | 0.00 | 0.00 |
March | 674.94 | 1443.31 | 992.70 | 410.75 | 581.95 | 0.00 | 0.00 |
April | 1102.33 | 1025.68 | 1266.59 | 627.71 | 638.88 | 0.00 | 0.00 |
May | 1337.50 | 803.45 | 1399.11 | 622.51 | 776.60 | 0.00 | 0.00 |
June | 2090.69 | 523.78 | 1810.97 | 931.92 | 879.05 | 0.00 | 0.00 |
July | 2438.98 | 416.77 | 1900.66 | 1074.49 | 826.17 | 0.00 | 0.00 |
August | 2049.99 | 475.62 | 1651.76 | 920.30 | 731.45 | 0.00 | 0.00 |
September | 1269.30 | 692.15 | 1168.46 | 603.15 | 565.31 | 0.00 | 0.00 |
October | 697.12 | 1019.53 | 838.31 | 425.68 | 412.63 | 0.00 | 0.00 |
November | 291.85 | 1458.93 | 531.30 | 248.05 | 283.26 | 0.00 | 0.00 |
December | 137.94 | 2022.57 | 391.87 | 168.31 | 223.56 | 0.00 | 0.00 |
Annual Sum or Average | 1065.31 | 1166.07 | 1098.71 | 552.27 | 546.44 | 0.00 | 0.00 |
Minimum of Months | 137.94 | 416.77 | 391.87 | 168.31 | 223.56 | 0.00 | 0.00 |
Maximum of Months | 2438.98 | 2370.33 | 1900.66 | 1074.49 | 879.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1775.77 | 3285.60 | 2173.46 | 1552.33 | 621.14 | 0.00 | 0.00 |
February | 2574.80 | 2469.53 | 2767.88 | 1990.76 | 777.12 | 0.00 | 0.00 |
March | 2286.67 | 2218.93 | 2474.12 | 1389.35 | 1084.77 | 0.00 | 0.00 |
April | 1949.63 | 1655.03 | 1988.78 | 951.24 | 1037.54 | 0.00 | 0.00 |
May | 1765.47 | 1316.78 | 1766.99 | 586.86 | 1180.13 | 0.00 | 0.00 |
June | 2093.59 | 907.14 | 1755.68 | 512.04 | 1243.65 | 0.00 | 0.00 |
July | 2616.96 | 703.23 | 1892.80 | 699.19 | 1193.61 | 0.00 | 0.00 |
August | 3001.35 | 798.35 | 2249.46 | 1134.13 | 1115.33 | 0.00 | 0.00 |
September | 3014.02 | 1131.31 | 2494.92 | 1528.71 | 966.21 | 0.00 | 0.00 |
October | 2800.16 | 1577.12 | 2608.30 | 1803.60 | 804.70 | 0.00 | 0.00 |
November | 2242.94 | 2057.96 | 2378.00 | 1722.52 | 655.47 | 0.00 | 0.00 |
December | 1742.60 | 2791.98 | 2066.84 | 1492.47 | 574.38 | 0.00 | 0.00 |
Annual Sum or Average | 2319.89 | 1740.11 | 2214.28 | 1275.54 | 938.74 | 0.00 | 0.00 |
Minimum of Months | 1742.60 | 703.23 | 1755.68 | 512.04 | 574.38 | 0.00 | 0.00 |
Maximum of Months | 3014.02 | 3285.60 | 2767.88 | 1990.76 | 1243.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.96 | 2493.72 | 427.56 | 172.31 | 255.25 | 0.00 | 0.00 |
February | 475.85 | 1824.02 | 729.77 | 358.72 | 371.05 | 0.00 | 0.00 |
March | 627.46 | 1529.89 | 933.93 | 342.21 | 591.73 | 0.00 | 0.00 |
April | 1087.23 | 1089.54 | 1219.26 | 540.18 | 679.07 | 0.00 | 0.00 |
May | 1521.00 | 865.25 | 1508.13 | 687.79 | 820.35 | 0.00 | 0.00 |
June | 1921.74 | 591.03 | 1640.79 | 753.67 | 887.12 | 0.00 | 0.00 |
July | 2207.73 | 480.67 | 1680.81 | 849.33 | 831.48 | 0.00 | 0.00 |
August | 1806.82 | 525.19 | 1427.23 | 700.45 | 726.78 | 0.00 | 0.00 |
September | 1296.58 | 756.53 | 1148.12 | 580.44 | 567.68 | 0.00 | 0.00 |
October | 727.01 | 1088.71 | 820.59 | 407.70 | 412.88 | 0.00 | 0.00 |
November | 388.19 | 1526.68 | 580.90 | 288.17 | 292.72 | 0.00 | 0.00 |
December | 157.59 | 2098.60 | 390.47 | 164.81 | 225.66 | 0.00 | 0.00 |
Annual Sum or Average | 1035.21 | 1237.07 | 1043.71 | 487.62 | 556.10 | 0.00 | 0.00 |
Minimum of Months | 157.59 | 480.67 | 390.47 | 164.81 | 225.66 | 0.00 | 0.00 |
Maximum of Months | 2207.73 | 2493.72 | 1680.81 | 849.33 | 887.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7057284.90 | 0.101636E+11 | 0.825882E+09 | 0.00 | 0.825882E+09 | 0.00 | 0.00 |
February | 93892908.39 | 0.676490E+10 | 0.105325E+10 | 0.00 | 0.105325E+10 | 0.00 | 0.00 |
March | 0.348612E+09 | 0.594360E+10 | 0.189427E+10 | 0.00 | 0.189427E+10 | 0.00 | 0.00 |
April | 0.822247E+09 | 0.393942E+10 | 0.209019E+10 | 12197831.14 | 0.207800E+10 | 0.00 | 0.00 |
May | 0.178136E+10 | 0.302065E+10 | 0.283642E+10 | 0.168075E+09 | 0.266835E+10 | 0.00 | 0.00 |
June | 0.305232E+10 | 0.185590E+10 | 0.319631E+10 | 0.367387E+09 | 0.282892E+10 | 0.00 | 0.00 |
July | 0.365669E+10 | 0.156230E+10 | 0.301734E+10 | 0.282608E+09 | 0.273473E+10 | 0.00 | 0.00 |
August | 0.263058E+10 | 0.179670E+10 | 0.241781E+10 | 64808205.07 | 0.235300E+10 | 0.00 | 0.00 |
September | 0.144006E+10 | 0.263588E+10 | 0.175236E+10 | 628838.05 | 0.175173E+10 | 0.00 | 0.00 |
October | 0.460461E+09 | 0.403796E+10 | 0.132085E+10 | 0.00 | 0.132085E+10 | 0.00 | 0.00 |
November | 81061136.07 | 0.585626E+10 | 0.868963E+09 | 0.00 | 0.868963E+09 | 0.00 | 0.00 |
December | 2025917.19 | 0.854285E+10 | 0.692548E+09 | 0.00 | 0.692548E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143764E+11 | 0.561200E+11 | 0.219662E+11 | 0.895704E+09 | 0.210705E+11 | 0.00 | 0.00 |
Minimum of Months | 2025917.19 | 0.156230E+10 | 0.692548E+09 | 0.00 | 0.692548E+09 | 0.00 | 0.00 |
Maximum of Months | 0.365669E+10 | 0.101636E+11 | 0.319631E+10 | 0.367387E+09 | 0.282892E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.516986E+09 | 0.619360E+10 | 0.126427E+10 | 0.579615E+09 | 0.684658E+09 | 0.00 | 0.00 |
February | 0.116128E+10 | 0.410248E+10 | 0.178607E+10 | 0.886738E+09 | 0.899334E+09 | 0.00 | 0.00 |
March | 0.186560E+10 | 0.365868E+10 | 0.265884E+10 | 0.110015E+10 | 0.155869E+10 | 0.00 | 0.00 |
April | 0.291862E+10 | 0.247686E+10 | 0.328299E+10 | 0.162702E+10 | 0.165597E+10 | 0.00 | 0.00 |
May | 0.363441E+10 | 0.200920E+10 | 0.374738E+10 | 0.166734E+10 | 0.208004E+10 | 0.00 | 0.00 |
June | 0.545375E+10 | 0.128428E+10 | 0.469402E+10 | 0.241553E+10 | 0.227850E+10 | 0.00 | 0.00 |
July | 0.655211E+10 | 0.105669E+10 | 0.509072E+10 | 0.287791E+10 | 0.221282E+10 | 0.00 | 0.00 |
August | 0.551858E+10 | 0.119077E+10 | 0.442407E+10 | 0.246494E+10 | 0.195913E+10 | 0.00 | 0.00 |
September | 0.334653E+10 | 0.165500E+10 | 0.302864E+10 | 0.156336E+10 | 0.146527E+10 | 0.00 | 0.00 |
October | 0.195822E+10 | 0.249263E+10 | 0.224532E+10 | 0.114013E+10 | 0.110519E+10 | 0.00 | 0.00 |
November | 0.810452E+09 | 0.353036E+10 | 0.137713E+10 | 0.642938E+09 | 0.734197E+09 | 0.00 | 0.00 |
December | 0.386957E+09 | 0.520847E+10 | 0.104957E+10 | 0.450792E+09 | 0.598782E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.341235E+11 | 0.348590E+11 | 0.346490E+11 | 0.174165E+11 | 0.172326E+11 | 0.00 | 0.00 |
Minimum of Months | 0.386957E+09 | 0.105669E+10 | 0.104957E+10 | 0.450792E+09 | 0.598782E+09 | 0.00 | 0.00 |
Maximum of Months | 0.655211E+10 | 0.619360E+10 | 0.509072E+10 | 0.287791E+10 | 0.227850E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.480919E+10 | 0.853822E+10 | 0.582141E+10 | 0.415776E+10 | 0.166365E+10 | 0.00 | 0.00 |
February | 0.629668E+10 | 0.569237E+10 | 0.669604E+10 | 0.481604E+10 | 0.188001E+10 | 0.00 | 0.00 |
March | 0.617787E+10 | 0.562187E+10 | 0.662669E+10 | 0.372123E+10 | 0.290546E+10 | 0.00 | 0.00 |
April | 0.510640E+10 | 0.399648E+10 | 0.515493E+10 | 0.246562E+10 | 0.268930E+10 | 0.00 | 0.00 |
May | 0.476394E+10 | 0.328433E+10 | 0.473270E+10 | 0.157185E+10 | 0.316085E+10 | 0.00 | 0.00 |
June | 0.545441E+10 | 0.219594E+10 | 0.455073E+10 | 0.132720E+10 | 0.322353E+10 | 0.00 | 0.00 |
July | 0.703143E+10 | 0.175397E+10 | 0.506968E+10 | 0.187271E+10 | 0.319697E+10 | 0.00 | 0.00 |
August | 0.806161E+10 | 0.197512E+10 | 0.602496E+10 | 0.303766E+10 | 0.298730E+10 | 0.00 | 0.00 |
September | 0.786058E+10 | 0.269501E+10 | 0.646683E+10 | 0.396242E+10 | 0.250441E+10 | 0.00 | 0.00 |
October | 0.759585E+10 | 0.386319E+10 | 0.698608E+10 | 0.483077E+10 | 0.215531E+10 | 0.00 | 0.00 |
November | 0.592738E+10 | 0.496785E+10 | 0.616377E+10 | 0.446478E+10 | 0.169899E+10 | 0.00 | 0.00 |
December | 0.474488E+10 | 0.714703E+10 | 0.553583E+10 | 0.399742E+10 | 0.153841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.738302E+11 | 0.517314E+11 | 0.698296E+11 | 0.402255E+11 | 0.296042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.474488E+10 | 0.175397E+10 | 0.455073E+10 | 0.132720E+10 | 0.153841E+10 | 0.00 | 0.00 |
Maximum of Months | 0.806161E+10 | 0.853822E+10 | 0.698608E+10 | 0.483077E+10 | 0.322353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.459553E+09 | 0.651707E+10 | 0.114517E+10 | 0.461509E+09 | 0.683658E+09 | 0.00 | 0.00 |
February | 0.116641E+10 | 0.422454E+10 | 0.176547E+10 | 0.867814E+09 | 0.897655E+09 | 0.00 | 0.00 |
March | 0.169519E+10 | 0.388806E+10 | 0.250145E+10 | 0.916564E+09 | 0.158488E+10 | 0.00 | 0.00 |
April | 0.283641E+10 | 0.263729E+10 | 0.316031E+10 | 0.140016E+10 | 0.176015E+10 | 0.00 | 0.00 |
May | 0.408091E+10 | 0.216624E+10 | 0.403938E+10 | 0.184216E+10 | 0.219722E+10 | 0.00 | 0.00 |
June | 0.498428E+10 | 0.144118E+10 | 0.425293E+10 | 0.195352E+10 | 0.229941E+10 | 0.00 | 0.00 |
July | 0.591489E+10 | 0.121154E+10 | 0.450187E+10 | 0.227485E+10 | 0.222702E+10 | 0.00 | 0.00 |
August | 0.484971E+10 | 0.131075E+10 | 0.382270E+10 | 0.187609E+10 | 0.194661E+10 | 0.00 | 0.00 |
September | 0.338022E+10 | 0.181264E+10 | 0.297592E+10 | 0.150450E+10 | 0.147142E+10 | 0.00 | 0.00 |
October | 0.198658E+10 | 0.267467E+10 | 0.219786E+10 | 0.109200E+10 | 0.110587E+10 | 0.00 | 0.00 |
November | 0.103593E+10 | 0.370534E+10 | 0.150569E+10 | 0.746947E+09 | 0.758742E+09 | 0.00 | 0.00 |
December | 0.432343E+09 | 0.540707E+10 | 0.104583E+10 | 0.441415E+09 | 0.604419E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.328224E+11 | 0.369964E+11 | 0.329146E+11 | 0.153775E+11 | 0.175371E+11 | 0.00 | 0.00 |
Minimum of Months | 0.432343E+09 | 0.121154E+10 | 0.104583E+10 | 0.441415E+09 | 0.604419E+09 | 0.00 | 0.00 |
Maximum of Months | 0.591489E+10 | 0.651707E+10 | 0.450187E+10 | 0.227485E+10 | 0.229941E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 3742299.28 | 0.102081E+11 | 0.825877E+09 | 0.00 | 0.825877E+09 | 0.00 | 0.00 |
February | 90919953.26 | 0.681534E+10 | 0.105324E+10 | 0.00 | 0.105324E+10 | 0.00 | 0.00 |
March | 0.399303E+09 | 0.594927E+10 | 0.189426E+10 | 0.00 | 0.189426E+10 | 0.00 | 0.00 |
April | 0.946658E+09 | 0.388442E+10 | 0.209018E+10 | 12197760.57 | 0.207798E+10 | 0.00 | 0.00 |
May | 0.196261E+10 | 0.299847E+10 | 0.283640E+10 | 0.168074E+09 | 0.266833E+10 | 0.00 | 0.00 |
June | 0.321960E+10 | 0.181301E+10 | 0.319629E+10 | 0.367385E+09 | 0.282891E+10 | 0.00 | 0.00 |
July | 0.374892E+10 | 0.155746E+10 | 0.301732E+10 | 0.282607E+09 | 0.273472E+10 | 0.00 | 0.00 |
August | 0.269517E+10 | 0.183706E+10 | 0.241780E+10 | 64807830.09 | 0.235299E+10 | 0.00 | 0.00 |
September | 0.144402E+10 | 0.281059E+10 | 0.175235E+10 | 628834.42 | 0.175172E+10 | 0.00 | 0.00 |
October | 0.420100E+09 | 0.443184E+10 | 0.132085E+10 | 0.00 | 0.132085E+10 | 0.00 | 0.00 |
November | 66311637.66 | 0.626151E+10 | 0.868958E+09 | 0.00 | 0.868958E+09 | 0.00 | 0.00 |
December | 2270879.97 | 0.881021E+10 | 0.692544E+09 | 0.00 | 0.692544E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.149996E+11 | 0.573773E+11 | 0.219661E+11 | 0.895699E+09 | 0.210704E+11 | 0.00 | 0.00 |
Minimum of Months | 2270879.97 | 0.155746E+10 | 0.692544E+09 | 0.00 | 0.692544E+09 | 0.00 | 0.00 |
Maximum of Months | 0.374892E+10 | 0.102081E+11 | 0.319629E+10 | 0.367385E+09 | 0.282891E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.519748E+09 | 0.624981E+10 | 0.126432E+10 | 0.579639E+09 | 0.684680E+09 | 0.00 | 0.00 |
February | 0.116897E+10 | 0.416321E+10 | 0.178613E+10 | 0.886774E+09 | 0.899361E+09 | 0.00 | 0.00 |
March | 0.191897E+10 | 0.371057E+10 | 0.265894E+10 | 0.110019E+10 | 0.155874E+10 | 0.00 | 0.00 |
April | 0.301581E+10 | 0.249503E+10 | 0.328311E+10 | 0.162708E+10 | 0.165602E+10 | 0.00 | 0.00 |
May | 0.374162E+10 | 0.204490E+10 | 0.374750E+10 | 0.166740E+10 | 0.208010E+10 | 0.00 | 0.00 |
June | 0.552887E+10 | 0.131369E+10 | 0.469419E+10 | 0.241562E+10 | 0.227856E+10 | 0.00 | 0.00 |
July | 0.659849E+10 | 0.111970E+10 | 0.509090E+10 | 0.287802E+10 | 0.221288E+10 | 0.00 | 0.00 |
August | 0.554786E+10 | 0.128082E+10 | 0.442422E+10 | 0.246504E+10 | 0.195918E+10 | 0.00 | 0.00 |
September | 0.333248E+10 | 0.182939E+10 | 0.302874E+10 | 0.156343E+10 | 0.146532E+10 | 0.00 | 0.00 |
October | 0.190157E+10 | 0.279622E+10 | 0.224540E+10 | 0.114018E+10 | 0.110522E+10 | 0.00 | 0.00 |
November | 0.772850E+09 | 0.381240E+10 | 0.137718E+10 | 0.642964E+09 | 0.734220E+09 | 0.00 | 0.00 |
December | 0.380803E+09 | 0.539688E+10 | 0.104961E+10 | 0.450810E+09 | 0.598801E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.344281E+11 | 0.362126E+11 | 0.346502E+11 | 0.174172E+11 | 0.172331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.380803E+09 | 0.111970E+10 | 0.104961E+10 | 0.450810E+09 | 0.598801E+09 | 0.00 | 0.00 |
Maximum of Months | 0.659849E+10 | 0.624981E+10 | 0.509090E+10 | 0.287802E+10 | 0.227856E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.491941E+10 | 0.854385E+10 | 0.582144E+10 | 0.415778E+10 | 0.166366E+10 | 0.00 | 0.00 |
February | 0.643083E+10 | 0.586619E+10 | 0.669608E+10 | 0.481606E+10 | 0.188002E+10 | 0.00 | 0.00 |
March | 0.636523E+10 | 0.575843E+10 | 0.662672E+10 | 0.372126E+10 | 0.290547E+10 | 0.00 | 0.00 |
April | 0.529443E+10 | 0.403596E+10 | 0.515495E+10 | 0.246564E+10 | 0.268931E+10 | 0.00 | 0.00 |
May | 0.497730E+10 | 0.330849E+10 | 0.473272E+10 | 0.157186E+10 | 0.316086E+10 | 0.00 | 0.00 |
June | 0.563107E+10 | 0.218758E+10 | 0.455074E+10 | 0.132721E+10 | 0.322354E+10 | 0.00 | 0.00 |
July | 0.713105E+10 | 0.182429E+10 | 0.506970E+10 | 0.187272E+10 | 0.319698E+10 | 0.00 | 0.00 |
August | 0.813879E+10 | 0.212407E+10 | 0.602499E+10 | 0.303768E+10 | 0.298731E+10 | 0.00 | 0.00 |
September | 0.789987E+10 | 0.302718E+10 | 0.646687E+10 | 0.396245E+10 | 0.250442E+10 | 0.00 | 0.00 |
October | 0.758676E+10 | 0.442616E+10 | 0.698611E+10 | 0.483080E+10 | 0.215531E+10 | 0.00 | 0.00 |
November | 0.590416E+10 | 0.545267E+10 | 0.616380E+10 | 0.446481E+10 | 0.169900E+10 | 0.00 | 0.00 |
December | 0.478177E+10 | 0.741923E+10 | 0.553586E+10 | 0.399745E+10 | 0.153841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.750607E+11 | 0.539741E+11 | 0.698300E+11 | 0.402257E+11 | 0.296043E+11 | 0.00 | 0.00 |
Minimum of Months | 0.478177E+10 | 0.182429E+10 | 0.455074E+10 | 0.132721E+10 | 0.153841E+10 | 0.00 | 0.00 |
Maximum of Months | 0.813879E+10 | 0.854385E+10 | 0.698611E+10 | 0.483080E+10 | 0.322354E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.473940E+09 | 0.654590E+10 | 0.114520E+10 | 0.461526E+09 | 0.683678E+09 | 0.00 | 0.00 |
February | 0.120029E+10 | 0.429490E+10 | 0.176553E+10 | 0.867846E+09 | 0.897681E+09 | 0.00 | 0.00 |
March | 0.177466E+10 | 0.392666E+10 | 0.250153E+10 | 0.916598E+09 | 0.158493E+10 | 0.00 | 0.00 |
April | 0.295130E+10 | 0.265252E+10 | 0.316041E+10 | 0.140021E+10 | 0.176020E+10 | 0.00 | 0.00 |
May | 0.420644E+10 | 0.221417E+10 | 0.403951E+10 | 0.184223E+10 | 0.219728E+10 | 0.00 | 0.00 |
June | 0.508175E+10 | 0.147453E+10 | 0.425306E+10 | 0.195359E+10 | 0.229947E+10 | 0.00 | 0.00 |
July | 0.596483E+10 | 0.128052E+10 | 0.450202E+10 | 0.227494E+10 | 0.222708E+10 | 0.00 | 0.00 |
August | 0.488192E+10 | 0.140276E+10 | 0.382282E+10 | 0.187616E+10 | 0.194666E+10 | 0.00 | 0.00 |
September | 0.338818E+10 | 0.199496E+10 | 0.297602E+10 | 0.150455E+10 | 0.147146E+10 | 0.00 | 0.00 |
October | 0.196268E+10 | 0.298766E+10 | 0.219794E+10 | 0.109204E+10 | 0.110590E+10 | 0.00 | 0.00 |
November | 0.102320E+10 | 0.399425E+10 | 0.150574E+10 | 0.746975E+09 | 0.758764E+09 | 0.00 | 0.00 |
December | 0.438705E+09 | 0.558638E+10 | 0.104587E+10 | 0.441432E+09 | 0.604437E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333479E+11 | 0.383552E+11 | 0.329156E+11 | 0.153781E+11 | 0.175375E+11 | 0.00 | 0.00 |
Minimum of Months | 0.438705E+09 | 0.128052E+10 | 0.104587E+10 | 0.441432E+09 | 0.604437E+09 | 0.00 | 0.00 |
Maximum of Months | 0.596483E+10 | 0.654590E+10 | 0.450202E+10 | 0.227494E+10 | 0.229947E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 3325507.06 | 0.104181E+11 | 0.825882E+09 | 0.00 | 0.825882E+09 | 0.00 | 0.00 |
February | 74913574.55 | 0.704926E+10 | 0.105325E+10 | 0.00 | 0.105325E+10 | 0.00 | 0.00 |
March | 0.324439E+09 | 0.626392E+10 | 0.189427E+10 | 0.00 | 0.189427E+10 | 0.00 | 0.00 |
April | 0.784521E+09 | 0.423106E+10 | 0.209019E+10 | 12197831.14 | 0.207800E+10 | 0.00 | 0.00 |
May | 0.173049E+10 | 0.324976E+10 | 0.283642E+10 | 0.168075E+09 | 0.266835E+10 | 0.00 | 0.00 |
June | 0.297794E+10 | 0.198484E+10 | 0.319631E+10 | 0.367387E+09 | 0.282892E+10 | 0.00 | 0.00 |
July | 0.359368E+10 | 0.166910E+10 | 0.301734E+10 | 0.282608E+09 | 0.273473E+10 | 0.00 | 0.00 |
August | 0.256931E+10 | 0.195567E+10 | 0.241781E+10 | 64808205.07 | 0.235300E+10 | 0.00 | 0.00 |
September | 0.137775E+10 | 0.287910E+10 | 0.175236E+10 | 628838.05 | 0.175173E+10 | 0.00 | 0.00 |
October | 0.399965E+09 | 0.441785E+10 | 0.132085E+10 | 0.00 | 0.132085E+10 | 0.00 | 0.00 |
November | 61301817.86 | 0.625374E+10 | 0.868963E+09 | 0.00 | 0.868963E+09 | 0.00 | 0.00 |
December | 1607520.10 | 0.887752E+10 | 0.692548E+09 | 0.00 | 0.692548E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.138992E+11 | 0.592499E+11 | 0.219662E+11 | 0.895704E+09 | 0.210705E+11 | 0.00 | 0.00 |
Minimum of Months | 1607520.10 | 0.166910E+10 | 0.692548E+09 | 0.00 | 0.692548E+09 | 0.00 | 0.00 |
Maximum of Months | 0.359368E+10 | 0.104181E+11 | 0.319631E+10 | 0.367387E+09 | 0.282892E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.501599E+09 | 0.634869E+10 | 0.126427E+10 | 0.579615E+09 | 0.684658E+09 | 0.00 | 0.00 |
February | 0.112104E+10 | 0.427686E+10 | 0.178607E+10 | 0.886738E+09 | 0.899334E+09 | 0.00 | 0.00 |
March | 0.180777E+10 | 0.386577E+10 | 0.265884E+10 | 0.110015E+10 | 0.155869E+10 | 0.00 | 0.00 |
April | 0.285723E+10 | 0.265855E+10 | 0.328299E+10 | 0.162702E+10 | 0.165597E+10 | 0.00 | 0.00 |
May | 0.358237E+10 | 0.215197E+10 | 0.374738E+10 | 0.166734E+10 | 0.208004E+10 | 0.00 | 0.00 |
June | 0.541908E+10 | 0.135763E+10 | 0.469402E+10 | 0.241553E+10 | 0.227850E+10 | 0.00 | 0.00 |
July | 0.653256E+10 | 0.111629E+10 | 0.509072E+10 | 0.287791E+10 | 0.221282E+10 | 0.00 | 0.00 |
August | 0.549070E+10 | 0.127389E+10 | 0.442407E+10 | 0.246494E+10 | 0.195913E+10 | 0.00 | 0.00 |
September | 0.329003E+10 | 0.179405E+10 | 0.302864E+10 | 0.156336E+10 | 0.146527E+10 | 0.00 | 0.00 |
October | 0.186717E+10 | 0.273071E+10 | 0.224532E+10 | 0.114013E+10 | 0.110519E+10 | 0.00 | 0.00 |
November | 0.756465E+09 | 0.378155E+10 | 0.137713E+10 | 0.642938E+09 | 0.734197E+09 | 0.00 | 0.00 |
December | 0.369468E+09 | 0.541724E+10 | 0.104957E+10 | 0.450792E+09 | 0.598782E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335955E+11 | 0.367732E+11 | 0.346490E+11 | 0.174165E+11 | 0.172326E+11 | 0.00 | 0.00 |
Minimum of Months | 0.369468E+09 | 0.111629E+10 | 0.104957E+10 | 0.450792E+09 | 0.598782E+09 | 0.00 | 0.00 |
Maximum of Months | 0.653256E+10 | 0.634869E+10 | 0.509072E+10 | 0.287791E+10 | 0.227850E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.475623E+10 | 0.880016E+10 | 0.582141E+10 | 0.415776E+10 | 0.166365E+10 | 0.00 | 0.00 |
February | 0.622897E+10 | 0.597430E+10 | 0.669604E+10 | 0.481604E+10 | 0.188001E+10 | 0.00 | 0.00 |
March | 0.612461E+10 | 0.594319E+10 | 0.662669E+10 | 0.372123E+10 | 0.290546E+10 | 0.00 | 0.00 |
April | 0.505345E+10 | 0.428983E+10 | 0.515493E+10 | 0.246562E+10 | 0.268930E+10 | 0.00 | 0.00 |
May | 0.472864E+10 | 0.352685E+10 | 0.473270E+10 | 0.157185E+10 | 0.316085E+10 | 0.00 | 0.00 |
June | 0.542658E+10 | 0.235130E+10 | 0.455073E+10 | 0.132720E+10 | 0.322353E+10 | 0.00 | 0.00 |
July | 0.700926E+10 | 0.188354E+10 | 0.506968E+10 | 0.187271E+10 | 0.319697E+10 | 0.00 | 0.00 |
August | 0.803880E+10 | 0.213830E+10 | 0.602496E+10 | 0.303766E+10 | 0.298730E+10 | 0.00 | 0.00 |
September | 0.781235E+10 | 0.293235E+10 | 0.646683E+10 | 0.396242E+10 | 0.250441E+10 | 0.00 | 0.00 |
October | 0.749995E+10 | 0.422417E+10 | 0.698608E+10 | 0.483077E+10 | 0.215531E+10 | 0.00 | 0.00 |
November | 0.581369E+10 | 0.533423E+10 | 0.616377E+10 | 0.446478E+10 | 0.169899E+10 | 0.00 | 0.00 |
December | 0.466737E+10 | 0.747804E+10 | 0.553583E+10 | 0.399742E+10 | 0.153841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.731599E+11 | 0.548763E+11 | 0.698296E+11 | 0.402255E+11 | 0.296042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.466737E+10 | 0.188354E+10 | 0.455073E+10 | 0.132720E+10 | 0.153841E+10 | 0.00 | 0.00 |
Maximum of Months | 0.803880E+10 | 0.880016E+10 | 0.698608E+10 | 0.483077E+10 | 0.322353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.452530E+09 | 0.667919E+10 | 0.114517E+10 | 0.461509E+09 | 0.683658E+09 | 0.00 | 0.00 |
February | 0.115119E+10 | 0.441268E+10 | 0.176547E+10 | 0.867814E+09 | 0.897655E+09 | 0.00 | 0.00 |
March | 0.168058E+10 | 0.409766E+10 | 0.250145E+10 | 0.916564E+09 | 0.158488E+10 | 0.00 | 0.00 |
April | 0.281811E+10 | 0.282408E+10 | 0.316031E+10 | 0.140016E+10 | 0.176015E+10 | 0.00 | 0.00 |
May | 0.407384E+10 | 0.231750E+10 | 0.403938E+10 | 0.184216E+10 | 0.219722E+10 | 0.00 | 0.00 |
June | 0.498116E+10 | 0.153194E+10 | 0.425293E+10 | 0.195352E+10 | 0.229941E+10 | 0.00 | 0.00 |
July | 0.591320E+10 | 0.128743E+10 | 0.450187E+10 | 0.227485E+10 | 0.222702E+10 | 0.00 | 0.00 |
August | 0.483938E+10 | 0.140668E+10 | 0.382270E+10 | 0.187609E+10 | 0.194661E+10 | 0.00 | 0.00 |
September | 0.336075E+10 | 0.196092E+10 | 0.297592E+10 | 0.150450E+10 | 0.147142E+10 | 0.00 | 0.00 |
October | 0.194722E+10 | 0.291599E+10 | 0.219786E+10 | 0.109200E+10 | 0.110587E+10 | 0.00 | 0.00 |
November | 0.100620E+10 | 0.395714E+10 | 0.150569E+10 | 0.746947E+09 | 0.758742E+09 | 0.00 | 0.00 |
December | 0.422101E+09 | 0.562089E+10 | 0.104583E+10 | 0.441415E+09 | 0.604419E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.326462E+11 | 0.390121E+11 | 0.329146E+11 | 0.153775E+11 | 0.175371E+11 | 0.00 | 0.00 |
Minimum of Months | 0.422101E+09 | 0.128743E+10 | 0.104583E+10 | 0.441415E+09 | 0.604419E+09 | 0.00 | 0.00 |
Maximum of Months | 0.591320E+10 | 0.667919E+10 | 0.450187E+10 | 0.227485E+10 | 0.229941E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.541057E+10 | -0.515797E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -252597248.2 | 60.05 | 0.00 | 0.00 |
February | 0.499082E+10 | -0.476848E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -222340006.3 | 60.05 | 0.00 | 0.00 |
March | 0.582973E+10 | -0.558766E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -242073161.5 | 60.05 | 0.00 | 0.00 |
April | 0.507793E+10 | -0.484790E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -230034188.6 | 60.05 | 0.00 | 0.00 |
May | 0.515615E+10 | -0.492077E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235374932.5 | 60.05 | 0.00 | 0.00 |
June | 0.481730E+10 | -0.459195E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225346517.3 | 60.05 | 0.00 | 0.00 |
July | 0.434282E+10 | -0.411123E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231588289.8 | 60.05 | 0.00 | 0.00 |
August | 0.467851E+10 | -0.444657E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231938630.2 | 60.05 | 0.00 | 0.00 |
September | 0.428229E+10 | -0.405707E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225215822.4 | 60.05 | 0.00 | 0.00 |
October | 0.461647E+10 | -0.438146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235012798.4 | 60.05 | 0.00 | 0.00 |
November | 0.480773E+10 | -0.457646E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -231268784.4 | 60.05 | 0.00 | 0.00 |
December | 0.504704E+10 | -0.480114E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -245898442.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.590574E+11 | -0.562487E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.280869E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.428229E+10 | -0.558766E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -252597248.2 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.582973E+10 | -0.405707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -222340006.3 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3965.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109632E+11 | 27359.45 | 09-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.470481E+10 | 23909.64 | 01-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142999E+10 | 20354.17 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28935372.75 | 5148.86 | 29-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19871348.95 | 2534.20 | 08-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 248032.74 | 5.38 | 22-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 276192.47 | 5.52 | 19-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68001.69 | 4.91 | 09-AUG-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94047.50 | 5.52 | 06-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38721985.33 | 5217.70 | 10-OCT-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.846287E+09 | 14277.41 | 27-NOV-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.536556E+10 | 26629.20 | 29-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 68001.69 | 4.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109632E+11 | 27359.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.499310E+09 | 16535.47 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64266788.42 | 16497.01 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15076033.31 | 16492.73 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14169523.69 | 16496.47 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.592823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.499310E+09 | 16535.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116237E+11 | 13068.87 | 09-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706684E+10 | 12903.21 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.641003E+10 | 12900.16 | 15-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.393911E+10 | 12906.34 | 21-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.313442E+10 | 13221.75 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.736761E+09 | 12933.09 | 14-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122626E+09 | 8651.89 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.385220E+09 | 12873.48 | 18-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.938090E+09 | 12928.47 | 12-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166345E+10 | 12908.84 | 20-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.403245E+10 | 12901.40 | 09-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.796836E+10 | 12941.47 | 29-DEC-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.122626E+09 | 8651.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116237E+11 | 13221.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.633677E+10 | 8463.07 | 09-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359080E+10 | 8355.80 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271692E+10 | 8349.54 | 06-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112470E+10 | 8343.25 | 22-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.570959E+09 | 8562.08 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28874142.81 | 4889.64 | 16-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1629953.42 | 434.95 | 17-AUG-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74557242.02 | 6587.11 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.365974E+09 | 8325.40 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170803E+10 | 8333.59 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399279E+10 | 8353.03 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.633677E+10 | 8562.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105812E+11 | 12863.71 | 09-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.655888E+10 | 12700.66 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.551660E+10 | 12691.15 | 06-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283856E+10 | 12687.75 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152500E+10 | 13014.20 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.104153E+09 | 8138.60 | 16-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11412651.25 | 5031.32 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266632E+09 | 11027.03 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101749E+10 | 12654.45 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322502E+10 | 12685.93 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670411E+10 | 12696.45 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105812E+11 | 13014.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.668824E+10 | 8676.56 | 09-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378898E+10 | 8566.44 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310761E+10 | 8560.11 | 06-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138637E+10 | 8532.71 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.676381E+09 | 8777.93 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54276997.04 | 5231.03 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9665862.55 | 4579.71 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104136E+09 | 6632.10 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.458472E+09 | 8535.24 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182876E+10 | 8543.69 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.417427E+10 | 8563.64 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.668824E+10 | 8777.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146015E+11 | 27846.39 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736567E+10 | 26422.01 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330965E+10 | 23081.53 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.404238E+09 | 9888.14 | 29-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.309512E+09 | 7930.56 | 08-MAY-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 210484.04 | 5.38 | 22-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 244826.04 | 5.80 | 19-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 50479.84 | 4.75 | 11-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 884466.29 | 548.57 | 19-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.320656E+09 | 11070.84 | 10-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.254080E+10 | 18480.32 | 27-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.891926E+10 | 27111.79 | 29-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 50479.84 | 4.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146015E+11 | 27846.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.363789E+10 | 22609.90 | 05-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121832E+10 | 22546.13 | 06-FEB-06:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.581171E+09 | 22579.98 | 20-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4809998.96 | 9604.54 | 10-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82023386.83 | 22618.17 | 08-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30550883.35 | 22602.79 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.501785E+09 | 22606.20 | 20-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165429E+10 | 22595.06 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.771084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.363789E+10 | 22618.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.700922E+10 | 13107.20 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331690E+10 | 12752.47 | 10-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245766E+10 | 12747.41 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.943424E+09 | 12707.81 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.684243E+09 | 12751.39 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40607301.86 | 7713.85 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 97566.05 | 476.14 | 08-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11383411.84 | 7150.86 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177696E+09 | 12646.88 | 19-SEP-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.599502E+09 | 12711.56 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.216173E+10 | 12741.42 | 27-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.457829E+10 | 12812.19 | 29-DEC-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 97566.05 | 476.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.700922E+10 | 13107.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.579929E+10 | 9274.14 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297180E+10 | 9022.12 | 10-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202122E+10 | 9017.97 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660898E+09 | 8989.70 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.402886E+09 | 9020.44 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19763787.49 | 5040.10 | 16-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6619165.36 | 1853.36 | 17-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161744E+09 | 8946.05 | 20-SEP-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.625730E+09 | 9008.31 | 11-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196967E+10 | 9014.24 | 27-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398870E+10 | 9029.40 | 29-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579929E+10 | 9274.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.962482E+10 | 12914.53 | 10-JAN-21:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.529422E+10 | 12601.77 | 02-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365725E+10 | 12564.78 | 07-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128838E+10 | 12518.98 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.748118E+09 | 12561.91 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23275679.63 | 7384.50 | 16-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8442975.51 | 5456.04 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256440E+09 | 12459.14 | 20-SEP-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112344E+10 | 12544.97 | 11-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334163E+10 | 12564.69 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.662639E+10 | 12647.63 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.962482E+10 | 12914.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.660862E+10 | 9666.13 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.353503E+10 | 9397.78 | 24-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264397E+10 | 9398.59 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.980401E+09 | 9369.04 | 10-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.601312E+09 | 9401.06 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57126872.23 | 5340.48 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 908265.05 | 1024.61 | 08-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20242440.44 | 4992.92 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.259153E+09 | 9323.33 | 20-SEP-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.881102E+09 | 9371.36 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240723E+10 | 9394.87 | 27-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.464290E+10 | 9402.61 | 29-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 908265.05 | 1024.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.660862E+10 | 9666.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161689E+11 | 23149.49 | 11-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.767694E+10 | 22955.20 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.361633E+10 | 22514.45 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.342478E+09 | 12604.35 | 29-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.229105E+09 | 7855.33 | 08-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 160374.50 | 6.00 | 22-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 102037.75 | 6.47 | 18-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6271308.73 | 2205.66 | 19-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.367265E+09 | 11580.90 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287363E+10 | 19872.37 | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102330E+11 | 23030.49 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161689E+11 | 23149.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132694E+11 | 37141.51 | 11-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675547E+10 | 36836.29 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.436111E+10 | 36304.61 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131503E+10 | 36298.38 | 28-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.945007E+09 | 36305.15 | 08-MAY-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21791672.57 | 25007.02 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5654300.17 | 10817.34 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148217E+09 | 36066.60 | 13-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114419E+10 | 36308.63 | 10-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.443206E+10 | 36304.47 | 29-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.937095E+10 | 36952.01 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.417689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132694E+11 | 37141.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112768E+11 | 17521.68 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.594343E+10 | 17201.46 | 01-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.507004E+10 | 16788.29 | 04-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.245214E+10 | 16630.47 | 22-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180131E+10 | 16594.75 | 09-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.312915E+09 | 16531.27 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 51151258.30 | 7968.98 | 08-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162486E+09 | 15891.05 | 18-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.839437E+09 | 16588.28 | 19-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197037E+10 | 16631.40 | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.454894E+10 | 16628.82 | 10-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.842740E+10 | 17285.70 | 29-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 51151258.30 | 7968.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112768E+11 | 17521.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.883053E+10 | 11312.52 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.490728E+10 | 11105.78 | 01-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369580E+10 | 10899.01 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149066E+10 | 10738.52 | 15-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.913191E+09 | 10714.07 | 09-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83248612.56 | 9352.68 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6261480.30 | 4543.82 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 54306962.63 | 10668.86 | 18-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.530972E+09 | 10709.89 | 19-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154958E+10 | 10743.77 | 05-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378993E+10 | 10744.60 | 13-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.682878E+10 | 11189.18 | 29-DEC-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6261480.30 | 4543.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.883053E+10 | 11312.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144256E+11 | 17307.54 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.854494E+10 | 17096.02 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681945E+10 | 16674.89 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.310358E+10 | 16429.35 | 15-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196727E+10 | 16389.83 | 02-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.245365E+09 | 15580.03 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24324807.68 | 7142.20 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165914E+09 | 15696.84 | 18-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117266E+10 | 16385.55 | 19-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.319233E+10 | 16437.38 | 05-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.659181E+10 | 16438.65 | 13-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111463E+11 | 17119.76 | 29-DEC-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 24324807.68 | 7142.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144256E+11 | 17307.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.929098E+10 | 11718.92 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.523803E+10 | 11504.48 | 01-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.424469E+10 | 11290.14 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186168E+10 | 11118.08 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121953E+10 | 11089.32 | 06-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.221736E+09 | 11055.39 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35979849.81 | 5001.83 | 08-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131716E+09 | 11051.05 | 18-AUG-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.745622E+09 | 11093.63 | 19-SEP-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190979E+10 | 11122.57 | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405810E+10 | 11119.66 | 24-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.713283E+10 | 11560.94 | 29-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 35979849.81 | 5001.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.929098E+10 | 11718.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.223454E+09 | 0.223454E+09 | 16069.94 | 27-FEB-15:30 | 16069.94 | 0.00 |
March | 0.00 | 0.00 | 6325454.30 | 6320037.50 | 1273.16 | 14-MAR-14:00 | 1265.97 | 0.00 |
April | 0.00 | 0.00 | 0.242851E+10 | 0.241780E+10 | 32731.05 | 07-APR-14:10 | 32731.05 | 0.00 |
May | 0.00 | 0.00 | 0.893109E+10 | 0.873704E+10 | 52514.49 | 19-MAY-15:40 | 52514.49 | 0.00 |
June | 0.00 | 0.00 | 0.304348E+11 | 0.291879E+11 | 66876.25 | 29-JUN-15:00 | 66876.25 | 0.00 |
July | 0.00 | 0.00 | 0.532080E+11 | 0.515495E+11 | 83652.89 | 17-JUL-16:00 | 83652.89 | 0.00 |
August | 0.00 | 0.00 | 0.460610E+11 | 0.456761E+11 | 80478.45 | 10-AUG-15:00 | 80478.45 | 0.00 |
September | 0.00 | 0.00 | 0.225851E+11 | 0.209037E+11 | 105084.17 | 07-SEP-14:50 | 52489.61 | 0.00 |
October | 0.00 | 0.00 | 0.523879E+10 | 0.522901E+10 | 53276.74 | 18-OCT-15:30 | 53276.74 | 0.00 |
November | 0.00 | 0.00 | 0.308908E+09 | 0.307370E+09 | 9923.34 | 17-NOV-17:00 | 9923.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169426E+12 | 0.164238E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.532080E+11 | 0.515495E+11 | 105084.17 | 83652.89 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.223837E+09 | 0.223837E+09 | 14327.12 | 27-FEB-15:02 | 14327.12 | 0.00 |
March | 0.00 | 0.00 | 7531202.98 | 7516521.76 | 1626.33 | 14-MAR-13:00 | 1626.33 | 0.00 |
April | 0.00 | 0.00 | 0.237975E+10 | 0.236786E+10 | 30410.81 | 06-APR-16:00 | 30410.81 | 0.00 |
May | 0.00 | 0.00 | 0.854702E+10 | 0.832343E+10 | 54471.96 | 19-MAY-15:30 | 54471.96 | 0.00 |
June | 0.00 | 0.00 | 0.293611E+11 | 0.279879E+11 | 66919.31 | 21-JUN-14:05 | 61049.33 | 0.00 |
July | 0.00 | 0.00 | 0.492507E+11 | 0.475543E+11 | 80818.30 | 17-JUL-16:00 | 80818.30 | 0.00 |
August | 0.00 | 0.00 | 0.416227E+11 | 0.411428E+11 | 76713.92 | 09-AUG-14:05 | 76713.92 | 0.00 |
September | 0.00 | 0.00 | 0.197286E+11 | 0.181659E+11 | 96649.63 | 07-SEP-14:50 | 48379.89 | 0.00 |
October | 0.00 | 0.00 | 0.432026E+10 | 0.430142E+10 | 45156.16 | 18-OCT-15:00 | 45156.16 | 0.00 |
November | 0.00 | 0.00 | 0.247631E+09 | 0.241880E+09 | 7458.30 | 04-NOV-14:02 | 7458.30 | 0.00 |
December | 0.00 | 0.00 | 60900.91 | 60900.91 | 609.01 | 08-DEC-07:03 | 609.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155689E+12 | 0.150317E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.492507E+11 | 0.475543E+11 | 96649.63 | 80818.30 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3800884.94 | 3783838.64 | 1746.08 | 31-JAN-06:06 | 1746.08 | 0.00 |
February | 0.00 | 0.00 | 0.234801E+09 | 0.234722E+09 | 15362.53 | 27-FEB-15:00 | 15362.53 | 0.00 |
March | 0.00 | 0.00 | 8008314.61 | 7734315.43 | 2271.85 | 06-MAR-06:30 | 2271.85 | 0.00 |
April | 0.00 | 0.00 | 0.265678E+10 | 0.262084E+10 | 32632.36 | 06-APR-16:00 | 32632.36 | 0.00 |
May | 0.00 | 0.00 | 0.104091E+11 | 0.989188E+10 | 69373.04 | 19-MAY-15:30 | 69373.04 | 0.00 |
June | 0.00 | 0.00 | 0.351534E+11 | 0.330094E+11 | 81278.63 | 29-JUN-15:00 | 81278.63 | 0.00 |
July | 0.00 | 0.00 | 0.585319E+11 | 0.557526E+11 | 98770.45 | 17-JUL-16:00 | 98770.45 | 0.00 |
August | 0.00 | 0.00 | 0.478083E+11 | 0.465520E+11 | 90993.09 | 07-AUG-14:40 | 90993.09 | 0.00 |
September | 0.00 | 0.00 | 0.225122E+11 | 0.203780E+11 | 94684.76 | 03-SEP-15:21 | 94684.76 | 0.00 |
October | 0.00 | 0.00 | 0.456480E+10 | 0.448799E+10 | 49385.67 | 18-OCT-15:00 | 49385.67 | 0.00 |
November | 0.00 | 0.00 | 0.299608E+09 | 0.277889E+09 | 8901.28 | 17-NOV-17:00 | 8104.02 | 0.00 |
December | 0.00 | 0.00 | 3948027.02 | 3921151.18 | 1038.29 | 23-DEC-06:06 | 1038.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182187E+12 | 0.173221E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 3800884.94 | 3783838.64 | 1038.29 | 1038.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.585319E+11 | 0.557526E+11 | 98770.45 | 98770.45 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 61947.65 | 375671.01 | 14-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 36300.85 | 411361.65 | 27-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22840.95 | 389347.94 | 18-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9248.30 | 465972.30 | 10-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5860.96 | 386100.82 | 02-MAY-05:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 744.83 | 181257.86 | 17-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 87.92 | 50520.90 | 05-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 363.07 | 145734.54 | 18-AUG-05:12 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2169.47 | 296001.16 | 13-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6395.04 | 324649.24 | 05-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 19465.23 | 371622.52 | 15-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 41397.61 | 379701.93 | 06-DEC-06:11 |
Annual Sum or Average | 0.00 | 17180.68 | ||||
Minimum of Months | 0.00 | 0.00 | 87.92 | 50520.90 | ||
Maximum of Months | 0.00 | 0.00 | 61947.65 | 465972.30 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1916.14 | 7053.94 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1961.40 | 7091.40 | 17-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2076.18 | 7078.79 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1860.80 | 6886.44 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1827.61 | 6581.43 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1762.01 | 6179.82 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1525.91 | 5809.89 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1650.70 | 5604.86 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1556.08 | 5739.52 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1626.60 | 6081.08 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1756.14 | 6470.00 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1783.17 | 6811.89 | 29-DEC-12:12 |
Annual Sum or Average | 0.00 | 1774.15 | ||||
Minimum of Months | 0.00 | 0.00 | 1525.91 | 5604.86 | ||
Maximum of Months | 0.00 | 0.00 | 2076.18 | 7091.40 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.551699E+10 | 0.71 | 6739.07 | 02-JAN-06:01 | 1.48 |
February | 0.425908E+10 | 0.62 | 6739.07 | 06-FEB-06:01 | 1.48 |
March | 0.491856E+10 | 0.64 | 6739.07 | 06-MAR-07:01 | 1.48 |
April | 0.453096E+10 | 0.58 | 8144.94 | 27-APR-05:01 | 1.60 |
May | 0.524907E+10 | 0.62 | 12806.18 | 22-MAY-05:01 | 1.94 |
June | 0.713308E+10 | 0.72 | 9537.41 | 29-JUN-15:00 | 1.70 |
July | 0.863678E+10 | 0.76 | 12607.87 | 17-JUL-16:00 | 1.91 |
August | 0.901747E+10 | 0.79 | 12582.55 | 10-AUG-15:00 | 1.92 |
September | 0.668754E+10 | 0.70 | 10908.46 | 05-SEP-14:10 | 1.79 |
October | 0.530135E+10 | 0.60 | 9567.78 | 21-OCT-05:02 | 1.71 |
November | 0.443308E+10 | 0.57 | 5731.38 | 02-NOV-05:01 | 1.38 |
December | 0.458599E+10 | 0.60 | 6739.07 | 26-DEC-07:01 | 1.48 |
Annual Sum or Average | 0.702699E+11 | 0.66 | |||
Minimum of Months | 0.425908E+10 | 0.57 | 5731.38 | 1.38 | |
Maximum of Months | 0.901747E+10 | 0.79 | 12806.18 | 1.94 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.486699E+10 | 0.68 | 6263.81 | 02-JAN-05:01 | 1.44 |
February | 0.376874E+10 | 0.60 | 6263.81 | 01-FEB-06:01 | 1.44 |
March | 0.421893E+10 | 0.60 | 6263.81 | 04-MAR-07:03 | 1.44 |
April | 0.377155E+10 | 0.54 | 5624.74 | 25-APR-16:00 | 1.37 |
May | 0.433993E+10 | 0.58 | 7631.12 | 19-MAY-15:30 | 1.55 |
June | 0.617887E+10 | 0.70 | 9585.86 | 29-JUN-14:30 | 1.71 |
July | 0.743150E+10 | 0.73 | 11776.12 | 17-JUL-15:50 | 1.86 |
August | 0.743861E+10 | 0.73 | 11525.50 | 09-AUG-14:05 | 1.85 |
September | 0.518781E+10 | 0.63 | 10009.12 | 05-SEP-14:05 | 1.74 |
October | 0.402217E+10 | 0.54 | 6519.47 | 18-OCT-15:10 | 1.46 |
November | 0.375752E+10 | 0.55 | 6263.81 | 13-NOV-06:01 | 1.44 |
December | 0.432623E+10 | 0.62 | 6263.81 | 01-DEC-07:02 | 1.44 |
Annual Sum or Average | 0.593088E+11 | 0.63 | |||
Minimum of Months | 0.375752E+10 | 0.54 | 5624.74 | 1.37 | |
Maximum of Months | 0.743861E+10 | 0.73 | 11776.12 | 1.86 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.623752E+10 | 0.69 | 6719.58 | 02-JAN-05:11 | 1.24 |
February | 0.464246E+10 | 0.58 | 6719.58 | 01-FEB-05:01 | 1.24 |
March | 0.500659E+10 | 0.56 | 6719.58 | 01-MAR-06:01 | 1.24 |
April | 0.413519E+10 | 0.48 | 6719.58 | 01-APR-05:11 | 1.24 |
May | 0.464185E+10 | 0.51 | 7057.33 | 19-MAY-15:30 | 1.25 |
June | 0.572331E+10 | 0.57 | 8517.81 | 29-JUN-14:50 | 1.36 |
July | 0.664345E+10 | 0.58 | 10870.30 | 17-JUL-16:00 | 1.50 |
August | 0.650416E+10 | 0.58 | 10148.11 | 07-AUG-15:00 | 1.46 |
September | 0.482790E+10 | 0.52 | 8126.21 | 01-SEP-15:20 | 1.33 |
October | 0.422875E+10 | 0.47 | 6719.58 | 05-OCT-05:01 | 1.23 |
November | 0.464420E+10 | 0.54 | 6719.58 | 02-NOV-06:02 | 1.24 |
December | 0.575366E+10 | 0.65 | 6719.58 | 01-DEC-06:01 | 1.24 |
Annual Sum or Average | 0.629890E+11 | 0.56 | |||
Minimum of Months | 0.413519E+10 | 0.47 | 6719.58 | 1.23 | |
Maximum of Months | 0.664345E+10 | 0.69 | 10870.30 | 1.50 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.124668E+10 | 0.112201E+10 | 1522.07 | 09-JAN-07:25 | 1369.87 | 1369.87 | 45.89 | 4.86 |
February | 0.675004E+09 | 0.607503E+09 | 1429.25 | 01-FEB-07:01 | 1286.32 | 1286.32 | 48.23 | 4.58 |
March | 0.472801E+09 | 0.425521E+09 | 1421.10 | 06-MAR-07:01 | 1278.99 | 1278.99 | 47.53 | 4.56 |
April | 0.182150E+09 | 0.163935E+09 | 1244.83 | 10-APR-06:03 | 1120.35 | 1120.35 | 41.20 | 3.65 |
May | 0.126654E+09 | 0.113988E+09 | 1283.22 | 08-MAY-06:01 | 1154.90 | 1154.90 | 44.09 | 3.93 |
June | 17861148.36 | 16075033.52 | 998.48 | 17-JUN-06:03 | 898.63 | 898.63 | 35.11 | 1.74 |
July | 1939754.14 | 1745778.73 | 366.06 | 05-JUL-06:03 | 329.46 | 329.46 | 31.40 | 0.42 |
August | 8922105.87 | 8029895.28 | 779.68 | 18-AUG-06:03 | 701.72 | 701.72 | 32.74 | 1.12 |
September | 44996472.62 | 40496825.36 | 1234.69 | 20-SEP-06:03 | 1111.22 | 1111.22 | 40.27 | 3.56 |
October | 0.128006E+09 | 0.115205E+09 | 1290.85 | 10-OCT-06:01 | 1161.77 | 1161.77 | 43.44 | 3.98 |
November | 0.387066E+09 | 0.348360E+09 | 1342.03 | 27-NOV-07:20 | 1207.83 | 1207.83 | 46.89 | 4.25 |
December | 0.852468E+09 | 0.767221E+09 | 1430.59 | 29-DEC-07:01 | 1287.53 | 1287.53 | 48.26 | 4.59 |
Annual Sum or Average | 0.414454E+10 | 0.373009E+10 | ||||||
Minimum of Months | 1939754.14 | 1745778.73 | 366.06 | 329.46 | 329.46 | 31.40 | 0.42 | |
Maximum of Months | 0.124668E+10 | 0.112201E+10 | 1522.07 | 1369.87 | 1369.87 | 48.26 | 4.86 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.91 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.77 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.76 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 56.58 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:01 | 2.06 | 2.06 | 57.42 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.01 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:02 | 2.06 | 2.06 | 57.24 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:02 | 2.06 | 2.06 | 57.36 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 57.37 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.12 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.99 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 57.05 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.58 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.12 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 33.56 | 33.56 | 61947.65 | 375671.01 | 14-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 35.70 | 35.70 | 36300.85 | 411361.65 | 27-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 27.30 | 27.30 | 22840.95 | 389347.94 | 18-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.94 | 29.94 | 9248.30 | 465972.30 | 10-APR-05:11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.11 | 60.00 | 5860.96 | 386100.82 | 02-MAY-05:11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 31.31 | 31.31 | 744.83 | 181257.86 | 17-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.14 | 30.14 | 87.92 | 50520.90 | 05-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 26.58 | 26.58 | 363.07 | 145734.54 | 18-AUG-05:12 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 32.07 | 32.07 | 2169.47 | 296001.16 | 13-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.70 | 22.70 | 6395.04 | 324649.24 | 05-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28.08 | 28.08 | 19465.23 | 371622.52 | 15-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 33.05 | 33.05 | 41397.61 | 379701.93 | 06-DEC-06:11 |
Annual Sum or Average | 0.00 | 17180.68 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.70 | 22.70 | 87.92 | 50520.90 | ||
Maximum of Months | 0.00 | 0.00 | 35.70 | 60.00 | 61947.65 | 465972.30 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.91 | 57.91 | 1916.14 | 7053.94 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.29 | 57.29 | 1961.40 | 7091.40 | 17-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.28 | 57.28 | 2076.18 | 7078.79 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.35 | 57.35 | 1860.80 | 6886.44 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.99 | 57.99 | 1827.61 | 6581.43 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.63 | 57.63 | 1762.01 | 6179.82 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.77 | 57.77 | 1525.91 | 5809.89 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.86 | 57.86 | 1650.70 | 5604.86 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.87 | 57.87 | 1556.08 | 5739.52 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.90 | 56.90 | 1626.60 | 6081.08 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.67 | 57.67 | 1756.14 | 6470.00 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.52 | 57.52 | 1783.17 | 6811.89 | 29-DEC-12:12 |
Annual Sum or Average | 0.00 | 1774.15 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.90 | 56.90 | 1525.91 | 5604.86 | ||
Maximum of Months | 0.00 | 0.00 | 57.99 | 57.99 | 2076.18 | 7091.40 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.466925E+11 | 0.00 | 0.00 | 0.551699E+10 | 0.00 | 0.00 |
February | 0.257746E+11 | 0.00 | 0.00 | 0.431840E+10 | 0.00 | 0.00 |
March | 0.191962E+11 | 0.00 | 0.00 | 0.492036E+10 | 0.00 | 0.00 |
April | 0.931768E+10 | 0.00 | 0.00 | 0.515334E+10 | 0.00 | 0.00 |
May | 0.592663E+10 | 0.00 | 0.00 | 0.746976E+10 | 0.00 | 0.00 |
June | 0.924313E+09 | 0.00 | 0.00 | 0.145554E+11 | 0.00 | 0.00 |
July | 0.122902E+09 | 0.00 | 0.00 | 0.219679E+11 | 0.00 | 0.00 |
August | 0.407996E+09 | 0.00 | 0.00 | 0.204728E+11 | 0.00 | 0.00 |
September | 0.138351E+10 | 0.00 | 0.00 | 0.122280E+11 | 0.00 | 0.00 |
October | 0.354410E+10 | 0.00 | 0.00 | 0.658735E+10 | 0.00 | 0.00 |
November | 0.116406E+11 | 0.00 | 0.00 | 0.451823E+10 | 0.00 | 0.00 |
December | 0.282193E+11 | 0.00 | 0.00 | 0.458599E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.153150E+12 | 0.00 | 0.00 | 0.112294E+12 | 0.00 | 0.00 |
Minimum of Months | 0.122902E+09 | 0.00 | 0.00 | 0.431840E+10 | 0.00 | 0.00 |
Maximum of Months | 0.466925E+11 | 0.00 | 0.00 | 0.219679E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.472813E+11 | 0.00 | 0.00 | 0.486699E+10 | 0.00 | 0.00 |
February | 0.237019E+11 | 0.00 | 0.00 | 0.382875E+10 | 0.00 | 0.00 |
March | 0.146709E+11 | 0.00 | 0.00 | 0.422107E+10 | 0.00 | 0.00 |
April | 0.428215E+10 | 0.00 | 0.00 | 0.438724E+10 | 0.00 | 0.00 |
May | 0.282810E+10 | 0.00 | 0.00 | 0.647687E+10 | 0.00 | 0.00 |
June | 0.140984E+09 | 0.00 | 0.00 | 0.133844E+11 | 0.00 | 0.00 |
July | 1250657.14 | 0.00 | 0.00 | 0.198641E+11 | 0.00 | 0.00 |
August | 46738472.99 | 0.00 | 0.00 | 0.178717E+11 | 0.00 | 0.00 |
September | 0.855917E+09 | 0.00 | 0.00 | 0.100800E+11 | 0.00 | 0.00 |
October | 0.358098E+10 | 0.00 | 0.00 | 0.510334E+10 | 0.00 | 0.00 |
November | 0.129228E+11 | 0.00 | 0.00 | 0.382616E+10 | 0.00 | 0.00 |
December | 0.304098E+11 | 0.00 | 0.00 | 0.432624E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.140723E+12 | 0.00 | 0.00 | 0.982369E+11 | 0.00 | 0.00 |
Minimum of Months | 1250657.14 | 0.00 | 0.00 | 0.382616E+10 | 0.00 | 0.00 |
Maximum of Months | 0.472813E+11 | 0.00 | 0.00 | 0.198641E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.732621E+11 | 0.00 | 0.00 | 0.623861E+10 | 0.00 | 0.00 |
February | 0.390661E+11 | 0.00 | 0.00 | 0.470644E+10 | 0.00 | 0.00 |
March | 0.278074E+11 | 0.00 | 0.00 | 0.500888E+10 | 0.00 | 0.00 |
April | 0.105656E+11 | 0.00 | 0.00 | 0.484197E+10 | 0.00 | 0.00 |
May | 0.707541E+10 | 0.00 | 0.00 | 0.730375E+10 | 0.00 | 0.00 |
June | 0.885217E+09 | 0.00 | 0.00 | 0.145367E+11 | 0.00 | 0.00 |
July | 0.117819E+09 | 0.00 | 0.00 | 0.217405E+11 | 0.00 | 0.00 |
August | 0.520077E+09 | 0.00 | 0.00 | 0.188042E+11 | 0.00 | 0.00 |
September | 0.344318E+10 | 0.00 | 0.00 | 0.105846E+11 | 0.00 | 0.00 |
October | 0.101335E+11 | 0.00 | 0.00 | 0.541266E+10 | 0.00 | 0.00 |
November | 0.262945E+11 | 0.00 | 0.00 | 0.472780E+10 | 0.00 | 0.00 |
December | 0.531393E+11 | 0.00 | 0.00 | 0.575479E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.252310E+12 | 0.00 | 0.00 | 0.109661E+12 | 0.00 | 0.00 |
Minimum of Months | 0.117819E+09 | 0.00 | 0.00 | 0.470644E+10 | 0.00 | 0.00 |
Maximum of Months | 0.732621E+11 | 0.00 | 0.00 | 0.217405E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.551699E+10 | 0.00 | 0.466925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425908E+10 | 0.223454E+09 | 0.257746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.491856E+10 | 6325454.30 | 0.191962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453096E+10 | 0.242851E+10 | 0.931768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.524907E+10 | 0.893109E+10 | 0.592663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.713308E+10 | 0.304348E+11 | 0.924313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.863678E+10 | 0.532080E+11 | 0.122902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.901747E+10 | 0.460610E+11 | 0.407996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.668754E+10 | 0.225851E+11 | 0.138351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.530135E+10 | 0.523879E+10 | 0.354410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.443308E+10 | 0.308908E+09 | 0.116406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458599E+10 | 0.00 | 0.282193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.702699E+11 | 0.169426E+12 | 0.153150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.425908E+10 | 0.00 | 0.122902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.901747E+10 | 0.532080E+11 | 0.466925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.486699E+10 | 0.00 | 0.472813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376874E+10 | 0.223837E+09 | 0.237019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.421893E+10 | 7531202.98 | 0.146709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377155E+10 | 0.237975E+10 | 0.428215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.433993E+10 | 0.854702E+10 | 0.282810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617887E+10 | 0.293611E+11 | 0.140984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.743150E+10 | 0.492507E+11 | 1250657.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.743861E+10 | 0.416227E+11 | 46738472.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.518781E+10 | 0.197286E+11 | 0.855917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402217E+10 | 0.432026E+10 | 0.358098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.375752E+10 | 0.247631E+09 | 0.129228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432623E+10 | 60900.91 | 0.304098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.593088E+11 | 0.155689E+12 | 0.140723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375752E+10 | 0.00 | 1250657.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.743861E+10 | 0.492507E+11 | 0.472813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.623752E+10 | 3800884.94 | 0.732621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464246E+10 | 0.234801E+09 | 0.390661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.500659E+10 | 8008314.61 | 0.278074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.413519E+10 | 0.265678E+10 | 0.105656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.464185E+10 | 0.104091E+11 | 0.707541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.572331E+10 | 0.351534E+11 | 0.885217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.664345E+10 | 0.585319E+11 | 0.117819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.650416E+10 | 0.478083E+11 | 0.520077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482790E+10 | 0.225122E+11 | 0.344318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.422875E+10 | 0.456480E+10 | 0.101335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464420E+10 | 0.299608E+09 | 0.262945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.575366E+10 | 3948027.02 | 0.531393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629890E+11 | 0.182187E+12 | 0.252310E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.413519E+10 | 3800884.94 | 0.117819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.664345E+10 | 0.585319E+11 | 0.732621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.551699E+10 | 0.466925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425908E+10 | 0.257746E+11 | 0.00 | 0.00 | 59318073.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.491856E+10 | 0.191962E+11 | 0.00 | 0.00 | 1803691.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453096E+10 | 0.931768E+10 | 0.00 | 0.00 | 0.622386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.524907E+10 | 0.592663E+10 | 0.00 | 0.00 | 0.222069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.713308E+10 | 0.924313E+09 | 0.00 | 0.00 | 0.742234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.863678E+10 | 0.122902E+09 | 0.00 | 0.00 | 0.133311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.901747E+10 | 0.407996E+09 | 0.00 | 0.00 | 0.114553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.668754E+10 | 0.138351E+10 | 0.00 | 0.00 | 0.554042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.530135E+10 | 0.354410E+10 | 0.00 | 0.00 | 0.128600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.443308E+10 | 0.116406E+11 | 0.00 | 0.00 | 85152356.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458599E+10 | 0.282193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.702699E+11 | 0.153150E+12 | 0.00 | 0.00 | 0.420245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.425908E+10 | 0.122902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.901747E+10 | 0.466925E+11 | 0.00 | 0.00 | 0.133311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.486699E+10 | 0.472813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376874E+10 | 0.237019E+11 | 0.00 | 0.00 | 60017831.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.421893E+10 | 0.146709E+11 | 0.00 | 0.00 | 2146125.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.377155E+10 | 0.428215E+10 | 0.00 | 0.00 | 0.615685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.433993E+10 | 0.282810E+10 | 0.00 | 0.00 | 0.213694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.617887E+10 | 0.140984E+09 | 0.00 | 0.00 | 0.720555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.743150E+10 | 1250657.14 | 0.00 | 0.00 | 0.124326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.743861E+10 | 46738472.99 | 0.00 | 0.00 | 0.104331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.518781E+10 | 0.855917E+09 | 0.00 | 0.00 | 0.489216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402217E+10 | 0.358098E+10 | 0.00 | 0.00 | 0.108117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.375752E+10 | 0.129228E+11 | 0.00 | 0.00 | 68643886.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432623E+10 | 0.304098E+11 | 0.00 | 0.00 | 17436.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.593088E+11 | 0.140723E+12 | 0.00 | 0.00 | 0.389281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375752E+10 | 1250657.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.743861E+10 | 0.472813E+11 | 0.00 | 0.00 | 0.124326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.623752E+10 | 0.732621E+11 | 0.00 | 0.00 | 1088862.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464246E+10 | 0.390661E+11 | 0.00 | 0.00 | 63980873.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.500659E+10 | 0.278074E+11 | 0.00 | 0.00 | 2289910.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.413519E+10 | 0.105656E+11 | 0.00 | 0.00 | 0.706782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.464185E+10 | 0.707541E+10 | 0.00 | 0.00 | 0.266189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.572331E+10 | 0.885217E+09 | 0.00 | 0.00 | 0.881337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.664345E+10 | 0.117819E+09 | 0.00 | 0.00 | 0.150970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.650416E+10 | 0.520077E+09 | 0.00 | 0.00 | 0.123001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482790E+10 | 0.344318E+10 | 0.00 | 0.00 | 0.575674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.422875E+10 | 0.101335E+11 | 0.00 | 0.00 | 0.118391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464420E+10 | 0.262945E+11 | 0.00 | 0.00 | 83597734.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.575366E+10 | 0.531393E+11 | 0.00 | 0.00 | 1131653.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629890E+11 | 0.252310E+12 | 0.00 | 0.00 | 0.466719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.413519E+10 | 0.117819E+09 | 0.00 | 0.00 | 1088862.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.664345E+10 | 0.732621E+11 | 0.00 | 0.00 | 0.150970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153040E+11 | 0.00 | 0.00 | 1075482.24 | 0.00 | 0.138570E+09 | 0.190513E+10 | 0.00 | 0.28 |
February | 0.997668E+10 | 0.00 | 0.00 | 6953145.19 | 0.00 | 10050227.68 | 0.472187E+10 | 0.00 | 0.34 |
March | 0.715445E+10 | 0.00 | 0.00 | 19355630.84 | 0.00 | 4514819.61 | 0.104821E+11 | 0.00 | 0.42 |
April | 0.302192E+10 | 0.00 | 0.00 | 27277229.48 | 0.00 | 0.00 | 0.138315E+11 | 0.00 | 0.61 |
May | 0.215322E+10 | 18241874.20 | 0.00 | 34101998.90 | 3386156.80 | 0.00 | 0.154229E+11 | 0.00 | 0.78 |
June | 0.654743E+09 | 0.198256E+09 | 0.00 | 41997828.13 | 363815.66 | 0.00 | 0.151161E+11 | 0.00 | 1.05 |
July | 0.495477E+09 | 0.375925E+09 | 0.00 | 37933598.73 | 15365386.93 | 0.00 | 0.831203E+10 | 0.00 | 0.83 |
August | 0.601534E+09 | 0.214915E+09 | 0.00 | 46586988.55 | 17156781.38 | 0.00 | 0.132340E+11 | 0.00 | 1.03 |
September | 0.802376E+09 | 0.245292E+09 | 0.00 | 43484385.87 | 13567457.70 | 0.00 | 0.169779E+11 | 0.00 | 0.99 |
October | 0.146509E+10 | 0.00 | 0.00 | 40795451.18 | 0.00 | 0.00 | 0.182318E+11 | 0.00 | 0.78 |
November | 0.432626E+10 | 0.00 | 0.00 | 24810867.39 | 0.00 | 0.00 | 0.124118E+11 | 0.00 | 0.50 |
December | 0.102176E+11 | 0.00 | 0.00 | 8330499.49 | 0.00 | 3725738.42 | 0.569643E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.561734E+11 | 0.105263E+10 | 0.00 | 0.332703E+09 | 49839598.46 | 0.156860E+09 | 0.136344E+12 | 0.00 | 0.66 |
Minimum of Months | 0.495477E+09 | 0.00 | 0.00 | 1075482.24 | 0.00 | 0.00 | 0.190513E+10 | 0.00 | 0.28 |
Maximum of Months | 0.153040E+11 | 0.375925E+09 | 0.00 | 46586988.55 | 17156781.38 | 0.138570E+09 | 0.182318E+11 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253522E+10 | 0.00 | 0.00 | 0.24 |
February | 0.111181E+11 | 0.00 | 0.00 | 172340.57 | 0.00 | 0.725560E+09 | 0.229030E+09 | 0.00 | 0.28 |
March | 0.113566E+11 | 0.00 | 0.00 | 1045265.95 | 0.00 | 0.196960E+09 | 0.141072E+10 | 0.00 | 0.31 |
April | 0.754751E+10 | 0.00 | 0.00 | 5451400.73 | 0.00 | 1563248.73 | 0.392149E+10 | 0.00 | 0.42 |
May | 0.590500E+10 | 1241030.01 | 0.00 | 11150491.23 | 21597466.14 | 42678385.60 | 0.575319E+10 | 0.00 | 0.53 |
June | 0.202116E+10 | 0.148009E+09 | 0.00 | 23653452.85 | 24285291.62 | 0.00 | 0.865006E+10 | 0.00 | 0.74 |
July | 0.109318E+10 | 0.280670E+09 | 0.00 | 22451196.39 | 15981149.87 | 0.00 | 0.471794E+10 | 0.00 | 0.58 |
August | 0.140677E+10 | 0.157332E+09 | 0.00 | 27013178.48 | 18003189.94 | 0.00 | 0.744547E+10 | 0.00 | 0.70 |
September | 0.343349E+10 | 0.195849E+09 | 0.00 | 17643753.65 | 17678834.55 | 0.00 | 0.723889E+10 | 0.00 | 0.63 |
October | 0.664685E+10 | 0.00 | 0.00 | 9512758.47 | 1051413.33 | 17693653.55 | 0.496210E+10 | 0.00 | 0.48 |
November | 0.953749E+10 | 0.00 | 0.00 | 1858173.52 | 0.00 | 0.164295E+09 | 0.164752E+10 | 0.00 | 0.34 |
December | 0.121937E+11 | 0.00 | 0.00 | 51855.44 | 0.00 | 0.956963E+09 | 0.143771E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.848899E+11 | 0.783101E+09 | 0.00 | 0.120004E+09 | 98597345.44 | 0.464093E+10 | 0.461202E+11 | 0.00 | 0.46 |
Minimum of Months | 0.109318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.126300E+11 | 0.280670E+09 | 0.00 | 27013178.48 | 24285291.62 | 0.253522E+10 | 0.865006E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.689524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661778E+10 | 0.00 | 0.00 | 0.23 |
February | 0.866516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294819E+10 | 0.00 | 0.00 | 0.29 |
March | 0.118901E+11 | 0.00 | 0.00 | 4361.22 | 0.00 | 0.158819E+10 | 86980204.84 | 0.00 | 0.35 |
April | 0.109771E+11 | 0.00 | 0.00 | 1659369.59 | 0.00 | 0.315326E+09 | 0.151266E+10 | 0.00 | 0.49 |
May | 0.971055E+10 | 1661704.78 | 0.00 | 6001564.11 | 4669077.84 | 0.184508E+09 | 0.358924E+10 | 0.00 | 0.62 |
June | 0.413164E+10 | 0.114066E+09 | 0.00 | 20017226.91 | 8816774.67 | 1011602.33 | 0.685065E+10 | 0.00 | 0.78 |
July | 0.223168E+10 | 0.251968E+09 | 0.00 | 19531600.15 | 14599504.70 | 0.00 | 0.337119E+10 | 0.00 | 0.61 |
August | 0.328503E+10 | 96895076.30 | 0.00 | 22075694.78 | 26019654.56 | 1160666.54 | 0.509784E+10 | 0.00 | 0.71 |
September | 0.677529E+10 | 0.162720E+09 | 0.00 | 8690330.45 | 33430301.29 | 18912904.44 | 0.349790E+10 | 0.00 | 0.66 |
October | 0.108321E+11 | 0.00 | 0.00 | 1164633.45 | 16931.35 | 0.265332E+09 | 0.833596E+09 | 0.00 | 0.53 |
November | 0.974385E+10 | 0.00 | 0.00 | 194.97 | 0.00 | 0.146233E+10 | 7583022.74 | 0.00 | 0.38 |
December | 0.774577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436698E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.928836E+11 | 0.627311E+09 | 0.00 | 79144975.63 | 87552244.41 | 0.177697E+11 | 0.248476E+11 | 0.00 | 0.49 |
Minimum of Months | 0.223168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.118901E+11 | 0.251968E+09 | 0.00 | 22075694.78 | 33430301.29 | 0.661778E+10 | 0.685065E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619414E+10 | 0.00 | 0.00 | 0.51 |
February | 0.124141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407051E+10 | 0.00 | 0.00 | 0.63 |
March | 0.322016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294483E+10 | 0.00 | 0.00 | 0.75 |
April | 0.448054E+10 | 0.00 | 0.00 | 15372.02 | 0.00 | 0.125669E+10 | 52607940.19 | 0.00 | 1.05 |
May | 0.491285E+10 | 1679399.28 | 0.00 | 565614.80 | 1193706.55 | 0.663014E+09 | 0.408340E+09 | 0.00 | 1.28 |
June | 0.332874E+10 | 37401754.78 | 0.00 | 3259592.89 | 10304305.72 | 41774061.51 | 0.116318E+10 | 0.00 | 1.49 |
July | 0.158832E+10 | 69142259.44 | 0.00 | 4018708.72 | 35454118.95 | 1389892.82 | 0.666176E+09 | 0.00 | 1.14 |
August | 0.262237E+10 | 34630828.97 | 0.00 | 3588825.26 | 16061256.35 | 24700114.86 | 0.769001E+09 | 0.00 | 1.34 |
September | 0.383892E+10 | 38819271.62 | 0.00 | 687611.92 | 37806461.64 | 0.359731E+09 | 0.295926E+09 | 0.00 | 1.33 |
October | 0.419479E+10 | 0.00 | 0.00 | 12.53 | 7683.97 | 0.121882E+10 | 554305.38 | 0.00 | 1.14 |
November | 0.214665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294619E+10 | 0.00 | 0.00 | 0.81 |
December | 0.733495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481391E+10 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.325130E+11 | 0.181674E+09 | 0.00 | 12135738.15 | 0.100828E+09 | 0.245357E+11 | 0.335579E+10 | 0.00 | 1.00 |
Minimum of Months | 0.204693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1389892.82 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.491285E+10 | 69142259.44 | 0.00 | 4018708.72 | 37806461.64 | 0.619414E+10 | 0.116318E+10 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.348655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380150E+10 | 0.00 | 0.00 | 0.53 |
February | 0.122562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224230E+10 | 0.00 | 0.00 | 0.65 |
March | 0.242925E+10 | 0.00 | 0.00 | 80188.04 | 0.00 | 0.149780E+10 | 96991483.09 | 0.00 | 0.77 |
April | 0.251762E+10 | 0.00 | 0.00 | 955166.99 | 0.00 | 0.550991E+09 | 0.770487E+09 | 0.00 | 1.11 |
May | 0.239679E+10 | 1157366.02 | 0.00 | 2161483.48 | 720625.12 | 0.319035E+09 | 0.132964E+10 | 0.00 | 1.39 |
June | 0.130851E+10 | 29613149.11 | 0.00 | 6244823.20 | 4855612.82 | 16417397.64 | 0.198481E+10 | 0.00 | 1.83 |
July | 0.625485E+09 | 65323944.66 | 0.00 | 7294486.18 | 17277938.22 | 542099.78 | 0.125172E+10 | 0.00 | 1.57 |
August | 0.108282E+10 | 37029053.87 | 0.00 | 6718617.39 | 4881264.34 | 7417770.29 | 0.154373E+10 | 0.00 | 1.71 |
September | 0.195379E+10 | 37816478.42 | 0.00 | 2142081.66 | 16734867.74 | 0.171013E+09 | 0.886021E+09 | 0.00 | 1.44 |
October | 0.283311E+10 | 0.00 | 0.00 | 223482.93 | 5022.59 | 0.575019E+09 | 0.132147E+09 | 0.00 | 1.18 |
November | 0.173716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159106E+10 | 0.00 | 0.00 | 0.83 |
December | 0.701113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292002E+10 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.191599E+11 | 0.170940E+09 | 0.00 | 25820329.88 | 44475330.83 | 0.136931E+11 | 0.799554E+10 | 0.00 | 1.13 |
Minimum of Months | 0.348655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 542099.78 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.283311E+10 | 65323944.66 | 0.00 | 7294486.18 | 17277938.22 | 0.380150E+10 | 0.198481E+10 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159826E+10 | 0.00 | 0.00 | 72130.71 | 0.00 | 0.464633E+10 | 0.111455E+09 | 0.00 | 0.51 |
February | 0.212208E+10 | 0.00 | 0.00 | 1747279.92 | 0.00 | 0.263776E+10 | 0.758731E+09 | 0.00 | 0.68 |
March | 0.289658E+10 | 0.00 | 0.00 | 3402579.98 | 0.00 | 0.200957E+10 | 0.168337E+10 | 0.00 | 0.81 |
April | 0.352480E+10 | 0.00 | 0.00 | 2922736.78 | 0.00 | 0.959320E+09 | 0.168549E+10 | 0.00 | 1.15 |
May | 0.371631E+10 | 1871830.68 | 0.00 | 3766953.87 | 1116128.60 | 0.617970E+09 | 0.194994E+10 | 0.00 | 1.37 |
June | 0.279400E+10 | 47367146.80 | 0.00 | 6291018.70 | 8333174.81 | 66616077.77 | 0.191571E+10 | 0.00 | 1.60 |
July | 0.139443E+10 | 96767132.32 | 0.00 | 7569722.78 | 27629903.85 | 4586273.53 | 0.108262E+10 | 0.00 | 1.27 |
August | 0.205108E+10 | 63767309.05 | 0.00 | 9965915.48 | 10910085.06 | 26651192.43 | 0.182055E+10 | 0.00 | 1.60 |
September | 0.276798E+10 | 94932723.34 | 0.00 | 6230130.20 | 18685134.48 | 0.287444E+09 | 0.211095E+10 | 0.00 | 1.61 |
October | 0.304621E+10 | 0.00 | 0.00 | 5424384.61 | 7779.16 | 0.726035E+09 | 0.213635E+10 | 0.00 | 1.30 |
November | 0.241395E+10 | 0.00 | 0.00 | 2641271.13 | 0.00 | 0.182732E+10 | 0.109955E+10 | 0.00 | 0.85 |
December | 0.179299E+10 | 0.00 | 0.00 | 312367.62 | 0.00 | 0.345338E+10 | 0.353253E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.301187E+11 | 0.304706E+09 | 0.00 | 50346491.79 | 66682205.97 | 0.172630E+11 | 0.167080E+11 | 0.00 | 1.11 |
Minimum of Months | 0.139443E+10 | 0.00 | 0.00 | 72130.71 | 0.00 | 4586273.53 | 0.111455E+09 | 0.00 | 0.51 |
Maximum of Months | 0.371631E+10 | 96767132.32 | 0.00 | 9965915.48 | 27629903.85 | 0.464633E+10 | 0.213635E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.389346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398695E+10 | 0.00 | 0.00 | 0.56 |
February | 0.111580E+10 | 0.00 | 0.00 | 67106.60 | 0.00 | 0.246294E+10 | 72783893.89 | 0.00 | 0.69 |
March | 0.214495E+10 | 0.00 | 0.00 | 393931.73 | 0.00 | 0.181893E+10 | 0.297171E+09 | 0.00 | 0.82 |
April | 0.269533E+10 | 0.00 | 0.00 | 1152497.21 | 0.00 | 0.718930E+09 | 0.732257E+09 | 0.00 | 1.22 |
May | 0.267153E+10 | 1219451.07 | 0.00 | 2522753.45 | 759281.90 | 0.402452E+09 | 0.127262E+10 | 0.00 | 1.50 |
June | 0.190159E+10 | 37411003.41 | 0.00 | 4756614.14 | 2944503.27 | 42751115.06 | 0.139334E+10 | 0.00 | 1.77 |
July | 0.102794E+10 | 70134960.13 | 0.00 | 4674685.24 | 19510730.25 | 3119958.09 | 0.680724E+09 | 0.00 | 1.39 |
August | 0.160731E+10 | 34156494.99 | 0.00 | 5026707.40 | 8852627.39 | 20444647.78 | 0.876995E+09 | 0.00 | 1.60 |
September | 0.231080E+10 | 56165725.91 | 0.00 | 1857539.77 | 12447856.00 | 0.237497E+09 | 0.671728E+09 | 0.00 | 1.54 |
October | 0.264965E+10 | 0.00 | 0.00 | 585402.18 | 5292.02 | 0.733758E+09 | 0.373670E+09 | 0.00 | 1.26 |
November | 0.175415E+10 | 0.00 | 0.00 | 18930.59 | 0.00 | 0.170380E+10 | 47875645.75 | 0.00 | 0.88 |
December | 0.740561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307474E+10 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.210089E+11 | 0.199088E+09 | 0.00 | 21056168.33 | 44520290.83 | 0.152063E+11 | 0.641916E+10 | 0.00 | 1.15 |
Minimum of Months | 0.389346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3119958.09 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.269533E+10 | 70134960.13 | 0.00 | 5026707.40 | 19510730.25 | 0.398695E+10 | 0.139334E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674220E+10 | 0.00 | 0.00 | 0.51 |
February | 0.834151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460964E+10 | 0.00 | 0.00 | 0.58 |
March | 0.218995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390537E+10 | 0.00 | 0.00 | 0.67 |
April | 0.333263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195468E+10 | 0.00 | 0.00 | 0.88 |
May | 0.422515E+10 | 0.00 | 0.00 | 24178.43 | 7405347.93 | 0.807297E+09 | 28285994.54 | 0.00 | 1.02 |
June | 0.349629E+10 | 29248302.01 | 0.00 | 699195.37 | 14113881.41 | 18040832.43 | 0.210571E+09 | 0.00 | 1.14 |
July | 0.163589E+10 | 74756382.48 | 0.00 | 1761686.07 | 16558122.07 | 0.00 | 0.360765E+09 | 0.00 | 0.87 |
August | 0.266960E+10 | 43167279.47 | 0.00 | 1417552.20 | 12029417.58 | 815379.27 | 0.419381E+09 | 0.00 | 1.05 |
September | 0.405192E+10 | 38369320.21 | 0.00 | 547332.05 | 16785520.32 | 59078307.11 | 0.240482E+09 | 0.00 | 1.10 |
October | 0.506660E+10 | 0.00 | 0.00 | 1189.72 | 0.00 | 0.411544E+09 | 10170794.43 | 0.00 | 0.99 |
November | 0.325828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210481E+10 | 0.00 | 0.00 | 0.73 |
December | 0.933513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492732E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.318586E+11 | 0.185541E+09 | 0.00 | 4451133.85 | 66892289.31 | 0.255408E+11 | 0.126966E+10 | 0.00 | 0.84 |
Minimum of Months | 0.164658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.506660E+10 | 74756382.48 | 0.00 | 1761686.07 | 16785520.32 | 0.674220E+10 | 0.419381E+09 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.303422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420661E+10 | 0.00 | 0.00 | 0.53 |
February | 0.104670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252678E+10 | 0.00 | 0.00 | 0.61 |
March | 0.204804E+10 | 0.00 | 0.00 | 5897.23 | 0.00 | 0.191277E+10 | 37261453.90 | 0.00 | 0.70 |
April | 0.247816E+10 | 0.00 | 0.00 | 231861.38 | 0.00 | 0.725967E+09 | 0.278138E+09 | 0.00 | 0.92 |
May | 0.245969E+10 | 1542221.80 | 0.00 | 863133.22 | 3330087.13 | 0.325654E+09 | 0.581838E+09 | 0.00 | 1.09 |
June | 0.125644E+10 | 36324742.44 | 0.00 | 4048009.78 | 912338.98 | 7743116.04 | 0.143575E+10 | 0.00 | 1.40 |
July | 0.531195E+09 | 76136963.22 | 0.00 | 5895075.52 | 3756929.87 | 0.00 | 0.119831E+10 | 0.00 | 1.28 |
August | 0.948485E+09 | 46994787.06 | 0.00 | 5781315.61 | 4182326.87 | 0.00 | 0.154452E+10 | 0.00 | 1.43 |
September | 0.195067E+10 | 36817495.30 | 0.00 | 2466648.68 | 3854591.76 | 8230260.06 | 0.103525E+10 | 0.00 | 1.23 |
October | 0.309799E+10 | 0.00 | 0.00 | 519193.78 | 0.00 | 0.141516E+09 | 0.380664E+09 | 0.00 | 1.03 |
November | 0.241329E+10 | 0.00 | 0.00 | 435.39 | 0.00 | 0.111010E+10 | 3288058.30 | 0.00 | 0.76 |
December | 0.100018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285372E+10 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.195343E+11 | 0.197816E+09 | 0.00 | 19811570.60 | 16036274.60 | 0.138191E+11 | 0.649502E+10 | 0.00 | 0.96 |
Minimum of Months | 0.303422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.309799E+10 | 76136963.22 | 0.00 | 5895075.52 | 4182326.87 | 0.420661E+10 | 0.154452E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.925053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706272E+10 | 0.00 | 0.00 | 0.58 |
February | 0.152000E+10 | 0.00 | 0.00 | 608552.28 | 0.00 | 0.436870E+10 | 0.293636E+09 | 0.00 | 0.66 |
March | 0.237561E+10 | 0.00 | 0.00 | 305757.62 | 0.00 | 0.393286E+10 | 0.327313E+09 | 0.00 | 0.73 |
April | 0.288205E+10 | 0.00 | 0.00 | 403070.28 | 0.00 | 0.260651E+10 | 0.207576E+09 | 0.00 | 0.94 |
May | 0.320790E+10 | 2838274.23 | 0.00 | 803926.30 | 4687685.86 | 0.188372E+10 | 0.308044E+09 | 0.00 | 1.08 |
June | 0.284586E+10 | 56656976.73 | 0.00 | 2349150.23 | 4476139.00 | 0.437150E+09 | 0.574010E+09 | 0.00 | 1.20 |
July | 0.141200E+10 | 0.138615E+09 | 0.00 | 4648007.95 | 5802560.79 | 90955802.30 | 0.589694E+09 | 0.00 | 0.98 |
August | 0.187061E+10 | 96401425.78 | 0.00 | 6773801.86 | 6555431.63 | 0.264690E+09 | 0.121292E+10 | 0.00 | 1.26 |
September | 0.263403E+10 | 0.101040E+09 | 0.00 | 5156847.04 | 3732563.44 | 0.507759E+09 | 0.172124E+10 | 0.00 | 1.33 |
October | 0.349520E+10 | 0.00 | 0.00 | 4255841.82 | 0.00 | 0.925390E+09 | 0.167801E+10 | 0.00 | 1.15 |
November | 0.292147E+10 | 0.00 | 0.00 | 1045918.13 | 0.00 | 0.228501E+10 | 0.635119E+09 | 0.00 | 0.79 |
December | 0.162869E+10 | 0.00 | 0.00 | 16361.61 | 0.00 | 0.506269E+10 | 47654014.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.277185E+11 | 0.395552E+09 | 0.00 | 26367235.11 | 25254380.71 | 0.294282E+11 | 0.759521E+10 | 0.00 | 0.94 |
Minimum of Months | 0.925053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90955802.30 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.349520E+10 | 0.138615E+09 | 0.00 | 6773801.86 | 6555431.63 | 0.706272E+10 | 0.172124E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436532E+10 | 0.00 | 0.00 | 0.54 |
February | 0.999391E+09 | 0.00 | 0.00 | 21933.33 | 0.00 | 0.264674E+10 | 38723415.30 | 0.00 | 0.63 |
March | 0.186947E+10 | 0.00 | 0.00 | 46690.57 | 0.00 | 0.217693E+10 | 90100463.65 | 0.00 | 0.72 |
April | 0.251339E+10 | 0.00 | 0.00 | 318800.83 | 0.00 | 0.894154E+09 | 0.203519E+09 | 0.00 | 0.96 |
May | 0.264009E+10 | 1707565.48 | 0.00 | 997385.83 | 3322602.57 | 0.363662E+09 | 0.464758E+09 | 0.00 | 1.13 |
June | 0.180312E+10 | 40008140.34 | 0.00 | 2467149.03 | 569307.12 | 11556740.12 | 0.772855E+09 | 0.00 | 1.30 |
July | 0.855822E+09 | 94866419.65 | 0.00 | 3193435.82 | 2269502.04 | 0.00 | 0.591286E+09 | 0.00 | 1.06 |
August | 0.139087E+10 | 51626247.67 | 0.00 | 3444422.59 | 2842283.12 | 1374729.54 | 0.794774E+09 | 0.00 | 1.24 |
September | 0.234330E+10 | 53273293.97 | 0.00 | 1761946.91 | 1870196.61 | 19883963.37 | 0.682703E+09 | 0.00 | 1.26 |
October | 0.321574E+10 | 0.00 | 0.00 | 588219.93 | 0.00 | 0.171841E+09 | 0.369061E+09 | 0.00 | 1.08 |
November | 0.235771E+10 | 0.00 | 0.00 | 38774.43 | 0.00 | 0.120230E+10 | 80468532.73 | 0.00 | 0.78 |
December | 0.909967E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306789E+10 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.211925E+11 | 0.241482E+09 | 0.00 | 12878759.26 | 10873891.46 | 0.149216E+11 | 0.408825E+10 | 0.00 | 0.94 |
Minimum of Months | 0.293629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.321574E+10 | 94866419.65 | 0.00 | 3444422.59 | 3322602.57 | 0.436532E+10 | 0.794774E+09 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.377586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673656E+10 | 0.00 | 0.00 | 0.53 |
February | 0.147022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400192E+10 | 0.00 | 0.00 | 0.59 |
March | 0.339827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245152E+10 | 0.00 | 0.00 | 0.65 |
April | 0.437727E+10 | 0.00 | 0.00 | 51396.08 | 0.00 | 0.624453E+09 | 48697315.26 | 0.00 | 0.87 |
May | 0.419331E+10 | 3846522.88 | 0.00 | 781490.97 | 6425748.03 | 0.333888E+09 | 0.402064E+09 | 0.00 | 1.03 |
June | 0.229409E+10 | 53313239.36 | 0.00 | 3756004.49 | 10923008.81 | 3543745.34 | 0.146127E+10 | 0.00 | 1.21 |
July | 0.116342E+10 | 0.106585E+09 | 0.00 | 4220636.62 | 8079097.78 | 0.00 | 0.843342E+09 | 0.00 | 0.95 |
August | 0.203030E+10 | 60720620.77 | 0.00 | 3863891.90 | 8247380.22 | 695160.18 | 0.986067E+09 | 0.00 | 1.09 |
September | 0.345555E+10 | 58233424.67 | 0.00 | 1244087.06 | 15722012.93 | 71927261.21 | 0.540331E+09 | 0.00 | 1.09 |
October | 0.448650E+10 | 0.00 | 0.00 | 50212.95 | 472903.40 | 0.513348E+09 | 28324182.15 | 0.00 | 0.95 |
November | 0.299378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211268E+10 | 0.00 | 0.00 | 0.71 |
December | 0.113583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490379E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.313761E+11 | 0.282699E+09 | 0.00 | 13967720.07 | 49870151.17 | 0.217543E+11 | 0.431010E+10 | 0.00 | 0.85 |
Minimum of Months | 0.377586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.448650E+10 | 0.106585E+09 | 0.00 | 4220636.62 | 15722012.93 | 0.673656E+10 | 0.146127E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.481075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409882E+10 | 0.00 | 0.00 | 0.53 |
February | 0.110102E+10 | 0.00 | 0.00 | 49634.49 | 0.00 | 0.232903E+10 | 32907554.69 | 0.00 | 0.58 |
March | 0.214649E+10 | 0.00 | 0.00 | 373025.27 | 0.00 | 0.137600E+10 | 0.186689E+09 | 0.00 | 0.65 |
April | 0.220244E+10 | 0.00 | 0.00 | 1565396.15 | 0.00 | 0.314040E+09 | 0.905990E+09 | 0.00 | 0.94 |
May | 0.197335E+10 | 5754113.38 | 0.00 | 2876065.57 | 1345811.69 | 0.185050E+09 | 0.139053E+10 | 0.00 | 1.21 |
June | 0.114956E+10 | 44625946.04 | 0.00 | 6229780.47 | 6557232.17 | 2767419.17 | 0.205807E+10 | 0.00 | 1.72 |
July | 0.575978E+09 | 83142115.80 | 0.00 | 7325512.05 | 6623927.87 | 0.00 | 0.144442E+10 | 0.00 | 1.53 |
August | 0.106309E+10 | 53298962.61 | 0.00 | 6560251.43 | 6125397.97 | 630652.09 | 0.171228E+10 | 0.00 | 1.64 |
September | 0.184650E+10 | 47321750.06 | 0.00 | 2890701.22 | 9050233.85 | 38353478.48 | 0.110212E+10 | 0.00 | 1.30 |
October | 0.252596E+10 | 0.00 | 0.00 | 911612.79 | 363859.18 | 0.283304E+09 | 0.435414E+09 | 0.00 | 0.98 |
November | 0.188468E+10 | 0.00 | 0.00 | 51569.27 | 0.00 | 0.128949E+10 | 22537271.39 | 0.00 | 0.69 |
December | 0.852104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300115E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.178023E+11 | 0.234143E+09 | 0.00 | 28833548.73 | 30066462.73 | 0.129186E+11 | 0.929096E+10 | 0.00 | 1.03 |
Minimum of Months | 0.481075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.252596E+10 | 83142115.80 | 0.00 | 7325512.05 | 9050233.85 | 0.409882E+10 | 0.205807E+10 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189909E+10 | 0.00 | 0.00 | 355090.92 | 0.00 | 0.492385E+10 | 0.304602E+09 | 0.00 | 0.53 |
February | 0.214102E+10 | 0.00 | 0.00 | 2617058.00 | 0.00 | 0.263396E+10 | 0.112360E+10 | 0.00 | 0.68 |
March | 0.303932E+10 | 0.00 | 0.00 | 4500988.46 | 0.00 | 0.166412E+10 | 0.191838E+10 | 0.00 | 0.77 |
April | 0.326840E+10 | 0.00 | 0.00 | 3738168.85 | 0.00 | 0.514507E+09 | 0.182615E+10 | 0.00 | 1.01 |
May | 0.310349E+10 | 11603209.63 | 0.00 | 4421681.28 | 1626711.80 | 0.362919E+09 | 0.189786E+10 | 0.00 | 1.17 |
June | 0.214443E+10 | 75404627.14 | 0.00 | 6350303.66 | 8295276.73 | 8524480.27 | 0.198485E+10 | 0.00 | 1.39 |
July | 0.114207E+10 | 0.150068E+09 | 0.00 | 6903928.66 | 7384140.03 | 0.00 | 0.113367E+10 | 0.00 | 1.13 |
August | 0.169632E+10 | 0.115385E+09 | 0.00 | 9310163.28 | 8371990.54 | 1764809.78 | 0.190129E+10 | 0.00 | 1.46 |
September | 0.249533E+10 | 0.136870E+09 | 0.00 | 7600968.67 | 7088043.35 | 49954694.65 | 0.245148E+10 | 0.00 | 1.50 |
October | 0.310891E+10 | 593466.73 | 0.00 | 7792744.55 | 90514.87 | 0.251899E+09 | 0.274107E+10 | 0.00 | 1.26 |
November | 0.264051E+10 | 0.00 | 0.00 | 4343196.36 | 0.00 | 0.146073E+10 | 0.166962E+10 | 0.00 | 0.81 |
December | 0.205486E+10 | 0.00 | 0.00 | 1245829.66 | 0.00 | 0.351521E+10 | 0.635465E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.287337E+11 | 0.489925E+09 | 0.00 | 59180122.34 | 32856677.33 | 0.153874E+11 | 0.195880E+11 | 0.00 | 1.02 |
Minimum of Months | 0.114207E+10 | 0.00 | 0.00 | 355090.92 | 0.00 | 0.00 | 0.304602E+09 | 0.00 | 0.53 |
Maximum of Months | 0.326840E+10 | 0.150068E+09 | 0.00 | 9310163.28 | 8371990.54 | 0.492385E+10 | 0.274107E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.597063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512027E+10 | 0.00 | 0.00 | 0.67 |
February | 0.145962E+10 | 0.00 | 0.00 | 136758.31 | 0.00 | 0.290119E+10 | 0.109179E+09 | 0.00 | 0.77 |
March | 0.271870E+10 | 0.00 | 0.00 | 499464.59 | 0.00 | 0.178217E+10 | 0.325299E+09 | 0.00 | 0.86 |
April | 0.315059E+10 | 0.00 | 0.00 | 1170718.91 | 0.00 | 0.481503E+09 | 0.660549E+09 | 0.00 | 1.20 |
May | 0.281321E+10 | 3168036.05 | 0.00 | 2521457.85 | 5254502.20 | 0.285117E+09 | 0.115172E+10 | 0.00 | 1.44 |
June | 0.189411E+10 | 55425936.39 | 0.00 | 4184197.12 | 7512134.08 | 7745550.91 | 0.136007E+10 | 0.00 | 1.71 |
July | 0.104354E+10 | 0.117032E+09 | 0.00 | 3938040.65 | 5332295.00 | 0.00 | 0.718325E+09 | 0.00 | 1.35 |
August | 0.165000E+10 | 65970705.94 | 0.00 | 4239687.79 | 5370837.31 | 2670032.10 | 0.929774E+09 | 0.00 | 1.54 |
September | 0.265569E+10 | 76903890.29 | 0.00 | 2046295.65 | 5185497.66 | 61519475.30 | 0.744563E+09 | 0.00 | 1.51 |
October | 0.329814E+10 | 0.00 | 0.00 | 829565.37 | 387747.46 | 0.382229E+09 | 0.486961E+09 | 0.00 | 1.26 |
November | 0.242881E+10 | 0.00 | 0.00 | 81896.82 | 0.00 | 0.162492E+10 | 0.128850E+09 | 0.00 | 0.92 |
December | 0.116746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375999E+10 | 0.00 | 0.00 | 0.70 |
Annual Sum or Average | 0.248769E+11 | 0.318501E+09 | 0.00 | 19648083.06 | 29043013.73 | 0.164093E+11 | 0.661529E+10 | 0.00 | 1.16 |
Minimum of Months | 0.597063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.329814E+10 | 0.117032E+09 | 0.00 | 4239687.79 | 7512134.08 | 0.512027E+10 | 0.136007E+10 | 0.00 | 1.71 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.167641E+12 | 0.290557E+11 | 0.00 | 0.165330E+12 | 0.780666E+11 |
February | 0.213990E+12 | 0.220907E+11 | 0.00 | 0.168253E+12 | 0.478210E+11 |
March | 0.339007E+12 | 0.208046E+11 | 0.00 | 0.204350E+12 | 0.363629E+11 |
April | 0.352883E+12 | 0.141189E+11 | 0.00 | 0.240431E+12 | 0.256265E+11 |
May | 0.459410E+12 | 0.137240E+11 | 0.00 | 0.257524E+12 | 0.451539E+11 |
June | 0.493979E+12 | 0.663397E+10 | 0.00 | 0.237302E+12 | 0.119813E+12 |
July | 0.490109E+12 | 0.370556E+10 | 0.00 | 0.205021E+12 | 0.202029E+12 |
August | 0.412528E+12 | 0.489014E+10 | 0.00 | 0.235471E+12 | 0.170402E+12 |
September | 0.318568E+12 | 0.894470E+10 | 0.00 | 0.237410E+12 | 0.849813E+11 |
October | 0.218353E+12 | 0.136416E+11 | 0.00 | 0.259150E+12 | 0.292962E+11 |
November | 0.130716E+12 | 0.194792E+11 | 0.00 | 0.204954E+12 | 0.310927E+11 |
December | 0.112864E+12 | 0.250939E+11 | 0.00 | 0.171438E+12 | 0.578461E+11 |
Annual Sum or Average | 0.371005E+13 | 0.182183E+12 | 0.00 | 0.258663E+13 | 0.928492E+12 |
Minimum of Months | 0.112864E+12 | 0.370556E+10 | 0.00 | 0.165330E+12 | 0.256265E+11 |